Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2015-09-09 19:00:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 6975.30 | 890.11 | 988.02 |
Net Site Energy | 6975.30 | 890.11 | 988.02 |
Total Source Energy | 14138.33 | 1804.17 | 2002.63 |
Net Source Energy | 14138.33 | 1804.17 | 2002.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 673.86 | 2349.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 668.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 426.74 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1467.86 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3157.51 | 3817.79 | 0.00 | 0.00 | 0.00 | 5205.26 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2349.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 673.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 161.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 668.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 426.74 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1467.86 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 64.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 216.13 | 540.77 | 0.00 | 0.00 | 0.00 | 0.74 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 447.25 | 540.77 | 0.00 | 0.00 | 0.00 | 0.74 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 194.71 | 487.18 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 402.93 | 487.18 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3157.51 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3157.51 | 100.00 |
Total On-Site and Utility Electric Sources | 3157.51 | 100.00 |
Total Electricity End Uses | 3157.51 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5205.26 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5205.26 | 100.00 |
Total Water End Uses | 5205.26 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 115.25 |
Time Setpoint Not Met During Occupied Cooling | 28.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4220.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59 |
RunPeriod | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JAN-23:00 | 29-JAN-07:00 | - | - | - | 29-JUL-17:15 |
Heating | 261078.47 | 254312.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7484.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 29363.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21186.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1756.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 89941.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 332168.45 | 344253.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 254312.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 6390.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 1093.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 29363.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 21186.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1756.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 89941.37 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 2134.12 | 2547.32 | 0.00 | 0.00 | 0.00 |
Cooling | 392.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 511.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2115.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 174.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 15.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1591.16 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9999.85 | 4138.48 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 302.29 | 360.82 | 0.00 | 0.00 | 0.00 |
Cooling | 55.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 299.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 225.38 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1416.43 | 586.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 302.29 | 360.82 | 0.00 | 0.00 | 0.00 |
Cooling | 55.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 299.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 225.38 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1416.43 | 586.20 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.219 | 0.228 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.42_SHGC_0.45 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.493 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.42_SHGC_0.45 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.493 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.42_SHGC_0.45 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.493 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.493 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.493 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.493 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.06 | 83.06 | 161.58 | |
Exterior Lighting Total | 10364.00 | 161.58 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 247552.88 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 198042.30 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3265.29 | 2545.80 | 719.49 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2420.70 | 1906.71 | 513.99 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5143.49 | 4004.00 | 1139.49 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2383.21 | 1903.52 | 479.69 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1619.08 | 1332.09 | 286.99 | 0.82 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1613.17 | 1329.66 | 283.51 | 0.82 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2499.75 | 1941.97 | 557.78 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2593.10 | 2013.98 | 579.12 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4363.84 | 3401.16 | 962.68 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3088.38 | 2421.98 | 666.40 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4559.12 | 3543.62 | 1015.51 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2482.40 | 1967.78 | 514.62 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1592.03 | 1277.82 | 314.21 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1571.16 | 1261.79 | 309.37 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3391.90 | 2634.25 | 757.65 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3426.42 | 2660.88 | 765.54 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4395.62 | 3428.70 | 966.93 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3132.65 | 2460.09 | 672.56 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4292.86 | 3342.20 | 950.66 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2532.79 | 2010.47 | 522.32 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1653.88 | 1327.82 | 326.06 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1633.37 | 1312.06 | 321.31 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3449.28 | 2680.97 | 768.31 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3465.81 | 2693.72 | 772.09 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4395.47 | 3431.61 | 963.85 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3133.71 | 2463.92 | 669.79 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4267.37 | 3325.53 | 941.83 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2532.55 | 2013.07 | 519.48 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1661.47 | 1335.50 | 325.96 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1640.97 | 1319.75 | 321.22 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3458.07 | 2689.59 | 768.48 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.10 | 2700.42 | 771.69 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4419.48 | 3452.62 | 966.86 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3158.44 | 2485.40 | 673.04 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4290.57 | 3345.89 | 944.68 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2555.59 | 2033.14 | 522.46 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1690.38 | 1359.23 | 331.15 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1669.93 | 1343.50 | 326.43 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3488.24 | 2714.37 | 773.86 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3501.89 | 2724.90 | 776.99 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4364.80 | 3412.52 | 952.28 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3104.02 | 2445.58 | 658.44 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4238.42 | 3307.71 | 930.71 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2502.11 | 1993.68 | 508.43 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1641.83 | 1323.18 | 318.66 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1621.47 | 1307.52 | 313.95 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3438.51 | 2677.28 | 761.23 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3452.12 | 2687.78 | 764.34 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4340.19 | 3395.37 | 944.82 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3080.11 | 2428.98 | 651.13 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4215.88 | 3292.13 | 923.75 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2490.45 | 1983.01 | 507.44 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1622.39 | 1309.33 | 313.06 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1602.10 | 1293.73 | 308.37 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3418.17 | 2662.70 | 755.47 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3431.75 | 2673.18 | 758.57 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4331.01 | 3389.93 | 941.08 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3072.78 | 2424.94 | 647.83 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4208.44 | 3288.01 | 920.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2482.97 | 1978.69 | 504.28 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1619.84 | 1308.36 | 311.48 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1599.67 | 1292.84 | 306.83 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3412.81 | 2659.58 | 753.23 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3426.40 | 2670.06 | 756.34 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4408.67 | 3452.45 | 956.22 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3159.65 | 2493.34 | 666.32 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4280.34 | 3345.04 | 935.30 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2514.10 | 2004.13 | 509.97 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1697.06 | 1368.64 | 328.41 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1676.06 | 1352.49 | 323.57 | 0.81 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.54 | 2706.62 | 765.93 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3487.82 | 2718.40 | 769.42 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5172.71 | 4039.50 | 1133.21 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3727.97 | 2932.23 | 795.74 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4928.12 | 3846.69 | 1081.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2892.70 | 2294.93 | 597.77 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1879.16 | 1505.98 | 373.18 | 0.80 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1914.77 | 1519.41 | 395.36 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4319.07 | 3360.83 | 958.24 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4334.29 | 3372.57 | 961.72 | 0.78 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3265.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2420.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5143.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2383.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1619.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1613.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2499.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2593.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4363.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3088.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4559.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2482.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1592.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1571.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3391.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3426.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4395.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3132.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4292.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2532.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1653.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1633.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3449.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3465.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4395.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3133.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4267.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2532.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1661.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1640.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3458.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4419.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3158.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4290.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2555.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1690.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1669.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3488.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3501.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4364.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3104.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4238.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2502.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1641.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1621.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3438.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3452.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4340.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3080.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4215.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2490.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1622.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1602.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3418.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3431.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4331.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3072.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4208.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2482.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1619.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1599.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3412.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3426.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4408.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3159.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4280.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2514.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1697.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1676.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3487.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5172.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3727.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4928.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2892.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1879.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1914.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4319.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4334.29 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 5905.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 5918.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 7328.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 5916.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 4891.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 4891.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 4877.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 4883.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 4951.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 4945.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 4966.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 4943.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 3763.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 3763.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 3772.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 3773.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 4745.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 4741.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 4743.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 4738.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 3551.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 3551.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 3556.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 3556.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 4721.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 4718.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 4718.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 4714.89 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 3517.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 3517.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 3521.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 3521.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 4702.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 4698.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 4698.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 4694.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 3490.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 3490.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 3496.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 3496.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 4754.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 4750.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 4750.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 4746.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 3533.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 3533.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 3538.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 3538.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 4783.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 4778.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 4778.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 4774.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 3555.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 3555.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 3561.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 3561.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 4826.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 4821.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 4821.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 4816.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 3593.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 3593.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 3600.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 3600.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 5074.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 5064.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 5069.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 5059.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 3820.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 3820.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 3831.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 3831.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 6182.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 6182.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 6177.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 6177.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 5008.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 5008.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 5006.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 5006.24 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 275.58 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.46 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 432.06 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.36 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 155.79 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 155.79 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.43 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.25 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 369.14 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 266.34 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 383.07 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.67 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 145.34 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 143.60 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.82 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 286.72 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 372.06 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 270.68 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 361.40 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.50 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.88 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 149.17 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 289.03 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.41 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 372.54 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 271.25 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 359.74 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.93 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 151.80 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.10 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.06 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 291.24 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 374.95 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 273.71 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 362.08 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 224.22 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 154.45 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 152.75 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 292.83 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.97 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 370.70 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 269.50 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 358.04 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 220.03 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.61 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 148.91 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 288.87 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.01 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 368.93 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 267.79 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 356.44 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 218.35 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 149.16 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 147.47 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 287.34 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 288.48 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 368.43 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 267.43 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 356.08 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 217.95 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 149.11 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 147.43 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 287.06 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 288.19 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 375.58 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 274.94 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 362.36 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 220.79 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 155.69 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 153.94 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 292.21 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.50 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 438.62 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 320.90 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 416.95 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 251.89 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.86 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 166.66 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 363.34 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 364.61 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0054 | 1719.50 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2487.05 | 2984.46 | 0.198 | 0.237 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
G NW APARTMENT | 1722.29 | 2066.75 | 0.137 | 0.164 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
OFFICE | 3899.32 | 4679.19 | 0.310 | 0.372 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40 | 0.00698 |
G NE APARTMENT | 1317.87 | 1581.45 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
G N1 APARTMENT | 839.62 | 1007.55 | 0.067 | 0.080 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
G N2 APARTMENT | 822.37 | 986.84 | 0.065 | 0.078 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
G S1 APARTMENT | 1881.06 | 2257.27 | 0.150 | 0.180 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
G S2 APARTMENT | 1951.62 | 2341.94 | 0.155 | 0.186 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F2 SW APARTMENT | 3331.43 | 3997.72 | 0.265 | 0.318 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F2 NW APARTMENT | 2403.62 | 2884.35 | 0.191 | 0.229 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F2 SE APARTMENT | 3457.15 | 4148.58 | 0.275 | 0.330 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F2 NE APARTMENT | 1955.41 | 2346.49 | 0.156 | 0.187 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F2 N1 APARTMENT | 1311.60 | 1573.92 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F2 N2 APARTMENT | 1295.94 | 1555.13 | 0.103 | 0.124 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F2 S1 APARTMENT | 2561.47 | 3073.76 | 0.204 | 0.244 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F2 S2 APARTMENT | 2587.57 | 3105.09 | 0.206 | 0.247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F3 SW APARTMENT | 3357.83 | 4029.39 | 0.267 | 0.321 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
F3 NW APARTMENT | 2442.85 | 2931.42 | 0.194 | 0.233 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F3 SE APARTMENT | 3261.59 | 3913.91 | 0.259 | 0.311 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F3 NE APARTMENT | 1999.03 | 2398.84 | 0.159 | 0.191 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F3 N1 APARTMENT | 1361.61 | 1633.93 | 0.108 | 0.130 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F3 N2 APARTMENT | 1346.21 | 1615.45 | 0.107 | 0.129 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F3 S1 APARTMENT | 2608.43 | 3130.11 | 0.207 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F3 S2 APARTMENT | 2620.93 | 3145.11 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F4 SW APARTMENT | 3362.13 | 4034.55 | 0.267 | 0.321 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
F4 NW APARTMENT | 2448.02 | 2937.63 | 0.195 | 0.234 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F4 SE APARTMENT | 3246.66 | 3895.99 | 0.258 | 0.310 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F4 NE APARTMENT | 2002.86 | 2403.44 | 0.159 | 0.191 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F4 N1 APARTMENT | 1369.98 | 1643.97 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F4 N2 APARTMENT | 1354.57 | 1625.48 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F4 S1 APARTMENT | 2617.75 | 3141.30 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F4 S2 APARTMENT | 2628.36 | 3154.04 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
M SW APARTMENT | 3383.90 | 4060.68 | 0.269 | 0.323 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
M NW APARTMENT | 2470.21 | 2964.25 | 0.196 | 0.236 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
M SE APARTMENT | 3267.78 | 3921.34 | 0.260 | 0.312 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
M NE APARTMENT | 2023.61 | 2428.33 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
M N1 APARTMENT | 1393.86 | 1672.63 | 0.111 | 0.133 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
M N2 APARTMENT | 1378.48 | 1654.17 | 0.110 | 0.132 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
M S1 APARTMENT | 2642.76 | 3171.31 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
M S2 APARTMENT | 2653.08 | 3183.70 | 0.211 | 0.253 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F6 SW APARTMENT | 3345.56 | 4014.67 | 0.266 | 0.319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
F6 NW APARTMENT | 2432.17 | 2918.61 | 0.193 | 0.232 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F6 SE APARTMENT | 3231.31 | 3877.58 | 0.257 | 0.308 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F6 NE APARTMENT | 1985.74 | 2382.88 | 0.158 | 0.190 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
F6 N1 APARTMENT | 1359.19 | 1631.02 | 0.108 | 0.130 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F6 N2 APARTMENT | 1343.87 | 1612.65 | 0.107 | 0.128 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F6 S1 APARTMENT | 2606.99 | 3128.39 | 0.207 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F6 S2 APARTMENT | 2617.29 | 3140.74 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F7 SW APARTMENT | 3329.60 | 3995.53 | 0.265 | 0.318 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
F7 NW APARTMENT | 2416.76 | 2900.11 | 0.192 | 0.231 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F7 SE APARTMENT | 3216.90 | 3860.27 | 0.256 | 0.307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F7 NE APARTMENT | 1970.58 | 2364.70 | 0.157 | 0.188 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 24.67 | 0.00698 |
F7 N1 APARTMENT | 1346.15 | 1615.38 | 0.107 | 0.128 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F7 N2 APARTMENT | 1330.90 | 1597.07 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F7 S1 APARTMENT | 2593.24 | 3111.89 | 0.206 | 0.248 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F7 S2 APARTMENT | 2603.51 | 3124.21 | 0.207 | 0.249 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F8 SW APARTMENT | 3325.05 | 3990.06 | 0.264 | 0.317 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
F8 NW APARTMENT | 2413.56 | 2896.27 | 0.192 | 0.230 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F8 SE APARTMENT | 3213.62 | 3856.35 | 0.256 | 0.307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F8 NE APARTMENT | 1967.01 | 2360.41 | 0.156 | 0.188 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 24.67 | 0.00698 |
F8 N1 APARTMENT | 1345.65 | 1614.78 | 0.107 | 0.128 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F8 N2 APARTMENT | 1330.47 | 1596.56 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F8 S1 APARTMENT | 2590.65 | 3108.78 | 0.206 | 0.247 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F8 S2 APARTMENT | 2600.92 | 3121.11 | 0.207 | 0.248 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F9 SW APARTMENT | 3389.59 | 4067.51 | 0.270 | 0.324 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
F9 NW APARTMENT | 2481.27 | 2977.52 | 0.197 | 0.237 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
F9 SE APARTMENT | 3270.27 | 3924.32 | 0.260 | 0.312 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
F9 NE APARTMENT | 1992.61 | 2391.13 | 0.158 | 0.190 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 24.67 | 0.00698 |
F9 N1 APARTMENT | 1405.03 | 1686.03 | 0.112 | 0.134 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F9 N2 APARTMENT | 1389.22 | 1667.06 | 0.111 | 0.133 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
F9 S1 APARTMENT | 2637.21 | 3164.65 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
F9 S2 APARTMENT | 2648.76 | 3178.52 | 0.211 | 0.253 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
T SW APARTMENT | 3958.52 | 4750.23 | 0.315 | 0.378 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 26.94 | 0.00698 |
T NW APARTMENT | 2896.12 | 3475.35 | 0.230 | 0.276 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
T SE APARTMENT | 3763.00 | 4515.60 | 0.299 | 0.359 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40 | 0.00698 |
T NE APARTMENT | 2273.36 | 2728.04 | 0.181 | 0.217 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 25.05 | 0.00698 |
T N1 APARTMENT | 1532.95 | 1839.53 | 0.122 | 0.146 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:45:00 | 21.61 | 0.00698 |
T N2 APARTMENT | 1504.06 | 1804.87 | 0.120 | 0.144 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
T S1 APARTMENT | 3279.10 | 3934.92 | 0.261 | 0.313 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
T S2 APARTMENT | 3290.61 | 3948.73 | 0.262 | 0.314 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 3331.07 | 3997.28 | 0.151 | 0.181 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G NW APARTMENT | 3342.11 | 4010.53 | 0.151 | 0.181 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
OFFICE | 3756.47 | 4507.77 | 0.170 | 0.204 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -41.90 | 0.00006 |
G NE APARTMENT | 3340.61 | 4008.74 | 0.151 | 0.181 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N1 APARTMENT | 2473.98 | 2968.77 | 0.112 | 0.134 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N2 APARTMENT | 2473.95 | 2968.73 | 0.112 | 0.134 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S1 APARTMENT | 2461.62 | 2953.94 | 0.111 | 0.134 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S2 APARTMENT | 2466.91 | 2960.29 | 0.112 | 0.134 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
F2 SW APARTMENT | 2524.98 | 3029.97 | 0.114 | 0.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 NW APARTMENT | 2519.88 | 3023.85 | 0.114 | 0.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 SE APARTMENT | 2537.61 | 3045.13 | 0.115 | 0.138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 NE APARTMENT | 2517.54 | 3021.04 | 0.114 | 0.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 N1 APARTMENT | 1519.86 | 1823.84 | 0.069 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 N2 APARTMENT | 1519.82 | 1823.78 | 0.069 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 S1 APARTMENT | 1527.92 | 1833.51 | 0.069 | 0.083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F2 S2 APARTMENT | 1528.76 | 1834.51 | 0.069 | 0.083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 SW APARTMENT | 2350.15 | 2820.18 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 NW APARTMENT | 2346.96 | 2816.35 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 SE APARTMENT | 2348.85 | 2818.62 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 NE APARTMENT | 2344.19 | 2813.03 | 0.106 | 0.127 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 N1 APARTMENT | 1340.39 | 1608.47 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 N2 APARTMENT | 1340.33 | 1608.40 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 S1 APARTMENT | 1344.93 | 1613.92 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F3 S2 APARTMENT | 1345.00 | 1614.00 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 SW APARTMENT | 2330.34 | 2796.41 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 NW APARTMENT | 2327.58 | 2793.10 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 SE APARTMENT | 2327.38 | 2792.86 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 NE APARTMENT | 2324.48 | 2789.37 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 N1 APARTMENT | 1311.76 | 1574.11 | 0.059 | 0.071 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 N2 APARTMENT | 1311.69 | 1574.03 | 0.059 | 0.071 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 S1 APARTMENT | 1315.62 | 1578.74 | 0.059 | 0.071 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F4 S2 APARTMENT | 1315.57 | 1578.68 | 0.059 | 0.071 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M SW APARTMENT | 2314.11 | 2776.93 | 0.105 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M NW APARTMENT | 2310.40 | 2772.49 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M SE APARTMENT | 2310.77 | 2772.92 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M NE APARTMENT | 2307.05 | 2768.46 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M N1 APARTMENT | 1288.95 | 1546.74 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M N2 APARTMENT | 1288.88 | 1546.65 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M S1 APARTMENT | 1293.81 | 1552.57 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
M S2 APARTMENT | 1293.74 | 1552.49 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 SW APARTMENT | 2357.98 | 2829.58 | 0.107 | 0.128 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 NW APARTMENT | 2354.60 | 2825.52 | 0.106 | 0.128 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 SE APARTMENT | 2354.41 | 2825.29 | 0.106 | 0.128 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 NE APARTMENT | 2351.01 | 2821.21 | 0.106 | 0.128 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 N1 APARTMENT | 1325.57 | 1590.68 | 0.060 | 0.072 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 N2 APARTMENT | 1325.49 | 1590.59 | 0.060 | 0.072 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 S1 APARTMENT | 1329.99 | 1595.99 | 0.060 | 0.072 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F6 S2 APARTMENT | 1329.91 | 1595.90 | 0.060 | 0.072 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 SW APARTMENT | 2382.11 | 2858.53 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 NW APARTMENT | 2378.25 | 2853.89 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 SE APARTMENT | 2378.34 | 2854.00 | 0.108 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 NE APARTMENT | 2374.47 | 2849.37 | 0.107 | 0.129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 N1 APARTMENT | 1344.41 | 1613.29 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 N2 APARTMENT | 1344.33 | 1613.20 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 S1 APARTMENT | 1349.34 | 1619.20 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F7 S2 APARTMENT | 1349.26 | 1619.11 | 0.061 | 0.073 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 SW APARTMENT | 2418.92 | 2902.71 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 NW APARTMENT | 2414.28 | 2897.14 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 SE APARTMENT | 2414.99 | 2897.98 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 NE APARTMENT | 2410.34 | 2892.41 | 0.109 | 0.131 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 N1 APARTMENT | 1376.51 | 1651.81 | 0.062 | 0.075 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 N2 APARTMENT | 1376.42 | 1651.71 | 0.062 | 0.075 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 S1 APARTMENT | 1382.23 | 1658.68 | 0.062 | 0.075 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F8 S2 APARTMENT | 1382.15 | 1658.58 | 0.062 | 0.075 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 SW APARTMENT | 2628.29 | 3153.95 | 0.119 | 0.143 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 NW APARTMENT | 2619.77 | 3143.72 | 0.118 | 0.142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 SE APARTMENT | 2624.16 | 3149.00 | 0.119 | 0.142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 NE APARTMENT | 2615.64 | 3138.76 | 0.118 | 0.142 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 N1 APARTMENT | 1567.91 | 1881.49 | 0.071 | 0.085 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 N2 APARTMENT | 1567.82 | 1881.38 | 0.071 | 0.085 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 S1 APARTMENT | 1577.15 | 1892.58 | 0.071 | 0.086 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
F9 S2 APARTMENT | 1577.06 | 1892.47 | 0.071 | 0.086 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T SW APARTMENT | 3565.43 | 4278.51 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T NW APARTMENT | 3565.68 | 4278.82 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T SE APARTMENT | 3561.41 | 4273.69 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T NE APARTMENT | 3561.66 | 4273.99 | 0.161 | 0.193 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T N1 APARTMENT | 2573.13 | 3087.75 | 0.116 | 0.140 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T N2 APARTMENT | 2573.04 | 3087.65 | 0.116 | 0.140 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T S1 APARTMENT | 2570.95 | 3085.14 | 0.116 | 0.139 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
T S2 APARTMENT | 2570.86 | 3085.03 | 0.116 | 0.139 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -41.90 | 0.00006 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.24 | 0.24 | 0.18 | 0.18 |
AIRLOOP G NW | 0.16 | 0.16 | 0.18 | 0.18 |
AIRLOOP OFFICE | 0.37 | 0.37 | 0.20 | 0.20 |
AIRLOOP G NE | 0.13 | 0.13 | 0.18 | 0.18 |
AIRLOOP G N1 | 0.08 | 0.08 | 0.13 | 0.13 |
AIRLOOP G N2 | 0.08 | 0.08 | 0.13 | 0.13 |
AIRLOOP G S1 | 0.18 | 0.18 | 0.13 | 0.13 |
AIRLOOP G S2 | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F2 SW | 0.32 | 0.32 | 0.14 | 0.14 |
AIRLOOP F2 NW | 0.23 | 0.23 | 0.14 | 0.14 |
AIRLOOP F2 SE | 0.33 | 0.33 | 0.14 | 0.14 |
AIRLOOP F2 NE | 0.19 | 0.19 | 0.14 | 0.14 |
AIRLOOP F2 N1 | 0.13 | 0.13 | 0.08 | 0.08 |
AIRLOOP F2 N2 | 0.12 | 0.12 | 0.08 | 0.08 |
AIRLOOP F2 S1 | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP F2 S2 | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F3 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F3 NW | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F3 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F3 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F3 N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F3 N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F3 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F3 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F4 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F4 NW | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F4 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F4 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F4 N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F4 N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F4 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F4 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP M SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP M NW | 0.24 | 0.24 | 0.13 | 0.13 |
AIRLOOP M SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP M NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP M N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP M N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP M S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP M S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F6 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F6 NW | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F6 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F6 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F6 N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F6 N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F6 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F6 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F7 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F7 NW | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F7 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F7 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F7 N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F7 N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F7 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F7 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F8 SW | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP F8 NW | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F8 SE | 0.31 | 0.31 | 0.13 | 0.13 |
AIRLOOP F8 NE | 0.19 | 0.19 | 0.13 | 0.13 |
AIRLOOP F8 N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F8 N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F8 S1 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F8 S2 | 0.25 | 0.25 | 0.07 | 0.07 |
AIRLOOP F9 SW | 0.32 | 0.32 | 0.14 | 0.14 |
AIRLOOP F9 NW | 0.24 | 0.24 | 0.14 | 0.14 |
AIRLOOP F9 SE | 0.31 | 0.31 | 0.14 | 0.14 |
AIRLOOP F9 NE | 0.19 | 0.19 | 0.14 | 0.14 |
AIRLOOP F9 N1 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP F9 N2 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP F9 S1 | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP F9 S2 | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP T SW | 0.38 | 0.38 | 0.19 | 0.19 |
AIRLOOP T NW | 0.28 | 0.28 | 0.19 | 0.19 |
AIRLOOP T SE | 0.36 | 0.36 | 0.19 | 0.19 |
AIRLOOP T NE | 0.22 | 0.22 | 0.19 | 0.19 |
AIRLOOP T N1 | 0.15 | 0.15 | 0.14 | 0.14 |
AIRLOOP T N2 | 0.14 | 0.14 | 0.14 | 0.14 |
AIRLOOP T S1 | 0.31 | 0.31 | 0.14 | 0.14 |
AIRLOOP T S2 | 0.31 | 0.31 | 0.14 | 0.14 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4317.75 | 6955.00 | 3414.50 |
G NW APARTMENT | 4427.25 | 7627.25 | 3949.00 |
OFFICE | 1260.75 | 1363.75 | 695.50 |
G NE APARTMENT | 4525.50 | 7469.75 | 3891.25 |
G N1 APARTMENT | 3751.50 | 7806.25 | 3456.25 |
G N2 APARTMENT | 3753.75 | 7790.75 | 3454.00 |
G S1 APARTMENT | 3527.00 | 7039.25 | 2743.50 |
G S2 APARTMENT | 3540.50 | 6936.75 | 2697.25 |
F2 SW APARTMENT | 4127.50 | 5888.50 | 2484.50 |
F2 NW APARTMENT | 4206.00 | 6928.75 | 3119.75 |
F2 SE APARTMENT | 4290.75 | 5638.25 | 2289.50 |
F2 NE APARTMENT | 4216.00 | 6798.00 | 3026.00 |
F2 N1 APARTMENT | 2479.75 | 7122.00 | 1611.00 |
F2 N2 APARTMENT | 2486.00 | 7112.75 | 1608.50 |
F2 S1 APARTMENT | 2696.75 | 5758.50 | 1109.25 |
F2 S2 APARTMENT | 2716.25 | 5719.00 | 1092.00 |
F3 SW APARTMENT | 4036.75 | 5748.50 | 2243.00 |
F3 NW APARTMENT | 4082.50 | 6773.00 | 2906.25 |
F3 SE APARTMENT | 4182.50 | 5639.50 | 2188.50 |
F3 NE APARTMENT | 4099.25 | 6651.25 | 2792.50 |
F3 N1 APARTMENT | 2222.00 | 6935.75 | 1199.75 |
F3 N2 APARTMENT | 2228.25 | 6917.00 | 1198.50 |
F3 S1 APARTMENT | 2515.00 | 5533.00 | 732.00 |
F3 S2 APARTMENT | 2534.25 | 5515.75 | 730.25 |
F4 SW APARTMENT | 4037.25 | 5740.75 | 2205.50 |
F4 NW APARTMENT | 4073.25 | 6732.50 | 2880.75 |
F4 SE APARTMENT | 4154.75 | 5656.75 | 2168.25 |
F4 NE APARTMENT | 4087.25 | 6618.75 | 2766.50 |
F4 N1 APARTMENT | 2213.00 | 6848.25 | 1147.75 |
F4 N2 APARTMENT | 2221.00 | 6832.50 | 1146.75 |
F4 S1 APARTMENT | 2525.75 | 5496.50 | 677.00 |
F4 S2 APARTMENT | 2535.00 | 5487.50 | 675.25 |
M SW APARTMENT | 3986.50 | 5762.50 | 2167.00 |
M NW APARTMENT | 4026.50 | 6748.25 | 2833.25 |
M SE APARTMENT | 4111.00 | 5676.75 | 2134.75 |
M NE APARTMENT | 4035.75 | 6638.00 | 2725.25 |
M N1 APARTMENT | 2166.50 | 6839.50 | 1083.25 |
M N2 APARTMENT | 2178.25 | 6823.50 | 1083.50 |
M S1 APARTMENT | 2480.25 | 5497.50 | 621.25 |
M S2 APARTMENT | 2488.00 | 5488.75 | 619.50 |
F6 SW APARTMENT | 3971.00 | 5872.75 | 2272.75 |
F6 NW APARTMENT | 4064.50 | 6879.50 | 2952.50 |
F6 SE APARTMENT | 4103.50 | 5774.00 | 2234.25 |
F6 NE APARTMENT | 4062.00 | 6760.75 | 2840.75 |
F6 N1 APARTMENT | 2177.75 | 6974.50 | 1191.00 |
F6 N2 APARTMENT | 2183.25 | 6961.50 | 1189.50 |
F6 S1 APARTMENT | 2460.25 | 5616.00 | 725.25 |
F6 S2 APARTMENT | 2475.00 | 5605.25 | 723.25 |
F7 SW APARTMENT | 3951.00 | 5964.25 | 2337.25 |
F7 NW APARTMENT | 4072.50 | 6974.75 | 3009.00 |
F7 SE APARTMENT | 4099.75 | 5860.25 | 2293.75 |
F7 NE APARTMENT | 4078.75 | 6858.50 | 2906.75 |
F7 N1 APARTMENT | 2171.75 | 7081.75 | 1250.00 |
F7 N2 APARTMENT | 2178.25 | 7063.75 | 1249.00 |
F7 S1 APARTMENT | 2436.50 | 5704.75 | 780.00 |
F7 S2 APARTMENT | 2452.50 | 5687.75 | 778.50 |
F8 SW APARTMENT | 3947.75 | 6049.75 | 2408.25 |
F8 NW APARTMENT | 4094.75 | 7059.00 | 3073.00 |
F8 SE APARTMENT | 4102.25 | 5932.50 | 2364.00 |
F8 NE APARTMENT | 4105.75 | 6943.00 | 2974.75 |
F8 N1 APARTMENT | 2218.25 | 7166.25 | 1341.25 |
F8 N2 APARTMENT | 2225.00 | 7151.00 | 1338.00 |
F8 S1 APARTMENT | 2447.50 | 5790.50 | 858.50 |
F8 S2 APARTMENT | 2460.75 | 5776.50 | 857.00 |
F9 SW APARTMENT | 4130.00 | 6173.75 | 2664.25 |
F9 NW APARTMENT | 4289.25 | 7130.00 | 3305.00 |
F9 SE APARTMENT | 4263.50 | 6043.75 | 2613.50 |
F9 NE APARTMENT | 4310.50 | 7027.50 | 3214.00 |
F9 N1 APARTMENT | 2632.75 | 7243.75 | 1789.50 |
F9 N2 APARTMENT | 2637.25 | 7237.50 | 1783.25 |
F9 S1 APARTMENT | 2733.25 | 5937.00 | 1253.00 |
F9 S2 APARTMENT | 2748.75 | 5918.25 | 1250.50 |
T SW APARTMENT | 5092.25 | 6445.25 | 3626.00 |
T NW APARTMENT | 5051.00 | 7169.50 | 4091.00 |
T SE APARTMENT | 5166.00 | 6356.25 | 3571.25 |
T NE APARTMENT | 5095.75 | 7110.25 | 4024.50 |
T N1 APARTMENT | 4398.75 | 7335.75 | 3559.00 |
T N2 APARTMENT | 4405.00 | 7327.25 | 3558.25 |
T S1 APARTMENT | 4446.25 | 6277.75 | 2958.75 |
T S2 APARTMENT | 4459.25 | 6262.25 | 2955.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6543.00 | 7890.75 | 4220.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
G NW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
OFFICE | 2.75 | 0.00 | 0.75 | 0.00 |
G NE APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
G N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
G N2 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
G S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F2 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F2 NW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F2 SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F2 NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F2 N1 APARTMENT | 0.50 | 2.75 | 0.50 | 2.75 |
F2 N2 APARTMENT | 0.75 | 3.00 | 0.75 | 3.00 |
F2 S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F2 S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F3 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F3 NW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F3 SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F3 NE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F3 N1 APARTMENT | 1.25 | 6.25 | 1.25 | 6.25 |
F3 N2 APARTMENT | 0.75 | 7.25 | 0.75 | 7.25 |
F3 S1 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
F3 S2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F4 SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F4 NW APARTMENT | 1.25 | 0.75 | 1.25 | 0.75 |
F4 SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F4 NE APARTMENT | 1.50 | 0.25 | 1.50 | 0.25 |
F4 N1 APARTMENT | 2.25 | 8.25 | 2.25 | 8.25 |
F4 N2 APARTMENT | 1.25 | 10.00 | 1.25 | 10.00 |
F4 S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F4 S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NW APARTMENT | 2.75 | 1.00 | 2.75 | 1.00 |
M SE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M NE APARTMENT | 2.25 | 0.75 | 2.25 | 0.75 |
M N1 APARTMENT | 2.00 | 10.00 | 2.00 | 10.00 |
M N2 APARTMENT | 1.25 | 11.25 | 1.25 | 11.25 |
M S1 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
M S2 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F6 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F6 NW APARTMENT | 1.25 | 1.50 | 1.25 | 1.50 |
F6 SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F6 NE APARTMENT | 1.50 | 1.00 | 1.50 | 1.00 |
F6 N1 APARTMENT | 0.75 | 10.75 | 0.75 | 10.75 |
F6 N2 APARTMENT | 0.50 | 11.50 | 0.50 | 11.50 |
F6 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F6 S2 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F7 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F7 NW APARTMENT | 1.50 | 1.75 | 1.50 | 1.75 |
F7 SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F7 NE APARTMENT | 3.25 | 1.75 | 3.25 | 1.75 |
F7 N1 APARTMENT | 1.00 | 11.25 | 1.00 | 11.25 |
F7 N2 APARTMENT | 1.50 | 12.25 | 1.50 | 12.25 |
F7 S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F7 S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F8 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F8 NW APARTMENT | 1.50 | 1.75 | 1.50 | 1.75 |
F8 SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F8 NE APARTMENT | 3.25 | 2.25 | 3.25 | 2.25 |
F8 N1 APARTMENT | 1.00 | 11.25 | 1.00 | 11.25 |
F8 N2 APARTMENT | 0.25 | 12.00 | 0.25 | 12.00 |
F8 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F8 S2 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
F9 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F9 NW APARTMENT | 1.00 | 1.75 | 1.00 | 1.75 |
F9 SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F9 NE APARTMENT | 2.50 | 3.25 | 2.50 | 3.25 |
F9 N1 APARTMENT | 0.50 | 10.50 | 0.50 | 10.50 |
F9 N2 APARTMENT | 1.50 | 11.25 | 1.50 | 11.25 |
F9 S1 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F9 S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NW APARTMENT | 0.25 | 0.75 | 0.25 | 0.75 |
T SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NE APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
T N1 APARTMENT | 6.25 | 28.25 | 6.25 | 28.25 |
T N2 APARTMENT | 4.25 | 24.75 | 4.25 | 24.75 |
T S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 117.00 | 28.25 | 115.25 | 28.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.114 | 0.000 | 0.190 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.114 | 0.000 | 0.183 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.520 | 0.110 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.114 | 0.000 | 0.186 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.069 | 0.000 | 0.179 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.069 | 0.000 | 0.180 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.069 | 0.000 | 0.188 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.069 | 0.000 | 0.188 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.164 | 0.000 | 0.213 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.164 | 0.000 | 0.208 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.164 | 0.000 | 0.214 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.164 | 0.000 | 0.210 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.099 | 0.000 | 0.205 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.099 | 0.000 | 0.205 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.099 | 0.000 | 0.212 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.099 | 0.000 | 0.212 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.226 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.222 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.226 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.194 | 0.000 | 0.224 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.117 | 0.000 | 0.219 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.117 | 0.000 | 0.219 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.117 | 0.000 | 0.225 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.117 | 0.000 | 0.225 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.217 | 0.000 | 0.224 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.217 | 0.000 | 0.222 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.217 | 0.000 | 0.225 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.217 | 0.000 | 0.223 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.219 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.131 | 0.000 | 0.219 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.131 | 0.000 | 0.224 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.131 | 0.000 | 0.224 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.236 | 0.000 | 0.232 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.236 | 0.000 | 0.230 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.236 | 0.000 | 0.233 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.236 | 0.000 | 0.231 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.142 | 0.000 | 0.227 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.142 | 0.000 | 0.228 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.142 | 0.000 | 0.232 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.142 | 0.000 | 0.232 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.252 | 0.000 | 0.239 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.252 | 0.000 | 0.237 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.252 | 0.000 | 0.240 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.252 | 0.000 | 0.238 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.152 | 0.000 | 0.234 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.152 | 0.000 | 0.234 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.152 | 0.000 | 0.239 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.152 | 0.000 | 0.239 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.267 | 0.000 | 0.245 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.266 | 0.000 | 0.243 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.267 | 0.000 | 0.246 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.266 | 0.000 | 0.244 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.161 | 0.000 | 0.240 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.161 | 0.000 | 0.240 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.161 | 0.000 | 0.245 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.161 | 0.000 | 0.245 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.279 | 0.000 | 0.251 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.279 | 0.000 | 0.248 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.279 | 0.000 | 0.252 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.279 | 0.000 | 0.249 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.245 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.168 | 0.000 | 0.246 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.169 | 0.000 | 0.250 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.169 | 0.000 | 0.250 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.291 | 0.000 | 0.257 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.291 | 0.000 | 0.254 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.291 | 0.000 | 0.257 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.291 | 0.000 | 0.255 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.175 | 0.000 | 0.251 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.175 | 0.000 | 0.251 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.176 | 0.000 | 0.256 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.176 | 0.000 | 0.256 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.302 | 0.000 | 0.260 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.302 | 0.000 | 0.258 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.302 | 0.000 | 0.261 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.302 | 0.000 | 0.259 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.182 | 0.000 | 0.255 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.182 | 0.000 | 0.255 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.182 | 0.000 | 0.260 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.182 | 0.000 | 0.260 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.503 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 668.13 | 21186.30 | 01-JAN-00:15 | 21186.30 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1502.13 | 21847.55 | 03-JUL-02:30 | 283199.94 | 28-JAN-24:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
ElectricityPurchased:Plant | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
Cogeneration:ElectricityPurchased | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
ElectricityNet:Plant | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
Cogeneration:ElectricityNet | 3157.51 | 47645.33 | 03-JUL-02:45 | 332168.45 | 28-JAN-24:00 |
ExteriorLights:Electricity | 161.58 | 0.00 | 01-JAN-11:30 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 161.58 | 0.00 | 01-JAN-11:30 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 668.13 | 21186.30 | 01-JAN-00:15 | 21186.30 | 01-JAN-00:15 |
Cooling:Electricity | 123.96 | 0.00 | 01-JAN-00:15 | 59159.15 | 21-JUL-14:15 |
Heating:Electricity | 673.86 | 0.00 | 17-APR-13:45 | 261078.47 | 28-JAN-24:00 |
Electricity:Plant | 59.92 | 36.93 | 17-APR-19:15 | 3756.57 | 29-JUL-16:15 |
HeatRejection:Electricity | 4.75 | 0.00 | 01-JAN-00:15 | 2000.14 | 29-JUL-16:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 55.17 | 36.93 | 17-APR-19:15 | 1756.43 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 3817.79 | 2357.00 | 13-APR-23:30 | 344253.99 | 29-JAN-08:00 |
Gas:Plant | 3817.79 | 2357.00 | 13-APR-23:30 | 344253.99 | 29-JAN-08:00 |
WaterSystems:Gas | 1467.86 | 2357.00 | 01-JAN-00:15 | 91426.54 | 13-MAR-07:00 |
Water Heater:WaterSystems:Gas | 1467.86 | 2357.00 | 01-JAN-00:15 | 91426.54 | 13-MAR-07:00 |
Heating:Gas | 2349.92 | 0.00 | 20-MAR-13:00 | 265464.84 | 29-JAN-00:45 |
Boiler:Heating:Gas | 2349.92 | 0.00 | 20-MAR-13:00 | 265464.84 | 29-JAN-00:45 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 478.22 | 0.00 | 01-JAN-00:15 | 256470.00 | 30-JUN-12:30 |
PlantLoopCoolingDemand:HVAC | 478.22 | 0.00 | 01-JAN-00:15 | 256470.00 | 30-JUN-12:30 |
CoolingCoils:PlantLoopCoolingDemand | 478.22 | 0.00 | 01-JAN-00:15 | 256470.00 | 30-JUN-12:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5205.26 | 0.00 | 01-JAN-02:15 | 0.00 | 29-JUL-17:15 |
Water:Plant | 5205.26 | 0.00 | 01-JAN-02:15 | 0.00 | 29-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5205.26 | 0.00 | 01-JAN-02:15 | 0.00 | 29-JUL-17:15 |
MainsWater:Plant | 5205.26 | 0.00 | 01-JAN-02:15 | 0.00 | 29-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 426.74 | 0.00 | 01-JAN-00:15 | 0.00 | 21-JUL-16:00 |
HeatRejection:MainsWater | 426.74 | 0.00 | 01-JAN-00:15 | 0.00 | 21-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 2948.45 | 648.32 | 18-AUG-01:30 | 263893.59 | 29-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 1146.99 | 643.92 | 10-SEP-01:30 | 71343.61 | 12-DEC-07:45 |
WaterSystems:PlantLoopHeatingDemand | 1146.99 | 643.92 | 10-SEP-01:30 | 71343.61 | 12-DEC-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 7531.77 | 6250.24 | 08-AUG-01:15 | 1045645.47 | 28-JAN-24:00 |
EnergyTransfer:Building | 1811.91 | 4002.68 | 18-JUN-17:00 | 364683.21 | 28-JAN-24:00 |
EnergyTransfer:Zone:G SW APARTMENT | 25.50 | 0.03 | 02-SEP-16:30 | 3812.46 | 28-JAN-24:00 |
Heating:EnergyTransfer | 1330.03 | 0.00 | 22-MAR-16:15 | 364683.21 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 21.59 | 0.00 | 09-FEB-11:45 | 3812.46 | 28-JAN-24:00 |
Cooling:EnergyTransfer | 481.88 | 0.00 | 01-JAN-00:15 | 175298.29 | 11-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 3.91 | 0.00 | 01-JAN-00:15 | 2330.98 | 11-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 27.35 | 0.06 | 02-JUL-19:45 | 3879.07 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 25.07 | 0.00 | 22-MAR-15:15 | 3879.07 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 2.28 | 0.00 | 01-JAN-00:15 | 1906.10 | 11-JUL-17:45 |
EnergyTransfer:Zone:OFFICE | 28.81 | 0.01 | 24-SEP-18:30 | 3833.06 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:OFFICE | 16.80 | 0.00 | 17-JAN-11:30 | 3833.06 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 12.01 | 0.00 | 01-JAN-00:15 | 3672.07 | 10-AUG-13:45 |
EnergyTransfer:Zone:G NE APARTMENT | 27.12 | 0.02 | 22-JUN-21:00 | 3886.95 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 24.54 | 0.00 | 20-MAR-09:45 | 3886.95 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 2.58 | 0.00 | 01-JAN-00:15 | 1388.83 | 11-JUL-05:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 18.58 | 0.02 | 16-JUL-10:15 | 2435.98 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 16.17 | 0.00 | 22-MAR-16:15 | 2435.98 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 1018.53 | 11-JUL-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 18.57 | 0.01 | 03-JUL-18:45 | 2436.10 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 16.14 | 0.00 | 22-MAR-16:15 | 2436.10 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 2.43 | 0.00 | 01-JAN-00:15 | 1014.47 | 11-JUL-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 17.03 | 0.00 | 16-AUG-12:45 | 2345.02 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 12.69 | 0.00 | 09-FEB-11:15 | 2345.02 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 4.35 | 0.00 | 01-JAN-00:15 | 1846.91 | 21-JUL-14:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 16.92 | 0.01 | 02-JUL-19:45 | 2339.45 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 12.40 | 0.00 | 09-FEB-11:15 | 2339.45 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 4.52 | 0.00 | 01-JAN-00:15 | 1909.96 | 21-JUL-14:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 25.11 | 0.00 | 26-JUN-03:45 | 4440.65 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 17.58 | 0.00 | 09-FEB-11:30 | 4440.65 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 7.53 | 0.00 | 01-JAN-00:15 | 3131.67 | 11-AUG-16:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 25.46 | 0.09 | 26-JUL-16:45 | 4567.23 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 21.55 | 0.00 | 18-MAR-15:15 | 4567.23 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 3.91 | 0.00 | 01-JAN-00:15 | 2499.14 | 11-JUL-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 26.02 | 0.05 | 06-AUG-12:00 | 4431.19 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 16.23 | 0.00 | 09-FEB-11:15 | 4431.19 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 9.78 | 0.00 | 01-JAN-00:15 | 3318.73 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 25.77 | 0.00 | 16-JUL-12:30 | 4581.18 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 20.91 | 0.00 | 18-MAR-12:15 | 4581.18 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 4.86 | 0.00 | 01-JAN-00:15 | 1993.08 | 11-JUL-16:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 14.89 | 0.02 | 22-MAY-16:00 | 2662.24 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 10.73 | 0.00 | 07-FEB-21:00 | 2662.24 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 4.16 | 0.00 | 01-JAN-00:15 | 1280.01 | 11-JUL-16:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 14.91 | 0.00 | 07-JUN-15:45 | 2662.42 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 10.70 | 0.00 | 07-FEB-21:00 | 2662.42 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 4.20 | 0.00 | 01-JAN-00:15 | 1264.84 | 11-JUL-16:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 15.81 | 0.03 | 21-JAN-21:15 | 2535.29 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 7.80 | 0.00 | 16-JAN-13:00 | 2535.29 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 8.01 | 0.00 | 01-JAN-00:15 | 2507.10 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 15.91 | 0.10 | 21-MAR-23:30 | 2533.91 | 21-JUL-14:15 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 7.73 | 0.00 | 16-JAN-13:00 | 2533.57 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 8.18 | 0.00 | 01-JAN-00:15 | 2533.91 | 21-JUL-14:15 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 25.11 | 0.09 | 25-JUN-00:15 | 4853.48 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 16.88 | 0.00 | 23-JAN-13:00 | 4853.48 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 8.23 | 0.00 | 01-JAN-00:15 | 3200.17 | 11-AUG-16:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 25.17 | 0.00 | 30-APR-03:15 | 4985.76 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 20.86 | 0.00 | 18-MAR-12:45 | 4985.76 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 4.30 | 0.00 | 01-JAN-00:15 | 2536.78 | 11-JUL-17:15 |
EnergyTransfer:Zone:F3 SE APARTMENT | 26.05 | 0.10 | 29-MAY-13:00 | 4865.00 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 16.38 | 0.00 | 23-JAN-12:45 | 4865.00 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 9.68 | 0.00 | 01-JAN-00:15 | 3321.35 | 22-JUL-12:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 25.56 | 0.12 | 07-JUN-11:15 | 5002.13 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 20.25 | 0.00 | 18-MAR-09:30 | 5002.13 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 5.31 | 0.00 | 01-JAN-00:15 | 2085.89 | 13-JUN-06:45 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 14.23 | 0.03 | 09-AUG-12:00 | 2856.30 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 9.61 | 0.00 | 21-JAN-20:45 | 2856.30 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 4.61 | 0.00 | 01-JAN-00:15 | 1361.79 | 29-JUN-19:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 14.24 | 0.01 | 13-MAY-19:00 | 2856.50 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 9.58 | 0.00 | 21-JAN-20:45 | 2856.50 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 4.66 | 0.00 | 01-JAN-00:15 | 1346.62 | 29-JUN-19:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 15.95 | 0.50 | 07-APR-07:45 | 2719.67 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 6.81 | 0.00 | 16-JAN-12:45 | 2719.67 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 9.15 | 0.00 | 01-JAN-00:15 | 2585.26 | 21-JUL-14:15 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 16.03 | 0.02 | 27-FEB-13:30 | 2719.34 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 6.78 | 0.00 | 16-JAN-12:45 | 2719.34 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 9.25 | 0.00 | 01-JAN-00:15 | 2602.87 | 21-JUL-14:15 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 25.62 | 0.09 | 06-JUN-00:15 | 5253.56 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 17.34 | 0.00 | 23-JAN-12:45 | 5253.56 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 8.28 | 0.00 | 01-JAN-00:15 | 3223.10 | 11-JUL-17:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 25.75 | 0.00 | 03-AUG-20:45 | 5389.10 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 21.41 | 0.00 | 18-MAR-12:15 | 5389.10 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 4.34 | 0.00 | 01-JAN-00:15 | 2538.42 | 11-JUL-17:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 26.55 | 0.03 | 25-JUN-13:30 | 5270.20 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 16.95 | 0.00 | 23-JAN-12:30 | 5270.20 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 9.60 | 0.00 | 01-JAN-00:15 | 3335.19 | 22-JUL-12:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 26.16 | 0.02 | 18-JUL-10:30 | 5407.06 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 20.80 | 0.00 | 18-MAR-09:30 | 5407.06 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 5.37 | 0.00 | 01-JAN-00:15 | 2133.19 | 13-JUN-07:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 14.45 | 0.00 | 02-JUN-15:45 | 3089.35 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 9.73 | 0.00 | 21-JAN-20:45 | 3089.35 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 4.72 | 0.00 | 01-JAN-00:15 | 1373.43 | 29-JUN-19:30 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 14.48 | 0.00 | 11-MAY-16:30 | 3089.58 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 9.70 | 0.00 | 21-JAN-20:45 | 3089.58 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 4.78 | 0.00 | 01-JAN-00:15 | 1357.93 | 29-JUN-19:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 16.26 | 0.00 | 11-OCT-16:00 | 2948.96 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 6.87 | 0.00 | 16-JAN-12:45 | 2948.96 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 9.39 | 0.00 | 01-JAN-00:15 | 2607.10 | 21-JUL-14:15 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 16.33 | 0.05 | 06-APR-05:15 | 2949.03 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 6.86 | 0.00 | 16-JAN-12:45 | 2949.03 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 9.47 | 0.00 | 01-JAN-00:15 | 2623.55 | 21-JUL-14:15 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 25.90 | 0.09 | 28-MAY-22:45 | 5579.14 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 17.71 | 0.00 | 23-JAN-12:45 | 5579.14 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 8.19 | 0.00 | 01-JAN-00:15 | 3262.34 | 11-JUL-17:30 |
EnergyTransfer:Zone:M NW APARTMENT | 26.10 | 0.05 | 17-MAY-14:00 | 5715.36 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 21.78 | 0.00 | 18-MAR-11:30 | 5715.36 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 4.32 | 0.00 | 01-JAN-00:15 | 2558.95 | 11-JUL-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 26.80 | 0.05 | 26-JUN-02:00 | 5597.45 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 17.33 | 0.00 | 23-JAN-12:15 | 5597.45 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 9.47 | 0.00 | 01-JAN-00:15 | 3368.32 | 22-JUL-12:00 |
EnergyTransfer:Zone:M NE APARTMENT | 26.51 | 0.01 | 20-MAR-18:45 | 5734.43 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 21.17 | 0.00 | 18-MAR-08:00 | 5734.43 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 5.34 | 0.00 | 01-JAN-00:15 | 2157.11 | 13-JUN-07:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 14.55 | 0.08 | 11-MAY-14:00 | 3277.05 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 9.78 | 0.00 | 19-JAN-19:00 | 3277.05 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 4.77 | 0.00 | 01-JAN-00:15 | 1401.83 | 29-JUN-19:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 14.57 | 0.06 | 01-AUG-14:30 | 3277.29 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 9.75 | 0.00 | 19-JAN-19:00 | 3277.29 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 4.82 | 0.00 | 01-JAN-00:15 | 1385.88 | 29-JUN-19:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 16.36 | 0.10 | 20-OCT-10:30 | 3136.02 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 6.94 | 0.00 | 16-JAN-12:45 | 3136.02 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 9.42 | 0.00 | 01-JAN-00:15 | 2639.30 | 21-JUL-14:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 16.43 | 0.17 | 28-FEB-20:00 | 3136.18 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 6.93 | 0.00 | 16-JAN-12:45 | 3136.18 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 9.50 | 0.00 | 01-JAN-00:15 | 2655.54 | 21-JUL-14:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 26.38 | 0.06 | 06-JUN-00:45 | 5913.53 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 18.84 | 0.00 | 23-JAN-12:45 | 5913.53 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 7.54 | 0.00 | 01-JAN-00:15 | 3237.11 | 11-JUL-17:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 26.98 | 0.06 | 19-SEP-13:45 | 6051.56 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 23.05 | 0.00 | 18-MAR-12:15 | 6051.56 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 3.93 | 0.00 | 01-JAN-00:15 | 2513.01 | 11-JUL-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 27.24 | 0.05 | 18-AUG-19:00 | 5932.84 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 18.45 | 0.00 | 23-JAN-12:30 | 5932.84 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 8.79 | 0.00 | 01-JAN-00:15 | 3340.70 | 22-JUL-12:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 27.33 | 0.03 | 18-JUN-18:15 | 6071.52 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 22.42 | 0.00 | 18-MAR-08:30 | 6071.52 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 4.91 | 0.00 | 01-JAN-00:15 | 2118.35 | 13-JUN-07:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 15.05 | 0.03 | 21-AUG-15:00 | 3491.88 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 10.63 | 0.00 | 21-JAN-20:45 | 3491.88 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 4.42 | 0.00 | 01-JAN-00:15 | 1360.91 | 29-JUN-19:30 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 15.07 | 0.01 | 04-JUN-18:15 | 3492.13 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 10.60 | 0.00 | 21-JAN-20:45 | 3492.13 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 4.46 | 0.00 | 01-JAN-00:15 | 1344.13 | 29-JUN-19:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 16.35 | 0.00 | 16-OCT-13:00 | 3348.75 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 7.61 | 0.00 | 16-JAN-12:45 | 3348.75 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 8.74 | 0.00 | 01-JAN-00:15 | 2606.80 | 21-JUL-14:15 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 16.42 | 0.02 | 12-FEB-24:00 | 3348.95 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 7.60 | 0.00 | 16-JAN-12:45 | 3348.95 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 8.82 | 0.00 | 01-JAN-00:15 | 2623.15 | 21-JUL-14:15 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 26.79 | 0.01 | 15-AUG-03:15 | 6195.62 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 19.68 | 0.00 | 23-JAN-13:00 | 6195.62 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 7.11 | 0.00 | 01-JAN-00:15 | 3230.95 | 11-JUL-17:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 27.64 | 0.03 | 19-MAY-13:00 | 6333.99 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 23.96 | 0.00 | 18-MAR-12:30 | 6333.99 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 3.68 | 0.00 | 01-JAN-00:15 | 2492.27 | 11-JUL-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 27.60 | 0.02 | 15-JUN-02:15 | 6215.66 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 19.27 | 0.00 | 23-JAN-13:00 | 6215.66 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 8.33 | 0.00 | 01-JAN-00:15 | 3334.31 | 22-JUL-12:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 27.96 | 0.00 | 06-SEP-04:30 | 6172.81 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 23.32 | 0.00 | 18-MAR-09:15 | 6172.81 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 4.64 | 0.00 | 01-JAN-00:15 | 2100.14 | 13-JUN-07:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 15.40 | 0.00 | 04-JUN-17:45 | 3668.24 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 11.21 | 0.00 | 21-JAN-21:00 | 3668.24 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 4.19 | 0.00 | 01-JAN-00:15 | 1344.17 | 29-JUN-19:45 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 15.41 | 0.02 | 02-OCT-09:45 | 3668.53 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 11.18 | 0.00 | 21-JAN-21:00 | 3668.53 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 4.23 | 0.00 | 01-JAN-00:15 | 1328.79 | 29-JUN-19:45 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 16.38 | 0.01 | 07-AUG-23:15 | 3524.86 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 8.09 | 0.00 | 16-JAN-12:45 | 3524.86 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 8.29 | 0.00 | 01-JAN-00:15 | 2594.79 | 21-JUL-14:15 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 16.44 | 0.01 | 30-OCT-10:15 | 3525.07 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 8.07 | 0.00 | 16-JAN-12:45 | 3525.07 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 8.37 | 0.00 | 01-JAN-00:15 | 2611.29 | 21-JUL-14:15 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 27.29 | 0.01 | 26-SEP-09:45 | 6458.40 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 20.55 | 0.00 | 23-JAN-13:00 | 6458.40 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 6.74 | 0.00 | 01-JAN-00:15 | 3233.39 | 11-JUL-17:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 28.41 | 0.01 | 04-MAY-04:30 | 6596.95 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 24.90 | 0.00 | 18-MAR-13:00 | 6596.95 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 3.50 | 0.00 | 01-JAN-00:15 | 2485.17 | 11-JUL-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 28.07 | 0.07 | 13-FEB-10:30 | 6479.07 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 20.13 | 0.00 | 23-JAN-12:45 | 6479.07 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 7.94 | 0.00 | 01-JAN-00:15 | 3335.82 | 22-JUL-12:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 28.68 | 0.01 | 14-MAY-10:15 | 6229.34 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 24.25 | 0.00 | 18-MAR-09:15 | 6229.34 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 4.43 | 0.00 | 01-JAN-00:15 | 2091.44 | 13-JUN-07:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 15.86 | 0.04 | 10-JUN-12:00 | 3835.73 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 11.85 | 0.00 | 21-JAN-21:00 | 3835.73 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 4.00 | 0.00 | 01-JAN-00:15 | 1344.66 | 29-JUN-19:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 15.86 | 0.01 | 03-AUG-13:45 | 3836.36 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 11.82 | 0.00 | 21-JAN-21:00 | 3836.36 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 4.04 | 0.00 | 01-JAN-00:15 | 1329.35 | 29-JUN-19:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 16.54 | 0.04 | 16-OCT-19:15 | 3692.38 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 8.64 | 0.00 | 16-JAN-12:45 | 3692.38 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 7.89 | 0.00 | 01-JAN-00:15 | 2591.67 | 21-JUL-14:15 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 16.60 | 0.07 | 28-AUG-19:00 | 3692.61 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 8.63 | 0.00 | 16-JAN-12:45 | 3692.61 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 7.97 | 0.00 | 01-JAN-00:15 | 2608.45 | 21-JUL-14:15 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 29.16 | 0.04 | 01-OCT-13:00 | 6813.27 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 22.83 | 0.00 | 09-FEB-11:45 | 6813.27 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 6.33 | 0.00 | 01-JAN-00:15 | 3301.56 | 11-JUL-17:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 30.69 | 0.02 | 11-SEP-17:00 | 6951.76 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 27.34 | 0.00 | 18-MAR-15:00 | 6951.76 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 3.35 | 0.00 | 01-JAN-00:15 | 2554.73 | 11-JUL-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 29.83 | 0.07 | 07-AUG-09:30 | 6835.02 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 22.37 | 0.00 | 09-FEB-11:30 | 6835.02 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 7.47 | 0.00 | 01-JAN-00:15 | 3376.43 | 22-JUL-12:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 30.89 | 0.01 | 24-JUL-09:45 | 6511.12 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 26.64 | 0.00 | 18-MAR-11:30 | 6511.12 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 4.24 | 0.00 | 01-JAN-00:15 | 2086.47 | 13-JUN-07:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 17.65 | 0.00 | 14-JUL-09:30 | 4093.95 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 13.85 | 0.00 | 07-FEB-21:00 | 4093.95 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.79 | 0.00 | 01-JAN-00:15 | 1408.63 | 29-JUN-19:45 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 17.65 | 0.00 | 08-JUL-11:30 | 4094.80 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 13.82 | 0.00 | 07-FEB-21:00 | 4094.80 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.84 | 0.00 | 01-JAN-00:15 | 1392.53 | 29-JUN-19:45 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 17.70 | 0.09 | 25-SEP-00:15 | 3950.07 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 10.37 | 0.00 | 16-JAN-13:00 | 3950.07 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 7.33 | 0.00 | 01-JAN-00:15 | 2623.54 | 21-JUL-14:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 17.75 | 0.06 | 10-JUN-12:30 | 3950.35 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 10.35 | 0.00 | 16-JAN-13:00 | 3950.35 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 7.40 | 0.00 | 01-JAN-00:15 | 2642.65 | 21-JUL-14:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 38.49 | 0.00 | 30-MAY-08:45 | 7710.36 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 32.46 | 0.00 | 09-FEB-11:45 | 7710.36 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 6.03 | 0.00 | 01-JAN-00:15 | 3781.60 | 20-JUN-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 39.61 | 0.01 | 23-MAY-22:00 | 7800.04 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 36.59 | 0.00 | 18-MAR-12:30 | 7800.04 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 3.01 | 0.00 | 01-JAN-00:15 | 3022.16 | 11-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 38.86 | 0.00 | 07-OCT-14:30 | 7733.03 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 31.92 | 0.00 | 09-FEB-11:30 | 7733.03 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 6.94 | 0.00 | 01-JAN-00:15 | 3920.17 | 22-JUL-12:00 |
EnergyTransfer:Zone:T NE APARTMENT | 39.67 | 0.03 | 14-JUL-00:15 | 7963.49 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 35.85 | 0.00 | 18-MAR-11:00 | 7963.49 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 3.83 | 0.00 | 01-JAN-00:15 | 2386.39 | 22-JUL-12:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 26.10 | 0.01 | 25-JUL-17:45 | 4897.77 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 22.84 | 0.00 | 18-MAR-11:15 | 4897.77 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 3.26 | 0.00 | 01-JAN-00:15 | 1565.17 | 29-JUN-19:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 26.11 | 0.07 | 30-MAY-13:45 | 4938.50 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 22.80 | 0.00 | 18-MAR-10:45 | 4938.50 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 3.31 | 0.00 | 01-JAN-00:15 | 1588.66 | 29-JUN-19:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 25.54 | 0.01 | 18-AUG-19:15 | 4800.50 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 19.21 | 0.00 | 23-JAN-12:30 | 4800.50 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 6.32 | 0.00 | 01-JAN-00:15 | 3275.20 | 21-JUL-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 25.58 | 0.01 | 05-OCT-17:00 | 4800.95 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 19.19 | 0.00 | 23-JAN-12:30 | 4800.95 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 6.39 | 0.00 | 01-JAN-00:15 | 3289.47 | 21-JUL-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 2908.99 | 643.92 | 10-SEP-01:30 | 261993.10 | 29-JAN-08:00 |
WaterSystems:EnergyTransfer | 1146.98 | 643.92 | 10-SEP-01:30 | 71336.31 | 12-DEC-07:45 |
sub cat:WaterSystems:EnergyTransfer | 1146.98 | 643.92 | 10-SEP-01:30 | 71336.31 | 12-DEC-07:45 |
EnergyTransfer:HVAC | 2810.87 | 0.00 | 17-APR-19:15 | 461294.56 | 28-JAN-24:00 |
CoolingCoils:EnergyTransfer | 368.59 | 0.00 | 01-JAN-00:15 | 200510.05 | 30-JUN-12:30 |
HeatingCoils:EnergyTransfer | 2442.28 | 0.00 | 17-APR-13:45 | 461294.56 | 28-JAN-24:00 |
PlantLoopHeatingDemand:HVAC | 1801.45 | 0.00 | 17-APR-13:45 | 200881.98 | 12-JAN-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 1801.45 | 0.00 | 17-APR-13:45 | 200881.98 | 12-JAN-04:00 |
Boilers:EnergyTransfer | 1762.01 | 0.00 | 20-MAR-13:00 | 199098.63 | 29-JAN-00:45 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 21.588 | -3.913 | 0.000 | 0.000 | 3.928 | 1.087 | 12.213 | 14.170 | 0.000 | 0.024 | 0.000 | 0.000 | -20.425 | 0.000 | -9.018 | -19.653 |
G NW APARTMENT | 25.070 | -2.277 | 0.000 | 0.000 | 3.965 | 1.087 | 12.213 | 5.809 | 0.000 | 0.025 | 0.000 | 0.000 | -21.771 | 0.000 | -8.572 | -15.549 |
OFFICE | 16.800 | -12.012 | 0.000 | 0.000 | 0.544 | 29.882 | 9.495 | 15.757 | 0.000 | 0.006 | 0.000 | 0.000 | -20.192 | 0.000 | -6.401 | -33.879 |
G NE APARTMENT | 24.536 | -2.581 | 0.000 | 0.000 | 3.963 | 1.087 | 12.213 | 7.281 | 0.000 | 0.025 | 0.000 | 0.000 | -21.280 | 0.000 | -8.690 | -16.554 |
G N1 APARTMENT | 16.170 | -2.410 | 0.000 | 0.000 | 3.972 | 1.087 | 12.213 | 2.270 | 0.000 | 0.022 | 0.000 | 0.000 | -13.500 | 0.000 | -5.924 | -13.900 |
G N2 APARTMENT | 16.137 | -2.431 | 0.000 | 0.000 | 3.971 | 1.087 | 12.213 | 2.266 | 0.000 | 0.022 | 0.000 | 0.000 | -13.501 | 0.000 | -5.934 | -13.829 |
G S1 APARTMENT | 12.687 | -4.345 | 0.000 | 0.000 | 3.924 | 1.087 | 12.213 | 10.992 | 0.000 | 0.022 | 0.000 | 0.000 | -12.401 | 0.000 | -6.395 | -17.783 |
G S2 APARTMENT | 12.400 | -4.519 | 0.000 | 0.000 | 3.919 | 1.087 | 12.213 | 10.976 | 0.000 | 0.022 | 0.000 | 0.000 | -12.416 | 0.000 | -6.436 | -17.245 |
F2 SW APARTMENT | 17.584 | -7.527 | 0.000 | 0.000 | 3.873 | 1.087 | 12.213 | 13.677 | 0.000 | 0.030 | 0.000 | 0.000 | -21.233 | 0.000 | -12.447 | -7.257 |
F2 NW APARTMENT | 21.545 | -3.910 | 0.000 | 0.000 | 3.927 | 1.087 | 12.213 | 5.438 | 0.000 | 0.030 | 0.000 | 0.000 | -22.509 | 0.000 | -11.964 | -5.855 |
F2 SE APARTMENT | 16.231 | -9.785 | 0.000 | 0.000 | 3.863 | 1.087 | 12.213 | 15.235 | 0.000 | 0.030 | 0.000 | 0.000 | -20.939 | 0.000 | -12.552 | -5.381 |
F2 NE APARTMENT | 20.913 | -4.860 | 0.000 | 0.000 | 3.928 | 1.087 | 12.213 | 6.907 | 0.000 | 0.030 | 0.000 | 0.000 | -22.002 | 0.000 | -12.046 | -6.170 |
F2 N1 APARTMENT | 10.733 | -4.155 | 0.000 | 0.000 | 3.937 | 1.087 | 12.213 | 2.067 | 0.000 | 0.026 | 0.000 | 0.000 | -14.010 | 0.000 | -8.139 | -3.758 |
F2 N2 APARTMENT | 10.704 | -4.203 | 0.000 | 0.000 | 3.936 | 1.087 | 12.213 | 2.063 | 0.000 | 0.026 | 0.000 | 0.000 | -14.012 | 0.000 | -8.150 | -3.663 |
F2 S1 APARTMENT | 7.802 | -8.007 | 0.000 | 0.000 | 3.862 | 1.087 | 12.213 | 10.681 | 0.000 | 0.026 | 0.000 | 0.000 | -12.899 | 0.000 | -8.727 | -6.038 |
F2 S2 APARTMENT | 7.730 | -8.180 | 0.000 | 0.000 | 3.860 | 1.087 | 12.213 | 10.674 | 0.000 | 0.026 | 0.000 | 0.000 | -12.906 | 0.000 | -8.740 | -5.763 |
F3 SW APARTMENT | 16.881 | -8.225 | 0.000 | 0.000 | 3.867 | 1.087 | 12.213 | 13.505 | 0.000 | 0.037 | 0.000 | 0.000 | -21.482 | 0.000 | -14.343 | -3.540 |
F3 NW APARTMENT | 20.864 | -4.302 | 0.000 | 0.000 | 3.919 | 1.087 | 12.213 | 5.317 | 0.000 | 0.038 | 0.000 | 0.000 | -22.767 | 0.000 | -13.857 | -2.511 |
F3 SE APARTMENT | 16.377 | -9.675 | 0.000 | 0.000 | 3.865 | 1.087 | 12.213 | 15.093 | 0.000 | 0.037 | 0.000 | 0.000 | -21.108 | 0.000 | -14.392 | -3.496 |
F3 NE APARTMENT | 20.250 | -5.309 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 6.786 | 0.000 | 0.038 | 0.000 | 0.000 | -22.253 | 0.000 | -13.928 | -2.804 |
F3 N1 APARTMENT | 9.612 | -4.613 | 0.000 | 0.000 | 3.925 | 1.087 | 12.213 | 2.003 | 0.000 | 0.032 | 0.000 | 0.000 | -14.186 | 0.000 | -9.380 | -0.691 |
F3 N2 APARTMENT | 9.582 | -4.660 | 0.000 | 0.000 | 3.925 | 1.087 | 12.213 | 1.999 | 0.000 | 0.032 | 0.000 | 0.000 | -14.188 | 0.000 | -9.391 | -0.598 |
F3 S1 APARTMENT | 6.806 | -9.147 | 0.000 | 0.000 | 3.851 | 1.087 | 12.213 | 10.563 | 0.000 | 0.033 | 0.000 | 0.000 | -13.065 | 0.000 | -9.964 | -2.377 |
F3 S2 APARTMENT | 6.781 | -9.250 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 10.559 | 0.000 | 0.033 | 0.000 | 0.000 | -13.068 | 0.000 | -9.971 | -2.235 |
F4 SW APARTMENT | 17.340 | -8.278 | 0.000 | 0.000 | 3.868 | 1.087 | 12.213 | 13.407 | 0.000 | 0.040 | 0.000 | 0.000 | -21.607 | 0.000 | -15.509 | -2.560 |
F4 NW APARTMENT | 21.405 | -4.343 | 0.000 | 0.000 | 3.918 | 1.087 | 12.213 | 5.255 | 0.000 | 0.040 | 0.000 | 0.000 | -22.907 | 0.000 | -15.038 | -1.629 |
F4 SE APARTMENT | 16.950 | -9.596 | 0.000 | 0.000 | 3.867 | 1.087 | 12.213 | 14.996 | 0.000 | 0.040 | 0.000 | 0.000 | -21.216 | 0.000 | -15.545 | -2.796 |
F4 NE APARTMENT | 20.796 | -5.367 | 0.000 | 0.000 | 3.920 | 1.087 | 12.213 | 6.722 | 0.000 | 0.040 | 0.000 | 0.000 | -22.388 | 0.000 | -15.101 | -1.920 |
F4 N1 APARTMENT | 9.726 | -4.723 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 1.971 | 0.000 | 0.033 | 0.129 | 0.000 | -14.281 | 0.000 | -10.075 | -0.000 |
F4 N2 APARTMENT | 9.701 | -4.776 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 1.967 | 0.000 | 0.033 | 0.223 | 0.000 | -14.284 | 0.000 | -10.085 | -0.000 |
F4 S1 APARTMENT | 6.873 | -9.386 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 10.495 | 0.000 | 0.035 | 0.000 | 0.000 | -13.146 | 0.000 | -10.629 | -1.392 |
F4 S2 APARTMENT | 6.857 | -9.468 | 0.000 | 0.000 | 3.849 | 1.087 | 12.213 | 10.492 | 0.000 | 0.035 | 0.000 | 0.000 | -13.148 | 0.000 | -10.634 | -1.284 |
M SW APARTMENT | 17.710 | -8.187 | 0.000 | 0.000 | 3.870 | 1.087 | 12.213 | 13.331 | 0.000 | 0.041 | 0.000 | 0.000 | -21.710 | 0.000 | -16.673 | -1.682 |
M NW APARTMENT | 21.777 | -4.320 | 0.000 | 0.000 | 3.919 | 1.087 | 12.213 | 5.213 | 0.000 | 0.042 | 0.000 | 0.000 | -23.019 | 0.000 | -16.177 | -0.733 |
M SE APARTMENT | 17.329 | -9.474 | 0.000 | 0.000 | 3.869 | 1.087 | 12.213 | 14.916 | 0.000 | 0.041 | 0.000 | 0.000 | -21.311 | 0.000 | -16.710 | -1.960 |
M NE APARTMENT | 21.168 | -5.341 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 6.676 | 0.000 | 0.041 | 0.000 | 0.000 | -22.497 | 0.000 | -16.241 | -1.026 |
M N1 APARTMENT | 9.783 | -4.771 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 1.950 | 0.000 | 0.034 | 0.944 | 0.000 | -14.356 | 0.000 | -10.804 | -0.000 |
M N2 APARTMENT | 9.754 | -4.820 | 0.000 | 0.000 | 3.920 | 1.087 | 12.213 | 1.947 | 0.000 | 0.034 | 1.038 | 0.000 | -14.359 | 0.000 | -10.814 | -0.001 |
M S1 APARTMENT | 6.941 | -9.422 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 10.442 | 0.000 | 0.037 | 0.000 | 0.000 | -13.210 | 0.000 | -11.376 | -0.562 |
M S2 APARTMENT | 6.931 | -9.502 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 10.439 | 0.000 | 0.037 | 0.001 | 0.000 | -13.211 | 0.000 | -11.381 | -0.461 |
F6 SW APARTMENT | 18.840 | -7.543 | 0.000 | 0.000 | 3.876 | 1.087 | 12.213 | 13.295 | 0.000 | 0.043 | 0.000 | 0.000 | -21.741 | 0.000 | -17.637 | -2.433 |
F6 NW APARTMENT | 23.049 | -3.933 | 0.000 | 0.000 | 3.927 | 1.087 | 12.213 | 5.209 | 0.000 | 0.043 | 0.000 | 0.000 | -23.057 | 0.000 | -17.088 | -1.450 |
F6 SE APARTMENT | 18.449 | -8.788 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 14.876 | 0.000 | 0.043 | 0.000 | 0.000 | -21.341 | 0.000 | -17.681 | -2.732 |
F6 NE APARTMENT | 22.420 | -4.912 | 0.000 | 0.000 | 3.929 | 1.087 | 12.213 | 6.667 | 0.000 | 0.043 | 0.000 | 0.000 | -22.532 | 0.000 | -17.161 | -1.753 |
F6 N1 APARTMENT | 10.632 | -4.416 | 0.000 | 0.000 | 3.929 | 1.087 | 12.213 | 1.952 | 0.000 | 0.035 | 0.305 | 0.000 | -14.378 | 0.000 | -11.359 | -0.000 |
F6 N2 APARTMENT | 10.603 | -4.464 | 0.000 | 0.000 | 3.929 | 1.087 | 12.213 | 1.949 | 0.000 | 0.035 | 0.399 | 0.000 | -14.380 | 0.000 | -11.369 | -0.000 |
F6 S1 APARTMENT | 7.608 | -8.741 | 0.000 | 0.000 | 3.857 | 1.087 | 12.213 | 10.415 | 0.000 | 0.038 | 0.000 | 0.000 | -13.227 | 0.000 | -11.983 | -1.266 |
F6 S2 APARTMENT | 7.598 | -8.820 | 0.000 | 0.000 | 3.856 | 1.087 | 12.213 | 10.412 | 0.000 | 0.038 | 0.000 | 0.000 | -13.229 | 0.000 | -11.989 | -1.165 |
F7 SW APARTMENT | 19.675 | -7.112 | 0.000 | 0.000 | 3.881 | 1.087 | 12.213 | 13.259 | 0.000 | 0.044 | 0.000 | 0.000 | -21.779 | 0.000 | -18.487 | -2.781 |
F7 NW APARTMENT | 23.958 | -3.684 | 0.000 | 0.000 | 3.934 | 1.087 | 12.213 | 5.202 | 0.000 | 0.044 | 0.000 | 0.000 | -23.100 | 0.000 | -17.897 | -1.756 |
F7 SE APARTMENT | 19.271 | -8.328 | 0.000 | 0.000 | 3.880 | 1.087 | 12.213 | 14.837 | 0.000 | 0.044 | 0.000 | 0.000 | -21.378 | 0.000 | -18.537 | -3.088 |
F7 NE APARTMENT | 23.319 | -4.639 | 0.000 | 0.000 | 3.935 | 1.087 | 12.213 | 6.656 | 0.000 | 0.044 | 0.000 | 0.000 | -22.573 | 0.000 | -17.976 | -2.064 |
F7 N1 APARTMENT | 11.210 | -4.186 | 0.000 | 0.000 | 3.936 | 1.087 | 12.213 | 1.952 | 0.000 | 0.036 | 0.009 | 0.000 | -14.403 | 0.000 | -11.853 | -0.000 |
F7 N2 APARTMENT | 11.177 | -4.232 | 0.000 | 0.000 | 3.935 | 1.087 | 12.213 | 1.948 | 0.000 | 0.035 | 0.105 | 0.000 | -14.406 | 0.000 | -11.864 | -0.000 |
F7 S1 APARTMENT | 8.088 | -8.290 | 0.000 | 0.000 | 3.861 | 1.087 | 12.213 | 10.388 | 0.000 | 0.039 | 0.000 | 0.000 | -13.249 | 0.000 | -12.519 | -1.619 |
F7 S2 APARTMENT | 8.075 | -8.365 | 0.000 | 0.000 | 3.861 | 1.087 | 12.213 | 10.385 | 0.000 | 0.039 | 0.000 | 0.000 | -13.250 | 0.000 | -12.525 | -1.519 |
F8 SW APARTMENT | 20.549 | -6.744 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 13.228 | 0.000 | 0.045 | 0.000 | 0.000 | -21.810 | 0.000 | -19.264 | -3.189 |
F8 NW APARTMENT | 24.902 | -3.503 | 0.000 | 0.000 | 3.939 | 1.087 | 12.213 | 5.194 | 0.000 | 0.045 | 0.000 | 0.000 | -23.138 | 0.000 | -18.638 | -2.101 |
F8 SE APARTMENT | 20.131 | -7.936 | 0.000 | 0.000 | 3.885 | 1.087 | 12.213 | 14.802 | 0.000 | 0.045 | 0.000 | 0.000 | -21.408 | 0.000 | -19.320 | -3.498 |
F8 NE APARTMENT | 24.250 | -4.429 | 0.000 | 0.000 | 3.940 | 1.087 | 12.213 | 6.645 | 0.000 | 0.044 | 0.000 | 0.000 | -22.609 | 0.000 | -18.723 | -2.418 |
F8 N1 APARTMENT | 11.853 | -4.002 | 0.000 | 0.000 | 3.941 | 1.087 | 12.213 | 1.951 | 0.000 | 0.036 | 0.000 | 0.000 | -14.425 | 0.000 | -12.312 | -0.342 |
F8 N2 APARTMENT | 11.817 | -4.045 | 0.000 | 0.000 | 3.941 | 1.087 | 12.213 | 1.947 | 0.000 | 0.036 | 0.000 | 0.000 | -14.427 | 0.000 | -12.324 | -0.245 |
F8 S1 APARTMENT | 8.642 | -7.894 | 0.000 | 0.000 | 3.866 | 1.087 | 12.213 | 10.366 | 0.000 | 0.039 | 0.000 | 0.000 | -13.265 | 0.000 | -13.013 | -2.040 |
F8 S2 APARTMENT | 8.629 | -7.971 | 0.000 | 0.000 | 3.866 | 1.087 | 12.213 | 10.363 | 0.000 | 0.039 | 0.000 | 0.000 | -13.267 | 0.000 | -13.020 | -1.939 |
F9 SW APARTMENT | 22.825 | -6.329 | 0.000 | 0.000 | 3.892 | 1.087 | 12.213 | 13.217 | 0.000 | 0.046 | 0.000 | 0.000 | -21.789 | 0.000 | -19.966 | -5.196 |
F9 NW APARTMENT | 27.337 | -3.355 | 0.000 | 0.000 | 3.943 | 1.087 | 12.213 | 5.193 | 0.000 | 0.046 | 0.000 | 0.000 | -23.129 | 0.000 | -19.321 | -4.014 |
F9 SE APARTMENT | 22.365 | -7.467 | 0.000 | 0.000 | 3.891 | 1.087 | 12.213 | 14.790 | 0.000 | 0.046 | 0.000 | 0.000 | -21.389 | 0.000 | -20.032 | -5.503 |
F9 NE APARTMENT | 26.641 | -4.244 | 0.000 | 0.000 | 3.945 | 1.087 | 12.213 | 6.643 | 0.000 | 0.045 | 0.000 | 0.000 | -22.598 | 0.000 | -19.410 | -4.321 |
F9 N1 APARTMENT | 13.850 | -3.794 | 0.000 | 0.000 | 3.946 | 1.087 | 12.213 | 1.953 | 0.000 | 0.037 | 0.000 | 0.000 | -14.414 | 0.000 | -12.739 | -2.139 |
F9 N2 APARTMENT | 13.815 | -3.837 | 0.000 | 0.000 | 3.946 | 1.087 | 12.213 | 1.949 | 0.000 | 0.037 | 0.000 | 0.000 | -14.415 | 0.000 | -12.751 | -2.043 |
F9 S1 APARTMENT | 10.369 | -7.327 | 0.000 | 0.000 | 3.873 | 1.087 | 12.213 | 10.359 | 0.000 | 0.041 | 0.000 | 0.000 | -13.247 | 0.000 | -13.458 | -3.908 |
F9 S2 APARTMENT | 10.350 | -7.398 | 0.000 | 0.000 | 3.872 | 1.087 | 12.213 | 10.355 | 0.000 | 0.041 | 0.000 | 0.000 | -13.249 | 0.000 | -13.467 | -3.804 |
T SW APARTMENT | 32.463 | -6.030 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 13.098 | 0.000 | 0.047 | 0.000 | 0.000 | -21.222 | 0.000 | -20.543 | -15.032 |
T NW APARTMENT | 36.593 | -3.014 | 0.000 | 0.000 | 3.957 | 1.087 | 12.213 | 5.115 | 0.000 | 0.047 | 0.000 | 0.000 | -22.637 | 0.000 | -19.974 | -13.387 |
T SE APARTMENT | 31.916 | -6.939 | 0.000 | 0.000 | 3.920 | 1.087 | 12.213 | 14.705 | 0.000 | 0.047 | 0.000 | 0.000 | -20.858 | 0.000 | -20.572 | -15.519 |
T NE APARTMENT | 35.845 | -3.827 | 0.000 | 0.000 | 3.963 | 1.087 | 12.213 | 6.587 | 0.000 | 0.047 | 0.000 | 0.000 | -22.119 | 0.000 | -20.001 | -13.794 |
T N1 APARTMENT | 22.841 | -3.258 | 0.000 | 0.000 | 3.962 | 1.087 | 12.213 | 1.942 | 0.000 | 0.033 | 0.000 | 0.000 | -14.083 | 0.000 | -13.119 | -11.617 |
T N2 APARTMENT | 22.800 | -3.307 | 0.000 | 0.000 | 3.962 | 1.087 | 12.213 | 1.937 | 0.000 | 0.035 | 0.000 | 0.000 | -14.083 | 0.000 | -13.129 | -11.514 |
T S1 APARTMENT | 19.211 | -6.323 | 0.000 | 0.000 | 3.903 | 1.087 | 12.213 | 10.298 | 0.000 | 0.041 | 0.000 | 0.000 | -12.930 | 0.000 | -13.814 | -13.685 |
T S2 APARTMENT | 19.188 | -6.391 | 0.000 | 0.000 | 3.902 | 1.087 | 12.213 | 10.292 | 0.000 | 0.041 | 0.000 | 0.000 | -12.930 | 0.000 | -13.821 | -13.581 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.364 | 0.000 | 0.030 | 106.468 | 0.000 | -4.356 | 0.000 | -121.946 | -0.002 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.313 | 0.000 | 0.000 | 0.000 | 0.000 | -2.712 | 0.000 | -1.617 | -13.425 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.277 | 0.000 | 0.000 | 0.000 | 0.000 | -2.816 | 0.000 | -1.968 | -12.933 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.260 | 0.000 | 0.000 | 0.000 | 0.000 | -2.852 | 0.000 | -2.217 | -12.631 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.241 | 0.000 | 0.000 | 0.000 | 0.000 | -2.896 | 0.000 | -2.474 | -28.751 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.248 | 0.000 | 0.000 | 0.000 | 0.000 | -2.871 | 0.000 | -2.569 | -12.248 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.249 | 0.000 | 0.000 | 0.000 | 0.000 | -2.865 | 0.000 | -2.698 | -12.126 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.248 | 0.000 | 0.000 | 0.000 | 0.000 | -2.865 | 0.000 | -2.820 | -12.003 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.248 | 0.000 | 0.000 | 0.000 | 0.000 | -2.852 | 0.000 | -2.923 | -11.913 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.223 | 0.000 | 0.000 | 0.000 | 0.000 | -2.777 | 0.000 | -3.056 | -19.982 |
Total Facility | 1329.982 | -481.888 | 0.000 | 0.000 | 309.191 | 296.560 | 982.450 | 669.314 | 0.000 | 2.954 | 109.623 | 0.000 | -1452.088 | 0.000 | -1223.094 | -543.004 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-AUG-16:15 | 0.00 | -2331.21 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3116.44 | 0.00 | 147.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1670.63 |
G NW APARTMENT | 11-JUL-17:45 | 0.00 | -1905.86 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2426.81 | 0.00 | 232.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1571.31 |
OFFICE | 10-AUG-13:45 | 0.00 | -3671.75 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 3633.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35.65 | -2925.98 |
G NE APARTMENT | 11-JUL-05:30 | 0.00 | -1389.19 | 0.00 | 0.00 | 162.99 | 45.40 | 317.85 | 3232.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.09 | -2279.31 |
G N1 APARTMENT | 11-JUL-17:30 | 0.00 | -1018.39 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 359.59 | 0.00 | 218.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.92 |
G N2 APARTMENT | 11-JUL-17:30 | 0.00 | -1014.33 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 359.62 | 0.00 | 218.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -382.01 |
G S1 APARTMENT | 21-JUL-14:15 | 0.00 | -1846.50 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2832.73 | 0.00 | 200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1650.49 |
G S2 APARTMENT | 21-JUL-14:15 | 0.00 | -1909.53 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2831.51 | 0.00 | 200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1586.23 |
F2 SW APARTMENT | 11-AUG-16:15 | 0.00 | -3131.97 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3071.68 | 0.00 | 190.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -868.20 |
F2 NW APARTMENT | 11-JUL-17:30 | 0.00 | -2498.76 | 0.00 | 0.00 | 141.62 | 87.56 | 588.62 | 2481.91 | 0.00 | 287.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1088.01 |
F2 SE APARTMENT | 21-JUL-14:15 | 0.00 | -3318.15 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3116.80 | 0.00 | 228.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491.00 |
F2 NE APARTMENT | 13-JUN-06:40 | 0.00 | -1993.46 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2696.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20.07 | -1246.47 |
F2 N1 APARTMENT | 11-JUL-16:15 | 0.00 | -1279.80 | 0.00 | 0.00 | 84.62 | 64.86 | 588.62 | 426.57 | 0.00 | 246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -131.36 |
F2 N2 APARTMENT | 11-JUL-16:15 | 0.00 | -1264.63 | 0.00 | 0.00 | 84.52 | 64.86 | 588.62 | 426.20 | 0.00 | 241.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -141.20 |
F2 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2506.63 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2812.42 | 0.00 | 219.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -988.75 |
F2 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2533.44 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2812.02 | 0.00 | 219.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -961.54 |
F3 SW APARTMENT | 11-AUG-16:15 | 0.00 | -3200.47 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3052.10 | 0.00 | 215.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -805.27 |
F3 NW APARTMENT | 11-JUL-17:30 | 0.00 | -2536.33 | 0.00 | 0.00 | 141.28 | 87.56 | 588.62 | 2467.24 | 0.00 | 313.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1061.54 |
F3 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3320.66 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3444.87 | 0.00 | 296.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -881.05 |
F3 NE APARTMENT | 13-JUN-06:40 | 0.00 | -2086.48 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2692.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23.80 | -1145.78 |
F3 N1 APARTMENT | 29-JUN-19:15 | 0.00 | -1362.18 | 0.00 | 0.00 | 141.79 | 103.77 | 523.87 | 495.88 | 0.00 | 86.19 | 10.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 29-JUN-19:15 | 0.00 | -1347.00 | 0.00 | 0.00 | 141.72 | 103.77 | 523.87 | 495.94 | 0.00 | 85.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.39 |
F3 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2584.81 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2801.76 | 0.00 | 231.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -911.99 |
F3 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2602.41 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2801.49 | 0.00 | 231.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -894.10 |
F4 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3222.60 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2671.32 | 0.00 | 318.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -585.04 |
F4 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2537.87 | 0.00 | 0.00 | 141.61 | 87.56 | 588.62 | 2391.66 | 0.00 | 350.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1022.45 |
F4 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3334.49 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3432.50 | 0.00 | 312.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -870.34 |
F4 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2133.85 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2635.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1065.30 |
F4 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1373.75 | 0.00 | 0.00 | 141.57 | 103.77 | 523.87 | 548.52 | 0.00 | 81.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.49 |
F4 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1358.25 | 0.00 | 0.00 | 141.45 | 103.77 | 523.87 | 548.50 | 0.00 | 80.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39.42 |
F4 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2606.67 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2793.93 | 0.00 | 240.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.42 |
F4 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2623.11 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2793.67 | 0.00 | 240.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -874.72 |
M SW APARTMENT | 11-JUL-17:30 | 0.00 | -3261.82 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2662.43 | 0.00 | 336.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -555.39 |
M NW APARTMENT | 11-JUL-17:15 | 0.00 | -2558.38 | 0.00 | 0.00 | 141.46 | 87.56 | 588.62 | 2383.76 | 0.00 | 366.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1009.48 |
M SE APARTMENT | 22-JUL-12:00 | 0.00 | -3367.61 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3421.70 | 0.00 | 324.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.94 |
M NE APARTMENT | 13-JUN-07:00 | 0.00 | -2157.79 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2634.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1040.17 |
M N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1402.16 | 0.00 | 0.00 | 141.48 | 103.77 | 523.87 | 545.60 | 0.00 | 83.34 | 4.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1386.22 | 0.00 | 0.00 | 141.34 | 103.77 | 523.87 | 545.56 | 0.00 | 81.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10.14 |
M S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2638.88 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2787.10 | 0.00 | 247.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -859.69 |
M S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2655.12 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2786.84 | 0.00 | 247.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -843.19 |
F6 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3236.58 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2656.62 | 0.00 | 351.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.86 |
F6 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2512.45 | 0.00 | 0.00 | 141.25 | 87.56 | 588.62 | 2378.56 | 0.00 | 376.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1060.46 |
F6 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3339.98 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3413.82 | 0.00 | 335.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -869.13 |
F6 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2119.03 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2635.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1079.47 |
F6 N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1361.24 | 0.00 | 0.00 | 141.33 | 103.77 | 523.87 | 544.13 | 0.00 | 83.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35.31 |
F6 N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1344.46 | 0.00 | 0.00 | 141.20 | 103.77 | 523.87 | 544.08 | 0.00 | 81.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.25 |
F6 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2606.39 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2782.10 | 0.00 | 253.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -893.23 |
F6 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2622.75 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2781.84 | 0.00 | 253.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.61 |
F7 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3230.42 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2651.14 | 0.00 | 364.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -603.05 |
F7 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2491.70 | 0.00 | 0.00 | 141.08 | 87.56 | 588.62 | 2373.62 | 0.00 | 385.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1084.90 |
F7 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3333.58 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3406.35 | 0.00 | 344.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.95 |
F7 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2100.81 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2635.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1097.65 |
F7 N1 APARTMENT | 29-JUN-19:45 | 0.00 | -1344.41 | 0.00 | 0.00 | 141.27 | 103.77 | 523.87 | 533.00 | 0.00 | 75.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33.18 |
F7 N2 APARTMENT | 29-JUN-19:45 | 0.00 | -1329.04 | 0.00 | 0.00 | 141.14 | 103.77 | 523.87 | 532.97 | 0.00 | 73.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46.71 |
F7 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2594.40 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2777.34 | 0.00 | 258.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -905.53 |
F7 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2610.90 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2777.07 | 0.00 | 258.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -888.77 |
F8 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3232.84 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2646.05 | 0.00 | 374.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -606.08 |
F8 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2484.60 | 0.00 | 0.00 | 140.97 | 87.56 | 588.62 | 2369.03 | 0.00 | 393.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1095.06 |
F8 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3335.09 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3399.43 | 0.00 | 351.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.19 |
F8 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2092.11 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2634.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1106.04 |
F8 N1 APARTMENT | 29-JUN-19:45 | 0.00 | -1344.92 | 0.00 | 0.00 | 141.25 | 103.77 | 523.87 | 531.41 | 0.00 | 76.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31.46 |
F8 N2 APARTMENT | 29-JUN-19:45 | 0.00 | -1329.60 | 0.00 | 0.00 | 141.12 | 103.77 | 523.87 | 531.37 | 0.00 | 74.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.88 |
F8 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2591.29 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2772.88 | 0.00 | 263.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -908.51 |
F8 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2608.06 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2772.61 | 0.00 | 263.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.46 |
F9 SW APARTMENT | 11-JUL-17:30 | 0.00 | -3301.00 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2639.49 | 0.00 | 383.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -540.29 |
F9 NW APARTMENT | 11-JUL-17:15 | 0.00 | -2554.14 | 0.00 | 0.00 | 141.08 | 87.56 | 588.62 | 2363.37 | 0.00 | 406.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.92 |
F9 SE APARTMENT | 22-JUL-12:00 | 0.00 | -3375.69 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3391.99 | 0.00 | 358.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.80 |
F9 NE APARTMENT | 13-JUN-07:00 | 0.00 | -2087.14 | 0.00 | 0.00 | 138.55 | 42.16 | 382.60 | 2634.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1110.63 |
F9 N1 APARTMENT | 29-JUN-19:45 | 0.00 | -1408.90 | 0.00 | 0.00 | 141.31 | 103.77 | 523.87 | 528.52 | 0.00 | 76.90 | 34.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 29-JUN-19:45 | 0.00 | -1392.80 | 0.00 | 0.00 | 141.20 | 103.77 | 523.87 | 528.54 | 0.00 | 75.32 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 21-JUL-14:15 | 0.00 | -2623.16 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2768.19 | 0.00 | 266.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.62 |
F9 S2 APARTMENT | 21-JUL-14:15 | 0.00 | -2642.27 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2767.87 | 0.00 | 266.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -856.20 |
T SW APARTMENT | 20-JUN-16:15 | 0.00 | -3781.34 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3156.41 | 0.00 | 200.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -314.09 |
T NW APARTMENT | 11-JUL-17:15 | 0.00 | -3021.46 | 0.00 | 0.00 | 141.47 | 87.56 | 588.62 | 2332.31 | 0.00 | 428.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -557.12 |
T SE APARTMENT | 22-JUL-12:00 | 0.00 | -3919.37 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3349.83 | 0.00 | 364.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -254.81 |
T NE APARTMENT | 22-JUL-12:00 | 0.00 | -2385.77 | 0.00 | 0.00 | 40.49 | 12.97 | 406.15 | 1095.26 | 0.00 | 339.69 | 491.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-JUN-19:30 | 0.00 | -1565.56 | 0.00 | 0.00 | 140.14 | 103.77 | 523.87 | 528.14 | 0.00 | 70.23 | 199.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUN-19:30 | 0.00 | -1589.04 | 0.00 | 0.00 | 141.03 | 103.77 | 523.87 | 530.13 | 0.00 | 82.31 | 207.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 21-JUL-14:15 | 0.00 | -3274.74 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2742.51 | 0.00 | 270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.54 |
T S2 APARTMENT | 21-JUL-14:15 | 0.00 | -3289.01 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2742.23 | 0.00 | 270.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -186.98 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-16:15 | 0.00 | -175271.48 | 0.00 | 0.00 | 6680.88 | 11327.17 | 47312.53 | 114084.90 | 0.00 | 24519.98 | 0.00 | 0.00 | 0.00 | 0.00 | -128.08 | -28525.90 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 28-JAN-24:00 | 3811.74 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1741.17 | 0.00 | -2066.53 | -551.31 |
G NW APARTMENT | 28-JAN-24:00 | 3878.27 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1752.49 | 0.00 | -2066.55 | -606.51 |
OFFICE | 28-JAN-24:00 | 3833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1752.25 | 0.00 | -2066.51 | -677.70 |
G NE APARTMENT | 28-JAN-24:00 | 3886.15 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1762.57 | 0.00 | -2066.55 | -604.30 |
G N1 APARTMENT | 29-JAN-00:15 | 2435.50 | 0.00 | 0.00 | 0.00 | 189.66 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1071.44 | 0.00 | -1214.70 | -610.38 |
G N2 APARTMENT | 29-JAN-00:15 | 2435.62 | 0.00 | 0.00 | 0.00 | 189.66 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1071.43 | 0.00 | -1214.70 | -610.50 |
G S1 APARTMENT | 29-JAN-00:15 | 2344.59 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1061.15 | 0.00 | -1214.68 | -529.78 |
G S2 APARTMENT | 29-JAN-00:15 | 2339.02 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1061.26 | 0.00 | -1214.68 | -524.11 |
F2 SW APARTMENT | 28-JAN-24:00 | 4439.92 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1801.25 | 0.00 | -2971.04 | -214.92 |
F2 NW APARTMENT | 28-JAN-24:00 | 4566.40 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1822.71 | 0.00 | -2971.06 | -319.91 |
F2 SE APARTMENT | 28-JAN-24:00 | 4430.48 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1819.68 | 0.00 | -2971.04 | -187.05 |
F2 NE APARTMENT | 28-JAN-24:00 | 4580.30 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1840.29 | 0.00 | -2971.08 | -316.20 |
F2 N1 APARTMENT | 29-JAN-00:15 | 2661.73 | 0.00 | 0.00 | 0.00 | 189.66 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.21 | 0.00 | -1746.38 | -255.17 |
F2 N2 APARTMENT | 29-JAN-00:15 | 2661.91 | 0.00 | 0.00 | 0.00 | 189.66 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.20 | 0.00 | -1746.38 | -255.35 |
F2 S1 APARTMENT | 29-JAN-00:15 | 2534.88 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1096.80 | 0.00 | -1746.33 | -152.78 |
F2 S2 APARTMENT | 29-JAN-00:15 | 2533.17 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1096.84 | 0.00 | -1746.33 | -151.03 |
F3 SW APARTMENT | 28-JAN-24:00 | 4852.72 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1825.24 | 0.00 | -3518.35 | -56.41 |
F3 NW APARTMENT | 28-JAN-24:00 | 4984.90 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1851.52 | 0.00 | -3518.38 | -162.28 |
F3 SE APARTMENT | 28-JAN-24:00 | 4864.23 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1846.39 | 0.00 | -3518.35 | -46.77 |
F3 NE APARTMENT | 28-JAN-24:00 | 5001.22 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1872.39 | 0.00 | -3518.39 | -157.71 |
F3 N1 APARTMENT | 28-JAN-24:00 | 2855.67 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1142.92 | 0.00 | -2122.23 | -137.79 |
F3 N2 APARTMENT | 28-JAN-24:00 | 2855.87 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1142.92 | 0.00 | -2122.23 | -137.99 |
F3 S1 APARTMENT | 28-JAN-24:00 | 2719.16 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1112.99 | 0.00 | -2122.18 | -31.27 |
F3 S2 APARTMENT | 28-JAN-24:00 | 2718.83 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1113.00 | 0.00 | -2122.18 | -30.93 |
F4 SW APARTMENT | 28-JAN-24:00 | 5252.76 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1839.07 | 0.00 | -3933.51 | -27.47 |
F4 NW APARTMENT | 28-JAN-24:00 | 5388.20 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1868.31 | 0.00 | -3933.53 | -133.63 |
F4 SE APARTMENT | 28-JAN-24:00 | 5269.39 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1862.11 | 0.00 | -3933.51 | -21.06 |
F4 NE APARTMENT | 28-JAN-24:00 | 5406.11 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1891.18 | 0.00 | -3933.55 | -128.66 |
F4 N1 APARTMENT | 28-JAN-24:00 | 3088.68 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.63 | 0.00 | -2372.64 | -108.68 |
F4 N2 APARTMENT | 28-JAN-24:00 | 3088.90 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.62 | 0.00 | -2372.64 | -108.91 |
F4 S1 APARTMENT | 28-JAN-24:00 | 2948.42 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.62 | 0.00 | -2372.59 | -1.49 |
F4 S2 APARTMENT | 28-JAN-24:00 | 2948.49 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.62 | 0.00 | -2372.59 | -1.56 |
M SW APARTMENT | 28-JAN-24:00 | 5578.31 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 | -1849.81 | 0.00 | -4275.80 | 0.00 |
M NW APARTMENT | 28-JAN-24:00 | 5714.43 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1881.14 | 0.00 | -4275.82 | -104.75 |
M SE APARTMENT | 28-JAN-24:00 | 5596.61 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 | -1874.26 | 0.00 | -4275.80 | 0.00 |
M NE APARTMENT | 28-JAN-24:00 | 5733.46 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.41 | 0.00 | -4275.85 | -99.48 |
M N1 APARTMENT | 28-JAN-24:00 | 3276.35 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.48 | 0.00 | -2579.10 | -81.04 |
M N2 APARTMENT | 28-JAN-24:00 | 3276.59 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.48 | 0.00 | -2579.11 | -81.28 |
M S1 APARTMENT | 28-JAN-24:00 | 3135.45 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 24.62 | 0.00 | -1128.30 | 0.00 | -2579.05 | 0.00 |
M S2 APARTMENT | 28-JAN-24:00 | 3135.61 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 | -1128.29 | 0.00 | -2579.05 | 0.00 |
F6 SW APARTMENT | 28-JAN-24:00 | 5912.67 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1856.79 | 0.00 | -4570.84 | -32.32 |
F6 NW APARTMENT | 28-JAN-24:00 | 6050.60 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1889.74 | 0.00 | -4570.87 | -137.27 |
F6 SE APARTMENT | 28-JAN-24:00 | 5931.96 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1882.28 | 0.00 | -4570.84 | -26.12 |
F6 NE APARTMENT | 28-JAN-24:00 | 6070.52 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1915.05 | 0.00 | -4570.89 | -131.85 |
F6 N1 APARTMENT | 28-JAN-24:00 | 3491.14 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.36 | 0.00 | -2757.07 | -111.98 |
F6 N2 APARTMENT | 28-JAN-24:00 | 3491.39 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1169.35 | 0.00 | -2757.07 | -112.24 |
F6 S1 APARTMENT | 28-JAN-24:00 | 3348.15 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1132.53 | 0.00 | -2757.01 | -5.89 |
F6 S2 APARTMENT | 28-JAN-24:00 | 3348.34 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1132.52 | 0.00 | -2757.01 | -6.09 |
F7 SW APARTMENT | 28-JAN-24:00 | 6194.74 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1863.12 | 0.00 | -4832.32 | -46.58 |
F7 NW APARTMENT | 28-JAN-24:00 | 6333.01 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.34 | 0.00 | -4832.35 | -150.59 |
F7 SE APARTMENT | 28-JAN-24:00 | 6214.77 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1889.44 | 0.00 | -4832.33 | -40.28 |
F7 NE APARTMENT | 28-JAN-24:00 | 6171.82 | 0.00 | 0.00 | 0.00 | 189.94 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 20.76 | 0.00 | -1922.82 | 0.00 | -4817.31 | 0.00 |
F7 N1 APARTMENT | 28-JAN-24:00 | 3667.47 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.52 | 0.00 | -2914.80 | -125.43 |
F7 N2 APARTMENT | 28-JAN-24:00 | 3667.76 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.51 | 0.00 | -2914.80 | -125.73 |
F7 S1 APARTMENT | 28-JAN-24:00 | 3524.23 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1136.36 | 0.00 | -2914.73 | -20.41 |
F7 S2 APARTMENT | 28-JAN-24:00 | 3524.44 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1136.36 | 0.00 | -2914.73 | -20.63 |
F8 SW APARTMENT | 28-JAN-24:00 | 6457.49 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1868.39 | 0.00 | -5068.54 | -67.84 |
F8 NW APARTMENT | 28-JAN-24:00 | 6595.95 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1903.65 | 0.00 | -5068.57 | -171.00 |
F8 SE APARTMENT | 28-JAN-24:00 | 6478.15 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1895.38 | 0.00 | -5068.54 | -61.50 |
F8 NE APARTMENT | 28-JAN-24:00 | 6228.34 | 0.00 | 0.00 | 0.00 | 191.57 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 174.53 | 0.00 | -1925.38 | 0.00 | -5026.67 | 0.00 |
F8 N1 APARTMENT | 28-JAN-24:00 | 3834.93 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1178.75 | 0.00 | -3057.28 | -146.18 |
F8 N2 APARTMENT | 28-JAN-24:00 | 3835.56 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1178.74 | 0.00 | -3057.28 | -146.81 |
F8 S1 APARTMENT | 28-JAN-24:00 | 3691.72 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1139.52 | 0.00 | -3057.21 | -42.27 |
F8 S2 APARTMENT | 28-JAN-24:00 | 3691.96 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1139.52 | 0.00 | -3057.21 | -42.51 |
F9 SW APARTMENT | 28-JAN-24:00 | 6812.33 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.78 | 0.00 | -5284.94 | -204.90 |
F9 NW APARTMENT | 28-JAN-24:00 | 6950.74 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.76 | 0.00 | -5284.97 | -307.28 |
F9 SE APARTMENT | 28-JAN-24:00 | 6834.07 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.27 | 0.00 | -5284.94 | -199.15 |
F9 NE APARTMENT | 28-JAN-24:00 | 6510.10 | 0.00 | 0.00 | 0.00 | 192.19 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 98.88 | 0.00 | -1926.15 | 0.00 | -5232.63 | 0.00 |
F9 N1 APARTMENT | 28-JAN-24:00 | 4093.12 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.15 | 0.00 | -3187.80 | -272.44 |
F9 N2 APARTMENT | 28-JAN-24:00 | 4093.97 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.14 | 0.00 | -3187.80 | -273.30 |
F9 S1 APARTMENT | 28-JAN-24:00 | 3949.38 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.18 | 0.00 | -3187.74 | -168.74 |
F9 S2 APARTMENT | 28-JAN-24:00 | 3949.67 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.18 | 0.00 | -3187.74 | -169.03 |
T SW APARTMENT | 28-JAN-24:00 | 7709.37 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1840.38 | 0.00 | -5484.85 | -931.42 |
T NW APARTMENT | 28-JAN-24:00 | 7798.95 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1876.38 | 0.00 | -5484.88 | -984.97 |
T SE APARTMENT | 28-JAN-24:00 | 7732.02 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1867.64 | 0.00 | -5484.85 | -926.81 |
T NE APARTMENT | 28-JAN-24:00 | 7962.33 | 0.00 | 0.00 | 0.00 | 188.13 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1907.43 | 0.00 | -5508.89 | -1091.75 |
T N1 APARTMENT | 28-JAN-24:00 | 4896.81 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1160.43 | 0.00 | -3308.52 | -975.13 |
T N2 APARTMENT | 28-JAN-24:00 | 4937.53 | 0.00 | 0.00 | 0.00 | 189.66 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1160.42 | 0.00 | -3310.65 | -1013.73 |
T S1 APARTMENT | 28-JAN-24:00 | 4799.72 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1123.57 | 0.00 | -3308.44 | -914.99 |
T S2 APARTMENT | 28-JAN-24:00 | 4800.18 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1123.56 | 0.00 | -3308.44 | -915.46 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JAN-24:00 | 364621.46 | 0.00 | 0.00 | 0.00 | 14986.73 | 7484.42 | 27274.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -122370.71 | 0.00 | -276163.06 | -15833.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Sec1.1A-General InformationData | |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 115.25 |
Number of hours cooling loads not met | 28.25 |
Number of hours not met | 143.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 7484.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.58 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 673.86 | 261078.47 | 2349.92 | 254312.63 | 0.00 | 0.00 |
Space Cooling | 123.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.17 | 1756.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 668.13 | 21186.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1467.86 | 89941.37 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 29363.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3157.51 | 3817.79 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 3157.51 |
Natural Gas | 0.00 | 3817.79 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 6975.30 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 85.99 |
Space Cooling | 15.82 |
Fans-Interior | 85.26 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 32.88 |
Subtotal | 402.93 |
Natural Gas [MJ/m2] | |
Space Heating | 299.87 |
Service Water Heating | 187.31 |
Miscellaneous | -0.00 |
Subtotal | 487.18 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.25 |
Space Heating | 43.35 |
Space Cooling | 1.78 |
Fans-Interior | 9.58 |
Service Water Heating | 21.04 |
Receptacle Equipment | 16.31 |
Miscellaneous | 3.69 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.237396 |
G NW APARTMENT DIRECT AIR | 0.181298 |
OFFICE DIRECT AIR | 0.372198 |
G NE APARTMENT DIRECT AIR | 0.181218 |
G N1 APARTMENT DIRECT AIR | 0.134206 |
G N2 APARTMENT DIRECT AIR | 0.134204 |
G S1 APARTMENT DIRECT AIR | 0.179553 |
G S2 APARTMENT DIRECT AIR | 0.186289 |
F2 SW APARTMENT DIRECT AIR | 0.317993 |
F2 NW APARTMENT DIRECT AIR | 0.229434 |
F2 SE APARTMENT DIRECT AIR | 0.329993 |
F2 NE APARTMENT DIRECT AIR | 0.186648 |
F2 N1 APARTMENT DIRECT AIR | 0.125199 |
F2 N2 APARTMENT DIRECT AIR | 0.123705 |
F2 S1 APARTMENT DIRECT AIR | 0.244500 |
F2 S2 APARTMENT DIRECT AIR | 0.246991 |
F3 SW APARTMENT DIRECT AIR | 0.320511 |
F3 NW APARTMENT DIRECT AIR | 0.233178 |
F3 SE APARTMENT DIRECT AIR | 0.311325 |
F3 NE APARTMENT DIRECT AIR | 0.190812 |
F3 N1 APARTMENT DIRECT AIR | 0.129973 |
F3 N2 APARTMENT DIRECT AIR | 0.128502 |
F3 S1 APARTMENT DIRECT AIR | 0.248982 |
F3 S2 APARTMENT DIRECT AIR | 0.250175 |
F4 SW APARTMENT DIRECT AIR | 0.320921 |
F4 NW APARTMENT DIRECT AIR | 0.233670 |
F4 SE APARTMENT DIRECT AIR | 0.309899 |
F4 NE APARTMENT DIRECT AIR | 0.191177 |
F4 N1 APARTMENT DIRECT AIR | 0.130771 |
F4 N2 APARTMENT DIRECT AIR | 0.129300 |
F4 S1 APARTMENT DIRECT AIR | 0.249871 |
F4 S2 APARTMENT DIRECT AIR | 0.250884 |
M SW APARTMENT DIRECT AIR | 0.322998 |
M NW APARTMENT DIRECT AIR | 0.235787 |
M SE APARTMENT DIRECT AIR | 0.311915 |
M NE APARTMENT DIRECT AIR | 0.193157 |
M N1 APARTMENT DIRECT AIR | 0.133050 |
M N2 APARTMENT DIRECT AIR | 0.131582 |
M S1 APARTMENT DIRECT AIR | 0.252258 |
M S2 APARTMENT DIRECT AIR | 0.253243 |
F6 SW APARTMENT DIRECT AIR | 0.319338 |
F6 NW APARTMENT DIRECT AIR | 0.232157 |
F6 SE APARTMENT DIRECT AIR | 0.308433 |
F6 NE APARTMENT DIRECT AIR | 0.189541 |
F6 N1 APARTMENT DIRECT AIR | 0.129741 |
F6 N2 APARTMENT DIRECT AIR | 0.128279 |
F6 S1 APARTMENT DIRECT AIR | 0.248844 |
F6 S2 APARTMENT DIRECT AIR | 0.249826 |
F7 SW APARTMENT DIRECT AIR | 0.317815 |
F7 NW APARTMENT DIRECT AIR | 0.230685 |
F7 SE APARTMENT DIRECT AIR | 0.307057 |
F7 NE APARTMENT DIRECT AIR | 0.188094 |
F7 N1 APARTMENT DIRECT AIR | 0.128496 |
F7 N2 APARTMENT DIRECT AIR | 0.127040 |
F7 S1 APARTMENT DIRECT AIR | 0.247531 |
F7 S2 APARTMENT DIRECT AIR | 0.248511 |
F8 SW APARTMENT DIRECT AIR | 0.317379 |
F8 NW APARTMENT DIRECT AIR | 0.230379 |
F8 SE APARTMENT DIRECT AIR | 0.306744 |
F8 NE APARTMENT DIRECT AIR | 0.187753 |
F8 N1 APARTMENT DIRECT AIR | 0.128448 |
F8 N2 APARTMENT DIRECT AIR | 0.126999 |
F8 S1 APARTMENT DIRECT AIR | 0.247283 |
F8 S2 APARTMENT DIRECT AIR | 0.248264 |
F9 SW APARTMENT DIRECT AIR | 0.323540 |
F9 NW APARTMENT DIRECT AIR | 0.236842 |
F9 SE APARTMENT DIRECT AIR | 0.312150 |
F9 NE APARTMENT DIRECT AIR | 0.190196 |
F9 N1 APARTMENT DIRECT AIR | 0.134116 |
F9 N2 APARTMENT DIRECT AIR | 0.132607 |
F9 S1 APARTMENT DIRECT AIR | 0.251727 |
F9 S2 APARTMENT DIRECT AIR | 0.252830 |
T SW APARTMENT DIRECT AIR | 0.377844 |
T NW APARTMENT DIRECT AIR | 0.276439 |
T SE APARTMENT DIRECT AIR | 0.359181 |
T NE APARTMENT DIRECT AIR | 0.216994 |
T N1 APARTMENT DIRECT AIR | 0.146326 |
T N2 APARTMENT DIRECT AIR | 0.143566 |
T S1 APARTMENT DIRECT AIR | 0.312997 |
T S2 APARTMENT DIRECT AIR | 0.314095 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.237396 |
AIRLOOP G NW MAIN BRANCH | 0.181298 |
AIRLOOP OFFICE MAIN BRANCH | 0.372198 |
AIRLOOP G NE MAIN BRANCH | 0.181218 |
AIRLOOP G N1 MAIN BRANCH | 0.134206 |
AIRLOOP G N2 MAIN BRANCH | 0.134204 |
AIRLOOP G S1 MAIN BRANCH | 0.179553 |
AIRLOOP G S2 MAIN BRANCH | 0.186289 |
AIRLOOP F2 SW MAIN BRANCH | 0.317993 |
AIRLOOP F2 NW MAIN BRANCH | 0.229434 |
AIRLOOP F2 SE MAIN BRANCH | 0.329993 |
AIRLOOP F2 NE MAIN BRANCH | 0.186648 |
AIRLOOP F2 N1 MAIN BRANCH | 0.125199 |
AIRLOOP F2 N2 MAIN BRANCH | 0.123705 |
AIRLOOP F2 S1 MAIN BRANCH | 0.244500 |
AIRLOOP F2 S2 MAIN BRANCH | 0.246991 |
AIRLOOP F3 SW MAIN BRANCH | 0.320511 |
AIRLOOP F3 NW MAIN BRANCH | 0.233178 |
AIRLOOP F3 SE MAIN BRANCH | 0.311325 |
AIRLOOP F3 NE MAIN BRANCH | 0.190812 |
AIRLOOP F3 N1 MAIN BRANCH | 0.129973 |
AIRLOOP F3 N2 MAIN BRANCH | 0.128502 |
AIRLOOP F3 S1 MAIN BRANCH | 0.248982 |
AIRLOOP F3 S2 MAIN BRANCH | 0.250175 |
AIRLOOP F4 SW MAIN BRANCH | 0.320921 |
AIRLOOP F4 NW MAIN BRANCH | 0.233670 |
AIRLOOP F4 SE MAIN BRANCH | 0.309899 |
AIRLOOP F4 NE MAIN BRANCH | 0.191177 |
AIRLOOP F4 N1 MAIN BRANCH | 0.130771 |
AIRLOOP F4 N2 MAIN BRANCH | 0.129300 |
AIRLOOP F4 S1 MAIN BRANCH | 0.249871 |
AIRLOOP F4 S2 MAIN BRANCH | 0.250884 |
AIRLOOP M SW MAIN BRANCH | 0.322998 |
AIRLOOP M NW MAIN BRANCH | 0.235787 |
AIRLOOP M SE MAIN BRANCH | 0.311915 |
AIRLOOP M NE MAIN BRANCH | 0.193157 |
AIRLOOP M N1 MAIN BRANCH | 0.133050 |
AIRLOOP M N2 MAIN BRANCH | 0.131582 |
AIRLOOP M S1 MAIN BRANCH | 0.252258 |
AIRLOOP M S2 MAIN BRANCH | 0.253243 |
AIRLOOP F6 SW MAIN BRANCH | 0.319338 |
AIRLOOP F6 NW MAIN BRANCH | 0.232157 |
AIRLOOP F6 SE MAIN BRANCH | 0.308433 |
AIRLOOP F6 NE MAIN BRANCH | 0.189541 |
AIRLOOP F6 N1 MAIN BRANCH | 0.129741 |
AIRLOOP F6 N2 MAIN BRANCH | 0.128279 |
AIRLOOP F6 S1 MAIN BRANCH | 0.248844 |
AIRLOOP F6 S2 MAIN BRANCH | 0.249826 |
AIRLOOP F7 SW MAIN BRANCH | 0.317815 |
AIRLOOP F7 NW MAIN BRANCH | 0.230685 |
AIRLOOP F7 SE MAIN BRANCH | 0.307057 |
AIRLOOP F7 NE MAIN BRANCH | 0.188094 |
AIRLOOP F7 N1 MAIN BRANCH | 0.128496 |
AIRLOOP F7 N2 MAIN BRANCH | 0.127040 |
AIRLOOP F7 S1 MAIN BRANCH | 0.247531 |
AIRLOOP F7 S2 MAIN BRANCH | 0.248511 |
AIRLOOP F8 SW MAIN BRANCH | 0.317379 |
AIRLOOP F8 NW MAIN BRANCH | 0.230379 |
AIRLOOP F8 SE MAIN BRANCH | 0.306744 |
AIRLOOP F8 NE MAIN BRANCH | 0.187753 |
AIRLOOP F8 N1 MAIN BRANCH | 0.128448 |
AIRLOOP F8 N2 MAIN BRANCH | 0.126999 |
AIRLOOP F8 S1 MAIN BRANCH | 0.247283 |
AIRLOOP F8 S2 MAIN BRANCH | 0.248264 |
AIRLOOP F9 SW MAIN BRANCH | 0.323540 |
AIRLOOP F9 NW MAIN BRANCH | 0.236842 |
AIRLOOP F9 SE MAIN BRANCH | 0.312150 |
AIRLOOP F9 NE MAIN BRANCH | 0.190196 |
AIRLOOP F9 N1 MAIN BRANCH | 0.134116 |
AIRLOOP F9 N2 MAIN BRANCH | 0.132607 |
AIRLOOP F9 S1 MAIN BRANCH | 0.251727 |
AIRLOOP F9 S2 MAIN BRANCH | 0.252830 |
AIRLOOP T SW MAIN BRANCH | 0.377844 |
AIRLOOP T NW MAIN BRANCH | 0.276439 |
AIRLOOP T SE MAIN BRANCH | 0.359181 |
AIRLOOP T NE MAIN BRANCH | 0.216994 |
AIRLOOP T N1 MAIN BRANCH | 0.146326 |
AIRLOOP T N2 MAIN BRANCH | 0.143566 |
AIRLOOP T S1 MAIN BRANCH | 0.312997 |
AIRLOOP T S2 MAIN BRANCH | 0.314095 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.237396 |
AIRLOOP G NW | 0.181298 |
AIRLOOP OFFICE | 0.372198 |
AIRLOOP G NE | 0.181218 |
AIRLOOP G N1 | 0.134206 |
AIRLOOP G N2 | 0.134204 |
AIRLOOP G S1 | 0.179553 |
AIRLOOP G S2 | 0.186289 |
AIRLOOP F2 SW | 0.317993 |
AIRLOOP F2 NW | 0.229434 |
AIRLOOP F2 SE | 0.329993 |
AIRLOOP F2 NE | 0.186648 |
AIRLOOP F2 N1 | 0.125199 |
AIRLOOP F2 N2 | 0.123705 |
AIRLOOP F2 S1 | 0.244500 |
AIRLOOP F2 S2 | 0.246991 |
AIRLOOP F3 SW | 0.320511 |
AIRLOOP F3 NW | 0.233178 |
AIRLOOP F3 SE | 0.311325 |
AIRLOOP F3 NE | 0.190812 |
AIRLOOP F3 N1 | 0.129973 |
AIRLOOP F3 N2 | 0.128502 |
AIRLOOP F3 S1 | 0.248982 |
AIRLOOP F3 S2 | 0.250175 |
AIRLOOP F4 SW | 0.320921 |
AIRLOOP F4 NW | 0.233670 |
AIRLOOP F4 SE | 0.309899 |
AIRLOOP F4 NE | 0.191177 |
AIRLOOP F4 N1 | 0.130771 |
AIRLOOP F4 N2 | 0.129300 |
AIRLOOP F4 S1 | 0.249871 |
AIRLOOP F4 S2 | 0.250884 |
AIRLOOP M SW | 0.322998 |
AIRLOOP M NW | 0.235787 |
AIRLOOP M SE | 0.311915 |
AIRLOOP M NE | 0.193157 |
AIRLOOP M N1 | 0.133050 |
AIRLOOP M N2 | 0.131582 |
AIRLOOP M S1 | 0.252258 |
AIRLOOP M S2 | 0.253243 |
AIRLOOP F6 SW | 0.319338 |
AIRLOOP F6 NW | 0.232157 |
AIRLOOP F6 SE | 0.308433 |
AIRLOOP F6 NE | 0.189541 |
AIRLOOP F6 N1 | 0.129741 |
AIRLOOP F6 N2 | 0.128279 |
AIRLOOP F6 S1 | 0.248844 |
AIRLOOP F6 S2 | 0.249826 |
AIRLOOP F7 SW | 0.317815 |
AIRLOOP F7 NW | 0.230685 |
AIRLOOP F7 SE | 0.307057 |
AIRLOOP F7 NE | 0.188094 |
AIRLOOP F7 N1 | 0.128496 |
AIRLOOP F7 N2 | 0.127040 |
AIRLOOP F7 S1 | 0.247531 |
AIRLOOP F7 S2 | 0.248511 |
AIRLOOP F8 SW | 0.317379 |
AIRLOOP F8 NW | 0.230379 |
AIRLOOP F8 SE | 0.306744 |
AIRLOOP F8 NE | 0.187753 |
AIRLOOP F8 N1 | 0.128448 |
AIRLOOP F8 N2 | 0.126999 |
AIRLOOP F8 S1 | 0.247283 |
AIRLOOP F8 S2 | 0.248264 |
AIRLOOP F9 SW | 0.323540 |
AIRLOOP F9 NW | 0.236842 |
AIRLOOP F9 SE | 0.312150 |
AIRLOOP F9 NE | 0.190196 |
AIRLOOP F9 N1 | 0.134116 |
AIRLOOP F9 N2 | 0.132607 |
AIRLOOP F9 S1 | 0.251727 |
AIRLOOP F9 S2 | 0.252830 |
AIRLOOP T SW | 0.377844 |
AIRLOOP T NW | 0.276439 |
AIRLOOP T SE | 0.359181 |
AIRLOOP T NE | 0.216994 |
AIRLOOP T N1 | 0.146326 |
AIRLOOP T N2 | 0.143566 |
AIRLOOP T S1 | 0.312997 |
AIRLOOP T S2 | 0.314095 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.237396 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.181298 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.372198 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.181218 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.134206 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.134204 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.179553 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.186289 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.317993 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.229434 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.329993 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.186648 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.125199 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.123705 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.244500 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.246991 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.320511 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.233178 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.311325 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.190812 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.129973 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.128502 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.248982 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.250175 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.320921 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.233670 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.309899 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.191177 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.130771 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.129300 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.249871 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.250884 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.322998 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.235787 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.311915 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.193157 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.133050 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.131582 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.252258 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.253243 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.319338 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.232157 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.308433 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.189541 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.129741 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.128279 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.248844 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.249826 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.317815 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.230685 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.307057 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.188094 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.128496 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.127040 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.247531 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.248511 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.317379 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.230379 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.306744 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.187753 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.128448 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.126999 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.247283 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.248264 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.323540 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.236842 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.312150 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.190196 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.134116 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.132607 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.251727 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.252830 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.377844 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.276439 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.359181 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.216994 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.146326 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.143566 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.312997 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.314095 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.237396 | 3265.29 | 2545.80 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.181298 | 2420.70 | 1906.71 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.372198 | 5143.49 | 4004.00 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.181218 | 2383.21 | 1903.52 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.134206 | 1619.08 | 1332.09 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.134204 | 1613.17 | 1329.66 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.179553 | 2499.75 | 1941.97 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.186289 | 2593.10 | 2013.98 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.317993 | 4363.84 | 3401.16 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.229434 | 3088.38 | 2421.98 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.329993 | 4559.12 | 3543.62 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.186648 | 2482.40 | 1967.78 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.125199 | 1592.03 | 1277.82 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.123705 | 1571.16 | 1261.79 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.244500 | 3391.90 | 2634.25 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.246991 | 3426.42 | 2660.88 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.320511 | 4395.62 | 3428.70 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.233178 | 3132.65 | 2460.09 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.311325 | 4292.86 | 3342.20 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.190812 | 2532.79 | 2010.47 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.129973 | 1653.88 | 1327.82 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.128502 | 1633.37 | 1312.06 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.248982 | 3449.28 | 2680.97 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.250175 | 3465.81 | 2693.72 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.320921 | 4395.47 | 3431.61 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.233670 | 3133.71 | 2463.92 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.309899 | 4267.37 | 3325.53 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.191177 | 2532.55 | 2013.07 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.130771 | 1661.47 | 1335.50 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.129300 | 1640.97 | 1319.75 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.249871 | 3458.07 | 2689.59 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.250884 | 3472.10 | 2700.42 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.322998 | 4419.48 | 3452.62 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.235787 | 3158.44 | 2485.40 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.311915 | 4290.57 | 3345.89 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.193157 | 2555.59 | 2033.14 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.133050 | 1690.38 | 1359.23 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.131582 | 1669.93 | 1343.50 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.252258 | 3488.24 | 2714.37 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.253243 | 3501.89 | 2724.90 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.319338 | 4364.80 | 3412.52 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.232157 | 3104.02 | 2445.58 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.308433 | 4238.42 | 3307.71 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.189541 | 2502.11 | 1993.68 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.129741 | 1641.83 | 1323.18 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.128279 | 1621.47 | 1307.52 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.248844 | 3438.51 | 2677.28 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.249826 | 3452.12 | 2687.78 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.317815 | 4340.19 | 3395.37 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.230685 | 3080.11 | 2428.98 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.307057 | 4215.88 | 3292.13 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.188094 | 2490.45 | 1983.01 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.128496 | 1622.39 | 1309.33 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.127040 | 1602.10 | 1293.73 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.247531 | 3418.17 | 2662.70 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.248511 | 3431.75 | 2673.18 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.317379 | 4331.01 | 3389.93 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.230379 | 3072.78 | 2424.94 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.306744 | 4208.44 | 3288.01 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.187753 | 2482.97 | 1978.69 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.128448 | 1619.84 | 1308.36 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.126999 | 1599.67 | 1292.84 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.247283 | 3412.81 | 2659.58 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.248264 | 3426.40 | 2670.06 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.323540 | 4408.67 | 3452.45 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.236842 | 3159.65 | 2493.34 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.312150 | 4280.34 | 3345.04 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.190196 | 2514.10 | 2004.13 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.134116 | 1697.06 | 1368.64 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.132607 | 1676.06 | 1352.49 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.251727 | 3472.54 | 2706.62 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.252830 | 3487.82 | 2718.40 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.377844 | 5172.71 | 4039.50 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.276439 | 3727.97 | 2932.23 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.359181 | 4928.12 | 3846.69 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.216994 | 2892.70 | 2294.93 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.146326 | 1879.16 | 1505.98 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.143566 | 1914.77 | 1519.41 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.312997 | 4319.07 | 3360.83 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.314095 | 4334.29 | 3372.57 | 0.000095 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.237396 | 0.237396 | 0.237396 | 0.237396 | 3265.29 | 3265.29 | 5905.22 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.181298 | 0.181298 | 0.181298 | 0.181298 | 2420.70 | 2420.70 | 5918.27 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.372198 | 0.372198 | 0.372198 | 0.372198 | 5143.49 | 5143.49 | 7328.82 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.181218 | 0.181218 | 0.181218 | 0.181218 | 2383.21 | 2383.21 | 5916.51 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.134206 | 0.134206 | 0.134206 | 0.134206 | 1619.08 | 1619.08 | 4891.70 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.134204 | 0.134204 | 0.134204 | 0.134204 | 1613.17 | 1613.17 | 4891.66 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.179553 | 0.179553 | 0.179553 | 0.179553 | 2499.75 | 2499.75 | 4877.08 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.186289 | 0.186289 | 0.186289 | 0.186289 | 2593.10 | 2593.10 | 4883.34 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.317993 | 0.317993 | 0.317993 | 0.317993 | 4363.84 | 4363.84 | 4951.99 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.229434 | 0.229434 | 0.229434 | 0.229434 | 3088.38 | 3088.38 | 4945.96 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.329993 | 0.329993 | 0.329993 | 0.329993 | 4559.12 | 4559.12 | 4966.93 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.186648 | 0.186648 | 0.186648 | 0.186648 | 2482.40 | 2482.40 | 4943.19 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.125199 | 0.125199 | 0.125199 | 0.125199 | 1592.03 | 1592.03 | 3763.43 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.123705 | 0.123705 | 0.123705 | 0.123705 | 1571.16 | 1571.16 | 3763.37 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.244500 | 0.244500 | 0.244500 | 0.244500 | 3391.90 | 3391.90 | 3772.96 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.246991 | 0.246991 | 0.246991 | 0.246991 | 3426.42 | 3426.42 | 3773.94 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.320511 | 0.320511 | 0.320511 | 0.320511 | 4395.62 | 4395.62 | 4745.26 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.233178 | 0.233178 | 0.233178 | 0.233178 | 3132.65 | 3132.65 | 4741.48 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.311325 | 0.311325 | 0.311325 | 0.311325 | 4292.86 | 4292.86 | 4743.72 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.190812 | 0.190812 | 0.190812 | 0.190812 | 2532.79 | 2532.79 | 4738.20 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.129973 | 0.129973 | 0.129973 | 0.129973 | 1653.88 | 1653.88 | 3551.20 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.128502 | 0.128502 | 0.128502 | 0.128502 | 1633.37 | 1633.37 | 3551.13 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.248982 | 0.248982 | 0.248982 | 0.248982 | 3449.28 | 3449.28 | 3556.57 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.250175 | 0.250175 | 0.250175 | 0.250175 | 3465.81 | 3465.81 | 3556.65 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.320921 | 0.320921 | 0.320921 | 0.320921 | 4395.47 | 4395.47 | 4721.83 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.233670 | 0.233670 | 0.233670 | 0.233670 | 3133.71 | 3133.71 | 4718.56 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.309899 | 0.309899 | 0.309899 | 0.309899 | 4267.37 | 4267.37 | 4718.33 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.191177 | 0.191177 | 0.191177 | 0.191177 | 2532.55 | 2532.55 | 4714.89 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.130771 | 0.130771 | 0.130771 | 0.130771 | 1661.47 | 1661.47 | 3517.34 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.129300 | 0.129300 | 0.129300 | 0.129300 | 1640.97 | 1640.97 | 3517.26 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.249871 | 0.249871 | 0.249871 | 0.249871 | 3458.07 | 3458.07 | 3521.90 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.250884 | 0.250884 | 0.250884 | 0.250884 | 3472.10 | 3472.10 | 3521.84 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.322998 | 0.322998 | 0.322998 | 0.322998 | 4419.48 | 4419.48 | 4702.63 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.235787 | 0.235787 | 0.235787 | 0.235787 | 3158.44 | 3158.44 | 4698.25 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.311915 | 0.311915 | 0.311915 | 0.311915 | 4290.57 | 4290.57 | 4698.68 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.193157 | 0.193157 | 0.193157 | 0.193157 | 2555.59 | 2555.59 | 4694.28 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.133050 | 0.133050 | 0.133050 | 0.133050 | 1690.38 | 1690.38 | 3490.36 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.131582 | 0.131582 | 0.131582 | 0.131582 | 1669.93 | 1669.93 | 3490.28 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.252258 | 0.252258 | 0.252258 | 0.252258 | 3488.24 | 3488.24 | 3496.11 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.253243 | 0.253243 | 0.253243 | 0.253243 | 3501.89 | 3501.89 | 3496.03 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.319338 | 0.319338 | 0.319338 | 0.319338 | 4364.80 | 4364.80 | 4754.51 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.232157 | 0.232157 | 0.232157 | 0.232157 | 3104.02 | 3104.02 | 4750.51 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.308433 | 0.308433 | 0.308433 | 0.308433 | 4238.42 | 4238.42 | 4750.28 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.189541 | 0.189541 | 0.189541 | 0.189541 | 2502.11 | 2502.11 | 4746.27 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.129741 | 0.129741 | 0.129741 | 0.129741 | 1641.83 | 1641.83 | 3533.67 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.128279 | 0.128279 | 0.128279 | 0.128279 | 1621.47 | 1621.47 | 3533.58 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.248844 | 0.248844 | 0.248844 | 0.248844 | 3438.51 | 3438.51 | 3538.90 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.249826 | 0.249826 | 0.249826 | 0.249826 | 3452.12 | 3452.12 | 3538.81 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.317815 | 0.317815 | 0.317815 | 0.317815 | 4340.19 | 4340.19 | 4783.04 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.230685 | 0.230685 | 0.230685 | 0.230685 | 3080.11 | 3080.11 | 4778.47 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.307057 | 0.307057 | 0.307057 | 0.307057 | 4215.88 | 4215.88 | 4778.58 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.188094 | 0.188094 | 0.188094 | 0.188094 | 2490.45 | 2490.45 | 4774.01 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.128496 | 0.128496 | 0.128496 | 0.128496 | 1622.39 | 1622.39 | 3555.95 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.127040 | 0.127040 | 0.127040 | 0.127040 | 1602.10 | 1602.10 | 3555.85 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.247531 | 0.247531 | 0.247531 | 0.247531 | 3418.17 | 3418.17 | 3561.77 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.248511 | 0.248511 | 0.248511 | 0.248511 | 3431.75 | 3431.75 | 3561.68 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.317379 | 0.317379 | 0.317379 | 0.317379 | 4331.01 | 4331.01 | 4826.57 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.230379 | 0.230379 | 0.230379 | 0.230379 | 3072.78 | 3072.78 | 4821.08 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.306744 | 0.306744 | 0.306744 | 0.306744 | 4208.44 | 4208.44 | 4821.92 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.187753 | 0.187753 | 0.187753 | 0.187753 | 2482.97 | 2482.97 | 4816.42 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.128448 | 0.128448 | 0.128448 | 0.128448 | 1619.84 | 1619.84 | 3593.90 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.126999 | 0.126999 | 0.126999 | 0.126999 | 1599.67 | 1599.67 | 3593.80 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.247283 | 0.247283 | 0.247283 | 0.247283 | 3412.81 | 3412.81 | 3600.67 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.248264 | 0.248264 | 0.248264 | 0.248264 | 3426.40 | 3426.40 | 3600.58 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.323540 | 0.323540 | 0.323540 | 0.323540 | 4408.67 | 4408.67 | 5074.16 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.236842 | 0.236842 | 0.236842 | 0.236842 | 3159.65 | 3159.65 | 5064.08 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.312150 | 0.312150 | 0.312150 | 0.312150 | 4280.34 | 4280.34 | 5069.28 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.190196 | 0.190196 | 0.190196 | 0.190196 | 2514.10 | 2514.10 | 5059.19 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.134116 | 0.134116 | 0.134116 | 0.134116 | 1697.06 | 1697.06 | 3820.24 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.132607 | 0.132607 | 0.132607 | 0.132607 | 1676.06 | 1676.06 | 3820.13 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.251727 | 0.251727 | 0.251727 | 0.251727 | 3472.54 | 3472.54 | 3831.16 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.252830 | 0.252830 | 0.252830 | 0.252830 | 3487.82 | 3487.82 | 3831.06 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.377844 | 0.377844 | 0.377844 | 0.377844 | 5172.71 | 5172.71 | 6182.34 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.276439 | 0.276439 | 0.276439 | 0.276439 | 3727.97 | 3727.97 | 6182.64 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.359181 | 0.359181 | 0.359181 | 0.359181 | 4928.12 | 4928.12 | 6177.58 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.216994 | 0.216994 | 0.216994 | 0.216994 | 2892.70 | 2892.70 | 6177.88 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.146326 | 0.146326 | 0.146326 | 0.146326 | 1879.16 | 1879.16 | 5008.93 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.143566 | 0.143566 | 0.143566 | 0.143566 | 1914.77 | 1914.77 | 5008.82 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.312997 | 0.312997 | 0.312997 | 0.312997 | 4319.07 | 4319.07 | 5006.35 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.314095 | 0.314095 | 0.314095 | 0.314095 | 4334.29 | 4334.29 | 5006.24 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.237396 |
AIRLOOP G NW SUPPLY FAN | 0.181298 |
AIRLOOP OFFICE SUPPLY FAN | 0.372198 |
AIRLOOP G NE SUPPLY FAN | 0.181218 |
AIRLOOP G N1 SUPPLY FAN | 0.134206 |
AIRLOOP G N2 SUPPLY FAN | 0.134204 |
AIRLOOP G S1 SUPPLY FAN | 0.179553 |
AIRLOOP G S2 SUPPLY FAN | 0.186289 |
AIRLOOP F2 SW SUPPLY FAN | 0.317993 |
AIRLOOP F2 NW SUPPLY FAN | 0.229434 |
AIRLOOP F2 SE SUPPLY FAN | 0.329993 |
AIRLOOP F2 NE SUPPLY FAN | 0.186648 |
AIRLOOP F2 N1 SUPPLY FAN | 0.125199 |
AIRLOOP F2 N2 SUPPLY FAN | 0.123705 |
AIRLOOP F2 S1 SUPPLY FAN | 0.244500 |
AIRLOOP F2 S2 SUPPLY FAN | 0.246991 |
AIRLOOP F3 SW SUPPLY FAN | 0.320511 |
AIRLOOP F3 NW SUPPLY FAN | 0.233178 |
AIRLOOP F3 SE SUPPLY FAN | 0.311325 |
AIRLOOP F3 NE SUPPLY FAN | 0.190812 |
AIRLOOP F3 N1 SUPPLY FAN | 0.129973 |
AIRLOOP F3 N2 SUPPLY FAN | 0.128502 |
AIRLOOP F3 S1 SUPPLY FAN | 0.248982 |
AIRLOOP F3 S2 SUPPLY FAN | 0.250175 |
AIRLOOP F4 SW SUPPLY FAN | 0.320921 |
AIRLOOP F4 NW SUPPLY FAN | 0.233670 |
AIRLOOP F4 SE SUPPLY FAN | 0.309899 |
AIRLOOP F4 NE SUPPLY FAN | 0.191177 |
AIRLOOP F4 N1 SUPPLY FAN | 0.130771 |
AIRLOOP F4 N2 SUPPLY FAN | 0.129300 |
AIRLOOP F4 S1 SUPPLY FAN | 0.249871 |
AIRLOOP F4 S2 SUPPLY FAN | 0.250884 |
AIRLOOP M SW SUPPLY FAN | 0.322998 |
AIRLOOP M NW SUPPLY FAN | 0.235787 |
AIRLOOP M SE SUPPLY FAN | 0.311915 |
AIRLOOP M NE SUPPLY FAN | 0.193157 |
AIRLOOP M N1 SUPPLY FAN | 0.133050 |
AIRLOOP M N2 SUPPLY FAN | 0.131582 |
AIRLOOP M S1 SUPPLY FAN | 0.252258 |
AIRLOOP M S2 SUPPLY FAN | 0.253243 |
AIRLOOP F6 SW SUPPLY FAN | 0.319338 |
AIRLOOP F6 NW SUPPLY FAN | 0.232157 |
AIRLOOP F6 SE SUPPLY FAN | 0.308433 |
AIRLOOP F6 NE SUPPLY FAN | 0.189541 |
AIRLOOP F6 N1 SUPPLY FAN | 0.129741 |
AIRLOOP F6 N2 SUPPLY FAN | 0.128279 |
AIRLOOP F6 S1 SUPPLY FAN | 0.248844 |
AIRLOOP F6 S2 SUPPLY FAN | 0.249826 |
AIRLOOP F7 SW SUPPLY FAN | 0.317815 |
AIRLOOP F7 NW SUPPLY FAN | 0.230685 |
AIRLOOP F7 SE SUPPLY FAN | 0.307057 |
AIRLOOP F7 NE SUPPLY FAN | 0.188094 |
AIRLOOP F7 N1 SUPPLY FAN | 0.128496 |
AIRLOOP F7 N2 SUPPLY FAN | 0.127040 |
AIRLOOP F7 S1 SUPPLY FAN | 0.247531 |
AIRLOOP F7 S2 SUPPLY FAN | 0.248511 |
AIRLOOP F8 SW SUPPLY FAN | 0.317379 |
AIRLOOP F8 NW SUPPLY FAN | 0.230379 |
AIRLOOP F8 SE SUPPLY FAN | 0.306744 |
AIRLOOP F8 NE SUPPLY FAN | 0.187753 |
AIRLOOP F8 N1 SUPPLY FAN | 0.128448 |
AIRLOOP F8 N2 SUPPLY FAN | 0.126999 |
AIRLOOP F8 S1 SUPPLY FAN | 0.247283 |
AIRLOOP F8 S2 SUPPLY FAN | 0.248264 |
AIRLOOP F9 SW SUPPLY FAN | 0.323540 |
AIRLOOP F9 NW SUPPLY FAN | 0.236842 |
AIRLOOP F9 SE SUPPLY FAN | 0.312150 |
AIRLOOP F9 NE SUPPLY FAN | 0.190196 |
AIRLOOP F9 N1 SUPPLY FAN | 0.134116 |
AIRLOOP F9 N2 SUPPLY FAN | 0.132607 |
AIRLOOP F9 S1 SUPPLY FAN | 0.251727 |
AIRLOOP F9 S2 SUPPLY FAN | 0.252830 |
AIRLOOP T SW SUPPLY FAN | 0.377844 |
AIRLOOP T NW SUPPLY FAN | 0.276439 |
AIRLOOP T SE SUPPLY FAN | 0.359181 |
AIRLOOP T NE SUPPLY FAN | 0.216994 |
AIRLOOP T N1 SUPPLY FAN | 0.146326 |
AIRLOOP T N2 SUPPLY FAN | 0.143566 |
AIRLOOP T S1 SUPPLY FAN | 0.312997 |
AIRLOOP T S2 SUPPLY FAN | 0.314095 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.237396 | 3265.29 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.181298 | 2420.70 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.372198 | 5143.49 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.181218 | 2383.21 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.134206 | 1619.08 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.134204 | 1613.17 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.179553 | 2499.75 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.186289 | 2593.10 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.317993 | 4363.84 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.229434 | 3088.38 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.329993 | 4559.12 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.186648 | 2482.40 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.125199 | 1592.03 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.123705 | 1571.16 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.244500 | 3391.90 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.246991 | 3426.42 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.320511 | 4395.62 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.233178 | 3132.65 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.311325 | 4292.86 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.190812 | 2532.79 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.129973 | 1653.88 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.128502 | 1633.37 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.248982 | 3449.28 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.250175 | 3465.81 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.320921 | 4395.47 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.233670 | 3133.71 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.309899 | 4267.37 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.191177 | 2532.55 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.130771 | 1661.47 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.129300 | 1640.97 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.249871 | 3458.07 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.250884 | 3472.10 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.322998 | 4419.48 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.235787 | 3158.44 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.311915 | 4290.57 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.193157 | 2555.59 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.133050 | 1690.38 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.131582 | 1669.93 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.252258 | 3488.24 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.253243 | 3501.89 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.319338 | 4364.80 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.232157 | 3104.02 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.308433 | 4238.42 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.189541 | 2502.11 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.129741 | 1641.83 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.128279 | 1621.47 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.248844 | 3438.51 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.249826 | 3452.12 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.317815 | 4340.19 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.230685 | 3080.11 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.307057 | 4215.88 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.188094 | 2490.45 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.128496 | 1622.39 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.127040 | 1602.10 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.247531 | 3418.17 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.248511 | 3431.75 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.317379 | 4331.01 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.230379 | 3072.78 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.306744 | 4208.44 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.187753 | 2482.97 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.128448 | 1619.84 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.126999 | 1599.67 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.247283 | 3412.81 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.248264 | 3426.40 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.323540 | 4408.67 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.236842 | 3159.65 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.312150 | 4280.34 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.190196 | 2514.10 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.134116 | 1697.06 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.132607 | 1676.06 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.251727 | 3472.54 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.252830 | 3487.82 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.377844 | 5172.71 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.276439 | 3727.97 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.359181 | 4928.12 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.216994 | 2892.70 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.146326 | 1879.16 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.143566 | 1914.77 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.312997 | 4319.07 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.314095 | 4334.29 | 0.000095 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 5905.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 5918.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 7328.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 5916.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 4891.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 4891.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 4877.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 4883.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 4951.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 4945.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 4966.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 4943.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 3763.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 3763.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 3772.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 3773.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 4745.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 4741.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 4743.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 4738.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 3551.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 3551.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 3556.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 3556.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 4721.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 4718.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 4718.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 4714.89 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 3517.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 3517.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 3521.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 3521.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 4702.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 4698.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 4698.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 4694.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 3490.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 3490.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 3496.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 3496.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 4754.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 4750.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 4750.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 4746.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 3533.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 3533.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 3538.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 3538.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 4783.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 4778.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 4778.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 4774.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 3555.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 3555.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 3561.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 3561.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 4826.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 4821.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 4821.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 4816.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 3593.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 3593.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 3600.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 3600.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 5074.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 5064.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 5069.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 5059.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 3820.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 3820.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 3831.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 3831.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 6182.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 6182.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 6177.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 6177.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 5008.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 5008.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 5006.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 5006.24 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005384 | 6.06 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005384 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005384 | 2599.31 | 6.95 | 7939.30 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005384 | 1719.50 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.72 | -10.3 |
April | 22.26 | 0.73 |
May | 22.85 | 10.60 |
June | 23.97 | 15.96 |
July | 24.10 | 16.86 |
August | 23.87 | 14.24 |
September | 22.82 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.52 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.10 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.80 | 0.73 |
May | 22.20 | 10.60 |
June | 23.77 | 15.96 |
July | 23.96 | 16.86 |
August | 23.45 | 14.24 |
September | 22.13 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.30 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.96 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.85 | -10.3 |
April | 22.45 | 0.73 |
May | 23.33 | 10.60 |
June | 24.23 | 15.96 |
July | 24.31 | 16.86 |
August | 24.15 | 14.24 |
September | 23.17 | 6.72 |
October | 21.91 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.69 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.77 | 0.73 |
May | 22.46 | 10.60 |
June | 23.85 | 15.96 |
July | 24.03 | 16.86 |
August | 23.55 | 14.24 |
September | 22.21 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.34 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.03 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.72 | 0.73 |
May | 22.05 | 10.60 |
June | 23.66 | 15.96 |
July | 23.90 | 16.86 |
August | 23.42 | 14.24 |
September | 22.16 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.26 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.90 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.72 | 0.73 |
May | 22.07 | 10.60 |
June | 23.67 | 15.96 |
July | 23.90 | 16.86 |
August | 23.43 | 14.24 |
September | 22.17 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.27 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.90 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.72 | -10.3 |
April | 22.23 | 0.73 |
May | 22.80 | 10.60 |
June | 23.94 | 15.96 |
July | 24.09 | 16.86 |
August | 23.93 | 14.24 |
September | 23.03 | 6.72 |
October | 21.79 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.53 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.09 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.73 | -10.3 |
April | 22.27 | 0.73 |
May | 22.88 | 10.60 |
June | 23.98 | 15.96 |
July | 24.12 | 16.86 |
August | 23.98 | 14.24 |
September | 23.09 | 6.72 |
October | 21.80 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.56 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.12 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.76 | -17.6 |
February | 10.72 | -15.4 |
March | 12.50 | -10.3 |
April | 16.34 | 0.73 |
May | 19.95 | 10.60 |
June | 22.63 | 15.96 |
July | 23.16 | 16.86 |
August | 22.02 | 14.24 |
September | 18.96 | 6.72 |
October | 14.68 | -3.1 |
November | 10.02 | -17.6 |
December | 9.33 | -19.3 |
Annual Sum or Average | 15.87 | -1.4 |
Minimum of Months | 9.33 | -19.3 |
Maximum of Months | 23.16 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.79 | -10.3 |
April | 22.75 | 0.73 |
May | 23.81 | 10.60 |
June | 24.29 | 15.96 |
July | 24.33 | 16.86 |
August | 24.20 | 14.24 |
September | 23.27 | 6.72 |
October | 21.84 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.76 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.97 | 0.73 |
May | 23.05 | 10.60 |
June | 24.15 | 15.96 |
July | 24.24 | 16.86 |
August | 23.83 | 14.24 |
September | 22.30 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.48 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.84 | -10.3 |
April | 22.86 | 0.73 |
May | 23.97 | 10.60 |
June | 24.34 | 15.96 |
July | 24.37 | 16.86 |
August | 24.27 | 14.24 |
September | 23.46 | 6.72 |
October | 21.93 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.83 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.37 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.95 | 0.73 |
May | 23.26 | 10.60 |
June | 24.17 | 15.96 |
July | 24.26 | 16.86 |
August | 23.85 | 14.24 |
September | 22.35 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.51 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.26 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.84 | 0.73 |
May | 22.82 | 10.60 |
June | 24.05 | 15.96 |
July | 24.18 | 16.86 |
August | 23.76 | 14.24 |
September | 22.30 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.18 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.84 | 0.73 |
May | 22.86 | 10.60 |
June | 24.06 | 15.96 |
July | 24.18 | 16.86 |
August | 23.77 | 14.24 |
September | 22.31 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.18 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.84 | -10.3 |
April | 22.86 | 0.73 |
May | 23.89 | 10.60 |
June | 24.28 | 15.96 |
July | 24.31 | 16.86 |
August | 24.24 | 14.24 |
September | 23.52 | 6.72 |
October | 21.98 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.85 | -10.3 |
April | 22.88 | 0.73 |
May | 23.91 | 10.60 |
June | 24.29 | 15.96 |
July | 24.32 | 16.86 |
August | 24.25 | 14.24 |
September | 23.55 | 6.72 |
October | 22.00 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.83 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.83 | -17.6 |
February | 20.31 | -15.4 |
March | 20.91 | -10.3 |
April | 22.57 | 0.73 |
May | 24.44 | 10.60 |
June | 25.81 | 15.96 |
July | 25.93 | 16.86 |
August | 25.36 | 14.24 |
September | 23.54 | 6.72 |
October | 21.30 | -3.1 |
November | 20.12 | -17.6 |
December | 19.68 | -19.3 |
Annual Sum or Average | 22.50 | -1.4 |
Minimum of Months | 19.68 | -19.3 |
Maximum of Months | 25.93 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.80 | -10.3 |
April | 22.83 | 0.73 |
May | 23.93 | 10.60 |
June | 24.30 | 15.96 |
July | 24.34 | 16.86 |
August | 24.21 | 14.24 |
September | 23.33 | 6.72 |
October | 21.85 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.79 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.03 | 0.73 |
May | 23.27 | 10.60 |
June | 24.16 | 15.96 |
July | 24.27 | 16.86 |
August | 23.88 | 14.24 |
September | 22.34 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.52 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.83 | -10.3 |
April | 22.86 | 0.73 |
May | 23.99 | 10.60 |
June | 24.32 | 15.96 |
July | 24.36 | 16.86 |
August | 24.24 | 14.24 |
September | 23.41 | 6.72 |
October | 21.90 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.01 | 0.73 |
May | 23.44 | 10.60 |
June | 24.18 | 15.96 |
July | 24.28 | 16.86 |
August | 23.89 | 14.24 |
September | 22.40 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.54 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.90 | 0.73 |
May | 23.15 | 10.60 |
June | 24.10 | 15.96 |
July | 24.22 | 16.86 |
August | 23.84 | 14.24 |
September | 22.38 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.49 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.22 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.90 | 0.73 |
May | 23.18 | 10.60 |
June | 24.10 | 15.96 |
July | 24.22 | 16.86 |
August | 23.85 | 14.24 |
September | 22.39 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.49 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.22 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.88 | -10.3 |
April | 23.00 | 0.73 |
May | 24.05 | 10.60 |
June | 24.29 | 15.96 |
July | 24.33 | 16.86 |
August | 24.27 | 14.24 |
September | 23.61 | 6.72 |
October | 22.05 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.86 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.89 | -10.3 |
April | 23.01 | 0.73 |
May | 24.06 | 10.60 |
June | 24.30 | 15.96 |
July | 24.33 | 16.86 |
August | 24.27 | 14.24 |
September | 23.63 | 6.72 |
October | 22.06 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | -17.6 |
February | 21.22 | -15.4 |
March | 21.71 | -10.3 |
April | 23.20 | 0.73 |
May | 25.05 | 10.60 |
June | 26.12 | 15.96 |
July | 26.20 | 16.86 |
August | 25.67 | 14.24 |
September | 23.94 | 6.72 |
October | 21.88 | -3.1 |
November | 21.10 | -17.6 |
December | 20.65 | -19.3 |
Annual Sum or Average | 23.14 | -1.4 |
Minimum of Months | 20.65 | -19.3 |
Maximum of Months | 26.20 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.80 | -10.3 |
April | 22.81 | 0.73 |
May | 23.93 | 10.60 |
June | 24.29 | 15.96 |
July | 24.35 | 16.86 |
August | 24.20 | 14.24 |
September | 23.33 | 6.72 |
October | 21.84 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.79 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.03 | 0.73 |
May | 23.32 | 10.60 |
June | 24.15 | 15.96 |
July | 24.28 | 16.86 |
August | 23.89 | 14.24 |
September | 22.37 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.53 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.82 | -10.3 |
April | 22.83 | 0.73 |
May | 23.98 | 10.60 |
June | 24.30 | 15.96 |
July | 24.36 | 16.86 |
August | 24.23 | 14.24 |
September | 23.38 | 6.72 |
October | 21.88 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.81 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.01 | 0.73 |
May | 23.48 | 10.60 |
June | 24.17 | 15.96 |
July | 24.29 | 16.86 |
August | 23.90 | 14.24 |
September | 22.42 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.55 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.91 | 0.73 |
May | 23.27 | 10.60 |
June | 24.10 | 15.96 |
July | 24.24 | 16.86 |
August | 23.87 | 14.24 |
September | 22.42 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.51 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.91 | 0.73 |
May | 23.30 | 10.60 |
June | 24.10 | 15.96 |
July | 24.24 | 16.86 |
August | 23.88 | 14.24 |
September | 22.44 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.51 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.88 | -10.3 |
April | 23.01 | 0.73 |
May | 24.08 | 10.60 |
June | 24.29 | 15.96 |
July | 24.34 | 16.86 |
August | 24.27 | 14.24 |
September | 23.63 | 6.72 |
October | 22.05 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.89 | -10.3 |
April | 23.01 | 0.73 |
May | 24.08 | 10.60 |
June | 24.29 | 15.96 |
July | 24.34 | 16.86 |
August | 24.27 | 14.24 |
September | 23.64 | 6.72 |
October | 22.06 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | -17.6 |
February | 21.42 | -15.4 |
March | 21.90 | -10.3 |
April | 23.36 | 0.73 |
May | 25.24 | 10.60 |
June | 26.22 | 15.96 |
July | 26.31 | 16.86 |
August | 25.78 | 14.24 |
September | 24.08 | 6.72 |
October | 22.03 | -3.1 |
November | 21.32 | -17.6 |
December | 20.86 | -19.3 |
Annual Sum or Average | 23.30 | -1.4 |
Minimum of Months | 20.86 | -19.3 |
Maximum of Months | 26.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.80 | -10.3 |
April | 22.79 | 0.73 |
May | 23.91 | 10.60 |
June | 24.27 | 15.96 |
July | 24.34 | 16.86 |
August | 24.19 | 14.24 |
September | 23.32 | 6.72 |
October | 21.84 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.78 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.02 | 0.73 |
May | 23.30 | 10.60 |
June | 24.13 | 15.96 |
July | 24.27 | 16.86 |
August | 23.87 | 14.24 |
September | 22.37 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.52 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.82 | -10.3 |
April | 22.81 | 0.73 |
May | 23.96 | 10.60 |
June | 24.29 | 15.96 |
July | 24.36 | 16.86 |
August | 24.22 | 14.24 |
September | 23.37 | 6.72 |
October | 21.87 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.80 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.36 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.01 | 0.73 |
May | 23.46 | 10.60 |
June | 24.14 | 15.96 |
July | 24.29 | 16.86 |
August | 23.88 | 14.24 |
September | 22.42 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.54 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.92 | 0.73 |
May | 23.28 | 10.60 |
June | 24.08 | 15.96 |
July | 24.24 | 16.86 |
August | 23.87 | 14.24 |
September | 22.44 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.51 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.92 | 0.73 |
May | 23.30 | 10.60 |
June | 24.09 | 15.96 |
July | 24.24 | 16.86 |
August | 23.88 | 14.24 |
September | 22.46 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.51 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.89 | -10.3 |
April | 23.00 | 0.73 |
May | 24.07 | 10.60 |
June | 24.28 | 15.96 |
July | 24.33 | 16.86 |
August | 24.27 | 14.24 |
September | 23.63 | 6.72 |
October | 22.05 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.89 | -10.3 |
April | 23.00 | 0.73 |
May | 24.07 | 10.60 |
June | 24.28 | 15.96 |
July | 24.34 | 16.86 |
August | 24.27 | 14.24 |
September | 23.64 | 6.72 |
October | 22.05 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.87 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | -17.6 |
February | 22.02 | -15.4 |
March | 22.48 | -10.3 |
April | 23.90 | 0.73 |
May | 25.78 | 10.60 |
June | 26.75 | 15.96 |
July | 26.86 | 16.86 |
August | 26.32 | 14.24 |
September | 24.65 | 6.72 |
October | 22.62 | -3.1 |
November | 21.93 | -17.6 |
December | 21.48 | -19.3 |
Annual Sum or Average | 23.88 | -1.4 |
Minimum of Months | 21.48 | -19.3 |
Maximum of Months | 26.86 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.79 | -10.3 |
April | 22.73 | 0.73 |
May | 23.83 | 10.60 |
June | 24.24 | 15.96 |
July | 24.33 | 16.86 |
August | 24.14 | 14.24 |
September | 23.24 | 6.72 |
October | 21.81 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.75 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.98 | 0.73 |
May | 23.16 | 10.60 |
June | 24.07 | 15.96 |
July | 24.24 | 16.86 |
August | 23.78 | 14.24 |
September | 22.27 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.48 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.81 | -10.3 |
April | 22.75 | 0.73 |
May | 23.89 | 10.60 |
June | 24.26 | 15.96 |
July | 24.35 | 16.86 |
August | 24.17 | 14.24 |
September | 23.29 | 6.72 |
October | 21.84 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.77 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.97 | 0.73 |
May | 23.34 | 10.60 |
June | 24.09 | 15.96 |
July | 24.26 | 16.86 |
August | 23.79 | 14.24 |
September | 22.32 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.50 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.26 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.88 | 0.73 |
May | 23.13 | 10.60 |
June | 24.03 | 15.96 |
July | 24.21 | 16.86 |
August | 23.79 | 14.24 |
September | 22.34 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.47 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.21 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.88 | 0.73 |
May | 23.16 | 10.60 |
June | 24.03 | 15.96 |
July | 24.21 | 16.86 |
August | 23.79 | 14.24 |
September | 22.35 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.48 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.21 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.86 | -10.3 |
April | 22.93 | 0.73 |
May | 24.01 | 10.60 |
June | 24.25 | 15.96 |
July | 24.32 | 16.86 |
August | 24.23 | 14.24 |
September | 23.56 | 6.72 |
October | 22.00 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.84 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.87 | -10.3 |
April | 22.94 | 0.73 |
May | 24.02 | 10.60 |
June | 24.25 | 15.96 |
July | 24.32 | 16.86 |
August | 24.24 | 14.24 |
September | 23.57 | 6.72 |
October | 22.01 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.84 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | -17.6 |
February | 21.41 | -15.4 |
March | 21.86 | -10.3 |
April | 23.27 | 0.73 |
May | 25.12 | 10.60 |
June | 26.15 | 15.96 |
July | 26.28 | 16.86 |
August | 25.70 | 14.24 |
September | 23.99 | 6.72 |
October | 21.98 | -3.1 |
November | 21.33 | -17.6 |
December | 20.86 | -19.3 |
Annual Sum or Average | 23.25 | -1.4 |
Minimum of Months | 20.86 | -19.3 |
Maximum of Months | 26.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.78 | -10.3 |
April | 22.69 | 0.73 |
May | 23.77 | 10.60 |
June | 24.21 | 15.96 |
July | 24.31 | 16.86 |
August | 24.10 | 14.24 |
September | 23.18 | 6.72 |
October | 21.80 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.73 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.95 | 0.73 |
May | 23.04 | 10.60 |
June | 24.03 | 15.96 |
July | 24.22 | 16.86 |
August | 23.71 | 14.24 |
September | 22.20 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.45 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.22 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.80 | -10.3 |
April | 22.70 | 0.73 |
May | 23.83 | 10.60 |
June | 24.23 | 15.96 |
July | 24.34 | 16.86 |
August | 24.14 | 14.24 |
September | 23.23 | 6.72 |
October | 21.82 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.75 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.94 | 0.73 |
May | 23.24 | 10.60 |
June | 24.04 | 15.96 |
July | 24.23 | 16.86 |
August | 23.72 | 14.24 |
September | 22.24 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.47 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.23 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.86 | 0.73 |
May | 23.00 | 10.60 |
June | 23.98 | 15.96 |
July | 24.19 | 16.86 |
August | 23.71 | 14.24 |
September | 22.26 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.86 | 0.73 |
May | 23.03 | 10.60 |
June | 23.98 | 15.96 |
July | 24.19 | 16.86 |
August | 23.72 | 14.24 |
September | 22.27 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.85 | -10.3 |
April | 22.89 | 0.73 |
May | 23.96 | 10.60 |
June | 24.22 | 15.96 |
July | 24.31 | 16.86 |
August | 24.21 | 14.24 |
September | 23.51 | 6.72 |
October | 21.96 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.85 | -10.3 |
April | 22.89 | 0.73 |
May | 23.97 | 10.60 |
June | 24.23 | 15.96 |
July | 24.31 | 16.86 |
August | 24.21 | 14.24 |
September | 23.52 | 6.72 |
October | 21.97 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.84 | -17.6 |
February | 21.28 | -15.4 |
March | 21.72 | -10.3 |
April | 23.11 | 0.73 |
May | 24.93 | 10.60 |
June | 26.02 | 15.96 |
July | 26.17 | 16.86 |
August | 25.56 | 14.24 |
September | 23.82 | 6.72 |
October | 21.83 | -3.1 |
November | 21.22 | -17.6 |
December | 20.74 | -19.3 |
Annual Sum or Average | 23.12 | -1.4 |
Minimum of Months | 20.74 | -19.3 |
Maximum of Months | 26.17 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.77 | -10.3 |
April | 22.65 | 0.73 |
May | 23.71 | 10.60 |
June | 24.18 | 15.96 |
July | 24.30 | 16.86 |
August | 24.06 | 14.24 |
September | 23.11 | 6.72 |
October | 21.78 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.70 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.93 | 0.73 |
May | 22.94 | 10.60 |
June | 23.99 | 15.96 |
July | 24.20 | 16.86 |
August | 23.64 | 14.24 |
September | 22.15 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.43 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.20 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.79 | -10.3 |
April | 22.66 | 0.73 |
May | 23.78 | 10.60 |
June | 24.21 | 15.96 |
July | 24.33 | 16.86 |
August | 24.10 | 14.24 |
September | 23.17 | 6.72 |
October | 21.80 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.73 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.92 | 0.73 |
May | 23.15 | 10.60 |
June | 24.00 | 15.96 |
July | 24.21 | 16.86 |
August | 23.65 | 14.24 |
September | 22.18 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.45 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.21 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.85 | 0.73 |
May | 22.90 | 10.60 |
June | 23.94 | 15.96 |
July | 24.16 | 16.86 |
August | 23.65 | 14.24 |
September | 22.20 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.41 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.16 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.85 | 0.73 |
May | 22.93 | 10.60 |
June | 23.95 | 15.96 |
July | 24.17 | 16.86 |
August | 23.65 | 14.24 |
September | 22.21 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.42 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.17 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.84 | -10.3 |
April | 22.84 | 0.73 |
May | 23.91 | 10.60 |
June | 24.20 | 15.96 |
July | 24.30 | 16.86 |
August | 24.18 | 14.24 |
September | 23.45 | 6.72 |
October | 21.93 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.79 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.84 | -10.3 |
April | 22.85 | 0.73 |
May | 23.92 | 10.60 |
June | 24.20 | 15.96 |
July | 24.30 | 16.86 |
August | 24.18 | 14.24 |
September | 23.46 | 6.72 |
October | 21.93 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.80 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | -17.6 |
February | 21.21 | -15.4 |
March | 21.64 | -10.3 |
April | 23.02 | 0.73 |
May | 24.82 | 10.60 |
June | 25.97 | 15.96 |
July | 26.14 | 16.86 |
August | 25.48 | 14.24 |
September | 23.71 | 6.72 |
October | 21.74 | -3.1 |
November | 21.16 | -17.6 |
December | 20.67 | -19.3 |
Annual Sum or Average | 23.04 | -1.4 |
Minimum of Months | 20.67 | -19.3 |
Maximum of Months | 26.14 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.76 | -10.3 |
April | 22.59 | 0.73 |
May | 23.62 | 10.60 |
June | 24.15 | 15.96 |
July | 24.29 | 16.86 |
August | 24.01 | 14.24 |
September | 23.00 | 6.72 |
October | 21.77 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.92 | 0.73 |
May | 22.86 | 10.60 |
June | 23.95 | 15.96 |
July | 24.17 | 16.86 |
August | 23.57 | 14.24 |
September | 22.10 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.40 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.17 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.78 | -10.3 |
April | 22.61 | 0.73 |
May | 23.72 | 10.60 |
June | 24.18 | 15.96 |
July | 24.31 | 16.86 |
August | 24.05 | 14.24 |
September | 23.06 | 6.72 |
October | 21.78 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.70 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.91 | 0.73 |
May | 23.07 | 10.60 |
June | 23.96 | 15.96 |
July | 24.19 | 16.86 |
August | 23.58 | 14.24 |
September | 22.12 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.42 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.84 | 0.73 |
May | 22.81 | 10.60 |
June | 23.90 | 15.96 |
July | 24.14 | 16.86 |
August | 23.57 | 14.24 |
September | 22.12 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.39 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.14 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.84 | 0.73 |
May | 22.84 | 10.60 |
June | 23.91 | 15.96 |
July | 24.14 | 16.86 |
August | 23.57 | 14.24 |
September | 22.13 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.39 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.14 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.82 | -10.3 |
April | 22.78 | 0.73 |
May | 23.84 | 10.60 |
June | 24.17 | 15.96 |
July | 24.29 | 16.86 |
August | 24.13 | 14.24 |
September | 23.33 | 6.72 |
October | 21.88 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.76 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.82 | -10.3 |
April | 22.78 | 0.73 |
May | 23.85 | 10.60 |
June | 24.18 | 15.96 |
July | 24.29 | 16.86 |
August | 24.14 | 14.24 |
September | 23.34 | 6.72 |
October | 21.89 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.76 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.29 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -17.6 |
February | 20.98 | -15.4 |
March | 21.44 | -10.3 |
April | 22.89 | 0.73 |
May | 24.71 | 10.60 |
June | 25.95 | 15.96 |
July | 26.15 | 16.86 |
August | 25.41 | 14.24 |
September | 23.54 | 6.72 |
October | 21.57 | -3.1 |
November | 20.91 | -17.6 |
December | 20.42 | -19.3 |
Annual Sum or Average | 22.89 | -1.4 |
Minimum of Months | 20.42 | -19.3 |
Maximum of Months | 26.15 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.81 | -10.3 |
April | 22.49 | 0.73 |
May | 23.27 | 10.60 |
June | 24.00 | 15.96 |
July | 24.19 | 16.86 |
August | 23.80 | 14.24 |
September | 22.70 | 6.72 |
October | 21.77 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.57 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.71 | -10.3 |
April | 22.00 | 0.73 |
May | 22.76 | 10.60 |
June | 23.81 | 15.96 |
July | 24.04 | 16.86 |
August | 23.38 | 14.24 |
September | 22.11 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.37 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.04 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.83 | -10.3 |
April | 22.51 | 0.73 |
May | 23.37 | 10.60 |
June | 24.03 | 15.96 |
July | 24.21 | 16.86 |
August | 23.83 | 14.24 |
September | 22.75 | 6.72 |
October | 21.78 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.60 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.21 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.71 | -10.3 |
April | 21.99 | 0.73 |
May | 22.93 | 10.60 |
June | 23.80 | 15.96 |
July | 24.03 | 16.86 |
August | 23.37 | 14.24 |
September | 22.11 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.37 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.03 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.91 | 0.73 |
May | 22.69 | 10.60 |
June | 23.76 | 15.96 |
July | 24.01 | 16.86 |
August | 23.34 | 14.24 |
September | 22.07 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.34 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.01 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.91 | 0.73 |
May | 22.72 | 10.60 |
June | 23.76 | 15.96 |
July | 24.01 | 16.86 |
August | 23.34 | 14.24 |
September | 22.07 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.34 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.01 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.87 | -10.3 |
April | 22.60 | 0.73 |
May | 23.46 | 10.60 |
June | 24.06 | 15.96 |
July | 24.23 | 16.86 |
August | 23.96 | 14.24 |
September | 22.95 | 6.72 |
October | 21.85 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.23 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.72 | -15.4 |
March | 21.88 | -10.3 |
April | 22.60 | 0.73 |
May | 23.47 | 10.60 |
June | 24.07 | 15.96 |
July | 24.23 | 16.86 |
August | 23.97 | 14.24 |
September | 22.96 | 6.72 |
October | 21.85 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.23 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:00:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.87 | -17.6 |
February | 20.42 | -15.4 |
March | 21.19 | -10.3 |
April | 23.03 | 0.73 |
May | 25.08 | 10.60 |
June | 26.54 | 15.96 |
July | 26.74 | 16.86 |
August | 25.81 | 14.24 |
September | 23.62 | 6.72 |
October | 21.43 | -3.1 |
November | 20.20 | -17.6 |
December | 19.72 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 19.72 | -19.3 |
Maximum of Months | 26.74 | 16.86 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:31
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.350580E+12 | 332168.454 | 28-JAN-23:00 | 7484.424 | 29363.654 | 21186.302 | 261078.471 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.289188E+12 | 229090.749 | 23-FEB-18:00 | 13120.457 | 57042.023 | 21186.302 | 123633.527 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.283809E+12 | 164583.444 | 02-MAR-04:00 | 7740.608 | 20063.478 | 21186.302 | 102811.346 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.230819E+12 | 166390.740 | 02-APR-19:00 | 14401.373 | 49889.926 | 21186.302 | 67151.404 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.209062E+12 | 131653.858 | 31-MAY-16:15 | 11327.174 | 57142.088 | 21186.302 | 0.000 | 37046.712 | 0.000 | 1756.430 | 1199.956 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.218332E+12 | 151594.786 | 20-JUN-17:15 | 13120.457 | 57042.023 | 21186.302 | 0.000 | 54706.090 | 0.000 | 1756.430 | 1795.671 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.235749E+12 | 153878.273 | 11-JUL-17:15 | 13120.457 | 57042.023 | 21186.302 | 0.000 | 56914.076 | 0.000 | 1756.430 | 1871.173 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.221574E+12 | 151358.450 | 11-AUG-17:15 | 13120.457 | 57042.023 | 21186.302 | 0.000 | 54492.539 | 0.000 | 1756.430 | 1772.887 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.206559E+12 | 113385.613 | 08-SEP-16:15 | 11327.174 | 57142.088 | 21186.302 | 0.000 | 19260.175 | 0.000 | 1756.430 | 718.247 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.263175E+12 | 153496.014 | 31-OCT-07:15 | 9617.308 | 41626.099 | 21186.302 | 67846.608 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.301050E+12 | 177744.909 | 29-NOV-07:00 | 9533.891 | 40866.781 | 21186.302 | 92970.610 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.347616E+12 | 192377.725 | 01-DEC-17:00 | 11327.174 | 57142.088 | 21186.302 | 88606.572 | 0.000 | 10364.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.315751E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.206559E+12 | 113385.613 | 7484.424 | 20063.478 | 21186.302 | 0.000 | 0.000 | 0.000 | 1756.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.350580E+12 | 332168.454 | 14401.373 | 57142.088 | 21186.302 | 261078.471 | 56914.076 | 10364.000 | 1756.430 | 1871.173 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:31
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.583800E+12 | 344253.993 | 29-JAN-07:00 | 0.000 | 0.000 | 0.000 | 344253.993 | 89941.367 | 89941.367 | 254312.626 |
February | 0.462208E+12 | 339615.400 | 24-FEB-06:45 | 0.000 | 0.000 | 0.000 | 339615.400 | 85768.070 | 85768.070 | 253847.331 |
March | 0.428552E+12 | 303863.358 | 02-MAR-07:00 | 0.000 | 0.000 | 0.000 | 303863.358 | 89941.177 | 89941.177 | 213922.181 |
April | 0.245888E+12 | 288700.793 | 02-APR-06:00 | 0.000 | 0.000 | 0.000 | 288700.793 | 89941.375 | 89941.375 | 198759.418 |
May | 0.135300E+12 | 166251.630 | 27-MAY-10:45 | 0.000 | 0.000 | 0.000 | 166251.630 | 71571.265 | 71571.265 | 94680.366 |
June | 0.122087E+12 | 90572.168 | 09-JUN-06:00 | 0.000 | 0.000 | 0.000 | 90572.168 | 90572.168 | 90572.168 | 0.000 |
July | 0.121656E+12 | 87936.208 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 87936.208 | 87936.208 | 87936.208 | 0.000 |
August | 0.119507E+12 | 111761.282 | 30-AUG-05:30 | 0.000 | 0.000 | 0.000 | 111761.282 | 79519.807 | 79519.807 | 32241.475 |
September | 0.138837E+12 | 168164.843 | 30-SEP-05:30 | 0.000 | 0.000 | 0.000 | 168164.843 | 79248.612 | 79248.612 | 88916.231 |
October | 0.345326E+12 | 287119.369 | 31-OCT-07:30 | 0.000 | 0.000 | 0.000 | 287119.369 | 85206.135 | 85206.135 | 201913.234 |
November | 0.509973E+12 | 317154.634 | 29-NOV-08:15 | 0.000 | 0.000 | 0.000 | 317154.634 | 87984.529 | 87984.529 | 229170.105 |
December | 0.604656E+12 | 326154.119 | 15-DEC-09:15 | 0.000 | 0.000 | 0.000 | 326154.119 | 84350.377 | 84350.377 | 241803.742 |
Annual Sum or Average | 0.381779E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.119507E+12 | 87936.208 | 0.000 | 0.000 | 0.000 | 87936.208 | 71571.265 | 71571.265 | 0.000 | |
Maximum of Months | 0.604656E+12 | 344253.993 | 0.000 | 0.000 | 0.000 | 344253.993 | 90572.168 | 90572.168 | 254312.626 |