Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:48

Tabular Output Report in Format: HTML

Building: MF+CZ6BWH+USA_MT_Helena.Rgnl.AP.727720+gasfurnace+unheatedbsmt+IECC_2012

Environment: ANNUAL ** Helena Regional Airport MT USA TMY3 WMO#=727720

Simulation Timestamp: 2019-02-14 08:48:15


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1149688.44 29.48 53.20
Net Site Energy 1149688.44 29.48 53.20
Total Source Energy 2043150.17 52.38 94.55
Net Source Energy 2043150.17 52.38 94.55


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 282065.98 0.00 0.00 0.00 0.00
Cooling 44460.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 261812.16 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23361.74 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 321081.86 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 382567.40 767121.04 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 282065.98 0.00 0.00 0.00 0.00
Cooling General 44460.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 23361.74 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 321081.86 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 3.14 27.91 0.00 0.00 0.00 17.48
Other 12.12 7.59 0.00 0.00 0.00 0.00
Total 17.70 35.50 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 1.74 15.46 0.00 0.00 0.00 9.68
Other 6.71 4.20 0.00 0.00 0.00 0.00
Total 9.81 19.67 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 382567.401 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 382567.401 100.00
     
Total On-Site and Utility Electric Sources 382567.401 100.00
Total Electricity End Uses 382567.401 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 553.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:48
RunPeriod ANNUAL
Weather File Helena Regional Airport MT USA TMY3 WMO#=727720
Latitude [deg] 46.60
Longitude [deg] -112.0
Elevation [ft] 3828.93
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 18953.34 7014.93 2461.74 7014.93 2461.74
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 11.22 7.58 21.60 7.58 21.60
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
UNHEATEDBSMT 7794.39 No Yes 58419.71 1.00 185.02 2590.34 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
Total 39005.17     325507.37   16363.00 2590.34 2126.74 2126.74 0.3689 1083.48 2.4729
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 4.4634
Unconditioned Total 17395.21     141767.99   1066.39 2590.34 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 21-JUL-18:15 16-JAN-08:15 - - - 01-JAN-08:15
Heating 0.00 207.64 0.00 0.00 0.00 0.00
Cooling 40.66 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 40.98 20.12 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 11.15 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 151.12 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 107.89 378.89 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 207.64 0.00 0.00 0.00 0.00
Cooling General 40.66 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.22 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.61 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.52 9.86 0.00 0.00 0.00 0.00
  gas_range 0.00 8.49 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 22.66 1.77 0.00 0.00 0.00 0.00
  IECC_adj 9.39 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 11.15 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 151.12 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 305759.53 0.00 0.00 0.00
Cooling 140806.37 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 829159.12 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 73986.63 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 348052.74 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1211590.96 831559.21 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 14.15 0.00 0.00 0.00
Cooling 6.52 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 38.37 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.42 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.11 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 56.07 38.48 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 14.15 0.00 0.00 0.00
Cooling 6.52 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 38.37 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.42 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.11 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 56.07 38.48 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB -15.3 0.00 -15.3 Wetbulb [F] 314.98 300.00
HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 92.66 28.98 61.52 Wetbulb [F] 964.61 290.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.064 0.066 839.40 839.40 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.064 0.066 455.77 455.77 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.064 0.066 839.40 839.40 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.064 0.066 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.320 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.320 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.320 0.330 0.882              
North Total or Average           531.68 0.320 0.330 0.882              
Non-North Total or Average           1595.05 0.320 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.252 0.320 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   25826.84 20626.74 5200.10 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6475.32 5171.55 1303.77 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8674.28 6927.76 1746.52 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13158.88 10509.41 2649.47 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6035.97 4820.66 1215.31 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8641.06 6901.23 1739.83 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13675.51 10922.02 2753.49 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6742.75 5385.13 1357.62 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8653.59 6911.24 1742.35 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13166.39 10515.41 2650.98 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6286.58 5020.81 1265.77 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8640.83 6901.04 1739.79 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14559.68 11628.16 2931.51 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7732.54 6175.63 1556.91 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8779.01 7011.40 1767.61 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14440.68 11533.12 2907.55 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7636.18 6098.67 1537.50 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8654.20 6911.73 1742.48 0.80 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.2 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   6099.92 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   13207.83 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   15926.24 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   15911.63 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   13206.36 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   15921.37 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   14461.20 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   11753.44 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   14474.90 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   14463.16 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   11751.63 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   14470.20 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   17705.39 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   14983.99 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   17715.12 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   17705.01 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   14981.52 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   17710.60 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 968.79 485.17 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 242.90 121.64 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 325.38 162.95 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 493.60 247.19 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 226.41 113.39 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 324.13 162.33 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 512.98 256.90 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 252.93 126.66 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 324.60 162.56 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 493.88 247.33 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 235.82 118.10 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 324.13 162.32 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 546.15 273.51 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 290.05 145.26 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 329.31 164.92 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 541.68 271.27 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 286.44 143.45 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 324.63 162.57 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 19784.17 19784.17 16.48 968.789 968.789 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00801 84.62 0.00635 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4960.29 4960.29 4.13 242.895 242.895 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00805 82.44 0.00635 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6644.79 6644.79 5.53 325.380 325.380 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00790 80.42 0.00635 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10080.13 10080.13 8.40 493.602 493.602 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00800 84.62 0.00635 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4623.73 4623.73 3.85 226.415 226.415 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00806 81.36 0.00635 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6619.35 6619.35 5.51 324.134 324.134 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00790 80.42 0.00635 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10475.82 10475.82 8.73 512.981 512.981 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00805 83.53 0.00635 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5165.12 5165.12 4.30 252.927 252.927 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00812 81.36 0.00635 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6628.94 6628.94 5.52 324.604 324.604 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 74.98 74.98 0.00793 81.65 0.00635 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10085.82 10085.82 8.40 493.884 493.884 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00805 83.53 0.00635 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4815.69 4815.69 4.01 235.816 235.816 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00812 81.36 0.00635 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6619.15 6619.15 5.51 324.125 324.125 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00794 80.42 0.00635 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6629.39 6629.39 5.52 324.627 324.627 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 83.53 0.00635 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6725.00 6725.00 5.60 329.309 329.309 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 83.53 0.00635 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11153.16 11153.16 9.29 546.147 546.147 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 83.53 0.00635 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5849.53 5849.53 4.87 286.440 286.440 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00806 81.36 0.00635 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5923.35 5923.35 4.93 290.055 290.055 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00806 81.36 0.00635 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11062.00 11062.00 9.21 541.683 541.683 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 83.53 0.00635 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2437.65 2437.65 2.03 51.038 51.038 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00360 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9650.97 9650.97 8.04 202.033 202.033 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00599 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12409.59 12409.59 10.34 259.778 259.778 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00626 -15.3 0.00039 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12394.76 12394.76 10.32 259.467 259.467 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00626 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9649.48 9649.48 8.04 202.001 202.001 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00599 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12404.65 12404.65 10.33 259.674 259.674 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00626 -15.3 0.00039 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10922.73 10922.73 9.10 228.669 228.669 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00644 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8174.92 8174.92 6.81 171.146 171.146 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00616 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10936.64 10936.64 9.11 228.960 228.960 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00644 -15.3 0.00039 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10924.73 10924.73 9.10 228.711 228.711 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00644 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8173.08 8173.08 6.81 171.107 171.107 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00616 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10931.87 10931.87 9.11 228.860 228.860 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00644 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 14220.32 14220.32 11.84 297.684 297.684 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00643 -15.3 0.00039 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 14224.90 14224.90 11.85 297.780 297.780 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00643 -15.3 0.00039 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14215.03 14215.03 11.84 297.573 297.573 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00643 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11450.86 11450.86 9.54 239.712 239.712 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00622 -15.3 0.00039 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11453.37 11453.37 9.54 239.765 239.765 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00622 -15.3 0.00039 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14214.64 14214.64 11.84 297.565 297.565 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00643 -15.3 0.00039 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 968.79 968.79 51.04 51.04
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 242.90 242.90 202.03 202.03
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.38 325.38 259.78 259.78
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 493.60 493.60 259.47 259.47
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.41 226.41 202.00 202.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 324.13 324.13 259.67 259.67
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 512.98 512.98 228.67 228.67
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.93 252.93 171.15 171.15
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.60 324.60 228.96 228.96
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.88 493.88 228.71 228.71
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.82 235.82 171.11 171.11
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.13 324.13 228.86 228.86
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.15 546.15 297.57 297.57
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 290.05 290.05 239.76 239.76
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.31 329.31 297.78 297.78
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 541.68 541.68 297.56 297.56
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 286.44 286.44 239.71 239.71
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 324.63 324.63 297.68 297.68


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 797.00 6264.50 23.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 507.50 6107.50 0.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1176.25 6056.75 133.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 964.50 6600.25 211.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 259.00 6574.75 6.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1000.25 6427.50 193.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1176.50 5922.25 80.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 681.75 5795.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1313.00 5796.25 115.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1059.75 6350.25 178.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 385.00 6255.25 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1138.75 6181.00 154.25
LIVING_UNIT3_BACKROW_TOPFLOOR 1540.50 6294.00 481.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 1523.25 6078.50 348.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 1414.50 6254.50 351.75
LIVING_UNIT2_BACKROW_TOPFLOOR 751.50 6421.25 153.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 838.50 6157.75 83.75
LIVING_UNIT1_BACKROW_TOPFLOOR 1448.75 6480.50 513.00
UNHEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 2129.25 7040.50 553.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
UNHEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.128 0.000 0.281
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.111 0.000 0.280
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.126 0.000 0.280
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.125 0.000 0.280
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.111 0.000 0.280
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.126 0.000 0.280
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.055 0.000 0.280
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.040 0.000 0.280
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.055 0.000 0.280
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.055 0.000 0.280
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.040 0.000 0.280
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.055 0.000 0.280
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.126 0.000 0.280
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.126 0.000 0.280
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.126 0.000 0.280
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.280
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.111 0.000 0.280
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.126 0.000 0.280
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1878
Defaulted Fields 500
Fields with Defaults 4920
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
Electricity:Building 89625.89 7014.87 02-JAN-03:15 16912.36 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 76678.43 6519.25 02-JAN-04:15 12694.94 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
Fans:Electricity 6842.09 140.20 27-MAR-00:15 3266.49 21-JUL-17:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
ElectricityPurchased:Plant 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
Cogeneration:ElectricityPurchased 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
ElectricityNet:Plant 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
Cogeneration:ElectricityNet 112044.71 8059.50 19-MAY-04:00 31597.67 21-JUL-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 19863.49 515.10 27-MAR-00:30 15399.42 21-JUL-17:30
General:Fans:Electricity 6842.09 140.20 27-MAR-00:15 3266.49 21-JUL-17:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 13021.40 0.00 01-JAN-01:45 12132.93 21-JUL-17:30
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 7671.21 2644.47 21-APR-03:15 378618.37 16-JAN-08:15
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 3210.82 0.00 01-JAN-00:15 151568.83 19-FEB-08:45
WaterSystems:Gas 3210.82 0.00 01-JAN-00:15 151568.83 19-FEB-08:45
Water Heater:WaterSystems:Gas 3210.82 0.00 01-JAN-00:15 151568.83 19-FEB-08:45
Gas:HVAC 2820.66 0.00 18-MAR-16:30 208272.75 24-FEB-06:00
Heating:Gas 2820.66 0.00 18-MAR-16:30 208272.75 24-FEB-06:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
Water:Plant 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
WaterSystems:Water 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
MainsWater:Plant 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
WaterSystems:MainsWater 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 26-SEP-02:30 0.18 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
PlantLoopHeatingDemand:Plant 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
WaterSystems:PlantLoopHeatingDemand 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1026048.87 16276.72 17-MAY-02:30 381333.25 24-FEB-07:15
EnergyTransfer:Building 417748.32 6723.39 27-MAR-00:15 173624.49 24-FEB-06:00
EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 234799.75 0.00 18-MAR-16:30 173624.49 24-FEB-06:00
Heating:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 182948.58 0.00 01-JAN-01:45 146296.06 21-JUL-18:15
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 66608.18 0.00 01-JAN-01:45 20447.33 18-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10.52 0.00 01-JAN-00:15 1447.74 24-FEB-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 66597.67 0.00 01-JAN-01:45 20447.33 18-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14672.84 0.00 02-JAN-13:15 8415.91 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9176.56 0.00 02-JAN-13:15 8415.91 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5496.28 0.00 01-JAN-00:15 5435.12 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21637.76 0.00 05-JAN-13:00 10976.47 24-FEB-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13737.50 0.00 05-JAN-13:00 10976.47 24-FEB-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7900.26 0.00 01-JAN-00:15 6990.52 19-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23127.01 0.00 11-FEB-16:15 11081.75 16-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16763.73 0.00 11-FEB-16:15 11081.75 16-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6363.27 0.00 01-JAN-00:15 10964.20 18-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16500.42 0.00 02-MAR-18:15 8610.32 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12528.38 0.00 02-MAR-18:15 8610.32 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3972.04 0.00 01-JAN-00:15 4962.25 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 22927.98 0.00 18-MAR-09:45 11128.57 16-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16594.42 0.00 18-MAR-09:45 11128.57 16-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6333.57 0.00 01-JAN-00:15 7041.22 19-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 19280.12 0.00 02-JAN-14:00 11388.25 18-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10290.75 0.00 02-JAN-14:00 9527.44 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8989.38 0.00 01-JAN-00:15 11388.25 18-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13489.25 0.00 02-JAN-13:00 7136.67 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7045.14 0.00 02-JAN-13:00 7136.67 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6444.11 0.00 01-JAN-00:15 5563.99 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 20019.83 0.00 02-JAN-14:15 9598.71 24-FEB-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11176.56 0.00 02-JAN-14:15 9598.71 24-FEB-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8843.27 0.00 01-JAN-00:15 6951.59 19-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 21084.12 0.00 11-FEB-16:15 10993.12 18-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13971.27 0.00 11-FEB-16:15 9716.55 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7112.85 0.00 01-JAN-00:15 10993.12 18-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14575.99 0.00 02-MAR-17:30 7275.07 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9752.24 0.00 02-MAR-17:30 7275.07 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4823.76 0.00 01-JAN-00:15 5099.32 21-JUL-19:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21033.39 0.00 05-MAR-16:15 9733.69 16-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 13823.71 0.00 05-MAR-16:15 9733.69 16-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7209.68 0.00 01-JAN-00:15 7022.22 19-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26734.10 0.00 18-MAR-15:15 12602.94 16-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 19369.42 0.00 18-MAR-15:15 12602.94 16-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 7364.68 0.00 01-JAN-00:15 7212.27 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 25011.73 0.00 21-JAN-13:45 12463.01 24-FEB-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 16685.65 0.00 21-JAN-13:45 12463.01 24-FEB-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 8326.08 0.00 01-JAN-00:15 7333.83 21-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 25212.72 0.00 21-JAN-14:30 12500.58 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 16759.40 0.00 21-JAN-14:30 12500.58 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 8453.32 0.00 01-JAN-00:15 12221.64 18-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 20351.99 0.00 04-MAR-18:30 10185.38 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 15155.27 0.00 04-MAR-18:30 10185.38 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5196.72 0.00 01-JAN-00:15 6246.79 21-JUL-19:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 18462.60 0.00 21-JAN-13:15 10063.50 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 12360.80 0.00 21-JAN-13:15 10063.50 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 6101.80 0.00 01-JAN-00:15 6365.70 21-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 27018.29 0.00 18-FEB-16:15 12640.38 24-FEB-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 19598.44 0.00 18-FEB-16:15 12640.38 24-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 7419.84 0.00 01-JAN-00:15 12141.51 18-JUL-18:15
EnergyTransfer:Plant 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
WaterSystems:EnergyTransfer 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 178662.42 1605.96 21-AUG-02:15 45117.54 18-FEB-08:45
EnergyTransfer:HVAC 429638.13 7201.45 27-MAR-00:15 166618.20 24-FEB-06:00
HeatingCoils:EnergyTransfer 225652.79 0.00 18-MAR-16:30 166618.20 24-FEB-06:00
CoolingCoils:EnergyTransfer 203985.34 0.00 01-JAN-01:45 157646.78 30-JUN-18:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 10.516 -5546.09 0.000 0.000 2876.229 2456.001 14468.945 8711.355 0.000 223.449 63846.061 0.000 -7831.08 0.000 -18163.87 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 9176.466 -457.71 0.000 0.000 3046.186 2456.001 14468.945 4257.806 0.000 215.776 0.000 0.000 -3024.88 0.000 -16409.65 -8690.39
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 13737.375 -657.91 0.000 0.000 3059.084 2456.001 14468.945 8869.055 0.000 223.447 0.000 0.000 -7233.92 0.000 -17034.75 -10645.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 16763.606 -529.92 0.000 0.000 3070.782 2456.001 14468.945 5617.634 0.000 223.448 0.000 0.000 -7912.42 0.000 -16910.57 -11414.19
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 12528.289 -330.78 0.000 0.000 3064.602 2456.001 14468.945 814.991 0.000 215.775 0.000 0.000 -3360.58 0.000 -16271.55 -9944.46
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 16594.295 -527.44 0.000 0.000 3070.672 2456.001 14468.945 5613.840 0.000 223.447 0.000 0.000 -7652.17 0.000 -16938.16 -11503.32
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 10290.643 -748.61 0.000 0.000 3041.758 2456.001 14468.945 8797.984 0.000 186.493 0.000 0.000 -7620.41 0.000 -13994.31 -8637.77
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 7045.061 -536.65 0.000 0.000 3030.766 2456.001 14468.945 4246.949 0.000 178.855 0.000 0.000 -3064.22 0.000 -13365.02 -8553.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 11176.461 -736.44 0.000 0.000 3046.411 2456.001 14468.945 8839.870 0.000 186.491 0.000 0.000 -7330.13 0.000 -13990.26 -10010.54
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 13971.161 -592.34 0.000 0.000 3058.021 2456.001 14468.945 5594.661 0.000 186.493 0.000 0.000 -8024.18 0.000 -13889.88 -10708.39
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 9752.160 -401.71 0.000 0.000 3051.049 2456.001 14468.945 808.345 0.000 178.855 0.000 0.000 -3404.94 0.000 -13250.45 -9236.21
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 13823.616 -600.40 0.000 0.000 3059.698 2456.001 14468.945 5590.049 0.000 186.491 0.000 0.000 -7748.35 0.000 -13906.73 -10720.07
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 19369.283 -613.31 0.000 0.000 3067.600 2456.001 14468.945 5616.250 0.000 221.433 0.000 0.000 -7701.81 0.000 -16975.22 -13157.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 16685.516 -693.37 0.000 0.000 3059.185 2456.001 14468.945 8892.880 0.000 221.432 0.000 0.000 -7269.72 0.000 -17042.87 -13145.33
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 16759.257 -703.97 0.000 0.000 3058.806 2456.001 14468.945 8863.336 0.000 221.435 0.000 0.000 -7522.51 0.000 -17020.64 -12831.35
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 15155.161 -432.77 0.000 0.000 3061.840 2456.001 14468.945 815.027 0.000 213.831 0.000 0.000 -3378.18 0.000 -16311.59 -11284.33
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 12360.695 -508.14 0.000 0.000 3049.978 2456.001 14468.945 4269.495 0.000 213.832 0.000 0.000 -3031.97 0.000 -16395.15 -11290.05
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 19598.300 -617.90 0.000 0.000 3067.462 2456.001 14468.945 5610.212 0.000 221.435 0.000 0.000 -7970.66 0.000 -16951.28 -13080.60
UNHEATEDBSMT 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4483.835 38319.549 0.000 0.000 0.000 -42803.38 -0.48
Total Facility 0.000 0.000 234797.863 -15235.49 0.000 0.000 54840.130 44208.020 260441.015 101829.739 0.000 8226.252 102165.611 0.000 -111082.15 0.000 -327625.35 -184853.56


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18-JUL-18:05 0.00 0.00 0.00 -1.7 0.00 0.00 427.02 721.37 2654.97 7857.12 0.00 603.11 8262.13 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 721.37 2654.97 471.95 0.00 848.36 313.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 19-JUL-08:47 0.00 0.00 0.00 -0.6 0.00 0.00 194.53 151.14 1613.42 7163.96 0.00 99.04 0.00 0.00 0.00 0.00 0.00 -2231.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18-JUL-18:03 0.00 0.00 0.00 -0.9 0.00 0.00 427.00 721.37 2654.97 7975.84 0.00 603.08 0.00 0.00 0.00 0.00 0.00 -1415.8
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.4 0.00 0.00 427.01 721.37 2654.97 611.48 0.00 848.35 0.00 0.00 0.00 0.00 0.00 -299.2
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19-JUL-08:47 0.00 0.00 0.00 -0.6 0.00 0.00 194.53 151.14 1613.42 7039.98 0.00 99.04 0.00 0.00 0.00 0.00 0.00 -2056.8
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18-JUL-18:03 0.00 0.00 0.00 -0.9 0.00 0.00 427.00 721.37 2654.97 7854.85 0.00 540.03 0.00 0.00 0.00 0.00 0.00 -807.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 721.37 2654.97 476.16 0.00 704.99 581.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 19-JUL-08:47 0.00 0.00 0.00 -0.6 0.00 0.00 194.53 151.14 1613.42 7153.34 0.00 89.49 0.00 0.00 0.00 0.00 0.00 -2250.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 18-JUL-18:03 0.00 0.00 0.00 -0.9 0.00 0.00 427.00 721.37 2654.97 7973.67 0.00 540.04 0.00 0.00 0.00 0.00 0.00 -1321.3
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21-JUL-18:51 0.00 0.00 0.00 -0.4 0.00 0.00 427.01 721.37 2654.97 517.53 0.00 576.16 203.20 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 19-JUL-08:47 0.00 0.00 0.00 -0.6 0.00 0.00 194.53 151.14 1613.42 7029.57 0.00 89.49 0.00 0.00 0.00 0.00 0.00 -2055.7
LIVING_UNIT3_BACKROW_TOPFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 721.37 2654.97 1292.97 0.00 874.99 1242.44 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.01 721.37 2654.97 1157.83 0.00 874.99 1499.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 18-JUL-18:03 0.00 0.00 0.00 -1.0 0.00 0.00 427.00 721.37 2654.97 7838.91 0.00 599.83 0.00 0.00 0.00 0.00 0.00 -17.6
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUL-18:54 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 721.37 2654.97 508.97 0.00 686.47 1248.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-18:24 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 721.37 2654.97 422.81 0.00 792.01 1348.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 18-JUL-18:03 0.00 0.00 0.00 -1.0 0.00 0.00 427.00 721.37 2654.97 7952.29 0.00 599.83 0.00 0.00 0.00 0.00 0.00 -211.2
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-JUL-18:09 0.00 0.00 0.00 -12.2 0.00 0.00 7686.23 12984.58 47789.53 47626.15 0.00 14751.08 26705.20 0.00 0.00 0.00 -11141.6 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 24-FEB-06:00 0.00 0.00 1447.72 0.00 0.00 0.00 526.31 343.51 1158.62 0.00 0.00 0.00 6450.08 0.00 -3244.5 0.00 -6681.7 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24-FEB-08:05 0.00 0.00 8415.79 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -576.8 0.00 -6363.1 -3455.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 24-FEB-06:00 0.00 0.00 10976.38 0.00 0.00 0.00 526.31 343.51 1158.62 0.00 0.00 0.00 0.00 0.00 -3238.8 0.00 -6681.7 -3084.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16-JAN-05:00 0.00 0.00 11081.53 0.00 0.00 0.00 526.31 164.88 1036.06 0.00 0.00 0.00 0.00 0.00 -3299.6 0.00 -6653.0 -2856.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 24-FEB-08:05 0.00 0.00 8610.21 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1178.5 0.00 -6363.1 -3048.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16-JAN-05:00 0.00 0.00 11128.34 0.00 0.00 0.00 526.31 164.88 1036.06 0.00 0.00 0.00 0.00 0.00 -3283.5 0.00 -6653.0 -2919.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24-FEB-08:05 0.00 0.00 9527.31 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -2307.6 0.00 -5275.7 -3923.6
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24-FEB-08:05 0.00 0.00 7136.58 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -576.3 0.00 -4981.5 -3558.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24-FEB-06:00 0.00 0.00 9598.63 0.00 0.00 0.00 526.31 343.51 1158.62 0.00 0.00 0.00 0.00 0.00 -3240.0 0.00 -5294.0 -3093.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 24-FEB-08:05 0.00 0.00 9716.42 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -2905.8 0.00 -5275.7 -3514.5
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 24-FEB-08:05 0.00 0.00 7274.98 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1178.5 0.00 -4981.5 -3094.6
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16-JAN-05:00 0.00 0.00 9733.48 0.00 0.00 0.00 526.31 164.88 1036.06 0.00 0.00 0.00 0.00 0.00 -3311.0 0.00 -5259.3 -2890.4
LIVING_UNIT3_BACKROW_TOPFLOOR 16-JAN-06:00 0.00 0.00 12602.88 0.00 0.00 0.00 526.31 343.51 1158.62 0.00 0.00 0.00 0.00 0.00 -3299.3 0.00 -6659.7 -4672.3
LIVING_UNIT3_FRONTROW_TOPFLOOR 24-FEB-06:00 0.00 0.00 12462.90 0.00 0.00 0.00 526.31 343.51 1158.62 0.00 0.00 0.00 0.00 0.00 -3213.1 0.00 -6688.4 -4589.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 24-FEB-08:05 0.00 0.00 12500.42 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -2277.8 0.00 -6663.8 -5538.5
LIVING_UNIT2_BACKROW_TOPFLOOR 24-FEB-08:05 0.00 0.00 10185.24 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -1165.6 0.00 -6369.3 -4629.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 24-FEB-08:05 0.00 0.00 10063.36 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -563.1 0.00 -6369.3 -5110.5
LIVING_UNIT1_BACKROW_TOPFLOOR 24-FEB-08:05 0.00 0.00 12640.22 0.00 0.00 0.00 215.05 151.14 1613.42 0.00 0.00 0.00 0.00 0.00 -2877.2 0.00 -6663.8 -5078.8
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-FEB-06:00 0.00 0.00 173623.05 0.00 0.00 0.00 9473.52 6183.13 20855.10 0.00 0.00 3184.06 0.00 0.00 -46622.0 0.00 -110211.1 -56485.8



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 968.789 2.00 2.00 1.00 44.9950 968.789 0.046 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 242.895 2.00 2.00 1.00 44.9950 242.895 0.185 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.380 2.00 2.00 1.00 44.9950 325.380 0.138 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 493.602 2.00 2.00 1.00 44.9950 493.602 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.415 2.00 2.00 1.00 44.9950 226.415 0.199 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 324.134 2.00 2.00 1.00 44.9950 324.134 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 512.981 2.00 2.00 1.00 44.9950 512.981 0.088 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.927 2.00 2.00 1.00 44.9950 252.927 0.178 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.604 2.00 2.00 1.00 44.9950 324.604 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.884 2.00 2.00 1.00 44.9950 493.884 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.816 2.00 2.00 1.00 44.9950 235.816 0.191 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.125 2.00 2.00 1.00 44.9950 324.125 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.147 2.00 2.00 1.00 44.9950 546.147 0.082 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 290.055 2.00 2.00 1.00 44.9950 290.055 0.155 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.309 2.00 2.00 1.00 44.9950 329.309 0.137 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 541.683 2.00 2.00 1.00 44.9950 541.683 0.083 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 286.440 2.00 2.00 1.00 44.9950 286.440 0.157 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 324.627 2.00 2.00 1.00 44.9950 324.627 0.139 1.000 44.9950 0.14


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 51.038 2.00 2.00 1.00 44.9950 51.038 1.000 1.000 44.9950 0.88
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 202.033 2.00 2.00 1.00 44.9950 202.033 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 259.778 2.00 2.00 1.00 44.9950 259.778 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 259.467 2.00 2.00 1.00 44.9950 259.467 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 202.001 2.00 2.00 1.00 44.9950 202.001 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 259.674 2.00 2.00 1.00 44.9950 259.674 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 228.669 2.00 2.00 1.00 44.9950 228.669 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 171.146 2.00 2.00 1.00 44.9950 171.146 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 228.960 2.00 2.00 1.00 44.9950 228.960 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 228.711 2.00 2.00 1.00 44.9950 228.711 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.107 2.00 2.00 1.00 44.9950 171.107 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 228.860 2.00 2.00 1.00 44.9950 228.860 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 297.573 2.00 2.00 1.00 44.9950 297.573 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 239.765 2.00 2.00 1.00 44.9950 239.765 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 297.780 2.00 2.00 1.00 44.9950 297.780 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 297.565 2.00 2.00 1.00 44.9950 297.565 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 239.712 2.00 2.00 1.00 44.9950 239.712 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 297.684 2.00 2.00 1.00 44.9950 297.684 1.000 1.000 44.9950 0.15


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   968.789 968.7887 193.7577 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   242.895 242.8951 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   325.380 325.3801 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   493.602 493.6018 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   226.415 226.4147 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   324.134 324.1341 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   512.981 512.9809 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   252.927 252.9268 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   324.604 324.6042 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   493.884 493.8836 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   235.816 235.8156 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   324.125 324.1254 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   324.627 324.6272 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   329.309 329.3087 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   546.147 546.1470 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   286.440 286.4401 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   290.055 290.0547 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   541.683 541.6831 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 968.79 968.789 968.79 193.7577 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 242.90 242.895 242.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.38 325.380 325.38 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 493.60 493.602 493.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.41 226.415 226.41 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 324.13 324.134 324.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 512.98 512.981 512.98 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.93 252.927 252.93 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.60 324.604 324.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.88 493.884 493.88 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.82 235.816 235.82 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.13 324.125 324.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.15 546.147 546.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 290.05 290.055 290.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.31 329.309 329.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 541.68 541.683 541.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 286.44 286.440 286.44 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 324.63 324.627 324.63 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   51.038 51.038 51.038 44.9950 0.882 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   202.033 202.033 202.033 44.9950 0.223 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   259.778 259.778 259.778 44.9950 0.173 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   259.467 259.467 259.467 44.9950 0.173 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   202.001 202.001 202.001 44.9950 0.223 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   259.674 259.674 259.674 44.9950 0.173 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   228.669 228.669 228.669 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   171.146 171.146 171.146 44.9950 0.263 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   228.960 228.960 228.960 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   228.711 228.711 228.711 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   171.107 171.107 171.107 44.9950 0.263 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   228.860 228.860 228.860 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   297.684 297.684 297.684 44.9950 0.151 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   297.780 297.780 297.780 44.9950 0.151 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   297.573 297.573 297.573 44.9950 0.151 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   239.712 239.712 239.712 44.9950 0.188 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   239.765 239.765 239.765 44.9950 0.188 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   297.565 297.565 297.565 44.9950 0.151 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 51.04 51.038 51.04 51.04 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 202.03 202.033 202.03 202.03 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 259.78 259.778 259.78 259.78 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 259.47 259.467 259.47 259.47 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 202.00 202.001 202.00 202.00 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 259.67 259.674 259.67 259.67 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 228.67 228.669 228.67 228.67 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 171.15 171.146 171.15 171.15 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 228.96 228.960 228.96 228.96 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 228.71 228.711 228.71 228.71 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.11 171.107 171.11 171.11 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 228.86 228.860 228.86 228.86 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 297.57 297.573 297.57 297.57 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 239.76 239.765 239.76 239.76 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 297.78 297.780 297.78 297.78 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 297.56 297.565 297.56 297.56 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 239.71 239.712 239.71 239.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 297.68 297.684 297.68 297.68 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Sec1.1A-General Information

Data
Weather File ANNUAL ** Helena Regional Airport MT USA TMY3 WMO#=727720
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
UNHEATEDBSMT 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 2820.66 207496.39 0.00 0.00
Space Cooling 13021.40 11907.72 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6842.09 3266.23 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3210.82 151011.69 0.00 0.00
Receptacle Equipment 76678.43 12003.41 1639.73 20110.29 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 112044.71   7671.21   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 261812.16 382567.40
Natural Gas 163973.19 767121.04
Additional 0.00 0.00
Total 425785.36 1149688.44


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 0.33
Fans-Interior 0.18
Service Water Heating 0.00
Receptacle Equipment 1.97
Miscellaneous 0.07
Subtotal 2.87


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 2.12
Service Water Heating 2.41
Miscellaneous 1.23
Subtotal 5.76


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 3.85
Space Heating 24.53
Space Cooling 3.87
Fans-Interior 2.03
Service Water Heating 27.93
Receptacle Equipment 37.03
Miscellaneous 0.76



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 968.79
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 242.90
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 325.38
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 493.60
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 226.41
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 324.13
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 512.98
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 252.93
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 324.60
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 493.88
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 235.82
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 324.13
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 324.63
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 329.31
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 546.15
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 286.44
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 290.05
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 541.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 968.79
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 242.90
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.38
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 493.60
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 226.41
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 324.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 512.98
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.93
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.60
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.88
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.82
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 546.15
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 290.05
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.31
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 541.68
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 286.44
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 324.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 968.79 2.15 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 242.90 0.539610 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 325.38 0.722856 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 493.60 1.10 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 226.41 0.502997 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 324.13 0.720088 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 512.98 1.14 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 252.93 0.561896 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 324.60 0.721132 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 493.88 1.10 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 235.82 0.523882 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 324.13 0.720069 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 546.15 1.21 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 290.05 0.644378 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 329.31 0.731584 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 541.68 1.20 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 286.44 0.636348 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 324.63 0.721184 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 968.79 968.79 968.79 6099.92 2.15 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 242.90 242.90 242.90 13207.83 0.539610 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 325.38 325.38 325.38 15926.24 0.722856 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 493.60 493.60 493.60 15911.63 1.10 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 226.41 226.41 226.41 13206.36 0.502997 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 324.13 324.13 324.13 15921.37 0.720088 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 512.98 512.98 512.98 14461.20 1.14 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 252.93 252.93 252.93 11753.44 0.561896 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 324.60 324.60 324.60 14474.90 0.721132 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 493.88 493.88 493.88 14463.16 1.10 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 235.82 235.82 235.82 11751.63 0.523882 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 324.13 324.13 324.13 14470.20 0.720069 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 546.15 546.15 546.15 17705.39 1.21 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 290.05 290.05 290.05 14983.99 0.644378 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 329.31 329.31 329.31 17715.12 0.731584 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 541.68 541.68 541.68 17705.01 1.20 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 286.44 286.44 286.44 14981.52 0.636348 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 324.63 324.63 324.63 17710.60 0.721184 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 968.79
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 242.90
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 325.38
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 493.60
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 226.41
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 324.13
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 512.98
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 252.93
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 324.60
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 493.88
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 235.82
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 324.13
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 546.15
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 290.05
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 329.31
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 541.68
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 286.44
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 324.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 6099.92
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 13207.83
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 15926.24
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 15911.63
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13206.36
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 15921.37
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 14461.20
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 11753.44
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 14474.90
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 14463.16
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 11751.63
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 14470.20
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 17705.39
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 14983.99
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 17715.12
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 17705.01
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 14981.52
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 17710.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:48:15

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 682.514 58.362 7.250 0.310 58.672
February 628.555 62.794 6.960 0.347 63.141
March 744.000 95.728 0.000 0.000 95.728
April 718.000 113.588 0.000 0.000 113.588
May 744.000 144.774 0.000 0.000 144.774
June 720.000 170.698 0.000 0.000 170.698
July 744.000 195.112 0.000 0.000 195.112
August 744.000 183.075 0.000 0.000 183.075
September 720.000 158.464 0.000 0.000 158.464
October 744.000 115.897 0.000 0.000 115.897
November 720.000 83.051 0.000 0.000 83.051
December 683.467 55.959 0.000 0.000 55.959
           
Annual Sum or Average 8592.536 1437.502 14.210 0.657 1438.159
Minimum of Months 628.555 55.959 0.000 0.000 55.959
Maximum of Months 744.000 195.112 7.250 0.347 195.112



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 687.025 18.340 18.340
February 0.917 0.002 587.683 14.301 14.303
March 64.846 1.708 535.458 8.996 10.704
April 145.813 4.596 339.308 5.203 9.800
May 299.284 9.615 154.937 1.249 10.864
June 510.007 22.661 8.333 0.026 22.687
July 665.882 34.372 0.000 0.000 34.372
August 577.661 29.159 3.750 0.010 29.169
September 425.339 20.204 63.625 0.340 20.544
October 184.916 5.234 353.354 4.511 9.745
November 42.613 0.446 542.212 9.806 10.252
December 6.125 0.056 670.638 19.099 19.155
           
Annual Sum or Average 2923.401 128.053 3946.325 81.881 209.934
Minimum of Months 0.000 0.000 0.000 0.000 9.745
Maximum of Months 665.882 34.372 687.025 19.099 34.372



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 721.117 29.776 29.776
February 0.000 0.000 624.420 22.877 22.877
March 57.964 1.905 562.192 14.634 16.538
April 169.856 6.521 332.088 7.931 14.452
May 376.334 16.483 185.583 2.409 18.892
June 529.459 35.133 31.958 0.197 35.330
July 642.917 49.897 3.000 0.009 49.906
August 570.035 40.956 15.750 0.092 41.049
September 411.253 25.952 95.167 1.006 26.958
October 163.321 5.311 412.354 8.404 13.716
November 14.400 0.196 605.167 17.325 17.521
December 1.250 0.004 719.392 31.057 31.062
           
Annual Sum or Average 2936.790 182.359 4308.186 135.718 318.076
Minimum of Months 0.000 0.000 3.000 0.009 13.716
Maximum of Months 642.917 49.897 721.117 31.057 49.906



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 52.749 52.749
February 0.000 0.000 658.308 40.798 40.798
March 23.385 0.607 627.246 27.104 27.711
April 108.621 4.349 442.917 15.343 19.692
May 255.842 14.492 243.517 4.580 19.072
June 465.978 31.987 42.125 0.348 32.335
July 614.561 46.552 6.000 0.029 46.580
August 502.368 34.244 29.972 0.223 34.467
September 310.730 18.251 152.621 2.334 20.585
October 49.975 1.247 534.417 16.897 18.144
November 0.000 0.000 688.079 32.653 32.653
December 0.000 0.000 744.000 54.089 54.089
           
Annual Sum or Average 2331.461 151.728 4913.201 247.147 398.874
Minimum of Months 0.000 0.000 6.000 0.029 18.144
Maximum of Months 614.561 46.552 744.000 54.089 54.089



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 22.479 22.479
February 0.000 0.000 672.000 18.212 18.212
March 8.958 0.113 671.025 12.050 12.163
April 63.042 1.286 458.389 6.381 7.667
May 247.769 7.138 193.833 1.483 8.620
June 500.640 20.509 9.990 0.028 20.537
July 667.582 30.906 0.000 0.000 30.906
August 558.403 22.931 5.400 0.017 22.948
September 334.786 11.277 100.708 0.581 11.858
October 23.301 0.261 543.713 6.616 6.877
November 0.000 0.000 677.646 13.598 13.598
December 0.000 0.000 742.750 22.986 22.986
           
Annual Sum or Average 2404.482 94.420 4819.454 104.431 198.852
Minimum of Months 0.000 0.000 0.000 0.000 6.877
Maximum of Months 667.582 30.906 744.000 22.986 30.906



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 35.153 35.153
February 0.000 0.000 672.000 27.838 27.838
March 12.563 0.224 684.244 18.224 18.448
April 103.721 2.570 400.767 9.000 11.570
May 347.360 13.622 192.225 2.578 16.200
June 526.758 33.197 32.467 0.197 33.394
July 643.017 46.679 3.000 0.009 46.688
August 563.566 35.127 17.125 0.103 35.230
September 351.297 17.071 111.600 1.210 18.281
October 33.354 0.296 568.649 10.779 11.075
November 0.000 0.000 713.208 22.009 22.009
December 0.000 0.000 744.000 36.283 36.283
           
Annual Sum or Average 2581.636 148.785 4883.284 163.384 312.169
Minimum of Months 0.000 0.000 3.000 0.009 11.075
Maximum of Months 643.017 46.679 744.000 36.283 46.688



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 4.000 0.048 686.946 39.261 39.309
February 20.625 0.592 560.036 29.022 29.614
March 98.325 4.024 481.583 17.742 21.766
April 195.989 10.197 318.083 10.203 20.400
May 333.591 19.886 150.833 2.456 22.342
June 529.563 38.139 14.056 0.088 38.227
July 668.081 54.630 0.000 0.000 54.630
August 581.446 44.556 5.550 0.044 44.600
September 424.377 30.231 74.000 0.924 31.155
October 188.837 8.257 370.728 10.189 18.447
November 48.625 0.858 539.042 21.304 22.161
December 5.542 0.099 677.433 41.009 41.108
           
Annual Sum or Average 3099.001 211.516 3878.290 172.242 383.758
Minimum of Months 4.000 0.048 0.000 0.000 18.447
Maximum of Months 668.081 54.630 686.946 41.009 54.630



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 660.071 17.045 17.045
February 7.000 0.024 550.392 13.070 13.095
March 75.631 2.101 466.575 7.609 9.710
April 181.444 5.633 278.811 4.211 9.844
May 352.467 12.118 108.318 0.787 12.905
June 576.833 26.714 1.250 0.001 26.715
July 718.926 39.203 0.000 0.000 39.203
August 647.331 33.494 0.000 0.000 33.494
September 487.912 23.370 34.096 0.162 23.532
October 210.680 6.364 305.619 3.708 10.072
November 53.900 0.780 499.604 8.692 9.472
December 9.937 0.083 640.538 17.893 17.976
           
Annual Sum or Average 3322.062 149.885 3545.273 73.180 223.064
Minimum of Months 0.000 0.000 0.000 0.000 9.472
Maximum of Months 718.926 39.203 660.071 17.893 39.203



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 707.958 27.448 27.448
February 0.000 0.000 599.946 20.707 20.707
March 66.718 2.271 530.833 12.510 14.781
April 199.391 7.736 286.121 6.483 14.219
May 412.422 19.414 139.333 1.602 21.016
June 569.899 39.083 12.083 0.065 39.148
July 686.932 54.344 0.000 0.000 54.344
August 614.979 44.969 4.250 0.032 45.000
September 458.403 28.845 69.500 0.631 29.476
October 186.532 6.293 373.150 7.074 13.366
November 23.258 0.319 579.062 15.486 15.805
December 1.500 0.008 711.542 28.763 28.771
           
Annual Sum or Average 3220.033 203.280 4013.779 120.801 324.081
Minimum of Months 0.000 0.000 0.000 0.000 13.366
Maximum of Months 686.932 54.344 711.542 28.763 54.344



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 49.843 49.843
February 0.000 0.000 654.650 37.884 37.884
March 26.345 0.705 597.892 23.949 24.654
April 129.900 5.040 402.326 12.809 17.849
May 295.698 16.605 186.105 3.223 19.828
June 518.100 35.739 18.257 0.123 35.862
July 668.142 51.180 0.000 0.000 51.180
August 560.911 38.133 8.050 0.080 38.212
September 361.229 20.632 116.854 1.563 22.195
October 63.861 1.437 496.092 14.782 16.219
November 0.000 0.000 666.975 30.141 30.141
December 0.000 0.000 744.000 51.194 51.194
           
Annual Sum or Average 2624.186 169.470 4635.200 225.591 395.061
Minimum of Months 0.000 0.000 0.000 0.000 16.219
Maximum of Months 668.142 51.180 744.000 51.194 51.194



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 21.334 21.334
February 0.000 0.000 672.000 17.004 17.004
March 13.938 0.197 638.125 10.392 10.588
April 80.911 1.852 378.616 5.015 6.867
May 312.612 9.524 127.380 0.887 10.411
June 572.386 24.739 0.625 0.000 24.739
July 719.767 35.974 0.000 0.000 35.974
August 635.545 27.430 1.500 0.002 27.432
September 399.857 14.097 59.875 0.282 14.379
October 39.329 0.459 472.155 5.490 5.949
November 0.000 0.000 651.542 12.426 12.426
December 0.000 0.000 739.500 21.855 21.855
           
Annual Sum or Average 2774.345 114.272 4485.317 94.687 208.959
Minimum of Months 0.000 0.000 0.000 0.000 5.949
Maximum of Months 719.767 35.974 744.000 21.855 35.974



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 33.249 33.249
February 0.000 0.000 672.000 25.960 25.960
March 17.521 0.322 663.500 15.991 16.312
April 118.274 3.334 339.994 7.397 10.731
May 399.619 16.613 148.958 1.751 18.364
June 566.327 37.284 11.417 0.064 37.347
July 687.385 51.360 0.000 0.000 51.360
August 609.677 39.375 4.833 0.035 39.410
September 398.732 19.796 83.000 0.780 20.577
October 43.050 0.539 525.386 9.311 9.850
November 0.000 0.000 696.250 20.312 20.312
December 0.000 0.000 744.000 34.397 34.397
           
Annual Sum or Average 2840.585 168.622 4633.339 149.247 317.869
Minimum of Months 0.000 0.000 0.000 0.000 9.850
Maximum of Months 687.385 51.360 744.000 34.397 51.360



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 733.983 53.483 53.483
February 5.076 0.085 626.992 40.454 40.539
March 53.875 2.074 574.375 26.504 28.578
April 148.725 7.557 400.271 15.467 23.024
May 280.413 17.935 233.052 4.846 22.780
June 484.693 38.001 39.875 0.375 38.376
July 639.239 56.227 5.321 0.026 56.254
August 543.224 44.484 30.535 0.243 44.726
September 367.904 27.936 120.375 2.099 30.035
October 125.379 5.073 448.107 15.786 20.858
November 10.667 0.095 628.054 31.422 31.516
December 0.000 0.000 728.250 55.054 55.054
           
Annual Sum or Average 2659.194 199.466 4569.190 245.758 445.224
Minimum of Months 0.000 0.000 5.321 0.026 20.858
Maximum of Months 639.239 56.227 733.983 55.054 56.254



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 728.896 25.776 25.776
February 0.000 0.000 640.054 20.029 20.029
March 42.586 1.028 589.821 12.841 13.870
April 126.150 4.052 383.599 7.163 11.215
May 291.018 10.784 185.550 1.873 12.656
June 523.319 27.011 17.625 0.055 27.066
July 690.309 41.200 0.000 0.000 41.200
August 593.369 33.743 8.750 0.033 33.776
September 412.152 21.389 77.056 0.580 21.970
October 137.176 3.438 400.608 6.600 10.038
November 6.750 0.045 607.792 14.466 14.511
December 0.000 0.000 722.688 26.493 26.493
           
Annual Sum or Average 2822.829 142.690 4362.438 115.910 258.600
Minimum of Months 0.000 0.000 0.000 0.000 10.038
Maximum of Months 690.309 41.200 728.896 26.493 41.200



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 739.208 33.112 33.112
February 0.000 0.000 654.733 25.466 25.466
March 40.329 1.187 612.208 16.369 17.557
April 140.667 5.442 362.271 8.446 13.888
May 359.476 16.663 184.208 2.473 19.136
June 546.056 38.459 28.625 0.162 38.622
July 674.300 55.511 2.000 0.004 55.515
August 592.851 44.462 14.933 0.086 44.548
September 406.418 26.358 96.662 1.052 27.410
October 126.036 3.450 440.617 9.318 12.768
November 2.250 0.016 642.083 19.681 19.697
December 0.000 0.000 731.554 34.275 34.275
           
Annual Sum or Average 2888.382 191.548 4509.104 150.444 341.992
Minimum of Months 0.000 0.000 2.000 0.004 12.768
Maximum of Months 674.300 55.511 739.208 34.275 55.515



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 61.035 61.035
February 0.000 0.000 665.979 46.998 46.998
March 20.958 0.499 640.812 31.149 31.648
April 111.469 4.483 445.617 17.138 21.621
May 266.863 16.487 248.744 5.149 21.636
June 483.544 37.142 40.583 0.368 37.510
July 643.440 54.778 5.750 0.027 54.806
August 531.923 40.633 33.111 0.274 40.907
September 327.322 21.129 154.354 2.674 23.802
October 45.500 1.044 545.958 19.652 20.696
November 0.000 0.000 710.000 38.263 38.263
December 0.000 0.000 744.000 62.435 62.435
           
Annual Sum or Average 2431.019 176.194 4978.909 285.163 461.357
Minimum of Months 0.000 0.000 5.750 0.027 20.696
Maximum of Months 643.440 54.778 744.000 62.435 62.435



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 30.391 30.391
February 0.000 0.000 672.000 24.209 24.209
March 7.812 0.113 683.125 15.955 16.068
April 70.958 1.765 455.292 8.245 10.009
May 265.110 9.579 201.758 2.008 11.587
June 522.759 26.280 17.806 0.048 26.327
July 695.068 39.867 0.000 0.000 39.867
August 582.703 30.040 10.250 0.038 30.079
September 346.987 14.726 114.574 0.842 15.568
October 22.788 0.285 557.792 9.083 9.368
November 0.000 0.000 691.542 18.628 18.628
December 0.000 0.000 744.000 30.974 30.974
           
Annual Sum or Average 2514.185 122.655 4892.138 140.421 263.076
Minimum of Months 0.000 0.000 0.000 0.000 9.368
Maximum of Months 695.068 39.867 744.000 30.974 39.867



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 37.244 37.244
February 0.000 0.000 672.000 29.224 29.224
March 8.937 0.182 689.958 19.159 19.341
April 98.059 2.705 430.794 9.190 11.895
May 344.978 15.227 188.997 2.543 17.771
June 545.175 37.681 27.875 0.157 37.839
July 675.313 54.139 2.000 0.004 54.143
August 589.520 40.885 15.400 0.090 40.975
September 365.914 19.656 113.896 1.208 20.864
October 20.854 0.229 584.208 11.587 11.816
November 0.000 0.000 718.354 23.573 23.573
December 0.000 0.000 744.000 38.298 38.298
           
Annual Sum or Average 2648.750 170.706 4931.483 172.277 342.983
Minimum of Months 0.000 0.000 2.000 0.004 11.816
Maximum of Months 675.313 54.139 744.000 38.298 54.143



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5.24 0.00
February 0.00 6.50 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.94 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6.50 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2676.54 0.00
February 0.00 2310.71 0.00
March 0.00 1312.94 0.00
April 0.00 784.72 0.00
May 0.00 182.22 0.00
June 0.00 3.94 0.00
July 0.00 0.00 0.00
August 0.00 1.45 0.00
September 0.00 51.33 0.00
October 0.00 658.30 0.00
November 0.00 1478.76 0.00
December 0.00 2787.34 0.00
       
Annual Sum or Average 0.00 1014.92 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2787.34 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3911.55 0.00
February 0.00 3327.34 0.00
March 0.00 1922.38 0.00
April 0.00 1076.57 0.00
May 0.00 316.47 0.00
June 0.00 26.81 0.00
July 0.00 1.15 0.00
August 0.00 12.13 0.00
September 0.00 136.62 0.00
October 0.00 1104.07 0.00
November 0.00 2351.74 0.00
December 0.00 4079.93 0.00
       
Annual Sum or Average 0.00 1514.23 0.00
Minimum of Months 0.00 1.15 0.00
Maximum of Months 0.00 4079.93 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4563.72 0.00
February 0.00 3907.90 0.00
March 0.00 2344.93 0.00
April 0.00 1371.67 0.00
May 0.00 396.28 0.00
June 0.00 31.13 0.00
July 0.00 2.48 0.00
August 0.00 19.28 0.00
September 0.00 208.69 0.00
October 0.00 1461.90 0.00
November 0.00 2919.24 0.00
December 0.00 4679.64 0.00
       
Annual Sum or Average 0.00 1816.05 0.00
Minimum of Months 0.00 2.48 0.00
Maximum of Months 0.00 4679.64 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3519.06 0.00
February 0.00 3156.57 0.00
March 0.00 1886.40 0.00
April 0.00 1032.23 0.00
May 0.00 232.09 0.00
June 0.00 4.48 0.00
July 0.00 0.00 0.00
August 0.00 2.65 0.00
September 0.00 93.97 0.00
October 0.00 1035.74 0.00
November 0.00 2199.68 0.00
December 0.00 3598.41 0.00
       
Annual Sum or Average 0.00 1388.49 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3598.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4634.33 0.00
February 0.00 4063.16 0.00
March 0.00 2402.49 0.00
April 0.00 1226.03 0.00
May 0.00 339.86 0.00
June 0.00 26.86 0.00
July 0.00 1.22 0.00
August 0.00 13.61 0.00
September 0.00 164.83 0.00
October 0.00 1420.98 0.00
November 0.00 2998.18 0.00
December 0.00 4783.33 0.00
       
Annual Sum or Average 0.00 1829.36 0.00
Minimum of Months 0.00 1.22 0.00
Maximum of Months 0.00 4783.33 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2970.49 0.00
February 0.00 2431.10 0.00
March 0.00 1342.35 0.00
April 0.00 797.66 0.00
May 0.00 185.84 0.00
June 0.00 6.92 0.00
July 0.00 0.00 0.00
August 0.00 3.37 0.00
September 0.00 72.23 0.00
October 0.00 770.93 0.00
November 0.00 1665.57 0.00
December 0.00 3102.77 0.00
       
Annual Sum or Average 0.00 1106.82 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3102.77 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2125.87 0.00
February 0.00 1804.81 0.00
March 0.00 949.04 0.00
April 0.00 542.65 0.00
May 0.00 98.16 0.00
June 0.00 0.18 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 20.91 0.00
October 0.00 462.48 0.00
November 0.00 1120.24 0.00
December 0.00 2231.60 0.00
       
Annual Sum or Average 0.00 775.17 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2231.60 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3284.97 0.00
February 0.00 2743.77 0.00
March 0.00 1497.21 0.00
April 0.00 801.80 0.00
May 0.00 191.78 0.00
June 0.00 8.05 0.00
July 0.00 0.00 0.00
August 0.00 3.77 0.00
September 0.00 78.04 0.00
October 0.00 846.62 0.00
November 0.00 1915.17 0.00
December 0.00 3442.38 0.00
       
Annual Sum or Average 0.00 1227.91 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3442.38 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3917.50 0.00
February 0.00 3296.62 0.00
March 0.00 1882.32 0.00
April 0.00 1040.31 0.00
May 0.00 253.30 0.00
June 0.00 10.01 0.00
July 0.00 0.00 0.00
August 0.00 6.25 0.00
September 0.00 126.95 0.00
October 0.00 1161.78 0.00
November 0.00 2447.96 0.00
December 0.00 4023.69 0.00
       
Annual Sum or Average 0.00 1505.90 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4023.69 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2853.37 0.00
February 0.00 2517.97 0.00
March 0.00 1389.90 0.00
April 0.00 693.09 0.00
May 0.00 118.65 0.00
June 0.00 0.04 0.00
July 0.00 0.00 0.00
August 0.00 0.22 0.00
September 0.00 38.98 0.00
October 0.00 734.25 0.00
November 0.00 1717.41 0.00
December 0.00 2923.13 0.00
       
Annual Sum or Average 0.00 1075.60 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2923.13 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3983.83 0.00
February 0.00 3443.85 0.00
March 0.00 1915.99 0.00
April 0.00 915.85 0.00
May 0.00 209.79 0.00
June 0.00 7.88 0.00
July 0.00 0.00 0.00
August 0.00 4.15 0.00
September 0.00 96.63 0.00
October 0.00 1115.62 0.00
November 0.00 2514.89 0.00
December 0.00 4121.49 0.00
       
Annual Sum or Average 0.00 1518.80 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4121.49 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4653.52 0.00
February 0.00 3896.97 0.00
March 0.00 2306.08 0.00
April 0.00 1390.60 0.00
May 0.00 421.61 0.00
June 0.00 33.69 0.00
July 0.00 2.30 0.00
August 0.00 21.12 0.00
September 0.00 188.71 0.00
October 0.00 1373.48 0.00
November 0.00 2825.10 0.00
December 0.00 4790.16 0.00
       
Annual Sum or Average 0.00 1816.10 0.00
Minimum of Months 0.00 2.30 0.00
Maximum of Months 0.00 4790.16 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3573.77 0.00
February 0.00 3074.47 0.00
March 0.00 1780.40 0.00
April 0.00 1026.28 0.00
May 0.00 259.66 0.00
June 0.00 7.84 0.00
July 0.00 0.00 0.00
August 0.00 4.58 0.00
September 0.00 83.16 0.00
October 0.00 915.12 0.00
November 0.00 2072.57 0.00
December 0.00 3673.23 0.00
       
Annual Sum or Average 0.00 1364.90 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3673.23 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4780.66 0.00
February 0.00 4070.69 0.00
March 0.00 2363.43 0.00
April 0.00 1260.07 0.00
May 0.00 357.09 0.00
June 0.00 24.24 0.00
July 0.00 0.59 0.00
August 0.00 12.49 0.00
September 0.00 156.93 0.00
October 0.00 1345.29 0.00
November 0.00 2936.19 0.00
December 0.00 4948.61 0.00
       
Annual Sum or Average 0.00 1844.81 0.00
Minimum of Months 0.00 0.59 0.00
Maximum of Months 0.00 4948.61 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5354.24 0.00
February 0.00 4564.61 0.00
March 0.00 2732.55 0.00
April 0.00 1553.55 0.00
May 0.00 451.70 0.00
June 0.00 33.38 0.00
July 0.00 2.40 0.00
August 0.00 24.05 0.00
September 0.00 242.36 0.00
October 0.00 1723.91 0.00
November 0.00 3468.45 0.00
December 0.00 5476.99 0.00
       
Annual Sum or Average 0.00 2124.61 0.00
Minimum of Months 0.00 2.40 0.00
Maximum of Months 0.00 5476.99 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4266.13 0.00
February 0.00 3762.41 0.00
March 0.00 2239.65 0.00
April 0.00 1195.90 0.00
May 0.00 281.86 0.00
June 0.00 6.89 0.00
July 0.00 0.00 0.00
August 0.00 5.37 0.00
September 0.00 122.18 0.00
October 0.00 1275.05 0.00
November 0.00 2702.13 0.00
December 0.00 4348.01 0.00
       
Annual Sum or Average 0.00 1674.13 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4348.01 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5453.49 0.00
February 0.00 4737.59 0.00
March 0.00 2805.29 0.00
April 0.00 1390.47 0.00
May 0.00 372.41 0.00
June 0.00 23.81 0.00
July 0.00 0.56 0.00
August 0.00 13.17 0.00
September 0.00 182.80 0.00
October 0.00 1696.63 0.00
November 0.00 3566.67 0.00
December 0.00 5607.81 0.00
       
Annual Sum or Average 0.00 2142.45 0.00
Minimum of Months 0.00 0.56 0.00
Maximum of Months 0.00 5607.81 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.34
February 0.00 0.00 0.41
March 0.00 0.00 0.55
April 0.00 0.00 0.67
May 0.00 0.00 0.81
June 0.00 0.00 0.98
July 0.00 0.00 1.07
August 0.00 0.00 1.01
September 0.00 0.00 0.92
October 0.00 0.00 0.66
November 0.00 0.00 0.49
December 0.00 0.00 0.33
       
Annual Sum or Average 0.00 0.00 0.69
Minimum of Months 0.00 0.00 0.33
Maximum of Months 0.00 0.00 1.07



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.05
June 0.00 0.00 0.13
July 0.00 0.00 0.19
August 0.00 0.00 0.16
September 0.00 0.00 0.12
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.09
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.22
September 0.00 0.00 0.15
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.08
June 0.00 0.00 0.18
July 0.00 0.00 0.25
August 0.00 0.00 0.18
September 0.00 0.00 0.10
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.04
June 0.00 0.00 0.11
July 0.00 0.00 0.17
August 0.00 0.00 0.12
September 0.00 0.00 0.06
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.19
July 0.00 0.00 0.25
August 0.00 0.00 0.19
September 0.00 0.00 0.09
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.06
May 0.00 0.00 0.11
June 0.00 0.00 0.21
July 0.00 0.00 0.29
August 0.00 0.00 0.24
September 0.00 0.00 0.17
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.15
July 0.00 0.00 0.21
August 0.00 0.00 0.18
September 0.00 0.00 0.13
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.11
June 0.00 0.00 0.22
July 0.00 0.00 0.30
August 0.00 0.00 0.25
September 0.00 0.00 0.16
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.09
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.20
September 0.00 0.00 0.11
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.20
August 0.00 0.00 0.15
September 0.00 0.00 0.08
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.09
June 0.00 0.00 0.21
July 0.00 0.00 0.28
August 0.00 0.00 0.21
September 0.00 0.00 0.11
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.10
June 0.00 0.00 0.21
July 0.00 0.00 0.30
August 0.00 0.00 0.24
September 0.00 0.00 0.15
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.22
August 0.00 0.00 0.18
September 0.00 0.00 0.12
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.09
June 0.00 0.00 0.22
July 0.00 0.00 0.31
August 0.00 0.00 0.24
September 0.00 0.00 0.15
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.09
June 0.00 0.00 0.20
July 0.00 0.00 0.29
August 0.00 0.00 0.21
September 0.00 0.00 0.12
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.05
June 0.00 0.00 0.15
July 0.00 0.00 0.22
August 0.00 0.00 0.16
September 0.00 0.00 0.08
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.21
July 0.00 0.00 0.30
August 0.00 0.00 0.22
September 0.00 0.00 0.11
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:48:15

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1779.79 1325.10
February 0.00 0.00 1814.19 1220.00
March 0.00 0.00 1793.86 1335.58
April 0.00 0.00 1738.20 1252.39
May 0.00 0.00 1646.00 1225.49
June 0.00 0.00 1550.66 1117.27
July 0.00 0.00 1479.51 1101.54
August 0.00 0.00 1442.36 1073.88
September 0.00 0.00 1459.96 1051.92
October 0.00 0.00 1523.37 1134.19
November 0.00 0.00 1610.57 1160.43
December 0.00 0.00 1709.15 1272.51
         
Annual Sum or Average 0.00 0.00 1627.88 14270.31
Minimum of Months 0.00 0.00 1442.36 1051.92
Maximum of Months 0.00 0.00 1814.19 1335.58