Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44
Tabular Output Report in Format: HTML
Building: MF+CZ5BWH+USA_ID_Boise.Air.Terminal.726810+oilfurnace+unheatedbsmt+IECC_2012
Environment: ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Simulation Timestamp: 2019-02-14 08:45:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 954131.67 | 24.46 | 44.15 |
Net Site Energy | 954131.67 | 24.46 | 44.15 |
Total Source Energy | 1932107.19 | 49.53 | 89.41 |
Net Source Energy | 1932107.19 | 49.53 | 89.41 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 230760.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 25477.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 292344.94 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 431026.62 | 523105.05 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 230760.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 52705.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25477.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 292344.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 3.62 | 24.21 | 0.00 | 0.00 | 0.00 | 17.48 |
Other | 13.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 19.95 | 24.21 | 0.00 | 0.00 | 0.00 | 17.48 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.00 | 13.41 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.05 | 13.41 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 431026.623 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 431026.623 | 100.00 |
Total On-Site and Utility Electric Sources | 431026.623 | 100.00 |
Total Electricity End Uses | 431026.623 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 966.75 |
Time Setpoint Not Met During Occupied Cooling | 29.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 369.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:44 |
RunPeriod | ANNUAL |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Latitude [deg] | 43.62 |
Longitude [deg] | -116.2 |
Elevation [ft] | 2299.98 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58419.71 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6659 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 141767.99 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 29-JUL-18:15 | 13-JAN-08:15 | - | - | - | 07-JAN-08:30 |
Heating | 0.00 | 181.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 115.56 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 124.50 | 297.15 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 181.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 115.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 250143.96 | 0.00 | 0.00 | 0.00 |
Cooling | 166917.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 80688.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 316901.91 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1365061.32 | 567045.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 11.58 | 0.00 | 0.00 | 0.00 |
Cooling | 7.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.66 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 63.17 | 26.24 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 11.58 | 0.00 | 0.00 | 0.00 |
Cooling | 7.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.66 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 63.17 | 26.24 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 2.66 | 0.00 | 2.66 | Wetbulb [F] | 452.78 | 120.00 |
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 98.06 | 30.06 | 64.22 | Wetbulb [F] | 826.81 | 330.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.064 | 0.066 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.064 | 0.066 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.064 | 0.066 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.064 | 0.066 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.320 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.320 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.320 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 400993.73 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 24844.10 | 19841.87 | 5002.23 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6277.49 | 5013.55 | 1263.94 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8526.57 | 6809.79 | 1716.78 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12799.69 | 10222.54 | 2577.15 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5761.04 | 4601.09 | 1159.96 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8521.94 | 6806.09 | 1715.85 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13316.96 | 10635.66 | 2681.30 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6455.76 | 5155.93 | 1299.83 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8473.96 | 6767.77 | 1706.19 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12774.59 | 10202.50 | 2572.10 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5967.70 | 4766.13 | 1201.56 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8481.58 | 6773.86 | 1707.72 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14373.51 | 11479.48 | 2894.03 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7588.25 | 6060.40 | 1527.85 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9034.10 | 7215.13 | 1818.97 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14298.37 | 11419.47 | 2878.90 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7518.67 | 6004.83 | 1513.85 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8913.07 | 7118.47 | 1794.60 | 0.80 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 49509.40 | 52797.95 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 14833.38 | 14503.73 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19035.31 | 19160.35 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 27018.46 | 27969.12 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13868.55 | 13429.31 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 19026.66 | 19150.79 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 27983.55 | 29030.18 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 15165.86 | 14872.64 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18936.25 | 19049.67 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 26970.34 | 27914.47 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 14254.12 | 13858.20 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 18950.48 | 19065.41 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29958.71 | 31203.92 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 17282.14 | 17220.34 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19983.49 | 20207.07 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 29818.33 | 31049.42 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 17152.15 | 17076.31 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 19757.37 | 19957.20 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 931.93 | 466.70 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 235.47 | 117.92 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 319.84 | 160.17 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 480.13 | 240.45 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 216.10 | 108.22 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 319.67 | 160.09 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 499.53 | 250.16 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 242.16 | 121.27 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 317.87 | 159.19 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 479.19 | 239.97 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 223.85 | 112.11 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 318.15 | 159.33 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 539.16 | 270.01 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 284.64 | 142.55 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 338.88 | 169.71 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 536.35 | 268.60 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 282.03 | 141.24 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 334.34 | 167.43 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 40.323007 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 20136.33 | 20136.33 | 16.77 | 931.925 | 931.925 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00801 | 89.72 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5087.96 | 5087.96 | 4.24 | 235.474 | 235.474 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00802 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6910.90 | 6910.90 | 5.76 | 319.840 | 319.840 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 74.98 | 74.98 | 0.00787 | 87.76 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10374.25 | 10374.25 | 8.64 | 480.128 | 480.128 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00802 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4669.37 | 4669.37 | 3.89 | 216.102 | 216.102 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00804 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6907.15 | 6907.15 | 5.75 | 319.666 | 319.666 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 74.98 | 74.98 | 0.00787 | 87.76 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10793.46 | 10793.46 | 8.99 | 499.531 | 499.531 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00805 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5232.43 | 5232.43 | 4.36 | 242.162 | 242.162 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00810 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6868.25 | 6868.25 | 5.72 | 317.866 | 317.866 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 74.98 | 74.98 | 0.00791 | 88.89 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10353.87 | 10353.87 | 8.62 | 479.187 | 479.187 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00805 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4836.85 | 4836.85 | 4.03 | 223.854 | 223.854 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00811 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6874.42 | 6874.42 | 5.73 | 318.152 | 318.152 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 74.98 | 74.98 | 0.00791 | 88.89 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7224.13 | 7224.13 | 6.02 | 334.337 | 334.337 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00801 | 89.72 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7322.27 | 7322.27 | 6.10 | 338.877 | 338.877 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00796 | 92.35 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11649.84 | 11649.84 | 9.70 | 539.164 | 539.164 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00802 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6093.94 | 6093.94 | 5.08 | 282.032 | 282.032 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00805 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6150.33 | 6150.33 | 5.12 | 284.642 | 284.642 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00805 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11588.94 | 11588.94 | 9.65 | 536.345 | 536.345 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00802 | 88.59 | 0.00627 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 598.93 | 598.93 | 0.50 | 11.853 | 44.995 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00239 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8240.93 | 8240.93 | 6.86 | 163.057 | 163.057 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00595 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10561.83 | 10561.83 | 8.80 | 208.976 | 208.976 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00622 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10565.56 | 10565.56 | 8.80 | 209.049 | 209.049 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00622 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8241.75 | 8241.75 | 6.86 | 163.073 | 163.073 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00595 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10558.93 | 10558.93 | 8.80 | 208.918 | 208.918 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00622 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9445.06 | 9445.06 | 7.87 | 186.890 | 186.890 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00640 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7121.43 | 7121.43 | 5.93 | 140.914 | 140.914 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00613 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9450.50 | 9450.50 | 7.87 | 186.998 | 186.998 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00640 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9450.31 | 9450.31 | 7.87 | 186.994 | 186.994 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00640 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7121.56 | 7121.56 | 5.93 | 140.917 | 140.917 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00613 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9447.72 | 9447.72 | 7.87 | 186.942 | 186.942 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00640 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 11976.81 | 11976.81 | 9.98 | 236.972 | 236.972 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00638 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 11979.50 | 11979.50 | 9.98 | 237.025 | 237.025 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00638 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11974.49 | 11974.49 | 9.97 | 236.926 | 236.926 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00638 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9649.39 | 9649.39 | 8.04 | 190.925 | 190.925 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9650.09 | 9650.09 | 8.04 | 190.939 | 190.939 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00617 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11976.26 | 11976.26 | 9.98 | 236.961 | 236.961 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00638 | 2.66 | 0.00098 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 | 931.93 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 | 235.47 | 163.06 | 163.06 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 | 319.84 | 208.98 | 208.98 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 | 480.13 | 209.05 | 209.05 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 | 216.10 | 163.07 | 163.07 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 | 319.67 | 208.92 | 208.92 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 | 499.53 | 186.89 | 186.89 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 | 242.16 | 140.91 | 140.91 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 | 317.87 | 187.00 | 187.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 | 479.19 | 186.99 | 186.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 | 223.85 | 140.92 | 140.92 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 | 318.15 | 186.94 | 186.94 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 539.16 | 539.16 | 236.93 | 236.93 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 284.64 | 284.64 | 190.94 | 190.94 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 338.88 | 338.88 | 237.03 | 237.03 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 536.35 | 536.35 | 236.96 | 236.96 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 282.03 | 282.03 | 190.93 | 190.93 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 334.34 | 334.34 | 236.97 | 236.97 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 919.00 | 6105.25 | 7.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 356.25 | 6236.00 | 35.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1014.00 | 5876.25 | 31.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 961.00 | 6601.75 | 211.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 173.50 | 6846.00 | 0.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 754.25 | 6307.75 | 37.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1130.25 | 5877.50 | 21.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 491.25 | 5898.75 | 8.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1167.00 | 5651.75 | 22.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1040.25 | 6352.25 | 173.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 299.00 | 6465.25 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 901.00 | 6059.50 | 28.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1098.25 | 6074.25 | 136.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1234.75 | 5814.50 | 102.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1219.50 | 6127.50 | 121.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 520.25 | 6465.50 | 29.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 630.00 | 6133.25 | 20.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1213.75 | 6378.50 | 235.50 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1988.75 | 7126.00 | 369.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 6.00 | 0.00 | 6.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 34.00 | 14.75 | 34.00 | 14.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 120.00 | 0.00 | 120.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 418.00 | 16.50 | 418.00 | 16.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 40.00 | 18.75 | 40.00 | 18.75 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16.25 | 0.00 | 16.25 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 48.50 | 13.25 | 48.50 | 13.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3.25 | 12.25 | 3.25 | 12.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 136.50 | 1.75 | 136.50 | 1.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 414.75 | 14.50 | 414.75 | 14.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 26.50 | 14.75 | 26.50 | 14.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 33.50 | 0.00 | 33.50 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23.00 | 15.25 | 23.00 | 15.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 56.50 | 17.50 | 56.50 | 17.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 134.25 | 14.25 | 134.25 | 14.25 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 15.50 | 15.50 | 15.50 | 15.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5.75 | 14.25 | 5.75 | 14.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 313.00 | 14.75 | 313.00 | 14.75 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 966.75 | 29.75 | 966.75 | 29.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.117 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.101 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.115 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.114 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.101 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.115 | 0.000 | 0.276 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.276 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.037 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.037 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.115 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.115 | 0.000 | 0.276 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.115 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.101 | 0.000 | 0.276 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.101 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.115 | 0.000 | 0.276 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1867 |
Defaulted Fields | 446 |
Fields with Defaults | 4744 |
Autosized Fields | 328 |
Autosizable Fields | 438 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Fans:Electricity | 7461.88 | 146.99 | 01-APR-00:15 | 3453.76 | 31-JUL-18:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
ElectricityPurchased:Plant | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
Cogeneration:ElectricityPurchased | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
ElectricityNet:Plant | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
Cogeneration:ElectricityNet | 126237.24 | 7370.91 | 18-JUN-03:15 | 36462.88 | 29-JUL-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 22897.99 | 547.47 | 01-APR-00:15 | 17034.57 | 31-JUL-18:00 |
General:Fans:Electricity | 7461.88 | 146.99 | 01-APR-00:15 | 3453.76 | 31-JUL-18:15 |
Cooling:Electricity | 15436.11 | 0.00 | 04-JAN-05:00 | 13587.94 | 31-JUL-18:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 5231.05 | 0.00 | 03-MAR-17:15 | 296942.53 | 13-JAN-08:15 |
Gas:Plant | 5231.05 | 0.00 | 03-MAR-17:15 | 296942.53 | 13-JAN-08:15 |
WaterSystems:Gas | 2923.45 | 0.00 | 01-JAN-00:15 | 115890.83 | 11-FEB-09:00 |
Water Heater:WaterSystems:Gas | 2923.45 | 0.00 | 01-JAN-00:15 | 115890.83 | 11-FEB-09:00 |
Heating:Gas | 2307.60 | 0.00 | 03-MAR-17:00 | 191875.08 | 13-JAN-08:30 |
Boiler:Heating:Gas | 2307.60 | 0.00 | 03-MAR-17:00 | 191875.08 | 13-JAN-08:30 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
Water:Plant | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
WaterSystems:Water | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
MainsWater:Plant | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 10-FEB-02:15 | 0.18 | 07-JAN-08:30 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 340285.43 | 1291.68 | 14-AUG-02:45 | 193096.73 | 13-JAN-08:30 |
PlantLoopHeatingDemand:Plant | 155702.00 | 1291.68 | 14-AUG-02:45 | 41487.87 | 11-FEB-08:30 |
WaterSystems:PlantLoopHeatingDemand | 155702.00 | 1291.68 | 14-AUG-02:45 | 41487.87 | 11-FEB-08:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1156600.07 | 16188.51 | 27-AUG-02:15 | 506217.67 | 13-JAN-08:30 |
EnergyTransfer:Building | 402854.32 | 6871.31 | 30-APR-01:15 | 159620.88 | 13-JAN-08:30 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 193941.88 | 0.00 | 03-MAR-17:15 | 159620.88 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 208912.44 | 0.00 | 04-JAN-05:00 | 151334.43 | 22-JUL-18:30 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 70710.42 | 0.00 | 04-JAN-05:00 | 20709.21 | 22-JUN-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.15 | 0.00 | 01-JAN-00:15 | 334.15 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 70710.27 | 0.00 | 04-JAN-05:00 | 20709.21 | 22-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13901.47 | 0.00 | 06-JAN-12:45 | 13520.55 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7668.21 | 0.00 | 06-JAN-12:45 | 13520.55 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6233.26 | 0.00 | 01-JAN-00:15 | 5442.42 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20788.95 | 0.00 | 06-JAN-13:45 | 10259.56 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11313.51 | 0.00 | 06-JAN-13:45 | 10259.56 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9475.45 | 0.00 | 01-JAN-00:15 | 7524.06 | 22-JUL-09:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21661.10 | 0.00 | 03-FEB-17:15 | 10934.27 | 14-JUL-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13811.64 | 0.00 | 03-FEB-17:15 | 9776.71 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7849.47 | 0.00 | 01-JAN-00:15 | 10934.27 | 14-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15175.90 | 0.00 | 03-MAR-16:30 | 7587.51 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 10724.26 | 0.00 | 03-MAR-16:30 | 7587.51 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4451.64 | 0.00 | 01-JAN-00:15 | 5002.06 | 21-JUN-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21212.48 | 0.00 | 02-MAR-10:15 | 9781.91 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13677.93 | 0.00 | 02-MAR-10:15 | 9781.91 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7534.56 | 0.00 | 01-JAN-00:15 | 7545.83 | 22-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 19373.80 | 0.00 | 01-JAN-15:45 | 11360.08 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8673.73 | 0.00 | 01-JAN-15:45 | 8592.87 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10700.07 | 0.00 | 01-JAN-00:15 | 11360.08 | 20-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 13239.87 | 0.00 | 06-JAN-12:45 | 7376.03 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6243.40 | 0.00 | 06-JAN-12:45 | 7376.03 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6996.48 | 0.00 | 01-JAN-00:15 | 5612.95 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 19641.36 | 0.00 | 06-JAN-13:00 | 8750.06 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9332.19 | 0.00 | 06-JAN-13:00 | 8750.06 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10309.17 | 0.00 | 01-JAN-00:15 | 7473.54 | 22-JUL-09:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20122.20 | 0.00 | 03-FEB-17:15 | 10899.53 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11622.99 | 0.00 | 03-FEB-17:15 | 8724.51 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8499.20 | 0.00 | 01-JAN-00:15 | 10899.53 | 20-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13717.56 | 0.00 | 10-FEB-18:15 | 6525.97 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8545.77 | 0.00 | 10-FEB-18:15 | 6525.97 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5171.79 | 0.00 | 01-JAN-00:15 | 5255.02 | 21-JUL-21:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 19845.62 | 0.00 | 02-MAR-10:15 | 8729.93 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11513.38 | 0.00 | 02-MAR-10:15 | 8729.93 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8332.23 | 0.00 | 01-JAN-00:15 | 7510.72 | 22-JUL-09:30 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 24588.73 | 0.00 | 03-MAR-17:15 | 11018.55 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 15512.65 | 0.00 | 03-MAR-17:15 | 11018.55 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 9076.08 | 0.00 | 01-JAN-00:15 | 7623.58 | 21-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23530.92 | 0.00 | 04-FEB-13:30 | 10989.93 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 13327.27 | 0.00 | 04-FEB-13:30 | 10989.93 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 10203.66 | 0.00 | 01-JAN-00:15 | 7726.61 | 21-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24144.62 | 0.00 | 06-JAN-15:30 | 12245.02 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 13537.03 | 0.00 | 06-JAN-15:30 | 10949.27 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 10607.59 | 0.00 | 01-JAN-00:15 | 12245.02 | 20-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 18660.15 | 0.00 | 03-MAR-17:00 | 8827.37 | 13-JAN-08:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 12489.92 | 0.00 | 03-MAR-17:00 | 8827.37 | 13-JAN-08:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 6170.22 | 0.00 | 01-JAN-00:15 | 6611.00 | 21-JUL-21:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 17295.86 | 0.00 | 23-JAN-14:30 | 8819.05 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 10110.35 | 0.00 | 23-JAN-14:30 | 8819.05 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 7185.51 | 0.00 | 01-JAN-00:15 | 6672.61 | 21-JUL-21:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25243.30 | 0.00 | 05-FEB-17:15 | 12193.02 | 14-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 15837.51 | 0.00 | 05-FEB-17:15 | 11016.16 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9405.79 | 0.00 | 01-JAN-00:15 | 12193.02 | 14-JUL-18:30 |
EnergyTransfer:Plant | 340310.09 | 1291.68 | 14-AUG-02:45 | 192447.31 | 13-JAN-08:30 |
WaterSystems:EnergyTransfer | 155702.00 | 1291.68 | 14-AUG-02:45 | 41487.87 | 11-FEB-08:30 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 155702.00 | 1291.68 | 14-AUG-02:45 | 41487.87 | 11-FEB-08:30 |
EnergyTransfer:HVAC | 413435.66 | 7160.30 | 14-JUN-06:00 | 166729.52 | 12-JUL-19:30 |
HeatingCoils:EnergyTransfer | 184583.43 | 0.00 | 03-MAR-17:00 | 154149.49 | 13-JAN-08:30 |
PlantLoopHeatingDemand:HVAC | 184583.43 | 0.00 | 03-MAR-17:00 | 154149.49 | 13-JAN-08:30 |
HeatingCoils:PlantLoopHeatingDemand | 184583.43 | 0.00 | 03-MAR-17:00 | 154149.49 | 13-JAN-08:30 |
CoolingCoils:EnergyTransfer | 228852.23 | 0.00 | 04-JAN-05:00 | 166729.52 | 12-JUL-19:30 |
Boilers:EnergyTransfer | 184608.09 | 0.00 | 03-MAR-17:00 | 153500.07 | 13-JAN-08:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.150 | -5888.58 | 0.000 | 0.000 | 2873.983 | 2456.001 | 10405.511 | 9879.888 | 0.000 | 564.387 | 65308.999 | 0.000 | -6450.84 | 0.000 | -14327.89 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 7668.133 | -519.09 | 0.000 | 0.000 | 3043.205 | 2456.001 | 10405.511 | 4396.239 | 0.000 | 544.977 | 0.000 | 0.000 | -2467.98 | 0.000 | -12749.18 | -7063.66 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 11313.390 | -789.09 | 0.000 | 0.000 | 3051.751 | 2456.001 | 10405.511 | 10063.747 | 0.000 | 564.683 | 0.000 | 0.000 | -5880.98 | 0.000 | -13258.42 | -9240.27 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 13811.512 | -653.68 | 0.000 | 0.000 | 3067.830 | 2456.001 | 10405.511 | 6855.799 | 0.000 | 563.889 | 0.000 | 0.000 | -6283.80 | 0.000 | -13037.11 | -9990.16 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 10724.167 | -370.72 | 0.000 | 0.000 | 3060.164 | 2456.001 | 10405.511 | 1078.816 | 0.000 | 545.022 | 0.000 | 0.000 | -2627.73 | 0.000 | -12624.16 | -8566.15 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 13677.811 | -627.46 | 0.000 | 0.000 | 3063.374 | 2456.001 | 10405.511 | 6844.177 | 0.000 | 564.769 | 0.000 | 0.000 | -6035.37 | 0.000 | -13156.59 | -10285.15 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 8673.636 | -891.08 | 0.000 | 0.000 | 3034.511 | 2456.001 | 10405.511 | 9974.588 | 0.000 | 473.473 | 0.000 | 0.000 | -6240.68 | 0.000 | -10979.56 | -7097.43 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6243.329 | -582.65 | 0.000 | 0.000 | 3024.246 | 2456.001 | 10405.511 | 4387.605 | 0.000 | 454.717 | 0.000 | 0.000 | -2506.98 | 0.000 | -10519.60 | -6948.35 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 9332.099 | -858.52 | 0.000 | 0.000 | 3039.216 | 2456.001 | 10405.511 | 10037.982 | 0.000 | 473.966 | 0.000 | 0.000 | -5973.35 | 0.000 | -10994.81 | -8467.47 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11622.891 | -707.79 | 0.000 | 0.000 | 3055.497 | 2456.001 | 10405.511 | 6837.723 | 0.000 | 473.583 | 0.000 | 0.000 | -6380.14 | 0.000 | -10820.13 | -9151.73 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8545.695 | -430.69 | 0.000 | 0.000 | 3046.097 | 2456.001 | 10405.511 | 1075.095 | 0.000 | 454.763 | 0.000 | 0.000 | -2666.74 | 0.000 | -10395.05 | -7749.57 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11513.287 | -693.89 | 0.000 | 0.000 | 3052.169 | 2456.001 | 10405.511 | 6822.854 | 0.000 | 474.120 | 0.000 | 0.000 | -6124.79 | 0.000 | -10908.06 | -9358.87 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 15512.524 | -755.83 | 0.000 | 0.000 | 3057.187 | 2456.001 | 10405.511 | 6839.014 | 0.000 | 560.093 | 0.000 | 0.000 | -6109.82 | 0.000 | -13203.88 | -10440.57 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13327.143 | -849.73 | 0.000 | 0.000 | 3048.436 | 2456.001 | 10405.511 | 10078.946 | 0.000 | 560.024 | 0.000 | 0.000 | -5941.26 | 0.000 | -13275.94 | -10455.23 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13536.900 | -883.38 | 0.000 | 0.000 | 3049.151 | 2456.001 | 10405.511 | 10033.303 | 0.000 | 560.133 | 0.000 | 0.000 | -6167.83 | 0.000 | -13222.02 | -10043.56 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 12489.822 | -513.84 | 0.000 | 0.000 | 3053.053 | 2456.001 | 10405.511 | 1078.795 | 0.000 | 541.634 | 0.000 | 0.000 | -2654.95 | 0.000 | -12686.14 | -8513.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 10110.257 | -598.39 | 0.000 | 0.000 | 3040.493 | 2456.001 | 10405.511 | 4405.105 | 0.000 | 541.424 | 0.000 | 0.000 | -2485.99 | 0.000 | -12773.74 | -8513.56 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 15837.376 | -783.29 | 0.000 | 0.000 | 3059.674 | 2456.001 | 10405.511 | 6840.502 | 0.000 | 560.413 | 0.000 | 0.000 | -6361.10 | 0.000 | -13123.39 | -10269.20 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4822.469 | 42020.268 | 0.000 | 0.000 | 0.000 | -46842.74 | -0.69 |
Total Facility | 0.000 | 0.000 | 193940.121 | -17397.72 | 0.000 | 0.000 | 54720.037 | 44208.020 | 187299.191 | 117530.179 | 0.000 | 14298.540 | 107329.267 | 0.000 | -89360.35 | 0.000 | -268898.41 | -152155.11 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 22-JUN-18:40 | 0.00 | 0.00 | 0.00 | -1.7 | 0.00 | 0.00 | 427.00 | 721.37 | 1713.78 | 7630.96 | 0.00 | 1163.07 | 9099.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21-JUL-20:48 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.88 | 799.44 | 1616.68 | 42.26 | 0.00 | 526.16 | 2106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-JUL-09:17 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.16 | 103.05 | 1113.11 | 7254.06 | 0.00 | 537.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1598.6 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 14-JUL-18:33 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 423.91 | 721.37 | 1713.78 | 7227.91 | 0.00 | 1027.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157.7 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21-JUL-20:48 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 425.07 | 799.44 | 1616.68 | 44.91 | 0.00 | 520.01 | 1661.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22-JUL-08:47 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.53 | 151.14 | 1168.32 | 7698.58 | 0.00 | 465.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2130.3 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 20-JUL-18:19 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 424.81 | 721.37 | 1713.78 | 7784.94 | 0.00 | 903.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -168.5 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21-JUL-20:48 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.82 | 799.44 | 1616.68 | 43.69 | 0.00 | 451.92 | 2352.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22-JUL-09:17 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.16 | 103.05 | 1113.11 | 7246.09 | 0.00 | 462.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1566.0 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 22-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 423.50 | 799.44 | 1651.33 | 5298.71 | 0.00 | 766.19 | 2011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-JUN-20:47 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.01 | 799.44 | 1616.68 | 51.33 | 0.00 | 457.47 | 1937.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 22-JUL-09:19 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.16 | 103.05 | 1113.11 | 7107.99 | 0.00 | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1390.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21-JUL-20:35 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 423.90 | 799.44 | 1616.68 | 178.51 | 0.00 | 684.58 | 4017.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21-JUL-20:35 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 424.17 | 799.44 | 1616.68 | 180.52 | 0.00 | 685.72 | 4117.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 20-JUL-18:19 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 424.62 | 721.37 | 1713.78 | 7762.40 | 0.00 | 1095.90 | 549.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21-JUN-20:47 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.01 | 799.44 | 1616.68 | 41.92 | 0.00 | 519.25 | 3238.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21-JUL-20:48 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 420.44 | 799.44 | 1616.68 | 32.30 | 0.00 | 500.83 | 3311.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 20-JUL-18:19 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 424.57 | 721.37 | 1713.78 | 7939.68 | 0.00 | 1095.58 | 310.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-18:20 | 0.00 | 0.00 | 0.00 | -12.6 | 0.00 | 0.00 | 7541.79 | 12984.58 | 31240.86 | 62667.49 | 0.00 | 21156.48 | 26882.32 | 0.00 | 0.00 | 0.00 | -10799.8 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13-JAN-08:04 | 0.00 | 0.00 | 775.80 | 0.00 | 0.00 | 0.00 | 214.34 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 5804.14 | 0.00 | -2725.1 | 0.00 | -5366.2 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13-JAN-08:04 | 0.00 | 0.00 | 14341.94 | 0.00 | 0.00 | 0.00 | 287.46 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -937.8 | 0.00 | -4033.6 | -10955.0 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-DEC-17:35 | 0.00 | 0.00 | 10761.85 | 0.00 | 0.00 | 0.00 | 300.93 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1724.2 | 0.00 | -2708.7 | -8822.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11-DEC-16:10 | 0.00 | 0.00 | 19589.22 | 0.00 | 0.00 | 0.00 | 176.68 | 384.73 | 1343.91 | 2035.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2381.9 | -21148.0 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 25-JAN-15:58 | 0.00 | 0.00 | 12033.11 | 0.00 | 0.00 | 0.00 | 127.31 | 178.62 | 1141.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -403.5 | 0.00 | -2688.6 | -10388.0 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13-JAN-08:01 | 0.00 | 0.00 | 9790.83 | 0.00 | 0.00 | 0.00 | 215.06 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2716.4 | 0.00 | -5365.9 | -3220.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28-MAR-10:09 | 0.00 | 0.00 | 18877.35 | 0.00 | 0.00 | 0.00 | 133.06 | 103.05 | 1079.31 | 1330.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1316.3 | -20206.6 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 13-JAN-08:03 | 0.00 | 0.00 | 7387.63 | 0.00 | 0.00 | 0.00 | 215.04 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1105.9 | 0.00 | -4065.4 | -3728.4 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 24-NOV-19:26 | 0.00 | 0.00 | 9163.04 | 0.00 | 0.00 | 0.00 | 490.32 | 799.44 | 1651.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2077.7 | 0.00 | -2882.0 | -7144.5 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20-FEB-14:56 | 0.00 | 0.00 | 19349.35 | 0.00 | 0.00 | 0.00 | 143.87 | 103.05 | 1085.09 | 2228.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1550.6 | -21359.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 26-FEB-18:18 | 0.00 | 0.00 | 10721.52 | 0.00 | 0.00 | 0.00 | 494.14 | 721.37 | 1735.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.4 | 0.00 | -1839.9 | -11225.3 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13-JAN-08:01 | 0.00 | 0.00 | 8734.74 | 0.00 | 0.00 | 0.00 | 215.06 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2746.1 | 0.00 | -4293.8 | -3206.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 13-JAN-08:01 | 0.00 | 0.00 | 11024.89 | 0.00 | 0.00 | 0.00 | 215.06 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2738.5 | 0.00 | -5372.2 | -4426.3 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 13-JAN-08:01 | 0.00 | 0.00 | 10996.63 | 0.00 | 0.00 | 0.00 | 215.06 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2738.8 | 0.00 | -5372.2 | -4397.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 13-MAY-09:19 | 0.00 | 0.00 | 19638.39 | 0.00 | 0.00 | 0.00 | 126.66 | 103.05 | 1113.11 | 439.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1426.9 | -19993.7 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 15-NOV-15:27 | 0.00 | 0.00 | 9292.38 | 0.00 | 0.00 | 0.00 | 127.31 | 178.62 | 1141.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -303.1 | 0.00 | -1886.8 | -8549.4 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 13-JAN-08:03 | 0.00 | 0.00 | 8834.80 | 0.00 | 0.00 | 0.00 | 215.04 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1109.3 | 0.00 | -5143.6 | -4094.0 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 31-MAR-10:08 | 0.00 | 0.00 | 20462.13 | 0.00 | 0.00 | 0.00 | 133.10 | 103.05 | 1079.31 | 480.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -840.0 | -21417.7 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JAN-08:04 | 0.00 | 0.00 | 162780.29 | 0.00 | 0.00 | 0.00 | 3942.61 | 2720.58 | 20626.19 | 0.00 | 0.00 | 1304.04 | 0.00 | 0.00 | -39295.4 | 0.00 | -87717.2 | -64361.1 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 931.925 | 2.00 | 2.00 | 1.00 | 44.9950 | 931.925 | 0.048 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 235.474 | 2.00 | 2.00 | 1.00 | 44.9950 | 235.474 | 0.191 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 319.840 | 2.00 | 2.00 | 1.00 | 44.9950 | 319.840 | 0.141 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 480.128 | 2.00 | 2.00 | 1.00 | 44.9950 | 480.128 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 216.102 | 2.00 | 2.00 | 1.00 | 44.9950 | 216.102 | 0.208 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 319.666 | 2.00 | 2.00 | 1.00 | 44.9950 | 319.666 | 0.141 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 499.531 | 2.00 | 2.00 | 1.00 | 44.9950 | 499.531 | 0.090 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 242.162 | 2.00 | 2.00 | 1.00 | 44.9950 | 242.162 | 0.186 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 317.866 | 2.00 | 2.00 | 1.00 | 44.9950 | 317.866 | 0.142 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 479.187 | 2.00 | 2.00 | 1.00 | 44.9950 | 479.187 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 223.854 | 2.00 | 2.00 | 1.00 | 44.9950 | 223.854 | 0.201 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 318.152 | 2.00 | 2.00 | 1.00 | 44.9950 | 318.152 | 0.141 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 539.164 | 2.00 | 2.00 | 1.00 | 44.9950 | 539.164 | 0.083 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 284.642 | 2.00 | 2.00 | 1.00 | 44.9950 | 284.642 | 0.158 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 338.877 | 2.00 | 2.00 | 1.00 | 44.9950 | 338.877 | 0.133 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 536.345 | 2.00 | 2.00 | 1.00 | 44.9950 | 536.345 | 0.084 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 282.032 | 2.00 | 2.00 | 1.00 | 44.9950 | 282.032 | 0.160 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 334.337 | 2.00 | 2.00 | 1.00 | 44.9950 | 334.337 | 0.135 | 1.000 | 44.9950 | 0.13 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 163.057 | 2.00 | 2.00 | 1.00 | 44.9950 | 163.057 | 1.000 | 1.000 | 44.9950 | 0.28 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.976 | 2.00 | 2.00 | 1.00 | 44.9950 | 208.976 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 209.049 | 2.00 | 2.00 | 1.00 | 44.9950 | 209.049 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 163.073 | 2.00 | 2.00 | 1.00 | 44.9950 | 163.073 | 1.000 | 1.000 | 44.9950 | 0.28 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 208.918 | 2.00 | 2.00 | 1.00 | 44.9950 | 208.918 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 186.890 | 2.00 | 2.00 | 1.00 | 44.9950 | 186.890 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 140.914 | 2.00 | 2.00 | 1.00 | 44.9950 | 140.914 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 186.998 | 2.00 | 2.00 | 1.00 | 44.9950 | 186.998 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 186.994 | 2.00 | 2.00 | 1.00 | 44.9950 | 186.994 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 140.917 | 2.00 | 2.00 | 1.00 | 44.9950 | 140.917 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 186.942 | 2.00 | 2.00 | 1.00 | 44.9950 | 186.942 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 236.926 | 2.00 | 2.00 | 1.00 | 44.9950 | 236.926 | 1.000 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 190.939 | 2.00 | 2.00 | 1.00 | 44.9950 | 190.939 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 237.025 | 2.00 | 2.00 | 1.00 | 44.9950 | 237.025 | 1.000 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 236.961 | 2.00 | 2.00 | 1.00 | 44.9950 | 236.961 | 1.000 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 190.925 | 2.00 | 2.00 | 1.00 | 44.9950 | 190.925 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 236.972 | 2.00 | 2.00 | 1.00 | 44.9950 | 236.972 | 1.000 | 1.000 | 44.9950 | 0.19 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 931.925 | 931.9252 | 186.3850 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 235.474 | 235.4745 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 319.840 | 319.8396 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 480.128 | 480.1284 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 216.102 | 216.1020 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 319.666 | 319.6659 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 499.531 | 499.5315 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 242.162 | 242.1617 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 317.866 | 317.8660 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 479.187 | 479.1868 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 223.854 | 223.8539 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 318.152 | 318.1519 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 334.337 | 334.3374 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 338.877 | 338.8775 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 539.164 | 539.1637 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 282.032 | 282.0324 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 284.642 | 284.6423 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 536.345 | 536.3451 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 | 931.925 | 931.93 | 186.3850 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 | 235.474 | 235.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 | 319.840 | 319.84 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 | 480.128 | 480.13 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 | 216.102 | 216.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 | 319.666 | 319.67 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 | 499.531 | 499.53 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 | 242.162 | 242.16 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 | 317.866 | 317.87 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 | 479.187 | 479.19 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 | 223.854 | 223.85 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 | 318.152 | 318.15 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 539.16 | 539.164 | 539.16 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 284.64 | 284.642 | 284.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 338.88 | 338.877 | 338.88 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 536.35 | 536.345 | 536.35 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 282.03 | 282.032 | 282.03 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 334.34 | 334.337 | 334.34 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 163.057 | 163.057 | 163.057 | 44.9950 | 0.276 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.976 | 208.976 | 208.976 | 44.9950 | 0.215 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 209.049 | 209.049 | 209.049 | 44.9950 | 0.215 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 163.073 | 163.073 | 163.073 | 44.9950 | 0.276 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 208.918 | 208.918 | 208.918 | 44.9950 | 0.215 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 186.890 | 186.890 | 186.890 | 44.9950 | 0.241 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 140.914 | 140.914 | 140.914 | 44.9950 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 186.998 | 186.998 | 186.998 | 44.9950 | 0.241 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 186.994 | 186.994 | 186.994 | 44.9950 | 0.241 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 140.917 | 140.917 | 140.917 | 44.9950 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 186.942 | 186.942 | 186.942 | 44.9950 | 0.241 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 236.972 | 236.972 | 236.972 | 44.9950 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 237.025 | 237.025 | 237.025 | 44.9950 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 236.926 | 236.926 | 236.926 | 44.9950 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 190.925 | 190.925 | 190.925 | 44.9950 | 0.236 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 190.939 | 190.939 | 190.939 | 44.9950 | 0.236 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 236.961 | 236.961 | 236.961 | 44.9950 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 163.06 | 163.057 | 163.06 | 163.06 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 208.98 | 208.976 | 208.98 | 208.98 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 209.05 | 209.049 | 209.05 | 209.05 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 163.07 | 163.073 | 163.07 | 163.07 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 208.92 | 208.918 | 208.92 | 208.92 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 186.89 | 186.890 | 186.89 | 186.89 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 140.91 | 140.914 | 140.91 | 140.91 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 187.00 | 186.998 | 187.00 | 187.00 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 186.99 | 186.994 | 186.99 | 186.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 140.92 | 140.917 | 140.92 | 140.92 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 186.94 | 186.942 | 186.94 | 186.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 236.93 | 236.926 | 236.93 | 236.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 190.94 | 190.939 | 190.94 | 190.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 237.03 | 237.025 | 237.03 | 237.03 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 236.96 | 236.961 | 236.96 | 236.96 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 190.93 | 190.925 | 190.93 | 190.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 236.97 | 236.972 | 236.97 | 236.97 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 966.75 |
Number of hours cooling loads not met | 29.75 |
Number of hours not met | 996.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 2307.60 | 181461.39 | 0.00 | 0.00 |
Space Cooling | 15436.11 | 13212.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 7461.88 | 3434.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2923.45 | 115481.14 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 15395.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 126237.24 | 5231.05 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 431026.62 |
Natural Gas | 0.00 | 523105.05 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 954131.67 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.40 |
Fans-Interior | 0.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 3.24 |
Natural Gas [kWh/ft2] | |
Space Heating | 1.73 |
Service Water Heating | 2.20 |
Miscellaneous | 0.00 |
Subtotal | 3.93 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.63 |
Space Heating | 24.19 |
Space Cooling | 5.52 |
Fans-Interior | 2.67 |
Service Water Heating | 30.64 |
Receptacle Equipment | 31.43 |
Miscellaneous | 0.91 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 334.34 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 338.88 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 539.16 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 282.03 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 284.64 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 536.35 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 539.16 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 284.64 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 338.88 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 536.35 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 282.03 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 334.34 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 | 2.07 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 | 0.523124 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 | 0.710548 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 | 1.07 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 | 0.480087 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 | 0.710162 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 | 1.11 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 | 0.537980 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 | 0.706163 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 | 1.06 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 | 0.497308 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 | 0.706798 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 539.16 | 1.20 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 284.64 | 0.632354 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 338.88 | 0.752842 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 536.35 | 1.19 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 282.03 | 0.626556 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 334.34 | 0.742756 | 0.798655 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 | 931.93 | 931.93 | 2.07 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 | 235.47 | 235.47 | 0.523124 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 | 319.84 | 319.84 | 0.710548 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 | 480.13 | 480.13 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 | 216.10 | 216.10 | 0.480087 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 | 319.67 | 319.67 | 0.710162 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 | 499.53 | 499.53 | 1.11 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 | 242.16 | 242.16 | 0.537980 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 | 317.87 | 317.87 | 0.706163 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 | 479.19 | 479.19 | 1.06 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 | 223.85 | 223.85 | 0.497308 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 | 318.15 | 318.15 | 0.706798 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 539.16 | 539.16 | 539.16 | 1.20 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 284.64 | 284.64 | 284.64 | 0.632354 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 338.88 | 338.88 | 338.88 | 0.752842 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 536.35 | 536.35 | 536.35 | 1.19 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 282.03 | 282.03 | 282.03 | 0.626556 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 334.34 | 334.34 | 334.34 | 0.742756 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 49509.40 | 5.00 | 703.40 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 14833.38 | 1.50 | 198.10 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19035.31 | 1.92 | 259.35 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 27018.46 | 2.73 | 375.38 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13868.55 | 1.40 | 183.98 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 19026.66 | 1.92 | 259.22 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 27983.55 | 2.82 | 389.34 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 15165.86 | 1.53 | 202.94 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 18936.25 | 1.91 | 257.87 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 26970.34 | 2.72 | 374.64 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 14254.12 | 1.44 | 189.61 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 18950.48 | 1.91 | 258.08 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29958.71 | 3.02 | 417.99 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 17282.14 | 1.74 | 233.82 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19983.49 | 2.02 | 273.11 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 29818.33 | 3.01 | 415.95 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 17152.15 | 1.73 | 231.92 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19757.37 | 1.99 | 269.82 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 931.93 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 235.47 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 319.84 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 480.13 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 216.10 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 319.67 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 499.53 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 242.16 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 317.87 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 479.19 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 223.85 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 318.15 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 539.16 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 284.64 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 338.88 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 536.35 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 282.03 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 334.34 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.39 | 101.07 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.39 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 400993.73 | 40.32 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:45:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 711.511 | 55.483 | 0.439 | 0.003 | 55.485 |
February | 672.000 | 74.502 | 0.000 | 0.000 | 74.502 |
March | 744.000 | 100.750 | 0.000 | 0.000 | 100.750 |
April | 720.000 | 129.602 | 0.000 | 0.000 | 129.602 |
May | 744.000 | 149.998 | 0.000 | 0.000 | 149.998 |
June | 720.000 | 174.673 | 0.000 | 0.000 | 174.673 |
July | 744.000 | 205.771 | 0.000 | 0.000 | 205.771 |
August | 744.000 | 188.921 | 0.000 | 0.000 | 188.921 |
September | 720.000 | 162.846 | 0.000 | 0.000 | 162.846 |
October | 744.000 | 134.085 | 0.000 | 0.000 | 134.085 |
November | 720.000 | 83.899 | 0.000 | 0.000 | 83.899 |
December | 744.000 | 71.834 | 0.000 | 0.000 | 71.834 |
Annual Sum or Average | 8727.511 | 1532.366 | 0.439 | 0.003 | 1532.368 |
Minimum of Months | 672.000 | 55.483 | 0.000 | 0.000 | 55.485 |
Maximum of Months | 744.000 | 205.771 | 0.439 | 0.003 | 205.771 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 678.208 | 12.644 | 16.423 |
February | 18.583 | 0.355 | 543.062 | 7.021 | 7.377 |
March | 67.754 | 1.499 | 499.896 | 5.101 | 6.600 |
April | 208.780 | 6.895 | 234.833 | 1.671 | 8.566 |
May | 283.025 | 9.803 | 140.188 | 0.578 | 10.381 |
June | 485.157 | 23.226 | 36.396 | 0.149 | 23.375 |
July | 678.864 | 39.341 | 0.000 | 0.000 | 39.341 |
August | 558.105 | 30.213 | 15.764 | 0.040 | 30.253 |
September | 423.033 | 21.284 | 52.888 | 0.170 | 21.454 |
October | 244.022 | 9.259 | 235.792 | 1.351 | 10.611 |
November | 41.973 | 1.197 | 544.075 | 6.833 | 8.030 |
December | 9.898 | 0.138 | 646.317 | 9.447 | 9.586 |
Annual Sum or Average | 3019.195 | 143.210 | 3627.419 | 45.007 | 191.997 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.600 |
Maximum of Months | 678.864 | 39.341 | 678.208 | 12.644 | 39.341 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 709.750 | 34.883 | 36.773 |
February | 12.804 | 0.248 | 537.937 | 19.323 | 24.840 |
March | 77.965 | 2.315 | 463.944 | 13.509 | 22.409 |
April | 265.278 | 11.468 | 177.304 | 4.230 | 23.114 |
May | 361.367 | 17.544 | 100.117 | 1.693 | 26.343 |
June | 526.822 | 37.864 | 17.750 | 0.301 | 40.196 |
July | 675.568 | 58.775 | 0.000 | 0.000 | 59.049 |
August | 578.924 | 44.767 | 8.625 | 0.141 | 47.257 |
September | 439.297 | 29.714 | 38.375 | 0.605 | 35.695 |
October | 249.219 | 12.241 | 202.017 | 4.200 | 26.410 |
November | 33.850 | 1.246 | 540.712 | 19.288 | 28.194 |
December | 4.554 | 0.079 | 644.265 | 26.124 | 31.767 |
Annual Sum or Average | 3225.647 | 216.261 | 3440.797 | 124.297 | 402.047 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 22.409 |
Maximum of Months | 675.568 | 58.775 | 709.750 | 34.883 | 59.049 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 723.810 | 43.005 | 47.752 |
February | 0.000 | 0.000 | 575.129 | 25.153 | 44.245 |
March | 25.554 | 0.795 | 533.159 | 18.172 | 42.568 |
April | 169.913 | 7.869 | 260.424 | 6.051 | 31.250 |
May | 266.361 | 16.118 | 174.141 | 2.466 | 26.894 |
June | 465.999 | 37.420 | 38.341 | 0.546 | 42.292 |
July | 648.339 | 56.607 | 3.143 | 0.012 | 56.808 |
August | 507.565 | 41.111 | 35.759 | 0.351 | 43.384 |
September | 335.902 | 20.333 | 100.877 | 1.183 | 25.944 |
October | 106.758 | 4.607 | 333.642 | 7.298 | 31.749 |
November | 3.062 | 0.045 | 611.352 | 25.350 | 43.727 |
December | 0.000 | 0.000 | 688.819 | 33.912 | 46.870 |
Annual Sum or Average | 2529.452 | 184.904 | 4078.595 | 163.499 | 483.483 |
Minimum of Months | 0.000 | 0.000 | 3.143 | 0.012 | 25.944 |
Maximum of Months | 648.339 | 56.607 | 723.810 | 43.005 | 56.808 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.471 | 17.363 | 17.411 |
February | 0.000 | 0.000 | 655.600 | 10.338 | 11.964 |
March | 5.542 | 0.067 | 640.610 | 7.484 | 12.029 |
April | 122.496 | 2.947 | 305.099 | 2.499 | 7.566 |
May | 242.872 | 6.972 | 164.347 | 0.809 | 8.375 |
June | 484.244 | 21.586 | 42.039 | 0.194 | 21.820 |
July | 679.960 | 36.341 | 0.000 | 0.000 | 36.341 |
August | 528.641 | 23.913 | 22.797 | 0.063 | 23.986 |
September | 334.850 | 10.584 | 82.436 | 0.330 | 10.961 |
October | 65.760 | 1.613 | 383.889 | 2.743 | 6.347 |
November | 0.000 | 0.000 | 678.791 | 10.071 | 10.578 |
December | 0.000 | 0.000 | 742.663 | 13.177 | 13.311 |
Annual Sum or Average | 2464.364 | 104.022 | 4461.743 | 65.070 | 180.688 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.347 |
Maximum of Months | 679.960 | 36.341 | 743.471 | 17.363 | 36.341 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.919 | 42.044 | 42.057 |
February | 0.000 | 0.000 | 670.825 | 26.062 | 26.211 |
March | 12.528 | 0.317 | 658.938 | 17.909 | 19.685 |
April | 191.479 | 6.542 | 234.467 | 5.407 | 17.184 |
May | 344.377 | 14.557 | 119.482 | 2.015 | 22.885 |
June | 523.020 | 36.402 | 18.625 | 0.347 | 38.500 |
July | 677.012 | 56.112 | 0.000 | 0.000 | 56.377 |
August | 569.371 | 38.789 | 12.000 | 0.194 | 41.076 |
September | 398.074 | 18.871 | 52.417 | 0.826 | 24.354 |
October | 112.528 | 3.467 | 342.825 | 6.515 | 17.136 |
November | 0.000 | 0.000 | 675.914 | 25.695 | 27.622 |
December | 0.000 | 0.000 | 743.906 | 33.736 | 33.751 |
Annual Sum or Average | 2828.389 | 175.057 | 4273.317 | 160.751 | 366.838 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.136 |
Maximum of Months | 677.012 | 56.112 | 743.919 | 42.044 | 56.377 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 3.583 | 0.042 | 703.150 | 31.208 | 31.249 |
February | 37.104 | 1.038 | 521.517 | 16.560 | 17.598 |
March | 95.979 | 4.422 | 462.557 | 11.879 | 19.481 |
April | 253.740 | 14.664 | 180.317 | 3.365 | 28.692 |
May | 335.973 | 21.636 | 107.693 | 1.175 | 27.037 |
June | 515.337 | 42.379 | 19.830 | 0.232 | 45.023 |
July | 684.299 | 63.375 | 0.000 | 0.000 | 63.375 |
August | 567.961 | 50.592 | 16.660 | 0.106 | 51.532 |
September | 435.122 | 33.926 | 44.081 | 0.404 | 36.785 |
October | 248.886 | 14.790 | 228.335 | 3.646 | 23.050 |
November | 49.500 | 1.816 | 544.900 | 16.622 | 18.520 |
December | 12.089 | 0.233 | 648.327 | 22.908 | 23.141 |
Annual Sum or Average | 3239.574 | 248.913 | 3477.367 | 108.105 | 385.483 |
Minimum of Months | 3.583 | 0.042 | 0.000 | 0.000 | 17.598 |
Maximum of Months | 684.299 | 63.375 | 703.150 | 31.208 | 63.375 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 696.542 | 11.771 | 12.406 |
February | 22.756 | 0.383 | 505.467 | 5.933 | 7.291 |
March | 77.979 | 1.734 | 447.652 | 4.223 | 6.826 |
April | 238.673 | 8.095 | 185.451 | 1.223 | 9.410 |
May | 330.006 | 11.663 | 92.743 | 0.376 | 12.185 |
June | 544.040 | 26.277 | 23.833 | 0.074 | 26.367 |
July | 718.670 | 43.186 | 0.000 | 0.000 | 43.186 |
August | 611.447 | 33.405 | 5.969 | 0.010 | 33.419 |
September | 475.077 | 23.830 | 28.875 | 0.094 | 23.924 |
October | 276.848 | 10.447 | 177.323 | 0.963 | 11.410 |
November | 47.650 | 1.353 | 509.512 | 5.806 | 7.557 |
December | 11.299 | 0.142 | 623.475 | 8.075 | 8.323 |
Annual Sum or Average | 3354.445 | 160.515 | 3296.841 | 38.547 | 202.304 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.826 |
Maximum of Months | 718.670 | 43.186 | 696.542 | 11.771 | 43.186 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 701.967 | 29.296 | 31.401 |
February | 15.335 | 0.277 | 510.196 | 15.733 | 22.068 |
March | 91.258 | 2.679 | 424.049 | 10.531 | 20.412 |
April | 301.184 | 13.062 | 133.225 | 2.763 | 23.490 |
May | 391.763 | 19.844 | 68.014 | 0.976 | 26.309 |
June | 566.838 | 41.106 | 8.750 | 0.127 | 42.349 |
July | 701.097 | 62.417 | 0.000 | 0.000 | 62.417 |
August | 608.445 | 47.887 | 2.375 | 0.029 | 49.370 |
September | 474.571 | 32.231 | 19.875 | 0.278 | 36.439 |
October | 274.120 | 13.431 | 147.808 | 2.706 | 26.934 |
November | 38.090 | 1.334 | 509.133 | 15.746 | 25.443 |
December | 5.292 | 0.081 | 623.733 | 21.651 | 28.114 |
Annual Sum or Average | 3467.992 | 234.348 | 3149.125 | 99.835 | 394.746 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 20.412 |
Maximum of Months | 701.097 | 62.417 | 701.967 | 29.296 | 62.417 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 717.096 | 37.510 | 43.849 |
February | 0.000 | 0.000 | 555.179 | 21.248 | 43.987 |
March | 29.358 | 0.800 | 502.083 | 14.880 | 39.581 |
April | 194.088 | 8.856 | 218.688 | 4.448 | 28.569 |
May | 301.583 | 17.914 | 125.689 | 1.532 | 26.009 |
June | 510.448 | 40.362 | 20.477 | 0.261 | 44.004 |
July | 683.451 | 60.476 | 0.000 | 0.000 | 60.476 |
August | 546.481 | 44.108 | 21.647 | 0.155 | 45.498 |
September | 378.164 | 22.435 | 63.840 | 0.672 | 26.771 |
October | 121.391 | 4.943 | 282.594 | 5.405 | 31.159 |
November | 2.741 | 0.025 | 586.572 | 21.531 | 42.448 |
December | 0.000 | 0.000 | 675.630 | 29.180 | 45.192 |
Annual Sum or Average | 2767.705 | 199.919 | 3769.494 | 136.821 | 477.542 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 26.009 |
Maximum of Months | 683.451 | 60.476 | 717.096 | 37.510 | 60.476 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.417 | 14.223 | 14.278 |
February | 0.000 | 0.000 | 653.819 | 8.393 | 10.143 |
March | 6.417 | 0.098 | 600.539 | 5.785 | 10.403 |
April | 152.986 | 3.916 | 244.301 | 1.651 | 7.183 |
May | 294.350 | 8.903 | 112.190 | 0.449 | 9.705 |
June | 539.052 | 24.840 | 24.808 | 0.079 | 24.928 |
July | 720.289 | 40.411 | 0.000 | 0.000 | 40.411 |
August | 589.488 | 27.314 | 7.295 | 0.012 | 27.333 |
September | 395.597 | 12.992 | 46.707 | 0.165 | 13.192 |
October | 84.271 | 2.038 | 324.029 | 1.910 | 4.968 |
November | 0.000 | 0.000 | 659.535 | 8.178 | 8.608 |
December | 0.000 | 0.000 | 742.354 | 10.794 | 10.978 |
Annual Sum or Average | 2782.450 | 120.512 | 4158.993 | 51.639 | 182.131 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.968 |
Maximum of Months | 720.289 | 40.411 | 743.417 | 14.223 | 40.411 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.908 | 35.830 | 35.844 |
February | 0.000 | 0.000 | 670.558 | 21.762 | 21.933 |
March | 14.392 | 0.377 | 606.702 | 14.014 | 18.271 |
April | 224.496 | 7.845 | 173.417 | 3.527 | 18.038 |
May | 373.271 | 16.969 | 80.613 | 1.188 | 22.938 |
June | 560.653 | 39.746 | 9.875 | 0.158 | 40.904 |
July | 701.316 | 60.002 | 0.000 | 0.000 | 60.002 |
August | 602.614 | 42.190 | 3.250 | 0.042 | 43.726 |
September | 437.545 | 21.512 | 26.125 | 0.390 | 25.984 |
October | 133.481 | 4.087 | 270.062 | 4.525 | 17.308 |
November | 0.000 | 0.000 | 655.094 | 21.478 | 24.084 |
December | 0.000 | 0.000 | 744.000 | 28.547 | 28.547 |
Annual Sum or Average | 3047.768 | 192.727 | 3983.605 | 131.461 | 357.580 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.308 |
Maximum of Months | 701.316 | 60.002 | 744.000 | 35.830 | 60.002 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 731.275 | 48.282 | 48.282 |
February | 11.813 | 0.303 | 584.096 | 27.338 | 27.647 |
March | 67.125 | 2.769 | 540.064 | 20.212 | 28.322 |
April | 213.909 | 12.782 | 207.086 | 5.955 | 39.129 |
May | 297.994 | 21.123 | 142.637 | 2.562 | 34.842 |
June | 489.439 | 44.301 | 30.519 | 0.496 | 50.866 |
July | 672.941 | 68.110 | 2.470 | 0.009 | 68.306 |
August | 546.421 | 52.464 | 26.367 | 0.310 | 55.025 |
September | 401.013 | 32.664 | 65.110 | 0.998 | 40.051 |
October | 198.929 | 11.988 | 288.204 | 7.062 | 28.629 |
November | 26.687 | 0.976 | 619.529 | 27.581 | 29.077 |
December | 1.000 | 0.009 | 706.433 | 37.134 | 37.144 |
Annual Sum or Average | 2927.272 | 247.491 | 3943.792 | 177.938 | 487.318 |
Minimum of Months | 0.000 | 0.000 | 2.470 | 0.009 | 27.647 |
Maximum of Months | 672.941 | 68.110 | 731.275 | 48.282 | 68.306 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 730.692 | 18.493 | 19.179 |
February | 5.583 | 0.050 | 574.020 | 10.147 | 13.151 |
March | 43.792 | 0.864 | 539.807 | 7.477 | 9.621 |
April | 200.468 | 7.295 | 246.968 | 2.443 | 10.008 |
May | 294.366 | 12.065 | 154.738 | 0.933 | 13.380 |
June | 513.009 | 28.918 | 36.858 | 0.221 | 29.166 |
July | 702.604 | 48.365 | 0.000 | 0.000 | 48.365 |
August | 583.952 | 35.916 | 21.425 | 0.064 | 35.993 |
September | 430.553 | 23.265 | 63.992 | 0.312 | 23.591 |
October | 221.270 | 8.154 | 269.858 | 2.198 | 10.386 |
November | 32.521 | 0.761 | 595.996 | 9.987 | 11.863 |
December | 0.750 | 0.002 | 695.208 | 13.589 | 14.406 |
Annual Sum or Average | 3028.869 | 165.655 | 3929.563 | 65.864 | 239.108 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 9.621 |
Maximum of Months | 702.604 | 48.365 | 730.692 | 18.493 | 48.365 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.833 | 37.760 | 38.506 |
February | 3.433 | 0.020 | 600.496 | 21.480 | 23.617 |
March | 50.007 | 1.422 | 518.167 | 14.782 | 21.031 |
April | 247.982 | 11.109 | 187.642 | 4.253 | 21.837 |
May | 363.279 | 19.071 | 108.708 | 1.732 | 26.278 |
June | 543.095 | 42.677 | 15.750 | 0.258 | 44.515 |
July | 697.747 | 66.655 | 0.000 | 0.000 | 66.727 |
August | 599.143 | 49.442 | 8.000 | 0.109 | 51.251 |
September | 447.964 | 30.883 | 45.225 | 0.646 | 36.089 |
October | 228.268 | 10.637 | 239.083 | 4.662 | 23.503 |
November | 26.525 | 0.816 | 601.067 | 21.510 | 26.335 |
December | 0.000 | 0.000 | 703.115 | 29.058 | 31.132 |
Annual Sum or Average | 3207.444 | 232.732 | 3765.086 | 136.248 | 410.823 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 21.031 |
Maximum of Months | 697.747 | 66.655 | 737.833 | 37.760 | 66.727 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 51.685 | 51.685 |
February | 0.000 | 0.000 | 618.117 | 30.886 | 43.084 |
March | 24.625 | 0.778 | 556.095 | 21.762 | 42.708 |
April | 185.000 | 9.606 | 243.792 | 6.660 | 36.464 |
May | 287.664 | 19.692 | 162.633 | 2.642 | 32.849 |
June | 492.653 | 44.064 | 31.888 | 0.477 | 50.391 |
July | 675.076 | 67.357 | 2.179 | 0.005 | 67.518 |
August | 535.089 | 49.211 | 28.887 | 0.318 | 51.806 |
September | 360.271 | 24.721 | 92.428 | 1.279 | 31.647 |
October | 113.393 | 5.242 | 336.775 | 8.573 | 36.098 |
November | 1.583 | 0.014 | 640.863 | 31.180 | 43.490 |
December | 0.000 | 0.000 | 718.123 | 41.370 | 48.184 |
Annual Sum or Average | 2675.354 | 220.685 | 4175.779 | 196.839 | 535.924 |
Minimum of Months | 0.000 | 0.000 | 2.179 | 0.005 | 31.647 |
Maximum of Months | 675.076 | 67.357 | 744.000 | 51.685 | 67.518 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 21.183 | 21.183 |
February | 0.000 | 0.000 | 664.629 | 13.039 | 13.896 |
March | 8.125 | 0.142 | 637.155 | 9.303 | 14.217 |
April | 153.933 | 4.821 | 289.149 | 2.952 | 9.872 |
May | 279.347 | 10.938 | 161.894 | 1.009 | 12.498 |
June | 516.762 | 28.893 | 39.125 | 0.230 | 29.169 |
July | 707.307 | 47.685 | 0.000 | 0.000 | 47.685 |
August | 569.575 | 32.818 | 23.223 | 0.068 | 32.903 |
September | 368.884 | 15.564 | 83.259 | 0.426 | 16.055 |
October | 81.519 | 2.494 | 391.459 | 3.524 | 8.140 |
November | 0.000 | 0.000 | 681.608 | 12.739 | 13.388 |
December | 0.000 | 0.000 | 743.492 | 16.683 | 16.755 |
Annual Sum or Average | 2685.450 | 143.355 | 4458.993 | 81.155 | 235.762 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.140 |
Maximum of Months | 707.307 | 47.685 | 744.000 | 21.183 | 47.685 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 41.710 | 41.710 |
February | 0.000 | 0.000 | 671.521 | 25.801 | 25.871 |
March | 13.483 | 0.379 | 658.654 | 17.562 | 19.813 |
April | 203.579 | 8.111 | 227.010 | 4.838 | 18.337 |
May | 355.484 | 17.875 | 116.958 | 1.829 | 25.016 |
June | 543.860 | 42.555 | 16.250 | 0.265 | 44.227 |
July | 698.341 | 65.867 | 0.000 | 0.000 | 65.924 |
August | 594.767 | 46.352 | 8.250 | 0.112 | 48.194 |
September | 414.418 | 23.032 | 53.667 | 0.752 | 28.052 |
October | 112.488 | 4.140 | 359.250 | 6.483 | 17.780 |
November | 0.000 | 0.000 | 683.771 | 25.686 | 27.084 |
December | 0.000 | 0.000 | 744.000 | 33.728 | 33.728 |
Annual Sum or Average | 2936.421 | 208.312 | 4283.331 | 158.766 | 395.735 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.780 |
Maximum of Months | 698.341 | 65.867 | 744.000 | 41.710 | 65.924 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.00 | 0.76 |
May | 0.00 | 0.00 | 0.84 |
June | 0.00 | 0.00 | 0.99 |
July | 0.00 | 0.00 | 1.11 |
August | 0.00 | 0.00 | 1.03 |
September | 0.00 | 0.00 | 0.94 |
October | 0.00 | 0.00 | 0.76 |
November | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 0.00 | 1.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.30 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.33 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:45:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1681.05 | 1251.59 |
February | 0.00 | 0.00 | 1707.38 | 1148.17 |
March | 0.00 | 0.00 | 1670.36 | 1243.63 |
April | 0.00 | 0.00 | 1592.25 | 1147.23 |
May | 0.00 | 0.00 | 1475.78 | 1098.76 |
June | 0.00 | 0.00 | 1363.75 | 982.60 |
July | 0.00 | 0.00 | 1286.23 | 957.63 |
August | 0.00 | 0.00 | 1258.17 | 936.74 |
September | 0.00 | 0.00 | 1293.35 | 931.87 |
October | 0.00 | 0.00 | 1378.72 | 1026.49 |
November | 0.00 | 0.00 | 1491.15 | 1074.39 |
December | 0.00 | 0.00 | 1603.70 | 1194.00 |
Annual Sum or Average | 0.00 | 0.00 | 1482.18 | 12993.11 |
Minimum of Months | 0.00 | 0.00 | 1258.17 | 931.87 |
Maximum of Months | 0.00 | 0.00 | 1707.38 | 1251.59 |