Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44

Tabular Output Report in Format: HTML

Building: MF+CZ5BWH+USA_ID_Boise.Air.Terminal.726810+elecres+heatedbsmt+IECC_2012

Environment: ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810

Simulation Timestamp: 2019-02-14 08:44:31


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 786632.61 20.17 26.75
Net Site Energy 786632.61 20.17 26.75
Total Source Energy 2491265.49 63.87 84.72
Net Source Energy 2491265.49 63.87 84.72


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 198092.83 0.00 0.00 0.00 0.00 0.00
Cooling 42302.14 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 21950.32 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 171443.98 0.00 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 786632.61 0.00 0.00 0.00 0.00 377715.79
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 198092.83 0.00 0.00 0.00 0.00 0.00
Cooling General 42302.14 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 21950.32 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 171443.98 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.80 0.00 0.00 0.00 0.00 0.00
HVAC 14.75 0.00 0.00 0.00 0.00 12.85
Other 10.20 0.00 0.00 0.00 0.00 0.00
Total 26.75 0.00 0.00 0.00 0.00 12.85


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 11.12 0.00 0.00 0.00 0.00 9.68
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 20.17 0.00 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 786632.615 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 786632.615 100.00
     
Total On-Site and Utility Electric Sources 786632.615 100.00
Total Electricity End Uses 786632.615 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 30.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 154.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44
RunPeriod ANNUAL
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Latitude [deg] 43.62
Longitude [deg] -116.2
Elevation [ft] 2299.98
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.4894 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 13-JAN-08:30 - - - - 07-JAN-08:30
Heating 154.79 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2.72 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.71 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.55 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 130.45 0.00 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 329.32 0.00 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 154.79 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 2.72 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 1.48 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.57 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.91 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.31 0.00 0.00 0.00 0.00 0.00
  electric_range 3.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 16.45 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.09 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.55 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 130.45 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 627360.01 0.00 0.00 0.00 0.00
Cooling 133970.89 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 69516.65 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 542963.08 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2491265.49 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 21.34 0.00 0.00 0.00 0.00
Cooling 4.56 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 18.47 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 84.72 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 21.34 0.00 0.00 0.00 0.00
Cooling 4.56 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 18.47 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 84.72 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 2.66 0.00 2.66 Wetbulb [F] 452.78 120.00
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 98.06 30.06 64.22 Wetbulb [F] 826.81 330.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.330 0.882              
North Total or Average           531.68 0.320 0.330 0.882              
Non-North Total or Average           1595.05 0.320 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15864.30 12670.11 3194.19 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6504.72 5195.03 1309.69 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8764.47 6999.79 1764.68 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13041.57 10415.71 2625.85 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   5988.70 4782.90 1205.79 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8759.03 6995.44 1763.58 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13342.57 10656.11 2686.46 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6482.33 5177.14 1305.18 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8502.82 6790.82 1712.00 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12801.04 10223.62 2577.42 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   5995.46 4788.31 1207.15 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8510.21 6796.72 1713.49 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14376.87 11482.16 2894.71 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7591.87 6063.29 1528.58 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9036.93 7217.39 1819.54 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14301.89 11422.28 2879.61 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7522.55 6007.92 1514.63 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8915.99 7120.81 1795.19 0.80 3.97    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   2014.54 1587.65 426.89 0.79 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.3 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNITHEATEDBSMT   0.2 3.21 10.96 11.61 11.18
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   11394.44 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   11035.41 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   13317.00 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   13320.60 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   11035.12 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   13314.06 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   12394.71 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   10100.72 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   12397.26 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   12397.02 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   10100.41 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   12394.46 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   14904.00 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   12612.29 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   14908.15 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   14904.93 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   12611.42 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   14905.48 1.00
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT Coil:Heating:Electric   6760.86 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 595.08 298.02 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 244.00 122.19 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 328.76 164.64 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 489.20 244.99 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 224.64 112.50 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 328.56 164.54 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 500.49 250.64 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 243.16 121.77 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 318.95 159.73 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 480.18 240.47 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 224.90 112.63 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 319.23 159.87 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 539.29 270.07 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 284.78 142.62 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 338.98 169.76 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 536.48 268.67 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 282.18 141.31 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 334.45 167.49 0.50 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.38 0.06 73.40 36.76 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12858.15 12858.15 10.71 595.085 595.085 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00801 89.72 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5272.13 5272.13 4.39 243.998 243.998 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7103.72 7103.72 5.92 328.763 328.763 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 74.98 74.98 0.00787 87.76 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10570.29 10570.29 8.80 489.201 489.201 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4853.88 4853.88 4.04 224.642 224.642 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00804 86.34 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7099.31 7099.31 5.91 328.559 328.559 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 74.98 74.98 0.00787 87.76 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10814.21 10814.21 9.01 500.492 500.492 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00805 88.59 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5253.95 5253.95 4.38 243.158 243.158 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00810 86.34 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6891.64 6891.64 5.74 318.949 318.949 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00791 88.89 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10375.30 10375.30 8.64 480.179 480.179 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00805 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4859.35 4859.35 4.05 224.895 224.895 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00811 86.34 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6897.63 6897.63 5.75 319.226 319.226 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00791 88.89 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7226.50 7226.50 6.02 334.447 334.447 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00801 89.72 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7324.56 7324.56 6.10 338.984 338.984 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00796 92.35 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11652.56 11652.56 9.71 539.290 539.290 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6097.08 6097.08 5.08 282.178 282.178 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00805 86.34 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6153.26 6153.26 5.13 284.778 284.778 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00805 86.34 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11591.79 11591.79 9.66 536.477 536.477 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
HEATEDBSMT 646.39 646.39 0.08 29.915 44.995 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 20:45:00 74.98 74.98 0.00767 81.00 0.00627 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8411.15 8411.15 7.01 166.425 166.425 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00591 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8046.82 8046.82 6.70 159.216 159.216 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00592 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10362.17 10362.17 8.63 205.025 205.025 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00619 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10365.82 10365.82 8.63 205.097 205.097 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00620 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8046.53 8046.53 6.70 159.210 159.210 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00592 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10359.19 10359.19 8.63 204.966 204.966 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00619 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9426.12 9426.12 7.85 186.515 186.515 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00640 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7098.18 7098.18 5.91 140.454 140.454 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00613 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9428.70 9428.70 7.85 186.566 186.566 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00640 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9428.46 9428.46 7.85 186.561 186.561 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00640 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7097.87 7097.87 5.91 140.448 140.448 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00613 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9425.87 9425.87 7.85 186.510 186.510 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00640 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11974.13 11974.13 9.97 236.919 236.919 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00638 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11976.84 11976.84 9.98 236.973 236.973 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00638 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11972.62 11972.62 9.97 236.889 236.889 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00638 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9646.13 9646.13 8.03 190.861 190.861 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00617 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9647.01 9647.01 8.04 190.878 190.878 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00617 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11973.58 11973.58 9.97 236.908 236.908 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00638 2.66 0.00098 44.995 0.00
HEATEDBSMT 3708.45 3708.45 0.48 73.397 73.397 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 17:15:00 72.00 72.00 0.00800 2.66 0.00098 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 595.08 595.08 166.43 166.43
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.00 244.00 159.22 159.22
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 328.76 328.76 205.03 205.03
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 489.20 489.20 205.10 205.10
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 224.64 224.64 159.21 159.21
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.56 328.56 204.97 204.97
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 500.49 500.49 186.52 186.52
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.16 243.16 140.45 140.45
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 318.95 318.95 186.57 186.57
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 480.18 480.18 186.56 186.56
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 224.90 224.90 140.45 140.45
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 319.23 319.23 186.51 186.51
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 539.29 539.29 236.89 236.89
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.78 284.78 190.88 190.88
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 338.98 338.98 236.97 236.97
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 536.48 536.48 236.91 236.91
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 282.18 282.18 190.86 190.86
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 334.45 334.45 236.92 236.92
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.99 73.40 73.40


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1034.25 5863.00 25.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 402.25 6026.25 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1094.25 5739.50 24.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 840.75 6448.75 38.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 222.00 6639.50 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 825.25 6179.75 31.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1143.00 5878.00 24.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 496.25 5860.25 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1177.75 5624.50 22.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 910.75 6318.75 33.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 306.00 6419.25 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 909.75 6035.50 28.25
LIVING_UNIT3_BACKROW_TOPFLOOR 1100.50 6066.75 136.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 1234.50 5809.25 102.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1208.50 6121.00 107.25
LIVING_UNIT2_BACKROW_TOPFLOOR 522.25 6458.50 29.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 631.50 6127.25 19.50
LIVING_UNIT1_BACKROW_TOPFLOOR 1126.75 6367.50 145.75
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 1800.00 6915.75 154.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 13.75 0.00 13.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 14.75 0.00 14.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 16.50 0.00 16.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 18.75 0.00 18.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 13.50 0.00 13.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 12.25 0.00 12.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 1.75 0.00 1.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 14.50 0.00 14.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 14.75 0.00 14.75
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 15.25 0.00 15.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 17.50 0.00 17.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 14.25 0.00 14.25
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 15.50 0.00 15.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 14.25 0.00 14.25
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 14.75 0.00 14.75
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 30.00 0.00 30.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.116 0.000 0.276
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.101 0.000 0.276
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.115 0.000 0.276
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.115 0.000 0.276
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.101 0.000 0.276
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.115 0.000 0.276
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.276
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.037 0.000 0.276
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.276
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.276
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.037 0.000 0.276
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.276
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.115 0.000 0.276
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.115 0.000 0.276
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.115 0.000 0.276
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.101 0.000 0.276
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.101 0.000 0.276
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.115 0.000 0.276
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1846
Defaulted Fields 455
Fields with Defaults 4639
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Electricity:Plant 50211.78 0.00 01-JAN-00:15 38639.03 11-FEB-08:15
WaterSystems:Electricity 50211.78 0.00 01-JAN-00:15 38639.03 11-FEB-08:15
Water Heater:WaterSystems:Electricity 50211.78 0.00 01-JAN-00:15 38639.03 11-FEB-08:15
Fans:Electricity 6428.72 0.00 16-MAY-01:15 3325.33 21-JUL-18:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
ElectricityPurchased:Plant 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
Cogeneration:ElectricityPurchased 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
ElectricityNet:Plant 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
Cogeneration:ElectricityNet 230385.61 6806.28 09-MAY-03:30 96448.62 13-JAN-08:30
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 76834.57 0.00 16-MAY-01:15 48142.16 13-JAN-08:15
General:Fans:Electricity 6428.72 0.00 16-MAY-01:15 3325.33 21-JUL-18:15
Heating:Electricity 58016.59 0.00 01-MAY-12:15 45906.84 13-JAN-08:15
Cooling:Electricity 12389.27 0.00 01-JAN-00:15 13075.32 31-JUL-18:00
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
Water:Plant 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
WaterSystems:Water 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
MainsWater:Plant 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
WaterSystems:MainsWater 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 12-JUL-02:30 0.18 07-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
PlantLoopHeatingDemand:Plant 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
WaterSystems:PlantLoopHeatingDemand 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 896834.19 1647.10 23-AUG-03:00 359842.51 13-JAN-08:15
EnergyTransfer:Building 367179.19 0.00 16-MAY-01:15 164261.05 13-JAN-08:15
EnergyTransfer:Zone:HEATEDBSMT 10455.72 0.00 01-MAY-12:15 3808.36 14-JAN-09:30
Heating:EnergyTransfer 207431.04 0.00 01-MAY-12:15 164261.05 13-JAN-08:15
Heating:EnergyTransfer:Zone:HEATEDBSMT 10212.73 0.00 01-MAY-12:15 3808.36 14-JAN-09:30
Cooling:EnergyTransfer 159748.15 0.00 01-JAN-00:15 145685.20 22-JUL-18:30
Cooling:EnergyTransfer:Zone:HEATEDBSMT 242.99 0.00 01-JAN-00:15 742.55 12-JUL-21:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 22572.91 0.00 01-JAN-14:00 13508.04 20-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4716.02 0.00 01-JAN-14:00 7667.72 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17856.89 0.00 01-JAN-00:15 13508.04 20-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14403.47 0.00 06-JAN-12:45 7365.44 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7608.23 0.00 06-JAN-12:45 7365.44 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6795.24 0.00 01-JAN-00:15 5639.51 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20881.54 0.00 06-JAN-13:15 9578.12 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10789.39 0.00 06-JAN-13:15 9578.12 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10092.15 0.00 01-JAN-00:15 7713.72 22-JUL-09:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 21813.17 0.00 03-FEB-16:30 11141.13 14-JUL-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13436.78 0.00 03-FEB-16:30 9611.49 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8376.39 0.00 01-JAN-00:15 11141.13 14-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15003.78 0.00 10-FEB-18:15 7427.64 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10069.96 0.00 10-FEB-18:15 7427.64 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4933.82 0.00 01-JAN-00:15 5199.12 21-JUN-20:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21127.99 0.00 02-MAR-10:00 9616.54 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13047.63 0.00 02-MAR-10:00 9616.54 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8080.36 0.00 01-JAN-00:15 7740.55 22-JUL-09:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20147.91 0.00 01-JAN-16:00 11381.82 20-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9414.30 0.00 01-JAN-16:00 8661.44 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10733.61 0.00 01-JAN-00:15 11381.82 20-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13293.38 0.00 06-JAN-12:45 6443.11 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6198.49 0.00 06-JAN-12:45 6443.11 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7094.89 0.00 01-JAN-00:15 5636.06 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 19707.38 0.00 06-JAN-13:00 8671.71 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9290.92 0.00 06-JAN-13:00 8671.71 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10416.45 0.00 01-JAN-00:15 7496.81 22-JUL-09:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20378.05 0.00 03-FEB-16:45 10922.00 20-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11758.42 0.00 03-FEB-16:45 8705.43 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8619.64 0.00 01-JAN-00:15 10922.00 20-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13668.87 0.00 10-FEB-18:15 6506.26 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8400.08 0.00 10-FEB-18:15 6506.26 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5268.79 0.00 01-JAN-00:15 5279.41 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 19848.82 0.00 02-MAR-10:15 8710.77 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11419.41 0.00 02-MAR-10:15 8710.77 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8429.41 0.00 01-JAN-00:15 7535.95 22-JUL-09:30
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 24590.13 0.00 03-MAR-17:15 11015.52 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 15493.60 0.00 03-MAR-17:15 11015.52 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 9096.53 0.00 01-JAN-00:15 7626.08 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 23547.39 0.00 04-FEB-13:30 10981.40 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 13321.66 0.00 04-FEB-13:30 10981.40 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10225.73 0.00 01-JAN-00:15 7729.01 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24390.05 0.00 06-JAN-15:45 12247.87 20-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 13757.54 0.00 06-JAN-15:45 10972.62 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10632.52 0.00 01-JAN-00:15 12247.87 20-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 18623.43 0.00 03-MAR-17:00 8825.04 13-JAN-08:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 12431.08 0.00 03-MAR-17:00 8825.04 13-JAN-08:45
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6192.35 0.00 01-JAN-00:15 6614.39 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 17307.56 0.00 23-JAN-14:30 8751.86 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10101.52 0.00 23-JAN-14:30 8751.86 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 7206.04 0.00 01-JAN-00:15 6675.78 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 25417.63 0.00 05-FEB-16:30 12196.01 14-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 15963.28 0.00 05-FEB-16:30 11014.42 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9454.35 0.00 01-JAN-00:15 12196.01 14-JUL-18:30
EnergyTransfer:Plant 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
WaterSystems:EnergyTransfer 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 155703.36 1291.68 11-AUG-03:00 41488.52 11-FEB-08:30
EnergyTransfer:HVAC 373951.63 0.00 16-MAY-01:15 160863.31 12-JUL-19:45
HeatingCoils:EnergyTransfer 198092.83 0.00 01-MAY-12:15 156634.15 13-JAN-08:15
CoolingCoils:EnergyTransfer 175858.80 0.00 01-JAN-00:15 160863.31 12-JUL-19:45



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 4715.960 -1487.08 0.000 0.000 2987.336 2456.001 10405.511 9935.127 0.000 563.950 6627.380 0.000 -6235.56 0.000 -13598.83 -0.41
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 7608.144 -565.89 0.000 0.000 3034.053 2456.001 10405.511 4387.542 0.000 544.979 0.000 0.000 -2482.26 0.000 -12808.75 -6349.99
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 10789.277 -840.45 0.000 0.000 3045.617 2456.001 10405.511 10041.635 0.000 564.689 0.000 0.000 -5916.78 0.000 -13292.87 -8000.97
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 13436.656 -697.57 0.000 0.000 3058.153 2456.001 10405.511 6811.704 0.000 563.784 0.000 0.000 -6333.41 0.000 -13139.40 -8882.62
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 10069.874 -410.88 0.000 0.000 3053.688 2456.001 10405.511 1069.603 0.000 544.980 0.000 0.000 -2646.04 0.000 -12660.36 -7359.44
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 13047.510 -672.91 0.000 0.000 3058.440 2456.001 10405.511 6823.251 0.000 564.769 0.000 0.000 -6071.41 0.000 -13183.49 -9020.24
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 9414.202 -893.87 0.000 0.000 3034.521 2456.001 10405.511 9983.086 0.000 473.469 0.000 0.000 -6221.33 0.000 -10978.28 -7833.58
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 6198.419 -590.85 0.000 0.000 3023.172 2456.001 10405.511 4386.070 0.000 454.717 0.000 0.000 -2508.95 0.000 -10524.29 -6795.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 9290.826 -867.46 0.000 0.000 3036.519 2456.001 10405.511 10033.405 0.000 473.970 0.000 0.000 -5982.57 0.000 -11006.39 -8290.85
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 11758.312 -717.82 0.000 0.000 3049.524 2456.001 10405.511 6813.714 0.000 473.547 0.000 0.000 -6401.16 0.000 -10880.61 -9055.19
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 8400.010 -438.77 0.000 0.000 3044.221 2456.001 10405.511 1072.891 0.000 454.747 0.000 0.000 -2671.36 0.000 -10403.72 -7489.52
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 11419.314 -701.98 0.000 0.000 3050.585 2456.001 10405.511 6818.366 0.000 474.121 0.000 0.000 -6132.37 0.000 -10915.06 -9147.08
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 15493.470 -757.54 0.000 0.000 3056.593 2456.001 10405.511 6837.713 0.000 560.093 0.000 0.000 -6111.92 0.000 -13207.05 -10393.90
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 13321.531 -851.57 0.000 0.000 3047.501 2456.001 10405.511 10077.577 0.000 560.024 0.000 0.000 -5944.01 0.000 -13280.81 -10417.63
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 13757.403 -885.45 0.000 0.000 3048.088 2456.001 10405.511 10028.098 0.000 560.132 0.000 0.000 -6165.29 0.000 -13237.48 -10219.95
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 12430.979 -515.68 0.000 0.000 3052.471 2456.001 10405.511 1078.072 0.000 541.621 0.000 0.000 -2656.49 0.000 -12689.71 -8426.10
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 10101.424 -600.10 0.000 0.000 3040.241 2456.001 10405.511 4404.585 0.000 541.424 0.000 0.000 -2486.41 0.000 -12775.50 -8481.24
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 15963.138 -787.34 0.000 0.000 3056.210 2456.001 10405.511 6822.082 0.000 560.380 0.000 0.000 -6369.93 0.000 -13171.26 -10267.79
HEATEDBSMT 0.000 0.000 10212.731 -20.24 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -9969.74
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4825.357 42024.599 0.000 0.000 0.000 -46849.96 -0.69
Total Facility 0.000 0.000 207429.179 -13303.44 0.000 0.000 54776.934 44208.020 187299.191 117424.522 0.000 14300.752 48651.980 0.000 -89337.23 0.000 -268603.81 -156402.68


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.1 0.00 0.00 425.84 721.37 1713.78 7796.63 0.00 1104.62 1759.10 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.5 0.00 0.00 426.79 799.44 1616.68 40.34 0.00 525.87 2308.71 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-09:17 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1113.11 7250.44 0.00 537.90 0.00 0.00 0.00 0.00 0.00 -1405.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14-JUL-18:33 0.00 0.00 0.00 -0.9 0.00 0.00 424.01 721.37 1713.78 7224.57 0.00 1027.80 50.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.4 0.00 0.00 425.27 799.44 1616.68 43.24 0.00 520.75 1861.65 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 22-JUL-09:21 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1113.11 7114.04 0.00 537.91 0.00 0.00 0.00 0.00 0.00 -1238.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.0 0.00 0.00 424.82 721.37 1713.78 7784.56 0.00 903.11 0.00 0.00 0.00 0.00 0.00 -146.4
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.5 0.00 0.00 424.82 799.44 1616.68 43.48 0.00 451.92 2376.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-09:39 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1113.11 6808.03 0.00 495.78 0.00 0.00 0.00 0.00 0.00 -1136.2
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22-JUN-19:33 0.00 0.00 0.00 -0.9 0.00 0.00 423.55 799.44 1651.33 5298.44 0.00 766.33 2033.99 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21-JUN-20:47 0.00 0.00 0.00 -0.4 0.00 0.00 427.01 799.44 1616.68 51.15 0.00 457.60 1962.35 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22-JUL-09:19 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 103.05 1113.11 7107.55 0.00 462.34 0.00 0.00 0.00 0.00 0.00 -1365.1
LIVING_UNIT3_BACKROW_TOPFLOOR 21-JUL-20:35 0.00 0.00 0.00 -0.6 0.00 0.00 423.90 799.44 1616.68 178.46 0.00 684.59 4019.59 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-20:35 0.00 0.00 0.00 -0.7 0.00 0.00 424.18 799.44 1616.68 180.50 0.00 685.76 4120.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.0 0.00 0.00 424.62 721.37 1713.78 7762.35 0.00 1095.90 552.07 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUN-20:47 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 799.44 1616.68 41.89 0.00 519.25 3239.26 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.6 0.00 0.00 420.44 799.44 1616.68 32.28 0.00 500.85 3315.08 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.0 0.00 0.00 424.57 721.37 1713.78 7939.62 0.00 1095.58 313.22 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 12-JUL-21:18 0.00 0.00 0.00 -0.1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 742.55 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-JUL-18:20 0.00 0.00 0.00 -12.2 0.00 0.00 7537.43 12984.58 31240.86 62638.12 0.00 21135.64 21257.10 0.00 0.00 0.00 -10799.9 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 7667.47 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2726.6 0.00 -5365.9 -1087.1
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 7365.19 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1109.2 0.00 -5137.6 -2630.4
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 9577.80 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2726.2 0.00 -5365.9 -2997.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 9611.17 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2720.8 0.00 -5365.9 -3036.6
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13-JAN-08:30 0.00 0.00 7427.26 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1043.4 0.00 -5137.6 -2758.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 9616.22 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2720.5 0.00 -5365.9 -3041.9
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 8661.14 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2749.2 0.00 -4293.8 -3130.2
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 6442.89 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1116.5 0.00 -4065.4 -2773.2
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 8671.41 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2749.0 0.00 -4293.8 -3140.6
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 8705.14 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2746.6 0.00 -4293.8 -3176.8
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13-JAN-08:30 0.00 0.00 6505.92 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1054.2 0.00 -4065.4 -2898.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 8710.46 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2746.5 0.00 -4293.8 -3182.2
LIVING_UNIT3_BACKROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 11015.15 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2738.6 0.00 -5372.2 -4416.4
LIVING_UNIT3_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 10981.03 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2739.0 0.00 -5372.2 -4381.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 10972.27 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2739.2 0.00 -5372.2 -4373.0
LIVING_UNIT2_BACKROW_TOPFLOOR 13-JAN-08:45 0.00 0.00 8824.62 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1018.2 0.00 -5143.6 -4174.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 8751.57 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -1110.0 0.00 -5143.5 -4010.1
LIVING_UNIT1_BACKROW_TOPFLOOR 13-JAN-08:30 0.00 0.00 11013.94 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -2588.9 0.00 -5372.2 -4565.0
HEATEDBSMT 14-JAN-09:30 0.00 0.00 3808.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -3808.4
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 13-JAN-08:15 0.00 0.00 164255.66 0.00 0.00 0.00 3870.98 2720.58 20626.19 0.00 0.00 1300.54 0.00 0.00 -39504.7 0.00 -88820.8 -64448.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 595.085 2.00 2.00 1.00 44.9950 595.085 0.076 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 243.998 2.00 2.00 1.00 44.9950 243.998 0.184 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 328.763 2.00 2.00 1.00 44.9950 328.763 0.137 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 489.201 2.00 2.00 1.00 44.9950 489.201 0.092 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 224.642 2.00 2.00 1.00 44.9950 224.642 0.200 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.559 2.00 2.00 1.00 44.9950 328.559 0.137 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 500.492 2.00 2.00 1.00 44.9950 500.492 0.090 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.158 2.00 2.00 1.00 44.9950 243.158 0.185 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 318.949 2.00 2.00 1.00 44.9950 318.949 0.141 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 480.179 2.00 2.00 1.00 44.9950 480.179 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 224.895 2.00 2.00 1.00 44.9950 224.895 0.200 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 319.226 2.00 2.00 1.00 44.9950 319.226 0.141 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 539.290 2.00 2.00 1.00 44.9950 539.290 0.083 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.778 2.00 2.00 1.00 44.9950 284.778 0.158 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 338.984 2.00 2.00 1.00 44.9950 338.984 0.133 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 536.477 2.00 2.00 1.00 44.9950 536.477 0.084 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 282.178 2.00 2.00 1.00 44.9950 282.178 0.159 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 334.447 2.00 2.00 1.00 44.9950 334.447 0.135 1.000 44.9950 0.13
CENTRAL SYSTEM_UNITHEATEDBSMT 44.995 0.00 0.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 166.425 2.00 2.00 1.00 44.9950 166.425 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 159.216 2.00 2.00 1.00 44.9950 159.216 1.000 1.000 44.9950 0.28
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 205.025 2.00 2.00 1.00 44.9950 205.025 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 205.097 2.00 2.00 1.00 44.9950 205.097 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 159.210 2.00 2.00 1.00 44.9950 159.210 1.000 1.000 44.9950 0.28
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 204.966 2.00 2.00 1.00 44.9950 204.966 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 186.515 2.00 2.00 1.00 44.9950 186.515 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 140.454 2.00 2.00 1.00 44.9950 140.454 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 186.566 2.00 2.00 1.00 44.9950 186.566 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 186.561 2.00 2.00 1.00 44.9950 186.561 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 140.448 2.00 2.00 1.00 44.9950 140.448 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 186.510 2.00 2.00 1.00 44.9950 186.510 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 236.889 2.00 2.00 1.00 44.9950 236.889 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.878 2.00 2.00 1.00 44.9950 190.878 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 236.973 2.00 2.00 1.00 44.9950 236.973 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 236.908 2.00 2.00 1.00 44.9950 236.908 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 190.861 2.00 2.00 1.00 44.9950 190.861 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 236.919 2.00 2.00 1.00 44.9950 236.919 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNITHEATEDBSMT 73.397 0.00 0.00 1.00 44.9950 73.397 1.000 1.000 44.9950 0.61


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   595.085 595.0846 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   243.998 243.9981 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   328.763 328.7632 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   489.201 489.2012 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   224.642 224.6416 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   328.559 328.5592 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   500.492 500.4920 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   243.158 243.1581 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   318.949 318.9487 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   480.179 480.1790 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   224.895 224.8953 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   319.226 319.2257 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   334.447 334.4472 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   338.984 338.9836 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   539.290 539.2896 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   282.178 282.1777 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   284.778 284.7780 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   536.477 536.4771 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   44.995 44.9950 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 595.08 595.085 595.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.00 243.998 244.00 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 328.76 328.763 328.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 489.20 489.201 489.20 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 224.64 224.642 224.64 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.56 328.559 328.56 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 500.49 500.492 500.49 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.16 243.158 243.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 318.95 318.949 318.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 480.18 480.179 480.18 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 224.90 224.895 224.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 319.23 319.226 319.23 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 539.29 539.290 539.29 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.78 284.778 284.78 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 338.98 338.984 338.98 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 536.48 536.477 536.48 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 282.18 282.178 282.18 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 334.45 334.447 334.45 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.995 44.99 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   166.425 166.425 166.425 44.9950 0.270 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   159.216 159.216 159.216 44.9950 0.283 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   205.025 205.025 205.025 44.9950 0.219 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   205.097 205.097 205.097 44.9950 0.219 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   159.210 159.210 159.210 44.9950 0.283 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   204.966 204.966 204.966 44.9950 0.220 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   186.515 186.515 186.515 44.9950 0.241 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   140.454 140.454 140.454 44.9950 0.320 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   186.566 186.566 186.566 44.9950 0.241 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   186.561 186.561 186.561 44.9950 0.241 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   140.448 140.448 140.448 44.9950 0.320 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   186.510 186.510 186.510 44.9950 0.241 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   236.919 236.919 236.919 44.9950 0.190 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   236.973 236.973 236.973 44.9950 0.190 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   236.889 236.889 236.889 44.9950 0.190 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   190.861 190.861 190.861 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   190.878 190.878 190.878 44.9950 0.236 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   236.908 236.908 236.908 44.9950 0.190 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   73.397 73.397 73.397 44.9950 0.613 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 166.43 166.425 166.43 166.43 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 159.22 159.216 159.22 159.22 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 205.03 205.025 205.03 205.03 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 205.10 205.097 205.10 205.10 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 159.21 159.210 159.21 159.21 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 204.97 204.966 204.97 204.97 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 186.52 186.515 186.52 186.52 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 140.45 140.454 140.45 140.45 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 186.57 186.566 186.57 186.57 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 186.56 186.561 186.56 186.56 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 140.45 140.448 140.45 140.45 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 186.51 186.510 186.51 186.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 236.89 236.889 236.89 236.89 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.88 190.878 190.88 190.88 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 236.97 236.973 236.97 236.97 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 236.91 236.908 236.91 236.91 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 190.86 190.861 190.86 190.86 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 236.92 236.919 236.92 236.92 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 73.40 73.397 73.40 73.40 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Sec1.1A-General Information

Data
Weather File ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 30.00
Number of hours not met 30.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 797.36 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 29.41 0.00 0.00 0.00 0.00
Space Heating 58016.59 45335.16 0.00 0.00 0.00 0.00
Space Cooling 12389.27 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6428.72 2210.29 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 50211.78 38204.94 0.00 0.00 0.00 0.00
Receptacle Equipment 87836.46 9871.46 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 230385.61   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 786632.61
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299910.33 786632.61


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 1.49
Space Cooling 0.32
Fans-Interior 0.16
Service Water Heating 1.29
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 5.91


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.62
Space Heating 25.18
Space Cooling 5.38
Fans-Interior 2.79
Service Water Heating 21.79
Receptacle Equipment 38.13
Miscellaneous 1.11



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 73.40
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 595.08
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 244.00
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 328.76
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 489.20
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 224.64
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 328.56
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 500.49
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 243.16
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 318.95
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 480.18
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 224.90
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 319.23
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 334.45
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 338.98
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 539.29
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 282.18
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 284.78
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 536.48
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 595.08
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 328.76
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 489.20
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 224.64
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.56
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 500.49
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 243.16
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 318.95
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 480.18
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 224.90
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 319.23
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 539.29
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 284.78
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 338.98
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 536.48
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 282.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 334.45
CENTRAL SYSTEM_UNITHEATEDBSMT 73.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 595.08 1.32 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 244.00 0.542060 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 328.76 0.730372 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 489.20 1.09 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 224.64 0.499058 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 328.56 0.729919 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 500.49 1.11 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 243.16 0.540194 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 318.95 0.708568 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 480.18 1.07 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 224.90 0.499622 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 319.23 0.709184 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 539.29 1.20 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 284.78 0.632656 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 338.98 0.753077 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 536.48 1.19 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 282.18 0.626879 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 334.45 0.742999 0.798655
DX COOLING COIL_UNITHEATEDBSMT 73.40 0.167878 0.788096
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 595.08 595.08 595.08 11394.44 1.32 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 244.00 244.00 244.00 11035.41 0.542060 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 328.76 328.76 328.76 13317.00 0.730372 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 489.20 489.20 489.20 13320.60 1.09 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 224.64 224.64 224.64 11035.12 0.499058 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 328.56 328.56 328.56 13314.06 0.729919 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 500.49 500.49 500.49 12394.71 1.11 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 243.16 243.16 243.16 10100.72 0.540194 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 318.95 318.95 318.95 12397.26 0.708568 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 480.18 480.18 480.18 12397.02 1.07 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 224.90 224.90 224.90 10100.41 0.499622 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 319.23 319.23 319.23 12394.46 0.709184 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 539.29 539.29 539.29 14904.00 1.20 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 284.78 284.78 284.78 12612.29 0.632656 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 338.98 338.98 338.98 14908.15 0.753077 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 536.48 536.48 536.48 14904.93 1.19 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 282.18 282.18 282.18 12611.42 0.626879 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 334.45 334.45 334.45 14905.48 0.742999 1.00
ACANDF_UNITHEATEDBSMT 73.40 73.40 73.40 6760.86 0.167878 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 595.08
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 244.00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 328.76
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 489.20
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 224.64
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 328.56
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 500.49
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 243.16
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 318.95
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 480.18
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 224.90
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 319.23
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 539.29
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 284.78
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 338.98
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 536.48
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 282.18
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 334.45
SUPPLY FAN_UNITHEATEDBSMT 73.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 11394.44
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 11035.41
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 13317.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 13320.60
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 11035.12
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 13314.06
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 12394.71
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 10100.72
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 12397.26
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 12397.02
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 10100.41
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 12394.46
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 14904.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 12612.29
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 14908.15
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 14904.93
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 12611.42
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 14905.48
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT 6760.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:44:31

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 18.708 0.538 652.717 40.520 41.058
February 101.233 3.941 399.411 16.958 20.899
March 212.556 10.363 296.158 9.686 20.049
April 438.381 28.543 82.517 2.182 30.725
May 588.031 40.304 12.986 0.101 40.404
June 672.062 66.570 4.417 0.039 66.609
July 742.833 91.987 0.000 0.000 91.987
August 718.164 76.863 0.000 0.000 76.863
September 652.593 56.157 2.500 0.018 56.175
October 452.863 29.017 64.075 1.400 30.417
November 138.399 5.348 367.054 16.815 22.163
December 58.358 1.709 539.321 25.441 27.149
           
Annual Sum or Average 4794.183 411.339 2421.155 113.159 524.498
Minimum of Months 18.708 0.538 0.000 0.000 20.049
Maximum of Months 742.833 91.987 652.717 40.520 91.987



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 708.504 23.508 23.508
February 20.525 0.405 537.033 12.587 12.993
March 73.162 1.685 488.500 9.245 10.930
April 218.477 7.475 222.931 3.015 10.490
May 306.723 10.959 119.258 0.962 11.922
June 513.015 25.371 30.375 0.234 25.604
July 700.241 42.227 0.000 0.000 42.227
August 584.977 32.783 11.083 0.049 32.833
September 449.376 23.231 39.014 0.239 23.470
October 262.461 10.230 212.077 2.288 12.517
November 45.003 1.314 533.208 12.154 13.467
December 12.042 0.169 641.617 16.839 17.008
           
Annual Sum or Average 3186.003 155.848 3543.601 81.120 236.969
Minimum of Months 0.000 0.000 0.000 0.000 10.490
Maximum of Months 700.241 42.227 708.504 23.508 42.227



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 721.242 35.613 35.613
February 16.688 0.309 566.858 19.821 20.130
March 87.391 2.610 499.250 13.844 16.454
April 278.906 12.282 221.225 4.511 16.793
May 377.041 18.964 137.850 1.838 20.801
June 543.814 40.158 27.792 0.339 40.497
July 685.884 61.643 1.500 0.007 61.650
August 591.947 47.413 20.750 0.195 47.609
September 456.928 31.741 68.750 0.703 32.443
October 264.228 13.340 253.583 4.389 17.729
November 35.406 1.368 590.046 19.808 21.176
December 6.583 0.107 680.042 26.837 26.944
           
Annual Sum or Average 3344.815 229.936 3788.888 127.903 357.839
Minimum of Months 0.000 0.000 1.500 0.007 16.454
Maximum of Months 685.884 61.643 721.242 35.613 61.650



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 59.398 59.398
February 0.000 0.000 647.117 35.968 35.968
March 30.667 0.996 619.671 26.548 27.545
April 180.242 8.626 325.143 9.661 18.287
May 284.386 17.335 197.734 3.514 20.850
June 486.861 39.613 53.312 0.903 40.515
July 666.093 59.513 2.986 0.012 59.525
August 529.068 43.598 38.000 0.459 44.057
September 359.979 22.113 106.625 1.603 23.716
October 118.782 5.258 404.075 10.854 16.112
November 3.884 0.065 687.375 35.990 36.055
December 0.000 0.000 744.000 47.460 47.460
           
Annual Sum or Average 2659.962 197.118 4570.038 232.370 429.488
Minimum of Months 0.000 0.000 2.986 0.012 16.112
Maximum of Months 666.093 59.513 744.000 59.398 59.525



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 26.044 26.044
February 0.000 0.000 671.650 16.087 16.087
March 6.250 0.089 671.533 11.702 11.791
April 134.788 3.347 308.125 3.824 7.171
May 269.044 8.036 144.291 1.107 9.143
June 508.774 23.729 33.300 0.241 23.970
July 703.491 39.228 0.000 0.000 39.228
August 560.330 26.399 13.000 0.060 26.458
September 364.647 12.256 62.428 0.385 12.641
October 78.874 1.956 365.768 3.964 5.920
November 0.000 0.000 675.013 15.431 15.431
December 0.000 0.000 744.000 20.296 20.296
           
Annual Sum or Average 2626.200 115.041 4433.108 99.139 214.180
Minimum of Months 0.000 0.000 0.000 0.000 5.920
Maximum of Months 703.491 39.228 744.000 26.044 39.228



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 40.756 40.756
February 0.000 0.000 672.000 25.053 25.053
March 13.931 0.361 657.666 16.963 17.324
April 204.819 7.144 262.017 5.235 12.379
May 359.599 15.925 148.308 1.982 17.907
June 538.127 38.666 26.667 0.347 39.013
July 686.596 58.982 1.500 0.006 58.988
August 584.166 41.422 22.375 0.212 41.634
September 420.324 20.798 76.875 0.815 21.613
October 129.290 4.040 365.398 6.047 10.087
November 0.000 0.000 686.177 24.669 24.669
December 0.000 0.000 744.000 32.529 32.529
           
Annual Sum or Average 2936.851 187.338 4406.982 154.615 341.953
Minimum of Months 0.000 0.000 1.500 0.006 10.087
Maximum of Months 686.596 58.982 744.000 40.756 58.988



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 2.417 0.022 710.683 50.281 50.303
February 31.754 0.879 531.800 27.041 27.920
March 92.362 4.247 488.521 19.776 24.023
April 252.902 14.700 235.069 6.482 21.182
May 337.470 21.753 135.124 2.189 23.942
June 518.825 42.677 34.688 0.539 43.215
July 685.921 63.767 0.000 0.000 63.767
August 571.188 50.934 22.083 0.213 51.147
September 437.892 34.185 57.625 0.809 34.994
October 247.650 14.694 258.333 6.119 20.813
November 45.813 1.685 555.854 27.090 28.775
December 9.500 0.174 657.858 37.422 37.596
           
Annual Sum or Average 3233.694 249.716 3687.640 177.961 427.677
Minimum of Months 2.417 0.022 0.000 0.000 20.813
Maximum of Months 685.921 63.767 710.683 50.281 63.767



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 702.875 21.535 21.535
February 23.048 0.383 519.700 11.185 11.568
March 78.625 1.758 460.521 7.945 9.704
April 241.208 8.216 185.786 2.259 10.475
May 335.919 11.922 91.375 0.672 12.595
June 548.836 26.667 22.533 0.126 26.793
July 722.421 43.605 0.000 0.000 43.605
August 616.676 33.845 5.250 0.015 33.860
September 481.238 24.198 27.250 0.156 24.355
October 280.455 10.614 170.358 1.740 12.354
November 47.796 1.364 512.825 10.907 12.271
December 11.367 0.142 624.771 15.184 15.326
           
Annual Sum or Average 3387.588 162.716 3323.244 71.725 234.441
Minimum of Months 0.000 0.000 0.000 0.000 9.704
Maximum of Months 722.421 43.605 702.875 21.535 43.605



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 717.629 32.900 32.900
February 15.583 0.288 554.229 17.914 18.202
March 94.175 2.744 478.719 12.103 14.847
April 305.347 13.248 187.750 3.446 16.695
May 396.857 20.131 109.733 1.326 21.456
June 570.703 41.487 16.750 0.194 41.681
July 701.808 62.799 0.000 0.000 62.799
August 611.769 48.306 12.625 0.101 48.407
September 478.903 32.594 49.146 0.475 33.070
October 278.240 13.662 224.146 3.527 17.189
November 38.525 1.360 573.942 18.027 19.387
December 5.917 0.087 671.438 24.569 24.655
           
Annual Sum or Average 3497.826 236.705 3596.106 114.584 351.289
Minimum of Months 0.000 0.000 0.000 0.000 14.847
Maximum of Months 701.808 62.799 717.629 32.900 62.799



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 56.082 56.082
February 0.000 0.000 646.304 33.393 33.393
March 33.521 0.951 600.058 23.948 24.899
April 199.525 9.207 283.488 7.834 17.041
May 306.121 18.225 162.021 2.619 20.844
June 514.238 40.775 37.975 0.584 41.359
July 686.342 60.893 0.000 0.000 60.893
August 552.028 44.548 28.388 0.286 44.833
September 382.199 22.846 82.439 1.204 24.050
October 127.472 5.198 375.867 9.452 14.649
November 3.354 0.036 679.667 33.705 33.741
December 0.000 0.000 744.000 44.668 44.668
           
Annual Sum or Average 2804.800 202.679 4384.206 213.774 416.453
Minimum of Months 0.000 0.000 0.000 0.000 14.649
Maximum of Months 686.342 60.893 744.000 56.082 60.893



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 24.498 24.498
February 0.000 0.000 671.150 14.820 14.820
March 6.625 0.106 642.999 10.299 10.404
April 161.022 4.040 255.201 2.892 6.932
May 299.496 9.179 111.823 0.761 9.940
June 543.941 25.240 22.875 0.124 25.364
July 724.121 40.837 0.000 0.000 40.837
August 595.236 27.784 6.625 0.017 27.802
September 408.578 13.389 43.150 0.261 13.650
October 92.426 2.147 325.711 3.269 5.416
November 0.000 0.000 664.125 14.306 14.306
December 0.000 0.000 744.000 18.922 18.922
           
Annual Sum or Average 2831.445 122.720 4231.659 90.170 212.890
Minimum of Months 0.000 0.000 0.000 0.000 5.416
Maximum of Months 724.121 40.837 744.000 24.498 40.837



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 38.149 38.149
February 0.000 0.000 672.000 23.117 23.117
March 14.648 0.388 634.225 14.987 15.375
April 227.138 7.998 221.034 4.026 12.024
May 379.100 17.250 116.925 1.451 18.701
June 565.493 40.124 17.036 0.206 40.330
July 703.224 60.388 0.000 0.000 60.388
August 606.382 42.623 13.750 0.111 42.734
September 442.787 21.893 56.625 0.563 22.456
October 137.128 4.234 333.729 5.106 9.340
November 0.000 0.000 676.188 22.912 22.912
December 0.000 0.000 744.000 30.354 30.354
           
Annual Sum or Average 3075.900 194.899 4229.512 140.982 335.881
Minimum of Months 0.000 0.000 0.000 0.000 9.340
Maximum of Months 703.224 60.388 744.000 38.149 60.388



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 732.375 62.166 62.166
February 11.538 0.285 585.942 35.291 35.577
March 67.167 2.805 562.562 26.667 29.472
April 216.680 12.978 293.617 9.620 22.598
May 298.870 21.173 203.542 4.080 25.254
June 490.123 44.371 58.903 1.091 45.462
July 673.466 68.169 4.250 0.021 68.190
August 546.976 52.525 37.625 0.542 53.067
September 402.025 32.753 101.450 1.760 34.513
October 200.331 12.024 336.232 9.838 21.862
November 26.604 0.958 625.554 35.617 36.575
December 1.000 0.008 707.650 47.922 47.930
           
Annual Sum or Average 2934.779 248.050 4249.702 234.616 482.666
Minimum of Months 0.000 0.000 4.250 0.021 21.862
Maximum of Months 673.466 68.169 732.375 62.166 68.190



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 737.917 30.642 30.642
February 5.750 0.048 604.195 17.074 17.122
March 43.842 0.874 554.250 12.522 13.397
April 201.621 7.341 250.557 4.055 11.396
May 295.371 12.126 157.785 1.549 13.675
June 514.033 28.991 36.542 0.363 29.354
July 703.427 48.429 0.000 0.000 48.429
August 584.789 35.996 21.750 0.103 36.100
September 430.903 23.346 63.531 0.508 23.854
October 221.981 8.199 271.142 3.645 11.845
November 32.521 0.763 607.992 16.716 17.479
December 0.750 0.002 704.171 22.727 22.729
           
Annual Sum or Average 3034.987 166.115 4009.830 109.904 276.019
Minimum of Months 0.000 0.000 0.000 0.000 11.396
Maximum of Months 703.427 48.429 737.917 30.642 48.429



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 39.985 39.985
February 3.558 0.020 617.337 22.822 22.842
March 50.236 1.435 553.333 15.850 17.285
April 249.026 11.161 232.140 4.782 15.943
May 364.156 19.140 151.042 2.048 21.188
June 544.112 42.743 27.875 0.337 43.080
July 697.897 66.709 0.875 0.003 66.712
August 599.633 49.523 20.250 0.191 49.714
September 448.990 30.960 79.375 0.871 31.830
October 229.898 10.700 297.750 5.280 15.980
November 26.567 0.823 633.225 22.916 23.739
December 0.000 0.000 718.721 30.835 30.835
           
Annual Sum or Average 3214.073 233.215 4075.924 145.919 379.134
Minimum of Months 0.000 0.000 0.875 0.003 15.943
Maximum of Months 697.897 66.709 744.000 39.985 66.712



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 68.551 68.551
February 0.000 0.000 661.971 41.923 41.923
March 29.317 0.920 629.854 30.658 31.578
April 188.396 9.883 325.333 10.738 20.621
May 289.122 19.820 212.457 4.269 24.088
June 493.627 44.173 58.778 1.077 45.250
July 675.940 67.421 4.000 0.015 67.437
August 535.855 49.302 39.500 0.568 49.870
September 361.055 24.846 120.225 2.109 26.955
October 116.327 5.397 432.500 13.203 18.600
November 2.048 0.020 691.458 42.314 42.334
December 0.000 0.000 744.000 55.454 55.454
           
Annual Sum or Average 2691.688 221.783 4664.077 270.879 492.662
Minimum of Months 0.000 0.000 4.000 0.015 18.600
Maximum of Months 675.940 67.421 744.000 68.551 68.551



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 34.748 34.748
February 0.000 0.000 672.000 21.576 21.576
March 8.250 0.148 674.538 15.521 15.669
April 155.717 4.867 307.642 4.909 9.776
May 280.593 11.016 167.052 1.668 12.684
June 517.697 28.975 39.875 0.372 29.347
July 707.879 47.750 0.000 0.000 47.750
August 570.537 32.915 23.208 0.109 33.024
September 370.187 15.659 82.167 0.688 16.347
October 82.474 2.527 409.717 5.833 8.361
November 0.000 0.000 687.925 21.061 21.061
December 0.000 0.000 744.000 27.582 27.582
           
Annual Sum or Average 2693.332 143.857 4552.124 134.068 277.925
Minimum of Months 0.000 0.000 0.000 0.000 8.361
Maximum of Months 707.879 47.750 744.000 34.748 47.750



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 43.747 43.747
February 0.000 0.000 672.000 27.056 27.056
March 13.525 0.383 672.938 18.463 18.846
April 205.001 8.159 264.300 5.289 13.447
May 356.142 17.946 159.854 2.125 20.071
June 545.083 42.621 26.500 0.335 42.956
July 698.773 65.922 0.875 0.002 65.924
August 595.904 46.439 20.750 0.196 46.635
September 415.476 23.116 85.100 0.948 24.063
October 114.599 4.180 414.367 7.040 11.220
November 0.000 0.000 695.408 26.979 26.979
December 0.000 0.000 744.000 35.371 35.371
           
Annual Sum or Average 2944.502 208.765 4500.092 167.551 376.317
Minimum of Months 0.000 0.000 0.875 0.002 11.220
Maximum of Months 698.773 65.922 744.000 43.747 65.924



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 12.379 12.379
February 0.000 0.000 672.000 9.518 9.518
March 0.000 0.000 744.000 8.923 8.923
April 0.000 0.000 720.000 5.115 5.115
May 0.000 0.000 42.485 0.081 0.081
June 38.212 0.127 0.000 0.000 0.127
July 487.735 3.582 0.000 0.000 3.582
August 318.577 2.224 0.000 0.000 2.224
September 13.750 0.029 0.000 0.000 0.029
October 0.000 0.000 12.229 0.011 0.011
November 0.000 0.000 715.250 7.704 7.704
December 0.000 0.000 744.000 10.742 10.742
           
Annual Sum or Average 858.274 5.962 4393.965 54.474 60.436
Minimum of Months 0.000 0.000 0.000 0.000 0.011
Maximum of Months 487.735 3.582 744.000 12.379 12.379



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2082.33 0.00
February 0.00 964.85 0.00
March 0.00 497.77 0.00
April 0.00 115.85 0.00
May 0.00 5.17 0.00
June 0.00 2.08 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.95 0.00
October 0.00 71.96 0.00
November 0.00 892.93 0.00
December 0.00 1307.40 0.00
       
Annual Sum or Average 0.00 493.90 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2082.33 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2853.52 0.00
February 0.00 1691.63 0.00
March 0.00 1122.23 0.00
April 0.00 378.12 0.00
May 0.00 116.82 0.00
June 0.00 29.31 0.00
July 0.00 0.00 0.00
August 0.00 5.99 0.00
September 0.00 30.03 0.00
October 0.00 277.69 0.00
November 0.00 1524.48 0.00
December 0.00 2044.02 0.00
       
Annual Sum or Average 0.00 836.31 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2853.52 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3871.62 0.00
February 0.00 2385.67 0.00
March 0.00 1505.05 0.00
April 0.00 506.74 0.00
May 0.00 199.79 0.00
June 0.00 38.04 0.00
July 0.00 0.74 0.00
August 0.00 21.24 0.00
September 0.00 78.94 0.00
October 0.00 477.11 0.00
November 0.00 2225.21 0.00
December 0.00 2917.63 0.00
       
Annual Sum or Average 0.00 1180.97 0.00
Minimum of Months 0.00 0.74 0.00
Maximum of Months 0.00 3871.62 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4340.86 0.00
February 0.00 2910.23 0.00
March 0.00 1940.17 0.00
April 0.00 729.60 0.00
May 0.00 256.83 0.00
June 0.00 68.16 0.00
July 0.00 0.86 0.00
August 0.00 33.54 0.00
September 0.00 121.02 0.00
October 0.00 793.23 0.00
November 0.00 2717.81 0.00
December 0.00 3468.38 0.00
       
Annual Sum or Average 0.00 1442.28 0.00
Minimum of Months 0.00 0.86 0.00
Maximum of Months 0.00 4340.86 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3433.67 0.00
February 0.00 2348.17 0.00
March 0.00 1542.77 0.00
April 0.00 520.96 0.00
May 0.00 145.94 0.00
June 0.00 32.79 0.00
July 0.00 0.00 0.00
August 0.00 7.86 0.00
September 0.00 52.44 0.00
October 0.00 522.62 0.00
November 0.00 2102.22 0.00
December 0.00 2675.82 0.00
       
Annual Sum or Average 0.00 1110.11 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3433.67 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4432.51 0.00
February 0.00 3016.64 0.00
March 0.00 1844.91 0.00
April 0.00 588.31 0.00
May 0.00 215.51 0.00
June 0.00 38.99 0.00
July 0.00 0.66 0.00
August 0.00 23.10 0.00
September 0.00 91.62 0.00
October 0.00 657.66 0.00
November 0.00 2772.42 0.00
December 0.00 3537.86 0.00
       
Annual Sum or Average 0.00 1428.18 0.00
Minimum of Months 0.00 0.66 0.00
Maximum of Months 0.00 4432.51 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3342.01 0.00
February 0.00 1989.93 0.00
March 0.00 1314.45 0.00
April 0.00 445.21 0.00
May 0.00 145.49 0.00
June 0.00 37.00 0.00
July 0.00 0.00 0.00
August 0.00 14.16 0.00
September 0.00 55.59 0.00
October 0.00 406.68 0.00
November 0.00 1860.60 0.00
December 0.00 2487.33 0.00
       
Annual Sum or Average 0.00 1004.61 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3342.01 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2400.87 0.00
February 0.00 1380.60 0.00
March 0.00 885.82 0.00
April 0.00 260.27 0.00
May 0.00 74.96 0.00
June 0.00 14.54 0.00
July 0.00 0.00 0.00
August 0.00 1.64 0.00
September 0.00 18.01 0.00
October 0.00 193.95 0.00
November 0.00 1256.55 0.00
December 0.00 1692.85 0.00
       
Annual Sum or Average 0.00 679.15 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2400.87 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3432.20 0.00
February 0.00 2069.04 0.00
March 0.00 1262.63 0.00
April 0.00 371.52 0.00
May 0.00 138.29 0.00
June 0.00 20.97 0.00
July 0.00 0.00 0.00
August 0.00 10.53 0.00
September 0.00 51.22 0.00
October 0.00 367.97 0.00
November 0.00 1943.29 0.00
December 0.00 2563.04 0.00
       
Annual Sum or Average 0.00 1015.23 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3432.20 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3886.03 0.00
February 0.00 2561.76 0.00
March 0.00 1659.36 0.00
April 0.00 560.94 0.00
May 0.00 181.48 0.00
June 0.00 41.79 0.00
July 0.00 0.00 0.00
August 0.00 19.81 0.00
September 0.00 86.24 0.00
October 0.00 654.93 0.00
November 0.00 2413.32 0.00
December 0.00 3095.09 0.00
       
Annual Sum or Average 0.00 1258.07 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3886.03 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2952.91 0.00
February 0.00 1977.76 0.00
March 0.00 1241.37 0.00
April 0.00 360.28 0.00
May 0.00 91.75 0.00
June 0.00 15.47 0.00
July 0.00 0.00 0.00
August 0.00 2.11 0.00
September 0.00 32.56 0.00
October 0.00 394.02 0.00
November 0.00 1781.96 0.00
December 0.00 2280.78 0.00
       
Annual Sum or Average 0.00 923.11 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2952.91 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3975.43 0.00
February 0.00 2667.09 0.00
March 0.00 1561.72 0.00
April 0.00 433.50 0.00
May 0.00 151.20 0.00
June 0.00 22.19 0.00
July 0.00 0.00 0.00
August 0.00 11.52 0.00
September 0.00 60.59 0.00
October 0.00 532.09 0.00
November 0.00 2467.12 0.00
December 0.00 3163.14 0.00
       
Annual Sum or Average 0.00 1247.75 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3975.43 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4611.08 0.00
February 0.00 2898.14 0.00
March 0.00 1977.97 0.00
April 0.00 737.34 0.00
May 0.00 302.65 0.00
June 0.00 83.60 0.00
July 0.00 1.58 0.00
August 0.00 40.20 0.00
September 0.00 134.88 0.00
October 0.00 729.73 0.00
November 0.00 2729.88 0.00
December 0.00 3554.55 0.00
       
Annual Sum or Average 0.00 1478.00 0.00
Minimum of Months 0.00 1.58 0.00
Maximum of Months 0.00 4611.08 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3642.20 0.00
February 0.00 2246.90 0.00
March 0.00 1488.44 0.00
April 0.00 498.02 0.00
May 0.00 184.15 0.00
June 0.00 44.57 0.00
July 0.00 0.00 0.00
August 0.00 12.28 0.00
September 0.00 62.42 0.00
October 0.00 433.32 0.00
November 0.00 2053.16 0.00
December 0.00 2701.40 0.00
       
Annual Sum or Average 0.00 1109.52 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3642.20 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4719.63 0.00
February 0.00 2982.39 0.00
March 0.00 1870.80 0.00
April 0.00 583.22 0.00
May 0.00 241.74 0.00
June 0.00 41.13 0.00
July 0.00 0.31 0.00
August 0.00 22.56 0.00
September 0.00 106.18 0.00
October 0.00 623.28 0.00
November 0.00 2795.11 0.00
December 0.00 3639.57 0.00
       
Annual Sum or Average 0.00 1462.82 0.00
Minimum of Months 0.00 0.31 0.00
Maximum of Months 0.00 4719.63 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5111.59 0.00
February 0.00 3461.01 0.00
March 0.00 2286.06 0.00
April 0.00 827.36 0.00
May 0.00 318.29 0.00
June 0.00 83.01 0.00
July 0.00 1.13 0.00
August 0.00 42.32 0.00
September 0.00 162.52 0.00
October 0.00 984.51 0.00
November 0.00 3260.42 0.00
December 0.00 4135.05 0.00
       
Annual Sum or Average 0.00 1715.49 0.00
Minimum of Months 0.00 1.13 0.00
Maximum of Months 0.00 5111.59 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4168.08 0.00
February 0.00 2865.42 0.00
March 0.00 1861.78 0.00
April 0.00 608.47 0.00
May 0.00 200.12 0.00
June 0.00 46.15 0.00
July 0.00 0.00 0.00
August 0.00 13.12 0.00
September 0.00 85.29 0.00
October 0.00 699.74 0.00
November 0.00 2610.49 0.00
December 0.00 3308.48 0.00
       
Annual Sum or Average 0.00 1365.85 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4168.08 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5232.80 0.00
February 0.00 3583.06 0.00
March 0.00 2208.49 0.00
April 0.00 653.69 0.00
May 0.00 254.20 0.00
June 0.00 41.35 0.00
July 0.00 0.24 0.00
August 0.00 23.43 0.00
September 0.00 117.13 0.00
October 0.00 842.09 0.00
November 0.00 3334.69 0.00
December 0.00 4230.92 0.00
       
Annual Sum or Average 0.00 1702.16 0.00
Minimum of Months 0.00 0.24 0.00
Maximum of Months 0.00 5232.80 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3060.44 0.00
February 0.00 2605.21 0.00
March 0.00 2205.98 0.00
April 0.00 1306.67 0.00
May 0.00 20.04 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 2.72 0.00
November 0.00 1968.19 0.00
December 0.00 2655.75 0.00
       
Annual Sum or Average 0.00 1143.79 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3060.44 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.16
May 0.00 0.00 0.22
June 0.00 0.00 0.37
July 0.00 0.00 0.48
August 0.00 0.00 0.41
September 0.00 0.00 0.31
October 0.00 0.00 0.16
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.14
July 0.00 0.00 0.23
August 0.00 0.00 0.18
September 0.00 0.00 0.13
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.10
June 0.00 0.00 0.22
July 0.00 0.00 0.33
August 0.00 0.00 0.25
September 0.00 0.00 0.18
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.22
July 0.00 0.00 0.31
August 0.00 0.00 0.23
September 0.00 0.00 0.12
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.13
July 0.00 0.00 0.21
August 0.00 0.00 0.14
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.08
June 0.00 0.00 0.21
July 0.00 0.00 0.32
August 0.00 0.00 0.22
September 0.00 0.00 0.11
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.12
June 0.00 0.00 0.23
July 0.00 0.00 0.33
August 0.00 0.00 0.27
September 0.00 0.00 0.19
October 0.00 0.00 0.08
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.23
August 0.00 0.00 0.18
September 0.00 0.00 0.14
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.11
June 0.00 0.00 0.23
July 0.00 0.00 0.34
August 0.00 0.00 0.26
September 0.00 0.00 0.18
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.10
June 0.00 0.00 0.22
July 0.00 0.00 0.32
August 0.00 0.00 0.23
September 0.00 0.00 0.12
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.22
August 0.00 0.00 0.15
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.09
June 0.00 0.00 0.22
July 0.00 0.00 0.33
August 0.00 0.00 0.23
September 0.00 0.00 0.12
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.11
June 0.00 0.00 0.24
July 0.00 0.00 0.36
August 0.00 0.00 0.28
September 0.00 0.00 0.18
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.16
July 0.00 0.00 0.26
August 0.00 0.00 0.19
September 0.00 0.00 0.13
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.10
June 0.00 0.00 0.24
July 0.00 0.00 0.36
August 0.00 0.00 0.27
September 0.00 0.00 0.17
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.11
June 0.00 0.00 0.24
July 0.00 0.00 0.35
August 0.00 0.00 0.26
September 0.00 0.00 0.13
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.06
June 0.00 0.00 0.16
July 0.00 0.00 0.26
August 0.00 0.00 0.17
September 0.00 0.00 0.09
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.10
June 0.00 0.00 0.24
July 0.00 0.00 0.36
August 0.00 0.00 0.25
September 0.00 0.00 0.13
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.02
August 0.00 0.00 0.01
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.02



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:44:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1289.06 959.74
February 0.00 0.00 1314.38 883.89
March 0.00 0.00 1277.28 950.97
April 0.00 0.00 1193.40 859.86
May 0.00 0.00 1078.77 803.17
June 0.00 0.00 966.74 696.54
July 0.00 0.00 888.71 661.67
August 0.00 0.00 859.71 640.08
September 0.00 0.00 895.90 645.51
October 0.00 0.00 981.68 730.89
November 0.00 0.00 1098.22 791.28
December 0.00 0.00 1210.26 901.07
         
Annual Sum or Average 0.00 0.00 1086.52 9524.67
Minimum of Months 0.00 0.00 859.71 640.08
Maximum of Months 0.00 0.00 1314.38 959.74