Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300

Simulation Timestamp: 2015-09-09 19:00:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 5654.51 721.56 800.93
Net Site Energy 5654.51 721.56 800.93
Total Source Energy 12631.01 1611.82 1789.12
Net Source Energy 12631.01 1611.82 1789.12


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 361.26 1355.40 0.00 0.00 0.00 0.00
Cooling 382.22 0.00 0.00 0.00 0.00 0.00
Interior Lighting 296.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 162.68 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 652.60 0.00 0.00 0.00 0.00 0.00
Pumps 74.60 0.00 0.00 0.00 0.00 0.00
Heat Rejection 17.81 0.00 0.00 0.00 0.00 1086.63
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1177.88 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3121.23 2533.28 0.00 0.00 0.00 5865.14
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 1355.40 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 361.26 0.00 0.00 0.00 0.00 0.00
Cooling General 382.22 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 242.55 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 54.01 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 162.68 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 652.60 0.00 0.00 0.00 0.00 0.00
Pumps General 74.60 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 17.81 0.00 0.00 0.00 0.00 1086.63
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1177.88 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.05 0.00 0.00 0.00 0.00 0.00
HVAC 210.84 358.83 0.00 0.00 0.00 0.83
Other 161.10 0.00 0.00 0.00 0.00 0.00
Total 442.11 358.83 0.00 0.00 0.00 0.83


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 58.60 0.00 0.00 0.00 0.00 0.00
HVAC 189.94 323.27 0.00 0.00 0.00 0.75
Other 145.13 0.00 0.00 0.00 0.00 0.00
Total 398.29 323.27 0.00 0.00 0.00 0.75


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3121.23 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3121.23 100.00
     
Total On-Site and Utility Electric Sources 3121.23 100.00
Total Electricity End Uses 3121.23 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 5865.14 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 5865.14 100.00
Total Water End Uses 5865.14 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 95.50
Time Setpoint Not Met During Occupied Cooling 99.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 3332.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
RunPeriod Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Weather File Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Latitude [deg] 41.98
Longitude [deg] -87.9
Elevation [m] 201.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 29.5362 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 6.7128   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 13.4255   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   264.3872
Total 7836.48     23884.04   3855.02 1150.39 4.3335 39.48 8.6291
Conditioned Total 7059.89     21517.16   3752.84 1125.85 3.9979 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 7.3840   26.4387
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JAN-22:00 27-JAN-07:30 - - - 17-JUL-17:15
Heating 143682.79 359120.69 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 9277.71 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 37445.77 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 20693.73 0.00 0.00 0.00 0.00 0.00
Pumps 2423.23 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 83123.27 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 225073.24 442243.97 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 359120.69 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 7711.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 1566.35 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 37445.77 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 20693.73 0.00 0.00 0.00 0.00 0.00
Pumps General 2423.23 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 83123.27 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 1144.11 1469.26 0.00 0.00 0.00
Cooling 1210.49 0.00 0.00 0.00 0.00
Interior Lighting 939.20 0.00 0.00 0.00 0.00
Exterior Lighting 515.22 0.00 0.00 0.00 0.00
Interior Equipment 3601.91 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2066.78 0.00 0.00 0.00 0.00
Pumps 236.27 0.00 0.00 0.00 0.00
Heat Rejection 56.42 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1276.82 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9884.93 2746.08 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 162.06 208.11 0.00 0.00 0.00
Cooling 171.46 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 72.98 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 292.75 0.00 0.00 0.00 0.00
Pumps 33.47 0.00 0.00 0.00 0.00
Heat Rejection 7.99 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 180.86 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1400.15 388.97 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 162.06 208.11 0.00 0.00 0.00
Cooling 171.46 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 72.98 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 292.75 0.00 0.00 0.00 0.00
Pumps 33.47 0.00 0.00 0.00 0.00
Heat Rejection 7.99 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 180.86 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1400.15 388.97 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB -20.00 0.00 -20.00 Wetbulb [C] 4.90 270.00
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 33.30 10.50 23.70 Wetbulb [C] 5.20 230.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.36 0.00 0.00 3.36 3.36 2.653 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.653 0.426 0.308              
North Total or Average           423.59 2.653 0.426 0.308              
Non-North Total or Average           726.80 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
OFFICE_LIGHTS_HARDWIRED OFFICE 14.7681 88.25 1303.26 GeneralLights LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
OFFICE_LIGHTS_PLUGIN OFFICE 14.7681 88.25 1303.26 GeneralLights-plugin LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 6.7128 77.66 521.30 GeneralLights-plugin LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.2679 14974.03 33959.19               296.56


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10364.00 AstronomicalClock -   83.62 83.62 162.68
Exterior Lighting Total 10364.00           162.68



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 343550.24 0.75    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 274840.19      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4140.37 2697.65 1442.72 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3911.89 2531.58 1380.31 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   6065.88 4013.16 2052.72 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3398.08 2133.35 1264.73 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2483.70 1510.60 973.10 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2495.49 1515.11 980.38 0.61 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2818.88 1759.22 1059.66 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2909.06 1825.57 1083.50 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5223.49 3452.12 1771.37 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4919.15 3227.28 1691.87 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5097.48 3353.19 1744.30 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3965.61 2538.79 1426.82 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2928.72 1828.34 1100.38 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2907.84 1813.38 1094.46 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3550.23 2270.19 1280.04 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3583.17 2294.59 1288.58 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5339.02 3506.78 1832.23 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5043.96 3289.78 1754.18 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4928.50 3198.05 1730.45 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4100.64 2610.28 1490.36 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3038.46 1892.14 1146.32 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3018.11 1877.60 1140.51 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3652.42 2328.82 1323.60 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3667.67 2340.12 1327.56 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5425.18 3547.88 1877.30 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5130.31 3331.71 1798.59 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4988.88 3221.24 1767.64 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4176.10 2646.52 1529.58 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3098.50 1925.21 1173.28 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3078.14 1910.72 1167.42 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3711.32 2359.82 1351.50 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3724.07 2369.25 1354.83 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5524.31 3602.91 1921.39 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5230.08 3387.70 1842.38 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5087.12 3276.40 1810.72 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4266.51 2697.19 1569.32 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3175.15 1972.09 1203.06 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3154.84 1957.66 1197.19 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3786.74 2405.21 1381.52 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3799.14 2414.37 1384.77 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5532.66 3593.88 1938.77 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5236.44 3377.90 1858.54 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5097.36 3269.76 1827.60 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4264.65 2683.71 1580.94 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3163.78 1957.24 1206.54 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3143.50 1942.89 1200.61 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3775.80 2388.96 1386.84 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3788.19 2398.08 1390.11 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5564.48 3604.19 1960.29 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5267.73 3388.33 1879.39 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5133.63 3283.67 1849.96 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4288.45 2690.45 1598.00 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3178.75 1962.18 1216.57 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3158.50 1947.90 1210.60 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3790.41 2392.51 1397.90 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3802.82 2401.62 1401.20 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5610.30 3626.22 1984.07 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5313.34 3410.63 1902.71 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5180.76 3307.28 1873.48 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4437.62 2778.16 1659.46 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3210.23 1979.50 1230.73 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3190.06 1965.30 1224.76 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3820.21 2407.90 1412.31 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3832.67 2417.03 1415.63 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5783.24 3742.31 2040.93 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5486.55 3526.71 1959.84 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   5323.66 3401.35 1922.31 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4722.30 2955.68 1766.62 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3353.34 2076.41 1276.93 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3332.96 2062.02 1270.94 0.62 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3934.56 2484.77 1449.79 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3946.82 2493.76 1453.06 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   6795.65 4472.85 2322.79 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   6351.30 4148.29 2203.00 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   6250.34 4070.40 2179.94 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   5382.81 3423.33 1959.48 0.64 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4048.81 2562.07 1486.74 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   4044.25 2558.67 1485.59 0.63 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   4989.41 3253.82 1735.59 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   5000.97 3262.48 1738.49 0.65 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   4140.37 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   3911.89 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   6065.88 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   3398.08 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2483.70 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2495.49 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2818.88 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2909.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5223.49 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4919.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5097.48 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3965.61 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2928.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2907.84 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3550.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3583.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5339.02 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5043.96 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4928.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4100.64 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3038.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3018.11 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3652.42 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3667.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5425.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5130.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   4988.88 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4176.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3098.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3078.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3711.32 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3724.07 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   5524.31 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   5230.08 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   5087.12 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   4266.51 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3175.15 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3154.84 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3786.74 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3799.14 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5532.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5236.44 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5097.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4264.65 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3163.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3143.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3775.80 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3788.19 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5564.48 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5267.73 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5133.63 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4288.45 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3178.75 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3158.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3790.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3802.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5610.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5313.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5180.76 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4437.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3210.23 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3190.06 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3820.21 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3832.67 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   5783.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   5486.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   5323.66 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   4722.30 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3353.34 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3332.96 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3934.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3946.82 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   6795.65 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   6351.30 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   6250.34 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   5382.81 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   4048.81 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   4044.25 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   4989.41 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   5000.97 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   4974.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   4983.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   5979.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   4984.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   3766.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   3766.90 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   3755.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   3761.92 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   5061.34 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   5060.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   5075.81 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   5056.73 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   3518.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   3518.01 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   3522.03 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   3523.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   5232.35 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   5233.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   5227.27 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   5226.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   3572.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   3572.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   3572.11 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   3572.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   5438.29 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   5440.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   5429.22 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   5430.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   3685.72 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   3685.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   3684.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   3684.38 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   5598.62 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   5599.65 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   5587.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   5588.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   3770.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   3769.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   3769.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   3769.57 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   5800.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   5802.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   5787.77 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   5789.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   3906.26 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   3905.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   3904.98 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   3904.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   5961.20 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   5962.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   5947.53 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   5949.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   4009.59 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   4009.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   4008.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   4008.23 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   6119.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   6120.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   6104.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   6105.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   4115.49 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   4115.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   4114.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   4114.66 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   6426.33 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   6423.71 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   6410.61 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   6407.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   4361.60 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   4361.25 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   4364.47 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   4364.12 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   7306.56 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   7312.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   7291.30 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   7296.89 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   5280.17 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   5279.80 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   5271.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   5271.57 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 260.10 1160.84 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 243.15 1160.84 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 391.53 1160.84 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 198.93 1160.84 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 133.57 1160.84 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 133.57 1160.84 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 159.65 1160.84 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 166.94 1160.84 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 339.25 1160.84 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 315.58 1160.84 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 327.21 1160.84 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 242.76 1160.84 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 168.58 1160.84 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 166.95 1160.84 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 213.32 1160.84 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 216.00 1160.84 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 342.88 1160.84 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 320.09 1160.84 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 307.86 1160.84 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 247.87 1160.84 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 173.77 1160.84 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 172.19 1160.84 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 218.35 1160.84 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 219.60 1160.84 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 345.62 1160.84 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 322.94 1160.84 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 308.68 1160.84 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 250.16 1160.84 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.38 1160.84 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 174.81 1160.84 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 220.70 1160.84 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 221.74 1160.84 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 350.22 1160.84 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 327.66 1160.84 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 313.31 1160.84 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 254.34 1160.84 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 180.69 1160.84 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 179.13 1160.84 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 224.82 1160.84 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 225.83 1160.84 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 348.02 1160.84 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 325.39 1160.84 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 311.40 1160.84 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 251.73 1160.84 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.38 1160.84 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.83 1160.84 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 222.32 1160.84 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 223.32 1160.84 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 348.08 1160.84 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 325.48 1160.84 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 311.73 1160.84 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 251.46 1160.84 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.32 1160.84 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.78 1160.84 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 222.07 1160.84 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 223.08 1160.84 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 349.54 1160.84 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 326.98 1160.84 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 313.38 1160.84 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 259.03 1160.84 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 179.67 1160.84 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.14 1160.84 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 223.19 1160.84 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 224.19 1160.84 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 361.35 1160.84 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 338.79 1160.84 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 322.78 1160.84 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 275.26 1160.84 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 189.72 1160.84 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.17 1160.84 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 230.92 1160.84 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 231.91 1160.84 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 439.24 1160.84 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 404.66 1160.84 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 395.24 1160.84 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 322.95 1160.84 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 238.74 1160.84 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 238.36 1160.84 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 314.72 1160.84 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 315.67 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 224180.02 0.0075 2386.30 319344.75 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2328.04 2793.65 0.187 0.224 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 32.25 0.01496
G NW APARTMENT 2176.40 2611.68 0.175 0.209 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
OFFICE 3504.42 4205.30 0.281 0.337 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
G NE APARTMENT 1605.44 1926.53 0.129 0.155 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 28.86 0.01496
G N1 APARTMENT 1106.69 1328.03 0.089 0.107 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 29.60 0.01496
G N2 APARTMENT 1089.40 1307.28 0.087 0.105 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 29.60 0.01496
G S1 APARTMENT 1429.05 1714.86 0.115 0.138 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
G S2 APARTMENT 1494.27 1793.12 0.120 0.144 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F2 SW APARTMENT 3036.29 3643.55 0.244 0.292 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F2 NW APARTMENT 2824.55 3389.46 0.227 0.272 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F2 SE APARTMENT 2928.56 3514.28 0.235 0.282 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
F2 NE APARTMENT 2172.68 2607.22 0.174 0.209 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 29.31 0.01496
F2 N1 APARTMENT 1508.96 1810.76 0.121 0.145 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 29.60 0.01496
F2 N2 APARTMENT 1494.38 1793.26 0.120 0.144 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 29.60 0.01496
F2 S1 APARTMENT 1909.39 2291.27 0.153 0.184 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F2 S2 APARTMENT 1933.39 2320.07 0.155 0.186 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F3 SW APARTMENT 3068.69 3682.43 0.246 0.295 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F3 NW APARTMENT 2864.89 3437.86 0.230 0.276 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F3 SE APARTMENT 2755.30 3306.36 0.221 0.265 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
F3 NE APARTMENT 2218.37 2662.04 0.178 0.214 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
F3 N1 APARTMENT 1555.38 1866.46 0.125 0.150 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F3 N2 APARTMENT 1541.23 1849.47 0.124 0.148 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F3 S1 APARTMENT 1954.36 2345.24 0.157 0.188 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F3 S2 APARTMENT 1965.49 2358.59 0.158 0.189 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F4 SW APARTMENT 3093.17 3711.80 0.248 0.298 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F4 NW APARTMENT 2890.36 3468.43 0.232 0.278 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F4 SE APARTMENT 2762.51 3315.01 0.222 0.266 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
F4 NE APARTMENT 2238.80 2686.57 0.180 0.216 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
F4 N1 APARTMENT 1578.76 1894.51 0.127 0.152 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F4 N2 APARTMENT 1564.67 1877.61 0.125 0.151 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F4 S1 APARTMENT 1975.36 2370.43 0.158 0.190 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F4 S2 APARTMENT 1984.65 2381.58 0.159 0.191 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
M SW APARTMENT 3134.25 3761.10 0.251 0.302 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
M NW APARTMENT 2932.52 3519.03 0.235 0.282 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
M SE APARTMENT 2803.92 3364.70 0.225 0.270 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
M NE APARTMENT 2276.17 2731.40 0.183 0.219 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
M N1 APARTMENT 1617.32 1940.79 0.130 0.156 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
M N2 APARTMENT 1603.30 1923.96 0.129 0.154 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
M S1 APARTMENT 2012.17 2414.61 0.161 0.194 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
M S2 APARTMENT 2021.20 2425.43 0.162 0.195 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F6 SW APARTMENT 3114.46 3737.35 0.250 0.300 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F6 NW APARTMENT 2912.14 3494.56 0.234 0.280 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F6 SE APARTMENT 2786.75 3344.09 0.224 0.268 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
F6 NE APARTMENT 2252.71 2703.26 0.181 0.217 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
F6 N1 APARTMENT 1596.62 1915.95 0.128 0.154 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F6 N2 APARTMENT 1582.71 1899.26 0.127 0.152 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F6 S1 APARTMENT 1989.77 2387.73 0.160 0.192 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F6 S2 APARTMENT 1998.76 2398.51 0.160 0.192 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F7 SW APARTMENT 3114.98 3737.97 0.250 0.300 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F7 NW APARTMENT 2912.93 3495.51 0.234 0.280 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F7 SE APARTMENT 2789.69 3347.63 0.224 0.269 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F7 NE APARTMENT 2250.32 2700.38 0.181 0.217 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
F7 N1 APARTMENT 1596.07 1915.28 0.128 0.154 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F7 N2 APARTMENT 1582.24 1898.69 0.127 0.152 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F7 S1 APARTMENT 1987.57 2385.08 0.159 0.191 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F7 S2 APARTMENT 1996.54 2395.85 0.160 0.192 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F8 SW APARTMENT 3127.98 3753.57 0.251 0.301 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F8 NW APARTMENT 2926.30 3511.57 0.235 0.282 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F8 SE APARTMENT 2804.42 3365.31 0.225 0.270 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F8 NE APARTMENT 2259.85 2711.82 0.181 0.218 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
F8 N1 APARTMENT 1608.15 1929.78 0.129 0.155 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F8 N2 APARTMENT 1594.42 1913.30 0.128 0.153 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F8 S1 APARTMENT 1997.54 2397.05 0.160 0.192 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F8 S2 APARTMENT 2006.52 2407.83 0.161 0.193 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F9 SW APARTMENT 3233.67 3880.40 0.259 0.311 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
F9 NW APARTMENT 3031.98 3638.38 0.243 0.292 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.04 0.01496
F9 SE APARTMENT 2888.53 3466.24 0.232 0.278 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
F9 NE APARTMENT 2309.48 2771.38 0.185 0.222 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.10 0.01496
F9 N1 APARTMENT 1698.10 2037.72 0.136 0.163 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F9 N2 APARTMENT 1684.18 2021.02 0.135 0.162 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
F9 S1 APARTMENT 2066.71 2480.05 0.166 0.199 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.17 0.01496
F9 S2 APARTMENT 2075.56 2490.67 0.166 0.200 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.17 0.01496
T SW APARTMENT 3930.51 4716.62 0.315 0.378 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 32.98 0.01496
T NW APARTMENT 3621.04 4345.25 0.290 0.349 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 32.25 0.01496
T SE APARTMENT 3536.81 4244.18 0.284 0.340 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
T NE APARTMENT 2824.83 3389.80 0.227 0.272 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.30 0.01496
T N1 APARTMENT 2136.65 2563.98 0.171 0.206 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.30 0.01496
T N2 APARTMENT 2133.26 2559.92 0.171 0.205 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.30 0.01496
T S1 APARTMENT 2816.61 3379.94 0.226 0.271 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
T S2 APARTMENT 2825.18 3390.21 0.227 0.272 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 3125.64 3750.77 0.142 0.171 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G NW APARTMENT 3132.83 3759.39 0.143 0.171 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
OFFICE 3468.57 4162.28 0.158 0.190 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -20.00 0.00065
G NE APARTMENT 3133.92 3760.70 0.143 0.171 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G N1 APARTMENT 2104.13 2524.96 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G N2 APARTMENT 2104.15 2524.97 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G S1 APARTMENT 2094.63 2513.55 0.095 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G S2 APARTMENT 2099.93 2519.91 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
F2 SW APARTMENT 3198.87 3838.64 0.146 0.175 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 NW APARTMENT 3198.04 3837.65 0.146 0.175 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 SE APARTMENT 3211.11 3853.33 0.146 0.176 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 NE APARTMENT 3194.97 3833.97 0.146 0.175 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 N1 APARTMENT 1893.78 2272.54 0.086 0.104 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 N2 APARTMENT 1893.71 2272.46 0.086 0.104 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 S1 APARTMENT 1897.12 2276.54 0.086 0.104 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F2 S2 APARTMENT 1897.99 2277.59 0.086 0.104 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 SW APARTMENT 3343.51 4012.21 0.152 0.183 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 NW APARTMENT 3344.46 4013.35 0.152 0.183 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 SE APARTMENT 3339.21 4007.06 0.152 0.183 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 NE APARTMENT 3338.61 4006.33 0.152 0.183 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 N1 APARTMENT 1939.57 2327.48 0.088 0.106 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 N2 APARTMENT 1939.44 2327.33 0.088 0.106 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 S1 APARTMENT 1939.48 2327.37 0.088 0.106 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F3 S2 APARTMENT 1939.48 2327.38 0.088 0.106 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 SW APARTMENT 3517.67 4221.21 0.160 0.192 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 NW APARTMENT 3519.27 4223.12 0.160 0.192 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 SE APARTMENT 3510.00 4212.00 0.160 0.192 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 NE APARTMENT 3511.45 4213.74 0.160 0.192 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 N1 APARTMENT 2035.56 2442.67 0.093 0.111 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 N2 APARTMENT 2035.38 2442.46 0.093 0.111 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 S1 APARTMENT 2034.58 2441.50 0.093 0.111 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F4 S2 APARTMENT 2034.42 2441.31 0.093 0.111 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M SW APARTMENT 3653.27 4383.92 0.166 0.200 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M NW APARTMENT 3654.14 4384.97 0.166 0.200 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M SE APARTMENT 3643.95 4372.75 0.166 0.199 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M NE APARTMENT 3644.82 4373.78 0.166 0.199 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M N1 APARTMENT 2107.01 2528.41 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M N2 APARTMENT 2106.79 2528.15 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M S1 APARTMENT 2106.68 2528.02 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
M S2 APARTMENT 2106.47 2527.77 0.096 0.115 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 SW APARTMENT 3823.78 4588.53 0.174 0.209 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 NW APARTMENT 3825.42 4590.50 0.174 0.209 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 SE APARTMENT 3813.23 4575.88 0.174 0.208 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 NE APARTMENT 3814.87 4577.85 0.174 0.209 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 N1 APARTMENT 2222.07 2666.49 0.101 0.121 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 N2 APARTMENT 2221.83 2666.20 0.101 0.121 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 S1 APARTMENT 2220.99 2665.19 0.101 0.121 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F6 S2 APARTMENT 2220.75 2664.90 0.101 0.121 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 SW APARTMENT 3959.90 4751.88 0.180 0.216 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 NW APARTMENT 3961.35 4753.62 0.180 0.217 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 SE APARTMENT 3948.34 4738.01 0.180 0.216 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 NE APARTMENT 3949.79 4739.75 0.180 0.216 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 N1 APARTMENT 2309.46 2771.35 0.105 0.126 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 N2 APARTMENT 2309.19 2771.03 0.105 0.126 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 S1 APARTMENT 2308.57 2770.28 0.105 0.126 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F7 S2 APARTMENT 2308.31 2769.97 0.105 0.126 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 SW APARTMENT 4093.37 4912.05 0.186 0.224 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 NW APARTMENT 4094.35 4913.22 0.187 0.224 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 SE APARTMENT 4080.95 4897.14 0.186 0.223 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 NE APARTMENT 4081.92 4898.31 0.186 0.223 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 N1 APARTMENT 2399.02 2878.82 0.109 0.131 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 N2 APARTMENT 2398.74 2878.48 0.109 0.131 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 S1 APARTMENT 2398.60 2878.32 0.109 0.131 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F8 S2 APARTMENT 2398.32 2877.98 0.109 0.131 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 SW APARTMENT 4353.26 5223.91 0.198 0.238 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 NW APARTMENT 4351.04 5221.25 0.198 0.238 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 SE APARTMENT 4339.96 5207.95 0.198 0.237 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 NE APARTMENT 4337.75 5205.30 0.198 0.237 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 N1 APARTMENT 2607.15 3128.58 0.119 0.143 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 N2 APARTMENT 2606.85 3128.22 0.119 0.143 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 S1 APARTMENT 2609.57 3131.49 0.119 0.143 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
F9 S2 APARTMENT 2609.27 3131.13 0.119 0.143 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T SW APARTMENT 5097.64 6117.17 0.232 0.279 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T NW APARTMENT 5102.38 6122.85 0.232 0.279 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T SE APARTMENT 5084.74 6101.68 0.232 0.278 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T NE APARTMENT 5089.47 6107.36 0.232 0.278 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T N1 APARTMENT 3383.95 4060.74 0.154 0.185 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T N2 APARTMENT 3383.64 4060.36 0.154 0.185 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T S1 APARTMENT 3376.99 4052.38 0.154 0.185 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065
T S2 APARTMENT 3376.67 4052.01 0.154 0.185 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -20.00 0.00065


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.22 0.22 0.17 0.17
AIRLOOP G NW 0.21 0.21 0.17 0.17
AIRLOOP OFFICE 0.34 0.34 0.19 0.19
AIRLOOP G NE 0.15 0.15 0.17 0.17
AIRLOOP G N1 0.11 0.11 0.12 0.12
AIRLOOP G N2 0.10 0.10 0.12 0.12
AIRLOOP G S1 0.14 0.14 0.11 0.11
AIRLOOP G S2 0.14 0.14 0.11 0.11
AIRLOOP F2 SW 0.29 0.29 0.17 0.17
AIRLOOP F2 NW 0.27 0.27 0.17 0.17
AIRLOOP F2 SE 0.28 0.28 0.18 0.18
AIRLOOP F2 NE 0.21 0.21 0.17 0.17
AIRLOOP F2 N1 0.15 0.15 0.10 0.10
AIRLOOP F2 N2 0.14 0.14 0.10 0.10
AIRLOOP F2 S1 0.18 0.18 0.10 0.10
AIRLOOP F2 S2 0.19 0.19 0.10 0.10
AIRLOOP F3 SW 0.30 0.30 0.18 0.18
AIRLOOP F3 NW 0.28 0.28 0.18 0.18
AIRLOOP F3 SE 0.27 0.27 0.18 0.18
AIRLOOP F3 NE 0.21 0.21 0.18 0.18
AIRLOOP F3 N1 0.15 0.15 0.11 0.11
AIRLOOP F3 N2 0.15 0.15 0.11 0.11
AIRLOOP F3 S1 0.19 0.19 0.11 0.11
AIRLOOP F3 S2 0.19 0.19 0.11 0.11
AIRLOOP F4 SW 0.30 0.30 0.19 0.19
AIRLOOP F4 NW 0.28 0.28 0.19 0.19
AIRLOOP F4 SE 0.27 0.27 0.19 0.19
AIRLOOP F4 NE 0.22 0.22 0.19 0.19
AIRLOOP F4 N1 0.15 0.15 0.11 0.11
AIRLOOP F4 N2 0.15 0.15 0.11 0.11
AIRLOOP F4 S1 0.19 0.19 0.11 0.11
AIRLOOP F4 S2 0.19 0.19 0.11 0.11
AIRLOOP M SW 0.30 0.30 0.20 0.20
AIRLOOP M NW 0.28 0.28 0.20 0.20
AIRLOOP M SE 0.27 0.27 0.20 0.20
AIRLOOP M NE 0.22 0.22 0.20 0.20
AIRLOOP M N1 0.16 0.16 0.12 0.12
AIRLOOP M N2 0.15 0.15 0.12 0.12
AIRLOOP M S1 0.19 0.19 0.12 0.12
AIRLOOP M S2 0.19 0.19 0.12 0.12
AIRLOOP F6 SW 0.30 0.30 0.21 0.21
AIRLOOP F6 NW 0.28 0.28 0.21 0.21
AIRLOOP F6 SE 0.27 0.27 0.21 0.21
AIRLOOP F6 NE 0.22 0.22 0.21 0.21
AIRLOOP F6 N1 0.15 0.15 0.12 0.12
AIRLOOP F6 N2 0.15 0.15 0.12 0.12
AIRLOOP F6 S1 0.19 0.19 0.12 0.12
AIRLOOP F6 S2 0.19 0.19 0.12 0.12
AIRLOOP F7 SW 0.30 0.30 0.22 0.22
AIRLOOP F7 NW 0.28 0.28 0.22 0.22
AIRLOOP F7 SE 0.27 0.27 0.22 0.22
AIRLOOP F7 NE 0.22 0.22 0.22 0.22
AIRLOOP F7 N1 0.15 0.15 0.13 0.13
AIRLOOP F7 N2 0.15 0.15 0.13 0.13
AIRLOOP F7 S1 0.19 0.19 0.13 0.13
AIRLOOP F7 S2 0.19 0.19 0.13 0.13
AIRLOOP F8 SW 0.30 0.30 0.22 0.22
AIRLOOP F8 NW 0.28 0.28 0.22 0.22
AIRLOOP F8 SE 0.27 0.27 0.22 0.22
AIRLOOP F8 NE 0.22 0.22 0.22 0.22
AIRLOOP F8 N1 0.15 0.15 0.13 0.13
AIRLOOP F8 N2 0.15 0.15 0.13 0.13
AIRLOOP F8 S1 0.19 0.19 0.13 0.13
AIRLOOP F8 S2 0.19 0.19 0.13 0.13
AIRLOOP F9 SW 0.31 0.31 0.24 0.24
AIRLOOP F9 NW 0.29 0.29 0.24 0.24
AIRLOOP F9 SE 0.28 0.28 0.24 0.24
AIRLOOP F9 NE 0.22 0.22 0.24 0.24
AIRLOOP F9 N1 0.16 0.16 0.14 0.14
AIRLOOP F9 N2 0.16 0.16 0.14 0.14
AIRLOOP F9 S1 0.20 0.20 0.14 0.14
AIRLOOP F9 S2 0.20 0.20 0.14 0.14
AIRLOOP T SW 0.38 0.38 0.28 0.28
AIRLOOP T NW 0.35 0.35 0.28 0.28
AIRLOOP T SE 0.34 0.34 0.28 0.28
AIRLOOP T NE 0.27 0.27 0.28 0.28
AIRLOOP T N1 0.21 0.21 0.19 0.19
AIRLOOP T N2 0.21 0.21 0.18 0.18
AIRLOOP T S1 0.27 0.27 0.18 0.18
AIRLOOP T S2 0.27 0.27 0.18 0.18



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3642.25 6467.50 1797.00
G NW APARTMENT 3984.25 6837.25 2416.75
OFFICE 1031.50 973.50 51.75
G NE APARTMENT 3990.00 6793.75 2391.00
G N1 APARTMENT 3175.00 7090.25 1874.00
G N2 APARTMENT 3174.25 7085.25 1870.00
G S1 APARTMENT 3002.50 6590.75 1315.25
G S2 APARTMENT 3021.00 6523.00 1286.75
F2 SW APARTMENT 3625.50 5477.00 1022.75
F2 NW APARTMENT 3709.25 6046.25 1528.25
F2 SE APARTMENT 3723.00 5190.25 892.75
F2 NE APARTMENT 3747.00 6036.75 1519.00
F2 N1 APARTMENT 2975.00 6250.00 1011.50
F2 N2 APARTMENT 2975.50 6249.75 1007.50
F2 S1 APARTMENT 3219.75 5488.50 717.00
F2 S2 APARTMENT 3237.75 5445.25 708.25
F3 SW APARTMENT 3651.75 5359.25 985.75
F3 NW APARTMENT 3698.75 5967.50 1450.75
F3 SE APARTMENT 3703.00 5304.25 949.75
F3 NE APARTMENT 3724.75 5971.25 1448.75
F3 N1 APARTMENT 2991.75 6116.50 933.50
F3 N2 APARTMENT 2988.75 6118.25 930.50
F3 S1 APARTMENT 3320.75 5229.25 673.00
F3 S2 APARTMENT 3327.25 5213.75 670.75
F4 SW APARTMENT 3684.75 5332.25 1005.75
F4 NW APARTMENT 3741.00 5959.50 1486.75
F4 SE APARTMENT 3716.50 5338.50 984.25
F4 NE APARTMENT 3764.25 5964.75 1485.25
F4 N1 APARTMENT 3025.00 6083.50 944.25
F4 N2 APARTMENT 3023.75 6088.00 940.50
F4 S1 APARTMENT 3385.50 5145.25 675.75
F4 S2 APARTMENT 3386.00 5139.00 675.50
M SW APARTMENT 3669.75 5365.50 1010.75
M NW APARTMENT 3730.25 5982.00 1487.75
M SE APARTMENT 3699.75 5375.00 985.25
M NE APARTMENT 3745.00 5981.75 1480.25
M N1 APARTMENT 3017.50 6073.00 928.50
M N2 APARTMENT 3011.25 6084.75 924.75
M S1 APARTMENT 3384.50 5154.75 669.00
M S2 APARTMENT 3386.00 5155.50 669.75
F6 SW APARTMENT 3627.00 5550.00 1088.00
F6 NW APARTMENT 3765.50 6118.50 1626.25
F6 SE APARTMENT 3662.75 5532.25 1055.50
F6 NE APARTMENT 3761.00 6128.50 1597.50
F6 N1 APARTMENT 2987.75 6215.75 1003.75
F6 N2 APARTMENT 2983.75 6223.25 1002.50
F6 S1 APARTMENT 3284.00 5334.75 709.75
F6 S2 APARTMENT 3286.25 5333.50 710.50
F7 SW APARTMENT 3601.25 5654.75 1135.00
F7 NW APARTMENT 3770.25 6214.25 1693.75
F7 SE APARTMENT 3629.50 5631.25 1104.25
F7 NE APARTMENT 3775.75 6234.25 1671.75
F7 N1 APARTMENT 2977.00 6321.25 1064.00
F7 N2 APARTMENT 2975.00 6324.50 1063.75
F7 S1 APARTMENT 3216.00 5466.00 739.50
F7 S2 APARTMENT 3217.00 5463.25 739.25
F8 SW APARTMENT 3585.25 5743.50 1181.25
F8 NW APARTMENT 3784.75 6283.50 1752.75
F8 SE APARTMENT 3605.25 5721.25 1152.25
F8 NE APARTMENT 3799.00 6285.50 1732.25
F8 N1 APARTMENT 2979.00 6390.25 1107.00
F8 N2 APARTMENT 2979.75 6396.00 1108.50
F8 S1 APARTMENT 3158.75 5589.00 765.00
F8 S2 APARTMENT 3159.00 5590.00 765.00
F9 SW APARTMENT 3660.50 5829.75 1306.50
F9 NW APARTMENT 3901.75 6324.25 1891.00
F9 SE APARTMENT 3676.25 5797.00 1273.25
F9 NE APARTMENT 3917.00 6321.75 1865.75
F9 N1 APARTMENT 3091.50 6454.00 1238.25
F9 N2 APARTMENT 3090.75 6458.25 1235.50
F9 S1 APARTMENT 3153.25 5715.25 823.75
F9 S2 APARTMENT 3156.25 5716.50 824.75
T SW APARTMENT 4582.75 6114.75 2422.50
T NW APARTMENT 4826.00 6534.00 2948.25
T SE APARTMENT 4619.25 6080.00 2393.75
T NE APARTMENT 4855.00 6544.00 2944.25
T N1 APARTMENT 4046.00 6641.50 2254.50
T N2 APARTMENT 4045.75 6644.50 2253.50
T S1 APARTMENT 3889.75 6031.25 1727.75
T S2 APARTMENT 3895.25 6029.50 1728.75
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5893.00 7239.25 3332.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 1.25 4.50 1.25 4.50
G NW APARTMENT 1.25 6.75 1.25 6.75
OFFICE 2.00 0.00 0.00 0.00
G NE APARTMENT 2.00 5.25 2.00 5.25
G N1 APARTMENT 3.50 10.50 3.50 10.50
G N2 APARTMENT 4.25 9.00 4.25 9.00
G S1 APARTMENT 1.50 9.75 1.50 9.75
G S2 APARTMENT 1.75 7.00 1.75 7.00
F2 SW APARTMENT 0.50 2.50 0.50 2.50
F2 NW APARTMENT 0.00 4.25 0.00 4.25
F2 SE APARTMENT 1.00 0.00 1.00 0.00
F2 NE APARTMENT 0.50 52.25 0.50 52.25
F2 N1 APARTMENT 3.00 30.00 3.00 30.00
F2 N2 APARTMENT 3.50 33.00 3.50 33.00
F2 S1 APARTMENT 3.50 6.75 3.50 6.75
F2 S2 APARTMENT 3.50 4.25 3.50 4.25
F3 SW APARTMENT 1.00 4.25 1.00 4.25
F3 NW APARTMENT 0.50 6.00 0.50 6.00
F3 SE APARTMENT 0.75 1.75 0.75 1.75
F3 NE APARTMENT 0.75 59.75 0.75 59.75
F3 N1 APARTMENT 3.75 39.75 3.75 39.75
F3 N2 APARTMENT 3.75 45.25 3.75 45.25
F3 S1 APARTMENT 3.25 10.25 3.25 10.25
F3 S2 APARTMENT 3.25 8.25 3.25 8.25
F4 SW APARTMENT 0.50 6.00 0.50 6.00
F4 NW APARTMENT 0.00 7.75 0.00 7.75
F4 SE APARTMENT 1.25 6.25 1.25 6.25
F4 NE APARTMENT 0.00 65.00 0.00 65.00
F4 N1 APARTMENT 3.00 43.50 3.00 43.50
F4 N2 APARTMENT 4.00 48.25 4.00 48.25
F4 S1 APARTMENT 3.00 12.75 3.00 12.75
F4 S2 APARTMENT 3.50 12.00 3.50 12.00
M SW APARTMENT 1.50 6.50 1.50 6.50
M NW APARTMENT 0.00 8.75 0.00 8.75
M SE APARTMENT 0.25 7.50 0.25 7.50
M NE APARTMENT 0.25 69.25 0.25 69.25
M N1 APARTMENT 3.25 45.50 3.25 45.50
M N2 APARTMENT 2.50 50.75 2.50 50.75
M S1 APARTMENT 2.50 14.25 2.50 14.25
M S2 APARTMENT 2.50 12.00 2.50 12.00
F6 SW APARTMENT 0.50 7.50 0.50 7.50
F6 NW APARTMENT 0.00 10.25 0.00 10.25
F6 SE APARTMENT 1.25 9.00 1.25 9.00
F6 NE APARTMENT 0.25 70.75 0.25 70.75
F6 N1 APARTMENT 2.25 47.00 2.25 47.00
F6 N2 APARTMENT 2.50 53.25 2.50 53.25
F6 S1 APARTMENT 2.75 16.50 2.75 16.50
F6 S2 APARTMENT 2.25 15.00 2.25 15.00
F7 SW APARTMENT 0.25 8.00 0.25 8.00
F7 NW APARTMENT 0.25 10.50 0.25 10.50
F7 SE APARTMENT 0.50 11.25 0.50 11.25
F7 NE APARTMENT 0.00 72.75 0.00 72.75
F7 N1 APARTMENT 1.50 48.50 1.50 48.50
F7 N2 APARTMENT 2.00 55.00 2.00 55.00
F7 S1 APARTMENT 3.00 17.75 3.00 17.75
F7 S2 APARTMENT 3.25 17.00 3.25 17.00
F8 SW APARTMENT 0.00 8.25 0.00 8.25
F8 NW APARTMENT 0.00 11.00 0.00 11.00
F8 SE APARTMENT 0.75 12.50 0.75 12.50
F8 NE APARTMENT 0.00 59.75 0.00 59.75
F8 N1 APARTMENT 2.25 50.00 2.25 50.00
F8 N2 APARTMENT 1.75 56.00 1.75 56.00
F8 S1 APARTMENT 3.75 19.25 3.75 19.25
F8 S2 APARTMENT 3.00 18.50 3.00 18.50
F9 SW APARTMENT 0.25 8.00 0.25 8.00
F9 NW APARTMENT 0.00 10.75 0.00 10.75
F9 SE APARTMENT 0.25 12.00 0.25 12.00
F9 NE APARTMENT 0.00 30.75 0.00 30.75
F9 N1 APARTMENT 3.25 43.25 3.25 43.25
F9 N2 APARTMENT 2.25 47.25 2.25 47.25
F9 S1 APARTMENT 1.00 17.75 1.00 17.75
F9 S2 APARTMENT 1.50 16.00 1.50 16.00
T SW APARTMENT 0.25 2.00 0.25 2.00
T NW APARTMENT 0.00 7.25 0.00 7.25
T SE APARTMENT 0.50 3.75 0.50 3.75
T NE APARTMENT 0.00 32.25 0.00 32.25
T N1 APARTMENT 0.50 31.50 0.50 31.50
T N2 APARTMENT 0.00 32.50 0.00 32.50
T S1 APARTMENT 0.75 1.75 0.75 1.75
T S2 APARTMENT 0.25 2.00 0.25 2.00
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 97.25 99.50 95.50 99.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.354 0.207 0.000 0.300
G NW APARTMENT 1.71 2.50 268.96 0.354 0.207 0.000 0.296
OFFICE 0.94 1.00 268.96 0.519 0.237 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.354 0.207 0.000 0.296
G N1 APARTMENT 1.71 2.50 268.96 0.354 0.125 0.000 0.291
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.125 0.000 0.291
G S1 APARTMENT 1.71 2.50 268.96 0.354 0.125 0.000 0.298
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.125 0.000 0.298
F2 SW APARTMENT 1.71 2.50 268.96 0.354 0.297 0.000 0.355
F2 NW APARTMENT 1.71 2.50 268.96 0.354 0.297 0.000 0.351
F2 SE APARTMENT 1.71 2.50 268.96 0.354 0.297 0.000 0.357
F2 NE APARTMENT 1.71 2.50 268.96 0.354 0.297 0.000 0.351
F2 N1 APARTMENT 1.71 2.50 268.96 0.354 0.179 0.000 0.348
F2 N2 APARTMENT 1.71 2.50 268.97 0.354 0.179 0.000 0.348
F2 S1 APARTMENT 1.71 2.50 268.96 0.354 0.179 0.000 0.354
F2 S2 APARTMENT 1.71 2.50 268.97 0.354 0.179 0.000 0.354
F3 SW APARTMENT 1.71 2.50 268.96 0.354 0.352 0.000 0.394
F3 NW APARTMENT 1.71 2.50 268.96 0.354 0.352 0.000 0.390
F3 SE APARTMENT 1.71 2.50 268.96 0.354 0.352 0.000 0.394
F3 NE APARTMENT 1.71 2.50 268.96 0.354 0.352 0.000 0.390
F3 N1 APARTMENT 1.71 2.50 268.96 0.354 0.212 0.000 0.387
F3 N2 APARTMENT 1.71 2.50 268.97 0.354 0.212 0.000 0.387
F3 S1 APARTMENT 1.71 2.50 268.96 0.354 0.212 0.000 0.392
F3 S2 APARTMENT 1.71 2.50 268.97 0.354 0.212 0.000 0.393
F4 SW APARTMENT 1.71 2.50 268.96 0.354 0.393 0.000 0.404
F4 NW APARTMENT 1.71 2.50 268.96 0.354 0.393 0.000 0.402
F4 SE APARTMENT 1.71 2.50 268.96 0.354 0.393 0.000 0.405
F4 NE APARTMENT 1.71 2.50 268.96 0.354 0.393 0.000 0.402
F4 N1 APARTMENT 1.71 2.50 268.96 0.354 0.237 0.000 0.399
F4 N2 APARTMENT 1.71 2.50 268.97 0.354 0.237 0.000 0.399
F4 S1 APARTMENT 1.71 2.50 268.96 0.354 0.237 0.000 0.404
F4 S2 APARTMENT 1.71 2.50 268.97 0.354 0.237 0.000 0.404
M SW APARTMENT 1.71 2.50 268.96 0.354 0.427 0.000 0.426
M NW APARTMENT 1.71 2.50 268.96 0.354 0.427 0.000 0.423
M SE APARTMENT 1.71 2.50 268.96 0.354 0.427 0.000 0.426
M NE APARTMENT 1.71 2.50 268.96 0.354 0.427 0.000 0.423
M N1 APARTMENT 1.71 2.50 268.96 0.354 0.258 0.000 0.421
M N2 APARTMENT 1.71 2.50 268.97 0.354 0.258 0.000 0.421
M S1 APARTMENT 1.71 2.50 268.96 0.354 0.258 0.000 0.425
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.258 0.000 0.425
F6 SW APARTMENT 1.71 2.50 268.96 0.354 0.457 0.000 0.444
F6 NW APARTMENT 1.71 2.50 268.96 0.354 0.456 0.000 0.441
F6 SE APARTMENT 1.71 2.50 268.96 0.354 0.457 0.000 0.445
F6 NE APARTMENT 1.71 2.50 268.96 0.354 0.456 0.000 0.442
F6 N1 APARTMENT 1.71 2.50 268.96 0.354 0.275 0.000 0.439
F6 N2 APARTMENT 1.71 2.50 268.97 0.354 0.275 0.000 0.439
F6 S1 APARTMENT 1.71 2.50 268.96 0.354 0.276 0.000 0.443
F6 S2 APARTMENT 1.71 2.50 268.97 0.354 0.276 0.000 0.443
F7 SW APARTMENT 1.71 2.50 268.96 0.354 0.483 0.000 0.460
F7 NW APARTMENT 1.71 2.50 268.96 0.354 0.482 0.000 0.457
F7 SE APARTMENT 1.71 2.50 268.96 0.354 0.483 0.000 0.460
F7 NE APARTMENT 1.71 2.50 268.96 0.354 0.482 0.000 0.457
F7 N1 APARTMENT 1.71 2.50 268.96 0.354 0.291 0.000 0.455
F7 N2 APARTMENT 1.71 2.50 268.97 0.354 0.291 0.000 0.455
F7 S1 APARTMENT 1.71 2.50 268.96 0.354 0.291 0.000 0.459
F7 S2 APARTMENT 1.71 2.50 268.97 0.354 0.291 0.000 0.459
F8 SW APARTMENT 1.71 2.50 268.96 0.354 0.506 0.000 0.476
F8 NW APARTMENT 1.71 2.50 268.96 0.354 0.506 0.000 0.473
F8 SE APARTMENT 1.71 2.50 268.96 0.354 0.506 0.000 0.477
F8 NE APARTMENT 1.71 2.50 268.96 0.354 0.506 0.000 0.474
F8 N1 APARTMENT 1.71 2.50 268.96 0.354 0.305 0.000 0.471
F8 N2 APARTMENT 1.71 2.50 268.97 0.354 0.305 0.000 0.471
F8 S1 APARTMENT 1.71 2.50 268.96 0.354 0.305 0.000 0.475
F8 S2 APARTMENT 1.71 2.50 268.97 0.354 0.305 0.000 0.475
F9 SW APARTMENT 1.71 2.50 268.96 0.354 0.527 0.000 0.492
F9 NW APARTMENT 1.71 2.50 268.96 0.354 0.527 0.000 0.489
F9 SE APARTMENT 1.71 2.50 268.96 0.354 0.527 0.000 0.492
F9 NE APARTMENT 1.71 2.50 268.96 0.354 0.527 0.000 0.490
F9 N1 APARTMENT 1.71 2.50 268.96 0.354 0.318 0.000 0.487
F9 N2 APARTMENT 1.71 2.50 268.97 0.354 0.318 0.000 0.487
F9 S1 APARTMENT 1.71 2.50 268.96 0.354 0.318 0.000 0.491
F9 S2 APARTMENT 1.71 2.50 268.97 0.354 0.318 0.000 0.491
T SW APARTMENT 1.71 2.50 268.96 0.354 0.547 0.000 0.501
T NW APARTMENT 1.71 2.50 268.96 0.354 0.547 0.000 0.499
T SE APARTMENT 1.71 2.50 268.96 0.354 0.547 0.000 0.502
T NE APARTMENT 1.71 2.50 268.96 0.353 0.547 0.000 0.500
T N1 APARTMENT 1.71 2.50 268.96 0.354 0.330 0.000 0.497
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.330 0.000 0.497
T S1 APARTMENT 1.71 2.50 268.96 0.354 0.330 0.000 0.501
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.330 0.000 0.501
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.501 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4156
Defaulted Fields 814
Fields with Defaults 11184
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
Electricity:Building 1433.88 25760.85 01-JAN-03:15 70162.48 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 296.56 6715.87 01-JAN-00:15 14401.37 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 242.55 5824.91 01-JAN-00:15 11484.27 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 39.38 663.42 01-JAN-00:15 2934.49 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 29.88 469.18 01-JAN-00:15 2345.88 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T CORRIDOR 179.47 1701.70 01-JAN-00:15 10868.20 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 54.01 890.97 01-JAN-00:15 2917.11 01-JAN-19:15
InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.50 194.24 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 163.03 1180.40 01-JAN-00:15 10346.90 01-JAN-07:15
Fans:Electricity 652.60 20693.73 01-JAN-00:15 20693.73 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1432.25 21354.97 06-MAY-02:30 174193.81 27-JAN-01:00
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
ElectricityPurchased:Plant 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
Cogeneration:ElectricityPurchased 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
ElectricityNet:Plant 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
Cogeneration:ElectricityNet 3121.23 55408.02 04-MAY-05:00 225073.24 26-JAN-23:00
ExteriorLights:Electricity 162.68 0.00 01-JAN-07:30 10364.00 01-JAN-00:15
General:ExteriorLights:Electricity 162.68 0.00 01-JAN-07:30 10364.00 01-JAN-00:15
General:Fans:Electricity 652.60 20693.73 01-JAN-00:15 20693.73 01-JAN-00:15
Cooling:Electricity 382.22 0.00 01-JAN-00:15 88567.13 19-JUL-17:00
Heating:Electricity 361.26 0.00 10-MAR-15:45 152757.45 27-JAN-01:00
Electricity:Plant 92.42 36.93 10-MAR-17:15 6030.51 08-JUN-12:15
HeatRejection:Electricity 17.81 0.00 01-JAN-00:15 3607.28 08-JUN-12:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 74.60 36.93 10-MAR-17:15 2423.23 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.44 0.00 01-JAN-00:15 21.60 01-JAN-19:30
WIRED_INT_EQUIP 979.40 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 2533.28 2357.00 12-FEB-00:15 442243.97 27-JAN-07:30
Gas:Plant 2533.28 2357.00 12-FEB-00:15 442243.97 27-JAN-07:30
WaterSystems:Gas 1177.88 2357.00 01-JAN-00:15 83631.21 09-FEB-08:00
Water Heater:WaterSystems:Gas 1177.88 2357.00 01-JAN-00:15 83631.21 09-FEB-08:00
Heating:Gas 1355.40 0.00 11-FEB-13:15 362300.75 27-JAN-01:30
Boiler:Heating:Gas 1355.40 0.00 11-FEB-13:15 362300.75 27-JAN-01:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 1664.44 0.00 01-JAN-00:15 426244.21 22-AUG-13:45
PlantLoopCoolingDemand:HVAC 1664.44 0.00 01-JAN-00:15 426244.21 22-AUG-13:45
CoolingCoils:PlantLoopCoolingDemand 1664.44 0.00 01-JAN-00:15 426244.21 22-AUG-13:45


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 5865.14 0.00 01-JAN-02:15 0.00 17-JUL-17:15
Water:Plant 5865.14 0.00 01-JAN-02:15 0.00 17-JUL-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 5865.14 0.00 01-JAN-02:15 0.00 17-JUL-17:15
MainsWater:Plant 5865.14 0.00 01-JAN-02:15 0.00 17-JUL-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 1086.63 0.00 01-JAN-00:15 0.00 19-JUL-15:00
HeatRejection:MainsWater 1086.63 0.00 01-JAN-00:15 0.00 19-JUL-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 1976.34 465.63 13-AUG-01:15 334770.41 27-JAN-07:15
PlantLoopHeatingDemand:Plant 916.94 465.63 13-AUG-01:15 63279.87 12-FEB-07:30
WaterSystems:PlantLoopHeatingDemand 916.94 465.63 13-AUG-01:15 63279.87 12-FEB-07:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 6398.62 5348.40 02-NOV-01:45 1052703.01 26-JAN-23:00
EnergyTransfer:Building 1773.62 3619.66 03-NOV-21:15 343315.10 27-JAN-01:00
EnergyTransfer:Zone:G SW APARTMENT 18.83 0.02 28-MAR-01:00 3473.91 27-JAN-01:00
Heating:EnergyTransfer 947.16 0.00 11-FEB-16:30 343315.10 27-JAN-01:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 10.78 0.00 05-JAN-14:00 3473.91 27-JAN-01:00
Cooling:EnergyTransfer 826.45 0.00 01-JAN-00:15 187218.09 19-JUL-14:45
Cooling:EnergyTransfer:Zone:G SW APARTMENT 8.05 0.00 01-JAN-00:15 2600.71 05-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 20.30 0.03 03-OCT-02:30 3678.49 27-JAN-08:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 14.35 0.00 11-FEB-14:00 3678.49 27-JAN-08:15
Cooling:EnergyTransfer:Zone:G NW APARTMENT 5.95 0.00 01-JAN-00:15 2261.77 25-JUL-17:15
EnergyTransfer:Zone:OFFICE 24.84 0.05 10-OCT-02:45 3729.16 05-SEP-13:30
Heating:EnergyTransfer:Zone:OFFICE 8.28 0.00 02-JAN-09:15 3352.48 26-JAN-23:00
Cooling:EnergyTransfer:Zone:OFFICE 16.56 0.00 01-JAN-00:15 3729.16 05-SEP-13:30
EnergyTransfer:Zone:G NE APARTMENT 20.14 0.01 21-OCT-02:45 3529.60 27-JAN-01:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 14.14 0.00 11-FEB-16:30 3529.60 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 6.00 0.00 01-JAN-00:15 1779.23 15-JUN-08:45
EnergyTransfer:Zone:G N1 APARTMENT 12.99 0.02 14-AUG-20:15 2373.82 27-JAN-08:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 8.33 0.00 11-FEB-15:30 2373.82 27-JAN-08:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.66 0.00 01-JAN-00:15 1231.81 25-JUL-17:15
EnergyTransfer:Zone:G N2 APARTMENT 12.99 0.01 03-OCT-12:30 2368.75 27-JAN-08:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 8.33 0.00 11-FEB-16:15 2368.75 27-JAN-08:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.66 0.00 01-JAN-00:15 1232.09 25-JUL-17:15
EnergyTransfer:Zone:G S1 APARTMENT 12.17 0.00 02-JUL-07:00 2082.00 27-JAN-01:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 4.95 0.00 01-JAN-10:30 2082.00 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.22 0.00 01-JAN-00:15 1869.82 30-AUG-13:15
EnergyTransfer:Zone:G S2 APARTMENT 12.20 0.00 08-SEP-09:00 2066.55 27-JAN-01:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 4.75 0.00 01-JAN-10:30 2066.55 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.45 0.00 01-JAN-00:15 1922.57 30-AUG-13:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 22.94 0.01 06-NOV-18:45 4176.15 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 9.94 0.00 01-JAN-17:15 4176.15 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 12.99 0.00 01-JAN-00:15 3304.13 05-SEP-15:15
EnergyTransfer:Zone:F2 NW APARTMENT 23.82 0.02 10-MAR-20:15 4279.21 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 14.26 0.00 11-FEB-13:30 4279.21 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 9.56 0.00 01-JAN-00:15 2935.66 25-JUL-17:15
EnergyTransfer:Zone:F2 SE APARTMENT 23.32 0.03 05-OCT-01:00 4100.81 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 9.00 0.00 01-JAN-17:00 4100.81 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 14.32 0.00 01-JAN-00:15 3177.30 28-SEP-12:30
EnergyTransfer:Zone:F2 NE APARTMENT 23.72 0.03 26-MAR-08:45 4290.80 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 13.98 0.00 11-FEB-14:15 4290.80 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 9.75 0.00 01-JAN-00:15 2293.25 16-JUN-08:45
EnergyTransfer:Zone:F2 N1 APARTMENT 14.30 0.00 18-JUN-17:45 2486.09 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 6.67 0.00 16-JAN-19:00 2486.09 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 7.63 0.00 01-JAN-00:15 1689.53 28-JUN-18:15
EnergyTransfer:Zone:F2 N2 APARTMENT 14.31 0.03 09-MAY-13:15 2487.41 27-JAN-01:00
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 6.67 0.00 16-JAN-19:00 2487.41 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 7.64 0.00 01-JAN-00:15 1681.44 28-JUN-18:15
EnergyTransfer:Zone:F2 S1 APARTMENT 15.25 0.10 03-SEP-20:30 2392.21 30-AUG-13:15
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 3.50 0.00 01-JAN-09:30 2375.60 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 11.74 0.00 01-JAN-00:15 2392.21 30-AUG-13:15
EnergyTransfer:Zone:F2 S2 APARTMENT 15.32 0.06 11-AUG-05:45 2409.19 30-AUG-13:15
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 3.46 0.00 01-JAN-09:30 2370.34 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 11.85 0.00 01-JAN-00:15 2409.19 30-AUG-13:15
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 24.10 0.01 16-OCT-11:45 4577.48 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 10.59 0.00 01-JAN-17:00 4577.48 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 13.50 0.00 01-JAN-00:15 3368.82 16-APR-14:30
EnergyTransfer:Zone:F3 NW APARTMENT 25.09 0.00 27-MAR-20:15 4688.62 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 15.02 0.00 11-FEB-13:30 4688.62 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 10.07 0.00 01-JAN-00:15 2991.81 25-JUL-17:15
EnergyTransfer:Zone:F3 SE APARTMENT 24.14 0.08 27-MAR-23:30 4574.25 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 10.28 0.00 01-JAN-17:00 4574.25 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 13.85 0.00 01-JAN-00:15 3149.05 16-APR-13:15
EnergyTransfer:Zone:F3 NE APARTMENT 24.99 0.03 12-OCT-01:30 4697.50 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 14.74 0.00 11-FEB-14:15 4697.50 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 10.25 0.00 01-JAN-00:15 2411.49 16-JUN-09:00
EnergyTransfer:Zone:F3 N1 APARTMENT 15.01 0.03 09-SEP-20:45 2691.34 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 6.76 0.00 01-JAN-17:15 2691.34 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 8.25 0.00 01-JAN-00:15 1852.05 20-JUL-18:00
EnergyTransfer:Zone:F3 N2 APARTMENT 15.02 0.01 12-APR-00:15 2692.61 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 6.76 0.00 01-JAN-17:15 2692.61 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 8.26 0.00 01-JAN-00:15 1847.12 20-JUL-18:00
EnergyTransfer:Zone:F3 S1 APARTMENT 16.10 0.06 24-JUN-08:30 2568.18 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 3.57 0.00 01-JAN-09:30 2568.18 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 12.53 0.00 01-JAN-00:15 2551.36 26-SEP-13:00
EnergyTransfer:Zone:F3 S2 APARTMENT 16.13 0.04 06-AUG-18:15 2568.29 27-JAN-01:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 3.56 0.00 01-JAN-09:30 2568.29 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 12.57 0.00 01-JAN-00:15 2561.84 26-SEP-13:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 25.04 0.04 01-MAY-08:30 4947.41 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 11.58 0.00 01-JAN-17:00 4947.41 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 13.47 0.00 01-JAN-00:15 3415.84 16-APR-14:30
EnergyTransfer:Zone:F4 NW APARTMENT 26.20 0.00 11-OCT-03:15 5062.48 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 16.10 0.00 11-FEB-13:45 5062.48 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 10.10 0.00 01-JAN-00:15 3018.36 25-JUL-17:15
EnergyTransfer:Zone:F4 SE APARTMENT 25.04 0.02 10-APR-19:00 4953.00 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 11.38 0.00 01-JAN-17:00 4953.00 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 13.67 0.00 01-JAN-00:15 3192.39 16-APR-13:15
EnergyTransfer:Zone:F4 NE APARTMENT 26.07 0.00 12-OCT-01:45 5069.35 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 15.79 0.00 11-FEB-14:30 5069.35 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 10.28 0.00 01-JAN-00:15 2442.13 16-JUN-09:00
EnergyTransfer:Zone:F4 N1 APARTMENT 15.59 0.00 18-JUN-10:45 2907.80 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 7.25 0.00 01-JAN-17:15 2907.80 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 8.35 0.00 01-JAN-00:15 1893.21 20-JUL-18:00
EnergyTransfer:Zone:F4 N2 APARTMENT 15.59 0.04 13-SEP-08:45 2909.04 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 7.24 0.00 01-JAN-17:15 2909.04 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 8.35 0.00 01-JAN-00:15 1888.63 20-JUL-18:00
EnergyTransfer:Zone:F4 S1 APARTMENT 16.57 0.00 12-MAY-13:15 2778.93 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 3.97 0.00 01-JAN-10:15 2778.93 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 12.59 0.00 01-JAN-00:15 2610.44 26-SEP-13:00
EnergyTransfer:Zone:F4 S2 APARTMENT 16.58 0.00 30-JUL-05:45 2780.11 27-JAN-01:00
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 3.97 0.00 01-JAN-10:30 2780.11 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 12.61 0.00 01-JAN-00:15 2618.96 26-SEP-13:00
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 25.88 0.03 18-JUN-04:30 5245.21 27-JAN-01:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 12.40 0.00 01-JAN-17:00 5245.21 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 13.47 0.00 01-JAN-00:15 3464.06 16-APR-14:30
EnergyTransfer:Zone:M NW APARTMENT 27.17 0.02 03-OCT-09:45 5360.95 27-JAN-01:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 16.96 0.00 11-FEB-13:45 5360.95 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 10.21 0.00 01-JAN-00:15 3062.09 25-JUL-17:15
EnergyTransfer:Zone:M SE APARTMENT 25.85 0.00 16-AUG-20:30 5250.66 27-JAN-01:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 12.21 0.00 01-JAN-17:00 5250.66 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 13.64 0.00 01-JAN-00:15 3239.00 16-APR-13:15
EnergyTransfer:Zone:M NE APARTMENT 27.01 0.06 19-OCT-12:30 5366.37 27-JAN-01:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 16.64 0.00 11-FEB-14:45 5366.37 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 10.37 0.00 01-JAN-00:15 2487.72 16-JUN-09:00
EnergyTransfer:Zone:M N1 APARTMENT 16.12 0.00 01-MAY-17:00 3078.57 27-JAN-01:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 7.64 0.00 01-JAN-17:15 3078.57 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 8.49 0.00 01-JAN-00:15 1945.24 20-JUL-18:00
EnergyTransfer:Zone:M N2 APARTMENT 16.13 0.05 28-MAY-20:45 3079.77 27-JAN-01:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 7.63 0.00 01-JAN-17:15 3079.77 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 8.49 0.00 01-JAN-00:15 1940.81 20-JUL-18:00
EnergyTransfer:Zone:M S1 APARTMENT 16.95 0.28 29-SEP-09:15 2948.72 27-JAN-01:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 4.31 0.00 01-JAN-10:15 2948.72 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 12.64 0.00 01-JAN-00:15 2659.70 26-SEP-13:00
EnergyTransfer:Zone:M S2 APARTMENT 16.96 0.07 20-NOV-16:15 2950.06 27-JAN-01:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 4.31 0.00 01-JAN-10:15 2950.06 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 12.65 0.00 01-JAN-00:15 2667.83 26-SEP-13:00
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 26.50 0.04 18-JUN-04:45 5556.25 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 13.69 0.00 01-JAN-17:00 5556.25 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 12.81 0.00 01-JAN-00:15 3446.36 16-APR-14:30
EnergyTransfer:Zone:F6 NW APARTMENT 28.16 0.02 13-JUN-02:15 5673.06 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 18.42 0.00 11-FEB-14:00 5673.06 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 9.74 0.00 01-JAN-00:15 3039.55 25-JUL-17:15
EnergyTransfer:Zone:F6 SE APARTMENT 26.44 0.02 05-OCT-02:15 5560.56 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 13.48 0.00 01-JAN-17:00 5560.56 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 12.96 0.00 01-JAN-00:15 3220.73 16-APR-13:15
EnergyTransfer:Zone:F6 NE APARTMENT 27.96 0.02 28-MAR-16:45 5677.30 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 18.08 0.00 11-FEB-15:15 5677.30 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 9.88 0.00 01-JAN-00:15 2470.40 16-JUN-09:00
EnergyTransfer:Zone:F6 N1 APARTMENT 16.57 0.00 08-JUN-20:30 3278.91 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 8.56 0.00 01-JAN-17:15 3278.91 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 8.01 0.00 01-JAN-00:15 1936.21 20-JUL-18:00
EnergyTransfer:Zone:F6 N2 APARTMENT 16.57 0.00 08-NOV-15:30 3280.05 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 8.55 0.00 01-JAN-17:15 3280.05 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 8.02 0.00 01-JAN-00:15 1928.46 20-JUL-18:00
EnergyTransfer:Zone:F6 S1 APARTMENT 16.89 0.05 30-SEP-12:15 3148.22 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 4.99 0.00 01-JAN-10:30 3148.22 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 11.90 0.00 01-JAN-00:15 2632.10 26-SEP-13:00
EnergyTransfer:Zone:F6 S2 APARTMENT 16.90 0.12 13-APR-13:45 3149.54 27-JAN-01:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 5.00 0.00 01-JAN-10:30 3149.54 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 11.90 0.00 01-JAN-00:15 2640.12 26-SEP-13:00
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 27.17 0.02 19-MAR-12:15 5817.85 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 14.74 0.00 01-JAN-17:15 5817.85 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 12.43 0.00 01-JAN-00:15 3447.40 16-APR-14:30
EnergyTransfer:Zone:F7 NW APARTMENT 29.05 0.03 19-APR-13:00 5934.07 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 19.57 0.00 11-FEB-15:30 5934.07 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 9.49 0.00 01-JAN-00:15 3039.23 25-JUL-17:15
EnergyTransfer:Zone:F7 SE APARTMENT 27.08 0.00 05-NOV-23:15 5821.05 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 14.52 0.00 01-JAN-17:00 5821.05 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 12.56 0.00 01-JAN-00:15 3221.81 16-APR-13:15
EnergyTransfer:Zone:F7 NE APARTMENT 28.82 0.01 10-OCT-00:15 5937.30 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 19.21 0.00 11-FEB-16:00 5937.30 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 9.62 0.00 01-JAN-00:15 2473.45 16-JUN-09:00
EnergyTransfer:Zone:F7 N1 APARTMENT 17.01 0.03 21-MAY-20:15 3442.44 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 9.26 0.00 01-JAN-17:15 3442.44 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 7.76 0.00 01-JAN-00:15 1944.84 20-JUL-18:00
EnergyTransfer:Zone:F7 N2 APARTMENT 17.02 0.05 01-JUL-14:30 3443.55 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 9.26 0.00 01-JAN-17:15 3443.55 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 7.76 0.00 01-JAN-00:15 1932.51 20-JUL-18:00
EnergyTransfer:Zone:F7 S1 APARTMENT 17.01 0.01 13-FEB-17:30 3313.50 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 5.56 0.00 01-JAN-10:45 3313.50 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 11.45 0.00 01-JAN-00:15 2618.00 26-SEP-13:00
EnergyTransfer:Zone:F7 S2 APARTMENT 17.01 0.02 16-AUG-20:15 3314.77 27-JAN-01:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 5.56 0.00 01-JAN-10:45 3314.77 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 11.45 0.00 01-JAN-00:15 2626.07 26-SEP-13:00
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 27.94 0.02 19-SEP-23:30 6062.05 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 15.77 0.00 01-JAN-17:15 6062.05 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 12.17 0.00 01-JAN-00:15 3458.96 16-APR-14:30
EnergyTransfer:Zone:F8 NW APARTMENT 30.01 0.00 11-FEB-15:30 6176.84 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 20.67 0.00 11-FEB-15:45 6176.84 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 9.34 0.00 01-JAN-00:15 3051.68 25-JUL-17:15
EnergyTransfer:Zone:F8 SE APARTMENT 27.82 0.00 05-NOV-12:15 6064.25 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 15.53 0.00 01-JAN-17:00 6064.25 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 12.29 0.00 01-JAN-00:15 3236.81 16-APR-13:15
EnergyTransfer:Zone:F8 NE APARTMENT 29.77 0.10 28-OCT-13:30 6179.17 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 20.31 0.00 11-FEB-16:15 6179.17 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 9.46 0.00 01-JAN-00:15 2545.04 16-JUN-09:00
EnergyTransfer:Zone:F8 N1 APARTMENT 17.57 0.07 04-APR-23:15 3597.53 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 9.97 0.00 01-JAN-17:15 3597.53 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 7.61 0.00 01-JAN-00:15 1962.47 20-JUL-18:00
EnergyTransfer:Zone:F8 N2 APARTMENT 17.57 0.04 22-OCT-01:45 3598.58 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 9.96 0.00 01-JAN-17:15 3598.58 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 7.61 0.00 01-JAN-00:15 1949.34 20-JUL-18:00
EnergyTransfer:Zone:F8 S1 APARTMENT 17.27 0.02 13-OCT-14:00 3471.66 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 6.14 0.00 01-JAN-11:15 3471.66 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 11.13 0.00 01-JAN-00:15 2597.42 26-SEP-13:00
EnergyTransfer:Zone:F8 S2 APARTMENT 17.27 0.06 10-FEB-00:30 3472.85 27-JAN-01:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 6.14 0.00 01-JAN-11:00 3472.85 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 11.13 0.00 01-JAN-00:15 2605.62 26-SEP-13:00
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 29.66 0.02 08-AUG-01:00 6408.44 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 17.54 0.00 01-JAN-17:15 6408.44 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 12.12 0.00 01-JAN-00:15 3527.84 16-APR-14:30
EnergyTransfer:Zone:F9 NW APARTMENT 31.99 0.02 23-SEP-03:00 6518.16 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 22.56 0.00 11-FEB-16:00 6518.16 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 9.42 0.00 01-JAN-00:15 3154.43 25-JUL-17:15
EnergyTransfer:Zone:F9 SE APARTMENT 29.46 0.01 22-JUN-22:30 6409.33 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 17.26 0.00 01-JAN-17:15 6409.33 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 12.20 0.00 01-JAN-00:15 3300.65 16-APR-13:15
EnergyTransfer:Zone:F9 NE APARTMENT 31.70 0.01 29-MAR-14:30 6519.33 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 22.19 0.00 11-FEB-16:15 6519.33 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 9.51 0.00 01-JAN-00:15 2692.65 16-JUN-09:00
EnergyTransfer:Zone:F9 N1 APARTMENT 19.02 0.02 09-NOV-05:00 3848.06 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 11.40 0.00 10-FEB-18:15 3848.06 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 7.62 0.00 01-JAN-00:15 2071.91 20-JUL-17:45
EnergyTransfer:Zone:F9 N2 APARTMENT 19.02 0.03 10-AUG-05:45 3849.05 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 11.39 0.00 10-FEB-18:15 3849.05 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 7.63 0.00 01-JAN-00:15 2058.18 20-JUL-17:45
EnergyTransfer:Zone:F9 S1 APARTMENT 18.21 0.06 19-JUN-03:30 3729.20 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 7.30 0.00 01-JAN-16:15 3729.20 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 10.91 0.00 01-JAN-00:15 2522.01 26-SEP-13:00
EnergyTransfer:Zone:F9 S2 APARTMENT 18.22 0.03 26-NOV-11:45 3730.29 27-JAN-01:00
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 7.30 0.00 01-JAN-16:15 3730.29 27-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 10.92 0.00 01-JAN-00:15 2532.06 26-SEP-13:00
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 37.19 0.01 27-SEP-01:45 7429.17 27-JAN-01:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 24.48 0.00 10-JAN-11:00 7429.17 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 12.71 0.00 01-JAN-00:15 4117.05 16-APR-14:15
EnergyTransfer:Zone:T NW APARTMENT 38.86 0.06 09-SEP-03:15 7503.13 27-JAN-01:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 28.78 0.00 11-FEB-16:15 7503.13 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 10.08 0.00 01-JAN-00:15 3714.01 19-JUL-14:45
EnergyTransfer:Zone:T SE APARTMENT 36.65 0.02 22-MAY-00:30 7417.36 27-JAN-01:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 24.07 0.00 10-JAN-10:30 7417.36 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 12.58 0.00 01-JAN-00:15 3822.44 05-SEP-12:00
EnergyTransfer:Zone:T NE APARTMENT 38.18 0.00 27-MAR-19:30 7491.43 27-JAN-01:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 28.22 0.00 11-FEB-16:15 7491.43 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 9.96 0.00 01-JAN-00:15 3113.01 16-JUN-09:00
EnergyTransfer:Zone:T N1 APARTMENT 24.82 0.02 23-FEB-15:00 4770.68 27-JAN-01:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 16.85 0.00 11-FEB-13:00 4770.68 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 7.97 0.00 01-JAN-00:15 2354.51 20-JUL-17:45
EnergyTransfer:Zone:T N2 APARTMENT 24.82 0.01 26-MAR-12:15 4770.95 27-JAN-01:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 16.85 0.00 11-FEB-13:00 4770.95 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 7.97 0.00 01-JAN-00:15 2339.82 30-MAY-18:00
EnergyTransfer:Zone:T S1 APARTMENT 23.81 0.00 21-MAR-18:45 4688.84 27-JAN-01:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 12.99 0.00 02-JAN-13:00 4688.84 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.82 0.00 01-JAN-00:15 3334.72 04-SEP-12:30
EnergyTransfer:Zone:T S2 APARTMENT 23.82 0.04 17-OCT-19:15 4689.15 27-JAN-01:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 12.99 0.00 02-JAN-13:00 4689.15 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.83 0.00 01-JAN-00:15 3348.35 04-SEP-12:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 1932.09 465.63 13-AUG-01:15 332836.44 27-JAN-07:15
WaterSystems:EnergyTransfer 916.94 465.63 13-AUG-01:15 63273.40 12-FEB-07:30
sub cat:WaterSystems:EnergyTransfer 916.94 465.63 13-AUG-01:15 63273.40 12-FEB-07:30
EnergyTransfer:HVAC 2692.92 0.00 10-MAR-17:15 426084.31 27-JAN-01:00
CoolingCoils:EnergyTransfer 1312.49 0.00 01-JAN-00:15 341588.26 22-AUG-13:45
HeatingCoils:EnergyTransfer 1380.42 0.00 10-MAR-15:45 426084.31 27-JAN-01:00
PlantLoopHeatingDemand:HVAC 1059.39 0.00 10-MAR-15:45 273413.85 27-JAN-01:00
HeatingCoils:PlantLoopHeatingDemand 1059.39 0.00 10-MAR-15:45 273413.85 27-JAN-01:00
Boilers:EnergyTransfer 1015.15 0.00 11-FEB-13:15 271725.56 27-JAN-01:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 10.775 -8.053 0.000 0.000 3.858 1.087 12.213 18.374 0.000 0.350 0.000 0.000 -11.643 0.000 -10.735 -16.226
G NW APARTMENT 14.351 -5.945 0.000 0.000 3.878 1.087 12.213 9.809 0.000 0.347 0.000 0.000 -12.235 0.000 -10.472 -13.032
OFFICE 8.279 -16.558 0.000 0.000 0.529 29.882 9.495 18.388 0.000 0.233 0.000 0.000 -11.704 0.000 -7.880 -30.663
G NE APARTMENT 14.140 -6.002 0.000 0.000 3.885 1.087 12.213 9.841 0.000 0.347 0.000 0.000 -12.009 0.000 -10.488 -13.013
G N1 APARTMENT 8.330 -4.664 0.000 0.000 3.888 1.087 12.213 3.802 0.000 0.255 0.000 0.000 -7.694 0.000 -7.247 -9.971
G N2 APARTMENT 8.327 -4.663 0.000 0.000 3.889 1.087 12.213 3.800 0.000 0.255 0.000 0.000 -7.692 0.000 -7.249 -9.967
G S1 APARTMENT 4.950 -7.223 0.000 0.000 3.859 1.087 12.213 12.448 0.000 0.257 0.000 0.000 -7.090 0.000 -7.549 -12.950
G S2 APARTMENT 4.750 -7.454 0.000 0.000 3.854 1.087 12.213 12.431 0.000 0.258 0.000 0.000 -7.106 0.000 -7.593 -12.439
F2 SW APARTMENT 9.941 -12.994 0.000 0.000 3.808 1.087 12.213 17.730 0.000 0.475 0.000 0.000 -12.403 0.000 -14.991 -4.865
F2 NW APARTMENT 14.259 -9.564 0.000 0.000 3.843 1.087 12.213 9.383 0.000 0.470 0.000 0.000 -12.967 0.000 -14.585 -4.139
F2 SE APARTMENT 8.999 -14.319 0.000 0.000 3.799 1.087 12.213 17.778 0.000 0.475 0.000 0.000 -12.339 0.000 -15.137 -2.557
F2 NE APARTMENT 13.975 -9.747 0.000 0.000 3.853 1.087 12.213 9.423 0.000 0.467 0.000 0.000 -12.702 0.000 -14.561 -4.006
F2 N1 APARTMENT 6.671 -7.633 0.000 0.000 3.851 1.087 12.213 3.572 0.000 0.336 0.000 0.000 -8.200 0.000 -9.980 -1.916
F2 N2 APARTMENT 6.670 -7.642 0.000 0.000 3.851 1.087 12.213 3.572 0.000 0.336 0.000 0.000 -8.198 0.000 -9.979 -1.910
F2 S1 APARTMENT 3.504 -11.742 0.000 0.000 3.800 1.087 12.213 12.036 0.000 0.343 0.000 0.000 -7.555 0.000 -10.434 -3.251
F2 S2 APARTMENT 3.463 -11.854 0.000 0.000 3.798 1.087 12.213 12.030 0.000 0.343 0.000 0.000 -7.562 0.000 -10.452 -3.065
F3 SW APARTMENT 10.592 -13.503 0.000 0.000 3.802 1.087 12.213 17.485 0.000 0.582 0.000 0.000 -12.635 0.000 -17.379 -2.244
F3 NW APARTMENT 15.021 -10.067 0.000 0.000 3.838 1.087 12.213 9.239 0.000 0.576 0.000 0.000 -13.218 0.000 -16.940 -1.747
F3 SE APARTMENT 10.283 -13.853 0.000 0.000 3.805 1.087 12.213 17.592 0.000 0.582 0.000 0.000 -12.474 0.000 -17.416 -1.819
F3 NE APARTMENT 14.735 -10.255 0.000 0.000 3.848 1.087 12.213 9.283 0.000 0.569 0.000 0.000 -12.938 0.000 -16.908 -1.634
F3 N1 APARTMENT 6.763 -8.250 0.000 0.000 3.842 1.087 12.213 3.504 0.000 0.416 0.329 0.000 -8.371 0.000 -11.532 -0.000
F3 N2 APARTMENT 6.764 -8.258 0.000 0.000 3.843 1.087 12.213 3.503 0.000 0.415 0.332 0.000 -8.368 0.000 -11.530 -0.000
F3 S1 APARTMENT 3.569 -12.531 0.000 0.000 3.789 1.087 12.213 11.869 0.000 0.426 0.001 0.000 -7.713 0.000 -12.027 -0.680
F3 S2 APARTMENT 3.561 -12.567 0.000 0.000 3.788 1.087 12.213 11.866 0.000 0.426 0.001 0.000 -7.714 0.000 -12.034 -0.626
F4 SW APARTMENT 11.578 -13.466 0.000 0.000 3.803 1.087 12.213 17.335 0.000 0.638 0.000 0.000 -12.756 0.000 -18.868 -1.563
F4 NW APARTMENT 16.098 -10.104 0.000 0.000 3.838 1.087 12.213 9.155 0.000 0.631 0.000 0.000 -13.358 0.000 -18.440 -1.120
F4 SE APARTMENT 11.376 -13.667 0.000 0.000 3.807 1.087 12.213 17.456 0.000 0.637 0.001 0.000 -12.572 0.000 -18.885 -1.453
F4 NE APARTMENT 15.792 -10.276 0.000 0.000 3.847 1.087 12.213 9.201 0.000 0.623 0.000 0.000 -13.068 0.000 -18.406 -1.013
F4 N1 APARTMENT 7.245 -8.347 0.000 0.000 3.839 1.087 12.213 3.467 0.000 0.453 0.935 0.000 -8.466 0.000 -12.425 -0.000
F4 N2 APARTMENT 7.242 -8.352 0.000 0.000 3.840 1.087 12.213 3.466 0.000 0.452 0.939 0.000 -8.463 0.000 -12.423 -0.000
F4 S1 APARTMENT 3.973 -12.593 0.000 0.000 3.787 1.087 12.213 11.768 0.000 0.464 0.006 0.000 -7.793 0.000 -12.910 -0.000
F4 S2 APARTMENT 3.974 -12.608 0.000 0.000 3.787 1.087 12.213 11.766 0.000 0.464 0.023 0.000 -7.792 0.000 -12.914 -0.000
M SW APARTMENT 12.403 -13.472 0.000 0.000 3.805 1.087 12.213 17.221 0.000 0.683 0.000 0.000 -12.851 0.000 -20.327 -0.763
M NW APARTMENT 16.963 -10.209 0.000 0.000 3.839 1.087 12.213 9.092 0.000 0.675 0.000 0.000 -13.469 0.000 -19.886 -0.304
M SE APARTMENT 12.209 -13.641 0.000 0.000 3.810 1.087 12.213 17.347 0.000 0.682 0.000 0.000 -12.657 0.000 -20.340 -0.708
M NE APARTMENT 16.638 -10.371 0.000 0.000 3.848 1.087 12.213 9.140 0.000 0.666 0.000 0.000 -13.173 0.000 -19.850 -0.197
M N1 APARTMENT 7.636 -8.488 0.000 0.000 3.839 1.087 12.213 3.440 0.000 0.482 1.699 0.000 -8.540 0.000 -13.366 -0.001
M N2 APARTMENT 7.634 -8.494 0.000 0.000 3.840 1.087 12.213 3.439 0.000 0.481 1.702 0.000 -8.537 0.000 -13.364 -0.000
M S1 APARTMENT 4.308 -12.637 0.000 0.000 3.788 1.087 12.213 11.691 0.000 0.494 0.775 0.000 -7.853 0.000 -13.865 -0.000
M S2 APARTMENT 4.311 -12.646 0.000 0.000 3.788 1.087 12.213 11.689 0.000 0.494 0.784 0.000 -7.852 0.000 -13.868 -0.000
F6 SW APARTMENT 13.689 -12.813 0.000 0.000 3.813 1.087 12.213 17.162 0.000 0.720 0.000 0.000 -12.870 0.000 -21.516 -1.485
F6 NW APARTMENT 18.421 -9.741 0.000 0.000 3.847 1.087 12.213 9.071 0.000 0.711 0.000 0.000 -13.501 0.000 -21.060 -1.046
F6 SE APARTMENT 13.479 -12.964 0.000 0.000 3.818 1.087 12.213 17.291 0.000 0.718 0.001 0.000 -12.672 0.000 -21.530 -1.440
F6 NE APARTMENT 18.076 -9.883 0.000 0.000 3.856 1.087 12.213 9.120 0.000 0.701 0.000 0.000 -13.201 0.000 -21.023 -0.944
F6 N1 APARTMENT 8.556 -8.013 0.000 0.000 3.847 1.087 12.213 3.437 0.000 0.506 1.026 0.000 -8.558 0.000 -14.100 -0.000
F6 N2 APARTMENT 8.551 -8.015 0.000 0.000 3.848 1.087 12.213 3.436 0.000 0.505 1.030 0.000 -8.556 0.000 -14.097 -0.000
F6 S1 APARTMENT 4.994 -11.898 0.000 0.000 3.797 1.087 12.213 11.651 0.000 0.519 0.121 0.000 -7.862 0.000 -14.621 -0.000
F6 S2 APARTMENT 4.996 -11.902 0.000 0.000 3.797 1.087 12.213 11.649 0.000 0.519 0.126 0.000 -7.860 0.000 -14.624 -0.000
F7 SW APARTMENT 14.744 -12.427 0.000 0.000 3.820 1.087 12.213 17.105 0.000 0.751 0.000 0.000 -12.897 0.000 -22.566 -1.829
F7 NW APARTMENT 19.565 -9.486 0.000 0.000 3.852 1.087 12.213 9.047 0.000 0.742 0.000 0.000 -13.542 0.000 -22.103 -1.374
F7 SE APARTMENT 14.519 -12.563 0.000 0.000 3.825 1.087 12.213 17.237 0.000 0.749 0.000 0.000 -12.696 0.000 -22.583 -1.786
F7 NE APARTMENT 19.206 -9.616 0.000 0.000 3.861 1.087 12.213 9.097 0.000 0.731 0.000 0.000 -13.238 0.000 -22.066 -1.274
F7 N1 APARTMENT 9.258 -7.755 0.000 0.000 3.853 1.087 12.213 3.431 0.000 0.526 0.722 0.000 -8.582 0.000 -14.751 -0.000
F7 N2 APARTMENT 9.255 -7.761 0.000 0.000 3.853 1.087 12.213 3.430 0.000 0.525 0.727 0.000 -8.579 0.000 -14.749 -0.000
F7 S1 APARTMENT 5.559 -11.447 0.000 0.000 3.803 1.087 12.213 11.613 0.000 0.540 0.000 0.000 -7.876 0.000 -15.287 -0.205
F7 S2 APARTMENT 5.559 -11.450 0.000 0.000 3.804 1.087 12.213 11.611 0.000 0.540 0.002 0.000 -7.875 0.000 -15.291 -0.198
F8 SW APARTMENT 15.771 -12.170 0.000 0.000 3.825 1.087 12.213 17.055 0.000 0.785 0.000 0.000 -12.923 0.000 -23.538 -2.104
F8 NW APARTMENT 20.665 -9.341 0.000 0.000 3.856 1.087 12.213 9.024 0.000 0.775 0.000 0.000 -13.580 0.000 -23.071 -1.627
F8 SE APARTMENT 15.529 -12.289 0.000 0.000 3.830 1.087 12.213 17.188 0.000 0.783 0.000 0.000 -12.719 0.000 -23.559 -2.062
F8 NE APARTMENT 20.308 -9.460 0.000 0.000 3.864 1.087 12.213 9.075 0.000 0.766 0.000 0.000 -13.275 0.000 -23.042 -1.536
F8 N1 APARTMENT 9.966 -7.606 0.000 0.000 3.857 1.087 12.213 3.424 0.000 0.549 0.480 0.000 -8.604 0.000 -15.365 -0.000
F8 N2 APARTMENT 9.960 -7.611 0.000 0.000 3.858 1.087 12.213 3.423 0.000 0.549 0.486 0.000 -8.601 0.000 -15.363 -0.000
F8 S1 APARTMENT 6.144 -11.127 0.000 0.000 3.809 1.087 12.213 11.580 0.000 0.565 0.000 0.000 -7.888 0.000 -15.910 -0.471
F8 S2 APARTMENT 6.142 -11.128 0.000 0.000 3.809 1.087 12.213 11.578 0.000 0.565 0.000 0.000 -7.887 0.000 -15.914 -0.465
F9 SW APARTMENT 17.540 -12.123 0.000 0.000 3.830 1.087 12.213 17.022 0.000 0.819 0.000 0.000 -12.920 0.000 -24.421 -3.047
F9 NW APARTMENT 22.564 -9.422 0.000 0.000 3.860 1.087 12.213 9.007 0.000 0.809 0.000 0.000 -13.591 0.000 -23.963 -2.564
F9 SE APARTMENT 17.257 -12.203 0.000 0.000 3.835 1.087 12.213 17.156 0.000 0.817 0.000 0.000 -12.715 0.000 -24.447 -2.999
F9 NE APARTMENT 22.193 -9.509 0.000 0.000 3.867 1.087 12.213 9.059 0.000 0.803 0.000 0.000 -13.285 0.000 -23.946 -2.483
F9 N1 APARTMENT 11.396 -7.624 0.000 0.000 3.861 1.087 12.213 3.420 0.000 0.576 0.000 0.000 -8.606 0.000 -15.933 -0.389
F9 N2 APARTMENT 11.389 -7.627 0.000 0.000 3.861 1.087 12.213 3.419 0.000 0.576 0.000 0.000 -8.604 0.000 -15.932 -0.382
F9 S1 APARTMENT 7.301 -10.912 0.000 0.000 3.816 1.087 12.213 11.560 0.000 0.591 0.000 0.000 -7.881 0.000 -16.471 -1.304
F9 S2 APARTMENT 7.300 -10.915 0.000 0.000 3.816 1.087 12.213 11.558 0.000 0.591 0.000 0.000 -7.879 0.000 -16.475 -1.296
T SW APARTMENT 24.480 -12.710 0.000 0.000 3.854 1.087 12.213 16.793 0.000 0.841 0.000 0.000 -12.461 0.000 -25.156 -8.940
T NW APARTMENT 28.779 -10.081 0.000 0.000 3.876 1.087 12.213 8.832 0.000 0.830 0.000 0.000 -13.180 0.000 -24.737 -7.616
T SE APARTMENT 24.068 -12.584 0.000 0.000 3.859 1.087 12.213 16.948 0.000 0.840 0.000 0.000 -12.275 0.000 -25.192 -8.964
T NE APARTMENT 28.219 -9.955 0.000 0.000 3.885 1.087 12.213 8.907 0.000 0.825 0.000 0.000 -12.893 0.000 -24.719 -7.568
T N1 APARTMENT 16.852 -7.967 0.000 0.000 3.877 1.087 12.213 3.360 0.000 0.594 0.000 0.000 -8.330 0.000 -16.408 -5.277
T N2 APARTMENT 16.850 -7.967 0.000 0.000 3.878 1.087 12.213 3.358 0.000 0.594 0.000 0.000 -8.327 0.000 -16.411 -5.273
T S1 APARTMENT 12.990 -10.820 0.000 0.000 3.841 1.087 12.213 11.437 0.000 0.608 0.000 0.000 -7.631 0.000 -16.916 -6.808
T S2 APARTMENT 12.994 -10.828 0.000 0.000 3.841 1.087 12.213 11.434 0.000 0.608 0.000 0.000 -7.628 0.000 -16.923 -6.798
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 4.156 0.000 1.273 44.186 0.000 -2.570 0.000 -63.484 -0.002
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.856 0.000 0.026 0.000 0.000 -1.590 0.000 -1.996 -14.735
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.815 0.000 0.029 0.000 0.000 -1.658 0.000 -2.426 -14.200
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.793 0.000 0.031 0.000 0.000 -1.688 0.000 -2.733 -13.842
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 32.880 0.000 1.767 0.000 0.026 0.000 0.000 -1.729 0.000 -3.076 -29.867
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.776 0.000 0.035 0.000 0.000 -1.703 0.000 -3.163 -13.386
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.776 0.000 0.038 0.000 0.000 -1.696 0.000 -3.315 -13.243
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.772 0.000 0.040 0.000 0.000 -1.696 0.000 -3.461 -13.094
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 1.770 0.000 0.039 0.000 0.000 -1.692 0.000 -3.586 -12.971
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 8.151 1.722 0.000 0.016 0.000 0.000 -1.647 0.000 -3.785 -20.899
Total Facility 947.137 -826.425 0.000 0.000 303.563 296.560 982.450 856.641 0.000 46.771 56.437 0.000 -853.447 0.000 -1412.042 -397.639


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 05-SEP-15:15 0.00 -2600.78 0.00 0.00 48.90 45.40 470.89 3527.40 0.00 71.93 0.00 0.00 0.00 0.00 0.00 -1563.75
G NW APARTMENT 25-JUL-17:08 0.00 -2291.63 0.00 0.00 141.82 87.56 588.62 2361.19 0.00 353.25 0.00 0.00 0.00 0.00 0.00 -1240.81
OFFICE 05-SEP-13:30 0.00 -3728.98 0.00 0.00 65.20 2345.88 588.62 2997.17 0.00 80.22 0.00 0.00 0.00 0.00 0.00 -2348.11
G NE APARTMENT 15-JUN-08:45 0.00 -1779.04 0.00 0.00 40.76 12.97 394.37 2543.29 0.00 358.29 0.00 0.00 0.00 0.00 0.00 -1570.64
G N1 APARTMENT 25-JUL-17:08 0.00 -1244.52 0.00 0.00 141.82 87.56 588.62 475.16 0.00 327.75 0.00 0.00 0.00 0.00 0.00 -376.39
G N2 APARTMENT 25-JUL-17:08 0.00 -1245.26 0.00 0.00 141.81 87.56 588.62 475.70 0.00 329.40 0.00 0.00 0.00 0.00 0.00 -377.82
G S1 APARTMENT 30-AUG-13:15 0.00 -1869.73 0.00 0.00 40.76 12.97 382.60 2695.09 0.00 207.16 0.00 0.00 0.00 0.00 0.00 -1468.85
G S2 APARTMENT 30-AUG-13:15 0.00 -1922.48 0.00 0.00 40.76 12.97 382.60 2694.02 0.00 207.15 0.00 0.00 0.00 0.00 0.00 -1415.02
F2 SW APARTMENT 05-SEP-15:15 0.00 -3304.24 0.00 0.00 48.90 45.40 470.89 3489.61 0.00 103.02 0.00 0.00 0.00 0.00 0.00 -853.59
F2 NW APARTMENT 25-JUL-17:08 0.00 -2973.57 0.00 0.00 141.82 87.56 588.62 2325.76 0.00 456.29 0.00 0.00 0.00 0.00 0.00 -626.48
F2 SE APARTMENT 28-SEP-12:30 0.00 -3177.17 0.00 0.00 40.76 12.97 388.49 3827.77 0.00 184.46 0.00 0.00 0.00 0.00 0.00 -1277.28
F2 NE APARTMENT 16-JUN-08:45 0.00 -2293.48 0.00 0.00 40.76 12.97 394.37 2373.00 0.00 361.18 0.00 0.00 0.00 0.00 0.00 -888.80
F2 N1 APARTMENT 28-JUN-18:15 0.00 -1690.36 0.00 0.00 141.83 103.77 547.42 457.00 0.00 296.61 143.73 0.00 0.00 0.00 0.00 0.00
F2 N2 APARTMENT 28-JUN-18:15 0.00 -1682.27 0.00 0.00 141.83 103.77 547.42 457.16 0.00 296.62 135.48 0.00 0.00 0.00 0.00 0.00
F2 S1 APARTMENT 30-AUG-13:15 0.00 -2392.12 0.00 0.00 40.75 12.97 382.60 2672.76 0.00 228.85 0.00 0.00 0.00 0.00 0.00 -945.82
F2 S2 APARTMENT 30-AUG-13:15 0.00 -2409.10 0.00 0.00 40.75 12.97 382.60 2672.47 0.00 228.84 0.00 0.00 0.00 0.00 0.00 -928.55
F3 SW APARTMENT 16-APR-14:30 0.00 -3368.38 0.00 0.00 40.76 22.70 400.26 3538.20 0.00 417.86 0.00 0.00 0.00 0.00 0.00 -1051.41
F3 NW APARTMENT 25-JUL-17:08 0.00 -3047.03 0.00 0.00 141.82 87.56 588.62 2311.26 0.00 518.63 0.00 0.00 0.00 0.00 0.00 -600.86
F3 SE APARTMENT 16-APR-13:15 0.00 -3148.75 0.00 0.00 40.76 12.97 382.60 2906.86 0.00 388.35 0.00 0.00 0.00 0.00 0.00 -582.79
F3 NE APARTMENT 16-JUN-09:00 0.00 -2411.87 0.00 0.00 40.76 12.97 394.37 2346.70 0.00 500.57 0.00 0.00 0.00 0.00 0.00 -883.51
F3 N1 APARTMENT 20-JUL-18:00 0.00 -1852.80 0.00 0.00 141.82 87.56 588.62 358.00 0.00 394.32 282.48 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 20-JUL-18:00 0.00 -1847.87 0.00 0.00 141.82 87.56 588.62 358.09 0.00 394.33 277.45 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 26-SEP-13:00 0.00 -2551.65 0.00 0.00 40.75 12.97 388.49 2692.87 0.00 492.27 0.00 0.00 0.00 0.00 0.00 -1075.70
F3 S2 APARTMENT 26-SEP-13:00 0.00 -2562.13 0.00 0.00 40.75 12.97 388.49 2692.67 0.00 492.27 0.00 0.00 0.00 0.00 0.00 -1065.02
F4 SW APARTMENT 16-APR-14:30 0.00 -3415.37 0.00 0.00 40.76 22.70 400.26 3514.92 0.00 465.48 0.00 0.00 0.00 0.00 0.00 -1028.74
F4 NW APARTMENT 25-JUL-17:08 0.00 -3077.69 0.00 0.00 141.82 87.56 588.62 2301.39 0.00 563.35 0.00 0.00 0.00 0.00 0.00 -605.05
F4 SE APARTMENT 16-APR-13:15 0.00 -3192.08 0.00 0.00 40.76 12.97 382.60 2888.86 0.00 432.50 0.00 0.00 0.00 0.00 0.00 -565.61
F4 NE APARTMENT 16-JUN-09:00 0.00 -2442.54 0.00 0.00 40.76 12.97 394.37 2333.65 0.00 542.18 0.00 0.00 0.00 0.00 0.00 -881.39
F4 N1 APARTMENT 20-JUL-18:00 0.00 -1893.99 0.00 0.00 141.82 87.56 588.62 356.38 0.00 424.73 294.88 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 20-JUL-18:00 0.00 -1889.42 0.00 0.00 141.82 87.56 588.62 356.47 0.00 424.73 290.21 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 26-SEP-13:00 0.00 -2610.76 0.00 0.00 40.75 12.97 388.49 2676.20 0.00 535.70 0.00 0.00 0.00 0.00 0.00 -1043.35
F4 S2 APARTMENT 26-SEP-13:00 0.00 -2619.29 0.00 0.00 40.75 12.97 388.49 2676.04 0.00 535.70 0.00 0.00 0.00 0.00 0.00 -1034.66
M SW APARTMENT 16-APR-14:30 0.00 -3463.58 0.00 0.00 40.76 22.70 400.26 3497.08 0.00 504.14 0.00 0.00 0.00 0.00 0.00 -1001.36
M NW APARTMENT 25-JUL-17:08 0.00 -3125.33 0.00 0.00 141.83 87.56 588.62 2293.06 0.00 599.15 0.00 0.00 0.00 0.00 0.00 -584.88
M SE APARTMENT 16-APR-13:15 0.00 -3238.69 0.00 0.00 40.76 12.97 382.60 2874.88 0.00 468.31 0.00 0.00 0.00 0.00 0.00 -540.83
M NE APARTMENT 16-JUN-09:00 0.00 -2488.15 0.00 0.00 40.76 12.97 394.37 2322.88 0.00 575.44 0.00 0.00 0.00 0.00 0.00 -858.28
M N1 APARTMENT 20-JUL-18:00 0.00 -1946.07 0.00 0.00 141.82 87.56 588.62 354.65 0.00 449.17 324.25 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 20-JUL-18:00 0.00 -1941.64 0.00 0.00 141.82 87.56 588.62 354.73 0.00 449.18 319.73 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 26-SEP-13:00 0.00 -2660.04 0.00 0.00 40.75 12.97 388.49 2663.17 0.00 570.43 0.00 0.00 0.00 0.00 0.00 -1015.77
M S2 APARTMENT 26-SEP-13:00 0.00 -2668.17 0.00 0.00 40.75 12.97 388.49 2663.02 0.00 570.43 0.00 0.00 0.00 0.00 0.00 -1007.48
F6 SW APARTMENT 16-APR-14:30 0.00 -3445.86 0.00 0.00 40.76 22.70 400.26 3484.52 0.00 536.96 0.00 0.00 0.00 0.00 0.00 -1039.34
F6 NW APARTMENT 25-JUL-17:08 0.00 -3104.65 0.00 0.00 141.83 87.56 588.62 2287.74 0.00 628.11 0.00 0.00 0.00 0.00 0.00 -629.20
F6 SE APARTMENT 16-APR-13:15 0.00 -3220.40 0.00 0.00 40.76 12.97 382.60 2865.35 0.00 498.67 0.00 0.00 0.00 0.00 0.00 -579.94
F6 NE APARTMENT 16-JUN-09:00 0.00 -2470.84 0.00 0.00 40.75 12.97 394.37 2315.57 0.00 602.30 0.00 0.00 0.00 0.00 0.00 -895.14
F6 N1 APARTMENT 20-JUL-18:00 0.00 -1937.05 0.00 0.00 141.83 87.56 588.62 354.22 0.00 469.56 295.27 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 20-JUL-18:00 0.00 -1929.30 0.00 0.00 141.83 87.56 588.62 354.30 0.00 469.09 287.91 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 26-SEP-13:00 0.00 -2632.46 0.00 0.00 40.75 12.97 388.49 2653.77 0.00 599.30 0.00 0.00 0.00 0.00 0.00 -1062.82
F6 S2 APARTMENT 26-SEP-13:00 0.00 -2640.47 0.00 0.00 40.75 12.97 388.49 2653.62 0.00 599.29 0.00 0.00 0.00 0.00 0.00 -1054.65
F7 SW APARTMENT 16-APR-14:30 0.00 -3446.89 0.00 0.00 40.76 22.70 400.26 3473.54 0.00 565.60 0.00 0.00 0.00 0.00 0.00 -1055.97
F7 NW APARTMENT 25-JUL-17:08 0.00 -3106.44 0.00 0.00 141.83 87.56 588.62 2282.49 0.00 652.88 0.00 0.00 0.00 0.00 0.00 -646.93
F7 SE APARTMENT 16-APR-13:15 0.00 -3221.48 0.00 0.00 40.76 12.97 382.60 2856.84 0.00 525.13 0.00 0.00 0.00 0.00 0.00 -596.82
F7 NE APARTMENT 16-JUN-09:00 0.00 -2473.91 0.00 0.00 40.75 12.97 394.37 2308.60 0.00 625.16 0.00 0.00 0.00 0.00 0.00 -907.95
F7 N1 APARTMENT 20-JUL-18:00 0.00 -1945.69 0.00 0.00 141.83 87.56 588.62 353.45 0.00 486.94 287.31 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 20-JUL-18:00 0.00 -1933.36 0.00 0.00 141.83 87.56 588.62 353.53 0.00 485.79 276.04 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 26-SEP-13:00 0.00 -2618.36 0.00 0.00 40.75 12.97 388.49 2645.57 0.00 623.86 0.00 0.00 0.00 0.00 0.00 -1093.28
F7 S2 APARTMENT 26-SEP-13:00 0.00 -2626.43 0.00 0.00 40.75 12.97 388.49 2645.41 0.00 623.86 0.00 0.00 0.00 0.00 0.00 -1085.05
F8 SW APARTMENT 16-APR-14:30 0.00 -3458.44 0.00 0.00 40.76 22.70 400.26 3463.78 0.00 591.06 0.00 0.00 0.00 0.00 0.00 -1060.12
F8 NW APARTMENT 25-JUL-17:08 0.00 -3121.10 0.00 0.00 141.83 87.56 588.62 2277.59 0.00 674.51 0.00 0.00 0.00 0.00 0.00 -649.01
F8 SE APARTMENT 16-APR-13:15 0.00 -3236.47 0.00 0.00 40.76 12.97 382.60 2849.05 0.00 548.63 0.00 0.00 0.00 0.00 0.00 -597.54
F8 NE APARTMENT 16-JUN-09:00 0.00 -2545.45 0.00 0.00 40.76 12.97 394.37 2302.37 0.00 656.94 0.00 0.00 0.00 0.00 0.00 -861.96
F8 N1 APARTMENT 20-JUL-18:00 0.00 -1963.35 0.00 0.00 141.83 87.56 588.62 352.47 0.00 501.96 290.91 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 20-JUL-18:00 0.00 -1950.21 0.00 0.00 141.83 87.56 588.62 352.57 0.00 500.74 278.91 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 26-SEP-13:00 0.00 -2597.79 0.00 0.00 40.75 12.97 388.49 2638.60 0.00 645.08 0.00 0.00 0.00 0.00 0.00 -1128.10
F8 S2 APARTMENT 26-SEP-13:00 0.00 -2605.99 0.00 0.00 40.75 12.97 388.49 2638.44 0.00 645.08 0.00 0.00 0.00 0.00 0.00 -1119.74
F9 SW APARTMENT 16-APR-14:30 0.00 -3527.30 0.00 0.00 40.76 22.70 400.26 3453.29 0.00 614.02 0.00 0.00 0.00 0.00 0.00 -1003.73
F9 NW APARTMENT 25-JUL-17:08 0.00 -3228.32 0.00 0.00 141.83 87.56 588.62 2270.63 0.00 696.69 0.00 0.00 0.00 0.00 0.00 -557.01
F9 SE APARTMENT 16-APR-13:15 0.00 -3300.30 0.00 0.00 40.76 12.97 382.60 2840.53 0.00 569.79 0.00 0.00 0.00 0.00 0.00 -546.36
F9 NE APARTMENT 16-JUN-09:00 0.00 -2692.99 0.00 0.00 40.76 12.97 394.37 2295.87 0.00 695.95 0.00 0.00 0.00 0.00 0.00 -746.95
F9 N1 APARTMENT 20-JUL-17:45 0.00 -2073.27 0.00 0.00 141.82 87.56 588.62 411.53 0.00 599.64 244.10 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 20-JUL-17:45 0.00 -2059.54 0.00 0.00 141.82 87.56 588.62 411.65 0.00 598.35 231.53 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 26-SEP-13:00 0.00 -2522.36 0.00 0.00 40.75 12.97 388.49 2633.70 0.00 663.59 0.00 0.00 0.00 0.00 0.00 -1217.14
F9 S2 APARTMENT 26-SEP-13:00 0.00 -2532.41 0.00 0.00 40.75 12.97 388.49 2633.50 0.00 663.59 0.00 0.00 0.00 0.00 0.00 -1206.88
T SW APARTMENT 16-APR-14:15 0.00 -4116.41 0.00 0.00 40.76 22.70 400.26 3504.95 0.00 634.95 0.00 0.00 0.00 0.00 0.00 -487.21
T NW APARTMENT 19-JUL-14:45 0.00 -3714.81 0.00 0.00 40.55 22.70 400.26 2434.59 0.00 911.99 0.00 0.00 0.00 0.00 0.00 -95.27
T SE APARTMENT 05-SEP-12:00 0.00 -3821.92 0.00 0.00 40.76 12.97 406.15 3254.57 0.00 147.66 0.00 0.00 0.00 0.00 0.00 -40.19
T NE APARTMENT 16-JUN-09:00 0.00 -3113.35 0.00 0.00 40.76 12.97 394.37 2261.72 0.00 714.59 0.00 0.00 0.00 0.00 0.00 -311.06
T N1 APARTMENT 20-JUL-17:45 0.00 -2356.15 0.00 0.00 141.82 87.56 588.62 403.01 0.00 628.75 506.39 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 30-MAY-18:00 0.00 -2340.08 0.00 0.00 141.83 87.56 588.62 464.45 0.00 872.43 185.20 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 04-SEP-12:30 0.00 -3334.62 0.00 0.00 40.76 12.97 388.49 2923.13 0.00 340.46 0.00 0.00 0.00 0.00 0.00 -371.18
T S2 APARTMENT 04-SEP-12:30 0.00 -3348.26 0.00 0.00 40.76 12.97 388.49 2922.85 0.00 340.46 0.00 0.00 0.00 0.00 0.00 -357.27
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-JUL-14:45 0.00 -187257.54 0.00 0.00 3240.32 9873.49 32370.09 127933.18 0.00 47043.44 0.00 0.00 0.00 0.00 0.00 -33202.98


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 27-JAN-01:00 3473.28 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1652.28 0.00 -1878.84 -403.19
G NW APARTMENT 27-JAN-08:10 3679.03 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -1461.07 0.00 -1642.19 -1057.69
OFFICE 26-JAN-23:00 3352.47 0.00 0.00 0.00 0.00 469.18 194.24 0.00 0.00 0.00 0.00 0.00 -1632.37 0.00 -1944.22 -439.30
G NE APARTMENT 27-JAN-01:00 3528.93 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1653.39 0.00 -1878.86 -457.71
G N1 APARTMENT 27-JAN-08:10 2374.27 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -891.76 0.00 -990.53 -973.89
G N2 APARTMENT 27-JAN-08:10 2369.19 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -891.84 0.00 -990.53 -968.73
G S1 APARTMENT 27-JAN-01:00 2081.52 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1002.30 0.00 -1133.27 -406.98
G S2 APARTMENT 27-JAN-01:00 2066.08 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1002.65 0.00 -1133.27 -391.19
F2 SW APARTMENT 27-JAN-01:00 4175.52 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1711.20 0.00 -2701.37 -224.00
F2 NW APARTMENT 27-JAN-01:00 4278.56 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1732.75 0.00 -2701.37 -305.48
F2 SE APARTMENT 27-JAN-01:00 4100.19 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1695.93 0.00 -2701.37 -163.92
F2 NE APARTMENT 27-JAN-01:00 4290.11 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1714.54 0.00 -2701.38 -335.22
F2 N1 APARTMENT 27-JAN-01:00 2485.58 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1058.27 0.00 -1629.40 -258.94
F2 N2 APARTMENT 27-JAN-01:00 2486.89 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1058.24 0.00 -1629.40 -260.28
F2 S1 APARTMENT 27-JAN-01:00 2375.13 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1033.54 0.00 -1629.40 -173.23
F2 S2 APARTMENT 27-JAN-01:00 2369.87 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1033.66 0.00 -1629.40 -167.86
F3 SW APARTMENT 27-JAN-01:00 4576.84 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1735.93 0.00 -3199.18 -102.77
F3 NW APARTMENT 27-JAN-01:00 4687.96 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1761.70 0.00 -3199.18 -188.10
F3 SE APARTMENT 27-JAN-01:00 4573.60 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1715.06 0.00 -3199.18 -120.38
F3 NE APARTMENT 27-JAN-01:00 4696.80 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1740.71 0.00 -3199.19 -217.93
F3 N1 APARTMENT 27-JAN-01:00 2690.81 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1076.45 0.00 -1929.67 -145.73
F3 N2 APARTMENT 27-JAN-01:00 2692.09 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1076.42 0.00 -1929.67 -147.03
F3 S1 APARTMENT 27-JAN-01:00 2567.70 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1047.06 0.00 -1929.66 -52.01
F3 S2 APARTMENT 27-JAN-01:00 2567.81 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1047.06 0.00 -1929.66 -52.12
F4 SW APARTMENT 27-JAN-01:00 4946.75 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1750.48 0.00 -3576.87 -80.43
F4 NW APARTMENT 27-JAN-01:00 5061.80 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1778.86 0.00 -3576.88 -167.10
F4 SE APARTMENT 27-JAN-01:00 4952.32 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1727.44 0.00 -3576.88 -109.04
F4 NE APARTMENT 27-JAN-01:00 5068.63 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1755.90 0.00 -3576.89 -196.87
F4 N1 APARTMENT 27-JAN-01:00 2907.26 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1087.15 0.00 -2157.49 -123.65
F4 N2 APARTMENT 27-JAN-01:00 2908.49 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1087.12 0.00 -2157.49 -124.91
F4 S1 APARTMENT 27-JAN-01:00 2778.43 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1055.08 0.00 -2157.48 -26.91
F4 S2 APARTMENT 27-JAN-01:00 2779.61 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1055.05 0.00 -2157.48 -28.11
M SW APARTMENT 27-JAN-01:00 5244.54 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1761.77 0.00 -3888.35 -55.46
M NW APARTMENT 27-JAN-01:00 5360.26 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1791.97 0.00 -3888.35 -140.97
M SE APARTMENT 27-JAN-01:00 5249.98 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1737.42 0.00 -3888.35 -85.23
M NE APARTMENT 27-JAN-01:00 5365.64 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1767.77 0.00 -3888.36 -170.54
M N1 APARTMENT 27-JAN-01:00 3078.02 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1095.33 0.00 -2345.36 -98.36
M N2 APARTMENT 27-JAN-01:00 3079.21 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1095.30 0.00 -2345.36 -99.58
M S1 APARTMENT 27-JAN-01:00 2948.21 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1061.34 0.00 -2345.35 -2.56
M S2 APARTMENT 27-JAN-01:00 2949.55 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1061.30 0.00 -2345.35 -3.93
F6 SW APARTMENT 27-JAN-01:00 5555.56 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1768.99 0.00 -4156.89 -90.72
F6 NW APARTMENT 27-JAN-01:00 5672.35 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1800.63 0.00 -4156.89 -175.87
F6 SE APARTMENT 27-JAN-01:00 5559.86 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1743.74 0.00 -4156.89 -120.26
F6 NE APARTMENT 27-JAN-01:00 5676.55 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1775.54 0.00 -4156.90 -205.15
F6 N1 APARTMENT 27-JAN-01:00 3278.33 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1100.61 0.00 -2507.34 -131.41
F6 N2 APARTMENT 27-JAN-01:00 3279.48 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1100.58 0.00 -2507.34 -132.59
F6 S1 APARTMENT 27-JAN-01:00 3147.69 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1065.13 0.00 -2507.33 -36.26
F6 S2 APARTMENT 27-JAN-01:00 3149.01 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1065.10 0.00 -2507.33 -37.62
F7 SW APARTMENT 27-JAN-01:00 5817.15 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1775.48 0.00 -4394.93 -107.78
F7 NW APARTMENT 27-JAN-01:00 5933.35 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1808.27 0.00 -4394.94 -191.18
F7 SE APARTMENT 27-JAN-01:00 5820.34 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1749.52 0.00 -4394.94 -136.91
F7 NE APARTMENT 27-JAN-01:00 5936.54 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1782.46 0.00 -4394.95 -220.16
F7 N1 APARTMENT 27-JAN-01:00 3441.85 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1105.28 0.00 -2650.92 -146.68
F7 N2 APARTMENT 27-JAN-01:00 3442.95 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1105.25 0.00 -2650.93 -147.81
F7 S1 APARTMENT 27-JAN-01:00 3312.96 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1068.91 0.00 -2650.91 -54.16
F7 S2 APARTMENT 27-JAN-01:00 3314.22 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1068.88 0.00 -2650.91 -55.46
F8 SW APARTMENT 27-JAN-01:00 6061.34 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1780.84 0.00 -4610.03 -131.51
F8 NW APARTMENT 27-JAN-01:00 6176.11 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1814.58 0.00 -4610.03 -212.53
F8 SE APARTMENT 27-JAN-01:00 6063.52 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1754.32 0.00 -4610.03 -160.21
F8 NE APARTMENT 27-JAN-01:00 6178.40 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1788.21 0.00 -4610.04 -241.18
F8 N1 APARTMENT 27-JAN-01:00 3596.92 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1109.10 0.00 -2780.66 -168.19
F8 N2 APARTMENT 27-JAN-01:00 3597.97 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1109.07 0.00 -2780.67 -169.27
F8 S1 APARTMENT 27-JAN-01:00 3471.09 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1071.73 0.00 -2780.65 -79.75
F8 S2 APARTMENT 27-JAN-01:00 3472.28 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1071.70 0.00 -2780.65 -80.96
F9 SW APARTMENT 27-JAN-01:00 6407.71 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1781.84 0.00 -4807.11 -279.78
F9 NW APARTMENT 27-JAN-01:00 6517.41 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1816.31 0.00 -4807.12 -355.01
F9 SE APARTMENT 27-JAN-01:00 6408.59 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1754.95 0.00 -4807.12 -307.56
F9 NE APARTMENT 27-JAN-01:00 6518.55 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1789.56 0.00 -4807.13 -382.89
F9 N1 APARTMENT 27-JAN-01:00 3847.43 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1109.97 0.00 -2899.54 -298.95
F9 N2 APARTMENT 27-JAN-01:00 3848.42 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1109.94 0.00 -2899.54 -299.97
F9 S1 APARTMENT 27-JAN-01:00 3728.61 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1071.83 0.00 -2899.53 -218.28
F9 S2 APARTMENT 27-JAN-01:00 3729.70 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1071.81 0.00 -2899.53 -219.40
T SW APARTMENT 27-JAN-01:00 7428.38 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1746.49 0.00 -4989.23 -1153.69
T NW APARTMENT 27-JAN-01:00 7502.32 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1780.39 0.00 -4989.24 -1193.72
T SE APARTMENT 27-JAN-01:00 7416.54 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1720.32 0.00 -4989.24 -1168.02
T NE APARTMENT 27-JAN-01:00 7490.57 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1754.32 0.00 -4989.25 -1208.04
T N1 APARTMENT 27-JAN-01:00 4769.94 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1086.52 0.00 -3009.50 -1134.95
T N2 APARTMENT 27-JAN-01:00 4770.22 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1086.51 0.00 -3009.50 -1135.23
T S1 APARTMENT 27-JAN-01:00 4688.15 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1051.81 0.00 -3009.49 -1087.89
T S2 APARTMENT 27-JAN-01:00 4688.47 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1051.80 0.00 -3009.49 -1088.21
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-JAN-01:00 343265.15 0.00 0.00 0.00 14983.89 6715.87 21178.66 0.00 0.00 0.00 0.00 0.00 -115069.74 0.00 -251202.54 -19871.29



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Sec1.1A-General Information

Data
Weather File Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 95.50
Number of hours cooling loads not met 99.50
Number of hours not met 195.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 296.56 9277.71 0.00 0.00 0.00 0.00
Exterior Lighting 162.68 10364.00 0.00 0.00 0.00 0.00
Space Heating 361.26 143682.79 1355.40 359120.69 0.00 0.00
Space Cooling 382.22 0.00 0.00 0.00 0.00 0.00
Pumps 74.60 2423.23 0.00 0.00 0.00 0.00
Heat Rejection 17.81 0.00 0.00 0.00 0.00 0.00
Fans-Interior 652.60 20693.73 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1177.88 83123.27 0.00 0.00
Receptacle Equipment 1137.32 37445.77 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3121.23   2533.28   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1137.32 3121.23
Natural Gas 0.00 2533.28
Additional 0.00 0.00
Total 1137.32 5654.51


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.84
Space Heating 46.10
Space Cooling 48.77
Fans-Interior 83.28
Service Water Heating 0.00
Receptacle Equipment 145.13
Miscellaneous 37.17
Subtotal 398.29


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 172.96
Service Water Heating 150.31
Miscellaneous -0.00
Subtotal 323.27


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.24
Space Heating 30.36
Space Cooling 6.76
Fans-Interior 11.54
Service Water Heating 20.83
Receptacle Equipment 20.11
Miscellaneous 5.15



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.224065
G NW APARTMENT DIRECT AIR 0.209462
OFFICE DIRECT AIR 0.337282
G NE APARTMENT DIRECT AIR 0.171367
G N1 APARTMENT DIRECT AIR 0.115062
G N2 APARTMENT DIRECT AIR 0.115063
G S1 APARTMENT DIRECT AIR 0.137534
G S2 APARTMENT DIRECT AIR 0.143810
F2 SW APARTMENT DIRECT AIR 0.292244
F2 NW APARTMENT DIRECT AIR 0.271851
F2 SE APARTMENT DIRECT AIR 0.281875
F2 NE APARTMENT DIRECT AIR 0.209124
F2 N1 APARTMENT DIRECT AIR 0.145222
F2 N2 APARTMENT DIRECT AIR 0.143819
F2 S1 APARTMENT DIRECT AIR 0.183767
F2 S2 APARTMENT DIRECT AIR 0.186076
F3 SW APARTMENT DIRECT AIR 0.295372
F3 NW APARTMENT DIRECT AIR 0.275740
F3 SE APARTMENT DIRECT AIR 0.265208
F3 NE APARTMENT DIRECT AIR 0.213529
F3 N1 APARTMENT DIRECT AIR 0.149692
F3 N2 APARTMENT DIRECT AIR 0.148330
F3 S1 APARTMENT DIRECT AIR 0.188100
F3 S2 APARTMENT DIRECT AIR 0.189171
F4 SW APARTMENT DIRECT AIR 0.297736
F4 NW APARTMENT DIRECT AIR 0.278198
F4 SE APARTMENT DIRECT AIR 0.265909
F4 NE APARTMENT DIRECT AIR 0.215501
F4 N1 APARTMENT DIRECT AIR 0.151944
F4 N2 APARTMENT DIRECT AIR 0.150588
F4 S1 APARTMENT DIRECT AIR 0.190123
F4 S2 APARTMENT DIRECT AIR 0.191017
M SW APARTMENT DIRECT AIR 0.301696
M NW APARTMENT DIRECT AIR 0.282260
M SE APARTMENT DIRECT AIR 0.269900
M NE APARTMENT DIRECT AIR 0.219101
M N1 APARTMENT DIRECT AIR 0.155657
M N2 APARTMENT DIRECT AIR 0.154307
M S1 APARTMENT DIRECT AIR 0.193669
M S2 APARTMENT DIRECT AIR 0.194538
F6 SW APARTMENT DIRECT AIR 0.299796
F6 NW APARTMENT DIRECT AIR 0.280302
F6 SE APARTMENT DIRECT AIR 0.268252
F6 NE APARTMENT DIRECT AIR 0.216848
F6 N1 APARTMENT DIRECT AIR 0.153666
F6 N2 APARTMENT DIRECT AIR 0.152327
F6 S1 APARTMENT DIRECT AIR 0.191516
F6 S2 APARTMENT DIRECT AIR 0.192381
F7 SW APARTMENT DIRECT AIR 0.299851
F7 NW APARTMENT DIRECT AIR 0.280381
F7 SE APARTMENT DIRECT AIR 0.268539
F7 NE APARTMENT DIRECT AIR 0.216620
F7 N1 APARTMENT DIRECT AIR 0.153614
F7 N2 APARTMENT DIRECT AIR 0.152283
F7 S1 APARTMENT DIRECT AIR 0.191305
F7 S2 APARTMENT DIRECT AIR 0.192169
F8 SW APARTMENT DIRECT AIR 0.301106
F8 NW APARTMENT DIRECT AIR 0.281671
F8 SE APARTMENT DIRECT AIR 0.269961
F8 NE APARTMENT DIRECT AIR 0.223141
F8 N1 APARTMENT DIRECT AIR 0.154777
F8 N2 APARTMENT DIRECT AIR 0.153456
F8 S1 APARTMENT DIRECT AIR 0.192267
F8 S2 APARTMENT DIRECT AIR 0.193132
F9 SW APARTMENT DIRECT AIR 0.311284
F9 NW APARTMENT DIRECT AIR 0.291846
F9 SE APARTMENT DIRECT AIR 0.278061
F9 NE APARTMENT DIRECT AIR 0.237123
F9 N1 APARTMENT DIRECT AIR 0.163436
F9 N2 APARTMENT DIRECT AIR 0.162096
F9 S1 APARTMENT DIRECT AIR 0.198926
F9 S2 APARTMENT DIRECT AIR 0.199777
T SW APARTMENT DIRECT AIR 0.378381
T NW APARTMENT DIRECT AIR 0.348590
T SE APARTMENT DIRECT AIR 0.340481
T NE APARTMENT DIRECT AIR 0.278204
T N1 APARTMENT DIRECT AIR 0.205663
T N2 APARTMENT DIRECT AIR 0.205337
T S1 APARTMENT DIRECT AIR 0.271113
T S2 APARTMENT DIRECT AIR 0.271937


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.224065
AIRLOOP G NW MAIN BRANCH 0.209462
AIRLOOP OFFICE MAIN BRANCH 0.337282
AIRLOOP G NE MAIN BRANCH 0.171367
AIRLOOP G N1 MAIN BRANCH 0.115062
AIRLOOP G N2 MAIN BRANCH 0.115063
AIRLOOP G S1 MAIN BRANCH 0.137534
AIRLOOP G S2 MAIN BRANCH 0.143810
AIRLOOP F2 SW MAIN BRANCH 0.292244
AIRLOOP F2 NW MAIN BRANCH 0.271851
AIRLOOP F2 SE MAIN BRANCH 0.281875
AIRLOOP F2 NE MAIN BRANCH 0.209124
AIRLOOP F2 N1 MAIN BRANCH 0.145222
AIRLOOP F2 N2 MAIN BRANCH 0.143819
AIRLOOP F2 S1 MAIN BRANCH 0.183767
AIRLOOP F2 S2 MAIN BRANCH 0.186076
AIRLOOP F3 SW MAIN BRANCH 0.295372
AIRLOOP F3 NW MAIN BRANCH 0.275740
AIRLOOP F3 SE MAIN BRANCH 0.265208
AIRLOOP F3 NE MAIN BRANCH 0.213529
AIRLOOP F3 N1 MAIN BRANCH 0.149692
AIRLOOP F3 N2 MAIN BRANCH 0.148330
AIRLOOP F3 S1 MAIN BRANCH 0.188100
AIRLOOP F3 S2 MAIN BRANCH 0.189171
AIRLOOP F4 SW MAIN BRANCH 0.297736
AIRLOOP F4 NW MAIN BRANCH 0.278198
AIRLOOP F4 SE MAIN BRANCH 0.265909
AIRLOOP F4 NE MAIN BRANCH 0.215501
AIRLOOP F4 N1 MAIN BRANCH 0.151944
AIRLOOP F4 N2 MAIN BRANCH 0.150588
AIRLOOP F4 S1 MAIN BRANCH 0.190123
AIRLOOP F4 S2 MAIN BRANCH 0.191017
AIRLOOP M SW MAIN BRANCH 0.301696
AIRLOOP M NW MAIN BRANCH 0.282260
AIRLOOP M SE MAIN BRANCH 0.269900
AIRLOOP M NE MAIN BRANCH 0.219101
AIRLOOP M N1 MAIN BRANCH 0.155657
AIRLOOP M N2 MAIN BRANCH 0.154307
AIRLOOP M S1 MAIN BRANCH 0.193669
AIRLOOP M S2 MAIN BRANCH 0.194538
AIRLOOP F6 SW MAIN BRANCH 0.299796
AIRLOOP F6 NW MAIN BRANCH 0.280302
AIRLOOP F6 SE MAIN BRANCH 0.268252
AIRLOOP F6 NE MAIN BRANCH 0.216848
AIRLOOP F6 N1 MAIN BRANCH 0.153666
AIRLOOP F6 N2 MAIN BRANCH 0.152327
AIRLOOP F6 S1 MAIN BRANCH 0.191516
AIRLOOP F6 S2 MAIN BRANCH 0.192381
AIRLOOP F7 SW MAIN BRANCH 0.299851
AIRLOOP F7 NW MAIN BRANCH 0.280381
AIRLOOP F7 SE MAIN BRANCH 0.268539
AIRLOOP F7 NE MAIN BRANCH 0.216620
AIRLOOP F7 N1 MAIN BRANCH 0.153614
AIRLOOP F7 N2 MAIN BRANCH 0.152283
AIRLOOP F7 S1 MAIN BRANCH 0.191305
AIRLOOP F7 S2 MAIN BRANCH 0.192169
AIRLOOP F8 SW MAIN BRANCH 0.301106
AIRLOOP F8 NW MAIN BRANCH 0.281671
AIRLOOP F8 SE MAIN BRANCH 0.269961
AIRLOOP F8 NE MAIN BRANCH 0.223141
AIRLOOP F8 N1 MAIN BRANCH 0.154777
AIRLOOP F8 N2 MAIN BRANCH 0.153456
AIRLOOP F8 S1 MAIN BRANCH 0.192267
AIRLOOP F8 S2 MAIN BRANCH 0.193132
AIRLOOP F9 SW MAIN BRANCH 0.311284
AIRLOOP F9 NW MAIN BRANCH 0.291846
AIRLOOP F9 SE MAIN BRANCH 0.278061
AIRLOOP F9 NE MAIN BRANCH 0.237123
AIRLOOP F9 N1 MAIN BRANCH 0.163436
AIRLOOP F9 N2 MAIN BRANCH 0.162096
AIRLOOP F9 S1 MAIN BRANCH 0.198926
AIRLOOP F9 S2 MAIN BRANCH 0.199777
AIRLOOP T SW MAIN BRANCH 0.378381
AIRLOOP T NW MAIN BRANCH 0.348590
AIRLOOP T SE MAIN BRANCH 0.340481
AIRLOOP T NE MAIN BRANCH 0.278204
AIRLOOP T N1 MAIN BRANCH 0.205663
AIRLOOP T N2 MAIN BRANCH 0.205337
AIRLOOP T S1 MAIN BRANCH 0.271113
AIRLOOP T S2 MAIN BRANCH 0.271937


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.224065
AIRLOOP G NW 0.209462
AIRLOOP OFFICE 0.337282
AIRLOOP G NE 0.171367
AIRLOOP G N1 0.115062
AIRLOOP G N2 0.115063
AIRLOOP G S1 0.137534
AIRLOOP G S2 0.143810
AIRLOOP F2 SW 0.292244
AIRLOOP F2 NW 0.271851
AIRLOOP F2 SE 0.281875
AIRLOOP F2 NE 0.209124
AIRLOOP F2 N1 0.145222
AIRLOOP F2 N2 0.143819
AIRLOOP F2 S1 0.183767
AIRLOOP F2 S2 0.186076
AIRLOOP F3 SW 0.295372
AIRLOOP F3 NW 0.275740
AIRLOOP F3 SE 0.265208
AIRLOOP F3 NE 0.213529
AIRLOOP F3 N1 0.149692
AIRLOOP F3 N2 0.148330
AIRLOOP F3 S1 0.188100
AIRLOOP F3 S2 0.189171
AIRLOOP F4 SW 0.297736
AIRLOOP F4 NW 0.278198
AIRLOOP F4 SE 0.265909
AIRLOOP F4 NE 0.215501
AIRLOOP F4 N1 0.151944
AIRLOOP F4 N2 0.150588
AIRLOOP F4 S1 0.190123
AIRLOOP F4 S2 0.191017
AIRLOOP M SW 0.301696
AIRLOOP M NW 0.282260
AIRLOOP M SE 0.269900
AIRLOOP M NE 0.219101
AIRLOOP M N1 0.155657
AIRLOOP M N2 0.154307
AIRLOOP M S1 0.193669
AIRLOOP M S2 0.194538
AIRLOOP F6 SW 0.299796
AIRLOOP F6 NW 0.280302
AIRLOOP F6 SE 0.268252
AIRLOOP F6 NE 0.216848
AIRLOOP F6 N1 0.153666
AIRLOOP F6 N2 0.152327
AIRLOOP F6 S1 0.191516
AIRLOOP F6 S2 0.192381
AIRLOOP F7 SW 0.299851
AIRLOOP F7 NW 0.280381
AIRLOOP F7 SE 0.268539
AIRLOOP F7 NE 0.216620
AIRLOOP F7 N1 0.153614
AIRLOOP F7 N2 0.152283
AIRLOOP F7 S1 0.191305
AIRLOOP F7 S2 0.192169
AIRLOOP F8 SW 0.301106
AIRLOOP F8 NW 0.281671
AIRLOOP F8 SE 0.269961
AIRLOOP F8 NE 0.223141
AIRLOOP F8 N1 0.154777
AIRLOOP F8 N2 0.153456
AIRLOOP F8 S1 0.192267
AIRLOOP F8 S2 0.193132
AIRLOOP F9 SW 0.311284
AIRLOOP F9 NW 0.291846
AIRLOOP F9 SE 0.278061
AIRLOOP F9 NE 0.237123
AIRLOOP F9 N1 0.163436
AIRLOOP F9 N2 0.162096
AIRLOOP F9 S1 0.198926
AIRLOOP F9 S2 0.199777
AIRLOOP T SW 0.378381
AIRLOOP T NW 0.348590
AIRLOOP T SE 0.340481
AIRLOOP T NE 0.278204
AIRLOOP T N1 0.205663
AIRLOOP T N2 0.205337
AIRLOOP T S1 0.271113
AIRLOOP T S2 0.271937


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.224065 0.025952
AIRLOOP G NW OA CONTROLLER 0.209462 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.337282 0.038103
AIRLOOP G NE OA CONTROLLER 0.171367 0.025952
AIRLOOP G N1 OA CONTROLLER 0.115062 0.025952
AIRLOOP G N2 OA CONTROLLER 0.115063 0.025952
AIRLOOP G S1 OA CONTROLLER 0.137534 0.025952
AIRLOOP G S2 OA CONTROLLER 0.143810 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.292244 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.271851 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.281875 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.209124 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.145222 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.143819 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.183767 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.186076 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.295372 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.275740 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.265208 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.213529 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.149692 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.148330 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.188100 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.189171 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.297736 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.278198 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.265909 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.215501 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.151944 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.150588 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.190123 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.191017 0.025952
AIRLOOP M SW OA CONTROLLER 0.301696 0.025952
AIRLOOP M NW OA CONTROLLER 0.282260 0.025952
AIRLOOP M SE OA CONTROLLER 0.269900 0.025952
AIRLOOP M NE OA CONTROLLER 0.219101 0.025952
AIRLOOP M N1 OA CONTROLLER 0.155657 0.025952
AIRLOOP M N2 OA CONTROLLER 0.154307 0.025952
AIRLOOP M S1 OA CONTROLLER 0.193669 0.025952
AIRLOOP M S2 OA CONTROLLER 0.194538 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.299796 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.280302 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.268252 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.216848 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.153666 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.152327 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.191516 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.192381 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.299851 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.280381 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.268539 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.216620 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.153614 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.152283 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.191305 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.192169 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.301106 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.281671 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.269961 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.223141 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.154777 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.153456 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.192267 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.193132 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.311284 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.291846 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.278061 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.237123 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.163436 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.162096 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.198926 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.199777 0.025952
AIRLOOP T SW OA CONTROLLER 0.378381 0.025952
AIRLOOP T NW OA CONTROLLER 0.348590 0.025952
AIRLOOP T SE OA CONTROLLER 0.340481 0.025952
AIRLOOP T NE OA CONTROLLER 0.278204 0.025952
AIRLOOP T N1 OA CONTROLLER 0.205663 0.025952
AIRLOOP T N2 OA CONTROLLER 0.205337 0.025952
AIRLOOP T S1 OA CONTROLLER 0.271113 0.025952
AIRLOOP T S2 OA CONTROLLER 0.271937 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.224065 4140.37 2697.65 0.000090
HEAT PUMP COOLING MODE AIRLOOP G NW 0.209462 3911.89 2531.58 0.000085
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.337282 6065.88 4013.16 0.000133
HEAT PUMP COOLING MODE AIRLOOP G NE 0.171367 3398.08 2133.35 0.000074
HEAT PUMP COOLING MODE AIRLOOP G N1 0.115062 2483.70 1510.60 0.000054
HEAT PUMP COOLING MODE AIRLOOP G N2 0.115063 2495.49 1515.11 0.000055
HEAT PUMP COOLING MODE AIRLOOP G S1 0.137534 2818.88 1759.22 0.000062
HEAT PUMP COOLING MODE AIRLOOP G S2 0.143810 2909.06 1825.57 0.000064
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.292244 5223.49 3452.12 0.000114
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.271851 4919.15 3227.28 0.000107
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.281875 5097.48 3353.19 0.000111
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.209124 3965.61 2538.79 0.000087
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.145222 2928.72 1828.34 0.000064
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.143819 2907.84 1813.38 0.000064
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.183767 3550.23 2270.19 0.000078
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.186076 3583.17 2294.59 0.000078
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.295372 5339.02 3506.78 0.000117
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.275740 5043.96 3289.78 0.000110
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.265208 4928.50 3198.05 0.000108
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.213529 4100.64 2610.28 0.000090
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.149692 3038.46 1892.14 0.000066
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.148330 3018.11 1877.60 0.000066
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.188100 3652.42 2328.82 0.000080
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.189171 3667.67 2340.12 0.000080
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.297736 5425.18 3547.88 0.000119
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.278198 5130.31 3331.71 0.000112
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.265909 4988.88 3221.24 0.000109
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.215501 4176.10 2646.52 0.000091
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.151944 3098.50 1925.21 0.000068
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.150588 3078.14 1910.72 0.000067
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.190123 3711.32 2359.82 0.000081
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.191017 3724.07 2369.25 0.000081
HEAT PUMP COOLING MODE AIRLOOP M SW 0.301696 5524.31 3602.91 0.000121
HEAT PUMP COOLING MODE AIRLOOP M NW 0.282260 5230.08 3387.70 0.000114
HEAT PUMP COOLING MODE AIRLOOP M SE 0.269900 5087.12 3276.40 0.000111
HEAT PUMP COOLING MODE AIRLOOP M NE 0.219101 4266.51 2697.19 0.000093
HEAT PUMP COOLING MODE AIRLOOP M N1 0.155657 3175.15 1972.09 0.000069
HEAT PUMP COOLING MODE AIRLOOP M N2 0.154307 3154.84 1957.66 0.000069
HEAT PUMP COOLING MODE AIRLOOP M S1 0.193669 3786.74 2405.21 0.000083
HEAT PUMP COOLING MODE AIRLOOP M S2 0.194538 3799.14 2414.37 0.000083
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.299796 5532.66 3593.88 0.000121
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.280302 5236.44 3377.90 0.000114
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.268252 5097.36 3269.76 0.000111
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.216848 4264.65 2683.71 0.000093
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.153666 3163.78 1957.24 0.000069
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.152327 3143.50 1942.89 0.000069
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.191516 3775.80 2388.96 0.000082
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.192381 3788.19 2398.08 0.000083
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.299851 5564.48 3604.19 0.000122
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.280381 5267.73 3388.33 0.000115
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.268539 5133.63 3283.67 0.000112
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.216620 4288.45 2690.45 0.000094
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.153614 3178.75 1962.18 0.000069
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.152283 3158.50 1947.90 0.000069
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.191305 3790.41 2392.51 0.000083
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.192169 3802.82 2401.62 0.000083
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.301106 5610.30 3626.22 0.000123
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.281671 5313.34 3410.63 0.000116
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.269961 5180.76 3307.28 0.000113
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.223141 4437.62 2778.16 0.000097
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.154777 3210.23 1979.50 0.000070
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.153456 3190.06 1965.30 0.000070
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.192267 3820.21 2407.90 0.000083
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.193132 3832.67 2417.03 0.000084
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.311284 5783.24 3742.31 0.000126
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.291846 5486.55 3526.71 0.000120
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.278061 5323.66 3401.35 0.000116
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.237123 4722.30 2955.68 0.000103
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.163436 3353.34 2076.41 0.000073
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.162096 3332.96 2062.02 0.000073
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.198926 3934.56 2484.77 0.000086
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.199777 3946.82 2493.76 0.000086
HEAT PUMP COOLING MODE AIRLOOP T SW 0.378381 6795.65 4472.85 0.000148
HEAT PUMP COOLING MODE AIRLOOP T NW 0.348590 6351.30 4148.29 0.000139
HEAT PUMP COOLING MODE AIRLOOP T SE 0.340481 6250.34 4070.40 0.000137
HEAT PUMP COOLING MODE AIRLOOP T NE 0.278204 5382.81 3423.33 0.000118
HEAT PUMP COOLING MODE AIRLOOP T N1 0.205663 4048.81 2562.07 0.000088
HEAT PUMP COOLING MODE AIRLOOP T N2 0.205337 4044.25 2558.67 0.000088
HEAT PUMP COOLING MODE AIRLOOP T S1 0.271113 4989.41 3253.82 0.000109
HEAT PUMP COOLING MODE AIRLOOP T S2 0.271937 5000.97 3262.48 0.000109


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.224065 0.224065 0.224065 0.224065 4140.37 4140.37 4974.82 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.209462 0.209462 0.209462 0.209462 3911.89 3911.89 4983.32 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.337282 0.337282 0.337282 0.337282 6065.88 6065.88 5979.01 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.171367 0.171367 0.171367 0.171367 3398.08 3398.08 4984.60 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.115062 0.115062 0.115062 0.115062 2483.70 2483.70 3766.89 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.115063 0.115063 0.115063 0.115063 2495.49 2495.49 3766.90 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.137534 0.137534 0.137534 0.137534 2818.88 2818.88 3755.65 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.143810 0.143810 0.143810 0.143810 2909.06 2909.06 3761.92 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.292244 0.292244 0.292244 0.292244 5223.49 5223.49 5061.34 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.271851 0.271851 0.271851 0.271851 4919.15 4919.15 5060.36 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.281875 0.281875 0.281875 0.281875 5097.48 5097.48 5075.81 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.209124 0.209124 0.209124 0.209124 3965.61 3965.61 5056.73 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.145222 0.145222 0.145222 0.145222 2928.72 2928.72 3518.09 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.143819 0.143819 0.143819 0.143819 2907.84 2907.84 3518.01 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.183767 0.183767 0.183767 0.183767 3550.23 3550.23 3522.03 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.186076 0.186076 0.186076 0.186076 3583.17 3583.17 3523.07 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.295372 0.295372 0.295372 0.295372 5339.02 5339.02 5232.35 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.275740 0.275740 0.275740 0.275740 5043.96 5043.96 5233.48 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.265208 0.265208 0.265208 0.265208 4928.50 4928.50 5227.27 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.213529 0.213529 0.213529 0.213529 4100.64 4100.64 5226.56 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.149692 0.149692 0.149692 0.149692 3038.46 3038.46 3572.22 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.148330 0.148330 0.148330 0.148330 3018.11 3018.11 3572.07 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.188100 0.188100 0.188100 0.188100 3652.42 3652.42 3572.11 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.189171 0.189171 0.189171 0.189171 3667.67 3667.67 3572.12 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.297736 0.297736 0.297736 0.297736 5425.18 5425.18 5438.29 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.278198 0.278198 0.278198 0.278198 5130.31 5130.31 5440.17 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.265909 0.265909 0.265909 0.265909 4988.88 4988.88 5429.22 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.215501 0.215501 0.215501 0.215501 4176.10 4176.10 5430.93 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.151944 0.151944 0.151944 0.151944 3098.50 3098.50 3685.72 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.150588 0.150588 0.150588 0.150588 3078.14 3078.14 3685.51 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.190123 0.190123 0.190123 0.190123 3711.32 3711.32 3684.57 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.191017 0.191017 0.191017 0.191017 3724.07 3724.07 3684.38 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.301696 0.301696 0.301696 0.301696 5524.31 5524.31 5598.62 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.282260 0.282260 0.282260 0.282260 5230.08 5230.08 5599.65 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.269900 0.269900 0.269900 0.269900 5087.12 5087.12 5587.60 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.219101 0.219101 0.219101 0.219101 4266.51 4266.51 5588.63 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.155657 0.155657 0.155657 0.155657 3175.15 3175.15 3770.20 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.154307 0.154307 0.154307 0.154307 3154.84 3154.84 3769.95 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.193669 0.193669 0.193669 0.193669 3786.74 3786.74 3769.82 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.194538 0.194538 0.194538 0.194538 3799.14 3799.14 3769.57 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.299796 0.299796 0.299796 0.299796 5532.66 5532.66 5800.24 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.280302 0.280302 0.280302 0.280302 5236.44 5236.44 5802.18 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.268252 0.268252 0.268252 0.268252 5097.36 5097.36 5787.77 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.216848 0.216848 0.216848 0.216848 4264.65 4264.65 5789.71 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.153666 0.153666 0.153666 0.153666 3163.78 3163.78 3906.26 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.152327 0.152327 0.152327 0.152327 3143.50 3143.50 3905.98 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.191516 0.191516 0.191516 0.191516 3775.80 3775.80 3904.98 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.192381 0.192381 0.192381 0.192381 3788.19 3788.19 3904.70 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.299851 0.299851 0.299851 0.299851 5564.48 5564.48 5961.20 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.280381 0.280381 0.280381 0.280381 5267.73 5267.73 5962.91 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.268539 0.268539 0.268539 0.268539 5133.63 5133.63 5947.53 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.216620 0.216620 0.216620 0.216620 4288.45 4288.45 5949.24 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.153614 0.153614 0.153614 0.153614 3178.75 3178.75 4009.59 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.152283 0.152283 0.152283 0.152283 3158.50 3158.50 4009.28 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.191305 0.191305 0.191305 0.191305 3790.41 3790.41 4008.54 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.192169 0.192169 0.192169 0.192169 3802.82 3802.82 4008.23 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.301106 0.301106 0.301106 0.301106 5610.30 5610.30 6119.02 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.281671 0.281671 0.281671 0.281671 5313.34 5313.34 6120.17 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.269961 0.269961 0.269961 0.269961 5180.76 5180.76 6104.33 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.223141 0.223141 0.223141 0.223141 4437.62 4437.62 6105.48 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.154777 0.154777 0.154777 0.154777 3210.23 3210.23 4115.49 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.153456 0.153456 0.153456 0.153456 3190.06 3190.06 4115.16 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.192267 0.192267 0.192267 0.192267 3820.21 3820.21 4114.99 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.193132 0.193132 0.193132 0.193132 3832.67 3832.67 4114.66 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.311284 0.311284 0.311284 0.311284 5783.24 5783.24 6426.33 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.291846 0.291846 0.291846 0.291846 5486.55 5486.55 6423.71 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.278061 0.278061 0.278061 0.278061 5323.66 5323.66 6410.61 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.237123 0.237123 0.237123 0.237123 4722.30 4722.30 6407.99 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.163436 0.163436 0.163436 0.163436 3353.34 3353.34 4361.60 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.162096 0.162096 0.162096 0.162096 3332.96 3332.96 4361.25 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.198926 0.198926 0.198926 0.198926 3934.56 3934.56 4364.47 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.199777 0.199777 0.199777 0.199777 3946.82 3946.82 4364.12 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.378381 0.378381 0.378381 0.378381 6795.65 6795.65 7306.56 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.348590 0.348590 0.348590 0.348590 6351.30 6351.30 7312.16 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.340481 0.340481 0.340481 0.340481 6250.34 6250.34 7291.30 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.278204 0.278204 0.278204 0.278204 5382.81 5382.81 7296.89 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.205663 0.205663 0.205663 0.205663 4048.81 4048.81 5280.17 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.205337 0.205337 0.205337 0.205337 4044.25 4044.25 5279.80 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.271113 0.271113 0.271113 0.271113 4989.41 4989.41 5271.94 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.271937 0.271937 0.271937 0.271937 5000.97 5000.97 5271.57 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.224065
AIRLOOP G NW SUPPLY FAN 0.209462
AIRLOOP OFFICE SUPPLY FAN 0.337282
AIRLOOP G NE SUPPLY FAN 0.171367
AIRLOOP G N1 SUPPLY FAN 0.115062
AIRLOOP G N2 SUPPLY FAN 0.115063
AIRLOOP G S1 SUPPLY FAN 0.137534
AIRLOOP G S2 SUPPLY FAN 0.143810
AIRLOOP F2 SW SUPPLY FAN 0.292244
AIRLOOP F2 NW SUPPLY FAN 0.271851
AIRLOOP F2 SE SUPPLY FAN 0.281875
AIRLOOP F2 NE SUPPLY FAN 0.209124
AIRLOOP F2 N1 SUPPLY FAN 0.145222
AIRLOOP F2 N2 SUPPLY FAN 0.143819
AIRLOOP F2 S1 SUPPLY FAN 0.183767
AIRLOOP F2 S2 SUPPLY FAN 0.186076
AIRLOOP F3 SW SUPPLY FAN 0.295372
AIRLOOP F3 NW SUPPLY FAN 0.275740
AIRLOOP F3 SE SUPPLY FAN 0.265208
AIRLOOP F3 NE SUPPLY FAN 0.213529
AIRLOOP F3 N1 SUPPLY FAN 0.149692
AIRLOOP F3 N2 SUPPLY FAN 0.148330
AIRLOOP F3 S1 SUPPLY FAN 0.188100
AIRLOOP F3 S2 SUPPLY FAN 0.189171
AIRLOOP F4 SW SUPPLY FAN 0.297736
AIRLOOP F4 NW SUPPLY FAN 0.278198
AIRLOOP F4 SE SUPPLY FAN 0.265909
AIRLOOP F4 NE SUPPLY FAN 0.215501
AIRLOOP F4 N1 SUPPLY FAN 0.151944
AIRLOOP F4 N2 SUPPLY FAN 0.150588
AIRLOOP F4 S1 SUPPLY FAN 0.190123
AIRLOOP F4 S2 SUPPLY FAN 0.191017
AIRLOOP M SW SUPPLY FAN 0.301696
AIRLOOP M NW SUPPLY FAN 0.282260
AIRLOOP M SE SUPPLY FAN 0.269900
AIRLOOP M NE SUPPLY FAN 0.219101
AIRLOOP M N1 SUPPLY FAN 0.155657
AIRLOOP M N2 SUPPLY FAN 0.154307
AIRLOOP M S1 SUPPLY FAN 0.193669
AIRLOOP M S2 SUPPLY FAN 0.194538
AIRLOOP F6 SW SUPPLY FAN 0.299796
AIRLOOP F6 NW SUPPLY FAN 0.280302
AIRLOOP F6 SE SUPPLY FAN 0.268252
AIRLOOP F6 NE SUPPLY FAN 0.216848
AIRLOOP F6 N1 SUPPLY FAN 0.153666
AIRLOOP F6 N2 SUPPLY FAN 0.152327
AIRLOOP F6 S1 SUPPLY FAN 0.191516
AIRLOOP F6 S2 SUPPLY FAN 0.192381
AIRLOOP F7 SW SUPPLY FAN 0.299851
AIRLOOP F7 NW SUPPLY FAN 0.280381
AIRLOOP F7 SE SUPPLY FAN 0.268539
AIRLOOP F7 NE SUPPLY FAN 0.216620
AIRLOOP F7 N1 SUPPLY FAN 0.153614
AIRLOOP F7 N2 SUPPLY FAN 0.152283
AIRLOOP F7 S1 SUPPLY FAN 0.191305
AIRLOOP F7 S2 SUPPLY FAN 0.192169
AIRLOOP F8 SW SUPPLY FAN 0.301106
AIRLOOP F8 NW SUPPLY FAN 0.281671
AIRLOOP F8 SE SUPPLY FAN 0.269961
AIRLOOP F8 NE SUPPLY FAN 0.223141
AIRLOOP F8 N1 SUPPLY FAN 0.154777
AIRLOOP F8 N2 SUPPLY FAN 0.153456
AIRLOOP F8 S1 SUPPLY FAN 0.192267
AIRLOOP F8 S2 SUPPLY FAN 0.193132
AIRLOOP F9 SW SUPPLY FAN 0.311284
AIRLOOP F9 NW SUPPLY FAN 0.291846
AIRLOOP F9 SE SUPPLY FAN 0.278061
AIRLOOP F9 NE SUPPLY FAN 0.237123
AIRLOOP F9 N1 SUPPLY FAN 0.163436
AIRLOOP F9 N2 SUPPLY FAN 0.162096
AIRLOOP F9 S1 SUPPLY FAN 0.198926
AIRLOOP F9 S2 SUPPLY FAN 0.199777
AIRLOOP T SW SUPPLY FAN 0.378381
AIRLOOP T NW SUPPLY FAN 0.348590
AIRLOOP T SE SUPPLY FAN 0.340481
AIRLOOP T NE SUPPLY FAN 0.278204
AIRLOOP T N1 SUPPLY FAN 0.205663
AIRLOOP T N2 SUPPLY FAN 0.205337
AIRLOOP T S1 SUPPLY FAN 0.271113
AIRLOOP T S2 SUPPLY FAN 0.271937


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.224065 4140.37 0.000090
HEAT PUMP HEATING MODE AIRLOOP G NW 0.209462 3911.89 0.000085
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.337282 6065.88 0.000133
HEAT PUMP HEATING MODE AIRLOOP G NE 0.171367 3398.08 0.000074
HEAT PUMP HEATING MODE AIRLOOP G N1 0.115062 2483.70 0.000054
HEAT PUMP HEATING MODE AIRLOOP G N2 0.115063 2495.49 0.000055
HEAT PUMP HEATING MODE AIRLOOP G S1 0.137534 2818.88 0.000062
HEAT PUMP HEATING MODE AIRLOOP G S2 0.143810 2909.06 0.000064
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.292244 5223.49 0.000114
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.271851 4919.15 0.000107
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.281875 5097.48 0.000111
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.209124 3965.61 0.000087
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.145222 2928.72 0.000064
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.143819 2907.84 0.000064
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.183767 3550.23 0.000078
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.186076 3583.17 0.000078
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.295372 5339.02 0.000117
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.275740 5043.96 0.000110
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.265208 4928.50 0.000108
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.213529 4100.64 0.000090
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.149692 3038.46 0.000066
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.148330 3018.11 0.000066
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.188100 3652.42 0.000080
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.189171 3667.67 0.000080
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.297736 5425.18 0.000119
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.278198 5130.31 0.000112
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.265909 4988.88 0.000109
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.215501 4176.10 0.000091
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.151944 3098.50 0.000068
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.150588 3078.14 0.000067
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.190123 3711.32 0.000081
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.191017 3724.07 0.000081
HEAT PUMP HEATING MODE AIRLOOP M SW 0.301696 5524.31 0.000121
HEAT PUMP HEATING MODE AIRLOOP M NW 0.282260 5230.08 0.000114
HEAT PUMP HEATING MODE AIRLOOP M SE 0.269900 5087.12 0.000111
HEAT PUMP HEATING MODE AIRLOOP M NE 0.219101 4266.51 0.000093
HEAT PUMP HEATING MODE AIRLOOP M N1 0.155657 3175.15 0.000069
HEAT PUMP HEATING MODE AIRLOOP M N2 0.154307 3154.84 0.000069
HEAT PUMP HEATING MODE AIRLOOP M S1 0.193669 3786.74 0.000083
HEAT PUMP HEATING MODE AIRLOOP M S2 0.194538 3799.14 0.000083
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.299796 5532.66 0.000121
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.280302 5236.44 0.000114
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.268252 5097.36 0.000111
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.216848 4264.65 0.000093
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.153666 3163.78 0.000069
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.152327 3143.50 0.000069
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.191516 3775.80 0.000082
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.192381 3788.19 0.000083
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.299851 5564.48 0.000122
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.280381 5267.73 0.000115
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.268539 5133.63 0.000112
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.216620 4288.45 0.000094
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.153614 3178.75 0.000069
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.152283 3158.50 0.000069
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.191305 3790.41 0.000083
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.192169 3802.82 0.000083
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.301106 5610.30 0.000123
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.281671 5313.34 0.000116
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.269961 5180.76 0.000113
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.223141 4437.62 0.000097
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.154777 3210.23 0.000070
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.153456 3190.06 0.000070
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.192267 3820.21 0.000083
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.193132 3832.67 0.000084
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.311284 5783.24 0.000126
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.291846 5486.55 0.000120
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.278061 5323.66 0.000116
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.237123 4722.30 0.000103
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.163436 3353.34 0.000073
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.162096 3332.96 0.000073
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.198926 3934.56 0.000086
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.199777 3946.82 0.000086
HEAT PUMP HEATING MODE AIRLOOP T SW 0.378381 6795.65 0.000148
HEAT PUMP HEATING MODE AIRLOOP T NW 0.348590 6351.30 0.000139
HEAT PUMP HEATING MODE AIRLOOP T SE 0.340481 6250.34 0.000137
HEAT PUMP HEATING MODE AIRLOOP T NE 0.278204 5382.81 0.000118
HEAT PUMP HEATING MODE AIRLOOP T N1 0.205663 4048.81 0.000088
HEAT PUMP HEATING MODE AIRLOOP T N2 0.205337 4044.25 0.000088
HEAT PUMP HEATING MODE AIRLOOP T S1 0.271113 4989.41 0.000109
HEAT PUMP HEATING MODE AIRLOOP T S2 0.271937 5000.97 0.000109


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 4974.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 4983.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 5979.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 4984.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 3766.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 3766.90
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 3755.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 3761.92
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 5061.34
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 5060.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 5075.81
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 5056.73
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 3518.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 3518.01
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 3522.03
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 3523.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 5232.35
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 5233.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 5227.27
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 5226.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 3572.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 3572.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 3572.11
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 3572.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 5438.29
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 5440.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 5429.22
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 5430.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 3685.72
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 3685.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 3684.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 3684.38
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 5598.62
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 5599.65
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 5587.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 5588.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 3770.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 3769.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 3769.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 3769.57
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 5800.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 5802.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 5787.77
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 5789.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 3906.26
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 3905.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 3904.98
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 3904.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 5961.20
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 5962.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 5947.53
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 5949.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 4009.59
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 4009.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 4008.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 4008.23
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 6119.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 6120.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 6104.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 6105.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 4115.49
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 4115.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 4114.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 4114.66
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 6426.33
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 6423.71
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 6410.61
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 6407.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 4361.60
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 4361.25
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 4364.47
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 4364.12
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 7306.56
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 7312.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 7291.30
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 7296.89
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 5280.17
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 5279.80
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 5271.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 5271.57


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.007472 8.41


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.007472


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.007472 3607.28 9.72 10928.40


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.007472 2386.30



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.75 -2.5
March 21.90 3.82
April 22.47 9.95
May 23.17 15.31
June 24.14 21.11
July 24.34 24.13
August 24.30 21.78
September 24.04 18.14
October 22.63 10.98
November 21.98 4.73
December 21.71 -3.7
     
Annual Sum or Average 22.85 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.29 9.95
May 23.02 15.31
June 24.13 21.11
July 24.34 24.13
August 24.29 21.78
September 23.88 18.14
October 22.07 10.98
November 21.81 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.73 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -4.6
February 21.88 -2.5
March 22.23 3.82
April 22.71 9.95
May 23.62 15.31
June 24.32 21.11
July 24.40 24.13
August 24.39 21.78
September 24.26 18.14
October 23.09 10.98
November 22.37 4.73
December 21.80 -3.7
     
Annual Sum or Average 23.08 9.99
Minimum of Months 21.80 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.25 9.95
May 22.99 15.31
June 24.11 21.11
July 24.34 24.13
August 24.29 21.78
September 23.85 18.14
October 22.01 10.98
November 21.78 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.71 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.19 9.95
May 22.80 15.31
June 24.05 21.11
July 24.32 24.13
August 24.25 21.78
September 23.79 18.14
October 21.99 10.98
November 21.80 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.67 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.32 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.19 9.95
May 22.80 15.31
June 24.05 21.11
July 24.32 24.13
August 24.25 21.78
September 23.79 18.14
October 21.99 10.98
November 21.80 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.67 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.32 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.75 -2.5
March 21.89 3.82
April 22.40 9.95
May 23.04 15.31
June 24.11 21.11
July 24.33 24.13
August 24.29 21.78
September 24.06 18.14
October 22.73 10.98
November 22.04 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.85 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.33 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.76 -2.5
March 21.92 3.82
April 22.42 9.95
May 23.09 15.31
June 24.13 21.11
July 24.33 24.13
August 24.30 21.78
September 24.09 18.14
October 22.79 10.98
November 22.08 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.33 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.96 -4.6
February 14.67 -2.5
March 16.83 3.82
April 19.13 9.95
May 21.71 15.31
June 24.52 21.11
July 25.69 24.13
August 24.83 21.78
September 23.46 18.14
October 19.74 10.98
November 17.12 4.73
December 14.27 -3.7
     
Annual Sum or Average 19.69 9.99
Minimum of Months 13.96 -4.6
Maximum of Months 25.69 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.80 -2.5
March 22.10 3.82
April 22.77 9.95
May 23.92 15.31
June 24.29 21.11
July 24.38 24.13
August 24.36 21.78
September 24.24 18.14
October 23.20 10.98
November 22.27 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.07 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.76 3.82
April 22.50 9.95
May 23.72 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.08 18.14
October 22.36 10.98
November 21.97 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.88 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -4.6
February 21.81 -2.5
March 22.20 3.82
April 22.83 9.95
May 24.02 15.31
June 24.31 21.11
July 24.38 24.13
August 24.37 21.78
September 24.29 18.14
October 23.38 10.98
November 22.35 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.13 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.44 9.95
May 23.64 15.31
June 24.26 21.11
July 24.40 24.13
August 24.35 21.78
September 24.04 18.14
October 22.26 10.98
November 21.90 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.85 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.39 9.95
May 23.54 15.31
June 24.23 21.11
July 24.37 24.13
August 24.33 21.78
September 24.01 18.14
October 22.30 10.98
November 21.99 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.84 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.38 9.95
May 23.53 15.31
June 24.23 21.11
July 24.38 24.13
August 24.33 21.78
September 24.01 18.14
October 22.30 10.98
November 21.98 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.84 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.18 3.82
April 22.75 9.95
May 23.86 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.25 18.14
October 23.44 10.98
November 22.40 4.73
December 21.76 -3.7
     
Annual Sum or Average 23.11 9.99
Minimum of Months 21.76 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.20 3.82
April 22.77 9.95
May 23.88 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.47 10.98
November 22.42 4.73
December 21.77 -3.7
     
Annual Sum or Average 23.12 9.99
Minimum of Months 21.77 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -4.6
February 21.05 -2.5
March 21.94 3.82
April 23.16 9.95
May 24.91 15.31
June 26.06 21.11
July 26.47 24.13
August 26.20 21.78
September 25.66 18.14
October 23.56 10.98
November 22.05 4.73
December 20.83 -3.7
     
Annual Sum or Average 23.56 9.99
Minimum of Months 20.74 -4.6
Maximum of Months 26.47 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.80 -2.5
March 22.11 3.82
April 22.80 9.95
May 24.03 15.31
June 24.28 21.11
July 24.38 24.13
August 24.36 21.78
September 24.24 18.14
October 23.26 10.98
November 22.32 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.10 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.77 3.82
April 22.53 9.95
May 23.85 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.08 18.14
October 22.40 10.98
November 22.01 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.90 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.78 -2.5
March 22.13 3.82
April 22.79 9.95
May 24.04 15.31
June 24.29 21.11
July 24.38 24.13
August 24.37 21.78
September 24.25 18.14
October 23.30 10.98
November 22.30 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.10 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.47 9.95
May 23.78 15.31
June 24.26 21.11
July 24.40 24.13
August 24.35 21.78
September 24.05 18.14
October 22.30 10.98
November 21.93 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.75 3.82
April 22.44 9.95
May 23.74 15.31
June 24.23 21.11
July 24.38 24.13
August 24.33 21.78
September 24.03 18.14
October 22.39 10.98
November 22.05 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.88 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.75 3.82
April 22.44 9.95
May 23.74 15.31
June 24.23 21.11
July 24.38 24.13
August 24.33 21.78
September 24.02 18.14
October 22.38 10.98
November 22.04 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -4.6
February 21.85 -2.5
March 22.24 3.82
April 22.83 9.95
May 24.03 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.58 10.98
November 22.49 4.73
December 21.77 -3.7
     
Annual Sum or Average 23.16 9.99
Minimum of Months 21.77 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -4.6
February 21.85 -2.5
March 22.25 3.82
April 22.83 9.95
May 24.03 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.59 10.98
November 22.49 4.73
December 21.77 -3.7
     
Annual Sum or Average 23.16 9.99
Minimum of Months 21.77 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 -4.6
February 21.56 -2.5
March 22.38 3.82
April 23.57 9.95
May 25.39 15.31
June 26.22 21.11
July 26.57 24.13
August 26.33 21.78
September 25.84 18.14
October 23.94 10.98
November 22.49 4.73
December 21.36 -3.7
     
Annual Sum or Average 23.92 9.99
Minimum of Months 21.28 -4.6
Maximum of Months 26.57 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.79 -2.5
March 22.09 3.82
April 22.79 9.95
May 24.05 15.31
June 24.28 21.11
July 24.38 24.13
August 24.36 21.78
September 24.24 18.14
October 23.26 10.98
November 22.33 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.09 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.76 3.82
April 22.53 9.95
May 23.89 15.31
June 24.26 21.11
July 24.37 24.13
August 24.35 21.78
September 24.07 18.14
October 22.41 10.98
November 22.01 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.90 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.77 -2.5
March 22.08 3.82
April 22.76 9.95
May 24.05 15.31
June 24.28 21.11
July 24.38 24.13
August 24.37 21.78
September 24.25 18.14
October 23.26 10.98
November 22.29 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.09 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.46 9.95
May 23.82 15.31
June 24.25 21.11
July 24.40 24.13
August 24.35 21.78
September 24.04 18.14
October 22.32 10.98
November 21.93 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.76 3.82
April 22.46 9.95
May 23.83 15.31
June 24.23 21.11
July 24.38 24.13
August 24.33 21.78
September 24.03 18.14
October 22.44 10.98
November 22.07 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.75 3.82
April 22.45 9.95
May 23.82 15.31
June 24.23 21.11
July 24.38 24.13
August 24.33 21.78
September 24.03 18.14
October 22.43 10.98
November 22.06 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.24 3.82
April 22.83 9.95
May 24.08 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.62 10.98
November 22.52 4.73
December 21.77 -3.7
     
Annual Sum or Average 23.17 9.99
Minimum of Months 21.77 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.24 3.82
April 22.83 9.95
May 24.09 15.31
June 24.27 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.62 10.98
November 22.52 4.73
December 21.77 -3.7
     
Annual Sum or Average 23.17 9.99
Minimum of Months 21.77 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.40 -4.6
February 21.69 -2.5
March 22.49 3.82
April 23.69 9.95
May 25.56 15.31
June 26.31 21.11
July 26.65 24.13
August 26.41 21.78
September 25.93 18.14
October 24.07 10.98
November 22.61 4.73
December 21.49 -3.7
     
Annual Sum or Average 24.04 9.99
Minimum of Months 21.40 -4.6
Maximum of Months 26.65 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.78 -2.5
March 22.06 3.82
April 22.77 9.95
May 24.04 15.31
June 24.27 21.11
July 24.38 24.13
August 24.36 21.78
September 24.23 18.14
October 23.22 10.98
November 22.31 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.08 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.76 3.82
April 22.52 9.95
May 23.88 15.31
June 24.25 21.11
July 24.37 24.13
August 24.34 21.78
September 24.05 18.14
October 22.39 10.98
November 22.00 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.77 -2.5
March 22.05 3.82
April 22.73 9.95
May 24.03 15.31
June 24.27 21.11
July 24.38 24.13
August 24.36 21.78
September 24.24 18.14
October 23.21 10.98
November 22.27 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.07 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.46 9.95
May 23.81 15.31
June 24.24 21.11
July 24.40 24.13
August 24.35 21.78
September 24.02 18.14
October 22.30 10.98
November 21.92 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.76 3.82
April 22.46 9.95
May 23.83 15.31
June 24.22 21.11
July 24.38 24.13
August 24.33 21.78
September 24.02 18.14
October 22.43 10.98
November 22.06 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.75 3.82
April 22.45 9.95
May 23.83 15.31
June 24.22 21.11
July 24.38 24.13
August 24.33 21.78
September 24.02 18.14
October 22.43 10.98
November 22.06 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.22 3.82
April 22.82 9.95
May 24.09 15.31
June 24.26 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.59 10.98
November 22.51 4.73
December 21.76 -3.7
     
Annual Sum or Average 23.16 9.99
Minimum of Months 21.76 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.6
February 21.84 -2.5
March 22.22 3.82
April 22.82 9.95
May 24.09 15.31
June 24.26 21.11
July 24.37 24.13
August 24.35 21.78
September 24.26 18.14
October 23.60 10.98
November 22.51 4.73
December 21.76 -3.7
     
Annual Sum or Average 23.16 9.99
Minimum of Months 21.76 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.94 -4.6
February 22.23 -2.5
March 23.03 3.82
April 24.24 9.95
May 26.11 15.31
June 26.83 21.11
July 27.19 24.13
August 26.95 21.78
September 26.46 18.14
October 24.59 10.98
November 23.16 4.73
December 22.05 -3.7
     
Annual Sum or Average 24.58 9.99
Minimum of Months 21.94 -4.6
Maximum of Months 27.19 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.77 -2.5
March 22.00 3.82
April 22.71 9.95
May 23.97 15.31
June 24.25 21.11
July 24.37 24.13
August 24.35 21.78
September 24.19 18.14
October 23.09 10.98
November 22.24 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.04 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.75 3.82
April 22.47 9.95
May 23.78 15.31
June 24.22 21.11
July 24.37 24.13
August 24.33 21.78
September 23.99 18.14
October 22.30 10.98
November 21.94 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.86 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.75 -2.5
March 22.00 3.82
April 22.68 9.95
May 23.96 15.31
June 24.25 21.11
July 24.38 24.13
August 24.36 21.78
September 24.20 18.14
October 23.08 10.98
November 22.20 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.03 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.42 9.95
May 23.71 15.31
June 24.20 21.11
July 24.40 24.13
August 24.34 21.78
September 23.95 18.14
October 22.21 10.98
November 21.87 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.83 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.41 9.95
May 23.74 15.31
June 24.19 21.11
July 24.38 24.13
August 24.31 21.78
September 23.96 18.14
October 22.34 10.98
November 22.01 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.85 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.41 9.95
May 23.73 15.31
June 24.19 21.11
July 24.38 24.13
August 24.31 21.78
September 23.95 18.14
October 22.33 10.98
November 22.00 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.85 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.82 -2.5
March 22.15 3.82
April 22.76 9.95
May 24.02 15.31
June 24.24 21.11
July 24.37 24.13
August 24.34 21.78
September 24.22 18.14
October 23.47 10.98
November 22.45 4.73
December 21.75 -3.7
     
Annual Sum or Average 23.12 9.99
Minimum of Months 21.75 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.82 -2.5
March 22.15 3.82
April 22.75 9.95
May 24.02 15.31
June 24.24 21.11
July 24.37 24.13
August 24.34 21.78
September 24.23 18.14
October 23.47 10.98
November 22.44 4.73
December 21.75 -3.7
     
Annual Sum or Average 23.12 9.99
Minimum of Months 21.75 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.32 -4.6
February 21.60 -2.5
March 22.38 3.82
April 23.60 9.95
May 25.48 15.31
June 26.26 21.11
July 26.64 24.13
August 26.39 21.78
September 25.86 18.14
October 23.93 10.98
November 22.50 4.73
December 21.42 -3.7
     
Annual Sum or Average 23.96 9.99
Minimum of Months 21.32 -4.6
Maximum of Months 26.64 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.76 -2.5
March 21.97 3.82
April 22.68 9.95
May 23.90 15.31
June 24.23 21.11
July 24.37 24.13
August 24.34 21.78
September 24.16 18.14
October 23.00 10.98
November 22.19 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.01 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.44 9.95
May 23.71 15.31
June 24.20 21.11
July 24.36 24.13
August 24.32 21.78
September 23.94 18.14
October 22.24 10.98
November 21.90 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.84 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -4.6
February 21.75 -2.5
March 21.96 3.82
April 22.64 9.95
May 23.89 15.31
June 24.23 21.11
July 24.37 24.13
August 24.35 21.78
September 24.17 18.14
October 22.98 10.98
November 22.15 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.00 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.72 3.82
April 22.39 9.95
May 23.63 15.31
June 24.18 21.11
July 24.40 24.13
August 24.33 21.78
September 23.90 18.14
October 22.15 10.98
November 21.84 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.81 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.38 9.95
May 23.65 15.31
June 24.17 21.11
July 24.37 24.13
August 24.30 21.78
September 23.91 18.14
October 22.27 10.98
November 21.97 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.83 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.38 9.95
May 23.65 15.31
June 24.17 21.11
July 24.38 24.13
August 24.30 21.78
September 23.90 18.14
October 22.26 10.98
November 21.96 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.83 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.80 -2.5
March 22.10 3.82
April 22.71 9.95
May 23.96 15.31
June 24.23 21.11
July 24.36 24.13
August 24.34 21.78
September 24.20 18.14
October 23.37 10.98
November 22.39 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.09 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.80 -2.5
March 22.10 3.82
April 22.71 9.95
May 23.96 15.31
June 24.23 21.11
July 24.36 24.13
August 24.34 21.78
September 24.20 18.14
October 23.37 10.98
November 22.39 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.09 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 -4.6
February 21.46 -2.5
March 22.22 3.82
April 23.46 9.95
May 25.32 15.31
June 26.15 21.11
July 26.56 24.13
August 26.30 21.78
September 25.73 18.14
October 23.74 10.98
November 22.33 4.73
December 21.28 -3.7
     
Annual Sum or Average 23.82 9.99
Minimum of Months 21.17 -4.6
Maximum of Months 26.56 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.75 -2.5
March 21.94 3.82
April 22.65 9.95
May 23.84 15.31
June 24.22 21.11
July 24.37 24.13
August 24.34 21.78
September 24.13 18.14
October 22.92 10.98
November 22.14 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.98 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.42 9.95
May 23.64 15.31
June 24.18 21.11
July 24.36 24.13
August 24.32 21.78
September 23.89 18.14
October 22.19 10.98
November 21.87 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.82 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -4.6
February 21.74 -2.5
March 21.93 3.82
April 22.61 9.95
May 23.84 15.31
June 24.22 21.11
July 24.37 24.13
August 24.35 21.78
September 24.14 18.14
October 22.90 10.98
November 22.10 4.73
December 21.71 -3.7
     
Annual Sum or Average 22.98 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.72 3.82
April 22.38 9.95
May 23.58 15.31
June 24.16 21.11
July 24.38 24.13
August 24.32 21.78
September 23.86 18.14
October 22.11 10.98
November 21.82 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.79 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.36 9.95
May 23.59 15.31
June 24.15 21.11
July 24.37 24.13
August 24.29 21.78
September 23.86 18.14
October 22.21 10.98
November 21.93 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.81 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.36 9.95
May 23.58 15.31
June 24.15 21.11
July 24.37 24.13
August 24.29 21.78
September 23.86 18.14
October 22.21 10.98
November 21.93 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.80 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -4.6
February 21.79 -2.5
March 22.06 3.82
April 22.68 9.95
May 23.90 15.31
June 24.21 21.11
July 24.36 24.13
August 24.33 21.78
September 24.17 18.14
October 23.28 10.98
November 22.33 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.06 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -4.6
February 21.79 -2.5
March 22.06 3.82
April 22.68 9.95
May 23.91 15.31
June 24.21 21.11
July 24.36 24.13
August 24.33 21.78
September 24.17 18.14
October 23.28 10.98
November 22.33 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.06 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 -4.6
February 21.37 -2.5
March 22.13 3.82
April 23.39 9.95
May 25.23 15.31
June 26.12 21.11
July 26.56 24.13
August 26.28 21.78
September 25.67 18.14
October 23.63 10.98
November 22.22 4.73
December 21.19 -3.7
     
Annual Sum or Average 23.75 9.99
Minimum of Months 21.08 -4.6
Maximum of Months 26.56 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -4.6
February 21.75 -2.5
March 21.91 3.82
April 22.62 9.95
May 23.78 15.31
June 24.20 21.11
July 24.37 24.13
August 24.33 21.78
September 24.08 18.14
October 22.83 10.98
November 22.08 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.96 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.41 9.95
May 23.59 15.31
June 24.16 21.11
July 24.36 24.13
August 24.31 21.78
September 23.84 18.14
October 22.15 10.98
November 21.85 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.80 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -4.6
February 21.74 -2.5
March 21.90 3.82
April 22.59 9.95
May 23.78 15.31
June 24.20 21.11
July 24.37 24.13
August 24.34 21.78
September 24.09 18.14
October 22.81 10.98
November 22.04 4.73
December 21.71 -3.7
     
Annual Sum or Average 22.95 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.72 3.82
April 22.37 9.95
May 23.53 15.31
June 24.14 21.11
July 24.37 24.13
August 24.31 21.78
September 23.81 18.14
October 22.08 10.98
November 21.81 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.78 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.36 9.95
May 23.53 15.31
June 24.13 21.11
July 24.36 24.13
August 24.28 21.78
September 23.81 18.14
October 22.16 10.98
November 21.90 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.79 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.35 9.95
May 23.52 15.31
June 24.13 21.11
July 24.37 24.13
August 24.28 21.78
September 23.80 18.14
October 22.16 10.98
November 21.89 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.78 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.37 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.78 -2.5
March 22.02 3.82
April 22.65 9.95
May 23.84 15.31
June 24.20 21.11
July 24.36 24.13
August 24.33 21.78
September 24.13 18.14
October 23.15 10.98
November 22.26 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.02 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.78 -2.5
March 22.02 3.82
April 22.65 9.95
May 23.84 15.31
June 24.20 21.11
July 24.36 24.13
August 24.33 21.78
September 24.13 18.14
October 23.15 10.98
November 22.26 4.73
December 21.73 -3.7
     
Annual Sum or Average 23.02 9.99
Minimum of Months 21.73 -4.6
Maximum of Months 24.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.88 -4.6
February 21.19 -2.5
March 21.99 3.82
April 23.31 9.95
May 25.18 15.31
June 26.15 21.11
July 26.63 24.13
August 26.33 21.78
September 25.63 18.14
October 23.49 10.98
November 22.05 4.73
December 21.00 -3.7
     
Annual Sum or Average 23.67 9.99
Minimum of Months 20.88 -4.6
Maximum of Months 26.63 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -4.6
February 21.77 -2.5
March 21.96 3.82
April 22.60 9.95
May 23.55 15.31
June 24.07 21.11
July 24.34 24.13
August 24.28 21.78
September 23.88 18.14
October 22.67 10.98
November 22.02 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.89 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.76 3.82
April 22.44 9.95
May 23.41 15.31
June 24.02 21.11
July 24.33 24.13
August 24.25 21.78
September 23.64 18.14
October 22.15 10.98
November 21.84 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.75 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.33 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.76 -2.5
March 21.95 3.82
April 22.58 9.95
May 23.55 15.31
June 24.07 21.11
July 24.34 24.13
August 24.29 21.78
September 23.88 18.14
October 22.65 10.98
November 21.98 4.73
December 21.72 -3.7
     
Annual Sum or Average 22.88 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.73 3.82
April 22.40 9.95
May 23.37 15.31
June 24.00 21.11
July 24.34 24.13
August 24.24 21.78
September 23.61 18.14
October 22.08 10.98
November 21.80 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.73 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.39 9.95
May 23.37 15.31
June 24.01 21.11
July 24.33 24.13
August 24.22 21.78
September 23.61 18.14
October 22.13 10.98
November 21.86 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.74 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.33 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.74 3.82
April 22.38 9.95
May 23.37 15.31
June 24.01 21.11
July 24.33 24.13
August 24.23 21.78
September 23.61 18.14
October 22.13 10.98
November 21.86 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.74 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.33 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.80 -2.5
March 22.03 3.82
April 22.62 9.95
May 23.62 15.31
June 24.09 21.11
July 24.34 24.13
August 24.28 21.78
September 23.95 18.14
October 22.90 10.98
November 22.17 4.73
December 21.74 -3.7
     
Annual Sum or Average 22.95 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.80 -2.5
March 22.03 3.82
April 22.62 9.95
May 23.62 15.31
June 24.09 21.11
July 24.34 24.13
August 24.28 21.78
September 23.96 18.14
October 22.90 10.98
November 22.17 4.73
December 21.74 -3.7
     
Annual Sum or Average 22.95 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.34 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -4.6
February 21.02 -2.5
March 22.08 3.82
April 23.66 9.95
May 25.66 15.31
June 26.84 21.11
July 27.46 24.13
August 27.02 21.78
September 26.09 18.14
October 23.69 10.98
November 22.05 4.73
December 20.73 -3.7
     
Annual Sum or Average 23.92 9.99
Minimum of Months 20.60 -4.6
Maximum of Months 27.46 24.13



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 19:00:30

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.296812E+12 225073.237 26-JAN-22:00 9277.707 37445.768 20693.728 143682.794 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.252099E+12 151955.609 04-FEB-17:15 11327.174 57042.023 20693.728 48117.813 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.245737E+12 155859.818 04-MAR-18:00 13120.457 57042.023 20693.728 50228.373 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.229809E+12 166958.717 16-APR-19:45 14401.373 49889.926 20693.728 0.000 65098.802 10364.000 2423.229 2446.356 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.226424E+12 173376.657 30-MAY-17:00 13120.457 57042.023 20693.728 0.000 75311.151 0.000 2423.229 2798.061 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.266917E+12 175450.518 19-JUN-19:00 14401.373 49889.926 20693.728 0.000 72928.543 10364.000 2423.229 3108.416 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.327593E+12 187362.451 19-JUL-17:15 13120.457 57042.023 20693.728 0.000 88487.926 0.000 2423.229 3607.278 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.293998E+12 182511.003 04-AUG-16:15 11327.174 57142.088 20693.728 0.000 85322.310 0.000 2423.229 3607.278 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.240221E+12 164320.147 05-SEP-17:15 13120.457 57042.023 20693.728 0.000 66577.938 0.000 2423.229 2474.961 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.214261E+12 124385.783 25-OCT-16:00 11327.174 57142.088 20693.728 20440.406 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.241396E+12 158083.434 25-NOV-18:00 13120.457 57042.023 20693.728 52451.989 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.285962E+12 180442.279 20-DEC-20:00 14401.373 49889.926 20693.728 81028.719 0.000 10364.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.312123E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.214261E+12 124385.783   9277.707 37445.768 20693.728 0.000 0.000 0.000 2423.229 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.327593E+12 225073.237   14401.373 57142.088 20693.728 143682.794 88487.926 10364.000 2423.229 3607.278 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 19:00:30

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.474634E+12 442243.967 27-JAN-07:30 0.000 0.000 0.000 442243.967 83123.275 83123.275 359120.692
February 0.371415E+12 337018.720 01-FEB-07:00 0.000 0.000 0.000 337018.720 83480.235 83480.235 253538.485
March 0.271306E+12 304780.956 05-MAR-06:15 0.000 0.000 0.000 304780.956 68683.898 68683.898 236097.058
April 0.165845E+12 175597.149 02-APR-19:15 0.000 0.000 0.000 175597.149 73749.803 73749.803 101847.346
May 0.999928E+11 79537.295 02-MAY-06:00 0.000 0.000 0.000 79537.295 79537.295 79537.295 0.000
June 0.901787E+11 77047.235 01-JUN-06:00 0.000 0.000 0.000 77047.235 77047.235 77047.235 0.000
July 0.882530E+11 74995.048 01-JUL-06:45 0.000 0.000 0.000 74995.048 74995.048 74995.048 0.000
August 0.864915E+11 73897.211 29-AUG-06:00 0.000 0.000 0.000 73897.211 73897.211 73897.211 0.000
September 0.855754E+11 75044.900 30-SEP-06:45 0.000 0.000 0.000 75044.900 75044.900 75044.900 0.000
October 0.110837E+12 154365.544 16-OCT-06:15 0.000 0.000 0.000 154365.544 75145.261 75145.261 79220.283
November 0.261846E+12 342604.795 25-NOV-22:15 0.000 0.000 0.000 342604.795 66166.696 66166.696 276438.099
December 0.426906E+12 376294.957 20-DEC-20:45 0.000 0.000 0.000 376294.957 72288.392 72288.392 304006.565
                     
Annual Sum or Average 0.253328E+13     0.000 0.000 0.000        
Minimum of Months 0.855754E+11 73897.211   0.000 0.000 0.000 73897.211 66166.696 66166.696 0.000
Maximum of Months 0.474634E+12 442243.967   0.000 0.000 0.000 442243.967 83480.235 83480.235 359120.692