Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2015-09-09 19:12:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4377.59 | 558.62 | 620.06 |
Net Site Energy | 4377.59 | 558.62 | 620.06 |
Total Source Energy | 10463.19 | 1335.19 | 1482.06 |
Net Source Energy | 10463.19 | 1335.19 | 1482.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 143.57 | 483.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 235.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 662.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 61.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 9.60 | 0.00 | 0.00 | 0.00 | 0.00 | 746.40 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1149.45 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2745.02 | 1632.57 | 0.00 | 0.00 | 0.00 | 5524.92 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 483.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 143.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 235.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 662.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 61.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 9.60 | 0.00 | 0.00 | 0.00 | 0.00 | 746.40 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1149.45 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.53 | 231.25 | 0.00 | 0.00 | 0.00 | 0.78 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 388.82 | 231.25 | 0.00 | 0.00 | 0.00 | 0.78 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.92 | 208.33 | 0.00 | 0.00 | 0.00 | 0.71 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 350.29 | 208.33 | 0.00 | 0.00 | 0.00 | 0.71 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2745.02 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2745.02 | 100.00 |
Total On-Site and Utility Electric Sources | 2745.02 | 100.00 |
Total Electricity End Uses | 2745.02 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5524.92 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5524.92 | 100.00 |
Total Water End Uses | 5524.92 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 155.00 |
Time Setpoint Not Met During Occupied Cooling | 86.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 449.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11 |
RunPeriod | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [m] | 60.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUL-17:15 | 20-DEC-07:00 | - | - | - | 17-JUL-17:15 |
Heating | 0.00 | 179384.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67773.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13120.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 21005.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1959.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2573.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 78981.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 165462.52 | 258366.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 179384.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 67773.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 10541.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2579.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 21005.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1959.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2573.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 78981.47 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 454.67 | 523.70 | 0.00 | 0.00 | 0.00 |
Cooling | 745.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 515.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2097.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 193.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 30.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1246.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8693.48 | 1769.70 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.40 | 74.18 | 0.00 | 0.00 | 0.00 |
Cooling | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 297.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 176.49 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1231.39 | 250.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 64.40 | 74.18 | 0.00 | 0.00 | 0.00 |
Cooling | 105.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 297.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 176.49 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1231.39 | 250.67 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00 | -5.60 | Wetbulb [C] | 2.10 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 15.40 | 19.40 | Wetbulb [C] | 4.30 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.68 | 83.68 | 162.79 | |
Exterior Lighting Total | 10364.00 | 162.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 276837.95 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 221470.36 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3842.70 | 2880.51 | 962.19 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2958.00 | 2210.06 | 747.94 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5610.84 | 4216.33 | 1394.51 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2057.38 | 1525.06 | 532.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1364.06 | 992.65 | 371.41 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1330.50 | 967.03 | 363.47 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2739.68 | 2020.41 | 719.27 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2831.51 | 2091.98 | 739.53 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4798.55 | 3620.45 | 1178.10 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3737.58 | 2811.66 | 925.92 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4756.20 | 3582.98 | 1173.22 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2718.42 | 2037.52 | 680.90 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1827.42 | 1347.69 | 479.73 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1797.53 | 1324.77 | 472.77 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3462.18 | 2579.09 | 883.08 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3495.78 | 2605.27 | 890.52 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4850.94 | 3658.87 | 1192.07 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3796.43 | 2855.25 | 941.18 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4518.65 | 3395.82 | 1122.83 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2776.34 | 2080.71 | 695.63 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1889.62 | 1394.74 | 494.88 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1859.66 | 1371.75 | 487.90 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3524.66 | 2626.38 | 898.28 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3540.44 | 2638.67 | 901.77 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4885.85 | 3684.28 | 1201.57 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3829.31 | 2879.22 | 950.10 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4527.09 | 3400.67 | 1126.41 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2812.66 | 2102.94 | 709.73 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1918.03 | 1415.97 | 502.06 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1888.04 | 1392.97 | 495.07 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3554.33 | 2648.46 | 905.87 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3567.55 | 2658.75 | 908.79 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4941.44 | 3726.11 | 1215.33 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3892.61 | 2925.00 | 967.61 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4581.05 | 3441.26 | 1139.78 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2856.48 | 2135.83 | 720.65 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1965.64 | 1452.11 | 513.54 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1935.64 | 1429.09 | 506.55 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3604.33 | 2686.55 | 917.79 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3617.14 | 2696.52 | 920.62 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4914.69 | 3704.10 | 1210.59 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3863.98 | 2901.70 | 962.27 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4556.18 | 3420.75 | 1135.43 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2821.07 | 2107.38 | 713.69 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1935.01 | 1428.09 | 506.92 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1905.17 | 1405.21 | 499.96 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3573.54 | 2661.88 | 911.66 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3586.28 | 2671.80 | 914.48 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4914.77 | 3703.11 | 1211.66 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3862.75 | 2899.82 | 962.93 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4557.80 | 3420.99 | 1136.81 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2813.19 | 2100.44 | 712.75 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1930.76 | 1424.44 | 506.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1913.34 | 1408.52 | 504.82 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3569.66 | 2658.25 | 911.41 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3582.35 | 2668.13 | 914.22 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4927.92 | 3712.40 | 1215.52 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3875.52 | 2908.90 | 966.63 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4572.10 | 3431.20 | 1140.91 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2819.01 | 2104.23 | 714.78 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1941.26 | 1432.18 | 509.08 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1924.71 | 1416.93 | 507.78 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3579.31 | 2665.20 | 914.10 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3592.01 | 2675.10 | 916.91 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5035.56 | 3795.22 | 1240.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3989.25 | 2996.34 | 992.91 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4666.71 | 3502.23 | 1164.48 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2992.31 | 2201.53 | 790.79 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2041.36 | 1508.85 | 532.51 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2024.47 | 1493.44 | 531.03 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3652.14 | 2721.33 | 930.81 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3666.45 | 2732.47 | 933.97 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6102.07 | 4619.74 | 1482.33 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4880.66 | 3682.92 | 1197.74 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5597.95 | 4227.27 | 1370.68 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3742.16 | 2783.06 | 959.10 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2896.99 | 2135.96 | 761.03 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2900.88 | 2136.76 | 764.12 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4725.45 | 3557.61 | 1167.83 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4738.94 | 3568.13 | 1170.82 | 0.75 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3842.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2958.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5610.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2057.38 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1364.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1330.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2739.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2831.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4798.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3737.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4756.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2718.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1827.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1797.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3462.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3495.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4850.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3796.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4518.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2776.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1889.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1859.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3524.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3540.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4885.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3829.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4527.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2812.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1918.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1888.04 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3554.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3567.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4941.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3892.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4581.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2856.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1965.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1935.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3604.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3617.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4914.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3863.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4556.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2821.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1935.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1905.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3573.54 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3586.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4914.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3862.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4557.80 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2813.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1930.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1913.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3569.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3582.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4927.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3875.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4572.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2819.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1941.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1924.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3579.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3592.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5035.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3989.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4666.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2992.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2041.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2024.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3652.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3666.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6102.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4880.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5597.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3742.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2896.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2900.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4725.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4738.94 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2633.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2633.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3380.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2633.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2008.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2008.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2004.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2010.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2528.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2523.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2546.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2523.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1755.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1755.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1762.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1763.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2515.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2512.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2517.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2512.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1712.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1712.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1716.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1716.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2554.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2552.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2554.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2552.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1725.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1725.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1728.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1728.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2574.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2572.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2574.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2572.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1726.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1726.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1729.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1729.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2653.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2652.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2653.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2652.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1786.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1786.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1787.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1787.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 2706.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 2706.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 2706.80 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 2706.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1824.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1824.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1825.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1825.03 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2764.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2763.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2764.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2763.83 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1867.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1867.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1868.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1868.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2934.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2932.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2934.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2932.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2016.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2016.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2018.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2018.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3525.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3529.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3525.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3529.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2650.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2650.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2642.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2642.57 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.43 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.38 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 429.40 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 154.49 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 98.77 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 96.07 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 201.27 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.89 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 372.17 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 289.32 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 367.43 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.08 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 136.33 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 133.90 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 260.38 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 263.17 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 376.14 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.85 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 347.34 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.58 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.27 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 138.84 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 265.34 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 266.65 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 378.75 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 296.32 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 347.76 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.05 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 143.49 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.05 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 267.64 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 268.73 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 383.14 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 300.63 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 352.01 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 218.50 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 147.30 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 144.86 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 271.65 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 272.71 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 380.72 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.09 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 349.76 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.41 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 144.72 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 142.30 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 268.98 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 270.04 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 380.56 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.83 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 349.73 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 214.62 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 144.31 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.94 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 268.56 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 269.61 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 381.50 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.76 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 350.77 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 214.99 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 145.11 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 142.81 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 269.27 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 270.32 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 390.29 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 308.03 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 358.02 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.50 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 153.23 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.91 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 275.22 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 276.41 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 477.56 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 379.89 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 435.61 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 281.33 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.21 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.97 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 364.65 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 365.77 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0060 | 1922.92 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2671.19 | 3205.43 | 0.211 | 0.253 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
G NW APARTMENT | 2051.68 | 2462.01 | 0.162 | 0.194 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
OFFICE | 3908.92 | 4690.70 | 0.308 | 0.370 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
G NE APARTMENT | 1406.29 | 1687.55 | 0.111 | 0.133 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
G N1 APARTMENT | 899.12 | 1078.95 | 0.071 | 0.085 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
G N2 APARTMENT | 874.52 | 1049.43 | 0.069 | 0.083 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
G S1 APARTMENT | 1832.21 | 2198.65 | 0.144 | 0.173 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
G S2 APARTMENT | 1901.56 | 2281.87 | 0.150 | 0.180 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F2 SW APARTMENT | 3387.90 | 4065.48 | 0.267 | 0.321 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F2 NW APARTMENT | 2633.70 | 3160.45 | 0.208 | 0.249 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
F2 SE APARTMENT | 3344.83 | 4013.79 | 0.264 | 0.317 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F2 NE APARTMENT | 1903.26 | 2283.91 | 0.150 | 0.180 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
F2 N1 APARTMENT | 1241.03 | 1489.24 | 0.098 | 0.117 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F2 N2 APARTMENT | 1218.93 | 1462.71 | 0.096 | 0.115 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F2 S1 APARTMENT | 2370.26 | 2844.31 | 0.187 | 0.224 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F2 S2 APARTMENT | 2395.65 | 2874.79 | 0.189 | 0.227 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F3 SW APARTMENT | 3424.04 | 4108.85 | 0.270 | 0.324 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F3 NW APARTMENT | 2674.96 | 3209.95 | 0.211 | 0.253 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
F3 SE APARTMENT | 3161.87 | 3794.24 | 0.249 | 0.299 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F3 NE APARTMENT | 1944.26 | 2333.12 | 0.153 | 0.184 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
F3 N1 APARTMENT | 1286.05 | 1543.25 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F3 N2 APARTMENT | 1263.88 | 1516.65 | 0.100 | 0.120 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F3 S1 APARTMENT | 2415.44 | 2898.53 | 0.190 | 0.229 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F3 S2 APARTMENT | 2427.37 | 2912.85 | 0.191 | 0.230 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F4 SW APARTMENT | 3447.84 | 4137.41 | 0.272 | 0.326 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F4 NW APARTMENT | 2697.42 | 3236.91 | 0.213 | 0.255 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
F4 SE APARTMENT | 3165.72 | 3798.86 | 0.250 | 0.300 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F4 NE APARTMENT | 1957.67 | 2349.21 | 0.154 | 0.185 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
F4 N1 APARTMENT | 1306.22 | 1567.46 | 0.103 | 0.124 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F4 N2 APARTMENT | 1284.04 | 1540.85 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F4 S1 APARTMENT | 2436.34 | 2923.61 | 0.192 | 0.231 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F4 S2 APARTMENT | 2446.33 | 2935.60 | 0.193 | 0.231 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
M SW APARTMENT | 3487.76 | 4185.31 | 0.275 | 0.330 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
M NW APARTMENT | 2736.71 | 3284.05 | 0.216 | 0.259 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
M SE APARTMENT | 3204.43 | 3845.31 | 0.253 | 0.303 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
M NE APARTMENT | 1989.02 | 2386.82 | 0.157 | 0.188 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
M N1 APARTMENT | 1340.86 | 1609.03 | 0.106 | 0.127 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
M N2 APARTMENT | 1318.66 | 1582.40 | 0.104 | 0.125 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
M S1 APARTMENT | 2472.87 | 2967.44 | 0.195 | 0.234 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
M S2 APARTMENT | 2482.54 | 2979.05 | 0.196 | 0.235 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F6 SW APARTMENT | 3465.76 | 4158.92 | 0.273 | 0.328 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F6 NW APARTMENT | 2713.55 | 3256.26 | 0.214 | 0.257 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
F6 SE APARTMENT | 3183.91 | 3820.69 | 0.251 | 0.301 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F6 NE APARTMENT | 1960.91 | 2353.10 | 0.155 | 0.186 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
F6 N1 APARTMENT | 1317.42 | 1580.90 | 0.104 | 0.125 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F6 N2 APARTMENT | 1295.36 | 1554.43 | 0.102 | 0.123 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F6 S1 APARTMENT | 2448.58 | 2938.30 | 0.193 | 0.232 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F6 S2 APARTMENT | 2458.21 | 2949.85 | 0.194 | 0.233 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F7 SW APARTMENT | 3464.27 | 4157.12 | 0.273 | 0.328 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F7 NW APARTMENT | 2711.24 | 3253.49 | 0.214 | 0.257 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
F7 SE APARTMENT | 3183.62 | 3820.35 | 0.251 | 0.301 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F7 NE APARTMENT | 1953.75 | 2344.50 | 0.154 | 0.185 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
F7 N1 APARTMENT | 1313.69 | 1576.43 | 0.104 | 0.124 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F7 N2 APARTMENT | 1292.09 | 1550.51 | 0.102 | 0.122 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 28.45 | 0.00850 |
F7 S1 APARTMENT | 2444.74 | 2933.69 | 0.193 | 0.231 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F7 S2 APARTMENT | 2454.33 | 2945.20 | 0.194 | 0.232 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F8 SW APARTMENT | 3472.81 | 4167.38 | 0.274 | 0.329 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F8 NW APARTMENT | 2719.62 | 3263.54 | 0.214 | 0.257 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
F8 SE APARTMENT | 3193.06 | 3831.68 | 0.252 | 0.302 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
F8 NE APARTMENT | 1957.05 | 2348.46 | 0.154 | 0.185 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
F8 N1 APARTMENT | 1320.99 | 1585.18 | 0.104 | 0.125 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F8 N2 APARTMENT | 1300.03 | 1560.04 | 0.103 | 0.123 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 28.45 | 0.00850 |
F8 S1 APARTMENT | 2451.21 | 2941.45 | 0.193 | 0.232 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F8 S2 APARTMENT | 2460.81 | 2952.97 | 0.194 | 0.233 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F9 SW APARTMENT | 3552.83 | 4263.39 | 0.280 | 0.336 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
F9 NW APARTMENT | 2804.08 | 3364.89 | 0.221 | 0.265 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
F9 SE APARTMENT | 3259.08 | 3910.89 | 0.257 | 0.308 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F9 NE APARTMENT | 1998.13 | 2397.76 | 0.158 | 0.189 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.30 | 0.00850 |
F9 N1 APARTMENT | 1394.88 | 1673.85 | 0.110 | 0.132 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
F9 N2 APARTMENT | 1373.76 | 1648.52 | 0.108 | 0.130 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 28.45 | 0.00850 |
F9 S1 APARTMENT | 2505.38 | 3006.46 | 0.198 | 0.237 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
F9 S2 APARTMENT | 2516.19 | 3019.43 | 0.198 | 0.238 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
T SW APARTMENT | 4347.28 | 5216.74 | 0.343 | 0.411 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.07 | 0.00850 |
T NW APARTMENT | 3458.16 | 4149.79 | 0.273 | 0.327 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 31.45 | 0.00850 |
T SE APARTMENT | 3965.40 | 4758.48 | 0.313 | 0.375 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
T NE APARTMENT | 2560.99 | 3073.19 | 0.202 | 0.242 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.30 | 0.00850 |
T N1 APARTMENT | 1940.86 | 2329.03 | 0.153 | 0.184 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.07 | 0.00850 |
T N2 APARTMENT | 1938.70 | 2326.44 | 0.153 | 0.183 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.30 | 0.00850 |
T S1 APARTMENT | 3319.45 | 3983.35 | 0.262 | 0.314 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
T S2 APARTMENT | 3329.67 | 3995.60 | 0.263 | 0.315 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1506.87 | 1808.24 | 0.068 | 0.081 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G NW APARTMENT | 1506.96 | 1808.35 | 0.068 | 0.081 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
OFFICE | 1801.79 | 2162.15 | 0.081 | 0.097 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.60 | 0.00237 |
G NE APARTMENT | 1506.96 | 1808.35 | 0.068 | 0.081 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G N1 APARTMENT | 978.34 | 1174.01 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G N2 APARTMENT | 978.34 | 1174.01 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G S1 APARTMENT | 975.11 | 1170.13 | 0.044 | 0.052 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G S2 APARTMENT | 980.43 | 1176.52 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
F2 SW APARTMENT | 1418.02 | 1701.62 | 0.064 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 NW APARTMENT | 1414.08 | 1696.90 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 SE APARTMENT | 1433.89 | 1720.67 | 0.064 | 0.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 NE APARTMENT | 1414.08 | 1696.90 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 N1 APARTMENT | 764.35 | 917.22 | 0.034 | 0.041 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 N2 APARTMENT | 764.35 | 917.22 | 0.034 | 0.041 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 S1 APARTMENT | 770.63 | 924.75 | 0.035 | 0.041 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F2 S2 APARTMENT | 771.69 | 926.02 | 0.035 | 0.041 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 SW APARTMENT | 1407.66 | 1689.20 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 NW APARTMENT | 1404.86 | 1685.83 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 SE APARTMENT | 1409.45 | 1691.34 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 NE APARTMENT | 1404.86 | 1685.83 | 0.063 | 0.076 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 N1 APARTMENT | 727.96 | 873.56 | 0.033 | 0.039 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 N2 APARTMENT | 727.96 | 873.56 | 0.033 | 0.039 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 S1 APARTMENT | 731.41 | 877.70 | 0.033 | 0.039 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F3 S2 APARTMENT | 731.58 | 877.90 | 0.033 | 0.039 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 SW APARTMENT | 1440.47 | 1728.56 | 0.065 | 0.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 NW APARTMENT | 1438.72 | 1726.46 | 0.064 | 0.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 SE APARTMENT | 1440.66 | 1728.79 | 0.065 | 0.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 NE APARTMENT | 1438.72 | 1726.46 | 0.064 | 0.077 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 N1 APARTMENT | 739.58 | 887.49 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 N2 APARTMENT | 739.58 | 887.49 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 S1 APARTMENT | 741.77 | 890.12 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F4 S2 APARTMENT | 741.79 | 890.15 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M SW APARTMENT | 1457.53 | 1749.04 | 0.065 | 0.078 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M NW APARTMENT | 1455.69 | 1746.82 | 0.065 | 0.078 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M SE APARTMENT | 1457.55 | 1749.07 | 0.065 | 0.078 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M NE APARTMENT | 1455.69 | 1746.82 | 0.065 | 0.078 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M N1 APARTMENT | 740.50 | 888.60 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M N2 APARTMENT | 740.50 | 888.60 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M S1 APARTMENT | 742.77 | 891.33 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
M S2 APARTMENT | 742.78 | 891.33 | 0.033 | 0.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 SW APARTMENT | 1524.12 | 1828.95 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 NW APARTMENT | 1523.49 | 1828.19 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 SE APARTMENT | 1524.13 | 1828.95 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 NE APARTMENT | 1523.49 | 1828.19 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 N1 APARTMENT | 790.82 | 948.98 | 0.035 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 N2 APARTMENT | 790.82 | 948.98 | 0.035 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 S1 APARTMENT | 791.82 | 950.18 | 0.035 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F6 S2 APARTMENT | 791.82 | 950.18 | 0.035 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 SW APARTMENT | 1569.15 | 1882.98 | 0.070 | 0.084 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 NW APARTMENT | 1568.84 | 1882.61 | 0.070 | 0.084 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 SE APARTMENT | 1569.15 | 1882.98 | 0.070 | 0.084 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 NE APARTMENT | 1568.84 | 1882.61 | 0.070 | 0.084 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 N1 APARTMENT | 822.78 | 987.34 | 0.037 | 0.044 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 N2 APARTMENT | 822.78 | 987.34 | 0.037 | 0.044 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 S1 APARTMENT | 823.46 | 988.15 | 0.037 | 0.044 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F7 S2 APARTMENT | 823.46 | 988.15 | 0.037 | 0.044 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 SW APARTMENT | 1617.58 | 1941.10 | 0.072 | 0.087 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 NW APARTMENT | 1617.38 | 1940.86 | 0.072 | 0.087 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 SE APARTMENT | 1617.58 | 1941.10 | 0.072 | 0.087 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 NE APARTMENT | 1617.38 | 1940.86 | 0.072 | 0.087 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 N1 APARTMENT | 859.52 | 1031.42 | 0.039 | 0.046 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 N2 APARTMENT | 859.52 | 1031.42 | 0.039 | 0.046 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 S1 APARTMENT | 860.07 | 1032.08 | 0.039 | 0.046 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F8 S2 APARTMENT | 860.07 | 1032.08 | 0.039 | 0.046 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 SW APARTMENT | 1761.83 | 2114.20 | 0.079 | 0.095 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 NW APARTMENT | 1760.01 | 2112.01 | 0.079 | 0.095 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 SE APARTMENT | 1761.83 | 2114.20 | 0.079 | 0.095 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 NE APARTMENT | 1760.01 | 2112.01 | 0.079 | 0.095 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 N1 APARTMENT | 985.23 | 1182.28 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 N2 APARTMENT | 985.23 | 1182.28 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 S1 APARTMENT | 987.03 | 1184.44 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
F9 S2 APARTMENT | 987.03 | 1184.44 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T SW APARTMENT | 2261.21 | 2713.45 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T NW APARTMENT | 2264.99 | 2717.99 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T SE APARTMENT | 2261.21 | 2713.45 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T NE APARTMENT | 2264.99 | 2717.99 | 0.101 | 0.122 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T N1 APARTMENT | 1521.14 | 1825.36 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T N2 APARTMENT | 1521.14 | 1825.36 | 0.068 | 0.082 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T S1 APARTMENT | 1514.82 | 1817.78 | 0.068 | 0.081 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
T S2 APARTMENT | 1514.82 | 1817.78 | 0.068 | 0.081 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.60 | 0.00237 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP G NW | 0.19 | 0.19 | 0.08 | 0.08 |
AIRLOOP OFFICE | 0.37 | 0.37 | 0.10 | 0.10 |
AIRLOOP G NE | 0.13 | 0.13 | 0.08 | 0.08 |
AIRLOOP G N1 | 0.09 | 0.09 | 0.05 | 0.05 |
AIRLOOP G N2 | 0.08 | 0.08 | 0.05 | 0.05 |
AIRLOOP G S1 | 0.17 | 0.17 | 0.05 | 0.05 |
AIRLOOP G S2 | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP F2 SW | 0.32 | 0.32 | 0.08 | 0.08 |
AIRLOOP F2 NW | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F2 SE | 0.32 | 0.32 | 0.08 | 0.08 |
AIRLOOP F2 NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F2 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F2 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F2 S1 | 0.22 | 0.22 | 0.04 | 0.04 |
AIRLOOP F2 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F3 SW | 0.32 | 0.32 | 0.08 | 0.08 |
AIRLOOP F3 NW | 0.25 | 0.25 | 0.08 | 0.08 |
AIRLOOP F3 SE | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F3 NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F3 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F3 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F3 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F3 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F4 SW | 0.33 | 0.33 | 0.08 | 0.08 |
AIRLOOP F4 NW | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP F4 SE | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F4 NE | 0.19 | 0.19 | 0.08 | 0.08 |
AIRLOOP F4 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F4 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F4 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F4 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP M SW | 0.33 | 0.33 | 0.08 | 0.08 |
AIRLOOP M NW | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP M SE | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP M NE | 0.19 | 0.19 | 0.08 | 0.08 |
AIRLOOP M N1 | 0.13 | 0.13 | 0.04 | 0.04 |
AIRLOOP M N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP M S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP M S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F6 SW | 0.33 | 0.33 | 0.08 | 0.08 |
AIRLOOP F6 NW | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP F6 SE | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F6 NE | 0.19 | 0.19 | 0.08 | 0.08 |
AIRLOOP F6 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F6 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F6 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F6 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F7 SW | 0.33 | 0.33 | 0.08 | 0.08 |
AIRLOOP F7 NW | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP F7 SE | 0.30 | 0.30 | 0.08 | 0.08 |
AIRLOOP F7 NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP F7 N1 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F7 N2 | 0.12 | 0.12 | 0.04 | 0.04 |
AIRLOOP F7 S1 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F7 S2 | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F8 SW | 0.33 | 0.33 | 0.09 | 0.09 |
AIRLOOP F8 NW | 0.26 | 0.26 | 0.09 | 0.09 |
AIRLOOP F8 SE | 0.30 | 0.30 | 0.09 | 0.09 |
AIRLOOP F8 NE | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F8 N1 | 0.13 | 0.13 | 0.05 | 0.05 |
AIRLOOP F8 N2 | 0.12 | 0.12 | 0.05 | 0.05 |
AIRLOOP F8 S1 | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F8 S2 | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F9 SW | 0.34 | 0.34 | 0.09 | 0.09 |
AIRLOOP F9 NW | 0.27 | 0.27 | 0.09 | 0.09 |
AIRLOOP F9 SE | 0.31 | 0.31 | 0.09 | 0.09 |
AIRLOOP F9 NE | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F9 N1 | 0.13 | 0.13 | 0.05 | 0.05 |
AIRLOOP F9 N2 | 0.13 | 0.13 | 0.05 | 0.05 |
AIRLOOP F9 S1 | 0.24 | 0.24 | 0.05 | 0.05 |
AIRLOOP F9 S2 | 0.24 | 0.24 | 0.05 | 0.05 |
AIRLOOP T SW | 0.41 | 0.41 | 0.12 | 0.12 |
AIRLOOP T NW | 0.33 | 0.33 | 0.12 | 0.12 |
AIRLOOP T SE | 0.38 | 0.38 | 0.12 | 0.12 |
AIRLOOP T NE | 0.24 | 0.24 | 0.12 | 0.12 |
AIRLOOP T N1 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP T N2 | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP T S1 | 0.31 | 0.31 | 0.08 | 0.08 |
AIRLOOP T S2 | 0.32 | 0.32 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2023.50 | 5856.00 | 82.50 |
G NW APARTMENT | 1655.50 | 6542.25 | 178.25 |
OFFICE | 919.75 | 919.25 | 3.75 |
G NE APARTMENT | 1637.75 | 6662.25 | 190.25 |
G N1 APARTMENT | 1162.25 | 6889.00 | 118.75 |
G N2 APARTMENT | 1159.25 | 6910.50 | 121.75 |
G S1 APARTMENT | 1809.00 | 6027.00 | 55.00 |
G S2 APARTMENT | 1874.50 | 5939.00 | 52.50 |
F2 SW APARTMENT | 3063.50 | 4435.50 | 31.75 |
F2 NW APARTMENT | 2367.00 | 5552.00 | 76.25 |
F2 SE APARTMENT | 3335.50 | 4245.75 | 24.50 |
F2 NE APARTMENT | 2271.00 | 5755.50 | 83.75 |
F2 N1 APARTMENT | 1971.50 | 5958.00 | 44.75 |
F2 N2 APARTMENT | 1961.75 | 5980.00 | 45.50 |
F2 S1 APARTMENT | 2963.25 | 4346.75 | 12.00 |
F2 S2 APARTMENT | 3001.00 | 4303.25 | 11.00 |
F3 SW APARTMENT | 3341.75 | 4167.50 | 24.75 |
F3 NW APARTMENT | 2523.25 | 5316.00 | 68.75 |
F3 SE APARTMENT | 3346.50 | 4231.75 | 23.75 |
F3 NE APARTMENT | 2415.00 | 5527.75 | 71.25 |
F3 N1 APARTMENT | 2185.50 | 5623.50 | 31.25 |
F3 N2 APARTMENT | 2170.25 | 5659.00 | 31.25 |
F3 S1 APARTMENT | 3389.25 | 3875.25 | 6.50 |
F3 S2 APARTMENT | 3394.00 | 3873.25 | 6.50 |
F4 SW APARTMENT | 3410.75 | 4130.00 | 24.25 |
F4 NW APARTMENT | 2570.25 | 5248.00 | 69.25 |
F4 SE APARTMENT | 3361.25 | 4258.25 | 24.25 |
F4 NE APARTMENT | 2452.00 | 5467.25 | 71.25 |
F4 N1 APARTMENT | 2252.75 | 5504.75 | 29.00 |
F4 N2 APARTMENT | 2234.50 | 5537.75 | 29.75 |
F4 S1 APARTMENT | 3533.50 | 3767.00 | 6.50 |
F4 S2 APARTMENT | 3530.75 | 3776.50 | 6.50 |
M SW APARTMENT | 3421.75 | 4137.50 | 23.75 |
M NW APARTMENT | 2583.50 | 5247.50 | 67.00 |
M SE APARTMENT | 3359.00 | 4279.50 | 23.75 |
M NE APARTMENT | 2463.00 | 5464.25 | 68.75 |
M N1 APARTMENT | 2292.50 | 5468.50 | 27.50 |
M N2 APARTMENT | 2272.25 | 5498.50 | 27.00 |
M S1 APARTMENT | 3572.50 | 3749.75 | 6.50 |
M S2 APARTMENT | 3566.75 | 3760.25 | 6.50 |
F6 SW APARTMENT | 3255.75 | 4308.75 | 25.75 |
F6 NW APARTMENT | 2449.75 | 5405.00 | 71.25 |
F6 SE APARTMENT | 3184.50 | 4439.25 | 25.50 |
F6 NE APARTMENT | 2332.25 | 5608.75 | 75.75 |
F6 N1 APARTMENT | 2134.50 | 5639.50 | 33.00 |
F6 N2 APARTMENT | 2119.75 | 5670.50 | 33.00 |
F6 S1 APARTMENT | 3374.25 | 3935.75 | 6.00 |
F6 S2 APARTMENT | 3363.25 | 3948.75 | 5.75 |
F7 SW APARTMENT | 3154.50 | 4430.50 | 27.25 |
F7 NW APARTMENT | 2368.75 | 5520.75 | 74.25 |
F7 SE APARTMENT | 3081.00 | 4565.00 | 27.25 |
F7 NE APARTMENT | 2251.00 | 5712.50 | 81.00 |
F7 N1 APARTMENT | 2036.50 | 5767.50 | 36.50 |
F7 N2 APARTMENT | 2020.25 | 5795.50 | 36.50 |
F7 S1 APARTMENT | 3233.00 | 4082.00 | 5.00 |
F7 S2 APARTMENT | 3224.00 | 4093.25 | 5.00 |
F8 SW APARTMENT | 3060.75 | 4544.75 | 28.00 |
F8 NW APARTMENT | 2301.75 | 5622.25 | 78.75 |
F8 SE APARTMENT | 2988.00 | 4670.00 | 28.25 |
F8 NE APARTMENT | 2177.75 | 5810.50 | 86.75 |
F8 N1 APARTMENT | 1968.75 | 5870.25 | 40.00 |
F8 N2 APARTMENT | 1956.75 | 5895.00 | 39.75 |
F8 S1 APARTMENT | 3112.25 | 4231.50 | 5.75 |
F8 S2 APARTMENT | 3108.00 | 4244.25 | 5.50 |
F9 SW APARTMENT | 2916.00 | 4718.25 | 38.50 |
F9 NW APARTMENT | 2241.00 | 5746.50 | 100.50 |
F9 SE APARTMENT | 2853.25 | 4827.50 | 40.75 |
F9 NE APARTMENT | 2109.75 | 5929.50 | 110.25 |
F9 N1 APARTMENT | 1909.50 | 5990.00 | 48.25 |
F9 N2 APARTMENT | 1888.00 | 6021.25 | 47.50 |
F9 S1 APARTMENT | 2940.00 | 4482.00 | 9.75 |
F9 S2 APARTMENT | 2934.00 | 4491.75 | 9.75 |
T SW APARTMENT | 2665.50 | 5279.75 | 233.75 |
T NW APARTMENT | 2164.75 | 6186.75 | 361.75 |
T SE APARTMENT | 2718.50 | 5353.00 | 234.50 |
T NE APARTMENT | 2196.75 | 6309.25 | 371.25 |
T N1 APARTMENT | 1790.75 | 6387.75 | 166.75 |
T N2 APARTMENT | 1781.50 | 6396.25 | 165.75 |
T S1 APARTMENT | 2595.75 | 5067.50 | 81.25 |
T S2 APARTMENT | 2593.25 | 5075.00 | 81.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4423.00 | 7137.25 | 449.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G NW APARTMENT | 3.00 | 23.00 | 3.00 | 23.00 |
OFFICE | 2.75 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 6.50 | 40.50 | 6.50 | 40.50 |
G N1 APARTMENT | 7.00 | 48.00 | 7.00 | 48.00 |
G N2 APARTMENT | 7.50 | 53.00 | 7.50 | 53.00 |
G S1 APARTMENT | 6.00 | 0.00 | 6.00 | 0.00 |
G S2 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
F2 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F2 NW APARTMENT | 1.50 | 21.75 | 1.50 | 21.75 |
F2 SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F2 NE APARTMENT | 4.75 | 48.75 | 4.75 | 48.75 |
F2 N1 APARTMENT | 4.50 | 49.75 | 4.50 | 49.75 |
F2 N2 APARTMENT | 5.00 | 53.00 | 5.00 | 53.00 |
F2 S1 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
F2 S2 APARTMENT | 4.00 | 0.00 | 4.00 | 0.00 |
F3 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F3 NW APARTMENT | 1.50 | 23.00 | 1.50 | 23.00 |
F3 SE APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
F3 NE APARTMENT | 4.00 | 54.75 | 4.00 | 54.75 |
F3 N1 APARTMENT | 6.50 | 56.75 | 6.50 | 56.75 |
F3 N2 APARTMENT | 6.25 | 60.75 | 6.25 | 60.75 |
F3 S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F3 S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
F4 SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F4 NW APARTMENT | 0.75 | 23.75 | 0.75 | 23.75 |
F4 SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F4 NE APARTMENT | 3.50 | 56.50 | 3.50 | 56.50 |
F4 N1 APARTMENT | 5.00 | 59.00 | 5.00 | 59.00 |
F4 N2 APARTMENT | 4.25 | 64.00 | 4.25 | 64.00 |
F4 S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F4 S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M SW APARTMENT | 0.50 | 0.25 | 0.50 | 0.25 |
M NW APARTMENT | 1.50 | 23.25 | 1.50 | 23.25 |
M SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M NE APARTMENT | 4.25 | 58.50 | 4.25 | 58.50 |
M N1 APARTMENT | 4.50 | 59.25 | 4.50 | 59.25 |
M N2 APARTMENT | 5.25 | 64.50 | 5.25 | 64.50 |
M S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F6 SW APARTMENT | 0.25 | 0.75 | 0.25 | 0.75 |
F6 NW APARTMENT | 1.00 | 24.25 | 1.00 | 24.25 |
F6 SE APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
F6 NE APARTMENT | 3.75 | 62.00 | 3.75 | 62.00 |
F6 N1 APARTMENT | 6.00 | 59.25 | 6.00 | 59.25 |
F6 N2 APARTMENT | 4.50 | 65.00 | 4.50 | 65.00 |
F6 S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
F6 S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F7 SW APARTMENT | 0.50 | 1.25 | 0.50 | 1.25 |
F7 NW APARTMENT | 0.75 | 25.00 | 0.75 | 25.00 |
F7 SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F7 NE APARTMENT | 2.75 | 63.25 | 2.75 | 63.25 |
F7 N1 APARTMENT | 7.50 | 59.75 | 7.50 | 59.75 |
F7 N2 APARTMENT | 6.50 | 62.25 | 6.50 | 62.25 |
F7 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F7 S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
F8 SW APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
F8 NW APARTMENT | 1.25 | 25.50 | 1.25 | 25.50 |
F8 SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F8 NE APARTMENT | 2.25 | 64.75 | 2.25 | 64.75 |
F8 N1 APARTMENT | 4.25 | 59.25 | 4.25 | 59.25 |
F8 N2 APARTMENT | 4.00 | 62.25 | 4.00 | 62.25 |
F8 S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
F8 S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
F9 SW APARTMENT | 0.25 | 2.25 | 0.25 | 2.25 |
F9 NW APARTMENT | 1.00 | 24.25 | 1.00 | 24.25 |
F9 SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 2.25 | 48.00 | 2.25 | 48.00 |
F9 N1 APARTMENT | 5.50 | 53.00 | 5.50 | 53.00 |
F9 N2 APARTMENT | 5.25 | 54.75 | 5.25 | 54.75 |
F9 S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F9 S2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.00 | 22.75 | 0.00 | 22.75 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.75 | 35.75 | 0.75 | 35.75 |
T N1 APARTMENT | 3.75 | 35.75 | 3.75 | 35.75 |
T N2 APARTMENT | 3.25 | 34.50 | 3.25 | 34.50 |
T S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 157.75 | 86.75 | 155.00 | 86.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.153 | 0.000 | 0.290 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.153 | 0.000 | 0.282 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.181 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.153 | 0.000 | 0.282 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.092 | 0.000 | 0.275 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.092 | 0.000 | 0.274 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.092 | 0.000 | 0.287 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.092 | 0.000 | 0.288 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.220 | 0.000 | 0.329 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.220 | 0.000 | 0.323 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.220 | 0.000 | 0.331 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.220 | 0.000 | 0.323 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.133 | 0.000 | 0.317 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.317 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.133 | 0.000 | 0.327 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.133 | 0.000 | 0.327 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.261 | 0.000 | 0.353 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.261 | 0.000 | 0.349 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.261 | 0.000 | 0.353 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.261 | 0.000 | 0.348 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.157 | 0.000 | 0.344 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.157 | 0.000 | 0.344 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.157 | 0.000 | 0.351 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.157 | 0.000 | 0.351 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.292 | 0.000 | 0.356 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.291 | 0.000 | 0.354 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.292 | 0.000 | 0.357 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.291 | 0.000 | 0.354 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.176 | 0.000 | 0.350 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.350 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.176 | 0.000 | 0.355 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.176 | 0.000 | 0.355 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.317 | 0.000 | 0.370 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.317 | 0.000 | 0.369 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.317 | 0.000 | 0.371 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.316 | 0.000 | 0.368 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.191 | 0.000 | 0.365 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.191 | 0.000 | 0.365 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.191 | 0.000 | 0.369 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.191 | 0.000 | 0.369 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.339 | 0.000 | 0.382 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.381 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.382 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.338 | 0.000 | 0.380 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.204 | 0.000 | 0.376 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.204 | 0.000 | 0.376 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.204 | 0.000 | 0.381 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.204 | 0.000 | 0.381 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.358 | 0.000 | 0.392 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.357 | 0.000 | 0.391 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.358 | 0.000 | 0.392 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.357 | 0.000 | 0.390 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.216 | 0.000 | 0.386 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.216 | 0.000 | 0.386 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.216 | 0.000 | 0.390 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.216 | 0.000 | 0.390 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.375 | 0.000 | 0.403 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.375 | 0.000 | 0.402 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.375 | 0.000 | 0.403 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.375 | 0.000 | 0.401 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.226 | 0.000 | 0.397 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.226 | 0.000 | 0.397 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.226 | 0.000 | 0.401 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.226 | 0.000 | 0.401 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.391 | 0.000 | 0.412 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.390 | 0.000 | 0.411 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.391 | 0.000 | 0.412 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.390 | 0.000 | 0.410 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.235 | 0.000 | 0.406 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.235 | 0.000 | 0.406 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.236 | 0.000 | 0.410 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.236 | 0.000 | 0.410 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.405 | 0.000 | 0.419 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.405 | 0.000 | 0.419 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.405 | 0.000 | 0.420 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.405 | 0.000 | 0.419 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.244 | 0.000 | 0.415 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.244 | 0.000 | 0.415 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.244 | 0.000 | 0.418 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.244 | 0.000 | 0.418 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.501 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 662.42 | 21005.32 | 11-FEB-17:15 | 21005.32 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1077.71 | 21666.56 | 04-MAY-03:00 | 92023.82 | 19-JUL-16:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
ElectricityPurchased:Plant | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
Cogeneration:ElectricityPurchased | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
ElectricityNet:Plant | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
Cogeneration:ElectricityNet | 2745.02 | 55719.61 | 30-MAY-05:00 | 165462.52 | 19-JUL-17:15 |
ExteriorLights:Electricity | 162.79 | 0.00 | 01-JAN-08:00 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.79 | 0.00 | 01-JAN-08:00 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 662.42 | 21005.32 | 11-FEB-17:15 | 21005.32 | 01-JAN-00:15 |
Cooling:Electricity | 235.55 | 0.00 | 01-JAN-00:15 | 69138.10 | 31-JUL-15:15 |
Heating:Electricity | 143.57 | 0.00 | 21-FEB-13:45 | 63192.47 | 15-FEB-02:00 |
Electricity:Plant | 70.63 | 36.93 | 04-APR-19:45 | 4605.14 | 18-JUL-16:00 |
HeatRejection:Electricity | 9.60 | 0.00 | 01-JAN-00:15 | 2645.30 | 18-JUL-16:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 61.04 | 36.93 | 04-APR-19:45 | 1959.84 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1632.57 | 2357.00 | 19-JAN-24:00 | 258366.00 | 20-DEC-08:00 |
Gas:Plant | 1632.57 | 2357.00 | 19-JAN-24:00 | 258366.00 | 20-DEC-08:00 |
WaterSystems:Gas | 1149.45 | 2357.00 | 01-JAN-00:15 | 80018.31 | 11-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1149.45 | 2357.00 | 01-JAN-00:15 | 80018.31 | 11-FEB-08:00 |
Heating:Gas | 483.12 | 0.00 | 15-JAN-16:00 | 211963.52 | 15-FEB-02:30 |
Boiler:Heating:Gas | 483.12 | 0.00 | 15-JAN-16:00 | 211963.52 | 15-FEB-02:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 960.08 | 0.00 | 01-JAN-00:15 | 318244.52 | 19-JUL-16:15 |
PlantLoopCoolingDemand:HVAC | 960.08 | 0.00 | 01-JAN-00:15 | 318244.52 | 19-JUL-16:15 |
CoolingCoils:PlantLoopCoolingDemand | 960.08 | 0.00 | 01-JAN-00:15 | 318244.52 | 19-JUL-16:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5524.92 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:15 |
Water:Plant | 5524.92 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5524.92 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:15 |
MainsWater:Plant | 5524.92 | 0.00 | 01-JAN-02:15 | 0.00 | 17-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 746.40 | 0.00 | 01-JAN-00:15 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 746.40 | 0.00 | 01-JAN-00:15 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1295.88 | 491.11 | 05-AUG-01:15 | 193777.68 | 15-FEB-06:15 |
PlantLoopHeatingDemand:Plant | 894.38 | 491.11 | 05-AUG-01:15 | 58046.59 | 09-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 894.38 | 491.11 | 05-AUG-01:15 | 58046.59 | 09-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 3650.46 | 7088.15 | 26-OCT-01:15 | 572209.03 | 15-FEB-02:15 |
EnergyTransfer:Building | 1122.14 | 4319.10 | 10-NOV-17:30 | 193304.42 | 09-SEP-15:15 |
EnergyTransfer:Zone:G SW APARTMENT | 12.10 | 0.01 | 21-APR-19:30 | 2928.99 | 10-SEP-15:30 |
Heating:EnergyTransfer | 356.64 | 0.00 | 31-JAN-13:15 | 191675.41 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 4.67 | 0.00 | 01-JAN-09:15 | 1912.16 | 15-FEB-02:00 |
Cooling:EnergyTransfer | 765.50 | 0.00 | 03-JAN-01:00 | 193304.42 | 09-SEP-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 7.43 | 0.00 | 01-JAN-00:15 | 2928.99 | 10-SEP-15:30 |
EnergyTransfer:Zone:G NW APARTMENT | 11.27 | 0.02 | 24-APR-01:45 | 2305.46 | 24-JUN-18:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.33 | 0.00 | 15-JAN-16:15 | 1937.26 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.94 | 0.00 | 01-JAN-00:15 | 2305.46 | 24-JUN-18:00 |
EnergyTransfer:Zone:OFFICE | 19.08 | 0.01 | 21-OCT-01:45 | 3791.43 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:OFFICE | 3.03 | 0.00 | 01-JAN-08:45 | 1699.43 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 16.06 | 0.00 | 01-JAN-00:15 | 3791.43 | 31-AUG-13:30 |
EnergyTransfer:Zone:G NE APARTMENT | 11.07 | 0.00 | 22-SEP-19:30 | 1940.50 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.24 | 0.00 | 15-JAN-17:15 | 1940.50 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.83 | 0.00 | 01-JAN-00:15 | 1616.99 | 04-JUN-09:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 7.49 | 0.02 | 17-AUG-09:45 | 1221.10 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.00 | 0.00 | 07-JAN-18:45 | 1221.10 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.49 | 0.00 | 01-JAN-00:15 | 1018.76 | 14-JUL-19:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 7.48 | 0.05 | 31-OCT-22:15 | 1221.48 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.00 | 0.00 | 07-JAN-18:45 | 1221.48 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.48 | 0.00 | 01-JAN-00:15 | 993.92 | 14-JUL-19:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 8.71 | 0.02 | 30-SEP-20:30 | 2045.42 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.61 | 0.00 | 01-JAN-00:15 | 1275.09 | 09-NOV-11:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.09 | 0.00 | 01-JAN-00:30 | 2045.42 | 31-AUG-12:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 8.78 | 0.04 | 03-MAR-22:30 | 2104.98 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.49 | 0.00 | 01-JAN-00:15 | 1196.99 | 09-NOV-11:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.29 | 0.00 | 01-JAN-00:30 | 2104.98 | 31-AUG-12:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 16.27 | 0.02 | 06-NOV-01:15 | 3705.43 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 3.80 | 0.00 | 01-JAN-00:15 | 2288.84 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 12.46 | 0.00 | 01-JAN-01:15 | 3705.43 | 09-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 13.25 | 0.00 | 30-MAR-19:15 | 2953.24 | 24-JUN-18:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 5.50 | 0.00 | 15-JAN-17:15 | 2379.64 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 7.75 | 0.00 | 01-JAN-00:15 | 2953.24 | 24-JUN-18:00 |
EnergyTransfer:Zone:F2 SE APARTMENT | 16.47 | 0.02 | 19-SEP-02:30 | 3368.03 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 3.21 | 0.00 | 01-JAN-00:15 | 2199.20 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 13.26 | 0.00 | 01-JAN-01:15 | 3368.03 | 09-SEP-13:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 12.95 | 0.01 | 09-NOV-10:45 | 2384.81 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 5.38 | 0.00 | 15-JAN-16:15 | 2384.81 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 7.57 | 0.00 | 01-JAN-00:15 | 2200.91 | 04-JUN-09:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 8.79 | 0.01 | 20-JUN-15:30 | 1438.81 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 1.77 | 0.00 | 01-JAN-17:15 | 1438.81 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 7.01 | 0.00 | 01-JAN-00:15 | 1395.20 | 14-JUL-19:00 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 8.77 | 0.01 | 04-MAY-09:45 | 1437.99 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 1.78 | 0.00 | 01-JAN-17:15 | 1437.99 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 6.99 | 0.00 | 01-JAN-00:15 | 1372.58 | 14-JUL-19:00 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 12.65 | 0.07 | 01-NOV-03:00 | 2619.35 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 1225.54 | 09-NOV-11:15 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 11.63 | 0.00 | 02-JAN-23:30 | 2619.35 | 31-AUG-12:45 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 12.73 | 0.04 | 26-OCT-23:00 | 2643.72 | 31-AUG-12:45 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 1.00 | 0.00 | 01-JAN-00:15 | 1183.56 | 15-FEB-02:15 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 11.73 | 0.00 | 02-JAN-23:30 | 2643.72 | 31-AUG-12:45 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 17.30 | 0.00 | 23-FEB-14:00 | 3757.93 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 3.93 | 0.00 | 01-JAN-00:15 | 2531.86 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 13.37 | 0.00 | 01-JAN-02:15 | 3757.93 | 09-SEP-15:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 13.99 | 0.02 | 25-MAY-10:00 | 3008.65 | 23-JUN-18:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 5.63 | 0.00 | 01-JAN-18:45 | 2632.76 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 8.36 | 0.00 | 01-JAN-00:15 | 3008.65 | 23-JUN-18:00 |
EnergyTransfer:Zone:F3 SE APARTMENT | 16.90 | 0.00 | 23-OCT-15:00 | 3395.78 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 3.76 | 0.00 | 01-JAN-00:15 | 2521.30 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 13.15 | 0.00 | 01-JAN-02:15 | 3395.78 | 09-SEP-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 13.68 | 0.03 | 10-JUL-08:30 | 2638.07 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 5.52 | 0.00 | 01-JAN-09:30 | 2638.07 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 8.16 | 0.00 | 01-JAN-00:15 | 2266.13 | 04-JUN-09:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 9.48 | 0.01 | 21-SEP-12:00 | 1621.64 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 1.72 | 0.00 | 01-JAN-08:00 | 1621.64 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.76 | 0.00 | 01-JAN-00:15 | 1458.77 | 22-JUN-16:15 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 9.46 | 0.01 | 04-OCT-09:30 | 1621.07 | 12-DEC-13:15 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 1.72 | 0.00 | 01-JAN-08:00 | 1621.07 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.74 | 0.00 | 01-JAN-00:15 | 1448.55 | 22-JUN-16:15 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 13.92 | 0.01 | 12-DEC-00:45 | 2709.16 | 30-AUG-14:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 1346.46 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 12.90 | 0.00 | 03-JAN-00:30 | 2709.16 | 30-AUG-14:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 13.92 | 0.04 | 09-FEB-19:45 | 2721.03 | 30-AUG-14:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 1343.94 | 12-DEC-13:15 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 12.91 | 0.00 | 03-JAN-00:30 | 2721.03 | 30-AUG-14:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 17.69 | 0.02 | 01-MAR-14:00 | 3792.32 | 09-SEP-15:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 4.25 | 0.00 | 01-JAN-00:15 | 2764.33 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 13.45 | 0.00 | 01-JAN-02:15 | 3792.32 | 09-SEP-15:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 14.43 | 0.03 | 21-FEB-13:00 | 3046.96 | 23-JUN-17:45 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 6.00 | 0.00 | 01-JAN-18:30 | 2865.76 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 8.43 | 0.00 | 01-JAN-00:15 | 3046.96 | 23-JUN-17:45 |
EnergyTransfer:Zone:F4 SE APARTMENT | 17.21 | 0.04 | 30-DEC-11:45 | 3432.39 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 4.16 | 0.00 | 01-JAN-00:15 | 2768.18 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 13.05 | 0.00 | 01-JAN-02:15 | 3432.39 | 09-SEP-13:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 14.13 | 0.00 | 27-JUN-18:15 | 2871.08 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 5.89 | 0.00 | 01-JAN-09:30 | 2871.08 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 8.25 | 0.00 | 01-JAN-00:15 | 2300.00 | 04-JUN-09:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 9.76 | 0.01 | 07-SEP-12:45 | 1554.71 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 1.83 | 0.00 | 01-JAN-07:15 | 1554.71 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 7.93 | 0.00 | 01-JAN-00:15 | 1511.68 | 22-JUN-16:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 9.74 | 0.01 | 18-JUN-18:15 | 1555.07 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 1.83 | 0.00 | 01-JAN-07:15 | 1555.07 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 7.90 | 0.00 | 01-JAN-00:15 | 1488.15 | 22-JUN-16:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 14.29 | 0.04 | 11-JUL-14:15 | 2729.88 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 1.11 | 0.00 | 01-JAN-00:15 | 1434.66 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 13.18 | 0.00 | 03-JAN-01:00 | 2729.88 | 31-AUG-13:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 14.27 | 0.07 | 27-OCT-01:45 | 2741.59 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 1.11 | 0.00 | 01-JAN-00:15 | 1434.63 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 13.16 | 0.00 | 03-JAN-01:00 | 2741.59 | 31-AUG-13:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 18.01 | 0.01 | 17-NOV-20:00 | 3841.83 | 09-SEP-15:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 4.55 | 0.00 | 01-JAN-00:15 | 2953.29 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 13.46 | 0.00 | 01-JAN-02:15 | 3841.83 | 09-SEP-15:30 |
EnergyTransfer:Zone:M NW APARTMENT | 14.81 | 0.03 | 20-SEP-08:45 | 3105.73 | 23-JUN-17:45 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 6.31 | 0.00 | 01-JAN-18:30 | 3050.70 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 8.49 | 0.00 | 01-JAN-00:15 | 3105.73 | 23-JUN-17:45 |
EnergyTransfer:Zone:M SE APARTMENT | 17.52 | 0.03 | 01-NOV-15:00 | 3484.75 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 4.48 | 0.00 | 01-JAN-00:15 | 2959.38 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 13.04 | 0.00 | 01-JAN-02:15 | 3484.75 | 09-SEP-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 14.52 | 0.02 | 10-JUL-21:00 | 3056.03 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 6.20 | 0.00 | 01-JAN-09:15 | 3056.03 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 8.32 | 0.00 | 01-JAN-00:15 | 2341.86 | 04-JUN-09:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 10.01 | 0.02 | 26-JUN-10:45 | 1657.82 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.93 | 0.00 | 01-JAN-07:00 | 1657.82 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 8.08 | 0.00 | 01-JAN-00:15 | 1552.44 | 22-JUN-16:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 9.99 | 0.01 | 08-AUG-10:15 | 1658.17 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.94 | 0.00 | 01-JAN-07:00 | 1658.17 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 8.05 | 0.00 | 01-JAN-00:15 | 1539.97 | 22-JUN-15:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 14.52 | 0.02 | 04-DEC-08:00 | 2768.75 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.21 | 0.00 | 01-JAN-00:15 | 1545.60 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 13.31 | 0.00 | 03-JAN-00:45 | 2768.75 | 31-AUG-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 14.49 | 0.03 | 28-JUN-15:15 | 2780.13 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.21 | 0.00 | 01-JAN-00:15 | 1545.84 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 13.28 | 0.00 | 03-JAN-01:00 | 2780.13 | 31-AUG-13:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 17.87 | 0.08 | 22-MAR-01:45 | 3822.68 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 5.18 | 0.00 | 01-JAN-00:15 | 3167.00 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 12.70 | 0.00 | 01-JAN-02:00 | 3822.68 | 09-SEP-15:15 |
EnergyTransfer:Zone:F6 NW APARTMENT | 15.06 | 0.03 | 13-OCT-11:45 | 3261.22 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 7.10 | 0.00 | 01-JAN-18:45 | 3261.22 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 7.96 | 0.00 | 01-JAN-00:15 | 3088.04 | 23-JUN-17:45 |
EnergyTransfer:Zone:F6 SE APARTMENT | 17.40 | 0.02 | 28-JUN-02:30 | 3472.69 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 5.11 | 0.00 | 01-JAN-00:15 | 3173.41 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 12.29 | 0.00 | 01-JAN-01:45 | 3472.69 | 09-SEP-13:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 14.80 | 0.00 | 09-NOV-16:15 | 3266.62 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 6.99 | 0.00 | 01-JAN-09:30 | 3266.62 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 7.81 | 0.00 | 01-JAN-00:15 | 2315.66 | 04-JUN-09:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 9.85 | 0.01 | 17-SEP-19:45 | 1793.76 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 2.33 | 0.00 | 01-JAN-07:15 | 1793.76 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 7.53 | 0.00 | 01-JAN-00:15 | 1528.74 | 26-AUG-18:15 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 9.83 | 0.00 | 04-AUG-20:00 | 1794.13 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 2.33 | 0.00 | 01-JAN-07:15 | 1794.13 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 7.50 | 0.00 | 01-JAN-00:15 | 1520.74 | 22-JUN-15:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 14.01 | 0.02 | 12-DEC-20:45 | 2741.62 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 1.46 | 0.00 | 01-JAN-00:15 | 1676.74 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 12.54 | 0.00 | 03-JAN-00:15 | 2741.62 | 31-AUG-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 13.98 | 0.01 | 14-JAN-23:45 | 2752.96 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 1.47 | 0.00 | 01-JAN-00:15 | 1677.03 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 12.51 | 0.00 | 03-JAN-00:15 | 2752.96 | 31-AUG-13:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 17.90 | 0.02 | 01-MAR-20:45 | 3824.73 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 5.70 | 0.00 | 01-JAN-00:15 | 3345.78 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 12.20 | 0.00 | 01-JAN-01:45 | 3824.73 | 09-SEP-15:15 |
EnergyTransfer:Zone:F7 NW APARTMENT | 15.35 | 0.02 | 27-OCT-07:00 | 3435.28 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 7.72 | 0.00 | 01-JAN-18:45 | 3435.28 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 7.63 | 0.00 | 01-JAN-00:15 | 3091.99 | 23-JUN-17:45 |
EnergyTransfer:Zone:F7 SE APARTMENT | 17.45 | 0.01 | 31-DEC-02:00 | 3478.10 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 5.64 | 0.00 | 01-JAN-00:15 | 3352.05 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 11.81 | 0.00 | 01-JAN-01:30 | 3478.10 | 09-SEP-13:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 15.10 | 0.02 | 14-APR-01:15 | 3440.74 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 7.60 | 0.00 | 01-JAN-09:30 | 3440.74 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 7.49 | 0.00 | 01-JAN-00:15 | 2311.69 | 04-JUN-09:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 9.83 | 0.01 | 22-MAY-13:15 | 1903.97 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 2.64 | 0.00 | 01-JAN-07:30 | 1903.97 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 7.19 | 0.00 | 01-JAN-00:15 | 1532.11 | 26-AUG-18:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 9.81 | 0.02 | 11-SEP-10:45 | 1904.34 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 2.64 | 0.00 | 01-JAN-07:30 | 1904.34 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 7.17 | 0.00 | 01-JAN-00:15 | 1521.16 | 26-AUG-18:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 13.73 | 0.03 | 26-OCT-22:45 | 2736.40 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 1.69 | 0.00 | 01-JAN-00:15 | 1788.98 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 12.04 | 0.00 | 02-JAN-23:30 | 2736.40 | 31-AUG-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 13.70 | 0.02 | 09-NOV-19:45 | 2747.71 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 1.69 | 0.00 | 01-JAN-00:15 | 1789.31 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 12.01 | 0.00 | 02-JAN-23:30 | 2747.71 | 31-AUG-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 18.02 | 0.03 | 16-MAR-00:15 | 3835.88 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 6.22 | 0.00 | 01-JAN-00:15 | 3514.18 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 11.80 | 0.00 | 01-JAN-01:15 | 3835.88 | 09-SEP-15:15 |
EnergyTransfer:Zone:F8 NW APARTMENT | 15.70 | 0.01 | 18-JUN-13:30 | 3597.64 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 8.31 | 0.00 | 01-JAN-19:00 | 3597.64 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 7.38 | 0.00 | 01-JAN-00:15 | 3100.42 | 23-JUN-18:00 |
EnergyTransfer:Zone:F8 SE APARTMENT | 17.59 | 0.02 | 06-JUN-04:15 | 3520.26 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 6.17 | 0.00 | 01-JAN-00:15 | 3520.26 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 11.42 | 0.00 | 01-JAN-01:15 | 3485.81 | 09-SEP-13:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 15.46 | 0.09 | 06-JUL-08:15 | 3603.17 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 8.20 | 0.00 | 01-JAN-10:00 | 3603.17 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 7.26 | 0.00 | 01-JAN-00:15 | 2340.04 | 04-JUN-09:45 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 9.89 | 0.01 | 02-DEC-20:30 | 2008.84 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 2.96 | 0.00 | 01-JAN-17:30 | 2008.84 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 6.92 | 0.00 | 01-JAN-00:15 | 1560.97 | 04-JUN-09:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 9.87 | 0.00 | 28-JUN-15:30 | 2009.22 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 2.97 | 0.00 | 01-JAN-17:30 | 2009.22 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 6.90 | 0.00 | 01-JAN-00:15 | 1548.72 | 04-JUN-09:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 13.53 | 0.01 | 17-SEP-20:45 | 2741.31 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 1.92 | 0.00 | 01-JAN-00:15 | 1899.19 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 11.60 | 0.00 | 02-JAN-23:00 | 2741.31 | 31-AUG-13:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 13.50 | 0.01 | 15-JAN-15:15 | 2752.65 | 31-AUG-13:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 1.93 | 0.00 | 01-JAN-00:15 | 1899.50 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 11.57 | 0.00 | 02-JAN-23:00 | 2752.65 | 31-AUG-13:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 18.52 | 0.00 | 29-OCT-18:30 | 3916.68 | 09-SEP-15:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 7.17 | 0.00 | 01-JAN-00:15 | 3748.44 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 11.35 | 0.00 | 01-JAN-00:30 | 3916.68 | 09-SEP-15:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 16.56 | 0.02 | 29-APR-04:15 | 3815.60 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 9.40 | 0.00 | 15-JAN-17:30 | 3815.60 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 7.16 | 0.00 | 01-JAN-00:15 | 3191.59 | 23-JUN-18:00 |
EnergyTransfer:Zone:F9 SE APARTMENT | 18.07 | 0.02 | 30-OCT-11:45 | 3754.35 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 7.11 | 0.00 | 01-JAN-00:15 | 3754.35 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 10.96 | 0.00 | 01-JAN-00:30 | 3512.99 | 09-SEP-13:45 |
EnergyTransfer:Zone:F9 NE APARTMENT | 16.30 | 0.01 | 18-OCT-12:30 | 3821.17 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 9.26 | 0.00 | 15-JAN-17:30 | 3821.17 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 7.04 | 0.00 | 01-JAN-00:15 | 2451.65 | 04-JUN-09:45 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 10.23 | 0.05 | 10-JUN-10:30 | 2167.72 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.65 | 0.00 | 01-JAN-18:00 | 2167.72 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 6.58 | 0.00 | 01-JAN-00:15 | 1598.07 | 24-JUN-21:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 10.22 | 0.04 | 07-JUN-13:00 | 2168.11 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.66 | 0.00 | 01-JAN-18:00 | 2168.11 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 6.56 | 0.00 | 01-JAN-00:15 | 1597.94 | 04-JUN-09:45 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 13.41 | 0.05 | 20-FEB-21:45 | 2800.09 | 31-AUG-13:15 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 2077.59 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 11.00 | 0.00 | 01-JAN-04:00 | 2800.09 | 31-AUG-13:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 13.39 | 0.15 | 08-NOV-12:00 | 2812.63 | 31-AUG-13:15 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 2.42 | 0.00 | 01-JAN-00:15 | 2077.88 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 10.97 | 0.00 | 01-JAN-04:00 | 2812.63 | 31-AUG-13:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 23.39 | 0.02 | 04-MAY-05:45 | 4663.18 | 17-JUL-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 11.75 | 0.00 | 01-JAN-09:15 | 4291.46 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 11.64 | 0.00 | 01-JAN-00:15 | 4663.18 | 17-JUL-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 21.19 | 0.03 | 19-JUN-18:45 | 4310.17 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.65 | 0.00 | 15-JAN-18:45 | 4310.17 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 7.53 | 0.00 | 01-JAN-00:15 | 3888.91 | 15-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 22.52 | 0.01 | 10-OCT-00:30 | 4294.19 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 11.50 | 0.00 | 01-JAN-08:45 | 4294.19 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.03 | 0.00 | 01-JAN-00:15 | 4179.51 | 09-SEP-13:15 |
EnergyTransfer:Zone:T NE APARTMENT | 20.41 | 0.00 | 28-SEP-03:15 | 4312.75 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 13.27 | 0.00 | 15-JAN-18:15 | 4312.75 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.14 | 0.00 | 01-JAN-00:15 | 3061.83 | 04-JUN-09:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 13.10 | 0.04 | 12-DEC-16:45 | 2627.86 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 6.86 | 0.00 | 15-JAN-16:15 | 2627.86 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 6.24 | 0.00 | 01-JAN-00:15 | 2258.43 | 24-JUN-19:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 13.08 | 0.03 | 08-NOV-14:45 | 2628.09 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 6.88 | 0.00 | 15-JAN-16:15 | 2628.09 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 6.21 | 0.00 | 01-JAN-00:15 | 2251.47 | 24-JUN-19:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 15.33 | 0.01 | 06-APR-23:45 | 3621.78 | 10-SEP-13:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 5.26 | 0.00 | 01-JAN-08:45 | 2596.64 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 10.07 | 0.00 | 01-JAN-00:15 | 3621.78 | 10-SEP-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 15.33 | 0.01 | 14-NOV-13:45 | 3634.20 | 10-SEP-13:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 5.28 | 0.00 | 01-JAN-08:45 | 2596.82 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 10.05 | 0.00 | 01-JAN-00:15 | 3634.20 | 10-SEP-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1256.27 | 491.11 | 05-AUG-01:15 | 194701.58 | 15-FEB-06:15 |
WaterSystems:EnergyTransfer | 894.38 | 491.11 | 05-AUG-01:15 | 58040.65 | 09-FEB-07:30 |
sub cat:WaterSystems:EnergyTransfer | 894.38 | 491.11 | 05-AUG-01:15 | 58040.65 | 09-FEB-07:30 |
EnergyTransfer:HVAC | 1272.05 | 0.00 | 04-APR-19:45 | 249587.41 | 19-JUL-16:15 |
CoolingCoils:EnergyTransfer | 747.18 | 0.00 | 01-JAN-00:15 | 249587.41 | 19-JUL-16:15 |
HeatingCoils:EnergyTransfer | 524.88 | 0.00 | 21-FEB-13:45 | 222620.38 | 15-FEB-02:00 |
PlantLoopHeatingDemand:HVAC | 401.49 | 0.00 | 21-FEB-13:45 | 161111.39 | 15-FEB-02:00 |
HeatingCoils:PlantLoopHeatingDemand | 401.49 | 0.00 | 21-FEB-13:45 | 161111.39 | 15-FEB-02:00 |
Boilers:EnergyTransfer | 361.89 | 0.00 | 15-JAN-16:00 | 158972.64 | 15-FEB-02:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 4.667 | -7.431 | 0.000 | 0.000 | 3.846 | 1.087 | 12.213 | 18.824 | 0.000 | 0.198 | 0.000 | 0.000 | -10.392 | 0.000 | -8.269 | -14.742 |
G NW APARTMENT | 6.329 | -4.938 | 0.000 | 0.000 | 3.892 | 1.087 | 12.213 | 10.285 | 0.000 | 0.200 | 0.000 | 0.000 | -10.408 | 0.000 | -7.765 | -10.893 |
OFFICE | 3.028 | -16.056 | 0.000 | 0.000 | 0.521 | 29.882 | 9.495 | 17.792 | 0.000 | 0.118 | 0.000 | 0.000 | -10.415 | 0.000 | -4.819 | -29.546 |
G NE APARTMENT | 6.243 | -4.829 | 0.000 | 0.000 | 3.913 | 1.087 | 12.213 | 9.342 | 0.000 | 0.199 | 0.000 | 0.000 | -10.112 | 0.000 | -7.725 | -10.330 |
G N1 APARTMENT | 2.998 | -4.488 | 0.000 | 0.000 | 3.915 | 1.087 | 12.213 | 3.551 | 0.000 | 0.152 | 0.000 | 0.000 | -6.365 | 0.000 | -5.639 | -7.424 |
G N2 APARTMENT | 3.001 | -4.477 | 0.000 | 0.000 | 3.917 | 1.087 | 12.213 | 3.551 | 0.000 | 0.152 | 0.000 | 0.000 | -6.360 | 0.000 | -5.634 | -7.448 |
G S1 APARTMENT | 1.611 | -7.094 | 0.000 | 0.000 | 3.845 | 1.087 | 12.213 | 12.190 | 0.000 | 0.151 | 0.000 | 0.000 | -6.347 | 0.000 | -6.242 | -11.414 |
G S2 APARTMENT | 1.495 | -7.287 | 0.000 | 0.000 | 3.839 | 1.087 | 12.213 | 12.171 | 0.000 | 0.151 | 0.000 | 0.000 | -6.366 | 0.000 | -6.298 | -11.004 |
F2 SW APARTMENT | 3.803 | -12.462 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 18.214 | 0.000 | 0.262 | 0.001 | 0.000 | -11.171 | 0.000 | -11.202 | -4.505 |
F2 NW APARTMENT | 5.501 | -7.753 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 9.829 | 0.000 | 0.266 | 0.000 | 0.000 | -11.062 | 0.000 | -10.596 | -3.315 |
F2 SE APARTMENT | 3.206 | -13.264 | 0.000 | 0.000 | 3.752 | 1.087 | 12.213 | 17.251 | 0.000 | 0.262 | 0.001 | 0.000 | -11.060 | 0.000 | -11.333 | -2.113 |
F2 NE APARTMENT | 5.381 | -7.568 | 0.000 | 0.000 | 3.854 | 1.087 | 12.213 | 8.912 | 0.000 | 0.264 | 0.000 | 0.000 | -10.730 | 0.000 | -10.518 | -2.893 |
F2 N1 APARTMENT | 1.774 | -7.013 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 3.301 | 0.000 | 0.197 | 0.000 | 0.000 | -6.812 | 0.000 | -7.613 | -0.983 |
F2 N2 APARTMENT | 1.779 | -6.994 | 0.000 | 0.000 | 3.852 | 1.087 | 12.213 | 3.302 | 0.000 | 0.196 | 0.000 | 0.000 | -6.805 | 0.000 | -7.604 | -1.026 |
F2 S1 APARTMENT | 1.019 | -11.633 | 0.000 | 0.000 | 3.745 | 1.087 | 12.213 | 11.813 | 0.000 | 0.195 | 0.002 | 0.000 | -6.845 | 0.000 | -8.370 | -3.222 |
F2 S2 APARTMENT | 0.998 | -11.734 | 0.000 | 0.000 | 3.742 | 1.087 | 12.213 | 11.807 | 0.000 | 0.195 | 0.002 | 0.000 | -6.853 | 0.000 | -8.387 | -3.068 |
F3 SW APARTMENT | 3.931 | -13.366 | 0.000 | 0.000 | 3.748 | 1.087 | 12.213 | 17.987 | 0.000 | 0.313 | 0.000 | 0.000 | -11.398 | 0.000 | -12.765 | -1.750 |
F3 NW APARTMENT | 5.629 | -8.364 | 0.000 | 0.000 | 3.818 | 1.087 | 12.213 | 9.665 | 0.000 | 0.318 | 0.000 | 0.000 | -11.273 | 0.000 | -12.136 | -0.957 |
F3 SE APARTMENT | 3.757 | -13.146 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 17.098 | 0.000 | 0.314 | 0.000 | 0.000 | -11.174 | 0.000 | -12.779 | -1.123 |
F3 NE APARTMENT | 5.519 | -8.161 | 0.000 | 0.000 | 3.841 | 1.087 | 12.213 | 8.764 | 0.000 | 0.316 | 0.000 | 0.000 | -10.935 | 0.000 | -12.047 | -0.595 |
F3 N1 APARTMENT | 1.720 | -7.764 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 3.219 | 0.000 | 0.236 | 1.098 | 0.000 | -6.959 | 0.000 | -8.679 | -0.000 |
F3 N2 APARTMENT | 1.724 | -7.739 | 0.000 | 0.000 | 3.833 | 1.087 | 12.213 | 3.220 | 0.000 | 0.236 | 1.048 | 0.000 | -6.952 | 0.000 | -8.669 | -0.000 |
F3 S1 APARTMENT | 1.018 | -12.901 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 11.665 | 0.000 | 0.235 | 0.001 | 0.000 | -7.011 | 0.000 | -9.457 | -0.570 |
F3 S2 APARTMENT | 1.015 | -12.909 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 11.663 | 0.000 | 0.235 | 0.000 | 0.000 | -7.011 | 0.000 | -9.461 | -0.553 |
F4 SW APARTMENT | 4.246 | -13.447 | 0.000 | 0.000 | 3.747 | 1.087 | 12.213 | 17.856 | 0.000 | 0.342 | 0.001 | 0.000 | -11.501 | 0.000 | -13.636 | -0.905 |
F4 NW APARTMENT | 6.000 | -8.431 | 0.000 | 0.000 | 3.815 | 1.087 | 12.213 | 9.576 | 0.000 | 0.348 | 0.000 | 0.000 | -11.377 | 0.000 | -13.025 | -0.205 |
F4 SE APARTMENT | 4.160 | -13.054 | 0.000 | 0.000 | 3.757 | 1.087 | 12.213 | 16.988 | 0.000 | 0.342 | 0.000 | 0.000 | -11.253 | 0.000 | -13.625 | -0.614 |
F4 NE APARTMENT | 5.887 | -8.248 | 0.000 | 0.000 | 3.838 | 1.087 | 12.213 | 8.685 | 0.000 | 0.345 | 0.160 | 0.000 | -11.037 | 0.000 | -12.929 | -0.000 |
F4 N1 APARTMENT | 1.826 | -7.932 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 3.177 | 0.000 | 0.256 | 1.794 | 0.000 | -7.034 | 0.000 | -9.210 | -0.000 |
F4 N2 APARTMENT | 1.831 | -7.905 | 0.000 | 0.000 | 3.826 | 1.087 | 12.213 | 3.179 | 0.000 | 0.256 | 1.741 | 0.000 | -7.026 | 0.000 | -9.200 | -0.000 |
F4 S1 APARTMENT | 1.108 | -13.182 | 0.000 | 0.000 | 3.717 | 1.087 | 12.213 | 11.581 | 0.000 | 0.254 | 0.269 | 0.000 | -7.086 | 0.000 | -9.962 | -0.000 |
F4 S2 APARTMENT | 1.110 | -13.157 | 0.000 | 0.000 | 3.718 | 1.087 | 12.213 | 11.580 | 0.000 | 0.254 | 0.243 | 0.000 | -7.084 | 0.000 | -9.963 | -0.000 |
M SW APARTMENT | 4.550 | -13.459 | 0.000 | 0.000 | 3.748 | 1.087 | 12.213 | 17.756 | 0.000 | 0.364 | 0.000 | 0.000 | -11.580 | 0.000 | -14.573 | -0.106 |
M NW APARTMENT | 6.314 | -8.494 | 0.000 | 0.000 | 3.815 | 1.087 | 12.213 | 9.511 | 0.000 | 0.370 | 0.588 | 0.000 | -11.459 | 0.000 | -13.943 | -0.001 |
M SE APARTMENT | 4.481 | -13.038 | 0.000 | 0.000 | 3.759 | 1.087 | 12.213 | 16.898 | 0.000 | 0.365 | 0.119 | 0.000 | -11.326 | 0.000 | -14.555 | -0.000 |
M NE APARTMENT | 6.195 | -8.322 | 0.000 | 0.000 | 3.838 | 1.087 | 12.213 | 8.627 | 0.000 | 0.367 | 0.952 | 0.000 | -11.118 | 0.000 | -13.840 | -0.000 |
M N1 APARTMENT | 1.935 | -8.077 | 0.000 | 0.000 | 3.822 | 1.087 | 12.213 | 3.149 | 0.000 | 0.272 | 2.517 | 0.000 | -7.091 | 0.000 | -9.825 | -0.000 |
M N2 APARTMENT | 1.938 | -8.050 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 3.150 | 0.000 | 0.271 | 2.465 | 0.000 | -7.083 | 0.000 | -9.815 | -0.000 |
M S1 APARTMENT | 1.208 | -13.310 | 0.000 | 0.000 | 3.717 | 1.087 | 12.213 | 11.518 | 0.000 | 0.270 | 1.031 | 0.000 | -7.140 | 0.000 | -10.593 | -0.000 |
M S2 APARTMENT | 1.211 | -13.277 | 0.000 | 0.000 | 3.717 | 1.087 | 12.213 | 11.518 | 0.000 | 0.270 | 0.992 | 0.000 | -7.137 | 0.000 | -10.593 | -0.000 |
F6 SW APARTMENT | 5.175 | -12.695 | 0.000 | 0.000 | 3.758 | 1.087 | 12.213 | 17.711 | 0.000 | 0.384 | 0.000 | 0.000 | -11.574 | 0.000 | -15.306 | -0.752 |
F6 NW APARTMENT | 7.102 | -7.958 | 0.000 | 0.000 | 3.825 | 1.087 | 12.213 | 9.494 | 0.000 | 0.391 | 0.000 | 0.000 | -11.456 | 0.000 | -14.640 | -0.056 |
F6 SE APARTMENT | 5.115 | -12.289 | 0.000 | 0.000 | 3.769 | 1.087 | 12.213 | 16.859 | 0.000 | 0.385 | 0.001 | 0.000 | -11.318 | 0.000 | -15.286 | -0.534 |
F6 NE APARTMENT | 6.988 | -7.811 | 0.000 | 0.000 | 3.848 | 1.087 | 12.213 | 8.618 | 0.000 | 0.386 | 0.315 | 0.000 | -11.114 | 0.000 | -14.530 | -0.000 |
F6 N1 APARTMENT | 2.327 | -7.525 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 3.149 | 0.000 | 0.286 | 1.968 | 0.000 | -7.085 | 0.000 | -10.251 | -0.000 |
F6 N2 APARTMENT | 2.328 | -7.497 | 0.000 | 0.000 | 3.834 | 1.087 | 12.213 | 3.151 | 0.000 | 0.285 | 1.917 | 0.000 | -7.078 | 0.000 | -10.239 | -0.000 |
F6 S1 APARTMENT | 1.465 | -12.542 | 0.000 | 0.000 | 3.728 | 1.087 | 12.213 | 11.490 | 0.000 | 0.284 | 0.470 | 0.000 | -7.134 | 0.000 | -11.060 | -0.000 |
F6 S2 APARTMENT | 1.468 | -12.509 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 11.490 | 0.000 | 0.284 | 0.429 | 0.000 | -7.131 | 0.000 | -11.060 | -0.000 |
F7 SW APARTMENT | 5.699 | -12.205 | 0.000 | 0.000 | 3.766 | 1.087 | 12.213 | 17.666 | 0.000 | 0.400 | 0.001 | 0.000 | -11.580 | 0.000 | -15.950 | -1.095 |
F7 NW APARTMENT | 7.718 | -7.632 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 9.475 | 0.000 | 0.407 | 0.000 | 0.000 | -11.465 | 0.000 | -15.260 | -0.374 |
F7 SE APARTMENT | 5.643 | -11.807 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 16.820 | 0.000 | 0.401 | 0.000 | 0.000 | -11.323 | 0.000 | -15.930 | -0.878 |
F7 NE APARTMENT | 7.601 | -7.495 | 0.000 | 0.000 | 3.855 | 1.087 | 12.213 | 8.605 | 0.000 | 0.402 | 0.000 | 0.000 | -11.123 | 0.000 | -15.143 | -0.001 |
F7 N1 APARTMENT | 2.638 | -7.188 | 0.000 | 0.000 | 3.840 | 1.087 | 12.213 | 3.147 | 0.000 | 0.297 | 1.683 | 0.000 | -7.087 | 0.000 | -10.630 | -0.000 |
F7 N2 APARTMENT | 2.643 | -7.165 | 0.000 | 0.000 | 3.843 | 1.087 | 12.213 | 3.149 | 0.000 | 0.296 | 1.633 | 0.000 | -7.080 | 0.000 | -10.618 | -0.000 |
F7 S1 APARTMENT | 1.689 | -12.040 | 0.000 | 0.000 | 3.737 | 1.087 | 12.213 | 11.464 | 0.000 | 0.295 | 0.161 | 0.000 | -7.135 | 0.000 | -11.469 | -0.000 |
F7 S2 APARTMENT | 1.692 | -12.007 | 0.000 | 0.000 | 3.738 | 1.087 | 12.213 | 11.463 | 0.000 | 0.295 | 0.120 | 0.000 | -7.132 | 0.000 | -11.468 | -0.000 |
F8 SW APARTMENT | 6.222 | -11.796 | 0.000 | 0.000 | 3.773 | 1.087 | 12.213 | 17.628 | 0.000 | 0.419 | 0.000 | 0.000 | -11.585 | 0.000 | -16.557 | -1.403 |
F8 NW APARTMENT | 8.312 | -7.384 | 0.000 | 0.000 | 3.838 | 1.087 | 12.213 | 9.458 | 0.000 | 0.426 | 0.000 | 0.000 | -11.474 | 0.000 | -15.844 | -0.633 |
F8 SE APARTMENT | 6.171 | -11.416 | 0.000 | 0.000 | 3.784 | 1.087 | 12.213 | 16.786 | 0.000 | 0.419 | 0.000 | 0.000 | -11.327 | 0.000 | -16.537 | -1.179 |
F8 NE APARTMENT | 8.200 | -7.256 | 0.000 | 0.000 | 3.861 | 1.087 | 12.213 | 8.593 | 0.000 | 0.421 | 0.000 | 0.000 | -11.133 | 0.000 | -15.724 | -0.262 |
F8 N1 APARTMENT | 2.964 | -6.922 | 0.000 | 0.000 | 3.847 | 1.087 | 12.213 | 3.145 | 0.000 | 0.311 | 1.443 | 0.000 | -7.090 | 0.000 | -10.998 | -0.001 |
F8 N2 APARTMENT | 2.968 | -6.899 | 0.000 | 0.000 | 3.849 | 1.087 | 12.213 | 3.146 | 0.000 | 0.311 | 1.393 | 0.000 | -7.083 | 0.000 | -10.986 | -0.000 |
F8 S1 APARTMENT | 1.925 | -11.603 | 0.000 | 0.000 | 3.746 | 1.087 | 12.213 | 11.441 | 0.000 | 0.309 | 0.000 | 0.000 | -7.134 | 0.000 | -11.862 | -0.121 |
F8 S2 APARTMENT | 1.930 | -11.572 | 0.000 | 0.000 | 3.746 | 1.087 | 12.213 | 11.441 | 0.000 | 0.309 | 0.001 | 0.000 | -7.130 | 0.000 | -11.861 | -0.162 |
F9 SW APARTMENT | 7.174 | -11.350 | 0.000 | 0.000 | 3.782 | 1.087 | 12.213 | 17.615 | 0.000 | 0.436 | 0.001 | 0.000 | -11.556 | 0.000 | -17.073 | -2.328 |
F9 NW APARTMENT | 9.395 | -7.162 | 0.000 | 0.000 | 3.844 | 1.087 | 12.213 | 9.459 | 0.000 | 0.443 | 0.000 | 0.000 | -11.460 | 0.000 | -16.348 | -1.471 |
F9 SE APARTMENT | 7.105 | -10.965 | 0.000 | 0.000 | 3.793 | 1.087 | 12.213 | 16.777 | 0.000 | 0.436 | 0.000 | 0.000 | -11.300 | 0.000 | -17.057 | -2.087 |
F9 NE APARTMENT | 9.259 | -7.042 | 0.000 | 0.000 | 3.867 | 1.087 | 12.213 | 8.598 | 0.000 | 0.440 | 0.000 | 0.000 | -11.121 | 0.000 | -16.230 | -1.071 |
F9 N1 APARTMENT | 3.651 | -6.577 | 0.000 | 0.000 | 3.854 | 1.087 | 12.213 | 3.151 | 0.000 | 0.325 | 0.685 | 0.000 | -7.076 | 0.000 | -11.311 | -0.000 |
F9 N2 APARTMENT | 3.658 | -6.558 | 0.000 | 0.000 | 3.856 | 1.087 | 12.213 | 3.152 | 0.000 | 0.325 | 0.637 | 0.000 | -7.069 | 0.000 | -11.300 | -0.001 |
F9 S1 APARTMENT | 2.410 | -11.002 | 0.000 | 0.000 | 3.757 | 1.087 | 12.213 | 11.436 | 0.000 | 0.322 | 0.000 | 0.000 | -7.109 | 0.000 | -12.183 | -0.931 |
F9 S2 APARTMENT | 2.415 | -10.971 | 0.000 | 0.000 | 3.758 | 1.087 | 12.213 | 11.435 | 0.000 | 0.322 | 0.001 | 0.000 | -7.106 | 0.000 | -12.183 | -0.969 |
T SW APARTMENT | 11.746 | -11.642 | 0.000 | 0.000 | 3.828 | 1.087 | 12.213 | 17.394 | 0.000 | 0.447 | 0.000 | 0.000 | -11.027 | 0.000 | -17.524 | -6.519 |
T NW APARTMENT | 13.654 | -7.534 | 0.000 | 0.000 | 3.878 | 1.087 | 12.213 | 9.275 | 0.000 | 0.455 | 0.000 | 0.000 | -11.002 | 0.000 | -16.861 | -5.163 |
T SE APARTMENT | 11.496 | -11.025 | 0.000 | 0.000 | 3.840 | 1.087 | 12.213 | 16.586 | 0.000 | 0.447 | 0.000 | 0.000 | -10.807 | 0.000 | -17.521 | -6.314 |
T NE APARTMENT | 13.270 | -7.141 | 0.000 | 0.000 | 3.903 | 1.087 | 12.213 | 8.449 | 0.000 | 0.454 | 0.000 | 0.000 | -10.702 | 0.000 | -16.765 | -4.767 |
T N1 APARTMENT | 6.857 | -6.240 | 0.000 | 0.000 | 3.887 | 1.087 | 12.213 | 3.093 | 0.000 | 0.336 | 0.000 | 0.000 | -6.783 | 0.000 | -11.662 | -2.788 |
T N2 APARTMENT | 6.875 | -6.208 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 3.091 | 0.000 | 0.337 | 0.000 | 0.000 | -6.775 | 0.000 | -11.661 | -2.847 |
T S1 APARTMENT | 5.263 | -10.067 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 11.325 | 0.000 | 0.329 | 0.000 | 0.000 | -6.818 | 0.000 | -12.475 | -4.661 |
T S2 APARTMENT | 5.277 | -10.049 | 0.000 | 0.000 | 3.806 | 1.087 | 12.213 | 11.323 | 0.000 | 0.329 | 0.000 | 0.000 | -6.814 | 0.000 | -12.477 | -4.694 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 4.099 | 0.000 | 0.942 | 32.115 | 0.000 | -2.332 | 0.000 | -51.263 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.915 | 0.000 | 0.014 | 0.000 | 0.000 | -1.421 | 0.000 | -1.249 | -15.699 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.872 | 0.000 | 0.016 | 0.000 | 0.000 | -1.481 | 0.000 | -1.527 | -15.320 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.850 | 0.000 | 0.017 | 0.000 | 0.000 | -1.508 | 0.000 | -1.726 | -15.072 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.824 | 0.000 | 0.015 | 0.000 | 0.000 | -1.546 | 0.000 | -1.963 | -31.210 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.834 | 0.000 | 0.020 | 0.000 | 0.000 | -1.519 | 0.000 | -1.999 | -14.776 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.835 | 0.000 | 0.021 | 0.000 | 0.000 | -1.510 | 0.000 | -2.091 | -14.695 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.833 | 0.000 | 0.022 | 0.000 | 0.000 | -1.508 | 0.000 | -2.181 | -14.606 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.833 | 0.000 | 0.022 | 0.000 | 0.000 | -1.503 | 0.000 | -2.256 | -14.536 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.786 | 0.000 | 0.011 | 0.000 | 0.000 | -1.460 | 0.000 | -2.419 | -22.509 |
Total Facility | 356.631 | -765.500 | 0.000 | 0.000 | 301.323 | 296.560 | 982.450 | 848.392 | 0.000 | 25.992 | 60.001 | 0.000 | -740.234 | 0.000 | -1021.809 | -343.797 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 10-SEP-15:30 | 0.00 | -2929.03 | 0.00 | 0.00 | 48.87 | 45.40 | 470.89 | 4041.59 | 0.00 | 124.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1801.72 |
G NW APARTMENT | 24-JUN-18:00 | 0.00 | -2305.68 | 0.00 | 0.00 | 137.68 | 87.56 | 588.62 | 3045.72 | 0.00 | 241.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1795.42 |
OFFICE | 31-AUG-13:30 | 0.00 | -3791.47 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 3343.04 | 0.00 | 34.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2586.21 |
G NE APARTMENT | 04-JUN-09:30 | 0.00 | -1616.72 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2375.07 | 0.00 | 313.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1531.80 |
G N1 APARTMENT | 14-JUL-19:00 | 0.00 | -1018.31 | 0.00 | 0.00 | 139.88 | 103.77 | 547.42 | 548.75 | 0.00 | 156.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.40 |
G N2 APARTMENT | 14-JUL-19:00 | 0.00 | -993.48 | 0.00 | 0.00 | 139.73 | 103.77 | 547.42 | 549.03 | 0.00 | 154.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.12 |
G S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2045.33 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3254.24 | 0.00 | 172.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1823.93 |
G S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2104.89 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3253.08 | 0.00 | 172.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1763.20 |
F2 SW APARTMENT | 09-SEP-15:30 | 0.00 | -3705.48 | 0.00 | 0.00 | 48.87 | 45.40 | 470.89 | 3840.11 | 0.00 | 351.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1051.25 |
F2 NW APARTMENT | 24-JUN-18:00 | 0.00 | -2953.41 | 0.00 | 0.00 | 137.72 | 87.56 | 588.62 | 3000.72 | 0.00 | 345.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1207.14 |
F2 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3367.96 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3454.93 | 0.00 | 313.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -836.38 |
F2 NE APARTMENT | 04-JUN-09:30 | 0.00 | -2200.60 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2327.12 | 0.00 | 397.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -984.16 |
F2 N1 APARTMENT | 14-JUL-19:00 | 0.00 | -1394.67 | 0.00 | 0.00 | 140.13 | 103.77 | 547.42 | 533.76 | 0.00 | 194.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -124.75 |
F2 N2 APARTMENT | 14-JUL-19:00 | 0.00 | -1372.05 | 0.00 | 0.00 | 140.01 | 103.77 | 547.42 | 533.89 | 0.00 | 192.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -145.43 |
F2 S1 APARTMENT | 31-AUG-12:45 | 0.00 | -2619.28 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3230.50 | 0.00 | 189.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1242.66 |
F2 S2 APARTMENT | 31-AUG-12:45 | 0.00 | -2643.66 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3230.12 | 0.00 | 189.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1217.91 |
F3 SW APARTMENT | 09-SEP-15:15 | 0.00 | -3757.95 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3959.68 | 0.00 | 407.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1174.75 |
F3 NW APARTMENT | 23-JUN-18:00 | 0.00 | -3008.71 | 0.00 | 0.00 | 140.39 | 87.56 | 588.62 | 2872.94 | 0.00 | 385.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1066.29 |
F3 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3395.70 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3440.98 | 0.00 | 369.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -851.35 |
F3 NE APARTMENT | 04-JUN-09:30 | 0.00 | -2265.82 | 0.00 | 0.00 | 40.68 | 12.97 | 406.15 | 2305.76 | 0.00 | 440.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -940.47 |
F3 N1 APARTMENT | 22-JUN-16:15 | 0.00 | -1458.93 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 473.68 | 0.00 | 443.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196.83 |
F3 N2 APARTMENT | 22-JUN-16:15 | 0.00 | -1448.70 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 473.90 | 0.00 | 443.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -207.28 |
F3 S1 APARTMENT | 30-AUG-14:00 | 0.00 | -2708.94 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2750.76 | 0.00 | 287.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.47 |
F3 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2720.85 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3173.30 | 0.00 | 254.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1148.75 |
F4 SW APARTMENT | 09-SEP-15:30 | 0.00 | -3792.47 | 0.00 | 0.00 | 48.80 | 45.40 | 470.89 | 3791.51 | 0.00 | 461.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1025.45 |
F4 NW APARTMENT | 23-JUN-17:45 | 0.00 | -3047.02 | 0.00 | 0.00 | 140.49 | 87.56 | 588.62 | 2941.22 | 0.00 | 440.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1151.47 |
F4 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3432.31 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3430.77 | 0.00 | 412.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -847.01 |
F4 NE APARTMENT | 04-JUN-09:30 | 0.00 | -2299.67 | 0.00 | 0.00 | 40.67 | 12.97 | 406.15 | 2292.15 | 0.00 | 477.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -930.18 |
F4 N1 APARTMENT | 22-JUN-16:15 | 0.00 | -1511.84 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 471.57 | 0.00 | 484.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -182.79 |
F4 N2 APARTMENT | 22-JUN-16:15 | 0.00 | -1488.30 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 471.79 | 0.00 | 482.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203.79 |
F4 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2729.86 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3165.26 | 0.00 | 263.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1140.78 |
F4 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2741.57 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3165.02 | 0.00 | 262.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1128.61 |
M SW APARTMENT | 09-SEP-15:30 | 0.00 | -3841.99 | 0.00 | 0.00 | 48.79 | 45.40 | 470.89 | 3775.74 | 0.00 | 499.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -998.70 |
M NW APARTMENT | 23-JUN-17:45 | 0.00 | -3105.78 | 0.00 | 0.00 | 140.53 | 87.56 | 588.62 | 2932.76 | 0.00 | 477.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.39 |
M SE APARTMENT | 09-SEP-13:30 | 0.00 | -3484.67 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3422.09 | 0.00 | 446.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -820.60 |
M NE APARTMENT | 04-JUN-09:30 | 0.00 | -2341.52 | 0.00 | 0.00 | 40.66 | 12.97 | 406.15 | 2281.03 | 0.00 | 506.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -906.20 |
M N1 APARTMENT | 22-JUN-16:15 | 0.00 | -1552.59 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 469.79 | 0.00 | 515.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -170.83 |
M N2 APARTMENT | 22-JUN-15:30 | 0.00 | -1540.25 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 549.27 | 0.00 | 602.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -177.14 |
M S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2768.73 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3158.26 | 0.00 | 270.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1102.41 |
M S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2780.12 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3158.02 | 0.00 | 270.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1090.54 |
F6 SW APARTMENT | 09-SEP-15:15 | 0.00 | -3822.70 | 0.00 | 0.00 | 48.88 | 45.40 | 470.89 | 3919.87 | 0.00 | 524.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1186.89 |
F6 NW APARTMENT | 23-JUN-17:45 | 0.00 | -3088.09 | 0.00 | 0.00 | 140.49 | 87.56 | 588.62 | 2927.25 | 0.00 | 508.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1164.43 |
F6 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3472.61 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3416.45 | 0.00 | 476.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -856.53 |
F6 NE APARTMENT | 04-JUN-09:30 | 0.00 | -2315.32 | 0.00 | 0.00 | 40.65 | 12.97 | 406.15 | 2273.63 | 0.00 | 529.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -947.70 |
F6 N1 APARTMENT | 22-JUN-15:30 | 0.00 | -1528.13 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 549.33 | 0.00 | 634.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -220.93 |
F6 N2 APARTMENT | 22-JUN-15:30 | 0.00 | -1521.02 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 549.47 | 0.00 | 634.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -228.19 |
F6 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2741.60 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3153.30 | 0.00 | 276.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1130.65 |
F6 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2752.94 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3153.06 | 0.00 | 276.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1118.82 |
F7 SW APARTMENT | 09-SEP-15:15 | 0.00 | -3824.75 | 0.00 | 0.00 | 48.86 | 45.40 | 470.89 | 3911.27 | 0.00 | 552.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1204.50 |
F7 NW APARTMENT | 23-JUN-17:45 | 0.00 | -3092.02 | 0.00 | 0.00 | 140.45 | 87.56 | 588.62 | 2922.08 | 0.00 | 535.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1182.42 |
F7 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3478.02 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3411.09 | 0.00 | 502.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.63 |
F7 NE APARTMENT | 04-JUN-09:30 | 0.00 | -2311.34 | 0.00 | 0.00 | 40.65 | 12.97 | 406.15 | 2266.81 | 0.00 | 549.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -964.55 |
F7 N1 APARTMENT | 26-AUG-18:15 | 0.00 | -1530.72 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 200.11 | 0.00 | 478.11 | 59.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 26-AUG-18:15 | 0.00 | -1519.78 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 200.36 | 0.00 | 478.12 | 48.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2736.38 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3148.67 | 0.00 | 282.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1136.58 |
F7 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2747.70 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3148.42 | 0.00 | 281.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1124.73 |
F8 SW APARTMENT | 09-SEP-15:15 | 0.00 | -3835.90 | 0.00 | 0.00 | 48.87 | 45.40 | 470.89 | 3903.83 | 0.00 | 578.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1211.61 |
F8 NW APARTMENT | 23-JUN-18:00 | 0.00 | -3100.44 | 0.00 | 0.00 | 140.26 | 87.56 | 588.62 | 2824.31 | 0.00 | 545.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1085.63 |
F8 SE APARTMENT | 09-SEP-13:30 | 0.00 | -3485.73 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3406.28 | 0.00 | 525.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -882.20 |
F8 NE APARTMENT | 04-JUN-09:45 | 0.00 | -2339.52 | 0.00 | 0.00 | 40.40 | 12.97 | 406.15 | 2147.32 | 0.00 | 685.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -953.27 |
F8 N1 APARTMENT | 04-JUN-09:45 | 0.00 | -1560.58 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 505.17 | 0.00 | 714.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -119.08 |
F8 N2 APARTMENT | 04-JUN-09:45 | 0.00 | -1548.34 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 504.66 | 0.00 | 707.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -124.01 |
F8 S1 APARTMENT | 31-AUG-13:00 | 0.00 | -2741.29 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3144.46 | 0.00 | 287.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1132.51 |
F8 S2 APARTMENT | 31-AUG-13:00 | 0.00 | -2752.64 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3144.21 | 0.00 | 286.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.62 |
F9 SW APARTMENT | 09-SEP-15:30 | 0.00 | -3916.83 | 0.00 | 0.00 | 48.84 | 45.40 | 470.89 | 3737.62 | 0.00 | 613.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -999.09 |
F9 NW APARTMENT | 23-JUN-18:00 | 0.00 | -3191.59 | 0.00 | 0.00 | 140.54 | 87.56 | 588.62 | 2817.25 | 0.00 | 569.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1011.53 |
F9 SE APARTMENT | 09-SEP-13:45 | 0.00 | -3512.95 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3274.85 | 0.00 | 556.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -754.81 |
F9 NE APARTMENT | 04-JUN-09:45 | 0.00 | -2451.10 | 0.00 | 0.00 | 40.65 | 12.97 | 406.15 | 2144.84 | 0.00 | 747.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -901.39 |
F9 N1 APARTMENT | 24-JUN-21:00 | 0.00 | -1599.31 | 0.00 | 0.00 | 161.10 | 71.34 | 500.33 | 0.00 | 0.00 | 240.22 | 665.16 | 0.00 | -38.84 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 04-JUN-09:45 | 0.00 | -1597.55 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 504.77 | 0.00 | 741.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -108.28 |
F9 S1 APARTMENT | 31-AUG-13:15 | 0.00 | -2800.01 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3052.71 | 0.00 | 337.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.40 |
F9 S2 APARTMENT | 31-AUG-13:15 | 0.00 | -2812.54 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3052.44 | 0.00 | 337.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1013.31 |
T SW APARTMENT | 17-JUL-16:15 | 0.00 | -4665.95 | 0.00 | 0.00 | 84.57 | 64.86 | 588.62 | 3212.03 | 0.00 | 652.51 | 63.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 15-JUL-17:20 | 0.00 | -3900.13 | 0.00 | 0.00 | 136.97 | 87.56 | 588.62 | 2937.02 | 0.00 | 576.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -426.28 |
T SE APARTMENT | 09-SEP-13:15 | 0.00 | -4179.44 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3441.35 | 0.00 | 554.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.91 |
T NE APARTMENT | 04-JUN-09:45 | 0.00 | -3061.16 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2109.57 | 0.00 | 817.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.42 |
T N1 APARTMENT | 24-JUN-19:15 | 0.00 | -2258.68 | 0.00 | 0.00 | 139.48 | 103.77 | 523.87 | 861.81 | 0.00 | 200.20 | 429.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 24-JUN-19:15 | 0.00 | -2251.70 | 0.00 | 0.00 | 140.19 | 103.77 | 523.87 | 864.11 | 0.00 | 202.36 | 417.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 10-SEP-13:15 | 0.00 | -3621.65 | 0.00 | 0.00 | 40.74 | 12.97 | 382.60 | 3146.64 | 0.00 | 128.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.90 |
T S2 APARTMENT | 10-SEP-13:15 | 0.00 | -3634.08 | 0.00 | 0.00 | 40.73 | 12.97 | 382.60 | 3146.33 | 0.00 | 128.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.12 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-SEP-15:15 | 0.00 | -193305.33 | 0.00 | 0.00 | 3862.72 | 9790.07 | 37759.52 | 151166.26 | 0.00 | 32891.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42164.44 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 15-FEB-02:00 | 1911.89 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.99 | 0.00 | -1225.66 | -231.72 |
G NW APARTMENT | 15-FEB-02:00 | 1936.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.46 | 0.00 | -1225.66 | -273.36 |
OFFICE | 15-FEB-02:00 | 1699.49 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -900.09 | 0.00 | -1225.66 | -237.16 |
G NE APARTMENT | 15-FEB-02:00 | 1940.23 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.33 | 0.00 | -1225.66 | -276.72 |
G N1 APARTMENT | 23-MAR-14:55 | 1386.83 | 0.00 | 0.00 | 0.00 | 46.91 | 22.70 | 400.26 | 379.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1515.62 | -720.78 |
G N2 APARTMENT | 23-MAR-14:55 | 1369.18 | 0.00 | 0.00 | 0.00 | 46.96 | 22.70 | 400.26 | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1515.54 | -703.89 |
G S1 APARTMENT | 09-NOV-10:55 | 1429.21 | 0.00 | 0.00 | 0.00 | 45.67 | 12.97 | 406.15 | 682.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1550.36 | -1025.74 |
G S2 APARTMENT | 26-OCT-13:00 | 1444.76 | 0.00 | 0.00 | 0.00 | 44.23 | 12.97 | 388.49 | 155.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1548.08 | -498.13 |
F2 SW APARTMENT | 15-FEB-02:00 | 2288.59 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.96 | 0.00 | -1763.03 | -29.09 |
F2 NW APARTMENT | 15-FEB-02:00 | 2379.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -910.67 | 0.00 | -1763.03 | -143.17 |
F2 SE APARTMENT | 15-FEB-02:00 | 2198.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 64.80 | 0.00 | -938.22 | 0.00 | -1763.03 | 0.00 |
F2 NE APARTMENT | 15-FEB-02:00 | 2384.56 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -910.47 | 0.00 | -1763.03 | -148.56 |
F2 N1 APARTMENT | 23-MAR-14:55 | 1696.71 | 0.00 | 0.00 | 0.00 | 44.98 | 22.70 | 400.26 | 340.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1954.24 | -550.90 |
F2 N2 APARTMENT | 23-MAR-14:55 | 1788.70 | 0.00 | 0.00 | 0.00 | 45.09 | 22.70 | 400.26 | 341.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1951.58 | -646.89 |
F2 S1 APARTMENT | 26-OCT-08:00 | 2132.79 | 0.00 | 0.00 | 0.00 | 65.59 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -130.60 | 0.00 | -2109.62 | -366.10 |
F2 S2 APARTMENT | 26-OCT-08:00 | 2114.63 | 0.00 | 0.00 | 0.00 | 65.40 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -131.89 | 0.00 | -2111.12 | -344.96 |
F3 SW APARTMENT | 15-FEB-02:00 | 2531.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 70.74 | 0.00 | -951.00 | 0.00 | -2088.86 | 0.00 |
F3 NW APARTMENT | 15-FEB-02:00 | 2632.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -924.97 | 0.00 | -2088.86 | -56.19 |
F3 SE APARTMENT | 15-FEB-02:00 | 2521.06 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 81.85 | 0.00 | -951.54 | 0.00 | -2088.86 | 0.00 |
F3 NE APARTMENT | 15-FEB-02:00 | 2637.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -924.74 | 0.00 | -2088.86 | -61.74 |
F3 N1 APARTMENT | 26-FEB-11:55 | 1760.27 | 0.00 | 0.00 | 0.00 | 46.19 | 12.97 | 412.03 | 198.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1617.13 | -813.06 |
F3 N2 APARTMENT | 26-FEB-11:55 | 1756.88 | 0.00 | 0.00 | 0.00 | 46.17 | 12.97 | 412.03 | 198.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1617.10 | -809.36 |
F3 S1 APARTMENT | 26-OCT-08:00 | 2325.01 | 0.00 | 0.00 | 0.00 | 64.69 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -145.13 | 0.00 | -2424.26 | -228.25 |
F3 S2 APARTMENT | 26-OCT-08:00 | 2323.29 | 0.00 | 0.00 | 0.00 | 64.65 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -145.32 | 0.00 | -2424.37 | -226.20 |
F4 SW APARTMENT | 15-FEB-02:00 | 2764.11 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 95.38 | 0.00 | -960.46 | 0.00 | -2336.52 | 0.00 |
F4 NW APARTMENT | 15-FEB-02:00 | 2865.54 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.13 | 0.00 | -2336.52 | -33.38 |
F4 SE APARTMENT | 15-FEB-02:00 | 2767.96 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 91.35 | 0.00 | -960.28 | 0.00 | -2336.52 | 0.00 |
F4 NE APARTMENT | 15-FEB-02:00 | 2870.89 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -932.90 | 0.00 | -2336.52 | -38.95 |
F4 N1 APARTMENT | 25-FEB-13:25 | 1787.66 | 0.00 | 0.00 | 0.00 | 45.99 | 12.97 | 388.49 | 302.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1574.08 | -964.02 |
F4 N2 APARTMENT | 25-FEB-13:25 | 1769.42 | 0.00 | 0.00 | 0.00 | 46.04 | 12.97 | 388.49 | 303.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1573.94 | -946.62 |
F4 S1 APARTMENT | 15-FEB-02:00 | 1434.47 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 127.51 | 0.00 | -590.14 | 0.00 | -1409.33 | 0.00 |
F4 S2 APARTMENT | 15-FEB-02:00 | 1434.44 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 127.54 | 0.00 | -590.14 | 0.00 | -1409.33 | 0.00 |
M SW APARTMENT | 15-FEB-02:00 | 2953.08 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 118.40 | 0.00 | -967.84 | 0.00 | -2541.12 | 0.00 |
M NW APARTMENT | 15-FEB-02:00 | 3050.50 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -939.74 | 0.00 | -2541.12 | -7.12 |
M SE APARTMENT | 15-FEB-02:00 | 2959.17 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 112.01 | 0.00 | -967.55 | 0.00 | -2541.12 | 0.00 |
M NE APARTMENT | 15-FEB-02:00 | 3055.85 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -939.51 | 0.00 | -2541.13 | -12.70 |
M N1 APARTMENT | 27-FEB-11:25 | 1861.22 | 0.00 | 0.00 | 0.00 | 45.91 | 12.97 | 412.03 | 189.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1646.79 | -874.99 |
M N2 APARTMENT | 25-FEB-13:25 | 1836.90 | 0.00 | 0.00 | 0.00 | 46.00 | 12.97 | 388.49 | 299.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1668.84 | -914.76 |
M S1 APARTMENT | 15-FEB-02:00 | 1545.41 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 144.68 | 0.00 | -594.85 | 0.00 | -1532.74 | 0.00 |
M S2 APARTMENT | 15-FEB-02:00 | 1545.65 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 144.44 | 0.00 | -594.83 | 0.00 | -1532.74 | 0.00 |
F6 SW APARTMENT | 15-FEB-02:00 | 3166.79 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 84.89 | 0.00 | -971.33 | 0.00 | -2717.84 | 0.00 |
F6 NW APARTMENT | 15-FEB-02:00 | 3261.02 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -942.99 | 0.00 | -2717.84 | -37.69 |
F6 SE APARTMENT | 15-FEB-02:00 | 3173.21 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 78.15 | 0.00 | -971.02 | 0.00 | -2717.84 | 0.00 |
F6 NE APARTMENT | 15-FEB-02:00 | 3266.45 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -942.75 | 0.00 | -2717.84 | -43.34 |
F6 N1 APARTMENT | 25-FEB-13:25 | 1831.43 | 0.00 | 0.00 | 0.00 | 46.19 | 12.97 | 388.49 | 298.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1753.23 | -823.97 |
F6 N2 APARTMENT | 25-OCT-11:10 | 1870.57 | 0.00 | 0.00 | 0.00 | 45.60 | 12.97 | 406.15 | 317.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1847.90 | -804.88 |
F6 S1 APARTMENT | 15-FEB-02:00 | 1676.55 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 122.10 | 0.00 | -596.81 | 0.00 | -1639.33 | 0.00 |
F6 S2 APARTMENT | 15-FEB-02:00 | 1676.84 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 121.80 | 0.00 | -596.80 | 0.00 | -1639.33 | 0.00 |
F7 SW APARTMENT | 15-FEB-02:00 | 3345.58 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 66.44 | 0.00 | -974.75 | 0.00 | -2874.76 | 0.00 |
F7 NW APARTMENT | 15-FEB-02:00 | 3435.10 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -946.25 | 0.00 | -2874.76 | -51.58 |
F7 SE APARTMENT | 15-FEB-02:00 | 3351.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 59.87 | 0.00 | -974.46 | 0.00 | -2874.76 | 0.00 |
F7 NE APARTMENT | 15-FEB-02:00 | 3440.59 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -946.01 | 0.00 | -2874.77 | -57.30 |
F7 N1 APARTMENT | 25-OCT-11:10 | 2107.47 | 0.00 | 0.00 | 0.00 | 45.73 | 12.97 | 406.15 | 316.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1926.16 | -962.73 |
F7 N2 APARTMENT | 25-OCT-11:10 | 2127.07 | 0.00 | 0.00 | 0.00 | 45.79 | 12.97 | 406.15 | 317.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1925.21 | -984.02 |
F7 S1 APARTMENT | 15-FEB-02:00 | 1788.79 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 106.47 | 0.00 | -598.76 | 0.00 | -1733.98 | 0.00 |
F7 S2 APARTMENT | 15-FEB-02:00 | 1789.11 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 106.13 | 0.00 | -598.75 | 0.00 | -1733.98 | 0.00 |
F8 SW APARTMENT | 15-FEB-02:00 | 3513.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 42.78 | 0.00 | -977.46 | 0.00 | -3016.80 | 0.00 |
F8 NW APARTMENT | 15-FEB-02:00 | 3597.47 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -948.92 | 0.00 | -3016.80 | -69.23 |
F8 SE APARTMENT | 15-FEB-02:00 | 3520.08 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 36.41 | 0.00 | -977.17 | 0.00 | -3016.80 | 0.00 |
F8 NE APARTMENT | 15-FEB-02:00 | 3603.03 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -948.68 | 0.00 | -3016.81 | -75.03 |
F8 N1 APARTMENT | 25-OCT-11:10 | 2161.95 | 0.00 | 0.00 | 0.00 | 45.89 | 12.97 | 406.15 | 316.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2001.66 | -941.79 |
F8 N2 APARTMENT | 25-OCT-11:10 | 2144.59 | 0.00 | 0.00 | 0.00 | 45.95 | 12.97 | 406.15 | 317.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2001.54 | -925.19 |
F8 S1 APARTMENT | 15-FEB-02:00 | 1898.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 83.33 | 0.00 | -600.15 | 0.00 | -1819.66 | 0.00 |
F8 S2 APARTMENT | 15-FEB-02:00 | 1899.30 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 83.01 | 0.00 | -600.14 | 0.00 | -1819.66 | 0.00 |
F9 SW APARTMENT | 15-FEB-02:00 | 3748.25 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -976.60 | 0.00 | -3147.18 | -61.96 |
F9 NW APARTMENT | 15-FEB-02:00 | 3815.43 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -948.63 | 0.00 | -3147.18 | -157.11 |
F9 SE APARTMENT | 15-FEB-02:00 | 3754.17 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -976.34 | 0.00 | -3147.18 | -68.14 |
F9 NE APARTMENT | 15-FEB-02:00 | 3821.04 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -948.40 | 0.00 | -3147.19 | -162.94 |
F9 N1 APARTMENT | 15-FEB-02:00 | 2167.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.09 | 0.00 | -1898.31 | -134.63 |
F9 N2 APARTMENT | 15-FEB-02:00 | 2167.93 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -572.08 | 0.00 | -1898.31 | -135.03 |
F9 S1 APARTMENT | 12-DEC-14:10 | 2083.51 | 0.00 | 0.00 | 0.00 | 45.06 | 12.97 | 382.60 | 1483.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2242.52 | -1765.34 |
F9 S2 APARTMENT | 12-DEC-14:10 | 2098.33 | 0.00 | 0.00 | 0.00 | 45.06 | 12.97 | 382.60 | 1483.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2242.44 | -1780.29 |
T SW APARTMENT | 15-FEB-02:00 | 4291.24 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -953.91 | 0.00 | -3267.87 | -506.94 |
T NW APARTMENT | 15-FEB-02:00 | 4309.97 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -927.38 | 0.00 | -3267.87 | -552.21 |
T SE APARTMENT | 15-FEB-02:00 | 4293.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -953.77 | 0.00 | -3267.87 | -509.82 |
T NE APARTMENT | 15-FEB-02:00 | 4312.59 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -927.26 | 0.00 | -3267.88 | -554.95 |
T N1 APARTMENT | 15-FEB-02:00 | 2627.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -557.26 | 0.00 | -1971.17 | -536.68 |
T N2 APARTMENT | 15-FEB-02:00 | 2627.85 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -557.25 | 0.00 | -1971.17 | -536.92 |
T S1 APARTMENT | 15-FEB-02:00 | 2596.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -585.41 | 0.00 | -1971.17 | -477.29 |
T S2 APARTMENT | 15-FEB-02:00 | 2596.57 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -585.40 | 0.00 | -1971.17 | -477.48 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-FEB-02:00 | 191659.60 | 0.00 | 0.00 | 0.00 | 14983.97 | 6715.87 | 19318.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61989.75 | 0.00 | -164296.27 | -6392.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Sec1.1A-General InformationData | |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 155.00 |
Number of hours cooling loads not met | 86.75 |
Number of hours not met | 241.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 13120.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 143.57 | 0.00 | 483.12 | 179384.52 | 0.00 | 0.00 |
Space Cooling | 235.55 | 67773.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 61.04 | 1959.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 9.60 | 2573.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 662.42 | 21005.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1149.45 | 78981.47 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 57042.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2745.02 | 1632.57 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 2745.02 |
Natural Gas | 0.00 | 1632.57 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4377.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 18.32 |
Space Cooling | 30.06 |
Fans-Interior | 84.53 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 34.40 |
Subtotal | 350.29 |
Natural Gas [MJ/m2] | |
Space Heating | 61.65 |
Service Water Heating | 146.68 |
Miscellaneous | -0.00 |
Subtotal | 208.33 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.77 |
Space Heating | 14.32 |
Space Cooling | 5.38 |
Fans-Interior | 15.13 |
Service Water Heating | 26.26 |
Receptacle Equipment | 25.98 |
Miscellaneous | 6.16 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.252777 |
G NW APARTMENT DIRECT AIR | 0.194152 |
OFFICE DIRECT AIR | 0.369901 |
G NE APARTMENT DIRECT AIR | 0.133081 |
G N1 APARTMENT DIRECT AIR | 0.085085 |
G N2 APARTMENT DIRECT AIR | 0.082757 |
G S1 APARTMENT DIRECT AIR | 0.173383 |
G S2 APARTMENT DIRECT AIR | 0.179946 |
F2 SW APARTMENT DIRECT AIR | 0.320601 |
F2 NW APARTMENT DIRECT AIR | 0.249230 |
F2 SE APARTMENT DIRECT AIR | 0.316525 |
F2 NE APARTMENT DIRECT AIR | 0.180108 |
F2 N1 APARTMENT DIRECT AIR | 0.117439 |
F2 N2 APARTMENT DIRECT AIR | 0.115348 |
F2 S1 APARTMENT DIRECT AIR | 0.224299 |
F2 S2 APARTMENT DIRECT AIR | 0.226702 |
F3 SW APARTMENT DIRECT AIR | 0.324021 |
F3 NW APARTMENT DIRECT AIR | 0.253134 |
F3 SE APARTMENT DIRECT AIR | 0.299212 |
F3 NE APARTMENT DIRECT AIR | 0.183989 |
F3 N1 APARTMENT DIRECT AIR | 0.121699 |
F3 N2 APARTMENT DIRECT AIR | 0.119602 |
F3 S1 APARTMENT DIRECT AIR | 0.228575 |
F3 S2 APARTMENT DIRECT AIR | 0.229704 |
F4 SW APARTMENT DIRECT AIR | 0.326274 |
F4 NW APARTMENT DIRECT AIR | 0.255260 |
F4 SE APARTMENT DIRECT AIR | 0.299576 |
F4 NE APARTMENT DIRECT AIR | 0.185258 |
F4 N1 APARTMENT DIRECT AIR | 0.123609 |
F4 N2 APARTMENT DIRECT AIR | 0.121510 |
F4 S1 APARTMENT DIRECT AIR | 0.230553 |
F4 S2 APARTMENT DIRECT AIR | 0.231499 |
M SW APARTMENT DIRECT AIR | 0.330052 |
M NW APARTMENT DIRECT AIR | 0.258978 |
M SE APARTMENT DIRECT AIR | 0.303240 |
M NE APARTMENT DIRECT AIR | 0.188225 |
M N1 APARTMENT DIRECT AIR | 0.126887 |
M N2 APARTMENT DIRECT AIR | 0.124786 |
M S1 APARTMENT DIRECT AIR | 0.234010 |
M S2 APARTMENT DIRECT AIR | 0.234925 |
F6 SW APARTMENT DIRECT AIR | 0.327971 |
F6 NW APARTMENT DIRECT AIR | 0.256787 |
F6 SE APARTMENT DIRECT AIR | 0.301298 |
F6 NE APARTMENT DIRECT AIR | 0.185565 |
F6 N1 APARTMENT DIRECT AIR | 0.124669 |
F6 N2 APARTMENT DIRECT AIR | 0.122581 |
F6 S1 APARTMENT DIRECT AIR | 0.231712 |
F6 S2 APARTMENT DIRECT AIR | 0.232623 |
F7 SW APARTMENT DIRECT AIR | 0.327830 |
F7 NW APARTMENT DIRECT AIR | 0.256568 |
F7 SE APARTMENT DIRECT AIR | 0.301272 |
F7 NE APARTMENT DIRECT AIR | 0.184887 |
F7 N1 APARTMENT DIRECT AIR | 0.124316 |
F7 N2 APARTMENT DIRECT AIR | 0.122271 |
F7 S1 APARTMENT DIRECT AIR | 0.231349 |
F7 S2 APARTMENT DIRECT AIR | 0.232256 |
F8 SW APARTMENT DIRECT AIR | 0.328639 |
F8 NW APARTMENT DIRECT AIR | 0.257361 |
F8 SE APARTMENT DIRECT AIR | 0.302165 |
F8 NE APARTMENT DIRECT AIR | 0.185199 |
F8 N1 APARTMENT DIRECT AIR | 0.125006 |
F8 N2 APARTMENT DIRECT AIR | 0.123023 |
F8 S1 APARTMENT DIRECT AIR | 0.231961 |
F8 S2 APARTMENT DIRECT AIR | 0.232869 |
F9 SW APARTMENT DIRECT AIR | 0.336210 |
F9 NW APARTMENT DIRECT AIR | 0.265354 |
F9 SE APARTMENT DIRECT AIR | 0.308412 |
F9 NE APARTMENT DIRECT AIR | 0.189087 |
F9 N1 APARTMENT DIRECT AIR | 0.131998 |
F9 N2 APARTMENT DIRECT AIR | 0.130000 |
F9 S1 APARTMENT DIRECT AIR | 0.237087 |
F9 S2 APARTMENT DIRECT AIR | 0.238110 |
T SW APARTMENT DIRECT AIR | 0.411393 |
T NW APARTMENT DIRECT AIR | 0.327253 |
T SE APARTMENT DIRECT AIR | 0.375254 |
T NE APARTMENT DIRECT AIR | 0.242352 |
T N1 APARTMENT DIRECT AIR | 0.183666 |
T N2 APARTMENT DIRECT AIR | 0.183462 |
T S1 APARTMENT DIRECT AIR | 0.314125 |
T S2 APARTMENT DIRECT AIR | 0.315091 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.252777 |
AIRLOOP G NW MAIN BRANCH | 0.194152 |
AIRLOOP OFFICE MAIN BRANCH | 0.369901 |
AIRLOOP G NE MAIN BRANCH | 0.133081 |
AIRLOOP G N1 MAIN BRANCH | 0.085085 |
AIRLOOP G N2 MAIN BRANCH | 0.082757 |
AIRLOOP G S1 MAIN BRANCH | 0.173383 |
AIRLOOP G S2 MAIN BRANCH | 0.179946 |
AIRLOOP F2 SW MAIN BRANCH | 0.320601 |
AIRLOOP F2 NW MAIN BRANCH | 0.249230 |
AIRLOOP F2 SE MAIN BRANCH | 0.316525 |
AIRLOOP F2 NE MAIN BRANCH | 0.180108 |
AIRLOOP F2 N1 MAIN BRANCH | 0.117439 |
AIRLOOP F2 N2 MAIN BRANCH | 0.115348 |
AIRLOOP F2 S1 MAIN BRANCH | 0.224299 |
AIRLOOP F2 S2 MAIN BRANCH | 0.226702 |
AIRLOOP F3 SW MAIN BRANCH | 0.324021 |
AIRLOOP F3 NW MAIN BRANCH | 0.253134 |
AIRLOOP F3 SE MAIN BRANCH | 0.299212 |
AIRLOOP F3 NE MAIN BRANCH | 0.183989 |
AIRLOOP F3 N1 MAIN BRANCH | 0.121699 |
AIRLOOP F3 N2 MAIN BRANCH | 0.119602 |
AIRLOOP F3 S1 MAIN BRANCH | 0.228575 |
AIRLOOP F3 S2 MAIN BRANCH | 0.229704 |
AIRLOOP F4 SW MAIN BRANCH | 0.326274 |
AIRLOOP F4 NW MAIN BRANCH | 0.255260 |
AIRLOOP F4 SE MAIN BRANCH | 0.299576 |
AIRLOOP F4 NE MAIN BRANCH | 0.185258 |
AIRLOOP F4 N1 MAIN BRANCH | 0.123609 |
AIRLOOP F4 N2 MAIN BRANCH | 0.121510 |
AIRLOOP F4 S1 MAIN BRANCH | 0.230553 |
AIRLOOP F4 S2 MAIN BRANCH | 0.231499 |
AIRLOOP M SW MAIN BRANCH | 0.330052 |
AIRLOOP M NW MAIN BRANCH | 0.258978 |
AIRLOOP M SE MAIN BRANCH | 0.303240 |
AIRLOOP M NE MAIN BRANCH | 0.188225 |
AIRLOOP M N1 MAIN BRANCH | 0.126887 |
AIRLOOP M N2 MAIN BRANCH | 0.124786 |
AIRLOOP M S1 MAIN BRANCH | 0.234010 |
AIRLOOP M S2 MAIN BRANCH | 0.234925 |
AIRLOOP F6 SW MAIN BRANCH | 0.327971 |
AIRLOOP F6 NW MAIN BRANCH | 0.256787 |
AIRLOOP F6 SE MAIN BRANCH | 0.301298 |
AIRLOOP F6 NE MAIN BRANCH | 0.185565 |
AIRLOOP F6 N1 MAIN BRANCH | 0.124669 |
AIRLOOP F6 N2 MAIN BRANCH | 0.122581 |
AIRLOOP F6 S1 MAIN BRANCH | 0.231712 |
AIRLOOP F6 S2 MAIN BRANCH | 0.232623 |
AIRLOOP F7 SW MAIN BRANCH | 0.327830 |
AIRLOOP F7 NW MAIN BRANCH | 0.256568 |
AIRLOOP F7 SE MAIN BRANCH | 0.301272 |
AIRLOOP F7 NE MAIN BRANCH | 0.184887 |
AIRLOOP F7 N1 MAIN BRANCH | 0.124316 |
AIRLOOP F7 N2 MAIN BRANCH | 0.122271 |
AIRLOOP F7 S1 MAIN BRANCH | 0.231349 |
AIRLOOP F7 S2 MAIN BRANCH | 0.232256 |
AIRLOOP F8 SW MAIN BRANCH | 0.328639 |
AIRLOOP F8 NW MAIN BRANCH | 0.257361 |
AIRLOOP F8 SE MAIN BRANCH | 0.302165 |
AIRLOOP F8 NE MAIN BRANCH | 0.185199 |
AIRLOOP F8 N1 MAIN BRANCH | 0.125006 |
AIRLOOP F8 N2 MAIN BRANCH | 0.123023 |
AIRLOOP F8 S1 MAIN BRANCH | 0.231961 |
AIRLOOP F8 S2 MAIN BRANCH | 0.232869 |
AIRLOOP F9 SW MAIN BRANCH | 0.336210 |
AIRLOOP F9 NW MAIN BRANCH | 0.265354 |
AIRLOOP F9 SE MAIN BRANCH | 0.308412 |
AIRLOOP F9 NE MAIN BRANCH | 0.189087 |
AIRLOOP F9 N1 MAIN BRANCH | 0.131998 |
AIRLOOP F9 N2 MAIN BRANCH | 0.130000 |
AIRLOOP F9 S1 MAIN BRANCH | 0.237087 |
AIRLOOP F9 S2 MAIN BRANCH | 0.238110 |
AIRLOOP T SW MAIN BRANCH | 0.411393 |
AIRLOOP T NW MAIN BRANCH | 0.327253 |
AIRLOOP T SE MAIN BRANCH | 0.375254 |
AIRLOOP T NE MAIN BRANCH | 0.242352 |
AIRLOOP T N1 MAIN BRANCH | 0.183666 |
AIRLOOP T N2 MAIN BRANCH | 0.183462 |
AIRLOOP T S1 MAIN BRANCH | 0.314125 |
AIRLOOP T S2 MAIN BRANCH | 0.315091 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.252777 |
AIRLOOP G NW | 0.194152 |
AIRLOOP OFFICE | 0.369901 |
AIRLOOP G NE | 0.133081 |
AIRLOOP G N1 | 0.085085 |
AIRLOOP G N2 | 0.082757 |
AIRLOOP G S1 | 0.173383 |
AIRLOOP G S2 | 0.179946 |
AIRLOOP F2 SW | 0.320601 |
AIRLOOP F2 NW | 0.249230 |
AIRLOOP F2 SE | 0.316525 |
AIRLOOP F2 NE | 0.180108 |
AIRLOOP F2 N1 | 0.117439 |
AIRLOOP F2 N2 | 0.115348 |
AIRLOOP F2 S1 | 0.224299 |
AIRLOOP F2 S2 | 0.226702 |
AIRLOOP F3 SW | 0.324021 |
AIRLOOP F3 NW | 0.253134 |
AIRLOOP F3 SE | 0.299212 |
AIRLOOP F3 NE | 0.183989 |
AIRLOOP F3 N1 | 0.121699 |
AIRLOOP F3 N2 | 0.119602 |
AIRLOOP F3 S1 | 0.228575 |
AIRLOOP F3 S2 | 0.229704 |
AIRLOOP F4 SW | 0.326274 |
AIRLOOP F4 NW | 0.255260 |
AIRLOOP F4 SE | 0.299576 |
AIRLOOP F4 NE | 0.185258 |
AIRLOOP F4 N1 | 0.123609 |
AIRLOOP F4 N2 | 0.121510 |
AIRLOOP F4 S1 | 0.230553 |
AIRLOOP F4 S2 | 0.231499 |
AIRLOOP M SW | 0.330052 |
AIRLOOP M NW | 0.258978 |
AIRLOOP M SE | 0.303240 |
AIRLOOP M NE | 0.188225 |
AIRLOOP M N1 | 0.126887 |
AIRLOOP M N2 | 0.124786 |
AIRLOOP M S1 | 0.234010 |
AIRLOOP M S2 | 0.234925 |
AIRLOOP F6 SW | 0.327971 |
AIRLOOP F6 NW | 0.256787 |
AIRLOOP F6 SE | 0.301298 |
AIRLOOP F6 NE | 0.185565 |
AIRLOOP F6 N1 | 0.124669 |
AIRLOOP F6 N2 | 0.122581 |
AIRLOOP F6 S1 | 0.231712 |
AIRLOOP F6 S2 | 0.232623 |
AIRLOOP F7 SW | 0.327830 |
AIRLOOP F7 NW | 0.256568 |
AIRLOOP F7 SE | 0.301272 |
AIRLOOP F7 NE | 0.184887 |
AIRLOOP F7 N1 | 0.124316 |
AIRLOOP F7 N2 | 0.122271 |
AIRLOOP F7 S1 | 0.231349 |
AIRLOOP F7 S2 | 0.232256 |
AIRLOOP F8 SW | 0.328639 |
AIRLOOP F8 NW | 0.257361 |
AIRLOOP F8 SE | 0.302165 |
AIRLOOP F8 NE | 0.185199 |
AIRLOOP F8 N1 | 0.125006 |
AIRLOOP F8 N2 | 0.123023 |
AIRLOOP F8 S1 | 0.231961 |
AIRLOOP F8 S2 | 0.232869 |
AIRLOOP F9 SW | 0.336210 |
AIRLOOP F9 NW | 0.265354 |
AIRLOOP F9 SE | 0.308412 |
AIRLOOP F9 NE | 0.189087 |
AIRLOOP F9 N1 | 0.131998 |
AIRLOOP F9 N2 | 0.130000 |
AIRLOOP F9 S1 | 0.237087 |
AIRLOOP F9 S2 | 0.238110 |
AIRLOOP T SW | 0.411393 |
AIRLOOP T NW | 0.327253 |
AIRLOOP T SE | 0.375254 |
AIRLOOP T NE | 0.242352 |
AIRLOOP T N1 | 0.183666 |
AIRLOOP T N2 | 0.183462 |
AIRLOOP T S1 | 0.314125 |
AIRLOOP T S2 | 0.315091 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.252777 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.194152 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.369901 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.133081 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.085085 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.082757 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.173383 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.179946 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.320601 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.249230 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.316525 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.180108 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.117439 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.115348 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.224299 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.226702 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.324021 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.253134 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.299212 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.183989 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.121699 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.119602 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.228575 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.229704 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.326274 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.255260 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.299576 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.185258 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.123609 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.121510 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.230553 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.231499 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.330052 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.258978 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.303240 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.188225 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.126887 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.124786 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.234010 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.234925 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.327971 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.256787 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.301298 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.185565 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.124669 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.122581 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.231712 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.232623 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.327830 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.256568 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.301272 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.184887 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.124316 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.122271 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.231349 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.232256 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.328639 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.257361 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.302165 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.185199 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.125006 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.123023 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.231961 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.232869 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.336210 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.265354 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.308412 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.189087 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.131998 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.130000 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.237087 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.238110 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.411393 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.327253 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.375254 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.242352 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.183666 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.183462 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.314125 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.315091 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.252777 | 3842.70 | 2880.51 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.194152 | 2958.00 | 2210.06 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.369901 | 5610.84 | 4216.33 | 0.000123 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.133081 | 2057.38 | 1525.06 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.085085 | 1364.06 | 992.65 | 0.000030 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.082757 | 1330.50 | 967.03 | 0.000029 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.173383 | 2739.68 | 2020.41 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.179946 | 2831.51 | 2091.98 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.320601 | 4798.55 | 3620.45 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.249230 | 3737.58 | 2811.66 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.316525 | 4756.20 | 3582.98 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.180108 | 2718.42 | 2037.52 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.117439 | 1827.42 | 1347.69 | 0.000040 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.115348 | 1797.53 | 1324.77 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.224299 | 3462.18 | 2579.09 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.226702 | 3495.78 | 2605.27 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.324021 | 4850.94 | 3658.87 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.253134 | 3796.43 | 2855.25 | 0.000083 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.299212 | 4518.65 | 3395.82 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.183989 | 2776.34 | 2080.71 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.121699 | 1889.62 | 1394.74 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.119602 | 1859.66 | 1371.75 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.228575 | 3524.66 | 2626.38 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.229704 | 3540.44 | 2638.67 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.326274 | 4885.85 | 3684.28 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.255260 | 3829.31 | 2879.22 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.299576 | 4527.09 | 3400.67 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.185258 | 2812.66 | 2102.94 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.123609 | 1918.03 | 1415.97 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.121510 | 1888.04 | 1392.97 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.230553 | 3554.33 | 2648.46 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.231499 | 3567.55 | 2658.75 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.330052 | 4941.44 | 3726.11 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.258978 | 3892.61 | 2925.00 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.303240 | 4581.05 | 3441.26 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.188225 | 2856.48 | 2135.83 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.126887 | 1965.64 | 1452.11 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.124786 | 1935.64 | 1429.09 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.234010 | 3604.33 | 2686.55 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.234925 | 3617.14 | 2696.52 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.327971 | 4914.69 | 3704.10 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.256787 | 3863.98 | 2901.70 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.301298 | 4556.18 | 3420.75 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.185565 | 2821.07 | 2107.38 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.124669 | 1935.01 | 1428.09 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.122581 | 1905.17 | 1405.21 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.231712 | 3573.54 | 2661.88 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.232623 | 3586.28 | 2671.80 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.327830 | 4914.77 | 3703.11 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.256568 | 3862.75 | 2899.82 | 0.000084 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.301272 | 4557.80 | 3420.99 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.184887 | 2813.19 | 2100.44 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.124316 | 1930.76 | 1424.44 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.122271 | 1913.34 | 1408.52 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.231349 | 3569.66 | 2658.25 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.232256 | 3582.35 | 2668.13 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.328639 | 4927.92 | 3712.40 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.257361 | 3875.52 | 2908.90 | 0.000085 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.302165 | 4572.10 | 3431.20 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.185199 | 2819.01 | 2104.23 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.125006 | 1941.26 | 1432.18 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.123023 | 1924.71 | 1416.93 | 0.000042 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.231961 | 3579.31 | 2665.20 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.232869 | 3592.01 | 2675.10 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.336210 | 5035.56 | 3795.22 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.265354 | 3989.25 | 2996.34 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.308412 | 4666.71 | 3502.23 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.189087 | 2992.31 | 2201.53 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.131998 | 2041.36 | 1508.85 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.130000 | 2024.47 | 1493.44 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.237087 | 3652.14 | 2721.33 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.238110 | 3666.45 | 2732.47 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.411393 | 6102.07 | 4619.74 | 0.000133 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.327253 | 4880.66 | 3682.92 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.375254 | 5597.95 | 4227.27 | 0.000122 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.242352 | 3742.16 | 2783.06 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.183666 | 2896.99 | 2135.96 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.183462 | 2900.88 | 2136.76 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.314125 | 4725.45 | 3557.61 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.315091 | 4738.94 | 3568.13 | 0.000104 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.252777 | 0.252777 | 0.252777 | 0.252777 | 3842.70 | 3842.70 | 2633.20 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.194152 | 0.194152 | 0.194152 | 0.194152 | 2958.00 | 2958.00 | 2633.31 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.369901 | 0.369901 | 0.369901 | 0.369901 | 5610.84 | 5610.84 | 3380.53 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.133081 | 0.133081 | 0.133081 | 0.133081 | 2057.38 | 2057.38 | 2633.31 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.085085 | 0.085085 | 0.085085 | 0.085085 | 1364.06 | 1364.06 | 2008.22 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.082757 | 0.082757 | 0.082757 | 0.082757 | 1330.50 | 1330.50 | 2008.22 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.173383 | 0.173383 | 0.173383 | 0.173383 | 2739.68 | 2739.68 | 2004.40 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.179946 | 0.179946 | 0.179946 | 0.179946 | 2831.51 | 2831.51 | 2010.69 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.320601 | 0.320601 | 0.320601 | 0.320601 | 4798.55 | 4798.55 | 2528.11 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.249230 | 0.249230 | 0.249230 | 0.249230 | 3737.58 | 3737.58 | 2523.45 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.316525 | 0.316525 | 0.316525 | 0.316525 | 4756.20 | 4756.20 | 2546.88 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.180108 | 0.180108 | 0.180108 | 0.180108 | 2718.42 | 2718.42 | 2523.45 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.117439 | 0.117439 | 0.117439 | 0.117439 | 1827.42 | 1827.42 | 1755.15 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.115348 | 0.115348 | 0.115348 | 0.115348 | 1797.53 | 1797.53 | 1755.15 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.224299 | 0.224299 | 0.224299 | 0.224299 | 3462.18 | 3462.18 | 1762.58 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.226702 | 0.226702 | 0.226702 | 0.226702 | 3495.78 | 3495.78 | 1763.83 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.324021 | 0.324021 | 0.324021 | 0.324021 | 4850.94 | 4850.94 | 2515.86 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.253134 | 0.253134 | 0.253134 | 0.253134 | 3796.43 | 3796.43 | 2512.54 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.299212 | 0.299212 | 0.299212 | 0.299212 | 4518.65 | 4518.65 | 2517.97 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.183989 | 0.183989 | 0.183989 | 0.183989 | 2776.34 | 2776.34 | 2512.54 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.121699 | 0.121699 | 0.121699 | 0.121699 | 1889.62 | 1889.62 | 1712.12 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.119602 | 0.119602 | 0.119602 | 0.119602 | 1859.66 | 1859.66 | 1712.12 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.228575 | 0.228575 | 0.228575 | 0.228575 | 3524.66 | 3524.66 | 1716.20 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.229704 | 0.229704 | 0.229704 | 0.229704 | 3540.44 | 3540.44 | 1716.40 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.326274 | 0.326274 | 0.326274 | 0.326274 | 4885.85 | 4885.85 | 2554.64 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.255260 | 0.255260 | 0.255260 | 0.255260 | 3829.31 | 3829.31 | 2552.57 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.299576 | 0.299576 | 0.299576 | 0.299576 | 4527.09 | 4527.09 | 2554.87 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.185258 | 0.185258 | 0.185258 | 0.185258 | 2812.66 | 2812.66 | 2552.57 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.123609 | 0.123609 | 0.123609 | 0.123609 | 1918.03 | 1918.03 | 1725.84 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.121510 | 0.121510 | 0.121510 | 0.121510 | 1888.04 | 1888.04 | 1725.84 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.230553 | 0.230553 | 0.230553 | 0.230553 | 3554.33 | 3554.33 | 1728.44 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.231499 | 0.231499 | 0.231499 | 0.231499 | 3567.55 | 3567.55 | 1728.47 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.330052 | 0.330052 | 0.330052 | 0.330052 | 4941.44 | 4941.44 | 2574.82 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.258978 | 0.258978 | 0.258978 | 0.258978 | 3892.61 | 3892.61 | 2572.63 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.303240 | 0.303240 | 0.303240 | 0.303240 | 4581.05 | 4581.05 | 2574.84 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.188225 | 0.188225 | 0.188225 | 0.188225 | 2856.48 | 2856.48 | 2572.63 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.126887 | 0.126887 | 0.126887 | 0.126887 | 1965.64 | 1965.64 | 1726.94 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.124786 | 0.124786 | 0.124786 | 0.124786 | 1935.64 | 1935.64 | 1726.94 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.234010 | 0.234010 | 0.234010 | 0.234010 | 3604.33 | 3604.33 | 1729.62 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.234925 | 0.234925 | 0.234925 | 0.234925 | 3617.14 | 3617.14 | 1729.63 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.327971 | 0.327971 | 0.327971 | 0.327971 | 4914.69 | 4914.69 | 2653.56 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.256787 | 0.256787 | 0.256787 | 0.256787 | 3863.98 | 3863.98 | 2652.81 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.301298 | 0.301298 | 0.301298 | 0.301298 | 4556.18 | 4556.18 | 2653.56 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.185565 | 0.185565 | 0.185565 | 0.185565 | 2821.07 | 2821.07 | 2652.81 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.124669 | 0.124669 | 0.124669 | 0.124669 | 1935.01 | 1935.01 | 1786.44 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.122581 | 0.122581 | 0.122581 | 0.122581 | 1905.17 | 1905.17 | 1786.44 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.231712 | 0.231712 | 0.231712 | 0.231712 | 3573.54 | 3573.54 | 1787.61 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.232623 | 0.232623 | 0.232623 | 0.232623 | 3586.28 | 3586.28 | 1787.61 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.327830 | 0.327830 | 0.327830 | 0.327830 | 4914.77 | 4914.77 | 2706.80 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.256568 | 0.256568 | 0.256568 | 0.256568 | 3862.75 | 3862.75 | 2706.44 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.301272 | 0.301272 | 0.301272 | 0.301272 | 4557.80 | 4557.80 | 2706.80 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.184887 | 0.184887 | 0.184887 | 0.184887 | 2813.19 | 2813.19 | 2706.44 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.124316 | 0.124316 | 0.124316 | 0.124316 | 1930.76 | 1930.76 | 1824.23 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.122271 | 0.122271 | 0.122271 | 0.122271 | 1913.34 | 1913.34 | 1824.23 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.231349 | 0.231349 | 0.231349 | 0.231349 | 3569.66 | 3569.66 | 1825.03 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.232256 | 0.232256 | 0.232256 | 0.232256 | 3582.35 | 3582.35 | 1825.03 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.328639 | 0.328639 | 0.328639 | 0.328639 | 4927.92 | 4927.92 | 2764.07 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.257361 | 0.257361 | 0.257361 | 0.257361 | 3875.52 | 3875.52 | 2763.83 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.302165 | 0.302165 | 0.302165 | 0.302165 | 4572.10 | 4572.10 | 2764.07 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.185199 | 0.185199 | 0.185199 | 0.185199 | 2819.01 | 2819.01 | 2763.83 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.125006 | 0.125006 | 0.125006 | 0.125006 | 1941.26 | 1941.26 | 1867.67 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.123023 | 0.123023 | 0.123023 | 0.123023 | 1924.71 | 1924.71 | 1867.67 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.231961 | 0.231961 | 0.231961 | 0.231961 | 3579.31 | 3579.31 | 1868.32 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.232869 | 0.232869 | 0.232869 | 0.232869 | 3592.01 | 3592.01 | 1868.32 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.336210 | 0.336210 | 0.336210 | 0.336210 | 5035.56 | 5035.56 | 2934.65 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.265354 | 0.265354 | 0.265354 | 0.265354 | 3989.25 | 3989.25 | 2932.49 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.308412 | 0.308412 | 0.308412 | 0.308412 | 4666.71 | 4666.71 | 2934.65 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.189087 | 0.189087 | 0.189087 | 0.189087 | 2992.31 | 2992.31 | 2932.49 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.131998 | 0.131998 | 0.131998 | 0.131998 | 2041.36 | 2041.36 | 2016.33 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.130000 | 0.130000 | 0.130000 | 0.130000 | 2024.47 | 2024.47 | 2016.33 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.237087 | 0.237087 | 0.237087 | 0.237087 | 3652.14 | 3652.14 | 2018.46 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.238110 | 0.238110 | 0.238110 | 0.238110 | 3666.45 | 3666.45 | 2018.46 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.411393 | 0.411393 | 0.411393 | 0.411393 | 6102.07 | 6102.07 | 3525.16 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.327253 | 0.327253 | 0.327253 | 0.327253 | 4880.66 | 4880.66 | 3529.64 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.375254 | 0.375254 | 0.375254 | 0.375254 | 5597.95 | 5597.95 | 3525.16 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.242352 | 0.242352 | 0.242352 | 0.242352 | 3742.16 | 3742.16 | 3529.64 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.183666 | 0.183666 | 0.183666 | 0.183666 | 2896.99 | 2896.99 | 2650.04 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.183462 | 0.183462 | 0.183462 | 0.183462 | 2900.88 | 2900.88 | 2650.04 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.314125 | 0.314125 | 0.314125 | 0.314125 | 4725.45 | 4725.45 | 2642.57 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.315091 | 0.315091 | 0.315091 | 0.315091 | 4738.94 | 4738.94 | 2642.57 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.252777 |
AIRLOOP G NW SUPPLY FAN | 0.194152 |
AIRLOOP OFFICE SUPPLY FAN | 0.369901 |
AIRLOOP G NE SUPPLY FAN | 0.133081 |
AIRLOOP G N1 SUPPLY FAN | 0.085085 |
AIRLOOP G N2 SUPPLY FAN | 0.082757 |
AIRLOOP G S1 SUPPLY FAN | 0.173383 |
AIRLOOP G S2 SUPPLY FAN | 0.179946 |
AIRLOOP F2 SW SUPPLY FAN | 0.320601 |
AIRLOOP F2 NW SUPPLY FAN | 0.249230 |
AIRLOOP F2 SE SUPPLY FAN | 0.316525 |
AIRLOOP F2 NE SUPPLY FAN | 0.180108 |
AIRLOOP F2 N1 SUPPLY FAN | 0.117439 |
AIRLOOP F2 N2 SUPPLY FAN | 0.115348 |
AIRLOOP F2 S1 SUPPLY FAN | 0.224299 |
AIRLOOP F2 S2 SUPPLY FAN | 0.226702 |
AIRLOOP F3 SW SUPPLY FAN | 0.324021 |
AIRLOOP F3 NW SUPPLY FAN | 0.253134 |
AIRLOOP F3 SE SUPPLY FAN | 0.299212 |
AIRLOOP F3 NE SUPPLY FAN | 0.183989 |
AIRLOOP F3 N1 SUPPLY FAN | 0.121699 |
AIRLOOP F3 N2 SUPPLY FAN | 0.119602 |
AIRLOOP F3 S1 SUPPLY FAN | 0.228575 |
AIRLOOP F3 S2 SUPPLY FAN | 0.229704 |
AIRLOOP F4 SW SUPPLY FAN | 0.326274 |
AIRLOOP F4 NW SUPPLY FAN | 0.255260 |
AIRLOOP F4 SE SUPPLY FAN | 0.299576 |
AIRLOOP F4 NE SUPPLY FAN | 0.185258 |
AIRLOOP F4 N1 SUPPLY FAN | 0.123609 |
AIRLOOP F4 N2 SUPPLY FAN | 0.121510 |
AIRLOOP F4 S1 SUPPLY FAN | 0.230553 |
AIRLOOP F4 S2 SUPPLY FAN | 0.231499 |
AIRLOOP M SW SUPPLY FAN | 0.330052 |
AIRLOOP M NW SUPPLY FAN | 0.258978 |
AIRLOOP M SE SUPPLY FAN | 0.303240 |
AIRLOOP M NE SUPPLY FAN | 0.188225 |
AIRLOOP M N1 SUPPLY FAN | 0.126887 |
AIRLOOP M N2 SUPPLY FAN | 0.124786 |
AIRLOOP M S1 SUPPLY FAN | 0.234010 |
AIRLOOP M S2 SUPPLY FAN | 0.234925 |
AIRLOOP F6 SW SUPPLY FAN | 0.327971 |
AIRLOOP F6 NW SUPPLY FAN | 0.256787 |
AIRLOOP F6 SE SUPPLY FAN | 0.301298 |
AIRLOOP F6 NE SUPPLY FAN | 0.185565 |
AIRLOOP F6 N1 SUPPLY FAN | 0.124669 |
AIRLOOP F6 N2 SUPPLY FAN | 0.122581 |
AIRLOOP F6 S1 SUPPLY FAN | 0.231712 |
AIRLOOP F6 S2 SUPPLY FAN | 0.232623 |
AIRLOOP F7 SW SUPPLY FAN | 0.327830 |
AIRLOOP F7 NW SUPPLY FAN | 0.256568 |
AIRLOOP F7 SE SUPPLY FAN | 0.301272 |
AIRLOOP F7 NE SUPPLY FAN | 0.184887 |
AIRLOOP F7 N1 SUPPLY FAN | 0.124316 |
AIRLOOP F7 N2 SUPPLY FAN | 0.122271 |
AIRLOOP F7 S1 SUPPLY FAN | 0.231349 |
AIRLOOP F7 S2 SUPPLY FAN | 0.232256 |
AIRLOOP F8 SW SUPPLY FAN | 0.328639 |
AIRLOOP F8 NW SUPPLY FAN | 0.257361 |
AIRLOOP F8 SE SUPPLY FAN | 0.302165 |
AIRLOOP F8 NE SUPPLY FAN | 0.185199 |
AIRLOOP F8 N1 SUPPLY FAN | 0.125006 |
AIRLOOP F8 N2 SUPPLY FAN | 0.123023 |
AIRLOOP F8 S1 SUPPLY FAN | 0.231961 |
AIRLOOP F8 S2 SUPPLY FAN | 0.232869 |
AIRLOOP F9 SW SUPPLY FAN | 0.336210 |
AIRLOOP F9 NW SUPPLY FAN | 0.265354 |
AIRLOOP F9 SE SUPPLY FAN | 0.308412 |
AIRLOOP F9 NE SUPPLY FAN | 0.189087 |
AIRLOOP F9 N1 SUPPLY FAN | 0.131998 |
AIRLOOP F9 N2 SUPPLY FAN | 0.130000 |
AIRLOOP F9 S1 SUPPLY FAN | 0.237087 |
AIRLOOP F9 S2 SUPPLY FAN | 0.238110 |
AIRLOOP T SW SUPPLY FAN | 0.411393 |
AIRLOOP T NW SUPPLY FAN | 0.327253 |
AIRLOOP T SE SUPPLY FAN | 0.375254 |
AIRLOOP T NE SUPPLY FAN | 0.242352 |
AIRLOOP T N1 SUPPLY FAN | 0.183666 |
AIRLOOP T N2 SUPPLY FAN | 0.183462 |
AIRLOOP T S1 SUPPLY FAN | 0.314125 |
AIRLOOP T S2 SUPPLY FAN | 0.315091 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.252777 | 3842.70 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.194152 | 2958.00 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.369901 | 5610.84 | 0.000123 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.133081 | 2057.38 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.085085 | 1364.06 | 0.000030 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.082757 | 1330.50 | 0.000029 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.173383 | 2739.68 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.179946 | 2831.51 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.320601 | 4798.55 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.249230 | 3737.58 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.316525 | 4756.20 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.180108 | 2718.42 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.117439 | 1827.42 | 0.000040 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.115348 | 1797.53 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.224299 | 3462.18 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.226702 | 3495.78 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.324021 | 4850.94 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.253134 | 3796.43 | 0.000083 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.299212 | 4518.65 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.183989 | 2776.34 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.121699 | 1889.62 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.119602 | 1859.66 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.228575 | 3524.66 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.229704 | 3540.44 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.326274 | 4885.85 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.255260 | 3829.31 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.299576 | 4527.09 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.185258 | 2812.66 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.123609 | 1918.03 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.121510 | 1888.04 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.230553 | 3554.33 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.231499 | 3567.55 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.330052 | 4941.44 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.258978 | 3892.61 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.303240 | 4581.05 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.188225 | 2856.48 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.126887 | 1965.64 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.124786 | 1935.64 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.234010 | 3604.33 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.234925 | 3617.14 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.327971 | 4914.69 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.256787 | 3863.98 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.301298 | 4556.18 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.185565 | 2821.07 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.124669 | 1935.01 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.122581 | 1905.17 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.231712 | 3573.54 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.232623 | 3586.28 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.327830 | 4914.77 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.256568 | 3862.75 | 0.000084 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.301272 | 4557.80 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.184887 | 2813.19 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.124316 | 1930.76 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.122271 | 1913.34 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.231349 | 3569.66 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.232256 | 3582.35 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.328639 | 4927.92 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.257361 | 3875.52 | 0.000085 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.302165 | 4572.10 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.185199 | 2819.01 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.125006 | 1941.26 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.123023 | 1924.71 | 0.000042 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.231961 | 3579.31 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.232869 | 3592.01 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.336210 | 5035.56 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.265354 | 3989.25 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.308412 | 4666.71 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.189087 | 2992.31 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.131998 | 2041.36 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.130000 | 2024.47 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.237087 | 3652.14 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.238110 | 3666.45 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.411393 | 6102.07 | 0.000133 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.327253 | 4880.66 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.375254 | 5597.95 | 0.000122 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.242352 | 3742.16 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.183666 | 2896.99 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.183462 | 2900.88 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.314125 | 4725.45 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.315091 | 4738.94 | 0.000104 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2633.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2633.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3380.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2633.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2008.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2008.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2004.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2010.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2528.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2523.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2546.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2523.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1755.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1755.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1762.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1763.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2515.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2512.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2517.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2512.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1712.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1712.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1716.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1716.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2554.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2552.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2554.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2552.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1725.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1725.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1728.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1728.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2574.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2572.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2574.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2572.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1726.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1726.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1729.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1729.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2653.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2652.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2653.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2652.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1786.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1786.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1787.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1787.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 2706.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 2706.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 2706.80 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 2706.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1824.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1824.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1825.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1825.03 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2764.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2763.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2764.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2763.83 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1867.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1867.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1868.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1868.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2934.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2932.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2934.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2932.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2016.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2016.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2018.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2018.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3525.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3529.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3525.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3529.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2650.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2650.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2642.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2642.57 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.006021 | 6.77 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.006021 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.006021 | 2906.80 | 7.70 | 8956.62 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.006021 | 1922.92 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.90 |
February | 21.95 | 5.21 |
March | 22.41 | 8.41 |
April | 22.61 | 10.40 |
May | 23.08 | 13.39 |
June | 23.98 | 17.41 |
July | 24.18 | 20.12 |
August | 24.26 | 19.46 |
September | 24.14 | 16.66 |
October | 22.82 | 11.27 |
November | 21.93 | 8.49 |
December | 21.80 | 4.55 |
Annual Sum or Average | 22.92 | 11.73 |
Minimum of Months | 21.80 | 4.55 |
Maximum of Months | 24.26 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.73 | 5.21 |
March | 21.89 | 8.41 |
April | 22.20 | 10.40 |
May | 22.73 | 13.39 |
June | 23.86 | 17.41 |
July | 24.14 | 20.12 |
August | 24.18 | 19.46 |
September | 23.86 | 16.66 |
October | 22.16 | 11.27 |
November | 21.73 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.66 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.18 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.90 |
February | 22.19 | 5.21 |
March | 22.82 | 8.41 |
April | 22.99 | 10.40 |
May | 23.48 | 13.39 |
June | 24.24 | 17.41 |
July | 24.34 | 20.12 |
August | 24.38 | 19.46 |
September | 24.28 | 16.66 |
October | 23.19 | 11.27 |
November | 22.39 | 8.49 |
December | 22.01 | 4.55 |
Annual Sum or Average | 23.20 | 11.73 |
Minimum of Months | 22.01 | 4.55 |
Maximum of Months | 24.38 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 21.83 | 8.41 |
April | 22.09 | 10.40 |
May | 22.57 | 13.39 |
June | 23.72 | 17.41 |
July | 24.12 | 20.12 |
August | 24.14 | 19.46 |
September | 23.76 | 16.66 |
October | 22.05 | 11.27 |
November | 21.71 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.60 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.14 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 21.78 | 8.41 |
April | 22.00 | 10.40 |
May | 22.42 | 13.39 |
June | 23.65 | 17.41 |
July | 24.05 | 20.12 |
August | 24.08 | 19.46 |
September | 23.69 | 16.66 |
October | 22.02 | 11.27 |
November | 21.71 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.55 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.08 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.70 | 5.21 |
March | 21.78 | 8.41 |
April | 22.00 | 10.40 |
May | 22.41 | 13.39 |
June | 23.64 | 17.41 |
July | 24.05 | 20.12 |
August | 24.07 | 19.46 |
September | 23.67 | 16.66 |
October | 22.02 | 11.27 |
November | 21.71 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.54 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.07 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 4.90 |
February | 21.95 | 5.21 |
March | 22.43 | 8.41 |
April | 22.56 | 10.40 |
May | 22.95 | 13.39 |
June | 23.92 | 17.41 |
July | 24.14 | 20.12 |
August | 24.24 | 19.46 |
September | 24.15 | 16.66 |
October | 22.92 | 11.27 |
November | 22.01 | 8.49 |
December | 21.82 | 4.55 |
Annual Sum or Average | 22.92 | 11.73 |
Minimum of Months | 21.82 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 4.90 |
February | 21.97 | 5.21 |
March | 22.49 | 8.41 |
April | 22.61 | 10.40 |
May | 23.02 | 13.39 |
June | 23.96 | 17.41 |
July | 24.16 | 20.12 |
August | 24.26 | 19.46 |
September | 24.17 | 16.66 |
October | 22.97 | 11.27 |
November | 22.05 | 8.49 |
December | 21.84 | 4.55 |
Annual Sum or Average | 22.95 | 11.73 |
Minimum of Months | 21.84 | 4.55 |
Maximum of Months | 24.26 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.91 | 4.90 |
February | 17.11 | 5.21 |
March | 18.62 | 8.41 |
April | 19.52 | 10.40 |
May | 20.96 | 13.39 |
June | 23.38 | 17.41 |
July | 24.57 | 20.12 |
August | 24.30 | 19.46 |
September | 23.20 | 16.66 |
October | 19.96 | 11.27 |
November | 18.16 | 8.49 |
December | 16.71 | 4.55 |
Annual Sum or Average | 20.30 | 11.73 |
Minimum of Months | 16.71 | 4.55 |
Maximum of Months | 24.57 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.14 | 5.21 |
March | 23.16 | 8.41 |
April | 23.32 | 10.40 |
May | 23.94 | 13.39 |
June | 24.26 | 17.41 |
July | 24.31 | 20.12 |
August | 24.35 | 19.46 |
September | 24.32 | 16.66 |
October | 23.55 | 11.27 |
November | 22.26 | 8.49 |
December | 21.92 | 4.55 |
Annual Sum or Average | 23.30 | 11.73 |
Minimum of Months | 21.92 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.77 | 5.21 |
March | 22.30 | 8.41 |
April | 22.73 | 10.40 |
May | 23.60 | 13.39 |
June | 24.19 | 17.41 |
July | 24.29 | 20.12 |
August | 24.32 | 19.46 |
September | 24.15 | 16.66 |
October | 22.61 | 11.27 |
November | 21.80 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.94 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.90 |
February | 22.18 | 5.21 |
March | 23.27 | 8.41 |
April | 23.39 | 10.40 |
May | 24.01 | 13.39 |
June | 24.29 | 17.41 |
July | 24.34 | 20.12 |
August | 24.37 | 19.46 |
September | 24.34 | 16.66 |
October | 23.65 | 11.27 |
November | 22.39 | 8.49 |
December | 21.96 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 21.96 | 4.55 |
Maximum of Months | 24.37 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.73 | 5.21 |
March | 22.15 | 8.41 |
April | 22.55 | 10.40 |
May | 23.39 | 13.39 |
June | 24.11 | 17.41 |
July | 24.29 | 20.12 |
August | 24.32 | 19.46 |
September | 24.09 | 16.66 |
October | 22.42 | 11.27 |
November | 21.74 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.86 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.13 | 8.41 |
April | 22.51 | 10.40 |
May | 23.33 | 13.39 |
June | 24.07 | 17.41 |
July | 24.24 | 20.12 |
August | 24.28 | 19.46 |
September | 24.04 | 16.66 |
October | 22.48 | 11.27 |
November | 21.80 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.84 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.11 | 8.41 |
April | 22.49 | 10.40 |
May | 23.31 | 13.39 |
June | 24.06 | 17.41 |
July | 24.24 | 20.12 |
August | 24.28 | 19.46 |
September | 24.03 | 16.66 |
October | 22.46 | 11.27 |
November | 21.79 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.83 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.13 | 4.90 |
February | 22.23 | 5.21 |
March | 23.32 | 8.41 |
April | 23.39 | 10.40 |
May | 23.93 | 13.39 |
June | 24.22 | 17.41 |
July | 24.28 | 20.12 |
August | 24.34 | 19.46 |
September | 24.31 | 16.66 |
October | 23.74 | 11.27 |
November | 22.51 | 8.49 |
December | 22.01 | 4.55 |
Annual Sum or Average | 23.37 | 11.73 |
Minimum of Months | 22.01 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 4.90 |
February | 22.24 | 5.21 |
March | 23.34 | 8.41 |
April | 23.41 | 10.40 |
May | 23.94 | 13.39 |
June | 24.22 | 17.41 |
July | 24.28 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 23.76 | 11.27 |
November | 22.54 | 8.49 |
December | 22.02 | 4.55 |
Annual Sum or Average | 23.39 | 11.73 |
Minimum of Months | 22.02 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 4.90 |
February | 21.89 | 5.21 |
March | 23.25 | 8.41 |
April | 23.66 | 10.40 |
May | 24.70 | 13.39 |
June | 25.74 | 17.41 |
July | 26.13 | 20.12 |
August | 26.08 | 19.46 |
September | 25.69 | 16.66 |
October | 23.86 | 11.27 |
November | 22.32 | 8.49 |
December | 21.58 | 4.55 |
Annual Sum or Average | 23.90 | 11.73 |
Minimum of Months | 21.58 | 4.55 |
Maximum of Months | 26.13 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.90 |
February | 22.18 | 5.21 |
March | 23.30 | 8.41 |
April | 23.43 | 10.40 |
May | 24.05 | 13.39 |
June | 24.26 | 17.41 |
July | 24.30 | 20.12 |
August | 24.35 | 19.46 |
September | 24.32 | 16.66 |
October | 23.69 | 11.27 |
November | 22.33 | 8.49 |
December | 21.94 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 21.94 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.77 | 5.21 |
March | 22.46 | 8.41 |
April | 22.86 | 10.40 |
May | 23.77 | 13.39 |
June | 24.20 | 17.41 |
July | 24.29 | 20.12 |
August | 24.33 | 19.46 |
September | 24.18 | 16.66 |
October | 22.74 | 11.27 |
November | 21.82 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 23.00 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.90 |
February | 22.14 | 5.21 |
March | 23.28 | 8.41 |
April | 23.36 | 10.40 |
May | 24.02 | 13.39 |
June | 24.26 | 17.41 |
July | 24.32 | 20.12 |
August | 24.37 | 19.46 |
September | 24.32 | 16.66 |
October | 23.66 | 11.27 |
November | 22.32 | 8.49 |
December | 21.94 | 4.55 |
Annual Sum or Average | 23.34 | 11.73 |
Minimum of Months | 21.94 | 4.55 |
Maximum of Months | 24.37 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.74 | 5.21 |
March | 22.30 | 8.41 |
April | 22.69 | 10.40 |
May | 23.58 | 13.39 |
June | 24.13 | 17.41 |
July | 24.30 | 20.12 |
August | 24.33 | 19.46 |
September | 24.12 | 16.66 |
October | 22.54 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.91 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.33 | 8.41 |
April | 22.71 | 10.40 |
May | 23.61 | 13.39 |
June | 24.12 | 17.41 |
July | 24.25 | 20.12 |
August | 24.29 | 19.46 |
September | 24.09 | 16.66 |
October | 22.66 | 11.27 |
November | 21.84 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.93 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.31 | 8.41 |
April | 22.69 | 10.40 |
May | 23.59 | 13.39 |
June | 24.12 | 17.41 |
July | 24.26 | 20.12 |
August | 24.29 | 19.46 |
September | 24.08 | 16.66 |
October | 22.64 | 11.27 |
November | 21.83 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.92 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 4.90 |
February | 22.31 | 5.21 |
March | 23.54 | 8.41 |
April | 23.58 | 10.40 |
May | 24.09 | 13.39 |
June | 24.24 | 17.41 |
July | 24.28 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 23.92 | 11.27 |
November | 22.68 | 8.49 |
December | 22.07 | 4.55 |
Annual Sum or Average | 23.47 | 11.73 |
Minimum of Months | 22.07 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 4.90 |
February | 22.31 | 5.21 |
March | 23.55 | 8.41 |
April | 23.58 | 10.40 |
May | 24.09 | 13.39 |
June | 24.24 | 17.41 |
July | 24.28 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 23.92 | 11.27 |
November | 22.69 | 8.49 |
December | 22.07 | 4.55 |
Annual Sum or Average | 23.47 | 11.73 |
Minimum of Months | 22.07 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 4.90 |
February | 22.31 | 5.21 |
March | 23.82 | 8.41 |
April | 24.18 | 10.40 |
May | 25.24 | 13.39 |
June | 25.98 | 17.41 |
July | 26.28 | 20.12 |
August | 26.25 | 19.46 |
September | 25.93 | 16.66 |
October | 24.35 | 11.27 |
November | 22.73 | 8.49 |
December | 22.00 | 4.55 |
Annual Sum or Average | 24.29 | 11.73 |
Minimum of Months | 22.00 | 4.55 |
Maximum of Months | 26.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 4.90 |
February | 22.17 | 5.21 |
March | 23.32 | 8.41 |
April | 23.43 | 10.40 |
May | 24.06 | 13.39 |
June | 24.26 | 17.41 |
July | 24.30 | 20.12 |
August | 24.35 | 19.46 |
September | 24.32 | 16.66 |
October | 23.74 | 11.27 |
November | 22.34 | 8.49 |
December | 21.95 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 21.95 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.77 | 5.21 |
March | 22.53 | 8.41 |
April | 22.87 | 10.40 |
May | 23.81 | 13.39 |
June | 24.20 | 17.41 |
July | 24.28 | 20.12 |
August | 24.33 | 19.46 |
September | 24.18 | 16.66 |
October | 22.79 | 11.27 |
November | 21.83 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 23.01 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.90 |
February | 22.12 | 5.21 |
March | 23.27 | 8.41 |
April | 23.33 | 10.40 |
May | 24.01 | 13.39 |
June | 24.25 | 17.41 |
July | 24.31 | 20.12 |
August | 24.36 | 19.46 |
September | 24.31 | 16.66 |
October | 23.68 | 11.27 |
November | 22.29 | 8.49 |
December | 21.93 | 4.55 |
Annual Sum or Average | 23.33 | 11.73 |
Minimum of Months | 21.93 | 4.55 |
Maximum of Months | 24.36 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.36 | 8.41 |
April | 22.71 | 10.40 |
May | 23.62 | 13.39 |
June | 24.13 | 17.41 |
July | 24.29 | 20.12 |
August | 24.33 | 19.46 |
September | 24.12 | 16.66 |
October | 22.58 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.93 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.75 | 5.21 |
March | 22.43 | 8.41 |
April | 22.76 | 10.40 |
May | 23.71 | 13.39 |
June | 24.14 | 17.41 |
July | 24.25 | 20.12 |
August | 24.29 | 19.46 |
September | 24.10 | 16.66 |
October | 22.75 | 11.27 |
November | 21.86 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.96 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.41 | 8.41 |
April | 22.74 | 10.40 |
May | 23.68 | 13.39 |
June | 24.13 | 17.41 |
July | 24.25 | 20.12 |
August | 24.29 | 19.46 |
September | 24.09 | 16.66 |
October | 22.72 | 11.27 |
November | 21.85 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.95 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 4.90 |
February | 22.32 | 5.21 |
March | 23.59 | 8.41 |
April | 23.61 | 10.40 |
May | 24.13 | 13.39 |
June | 24.24 | 17.41 |
July | 24.27 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 23.99 | 11.27 |
November | 22.72 | 8.49 |
December | 22.08 | 4.55 |
Annual Sum or Average | 23.50 | 11.73 |
Minimum of Months | 22.08 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 4.90 |
February | 22.32 | 5.21 |
March | 23.59 | 8.41 |
April | 23.60 | 10.40 |
May | 24.13 | 13.39 |
June | 24.24 | 17.41 |
July | 24.27 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 23.99 | 11.27 |
November | 22.72 | 8.49 |
December | 22.08 | 4.55 |
Annual Sum or Average | 23.49 | 11.73 |
Minimum of Months | 22.08 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.42 | 4.90 |
February | 22.44 | 5.21 |
March | 24.02 | 8.41 |
April | 24.34 | 10.40 |
May | 25.42 | 13.39 |
June | 26.08 | 17.41 |
July | 26.36 | 20.12 |
August | 26.34 | 19.46 |
September | 26.03 | 16.66 |
October | 24.53 | 11.27 |
November | 22.87 | 8.49 |
December | 22.12 | 4.55 |
Annual Sum or Average | 24.43 | 11.73 |
Minimum of Months | 22.12 | 4.55 |
Maximum of Months | 26.36 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 4.90 |
February | 22.16 | 5.21 |
March | 23.31 | 8.41 |
April | 23.40 | 10.40 |
May | 24.04 | 13.39 |
June | 24.25 | 17.41 |
July | 24.29 | 20.12 |
August | 24.35 | 19.46 |
September | 24.32 | 16.66 |
October | 23.74 | 11.27 |
November | 22.33 | 8.49 |
December | 21.95 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 21.95 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.77 | 5.21 |
March | 22.56 | 8.41 |
April | 22.86 | 10.40 |
May | 23.79 | 13.39 |
June | 24.19 | 17.41 |
July | 24.27 | 20.12 |
August | 24.32 | 19.46 |
September | 24.18 | 16.66 |
October | 22.81 | 11.27 |
November | 21.83 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 23.01 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.90 |
February | 22.11 | 5.21 |
March | 23.26 | 8.41 |
April | 23.30 | 10.40 |
May | 23.99 | 13.39 |
June | 24.23 | 17.41 |
July | 24.30 | 20.12 |
August | 24.36 | 19.46 |
September | 24.31 | 16.66 |
October | 23.68 | 11.27 |
November | 22.28 | 8.49 |
December | 21.93 | 4.55 |
Annual Sum or Average | 23.32 | 11.73 |
Minimum of Months | 21.93 | 4.55 |
Maximum of Months | 24.36 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.39 | 8.41 |
April | 22.70 | 10.40 |
May | 23.61 | 13.39 |
June | 24.12 | 17.41 |
July | 24.28 | 20.12 |
August | 24.32 | 19.46 |
September | 24.12 | 16.66 |
October | 22.60 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.93 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.75 | 5.21 |
March | 22.48 | 8.41 |
April | 22.78 | 10.40 |
May | 23.72 | 13.39 |
June | 24.13 | 17.41 |
July | 24.24 | 20.12 |
August | 24.29 | 19.46 |
September | 24.11 | 16.66 |
October | 22.79 | 11.27 |
November | 21.87 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.97 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.75 | 5.21 |
March | 22.46 | 8.41 |
April | 22.76 | 10.40 |
May | 23.69 | 13.39 |
June | 24.12 | 17.41 |
July | 24.24 | 20.12 |
August | 24.29 | 19.46 |
September | 24.10 | 16.66 |
October | 22.76 | 11.27 |
November | 21.86 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.96 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.90 |
February | 22.32 | 5.21 |
March | 23.59 | 8.41 |
April | 23.60 | 10.40 |
May | 24.13 | 13.39 |
June | 24.23 | 17.41 |
July | 24.27 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 24.00 | 11.27 |
November | 22.72 | 8.49 |
December | 22.09 | 4.55 |
Annual Sum or Average | 23.50 | 11.73 |
Minimum of Months | 22.09 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.90 |
February | 22.31 | 5.21 |
March | 23.59 | 8.41 |
April | 23.59 | 10.40 |
May | 24.12 | 13.39 |
June | 24.23 | 17.41 |
July | 24.27 | 20.12 |
August | 24.34 | 19.46 |
September | 24.32 | 16.66 |
October | 24.00 | 11.27 |
November | 22.72 | 8.49 |
December | 22.09 | 4.55 |
Annual Sum or Average | 23.49 | 11.73 |
Minimum of Months | 22.09 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 4.90 |
February | 23.00 | 5.21 |
March | 24.60 | 8.41 |
April | 24.89 | 10.40 |
May | 25.97 | 13.39 |
June | 26.61 | 17.41 |
July | 26.89 | 20.12 |
August | 26.88 | 19.46 |
September | 26.58 | 16.66 |
October | 25.11 | 11.27 |
November | 23.45 | 8.49 |
December | 22.71 | 4.55 |
Annual Sum or Average | 24.99 | 11.73 |
Minimum of Months | 22.71 | 4.55 |
Maximum of Months | 26.89 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 4.90 |
February | 22.13 | 5.21 |
March | 23.24 | 8.41 |
April | 23.30 | 10.40 |
May | 23.97 | 13.39 |
June | 24.22 | 17.41 |
July | 24.27 | 20.12 |
August | 24.34 | 19.46 |
September | 24.30 | 16.66 |
October | 23.66 | 11.27 |
November | 22.25 | 8.49 |
December | 21.93 | 4.55 |
Annual Sum or Average | 23.31 | 11.73 |
Minimum of Months | 21.93 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.76 | 5.21 |
March | 22.48 | 8.41 |
April | 22.77 | 10.40 |
May | 23.69 | 13.39 |
June | 24.14 | 17.41 |
July | 24.24 | 20.12 |
August | 24.31 | 19.46 |
September | 24.14 | 16.66 |
October | 22.72 | 11.27 |
November | 21.80 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.96 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.31 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 4.90 |
February | 22.08 | 5.21 |
March | 23.19 | 8.41 |
April | 23.21 | 10.40 |
May | 23.90 | 13.39 |
June | 24.20 | 17.41 |
July | 24.28 | 20.12 |
August | 24.35 | 19.46 |
September | 24.29 | 16.66 |
October | 23.60 | 11.27 |
November | 22.20 | 8.49 |
December | 21.91 | 4.55 |
Annual Sum or Average | 23.27 | 11.73 |
Minimum of Months | 21.91 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.73 | 5.21 |
March | 22.32 | 8.41 |
April | 22.61 | 10.40 |
May | 23.50 | 13.39 |
June | 24.06 | 17.41 |
July | 24.26 | 20.12 |
August | 24.31 | 19.46 |
September | 24.07 | 16.66 |
October | 22.51 | 11.27 |
November | 21.74 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.88 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.31 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.40 | 8.41 |
April | 22.69 | 10.40 |
May | 23.61 | 13.39 |
June | 24.07 | 17.41 |
July | 24.21 | 20.12 |
August | 24.28 | 19.46 |
September | 24.06 | 16.66 |
October | 22.69 | 11.27 |
November | 21.83 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.92 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.38 | 8.41 |
April | 22.67 | 10.40 |
May | 23.58 | 13.39 |
June | 24.07 | 17.41 |
July | 24.22 | 20.12 |
August | 24.28 | 19.46 |
September | 24.05 | 16.66 |
October | 22.66 | 11.27 |
November | 21.82 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.91 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.90 |
February | 22.26 | 5.21 |
March | 23.52 | 8.41 |
April | 23.50 | 10.40 |
May | 24.06 | 13.39 |
June | 24.20 | 17.41 |
July | 24.25 | 20.12 |
August | 24.33 | 19.46 |
September | 24.31 | 16.66 |
October | 23.94 | 11.27 |
November | 22.62 | 8.49 |
December | 22.05 | 4.55 |
Annual Sum or Average | 23.44 | 11.73 |
Minimum of Months | 22.05 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.90 |
February | 22.26 | 5.21 |
March | 23.51 | 8.41 |
April | 23.49 | 10.40 |
May | 24.06 | 13.39 |
June | 24.20 | 17.41 |
July | 24.25 | 20.12 |
August | 24.33 | 19.46 |
September | 24.31 | 16.66 |
October | 23.94 | 11.27 |
November | 22.61 | 8.49 |
December | 22.05 | 4.55 |
Annual Sum or Average | 23.44 | 11.73 |
Minimum of Months | 22.05 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 4.90 |
February | 22.36 | 5.21 |
March | 23.97 | 8.41 |
April | 24.23 | 10.40 |
May | 25.33 | 13.39 |
June | 26.01 | 17.41 |
July | 26.31 | 20.12 |
August | 26.31 | 19.46 |
September | 25.99 | 16.66 |
October | 24.48 | 11.27 |
November | 22.79 | 8.49 |
December | 22.08 | 4.55 |
Annual Sum or Average | 24.37 | 11.73 |
Minimum of Months | 22.08 | 4.55 |
Maximum of Months | 26.31 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.10 | 5.21 |
March | 23.18 | 8.41 |
April | 23.23 | 10.40 |
May | 23.91 | 13.39 |
June | 24.19 | 17.41 |
July | 24.25 | 20.12 |
August | 24.33 | 19.46 |
September | 24.29 | 16.66 |
October | 23.60 | 11.27 |
November | 22.19 | 8.49 |
December | 21.91 | 4.55 |
Annual Sum or Average | 23.27 | 11.73 |
Minimum of Months | 21.91 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.75 | 5.21 |
March | 22.43 | 8.41 |
April | 22.70 | 10.40 |
May | 23.61 | 13.39 |
June | 24.11 | 17.41 |
July | 24.23 | 20.12 |
August | 24.30 | 19.46 |
September | 24.11 | 16.66 |
October | 22.65 | 11.27 |
November | 21.78 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.93 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.30 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.90 |
February | 22.05 | 5.21 |
March | 23.13 | 8.41 |
April | 23.14 | 10.40 |
May | 23.84 | 13.39 |
June | 24.17 | 17.41 |
July | 24.26 | 20.12 |
August | 24.35 | 19.46 |
September | 24.28 | 16.66 |
October | 23.53 | 11.27 |
November | 22.14 | 8.49 |
December | 21.89 | 4.55 |
Annual Sum or Average | 23.24 | 11.73 |
Minimum of Months | 21.89 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.72 | 5.21 |
March | 22.27 | 8.41 |
April | 22.54 | 10.40 |
May | 23.42 | 13.39 |
June | 24.01 | 17.41 |
July | 24.24 | 20.12 |
August | 24.29 | 19.46 |
September | 24.03 | 16.66 |
October | 22.45 | 11.27 |
November | 21.73 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.85 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.34 | 8.41 |
April | 22.61 | 10.40 |
May | 23.52 | 13.39 |
June | 24.03 | 17.41 |
July | 24.19 | 20.12 |
August | 24.26 | 19.46 |
September | 24.02 | 16.66 |
October | 22.61 | 11.27 |
November | 21.80 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.89 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.26 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.32 | 8.41 |
April | 22.59 | 10.40 |
May | 23.49 | 13.39 |
June | 24.02 | 17.41 |
July | 24.19 | 20.12 |
August | 24.26 | 19.46 |
September | 24.02 | 16.66 |
October | 22.59 | 11.27 |
November | 21.80 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.88 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.26 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 4.90 |
February | 22.22 | 5.21 |
March | 23.45 | 8.41 |
April | 23.41 | 10.40 |
May | 24.01 | 13.39 |
June | 24.18 | 17.41 |
July | 24.23 | 20.12 |
August | 24.32 | 19.46 |
September | 24.29 | 16.66 |
October | 23.88 | 11.27 |
November | 22.53 | 8.49 |
December | 22.03 | 4.55 |
Annual Sum or Average | 23.40 | 11.73 |
Minimum of Months | 22.03 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 4.90 |
February | 22.22 | 5.21 |
March | 23.45 | 8.41 |
April | 23.40 | 10.40 |
May | 24.00 | 13.39 |
June | 24.18 | 17.41 |
July | 24.23 | 20.12 |
August | 24.32 | 19.46 |
September | 24.29 | 16.66 |
October | 23.88 | 11.27 |
November | 22.53 | 8.49 |
December | 22.03 | 4.55 |
Annual Sum or Average | 23.40 | 11.73 |
Minimum of Months | 22.03 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 4.90 |
February | 22.21 | 5.21 |
March | 23.81 | 8.41 |
April | 24.05 | 10.40 |
May | 25.17 | 13.39 |
June | 25.89 | 17.41 |
July | 26.21 | 20.12 |
August | 26.22 | 19.46 |
September | 25.88 | 16.66 |
October | 24.31 | 11.27 |
November | 22.63 | 8.49 |
December | 21.94 | 4.55 |
Annual Sum or Average | 24.23 | 11.73 |
Minimum of Months | 21.94 | 4.55 |
Maximum of Months | 26.22 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 4.90 |
February | 22.08 | 5.21 |
March | 23.13 | 8.41 |
April | 23.16 | 10.40 |
May | 23.86 | 13.39 |
June | 24.17 | 17.41 |
July | 24.24 | 20.12 |
August | 24.33 | 19.46 |
September | 24.27 | 16.66 |
October | 23.53 | 11.27 |
November | 22.14 | 8.49 |
December | 21.90 | 4.55 |
Annual Sum or Average | 23.24 | 11.73 |
Minimum of Months | 21.90 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.37 | 8.41 |
April | 22.64 | 10.40 |
May | 23.54 | 13.39 |
June | 24.07 | 17.41 |
July | 24.21 | 20.12 |
August | 24.29 | 19.46 |
September | 24.08 | 16.66 |
October | 22.58 | 11.27 |
November | 21.77 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.90 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 4.90 |
February | 22.03 | 5.21 |
March | 23.08 | 8.41 |
April | 23.08 | 10.40 |
May | 23.78 | 13.39 |
June | 24.14 | 17.41 |
July | 24.25 | 20.12 |
August | 24.34 | 19.46 |
September | 24.26 | 16.66 |
October | 23.46 | 11.27 |
November | 22.09 | 8.49 |
December | 21.88 | 4.55 |
Annual Sum or Average | 23.20 | 11.73 |
Minimum of Months | 21.88 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.72 | 5.21 |
March | 22.23 | 8.41 |
April | 22.48 | 10.40 |
May | 23.34 | 13.39 |
June | 23.97 | 17.41 |
July | 24.22 | 20.12 |
August | 24.28 | 19.46 |
September | 24.00 | 16.66 |
October | 22.39 | 11.27 |
November | 21.72 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.82 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.29 | 8.41 |
April | 22.55 | 10.40 |
May | 23.44 | 13.39 |
June | 24.00 | 17.41 |
July | 24.17 | 20.12 |
August | 24.25 | 19.46 |
September | 23.99 | 16.66 |
October | 22.54 | 11.27 |
November | 21.78 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.85 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.25 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.27 | 8.41 |
April | 22.53 | 10.40 |
May | 23.42 | 13.39 |
June | 23.98 | 17.41 |
July | 24.17 | 20.12 |
August | 24.25 | 19.46 |
September | 23.98 | 16.66 |
October | 22.52 | 11.27 |
November | 21.78 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.84 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.25 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 4.90 |
February | 22.19 | 5.21 |
March | 23.39 | 8.41 |
April | 23.33 | 10.40 |
May | 23.95 | 13.39 |
June | 24.16 | 17.41 |
July | 24.22 | 20.12 |
August | 24.32 | 19.46 |
September | 24.28 | 16.66 |
October | 23.82 | 11.27 |
November | 22.45 | 8.49 |
December | 22.00 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 22.00 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 4.90 |
February | 22.18 | 5.21 |
March | 23.38 | 8.41 |
April | 23.32 | 10.40 |
May | 23.94 | 13.39 |
June | 24.16 | 17.41 |
July | 24.22 | 20.12 |
August | 24.32 | 19.46 |
September | 24.28 | 16.66 |
October | 23.81 | 11.27 |
November | 22.45 | 8.49 |
December | 22.00 | 4.55 |
Annual Sum or Average | 23.36 | 11.73 |
Minimum of Months | 22.00 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 4.90 |
February | 22.13 | 5.21 |
March | 23.70 | 8.41 |
April | 23.94 | 10.40 |
May | 25.07 | 13.39 |
June | 25.84 | 17.41 |
July | 26.18 | 20.12 |
August | 26.20 | 19.46 |
September | 25.82 | 16.66 |
October | 24.20 | 11.27 |
November | 22.54 | 8.49 |
December | 21.86 | 4.55 |
Annual Sum or Average | 24.15 | 11.73 |
Minimum of Months | 21.86 | 4.55 |
Maximum of Months | 26.20 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.90 |
February | 22.05 | 5.21 |
March | 23.04 | 8.41 |
April | 23.09 | 10.40 |
May | 23.79 | 13.39 |
June | 24.14 | 17.41 |
July | 24.23 | 20.12 |
August | 24.32 | 19.46 |
September | 24.25 | 16.66 |
October | 23.40 | 11.27 |
November | 22.08 | 8.49 |
December | 21.88 | 4.55 |
Annual Sum or Average | 23.19 | 11.73 |
Minimum of Months | 21.88 | 4.55 |
Maximum of Months | 24.32 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.31 | 8.41 |
April | 22.58 | 10.40 |
May | 23.47 | 13.39 |
June | 24.03 | 17.41 |
July | 24.19 | 20.12 |
August | 24.28 | 19.46 |
September | 24.03 | 16.66 |
October | 22.50 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.87 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.90 |
February | 22.01 | 5.21 |
March | 22.99 | 8.41 |
April | 23.01 | 10.40 |
May | 23.71 | 13.39 |
June | 24.11 | 17.41 |
July | 24.23 | 20.12 |
August | 24.33 | 19.46 |
September | 24.24 | 16.66 |
October | 23.33 | 11.27 |
November | 22.04 | 8.49 |
December | 21.87 | 4.55 |
Annual Sum or Average | 23.16 | 11.73 |
Minimum of Months | 21.87 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 22.18 | 8.41 |
April | 22.43 | 10.40 |
May | 23.27 | 13.39 |
June | 23.92 | 17.41 |
July | 24.19 | 20.12 |
August | 24.26 | 19.46 |
September | 23.94 | 16.66 |
October | 22.32 | 11.27 |
November | 21.72 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.79 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.26 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.72 | 5.21 |
March | 22.23 | 8.41 |
April | 22.49 | 10.40 |
May | 23.37 | 13.39 |
June | 23.96 | 17.41 |
July | 24.16 | 20.12 |
August | 24.24 | 19.46 |
September | 23.95 | 16.66 |
October | 22.45 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.82 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.72 | 5.21 |
March | 22.21 | 8.41 |
April | 22.48 | 10.40 |
May | 23.34 | 13.39 |
June | 23.95 | 17.41 |
July | 24.16 | 20.12 |
August | 24.24 | 19.46 |
September | 23.94 | 16.66 |
October | 22.43 | 11.27 |
November | 21.76 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.81 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.90 |
February | 22.14 | 5.21 |
March | 23.27 | 8.41 |
April | 23.24 | 10.40 |
May | 23.88 | 13.39 |
June | 24.13 | 17.41 |
July | 24.20 | 20.12 |
August | 24.31 | 19.46 |
September | 24.27 | 16.66 |
October | 23.68 | 11.27 |
November | 22.34 | 8.49 |
December | 21.97 | 4.55 |
Annual Sum or Average | 23.30 | 11.73 |
Minimum of Months | 21.97 | 4.55 |
Maximum of Months | 24.31 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.90 |
February | 22.14 | 5.21 |
March | 23.27 | 8.41 |
April | 23.23 | 10.40 |
May | 23.87 | 13.39 |
June | 24.13 | 17.41 |
July | 24.20 | 20.12 |
August | 24.31 | 19.46 |
September | 24.27 | 16.66 |
October | 23.68 | 11.27 |
November | 22.34 | 8.49 |
December | 21.97 | 4.55 |
Annual Sum or Average | 23.30 | 11.73 |
Minimum of Months | 21.97 | 4.55 |
Maximum of Months | 24.31 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 4.90 |
February | 21.99 | 5.21 |
March | 23.55 | 8.41 |
April | 23.83 | 10.40 |
May | 24.98 | 13.39 |
June | 25.83 | 17.41 |
July | 26.21 | 20.12 |
August | 26.21 | 19.46 |
September | 25.77 | 16.66 |
October | 24.03 | 11.27 |
November | 22.39 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 24.05 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 26.21 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.90 |
February | 22.03 | 5.21 |
March | 22.77 | 8.41 |
April | 22.91 | 10.40 |
May | 23.49 | 13.39 |
June | 23.94 | 17.41 |
July | 24.12 | 20.12 |
August | 24.22 | 19.46 |
September | 24.03 | 16.66 |
October | 23.01 | 11.27 |
November | 22.06 | 8.49 |
December | 21.88 | 4.55 |
Annual Sum or Average | 23.04 | 11.73 |
Minimum of Months | 21.88 | 4.55 |
Maximum of Months | 24.22 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.90 |
February | 21.77 | 5.21 |
March | 22.28 | 8.41 |
April | 22.53 | 10.40 |
May | 23.22 | 13.39 |
June | 23.79 | 17.41 |
July | 24.05 | 20.12 |
August | 24.10 | 19.46 |
September | 23.70 | 16.66 |
October | 22.40 | 11.27 |
November | 21.78 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.76 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.10 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.90 |
February | 22.01 | 5.21 |
March | 22.74 | 8.41 |
April | 22.86 | 10.40 |
May | 23.43 | 13.39 |
June | 23.90 | 17.41 |
July | 24.12 | 20.12 |
August | 24.22 | 19.46 |
September | 24.00 | 16.66 |
October | 22.96 | 11.27 |
November | 22.03 | 8.49 |
December | 21.87 | 4.55 |
Annual Sum or Average | 23.01 | 11.73 |
Minimum of Months | 21.87 | 4.55 |
Maximum of Months | 24.22 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.18 | 8.41 |
April | 22.41 | 10.40 |
May | 23.08 | 13.39 |
June | 23.67 | 17.41 |
July | 24.03 | 20.12 |
August | 24.06 | 19.46 |
September | 23.60 | 16.66 |
October | 22.25 | 11.27 |
November | 21.73 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.68 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.06 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.74 | 5.21 |
March | 22.19 | 8.41 |
April | 22.45 | 10.40 |
May | 23.15 | 13.39 |
June | 23.75 | 17.41 |
July | 24.01 | 20.12 |
August | 24.06 | 19.46 |
September | 23.64 | 16.66 |
October | 22.32 | 11.27 |
November | 21.76 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.71 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.06 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.73 | 5.21 |
March | 22.18 | 8.41 |
April | 22.44 | 10.40 |
May | 23.14 | 13.39 |
June | 23.74 | 17.41 |
July | 24.01 | 20.12 |
August | 24.06 | 19.46 |
September | 23.63 | 16.66 |
October | 22.30 | 11.27 |
November | 21.76 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.71 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.06 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.09 | 5.21 |
March | 22.95 | 8.41 |
April | 23.05 | 10.40 |
May | 23.61 | 13.39 |
June | 24.00 | 17.41 |
July | 24.12 | 20.12 |
August | 24.24 | 19.46 |
September | 24.10 | 16.66 |
October | 23.23 | 11.27 |
November | 22.22 | 8.49 |
December | 21.94 | 4.55 |
Annual Sum or Average | 23.14 | 11.73 |
Minimum of Months | 21.94 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.09 | 5.21 |
March | 22.94 | 8.41 |
April | 23.05 | 10.40 |
May | 23.60 | 13.39 |
June | 23.99 | 17.41 |
July | 24.12 | 20.12 |
August | 24.24 | 19.46 |
September | 24.10 | 16.66 |
October | 23.23 | 11.27 |
November | 22.22 | 8.49 |
December | 21.94 | 4.55 |
Annual Sum or Average | 23.13 | 11.73 |
Minimum of Months | 21.94 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:12:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.06 | 5.21 |
March | 23.65 | 8.41 |
April | 24.15 | 10.40 |
May | 25.37 | 13.39 |
June | 26.36 | 17.41 |
July | 26.89 | 20.12 |
August | 26.80 | 19.46 |
September | 26.13 | 16.66 |
October | 24.09 | 11.27 |
November | 22.50 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 24.32 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 26.89 | 20.12 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:13
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.235133E+12 | 126492.141 | 10-JAN-17:15 | 11327.174 | 57142.088 | 21005.320 | 22698.518 | 0.000 | 10364.000 | 1959.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.218811E+12 | 135718.324 | 07-FEB-18:00 | 13120.457 | 57042.023 | 21005.320 | 30238.671 | 0.000 | 10364.000 | 1959.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.215029E+12 | 120298.190 | 20-MAR-18:30 | 14401.373 | 51749.961 | 21005.320 | 0.000 | 18552.749 | 10364.000 | 1959.845 | 503.918 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.205757E+12 | 148909.650 | 29-APR-16:15 | 11327.174 | 57042.023 | 21005.320 | 0.000 | 53415.972 | 0.000 | 1959.845 | 2171.674 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.214828E+12 | 155432.416 | 05-MAY-16:15 | 11327.174 | 57142.088 | 21005.320 | 0.000 | 59710.048 | 0.000 | 1959.845 | 2292.744 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.227634E+12 | 161304.406 | 25-JUN-17:15 | 13120.457 | 57042.023 | 21005.320 | 0.000 | 63995.978 | 0.000 | 1959.845 | 2192.973 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.260351E+12 | 165462.525 | 19-JUL-17:15 | 13120.457 | 57042.023 | 21005.320 | 0.000 | 67773.435 | 0.000 | 1959.845 | 2573.634 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.259016E+12 | 161152.537 | 31-AUG-16:30 | 11327.174 | 57142.088 | 21005.320 | 0.000 | 65477.740 | 0.000 | 1959.845 | 2245.212 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.233789E+12 | 162989.237 | 09-SEP-16:15 | 11327.174 | 57042.023 | 21005.320 | 0.000 | 67273.385 | 0.000 | 1959.845 | 2393.848 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.215019E+12 | 132763.638 | 01-OCT-16:15 | 11327.174 | 57042.023 | 21005.320 | 0.000 | 37905.591 | 0.000 | 1959.845 | 1536.043 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.213916E+12 | 121656.378 | 26-NOV-18:00 | 13120.457 | 57042.023 | 21005.320 | 16176.725 | 0.000 | 10364.000 | 1959.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.245739E+12 | 139683.963 | 20-DEC-17:00 | 11327.174 | 57142.088 | 21005.320 | 35890.377 | 0.000 | 10364.000 | 1959.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.274502E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.205757E+12 | 120298.190 | 11327.174 | 51749.961 | 21005.320 | 0.000 | 0.000 | 0.000 | 1959.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.260351E+12 | 165462.525 | 14401.373 | 57142.088 | 21005.320 | 35890.377 | 67773.435 | 10364.000 | 1959.845 | 2573.634 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:13
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.208621E+12 | 183360.365 | 03-JAN-07:30 | 0.000 | 0.000 | 0.000 | 183360.365 | 79193.909 | 79193.909 | 104166.457 |
February | 0.220870E+12 | 254268.154 | 15-FEB-06:15 | 0.000 | 0.000 | 0.000 | 254268.154 | 67283.937 | 67283.937 | 186984.218 |
March | 0.128199E+12 | 159478.822 | 03-MAR-06:15 | 0.000 | 0.000 | 0.000 | 159478.822 | 66369.610 | 66369.610 | 93109.212 |
April | 0.114535E+12 | 140653.624 | 11-APR-05:30 | 0.000 | 0.000 | 0.000 | 140653.624 | 74423.600 | 74423.600 | 66230.024 |
May | 0.978567E+11 | 96124.937 | 24-MAY-05:45 | 0.000 | 0.000 | 0.000 | 96124.937 | 74770.273 | 74770.273 | 21354.664 |
June | 0.909604E+11 | 76787.293 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 76787.293 | 76787.293 | 76787.293 | 0.000 |
July | 0.916330E+11 | 75785.195 | 01-JUL-06:00 | 0.000 | 0.000 | 0.000 | 75785.195 | 75785.195 | 75785.195 | 0.000 |
August | 0.908674E+11 | 75272.210 | 29-AUG-06:00 | 0.000 | 0.000 | 0.000 | 75272.210 | 75272.210 | 75272.210 | 0.000 |
September | 0.889742E+11 | 75910.364 | 29-SEP-06:00 | 0.000 | 0.000 | 0.000 | 75910.364 | 75910.364 | 75910.364 | 0.000 |
October | 0.998397E+11 | 129290.659 | 31-OCT-09:15 | 0.000 | 0.000 | 0.000 | 129290.659 | 71031.342 | 71031.342 | 58259.317 |
November | 0.147386E+12 | 155355.528 | 20-NOV-09:15 | 0.000 | 0.000 | 0.000 | 155355.528 | 74575.194 | 74575.194 | 80780.334 |
December | 0.252825E+12 | 258365.998 | 20-DEC-07:00 | 0.000 | 0.000 | 0.000 | 258365.998 | 78981.475 | 78981.475 | 179384.523 |
Annual Sum or Average | 0.163257E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.889742E+11 | 75272.210 | 0.000 | 0.000 | 0.000 | 75272.210 | 66369.610 | 66369.610 | 0.000 | |
Maximum of Months | 0.252825E+12 | 258365.998 | 0.000 | 0.000 | 0.000 | 258365.998 | 79193.909 | 79193.909 | 186984.218 |