Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2015-09-09 19:00:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4112.35 | 524.77 | 582.49 |
Net Site Energy | 4112.35 | 524.77 | 582.49 |
Total Source Energy | 10864.79 | 1386.44 | 1538.95 |
Net Source Energy | 10864.79 | 1386.44 | 1538.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 30.37 | 61.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 636.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 695.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.76 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 974.83 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3075.86 | 1036.49 | 0.00 | 0.00 | 0.00 | 6965.27 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 61.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 30.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 636.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 695.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 56.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 24.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.76 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 974.83 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 204.37 | 146.81 | 0.00 | 0.00 | 0.00 | 0.99 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 435.68 | 146.81 | 0.00 | 0.00 | 0.00 | 0.99 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 184.12 | 132.26 | 0.00 | 0.00 | 0.00 | 0.89 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 392.50 | 132.26 | 0.00 | 0.00 | 0.00 | 0.89 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3075.86 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3075.86 | 100.00 |
Total On-Site and Utility Electric Sources | 3075.86 | 100.00 |
Total Electricity End Uses | 3075.86 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6965.27 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6965.27 | 100.00 |
Total Water End Uses | 6965.27 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 65.00 |
Time Setpoint Not Met During Occupied Cooling | 245.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1242.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-19:00 | 27-DEC-07:30 | - | - | - | 14-JUN-17:15 |
Heating | 0.00 | 82687.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 63390.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22038.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1833.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2346.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 76170.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 165905.79 | 158857.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 82687.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 63390.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 11484.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2917.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22038.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1833.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2346.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 76170.72 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 96.17 | 66.84 | 0.00 | 0.00 | 0.00 |
Cooling | 2016.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 516.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2201.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 180.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 76.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1056.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9741.24 | 1123.55 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 13.62 | 9.47 | 0.00 | 0.00 | 0.00 |
Cooling | 285.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 311.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.68 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1379.80 | 159.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 13.62 | 9.47 | 0.00 | 0.00 | 0.00 |
Cooling | 285.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 311.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 25.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 149.68 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1379.80 | 159.15 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.77 | 83.77 | 162.97 | |
Exterior Lighting Total | 10364.00 | 162.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 258651.50 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 206921.20 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3331.51 | 2202.53 | 1128.98 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3281.06 | 2172.23 | 1108.82 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4816.47 | 3203.36 | 1613.10 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2543.24 | 1687.17 | 856.07 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1935.73 | 1265.39 | 670.34 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1920.33 | 1255.04 | 665.29 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2030.42 | 1308.69 | 721.73 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2108.76 | 1363.00 | 745.76 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4026.71 | 2679.14 | 1347.56 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3963.59 | 2638.95 | 1324.64 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3771.45 | 2498.92 | 1272.53 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3146.76 | 2101.37 | 1045.39 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2382.04 | 1567.84 | 814.21 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2369.64 | 1559.50 | 810.15 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2492.55 | 1625.60 | 866.95 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2518.22 | 1642.95 | 875.28 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4042.36 | 2694.22 | 1348.13 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3983.93 | 2657.21 | 1326.72 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3521.20 | 2334.69 | 1186.51 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3184.26 | 2131.03 | 1053.22 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2415.59 | 1593.04 | 822.55 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2403.42 | 1584.85 | 818.57 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2530.52 | 1653.83 | 876.69 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2539.45 | 1659.86 | 879.59 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4071.42 | 2716.14 | 1355.29 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4006.92 | 2676.09 | 1330.83 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3531.51 | 2343.70 | 1187.80 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3206.49 | 2149.29 | 1057.21 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2441.03 | 1612.12 | 828.91 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2429.02 | 1604.03 | 824.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2556.23 | 1673.13 | 883.10 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2562.68 | 1677.48 | 885.20 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4121.80 | 2752.82 | 1368.98 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4057.32 | 2712.78 | 1344.54 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3587.07 | 2383.83 | 1203.24 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3255.56 | 2185.02 | 1070.53 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2491.53 | 1647.71 | 843.83 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2479.65 | 1639.71 | 839.95 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2606.07 | 1708.39 | 897.68 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2612.18 | 1712.51 | 899.67 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4090.88 | 2734.34 | 1356.54 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4024.40 | 2692.98 | 1331.42 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3564.39 | 2370.77 | 1193.62 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3237.61 | 2171.66 | 1065.95 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2461.61 | 1628.92 | 832.68 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2449.89 | 1621.03 | 828.86 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2577.23 | 1690.22 | 887.02 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2583.30 | 1694.31 | 888.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4088.29 | 2734.65 | 1353.64 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4021.23 | 2692.90 | 1328.32 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3568.84 | 2375.74 | 1193.11 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3235.61 | 2172.26 | 1063.34 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2459.91 | 1628.97 | 830.94 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2448.33 | 1621.17 | 827.16 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2575.67 | 1690.27 | 885.40 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2581.61 | 1694.33 | 887.28 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4104.83 | 2747.63 | 1357.20 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4037.33 | 2705.59 | 1331.73 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3590.71 | 2392.26 | 1198.45 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3332.70 | 2219.30 | 1113.40 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2477.23 | 1641.70 | 835.53 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2465.79 | 1633.99 | 831.80 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2592.36 | 1702.60 | 889.76 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2598.03 | 1706.48 | 891.54 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4250.32 | 2848.37 | 1401.95 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4190.91 | 2810.71 | 1380.20 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3718.63 | 2480.18 | 1238.45 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.36 | 2315.25 | 1157.11 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2617.11 | 1736.89 | 880.22 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2605.68 | 1729.19 | 876.50 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2702.00 | 1777.75 | 924.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2707.60 | 1781.53 | 926.07 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5405.36 | 3622.37 | 1782.98 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5261.53 | 3528.82 | 1732.70 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4821.01 | 3225.05 | 1595.96 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4510.40 | 3015.73 | 1494.67 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3559.47 | 2357.55 | 1201.92 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3555.69 | 2354.99 | 1200.70 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3856.69 | 2557.89 | 1298.80 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3861.51 | 2561.13 | 1300.38 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3331.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3281.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4816.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2543.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1935.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1920.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2030.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2108.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4026.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3963.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3771.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3146.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2382.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2369.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2492.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2518.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4042.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3983.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3521.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3184.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2415.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2403.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2530.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2539.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4071.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4006.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3531.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3206.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2441.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2429.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2556.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2562.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4121.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4057.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3587.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3255.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2491.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2479.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2606.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2612.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4090.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4024.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3564.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3237.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2461.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2449.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2577.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2583.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4088.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4021.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3568.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3235.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2459.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2448.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2575.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2581.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4104.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4037.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3590.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3332.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2477.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2465.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2592.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2598.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4250.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4190.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3718.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2617.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2605.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2702.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2707.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5405.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5261.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4821.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4510.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3559.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3555.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3856.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3861.51 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2461.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2460.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3141.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2456.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1835.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1835.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1833.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1839.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2399.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2394.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2414.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2390.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1626.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1626.59 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1634.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1635.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2388.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2385.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2387.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2382.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1588.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1588.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1592.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1592.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2423.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2421.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2421.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2418.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1600.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1600.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1603.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1603.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2438.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2436.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2437.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2434.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1599.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1599.52 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1602.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1602.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2513.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2513.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2512.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2511.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1657.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1657.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1657.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1657.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2563.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2562.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2562.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2562.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1692.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1692.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1693.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1693.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2616.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2616.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2616.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2616.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1734.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1734.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1734.34 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1734.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2783.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2781.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2783.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2781.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1879.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1879.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1881.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1881.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3352.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3357.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3353.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3358.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2497.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2497.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2489.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2489.38 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.67 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 280.68 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 415.65 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.84 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 159.09 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 157.69 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 160.43 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.96 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 349.28 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 344.60 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.73 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 273.59 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 199.67 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 198.54 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 203.44 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 205.79 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 351.58 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 347.34 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 300.64 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 277.87 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 203.23 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 202.12 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 207.40 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.22 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 354.40 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 350.09 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.80 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 280.53 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 205.93 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 204.83 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.12 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.71 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 359.54 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 355.24 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 307.40 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 285.54 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.84 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.76 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 214.98 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.54 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 357.15 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 352.67 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.75 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.10 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.37 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 207.30 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.59 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.14 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 357.31 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 352.77 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 306.53 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.29 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.44 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 207.38 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.66 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.21 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 359.18 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 354.60 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 308.87 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 285.63 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.23 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.18 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 214.39 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 214.91 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 373.35 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 369.02 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 320.92 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.76 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 223.20 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.16 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 224.62 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.14 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 477.50 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 465.46 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 422.45 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 393.93 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 303.41 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 303.06 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 330.66 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 331.10 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0056 | 1796.59 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2255.34 | 2706.41 | 0.204 | 0.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
G NW APARTMENT | 2231.55 | 2677.86 | 0.201 | 0.242 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
OFFICE | 3304.73 | 3965.68 | 0.298 | 0.358 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 35.44 | 0.00682 |
G NE APARTMENT | 1723.97 | 2068.77 | 0.156 | 0.187 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
G N1 APARTMENT | 1264.83 | 1517.79 | 0.114 | 0.137 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G N2 APARTMENT | 1253.71 | 1504.45 | 0.113 | 0.136 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G S1 APARTMENT | 1275.49 | 1530.59 | 0.115 | 0.138 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
G S2 APARTMENT | 1335.36 | 1602.44 | 0.121 | 0.145 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F2 SW APARTMENT | 2777.00 | 3332.40 | 0.251 | 0.301 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F2 NW APARTMENT | 2739.78 | 3287.74 | 0.247 | 0.297 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F2 SE APARTMENT | 2565.93 | 3079.12 | 0.232 | 0.278 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F2 NE APARTMENT | 2175.21 | 2610.25 | 0.196 | 0.236 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F2 N1 APARTMENT | 1587.47 | 1904.97 | 0.143 | 0.172 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F2 N2 APARTMENT | 1578.48 | 1894.18 | 0.143 | 0.171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F2 S1 APARTMENT | 1617.47 | 1940.97 | 0.146 | 0.175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F2 S2 APARTMENT | 1636.13 | 1963.35 | 0.148 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F3 SW APARTMENT | 2795.31 | 3354.38 | 0.252 | 0.303 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F3 NW APARTMENT | 2761.55 | 3313.86 | 0.249 | 0.299 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F3 SE APARTMENT | 2390.29 | 2868.35 | 0.216 | 0.259 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
F3 NE APARTMENT | 2209.23 | 2651.07 | 0.199 | 0.239 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F3 N1 APARTMENT | 1615.80 | 1938.96 | 0.146 | 0.175 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F3 N2 APARTMENT | 1606.97 | 1928.36 | 0.145 | 0.174 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F3 S1 APARTMENT | 1648.97 | 1978.76 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F3 S2 APARTMENT | 1655.45 | 1986.54 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F4 SW APARTMENT | 2817.71 | 3381.25 | 0.254 | 0.305 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
F4 NW APARTMENT | 2783.48 | 3340.18 | 0.251 | 0.302 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F4 SE APARTMENT | 2399.54 | 2879.45 | 0.217 | 0.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F4 NE APARTMENT | 2230.41 | 2676.49 | 0.201 | 0.242 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
F4 N1 APARTMENT | 1637.24 | 1964.68 | 0.148 | 0.177 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F4 N2 APARTMENT | 1628.51 | 1954.21 | 0.147 | 0.176 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F4 S1 APARTMENT | 1670.57 | 2004.69 | 0.151 | 0.181 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F4 S2 APARTMENT | 1675.26 | 2010.31 | 0.151 | 0.182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
M SW APARTMENT | 2858.63 | 3430.36 | 0.258 | 0.310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
M NW APARTMENT | 2824.41 | 3389.30 | 0.255 | 0.306 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
M SE APARTMENT | 2444.08 | 2932.90 | 0.221 | 0.265 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
M NE APARTMENT | 2270.26 | 2724.31 | 0.205 | 0.246 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
M N1 APARTMENT | 1676.32 | 2011.59 | 0.151 | 0.182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M N2 APARTMENT | 1667.69 | 2001.23 | 0.151 | 0.181 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M S1 APARTMENT | 1709.22 | 2051.07 | 0.154 | 0.185 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
M S2 APARTMENT | 1713.66 | 2056.39 | 0.155 | 0.186 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F6 SW APARTMENT | 2839.65 | 3407.58 | 0.256 | 0.308 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
F6 NW APARTMENT | 2804.00 | 3364.80 | 0.253 | 0.304 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F6 SE APARTMENT | 2430.93 | 2917.12 | 0.219 | 0.263 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F6 NE APARTMENT | 2250.89 | 2701.06 | 0.203 | 0.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
F6 N1 APARTMENT | 1656.65 | 1987.98 | 0.150 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F6 N2 APARTMENT | 1648.14 | 1977.77 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F6 S1 APARTMENT | 1690.23 | 2028.28 | 0.153 | 0.183 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F6 S2 APARTMENT | 1694.64 | 2033.57 | 0.153 | 0.184 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F7 SW APARTMENT | 2840.87 | 3409.05 | 0.257 | 0.308 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
F7 NW APARTMENT | 2804.82 | 3365.78 | 0.253 | 0.304 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F7 SE APARTMENT | 2437.16 | 2924.59 | 0.220 | 0.264 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F7 NE APARTMENT | 2252.38 | 2702.86 | 0.203 | 0.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
F7 N1 APARTMENT | 1657.22 | 1988.67 | 0.150 | 0.180 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F7 N2 APARTMENT | 1648.80 | 1978.56 | 0.149 | 0.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F7 S1 APARTMENT | 1690.77 | 2028.93 | 0.153 | 0.183 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
F7 S2 APARTMENT | 1695.17 | 2034.20 | 0.153 | 0.184 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F8 SW APARTMENT | 2855.73 | 3426.88 | 0.258 | 0.309 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
F8 NW APARTMENT | 2819.36 | 3383.23 | 0.255 | 0.305 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F8 SE APARTMENT | 2455.79 | 2946.95 | 0.222 | 0.266 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F8 NE APARTMENT | 2270.95 | 2725.14 | 0.205 | 0.246 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
F8 N1 APARTMENT | 1671.42 | 2005.71 | 0.151 | 0.181 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F8 N2 APARTMENT | 1663.09 | 1995.71 | 0.150 | 0.180 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F8 S1 APARTMENT | 1704.51 | 2045.41 | 0.154 | 0.185 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
F8 S2 APARTMENT | 1708.71 | 2050.45 | 0.154 | 0.185 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
F9 SW APARTMENT | 2968.40 | 3562.07 | 0.268 | 0.322 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
F9 NW APARTMENT | 2933.97 | 3520.77 | 0.265 | 0.318 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
F9 SE APARTMENT | 2551.60 | 3061.92 | 0.230 | 0.276 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
F9 NE APARTMENT | 2375.42 | 2850.51 | 0.214 | 0.257 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
F9 N1 APARTMENT | 1774.61 | 2129.53 | 0.160 | 0.192 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F9 N2 APARTMENT | 1766.29 | 2119.55 | 0.159 | 0.191 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
F9 S1 APARTMENT | 1785.91 | 2143.10 | 0.161 | 0.194 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
F9 S2 APARTMENT | 1789.98 | 2147.98 | 0.162 | 0.194 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
T SW APARTMENT | 3796.51 | 4555.81 | 0.343 | 0.411 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
T NW APARTMENT | 3700.78 | 4440.94 | 0.334 | 0.401 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
T SE APARTMENT | 3358.86 | 4030.64 | 0.303 | 0.364 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T NE APARTMENT | 3132.11 | 3758.53 | 0.283 | 0.339 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10 | 0.00682 |
T N1 APARTMENT | 2412.33 | 2894.79 | 0.218 | 0.261 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T N2 APARTMENT | 2409.55 | 2891.46 | 0.218 | 0.261 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T S1 APARTMENT | 2628.97 | 3154.76 | 0.237 | 0.285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T S2 APARTMENT | 2632.47 | 3158.96 | 0.238 | 0.285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1461.83 | 1754.20 | 0.075 | 0.090 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G NW APARTMENT | 1460.87 | 1753.04 | 0.075 | 0.090 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
OFFICE | 1747.16 | 2096.60 | 0.090 | 0.108 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.20 | 0.00281 |
G NE APARTMENT | 1457.96 | 1749.56 | 0.075 | 0.090 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N1 APARTMENT | 932.90 | 1119.48 | 0.048 | 0.057 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N2 APARTMENT | 932.82 | 1119.39 | 0.048 | 0.057 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S1 APARTMENT | 930.75 | 1116.89 | 0.048 | 0.057 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S2 APARTMENT | 935.98 | 1123.17 | 0.048 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
F2 SW APARTMENT | 1409.75 | 1691.70 | 0.072 | 0.087 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 NW APARTMENT | 1405.37 | 1686.44 | 0.072 | 0.087 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 SE APARTMENT | 1422.66 | 1707.20 | 0.073 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 NE APARTMENT | 1402.39 | 1682.86 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 N1 APARTMENT | 756.09 | 907.30 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 N2 APARTMENT | 756.01 | 907.21 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 S1 APARTMENT | 762.74 | 915.29 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F2 S2 APARTMENT | 763.72 | 916.47 | 0.039 | 0.047 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 SW APARTMENT | 1400.48 | 1680.58 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 NW APARTMENT | 1397.50 | 1677.01 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 SE APARTMENT | 1399.81 | 1679.77 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 NE APARTMENT | 1395.05 | 1674.06 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 N1 APARTMENT | 723.69 | 868.43 | 0.037 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 N2 APARTMENT | 723.63 | 868.35 | 0.037 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 S1 APARTMENT | 727.25 | 872.70 | 0.037 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F3 S2 APARTMENT | 727.36 | 872.83 | 0.037 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 SW APARTMENT | 1429.79 | 1715.75 | 0.073 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 NW APARTMENT | 1428.00 | 1713.60 | 0.073 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 SE APARTMENT | 1428.01 | 1713.62 | 0.073 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 NE APARTMENT | 1426.04 | 1711.24 | 0.073 | 0.088 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 N1 APARTMENT | 734.22 | 881.06 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 N2 APARTMENT | 734.16 | 881.00 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 S1 APARTMENT | 736.38 | 883.66 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F4 S2 APARTMENT | 736.35 | 883.62 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M SW APARTMENT | 1442.87 | 1731.44 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M NW APARTMENT | 1441.08 | 1729.30 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M SE APARTMENT | 1441.38 | 1729.65 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M NE APARTMENT | 1439.57 | 1727.48 | 0.074 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M N1 APARTMENT | 733.17 | 879.80 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M N2 APARTMENT | 733.13 | 879.75 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M S1 APARTMENT | 735.30 | 882.36 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
M S2 APARTMENT | 735.26 | 882.31 | 0.038 | 0.045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 SW APARTMENT | 1506.15 | 1807.38 | 0.077 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 NW APARTMENT | 1505.69 | 1806.83 | 0.077 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 SE APARTMENT | 1505.04 | 1806.05 | 0.077 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 NE APARTMENT | 1504.58 | 1805.50 | 0.077 | 0.093 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 N1 APARTMENT | 781.78 | 938.14 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 N2 APARTMENT | 781.75 | 938.11 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 S1 APARTMENT | 782.53 | 939.04 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F6 S2 APARTMENT | 782.50 | 939.01 | 0.040 | 0.048 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 SW APARTMENT | 1547.97 | 1857.57 | 0.079 | 0.095 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 NW APARTMENT | 1547.90 | 1857.48 | 0.079 | 0.095 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 SE APARTMENT | 1547.23 | 1856.68 | 0.079 | 0.095 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 NE APARTMENT | 1547.16 | 1856.59 | 0.079 | 0.095 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 N1 APARTMENT | 812.04 | 974.45 | 0.042 | 0.050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 N2 APARTMENT | 812.02 | 974.42 | 0.042 | 0.050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 S1 APARTMENT | 812.37 | 974.85 | 0.042 | 0.050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F7 S2 APARTMENT | 812.35 | 974.82 | 0.042 | 0.050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 SW APARTMENT | 1593.27 | 1911.92 | 0.082 | 0.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 NW APARTMENT | 1593.37 | 1912.05 | 0.082 | 0.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 SE APARTMENT | 1592.87 | 1911.44 | 0.082 | 0.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 NE APARTMENT | 1592.97 | 1911.57 | 0.082 | 0.098 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 N1 APARTMENT | 847.00 | 1016.40 | 0.043 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 N2 APARTMENT | 846.99 | 1016.39 | 0.043 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 S1 APARTMENT | 847.14 | 1016.57 | 0.043 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F8 S2 APARTMENT | 847.13 | 1016.56 | 0.043 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 SW APARTMENT | 1734.09 | 2080.91 | 0.089 | 0.107 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 NW APARTMENT | 1732.53 | 2079.04 | 0.089 | 0.107 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 SE APARTMENT | 1734.00 | 2080.80 | 0.089 | 0.107 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 NE APARTMENT | 1732.44 | 2078.93 | 0.089 | 0.107 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 N1 APARTMENT | 970.24 | 1164.29 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 N2 APARTMENT | 970.24 | 1164.28 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 S1 APARTMENT | 971.68 | 1166.02 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
F9 S2 APARTMENT | 971.68 | 1166.01 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T SW APARTMENT | 2215.96 | 2659.15 | 0.114 | 0.136 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T NW APARTMENT | 2220.06 | 2664.07 | 0.114 | 0.137 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T SE APARTMENT | 2216.13 | 2659.36 | 0.114 | 0.136 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T NE APARTMENT | 2220.23 | 2664.28 | 0.114 | 0.137 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T N1 APARTMENT | 1492.22 | 1790.66 | 0.077 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T N2 APARTMENT | 1492.22 | 1790.66 | 0.077 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T S1 APARTMENT | 1485.64 | 1782.77 | 0.076 | 0.091 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
T S2 APARTMENT | 1485.65 | 1782.78 | 0.076 | 0.091 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP G NW | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP OFFICE | 0.36 | 0.36 | 0.11 | 0.11 |
AIRLOOP G NE | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP G N1 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP G N2 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP G S1 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP G S2 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP F2 SW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F2 NW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F2 SE | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP F2 NE | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F2 N1 | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F2 N2 | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP F2 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F3 SW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F3 NW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F3 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F3 NE | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F3 N1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F3 N2 | 0.17 | 0.17 | 0.04 | 0.04 |
AIRLOOP F3 S1 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F3 S2 | 0.18 | 0.18 | 0.04 | 0.04 |
AIRLOOP F4 SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F4 NW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F4 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F4 NE | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F4 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F4 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F4 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F4 S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP M SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP M NW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP M SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP M NE | 0.25 | 0.25 | 0.09 | 0.09 |
AIRLOOP M N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP M N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP M S1 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F6 SW | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F6 NW | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F6 SE | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F6 NE | 0.24 | 0.24 | 0.09 | 0.09 |
AIRLOOP F6 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F6 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F6 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F6 S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 SW | 0.31 | 0.31 | 0.10 | 0.10 |
AIRLOOP F7 NW | 0.30 | 0.30 | 0.10 | 0.10 |
AIRLOOP F7 SE | 0.26 | 0.26 | 0.10 | 0.10 |
AIRLOOP F7 NE | 0.24 | 0.24 | 0.10 | 0.10 |
AIRLOOP F7 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F7 S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 SW | 0.31 | 0.31 | 0.10 | 0.10 |
AIRLOOP F8 NW | 0.31 | 0.31 | 0.10 | 0.10 |
AIRLOOP F8 SE | 0.27 | 0.27 | 0.10 | 0.10 |
AIRLOOP F8 NE | 0.25 | 0.25 | 0.10 | 0.10 |
AIRLOOP F8 N1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 N2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 S1 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F8 S2 | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F9 SW | 0.32 | 0.32 | 0.11 | 0.11 |
AIRLOOP F9 NW | 0.32 | 0.32 | 0.11 | 0.11 |
AIRLOOP F9 SE | 0.28 | 0.28 | 0.11 | 0.11 |
AIRLOOP F9 NE | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F9 N1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F9 N2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F9 S1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F9 S2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP T SW | 0.41 | 0.41 | 0.14 | 0.14 |
AIRLOOP T NW | 0.40 | 0.40 | 0.14 | 0.14 |
AIRLOOP T SE | 0.36 | 0.36 | 0.14 | 0.14 |
AIRLOOP T NE | 0.34 | 0.34 | 0.14 | 0.14 |
AIRLOOP T N1 | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP T N2 | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP T S1 | 0.28 | 0.28 | 0.09 | 0.09 |
AIRLOOP T S2 | 0.29 | 0.29 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3364.75 | 4855.00 | 641.50 |
G NW APARTMENT | 3200.25 | 5620.75 | 756.50 |
OFFICE | 1151.50 | 333.50 | 2.50 |
G NE APARTMENT | 3226.75 | 5625.25 | 761.75 |
G N1 APARTMENT | 2986.00 | 6028.75 | 896.50 |
G N2 APARTMENT | 2985.75 | 6028.25 | 895.50 |
G S1 APARTMENT | 3168.50 | 5200.25 | 742.00 |
G S2 APARTMENT | 3203.50 | 5101.75 | 726.50 |
F2 SW APARTMENT | 3969.00 | 3211.25 | 417.50 |
F2 NW APARTMENT | 3501.00 | 4639.25 | 486.25 |
F2 SE APARTMENT | 4116.00 | 2815.50 | 348.50 |
F2 NE APARTMENT | 3550.00 | 4651.50 | 493.00 |
F2 N1 APARTMENT | 3325.75 | 4936.75 | 587.50 |
F2 N2 APARTMENT | 3321.00 | 4942.25 | 586.50 |
F2 S1 APARTMENT | 3892.75 | 3058.25 | 473.50 |
F2 S2 APARTMENT | 3910.25 | 2999.75 | 469.25 |
F3 SW APARTMENT | 4068.25 | 2920.25 | 412.75 |
F3 NW APARTMENT | 3569.75 | 4485.00 | 477.00 |
F3 SE APARTMENT | 4111.25 | 2829.75 | 388.75 |
F3 NE APARTMENT | 3607.00 | 4507.50 | 481.75 |
F3 N1 APARTMENT | 3434.00 | 4677.00 | 568.50 |
F3 N2 APARTMENT | 3432.75 | 4680.25 | 569.25 |
F3 S1 APARTMENT | 4086.50 | 2598.75 | 462.25 |
F3 S2 APARTMENT | 4089.75 | 2585.25 | 461.75 |
F4 SW APARTMENT | 4067.25 | 2913.50 | 427.00 |
F4 NW APARTMENT | 3572.00 | 4466.00 | 482.75 |
F4 SE APARTMENT | 4089.00 | 2866.00 | 407.00 |
F4 NE APARTMENT | 3610.00 | 4500.00 | 492.75 |
F4 N1 APARTMENT | 3448.25 | 4624.75 | 565.25 |
F4 N2 APARTMENT | 3446.00 | 4628.50 | 568.50 |
F4 S1 APARTMENT | 4112.00 | 2527.50 | 464.00 |
F4 S2 APARTMENT | 4112.50 | 2528.00 | 465.50 |
M SW APARTMENT | 4064.25 | 2948.50 | 428.75 |
M NW APARTMENT | 3579.25 | 4458.25 | 476.25 |
M SE APARTMENT | 4087.75 | 2895.50 | 405.50 |
M NE APARTMENT | 3614.00 | 4501.25 | 489.75 |
M N1 APARTMENT | 3459.25 | 4594.50 | 551.75 |
M N2 APARTMENT | 3458.25 | 4600.50 | 552.25 |
M S1 APARTMENT | 4119.50 | 2526.00 | 457.50 |
M S2 APARTMENT | 4116.75 | 2526.00 | 458.50 |
F6 SW APARTMENT | 3975.00 | 3174.75 | 457.75 |
F6 NW APARTMENT | 3523.50 | 4572.75 | 502.50 |
F6 SE APARTMENT | 3986.00 | 3115.25 | 439.00 |
F6 NE APARTMENT | 3566.00 | 4603.25 | 517.25 |
F6 N1 APARTMENT | 3397.00 | 4716.75 | 586.00 |
F6 N2 APARTMENT | 3397.50 | 4724.25 | 587.00 |
F6 S1 APARTMENT | 4008.25 | 2767.75 | 486.75 |
F6 S2 APARTMENT | 4005.25 | 2759.75 | 486.25 |
F7 SW APARTMENT | 3927.00 | 3321.00 | 471.75 |
F7 NW APARTMENT | 3496.50 | 4642.00 | 516.75 |
F7 SE APARTMENT | 3934.50 | 3268.00 | 452.25 |
F7 NE APARTMENT | 3531.00 | 4669.00 | 538.00 |
F7 N1 APARTMENT | 3361.00 | 4797.00 | 601.25 |
F7 N2 APARTMENT | 3359.50 | 4803.00 | 600.25 |
F7 S1 APARTMENT | 3940.00 | 2931.50 | 502.00 |
F7 S2 APARTMENT | 3936.00 | 2933.25 | 502.75 |
F8 SW APARTMENT | 3881.75 | 3446.25 | 480.25 |
F8 NW APARTMENT | 3476.50 | 4693.00 | 532.25 |
F8 SE APARTMENT | 3889.25 | 3393.75 | 461.00 |
F8 NE APARTMENT | 3509.25 | 4708.25 | 534.00 |
F8 N1 APARTMENT | 3336.75 | 4843.75 | 604.75 |
F8 N2 APARTMENT | 3336.25 | 4851.75 | 605.75 |
F8 S1 APARTMENT | 3884.50 | 3086.25 | 511.00 |
F8 S2 APARTMENT | 3882.50 | 3085.50 | 510.50 |
F9 SW APARTMENT | 3840.50 | 3580.75 | 475.00 |
F9 NW APARTMENT | 3487.25 | 4724.25 | 538.25 |
F9 SE APARTMENT | 3844.25 | 3533.75 | 455.50 |
F9 NE APARTMENT | 3527.50 | 4736.00 | 538.75 |
F9 N1 APARTMENT | 3337.50 | 4864.50 | 585.75 |
F9 N2 APARTMENT | 3334.50 | 4869.50 | 586.00 |
F9 S1 APARTMENT | 3821.25 | 3278.00 | 497.75 |
F9 S2 APARTMENT | 3820.50 | 3273.00 | 496.50 |
T SW APARTMENT | 4232.00 | 3880.50 | 631.75 |
T NW APARTMENT | 3849.50 | 4821.75 | 848.75 |
T SE APARTMENT | 4294.50 | 3808.75 | 631.00 |
T NE APARTMENT | 3893.25 | 4822.00 | 836.25 |
T N1 APARTMENT | 3567.00 | 4970.50 | 695.50 |
T N2 APARTMENT | 3569.50 | 4976.25 | 698.75 |
T S1 APARTMENT | 4062.75 | 3725.75 | 547.50 |
T S2 APARTMENT | 4069.50 | 3723.00 | 547.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5140.25 | 6080.50 | 1242.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.50 | 13.00 | 1.50 | 13.00 |
G NW APARTMENT | 0.00 | 21.25 | 0.00 | 21.25 |
OFFICE | 2.25 | 7.25 | 0.00 | 6.00 |
G NE APARTMENT | 1.25 | 30.25 | 1.25 | 30.25 |
G N1 APARTMENT | 9.25 | 32.50 | 9.25 | 32.50 |
G N2 APARTMENT | 8.00 | 33.50 | 8.00 | 33.50 |
G S1 APARTMENT | 1.25 | 87.25 | 1.25 | 87.25 |
G S2 APARTMENT | 1.50 | 69.25 | 1.50 | 69.25 |
F2 SW APARTMENT | 0.50 | 18.00 | 0.50 | 18.00 |
F2 NW APARTMENT | 0.25 | 19.75 | 0.25 | 19.75 |
F2 SE APARTMENT | 1.00 | 7.25 | 1.00 | 7.25 |
F2 NE APARTMENT | 0.25 | 31.00 | 0.25 | 31.00 |
F2 N1 APARTMENT | 4.50 | 26.75 | 4.50 | 26.75 |
F2 N2 APARTMENT | 4.50 | 26.75 | 4.50 | 26.75 |
F2 S1 APARTMENT | 0.00 | 116.50 | 0.00 | 116.50 |
F2 S2 APARTMENT | 0.00 | 108.50 | 0.00 | 108.50 |
F3 SW APARTMENT | 0.25 | 23.00 | 0.25 | 23.00 |
F3 NW APARTMENT | 0.25 | 22.00 | 0.25 | 22.00 |
F3 SE APARTMENT | 0.75 | 38.50 | 0.75 | 38.50 |
F3 NE APARTMENT | 0.25 | 43.50 | 0.25 | 43.50 |
F3 N1 APARTMENT | 2.25 | 34.75 | 2.25 | 34.75 |
F3 N2 APARTMENT | 2.25 | 35.25 | 2.25 | 35.25 |
F3 S1 APARTMENT | 0.00 | 129.25 | 0.00 | 129.25 |
F3 S2 APARTMENT | 0.25 | 128.25 | 0.25 | 128.25 |
F4 SW APARTMENT | 0.25 | 23.75 | 0.25 | 23.75 |
F4 NW APARTMENT | 0.00 | 23.00 | 0.00 | 23.00 |
F4 SE APARTMENT | 0.25 | 38.25 | 0.25 | 38.25 |
F4 NE APARTMENT | 1.00 | 52.25 | 1.00 | 52.25 |
F4 N1 APARTMENT | 2.75 | 37.50 | 2.75 | 37.50 |
F4 N2 APARTMENT | 3.25 | 39.25 | 3.25 | 39.25 |
F4 S1 APARTMENT | 0.00 | 125.00 | 0.00 | 125.00 |
F4 S2 APARTMENT | 0.00 | 124.00 | 0.00 | 124.00 |
M SW APARTMENT | 0.75 | 23.00 | 0.75 | 23.00 |
M NW APARTMENT | 0.00 | 24.50 | 0.00 | 24.50 |
M SE APARTMENT | 0.25 | 32.25 | 0.25 | 32.25 |
M NE APARTMENT | 0.75 | 59.50 | 0.75 | 59.50 |
M N1 APARTMENT | 1.75 | 39.50 | 1.75 | 39.50 |
M N2 APARTMENT | 1.50 | 42.00 | 1.50 | 42.00 |
M S1 APARTMENT | 0.25 | 120.25 | 0.25 | 120.25 |
M S2 APARTMENT | 0.25 | 117.00 | 0.25 | 117.00 |
F6 SW APARTMENT | 0.00 | 23.75 | 0.00 | 23.75 |
F6 NW APARTMENT | 0.00 | 25.50 | 0.00 | 25.50 |
F6 SE APARTMENT | 1.00 | 30.25 | 1.00 | 30.25 |
F6 NE APARTMENT | 0.00 | 63.25 | 0.00 | 63.25 |
F6 N1 APARTMENT | 2.25 | 42.00 | 2.25 | 42.00 |
F6 N2 APARTMENT | 2.25 | 44.25 | 2.25 | 44.25 |
F6 S1 APARTMENT | 0.00 | 114.00 | 0.00 | 114.00 |
F6 S2 APARTMENT | 0.00 | 114.00 | 0.00 | 114.00 |
F7 SW APARTMENT | 0.00 | 23.75 | 0.00 | 23.75 |
F7 NW APARTMENT | 0.00 | 26.00 | 0.00 | 26.00 |
F7 SE APARTMENT | 0.25 | 28.25 | 0.25 | 28.25 |
F7 NE APARTMENT | 0.25 | 67.75 | 0.25 | 67.75 |
F7 N1 APARTMENT | 2.75 | 43.00 | 2.75 | 43.00 |
F7 N2 APARTMENT | 2.75 | 45.25 | 2.75 | 45.25 |
F7 S1 APARTMENT | 0.00 | 109.75 | 0.00 | 109.75 |
F7 S2 APARTMENT | 0.00 | 109.50 | 0.00 | 109.50 |
F8 SW APARTMENT | 0.00 | 23.75 | 0.00 | 23.75 |
F8 NW APARTMENT | 0.00 | 26.25 | 0.00 | 26.25 |
F8 SE APARTMENT | 0.50 | 26.75 | 0.50 | 26.75 |
F8 NE APARTMENT | 0.25 | 51.50 | 0.25 | 51.50 |
F8 N1 APARTMENT | 3.00 | 44.50 | 3.00 | 44.50 |
F8 N2 APARTMENT | 3.50 | 46.25 | 3.50 | 46.25 |
F8 S1 APARTMENT | 0.50 | 104.75 | 0.50 | 104.75 |
F8 S2 APARTMENT | 0.25 | 102.50 | 0.25 | 102.50 |
F9 SW APARTMENT | 0.25 | 20.25 | 0.25 | 20.25 |
F9 NW APARTMENT | 0.00 | 25.75 | 0.00 | 25.75 |
F9 SE APARTMENT | 0.50 | 18.50 | 0.50 | 18.50 |
F9 NE APARTMENT | 0.25 | 44.25 | 0.25 | 44.25 |
F9 N1 APARTMENT | 2.25 | 42.00 | 2.25 | 42.00 |
F9 N2 APARTMENT | 2.75 | 42.25 | 2.75 | 42.25 |
F9 S1 APARTMENT | 0.25 | 82.50 | 0.25 | 82.50 |
F9 S2 APARTMENT | 0.25 | 82.00 | 0.25 | 82.00 |
T SW APARTMENT | 0.00 | 12.00 | 0.00 | 12.00 |
T NW APARTMENT | 0.00 | 20.75 | 0.00 | 20.75 |
T SE APARTMENT | 0.00 | 12.50 | 0.00 | 12.50 |
T NE APARTMENT | 0.00 | 15.75 | 0.00 | 15.75 |
T N1 APARTMENT | 0.00 | 11.50 | 0.00 | 11.50 |
T N2 APARTMENT | 0.00 | 10.75 | 0.00 | 10.75 |
T S1 APARTMENT | 0.00 | 46.25 | 0.00 | 46.25 |
T S2 APARTMENT | 0.25 | 45.50 | 0.25 | 45.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 66.75 | 246.25 | 65.00 | 245.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.163 | 0.000 | 0.346 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.163 | 0.000 | 0.329 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.178 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.163 | 0.000 | 0.329 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.098 | 0.000 | 0.321 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.321 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.098 | 0.000 | 0.342 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.343 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.235 | 0.000 | 0.406 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.235 | 0.000 | 0.389 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.235 | 0.000 | 0.407 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.234 | 0.000 | 0.388 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.141 | 0.000 | 0.384 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.141 | 0.000 | 0.384 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.142 | 0.000 | 0.404 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.142 | 0.000 | 0.405 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.278 | 0.000 | 0.448 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.278 | 0.000 | 0.431 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.278 | 0.000 | 0.448 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.278 | 0.000 | 0.430 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.167 | 0.000 | 0.427 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.167 | 0.000 | 0.426 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.168 | 0.000 | 0.447 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.168 | 0.000 | 0.447 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.311 | 0.000 | 0.466 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.310 | 0.000 | 0.448 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.311 | 0.000 | 0.466 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.310 | 0.000 | 0.447 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.187 | 0.000 | 0.444 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.187 | 0.000 | 0.444 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.187 | 0.000 | 0.465 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.187 | 0.000 | 0.465 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.338 | 0.000 | 0.489 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.337 | 0.000 | 0.470 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.338 | 0.000 | 0.489 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.337 | 0.000 | 0.470 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.203 | 0.000 | 0.467 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.203 | 0.000 | 0.467 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.204 | 0.000 | 0.488 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.204 | 0.000 | 0.488 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.361 | 0.000 | 0.508 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.360 | 0.000 | 0.489 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.361 | 0.000 | 0.508 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.360 | 0.000 | 0.488 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.217 | 0.000 | 0.485 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.217 | 0.000 | 0.485 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.218 | 0.000 | 0.507 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.218 | 0.000 | 0.508 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.381 | 0.000 | 0.525 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.381 | 0.000 | 0.505 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.381 | 0.000 | 0.525 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.380 | 0.000 | 0.504 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.230 | 0.000 | 0.501 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.230 | 0.000 | 0.501 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.230 | 0.000 | 0.524 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.230 | 0.000 | 0.524 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.399 | 0.000 | 0.543 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.399 | 0.000 | 0.522 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.399 | 0.000 | 0.543 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.399 | 0.000 | 0.521 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.241 | 0.000 | 0.518 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.241 | 0.000 | 0.518 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.241 | 0.000 | 0.542 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.241 | 0.000 | 0.542 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.416 | 0.000 | 0.559 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.416 | 0.000 | 0.537 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.416 | 0.000 | 0.559 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.416 | 0.000 | 0.536 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.251 | 0.000 | 0.534 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.251 | 0.000 | 0.534 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.251 | 0.000 | 0.558 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.251 | 0.000 | 0.558 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.432 | 0.000 | 0.571 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.431 | 0.000 | 0.551 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.432 | 0.000 | 0.571 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.431 | 0.000 | 0.551 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.260 | 0.000 | 0.547 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.260 | 0.000 | 0.548 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.260 | 0.000 | 0.570 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.260 | 0.000 | 0.570 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.506 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 695.01 | 22038.65 | 01-JAN-00:15 | 22038.65 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1398.15 | 22699.89 | 08-FEB-03:15 | 90201.29 | 05-JUN-17:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
ElectricityPurchased:Plant | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
Cogeneration:ElectricityPurchased | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
ElectricityNet:Plant | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
Cogeneration:ElectricityNet | 3075.86 | 58861.67 | 08-FEB-03:15 | 165905.79 | 17-JUL-20:00 |
ExteriorLights:Electricity | 162.97 | 0.00 | 01-JAN-07:15 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.97 | 0.00 | 01-JAN-07:15 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 695.01 | 22038.65 | 01-JAN-00:15 | 22038.65 | 01-JAN-00:15 |
Cooling:Electricity | 636.60 | 0.00 | 01-JAN-00:15 | 66257.90 | 15-JUN-16:00 |
Heating:Electricity | 30.37 | 0.00 | 01-JAN-10:45 | 33976.03 | 10-APR-17:00 |
Electricity:Plant | 80.85 | 36.93 | 16-JAN-17:15 | 4389.62 | 20-JUL-16:15 |
HeatRejection:Electricity | 24.02 | 0.00 | 01-JAN-00:15 | 2556.10 | 20-JUL-16:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 56.84 | 36.93 | 16-JAN-17:15 | 1833.52 | 01-JAN-06:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1036.49 | 2357.00 | 01-JAN-00:15 | 158857.86 | 27-DEC-07:30 |
Gas:Plant | 1036.49 | 2357.00 | 01-JAN-00:15 | 158857.86 | 27-DEC-07:30 |
WaterSystems:Gas | 974.83 | 2357.00 | 01-JAN-00:15 | 77147.37 | 28-JAN-08:00 |
Water Heater:WaterSystems:Gas | 974.83 | 2357.00 | 01-JAN-00:15 | 77147.37 | 28-JAN-08:00 |
Heating:Gas | 61.66 | 0.00 | 01-JAN-00:15 | 109879.08 | 09-FEB-01:15 |
Boiler:Heating:Gas | 61.66 | 0.00 | 01-JAN-00:15 | 109879.08 | 09-FEB-01:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 2608.76 | 0.00 | 01-JAN-00:15 | 311129.53 | 20-JUL-16:15 |
PlantLoopCoolingDemand:HVAC | 2608.76 | 0.00 | 01-JAN-00:15 | 311129.53 | 20-JUL-16:15 |
CoolingCoils:PlantLoopCoolingDemand | 2608.76 | 0.00 | 01-JAN-00:15 | 311129.53 | 20-JUL-16:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6965.27 | 0.00 | 01-JAN-02:15 | 0.00 | 14-JUN-17:15 |
Water:Plant | 6965.27 | 0.00 | 01-JAN-02:15 | 0.00 | 14-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6965.27 | 0.00 | 01-JAN-02:15 | 0.00 | 14-JUN-17:15 |
MainsWater:Plant | 6965.27 | 0.00 | 01-JAN-02:15 | 0.00 | 14-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 2186.76 | 0.00 | 01-JAN-00:15 | 0.00 | 02-JUN-16:15 |
HeatRejection:MainsWater | 2186.76 | 0.00 | 01-JAN-00:15 | 0.00 | 02-JUN-16:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 838.04 | 368.60 | 06-AUG-01:15 | 136859.14 | 10-APR-17:00 |
PlantLoopHeatingDemand:Plant | 755.89 | 368.60 | 06-AUG-01:15 | 53564.12 | 01-FEB-07:45 |
WaterSystems:PlantLoopHeatingDemand | 755.89 | 368.60 | 06-AUG-01:15 | 53564.12 | 01-FEB-07:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4579.04 | 5769.98 | 02-MAY-02:00 | 436158.98 | 06-JUL-17:15 |
EnergyTransfer:Building | 1656.91 | 3561.05 | 06-MAR-22:15 | 180722.48 | 05-JUN-17:00 |
EnergyTransfer:Zone:G SW APARTMENT | 16.04 | 0.00 | 13-FEB-10:45 | 2584.55 | 29-SEP-15:15 |
Heating:EnergyTransfer | 107.26 | 0.00 | 21-JAN-11:00 | 144493.56 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.17 | 0.00 | 01-JAN-00:15 | 956.86 | 09-FEB-01:00 |
Cooling:EnergyTransfer | 1549.65 | 0.00 | 03-JAN-18:30 | 180722.48 | 05-JUN-17:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 14.87 | 0.00 | 01-JAN-14:00 | 2584.55 | 29-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 14.34 | 0.01 | 07-MAY-04:30 | 2426.27 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.77 | 0.00 | 01-JAN-09:00 | 1179.20 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 11.57 | 0.00 | 01-JAN-00:15 | 2426.27 | 09-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 26.74 | 0.01 | 06-OCT-05:00 | 3587.94 | 29-SEP-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 0.63 | 0.00 | 01-JAN-00:15 | 798.28 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 26.11 | 0.00 | 01-JAN-06:30 | 3587.94 | 29-SEP-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 14.14 | 0.03 | 10-FEB-23:15 | 1825.78 | 07-JUN-09:45 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.42 | 0.00 | 01-JAN-08:45 | 1186.09 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 11.72 | 0.00 | 01-JAN-00:15 | 1825.78 | 07-JUN-09:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.79 | 0.04 | 10-DEC-07:00 | 1353.06 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.20 | 0.00 | 01-JAN-00:15 | 1080.23 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 8.59 | 0.00 | 01-JAN-00:30 | 1353.06 | 09-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.79 | 0.05 | 08-FEB-14:30 | 1341.19 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 1080.93 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 8.60 | 0.00 | 01-JAN-00:30 | 1341.19 | 09-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 12.64 | 0.00 | 09-APR-23:15 | 1567.40 | 30-SEP-11:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 821.41 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 12.46 | 0.00 | 02-JAN-15:30 | 1567.40 | 30-SEP-11:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.97 | 0.01 | 25-MAY-00:30 | 1624.96 | 29-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 755.79 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 12.80 | 0.00 | 02-JAN-15:15 | 1624.96 | 29-SEP-13:00 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 24.28 | 0.04 | 13-APR-01:30 | 3149.17 | 29-SEP-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 970.07 | 26-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 23.69 | 0.00 | 01-JAN-14:00 | 3149.17 | 29-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 19.64 | 0.01 | 30-OCT-03:45 | 2944.99 | 09-JUN-17:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 2.06 | 0.00 | 01-JAN-00:15 | 1315.62 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 17.57 | 0.00 | 01-JAN-02:45 | 2944.99 | 09-JUN-17:15 |
EnergyTransfer:Zone:F2 SE APARTMENT | 26.34 | 0.06 | 22-MAR-01:45 | 2842.37 | 01-OCT-13:15 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.39 | 0.00 | 01-JAN-00:15 | 808.90 | 26-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 25.94 | 0.00 | 01-JAN-14:00 | 2842.37 | 01-OCT-13:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 19.66 | 0.01 | 29-JAN-12:15 | 2345.81 | 07-JUN-09:30 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 1.73 | 0.00 | 01-JAN-00:15 | 1328.10 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 17.92 | 0.00 | 01-JAN-00:30 | 2345.81 | 07-JUN-09:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 14.36 | 0.03 | 11-JAN-14:30 | 1717.36 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.60 | 0.00 | 01-JAN-00:15 | 1185.58 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 13.75 | 0.00 | 01-JAN-14:00 | 1717.36 | 09-JUN-17:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 14.37 | 0.13 | 24-OCT-13:45 | 1708.79 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.61 | 0.00 | 01-JAN-00:15 | 1186.67 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 13.76 | 0.00 | 01-JAN-14:00 | 1708.79 | 09-JUN-17:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 20.27 | 0.04 | 14-MAR-10:45 | 2017.71 | 28-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 702.80 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 20.17 | 0.00 | 02-JAN-16:00 | 2017.71 | 28-OCT-14:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 20.45 | 0.04 | 30-JAN-16:45 | 2026.96 | 28-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 659.03 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 20.34 | 0.00 | 01-JAN-15:15 | 2026.96 | 28-OCT-14:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 25.58 | 0.05 | 08-FEB-15:30 | 3150.81 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.54 | 0.00 | 01-JAN-00:15 | 1081.13 | 26-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 25.04 | 0.00 | 01-JAN-14:00 | 3150.81 | 29-SEP-15:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 20.53 | 0.01 | 14-NOV-08:45 | 2979.01 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 1.96 | 0.00 | 01-JAN-00:15 | 1458.17 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 18.58 | 0.00 | 01-JAN-03:00 | 2979.01 | 09-JUN-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 26.08 | 0.05 | 03-JAN-23:30 | 2771.02 | 01-OCT-10:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 1046.98 | 26-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 25.69 | 0.00 | 01-JAN-14:00 | 2771.02 | 01-OCT-10:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 20.60 | 0.00 | 15-FEB-15:45 | 2379.35 | 07-JUN-09:15 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 1.65 | 0.00 | 01-JAN-00:15 | 1472.16 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 18.95 | 0.00 | 01-JAN-03:30 | 2379.35 | 07-JUN-09:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 15.46 | 0.03 | 25-JAN-01:30 | 1754.87 | 09-JUN-17:45 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.52 | 0.00 | 01-JAN-00:15 | 1297.04 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 14.94 | 0.00 | 01-JAN-14:00 | 1754.87 | 09-JUN-17:45 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 15.47 | 0.12 | 03-FEB-13:30 | 1745.71 | 09-JUN-17:45 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.52 | 0.00 | 01-JAN-00:15 | 1300.54 | 31-JAN-17:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 14.95 | 0.00 | 01-JAN-14:00 | 1745.71 | 09-JUN-17:45 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 22.06 | 0.10 | 06-OCT-12:00 | 2059.72 | 28-OCT-14:15 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 916.82 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 21.96 | 0.00 | 01-JAN-15:00 | 2059.72 | 28-OCT-14:15 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 22.11 | 0.05 | 10-DEC-12:15 | 2066.36 | 28-OCT-14:15 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 894.82 | 06-APR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 22.01 | 0.00 | 01-JAN-15:00 | 2066.36 | 28-OCT-14:15 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 25.74 | 0.04 | 08-OCT-01:30 | 3161.87 | 22-OCT-15:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.58 | 0.00 | 01-JAN-00:15 | 1221.16 | 26-JAN-00:30 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 25.16 | 0.00 | 01-JAN-14:15 | 3161.87 | 22-OCT-15:00 |
EnergyTransfer:Zone:F4 NW APARTMENT | 20.85 | 0.01 | 10-OCT-00:15 | 2988.95 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 2.07 | 0.00 | 01-JAN-00:15 | 1637.52 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 18.78 | 0.00 | 01-JAN-03:00 | 2988.95 | 09-JUN-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 26.01 | 0.05 | 15-OCT-06:30 | 2777.03 | 01-OCT-10:30 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.44 | 0.00 | 01-JAN-00:15 | 1270.42 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 25.57 | 0.00 | 01-JAN-14:15 | 2777.03 | 01-OCT-10:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 20.89 | 0.02 | 05-JAN-15:15 | 2392.17 | 07-JUN-09:15 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 1.74 | 0.00 | 01-JAN-00:15 | 1648.70 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 19.16 | 0.00 | 01-JAN-03:45 | 2392.17 | 07-JUN-09:15 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 15.74 | 0.03 | 27-JAN-11:45 | 1773.47 | 09-JUN-17:45 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 1358.21 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 15.23 | 0.00 | 01-JAN-14:15 | 1773.47 | 09-JUN-17:45 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 15.75 | 0.00 | 14-NOV-00:45 | 1770.08 | 08-JUN-20:30 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 1356.71 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 15.24 | 0.00 | 01-JAN-14:15 | 1770.08 | 08-JUN-20:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 22.42 | 0.02 | 10-JAN-14:00 | 2082.40 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 1110.83 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 22.31 | 0.00 | 01-JAN-15:00 | 2082.40 | 03-NOV-14:30 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 22.44 | 0.13 | 06-OCT-11:45 | 2086.59 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 1109.65 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 22.33 | 0.00 | 01-JAN-15:00 | 2086.59 | 03-NOV-14:30 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 26.00 | 0.00 | 24-JAN-14:45 | 3184.75 | 22-OCT-15:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.66 | 0.00 | 01-JAN-00:15 | 1561.02 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 25.34 | 0.00 | 01-JAN-14:15 | 3184.75 | 22-OCT-15:00 |
EnergyTransfer:Zone:M NW APARTMENT | 21.35 | 0.01 | 17-NOV-10:30 | 3022.28 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.21 | 0.00 | 01-JAN-00:15 | 1794.59 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 19.13 | 0.00 | 01-JAN-02:45 | 3022.28 | 09-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 26.23 | 0.03 | 07-APR-00:30 | 2813.68 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.52 | 0.00 | 01-JAN-00:15 | 1625.97 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 25.71 | 0.00 | 01-JAN-14:15 | 2813.68 | 29-SEP-12:00 |
EnergyTransfer:Zone:M NE APARTMENT | 21.37 | 0.04 | 14-DEC-13:15 | 2426.95 | 07-JUN-09:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.87 | 0.00 | 01-JAN-00:15 | 1832.30 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 19.51 | 0.00 | 01-JAN-03:45 | 2426.95 | 07-JUN-09:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 16.17 | 0.02 | 30-JAN-16:15 | 1825.00 | 08-JUN-20:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.55 | 0.00 | 01-JAN-00:15 | 1657.01 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 15.62 | 0.00 | 01-JAN-14:15 | 1825.00 | 08-JUN-20:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 16.18 | 0.05 | 30-JAN-16:15 | 1817.25 | 08-JUN-20:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.55 | 0.00 | 01-JAN-00:15 | 1655.30 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 15.63 | 0.00 | 01-JAN-14:15 | 1817.25 | 08-JUN-20:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 22.75 | 0.17 | 13-MAR-18:30 | 2123.24 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 1427.62 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 22.62 | 0.00 | 01-JAN-14:15 | 2123.24 | 03-NOV-14:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 22.76 | 0.15 | 06-OCT-11:30 | 2127.06 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 1426.31 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 22.63 | 0.00 | 01-JAN-14:15 | 2127.06 | 03-NOV-14:30 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 25.16 | 0.01 | 26-APR-06:00 | 3144.48 | 22-OCT-15:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 0.82 | 0.00 | 01-JAN-00:15 | 1937.83 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 24.34 | 0.00 | 01-JAN-14:15 | 3144.48 | 22-OCT-15:00 |
EnergyTransfer:Zone:F6 NW APARTMENT | 21.15 | 0.02 | 12-DEC-15:45 | 2990.88 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 2.59 | 0.00 | 01-JAN-00:15 | 2144.14 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 18.55 | 0.00 | 01-JAN-02:45 | 2990.88 | 09-JUN-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 25.35 | 0.00 | 28-FEB-16:45 | 2797.91 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.66 | 0.00 | 01-JAN-00:15 | 1995.32 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 24.69 | 0.00 | 01-JAN-14:15 | 2797.91 | 29-SEP-12:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 21.13 | 0.01 | 08-OCT-00:15 | 2409.07 | 07-JUN-09:15 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 2.23 | 0.00 | 01-JAN-00:15 | 2192.66 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 18.90 | 0.00 | 01-JAN-01:00 | 2409.07 | 07-JUN-09:15 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 15.71 | 0.01 | 15-DEC-19:45 | 1988.89 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.70 | 0.00 | 01-JAN-00:15 | 1988.89 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 15.00 | 0.00 | 01-JAN-14:15 | 1811.58 | 09-MAY-20:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 15.72 | 0.01 | 17-AUG-09:30 | 1986.72 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.71 | 0.00 | 01-JAN-00:15 | 1986.72 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 15.01 | 0.00 | 01-JAN-14:15 | 1806.64 | 09-MAY-20:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 21.80 | 0.12 | 07-DEC-15:15 | 2097.94 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.16 | 0.00 | 01-JAN-00:15 | 1768.84 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 21.65 | 0.00 | 01-JAN-14:15 | 2097.94 | 03-NOV-14:30 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 21.81 | 0.18 | 13-MAR-12:15 | 2101.48 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.16 | 0.00 | 01-JAN-00:15 | 1767.28 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 21.66 | 0.00 | 01-JAN-14:15 | 2101.48 | 03-NOV-14:30 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 24.75 | 0.00 | 13-JAN-21:45 | 3124.55 | 22-OCT-15:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 2250.65 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 23.78 | 0.00 | 01-JAN-14:15 | 3124.55 | 22-OCT-15:00 |
EnergyTransfer:Zone:F7 NW APARTMENT | 21.23 | 0.01 | 01-NOV-04:45 | 2983.80 | 09-JUN-17:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 2.93 | 0.00 | 01-JAN-00:15 | 2450.58 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 18.30 | 0.00 | 01-JAN-02:45 | 2983.80 | 09-JUN-17:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 24.92 | 0.00 | 13-FEB-03:45 | 2802.95 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 0.80 | 0.00 | 01-JAN-00:15 | 2302.13 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 24.12 | 0.00 | 01-JAN-14:15 | 2802.95 | 29-SEP-12:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 21.17 | 0.00 | 02-JAN-19:45 | 2493.03 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 2.55 | 0.00 | 01-JAN-03:00 | 2493.03 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 18.62 | 0.00 | 01-JAN-00:15 | 2410.97 | 02-JUL-21:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 15.56 | 0.07 | 07-DEC-13:30 | 2264.49 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.84 | 0.00 | 01-JAN-00:15 | 2264.49 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 14.72 | 0.00 | 01-JAN-14:15 | 1820.86 | 09-MAY-20:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 15.57 | 0.05 | 21-DEC-02:00 | 2261.93 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.85 | 0.00 | 01-JAN-00:15 | 2261.93 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 14.73 | 0.00 | 01-JAN-14:15 | 1812.46 | 09-MAY-20:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 21.28 | 0.26 | 08-APR-00:30 | 2087.42 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 2051.91 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 21.10 | 0.00 | 01-JAN-14:15 | 2087.42 | 03-NOV-14:30 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 21.29 | 0.11 | 04-MAY-04:45 | 2081.76 | 03-NOV-14:30 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 2050.08 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 21.11 | 0.00 | 01-JAN-14:15 | 2081.76 | 03-NOV-14:30 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 24.56 | 0.03 | 07-OCT-09:30 | 3111.29 | 22-OCT-15:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 1.14 | 0.00 | 01-JAN-00:15 | 2522.95 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 23.43 | 0.00 | 01-JAN-14:15 | 3111.29 | 22-OCT-15:00 |
EnergyTransfer:Zone:F8 NW APARTMENT | 21.49 | 0.04 | 15-NOV-02:15 | 2995.92 | 06-JUL-16:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 3.25 | 0.00 | 01-JAN-00:15 | 2717.46 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 18.24 | 0.00 | 01-JAN-01:00 | 2995.92 | 06-JUL-16:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 24.72 | 0.02 | 15-FEB-16:15 | 2811.32 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 0.95 | 0.00 | 01-JAN-00:15 | 2569.76 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 23.77 | 0.00 | 01-JAN-14:15 | 2811.32 | 29-SEP-12:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 21.42 | 0.01 | 23-JAN-15:45 | 2755.09 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 2.86 | 0.00 | 01-JAN-08:15 | 2755.09 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 18.56 | 0.00 | 01-JAN-00:15 | 2474.77 | 02-JUL-21:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 15.60 | 0.01 | 14-DEC-00:45 | 2503.79 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.99 | 0.00 | 01-JAN-00:15 | 2503.79 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 14.61 | 0.00 | 01-JAN-14:00 | 1832.78 | 09-MAY-20:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 15.61 | 0.05 | 12-DEC-23:45 | 2500.94 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.99 | 0.00 | 01-JAN-00:15 | 2500.94 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 14.62 | 0.00 | 01-JAN-14:00 | 1824.82 | 08-JUN-20:30 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 20.95 | 0.19 | 08-OCT-09:45 | 2297.47 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 2297.47 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 20.74 | 0.00 | 01-JAN-14:15 | 2067.56 | 22-OCT-12:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 20.96 | 0.11 | 14-MAR-10:30 | 2295.43 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.22 | 0.00 | 01-JAN-00:15 | 2295.43 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 20.74 | 0.00 | 01-JAN-14:15 | 2072.43 | 22-OCT-12:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 24.99 | 0.00 | 12-DEC-21:45 | 3219.61 | 22-OCT-15:15 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 1.48 | 0.00 | 01-JAN-00:15 | 2740.94 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 23.51 | 0.00 | 01-JAN-03:00 | 3219.61 | 22-OCT-15:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 22.52 | 0.02 | 08-OCT-06:30 | 3120.85 | 06-JUL-16:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 3.80 | 0.00 | 01-JAN-00:30 | 2933.80 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 18.72 | 0.00 | 01-JAN-00:15 | 3120.85 | 06-JUL-16:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 25.07 | 0.01 | 30-NOV-19:30 | 2836.38 | 29-SEP-12:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 1.25 | 0.00 | 01-JAN-00:15 | 2783.19 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 23.82 | 0.00 | 01-JAN-14:15 | 2836.38 | 29-SEP-12:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 22.34 | 0.01 | 22-APR-03:15 | 2967.72 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 3.35 | 0.00 | 01-JAN-08:30 | 2967.72 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 18.99 | 0.00 | 01-JAN-00:15 | 2597.62 | 02-JUL-21:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 16.19 | 0.00 | 04-MAR-20:00 | 2698.04 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 1.26 | 0.00 | 01-JAN-00:15 | 2698.04 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 14.92 | 0.00 | 01-JAN-12:45 | 1941.29 | 08-JUN-20:30 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 16.20 | 0.03 | 21-MAR-15:15 | 2694.74 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 1.27 | 0.00 | 01-JAN-00:15 | 2694.74 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 14.93 | 0.00 | 01-JAN-12:45 | 1933.73 | 08-JUN-20:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 20.96 | 0.21 | 16-JAN-03:00 | 2493.29 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 2493.29 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 20.67 | 0.00 | 01-JAN-14:15 | 2147.04 | 22-OCT-13:00 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 20.97 | 0.12 | 07-DEC-15:00 | 2490.78 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.29 | 0.00 | 01-JAN-00:15 | 2490.78 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 20.69 | 0.00 | 01-JAN-14:15 | 2151.61 | 22-OCT-13:00 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 30.67 | 0.05 | 14-AUG-02:30 | 4108.38 | 01-OCT-14:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 4.62 | 0.00 | 01-JAN-08:45 | 3664.13 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 26.05 | 0.00 | 01-JAN-00:15 | 4108.38 | 01-OCT-14:15 |
EnergyTransfer:Zone:T NW APARTMENT | 28.09 | 0.09 | 05-OCT-05:15 | 3975.83 | 06-JUL-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 7.16 | 0.00 | 06-JAN-15:00 | 3772.25 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 20.93 | 0.00 | 01-JAN-00:15 | 3975.83 | 06-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 30.15 | 0.01 | 22-OCT-02:30 | 3764.67 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 4.19 | 0.00 | 01-JAN-08:30 | 3764.67 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 25.96 | 0.00 | 01-JAN-00:15 | 3710.56 | 01-OCT-12:15 |
EnergyTransfer:Zone:T NE APARTMENT | 27.31 | 0.01 | 28-DEC-12:45 | 3869.10 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 6.47 | 0.00 | 01-JAN-08:45 | 3869.10 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 20.83 | 0.00 | 01-JAN-00:15 | 3284.16 | 05-JUN-17:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 19.59 | 0.01 | 04-JAN-17:00 | 3487.75 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 3.24 | 0.00 | 01-JAN-08:45 | 3487.75 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.35 | 0.00 | 01-JAN-00:15 | 2560.58 | 17-JUN-18:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 19.61 | 0.00 | 11-MAR-08:45 | 3489.39 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 3.25 | 0.00 | 01-JAN-08:45 | 3489.39 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.36 | 0.00 | 01-JAN-00:15 | 2554.26 | 17-JUN-18:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 23.48 | 0.01 | 05-MAR-01:15 | 3369.23 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.51 | 0.00 | 01-JAN-00:15 | 3369.23 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 21.97 | 0.00 | 01-JAN-14:30 | 3059.85 | 22-OCT-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 23.51 | 0.01 | 12-NOV-00:15 | 3371.28 | 10-APR-17:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.52 | 0.00 | 01-JAN-00:15 | 3371.28 | 10-APR-17:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 22.00 | 0.00 | 01-JAN-14:30 | 3063.77 | 22-OCT-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 801.81 | 368.60 | 06-AUG-01:15 | 116382.92 | 26-JAN-07:15 |
WaterSystems:EnergyTransfer | 755.89 | 368.60 | 06-AUG-01:15 | 53558.64 | 01-FEB-07:45 |
sub cat:WaterSystems:EnergyTransfer | 755.89 | 368.60 | 06-AUG-01:15 | 53558.64 | 01-FEB-07:45 |
EnergyTransfer:HVAC | 2120.31 | 0.00 | 16-JAN-17:15 | 246828.89 | 20-JUL-16:15 |
CoolingCoils:EnergyTransfer | 2013.09 | 0.00 | 01-JAN-00:15 | 246828.89 | 20-JUL-16:15 |
HeatingCoils:EnergyTransfer | 107.22 | 0.00 | 01-JAN-10:45 | 133253.21 | 10-APR-17:00 |
PlantLoopHeatingDemand:HVAC | 82.15 | 0.00 | 01-JAN-10:45 | 101490.61 | 10-APR-17:00 |
HeatingCoils:PlantLoopHeatingDemand | 82.15 | 0.00 | 01-JAN-10:45 | 101490.61 | 10-APR-17:00 |
Boilers:EnergyTransfer | 45.92 | 0.00 | 01-JAN-00:15 | 82409.31 | 09-FEB-01:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.167 | -14.871 | 0.000 | 0.000 | 3.702 | 1.087 | 12.213 | 23.177 | 0.000 | 0.735 | 0.001 | 0.000 | -7.451 | 0.000 | -5.651 | -14.108 |
G NW APARTMENT | 2.769 | -11.569 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 13.146 | 0.000 | 0.732 | 0.000 | 0.000 | -7.441 | 0.000 | -4.993 | -9.698 |
OFFICE | 0.631 | -26.108 | 0.000 | 0.000 | 0.505 | 29.882 | 9.495 | 23.198 | 0.000 | 0.582 | 0.000 | 0.000 | -7.426 | 0.000 | -2.613 | -28.148 |
G NE APARTMENT | 2.419 | -11.719 | 0.000 | 0.000 | 3.768 | 1.087 | 12.213 | 13.030 | 0.000 | 0.731 | 0.000 | 0.000 | -7.041 | 0.000 | -4.958 | -9.530 |
G N1 APARTMENT | 1.197 | -8.591 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 4.706 | 0.000 | 0.502 | 0.000 | 0.000 | -4.522 | 0.000 | -3.771 | -6.591 |
G N2 APARTMENT | 1.193 | -8.596 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 4.704 | 0.000 | 0.502 | 0.000 | 0.000 | -4.518 | 0.000 | -3.771 | -6.585 |
G S1 APARTMENT | 0.178 | -12.459 | 0.000 | 0.000 | 3.700 | 1.087 | 12.213 | 14.886 | 0.000 | 0.503 | 0.000 | 0.000 | -4.510 | 0.000 | -4.496 | -11.101 |
G S2 APARTMENT | 0.175 | -12.797 | 0.000 | 0.000 | 3.694 | 1.087 | 12.213 | 14.866 | 0.000 | 0.503 | 0.000 | 0.000 | -4.525 | 0.000 | -4.544 | -10.672 |
F2 SW APARTMENT | 0.591 | -23.687 | 0.000 | 0.000 | 3.620 | 1.087 | 12.213 | 22.200 | 0.000 | 1.017 | 0.000 | 0.000 | -8.134 | 0.000 | -7.619 | -1.288 |
F2 NW APARTMENT | 2.064 | -17.574 | 0.000 | 0.000 | 3.703 | 1.087 | 12.213 | 12.487 | 0.000 | 1.011 | 0.000 | 0.000 | -8.028 | 0.000 | -6.818 | -0.145 |
F2 SE APARTMENT | 0.394 | -25.943 | 0.000 | 0.000 | 3.613 | 1.087 | 12.213 | 22.222 | 0.000 | 1.017 | 1.116 | 0.000 | -7.998 | 0.000 | -7.719 | -0.000 |
F2 NE APARTMENT | 1.734 | -17.923 | 0.000 | 0.000 | 3.719 | 1.087 | 12.213 | 12.392 | 0.000 | 1.010 | 0.104 | 0.000 | -7.574 | 0.000 | -6.761 | -0.000 |
F2 N1 APARTMENT | 0.604 | -13.751 | 0.000 | 0.000 | 3.713 | 1.087 | 12.213 | 4.378 | 0.000 | 0.680 | 1.165 | 0.000 | -4.940 | 0.000 | -5.150 | -0.000 |
F2 N2 APARTMENT | 0.606 | -13.761 | 0.000 | 0.000 | 3.714 | 1.087 | 12.213 | 4.377 | 0.000 | 0.680 | 1.168 | 0.000 | -4.935 | 0.000 | -5.148 | -0.000 |
F2 S1 APARTMENT | 0.103 | -20.169 | 0.000 | 0.000 | 3.602 | 1.087 | 12.213 | 14.268 | 0.000 | 0.683 | 0.000 | 0.000 | -4.937 | 0.000 | -6.051 | -0.799 |
F2 S2 APARTMENT | 0.103 | -20.343 | 0.000 | 0.000 | 3.601 | 1.087 | 12.213 | 14.262 | 0.000 | 0.684 | 0.000 | 0.000 | -4.943 | 0.000 | -6.065 | -0.598 |
F3 SW APARTMENT | 0.539 | -25.038 | 0.000 | 0.000 | 3.609 | 1.087 | 12.213 | 21.791 | 0.000 | 1.222 | 1.474 | 0.000 | -8.281 | 0.000 | -8.616 | -0.000 |
F3 NW APARTMENT | 1.956 | -18.576 | 0.000 | 0.000 | 3.694 | 1.087 | 12.213 | 12.236 | 0.000 | 1.214 | 2.140 | 0.000 | -8.191 | 0.000 | -7.772 | -0.000 |
F3 SE APARTMENT | 0.384 | -25.691 | 0.000 | 0.000 | 3.615 | 1.087 | 12.213 | 21.895 | 0.000 | 1.221 | 1.966 | 0.000 | -8.062 | 0.000 | -8.626 | -0.000 |
F3 NE APARTMENT | 1.649 | -18.954 | 0.000 | 0.000 | 3.709 | 1.087 | 12.213 | 12.157 | 0.000 | 1.212 | 2.361 | 0.000 | -7.724 | 0.000 | -7.710 | -0.000 |
F3 N1 APARTMENT | 0.519 | -14.936 | 0.000 | 0.000 | 3.697 | 1.087 | 12.213 | 4.278 | 0.000 | 0.823 | 3.256 | 0.000 | -5.069 | 0.000 | -5.869 | 0.000 |
F3 N2 APARTMENT | 0.521 | -14.945 | 0.000 | 0.000 | 3.698 | 1.087 | 12.213 | 4.277 | 0.000 | 0.823 | 3.257 | 0.000 | -5.064 | 0.000 | -5.867 | 0.000 |
F3 S1 APARTMENT | 0.096 | -21.960 | 0.000 | 0.000 | 3.585 | 1.087 | 12.213 | 14.007 | 0.000 | 0.826 | 1.993 | 0.000 | -5.046 | 0.000 | -6.799 | -0.000 |
F3 S2 APARTMENT | 0.096 | -22.012 | 0.000 | 0.000 | 3.584 | 1.087 | 12.213 | 14.004 | 0.000 | 0.827 | 2.051 | 0.000 | -5.046 | 0.000 | -6.804 | -0.000 |
F4 SW APARTMENT | 0.584 | -25.161 | 0.000 | 0.000 | 3.610 | 1.087 | 12.213 | 21.531 | 0.000 | 1.348 | 2.263 | 0.000 | -8.332 | 0.000 | -9.142 | -0.000 |
F4 NW APARTMENT | 2.066 | -18.779 | 0.000 | 0.000 | 3.692 | 1.087 | 12.213 | 12.085 | 0.000 | 1.339 | 2.851 | 0.000 | -8.261 | 0.000 | -8.292 | -0.000 |
F4 SE APARTMENT | 0.441 | -25.567 | 0.000 | 0.000 | 3.618 | 1.087 | 12.213 | 21.659 | 0.000 | 1.346 | 2.441 | 0.000 | -8.096 | 0.000 | -9.142 | -0.000 |
F4 NE APARTMENT | 1.737 | -19.157 | 0.000 | 0.000 | 3.708 | 1.087 | 12.213 | 12.018 | 0.000 | 1.335 | 3.074 | 0.000 | -7.787 | 0.000 | -8.227 | -0.000 |
F4 N1 APARTMENT | 0.513 | -15.230 | 0.000 | 0.000 | 3.692 | 1.087 | 12.213 | 4.225 | 0.000 | 0.904 | 3.934 | 0.000 | -5.127 | 0.000 | -6.210 | 0.000 |
F4 N2 APARTMENT | 0.515 | -15.238 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 4.223 | 0.000 | 0.903 | 3.934 | 0.000 | -5.122 | 0.000 | -6.208 | 0.000 |
F4 S1 APARTMENT | 0.108 | -22.311 | 0.000 | 0.000 | 3.582 | 1.087 | 12.213 | 13.841 | 0.000 | 0.907 | 2.792 | 0.000 | -5.086 | 0.000 | -7.134 | -0.000 |
F4 S2 APARTMENT | 0.108 | -22.329 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 13.840 | 0.000 | 0.907 | 2.812 | 0.000 | -5.084 | 0.000 | -7.136 | -0.000 |
M SW APARTMENT | 0.661 | -25.341 | 0.000 | 0.000 | 3.612 | 1.087 | 12.213 | 21.324 | 0.000 | 1.448 | 3.091 | 0.000 | -8.371 | 0.000 | -9.723 | -0.000 |
M NW APARTMENT | 2.213 | -19.134 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 11.966 | 0.000 | 1.439 | 3.676 | 0.000 | -8.314 | 0.000 | -8.839 | 0.000 |
M SE APARTMENT | 0.515 | -25.711 | 0.000 | 0.000 | 3.620 | 1.087 | 12.213 | 21.464 | 0.000 | 1.447 | 3.218 | 0.000 | -8.131 | 0.000 | -9.722 | -0.000 |
M NE APARTMENT | 1.867 | -19.507 | 0.000 | 0.000 | 3.708 | 1.087 | 12.213 | 11.905 | 0.000 | 1.434 | 3.900 | 0.000 | -7.834 | 0.000 | -8.772 | 0.000 |
M N1 APARTMENT | 0.554 | -15.619 | 0.000 | 0.000 | 3.691 | 1.087 | 12.213 | 4.182 | 0.000 | 0.968 | 4.700 | 0.000 | -5.170 | 0.000 | -6.606 | 0.000 |
M N2 APARTMENT | 0.555 | -15.627 | 0.000 | 0.000 | 3.692 | 1.087 | 12.213 | 4.181 | 0.000 | 0.967 | 4.700 | 0.000 | -5.165 | 0.000 | -6.603 | 0.000 |
M S1 APARTMENT | 0.129 | -22.622 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 13.710 | 0.000 | 0.972 | 3.598 | 0.000 | -5.114 | 0.000 | -7.555 | -0.001 |
M S2 APARTMENT | 0.129 | -22.633 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 13.709 | 0.000 | 0.972 | 3.610 | 0.000 | -5.112 | 0.000 | -7.557 | -0.000 |
F6 SW APARTMENT | 0.817 | -24.340 | 0.000 | 0.000 | 3.622 | 1.087 | 12.213 | 21.192 | 0.000 | 1.533 | 2.383 | 0.000 | -8.345 | 0.000 | -10.162 | -0.000 |
F6 NW APARTMENT | 2.593 | -18.553 | 0.000 | 0.000 | 3.703 | 1.087 | 12.213 | 11.909 | 0.000 | 1.522 | 3.031 | 0.000 | -8.288 | 0.000 | -9.218 | 0.000 |
F6 SE APARTMENT | 0.658 | -24.691 | 0.000 | 0.000 | 3.630 | 1.087 | 12.213 | 21.341 | 0.000 | 1.532 | 2.497 | 0.000 | -8.104 | 0.000 | -10.163 | -0.000 |
F6 NE APARTMENT | 2.234 | -18.896 | 0.000 | 0.000 | 3.717 | 1.087 | 12.213 | 11.854 | 0.000 | 1.518 | 3.236 | 0.000 | -7.809 | 0.000 | -9.154 | 0.000 |
F6 N1 APARTMENT | 0.702 | -15.003 | 0.000 | 0.000 | 3.701 | 1.087 | 12.213 | 4.171 | 0.000 | 1.021 | 4.115 | 0.000 | -5.153 | 0.000 | -6.853 | 0.000 |
F6 N2 APARTMENT | 0.705 | -15.014 | 0.000 | 0.000 | 3.703 | 1.087 | 12.213 | 4.170 | 0.000 | 1.021 | 4.115 | 0.000 | -5.148 | 0.000 | -6.851 | 0.000 |
F6 S1 APARTMENT | 0.155 | -21.648 | 0.000 | 0.000 | 3.592 | 1.087 | 12.213 | 13.627 | 0.000 | 1.027 | 2.907 | 0.000 | -5.100 | 0.000 | -7.860 | -0.000 |
F6 S2 APARTMENT | 0.156 | -21.657 | 0.000 | 0.000 | 3.593 | 1.087 | 12.213 | 13.625 | 0.000 | 1.027 | 2.917 | 0.000 | -5.098 | 0.000 | -7.862 | -0.000 |
F7 SW APARTMENT | 0.968 | -23.776 | 0.000 | 0.000 | 3.629 | 1.087 | 12.213 | 21.071 | 0.000 | 1.606 | 2.073 | 0.000 | -8.333 | 0.000 | -10.537 | -0.001 |
F7 NW APARTMENT | 2.926 | -18.303 | 0.000 | 0.000 | 3.710 | 1.087 | 12.213 | 11.851 | 0.000 | 1.595 | 2.757 | 0.000 | -8.279 | 0.000 | -9.556 | -0.000 |
F7 SE APARTMENT | 0.797 | -24.120 | 0.000 | 0.000 | 3.638 | 1.087 | 12.213 | 21.226 | 0.000 | 1.604 | 2.185 | 0.000 | -8.091 | 0.000 | -10.538 | -0.000 |
F7 NE APARTMENT | 2.550 | -18.622 | 0.000 | 0.000 | 3.724 | 1.087 | 12.213 | 11.800 | 0.000 | 1.589 | 2.951 | 0.000 | -7.800 | 0.000 | -9.492 | -0.000 |
F7 N1 APARTMENT | 0.843 | -14.715 | 0.000 | 0.000 | 3.709 | 1.087 | 12.213 | 4.156 | 0.000 | 1.067 | 3.860 | 0.000 | -5.147 | 0.000 | -7.072 | 0.000 |
F7 N2 APARTMENT | 0.845 | -14.725 | 0.000 | 0.000 | 3.710 | 1.087 | 12.213 | 4.155 | 0.000 | 1.067 | 3.862 | 0.000 | -5.142 | 0.000 | -7.069 | 0.000 |
F7 S1 APARTMENT | 0.183 | -21.097 | 0.000 | 0.000 | 3.600 | 1.087 | 12.213 | 13.550 | 0.000 | 1.073 | 2.600 | 0.000 | -5.093 | 0.000 | -8.115 | -0.000 |
F7 S2 APARTMENT | 0.184 | -21.107 | 0.000 | 0.000 | 3.600 | 1.087 | 12.213 | 13.548 | 0.000 | 1.074 | 2.610 | 0.000 | -5.091 | 0.000 | -8.117 | -0.000 |
F8 SW APARTMENT | 1.135 | -23.426 | 0.000 | 0.000 | 3.636 | 1.087 | 12.213 | 20.962 | 0.000 | 1.680 | 1.936 | 0.000 | -8.325 | 0.000 | -10.898 | -0.001 |
F8 NW APARTMENT | 3.249 | -18.243 | 0.000 | 0.000 | 3.716 | 1.087 | 12.213 | 11.794 | 0.000 | 1.668 | 2.687 | 0.000 | -8.279 | 0.000 | -9.890 | -0.000 |
F8 SE APARTMENT | 0.953 | -23.766 | 0.000 | 0.000 | 3.644 | 1.087 | 12.213 | 21.121 | 0.000 | 1.679 | 2.053 | 0.000 | -8.083 | 0.000 | -10.900 | -0.000 |
F8 NE APARTMENT | 2.857 | -18.562 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 11.748 | 0.000 | 1.664 | 2.891 | 0.000 | -7.799 | 0.000 | -9.827 | -0.000 |
F8 N1 APARTMENT | 0.992 | -14.611 | 0.000 | 0.000 | 3.714 | 1.087 | 12.213 | 4.140 | 0.000 | 1.117 | 3.794 | 0.000 | -5.146 | 0.000 | -7.299 | 0.000 |
F8 N2 APARTMENT | 0.993 | -14.621 | 0.000 | 0.000 | 3.715 | 1.087 | 12.213 | 4.138 | 0.000 | 1.116 | 3.796 | 0.000 | -5.142 | 0.000 | -7.297 | 0.000 |
F8 S1 APARTMENT | 0.216 | -20.735 | 0.000 | 0.000 | 3.607 | 1.087 | 12.213 | 13.481 | 0.000 | 1.125 | 2.461 | 0.000 | -5.087 | 0.000 | -8.367 | -0.000 |
F8 S2 APARTMENT | 0.216 | -20.744 | 0.000 | 0.000 | 3.607 | 1.087 | 12.213 | 13.480 | 0.000 | 1.125 | 2.472 | 0.000 | -5.085 | 0.000 | -8.369 | -0.000 |
F9 SW APARTMENT | 1.482 | -23.506 | 0.000 | 0.000 | 3.644 | 1.087 | 12.213 | 20.872 | 0.000 | 1.744 | 1.977 | 0.000 | -8.310 | 0.000 | -11.202 | -0.001 |
F9 NW APARTMENT | 3.799 | -18.719 | 0.000 | 0.000 | 3.719 | 1.087 | 12.213 | 11.738 | 0.000 | 1.731 | 2.919 | 0.000 | -8.287 | 0.000 | -10.199 | -0.000 |
F9 SE APARTMENT | 1.248 | -23.821 | 0.000 | 0.000 | 3.653 | 1.087 | 12.213 | 21.032 | 0.000 | 1.744 | 2.122 | 0.000 | -8.068 | 0.000 | -11.208 | -0.000 |
F9 NE APARTMENT | 3.347 | -18.995 | 0.000 | 0.000 | 3.732 | 1.087 | 12.213 | 11.695 | 0.000 | 1.728 | 3.144 | 0.000 | -7.808 | 0.000 | -10.142 | -0.000 |
F9 N1 APARTMENT | 1.265 | -14.922 | 0.000 | 0.000 | 3.718 | 1.087 | 12.213 | 4.121 | 0.000 | 1.159 | 4.019 | 0.000 | -5.149 | 0.000 | -7.510 | 0.000 |
F9 N2 APARTMENT | 1.267 | -14.933 | 0.000 | 0.000 | 3.719 | 1.087 | 12.213 | 4.119 | 0.000 | 1.159 | 4.023 | 0.000 | -5.144 | 0.000 | -7.509 | 0.000 |
F9 S1 APARTMENT | 0.286 | -20.674 | 0.000 | 0.000 | 3.617 | 1.087 | 12.213 | 13.426 | 0.000 | 1.169 | 2.519 | 0.000 | -5.074 | 0.000 | -8.568 | -0.000 |
F9 S2 APARTMENT | 0.286 | -20.687 | 0.000 | 0.000 | 3.618 | 1.087 | 12.213 | 13.424 | 0.000 | 1.169 | 2.534 | 0.000 | -5.072 | 0.000 | -8.571 | -0.000 |
T SW APARTMENT | 4.623 | -26.045 | 0.000 | 0.000 | 3.686 | 1.087 | 12.213 | 20.459 | 0.000 | 1.797 | 1.479 | 0.000 | -7.868 | 0.000 | -11.429 | -0.000 |
T NW APARTMENT | 7.156 | -20.933 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 11.354 | 0.000 | 1.783 | 2.213 | 0.000 | -7.963 | 0.000 | -10.638 | -0.000 |
T SE APARTMENT | 4.191 | -25.958 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 20.636 | 0.000 | 1.797 | 1.445 | 0.000 | -7.653 | 0.000 | -11.449 | -0.000 |
T NE APARTMENT | 6.472 | -20.834 | 0.000 | 0.000 | 3.743 | 1.087 | 12.213 | 11.370 | 0.000 | 1.784 | 2.306 | 0.000 | -7.546 | 0.000 | -10.594 | -0.001 |
T N1 APARTMENT | 3.242 | -16.347 | 0.000 | 0.000 | 3.730 | 1.087 | 12.213 | 3.973 | 0.000 | 1.195 | 3.679 | 0.000 | -4.948 | 0.000 | -7.825 | -0.000 |
T N2 APARTMENT | 3.254 | -16.360 | 0.000 | 0.000 | 3.731 | 1.087 | 12.213 | 3.969 | 0.000 | 1.195 | 3.682 | 0.000 | -4.942 | 0.000 | -7.829 | -0.000 |
T S1 APARTMENT | 1.511 | -21.973 | 0.000 | 0.000 | 3.666 | 1.087 | 12.213 | 13.208 | 0.000 | 1.207 | 2.626 | 0.000 | -4.831 | 0.000 | -8.713 | -0.000 |
T S2 APARTMENT | 1.516 | -21.996 | 0.000 | 0.000 | 3.666 | 1.087 | 12.213 | 13.204 | 0.000 | 1.207 | 2.648 | 0.000 | -4.828 | 0.000 | -8.717 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 5.528 | 0.000 | 5.420 | 2.622 | 0.000 | -1.759 | 0.000 | -28.252 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.536 | 0.000 | 0.085 | 0.000 | 0.000 | -1.040 | 0.000 | -0.721 | -17.299 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.473 | 0.000 | 0.097 | 0.000 | 0.000 | -1.078 | 0.000 | -0.887 | -17.045 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.434 | 0.000 | 0.105 | 0.000 | 0.000 | -1.095 | 0.000 | -1.005 | -16.878 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 2.391 | 0.000 | 0.098 | 0.000 | 0.000 | -1.122 | 0.000 | -1.155 | -33.092 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.395 | 0.000 | 0.121 | 0.000 | 0.000 | -1.099 | 0.000 | -1.162 | -16.695 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.388 | 0.000 | 0.130 | 0.000 | 0.000 | -1.091 | 0.000 | -1.212 | -16.655 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.377 | 0.000 | 0.135 | 0.000 | 0.000 | -1.089 | 0.000 | -1.264 | -16.598 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.365 | 0.000 | 0.135 | 0.000 | 0.000 | -1.091 | 0.000 | -1.313 | -16.535 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 2.273 | 0.000 | 0.081 | 0.000 | 0.000 | -1.064 | 0.000 | -1.428 | -24.453 |
Total Facility | 107.258 | -1549.618 | 0.000 | 0.000 | 290.516 | 296.560 | 982.450 | 1058.681 | 0.000 | 100.403 | 192.794 | 0.000 | -531.500 | 0.000 | -673.028 | -274.524 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-SEP-15:15 | 0.00 | -2584.63 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3487.59 | 0.00 | 30.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1498.22 |
G NW APARTMENT | 09-JUN-17:20 | 0.00 | -2427.13 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2490.23 | 0.00 | 194.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1075.99 |
OFFICE | 29-SEP-13:30 | 0.00 | -3587.36 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 2672.12 | 0.00 | 46.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2130.89 |
G NE APARTMENT | 07-JUN-09:45 | 0.00 | -1825.61 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2039.78 | 0.00 | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -867.93 |
G N1 APARTMENT | 09-JUN-17:20 | 0.00 | -1356.06 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 818.89 | 0.00 | 117.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -398.39 |
G N2 APARTMENT | 09-JUN-17:20 | 0.00 | -1343.89 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 819.18 | 0.00 | 117.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -410.84 |
G S1 APARTMENT | 30-SEP-11:15 | 0.00 | -1567.45 | 0.00 | 0.00 | 40.58 | 12.97 | 406.15 | 2662.21 | 0.00 | 41.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1596.33 |
G S2 APARTMENT | 29-SEP-13:00 | 0.00 | -1624.92 | 0.00 | 0.00 | 39.78 | 12.97 | 388.49 | 2470.71 | 0.00 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1308.62 |
F2 SW APARTMENT | 29-SEP-15:15 | 0.00 | -3149.28 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3432.71 | 0.00 | 43.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.84 |
F2 NW APARTMENT | 09-JUN-17:10 | 0.00 | -2945.39 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2415.32 | 0.00 | 319.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -607.58 |
F2 SE APARTMENT | 01-OCT-13:15 | 0.00 | -2842.13 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2907.40 | 0.00 | 58.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -559.88 |
F2 NE APARTMENT | 07-JUN-09:30 | 0.00 | -2345.54 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2058.94 | 0.00 | 254.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -427.56 |
F2 N1 APARTMENT | 09-JUN-17:20 | 0.00 | -1718.32 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 794.56 | 0.00 | 168.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.79 |
F2 N2 APARTMENT | 09-JUN-17:20 | 0.00 | -1710.16 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 794.71 | 0.00 | 168.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.10 |
F2 S1 APARTMENT | 28-OCT-14:30 | 0.00 | -2017.64 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2214.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.72 | -560.30 |
F2 S2 APARTMENT | 28-OCT-14:30 | 0.00 | -2026.89 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2214.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.62 | -550.99 |
F3 SW APARTMENT | 29-SEP-15:30 | 0.00 | -3151.04 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3270.80 | 0.00 | 52.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -737.72 |
F3 NW APARTMENT | 09-JUN-17:30 | 0.00 | -2980.45 | 0.00 | 0.00 | 141.63 | 87.56 | 588.62 | 2366.28 | 0.00 | 330.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.66 |
F3 SE APARTMENT | 01-OCT-10:30 | 0.00 | -2770.88 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3433.26 | 0.00 | 106.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1234.85 |
F3 NE APARTMENT | 07-JUN-09:15 | 0.00 | -2379.07 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2106.16 | 0.00 | 273.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -460.36 |
F3 N1 APARTMENT | 09-JUN-17:45 | 0.00 | -1755.10 | 0.00 | 0.00 | 141.54 | 87.56 | 588.62 | 766.70 | 0.00 | 171.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.79 |
F3 N2 APARTMENT | 09-JUN-17:45 | 0.00 | -1745.94 | 0.00 | 0.00 | 141.51 | 87.56 | 588.62 | 766.82 | 0.00 | 171.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10.01 |
F3 S1 APARTMENT | 28-OCT-14:15 | 0.00 | -2059.54 | 0.00 | 0.00 | 40.72 | 22.70 | 400.26 | 2294.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -153.66 | -545.47 |
F3 S2 APARTMENT | 28-OCT-14:15 | 0.00 | -2066.18 | 0.00 | 0.00 | 40.73 | 22.70 | 400.26 | 2294.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -153.05 | -539.43 |
F4 SW APARTMENT | 22-OCT-15:00 | 0.00 | -3161.66 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3311.16 | 0.00 | 202.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -816.05 |
F4 NW APARTMENT | 09-JUN-17:30 | 0.00 | -2990.05 | 0.00 | 0.00 | 141.44 | 87.56 | 588.62 | 2336.73 | 0.00 | 367.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -531.61 |
F4 SE APARTMENT | 01-OCT-10:30 | 0.00 | -2776.90 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3432.25 | 0.00 | 104.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1225.90 |
F4 NE APARTMENT | 07-JUN-09:15 | 0.00 | -2391.84 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2086.60 | 0.00 | 304.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -458.82 |
F4 N1 APARTMENT | 09-JUN-17:45 | 0.00 | -1773.69 | 0.00 | 0.00 | 141.38 | 87.56 | 588.62 | 760.76 | 0.00 | 190.87 | 4.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 08-JUN-20:30 | 0.00 | -1769.17 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 0.00 | 0.00 | 569.08 | 465.67 | 0.00 | -0.25 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2082.38 | 0.00 | 0.00 | 40.59 | 22.70 | 400.26 | 2338.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.12 | -618.45 |
F4 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2086.57 | 0.00 | 0.00 | 40.60 | 22.70 | 400.26 | 2338.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -100.30 | -615.23 |
M SW APARTMENT | 22-OCT-15:00 | 0.00 | -3184.55 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3299.56 | 0.00 | 204.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -783.26 |
M NW APARTMENT | 09-JUN-17:30 | 0.00 | -3023.18 | 0.00 | 0.00 | 141.33 | 87.56 | 588.62 | 2313.14 | 0.00 | 397.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -505.26 |
M SE APARTMENT | 29-SEP-12:00 | 0.00 | -2812.81 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2481.74 | 0.00 | 404.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.16 |
M NE APARTMENT | 07-JUN-09:15 | 0.00 | -2426.59 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2070.64 | 0.00 | 329.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -433.18 |
M N1 APARTMENT | 08-JUN-20:30 | 0.00 | -1824.07 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 0.00 | 0.00 | 606.22 | 483.38 | 0.00 | -0.21 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 08-JUN-20:30 | 0.00 | -1816.31 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 0.00 | 0.00 | 604.53 | 477.35 | 0.00 | -0.24 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2123.22 | 0.00 | 0.00 | 40.66 | 22.70 | 400.26 | 2333.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.95 | -571.70 |
M S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2127.04 | 0.00 | 0.00 | 40.68 | 22.70 | 400.26 | 2333.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.07 | -568.94 |
F6 SW APARTMENT | 22-OCT-15:00 | 0.00 | -3144.28 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3291.06 | 0.00 | 205.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -816.22 |
F6 NW APARTMENT | 09-JUN-17:20 | 0.00 | -2991.93 | 0.00 | 0.00 | 141.17 | 87.56 | 588.62 | 2295.17 | 0.00 | 422.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -543.15 |
F6 SE APARTMENT | 29-SEP-12:00 | 0.00 | -2797.02 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2460.23 | 0.00 | 424.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -547.62 |
F6 NE APARTMENT | 07-JUN-09:15 | 0.00 | -2408.69 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2059.15 | 0.00 | 350.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -461.14 |
F6 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1809.16 | 0.00 | 0.00 | 141.81 | 103.77 | 523.87 | 0.00 | 0.00 | 709.15 | 343.84 | 0.00 | -13.29 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1804.22 | 0.00 | 0.00 | 141.81 | 103.77 | 523.87 | 0.00 | 0.00 | 709.15 | 338.76 | 0.00 | -13.15 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2097.92 | 0.00 | 0.00 | 40.73 | 22.70 | 400.26 | 2330.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -102.00 | -593.83 |
F6 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2101.46 | 0.00 | 0.00 | 40.74 | 22.70 | 400.26 | 2330.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.18 | -591.24 |
F7 SW APARTMENT | 22-OCT-15:00 | 0.00 | -3124.35 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3282.90 | 0.00 | 206.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -828.80 |
F7 NW APARTMENT | 09-JUN-17:20 | 0.00 | -2984.97 | 0.00 | 0.00 | 141.06 | 87.56 | 588.62 | 2279.35 | 0.00 | 444.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -556.56 |
F7 SE APARTMENT | 29-SEP-12:00 | 0.00 | -2802.05 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2441.10 | 0.00 | 442.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -541.21 |
F7 NE APARTMENT | 02-JUL-21:00 | 0.00 | -2411.22 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 314.83 | 0.00 | 782.72 | 579.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 09-MAY-20:00 | 0.00 | -1818.40 | 0.00 | 0.00 | 141.81 | 103.77 | 523.87 | 0.00 | 0.00 | 737.30 | 324.06 | 0.00 | -12.41 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 09-MAY-20:00 | 0.00 | -1810.01 | 0.00 | 0.00 | 141.81 | 103.77 | 523.87 | 0.00 | 0.00 | 736.49 | 316.34 | 0.00 | -12.27 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 03-NOV-14:30 | 0.00 | -2087.41 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2326.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.07 | -600.03 |
F7 S2 APARTMENT | 03-NOV-14:30 | 0.00 | -2081.74 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2326.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -103.07 | -605.77 |
F8 SW APARTMENT | 22-OCT-15:00 | 0.00 | -3111.10 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3275.28 | 0.00 | 207.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.97 |
F8 NW APARTMENT | 06-JUL-16:30 | 0.00 | -2996.54 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2512.24 | 0.00 | 480.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -734.90 |
F8 SE APARTMENT | 29-SEP-12:00 | 0.00 | -2810.40 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2423.95 | 0.00 | 457.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -530.74 |
F8 NE APARTMENT | 02-JUL-21:00 | 0.00 | -2475.07 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 316.46 | 0.00 | 820.62 | 603.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 08-JUN-20:30 | 0.00 | -1831.39 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 1.39 | 0.00 | 679.98 | 415.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 08-JUN-20:30 | 0.00 | -1823.86 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 1.35 | 0.00 | 678.06 | 409.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 22-OCT-12:30 | 0.00 | -2067.88 | 0.00 | 0.00 | 40.68 | 12.97 | 388.49 | 2533.25 | 0.00 | 5.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -912.97 |
F8 S2 APARTMENT | 22-OCT-12:30 | 0.00 | -2072.74 | 0.00 | 0.00 | 40.67 | 12.97 | 388.49 | 2533.09 | 0.00 | 5.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -907.75 |
F9 SW APARTMENT | 22-OCT-15:15 | 0.00 | -3219.39 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3170.29 | 0.00 | 232.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -748.93 |
F9 NW APARTMENT | 06-JUL-16:30 | 0.00 | -3121.51 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2500.42 | 0.00 | 500.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -617.81 |
F9 SE APARTMENT | 29-SEP-12:00 | 0.00 | -2835.45 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2407.66 | 0.00 | 469.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.29 |
F9 NE APARTMENT | 02-JUL-21:00 | 0.00 | -2597.96 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 313.50 | 0.00 | 852.93 | 696.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 08-JUN-20:30 | 0.00 | -1940.30 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 0.00 | 0.00 | 703.97 | 502.36 | 0.00 | -0.70 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 08-JUN-20:30 | 0.00 | -1932.74 | 0.00 | 0.00 | 163.00 | 71.34 | 500.33 | 0.00 | 0.00 | 702.13 | 496.66 | 0.00 | -0.72 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2147.29 | 0.00 | 0.00 | 40.60 | 12.97 | 388.49 | 2531.40 | 0.00 | 44.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.03 |
F9 S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2151.86 | 0.00 | 0.00 | 40.59 | 12.97 | 388.49 | 2531.21 | 0.00 | 44.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -866.00 |
T SW APARTMENT | 01-OCT-14:15 | 0.00 | -4108.09 | 0.00 | 0.00 | 40.62 | 22.70 | 400.26 | 3468.31 | 0.00 | 223.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47.26 |
T NW APARTMENT | 06-JUL-16:30 | 0.00 | -3976.62 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2444.33 | 0.00 | 519.16 | 274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 01-OCT-12:15 | 0.00 | -3710.11 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2894.22 | 0.00 | 115.71 | 257.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 05-JUN-17:00 | 0.00 | -3283.69 | 0.00 | 0.00 | 83.17 | 64.86 | 588.62 | 1142.88 | 0.00 | 951.25 | 452.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 17-JUN-18:00 | 0.00 | -2560.76 | 0.00 | 0.00 | 141.36 | 87.56 | 588.62 | 782.89 | 0.00 | 308.70 | 651.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 17-JUN-18:00 | 0.00 | -2554.45 | 0.00 | 0.00 | 141.66 | 87.56 | 588.62 | 784.06 | 0.00 | 309.68 | 642.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 22-OCT-13:15 | 0.00 | -3060.08 | 0.00 | 0.00 | 40.63 | 12.97 | 382.60 | 2451.77 | 0.00 | 70.00 | 102.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 22-OCT-13:15 | 0.00 | -3064.00 | 0.00 | 0.00 | 40.63 | 12.97 | 382.60 | 2451.62 | 0.00 | 69.84 | 106.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUN-17:00 | 0.00 | -180704.53 | 0.00 | 0.00 | 6570.07 | 11327.17 | 47312.53 | 99215.70 | 0.00 | 53858.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37579.55 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-APR-14:00 | 1693.54 | 0.00 | 0.00 | 0.00 | 42.50 | 12.97 | 382.60 | 1415.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2202.03 | -1344.59 |
G NW APARTMENT | 06-APR-14:00 | 1525.64 | 0.00 | 0.00 | 0.00 | 43.96 | 12.97 | 382.60 | 963.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2198.59 | -730.26 |
OFFICE | 09-FEB-01:00 | 798.27 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 452.24 | 0.00 | -986.75 | 0.00 | -927.18 | 0.00 |
G NE APARTMENT | 11-MAR-15:55 | 1628.54 | 0.00 | 0.00 | 0.00 | 45.65 | 22.70 | 400.26 | 183.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1535.34 | -744.91 |
G N1 APARTMENT | 06-APR-13:55 | 1648.79 | 0.00 | 0.00 | 0.00 | 44.29 | 12.97 | 382.60 | 271.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2057.94 | -302.27 |
G N2 APARTMENT | 06-APR-13:55 | 1622.47 | 0.00 | 0.00 | 0.00 | 44.24 | 12.97 | 382.60 | 271.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2058.62 | -274.69 |
G S1 APARTMENT | 06-APR-14:00 | 1708.26 | 0.00 | 0.00 | 0.00 | 42.62 | 12.97 | 382.60 | 730.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2038.53 | -838.73 |
G S2 APARTMENT | 06-APR-14:00 | 1768.22 | 0.00 | 0.00 | 0.00 | 42.19 | 12.97 | 382.60 | 726.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2039.21 | -892.97 |
F2 SW APARTMENT | 06-APR-14:00 | 1253.87 | 0.00 | 0.00 | 0.00 | 40.83 | 12.97 | 382.60 | 1216.21 | 0.00 | 0.00 | 142.53 | 0.00 | 0.00 | 0.00 | -3049.02 | 0.00 |
F2 NW APARTMENT | 06-APR-14:00 | 1733.60 | 0.00 | 0.00 | 0.00 | 42.10 | 12.97 | 382.60 | 817.40 | 0.00 | 0.00 | 42.81 | 0.00 | 0.00 | 0.00 | -3031.48 | 0.00 |
F2 SE APARTMENT | 26-JAN-00:30 | 808.76 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 526.92 | 0.00 | -769.41 | 0.00 | -1027.31 | 0.00 |
F2 NE APARTMENT | 06-APR-14:00 | 1690.67 | 0.00 | 0.00 | 0.00 | 41.90 | 12.97 | 382.60 | 332.11 | 0.00 | 0.00 | 568.87 | 0.00 | 0.00 | 0.00 | -3029.12 | 0.00 |
F2 N1 APARTMENT | 06-APR-14:00 | 1829.13 | 0.00 | 0.00 | 0.00 | 41.91 | 12.97 | 382.60 | 207.96 | 0.00 | 0.00 | 322.62 | 0.00 | 0.00 | 0.00 | -2797.19 | 0.00 |
F2 N2 APARTMENT | 06-APR-14:00 | 1830.85 | 0.00 | 0.00 | 0.00 | 41.86 | 12.97 | 382.60 | 207.28 | 0.00 | 0.00 | 321.66 | 0.00 | 0.00 | 0.00 | -2797.22 | 0.00 |
F2 S1 APARTMENT | 06-APR-14:00 | 1672.51 | 0.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 617.41 | 0.00 | 0.00 | 75.50 | 0.00 | 0.00 | 0.00 | -2801.75 | 0.00 |
F2 S2 APARTMENT | 06-APR-14:00 | 1538.79 | 0.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 616.54 | 0.00 | 0.00 | 212.22 | 0.00 | 0.00 | 0.00 | -2803.87 | 0.00 |
F3 SW APARTMENT | 06-APR-14:00 | 1830.31 | 0.00 | 0.00 | 0.00 | 41.00 | 12.97 | 382.60 | 1146.55 | 0.00 | 0.00 | 140.35 | 0.00 | 0.00 | 0.00 | -3553.80 | 0.00 |
F3 NW APARTMENT | 06-APR-14:00 | 1875.94 | 0.00 | 0.00 | 0.00 | 42.13 | 12.97 | 382.60 | 768.26 | 0.00 | 0.00 | 468.88 | 0.00 | 0.00 | 0.00 | -3550.79 | 0.00 |
F3 SE APARTMENT | 06-APR-14:00 | 1778.09 | 0.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 682.87 | 0.00 | 0.00 | 654.53 | 0.00 | 0.00 | 0.00 | -3551.81 | 0.00 |
F3 NE APARTMENT | 06-APR-14:00 | 1826.70 | 0.00 | 0.00 | 0.00 | 41.92 | 12.97 | 382.60 | 304.69 | 0.00 | 0.00 | 979.86 | 0.00 | 0.00 | 0.00 | -3548.75 | 0.00 |
F3 N1 APARTMENT | 06-APR-14:00 | 1962.07 | 0.00 | 0.00 | 0.00 | 41.63 | 12.97 | 382.60 | 188.78 | 0.00 | 0.00 | 686.21 | 0.00 | 0.00 | 0.00 | -3274.27 | 0.00 |
F3 N2 APARTMENT | 06-APR-14:00 | 1962.20 | 0.00 | 0.00 | 0.00 | 41.58 | 12.97 | 382.60 | 188.12 | 0.00 | 0.00 | 686.83 | 0.00 | 0.00 | 0.00 | -3274.29 | 0.00 |
F3 S1 APARTMENT | 06-APR-14:00 | 1884.03 | 0.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 577.60 | 0.00 | 0.00 | 377.48 | 0.00 | 0.00 | 0.00 | -3275.44 | 0.00 |
F3 S2 APARTMENT | 06-APR-14:00 | 1865.35 | 0.00 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 577.13 | 0.00 | 0.00 | 396.67 | 0.00 | 0.00 | 0.00 | -3275.48 | 0.00 |
F4 SW APARTMENT | 06-APR-14:15 | 1737.85 | 0.00 | 0.00 | 0.00 | 41.40 | 22.70 | 400.26 | 1176.48 | 0.00 | 0.00 | 221.17 | 0.00 | 0.00 | 0.00 | -3599.86 | 0.00 |
F4 NW APARTMENT | 06-APR-14:15 | 1794.58 | 0.00 | 0.00 | 0.00 | 42.43 | 22.70 | 400.26 | 826.40 | 0.00 | 0.00 | 510.72 | 0.00 | 0.00 | 0.00 | -3597.08 | 0.00 |
F4 SE APARTMENT | 06-APR-14:15 | 1702.72 | 0.00 | 0.00 | 0.00 | 41.27 | 22.70 | 400.26 | 621.59 | 0.00 | 0.00 | 809.16 | 0.00 | 0.00 | 0.00 | -3597.69 | 0.00 |
F4 NE APARTMENT | 06-APR-14:15 | 1741.09 | 0.00 | 0.00 | 0.00 | 42.38 | 22.70 | 400.26 | 271.57 | 0.00 | 0.00 | 1116.88 | 0.00 | 0.00 | 0.00 | -3594.88 | 0.00 |
F4 N1 APARTMENT | 06-APR-14:15 | 1892.82 | 0.00 | 0.00 | 0.00 | 41.87 | 22.70 | 400.26 | 167.01 | 0.00 | 0.00 | 791.84 | 0.00 | 0.00 | 0.00 | -3316.49 | 0.00 |
F4 N2 APARTMENT | 06-APR-14:15 | 1892.25 | 0.00 | 0.00 | 0.00 | 41.82 | 22.70 | 400.26 | 166.40 | 0.00 | 0.00 | 793.09 | 0.00 | 0.00 | 0.00 | -3316.51 | 0.00 |
F4 S1 APARTMENT | 06-APR-14:15 | 1905.24 | 0.00 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 525.49 | 0.00 | 0.00 | 423.42 | 0.00 | 0.00 | 0.00 | -3317.85 | 0.00 |
F4 S2 APARTMENT | 06-APR-14:15 | 1887.93 | 0.00 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 525.08 | 0.00 | 0.00 | 441.16 | 0.00 | 0.00 | 0.00 | -3317.88 | 0.00 |
M SW APARTMENT | 06-APR-14:15 | 1852.46 | 0.00 | 0.00 | 0.00 | 41.75 | 22.70 | 400.26 | 1148.37 | 0.00 | 0.00 | 438.45 | 0.00 | 0.00 | 0.00 | -3904.00 | 0.00 |
M NW APARTMENT | 06-APR-14:10 | 2014.86 | 0.00 | 0.00 | 0.00 | 42.72 | 22.70 | 400.26 | 807.26 | 0.00 | 0.00 | 667.35 | 0.00 | 0.00 | 0.00 | -3955.15 | 0.00 |
M SE APARTMENT | 06-APR-14:15 | 1813.81 | 0.00 | 0.00 | 0.00 | 41.62 | 22.70 | 400.26 | 604.56 | 0.00 | 0.00 | 1019.18 | 0.00 | 0.00 | 0.00 | -3902.13 | 0.00 |
M NE APARTMENT | 06-APR-14:10 | 1984.04 | 0.00 | 0.00 | 0.00 | 42.66 | 22.70 | 400.26 | 263.36 | 0.00 | 0.00 | 1232.31 | 0.00 | 0.00 | 0.00 | -3945.34 | 0.00 |
M N1 APARTMENT | 06-APR-14:15 | 1990.36 | 0.00 | 0.00 | 0.00 | 42.03 | 22.70 | 400.26 | 161.10 | 0.00 | 0.00 | 980.10 | 0.00 | 0.00 | 0.00 | -3596.54 | 0.00 |
M N2 APARTMENT | 06-APR-14:15 | 1989.21 | 0.00 | 0.00 | 0.00 | 41.98 | 22.70 | 400.26 | 160.50 | 0.00 | 0.00 | 981.91 | 0.00 | 0.00 | 0.00 | -3596.56 | 0.00 |
M S1 APARTMENT | 06-APR-14:15 | 1995.32 | 0.00 | 0.00 | 0.00 | 40.94 | 22.70 | 400.26 | 510.13 | 0.00 | 0.00 | 628.52 | 0.00 | 0.00 | 0.00 | -3597.87 | 0.00 |
M S2 APARTMENT | 06-APR-14:15 | 1995.97 | 0.00 | 0.00 | 0.00 | 40.88 | 22.70 | 400.26 | 509.45 | 0.00 | 0.00 | 628.68 | 0.00 | 0.00 | 0.00 | -3597.95 | 0.00 |
F6 SW APARTMENT | 06-APR-14:10 | 1986.08 | 0.00 | 0.00 | 0.00 | 42.27 | 22.70 | 400.26 | 1131.54 | 0.00 | 0.00 | 648.56 | 0.00 | 0.00 | 0.00 | -4231.41 | 0.00 |
F6 NW APARTMENT | 06-APR-14:10 | 2660.87 | 0.00 | 0.00 | 0.00 | 43.19 | 22.70 | 400.26 | 796.78 | 0.00 | 0.00 | 281.48 | 0.00 | 0.00 | 0.00 | -4205.27 | 0.00 |
F6 SE APARTMENT | 10-APR-17:00 | 1995.29 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 1966.99 | 0.00 | -144.10 | 0.00 | -4570.29 | 0.00 |
F6 NE APARTMENT | 06-APR-14:10 | 2647.50 | 0.00 | 0.00 | 0.00 | 43.13 | 22.70 | 400.26 | 261.33 | 0.00 | 0.00 | 822.73 | 0.00 | 0.00 | 0.00 | -4197.65 | 0.00 |
F6 N1 APARTMENT | 06-APR-14:10 | 2563.80 | 0.00 | 0.00 | 0.00 | 42.42 | 22.70 | 400.26 | 159.27 | 0.00 | 0.00 | 686.16 | 0.00 | 0.00 | 0.00 | -3874.61 | 0.00 |
F6 N2 APARTMENT | 06-APR-14:10 | 2533.53 | 0.00 | 0.00 | 0.00 | 42.37 | 22.70 | 400.26 | 158.69 | 0.00 | 0.00 | 717.69 | 0.00 | 0.00 | 0.00 | -3875.24 | 0.00 |
F6 S1 APARTMENT | 06-APR-14:15 | 2072.67 | 0.00 | 0.00 | 0.00 | 41.38 | 22.70 | 400.26 | 501.57 | 0.00 | 0.00 | 803.90 | 0.00 | 0.00 | 0.00 | -3842.48 | 0.00 |
F6 S2 APARTMENT | 06-APR-14:15 | 2073.22 | 0.00 | 0.00 | 0.00 | 41.33 | 22.70 | 400.26 | 500.90 | 0.00 | 0.00 | 804.15 | 0.00 | 0.00 | 0.00 | -3842.56 | 0.00 |
F7 SW APARTMENT | 06-APR-14:10 | 2533.32 | 0.00 | 0.00 | 0.00 | 42.64 | 22.70 | 400.26 | 1116.72 | 0.00 | 0.00 | 342.08 | 0.00 | 0.00 | 0.00 | -4457.71 | 0.00 |
F7 NW APARTMENT | 06-APR-14:10 | 3188.09 | 0.00 | 0.00 | 0.00 | 43.52 | 22.70 | 400.26 | 787.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4432.17 | -9.57 |
F7 SE APARTMENT | 06-APR-14:10 | 2471.08 | 0.00 | 0.00 | 0.00 | 42.51 | 22.70 | 400.26 | 588.10 | 0.00 | 0.00 | 928.07 | 0.00 | 0.00 | 0.00 | -4452.73 | 0.00 |
F7 NE APARTMENT | 06-APR-14:10 | 3186.97 | 0.00 | 0.00 | 0.00 | 43.47 | 22.70 | 400.26 | 258.56 | 0.00 | 0.00 | 514.39 | 0.00 | 0.00 | 0.00 | -4426.35 | 0.00 |
F7 N1 APARTMENT | 06-APR-14:10 | 3056.41 | 0.00 | 0.00 | 0.00 | 42.69 | 22.70 | 400.26 | 157.06 | 0.00 | 0.00 | 408.21 | 0.00 | 0.00 | 0.00 | -4087.32 | 0.00 |
F7 N2 APARTMENT | 06-APR-14:10 | 3027.00 | 0.00 | 0.00 | 0.00 | 42.64 | 22.70 | 400.26 | 156.49 | 0.00 | 0.00 | 438.88 | 0.00 | 0.00 | 0.00 | -4087.96 | 0.00 |
F7 S1 APARTMENT | 06-APR-14:10 | 2369.79 | 0.00 | 0.00 | 0.00 | 41.69 | 22.70 | 400.26 | 493.86 | 0.00 | 0.00 | 777.90 | 0.00 | 0.00 | 0.00 | -4106.21 | 0.00 |
F7 S2 APARTMENT | 06-APR-14:10 | 2336.48 | 0.00 | 0.00 | 0.00 | 41.64 | 22.70 | 400.26 | 493.20 | 0.00 | 0.00 | 812.95 | 0.00 | 0.00 | 0.00 | -4107.23 | 0.00 |
F8 SW APARTMENT | 06-APR-14:10 | 3010.50 | 0.00 | 0.00 | 0.00 | 42.95 | 22.70 | 400.26 | 1103.98 | 0.00 | 0.00 | 85.32 | 0.00 | 0.00 | 0.00 | -4665.71 | 0.00 |
F8 NW APARTMENT | 06-APR-14:10 | 3648.38 | 0.00 | 0.00 | 0.00 | 43.80 | 22.70 | 400.26 | 778.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4640.53 | -253.40 |
F8 SE APARTMENT | 06-APR-14:10 | 2954.17 | 0.00 | 0.00 | 0.00 | 42.81 | 22.70 | 400.26 | 581.00 | 0.00 | 0.00 | 661.10 | 0.00 | 0.00 | 0.00 | -4662.05 | 0.00 |
F8 NE APARTMENT | 06-APR-14:10 | 3653.37 | 0.00 | 0.00 | 0.00 | 43.74 | 22.70 | 400.26 | 255.80 | 0.00 | 0.00 | 260.59 | 0.00 | 0.00 | 0.00 | -4636.47 | 0.00 |
F8 N1 APARTMENT | 06-APR-14:10 | 3483.56 | 0.00 | 0.00 | 0.00 | 42.90 | 22.70 | 400.26 | 154.91 | 0.00 | 0.00 | 178.46 | 0.00 | 0.00 | 0.00 | -4282.79 | 0.00 |
F8 N2 APARTMENT | 06-APR-14:10 | 3454.53 | 0.00 | 0.00 | 0.00 | 42.86 | 22.70 | 400.26 | 154.34 | 0.00 | 0.00 | 208.78 | 0.00 | 0.00 | 0.00 | -4283.46 | 0.00 |
F8 S1 APARTMENT | 06-APR-14:10 | 2815.53 | 0.00 | 0.00 | 0.00 | 41.93 | 22.70 | 400.26 | 487.13 | 0.00 | 0.00 | 533.68 | 0.00 | 0.00 | 0.00 | -4301.24 | 0.00 |
F8 S2 APARTMENT | 06-APR-14:10 | 2782.53 | 0.00 | 0.00 | 0.00 | 41.88 | 22.70 | 400.26 | 486.47 | 0.00 | 0.00 | 568.40 | 0.00 | 0.00 | 0.00 | -4302.25 | 0.00 |
F9 SW APARTMENT | 06-APR-14:10 | 3472.26 | 0.00 | 0.00 | 0.00 | 43.25 | 22.70 | 400.26 | 1094.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4859.03 | -173.78 |
F9 NW APARTMENT | 06-APR-14:10 | 3956.90 | 0.00 | 0.00 | 0.00 | 44.08 | 22.70 | 400.26 | 773.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4838.51 | -358.74 |
F9 SE APARTMENT | 06-APR-14:10 | 3403.37 | 0.00 | 0.00 | 0.00 | 43.09 | 22.70 | 400.26 | 575.50 | 0.00 | 0.00 | 412.11 | 0.00 | 0.00 | 0.00 | -4857.03 | 0.00 |
F9 NE APARTMENT | 06-APR-14:10 | 3971.54 | 0.00 | 0.00 | 0.00 | 44.00 | 22.70 | 400.26 | 254.44 | 0.00 | 0.00 | 142.18 | 0.00 | 0.00 | 0.00 | -4835.12 | 0.00 |
F9 N1 APARTMENT | 06-APR-14:10 | 3906.04 | 0.00 | 0.00 | 0.00 | 43.12 | 22.70 | 400.26 | 153.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4464.24 | -61.78 |
F9 N2 APARTMENT | 06-APR-14:10 | 3873.84 | 0.00 | 0.00 | 0.00 | 43.07 | 22.70 | 400.26 | 153.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4465.07 | -28.06 |
F9 S1 APARTMENT | 06-APR-14:10 | 3243.70 | 0.00 | 0.00 | 0.00 | 42.17 | 22.70 | 400.26 | 481.94 | 0.00 | 0.00 | 292.18 | 0.00 | 0.00 | 0.00 | -4482.95 | 0.00 |
F9 S2 APARTMENT | 06-APR-14:10 | 3207.26 | 0.00 | 0.00 | 0.00 | 42.11 | 22.70 | 400.26 | 481.20 | 0.00 | 0.00 | 330.53 | 0.00 | 0.00 | 0.00 | -4484.07 | 0.00 |
T SW APARTMENT | 10-APR-16:53 | 3664.08 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 141.99 | 0.00 | 0.00 | 967.31 | 0.00 | 0.00 | 0.00 | -5525.49 | 0.00 |
T NW APARTMENT | 06-APR-14:25 | 3902.34 | 0.00 | 0.00 | 0.00 | 44.12 | 22.70 | 400.26 | 846.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4546.99 | -669.33 |
T SE APARTMENT | 10-APR-16:53 | 3764.62 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 1142.32 | 0.00 | -133.55 | 0.00 | -5525.49 | 0.00 |
T NE APARTMENT | 06-APR-14:25 | 3929.85 | 0.00 | 0.00 | 0.00 | 44.51 | 22.70 | 400.26 | 238.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4541.22 | -94.52 |
T N1 APARTMENT | 06-APR-14:25 | 3921.70 | 0.00 | 0.00 | 0.00 | 43.27 | 22.70 | 400.26 | 142.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4195.52 | -334.49 |
T N2 APARTMENT | 06-APR-14:25 | 3896.28 | 0.00 | 0.00 | 0.00 | 43.23 | 22.70 | 400.26 | 141.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4196.61 | -307.31 |
T S1 APARTMENT | 10-APR-16:53 | 3369.18 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 1043.50 | 0.00 | -85.20 | 0.00 | -5079.59 | 0.00 |
T S2 APARTMENT | 10-APR-16:53 | 3371.23 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 1041.40 | 0.00 | -85.14 | 0.00 | -5079.59 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-APR-17:00 | 145375.50 | 0.00 | 0.00 | 0.00 | 7787.67 | 11327.17 | 47312.53 | 3507.54 | 0.00 | 0.00 | 119381.12 | 0.00 | -6016.70 | 0.00 | -328674.84 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sec1.1A-General InformationData | |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 65.00 |
Number of hours cooling loads not met | 245.00 |
Number of hours not met | 310.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.97 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 30.37 | 0.00 | 61.66 | 82687.13 | 0.00 | 0.00 |
Space Cooling | 636.60 | 63390.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56.84 | 1833.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 24.02 | 2346.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 695.01 | 22038.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 974.83 | 76170.72 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3075.86 | 1036.49 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 3075.86 |
Natural Gas | 0.00 | 1036.49 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4112.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 3.88 |
Space Cooling | 81.24 |
Fans-Interior | 88.69 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 35.73 |
Subtotal | 392.50 |
Natural Gas [MJ/m2] | |
Space Heating | 7.87 |
Service Water Heating | 124.40 |
Miscellaneous | -0.00 |
Subtotal | 132.26 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.21 |
Space Heating | 2.24 |
Space Cooling | 15.48 |
Fans-Interior | 16.90 |
Service Water Heating | 23.70 |
Receptacle Equipment | 27.66 |
Miscellaneous | 6.81 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.244365 |
G NW APARTMENT DIRECT AIR | 0.241788 |
OFFICE DIRECT AIR | 0.358063 |
G NE APARTMENT DIRECT AIR | 0.186792 |
G N1 APARTMENT DIRECT AIR | 0.137045 |
G N2 APARTMENT DIRECT AIR | 0.135840 |
G S1 APARTMENT DIRECT AIR | 0.138200 |
G S2 APARTMENT DIRECT AIR | 0.144687 |
F2 SW APARTMENT DIRECT AIR | 0.300885 |
F2 NW APARTMENT DIRECT AIR | 0.296853 |
F2 SE APARTMENT DIRECT AIR | 0.278016 |
F2 NE APARTMENT DIRECT AIR | 0.235682 |
F2 N1 APARTMENT DIRECT AIR | 0.172003 |
F2 N2 APARTMENT DIRECT AIR | 0.171029 |
F2 S1 APARTMENT DIRECT AIR | 0.175253 |
F2 S2 APARTMENT DIRECT AIR | 0.177274 |
F3 SW APARTMENT DIRECT AIR | 0.302868 |
F3 NW APARTMENT DIRECT AIR | 0.299210 |
F3 SE APARTMENT DIRECT AIR | 0.258984 |
F3 NE APARTMENT DIRECT AIR | 0.239366 |
F3 N1 APARTMENT DIRECT AIR | 0.175073 |
F3 N2 APARTMENT DIRECT AIR | 0.174115 |
F3 S1 APARTMENT DIRECT AIR | 0.178665 |
F3 S2 APARTMENT DIRECT AIR | 0.179367 |
F4 SW APARTMENT DIRECT AIR | 0.305293 |
F4 NW APARTMENT DIRECT AIR | 0.301585 |
F4 SE APARTMENT DIRECT AIR | 0.259986 |
F4 NE APARTMENT DIRECT AIR | 0.241660 |
F4 N1 APARTMENT DIRECT AIR | 0.177395 |
F4 N2 APARTMENT DIRECT AIR | 0.176449 |
F4 S1 APARTMENT DIRECT AIR | 0.181006 |
F4 S2 APARTMENT DIRECT AIR | 0.181513 |
M SW APARTMENT DIRECT AIR | 0.309726 |
M NW APARTMENT DIRECT AIR | 0.306020 |
M SE APARTMENT DIRECT AIR | 0.264811 |
M NE APARTMENT DIRECT AIR | 0.245977 |
M N1 APARTMENT DIRECT AIR | 0.181630 |
M N2 APARTMENT DIRECT AIR | 0.180694 |
M S1 APARTMENT DIRECT AIR | 0.185193 |
M S2 APARTMENT DIRECT AIR | 0.185673 |
F6 SW APARTMENT DIRECT AIR | 0.307669 |
F6 NW APARTMENT DIRECT AIR | 0.303807 |
F6 SE APARTMENT DIRECT AIR | 0.263385 |
F6 NE APARTMENT DIRECT AIR | 0.243878 |
F6 N1 APARTMENT DIRECT AIR | 0.179498 |
F6 N2 APARTMENT DIRECT AIR | 0.178576 |
F6 S1 APARTMENT DIRECT AIR | 0.183135 |
F6 S2 APARTMENT DIRECT AIR | 0.183612 |
F7 SW APARTMENT DIRECT AIR | 0.307801 |
F7 NW APARTMENT DIRECT AIR | 0.303895 |
F7 SE APARTMENT DIRECT AIR | 0.264060 |
F7 NE APARTMENT DIRECT AIR | 0.244039 |
F7 N1 APARTMENT DIRECT AIR | 0.179560 |
F7 N2 APARTMENT DIRECT AIR | 0.178647 |
F7 S1 APARTMENT DIRECT AIR | 0.183193 |
F7 S2 APARTMENT DIRECT AIR | 0.183670 |
F8 SW APARTMENT DIRECT AIR | 0.309410 |
F8 NW APARTMENT DIRECT AIR | 0.305470 |
F8 SE APARTMENT DIRECT AIR | 0.266078 |
F8 NE APARTMENT DIRECT AIR | 0.246051 |
F8 N1 APARTMENT DIRECT AIR | 0.181098 |
F8 N2 APARTMENT DIRECT AIR | 0.180196 |
F8 S1 APARTMENT DIRECT AIR | 0.184681 |
F8 S2 APARTMENT DIRECT AIR | 0.185136 |
F9 SW APARTMENT DIRECT AIR | 0.321616 |
F9 NW APARTMENT DIRECT AIR | 0.317888 |
F9 SE APARTMENT DIRECT AIR | 0.276457 |
F9 NE APARTMENT DIRECT AIR | 0.257370 |
F9 N1 APARTMENT DIRECT AIR | 0.192278 |
F9 N2 APARTMENT DIRECT AIR | 0.191377 |
F9 S1 APARTMENT DIRECT AIR | 0.193501 |
F9 S2 APARTMENT DIRECT AIR | 0.193942 |
T SW APARTMENT DIRECT AIR | 0.411338 |
T NW APARTMENT DIRECT AIR | 0.400966 |
T SE APARTMENT DIRECT AIR | 0.363921 |
T NE APARTMENT DIRECT AIR | 0.339353 |
T N1 APARTMENT DIRECT AIR | 0.261372 |
T N2 APARTMENT DIRECT AIR | 0.261071 |
T S1 APARTMENT DIRECT AIR | 0.284844 |
T S2 APARTMENT DIRECT AIR | 0.285223 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.244365 |
AIRLOOP G NW MAIN BRANCH | 0.241788 |
AIRLOOP OFFICE MAIN BRANCH | 0.358063 |
AIRLOOP G NE MAIN BRANCH | 0.186792 |
AIRLOOP G N1 MAIN BRANCH | 0.137045 |
AIRLOOP G N2 MAIN BRANCH | 0.135840 |
AIRLOOP G S1 MAIN BRANCH | 0.138200 |
AIRLOOP G S2 MAIN BRANCH | 0.144687 |
AIRLOOP F2 SW MAIN BRANCH | 0.300885 |
AIRLOOP F2 NW MAIN BRANCH | 0.296853 |
AIRLOOP F2 SE MAIN BRANCH | 0.278016 |
AIRLOOP F2 NE MAIN BRANCH | 0.235682 |
AIRLOOP F2 N1 MAIN BRANCH | 0.172003 |
AIRLOOP F2 N2 MAIN BRANCH | 0.171029 |
AIRLOOP F2 S1 MAIN BRANCH | 0.175253 |
AIRLOOP F2 S2 MAIN BRANCH | 0.177274 |
AIRLOOP F3 SW MAIN BRANCH | 0.302868 |
AIRLOOP F3 NW MAIN BRANCH | 0.299210 |
AIRLOOP F3 SE MAIN BRANCH | 0.258984 |
AIRLOOP F3 NE MAIN BRANCH | 0.239366 |
AIRLOOP F3 N1 MAIN BRANCH | 0.175073 |
AIRLOOP F3 N2 MAIN BRANCH | 0.174115 |
AIRLOOP F3 S1 MAIN BRANCH | 0.178665 |
AIRLOOP F3 S2 MAIN BRANCH | 0.179367 |
AIRLOOP F4 SW MAIN BRANCH | 0.305293 |
AIRLOOP F4 NW MAIN BRANCH | 0.301585 |
AIRLOOP F4 SE MAIN BRANCH | 0.259986 |
AIRLOOP F4 NE MAIN BRANCH | 0.241660 |
AIRLOOP F4 N1 MAIN BRANCH | 0.177395 |
AIRLOOP F4 N2 MAIN BRANCH | 0.176449 |
AIRLOOP F4 S1 MAIN BRANCH | 0.181006 |
AIRLOOP F4 S2 MAIN BRANCH | 0.181513 |
AIRLOOP M SW MAIN BRANCH | 0.309726 |
AIRLOOP M NW MAIN BRANCH | 0.306020 |
AIRLOOP M SE MAIN BRANCH | 0.264811 |
AIRLOOP M NE MAIN BRANCH | 0.245977 |
AIRLOOP M N1 MAIN BRANCH | 0.181630 |
AIRLOOP M N2 MAIN BRANCH | 0.180694 |
AIRLOOP M S1 MAIN BRANCH | 0.185193 |
AIRLOOP M S2 MAIN BRANCH | 0.185673 |
AIRLOOP F6 SW MAIN BRANCH | 0.307669 |
AIRLOOP F6 NW MAIN BRANCH | 0.303807 |
AIRLOOP F6 SE MAIN BRANCH | 0.263385 |
AIRLOOP F6 NE MAIN BRANCH | 0.243878 |
AIRLOOP F6 N1 MAIN BRANCH | 0.179498 |
AIRLOOP F6 N2 MAIN BRANCH | 0.178576 |
AIRLOOP F6 S1 MAIN BRANCH | 0.183135 |
AIRLOOP F6 S2 MAIN BRANCH | 0.183612 |
AIRLOOP F7 SW MAIN BRANCH | 0.307801 |
AIRLOOP F7 NW MAIN BRANCH | 0.303895 |
AIRLOOP F7 SE MAIN BRANCH | 0.264060 |
AIRLOOP F7 NE MAIN BRANCH | 0.244039 |
AIRLOOP F7 N1 MAIN BRANCH | 0.179560 |
AIRLOOP F7 N2 MAIN BRANCH | 0.178647 |
AIRLOOP F7 S1 MAIN BRANCH | 0.183193 |
AIRLOOP F7 S2 MAIN BRANCH | 0.183670 |
AIRLOOP F8 SW MAIN BRANCH | 0.309410 |
AIRLOOP F8 NW MAIN BRANCH | 0.305470 |
AIRLOOP F8 SE MAIN BRANCH | 0.266078 |
AIRLOOP F8 NE MAIN BRANCH | 0.246051 |
AIRLOOP F8 N1 MAIN BRANCH | 0.181098 |
AIRLOOP F8 N2 MAIN BRANCH | 0.180196 |
AIRLOOP F8 S1 MAIN BRANCH | 0.184681 |
AIRLOOP F8 S2 MAIN BRANCH | 0.185136 |
AIRLOOP F9 SW MAIN BRANCH | 0.321616 |
AIRLOOP F9 NW MAIN BRANCH | 0.317888 |
AIRLOOP F9 SE MAIN BRANCH | 0.276457 |
AIRLOOP F9 NE MAIN BRANCH | 0.257370 |
AIRLOOP F9 N1 MAIN BRANCH | 0.192278 |
AIRLOOP F9 N2 MAIN BRANCH | 0.191377 |
AIRLOOP F9 S1 MAIN BRANCH | 0.193501 |
AIRLOOP F9 S2 MAIN BRANCH | 0.193942 |
AIRLOOP T SW MAIN BRANCH | 0.411338 |
AIRLOOP T NW MAIN BRANCH | 0.400966 |
AIRLOOP T SE MAIN BRANCH | 0.363921 |
AIRLOOP T NE MAIN BRANCH | 0.339353 |
AIRLOOP T N1 MAIN BRANCH | 0.261372 |
AIRLOOP T N2 MAIN BRANCH | 0.261071 |
AIRLOOP T S1 MAIN BRANCH | 0.284844 |
AIRLOOP T S2 MAIN BRANCH | 0.285223 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.244365 |
AIRLOOP G NW | 0.241788 |
AIRLOOP OFFICE | 0.358063 |
AIRLOOP G NE | 0.186792 |
AIRLOOP G N1 | 0.137045 |
AIRLOOP G N2 | 0.135840 |
AIRLOOP G S1 | 0.138200 |
AIRLOOP G S2 | 0.144687 |
AIRLOOP F2 SW | 0.300885 |
AIRLOOP F2 NW | 0.296853 |
AIRLOOP F2 SE | 0.278016 |
AIRLOOP F2 NE | 0.235682 |
AIRLOOP F2 N1 | 0.172003 |
AIRLOOP F2 N2 | 0.171029 |
AIRLOOP F2 S1 | 0.175253 |
AIRLOOP F2 S2 | 0.177274 |
AIRLOOP F3 SW | 0.302868 |
AIRLOOP F3 NW | 0.299210 |
AIRLOOP F3 SE | 0.258984 |
AIRLOOP F3 NE | 0.239366 |
AIRLOOP F3 N1 | 0.175073 |
AIRLOOP F3 N2 | 0.174115 |
AIRLOOP F3 S1 | 0.178665 |
AIRLOOP F3 S2 | 0.179367 |
AIRLOOP F4 SW | 0.305293 |
AIRLOOP F4 NW | 0.301585 |
AIRLOOP F4 SE | 0.259986 |
AIRLOOP F4 NE | 0.241660 |
AIRLOOP F4 N1 | 0.177395 |
AIRLOOP F4 N2 | 0.176449 |
AIRLOOP F4 S1 | 0.181006 |
AIRLOOP F4 S2 | 0.181513 |
AIRLOOP M SW | 0.309726 |
AIRLOOP M NW | 0.306020 |
AIRLOOP M SE | 0.264811 |
AIRLOOP M NE | 0.245977 |
AIRLOOP M N1 | 0.181630 |
AIRLOOP M N2 | 0.180694 |
AIRLOOP M S1 | 0.185193 |
AIRLOOP M S2 | 0.185673 |
AIRLOOP F6 SW | 0.307669 |
AIRLOOP F6 NW | 0.303807 |
AIRLOOP F6 SE | 0.263385 |
AIRLOOP F6 NE | 0.243878 |
AIRLOOP F6 N1 | 0.179498 |
AIRLOOP F6 N2 | 0.178576 |
AIRLOOP F6 S1 | 0.183135 |
AIRLOOP F6 S2 | 0.183612 |
AIRLOOP F7 SW | 0.307801 |
AIRLOOP F7 NW | 0.303895 |
AIRLOOP F7 SE | 0.264060 |
AIRLOOP F7 NE | 0.244039 |
AIRLOOP F7 N1 | 0.179560 |
AIRLOOP F7 N2 | 0.178647 |
AIRLOOP F7 S1 | 0.183193 |
AIRLOOP F7 S2 | 0.183670 |
AIRLOOP F8 SW | 0.309410 |
AIRLOOP F8 NW | 0.305470 |
AIRLOOP F8 SE | 0.266078 |
AIRLOOP F8 NE | 0.246051 |
AIRLOOP F8 N1 | 0.181098 |
AIRLOOP F8 N2 | 0.180196 |
AIRLOOP F8 S1 | 0.184681 |
AIRLOOP F8 S2 | 0.185136 |
AIRLOOP F9 SW | 0.321616 |
AIRLOOP F9 NW | 0.317888 |
AIRLOOP F9 SE | 0.276457 |
AIRLOOP F9 NE | 0.257370 |
AIRLOOP F9 N1 | 0.192278 |
AIRLOOP F9 N2 | 0.191377 |
AIRLOOP F9 S1 | 0.193501 |
AIRLOOP F9 S2 | 0.193942 |
AIRLOOP T SW | 0.411338 |
AIRLOOP T NW | 0.400966 |
AIRLOOP T SE | 0.363921 |
AIRLOOP T NE | 0.339353 |
AIRLOOP T N1 | 0.261372 |
AIRLOOP T N2 | 0.261071 |
AIRLOOP T S1 | 0.284844 |
AIRLOOP T S2 | 0.285223 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.244365 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.241788 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.358063 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.186792 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.137045 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.135840 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.138200 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.144687 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.300885 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.296853 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.278016 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.235682 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.172003 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.171029 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.175253 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.177274 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.302868 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.299210 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.258984 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.239366 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.175073 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.174115 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.178665 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.179367 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.305293 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.301585 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.259986 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.241660 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.177395 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.176449 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.181006 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.181513 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.309726 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.306020 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.264811 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.245977 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.181630 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.180694 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.185193 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.185673 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.307669 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.303807 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.263385 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.243878 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.179498 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.178576 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.183135 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.183612 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.307801 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.303895 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.264060 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.244039 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.179560 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.178647 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.183193 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.183670 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.309410 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.305470 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.266078 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.246051 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.181098 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.180196 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.184681 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.185136 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.321616 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.317888 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.276457 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.257370 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.192278 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.191377 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.193501 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.193942 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.411338 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.400966 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.363921 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.339353 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.261372 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.261071 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.284844 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.285223 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.244365 | 3331.51 | 2202.53 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.241788 | 3281.06 | 2172.23 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.358063 | 4816.47 | 3203.36 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.186792 | 2543.24 | 1687.17 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.137045 | 1935.73 | 1265.39 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.135840 | 1920.33 | 1255.04 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.138200 | 2030.42 | 1308.69 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.144687 | 2108.76 | 1363.00 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.300885 | 4026.71 | 2679.14 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.296853 | 3963.59 | 2638.95 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.278016 | 3771.45 | 2498.92 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.235682 | 3146.76 | 2101.37 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.172003 | 2382.04 | 1567.84 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.171029 | 2369.64 | 1559.50 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.175253 | 2492.55 | 1625.60 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.177274 | 2518.22 | 1642.95 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.302868 | 4042.36 | 2694.22 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.299210 | 3983.93 | 2657.21 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.258984 | 3521.20 | 2334.69 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.239366 | 3184.26 | 2131.03 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.175073 | 2415.59 | 1593.04 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.174115 | 2403.42 | 1584.85 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.178665 | 2530.52 | 1653.83 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.179367 | 2539.45 | 1659.86 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.305293 | 4071.42 | 2716.14 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.301585 | 4006.92 | 2676.09 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.259986 | 3531.51 | 2343.70 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.241660 | 3206.49 | 2149.29 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.177395 | 2441.03 | 1612.12 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.176449 | 2429.02 | 1604.03 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.181006 | 2556.23 | 1673.13 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.181513 | 2562.68 | 1677.48 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.309726 | 4121.80 | 2752.82 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.306020 | 4057.32 | 2712.78 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.264811 | 3587.07 | 2383.83 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.245977 | 3255.56 | 2185.02 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.181630 | 2491.53 | 1647.71 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.180694 | 2479.65 | 1639.71 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.185193 | 2606.07 | 1708.39 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.185673 | 2612.18 | 1712.51 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.307669 | 4090.88 | 2734.34 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.303807 | 4024.40 | 2692.98 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.263385 | 3564.39 | 2370.77 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.243878 | 3237.61 | 2171.66 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.179498 | 2461.61 | 1628.92 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.178576 | 2449.89 | 1621.03 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.183135 | 2577.23 | 1690.22 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.183612 | 2583.30 | 1694.31 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.307801 | 4088.29 | 2734.65 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.303895 | 4021.23 | 2692.90 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.264060 | 3568.84 | 2375.74 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.244039 | 3235.61 | 2172.26 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.179560 | 2459.91 | 1628.97 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.178647 | 2448.33 | 1621.17 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.183193 | 2575.67 | 1690.27 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.183670 | 2581.61 | 1694.33 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.309410 | 4104.83 | 2747.63 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.305470 | 4037.33 | 2705.59 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.266078 | 3590.71 | 2392.26 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.246051 | 3332.70 | 2219.30 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.181098 | 2477.23 | 1641.70 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.180196 | 2465.79 | 1633.99 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.184681 | 2592.36 | 1702.60 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.185136 | 2598.03 | 1706.48 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.321616 | 4250.32 | 2848.37 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.317888 | 4190.91 | 2810.71 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.276457 | 3718.63 | 2480.18 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.257370 | 3472.36 | 2315.25 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.192278 | 2617.11 | 1736.89 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.191377 | 2605.68 | 1729.19 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.193501 | 2702.00 | 1777.75 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.193942 | 2707.60 | 1781.53 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.411338 | 5405.36 | 3622.37 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.400966 | 5261.53 | 3528.82 | 0.000115 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.363921 | 4821.01 | 3225.05 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.339353 | 4510.40 | 3015.73 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.261372 | 3559.47 | 2357.55 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.261071 | 3555.69 | 2354.99 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.284844 | 3856.69 | 2557.89 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.285223 | 3861.51 | 2561.13 | 0.000084 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.244365 | 0.244365 | 0.244365 | 0.244365 | 3331.51 | 3331.51 | 2461.24 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.241788 | 0.241788 | 0.241788 | 0.241788 | 3281.06 | 3281.06 | 2460.11 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.358063 | 0.358063 | 0.358063 | 0.358063 | 4816.47 | 4816.47 | 3141.65 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.186792 | 0.186792 | 0.186792 | 0.186792 | 2543.24 | 2543.24 | 2456.67 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.137045 | 0.137045 | 0.137045 | 0.137045 | 1935.73 | 1935.73 | 1835.78 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.135840 | 0.135840 | 0.135840 | 0.135840 | 1920.33 | 1920.33 | 1835.69 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.138200 | 0.138200 | 0.138200 | 0.138200 | 2030.42 | 2030.42 | 1833.23 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.144687 | 0.144687 | 0.144687 | 0.144687 | 2108.76 | 2108.76 | 1839.42 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.300885 | 0.300885 | 0.300885 | 0.300885 | 4026.71 | 4026.71 | 2399.64 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.296853 | 0.296853 | 0.296853 | 0.296853 | 3963.59 | 3963.59 | 2394.45 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.278016 | 0.278016 | 0.278016 | 0.278016 | 3771.45 | 3771.45 | 2414.91 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.235682 | 0.235682 | 0.235682 | 0.235682 | 3146.76 | 3146.76 | 2390.93 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.172003 | 0.172003 | 0.172003 | 0.172003 | 2382.04 | 2382.04 | 1626.68 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.171029 | 0.171029 | 0.171029 | 0.171029 | 2369.64 | 2369.64 | 1626.59 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.175253 | 0.175253 | 0.175253 | 0.175253 | 2492.55 | 2492.55 | 1634.55 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.177274 | 0.177274 | 0.177274 | 0.177274 | 2518.22 | 2518.22 | 1635.71 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.302868 | 0.302868 | 0.302868 | 0.302868 | 4042.36 | 4042.36 | 2388.67 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.299210 | 0.299210 | 0.299210 | 0.299210 | 3983.93 | 3983.93 | 2385.15 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.258984 | 0.258984 | 0.258984 | 0.258984 | 3521.20 | 3521.20 | 2387.87 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.239366 | 0.239366 | 0.239366 | 0.239366 | 3184.26 | 3184.26 | 2382.24 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.175073 | 0.175073 | 0.175073 | 0.175073 | 2415.59 | 2415.59 | 1588.37 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.174115 | 0.174115 | 0.174115 | 0.174115 | 2403.42 | 2403.42 | 1588.29 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.178665 | 0.178665 | 0.178665 | 0.178665 | 2530.52 | 2530.52 | 1592.58 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.179367 | 0.179367 | 0.179367 | 0.179367 | 2539.45 | 2539.45 | 1592.70 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.305293 | 0.305293 | 0.305293 | 0.305293 | 4071.42 | 4071.42 | 2423.32 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.301585 | 0.301585 | 0.301585 | 0.301585 | 4006.92 | 4006.92 | 2421.20 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.259986 | 0.259986 | 0.259986 | 0.259986 | 3531.51 | 3531.51 | 2421.22 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.241660 | 0.241660 | 0.241660 | 0.241660 | 3206.49 | 3206.49 | 2418.88 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.177395 | 0.177395 | 0.177395 | 0.177395 | 2441.03 | 2441.03 | 1600.81 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.176449 | 0.176449 | 0.176449 | 0.176449 | 2429.02 | 2429.02 | 1600.75 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.181006 | 0.181006 | 0.181006 | 0.181006 | 2556.23 | 2556.23 | 1603.37 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.181513 | 0.181513 | 0.181513 | 0.181513 | 2562.68 | 2562.68 | 1603.34 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.309726 | 0.309726 | 0.309726 | 0.309726 | 4121.80 | 4121.80 | 2438.78 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.306020 | 0.306020 | 0.306020 | 0.306020 | 4057.32 | 4057.32 | 2436.67 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.264811 | 0.264811 | 0.264811 | 0.264811 | 3587.07 | 3587.07 | 2437.02 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.245977 | 0.245977 | 0.245977 | 0.245977 | 3255.56 | 3255.56 | 2434.88 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.181630 | 0.181630 | 0.181630 | 0.181630 | 2491.53 | 2491.53 | 1599.56 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.180694 | 0.180694 | 0.180694 | 0.180694 | 2479.65 | 2479.65 | 1599.52 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.185193 | 0.185193 | 0.185193 | 0.185193 | 2606.07 | 2606.07 | 1602.09 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.185673 | 0.185673 | 0.185673 | 0.185673 | 2612.18 | 2612.18 | 1602.04 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.307669 | 0.307669 | 0.307669 | 0.307669 | 4090.88 | 4090.88 | 2513.61 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.303807 | 0.303807 | 0.303807 | 0.303807 | 4024.40 | 4024.40 | 2513.07 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.263385 | 0.263385 | 0.263385 | 0.263385 | 3564.39 | 3564.39 | 2512.30 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.243878 | 0.243878 | 0.243878 | 0.243878 | 3237.61 | 3237.61 | 2511.76 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.179498 | 0.179498 | 0.179498 | 0.179498 | 2461.61 | 2461.61 | 1657.05 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.178576 | 0.178576 | 0.178576 | 0.178576 | 2449.89 | 2449.89 | 1657.02 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.183135 | 0.183135 | 0.183135 | 0.183135 | 2577.23 | 2577.23 | 1657.94 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.183612 | 0.183612 | 0.183612 | 0.183612 | 2583.30 | 2583.30 | 1657.91 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.307801 | 0.307801 | 0.307801 | 0.307801 | 4088.29 | 4088.29 | 2563.07 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.303895 | 0.303895 | 0.303895 | 0.303895 | 4021.23 | 4021.23 | 2562.98 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.264060 | 0.264060 | 0.264060 | 0.264060 | 3568.84 | 3568.84 | 2562.19 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.244039 | 0.244039 | 0.244039 | 0.244039 | 3235.61 | 3235.61 | 2562.10 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.179560 | 0.179560 | 0.179560 | 0.179560 | 2459.91 | 2459.91 | 1692.83 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.178647 | 0.178647 | 0.178647 | 0.178647 | 2448.33 | 2448.33 | 1692.80 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.183193 | 0.183193 | 0.183193 | 0.183193 | 2575.67 | 2575.67 | 1693.22 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.183670 | 0.183670 | 0.183670 | 0.183670 | 2581.61 | 2581.61 | 1693.20 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.309410 | 0.309410 | 0.309410 | 0.309410 | 4104.83 | 4104.83 | 2616.62 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.305470 | 0.305470 | 0.305470 | 0.305470 | 4037.33 | 4037.33 | 2616.75 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.266078 | 0.266078 | 0.266078 | 0.266078 | 3590.71 | 3590.71 | 2616.15 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.246051 | 0.246051 | 0.246051 | 0.246051 | 3332.70 | 3332.70 | 2616.27 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.181098 | 0.181098 | 0.181098 | 0.181098 | 2477.23 | 2477.23 | 1734.17 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.180196 | 0.180196 | 0.180196 | 0.180196 | 2465.79 | 2465.79 | 1734.16 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.184681 | 0.184681 | 0.184681 | 0.184681 | 2592.36 | 2592.36 | 1734.34 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.185136 | 0.185136 | 0.185136 | 0.185136 | 2598.03 | 2598.03 | 1734.33 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.321616 | 0.321616 | 0.321616 | 0.321616 | 4250.32 | 4250.32 | 2783.15 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.317888 | 0.317888 | 0.317888 | 0.317888 | 4190.91 | 4190.91 | 2781.30 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.276457 | 0.276457 | 0.276457 | 0.276457 | 3718.63 | 3718.63 | 2783.04 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.257370 | 0.257370 | 0.257370 | 0.257370 | 3472.36 | 3472.36 | 2781.20 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.192278 | 0.192278 | 0.192278 | 0.192278 | 2617.11 | 2617.11 | 1879.90 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.191377 | 0.191377 | 0.191377 | 0.191377 | 2605.68 | 2605.68 | 1879.90 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.193501 | 0.193501 | 0.193501 | 0.193501 | 2702.00 | 2702.00 | 1881.61 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.193942 | 0.193942 | 0.193942 | 0.193942 | 2707.60 | 2707.60 | 1881.60 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.411338 | 0.411338 | 0.411338 | 0.411338 | 5405.36 | 5405.36 | 3352.96 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.400966 | 0.400966 | 0.400966 | 0.400966 | 5261.53 | 5261.53 | 3357.81 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.363921 | 0.363921 | 0.363921 | 0.363921 | 4821.01 | 4821.01 | 3353.16 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.339353 | 0.339353 | 0.339353 | 0.339353 | 4510.40 | 4510.40 | 3358.01 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.261372 | 0.261372 | 0.261372 | 0.261372 | 3559.47 | 3559.47 | 2497.15 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.261071 | 0.261071 | 0.261071 | 0.261071 | 3555.69 | 3555.69 | 2497.15 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.284844 | 0.284844 | 0.284844 | 0.284844 | 3856.69 | 3856.69 | 2489.37 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.285223 | 0.285223 | 0.285223 | 0.285223 | 3861.51 | 3861.51 | 2489.38 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.244365 |
AIRLOOP G NW SUPPLY FAN | 0.241788 |
AIRLOOP OFFICE SUPPLY FAN | 0.358063 |
AIRLOOP G NE SUPPLY FAN | 0.186792 |
AIRLOOP G N1 SUPPLY FAN | 0.137045 |
AIRLOOP G N2 SUPPLY FAN | 0.135840 |
AIRLOOP G S1 SUPPLY FAN | 0.138200 |
AIRLOOP G S2 SUPPLY FAN | 0.144687 |
AIRLOOP F2 SW SUPPLY FAN | 0.300885 |
AIRLOOP F2 NW SUPPLY FAN | 0.296853 |
AIRLOOP F2 SE SUPPLY FAN | 0.278016 |
AIRLOOP F2 NE SUPPLY FAN | 0.235682 |
AIRLOOP F2 N1 SUPPLY FAN | 0.172003 |
AIRLOOP F2 N2 SUPPLY FAN | 0.171029 |
AIRLOOP F2 S1 SUPPLY FAN | 0.175253 |
AIRLOOP F2 S2 SUPPLY FAN | 0.177274 |
AIRLOOP F3 SW SUPPLY FAN | 0.302868 |
AIRLOOP F3 NW SUPPLY FAN | 0.299210 |
AIRLOOP F3 SE SUPPLY FAN | 0.258984 |
AIRLOOP F3 NE SUPPLY FAN | 0.239366 |
AIRLOOP F3 N1 SUPPLY FAN | 0.175073 |
AIRLOOP F3 N2 SUPPLY FAN | 0.174115 |
AIRLOOP F3 S1 SUPPLY FAN | 0.178665 |
AIRLOOP F3 S2 SUPPLY FAN | 0.179367 |
AIRLOOP F4 SW SUPPLY FAN | 0.305293 |
AIRLOOP F4 NW SUPPLY FAN | 0.301585 |
AIRLOOP F4 SE SUPPLY FAN | 0.259986 |
AIRLOOP F4 NE SUPPLY FAN | 0.241660 |
AIRLOOP F4 N1 SUPPLY FAN | 0.177395 |
AIRLOOP F4 N2 SUPPLY FAN | 0.176449 |
AIRLOOP F4 S1 SUPPLY FAN | 0.181006 |
AIRLOOP F4 S2 SUPPLY FAN | 0.181513 |
AIRLOOP M SW SUPPLY FAN | 0.309726 |
AIRLOOP M NW SUPPLY FAN | 0.306020 |
AIRLOOP M SE SUPPLY FAN | 0.264811 |
AIRLOOP M NE SUPPLY FAN | 0.245977 |
AIRLOOP M N1 SUPPLY FAN | 0.181630 |
AIRLOOP M N2 SUPPLY FAN | 0.180694 |
AIRLOOP M S1 SUPPLY FAN | 0.185193 |
AIRLOOP M S2 SUPPLY FAN | 0.185673 |
AIRLOOP F6 SW SUPPLY FAN | 0.307669 |
AIRLOOP F6 NW SUPPLY FAN | 0.303807 |
AIRLOOP F6 SE SUPPLY FAN | 0.263385 |
AIRLOOP F6 NE SUPPLY FAN | 0.243878 |
AIRLOOP F6 N1 SUPPLY FAN | 0.179498 |
AIRLOOP F6 N2 SUPPLY FAN | 0.178576 |
AIRLOOP F6 S1 SUPPLY FAN | 0.183135 |
AIRLOOP F6 S2 SUPPLY FAN | 0.183612 |
AIRLOOP F7 SW SUPPLY FAN | 0.307801 |
AIRLOOP F7 NW SUPPLY FAN | 0.303895 |
AIRLOOP F7 SE SUPPLY FAN | 0.264060 |
AIRLOOP F7 NE SUPPLY FAN | 0.244039 |
AIRLOOP F7 N1 SUPPLY FAN | 0.179560 |
AIRLOOP F7 N2 SUPPLY FAN | 0.178647 |
AIRLOOP F7 S1 SUPPLY FAN | 0.183193 |
AIRLOOP F7 S2 SUPPLY FAN | 0.183670 |
AIRLOOP F8 SW SUPPLY FAN | 0.309410 |
AIRLOOP F8 NW SUPPLY FAN | 0.305470 |
AIRLOOP F8 SE SUPPLY FAN | 0.266078 |
AIRLOOP F8 NE SUPPLY FAN | 0.246051 |
AIRLOOP F8 N1 SUPPLY FAN | 0.181098 |
AIRLOOP F8 N2 SUPPLY FAN | 0.180196 |
AIRLOOP F8 S1 SUPPLY FAN | 0.184681 |
AIRLOOP F8 S2 SUPPLY FAN | 0.185136 |
AIRLOOP F9 SW SUPPLY FAN | 0.321616 |
AIRLOOP F9 NW SUPPLY FAN | 0.317888 |
AIRLOOP F9 SE SUPPLY FAN | 0.276457 |
AIRLOOP F9 NE SUPPLY FAN | 0.257370 |
AIRLOOP F9 N1 SUPPLY FAN | 0.192278 |
AIRLOOP F9 N2 SUPPLY FAN | 0.191377 |
AIRLOOP F9 S1 SUPPLY FAN | 0.193501 |
AIRLOOP F9 S2 SUPPLY FAN | 0.193942 |
AIRLOOP T SW SUPPLY FAN | 0.411338 |
AIRLOOP T NW SUPPLY FAN | 0.400966 |
AIRLOOP T SE SUPPLY FAN | 0.363921 |
AIRLOOP T NE SUPPLY FAN | 0.339353 |
AIRLOOP T N1 SUPPLY FAN | 0.261372 |
AIRLOOP T N2 SUPPLY FAN | 0.261071 |
AIRLOOP T S1 SUPPLY FAN | 0.284844 |
AIRLOOP T S2 SUPPLY FAN | 0.285223 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.244365 | 3331.51 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.241788 | 3281.06 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.358063 | 4816.47 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.186792 | 2543.24 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.137045 | 1935.73 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.135840 | 1920.33 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.138200 | 2030.42 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.144687 | 2108.76 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.300885 | 4026.71 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.296853 | 3963.59 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.278016 | 3771.45 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.235682 | 3146.76 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.172003 | 2382.04 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.171029 | 2369.64 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.175253 | 2492.55 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.177274 | 2518.22 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.302868 | 4042.36 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.299210 | 3983.93 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.258984 | 3521.20 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.239366 | 3184.26 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.175073 | 2415.59 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.174115 | 2403.42 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.178665 | 2530.52 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.179367 | 2539.45 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.305293 | 4071.42 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.301585 | 4006.92 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.259986 | 3531.51 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.241660 | 3206.49 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.177395 | 2441.03 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.176449 | 2429.02 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.181006 | 2556.23 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.181513 | 2562.68 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.309726 | 4121.80 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.306020 | 4057.32 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.264811 | 3587.07 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.245977 | 3255.56 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.181630 | 2491.53 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.180694 | 2479.65 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.185193 | 2606.07 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.185673 | 2612.18 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.307669 | 4090.88 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.303807 | 4024.40 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.263385 | 3564.39 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.243878 | 3237.61 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.179498 | 2461.61 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.178576 | 2449.89 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.183135 | 2577.23 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.183612 | 2583.30 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.307801 | 4088.29 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.303895 | 4021.23 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.264060 | 3568.84 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.244039 | 3235.61 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.179560 | 2459.91 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.178647 | 2448.33 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.183193 | 2575.67 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.183670 | 2581.61 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.309410 | 4104.83 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.305470 | 4037.33 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.266078 | 3590.71 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.246051 | 3332.70 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.181098 | 2477.23 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.180196 | 2465.79 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.184681 | 2592.36 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.185136 | 2598.03 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.321616 | 4250.32 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.317888 | 4190.91 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.276457 | 3718.63 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.257370 | 3472.36 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.192278 | 2617.11 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.191377 | 2605.68 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.193501 | 2702.00 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.193942 | 2707.60 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.411338 | 5405.36 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.400966 | 5261.53 | 0.000115 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.363921 | 4821.01 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.339353 | 4510.40 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.261372 | 3559.47 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.261071 | 3555.69 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.284844 | 3856.69 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.285223 | 3861.51 | 0.000084 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2461.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2460.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3141.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2456.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1835.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1835.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1833.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1839.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2399.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2394.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2414.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2390.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1626.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1626.59 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1634.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1635.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2388.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2385.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2387.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2382.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1588.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1588.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1592.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1592.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2423.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2421.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2421.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2418.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1600.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1600.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1603.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1603.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2438.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2436.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2437.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2434.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1599.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1599.52 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1602.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1602.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2513.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2513.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2512.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2511.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1657.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1657.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1657.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1657.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2563.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2562.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2562.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2562.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1692.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1692.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1693.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1693.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2616.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2616.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2616.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2616.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1734.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1734.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1734.34 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1734.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2783.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2781.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2783.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2781.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1879.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1879.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1881.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1881.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3352.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3357.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3353.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3358.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2497.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2497.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2489.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2489.38 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005626 | 6.33 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005626 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005626 | 2715.84 | 8.24 | 7301.46 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005626 | 1796.59 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 8.14 |
February | 22.84 | 10.27 |
March | 23.00 | 12.55 |
April | 23.79 | 19.23 |
May | 24.21 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.34 | 23.38 |
October | 24.00 | 18.30 |
November | 23.17 | 11.18 |
December | 22.67 | 6.79 |
Annual Sum or Average | 23.66 | 17.98 |
Minimum of Months | 22.67 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 8.14 |
February | 22.10 | 10.27 |
March | 22.48 | 12.55 |
April | 23.67 | 19.23 |
May | 24.21 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.33 | 23.38 |
October | 23.73 | 18.30 |
November | 22.32 | 11.18 |
December | 21.85 | 6.79 |
Annual Sum or Average | 23.32 | 17.98 |
Minimum of Months | 21.85 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 8.14 |
February | 23.19 | 10.27 |
March | 23.44 | 12.55 |
April | 24.11 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.19 | 18.30 |
November | 23.37 | 11.18 |
December | 22.84 | 6.79 |
Annual Sum or Average | 23.84 | 17.98 |
Minimum of Months | 22.84 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 8.14 |
February | 22.05 | 10.27 |
March | 22.42 | 12.55 |
April | 23.69 | 19.23 |
May | 24.23 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.38 | 26.28 |
September | 24.34 | 23.38 |
October | 23.64 | 18.30 |
November | 22.20 | 11.18 |
December | 21.78 | 6.79 |
Annual Sum or Average | 23.28 | 17.98 |
Minimum of Months | 21.78 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 8.14 |
February | 21.95 | 10.27 |
March | 22.24 | 12.55 |
April | 23.52 | 19.23 |
May | 24.16 | 23.84 |
June | 24.39 | 27.86 |
July | 24.41 | 27.54 |
August | 24.37 | 26.28 |
September | 24.31 | 23.38 |
October | 23.57 | 18.30 |
November | 22.13 | 11.18 |
December | 21.77 | 6.79 |
Annual Sum or Average | 23.22 | 17.98 |
Minimum of Months | 21.76 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 8.14 |
February | 21.95 | 10.27 |
March | 22.24 | 12.55 |
April | 23.52 | 19.23 |
May | 24.16 | 23.84 |
June | 24.39 | 27.86 |
July | 24.41 | 27.54 |
August | 24.37 | 26.28 |
September | 24.31 | 23.38 |
October | 23.56 | 18.30 |
November | 22.12 | 11.18 |
December | 21.76 | 6.79 |
Annual Sum or Average | 23.22 | 17.98 |
Minimum of Months | 21.76 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 8.14 |
February | 22.88 | 10.27 |
March | 22.95 | 12.55 |
April | 23.71 | 19.23 |
May | 24.17 | 23.84 |
June | 24.38 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.38 | 23.38 |
October | 23.98 | 18.30 |
November | 23.23 | 11.18 |
December | 22.74 | 6.79 |
Annual Sum or Average | 23.67 | 17.98 |
Minimum of Months | 22.74 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 8.14 |
February | 22.93 | 10.27 |
March | 23.02 | 12.55 |
April | 23.75 | 19.23 |
May | 24.18 | 23.84 |
June | 24.38 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.37 | 23.38 |
October | 24.01 | 18.30 |
November | 23.27 | 11.18 |
December | 22.78 | 6.79 |
Annual Sum or Average | 23.69 | 17.98 |
Minimum of Months | 22.78 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.86 | 8.14 |
February | 19.70 | 10.27 |
March | 20.62 | 12.55 |
April | 23.14 | 19.23 |
May | 24.91 | 23.84 |
June | 26.81 | 27.86 |
July | 26.78 | 27.54 |
August | 26.35 | 26.28 |
September | 25.57 | 23.38 |
October | 23.03 | 18.30 |
November | 20.22 | 11.18 |
December | 18.52 | 6.79 |
Annual Sum or Average | 22.89 | 17.98 |
Minimum of Months | 18.52 | 6.79 |
Maximum of Months | 26.81 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 8.14 |
February | 23.51 | 10.27 |
March | 23.72 | 12.55 |
April | 24.17 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.33 | 18.30 |
November | 23.80 | 11.18 |
December | 23.23 | 6.79 |
Annual Sum or Average | 24.00 | 17.98 |
Minimum of Months | 23.23 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 8.14 |
February | 22.49 | 10.27 |
March | 23.02 | 12.55 |
April | 24.06 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.18 | 18.30 |
November | 22.84 | 11.18 |
December | 22.03 | 6.79 |
Annual Sum or Average | 23.56 | 17.98 |
Minimum of Months | 22.03 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 8.14 |
February | 23.62 | 10.27 |
March | 23.83 | 12.55 |
April | 24.24 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.34 | 18.30 |
November | 23.84 | 11.18 |
December | 23.32 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 23.32 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 8.14 |
February | 22.42 | 10.27 |
March | 22.94 | 12.55 |
April | 24.07 | 19.23 |
May | 24.35 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.11 | 18.30 |
November | 22.67 | 11.18 |
December | 21.94 | 6.79 |
Annual Sum or Average | 23.51 | 17.98 |
Minimum of Months | 21.94 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 8.14 |
February | 22.38 | 10.27 |
March | 22.85 | 12.55 |
April | 23.99 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.11 | 18.30 |
November | 22.68 | 11.18 |
December | 21.96 | 6.79 |
Annual Sum or Average | 23.49 | 17.98 |
Minimum of Months | 21.96 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 8.14 |
February | 22.37 | 10.27 |
March | 22.84 | 12.55 |
April | 23.99 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.11 | 18.30 |
November | 22.66 | 11.18 |
December | 21.96 | 6.79 |
Annual Sum or Average | 23.49 | 17.98 |
Minimum of Months | 21.96 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 8.14 |
February | 23.68 | 10.27 |
March | 23.79 | 12.55 |
April | 24.14 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.42 | 23.38 |
October | 24.35 | 18.30 |
November | 23.92 | 11.18 |
December | 23.47 | 6.79 |
Annual Sum or Average | 24.07 | 17.98 |
Minimum of Months | 23.47 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.54 | 8.14 |
February | 23.70 | 10.27 |
March | 23.81 | 12.55 |
April | 24.15 | 19.23 |
May | 24.33 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.35 | 18.30 |
November | 23.93 | 11.18 |
December | 23.49 | 6.79 |
Annual Sum or Average | 24.08 | 17.98 |
Minimum of Months | 23.49 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 8.14 |
February | 23.63 | 10.27 |
March | 24.13 | 12.55 |
April | 25.38 | 19.23 |
May | 26.06 | 23.84 |
June | 26.63 | 27.86 |
July | 26.61 | 27.54 |
August | 26.50 | 26.28 |
September | 26.33 | 23.38 |
October | 25.53 | 18.30 |
November | 24.06 | 11.18 |
December | 23.06 | 6.79 |
Annual Sum or Average | 25.10 | 17.98 |
Minimum of Months | 23.06 | 6.79 |
Maximum of Months | 26.63 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 8.14 |
February | 23.60 | 10.27 |
March | 23.81 | 12.55 |
April | 24.18 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.35 | 18.30 |
November | 23.87 | 11.18 |
December | 23.33 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 23.33 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 8.14 |
February | 22.58 | 10.27 |
March | 23.13 | 12.55 |
April | 24.09 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.23 | 18.30 |
November | 22.97 | 11.18 |
December | 22.09 | 6.79 |
Annual Sum or Average | 23.60 | 17.98 |
Minimum of Months | 22.09 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 8.14 |
February | 23.60 | 10.27 |
March | 23.80 | 12.55 |
April | 24.21 | 19.23 |
May | 24.36 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.34 | 18.30 |
November | 23.83 | 11.18 |
December | 23.31 | 6.79 |
Annual Sum or Average | 24.03 | 17.98 |
Minimum of Months | 23.31 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 8.14 |
February | 22.51 | 10.27 |
March | 23.06 | 12.55 |
April | 24.10 | 19.23 |
May | 24.36 | 23.84 |
June | 24.42 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.18 | 18.30 |
November | 22.80 | 11.18 |
December | 21.99 | 6.79 |
Annual Sum or Average | 23.55 | 17.98 |
Minimum of Months | 21.99 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 8.14 |
February | 22.53 | 10.27 |
March | 23.05 | 12.55 |
April | 24.06 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.19 | 18.30 |
November | 22.89 | 11.18 |
December | 22.05 | 6.79 |
Annual Sum or Average | 23.57 | 17.98 |
Minimum of Months | 22.05 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 8.14 |
February | 22.53 | 10.27 |
March | 23.04 | 12.55 |
April | 24.06 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.19 | 18.30 |
November | 22.87 | 11.18 |
December | 22.05 | 6.79 |
Annual Sum or Average | 23.56 | 17.98 |
Minimum of Months | 22.05 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 8.14 |
February | 23.84 | 10.27 |
March | 23.93 | 12.55 |
April | 24.18 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.42 | 23.38 |
October | 24.38 | 18.30 |
November | 24.03 | 11.18 |
December | 23.65 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.65 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 8.14 |
February | 23.85 | 10.27 |
March | 23.94 | 12.55 |
April | 24.19 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.42 | 23.38 |
October | 24.38 | 18.30 |
November | 24.03 | 11.18 |
December | 23.66 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.66 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 8.14 |
February | 24.10 | 10.27 |
March | 24.58 | 12.55 |
April | 25.71 | 19.23 |
May | 26.28 | 23.84 |
June | 26.68 | 27.86 |
July | 26.64 | 27.54 |
August | 26.55 | 26.28 |
September | 26.42 | 23.38 |
October | 25.86 | 18.30 |
November | 24.53 | 11.18 |
December | 23.55 | 6.79 |
Annual Sum or Average | 25.38 | 17.98 |
Minimum of Months | 23.55 | 6.79 |
Maximum of Months | 26.68 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 8.14 |
February | 23.59 | 10.27 |
March | 23.80 | 12.55 |
April | 24.17 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.35 | 18.30 |
November | 23.87 | 11.18 |
December | 23.33 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 23.33 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 8.14 |
February | 22.59 | 10.27 |
March | 23.15 | 12.55 |
April | 24.08 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.23 | 18.30 |
November | 22.99 | 11.18 |
December | 22.11 | 6.79 |
Annual Sum or Average | 23.61 | 17.98 |
Minimum of Months | 22.11 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 8.14 |
February | 23.56 | 10.27 |
March | 23.78 | 12.55 |
April | 24.19 | 19.23 |
May | 24.36 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.34 | 18.30 |
November | 23.81 | 11.18 |
December | 23.29 | 6.79 |
Annual Sum or Average | 24.02 | 17.98 |
Minimum of Months | 23.29 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 8.14 |
February | 22.52 | 10.27 |
March | 23.07 | 12.55 |
April | 24.09 | 19.23 |
May | 24.35 | 23.84 |
June | 24.42 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.18 | 18.30 |
November | 22.82 | 11.18 |
December | 22.00 | 6.79 |
Annual Sum or Average | 23.56 | 17.98 |
Minimum of Months | 22.00 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 8.14 |
February | 22.58 | 10.27 |
March | 23.11 | 12.55 |
April | 24.06 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.21 | 18.30 |
November | 22.95 | 11.18 |
December | 22.09 | 6.79 |
Annual Sum or Average | 23.59 | 17.98 |
Minimum of Months | 22.09 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 8.14 |
February | 22.57 | 10.27 |
March | 23.10 | 12.55 |
April | 24.06 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.21 | 18.30 |
November | 22.93 | 11.18 |
December | 22.08 | 6.79 |
Annual Sum or Average | 23.59 | 17.98 |
Minimum of Months | 22.08 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 8.14 |
February | 23.86 | 10.27 |
March | 23.95 | 12.55 |
April | 24.18 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.42 | 23.38 |
October | 24.38 | 18.30 |
November | 24.04 | 11.18 |
December | 23.68 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.68 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.73 | 8.14 |
February | 23.86 | 10.27 |
March | 23.95 | 12.55 |
April | 24.18 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.42 | 23.38 |
October | 24.38 | 18.30 |
November | 24.04 | 11.18 |
December | 23.68 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.68 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.80 | 8.14 |
February | 24.25 | 10.27 |
March | 24.73 | 12.55 |
April | 25.82 | 19.23 |
May | 26.38 | 23.84 |
June | 26.76 | 27.86 |
July | 26.71 | 27.54 |
August | 26.62 | 26.28 |
September | 26.50 | 23.38 |
October | 25.99 | 18.30 |
November | 24.68 | 11.18 |
December | 23.71 | 6.79 |
Annual Sum or Average | 25.50 | 17.98 |
Minimum of Months | 23.71 | 6.79 |
Maximum of Months | 26.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.36 | 8.14 |
February | 23.57 | 10.27 |
March | 23.76 | 12.55 |
April | 24.15 | 19.23 |
May | 24.34 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.34 | 18.30 |
November | 23.86 | 11.18 |
December | 23.31 | 6.79 |
Annual Sum or Average | 24.02 | 17.98 |
Minimum of Months | 23.31 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 8.14 |
February | 22.58 | 10.27 |
March | 23.12 | 12.55 |
April | 24.06 | 19.23 |
May | 24.33 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.23 | 18.30 |
November | 22.99 | 11.18 |
December | 22.12 | 6.79 |
Annual Sum or Average | 23.60 | 17.98 |
Minimum of Months | 22.12 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 8.14 |
February | 23.53 | 10.27 |
March | 23.74 | 12.55 |
April | 24.17 | 19.23 |
May | 24.35 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.33 | 18.30 |
November | 23.80 | 11.18 |
December | 23.27 | 6.79 |
Annual Sum or Average | 24.01 | 17.98 |
Minimum of Months | 23.27 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 8.14 |
February | 22.52 | 10.27 |
March | 23.04 | 12.55 |
April | 24.07 | 19.23 |
May | 24.35 | 23.84 |
June | 24.43 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.18 | 18.30 |
November | 22.81 | 11.18 |
December | 22.01 | 6.79 |
Annual Sum or Average | 23.56 | 17.98 |
Minimum of Months | 22.01 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 8.14 |
February | 22.59 | 10.27 |
March | 23.11 | 12.55 |
April | 24.05 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.21 | 18.30 |
November | 22.97 | 11.18 |
December | 22.11 | 6.79 |
Annual Sum or Average | 23.60 | 17.98 |
Minimum of Months | 22.11 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 8.14 |
February | 22.59 | 10.27 |
March | 23.10 | 12.55 |
April | 24.05 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.21 | 18.30 |
November | 22.96 | 11.18 |
December | 22.11 | 6.79 |
Annual Sum or Average | 23.59 | 17.98 |
Minimum of Months | 22.11 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.73 | 8.14 |
February | 23.85 | 10.27 |
March | 23.94 | 12.55 |
April | 24.17 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.38 | 18.30 |
November | 24.04 | 11.18 |
December | 23.68 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.68 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.73 | 8.14 |
February | 23.85 | 10.27 |
March | 23.94 | 12.55 |
April | 24.17 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.38 | 18.30 |
November | 24.04 | 11.18 |
December | 23.68 | 6.79 |
Annual Sum or Average | 24.14 | 17.98 |
Minimum of Months | 23.68 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.36 | 8.14 |
February | 24.79 | 10.27 |
March | 25.26 | 12.55 |
April | 26.34 | 19.23 |
May | 26.91 | 23.84 |
June | 27.28 | 27.86 |
July | 27.24 | 27.54 |
August | 27.15 | 26.28 |
September | 27.03 | 23.38 |
October | 26.53 | 18.30 |
November | 25.24 | 11.18 |
December | 24.27 | 6.79 |
Annual Sum or Average | 26.04 | 17.98 |
Minimum of Months | 24.27 | 6.79 |
Maximum of Months | 27.28 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.27 | 8.14 |
February | 23.47 | 10.27 |
March | 23.65 | 12.55 |
April | 24.11 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.32 | 18.30 |
November | 23.80 | 11.18 |
December | 23.23 | 6.79 |
Annual Sum or Average | 23.98 | 17.98 |
Minimum of Months | 23.23 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 8.14 |
February | 22.48 | 10.27 |
March | 22.98 | 12.55 |
April | 24.01 | 19.23 |
May | 24.32 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.19 | 18.30 |
November | 22.87 | 11.18 |
December | 22.06 | 6.79 |
Annual Sum or Average | 23.55 | 17.98 |
Minimum of Months | 22.06 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 8.14 |
February | 23.44 | 10.27 |
March | 23.63 | 12.55 |
April | 24.13 | 19.23 |
May | 24.34 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.31 | 18.30 |
November | 23.74 | 11.18 |
December | 23.19 | 6.79 |
Annual Sum or Average | 23.97 | 17.98 |
Minimum of Months | 23.19 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 8.14 |
February | 22.43 | 10.27 |
March | 22.92 | 12.55 |
April | 24.03 | 19.23 |
May | 24.34 | 23.84 |
June | 24.43 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.13 | 18.30 |
November | 22.70 | 11.18 |
December | 21.96 | 6.79 |
Annual Sum or Average | 23.51 | 17.98 |
Minimum of Months | 21.96 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 8.14 |
February | 22.49 | 10.27 |
March | 22.97 | 12.55 |
April | 24.00 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.17 | 18.30 |
November | 22.85 | 11.18 |
December | 22.05 | 6.79 |
Annual Sum or Average | 23.55 | 17.98 |
Minimum of Months | 22.05 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 8.14 |
February | 22.48 | 10.27 |
March | 22.96 | 12.55 |
April | 24.01 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.17 | 18.30 |
November | 22.83 | 11.18 |
December | 22.04 | 6.79 |
Annual Sum or Average | 23.54 | 17.98 |
Minimum of Months | 22.04 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 8.14 |
February | 23.76 | 10.27 |
March | 23.84 | 12.55 |
April | 24.13 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.36 | 18.30 |
November | 23.99 | 11.18 |
December | 23.60 | 6.79 |
Annual Sum or Average | 24.10 | 17.98 |
Minimum of Months | 23.60 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.64 | 8.14 |
February | 23.76 | 10.27 |
March | 23.84 | 12.55 |
April | 24.13 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.41 | 23.38 |
October | 24.36 | 18.30 |
November | 23.99 | 11.18 |
December | 23.60 | 6.79 |
Annual Sum or Average | 24.10 | 17.98 |
Minimum of Months | 23.60 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 8.14 |
February | 24.14 | 10.27 |
March | 24.59 | 12.55 |
April | 25.75 | 19.23 |
May | 26.35 | 23.84 |
June | 26.75 | 27.86 |
July | 26.70 | 27.54 |
August | 26.61 | 26.28 |
September | 26.48 | 23.38 |
October | 25.94 | 18.30 |
November | 24.59 | 11.18 |
December | 23.64 | 6.79 |
Annual Sum or Average | 25.44 | 17.98 |
Minimum of Months | 23.64 | 6.79 |
Maximum of Months | 26.75 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 8.14 |
February | 23.39 | 10.27 |
March | 23.56 | 12.55 |
April | 24.08 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.31 | 18.30 |
November | 23.75 | 11.18 |
December | 23.17 | 6.79 |
Annual Sum or Average | 23.95 | 17.98 |
Minimum of Months | 23.17 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 8.14 |
February | 22.42 | 10.27 |
March | 22.88 | 12.55 |
April | 23.98 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.16 | 18.30 |
November | 22.78 | 11.18 |
December | 22.02 | 6.79 |
Annual Sum or Average | 23.52 | 17.98 |
Minimum of Months | 22.02 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 8.14 |
February | 23.36 | 10.27 |
March | 23.54 | 12.55 |
April | 24.10 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.29 | 18.30 |
November | 23.69 | 11.18 |
December | 23.13 | 6.79 |
Annual Sum or Average | 23.93 | 17.98 |
Minimum of Months | 23.13 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 8.14 |
February | 22.37 | 10.27 |
March | 22.82 | 12.55 |
April | 23.99 | 19.23 |
May | 24.33 | 23.84 |
June | 24.43 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.09 | 18.30 |
November | 22.61 | 11.18 |
December | 21.93 | 6.79 |
Annual Sum or Average | 23.48 | 17.98 |
Minimum of Months | 21.92 | 6.79 |
Maximum of Months | 24.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 8.14 |
February | 22.42 | 10.27 |
March | 22.86 | 12.55 |
April | 23.97 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.15 | 18.30 |
November | 22.76 | 11.18 |
December | 22.01 | 6.79 |
Annual Sum or Average | 23.51 | 17.98 |
Minimum of Months | 22.01 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 8.14 |
February | 22.42 | 10.27 |
March | 22.86 | 12.55 |
April | 23.97 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.14 | 18.30 |
November | 22.74 | 11.18 |
December | 22.01 | 6.79 |
Annual Sum or Average | 23.51 | 17.98 |
Minimum of Months | 22.01 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 8.14 |
February | 23.69 | 10.27 |
March | 23.76 | 12.55 |
April | 24.09 | 19.23 |
May | 24.31 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.35 | 18.30 |
November | 23.95 | 11.18 |
December | 23.53 | 6.79 |
Annual Sum or Average | 24.07 | 17.98 |
Minimum of Months | 23.53 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 8.14 |
February | 23.69 | 10.27 |
March | 23.76 | 12.55 |
April | 24.10 | 19.23 |
May | 24.31 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.35 | 18.30 |
November | 23.95 | 11.18 |
December | 23.53 | 6.79 |
Annual Sum or Average | 24.07 | 17.98 |
Minimum of Months | 23.53 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.55 | 8.14 |
February | 23.97 | 10.27 |
March | 24.40 | 12.55 |
April | 25.62 | 19.23 |
May | 26.27 | 23.84 |
June | 26.68 | 27.86 |
July | 26.64 | 27.54 |
August | 26.54 | 26.28 |
September | 26.41 | 23.38 |
October | 25.83 | 18.30 |
November | 24.43 | 11.18 |
December | 23.48 | 6.79 |
Annual Sum or Average | 25.32 | 17.98 |
Minimum of Months | 23.48 | 6.79 |
Maximum of Months | 26.68 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 8.14 |
February | 23.32 | 10.27 |
March | 23.48 | 12.55 |
April | 24.05 | 19.23 |
May | 24.31 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.30 | 18.30 |
November | 23.70 | 11.18 |
December | 23.11 | 6.79 |
Annual Sum or Average | 23.92 | 17.98 |
Minimum of Months | 23.11 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 8.14 |
February | 22.37 | 10.27 |
March | 22.81 | 12.55 |
April | 23.95 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.13 | 18.30 |
November | 22.71 | 11.18 |
December | 21.99 | 6.79 |
Annual Sum or Average | 23.49 | 17.98 |
Minimum of Months | 21.99 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.08 | 8.14 |
February | 23.30 | 10.27 |
March | 23.46 | 12.55 |
April | 24.07 | 19.23 |
May | 24.33 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.27 | 18.30 |
November | 23.65 | 11.18 |
December | 23.07 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 23.07 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 8.14 |
February | 22.32 | 10.27 |
March | 22.75 | 12.55 |
April | 23.97 | 19.23 |
May | 24.32 | 23.84 |
June | 24.42 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.06 | 18.30 |
November | 22.55 | 11.18 |
December | 21.91 | 6.79 |
Annual Sum or Average | 23.45 | 17.98 |
Minimum of Months | 21.90 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 8.14 |
February | 22.37 | 10.27 |
March | 22.78 | 12.55 |
April | 23.95 | 19.23 |
May | 24.29 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.35 | 23.38 |
October | 24.12 | 18.30 |
November | 22.68 | 11.18 |
December | 21.98 | 6.79 |
Annual Sum or Average | 23.48 | 17.98 |
Minimum of Months | 21.98 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 8.14 |
February | 22.36 | 10.27 |
March | 22.78 | 12.55 |
April | 23.95 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.35 | 23.38 |
October | 24.12 | 18.30 |
November | 22.67 | 11.18 |
December | 21.97 | 6.79 |
Annual Sum or Average | 23.48 | 17.98 |
Minimum of Months | 21.97 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.50 | 8.14 |
February | 23.62 | 10.27 |
March | 23.68 | 12.55 |
April | 24.07 | 19.23 |
May | 24.30 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.34 | 18.30 |
November | 23.91 | 11.18 |
December | 23.46 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 23.46 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.49 | 8.14 |
February | 23.62 | 10.27 |
March | 23.68 | 12.55 |
April | 24.07 | 19.23 |
May | 24.30 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.40 | 23.38 |
October | 24.34 | 18.30 |
November | 23.91 | 11.18 |
December | 23.46 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 23.46 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.45 | 8.14 |
February | 23.87 | 10.27 |
March | 24.28 | 12.55 |
April | 25.58 | 19.23 |
May | 26.26 | 23.84 |
June | 26.69 | 27.86 |
July | 26.65 | 27.54 |
August | 26.54 | 26.28 |
September | 26.40 | 23.38 |
October | 25.79 | 18.30 |
November | 24.33 | 11.18 |
December | 23.38 | 6.79 |
Annual Sum or Average | 25.27 | 17.98 |
Minimum of Months | 23.38 | 6.79 |
Maximum of Months | 26.69 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 8.14 |
February | 23.23 | 10.27 |
March | 23.39 | 12.55 |
April | 24.02 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.27 | 18.30 |
November | 23.62 | 11.18 |
December | 23.03 | 6.79 |
Annual Sum or Average | 23.88 | 17.98 |
Minimum of Months | 23.03 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 8.14 |
February | 22.34 | 10.27 |
March | 22.76 | 12.55 |
April | 23.92 | 19.23 |
May | 24.30 | 23.84 |
June | 24.41 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.36 | 23.38 |
October | 24.10 | 18.30 |
November | 22.65 | 11.18 |
December | 21.97 | 6.79 |
Annual Sum or Average | 23.47 | 17.98 |
Minimum of Months | 21.97 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.22 | 10.27 |
March | 23.37 | 12.55 |
April | 24.04 | 19.23 |
May | 24.32 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.38 | 23.38 |
October | 24.24 | 18.30 |
November | 23.57 | 11.18 |
December | 22.99 | 6.79 |
Annual Sum or Average | 23.86 | 17.98 |
Minimum of Months | 22.99 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 8.14 |
February | 22.30 | 10.27 |
March | 22.71 | 12.55 |
April | 23.94 | 19.23 |
May | 24.31 | 23.84 |
June | 24.42 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.37 | 23.38 |
October | 24.02 | 18.30 |
November | 22.49 | 11.18 |
December | 21.89 | 6.79 |
Annual Sum or Average | 23.43 | 17.98 |
Minimum of Months | 21.88 | 6.79 |
Maximum of Months | 24.42 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 8.14 |
February | 22.33 | 10.27 |
March | 22.73 | 12.55 |
April | 23.92 | 19.23 |
May | 24.29 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.35 | 23.38 |
October | 24.09 | 18.30 |
November | 22.61 | 11.18 |
December | 21.95 | 6.79 |
Annual Sum or Average | 23.46 | 17.98 |
Minimum of Months | 21.95 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 8.14 |
February | 22.33 | 10.27 |
March | 22.73 | 12.55 |
April | 23.93 | 19.23 |
May | 24.29 | 23.84 |
June | 24.41 | 27.86 |
July | 24.41 | 27.54 |
August | 24.39 | 26.28 |
September | 24.35 | 23.38 |
October | 24.08 | 18.30 |
November | 22.60 | 11.18 |
December | 21.95 | 6.79 |
Annual Sum or Average | 23.46 | 17.98 |
Minimum of Months | 21.95 | 6.79 |
Maximum of Months | 24.41 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 8.14 |
February | 23.51 | 10.27 |
March | 23.57 | 12.55 |
April | 24.04 | 19.23 |
May | 24.30 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.32 | 18.30 |
November | 23.83 | 11.18 |
December | 23.34 | 6.79 |
Annual Sum or Average | 23.99 | 17.98 |
Minimum of Months | 23.34 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 8.14 |
February | 23.51 | 10.27 |
March | 23.57 | 12.55 |
April | 24.04 | 19.23 |
May | 24.30 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.39 | 26.28 |
September | 24.39 | 23.38 |
October | 24.31 | 18.30 |
November | 23.83 | 11.18 |
December | 23.34 | 6.79 |
Annual Sum or Average | 23.99 | 17.98 |
Minimum of Months | 23.34 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 8.14 |
February | 23.75 | 10.27 |
March | 24.18 | 12.55 |
April | 25.58 | 19.23 |
May | 26.33 | 23.84 |
June | 26.82 | 27.86 |
July | 26.77 | 27.54 |
August | 26.65 | 26.28 |
September | 26.48 | 23.38 |
October | 25.76 | 18.30 |
November | 24.20 | 11.18 |
December | 23.23 | 6.79 |
Annual Sum or Average | 25.26 | 17.98 |
Minimum of Months | 23.23 | 6.79 |
Maximum of Months | 26.82 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 8.14 |
February | 23.00 | 10.27 |
March | 23.15 | 12.55 |
April | 23.89 | 19.23 |
May | 24.25 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.34 | 23.38 |
October | 24.09 | 18.30 |
November | 23.28 | 11.18 |
December | 22.82 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 22.82 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 8.14 |
February | 22.43 | 10.27 |
March | 22.74 | 12.55 |
April | 23.81 | 19.23 |
May | 24.25 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.32 | 23.38 |
October | 23.90 | 18.30 |
November | 22.66 | 11.18 |
December | 22.16 | 6.79 |
Annual Sum or Average | 23.47 | 17.98 |
Minimum of Months | 22.16 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.80 | 8.14 |
February | 22.98 | 10.27 |
March | 23.15 | 12.55 |
April | 23.92 | 19.23 |
May | 24.28 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.35 | 23.38 |
October | 24.05 | 18.30 |
November | 23.24 | 11.18 |
December | 22.81 | 6.79 |
Annual Sum or Average | 23.73 | 17.98 |
Minimum of Months | 22.80 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 8.14 |
February | 22.41 | 10.27 |
March | 22.72 | 12.55 |
April | 23.84 | 19.23 |
May | 24.27 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.33 | 23.38 |
October | 23.84 | 18.30 |
November | 22.54 | 11.18 |
December | 22.04 | 6.79 |
Annual Sum or Average | 23.44 | 17.98 |
Minimum of Months | 22.03 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 8.14 |
February | 22.39 | 10.27 |
March | 22.70 | 12.55 |
April | 23.82 | 19.23 |
May | 24.25 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.31 | 23.38 |
October | 23.92 | 18.30 |
November | 22.60 | 11.18 |
December | 22.07 | 6.79 |
Annual Sum or Average | 23.45 | 17.98 |
Minimum of Months | 22.07 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 8.14 |
February | 22.39 | 10.27 |
March | 22.70 | 12.55 |
April | 23.82 | 19.23 |
May | 24.25 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.31 | 23.38 |
October | 23.92 | 18.30 |
November | 22.59 | 11.18 |
December | 22.06 | 6.79 |
Annual Sum or Average | 23.45 | 17.98 |
Minimum of Months | 22.06 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.19 | 10.27 |
March | 23.28 | 12.55 |
April | 23.93 | 19.23 |
May | 24.26 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.35 | 23.38 |
October | 24.18 | 18.30 |
November | 23.46 | 11.18 |
December | 22.99 | 6.79 |
Annual Sum or Average | 23.82 | 17.98 |
Minimum of Months | 22.99 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 8.14 |
February | 23.19 | 10.27 |
March | 23.29 | 12.55 |
April | 23.93 | 19.23 |
May | 24.26 | 23.84 |
June | 24.39 | 27.86 |
July | 24.40 | 27.54 |
August | 24.38 | 26.28 |
September | 24.35 | 23.38 |
October | 24.18 | 18.30 |
November | 23.45 | 11.18 |
December | 22.99 | 6.79 |
Annual Sum or Average | 23.82 | 17.98 |
Minimum of Months | 22.99 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.43 | 8.14 |
February | 23.98 | 10.27 |
March | 24.51 | 12.55 |
April | 26.20 | 19.23 |
May | 27.13 | 23.84 |
June | 27.84 | 27.86 |
July | 27.80 | 27.54 |
August | 27.61 | 26.28 |
September | 27.28 | 23.38 |
October | 26.25 | 18.30 |
November | 24.39 | 11.18 |
December | 23.29 | 6.79 |
Annual Sum or Average | 25.82 | 17.98 |
Minimum of Months | 23.29 | 6.79 |
Maximum of Months | 27.84 | 27.86 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.219868E+12 | 115309.641 | 02-JAN-18:15 | 13120.457 | 57042.023 | 22038.649 | 0.000 | 8607.827 | 10364.000 | 1833.522 | 315.352 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.196895E+12 | 124882.929 | 23-FEB-18:45 | 13120.457 | 57042.023 | 22038.649 | 18496.270 | 0.000 | 10364.000 | 1833.522 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.213439E+12 | 134733.724 | 21-MAR-16:15 | 11327.174 | 57142.088 | 22038.649 | 0.000 | 39186.502 | 0.000 | 1833.522 | 1210.593 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.243107E+12 | 159018.747 | 21-APR-19:30 | 14401.373 | 49889.926 | 22038.649 | 0.000 | 57172.852 | 10364.000 | 1833.522 | 1677.122 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.282953E+12 | 161295.026 | 19-MAY-17:15 | 13120.457 | 57042.023 | 22038.649 | 0.000 | 63211.557 | 0.000 | 1833.522 | 2061.006 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.306755E+12 | 164932.931 | 14-JUN-19:15 | 14401.373 | 49889.926 | 22038.649 | 0.000 | 62805.975 | 10364.000 | 1833.522 | 1958.181 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.328232E+12 | 165905.791 | 17-JUL-19:00 | 14401.373 | 49889.926 | 22038.649 | 0.000 | 63390.957 | 10364.000 | 1833.522 | 2346.059 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.311634E+12 | 164054.064 | 07-AUG-18:00 | 14401.373 | 51749.961 | 22038.649 | 0.000 | 59786.260 | 10364.000 | 1833.522 | 2119.273 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.287734E+12 | 158929.557 | 15-SEP-18:30 | 14401.373 | 51749.961 | 22038.649 | 0.000 | 54809.465 | 10364.000 | 1833.522 | 1971.562 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.250078E+12 | 161398.300 | 05-OCT-17:45 | 13120.457 | 57042.023 | 22038.649 | 0.000 | 53044.857 | 10364.000 | 1833.522 | 1966.783 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.213757E+12 | 126050.204 | 03-NOV-16:15 | 11327.174 | 57142.088 | 22038.649 | 0.000 | 30453.495 | 0.000 | 1833.522 | 1260.080 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.221405E+12 | 115373.087 | 07-DEC-18:00 | 13120.457 | 57042.023 | 22038.649 | 0.000 | 8687.530 | 10364.000 | 1833.522 | 298.898 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.307586E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.196895E+12 | 115309.641 | 11327.174 | 49889.926 | 22038.649 | 0.000 | 0.000 | 0.000 | 1833.522 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.328232E+12 | 165905.791 | 14401.373 | 57142.088 | 22038.649 | 18496.270 | 63390.957 | 10364.000 | 1833.522 | 2346.059 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.113375E+12 | 156451.273 | 27-JAN-06:00 | 0.000 | 0.000 | 0.000 | 156451.273 | 75135.826 | 75135.826 | 81315.448 |
February | 0.991224E+11 | 145933.386 | 02-FEB-06:30 | 0.000 | 0.000 | 0.000 | 145933.386 | 73167.262 | 73167.262 | 72766.124 |
March | 0.960748E+11 | 127273.095 | 02-MAR-06:00 | 0.000 | 0.000 | 0.000 | 127273.095 | 74557.886 | 74557.886 | 52715.208 |
April | 0.842838E+11 | 81115.041 | 11-APR-05:45 | 0.000 | 0.000 | 0.000 | 81115.041 | 72168.514 | 72168.514 | 8946.528 |
May | 0.793840E+11 | 72650.350 | 01-MAY-06:45 | 0.000 | 0.000 | 0.000 | 72650.350 | 72650.350 | 72650.350 | 0.000 |
June | 0.708862E+11 | 70531.161 | 02-JUN-06:00 | 0.000 | 0.000 | 0.000 | 70531.161 | 70531.161 | 70531.161 | 0.000 |
July | 0.696886E+11 | 69151.443 | 02-JUL-06:00 | 0.000 | 0.000 | 0.000 | 69151.443 | 69151.443 | 69151.443 | 0.000 |
August | 0.696887E+11 | 69162.369 | 30-AUG-06:00 | 0.000 | 0.000 | 0.000 | 69162.369 | 69162.369 | 69162.369 | 0.000 |
September | 0.708857E+11 | 70509.808 | 29-SEP-06:45 | 0.000 | 0.000 | 0.000 | 70509.808 | 70509.808 | 70509.808 | 0.000 |
October | 0.793892E+11 | 72664.754 | 31-OCT-06:00 | 0.000 | 0.000 | 0.000 | 72664.754 | 72664.754 | 72664.754 | 0.000 |
November | 0.890291E+11 | 140875.871 | 28-NOV-06:45 | 0.000 | 0.000 | 0.000 | 140875.871 | 72656.310 | 72656.310 | 68219.561 |
December | 0.114683E+12 | 158857.856 | 27-DEC-07:30 | 0.000 | 0.000 | 0.000 | 158857.856 | 76170.724 | 76170.724 | 82687.131 |
Annual Sum or Average | 0.103649E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.696886E+11 | 69151.443 | 0.000 | 0.000 | 0.000 | 69151.443 | 69151.443 | 69151.443 | 0.000 | |
Maximum of Months | 0.114683E+12 | 158857.856 | 0.000 | 0.000 | 0.000 | 158857.856 | 76170.724 | 76170.724 | 82687.131 |