Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Memphis International Ap TN USA TMY3 WMO#=723340

Simulation Timestamp: 2015-09-09 19:11:14


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4622.39 589.85 654.74
Net Site Energy 4622.39 589.85 654.74
Total Source Energy 11563.59 1475.61 1637.93
Net Source Energy 11563.59 1475.61 1637.93


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 135.05 473.91 0.00 0.00 0.00 0.00
Cooling 674.94 0.00 0.00 0.00 0.00 0.00
Interior Lighting 296.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 162.95 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 599.19 0.00 0.00 0.00 0.00 0.00
Pumps 71.11 0.00 0.00 0.00 0.00 0.00
Heat Rejection 32.61 0.00 0.00 0.00 0.00 1869.94
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1002.57 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3145.91 1476.48 0.00 0.00 0.00 6648.45
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 473.91 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 135.05 0.00 0.00 0.00 0.00 0.00
Cooling General 674.94 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 242.55 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 54.01 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 162.95 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 599.19 0.00 0.00 0.00 0.00 0.00
Pumps General 71.11 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 32.61 0.00 0.00 0.00 0.00 1869.94
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1002.57 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.09 0.00 0.00 0.00 0.00 0.00
HVAC 214.29 209.14 0.00 0.00 0.00 0.94
Other 161.10 0.00 0.00 0.00 0.00 0.00
Total 445.60 209.14 0.00 0.00 0.00 0.94


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 58.64 0.00 0.00 0.00 0.00 0.00
HVAC 193.06 188.41 0.00 0.00 0.00 0.85
Other 145.13 0.00 0.00 0.00 0.00 0.00
Total 401.44 188.41 0.00 0.00 0.00 0.85


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3145.91 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3145.91 100.00
     
Total On-Site and Utility Electric Sources 3145.91 100.00
Total Electricity End Uses 3145.91 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6648.45 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6648.45 100.00
Total Water End Uses 6648.45 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 83.50
Time Setpoint Not Met During Occupied Cooling 101.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2332.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10
RunPeriod Memphis International Ap TN USA TMY3 WMO#=723340
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
Latitude [deg] 35.07
Longitude [deg] -90.0
Elevation [m] 81.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 29.5362 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 6.7128   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 13.4255   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   264.3872
Total 7836.48     23884.04   3855.02 1150.39 4.3335 39.48 8.6291
Conditioned Total 7059.89     21517.16   3752.84 1125.85 3.9979 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 7.3840   26.4387
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-AUG-18:30 31-JAN-06:00 - - - 29-AUG-17:15
Heating 0.00 294826.64 0.00 0.00 0.00 0.00
Cooling 78343.46 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14401.37 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51749.96 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19000.27 0.00 0.00 0.00 0.00 0.00
Pumps 2349.24 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3357.38 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 75821.85 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 181326.71 370648.49 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 294826.64 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 78343.46 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 11484.27 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 2917.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 51749.96 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 19000.27 0.00 0.00 0.00 0.00 0.00
Pumps General 2349.24 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 3357.38 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 75821.85 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 427.69 513.72 0.00 0.00 0.00
Cooling 2137.52 0.00 0.00 0.00 0.00
Interior Lighting 939.20 0.00 0.00 0.00 0.00
Exterior Lighting 516.07 0.00 0.00 0.00 0.00
Interior Equipment 3601.91 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1897.64 0.00 0.00 0.00 0.00
Pumps 225.20 0.00 0.00 0.00 0.00
Heat Rejection 103.29 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1086.79 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9963.08 1600.50 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 60.58 72.77 0.00 0.00 0.00
Cooling 302.77 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.10 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 268.79 0.00 0.00 0.00 0.00
Pumps 31.90 0.00 0.00 0.00 0.00
Heat Rejection 14.63 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 153.94 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1411.22 226.70 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 60.58 72.77 0.00 0.00 0.00
Cooling 302.77 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.10 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 268.79 0.00 0.00 0.00 0.00
Pumps 31.90 0.00 0.00 0.00 0.00
Heat Rejection 14.63 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 153.94 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1411.22 226.70 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB -8.30 0.00 -8.30 Wetbulb [C] 4.10 0.00
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 35.60 9.20 25.20 Wetbulb [C] 3.80 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.65_SHGC_0.25 3.36 0.00 0.00 3.36 3.36 2.848 0.287 0.200     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.65_SHGC_0.25 6.97 0.00 0.00 6.97 6.97 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.65_SHGC_0.25 10.59 0.00 0.00 10.59 10.59 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.65_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.848 0.287 0.200              
North Total or Average           423.59 2.848 0.287 0.200              
Non-North Total or Average           726.80 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
OFFICE_LIGHTS_HARDWIRED OFFICE 14.7681 88.25 1303.26 GeneralLights LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
OFFICE_LIGHTS_PLUGIN OFFICE 14.7681 88.25 1303.26 GeneralLights-plugin LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 6.7128 77.66 521.30 GeneralLights-plugin LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.2679 14974.03 33959.19               296.56


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10364.00 AstronomicalClock -   83.76 83.76 162.95
Exterior Lighting Total 10364.00           162.95



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 332898.18 0.75    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 266318.55      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4089.33 2665.72 1423.61 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4025.42 2619.30 1406.12 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   5922.42 3923.34 1999.09 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3326.60 2110.51 1216.09 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2580.22 1583.81 996.41 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2562.41 1570.95 991.46 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2729.55 1680.21 1049.34 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2815.25 1743.57 1071.68 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4927.57 3253.14 1674.44 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4837.03 3186.11 1650.92 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4665.33 3061.45 1603.88 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4070.88 2624.58 1446.30 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3099.53 1943.06 1156.47 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3085.19 1932.58 1152.60 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3283.13 2068.74 1214.39 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3312.09 2090.31 1221.78 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5012.12 3290.43 1721.70 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4929.13 3229.34 1699.78 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4472.45 2892.13 1580.32 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4174.31 2678.40 1495.90 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3176.97 1987.60 1189.38 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3162.83 1977.31 1185.52 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3358.42 2111.54 1246.88 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3370.37 2120.44 1249.92 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5082.31 3323.83 1758.48 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5001.06 3264.24 1736.82 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4512.72 2904.46 1608.26 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4242.66 2712.23 1530.43 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3230.82 2017.95 1212.86 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3216.78 2007.78 1209.01 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3407.92 2138.53 1269.39 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3417.37 2145.56 1271.80 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5169.68 3373.76 1795.92 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5090.66 3315.94 1774.73 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4636.25 2971.84 1664.41 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4329.25 2762.70 1566.55 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3304.58 2064.53 1240.05 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3290.66 2054.45 1236.22 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3477.34 2181.96 1295.38 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3486.43 2188.72 1297.71 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5169.64 3360.79 1808.85 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5090.35 3302.97 1787.38 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4640.90 2963.67 1677.23 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4326.41 2749.51 1576.90 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3292.46 2049.59 1242.87 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3278.65 2039.63 1239.02 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3464.85 2165.92 1298.93 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3472.17 2171.74 1300.43 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5194.08 3367.83 1826.25 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5115.75 3310.86 1804.89 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4669.70 2974.89 1694.81 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4355.99 2760.38 1595.61 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3306.89 2054.84 1252.05 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3293.18 2044.98 1248.20 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3476.76 2169.10 1307.66 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3483.86 2174.73 1309.13 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5235.52 3388.75 1846.78 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5158.18 3332.60 1825.58 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4714.22 2998.78 1715.43 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4396.26 2781.42 1614.84 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3339.91 2074.13 1265.78 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3326.31 2064.36 1261.95 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3506.45 2185.89 1320.56 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3513.31 2191.34 1321.97 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5413.81 3512.02 1901.80 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5338.92 3457.56 1881.36 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4863.88 3100.48 1763.40 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4503.70 2852.00 1651.71 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3498.59 2184.79 1313.80 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3484.99 2174.98 1310.00 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3630.79 2272.05 1358.74 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3639.73 2278.66 1361.07 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   6492.52 4304.98 2187.54 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6310.39 4171.76 2138.63 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5949.07 3897.03 2052.03 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5420.29 3514.43 1905.87 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4323.83 2778.60 1545.23 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4322.73 2777.92 1544.81 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4779.92 3119.96 1659.96 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4787.24 3125.54 1661.69 0.65 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4089.33 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   4025.42 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   5922.42 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   3326.60 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2580.22 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2562.41 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2729.55 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2815.25 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4927.57 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4837.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4665.33 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4070.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3099.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3085.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3283.13 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3312.09 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5012.12 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4929.13 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4472.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4174.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3176.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3162.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3358.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3370.37 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5082.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5001.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4512.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4242.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3230.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3216.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3407.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3417.37 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5169.68 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   5090.66 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   4636.25 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   4329.25 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3304.58 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3290.66 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3477.34 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3486.43 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5169.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5090.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4640.90 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4326.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3292.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3278.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3464.85 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3472.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5194.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5115.75 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4669.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4355.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3306.89 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3293.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3476.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3483.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5235.52 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5158.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4714.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4396.26 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3339.91 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3326.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3506.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3513.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5413.81 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5338.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4863.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4503.70 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3498.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3484.99 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3630.79 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3639.73 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   6492.52 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   6310.39 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   5949.07 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   5420.29 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   4323.83 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   4322.73 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4779.92 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   4787.24 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   3368.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   3370.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   4164.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   3370.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   2526.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   2526.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   2521.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   2527.68 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   3396.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   3397.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   3414.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   3397.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   2334.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   2334.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   2336.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   2337.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   3472.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   3477.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   3474.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   3477.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   2343.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   2343.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   2339.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   2339.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   3584.04 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   3592.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   3584.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   3592.00 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   2403.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   2403.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   2395.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   2395.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   3665.19 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   3674.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   3665.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   3674.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   2441.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   2441.15 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   2432.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   2432.44 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   3795.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   3807.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   3795.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   3807.37 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   2534.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   2534.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   2523.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   2523.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   3895.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   3907.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   3895.14 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   3907.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   2600.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   2600.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   2588.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   2588.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   3993.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   4007.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   3993.96 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   4007.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   2669.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   2669.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   2656.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   2656.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   4208.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   4220.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   4208.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   4220.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   2846.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   2846.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   2834.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   2834.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   4832.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   4850.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   4832.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   4850.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   3509.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   3509.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   3488.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   3488.70 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 244.02 1160.84 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 239.65 1160.84 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 366.07 1160.84 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 187.49 1160.84 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 133.01 1160.84 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 131.64 1160.84 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 141.00 1160.84 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 147.75 1160.84 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 303.29 1160.84 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 296.72 1160.84 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 283.86 1160.84 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 238.74 1160.84 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 169.03 1160.84 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 167.92 1160.84 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 180.27 1160.84 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 182.58 1160.84 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 305.16 1160.84 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 299.22 1160.84 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 263.65 1160.84 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 242.42 1160.84 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 172.53 1160.84 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 171.44 1160.84 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 183.60 1160.84 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 184.55 1160.84 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 307.14 1160.84 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 301.37 1160.84 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 263.40 1160.84 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 244.47 1160.84 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 174.83 1160.84 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 173.75 1160.84 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 185.55 1160.84 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 186.30 1160.84 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 311.18 1160.84 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 305.60 1160.84 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 267.25 1160.84 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 248.59 1160.84 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 179.03 1160.84 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 177.96 1160.84 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 189.41 1160.84 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 190.13 1160.84 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 308.69 1160.84 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 303.11 1160.84 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 265.31 1160.84 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 246.11 1160.84 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.79 1160.84 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 175.73 1160.84 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 186.97 1160.84 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 187.69 1160.84 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 308.48 1160.84 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 302.99 1160.84 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 265.57 1160.84 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 245.96 1160.84 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.78 1160.84 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 175.74 1160.84 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 186.75 1160.84 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 187.44 1160.84 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 309.84 1160.84 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 304.44 1160.84 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 267.27 1160.84 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 247.36 1160.84 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.32 1160.84 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 177.29 1160.84 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.02 1160.84 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.70 1160.84 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 322.19 1160.84 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 316.96 1160.84 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 277.29 1160.84 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 254.09 1160.84 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 189.61 1160.84 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.58 1160.84 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 196.68 1160.84 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 197.38 1160.84 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 405.03 1160.84 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 391.62 1160.84 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 361.39 1160.84 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 323.01 1160.84 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 249.98 1160.84 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 249.92 1160.84 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 286.52 1160.84 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 287.12 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 224180.02 0.0072 2312.31 319344.75 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2215.53 2658.64 0.175 0.210 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
G NW APARTMENT 2175.88 2611.05 0.172 0.206 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
OFFICE 3323.73 3988.47 0.263 0.315 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 33.48 0.01615
G NE APARTMENT 1702.21 2042.65 0.135 0.162 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 32.10 0.01615
G N1 APARTMENT 1207.70 1449.24 0.095 0.115 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.70 0.01615
G N2 APARTMENT 1195.31 1434.38 0.095 0.113 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.70 0.01615
G S1 APARTMENT 1280.26 1536.32 0.101 0.121 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
G S2 APARTMENT 1341.50 1609.81 0.106 0.127 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F2 SW APARTMENT 2753.54 3304.24 0.218 0.261 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F2 NW APARTMENT 2693.96 3232.76 0.213 0.256 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F2 SE APARTMENT 2577.10 3092.52 0.204 0.245 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.71 0.01615
F2 NE APARTMENT 2167.50 2601.00 0.171 0.206 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
F2 N1 APARTMENT 1534.73 1841.68 0.121 0.146 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F2 N2 APARTMENT 1524.64 1829.57 0.121 0.145 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F2 S1 APARTMENT 1636.79 1964.15 0.129 0.155 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F2 S2 APARTMENT 1657.70 1989.24 0.131 0.157 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F3 SW APARTMENT 2770.39 3324.47 0.219 0.263 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F3 NW APARTMENT 2716.63 3259.96 0.215 0.258 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F3 SE APARTMENT 2393.52 2872.22 0.189 0.227 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.71 0.01615
F3 NE APARTMENT 2200.78 2640.93 0.174 0.209 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
F3 N1 APARTMENT 1566.50 1879.79 0.124 0.149 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F3 N2 APARTMENT 1556.59 1867.91 0.123 0.148 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F3 S1 APARTMENT 1666.95 2000.34 0.132 0.158 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F3 S2 APARTMENT 1675.60 2010.72 0.132 0.159 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F4 SW APARTMENT 2788.33 3346.00 0.220 0.265 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F4 NW APARTMENT 2736.05 3283.26 0.216 0.260 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F4 SE APARTMENT 2391.22 2869.46 0.189 0.227 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.71 0.01615
F4 NE APARTMENT 2219.40 2663.28 0.176 0.211 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
F4 N1 APARTMENT 1587.36 1904.84 0.126 0.151 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F4 N2 APARTMENT 1577.58 1893.10 0.125 0.150 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F4 S1 APARTMENT 1684.60 2021.52 0.133 0.160 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F4 S2 APARTMENT 1691.44 2029.73 0.134 0.160 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
M SW APARTMENT 2824.95 3389.94 0.223 0.268 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
M NW APARTMENT 2774.40 3329.28 0.219 0.263 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
M SE APARTMENT 2426.17 2911.41 0.192 0.230 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
M NE APARTMENT 2256.76 2708.11 0.178 0.214 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
M N1 APARTMENT 1625.49 1950.59 0.129 0.154 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
M N2 APARTMENT 1615.81 1938.97 0.128 0.153 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
M S1 APARTMENT 1719.65 2063.58 0.136 0.163 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
M S2 APARTMENT 1726.23 2071.48 0.136 0.164 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F6 SW APARTMENT 2802.34 3362.81 0.222 0.266 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F6 NW APARTMENT 2751.82 3302.19 0.218 0.261 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F6 SE APARTMENT 2408.55 2890.26 0.190 0.229 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F6 NE APARTMENT 2234.17 2681.00 0.177 0.212 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
F6 N1 APARTMENT 1605.13 1926.16 0.127 0.152 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F6 N2 APARTMENT 1595.57 1914.69 0.126 0.151 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F6 S1 APARTMENT 1697.49 2036.98 0.134 0.161 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
F6 S2 APARTMENT 1704.00 2044.80 0.135 0.162 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F7 SW APARTMENT 2800.36 3360.43 0.221 0.266 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F7 NW APARTMENT 2750.69 3300.82 0.218 0.261 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F7 SE APARTMENT 2410.86 2893.03 0.191 0.229 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F7 NE APARTMENT 2232.82 2679.38 0.177 0.212 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.79 0.01615
F7 N1 APARTMENT 1605.03 1926.04 0.127 0.152 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F7 N2 APARTMENT 1595.58 1914.69 0.126 0.151 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F7 S1 APARTMENT 1695.45 2034.54 0.134 0.161 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
F7 S2 APARTMENT 1701.76 2042.11 0.135 0.161 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F8 SW APARTMENT 2812.71 3375.25 0.222 0.267 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F8 NW APARTMENT 2763.85 3316.62 0.219 0.262 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F8 SE APARTMENT 2426.26 2911.51 0.192 0.230 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F8 NE APARTMENT 2245.49 2694.59 0.178 0.213 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.79 0.01615
F8 N1 APARTMENT 1619.02 1942.83 0.128 0.154 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F8 N2 APARTMENT 1609.67 1931.60 0.127 0.153 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F8 S1 APARTMENT 1707.04 2048.44 0.135 0.162 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
F8 S2 APARTMENT 1713.17 2055.80 0.135 0.163 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F9 SW APARTMENT 2924.71 3509.66 0.231 0.278 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
F9 NW APARTMENT 2877.49 3452.99 0.228 0.273 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.85 0.01615
F9 SE APARTMENT 2517.20 3020.64 0.199 0.239 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
F9 NE APARTMENT 2306.50 2767.80 0.182 0.219 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.79 0.01615
F9 N1 APARTMENT 1721.54 2065.85 0.136 0.163 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F9 N2 APARTMENT 1712.14 2054.56 0.135 0.162 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
F9 S1 APARTMENT 1785.56 2142.67 0.141 0.169 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
F9 S2 APARTMENT 1791.99 2150.39 0.142 0.170 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
T SW APARTMENT 3676.59 4411.91 0.291 0.349 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 35.32 0.01615
T NW APARTMENT 3554.88 4265.86 0.281 0.337 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 34.68 0.01615
T SE APARTMENT 3280.53 3936.63 0.259 0.311 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
T NE APARTMENT 2932.11 3518.53 0.232 0.278 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 33.48 0.01615
T N1 APARTMENT 2269.46 2723.35 0.179 0.215 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.60 0.01615
T N2 APARTMENT 2268.91 2722.69 0.179 0.215 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.60 0.01615
T S1 APARTMENT 2601.18 3121.42 0.206 0.247 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
T S2 APARTMENT 2606.66 3128.00 0.206 0.247 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2059.23 2471.07 0.093 0.111 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G NW APARTMENT 2060.97 2473.17 0.093 0.111 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
OFFICE 2363.04 2835.64 0.106 0.127 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -8.30 0.00188
G NE APARTMENT 2060.97 2473.17 0.093 0.111 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G N1 APARTMENT 1347.75 1617.30 0.061 0.073 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G N2 APARTMENT 1347.75 1617.30 0.061 0.073 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G S1 APARTMENT 1343.11 1611.73 0.060 0.072 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G S2 APARTMENT 1348.41 1618.09 0.061 0.073 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
F2 SW APARTMENT 2083.05 2499.67 0.094 0.112 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 NW APARTMENT 2083.62 2500.34 0.094 0.112 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 SE APARTMENT 2098.70 2518.45 0.094 0.113 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 NE APARTMENT 2083.62 2500.34 0.094 0.112 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 N1 APARTMENT 1184.91 1421.89 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 N2 APARTMENT 1184.91 1421.89 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 S1 APARTMENT 1186.62 1423.95 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F2 S2 APARTMENT 1187.64 1425.17 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 SW APARTMENT 2147.15 2576.58 0.096 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 NW APARTMENT 2151.38 2581.65 0.097 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 SE APARTMENT 2148.85 2578.62 0.097 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 NE APARTMENT 2151.38 2581.65 0.097 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 N1 APARTMENT 1193.04 1431.64 0.054 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 N2 APARTMENT 1193.04 1431.64 0.054 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 S1 APARTMENT 1189.40 1427.28 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F3 S2 APARTMENT 1189.55 1427.47 0.053 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 SW APARTMENT 2241.80 2690.16 0.101 0.121 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 NW APARTMENT 2248.53 2698.24 0.101 0.121 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 SE APARTMENT 2241.98 2690.37 0.101 0.121 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 NE APARTMENT 2248.53 2698.24 0.101 0.121 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 N1 APARTMENT 1243.18 1491.82 0.056 0.067 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 N2 APARTMENT 1243.18 1491.82 0.056 0.067 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 S1 APARTMENT 1236.77 1484.13 0.056 0.067 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F4 S2 APARTMENT 1236.80 1484.16 0.056 0.067 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M SW APARTMENT 2310.43 2772.52 0.104 0.125 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M NW APARTMENT 2318.01 2781.62 0.104 0.125 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M SE APARTMENT 2310.45 2772.54 0.104 0.125 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M NE APARTMENT 2318.01 2781.62 0.104 0.125 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M N1 APARTMENT 1275.28 1530.33 0.057 0.069 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M N2 APARTMENT 1275.28 1530.33 0.057 0.069 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M S1 APARTMENT 1267.92 1521.50 0.057 0.068 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
M S2 APARTMENT 1267.92 1521.50 0.057 0.068 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 SW APARTMENT 2420.98 2905.18 0.109 0.130 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 NW APARTMENT 2430.67 2916.81 0.109 0.131 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 SE APARTMENT 2420.98 2905.18 0.109 0.130 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 NE APARTMENT 2430.67 2916.81 0.109 0.131 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 N1 APARTMENT 1354.12 1624.95 0.061 0.073 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 N2 APARTMENT 1354.12 1624.95 0.061 0.073 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 S1 APARTMENT 1344.65 1613.58 0.060 0.072 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F6 S2 APARTMENT 1344.65 1613.58 0.060 0.072 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 SW APARTMENT 2504.90 3005.88 0.113 0.135 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 NW APARTMENT 2515.55 3018.66 0.113 0.136 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 SE APARTMENT 2504.90 3005.88 0.113 0.135 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 NE APARTMENT 2515.55 3018.66 0.113 0.136 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 N1 APARTMENT 1410.18 1692.21 0.063 0.076 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 N2 APARTMENT 1410.18 1692.21 0.063 0.076 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 S1 APARTMENT 1399.74 1679.69 0.063 0.075 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F7 S2 APARTMENT 1399.74 1679.69 0.063 0.075 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 SW APARTMENT 2588.47 3106.17 0.116 0.140 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 NW APARTMENT 2599.70 3119.64 0.117 0.140 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 SE APARTMENT 2588.47 3106.17 0.116 0.140 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 NE APARTMENT 2599.70 3119.64 0.117 0.140 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 N1 APARTMENT 1468.60 1762.32 0.066 0.079 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 N2 APARTMENT 1468.60 1762.32 0.066 0.079 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 S1 APARTMENT 1457.56 1749.08 0.065 0.079 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F8 S2 APARTMENT 1457.56 1749.08 0.065 0.079 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 SW APARTMENT 2770.10 3324.12 0.124 0.149 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 NW APARTMENT 2779.85 3335.82 0.125 0.150 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 SE APARTMENT 2770.10 3324.12 0.124 0.149 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 NE APARTMENT 2779.85 3335.82 0.125 0.150 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 N1 APARTMENT 1618.27 1941.93 0.073 0.087 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 N2 APARTMENT 1618.27 1941.93 0.073 0.087 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 S1 APARTMENT 1608.35 1930.02 0.072 0.087 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
F9 S2 APARTMENT 1608.35 1930.02 0.072 0.087 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T SW APARTMENT 3297.92 3957.50 0.148 0.178 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T NW APARTMENT 3313.03 3975.63 0.149 0.179 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T SE APARTMENT 3297.92 3957.50 0.148 0.178 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T NE APARTMENT 3313.03 3975.63 0.149 0.179 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T N1 APARTMENT 2178.92 2614.70 0.098 0.117 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T N2 APARTMENT 2178.92 2614.70 0.098 0.117 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T S1 APARTMENT 2161.17 2593.40 0.097 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188
T S2 APARTMENT 2161.17 2593.40 0.097 0.116 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -8.30 0.00188


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.21 0.21 0.11 0.11
AIRLOOP G NW 0.21 0.21 0.11 0.11
AIRLOOP OFFICE 0.32 0.32 0.13 0.13
AIRLOOP G NE 0.16 0.16 0.11 0.11
AIRLOOP G N1 0.11 0.11 0.07 0.07
AIRLOOP G N2 0.11 0.11 0.07 0.07
AIRLOOP G S1 0.12 0.12 0.07 0.07
AIRLOOP G S2 0.13 0.13 0.07 0.07
AIRLOOP F2 SW 0.26 0.26 0.11 0.11
AIRLOOP F2 NW 0.26 0.26 0.11 0.11
AIRLOOP F2 SE 0.24 0.24 0.11 0.11
AIRLOOP F2 NE 0.21 0.21 0.11 0.11
AIRLOOP F2 N1 0.15 0.15 0.06 0.06
AIRLOOP F2 N2 0.14 0.14 0.06 0.06
AIRLOOP F2 S1 0.16 0.16 0.06 0.06
AIRLOOP F2 S2 0.16 0.16 0.06 0.06
AIRLOOP F3 SW 0.26 0.26 0.12 0.12
AIRLOOP F3 NW 0.26 0.26 0.12 0.12
AIRLOOP F3 SE 0.23 0.23 0.12 0.12
AIRLOOP F3 NE 0.21 0.21 0.12 0.12
AIRLOOP F3 N1 0.15 0.15 0.06 0.06
AIRLOOP F3 N2 0.15 0.15 0.06 0.06
AIRLOOP F3 S1 0.16 0.16 0.06 0.06
AIRLOOP F3 S2 0.16 0.16 0.06 0.06
AIRLOOP F4 SW 0.26 0.26 0.12 0.12
AIRLOOP F4 NW 0.26 0.26 0.12 0.12
AIRLOOP F4 SE 0.23 0.23 0.12 0.12
AIRLOOP F4 NE 0.21 0.21 0.12 0.12
AIRLOOP F4 N1 0.15 0.15 0.07 0.07
AIRLOOP F4 N2 0.15 0.15 0.07 0.07
AIRLOOP F4 S1 0.16 0.16 0.07 0.07
AIRLOOP F4 S2 0.16 0.16 0.07 0.07
AIRLOOP M SW 0.27 0.27 0.12 0.12
AIRLOOP M NW 0.26 0.26 0.12 0.12
AIRLOOP M SE 0.23 0.23 0.12 0.12
AIRLOOP M NE 0.21 0.21 0.12 0.12
AIRLOOP M N1 0.15 0.15 0.07 0.07
AIRLOOP M N2 0.15 0.15 0.07 0.07
AIRLOOP M S1 0.16 0.16 0.07 0.07
AIRLOOP M S2 0.16 0.16 0.07 0.07
AIRLOOP F6 SW 0.27 0.27 0.13 0.13
AIRLOOP F6 NW 0.26 0.26 0.13 0.13
AIRLOOP F6 SE 0.23 0.23 0.13 0.13
AIRLOOP F6 NE 0.21 0.21 0.13 0.13
AIRLOOP F6 N1 0.15 0.15 0.07 0.07
AIRLOOP F6 N2 0.15 0.15 0.07 0.07
AIRLOOP F6 S1 0.16 0.16 0.07 0.07
AIRLOOP F6 S2 0.16 0.16 0.07 0.07
AIRLOOP F7 SW 0.27 0.27 0.14 0.14
AIRLOOP F7 NW 0.26 0.26 0.14 0.14
AIRLOOP F7 SE 0.23 0.23 0.14 0.14
AIRLOOP F7 NE 0.21 0.21 0.14 0.14
AIRLOOP F7 N1 0.15 0.15 0.08 0.08
AIRLOOP F7 N2 0.15 0.15 0.08 0.08
AIRLOOP F7 S1 0.16 0.16 0.08 0.08
AIRLOOP F7 S2 0.16 0.16 0.08 0.08
AIRLOOP F8 SW 0.27 0.27 0.14 0.14
AIRLOOP F8 NW 0.26 0.26 0.14 0.14
AIRLOOP F8 SE 0.23 0.23 0.14 0.14
AIRLOOP F8 NE 0.21 0.21 0.14 0.14
AIRLOOP F8 N1 0.15 0.15 0.08 0.08
AIRLOOP F8 N2 0.15 0.15 0.08 0.08
AIRLOOP F8 S1 0.16 0.16 0.08 0.08
AIRLOOP F8 S2 0.16 0.16 0.08 0.08
AIRLOOP F9 SW 0.28 0.28 0.15 0.15
AIRLOOP F9 NW 0.27 0.27 0.15 0.15
AIRLOOP F9 SE 0.24 0.24 0.15 0.15
AIRLOOP F9 NE 0.22 0.22 0.15 0.15
AIRLOOP F9 N1 0.16 0.16 0.09 0.09
AIRLOOP F9 N2 0.16 0.16 0.09 0.09
AIRLOOP F9 S1 0.17 0.17 0.09 0.09
AIRLOOP F9 S2 0.17 0.17 0.09 0.09
AIRLOOP T SW 0.35 0.35 0.18 0.18
AIRLOOP T NW 0.34 0.34 0.18 0.18
AIRLOOP T SE 0.31 0.31 0.18 0.18
AIRLOOP T NE 0.28 0.28 0.18 0.18
AIRLOOP T N1 0.22 0.22 0.12 0.12
AIRLOOP T N2 0.22 0.22 0.12 0.12
AIRLOOP T S1 0.25 0.25 0.12 0.12
AIRLOOP T S2 0.25 0.25 0.12 0.12



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4151.50 5665.00 1536.25
G NW APARTMENT 4112.00 6081.00 1772.25
OFFICE 1299.75 616.50 15.50
G NE APARTMENT 4108.00 6003.25 1672.25
G N1 APARTMENT 3756.00 6282.25 1565.00
G N2 APARTMENT 3757.50 6273.00 1557.00
G S1 APARTMENT 3833.00 5769.25 1337.50
G S2 APARTMENT 3856.00 5698.00 1315.00
F2 SW APARTMENT 4553.25 4228.50 901.00
F2 NW APARTMENT 4286.25 5020.75 1072.00
F2 SE APARTMENT 4719.50 3909.25 768.00
F2 NE APARTMENT 4269.25 5023.25 1000.75
F2 N1 APARTMENT 3991.25 5205.75 913.75
F2 N2 APARTMENT 3989.50 5208.25 910.50
F2 S1 APARTMENT 4389.25 4224.75 812.50
F2 S2 APARTMENT 4411.75 4181.00 807.75
F3 SW APARTMENT 4683.50 4029.75 882.00
F3 NW APARTMENT 4382.25 4815.50 1038.50
F3 SE APARTMENT 4730.25 3984.75 817.50
F3 NE APARTMENT 4373.75 4846.25 966.75
F3 N1 APARTMENT 4107.00 4932.25 867.00
F3 N2 APARTMENT 4104.00 4943.25 867.50
F3 S1 APARTMENT 4591.00 3899.25 781.75
F3 S2 APARTMENT 4596.75 3891.25 780.75
F4 SW APARTMENT 4717.50 4033.75 907.50
F4 NW APARTMENT 4406.75 4804.25 1066.25
F4 SE APARTMENT 4736.50 4034.50 857.25
F4 NE APARTMENT 4409.00 4812.25 991.00
F4 N1 APARTMENT 4139.00 4878.50 876.75
F4 N2 APARTMENT 4137.00 4885.75 875.50
F4 S1 APARTMENT 4642.00 3861.75 794.00
F4 S2 APARTMENT 4642.00 3860.25 793.25
M SW APARTMENT 4718.25 4064.75 911.50
M NW APARTMENT 4406.00 4800.25 1063.00
M SE APARTMENT 4729.50 4055.25 857.25
M NE APARTMENT 4411.50 4807.25 991.25
M N1 APARTMENT 4149.00 4852.00 867.75
M N2 APARTMENT 4147.50 4858.00 864.75
M S1 APARTMENT 4648.25 3870.00 790.25
M S2 APARTMENT 4646.50 3872.50 791.00
F6 SW APARTMENT 4650.50 4241.00 984.00
F6 NW APARTMENT 4365.50 4970.75 1153.75
F6 SE APARTMENT 4664.50 4207.75 920.25
F6 NE APARTMENT 4352.50 4965.50 1069.00
F6 N1 APARTMENT 4097.25 4992.00 925.25
F6 N2 APARTMENT 4092.50 5003.00 924.75
F6 S1 APARTMENT 4557.25 4065.50 842.50
F6 S2 APARTMENT 4556.00 4073.00 842.25
F7 SW APARTMENT 4601.00 4361.50 1030.75
F7 NW APARTMENT 4343.25 5070.75 1205.00
F7 SE APARTMENT 4624.25 4314.00 959.75
F7 NE APARTMENT 4328.50 5058.50 1121.00
F7 N1 APARTMENT 4066.00 5091.25 956.00
F7 N2 APARTMENT 4061.75 5099.75 954.75
F7 S1 APARTMENT 4500.25 4204.75 870.25
F7 S2 APARTMENT 4501.00 4210.75 871.00
F8 SW APARTMENT 4566.25 4453.50 1063.25
F8 NW APARTMENT 4329.50 5141.00 1242.00
F8 SE APARTMENT 4579.50 4400.75 985.50
F8 NE APARTMENT 4321.50 5127.00 1162.25
F8 N1 APARTMENT 4047.00 5162.75 977.00
F8 N2 APARTMENT 4044.50 5169.00 975.50
F8 S1 APARTMENT 4453.25 4301.50 888.25
F8 S2 APARTMENT 4454.00 4306.25 890.75
F9 SW APARTMENT 4546.50 4540.75 1105.00
F9 NW APARTMENT 4380.75 5178.50 1306.25
F9 SE APARTMENT 4569.00 4487.50 1032.50
F9 NE APARTMENT 4367.00 5164.50 1227.75
F9 N1 APARTMENT 4064.75 5205.00 1007.00
F9 N2 APARTMENT 4064.00 5211.25 1006.00
F9 S1 APARTMENT 4402.25 4406.00 903.50
F9 S2 APARTMENT 4402.00 4408.75 903.25
T SW APARTMENT 4923.25 4912.00 1648.00
T NW APARTMENT 4852.50 5436.00 1903.00
T SE APARTMENT 4937.50 4871.75 1616.00
T NE APARTMENT 4820.50 5435.00 1852.75
T N1 APARTMENT 4438.50 5448.75 1501.00
T N2 APARTMENT 4439.25 5453.75 1503.75
T S1 APARTMENT 4618.25 4731.25 1290.25
T S2 APARTMENT 4618.50 4730.75 1289.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5803.75 6417.50 2332.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 2.25 5.75 2.25 5.75
G NW APARTMENT 1.50 0.00 1.50 0.00
OFFICE 1.25 5.50 0.00 5.50
G NE APARTMENT 1.25 8.00 1.25 8.00
G N1 APARTMENT 3.50 5.75 3.50 5.75
G N2 APARTMENT 3.25 6.50 3.25 6.50
G S1 APARTMENT 3.75 69.50 3.75 69.50
G S2 APARTMENT 2.75 52.00 2.75 52.00
F2 SW APARTMENT 0.25 2.50 0.25 2.50
F2 NW APARTMENT 1.25 0.00 1.25 0.00
F2 SE APARTMENT 1.75 9.75 1.75 9.75
F2 NE APARTMENT 1.00 6.25 1.00 6.25
F2 N1 APARTMENT 4.00 4.00 4.00 4.00
F2 N2 APARTMENT 3.25 4.25 3.25 4.25
F2 S1 APARTMENT 2.00 49.25 2.00 49.25
F2 S2 APARTMENT 2.00 45.25 2.00 45.25
F3 SW APARTMENT 0.50 4.50 0.50 4.50
F3 NW APARTMENT 0.25 0.00 0.25 0.00
F3 SE APARTMENT 1.00 25.00 1.00 25.00
F3 NE APARTMENT 1.00 8.75 1.00 8.75
F3 N1 APARTMENT 4.00 7.00 4.00 7.00
F3 N2 APARTMENT 4.50 7.50 4.50 7.50
F3 S1 APARTMENT 1.00 51.25 1.00 51.25
F3 S2 APARTMENT 2.00 50.75 2.00 50.75
F4 SW APARTMENT 0.75 5.50 0.75 5.50
F4 NW APARTMENT 0.25 0.00 0.25 0.00
F4 SE APARTMENT 0.25 28.75 0.25 28.75
F4 NE APARTMENT 1.50 14.50 1.50 14.50
F4 N1 APARTMENT 3.75 8.50 3.75 8.50
F4 N2 APARTMENT 2.75 8.75 2.75 8.75
F4 S1 APARTMENT 1.25 51.25 1.25 51.25
F4 S2 APARTMENT 2.00 50.50 2.00 50.50
M SW APARTMENT 0.25 6.00 0.25 6.00
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.75 23.50 0.75 23.50
M NE APARTMENT 0.75 16.50 0.75 16.50
M N1 APARTMENT 2.75 9.00 2.75 9.00
M N2 APARTMENT 3.75 10.00 3.75 10.00
M S1 APARTMENT 1.25 50.50 1.25 50.50
M S2 APARTMENT 1.50 50.25 1.50 50.25
F6 SW APARTMENT 0.25 6.25 0.25 6.25
F6 NW APARTMENT 0.00 0.00 0.00 0.00
F6 SE APARTMENT 0.50 24.00 0.50 24.00
F6 NE APARTMENT 1.25 18.50 1.25 18.50
F6 N1 APARTMENT 3.75 9.75 3.75 9.75
F6 N2 APARTMENT 2.50 11.00 2.50 11.00
F6 S1 APARTMENT 1.50 48.50 1.50 48.50
F6 S2 APARTMENT 1.00 48.50 1.00 48.50
F7 SW APARTMENT 0.75 6.75 0.75 6.75
F7 NW APARTMENT 0.00 0.00 0.00 0.00
F7 SE APARTMENT 0.25 23.50 0.25 23.50
F7 NE APARTMENT 0.25 19.50 0.25 19.50
F7 N1 APARTMENT 3.50 11.25 3.50 11.25
F7 N2 APARTMENT 2.25 13.00 2.25 13.00
F7 S1 APARTMENT 0.75 48.25 0.75 48.25
F7 S2 APARTMENT 1.50 48.50 1.50 48.50
F8 SW APARTMENT 0.25 6.75 0.25 6.75
F8 NW APARTMENT 0.00 0.00 0.00 0.00
F8 SE APARTMENT 0.50 23.50 0.50 23.50
F8 NE APARTMENT 0.00 20.75 0.00 20.75
F8 N1 APARTMENT 2.50 12.50 2.50 12.50
F8 N2 APARTMENT 2.25 14.00 2.25 14.00
F8 S1 APARTMENT 1.75 49.25 1.75 49.25
F8 S2 APARTMENT 1.50 49.50 1.50 49.50
F9 SW APARTMENT 0.50 6.25 0.50 6.25
F9 NW APARTMENT 0.00 0.00 0.00 0.00
F9 SE APARTMENT 0.00 19.00 0.00 19.00
F9 NE APARTMENT 0.00 23.50 0.00 23.50
F9 N1 APARTMENT 0.75 9.75 0.75 9.75
F9 N2 APARTMENT 1.00 12.00 1.00 12.00
F9 S1 APARTMENT 1.25 42.25 1.25 42.25
F9 S2 APARTMENT 1.00 41.75 1.00 41.75
T SW APARTMENT 0.25 1.75 0.25 1.75
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.50 6.75 0.50 6.75
T NE APARTMENT 0.00 9.00 0.00 9.00
T N1 APARTMENT 0.50 0.25 0.50 0.25
T N2 APARTMENT 0.75 0.25 0.75 0.25
T S1 APARTMENT 1.25 8.25 1.25 8.25
T S2 APARTMENT 0.25 8.75 0.25 8.75
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 84.50 101.00 83.50 101.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.359
G NW APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.343
OFFICE 0.94 1.00 268.96 0.520 0.192 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.355 0.162 0.000 0.342
G N1 APARTMENT 1.71 2.50 268.96 0.355 0.098 0.000 0.335
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.098 0.000 0.335
G S1 APARTMENT 1.71 2.50 268.96 0.355 0.098 0.000 0.355
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.098 0.000 0.357
F2 SW APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.424
F2 NW APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.404
F2 SE APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.426
F2 NE APARTMENT 1.71 2.50 268.96 0.355 0.233 0.000 0.403
F2 N1 APARTMENT 1.71 2.50 268.96 0.355 0.140 0.000 0.399
F2 N2 APARTMENT 1.71 2.50 268.97 0.355 0.140 0.000 0.399
F2 S1 APARTMENT 1.71 2.50 268.96 0.355 0.141 0.000 0.421
F2 S2 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.422
F3 SW APARTMENT 1.71 2.50 268.96 0.355 0.276 0.000 0.469
F3 NW APARTMENT 1.71 2.50 268.96 0.355 0.276 0.000 0.447
F3 SE APARTMENT 1.71 2.50 268.96 0.355 0.276 0.000 0.469
F3 NE APARTMENT 1.71 2.50 268.96 0.355 0.276 0.000 0.447
F3 N1 APARTMENT 1.71 2.50 268.96 0.355 0.166 0.000 0.443
F3 N2 APARTMENT 1.71 2.50 268.97 0.355 0.166 0.000 0.443
F3 S1 APARTMENT 1.71 2.50 268.96 0.355 0.166 0.000 0.467
F3 S2 APARTMENT 1.71 2.50 268.97 0.355 0.166 0.000 0.468
F4 SW APARTMENT 1.71 2.50 268.96 0.355 0.308 0.000 0.487
F4 NW APARTMENT 1.71 2.50 268.96 0.355 0.308 0.000 0.465
F4 SE APARTMENT 1.71 2.50 268.96 0.355 0.308 0.000 0.487
F4 NE APARTMENT 1.71 2.50 268.96 0.355 0.308 0.000 0.464
F4 N1 APARTMENT 1.71 2.50 268.96 0.355 0.186 0.000 0.461
F4 N2 APARTMENT 1.71 2.50 268.97 0.355 0.186 0.000 0.461
F4 S1 APARTMENT 1.71 2.50 268.96 0.355 0.186 0.000 0.486
F4 S2 APARTMENT 1.71 2.50 268.97 0.355 0.186 0.000 0.486
M SW APARTMENT 1.71 2.50 268.96 0.355 0.335 0.000 0.511
M NW APARTMENT 1.71 2.50 268.96 0.355 0.335 0.000 0.488
M SE APARTMENT 1.71 2.50 268.96 0.355 0.335 0.000 0.511
M NE APARTMENT 1.71 2.50 268.96 0.355 0.335 0.000 0.487
M N1 APARTMENT 1.71 2.50 268.96 0.355 0.202 0.000 0.484
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.202 0.000 0.484
M S1 APARTMENT 1.71 2.50 268.96 0.355 0.202 0.000 0.510
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.202 0.000 0.510
F6 SW APARTMENT 1.71 2.50 268.96 0.355 0.358 0.000 0.532
F6 NW APARTMENT 1.71 2.50 268.96 0.355 0.358 0.000 0.506
F6 SE APARTMENT 1.71 2.50 268.96 0.355 0.358 0.000 0.532
F6 NE APARTMENT 1.71 2.50 268.96 0.355 0.357 0.000 0.506
F6 N1 APARTMENT 1.71 2.50 268.96 0.355 0.216 0.000 0.503
F6 N2 APARTMENT 1.71 2.50 268.97 0.355 0.216 0.000 0.503
F6 S1 APARTMENT 1.71 2.50 268.96 0.355 0.216 0.000 0.531
F6 S2 APARTMENT 1.71 2.50 268.97 0.355 0.216 0.000 0.531
F7 SW APARTMENT 1.71 2.50 268.96 0.355 0.378 0.000 0.550
F7 NW APARTMENT 1.71 2.50 268.96 0.355 0.378 0.000 0.523
F7 SE APARTMENT 1.71 2.50 268.96 0.355 0.378 0.000 0.550
F7 NE APARTMENT 1.71 2.50 268.96 0.355 0.378 0.000 0.522
F7 N1 APARTMENT 1.71 2.50 268.96 0.355 0.228 0.000 0.520
F7 N2 APARTMENT 1.71 2.50 268.97 0.355 0.228 0.000 0.520
F7 S1 APARTMENT 1.71 2.50 268.96 0.355 0.228 0.000 0.549
F7 S2 APARTMENT 1.71 2.50 268.97 0.355 0.228 0.000 0.549
F8 SW APARTMENT 1.71 2.50 268.96 0.355 0.396 0.000 0.568
F8 NW APARTMENT 1.71 2.50 268.96 0.355 0.396 0.000 0.540
F8 SE APARTMENT 1.71 2.50 268.96 0.355 0.396 0.000 0.568
F8 NE APARTMENT 1.71 2.50 268.96 0.355 0.396 0.000 0.539
F8 N1 APARTMENT 1.71 2.50 268.96 0.355 0.239 0.000 0.537
F8 N2 APARTMENT 1.71 2.50 268.97 0.355 0.239 0.000 0.537
F8 S1 APARTMENT 1.71 2.50 268.96 0.355 0.239 0.000 0.567
F8 S2 APARTMENT 1.71 2.50 268.97 0.355 0.239 0.000 0.567
F9 SW APARTMENT 1.71 2.50 268.96 0.355 0.413 0.000 0.585
F9 NW APARTMENT 1.71 2.50 268.96 0.355 0.413 0.000 0.557
F9 SE APARTMENT 1.71 2.50 268.96 0.355 0.413 0.000 0.585
F9 NE APARTMENT 1.71 2.50 268.96 0.355 0.413 0.000 0.556
F9 N1 APARTMENT 1.71 2.50 268.96 0.355 0.249 0.000 0.554
F9 N2 APARTMENT 1.71 2.50 268.97 0.355 0.249 0.000 0.554
F9 S1 APARTMENT 1.71 2.50 268.96 0.355 0.249 0.000 0.584
F9 S2 APARTMENT 1.71 2.50 268.97 0.355 0.249 0.000 0.584
T SW APARTMENT 1.71 2.50 268.96 0.355 0.428 0.000 0.599
T NW APARTMENT 1.71 2.50 268.96 0.355 0.428 0.000 0.570
T SE APARTMENT 1.71 2.50 268.96 0.355 0.428 0.000 0.599
T NE APARTMENT 1.71 2.50 268.96 0.355 0.428 0.000 0.570
T N1 APARTMENT 1.71 2.50 268.96 0.355 0.258 0.000 0.568
T N2 APARTMENT 1.71 2.50 268.97 0.355 0.258 0.000 0.568
T S1 APARTMENT 1.71 2.50 268.96 0.355 0.258 0.000 0.598
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.258 0.000 0.598
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.504 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4156
Defaulted Fields 814
Fields with Defaults 11184
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
Electricity:Building 1433.88 25760.85 01-JAN-03:15 70162.48 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 296.56 6715.87 01-JAN-00:15 14401.37 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 242.55 5824.91 01-JAN-00:15 11484.27 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 39.38 663.42 01-JAN-00:15 2934.49 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 29.88 469.18 01-JAN-00:15 2345.88 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T CORRIDOR 179.47 1701.70 01-JAN-00:15 10868.20 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 54.01 890.97 01-JAN-00:15 2917.11 01-JAN-19:15
InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.50 194.24 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 163.03 1180.40 01-JAN-00:15 10346.90 01-JAN-07:15
Fans:Electricity 599.19 19000.27 01-JAN-00:15 19000.27 01-JAN-00:30
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1445.35 19661.52 18-JAN-03:15 107444.82 21-AUG-15:15
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
ElectricityPurchased:Plant 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
Cogeneration:ElectricityPurchased 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
ElectricityNet:Plant 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
Cogeneration:ElectricityNet 3145.91 53714.57 18-MAY-05:00 181326.71 29-AUG-18:30
ExteriorLights:Electricity 162.95 0.00 01-JAN-07:15 10364.00 01-JAN-00:15
General:ExteriorLights:Electricity 162.95 0.00 01-JAN-07:15 10364.00 01-JAN-00:15
General:Fans:Electricity 599.19 19000.27 01-JAN-00:15 19000.27 01-JAN-00:30
Cooling:Electricity 674.94 0.00 01-JAN-00:15 87026.09 21-AUG-15:15
Heating:Electricity 135.05 0.00 13-JAN-17:45 77030.10 31-JAN-04:00
Electricity:Plant 103.72 36.93 13-JAN-17:45 5844.67 31-MAY-16:15
HeatRejection:Electricity 32.61 0.00 01-JAN-00:15 3495.43 31-MAY-16:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 71.11 36.93 13-JAN-17:45 2349.24 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.44 0.00 01-JAN-00:15 21.60 01-JAN-19:30
WIRED_INT_EQUIP 979.40 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1476.48 2357.00 14-JAN-24:00 370648.49 31-JAN-07:00
Gas:Plant 1476.48 2357.00 14-JAN-24:00 370648.49 31-JAN-07:00
WaterSystems:Gas 1002.57 2357.00 01-JAN-00:15 77910.06 29-JAN-08:00
Water Heater:WaterSystems:Gas 1002.57 2357.00 01-JAN-00:15 77910.06 29-JAN-08:00
Heating:Gas 473.91 0.00 10-JAN-14:30 312472.66 31-JAN-04:15
Boiler:Heating:Gas 473.91 0.00 10-JAN-14:30 312472.66 31-JAN-04:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 2981.87 0.00 01-JAN-00:15 413980.45 03-AUG-14:45
PlantLoopCoolingDemand:HVAC 2981.87 0.00 01-JAN-00:15 413980.45 03-AUG-14:45
CoolingCoils:PlantLoopCoolingDemand 2981.87 0.00 01-JAN-00:15 413980.45 03-AUG-14:45


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 6648.45 0.00 01-JAN-02:15 0.00 29-AUG-17:15
Water:Plant 6648.45 0.00 01-JAN-02:15 0.00 29-AUG-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 6648.45 0.00 01-JAN-02:15 0.00 29-AUG-17:15
MainsWater:Plant 6648.45 0.00 01-JAN-02:15 0.00 29-AUG-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 1869.94 0.00 01-JAN-00:15 0.00 29-AUG-14:15
HeatRejection:MainsWater 1869.94 0.00 01-JAN-00:15 0.00 29-AUG-14:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 1161.52 383.77 30-JUL-01:15 275230.20 31-JAN-06:15
PlantLoopHeatingDemand:Plant 777.89 383.77 30-JUL-01:15 54794.45 30-JAN-08:00
WaterSystems:PlantLoopHeatingDemand 777.89 383.77 30-JUL-01:15 54794.45 30-JAN-08:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 5676.94 4813.22 22-APR-02:00 799905.91 31-JAN-04:15
EnergyTransfer:Building 1693.26 3313.17 01-NOV-21:15 253648.02 31-JAN-04:00
EnergyTransfer:Zone:G SW APARTMENT 17.22 0.01 08-APR-04:15 2722.63 30-AUG-15:15
Heating:EnergyTransfer 364.50 0.00 26-FEB-19:45 253648.02 31-JAN-04:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 4.28 0.00 01-JAN-11:00 2556.30 31-JAN-04:00
Cooling:EnergyTransfer 1328.76 0.00 01-JAN-00:15 187379.53 10-JUL-16:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 12.94 0.00 01-JAN-00:15 2722.63 30-AUG-15:15
EnergyTransfer:Zone:G NW APARTMENT 16.78 0.02 22-OCT-00:15 2582.77 31-JAN-04:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 6.09 0.00 10-JAN-14:30 2582.77 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 10.69 0.00 01-JAN-00:15 2421.50 02-JUN-17:15
EnergyTransfer:Zone:OFFICE 25.04 0.00 03-MAY-23:30 3824.70 30-AUG-13:00
Heating:EnergyTransfer:Zone:OFFICE 2.82 0.00 01-JAN-08:30 2416.69 06-JAN-22:00
Cooling:EnergyTransfer:Zone:OFFICE 22.22 0.00 01-JAN-00:15 3824.70 30-AUG-13:00
EnergyTransfer:Zone:G NE APARTMENT 16.52 0.01 02-MAY-00:15 2592.62 31-JAN-04:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 5.86 0.00 13-JAN-10:30 2592.62 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 10.67 0.00 01-JAN-00:15 1858.55 10-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 11.43 0.01 04-OCT-10:00 1528.61 31-JAN-04:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.28 0.00 04-JAN-20:30 1528.61 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 8.15 0.00 01-JAN-00:15 1351.66 04-JUN-17:30
EnergyTransfer:Zone:G N2 APARTMENT 11.43 0.01 01-NOV-12:00 1529.08 31-JAN-04:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.28 0.00 04-JAN-20:30 1529.08 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 8.15 0.00 01-JAN-00:15 1338.31 04-JUN-17:30
EnergyTransfer:Zone:G S1 APARTMENT 12.57 0.01 13-JAN-16:30 1748.01 30-AUG-15:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 1.69 0.00 01-JAN-06:30 1469.20 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 10.87 0.00 01-JAN-00:15 1748.01 30-AUG-15:00
EnergyTransfer:Zone:G S2 APARTMENT 12.77 0.00 17-MAR-13:30 1813.59 30-AUG-14:45
Heating:EnergyTransfer:Zone:G S2 APARTMENT 1.60 0.00 01-JAN-06:30 1454.74 31-JAN-04:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 11.16 0.00 01-JAN-00:15 1813.59 30-AUG-14:45
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 23.34 0.02 02-NOV-03:45 3314.28 30-AUG-16:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 3.65 0.00 01-JAN-07:45 3067.57 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 19.69 0.00 01-JAN-00:15 3314.28 30-AUG-16:15
EnergyTransfer:Zone:F2 NW APARTMENT 21.55 0.01 23-NOV-11:15 3169.91 31-JAN-04:00
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 5.65 0.00 04-JAN-20:45 3169.91 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 15.91 0.00 01-JAN-00:15 2976.83 02-JUN-17:30
EnergyTransfer:Zone:F2 SE APARTMENT 24.42 0.06 01-DEC-16:00 3148.01 30-AUG-13:00
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 3.15 0.00 01-JAN-07:15 3012.46 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 21.27 0.00 01-JAN-00:15 3148.01 30-AUG-13:00
EnergyTransfer:Zone:F2 NE APARTMENT 21.38 0.05 08-APR-01:45 3188.67 31-JAN-04:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 5.43 0.00 04-JAN-20:45 3188.67 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 15.95 0.00 01-JAN-00:15 2370.51 10-JUL-16:30
EnergyTransfer:Zone:F2 N1 APARTMENT 14.95 0.03 29-APR-20:45 1776.51 31-JAN-04:00
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 2.31 0.00 01-JAN-06:30 1776.51 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 12.64 0.00 01-JAN-00:15 1716.11 04-JUN-17:30
EnergyTransfer:Zone:F2 N2 APARTMENT 14.95 0.02 03-NOV-11:00 1777.62 31-JAN-04:00
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 2.31 0.00 01-JAN-06:30 1777.62 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 12.64 0.00 01-JAN-00:15 1705.74 04-JUN-17:30
EnergyTransfer:Zone:F2 S1 APARTMENT 17.96 0.05 02-MAY-09:45 2188.25 30-AUG-15:00
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 1.16 0.00 01-JAN-01:00 1657.22 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 16.80 0.00 01-JAN-00:15 2188.25 30-AUG-15:00
EnergyTransfer:Zone:F2 S2 APARTMENT 18.06 0.04 15-MAR-12:00 2209.73 30-AUG-15:00
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 1.14 0.00 01-JAN-01:00 1652.86 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 16.93 0.00 01-JAN-00:15 2209.73 30-AUG-15:00
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 24.48 0.09 28-FEB-00:30 3360.97 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 3.83 0.00 01-JAN-07:45 3360.97 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 20.65 0.00 01-JAN-00:15 3328.91 30-AUG-15:15
EnergyTransfer:Zone:F3 NW APARTMENT 22.61 0.03 12-MAR-02:00 3485.68 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 5.86 0.00 04-JAN-20:30 3485.68 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 16.75 0.00 01-JAN-00:15 3015.99 02-JUN-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 24.54 0.02 18-MAR-23:00 3376.28 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 3.63 0.00 01-JAN-07:15 3376.28 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 20.91 0.00 01-JAN-00:15 3020.99 30-AUG-13:30
EnergyTransfer:Zone:F3 NE APARTMENT 22.44 0.11 08-MAR-23:45 3508.28 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 5.66 0.00 04-JAN-20:45 3508.28 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 16.79 0.00 01-JAN-00:15 2433.25 10-JUL-17:00
EnergyTransfer:Zone:F3 N1 APARTMENT 15.88 0.01 02-OCT-16:30 1931.16 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 2.29 0.00 01-JAN-03:00 1931.16 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 13.59 0.00 01-JAN-00:15 1763.26 04-JUN-17:30
EnergyTransfer:Zone:F3 N2 APARTMENT 15.88 0.00 25-MAR-08:00 1932.67 31-JAN-04:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 2.29 0.00 01-JAN-03:00 1932.67 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 13.59 0.00 01-JAN-00:15 1753.16 04-JUN-17:30
EnergyTransfer:Zone:F3 S1 APARTMENT 19.21 0.06 17-MAR-13:30 2315.49 22-OCT-13:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 1.17 0.00 01-JAN-00:45 1789.56 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 18.04 0.00 01-JAN-00:15 2315.49 22-OCT-13:00
EnergyTransfer:Zone:F3 S2 APARTMENT 19.24 0.00 04-APR-15:30 2322.91 22-OCT-13:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 1.17 0.00 01-JAN-00:45 1790.21 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 18.08 0.00 01-JAN-00:15 2322.91 22-OCT-13:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 24.97 0.02 05-MAR-01:15 3640.85 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 4.19 0.00 01-JAN-07:45 3640.85 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 20.77 0.00 01-JAN-00:15 3351.09 30-AUG-15:15
EnergyTransfer:Zone:F4 NW APARTMENT 23.19 0.02 10-OCT-08:45 3770.76 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 6.28 0.00 04-JAN-20:30 3770.76 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 16.92 0.00 01-JAN-00:15 3040.48 02-JUN-17:30
EnergyTransfer:Zone:F4 SE APARTMENT 24.89 0.12 22-DEC-01:00 3668.94 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 4.06 0.00 01-JAN-07:30 3668.94 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 20.83 0.00 01-JAN-00:15 3038.92 30-AUG-13:30
EnergyTransfer:Zone:F4 NE APARTMENT 23.03 0.02 27-APR-10:00 3795.06 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 6.08 0.00 04-JAN-20:45 3795.06 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 16.95 0.00 01-JAN-00:15 2466.05 10-JUL-17:00
EnergyTransfer:Zone:F4 N1 APARTMENT 16.27 0.01 01-NOV-10:15 2092.00 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 2.45 0.00 01-JAN-02:45 2092.00 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 13.82 0.00 01-JAN-00:15 1787.13 04-JUN-17:30
EnergyTransfer:Zone:F4 N2 APARTMENT 16.27 0.01 17-MAR-12:45 2093.68 31-JAN-04:00
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 2.45 0.00 01-JAN-03:00 2093.68 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 13.81 0.00 01-JAN-00:15 1777.29 04-JUN-17:30
EnergyTransfer:Zone:F4 S1 APARTMENT 19.58 0.01 02-MAY-12:00 2348.53 22-OCT-13:00
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 1.30 0.00 01-JAN-00:45 1947.97 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 18.28 0.00 01-JAN-00:15 2348.53 22-OCT-13:00
EnergyTransfer:Zone:F4 S2 APARTMENT 19.59 0.02 17-OCT-19:00 2354.73 22-OCT-13:00
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 1.30 0.00 01-JAN-00:45 1949.83 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 18.29 0.00 01-JAN-00:15 2354.73 22-OCT-13:00
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 25.51 0.01 16-MAR-00:15 3871.01 31-JAN-04:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 4.53 0.00 01-JAN-07:45 3871.01 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 20.99 0.00 01-JAN-00:15 3391.86 30-AUG-15:15
EnergyTransfer:Zone:M NW APARTMENT 23.87 0.01 10-NOV-16:45 3998.26 31-JAN-04:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 6.64 0.00 04-JAN-20:30 3998.26 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 17.23 0.00 01-JAN-00:15 3081.15 02-JUN-17:30
EnergyTransfer:Zone:M SE APARTMENT 25.42 0.01 05-NOV-09:45 3901.22 31-JAN-04:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 4.40 0.00 01-JAN-07:30 3901.22 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 21.02 0.00 01-JAN-00:15 3113.39 30-AUG-13:15
EnergyTransfer:Zone:M NE APARTMENT 23.70 0.00 05-OCT-09:30 4023.04 31-JAN-04:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 6.43 0.00 04-JAN-20:45 4023.04 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 17.27 0.00 01-JAN-00:15 2516.50 10-JUL-17:00
EnergyTransfer:Zone:M N1 APARTMENT 16.77 0.03 19-DEC-03:15 2220.45 31-JAN-04:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 2.61 0.00 01-JAN-02:45 2220.45 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 14.16 0.00 01-JAN-00:15 1827.95 10-JUL-17:00
EnergyTransfer:Zone:M N2 APARTMENT 16.77 0.01 17-MAY-05:45 2222.05 31-JAN-04:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 2.61 0.00 01-JAN-02:45 2222.05 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 14.16 0.00 01-JAN-00:15 1818.41 10-JUL-17:00
EnergyTransfer:Zone:M S1 APARTMENT 19.98 0.00 10-APR-19:15 2376.91 22-OCT-13:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 1.43 0.00 01-JAN-01:00 2080.46 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 18.55 0.00 01-JAN-00:15 2376.91 22-OCT-13:00
EnergyTransfer:Zone:M S2 APARTMENT 19.98 0.04 15-NOV-13:45 2382.83 22-OCT-13:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 1.43 0.00 01-JAN-01:00 2082.30 31-JAN-04:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 18.55 0.00 01-JAN-00:15 2382.83 22-OCT-13:00
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 25.34 0.06 16-NOV-04:15 4126.15 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 5.11 0.00 01-JAN-11:00 4126.15 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 20.23 0.00 01-JAN-00:15 3372.62 30-AUG-15:15
EnergyTransfer:Zone:F6 NW APARTMENT 24.04 0.08 22-FEB-23:00 4250.45 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 7.36 0.00 04-JAN-20:45 4250.45 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 16.68 0.00 01-JAN-00:15 3059.62 02-JUN-17:30
EnergyTransfer:Zone:F6 SE APARTMENT 25.23 0.00 08-MAR-23:30 4156.81 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 4.98 0.00 01-JAN-07:45 4156.81 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 20.25 0.00 01-JAN-00:15 3104.00 30-AUG-13:15
EnergyTransfer:Zone:F6 NE APARTMENT 23.86 0.02 13-MAR-03:30 4274.93 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 7.14 0.00 04-JAN-20:45 4274.93 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 16.72 0.00 01-JAN-00:15 2501.39 10-JUL-17:00
EnergyTransfer:Zone:F6 N1 APARTMENT 16.62 0.00 06-APR-09:30 2385.94 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 3.03 0.00 01-JAN-06:30 2385.94 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 13.59 0.00 01-JAN-00:15 1810.62 10-JUL-17:00
EnergyTransfer:Zone:F6 N2 APARTMENT 16.62 0.00 06-APR-20:45 2387.34 31-JAN-04:00
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 3.03 0.00 01-JAN-06:30 2387.34 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 13.59 0.00 01-JAN-00:15 1801.24 10-JUL-17:00
EnergyTransfer:Zone:F6 S1 APARTMENT 19.46 0.01 15-MAR-12:00 2338.25 22-OCT-13:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 1.69 0.00 01-JAN-01:00 2244.36 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 17.77 0.00 01-JAN-00:15 2338.25 22-OCT-13:00
EnergyTransfer:Zone:F6 S2 APARTMENT 19.46 0.02 14-OCT-18:45 2344.23 22-OCT-13:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 1.70 0.00 01-JAN-01:00 2246.17 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 17.77 0.00 01-JAN-00:15 2344.23 22-OCT-13:00
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 25.42 0.03 10-APR-21:45 4340.11 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 5.60 0.00 01-JAN-11:00 4340.11 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 19.82 0.00 01-JAN-00:15 3373.62 30-AUG-15:15
EnergyTransfer:Zone:F7 NW APARTMENT 24.36 0.04 06-NOV-10:30 4459.48 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 7.92 0.00 04-JAN-20:45 4459.48 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 16.44 0.00 01-JAN-00:15 3059.45 10-JUL-16:30
EnergyTransfer:Zone:F7 SE APARTMENT 25.30 0.00 04-MAR-15:15 4370.74 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 5.45 0.00 01-JAN-07:45 4370.74 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 19.85 0.00 01-JAN-00:15 3115.58 30-AUG-13:15
EnergyTransfer:Zone:F7 NE APARTMENT 24.18 0.04 22-APR-02:00 4483.53 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 7.71 0.00 04-JAN-20:45 4483.53 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 16.47 0.00 01-JAN-00:15 2511.60 10-JUL-17:00
EnergyTransfer:Zone:F7 N1 APARTMENT 16.71 0.02 10-APR-18:15 2520.51 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 3.37 0.00 01-JAN-06:30 2520.51 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 13.34 0.00 01-JAN-00:15 1814.36 10-JUL-17:00
EnergyTransfer:Zone:F7 N2 APARTMENT 16.71 0.07 20-JUN-05:45 2521.72 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 3.37 0.00 01-JAN-06:30 2521.72 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 13.34 0.00 01-JAN-00:15 1805.10 10-JUL-17:00
EnergyTransfer:Zone:F7 S1 APARTMENT 19.26 0.01 07-APR-20:45 2380.67 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 1.92 0.00 01-JAN-01:00 2380.67 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 17.34 0.00 01-JAN-00:15 2317.20 22-OCT-13:00
EnergyTransfer:Zone:F7 S2 APARTMENT 19.26 0.00 02-MAY-11:15 2382.44 31-JAN-04:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 1.93 0.00 01-JAN-01:00 2382.44 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 17.34 0.00 01-JAN-00:15 2323.23 22-OCT-13:00
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 25.67 0.00 23-NOV-10:30 4538.34 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 6.06 0.00 01-JAN-11:15 4538.34 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 19.61 0.00 01-JAN-00:15 3385.25 30-AUG-15:15
EnergyTransfer:Zone:F8 NW APARTMENT 24.82 0.00 05-APR-08:45 4650.99 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 8.46 0.00 04-JAN-20:45 4650.99 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 16.36 0.00 01-JAN-00:15 3078.73 10-JUL-16:30
EnergyTransfer:Zone:F8 SE APARTMENT 25.54 0.01 25-DEC-21:30 4568.78 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 5.91 0.00 01-JAN-08:00 4568.78 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 19.63 0.00 01-JAN-00:15 3137.43 30-AUG-13:15
EnergyTransfer:Zone:F8 NE APARTMENT 24.64 0.02 15-MAR-23:45 4674.98 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 8.24 0.00 04-JAN-21:00 4674.98 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 16.40 0.00 01-JAN-00:15 2531.73 10-JUL-17:00
EnergyTransfer:Zone:F8 N1 APARTMENT 16.96 0.00 22-MAY-18:15 2644.92 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 3.70 0.00 01-JAN-06:30 2644.92 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 13.26 0.00 01-JAN-00:15 1966.79 06-AUG-18:15
EnergyTransfer:Zone:F8 N2 APARTMENT 16.96 0.02 25-OCT-20:30 2646.05 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 3.71 0.00 01-JAN-06:30 2646.05 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 13.26 0.00 01-JAN-00:15 1960.44 06-AUG-18:15
EnergyTransfer:Zone:F8 S1 APARTMENT 19.25 0.01 29-OCT-19:15 2509.18 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 2.16 0.00 01-JAN-01:00 2509.18 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 17.10 0.00 01-JAN-00:15 2315.52 30-AUG-14:30
EnergyTransfer:Zone:F8 S2 APARTMENT 19.25 0.03 17-OCT-20:15 2510.94 31-JAN-04:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 2.16 0.00 01-JAN-01:00 2510.94 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 17.09 0.00 01-JAN-00:15 2321.14 30-AUG-14:30
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 26.68 0.00 13-JAN-21:45 4825.06 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 6.83 0.00 01-JAN-11:15 4825.06 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 19.85 0.00 01-JAN-00:15 3472.41 30-AUG-15:15
EnergyTransfer:Zone:F9 NW APARTMENT 26.12 0.02 15-OCT-01:00 4920.33 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 9.35 0.00 04-JAN-21:00 4920.33 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 16.76 0.00 01-JAN-00:15 3200.03 10-JUL-16:30
EnergyTransfer:Zone:F9 SE APARTMENT 26.52 0.06 05-MAR-05:45 4854.31 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 6.66 0.00 01-JAN-11:15 4854.31 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 19.86 0.00 01-JAN-00:15 3228.86 30-AUG-13:00
EnergyTransfer:Zone:F9 NE APARTMENT 25.90 0.00 27-FEB-19:45 4944.50 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 9.10 0.00 04-JAN-21:00 4944.50 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 16.80 0.00 01-JAN-00:15 2608.82 10-JUL-17:00
EnergyTransfer:Zone:F9 N1 APARTMENT 17.92 0.04 02-MAY-24:00 2843.61 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 4.34 0.00 04-JAN-19:30 2843.61 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 13.58 0.00 01-JAN-00:15 2038.25 06-AUG-18:15
EnergyTransfer:Zone:F9 N2 APARTMENT 17.93 0.05 13-MAR-08:30 2844.68 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 4.35 0.00 04-JAN-19:45 2844.68 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 13.58 0.00 01-JAN-00:15 2032.07 06-AUG-18:15
EnergyTransfer:Zone:F9 S1 APARTMENT 19.81 0.01 22-MAY-20:15 2724.09 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 2.60 0.00 01-JAN-02:45 2724.09 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 17.21 0.00 01-JAN-00:15 2395.24 30-AUG-14:15
EnergyTransfer:Zone:F9 S2 APARTMENT 19.81 0.01 29-OCT-07:45 2725.79 31-JAN-04:00
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 2.60 0.00 01-JAN-02:45 2725.79 31-JAN-04:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 17.21 0.00 01-JAN-00:15 2402.47 30-AUG-14:15
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 31.54 0.02 16-APR-22:45 5623.65 31-JAN-04:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 10.32 0.00 01-JAN-11:30 5623.65 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 21.22 0.00 01-JAN-00:15 4189.37 30-AUG-14:45
EnergyTransfer:Zone:T NW APARTMENT 30.86 0.01 22-OCT-23:15 5682.93 31-JAN-04:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 12.63 0.00 10-JAN-14:00 5682.93 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 18.23 0.00 01-JAN-00:15 3796.90 10-JUL-16:30
EnergyTransfer:Zone:T SE APARTMENT 31.05 0.01 05-OCT-02:00 5646.94 31-JAN-04:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 10.04 0.00 01-JAN-11:15 5646.94 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 21.01 0.00 01-JAN-00:15 3920.78 30-AUG-13:00
EnergyTransfer:Zone:T NE APARTMENT 30.24 0.01 23-NOV-14:15 5704.56 31-JAN-04:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 12.20 0.00 15-JAN-07:45 5704.56 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 18.04 0.00 01-JAN-00:15 3261.21 05-JUN-14:00
EnergyTransfer:Zone:T N1 APARTMENT 21.62 0.02 20-DEC-18:45 3566.93 31-JAN-04:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 6.90 0.00 04-JAN-20:30 3566.93 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 14.72 0.00 01-JAN-00:15 2505.75 10-JUL-16:30
EnergyTransfer:Zone:T N2 APARTMENT 21.62 0.02 20-DEC-18:00 3567.65 31-JAN-04:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 6.91 0.00 04-JAN-20:30 3567.65 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 14.71 0.00 01-JAN-00:15 2490.50 10-JUL-16:30
EnergyTransfer:Zone:T S1 APARTMENT 23.12 0.00 15-JAN-04:30 3494.22 31-JAN-04:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 5.11 0.00 01-JAN-08:00 3494.22 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 18.01 0.00 01-JAN-00:15 3215.90 30-AUG-13:00
EnergyTransfer:Zone:T S2 APARTMENT 23.13 0.01 23-MAY-03:45 3495.21 31-JAN-04:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 5.12 0.00 01-JAN-08:00 3495.21 31-JAN-04:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 18.02 0.00 01-JAN-00:15 3225.31 30-AUG-13:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 1131.52 383.77 30-JUL-01:15 274097.09 31-JAN-06:15
WaterSystems:EnergyTransfer 777.88 383.77 30-JUL-01:15 54788.85 30-JAN-08:00
sub cat:WaterSystems:EnergyTransfer 777.88 383.77 30-JUL-01:15 54788.85 30-JAN-08:00
EnergyTransfer:HVAC 2852.16 0.00 13-JAN-17:45 330429.08 03-AUG-14:45
CoolingCoils:EnergyTransfer 2351.75 0.00 01-JAN-00:15 330429.08 03-AUG-14:45
HeatingCoils:EnergyTransfer 500.41 0.00 13-JAN-17:45 313191.48 31-JAN-04:00
PlantLoopHeatingDemand:HVAC 383.64 0.00 13-JAN-17:45 237138.33 31-JAN-04:00
HeatingCoils:PlantLoopHeatingDemand 383.64 0.00 13-JAN-17:45 237138.33 31-JAN-04:00
Boilers:EnergyTransfer 353.64 0.00 10-JAN-14:30 234354.50 31-JAN-04:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 4.279 -12.938 0.000 0.000 3.762 1.087 12.213 18.230 0.000 0.660 0.000 0.000 -7.638 0.000 -7.023 -12.630
G NW APARTMENT 6.089 -10.692 0.000 0.000 3.789 1.087 12.213 11.050 0.000 0.658 0.000 0.000 -7.857 0.000 -6.508 -9.829
OFFICE 2.824 -22.218 0.000 0.000 0.514 29.882 9.495 17.932 0.000 0.502 0.000 0.000 -7.706 0.000 -3.767 -27.459
G NE APARTMENT 5.856 -10.666 0.000 0.000 3.800 1.087 12.213 10.717 0.000 0.658 0.000 0.000 -7.574 0.000 -6.455 -9.636
G N1 APARTMENT 3.277 -8.148 0.000 0.000 3.803 1.087 12.213 4.440 0.000 0.461 0.000 0.000 -4.858 0.000 -4.845 -7.430
G N2 APARTMENT 3.279 -8.150 0.000 0.000 3.804 1.087 12.213 4.439 0.000 0.461 0.000 0.000 -4.855 0.000 -4.842 -7.435
G S1 APARTMENT 1.695 -10.873 0.000 0.000 3.764 1.087 12.213 11.694 0.000 0.460 0.000 0.000 -4.628 0.000 -5.410 -10.001
G S2 APARTMENT 1.603 -11.164 0.000 0.000 3.759 1.087 12.213 11.675 0.000 0.460 0.000 0.000 -4.645 0.000 -5.471 -9.517
F2 SW APARTMENT 3.654 -19.687 0.000 0.000 3.700 1.087 12.213 17.359 0.000 0.905 0.000 0.000 -8.298 0.000 -9.647 -1.286
F2 NW APARTMENT 5.646 -15.907 0.000 0.000 3.744 1.087 12.213 10.445 0.000 0.900 0.000 0.000 -8.483 0.000 -8.943 -0.703
F2 SE APARTMENT 3.150 -21.265 0.000 0.000 3.693 1.087 12.213 17.087 0.000 0.904 1.170 0.000 -8.232 0.000 -9.805 -0.000
F2 NE APARTMENT 5.427 -15.950 0.000 0.000 3.756 1.087 12.213 10.132 0.000 0.900 0.000 0.000 -8.168 0.000 -8.874 -0.522
F2 N1 APARTMENT 2.307 -12.645 0.000 0.000 3.753 1.087 12.213 4.126 0.000 0.616 0.476 0.000 -5.301 0.000 -6.632 -0.000
F2 N2 APARTMENT 2.309 -12.644 0.000 0.000 3.754 1.087 12.213 4.126 0.000 0.616 0.464 0.000 -5.297 0.000 -6.627 -0.000
F2 S1 APARTMENT 1.156 -16.798 0.000 0.000 3.693 1.087 12.213 11.143 0.000 0.618 0.002 0.000 -5.035 0.000 -7.421 -0.655
F2 S2 APARTMENT 1.136 -16.925 0.000 0.000 3.691 1.087 12.213 11.137 0.000 0.618 0.000 0.000 -5.042 0.000 -7.443 -0.472
F3 SW APARTMENT 3.828 -20.654 0.000 0.000 3.693 1.087 12.213 16.994 0.000 1.104 1.190 0.000 -8.464 0.000 -10.990 -0.000
F3 NW APARTMENT 5.856 -16.749 0.000 0.000 3.736 1.087 12.213 10.212 0.000 1.096 1.469 0.000 -8.672 0.000 -10.247 -0.000
F3 SE APARTMENT 3.630 -20.913 0.000 0.000 3.698 1.087 12.213 16.798 0.000 1.102 1.688 0.000 -8.302 0.000 -10.999 -0.000
F3 NE APARTMENT 5.657 -16.787 0.000 0.000 3.747 1.087 12.213 9.913 0.000 1.095 1.606 0.000 -8.352 0.000 -10.179 -0.000
F3 N1 APARTMENT 2.288 -13.592 0.000 0.000 3.741 1.087 12.213 4.026 0.000 0.759 2.503 0.000 -5.440 0.000 -7.585 -0.000
F3 N2 APARTMENT 2.290 -13.591 0.000 0.000 3.742 1.087 12.213 4.026 0.000 0.759 2.489 0.000 -5.436 0.000 -7.579 -0.000
F3 S1 APARTMENT 1.168 -18.045 0.000 0.000 3.680 1.087 12.213 10.907 0.000 0.764 1.797 0.000 -5.153 0.000 -8.417 -0.000
F3 S2 APARTMENT 1.167 -18.075 0.000 0.000 3.680 1.087 12.213 10.905 0.000 0.764 1.837 0.000 -5.153 0.000 -8.423 -0.000
F4 SW APARTMENT 4.194 -20.771 0.000 0.000 3.693 1.087 12.213 16.758 0.000 1.214 1.896 0.000 -8.536 0.000 -11.747 -0.000
F4 NW APARTMENT 6.277 -16.916 0.000 0.000 3.734 1.087 12.213 10.069 0.000 1.205 2.103 0.000 -8.768 0.000 -11.004 -0.000
F4 SE APARTMENT 4.061 -20.828 0.000 0.000 3.700 1.087 12.213 16.585 0.000 1.211 2.057 0.000 -8.355 0.000 -11.729 -0.000
F4 NE APARTMENT 6.076 -16.953 0.000 0.000 3.745 1.087 12.213 9.780 0.000 1.204 2.234 0.000 -8.446 0.000 -10.939 -0.000
F4 N1 APARTMENT 2.452 -13.818 0.000 0.000 3.736 1.087 12.213 3.969 0.000 0.830 3.115 0.000 -5.511 0.000 -8.073 -0.000
F4 N2 APARTMENT 2.453 -13.814 0.000 0.000 3.737 1.087 12.213 3.969 0.000 0.830 3.101 0.000 -5.507 0.000 -8.067 -0.000
F4 S1 APARTMENT 1.299 -18.283 0.000 0.000 3.678 1.087 12.213 10.756 0.000 0.835 2.518 0.000 -5.204 0.000 -8.899 -0.000
F4 S2 APARTMENT 1.304 -18.287 0.000 0.000 3.679 1.087 12.213 10.755 0.000 0.835 2.517 0.000 -5.202 0.000 -8.901 -0.000
M SW APARTMENT 4.528 -20.985 0.000 0.000 3.695 1.087 12.213 16.570 0.000 1.302 2.714 0.000 -8.593 0.000 -12.531 -0.000
M NW APARTMENT 6.638 -17.229 0.000 0.000 3.735 1.087 12.213 9.955 0.000 1.293 2.924 0.000 -8.844 0.000 -11.770 -0.000
M SE APARTMENT 4.404 -21.016 0.000 0.000 3.702 1.087 12.213 16.409 0.000 1.299 2.818 0.000 -8.408 0.000 -12.507 -0.000
M NE APARTMENT 6.431 -17.266 0.000 0.000 3.745 1.087 12.213 9.674 0.000 1.290 3.051 0.000 -8.520 0.000 -11.704 -0.000
M N1 APARTMENT 2.606 -14.162 0.000 0.000 3.735 1.087 12.213 3.924 0.000 0.886 3.889 0.000 -5.566 0.000 -8.611 -0.000
M N2 APARTMENT 2.606 -14.160 0.000 0.000 3.736 1.087 12.213 3.924 0.000 0.886 3.877 0.000 -5.562 0.000 -8.605 -0.000
M S1 APARTMENT 1.426 -18.553 0.000 0.000 3.679 1.087 12.213 10.637 0.000 0.892 3.312 0.000 -5.241 0.000 -9.452 -0.000
M S2 APARTMENT 1.432 -18.549 0.000 0.000 3.680 1.087 12.213 10.637 0.000 0.892 3.301 0.000 -5.239 0.000 -9.452 -0.000
F6 SW APARTMENT 5.109 -20.228 0.000 0.000 3.703 1.087 12.213 16.452 0.000 1.375 1.998 0.000 -8.582 0.000 -13.127 -0.000
F6 NW APARTMENT 7.356 -16.682 0.000 0.000 3.742 1.087 12.213 9.895 0.000 1.366 2.206 0.000 -8.845 0.000 -12.337 -0.000
F6 SE APARTMENT 4.975 -20.250 0.000 0.000 3.710 1.087 12.213 16.299 0.000 1.372 2.091 0.000 -8.397 0.000 -13.101 -0.000
F6 NE APARTMENT 7.143 -16.718 0.000 0.000 3.752 1.087 12.213 9.623 0.000 1.363 2.330 0.000 -8.521 0.000 -12.270 -0.000
F6 N1 APARTMENT 3.026 -13.595 0.000 0.000 3.742 1.087 12.213 3.909 0.000 0.933 3.228 0.000 -5.567 0.000 -8.976 -0.000
F6 N2 APARTMENT 3.028 -13.594 0.000 0.000 3.743 1.087 12.213 3.908 0.000 0.933 3.215 0.000 -5.563 0.000 -8.970 -0.000
F6 S1 APARTMENT 1.689 -17.772 0.000 0.000 3.688 1.087 12.213 10.564 0.000 0.940 2.667 0.000 -5.232 0.000 -9.843 -0.000
F6 S2 APARTMENT 1.695 -17.766 0.000 0.000 3.689 1.087 12.213 10.563 0.000 0.940 2.654 0.000 -5.230 0.000 -9.843 -0.000
F7 SW APARTMENT 5.597 -19.823 0.000 0.000 3.709 1.087 12.213 16.342 0.000 1.439 1.690 0.000 -8.586 0.000 -13.667 -0.000
F7 NW APARTMENT 7.924 -16.438 0.000 0.000 3.747 1.087 12.213 9.837 0.000 1.429 1.918 0.000 -8.858 0.000 -12.856 -0.000
F7 SE APARTMENT 5.455 -19.845 0.000 0.000 3.716 1.087 12.213 16.196 0.000 1.435 1.783 0.000 -8.400 0.000 -13.640 -0.000
F7 NE APARTMENT 7.705 -16.473 0.000 0.000 3.757 1.087 12.213 9.571 0.000 1.425 2.040 0.000 -8.535 0.000 -12.789 -0.000
F7 N1 APARTMENT 3.368 -13.342 0.000 0.000 3.748 1.087 12.213 3.891 0.000 0.973 2.954 0.000 -5.575 0.000 -9.316 -0.000
F7 N2 APARTMENT 3.371 -13.342 0.000 0.000 3.749 1.087 12.213 3.890 0.000 0.973 2.941 0.000 -5.572 0.000 -9.310 -0.000
F7 S1 APARTMENT 1.921 -17.340 0.000 0.000 3.695 1.087 12.213 10.495 0.000 0.980 2.383 0.000 -5.232 0.000 -10.200 -0.000
F7 S2 APARTMENT 1.926 -17.335 0.000 0.000 3.695 1.087 12.213 10.494 0.000 0.980 2.370 0.000 -5.230 0.000 -10.200 -0.000
F8 SW APARTMENT 6.061 -19.609 0.000 0.000 3.714 1.087 12.213 16.242 0.000 1.500 1.557 0.000 -8.594 0.000 -14.170 -0.000
F8 NW APARTMENT 8.455 -16.362 0.000 0.000 3.751 1.087 12.213 9.781 0.000 1.490 1.807 0.000 -8.876 0.000 -13.344 -0.000
F8 SE APARTMENT 5.913 -19.631 0.000 0.000 3.721 1.087 12.213 16.101 0.000 1.497 1.651 0.000 -8.408 0.000 -14.143 -0.000
F8 NE APARTMENT 8.235 -16.400 0.000 0.000 3.761 1.087 12.213 9.520 0.000 1.486 1.927 0.000 -8.552 0.000 -13.276 -0.000
F8 N1 APARTMENT 3.703 -13.258 0.000 0.000 3.752 1.087 12.213 3.872 0.000 1.014 2.846 0.000 -5.587 0.000 -9.641 -0.000
F8 N2 APARTMENT 3.705 -13.258 0.000 0.000 3.753 1.087 12.213 3.871 0.000 1.014 2.834 0.000 -5.583 0.000 -9.635 -0.000
F8 S1 APARTMENT 2.155 -17.096 0.000 0.000 3.700 1.087 12.213 10.432 0.000 1.021 2.262 0.000 -5.235 0.000 -10.539 -0.000
F8 S2 APARTMENT 2.161 -17.092 0.000 0.000 3.701 1.087 12.213 10.431 0.000 1.021 2.249 0.000 -5.233 0.000 -10.539 -0.000
F9 SW APARTMENT 6.835 -19.847 0.000 0.000 3.718 1.087 12.213 16.152 0.000 1.565 1.491 0.000 -8.596 0.000 -14.617 -0.000
F9 NW APARTMENT 9.353 -16.763 0.000 0.000 3.753 1.087 12.213 9.724 0.000 1.554 1.761 0.000 -8.890 0.000 -13.792 -0.000
F9 SE APARTMENT 6.661 -19.861 0.000 0.000 3.725 1.087 12.213 16.016 0.000 1.562 1.602 0.000 -8.411 0.000 -14.593 -0.001
F9 NE APARTMENT 9.099 -16.798 0.000 0.000 3.764 1.087 12.213 9.469 0.000 1.550 1.904 0.000 -8.566 0.000 -13.721 -0.000
F9 N1 APARTMENT 4.344 -13.580 0.000 0.000 3.754 1.087 12.213 3.850 0.000 1.060 2.808 0.000 -5.593 0.000 -9.942 -0.000
F9 N2 APARTMENT 4.346 -13.582 0.000 0.000 3.755 1.087 12.213 3.849 0.000 1.060 2.798 0.000 -5.589 0.000 -9.937 -0.000
F9 S1 APARTMENT 2.596 -17.214 0.000 0.000 3.706 1.087 12.213 10.377 0.000 1.069 2.232 0.000 -5.233 0.000 -10.832 -0.000
F9 S2 APARTMENT 2.601 -17.210 0.000 0.000 3.706 1.087 12.213 10.376 0.000 1.069 2.223 0.000 -5.231 0.000 -10.832 -0.000
T SW APARTMENT 10.317 -21.223 0.000 0.000 3.740 1.087 12.213 15.807 0.000 1.610 0.001 0.000 -8.251 0.000 -15.043 -0.256
T NW APARTMENT 12.631 -18.233 0.000 0.000 3.765 1.087 12.213 9.438 0.000 1.597 0.376 0.000 -8.589 0.000 -14.285 -0.000
T SE APARTMENT 10.043 -21.009 0.000 0.000 3.746 1.087 12.213 15.690 0.000 1.609 0.001 0.000 -8.090 0.000 -15.058 -0.230
T NE APARTMENT 12.200 -18.039 0.000 0.000 3.776 1.087 12.213 9.219 0.000 1.597 0.480 0.000 -8.300 0.000 -14.232 -0.000
T N1 APARTMENT 6.899 -14.715 0.000 0.000 3.767 1.087 12.213 3.739 0.000 1.091 1.587 0.000 -5.390 0.000 -10.277 -0.001
T N2 APARTMENT 6.907 -14.713 0.000 0.000 3.768 1.087 12.213 3.737 0.000 1.091 1.574 0.000 -5.386 0.000 -10.277 -0.000
T S1 APARTMENT 5.108 -18.013 0.000 0.000 3.728 1.087 12.213 10.188 0.000 1.103 0.774 0.000 -5.053 0.000 -11.136 -0.000
T S2 APARTMENT 5.116 -18.015 0.000 0.000 3.729 1.087 12.213 10.186 0.000 1.103 0.771 0.000 -5.050 0.000 -11.139 -0.000
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 4.224 0.000 4.479 10.327 0.000 -1.750 0.000 -33.719 -0.001
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.936 0.000 0.070 0.000 0.000 -1.078 0.000 -0.979 -16.389
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.881 0.000 0.081 0.000 0.000 -1.124 0.000 -1.197 -16.080
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.847 0.000 0.087 0.000 0.000 -1.146 0.000 -1.354 -15.873
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 32.880 0.000 1.809 0.000 0.081 0.000 0.000 -1.178 0.000 -1.548 -32.043
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.813 0.000 0.101 0.000 0.000 -1.155 0.000 -1.566 -15.633
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.807 0.000 0.108 0.000 0.000 -1.147 0.000 -1.636 -15.571
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.796 0.000 0.112 0.000 0.000 -1.147 0.000 -1.708 -15.494
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.784 0.000 0.112 0.000 0.000 -1.148 0.000 -1.773 -15.415
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 8.151 1.707 0.000 0.067 0.000 0.000 -1.127 0.000 -1.914 -23.325
Total Facility 364.488 -1328.730 0.000 0.000 295.244 296.560 982.450 844.481 0.000 90.228 150.429 0.000 -560.301 0.000 -870.961 -263.896


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 30-AUG-15:15 0.00 -2722.57 0.00 0.00 48.90 45.40 470.89 3048.79 0.00 194.59 0.00 0.00 0.00 0.00 0.00 -1086.01
G NW APARTMENT 02-JUN-17:05 0.00 -2423.06 0.00 0.00 141.83 87.56 588.62 2516.30 0.00 168.47 0.00 0.00 0.00 0.00 0.00 -1079.72
OFFICE 30-AUG-13:00 0.00 -3824.28 0.00 0.00 65.20 2345.88 588.62 2506.12 0.00 229.64 0.00 0.00 0.00 0.00 0.00 -1911.18
G NE APARTMENT 10-JUL-17:15 0.00 -1858.89 0.00 0.00 141.83 87.56 588.62 961.42 0.00 252.28 0.00 0.00 0.00 0.00 0.00 -172.81
G N1 APARTMENT 04-JUN-17:20 0.00 -1351.73 0.00 0.00 141.82 87.56 588.62 791.40 0.00 82.73 0.00 0.00 0.00 0.00 0.00 -340.39
G N2 APARTMENT 04-JUN-17:20 0.00 -1338.38 0.00 0.00 141.82 87.56 588.62 791.71 0.00 82.73 0.00 0.00 0.00 0.00 0.00 -354.05
G S1 APARTMENT 30-AUG-15:00 0.00 -1747.88 0.00 0.00 40.48 22.70 400.26 1377.82 0.00 115.70 0.00 0.00 0.00 0.00 0.00 -209.08
G S2 APARTMENT 30-AUG-14:45 0.00 -1813.45 0.00 0.00 40.44 22.70 400.26 1523.40 0.00 110.66 0.00 0.00 0.00 0.00 0.00 -284.01
F2 SW APARTMENT 30-AUG-16:10 0.00 -3315.26 0.00 0.00 84.76 64.86 588.62 2559.57 0.00 273.39 0.00 0.00 0.00 0.00 0.00 -255.93
F2 NW APARTMENT 02-JUN-17:30 0.00 -2977.10 0.00 0.00 141.82 87.56 588.62 2415.88 0.00 221.49 0.00 0.00 0.00 0.00 0.00 -478.26
F2 SE APARTMENT 30-AUG-13:00 0.00 -3147.55 0.00 0.00 40.75 12.97 388.49 2426.49 0.00 329.40 0.00 0.00 0.00 0.00 0.00 -50.55
F2 NE APARTMENT 10-JUL-16:38 0.00 -2371.36 0.00 0.00 84.76 64.86 588.62 1025.10 0.00 395.93 212.10 0.00 0.00 0.00 0.00 0.00
F2 N1 APARTMENT 04-JUN-17:20 0.00 -1716.16 0.00 0.00 141.82 87.56 588.62 773.96 0.00 118.66 5.54 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 04-JUN-17:20 0.00 -1705.79 0.00 0.00 141.82 87.56 588.62 774.15 0.00 118.66 0.00 0.00 0.00 0.00 0.00 -5.02
F2 S1 APARTMENT 30-AUG-15:00 0.00 -2188.10 0.00 0.00 40.44 22.70 400.26 1346.66 0.00 165.43 212.62 0.00 0.00 0.00 0.00 0.00
F2 S2 APARTMENT 30-AUG-15:00 0.00 -2209.58 0.00 0.00 40.49 22.70 400.26 1346.80 0.00 165.76 233.58 0.00 0.00 0.00 0.00 0.00
F3 SW APARTMENT 30-AUG-15:15 0.00 -3328.88 0.00 0.00 48.90 45.40 470.89 2936.04 0.00 329.68 0.00 0.00 0.00 0.00 0.00 -502.04
F3 NW APARTMENT 02-JUN-17:30 0.00 -3016.27 0.00 0.00 141.82 87.56 588.62 2392.55 0.00 261.60 0.00 0.00 0.00 0.00 0.00 -455.87
F3 SE APARTMENT 30-AUG-13:30 0.00 -3020.57 0.00 0.00 40.54 12.97 382.60 2251.99 0.00 329.98 2.48 0.00 0.00 0.00 0.00 0.00
F3 NE APARTMENT 10-JUL-17:00 0.00 -2433.20 0.00 0.00 84.63 64.86 588.62 986.93 0.00 477.24 230.92 0.00 0.00 0.00 0.00 0.00
F3 N1 APARTMENT 04-JUN-17:20 0.00 -1763.30 0.00 0.00 141.82 87.56 588.62 768.23 0.00 140.19 36.89 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 04-JUN-17:20 0.00 -1753.20 0.00 0.00 141.82 87.56 588.62 768.42 0.00 140.19 26.60 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 22-OCT-13:00 0.00 -2315.54 0.00 0.00 40.75 12.97 388.49 2475.11 0.00 171.41 0.00 0.00 0.00 0.00 0.00 -773.19
F3 S2 APARTMENT 22-OCT-13:00 0.00 -2322.95 0.00 0.00 40.75 12.97 388.49 2474.97 0.00 171.40 0.00 0.00 0.00 0.00 0.00 -765.64
F4 SW APARTMENT 30-AUG-15:15 0.00 -3351.07 0.00 0.00 48.90 45.40 470.89 2908.12 0.00 367.68 0.00 0.00 0.00 0.00 0.00 -489.94
F4 NW APARTMENT 02-JUN-17:30 0.00 -3040.76 0.00 0.00 141.82 87.56 588.62 2375.87 0.00 291.70 0.00 0.00 0.00 0.00 0.00 -444.80
F4 SE APARTMENT 30-AUG-13:30 0.00 -3038.49 0.00 0.00 40.51 12.97 382.60 2233.96 0.00 367.73 0.71 0.00 0.00 0.00 0.00 0.00
F4 NE APARTMENT 10-JUL-17:00 0.00 -2465.99 0.00 0.00 84.47 64.86 588.62 982.46 0.00 530.80 214.79 0.00 0.00 0.00 0.00 0.00
F4 N1 APARTMENT 04-JUN-17:20 0.00 -1787.17 0.00 0.00 141.82 87.56 588.62 764.13 0.00 156.36 48.68 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 04-JUN-17:20 0.00 -1777.33 0.00 0.00 141.82 87.56 588.62 764.31 0.00 156.36 38.66 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 22-OCT-13:00 0.00 -2348.58 0.00 0.00 40.75 12.97 388.49 2460.21 0.00 177.89 0.00 0.00 0.00 0.00 0.00 -731.73
F4 S2 APARTMENT 22-OCT-13:00 0.00 -2354.78 0.00 0.00 40.75 12.97 388.49 2460.09 0.00 177.89 0.00 0.00 0.00 0.00 0.00 -725.41
M SW APARTMENT 30-AUG-15:15 0.00 -3391.84 0.00 0.00 48.90 45.40 470.89 2885.45 0.00 398.70 0.00 0.00 0.00 0.00 0.00 -457.50
M NW APARTMENT 02-JUN-17:30 0.00 -3081.43 0.00 0.00 141.82 87.56 588.62 2362.24 0.00 316.24 0.00 0.00 0.00 0.00 0.00 -415.04
M SE APARTMENT 30-AUG-13:15 0.00 -3112.97 0.00 0.00 40.57 12.97 382.60 2296.05 0.00 433.16 0.00 0.00 0.00 0.00 0.00 -52.38
M NE APARTMENT 10-JUL-17:00 0.00 -2516.45 0.00 0.00 84.35 64.86 588.62 978.20 0.00 574.45 225.97 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 10-JUL-17:15 0.00 -1828.01 0.00 0.00 140.84 87.56 588.62 622.91 0.00 308.02 80.06 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 10-JUL-17:10 0.00 -1818.44 0.00 0.00 140.81 87.56 588.62 622.98 0.00 308.07 70.41 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 22-OCT-13:00 0.00 -2376.98 0.00 0.00 40.75 12.97 388.49 2447.48 0.00 182.95 0.00 0.00 0.00 0.00 0.00 -695.66
M S2 APARTMENT 22-OCT-13:00 0.00 -2382.90 0.00 0.00 40.75 12.97 388.49 2447.36 0.00 182.95 0.00 0.00 0.00 0.00 0.00 -689.63
F6 SW APARTMENT 30-AUG-15:15 0.00 -3372.60 0.00 0.00 48.90 45.40 470.89 2868.24 0.00 425.16 0.00 0.00 0.00 0.00 0.00 -485.99
F6 NW APARTMENT 02-JUN-17:30 0.00 -3059.90 0.00 0.00 141.82 87.56 588.62 2352.21 0.00 337.16 0.00 0.00 0.00 0.00 0.00 -447.46
F6 SE APARTMENT 30-AUG-13:15 0.00 -3103.57 0.00 0.00 40.60 12.97 382.60 2285.02 0.00 462.35 0.00 0.00 0.00 0.00 0.00 -79.97
F6 NE APARTMENT 10-JUL-17:00 0.00 -2501.33 0.00 0.00 84.22 64.86 588.62 976.04 0.00 611.20 176.39 0.00 0.00 0.00 0.00 0.00
F6 N1 APARTMENT 10-JUL-17:00 0.00 -1810.59 0.00 0.00 84.12 64.86 588.62 642.99 0.00 367.86 62.14 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 10-JUL-17:00 0.00 -1801.21 0.00 0.00 84.10 64.86 588.62 643.06 0.00 367.71 52.87 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 22-OCT-13:00 0.00 -2338.32 0.00 0.00 40.75 12.97 388.49 2437.43 0.00 187.02 0.00 0.00 0.00 0.00 0.00 -728.35
F6 S2 APARTMENT 22-OCT-13:00 0.00 -2344.30 0.00 0.00 40.75 12.97 388.49 2437.31 0.00 187.02 0.00 0.00 0.00 0.00 0.00 -722.25
F7 SW APARTMENT 30-AUG-15:15 0.00 -3373.61 0.00 0.00 48.90 45.40 470.89 2852.92 0.00 448.38 0.00 0.00 0.00 0.00 0.00 -492.89
F7 NW APARTMENT 10-JUL-16:30 0.00 -3059.46 0.00 0.00 84.77 64.86 588.62 2050.00 0.00 621.43 0.00 0.00 0.00 0.00 0.00 -350.21
F7 SE APARTMENT 30-AUG-13:15 0.00 -3115.13 0.00 0.00 40.62 12.97 382.60 2275.01 0.00 488.08 0.00 0.00 0.00 0.00 0.00 -84.15
F7 NE APARTMENT 10-JUL-17:00 0.00 -2511.54 0.00 0.00 84.14 64.86 588.62 973.68 0.00 643.67 156.58 0.00 0.00 0.00 0.00 0.00
F7 N1 APARTMENT 10-JUL-17:00 0.00 -1814.33 0.00 0.00 84.07 64.86 588.62 641.33 0.00 387.67 47.78 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 10-JUL-17:00 0.00 -1805.06 0.00 0.00 84.05 64.86 588.62 641.39 0.00 387.51 38.64 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 22-OCT-13:00 0.00 -2317.27 0.00 0.00 40.75 12.97 388.49 2428.11 0.00 190.33 0.00 0.00 0.00 0.00 0.00 -743.38
F7 S2 APARTMENT 22-OCT-13:00 0.00 -2323.30 0.00 0.00 40.75 12.97 388.49 2427.99 0.00 190.33 0.00 0.00 0.00 0.00 0.00 -737.23
F8 SW APARTMENT 30-AUG-15:15 0.00 -3385.24 0.00 0.00 48.90 45.40 470.89 2839.15 0.00 469.14 0.00 0.00 0.00 0.00 0.00 -488.24
F8 NW APARTMENT 10-JUL-16:30 0.00 -3078.74 0.00 0.00 84.75 64.86 588.62 2038.79 0.00 649.98 0.00 0.00 0.00 0.00 0.00 -348.24
F8 SE APARTMENT 30-AUG-13:15 0.00 -3136.97 0.00 0.00 40.66 12.97 382.60 2265.94 0.00 511.29 0.00 0.00 0.00 0.00 0.00 -76.50
F8 NE APARTMENT 10-JUL-17:00 0.00 -2531.67 0.00 0.00 84.05 64.86 588.62 971.00 0.00 672.50 150.65 0.00 0.00 0.00 0.00 0.00
F8 N1 APARTMENT 06-AUG-18:15 0.00 -1967.41 0.00 0.00 141.82 103.77 547.42 211.38 0.00 741.56 221.46 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 06-AUG-18:15 0.00 -1961.06 0.00 0.00 141.82 103.77 547.42 211.51 0.00 741.57 214.97 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 30-AUG-14:30 0.00 -2315.30 0.00 0.00 40.61 22.70 400.26 1579.42 0.00 256.24 16.07 0.00 0.00 0.00 0.00 0.00
F8 S2 APARTMENT 30-AUG-14:30 0.00 -2320.92 0.00 0.00 40.60 22.70 400.26 1579.20 0.00 256.19 21.97 0.00 0.00 0.00 0.00 0.00
F9 SW APARTMENT 30-AUG-15:15 0.00 -3472.40 0.00 0.00 48.90 45.40 470.89 2824.30 0.00 487.96 0.00 0.00 0.00 0.00 0.00 -405.05
F9 NW APARTMENT 10-JUL-16:30 0.00 -3200.03 0.00 0.00 84.77 64.86 588.62 2025.87 0.00 676.98 0.00 0.00 0.00 0.00 0.00 -241.07
F9 SE APARTMENT 30-AUG-13:00 0.00 -3228.30 0.00 0.00 40.76 12.97 388.49 2320.00 0.00 575.63 0.00 0.00 0.00 0.00 0.00 -109.55
F9 NE APARTMENT 10-JUL-17:00 0.00 -2608.76 0.00 0.00 83.83 64.86 588.62 964.74 0.00 696.75 209.96 0.00 0.00 0.00 0.00 0.00
F9 N1 APARTMENT 06-AUG-18:15 0.00 -2038.92 0.00 0.00 141.82 103.77 547.42 208.37 0.00 763.46 274.08 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 06-AUG-18:15 0.00 -2032.74 0.00 0.00 141.82 103.77 547.42 208.49 0.00 763.46 267.78 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 30-AUG-14:15 0.00 -2394.93 0.00 0.00 40.69 22.70 400.26 1653.61 0.00 255.98 21.69 0.00 0.00 0.00 0.00 0.00
F9 S2 APARTMENT 30-AUG-14:15 0.00 -2402.16 0.00 0.00 40.69 22.70 400.26 1653.39 0.00 255.95 29.17 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 30-AUG-14:45 0.00 -4189.05 0.00 0.00 40.75 22.70 400.26 3024.44 0.00 479.17 221.73 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 10-JUL-16:30 0.00 -3796.94 0.00 0.00 84.77 64.86 588.62 1979.76 0.00 701.45 377.48 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 30-AUG-13:00 0.00 -3920.19 0.00 0.00 40.76 12.97 388.49 2268.67 0.00 596.40 612.90 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 05-JUN-14:00 0.00 -3260.80 0.00 0.00 40.76 12.97 382.60 1320.22 0.00 721.85 782.40 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 10-JUL-16:30 0.00 -2505.79 0.00 0.00 84.77 64.86 588.62 652.53 0.00 423.08 691.94 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 26-JUN-13:38 0.00 -2507.06 0.00 0.00 40.75 12.97 382.60 357.99 0.00 986.69 726.05 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 30-AUG-13:00 0.00 -3215.37 0.00 0.00 40.76 12.97 388.49 1885.19 0.00 359.73 528.24 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 30-AUG-13:00 0.00 -3224.79 0.00 0.00 40.76 12.97 388.49 1884.97 0.00 359.73 537.87 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-JUL-16:30 0.00 -187383.05 0.00 0.00 6686.73 11327.17 47312.53 89532.25 0.00 39514.89 0.00 0.00 0.00 0.00 0.00 -6990.52


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 31-JAN-04:00 2556.03 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1327.06 0.00 -1459.09 -189.72
G NW APARTMENT 31-JAN-04:00 2582.51 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1339.51 0.00 -1459.09 -203.74
OFFICE 06-JAN-22:00 2416.57 0.00 0.00 0.00 0.00 469.18 194.24 0.00 0.00 0.00 0.00 0.00 -1213.72 0.00 -1480.59 -385.68
G NE APARTMENT 31-JAN-04:00 2592.36 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1349.74 0.00 -1459.09 -203.37
G N1 APARTMENT 31-JAN-04:00 1528.43 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -822.89 0.00 -880.09 -245.29
G N2 APARTMENT 31-JAN-04:00 1528.90 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -822.87 0.00 -880.09 -245.77
G S1 APARTMENT 31-JAN-04:00 1469.02 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -811.35 0.00 -880.08 -197.42
G S2 APARTMENT 31-JAN-04:00 1454.56 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -811.74 0.00 -880.08 -182.57
F2 SW APARTMENT 31-JAN-04:00 3067.31 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1374.85 0.00 -2098.17 -14.11
F2 NW APARTMENT 31-JAN-04:00 3169.64 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1395.11 0.00 -2098.17 -96.18
F2 SE APARTMENT 31-JAN-04:00 3012.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 60.47 0.00 -1394.33 0.00 -2098.17 0.00
F2 NE APARTMENT 31-JAN-04:00 3188.41 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1411.43 0.00 -2098.17 -98.64
F2 N1 APARTMENT 31-JAN-04:00 1776.32 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -863.52 0.00 -1265.56 -67.07
F2 N2 APARTMENT 31-JAN-04:00 1777.43 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -863.50 0.00 -1265.56 -68.21
F2 S1 APARTMENT 31-JAN-04:00 1657.04 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 29.25 0.00 -840.56 0.00 -1265.56 0.00
F2 S2 APARTMENT 31-JAN-04:00 1652.69 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 33.73 0.00 -840.69 0.00 -1265.56 0.00
F3 SW APARTMENT 31-JAN-04:00 3360.70 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 100.33 0.00 -1395.67 0.00 -2485.20 0.00
F3 NW APARTMENT 31-JAN-04:00 3485.41 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1419.06 0.00 -2485.20 -0.98
F3 SE APARTMENT 31-JAN-04:00 3376.02 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 104.36 0.00 -1415.01 0.00 -2485.20 0.00
F3 NE APARTMENT 31-JAN-04:00 3508.01 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1437.95 0.00 -2485.20 -4.69
F3 N1 APARTMENT 31-JAN-04:00 1930.98 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 28.61 0.00 -880.41 0.00 -1499.01 0.00
F3 N2 APARTMENT 31-JAN-04:00 1932.49 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 27.06 0.00 -880.37 0.00 -1499.01 0.00
F3 S1 APARTMENT 31-JAN-04:00 1789.39 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 143.90 0.00 -854.11 0.00 -1499.01 0.00
F3 S2 APARTMENT 31-JAN-04:00 1790.03 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 143.24 0.00 -854.09 0.00 -1499.01 0.00
F4 SW APARTMENT 31-JAN-04:00 3640.58 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 126.44 0.00 -1407.83 0.00 -2779.03 0.00
F4 NW APARTMENT 31-JAN-04:00 3770.48 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 22.16 0.00 -1433.45 0.00 -2779.03 0.00
F4 SE APARTMENT 31-JAN-04:00 3668.68 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 118.79 0.00 -1428.27 0.00 -2779.03 0.00
F4 NE APARTMENT 31-JAN-04:00 3794.79 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 18.31 0.00 -1453.91 0.00 -2779.03 0.00
F4 N1 APARTMENT 31-JAN-04:00 2091.81 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 55.11 0.00 -890.51 0.00 -1676.24 0.00
F4 N2 APARTMENT 31-JAN-04:00 2093.50 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 53.37 0.00 -890.46 0.00 -1676.24 0.00
F4 S1 APARTMENT 31-JAN-04:00 1947.79 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 170.45 0.00 -861.84 0.00 -1676.24 0.00
F4 S2 APARTMENT 31-JAN-04:00 1949.65 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 168.53 0.00 -861.77 0.00 -1676.24 0.00
M SW APARTMENT 31-JAN-04:00 3870.73 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 148.16 0.00 -1417.24 0.00 -3021.48 0.00
M NW APARTMENT 31-JAN-04:00 3997.98 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 48.27 0.00 -1444.60 0.00 -3021.48 0.00
M SE APARTMENT 31-JAN-04:00 3900.95 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 139.45 0.00 -1438.75 0.00 -3021.48 0.00
M NE APARTMENT 31-JAN-04:00 4022.76 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 45.08 0.00 -1466.19 0.00 -3021.48 0.00
M N1 APARTMENT 31-JAN-04:00 2220.26 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 80.61 0.00 -898.22 0.00 -1822.48 0.00
M N2 APARTMENT 31-JAN-04:00 2221.86 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 78.96 0.00 -898.17 0.00 -1822.48 0.00
M S1 APARTMENT 31-JAN-04:00 2080.28 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 190.10 0.00 -867.73 0.00 -1822.48 0.00
M S2 APARTMENT 31-JAN-04:00 2082.12 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 188.20 0.00 -867.67 0.00 -1822.48 0.00
F6 SW APARTMENT 31-JAN-04:00 4125.86 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 107.53 0.00 -1422.58 0.00 -3230.64 0.00
F6 NW APARTMENT 31-JAN-04:00 4250.16 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 12.08 0.00 -1451.43 0.00 -3230.64 0.00
F6 SE APARTMENT 31-JAN-04:00 4156.53 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 99.20 0.00 -1444.92 0.00 -3230.64 0.00
F6 NE APARTMENT 31-JAN-04:00 4274.65 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 10.03 0.00 -1473.87 0.00 -3230.64 0.00
F6 N1 APARTMENT 31-JAN-04:00 2385.74 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 45.85 0.00 -902.79 0.00 -1948.64 0.00
F6 N2 APARTMENT 31-JAN-04:00 2387.14 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 44.41 0.00 -902.75 0.00 -1948.64 0.00
F6 S1 APARTMENT 31-JAN-04:00 2244.17 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 155.51 0.00 -870.88 0.00 -1948.64 0.00
F6 S2 APARTMENT 31-JAN-04:00 2245.98 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 153.64 0.00 -870.82 0.00 -1948.64 0.00
F7 SW APARTMENT 31-JAN-04:00 4339.82 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 84.07 0.00 -1427.57 0.00 -3416.16 0.00
F7 NW APARTMENT 31-JAN-04:00 4459.18 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1457.64 0.00 -3416.16 -5.22
F7 SE APARTMENT 31-JAN-04:00 4370.46 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 76.45 0.00 -1450.57 0.00 -3416.16 0.00
F7 NE APARTMENT 31-JAN-04:00 4483.24 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1480.76 0.00 -3416.16 -6.15
F7 N1 APARTMENT 31-JAN-04:00 2520.31 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 27.28 0.00 -906.88 0.00 -2060.54 0.00
F7 N2 APARTMENT 31-JAN-04:00 2521.52 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 26.04 0.00 -906.85 0.00 -2060.54 0.00
F7 S1 APARTMENT 31-JAN-04:00 2380.47 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 134.06 0.00 -873.82 0.00 -2060.54 0.00
F7 S2 APARTMENT 31-JAN-04:00 2382.25 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 132.23 0.00 -873.77 0.00 -2060.54 0.00
F8 SW APARTMENT 31-JAN-04:00 4538.05 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 57.76 0.00 -1431.75 0.00 -3583.89 0.00
F8 NW APARTMENT 31-JAN-04:00 4650.69 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1462.90 0.00 -3583.89 -23.73
F8 SE APARTMENT 31-JAN-04:00 4568.49 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 50.88 0.00 -1455.31 0.00 -3583.89 0.00
F8 NE APARTMENT 31-JAN-04:00 4674.69 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1486.57 0.00 -3583.89 -24.05
F8 N1 APARTMENT 31-JAN-04:00 2644.72 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 7.48 0.00 -910.32 0.00 -2161.71 0.00
F8 N2 APARTMENT 31-JAN-04:00 2645.84 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 6.32 0.00 -910.29 0.00 -2161.71 0.00
F8 S1 APARTMENT 31-JAN-04:00 2508.98 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 109.15 0.00 -876.25 0.00 -2161.71 0.00
F8 S2 APARTMENT 31-JAN-04:00 2510.74 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 107.34 0.00 -876.20 0.00 -2161.71 0.00
F9 SW APARTMENT 31-JAN-04:00 4824.75 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1431.81 0.00 -3737.67 -75.10
F9 NW APARTMENT 31-JAN-04:00 4920.01 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1464.17 0.00 -3737.67 -138.00
F9 SE APARTMENT 31-JAN-04:00 4854.01 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1455.83 0.00 -3737.67 -80.34
F9 NE APARTMENT 31-JAN-04:00 4944.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1488.24 0.00 -3737.68 -138.11
F9 N1 APARTMENT 31-JAN-04:00 2843.39 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -911.05 0.00 -2254.47 -97.70
F9 N2 APARTMENT 31-JAN-04:00 2844.47 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -911.02 0.00 -2254.47 -98.81
F9 S1 APARTMENT 31-JAN-04:00 2723.88 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -875.84 0.00 -2254.47 -13.40
F9 S2 APARTMENT 31-JAN-04:00 2725.58 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -875.80 0.00 -2254.47 -15.15
T SW APARTMENT 31-JAN-04:00 5623.28 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1401.72 0.00 -3879.86 -761.54
T NW APARTMENT 31-JAN-04:00 5682.56 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1433.88 0.00 -3879.86 -788.65
T SE APARTMENT 31-JAN-04:00 5646.58 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1425.67 0.00 -3879.86 -760.88
T NE APARTMENT 31-JAN-04:00 5704.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1457.83 0.00 -3879.86 -786.35
T N1 APARTMENT 31-JAN-04:00 3566.64 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -890.35 0.00 -2340.32 -755.81
T N2 APARTMENT 31-JAN-04:00 3567.37 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -890.33 0.00 -2340.32 -756.55
T S1 APARTMENT 31-JAN-04:00 3493.94 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -858.18 0.00 -2340.32 -715.26
T S2 APARTMENT 31-JAN-04:00 3494.92 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -858.16 0.00 -2340.32 -716.28
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-04:00 253628.67 0.00 0.00 0.00 14983.98 6715.87 17923.60 0.00 0.00 0.00 0.00 0.00 -93978.02 0.00 -195290.74 -3983.36



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Sec1.1A-General Information

Data
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 83.50
Number of hours cooling loads not met 101.00
Number of hours not met 184.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 296.56 14401.37 0.00 0.00 0.00 0.00
Exterior Lighting 162.95 10364.00 0.00 0.00 0.00 0.00
Space Heating 135.05 0.00 473.91 294826.64 0.00 0.00
Space Cooling 674.94 78343.46 0.00 0.00 0.00 0.00
Pumps 71.11 2349.24 0.00 0.00 0.00 0.00
Heat Rejection 32.61 3357.38 0.00 0.00 0.00 0.00
Fans-Interior 599.19 19000.27 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1002.57 75821.85 0.00 0.00
Receptacle Equipment 1137.32 51749.96 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3145.91   1476.48   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1137.32 3145.91
Natural Gas 0.00 1476.48
Additional 0.00 0.00
Total 1137.32 4622.39


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.84
Space Heating 17.23
Space Cooling 86.13
Fans-Interior 76.46
Service Water Heating 0.00
Receptacle Equipment 145.13
Miscellaneous 38.65
Subtotal 401.44


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 60.47
Service Water Heating 127.94
Miscellaneous -0.00
Subtotal 188.41


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.42
Space Heating 13.17
Space Cooling 14.60
Fans-Interior 12.96
Service Water Heating 21.69
Receptacle Equipment 24.60
Miscellaneous 6.55



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.210212
G NW APARTMENT DIRECT AIR 0.206443
OFFICE DIRECT AIR 0.315353
G NE APARTMENT DIRECT AIR 0.161511
G N1 APARTMENT DIRECT AIR 0.114578
G N2 APARTMENT DIRECT AIR 0.113403
G S1 APARTMENT DIRECT AIR 0.121467
G S2 APARTMENT DIRECT AIR 0.127277
F2 SW APARTMENT DIRECT AIR 0.261267
F2 NW APARTMENT DIRECT AIR 0.255606
F2 SE APARTMENT DIRECT AIR 0.244527
F2 NE APARTMENT DIRECT AIR 0.205664
F2 N1 APARTMENT DIRECT AIR 0.145607
F2 N2 APARTMENT DIRECT AIR 0.144650
F2 S1 APARTMENT DIRECT AIR 0.155296
F2 S2 APARTMENT DIRECT AIR 0.157280
F3 SW APARTMENT DIRECT AIR 0.262875
F3 NW APARTMENT DIRECT AIR 0.257763
F3 SE APARTMENT DIRECT AIR 0.227116
F3 NE APARTMENT DIRECT AIR 0.208829
F3 N1 APARTMENT DIRECT AIR 0.148623
F3 N2 APARTMENT DIRECT AIR 0.147683
F3 S1 APARTMENT DIRECT AIR 0.158161
F3 S2 APARTMENT DIRECT AIR 0.158982
F4 SW APARTMENT DIRECT AIR 0.264584
F4 NW APARTMENT DIRECT AIR 0.259611
F4 SE APARTMENT DIRECT AIR 0.226903
F4 NE APARTMENT DIRECT AIR 0.210601
F4 N1 APARTMENT DIRECT AIR 0.150604
F4 N2 APARTMENT DIRECT AIR 0.149676
F4 S1 APARTMENT DIRECT AIR 0.159838
F4 S2 APARTMENT DIRECT AIR 0.160487
M SW APARTMENT DIRECT AIR 0.268064
M NW APARTMENT DIRECT AIR 0.263254
M SE APARTMENT DIRECT AIR 0.230223
M NE APARTMENT DIRECT AIR 0.214150
M N1 APARTMENT DIRECT AIR 0.154223
M N2 APARTMENT DIRECT AIR 0.153304
M S1 APARTMENT DIRECT AIR 0.163166
M S2 APARTMENT DIRECT AIR 0.163790
F6 SW APARTMENT DIRECT AIR 0.265923
F6 NW APARTMENT DIRECT AIR 0.261115
F6 SE APARTMENT DIRECT AIR 0.228554
F6 NE APARTMENT DIRECT AIR 0.212010
F6 N1 APARTMENT DIRECT AIR 0.152292
F6 N2 APARTMENT DIRECT AIR 0.151386
F6 S1 APARTMENT DIRECT AIR 0.161064
F6 S2 APARTMENT DIRECT AIR 0.161683
F7 SW APARTMENT DIRECT AIR 0.265738
F7 NW APARTMENT DIRECT AIR 0.261010
F7 SE APARTMENT DIRECT AIR 0.228777
F7 NE APARTMENT DIRECT AIR 0.211883
F7 N1 APARTMENT DIRECT AIR 0.152284
F7 N2 APARTMENT DIRECT AIR 0.151387
F7 S1 APARTMENT DIRECT AIR 0.160872
F7 S2 APARTMENT DIRECT AIR 0.161472
F8 SW APARTMENT DIRECT AIR 0.266914
F8 NW APARTMENT DIRECT AIR 0.262262
F8 SE APARTMENT DIRECT AIR 0.230241
F8 NE APARTMENT DIRECT AIR 0.213089
F8 N1 APARTMENT DIRECT AIR 0.153612
F8 N2 APARTMENT DIRECT AIR 0.152725
F8 S1 APARTMENT DIRECT AIR 0.161973
F8 S2 APARTMENT DIRECT AIR 0.162555
F9 SW APARTMENT DIRECT AIR 0.277545
F9 NW APARTMENT DIRECT AIR 0.273047
F9 SE APARTMENT DIRECT AIR 0.238873
F9 NE APARTMENT DIRECT AIR 0.218881
F9 N1 APARTMENT DIRECT AIR 0.163340
F9 N2 APARTMENT DIRECT AIR 0.162447
F9 S1 APARTMENT DIRECT AIR 0.169425
F9 S2 APARTMENT DIRECT AIR 0.170035
T SW APARTMENT DIRECT AIR 0.348908
T NW APARTMENT DIRECT AIR 0.337357
T SE APARTMENT DIRECT AIR 0.311321
T NE APARTMENT DIRECT AIR 0.278258
T N1 APARTMENT DIRECT AIR 0.215344
T N2 APARTMENT DIRECT AIR 0.215292
T S1 APARTMENT DIRECT AIR 0.246821
T S2 APARTMENT DIRECT AIR 0.247341


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.210212
AIRLOOP G NW MAIN BRANCH 0.206443
AIRLOOP OFFICE MAIN BRANCH 0.315353
AIRLOOP G NE MAIN BRANCH 0.161511
AIRLOOP G N1 MAIN BRANCH 0.114578
AIRLOOP G N2 MAIN BRANCH 0.113403
AIRLOOP G S1 MAIN BRANCH 0.121467
AIRLOOP G S2 MAIN BRANCH 0.127277
AIRLOOP F2 SW MAIN BRANCH 0.261267
AIRLOOP F2 NW MAIN BRANCH 0.255606
AIRLOOP F2 SE MAIN BRANCH 0.244527
AIRLOOP F2 NE MAIN BRANCH 0.205664
AIRLOOP F2 N1 MAIN BRANCH 0.145607
AIRLOOP F2 N2 MAIN BRANCH 0.144650
AIRLOOP F2 S1 MAIN BRANCH 0.155296
AIRLOOP F2 S2 MAIN BRANCH 0.157280
AIRLOOP F3 SW MAIN BRANCH 0.262875
AIRLOOP F3 NW MAIN BRANCH 0.257763
AIRLOOP F3 SE MAIN BRANCH 0.227116
AIRLOOP F3 NE MAIN BRANCH 0.208829
AIRLOOP F3 N1 MAIN BRANCH 0.148623
AIRLOOP F3 N2 MAIN BRANCH 0.147683
AIRLOOP F3 S1 MAIN BRANCH 0.158161
AIRLOOP F3 S2 MAIN BRANCH 0.158982
AIRLOOP F4 SW MAIN BRANCH 0.264584
AIRLOOP F4 NW MAIN BRANCH 0.259611
AIRLOOP F4 SE MAIN BRANCH 0.226903
AIRLOOP F4 NE MAIN BRANCH 0.210601
AIRLOOP F4 N1 MAIN BRANCH 0.150604
AIRLOOP F4 N2 MAIN BRANCH 0.149676
AIRLOOP F4 S1 MAIN BRANCH 0.159838
AIRLOOP F4 S2 MAIN BRANCH 0.160487
AIRLOOP M SW MAIN BRANCH 0.268064
AIRLOOP M NW MAIN BRANCH 0.263254
AIRLOOP M SE MAIN BRANCH 0.230223
AIRLOOP M NE MAIN BRANCH 0.214150
AIRLOOP M N1 MAIN BRANCH 0.154223
AIRLOOP M N2 MAIN BRANCH 0.153304
AIRLOOP M S1 MAIN BRANCH 0.163166
AIRLOOP M S2 MAIN BRANCH 0.163790
AIRLOOP F6 SW MAIN BRANCH 0.265923
AIRLOOP F6 NW MAIN BRANCH 0.261115
AIRLOOP F6 SE MAIN BRANCH 0.228554
AIRLOOP F6 NE MAIN BRANCH 0.212010
AIRLOOP F6 N1 MAIN BRANCH 0.152292
AIRLOOP F6 N2 MAIN BRANCH 0.151386
AIRLOOP F6 S1 MAIN BRANCH 0.161064
AIRLOOP F6 S2 MAIN BRANCH 0.161683
AIRLOOP F7 SW MAIN BRANCH 0.265738
AIRLOOP F7 NW MAIN BRANCH 0.261010
AIRLOOP F7 SE MAIN BRANCH 0.228777
AIRLOOP F7 NE MAIN BRANCH 0.211883
AIRLOOP F7 N1 MAIN BRANCH 0.152284
AIRLOOP F7 N2 MAIN BRANCH 0.151387
AIRLOOP F7 S1 MAIN BRANCH 0.160872
AIRLOOP F7 S2 MAIN BRANCH 0.161472
AIRLOOP F8 SW MAIN BRANCH 0.266914
AIRLOOP F8 NW MAIN BRANCH 0.262262
AIRLOOP F8 SE MAIN BRANCH 0.230241
AIRLOOP F8 NE MAIN BRANCH 0.213089
AIRLOOP F8 N1 MAIN BRANCH 0.153612
AIRLOOP F8 N2 MAIN BRANCH 0.152725
AIRLOOP F8 S1 MAIN BRANCH 0.161973
AIRLOOP F8 S2 MAIN BRANCH 0.162555
AIRLOOP F9 SW MAIN BRANCH 0.277545
AIRLOOP F9 NW MAIN BRANCH 0.273047
AIRLOOP F9 SE MAIN BRANCH 0.238873
AIRLOOP F9 NE MAIN BRANCH 0.218881
AIRLOOP F9 N1 MAIN BRANCH 0.163340
AIRLOOP F9 N2 MAIN BRANCH 0.162447
AIRLOOP F9 S1 MAIN BRANCH 0.169425
AIRLOOP F9 S2 MAIN BRANCH 0.170035
AIRLOOP T SW MAIN BRANCH 0.348908
AIRLOOP T NW MAIN BRANCH 0.337357
AIRLOOP T SE MAIN BRANCH 0.311321
AIRLOOP T NE MAIN BRANCH 0.278258
AIRLOOP T N1 MAIN BRANCH 0.215344
AIRLOOP T N2 MAIN BRANCH 0.215292
AIRLOOP T S1 MAIN BRANCH 0.246821
AIRLOOP T S2 MAIN BRANCH 0.247341


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.210212
AIRLOOP G NW 0.206443
AIRLOOP OFFICE 0.315353
AIRLOOP G NE 0.161511
AIRLOOP G N1 0.114578
AIRLOOP G N2 0.113403
AIRLOOP G S1 0.121467
AIRLOOP G S2 0.127277
AIRLOOP F2 SW 0.261267
AIRLOOP F2 NW 0.255606
AIRLOOP F2 SE 0.244527
AIRLOOP F2 NE 0.205664
AIRLOOP F2 N1 0.145607
AIRLOOP F2 N2 0.144650
AIRLOOP F2 S1 0.155296
AIRLOOP F2 S2 0.157280
AIRLOOP F3 SW 0.262875
AIRLOOP F3 NW 0.257763
AIRLOOP F3 SE 0.227116
AIRLOOP F3 NE 0.208829
AIRLOOP F3 N1 0.148623
AIRLOOP F3 N2 0.147683
AIRLOOP F3 S1 0.158161
AIRLOOP F3 S2 0.158982
AIRLOOP F4 SW 0.264584
AIRLOOP F4 NW 0.259611
AIRLOOP F4 SE 0.226903
AIRLOOP F4 NE 0.210601
AIRLOOP F4 N1 0.150604
AIRLOOP F4 N2 0.149676
AIRLOOP F4 S1 0.159838
AIRLOOP F4 S2 0.160487
AIRLOOP M SW 0.268064
AIRLOOP M NW 0.263254
AIRLOOP M SE 0.230223
AIRLOOP M NE 0.214150
AIRLOOP M N1 0.154223
AIRLOOP M N2 0.153304
AIRLOOP M S1 0.163166
AIRLOOP M S2 0.163790
AIRLOOP F6 SW 0.265923
AIRLOOP F6 NW 0.261115
AIRLOOP F6 SE 0.228554
AIRLOOP F6 NE 0.212010
AIRLOOP F6 N1 0.152292
AIRLOOP F6 N2 0.151386
AIRLOOP F6 S1 0.161064
AIRLOOP F6 S2 0.161683
AIRLOOP F7 SW 0.265738
AIRLOOP F7 NW 0.261010
AIRLOOP F7 SE 0.228777
AIRLOOP F7 NE 0.211883
AIRLOOP F7 N1 0.152284
AIRLOOP F7 N2 0.151387
AIRLOOP F7 S1 0.160872
AIRLOOP F7 S2 0.161472
AIRLOOP F8 SW 0.266914
AIRLOOP F8 NW 0.262262
AIRLOOP F8 SE 0.230241
AIRLOOP F8 NE 0.213089
AIRLOOP F8 N1 0.153612
AIRLOOP F8 N2 0.152725
AIRLOOP F8 S1 0.161973
AIRLOOP F8 S2 0.162555
AIRLOOP F9 SW 0.277545
AIRLOOP F9 NW 0.273047
AIRLOOP F9 SE 0.238873
AIRLOOP F9 NE 0.218881
AIRLOOP F9 N1 0.163340
AIRLOOP F9 N2 0.162447
AIRLOOP F9 S1 0.169425
AIRLOOP F9 S2 0.170035
AIRLOOP T SW 0.348908
AIRLOOP T NW 0.337357
AIRLOOP T SE 0.311321
AIRLOOP T NE 0.278258
AIRLOOP T N1 0.215344
AIRLOOP T N2 0.215292
AIRLOOP T S1 0.246821
AIRLOOP T S2 0.247341


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.210212 0.025952
AIRLOOP G NW OA CONTROLLER 0.206443 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.315353 0.038103
AIRLOOP G NE OA CONTROLLER 0.161511 0.025952
AIRLOOP G N1 OA CONTROLLER 0.114578 0.025952
AIRLOOP G N2 OA CONTROLLER 0.113403 0.025952
AIRLOOP G S1 OA CONTROLLER 0.121467 0.025952
AIRLOOP G S2 OA CONTROLLER 0.127277 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.261267 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.255606 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.244527 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.205664 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.145607 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.144650 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.155296 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.157280 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.262875 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.257763 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.227116 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.208829 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.148623 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.147683 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.158161 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.158982 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.264584 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.259611 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.226903 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.210601 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.150604 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.149676 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.159838 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.160487 0.025952
AIRLOOP M SW OA CONTROLLER 0.268064 0.025952
AIRLOOP M NW OA CONTROLLER 0.263254 0.025952
AIRLOOP M SE OA CONTROLLER 0.230223 0.025952
AIRLOOP M NE OA CONTROLLER 0.214150 0.025952
AIRLOOP M N1 OA CONTROLLER 0.154223 0.025952
AIRLOOP M N2 OA CONTROLLER 0.153304 0.025952
AIRLOOP M S1 OA CONTROLLER 0.163166 0.025952
AIRLOOP M S2 OA CONTROLLER 0.163790 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.265923 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.261115 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.228554 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.212010 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.152292 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.151386 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.161064 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.161683 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.265738 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.261010 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.228777 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.211883 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.152284 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.151387 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.160872 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.161472 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.266914 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.262262 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.230241 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.213089 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.153612 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.152725 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.161973 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.162555 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.277545 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.273047 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.238873 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.218881 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.163340 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.162447 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.169425 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.170035 0.025952
AIRLOOP T SW OA CONTROLLER 0.348908 0.025952
AIRLOOP T NW OA CONTROLLER 0.337357 0.025952
AIRLOOP T SE OA CONTROLLER 0.311321 0.025952
AIRLOOP T NE OA CONTROLLER 0.278258 0.025952
AIRLOOP T N1 OA CONTROLLER 0.215344 0.025952
AIRLOOP T N2 OA CONTROLLER 0.215292 0.025952
AIRLOOP T S1 OA CONTROLLER 0.246821 0.025952
AIRLOOP T S2 OA CONTROLLER 0.247341 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.210212 4089.33 2665.72 0.000089
HEAT PUMP COOLING MODE AIRLOOP G NW 0.206443 4025.42 2619.30 0.000088
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.315353 5922.42 3923.34 0.000129
HEAT PUMP COOLING MODE AIRLOOP G NE 0.161511 3326.60 2110.51 0.000073
HEAT PUMP COOLING MODE AIRLOOP G N1 0.114578 2580.22 1583.81 0.000056
HEAT PUMP COOLING MODE AIRLOOP G N2 0.113403 2562.41 1570.95 0.000056
HEAT PUMP COOLING MODE AIRLOOP G S1 0.121467 2729.55 1680.21 0.000060
HEAT PUMP COOLING MODE AIRLOOP G S2 0.127277 2815.25 1743.57 0.000061
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.261267 4927.57 3253.14 0.000108
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.255606 4837.03 3186.11 0.000106
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.244527 4665.33 3061.45 0.000102
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.205664 4070.88 2624.58 0.000089
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.145607 3099.53 1943.06 0.000068
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.144650 3085.19 1932.58 0.000067
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.155296 3283.13 2068.74 0.000072
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.157280 3312.09 2090.31 0.000072
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.262875 5012.12 3290.43 0.000109
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.257763 4929.13 3229.34 0.000108
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.227116 4472.45 2892.13 0.000098
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.208829 4174.31 2678.40 0.000091
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.148623 3176.97 1987.60 0.000069
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.147683 3162.83 1977.31 0.000069
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.158161 3358.42 2111.54 0.000073
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.158982 3370.37 2120.44 0.000074
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.264584 5082.31 3323.83 0.000111
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.259611 5001.06 3264.24 0.000109
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.226903 4512.72 2904.46 0.000099
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.210601 4242.66 2712.23 0.000093
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.150604 3230.82 2017.95 0.000071
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.149676 3216.78 2007.78 0.000070
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.159838 3407.92 2138.53 0.000074
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.160487 3417.37 2145.56 0.000075
HEAT PUMP COOLING MODE AIRLOOP M SW 0.268064 5169.68 3373.76 0.000113
HEAT PUMP COOLING MODE AIRLOOP M NW 0.263254 5090.66 3315.94 0.000111
HEAT PUMP COOLING MODE AIRLOOP M SE 0.230223 4636.25 2971.84 0.000101
HEAT PUMP COOLING MODE AIRLOOP M NE 0.214150 4329.25 2762.70 0.000095
HEAT PUMP COOLING MODE AIRLOOP M N1 0.154223 3304.58 2064.53 0.000072
HEAT PUMP COOLING MODE AIRLOOP M N2 0.153304 3290.66 2054.45 0.000072
HEAT PUMP COOLING MODE AIRLOOP M S1 0.163166 3477.34 2181.96 0.000076
HEAT PUMP COOLING MODE AIRLOOP M S2 0.163790 3486.43 2188.72 0.000076
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.265923 5169.64 3360.79 0.000113
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.261115 5090.35 3302.97 0.000111
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.228554 4640.90 2963.67 0.000101
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.212010 4326.41 2749.51 0.000095
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.152292 3292.46 2049.59 0.000072
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.151386 3278.65 2039.63 0.000072
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.161064 3464.85 2165.92 0.000076
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.161683 3472.17 2171.74 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.265738 5194.08 3367.83 0.000113
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.261010 5115.75 3310.86 0.000112
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.228777 4669.70 2974.89 0.000102
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.211883 4355.99 2760.38 0.000095
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.152284 3306.89 2054.84 0.000072
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.151387 3293.18 2044.98 0.000072
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.160872 3476.76 2169.10 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.161472 3483.86 2174.73 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.266914 5235.52 3388.75 0.000114
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.262262 5158.18 3332.60 0.000113
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.230241 4714.22 2998.78 0.000103
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.213089 4396.26 2781.42 0.000096
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.153612 3339.91 2074.13 0.000073
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.152725 3326.31 2064.36 0.000073
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.161973 3506.45 2185.89 0.000077
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.162555 3513.31 2191.34 0.000077
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.277545 5413.81 3512.02 0.000118
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.273047 5338.92 3457.56 0.000117
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.238873 4863.88 3100.48 0.000106
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.218881 4503.70 2852.00 0.000098
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.163340 3498.59 2184.79 0.000076
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.162447 3484.99 2174.98 0.000076
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.169425 3630.79 2272.05 0.000079
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.170035 3639.73 2278.66 0.000080
HEAT PUMP COOLING MODE AIRLOOP T SW 0.348908 6492.52 4304.98 0.000142
HEAT PUMP COOLING MODE AIRLOOP T NW 0.337357 6310.39 4171.76 0.000138
HEAT PUMP COOLING MODE AIRLOOP T SE 0.311321 5949.07 3897.03 0.000130
HEAT PUMP COOLING MODE AIRLOOP T NE 0.278258 5420.29 3514.43 0.000118
HEAT PUMP COOLING MODE AIRLOOP T N1 0.215344 4323.83 2778.60 0.000094
HEAT PUMP COOLING MODE AIRLOOP T N2 0.215292 4322.73 2777.92 0.000094
HEAT PUMP COOLING MODE AIRLOOP T S1 0.246821 4779.92 3119.96 0.000104
HEAT PUMP COOLING MODE AIRLOOP T S2 0.247341 4787.24 3125.54 0.000105


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.210212 0.210212 0.210212 0.210212 4089.33 4089.33 3368.22 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.206443 0.206443 0.206443 0.206443 4025.42 4025.42 3370.28 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.315353 0.315353 0.315353 0.315353 5922.42 5922.42 4164.37 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.161511 0.161511 0.161511 0.161511 3326.60 3326.60 3370.28 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.114578 0.114578 0.114578 0.114578 2580.22 2580.22 2526.90 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.113403 0.113403 0.113403 0.113403 2562.41 2562.41 2526.90 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.121467 0.121467 0.121467 0.121467 2729.55 2729.55 2521.41 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.127277 0.127277 0.127277 0.127277 2815.25 2815.25 2527.68 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.261267 0.261267 0.261267 0.261267 4927.57 4927.57 3396.35 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.255606 0.255606 0.255606 0.255606 4837.03 4837.03 3397.01 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.244527 0.244527 0.244527 0.244527 4665.33 4665.33 3414.85 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.205664 0.205664 0.205664 0.205664 4070.88 4070.88 3397.01 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.145607 0.145607 0.145607 0.145607 3099.53 3099.53 2334.30 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.144650 0.144650 0.144650 0.144650 3085.19 3085.19 2334.30 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.155296 0.155296 0.155296 0.155296 3283.13 3283.13 2336.33 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.157280 0.157280 0.157280 0.157280 3312.09 3312.09 2337.53 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.262875 0.262875 0.262875 0.262875 5012.12 5012.12 3472.13 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.257763 0.257763 0.257763 0.257763 4929.13 4929.13 3477.12 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.227116 0.227116 0.227116 0.227116 4472.45 4472.45 3474.14 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.208829 0.208829 0.208829 0.208829 4174.31 4174.31 3477.12 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.148623 0.148623 0.148623 0.148623 3176.97 3176.97 2343.90 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.147683 0.147683 0.147683 0.147683 3162.83 3162.83 2343.90 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.158161 0.158161 0.158161 0.158161 3358.42 3358.42 2339.60 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.158982 0.158982 0.158982 0.158982 3370.37 3370.37 2339.79 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.264584 0.264584 0.264584 0.264584 5082.31 5082.31 3584.04 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.259611 0.259611 0.259611 0.259611 5001.06 5001.06 3592.00 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.226903 0.226903 0.226903 0.226903 4512.72 4512.72 3584.25 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.210601 0.210601 0.210601 0.210601 4242.66 4242.66 3592.00 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.150604 0.150604 0.150604 0.150604 3230.82 3230.82 2403.20 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.149676 0.149676 0.149676 0.149676 3216.78 3216.78 2403.20 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.159838 0.159838 0.159838 0.159838 3407.92 3407.92 2395.62 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.160487 0.160487 0.160487 0.160487 3417.37 3417.37 2395.65 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.268064 0.268064 0.268064 0.268064 5169.68 5169.68 3665.19 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.263254 0.263254 0.263254 0.263254 5090.66 5090.66 3674.15 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.230223 0.230223 0.230223 0.230223 4636.25 4636.25 3665.21 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.214150 0.214150 0.214150 0.214150 4329.25 4329.25 3674.15 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.154223 0.154223 0.154223 0.154223 3304.58 3304.58 2441.15 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.153304 0.153304 0.153304 0.153304 3290.66 3290.66 2441.15 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.163166 0.163166 0.163166 0.163166 3477.34 3477.34 2432.44 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.163790 0.163790 0.163790 0.163790 3486.43 3486.43 2432.44 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.265923 0.265923 0.265923 0.265923 5169.64 5169.64 3795.91 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.261115 0.261115 0.261115 0.261115 5090.35 5090.35 3807.37 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.228554 0.228554 0.228554 0.228554 4640.90 4640.90 3795.91 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.212010 0.212010 0.212010 0.212010 4326.41 4326.41 3807.37 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.152292 0.152292 0.152292 0.152292 3292.46 3292.46 2534.38 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.151386 0.151386 0.151386 0.151386 3278.65 3278.65 2534.38 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.161064 0.161064 0.161064 0.161064 3464.85 3464.85 2523.17 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.161683 0.161683 0.161683 0.161683 3472.17 3472.17 2523.17 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.265738 0.265738 0.265738 0.265738 5194.08 5194.08 3895.14 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.261010 0.261010 0.261010 0.261010 5115.75 5115.75 3907.73 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.228777 0.228777 0.228777 0.228777 4669.70 4669.70 3895.14 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.211883 0.211883 0.211883 0.211883 4355.99 4355.99 3907.73 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.152284 0.152284 0.152284 0.152284 3306.89 3306.89 2600.66 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.151387 0.151387 0.151387 0.151387 3293.18 3293.18 2600.66 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.160872 0.160872 0.160872 0.160872 3476.76 3476.76 2588.32 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.161472 0.161472 0.161472 0.161472 3483.86 3483.86 2588.32 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.266914 0.266914 0.266914 0.266914 5235.52 5235.52 3993.96 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.262262 0.262262 0.262262 0.262262 5158.18 5158.18 4007.24 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.230241 0.230241 0.230241 0.230241 4714.22 4714.22 3993.96 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.213089 0.213089 0.213089 0.213089 4396.26 4396.26 4007.24 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.153612 0.153612 0.153612 0.153612 3339.91 3339.91 2669.74 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.152725 0.152725 0.152725 0.152725 3326.31 3326.31 2669.74 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.161973 0.161973 0.161973 0.161973 3506.45 3506.45 2656.69 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.162555 0.162555 0.162555 0.162555 3513.31 3513.31 2656.69 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.277545 0.277545 0.277545 0.277545 5413.81 5413.81 4208.73 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.273047 0.273047 0.273047 0.273047 5338.92 5338.92 4220.26 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.238873 0.238873 0.238873 0.238873 4863.88 4863.88 4208.73 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.218881 0.218881 0.218881 0.218881 4503.70 4503.70 4220.26 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.163340 0.163340 0.163340 0.163340 3498.59 3498.59 2846.73 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.162447 0.162447 0.162447 0.162447 3484.99 3484.99 2846.73 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.169425 0.169425 0.169425 0.169425 3630.79 3630.79 2834.99 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.170035 0.170035 0.170035 0.170035 3639.73 3639.73 2834.99 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.348908 0.348908 0.348908 0.348908 6492.52 6492.52 4832.87 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.337357 0.337357 0.337357 0.337357 6310.39 6310.39 4850.74 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.311321 0.311321 0.311321 0.311321 5949.07 5949.07 4832.87 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.278258 0.278258 0.278258 0.278258 5420.29 5420.29 4850.74 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.215344 0.215344 0.215344 0.215344 4323.83 4323.83 3509.69 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.215292 0.215292 0.215292 0.215292 4322.73 4322.73 3509.69 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.246821 0.246821 0.246821 0.246821 4779.92 4779.92 3488.70 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.247341 0.247341 0.247341 0.247341 4787.24 4787.24 3488.70 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.210212
AIRLOOP G NW SUPPLY FAN 0.206443
AIRLOOP OFFICE SUPPLY FAN 0.315353
AIRLOOP G NE SUPPLY FAN 0.161511
AIRLOOP G N1 SUPPLY FAN 0.114578
AIRLOOP G N2 SUPPLY FAN 0.113403
AIRLOOP G S1 SUPPLY FAN 0.121467
AIRLOOP G S2 SUPPLY FAN 0.127277
AIRLOOP F2 SW SUPPLY FAN 0.261267
AIRLOOP F2 NW SUPPLY FAN 0.255606
AIRLOOP F2 SE SUPPLY FAN 0.244527
AIRLOOP F2 NE SUPPLY FAN 0.205664
AIRLOOP F2 N1 SUPPLY FAN 0.145607
AIRLOOP F2 N2 SUPPLY FAN 0.144650
AIRLOOP F2 S1 SUPPLY FAN 0.155296
AIRLOOP F2 S2 SUPPLY FAN 0.157280
AIRLOOP F3 SW SUPPLY FAN 0.262875
AIRLOOP F3 NW SUPPLY FAN 0.257763
AIRLOOP F3 SE SUPPLY FAN 0.227116
AIRLOOP F3 NE SUPPLY FAN 0.208829
AIRLOOP F3 N1 SUPPLY FAN 0.148623
AIRLOOP F3 N2 SUPPLY FAN 0.147683
AIRLOOP F3 S1 SUPPLY FAN 0.158161
AIRLOOP F3 S2 SUPPLY FAN 0.158982
AIRLOOP F4 SW SUPPLY FAN 0.264584
AIRLOOP F4 NW SUPPLY FAN 0.259611
AIRLOOP F4 SE SUPPLY FAN 0.226903
AIRLOOP F4 NE SUPPLY FAN 0.210601
AIRLOOP F4 N1 SUPPLY FAN 0.150604
AIRLOOP F4 N2 SUPPLY FAN 0.149676
AIRLOOP F4 S1 SUPPLY FAN 0.159838
AIRLOOP F4 S2 SUPPLY FAN 0.160487
AIRLOOP M SW SUPPLY FAN 0.268064
AIRLOOP M NW SUPPLY FAN 0.263254
AIRLOOP M SE SUPPLY FAN 0.230223
AIRLOOP M NE SUPPLY FAN 0.214150
AIRLOOP M N1 SUPPLY FAN 0.154223
AIRLOOP M N2 SUPPLY FAN 0.153304
AIRLOOP M S1 SUPPLY FAN 0.163166
AIRLOOP M S2 SUPPLY FAN 0.163790
AIRLOOP F6 SW SUPPLY FAN 0.265923
AIRLOOP F6 NW SUPPLY FAN 0.261115
AIRLOOP F6 SE SUPPLY FAN 0.228554
AIRLOOP F6 NE SUPPLY FAN 0.212010
AIRLOOP F6 N1 SUPPLY FAN 0.152292
AIRLOOP F6 N2 SUPPLY FAN 0.151386
AIRLOOP F6 S1 SUPPLY FAN 0.161064
AIRLOOP F6 S2 SUPPLY FAN 0.161683
AIRLOOP F7 SW SUPPLY FAN 0.265738
AIRLOOP F7 NW SUPPLY FAN 0.261010
AIRLOOP F7 SE SUPPLY FAN 0.228777
AIRLOOP F7 NE SUPPLY FAN 0.211883
AIRLOOP F7 N1 SUPPLY FAN 0.152284
AIRLOOP F7 N2 SUPPLY FAN 0.151387
AIRLOOP F7 S1 SUPPLY FAN 0.160872
AIRLOOP F7 S2 SUPPLY FAN 0.161472
AIRLOOP F8 SW SUPPLY FAN 0.266914
AIRLOOP F8 NW SUPPLY FAN 0.262262
AIRLOOP F8 SE SUPPLY FAN 0.230241
AIRLOOP F8 NE SUPPLY FAN 0.213089
AIRLOOP F8 N1 SUPPLY FAN 0.153612
AIRLOOP F8 N2 SUPPLY FAN 0.152725
AIRLOOP F8 S1 SUPPLY FAN 0.161973
AIRLOOP F8 S2 SUPPLY FAN 0.162555
AIRLOOP F9 SW SUPPLY FAN 0.277545
AIRLOOP F9 NW SUPPLY FAN 0.273047
AIRLOOP F9 SE SUPPLY FAN 0.238873
AIRLOOP F9 NE SUPPLY FAN 0.218881
AIRLOOP F9 N1 SUPPLY FAN 0.163340
AIRLOOP F9 N2 SUPPLY FAN 0.162447
AIRLOOP F9 S1 SUPPLY FAN 0.169425
AIRLOOP F9 S2 SUPPLY FAN 0.170035
AIRLOOP T SW SUPPLY FAN 0.348908
AIRLOOP T NW SUPPLY FAN 0.337357
AIRLOOP T SE SUPPLY FAN 0.311321
AIRLOOP T NE SUPPLY FAN 0.278258
AIRLOOP T N1 SUPPLY FAN 0.215344
AIRLOOP T N2 SUPPLY FAN 0.215292
AIRLOOP T S1 SUPPLY FAN 0.246821
AIRLOOP T S2 SUPPLY FAN 0.247341


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.210212 4089.33 0.000089
HEAT PUMP HEATING MODE AIRLOOP G NW 0.206443 4025.42 0.000088
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.315353 5922.42 0.000129
HEAT PUMP HEATING MODE AIRLOOP G NE 0.161511 3326.60 0.000073
HEAT PUMP HEATING MODE AIRLOOP G N1 0.114578 2580.22 0.000056
HEAT PUMP HEATING MODE AIRLOOP G N2 0.113403 2562.41 0.000056
HEAT PUMP HEATING MODE AIRLOOP G S1 0.121467 2729.55 0.000060
HEAT PUMP HEATING MODE AIRLOOP G S2 0.127277 2815.25 0.000061
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.261267 4927.57 0.000108
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.255606 4837.03 0.000106
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.244527 4665.33 0.000102
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.205664 4070.88 0.000089
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.145607 3099.53 0.000068
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.144650 3085.19 0.000067
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.155296 3283.13 0.000072
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.157280 3312.09 0.000072
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.262875 5012.12 0.000109
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.257763 4929.13 0.000108
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.227116 4472.45 0.000098
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.208829 4174.31 0.000091
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.148623 3176.97 0.000069
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.147683 3162.83 0.000069
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.158161 3358.42 0.000073
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.158982 3370.37 0.000074
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.264584 5082.31 0.000111
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.259611 5001.06 0.000109
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.226903 4512.72 0.000099
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.210601 4242.66 0.000093
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.150604 3230.82 0.000071
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.149676 3216.78 0.000070
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.159838 3407.92 0.000074
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.160487 3417.37 0.000075
HEAT PUMP HEATING MODE AIRLOOP M SW 0.268064 5169.68 0.000113
HEAT PUMP HEATING MODE AIRLOOP M NW 0.263254 5090.66 0.000111
HEAT PUMP HEATING MODE AIRLOOP M SE 0.230223 4636.25 0.000101
HEAT PUMP HEATING MODE AIRLOOP M NE 0.214150 4329.25 0.000095
HEAT PUMP HEATING MODE AIRLOOP M N1 0.154223 3304.58 0.000072
HEAT PUMP HEATING MODE AIRLOOP M N2 0.153304 3290.66 0.000072
HEAT PUMP HEATING MODE AIRLOOP M S1 0.163166 3477.34 0.000076
HEAT PUMP HEATING MODE AIRLOOP M S2 0.163790 3486.43 0.000076
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.265923 5169.64 0.000113
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.261115 5090.35 0.000111
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.228554 4640.90 0.000101
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.212010 4326.41 0.000095
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.152292 3292.46 0.000072
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.151386 3278.65 0.000072
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.161064 3464.85 0.000076
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.161683 3472.17 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.265738 5194.08 0.000113
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.261010 5115.75 0.000112
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.228777 4669.70 0.000102
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.211883 4355.99 0.000095
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.152284 3306.89 0.000072
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.151387 3293.18 0.000072
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.160872 3476.76 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.161472 3483.86 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.266914 5235.52 0.000114
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.262262 5158.18 0.000113
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.230241 4714.22 0.000103
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.213089 4396.26 0.000096
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.153612 3339.91 0.000073
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.152725 3326.31 0.000073
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.161973 3506.45 0.000077
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.162555 3513.31 0.000077
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.277545 5413.81 0.000118
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.273047 5338.92 0.000117
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.238873 4863.88 0.000106
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.218881 4503.70 0.000098
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.163340 3498.59 0.000076
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.162447 3484.99 0.000076
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.169425 3630.79 0.000079
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.170035 3639.73 0.000080
HEAT PUMP HEATING MODE AIRLOOP T SW 0.348908 6492.52 0.000142
HEAT PUMP HEATING MODE AIRLOOP T NW 0.337357 6310.39 0.000138
HEAT PUMP HEATING MODE AIRLOOP T SE 0.311321 5949.07 0.000130
HEAT PUMP HEATING MODE AIRLOOP T NE 0.278258 5420.29 0.000118
HEAT PUMP HEATING MODE AIRLOOP T N1 0.215344 4323.83 0.000094
HEAT PUMP HEATING MODE AIRLOOP T N2 0.215292 4322.73 0.000094
HEAT PUMP HEATING MODE AIRLOOP T S1 0.246821 4779.92 0.000104
HEAT PUMP HEATING MODE AIRLOOP T S2 0.247341 4787.24 0.000105


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 3368.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 3370.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 4164.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 3370.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 2526.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 2526.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 2521.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 2527.68
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 3396.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 3397.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 3414.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 3397.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 2334.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 2334.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 2336.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 2337.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 3472.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 3477.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 3474.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 3477.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 2343.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 2343.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 2339.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 2339.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 3584.04
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 3592.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 3584.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 3592.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 2403.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 2403.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 2395.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 2395.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 3665.19
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 3674.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 3665.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 3674.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 2441.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 2441.15
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 2432.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 2432.44
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 3795.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 3807.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 3795.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 3807.37
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 2534.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 2534.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 2523.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 2523.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 3895.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 3907.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 3895.14
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 3907.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 2600.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 2600.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 2588.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 2588.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 3993.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 4007.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 3993.96
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 4007.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 2669.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 2669.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 2656.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 2656.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 4208.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 4220.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 4208.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 4220.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 2846.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 2846.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 2834.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 2834.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 4832.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 4850.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 4832.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 4850.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 3509.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 3509.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 3488.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 3488.70


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.007241 8.15


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.007241


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.007241 3495.43 9.29 10743.26


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.007241 2312.31



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 19:11:14

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 4.12
February 22.06 6.58
March 22.61 12.40
April 23.21 16.79
May 24.03 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.64 16.70
November 22.73 12.13
December 22.05 6.84
     
Annual Sum or Average 23.32 17.04
Minimum of Months 21.93 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 4.12
February 21.79 6.58
March 22.26 12.40
April 23.05 16.79
May 24.03 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.35 24.35
October 23.24 16.70
November 22.22 12.13
December 21.78 6.84
     
Annual Sum or Average 23.14 17.04
Minimum of Months 21.74 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 4.12
February 22.39 6.58
March 23.18 12.40
April 23.79 16.79
May 24.33 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 23.97 16.70
November 23.20 12.13
December 22.43 6.84
     
Annual Sum or Average 23.60 17.04
Minimum of Months 22.19 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 4.12
February 21.76 6.58
March 22.17 12.40
April 23.00 16.79
May 24.01 22.07
June 24.38 26.01
July 24.41 28.31
August 24.39 27.55
September 24.36 24.35
October 23.13 16.70
November 22.13 12.13
December 21.76 6.84
     
Annual Sum or Average 23.11 17.04
Minimum of Months 21.72 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 4.12
February 21.75 6.58
March 22.10 12.40
April 22.83 16.79
May 23.93 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.34 24.35
October 23.05 16.70
November 22.11 12.13
December 21.76 6.84
     
Annual Sum or Average 23.07 17.04
Minimum of Months 21.72 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 4.12
February 21.75 6.58
March 22.09 12.40
April 22.83 16.79
May 23.92 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.34 24.35
October 23.04 16.70
November 22.10 12.13
December 21.76 6.84
     
Annual Sum or Average 23.07 17.04
Minimum of Months 21.72 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 4.12
February 22.06 6.58
March 22.53 12.40
April 23.09 16.79
May 23.97 22.07
June 24.37 26.01
July 24.40 28.31
August 24.41 27.55
September 24.38 24.35
October 23.62 16.70
November 22.74 12.13
December 22.08 6.84
     
Annual Sum or Average 23.31 17.04
Minimum of Months 21.94 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.96 4.12
February 22.09 6.58
March 22.58 12.40
April 23.14 16.79
May 24.00 22.07
June 24.38 26.01
July 24.40 28.31
August 24.41 27.55
September 24.38 24.35
October 23.66 16.70
November 22.80 12.13
December 22.12 6.84
     
Annual Sum or Average 23.33 17.04
Minimum of Months 21.96 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.68 4.12
February 17.57 6.58
March 19.97 12.40
April 21.81 16.79
May 24.11 22.07
June 26.17 26.01
July 27.05 28.31
August 26.80 27.55
September 25.63 24.35
October 22.13 16.70
November 20.00 12.13
December 17.75 6.84
     
Annual Sum or Average 22.16 17.04
Minimum of Months 16.68 4.12
Maximum of Months 27.05 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.09 4.12
February 22.34 6.58
March 23.19 12.40
April 23.75 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 24.17 16.70
November 23.30 12.13
December 22.25 6.84
     
Annual Sum or Average 23.58 17.04
Minimum of Months 22.09 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.12
February 21.89 6.58
March 22.70 12.40
April 23.52 16.79
May 24.26 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 23.80 16.70
November 22.64 12.13
December 21.82 6.84
     
Annual Sum or Average 23.34 17.04
Minimum of Months 21.78 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.10 4.12
February 22.41 6.58
March 23.30 12.40
April 23.85 16.79
May 24.31 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 24.22 16.70
November 23.39 12.13
December 22.34 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 22.10 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.85 6.58
March 22.57 12.40
April 23.47 16.79
May 24.26 22.07
June 24.40 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 23.70 16.70
November 22.52 12.13
December 21.80 6.84
     
Annual Sum or Average 23.30 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 4.12
February 21.85 6.58
March 22.56 12.40
April 23.36 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.68 16.70
November 22.56 12.13
December 21.81 6.84
     
Annual Sum or Average 23.29 17.04
Minimum of Months 21.77 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 4.12
February 21.85 6.58
March 22.55 12.40
April 23.35 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.67 16.70
November 22.55 12.13
December 21.81 6.84
     
Annual Sum or Average 23.28 17.04
Minimum of Months 21.77 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 4.12
February 22.43 6.58
March 23.19 12.40
April 23.68 16.79
May 24.24 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.18 16.70
November 23.41 12.13
December 22.41 6.84
     
Annual Sum or Average 23.62 17.04
Minimum of Months 22.18 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 4.12
February 22.44 6.58
March 23.21 12.40
April 23.70 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.19 16.70
November 23.43 12.13
December 22.43 6.84
     
Annual Sum or Average 23.62 17.04
Minimum of Months 22.18 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.65 4.12
February 22.11 6.58
March 23.58 12.40
April 24.60 16.79
May 25.76 22.07
June 26.44 26.01
July 26.67 28.31
August 26.61 27.55
September 26.29 24.35
October 25.04 16.70
November 23.66 12.13
December 22.19 6.84
     
Annual Sum or Average 24.56 17.04
Minimum of Months 21.65 4.12
Maximum of Months 26.67 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.09 4.12
February 22.38 6.58
March 23.27 12.40
April 23.81 16.79
May 24.28 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 24.23 16.70
November 23.39 12.13
December 22.25 6.84
     
Annual Sum or Average 23.61 17.04
Minimum of Months 22.09 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.90 6.58
March 22.79 12.40
April 23.59 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 23.90 16.70
November 22.76 12.13
December 21.82 6.84
     
Annual Sum or Average 23.37 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 4.12
February 22.37 6.58
March 23.23 12.40
April 23.82 16.79
May 24.30 22.07
June 24.40 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.21 16.70
November 23.36 12.13
December 22.24 6.84
     
Annual Sum or Average 23.60 17.04
Minimum of Months 22.04 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.86 6.58
March 22.67 12.40
April 23.55 16.79
May 24.28 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.82 16.70
November 22.65 12.13
December 21.80 6.84
     
Annual Sum or Average 23.34 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.89 6.58
March 22.70 12.40
April 23.47 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.84 16.70
November 22.72 12.13
December 21.82 6.84
     
Annual Sum or Average 23.34 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.12
February 21.88 6.58
March 22.69 12.40
April 23.47 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.83 16.70
November 22.71 12.13
December 21.82 6.84
     
Annual Sum or Average 23.34 17.04
Minimum of Months 21.78 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.21 4.12
February 22.51 6.58
March 23.33 12.40
April 23.79 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.25 16.70
November 23.54 12.13
December 22.49 6.84
     
Annual Sum or Average 23.67 17.04
Minimum of Months 22.21 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.21 4.12
February 22.51 6.58
March 23.34 12.40
April 23.79 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.25 16.70
November 23.54 12.13
December 22.49 6.84
     
Annual Sum or Average 23.67 17.04
Minimum of Months 22.21 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.06 4.12
February 22.53 6.58
March 24.01 12.40
April 24.98 16.79
May 26.03 22.07
June 26.51 26.01
July 26.69 28.31
August 26.64 27.55
September 26.37 24.35
October 25.44 16.70
November 24.12 12.13
December 22.59 6.84
     
Annual Sum or Average 24.84 17.04
Minimum of Months 22.06 4.12
Maximum of Months 26.69 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.06 4.12
February 22.37 6.58
March 23.26 12.40
April 23.81 16.79
May 24.29 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 24.23 16.70
November 23.40 12.13
December 22.22 6.84
     
Annual Sum or Average 23.61 17.04
Minimum of Months 22.06 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.12
February 21.91 6.58
March 22.80 12.40
April 23.60 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 23.95 16.70
November 22.80 12.13
December 21.82 6.84
     
Annual Sum or Average 23.38 17.04
Minimum of Months 21.78 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 4.12
February 22.35 6.58
March 23.19 12.40
April 23.80 16.79
May 24.30 22.07
June 24.40 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.22 16.70
November 23.36 12.13
December 22.18 6.84
     
Annual Sum or Average 23.59 17.04
Minimum of Months 22.00 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.87 6.58
March 22.67 12.40
April 23.55 16.79
May 24.28 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.87 16.70
November 22.70 12.13
December 21.79 6.84
     
Annual Sum or Average 23.35 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.90 6.58
March 22.74 12.40
April 23.50 16.79
May 24.26 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.91 16.70
November 22.80 12.13
December 21.82 6.84
     
Annual Sum or Average 23.36 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.90 6.58
March 22.73 12.40
April 23.50 16.79
May 24.26 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.90 16.70
November 22.79 12.13
December 21.82 6.84
     
Annual Sum or Average 23.36 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 4.12
February 22.52 6.58
March 23.35 12.40
April 23.81 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.26 16.70
November 23.57 12.13
December 22.47 6.84
     
Annual Sum or Average 23.68 17.04
Minimum of Months 22.19 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.19 4.12
February 22.52 6.58
March 23.35 12.40
April 23.81 16.79
May 24.28 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.26 16.70
November 23.57 12.13
December 22.47 6.84
     
Annual Sum or Average 23.68 17.04
Minimum of Months 22.19 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.16 4.12
February 22.65 6.58
March 24.15 12.40
April 25.11 16.79
May 26.14 22.07
June 26.59 26.01
July 26.76 28.31
August 26.71 27.55
September 26.45 24.35
October 25.60 16.70
November 24.29 12.13
December 22.70 6.84
     
Annual Sum or Average 24.95 17.04
Minimum of Months 22.16 4.12
Maximum of Months 26.76 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 4.12
February 22.35 6.58
March 23.23 12.40
April 23.79 16.79
May 24.28 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 24.23 16.70
November 23.40 12.13
December 22.19 6.84
     
Annual Sum or Average 23.60 17.04
Minimum of Months 22.04 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 4.12
February 21.90 6.58
March 22.78 12.40
April 23.58 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 23.95 16.70
November 22.82 12.13
December 21.81 6.84
     
Annual Sum or Average 23.38 17.04
Minimum of Months 21.78 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 4.12
February 22.32 6.58
March 23.16 12.40
April 23.78 16.79
May 24.29 22.07
June 24.40 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.21 16.70
November 23.35 12.13
December 22.15 6.84
     
Annual Sum or Average 23.58 17.04
Minimum of Months 21.98 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.86 6.58
March 22.66 12.40
April 23.54 16.79
May 24.27 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.88 16.70
November 22.71 12.13
December 21.79 6.84
     
Annual Sum or Average 23.35 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.90 6.58
March 22.74 12.40
April 23.50 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.93 16.70
November 22.83 12.13
December 21.82 6.84
     
Annual Sum or Average 23.37 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 4.12
February 21.90 6.58
March 22.73 12.40
April 23.50 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.92 16.70
November 22.82 12.13
December 21.82 6.84
     
Annual Sum or Average 23.36 17.04
Minimum of Months 21.79 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.17 4.12
February 22.51 6.58
March 23.34 12.40
April 23.80 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.27 16.70
November 23.57 12.13
December 22.45 6.84
     
Annual Sum or Average 23.67 17.04
Minimum of Months 22.17 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.17 4.12
February 22.51 6.58
March 23.33 12.40
April 23.80 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.40 24.35
October 24.26 16.70
November 23.56 12.13
December 22.45 6.84
     
Annual Sum or Average 23.67 17.04
Minimum of Months 22.17 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 4.12
February 23.21 6.58
March 24.69 12.40
April 25.65 16.79
May 26.67 22.07
June 27.12 26.01
July 27.29 28.31
August 27.24 27.55
September 26.98 24.35
October 26.16 16.70
November 24.85 12.13
December 23.25 6.84
     
Annual Sum or Average 25.50 17.04
Minimum of Months 22.69 4.12
Maximum of Months 27.29 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.99 4.12
February 22.28 6.58
March 23.14 12.40
April 23.73 16.79
May 24.26 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 24.20 16.70
November 23.33 12.13
December 22.12 6.84
     
Annual Sum or Average 23.56 17.04
Minimum of Months 21.99 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.87 6.58
March 22.68 12.40
April 23.51 16.79
May 24.24 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.89 16.70
November 22.74 12.13
December 21.80 6.84
     
Annual Sum or Average 23.34 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 4.12
February 22.26 6.58
March 23.06 12.40
April 23.71 16.79
May 24.27 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.18 16.70
November 23.29 12.13
December 22.09 6.84
     
Annual Sum or Average 23.54 17.04
Minimum of Months 21.94 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 4.12
February 21.83 6.58
March 22.56 12.40
April 23.47 16.79
May 24.25 22.07
June 24.40 26.01
July 24.41 28.31
August 24.40 27.55
September 24.38 24.35
October 23.81 16.70
November 22.64 12.13
December 21.78 6.84
     
Annual Sum or Average 23.31 17.04
Minimum of Months 21.74 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 4.12
February 21.87 6.58
March 22.65 12.40
April 23.43 16.79
May 24.23 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.86 16.70
November 22.75 12.13
December 21.80 6.84
     
Annual Sum or Average 23.33 17.04
Minimum of Months 21.77 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 4.12
February 21.87 6.58
March 22.63 12.40
April 23.43 16.79
May 24.23 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.85 16.70
November 22.74 12.13
December 21.80 6.84
     
Annual Sum or Average 23.33 17.04
Minimum of Months 21.77 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.11 4.12
February 22.43 6.58
March 23.23 12.40
April 23.73 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.24 16.70
November 23.50 12.13
December 22.36 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 22.11 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.11 4.12
February 22.43 6.58
March 23.23 12.40
April 23.73 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.24 16.70
November 23.50 12.13
December 22.36 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 22.11 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.05 4.12
February 22.55 6.58
March 24.03 12.40
April 25.02 16.79
May 26.10 22.07
June 26.58 26.01
July 26.75 28.31
August 26.70 27.55
September 26.43 24.35
October 25.55 16.70
November 24.22 12.13
December 22.60 6.84
     
Annual Sum or Average 24.90 17.04
Minimum of Months 22.05 4.12
Maximum of Months 26.75 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.96 4.12
February 22.23 6.58
March 23.06 12.40
April 23.68 16.79
May 24.24 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 24.17 16.70
November 23.29 12.13
December 22.08 6.84
     
Annual Sum or Average 23.53 17.04
Minimum of Months 21.96 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.85 6.58
March 22.61 12.40
April 23.46 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.83 16.70
November 22.69 12.13
December 21.79 6.84
     
Annual Sum or Average 23.32 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 4.12
February 22.21 6.58
March 22.98 12.40
April 23.66 16.79
May 24.25 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.15 16.70
November 23.24 12.13
December 22.04 6.84
     
Annual Sum or Average 23.51 17.04
Minimum of Months 21.91 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.82 6.58
March 22.49 12.40
April 23.42 16.79
May 24.23 22.07
June 24.39 26.01
July 24.41 28.31
August 24.40 27.55
September 24.37 24.35
October 23.75 16.70
November 22.59 12.13
December 21.77 6.84
     
Annual Sum or Average 23.29 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.85 6.58
March 22.57 12.40
April 23.38 16.79
May 24.21 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.81 16.70
November 22.68 12.13
December 21.79 6.84
     
Annual Sum or Average 23.31 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.85 6.58
March 22.56 12.40
April 23.38 16.79
May 24.21 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.80 16.70
November 22.67 12.13
December 21.79 6.84
     
Annual Sum or Average 23.30 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.07 4.12
February 22.37 6.58
March 23.16 12.40
April 23.67 16.79
May 24.23 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.22 16.70
November 23.45 12.13
December 22.30 6.84
     
Annual Sum or Average 23.59 17.04
Minimum of Months 22.07 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.07 4.12
February 22.37 6.58
March 23.15 12.40
April 23.67 16.79
May 24.23 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.22 16.70
November 23.44 12.13
December 22.29 6.84
     
Annual Sum or Average 23.59 17.04
Minimum of Months 22.07 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 4.12
February 22.40 6.58
March 23.86 12.40
April 24.88 16.79
May 26.00 22.07
June 26.51 26.01
July 26.69 28.31
August 26.63 27.55
September 26.36 24.35
October 25.43 16.70
November 24.07 12.13
December 22.44 6.84
     
Annual Sum or Average 24.77 17.04
Minimum of Months 21.90 4.12
Maximum of Months 26.69 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 4.12
February 22.18 6.58
March 23.00 12.40
April 23.64 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 24.15 16.70
November 23.25 12.13
December 22.04 6.84
     
Annual Sum or Average 23.50 17.04
Minimum of Months 21.94 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 4.12
February 21.83 6.58
March 22.55 12.40
April 23.43 16.79
May 24.21 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.37 24.35
October 23.79 16.70
November 22.64 12.13
December 21.78 6.84
     
Annual Sum or Average 23.30 17.04
Minimum of Months 21.74 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 4.12
February 22.17 6.58
March 22.92 12.40
April 23.62 16.79
May 24.24 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.38 24.35
October 24.13 16.70
November 23.20 12.13
December 22.01 6.84
     
Annual Sum or Average 23.48 17.04
Minimum of Months 21.89 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.80 6.58
March 22.44 12.40
April 23.39 16.79
May 24.21 22.07
June 24.39 26.01
July 24.41 28.31
August 24.40 27.55
September 24.37 24.35
October 23.70 16.70
November 22.54 12.13
December 21.76 6.84
     
Annual Sum or Average 23.27 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.84 6.58
March 22.52 12.40
April 23.35 16.79
May 24.19 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.76 16.70
November 22.63 12.13
December 21.78 6.84
     
Annual Sum or Average 23.29 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.84 6.58
March 22.51 12.40
April 23.34 16.79
May 24.19 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.75 16.70
November 22.62 12.13
December 21.78 6.84
     
Annual Sum or Average 23.28 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 4.12
February 22.33 6.58
March 23.09 12.40
April 23.63 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.20 16.70
November 23.40 12.13
December 22.24 6.84
     
Annual Sum or Average 23.57 17.04
Minimum of Months 22.04 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 4.12
February 22.32 6.58
March 23.09 12.40
April 23.63 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.20 16.70
November 23.40 12.13
December 22.24 6.84
     
Annual Sum or Average 23.57 17.04
Minimum of Months 22.04 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 4.12
February 22.31 6.58
March 23.77 12.40
April 24.82 16.79
May 25.98 22.07
June 26.51 26.01
July 26.70 28.31
August 26.64 27.55
September 26.35 24.35
October 25.36 16.70
November 23.98 12.13
December 22.36 6.84
     
Annual Sum or Average 24.73 17.04
Minimum of Months 21.81 4.12
Maximum of Months 26.70 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 4.12
February 22.16 6.58
March 22.94 12.40
April 23.61 16.79
May 24.21 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.38 24.35
October 24.10 16.70
November 23.19 12.13
December 22.01 6.84
     
Annual Sum or Average 23.48 17.04
Minimum of Months 21.91 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 4.12
February 21.83 6.58
March 22.52 12.40
April 23.41 16.79
May 24.20 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.73 16.70
November 22.59 12.13
December 21.78 6.84
     
Annual Sum or Average 23.29 17.04
Minimum of Months 21.74 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 4.12
February 22.14 6.58
March 22.86 12.40
April 23.59 16.79
May 24.22 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 24.08 16.70
November 23.14 12.13
December 21.98 6.84
     
Annual Sum or Average 23.46 17.04
Minimum of Months 21.87 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.80 6.58
March 22.41 12.40
April 23.37 16.79
May 24.20 22.07
June 24.39 26.01
July 24.41 28.31
August 24.40 27.55
September 24.37 24.35
October 23.63 16.70
November 22.48 12.13
December 21.76 6.84
     
Annual Sum or Average 23.25 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.83 6.58
March 22.49 12.40
April 23.34 16.79
May 24.18 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.70 16.70
November 22.57 12.13
December 21.78 6.84
     
Annual Sum or Average 23.27 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.83 6.58
March 22.48 12.40
April 23.33 16.79
May 24.18 22.07
June 24.39 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.69 16.70
November 22.56 12.13
December 21.78 6.84
     
Annual Sum or Average 23.27 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 4.12
February 22.28 6.58
March 23.03 12.40
April 23.60 16.79
May 24.20 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.16 16.70
November 23.33 12.13
December 22.18 6.84
     
Annual Sum or Average 23.54 17.04
Minimum of Months 22.00 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 4.12
February 22.28 6.58
March 23.03 12.40
April 23.60 16.79
May 24.20 22.07
June 24.39 26.01
July 24.40 28.31
August 24.41 27.55
September 24.39 24.35
October 24.16 16.70
November 23.32 12.13
December 22.18 6.84
     
Annual Sum or Average 23.54 17.04
Minimum of Months 22.00 4.12
Maximum of Months 24.41 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.67 4.12
February 22.20 6.58
March 23.69 12.40
April 24.80 16.79
May 26.02 22.07
June 26.61 26.01
July 26.82 28.31
August 26.75 27.55
September 26.42 24.35
October 25.29 16.70
November 23.85 12.13
December 22.23 6.84
     
Annual Sum or Average 24.71 17.04
Minimum of Months 21.67 4.12
Maximum of Months 26.82 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.95 4.12
February 22.15 6.58
March 22.83 12.40
April 23.48 16.79
May 24.15 22.07
June 24.37 26.01
July 24.40 28.31
August 24.39 27.55
September 24.35 24.35
October 23.82 16.70
November 22.97 12.13
December 22.08 6.84
     
Annual Sum or Average 23.42 17.04
Minimum of Months 21.95 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.87 6.58
March 22.51 12.40
April 23.34 16.79
May 24.13 22.07
June 24.38 26.01
July 24.40 28.31
August 24.38 27.55
September 24.33 24.35
October 23.51 16.70
November 22.52 12.13
December 21.81 6.84
     
Annual Sum or Average 23.25 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 4.12
February 22.13 6.58
March 22.78 12.40
April 23.49 16.79
May 24.16 22.07
June 24.38 26.01
July 24.40 28.31
August 24.40 27.55
September 24.36 24.35
October 23.80 16.70
November 22.94 12.13
December 22.05 6.84
     
Annual Sum or Average 23.40 17.04
Minimum of Months 21.90 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 4.12
February 21.83 6.58
March 22.41 12.40
April 23.32 16.79
May 24.13 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.34 24.35
October 23.43 16.70
November 22.43 12.13
December 21.78 6.84
     
Annual Sum or Average 23.22 17.04
Minimum of Months 21.74 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.86 6.58
March 22.46 12.40
April 23.28 16.79
May 24.12 22.07
June 24.38 26.01
July 24.40 28.31
August 24.38 27.55
September 24.33 24.35
October 23.48 16.70
November 22.48 12.13
December 21.80 6.84
     
Annual Sum or Average 23.23 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 4.12
February 21.86 6.58
March 22.45 12.40
April 23.28 16.79
May 24.12 22.07
June 24.38 26.01
July 24.40 28.31
August 24.38 27.55
September 24.33 24.35
October 23.47 16.70
November 22.47 12.13
December 21.80 6.84
     
Annual Sum or Average 23.23 17.04
Minimum of Months 21.76 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 4.12
February 22.24 6.58
March 22.93 12.40
April 23.50 16.79
May 24.15 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.91 16.70
November 23.09 12.13
December 22.20 6.84
     
Annual Sum or Average 23.47 17.04
Minimum of Months 22.03 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 4.12
February 22.24 6.58
March 22.93 12.40
April 23.50 16.79
May 24.16 22.07
June 24.38 26.01
July 24.40 28.31
August 24.39 27.55
September 24.36 24.35
October 23.91 16.70
November 23.09 12.13
December 22.19 6.84
     
Annual Sum or Average 23.47 17.04
Minimum of Months 22.02 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 19:11:14

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 22.37 6.58
March 24.07 12.40
April 25.35 16.79
May 26.75 22.07
June 27.54 26.01
July 27.83 28.31
August 27.71 27.55
September 27.21 24.35
October 25.63 16.70
November 24.00 12.13
December 22.33 6.84
     
Annual Sum or Average 25.22 17.04
Minimum of Months 21.73 4.12
Maximum of Months 27.83 28.31



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 19:11:14

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.253136E+12 171519.599 06-JAN-18:00 13120.457 57042.023 19000.275 67655.596 0.000 10364.000 2349.239 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.211462E+12 132409.459 12-FEB-18:15 13120.457 57042.023 19000.275 28545.653 0.000 10364.000 2349.239 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.209223E+12 134902.356 27-MAR-16:15 11327.174 57142.088 19000.275 0.000 41321.728 0.000 2349.239 1766.655 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.212866E+12 156402.113 30-APR-16:30 11327.174 57042.023 19000.275 0.000 61900.326 0.000 2349.239 2795.265 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.272564E+12 174857.616 31-MAY-17:30 13120.457 57042.023 19000.275 0.000 77862.182 0.000 2349.239 3495.431 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.320073E+12 178286.671 25-JUN-17:30 13120.457 57042.023 19000.275 0.000 81484.123 0.000 2349.239 3302.545 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.353750E+12 180896.339 23-JUL-17:15 13120.457 57042.023 19000.275 0.000 83901.102 0.000 2349.239 3495.431 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.344438E+12 181326.709 29-AUG-18:30 14401.373 51749.961 19000.275 0.000 78343.458 10364.000 2349.239 3357.378 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.308383E+12 178725.300 22-SEP-17:00 13120.457 57042.023 19000.275 0.000 71520.004 10364.000 2349.239 3341.293 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.227236E+12 170284.638 01-OCT-17:45 13120.457 57042.023 19000.275 0.000 63227.189 10364.000 2349.239 3193.446 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.204992E+12 123146.051 30-NOV-17:45 11327.174 57142.088 19000.275 20968.116 0.000 10364.000 2349.239 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.227782E+12 135028.194 08-DEC-17:15 11327.174 57142.088 19000.275 32850.221 0.000 10364.000 2349.239 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.314591E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.204992E+12 123146.051   11327.174 51749.961 19000.275 0.000 0.000 0.000 2349.239 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.353750E+12 181326.709   14401.373 57142.088 19000.275 67655.596 83901.102 10364.000 2349.239 3495.431 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 19:11:14

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.306655E+12 370648.491 31-JAN-06:00 0.000 0.000 0.000 370648.491 75821.852 75821.852 294826.639
February 0.205451E+12 306277.182 12-FEB-06:30 0.000 0.000 0.000 306277.182 73531.063 73531.063 232746.120
March 0.119878E+12 179777.727 10-MAR-06:00 0.000 0.000 0.000 179777.727 74995.779 74995.779 104781.948
April 0.923372E+11 132694.883 13-APR-05:45 0.000 0.000 0.000 132694.883 71256.106 71256.106 61438.778
May 0.822138E+11 73553.565 01-MAY-06:00 0.000 0.000 0.000 73553.565 73553.565 73553.565 0.000
June 0.736141E+11 71406.264 01-JUN-06:45 0.000 0.000 0.000 71406.264 71406.264 71406.264 0.000
July 0.723490E+11 69937.219 01-JUL-06:45 0.000 0.000 0.000 69937.219 69937.219 69937.219 0.000
August 0.721356E+11 69840.704 31-AUG-06:00 0.000 0.000 0.000 69840.704 69840.704 69840.704 0.000
September 0.729670E+11 71184.239 30-SEP-06:00 0.000 0.000 0.000 71184.239 71184.239 71184.239 0.000
October 0.813604E+11 73268.645 31-OCT-06:00 0.000 0.000 0.000 73268.645 73268.645 73268.645 0.000
November 0.103480E+12 145622.816 30-NOV-13:30 0.000 0.000 0.000 145622.816 32467.427 32467.427 113155.389
December 0.194040E+12 254497.265 09-DEC-06:00 0.000 0.000 0.000 254497.265 74137.566 74137.566 180359.699
                     
Annual Sum or Average 0.147648E+13     0.000 0.000 0.000        
Minimum of Months 0.721356E+11 69840.704   0.000 0.000 0.000 69840.704 32467.427 32467.427 0.000
Maximum of Months 0.306655E+12 370648.491   0.000 0.000 0.000 370648.491 75821.852 75821.852 294826.639