Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Simulation Timestamp: 2015-09-09 19:12:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4506.85 | 575.11 | 638.37 |
Net Site Energy | 4506.85 | 575.11 | 638.37 |
Total Source Energy | 10208.19 | 1302.65 | 1445.94 |
Net Source Energy | 10208.19 | 1302.65 | 1445.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 213.87 | 772.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 553.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.24 | 0.00 | 0.00 | 0.00 | 0.00 | 313.33 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1178.71 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2555.34 | 1951.51 | 0.00 | 0.00 | 0.00 | 5091.84 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 772.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 213.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 99.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 553.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 52.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 4.24 | 0.00 | 0.00 | 0.00 | 0.00 | 313.33 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1178.71 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 130.71 | 276.42 | 0.00 | 0.00 | 0.00 | 0.72 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 361.95 | 276.42 | 0.00 | 0.00 | 0.00 | 0.72 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.75 | 249.03 | 0.00 | 0.00 | 0.00 | 0.65 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 326.08 | 249.03 | 0.00 | 0.00 | 0.00 | 0.65 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2555.34 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2555.34 | 100.00 |
Total On-Site and Utility Electric Sources | 2555.34 | 100.00 |
Total Electricity End Uses | 2555.34 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5091.84 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5091.84 | 100.00 |
Total Water End Uses | 5091.84 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 200.25 |
Time Setpoint Not Met During Occupied Cooling | 6.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 728.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11 |
RunPeriod | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Latitude [deg] | 49.18 |
Longitude [deg] | -123.2 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-DEC-17:15 | 16-DEC-18:00 | - | - | - | 11-JUL-17:15 |
Heating | 63322.24 | 183438.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1677.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 74728.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 163265.22 | 258166.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 183438.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 9220.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2106.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 17544.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1677.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 74728.68 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 677.34 | 837.72 | 0.00 | 0.00 | 0.00 |
Cooling | 313.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 514.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1752.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 165.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1277.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8092.75 | 2115.44 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 95.94 | 118.66 | 0.00 | 0.00 | 0.00 |
Cooling | 44.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 180.98 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1146.30 | 299.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 95.94 | 118.66 | 0.00 | 0.00 | 0.00 |
Cooling | 44.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 180.98 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1146.30 | 299.64 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00 | -7.00 | Wetbulb [C] | 2.90 | 100.00 |
VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 7.60 | 18.20 | Wetbulb [C] | 3.60 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.53 | 83.53 | 162.51 | |
Exterior Lighting Total | 10364.00 | 162.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 236149.76 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 188919.81 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3301.54 | 2450.76 | 850.78 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2296.82 | 1672.42 | 624.40 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5084.36 | 3812.04 | 1272.32 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1656.97 | 1180.74 | 476.23 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1012.32 | 696.39 | 315.93 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1015.61 | 696.74 | 318.87 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2446.12 | 1794.31 | 651.81 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2538.35 | 1866.42 | 671.93 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4248.57 | 3174.90 | 1073.67 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3026.90 | 2226.05 | 800.85 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4274.09 | 3193.58 | 1080.51 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2281.79 | 1658.55 | 623.24 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1458.60 | 1031.49 | 427.11 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1425.63 | 1006.67 | 418.96 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3187.56 | 2364.19 | 823.37 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3223.36 | 2392.18 | 831.18 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4284.54 | 3193.70 | 1090.84 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3079.39 | 2258.76 | 820.63 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4017.07 | 2983.73 | 1033.33 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2341.05 | 1697.58 | 643.47 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1523.54 | 1077.63 | 445.90 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1490.39 | 1052.69 | 437.70 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3246.84 | 2404.97 | 841.86 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3264.27 | 2418.61 | 845.66 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4295.85 | 3195.65 | 1100.20 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3093.12 | 2263.46 | 829.66 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4002.79 | 2965.89 | 1036.91 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2351.59 | 1700.56 | 651.03 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1541.54 | 1088.83 | 452.71 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1508.27 | 1063.84 | 444.43 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3263.55 | 2413.90 | 849.65 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3278.36 | 2425.48 | 852.88 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4329.52 | 3216.35 | 1113.17 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3127.84 | 2285.60 | 842.24 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4036.10 | 2986.42 | 1049.68 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2382.94 | 1720.68 | 662.26 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1578.24 | 1114.73 | 463.51 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1544.93 | 1089.72 | 455.21 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3300.66 | 2439.50 | 861.16 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3315.10 | 2450.79 | 864.31 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4283.41 | 3175.71 | 1107.69 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3081.49 | 2245.71 | 835.78 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3993.20 | 2948.45 | 1044.75 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2335.57 | 1680.64 | 654.94 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1537.18 | 1081.85 | 455.33 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1503.94 | 1056.98 | 446.96 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3257.67 | 2403.14 | 854.53 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3272.10 | 2414.42 | 857.68 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4265.64 | 3157.79 | 1107.84 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3063.90 | 2228.66 | 835.24 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3978.07 | 2932.71 | 1045.36 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2316.23 | 1662.79 | 653.45 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1523.20 | 1069.83 | 453.37 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1490.01 | 1045.05 | 444.96 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3242.58 | 2388.91 | 853.67 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3257.02 | 2400.19 | 856.83 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4260.80 | 3150.40 | 1110.40 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3059.92 | 2222.54 | 837.38 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3975.22 | 2926.97 | 1048.25 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2309.84 | 1655.30 | 654.54 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1523.36 | 1068.69 | 454.67 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1490.25 | 1044.01 | 446.24 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3240.17 | 2384.83 | 855.34 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3254.64 | 2396.13 | 858.51 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4335.87 | 3205.47 | 1130.40 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3138.96 | 2280.68 | 858.27 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4033.47 | 2968.41 | 1065.06 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2309.30 | 1652.43 | 656.88 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1596.30 | 1122.64 | 473.65 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1562.89 | 1097.70 | 465.19 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3289.87 | 2420.97 | 868.90 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3304.39 | 2432.30 | 872.08 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5209.30 | 3880.80 | 1328.50 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3789.16 | 2781.96 | 1007.21 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4834.41 | 3589.33 | 1245.08 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2848.36 | 2061.68 | 786.69 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2104.10 | 1500.74 | 603.36 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2106.64 | 1502.64 | 604.00 | 0.71 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4233.06 | 3155.17 | 1077.89 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4247.16 | 3166.21 | 1080.94 | 0.75 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3301.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2296.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5084.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1656.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1012.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1015.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2446.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2538.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4248.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3026.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4274.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2281.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1458.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1425.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3187.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3223.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4284.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3079.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4017.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2341.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1523.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1490.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3246.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3264.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4295.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3093.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4002.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2351.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1541.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1508.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3263.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3278.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4329.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3127.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4036.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2382.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1578.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1544.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3300.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3315.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4283.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3081.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3993.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2335.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1537.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1503.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3257.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3272.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4265.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3063.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3978.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2316.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1523.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1490.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3242.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3257.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4260.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3059.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3975.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2309.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1523.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1490.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3240.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3254.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4335.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3138.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4033.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2309.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1596.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1562.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3289.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3304.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5209.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3789.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4834.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2848.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2104.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2106.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4233.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4247.16 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2947.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2952.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3720.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2949.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2241.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2241.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2232.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2238.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2880.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2880.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2896.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2878.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1997.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1997.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1999.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 2000.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2901.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2902.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2902.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2901.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1973.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1973.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1972.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1972.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2969.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2971.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2969.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2971.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 2004.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 2004.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 2003.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 2003.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 3015.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 3015.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 3015.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 3016.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 2020.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 2020.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 2020.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 2020.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 3114.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 3116.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 3115.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 3117.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 2093.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 2093.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 2092.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 2092.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 3186.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 3188.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 3188.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 3190.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 2142.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 2142.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 2141.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 2141.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 3261.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 3262.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 3263.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 3264.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2196.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2196.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2195.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2195.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 3449.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 3448.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 3452.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 3451.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2356.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2356.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2358.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2358.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 4058.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 4063.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 4061.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 4065.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 3005.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 3005.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2998.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2998.16 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 250.54 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 170.20 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 391.83 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 120.17 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 70.27 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 70.26 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.73 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 189.35 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 325.97 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 227.62 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 327.70 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.70 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 104.83 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 102.27 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 241.29 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.24 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 327.40 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.57 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.04 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 173.36 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 109.41 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 106.83 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 245.26 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 246.70 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 327.20 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.70 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 302.76 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 173.34 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 110.40 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 107.82 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 245.96 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 247.18 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 329.05 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 232.72 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 304.60 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 175.19 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 112.96 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 110.38 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 248.46 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 249.65 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.49 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 228.28 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 300.32 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 170.76 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 109.42 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 106.85 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.45 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 245.64 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.36 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 226.27 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.43 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 168.69 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 108.06 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 105.51 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 242.80 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 243.99 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 321.36 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.44 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.61 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.74 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 107.85 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 105.32 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 242.24 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 243.43 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 326.96 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 231.36 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.63 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.27 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.37 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 110.80 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 245.79 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 246.99 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 397.52 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.26 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 366.95 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.16 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 148.94 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 149.14 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 323.17 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.34 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0051 | 1640.30 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2296.39 | 2755.66 | 0.180 | 0.216 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
G NW APARTMENT | 1560.03 | 1872.03 | 0.122 | 0.147 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
OFFICE | 3591.49 | 4309.78 | 0.281 | 0.338 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
G NE APARTMENT | 1101.40 | 1321.68 | 0.086 | 0.104 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.11 | 0.01029 |
G N1 APARTMENT | 630.26 | 756.31 | 0.049 | 0.059 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
G N2 APARTMENT | 606.09 | 727.31 | 0.047 | 0.057 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
G S1 APARTMENT | 1665.73 | 1998.88 | 0.130 | 0.157 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
G S2 APARTMENT | 1735.52 | 2082.62 | 0.136 | 0.163 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F2 SW APARTMENT | 2987.70 | 3585.24 | 0.234 | 0.281 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F2 NW APARTMENT | 2086.35 | 2503.62 | 0.163 | 0.196 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F2 SE APARTMENT | 3003.58 | 3604.30 | 0.235 | 0.282 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F2 NE APARTMENT | 1555.37 | 1866.45 | 0.122 | 0.146 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F2 N1 APARTMENT | 960.90 | 1153.07 | 0.075 | 0.090 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F2 N2 APARTMENT | 937.37 | 1124.84 | 0.073 | 0.088 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F2 S1 APARTMENT | 2211.65 | 2653.98 | 0.173 | 0.208 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F2 S2 APARTMENT | 2238.71 | 2686.46 | 0.175 | 0.210 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F3 SW APARTMENT | 3000.84 | 3601.01 | 0.235 | 0.282 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F3 NW APARTMENT | 2113.33 | 2536.00 | 0.166 | 0.199 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F3 SE APARTMENT | 2795.86 | 3355.03 | 0.219 | 0.263 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F3 NE APARTMENT | 1588.95 | 1906.74 | 0.124 | 0.149 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F3 N1 APARTMENT | 1002.85 | 1203.42 | 0.079 | 0.094 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F3 N2 APARTMENT | 979.21 | 1175.05 | 0.077 | 0.092 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F3 S1 APARTMENT | 2248.04 | 2697.65 | 0.176 | 0.211 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F3 S2 APARTMENT | 2261.23 | 2713.47 | 0.177 | 0.213 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F4 SW APARTMENT | 2998.97 | 3598.77 | 0.235 | 0.282 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F4 NW APARTMENT | 2114.48 | 2537.38 | 0.166 | 0.199 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F4 SE APARTMENT | 2774.95 | 3329.93 | 0.217 | 0.261 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F4 NE APARTMENT | 1588.76 | 1906.51 | 0.124 | 0.149 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F4 N1 APARTMENT | 1011.93 | 1214.31 | 0.079 | 0.095 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F4 N2 APARTMENT | 988.27 | 1185.93 | 0.077 | 0.093 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F4 S1 APARTMENT | 2254.39 | 2705.27 | 0.177 | 0.212 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F4 S2 APARTMENT | 2265.60 | 2718.72 | 0.177 | 0.213 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
M SW APARTMENT | 3015.93 | 3619.11 | 0.236 | 0.283 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
M NW APARTMENT | 2133.07 | 2559.69 | 0.167 | 0.200 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
M SE APARTMENT | 2791.78 | 3350.13 | 0.219 | 0.262 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
M NE APARTMENT | 1605.69 | 1926.83 | 0.126 | 0.151 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
M N1 APARTMENT | 1035.36 | 1242.43 | 0.081 | 0.097 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
M N2 APARTMENT | 1011.69 | 1214.03 | 0.079 | 0.095 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
M S1 APARTMENT | 2277.28 | 2732.74 | 0.178 | 0.214 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
M S2 APARTMENT | 2288.20 | 2745.84 | 0.179 | 0.215 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F6 SW APARTMENT | 2974.12 | 3568.94 | 0.233 | 0.280 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F6 NW APARTMENT | 2092.35 | 2510.82 | 0.164 | 0.197 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F6 SE APARTMENT | 2752.60 | 3303.12 | 0.216 | 0.259 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F6 NE APARTMENT | 1565.07 | 1878.08 | 0.123 | 0.147 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F6 N1 APARTMENT | 1002.88 | 1203.45 | 0.079 | 0.094 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F6 N2 APARTMENT | 979.39 | 1175.26 | 0.077 | 0.092 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F6 S1 APARTMENT | 2240.59 | 2688.71 | 0.175 | 0.211 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F6 S2 APARTMENT | 2251.50 | 2701.80 | 0.176 | 0.212 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F7 SW APARTMENT | 2954.57 | 3545.49 | 0.231 | 0.278 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F7 NW APARTMENT | 2073.94 | 2488.72 | 0.162 | 0.195 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F7 SE APARTMENT | 2735.21 | 3282.25 | 0.214 | 0.257 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F7 NE APARTMENT | 1546.12 | 1855.35 | 0.121 | 0.145 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F7 N1 APARTMENT | 990.48 | 1188.58 | 0.078 | 0.093 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F7 N2 APARTMENT | 967.10 | 1160.52 | 0.076 | 0.091 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F7 S1 APARTMENT | 2225.47 | 2670.57 | 0.174 | 0.209 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F7 S2 APARTMENT | 2236.38 | 2683.65 | 0.175 | 0.210 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F8 SW APARTMENT | 2945.43 | 3534.51 | 0.231 | 0.277 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F8 NW APARTMENT | 2066.27 | 2479.52 | 0.162 | 0.194 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F8 SE APARTMENT | 2727.70 | 3273.24 | 0.214 | 0.256 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
F8 NE APARTMENT | 1537.37 | 1844.84 | 0.120 | 0.144 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F8 N1 APARTMENT | 988.57 | 1186.28 | 0.077 | 0.093 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F8 N2 APARTMENT | 965.30 | 1158.35 | 0.076 | 0.091 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F8 S1 APARTMENT | 2220.30 | 2664.36 | 0.174 | 0.209 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F8 S2 APARTMENT | 2231.23 | 2677.48 | 0.175 | 0.210 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F9 SW APARTMENT | 2996.70 | 3596.04 | 0.235 | 0.282 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
F9 NW APARTMENT | 2120.51 | 2544.62 | 0.166 | 0.199 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
F9 SE APARTMENT | 2764.59 | 3317.51 | 0.217 | 0.260 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
F9 NE APARTMENT | 1533.10 | 1839.72 | 0.120 | 0.144 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
F9 N1 APARTMENT | 1039.13 | 1246.96 | 0.081 | 0.098 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F9 N2 APARTMENT | 1015.60 | 1218.72 | 0.080 | 0.095 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
F9 S1 APARTMENT | 2252.84 | 2703.40 | 0.176 | 0.212 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 25.00 | 0.01029 |
F9 S2 APARTMENT | 2263.80 | 2716.55 | 0.177 | 0.213 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 25.00 | 0.01029 |
T SW APARTMENT | 3643.40 | 4372.07 | 0.285 | 0.342 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 24.89 | 0.01029 |
T NW APARTMENT | 2596.19 | 3115.43 | 0.203 | 0.244 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.94 | 0.01029 |
T SE APARTMENT | 3363.21 | 4035.85 | 0.263 | 0.316 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
T NE APARTMENT | 1916.99 | 2300.38 | 0.150 | 0.180 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 22.97 | 0.01029 |
T N1 APARTMENT | 1365.15 | 1638.17 | 0.107 | 0.128 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 25.00 | 0.01029 |
T N2 APARTMENT | 1366.94 | 1640.33 | 0.107 | 0.128 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 25.00 | 0.01029 |
T S1 APARTMENT | 2962.08 | 3554.50 | 0.232 | 0.278 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
T S2 APARTMENT | 2972.77 | 3567.32 | 0.233 | 0.279 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1730.58 | 2076.70 | 0.077 | 0.092 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G NW APARTMENT | 1735.16 | 2082.20 | 0.077 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
OFFICE | 2027.79 | 2433.35 | 0.090 | 0.108 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -7.00 | 0.00208 |
G NE APARTMENT | 1732.58 | 2079.10 | 0.077 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G N1 APARTMENT | 1133.38 | 1360.06 | 0.050 | 0.061 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G N2 APARTMENT | 1133.32 | 1359.99 | 0.050 | 0.061 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G S1 APARTMENT | 1125.73 | 1350.87 | 0.050 | 0.060 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G S2 APARTMENT | 1130.99 | 1357.19 | 0.050 | 0.060 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
F2 SW APARTMENT | 1673.74 | 2008.49 | 0.074 | 0.089 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 NW APARTMENT | 1674.04 | 2008.84 | 0.074 | 0.089 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 SE APARTMENT | 1687.62 | 2025.15 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 NE APARTMENT | 1672.14 | 2006.56 | 0.074 | 0.089 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 N1 APARTMENT | 927.08 | 1112.49 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 N2 APARTMENT | 927.03 | 1112.43 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 S1 APARTMENT | 929.10 | 1114.93 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F2 S2 APARTMENT | 930.10 | 1116.12 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 SW APARTMENT | 1691.72 | 2030.06 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 NW APARTMENT | 1692.66 | 2031.19 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 SE APARTMENT | 1692.51 | 2031.01 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 NE APARTMENT | 1691.69 | 2030.03 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 N1 APARTMENT | 906.51 | 1087.82 | 0.040 | 0.048 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 N2 APARTMENT | 906.49 | 1087.79 | 0.040 | 0.048 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 S1 APARTMENT | 906.24 | 1087.48 | 0.040 | 0.048 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F3 S2 APARTMENT | 906.38 | 1087.65 | 0.040 | 0.048 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 SW APARTMENT | 1749.36 | 2099.23 | 0.078 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 NW APARTMENT | 1750.72 | 2100.86 | 0.078 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 SE APARTMENT | 1749.34 | 2099.21 | 0.078 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 NE APARTMENT | 1750.52 | 2100.62 | 0.078 | 0.093 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 N1 APARTMENT | 933.15 | 1119.78 | 0.042 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 N2 APARTMENT | 933.14 | 1119.77 | 0.042 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 S1 APARTMENT | 932.21 | 1118.66 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F4 S2 APARTMENT | 932.23 | 1118.68 | 0.041 | 0.050 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M SW APARTMENT | 1787.78 | 2145.34 | 0.080 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M NW APARTMENT | 1788.45 | 2146.14 | 0.080 | 0.096 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M SE APARTMENT | 1788.24 | 2145.89 | 0.080 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M NE APARTMENT | 1788.89 | 2146.66 | 0.080 | 0.096 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M N1 APARTMENT | 946.51 | 1135.81 | 0.042 | 0.051 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M N2 APARTMENT | 946.52 | 1135.82 | 0.042 | 0.051 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M S1 APARTMENT | 946.24 | 1135.49 | 0.042 | 0.051 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
M S2 APARTMENT | 946.25 | 1135.50 | 0.042 | 0.051 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 SW APARTMENT | 1872.00 | 2246.40 | 0.083 | 0.100 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 NW APARTMENT | 1873.39 | 2248.07 | 0.083 | 0.100 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 SE APARTMENT | 1872.99 | 2247.59 | 0.083 | 0.100 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 NE APARTMENT | 1874.38 | 2249.25 | 0.083 | 0.100 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 N1 APARTMENT | 1008.31 | 1209.97 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 N2 APARTMENT | 1008.33 | 1210.00 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 S1 APARTMENT | 1007.29 | 1208.75 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F6 S2 APARTMENT | 1007.32 | 1208.78 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 SW APARTMENT | 1932.97 | 2319.56 | 0.086 | 0.103 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 NW APARTMENT | 1934.19 | 2321.02 | 0.086 | 0.103 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 SE APARTMENT | 1934.44 | 2321.33 | 0.086 | 0.103 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 NE APARTMENT | 1935.66 | 2322.79 | 0.086 | 0.103 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 N1 APARTMENT | 1049.95 | 1259.94 | 0.047 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 N2 APARTMENT | 1049.99 | 1259.99 | 0.047 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 S1 APARTMENT | 1049.11 | 1258.94 | 0.047 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F7 S2 APARTMENT | 1049.15 | 1258.98 | 0.047 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 SW APARTMENT | 1995.82 | 2394.99 | 0.089 | 0.107 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 NW APARTMENT | 1996.68 | 2396.01 | 0.089 | 0.107 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 SE APARTMENT | 1997.73 | 2397.27 | 0.089 | 0.107 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 NE APARTMENT | 1998.58 | 2398.30 | 0.089 | 0.107 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 N1 APARTMENT | 1095.45 | 1314.54 | 0.049 | 0.059 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 N2 APARTMENT | 1095.50 | 1314.60 | 0.049 | 0.059 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 S1 APARTMENT | 1094.96 | 1313.96 | 0.049 | 0.058 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F8 S2 APARTMENT | 1095.01 | 1314.01 | 0.049 | 0.058 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 SW APARTMENT | 2155.52 | 2586.62 | 0.096 | 0.115 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 NW APARTMENT | 2154.20 | 2585.04 | 0.096 | 0.115 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 SE APARTMENT | 2157.83 | 2589.40 | 0.096 | 0.115 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 NE APARTMENT | 2156.51 | 2587.81 | 0.096 | 0.115 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 N1 APARTMENT | 1231.05 | 1477.26 | 0.055 | 0.066 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 N2 APARTMENT | 1231.11 | 1477.33 | 0.055 | 0.066 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 S1 APARTMENT | 1232.37 | 1478.84 | 0.055 | 0.066 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
F9 S2 APARTMENT | 1232.43 | 1478.91 | 0.055 | 0.066 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T SW APARTMENT | 2669.90 | 3203.89 | 0.119 | 0.143 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T NW APARTMENT | 2673.94 | 3208.73 | 0.119 | 0.143 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T SE APARTMENT | 2672.34 | 3206.80 | 0.119 | 0.143 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T NE APARTMENT | 2676.37 | 3211.65 | 0.119 | 0.143 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T N1 APARTMENT | 1779.86 | 2135.83 | 0.079 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T N2 APARTMENT | 1779.92 | 2135.91 | 0.079 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T S1 APARTMENT | 1773.33 | 2128.00 | 0.079 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
T S2 APARTMENT | 1773.40 | 2128.08 | 0.079 | 0.095 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.00 | 0.00208 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.22 | 0.22 | 0.09 | 0.09 |
AIRLOOP G NW | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP OFFICE | 0.34 | 0.34 | 0.11 | 0.11 |
AIRLOOP G NE | 0.10 | 0.10 | 0.09 | 0.09 |
AIRLOOP G N1 | 0.06 | 0.06 | 0.06 | 0.06 |
AIRLOOP G N2 | 0.06 | 0.06 | 0.06 | 0.06 |
AIRLOOP G S1 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP G S2 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F2 SW | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F2 NW | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP F2 SE | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F2 NE | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F2 N1 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F2 N2 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F2 S1 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F2 S2 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F3 SW | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F3 NW | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP F3 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F3 NE | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F3 N1 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F3 N2 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F3 S1 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F3 S2 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F4 SW | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F4 NW | 0.20 | 0.20 | 0.09 | 0.09 |
AIRLOOP F4 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F4 NE | 0.15 | 0.15 | 0.09 | 0.09 |
AIRLOOP F4 N1 | 0.10 | 0.10 | 0.05 | 0.05 |
AIRLOOP F4 N2 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F4 S1 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F4 S2 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP M SW | 0.28 | 0.28 | 0.10 | 0.10 |
AIRLOOP M NW | 0.20 | 0.20 | 0.10 | 0.10 |
AIRLOOP M SE | 0.26 | 0.26 | 0.10 | 0.10 |
AIRLOOP M NE | 0.15 | 0.15 | 0.10 | 0.10 |
AIRLOOP M N1 | 0.10 | 0.10 | 0.05 | 0.05 |
AIRLOOP M N2 | 0.10 | 0.10 | 0.05 | 0.05 |
AIRLOOP M S1 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP M S2 | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F6 SW | 0.28 | 0.28 | 0.10 | 0.10 |
AIRLOOP F6 NW | 0.20 | 0.20 | 0.10 | 0.10 |
AIRLOOP F6 SE | 0.26 | 0.26 | 0.10 | 0.10 |
AIRLOOP F6 NE | 0.15 | 0.15 | 0.10 | 0.10 |
AIRLOOP F6 N1 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F6 N2 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP F6 S1 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F6 S2 | 0.21 | 0.21 | 0.05 | 0.05 |
AIRLOOP F7 SW | 0.28 | 0.28 | 0.10 | 0.10 |
AIRLOOP F7 NW | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F7 SE | 0.26 | 0.26 | 0.10 | 0.10 |
AIRLOOP F7 NE | 0.15 | 0.15 | 0.10 | 0.10 |
AIRLOOP F7 N1 | 0.09 | 0.09 | 0.06 | 0.06 |
AIRLOOP F7 N2 | 0.09 | 0.09 | 0.06 | 0.06 |
AIRLOOP F7 S1 | 0.21 | 0.21 | 0.06 | 0.06 |
AIRLOOP F7 S2 | 0.21 | 0.21 | 0.06 | 0.06 |
AIRLOOP F8 SW | 0.28 | 0.28 | 0.11 | 0.11 |
AIRLOOP F8 NW | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP F8 SE | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F8 NE | 0.14 | 0.14 | 0.11 | 0.11 |
AIRLOOP F8 N1 | 0.09 | 0.09 | 0.06 | 0.06 |
AIRLOOP F8 N2 | 0.09 | 0.09 | 0.06 | 0.06 |
AIRLOOP F8 S1 | 0.21 | 0.21 | 0.06 | 0.06 |
AIRLOOP F8 S2 | 0.21 | 0.21 | 0.06 | 0.06 |
AIRLOOP F9 SW | 0.28 | 0.28 | 0.12 | 0.12 |
AIRLOOP F9 NW | 0.20 | 0.20 | 0.12 | 0.12 |
AIRLOOP F9 SE | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F9 NE | 0.14 | 0.14 | 0.12 | 0.12 |
AIRLOOP F9 N1 | 0.10 | 0.10 | 0.07 | 0.07 |
AIRLOOP F9 N2 | 0.10 | 0.10 | 0.07 | 0.07 |
AIRLOOP F9 S1 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP F9 S2 | 0.21 | 0.21 | 0.07 | 0.07 |
AIRLOOP T SW | 0.34 | 0.34 | 0.14 | 0.14 |
AIRLOOP T NW | 0.24 | 0.24 | 0.14 | 0.14 |
AIRLOOP T SE | 0.32 | 0.32 | 0.14 | 0.14 |
AIRLOOP T NE | 0.18 | 0.18 | 0.14 | 0.14 |
AIRLOOP T N1 | 0.13 | 0.13 | 0.10 | 0.10 |
AIRLOOP T N2 | 0.13 | 0.13 | 0.10 | 0.10 |
AIRLOOP T S1 | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP T S2 | 0.28 | 0.28 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1574.25 | 6419.50 | 105.50 |
G NW APARTMENT | 964.25 | 7453.50 | 205.50 |
OFFICE | 829.75 | 1086.25 | 7.25 |
G NE APARTMENT | 899.00 | 7617.75 | 226.25 |
G N1 APARTMENT | 427.50 | 7989.00 | 98.00 |
G N2 APARTMENT | 421.50 | 8010.00 | 98.00 |
G S1 APARTMENT | 1312.50 | 6620.75 | 54.75 |
G S2 APARTMENT | 1387.00 | 6496.75 | 53.00 |
F2 SW APARTMENT | 2598.75 | 5198.00 | 24.25 |
F2 NW APARTMENT | 1534.25 | 6505.50 | 71.25 |
F2 SE APARTMENT | 2854.00 | 4990.25 | 19.75 |
F2 NE APARTMENT | 1404.25 | 6737.75 | 89.75 |
F2 N1 APARTMENT | 995.00 | 7155.50 | 65.25 |
F2 N2 APARTMENT | 974.00 | 7185.50 | 67.00 |
F2 S1 APARTMENT | 2510.00 | 5084.75 | 21.25 |
F2 S2 APARTMENT | 2545.75 | 5042.75 | 20.50 |
F3 SW APARTMENT | 2792.50 | 5008.75 | 20.50 |
F3 NW APARTMENT | 1713.25 | 6298.00 | 56.75 |
F3 SE APARTMENT | 2809.75 | 5038.25 | 21.50 |
F3 NE APARTMENT | 1554.00 | 6534.00 | 66.75 |
F3 N1 APARTMENT | 1203.25 | 6831.75 | 49.25 |
F3 N2 APARTMENT | 1180.50 | 6864.00 | 51.25 |
F3 S1 APARTMENT | 2833.00 | 4727.50 | 18.25 |
F3 S2 APARTMENT | 2844.25 | 4723.00 | 18.25 |
F4 SW APARTMENT | 2855.25 | 4967.75 | 20.00 |
F4 NW APARTMENT | 1791.50 | 6230.25 | 58.50 |
F4 SE APARTMENT | 2824.50 | 5042.00 | 22.25 |
F4 NE APARTMENT | 1650.00 | 6457.75 | 68.00 |
F4 N1 APARTMENT | 1326.25 | 6678.75 | 57.50 |
F4 N2 APARTMENT | 1294.00 | 6716.25 | 57.75 |
F4 S1 APARTMENT | 2968.25 | 4639.25 | 19.25 |
F4 S2 APARTMENT | 2965.50 | 4642.50 | 19.50 |
M SW APARTMENT | 2845.75 | 4984.00 | 17.00 |
M NW APARTMENT | 1794.00 | 6243.00 | 54.50 |
M SE APARTMENT | 2803.75 | 5058.00 | 19.50 |
M NE APARTMENT | 1644.50 | 6464.75 | 62.75 |
M N1 APARTMENT | 1365.25 | 6634.75 | 54.75 |
M N2 APARTMENT | 1333.00 | 6669.00 | 55.25 |
M S1 APARTMENT | 2984.00 | 4632.25 | 18.25 |
M S2 APARTMENT | 2982.00 | 4638.25 | 17.75 |
F6 SW APARTMENT | 2668.75 | 5141.75 | 19.75 |
F6 NW APARTMENT | 1635.00 | 6418.00 | 63.00 |
F6 SE APARTMENT | 2629.25 | 5223.50 | 25.00 |
F6 NE APARTMENT | 1471.25 | 6622.25 | 73.25 |
F6 N1 APARTMENT | 1170.75 | 6846.50 | 56.00 |
F6 N2 APARTMENT | 1142.00 | 6880.00 | 56.00 |
F6 S1 APARTMENT | 2808.25 | 4804.25 | 20.75 |
F6 S2 APARTMENT | 2802.25 | 4808.50 | 20.75 |
F7 SW APARTMENT | 2543.75 | 5266.75 | 20.75 |
F7 NW APARTMENT | 1528.25 | 6566.75 | 71.50 |
F7 SE APARTMENT | 2504.25 | 5340.75 | 27.75 |
F7 NE APARTMENT | 1356.00 | 6764.25 | 78.50 |
F7 N1 APARTMENT | 1048.25 | 7000.25 | 55.50 |
F7 N2 APARTMENT | 1023.00 | 7041.75 | 58.25 |
F7 S1 APARTMENT | 2675.00 | 4957.75 | 23.00 |
F7 S2 APARTMENT | 2667.75 | 4963.00 | 23.25 |
F8 SW APARTMENT | 2437.75 | 5382.25 | 24.50 |
F8 NW APARTMENT | 1433.75 | 6678.00 | 77.25 |
F8 SE APARTMENT | 2384.50 | 5467.25 | 30.50 |
F8 NE APARTMENT | 1251.75 | 6877.75 | 82.25 |
F8 N1 APARTMENT | 958.25 | 7131.75 | 58.50 |
F8 N2 APARTMENT | 931.75 | 7163.75 | 59.75 |
F8 S1 APARTMENT | 2548.25 | 5101.00 | 25.75 |
F8 S2 APARTMENT | 2538.75 | 5108.50 | 25.50 |
F9 SW APARTMENT | 2291.50 | 5558.75 | 36.50 |
F9 NW APARTMENT | 1371.00 | 6806.50 | 102.00 |
F9 SE APARTMENT | 2235.00 | 5626.50 | 40.75 |
F9 NE APARTMENT | 1190.50 | 6998.50 | 115.75 |
F9 N1 APARTMENT | 911.75 | 7230.75 | 67.25 |
F9 N2 APARTMENT | 885.75 | 7262.25 | 67.75 |
F9 S1 APARTMENT | 2359.75 | 5319.25 | 28.25 |
F9 S2 APARTMENT | 2352.25 | 5329.75 | 28.00 |
T SW APARTMENT | 2379.75 | 6066.75 | 466.25 |
T NW APARTMENT | 1763.00 | 7077.50 | 619.00 |
T SE APARTMENT | 2390.50 | 6097.25 | 476.75 |
T NE APARTMENT | 1746.75 | 7189.25 | 656.25 |
T N1 APARTMENT | 1059.50 | 7383.75 | 216.25 |
T N2 APARTMENT | 1055.75 | 7398.25 | 218.75 |
T S1 APARTMENT | 2085.25 | 5801.50 | 104.50 |
T S2 APARTMENT | 2081.00 | 5807.25 | 104.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4159.75 | 8157.25 | 728.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
G NW APARTMENT | 5.25 | 3.00 | 5.25 | 3.00 |
OFFICE | 2.50 | 0.00 | 0.25 | 0.00 |
G NE APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
G N1 APARTMENT | 6.50 | 2.50 | 6.50 | 2.50 |
G N2 APARTMENT | 7.75 | 2.25 | 7.75 | 2.25 |
G S1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
G S2 APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
F2 SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F2 NW APARTMENT | 3.25 | 3.00 | 3.25 | 3.00 |
F2 SE APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F2 NE APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
F2 N1 APARTMENT | 5.25 | 2.50 | 5.25 | 2.50 |
F2 N2 APARTMENT | 6.00 | 2.50 | 6.00 | 2.50 |
F2 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F2 S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F3 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F3 NW APARTMENT | 1.75 | 3.00 | 1.75 | 3.00 |
F3 SE APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F3 NE APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F3 N1 APARTMENT | 5.25 | 2.50 | 5.25 | 2.50 |
F3 N2 APARTMENT | 5.25 | 2.75 | 5.25 | 2.75 |
F3 S1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
F3 S2 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
F4 SW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F4 NW APARTMENT | 1.25 | 3.00 | 1.25 | 3.00 |
F4 SE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F4 NE APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F4 N1 APARTMENT | 5.75 | 2.75 | 5.75 | 2.75 |
F4 N2 APARTMENT | 7.25 | 2.75 | 7.25 | 2.75 |
F4 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F4 S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M NW APARTMENT | 2.00 | 3.00 | 2.00 | 3.00 |
M SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M NE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M N1 APARTMENT | 6.25 | 2.75 | 6.25 | 2.75 |
M N2 APARTMENT | 7.00 | 2.75 | 7.00 | 2.75 |
M S1 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
M S2 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
F6 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F6 NW APARTMENT | 1.50 | 2.75 | 1.50 | 2.75 |
F6 SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F6 NE APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F6 N1 APARTMENT | 4.25 | 2.75 | 4.25 | 2.75 |
F6 N2 APARTMENT | 5.50 | 2.75 | 5.50 | 2.75 |
F6 S1 APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
F6 S2 APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
F7 SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F7 NW APARTMENT | 2.25 | 2.50 | 2.25 | 2.50 |
F7 SE APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F7 NE APARTMENT | 6.75 | 0.00 | 6.75 | 0.00 |
F7 N1 APARTMENT | 4.00 | 2.75 | 4.00 | 2.75 |
F7 N2 APARTMENT | 5.00 | 2.75 | 5.00 | 2.75 |
F7 S1 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
F7 S2 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
F8 SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F8 NW APARTMENT | 0.75 | 2.25 | 0.75 | 2.25 |
F8 SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F8 NE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F8 N1 APARTMENT | 5.50 | 2.75 | 5.50 | 2.75 |
F8 N2 APARTMENT | 6.25 | 2.75 | 6.25 | 2.75 |
F8 S1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
F8 S2 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F9 SW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F9 NW APARTMENT | 1.75 | 2.25 | 1.75 | 2.25 |
F9 SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F9 NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F9 N1 APARTMENT | 7.75 | 2.50 | 7.75 | 2.50 |
F9 N2 APARTMENT | 8.75 | 2.75 | 8.75 | 2.75 |
F9 S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F9 S2 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
T SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NW APARTMENT | 0.00 | 4.50 | 0.00 | 4.50 |
T SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T NE APARTMENT | 0.25 | 0.25 | 0.25 | 0.25 |
T N1 APARTMENT | 6.75 | 4.25 | 6.75 | 4.25 |
T N2 APARTMENT | 7.50 | 3.75 | 7.50 | 3.75 |
T S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T S2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 202.50 | 6.25 | 200.25 | 6.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.151 | 0.000 | 0.278 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.263 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.175 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.263 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.091 | 0.000 | 0.253 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.253 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.091 | 0.000 | 0.274 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.091 | 0.000 | 0.275 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.218 | 0.000 | 0.307 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.217 | 0.000 | 0.292 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.218 | 0.000 | 0.310 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.291 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.131 | 0.000 | 0.283 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.283 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.131 | 0.000 | 0.305 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.305 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.258 | 0.000 | 0.324 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.257 | 0.000 | 0.306 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.258 | 0.000 | 0.324 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.257 | 0.000 | 0.306 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.155 | 0.000 | 0.299 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.155 | 0.000 | 0.299 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.155 | 0.000 | 0.322 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.155 | 0.000 | 0.322 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.288 | 0.000 | 0.316 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.288 | 0.000 | 0.298 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.288 | 0.000 | 0.317 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.288 | 0.000 | 0.298 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.173 | 0.000 | 0.292 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.173 | 0.000 | 0.292 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.174 | 0.000 | 0.315 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.174 | 0.000 | 0.315 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.313 | 0.000 | 0.327 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.312 | 0.000 | 0.307 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.313 | 0.000 | 0.327 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.312 | 0.000 | 0.307 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.188 | 0.000 | 0.301 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.188 | 0.000 | 0.301 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.189 | 0.000 | 0.325 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.189 | 0.000 | 0.325 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.334 | 0.000 | 0.335 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.334 | 0.000 | 0.314 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.334 | 0.000 | 0.336 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.334 | 0.000 | 0.314 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.201 | 0.000 | 0.308 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.201 | 0.000 | 0.308 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.202 | 0.000 | 0.333 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.202 | 0.000 | 0.333 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.353 | 0.000 | 0.342 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.353 | 0.000 | 0.319 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.353 | 0.000 | 0.342 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.353 | 0.000 | 0.319 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.213 | 0.000 | 0.313 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.213 | 0.000 | 0.313 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.213 | 0.000 | 0.340 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.213 | 0.000 | 0.340 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.370 | 0.000 | 0.350 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.370 | 0.000 | 0.326 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.370 | 0.000 | 0.350 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.370 | 0.000 | 0.325 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.223 | 0.000 | 0.319 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.223 | 0.000 | 0.319 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.223 | 0.000 | 0.348 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.223 | 0.000 | 0.348 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.386 | 0.000 | 0.355 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.385 | 0.000 | 0.330 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.386 | 0.000 | 0.356 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.385 | 0.000 | 0.330 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.232 | 0.000 | 0.324 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.232 | 0.000 | 0.324 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.233 | 0.000 | 0.354 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.233 | 0.000 | 0.354 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.400 | 0.000 | 0.358 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.400 | 0.000 | 0.334 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.400 | 0.000 | 0.359 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.400 | 0.000 | 0.334 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.241 | 0.000 | 0.329 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.241 | 0.000 | 0.329 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.241 | 0.000 | 0.357 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.241 | 0.000 | 0.357 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 553.30 | 17544.92 | 06-JAN-08:45 | 17544.92 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 902.47 | 18206.16 | 29-MAY-02:15 | 90189.44 | 16-DEC-17:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
ElectricityPurchased:Plant | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
Cogeneration:ElectricityPurchased | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
ElectricityNet:Plant | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
Cogeneration:ElectricityNet | 2555.34 | 52259.14 | 11-JUN-04:15 | 163265.22 | 16-DEC-17:15 |
ExteriorLights:Electricity | 162.51 | 0.00 | 01-JAN-08:15 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.51 | 0.00 | 01-JAN-08:15 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 553.30 | 17544.92 | 06-JAN-08:45 | 17544.92 | 01-JAN-00:15 |
Cooling:Electricity | 99.13 | 0.00 | 01-JAN-00:15 | 54119.07 | 11-JUL-17:00 |
Heating:Electricity | 213.87 | 0.00 | 25-MAR-16:30 | 71247.61 | 16-DEC-17:00 |
Electricity:Plant | 56.47 | 36.93 | 03-MAY-06:00 | 3638.53 | 12-JUL-15:00 |
HeatRejection:Electricity | 4.24 | 0.00 | 01-JAN-00:15 | 1961.30 | 12-JUL-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 52.23 | 36.93 | 03-MAY-06:00 | 1677.22 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1951.51 | 2357.00 | 22-FEB-23:45 | 258166.95 | 16-DEC-19:00 |
Gas:Plant | 1951.51 | 2357.00 | 22-FEB-23:45 | 258166.95 | 16-DEC-19:00 |
WaterSystems:Gas | 1178.71 | 2357.00 | 01-JAN-00:15 | 80844.40 | 14-FEB-07:45 |
Water Heater:WaterSystems:Gas | 1178.71 | 2357.00 | 01-JAN-00:15 | 80844.40 | 14-FEB-07:45 |
Heating:Gas | 772.80 | 0.00 | 06-FEB-16:15 | 194476.20 | 16-DEC-17:00 |
Boiler:Heating:Gas | 772.80 | 0.00 | 06-FEB-16:15 | 194476.20 | 16-DEC-17:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 389.82 | 0.00 | 01-JAN-00:15 | 243466.96 | 11-JUL-17:00 |
PlantLoopCoolingDemand:HVAC | 389.82 | 0.00 | 01-JAN-00:15 | 243466.96 | 11-JUL-17:00 |
CoolingCoils:PlantLoopCoolingDemand | 389.82 | 0.00 | 01-JAN-00:15 | 243466.96 | 11-JUL-17:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5091.84 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:15 |
Water:Plant | 5091.84 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5091.84 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:15 |
MainsWater:Plant | 5091.84 | 0.00 | 01-JAN-02:15 | 0.00 | 11-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 313.33 | 0.00 | 01-JAN-00:15 | 0.00 | 11-JUL-17:00 |
HeatRejection:MainsWater | 313.33 | 0.00 | 01-JAN-00:15 | 0.00 | 11-JUL-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1538.31 | 505.43 | 11-AUG-01:15 | 189396.87 | 16-DEC-19:00 |
PlantLoopHeatingDemand:Plant | 917.61 | 505.43 | 11-AUG-01:15 | 59373.88 | 16-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 917.61 | 505.43 | 11-AUG-01:15 | 59373.88 | 16-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 3559.45 | 5743.68 | 04-SEP-03:00 | 577948.63 | 16-DEC-17:00 |
EnergyTransfer:Building | 950.36 | 3799.20 | 02-SEP-11:15 | 191361.77 | 03-DEC-02:00 |
EnergyTransfer:Zone:G SW APARTMENT | 11.28 | 0.00 | 09-MAR-20:45 | 2311.72 | 13-SEP-15:15 |
Heating:EnergyTransfer | 503.40 | 0.00 | 11-MAR-12:30 | 191361.77 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 7.01 | 0.00 | 01-JAN-10:30 | 1864.49 | 16-DEC-17:00 |
Cooling:EnergyTransfer | 446.96 | 0.00 | 02-JAN-19:45 | 143019.27 | 11-JUL-16:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 4.27 | 0.00 | 01-JAN-00:15 | 2311.72 | 13-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 11.40 | 0.03 | 12-AUG-09:00 | 1862.78 | 16-DEC-17:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 8.88 | 0.00 | 06-FEB-14:45 | 1862.78 | 16-DEC-17:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 2.52 | 0.00 | 01-JAN-00:15 | 1787.49 | 15-JUL-18:00 |
EnergyTransfer:Zone:OFFICE | 17.79 | 0.06 | 03-DEC-14:00 | 3592.82 | 13-SEP-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 4.79 | 0.00 | 01-JAN-10:15 | 2022.53 | 16-DEC-19:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 13.00 | 0.00 | 01-JAN-00:15 | 3592.82 | 13-SEP-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 11.46 | 0.00 | 05-JUN-17:00 | 1867.25 | 16-DEC-17:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 8.93 | 0.00 | 05-FEB-09:30 | 1867.25 | 16-DEC-17:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 2.54 | 0.00 | 01-JAN-00:15 | 1101.32 | 11-JUL-16:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 7.37 | 0.07 | 28-MAY-14:00 | 1102.99 | 16-DEC-16:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 4.39 | 0.00 | 21-JAN-17:15 | 1102.99 | 16-DEC-16:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 2.97 | 0.00 | 01-JAN-00:15 | 732.84 | 03-JUL-19:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 7.36 | 0.01 | 22-OCT-10:45 | 1102.99 | 16-DEC-16:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 4.40 | 0.00 | 21-JAN-17:15 | 1102.99 | 16-DEC-16:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 2.95 | 0.00 | 01-JAN-00:15 | 732.57 | 03-JUL-19:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.19 | 0.00 | 18-JUL-20:45 | 1642.17 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 2.71 | 0.00 | 01-JAN-10:00 | 1097.52 | 16-DEC-16:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 4.48 | 0.00 | 01-JAN-00:15 | 1642.17 | 13-SEP-13:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.15 | 0.03 | 18-JUN-15:30 | 1699.92 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 2.55 | 0.00 | 01-JAN-09:30 | 1088.60 | 16-DEC-16:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 4.61 | 0.00 | 01-JAN-00:15 | 1699.92 | 13-SEP-13:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 13.61 | 0.07 | 19-JUL-05:45 | 2998.27 | 13-SEP-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 5.81 | 0.00 | 01-JAN-09:15 | 2279.17 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 7.80 | 0.00 | 01-JAN-00:15 | 2998.27 | 13-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 11.76 | 0.05 | 15-OCT-24:00 | 2385.29 | 15-JUL-18:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 7.93 | 0.00 | 06-JAN-15:00 | 2300.59 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 3.84 | 0.00 | 01-JAN-00:15 | 2385.29 | 15-JUL-18:00 |
EnergyTransfer:Zone:F2 SE APARTMENT | 13.36 | 0.01 | 01-SEP-22:45 | 2768.11 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 5.09 | 0.00 | 01-JAN-09:00 | 2240.85 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 8.27 | 0.00 | 01-JAN-00:15 | 2768.11 | 13-SEP-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 11.49 | 0.00 | 30-APR-13:30 | 2290.12 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 7.92 | 0.00 | 21-JAN-17:15 | 2290.12 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 3.57 | 0.00 | 01-JAN-00:15 | 1590.87 | 11-JUL-16:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 6.90 | 0.01 | 05-JAN-19:00 | 1245.23 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 2.72 | 0.00 | 01-JAN-11:00 | 1245.23 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 4.18 | 0.00 | 01-JAN-00:15 | 1056.78 | 16-JUL-18:15 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 6.91 | 0.00 | 03-NOV-02:00 | 1244.70 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 2.73 | 0.00 | 01-JAN-11:00 | 1244.70 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 4.18 | 0.00 | 01-JAN-00:15 | 1038.79 | 03-JUL-19:00 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 9.40 | 0.03 | 03-AUG-11:45 | 2219.02 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 1.69 | 0.00 | 01-JAN-00:15 | 1224.45 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 7.71 | 0.00 | 01-JAN-05:15 | 2219.02 | 13-SEP-13:45 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 9.46 | 0.05 | 14-MAR-14:15 | 2239.43 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 1.66 | 0.00 | 01-JAN-00:15 | 1221.53 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 7.80 | 0.00 | 02-JAN-10:00 | 2239.43 | 13-SEP-13:45 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 14.32 | 0.01 | 15-JUN-22:00 | 3015.34 | 13-SEP-15:15 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 5.88 | 0.00 | 01-JAN-00:30 | 2570.45 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 8.43 | 0.00 | 01-JAN-00:15 | 3015.34 | 13-SEP-15:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 12.24 | 0.00 | 04-SEP-00:45 | 2591.93 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 8.02 | 0.00 | 01-JAN-17:15 | 2591.93 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 4.22 | 0.00 | 01-JAN-00:15 | 2428.49 | 15-JUL-18:00 |
EnergyTransfer:Zone:F3 SE APARTMENT | 13.79 | 0.00 | 02-JAN-00:30 | 2652.85 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 5.76 | 0.00 | 01-JAN-00:30 | 2553.43 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 8.02 | 0.00 | 01-JAN-00:15 | 2652.85 | 13-SEP-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 11.93 | 0.02 | 09-SEP-11:15 | 2581.06 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 8.02 | 0.00 | 01-JAN-18:15 | 2581.06 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 3.90 | 0.00 | 01-JAN-00:15 | 1635.87 | 11-JUL-16:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 7.22 | 0.10 | 22-AUG-14:30 | 1398.14 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 2.60 | 0.00 | 01-JAN-06:45 | 1398.14 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 4.62 | 0.00 | 01-JAN-00:15 | 1109.65 | 16-JUL-18:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 7.22 | 0.05 | 05-FEB-04:30 | 1397.60 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 2.61 | 0.00 | 01-JAN-06:45 | 1397.60 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 4.61 | 0.00 | 01-JAN-00:15 | 1089.98 | 03-JUL-19:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 10.34 | 0.01 | 13-JUL-08:30 | 2257.93 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 1.61 | 0.00 | 01-JAN-00:15 | 1375.40 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 8.72 | 0.00 | 02-JAN-10:45 | 2257.93 | 13-SEP-13:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 10.34 | 0.03 | 02-AUG-09:15 | 2269.02 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 1.61 | 0.00 | 01-JAN-00:15 | 1374.16 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 8.73 | 0.00 | 02-JAN-10:45 | 2269.02 | 13-SEP-13:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 14.80 | 0.01 | 15-JUN-22:00 | 3019.25 | 11-JUL-17:15 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 6.28 | 0.00 | 01-JAN-00:15 | 2819.29 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 8.52 | 0.00 | 01-JAN-03:15 | 3019.25 | 11-JUL-17:15 |
EnergyTransfer:Zone:F4 NW APARTMENT | 12.80 | 0.01 | 06-JUN-14:15 | 2841.33 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 8.49 | 0.00 | 01-JAN-17:15 | 2841.33 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 4.31 | 0.00 | 01-JAN-00:15 | 2437.41 | 15-JUL-18:00 |
EnergyTransfer:Zone:F4 SE APARTMENT | 14.23 | 0.04 | 07-SEP-16:00 | 2807.06 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 6.28 | 0.00 | 01-JAN-00:15 | 2807.06 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 7.95 | 0.00 | 01-JAN-00:30 | 2629.50 | 13-SEP-13:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 12.47 | 0.00 | 16-JUN-13:45 | 2830.27 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 8.49 | 0.00 | 01-JAN-11:00 | 2830.27 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 3.99 | 0.00 | 01-JAN-00:15 | 1639.80 | 11-JUL-16:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 7.54 | 0.04 | 22-OCT-11:00 | 1541.22 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 2.78 | 0.00 | 01-JAN-01:00 | 1541.22 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 4.76 | 0.00 | 01-JAN-00:15 | 1123.55 | 16-JUL-18:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 7.54 | 0.01 | 17-APR-05:15 | 1540.67 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 2.79 | 0.00 | 01-JAN-01:00 | 1540.67 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 4.75 | 0.00 | 01-JAN-00:15 | 1101.67 | 15-JUL-18:00 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 10.76 | 0.00 | 05-JUN-12:15 | 2255.75 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 1.74 | 0.00 | 01-JAN-00:15 | 1517.74 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 9.01 | 0.00 | 02-JAN-12:30 | 2255.75 | 13-SEP-13:45 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 10.74 | 0.06 | 23-SEP-16:00 | 2265.34 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 1.75 | 0.00 | 01-JAN-00:15 | 1517.05 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 8.99 | 0.00 | 02-JAN-12:30 | 2265.34 | 13-SEP-13:45 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 14.99 | 0.03 | 18-APR-22:15 | 3044.14 | 11-JUL-17:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 6.60 | 0.00 | 01-JAN-00:15 | 3015.86 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 8.39 | 0.00 | 01-JAN-03:45 | 3044.14 | 11-JUL-17:15 |
EnergyTransfer:Zone:M NW APARTMENT | 13.10 | 0.04 | 29-OCT-14:30 | 3037.25 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 8.82 | 0.00 | 01-JAN-17:15 | 3037.25 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 4.28 | 0.00 | 01-JAN-00:15 | 2463.15 | 15-JUL-18:00 |
EnergyTransfer:Zone:M SE APARTMENT | 14.41 | 0.05 | 21-JAN-14:30 | 3004.55 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 6.61 | 0.00 | 01-JAN-00:15 | 3004.55 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 7.80 | 0.00 | 01-JAN-03:45 | 2645.26 | 11-JUL-13:00 |
EnergyTransfer:Zone:M NE APARTMENT | 12.77 | 0.01 | 30-AUG-10:45 | 3026.11 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 8.81 | 0.00 | 01-JAN-10:45 | 3026.11 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 3.96 | 0.00 | 01-JAN-00:15 | 1659.98 | 11-JUL-16:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 7.71 | 0.04 | 28-AUG-15:00 | 1652.09 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.89 | 0.00 | 01-JAN-01:45 | 1652.09 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 4.82 | 0.00 | 01-JAN-00:15 | 1151.37 | 16-JUL-18:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 7.71 | 0.10 | 02-APR-01:30 | 1651.55 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.90 | 0.00 | 01-JAN-01:45 | 1651.55 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 4.81 | 0.00 | 01-JAN-00:15 | 1126.68 | 16-JUL-18:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 10.89 | 0.00 | 12-AUG-09:45 | 2262.60 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.85 | 0.00 | 01-JAN-00:15 | 1629.61 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 9.03 | 0.00 | 02-JAN-12:45 | 2262.60 | 13-SEP-13:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 10.86 | 0.00 | 11-SEP-20:00 | 2271.94 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.86 | 0.00 | 01-JAN-00:15 | 1629.14 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 9.00 | 0.00 | 02-JAN-12:45 | 2271.94 | 13-SEP-13:45 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 15.00 | 0.00 | 20-SEP-01:15 | 3232.72 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 7.37 | 0.00 | 01-JAN-00:30 | 3232.72 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 7.63 | 0.00 | 01-JAN-00:15 | 3006.08 | 11-JUL-17:15 |
EnergyTransfer:Zone:F6 NW APARTMENT | 13.62 | 0.00 | 21-AUG-23:30 | 3254.93 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 9.77 | 0.00 | 01-JAN-17:15 | 3254.93 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 3.85 | 0.00 | 01-JAN-00:15 | 2422.35 | 15-JUL-18:00 |
EnergyTransfer:Zone:F6 SE APARTMENT | 14.44 | 0.01 | 14-OCT-20:45 | 3221.42 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 7.39 | 0.00 | 01-JAN-00:30 | 3221.42 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 7.05 | 0.00 | 01-JAN-00:15 | 2607.86 | 11-JUL-13:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 13.33 | 0.01 | 18-AUG-08:00 | 3243.69 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 9.76 | 0.00 | 01-JAN-11:00 | 3243.69 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 3.57 | 0.00 | 01-JAN-00:15 | 1618.86 | 11-JUL-16:15 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 7.83 | 0.02 | 20-OCT-02:30 | 1918.95 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 3.41 | 0.00 | 01-JAN-01:00 | 1918.95 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 4.42 | 0.00 | 01-JAN-00:15 | 1118.18 | 16-JUL-18:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 7.84 | 0.02 | 10-MAR-24:00 | 1946.08 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 3.43 | 0.00 | 01-JAN-01:00 | 1946.08 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 4.41 | 0.00 | 01-JAN-00:15 | 1093.61 | 16-JUL-18:15 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 10.49 | 0.01 | 23-SEP-15:45 | 2205.81 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 2.21 | 0.00 | 01-JAN-00:15 | 1767.29 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 8.29 | 0.00 | 02-JAN-10:30 | 2205.81 | 13-SEP-13:45 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 10.47 | 0.05 | 13-JUL-08:30 | 2215.16 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 2.21 | 0.00 | 01-JAN-00:15 | 1766.75 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 8.25 | 0.00 | 02-JAN-10:30 | 2215.16 | 13-SEP-13:45 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 15.09 | 0.05 | 14-JUN-08:30 | 3413.54 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 7.98 | 0.00 | 01-JAN-00:45 | 3413.54 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 7.11 | 0.00 | 01-JAN-00:15 | 2988.40 | 11-JUL-17:15 |
EnergyTransfer:Zone:F7 NW APARTMENT | 14.05 | 0.05 | 06-JUN-14:30 | 3435.53 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 10.49 | 0.00 | 01-JAN-17:15 | 3435.53 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 3.56 | 0.00 | 01-JAN-00:15 | 2405.14 | 15-JUL-18:00 |
EnergyTransfer:Zone:F7 SE APARTMENT | 14.55 | 0.02 | 03-SEP-08:30 | 3402.20 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 8.00 | 0.00 | 01-JAN-00:45 | 3402.20 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 6.55 | 0.00 | 01-JAN-00:15 | 2590.32 | 11-JUL-13:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 13.80 | 0.02 | 06-SEP-12:45 | 3424.27 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 10.48 | 0.00 | 01-JAN-17:30 | 3424.27 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 3.32 | 0.00 | 01-JAN-00:15 | 1599.99 | 11-JUL-16:15 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 7.97 | 0.04 | 29-OCT-21:00 | 2204.03 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 3.81 | 0.00 | 01-JAN-01:00 | 2204.03 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 4.16 | 0.00 | 01-JAN-00:15 | 1105.72 | 16-JUL-18:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 7.97 | 0.01 | 17-AUG-13:45 | 2230.29 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 3.82 | 0.00 | 01-JAN-01:00 | 2230.29 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 4.15 | 0.00 | 01-JAN-00:15 | 1081.58 | 16-JUL-18:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 10.26 | 0.03 | 29-AUG-10:00 | 2169.56 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 2.50 | 0.00 | 01-JAN-00:15 | 1880.57 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 7.77 | 0.00 | 02-JAN-10:30 | 2169.56 | 13-SEP-13:45 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 10.24 | 0.01 | 05-JUL-10:15 | 2178.93 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 2.50 | 0.00 | 01-JAN-00:15 | 1879.99 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 7.74 | 0.00 | 02-JAN-10:30 | 2178.93 | 13-SEP-13:45 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 15.24 | 0.01 | 27-FEB-11:15 | 3578.54 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 8.59 | 0.00 | 01-JAN-00:45 | 3578.54 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 6.65 | 0.00 | 01-JAN-00:15 | 2979.67 | 11-JUL-17:15 |
EnergyTransfer:Zone:F8 NW APARTMENT | 14.50 | 0.02 | 31-JUL-20:30 | 3600.24 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 11.18 | 0.00 | 01-JAN-17:15 | 3600.24 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 3.32 | 0.00 | 01-JAN-00:15 | 2397.72 | 15-JUL-18:00 |
EnergyTransfer:Zone:F8 SE APARTMENT | 14.73 | 0.00 | 03-SEP-01:00 | 3567.15 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 8.61 | 0.00 | 01-JAN-01:15 | 3567.15 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 6.11 | 0.00 | 01-JAN-00:15 | 2580.56 | 11-JUL-13:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 14.29 | 0.00 | 29-AUG-17:00 | 3588.93 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 11.18 | 0.00 | 29-JAN-17:15 | 3588.93 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 3.11 | 0.00 | 01-JAN-00:15 | 1591.56 | 11-JUL-16:15 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 8.17 | 0.03 | 13-AUG-12:00 | 2447.13 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 4.23 | 0.00 | 01-JAN-07:45 | 2447.13 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 3.95 | 0.00 | 01-JAN-00:15 | 1104.06 | 16-JUL-18:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 8.18 | 0.02 | 28-AUG-14:30 | 2469.70 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 4.24 | 0.00 | 01-JAN-07:30 | 2469.70 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 3.94 | 0.00 | 01-JAN-00:15 | 1080.13 | 16-JUL-18:00 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 10.10 | 0.01 | 15-OCT-11:15 | 2138.24 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 2.80 | 0.00 | 01-JAN-00:15 | 1984.92 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 7.30 | 0.00 | 02-JAN-10:15 | 2138.24 | 13-SEP-13:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 10.08 | 0.07 | 20-JAN-18:30 | 2147.71 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 2.81 | 0.00 | 01-JAN-00:15 | 1984.33 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 7.27 | 0.00 | 02-JAN-10:15 | 2147.71 | 13-SEP-13:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 15.93 | 0.03 | 06-NOV-17:15 | 3777.48 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 9.80 | 0.00 | 01-JAN-01:00 | 3777.48 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 6.14 | 0.00 | 01-JAN-00:15 | 3045.29 | 11-JUL-17:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 15.65 | 0.00 | 03-SEP-22:30 | 3797.73 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 12.54 | 0.00 | 06-JAN-15:00 | 3797.73 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 3.11 | 0.00 | 01-JAN-00:15 | 2436.57 | 15-JUL-18:00 |
EnergyTransfer:Zone:F9 SE APARTMENT | 15.40 | 0.03 | 17-AUG-00:15 | 3766.07 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 9.80 | 0.00 | 01-JAN-01:00 | 3766.07 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 5.60 | 0.00 | 01-JAN-00:15 | 2600.50 | 11-JUL-13:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 15.46 | 0.01 | 23-MAR-11:30 | 3786.42 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 12.51 | 0.00 | 31-JAN-21:00 | 3786.42 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 2.95 | 0.00 | 01-JAN-00:15 | 1624.59 | 11-JUL-19:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 8.77 | 0.03 | 16-MAY-01:45 | 2706.55 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 5.15 | 0.00 | 01-JAN-11:30 | 2706.55 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.62 | 0.00 | 01-JAN-00:15 | 1141.92 | 16-JUL-18:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 8.78 | 0.03 | 25-AUG-12:30 | 2725.73 | 01-SEP-13:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 5.17 | 0.00 | 01-JAN-11:00 | 2725.73 | 01-SEP-13:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.61 | 0.00 | 01-JAN-00:15 | 1129.08 | 16-JUL-18:00 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 10.12 | 0.11 | 23-MAY-17:00 | 2202.31 | 15-MAY-15:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 3.48 | 0.00 | 01-JAN-00:15 | 2202.31 | 15-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 6.64 | 0.00 | 01-JAN-05:30 | 2118.69 | 13-SEP-14:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 10.10 | 0.21 | 13-MAR-08:30 | 2204.30 | 15-MAY-15:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 3.49 | 0.00 | 01-JAN-00:15 | 2204.30 | 15-MAY-15:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 6.61 | 0.00 | 01-JAN-05:30 | 2126.06 | 13-SEP-14:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 21.50 | 0.02 | 08-APR-18:45 | 4190.49 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 15.16 | 0.00 | 01-JAN-10:15 | 4190.49 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 6.34 | 0.00 | 01-JAN-00:15 | 3680.85 | 11-JUL-17:00 |
EnergyTransfer:Zone:T NW APARTMENT | 20.66 | 0.02 | 13-JUN-07:45 | 4207.39 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 17.53 | 0.00 | 06-JAN-14:00 | 4207.39 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 3.14 | 0.00 | 01-JAN-00:15 | 3001.53 | 15-JUL-17:45 |
EnergyTransfer:Zone:T SE APARTMENT | 20.74 | 0.00 | 10-JUL-01:30 | 4182.43 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 15.08 | 0.00 | 01-JAN-10:00 | 4182.43 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 5.66 | 0.00 | 01-JAN-00:15 | 3343.28 | 11-JUL-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 20.14 | 0.03 | 08-JUN-12:15 | 4199.43 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 17.41 | 0.00 | 05-FEB-09:30 | 4199.43 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 2.73 | 0.00 | 01-JAN-00:15 | 2162.36 | 11-JUL-13:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 12.17 | 0.01 | 31-JUL-07:00 | 3204.45 | 01-SEP-12:45 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 9.31 | 0.00 | 06-JAN-14:00 | 3204.45 | 01-SEP-12:45 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 2.86 | 0.00 | 01-JAN-00:15 | 1586.16 | 11-JUL-14:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 12.14 | 0.01 | 01-AUG-19:15 | 3208.76 | 01-SEP-12:45 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 9.32 | 0.00 | 06-JAN-14:00 | 3208.76 | 01-SEP-12:45 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 2.82 | 0.00 | 01-JAN-00:15 | 1588.90 | 11-JUL-14:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 12.99 | 0.01 | 23-JUN-10:00 | 3053.37 | 01-SEP-12:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 7.31 | 0.00 | 01-JAN-09:45 | 3053.37 | 01-SEP-12:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 5.68 | 0.00 | 01-JAN-00:15 | 2826.81 | 11-JUL-13:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 12.99 | 0.01 | 05-JUN-00:45 | 3055.77 | 01-SEP-12:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 7.33 | 0.00 | 01-JAN-09:45 | 3055.77 | 01-SEP-12:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 5.67 | 0.00 | 01-JAN-00:15 | 2843.33 | 11-JUL-13:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1496.03 | 505.43 | 11-AUG-01:15 | 187074.50 | 16-DEC-19:00 |
WaterSystems:EnergyTransfer | 917.60 | 505.43 | 11-AUG-01:15 | 59367.80 | 16-FEB-07:30 |
sub cat:WaterSystems:EnergyTransfer | 917.60 | 505.43 | 11-AUG-01:15 | 59367.80 | 16-FEB-07:30 |
EnergyTransfer:HVAC | 1113.06 | 0.00 | 03-MAY-06:00 | 217722.90 | 16-DEC-17:00 |
CoolingCoils:EnergyTransfer | 303.45 | 0.00 | 01-JAN-00:15 | 190291.50 | 11-JUL-17:00 |
HeatingCoils:EnergyTransfer | 809.61 | 0.00 | 25-MAR-16:30 | 217722.90 | 16-DEC-17:00 |
PlantLoopHeatingDemand:HVAC | 620.70 | 0.00 | 25-MAR-16:30 | 147676.03 | 16-DEC-17:00 |
HeatingCoils:PlantLoopHeatingDemand | 620.70 | 0.00 | 25-MAR-16:30 | 147676.03 | 16-DEC-17:00 |
Boilers:EnergyTransfer | 578.43 | 0.00 | 06-FEB-16:15 | 145857.15 | 16-DEC-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 7.007 | -4.272 | 0.000 | 0.000 | 3.892 | 1.087 | 12.213 | 17.198 | 0.000 | 0.001 | 0.000 | 0.000 | -12.641 | 0.000 | -9.786 | -14.698 |
G NW APARTMENT | 8.876 | -2.520 | 0.000 | 0.000 | 3.946 | 1.087 | 12.213 | 8.558 | 0.000 | 0.001 | 0.000 | 0.000 | -12.548 | 0.000 | -9.090 | -10.522 |
OFFICE | 4.788 | -13.002 | 0.000 | 0.000 | 0.529 | 29.882 | 9.495 | 16.107 | 0.000 | 0.000 | 0.000 | 0.000 | -12.756 | 0.000 | -5.556 | -29.487 |
G NE APARTMENT | 8.925 | -2.539 | 0.000 | 0.000 | 3.969 | 1.087 | 12.213 | 7.600 | 0.000 | 0.001 | 0.000 | 0.000 | -12.341 | 0.000 | -9.030 | -9.885 |
G N1 APARTMENT | 4.395 | -2.974 | 0.000 | 0.000 | 3.976 | 1.087 | 12.213 | 2.594 | 0.000 | 0.001 | 0.000 | 0.000 | -7.686 | 0.000 | -6.531 | -7.073 |
G N2 APARTMENT | 4.402 | -2.953 | 0.000 | 0.000 | 3.977 | 1.087 | 12.213 | 2.594 | 0.000 | 0.001 | 0.000 | 0.000 | -7.681 | 0.000 | -6.528 | -7.111 |
G S1 APARTMENT | 2.715 | -4.475 | 0.000 | 0.000 | 3.891 | 1.087 | 12.213 | 11.324 | 0.000 | 0.001 | 0.000 | 0.000 | -7.765 | 0.000 | -7.419 | -11.571 |
G S2 APARTMENT | 2.545 | -4.606 | 0.000 | 0.000 | 3.885 | 1.087 | 12.213 | 11.306 | 0.000 | 0.001 | 0.000 | 0.000 | -7.787 | 0.000 | -7.483 | -11.160 |
F2 SW APARTMENT | 5.812 | -7.802 | 0.000 | 0.000 | 3.818 | 1.087 | 12.213 | 16.661 | 0.000 | 0.001 | 0.000 | 0.000 | -13.397 | 0.000 | -13.065 | -5.328 |
F2 NW APARTMENT | 7.925 | -3.838 | 0.000 | 0.000 | 3.894 | 1.087 | 12.213 | 8.155 | 0.000 | 0.001 | 0.000 | 0.000 | -13.168 | 0.000 | -12.260 | -4.009 |
F2 SE APARTMENT | 5.086 | -8.270 | 0.000 | 0.000 | 3.810 | 1.087 | 12.213 | 15.641 | 0.000 | 0.001 | 0.000 | 0.000 | -13.357 | 0.000 | -13.242 | -2.969 |
F2 NE APARTMENT | 7.922 | -3.567 | 0.000 | 0.000 | 3.917 | 1.087 | 12.213 | 7.218 | 0.000 | 0.001 | 0.000 | 0.000 | -12.941 | 0.000 | -12.196 | -3.654 |
F2 N1 APARTMENT | 2.722 | -4.178 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 2.375 | 0.000 | 0.001 | 0.000 | 0.000 | -8.123 | 0.000 | -8.706 | -1.312 |
F2 N2 APARTMENT | 2.731 | -4.175 | 0.000 | 0.000 | 3.924 | 1.087 | 12.213 | 2.377 | 0.000 | 0.001 | 0.000 | 0.000 | -8.116 | 0.000 | -8.695 | -1.345 |
F2 S1 APARTMENT | 1.690 | -7.708 | 0.000 | 0.000 | 3.801 | 1.087 | 12.213 | 10.990 | 0.000 | 0.001 | 0.000 | 0.000 | -8.265 | 0.000 | -9.783 | -4.025 |
F2 S2 APARTMENT | 1.664 | -7.801 | 0.000 | 0.000 | 3.799 | 1.087 | 12.213 | 10.985 | 0.000 | 0.001 | 0.001 | 0.000 | -8.274 | 0.000 | -9.803 | -3.871 |
F3 SW APARTMENT | 5.884 | -8.434 | 0.000 | 0.000 | 3.808 | 1.087 | 12.213 | 16.456 | 0.000 | 0.001 | 0.001 | 0.000 | -13.610 | 0.000 | -14.818 | -2.587 |
F3 NW APARTMENT | 8.024 | -4.219 | 0.000 | 0.000 | 3.885 | 1.087 | 12.213 | 8.010 | 0.000 | 0.001 | 0.000 | 0.000 | -13.364 | 0.000 | -13.961 | -1.675 |
F3 SE APARTMENT | 5.764 | -8.024 | 0.000 | 0.000 | 3.815 | 1.087 | 12.213 | 15.499 | 0.000 | 0.001 | 0.001 | 0.000 | -13.453 | 0.000 | -14.872 | -2.028 |
F3 NE APARTMENT | 8.020 | -3.905 | 0.000 | 0.000 | 3.907 | 1.087 | 12.213 | 7.086 | 0.000 | 0.001 | 0.000 | 0.000 | -13.138 | 0.000 | -13.889 | -1.382 |
F3 N1 APARTMENT | 2.599 | -4.624 | 0.000 | 0.000 | 3.905 | 1.087 | 12.213 | 2.300 | 0.000 | 0.001 | 0.655 | 0.000 | -8.268 | 0.000 | -9.869 | -0.000 |
F3 N2 APARTMENT | 2.608 | -4.615 | 0.000 | 0.000 | 3.908 | 1.087 | 12.213 | 2.302 | 0.000 | 0.001 | 0.614 | 0.000 | -8.260 | 0.000 | -9.856 | -0.000 |
F3 S1 APARTMENT | 1.613 | -8.725 | 0.000 | 0.000 | 3.782 | 1.087 | 12.213 | 10.856 | 0.000 | 0.001 | 0.001 | 0.000 | -8.431 | 0.000 | -10.987 | -1.408 |
F3 S2 APARTMENT | 1.610 | -8.730 | 0.000 | 0.000 | 3.782 | 1.087 | 12.213 | 10.853 | 0.000 | 0.001 | 0.001 | 0.000 | -8.431 | 0.000 | -10.993 | -1.392 |
F4 SW APARTMENT | 6.277 | -8.521 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 16.330 | 0.000 | 0.002 | 0.001 | 0.000 | -13.704 | 0.000 | -15.694 | -1.797 |
F4 NW APARTMENT | 8.494 | -4.309 | 0.000 | 0.000 | 3.883 | 1.087 | 12.213 | 7.925 | 0.000 | 0.001 | 0.000 | 0.000 | -13.464 | 0.000 | -14.836 | -0.993 |
F4 SE APARTMENT | 6.276 | -7.951 | 0.000 | 0.000 | 3.816 | 1.087 | 12.213 | 15.392 | 0.000 | 0.002 | 0.001 | 0.000 | -13.527 | 0.000 | -15.727 | -1.580 |
F4 NE APARTMENT | 8.487 | -3.986 | 0.000 | 0.000 | 3.904 | 1.087 | 12.213 | 7.010 | 0.000 | 0.001 | 0.000 | 0.000 | -13.239 | 0.000 | -14.766 | -0.711 |
F4 N1 APARTMENT | 2.777 | -4.760 | 0.000 | 0.000 | 3.898 | 1.087 | 12.213 | 2.258 | 0.000 | 0.001 | 1.227 | 0.000 | -8.345 | 0.000 | -10.355 | -0.000 |
F4 N2 APARTMENT | 2.787 | -4.750 | 0.000 | 0.000 | 3.900 | 1.087 | 12.213 | 2.259 | 0.000 | 0.001 | 1.183 | 0.000 | -8.337 | 0.000 | -10.342 | -0.000 |
F4 S1 APARTMENT | 1.745 | -9.013 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 10.773 | 0.000 | 0.001 | 0.000 | 0.000 | -8.504 | 0.000 | -11.449 | -0.630 |
F4 S2 APARTMENT | 1.748 | -8.988 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 10.772 | 0.000 | 0.001 | 0.001 | 0.000 | -8.501 | 0.000 | -11.451 | -0.658 |
M SW APARTMENT | 6.596 | -8.392 | 0.000 | 0.000 | 3.809 | 1.087 | 12.213 | 16.234 | 0.000 | 0.002 | 0.001 | 0.000 | -13.778 | 0.000 | -16.764 | -1.006 |
M NW APARTMENT | 8.819 | -4.281 | 0.000 | 0.000 | 3.884 | 1.087 | 12.213 | 7.866 | 0.000 | 0.001 | 0.000 | 0.000 | -13.542 | 0.000 | -15.856 | -0.190 |
M SE APARTMENT | 6.612 | -7.796 | 0.000 | 0.000 | 3.818 | 1.087 | 12.213 | 15.305 | 0.000 | 0.002 | 0.001 | 0.000 | -13.597 | 0.000 | -16.790 | -0.854 |
M NE APARTMENT | 8.807 | -3.961 | 0.000 | 0.000 | 3.905 | 1.087 | 12.213 | 6.959 | 0.000 | 0.001 | 0.089 | 0.000 | -13.319 | 0.000 | -15.779 | -0.000 |
M N1 APARTMENT | 2.888 | -4.820 | 0.000 | 0.000 | 3.896 | 1.087 | 12.213 | 2.231 | 0.000 | 0.001 | 1.937 | 0.000 | -8.403 | 0.000 | -11.030 | -0.000 |
M N2 APARTMENT | 2.897 | -4.808 | 0.000 | 0.000 | 3.899 | 1.087 | 12.213 | 2.233 | 0.000 | 0.001 | 1.891 | 0.000 | -8.396 | 0.000 | -11.017 | -0.000 |
M S1 APARTMENT | 1.853 | -9.033 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 10.712 | 0.000 | 0.001 | 0.112 | 0.000 | -8.556 | 0.000 | -12.165 | -0.000 |
M S2 APARTMENT | 1.858 | -9.000 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 10.711 | 0.000 | 0.001 | 0.072 | 0.000 | -8.553 | 0.000 | -12.166 | -0.000 |
F6 SW APARTMENT | 7.365 | -7.631 | 0.000 | 0.000 | 3.818 | 1.087 | 12.213 | 16.188 | 0.000 | 0.002 | 0.000 | 0.000 | -13.762 | 0.000 | -17.614 | -1.665 |
F6 NW APARTMENT | 9.769 | -3.847 | 0.000 | 0.000 | 3.894 | 1.087 | 12.213 | 7.855 | 0.000 | 0.001 | 0.000 | 0.000 | -13.530 | 0.000 | -16.626 | -0.816 |
F6 SE APARTMENT | 7.387 | -7.054 | 0.000 | 0.000 | 3.829 | 1.087 | 12.213 | 15.266 | 0.000 | 0.002 | 0.002 | 0.000 | -13.581 | 0.000 | -17.632 | -1.516 |
F6 NE APARTMENT | 9.759 | -3.569 | 0.000 | 0.000 | 3.916 | 1.087 | 12.213 | 6.955 | 0.000 | 0.001 | 0.000 | 0.000 | -13.308 | 0.000 | -16.537 | -0.517 |
F6 N1 APARTMENT | 3.413 | -4.421 | 0.000 | 0.000 | 3.908 | 1.087 | 12.213 | 2.234 | 0.000 | 0.001 | 1.440 | 0.000 | -8.394 | 0.000 | -11.483 | -0.000 |
F6 N2 APARTMENT | 3.426 | -4.412 | 0.000 | 0.000 | 3.911 | 1.087 | 12.213 | 2.236 | 0.000 | 0.001 | 1.394 | 0.000 | -8.386 | 0.000 | -11.469 | -0.000 |
F6 S1 APARTMENT | 2.206 | -8.287 | 0.000 | 0.000 | 3.788 | 1.087 | 12.213 | 10.682 | 0.000 | 0.001 | 0.002 | 0.000 | -8.543 | 0.000 | -12.701 | -0.445 |
F6 S2 APARTMENT | 2.214 | -8.254 | 0.000 | 0.000 | 3.788 | 1.087 | 12.213 | 10.681 | 0.000 | 0.001 | 0.003 | 0.000 | -8.540 | 0.000 | -12.702 | -0.488 |
F7 SW APARTMENT | 7.981 | -7.108 | 0.000 | 0.000 | 3.826 | 1.087 | 12.213 | 16.144 | 0.000 | 0.002 | 0.001 | 0.000 | -13.762 | 0.000 | -18.359 | -2.024 |
F7 NW APARTMENT | 10.487 | -3.558 | 0.000 | 0.000 | 3.902 | 1.087 | 12.213 | 7.840 | 0.000 | 0.001 | 0.000 | 0.000 | -13.533 | 0.000 | -17.309 | -1.130 |
F7 SE APARTMENT | 8.003 | -6.551 | 0.000 | 0.000 | 3.836 | 1.087 | 12.213 | 15.228 | 0.000 | 0.002 | 0.000 | 0.000 | -13.580 | 0.000 | -18.370 | -1.866 |
F7 NE APARTMENT | 10.480 | -3.317 | 0.000 | 0.000 | 3.924 | 1.087 | 12.213 | 6.948 | 0.000 | 0.001 | 0.000 | 0.000 | -13.311 | 0.000 | -17.206 | -0.819 |
F7 N1 APARTMENT | 3.811 | -4.158 | 0.000 | 0.000 | 3.918 | 1.087 | 12.213 | 2.235 | 0.000 | 0.001 | 1.174 | 0.000 | -8.393 | 0.000 | -11.886 | -0.000 |
F7 N2 APARTMENT | 3.822 | -4.151 | 0.000 | 0.000 | 3.920 | 1.087 | 12.213 | 2.237 | 0.000 | 0.001 | 1.130 | 0.000 | -8.386 | 0.000 | -11.871 | -0.000 |
F7 S1 APARTMENT | 2.495 | -7.769 | 0.000 | 0.000 | 3.796 | 1.087 | 12.213 | 10.653 | 0.000 | 0.001 | 0.001 | 0.000 | -8.539 | 0.000 | -13.170 | -0.768 |
F7 S2 APARTMENT | 2.504 | -7.736 | 0.000 | 0.000 | 3.797 | 1.087 | 12.213 | 10.652 | 0.000 | 0.001 | 0.000 | 0.000 | -8.536 | 0.000 | -13.171 | -0.812 |
F8 SW APARTMENT | 8.594 | -6.649 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 16.107 | 0.000 | 0.002 | 0.000 | 0.000 | -13.760 | 0.000 | -19.056 | -2.369 |
F8 NW APARTMENT | 11.180 | -3.324 | 0.000 | 0.000 | 3.909 | 1.087 | 12.213 | 7.827 | 0.000 | 0.001 | 0.000 | 0.000 | -13.538 | 0.000 | -17.952 | -1.402 |
F8 SE APARTMENT | 8.612 | -6.115 | 0.000 | 0.000 | 3.844 | 1.087 | 12.213 | 15.195 | 0.000 | 0.002 | 0.000 | 0.000 | -13.579 | 0.000 | -19.063 | -2.195 |
F8 NE APARTMENT | 11.175 | -3.114 | 0.000 | 0.000 | 3.931 | 1.087 | 12.213 | 6.941 | 0.000 | 0.001 | 0.000 | 0.000 | -13.318 | 0.000 | -17.838 | -1.077 |
F8 N1 APARTMENT | 4.228 | -3.946 | 0.000 | 0.000 | 3.925 | 1.087 | 12.213 | 2.235 | 0.000 | 0.001 | 0.934 | 0.000 | -8.395 | 0.000 | -12.281 | -0.000 |
F8 N2 APARTMENT | 4.241 | -3.942 | 0.000 | 0.000 | 3.928 | 1.087 | 12.213 | 2.236 | 0.000 | 0.001 | 0.889 | 0.000 | -8.387 | 0.000 | -12.265 | -0.001 |
F8 S1 APARTMENT | 2.802 | -7.302 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 10.630 | 0.000 | 0.001 | 0.000 | 0.000 | -8.533 | 0.000 | -13.618 | -1.084 |
F8 S2 APARTMENT | 2.810 | -7.268 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 10.629 | 0.000 | 0.001 | 0.001 | 0.000 | -8.529 | 0.000 | -13.618 | -1.129 |
F9 SW APARTMENT | 9.797 | -6.137 | 0.000 | 0.000 | 3.841 | 1.087 | 12.213 | 16.093 | 0.000 | 0.002 | 0.000 | 0.000 | -13.714 | 0.000 | -19.647 | -3.534 |
F9 NW APARTMENT | 12.538 | -3.108 | 0.000 | 0.000 | 3.914 | 1.087 | 12.213 | 7.827 | 0.000 | 0.001 | 0.000 | 0.000 | -13.516 | 0.000 | -18.515 | -2.442 |
F9 SE APARTMENT | 9.803 | -5.597 | 0.000 | 0.000 | 3.853 | 1.087 | 12.213 | 15.185 | 0.000 | 0.002 | 0.000 | 0.000 | -13.537 | 0.000 | -19.662 | -3.345 |
F9 NE APARTMENT | 12.511 | -2.945 | 0.000 | 0.000 | 3.938 | 1.087 | 12.213 | 6.945 | 0.000 | 0.001 | 0.000 | 0.000 | -13.297 | 0.000 | -18.400 | -2.052 |
F9 N1 APARTMENT | 5.154 | -3.617 | 0.000 | 0.000 | 3.930 | 1.087 | 12.213 | 2.239 | 0.000 | 0.001 | 0.006 | 0.000 | -8.378 | 0.000 | -12.635 | -0.000 |
F9 N2 APARTMENT | 5.166 | -3.612 | 0.000 | 0.000 | 3.933 | 1.087 | 12.213 | 2.241 | 0.000 | 0.001 | 0.000 | 0.000 | -8.371 | 0.000 | -12.621 | -0.036 |
F9 S1 APARTMENT | 3.482 | -6.635 | 0.000 | 0.000 | 3.816 | 1.087 | 12.213 | 10.621 | 0.000 | 0.001 | 0.000 | 0.000 | -8.495 | 0.000 | -13.991 | -2.099 |
F9 S2 APARTMENT | 3.492 | -6.607 | 0.000 | 0.000 | 3.817 | 1.087 | 12.213 | 10.620 | 0.000 | 0.001 | 0.000 | 0.000 | -8.491 | 0.000 | -13.992 | -2.140 |
T SW APARTMENT | 15.157 | -6.338 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 15.886 | 0.000 | 0.001 | 0.000 | 0.000 | -13.127 | 0.000 | -20.082 | -8.684 |
T NW APARTMENT | 17.525 | -3.135 | 0.000 | 0.000 | 3.942 | 1.087 | 12.213 | 7.672 | 0.000 | 0.001 | 0.000 | 0.000 | -13.032 | 0.000 | -19.082 | -7.189 |
T SE APARTMENT | 15.077 | -5.660 | 0.000 | 0.000 | 3.897 | 1.087 | 12.213 | 15.009 | 0.000 | 0.001 | 0.000 | 0.000 | -12.988 | 0.000 | -20.118 | -8.519 |
T NE APARTMENT | 17.405 | -2.731 | 0.000 | 0.000 | 3.964 | 1.087 | 12.213 | 6.812 | 0.000 | 0.001 | 0.000 | 0.000 | -12.851 | 0.000 | -19.024 | -6.876 |
T N1 APARTMENT | 9.305 | -2.862 | 0.000 | 0.000 | 3.954 | 1.087 | 12.213 | 2.190 | 0.000 | 0.001 | 0.000 | 0.000 | -8.069 | 0.000 | -13.081 | -4.737 |
T N2 APARTMENT | 9.321 | -2.823 | 0.000 | 0.000 | 3.956 | 1.087 | 12.213 | 2.188 | 0.000 | 0.001 | 0.000 | 0.000 | -8.061 | 0.000 | -13.081 | -4.800 |
T S1 APARTMENT | 7.310 | -5.680 | 0.000 | 0.000 | 3.862 | 1.087 | 12.213 | 10.516 | 0.000 | 0.001 | 0.000 | 0.000 | -8.166 | 0.000 | -14.280 | -6.863 |
T S2 APARTMENT | 7.326 | -5.665 | 0.000 | 0.000 | 3.863 | 1.087 | 12.213 | 10.513 | 0.000 | 0.001 | 0.000 | 0.000 | -8.160 | 0.000 | -14.284 | -6.893 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.604 | 0.000 | 0.000 | 44.120 | 0.000 | -2.764 | 0.000 | -61.401 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.683 | 0.000 | 0.000 | 0.000 | 0.000 | -1.698 | 0.000 | -1.421 | -15.004 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.645 | 0.000 | 0.000 | 0.000 | 0.000 | -1.764 | 0.000 | -1.732 | -14.589 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.625 | 0.000 | 0.000 | 0.000 | 0.000 | -1.792 | 0.000 | -1.956 | -14.316 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.602 | 0.000 | 0.000 | 0.000 | 0.000 | -1.836 | 0.000 | -2.215 | -30.431 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.611 | 0.000 | 0.000 | 0.000 | 0.000 | -1.800 | 0.000 | -2.265 | -13.987 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.612 | 0.000 | 0.000 | 0.000 | 0.000 | -1.788 | 0.000 | -2.370 | -13.894 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.610 | 0.000 | 0.000 | 0.000 | 0.000 | -1.784 | 0.000 | -2.472 | -13.793 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.610 | 0.000 | 0.000 | 0.000 | 0.000 | -1.775 | 0.000 | -2.558 | -13.717 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.571 | 0.000 | 0.000 | 0.000 | 0.000 | -1.726 | 0.000 | -2.714 | -21.723 |
Total Facility | 503.379 | -446.960 | 0.000 | 0.000 | 306.385 | 296.560 | 982.450 | 746.581 | 0.000 | 0.107 | 58.889 | 0.000 | -884.669 | 0.000 | -1172.002 | -390.702 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 13-SEP-15:15 | 0.00 | -2312.33 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3819.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -115.89 | -1956.25 |
G NW APARTMENT | 15-JUL-18:00 | 0.00 | -1787.42 | 0.00 | 0.00 | 141.76 | 87.56 | 588.62 | 2776.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.68 | -1729.17 |
OFFICE | 13-SEP-13:15 | 0.00 | -3592.99 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 3432.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.65 | -2813.08 |
G NE APARTMENT | 11-JUL-16:45 | 0.00 | -1101.44 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 617.76 | 0.00 | 104.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -358.97 |
G N1 APARTMENT | 03-JUL-19:00 | 0.00 | -732.95 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 655.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.02 | -715.13 |
G N2 APARTMENT | 03-JUL-19:00 | 0.00 | -732.67 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 655.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -715.68 |
G S1 APARTMENT | 13-SEP-13:45 | 0.00 | -1642.33 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2971.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -170.97 | -1594.66 |
G S2 APARTMENT | 13-SEP-13:45 | 0.00 | -1700.08 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2970.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -170.97 | -1535.73 |
F2 SW APARTMENT | 13-SEP-15:15 | 0.00 | -2999.03 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3773.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144.56 | -1195.50 |
F2 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2385.20 | 0.00 | 0.00 | 141.76 | 87.56 | 588.62 | 2752.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.01 | -1098.90 |
F2 SE APARTMENT | 13-SEP-13:30 | 0.00 | -2768.31 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3275.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -233.83 | -709.91 |
F2 NE APARTMENT | 11-JUL-16:30 | 0.00 | -1591.05 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 651.72 | 0.00 | 81.15 | 119.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 11-JUL-21:10 | 0.00 | -1086.29 | 0.00 | 0.00 | 168.33 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 764.26 | 0.00 | -241.28 | 0.00 | -61.85 | 0.00 |
F2 N2 APARTMENT | 14-JUL-21:10 | 0.00 | -1066.19 | 0.00 | 0.00 | 166.14 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 691.73 | 0.00 | -237.51 | 0.00 | -11.00 | 0.00 |
F2 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2219.24 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2943.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.28 | -959.05 |
F2 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2239.66 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2942.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.28 | -938.30 |
F3 SW APARTMENT | 13-SEP-15:15 | 0.00 | -3016.14 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3749.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164.83 | -1133.98 |
F3 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2428.40 | 0.00 | 0.00 | 141.62 | 87.56 | 588.62 | 2741.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93.90 | -1036.94 |
F3 SE APARTMENT | 13-SEP-13:30 | 0.00 | -2653.07 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3262.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -258.73 | -786.60 |
F3 NE APARTMENT | 11-JUL-16:15 | 0.00 | -1636.00 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 710.65 | 0.00 | 60.88 | 126.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 11-JUL-21:10 | 0.00 | -1133.83 | 0.00 | 0.00 | 167.80 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 827.11 | 0.00 | -244.24 | 0.00 | -73.67 | 0.00 |
F3 N2 APARTMENT | 11-JUL-21:10 | 0.00 | -1111.44 | 0.00 | 0.00 | 167.93 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 804.39 | 0.00 | -243.94 | 0.00 | -73.77 | 0.00 |
F3 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2258.18 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2928.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.14 | -883.72 |
F3 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2269.27 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2928.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.14 | -872.44 |
F4 SW APARTMENT | 11-JUL-17:15 | 0.00 | -3019.28 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2793.44 | 0.00 | 81.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -674.01 |
F4 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2437.31 | 0.00 | 0.00 | 141.63 | 87.56 | 588.62 | 2734.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -99.26 | -1015.44 |
F4 SE APARTMENT | 13-SEP-13:30 | 0.00 | -2629.73 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3250.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -279.55 | -777.87 |
F4 NE APARTMENT | 09-JUN-08:55 | 0.00 | -1973.83 | 0.00 | 0.00 | 42.33 | 12.97 | 394.37 | 2217.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -296.81 | -396.08 |
F4 N1 APARTMENT | 06-JUL-20:00 | 0.00 | -1186.91 | 0.00 | 0.00 | 150.72 | 103.77 | 523.87 | 151.07 | 0.00 | 0.00 | 346.94 | 0.00 | 0.00 | 0.00 | -89.46 | 0.00 |
F4 N2 APARTMENT | 06-JUL-20:00 | 0.00 | -1202.04 | 0.00 | 0.00 | 151.07 | 103.77 | 523.87 | 152.24 | 0.00 | 0.00 | 360.55 | 0.00 | 0.00 | 0.00 | -89.46 | 0.00 |
F4 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2256.02 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2918.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.51 | -857.40 |
F4 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2265.61 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2918.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.51 | -847.63 |
M SW APARTMENT | 11-JUL-17:15 | 0.00 | -3044.16 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2789.99 | 0.00 | 81.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.73 |
M NW APARTMENT | 15-JUL-18:00 | 0.00 | -2463.04 | 0.00 | 0.00 | 141.70 | 87.56 | 588.62 | 2727.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.54 | -979.04 |
M SE APARTMENT | 11-JUL-13:00 | 0.00 | -2645.23 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2639.90 | 0.00 | 163.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -600.18 |
M NE APARTMENT | 09-JUN-08:55 | 0.00 | -1996.99 | 0.00 | 0.00 | 42.44 | 12.97 | 394.37 | 2206.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -322.86 | -336.63 |
M N1 APARTMENT | 06-JUL-20:00 | 0.00 | -1195.25 | 0.00 | 0.00 | 150.83 | 103.77 | 523.87 | 149.23 | 0.00 | 0.00 | 364.97 | 0.00 | 0.00 | 0.00 | -97.42 | 0.00 |
M N2 APARTMENT | 06-JUL-20:00 | 0.00 | -1210.38 | 0.00 | 0.00 | 151.19 | 103.77 | 523.87 | 150.43 | 0.00 | 0.00 | 378.54 | 0.00 | 0.00 | 0.00 | -97.42 | 0.00 |
M S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2262.87 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2910.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.87 | -825.92 |
M S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2272.22 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2910.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.87 | -816.41 |
F6 SW APARTMENT | 11-JUL-17:15 | 0.00 | -3006.09 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2788.43 | 0.00 | 81.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -682.04 |
F6 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2422.24 | 0.00 | 0.00 | 141.75 | 87.56 | 588.62 | 2723.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.82 | -1011.65 |
F6 SE APARTMENT | 11-JUL-13:00 | 0.00 | -2607.84 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2636.71 | 0.00 | 165.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.30 |
F6 NE APARTMENT | 09-JUN-08:55 | 0.00 | -1697.60 | 0.00 | 0.00 | 42.76 | 12.97 | 394.37 | 2202.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -345.46 | -609.44 |
F6 N1 APARTMENT | 06-JUL-20:00 | 0.00 | -1192.87 | 0.00 | 0.00 | 151.79 | 103.77 | 523.87 | 150.51 | 0.00 | 0.00 | 367.25 | 0.00 | 0.00 | 0.00 | -104.32 | 0.00 |
F6 N2 APARTMENT | 11-JUL-21:10 | 0.00 | -1115.34 | 0.00 | 0.00 | 168.44 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 832.31 | 0.00 | -245.97 | 0.00 | -96.27 | 0.00 |
F6 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2206.09 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2904.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.91 | -861.78 |
F6 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2215.45 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2904.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.91 | -852.25 |
F7 SW APARTMENT | 11-JUL-17:15 | 0.00 | -2988.40 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2786.47 | 0.00 | 81.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -697.38 |
F7 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2405.03 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2719.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -111.72 | -1020.97 |
F7 SE APARTMENT | 11-JUL-13:00 | 0.00 | -2590.30 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2633.25 | 0.00 | 166.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -651.83 |
F7 NE APARTMENT | 11-JUL-16:15 | 0.00 | -1600.08 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 704.88 | 0.00 | 61.34 | 95.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 11-JUL-21:10 | 0.00 | -1122.08 | 0.00 | 0.00 | 168.70 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 844.36 | 0.00 | -246.14 | 0.00 | -101.68 | 0.00 |
F7 N2 APARTMENT | 12-JUL-21:10 | 0.00 | -1092.00 | 0.00 | 0.00 | 166.30 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 843.56 | 0.00 | -219.71 | 0.00 | -154.98 | 0.00 |
F7 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2169.84 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2899.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -287.00 | -878.57 |
F7 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2179.22 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2898.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -287.00 | -869.02 |
F8 SW APARTMENT | 11-JUL-17:15 | 0.00 | -2979.67 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2784.43 | 0.00 | 80.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -703.52 |
F8 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2397.60 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2715.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -115.63 | -1020.58 |
F8 SE APARTMENT | 11-JUL-13:00 | 0.00 | -2580.53 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2629.96 | 0.00 | 167.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -659.38 |
F8 NE APARTMENT | 11-JUL-16:15 | 0.00 | -1591.64 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 703.87 | 0.00 | 61.03 | 88.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 12-JUL-21:10 | 0.00 | -1115.74 | 0.00 | 0.00 | 166.55 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 875.38 | 0.00 | -220.03 | 0.00 | -162.99 | 0.00 |
F8 N2 APARTMENT | 12-JUL-21:10 | 0.00 | -1105.06 | 0.00 | 0.00 | 166.70 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 864.15 | 0.00 | -219.63 | 0.00 | -162.99 | 0.00 |
F8 S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2138.53 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2894.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -300.38 | -891.72 |
F8 S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2148.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2894.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -300.38 | -882.07 |
F9 SW APARTMENT | 11-JUL-17:15 | 0.00 | -3045.28 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2780.37 | 0.00 | 80.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -633.17 |
F9 NW APARTMENT | 15-JUL-18:00 | 0.00 | -2436.44 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2710.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -120.17 | -971.70 |
F9 SE APARTMENT | 11-JUL-13:00 | 0.00 | -2600.47 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2626.04 | 0.00 | 168.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.28 |
F9 NE APARTMENT | 11-JUL-19:00 | 0.00 | -1624.21 | 0.00 | 0.00 | 141.49 | 103.77 | 547.42 | 614.18 | 0.00 | 0.00 | 300.30 | 0.00 | 0.00 | 0.00 | -82.95 | 0.00 |
F9 N1 APARTMENT | 11-JUL-21:10 | 0.00 | -1178.36 | 0.00 | 0.00 | 168.29 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 914.86 | 0.00 | -249.44 | 0.00 | -112.19 | 0.00 |
F9 N2 APARTMENT | 11-JUL-21:10 | 0.00 | -1155.24 | 0.00 | 0.00 | 168.43 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 891.26 | 0.00 | -249.07 | 0.00 | -112.21 | 0.00 |
F9 S1 APARTMENT | 13-SEP-14:15 | 0.00 | -2119.23 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2576.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.74 | -648.48 |
F9 S2 APARTMENT | 13-SEP-14:15 | 0.00 | -2126.60 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2576.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -272.74 | -640.95 |
T SW APARTMENT | 11-JUL-17:00 | 0.00 | -3680.76 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2786.00 | 0.00 | 124.91 | 31.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 15-JUL-17:45 | 0.00 | -3001.55 | 0.00 | 0.00 | 141.51 | 87.56 | 588.62 | 2644.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.35 | -352.97 |
T SE APARTMENT | 11-JUL-13:00 | 0.00 | -3343.25 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2583.87 | 0.00 | 169.01 | 148.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 11-JUL-13:45 | 0.00 | -2162.17 | 0.00 | 0.00 | 40.65 | 12.97 | 382.60 | 1008.78 | 0.00 | 51.77 | 665.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 11-JUL-14:00 | 0.00 | -1586.06 | 0.00 | 0.00 | 40.37 | 12.97 | 382.60 | 619.52 | 0.00 | 12.23 | 518.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 11-JUL-14:00 | 0.00 | -1588.79 | 0.00 | 0.00 | 40.34 | 12.97 | 382.60 | 619.16 | 0.00 | 11.71 | 522.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 11-JUL-13:00 | 0.00 | -2826.77 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2225.78 | 0.00 | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1.56 |
T S2 APARTMENT | 11-JUL-13:00 | 0.00 | -2843.29 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2225.45 | 0.00 | 160.35 | 15.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-16:30 | 0.00 | -143031.19 | 0.00 | 0.00 | 6675.37 | 11327.17 | 47312.53 | 91471.64 | 0.00 | 5831.92 | 0.00 | 0.00 | 0.00 | 0.00 | -81.37 | -19506.09 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 16-DEC-17:00 | 1864.37 | 0.00 | 0.00 | 0.00 | 56.90 | 45.40 | 470.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -868.05 | 0.00 | -1150.77 | -418.74 |
G NW APARTMENT | 16-DEC-17:00 | 1862.68 | 0.00 | 0.00 | 0.00 | 56.90 | 45.40 | 470.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -866.25 | 0.00 | -1150.77 | -418.85 |
OFFICE | 16-DEC-19:00 | 2022.58 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1006.84 | 0.00 | -1114.70 | -564.45 |
G NE APARTMENT | 16-DEC-17:00 | 1867.16 | 0.00 | 0.00 | 0.00 | 56.90 | 45.40 | 470.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -874.24 | 0.00 | -1150.79 | -415.32 |
G N1 APARTMENT | 03-MAY-13:55 | 1325.81 | 0.00 | 0.00 | 0.00 | 45.95 | 12.97 | 382.60 | 338.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1310.77 | -794.74 |
G N2 APARTMENT | 05-SEP-08:00 | 1355.46 | 0.00 | 0.00 | 0.00 | 68.74 | 19.46 | 388.49 | 80.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1666.78 | -245.59 |
G S1 APARTMENT | 15-MAY-14:40 | 1417.28 | 0.00 | 0.00 | 0.00 | 45.74 | 22.70 | 400.26 | 474.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1438.52 | -921.99 |
G S2 APARTMENT | 15-MAY-14:40 | 1105.87 | 0.00 | 0.00 | 0.00 | 45.36 | 22.70 | 400.26 | 471.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1450.34 | -594.86 |
F2 SW APARTMENT | 03-DEC-02:00 | 2278.34 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -749.93 | 0.00 | -1870.30 | -95.59 |
F2 NW APARTMENT | 03-DEC-02:00 | 2299.76 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -758.07 | 0.00 | -1870.31 | -108.87 |
F2 SE APARTMENT | 03-DEC-02:00 | 2240.03 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -744.84 | 0.00 | -1870.30 | -62.38 |
F2 NE APARTMENT | 03-DEC-02:00 | 2289.31 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -751.76 | 0.00 | -1870.31 | -104.73 |
F2 N1 APARTMENT | 05-SEP-08:00 | 1480.05 | 0.00 | 0.00 | 0.00 | 68.21 | 19.46 | 388.49 | 60.32 | 0.00 | 0.00 | 147.24 | 0.00 | 0.00 | 0.00 | -2163.76 | 0.00 |
F2 N2 APARTMENT | 05-SEP-08:00 | 1482.65 | 0.00 | 0.00 | 0.00 | 68.15 | 19.46 | 388.49 | 59.90 | 0.00 | 0.00 | 145.10 | 0.00 | 0.00 | 0.00 | -2163.75 | 0.00 |
F2 S1 APARTMENT | 15-MAY-14:45 | 1614.78 | 0.00 | 0.00 | 0.00 | 43.04 | 22.70 | 400.26 | 421.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1807.20 | -695.09 |
F2 S2 APARTMENT | 15-MAY-14:45 | 1581.50 | 0.00 | 0.00 | 0.00 | 42.97 | 22.70 | 400.26 | 420.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1808.78 | -659.48 |
F3 SW APARTMENT | 03-DEC-02:00 | 2569.55 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -758.10 | 0.00 | -2216.61 | -32.33 |
F3 NW APARTMENT | 03-DEC-02:00 | 2591.05 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -766.93 | 0.00 | -2216.61 | -45.00 |
F3 SE APARTMENT | 03-DEC-02:00 | 2552.54 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -751.58 | 0.00 | -2216.61 | -21.84 |
F3 NE APARTMENT | 03-DEC-02:00 | 2580.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -760.19 | 0.00 | -2216.62 | -40.88 |
F3 N1 APARTMENT | 05-SEP-08:00 | 1538.69 | 0.00 | 0.00 | 0.00 | 68.38 | 19.46 | 388.49 | 54.46 | 0.00 | 0.00 | 416.95 | 0.00 | 0.00 | 0.00 | -2486.43 | 0.00 |
F3 N2 APARTMENT | 05-SEP-08:00 | 1541.18 | 0.00 | 0.00 | 0.00 | 68.34 | 19.46 | 388.49 | 54.19 | 0.00 | 0.00 | 414.75 | 0.00 | 0.00 | 0.00 | -2486.41 | 0.00 |
F3 S1 APARTMENT | 03-DEC-02:00 | 1374.87 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.66 | 0.00 | -1337.00 | -14.70 |
F3 S2 APARTMENT | 03-DEC-02:00 | 1373.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.70 | 0.00 | -1337.00 | -13.42 |
F4 SW APARTMENT | 03-DEC-02:00 | 2818.34 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -762.67 | 0.00 | -2480.13 | -13.03 |
F4 NW APARTMENT | 03-DEC-02:00 | 2840.40 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -771.84 | 0.00 | -2480.13 | -25.92 |
F4 SE APARTMENT | 03-DEC-02:00 | 2806.11 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -755.68 | 0.00 | -2480.13 | -7.80 |
F4 NE APARTMENT | 03-DEC-02:00 | 2829.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -764.87 | 0.00 | -2480.15 | -21.85 |
F4 N1 APARTMENT | 05-SEP-08:15 | 1650.01 | 0.00 | 0.00 | 0.00 | 43.78 | 12.97 | 394.37 | 63.92 | 0.00 | 0.00 | 578.24 | 0.00 | 0.00 | 0.00 | -2743.29 | 0.00 |
F4 N2 APARTMENT | 05-SEP-08:15 | 1648.68 | 0.00 | 0.00 | 0.00 | 43.77 | 12.97 | 394.37 | 63.73 | 0.00 | 0.00 | 579.74 | 0.00 | 0.00 | 0.00 | -2743.27 | 0.00 |
F4 S1 APARTMENT | 15-MAY-14:45 | 1614.59 | 0.00 | 0.00 | 0.00 | 42.14 | 22.70 | 400.26 | 391.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2252.38 | -218.65 |
F4 S2 APARTMENT | 15-MAY-14:45 | 1617.18 | 0.00 | 0.00 | 0.00 | 42.14 | 22.70 | 400.26 | 391.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2252.46 | -221.14 |
M SW APARTMENT | 03-DEC-02:00 | 3014.87 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 12.59 | 0.00 | -766.86 | 0.00 | -2698.08 | 0.00 |
M NW APARTMENT | 03-DEC-02:00 | 3036.29 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.55 | 0.00 | -776.24 | 0.00 | -2698.09 | 0.00 |
M SE APARTMENT | 03-DEC-02:00 | 3003.57 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 16.68 | 0.00 | -759.65 | 0.00 | -2698.08 | 0.00 |
M NE APARTMENT | 03-DEC-02:00 | 3025.19 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 | -769.10 | 0.00 | -2698.11 | 0.00 |
M N1 APARTMENT | 05-SEP-08:10 | 1980.90 | 0.00 | 0.00 | 0.00 | 43.78 | 12.97 | 394.37 | 60.10 | 0.00 | 0.00 | 491.63 | 0.00 | 0.00 | 0.00 | -2983.75 | 0.00 |
M N2 APARTMENT | 05-SEP-08:10 | 1969.10 | 0.00 | 0.00 | 0.00 | 43.77 | 12.97 | 394.37 | 59.96 | 0.00 | 0.00 | 503.52 | 0.00 | 0.00 | 0.00 | -2983.71 | 0.00 |
M S1 APARTMENT | 15-MAY-14:45 | 1913.22 | 0.00 | 0.00 | 0.00 | 42.22 | 22.70 | 400.26 | 386.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2411.04 | -353.68 |
M S2 APARTMENT | 15-MAY-14:45 | 1915.59 | 0.00 | 0.00 | 0.00 | 42.22 | 22.70 | 400.26 | 386.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2411.09 | -356.04 |
F6 SW APARTMENT | 03-DEC-02:00 | 3231.68 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -768.02 | 0.00 | -2886.54 | -14.61 |
F6 NW APARTMENT | 03-DEC-02:00 | 3253.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -777.57 | 0.00 | -2886.55 | -27.29 |
F6 SE APARTMENT | 03-DEC-02:00 | 3220.39 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -760.71 | 0.00 | -2886.54 | -10.62 |
F6 NE APARTMENT | 03-DEC-02:00 | 3242.73 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -770.34 | 0.00 | -2886.58 | -23.30 |
F6 N1 APARTMENT | 05-SEP-08:10 | 2601.67 | 0.00 | 0.00 | 0.00 | 44.19 | 12.97 | 394.37 | 62.04 | 0.00 | 0.00 | 49.48 | 0.00 | 0.00 | 0.00 | -3164.73 | 0.00 |
F6 N2 APARTMENT | 05-SEP-08:10 | 2593.68 | 0.00 | 0.00 | 0.00 | 44.18 | 12.97 | 394.37 | 61.96 | 0.00 | 0.00 | 57.51 | 0.00 | 0.00 | 0.00 | -3164.68 | 0.00 |
F6 S1 APARTMENT | 05-SEP-08:15 | 2095.85 | 0.00 | 0.00 | 0.00 | 41.56 | 12.97 | 394.37 | 987.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3157.34 | -375.15 |
F6 S2 APARTMENT | 05-SEP-08:15 | 2103.66 | 0.00 | 0.00 | 0.00 | 41.48 | 12.97 | 394.37 | 986.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3157.55 | -381.85 |
F7 SW APARTMENT | 03-DEC-02:00 | 3412.46 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -769.65 | 0.00 | -3054.08 | -26.22 |
F7 NW APARTMENT | 03-DEC-02:00 | 3434.50 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -779.33 | 0.00 | -3054.10 | -38.56 |
F7 SE APARTMENT | 03-DEC-02:00 | 3401.14 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -762.27 | 0.00 | -3054.08 | -22.28 |
F7 NE APARTMENT | 03-DEC-02:00 | 3423.28 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.03 | 0.00 | -3054.12 | -34.62 |
F7 N1 APARTMENT | 05-SEP-08:10 | 3151.87 | 0.00 | 0.00 | 0.00 | 44.54 | 12.97 | 394.37 | 63.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3328.81 | -338.75 |
F7 N2 APARTMENT | 05-SEP-08:10 | 3145.96 | 0.00 | 0.00 | 0.00 | 44.53 | 12.97 | 394.37 | 63.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3328.80 | -332.79 |
F7 S1 APARTMENT | 05-SEP-08:15 | 2119.36 | 0.00 | 0.00 | 0.00 | 41.93 | 12.97 | 394.37 | 986.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3328.46 | -226.25 |
F7 S2 APARTMENT | 05-SEP-08:15 | 2126.18 | 0.00 | 0.00 | 0.00 | 41.85 | 12.97 | 394.37 | 985.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3328.64 | -232.04 |
F8 SW APARTMENT | 03-DEC-02:00 | 3577.43 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -771.11 | 0.00 | -3205.90 | -37.91 |
F8 NW APARTMENT | 03-DEC-02:00 | 3599.18 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -780.89 | 0.00 | -3205.92 | -49.86 |
F8 SE APARTMENT | 03-DEC-02:00 | 3566.06 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -763.66 | 0.00 | -3205.90 | -33.99 |
F8 NE APARTMENT | 03-DEC-02:00 | 3587.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.52 | 0.00 | -3205.95 | -45.94 |
F8 N1 APARTMENT | 05-SEP-08:10 | 3862.60 | 0.00 | 0.00 | 0.00 | 44.80 | 12.97 | 394.37 | 64.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3527.70 | -851.82 |
F8 N2 APARTMENT | 05-SEP-08:10 | 3797.49 | 0.00 | 0.00 | 0.00 | 44.79 | 12.97 | 394.37 | 64.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3539.58 | -774.77 |
F8 S1 APARTMENT | 05-SEP-08:15 | 2149.91 | 0.00 | 0.00 | 0.00 | 42.23 | 12.97 | 394.37 | 984.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3485.59 | -98.39 |
F8 S2 APARTMENT | 05-SEP-08:15 | 2156.02 | 0.00 | 0.00 | 0.00 | 42.16 | 12.97 | 394.37 | 983.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3485.77 | -103.51 |
F9 SW APARTMENT | 03-DEC-02:00 | 3776.33 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -770.50 | 0.00 | -3345.41 | -97.91 |
F9 NW APARTMENT | 03-DEC-02:00 | 3796.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -780.29 | 0.00 | -3345.43 | -108.40 |
F9 SE APARTMENT | 03-DEC-02:00 | 3764.94 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -763.02 | 0.00 | -3345.41 | -93.99 |
F9 NE APARTMENT | 03-DEC-02:00 | 3785.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.90 | 0.00 | -3345.46 | -104.51 |
F9 N1 APARTMENT | 05-SEP-08:10 | 3715.72 | 0.00 | 0.00 | 0.00 | 45.00 | 12.97 | 394.37 | 65.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3657.87 | -575.82 |
F9 N2 APARTMENT | 05-SEP-08:10 | 3790.79 | 0.00 | 0.00 | 0.00 | 44.99 | 12.97 | 394.37 | 65.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3672.03 | -636.59 |
F9 S1 APARTMENT | 15-MAY-14:55 | 2493.44 | 0.00 | 0.00 | 0.00 | 44.02 | 22.70 | 400.26 | 449.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2975.00 | -435.00 |
F9 S2 APARTMENT | 15-MAY-14:55 | 2493.64 | 0.00 | 0.00 | 0.00 | 44.02 | 22.70 | 400.26 | 449.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2975.17 | -435.01 |
T SW APARTMENT | 03-DEC-02:00 | 4189.19 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -752.72 | 0.00 | -3474.69 | -399.27 |
T NW APARTMENT | 03-DEC-02:00 | 4206.15 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -761.19 | 0.00 | -3474.70 | -407.75 |
T SE APARTMENT | 03-DEC-02:00 | 4181.15 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -745.44 | 0.00 | -3474.69 | -398.51 |
T NE APARTMENT | 03-DEC-02:00 | 4198.25 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -753.94 | 0.00 | -3474.73 | -407.06 |
T N1 APARTMENT | 05-SEP-08:25 | 3521.35 | 0.00 | 0.00 | 0.00 | 46.07 | 12.97 | 394.37 | 110.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3779.59 | -305.35 |
T N2 APARTMENT | 05-SEP-08:25 | 3557.63 | 0.00 | 0.00 | 0.00 | 45.89 | 12.97 | 394.37 | 107.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3779.79 | -338.57 |
T S1 APARTMENT | 01-SEP-12:25 | 3651.22 | 0.00 | 0.00 | 0.00 | 43.91 | 12.97 | 388.49 | 87.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3611.90 | -572.53 |
T S2 APARTMENT | 01-SEP-12:25 | 3654.34 | 0.00 | 0.00 | 0.00 | 43.91 | 12.97 | 388.49 | 87.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3611.92 | -575.72 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-DEC-02:00 | 191298.08 | 0.00 | 0.00 | 0.00 | 14983.93 | 6715.87 | 19318.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50147.48 | 0.00 | -174456.49 | -7712.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Sec1.1A-General InformationData | |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 200.25 |
Number of hours cooling loads not met | 6.25 |
Number of hours not met | 206.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.51 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 213.87 | 63322.24 | 772.80 | 183438.27 | 0.00 | 0.00 |
Space Cooling | 99.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.23 | 1677.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 553.30 | 17544.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1178.71 | 74728.68 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2555.34 | 1951.51 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 2555.34 |
Natural Gas | 0.00 | 1951.51 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4506.85 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 27.29 |
Space Cooling | 12.65 |
Fans-Interior | 70.61 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 32.56 |
Subtotal | 326.08 |
Natural Gas [MJ/m2] | |
Space Heating | 98.62 |
Service Water Heating | 150.41 |
Miscellaneous | -0.00 |
Subtotal | 249.03 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.58 |
Space Heating | 21.89 |
Space Cooling | 2.20 |
Fans-Interior | 12.28 |
Service Water Heating | 26.15 |
Receptacle Equipment | 25.24 |
Miscellaneous | 5.66 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.215826 |
G NW APARTMENT DIRECT AIR | 0.146618 |
OFFICE DIRECT AIR | 0.337541 |
G NE APARTMENT DIRECT AIR | 0.103519 |
G N1 APARTMENT DIRECT AIR | 0.060532 |
G N2 APARTMENT DIRECT AIR | 0.060528 |
G S1 APARTMENT DIRECT AIR | 0.156552 |
G S2 APARTMENT DIRECT AIR | 0.163111 |
F2 SW APARTMENT DIRECT AIR | 0.280801 |
F2 NW APARTMENT DIRECT AIR | 0.196086 |
F2 SE APARTMENT DIRECT AIR | 0.282294 |
F2 NE APARTMENT DIRECT AIR | 0.146185 |
F2 N1 APARTMENT DIRECT AIR | 0.090309 |
F2 N2 APARTMENT DIRECT AIR | 0.088098 |
F2 S1 APARTMENT DIRECT AIR | 0.207860 |
F2 S2 APARTMENT DIRECT AIR | 0.210404 |
F3 SW APARTMENT DIRECT AIR | 0.282039 |
F3 NW APARTMENT DIRECT AIR | 0.198623 |
F3 SE APARTMENT DIRECT AIR | 0.262773 |
F3 NE APARTMENT DIRECT AIR | 0.149341 |
F3 N1 APARTMENT DIRECT AIR | 0.094253 |
F3 N2 APARTMENT DIRECT AIR | 0.092031 |
F3 S1 APARTMENT DIRECT AIR | 0.211281 |
F3 S2 APARTMENT DIRECT AIR | 0.212521 |
F4 SW APARTMENT DIRECT AIR | 0.281865 |
F4 NW APARTMENT DIRECT AIR | 0.198732 |
F4 SE APARTMENT DIRECT AIR | 0.260809 |
F4 NE APARTMENT DIRECT AIR | 0.149324 |
F4 N1 APARTMENT DIRECT AIR | 0.095106 |
F4 N2 APARTMENT DIRECT AIR | 0.092883 |
F4 S1 APARTMENT DIRECT AIR | 0.211879 |
F4 S2 APARTMENT DIRECT AIR | 0.212933 |
M SW APARTMENT DIRECT AIR | 0.283460 |
M NW APARTMENT DIRECT AIR | 0.200480 |
M SE APARTMENT DIRECT AIR | 0.262392 |
M NE APARTMENT DIRECT AIR | 0.150917 |
M N1 APARTMENT DIRECT AIR | 0.097309 |
M N2 APARTMENT DIRECT AIR | 0.095084 |
M S1 APARTMENT DIRECT AIR | 0.214031 |
M S2 APARTMENT DIRECT AIR | 0.215057 |
F6 SW APARTMENT DIRECT AIR | 0.279532 |
F6 NW APARTMENT DIRECT AIR | 0.196653 |
F6 SE APARTMENT DIRECT AIR | 0.258712 |
F6 NE APARTMENT DIRECT AIR | 0.147099 |
F6 N1 APARTMENT DIRECT AIR | 0.094256 |
F6 N2 APARTMENT DIRECT AIR | 0.092048 |
F6 S1 APARTMENT DIRECT AIR | 0.210583 |
F6 S2 APARTMENT DIRECT AIR | 0.211608 |
F7 SW APARTMENT DIRECT AIR | 0.277696 |
F7 NW APARTMENT DIRECT AIR | 0.194923 |
F7 SE APARTMENT DIRECT AIR | 0.257078 |
F7 NE APARTMENT DIRECT AIR | 0.145319 |
F7 N1 APARTMENT DIRECT AIR | 0.093091 |
F7 N2 APARTMENT DIRECT AIR | 0.090893 |
F7 S1 APARTMENT DIRECT AIR | 0.209163 |
F7 S2 APARTMENT DIRECT AIR | 0.210188 |
F8 SW APARTMENT DIRECT AIR | 0.276837 |
F8 NW APARTMENT DIRECT AIR | 0.194203 |
F8 SE APARTMENT DIRECT AIR | 0.256373 |
F8 NE APARTMENT DIRECT AIR | 0.144497 |
F8 N1 APARTMENT DIRECT AIR | 0.092911 |
F8 N2 APARTMENT DIRECT AIR | 0.090724 |
F8 S1 APARTMENT DIRECT AIR | 0.208678 |
F8 S2 APARTMENT DIRECT AIR | 0.209705 |
F9 SW APARTMENT DIRECT AIR | 0.281657 |
F9 NW APARTMENT DIRECT AIR | 0.199302 |
F9 SE APARTMENT DIRECT AIR | 0.259841 |
F9 NE APARTMENT DIRECT AIR | 0.144096 |
F9 N1 APARTMENT DIRECT AIR | 0.097664 |
F9 N2 APARTMENT DIRECT AIR | 0.095452 |
F9 S1 APARTMENT DIRECT AIR | 0.211736 |
F9 S2 APARTMENT DIRECT AIR | 0.212766 |
T SW APARTMENT DIRECT AIR | 0.342443 |
T NW APARTMENT DIRECT AIR | 0.244016 |
T SE APARTMENT DIRECT AIR | 0.316108 |
T NE APARTMENT DIRECT AIR | 0.180179 |
T N1 APARTMENT DIRECT AIR | 0.128306 |
T N2 APARTMENT DIRECT AIR | 0.128475 |
T S1 APARTMENT DIRECT AIR | 0.278397 |
T S2 APARTMENT DIRECT AIR | 0.279401 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.215826 |
AIRLOOP G NW MAIN BRANCH | 0.146618 |
AIRLOOP OFFICE MAIN BRANCH | 0.337541 |
AIRLOOP G NE MAIN BRANCH | 0.103519 |
AIRLOOP G N1 MAIN BRANCH | 0.060532 |
AIRLOOP G N2 MAIN BRANCH | 0.060528 |
AIRLOOP G S1 MAIN BRANCH | 0.156552 |
AIRLOOP G S2 MAIN BRANCH | 0.163111 |
AIRLOOP F2 SW MAIN BRANCH | 0.280801 |
AIRLOOP F2 NW MAIN BRANCH | 0.196086 |
AIRLOOP F2 SE MAIN BRANCH | 0.282294 |
AIRLOOP F2 NE MAIN BRANCH | 0.146185 |
AIRLOOP F2 N1 MAIN BRANCH | 0.090309 |
AIRLOOP F2 N2 MAIN BRANCH | 0.088098 |
AIRLOOP F2 S1 MAIN BRANCH | 0.207860 |
AIRLOOP F2 S2 MAIN BRANCH | 0.210404 |
AIRLOOP F3 SW MAIN BRANCH | 0.282039 |
AIRLOOP F3 NW MAIN BRANCH | 0.198623 |
AIRLOOP F3 SE MAIN BRANCH | 0.262773 |
AIRLOOP F3 NE MAIN BRANCH | 0.149341 |
AIRLOOP F3 N1 MAIN BRANCH | 0.094253 |
AIRLOOP F3 N2 MAIN BRANCH | 0.092031 |
AIRLOOP F3 S1 MAIN BRANCH | 0.211281 |
AIRLOOP F3 S2 MAIN BRANCH | 0.212521 |
AIRLOOP F4 SW MAIN BRANCH | 0.281865 |
AIRLOOP F4 NW MAIN BRANCH | 0.198732 |
AIRLOOP F4 SE MAIN BRANCH | 0.260809 |
AIRLOOP F4 NE MAIN BRANCH | 0.149324 |
AIRLOOP F4 N1 MAIN BRANCH | 0.095106 |
AIRLOOP F4 N2 MAIN BRANCH | 0.092883 |
AIRLOOP F4 S1 MAIN BRANCH | 0.211879 |
AIRLOOP F4 S2 MAIN BRANCH | 0.212933 |
AIRLOOP M SW MAIN BRANCH | 0.283460 |
AIRLOOP M NW MAIN BRANCH | 0.200480 |
AIRLOOP M SE MAIN BRANCH | 0.262392 |
AIRLOOP M NE MAIN BRANCH | 0.150917 |
AIRLOOP M N1 MAIN BRANCH | 0.097309 |
AIRLOOP M N2 MAIN BRANCH | 0.095084 |
AIRLOOP M S1 MAIN BRANCH | 0.214031 |
AIRLOOP M S2 MAIN BRANCH | 0.215057 |
AIRLOOP F6 SW MAIN BRANCH | 0.279532 |
AIRLOOP F6 NW MAIN BRANCH | 0.196653 |
AIRLOOP F6 SE MAIN BRANCH | 0.258712 |
AIRLOOP F6 NE MAIN BRANCH | 0.147099 |
AIRLOOP F6 N1 MAIN BRANCH | 0.094256 |
AIRLOOP F6 N2 MAIN BRANCH | 0.092048 |
AIRLOOP F6 S1 MAIN BRANCH | 0.210583 |
AIRLOOP F6 S2 MAIN BRANCH | 0.211608 |
AIRLOOP F7 SW MAIN BRANCH | 0.277696 |
AIRLOOP F7 NW MAIN BRANCH | 0.194923 |
AIRLOOP F7 SE MAIN BRANCH | 0.257078 |
AIRLOOP F7 NE MAIN BRANCH | 0.145319 |
AIRLOOP F7 N1 MAIN BRANCH | 0.093091 |
AIRLOOP F7 N2 MAIN BRANCH | 0.090893 |
AIRLOOP F7 S1 MAIN BRANCH | 0.209163 |
AIRLOOP F7 S2 MAIN BRANCH | 0.210188 |
AIRLOOP F8 SW MAIN BRANCH | 0.276837 |
AIRLOOP F8 NW MAIN BRANCH | 0.194203 |
AIRLOOP F8 SE MAIN BRANCH | 0.256373 |
AIRLOOP F8 NE MAIN BRANCH | 0.144497 |
AIRLOOP F8 N1 MAIN BRANCH | 0.092911 |
AIRLOOP F8 N2 MAIN BRANCH | 0.090724 |
AIRLOOP F8 S1 MAIN BRANCH | 0.208678 |
AIRLOOP F8 S2 MAIN BRANCH | 0.209705 |
AIRLOOP F9 SW MAIN BRANCH | 0.281657 |
AIRLOOP F9 NW MAIN BRANCH | 0.199302 |
AIRLOOP F9 SE MAIN BRANCH | 0.259841 |
AIRLOOP F9 NE MAIN BRANCH | 0.144096 |
AIRLOOP F9 N1 MAIN BRANCH | 0.097664 |
AIRLOOP F9 N2 MAIN BRANCH | 0.095452 |
AIRLOOP F9 S1 MAIN BRANCH | 0.211736 |
AIRLOOP F9 S2 MAIN BRANCH | 0.212766 |
AIRLOOP T SW MAIN BRANCH | 0.342443 |
AIRLOOP T NW MAIN BRANCH | 0.244016 |
AIRLOOP T SE MAIN BRANCH | 0.316108 |
AIRLOOP T NE MAIN BRANCH | 0.180179 |
AIRLOOP T N1 MAIN BRANCH | 0.128306 |
AIRLOOP T N2 MAIN BRANCH | 0.128475 |
AIRLOOP T S1 MAIN BRANCH | 0.278397 |
AIRLOOP T S2 MAIN BRANCH | 0.279401 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.215826 |
AIRLOOP G NW | 0.146618 |
AIRLOOP OFFICE | 0.337541 |
AIRLOOP G NE | 0.103519 |
AIRLOOP G N1 | 0.060532 |
AIRLOOP G N2 | 0.060528 |
AIRLOOP G S1 | 0.156552 |
AIRLOOP G S2 | 0.163111 |
AIRLOOP F2 SW | 0.280801 |
AIRLOOP F2 NW | 0.196086 |
AIRLOOP F2 SE | 0.282294 |
AIRLOOP F2 NE | 0.146185 |
AIRLOOP F2 N1 | 0.090309 |
AIRLOOP F2 N2 | 0.088098 |
AIRLOOP F2 S1 | 0.207860 |
AIRLOOP F2 S2 | 0.210404 |
AIRLOOP F3 SW | 0.282039 |
AIRLOOP F3 NW | 0.198623 |
AIRLOOP F3 SE | 0.262773 |
AIRLOOP F3 NE | 0.149341 |
AIRLOOP F3 N1 | 0.094253 |
AIRLOOP F3 N2 | 0.092031 |
AIRLOOP F3 S1 | 0.211281 |
AIRLOOP F3 S2 | 0.212521 |
AIRLOOP F4 SW | 0.281865 |
AIRLOOP F4 NW | 0.198732 |
AIRLOOP F4 SE | 0.260809 |
AIRLOOP F4 NE | 0.149324 |
AIRLOOP F4 N1 | 0.095106 |
AIRLOOP F4 N2 | 0.092883 |
AIRLOOP F4 S1 | 0.211879 |
AIRLOOP F4 S2 | 0.212933 |
AIRLOOP M SW | 0.283460 |
AIRLOOP M NW | 0.200480 |
AIRLOOP M SE | 0.262392 |
AIRLOOP M NE | 0.150917 |
AIRLOOP M N1 | 0.097309 |
AIRLOOP M N2 | 0.095084 |
AIRLOOP M S1 | 0.214031 |
AIRLOOP M S2 | 0.215057 |
AIRLOOP F6 SW | 0.279532 |
AIRLOOP F6 NW | 0.196653 |
AIRLOOP F6 SE | 0.258712 |
AIRLOOP F6 NE | 0.147099 |
AIRLOOP F6 N1 | 0.094256 |
AIRLOOP F6 N2 | 0.092048 |
AIRLOOP F6 S1 | 0.210583 |
AIRLOOP F6 S2 | 0.211608 |
AIRLOOP F7 SW | 0.277696 |
AIRLOOP F7 NW | 0.194923 |
AIRLOOP F7 SE | 0.257078 |
AIRLOOP F7 NE | 0.145319 |
AIRLOOP F7 N1 | 0.093091 |
AIRLOOP F7 N2 | 0.090893 |
AIRLOOP F7 S1 | 0.209163 |
AIRLOOP F7 S2 | 0.210188 |
AIRLOOP F8 SW | 0.276837 |
AIRLOOP F8 NW | 0.194203 |
AIRLOOP F8 SE | 0.256373 |
AIRLOOP F8 NE | 0.144497 |
AIRLOOP F8 N1 | 0.092911 |
AIRLOOP F8 N2 | 0.090724 |
AIRLOOP F8 S1 | 0.208678 |
AIRLOOP F8 S2 | 0.209705 |
AIRLOOP F9 SW | 0.281657 |
AIRLOOP F9 NW | 0.199302 |
AIRLOOP F9 SE | 0.259841 |
AIRLOOP F9 NE | 0.144096 |
AIRLOOP F9 N1 | 0.097664 |
AIRLOOP F9 N2 | 0.095452 |
AIRLOOP F9 S1 | 0.211736 |
AIRLOOP F9 S2 | 0.212766 |
AIRLOOP T SW | 0.342443 |
AIRLOOP T NW | 0.244016 |
AIRLOOP T SE | 0.316108 |
AIRLOOP T NE | 0.180179 |
AIRLOOP T N1 | 0.128306 |
AIRLOOP T N2 | 0.128475 |
AIRLOOP T S1 | 0.278397 |
AIRLOOP T S2 | 0.279401 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.215826 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.146618 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.337541 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.103519 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.060532 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.060528 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.156552 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.163111 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.280801 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.196086 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.282294 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.146185 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.090309 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.088098 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.207860 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.210404 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.282039 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.198623 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.262773 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.149341 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.094253 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.092031 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.211281 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.212521 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.281865 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.198732 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.260809 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.149324 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.095106 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.092883 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.211879 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.212933 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.283460 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.200480 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.262392 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.150917 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.097309 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.095084 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.214031 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.215057 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.279532 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.196653 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.258712 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.147099 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.094256 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.092048 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.210583 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.211608 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.277696 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.194923 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.257078 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.145319 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.093091 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.090893 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.209163 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.210188 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.276837 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.194203 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.256373 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.144497 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.092911 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.090724 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.208678 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.209705 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.281657 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.199302 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.259841 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.144096 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.097664 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.095452 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.211736 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.212766 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.342443 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.244016 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.316108 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.180179 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.128306 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.128475 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.278397 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.279401 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.215826 | 3301.54 | 2450.76 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.146618 | 2296.82 | 1672.42 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.337541 | 5084.36 | 3812.04 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.103519 | 1656.97 | 1180.74 | 0.000036 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.060532 | 1012.32 | 696.39 | 0.000022 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.060528 | 1015.61 | 696.74 | 0.000022 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.156552 | 2446.12 | 1794.31 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.163111 | 2538.35 | 1866.42 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.280801 | 4248.57 | 3174.90 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.196086 | 3026.90 | 2226.05 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.282294 | 4274.09 | 3193.58 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.146185 | 2281.79 | 1658.55 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.090309 | 1458.60 | 1031.49 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.088098 | 1425.63 | 1006.67 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.207860 | 3187.56 | 2364.19 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.210404 | 3223.36 | 2392.18 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.282039 | 4284.54 | 3193.70 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.198623 | 3079.39 | 2258.76 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.262773 | 4017.07 | 2983.73 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.149341 | 2341.05 | 1697.58 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.094253 | 1523.54 | 1077.63 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.092031 | 1490.39 | 1052.69 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.211281 | 3246.84 | 2404.97 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.212521 | 3264.27 | 2418.61 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.281865 | 4295.85 | 3195.65 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.198732 | 3093.12 | 2263.46 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.260809 | 4002.79 | 2965.89 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.149324 | 2351.59 | 1700.56 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.095106 | 1541.54 | 1088.83 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.092883 | 1508.27 | 1063.84 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.211879 | 3263.55 | 2413.90 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.212933 | 3278.36 | 2425.48 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.283460 | 4329.52 | 3216.35 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.200480 | 3127.84 | 2285.60 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.262392 | 4036.10 | 2986.42 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.150917 | 2382.94 | 1720.68 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.097309 | 1578.24 | 1114.73 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.095084 | 1544.93 | 1089.72 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.214031 | 3300.66 | 2439.50 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.215057 | 3315.10 | 2450.79 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.279532 | 4283.41 | 3175.71 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.196653 | 3081.49 | 2245.71 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.258712 | 3993.20 | 2948.45 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.147099 | 2335.57 | 1680.64 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.094256 | 1537.18 | 1081.85 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.092048 | 1503.94 | 1056.98 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.210583 | 3257.67 | 2403.14 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.211608 | 3272.10 | 2414.42 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.277696 | 4265.64 | 3157.79 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.194923 | 3063.90 | 2228.66 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.257078 | 3978.07 | 2932.71 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.145319 | 2316.23 | 1662.79 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.093091 | 1523.20 | 1069.83 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.090893 | 1490.01 | 1045.05 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.209163 | 3242.58 | 2388.91 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.210188 | 3257.02 | 2400.19 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.276837 | 4260.80 | 3150.40 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.194203 | 3059.92 | 2222.54 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.256373 | 3975.22 | 2926.97 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.144497 | 2309.84 | 1655.30 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.092911 | 1523.36 | 1068.69 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.090724 | 1490.25 | 1044.01 | 0.000033 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.208678 | 3240.17 | 2384.83 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.209705 | 3254.64 | 2396.13 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.281657 | 4335.87 | 3205.47 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.199302 | 3138.96 | 2280.68 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.259841 | 4033.47 | 2968.41 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.144096 | 2309.30 | 1652.43 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.097664 | 1596.30 | 1122.64 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.095452 | 1562.89 | 1097.70 | 0.000034 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.211736 | 3289.87 | 2420.97 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.212766 | 3304.39 | 2432.30 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.342443 | 5209.30 | 3880.80 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.244016 | 3789.16 | 2781.96 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.316108 | 4834.41 | 3589.33 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.180179 | 2848.36 | 2061.68 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.128306 | 2104.10 | 1500.74 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.128475 | 2106.64 | 1502.64 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.278397 | 4233.06 | 3155.17 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.279401 | 4247.16 | 3166.21 | 0.000093 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.215826 | 0.215826 | 0.215826 | 0.215826 | 3301.54 | 3301.54 | 2947.58 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.146618 | 0.146618 | 0.146618 | 0.146618 | 2296.82 | 2296.82 | 2952.99 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.337541 | 0.337541 | 0.337541 | 0.337541 | 5084.36 | 5084.36 | 3720.93 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.103519 | 0.103519 | 0.103519 | 0.103519 | 1656.97 | 1656.97 | 2949.94 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.060532 | 0.060532 | 0.060532 | 0.060532 | 1012.32 | 1012.32 | 2241.39 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.060528 | 0.060528 | 0.060528 | 0.060528 | 1015.61 | 1015.61 | 2241.32 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.156552 | 0.156552 | 0.156552 | 0.156552 | 2446.12 | 2446.12 | 2232.33 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.163111 | 0.163111 | 0.163111 | 0.163111 | 2538.35 | 2538.35 | 2238.56 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.280801 | 0.280801 | 0.280801 | 0.280801 | 4248.57 | 4248.57 | 2880.32 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.196086 | 0.196086 | 0.196086 | 0.196086 | 3026.90 | 3026.90 | 2880.67 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.282294 | 0.282294 | 0.282294 | 0.282294 | 4274.09 | 4274.09 | 2896.74 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.146185 | 0.146185 | 0.146185 | 0.146185 | 2281.79 | 2281.79 | 2878.42 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.090309 | 0.090309 | 0.090309 | 0.090309 | 1458.60 | 1458.60 | 1997.40 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.088098 | 0.088098 | 0.088098 | 0.088098 | 1425.63 | 1425.63 | 1997.35 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.207860 | 0.207860 | 0.207860 | 0.207860 | 3187.56 | 3187.56 | 1999.80 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.210404 | 0.210404 | 0.210404 | 0.210404 | 3223.36 | 3223.36 | 2000.97 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.282039 | 0.282039 | 0.282039 | 0.282039 | 4284.54 | 4284.54 | 2901.57 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.198623 | 0.198623 | 0.198623 | 0.198623 | 3079.39 | 3079.39 | 2902.68 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.262773 | 0.262773 | 0.262773 | 0.262773 | 4017.07 | 4017.07 | 2902.50 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.149341 | 0.149341 | 0.149341 | 0.149341 | 2341.05 | 2341.05 | 2901.54 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.094253 | 0.094253 | 0.094253 | 0.094253 | 1523.54 | 1523.54 | 1973.08 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.092031 | 0.092031 | 0.092031 | 0.092031 | 1490.39 | 1490.39 | 1973.05 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.211281 | 0.211281 | 0.211281 | 0.211281 | 3246.84 | 3246.84 | 1972.75 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.212521 | 0.212521 | 0.212521 | 0.212521 | 3264.27 | 3264.27 | 1972.92 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.281865 | 0.281865 | 0.281865 | 0.281865 | 4295.85 | 4295.85 | 2969.72 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.198732 | 0.198732 | 0.198732 | 0.198732 | 3093.12 | 3093.12 | 2971.33 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.260809 | 0.260809 | 0.260809 | 0.260809 | 4002.79 | 4002.79 | 2969.70 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.149324 | 0.149324 | 0.149324 | 0.149324 | 2351.59 | 2351.59 | 2971.09 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.095106 | 0.095106 | 0.095106 | 0.095106 | 1541.54 | 1541.54 | 2004.57 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.092883 | 0.092883 | 0.092883 | 0.092883 | 1508.27 | 1508.27 | 2004.56 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.211879 | 0.211879 | 0.211879 | 0.211879 | 3263.55 | 3263.55 | 2003.47 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.212933 | 0.212933 | 0.212933 | 0.212933 | 3278.36 | 3278.36 | 2003.49 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.283460 | 0.283460 | 0.283460 | 0.283460 | 4329.52 | 4329.52 | 3015.16 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.200480 | 0.200480 | 0.200480 | 0.200480 | 3127.84 | 3127.84 | 3015.94 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.262392 | 0.262392 | 0.262392 | 0.262392 | 4036.10 | 4036.10 | 3015.70 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.150917 | 0.150917 | 0.150917 | 0.150917 | 2382.94 | 2382.94 | 3016.46 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.097309 | 0.097309 | 0.097309 | 0.097309 | 1578.24 | 1578.24 | 2020.36 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.095084 | 0.095084 | 0.095084 | 0.095084 | 1544.93 | 1544.93 | 2020.37 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.214031 | 0.214031 | 0.214031 | 0.214031 | 3300.66 | 3300.66 | 2020.04 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.215057 | 0.215057 | 0.215057 | 0.215057 | 3315.10 | 3315.10 | 2020.06 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.279532 | 0.279532 | 0.279532 | 0.279532 | 4283.41 | 4283.41 | 3114.74 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.196653 | 0.196653 | 0.196653 | 0.196653 | 3081.49 | 3081.49 | 3116.38 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.258712 | 0.258712 | 0.258712 | 0.258712 | 3993.20 | 3993.20 | 3115.91 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.147099 | 0.147099 | 0.147099 | 0.147099 | 2335.57 | 2335.57 | 3117.55 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.094256 | 0.094256 | 0.094256 | 0.094256 | 1537.18 | 1537.18 | 2093.44 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.092048 | 0.092048 | 0.092048 | 0.092048 | 1503.94 | 1503.94 | 2093.47 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.210583 | 0.210583 | 0.210583 | 0.210583 | 3257.67 | 3257.67 | 2092.24 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.211608 | 0.211608 | 0.211608 | 0.211608 | 3272.10 | 3272.10 | 2092.27 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.277696 | 0.277696 | 0.277696 | 0.277696 | 4265.64 | 4265.64 | 3186.83 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.194923 | 0.194923 | 0.194923 | 0.194923 | 3063.90 | 3063.90 | 3188.27 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.257078 | 0.257078 | 0.257078 | 0.257078 | 3978.07 | 3978.07 | 3188.57 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.145319 | 0.145319 | 0.145319 | 0.145319 | 2316.23 | 2316.23 | 3190.01 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.093091 | 0.093091 | 0.093091 | 0.093091 | 1523.20 | 1523.20 | 2142.68 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.090893 | 0.090893 | 0.090893 | 0.090893 | 1490.01 | 1490.01 | 2142.73 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.209163 | 0.209163 | 0.209163 | 0.209163 | 3242.58 | 3242.58 | 2141.69 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.210188 | 0.210188 | 0.210188 | 0.210188 | 3257.02 | 3257.02 | 2141.74 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.276837 | 0.276837 | 0.276837 | 0.276837 | 4260.80 | 4260.80 | 3261.15 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.194203 | 0.194203 | 0.194203 | 0.194203 | 3059.92 | 3059.92 | 3262.16 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.256373 | 0.256373 | 0.256373 | 0.256373 | 3975.22 | 3975.22 | 3263.40 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.144497 | 0.144497 | 0.144497 | 0.144497 | 2309.84 | 2309.84 | 3264.41 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.092911 | 0.092911 | 0.092911 | 0.092911 | 1523.36 | 1523.36 | 2196.48 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.090724 | 0.090724 | 0.090724 | 0.090724 | 1490.25 | 1490.25 | 2196.54 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.208678 | 0.208678 | 0.208678 | 0.208678 | 3240.17 | 3240.17 | 2195.91 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.209705 | 0.209705 | 0.209705 | 0.209705 | 3254.64 | 3254.64 | 2195.96 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.281657 | 0.281657 | 0.281657 | 0.281657 | 4335.87 | 4335.87 | 3449.99 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.199302 | 0.199302 | 0.199302 | 0.199302 | 3138.96 | 3138.96 | 3448.43 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.259841 | 0.259841 | 0.259841 | 0.259841 | 4033.47 | 4033.47 | 3452.73 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.144096 | 0.144096 | 0.144096 | 0.144096 | 2309.30 | 2309.30 | 3451.16 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.097664 | 0.097664 | 0.097664 | 0.097664 | 1596.30 | 1596.30 | 2356.83 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.095452 | 0.095452 | 0.095452 | 0.095452 | 1562.89 | 1562.89 | 2356.90 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.211736 | 0.211736 | 0.211736 | 0.211736 | 3289.87 | 3289.87 | 2358.39 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.212766 | 0.212766 | 0.212766 | 0.212766 | 3304.39 | 3304.39 | 2358.46 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.342443 | 0.342443 | 0.342443 | 0.342443 | 5209.30 | 5209.30 | 4058.25 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.244016 | 0.244016 | 0.244016 | 0.244016 | 3789.16 | 3789.16 | 4063.02 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.316108 | 0.316108 | 0.316108 | 0.316108 | 4834.41 | 4834.41 | 4061.13 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.180179 | 0.180179 | 0.180179 | 0.180179 | 2848.36 | 2848.36 | 4065.90 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.128306 | 0.128306 | 0.128306 | 0.128306 | 2104.10 | 2104.10 | 3005.80 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.128475 | 0.128475 | 0.128475 | 0.128475 | 2106.64 | 2106.64 | 3005.87 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.278397 | 0.278397 | 0.278397 | 0.278397 | 4233.06 | 4233.06 | 2998.08 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.279401 | 0.279401 | 0.279401 | 0.279401 | 4247.16 | 4247.16 | 2998.16 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.215826 |
AIRLOOP G NW SUPPLY FAN | 0.146618 |
AIRLOOP OFFICE SUPPLY FAN | 0.337541 |
AIRLOOP G NE SUPPLY FAN | 0.103519 |
AIRLOOP G N1 SUPPLY FAN | 0.060532 |
AIRLOOP G N2 SUPPLY FAN | 0.060528 |
AIRLOOP G S1 SUPPLY FAN | 0.156552 |
AIRLOOP G S2 SUPPLY FAN | 0.163111 |
AIRLOOP F2 SW SUPPLY FAN | 0.280801 |
AIRLOOP F2 NW SUPPLY FAN | 0.196086 |
AIRLOOP F2 SE SUPPLY FAN | 0.282294 |
AIRLOOP F2 NE SUPPLY FAN | 0.146185 |
AIRLOOP F2 N1 SUPPLY FAN | 0.090309 |
AIRLOOP F2 N2 SUPPLY FAN | 0.088098 |
AIRLOOP F2 S1 SUPPLY FAN | 0.207860 |
AIRLOOP F2 S2 SUPPLY FAN | 0.210404 |
AIRLOOP F3 SW SUPPLY FAN | 0.282039 |
AIRLOOP F3 NW SUPPLY FAN | 0.198623 |
AIRLOOP F3 SE SUPPLY FAN | 0.262773 |
AIRLOOP F3 NE SUPPLY FAN | 0.149341 |
AIRLOOP F3 N1 SUPPLY FAN | 0.094253 |
AIRLOOP F3 N2 SUPPLY FAN | 0.092031 |
AIRLOOP F3 S1 SUPPLY FAN | 0.211281 |
AIRLOOP F3 S2 SUPPLY FAN | 0.212521 |
AIRLOOP F4 SW SUPPLY FAN | 0.281865 |
AIRLOOP F4 NW SUPPLY FAN | 0.198732 |
AIRLOOP F4 SE SUPPLY FAN | 0.260809 |
AIRLOOP F4 NE SUPPLY FAN | 0.149324 |
AIRLOOP F4 N1 SUPPLY FAN | 0.095106 |
AIRLOOP F4 N2 SUPPLY FAN | 0.092883 |
AIRLOOP F4 S1 SUPPLY FAN | 0.211879 |
AIRLOOP F4 S2 SUPPLY FAN | 0.212933 |
AIRLOOP M SW SUPPLY FAN | 0.283460 |
AIRLOOP M NW SUPPLY FAN | 0.200480 |
AIRLOOP M SE SUPPLY FAN | 0.262392 |
AIRLOOP M NE SUPPLY FAN | 0.150917 |
AIRLOOP M N1 SUPPLY FAN | 0.097309 |
AIRLOOP M N2 SUPPLY FAN | 0.095084 |
AIRLOOP M S1 SUPPLY FAN | 0.214031 |
AIRLOOP M S2 SUPPLY FAN | 0.215057 |
AIRLOOP F6 SW SUPPLY FAN | 0.279532 |
AIRLOOP F6 NW SUPPLY FAN | 0.196653 |
AIRLOOP F6 SE SUPPLY FAN | 0.258712 |
AIRLOOP F6 NE SUPPLY FAN | 0.147099 |
AIRLOOP F6 N1 SUPPLY FAN | 0.094256 |
AIRLOOP F6 N2 SUPPLY FAN | 0.092048 |
AIRLOOP F6 S1 SUPPLY FAN | 0.210583 |
AIRLOOP F6 S2 SUPPLY FAN | 0.211608 |
AIRLOOP F7 SW SUPPLY FAN | 0.277696 |
AIRLOOP F7 NW SUPPLY FAN | 0.194923 |
AIRLOOP F7 SE SUPPLY FAN | 0.257078 |
AIRLOOP F7 NE SUPPLY FAN | 0.145319 |
AIRLOOP F7 N1 SUPPLY FAN | 0.093091 |
AIRLOOP F7 N2 SUPPLY FAN | 0.090893 |
AIRLOOP F7 S1 SUPPLY FAN | 0.209163 |
AIRLOOP F7 S2 SUPPLY FAN | 0.210188 |
AIRLOOP F8 SW SUPPLY FAN | 0.276837 |
AIRLOOP F8 NW SUPPLY FAN | 0.194203 |
AIRLOOP F8 SE SUPPLY FAN | 0.256373 |
AIRLOOP F8 NE SUPPLY FAN | 0.144497 |
AIRLOOP F8 N1 SUPPLY FAN | 0.092911 |
AIRLOOP F8 N2 SUPPLY FAN | 0.090724 |
AIRLOOP F8 S1 SUPPLY FAN | 0.208678 |
AIRLOOP F8 S2 SUPPLY FAN | 0.209705 |
AIRLOOP F9 SW SUPPLY FAN | 0.281657 |
AIRLOOP F9 NW SUPPLY FAN | 0.199302 |
AIRLOOP F9 SE SUPPLY FAN | 0.259841 |
AIRLOOP F9 NE SUPPLY FAN | 0.144096 |
AIRLOOP F9 N1 SUPPLY FAN | 0.097664 |
AIRLOOP F9 N2 SUPPLY FAN | 0.095452 |
AIRLOOP F9 S1 SUPPLY FAN | 0.211736 |
AIRLOOP F9 S2 SUPPLY FAN | 0.212766 |
AIRLOOP T SW SUPPLY FAN | 0.342443 |
AIRLOOP T NW SUPPLY FAN | 0.244016 |
AIRLOOP T SE SUPPLY FAN | 0.316108 |
AIRLOOP T NE SUPPLY FAN | 0.180179 |
AIRLOOP T N1 SUPPLY FAN | 0.128306 |
AIRLOOP T N2 SUPPLY FAN | 0.128475 |
AIRLOOP T S1 SUPPLY FAN | 0.278397 |
AIRLOOP T S2 SUPPLY FAN | 0.279401 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.215826 | 3301.54 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.146618 | 2296.82 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.337541 | 5084.36 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.103519 | 1656.97 | 0.000036 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.060532 | 1012.32 | 0.000022 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.060528 | 1015.61 | 0.000022 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.156552 | 2446.12 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.163111 | 2538.35 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.280801 | 4248.57 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.196086 | 3026.90 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.282294 | 4274.09 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.146185 | 2281.79 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.090309 | 1458.60 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.088098 | 1425.63 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.207860 | 3187.56 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.210404 | 3223.36 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.282039 | 4284.54 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.198623 | 3079.39 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.262773 | 4017.07 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.149341 | 2341.05 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.094253 | 1523.54 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.092031 | 1490.39 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.211281 | 3246.84 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.212521 | 3264.27 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.281865 | 4295.85 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.198732 | 3093.12 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.260809 | 4002.79 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.149324 | 2351.59 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.095106 | 1541.54 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.092883 | 1508.27 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.211879 | 3263.55 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.212933 | 3278.36 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.283460 | 4329.52 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.200480 | 3127.84 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.262392 | 4036.10 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.150917 | 2382.94 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.097309 | 1578.24 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.095084 | 1544.93 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.214031 | 3300.66 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.215057 | 3315.10 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.279532 | 4283.41 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.196653 | 3081.49 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.258712 | 3993.20 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.147099 | 2335.57 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.094256 | 1537.18 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.092048 | 1503.94 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.210583 | 3257.67 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.211608 | 3272.10 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.277696 | 4265.64 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.194923 | 3063.90 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.257078 | 3978.07 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.145319 | 2316.23 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.093091 | 1523.20 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.090893 | 1490.01 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.209163 | 3242.58 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.210188 | 3257.02 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.276837 | 4260.80 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.194203 | 3059.92 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.256373 | 3975.22 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.144497 | 2309.84 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.092911 | 1523.36 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.090724 | 1490.25 | 0.000033 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.208678 | 3240.17 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.209705 | 3254.64 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.281657 | 4335.87 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.199302 | 3138.96 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.259841 | 4033.47 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.144096 | 2309.30 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.097664 | 1596.30 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.095452 | 1562.89 | 0.000034 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.211736 | 3289.87 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.212766 | 3304.39 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.342443 | 5209.30 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.244016 | 3789.16 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.316108 | 4834.41 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.180179 | 2848.36 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.128306 | 2104.10 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.128475 | 2106.64 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.278397 | 4233.06 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.279401 | 4247.16 | 0.000093 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2947.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2952.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3720.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2949.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2241.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2241.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2232.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2238.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2880.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2880.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2896.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2878.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1997.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1997.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1999.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 2000.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2901.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2902.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2902.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2901.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1973.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1973.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1972.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1972.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2969.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2971.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2969.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2971.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 2004.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 2004.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 2003.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 2003.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 3015.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 3015.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 3015.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 3016.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 2020.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 2020.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 2020.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 2020.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 3114.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 3116.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 3115.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 3117.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 2093.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 2093.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 2092.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 2092.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 3186.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 3188.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 3188.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 3190.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 2142.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 2142.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 2141.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 2141.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 3261.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 3262.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 3263.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 3264.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2196.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2196.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2195.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2195.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 3449.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 3448.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 3452.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 3451.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2356.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2356.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2358.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2358.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 4058.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 4063.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 4061.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 4065.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 3005.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 3005.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2998.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2998.16 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005136 | 5.78 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005136 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005136 | 2479.57 | 6.53 | 7693.53 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005136 | 1640.30 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 3.20 |
February | 21.92 | 5.10 |
March | 22.09 | 6.09 |
April | 22.52 | 8.68 |
May | 23.00 | 11.83 |
June | 23.69 | 15.06 |
July | 24.02 | 16.98 |
August | 23.95 | 17.08 |
September | 23.58 | 13.78 |
October | 22.28 | 9.83 |
November | 21.81 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.70 | 9.74 |
Minimum of Months | 21.71 | 3.20 |
Maximum of Months | 24.02 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.76 | 6.09 |
April | 21.93 | 8.68 |
May | 22.44 | 11.83 |
June | 23.40 | 15.06 |
July | 23.84 | 16.98 |
August | 23.64 | 17.08 |
September | 22.87 | 13.78 |
October | 21.80 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.38 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.84 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 3.20 |
February | 22.17 | 5.10 |
March | 22.37 | 6.09 |
April | 22.76 | 8.68 |
May | 23.32 | 11.83 |
June | 24.14 | 15.06 |
July | 24.32 | 16.98 |
August | 24.35 | 17.08 |
September | 23.94 | 13.78 |
October | 22.57 | 9.83 |
November | 22.06 | 5.28 |
December | 21.84 | 3.63 |
Annual Sum or Average | 22.98 | 9.74 |
Minimum of Months | 21.83 | 3.20 |
Maximum of Months | 24.35 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.72 | 6.09 |
April | 21.84 | 8.68 |
May | 22.27 | 11.83 |
June | 23.21 | 15.06 |
July | 23.75 | 16.98 |
August | 23.57 | 17.08 |
September | 22.73 | 13.78 |
October | 21.78 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.31 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.71 | 6.09 |
April | 21.76 | 8.68 |
May | 22.06 | 11.83 |
June | 23.05 | 15.06 |
July | 23.59 | 16.98 |
August | 23.39 | 17.08 |
September | 22.66 | 13.78 |
October | 21.76 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.24 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.59 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.71 | 6.09 |
April | 21.75 | 8.68 |
May | 22.05 | 11.83 |
June | 23.04 | 15.06 |
July | 23.58 | 16.98 |
August | 23.38 | 17.08 |
September | 22.64 | 13.78 |
October | 21.76 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.23 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.58 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.20 |
February | 21.94 | 5.10 |
March | 22.09 | 6.09 |
April | 22.48 | 8.68 |
May | 22.88 | 11.83 |
June | 23.58 | 15.06 |
July | 23.97 | 16.98 |
August | 23.94 | 17.08 |
September | 23.70 | 13.78 |
October | 22.43 | 9.83 |
November | 21.84 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.70 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 23.97 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 21.96 | 5.10 |
March | 22.13 | 6.09 |
April | 22.52 | 8.68 |
May | 22.95 | 11.83 |
June | 23.64 | 15.06 |
July | 24.00 | 16.98 |
August | 23.98 | 17.08 |
September | 23.75 | 13.78 |
October | 22.48 | 9.83 |
November | 21.85 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.73 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.00 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.15 | 3.20 |
February | 17.01 | 5.10 |
March | 17.49 | 6.09 |
April | 18.72 | 8.68 |
May | 20.12 | 11.83 |
June | 22.04 | 15.06 |
July | 23.10 | 16.98 |
August | 22.93 | 17.08 |
September | 21.49 | 13.78 |
October | 18.80 | 9.83 |
November | 16.94 | 5.28 |
December | 16.20 | 3.63 |
Annual Sum or Average | 19.26 | 9.74 |
Minimum of Months | 16.15 | 3.20 |
Maximum of Months | 23.10 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.15 | 5.10 |
March | 22.46 | 6.09 |
April | 23.20 | 8.68 |
May | 23.85 | 11.83 |
June | 24.12 | 15.06 |
July | 24.24 | 16.98 |
August | 24.17 | 17.08 |
September | 23.88 | 13.78 |
October | 22.72 | 9.83 |
November | 21.94 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.02 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.24 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.88 | 6.09 |
April | 22.24 | 8.68 |
May | 23.31 | 11.83 |
June | 23.90 | 15.06 |
July | 24.15 | 16.98 |
August | 23.97 | 17.08 |
September | 23.16 | 13.78 |
October | 21.94 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.62 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.20 |
February | 22.22 | 5.10 |
March | 22.52 | 6.09 |
April | 23.24 | 8.68 |
May | 23.92 | 11.83 |
June | 24.18 | 15.06 |
July | 24.30 | 16.98 |
August | 24.25 | 17.08 |
September | 23.97 | 13.78 |
October | 22.84 | 9.83 |
November | 21.99 | 5.28 |
December | 21.76 | 3.63 |
Annual Sum or Average | 23.08 | 9.74 |
Minimum of Months | 21.75 | 3.20 |
Maximum of Months | 24.30 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 22.12 | 8.68 |
May | 23.12 | 11.83 |
June | 23.74 | 15.06 |
July | 24.11 | 16.98 |
August | 23.92 | 17.08 |
September | 22.99 | 13.78 |
October | 21.92 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.55 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.11 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.81 | 6.09 |
April | 21.98 | 8.68 |
May | 22.95 | 11.83 |
June | 23.62 | 15.06 |
July | 23.99 | 16.98 |
August | 23.78 | 17.08 |
September | 22.92 | 13.78 |
October | 21.94 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.49 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.99 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.80 | 6.09 |
April | 21.97 | 8.68 |
May | 22.92 | 11.83 |
June | 23.60 | 15.06 |
July | 23.98 | 16.98 |
August | 23.77 | 17.08 |
September | 22.89 | 13.78 |
October | 21.94 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.48 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.98 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.35 | 5.10 |
March | 22.56 | 6.09 |
April | 23.32 | 8.68 |
May | 23.91 | 11.83 |
June | 24.05 | 15.06 |
July | 24.20 | 16.98 |
August | 24.15 | 17.08 |
September | 24.00 | 13.78 |
October | 23.04 | 9.83 |
November | 22.06 | 5.28 |
December | 21.79 | 3.63 |
Annual Sum or Average | 23.11 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.20 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.36 | 5.10 |
March | 22.57 | 6.09 |
April | 23.33 | 8.68 |
May | 23.93 | 11.83 |
June | 24.06 | 15.06 |
July | 24.21 | 16.98 |
August | 24.16 | 17.08 |
September | 24.02 | 13.78 |
October | 23.07 | 9.83 |
November | 22.07 | 5.28 |
December | 21.79 | 3.63 |
Annual Sum or Average | 23.12 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.21 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 3.20 |
February | 22.00 | 5.10 |
March | 22.29 | 6.09 |
April | 23.31 | 8.68 |
May | 24.40 | 11.83 |
June | 25.26 | 15.06 |
July | 25.76 | 16.98 |
August | 25.55 | 17.08 |
September | 24.65 | 13.78 |
October | 22.82 | 9.83 |
November | 21.67 | 5.28 |
December | 21.20 | 3.63 |
Annual Sum or Average | 23.36 | 9.74 |
Minimum of Months | 21.20 | 3.20 |
Maximum of Months | 25.76 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.22 | 5.10 |
March | 22.53 | 6.09 |
April | 23.33 | 8.68 |
May | 23.96 | 11.83 |
June | 24.15 | 15.06 |
July | 24.24 | 16.98 |
August | 24.17 | 17.08 |
September | 23.88 | 13.78 |
October | 22.79 | 9.83 |
November | 21.97 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.06 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.24 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.93 | 6.09 |
April | 22.33 | 8.68 |
May | 23.51 | 11.83 |
June | 23.95 | 15.06 |
July | 24.17 | 16.98 |
August | 23.98 | 17.08 |
September | 23.18 | 13.78 |
October | 21.99 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.66 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.17 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.19 | 5.10 |
March | 22.50 | 6.09 |
April | 23.25 | 8.68 |
May | 23.94 | 11.83 |
June | 24.13 | 15.06 |
July | 24.27 | 16.98 |
August | 24.20 | 17.08 |
September | 23.89 | 13.78 |
October | 22.81 | 9.83 |
November | 21.97 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.06 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.27 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.86 | 6.09 |
April | 22.20 | 8.68 |
May | 23.33 | 11.83 |
June | 23.82 | 15.06 |
July | 24.14 | 16.98 |
August | 23.94 | 17.08 |
September | 23.00 | 13.78 |
October | 21.97 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.59 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.14 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.87 | 6.09 |
April | 22.10 | 8.68 |
May | 23.29 | 11.83 |
June | 23.74 | 15.06 |
July | 24.04 | 16.98 |
August | 23.82 | 17.08 |
September | 22.97 | 13.78 |
October | 22.03 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.56 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.04 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.86 | 6.09 |
April | 22.08 | 8.68 |
May | 23.26 | 11.83 |
June | 23.72 | 15.06 |
July | 24.04 | 16.98 |
August | 23.81 | 17.08 |
September | 22.95 | 13.78 |
October | 22.03 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.55 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.04 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.20 |
February | 22.52 | 5.10 |
March | 22.68 | 6.09 |
April | 23.53 | 8.68 |
May | 24.08 | 11.83 |
June | 24.10 | 15.06 |
July | 24.21 | 16.98 |
August | 24.16 | 17.08 |
September | 24.02 | 13.78 |
October | 23.20 | 9.83 |
November | 22.14 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.19 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.21 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.20 |
February | 22.52 | 5.10 |
March | 22.68 | 6.09 |
April | 23.52 | 8.68 |
May | 24.09 | 11.83 |
June | 24.10 | 15.06 |
July | 24.21 | 16.98 |
August | 24.16 | 17.08 |
September | 24.02 | 13.78 |
October | 23.21 | 9.83 |
November | 22.14 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.19 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.21 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.20 |
February | 22.49 | 5.10 |
March | 22.76 | 6.09 |
April | 23.83 | 8.68 |
May | 24.98 | 11.83 |
June | 25.59 | 15.06 |
July | 26.00 | 16.98 |
August | 25.76 | 17.08 |
September | 24.90 | 13.78 |
October | 23.22 | 9.83 |
November | 22.10 | 5.28 |
December | 21.61 | 3.63 |
Annual Sum or Average | 23.76 | 9.74 |
Minimum of Months | 21.61 | 3.20 |
Maximum of Months | 26.00 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.22 | 5.10 |
March | 22.54 | 6.09 |
April | 23.33 | 8.68 |
May | 23.96 | 11.83 |
June | 24.17 | 15.06 |
July | 24.25 | 16.98 |
August | 24.16 | 17.08 |
September | 23.92 | 13.78 |
October | 22.78 | 9.83 |
November | 21.98 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.07 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.25 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.95 | 6.09 |
April | 22.34 | 8.68 |
May | 23.54 | 11.83 |
June | 24.00 | 15.06 |
July | 24.18 | 16.98 |
August | 23.97 | 17.08 |
September | 23.23 | 13.78 |
October | 21.99 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.67 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.18 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.17 | 5.10 |
March | 22.50 | 6.09 |
April | 23.23 | 8.68 |
May | 23.93 | 11.83 |
June | 24.13 | 15.06 |
July | 24.28 | 16.98 |
August | 24.18 | 17.08 |
September | 23.90 | 13.78 |
October | 22.78 | 9.83 |
November | 21.96 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.05 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.28 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.87 | 6.09 |
April | 22.21 | 8.68 |
May | 23.39 | 11.83 |
June | 23.87 | 15.06 |
July | 24.15 | 16.98 |
August | 23.92 | 17.08 |
September | 23.05 | 13.78 |
October | 21.97 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.61 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.90 | 6.09 |
April | 22.14 | 8.68 |
May | 23.41 | 11.83 |
June | 23.83 | 15.06 |
July | 24.07 | 16.98 |
August | 23.81 | 17.08 |
September | 23.07 | 13.78 |
October | 22.05 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.60 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.07 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.89 | 6.09 |
April | 22.13 | 8.68 |
May | 23.38 | 11.83 |
June | 23.81 | 15.06 |
July | 24.07 | 16.98 |
August | 23.80 | 17.08 |
September | 23.04 | 13.78 |
October | 22.05 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.59 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.07 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.20 |
February | 22.55 | 5.10 |
March | 22.70 | 6.09 |
April | 23.56 | 8.68 |
May | 24.11 | 11.83 |
June | 24.14 | 15.06 |
July | 24.23 | 16.98 |
August | 24.15 | 17.08 |
September | 24.07 | 13.78 |
October | 23.22 | 9.83 |
November | 22.16 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.21 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.23 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 3.20 |
February | 22.55 | 5.10 |
March | 22.70 | 6.09 |
April | 23.55 | 8.68 |
May | 24.11 | 11.83 |
June | 24.14 | 15.06 |
July | 24.23 | 16.98 |
August | 24.15 | 17.08 |
September | 24.07 | 13.78 |
October | 23.23 | 9.83 |
November | 22.16 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.21 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.23 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 3.20 |
February | 22.64 | 5.10 |
March | 22.91 | 6.09 |
April | 23.99 | 8.68 |
May | 25.17 | 11.83 |
June | 25.73 | 15.06 |
July | 26.11 | 16.98 |
August | 25.84 | 17.08 |
September | 25.03 | 13.78 |
October | 23.36 | 9.83 |
November | 22.23 | 5.28 |
December | 21.73 | 3.63 |
Annual Sum or Average | 23.89 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 26.11 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.20 |
February | 22.22 | 5.10 |
March | 22.54 | 6.09 |
April | 23.31 | 8.68 |
May | 23.94 | 11.83 |
June | 24.16 | 15.06 |
July | 24.25 | 16.98 |
August | 24.15 | 17.08 |
September | 23.90 | 13.78 |
October | 22.76 | 9.83 |
November | 21.98 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.06 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.25 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.95 | 6.09 |
April | 22.34 | 8.68 |
May | 23.53 | 11.83 |
June | 23.98 | 15.06 |
July | 24.17 | 16.98 |
August | 23.95 | 17.08 |
September | 23.21 | 13.78 |
October | 21.99 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.67 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.17 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.17 | 5.10 |
March | 22.49 | 6.09 |
April | 23.21 | 8.68 |
May | 23.91 | 11.83 |
June | 24.12 | 15.06 |
July | 24.27 | 16.98 |
August | 24.17 | 17.08 |
September | 23.88 | 13.78 |
October | 22.76 | 9.83 |
November | 21.96 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 23.04 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 24.27 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.88 | 6.09 |
April | 22.20 | 8.68 |
May | 23.38 | 11.83 |
June | 23.86 | 15.06 |
July | 24.15 | 16.98 |
August | 23.90 | 17.08 |
September | 23.03 | 13.78 |
October | 21.97 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.60 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.91 | 6.09 |
April | 22.16 | 8.68 |
May | 23.43 | 11.83 |
June | 23.83 | 15.06 |
July | 24.07 | 16.98 |
August | 23.80 | 17.08 |
September | 23.08 | 13.78 |
October | 22.07 | 9.83 |
November | 21.71 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.60 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.07 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.90 | 6.09 |
April | 22.14 | 8.68 |
May | 23.41 | 11.83 |
June | 23.82 | 15.06 |
July | 24.07 | 16.98 |
August | 23.79 | 17.08 |
September | 23.05 | 13.78 |
October | 22.07 | 9.83 |
November | 21.71 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.59 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.07 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 3.20 |
February | 22.57 | 5.10 |
March | 22.70 | 6.09 |
April | 23.57 | 8.68 |
May | 24.11 | 11.83 |
June | 24.14 | 15.06 |
July | 24.22 | 16.98 |
August | 24.14 | 17.08 |
September | 24.06 | 13.78 |
October | 23.22 | 9.83 |
November | 22.17 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.21 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.22 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 3.20 |
February | 22.57 | 5.10 |
March | 22.70 | 6.09 |
April | 23.55 | 8.68 |
May | 24.11 | 11.83 |
June | 24.14 | 15.06 |
July | 24.22 | 16.98 |
August | 24.14 | 17.08 |
September | 24.06 | 13.78 |
October | 23.22 | 9.83 |
November | 22.17 | 5.28 |
December | 21.80 | 3.63 |
Annual Sum or Average | 23.21 | 9.74 |
Minimum of Months | 21.80 | 3.20 |
Maximum of Months | 24.22 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.49 | 3.20 |
February | 23.23 | 5.10 |
March | 23.50 | 6.09 |
April | 24.55 | 8.68 |
May | 25.73 | 11.83 |
June | 26.27 | 15.06 |
July | 26.64 | 16.98 |
August | 26.37 | 17.08 |
September | 25.57 | 13.78 |
October | 23.93 | 9.83 |
November | 22.83 | 5.28 |
December | 22.32 | 3.63 |
Annual Sum or Average | 24.46 | 9.74 |
Minimum of Months | 22.32 | 3.20 |
Maximum of Months | 26.64 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.17 | 5.10 |
March | 22.49 | 6.09 |
April | 23.23 | 8.68 |
May | 23.87 | 11.83 |
June | 24.11 | 15.06 |
July | 24.22 | 16.98 |
August | 24.11 | 17.08 |
September | 23.84 | 13.78 |
October | 22.69 | 9.83 |
November | 21.96 | 5.28 |
December | 21.73 | 3.63 |
Annual Sum or Average | 23.02 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.22 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.92 | 6.09 |
April | 22.25 | 8.68 |
May | 23.42 | 11.83 |
June | 23.90 | 15.06 |
July | 24.13 | 16.98 |
August | 23.87 | 17.08 |
September | 23.08 | 13.78 |
October | 21.94 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.62 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.13 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.12 | 5.10 |
March | 22.45 | 6.09 |
April | 23.13 | 8.68 |
May | 23.84 | 11.83 |
June | 24.05 | 15.06 |
July | 24.24 | 16.98 |
August | 24.12 | 17.08 |
September | 23.81 | 13.78 |
October | 22.68 | 9.83 |
November | 21.94 | 5.28 |
December | 21.73 | 3.63 |
Annual Sum or Average | 22.99 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.24 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.85 | 6.09 |
April | 22.14 | 8.68 |
May | 23.27 | 11.83 |
June | 23.76 | 15.06 |
July | 24.09 | 16.98 |
August | 23.81 | 17.08 |
September | 22.91 | 13.78 |
October | 21.93 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.55 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.09 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.88 | 6.09 |
April | 22.08 | 8.68 |
May | 23.30 | 11.83 |
June | 23.74 | 15.06 |
July | 24.01 | 16.98 |
August | 23.71 | 17.08 |
September | 22.95 | 13.78 |
October | 22.01 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.55 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.01 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.87 | 6.09 |
April | 22.07 | 8.68 |
May | 23.28 | 11.83 |
June | 23.72 | 15.06 |
July | 24.00 | 16.98 |
August | 23.70 | 17.08 |
September | 22.92 | 13.78 |
October | 22.01 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.54 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.00 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.20 |
February | 22.49 | 5.10 |
March | 22.66 | 6.09 |
April | 23.48 | 8.68 |
May | 24.05 | 11.83 |
June | 24.09 | 15.06 |
July | 24.19 | 16.98 |
August | 24.10 | 17.08 |
September | 24.00 | 13.78 |
October | 23.12 | 9.83 |
November | 22.13 | 5.28 |
December | 21.78 | 3.63 |
Annual Sum or Average | 23.16 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.19 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.20 |
February | 22.49 | 5.10 |
March | 22.65 | 6.09 |
April | 23.47 | 8.68 |
May | 24.05 | 11.83 |
June | 24.08 | 15.06 |
July | 24.19 | 16.98 |
August | 24.10 | 17.08 |
September | 24.00 | 13.78 |
October | 23.12 | 9.83 |
November | 22.13 | 5.28 |
December | 21.78 | 3.63 |
Annual Sum or Average | 23.16 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.19 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 3.20 |
February | 22.60 | 5.10 |
March | 22.86 | 6.09 |
April | 23.91 | 8.68 |
May | 25.08 | 11.83 |
June | 25.64 | 15.06 |
July | 26.05 | 16.98 |
August | 25.75 | 17.08 |
September | 24.92 | 13.78 |
October | 23.28 | 9.83 |
November | 22.19 | 5.28 |
December | 21.68 | 3.63 |
Annual Sum or Average | 23.83 | 9.74 |
Minimum of Months | 21.68 | 3.20 |
Maximum of Months | 26.05 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 3.20 |
February | 22.13 | 5.10 |
March | 22.46 | 6.09 |
April | 23.16 | 8.68 |
May | 23.82 | 11.83 |
June | 24.07 | 15.06 |
July | 24.20 | 16.98 |
August | 24.07 | 17.08 |
September | 23.78 | 13.78 |
October | 22.63 | 9.83 |
November | 21.94 | 5.28 |
December | 21.73 | 3.63 |
Annual Sum or Average | 22.98 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.20 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.89 | 6.09 |
April | 22.20 | 8.68 |
May | 23.34 | 11.83 |
June | 23.84 | 15.06 |
July | 24.10 | 16.98 |
August | 23.81 | 17.08 |
September | 22.98 | 13.78 |
October | 21.91 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.58 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.10 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.09 | 5.10 |
March | 22.42 | 6.09 |
April | 23.07 | 8.68 |
May | 23.77 | 11.83 |
June | 24.01 | 15.06 |
July | 24.22 | 16.98 |
August | 24.08 | 17.08 |
September | 23.75 | 13.78 |
October | 22.63 | 9.83 |
November | 21.93 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.96 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.22 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.83 | 6.09 |
April | 22.09 | 8.68 |
May | 23.18 | 11.83 |
June | 23.69 | 15.06 |
July | 24.04 | 16.98 |
August | 23.73 | 17.08 |
September | 22.81 | 13.78 |
October | 21.90 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.51 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.04 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.86 | 6.09 |
April | 22.03 | 8.68 |
May | 23.20 | 11.83 |
June | 23.67 | 15.06 |
July | 23.97 | 16.98 |
August | 23.63 | 17.08 |
September | 22.85 | 13.78 |
October | 21.96 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.50 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.97 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.85 | 6.09 |
April | 22.02 | 8.68 |
May | 23.17 | 11.83 |
June | 23.64 | 15.06 |
July | 23.95 | 16.98 |
August | 23.62 | 17.08 |
September | 22.82 | 13.78 |
October | 21.96 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.49 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.95 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.43 | 5.10 |
March | 22.62 | 6.09 |
April | 23.41 | 8.68 |
May | 24.00 | 11.83 |
June | 24.04 | 15.06 |
July | 24.17 | 16.98 |
August | 24.07 | 17.08 |
September | 23.95 | 13.78 |
October | 23.03 | 9.83 |
November | 22.10 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.12 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.17 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.43 | 5.10 |
March | 22.62 | 6.09 |
April | 23.40 | 8.68 |
May | 24.00 | 11.83 |
June | 24.04 | 15.06 |
July | 24.18 | 16.98 |
August | 24.07 | 17.08 |
September | 23.94 | 13.78 |
October | 23.04 | 9.83 |
November | 22.10 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.12 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.18 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.46 | 5.10 |
March | 22.72 | 6.09 |
April | 23.74 | 8.68 |
May | 24.91 | 11.83 |
June | 25.49 | 15.06 |
July | 25.93 | 16.98 |
August | 25.61 | 17.08 |
September | 24.75 | 13.78 |
October | 23.12 | 9.83 |
November | 22.06 | 5.28 |
December | 21.55 | 3.63 |
Annual Sum or Average | 23.68 | 9.74 |
Minimum of Months | 21.55 | 3.20 |
Maximum of Months | 25.93 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.10 | 5.10 |
March | 22.43 | 6.09 |
April | 23.10 | 8.68 |
May | 23.77 | 11.83 |
June | 24.02 | 15.06 |
July | 24.18 | 16.98 |
August | 24.04 | 17.08 |
September | 23.73 | 13.78 |
October | 22.58 | 9.83 |
November | 21.92 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.95 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.18 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.87 | 6.09 |
April | 22.16 | 8.68 |
May | 23.26 | 11.83 |
June | 23.78 | 15.06 |
July | 24.07 | 16.98 |
August | 23.76 | 17.08 |
September | 22.90 | 13.78 |
October | 21.88 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.55 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.07 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.06 | 5.10 |
March | 22.39 | 6.09 |
April | 23.01 | 8.68 |
May | 23.71 | 11.83 |
June | 23.96 | 15.06 |
July | 24.19 | 16.98 |
August | 24.05 | 17.08 |
September | 23.70 | 13.78 |
October | 22.58 | 9.83 |
November | 21.91 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.92 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.19 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 22.06 | 8.68 |
May | 23.10 | 11.83 |
June | 23.62 | 15.06 |
July | 23.99 | 16.98 |
August | 23.67 | 17.08 |
September | 22.73 | 13.78 |
October | 21.87 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.48 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.99 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.84 | 6.09 |
April | 21.99 | 8.68 |
May | 23.11 | 11.83 |
June | 23.60 | 15.06 |
July | 23.92 | 16.98 |
August | 23.57 | 17.08 |
September | 22.76 | 13.78 |
October | 21.93 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.47 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.92 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.83 | 6.09 |
April | 21.98 | 8.68 |
May | 23.09 | 11.83 |
June | 23.58 | 15.06 |
July | 23.91 | 16.98 |
August | 23.55 | 17.08 |
September | 22.74 | 13.78 |
October | 21.93 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.46 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.91 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.20 |
February | 22.36 | 5.10 |
March | 22.58 | 6.09 |
April | 23.34 | 8.68 |
May | 23.95 | 11.83 |
June | 24.00 | 15.06 |
July | 24.15 | 16.98 |
August | 24.04 | 17.08 |
September | 23.89 | 13.78 |
October | 22.95 | 9.83 |
November | 22.06 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.08 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.20 |
February | 22.36 | 5.10 |
March | 22.58 | 6.09 |
April | 23.33 | 8.68 |
May | 23.95 | 11.83 |
June | 24.00 | 15.06 |
July | 24.16 | 16.98 |
August | 24.04 | 17.08 |
September | 23.89 | 13.78 |
October | 22.96 | 9.83 |
November | 22.06 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.08 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.16 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 3.20 |
February | 22.37 | 5.10 |
March | 22.63 | 6.09 |
April | 23.65 | 8.68 |
May | 24.81 | 11.83 |
June | 25.42 | 15.06 |
July | 25.88 | 16.98 |
August | 25.55 | 17.08 |
September | 24.65 | 13.78 |
October | 23.02 | 9.83 |
November | 21.98 | 5.28 |
December | 21.48 | 3.63 |
Annual Sum or Average | 23.60 | 9.74 |
Minimum of Months | 21.48 | 3.20 |
Maximum of Months | 25.88 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.06 | 5.10 |
March | 22.37 | 6.09 |
April | 23.00 | 8.68 |
May | 23.68 | 11.83 |
June | 23.97 | 15.06 |
July | 24.15 | 16.98 |
August | 24.01 | 17.08 |
September | 23.65 | 13.78 |
October | 22.52 | 9.83 |
November | 21.90 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.90 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.86 | 6.09 |
April | 22.14 | 8.68 |
May | 23.18 | 11.83 |
June | 23.72 | 15.06 |
July | 24.03 | 16.98 |
August | 23.71 | 17.08 |
September | 22.82 | 13.78 |
October | 21.86 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.51 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.03 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.02 | 5.10 |
March | 22.34 | 6.09 |
April | 22.93 | 8.68 |
May | 23.63 | 11.83 |
June | 23.91 | 15.06 |
July | 24.15 | 16.98 |
August | 24.01 | 17.08 |
September | 23.61 | 13.78 |
October | 22.52 | 9.83 |
November | 21.88 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.88 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.80 | 6.09 |
April | 22.04 | 8.68 |
May | 23.01 | 11.83 |
June | 23.55 | 15.06 |
July | 23.93 | 16.98 |
August | 23.62 | 17.08 |
September | 22.65 | 13.78 |
October | 21.85 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.44 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.93 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 21.98 | 8.68 |
May | 23.03 | 11.83 |
June | 23.55 | 15.06 |
July | 23.89 | 16.98 |
August | 23.53 | 17.08 |
September | 22.68 | 13.78 |
October | 21.89 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.43 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.89 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 21.97 | 8.68 |
May | 23.00 | 11.83 |
June | 23.52 | 15.06 |
July | 23.87 | 16.98 |
August | 23.51 | 17.08 |
September | 22.66 | 13.78 |
October | 21.89 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.43 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.87 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 3.20 |
February | 22.27 | 5.10 |
March | 22.52 | 6.09 |
April | 23.22 | 8.68 |
May | 23.86 | 11.83 |
June | 23.96 | 15.06 |
July | 24.13 | 16.98 |
August | 24.02 | 17.08 |
September | 23.82 | 13.78 |
October | 22.84 | 9.83 |
November | 22.01 | 5.28 |
December | 21.75 | 3.63 |
Annual Sum or Average | 23.02 | 9.74 |
Minimum of Months | 21.75 | 3.20 |
Maximum of Months | 24.13 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 3.20 |
February | 22.26 | 5.10 |
March | 22.52 | 6.09 |
April | 23.21 | 8.68 |
May | 23.86 | 11.83 |
June | 23.96 | 15.06 |
July | 24.13 | 16.98 |
August | 24.02 | 17.08 |
September | 23.81 | 13.78 |
October | 22.84 | 9.83 |
November | 22.01 | 5.28 |
December | 21.75 | 3.63 |
Annual Sum or Average | 23.02 | 9.74 |
Minimum of Months | 21.75 | 3.20 |
Maximum of Months | 24.13 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 3.20 |
February | 22.22 | 5.10 |
March | 22.50 | 6.09 |
April | 23.53 | 8.68 |
May | 24.70 | 11.83 |
June | 25.37 | 15.06 |
July | 25.87 | 16.98 |
August | 25.52 | 17.08 |
September | 24.53 | 13.78 |
October | 22.87 | 9.83 |
November | 21.83 | 5.28 |
December | 21.34 | 3.63 |
Annual Sum or Average | 23.49 | 9.74 |
Minimum of Months | 21.34 | 3.20 |
Maximum of Months | 25.87 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.20 |
February | 22.07 | 5.10 |
March | 22.28 | 6.09 |
April | 22.75 | 8.68 |
May | 23.34 | 11.83 |
June | 23.76 | 15.06 |
July | 23.97 | 16.98 |
August | 23.80 | 17.08 |
September | 23.32 | 13.78 |
October | 22.38 | 9.83 |
November | 21.89 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.76 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 23.97 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.72 | 5.10 |
March | 21.90 | 6.09 |
April | 22.23 | 8.68 |
May | 22.96 | 11.83 |
June | 23.50 | 15.06 |
July | 23.78 | 16.98 |
August | 23.47 | 17.08 |
September | 22.64 | 13.78 |
October | 21.91 | 9.83 |
November | 21.71 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.44 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.78 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 3.20 |
February | 22.04 | 5.10 |
March | 22.25 | 6.09 |
April | 22.73 | 8.68 |
May | 23.32 | 11.83 |
June | 23.69 | 15.06 |
July | 23.95 | 16.98 |
August | 23.80 | 17.08 |
September | 23.28 | 13.78 |
October | 22.39 | 9.83 |
November | 21.88 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.74 | 9.74 |
Minimum of Months | 21.74 | 3.20 |
Maximum of Months | 23.95 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.84 | 6.09 |
April | 22.14 | 8.68 |
May | 22.88 | 11.83 |
June | 23.36 | 15.06 |
July | 23.69 | 16.98 |
August | 23.38 | 17.08 |
September | 22.53 | 13.78 |
October | 21.88 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.38 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.69 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.84 | 6.09 |
April | 22.08 | 8.68 |
May | 22.88 | 11.83 |
June | 23.38 | 15.06 |
July | 23.70 | 16.98 |
August | 23.35 | 17.08 |
September | 22.52 | 13.78 |
October | 21.89 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.37 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.70 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.84 | 6.09 |
April | 22.07 | 8.68 |
May | 22.87 | 11.83 |
June | 23.36 | 15.06 |
July | 23.69 | 16.98 |
August | 23.34 | 17.08 |
September | 22.51 | 13.78 |
October | 21.89 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.37 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.69 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.16 | 5.10 |
March | 22.38 | 6.09 |
April | 22.89 | 8.68 |
May | 23.52 | 11.83 |
June | 23.83 | 15.06 |
July | 24.02 | 16.98 |
August | 23.89 | 17.08 |
September | 23.53 | 13.78 |
October | 22.58 | 9.83 |
November | 21.95 | 5.28 |
December | 21.78 | 3.63 |
Annual Sum or Average | 22.86 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.02 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.16 | 5.10 |
March | 22.38 | 6.09 |
April | 22.88 | 8.68 |
May | 23.51 | 11.83 |
June | 23.82 | 15.06 |
July | 24.02 | 16.98 |
August | 23.89 | 17.08 |
September | 23.53 | 13.78 |
October | 22.59 | 9.83 |
November | 21.95 | 5.28 |
December | 21.78 | 3.63 |
Annual Sum or Average | 22.86 | 9.74 |
Minimum of Months | 21.78 | 3.20 |
Maximum of Months | 24.02 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:12:21
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 3.20 |
February | 22.21 | 5.10 |
March | 22.62 | 6.09 |
April | 23.77 | 8.68 |
May | 25.02 | 11.83 |
June | 25.89 | 15.06 |
July | 26.44 | 16.98 |
August | 26.01 | 17.08 |
September | 24.82 | 13.78 |
October | 23.01 | 9.83 |
November | 21.81 | 5.28 |
December | 21.33 | 3.63 |
Annual Sum or Average | 23.71 | 9.74 |
Minimum of Months | 21.33 | 3.20 |
Maximum of Months | 26.44 | 17.08 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:21
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.240809E+12 | 138860.378 | 09-JAN-17:15 | 11327.174 | 57142.088 | 17544.917 | 38809.779 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.199188E+12 | 144936.822 | 17-FEB-17:30 | 11327.174 | 57142.088 | 17544.917 | 44886.260 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.220230E+12 | 130539.304 | 04-MAR-17:00 | 11327.174 | 57042.023 | 17544.917 | 30596.155 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.196792E+12 | 122611.349 | 29-APR-17:15 | 13120.457 | 57042.023 | 17544.917 | 0.000 | 30128.168 | 0.000 | 1677.224 | 1110.748 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.198655E+12 | 115672.123 | 23-MAY-19:00 | 14401.373 | 49889.926 | 17544.917 | 0.000 | 19382.067 | 10364.000 | 1677.224 | 771.312 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.194088E+12 | 136154.679 | 28-JUN-17:00 | 13120.457 | 57042.023 | 17544.917 | 0.000 | 43165.166 | 0.000 | 1677.224 | 1616.884 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.216965E+12 | 146997.284 | 11-JUL-17:15 | 13120.457 | 57042.023 | 17544.917 | 0.000 | 53689.936 | 0.000 | 1677.224 | 1934.916 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.210428E+12 | 138981.765 | 12-AUG-17:15 | 13120.457 | 57042.023 | 17544.917 | 0.000 | 45895.220 | 0.000 | 1677.224 | 1714.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.197914E+12 | 136597.400 | 13-SEP-16:15 | 11327.174 | 57142.088 | 17544.917 | 0.000 | 45130.163 | 0.000 | 1677.224 | 1780.637 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.207490E+12 | 111666.161 | 27-OCT-17:00 | 13120.457 | 57042.023 | 17544.917 | 9929.531 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.223282E+12 | 154277.434 | 20-NOV-17:00 | 11327.174 | 57142.088 | 17544.917 | 54226.872 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.249496E+12 | 163265.216 | 16-DEC-17:15 | 11327.174 | 57042.023 | 17544.917 | 63322.236 | 0.000 | 10364.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.255534E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.194088E+12 | 111666.161 | 11327.174 | 49889.926 | 17544.917 | 0.000 | 0.000 | 0.000 | 1677.224 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.249496E+12 | 163265.216 | 14401.373 | 57142.088 | 17544.917 | 63322.236 | 53689.936 | 10364.000 | 1677.224 | 1934.916 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:21
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.283876E+12 | 216010.668 | 09-JAN-08:45 | 0.000 | 0.000 | 0.000 | 216010.668 | 77649.086 | 77649.086 | 138361.582 |
February | 0.185278E+12 | 231766.602 | 17-FEB-17:30 | 0.000 | 0.000 | 0.000 | 231766.602 | 70811.043 | 70811.043 | 160955.558 |
March | 0.202360E+12 | 198831.409 | 20-MAR-07:45 | 0.000 | 0.000 | 0.000 | 198831.409 | 78951.274 | 78951.274 | 119880.135 |
April | 0.125058E+12 | 222705.551 | 15-APR-05:00 | 0.000 | 0.000 | 0.000 | 222705.551 | 77378.439 | 77378.439 | 145327.112 |
May | 0.101825E+12 | 100455.044 | 16-MAY-07:30 | 0.000 | 0.000 | 0.000 | 100455.044 | 77172.186 | 77172.186 | 23282.858 |
June | 0.936225E+11 | 77699.218 | 02-JUN-06:00 | 0.000 | 0.000 | 0.000 | 77699.218 | 77699.218 | 77699.218 | 0.000 |
July | 0.942978E+11 | 76707.876 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 76707.876 | 76707.876 | 76707.876 | 0.000 |
August | 0.934266E+11 | 76127.744 | 01-AUG-06:00 | 0.000 | 0.000 | 0.000 | 76127.744 | 76127.744 | 76127.744 | 0.000 |
September | 0.959984E+11 | 144833.776 | 01-SEP-13:45 | 0.000 | 0.000 | 0.000 | 144833.776 | 31923.156 | 31923.156 | 112910.620 |
October | 0.134447E+12 | 174392.219 | 28-OCT-05:15 | 0.000 | 0.000 | 0.000 | 174392.219 | 66267.174 | 66267.174 | 108125.046 |
November | 0.228366E+12 | 243575.375 | 20-NOV-18:30 | 0.000 | 0.000 | 0.000 | 243575.375 | 73530.092 | 73530.092 | 170045.283 |
December | 0.312958E+12 | 258166.951 | 16-DEC-18:00 | 0.000 | 0.000 | 0.000 | 258166.951 | 74728.682 | 74728.682 | 183438.269 |
Annual Sum or Average | 0.195151E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.934266E+11 | 76127.744 | 0.000 | 0.000 | 0.000 | 76127.744 | 31923.156 | 31923.156 | 0.000 | |
Maximum of Months | 0.312958E+12 | 258166.951 | 0.000 | 0.000 | 0.000 | 258166.951 | 78951.274 | 78951.274 | 183438.269 |