Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2015-09-09 19:12:00


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4684.41 597.77 663.52
Net Site Energy 4684.41 597.77 663.52
Total Source Energy 13140.25 1676.81 1861.25
Net Source Energy 13140.25 1676.81 1861.25


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 2.28 2.69 0.00 0.00 0.00 0.00
Cooling 1430.98 0.00 0.00 0.00 0.00 0.00
Interior Lighting 296.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 163.14 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 650.69 0.00 0.00 0.00 0.00 0.00
Pumps 79.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection 73.72 0.00 0.00 0.00 0.00 3631.50
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 811.17 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3870.55 813.86 0.00 0.00 0.00 8410.01
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 2.69 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 2.28 0.00 0.00 0.00 0.00 0.00
Cooling General 1430.98 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 242.55 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 54.01 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 163.14 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 650.69 0.00 0.00 0.00 0.00 0.00
Pumps General 79.68 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 73.72 0.00 0.00 0.00 0.00 3631.50
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 811.17 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.11 0.00 0.00 0.00 0.00 0.00
HVAC 316.91 115.28 0.00 0.00 0.00 1.19
Other 161.10 0.00 0.00 0.00 0.00 0.00
Total 548.24 115.28 0.00 0.00 0.00 1.19


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 58.66 0.00 0.00 0.00 0.00 0.00
HVAC 285.50 103.86 0.00 0.00 0.00 1.07
Other 145.13 0.00 0.00 0.00 0.00 0.00
Total 493.91 103.86 0.00 0.00 0.00 1.07


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3870.55 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3870.55 100.00
     
Total On-Site and Utility Electric Sources 3870.55 100.00
Total Electricity End Uses 3870.55 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8410.01 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8410.01 100.00
Total Water End Uses 8410.01 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.50
Time Setpoint Not Met During Occupied Cooling 980.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 4324.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10
RunPeriod Miami Intl Ap FL USA TMY3 WMO#=722020
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 29.5362 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 6.7128   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 13.4255   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   264.3872
Total 7836.48     23884.04   3855.02 1150.39 4.3335 39.48 8.6291
Conditioned Total 7059.89     21517.16   3752.84 1125.85 3.9979 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 7.3840   26.4387
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-NOV-18:30 04-FEB-07:15 - - - 27-JUL-17:15
Heating 0.00 73437.26 0.00 0.00 0.00 0.00
Cooling 80892.51 0.00 0.00 0.00 0.00 0.00
Interior Lighting 13120.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 57042.02 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 20633.29 0.00 0.00 0.00 0.00 0.00
Pumps 2580.93 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3797.79 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 69627.49 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 190419.01 143064.75 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 73437.26 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 80892.51 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 10541.04 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 2579.42 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 57042.02 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 20633.29 0.00 0.00 0.00 0.00 0.00
Pumps General 2580.93 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 3797.79 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 69627.49 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 7.21 2.92 0.00 0.00 0.00
Cooling 4531.93 0.00 0.00 0.00 0.00
Interior Lighting 939.20 0.00 0.00 0.00 0.00
Exterior Lighting 516.66 0.00 0.00 0.00 0.00
Interior Equipment 3601.91 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2060.74 0.00 0.00 0.00 0.00
Pumps 252.35 0.00 0.00 0.00 0.00
Heat Rejection 233.46 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 879.31 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 12258.02 882.23 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.02 0.41 0.00 0.00 0.00
Cooling 641.93 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.18 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 291.89 0.00 0.00 0.00 0.00
Pumps 35.74 0.00 0.00 0.00 0.00
Heat Rejection 33.07 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 124.55 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1736.29 124.96 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.02 0.41 0.00 0.00 0.00
Cooling 641.93 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.18 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 291.89 0.00 0.00 0.00 0.00
Pumps 35.74 0.00 0.00 0.00 0.00
Heat Rejection 33.07 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 124.55 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1736.29 124.96 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 5.778 0.306 0.155     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_1.22_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_1.22_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 5.778 0.306 0.155              
North Total or Average           423.59 5.778 0.306 0.155              
Non-North Total or Average           726.80 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F2WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F3WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F4WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F6WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F7WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F8WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
F9WINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW3 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW9 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
OFFICE_LIGHTS_HARDWIRED OFFICE 14.7681 88.25 1303.26 GeneralLights LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
OFFICE_LIGHTS_PLUGIN OFFICE 14.7681 88.25 1303.26 GeneralLights-plugin LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 6.7128 77.66 521.30 GeneralLights-plugin LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.2679 14974.03 33959.19               296.56


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10364.00 AstronomicalClock -   83.86 83.86 163.14
Exterior Lighting Total 10364.00           163.14



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 366254.79 0.75    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 293003.83      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4657.48 3073.42 1584.07 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4863.02 3228.39 1634.63 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   6318.01 4202.77 2115.23 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4067.74 2636.58 1431.16 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2953.10 1845.21 1107.89 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2932.89 1830.49 1102.39 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2652.61 1628.90 1023.71 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2760.08 1697.86 1062.22 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5520.21 3668.16 1852.05 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5743.42 3836.61 1906.81 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5069.75 3332.45 1737.30 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4824.96 3151.30 1673.66 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3525.90 2240.36 1285.54 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3509.93 2228.61 1281.31 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3211.16 2010.90 1200.25 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3250.39 2031.94 1218.45 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5618.89 3708.27 1910.61 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5843.03 3876.39 1966.64 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4884.90 3162.20 1722.70 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4921.46 3192.19 1729.27 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3606.30 2283.30 1323.00 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3590.28 2271.58 1318.71 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3291.30 2054.94 1236.35 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3320.73 2068.83 1251.90 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5701.31 3745.16 1956.15 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5924.10 3911.65 2012.45 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4925.51 3170.25 1755.26 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4991.07 3220.72 1770.36 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3664.22 2313.94 1350.28 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3648.15 2302.23 1345.92 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3351.33 2088.06 1263.26 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3378.06 2100.00 1278.06 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5798.04 3797.68 2000.36 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6020.88 3963.78 2057.10 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5006.93 3213.01 1793.91 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5075.18 3265.26 1809.92 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3741.14 2360.73 1380.41 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3725.04 2349.02 1376.02 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3428.91 2135.75 1293.15 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3454.89 2147.24 1307.64 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5807.28 3787.85 2019.43 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6027.95 3951.79 2076.16 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5004.87 3197.12 1807.75 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5071.14 3247.63 1823.51 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3732.06 2346.19 1385.87 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3715.94 2334.52 1381.41 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3422.08 2123.99 1298.09 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3447.63 2135.03 1312.60 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5839.18 3797.27 2041.91 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6059.31 3960.40 2098.91 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5027.06 3201.16 1825.90 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5092.68 3250.98 1841.69 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3748.82 2351.63 1397.19 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3738.74 2342.98 1395.76 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3439.66 2130.75 1308.91 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3464.95 2141.55 1323.40 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5885.54 3819.10 2066.44 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6105.26 3981.58 2123.67 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5063.99 3217.44 1846.55 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5128.81 3266.52 1862.29 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3788.32 2372.90 1415.43 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3772.41 2361.46 1410.95 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3474.14 2150.23 1323.91 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3497.97 2160.00 1337.96 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   6058.01 3935.09 2122.92 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6280.73 4100.43 2180.30 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5167.55 3282.99 1884.56 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5226.28 3327.73 1898.54 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3933.58 2474.06 1459.52 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3917.41 2462.38 1455.03 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3627.29 2254.74 1372.54 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3611.35 2243.43 1367.92 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   7019.59 4642.32 2377.27 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   7167.59 4755.05 2412.53 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   6064.54 3931.73 2132.81 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   6083.65 3947.07 2136.59 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4575.97 2941.24 1634.74 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4541.53 2915.86 1625.66 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4636.37 2980.13 1656.24 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4640.93 2983.68 1657.26 0.64 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4657.48 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   4863.02 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   6318.01 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   4067.74 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2953.10 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2932.89 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2652.61 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2760.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5520.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5743.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5069.75 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4824.96 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3525.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3509.93 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3211.16 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3250.39 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5618.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5843.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4884.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4921.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3606.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3590.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3291.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3320.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5701.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5924.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4925.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4991.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3664.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3648.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3351.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3378.06 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5798.04 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   6020.88 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   5006.93 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   5075.18 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3741.14 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3725.04 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3428.91 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3454.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5807.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   6027.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5004.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   5071.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3732.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3715.94 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3422.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3447.63 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5839.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   6059.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5027.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   5092.68 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3748.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3738.74 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3439.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3464.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5885.54 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   6105.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5063.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   5128.81 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3788.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3772.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3474.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3497.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   6058.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   6280.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5167.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   5226.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3933.58 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3917.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3627.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3611.35 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   7019.59 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   7167.59 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   6064.54 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   6083.65 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   4575.97 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   4541.53 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4636.37 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4640.93 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   1633.64 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   1628.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   2118.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   1630.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   1092.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   1092.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   1094.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   1099.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   1791.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   1790.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   1810.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   1790.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1115.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1115.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1117.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1119.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   1826.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   1828.78 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   1827.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   1827.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1122.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1122.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1119.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1120.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   1870.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   1875.55 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   1867.86 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   1872.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1145.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1145.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1139.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1139.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   1890.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   1896.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   1885.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   1891.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1148.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1148.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1141.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1140.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   1964.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   1972.77 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   1959.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   1967.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1205.55 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1205.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1195.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1195.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   2013.46 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   2023.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   2007.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   2016.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1240.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1240.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1229.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1229.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   2060.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   2070.97 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   2053.40 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   2063.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   1275.42 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   1275.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   1263.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   1263.10 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   2172.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   2181.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   2164.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   2173.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   1367.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   1367.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   1356.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   1356.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   2412.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   2425.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   2404.52 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   2418.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   1654.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   1653.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   1637.31 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   1637.09 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 280.08 1160.84 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 296.64 1160.84 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 386.58 1160.84 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 235.41 1160.84 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 155.21 1160.84 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 153.66 1160.84 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 132.46 1160.84 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 138.20 1160.84 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 338.08 1160.84 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 355.92 1160.84 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 303.39 1160.84 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 284.91 1160.84 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 194.10 1160.84 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 192.87 1160.84 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 169.93 1160.84 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 170.54 1160.84 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 339.26 1160.84 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 357.17 1160.84 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 282.52 1160.84 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 286.32 1160.84 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 196.89 1160.84 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 195.66 1160.84 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 172.88 1160.84 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 172.75 1160.84 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 340.96 1160.84 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 358.68 1160.84 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 281.21 1160.84 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 286.90 1160.84 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 198.82 1160.84 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 197.59 1160.84 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 175.10 1160.84 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 174.77 1160.84 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 344.71 1160.84 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 362.37 1160.84 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 283.96 1160.84 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 289.82 1160.84 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 202.69 1160.84 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 201.46 1160.84 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 179.08 1160.84 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.71 1160.84 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 342.15 1160.84 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 359.57 1160.84 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 280.80 1160.84 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 286.47 1160.84 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 200.25 1160.84 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 199.02 1160.84 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.97 1160.84 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.56 1160.84 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 341.80 1160.84 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 359.13 1160.84 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 279.91 1160.84 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 285.52 1160.84 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 200.02 1160.84 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 198.82 1160.84 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.92 1160.84 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.48 1160.84 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 342.90 1160.84 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 360.15 1160.84 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 280.46 1160.84 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 285.98 1160.84 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 201.25 1160.84 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 200.05 1160.84 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.27 1160.84 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 177.74 1160.84 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 354.07 1160.84 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 371.55 1160.84 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 286.13 1160.84 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 291.32 1160.84 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 211.53 1160.84 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 210.31 1160.84 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.57 1160.84 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 187.40 1160.84 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.37 427.08 1160.84 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 439.29 1160.84 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 353.01 1160.84 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 354.87 1160.84 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 259.99 1160.84 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 257.33 1160.84 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 262.53 1160.84 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 262.92 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 224180.02 0.0080 2544.01 319344.75 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2564.02 3076.82 0.201 0.241 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
G NW APARTMENT 2715.71 3258.85 0.213 0.256 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
OFFICE 3539.03 4246.84 0.278 0.333 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
G NE APARTMENT 2155.06 2586.07 0.169 0.203 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.16 0.01715
G N1 APARTMENT 1420.98 1705.17 0.111 0.134 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
G N2 APARTMENT 1406.78 1688.14 0.110 0.132 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
G S1 APARTMENT 1212.72 1455.26 0.095 0.114 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
G S2 APARTMENT 1265.24 1518.29 0.099 0.119 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F2 SW APARTMENT 3094.85 3713.82 0.243 0.291 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.09 0.01715
F2 NW APARTMENT 3258.29 3909.94 0.256 0.307 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F2 SE APARTMENT 2777.24 3332.69 0.218 0.261 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F2 NE APARTMENT 2608.08 3129.70 0.205 0.245 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.16 0.01715
F2 N1 APARTMENT 1777.04 2132.44 0.139 0.167 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F2 N2 APARTMENT 1765.73 2118.87 0.138 0.166 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F2 S1 APARTMENT 1555.72 1866.86 0.122 0.146 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F2 S2 APARTMENT 1561.31 1873.57 0.122 0.147 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F3 SW APARTMENT 3105.48 3726.58 0.244 0.292 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
F3 NW APARTMENT 3269.57 3923.49 0.256 0.308 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F3 SE APARTMENT 2586.08 3103.29 0.203 0.243 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F3 NE APARTMENT 2620.86 3145.03 0.206 0.247 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.16 0.01715
F3 N1 APARTMENT 1802.50 2163.00 0.141 0.170 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F3 N2 APARTMENT 1791.23 2149.48 0.140 0.169 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F3 S1 APARTMENT 1582.69 1899.23 0.124 0.149 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F3 S2 APARTMENT 1581.46 1897.76 0.124 0.149 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F4 SW APARTMENT 3120.91 3745.09 0.245 0.294 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
F4 NW APARTMENT 3283.31 3939.97 0.257 0.309 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F4 SE APARTMENT 2574.02 3088.82 0.202 0.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F4 NE APARTMENT 2626.05 3151.26 0.206 0.247 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
F4 N1 APARTMENT 1820.12 2184.14 0.143 0.171 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F4 N2 APARTMENT 1808.86 2170.63 0.142 0.170 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F4 S1 APARTMENT 1603.00 1923.60 0.126 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F4 S2 APARTMENT 1599.93 1919.92 0.125 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
M SW APARTMENT 3155.14 3786.17 0.247 0.297 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
M NW APARTMENT 3317.06 3980.47 0.260 0.312 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
M SE APARTMENT 2599.11 3118.93 0.204 0.245 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
M NE APARTMENT 2652.80 3183.36 0.208 0.250 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
M N1 APARTMENT 1855.52 2226.62 0.146 0.175 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
M N2 APARTMENT 1844.27 2213.13 0.145 0.174 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
M S1 APARTMENT 1639.43 1967.32 0.129 0.154 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
M S2 APARTMENT 1635.94 1963.13 0.128 0.154 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F6 SW APARTMENT 3131.65 3757.98 0.246 0.295 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
F6 NW APARTMENT 3291.38 3949.65 0.258 0.310 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F6 SE APARTMENT 2570.10 3084.12 0.202 0.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F6 NE APARTMENT 2622.07 3146.49 0.206 0.247 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
F6 N1 APARTMENT 1833.16 2199.79 0.144 0.173 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F6 N2 APARTMENT 1821.97 2186.36 0.143 0.171 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F6 S1 APARTMENT 1620.11 1944.14 0.127 0.152 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F6 S2 APARTMENT 1616.27 1939.52 0.127 0.152 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F7 SW APARTMENT 3128.44 3754.13 0.245 0.294 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
F7 NW APARTMENT 3287.29 3944.75 0.258 0.309 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F7 SE APARTMENT 2561.99 3074.39 0.201 0.241 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F7 NE APARTMENT 2613.26 3135.91 0.205 0.246 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
F7 N1 APARTMENT 1831.12 2197.34 0.144 0.172 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F7 N2 APARTMENT 1820.10 2184.12 0.143 0.171 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F7 S1 APARTMENT 1619.58 1943.50 0.127 0.152 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F7 S2 APARTMENT 1615.55 1938.66 0.127 0.152 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F8 SW APARTMENT 3138.45 3766.14 0.246 0.295 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
F8 NW APARTMENT 3296.60 3955.92 0.259 0.310 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F8 SE APARTMENT 2566.91 3080.30 0.201 0.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
F8 NE APARTMENT 2617.42 3140.91 0.205 0.246 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
F8 N1 APARTMENT 1842.29 2210.75 0.144 0.173 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F8 N2 APARTMENT 1831.37 2197.65 0.144 0.172 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F8 S1 APARTMENT 1631.97 1958.37 0.128 0.154 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F8 S2 APARTMENT 1626.98 1952.38 0.128 0.153 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
F9 SW APARTMENT 3240.73 3888.88 0.254 0.305 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.09 0.01715
F9 NW APARTMENT 3400.88 4081.06 0.267 0.320 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
F9 SE APARTMENT 2618.79 3142.55 0.205 0.246 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 31.83 0.01715
F9 NE APARTMENT 2666.28 3199.53 0.209 0.251 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
F9 N1 APARTMENT 1936.43 2323.72 0.152 0.182 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F9 N2 APARTMENT 1925.24 2310.29 0.151 0.181 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
F9 S1 APARTMENT 1726.25 2071.50 0.135 0.162 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
F9 S2 APARTMENT 1715.52 2058.62 0.135 0.161 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
T SW APARTMENT 3908.72 4690.46 0.307 0.368 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 32.53 0.01715
T NW APARTMENT 4020.48 4824.57 0.315 0.378 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
T SE APARTMENT 3230.81 3876.98 0.253 0.304 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 31.99 0.01715
T NE APARTMENT 3247.78 3897.34 0.255 0.306 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 31.83 0.01715
T N1 APARTMENT 2379.97 2855.97 0.187 0.224 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.76 0.01715
T N2 APARTMENT 2355.63 2826.76 0.185 0.222 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.76 0.01715
T S1 APARTMENT 2403.08 2883.69 0.188 0.226 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715
T S2 APARTMENT 2406.64 2887.97 0.189 0.226 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.20 0.01715


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1036.68 1244.02 0.046 0.055 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
G NW APARTMENT 1032.09 1238.51 0.046 0.055 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
OFFICE 1284.94 1541.93 0.057 0.069 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:00:00 8.70 0.00699
G NE APARTMENT 1034.23 1241.08 0.046 0.055 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
G N1 APARTMENT 579.37 695.24 0.026 0.031 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
G N2 APARTMENT 579.42 695.30 0.026 0.031 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
G S1 APARTMENT 580.44 696.53 0.026 0.031 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
G S2 APARTMENT 584.62 701.54 0.026 0.031 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 SW APARTMENT 1170.12 1404.15 0.052 0.063 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 NW APARTMENT 1169.11 1402.93 0.052 0.063 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 SE APARTMENT 1185.99 1423.19 0.053 0.063 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 NE APARTMENT 1169.44 1403.32 0.052 0.063 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 N1 APARTMENT 598.29 717.95 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 N2 APARTMENT 598.30 717.96 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 S1 APARTMENT 600.50 720.59 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F2 S2 APARTMENT 601.58 721.90 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 SW APARTMENT 1199.87 1439.85 0.053 0.064 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 NW APARTMENT 1201.70 1442.04 0.054 0.064 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 SE APARTMENT 1200.32 1440.38 0.053 0.064 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 NE APARTMENT 1200.37 1440.45 0.053 0.064 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 N1 APARTMENT 604.77 725.73 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 N2 APARTMENT 604.74 725.69 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 S1 APARTMENT 602.23 722.68 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F3 S2 APARTMENT 602.38 722.85 0.027 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 SW APARTMENT 1237.18 1484.61 0.055 0.066 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 NW APARTMENT 1241.26 1489.51 0.055 0.066 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 SE APARTMENT 1234.75 1481.70 0.055 0.066 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 NE APARTMENT 1238.65 1486.38 0.055 0.066 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 N1 APARTMENT 623.79 748.55 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 N2 APARTMENT 623.72 748.47 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 S1 APARTMENT 618.65 742.38 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F4 S2 APARTMENT 618.61 742.33 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M SW APARTMENT 1253.66 1504.39 0.056 0.067 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M NW APARTMENT 1258.59 1510.31 0.056 0.067 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M SE APARTMENT 1250.00 1500.00 0.056 0.067 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M NE APARTMENT 1254.94 1505.93 0.056 0.067 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M N1 APARTMENT 626.28 751.54 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M N2 APARTMENT 626.19 751.42 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M S1 APARTMENT 620.14 744.17 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
M S2 APARTMENT 620.05 744.06 0.028 0.033 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 SW APARTMENT 1316.41 1579.69 0.059 0.070 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 NW APARTMENT 1323.47 1588.16 0.059 0.071 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 SE APARTMENT 1311.84 1574.20 0.058 0.070 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 NE APARTMENT 1318.92 1582.70 0.059 0.071 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 N1 APARTMENT 674.67 809.60 0.030 0.036 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 N2 APARTMENT 674.55 809.46 0.030 0.036 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 S1 APARTMENT 666.30 799.56 0.030 0.036 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F6 S2 APARTMENT 666.18 799.42 0.030 0.036 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 SW APARTMENT 1357.88 1629.45 0.060 0.073 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 NW APARTMENT 1365.95 1639.14 0.061 0.073 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 SE APARTMENT 1352.51 1623.02 0.060 0.072 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 NE APARTMENT 1360.62 1632.74 0.061 0.073 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 N1 APARTMENT 704.47 845.36 0.031 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 N2 APARTMENT 704.33 845.19 0.031 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 S1 APARTMENT 694.99 833.99 0.031 0.037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F7 S2 APARTMENT 694.85 833.82 0.031 0.037 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 SW APARTMENT 1397.72 1677.27 0.062 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 NW APARTMENT 1406.51 1687.81 0.063 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 SE APARTMENT 1391.66 1669.99 0.062 0.074 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 NE APARTMENT 1400.48 1680.58 0.062 0.075 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 N1 APARTMENT 733.75 880.50 0.033 0.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 N2 APARTMENT 733.59 880.31 0.033 0.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 S1 APARTMENT 723.49 868.19 0.032 0.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F8 S2 APARTMENT 723.33 868.00 0.032 0.039 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 SW APARTMENT 1492.02 1790.42 0.066 0.080 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 NW APARTMENT 1499.70 1799.64 0.067 0.080 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 SE APARTMENT 1485.28 1782.34 0.066 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 NE APARTMENT 1493.00 1791.60 0.067 0.080 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 N1 APARTMENT 811.52 973.82 0.036 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 N2 APARTMENT 811.34 973.61 0.036 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 S1 APARTMENT 802.14 962.57 0.036 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
F9 S2 APARTMENT 801.96 962.36 0.036 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T SW APARTMENT 1695.14 2034.17 0.076 0.091 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T NW APARTMENT 1706.54 2047.84 0.076 0.091 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T SE APARTMENT 1688.59 2026.31 0.075 0.090 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T NE APARTMENT 1700.00 2040.00 0.076 0.091 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T N1 APARTMENT 1053.91 1264.69 0.047 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T N2 APARTMENT 1053.73 1264.47 0.047 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T S1 APARTMENT 1039.78 1247.74 0.046 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699
T S2 APARTMENT 1039.60 1247.52 0.046 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8.70 0.00699


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.24 0.24 0.06 0.06
AIRLOOP G NW 0.26 0.26 0.06 0.06
AIRLOOP OFFICE 0.33 0.33 0.07 0.07
AIRLOOP G NE 0.20 0.20 0.06 0.06
AIRLOOP G N1 0.13 0.13 0.03 0.03
AIRLOOP G N2 0.13 0.13 0.03 0.03
AIRLOOP G S1 0.11 0.11 0.03 0.03
AIRLOOP G S2 0.12 0.12 0.03 0.03
AIRLOOP F2 SW 0.29 0.29 0.06 0.06
AIRLOOP F2 NW 0.31 0.31 0.06 0.06
AIRLOOP F2 SE 0.26 0.26 0.06 0.06
AIRLOOP F2 NE 0.25 0.25 0.06 0.06
AIRLOOP F2 N1 0.17 0.17 0.03 0.03
AIRLOOP F2 N2 0.17 0.17 0.03 0.03
AIRLOOP F2 S1 0.15 0.15 0.03 0.03
AIRLOOP F2 S2 0.15 0.15 0.03 0.03
AIRLOOP F3 SW 0.29 0.29 0.06 0.06
AIRLOOP F3 NW 0.31 0.31 0.06 0.06
AIRLOOP F3 SE 0.24 0.24 0.06 0.06
AIRLOOP F3 NE 0.25 0.25 0.06 0.06
AIRLOOP F3 N1 0.17 0.17 0.03 0.03
AIRLOOP F3 N2 0.17 0.17 0.03 0.03
AIRLOOP F3 S1 0.15 0.15 0.03 0.03
AIRLOOP F3 S2 0.15 0.15 0.03 0.03
AIRLOOP F4 SW 0.29 0.29 0.07 0.07
AIRLOOP F4 NW 0.31 0.31 0.07 0.07
AIRLOOP F4 SE 0.24 0.24 0.07 0.07
AIRLOOP F4 NE 0.25 0.25 0.07 0.07
AIRLOOP F4 N1 0.17 0.17 0.03 0.03
AIRLOOP F4 N2 0.17 0.17 0.03 0.03
AIRLOOP F4 S1 0.15 0.15 0.03 0.03
AIRLOOP F4 S2 0.15 0.15 0.03 0.03
AIRLOOP M SW 0.30 0.30 0.07 0.07
AIRLOOP M NW 0.31 0.31 0.07 0.07
AIRLOOP M SE 0.24 0.24 0.07 0.07
AIRLOOP M NE 0.25 0.25 0.07 0.07
AIRLOOP M N1 0.17 0.17 0.03 0.03
AIRLOOP M N2 0.17 0.17 0.03 0.03
AIRLOOP M S1 0.15 0.15 0.03 0.03
AIRLOOP M S2 0.15 0.15 0.03 0.03
AIRLOOP F6 SW 0.29 0.29 0.07 0.07
AIRLOOP F6 NW 0.31 0.31 0.07 0.07
AIRLOOP F6 SE 0.24 0.24 0.07 0.07
AIRLOOP F6 NE 0.25 0.25 0.07 0.07
AIRLOOP F6 N1 0.17 0.17 0.04 0.04
AIRLOOP F6 N2 0.17 0.17 0.04 0.04
AIRLOOP F6 S1 0.15 0.15 0.04 0.04
AIRLOOP F6 S2 0.15 0.15 0.04 0.04
AIRLOOP F7 SW 0.29 0.29 0.07 0.07
AIRLOOP F7 NW 0.31 0.31 0.07 0.07
AIRLOOP F7 SE 0.24 0.24 0.07 0.07
AIRLOOP F7 NE 0.25 0.25 0.07 0.07
AIRLOOP F7 N1 0.17 0.17 0.04 0.04
AIRLOOP F7 N2 0.17 0.17 0.04 0.04
AIRLOOP F7 S1 0.15 0.15 0.04 0.04
AIRLOOP F7 S2 0.15 0.15 0.04 0.04
AIRLOOP F8 SW 0.30 0.30 0.07 0.07
AIRLOOP F8 NW 0.31 0.31 0.08 0.08
AIRLOOP F8 SE 0.24 0.24 0.07 0.07
AIRLOOP F8 NE 0.25 0.25 0.07 0.07
AIRLOOP F8 N1 0.17 0.17 0.04 0.04
AIRLOOP F8 N2 0.17 0.17 0.04 0.04
AIRLOOP F8 S1 0.15 0.15 0.04 0.04
AIRLOOP F8 S2 0.15 0.15 0.04 0.04
AIRLOOP F9 SW 0.31 0.31 0.08 0.08
AIRLOOP F9 NW 0.32 0.32 0.08 0.08
AIRLOOP F9 SE 0.25 0.25 0.08 0.08
AIRLOOP F9 NE 0.25 0.25 0.08 0.08
AIRLOOP F9 N1 0.18 0.18 0.04 0.04
AIRLOOP F9 N2 0.18 0.18 0.04 0.04
AIRLOOP F9 S1 0.16 0.16 0.04 0.04
AIRLOOP F9 S2 0.16 0.16 0.04 0.04
AIRLOOP T SW 0.37 0.37 0.09 0.09
AIRLOOP T NW 0.38 0.38 0.09 0.09
AIRLOOP T SE 0.30 0.30 0.09 0.09
AIRLOOP T NE 0.31 0.31 0.09 0.09
AIRLOOP T N1 0.22 0.22 0.06 0.06
AIRLOOP T N2 0.22 0.22 0.06 0.06
AIRLOOP T S1 0.23 0.23 0.06 0.06
AIRLOOP T S2 0.23 0.23 0.06 0.06



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 7579.50 4298.25 3416.00
G NW APARTMENT 7257.25 4908.00 3716.50
OFFICE 2170.50 29.75 12.00
G NE APARTMENT 7263.25 4794.00 3568.25
G N1 APARTMENT 7204.50 5315.00 3991.75
G N2 APARTMENT 7204.50 5306.50 3982.25
G S1 APARTMENT 7523.25 4196.50 3295.25
G S2 APARTMENT 7548.75 4116.75 3236.75
F2 SW APARTMENT 7944.25 2338.00 1884.00
F2 NW APARTMENT 7537.25 3176.50 2274.50
F2 SE APARTMENT 8029.50 2030.50 1647.00
F2 NE APARTMENT 7531.00 3078.50 2163.75
F2 N1 APARTMENT 7453.00 3302.25 2338.00
F2 N2 APARTMENT 7452.25 3295.00 2330.50
F2 S1 APARTMENT 7989.75 2115.75 1724.25
F2 S2 APARTMENT 7998.00 2086.00 1703.00
F3 SW APARTMENT 7995.25 2387.50 1983.50
F3 NW APARTMENT 7602.00 3167.75 2314.00
F3 SE APARTMENT 8024.00 2235.25 1829.00
F3 NE APARTMENT 7597.50 3062.75 2190.25
F3 N1 APARTMENT 7540.50 3131.25 2252.50
F3 N2 APARTMENT 7539.50 3129.50 2248.25
F3 S1 APARTMENT 8076.75 2085.75 1779.00
F3 S2 APARTMENT 8078.00 2072.75 1768.00
F4 SW APARTMENT 7993.25 2450.00 2048.25
F4 NW APARTMENT 7611.25 3220.25 2372.00
F4 SE APARTMENT 8013.25 2339.00 1914.00
F4 NE APARTMENT 7607.25 3116.75 2246.25
F4 N1 APARTMENT 7565.25 3128.75 2272.00
F4 N2 APARTMENT 7565.75 3127.00 2269.00
F4 S1 APARTMENT 8088.00 2116.50 1821.50
F4 S2 APARTMENT 8089.50 2106.50 1810.00
M SW APARTMENT 7988.50 2489.75 2071.75
M NW APARTMENT 7615.50 3231.75 2378.75
M SE APARTMENT 8003.50 2384.25 1942.00
M NE APARTMENT 7607.25 3129.50 2256.25
M N1 APARTMENT 7576.50 3106.25 2261.50
M N2 APARTMENT 7575.50 3110.25 2259.00
M S1 APARTMENT 8084.00 2140.50 1840.00
M S2 APARTMENT 8082.00 2129.75 1827.00
F6 SW APARTMENT 7944.50 2679.00 2199.75
F6 NW APARTMENT 7568.75 3420.75 2518.00
F6 SE APARTMENT 7959.25 2554.50 2060.75
F6 NE APARTMENT 7566.75 3302.00 2389.25
F6 N1 APARTMENT 7529.25 3314.75 2405.25
F6 N2 APARTMENT 7529.00 3312.75 2400.75
F6 S1 APARTMENT 8028.75 2301.25 1941.00
F6 S2 APARTMENT 8025.50 2288.25 1926.25
F7 SW APARTMENT 7912.00 2791.75 2276.25
F7 NW APARTMENT 7541.00 3520.25 2592.75
F7 SE APARTMENT 7924.25 2666.00 2136.25
F7 NE APARTMENT 7537.50 3407.00 2470.75
F7 N1 APARTMENT 7500.25 3430.50 2486.75
F7 N2 APARTMENT 7500.25 3424.50 2479.50
F7 S1 APARTMENT 7992.00 2405.25 2010.50
F7 S2 APARTMENT 7990.50 2397.00 2000.25
F8 SW APARTMENT 7883.50 2879.50 2329.25
F8 NW APARTMENT 7519.75 3600.75 2648.00
F8 SE APARTMENT 7897.75 2764.00 2193.25
F8 NE APARTMENT 7505.50 3486.50 2527.00
F8 N1 APARTMENT 7479.50 3498.25 2528.50
F8 N2 APARTMENT 7479.25 3495.50 2525.25
F8 S1 APARTMENT 7962.00 2489.00 2062.75
F8 S2 APARTMENT 7963.00 2483.50 2053.25
F9 SW APARTMENT 7847.50 2941.50 2344.25
F9 NW APARTMENT 7501.00 3629.75 2659.25
F9 SE APARTMENT 7859.75 2830.25 2215.25
F9 NE APARTMENT 7486.50 3509.25 2528.25
F9 N1 APARTMENT 7464.25 3541.00 2548.00
F9 N2 APARTMENT 7461.00 3537.25 2542.75
F9 S1 APARTMENT 7924.00 2575.75 2101.50
F9 S2 APARTMENT 7920.50 2578.75 2101.25
T SW APARTMENT 7756.00 3638.25 2860.25
T NW APARTMENT 7531.75 4088.25 3069.00
T SE APARTMENT 7771.00 3584.50 2808.50
T NE APARTMENT 7514.50 4045.25 3010.00
T N1 APARTMENT 7493.25 3929.75 2894.25
T N2 APARTMENT 7491.25 3930.50 2892.50
T S1 APARTMENT 7806.00 3274.00 2591.00
T S2 APARTMENT 7806.25 3277.75 2593.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 8176.50 5638.75 4324.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 8.25 0.00 8.25
G NW APARTMENT 0.00 0.00 0.00 0.00
OFFICE 0.00 2.00 0.00 0.00
G NE APARTMENT 0.00 0.00 0.00 0.00
G N1 APARTMENT 0.75 1.75 0.75 1.75
G N2 APARTMENT 0.25 1.75 0.25 1.75
G S1 APARTMENT 0.00 503.50 0.00 503.50
G S2 APARTMENT 0.25 412.75 0.25 412.75
F2 SW APARTMENT 0.00 8.25 0.00 8.25
F2 NW APARTMENT 0.00 0.00 0.00 0.00
F2 SE APARTMENT 0.00 43.50 0.00 43.50
F2 NE APARTMENT 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 0.00 1.25 0.00 1.25
F2 N2 APARTMENT 0.00 1.50 0.00 1.50
F2 S1 APARTMENT 0.00 674.25 0.00 674.25
F2 S2 APARTMENT 0.00 629.00 0.00 629.00
F3 SW APARTMENT 0.00 16.75 0.00 16.75
F3 NW APARTMENT 0.00 0.25 0.00 0.25
F3 SE APARTMENT 0.00 149.25 0.00 149.25
F3 NE APARTMENT 0.00 1.50 0.00 1.50
F3 N1 APARTMENT 0.00 10.75 0.00 10.75
F3 N2 APARTMENT 0.00 11.50 0.00 11.50
F3 S1 APARTMENT 0.00 862.50 0.00 862.50
F3 S2 APARTMENT 0.00 822.25 0.00 822.25
F4 SW APARTMENT 0.00 16.25 0.00 16.25
F4 NW APARTMENT 0.00 0.00 0.00 0.00
F4 SE APARTMENT 0.00 153.25 0.00 153.25
F4 NE APARTMENT 0.00 2.00 0.00 2.00
F4 N1 APARTMENT 0.00 18.75 0.00 18.75
F4 N2 APARTMENT 0.00 21.00 0.00 21.00
F4 S1 APARTMENT 0.00 839.50 0.00 839.50
F4 S2 APARTMENT 0.00 804.25 0.00 804.25
M SW APARTMENT 0.00 17.25 0.00 17.25
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 145.75 0.00 145.75
M NE APARTMENT 0.00 2.50 0.00 2.50
M N1 APARTMENT 0.00 22.25 0.00 22.25
M N2 APARTMENT 0.00 23.50 0.00 23.50
M S1 APARTMENT 0.00 805.75 0.00 805.75
M S2 APARTMENT 0.25 769.25 0.25 769.25
F6 SW APARTMENT 0.00 17.25 0.00 17.25
F6 NW APARTMENT 0.00 0.00 0.00 0.00
F6 SE APARTMENT 0.00 141.00 0.00 141.00
F6 NE APARTMENT 0.00 2.75 0.00 2.75
F6 N1 APARTMENT 0.00 24.00 0.00 24.00
F6 N2 APARTMENT 0.00 24.75 0.00 24.75
F6 S1 APARTMENT 0.00 770.50 0.00 770.50
F6 S2 APARTMENT 0.00 736.00 0.00 736.00
F7 SW APARTMENT 0.00 16.75 0.00 16.75
F7 NW APARTMENT 0.00 0.00 0.00 0.00
F7 SE APARTMENT 0.00 133.75 0.00 133.75
F7 NE APARTMENT 0.00 3.00 0.00 3.00
F7 N1 APARTMENT 0.00 25.00 0.00 25.00
F7 N2 APARTMENT 0.00 26.00 0.00 26.00
F7 S1 APARTMENT 0.25 738.50 0.25 738.50
F7 S2 APARTMENT 0.25 706.00 0.25 706.00
F8 SW APARTMENT 0.00 16.00 0.00 16.00
F8 NW APARTMENT 0.00 0.00 0.00 0.00
F8 SE APARTMENT 0.00 126.00 0.00 126.00
F8 NE APARTMENT 0.00 3.25 0.00 3.25
F8 N1 APARTMENT 0.00 25.50 0.00 25.50
F8 N2 APARTMENT 0.00 27.00 0.00 27.00
F8 S1 APARTMENT 0.00 700.00 0.00 700.00
F8 S2 APARTMENT 0.00 675.50 0.00 675.50
F9 SW APARTMENT 0.00 12.25 0.00 12.25
F9 NW APARTMENT 0.00 0.75 0.00 0.75
F9 SE APARTMENT 0.00 118.50 0.00 118.50
F9 NE APARTMENT 0.00 3.00 0.00 3.00
F9 N1 APARTMENT 0.00 24.00 0.00 24.00
F9 N2 APARTMENT 0.00 25.00 0.00 25.00
F9 S1 APARTMENT 0.00 597.50 0.00 597.50
F9 S2 APARTMENT 0.00 618.50 0.00 618.50
T SW APARTMENT 0.00 13.25 0.00 13.25
T NW APARTMENT 0.00 3.00 0.00 3.00
T SE APARTMENT 0.00 91.50 0.00 91.50
T NE APARTMENT 0.00 2.25 0.00 2.25
T N1 APARTMENT 0.00 9.75 0.00 9.75
T N2 APARTMENT 0.00 10.25 0.00 10.25
T S1 APARTMENT 0.00 276.25 0.00 276.25
T S2 APARTMENT 0.00 278.00 0.00 278.00
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 1.50 982.25 1.50 980.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.357 0.178 0.000 0.411
G NW APARTMENT 1.71 2.50 268.96 0.357 0.178 0.000 0.397
OFFICE 0.94 1.00 268.96 0.522 0.214 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.357 0.178 0.000 0.397
G N1 APARTMENT 1.71 2.50 268.96 0.357 0.107 0.000 0.392
G N2 APARTMENT 1.71 2.50 268.97 0.357 0.107 0.000 0.392
G S1 APARTMENT 1.71 2.50 268.96 0.357 0.107 0.000 0.408
G S2 APARTMENT 1.71 2.50 268.97 0.357 0.107 0.000 0.409
F2 SW APARTMENT 1.71 2.50 268.96 0.356 0.256 0.000 0.501
F2 NW APARTMENT 1.71 2.50 268.96 0.357 0.256 0.000 0.486
F2 SE APARTMENT 1.71 2.50 268.96 0.356 0.256 0.000 0.502
F2 NE APARTMENT 1.71 2.50 268.96 0.356 0.256 0.000 0.486
F2 N1 APARTMENT 1.71 2.50 268.96 0.357 0.154 0.000 0.483
F2 N2 APARTMENT 1.71 2.50 268.97 0.357 0.154 0.000 0.483
F2 S1 APARTMENT 1.71 2.50 268.96 0.357 0.155 0.000 0.499
F2 S2 APARTMENT 1.71 2.50 268.97 0.356 0.155 0.000 0.499
F3 SW APARTMENT 1.71 2.50 268.96 0.357 0.303 0.000 0.597
F3 NW APARTMENT 1.71 2.50 268.96 0.357 0.303 0.000 0.579
F3 SE APARTMENT 1.71 2.50 268.96 0.356 0.303 0.000 0.597
F3 NE APARTMENT 1.71 2.50 268.96 0.356 0.303 0.000 0.579
F3 N1 APARTMENT 1.71 2.50 268.96 0.357 0.183 0.000 0.577
F3 N2 APARTMENT 1.71 2.50 268.97 0.357 0.183 0.000 0.577
F3 S1 APARTMENT 1.71 2.50 268.96 0.357 0.183 0.000 0.593
F3 S2 APARTMENT 1.71 2.50 268.97 0.357 0.183 0.000 0.593
F4 SW APARTMENT 1.71 2.50 268.96 0.357 0.339 0.000 0.639
F4 NW APARTMENT 1.71 2.50 268.96 0.357 0.339 0.000 0.621
F4 SE APARTMENT 1.71 2.50 268.96 0.356 0.339 0.000 0.639
F4 NE APARTMENT 1.71 2.50 268.96 0.356 0.339 0.000 0.620
F4 N1 APARTMENT 1.71 2.50 268.96 0.357 0.204 0.000 0.619
F4 N2 APARTMENT 1.71 2.50 268.97 0.357 0.204 0.000 0.619
F4 S1 APARTMENT 1.71 2.50 268.96 0.357 0.204 0.000 0.636
F4 S2 APARTMENT 1.71 2.50 268.97 0.357 0.204 0.000 0.636
M SW APARTMENT 1.71 2.50 268.96 0.357 0.368 0.000 0.678
M NW APARTMENT 1.71 2.50 268.96 0.357 0.368 0.000 0.658
M SE APARTMENT 1.71 2.50 268.96 0.356 0.368 0.000 0.678
M NE APARTMENT 1.71 2.50 268.96 0.356 0.368 0.000 0.658
M N1 APARTMENT 1.71 2.50 268.96 0.357 0.222 0.000 0.656
M N2 APARTMENT 1.71 2.50 268.97 0.357 0.222 0.000 0.656
M S1 APARTMENT 1.71 2.50 268.96 0.357 0.222 0.000 0.675
M S2 APARTMENT 1.71 2.50 268.97 0.357 0.222 0.000 0.675
F6 SW APARTMENT 1.71 2.50 268.96 0.357 0.393 0.000 0.711
F6 NW APARTMENT 1.71 2.50 268.96 0.357 0.393 0.000 0.690
F6 SE APARTMENT 1.71 2.50 268.96 0.357 0.393 0.000 0.711
F6 NE APARTMENT 1.71 2.50 268.96 0.357 0.393 0.000 0.689
F6 N1 APARTMENT 1.71 2.50 268.96 0.357 0.237 0.000 0.688
F6 N2 APARTMENT 1.71 2.50 268.97 0.357 0.237 0.000 0.688
F6 S1 APARTMENT 1.71 2.50 268.96 0.357 0.237 0.000 0.708
F6 S2 APARTMENT 1.71 2.50 268.97 0.357 0.237 0.000 0.708
F7 SW APARTMENT 1.71 2.50 268.96 0.357 0.416 0.000 0.740
F7 NW APARTMENT 1.71 2.50 268.96 0.357 0.416 0.000 0.718
F7 SE APARTMENT 1.71 2.50 268.96 0.357 0.416 0.000 0.740
F7 NE APARTMENT 1.71 2.50 268.96 0.357 0.416 0.000 0.718
F7 N1 APARTMENT 1.71 2.50 268.96 0.357 0.251 0.000 0.716
F7 N2 APARTMENT 1.71 2.50 268.97 0.357 0.251 0.000 0.716
F7 S1 APARTMENT 1.71 2.50 268.96 0.357 0.251 0.000 0.738
F7 S2 APARTMENT 1.71 2.50 268.97 0.357 0.251 0.000 0.738
F8 SW APARTMENT 1.71 2.50 268.96 0.357 0.436 0.000 0.769
F8 NW APARTMENT 1.71 2.50 268.96 0.357 0.436 0.000 0.746
F8 SE APARTMENT 1.71 2.50 268.96 0.357 0.436 0.000 0.768
F8 NE APARTMENT 1.71 2.50 268.96 0.357 0.436 0.000 0.745
F8 N1 APARTMENT 1.71 2.50 268.96 0.357 0.263 0.000 0.744
F8 N2 APARTMENT 1.71 2.50 268.97 0.357 0.263 0.000 0.744
F8 S1 APARTMENT 1.71 2.50 268.96 0.357 0.263 0.000 0.766
F8 S2 APARTMENT 1.71 2.50 268.97 0.357 0.263 0.000 0.766
F9 SW APARTMENT 1.71 2.50 268.96 0.357 0.454 0.000 0.801
F9 NW APARTMENT 1.71 2.50 268.96 0.357 0.454 0.000 0.777
F9 SE APARTMENT 1.71 2.50 268.96 0.357 0.454 0.000 0.801
F9 NE APARTMENT 1.71 2.50 268.96 0.356 0.454 0.000 0.776
F9 N1 APARTMENT 1.71 2.50 268.96 0.357 0.274 0.000 0.775
F9 N2 APARTMENT 1.71 2.50 268.97 0.357 0.274 0.000 0.775
F9 S1 APARTMENT 1.71 2.50 268.96 0.357 0.274 0.000 0.800
F9 S2 APARTMENT 1.71 2.50 268.97 0.357 0.274 0.000 0.799
T SW APARTMENT 1.71 2.50 268.96 0.357 0.471 0.000 0.823
T NW APARTMENT 1.71 2.50 268.96 0.357 0.471 0.000 0.799
T SE APARTMENT 1.71 2.50 268.96 0.357 0.471 0.000 0.823
T NE APARTMENT 1.71 2.50 268.96 0.357 0.471 0.000 0.799
T N1 APARTMENT 1.71 2.50 268.96 0.357 0.284 0.000 0.797
T N2 APARTMENT 1.71 2.50 268.97 0.357 0.284 0.000 0.797
T S1 APARTMENT 1.71 2.50 268.96 0.357 0.284 0.000 0.822
T S2 APARTMENT 1.71 2.50 268.97 0.357 0.284 0.000 0.823
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.508 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.345 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4156
Defaulted Fields 814
Fields with Defaults 11184
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
Electricity:Building 1433.88 25760.85 01-JAN-03:15 70162.48 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 296.56 6715.87 01-JAN-00:15 14401.37 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 242.55 5824.91 01-JAN-00:15 11484.27 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 39.38 663.42 01-JAN-00:15 2934.49 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 29.88 469.18 01-JAN-00:15 2345.88 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T CORRIDOR 179.47 1701.70 01-JAN-00:15 10868.20 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 54.01 890.97 01-JAN-00:15 2917.11 01-JAN-19:15
InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.50 194.24 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 163.03 1180.40 01-JAN-00:15 10346.90 01-JAN-07:15
Fans:Electricity 650.69 20633.29 08-APR-07:30 20633.29 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 2120.12 21294.53 17-JAN-03:15 113767.42 27-JUL-16:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
ElectricityPurchased:Plant 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
Cogeneration:ElectricityPurchased 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
ElectricityNet:Plant 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
Cogeneration:ElectricityNet 3870.55 57456.31 17-JAN-03:15 190419.01 29-NOV-18:30
ExteriorLights:Electricity 163.14 0.00 01-JAN-07:15 10364.00 01-JAN-00:15
General:ExteriorLights:Electricity 163.14 0.00 01-JAN-07:15 10364.00 01-JAN-00:15
General:Fans:Electricity 650.69 20633.29 08-APR-07:30 20633.29 01-JAN-00:15
Cooling:Electricity 1430.98 0.00 01-JAN-06:15 91138.94 27-JUL-16:15
Heating:Electricity 2.28 0.00 01-JAN-00:15 23370.41 04-FEB-06:00
Electricity:Plant 153.40 36.93 01-JAN-06:15 6426.61 08-JUN-16:15
HeatRejection:Electricity 73.72 0.00 01-JAN-06:15 3845.68 08-JUN-16:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 79.68 36.93 01-JAN-06:15 2580.93 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.44 0.00 01-JAN-00:15 21.60 01-JAN-19:30
WIRED_INT_EQUIP 979.40 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 813.86 2357.00 01-JAN-00:15 143064.75 04-FEB-07:15
Gas:Plant 813.86 2357.00 01-JAN-00:15 143064.75 04-FEB-07:15
WaterSystems:Gas 811.17 2357.00 01-JAN-00:15 70351.58 18-JAN-08:00
Water Heater:WaterSystems:Gas 811.17 2357.00 01-JAN-00:15 70351.58 18-JAN-08:00
Heating:Gas 2.69 0.00 01-JAN-00:15 81475.49 04-FEB-06:00
Boiler:Heating:Gas 2.69 0.00 01-JAN-00:15 81475.49 04-FEB-06:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 6512.96 0.00 01-JAN-06:15 454062.42 29-NOV-11:45
PlantLoopCoolingDemand:HVAC 6512.96 0.00 01-JAN-06:15 454062.42 29-NOV-11:45
CoolingCoils:PlantLoopCoolingDemand 6512.96 0.00 01-JAN-06:15 454062.42 29-NOV-11:45


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 8410.01 0.00 09-JAN-02:15 0.00 27-JUL-17:15
Water:Plant 8410.01 0.00 09-JAN-02:15 0.00 27-JUL-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 8410.01 0.00 09-JAN-02:15 0.00 27-JUL-17:15
MainsWater:Plant 8410.01 0.00 09-JAN-02:15 0.00 27-JUL-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 3631.50 0.00 01-JAN-06:15 0.00 27-JUL-16:30
HeatRejection:MainsWater 3631.50 0.00 01-JAN-06:15 0.00 27-JUL-16:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 631.85 332.83 23-JUL-01:15 101226.98 04-FEB-06:15
PlantLoopHeatingDemand:Plant 626.05 332.83 23-JUL-01:15 41392.23 19-JAN-07:45
WaterSystems:PlantLoopHeatingDemand 626.05 332.83 23-JUL-01:15 41392.23 19-JAN-07:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 8344.44 5920.01 28-DEC-04:00 569828.07 27-JUL-16:15
EnergyTransfer:Building 2540.13 4132.33 21-DEC-22:15 209377.86 29-JUL-16:30
EnergyTransfer:Zone:G SW APARTMENT 25.08 0.01 11-JAN-05:30 3006.31 30-SEP-14:30
Heating:EnergyTransfer 35.62 0.00 01-JAN-09:45 69502.74 05-FEB-09:30
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.58 0.00 01-JAN-00:15 796.06 04-FEB-05:00
Cooling:EnergyTransfer 2504.51 0.00 01-JAN-06:15 209377.86 29-JUL-16:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 24.51 0.00 01-JAN-01:15 3006.31 30-SEP-14:30
EnergyTransfer:Zone:G NW APARTMENT 20.85 0.04 05-JAN-23:00 2929.87 29-JUL-16:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.05 0.00 01-JAN-09:45 1109.32 05-FEB-09:30
Cooling:EnergyTransfer:Zone:G NW APARTMENT 19.80 0.00 01-JAN-00:15 2929.87 29-JUL-16:30
EnergyTransfer:Zone:OFFICE 35.89 0.02 23-FEB-06:00 4140.60 29-SEP-12:30
Heating:EnergyTransfer:Zone:OFFICE 0.22 0.00 01-JAN-00:15 782.32 04-FEB-07:00
Cooling:EnergyTransfer:Zone:OFFICE 35.67 0.00 01-JAN-02:15 4140.60 29-SEP-12:30
EnergyTransfer:Zone:G NE APARTMENT 20.80 0.06 10-JAN-00:30 2298.17 25-JUL-10:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 0.76 0.00 01-JAN-00:15 945.22 04-FEB-05:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 20.04 0.00 01-JAN-00:30 2298.17 25-JUL-10:15
EnergyTransfer:Zone:G N1 APARTMENT 14.31 0.01 02-NOV-00:45 1608.51 29-JUL-16:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.41 0.00 01-JAN-00:15 948.26 05-FEB-09:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 13.90 0.00 01-JAN-00:30 1608.51 29-JUL-16:30
EnergyTransfer:Zone:G N2 APARTMENT 14.32 0.00 27-FEB-23:45 1595.16 29-JUL-16:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.40 0.00 01-JAN-00:15 936.78 05-FEB-09:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 13.92 0.00 01-JAN-00:30 1595.16 29-JUL-16:30
EnergyTransfer:Zone:G S1 APARTMENT 18.67 0.00 11-MAR-20:30 1903.65 27-FEB-13:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.07 0.00 01-JAN-00:15 326.83 19-DEC-09:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 18.60 0.00 01-JAN-06:15 1903.65 27-FEB-13:15
EnergyTransfer:Zone:G S2 APARTMENT 19.21 0.03 06-DEC-04:15 1951.84 27-FEB-13:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.07 0.00 01-JAN-00:15 308.64 12-NOV-09:45
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 19.14 0.00 01-JAN-06:15 1951.84 27-FEB-13:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 38.24 0.07 20-MAR-10:30 3932.72 07-NOV-15:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 0.34 0.00 01-JAN-00:15 714.87 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 37.89 0.00 01-JAN-06:15 3932.72 07-NOV-15:15
EnergyTransfer:Zone:F2 NW APARTMENT 31.47 0.04 15-JAN-01:45 3472.95 29-JUL-16:30
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 0.77 0.00 01-JAN-00:15 1240.34 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 30.70 0.00 01-JAN-06:15 3472.95 29-JUL-16:30
EnergyTransfer:Zone:F2 SE APARTMENT 40.71 0.06 23-FEB-07:00 3518.27 07-NOV-14:30
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.23 0.00 01-JAN-00:15 660.48 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 40.48 0.00 01-JAN-06:15 3518.27 07-NOV-14:30
EnergyTransfer:Zone:F2 NE APARTMENT 31.53 0.07 01-MAR-03:00 2818.65 29-JUL-16:30
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 0.51 0.00 01-JAN-00:15 997.93 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 31.02 0.00 01-JAN-06:15 2818.65 29-JUL-16:30
EnergyTransfer:Zone:F2 N1 APARTMENT 23.37 0.01 18-DEC-01:45 2020.12 29-JUL-16:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 0.23 0.00 01-JAN-00:15 973.33 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 23.14 0.00 01-JAN-06:15 2020.12 29-JUL-16:30
EnergyTransfer:Zone:F2 N2 APARTMENT 23.38 0.03 12-FEB-07:00 2009.61 29-JUL-16:30
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 0.22 0.00 01-JAN-00:15 966.24 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 23.16 0.00 01-JAN-06:15 2009.61 29-JUL-16:30
EnergyTransfer:Zone:F2 S1 APARTMENT 30.06 0.01 27-DEC-19:00 2539.70 22-FEB-14:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.03 0.00 01-JAN-00:15 98.24 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 30.03 0.00 01-JAN-06:15 2539.70 22-FEB-14:00
EnergyTransfer:Zone:F2 S2 APARTMENT 30.26 0.04 26-DEC-10:30 2568.32 22-FEB-14:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.03 0.00 01-JAN-00:15 100.26 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 30.23 0.00 01-JAN-06:15 2568.32 22-FEB-14:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 39.89 0.06 10-APR-05:15 3988.53 07-NOV-15:15
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.33 0.00 01-JAN-00:15 757.33 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 39.56 0.00 01-JAN-06:15 3988.53 07-NOV-15:15
EnergyTransfer:Zone:F3 NW APARTMENT 33.28 0.08 21-DEC-02:00 3487.07 29-JUL-16:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 0.74 0.00 01-JAN-00:15 1410.71 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 32.54 0.00 01-JAN-06:15 3487.07 29-JUL-16:30
EnergyTransfer:Zone:F3 SE APARTMENT 40.30 0.01 15-MAR-00:15 3364.39 07-NOV-15:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.21 0.00 01-JAN-00:15 792.57 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 40.09 0.00 01-JAN-06:15 3364.39 07-NOV-15:00
EnergyTransfer:Zone:F3 NE APARTMENT 33.33 0.02 26-FEB-06:00 2848.50 29-JUL-16:30
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 0.49 0.00 01-JAN-00:15 1071.59 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 32.84 0.00 01-JAN-06:15 2848.50 29-JUL-16:30
EnergyTransfer:Zone:F3 N1 APARTMENT 25.40 0.01 19-DEC-09:45 2061.68 29-JUL-16:30
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 0.21 0.00 01-JAN-00:15 1118.63 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 25.19 0.00 01-JAN-06:15 2061.68 29-JUL-16:30
EnergyTransfer:Zone:F3 N2 APARTMENT 25.41 0.04 18-DEC-03:15 2051.17 29-JUL-16:30
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 0.21 0.00 01-JAN-00:15 1114.35 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 25.20 0.00 01-JAN-06:15 2051.17 29-JUL-16:30
EnergyTransfer:Zone:F3 S1 APARTMENT 31.89 0.05 17-DEC-21:00 2637.42 21-FEB-14:45
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.03 0.00 01-JAN-00:15 101.62 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 31.86 0.00 01-JAN-06:15 2637.42 21-FEB-14:45
EnergyTransfer:Zone:F3 S2 APARTMENT 31.98 0.09 19-DEC-19:45 2636.10 21-FEB-14:45
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.03 0.00 01-JAN-00:15 101.17 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 31.95 0.00 01-JAN-06:15 2636.10 21-FEB-14:45
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 40.05 0.02 23-JAN-02:45 3992.31 07-NOV-15:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 0.36 0.00 01-JAN-00:15 863.76 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 39.69 0.00 01-JAN-06:15 3992.31 07-NOV-15:00
EnergyTransfer:Zone:F4 NW APARTMENT 33.64 0.01 27-NOV-00:15 3502.25 29-JUL-16:30
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 0.78 0.00 01-JAN-00:15 1582.34 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 32.86 0.00 01-JAN-06:15 3502.25 29-JUL-16:30
EnergyTransfer:Zone:F4 SE APARTMENT 40.21 0.01 27-NOV-10:45 3376.49 07-NOV-15:00
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.23 0.00 01-JAN-00:15 920.71 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 39.98 0.00 01-JAN-06:15 3376.49 07-NOV-15:00
EnergyTransfer:Zone:F4 NE APARTMENT 33.67 0.01 02-MAR-04:45 2875.16 29-JUL-16:30
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 0.52 0.00 01-JAN-00:15 1170.42 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 33.14 0.00 01-JAN-06:15 2875.16 29-JUL-16:30
EnergyTransfer:Zone:F4 N1 APARTMENT 25.85 0.01 05-JAN-07:45 2084.05 29-JUL-16:30
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 0.22 0.00 01-JAN-00:15 1281.70 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 25.62 0.00 01-JAN-06:15 2084.05 29-JUL-16:30
EnergyTransfer:Zone:F4 N2 APARTMENT 25.86 0.01 21-MAR-23:00 2078.44 29-JUL-16:30
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 0.22 0.00 01-JAN-00:15 1277.88 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 25.64 0.00 01-JAN-06:15 2078.44 29-JUL-16:30
EnergyTransfer:Zone:F4 S1 APARTMENT 32.21 0.12 16-JAN-19:30 2688.99 21-FEB-14:45
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.04 0.00 01-JAN-00:15 111.57 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 32.17 0.00 01-JAN-06:15 2688.99 21-FEB-14:45
EnergyTransfer:Zone:F4 S2 APARTMENT 32.26 0.05 18-APR-06:45 2705.63 21-FEB-14:45
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.04 0.00 01-JAN-00:15 111.33 18-MAR-05:15
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 32.23 0.00 01-JAN-06:15 2705.63 21-FEB-14:45
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 40.54 0.01 22-FEB-04:15 4001.92 07-NOV-15:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.39 0.00 01-JAN-00:15 959.74 04-FEB-06:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 40.15 0.00 01-JAN-06:15 4001.92 07-NOV-15:00
EnergyTransfer:Zone:M NW APARTMENT 34.31 0.05 21-DEC-00:15 3536.81 29-JUL-16:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.83 0.00 01-JAN-00:15 1711.87 05-FEB-09:30
Cooling:EnergyTransfer:Zone:M NW APARTMENT 33.48 0.00 01-JAN-06:15 3536.81 29-JUL-16:30
EnergyTransfer:Zone:M SE APARTMENT 40.66 0.04 17-JAN-00:45 3416.81 07-NOV-14:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.26 0.00 01-JAN-00:15 1021.88 04-FEB-05:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 40.40 0.00 01-JAN-06:15 3416.81 07-NOV-14:45
EnergyTransfer:Zone:M NE APARTMENT 34.31 0.04 18-JAN-03:45 2918.72 29-JUL-16:30
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.56 0.00 01-JAN-00:15 1277.76 04-FEB-19:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 33.74 0.00 01-JAN-06:15 2918.72 29-JUL-16:30
EnergyTransfer:Zone:M N1 APARTMENT 26.54 0.01 18-DEC-02:15 2121.46 29-JUL-16:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.25 0.00 01-JAN-00:15 1407.10 05-FEB-09:30
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 26.30 0.00 01-JAN-06:15 2121.46 29-JUL-16:30
EnergyTransfer:Zone:M N2 APARTMENT 26.55 0.02 12-FEB-07:00 2115.94 29-JUL-16:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.24 0.00 01-JAN-00:15 1404.11 05-FEB-09:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 26.31 0.00 01-JAN-06:15 2115.94 29-JUL-16:30
EnergyTransfer:Zone:M S1 APARTMENT 32.78 0.01 05-FEB-23:30 2748.88 21-FEB-14:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.05 0.00 01-JAN-00:15 123.68 18-MAR-05:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 32.73 0.00 01-JAN-06:15 2748.88 21-FEB-14:45
EnergyTransfer:Zone:M S2 APARTMENT 32.83 0.01 16-MAR-14:15 2740.62 21-FEB-14:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.05 0.00 01-JAN-00:15 211.04 04-FEB-06:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 32.78 0.00 01-JAN-06:15 2740.62 21-FEB-14:45
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 39.59 0.05 02-MAR-05:30 3952.83 07-NOV-15:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 0.45 0.00 01-JAN-00:15 1101.27 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 39.14 0.00 01-JAN-06:15 3952.83 07-NOV-15:00
EnergyTransfer:Zone:F6 NW APARTMENT 33.59 0.08 01-MAR-20:15 3511.32 29-JUL-16:30
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 0.92 0.00 01-JAN-00:15 1870.23 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 32.67 0.00 01-JAN-06:15 3511.32 29-JUL-16:30
EnergyTransfer:Zone:F6 SE APARTMENT 39.66 0.05 16-JAN-06:00 3396.13 07-NOV-14:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 0.30 0.00 01-JAN-00:15 1159.64 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 39.36 0.00 01-JAN-06:15 3396.13 07-NOV-14:45
EnergyTransfer:Zone:F6 NE APARTMENT 33.55 0.01 10-JAN-03:15 2902.19 29-JUL-16:30
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 0.64 0.00 01-JAN-00:15 1434.65 04-FEB-19:15
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 32.91 0.00 01-JAN-06:15 2902.19 29-JUL-16:30
EnergyTransfer:Zone:F6 N1 APARTMENT 25.81 0.10 01-FEB-01:00 2100.11 29-JUL-16:30
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 0.29 0.00 01-JAN-00:15 1586.67 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 25.52 0.00 01-JAN-06:15 2100.11 29-JUL-16:30
EnergyTransfer:Zone:F6 N2 APARTMENT 25.82 0.11 01-FEB-10:45 2094.70 29-JUL-16:30
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 0.28 0.00 01-JAN-00:15 1583.40 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 25.54 0.00 01-JAN-06:15 2094.70 29-JUL-16:30
EnergyTransfer:Zone:F6 S1 APARTMENT 31.82 0.09 16-MAR-20:30 2704.01 22-FEB-14:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.06 0.00 01-JAN-00:15 210.93 04-FEB-04:30
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 31.76 0.00 01-JAN-06:15 2704.01 22-FEB-14:00
EnergyTransfer:Zone:F6 S2 APARTMENT 31.87 0.07 16-JAN-20:30 2716.53 22-FEB-14:15
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.06 0.00 01-JAN-00:15 180.39 12-NOV-09:45
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 31.81 0.00 01-JAN-06:15 2716.53 22-FEB-14:15
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 39.17 0.01 23-FEB-03:00 3926.38 07-NOV-15:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 0.50 0.00 01-JAN-00:15 1213.97 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 38.67 0.00 01-JAN-06:15 3926.38 07-NOV-15:00
EnergyTransfer:Zone:F7 NW APARTMENT 33.37 0.24 16-NOV-07:00 3507.31 29-JUL-16:30
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 1.00 0.00 01-JAN-00:15 1998.72 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 32.37 0.00 01-JAN-06:15 3507.31 29-JUL-16:30
EnergyTransfer:Zone:F7 SE APARTMENT 39.21 0.08 22-JAN-02:00 3389.47 07-NOV-14:30
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 0.34 0.00 01-JAN-00:15 1264.17 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 38.88 0.00 01-JAN-06:15 3389.47 07-NOV-14:30
EnergyTransfer:Zone:F7 NE APARTMENT 33.31 0.06 09-JAN-01:30 2905.65 29-JUL-16:30
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 0.71 0.00 01-JAN-00:15 1560.31 04-FEB-19:15
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 32.59 0.00 01-JAN-06:15 2905.65 29-JUL-16:30
EnergyTransfer:Zone:F7 N1 APARTMENT 25.57 0.04 01-FEB-00:45 2099.02 29-JUL-16:30
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 0.33 0.00 01-JAN-00:15 1711.12 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 25.25 0.00 01-JAN-06:15 2099.02 29-JUL-16:30
EnergyTransfer:Zone:F7 N2 APARTMENT 25.58 0.04 17-DEC-24:00 2093.70 29-JUL-16:30
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 0.32 0.00 01-JAN-00:15 1708.04 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 25.26 0.00 01-JAN-06:15 2093.70 29-JUL-16:30
EnergyTransfer:Zone:F7 S1 APARTMENT 31.40 0.02 27-DEC-21:45 2684.31 22-FEB-16:30
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.07 0.00 01-JAN-00:15 237.43 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 31.33 0.00 01-JAN-06:15 2684.31 22-FEB-16:30
EnergyTransfer:Zone:F7 S2 APARTMENT 31.45 0.04 20-JAN-13:00 2684.69 22-FEB-14:15
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.07 0.00 01-JAN-00:15 243.13 04-FEB-06:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 31.38 0.00 01-JAN-06:15 2684.69 22-FEB-14:15
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 39.05 0.03 26-JAN-03:30 3910.06 07-NOV-15:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 0.55 0.00 01-JAN-00:15 1309.17 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 38.50 0.00 01-JAN-06:15 3910.06 07-NOV-15:00
EnergyTransfer:Zone:F8 NW APARTMENT 33.42 0.06 20-DEC-20:30 3516.06 29-JUL-16:30
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 1.08 0.00 01-JAN-00:15 2115.71 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 32.33 0.00 01-JAN-06:15 3516.06 29-JUL-16:30
EnergyTransfer:Zone:F8 SE APARTMENT 39.06 0.05 30-JAN-16:15 3402.90 07-NOV-14:30
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 0.37 0.00 01-JAN-00:15 1348.78 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 38.68 0.00 01-JAN-06:15 3402.90 07-NOV-14:30
EnergyTransfer:Zone:F8 NE APARTMENT 33.32 0.06 26-JAN-00:30 2920.97 29-JUL-16:30
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 0.78 0.00 01-JAN-00:15 1672.87 04-FEB-19:15
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 32.54 0.00 01-JAN-06:15 2920.97 29-JUL-16:30
EnergyTransfer:Zone:F8 N1 APARTMENT 25.60 0.08 25-DEC-07:00 2110.21 29-JUL-16:30
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 0.37 0.00 01-JAN-00:15 1827.02 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 25.24 0.00 01-JAN-06:15 2110.21 29-JUL-16:30
EnergyTransfer:Zone:F8 N2 APARTMENT 25.61 0.20 19-DEC-03:00 2104.98 29-JUL-16:30
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 0.36 0.00 01-JAN-00:15 1822.90 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 25.25 0.00 01-JAN-06:15 2104.98 29-JUL-16:30
EnergyTransfer:Zone:F8 S1 APARTMENT 31.27 0.01 01-FEB-02:30 2748.62 22-FEB-12:45
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.08 0.00 01-JAN-00:15 341.54 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 31.19 0.00 01-JAN-06:15 2748.62 22-FEB-12:45
EnergyTransfer:Zone:F8 S2 APARTMENT 31.32 0.01 25-DEC-08:00 2764.28 22-FEB-12:45
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.08 0.00 01-JAN-00:15 342.20 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 31.24 0.00 01-JAN-06:15 2764.28 22-FEB-12:45
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 39.84 0.15 21-MAR-12:30 3959.21 07-NOV-15:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 0.64 0.00 01-JAN-00:15 1434.52 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 39.21 0.00 01-JAN-06:15 3959.21 07-NOV-15:00
EnergyTransfer:Zone:F9 NW APARTMENT 34.36 0.16 27-NOV-03:15 3620.48 29-JUL-16:30
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 1.22 0.00 01-JAN-00:15 2257.48 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 33.14 0.00 01-JAN-06:15 3620.48 29-JUL-16:30
EnergyTransfer:Zone:F9 SE APARTMENT 39.80 0.01 31-JAN-02:30 3467.84 07-NOV-14:30
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 0.43 0.00 01-JAN-00:15 1476.34 04-FEB-05:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 39.37 0.00 01-JAN-06:15 3467.84 07-NOV-14:30
EnergyTransfer:Zone:F9 NE APARTMENT 34.21 0.00 09-JAN-03:15 3029.51 29-JUL-16:30
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 0.88 0.00 01-JAN-00:15 1774.66 03-FEB-16:30
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 33.33 0.00 01-JAN-06:15 3029.51 29-JUL-16:30
EnergyTransfer:Zone:F9 N1 APARTMENT 26.45 0.15 18-APR-13:00 2203.49 29-JUL-16:30
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 0.44 0.00 01-JAN-00:15 1953.02 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 26.01 0.00 01-JAN-06:15 2203.49 29-JUL-16:30
EnergyTransfer:Zone:F9 N2 APARTMENT 26.45 0.17 31-DEC-02:45 2198.52 29-JUL-16:30
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 0.44 0.00 01-JAN-00:15 1949.28 05-FEB-09:30
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 26.02 0.00 01-JAN-06:15 2198.52 29-JUL-16:30
EnergyTransfer:Zone:F9 S1 APARTMENT 32.04 0.00 22-JAN-20:30 2712.02 22-FEB-12:45
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.11 0.00 01-JAN-00:15 503.26 12-NOV-10:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 31.93 0.00 01-JAN-06:15 2712.02 22-FEB-12:45
EnergyTransfer:Zone:F9 S2 APARTMENT 32.03 0.01 21-JAN-12:00 2722.77 22-FEB-12:45
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.11 0.00 01-JAN-00:15 500.85 12-NOV-10:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 31.92 0.00 01-JAN-06:15 2722.77 22-FEB-12:45
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 42.07 0.17 01-NOV-03:30 4730.24 07-NOV-15:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.32 0.00 01-JAN-00:15 2101.27 04-FEB-05:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 40.75 0.00 01-JAN-04:00 4730.24 07-NOV-15:00
EnergyTransfer:Zone:T NW APARTMENT 36.91 0.12 10-MAR-07:00 4358.60 29-JUL-16:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 1.92 0.00 01-JAN-00:15 2359.25 05-FEB-09:30
Cooling:EnergyTransfer:Zone:T NW APARTMENT 35.00 0.00 01-JAN-02:30 4358.60 29-JUL-16:30
EnergyTransfer:Zone:T SE APARTMENT 41.85 0.44 22-MAR-06:45 4171.02 07-NOV-14:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.05 0.00 01-JAN-00:15 2131.09 04-FEB-05:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 40.80 0.00 01-JAN-05:00 4171.02 07-NOV-14:15
EnergyTransfer:Zone:T NE APARTMENT 36.59 0.41 07-NOV-05:15 3629.33 29-JUL-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 1.54 0.00 01-JAN-00:15 2274.88 04-FEB-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 35.05 0.00 01-JAN-02:30 3629.33 29-JUL-16:15
EnergyTransfer:Zone:T N1 APARTMENT 28.80 0.00 21-JAN-04:30 2798.27 29-JUL-16:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.77 0.00 01-JAN-00:15 2078.76 05-FEB-09:30
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 28.04 0.00 01-JAN-06:15 2798.27 29-JUL-16:30
EnergyTransfer:Zone:T N2 APARTMENT 28.81 0.01 11-JAN-04:30 2774.50 29-JUL-16:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.76 0.00 01-JAN-00:15 2066.69 05-FEB-09:30
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 28.05 0.00 01-JAN-06:15 2774.50 29-JUL-16:30
EnergyTransfer:Zone:T S1 APARTMENT 34.27 0.00 20-MAR-23:45 3478.41 22-FEB-12:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.39 0.00 01-JAN-00:15 1108.91 04-FEB-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 33.88 0.00 01-JAN-06:15 3478.41 22-FEB-12:45
EnergyTransfer:Zone:T S2 APARTMENT 34.30 0.04 18-JAN-02:45 3496.32 22-FEB-12:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.39 0.00 01-JAN-00:15 1112.15 04-FEB-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 33.91 0.00 01-JAN-06:15 3496.32 22-FEB-12:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 628.03 332.83 23-JUL-01:15 99545.43 04-FEB-06:15
WaterSystems:EnergyTransfer 626.05 332.83 23-JUL-01:15 41388.00 19-JAN-07:45
sub cat:WaterSystems:EnergyTransfer 626.05 332.83 23-JUL-01:15 41388.00 19-JAN-07:45
EnergyTransfer:HVAC 5176.28 0.00 01-JAN-06:15 365153.16 29-NOV-11:45
CoolingCoils:EnergyTransfer 5168.71 0.00 01-JAN-06:15 365153.16 29-NOV-11:45
HeatingCoils:EnergyTransfer 7.57 0.00 01-JAN-00:15 84029.37 04-FEB-06:00
PlantLoopHeatingDemand:HVAC 5.80 0.00 01-JAN-00:15 64013.05 04-FEB-06:00
HeatingCoils:PlantLoopHeatingDemand 5.80 0.00 01-JAN-00:15 64013.05 04-FEB-06:00
Boilers:EnergyTransfer 1.98 0.00 01-JAN-00:15 61106.62 04-FEB-06:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.577 -24.505 0.000 0.000 3.563 1.087 12.213 24.068 0.000 1.439 0.000 0.000 -3.540 0.000 -2.909 -11.992
G NW APARTMENT 1.048 -19.799 0.000 0.000 3.577 1.087 12.213 16.585 0.000 1.423 0.000 0.000 -3.408 0.000 -2.586 -10.139
OFFICE 0.218 -35.671 0.000 0.000 0.503 29.882 9.495 24.183 0.000 0.941 0.000 0.000 -3.696 0.000 -0.747 -25.108
G NE APARTMENT 0.762 -20.038 0.000 0.000 3.584 1.087 12.213 16.878 0.000 1.423 0.000 0.000 -3.238 0.000 -2.559 -10.112
G N1 APARTMENT 0.410 -13.902 0.000 0.000 3.585 1.087 12.213 7.692 0.000 1.051 0.000 0.000 -1.982 0.000 -2.133 -8.020
G N2 APARTMENT 0.404 -13.917 0.000 0.000 3.586 1.087 12.213 7.690 0.000 1.051 0.000 0.000 -1.980 0.000 -2.131 -8.003
G S1 APARTMENT 0.068 -18.604 0.000 0.000 3.560 1.087 12.213 15.225 0.000 1.039 0.000 0.000 -2.117 0.000 -2.550 -9.921
G S2 APARTMENT 0.070 -19.137 0.000 0.000 3.559 1.087 12.213 15.208 0.000 1.045 0.000 0.000 -2.129 0.000 -2.575 -9.338
F2 SW APARTMENT 0.345 -37.893 0.000 0.000 3.537 1.087 12.213 22.836 0.000 1.947 3.932 0.000 -4.207 0.000 -3.796 -0.000
F2 NW APARTMENT 0.770 -30.696 0.000 0.000 3.554 1.087 12.213 15.622 0.000 1.922 3.066 0.000 -4.092 0.000 -3.445 -0.000
F2 SE APARTMENT 0.226 -40.481 0.000 0.000 3.535 1.087 12.213 23.080 0.000 1.944 6.430 0.000 -4.186 0.000 -3.849 -0.000
F2 NE APARTMENT 0.512 -31.018 0.000 0.000 3.560 1.087 12.213 15.865 0.000 1.922 3.161 0.000 -3.886 0.000 -3.416 -0.000
F2 N1 APARTMENT 0.227 -23.140 0.000 0.000 3.557 1.087 12.213 7.109 0.000 1.389 2.930 0.000 -2.461 0.000 -2.910 -0.000
F2 N2 APARTMENT 0.224 -23.156 0.000 0.000 3.557 1.087 12.213 7.108 0.000 1.389 2.946 0.000 -2.458 0.000 -2.908 -0.000
F2 S1 APARTMENT 0.032 -30.026 0.000 0.000 3.529 1.087 12.213 14.394 0.000 1.342 3.300 0.000 -2.523 0.000 -3.348 -0.000
F2 S2 APARTMENT 0.032 -30.231 0.000 0.000 3.529 1.087 12.213 14.392 0.000 1.347 3.511 0.000 -2.526 0.000 -3.354 -0.000
F3 SW APARTMENT 0.331 -39.560 0.000 0.000 3.535 1.087 12.213 22.351 0.000 2.503 6.061 0.000 -4.310 0.000 -4.210 -0.001
F3 NW APARTMENT 0.742 -32.539 0.000 0.000 3.552 1.087 12.213 15.298 0.000 2.468 5.255 0.000 -4.224 0.000 -3.852 -0.000
F3 SE APARTMENT 0.212 -40.084 0.000 0.000 3.537 1.087 12.213 22.640 0.000 2.479 6.347 0.000 -4.217 0.000 -4.212 -0.001
F3 NE APARTMENT 0.493 -32.838 0.000 0.000 3.557 1.087 12.213 15.518 0.000 2.468 5.331 0.000 -4.006 0.000 -3.822 -0.000
F3 N1 APARTMENT 0.211 -25.190 0.000 0.000 3.552 1.087 12.213 6.952 0.000 1.836 5.169 0.000 -2.561 0.000 -3.267 0.000
F3 N2 APARTMENT 0.208 -25.204 0.000 0.000 3.552 1.087 12.213 6.950 0.000 1.836 5.182 0.000 -2.559 0.000 -3.265 0.000
F3 S1 APARTMENT 0.030 -31.861 0.000 0.000 3.524 1.087 12.213 14.062 0.000 1.712 5.534 0.000 -2.599 0.000 -3.702 -0.000
F3 S2 APARTMENT 0.030 -31.945 0.000 0.000 3.525 1.087 12.213 14.063 0.000 1.719 5.609 0.000 -2.598 0.000 -3.702 -0.000
F4 SW APARTMENT 0.357 -39.692 0.000 0.000 3.536 1.087 12.213 22.032 0.000 2.739 6.516 0.000 -4.345 0.000 -4.442 -0.000
F4 NW APARTMENT 0.779 -32.863 0.000 0.000 3.552 1.087 12.213 15.101 0.000 2.700 5.777 0.000 -4.272 0.000 -4.073 0.000
F4 SE APARTMENT 0.233 -39.978 0.000 0.000 3.538 1.087 12.213 22.315 0.000 2.711 6.553 0.000 -4.238 0.000 -4.434 -0.000
F4 NE APARTMENT 0.524 -33.141 0.000 0.000 3.557 1.087 12.213 15.303 0.000 2.699 5.845 0.000 -4.046 0.000 -4.041 -0.000
F4 N1 APARTMENT 0.224 -25.623 0.000 0.000 3.551 1.087 12.213 6.862 0.000 1.996 5.732 0.000 -2.600 0.000 -3.442 0.000
F4 N2 APARTMENT 0.222 -25.636 0.000 0.000 3.552 1.087 12.213 6.861 0.000 1.995 5.744 0.000 -2.597 0.000 -3.440 0.000
F4 S1 APARTMENT 0.037 -32.169 0.000 0.000 3.524 1.087 12.213 13.855 0.000 1.863 6.093 0.000 -2.624 0.000 -3.879 -0.000
F4 S2 APARTMENT 0.036 -32.225 0.000 0.000 3.525 1.087 12.213 13.856 0.000 1.870 6.140 0.000 -2.622 0.000 -3.879 -0.001
M SW APARTMENT 0.392 -40.152 0.000 0.000 3.537 1.087 12.213 21.767 0.000 2.926 7.311 0.000 -4.386 0.000 -4.694 -0.001
M NW APARTMENT 0.827 -33.482 0.000 0.000 3.553 1.087 12.213 14.931 0.000 2.884 6.617 0.000 -4.319 0.000 -4.311 0.000
M SE APARTMENT 0.260 -40.395 0.000 0.000 3.539 1.087 12.213 22.040 0.000 2.897 7.317 0.000 -4.273 0.000 -4.683 -0.000
M NE APARTMENT 0.564 -33.741 0.000 0.000 3.558 1.087 12.213 15.120 0.000 2.883 6.679 0.000 -4.086 0.000 -4.276 0.000
M N1 APARTMENT 0.247 -26.297 0.000 0.000 3.552 1.087 12.213 6.784 0.000 2.122 6.568 0.000 -2.635 0.000 -3.640 0.000
M N2 APARTMENT 0.244 -26.309 0.000 0.000 3.552 1.087 12.213 6.783 0.000 2.121 6.579 0.000 -2.632 0.000 -3.637 0.000
M S1 APARTMENT 0.046 -32.733 0.000 0.000 3.525 1.087 12.213 13.684 0.000 1.989 6.925 0.000 -2.649 0.000 -4.086 -0.000
M S2 APARTMENT 0.046 -32.783 0.000 0.000 3.526 1.087 12.213 13.685 0.000 1.995 6.964 0.000 -2.647 0.000 -4.085 -0.000
F6 SW APARTMENT 0.447 -39.141 0.000 0.000 3.540 1.087 12.213 21.601 0.000 3.081 6.418 0.000 -4.365 0.000 -4.880 -0.000
F6 NW APARTMENT 0.920 -32.672 0.000 0.000 3.557 1.087 12.213 14.845 0.000 3.036 5.778 0.000 -4.297 0.000 -4.467 0.000
F6 SE APARTMENT 0.300 -39.361 0.000 0.000 3.542 1.087 12.213 21.865 0.000 3.050 6.420 0.000 -4.250 0.000 -4.867 -0.000
F6 NE APARTMENT 0.642 -32.913 0.000 0.000 3.562 1.087 12.213 15.024 0.000 3.035 5.838 0.000 -4.061 0.000 -4.427 0.000
F6 N1 APARTMENT 0.288 -25.524 0.000 0.000 3.555 1.087 12.213 6.754 0.000 2.226 5.775 0.000 -2.621 0.000 -3.753 0.000
F6 N2 APARTMENT 0.285 -25.535 0.000 0.000 3.556 1.087 12.213 6.753 0.000 2.225 5.786 0.000 -2.619 0.000 -3.750 0.000
F6 S1 APARTMENT 0.058 -31.762 0.000 0.000 3.528 1.087 12.213 13.577 0.000 2.094 6.074 0.000 -2.636 0.000 -4.232 -0.001
F6 S2 APARTMENT 0.057 -31.809 0.000 0.000 3.529 1.087 12.213 13.578 0.000 2.100 6.111 0.000 -2.634 0.000 -4.231 -0.000
F7 SW APARTMENT 0.496 -38.674 0.000 0.000 3.542 1.087 12.213 21.440 0.000 3.213 6.095 0.000 -4.364 0.000 -5.046 -0.000
F7 NW APARTMENT 1.003 -32.368 0.000 0.000 3.559 1.087 12.213 14.754 0.000 3.165 5.497 0.000 -4.296 0.000 -4.613 0.000
F7 SE APARTMENT 0.338 -38.876 0.000 0.000 3.544 1.087 12.213 21.697 0.000 3.180 6.095 0.000 -4.246 0.000 -5.031 -0.001
F7 NE APARTMENT 0.711 -32.594 0.000 0.000 3.565 1.087 12.213 14.924 0.000 3.163 5.555 0.000 -4.056 0.000 -4.568 -0.000
F7 N1 APARTMENT 0.325 -25.246 0.000 0.000 3.558 1.087 12.213 6.718 0.000 2.313 5.514 0.000 -2.621 0.000 -3.861 0.000
F7 N2 APARTMENT 0.323 -25.259 0.000 0.000 3.558 1.087 12.213 6.716 0.000 2.313 5.525 0.000 -2.618 0.000 -3.857 0.000
F7 S1 APARTMENT 0.069 -31.333 0.000 0.000 3.530 1.087 12.213 13.475 0.000 2.183 5.774 0.000 -2.635 0.000 -4.362 -0.000
F7 S2 APARTMENT 0.069 -31.380 0.000 0.000 3.531 1.087 12.213 13.476 0.000 2.189 5.810 0.000 -2.633 0.000 -4.362 -0.000
F8 SW APARTMENT 0.546 -38.499 0.000 0.000 3.544 1.087 12.213 21.288 0.000 3.335 6.071 0.000 -4.373 0.000 -5.211 -0.000
F8 NW APARTMENT 1.083 -32.331 0.000 0.000 3.561 1.087 12.213 14.662 0.000 3.285 5.508 0.000 -4.306 0.000 -4.761 0.000
F8 SE APARTMENT 0.374 -38.684 0.000 0.000 3.546 1.087 12.213 21.539 0.000 3.302 6.071 0.000 -4.252 0.000 -5.195 -0.000
F8 NE APARTMENT 0.779 -32.544 0.000 0.000 3.567 1.087 12.213 14.824 0.000 3.283 5.566 0.000 -4.062 0.000 -4.711 -0.000
F8 N1 APARTMENT 0.365 -25.237 0.000 0.000 3.560 1.087 12.213 6.678 0.000 2.397 5.539 0.000 -2.627 0.000 -3.974 0.000
F8 N2 APARTMENT 0.362 -25.248 0.000 0.000 3.561 1.087 12.213 6.677 0.000 2.396 5.549 0.000 -2.625 0.000 -3.970 0.000
F8 S1 APARTMENT 0.083 -31.191 0.000 0.000 3.532 1.087 12.213 13.379 0.000 2.270 5.761 0.000 -2.640 0.000 -4.494 -0.001
F8 S2 APARTMENT 0.082 -31.239 0.000 0.000 3.533 1.087 12.213 13.380 0.000 2.276 5.801 0.000 -2.638 0.000 -4.493 -0.000
F9 SW APARTMENT 0.635 -39.209 0.000 0.000 3.546 1.087 12.213 21.125 0.000 3.483 6.880 0.000 -4.401 0.000 -5.359 -0.000
F9 NW APARTMENT 1.220 -33.137 0.000 0.000 3.563 1.087 12.213 14.548 0.000 3.427 6.319 0.000 -4.337 0.000 -4.902 0.000
F9 SE APARTMENT 0.433 -39.365 0.000 0.000 3.549 1.087 12.213 21.367 0.000 3.448 6.884 0.000 -4.276 0.000 -5.340 -0.001
F9 NE APARTMENT 0.878 -33.333 0.000 0.000 3.569 1.087 12.213 14.702 0.000 3.425 6.395 0.000 -4.090 0.000 -4.845 -0.000
F9 N1 APARTMENT 0.439 -26.007 0.000 0.000 3.562 1.087 12.213 6.621 0.000 2.508 6.306 0.000 -2.646 0.000 -4.083 0.000
F9 N2 APARTMENT 0.436 -26.018 0.000 0.000 3.562 1.087 12.213 6.620 0.000 2.507 6.315 0.000 -2.643 0.000 -4.079 0.000
F9 S1 APARTMENT 0.113 -31.930 0.000 0.000 3.535 1.087 12.213 13.283 0.000 2.403 6.562 0.000 -2.654 0.000 -4.611 -0.000
F9 S2 APARTMENT 0.111 -31.916 0.000 0.000 3.535 1.087 12.213 13.280 0.000 2.397 6.556 0.000 -2.653 0.000 -4.610 -0.000
T SW APARTMENT 1.318 -40.745 0.000 0.000 3.560 1.087 12.213 20.423 0.000 3.574 8.111 0.000 -4.124 0.000 -5.416 -0.001
T NW APARTMENT 1.916 -34.997 0.000 0.000 3.573 1.087 12.213 13.936 0.000 3.513 7.865 0.000 -4.085 0.000 -5.020 0.000
T SE APARTMENT 1.046 -40.804 0.000 0.000 3.564 1.087 12.213 20.664 0.000 3.550 8.090 0.000 -4.008 0.000 -5.402 -0.000
T NE APARTMENT 1.539 -35.048 0.000 0.000 3.579 1.087 12.213 14.105 0.000 3.513 7.863 0.000 -3.871 0.000 -4.979 -0.000
T N1 APARTMENT 0.767 -28.036 0.000 0.000 3.573 1.087 12.213 6.366 0.000 2.574 8.100 0.000 -2.474 0.000 -4.169 -0.000
T N2 APARTMENT 0.759 -28.048 0.000 0.000 3.573 1.087 12.213 6.363 0.000 2.573 8.115 0.000 -2.470 0.000 -4.165 -0.000
T S1 APARTMENT 0.389 -33.883 0.000 0.000 3.553 1.087 12.213 12.913 0.000 2.559 8.346 0.000 -2.526 0.000 -4.650 -0.000
T S2 APARTMENT 0.392 -33.906 0.000 0.000 3.553 1.087 12.213 12.910 0.000 2.558 8.368 0.000 -2.523 0.000 -4.651 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 5.784 0.000 5.486 0.000 0.000 -0.930 0.000 -6.301 -20.478
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.655 0.000 0.096 0.000 0.000 -0.626 0.000 -0.273 -18.292
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.575 0.000 0.107 0.000 0.000 -0.659 0.000 -0.346 -18.117
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.521 0.000 0.114 0.000 0.000 -0.678 0.000 -0.398 -17.998
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 32.880 0.000 2.440 0.000 0.095 0.000 0.000 -0.729 0.000 -0.501 -34.184
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.467 0.000 0.131 0.000 0.000 -0.683 0.000 -0.461 -17.893
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.458 0.000 0.142 0.000 0.000 -0.674 0.000 -0.476 -17.889
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.439 0.000 0.147 0.000 0.000 -0.675 0.000 -0.498 -17.854
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.412 0.000 0.144 0.000 0.000 -0.687 0.000 -0.525 -17.784
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 8.151 2.243 0.000 0.063 0.000 0.000 -0.693 0.000 -0.666 -25.538
Total Facility 35.617 -2504.455 0.000 0.000 280.993 296.560 982.450 1183.592 0.000 197.667 434.130 0.000 -273.758 0.000 -334.135 -298.674


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 30-SEP-14:30 0.00 -3006.48 0.00 0.00 38.92 22.70 400.26 4255.39 0.00 98.90 0.00 0.00 0.00 0.00 0.00 -1809.68
G NW APARTMENT 29-JUL-16:30 0.00 -2929.98 0.00 0.00 84.76 64.86 588.62 2824.45 0.00 142.36 0.00 0.00 0.00 0.00 0.00 -775.07
OFFICE 29-SEP-12:30 0.00 -4140.51 0.00 0.00 65.20 2345.88 588.62 3165.29 0.00 81.63 0.00 0.00 0.00 0.00 0.00 -2106.10
G NE APARTMENT 25-JUL-10:15 0.00 -2297.95 0.00 0.00 40.65 12.97 412.03 2550.48 0.00 62.75 0.00 0.00 0.00 0.00 0.00 -780.94
G N1 APARTMENT 29-JUL-16:30 0.00 -1608.60 0.00 0.00 84.58 64.86 588.62 1090.78 0.00 85.38 0.00 0.00 0.00 0.00 0.00 -305.60
G N2 APARTMENT 29-JUL-16:30 0.00 -1595.26 0.00 0.00 84.53 64.86 588.62 1090.91 0.00 85.31 0.00 0.00 0.00 0.00 0.00 -318.97
G S1 APARTMENT 27-FEB-13:15 0.00 -1903.64 0.00 0.00 40.75 12.97 388.49 2845.77 0.00 272.78 0.00 0.00 0.00 0.00 0.00 -1657.13
G S2 APARTMENT 27-FEB-13:15 0.00 -1951.84 0.00 0.00 40.75 12.97 388.49 2843.82 0.00 272.77 0.00 0.00 0.00 0.00 0.00 -1606.97
F2 SW APARTMENT 07-NOV-15:15 0.00 -3932.54 0.00 0.00 40.70 22.70 400.26 4021.17 0.00 42.87 0.00 0.00 0.00 0.00 0.00 -595.16
F2 NW APARTMENT 29-JUL-16:30 0.00 -3473.09 0.00 0.00 84.76 64.86 588.62 2772.82 0.00 204.20 0.00 0.00 0.00 0.00 0.00 -242.17
F2 SE APARTMENT 07-NOV-14:30 0.00 -3517.83 0.00 0.00 40.49 12.97 382.60 2863.97 0.00 48.34 169.46 0.00 0.00 0.00 0.00 0.00
F2 NE APARTMENT 29-JUL-16:30 0.00 -2818.80 0.00 0.00 84.76 64.86 588.62 1624.15 0.00 204.20 252.21 0.00 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 29-JUL-16:30 0.00 -2020.22 0.00 0.00 84.76 64.86 588.62 1073.49 0.00 123.05 85.45 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 29-JUL-16:30 0.00 -2009.72 0.00 0.00 84.76 64.86 588.62 1073.63 0.00 123.01 74.84 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 22-FEB-14:00 0.00 -2539.76 0.00 0.00 40.68 12.97 388.49 2979.87 0.00 18.99 0.00 0.00 0.00 0.00 0.00 -901.25
F2 S2 APARTMENT 22-FEB-14:00 0.00 -2568.37 0.00 0.00 40.71 12.97 388.49 2979.65 0.00 19.10 0.00 0.00 0.00 0.00 0.00 -872.54
F3 SW APARTMENT 07-NOV-15:15 0.00 -3988.34 0.00 0.00 40.71 22.70 400.26 3984.11 0.00 50.56 0.00 0.00 0.00 0.00 0.00 -510.00
F3 NW APARTMENT 29-JUL-16:30 0.00 -3487.21 0.00 0.00 84.76 64.86 588.62 2745.63 0.00 241.26 0.00 0.00 0.00 0.00 0.00 -237.92
F3 SE APARTMENT 07-NOV-15:00 0.00 -3363.89 0.00 0.00 40.34 12.97 382.60 2557.94 0.00 36.86 333.17 0.00 0.00 0.00 0.00 0.00
F3 NE APARTMENT 29-JUL-16:30 0.00 -2848.66 0.00 0.00 84.76 64.86 588.62 1618.04 0.00 241.26 251.11 0.00 0.00 0.00 0.00 0.00
F3 N1 APARTMENT 29-JUL-16:30 0.00 -2061.77 0.00 0.00 84.76 64.86 588.62 1068.14 0.00 145.50 109.90 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 29-JUL-16:30 0.00 -2051.27 0.00 0.00 84.76 64.86 588.62 1068.28 0.00 145.45 99.29 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 21-FEB-14:45 0.00 -2636.39 0.00 0.00 40.67 12.97 382.60 2415.68 0.00 244.21 0.00 0.00 0.00 0.00 0.00 -459.73
F3 S2 APARTMENT 21-FEB-14:45 0.00 -2635.07 0.00 0.00 40.72 12.97 382.60 2416.17 0.00 245.67 0.00 0.00 0.00 0.00 0.00 -463.07
F4 SW APARTMENT 07-NOV-15:00 0.00 -3991.73 0.00 0.00 40.76 12.97 382.60 4123.99 0.00 41.76 0.00 0.00 0.00 0.00 0.00 -610.34
F4 NW APARTMENT 29-JUL-16:30 0.00 -3502.38 0.00 0.00 84.76 64.86 588.62 2724.75 0.00 269.11 0.00 0.00 0.00 0.00 0.00 -229.71
F4 SE APARTMENT 07-NOV-15:00 0.00 -3375.95 0.00 0.00 40.40 12.97 382.60 2547.24 0.00 41.21 351.52 0.00 0.00 0.00 0.00 0.00
F4 NE APARTMENT 29-JUL-16:30 0.00 -2875.32 0.00 0.00 84.76 64.86 588.62 1613.10 0.00 269.11 254.87 0.00 0.00 0.00 0.00 0.00
F4 N1 APARTMENT 29-JUL-16:30 0.00 -2084.14 0.00 0.00 84.76 64.86 588.62 1064.09 0.00 162.32 119.48 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 29-JUL-16:30 0.00 -2078.53 0.00 0.00 84.76 64.86 588.62 1064.24 0.00 162.32 113.73 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 21-FEB-14:45 0.00 -2687.91 0.00 0.00 40.61 12.97 382.60 2380.38 0.00 258.39 0.00 0.00 0.00 0.00 0.00 -387.04
F4 S2 APARTMENT 21-FEB-14:45 0.00 -2704.54 0.00 0.00 40.65 12.97 382.60 2380.84 0.00 261.79 0.00 0.00 0.00 0.00 0.00 -374.31
M SW APARTMENT 07-NOV-15:00 0.00 -4001.31 0.00 0.00 40.76 12.97 382.60 4107.92 0.00 45.14 0.00 0.00 0.00 0.00 0.00 -588.08
M NW APARTMENT 29-JUL-16:30 0.00 -3536.95 0.00 0.00 84.76 64.86 588.62 2706.75 0.00 291.85 0.00 0.00 0.00 0.00 0.00 -199.89
M SE APARTMENT 07-NOV-14:45 0.00 -3416.25 0.00 0.00 40.35 12.97 382.60 2681.87 0.00 55.98 242.47 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 29-JUL-16:30 0.00 -2918.89 0.00 0.00 84.76 64.86 588.62 1607.92 0.00 291.86 280.87 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 29-JUL-16:30 0.00 -2121.55 0.00 0.00 84.76 64.86 588.62 1060.08 0.00 176.04 147.19 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 29-JUL-16:30 0.00 -2116.03 0.00 0.00 84.76 64.86 588.62 1060.23 0.00 176.04 141.53 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 21-FEB-14:45 0.00 -2747.74 0.00 0.00 40.69 12.97 382.60 2354.99 0.00 278.56 0.00 0.00 0.00 0.00 0.00 -322.07
M S2 APARTMENT 21-FEB-14:45 0.00 -2739.48 0.00 0.00 40.73 12.97 382.60 2355.42 0.00 279.13 0.00 0.00 0.00 0.00 0.00 -331.37
F6 SW APARTMENT 07-NOV-15:00 0.00 -3952.20 0.00 0.00 40.76 12.97 382.60 4096.26 0.00 47.98 0.00 0.00 0.00 0.00 0.00 -628.38
F6 NW APARTMENT 29-JUL-16:30 0.00 -3511.46 0.00 0.00 84.77 64.86 588.62 2693.77 0.00 311.27 0.00 0.00 0.00 0.00 0.00 -231.83
F6 SE APARTMENT 07-NOV-14:45 0.00 -3395.55 0.00 0.00 40.46 12.97 382.60 2675.38 0.00 60.15 223.99 0.00 0.00 0.00 0.00 0.00
F6 NE APARTMENT 29-JUL-16:30 0.00 -2902.36 0.00 0.00 84.77 64.86 588.62 1605.81 0.00 311.28 247.03 0.00 0.00 0.00 0.00 0.00
F6 N1 APARTMENT 29-JUL-16:30 0.00 -2100.20 0.00 0.00 84.76 64.86 588.62 1058.23 0.00 187.75 115.98 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 29-JUL-16:30 0.00 -2094.79 0.00 0.00 84.76 64.86 588.62 1058.37 0.00 187.75 110.43 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 22-FEB-14:00 0.00 -2704.09 0.00 0.00 40.75 12.97 388.49 2912.43 0.00 28.82 0.00 0.00 0.00 0.00 0.00 -679.37
F6 S2 APARTMENT 22-FEB-14:15 0.00 -2716.61 0.00 0.00 40.75 12.97 382.60 2840.52 0.00 30.45 0.00 0.00 0.00 0.00 0.00 -590.69
F7 SW APARTMENT 07-NOV-15:00 0.00 -3925.73 0.00 0.00 40.76 12.97 382.60 4084.93 0.00 50.44 0.00 0.00 0.00 0.00 0.00 -645.97
F7 NW APARTMENT 29-JUL-16:30 0.00 -3507.44 0.00 0.00 84.77 64.86 588.62 2681.49 0.00 328.32 0.00 0.00 0.00 0.00 0.00 -240.61
F7 SE APARTMENT 07-NOV-14:30 0.00 -3388.91 0.00 0.00 40.41 12.97 382.60 2786.20 0.00 75.94 90.79 0.00 0.00 0.00 0.00 0.00
F7 NE APARTMENT 29-JUL-16:30 0.00 -2905.81 0.00 0.00 84.77 64.86 588.62 1602.97 0.00 328.32 236.28 0.00 0.00 0.00 0.00 0.00
F7 N1 APARTMENT 29-JUL-16:30 0.00 -2099.11 0.00 0.00 84.76 64.86 588.62 1055.97 0.00 198.03 106.88 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 29-JUL-16:30 0.00 -2093.79 0.00 0.00 84.76 64.86 588.62 1056.11 0.00 198.03 101.41 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 22-FEB-16:30 0.00 -2683.58 0.00 0.00 48.90 45.40 470.89 1396.91 0.00 465.47 256.01 0.00 0.00 0.00 0.00 0.00
F7 S2 APARTMENT 22-FEB-14:15 0.00 -2684.76 0.00 0.00 40.75 12.97 382.60 2831.13 0.00 31.95 0.00 0.00 0.00 0.00 0.00 -614.65
F8 SW APARTMENT 07-NOV-15:00 0.00 -3909.39 0.00 0.00 40.76 12.97 382.60 4074.19 0.00 52.61 0.00 0.00 0.00 0.00 0.00 -653.73
F8 NW APARTMENT 29-JUL-16:30 0.00 -3516.20 0.00 0.00 84.77 64.86 588.62 2669.83 0.00 343.57 0.00 0.00 0.00 0.00 0.00 -235.44
F8 SE APARTMENT 07-NOV-14:30 0.00 -3402.32 0.00 0.00 40.52 12.97 382.60 2778.94 0.00 80.12 107.18 0.00 0.00 0.00 0.00 0.00
F8 NE APARTMENT 29-JUL-16:30 0.00 -2921.13 0.00 0.00 84.77 64.86 588.62 1599.67 0.00 343.57 239.65 0.00 0.00 0.00 0.00 0.00
F8 N1 APARTMENT 29-JUL-16:30 0.00 -2110.30 0.00 0.00 84.76 64.86 588.62 1053.44 0.00 207.23 111.40 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 29-JUL-16:30 0.00 -2105.07 0.00 0.00 84.76 64.86 588.62 1053.58 0.00 207.23 106.03 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 22-FEB-12:45 0.00 -2747.54 0.00 0.00 40.75 12.97 406.15 2935.25 0.00 337.80 0.00 0.00 0.00 0.00 0.00 -985.39
F8 S2 APARTMENT 22-FEB-12:45 0.00 -2763.20 0.00 0.00 40.75 12.97 406.15 2934.97 0.00 338.37 0.00 0.00 0.00 0.00 0.00 -970.02
F9 SW APARTMENT 07-NOV-15:00 0.00 -3958.51 0.00 0.00 40.76 12.97 382.60 4061.26 0.00 54.54 0.00 0.00 0.00 0.00 0.00 -593.62
F9 NW APARTMENT 29-JUL-16:30 0.00 -3620.62 0.00 0.00 84.77 64.86 588.62 2653.74 0.00 357.40 0.00 0.00 0.00 0.00 0.00 -128.77
F9 SE APARTMENT 07-NOV-14:30 0.00 -3467.23 0.00 0.00 40.58 12.97 382.60 2767.95 0.00 83.44 179.69 0.00 0.00 0.00 0.00 0.00
F9 NE APARTMENT 29-JUL-16:30 0.00 -3029.68 0.00 0.00 84.77 64.86 588.62 1591.13 0.00 357.41 342.90 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 29-JUL-16:30 0.00 -2203.59 0.00 0.00 84.76 64.86 588.62 1047.79 0.00 215.57 201.98 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 29-JUL-16:30 0.00 -2198.62 0.00 0.00 84.76 64.86 588.62 1047.92 0.00 215.57 196.88 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 22-FEB-12:45 0.00 -2710.92 0.00 0.00 40.75 12.97 406.15 2924.31 0.00 345.46 0.00 0.00 0.00 0.00 0.00 -1018.72
F9 S2 APARTMENT 22-FEB-12:45 0.00 -2721.68 0.00 0.00 40.75 12.97 406.15 2923.99 0.00 345.46 0.00 0.00 0.00 0.00 0.00 -1007.65
T SW APARTMENT 07-NOV-15:00 0.00 -4729.53 0.00 0.00 40.76 12.97 382.60 3974.13 0.00 56.28 262.79 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 29-JUL-16:30 0.00 -4358.81 0.00 0.00 84.77 64.86 588.62 2567.84 0.00 370.06 682.66 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 07-NOV-14:15 0.00 -4170.39 0.00 0.00 40.46 12.97 382.60 2768.78 0.00 100.74 864.85 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 29-JUL-16:10 0.00 -3631.43 0.00 0.00 84.78 64.86 588.62 1572.58 0.00 380.29 940.31 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-JUL-16:30 0.00 -2798.47 0.00 0.00 84.45 64.86 588.62 1009.76 0.00 221.77 829.01 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUL-16:30 0.00 -2774.71 0.00 0.00 84.39 64.86 588.62 1010.04 0.00 221.49 805.31 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 22-FEB-12:45 0.00 -3477.09 0.00 0.00 40.75 12.97 406.15 2870.48 0.00 349.98 0.00 0.00 0.00 0.00 0.00 -203.24
T S2 APARTMENT 22-FEB-12:45 0.00 -3494.99 0.00 0.00 40.75 12.97 406.15 2869.83 0.00 349.98 0.00 0.00 0.00 0.00 0.00 -184.69
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:30 0.00 -209390.03 0.00 0.00 6680.31 11327.17 47212.47 124958.84 0.00 22504.19 0.00 0.00 0.00 0.00 0.00 -3292.94


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 12-NOV-09:45 1066.19 0.00 0.00 0.00 44.54 12.97 394.37 286.69 0.00 0.00 0.00 0.00 0.00 0.00 -1340.22 -464.55
G NW APARTMENT 16-MAR-11:55 1307.24 0.00 0.00 0.00 46.35 12.97 406.15 251.09 0.00 0.00 0.00 0.00 0.00 0.00 -1241.69 -782.10
OFFICE 04-FEB-07:00 782.29 0.00 0.00 0.00 0.00 469.18 194.24 0.00 0.00 0.00 245.18 0.00 -1292.42 0.00 -398.48 0.00
G NE APARTMENT 24-JAN-14:30 1219.48 0.00 0.00 0.00 44.77 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -37.87 0.00 -1251.67 -370.28
G N1 APARTMENT 16-MAR-11:55 1282.18 0.00 0.00 0.00 46.44 12.97 406.15 152.22 0.00 0.00 0.00 0.00 0.00 0.00 -1172.54 -727.43
G N2 APARTMENT 16-MAR-11:55 1309.51 0.00 0.00 0.00 46.35 12.97 406.15 150.21 0.00 0.00 0.00 0.00 0.00 0.00 -1172.72 -752.47
G S1 APARTMENT 12-NOV-09:45 937.78 0.00 0.00 0.00 44.04 12.97 394.37 216.24 0.00 0.00 0.00 0.00 0.00 0.00 -1259.63 -345.77
G S2 APARTMENT 12-NOV-09:45 904.39 0.00 0.00 0.00 43.94 12.97 394.37 214.85 0.00 0.00 0.00 0.00 0.00 0.00 -1261.85 -308.68
F2 SW APARTMENT 04-FEB-06:00 714.84 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 736.40 0.00 -1336.26 0.00 -599.90 0.00
F2 NW APARTMENT 03-FEB-13:00 1511.62 0.00 0.00 0.00 44.34 12.97 406.15 225.89 0.00 0.00 0.00 0.00 0.00 0.00 -1801.21 -399.77
F2 SE APARTMENT 04-FEB-06:00 660.45 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 795.12 0.00 -1340.60 0.00 -599.90 0.00
F2 NE APARTMENT 03-FEB-13:00 1493.58 0.00 0.00 0.00 44.15 12.97 406.15 123.12 0.00 0.00 0.00 0.00 0.00 0.00 -1799.69 -280.27
F2 N1 APARTMENT 03-FEB-13:00 1588.02 0.00 0.00 0.00 43.65 12.97 406.15 66.55 0.00 0.00 0.00 0.00 0.00 0.00 -1696.91 -420.43
F2 N2 APARTMENT 03-FEB-13:00 1583.84 0.00 0.00 0.00 43.64 12.97 406.15 66.13 0.00 0.00 0.00 0.00 0.00 0.00 -1696.90 -415.83
F2 S1 APARTMENT 18-MAR-05:20 119.70 0.00 0.00 0.00 175.83 45.40 317.85 0.00 0.00 0.00 479.20 0.00 -273.38 0.00 -864.60 0.00
F2 S2 APARTMENT 18-MAR-05:20 121.04 0.00 0.00 0.00 176.00 45.40 317.85 0.00 0.00 0.00 475.39 0.00 -273.84 0.00 -861.84 0.00
F3 SW APARTMENT 04-FEB-06:00 757.30 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 837.04 0.00 -1368.30 0.00 -710.98 0.00
F3 NW APARTMENT 05-FEB-09:25 1520.21 0.00 0.00 0.00 47.10 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -49.30 0.00 -1683.93 -241.43
F3 SE APARTMENT 04-FEB-06:00 792.54 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 798.47 0.00 -1364.97 0.00 -710.98 0.00
F3 NE APARTMENT 03-FEB-13:00 1477.44 0.00 0.00 0.00 44.18 12.97 406.15 75.52 0.00 0.00 15.35 0.00 0.00 0.00 -2031.61 0.00
F3 N1 APARTMENT 03-FEB-13:00 1632.50 0.00 0.00 0.00 43.37 12.97 406.15 31.79 0.00 0.00 0.00 0.00 0.00 0.00 -1910.66 -216.12
F3 N2 APARTMENT 03-FEB-13:00 1629.82 0.00 0.00 0.00 43.35 12.97 406.15 31.41 0.00 0.00 0.00 0.00 0.00 0.00 -1910.65 -213.06
F3 S1 APARTMENT 18-MAR-05:20 117.20 0.00 0.00 0.00 175.64 45.40 317.85 0.00 0.00 0.00 623.75 0.00 -283.83 0.00 -996.01 0.00
F3 S2 APARTMENT 18-MAR-05:20 116.68 0.00 0.00 0.00 175.61 45.40 317.85 0.00 0.00 0.00 625.59 0.00 -284.01 0.00 -997.11 0.00
F4 SW APARTMENT 04-FEB-06:00 863.72 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 832.13 0.00 -1385.28 0.00 -795.50 0.00
F4 NW APARTMENT 05-FEB-09:25 1624.55 0.00 0.00 0.00 47.25 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -62.07 0.00 -1832.17 -184.92
F4 SE APARTMENT 04-FEB-06:00 920.68 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 769.92 0.00 -1380.02 0.00 -795.50 0.00
F4 NE APARTMENT 03-FEB-13:15 1347.79 0.00 0.00 0.00 44.30 12.97 388.49 90.55 0.00 0.00 0.00 0.00 0.00 0.00 -1794.60 -89.50
F4 N1 APARTMENT 05-FEB-09:25 1649.10 0.00 0.00 0.00 46.67 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -61.65 0.00 -1722.28 -319.18
F4 N2 APARTMENT 05-FEB-09:25 1649.46 0.00 0.00 0.00 46.66 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -62.08 0.00 -1722.29 -319.10
F4 S1 APARTMENT 18-MAR-05:20 126.52 0.00 0.00 0.00 176.55 45.40 317.85 0.00 0.00 0.00 685.56 0.00 -285.78 0.00 -1066.10 0.00
F4 S2 APARTMENT 18-MAR-05:20 126.33 0.00 0.00 0.00 176.58 45.40 317.85 0.00 0.00 0.00 684.52 0.00 -285.65 0.00 -1065.05 0.00
M SW APARTMENT 04-FEB-06:00 959.70 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 818.63 0.00 -1397.85 0.00 -865.41 0.00
M NW APARTMENT 05-FEB-09:25 1739.70 0.00 0.00 0.00 47.31 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -73.43 0.00 -1959.30 -161.63
M SE APARTMENT 04-FEB-05:00 1021.77 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 821.39 0.00 -1371.20 0.00 -904.76 0.00
M NE APARTMENT 05-FEB-09:25 1682.50 0.00 0.00 0.00 45.71 12.97 394.37 1156.48 0.00 0.00 0.00 0.00 0.00 0.00 -1967.74 -1324.30
M N1 APARTMENT 05-FEB-09:25 1744.09 0.00 0.00 0.00 46.72 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -70.16 0.00 -1839.49 -288.52
M N2 APARTMENT 05-FEB-09:25 1745.59 0.00 0.00 0.00 46.71 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -70.61 0.00 -1839.50 -289.54
M S1 APARTMENT 18-MAR-05:10 138.35 0.00 0.00 0.00 162.99 45.40 317.85 0.00 0.00 0.00 913.81 0.00 -309.96 0.00 -1268.45 0.00
M S2 APARTMENT 04-FEB-06:00 211.04 0.00 0.00 0.00 191.66 42.16 253.11 0.00 0.00 0.00 671.99 0.00 -848.85 0.00 -521.11 0.00
F6 SW APARTMENT 12-NOV-09:45 1172.16 0.00 0.00 0.00 43.62 12.97 394.37 58.06 0.00 0.00 489.55 0.00 0.00 0.00 -2170.74 0.00
F6 NW APARTMENT 05-FEB-09:20 1869.27 0.00 0.00 0.00 47.42 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -77.44 0.00 -2071.86 -174.73
F6 SE APARTMENT 12-NOV-09:45 1175.27 0.00 0.00 0.00 43.61 12.97 394.37 159.27 0.00 0.00 381.42 0.00 0.00 0.00 -2166.92 0.00
F6 NE APARTMENT 05-FEB-09:25 1859.29 0.00 0.00 0.00 46.07 12.97 394.37 1133.91 0.00 0.00 0.00 0.00 0.00 0.00 -2075.87 -1370.75
F6 N1 APARTMENT 05-FEB-09:25 1768.21 0.00 0.00 0.00 47.00 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -72.25 0.00 -1943.07 -207.24
F6 N2 APARTMENT 05-FEB-09:25 1769.26 0.00 0.00 0.00 46.99 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -72.70 0.00 -1943.08 -207.81
F6 S1 APARTMENT 12-NOV-09:45 369.82 0.00 0.00 0.00 41.97 12.97 394.37 75.49 0.00 0.00 1111.16 0.00 0.00 0.00 -2005.79 0.00
F6 S2 APARTMENT 12-NOV-09:45 364.72 0.00 0.00 0.00 41.97 12.97 394.37 75.40 0.00 0.00 1116.43 0.00 0.00 0.00 -2005.86 0.00
F7 SW APARTMENT 12-NOV-10:00 1236.08 0.00 0.00 0.00 43.72 12.97 394.37 54.20 0.00 0.00 401.42 0.00 0.00 0.00 -2142.77 0.00
F7 NW APARTMENT 05-FEB-09:20 1997.69 0.00 0.00 0.00 47.42 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -82.90 0.00 -2174.39 -195.17
F7 SE APARTMENT 04-FEB-05:00 1264.04 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 709.18 0.00 -1381.80 0.00 -1024.22 0.00
F7 NE APARTMENT 03-FEB-15:10 1956.64 0.00 0.00 0.00 46.25 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -98.79 0.00 -2132.10 -194.95
F7 N1 APARTMENT 05-FEB-09:25 1818.10 0.00 0.00 0.00 47.16 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -75.24 0.00 -2037.43 -159.93
F7 N2 APARTMENT 05-FEB-09:25 1811.84 0.00 0.00 0.00 47.16 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -75.63 0.00 -2037.42 -153.29
F7 S1 APARTMENT 05-FEB-09:30 531.79 0.00 0.00 0.00 43.95 12.97 394.37 1288.06 0.00 0.00 0.00 0.00 0.00 0.00 -1530.49 -740.66
F7 S2 APARTMENT 05-FEB-09:30 534.47 0.00 0.00 0.00 43.94 12.97 394.37 1287.71 0.00 0.00 0.00 0.00 0.00 0.00 -1530.58 -742.88
F8 SW APARTMENT 12-NOV-10:00 1439.35 0.00 0.00 0.00 44.01 12.97 394.37 50.45 0.00 0.00 284.99 0.00 0.00 0.00 -2226.16 0.00
F8 NW APARTMENT 05-FEB-09:20 2114.62 0.00 0.00 0.00 47.42 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -88.00 0.00 -2268.99 -212.39
F8 SE APARTMENT 12-NOV-10:00 1397.46 0.00 0.00 0.00 44.02 12.97 394.37 138.46 0.00 0.00 237.02 0.00 0.00 0.00 -2224.30 0.00
F8 NE APARTMENT 03-FEB-15:10 1992.83 0.00 0.00 0.00 46.41 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -103.24 0.00 -2220.04 -138.92
F8 N1 APARTMENT 05-FEB-09:25 1864.02 0.00 0.00 0.00 47.30 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -77.81 0.00 -2124.59 -116.26
F8 N2 APARTMENT 05-FEB-09:25 1861.76 0.00 0.00 0.00 47.29 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -78.23 0.00 -2124.60 -113.57
F8 S1 APARTMENT 05-FEB-09:30 869.30 0.00 0.00 0.00 44.26 12.97 394.37 1279.65 0.00 0.00 0.00 0.00 0.00 0.00 -1573.53 -1027.02
F8 S2 APARTMENT 05-FEB-09:30 872.57 0.00 0.00 0.00 44.25 12.97 394.37 1279.27 0.00 0.00 0.00 0.00 0.00 0.00 -1573.60 -1029.84
F9 SW APARTMENT 12-NOV-10:00 1443.00 0.00 0.00 0.00 44.55 12.97 394.37 59.32 0.00 0.00 354.62 0.00 0.00 0.00 -2308.84 0.00
F9 NW APARTMENT 05-FEB-09:20 2256.31 0.00 0.00 0.00 47.42 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -89.14 0.00 -2357.32 -264.62
F9 SE APARTMENT 04-FEB-05:00 1476.20 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 598.37 0.00 -1385.36 0.00 -1122.01 0.00
F9 NE APARTMENT 03-FEB-13:10 2148.69 0.00 0.00 0.00 46.04 12.97 388.49 61.20 0.00 0.00 0.00 0.00 0.00 0.00 -2272.70 -384.69
F9 N1 APARTMENT 03-FEB-15:10 2095.75 0.00 0.00 0.00 45.92 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -92.83 0.00 -2128.68 -343.12
F9 N2 APARTMENT 03-FEB-15:10 2104.01 0.00 0.00 0.00 45.93 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -92.68 0.00 -2128.43 -351.78
F9 S1 APARTMENT 12-NOV-10:00 1246.84 0.00 0.00 0.00 42.85 12.97 394.37 68.92 0.00 0.00 344.06 0.00 0.00 0.00 -2110.02 0.00
F9 S2 APARTMENT 12-NOV-10:00 1244.05 0.00 0.00 0.00 42.85 12.97 394.37 68.86 0.00 0.00 346.87 0.00 0.00 0.00 -2109.98 0.00
T SW APARTMENT 12-NOV-09:55 2221.03 0.00 0.00 0.00 46.16 12.97 394.37 111.55 0.00 0.00 0.00 0.00 0.00 0.00 -2389.43 -396.66
T NW APARTMENT 05-FEB-09:20 2358.04 0.00 0.00 0.00 47.42 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -83.39 0.00 -2440.53 -288.89
T SE APARTMENT 12-NOV-09:55 2173.44 0.00 0.00 0.00 46.19 12.97 394.37 195.65 0.00 0.00 0.00 0.00 0.00 0.00 -2387.81 -434.82
T NE APARTMENT 04-FEB-05:00 2274.65 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1350.43 0.00 -1165.41 -191.61
T N1 APARTMENT 12-NOV-09:55 2294.34 0.00 0.00 0.00 45.73 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -25.47 0.00 -2173.36 -548.60
T N2 APARTMENT 12-NOV-09:55 2286.54 0.00 0.00 0.00 45.74 12.97 394.37 0.00 0.00 0.00 0.00 0.00 -25.42 0.00 -2173.25 -540.96
T S1 APARTMENT 19-MAR-13:30 1647.26 0.00 0.00 0.00 43.53 12.97 382.60 76.34 0.00 0.00 0.00 0.00 0.00 0.00 -2146.96 -15.74
T S2 APARTMENT 19-MAR-13:30 1647.77 0.00 0.00 0.00 43.53 12.97 382.60 76.28 0.00 0.00 0.00 0.00 0.00 0.00 -2146.98 -16.17
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-FEB-09:30 77007.25 0.00 0.00 0.00 3580.91 7228.24 31714.40 79290.67 0.00 0.00 0.00 0.00 -1811.33 0.00 -137827.48 -59182.66



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Sec1.1A-General Information

Data
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.50
Number of hours cooling loads not met 980.25
Number of hours not met 981.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 296.56 13120.46 0.00 0.00 0.00 0.00
Exterior Lighting 163.14 10364.00 0.00 0.00 0.00 0.00
Space Heating 2.28 0.00 2.69 73437.26 0.00 0.00
Space Cooling 1430.98 80892.51 0.00 0.00 0.00 0.00
Pumps 79.68 2580.93 0.00 0.00 0.00 0.00
Heat Rejection 73.72 3797.79 0.00 0.00 0.00 0.00
Fans-Interior 650.69 20633.29 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 811.17 69627.49 0.00 0.00
Receptacle Equipment 1137.32 57042.02 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3870.55   813.86   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1137.32 3870.55
Natural Gas 0.00 813.86
Additional 0.00 0.00
Total 1137.32 4684.41


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.84
Space Heating 0.29
Space Cooling 182.61
Fans-Interior 83.03
Service Water Heating 0.00
Receptacle Equipment 145.13
Miscellaneous 45.01
Subtotal 493.91


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.34
Service Water Heating 103.51
Miscellaneous -0.00
Subtotal 103.86


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.33
Space Heating 0.11
Space Cooling 30.55
Fans-Interior 13.89
Service Water Heating 17.32
Receptacle Equipment 24.28
Miscellaneous 7.53



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.241276
G NW APARTMENT DIRECT AIR 0.255539
OFFICE DIRECT AIR 0.333019
G NE APARTMENT DIRECT AIR 0.202794
G N1 APARTMENT DIRECT AIR 0.133702
G N2 APARTMENT DIRECT AIR 0.132367
G S1 APARTMENT DIRECT AIR 0.114106
G S2 APARTMENT DIRECT AIR 0.119052
F2 SW APARTMENT DIRECT AIR 0.291236
F2 NW APARTMENT DIRECT AIR 0.306607
F2 SE APARTMENT DIRECT AIR 0.261354
F2 NE APARTMENT DIRECT AIR 0.245436
F2 N1 APARTMENT DIRECT AIR 0.167209
F2 N2 APARTMENT DIRECT AIR 0.166145
F2 S1 APARTMENT DIRECT AIR 0.146383
F2 S2 APARTMENT DIRECT AIR 0.146915
F3 SW APARTMENT DIRECT AIR 0.292255
F3 NW APARTMENT DIRECT AIR 0.307680
F3 SE APARTMENT DIRECT AIR 0.243375
F3 NE APARTMENT DIRECT AIR 0.246649
F3 N1 APARTMENT DIRECT AIR 0.169609
F3 N2 APARTMENT DIRECT AIR 0.168548
F3 S1 APARTMENT DIRECT AIR 0.148924
F3 S2 APARTMENT DIRECT AIR 0.148815
F4 SW APARTMENT DIRECT AIR 0.293716
F4 NW APARTMENT DIRECT AIR 0.308980
F4 SE APARTMENT DIRECT AIR 0.242248
F4 NE APARTMENT DIRECT AIR 0.247145
F4 N1 APARTMENT DIRECT AIR 0.171269
F4 N2 APARTMENT DIRECT AIR 0.170209
F4 S1 APARTMENT DIRECT AIR 0.150837
F4 S2 APARTMENT DIRECT AIR 0.150556
M SW APARTMENT DIRECT AIR 0.296945
M NW APARTMENT DIRECT AIR 0.312163
M SE APARTMENT DIRECT AIR 0.244615
M NE APARTMENT DIRECT AIR 0.249668
M N1 APARTMENT DIRECT AIR 0.174602
M N2 APARTMENT DIRECT AIR 0.173544
M S1 APARTMENT DIRECT AIR 0.154268
M S2 APARTMENT DIRECT AIR 0.153947
F6 SW APARTMENT DIRECT AIR 0.294740
F6 NW APARTMENT DIRECT AIR 0.309751
F6 SE APARTMENT DIRECT AIR 0.241890
F6 NE APARTMENT DIRECT AIR 0.246781
F6 N1 APARTMENT DIRECT AIR 0.172500
F6 N2 APARTMENT DIRECT AIR 0.171447
F6 S1 APARTMENT DIRECT AIR 0.152451
F6 S2 APARTMENT DIRECT AIR 0.152098
F7 SW APARTMENT DIRECT AIR 0.294444
F7 NW APARTMENT DIRECT AIR 0.309371
F7 SE APARTMENT DIRECT AIR 0.241131
F7 NE APARTMENT DIRECT AIR 0.245956
F7 N1 APARTMENT DIRECT AIR 0.172309
F7 N2 APARTMENT DIRECT AIR 0.171273
F7 S1 APARTMENT DIRECT AIR 0.152403
F7 S2 APARTMENT DIRECT AIR 0.152032
F8 SW APARTMENT DIRECT AIR 0.295390
F8 NW APARTMENT DIRECT AIR 0.310252
F8 SE APARTMENT DIRECT AIR 0.241599
F8 NE APARTMENT DIRECT AIR 0.246352
F8 N1 APARTMENT DIRECT AIR 0.173363
F8 N2 APARTMENT DIRECT AIR 0.172335
F8 S1 APARTMENT DIRECT AIR 0.153570
F8 S2 APARTMENT DIRECT AIR 0.153110
F9 SW APARTMENT DIRECT AIR 0.305011
F9 NW APARTMENT DIRECT AIR 0.320069
F9 SE APARTMENT DIRECT AIR 0.246484
F9 NE APARTMENT DIRECT AIR 0.250954
F9 N1 APARTMENT DIRECT AIR 0.182223
F9 N2 APARTMENT DIRECT AIR 0.181170
F9 S1 APARTMENT DIRECT AIR 0.162442
F9 S2 APARTMENT DIRECT AIR 0.161433
T SW APARTMENT DIRECT AIR 0.367908
T NW APARTMENT DIRECT AIR 0.378428
T SE APARTMENT DIRECT AIR 0.304103
T NE APARTMENT DIRECT AIR 0.305700
T N1 APARTMENT DIRECT AIR 0.223964
T N2 APARTMENT DIRECT AIR 0.221673
T S1 APARTMENT DIRECT AIR 0.226153
T S2 APARTMENT DIRECT AIR 0.226488


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.241276
AIRLOOP G NW MAIN BRANCH 0.255539
AIRLOOP OFFICE MAIN BRANCH 0.333019
AIRLOOP G NE MAIN BRANCH 0.202794
AIRLOOP G N1 MAIN BRANCH 0.133702
AIRLOOP G N2 MAIN BRANCH 0.132367
AIRLOOP G S1 MAIN BRANCH 0.114106
AIRLOOP G S2 MAIN BRANCH 0.119052
AIRLOOP F2 SW MAIN BRANCH 0.291236
AIRLOOP F2 NW MAIN BRANCH 0.306607
AIRLOOP F2 SE MAIN BRANCH 0.261354
AIRLOOP F2 NE MAIN BRANCH 0.245436
AIRLOOP F2 N1 MAIN BRANCH 0.167209
AIRLOOP F2 N2 MAIN BRANCH 0.166145
AIRLOOP F2 S1 MAIN BRANCH 0.146383
AIRLOOP F2 S2 MAIN BRANCH 0.146915
AIRLOOP F3 SW MAIN BRANCH 0.292255
AIRLOOP F3 NW MAIN BRANCH 0.307680
AIRLOOP F3 SE MAIN BRANCH 0.243375
AIRLOOP F3 NE MAIN BRANCH 0.246649
AIRLOOP F3 N1 MAIN BRANCH 0.169609
AIRLOOP F3 N2 MAIN BRANCH 0.168548
AIRLOOP F3 S1 MAIN BRANCH 0.148924
AIRLOOP F3 S2 MAIN BRANCH 0.148815
AIRLOOP F4 SW MAIN BRANCH 0.293716
AIRLOOP F4 NW MAIN BRANCH 0.308980
AIRLOOP F4 SE MAIN BRANCH 0.242248
AIRLOOP F4 NE MAIN BRANCH 0.247145
AIRLOOP F4 N1 MAIN BRANCH 0.171269
AIRLOOP F4 N2 MAIN BRANCH 0.170209
AIRLOOP F4 S1 MAIN BRANCH 0.150837
AIRLOOP F4 S2 MAIN BRANCH 0.150556
AIRLOOP M SW MAIN BRANCH 0.296945
AIRLOOP M NW MAIN BRANCH 0.312163
AIRLOOP M SE MAIN BRANCH 0.244615
AIRLOOP M NE MAIN BRANCH 0.249668
AIRLOOP M N1 MAIN BRANCH 0.174602
AIRLOOP M N2 MAIN BRANCH 0.173544
AIRLOOP M S1 MAIN BRANCH 0.154268
AIRLOOP M S2 MAIN BRANCH 0.153947
AIRLOOP F6 SW MAIN BRANCH 0.294740
AIRLOOP F6 NW MAIN BRANCH 0.309751
AIRLOOP F6 SE MAIN BRANCH 0.241890
AIRLOOP F6 NE MAIN BRANCH 0.246781
AIRLOOP F6 N1 MAIN BRANCH 0.172500
AIRLOOP F6 N2 MAIN BRANCH 0.171447
AIRLOOP F6 S1 MAIN BRANCH 0.152451
AIRLOOP F6 S2 MAIN BRANCH 0.152098
AIRLOOP F7 SW MAIN BRANCH 0.294444
AIRLOOP F7 NW MAIN BRANCH 0.309371
AIRLOOP F7 SE MAIN BRANCH 0.241131
AIRLOOP F7 NE MAIN BRANCH 0.245956
AIRLOOP F7 N1 MAIN BRANCH 0.172309
AIRLOOP F7 N2 MAIN BRANCH 0.171273
AIRLOOP F7 S1 MAIN BRANCH 0.152403
AIRLOOP F7 S2 MAIN BRANCH 0.152032
AIRLOOP F8 SW MAIN BRANCH 0.295390
AIRLOOP F8 NW MAIN BRANCH 0.310252
AIRLOOP F8 SE MAIN BRANCH 0.241599
AIRLOOP F8 NE MAIN BRANCH 0.246352
AIRLOOP F8 N1 MAIN BRANCH 0.173363
AIRLOOP F8 N2 MAIN BRANCH 0.172335
AIRLOOP F8 S1 MAIN BRANCH 0.153570
AIRLOOP F8 S2 MAIN BRANCH 0.153110
AIRLOOP F9 SW MAIN BRANCH 0.305011
AIRLOOP F9 NW MAIN BRANCH 0.320069
AIRLOOP F9 SE MAIN BRANCH 0.246484
AIRLOOP F9 NE MAIN BRANCH 0.250954
AIRLOOP F9 N1 MAIN BRANCH 0.182223
AIRLOOP F9 N2 MAIN BRANCH 0.181170
AIRLOOP F9 S1 MAIN BRANCH 0.162442
AIRLOOP F9 S2 MAIN BRANCH 0.161433
AIRLOOP T SW MAIN BRANCH 0.367908
AIRLOOP T NW MAIN BRANCH 0.378428
AIRLOOP T SE MAIN BRANCH 0.304103
AIRLOOP T NE MAIN BRANCH 0.305700
AIRLOOP T N1 MAIN BRANCH 0.223964
AIRLOOP T N2 MAIN BRANCH 0.221673
AIRLOOP T S1 MAIN BRANCH 0.226153
AIRLOOP T S2 MAIN BRANCH 0.226488


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.241276
AIRLOOP G NW 0.255539
AIRLOOP OFFICE 0.333019
AIRLOOP G NE 0.202794
AIRLOOP G N1 0.133702
AIRLOOP G N2 0.132367
AIRLOOP G S1 0.114106
AIRLOOP G S2 0.119052
AIRLOOP F2 SW 0.291236
AIRLOOP F2 NW 0.306607
AIRLOOP F2 SE 0.261354
AIRLOOP F2 NE 0.245436
AIRLOOP F2 N1 0.167209
AIRLOOP F2 N2 0.166145
AIRLOOP F2 S1 0.146383
AIRLOOP F2 S2 0.146915
AIRLOOP F3 SW 0.292255
AIRLOOP F3 NW 0.307680
AIRLOOP F3 SE 0.243375
AIRLOOP F3 NE 0.246649
AIRLOOP F3 N1 0.169609
AIRLOOP F3 N2 0.168548
AIRLOOP F3 S1 0.148924
AIRLOOP F3 S2 0.148815
AIRLOOP F4 SW 0.293716
AIRLOOP F4 NW 0.308980
AIRLOOP F4 SE 0.242248
AIRLOOP F4 NE 0.247145
AIRLOOP F4 N1 0.171269
AIRLOOP F4 N2 0.170209
AIRLOOP F4 S1 0.150837
AIRLOOP F4 S2 0.150556
AIRLOOP M SW 0.296945
AIRLOOP M NW 0.312163
AIRLOOP M SE 0.244615
AIRLOOP M NE 0.249668
AIRLOOP M N1 0.174602
AIRLOOP M N2 0.173544
AIRLOOP M S1 0.154268
AIRLOOP M S2 0.153947
AIRLOOP F6 SW 0.294740
AIRLOOP F6 NW 0.309751
AIRLOOP F6 SE 0.241890
AIRLOOP F6 NE 0.246781
AIRLOOP F6 N1 0.172500
AIRLOOP F6 N2 0.171447
AIRLOOP F6 S1 0.152451
AIRLOOP F6 S2 0.152098
AIRLOOP F7 SW 0.294444
AIRLOOP F7 NW 0.309371
AIRLOOP F7 SE 0.241131
AIRLOOP F7 NE 0.245956
AIRLOOP F7 N1 0.172309
AIRLOOP F7 N2 0.171273
AIRLOOP F7 S1 0.152403
AIRLOOP F7 S2 0.152032
AIRLOOP F8 SW 0.295390
AIRLOOP F8 NW 0.310252
AIRLOOP F8 SE 0.241599
AIRLOOP F8 NE 0.246352
AIRLOOP F8 N1 0.173363
AIRLOOP F8 N2 0.172335
AIRLOOP F8 S1 0.153570
AIRLOOP F8 S2 0.153110
AIRLOOP F9 SW 0.305011
AIRLOOP F9 NW 0.320069
AIRLOOP F9 SE 0.246484
AIRLOOP F9 NE 0.250954
AIRLOOP F9 N1 0.182223
AIRLOOP F9 N2 0.181170
AIRLOOP F9 S1 0.162442
AIRLOOP F9 S2 0.161433
AIRLOOP T SW 0.367908
AIRLOOP T NW 0.378428
AIRLOOP T SE 0.304103
AIRLOOP T NE 0.305700
AIRLOOP T N1 0.223964
AIRLOOP T N2 0.221673
AIRLOOP T S1 0.226153
AIRLOOP T S2 0.226488


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.241276 0.025952
AIRLOOP G NW OA CONTROLLER 0.255539 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.333019 0.038103
AIRLOOP G NE OA CONTROLLER 0.202794 0.025952
AIRLOOP G N1 OA CONTROLLER 0.133702 0.025952
AIRLOOP G N2 OA CONTROLLER 0.132367 0.025952
AIRLOOP G S1 OA CONTROLLER 0.114106 0.025952
AIRLOOP G S2 OA CONTROLLER 0.119052 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.291236 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.306607 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.261354 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.245436 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.167209 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.166145 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.146383 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.146915 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.292255 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.307680 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.243375 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.246649 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.169609 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.168548 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.148924 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.148815 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.293716 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.308980 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.242248 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.247145 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.171269 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.170209 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.150837 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.150556 0.025952
AIRLOOP M SW OA CONTROLLER 0.296945 0.025952
AIRLOOP M NW OA CONTROLLER 0.312163 0.025952
AIRLOOP M SE OA CONTROLLER 0.244615 0.025952
AIRLOOP M NE OA CONTROLLER 0.249668 0.025952
AIRLOOP M N1 OA CONTROLLER 0.174602 0.025952
AIRLOOP M N2 OA CONTROLLER 0.173544 0.025952
AIRLOOP M S1 OA CONTROLLER 0.154268 0.025952
AIRLOOP M S2 OA CONTROLLER 0.153947 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.294740 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.309751 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.241890 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.246781 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.172500 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.171447 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.152451 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.152098 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.294444 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.309371 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.241131 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.245956 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.172309 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.171273 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.152403 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.152032 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.295390 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.310252 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.241599 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.246352 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.173363 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.172335 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.153570 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.153110 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.305011 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.320069 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.246484 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.250954 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.182223 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.181170 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.162442 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.161433 0.025952
AIRLOOP T SW OA CONTROLLER 0.367908 0.025952
AIRLOOP T NW OA CONTROLLER 0.378428 0.025952
AIRLOOP T SE OA CONTROLLER 0.304103 0.025952
AIRLOOP T NE OA CONTROLLER 0.305700 0.025952
AIRLOOP T N1 OA CONTROLLER 0.223964 0.025952
AIRLOOP T N2 OA CONTROLLER 0.221673 0.025952
AIRLOOP T S1 OA CONTROLLER 0.226153 0.025952
AIRLOOP T S2 OA CONTROLLER 0.226488 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.241276 4657.48 3073.42 0.000102
HEAT PUMP COOLING MODE AIRLOOP G NW 0.255539 4863.02 3228.39 0.000106
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.333019 6318.01 4202.77 0.000138
HEAT PUMP COOLING MODE AIRLOOP G NE 0.202794 4067.74 2636.58 0.000089
HEAT PUMP COOLING MODE AIRLOOP G N1 0.133702 2953.10 1845.21 0.000065
HEAT PUMP COOLING MODE AIRLOOP G N2 0.132367 2932.89 1830.49 0.000064
HEAT PUMP COOLING MODE AIRLOOP G S1 0.114106 2652.61 1628.90 0.000058
HEAT PUMP COOLING MODE AIRLOOP G S2 0.119052 2760.08 1697.86 0.000060
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.291236 5520.21 3668.16 0.000121
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.306607 5743.42 3836.61 0.000125
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.261354 5069.75 3332.45 0.000111
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.245436 4824.96 3151.30 0.000105
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.167209 3525.90 2240.36 0.000077
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.166145 3509.93 2228.61 0.000077
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.146383 3211.16 2010.90 0.000070
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.146915 3250.39 2031.94 0.000071
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.292255 5618.89 3708.27 0.000123
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.307680 5843.03 3876.39 0.000128
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.243375 4884.90 3162.20 0.000107
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.246649 4921.46 3192.19 0.000108
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.169609 3606.30 2283.30 0.000079
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.168548 3590.28 2271.58 0.000078
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.148924 3291.30 2054.94 0.000072
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.148815 3320.73 2068.83 0.000073
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.293716 5701.31 3745.16 0.000125
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.308980 5924.10 3911.65 0.000129
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.242248 4925.51 3170.25 0.000108
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.247145 4991.07 3220.72 0.000109
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.171269 3664.22 2313.94 0.000080
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.170209 3648.15 2302.23 0.000080
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.150837 3351.33 2088.06 0.000073
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.150556 3378.06 2100.00 0.000074
HEAT PUMP COOLING MODE AIRLOOP M SW 0.296945 5798.04 3797.68 0.000127
HEAT PUMP COOLING MODE AIRLOOP M NW 0.312163 6020.88 3963.78 0.000132
HEAT PUMP COOLING MODE AIRLOOP M SE 0.244615 5006.93 3213.01 0.000109
HEAT PUMP COOLING MODE AIRLOOP M NE 0.249668 5075.18 3265.26 0.000111
HEAT PUMP COOLING MODE AIRLOOP M N1 0.174602 3741.14 2360.73 0.000082
HEAT PUMP COOLING MODE AIRLOOP M N2 0.173544 3725.04 2349.02 0.000081
HEAT PUMP COOLING MODE AIRLOOP M S1 0.154268 3428.91 2135.75 0.000075
HEAT PUMP COOLING MODE AIRLOOP M S2 0.153947 3454.89 2147.24 0.000075
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.294740 5807.28 3787.85 0.000127
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.309751 6027.95 3951.79 0.000132
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.241890 5004.87 3197.12 0.000109
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.246781 5071.14 3247.63 0.000111
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.172500 3732.06 2346.19 0.000082
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.171447 3715.94 2334.52 0.000081
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.152451 3422.08 2123.99 0.000075
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.152098 3447.63 2135.03 0.000075
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.294444 5839.18 3797.27 0.000128
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.309371 6059.31 3960.40 0.000132
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.241131 5027.06 3201.16 0.000110
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.245956 5092.68 3250.98 0.000111
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.172309 3748.82 2351.63 0.000082
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.171273 3738.74 2342.98 0.000082
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.152403 3439.66 2130.75 0.000075
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.152032 3464.95 2141.55 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.295390 5885.54 3819.10 0.000129
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.310252 6105.26 3981.58 0.000133
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.241599 5063.99 3217.44 0.000111
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.246352 5128.81 3266.52 0.000112
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.173363 3788.32 2372.90 0.000083
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.172335 3772.41 2361.46 0.000082
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.153570 3474.14 2150.23 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.153110 3497.97 2160.00 0.000076
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.305011 6058.01 3935.09 0.000132
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.320069 6280.73 4100.43 0.000137
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.246484 5167.55 3282.99 0.000113
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.250954 5226.28 3327.73 0.000114
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.182223 3933.58 2474.06 0.000086
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.181170 3917.41 2462.38 0.000086
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.162442 3627.29 2254.74 0.000079
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.161433 3611.35 2243.43 0.000079
HEAT PUMP COOLING MODE AIRLOOP T SW 0.367908 7019.59 4642.32 0.000153
HEAT PUMP COOLING MODE AIRLOOP T NW 0.378428 7167.59 4755.05 0.000157
HEAT PUMP COOLING MODE AIRLOOP T SE 0.304103 6064.54 3931.73 0.000132
HEAT PUMP COOLING MODE AIRLOOP T NE 0.305700 6083.65 3947.07 0.000133
HEAT PUMP COOLING MODE AIRLOOP T N1 0.223964 4575.97 2941.24 0.000100
HEAT PUMP COOLING MODE AIRLOOP T N2 0.221673 4541.53 2915.86 0.000099
HEAT PUMP COOLING MODE AIRLOOP T S1 0.226153 4636.37 2980.13 0.000101
HEAT PUMP COOLING MODE AIRLOOP T S2 0.226488 4640.93 2983.68 0.000101


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.241276 0.241276 0.241276 0.241276 4657.48 4657.48 1633.64 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.255539 0.255539 0.255539 0.255539 4863.02 4863.02 1628.22 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.333019 0.333019 0.333019 0.333019 6318.01 6318.01 2118.13 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.202794 0.202794 0.202794 0.202794 4067.74 4067.74 1630.75 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.133702 0.133702 0.133702 0.133702 2953.10 2953.10 1092.87 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.132367 0.132367 0.132367 0.132367 2932.89 2932.89 1092.92 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.114106 0.114106 0.114106 0.114106 2652.61 2652.61 1094.13 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.119052 0.119052 0.119052 0.119052 2760.08 2760.08 1099.07 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.291236 0.291236 0.291236 0.291236 5520.21 5520.21 1791.44 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.306607 0.306607 0.306607 0.306607 5743.42 5743.42 1790.24 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.261354 0.261354 0.261354 0.261354 5069.75 5069.75 1810.20 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.245436 0.245436 0.245436 0.245436 4824.96 4824.96 1790.62 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.167209 0.167209 0.167209 0.167209 3525.90 3525.90 1115.24 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.166145 0.166145 0.166145 0.166145 3509.93 3509.93 1115.25 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.146383 0.146383 0.146383 0.146383 3211.16 3211.16 1117.85 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.146915 0.146915 0.146915 0.146915 3250.39 3250.39 1119.13 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.292255 0.292255 0.292255 0.292255 5618.89 5618.89 1826.61 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.307680 0.307680 0.307680 0.307680 5843.03 5843.03 1828.78 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.243375 0.243375 0.243375 0.243375 4884.90 4884.90 1827.15 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.246649 0.246649 0.246649 0.246649 4921.46 4921.46 1827.21 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.169609 0.169609 0.169609 0.169609 3606.30 3606.30 1122.90 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.168548 0.168548 0.168548 0.168548 3590.28 3590.28 1122.86 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.148924 0.148924 0.148924 0.148924 3291.30 3291.30 1119.90 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.148815 0.148815 0.148815 0.148815 3320.73 3320.73 1120.07 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.293716 0.293716 0.293716 0.293716 5701.31 5701.31 1870.73 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.308980 0.308980 0.308980 0.308980 5924.10 5924.10 1875.55 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.242248 0.242248 0.242248 0.242248 4925.51 4925.51 1867.86 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.247145 0.247145 0.247145 0.247145 4991.07 4991.07 1872.47 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.171269 0.171269 0.171269 0.171269 3664.22 3664.22 1145.39 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.170209 0.170209 0.170209 0.170209 3648.15 3648.15 1145.31 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.150837 0.150837 0.150837 0.150837 3351.33 3351.33 1139.31 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.150556 0.150556 0.150556 0.150556 3378.06 3378.06 1139.26 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.296945 0.296945 0.296945 0.296945 5798.04 5798.04 1890.21 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.312163 0.312163 0.312163 0.312163 6020.88 6020.88 1896.05 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.244615 0.244615 0.244615 0.244615 5006.93 5006.93 1885.89 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.249668 0.249668 0.249668 0.249668 5075.18 5075.18 1891.73 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.174602 0.174602 0.174602 0.174602 3741.14 3741.14 1148.34 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.173544 0.173544 0.173544 0.173544 3725.04 3725.04 1148.22 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.154268 0.154268 0.154268 0.154268 3428.91 3428.91 1141.08 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.153947 0.153947 0.153947 0.153947 3454.89 3454.89 1140.97 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.294740 0.294740 0.294740 0.294740 5807.28 5807.28 1964.42 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.309751 0.309751 0.309751 0.309751 6027.95 6027.95 1972.77 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.241890 0.241890 0.241890 0.241890 5004.87 5004.87 1959.01 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.246781 0.246781 0.246781 0.246781 5071.14 5071.14 1967.38 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.172500 0.172500 0.172500 0.172500 3732.06 3732.06 1205.55 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.171447 0.171447 0.171447 0.171447 3715.94 3715.94 1205.41 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.152451 0.152451 0.152451 0.152451 3422.08 3422.08 1195.66 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.152098 0.152098 0.152098 0.152098 3447.63 3447.63 1195.52 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.294444 0.294444 0.294444 0.294444 5839.18 5839.18 2013.46 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.309371 0.309371 0.309371 0.309371 6059.31 6059.31 2023.00 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.241131 0.241131 0.241131 0.241131 5027.06 5027.06 2007.11 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.245956 0.245956 0.245956 0.245956 5092.68 5092.68 2016.69 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.172309 0.172309 0.172309 0.172309 3748.82 3748.82 1240.79 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.171273 0.171273 0.171273 0.171273 3738.74 3738.74 1240.63 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.152403 0.152403 0.152403 0.152403 3439.66 3439.66 1229.59 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.152032 0.152032 0.152032 0.152032 3464.95 3464.95 1229.42 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.295390 0.295390 0.295390 0.295390 5885.54 5885.54 2060.57 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.310252 0.310252 0.310252 0.310252 6105.26 6105.26 2070.97 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.241599 0.241599 0.241599 0.241599 5063.99 5063.99 2053.40 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.246352 0.246352 0.246352 0.246352 5128.81 5128.81 2063.84 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.173363 0.173363 0.173363 0.173363 3788.32 3788.32 1275.42 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.172335 0.172335 0.172335 0.172335 3772.41 3772.41 1275.23 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.153570 0.153570 0.153570 0.153570 3474.14 3474.14 1263.29 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.153110 0.153110 0.153110 0.153110 3497.97 3497.97 1263.10 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.305011 0.305011 0.305011 0.305011 6058.01 6058.01 2172.08 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.320069 0.320069 0.320069 0.320069 6280.73 6280.73 2181.16 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.246484 0.246484 0.246484 0.246484 5167.55 5167.55 2164.11 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.250954 0.250954 0.250954 0.250954 5226.28 5226.28 2173.24 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.182223 0.182223 0.182223 0.182223 3933.58 3933.58 1367.38 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.181170 0.181170 0.181170 0.181170 3917.41 3917.41 1367.17 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.162442 0.162442 0.162442 0.162442 3627.29 3627.29 1356.29 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.161433 0.161433 0.161433 0.161433 3611.35 3611.35 1356.08 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.367908 0.367908 0.367908 0.367908 7019.59 7019.59 2412.28 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.378428 0.378428 0.378428 0.378428 7167.59 7167.59 2425.75 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.304103 0.304103 0.304103 0.304103 6064.54 6064.54 2404.52 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.305700 0.305700 0.305700 0.305700 6083.65 6083.65 2418.02 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.223964 0.223964 0.223964 0.223964 4575.97 4575.97 1654.01 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.221673 0.221673 0.221673 0.221673 4541.53 4541.53 1653.79 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.226153 0.226153 0.226153 0.226153 4636.37 4636.37 1637.31 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.226488 0.226488 0.226488 0.226488 4640.93 4640.93 1637.09 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.241276
AIRLOOP G NW SUPPLY FAN 0.255539
AIRLOOP OFFICE SUPPLY FAN 0.333019
AIRLOOP G NE SUPPLY FAN 0.202794
AIRLOOP G N1 SUPPLY FAN 0.133702
AIRLOOP G N2 SUPPLY FAN 0.132367
AIRLOOP G S1 SUPPLY FAN 0.114106
AIRLOOP G S2 SUPPLY FAN 0.119052
AIRLOOP F2 SW SUPPLY FAN 0.291236
AIRLOOP F2 NW SUPPLY FAN 0.306607
AIRLOOP F2 SE SUPPLY FAN 0.261354
AIRLOOP F2 NE SUPPLY FAN 0.245436
AIRLOOP F2 N1 SUPPLY FAN 0.167209
AIRLOOP F2 N2 SUPPLY FAN 0.166145
AIRLOOP F2 S1 SUPPLY FAN 0.146383
AIRLOOP F2 S2 SUPPLY FAN 0.146915
AIRLOOP F3 SW SUPPLY FAN 0.292255
AIRLOOP F3 NW SUPPLY FAN 0.307680
AIRLOOP F3 SE SUPPLY FAN 0.243375
AIRLOOP F3 NE SUPPLY FAN 0.246649
AIRLOOP F3 N1 SUPPLY FAN 0.169609
AIRLOOP F3 N2 SUPPLY FAN 0.168548
AIRLOOP F3 S1 SUPPLY FAN 0.148924
AIRLOOP F3 S2 SUPPLY FAN 0.148815
AIRLOOP F4 SW SUPPLY FAN 0.293716
AIRLOOP F4 NW SUPPLY FAN 0.308980
AIRLOOP F4 SE SUPPLY FAN 0.242248
AIRLOOP F4 NE SUPPLY FAN 0.247145
AIRLOOP F4 N1 SUPPLY FAN 0.171269
AIRLOOP F4 N2 SUPPLY FAN 0.170209
AIRLOOP F4 S1 SUPPLY FAN 0.150837
AIRLOOP F4 S2 SUPPLY FAN 0.150556
AIRLOOP M SW SUPPLY FAN 0.296945
AIRLOOP M NW SUPPLY FAN 0.312163
AIRLOOP M SE SUPPLY FAN 0.244615
AIRLOOP M NE SUPPLY FAN 0.249668
AIRLOOP M N1 SUPPLY FAN 0.174602
AIRLOOP M N2 SUPPLY FAN 0.173544
AIRLOOP M S1 SUPPLY FAN 0.154268
AIRLOOP M S2 SUPPLY FAN 0.153947
AIRLOOP F6 SW SUPPLY FAN 0.294740
AIRLOOP F6 NW SUPPLY FAN 0.309751
AIRLOOP F6 SE SUPPLY FAN 0.241890
AIRLOOP F6 NE SUPPLY FAN 0.246781
AIRLOOP F6 N1 SUPPLY FAN 0.172500
AIRLOOP F6 N2 SUPPLY FAN 0.171447
AIRLOOP F6 S1 SUPPLY FAN 0.152451
AIRLOOP F6 S2 SUPPLY FAN 0.152098
AIRLOOP F7 SW SUPPLY FAN 0.294444
AIRLOOP F7 NW SUPPLY FAN 0.309371
AIRLOOP F7 SE SUPPLY FAN 0.241131
AIRLOOP F7 NE SUPPLY FAN 0.245956
AIRLOOP F7 N1 SUPPLY FAN 0.172309
AIRLOOP F7 N2 SUPPLY FAN 0.171273
AIRLOOP F7 S1 SUPPLY FAN 0.152403
AIRLOOP F7 S2 SUPPLY FAN 0.152032
AIRLOOP F8 SW SUPPLY FAN 0.295390
AIRLOOP F8 NW SUPPLY FAN 0.310252
AIRLOOP F8 SE SUPPLY FAN 0.241599
AIRLOOP F8 NE SUPPLY FAN 0.246352
AIRLOOP F8 N1 SUPPLY FAN 0.173363
AIRLOOP F8 N2 SUPPLY FAN 0.172335
AIRLOOP F8 S1 SUPPLY FAN 0.153570
AIRLOOP F8 S2 SUPPLY FAN 0.153110
AIRLOOP F9 SW SUPPLY FAN 0.305011
AIRLOOP F9 NW SUPPLY FAN 0.320069
AIRLOOP F9 SE SUPPLY FAN 0.246484
AIRLOOP F9 NE SUPPLY FAN 0.250954
AIRLOOP F9 N1 SUPPLY FAN 0.182223
AIRLOOP F9 N2 SUPPLY FAN 0.181170
AIRLOOP F9 S1 SUPPLY FAN 0.162442
AIRLOOP F9 S2 SUPPLY FAN 0.161433
AIRLOOP T SW SUPPLY FAN 0.367908
AIRLOOP T NW SUPPLY FAN 0.378428
AIRLOOP T SE SUPPLY FAN 0.304103
AIRLOOP T NE SUPPLY FAN 0.305700
AIRLOOP T N1 SUPPLY FAN 0.223964
AIRLOOP T N2 SUPPLY FAN 0.221673
AIRLOOP T S1 SUPPLY FAN 0.226153
AIRLOOP T S2 SUPPLY FAN 0.226488


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.241276 4657.48 0.000102
HEAT PUMP HEATING MODE AIRLOOP G NW 0.255539 4863.02 0.000106
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.333019 6318.01 0.000138
HEAT PUMP HEATING MODE AIRLOOP G NE 0.202794 4067.74 0.000089
HEAT PUMP HEATING MODE AIRLOOP G N1 0.133702 2953.10 0.000065
HEAT PUMP HEATING MODE AIRLOOP G N2 0.132367 2932.89 0.000064
HEAT PUMP HEATING MODE AIRLOOP G S1 0.114106 2652.61 0.000058
HEAT PUMP HEATING MODE AIRLOOP G S2 0.119052 2760.08 0.000060
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.291236 5520.21 0.000121
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.306607 5743.42 0.000125
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.261354 5069.75 0.000111
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.245436 4824.96 0.000105
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.167209 3525.90 0.000077
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.166145 3509.93 0.000077
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.146383 3211.16 0.000070
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.146915 3250.39 0.000071
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.292255 5618.89 0.000123
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.307680 5843.03 0.000128
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.243375 4884.90 0.000107
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.246649 4921.46 0.000108
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.169609 3606.30 0.000079
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.168548 3590.28 0.000078
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.148924 3291.30 0.000072
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.148815 3320.73 0.000073
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.293716 5701.31 0.000125
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.308980 5924.10 0.000129
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.242248 4925.51 0.000108
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.247145 4991.07 0.000109
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.171269 3664.22 0.000080
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.170209 3648.15 0.000080
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.150837 3351.33 0.000073
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.150556 3378.06 0.000074
HEAT PUMP HEATING MODE AIRLOOP M SW 0.296945 5798.04 0.000127
HEAT PUMP HEATING MODE AIRLOOP M NW 0.312163 6020.88 0.000132
HEAT PUMP HEATING MODE AIRLOOP M SE 0.244615 5006.93 0.000109
HEAT PUMP HEATING MODE AIRLOOP M NE 0.249668 5075.18 0.000111
HEAT PUMP HEATING MODE AIRLOOP M N1 0.174602 3741.14 0.000082
HEAT PUMP HEATING MODE AIRLOOP M N2 0.173544 3725.04 0.000081
HEAT PUMP HEATING MODE AIRLOOP M S1 0.154268 3428.91 0.000075
HEAT PUMP HEATING MODE AIRLOOP M S2 0.153947 3454.89 0.000075
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.294740 5807.28 0.000127
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.309751 6027.95 0.000132
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.241890 5004.87 0.000109
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.246781 5071.14 0.000111
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.172500 3732.06 0.000082
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.171447 3715.94 0.000081
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.152451 3422.08 0.000075
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.152098 3447.63 0.000075
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.294444 5839.18 0.000128
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.309371 6059.31 0.000132
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.241131 5027.06 0.000110
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.245956 5092.68 0.000111
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.172309 3748.82 0.000082
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.171273 3738.74 0.000082
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.152403 3439.66 0.000075
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.152032 3464.95 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.295390 5885.54 0.000129
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.310252 6105.26 0.000133
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.241599 5063.99 0.000111
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.246352 5128.81 0.000112
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.173363 3788.32 0.000083
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.172335 3772.41 0.000082
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.153570 3474.14 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.153110 3497.97 0.000076
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.305011 6058.01 0.000132
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.320069 6280.73 0.000137
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.246484 5167.55 0.000113
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.250954 5226.28 0.000114
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.182223 3933.58 0.000086
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.181170 3917.41 0.000086
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.162442 3627.29 0.000079
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.161433 3611.35 0.000079
HEAT PUMP HEATING MODE AIRLOOP T SW 0.367908 7019.59 0.000153
HEAT PUMP HEATING MODE AIRLOOP T NW 0.378428 7167.59 0.000157
HEAT PUMP HEATING MODE AIRLOOP T SE 0.304103 6064.54 0.000132
HEAT PUMP HEATING MODE AIRLOOP T NE 0.305700 6083.65 0.000133
HEAT PUMP HEATING MODE AIRLOOP T N1 0.223964 4575.97 0.000100
HEAT PUMP HEATING MODE AIRLOOP T N2 0.221673 4541.53 0.000099
HEAT PUMP HEATING MODE AIRLOOP T S1 0.226153 4636.37 0.000101
HEAT PUMP HEATING MODE AIRLOOP T S2 0.226488 4640.93 0.000101


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 1633.64
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 1628.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 2118.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 1630.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 1092.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 1092.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 1094.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 1099.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 1791.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 1790.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 1810.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 1790.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1115.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1115.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1117.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1119.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 1826.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 1828.78
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 1827.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 1827.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1122.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1122.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1119.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1120.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 1870.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 1875.55
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 1867.86
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 1872.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1145.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1145.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1139.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1139.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 1890.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 1896.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 1885.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 1891.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1148.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1148.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1141.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1140.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 1964.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 1972.77
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 1959.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 1967.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1205.55
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1205.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1195.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1195.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 2013.46
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 2023.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 2007.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 2016.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1240.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1240.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1229.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1229.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 2060.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 2070.97
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 2053.40
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 2063.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 1275.42
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 1275.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 1263.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 1263.10
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 2172.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 2181.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 2164.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 2173.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 1367.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 1367.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 1356.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 1356.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 2412.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 2425.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 2404.52
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 2418.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 1654.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 1653.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 1637.31
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 1637.09


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.007966 8.96


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.007966


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.007966 3845.68 10.13 11919.36


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.007966 2544.01



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 19:12:00

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.81 19.42
February 23.95 20.87
March 24.04 21.57
April 24.35 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.22 23.59
December 23.87 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.81 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.46 19.42
February 23.79 20.87
March 23.93 21.57
April 24.35 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.16 23.59
December 23.60 20.30
     
Annual Sum or Average 24.14 24.51
Minimum of Months 23.46 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 19.42
February 24.14 20.87
March 24.22 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.30 23.59
December 24.13 20.30
     
Annual Sum or Average 24.31 24.51
Minimum of Months 24.08 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 19.42
February 23.77 20.87
March 23.92 21.57
April 24.35 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.16 23.59
December 23.51 20.30
     
Annual Sum or Average 24.13 24.51
Minimum of Months 23.40 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 19.42
February 23.70 20.87
March 23.83 21.57
April 24.33 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.13 23.59
December 23.47 20.30
     
Annual Sum or Average 24.10 24.51
Minimum of Months 23.31 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 19.42
February 23.70 20.87
March 23.83 21.57
April 24.33 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.13 23.59
December 23.47 20.30
     
Annual Sum or Average 24.10 24.51
Minimum of Months 23.31 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.82 19.42
February 23.95 20.87
March 24.01 21.57
April 24.34 24.11
May 24.40 26.41
June 24.40 27.68
July 24.41 28.13
August 24.46 27.97
September 24.56 27.49
October 24.46 26.35
November 24.28 23.59
December 23.90 20.30
     
Annual Sum or Average 24.25 24.51
Minimum of Months 23.82 19.42
Maximum of Months 24.56 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 19.42
February 23.97 20.87
March 24.03 21.57
April 24.34 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.44 27.97
September 24.53 27.49
October 24.45 26.35
November 24.28 23.59
December 23.92 20.30
     
Annual Sum or Average 24.25 24.51
Minimum of Months 23.84 19.42
Maximum of Months 24.53 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.84 19.42
February 23.48 20.87
March 23.76 21.57
April 24.90 24.11
May 25.76 26.41
June 26.62 27.68
July 26.99 28.13
August 26.83 27.97
September 26.73 27.49
October 25.80 26.35
November 24.60 23.59
December 23.18 20.30
     
Annual Sum or Average 25.13 24.51
Minimum of Months 22.84 19.42
Maximum of Months 26.99 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 19.42
February 24.17 20.87
March 24.21 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.32 23.59
December 24.16 20.30
     
Annual Sum or Average 24.32 24.51
Minimum of Months 24.16 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.83 19.42
February 24.00 20.87
March 24.08 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.85 20.30
     
Annual Sum or Average 24.23 24.51
Minimum of Months 23.83 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 19.42
February 24.19 20.87
March 24.25 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.41 27.49
October 24.41 26.35
November 24.33 23.59
December 24.18 20.30
     
Annual Sum or Average 24.33 24.51
Minimum of Months 24.18 19.42
Maximum of Months 24.41 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 19.42
February 23.99 20.87
March 24.08 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.75 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.75 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 19.42
February 23.98 20.87
March 24.04 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.27 23.59
December 23.78 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.76 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 19.42
February 23.98 20.87
March 24.04 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.27 23.59
December 23.77 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.76 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 19.42
February 24.22 20.87
March 24.23 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.41 28.13
August 24.44 27.97
September 24.53 27.49
October 24.53 26.35
November 24.44 23.59
December 24.26 20.30
     
Annual Sum or Average 24.37 24.51
Minimum of Months 24.22 19.42
Maximum of Months 24.53 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.25 19.42
February 24.23 20.87
March 24.23 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.43 27.97
September 24.52 27.49
October 24.52 26.35
November 24.43 23.59
December 24.26 20.30
     
Annual Sum or Average 24.37 24.51
Minimum of Months 24.23 19.42
Maximum of Months 24.52 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.15 19.42
February 25.36 20.87
March 25.56 21.57
April 26.12 24.11
May 26.37 26.41
June 26.64 27.68
July 26.75 28.13
August 26.66 27.97
September 26.70 27.49
October 26.42 26.35
November 25.91 23.59
December 25.23 20.30
     
Annual Sum or Average 26.08 24.51
Minimum of Months 25.15 19.42
Maximum of Months 26.75 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 19.42
February 24.17 20.87
March 24.21 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.32 23.59
December 24.18 20.30
     
Annual Sum or Average 24.32 24.51
Minimum of Months 24.17 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 19.42
February 24.02 20.87
March 24.09 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.27 23.59
December 23.87 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.87 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 19.42
February 24.17 20.87
March 24.23 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.35 23.59
December 24.17 20.30
     
Annual Sum or Average 24.33 24.51
Minimum of Months 24.17 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 19.42
February 24.00 20.87
March 24.09 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.27 23.59
December 23.78 20.30
     
Annual Sum or Average 24.23 24.51
Minimum of Months 23.78 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.85 19.42
February 24.01 20.87
March 24.06 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.29 23.59
December 23.84 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.84 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.85 19.42
February 24.01 20.87
March 24.06 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.29 23.59
December 23.83 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.83 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 19.42
February 24.26 20.87
March 24.26 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.41 28.13
August 24.44 27.97
September 24.52 27.49
October 24.56 26.35
November 24.51 23.59
December 24.31 20.30
     
Annual Sum or Average 24.40 24.51
Minimum of Months 24.26 19.42
Maximum of Months 24.56 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 19.42
February 24.26 20.87
March 24.26 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.43 27.97
September 24.52 27.49
October 24.55 26.35
November 24.51 23.59
December 24.31 20.30
     
Annual Sum or Average 24.40 24.51
Minimum of Months 24.26 19.42
Maximum of Months 24.55 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.47 19.42
February 25.61 20.87
March 25.80 21.57
April 26.32 24.11
May 26.54 26.41
June 26.70 27.68
July 26.78 28.13
August 26.70 27.97
September 26.73 27.49
October 26.58 26.35
November 26.13 23.59
December 25.50 20.30
     
Annual Sum or Average 26.24 24.51
Minimum of Months 25.47 19.42
Maximum of Months 26.78 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 19.42
February 24.17 20.87
March 24.20 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.31 23.59
December 24.18 20.30
     
Annual Sum or Average 24.32 24.51
Minimum of Months 24.17 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.90 19.42
February 24.01 20.87
March 24.07 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.87 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.87 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.21 19.42
February 24.16 20.87
March 24.21 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.34 23.59
December 24.15 20.30
     
Annual Sum or Average 24.33 24.51
Minimum of Months 24.15 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.85 19.42
February 24.00 20.87
March 24.07 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.77 20.30
     
Annual Sum or Average 24.23 24.51
Minimum of Months 23.77 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 19.42
February 24.02 20.87
March 24.06 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.28 23.59
December 23.85 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.85 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 19.42
February 24.02 20.87
March 24.06 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.28 23.59
December 23.84 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.84 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 19.42
February 24.25 20.87
March 24.25 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.41 28.13
August 24.43 27.97
September 24.51 27.49
October 24.55 26.35
November 24.51 23.59
December 24.31 20.30
     
Annual Sum or Average 24.40 24.51
Minimum of Months 24.25 19.42
Maximum of Months 24.55 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 19.42
February 24.25 20.87
March 24.25 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.43 27.97
September 24.51 27.49
October 24.54 26.35
November 24.50 23.59
December 24.31 20.30
     
Annual Sum or Average 24.39 24.51
Minimum of Months 24.25 19.42
Maximum of Months 24.54 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.59 19.42
February 25.71 20.87
March 25.88 21.57
April 26.42 24.11
May 26.63 26.41
June 26.77 27.68
July 26.85 28.13
August 26.76 27.97
September 26.80 27.49
October 26.67 26.35
November 26.23 23.59
December 25.61 20.30
     
Annual Sum or Average 26.33 24.51
Minimum of Months 25.59 19.42
Maximum of Months 26.85 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.22 19.42
February 24.15 20.87
March 24.19 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.31 23.59
December 24.16 20.30
     
Annual Sum or Average 24.32 24.51
Minimum of Months 24.15 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 19.42
February 24.00 20.87
March 24.06 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.25 23.59
December 23.85 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.85 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 19.42
February 24.14 20.87
March 24.19 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.34 23.59
December 24.13 20.30
     
Annual Sum or Average 24.32 24.51
Minimum of Months 24.13 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 19.42
February 23.99 20.87
March 24.06 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.25 23.59
December 23.76 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.76 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 19.42
February 24.02 20.87
March 24.05 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.28 23.59
December 23.84 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.84 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 19.42
February 24.02 20.87
March 24.05 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.28 23.59
December 23.83 20.30
     
Annual Sum or Average 24.24 24.51
Minimum of Months 23.83 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 19.42
February 24.24 20.87
March 24.24 21.57
April 24.39 24.11
May 24.41 26.41
June 24.41 27.68
July 24.40 28.13
August 24.43 27.97
September 24.51 27.49
October 24.54 26.35
November 24.50 23.59
December 24.30 20.30
     
Annual Sum or Average 24.39 24.51
Minimum of Months 24.24 19.42
Maximum of Months 24.54 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.31 19.42
February 24.24 20.87
March 24.24 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.43 27.97
September 24.50 27.49
October 24.53 26.35
November 24.49 23.59
December 24.30 20.30
     
Annual Sum or Average 24.39 24.51
Minimum of Months 24.24 19.42
Maximum of Months 24.53 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.13 19.42
February 26.22 20.87
March 26.39 21.57
April 26.94 24.11
May 27.15 26.41
June 27.29 27.68
July 27.37 28.13
August 27.29 27.97
September 27.32 27.49
October 27.19 26.35
November 26.75 23.59
December 26.13 20.30
     
Annual Sum or Average 26.85 24.51
Minimum of Months 26.13 19.42
Maximum of Months 27.37 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.19 19.42
February 24.12 20.87
March 24.16 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.29 23.59
December 24.12 20.30
     
Annual Sum or Average 24.31 24.51
Minimum of Months 24.12 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 19.42
February 23.97 20.87
March 24.02 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.23 23.59
December 23.79 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.79 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 19.42
February 24.11 20.87
March 24.16 21.57
April 24.39 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.32 23.59
December 24.09 20.30
     
Annual Sum or Average 24.31 24.51
Minimum of Months 24.09 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 19.42
February 23.95 20.87
March 24.02 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.23 23.59
December 23.70 20.30
     
Annual Sum or Average 24.20 24.51
Minimum of Months 23.70 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.83 19.42
February 23.98 20.87
March 24.01 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.78 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.78 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.83 19.42
February 23.98 20.87
March 24.01 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 23.77 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.77 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 19.42
February 24.21 20.87
March 24.21 21.57
April 24.39 24.11
May 24.41 26.41
June 24.41 27.68
July 24.40 28.13
August 24.43 27.97
September 24.50 27.49
October 24.53 26.35
November 24.48 23.59
December 24.26 20.30
     
Annual Sum or Average 24.38 24.51
Minimum of Months 24.21 19.42
Maximum of Months 24.53 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 19.42
February 24.21 20.87
March 24.21 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.43 27.97
September 24.50 27.49
October 24.52 26.35
November 24.48 23.59
December 24.26 20.30
     
Annual Sum or Average 24.37 24.51
Minimum of Months 24.21 19.42
Maximum of Months 24.52 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.54 19.42
February 25.64 20.87
March 25.81 21.57
April 26.39 24.11
May 26.62 26.41
June 26.76 27.68
July 26.84 28.13
August 26.75 27.97
September 26.79 27.49
October 26.65 26.35
November 26.19 23.59
December 25.53 20.30
     
Annual Sum or Average 26.29 24.51
Minimum of Months 25.53 19.42
Maximum of Months 26.84 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 19.42
February 24.10 20.87
March 24.13 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.29 23.59
December 24.09 20.30
     
Annual Sum or Average 24.30 24.51
Minimum of Months 24.09 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.80 19.42
February 23.94 20.87
March 24.00 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.22 23.59
December 23.75 20.30
     
Annual Sum or Average 24.21 24.51
Minimum of Months 23.75 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 19.42
February 24.09 20.87
March 24.14 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.31 23.59
December 24.05 20.30
     
Annual Sum or Average 24.30 24.51
Minimum of Months 24.05 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 19.42
February 23.93 20.87
March 23.99 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.22 23.59
December 23.65 20.30
     
Annual Sum or Average 24.19 24.51
Minimum of Months 23.65 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.79 19.42
February 23.96 20.87
March 23.98 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.25 23.59
December 23.73 20.30
     
Annual Sum or Average 24.21 24.51
Minimum of Months 23.73 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.79 19.42
February 23.96 20.87
March 23.98 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.25 23.59
December 23.72 20.30
     
Annual Sum or Average 24.21 24.51
Minimum of Months 23.72 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.26 19.42
February 24.18 20.87
March 24.19 21.57
April 24.39 24.11
May 24.41 26.41
June 24.41 27.68
July 24.40 28.13
August 24.43 27.97
September 24.50 27.49
October 24.52 26.35
November 24.47 23.59
December 24.23 20.30
     
Annual Sum or Average 24.37 24.51
Minimum of Months 24.18 19.42
Maximum of Months 24.52 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.26 19.42
February 24.18 20.87
March 24.18 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.42 27.97
September 24.49 27.49
October 24.52 26.35
November 24.46 23.59
December 24.22 20.30
     
Annual Sum or Average 24.36 24.51
Minimum of Months 24.18 19.42
Maximum of Months 24.52 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.42 19.42
February 25.52 20.87
March 25.70 21.57
April 26.31 24.11
May 26.55 26.41
June 26.69 27.68
July 26.77 28.13
August 26.68 27.97
September 26.72 27.49
October 26.58 26.35
November 26.10 23.59
December 25.41 20.30
     
Annual Sum or Average 26.21 24.51
Minimum of Months 25.41 19.42
Maximum of Months 26.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 19.42
February 24.08 20.87
March 24.11 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.28 23.59
December 24.06 20.30
     
Annual Sum or Average 24.29 24.51
Minimum of Months 24.06 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 19.42
February 23.92 20.87
March 23.98 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.21 23.59
December 23.72 20.30
     
Annual Sum or Average 24.20 24.51
Minimum of Months 23.72 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.11 19.42
February 24.07 20.87
March 24.12 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.42 26.35
November 24.30 23.59
December 24.02 20.30
     
Annual Sum or Average 24.29 24.51
Minimum of Months 24.02 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.70 19.42
February 23.91 20.87
March 23.97 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.21 23.59
December 23.62 20.30
     
Annual Sum or Average 24.18 24.51
Minimum of Months 23.62 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 19.42
February 23.94 20.87
March 23.96 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.24 23.59
December 23.70 20.30
     
Annual Sum or Average 24.20 24.51
Minimum of Months 23.70 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.75 19.42
February 23.94 20.87
March 23.96 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.24 23.59
December 23.69 20.30
     
Annual Sum or Average 24.20 24.51
Minimum of Months 23.69 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.24 19.42
February 24.16 20.87
March 24.16 21.57
April 24.39 24.11
May 24.41 26.41
June 24.41 27.68
July 24.40 28.13
August 24.43 27.97
September 24.49 27.49
October 24.51 26.35
November 24.45 23.59
December 24.20 20.30
     
Annual Sum or Average 24.35 24.51
Minimum of Months 24.16 19.42
Maximum of Months 24.51 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.24 19.42
February 24.16 20.87
March 24.16 21.57
April 24.39 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.42 27.97
September 24.49 27.49
October 24.51 26.35
November 24.45 23.59
December 24.19 20.30
     
Annual Sum or Average 24.35 24.51
Minimum of Months 24.16 19.42
Maximum of Months 24.51 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.36 19.42
February 25.48 20.87
March 25.66 21.57
April 26.30 24.11
May 26.55 26.41
June 26.70 27.68
July 26.78 28.13
August 26.69 27.97
September 26.72 27.49
October 26.58 26.35
November 26.07 23.59
December 25.36 20.30
     
Annual Sum or Average 26.19 24.51
Minimum of Months 25.36 19.42
Maximum of Months 26.78 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.10 19.42
February 24.06 20.87
March 24.09 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.26 23.59
December 24.03 20.30
     
Annual Sum or Average 24.28 24.51
Minimum of Months 24.03 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.73 19.42
February 23.91 20.87
March 23.96 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.20 23.59
December 23.69 20.30
     
Annual Sum or Average 24.19 24.51
Minimum of Months 23.69 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.07 19.42
February 24.04 20.87
March 24.10 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.42 27.49
October 24.41 26.35
November 24.29 23.59
December 23.98 20.30
     
Annual Sum or Average 24.28 24.51
Minimum of Months 23.98 19.42
Maximum of Months 24.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.66 19.42
February 23.89 20.87
March 23.95 21.57
April 24.38 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.20 23.59
December 23.59 20.30
     
Annual Sum or Average 24.17 24.51
Minimum of Months 23.59 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.72 19.42
February 23.92 20.87
March 23.95 21.57
April 24.37 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.22 23.59
December 23.66 20.30
     
Annual Sum or Average 24.19 24.51
Minimum of Months 23.66 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 19.42
February 23.92 20.87
March 23.95 21.57
April 24.37 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.22 23.59
December 23.66 20.30
     
Annual Sum or Average 24.19 24.51
Minimum of Months 23.66 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 19.42
February 24.13 20.87
March 24.14 21.57
April 24.38 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.42 27.97
September 24.47 27.49
October 24.49 26.35
November 24.42 23.59
December 24.15 20.30
     
Annual Sum or Average 24.34 24.51
Minimum of Months 24.13 19.42
Maximum of Months 24.49 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.20 19.42
February 24.13 20.87
March 24.14 21.57
April 24.38 24.11
May 24.41 26.41
June 24.40 27.68
July 24.40 28.13
August 24.42 27.97
September 24.48 27.49
October 24.49 26.35
November 24.43 23.59
December 24.15 20.30
     
Annual Sum or Average 24.34 24.51
Minimum of Months 24.13 19.42
Maximum of Months 24.49 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.33 19.42
February 25.47 20.87
March 25.68 21.57
April 26.37 24.11
May 26.64 26.41
June 26.80 27.68
July 26.90 28.13
August 26.79 27.97
September 26.81 27.49
October 26.65 26.35
November 26.10 23.59
December 25.34 20.30
     
Annual Sum or Average 26.24 24.51
Minimum of Months 25.33 19.42
Maximum of Months 26.90 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 19.42
February 23.95 20.87
March 24.02 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.21 23.59
December 23.90 20.30
     
Annual Sum or Average 24.23 24.51
Minimum of Months 23.89 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.58 19.42
February 23.81 20.87
March 23.92 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.16 23.59
December 23.64 20.30
     
Annual Sum or Average 24.15 24.51
Minimum of Months 23.58 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.85 19.42
February 23.92 20.87
March 24.03 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.41 27.49
October 24.41 26.35
November 24.23 23.59
December 23.86 20.30
     
Annual Sum or Average 24.22 24.51
Minimum of Months 23.85 19.42
Maximum of Months 24.41 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.53 19.42
February 23.79 20.87
March 23.91 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.16 23.59
December 23.55 20.30
     
Annual Sum or Average 24.14 24.51
Minimum of Months 23.53 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.57 19.42
February 23.82 20.87
March 23.90 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.17 23.59
December 23.60 20.30
     
Annual Sum or Average 24.15 24.51
Minimum of Months 23.57 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.57 19.42
February 23.82 20.87
March 23.90 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.40 27.49
October 24.40 26.35
November 24.17 23.59
December 23.59 20.30
     
Annual Sum or Average 24.15 24.51
Minimum of Months 23.57 19.42
Maximum of Months 24.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.00 19.42
February 24.02 20.87
March 24.05 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.43 27.49
October 24.43 26.35
November 24.30 23.59
December 23.99 20.30
     
Annual Sum or Average 24.27 24.51
Minimum of Months 23.99 19.42
Maximum of Months 24.43 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.99 19.42
February 24.02 20.87
March 24.05 21.57
April 24.36 24.11
May 24.40 26.41
June 24.40 27.68
July 24.40 28.13
August 24.40 27.97
September 24.43 27.49
October 24.44 26.35
November 24.31 23.59
December 23.98 20.30
     
Annual Sum or Average 24.27 24.51
Minimum of Months 23.98 19.42
Maximum of Months 24.44 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 19:12:00

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.77 19.42
February 26.05 20.87
March 26.33 21.57
April 27.15 24.11
May 27.52 26.41
June 27.74 27.68
July 27.88 28.13
August 27.70 27.97
September 27.71 27.49
October 27.44 26.35
November 26.76 23.59
December 25.87 20.30
     
Annual Sum or Average 27.00 24.51
Minimum of Months 25.77 19.42
Maximum of Months 27.88 28.13



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 19:12:00

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.254114E+12 163501.228 01-JAN-17:45 11327.174 57042.023 20633.287 0.000 56672.508 10364.000 2580.935 2893.490 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.244328E+12 187414.813 11-FEB-18:15 13120.457 57042.023 20633.287 0.000 78137.284 10364.000 2580.935 3549.016 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.284553E+12 180493.085 28-MAR-16:15 11327.174 57142.088 20633.287 0.000 83531.517 0.000 2580.935 3282.888 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.308116E+12 181958.946 13-APR-18:45 14401.373 51749.961 20633.287 0.000 77000.809 10364.000 2580.935 3467.556 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.358461E+12 186891.722 29-MAY-17:15 13120.457 57042.023 20633.287 0.000 87751.474 0.000 2580.935 3775.735 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.364274E+12 189609.733 26-JUN-17:30 13120.457 57042.023 20633.287 0.000 90399.348 0.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.377008E+12 189317.954 27-JUL-17:30 13120.457 57042.023 20633.287 0.000 90107.569 0.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.376337E+12 186495.844 16-AUG-16:15 11327.174 57142.088 20633.287 0.000 88971.490 0.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.363678E+12 187642.744 18-SEP-18:30 14401.373 51749.961 20633.287 0.000 82306.488 10364.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.360581E+12 182992.198 03-OCT-16:30 11327.174 57142.088 20633.287 0.000 85467.881 0.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.310467E+12 190419.011 29-NOV-18:30 13120.457 57042.023 20633.287 0.000 80892.513 10364.000 2580.935 3797.788 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.268631E+12 180299.237 08-DEC-17:30 11327.174 57142.088 20633.287 0.000 72895.303 10364.000 2580.935 3361.291 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.387055E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.244328E+12 163501.228   11327.174 51749.961 20633.287 0.000 56672.508 0.000 2580.935 2893.490 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.377008E+12 190419.011   14401.373 57142.088 20633.287 0.000 90399.348 10364.000 2580.935 3845.675 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 19:12:00

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.749307E+11 70351.581 18-JAN-07:00 0.000 0.000 0.000 70351.581 70351.581 70351.581 0.000
February 0.695859E+11 143064.745 04-FEB-07:15 0.000 0.000 0.000 143064.745 69627.488 69627.488 73437.258
March 0.724998E+11 103425.035 16-MAR-06:30 0.000 0.000 0.000 103425.035 69459.901 69459.901 33965.135
April 0.670846E+11 69164.211 01-APR-06:00 0.000 0.000 0.000 69164.211 69164.211 69164.211 0.000
May 0.662221E+11 68289.198 02-MAY-06:00 0.000 0.000 0.000 68289.198 68289.198 68289.198 0.000
June 0.618138E+11 67522.640 01-JUN-06:45 0.000 0.000 0.000 67522.640 67522.640 67522.640 0.000
July 0.628685E+11 67100.724 01-JUL-06:00 0.000 0.000 0.000 67100.724 67100.724 67100.724 0.000
August 0.634900E+11 67369.016 29-AUG-06:45 0.000 0.000 0.000 67369.016 67369.016 67369.016 0.000
September 0.634782E+11 68009.371 27-SEP-06:45 0.000 0.000 0.000 68009.371 68009.371 68009.371 0.000
October 0.685629E+11 68987.837 31-OCT-06:00 0.000 0.000 0.000 68987.837 68987.837 68987.837 0.000
November 0.693362E+11 69734.549 30-NOV-07:45 0.000 0.000 0.000 69734.549 69734.549 69734.549 0.000
December 0.739889E+11 70246.762 31-DEC-07:45 0.000 0.000 0.000 70246.762 70246.762 70246.762 0.000
                     
Annual Sum or Average 0.813862E+12     0.000 0.000 0.000        
Minimum of Months 0.618138E+11 67100.724   0.000 0.000 0.000 67100.724 67100.724 67100.724 0.000
Maximum of Months 0.749307E+11 143064.745   0.000 0.000 0.000 143064.745 70351.581 70351.581 73437.258