Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Burlington International Ap VT USA TMY3 WMO#=726170
Simulation Timestamp: 2015-09-09 19:00:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 5745.17 | 733.13 | 813.78 |
Net Site Energy | 5745.17 | 733.13 | 813.78 |
Total Source Energy | 12362.72 | 1577.59 | 1751.12 |
Net Source Energy | 12362.72 | 1577.59 | 1751.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 402.19 | 1558.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 230.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 605.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.13 | 0.00 | 0.00 | 0.00 | 0.00 | 692.77 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1241.86 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2945.25 | 2799.92 | 0.00 | 0.00 | 0.00 | 5471.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1558.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 402.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 230.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 605.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 64.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 10.13 | 0.00 | 0.00 | 0.00 | 0.00 | 692.77 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1241.86 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 185.91 | 396.60 | 0.00 | 0.00 | 0.00 | 0.77 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 417.18 | 396.60 | 0.00 | 0.00 | 0.00 | 0.77 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.49 | 357.29 | 0.00 | 0.00 | 0.00 | 0.70 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 375.84 | 357.29 | 0.00 | 0.00 | 0.00 | 0.70 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2945.25 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2945.25 | 100.00 |
Total On-Site and Utility Electric Sources | 2945.25 | 100.00 |
Total Electricity End Uses | 2945.25 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5471.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5471.28 | 100.00 |
Total Water End Uses | 5471.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 120.25 |
Time Setpoint Not Met During Occupied Cooling | 100.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3353.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59 |
RunPeriod | Burlington International Ap VT USA TMY3 WMO#=726170 |
Weather File | Burlington International Ap VT USA TMY3 WMO#=726170 |
Latitude [deg] | 44.47 |
Longitude [deg] | -73.2 |
Elevation [m] | 101.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-FEB-17:00 | 24-JAN-07:30 | - | - | - | 20-JUL-17:15 |
Heating | 87652.69 | 287983.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19201.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2079.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 84624.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 189762.54 | 372607.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 287983.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 9220.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2106.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19201.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2079.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 84624.48 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1273.75 | 1688.94 | 0.00 | 0.00 | 0.00 |
Cooling | 729.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 515.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1917.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 203.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1346.17 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9327.60 | 3035.12 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 180.42 | 239.23 | 0.00 | 0.00 | 0.00 |
Cooling | 103.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 190.68 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1321.21 | 429.91 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 180.42 | 239.23 | 0.00 | 0.00 | 0.00 |
Cooling | 103.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 190.68 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1321.21 | 429.91 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00 | -22.40 | Wetbulb [C] | 3.00 | 60.00 |
BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 10.70 | 21.70 | Wetbulb [C] | 4.50 | 170.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.63 | 83.63 | 162.69 | |
Exterior Lighting Total | 10364.00 | 162.69 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 294118.77 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 235295.01 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3615.89 | 2481.30 | 1134.59 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3274.33 | 2230.09 | 1044.25 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5487.24 | 3826.54 | 1660.70 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2865.06 | 1896.97 | 968.09 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2114.52 | 1356.97 | 757.55 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2123.52 | 1360.25 | 763.27 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2486.75 | 1648.50 | 838.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2576.07 | 1716.41 | 859.66 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4609.02 | 3210.05 | 1398.97 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4198.77 | 2900.91 | 1297.85 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4567.41 | 3173.61 | 1393.80 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3291.40 | 2228.56 | 1062.83 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2426.09 | 1602.37 | 823.72 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2406.11 | 1587.54 | 818.58 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3198.48 | 2171.12 | 1027.37 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3231.48 | 2196.27 | 1035.20 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4689.66 | 3251.77 | 1437.89 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4289.48 | 2951.12 | 1338.36 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4359.19 | 2995.77 | 1363.42 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3387.18 | 2282.92 | 1104.26 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2510.47 | 1656.44 | 854.03 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2490.59 | 1641.71 | 848.88 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3281.95 | 2223.57 | 1058.38 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3296.98 | 2235.04 | 1061.94 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4748.68 | 3280.84 | 1467.85 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4343.30 | 2978.20 | 1365.10 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4383.30 | 3000.22 | 1383.08 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3427.72 | 2301.36 | 1126.36 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2550.81 | 1679.95 | 870.86 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2530.89 | 1665.22 | 865.67 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3320.96 | 2245.02 | 1075.95 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3333.37 | 2254.48 | 1078.89 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4819.33 | 3322.83 | 1496.50 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4414.47 | 3021.03 | 1393.44 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4450.14 | 3039.74 | 1410.40 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3487.52 | 2336.60 | 1150.92 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2609.34 | 1718.17 | 891.17 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2589.43 | 1703.46 | 885.97 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3378.20 | 2281.80 | 1096.41 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3390.20 | 2290.93 | 1099.26 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4804.55 | 3301.81 | 1502.74 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4397.84 | 2999.26 | 1398.58 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4435.03 | 3019.02 | 1416.01 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3461.88 | 2309.49 | 1152.39 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2584.31 | 1695.28 | 889.03 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2564.43 | 1680.65 | 883.78 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3352.94 | 2257.15 | 1095.79 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3364.87 | 2266.22 | 1098.65 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4815.47 | 3301.59 | 1513.88 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4408.15 | 2999.08 | 1409.07 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4448.89 | 3020.82 | 1428.07 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3463.85 | 2304.16 | 1159.69 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2586.42 | 1693.12 | 893.30 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2566.57 | 1678.54 | 888.03 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3354.25 | 2253.34 | 1100.91 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3366.15 | 2262.39 | 1103.77 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4840.81 | 3313.23 | 1527.58 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4433.65 | 3011.23 | 1422.42 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4473.98 | 3032.63 | 1441.36 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3480.66 | 2310.70 | 1169.96 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2605.10 | 1703.60 | 901.50 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2585.31 | 1689.08 | 896.23 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3370.65 | 2261.47 | 1109.19 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3382.56 | 2270.50 | 1112.06 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4976.17 | 3409.99 | 1566.19 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4578.53 | 3113.66 | 1464.87 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4586.19 | 3110.55 | 1475.64 | 0.68 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3550.26 | 2355.27 | 1194.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2727.79 | 1790.96 | 936.83 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2707.68 | 1776.18 | 931.51 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3463.06 | 2326.54 | 1136.52 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3474.79 | 2335.45 | 1139.34 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5999.32 | 4173.57 | 1825.75 | 0.70 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5415.59 | 3736.12 | 1679.48 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5496.21 | 3792.90 | 1703.31 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4353.25 | 2928.18 | 1425.07 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3402.57 | 2276.94 | 1125.64 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3399.99 | 2274.85 | 1125.14 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4504.17 | 3112.60 | 1391.58 | 0.69 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4515.29 | 3121.14 | 1394.15 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3615.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3274.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5487.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2865.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2114.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2123.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2486.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2576.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4609.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4198.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4567.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3291.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2426.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2406.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3198.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3231.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4689.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4289.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4359.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3387.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2510.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2490.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3281.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3296.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4748.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4343.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4383.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3427.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2550.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2530.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3320.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3333.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4819.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4414.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4450.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3487.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2609.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2589.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3378.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3390.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4804.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4397.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4435.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3461.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2584.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2564.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3352.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3364.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4815.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4408.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4448.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3463.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2586.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2566.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3354.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3366.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4840.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4433.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4473.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3480.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2605.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2585.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3370.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3382.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4976.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4578.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4586.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3550.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2727.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2707.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3463.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3474.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5999.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5415.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5496.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4353.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3402.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3399.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4504.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4515.29 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 4791.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 4792.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 5842.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 4787.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 3709.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 3709.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 3705.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 3712.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 4635.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 4629.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 4650.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 4625.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 3290.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 3290.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 3300.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 3301.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 4687.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 4685.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 4687.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 4684.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 3270.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 3270.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 3273.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 3273.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 4808.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 4811.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 4809.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 4811.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 3334.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 3334.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 3333.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 3333.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 4901.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 4905.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 4903.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 4906.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 3379.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 3379.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 3377.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 3377.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 5046.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 5052.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 5048.77 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 5055.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 3482.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 3482.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 3477.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 3477.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 5156.64 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 5164.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 5160.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 5168.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 3557.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 3557.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 3549.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 3550.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 5270.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 5279.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 5275.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 5283.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 3638.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 3638.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 3630.10 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 3630.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 5546.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 5553.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 5552.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 5558.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 3870.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 3870.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 3864.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 3864.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 6473.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 6489.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 6479.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 6495.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 4848.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 4848.98 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 4830.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 4830.81 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 242.07 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 217.30 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 378.19 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.36 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 124.19 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 124.19 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 154.27 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.57 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 318.99 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 287.18 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 314.13 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 217.75 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 152.11 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.52 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.09 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 211.79 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.15 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 291.28 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.72 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.87 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 157.18 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 155.61 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.94 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.17 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.00 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.23 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.24 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.94 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 159.17 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 157.60 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.66 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.68 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 327.70 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.04 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 296.69 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.98 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 162.82 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.25 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.13 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 220.11 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.77 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.05 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.81 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.46 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 160.01 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 158.46 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.08 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 217.06 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.15 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.46 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.26 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.36 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 159.47 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 157.92 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.32 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.30 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.87 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.25 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.01 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.58 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 160.30 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 158.76 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.88 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.85 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 335.05 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 304.73 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.87 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.40 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.35 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.78 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.39 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 223.35 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 415.22 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 369.55 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 374.70 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 281.60 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.67 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.44 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 306.59 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 307.52 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0064 | 2042.95 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2192.67 | 2631.20 | 0.174 | 0.209 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.82 | 0.01255 |
G NW APARTMENT | 1968.41 | 2362.09 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
OFFICE | 3425.75 | 4110.90 | 0.271 | 0.326 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
G NE APARTMENT | 1424.52 | 1709.42 | 0.113 | 0.135 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 26.78 | 0.01255 |
G N1 APARTMENT | 974.12 | 1168.94 | 0.077 | 0.093 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
G N2 APARTMENT | 957.28 | 1148.73 | 0.076 | 0.091 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
G S1 APARTMENT | 1397.42 | 1676.90 | 0.111 | 0.133 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
G S2 APARTMENT | 1463.58 | 1756.29 | 0.116 | 0.139 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F2 SW APARTMENT | 2889.45 | 3467.34 | 0.229 | 0.275 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
F2 NW APARTMENT | 2601.35 | 3121.62 | 0.206 | 0.247 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F2 SE APARTMENT | 2845.42 | 3414.51 | 0.226 | 0.271 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
F2 NE APARTMENT | 1972.36 | 2366.84 | 0.156 | 0.188 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.23 | 0.01255 |
F2 N1 APARTMENT | 1377.84 | 1653.41 | 0.109 | 0.131 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F2 N2 APARTMENT | 1363.51 | 1636.21 | 0.108 | 0.130 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F2 S1 APARTMENT | 1893.98 | 2272.77 | 0.150 | 0.180 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F2 S2 APARTMENT | 1918.49 | 2302.18 | 0.152 | 0.182 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F3 SW APARTMENT | 2918.01 | 3501.61 | 0.231 | 0.278 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
F3 NW APARTMENT | 2638.46 | 3166.15 | 0.209 | 0.251 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F3 SE APARTMENT | 2660.48 | 3192.58 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
F3 NE APARTMENT | 2009.68 | 2411.61 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
F3 N1 APARTMENT | 1423.80 | 1708.56 | 0.113 | 0.135 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F3 N2 APARTMENT | 1409.56 | 1691.48 | 0.112 | 0.134 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F3 S1 APARTMENT | 1937.91 | 2325.50 | 0.154 | 0.184 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F3 S2 APARTMENT | 1949.09 | 2338.91 | 0.154 | 0.185 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F4 SW APARTMENT | 2934.65 | 3521.58 | 0.233 | 0.279 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.44 | 0.01255 |
F4 NW APARTMENT | 2656.05 | 3187.26 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F4 SE APARTMENT | 2656.04 | 3187.24 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
F4 NE APARTMENT | 2019.33 | 2423.20 | 0.160 | 0.192 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
F4 N1 APARTMENT | 1441.76 | 1730.11 | 0.114 | 0.137 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F4 N2 APARTMENT | 1427.54 | 1713.05 | 0.113 | 0.136 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F4 S1 APARTMENT | 1953.46 | 2344.15 | 0.155 | 0.186 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F4 S2 APARTMENT | 1962.68 | 2355.22 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
M SW APARTMENT | 2968.19 | 3561.83 | 0.235 | 0.282 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.44 | 0.01255 |
M NW APARTMENT | 2690.58 | 3228.70 | 0.213 | 0.256 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
M SE APARTMENT | 2687.31 | 3224.77 | 0.213 | 0.256 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
M NE APARTMENT | 2046.84 | 2456.21 | 0.162 | 0.195 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
M N1 APARTMENT | 1474.84 | 1769.81 | 0.117 | 0.140 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
M N2 APARTMENT | 1460.65 | 1752.78 | 0.116 | 0.139 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
M S1 APARTMENT | 1984.87 | 2381.84 | 0.157 | 0.189 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
M S2 APARTMENT | 1993.78 | 2392.54 | 0.158 | 0.190 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F6 SW APARTMENT | 2941.58 | 3529.89 | 0.233 | 0.280 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.44 | 0.01255 |
F6 NW APARTMENT | 2663.47 | 3196.16 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F6 SE APARTMENT | 2661.18 | 3193.41 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
F6 NE APARTMENT | 2014.95 | 2417.94 | 0.160 | 0.192 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
F6 N1 APARTMENT | 1449.42 | 1739.31 | 0.115 | 0.138 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F6 N2 APARTMENT | 1435.33 | 1722.39 | 0.114 | 0.137 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F6 S1 APARTMENT | 1957.27 | 2348.72 | 0.155 | 0.186 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F6 S2 APARTMENT | 1966.12 | 2359.34 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F7 SW APARTMENT | 2935.97 | 3523.16 | 0.233 | 0.279 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.44 | 0.01255 |
F7 NW APARTMENT | 2658.08 | 3189.69 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F7 SE APARTMENT | 2656.17 | 3187.41 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F7 NE APARTMENT | 2004.92 | 2405.90 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
F7 N1 APARTMENT | 1444.48 | 1733.38 | 0.114 | 0.137 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F7 N2 APARTMENT | 1430.45 | 1716.54 | 0.113 | 0.136 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F7 S1 APARTMENT | 1950.38 | 2340.46 | 0.155 | 0.185 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F7 S2 APARTMENT | 1959.19 | 2351.03 | 0.155 | 0.186 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F8 SW APARTMENT | 2942.45 | 3530.94 | 0.233 | 0.280 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 30.44 | 0.01255 |
F8 NW APARTMENT | 2665.20 | 3198.24 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F8 SE APARTMENT | 2662.94 | 3195.53 | 0.211 | 0.253 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F8 NE APARTMENT | 2006.91 | 2408.29 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
F8 N1 APARTMENT | 1452.04 | 1742.45 | 0.115 | 0.138 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F8 N2 APARTMENT | 1438.08 | 1725.70 | 0.114 | 0.137 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F8 S1 APARTMENT | 1955.40 | 2346.48 | 0.155 | 0.186 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F8 S2 APARTMENT | 1964.20 | 2357.04 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F9 SW APARTMENT | 3034.59 | 3641.51 | 0.241 | 0.289 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
F9 NW APARTMENT | 2760.15 | 3312.18 | 0.219 | 0.263 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 29.00 | 0.01255 |
F9 SE APARTMENT | 2734.11 | 3280.93 | 0.217 | 0.260 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
F9 NE APARTMENT | 2041.45 | 2449.74 | 0.162 | 0.194 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 28.04 | 0.01255 |
F9 N1 APARTMENT | 1533.94 | 1840.73 | 0.122 | 0.146 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F9 N2 APARTMENT | 1519.72 | 1823.67 | 0.120 | 0.145 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
F9 S1 APARTMENT | 2014.42 | 2417.30 | 0.160 | 0.192 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.17 | 0.01255 |
F9 S2 APARTMENT | 2023.10 | 2427.72 | 0.160 | 0.192 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.17 | 0.01255 |
T SW APARTMENT | 3760.61 | 4512.73 | 0.298 | 0.358 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 31.14 | 0.01255 |
T NW APARTMENT | 3347.06 | 4016.47 | 0.265 | 0.318 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
T SE APARTMENT | 3393.70 | 4072.44 | 0.269 | 0.323 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
T NE APARTMENT | 2550.43 | 3060.52 | 0.202 | 0.243 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 31.30 | 0.01255 |
T N1 APARTMENT | 1962.57 | 2355.09 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.30 | 0.01255 |
T N2 APARTMENT | 1960.45 | 2352.54 | 0.155 | 0.186 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.30 | 0.01255 |
T S1 APARTMENT | 2777.04 | 3332.45 | 0.220 | 0.264 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
T S2 APARTMENT | 2785.39 | 3342.47 | 0.221 | 0.265 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2894.61 | 3473.53 | 0.130 | 0.156 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G NW APARTMENT | 2895.70 | 3474.84 | 0.130 | 0.156 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
OFFICE | 3242.00 | 3890.40 | 0.146 | 0.175 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -22.40 | 0.00051 |
G NE APARTMENT | 2891.26 | 3469.52 | 0.130 | 0.156 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G N1 APARTMENT | 1979.82 | 2375.79 | 0.089 | 0.107 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G N2 APARTMENT | 1979.73 | 2375.67 | 0.089 | 0.107 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G S1 APARTMENT | 1976.58 | 2371.89 | 0.089 | 0.107 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G S2 APARTMENT | 1981.79 | 2378.15 | 0.089 | 0.107 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
F2 SW APARTMENT | 2762.90 | 3315.48 | 0.124 | 0.149 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 NW APARTMENT | 2757.34 | 3308.81 | 0.124 | 0.149 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 SE APARTMENT | 2775.14 | 3330.17 | 0.125 | 0.150 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 NE APARTMENT | 2754.28 | 3305.13 | 0.124 | 0.149 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 N1 APARTMENT | 1625.50 | 1950.60 | 0.073 | 0.088 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 N2 APARTMENT | 1625.43 | 1950.52 | 0.073 | 0.088 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 S1 APARTMENT | 1633.68 | 1960.42 | 0.074 | 0.088 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F2 S2 APARTMENT | 1634.55 | 1961.46 | 0.074 | 0.088 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 SW APARTMENT | 2806.40 | 3367.68 | 0.126 | 0.152 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 NW APARTMENT | 2805.37 | 3366.44 | 0.126 | 0.152 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 SE APARTMENT | 2806.63 | 3367.96 | 0.126 | 0.152 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 NE APARTMENT | 2804.04 | 3364.85 | 0.126 | 0.152 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 N1 APARTMENT | 1608.79 | 1930.54 | 0.072 | 0.087 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 N2 APARTMENT | 1608.76 | 1930.51 | 0.072 | 0.087 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 S1 APARTMENT | 1610.80 | 1932.96 | 0.073 | 0.087 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F3 S2 APARTMENT | 1610.91 | 1933.09 | 0.073 | 0.087 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 SW APARTMENT | 2909.47 | 3491.37 | 0.131 | 0.157 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 NW APARTMENT | 2911.33 | 3493.60 | 0.131 | 0.157 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 SE APARTMENT | 2909.72 | 3491.66 | 0.131 | 0.157 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 NE APARTMENT | 2911.43 | 3493.72 | 0.131 | 0.157 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 N1 APARTMENT | 1662.72 | 1995.27 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 N2 APARTMENT | 1662.72 | 1995.27 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 S1 APARTMENT | 1661.60 | 1993.92 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F4 S2 APARTMENT | 1661.62 | 1993.94 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M SW APARTMENT | 2988.08 | 3585.70 | 0.135 | 0.161 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M NW APARTMENT | 2991.09 | 3589.31 | 0.135 | 0.162 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M SE APARTMENT | 2989.39 | 3587.27 | 0.135 | 0.162 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M NE APARTMENT | 2992.39 | 3590.87 | 0.135 | 0.162 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M N1 APARTMENT | 1700.94 | 2041.12 | 0.077 | 0.092 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M N2 APARTMENT | 1700.97 | 2041.16 | 0.077 | 0.092 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M S1 APARTMENT | 1698.58 | 2038.29 | 0.076 | 0.092 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
M S2 APARTMENT | 1698.61 | 2038.33 | 0.076 | 0.092 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 SW APARTMENT | 3109.99 | 3731.98 | 0.140 | 0.168 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 NW APARTMENT | 3115.39 | 3738.47 | 0.140 | 0.168 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 SE APARTMENT | 3112.32 | 3734.78 | 0.140 | 0.168 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 NE APARTMENT | 3117.72 | 3741.27 | 0.140 | 0.168 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 N1 APARTMENT | 1787.91 | 2145.49 | 0.081 | 0.097 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 N2 APARTMENT | 1787.96 | 2145.55 | 0.081 | 0.097 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 S1 APARTMENT | 1783.15 | 2139.78 | 0.080 | 0.096 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F6 S2 APARTMENT | 1783.20 | 2139.85 | 0.080 | 0.096 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 SW APARTMENT | 3203.55 | 3844.26 | 0.144 | 0.173 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 NW APARTMENT | 3210.18 | 3852.21 | 0.145 | 0.173 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 SE APARTMENT | 3206.79 | 3848.15 | 0.144 | 0.173 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 NE APARTMENT | 3213.42 | 3856.10 | 0.145 | 0.174 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 N1 APARTMENT | 1850.77 | 2220.93 | 0.083 | 0.100 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 N2 APARTMENT | 1850.85 | 2221.02 | 0.083 | 0.100 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 S1 APARTMENT | 1844.79 | 2213.75 | 0.083 | 0.100 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F7 S2 APARTMENT | 1844.86 | 2213.83 | 0.083 | 0.100 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 SW APARTMENT | 3299.78 | 3959.73 | 0.149 | 0.178 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 NW APARTMENT | 3307.19 | 3968.63 | 0.149 | 0.179 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 SE APARTMENT | 3303.83 | 3964.59 | 0.149 | 0.178 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 NE APARTMENT | 3311.24 | 3973.49 | 0.149 | 0.179 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 N1 APARTMENT | 1919.36 | 2303.24 | 0.086 | 0.104 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 N2 APARTMENT | 1919.45 | 2303.35 | 0.086 | 0.104 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 S1 APARTMENT | 1912.59 | 2295.10 | 0.086 | 0.103 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F8 S2 APARTMENT | 1912.68 | 2295.21 | 0.086 | 0.103 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 SW APARTMENT | 3533.31 | 4239.97 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 NW APARTMENT | 3538.77 | 4246.53 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 SE APARTMENT | 3538.13 | 4245.76 | 0.159 | 0.191 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 NE APARTMENT | 3543.60 | 4252.32 | 0.160 | 0.191 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 N1 APARTMENT | 2116.12 | 2539.35 | 0.095 | 0.114 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 N2 APARTMENT | 2116.23 | 2539.48 | 0.095 | 0.114 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 S1 APARTMENT | 2110.92 | 2533.10 | 0.095 | 0.114 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
F9 S2 APARTMENT | 2111.02 | 2533.23 | 0.095 | 0.114 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T SW APARTMENT | 4317.41 | 5180.90 | 0.194 | 0.233 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T NW APARTMENT | 4330.43 | 5196.52 | 0.195 | 0.234 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T SE APARTMENT | 4322.48 | 5186.98 | 0.195 | 0.234 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T NE APARTMENT | 4335.50 | 5202.60 | 0.195 | 0.234 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T N1 APARTMENT | 2943.22 | 3531.87 | 0.133 | 0.159 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T N2 APARTMENT | 2943.35 | 3532.01 | 0.133 | 0.159 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T S1 APARTMENT | 2927.86 | 3513.43 | 0.132 | 0.158 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
T S2 APARTMENT | 2927.98 | 3513.57 | 0.132 | 0.158 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -22.40 | 0.00051 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.21 | 0.21 | 0.16 | 0.16 |
AIRLOOP G NW | 0.19 | 0.19 | 0.16 | 0.16 |
AIRLOOP OFFICE | 0.33 | 0.33 | 0.18 | 0.18 |
AIRLOOP G NE | 0.14 | 0.14 | 0.16 | 0.16 |
AIRLOOP G N1 | 0.09 | 0.09 | 0.11 | 0.11 |
AIRLOOP G N2 | 0.09 | 0.09 | 0.11 | 0.11 |
AIRLOOP G S1 | 0.13 | 0.13 | 0.11 | 0.11 |
AIRLOOP G S2 | 0.14 | 0.14 | 0.11 | 0.11 |
AIRLOOP F2 SW | 0.27 | 0.27 | 0.15 | 0.15 |
AIRLOOP F2 NW | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP F2 SE | 0.27 | 0.27 | 0.15 | 0.15 |
AIRLOOP F2 NE | 0.19 | 0.19 | 0.15 | 0.15 |
AIRLOOP F2 N1 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP F2 N2 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP F2 S1 | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP F2 S2 | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP F3 SW | 0.28 | 0.28 | 0.15 | 0.15 |
AIRLOOP F3 NW | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP F3 SE | 0.25 | 0.25 | 0.15 | 0.15 |
AIRLOOP F3 NE | 0.19 | 0.19 | 0.15 | 0.15 |
AIRLOOP F3 N1 | 0.14 | 0.14 | 0.09 | 0.09 |
AIRLOOP F3 N2 | 0.13 | 0.13 | 0.09 | 0.09 |
AIRLOOP F3 S1 | 0.18 | 0.18 | 0.09 | 0.09 |
AIRLOOP F3 S2 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F4 SW | 0.28 | 0.28 | 0.16 | 0.16 |
AIRLOOP F4 NW | 0.25 | 0.25 | 0.16 | 0.16 |
AIRLOOP F4 SE | 0.25 | 0.25 | 0.16 | 0.16 |
AIRLOOP F4 NE | 0.19 | 0.19 | 0.16 | 0.16 |
AIRLOOP F4 N1 | 0.14 | 0.14 | 0.09 | 0.09 |
AIRLOOP F4 N2 | 0.14 | 0.14 | 0.09 | 0.09 |
AIRLOOP F4 S1 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F4 S2 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP M SW | 0.28 | 0.28 | 0.16 | 0.16 |
AIRLOOP M NW | 0.26 | 0.26 | 0.16 | 0.16 |
AIRLOOP M SE | 0.26 | 0.26 | 0.16 | 0.16 |
AIRLOOP M NE | 0.19 | 0.19 | 0.16 | 0.16 |
AIRLOOP M N1 | 0.14 | 0.14 | 0.09 | 0.09 |
AIRLOOP M N2 | 0.14 | 0.14 | 0.09 | 0.09 |
AIRLOOP M S1 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP M S2 | 0.19 | 0.19 | 0.09 | 0.09 |
AIRLOOP F6 SW | 0.28 | 0.28 | 0.17 | 0.17 |
AIRLOOP F6 NW | 0.25 | 0.25 | 0.17 | 0.17 |
AIRLOOP F6 SE | 0.25 | 0.25 | 0.17 | 0.17 |
AIRLOOP F6 NE | 0.19 | 0.19 | 0.17 | 0.17 |
AIRLOOP F6 N1 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F6 N2 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F6 S1 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F6 S2 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F7 SW | 0.28 | 0.28 | 0.17 | 0.17 |
AIRLOOP F7 NW | 0.25 | 0.25 | 0.17 | 0.17 |
AIRLOOP F7 SE | 0.25 | 0.25 | 0.17 | 0.17 |
AIRLOOP F7 NE | 0.19 | 0.19 | 0.17 | 0.17 |
AIRLOOP F7 N1 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F7 N2 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F7 S1 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F7 S2 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F8 SW | 0.28 | 0.28 | 0.18 | 0.18 |
AIRLOOP F8 NW | 0.25 | 0.25 | 0.18 | 0.18 |
AIRLOOP F8 SE | 0.25 | 0.25 | 0.18 | 0.18 |
AIRLOOP F8 NE | 0.19 | 0.19 | 0.18 | 0.18 |
AIRLOOP F8 N1 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F8 N2 | 0.14 | 0.14 | 0.10 | 0.10 |
AIRLOOP F8 S1 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F8 S2 | 0.19 | 0.19 | 0.10 | 0.10 |
AIRLOOP F9 SW | 0.29 | 0.29 | 0.19 | 0.19 |
AIRLOOP F9 NW | 0.26 | 0.26 | 0.19 | 0.19 |
AIRLOOP F9 SE | 0.26 | 0.26 | 0.19 | 0.19 |
AIRLOOP F9 NE | 0.19 | 0.19 | 0.19 | 0.19 |
AIRLOOP F9 N1 | 0.15 | 0.15 | 0.11 | 0.11 |
AIRLOOP F9 N2 | 0.14 | 0.14 | 0.11 | 0.11 |
AIRLOOP F9 S1 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP F9 S2 | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP T SW | 0.36 | 0.36 | 0.23 | 0.23 |
AIRLOOP T NW | 0.32 | 0.32 | 0.23 | 0.23 |
AIRLOOP T SE | 0.32 | 0.32 | 0.23 | 0.23 |
AIRLOOP T NE | 0.24 | 0.24 | 0.23 | 0.23 |
AIRLOOP T N1 | 0.19 | 0.19 | 0.16 | 0.16 |
AIRLOOP T N2 | 0.19 | 0.19 | 0.16 | 0.16 |
AIRLOOP T S1 | 0.26 | 0.26 | 0.16 | 0.16 |
AIRLOOP T S2 | 0.26 | 0.26 | 0.16 | 0.16 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3334.25 | 6705.25 | 1880.75 |
G NW APARTMENT | 3739.00 | 7082.75 | 2542.75 |
OFFICE | 926.75 | 1131.25 | 114.75 |
G NE APARTMENT | 3773.00 | 7085.25 | 2538.75 |
G N1 APARTMENT | 2724.50 | 7334.00 | 1798.00 |
G N2 APARTMENT | 2730.25 | 7332.00 | 1798.50 |
G S1 APARTMENT | 2471.25 | 6880.75 | 1201.50 |
G S2 APARTMENT | 2486.25 | 6798.75 | 1162.25 |
F2 SW APARTMENT | 3212.00 | 5713.75 | 1033.50 |
F2 NW APARTMENT | 3439.75 | 6351.75 | 1551.75 |
F2 SE APARTMENT | 3308.75 | 5406.00 | 901.00 |
F2 NE APARTMENT | 3440.00 | 6412.50 | 1570.50 |
F2 N1 APARTMENT | 2519.25 | 6608.25 | 900.75 |
F2 N2 APARTMENT | 2518.25 | 6613.50 | 902.50 |
F2 S1 APARTMENT | 2604.75 | 5786.75 | 574.50 |
F2 S2 APARTMENT | 2628.25 | 5735.25 | 569.25 |
F3 SW APARTMENT | 3226.25 | 5529.25 | 958.50 |
F3 NW APARTMENT | 3425.50 | 6226.00 | 1460.25 |
F3 SE APARTMENT | 3273.50 | 5477.00 | 937.25 |
F3 NE APARTMENT | 3416.00 | 6279.75 | 1474.75 |
F3 N1 APARTMENT | 2527.75 | 6441.25 | 790.50 |
F3 N2 APARTMENT | 2523.50 | 6451.00 | 790.25 |
F3 S1 APARTMENT | 2724.75 | 5475.25 | 522.50 |
F3 S2 APARTMENT | 2733.00 | 5454.25 | 520.50 |
F4 SW APARTMENT | 3256.00 | 5517.75 | 977.25 |
F4 NW APARTMENT | 3461.75 | 6197.50 | 1487.25 |
F4 SE APARTMENT | 3280.25 | 5519.50 | 970.75 |
F4 NE APARTMENT | 3442.25 | 6262.00 | 1502.50 |
F4 N1 APARTMENT | 2563.50 | 6374.50 | 793.00 |
F4 N2 APARTMENT | 2558.00 | 6383.75 | 791.25 |
F4 S1 APARTMENT | 2762.00 | 5401.25 | 517.75 |
F4 S2 APARTMENT | 2766.25 | 5393.75 | 518.50 |
M SW APARTMENT | 3239.00 | 5556.25 | 975.25 |
M NW APARTMENT | 3452.75 | 6208.50 | 1480.00 |
M SE APARTMENT | 3256.50 | 5560.00 | 968.00 |
M NE APARTMENT | 3427.00 | 6281.25 | 1492.00 |
M N1 APARTMENT | 2564.50 | 6361.50 | 777.75 |
M N2 APARTMENT | 2557.25 | 6371.75 | 776.25 |
M S1 APARTMENT | 2753.00 | 5416.00 | 511.00 |
M S2 APARTMENT | 2755.00 | 5413.75 | 511.75 |
F6 SW APARTMENT | 3204.75 | 5735.25 | 1056.75 |
F6 NW APARTMENT | 3471.00 | 6349.75 | 1601.50 |
F6 SE APARTMENT | 3226.25 | 5750.75 | 1050.00 |
F6 NE APARTMENT | 3462.25 | 6419.00 | 1623.25 |
F6 N1 APARTMENT | 2547.00 | 6498.25 | 870.25 |
F6 N2 APARTMENT | 2545.50 | 6507.25 | 871.00 |
F6 S1 APARTMENT | 2653.25 | 5615.25 | 554.25 |
F6 S2 APARTMENT | 2655.00 | 5615.75 | 553.75 |
F7 SW APARTMENT | 3178.50 | 5872.25 | 1112.00 |
F7 NW APARTMENT | 3486.25 | 6432.00 | 1682.00 |
F7 SE APARTMENT | 3204.75 | 5880.75 | 1107.00 |
F7 NE APARTMENT | 3479.75 | 6515.75 | 1702.50 |
F7 N1 APARTMENT | 2540.00 | 6586.75 | 923.75 |
F7 N2 APARTMENT | 2538.00 | 6596.00 | 925.00 |
F7 S1 APARTMENT | 2594.00 | 5762.00 | 579.00 |
F7 S2 APARTMENT | 2594.50 | 5757.75 | 579.25 |
F8 SW APARTMENT | 3168.25 | 5997.50 | 1166.00 |
F8 NW APARTMENT | 3512.75 | 6504.00 | 1762.75 |
F8 SE APARTMENT | 3200.25 | 5991.50 | 1170.25 |
F8 NE APARTMENT | 3509.75 | 6592.50 | 1778.50 |
F8 N1 APARTMENT | 2543.75 | 6652.75 | 975.50 |
F8 N2 APARTMENT | 2539.25 | 6665.25 | 977.25 |
F8 S1 APARTMENT | 2548.25 | 5888.00 | 604.00 |
F8 S2 APARTMENT | 2548.00 | 5886.00 | 603.75 |
F9 SW APARTMENT | 3301.50 | 6097.50 | 1360.00 |
F9 NW APARTMENT | 3684.25 | 6551.25 | 1984.50 |
F9 SE APARTMENT | 3327.75 | 6091.50 | 1359.00 |
F9 NE APARTMENT | 3697.25 | 6648.25 | 2006.25 |
F9 N1 APARTMENT | 2663.00 | 6720.50 | 1128.75 |
F9 N2 APARTMENT | 2660.50 | 6737.50 | 1131.00 |
F9 S1 APARTMENT | 2595.00 | 6045.50 | 727.25 |
F9 S2 APARTMENT | 2598.00 | 6046.25 | 728.00 |
T SW APARTMENT | 4297.50 | 6285.50 | 2485.25 |
T NW APARTMENT | 4564.50 | 6759.50 | 3044.50 |
T SE APARTMENT | 4357.50 | 6309.00 | 2504.25 |
T NE APARTMENT | 4575.75 | 6842.75 | 3070.25 |
T N1 APARTMENT | 3761.75 | 6902.00 | 2367.00 |
T N2 APARTMENT | 3761.00 | 6909.75 | 2368.25 |
T S1 APARTMENT | 3518.25 | 6215.00 | 1752.50 |
T S2 APARTMENT | 3530.00 | 6213.25 | 1753.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5789.75 | 7507.25 | 3353.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.50 | 7.00 | 3.50 | 7.00 |
G NW APARTMENT | 1.00 | 8.75 | 1.00 | 8.75 |
OFFICE | 3.00 | 0.00 | 0.50 | 0.00 |
G NE APARTMENT | 4.00 | 6.00 | 4.00 | 6.00 |
G N1 APARTMENT | 5.25 | 13.75 | 5.25 | 13.75 |
G N2 APARTMENT | 5.50 | 12.75 | 5.50 | 12.75 |
G S1 APARTMENT | 2.75 | 20.25 | 2.75 | 20.25 |
G S2 APARTMENT | 2.75 | 18.75 | 2.75 | 18.75 |
F2 SW APARTMENT | 1.50 | 7.50 | 1.50 | 7.50 |
F2 NW APARTMENT | 1.75 | 7.75 | 1.75 | 7.75 |
F2 SE APARTMENT | 1.50 | 6.00 | 1.50 | 6.00 |
F2 NE APARTMENT | 1.75 | 50.50 | 1.75 | 50.50 |
F2 N1 APARTMENT | 1.50 | 42.25 | 1.50 | 42.25 |
F2 N2 APARTMENT | 3.00 | 43.75 | 3.00 | 43.75 |
F2 S1 APARTMENT | 2.75 | 18.75 | 2.75 | 18.75 |
F2 S2 APARTMENT | 2.75 | 17.75 | 2.75 | 17.75 |
F3 SW APARTMENT | 0.25 | 10.25 | 0.25 | 10.25 |
F3 NW APARTMENT | 0.50 | 10.00 | 0.50 | 10.00 |
F3 SE APARTMENT | 1.00 | 20.75 | 1.00 | 20.75 |
F3 NE APARTMENT | 0.75 | 61.75 | 0.75 | 61.75 |
F3 N1 APARTMENT | 2.25 | 56.50 | 2.25 | 56.50 |
F3 N2 APARTMENT | 4.50 | 63.25 | 4.50 | 63.25 |
F3 S1 APARTMENT | 5.75 | 29.00 | 5.75 | 29.00 |
F3 S2 APARTMENT | 5.00 | 28.00 | 5.00 | 28.00 |
F4 SW APARTMENT | 1.00 | 11.25 | 1.00 | 11.25 |
F4 NW APARTMENT | 0.25 | 11.50 | 0.25 | 11.50 |
F4 SE APARTMENT | 0.00 | 23.50 | 0.00 | 23.50 |
F4 NE APARTMENT | 1.50 | 66.00 | 1.50 | 66.00 |
F4 N1 APARTMENT | 4.25 | 59.25 | 4.25 | 59.25 |
F4 N2 APARTMENT | 4.25 | 67.75 | 4.25 | 67.75 |
F4 S1 APARTMENT | 3.75 | 31.50 | 3.75 | 31.50 |
F4 S2 APARTMENT | 2.50 | 30.25 | 2.50 | 30.25 |
M SW APARTMENT | 1.25 | 12.25 | 1.25 | 12.25 |
M NW APARTMENT | 1.25 | 12.25 | 1.25 | 12.25 |
M SE APARTMENT | 1.00 | 24.75 | 1.00 | 24.75 |
M NE APARTMENT | 1.50 | 68.50 | 1.50 | 68.50 |
M N1 APARTMENT | 2.75 | 61.00 | 2.75 | 61.00 |
M N2 APARTMENT | 3.50 | 70.00 | 3.50 | 70.00 |
M S1 APARTMENT | 2.50 | 33.50 | 2.50 | 33.50 |
M S2 APARTMENT | 2.00 | 33.50 | 2.00 | 33.50 |
F6 SW APARTMENT | 1.25 | 12.25 | 1.25 | 12.25 |
F6 NW APARTMENT | 1.25 | 13.75 | 1.25 | 13.75 |
F6 SE APARTMENT | 0.50 | 25.00 | 0.50 | 25.00 |
F6 NE APARTMENT | 1.25 | 69.50 | 1.25 | 69.50 |
F6 N1 APARTMENT | 2.75 | 62.25 | 2.75 | 62.25 |
F6 N2 APARTMENT | 3.25 | 71.75 | 3.25 | 71.75 |
F6 S1 APARTMENT | 3.25 | 34.25 | 3.25 | 34.25 |
F6 S2 APARTMENT | 3.50 | 33.50 | 3.50 | 33.50 |
F7 SW APARTMENT | 1.00 | 13.25 | 1.00 | 13.25 |
F7 NW APARTMENT | 0.75 | 14.25 | 0.75 | 14.25 |
F7 SE APARTMENT | 1.00 | 25.00 | 1.00 | 25.00 |
F7 NE APARTMENT | 1.75 | 70.50 | 1.75 | 70.50 |
F7 N1 APARTMENT | 1.75 | 63.50 | 1.75 | 63.50 |
F7 N2 APARTMENT | 2.75 | 73.25 | 2.75 | 73.25 |
F7 S1 APARTMENT | 2.75 | 34.25 | 2.75 | 34.25 |
F7 S2 APARTMENT | 3.00 | 34.50 | 3.00 | 34.50 |
F8 SW APARTMENT | 0.75 | 13.25 | 0.75 | 13.25 |
F8 NW APARTMENT | 0.50 | 15.00 | 0.50 | 15.00 |
F8 SE APARTMENT | 1.75 | 25.50 | 1.75 | 25.50 |
F8 NE APARTMENT | 1.50 | 72.00 | 1.50 | 72.00 |
F8 N1 APARTMENT | 1.00 | 64.25 | 1.00 | 64.25 |
F8 N2 APARTMENT | 2.00 | 72.50 | 2.00 | 72.50 |
F8 S1 APARTMENT | 2.50 | 35.25 | 2.50 | 35.25 |
F8 S2 APARTMENT | 3.00 | 35.00 | 3.00 | 35.00 |
F9 SW APARTMENT | 0.50 | 13.50 | 0.50 | 13.50 |
F9 NW APARTMENT | 0.50 | 13.75 | 0.50 | 13.75 |
F9 SE APARTMENT | 0.25 | 24.25 | 0.25 | 24.25 |
F9 NE APARTMENT | 1.00 | 73.75 | 1.00 | 73.75 |
F9 N1 APARTMENT | 1.75 | 57.50 | 1.75 | 57.50 |
F9 N2 APARTMENT | 3.25 | 63.25 | 3.25 | 63.25 |
F9 S1 APARTMENT | 3.00 | 34.75 | 3.00 | 34.75 |
F9 S2 APARTMENT | 2.75 | 34.50 | 2.75 | 34.50 |
T SW APARTMENT | 0.00 | 8.50 | 0.00 | 8.50 |
T NW APARTMENT | 0.00 | 12.25 | 0.00 | 12.25 |
T SE APARTMENT | 0.50 | 19.50 | 0.50 | 19.50 |
T NE APARTMENT | 0.00 | 49.00 | 0.00 | 49.00 |
T N1 APARTMENT | 0.75 | 41.50 | 0.75 | 41.50 |
T N2 APARTMENT | 1.00 | 44.50 | 1.00 | 44.50 |
T S1 APARTMENT | 0.75 | 17.75 | 0.75 | 17.75 |
T S2 APARTMENT | 0.75 | 17.50 | 0.75 | 17.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 122.75 | 100.50 | 120.25 | 100.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.192 | 0.000 | 0.308 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.192 | 0.000 | 0.281 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.519 | 0.220 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.192 | 0.000 | 0.282 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.116 | 0.000 | 0.275 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.116 | 0.000 | 0.275 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.116 | 0.000 | 0.304 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.116 | 0.000 | 0.305 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.276 | 0.000 | 0.363 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.276 | 0.000 | 0.322 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.276 | 0.000 | 0.366 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.276 | 0.000 | 0.322 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.166 | 0.000 | 0.317 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.166 | 0.000 | 0.317 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.167 | 0.000 | 0.361 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.167 | 0.000 | 0.361 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.327 | 0.000 | 0.402 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.327 | 0.000 | 0.350 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.327 | 0.000 | 0.403 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.327 | 0.000 | 0.350 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.197 | 0.000 | 0.346 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.197 | 0.000 | 0.346 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.197 | 0.000 | 0.400 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.197 | 0.000 | 0.400 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.365 | 0.000 | 0.415 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.365 | 0.000 | 0.358 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.365 | 0.000 | 0.416 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.365 | 0.000 | 0.358 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.220 | 0.000 | 0.354 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.220 | 0.000 | 0.354 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.220 | 0.000 | 0.414 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.220 | 0.000 | 0.414 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.397 | 0.000 | 0.437 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.397 | 0.000 | 0.373 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.397 | 0.000 | 0.437 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.397 | 0.000 | 0.373 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.239 | 0.000 | 0.370 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.239 | 0.000 | 0.370 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.239 | 0.000 | 0.435 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.239 | 0.000 | 0.435 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.424 | 0.000 | 0.455 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.424 | 0.000 | 0.386 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.424 | 0.000 | 0.455 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.424 | 0.000 | 0.386 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.256 | 0.000 | 0.382 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.256 | 0.000 | 0.382 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.256 | 0.000 | 0.453 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.256 | 0.000 | 0.453 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.448 | 0.000 | 0.470 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.448 | 0.000 | 0.397 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.448 | 0.000 | 0.471 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.448 | 0.000 | 0.397 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.270 | 0.000 | 0.393 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.270 | 0.000 | 0.393 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.270 | 0.000 | 0.468 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.270 | 0.000 | 0.468 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.470 | 0.000 | 0.485 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.469 | 0.000 | 0.408 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.470 | 0.000 | 0.486 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.469 | 0.000 | 0.408 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.283 | 0.000 | 0.404 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.283 | 0.000 | 0.404 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.283 | 0.000 | 0.483 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.283 | 0.000 | 0.483 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.490 | 0.000 | 0.500 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.489 | 0.000 | 0.419 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.489 | 0.000 | 0.501 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.489 | 0.000 | 0.419 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.295 | 0.000 | 0.415 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.295 | 0.000 | 0.415 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.295 | 0.000 | 0.498 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.295 | 0.000 | 0.498 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.508 | 0.000 | 0.511 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.507 | 0.000 | 0.427 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.508 | 0.000 | 0.511 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.507 | 0.000 | 0.427 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.306 | 0.000 | 0.424 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.306 | 0.000 | 0.424 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.306 | 0.000 | 0.509 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.306 | 0.000 | 0.510 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.500 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 605.54 | 19201.55 | 01-JAN-00:15 | 19201.55 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1274.21 | 19862.80 | 06-MAY-02:15 | 119522.29 | 07-FEB-02:00 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
ElectricityPurchased:Plant | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
Cogeneration:ElectricityPurchased | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
ElectricityNet:Plant | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
Cogeneration:ElectricityNet | 2945.25 | 53915.77 | 24-JUN-04:15 | 189762.54 | 07-FEB-18:00 |
ExteriorLights:Electricity | 162.69 | 0.00 | 01-JAN-07:45 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.69 | 0.00 | 01-JAN-07:45 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 605.54 | 19201.55 | 01-JAN-00:15 | 19201.55 | 01-JAN-00:15 |
Cooling:Electricity | 230.30 | 0.00 | 01-JAN-00:15 | 77321.23 | 16-JUN-14:15 |
Heating:Electricity | 402.19 | 0.00 | 28-MAR-16:15 | 99626.45 | 07-FEB-02:00 |
Electricity:Plant | 74.46 | 36.93 | 11-APR-18:30 | 5168.12 | 16-JUN-10:15 |
HeatRejection:Electricity | 10.13 | 0.00 | 01-JAN-00:15 | 3088.25 | 16-JUN-10:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 64.33 | 36.93 | 11-APR-18:30 | 2079.88 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 2799.92 | 2357.00 | 17-MAR-23:30 | 372607.72 | 24-JAN-07:30 |
Gas:Plant | 2799.92 | 2357.00 | 17-MAR-23:30 | 372607.72 | 24-JAN-07:30 |
WaterSystems:Gas | 1241.86 | 2357.00 | 01-JAN-00:15 | 85459.07 | 18-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1241.86 | 2357.00 | 01-JAN-00:15 | 85459.07 | 18-FEB-08:00 |
Heating:Gas | 1558.07 | 0.00 | 17-MAR-11:45 | 295852.49 | 27-JAN-07:15 |
Boiler:Heating:Gas | 1558.07 | 0.00 | 17-MAR-11:45 | 295852.49 | 27-JAN-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 972.24 | 0.00 | 01-JAN-00:15 | 381335.90 | 04-AUG-15:30 |
PlantLoopCoolingDemand:HVAC | 972.24 | 0.00 | 01-JAN-00:15 | 381335.90 | 04-AUG-15:30 |
CoolingCoils:PlantLoopCoolingDemand | 972.24 | 0.00 | 01-JAN-00:15 | 381335.90 | 04-AUG-15:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 5471.28 | 0.00 | 01-JAN-02:15 | 0.00 | 20-JUL-17:15 |
Water:Plant | 5471.28 | 0.00 | 01-JAN-02:15 | 0.00 | 20-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 5471.28 | 0.00 | 01-JAN-02:15 | 0.00 | 20-JUL-17:15 |
MainsWater:Plant | 5471.28 | 0.00 | 01-JAN-02:15 | 0.00 | 20-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 692.77 | 0.00 | 01-JAN-00:15 | 0.00 | 20-JUL-16:00 |
HeatRejection:MainsWater | 692.77 | 0.00 | 01-JAN-00:15 | 0.00 | 20-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 2178.07 | 503.62 | 11-AUG-01:15 | 288976.62 | 27-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 967.69 | 503.62 | 11-AUG-01:15 | 65723.37 | 19-FEB-07:30 |
WaterSystems:PlantLoopHeatingDemand | 967.69 | 503.62 | 11-AUG-01:15 | 65723.37 | 19-FEB-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 6107.63 | 4973.91 | 27-SEP-03:00 | 815780.51 | 17-DEC-08:30 |
EnergyTransfer:Building | 1634.86 | 3012.22 | 27-MAY-13:30 | 252506.43 | 07-MAR-14:00 |
EnergyTransfer:Zone:G SW APARTMENT | 18.03 | 0.10 | 12-AUG-14:45 | 2638.98 | 17-DEC-08:30 |
Heating:EnergyTransfer | 1037.82 | 0.00 | 17-MAR-15:15 | 252506.43 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 12.23 | 0.00 | 01-JAN-11:30 | 2638.98 | 17-DEC-08:30 |
Cooling:EnergyTransfer | 597.04 | 0.00 | 01-JAN-00:15 | 179906.83 | 29-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 5.80 | 0.00 | 01-JAN-00:15 | 2540.47 | 13-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 19.70 | 0.18 | 31-AUG-08:30 | 3010.13 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 15.59 | 0.00 | 18-FEB-15:00 | 3010.13 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.11 | 0.00 | 01-JAN-00:15 | 2162.61 | 05-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 23.39 | 0.02 | 04-OCT-02:00 | 3517.62 | 20-JUL-13:00 |
Heating:EnergyTransfer:Zone:OFFICE | 9.31 | 0.00 | 01-JAN-11:30 | 2656.40 | 17-DEC-08:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 14.08 | 0.00 | 01-JAN-00:15 | 3517.62 | 20-JUL-13:00 |
EnergyTransfer:Zone:G NE APARTMENT | 19.37 | 0.00 | 25-OCT-13:00 | 2769.58 | 07-FEB-18:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 15.36 | 0.00 | 17-MAR-08:00 | 2769.58 | 07-FEB-18:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.01 | 0.00 | 01-JAN-00:15 | 1632.63 | 15-JUL-09:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 12.64 | 0.03 | 28-APR-13:30 | 2033.85 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 9.13 | 0.00 | 01-FEB-19:45 | 2033.85 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.51 | 0.00 | 01-JAN-00:15 | 1284.84 | 01-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 12.63 | 0.03 | 21-AUG-06:00 | 2030.20 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 9.13 | 0.00 | 01-FEB-19:45 | 2030.20 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.50 | 0.00 | 01-JAN-00:15 | 1261.70 | 01-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.56 | 0.00 | 30-MAY-20:45 | 1673.07 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 5.92 | 0.00 | 01-JAN-11:00 | 1610.45 | 17-DEC-08:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 5.64 | 0.00 | 01-JAN-00:15 | 1673.07 | 01-AUG-13:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.54 | 0.00 | 03-JUN-09:30 | 1742.11 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 5.71 | 0.00 | 01-JAN-11:00 | 1602.77 | 17-DEC-08:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 5.82 | 0.00 | 01-JAN-00:15 | 1742.11 | 01-AUG-13:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 20.93 | 0.01 | 12-MAY-09:15 | 3195.97 | 13-SEP-15:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 11.34 | 0.00 | 01-JAN-11:15 | 2967.02 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 9.59 | 0.00 | 01-JAN-00:15 | 3195.97 | 13-SEP-15:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 21.99 | 0.01 | 27-APR-23:15 | 3258.06 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 15.31 | 0.00 | 01-FEB-19:45 | 3258.06 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 6.67 | 0.00 | 01-JAN-00:15 | 2791.95 | 01-JUL-18:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 21.01 | 0.05 | 09-APR-22:00 | 2931.23 | 02-SEP-12:45 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 10.42 | 0.00 | 01-JAN-11:00 | 2843.52 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 10.59 | 0.00 | 01-JAN-00:15 | 2931.23 | 02-SEP-12:45 |
EnergyTransfer:Zone:F2 NE APARTMENT | 21.78 | 0.01 | 23-OCT-23:00 | 3215.77 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 15.06 | 0.00 | 01-FEB-19:45 | 3215.77 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 6.72 | 0.00 | 01-JAN-00:15 | 2112.00 | 29-JUL-16:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 12.96 | 0.00 | 25-AUG-16:00 | 1877.68 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 7.22 | 0.00 | 15-JAN-23:00 | 1877.68 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 5.74 | 0.00 | 01-JAN-00:15 | 1731.29 | 01-JUL-18:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 12.96 | 0.00 | 04-JUN-15:15 | 1875.26 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 7.22 | 0.00 | 15-JAN-23:00 | 1875.26 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 5.74 | 0.00 | 01-JAN-00:15 | 1714.21 | 01-JUL-18:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 13.45 | 0.00 | 30-MAY-10:45 | 2238.03 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 4.33 | 0.00 | 01-JAN-10:00 | 1613.66 | 25-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 9.13 | 0.00 | 01-JAN-00:15 | 2238.03 | 01-AUG-13:45 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 13.51 | 0.04 | 01-JUN-11:00 | 2262.31 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 4.29 | 0.00 | 01-JAN-10:15 | 1608.63 | 25-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 9.22 | 0.00 | 01-JAN-00:15 | 2262.31 | 01-AUG-13:45 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 22.04 | 0.07 | 03-FEB-16:30 | 3254.22 | 13-SEP-15:15 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 12.00 | 0.00 | 01-JAN-11:15 | 3234.12 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 10.04 | 0.00 | 01-JAN-00:15 | 3254.22 | 13-SEP-15:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 23.15 | 0.01 | 28-APR-01:30 | 3510.44 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 16.05 | 0.00 | 01-FEB-19:45 | 3510.44 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 7.10 | 0.00 | 01-JAN-00:15 | 2863.07 | 01-JUL-18:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 21.92 | 0.01 | 11-DEC-20:15 | 3199.78 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 11.75 | 0.00 | 01-JAN-11:00 | 3199.78 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 10.17 | 0.00 | 01-JAN-00:15 | 2881.02 | 29-JUL-15:45 |
EnergyTransfer:Zone:F3 NE APARTMENT | 22.93 | 0.05 | 26-JUN-12:45 | 3479.29 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 15.80 | 0.00 | 01-FEB-19:45 | 3479.29 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 7.12 | 0.00 | 01-JAN-00:15 | 2189.14 | 29-JUL-15:45 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 13.54 | 0.01 | 10-NOV-20:00 | 2007.15 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 7.26 | 0.00 | 10-JAN-19:00 | 2007.15 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 6.28 | 0.00 | 01-JAN-00:15 | 1801.63 | 01-JUL-18:30 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 13.54 | 0.01 | 27-NOV-17:30 | 2003.87 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 7.26 | 0.00 | 10-JAN-19:00 | 2003.87 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 6.28 | 0.00 | 01-JAN-00:15 | 1784.67 | 01-JUL-18:30 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 14.27 | 0.01 | 21-APR-06:00 | 2303.17 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 4.41 | 0.00 | 01-JAN-09:45 | 1739.93 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 9.86 | 0.00 | 01-JAN-00:15 | 2303.17 | 01-AUG-13:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 14.29 | 0.05 | 22-MAY-14:45 | 2313.89 | 01-AUG-13:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 4.40 | 0.00 | 01-JAN-09:45 | 1736.43 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 9.89 | 0.00 | 01-JAN-00:15 | 2313.89 | 01-AUG-13:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 22.96 | 0.01 | 25-MAR-21:30 | 3558.81 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 13.03 | 0.00 | 01-JAN-11:15 | 3558.81 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 9.93 | 0.00 | 01-JAN-00:15 | 3281.98 | 01-AUG-17:00 |
EnergyTransfer:Zone:F4 NW APARTMENT | 24.27 | 0.03 | 25-SEP-19:00 | 3836.90 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 17.19 | 0.00 | 01-FEB-19:45 | 3836.90 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 7.08 | 0.00 | 01-JAN-00:15 | 2903.71 | 01-JUL-18:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 22.83 | 0.01 | 04-OCT-02:30 | 3529.88 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 12.89 | 0.00 | 01-JAN-11:15 | 3529.88 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 9.94 | 0.00 | 01-JAN-00:15 | 2909.09 | 29-JUL-15:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 24.05 | 0.01 | 29-OCT-15:30 | 3805.46 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 16.93 | 0.00 | 01-FEB-19:45 | 3805.46 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 7.12 | 0.00 | 01-JAN-00:15 | 2223.13 | 29-JUL-15:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 14.12 | 0.00 | 24-MAY-10:15 | 2194.74 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 7.78 | 0.00 | 14-JAN-19:00 | 2194.74 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 6.35 | 0.00 | 01-JAN-00:15 | 1838.46 | 01-JUL-18:45 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 14.12 | 0.00 | 22-AUG-20:00 | 2191.48 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 7.78 | 0.00 | 14-JAN-19:00 | 2191.48 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 6.34 | 0.00 | 01-JAN-00:15 | 1817.90 | 01-JUL-18:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 14.74 | 0.06 | 19-MAY-18:00 | 2349.63 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 4.85 | 0.00 | 01-JAN-09:45 | 1926.27 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 9.89 | 0.00 | 01-JAN-00:15 | 2349.63 | 19-AUG-13:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 14.75 | 0.06 | 14-MAR-17:15 | 2358.51 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 4.85 | 0.00 | 01-JAN-09:45 | 1923.33 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 9.90 | 0.00 | 01-JAN-00:15 | 2358.51 | 19-AUG-13:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 23.71 | 0.02 | 15-JUN-11:30 | 3821.03 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 13.88 | 0.00 | 01-JAN-11:15 | 3821.03 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 9.84 | 0.00 | 01-JAN-00:15 | 3331.85 | 01-AUG-17:00 |
EnergyTransfer:Zone:M NW APARTMENT | 25.18 | 0.01 | 28-APR-04:30 | 4097.68 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 18.07 | 0.00 | 01-FEB-19:45 | 4097.68 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 7.11 | 0.00 | 01-JAN-00:15 | 2955.34 | 01-JUL-18:30 |
EnergyTransfer:Zone:M SE APARTMENT | 23.57 | 0.05 | 14-DEC-13:45 | 3792.48 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 13.75 | 0.00 | 01-JAN-11:15 | 3792.48 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 9.82 | 0.00 | 01-JAN-00:15 | 2952.55 | 29-JUL-15:30 |
EnergyTransfer:Zone:M NE APARTMENT | 24.93 | 0.04 | 15-JUN-02:15 | 4066.05 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 17.80 | 0.00 | 01-FEB-19:45 | 4066.05 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 7.13 | 0.00 | 01-JAN-00:15 | 2261.35 | 29-JUL-15:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 14.59 | 0.01 | 02-JUN-20:15 | 2343.18 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 8.17 | 0.00 | 14-JAN-19:00 | 2343.18 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 6.42 | 0.00 | 01-JAN-00:15 | 1891.15 | 01-JUL-18:45 |
EnergyTransfer:Zone:M N2 APARTMENT | 14.59 | 0.01 | 13-JUN-09:45 | 2339.94 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 8.17 | 0.00 | 14-JAN-19:00 | 2339.94 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 6.42 | 0.00 | 01-JAN-00:15 | 1867.17 | 01-JUL-18:45 |
EnergyTransfer:Zone:M S1 APARTMENT | 15.10 | 0.01 | 11-SEP-16:00 | 2400.51 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 5.22 | 0.00 | 01-JAN-09:45 | 2078.09 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 9.88 | 0.00 | 01-JAN-00:15 | 2400.51 | 19-AUG-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 15.10 | 0.01 | 01-JUL-05:45 | 2409.16 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 5.22 | 0.00 | 01-JAN-09:45 | 2075.30 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 9.88 | 0.00 | 01-JAN-00:15 | 2409.16 | 19-AUG-13:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 24.40 | 0.01 | 13-OCT-03:45 | 4091.68 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 15.23 | 0.00 | 01-JAN-11:30 | 4091.68 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 9.17 | 0.00 | 01-JAN-00:15 | 3316.66 | 01-AUG-17:00 |
EnergyTransfer:Zone:F6 NW APARTMENT | 26.24 | 0.00 | 16-OCT-12:30 | 4371.45 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 19.60 | 0.00 | 01-FEB-19:45 | 4371.45 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 6.64 | 0.00 | 01-JAN-00:15 | 2942.15 | 01-JUL-18:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 24.24 | 0.02 | 12-DEC-13:15 | 4062.71 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 15.09 | 0.00 | 01-JAN-11:15 | 4062.71 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 9.15 | 0.00 | 01-JAN-00:15 | 2933.49 | 29-JUL-15:30 |
EnergyTransfer:Zone:F6 NE APARTMENT | 25.94 | 0.01 | 02-NOV-15:00 | 4339.54 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 19.30 | 0.00 | 01-FEB-19:45 | 4339.54 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 6.64 | 0.00 | 01-JAN-00:15 | 2234.71 | 29-JUL-15:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 15.07 | 0.04 | 16-MAY-16:00 | 2518.32 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 9.12 | 0.00 | 14-JAN-22:45 | 2518.32 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 5.95 | 0.00 | 01-JAN-00:15 | 1884.97 | 01-JUL-18:45 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 15.07 | 0.02 | 10-JUL-09:30 | 2515.06 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 9.12 | 0.00 | 14-JAN-22:45 | 2515.06 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 5.95 | 0.00 | 01-JAN-00:15 | 1861.19 | 01-JUL-18:45 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 15.12 | 0.04 | 12-JUN-19:45 | 2383.39 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 5.94 | 0.00 | 01-JAN-10:00 | 2247.71 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 9.18 | 0.00 | 01-JAN-00:15 | 2383.39 | 19-AUG-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 15.12 | 0.01 | 25-DEC-17:15 | 2392.05 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 5.94 | 0.00 | 01-JAN-10:00 | 2244.81 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 9.18 | 0.00 | 01-JAN-00:15 | 2392.05 | 19-AUG-13:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 25.09 | 0.04 | 11-SEP-09:45 | 4320.36 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 16.33 | 0.00 | 01-JAN-11:30 | 4320.36 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 8.76 | 0.00 | 01-JAN-00:15 | 3321.52 | 01-AUG-17:00 |
EnergyTransfer:Zone:F7 NW APARTMENT | 27.16 | 0.01 | 17-MAY-10:45 | 4600.54 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 20.80 | 0.00 | 01-FEB-19:45 | 4600.54 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 6.36 | 0.00 | 01-JAN-00:15 | 2948.04 | 01-JUL-18:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 24.90 | 0.02 | 04-OCT-08:00 | 4291.18 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 16.18 | 0.00 | 01-JAN-11:30 | 4291.18 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 8.72 | 0.00 | 01-JAN-00:15 | 2936.21 | 29-JUL-15:30 |
EnergyTransfer:Zone:F7 NE APARTMENT | 26.84 | 0.08 | 14-OCT-02:30 | 4568.50 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 20.49 | 0.00 | 01-FEB-19:45 | 4568.50 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 6.35 | 0.00 | 01-JAN-00:15 | 2241.19 | 18-JUN-18:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 15.51 | 0.00 | 13-SEP-08:30 | 2661.59 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 9.85 | 0.00 | 14-JAN-23:00 | 2661.59 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 5.67 | 0.00 | 01-JAN-00:15 | 1891.19 | 01-JUL-18:45 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 15.51 | 0.01 | 18-SEP-12:45 | 2658.33 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 9.85 | 0.00 | 14-JAN-23:00 | 2658.33 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 5.66 | 0.00 | 01-JAN-00:15 | 1870.86 | 01-JUL-18:45 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 15.26 | 0.03 | 05-MAY-11:30 | 2390.06 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 6.53 | 0.00 | 01-JAN-10:00 | 2390.06 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 8.74 | 0.00 | 01-JAN-00:15 | 2383.59 | 19-AUG-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 15.26 | 0.02 | 29-APR-00:45 | 2392.26 | 19-AUG-13:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 6.53 | 0.00 | 01-JAN-10:00 | 2387.13 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 8.73 | 0.00 | 01-JAN-00:15 | 2392.26 | 19-AUG-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 25.85 | 0.00 | 10-JUN-00:15 | 4535.11 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 17.41 | 0.00 | 01-JAN-11:30 | 4535.11 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 8.44 | 0.00 | 01-JAN-00:15 | 3332.97 | 01-AUG-17:00 |
EnergyTransfer:Zone:F8 NW APARTMENT | 28.12 | 0.02 | 02-OCT-09:15 | 4814.71 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 21.95 | 0.00 | 01-FEB-19:45 | 4814.71 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 6.17 | 0.00 | 01-JAN-00:15 | 2963.30 | 01-JUL-18:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 25.64 | 0.01 | 10-SEP-19:00 | 4505.50 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 17.24 | 0.00 | 01-JAN-11:30 | 4505.50 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 8.40 | 0.00 | 01-JAN-00:15 | 2947.79 | 29-JUL-15:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 27.78 | 0.13 | 01-OCT-05:45 | 4782.33 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 21.63 | 0.00 | 01-FEB-19:45 | 4782.33 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 6.15 | 0.00 | 01-JAN-00:15 | 2255.25 | 18-JUN-18:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 16.04 | 0.04 | 14-SEP-08:00 | 2798.55 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 10.58 | 0.00 | 14-JAN-23:00 | 2798.55 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 5.47 | 0.00 | 01-JAN-00:15 | 1906.17 | 01-JUL-18:45 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 16.04 | 0.02 | 24-JUN-20:15 | 2795.27 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 10.58 | 0.00 | 14-JAN-23:00 | 2795.27 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 5.46 | 0.00 | 01-JAN-00:15 | 1888.03 | 01-JUL-18:45 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 15.51 | 0.04 | 21-SEP-13:45 | 2527.31 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 7.13 | 0.00 | 01-JAN-10:15 | 2527.31 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 8.38 | 0.00 | 01-JAN-00:15 | 2387.25 | 19-AUG-13:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 15.51 | 0.06 | 02-AUG-05:45 | 2524.32 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 7.13 | 0.00 | 01-JAN-10:15 | 2524.32 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 8.37 | 0.00 | 01-JAN-00:15 | 2395.95 | 19-AUG-13:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 27.55 | 0.02 | 20-SEP-09:15 | 4811.97 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 19.31 | 0.00 | 01-JAN-12:00 | 4811.97 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 8.24 | 0.00 | 01-JAN-00:15 | 3472.94 | 01-AUG-16:45 |
EnergyTransfer:Zone:F9 NW APARTMENT | 30.11 | 0.01 | 11-OCT-14:30 | 5096.19 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 24.00 | 0.00 | 01-FEB-20:00 | 5096.19 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 6.12 | 0.00 | 01-JAN-00:15 | 3052.31 | 01-JUL-18:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 27.26 | 0.01 | 29-MAY-02:45 | 4778.37 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 19.09 | 0.00 | 01-JAN-11:45 | 4778.37 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 8.17 | 0.00 | 01-JAN-00:15 | 3011.11 | 29-JUL-15:45 |
EnergyTransfer:Zone:F9 NE APARTMENT | 29.70 | 0.01 | 23-JUL-09:00 | 5060.00 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 23.63 | 0.00 | 01-FEB-20:00 | 5060.00 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 6.07 | 0.00 | 01-JAN-00:15 | 2368.25 | 18-JUN-17:45 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 17.46 | 0.03 | 08-JUL-15:15 | 3006.53 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 12.12 | 0.00 | 15-JAN-23:00 | 3006.53 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 5.34 | 0.00 | 01-JAN-00:15 | 1974.23 | 01-JUL-18:30 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 17.45 | 0.00 | 24-JUN-21:00 | 3002.89 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 12.12 | 0.00 | 15-JAN-23:00 | 3002.89 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 5.33 | 0.00 | 01-JAN-00:15 | 1957.02 | 01-JUL-18:30 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 16.43 | 0.00 | 20-JUN-18:45 | 2728.29 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 8.39 | 0.00 | 01-JAN-10:45 | 2728.29 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 8.03 | 0.00 | 01-JAN-00:15 | 2420.97 | 01-AUG-13:45 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 16.43 | 0.03 | 25-MAY-10:00 | 2724.86 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 8.40 | 0.00 | 01-JAN-10:45 | 2724.86 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 8.03 | 0.00 | 01-JAN-00:15 | 2429.40 | 01-AUG-13:45 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 35.08 | 0.01 | 06-NOV-19:30 | 5492.75 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 26.67 | 0.00 | 01-JAN-11:45 | 5492.75 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 8.41 | 0.00 | 01-JAN-00:15 | 4092.16 | 01-AUG-13:45 |
EnergyTransfer:Zone:T NW APARTMENT | 37.07 | 0.02 | 29-MAY-17:45 | 5618.29 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 30.73 | 0.00 | 18-FEB-14:15 | 5618.29 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 6.35 | 0.00 | 01-JAN-00:15 | 3448.46 | 20-JUL-15:30 |
EnergyTransfer:Zone:T SE APARTMENT | 34.42 | 0.00 | 23-AUG-04:45 | 5463.15 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 26.30 | 0.00 | 01-JAN-11:30 | 5463.15 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 8.12 | 0.00 | 01-JAN-00:15 | 3710.46 | 01-AUG-13:45 |
EnergyTransfer:Zone:T NE APARTMENT | 36.32 | 0.03 | 18-MAY-02:00 | 5615.57 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 30.19 | 0.00 | 18-FEB-15:00 | 5615.57 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 6.14 | 0.00 | 01-JAN-00:15 | 2810.14 | 29-JUL-15:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 23.32 | 0.01 | 26-OCT-19:45 | 3588.46 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 18.09 | 0.00 | 01-FEB-19:45 | 3588.46 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 5.22 | 0.00 | 01-JAN-00:15 | 2275.04 | 01-JUL-18:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 23.31 | 0.08 | 27-OCT-12:30 | 3587.19 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 18.10 | 0.00 | 01-FEB-19:45 | 3587.19 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 5.21 | 0.00 | 01-JAN-00:15 | 2240.43 | 01-JUL-18:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.00 | 0.01 | 10-MAY-08:00 | 3445.62 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 14.54 | 0.00 | 01-JAN-11:00 | 3445.62 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 7.46 | 0.00 | 01-JAN-00:15 | 3277.35 | 01-AUG-13:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.00 | 0.01 | 28-JUL-20:45 | 3443.97 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 14.54 | 0.00 | 01-JAN-11:00 | 3443.97 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 7.46 | 0.00 | 01-JAN-00:15 | 3284.66 | 01-AUG-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 2135.16 | 503.62 | 11-AUG-01:15 | 287055.89 | 27-JAN-07:15 |
WaterSystems:EnergyTransfer | 967.68 | 503.62 | 11-AUG-01:15 | 65716.65 | 19-FEB-07:30 |
sub cat:WaterSystems:EnergyTransfer | 967.68 | 503.62 | 11-AUG-01:15 | 65716.65 | 19-FEB-07:30 |
EnergyTransfer:HVAC | 2337.61 | 0.00 | 11-APR-18:30 | 323048.65 | 07-FEB-02:00 |
CoolingCoils:EnergyTransfer | 761.83 | 0.00 | 01-JAN-00:15 | 305286.57 | 04-AUG-15:45 |
HeatingCoils:EnergyTransfer | 1575.79 | 0.00 | 28-MAR-16:15 | 323048.65 | 07-FEB-02:00 |
PlantLoopHeatingDemand:HVAC | 1210.38 | 0.00 | 28-MAR-16:15 | 223906.46 | 27-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 1210.38 | 0.00 | 28-MAR-16:15 | 223906.46 | 27-JAN-07:00 |
Boilers:EnergyTransfer | 1167.47 | 0.00 | 17-MAR-11:45 | 221889.37 | 27-JAN-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 12.230 | -5.801 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 16.834 | 0.000 | 0.167 | 0.000 | 0.000 | -12.815 | 0.000 | -11.638 | -16.163 |
G NW APARTMENT | 15.592 | -4.106 | 0.000 | 0.000 | 3.909 | 1.087 | 12.213 | 8.687 | 0.000 | 0.154 | 0.000 | 0.000 | -13.443 | 0.000 | -11.179 | -12.914 |
OFFICE | 9.308 | -14.077 | 0.000 | 0.000 | 0.533 | 29.882 | 9.495 | 16.561 | 0.000 | 0.080 | 0.000 | 0.000 | -12.800 | 0.000 | -8.358 | -30.624 |
G NE APARTMENT | 15.363 | -4.007 | 0.000 | 0.000 | 3.917 | 1.087 | 12.213 | 8.511 | 0.000 | 0.154 | 0.000 | 0.000 | -13.208 | 0.000 | -11.193 | -12.837 |
G N1 APARTMENT | 9.130 | -3.511 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 3.159 | 0.000 | 0.123 | 0.000 | 0.000 | -8.455 | 0.000 | -7.696 | -9.969 |
G N2 APARTMENT | 9.130 | -3.503 | 0.000 | 0.000 | 3.921 | 1.087 | 12.213 | 3.157 | 0.000 | 0.123 | 0.000 | 0.000 | -8.453 | 0.000 | -7.698 | -9.975 |
G S1 APARTMENT | 5.918 | -5.641 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 11.376 | 0.000 | 0.134 | 0.000 | 0.000 | -7.805 | 0.000 | -8.189 | -12.979 |
G S2 APARTMENT | 5.713 | -5.824 | 0.000 | 0.000 | 3.883 | 1.087 | 12.213 | 11.357 | 0.000 | 0.134 | 0.000 | 0.000 | -7.821 | 0.000 | -8.247 | -12.495 |
F2 SW APARTMENT | 11.337 | -9.589 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 16.181 | 0.000 | 0.222 | 0.000 | 0.000 | -13.610 | 0.000 | -16.215 | -5.455 |
F2 NW APARTMENT | 15.313 | -6.673 | 0.000 | 0.000 | 3.870 | 1.087 | 12.213 | 8.253 | 0.000 | 0.202 | 0.000 | 0.000 | -14.216 | 0.000 | -15.516 | -4.532 |
F2 SE APARTMENT | 10.417 | -10.593 | 0.000 | 0.000 | 3.819 | 1.087 | 12.213 | 15.950 | 0.000 | 0.222 | 0.001 | 0.000 | -13.485 | 0.000 | -16.404 | -3.225 |
F2 NE APARTMENT | 15.061 | -6.716 | 0.000 | 0.000 | 3.881 | 1.087 | 12.213 | 8.092 | 0.000 | 0.198 | 0.000 | 0.000 | -13.949 | 0.000 | -15.493 | -4.375 |
F2 N1 APARTMENT | 7.216 | -5.741 | 0.000 | 0.000 | 3.881 | 1.087 | 12.213 | 2.933 | 0.000 | 0.153 | 0.000 | 0.000 | -8.989 | 0.000 | -10.555 | -2.198 |
F2 N2 APARTMENT | 7.219 | -5.741 | 0.000 | 0.000 | 3.882 | 1.087 | 12.213 | 2.932 | 0.000 | 0.153 | 0.000 | 0.000 | -8.986 | 0.000 | -10.554 | -2.203 |
F2 S1 APARTMENT | 4.328 | -9.125 | 0.000 | 0.000 | 3.821 | 1.087 | 12.213 | 10.967 | 0.000 | 0.174 | 0.000 | 0.000 | -8.294 | 0.000 | -11.335 | -3.836 |
F2 S2 APARTMENT | 4.286 | -9.223 | 0.000 | 0.000 | 3.819 | 1.087 | 12.213 | 10.960 | 0.000 | 0.175 | 0.000 | 0.000 | -8.301 | 0.000 | -11.358 | -3.657 |
F3 SW APARTMENT | 12.002 | -10.041 | 0.000 | 0.000 | 3.823 | 1.087 | 12.213 | 15.933 | 0.000 | 0.293 | 0.001 | 0.000 | -13.861 | 0.000 | -18.761 | -2.687 |
F3 NW APARTMENT | 16.048 | -7.097 | 0.000 | 0.000 | 3.865 | 1.087 | 12.213 | 8.101 | 0.000 | 0.261 | 0.000 | 0.000 | -14.489 | 0.000 | -17.965 | -2.022 |
F3 SE APARTMENT | 11.752 | -10.172 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 15.765 | 0.000 | 0.291 | 0.001 | 0.000 | -13.642 | 0.000 | -18.836 | -2.282 |
F3 NE APARTMENT | 15.803 | -7.124 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 7.947 | 0.000 | 0.254 | 0.000 | 0.000 | -14.214 | 0.000 | -17.937 | -1.903 |
F3 N1 APARTMENT | 7.258 | -6.277 | 0.000 | 0.000 | 3.871 | 1.087 | 12.213 | 2.862 | 0.000 | 0.200 | 0.117 | 0.000 | -9.176 | 0.000 | -12.155 | -0.000 |
F3 N2 APARTMENT | 7.261 | -6.276 | 0.000 | 0.000 | 3.872 | 1.087 | 12.213 | 2.862 | 0.000 | 0.200 | 0.109 | 0.000 | -9.173 | 0.000 | -12.153 | -0.000 |
F3 S1 APARTMENT | 4.411 | -9.860 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 10.802 | 0.000 | 0.234 | 0.000 | 0.000 | -8.466 | 0.000 | -13.038 | -1.189 |
F3 S2 APARTMENT | 4.403 | -9.888 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 10.798 | 0.000 | 0.235 | 0.000 | 0.000 | -8.467 | 0.000 | -13.049 | -1.139 |
F4 SW APARTMENT | 13.030 | -9.933 | 0.000 | 0.000 | 3.823 | 1.087 | 12.213 | 15.785 | 0.000 | 0.319 | 0.000 | 0.000 | -13.990 | 0.000 | -20.418 | -1.915 |
F4 NW APARTMENT | 17.185 | -7.082 | 0.000 | 0.000 | 3.864 | 1.087 | 12.213 | 8.014 | 0.000 | 0.283 | 0.000 | 0.000 | -14.643 | 0.000 | -19.588 | -1.332 |
F4 SE APARTMENT | 12.889 | -9.942 | 0.000 | 0.000 | 3.827 | 1.087 | 12.213 | 15.634 | 0.000 | 0.316 | 0.000 | 0.000 | -13.750 | 0.000 | -20.462 | -1.812 |
F4 NE APARTMENT | 16.932 | -7.117 | 0.000 | 0.000 | 3.874 | 1.087 | 12.213 | 7.866 | 0.000 | 0.274 | 0.000 | 0.000 | -14.363 | 0.000 | -19.553 | -1.212 |
F4 N1 APARTMENT | 7.777 | -6.347 | 0.000 | 0.000 | 3.868 | 1.087 | 12.213 | 2.825 | 0.000 | 0.215 | 0.777 | 0.000 | -9.282 | 0.000 | -13.133 | -0.000 |
F4 N2 APARTMENT | 7.777 | -6.341 | 0.000 | 0.000 | 3.869 | 1.087 | 12.213 | 2.824 | 0.000 | 0.215 | 0.768 | 0.000 | -9.279 | 0.000 | -13.132 | -0.000 |
F4 S1 APARTMENT | 4.849 | -9.894 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 10.704 | 0.000 | 0.253 | 0.000 | 0.000 | -8.551 | 0.000 | -14.047 | -0.418 |
F4 S2 APARTMENT | 4.848 | -9.898 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 10.702 | 0.000 | 0.254 | 0.000 | 0.000 | -8.551 | 0.000 | -14.054 | -0.406 |
M SW APARTMENT | 13.878 | -9.836 | 0.000 | 0.000 | 3.826 | 1.087 | 12.213 | 15.673 | 0.000 | 0.339 | 0.001 | 0.000 | -14.091 | 0.000 | -21.971 | -1.117 |
M NW APARTMENT | 18.073 | -7.105 | 0.000 | 0.000 | 3.865 | 1.087 | 12.213 | 7.949 | 0.000 | 0.300 | 0.000 | 0.000 | -14.766 | 0.000 | -21.092 | -0.524 |
M SE APARTMENT | 13.749 | -9.820 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 15.529 | 0.000 | 0.336 | 0.001 | 0.000 | -13.844 | 0.000 | -22.011 | -1.069 |
M NE APARTMENT | 17.799 | -7.130 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 7.805 | 0.000 | 0.290 | 0.000 | 0.000 | -14.484 | 0.000 | -21.053 | -0.402 |
M N1 APARTMENT | 8.170 | -6.420 | 0.000 | 0.000 | 3.868 | 1.087 | 12.213 | 2.798 | 0.000 | 0.227 | 1.523 | 0.000 | -9.365 | 0.000 | -14.100 | -0.000 |
M N2 APARTMENT | 8.172 | -6.418 | 0.000 | 0.000 | 3.869 | 1.087 | 12.213 | 2.797 | 0.000 | 0.227 | 1.515 | 0.000 | -9.362 | 0.000 | -14.099 | -0.000 |
M S1 APARTMENT | 5.217 | -9.880 | 0.000 | 0.000 | 3.806 | 1.087 | 12.213 | 10.632 | 0.000 | 0.268 | 0.336 | 0.000 | -8.615 | 0.000 | -15.063 | -0.000 |
M S2 APARTMENT | 5.218 | -9.877 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 10.630 | 0.000 | 0.269 | 0.338 | 0.000 | -8.614 | 0.000 | -15.068 | -0.000 |
F6 SW APARTMENT | 15.228 | -9.172 | 0.000 | 0.000 | 3.834 | 1.087 | 12.213 | 15.617 | 0.000 | 0.356 | 0.000 | 0.000 | -14.113 | 0.000 | -23.233 | -1.818 |
F6 NW APARTMENT | 19.600 | -6.638 | 0.000 | 0.000 | 3.872 | 1.087 | 12.213 | 7.927 | 0.000 | 0.315 | 0.000 | 0.000 | -14.807 | 0.000 | -22.309 | -1.260 |
F6 SE APARTMENT | 15.087 | -9.149 | 0.000 | 0.000 | 3.840 | 1.087 | 12.213 | 15.478 | 0.000 | 0.352 | 0.000 | 0.000 | -13.863 | 0.000 | -23.272 | -1.772 |
F6 NE APARTMENT | 19.304 | -6.639 | 0.000 | 0.000 | 3.883 | 1.087 | 12.213 | 7.787 | 0.000 | 0.304 | 0.000 | 0.000 | -14.524 | 0.000 | -22.269 | -1.144 |
F6 N1 APARTMENT | 9.119 | -5.951 | 0.000 | 0.000 | 3.876 | 1.087 | 12.213 | 2.796 | 0.000 | 0.237 | 0.864 | 0.000 | -9.390 | 0.000 | -14.850 | -0.000 |
F6 N2 APARTMENT | 9.119 | -5.946 | 0.000 | 0.000 | 3.877 | 1.087 | 12.213 | 2.795 | 0.000 | 0.236 | 0.855 | 0.000 | -9.387 | 0.000 | -14.848 | -0.000 |
F6 S1 APARTMENT | 5.937 | -9.183 | 0.000 | 0.000 | 3.816 | 1.087 | 12.213 | 10.596 | 0.000 | 0.280 | 0.000 | 0.000 | -8.625 | 0.000 | -15.854 | -0.267 |
F6 S2 APARTMENT | 5.939 | -9.179 | 0.000 | 0.000 | 3.816 | 1.087 | 12.213 | 10.594 | 0.000 | 0.281 | 0.001 | 0.000 | -8.623 | 0.000 | -15.859 | -0.268 |
F7 SW APARTMENT | 16.334 | -8.756 | 0.000 | 0.000 | 3.841 | 1.087 | 12.213 | 15.564 | 0.000 | 0.370 | 0.001 | 0.000 | -14.142 | 0.000 | -24.348 | -2.162 |
F7 NW APARTMENT | 20.796 | -6.362 | 0.000 | 0.000 | 3.878 | 1.087 | 12.213 | 7.903 | 0.000 | 0.326 | 0.000 | 0.000 | -14.854 | 0.000 | -23.390 | -1.597 |
F7 SE APARTMENT | 16.177 | -8.723 | 0.000 | 0.000 | 3.847 | 1.087 | 12.213 | 15.428 | 0.000 | 0.366 | 0.001 | 0.000 | -13.891 | 0.000 | -24.387 | -2.116 |
F7 NE APARTMENT | 20.488 | -6.351 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 7.765 | 0.000 | 0.315 | 0.000 | 0.000 | -14.570 | 0.000 | -23.350 | -1.484 |
F7 N1 APARTMENT | 9.845 | -5.667 | 0.000 | 0.000 | 3.881 | 1.087 | 12.213 | 2.790 | 0.000 | 0.245 | 0.543 | 0.000 | -9.420 | 0.000 | -15.517 | -0.000 |
F7 N2 APARTMENT | 9.846 | -5.663 | 0.000 | 0.000 | 3.882 | 1.087 | 12.213 | 2.790 | 0.000 | 0.245 | 0.534 | 0.000 | -9.417 | 0.000 | -15.515 | -0.001 |
F7 S1 APARTMENT | 6.527 | -8.735 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 10.563 | 0.000 | 0.291 | 0.001 | 0.000 | -8.639 | 0.000 | -16.550 | -0.580 |
F7 S2 APARTMENT | 6.529 | -8.732 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 10.561 | 0.000 | 0.291 | 0.001 | 0.000 | -8.637 | 0.000 | -16.555 | -0.581 |
F8 SW APARTMENT | 17.411 | -8.439 | 0.000 | 0.000 | 3.847 | 1.087 | 12.213 | 15.517 | 0.000 | 0.382 | 0.000 | 0.000 | -14.169 | 0.000 | -25.376 | -2.473 |
F8 NW APARTMENT | 21.947 | -6.172 | 0.000 | 0.000 | 3.882 | 1.087 | 12.213 | 7.881 | 0.000 | 0.337 | 0.000 | 0.000 | -14.898 | 0.000 | -24.390 | -1.886 |
F8 SE APARTMENT | 17.237 | -8.399 | 0.000 | 0.000 | 3.853 | 1.087 | 12.213 | 15.384 | 0.000 | 0.378 | 0.000 | 0.000 | -13.916 | 0.000 | -25.415 | -2.422 |
F8 NE APARTMENT | 21.628 | -6.149 | 0.000 | 0.000 | 3.892 | 1.087 | 12.213 | 7.745 | 0.000 | 0.325 | 0.000 | 0.000 | -14.613 | 0.000 | -24.350 | -1.778 |
F8 N1 APARTMENT | 10.578 | -5.467 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 2.784 | 0.000 | 0.253 | 0.256 | 0.000 | -9.446 | 0.000 | -16.143 | -0.000 |
F8 N2 APARTMENT | 10.575 | -5.460 | 0.000 | 0.000 | 3.887 | 1.087 | 12.213 | 2.784 | 0.000 | 0.252 | 0.248 | 0.000 | -9.443 | 0.000 | -16.141 | -0.000 |
F8 S1 APARTMENT | 7.130 | -8.376 | 0.000 | 0.000 | 3.831 | 1.087 | 12.213 | 10.533 | 0.000 | 0.299 | 0.000 | 0.000 | -8.650 | 0.000 | -17.199 | -0.869 |
F8 S2 APARTMENT | 7.135 | -8.373 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 10.532 | 0.000 | 0.300 | 0.000 | 0.000 | -8.649 | 0.000 | -17.205 | -0.870 |
F9 SW APARTMENT | 19.310 | -8.238 | 0.000 | 0.000 | 3.853 | 1.087 | 12.213 | 15.491 | 0.000 | 0.402 | 0.000 | 0.000 | -14.161 | 0.000 | -26.302 | -3.654 |
F9 NW APARTMENT | 23.995 | -6.116 | 0.000 | 0.000 | 3.885 | 1.087 | 12.213 | 7.867 | 0.000 | 0.354 | 0.000 | 0.000 | -14.909 | 0.000 | -25.305 | -3.071 |
F9 SE APARTMENT | 19.094 | -8.170 | 0.000 | 0.000 | 3.859 | 1.087 | 12.213 | 15.361 | 0.000 | 0.399 | 0.000 | 0.000 | -13.909 | 0.000 | -26.345 | -3.588 |
F9 NE APARTMENT | 23.633 | -6.068 | 0.000 | 0.000 | 3.896 | 1.087 | 12.213 | 7.734 | 0.000 | 0.340 | 0.000 | 0.000 | -14.623 | 0.000 | -25.262 | -2.950 |
F9 N1 APARTMENT | 12.121 | -5.336 | 0.000 | 0.000 | 3.889 | 1.087 | 12.213 | 2.782 | 0.000 | 0.268 | 0.000 | 0.000 | -9.449 | 0.000 | -16.720 | -0.855 |
F9 N2 APARTMENT | 12.119 | -5.332 | 0.000 | 0.000 | 3.890 | 1.087 | 12.213 | 2.782 | 0.000 | 0.267 | 0.000 | 0.000 | -9.446 | 0.000 | -16.718 | -0.862 |
F9 S1 APARTMENT | 8.395 | -8.034 | 0.000 | 0.000 | 3.839 | 1.087 | 12.213 | 10.519 | 0.000 | 0.317 | 0.000 | 0.000 | -8.639 | 0.000 | -17.782 | -1.914 |
F9 S2 APARTMENT | 8.398 | -8.031 | 0.000 | 0.000 | 3.840 | 1.087 | 12.213 | 10.517 | 0.000 | 0.317 | 0.000 | 0.000 | -8.637 | 0.000 | -17.788 | -1.915 |
T SW APARTMENT | 26.669 | -8.411 | 0.000 | 0.000 | 3.879 | 1.087 | 12.213 | 15.295 | 0.000 | 0.415 | 0.000 | 0.000 | -13.673 | 0.000 | -27.124 | -10.349 |
T NW APARTMENT | 30.728 | -6.345 | 0.000 | 0.000 | 3.902 | 1.087 | 12.213 | 7.720 | 0.000 | 0.363 | 0.000 | 0.000 | -14.474 | 0.000 | -26.161 | -9.031 |
T SE APARTMENT | 26.299 | -8.122 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 15.189 | 0.000 | 0.411 | 0.000 | 0.000 | -13.446 | 0.000 | -27.173 | -10.344 |
T NE APARTMENT | 30.185 | -6.138 | 0.000 | 0.000 | 3.915 | 1.087 | 12.213 | 7.614 | 0.000 | 0.354 | 0.000 | 0.000 | -14.212 | 0.000 | -26.106 | -8.912 |
T N1 APARTMENT | 18.094 | -5.220 | 0.000 | 0.000 | 3.907 | 1.087 | 12.213 | 2.738 | 0.000 | 0.277 | 0.000 | 0.000 | -9.159 | 0.000 | -17.252 | -6.684 |
T N2 APARTMENT | 18.096 | -5.211 | 0.000 | 0.000 | 3.907 | 1.087 | 12.213 | 2.735 | 0.000 | 0.277 | 0.000 | 0.000 | -9.155 | 0.000 | -17.255 | -6.695 |
T S1 APARTMENT | 14.535 | -7.464 | 0.000 | 0.000 | 3.866 | 1.087 | 12.213 | 10.416 | 0.000 | 0.332 | 0.000 | 0.000 | -8.372 | 0.000 | -18.329 | -8.284 |
T S2 APARTMENT | 14.540 | -7.464 | 0.000 | 0.000 | 3.867 | 1.087 | 12.213 | 10.412 | 0.000 | 0.332 | 0.000 | 0.000 | -8.369 | 0.000 | -18.337 | -8.281 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.789 | 0.000 | 0.475 | 55.346 | 0.000 | -2.780 | 0.000 | -73.270 | -0.002 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.670 | 0.000 | 0.007 | 0.000 | 0.000 | -1.731 | 0.000 | -2.107 | -14.280 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.627 | 0.000 | 0.008 | 0.000 | 0.000 | -1.807 | 0.000 | -2.560 | -13.709 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.604 | 0.000 | 0.008 | 0.000 | 0.000 | -1.839 | 0.000 | -2.883 | -13.330 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.579 | 0.000 | 0.007 | 0.000 | 0.000 | -1.883 | 0.000 | -3.238 | -29.345 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.587 | 0.000 | 0.010 | 0.000 | 0.000 | -1.857 | 0.000 | -3.337 | -12.843 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.587 | 0.000 | 0.011 | 0.000 | 0.000 | -1.851 | 0.000 | -3.498 | -12.689 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.584 | 0.000 | 0.011 | 0.000 | 0.000 | -1.850 | 0.000 | -3.653 | -12.531 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.582 | 0.000 | 0.011 | 0.000 | 0.000 | -1.845 | 0.000 | -3.783 | -12.405 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.542 | 0.000 | 0.005 | 0.000 | 0.000 | -1.795 | 0.000 | -3.981 | -20.363 |
Total Facility | 1037.789 | -597.030 | 0.000 | 0.000 | 305.562 | 296.560 | 982.450 | 762.587 | 0.000 | 22.234 | 64.143 | 0.000 | -936.226 | 0.000 | -1514.958 | -423.100 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 13-SEP-15:15 | 0.00 | -2540.40 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3596.36 | 0.00 | 288.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1910.05 |
G NW APARTMENT | 05-JUL-17:30 | 0.00 | -2162.10 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2620.89 | 0.00 | 259.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1535.81 |
OFFICE | 20-JUL-13:00 | 0.00 | -3517.48 | 0.00 | 0.00 | 65.04 | 2345.88 | 588.62 | 2463.94 | 0.00 | 178.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2124.92 |
G NE APARTMENT | 15-JUL-09:15 | 0.00 | -1632.16 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2466.44 | 0.00 | 280.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1574.87 |
G N1 APARTMENT | 01-JUL-18:30 | 0.00 | -1284.24 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 636.42 | 0.00 | 303.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -448.34 |
G N2 APARTMENT | 01-JUL-18:30 | 0.00 | -1261.11 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 637.05 | 0.00 | 303.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -472.09 |
G S1 APARTMENT | 01-AUG-13:45 | 0.00 | -1673.24 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2084.46 | 0.00 | 328.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1176.10 |
G S2 APARTMENT | 01-AUG-13:45 | 0.00 | -1742.29 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2083.43 | 0.00 | 330.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1108.43 |
F2 SW APARTMENT | 13-SEP-15:15 | 0.00 | -3195.87 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3539.13 | 0.00 | 359.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.42 |
F2 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2791.11 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1782.52 | 0.00 | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -190.27 |
F2 SE APARTMENT | 02-SEP-12:45 | 0.00 | -2930.72 | 0.00 | 0.00 | 40.24 | 12.97 | 388.49 | 3014.77 | 0.00 | 438.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -963.77 |
F2 NE APARTMENT | 29-JUL-16:15 | 0.00 | -2112.94 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 696.94 | 0.00 | 729.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52.19 |
F2 N1 APARTMENT | 01-JUL-18:30 | 0.00 | -1730.49 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 620.00 | 0.00 | 375.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58.01 |
F2 N2 APARTMENT | 01-JUL-18:30 | 0.00 | -1713.41 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 620.46 | 0.00 | 376.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.18 |
F2 S1 APARTMENT | 01-AUG-13:45 | 0.00 | -2238.52 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2042.96 | 0.00 | 422.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -663.46 |
F2 S2 APARTMENT | 01-AUG-13:45 | 0.00 | -2262.79 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2042.77 | 0.00 | 424.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -640.73 |
F3 SW APARTMENT | 13-SEP-15:15 | 0.00 | -3254.12 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3508.97 | 0.00 | 404.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1224.11 |
F3 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2862.17 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1769.49 | 0.00 | 457.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157.97 |
F3 SE APARTMENT | 29-JUL-15:45 | 0.00 | -2882.19 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 886.58 | 0.00 | 1439.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9.30 |
F3 NE APARTMENT | 29-JUL-15:45 | 0.00 | -2189.97 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 851.92 | 0.00 | 931.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -159.08 |
F3 N1 APARTMENT | 01-JUL-18:30 | 0.00 | -1800.77 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 615.70 | 0.00 | 419.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27.11 |
F3 N2 APARTMENT | 01-JUL-18:30 | 0.00 | -1783.81 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 616.15 | 0.00 | 419.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.12 |
F3 S1 APARTMENT | 01-AUG-13:45 | 0.00 | -2303.80 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2022.12 | 0.00 | 474.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -629.63 |
F3 S2 APARTMENT | 01-AUG-13:45 | 0.00 | -2314.52 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2022.06 | 0.00 | 476.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -620.08 |
F4 SW APARTMENT | 01-AUG-17:00 | 0.00 | -3281.46 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2308.56 | 0.00 | 535.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -301.06 |
F4 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2902.77 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1760.57 | 0.00 | 496.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.05 |
F4 SE APARTMENT | 29-JUL-15:30 | 0.00 | -2910.52 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 984.36 | 0.00 | 1335.33 | 25.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 NE APARTMENT | 29-JUL-15:30 | 0.00 | -2224.00 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 925.81 | 0.00 | 860.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -127.24 |
F4 N1 APARTMENT | 01-JUL-18:45 | 0.00 | -1837.38 | 0.00 | 0.00 | 141.40 | 103.77 | 547.42 | 562.52 | 0.00 | 366.29 | 115.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 01-JUL-18:30 | 0.00 | -1817.00 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 613.46 | 0.00 | 452.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.82 |
F4 S1 APARTMENT | 19-AUG-13:00 | 0.00 | -2349.30 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2228.79 | 0.00 | 486.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -807.76 |
F4 S2 APARTMENT | 19-AUG-13:00 | 0.00 | -2358.18 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2228.62 | 0.00 | 486.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -798.71 |
M SW APARTMENT | 01-AUG-17:00 | 0.00 | -3331.31 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2298.87 | 0.00 | 569.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -275.64 |
M NW APARTMENT | 01-JUL-18:30 | 0.00 | -2954.36 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1753.03 | 0.00 | 527.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -118.79 |
M SE APARTMENT | 29-JUL-15:30 | 0.00 | -2954.03 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 979.94 | 0.00 | 1415.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6.33 |
M NE APARTMENT | 29-JUL-15:30 | 0.00 | -2262.28 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 922.12 | 0.00 | 912.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -137.50 |
M N1 APARTMENT | 01-JUL-18:45 | 0.00 | -1890.03 | 0.00 | 0.00 | 141.36 | 103.77 | 547.42 | 560.27 | 0.00 | 387.76 | 149.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 01-JUL-18:45 | 0.00 | -1866.05 | 0.00 | 0.00 | 141.39 | 103.77 | 547.42 | 560.74 | 0.00 | 387.88 | 124.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 19-AUG-13:00 | 0.00 | -2400.18 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2217.23 | 0.00 | 516.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -775.26 |
M S2 APARTMENT | 19-AUG-13:00 | 0.00 | -2408.83 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2217.06 | 0.00 | 516.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -766.44 |
F6 SW APARTMENT | 01-AUG-17:00 | 0.00 | -3316.10 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2292.46 | 0.00 | 598.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -312.80 |
F6 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2941.15 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1748.33 | 0.00 | 552.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -152.94 |
F6 SE APARTMENT | 29-JUL-15:30 | 0.00 | -2934.94 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 978.36 | 0.00 | 1479.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88.24 |
F6 NE APARTMENT | 29-JUL-15:30 | 0.00 | -2235.63 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 921.14 | 0.00 | 954.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.61 |
F6 N1 APARTMENT | 01-JUL-18:45 | 0.00 | -1883.84 | 0.00 | 0.00 | 141.28 | 103.77 | 547.42 | 559.41 | 0.00 | 405.35 | 126.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 01-JUL-18:45 | 0.00 | -1860.06 | 0.00 | 0.00 | 141.31 | 103.77 | 547.42 | 559.88 | 0.00 | 405.46 | 102.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 19-AUG-13:00 | 0.00 | -2383.05 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2208.81 | 0.00 | 540.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -808.89 |
F6 S2 APARTMENT | 19-AUG-13:00 | 0.00 | -2391.72 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2208.64 | 0.00 | 540.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -800.06 |
F7 SW APARTMENT | 01-AUG-17:00 | 0.00 | -3320.95 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2286.33 | 0.00 | 622.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.98 |
F7 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2947.02 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1743.77 | 0.00 | 574.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164.31 |
F7 SE APARTMENT | 29-JUL-15:30 | 0.00 | -2937.66 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 976.44 | 0.00 | 1534.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -138.87 |
F7 NE APARTMENT | 18-JUN-18:00 | 0.00 | -2240.58 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 707.07 | 0.00 | 545.70 | 169.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 01-JUL-18:45 | 0.00 | -1890.03 | 0.00 | 0.00 | 141.23 | 103.77 | 547.42 | 558.29 | 0.00 | 419.73 | 119.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 01-JUL-18:45 | 0.00 | -1869.71 | 0.00 | 0.00 | 141.26 | 103.77 | 547.42 | 558.75 | 0.00 | 420.33 | 98.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 19-AUG-13:00 | 0.00 | -2383.25 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2201.31 | 0.00 | 562.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.41 |
F7 S2 APARTMENT | 19-AUG-13:00 | 0.00 | -2391.92 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2201.14 | 0.00 | 562.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -813.57 |
F8 SW APARTMENT | 01-AUG-17:00 | 0.00 | -3332.38 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2280.69 | 0.00 | 643.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -329.77 |
F8 NW APARTMENT | 01-JUL-18:30 | 0.00 | -2962.27 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 1739.39 | 0.00 | 593.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -163.51 |
F8 SE APARTMENT | 29-JUL-15:30 | 0.00 | -2949.24 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 974.51 | 0.00 | 1583.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -173.86 |
F8 NE APARTMENT | 18-JUN-18:00 | 0.00 | -2254.62 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 705.55 | 0.00 | 562.75 | 168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 01-JUL-18:45 | 0.00 | -1905.00 | 0.00 | 0.00 | 141.21 | 103.77 | 547.42 | 557.02 | 0.00 | 432.17 | 123.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 01-JUL-18:45 | 0.00 | -1886.86 | 0.00 | 0.00 | 141.24 | 103.77 | 547.42 | 557.49 | 0.00 | 433.11 | 103.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 19-AUG-13:00 | 0.00 | -2386.92 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2194.67 | 0.00 | 580.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -830.47 |
F8 S2 APARTMENT | 19-AUG-13:00 | 0.00 | -2395.61 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2194.50 | 0.00 | 580.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -821.60 |
F9 SW APARTMENT | 01-AUG-16:45 | 0.00 | -3472.37 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2451.55 | 0.00 | 665.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -382.44 |
F9 NW APARTMENT | 01-JUL-18:30 | 0.00 | -3051.25 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 1732.76 | 0.00 | 609.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.31 |
F9 SE APARTMENT | 29-JUL-15:45 | 0.00 | -3012.23 | 0.00 | 0.00 | 48.52 | 45.40 | 470.89 | 870.04 | 0.00 | 1818.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.09 |
F9 NE APARTMENT | 18-JUN-17:45 | 0.00 | -2367.82 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 726.89 | 0.00 | 625.04 | 197.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 01-JUL-18:30 | 0.00 | -1973.18 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 604.02 | 0.00 | 551.08 | 25.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 01-JUL-18:30 | 0.00 | -1955.97 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 604.48 | 0.00 | 551.86 | 6.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 01-AUG-13:45 | 0.00 | -2421.94 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1967.47 | 0.00 | 631.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -613.32 |
F9 S2 APARTMENT | 01-AUG-13:45 | 0.00 | -2430.37 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1967.41 | 0.00 | 632.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -606.13 |
T SW APARTMENT | 01-AUG-13:45 | 0.00 | -4093.93 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 3245.01 | 0.00 | 714.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -302.28 |
T NW APARTMENT | 20-JUL-15:30 | 0.00 | -3449.07 | 0.00 | 0.00 | 46.24 | 45.40 | 470.89 | 2782.97 | 0.00 | 656.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -552.93 |
T SE APARTMENT | 01-AUG-13:45 | 0.00 | -3712.33 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2259.89 | 0.00 | 714.82 | 301.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 29-JUL-15:45 | 0.00 | -2811.15 | 0.00 | 0.00 | 48.91 | 45.40 | 470.89 | 814.46 | 0.00 | 1335.50 | 95.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 01-JUL-18:30 | 0.00 | -2273.93 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 595.02 | 0.00 | 578.06 | 307.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 01-JUL-18:30 | 0.00 | -2239.33 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 595.89 | 0.00 | 578.05 | 272.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 01-AUG-13:45 | 0.00 | -3278.91 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1934.26 | 0.00 | 659.39 | 248.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 01-AUG-13:45 | 0.00 | -3286.22 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1934.25 | 0.00 | 661.19 | 254.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-16:15 | 0.00 | -179922.27 | 0.00 | 0.00 | 6545.00 | 11327.17 | 47212.47 | 57933.58 | 0.00 | 79430.75 | 0.00 | 0.00 | 0.00 | 0.00 | -139.08 | -22387.62 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 17-DEC-08:30 | 2639.17 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1143.92 | 0.00 | -1391.04 | -586.13 |
G NW APARTMENT | 27-JAN-08:15 | 3010.74 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1554.73 | 0.00 | -762.53 | -1175.39 |
OFFICE | 17-DEC-08:25 | 2656.55 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1109.74 | 0.00 | -1391.04 | -819.20 |
G NE APARTMENT | 07-FEB-18:00 | 2769.64 | 0.00 | 0.00 | 0.00 | 98.63 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1292.94 | 0.00 | -1557.89 | -670.93 |
G N1 APARTMENT | 27-JAN-08:15 | 2034.36 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -943.79 | 0.00 | -459.94 | -1112.54 |
G N2 APARTMENT | 27-JAN-08:15 | 2030.71 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -943.84 | 0.00 | -459.94 | -1108.85 |
G S1 APARTMENT | 17-DEC-08:30 | 1610.64 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.07 | 0.00 | -839.04 | -575.45 |
G S2 APARTMENT | 17-DEC-08:30 | 1602.96 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.25 | 0.00 | -839.04 | -567.59 |
F2 SW APARTMENT | 07-FEB-02:00 | 2966.47 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 49.71 | 0.00 | -1577.63 | 0.00 | -1876.04 | 0.00 |
F2 NW APARTMENT | 07-FEB-02:00 | 3257.44 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1565.46 | 0.00 | -1876.04 | -253.44 |
F2 SE APARTMENT | 07-FEB-02:00 | 2842.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 166.72 | 0.00 | -1571.16 | 0.00 | -1876.04 | 0.00 |
F2 NE APARTMENT | 07-FEB-02:00 | 3215.15 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1555.81 | 0.00 | -1876.05 | -220.78 |
F2 N1 APARTMENT | 07-FEB-02:00 | 1877.25 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.65 | 0.00 | -1131.58 | -227.51 |
F2 N2 APARTMENT | 07-FEB-02:00 | 1874.83 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.70 | 0.00 | -1131.58 | -225.04 |
F2 S1 APARTMENT | 25-JAN-05:00 | 1613.52 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -922.37 | 0.00 | -916.85 | -207.11 |
F2 S2 APARTMENT | 25-JAN-05:00 | 1608.49 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -922.48 | 0.00 | -916.85 | -201.96 |
F3 SW APARTMENT | 07-MAR-14:00 | 3233.72 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -163.78 | 0.00 | -2773.24 | -745.58 |
F3 NW APARTMENT | 07-MAR-14:00 | 3510.00 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -584.81 | 0.00 | -2773.24 | -600.82 |
F3 SE APARTMENT | 07-MAR-14:00 | 3199.38 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -347.18 | 0.00 | -2773.24 | -527.83 |
F3 NE APARTMENT | 07-MAR-14:00 | 3478.84 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -767.91 | 0.00 | -2773.26 | -386.54 |
F3 N1 APARTMENT | 07-MAR-14:00 | 2006.85 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.71 | 0.00 | -1672.76 | -311.25 |
F3 N2 APARTMENT | 07-MAR-14:00 | 2003.57 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.81 | 0.00 | -1672.76 | -307.88 |
F3 S1 APARTMENT | 07-MAR-14:00 | 1739.68 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44.90 | 0.00 | -1672.75 | -470.91 |
F3 S2 APARTMENT | 07-MAR-14:00 | 1736.18 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45.03 | 0.00 | -1672.75 | -467.28 |
F4 SW APARTMENT | 07-MAR-14:00 | 3558.38 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -182.99 | 0.00 | -3101.02 | -723.24 |
F4 NW APARTMENT | 07-MAR-14:00 | 3836.43 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -604.64 | 0.00 | -3101.02 | -579.65 |
F4 SE APARTMENT | 07-MAR-14:00 | 3529.45 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -364.69 | 0.00 | -3101.02 | -512.61 |
F4 NE APARTMENT | 07-MAR-14:00 | 3804.98 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -786.32 | 0.00 | -3101.04 | -366.50 |
F4 N1 APARTMENT | 07-MAR-14:00 | 2194.42 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -483.12 | 0.00 | -1870.47 | -289.71 |
F4 N2 APARTMENT | 07-MAR-14:00 | 2191.16 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -483.22 | 0.00 | -1870.47 | -286.35 |
F4 S1 APARTMENT | 07-MAR-14:00 | 1926.00 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55.64 | 0.00 | -1870.45 | -448.78 |
F4 S2 APARTMENT | 07-MAR-14:00 | 1923.06 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55.75 | 0.00 | -1870.45 | -445.73 |
M SW APARTMENT | 07-MAR-14:00 | 3820.58 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -197.76 | 0.00 | -3371.46 | -700.24 |
M NW APARTMENT | 07-MAR-14:00 | 4097.19 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -619.71 | 0.00 | -3371.46 | -554.89 |
M SE APARTMENT | 07-MAR-14:00 | 3792.02 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.40 | 0.00 | -3371.46 | -491.04 |
M NE APARTMENT | 07-MAR-14:00 | 4065.55 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -800.35 | 0.00 | -3371.48 | -342.59 |
M N1 APARTMENT | 07-MAR-14:00 | 2342.83 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491.81 | 0.00 | -2033.59 | -266.31 |
M N2 APARTMENT | 07-MAR-14:00 | 2339.60 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -491.91 | 0.00 | -2033.59 | -262.97 |
M S1 APARTMENT | 07-MAR-14:00 | 2077.80 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.95 | 0.00 | -2033.57 | -429.15 |
M S2 APARTMENT | 07-MAR-14:00 | 2075.01 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -64.07 | 0.00 | -2033.57 | -426.24 |
F6 SW APARTMENT | 07-MAR-14:00 | 4091.21 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -207.48 | 0.00 | -3604.72 | -727.89 |
F6 NW APARTMENT | 07-MAR-14:00 | 4370.94 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -629.72 | 0.00 | -3604.73 | -585.37 |
F6 SE APARTMENT | 07-MAR-14:00 | 4062.23 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387.26 | 0.00 | -3604.73 | -519.12 |
F6 NE APARTMENT | 07-MAR-14:00 | 4339.01 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -809.52 | 0.00 | -3604.75 | -373.62 |
F6 N1 APARTMENT | 07-MAR-14:00 | 2517.96 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -497.38 | 0.00 | -2174.30 | -295.16 |
F6 N2 APARTMENT | 07-MAR-14:00 | 2514.70 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -497.48 | 0.00 | -2174.30 | -291.80 |
F6 S1 APARTMENT | 07-MAR-14:00 | 2247.40 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.17 | 0.00 | -2174.28 | -452.82 |
F6 S2 APARTMENT | 07-MAR-14:00 | 2244.50 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.28 | 0.00 | -2174.28 | -449.82 |
F7 SW APARTMENT | 07-MAR-14:00 | 4319.87 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -216.08 | 0.00 | -3811.60 | -741.06 |
F7 NW APARTMENT | 07-MAR-14:00 | 4600.02 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -638.48 | 0.00 | -3811.61 | -598.80 |
F7 SE APARTMENT | 07-MAR-14:00 | 4290.69 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -395.17 | 0.00 | -3811.61 | -532.79 |
F7 NE APARTMENT | 07-MAR-14:00 | 4567.96 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -817.60 | 0.00 | -3811.64 | -387.60 |
F7 N1 APARTMENT | 07-MAR-14:00 | 2661.21 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -502.29 | 0.00 | -2299.08 | -308.71 |
F7 N2 APARTMENT | 07-MAR-14:00 | 2657.95 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -502.39 | 0.00 | -2299.08 | -305.35 |
F7 S1 APARTMENT | 07-MAR-14:00 | 2389.73 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.87 | 0.00 | -2299.06 | -465.68 |
F7 S2 APARTMENT | 07-MAR-14:00 | 2386.80 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.97 | 0.00 | -2299.06 | -462.64 |
F8 SW APARTMENT | 07-MAR-14:00 | 4534.61 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.16 | 0.00 | -3998.63 | -761.70 |
F8 NW APARTMENT | 07-MAR-14:00 | 4814.16 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.69 | 0.00 | -3998.64 | -618.71 |
F8 SE APARTMENT | 07-MAR-14:00 | 4505.00 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.66 | 0.00 | -3998.63 | -553.58 |
F8 NE APARTMENT | 07-MAR-14:00 | 4781.78 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -824.23 | 0.00 | -3998.66 | -407.76 |
F8 N1 APARTMENT | 07-MAR-14:00 | 2798.15 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.29 | 0.00 | -2411.89 | -328.84 |
F8 N2 APARTMENT | 07-MAR-14:00 | 2794.88 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.39 | 0.00 | -2411.89 | -325.47 |
F8 S1 APARTMENT | 07-MAR-14:00 | 2526.96 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.68 | 0.00 | -2411.87 | -486.30 |
F8 S2 APARTMENT | 07-MAR-14:00 | 2523.98 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.78 | 0.00 | -2411.87 | -483.21 |
F9 SW APARTMENT | 07-MAR-14:00 | 4811.44 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -226.22 | 0.00 | -4170.07 | -864.03 |
F9 NW APARTMENT | 07-MAR-14:00 | 5095.63 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -648.81 | 0.00 | -4170.08 | -725.62 |
F9 SE APARTMENT | 07-MAR-14:00 | 4777.84 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -404.25 | 0.00 | -4170.07 | -652.40 |
F9 NE APARTMENT | 07-MAR-14:00 | 5059.42 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -826.92 | 0.00 | -4170.10 | -511.28 |
F9 N1 APARTMENT | 07-MAR-14:00 | 3006.12 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -507.64 | 0.00 | -2515.30 | -432.06 |
F9 N2 APARTMENT | 07-MAR-14:00 | 3002.47 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -507.74 | 0.00 | -2515.30 | -428.31 |
F9 S1 APARTMENT | 07-MAR-14:00 | 2727.93 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -78.88 | 0.00 | -2515.28 | -582.65 |
F9 S2 APARTMENT | 07-MAR-14:00 | 2724.50 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -78.98 | 0.00 | -2515.28 | -579.12 |
T SW APARTMENT | 07-FEB-02:00 | 5491.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1624.42 | 0.00 | -3466.04 | -838.98 |
T NW APARTMENT | 07-FEB-02:00 | 5617.48 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1615.63 | 0.00 | -3466.05 | -973.29 |
T SE APARTMENT | 07-FEB-02:00 | 5462.36 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1605.01 | 0.00 | -3466.04 | -828.80 |
T NE APARTMENT | 07-MAR-14:00 | 5614.95 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -806.71 | 0.00 | -4328.59 | -928.53 |
T N1 APARTMENT | 07-FEB-02:00 | 3587.80 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -985.19 | 0.00 | -2090.72 | -949.39 |
T N2 APARTMENT | 07-FEB-02:00 | 3586.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -985.22 | 0.00 | -2090.72 | -948.08 |
T S1 APARTMENT | 07-FEB-02:00 | 3444.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.25 | 0.00 | -2090.70 | -798.52 |
T S2 APARTMENT | 07-FEB-02:00 | 3443.35 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.30 | 0.00 | -2090.70 | -796.84 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-MAR-14:00 | 252474.44 | 0.00 | 0.00 | 0.00 | 3821.85 | 9104.94 | 31440.07 | 29.62 | 0.00 | 0.00 | 0.00 | 0.00 | -30731.14 | 0.00 | -224157.35 | -41982.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sec1.1A-General InformationData | |
Weather File | Burlington International Ap VT USA TMY3 WMO#=726170 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 120.25 |
Number of hours cooling loads not met | 100.50 |
Number of hours not met | 220.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.69 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 402.19 | 87652.69 | 1558.07 | 287983.24 | 0.00 | 0.00 |
Space Cooling | 230.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.33 | 2079.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 605.54 | 19201.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1241.86 | 84624.48 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2945.25 | 2799.92 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 2945.25 |
Natural Gas | 0.00 | 2799.92 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 5745.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 51.32 |
Space Cooling | 29.39 |
Fans-Interior | 77.27 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 34.88 |
Subtotal | 375.84 |
Natural Gas [MJ/m2] | |
Space Heating | 198.82 |
Service Water Heating | 158.47 |
Miscellaneous | 0.00 |
Subtotal | 357.29 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.16 |
Space Heating | 34.12 |
Space Cooling | 4.01 |
Fans-Interior | 10.54 |
Service Water Heating | 21.62 |
Receptacle Equipment | 19.80 |
Miscellaneous | 4.76 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.208526 |
G NW APARTMENT DIRECT AIR | 0.187195 |
OFFICE DIRECT AIR | 0.325790 |
G NE APARTMENT DIRECT AIR | 0.156235 |
G N1 APARTMENT DIRECT AIR | 0.106987 |
G N2 APARTMENT DIRECT AIR | 0.106982 |
G S1 APARTMENT DIRECT AIR | 0.132893 |
G S2 APARTMENT DIRECT AIR | 0.139184 |
F2 SW APARTMENT DIRECT AIR | 0.274797 |
F2 NW APARTMENT DIRECT AIR | 0.247392 |
F2 SE APARTMENT DIRECT AIR | 0.270610 |
F2 NE APARTMENT DIRECT AIR | 0.187579 |
F2 N1 APARTMENT DIRECT AIR | 0.131032 |
F2 N2 APARTMENT DIRECT AIR | 0.129668 |
F2 S1 APARTMENT DIRECT AIR | 0.180117 |
F2 S2 APARTMENT DIRECT AIR | 0.182448 |
F3 SW APARTMENT DIRECT AIR | 0.277518 |
F3 NW APARTMENT DIRECT AIR | 0.250925 |
F3 SE APARTMENT DIRECT AIR | 0.253027 |
F3 NE APARTMENT DIRECT AIR | 0.191133 |
F3 N1 APARTMENT DIRECT AIR | 0.135403 |
F3 N2 APARTMENT DIRECT AIR | 0.134050 |
F3 S1 APARTMENT DIRECT AIR | 0.184298 |
F3 S2 APARTMENT DIRECT AIR | 0.185361 |
F4 SW APARTMENT DIRECT AIR | 0.279105 |
F4 NW APARTMENT DIRECT AIR | 0.252601 |
F4 SE APARTMENT DIRECT AIR | 0.252608 |
F4 NE APARTMENT DIRECT AIR | 0.192054 |
F4 N1 APARTMENT DIRECT AIR | 0.137112 |
F4 N2 APARTMENT DIRECT AIR | 0.135761 |
F4 S1 APARTMENT DIRECT AIR | 0.185778 |
F4 S2 APARTMENT DIRECT AIR | 0.186655 |
M SW APARTMENT DIRECT AIR | 0.282299 |
M NW APARTMENT DIRECT AIR | 0.255888 |
M SE APARTMENT DIRECT AIR | 0.255585 |
M NE APARTMENT DIRECT AIR | 0.194673 |
M N1 APARTMENT DIRECT AIR | 0.140259 |
M N2 APARTMENT DIRECT AIR | 0.138910 |
M S1 APARTMENT DIRECT AIR | 0.188767 |
M S2 APARTMENT DIRECT AIR | 0.189614 |
F6 SW APARTMENT DIRECT AIR | 0.279770 |
F6 NW APARTMENT DIRECT AIR | 0.253311 |
F6 SE APARTMENT DIRECT AIR | 0.253102 |
F6 NE APARTMENT DIRECT AIR | 0.191641 |
F6 N1 APARTMENT DIRECT AIR | 0.137843 |
F6 N2 APARTMENT DIRECT AIR | 0.136502 |
F6 S1 APARTMENT DIRECT AIR | 0.186143 |
F6 S2 APARTMENT DIRECT AIR | 0.186985 |
F7 SW APARTMENT DIRECT AIR | 0.279239 |
F7 NW APARTMENT DIRECT AIR | 0.252800 |
F7 SE APARTMENT DIRECT AIR | 0.252628 |
F7 NE APARTMENT DIRECT AIR | 0.190689 |
F7 N1 APARTMENT DIRECT AIR | 0.137373 |
F7 N2 APARTMENT DIRECT AIR | 0.136039 |
F7 S1 APARTMENT DIRECT AIR | 0.185489 |
F7 S2 APARTMENT DIRECT AIR | 0.186327 |
F8 SW APARTMENT DIRECT AIR | 0.279858 |
F8 NW APARTMENT DIRECT AIR | 0.253479 |
F8 SE APARTMENT DIRECT AIR | 0.253274 |
F8 NE APARTMENT DIRECT AIR | 0.190880 |
F8 N1 APARTMENT DIRECT AIR | 0.138093 |
F8 N2 APARTMENT DIRECT AIR | 0.136766 |
F8 S1 APARTMENT DIRECT AIR | 0.185967 |
F8 S2 APARTMENT DIRECT AIR | 0.186805 |
F9 SW APARTMENT DIRECT AIR | 0.288623 |
F9 NW APARTMENT DIRECT AIR | 0.262511 |
F9 SE APARTMENT DIRECT AIR | 0.260045 |
F9 NE APARTMENT DIRECT AIR | 0.194166 |
F9 N1 APARTMENT DIRECT AIR | 0.145883 |
F9 N2 APARTMENT DIRECT AIR | 0.144530 |
F9 S1 APARTMENT DIRECT AIR | 0.191581 |
F9 S2 APARTMENT DIRECT AIR | 0.192406 |
T SW APARTMENT DIRECT AIR | 0.357686 |
T NW APARTMENT DIRECT AIR | 0.318351 |
T SE APARTMENT DIRECT AIR | 0.322787 |
T NE APARTMENT DIRECT AIR | 0.242581 |
T N1 APARTMENT DIRECT AIR | 0.186653 |
T N2 APARTMENT DIRECT AIR | 0.186451 |
T S1 APARTMENT DIRECT AIR | 0.264114 |
T S2 APARTMENT DIRECT AIR | 0.264908 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.208526 |
AIRLOOP G NW MAIN BRANCH | 0.187195 |
AIRLOOP OFFICE MAIN BRANCH | 0.325790 |
AIRLOOP G NE MAIN BRANCH | 0.156235 |
AIRLOOP G N1 MAIN BRANCH | 0.106987 |
AIRLOOP G N2 MAIN BRANCH | 0.106982 |
AIRLOOP G S1 MAIN BRANCH | 0.132893 |
AIRLOOP G S2 MAIN BRANCH | 0.139184 |
AIRLOOP F2 SW MAIN BRANCH | 0.274797 |
AIRLOOP F2 NW MAIN BRANCH | 0.247392 |
AIRLOOP F2 SE MAIN BRANCH | 0.270610 |
AIRLOOP F2 NE MAIN BRANCH | 0.187579 |
AIRLOOP F2 N1 MAIN BRANCH | 0.131032 |
AIRLOOP F2 N2 MAIN BRANCH | 0.129668 |
AIRLOOP F2 S1 MAIN BRANCH | 0.180117 |
AIRLOOP F2 S2 MAIN BRANCH | 0.182448 |
AIRLOOP F3 SW MAIN BRANCH | 0.277518 |
AIRLOOP F3 NW MAIN BRANCH | 0.250925 |
AIRLOOP F3 SE MAIN BRANCH | 0.253027 |
AIRLOOP F3 NE MAIN BRANCH | 0.191133 |
AIRLOOP F3 N1 MAIN BRANCH | 0.135403 |
AIRLOOP F3 N2 MAIN BRANCH | 0.134050 |
AIRLOOP F3 S1 MAIN BRANCH | 0.184298 |
AIRLOOP F3 S2 MAIN BRANCH | 0.185361 |
AIRLOOP F4 SW MAIN BRANCH | 0.279105 |
AIRLOOP F4 NW MAIN BRANCH | 0.252601 |
AIRLOOP F4 SE MAIN BRANCH | 0.252608 |
AIRLOOP F4 NE MAIN BRANCH | 0.192054 |
AIRLOOP F4 N1 MAIN BRANCH | 0.137112 |
AIRLOOP F4 N2 MAIN BRANCH | 0.135761 |
AIRLOOP F4 S1 MAIN BRANCH | 0.185778 |
AIRLOOP F4 S2 MAIN BRANCH | 0.186655 |
AIRLOOP M SW MAIN BRANCH | 0.282299 |
AIRLOOP M NW MAIN BRANCH | 0.255888 |
AIRLOOP M SE MAIN BRANCH | 0.255585 |
AIRLOOP M NE MAIN BRANCH | 0.194673 |
AIRLOOP M N1 MAIN BRANCH | 0.140259 |
AIRLOOP M N2 MAIN BRANCH | 0.138910 |
AIRLOOP M S1 MAIN BRANCH | 0.188767 |
AIRLOOP M S2 MAIN BRANCH | 0.189614 |
AIRLOOP F6 SW MAIN BRANCH | 0.279770 |
AIRLOOP F6 NW MAIN BRANCH | 0.253311 |
AIRLOOP F6 SE MAIN BRANCH | 0.253102 |
AIRLOOP F6 NE MAIN BRANCH | 0.191641 |
AIRLOOP F6 N1 MAIN BRANCH | 0.137843 |
AIRLOOP F6 N2 MAIN BRANCH | 0.136502 |
AIRLOOP F6 S1 MAIN BRANCH | 0.186143 |
AIRLOOP F6 S2 MAIN BRANCH | 0.186985 |
AIRLOOP F7 SW MAIN BRANCH | 0.279239 |
AIRLOOP F7 NW MAIN BRANCH | 0.252800 |
AIRLOOP F7 SE MAIN BRANCH | 0.252628 |
AIRLOOP F7 NE MAIN BRANCH | 0.190689 |
AIRLOOP F7 N1 MAIN BRANCH | 0.137373 |
AIRLOOP F7 N2 MAIN BRANCH | 0.136039 |
AIRLOOP F7 S1 MAIN BRANCH | 0.185489 |
AIRLOOP F7 S2 MAIN BRANCH | 0.186327 |
AIRLOOP F8 SW MAIN BRANCH | 0.279858 |
AIRLOOP F8 NW MAIN BRANCH | 0.253479 |
AIRLOOP F8 SE MAIN BRANCH | 0.253274 |
AIRLOOP F8 NE MAIN BRANCH | 0.190880 |
AIRLOOP F8 N1 MAIN BRANCH | 0.138093 |
AIRLOOP F8 N2 MAIN BRANCH | 0.136766 |
AIRLOOP F8 S1 MAIN BRANCH | 0.185967 |
AIRLOOP F8 S2 MAIN BRANCH | 0.186805 |
AIRLOOP F9 SW MAIN BRANCH | 0.288623 |
AIRLOOP F9 NW MAIN BRANCH | 0.262511 |
AIRLOOP F9 SE MAIN BRANCH | 0.260045 |
AIRLOOP F9 NE MAIN BRANCH | 0.194166 |
AIRLOOP F9 N1 MAIN BRANCH | 0.145883 |
AIRLOOP F9 N2 MAIN BRANCH | 0.144530 |
AIRLOOP F9 S1 MAIN BRANCH | 0.191581 |
AIRLOOP F9 S2 MAIN BRANCH | 0.192406 |
AIRLOOP T SW MAIN BRANCH | 0.357686 |
AIRLOOP T NW MAIN BRANCH | 0.318351 |
AIRLOOP T SE MAIN BRANCH | 0.322787 |
AIRLOOP T NE MAIN BRANCH | 0.242581 |
AIRLOOP T N1 MAIN BRANCH | 0.186653 |
AIRLOOP T N2 MAIN BRANCH | 0.186451 |
AIRLOOP T S1 MAIN BRANCH | 0.264114 |
AIRLOOP T S2 MAIN BRANCH | 0.264908 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.208526 |
AIRLOOP G NW | 0.187195 |
AIRLOOP OFFICE | 0.325790 |
AIRLOOP G NE | 0.156235 |
AIRLOOP G N1 | 0.106987 |
AIRLOOP G N2 | 0.106982 |
AIRLOOP G S1 | 0.132893 |
AIRLOOP G S2 | 0.139184 |
AIRLOOP F2 SW | 0.274797 |
AIRLOOP F2 NW | 0.247392 |
AIRLOOP F2 SE | 0.270610 |
AIRLOOP F2 NE | 0.187579 |
AIRLOOP F2 N1 | 0.131032 |
AIRLOOP F2 N2 | 0.129668 |
AIRLOOP F2 S1 | 0.180117 |
AIRLOOP F2 S2 | 0.182448 |
AIRLOOP F3 SW | 0.277518 |
AIRLOOP F3 NW | 0.250925 |
AIRLOOP F3 SE | 0.253027 |
AIRLOOP F3 NE | 0.191133 |
AIRLOOP F3 N1 | 0.135403 |
AIRLOOP F3 N2 | 0.134050 |
AIRLOOP F3 S1 | 0.184298 |
AIRLOOP F3 S2 | 0.185361 |
AIRLOOP F4 SW | 0.279105 |
AIRLOOP F4 NW | 0.252601 |
AIRLOOP F4 SE | 0.252608 |
AIRLOOP F4 NE | 0.192054 |
AIRLOOP F4 N1 | 0.137112 |
AIRLOOP F4 N2 | 0.135761 |
AIRLOOP F4 S1 | 0.185778 |
AIRLOOP F4 S2 | 0.186655 |
AIRLOOP M SW | 0.282299 |
AIRLOOP M NW | 0.255888 |
AIRLOOP M SE | 0.255585 |
AIRLOOP M NE | 0.194673 |
AIRLOOP M N1 | 0.140259 |
AIRLOOP M N2 | 0.138910 |
AIRLOOP M S1 | 0.188767 |
AIRLOOP M S2 | 0.189614 |
AIRLOOP F6 SW | 0.279770 |
AIRLOOP F6 NW | 0.253311 |
AIRLOOP F6 SE | 0.253102 |
AIRLOOP F6 NE | 0.191641 |
AIRLOOP F6 N1 | 0.137843 |
AIRLOOP F6 N2 | 0.136502 |
AIRLOOP F6 S1 | 0.186143 |
AIRLOOP F6 S2 | 0.186985 |
AIRLOOP F7 SW | 0.279239 |
AIRLOOP F7 NW | 0.252800 |
AIRLOOP F7 SE | 0.252628 |
AIRLOOP F7 NE | 0.190689 |
AIRLOOP F7 N1 | 0.137373 |
AIRLOOP F7 N2 | 0.136039 |
AIRLOOP F7 S1 | 0.185489 |
AIRLOOP F7 S2 | 0.186327 |
AIRLOOP F8 SW | 0.279858 |
AIRLOOP F8 NW | 0.253479 |
AIRLOOP F8 SE | 0.253274 |
AIRLOOP F8 NE | 0.190880 |
AIRLOOP F8 N1 | 0.138093 |
AIRLOOP F8 N2 | 0.136766 |
AIRLOOP F8 S1 | 0.185967 |
AIRLOOP F8 S2 | 0.186805 |
AIRLOOP F9 SW | 0.288623 |
AIRLOOP F9 NW | 0.262511 |
AIRLOOP F9 SE | 0.260045 |
AIRLOOP F9 NE | 0.194166 |
AIRLOOP F9 N1 | 0.145883 |
AIRLOOP F9 N2 | 0.144530 |
AIRLOOP F9 S1 | 0.191581 |
AIRLOOP F9 S2 | 0.192406 |
AIRLOOP T SW | 0.357686 |
AIRLOOP T NW | 0.318351 |
AIRLOOP T SE | 0.322787 |
AIRLOOP T NE | 0.242581 |
AIRLOOP T N1 | 0.186653 |
AIRLOOP T N2 | 0.186451 |
AIRLOOP T S1 | 0.264114 |
AIRLOOP T S2 | 0.264908 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.208526 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.187195 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.325790 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.156235 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.106987 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.106982 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.132893 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.139184 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.274797 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.247392 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.270610 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.187579 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.131032 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.129668 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.180117 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.182448 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.277518 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.250925 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.253027 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.191133 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.135403 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.134050 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.184298 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.185361 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.279105 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.252601 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.252608 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.192054 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.137112 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.135761 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.185778 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.186655 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.282299 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.255888 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.255585 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.194673 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.140259 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.138910 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.188767 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.189614 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.279770 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.253311 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.253102 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.191641 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.137843 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.136502 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.186143 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.186985 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.279239 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.252800 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.252628 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.190689 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.137373 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.136039 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.185489 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.186327 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.279858 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.253479 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.253274 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.190880 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.138093 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.136766 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.185967 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.186805 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.288623 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.262511 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.260045 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.194166 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.145883 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.144530 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.191581 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.192406 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.357686 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.318351 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.322787 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.242581 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.186653 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.186451 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.264114 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.264908 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.208526 | 3615.89 | 2481.30 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.187195 | 3274.33 | 2230.09 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.325790 | 5487.24 | 3826.54 | 0.000120 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.156235 | 2865.06 | 1896.97 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.106987 | 2114.52 | 1356.97 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.106982 | 2123.52 | 1360.25 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.132893 | 2486.75 | 1648.50 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.139184 | 2576.07 | 1716.41 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.274797 | 4609.02 | 3210.05 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.247392 | 4198.77 | 2900.91 | 0.000092 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.270610 | 4567.41 | 3173.61 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.187579 | 3291.40 | 2228.56 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.131032 | 2426.09 | 1602.37 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.129668 | 2406.11 | 1587.54 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.180117 | 3198.48 | 2171.12 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.182448 | 3231.48 | 2196.27 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.277518 | 4689.66 | 3251.77 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.250925 | 4289.48 | 2951.12 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.253027 | 4359.19 | 2995.77 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.191133 | 3387.18 | 2282.92 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.135403 | 2510.47 | 1656.44 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.134050 | 2490.59 | 1641.71 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.184298 | 3281.95 | 2223.57 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.185361 | 3296.98 | 2235.04 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.279105 | 4748.68 | 3280.84 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.252601 | 4343.30 | 2978.20 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.252608 | 4383.30 | 3000.22 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.192054 | 3427.72 | 2301.36 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.137112 | 2550.81 | 1679.95 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.135761 | 2530.89 | 1665.22 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.185778 | 3320.96 | 2245.02 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.186655 | 3333.37 | 2254.48 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.282299 | 4819.33 | 3322.83 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.255888 | 4414.47 | 3021.03 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.255585 | 4450.14 | 3039.74 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.194673 | 3487.52 | 2336.60 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.140259 | 2609.34 | 1718.17 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.138910 | 2589.43 | 1703.46 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.188767 | 3378.20 | 2281.80 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.189614 | 3390.20 | 2290.93 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.279770 | 4804.55 | 3301.81 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.253311 | 4397.84 | 2999.26 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.253102 | 4435.03 | 3019.02 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.191641 | 3461.88 | 2309.49 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.137843 | 2584.31 | 1695.28 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.136502 | 2564.43 | 1680.65 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.186143 | 3352.94 | 2257.15 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.186985 | 3364.87 | 2266.22 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.279239 | 4815.47 | 3301.59 | 0.000105 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.252800 | 4408.15 | 2999.08 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.252628 | 4448.89 | 3020.82 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.190689 | 3463.85 | 2304.16 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.137373 | 2586.42 | 1693.12 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.136039 | 2566.57 | 1678.54 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.185489 | 3354.25 | 2253.34 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.186327 | 3366.15 | 2262.39 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.279858 | 4840.81 | 3313.23 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.253479 | 4433.65 | 3011.23 | 0.000097 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.253274 | 4473.98 | 3032.63 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.190880 | 3480.66 | 2310.70 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.138093 | 2605.10 | 1703.60 | 0.000057 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.136766 | 2585.31 | 1689.08 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.185967 | 3370.65 | 2261.47 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.186805 | 3382.56 | 2270.50 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.288623 | 4976.17 | 3409.99 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.262511 | 4578.53 | 3113.66 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.260045 | 4586.19 | 3110.55 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.194166 | 3550.26 | 2355.27 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.145883 | 2727.79 | 1790.96 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.144530 | 2707.68 | 1776.18 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.191581 | 3463.06 | 2326.54 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.192406 | 3474.79 | 2335.45 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.357686 | 5999.32 | 4173.57 | 0.000131 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.318351 | 5415.59 | 3736.12 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.322787 | 5496.21 | 3792.90 | 0.000120 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.242581 | 4353.25 | 2928.18 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.186653 | 3402.57 | 2276.94 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.186451 | 3399.99 | 2274.85 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.264114 | 4504.17 | 3112.60 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.264908 | 4515.29 | 3121.14 | 0.000099 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.208526 | 0.208526 | 0.208526 | 0.208526 | 3615.89 | 3615.89 | 4791.42 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.187195 | 0.187195 | 0.187195 | 0.187195 | 3274.33 | 3274.33 | 4792.71 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.325790 | 0.325790 | 0.325790 | 0.325790 | 5487.24 | 5487.24 | 5842.94 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.156235 | 0.156235 | 0.156235 | 0.156235 | 2865.06 | 2865.06 | 4787.47 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.106987 | 0.106987 | 0.106987 | 0.106987 | 2114.52 | 2114.52 | 3709.69 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.106982 | 0.106982 | 0.106982 | 0.106982 | 2123.52 | 2123.52 | 3709.57 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.132893 | 0.132893 | 0.132893 | 0.132893 | 2486.75 | 2486.75 | 3705.85 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.139184 | 0.139184 | 0.139184 | 0.139184 | 2576.07 | 2576.07 | 3712.01 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.274797 | 0.274797 | 0.274797 | 0.274797 | 4609.02 | 4609.02 | 4635.62 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.247392 | 0.247392 | 0.247392 | 0.247392 | 4198.77 | 4198.77 | 4629.05 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.270610 | 0.270610 | 0.270610 | 0.270610 | 4567.41 | 4567.41 | 4650.10 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.187579 | 0.187579 | 0.187579 | 0.187579 | 3291.40 | 3291.40 | 4625.42 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.131032 | 0.131032 | 0.131032 | 0.131032 | 2426.09 | 2426.09 | 3290.66 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.129668 | 0.129668 | 0.129668 | 0.129668 | 2406.11 | 2406.11 | 3290.58 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.180117 | 0.180117 | 0.180117 | 0.180117 | 3198.48 | 3198.48 | 3300.33 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.182448 | 0.182448 | 0.182448 | 0.182448 | 3231.48 | 3231.48 | 3301.36 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.277518 | 0.277518 | 0.277518 | 0.277518 | 4689.66 | 4689.66 | 4687.04 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.250925 | 0.250925 | 0.250925 | 0.250925 | 4289.48 | 4289.48 | 4685.82 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.253027 | 0.253027 | 0.253027 | 0.253027 | 4359.19 | 4359.19 | 4687.32 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.191133 | 0.191133 | 0.191133 | 0.191133 | 3387.18 | 3387.18 | 4684.26 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.135403 | 0.135403 | 0.135403 | 0.135403 | 2510.47 | 2510.47 | 3270.88 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.134050 | 0.134050 | 0.134050 | 0.134050 | 2490.59 | 2490.59 | 3270.85 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.184298 | 0.184298 | 0.184298 | 0.184298 | 3281.95 | 3281.95 | 3273.27 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.185361 | 0.185361 | 0.185361 | 0.185361 | 3296.98 | 3296.98 | 3273.39 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.279105 | 0.279105 | 0.279105 | 0.279105 | 4748.68 | 4748.68 | 4808.92 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.252601 | 0.252601 | 0.252601 | 0.252601 | 4343.30 | 4343.30 | 4811.12 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.252608 | 0.252608 | 0.252608 | 0.252608 | 4383.30 | 4383.30 | 4809.21 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.192054 | 0.192054 | 0.192054 | 0.192054 | 3427.72 | 3427.72 | 4811.23 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.137112 | 0.137112 | 0.137112 | 0.137112 | 2550.81 | 2550.81 | 3334.65 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.135761 | 0.135761 | 0.135761 | 0.135761 | 2530.89 | 2530.89 | 3334.66 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.185778 | 0.185778 | 0.185778 | 0.185778 | 3320.96 | 3320.96 | 3333.33 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.186655 | 0.186655 | 0.186655 | 0.186655 | 3333.37 | 3333.37 | 3333.35 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.282299 | 0.282299 | 0.282299 | 0.282299 | 4819.33 | 4819.33 | 4901.86 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.255888 | 0.255888 | 0.255888 | 0.255888 | 4414.47 | 4414.47 | 4905.43 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.255585 | 0.255585 | 0.255585 | 0.255585 | 4450.14 | 4450.14 | 4903.41 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.194673 | 0.194673 | 0.194673 | 0.194673 | 3487.52 | 3487.52 | 4906.96 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.140259 | 0.140259 | 0.140259 | 0.140259 | 2609.34 | 2609.34 | 3379.84 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.138910 | 0.138910 | 0.138910 | 0.138910 | 2589.43 | 2589.43 | 3379.87 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.188767 | 0.188767 | 0.188767 | 0.188767 | 3378.20 | 3378.20 | 3377.05 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.189614 | 0.189614 | 0.189614 | 0.189614 | 3390.20 | 3390.20 | 3377.08 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.279770 | 0.279770 | 0.279770 | 0.279770 | 4804.55 | 4804.55 | 5046.01 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.253311 | 0.253311 | 0.253311 | 0.253311 | 4397.84 | 4397.84 | 5052.40 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.253102 | 0.253102 | 0.253102 | 0.253102 | 4435.03 | 4435.03 | 5048.77 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.191641 | 0.191641 | 0.191641 | 0.191641 | 3461.88 | 3461.88 | 5055.16 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.137843 | 0.137843 | 0.137843 | 0.137843 | 2584.31 | 2584.31 | 3482.67 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.136502 | 0.136502 | 0.136502 | 0.136502 | 2564.43 | 2564.43 | 3482.74 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.186143 | 0.186143 | 0.186143 | 0.186143 | 3352.94 | 3352.94 | 3477.05 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.186985 | 0.186985 | 0.186985 | 0.186985 | 3364.87 | 3364.87 | 3477.11 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.279239 | 0.279239 | 0.279239 | 0.279239 | 4815.47 | 4815.47 | 5156.64 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.252800 | 0.252800 | 0.252800 | 0.252800 | 4408.15 | 4408.15 | 5164.48 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.252628 | 0.252628 | 0.252628 | 0.252628 | 4448.89 | 4448.89 | 5160.47 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.190689 | 0.190689 | 0.190689 | 0.190689 | 3463.85 | 3463.85 | 5168.32 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.137373 | 0.137373 | 0.137373 | 0.137373 | 2586.42 | 2586.42 | 3557.01 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.136039 | 0.136039 | 0.136039 | 0.136039 | 2566.57 | 2566.57 | 3557.10 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.185489 | 0.185489 | 0.185489 | 0.185489 | 3354.25 | 3354.25 | 3549.93 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.186327 | 0.186327 | 0.186327 | 0.186327 | 3366.15 | 3366.15 | 3550.02 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.279858 | 0.279858 | 0.279858 | 0.279858 | 4840.81 | 4840.81 | 5270.43 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.253479 | 0.253479 | 0.253479 | 0.253479 | 4433.65 | 4433.65 | 5279.20 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.253274 | 0.253274 | 0.253274 | 0.253274 | 4473.98 | 4473.98 | 5275.22 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.190880 | 0.190880 | 0.190880 | 0.190880 | 3480.66 | 3480.66 | 5283.99 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.138093 | 0.138093 | 0.138093 | 0.138093 | 2605.10 | 2605.10 | 3638.12 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.136766 | 0.136766 | 0.136766 | 0.136766 | 2585.31 | 2585.31 | 3638.22 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.185967 | 0.185967 | 0.185967 | 0.185967 | 3370.65 | 3370.65 | 3630.10 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.186805 | 0.186805 | 0.186805 | 0.186805 | 3382.56 | 3382.56 | 3630.21 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.288623 | 0.288623 | 0.288623 | 0.288623 | 4976.17 | 4976.17 | 5546.58 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.262511 | 0.262511 | 0.262511 | 0.262511 | 4578.53 | 4578.53 | 5553.04 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.260045 | 0.260045 | 0.260045 | 0.260045 | 4586.19 | 4586.19 | 5552.28 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.194166 | 0.194166 | 0.194166 | 0.194166 | 3550.26 | 3550.26 | 5558.75 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.145883 | 0.145883 | 0.145883 | 0.145883 | 2727.79 | 2727.79 | 3870.79 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.144530 | 0.144530 | 0.144530 | 0.144530 | 2707.68 | 2707.68 | 3870.92 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.191581 | 0.191581 | 0.191581 | 0.191581 | 3463.06 | 3463.06 | 3864.63 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.192406 | 0.192406 | 0.192406 | 0.192406 | 3474.79 | 3474.79 | 3864.76 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.357686 | 0.357686 | 0.357686 | 0.357686 | 5999.32 | 5999.32 | 6473.79 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.318351 | 0.318351 | 0.318351 | 0.318351 | 5415.59 | 5415.59 | 6489.18 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.322787 | 0.322787 | 0.322787 | 0.322787 | 5496.21 | 5496.21 | 6479.78 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.242581 | 0.242581 | 0.242581 | 0.242581 | 4353.25 | 4353.25 | 6495.17 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.186653 | 0.186653 | 0.186653 | 0.186653 | 3402.57 | 3402.57 | 4848.84 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.186451 | 0.186451 | 0.186451 | 0.186451 | 3399.99 | 3399.99 | 4848.98 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.264114 | 0.264114 | 0.264114 | 0.264114 | 4504.17 | 4504.17 | 4830.67 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.264908 | 0.264908 | 0.264908 | 0.264908 | 4515.29 | 4515.29 | 4830.81 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.208526 |
AIRLOOP G NW SUPPLY FAN | 0.187195 |
AIRLOOP OFFICE SUPPLY FAN | 0.325790 |
AIRLOOP G NE SUPPLY FAN | 0.156235 |
AIRLOOP G N1 SUPPLY FAN | 0.106987 |
AIRLOOP G N2 SUPPLY FAN | 0.106982 |
AIRLOOP G S1 SUPPLY FAN | 0.132893 |
AIRLOOP G S2 SUPPLY FAN | 0.139184 |
AIRLOOP F2 SW SUPPLY FAN | 0.274797 |
AIRLOOP F2 NW SUPPLY FAN | 0.247392 |
AIRLOOP F2 SE SUPPLY FAN | 0.270610 |
AIRLOOP F2 NE SUPPLY FAN | 0.187579 |
AIRLOOP F2 N1 SUPPLY FAN | 0.131032 |
AIRLOOP F2 N2 SUPPLY FAN | 0.129668 |
AIRLOOP F2 S1 SUPPLY FAN | 0.180117 |
AIRLOOP F2 S2 SUPPLY FAN | 0.182448 |
AIRLOOP F3 SW SUPPLY FAN | 0.277518 |
AIRLOOP F3 NW SUPPLY FAN | 0.250925 |
AIRLOOP F3 SE SUPPLY FAN | 0.253027 |
AIRLOOP F3 NE SUPPLY FAN | 0.191133 |
AIRLOOP F3 N1 SUPPLY FAN | 0.135403 |
AIRLOOP F3 N2 SUPPLY FAN | 0.134050 |
AIRLOOP F3 S1 SUPPLY FAN | 0.184298 |
AIRLOOP F3 S2 SUPPLY FAN | 0.185361 |
AIRLOOP F4 SW SUPPLY FAN | 0.279105 |
AIRLOOP F4 NW SUPPLY FAN | 0.252601 |
AIRLOOP F4 SE SUPPLY FAN | 0.252608 |
AIRLOOP F4 NE SUPPLY FAN | 0.192054 |
AIRLOOP F4 N1 SUPPLY FAN | 0.137112 |
AIRLOOP F4 N2 SUPPLY FAN | 0.135761 |
AIRLOOP F4 S1 SUPPLY FAN | 0.185778 |
AIRLOOP F4 S2 SUPPLY FAN | 0.186655 |
AIRLOOP M SW SUPPLY FAN | 0.282299 |
AIRLOOP M NW SUPPLY FAN | 0.255888 |
AIRLOOP M SE SUPPLY FAN | 0.255585 |
AIRLOOP M NE SUPPLY FAN | 0.194673 |
AIRLOOP M N1 SUPPLY FAN | 0.140259 |
AIRLOOP M N2 SUPPLY FAN | 0.138910 |
AIRLOOP M S1 SUPPLY FAN | 0.188767 |
AIRLOOP M S2 SUPPLY FAN | 0.189614 |
AIRLOOP F6 SW SUPPLY FAN | 0.279770 |
AIRLOOP F6 NW SUPPLY FAN | 0.253311 |
AIRLOOP F6 SE SUPPLY FAN | 0.253102 |
AIRLOOP F6 NE SUPPLY FAN | 0.191641 |
AIRLOOP F6 N1 SUPPLY FAN | 0.137843 |
AIRLOOP F6 N2 SUPPLY FAN | 0.136502 |
AIRLOOP F6 S1 SUPPLY FAN | 0.186143 |
AIRLOOP F6 S2 SUPPLY FAN | 0.186985 |
AIRLOOP F7 SW SUPPLY FAN | 0.279239 |
AIRLOOP F7 NW SUPPLY FAN | 0.252800 |
AIRLOOP F7 SE SUPPLY FAN | 0.252628 |
AIRLOOP F7 NE SUPPLY FAN | 0.190689 |
AIRLOOP F7 N1 SUPPLY FAN | 0.137373 |
AIRLOOP F7 N2 SUPPLY FAN | 0.136039 |
AIRLOOP F7 S1 SUPPLY FAN | 0.185489 |
AIRLOOP F7 S2 SUPPLY FAN | 0.186327 |
AIRLOOP F8 SW SUPPLY FAN | 0.279858 |
AIRLOOP F8 NW SUPPLY FAN | 0.253479 |
AIRLOOP F8 SE SUPPLY FAN | 0.253274 |
AIRLOOP F8 NE SUPPLY FAN | 0.190880 |
AIRLOOP F8 N1 SUPPLY FAN | 0.138093 |
AIRLOOP F8 N2 SUPPLY FAN | 0.136766 |
AIRLOOP F8 S1 SUPPLY FAN | 0.185967 |
AIRLOOP F8 S2 SUPPLY FAN | 0.186805 |
AIRLOOP F9 SW SUPPLY FAN | 0.288623 |
AIRLOOP F9 NW SUPPLY FAN | 0.262511 |
AIRLOOP F9 SE SUPPLY FAN | 0.260045 |
AIRLOOP F9 NE SUPPLY FAN | 0.194166 |
AIRLOOP F9 N1 SUPPLY FAN | 0.145883 |
AIRLOOP F9 N2 SUPPLY FAN | 0.144530 |
AIRLOOP F9 S1 SUPPLY FAN | 0.191581 |
AIRLOOP F9 S2 SUPPLY FAN | 0.192406 |
AIRLOOP T SW SUPPLY FAN | 0.357686 |
AIRLOOP T NW SUPPLY FAN | 0.318351 |
AIRLOOP T SE SUPPLY FAN | 0.322787 |
AIRLOOP T NE SUPPLY FAN | 0.242581 |
AIRLOOP T N1 SUPPLY FAN | 0.186653 |
AIRLOOP T N2 SUPPLY FAN | 0.186451 |
AIRLOOP T S1 SUPPLY FAN | 0.264114 |
AIRLOOP T S2 SUPPLY FAN | 0.264908 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.208526 | 3615.89 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.187195 | 3274.33 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.325790 | 5487.24 | 0.000120 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.156235 | 2865.06 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.106987 | 2114.52 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.106982 | 2123.52 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.132893 | 2486.75 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.139184 | 2576.07 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.274797 | 4609.02 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.247392 | 4198.77 | 0.000092 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.270610 | 4567.41 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.187579 | 3291.40 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.131032 | 2426.09 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.129668 | 2406.11 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.180117 | 3198.48 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.182448 | 3231.48 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.277518 | 4689.66 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.250925 | 4289.48 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.253027 | 4359.19 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.191133 | 3387.18 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.135403 | 2510.47 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.134050 | 2490.59 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.184298 | 3281.95 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.185361 | 3296.98 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.279105 | 4748.68 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.252601 | 4343.30 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.252608 | 4383.30 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.192054 | 3427.72 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.137112 | 2550.81 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.135761 | 2530.89 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.185778 | 3320.96 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.186655 | 3333.37 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.282299 | 4819.33 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.255888 | 4414.47 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.255585 | 4450.14 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.194673 | 3487.52 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.140259 | 2609.34 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.138910 | 2589.43 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.188767 | 3378.20 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.189614 | 3390.20 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.279770 | 4804.55 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.253311 | 4397.84 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.253102 | 4435.03 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.191641 | 3461.88 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.137843 | 2584.31 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.136502 | 2564.43 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.186143 | 3352.94 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.186985 | 3364.87 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.279239 | 4815.47 | 0.000105 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.252800 | 4408.15 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.252628 | 4448.89 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.190689 | 3463.85 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.137373 | 2586.42 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.136039 | 2566.57 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.185489 | 3354.25 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.186327 | 3366.15 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.279858 | 4840.81 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.253479 | 4433.65 | 0.000097 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.253274 | 4473.98 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.190880 | 3480.66 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.138093 | 2605.10 | 0.000057 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.136766 | 2585.31 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.185967 | 3370.65 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.186805 | 3382.56 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.288623 | 4976.17 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.262511 | 4578.53 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.260045 | 4586.19 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.194166 | 3550.26 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.145883 | 2727.79 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.144530 | 2707.68 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.191581 | 3463.06 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.192406 | 3474.79 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.357686 | 5999.32 | 0.000131 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.318351 | 5415.59 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.322787 | 5496.21 | 0.000120 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.242581 | 4353.25 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.186653 | 3402.57 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.186451 | 3399.99 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.264114 | 4504.17 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.264908 | 4515.29 | 0.000099 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 4791.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 4792.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 5842.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 4787.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 3709.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 3709.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 3705.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 3712.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 4635.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 4629.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 4650.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 4625.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 3290.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 3290.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 3300.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 3301.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 4687.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 4685.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 4687.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 4684.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 3270.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 3270.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 3273.27 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 3273.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 4808.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 4811.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 4809.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 4811.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 3334.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 3334.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 3333.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 3333.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 4901.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 4905.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 4903.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 4906.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 3379.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 3379.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 3377.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 3377.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 5046.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 5052.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 5048.77 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 5055.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 3482.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 3482.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 3477.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 3477.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 5156.64 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 5164.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 5160.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 5168.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 3557.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 3557.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 3549.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 3550.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 5270.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 5279.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 5275.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 5283.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 3638.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 3638.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 3630.10 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 3630.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 5546.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 5553.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 5552.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 5558.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 3870.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 3870.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 3864.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 3864.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 6473.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 6489.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 6479.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 6495.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 4848.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 4848.98 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 4830.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 4830.81 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.006397 | 7.20 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.006397 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.006397 | 3088.25 | 8.22 | 9469.02 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.006397 | 2042.95 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.72 | -5.6 |
March | 21.92 | -0.5 |
April | 22.27 | 7.83 |
May | 22.83 | 13.82 |
June | 24.09 | 19.28 |
July | 24.19 | 21.06 |
August | 24.18 | 19.79 |
September | 23.68 | 15.09 |
October | 22.29 | 8.66 |
November | 21.87 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.71 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.19 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.04 | 7.83 |
May | 22.58 | 13.82 |
June | 24.07 | 19.28 |
July | 24.18 | 21.06 |
August | 24.09 | 19.79 |
September | 23.38 | 15.09 |
October | 21.86 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.57 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.18 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.09 | -0.5 |
April | 22.67 | 7.83 |
May | 23.48 | 13.82 |
June | 24.34 | 19.28 |
July | 24.37 | 21.06 |
August | 24.35 | 19.79 |
September | 23.90 | 15.09 |
October | 22.75 | 8.66 |
November | 22.10 | 2.78 |
December | 21.79 | -1.5 |
Annual Sum or Average | 22.95 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.37 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.71 | -0.5 |
April | 22.01 | 7.83 |
May | 22.52 | 13.82 |
June | 24.07 | 19.28 |
July | 24.19 | 21.06 |
August | 24.08 | 19.79 |
September | 23.34 | 15.09 |
October | 21.80 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.55 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.19 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.70 | -0.5 |
April | 21.93 | 7.83 |
May | 22.34 | 13.82 |
June | 23.96 | 19.28 |
July | 24.11 | 21.06 |
August | 23.99 | 19.79 |
September | 23.35 | 15.09 |
October | 21.83 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.50 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.11 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.70 | -0.5 |
April | 21.93 | 7.83 |
May | 22.33 | 13.82 |
June | 23.96 | 19.28 |
July | 24.11 | 21.06 |
August | 23.99 | 19.79 |
September | 23.35 | 15.09 |
October | 21.82 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.50 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.11 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.72 | -5.6 |
March | 21.90 | -0.5 |
April | 22.19 | 7.83 |
May | 22.68 | 13.82 |
June | 24.02 | 19.28 |
July | 24.16 | 21.06 |
August | 24.15 | 19.79 |
September | 23.77 | 15.09 |
October | 22.38 | 8.66 |
November | 21.91 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.70 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.16 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 21.92 | -0.5 |
April | 22.23 | 7.83 |
May | 22.76 | 13.82 |
June | 24.05 | 19.28 |
July | 24.17 | 21.06 |
August | 24.17 | 19.79 |
September | 23.81 | 15.09 |
October | 22.43 | 8.66 |
November | 21.93 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.72 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.17 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.16 | -7.2 |
February | 13.65 | -5.6 |
March | 15.46 | -0.5 |
April | 18.51 | 7.83 |
May | 20.87 | 13.82 |
June | 23.80 | 19.28 |
July | 24.57 | 21.06 |
August | 24.09 | 19.79 |
September | 22.11 | 15.09 |
October | 18.72 | 8.66 |
November | 16.33 | 2.78 |
December | 14.77 | -1.5 |
Annual Sum or Average | 18.86 | 7.87 |
Minimum of Months | 13.16 | -7.2 |
Maximum of Months | 24.57 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.14 | -0.5 |
April | 22.74 | 7.83 |
May | 23.75 | 13.82 |
June | 24.30 | 19.28 |
July | 24.32 | 21.06 |
August | 24.32 | 19.79 |
September | 23.91 | 15.09 |
October | 22.83 | 8.66 |
November | 22.03 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.97 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.79 | -0.5 |
April | 22.32 | 7.83 |
May | 23.41 | 13.82 |
June | 24.30 | 19.28 |
July | 24.31 | 21.06 |
August | 24.24 | 19.79 |
September | 23.59 | 15.09 |
October | 22.05 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.21 | -0.5 |
April | 22.90 | 7.83 |
May | 23.93 | 13.82 |
June | 24.34 | 19.28 |
July | 24.35 | 21.06 |
August | 24.35 | 19.79 |
September | 23.99 | 15.09 |
October | 22.99 | 8.66 |
November | 22.09 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 23.03 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.35 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.27 | 7.83 |
May | 23.30 | 13.82 |
June | 24.30 | 19.28 |
July | 24.33 | 21.06 |
August | 24.24 | 19.79 |
September | 23.52 | 15.09 |
October | 21.93 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.71 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.19 | 7.83 |
May | 23.15 | 13.82 |
June | 24.24 | 19.28 |
July | 24.27 | 21.06 |
August | 24.16 | 19.79 |
September | 23.57 | 15.09 |
October | 22.02 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.69 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.27 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.19 | 7.83 |
May | 23.14 | 13.82 |
June | 24.24 | 19.28 |
July | 24.28 | 21.06 |
August | 24.16 | 19.79 |
September | 23.57 | 15.09 |
October | 22.01 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.68 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.20 | -0.5 |
April | 22.77 | 7.83 |
May | 23.68 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.30 | 19.79 |
September | 24.03 | 15.09 |
October | 23.09 | 8.66 |
November | 22.16 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.01 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.21 | -0.5 |
April | 22.79 | 7.83 |
May | 23.72 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.31 | 19.79 |
September | 24.04 | 15.09 |
October | 23.12 | 8.66 |
November | 22.17 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.02 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -7.2 |
February | 20.75 | -5.6 |
March | 21.60 | -0.5 |
April | 23.09 | 7.83 |
May | 24.49 | 13.82 |
June | 25.94 | 19.28 |
July | 26.14 | 21.06 |
August | 25.98 | 19.79 |
September | 25.01 | 15.09 |
October | 23.03 | 8.66 |
November | 21.68 | 2.78 |
December | 20.87 | -1.5 |
Annual Sum or Average | 23.27 | 7.87 |
Minimum of Months | 20.51 | -7.2 |
Maximum of Months | 26.14 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.18 | -0.5 |
April | 22.82 | 7.83 |
May | 23.90 | 13.82 |
June | 24.29 | 19.28 |
July | 24.31 | 21.06 |
August | 24.32 | 19.79 |
September | 23.90 | 15.09 |
October | 22.91 | 8.66 |
November | 22.06 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 23.00 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.38 | 7.83 |
May | 23.58 | 13.82 |
June | 24.30 | 19.28 |
July | 24.31 | 21.06 |
August | 24.25 | 19.79 |
September | 23.59 | 15.09 |
October | 22.09 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.77 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.18 | -0.5 |
April | 22.86 | 7.83 |
May | 23.93 | 13.82 |
June | 24.31 | 19.28 |
July | 24.33 | 21.06 |
August | 24.34 | 19.79 |
September | 23.91 | 15.09 |
October | 22.92 | 8.66 |
November | 22.06 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 23.01 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.33 | 7.83 |
May | 23.48 | 13.82 |
June | 24.31 | 19.28 |
July | 24.34 | 21.06 |
August | 24.24 | 19.79 |
September | 23.52 | 15.09 |
October | 21.96 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.30 | 7.83 |
May | 23.39 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.18 | 19.79 |
September | 23.60 | 15.09 |
October | 22.09 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.73 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.29 | 7.83 |
May | 23.38 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.18 | 19.79 |
September | 23.59 | 15.09 |
October | 22.08 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.73 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.80 | -5.6 |
March | 22.27 | -0.5 |
April | 22.93 | 7.83 |
May | 23.91 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.31 | 19.79 |
September | 24.04 | 15.09 |
October | 23.27 | 8.66 |
November | 22.21 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.07 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.80 | -5.6 |
March | 22.27 | -0.5 |
April | 22.94 | 7.83 |
May | 23.92 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.31 | 19.79 |
September | 24.04 | 15.09 |
October | 23.28 | 8.66 |
November | 22.22 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.07 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.10 | -7.2 |
February | 21.32 | -5.6 |
March | 22.15 | -0.5 |
April | 23.58 | 7.83 |
May | 25.01 | 13.82 |
June | 26.15 | 19.28 |
July | 26.30 | 21.06 |
August | 26.16 | 19.79 |
September | 25.24 | 15.09 |
October | 23.46 | 8.66 |
November | 22.13 | 2.78 |
December | 21.35 | -1.5 |
Annual Sum or Average | 23.67 | 7.87 |
Minimum of Months | 21.10 | -7.2 |
Maximum of Months | 26.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.17 | -0.5 |
April | 22.80 | 7.83 |
May | 23.91 | 13.82 |
June | 24.28 | 19.28 |
July | 24.31 | 21.06 |
August | 24.33 | 19.79 |
September | 23.89 | 15.09 |
October | 22.92 | 8.66 |
November | 22.05 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.99 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.38 | 7.83 |
May | 23.60 | 13.82 |
June | 24.30 | 19.28 |
July | 24.31 | 21.06 |
August | 24.26 | 19.79 |
September | 23.59 | 15.09 |
October | 22.10 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.77 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.16 | -0.5 |
April | 22.82 | 7.83 |
May | 23.91 | 13.82 |
June | 24.30 | 19.28 |
July | 24.33 | 21.06 |
August | 24.34 | 19.79 |
September | 23.89 | 15.09 |
October | 22.88 | 8.66 |
November | 22.04 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.99 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.34 | 7.83 |
May | 23.51 | 13.82 |
June | 24.30 | 19.28 |
July | 24.34 | 21.06 |
August | 24.25 | 19.79 |
September | 23.53 | 15.09 |
October | 21.97 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.32 | 7.83 |
May | 23.46 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.20 | 19.79 |
September | 23.62 | 15.09 |
October | 22.12 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.32 | 7.83 |
May | 23.45 | 13.82 |
June | 24.26 | 19.28 |
July | 24.29 | 21.06 |
August | 24.20 | 19.79 |
September | 23.62 | 15.09 |
October | 22.11 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.27 | -0.5 |
April | 22.95 | 7.83 |
May | 23.95 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.32 | 19.79 |
September | 24.04 | 15.09 |
October | 23.32 | 8.66 |
November | 22.21 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.08 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.27 | -0.5 |
April | 22.96 | 7.83 |
May | 23.95 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.32 | 19.79 |
September | 24.04 | 15.09 |
October | 23.32 | 8.66 |
November | 22.22 | 2.78 |
December | 21.74 | -1.5 |
Annual Sum or Average | 23.08 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | -7.2 |
February | 21.45 | -5.6 |
March | 22.28 | -0.5 |
April | 23.71 | 7.83 |
May | 25.18 | 13.82 |
June | 26.24 | 19.28 |
July | 26.38 | 21.06 |
August | 26.25 | 19.79 |
September | 25.33 | 15.09 |
October | 23.59 | 8.66 |
November | 22.26 | 2.78 |
December | 21.47 | -1.5 |
Annual Sum or Average | 23.79 | 7.87 |
Minimum of Months | 21.23 | -7.2 |
Maximum of Months | 26.38 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.16 | -0.5 |
April | 22.77 | 7.83 |
May | 23.89 | 13.82 |
June | 24.27 | 19.28 |
July | 24.30 | 21.06 |
August | 24.32 | 19.79 |
September | 23.87 | 15.09 |
October | 22.88 | 8.66 |
November | 22.03 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.98 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.37 | 7.83 |
May | 23.58 | 13.82 |
June | 24.29 | 19.28 |
July | 24.30 | 21.06 |
August | 24.25 | 19.79 |
September | 23.57 | 15.09 |
October | 22.09 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.76 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.15 | -0.5 |
April | 22.78 | 7.83 |
May | 23.88 | 13.82 |
June | 24.29 | 19.28 |
July | 24.32 | 21.06 |
August | 24.33 | 19.79 |
September | 23.86 | 15.09 |
October | 22.83 | 8.66 |
November | 22.03 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.97 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.32 | 7.83 |
May | 23.49 | 13.82 |
June | 24.29 | 19.28 |
July | 24.33 | 21.06 |
August | 24.24 | 19.79 |
September | 23.52 | 15.09 |
October | 21.97 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.73 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.33 | 7.83 |
May | 23.47 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.20 | 19.79 |
September | 23.62 | 15.09 |
October | 22.13 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.32 | 7.83 |
May | 23.46 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.20 | 19.79 |
September | 23.61 | 15.09 |
October | 22.12 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.74 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.27 | -0.5 |
April | 22.93 | 7.83 |
May | 23.94 | 13.82 |
June | 24.24 | 19.28 |
July | 24.28 | 21.06 |
August | 24.31 | 19.79 |
September | 24.02 | 15.09 |
October | 23.30 | 8.66 |
November | 22.21 | 2.78 |
December | 21.73 | -1.5 |
Annual Sum or Average | 23.07 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.79 | -5.6 |
March | 22.27 | -0.5 |
April | 22.94 | 7.83 |
May | 23.94 | 13.82 |
June | 24.24 | 19.28 |
July | 24.28 | 21.06 |
August | 24.32 | 19.79 |
September | 24.02 | 15.09 |
October | 23.30 | 8.66 |
November | 22.21 | 2.78 |
December | 21.73 | -1.5 |
Annual Sum or Average | 23.07 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -7.2 |
February | 21.99 | -5.6 |
March | 22.83 | -0.5 |
April | 24.25 | 7.83 |
May | 25.72 | 13.82 |
June | 26.77 | 19.28 |
July | 26.91 | 21.06 |
August | 26.78 | 19.79 |
September | 25.86 | 15.09 |
October | 24.14 | 8.66 |
November | 22.83 | 2.78 |
December | 22.04 | -1.5 |
Annual Sum or Average | 24.34 | 7.87 |
Minimum of Months | 21.78 | -7.2 |
Maximum of Months | 26.91 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.12 | -0.5 |
April | 22.68 | 7.83 |
May | 23.78 | 13.82 |
June | 24.25 | 19.28 |
July | 24.29 | 21.06 |
August | 24.31 | 19.79 |
September | 23.80 | 15.09 |
October | 22.76 | 8.66 |
November | 22.00 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.93 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.78 | -0.5 |
April | 22.31 | 7.83 |
May | 23.46 | 13.82 |
June | 24.27 | 19.28 |
July | 24.29 | 21.06 |
August | 24.22 | 19.79 |
September | 23.50 | 15.09 |
October | 22.03 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.73 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 22.11 | -0.5 |
April | 22.69 | 7.83 |
May | 23.77 | 13.82 |
June | 24.26 | 19.28 |
July | 24.30 | 21.06 |
August | 24.32 | 19.79 |
September | 23.79 | 15.09 |
October | 22.71 | 8.66 |
November | 21.99 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.93 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.26 | 7.83 |
May | 23.36 | 13.82 |
June | 24.27 | 19.28 |
July | 24.32 | 21.06 |
August | 24.21 | 19.79 |
September | 23.44 | 15.09 |
October | 21.91 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.70 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.26 | 7.83 |
May | 23.35 | 13.82 |
June | 24.22 | 19.28 |
July | 24.27 | 21.06 |
August | 24.16 | 19.79 |
September | 23.54 | 15.09 |
October | 22.06 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.71 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.27 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.26 | 7.83 |
May | 23.34 | 13.82 |
June | 24.22 | 19.28 |
July | 24.27 | 21.06 |
August | 24.16 | 19.79 |
September | 23.54 | 15.09 |
October | 22.05 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.71 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.27 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.78 | -5.6 |
March | 22.23 | -0.5 |
April | 22.83 | 7.83 |
May | 23.84 | 13.82 |
June | 24.21 | 19.28 |
July | 24.26 | 21.06 |
August | 24.29 | 19.79 |
September | 23.95 | 15.09 |
October | 23.17 | 8.66 |
November | 22.16 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 23.02 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.78 | -5.6 |
March | 22.23 | -0.5 |
April | 22.84 | 7.83 |
May | 23.84 | 13.82 |
June | 24.21 | 19.28 |
July | 24.26 | 21.06 |
August | 24.29 | 19.79 |
September | 23.95 | 15.09 |
October | 23.17 | 8.66 |
November | 22.16 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 23.02 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | -7.2 |
February | 21.37 | -5.6 |
March | 22.20 | -0.5 |
April | 23.60 | 7.83 |
May | 25.06 | 13.82 |
June | 26.19 | 19.28 |
July | 26.34 | 21.06 |
August | 26.20 | 19.79 |
September | 25.23 | 15.09 |
October | 23.47 | 8.66 |
November | 22.19 | 2.78 |
December | 21.40 | -1.5 |
Annual Sum or Average | 23.71 | 7.87 |
Minimum of Months | 21.16 | -7.2 |
Maximum of Months | 26.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.09 | -0.5 |
April | 22.61 | 7.83 |
May | 23.69 | 13.82 |
June | 24.23 | 19.28 |
July | 24.27 | 21.06 |
August | 24.29 | 19.79 |
September | 23.75 | 15.09 |
October | 22.66 | 8.66 |
November | 21.97 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.90 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.77 | -0.5 |
April | 22.27 | 7.83 |
May | 23.37 | 13.82 |
June | 24.25 | 19.28 |
July | 24.27 | 21.06 |
August | 24.20 | 19.79 |
September | 23.44 | 15.09 |
October | 21.98 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.70 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.27 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 22.08 | -0.5 |
April | 22.62 | 7.83 |
May | 23.68 | 13.82 |
June | 24.24 | 19.28 |
July | 24.29 | 21.06 |
August | 24.30 | 19.79 |
September | 23.74 | 15.09 |
October | 22.61 | 8.66 |
November | 21.97 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.89 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.23 | 7.83 |
May | 23.26 | 13.82 |
June | 24.24 | 19.28 |
July | 24.30 | 21.06 |
August | 24.19 | 19.79 |
September | 23.38 | 15.09 |
October | 21.88 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.67 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.22 | 7.83 |
May | 23.25 | 13.82 |
June | 24.20 | 19.28 |
July | 24.25 | 21.06 |
August | 24.13 | 19.79 |
September | 23.48 | 15.09 |
October | 22.01 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.68 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.74 | -0.5 |
April | 22.21 | 7.83 |
May | 23.24 | 13.82 |
June | 24.20 | 19.28 |
July | 24.25 | 21.06 |
August | 24.13 | 19.79 |
September | 23.48 | 15.09 |
October | 22.00 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.68 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.77 | -5.6 |
March | 22.20 | -0.5 |
April | 22.75 | 7.83 |
May | 23.75 | 13.82 |
June | 24.19 | 19.28 |
July | 24.25 | 21.06 |
August | 24.28 | 19.79 |
September | 23.89 | 15.09 |
October | 23.06 | 8.66 |
November | 22.13 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.98 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.77 | -5.6 |
March | 22.19 | -0.5 |
April | 22.76 | 7.83 |
May | 23.75 | 13.82 |
June | 24.19 | 19.28 |
July | 24.25 | 21.06 |
August | 24.28 | 19.79 |
September | 23.90 | 15.09 |
October | 23.05 | 8.66 |
November | 22.13 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.98 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.02 | -7.2 |
February | 21.22 | -5.6 |
March | 22.05 | -0.5 |
April | 23.43 | 7.83 |
May | 24.88 | 13.82 |
June | 26.08 | 19.28 |
July | 26.25 | 21.06 |
August | 26.10 | 19.79 |
September | 25.08 | 15.09 |
October | 23.29 | 8.66 |
November | 22.04 | 2.78 |
December | 21.26 | -1.5 |
Annual Sum or Average | 23.57 | 7.87 |
Minimum of Months | 21.02 | -7.2 |
Maximum of Months | 26.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.07 | -0.5 |
April | 22.56 | 7.83 |
May | 23.62 | 13.82 |
June | 24.21 | 19.28 |
July | 24.26 | 21.06 |
August | 24.28 | 19.79 |
September | 23.70 | 15.09 |
October | 22.58 | 8.66 |
November | 21.95 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.87 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.77 | -0.5 |
April | 22.24 | 7.83 |
May | 23.29 | 13.82 |
June | 24.23 | 19.28 |
July | 24.26 | 21.06 |
August | 24.18 | 19.79 |
September | 23.39 | 15.09 |
October | 21.95 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.68 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.26 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 22.05 | -0.5 |
April | 22.57 | 7.83 |
May | 23.60 | 13.82 |
June | 24.22 | 19.28 |
July | 24.28 | 21.06 |
August | 24.29 | 19.79 |
September | 23.69 | 15.09 |
October | 22.52 | 8.66 |
November | 21.94 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.86 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.20 | 7.83 |
May | 23.17 | 13.82 |
June | 24.23 | 19.28 |
July | 24.29 | 21.06 |
August | 24.16 | 19.79 |
September | 23.33 | 15.09 |
October | 21.85 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.65 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.29 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.18 | 7.83 |
May | 23.17 | 13.82 |
June | 24.18 | 19.28 |
July | 24.24 | 21.06 |
August | 24.11 | 19.79 |
September | 23.43 | 15.09 |
October | 21.98 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.66 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.24 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.18 | 7.83 |
May | 23.16 | 13.82 |
June | 24.18 | 19.28 |
July | 24.24 | 21.06 |
August | 24.11 | 19.79 |
September | 23.43 | 15.09 |
October | 21.97 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.66 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.24 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.17 | -0.5 |
April | 22.68 | 7.83 |
May | 23.67 | 13.82 |
June | 24.17 | 19.28 |
July | 24.24 | 21.06 |
August | 24.26 | 19.79 |
September | 23.84 | 15.09 |
October | 22.95 | 8.66 |
November | 22.10 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.95 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.26 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.76 | -5.6 |
March | 22.17 | -0.5 |
April | 22.69 | 7.83 |
May | 23.67 | 13.82 |
June | 24.17 | 19.28 |
July | 24.24 | 21.06 |
August | 24.26 | 19.79 |
September | 23.85 | 15.09 |
October | 22.95 | 8.66 |
November | 22.10 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.95 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.26 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | -7.2 |
February | 21.13 | -5.6 |
March | 21.96 | -0.5 |
April | 23.33 | 7.83 |
May | 24.77 | 13.82 |
June | 26.05 | 19.28 |
July | 26.23 | 21.06 |
August | 26.07 | 19.79 |
September | 24.99 | 15.09 |
October | 23.17 | 8.66 |
November | 21.95 | 2.78 |
December | 21.18 | -1.5 |
Annual Sum or Average | 23.49 | 7.87 |
Minimum of Months | 20.93 | -7.2 |
Maximum of Months | 26.23 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.04 | -0.5 |
April | 22.51 | 7.83 |
May | 23.53 | 13.82 |
June | 24.19 | 19.28 |
July | 24.25 | 21.06 |
August | 24.26 | 19.79 |
September | 23.64 | 15.09 |
October | 22.48 | 8.66 |
November | 21.92 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.84 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.26 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.22 | 7.83 |
May | 23.22 | 13.82 |
June | 24.21 | 19.28 |
July | 24.25 | 21.06 |
August | 24.15 | 19.79 |
September | 23.34 | 15.09 |
October | 21.92 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.66 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 22.02 | -0.5 |
April | 22.52 | 7.83 |
May | 23.51 | 13.82 |
June | 24.20 | 19.28 |
July | 24.26 | 21.06 |
August | 24.27 | 19.79 |
September | 23.63 | 15.09 |
October | 22.42 | 8.66 |
November | 21.91 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.83 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.27 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.18 | 7.83 |
May | 23.10 | 13.82 |
June | 24.20 | 19.28 |
July | 24.28 | 21.06 |
August | 24.14 | 19.79 |
September | 23.27 | 15.09 |
October | 21.83 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.63 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.16 | 7.83 |
May | 23.11 | 13.82 |
June | 24.17 | 19.28 |
July | 24.22 | 21.06 |
August | 24.09 | 19.79 |
September | 23.37 | 15.09 |
October | 21.95 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.64 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.22 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.73 | -0.5 |
April | 22.16 | 7.83 |
May | 23.10 | 13.82 |
June | 24.17 | 19.28 |
July | 24.23 | 21.06 |
August | 24.09 | 19.79 |
September | 23.36 | 15.09 |
October | 21.94 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.64 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.23 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.13 | -0.5 |
April | 22.61 | 7.83 |
May | 23.59 | 13.82 |
June | 24.16 | 19.28 |
July | 24.22 | 21.06 |
August | 24.25 | 19.79 |
September | 23.78 | 15.09 |
October | 22.81 | 8.66 |
November | 22.05 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.90 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.13 | -0.5 |
April | 22.61 | 7.83 |
May | 23.59 | 13.82 |
June | 24.16 | 19.28 |
July | 24.22 | 21.06 |
August | 24.25 | 19.79 |
September | 23.78 | 15.09 |
October | 22.81 | 8.66 |
November | 22.05 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.90 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.25 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | -7.2 |
February | 20.93 | -5.6 |
March | 21.79 | -0.5 |
April | 23.22 | 7.83 |
May | 24.69 | 13.82 |
June | 26.06 | 19.28 |
July | 26.26 | 21.06 |
August | 26.08 | 19.79 |
September | 24.91 | 15.09 |
October | 23.02 | 8.66 |
November | 21.78 | 2.78 |
December | 21.00 | -1.5 |
Annual Sum or Average | 23.39 | 7.87 |
Minimum of Months | 20.72 | -7.2 |
Maximum of Months | 26.26 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.02 | -0.5 |
April | 22.46 | 7.83 |
May | 23.29 | 13.82 |
June | 24.06 | 19.28 |
July | 24.15 | 21.06 |
August | 24.14 | 19.79 |
September | 23.48 | 15.09 |
October | 22.38 | 8.66 |
November | 21.91 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.76 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.15 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.22 | 7.83 |
May | 23.06 | 13.82 |
June | 24.07 | 19.28 |
July | 24.15 | 21.06 |
August | 24.04 | 19.79 |
September | 23.20 | 15.09 |
October | 21.95 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.61 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.15 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.01 | -0.5 |
April | 22.46 | 7.83 |
May | 23.27 | 13.82 |
June | 24.07 | 19.28 |
July | 24.17 | 21.06 |
August | 24.16 | 19.79 |
September | 23.46 | 15.09 |
October | 22.34 | 8.66 |
November | 21.90 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.75 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.17 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.18 | 7.83 |
May | 22.97 | 13.82 |
June | 24.05 | 19.28 |
July | 24.16 | 21.06 |
August | 24.02 | 19.79 |
September | 23.12 | 15.09 |
October | 21.85 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.58 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.16 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.15 | 7.83 |
May | 22.97 | 13.82 |
June | 24.05 | 19.28 |
July | 24.13 | 21.06 |
August | 23.98 | 19.79 |
September | 23.21 | 15.09 |
October | 21.93 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.59 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.13 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.15 | 7.83 |
May | 22.97 | 13.82 |
June | 24.05 | 19.28 |
July | 24.13 | 21.06 |
August | 23.98 | 19.79 |
September | 23.20 | 15.09 |
October | 21.92 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.58 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.13 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.77 | -5.6 |
March | 22.08 | -0.5 |
April | 22.53 | 7.83 |
May | 23.40 | 13.82 |
June | 24.06 | 19.28 |
July | 24.14 | 21.06 |
August | 24.16 | 19.79 |
September | 23.61 | 15.09 |
October | 22.59 | 8.66 |
November | 22.00 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.82 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.16 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -7.2 |
February | 21.77 | -5.6 |
March | 22.08 | -0.5 |
April | 22.53 | 7.83 |
May | 23.40 | 13.82 |
June | 24.06 | 19.28 |
July | 24.15 | 21.06 |
August | 24.16 | 19.79 |
September | 23.62 | 15.09 |
October | 22.59 | 8.66 |
November | 22.00 | 2.78 |
December | 21.72 | -1.5 |
Annual Sum or Average | 22.82 | 7.87 |
Minimum of Months | 21.71 | -7.2 |
Maximum of Months | 24.16 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.36 | -7.2 |
February | 20.68 | -5.6 |
March | 21.73 | -0.5 |
April | 23.46 | 7.83 |
May | 25.10 | 13.82 |
June | 26.71 | 19.28 |
July | 26.96 | 21.06 |
August | 26.71 | 19.79 |
September | 25.27 | 15.09 |
October | 23.16 | 8.66 |
November | 21.72 | 2.78 |
December | 20.81 | -1.5 |
Annual Sum or Average | 23.57 | 7.87 |
Minimum of Months | 20.36 | -7.2 |
Maximum of Months | 26.96 | 21.06 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.299647E+12 | 175367.334 | 23-JAN-21:00 | 11839.540 | 45992.891 | 19201.552 | 84361.088 | 0.000 | 10364.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.262556E+12 | 189762.541 | 07-FEB-17:00 | 11327.174 | 57142.088 | 19201.552 | 87652.691 | 0.000 | 10364.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.255630E+12 | 164244.593 | 07-MAR-13:00 | 9104.941 | 34496.599 | 19201.552 | 98262.384 | 0.000 | 0.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.211668E+12 | 147413.915 | 21-APR-17:15 | 13120.457 | 57042.023 | 19201.552 | 0.000 | 52023.763 | 0.000 | 2079.877 | 1958.432 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.202342E+12 | 150261.171 | 31-MAY-17:30 | 13120.457 | 57042.023 | 19201.552 | 0.000 | 54780.580 | 0.000 | 2079.877 | 2048.673 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.236961E+12 | 171885.493 | 16-JUN-19:45 | 14401.373 | 49889.926 | 19201.552 | 0.000 | 71497.415 | 10364.000 | 2079.877 | 2810.046 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.269929E+12 | 174798.235 | 20-JUL-19:30 | 14401.373 | 49889.926 | 19201.552 | 0.000 | 74131.956 | 10364.000 | 2079.877 | 3088.247 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.261242E+12 | 171984.683 | 04-AUG-17:15 | 13120.457 | 57042.023 | 19201.552 | 0.000 | 75519.016 | 0.000 | 2079.877 | 3033.946 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.218181E+12 | 153170.629 | 04-SEP-16:15 | 11327.174 | 57042.023 | 19201.552 | 0.000 | 59239.753 | 0.000 | 2079.877 | 2292.608 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.210785E+12 | 120473.186 | 06-OCT-17:30 | 13120.457 | 57042.023 | 19201.552 | 16677.268 | 0.000 | 10364.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.238332E+12 | 141526.437 | 29-NOV-17:15 | 11327.174 | 57142.088 | 19201.552 | 39416.550 | 0.000 | 10364.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.277974E+12 | 171502.437 | 17-DEC-17:00 | 11327.174 | 57042.023 | 19201.552 | 69499.999 | 0.000 | 10364.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.294525E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.202342E+12 | 120473.186 | 9104.941 | 34496.599 | 19201.552 | 0.000 | 0.000 | 0.000 | 2079.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.299647E+12 | 189762.541 | 14401.373 | 57142.088 | 19201.552 | 98262.384 | 75519.016 | 10364.000 | 2079.877 | 3088.247 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.526105E+12 | 372607.720 | 24-JAN-07:30 | 0.000 | 0.000 | 0.000 | 372607.720 | 84624.482 | 84624.482 | 287983.237 |
February | 0.443849E+12 | 360430.053 | 22-FEB-08:45 | 0.000 | 0.000 | 0.000 | 360430.053 | 83565.156 | 83565.156 | 276864.896 |
March | 0.343465E+12 | 366275.098 | 07-MAR-07:30 | 0.000 | 0.000 | 0.000 | 366275.098 | 82672.134 | 82672.134 | 283602.964 |
April | 0.174643E+12 | 269396.118 | 09-APR-05:15 | 0.000 | 0.000 | 0.000 | 269396.118 | 68807.741 | 68807.741 | 200588.377 |
May | 0.108502E+12 | 105159.686 | 08-MAY-07:15 | 0.000 | 0.000 | 0.000 | 105159.686 | 80670.615 | 80670.615 | 24489.070 |
June | 0.968108E+11 | 79442.548 | 01-JUN-06:00 | 0.000 | 0.000 | 0.000 | 79442.548 | 79442.548 | 79442.548 | 0.000 |
July | 0.951746E+11 | 77329.825 | 01-JUL-06:45 | 0.000 | 0.000 | 0.000 | 77329.825 | 77329.825 | 77329.825 | 0.000 |
August | 0.930332E+11 | 76071.875 | 03-AUG-06:00 | 0.000 | 0.000 | 0.000 | 76071.875 | 76071.875 | 76071.875 | 0.000 |
September | 0.951095E+11 | 121028.134 | 30-SEP-07:30 | 0.000 | 0.000 | 0.000 | 121028.134 | 75775.498 | 75775.498 | 45252.636 |
October | 0.134225E+12 | 165756.512 | 31-OCT-06:45 | 0.000 | 0.000 | 0.000 | 165756.512 | 78865.142 | 78865.142 | 86891.370 |
November | 0.269234E+12 | 263622.334 | 29-NOV-08:15 | 0.000 | 0.000 | 0.000 | 263622.334 | 80415.379 | 80415.379 | 183206.955 |
December | 0.419772E+12 | 368998.485 | 17-DEC-07:30 | 0.000 | 0.000 | 0.000 | 368998.485 | 82448.686 | 82448.686 | 286549.799 |
Annual Sum or Average | 0.279992E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.930332E+11 | 76071.875 | 0.000 | 0.000 | 0.000 | 76071.875 | 68807.741 | 68807.741 | 0.000 | |
Maximum of Months | 0.526105E+12 | 372607.720 | 0.000 | 0.000 | 0.000 | 372607.720 | 84624.482 | 84624.482 | 287983.237 |