Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: RIYADH - SAU IWEC Data WMO#=404380
Simulation Timestamp: 2015-09-09 19:11:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4825.16 | 615.73 | 683.46 |
Net Site Energy | 4825.16 | 615.73 | 683.46 |
Total Source Energy | 13682.16 | 1745.96 | 1938.01 |
Net Source Energy | 13682.16 | 1745.96 | 1938.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 5.04 | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1286.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1005.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 80.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.78 | 0.00 | 0.00 | 0.00 | 0.00 | 5118.01 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 764.50 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4057.46 | 767.70 | 0.00 | 0.00 | 0.00 | 9896.52 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 5.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1286.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 163.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1005.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 80.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 46.78 | 0.00 | 0.00 | 0.00 | 0.00 | 5118.01 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 764.50 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 343.40 | 108.74 | 0.00 | 0.00 | 0.00 | 1.40 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 574.72 | 108.74 | 0.00 | 0.00 | 0.00 | 1.40 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 309.37 | 97.97 | 0.00 | 0.00 | 0.00 | 1.26 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 517.77 | 97.97 | 0.00 | 0.00 | 0.00 | 1.26 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 4057.46 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 4057.46 | 100.00 |
Total On-Site and Utility Electric Sources | 4057.46 | 100.00 |
Total Electricity End Uses | 4057.46 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9896.52 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9896.52 | 100.00 |
Total Water End Uses | 9896.52 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1093.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 389.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11 |
RunPeriod | RIYADH - SAU IWEC Data WMO#=404380 |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
Latitude [deg] | 24.70 |
Longitude [deg] | 46.80 |
Elevation [m] | 612.00 |
Time Zone | 3.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUL-18:45 | 09-JAN-06:30 | - | - | - | 25-JUL-17:15 |
Heating | 0.00 | 48692.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 91462.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31891.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2606.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2994.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 54400.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 207230.49 | 103093.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 48692.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 91462.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 11484.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2917.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31891.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2606.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2994.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 54400.98 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 15.95 | 3.47 | 0.00 | 0.00 | 0.00 |
Cooling | 4073.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 516.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3185.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 254.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 148.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 828.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 12849.97 | 832.19 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 2.26 | 0.49 | 0.00 | 0.00 | 0.00 |
Cooling | 577.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 451.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.38 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1820.14 | 117.88 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 2.26 | 0.49 | 0.00 | 0.00 | 0.00 |
Cooling | 577.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 451.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 117.38 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1820.14 | 117.88 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00 | 5.90 | Wetbulb [C] | 1.60 | 320.00 |
RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 13.50 | 18.70 | Wetbulb [C] | 4.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_1.22_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 5.778 | 0.306 | 0.155 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_1.22_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 5.778 | 0.306 | 0.155 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_1.22_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 5.778 | 0.306 | 0.155 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 423.59 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 726.80 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.78 | 83.78 | 163.00 | |
Exterior Lighting Total | 10364.00 | 163.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 369884.27 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 295907.41 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4960.28 | 3649.21 | 1311.07 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5011.98 | 3691.25 | 1320.73 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6204.90 | 4544.14 | 1660.76 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4077.61 | 3004.47 | 1073.14 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2900.22 | 2125.27 | 774.95 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2885.24 | 2114.29 | 770.95 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2857.63 | 2081.42 | 776.21 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2929.33 | 2132.08 | 797.26 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5783.47 | 4281.42 | 1502.06 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5843.66 | 4329.77 | 1513.90 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5230.93 | 3874.19 | 1356.74 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4906.36 | 3641.30 | 1265.06 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3434.15 | 2538.73 | 895.42 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3422.22 | 2530.02 | 892.20 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3385.29 | 2487.01 | 898.28 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3397.10 | 2495.63 | 901.47 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5795.32 | 4310.02 | 1485.30 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5856.62 | 4359.33 | 1497.29 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5000.20 | 3725.63 | 1274.57 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4949.94 | 3692.58 | 1257.37 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3473.65 | 2575.25 | 898.39 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3462.67 | 2567.22 | 895.45 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3415.42 | 2520.51 | 894.91 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3413.14 | 2518.82 | 894.32 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5835.46 | 4354.21 | 1481.25 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5894.74 | 4402.16 | 1492.58 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5031.69 | 3763.22 | 1268.46 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5007.98 | 3749.53 | 1258.45 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3512.23 | 2612.14 | 900.09 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3501.40 | 2604.20 | 897.19 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3456.41 | 2559.14 | 897.27 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3452.27 | 2556.07 | 896.19 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5901.32 | 4414.42 | 1486.90 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5959.85 | 4461.90 | 1497.95 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5106.98 | 3830.13 | 1276.85 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5088.47 | 3820.22 | 1268.26 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3575.97 | 2665.85 | 910.12 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3565.26 | 2658.00 | 907.25 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3521.08 | 2613.55 | 907.52 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3516.72 | 2610.34 | 906.39 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5886.14 | 4413.82 | 1472.32 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5941.86 | 4459.34 | 1482.52 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5102.82 | 3837.30 | 1265.53 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5085.01 | 3827.89 | 1257.12 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3558.82 | 2659.37 | 899.45 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3548.25 | 2651.62 | 896.62 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3506.91 | 2609.19 | 897.73 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3502.58 | 2605.99 | 896.60 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5897.33 | 4431.18 | 1466.16 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5951.82 | 4475.86 | 1475.95 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5123.21 | 3861.16 | 1262.05 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5107.05 | 3852.95 | 1254.09 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3568.47 | 2671.77 | 896.70 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3558.00 | 2664.10 | 893.91 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3518.01 | 2622.62 | 895.39 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3513.71 | 2619.44 | 894.28 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5927.09 | 4461.13 | 1465.96 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5980.22 | 4504.88 | 1475.33 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5160.89 | 3896.76 | 1264.13 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5145.73 | 3889.27 | 1256.46 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3596.50 | 2697.09 | 899.41 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3586.14 | 2689.49 | 896.65 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3547.20 | 2648.79 | 898.42 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3542.95 | 2645.63 | 897.31 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6109.35 | 4601.57 | 1507.78 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6165.32 | 4647.42 | 1517.90 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5338.69 | 4034.11 | 1304.59 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5329.68 | 4031.08 | 1298.60 | 0.76 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3763.14 | 2823.51 | 939.63 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3752.96 | 2816.05 | 936.92 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3703.47 | 2767.80 | 935.67 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3699.71 | 2765.02 | 934.70 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 7345.22 | 5506.94 | 1838.28 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 7387.88 | 5539.54 | 1848.34 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6464.48 | 4862.38 | 1602.10 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6416.11 | 4827.12 | 1588.99 | 0.75 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4844.30 | 3605.92 | 1238.38 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4836.14 | 3598.17 | 1237.97 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4879.56 | 3629.84 | 1249.71 | 0.74 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4876.40 | 3627.51 | 1248.89 | 0.74 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4960.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5011.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 6204.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4077.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2900.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2885.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2857.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2929.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5783.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5843.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5230.93 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4906.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3434.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3422.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3385.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3397.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5795.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5856.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5000.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4949.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3473.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3462.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3415.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3413.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5835.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5894.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5031.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5007.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3512.23 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3501.40 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3456.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3452.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5901.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5959.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5106.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5088.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3575.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3565.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3521.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3516.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5886.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5941.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5102.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5085.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3558.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3548.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3506.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3502.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5897.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5951.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5123.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5107.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3568.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3558.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3518.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3513.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5927.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5980.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5160.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5145.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3596.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3586.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3547.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3542.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6109.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6165.32 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5338.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5329.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3763.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3752.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3703.47 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3699.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 7345.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 7387.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 6464.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 6416.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4844.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4836.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4879.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4876.40 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 1821.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 1814.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2344.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 1819.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1255.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1255.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1258.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1264.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 1905.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 1894.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 1929.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 1900.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1211.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1211.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1223.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1224.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1891.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1882.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1899.55 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1888.29 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1184.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1184.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1193.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1193.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1905.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1896.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1911.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1902.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1186.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1186.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1194.23 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1194.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1899.76 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1890.92 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1904.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1896.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1172.40 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1172.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1180.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1180.61 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 1954.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 1947.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 1959.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 1951.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1217.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1217.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1224.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1224.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 1986.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 1978.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 1990.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 1983.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1241.11 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1241.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1247.42 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1247.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 2019.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 2012.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 2023.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 2016.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1267.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1267.58 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1273.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1273.81 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 2136.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 2126.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 2140.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 2130.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1368.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1368.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1377.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1377.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2456.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2453.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2459.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2456.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 1748.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 1748.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 1748.72 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 1748.82 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 421.91 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 427.66 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 519.40 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 344.17 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 238.94 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 237.63 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 231.92 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 237.71 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 499.67 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 506.20 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 449.79 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 422.34 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.15 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 289.10 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 281.35 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 282.38 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 504.12 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 510.78 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 432.89 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 429.49 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.36 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 293.39 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 285.93 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 285.73 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 510.20 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 516.70 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 438.14 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 437.08 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 299.21 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.26 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.98 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 290.62 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 518.06 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 524.52 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 446.79 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 446.18 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 306.01 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.07 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.86 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.47 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 518.51 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 524.74 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 448.16 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 447.61 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.53 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 304.60 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.63 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.24 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 521.06 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 527.19 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 451.48 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 451.07 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 307.28 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 306.36 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 299.50 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 299.11 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 525.09 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.46 | 531.10 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 456.17 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 455.85 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 310.56 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 309.64 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 302.87 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 302.49 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 542.40 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 548.67 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 473.09 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 473.31 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 325.97 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 325.08 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 317.38 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 317.05 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.56 | 651.64 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.56 | 655.87 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 573.31 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 569.06 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 418.38 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 417.16 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 420.97 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 420.69 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0080 | 2569.22 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 3595.96 | 4315.16 | 0.303 | 0.363 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
G NW APARTMENT | 3644.94 | 4373.92 | 0.307 | 0.368 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
OFFICE | 4426.90 | 5312.28 | 0.373 | 0.447 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 44.20 | 0.00412 |
G NE APARTMENT | 2933.36 | 3520.03 | 0.247 | 0.296 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
G N1 APARTMENT | 2036.46 | 2443.76 | 0.172 | 0.206 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
G N2 APARTMENT | 2025.28 | 2430.34 | 0.171 | 0.205 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
G S1 APARTMENT | 1976.64 | 2371.97 | 0.166 | 0.200 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
G S2 APARTMENT | 2025.97 | 2431.16 | 0.171 | 0.205 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 44.20 | 0.00412 |
F2 SW APARTMENT | 4258.76 | 5110.51 | 0.359 | 0.430 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F2 NW APARTMENT | 4314.47 | 5177.37 | 0.363 | 0.436 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F2 SE APARTMENT | 3833.61 | 4600.34 | 0.323 | 0.387 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
F2 NE APARTMENT | 3599.74 | 4319.68 | 0.303 | 0.364 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F2 N1 APARTMENT | 2472.87 | 2967.44 | 0.208 | 0.250 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 41.97 | 0.00412 |
F2 N2 APARTMENT | 2463.96 | 2956.75 | 0.208 | 0.249 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 41.97 | 0.00412 |
F2 S1 APARTMENT | 2397.94 | 2877.52 | 0.202 | 0.242 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F2 S2 APARTMENT | 2406.73 | 2888.07 | 0.203 | 0.243 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F3 SW APARTMENT | 4296.79 | 5156.15 | 0.362 | 0.434 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F3 NW APARTMENT | 4353.57 | 5224.28 | 0.367 | 0.440 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F3 SE APARTMENT | 3689.69 | 4427.63 | 0.311 | 0.373 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
F3 NE APARTMENT | 3660.71 | 4392.85 | 0.308 | 0.370 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F3 N1 APARTMENT | 2508.80 | 3010.55 | 0.211 | 0.254 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F3 N2 APARTMENT | 2500.57 | 3000.68 | 0.211 | 0.253 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F3 S1 APARTMENT | 2436.99 | 2924.39 | 0.205 | 0.246 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F3 S2 APARTMENT | 2435.25 | 2922.30 | 0.205 | 0.246 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F4 SW APARTMENT | 4348.64 | 5218.37 | 0.366 | 0.440 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F4 NW APARTMENT | 4404.07 | 5284.89 | 0.371 | 0.445 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F4 SE APARTMENT | 3734.51 | 4481.41 | 0.315 | 0.377 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
F4 NE APARTMENT | 3725.40 | 4470.48 | 0.314 | 0.377 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F4 N1 APARTMENT | 2550.19 | 3060.23 | 0.215 | 0.258 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F4 N2 APARTMENT | 2542.07 | 3050.48 | 0.214 | 0.257 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F4 S1 APARTMENT | 2480.07 | 2976.09 | 0.209 | 0.251 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F4 S2 APARTMENT | 2476.93 | 2972.32 | 0.209 | 0.250 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
M SW APARTMENT | 4415.74 | 5298.89 | 0.372 | 0.446 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
M NW APARTMENT | 4470.75 | 5364.90 | 0.377 | 0.452 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
M SE APARTMENT | 3808.28 | 4569.93 | 0.321 | 0.385 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
M NE APARTMENT | 3803.05 | 4563.66 | 0.320 | 0.384 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
M N1 APARTMENT | 2608.16 | 3129.79 | 0.220 | 0.264 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
M N2 APARTMENT | 2600.12 | 3120.14 | 0.219 | 0.263 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
M S1 APARTMENT | 2538.67 | 3046.40 | 0.214 | 0.257 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
M S2 APARTMENT | 2535.37 | 3042.44 | 0.214 | 0.256 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F6 SW APARTMENT | 4419.62 | 5303.54 | 0.372 | 0.447 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F6 NW APARTMENT | 4472.65 | 5367.18 | 0.377 | 0.452 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F6 SE APARTMENT | 3819.96 | 4583.96 | 0.322 | 0.386 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
F6 NE APARTMENT | 3815.25 | 4578.30 | 0.321 | 0.386 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F6 N1 APARTMENT | 2604.08 | 3124.89 | 0.219 | 0.263 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F6 N2 APARTMENT | 2596.13 | 3115.36 | 0.219 | 0.262 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F6 S1 APARTMENT | 2536.72 | 3044.07 | 0.214 | 0.256 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F6 S2 APARTMENT | 2533.44 | 3040.12 | 0.213 | 0.256 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F7 SW APARTMENT | 4441.39 | 5329.67 | 0.374 | 0.449 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F7 NW APARTMENT | 4493.59 | 5392.31 | 0.378 | 0.454 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F7 SE APARTMENT | 3848.28 | 4617.93 | 0.324 | 0.389 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
F7 NE APARTMENT | 3844.80 | 4613.76 | 0.324 | 0.389 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F7 N1 APARTMENT | 2619.01 | 3142.81 | 0.221 | 0.265 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F7 N2 APARTMENT | 2611.14 | 3133.37 | 0.220 | 0.264 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F7 S1 APARTMENT | 2552.67 | 3063.21 | 0.215 | 0.258 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F7 S2 APARTMENT | 2549.41 | 3059.29 | 0.215 | 0.258 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F8 SW APARTMENT | 4475.70 | 5370.84 | 0.377 | 0.452 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F8 NW APARTMENT | 4526.98 | 5432.37 | 0.381 | 0.458 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F8 SE APARTMENT | 3888.25 | 4665.90 | 0.327 | 0.393 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 44.20 | 0.00412 |
F8 NE APARTMENT | 3885.51 | 4662.62 | 0.327 | 0.393 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F8 N1 APARTMENT | 2646.95 | 3176.34 | 0.223 | 0.268 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F8 N2 APARTMENT | 2639.16 | 3166.99 | 0.222 | 0.267 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F8 S1 APARTMENT | 2581.44 | 3097.73 | 0.217 | 0.261 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F8 S2 APARTMENT | 2578.20 | 3093.84 | 0.217 | 0.261 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F9 SW APARTMENT | 4623.29 | 5547.95 | 0.389 | 0.467 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
F9 NW APARTMENT | 4676.77 | 5612.12 | 0.394 | 0.473 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
F9 SE APARTMENT | 4032.53 | 4839.04 | 0.340 | 0.408 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 44.20 | 0.00412 |
F9 NE APARTMENT | 4034.40 | 4841.28 | 0.340 | 0.408 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
F9 N1 APARTMENT | 2778.38 | 3334.06 | 0.234 | 0.281 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F9 N2 APARTMENT | 2770.73 | 3324.87 | 0.233 | 0.280 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
F9 S1 APARTMENT | 2705.15 | 3246.18 | 0.228 | 0.273 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
F9 S2 APARTMENT | 2702.29 | 3242.75 | 0.228 | 0.273 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
T SW APARTMENT | 5554.55 | 6665.46 | 0.468 | 0.561 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
T NW APARTMENT | 5590.59 | 6708.70 | 0.471 | 0.565 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
T SE APARTMENT | 4886.91 | 5864.29 | 0.412 | 0.494 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 44.20 | 0.00412 |
T NE APARTMENT | 4850.65 | 5820.79 | 0.409 | 0.490 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
T N1 APARTMENT | 3566.02 | 4279.23 | 0.300 | 0.360 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
T N2 APARTMENT | 3555.63 | 4266.75 | 0.299 | 0.359 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 44.20 | 0.00412 |
T S1 APARTMENT | 3588.12 | 4305.74 | 0.302 | 0.363 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 44.20 | 0.00412 |
T S2 APARTMENT | 3585.72 | 4302.86 | 0.302 | 0.362 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 44.20 | 0.00412 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1150.67 | 1380.81 | 0.055 | 0.066 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
G NW APARTMENT | 1144.41 | 1373.29 | 0.055 | 0.066 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
OFFICE | 1410.14 | 1692.17 | 0.068 | 0.081 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 5.90 | 0.00619 |
G NE APARTMENT | 1148.42 | 1378.11 | 0.055 | 0.066 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
G N1 APARTMENT | 671.22 | 805.47 | 0.032 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
G N2 APARTMENT | 671.32 | 805.59 | 0.032 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
G S1 APARTMENT | 674.48 | 809.38 | 0.032 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
G S2 APARTMENT | 679.55 | 815.46 | 0.033 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
F2 SW APARTMENT | 1220.96 | 1465.15 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 NW APARTMENT | 1212.35 | 1454.82 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 SE APARTMENT | 1241.38 | 1489.66 | 0.059 | 0.071 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 NE APARTMENT | 1217.34 | 1460.81 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 N1 APARTMENT | 634.24 | 761.08 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 N2 APARTMENT | 634.36 | 761.24 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 S1 APARTMENT | 644.30 | 773.16 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F2 S2 APARTMENT | 645.46 | 774.56 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 SW APARTMENT | 1209.71 | 1451.65 | 0.058 | 0.069 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 NW APARTMENT | 1201.91 | 1442.29 | 0.058 | 0.069 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 SE APARTMENT | 1216.30 | 1459.56 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 NE APARTMENT | 1206.78 | 1448.14 | 0.058 | 0.069 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 N1 APARTMENT | 611.65 | 733.98 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 N2 APARTMENT | 611.77 | 734.13 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 S1 APARTMENT | 619.14 | 742.97 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F3 S2 APARTMENT | 619.43 | 743.31 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 SW APARTMENT | 1221.17 | 1465.40 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 NW APARTMENT | 1214.04 | 1456.85 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 SE APARTMENT | 1225.99 | 1471.19 | 0.059 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 NE APARTMENT | 1218.68 | 1462.41 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 N1 APARTMENT | 613.28 | 735.93 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 N2 APARTMENT | 613.40 | 736.08 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 S1 APARTMENT | 619.84 | 743.81 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F4 S2 APARTMENT | 619.98 | 743.98 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M SW APARTMENT | 1216.47 | 1459.77 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M NW APARTMENT | 1209.01 | 1450.81 | 0.058 | 0.069 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M SE APARTMENT | 1220.86 | 1465.03 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M NE APARTMENT | 1213.36 | 1456.03 | 0.058 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M N1 APARTMENT | 601.38 | 721.66 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M N2 APARTMENT | 601.49 | 721.79 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M S1 APARTMENT | 608.21 | 729.85 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
M S2 APARTMENT | 608.32 | 729.99 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 SW APARTMENT | 1262.77 | 1515.32 | 0.060 | 0.073 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 NW APARTMENT | 1256.47 | 1507.77 | 0.060 | 0.072 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 SE APARTMENT | 1266.85 | 1520.22 | 0.061 | 0.073 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 NE APARTMENT | 1260.55 | 1512.66 | 0.060 | 0.072 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 N1 APARTMENT | 639.39 | 767.27 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 N2 APARTMENT | 639.49 | 767.39 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 S1 APARTMENT | 645.02 | 774.02 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F6 S2 APARTMENT | 645.12 | 774.15 | 0.031 | 0.037 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 SW APARTMENT | 1289.44 | 1547.33 | 0.062 | 0.074 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 NW APARTMENT | 1283.40 | 1540.08 | 0.061 | 0.074 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 SE APARTMENT | 1293.24 | 1551.89 | 0.062 | 0.074 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 NE APARTMENT | 1287.19 | 1544.63 | 0.062 | 0.074 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 N1 APARTMENT | 659.49 | 791.38 | 0.032 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 N2 APARTMENT | 659.58 | 791.50 | 0.032 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 S1 APARTMENT | 664.83 | 797.79 | 0.032 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F7 S2 APARTMENT | 664.92 | 797.91 | 0.032 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 SW APARTMENT | 1317.55 | 1581.06 | 0.063 | 0.076 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 NW APARTMENT | 1311.57 | 1573.88 | 0.063 | 0.075 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 SE APARTMENT | 1321.07 | 1585.28 | 0.063 | 0.076 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 NE APARTMENT | 1315.08 | 1578.09 | 0.063 | 0.076 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 N1 APARTMENT | 681.78 | 818.14 | 0.033 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 N2 APARTMENT | 681.87 | 818.25 | 0.033 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 S1 APARTMENT | 687.05 | 824.46 | 0.033 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F8 S2 APARTMENT | 687.14 | 824.57 | 0.033 | 0.039 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 SW APARTMENT | 1416.41 | 1699.69 | 0.068 | 0.081 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 NW APARTMENT | 1408.39 | 1690.06 | 0.067 | 0.081 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 SE APARTMENT | 1419.68 | 1703.61 | 0.068 | 0.082 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 NE APARTMENT | 1411.64 | 1693.97 | 0.068 | 0.081 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 N1 APARTMENT | 767.51 | 921.02 | 0.037 | 0.044 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 N2 APARTMENT | 767.60 | 921.12 | 0.037 | 0.044 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 S1 APARTMENT | 774.58 | 929.50 | 0.037 | 0.044 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
F9 S2 APARTMENT | 774.67 | 929.60 | 0.037 | 0.044 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T SW APARTMENT | 1687.32 | 2024.79 | 0.081 | 0.097 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T NW APARTMENT | 1684.73 | 2021.68 | 0.081 | 0.097 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T SE APARTMENT | 1690.06 | 2028.08 | 0.081 | 0.097 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T NE APARTMENT | 1687.47 | 2024.97 | 0.081 | 0.097 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T N1 APARTMENT | 1088.32 | 1305.99 | 0.052 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T N2 APARTMENT | 1088.40 | 1306.08 | 0.052 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T S1 APARTMENT | 1088.75 | 1306.50 | 0.052 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
T S2 APARTMENT | 1088.83 | 1306.60 | 0.052 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.36 | 0.36 | 0.07 | 0.07 |
AIRLOOP G NW | 0.37 | 0.37 | 0.07 | 0.07 |
AIRLOOP OFFICE | 0.45 | 0.45 | 0.08 | 0.08 |
AIRLOOP G NE | 0.30 | 0.30 | 0.07 | 0.07 |
AIRLOOP G N1 | 0.21 | 0.21 | 0.04 | 0.04 |
AIRLOOP G N2 | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP G S1 | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP G S2 | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP F2 SW | 0.43 | 0.43 | 0.07 | 0.07 |
AIRLOOP F2 NW | 0.44 | 0.44 | 0.07 | 0.07 |
AIRLOOP F2 SE | 0.39 | 0.39 | 0.07 | 0.07 |
AIRLOOP F2 NE | 0.36 | 0.36 | 0.07 | 0.07 |
AIRLOOP F2 N1 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F2 N2 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F2 S1 | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F2 S2 | 0.24 | 0.24 | 0.04 | 0.04 |
AIRLOOP F3 SW | 0.43 | 0.43 | 0.07 | 0.07 |
AIRLOOP F3 NW | 0.44 | 0.44 | 0.07 | 0.07 |
AIRLOOP F3 SE | 0.37 | 0.37 | 0.07 | 0.07 |
AIRLOOP F3 NE | 0.37 | 0.37 | 0.07 | 0.07 |
AIRLOOP F3 N1 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F3 N2 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F3 S1 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F3 S2 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F4 SW | 0.44 | 0.44 | 0.07 | 0.07 |
AIRLOOP F4 NW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP F4 SE | 0.38 | 0.38 | 0.07 | 0.07 |
AIRLOOP F4 NE | 0.38 | 0.38 | 0.07 | 0.07 |
AIRLOOP F4 N1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F4 N2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F4 S1 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP F4 S2 | 0.25 | 0.25 | 0.04 | 0.04 |
AIRLOOP M SW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP M NW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP M SE | 0.38 | 0.38 | 0.07 | 0.07 |
AIRLOOP M NE | 0.38 | 0.38 | 0.07 | 0.07 |
AIRLOOP M N1 | 0.26 | 0.26 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.26 | 0.26 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.26 | 0.26 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.26 | 0.26 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP F6 NW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP F6 SE | 0.39 | 0.39 | 0.07 | 0.07 |
AIRLOOP F6 NE | 0.39 | 0.39 | 0.07 | 0.07 |
AIRLOOP F6 N1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F6 N2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F6 S1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F6 S2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F7 SW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP F7 NW | 0.45 | 0.45 | 0.07 | 0.07 |
AIRLOOP F7 SE | 0.39 | 0.39 | 0.07 | 0.07 |
AIRLOOP F7 NE | 0.39 | 0.39 | 0.07 | 0.07 |
AIRLOOP F7 N1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F7 N2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F7 S1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F7 S2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F8 SW | 0.45 | 0.45 | 0.08 | 0.08 |
AIRLOOP F8 NW | 0.46 | 0.46 | 0.08 | 0.08 |
AIRLOOP F8 SE | 0.39 | 0.39 | 0.08 | 0.08 |
AIRLOOP F8 NE | 0.39 | 0.39 | 0.08 | 0.08 |
AIRLOOP F8 N1 | 0.27 | 0.27 | 0.04 | 0.04 |
AIRLOOP F8 N2 | 0.27 | 0.27 | 0.04 | 0.04 |
AIRLOOP F8 S1 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F8 S2 | 0.26 | 0.26 | 0.04 | 0.04 |
AIRLOOP F9 SW | 0.47 | 0.47 | 0.08 | 0.08 |
AIRLOOP F9 NW | 0.47 | 0.47 | 0.08 | 0.08 |
AIRLOOP F9 SE | 0.41 | 0.41 | 0.08 | 0.08 |
AIRLOOP F9 NE | 0.41 | 0.41 | 0.08 | 0.08 |
AIRLOOP F9 N1 | 0.28 | 0.28 | 0.04 | 0.04 |
AIRLOOP F9 N2 | 0.28 | 0.28 | 0.04 | 0.04 |
AIRLOOP F9 S1 | 0.27 | 0.27 | 0.04 | 0.04 |
AIRLOOP F9 S2 | 0.27 | 0.27 | 0.04 | 0.04 |
AIRLOOP T SW | 0.56 | 0.56 | 0.10 | 0.10 |
AIRLOOP T NW | 0.56 | 0.56 | 0.10 | 0.10 |
AIRLOOP T SE | 0.49 | 0.49 | 0.10 | 0.10 |
AIRLOOP T NE | 0.49 | 0.49 | 0.10 | 0.10 |
AIRLOOP T N1 | 0.36 | 0.36 | 0.06 | 0.06 |
AIRLOOP T N2 | 0.36 | 0.36 | 0.06 | 0.06 |
AIRLOOP T S1 | 0.36 | 0.36 | 0.06 | 0.06 |
AIRLOOP T S2 | 0.36 | 0.36 | 0.06 | 0.06 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4037.25 | 2653.50 | 104.25 |
G NW APARTMENT | 3458.00 | 3541.75 | 108.75 |
OFFICE | 1655.25 | 100.00 | 5.75 |
G NE APARTMENT | 3465.00 | 3542.25 | 109.75 |
G N1 APARTMENT | 2904.75 | 3886.00 | 155.00 |
G N2 APARTMENT | 2904.75 | 3888.25 | 154.50 |
G S1 APARTMENT | 3517.50 | 2818.00 | 150.00 |
G S2 APARTMENT | 3569.25 | 2756.00 | 148.00 |
F2 SW APARTMENT | 4890.75 | 1498.75 | 69.75 |
F2 NW APARTMENT | 4149.25 | 2623.25 | 85.50 |
F2 SE APARTMENT | 5135.25 | 1364.00 | 73.00 |
F2 NE APARTMENT | 4149.75 | 2637.50 | 87.25 |
F2 N1 APARTMENT | 3702.50 | 2774.00 | 117.00 |
F2 N2 APARTMENT | 3704.50 | 2774.25 | 116.75 |
F2 S1 APARTMENT | 4568.50 | 1285.50 | 106.25 |
F2 S2 APARTMENT | 4582.50 | 1268.75 | 105.75 |
F3 SW APARTMENT | 4961.00 | 1320.50 | 65.25 |
F3 NW APARTMENT | 4210.00 | 2436.75 | 82.25 |
F3 SE APARTMENT | 5053.00 | 1354.25 | 70.25 |
F3 NE APARTMENT | 4204.75 | 2424.50 | 81.75 |
F3 N1 APARTMENT | 3769.25 | 2495.00 | 105.75 |
F3 N2 APARTMENT | 3771.00 | 2497.50 | 105.75 |
F3 S1 APARTMENT | 4695.00 | 1017.50 | 95.50 |
F3 S2 APARTMENT | 4697.00 | 1020.25 | 95.50 |
F4 SW APARTMENT | 4933.50 | 1319.75 | 64.25 |
F4 NW APARTMENT | 4189.00 | 2414.25 | 80.25 |
F4 SE APARTMENT | 5006.50 | 1368.50 | 68.75 |
F4 NE APARTMENT | 4182.50 | 2389.25 | 79.75 |
F4 N1 APARTMENT | 3762.75 | 2431.75 | 100.00 |
F4 N2 APARTMENT | 3762.75 | 2434.25 | 99.75 |
F4 S1 APARTMENT | 4679.00 | 988.25 | 92.00 |
F4 S2 APARTMENT | 4682.00 | 993.50 | 91.25 |
M SW APARTMENT | 4943.00 | 1314.50 | 62.00 |
M NW APARTMENT | 4202.25 | 2388.75 | 78.25 |
M SE APARTMENT | 5015.75 | 1360.00 | 67.00 |
M NE APARTMENT | 4195.75 | 2360.75 | 77.00 |
M N1 APARTMENT | 3787.00 | 2390.50 | 93.25 |
M N2 APARTMENT | 3788.25 | 2391.50 | 92.75 |
M S1 APARTMENT | 4703.25 | 972.75 | 87.00 |
M S2 APARTMENT | 4704.50 | 981.25 | 87.25 |
F6 SW APARTMENT | 4818.25 | 1415.25 | 61.00 |
F6 NW APARTMENT | 4105.25 | 2459.25 | 76.25 |
F6 SE APARTMENT | 4900.25 | 1452.00 | 66.75 |
F6 NE APARTMENT | 4103.25 | 2444.75 | 77.50 |
F6 N1 APARTMENT | 3667.00 | 2476.50 | 90.50 |
F6 N2 APARTMENT | 3670.75 | 2476.00 | 90.50 |
F6 S1 APARTMENT | 4546.75 | 1092.00 | 84.25 |
F6 S2 APARTMENT | 4549.50 | 1097.25 | 84.25 |
F7 SW APARTMENT | 4752.00 | 1481.75 | 62.25 |
F7 NW APARTMENT | 4059.25 | 2498.00 | 76.50 |
F7 SE APARTMENT | 4839.00 | 1513.25 | 68.25 |
F7 NE APARTMENT | 4065.00 | 2488.75 | 78.25 |
F7 N1 APARTMENT | 3613.25 | 2527.25 | 89.25 |
F7 N2 APARTMENT | 3617.00 | 2527.25 | 89.00 |
F7 S1 APARTMENT | 4469.50 | 1166.50 | 82.50 |
F7 S2 APARTMENT | 4473.25 | 1176.75 | 82.75 |
F8 SW APARTMENT | 4712.50 | 1535.50 | 64.25 |
F8 NW APARTMENT | 4040.50 | 2525.25 | 76.50 |
F8 SE APARTMENT | 4802.75 | 1559.25 | 70.25 |
F8 NE APARTMENT | 4050.50 | 2515.00 | 79.00 |
F8 N1 APARTMENT | 3591.75 | 2559.75 | 87.75 |
F8 N2 APARTMENT | 3593.25 | 2557.00 | 87.25 |
F8 S1 APARTMENT | 4423.50 | 1229.00 | 81.00 |
F8 S2 APARTMENT | 4427.75 | 1236.75 | 81.00 |
F9 SW APARTMENT | 4746.50 | 1616.50 | 63.75 |
F9 NW APARTMENT | 4115.75 | 2549.75 | 77.00 |
F9 SE APARTMENT | 4833.00 | 1621.00 | 68.50 |
F9 NE APARTMENT | 4112.25 | 2539.75 | 78.75 |
F9 N1 APARTMENT | 3704.50 | 2582.00 | 85.00 |
F9 N2 APARTMENT | 3711.00 | 2581.75 | 85.25 |
F9 S1 APARTMENT | 4482.00 | 1314.50 | 75.75 |
F9 S2 APARTMENT | 4485.00 | 1320.50 | 75.50 |
T SW APARTMENT | 4921.00 | 2264.00 | 194.00 |
T NW APARTMENT | 4358.50 | 2776.50 | 181.75 |
T SE APARTMENT | 5015.25 | 2181.00 | 154.00 |
T NE APARTMENT | 4413.00 | 2743.00 | 171.25 |
T N1 APARTMENT | 4072.25 | 2772.50 | 92.00 |
T N2 APARTMENT | 4075.50 | 2772.00 | 92.00 |
T S1 APARTMENT | 4831.00 | 2032.25 | 113.25 |
T S2 APARTMENT | 4834.50 | 2036.75 | 116.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5713.75 | 4076.50 | 389.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 201.25 | 0.00 | 201.25 |
G NW APARTMENT | 0.00 | 150.75 | 0.00 | 150.75 |
OFFICE | 0.00 | 323.00 | 0.00 | 310.25 |
G NE APARTMENT | 0.00 | 223.75 | 0.00 | 223.75 |
G N1 APARTMENT | 0.00 | 241.25 | 0.00 | 241.25 |
G N2 APARTMENT | 0.00 | 246.75 | 0.00 | 246.75 |
G S1 APARTMENT | 0.00 | 551.50 | 0.00 | 551.50 |
G S2 APARTMENT | 0.00 | 497.50 | 0.00 | 497.50 |
F2 SW APARTMENT | 0.00 | 249.50 | 0.00 | 249.50 |
F2 NW APARTMENT | 0.00 | 163.75 | 0.00 | 163.75 |
F2 SE APARTMENT | 0.00 | 265.00 | 0.00 | 265.00 |
F2 NE APARTMENT | 0.00 | 260.25 | 0.00 | 260.25 |
F2 N1 APARTMENT | 0.00 | 269.00 | 0.00 | 269.00 |
F2 N2 APARTMENT | 0.00 | 274.00 | 0.00 | 274.00 |
F2 S1 APARTMENT | 0.00 | 654.00 | 0.00 | 654.00 |
F2 S2 APARTMENT | 0.00 | 647.75 | 0.00 | 647.75 |
F3 SW APARTMENT | 0.00 | 289.25 | 0.00 | 289.25 |
F3 NW APARTMENT | 0.00 | 196.25 | 0.00 | 196.25 |
F3 SE APARTMENT | 0.00 | 431.75 | 0.00 | 431.75 |
F3 NE APARTMENT | 0.00 | 313.50 | 0.00 | 313.50 |
F3 N1 APARTMENT | 0.00 | 306.50 | 0.00 | 306.50 |
F3 N2 APARTMENT | 0.00 | 311.50 | 0.00 | 311.50 |
F3 S1 APARTMENT | 0.00 | 728.00 | 0.00 | 728.00 |
F3 S2 APARTMENT | 0.00 | 734.00 | 0.00 | 734.00 |
F4 SW APARTMENT | 0.00 | 311.50 | 0.00 | 311.50 |
F4 NW APARTMENT | 0.00 | 215.00 | 0.00 | 215.00 |
F4 SE APARTMENT | 0.00 | 477.75 | 0.00 | 477.75 |
F4 NE APARTMENT | 0.00 | 346.25 | 0.00 | 346.25 |
F4 N1 APARTMENT | 0.00 | 334.50 | 0.00 | 334.50 |
F4 N2 APARTMENT | 0.00 | 342.00 | 0.00 | 342.00 |
F4 S1 APARTMENT | 0.00 | 743.75 | 0.00 | 743.75 |
F4 S2 APARTMENT | 0.00 | 756.50 | 0.00 | 756.50 |
M SW APARTMENT | 0.00 | 328.50 | 0.00 | 328.50 |
M NW APARTMENT | 0.00 | 233.75 | 0.00 | 233.75 |
M SE APARTMENT | 0.00 | 490.50 | 0.00 | 490.50 |
M NE APARTMENT | 0.00 | 372.25 | 0.00 | 372.25 |
M N1 APARTMENT | 0.00 | 353.50 | 0.00 | 353.50 |
M N2 APARTMENT | 0.00 | 359.50 | 0.00 | 359.50 |
M S1 APARTMENT | 0.00 | 749.25 | 0.00 | 749.25 |
M S2 APARTMENT | 0.00 | 757.00 | 0.00 | 757.00 |
F6 SW APARTMENT | 0.00 | 345.25 | 0.00 | 345.25 |
F6 NW APARTMENT | 0.00 | 246.75 | 0.00 | 246.75 |
F6 SE APARTMENT | 0.00 | 506.75 | 0.00 | 506.75 |
F6 NE APARTMENT | 0.00 | 387.50 | 0.00 | 387.50 |
F6 N1 APARTMENT | 0.00 | 371.00 | 0.00 | 371.00 |
F6 N2 APARTMENT | 0.00 | 381.00 | 0.00 | 381.00 |
F6 S1 APARTMENT | 0.00 | 757.75 | 0.00 | 757.75 |
F6 S2 APARTMENT | 0.00 | 767.25 | 0.00 | 767.25 |
F7 SW APARTMENT | 0.00 | 357.75 | 0.00 | 357.75 |
F7 NW APARTMENT | 0.00 | 259.00 | 0.00 | 259.00 |
F7 SE APARTMENT | 0.00 | 517.50 | 0.00 | 517.50 |
F7 NE APARTMENT | 0.00 | 405.00 | 0.00 | 405.00 |
F7 N1 APARTMENT | 0.00 | 387.00 | 0.00 | 387.00 |
F7 N2 APARTMENT | 0.00 | 395.50 | 0.00 | 395.50 |
F7 S1 APARTMENT | 0.00 | 758.00 | 0.00 | 758.00 |
F7 S2 APARTMENT | 0.00 | 765.00 | 0.00 | 765.00 |
F8 SW APARTMENT | 0.00 | 366.75 | 0.00 | 366.75 |
F8 NW APARTMENT | 0.00 | 271.00 | 0.00 | 271.00 |
F8 SE APARTMENT | 0.00 | 526.00 | 0.00 | 526.00 |
F8 NE APARTMENT | 0.00 | 419.00 | 0.00 | 419.00 |
F8 N1 APARTMENT | 0.00 | 398.50 | 0.00 | 398.50 |
F8 N2 APARTMENT | 0.00 | 406.25 | 0.00 | 406.25 |
F8 S1 APARTMENT | 0.00 | 748.00 | 0.00 | 748.00 |
F8 S2 APARTMENT | 0.00 | 758.50 | 0.00 | 758.50 |
F9 SW APARTMENT | 0.00 | 363.25 | 0.00 | 363.25 |
F9 NW APARTMENT | 0.00 | 272.25 | 0.00 | 272.25 |
F9 SE APARTMENT | 0.00 | 504.00 | 0.00 | 504.00 |
F9 NE APARTMENT | 0.00 | 409.25 | 0.00 | 409.25 |
F9 N1 APARTMENT | 0.00 | 384.00 | 0.00 | 384.00 |
F9 N2 APARTMENT | 0.00 | 391.00 | 0.00 | 391.00 |
F9 S1 APARTMENT | 0.00 | 692.50 | 0.00 | 692.50 |
F9 S2 APARTMENT | 0.00 | 700.75 | 0.00 | 700.75 |
T SW APARTMENT | 0.00 | 303.00 | 0.00 | 303.00 |
T NW APARTMENT | 0.00 | 219.75 | 0.00 | 219.75 |
T SE APARTMENT | 0.00 | 392.25 | 0.00 | 392.25 |
T NE APARTMENT | 0.00 | 292.25 | 0.00 | 292.25 |
T N1 APARTMENT | 0.00 | 254.50 | 0.00 | 254.50 |
T N2 APARTMENT | 0.00 | 253.00 | 0.00 | 253.00 |
T S1 APARTMENT | 0.00 | 469.50 | 0.00 | 469.50 |
T S2 APARTMENT | 0.00 | 469.00 | 0.00 | 469.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1097.75 | 0.00 | 1093.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.129 | 0.000 | 0.283 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.129 | 0.000 | 0.266 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.523 | 0.150 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.129 | 0.000 | 0.265 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.078 | 0.000 | 0.257 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.078 | 0.000 | 0.257 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.078 | 0.000 | 0.280 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.078 | 0.000 | 0.280 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.186 | 0.000 | 0.316 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.186 | 0.000 | 0.299 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.186 | 0.000 | 0.316 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.186 | 0.000 | 0.298 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.112 | 0.000 | 0.293 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.112 | 0.000 | 0.293 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.112 | 0.000 | 0.315 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.112 | 0.000 | 0.315 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.220 | 0.000 | 0.335 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.220 | 0.000 | 0.318 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.220 | 0.000 | 0.335 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.220 | 0.000 | 0.317 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.133 | 0.000 | 0.313 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.133 | 0.000 | 0.313 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.133 | 0.000 | 0.334 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.133 | 0.000 | 0.334 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.246 | 0.000 | 0.349 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.246 | 0.000 | 0.331 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.246 | 0.000 | 0.348 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.246 | 0.000 | 0.329 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.148 | 0.000 | 0.326 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.148 | 0.000 | 0.326 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.148 | 0.000 | 0.348 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.148 | 0.000 | 0.348 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.267 | 0.000 | 0.361 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.267 | 0.000 | 0.342 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.267 | 0.000 | 0.361 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.267 | 0.000 | 0.341 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.161 | 0.000 | 0.338 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.161 | 0.000 | 0.338 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.161 | 0.000 | 0.361 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.161 | 0.000 | 0.361 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.285 | 0.000 | 0.374 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.285 | 0.000 | 0.354 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.285 | 0.000 | 0.374 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.285 | 0.000 | 0.353 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.172 | 0.000 | 0.350 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.172 | 0.000 | 0.350 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.172 | 0.000 | 0.374 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.172 | 0.000 | 0.374 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.302 | 0.000 | 0.384 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.301 | 0.000 | 0.362 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.302 | 0.000 | 0.384 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.301 | 0.000 | 0.361 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.182 | 0.000 | 0.358 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.182 | 0.000 | 0.358 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.182 | 0.000 | 0.383 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.182 | 0.000 | 0.383 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.316 | 0.000 | 0.394 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.316 | 0.000 | 0.372 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.316 | 0.000 | 0.394 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.316 | 0.000 | 0.371 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.191 | 0.000 | 0.368 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.191 | 0.000 | 0.368 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.191 | 0.000 | 0.394 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.191 | 0.000 | 0.393 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.330 | 0.000 | 0.401 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.329 | 0.000 | 0.378 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.330 | 0.000 | 0.401 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.329 | 0.000 | 0.377 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.199 | 0.000 | 0.374 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.199 | 0.000 | 0.374 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.199 | 0.000 | 0.400 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.199 | 0.000 | 0.400 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.342 | 0.000 | 0.408 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.342 | 0.000 | 0.387 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.342 | 0.000 | 0.408 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.342 | 0.000 | 0.386 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.356 | 0.206 | 0.000 | 0.383 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.206 | 0.000 | 0.383 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.357 | 0.206 | 0.000 | 0.407 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.206 | 0.000 | 0.407 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.508 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.347 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.347 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.346 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.346 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 1005.71 | 31891.01 | 01-JAN-04:30 | 31891.01 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 2333.28 | 32552.26 | 13-JAN-03:15 | 125724.88 | 25-JUL-16:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
ElectricityPurchased:Plant | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
Cogeneration:ElectricityPurchased | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
ElectricityNet:Plant | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
Cogeneration:ElectricityNet | 4057.46 | 68714.04 | 13-JAN-03:15 | 207230.49 | 30-JUL-18:45 |
ExteriorLights:Electricity | 163.00 | 0.00 | 01-JAN-06:45 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 163.00 | 0.00 | 01-JAN-06:45 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 1005.71 | 31891.01 | 01-JAN-04:30 | 31891.01 | 01-JAN-00:15 |
Cooling:Electricity | 1286.36 | 0.00 | 01-JAN-00:15 | 92022.40 | 27-JUL-15:15 |
Heating:Electricity | 5.04 | 0.00 | 01-JAN-10:00 | 21832.70 | 09-JAN-05:00 |
Electricity:Plant | 127.29 | 36.93 | 02-JAN-23:15 | 6199.28 | 15-JUN-11:00 |
HeatRejection:Electricity | 46.78 | 0.00 | 01-JAN-02:00 | 3593.13 | 15-JUN-11:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 80.51 | 36.93 | 02-JAN-23:15 | 2606.14 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 767.70 | 2357.00 | 01-JAN-00:15 | 103093.13 | 09-JAN-06:30 |
Gas:Plant | 767.70 | 2357.00 | 01-JAN-00:15 | 103093.13 | 09-JAN-06:30 |
WaterSystems:Gas | 764.50 | 2357.00 | 01-JAN-00:15 | 72695.53 | 17-JAN-08:00 |
Water Heater:WaterSystems:Gas | 764.50 | 2357.00 | 01-JAN-00:15 | 72695.53 | 17-JAN-08:00 |
Heating:Gas | 3.20 | 0.00 | 01-JAN-00:15 | 72747.48 | 09-JAN-05:00 |
Boiler:Heating:Gas | 3.20 | 0.00 | 01-JAN-00:15 | 72747.48 | 09-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 5268.57 | 0.00 | 01-JAN-00:15 | 425808.43 | 15-JUN-16:30 |
PlantLoopCoolingDemand:HVAC | 5268.57 | 0.00 | 01-JAN-00:15 | 425808.43 | 15-JUN-16:30 |
CoolingCoils:PlantLoopCoolingDemand | 5268.57 | 0.00 | 01-JAN-00:15 | 425808.43 | 15-JUN-16:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 9896.52 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUL-17:15 |
Water:Plant | 9896.52 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 9896.52 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUL-17:15 |
MainsWater:Plant | 9896.52 | 0.00 | 01-JAN-02:15 | 0.00 | 25-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 5118.01 | 0.00 | 01-JAN-02:00 | 0.00 | 25-JUL-16:00 |
HeatRejection:MainsWater | 5118.01 | 0.00 | 01-JAN-02:00 | 0.00 | 25-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 601.62 | 245.04 | 16-JUL-01:15 | 83592.01 | 09-JAN-06:15 |
PlantLoopHeatingDemand:Plant | 589.03 | 245.04 | 16-JUL-01:15 | 45879.90 | 17-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 589.03 | 245.04 | 16-JUL-01:15 | 45879.90 | 17-JAN-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 7846.84 | 8267.15 | 20-DEC-04:00 | 613810.87 | 15-JUN-16:30 |
EnergyTransfer:Building | 3182.51 | 5041.25 | 17-FEB-21:45 | 264303.98 | 27-JUL-15:00 |
EnergyTransfer:Zone:G SW APARTMENT | 34.78 | 0.08 | 29-DEC-00:45 | 3764.07 | 30-SEP-14:15 |
Heating:EnergyTransfer | 99.87 | 0.00 | 25-JAN-12:15 | 80885.39 | 18-JAN-12:45 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.51 | 0.00 | 01-JAN-02:00 | 1151.81 | 09-JAN-05:00 |
Cooling:EnergyTransfer | 3082.64 | 0.00 | 05-JAN-20:15 | 264303.98 | 27-JUL-15:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 33.28 | 0.00 | 01-JAN-00:15 | 3764.07 | 30-SEP-14:15 |
EnergyTransfer:Zone:G NW APARTMENT | 30.26 | 0.32 | 10-APR-21:30 | 3675.88 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.50 | 0.00 | 24-JAN-14:00 | 1205.19 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 27.76 | 0.00 | 01-JAN-00:15 | 3675.88 | 03-JUN-16:30 |
EnergyTransfer:Zone:OFFICE | 45.27 | 0.06 | 21-NOV-06:45 | 4450.48 | 14-SEP-10:00 |
Heating:EnergyTransfer:Zone:OFFICE | 0.69 | 0.00 | 01-JAN-00:30 | 1082.15 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 44.58 | 0.00 | 01-JAN-00:15 | 4450.48 | 14-SEP-10:00 |
EnergyTransfer:Zone:G NE APARTMENT | 29.25 | 0.03 | 20-JAN-10:00 | 2983.28 | 28-JUL-10:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.96 | 0.00 | 01-JAN-07:15 | 1223.95 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 27.29 | 0.00 | 01-JAN-00:15 | 2983.28 | 28-JUL-10:00 |
EnergyTransfer:Zone:G N1 APARTMENT | 19.22 | 0.02 | 22-DEC-09:45 | 2055.22 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.97 | 0.00 | 01-JAN-09:15 | 961.26 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 18.25 | 0.00 | 01-JAN-00:15 | 2055.22 | 26-JUL-19:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 19.22 | 0.02 | 18-DEC-00:45 | 2043.94 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.96 | 0.00 | 01-JAN-09:00 | 963.11 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 18.26 | 0.00 | 01-JAN-00:15 | 2043.94 | 26-JUL-19:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 24.18 | 0.04 | 20-FEB-02:45 | 2252.11 | 28-OCT-12:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 502.02 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 23.88 | 0.00 | 02-JAN-12:30 | 2252.11 | 28-OCT-12:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 24.67 | 0.01 | 02-FEB-00:30 | 2302.82 | 28-OCT-12:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 495.49 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 24.37 | 0.00 | 02-JAN-12:30 | 2302.82 | 28-OCT-12:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 48.55 | 0.03 | 26-MAR-08:15 | 4458.17 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 1.07 | 0.00 | 01-JAN-05:15 | 1066.03 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 47.48 | 0.00 | 01-JAN-00:15 | 4458.17 | 12-OCT-14:30 |
EnergyTransfer:Zone:F2 NW APARTMENT | 41.18 | 0.59 | 06-MAR-10:15 | 4373.58 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 2.23 | 0.00 | 24-JAN-13:30 | 1222.41 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 38.95 | 0.00 | 01-JAN-00:15 | 4373.58 | 03-JUN-16:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 50.21 | 0.11 | 20-JAN-03:15 | 3968.46 | 30-AUG-10:30 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.78 | 0.00 | 01-JAN-01:00 | 1061.07 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 49.43 | 0.00 | 01-JAN-00:15 | 3968.46 | 30-AUG-10:30 |
EnergyTransfer:Zone:F2 NE APARTMENT | 40.33 | 0.30 | 13-FEB-09:15 | 3603.75 | 26-JUL-15:45 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 1.75 | 0.00 | 01-JAN-07:00 | 1264.57 | 27-DEC-14:45 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 38.58 | 0.00 | 01-JAN-00:15 | 3603.75 | 26-JUL-15:45 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 27.58 | 0.02 | 16-MAR-18:00 | 2486.73 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.71 | 0.00 | 01-JAN-00:15 | 1093.46 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 26.87 | 0.00 | 01-JAN-11:00 | 2486.73 | 26-JUL-19:00 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 27.59 | 0.00 | 20-JAN-19:15 | 2477.85 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.71 | 0.00 | 01-JAN-00:15 | 1094.18 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 26.88 | 0.00 | 01-JAN-11:00 | 2477.85 | 26-JUL-19:00 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 35.76 | 0.09 | 04-FEB-04:30 | 2745.36 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 350.18 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 35.55 | 0.00 | 02-JAN-12:30 | 2745.36 | 28-OCT-12:00 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 35.92 | 0.03 | 13-JAN-09:45 | 2755.69 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 349.30 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 35.71 | 0.00 | 02-JAN-12:30 | 2755.69 | 28-OCT-12:00 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 49.94 | 0.13 | 15-MAR-08:30 | 4474.33 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 1.00 | 0.00 | 01-JAN-05:15 | 1039.68 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 48.94 | 0.00 | 01-JAN-00:15 | 4474.33 | 12-OCT-14:30 |
EnergyTransfer:Zone:F3 NW APARTMENT | 42.55 | 0.16 | 09-MAR-02:45 | 4408.95 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 2.14 | 0.00 | 06-JAN-16:00 | 1299.56 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 40.41 | 0.00 | 01-JAN-00:15 | 4408.95 | 03-JUN-16:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 49.67 | 0.06 | 16-FEB-05:45 | 3825.02 | 30-SEP-12:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.73 | 0.00 | 01-JAN-00:45 | 1058.25 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 48.94 | 0.00 | 01-JAN-00:15 | 3825.02 | 30-SEP-12:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 41.74 | 0.27 | 17-JAN-07:00 | 3661.05 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 1.68 | 0.00 | 01-JAN-06:45 | 1416.38 | 27-DEC-14:45 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 40.07 | 0.00 | 01-JAN-00:15 | 3661.05 | 26-JUL-19:00 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 29.03 | 0.03 | 11-DEC-09:45 | 2513.65 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.65 | 0.00 | 01-JAN-00:15 | 1209.24 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 28.37 | 0.00 | 01-JAN-11:00 | 2513.65 | 26-JUL-19:00 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 29.04 | 0.01 | 09-FEB-23:00 | 2505.56 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.65 | 0.00 | 01-JAN-00:15 | 1210.31 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 28.38 | 0.00 | 01-JAN-11:00 | 2505.56 | 26-JUL-19:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 37.49 | 0.08 | 02-FEB-11:00 | 2786.52 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 268.14 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 37.29 | 0.00 | 02-JAN-12:30 | 2786.52 | 28-OCT-12:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 37.52 | 0.04 | 21-DEC-15:15 | 2786.37 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 270.01 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 37.32 | 0.00 | 02-JAN-12:30 | 2786.37 | 28-OCT-12:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 50.45 | 0.10 | 14-MAR-02:00 | 4500.89 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 1.05 | 0.00 | 01-JAN-05:15 | 1082.20 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 49.40 | 0.00 | 01-JAN-00:15 | 4500.89 | 12-OCT-14:30 |
EnergyTransfer:Zone:F4 NW APARTMENT | 43.22 | 0.03 | 06-MAR-10:15 | 4449.49 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 2.20 | 0.00 | 05-JAN-15:30 | 1472.00 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 41.02 | 0.00 | 01-JAN-00:15 | 4449.49 | 03-JUN-16:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 50.00 | 0.13 | 09-FEB-02:45 | 3833.24 | 30-SEP-12:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.79 | 0.00 | 01-JAN-00:45 | 1106.85 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 49.21 | 0.00 | 01-JAN-00:15 | 3833.24 | 30-SEP-12:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 42.44 | 0.04 | 04-MAR-06:45 | 3702.04 | 26-JUL-19:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 1.75 | 0.00 | 01-JAN-02:45 | 1582.69 | 27-DEC-14:45 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 40.69 | 0.00 | 01-JAN-00:15 | 3702.04 | 26-JUL-19:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 29.62 | 0.08 | 15-MAR-09:15 | 2543.00 | 03-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 1348.38 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 28.94 | 0.00 | 01-JAN-11:00 | 2543.00 | 03-JUN-17:15 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 29.63 | 0.01 | 04-JAN-10:45 | 2534.30 | 03-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 0.68 | 0.00 | 01-JAN-00:15 | 1349.55 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 28.95 | 0.00 | 01-JAN-11:00 | 2534.30 | 03-JUN-17:15 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 37.98 | 0.06 | 20-FEB-06:00 | 2822.84 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 278.80 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 37.77 | 0.00 | 02-JAN-12:30 | 2822.84 | 28-OCT-12:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 37.99 | 0.05 | 04-FEB-04:45 | 2821.29 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 278.43 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 37.78 | 0.00 | 02-JAN-12:30 | 2821.29 | 28-OCT-12:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 51.25 | 0.09 | 26-JAN-23:30 | 4547.34 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.11 | 0.00 | 01-JAN-05:30 | 1127.77 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 50.14 | 0.00 | 01-JAN-00:15 | 4547.34 | 12-OCT-14:30 |
EnergyTransfer:Zone:M NW APARTMENT | 44.17 | 0.03 | 22-FEB-11:00 | 4507.02 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.27 | 0.00 | 05-JAN-15:30 | 1639.78 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 41.90 | 0.00 | 01-JAN-00:15 | 4507.02 | 03-JUN-16:30 |
EnergyTransfer:Zone:M SE APARTMENT | 50.78 | 0.00 | 30-DEC-04:30 | 3874.99 | 28-SEP-10:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.85 | 0.00 | 01-JAN-00:45 | 1152.49 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 49.94 | 0.00 | 01-JAN-00:15 | 3874.99 | 28-SEP-10:15 |
EnergyTransfer:Zone:M NE APARTMENT | 43.39 | 0.01 | 09-APR-02:15 | 3783.84 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.82 | 0.00 | 01-JAN-03:15 | 1666.82 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 41.57 | 0.00 | 01-JAN-00:15 | 3783.84 | 15-JUN-17:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 30.47 | 0.01 | 08-JAN-02:30 | 2598.57 | 03-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.71 | 0.00 | 01-JAN-00:15 | 1467.46 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 29.75 | 0.00 | 01-JAN-10:45 | 2598.57 | 03-JUN-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 30.48 | 0.01 | 08-DEC-20:00 | 2589.65 | 03-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.71 | 0.00 | 01-JAN-00:15 | 1468.69 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 29.77 | 0.00 | 01-JAN-10:45 | 2589.65 | 03-JUN-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 38.73 | 0.16 | 01-FEB-19:30 | 2876.28 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 304.35 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 38.50 | 0.00 | 02-JAN-12:30 | 2876.28 | 28-OCT-12:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 38.74 | 0.07 | 22-DEC-03:15 | 2874.58 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.23 | 0.00 | 01-JAN-00:15 | 303.93 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 38.51 | 0.00 | 02-JAN-12:30 | 2874.58 | 28-OCT-12:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 50.66 | 0.01 | 16-FEB-06:45 | 4528.79 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 1.22 | 0.00 | 01-JAN-05:30 | 1210.00 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 49.44 | 0.00 | 01-JAN-00:15 | 4528.79 | 12-OCT-14:30 |
EnergyTransfer:Zone:F6 NW APARTMENT | 43.89 | 0.10 | 02-MAR-15:30 | 4500.63 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 2.43 | 0.00 | 06-JAN-16:30 | 1867.90 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 41.46 | 0.00 | 01-JAN-00:15 | 4500.63 | 03-JUN-16:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 50.18 | 0.04 | 03-DEC-02:15 | 3852.34 | 28-SEP-10:15 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 0.94 | 0.00 | 01-JAN-00:45 | 1236.55 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 49.24 | 0.00 | 01-JAN-00:15 | 3852.34 | 28-SEP-10:15 |
EnergyTransfer:Zone:F6 NE APARTMENT | 43.12 | 0.03 | 11-JAN-07:00 | 3793.36 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 1.99 | 0.00 | 01-JAN-06:45 | 1849.10 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 41.13 | 0.00 | 01-JAN-00:15 | 3793.36 | 15-JUN-17:45 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 30.04 | 0.02 | 10-DEC-09:45 | 2585.32 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 0.79 | 0.00 | 01-JAN-00:15 | 1633.80 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 29.25 | 0.00 | 01-JAN-10:45 | 2585.32 | 15-JUN-18:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 30.06 | 0.01 | 06-FEB-10:45 | 2577.40 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 0.79 | 0.00 | 01-JAN-00:15 | 1635.42 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 29.27 | 0.00 | 01-JAN-10:45 | 2577.40 | 15-JUN-18:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 37.96 | 0.00 | 22-DEC-04:00 | 2865.11 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 401.28 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 37.71 | 0.00 | 02-JAN-12:30 | 2865.11 | 28-OCT-12:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 37.97 | 0.01 | 22-DEC-04:00 | 2863.43 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.25 | 0.00 | 01-JAN-00:15 | 399.86 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 37.72 | 0.00 | 02-JAN-12:30 | 2863.43 | 28-OCT-12:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 50.54 | 0.03 | 09-FEB-05:30 | 4531.47 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 1.32 | 0.00 | 01-JAN-05:30 | 1281.76 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 49.22 | 0.00 | 01-JAN-00:15 | 4531.47 | 12-OCT-14:30 |
EnergyTransfer:Zone:F7 NW APARTMENT | 44.01 | 0.13 | 17-MAR-15:45 | 4513.68 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 2.58 | 0.00 | 06-JAN-16:45 | 2058.45 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 41.44 | 0.00 | 01-JAN-00:15 | 4513.68 | 03-JUN-16:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 50.05 | 0.02 | 14-DEC-18:45 | 3857.87 | 28-SEP-10:15 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 1.03 | 0.00 | 01-JAN-00:45 | 1310.28 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 49.02 | 0.00 | 01-JAN-00:15 | 3857.87 | 28-SEP-10:15 |
EnergyTransfer:Zone:F7 NE APARTMENT | 43.24 | 0.06 | 24-NOV-02:00 | 3821.59 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 2.13 | 0.00 | 01-JAN-06:45 | 2027.62 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 41.11 | 0.00 | 01-JAN-00:15 | 3821.59 | 15-JUN-17:45 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 30.03 | 0.07 | 26-DEC-08:45 | 2600.02 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 0.87 | 0.00 | 01-JAN-00:15 | 1770.74 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 29.17 | 0.00 | 01-JAN-10:45 | 2600.02 | 15-JUN-18:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 30.05 | 0.01 | 08-JAN-04:30 | 2592.19 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 0.87 | 0.00 | 01-JAN-00:15 | 1772.35 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 29.18 | 0.00 | 01-JAN-10:45 | 2592.19 | 15-JUN-18:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 37.69 | 0.15 | 21-DEC-13:30 | 2874.39 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 552.93 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 37.41 | 0.00 | 02-JAN-12:30 | 2874.39 | 28-OCT-12:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 37.70 | 0.11 | 10-DEC-11:45 | 2872.75 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 551.32 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 37.42 | 0.00 | 02-JAN-12:30 | 2872.75 | 28-OCT-12:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 50.69 | 0.02 | 04-DEC-10:00 | 4548.61 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 1.41 | 0.00 | 01-JAN-06:15 | 1360.10 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 49.27 | 0.00 | 01-JAN-00:15 | 4548.61 | 12-OCT-14:30 |
EnergyTransfer:Zone:F8 NW APARTMENT | 44.36 | 0.00 | 24-NOV-02:15 | 4534.42 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 2.71 | 0.00 | 24-JAN-13:30 | 2220.12 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 41.65 | 0.00 | 01-JAN-00:15 | 4534.42 | 03-JUN-16:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 50.19 | 0.06 | 31-MAR-06:30 | 3876.82 | 30-AUG-10:30 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 1.12 | 0.00 | 01-JAN-00:45 | 1389.36 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 49.07 | 0.00 | 01-JAN-00:15 | 3876.82 | 30-AUG-10:30 |
EnergyTransfer:Zone:F8 NE APARTMENT | 43.60 | 0.23 | 02-DEC-22:00 | 3861.96 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 2.27 | 0.00 | 01-JAN-06:45 | 2200.22 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 41.33 | 0.00 | 01-JAN-00:15 | 3861.96 | 15-JUN-17:45 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 30.27 | 0.01 | 16-DEC-03:00 | 2624.82 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 0.94 | 0.00 | 01-JAN-00:15 | 1894.64 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 29.33 | 0.00 | 01-JAN-10:45 | 2624.82 | 15-JUN-18:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 30.29 | 0.02 | 14-JAN-10:15 | 2616.67 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 0.94 | 0.00 | 01-JAN-00:15 | 1896.00 | 19-JAN-15:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 29.35 | 0.00 | 01-JAN-10:45 | 2616.67 | 15-JUN-18:00 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 37.71 | 0.01 | 28-FEB-23:30 | 2897.77 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 693.02 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 37.40 | 0.00 | 02-JAN-12:30 | 2897.77 | 28-OCT-12:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 37.72 | 0.00 | 13-JAN-20:45 | 2895.07 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 691.14 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 37.41 | 0.00 | 02-JAN-12:30 | 2895.07 | 28-OCT-12:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 52.04 | 0.11 | 23-MAR-05:00 | 4676.23 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 1.61 | 0.00 | 01-JAN-06:45 | 1533.84 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 50.43 | 0.00 | 01-JAN-00:15 | 4676.23 | 12-OCT-14:30 |
EnergyTransfer:Zone:F9 NW APARTMENT | 45.90 | 0.09 | 10-MAR-10:00 | 4683.47 | 03-JUN-16:30 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 2.95 | 0.00 | 24-JAN-13:45 | 2398.29 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 42.94 | 0.00 | 01-JAN-00:15 | 4683.47 | 03-JUN-16:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 51.51 | 0.08 | 16-DEC-19:15 | 4012.08 | 15-AUG-13:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 1.30 | 0.00 | 01-JAN-01:00 | 1560.73 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 50.21 | 0.00 | 01-JAN-00:15 | 4012.08 | 15-AUG-13:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 45.11 | 0.25 | 12-MAR-08:45 | 4017.73 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 2.50 | 0.00 | 01-JAN-06:45 | 2377.30 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 42.61 | 0.00 | 01-JAN-00:15 | 4017.73 | 15-JUN-17:45 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 31.57 | 0.01 | 30-DEC-22:00 | 2761.89 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 1.10 | 0.00 | 01-JAN-00:15 | 2051.94 | 19-JAN-13:30 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 30.47 | 0.00 | 01-JAN-10:30 | 2761.89 | 15-JUN-18:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 31.58 | 0.04 | 22-JAN-01:00 | 2753.86 | 15-JUN-18:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 1.10 | 0.00 | 01-JAN-00:15 | 2047.29 | 19-JAN-13:30 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 30.49 | 0.00 | 01-JAN-10:30 | 2753.86 | 15-JUN-18:00 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 38.75 | 0.04 | 02-MAR-05:00 | 3010.98 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 870.87 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 38.38 | 0.00 | 02-JAN-12:45 | 3010.98 | 28-OCT-12:00 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 38.77 | 0.01 | 02-MAR-05:00 | 3010.64 | 28-OCT-12:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 869.09 | 12-JAN-10:45 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 38.40 | 0.00 | 02-JAN-12:45 | 3010.64 | 28-OCT-12:00 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 57.18 | 0.46 | 23-MAR-12:15 | 5724.70 | 12-OCT-14:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 3.10 | 0.00 | 01-JAN-09:00 | 2028.52 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 54.08 | 0.00 | 01-JAN-00:15 | 5724.70 | 12-OCT-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 51.16 | 0.03 | 21-MAR-22:45 | 5558.34 | 27-JUL-15:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 4.51 | 0.00 | 01-JAN-14:30 | 2620.24 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 46.65 | 0.00 | 01-JAN-00:15 | 5558.34 | 27-JUL-15:00 |
EnergyTransfer:Zone:T SE APARTMENT | 56.53 | 0.06 | 08-APR-22:45 | 4937.42 | 15-AUG-13:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 2.71 | 0.00 | 01-JAN-07:30 | 2037.85 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 53.82 | 0.00 | 01-JAN-00:15 | 4937.42 | 15-AUG-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 50.19 | 0.11 | 12-APR-00:45 | 4792.42 | 15-AUG-13:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 3.97 | 0.00 | 01-JAN-10:00 | 2605.38 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 46.21 | 0.00 | 01-JAN-00:15 | 4792.42 | 15-AUG-13:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 36.66 | 0.06 | 18-NOV-07:30 | 3524.31 | 26-JUL-16:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 2.18 | 0.00 | 01-JAN-08:45 | 2274.58 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 34.48 | 0.00 | 01-JAN-00:15 | 3524.31 | 26-JUL-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 36.67 | 0.37 | 19-FEB-11:15 | 3521.14 | 26-JUL-14:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 2.17 | 0.00 | 01-JAN-08:45 | 2269.99 | 18-JAN-12:45 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 34.50 | 0.00 | 01-JAN-00:15 | 3521.14 | 26-JUL-14:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 43.28 | 0.01 | 16-FEB-12:30 | 3970.57 | 28-OCT-12:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 1.13 | 0.00 | 01-JAN-01:00 | 1119.80 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 42.15 | 0.00 | 01-JAN-00:15 | 3970.57 | 28-OCT-12:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 43.31 | 0.01 | 20-NOV-02:15 | 3971.84 | 28-OCT-12:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 1.14 | 0.00 | 01-JAN-01:00 | 1121.43 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 42.17 | 0.00 | 01-JAN-00:15 | 3971.84 | 28-OCT-12:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 591.42 | 245.04 | 16-JUL-01:15 | 82581.58 | 09-JAN-06:15 |
WaterSystems:EnergyTransfer | 589.02 | 245.04 | 16-JUL-01:15 | 45875.21 | 17-JAN-08:00 |
sub cat:WaterSystems:EnergyTransfer | 589.02 | 245.04 | 16-JUL-01:15 | 45875.21 | 17-JAN-08:00 |
EnergyTransfer:HVAC | 4072.91 | 0.00 | 02-JAN-23:15 | 334726.63 | 15-JUN-16:45 |
CoolingCoils:EnergyTransfer | 4056.48 | 0.00 | 01-JAN-00:15 | 334726.63 | 15-JUN-16:45 |
HeatingCoils:EnergyTransfer | 16.42 | 0.00 | 01-JAN-10:00 | 76116.83 | 09-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 12.59 | 0.00 | 01-JAN-10:00 | 57601.44 | 09-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 12.59 | 0.00 | 01-JAN-10:00 | 57601.44 | 09-JAN-05:00 |
Boilers:EnergyTransfer | 2.40 | 0.00 | 01-JAN-00:15 | 54560.61 | 09-JAN-05:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.508 | -33.275 | 0.000 | 0.000 | 3.592 | 1.087 | 12.213 | 32.618 | 0.000 | 2.173 | 0.001 | 0.000 | -5.707 | 0.000 | -3.794 | -10.415 |
G NW APARTMENT | 2.501 | -27.757 | 0.000 | 0.000 | 3.626 | 1.087 | 12.213 | 22.692 | 0.000 | 2.172 | 0.000 | 0.000 | -5.634 | 0.000 | -3.186 | -7.713 |
OFFICE | 0.691 | -44.580 | 0.000 | 0.000 | 0.500 | 29.882 | 9.495 | 32.023 | 0.000 | 2.044 | 0.001 | 0.000 | -5.759 | 0.000 | -0.875 | -23.423 |
G NE APARTMENT | 1.965 | -27.289 | 0.000 | 0.000 | 3.636 | 1.087 | 12.213 | 22.152 | 0.000 | 2.166 | 0.000 | 0.000 | -5.252 | 0.000 | -3.127 | -7.550 |
G N1 APARTMENT | 0.965 | -18.254 | 0.000 | 0.000 | 3.638 | 1.087 | 12.213 | 10.244 | 0.000 | 1.355 | 0.000 | 0.000 | -3.381 | 0.000 | -2.583 | -5.283 |
G N2 APARTMENT | 0.963 | -18.260 | 0.000 | 0.000 | 3.639 | 1.087 | 12.213 | 10.241 | 0.000 | 1.355 | 0.000 | 0.000 | -3.377 | 0.000 | -2.581 | -5.280 |
G S1 APARTMENT | 0.299 | -23.882 | 0.000 | 0.000 | 3.588 | 1.087 | 12.213 | 20.322 | 0.000 | 1.352 | 0.001 | 0.000 | -3.441 | 0.000 | -3.330 | -8.208 |
G S2 APARTMENT | 0.302 | -24.367 | 0.000 | 0.000 | 3.586 | 1.087 | 12.213 | 20.302 | 0.000 | 1.354 | 0.001 | 0.000 | -3.454 | 0.000 | -3.360 | -7.663 |
F2 SW APARTMENT | 1.071 | -47.476 | 0.000 | 0.000 | 3.548 | 1.087 | 12.213 | 31.787 | 0.000 | 3.075 | 5.792 | 0.000 | -6.379 | 0.000 | -4.717 | -0.000 |
F2 NW APARTMENT | 2.232 | -38.950 | 0.000 | 0.000 | 3.590 | 1.087 | 12.213 | 22.122 | 0.000 | 3.072 | 4.996 | 0.000 | -6.279 | 0.000 | -4.082 | -0.000 |
F2 SE APARTMENT | 0.775 | -49.431 | 0.000 | 0.000 | 3.548 | 1.087 | 12.213 | 31.405 | 0.000 | 3.072 | 8.339 | 0.000 | -6.261 | 0.000 | -4.747 | -0.000 |
F2 NE APARTMENT | 1.751 | -38.582 | 0.000 | 0.000 | 3.599 | 1.087 | 12.213 | 21.595 | 0.000 | 3.062 | 5.122 | 0.000 | -5.836 | 0.000 | -4.011 | -0.000 |
F2 N1 APARTMENT | 0.712 | -26.865 | 0.000 | 0.000 | 3.597 | 1.087 | 12.213 | 9.942 | 0.000 | 1.902 | 4.609 | 0.000 | -3.830 | 0.000 | -3.367 | -0.000 |
F2 N2 APARTMENT | 0.713 | -26.875 | 0.000 | 0.000 | 3.597 | 1.087 | 12.213 | 9.940 | 0.000 | 1.902 | 4.612 | 0.000 | -3.825 | 0.000 | -3.363 | -0.000 |
F2 S1 APARTMENT | 0.214 | -35.550 | 0.000 | 0.000 | 3.539 | 1.087 | 12.213 | 19.787 | 0.000 | 1.896 | 4.826 | 0.000 | -3.851 | 0.000 | -4.160 | -0.000 |
F2 S2 APARTMENT | 0.213 | -35.706 | 0.000 | 0.000 | 3.538 | 1.087 | 12.213 | 19.782 | 0.000 | 1.897 | 4.997 | 0.000 | -3.855 | 0.000 | -4.165 | -0.000 |
F3 SW APARTMENT | 1.004 | -48.939 | 0.000 | 0.000 | 3.543 | 1.087 | 12.213 | 31.503 | 0.000 | 3.612 | 7.613 | 0.000 | -6.505 | 0.000 | -5.131 | -0.001 |
F3 NW APARTMENT | 2.138 | -40.412 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 21.991 | 0.000 | 3.609 | 6.713 | 0.000 | -6.438 | 0.000 | -4.485 | -0.001 |
F3 SE APARTMENT | 0.730 | -48.941 | 0.000 | 0.000 | 3.547 | 1.087 | 12.213 | 31.213 | 0.000 | 3.597 | 7.969 | 0.000 | -6.312 | 0.000 | -5.102 | -0.001 |
F3 NE APARTMENT | 1.677 | -40.067 | 0.000 | 0.000 | 3.592 | 1.087 | 12.213 | 21.479 | 0.000 | 3.594 | 6.818 | 0.000 | -5.980 | 0.000 | -4.412 | -0.000 |
F3 N1 APARTMENT | 0.653 | -28.373 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 9.926 | 0.000 | 2.229 | 6.345 | 0.000 | -3.953 | 0.000 | -3.714 | -0.000 |
F3 N2 APARTMENT | 0.654 | -28.384 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 9.924 | 0.000 | 2.228 | 6.350 | 0.000 | -3.948 | 0.000 | -3.710 | -0.000 |
F3 S1 APARTMENT | 0.198 | -37.288 | 0.000 | 0.000 | 3.531 | 1.087 | 12.213 | 19.612 | 0.000 | 2.220 | 6.867 | 0.000 | -3.939 | 0.000 | -4.501 | -0.000 |
F3 S2 APARTMENT | 0.198 | -37.319 | 0.000 | 0.000 | 3.531 | 1.087 | 12.213 | 19.610 | 0.000 | 2.220 | 6.900 | 0.000 | -3.938 | 0.000 | -4.501 | -0.000 |
F4 SW APARTMENT | 1.055 | -49.395 | 0.000 | 0.000 | 3.543 | 1.087 | 12.213 | 31.318 | 0.000 | 4.013 | 8.111 | 0.000 | -6.549 | 0.000 | -5.395 | -0.001 |
F4 NW APARTMENT | 2.199 | -41.024 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 21.920 | 0.000 | 4.010 | 7.245 | 0.000 | -6.501 | 0.000 | -4.732 | -0.000 |
F4 SE APARTMENT | 0.790 | -49.206 | 0.000 | 0.000 | 3.547 | 1.087 | 12.213 | 31.053 | 0.000 | 3.993 | 8.222 | 0.000 | -6.342 | 0.000 | -5.356 | -0.000 |
F4 NE APARTMENT | 1.749 | -40.690 | 0.000 | 0.000 | 3.590 | 1.087 | 12.213 | 21.420 | 0.000 | 3.990 | 7.338 | 0.000 | -6.036 | 0.000 | -4.660 | -0.000 |
F4 N1 APARTMENT | 0.676 | -28.941 | 0.000 | 0.000 | 3.584 | 1.087 | 12.213 | 9.932 | 0.000 | 2.472 | 6.896 | 0.000 | -4.005 | 0.000 | -3.912 | -0.000 |
F4 N2 APARTMENT | 0.675 | -28.954 | 0.000 | 0.000 | 3.584 | 1.087 | 12.213 | 9.929 | 0.000 | 2.471 | 6.903 | 0.000 | -4.000 | 0.000 | -3.908 | -0.000 |
F4 S1 APARTMENT | 0.212 | -37.768 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 19.504 | 0.000 | 2.463 | 7.434 | 0.000 | -3.971 | 0.000 | -4.703 | -0.000 |
F4 S2 APARTMENT | 0.212 | -37.779 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 19.501 | 0.000 | 2.463 | 7.445 | 0.000 | -3.969 | 0.000 | -4.702 | -0.000 |
M SW APARTMENT | 1.113 | -50.137 | 0.000 | 0.000 | 3.543 | 1.087 | 12.213 | 31.148 | 0.000 | 4.339 | 8.926 | 0.000 | -6.591 | 0.000 | -5.640 | -0.000 |
M NW APARTMENT | 2.271 | -41.898 | 0.000 | 0.000 | 3.582 | 1.087 | 12.213 | 21.845 | 0.000 | 4.335 | 8.077 | 0.000 | -6.555 | 0.000 | -4.957 | -0.000 |
M SE APARTMENT | 0.847 | -49.937 | 0.000 | 0.000 | 3.547 | 1.087 | 12.213 | 30.899 | 0.000 | 4.316 | 9.007 | 0.000 | -6.380 | 0.000 | -5.598 | -0.000 |
M NE APARTMENT | 1.824 | -41.570 | 0.000 | 0.000 | 3.589 | 1.087 | 12.213 | 21.353 | 0.000 | 4.312 | 8.165 | 0.000 | -6.086 | 0.000 | -4.886 | -0.001 |
M N1 APARTMENT | 0.711 | -29.754 | 0.000 | 0.000 | 3.582 | 1.087 | 12.213 | 9.924 | 0.000 | 2.669 | 7.710 | 0.000 | -4.047 | 0.000 | -4.094 | -0.000 |
M N2 APARTMENT | 0.711 | -29.769 | 0.000 | 0.000 | 3.583 | 1.087 | 12.213 | 9.922 | 0.000 | 2.668 | 7.719 | 0.000 | -4.043 | 0.000 | -4.090 | -0.000 |
M S1 APARTMENT | 0.229 | -38.497 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 19.404 | 0.000 | 2.661 | 8.268 | 0.000 | -3.999 | 0.000 | -4.896 | -0.001 |
M S2 APARTMENT | 0.229 | -38.506 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 19.402 | 0.000 | 2.660 | 8.276 | 0.000 | -3.996 | 0.000 | -4.894 | -0.000 |
F6 SW APARTMENT | 1.223 | -49.439 | 0.000 | 0.000 | 3.546 | 1.087 | 12.213 | 31.063 | 0.000 | 4.630 | 8.070 | 0.000 | -6.575 | 0.000 | -5.819 | -0.000 |
F6 NW APARTMENT | 2.434 | -41.458 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 21.841 | 0.000 | 4.625 | 7.295 | 0.000 | -6.533 | 0.000 | -5.090 | -0.000 |
F6 SE APARTMENT | 0.945 | -49.236 | 0.000 | 0.000 | 3.550 | 1.087 | 12.213 | 30.826 | 0.000 | 4.603 | 8.148 | 0.000 | -6.362 | 0.000 | -5.773 | -0.000 |
F6 NE APARTMENT | 1.989 | -41.130 | 0.000 | 0.000 | 3.593 | 1.087 | 12.213 | 21.360 | 0.000 | 4.599 | 7.375 | 0.000 | -6.064 | 0.000 | -5.020 | -0.001 |
F6 N1 APARTMENT | 0.790 | -29.249 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 9.956 | 0.000 | 2.850 | 6.984 | 0.000 | -4.034 | 0.000 | -4.182 | -0.000 |
F6 N2 APARTMENT | 0.790 | -29.266 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 9.953 | 0.000 | 2.849 | 6.995 | 0.000 | -4.029 | 0.000 | -4.178 | -0.000 |
F6 S1 APARTMENT | 0.254 | -37.707 | 0.000 | 0.000 | 3.533 | 1.087 | 12.213 | 19.357 | 0.000 | 2.843 | 7.441 | 0.000 | -3.991 | 0.000 | -5.029 | -0.000 |
F6 S2 APARTMENT | 0.254 | -37.718 | 0.000 | 0.000 | 3.533 | 1.087 | 12.213 | 19.355 | 0.000 | 2.842 | 7.450 | 0.000 | -3.988 | 0.000 | -5.027 | -0.000 |
F7 SW APARTMENT | 1.320 | -49.218 | 0.000 | 0.000 | 3.549 | 1.087 | 12.213 | 30.969 | 0.000 | 4.872 | 7.768 | 0.000 | -6.573 | 0.000 | -5.987 | -0.000 |
F7 NW APARTMENT | 2.576 | -41.435 | 0.000 | 0.000 | 3.590 | 1.087 | 12.213 | 21.816 | 0.000 | 4.868 | 7.039 | 0.000 | -6.529 | 0.000 | -5.225 | -0.000 |
F7 SE APARTMENT | 1.033 | -49.017 | 0.000 | 0.000 | 3.553 | 1.087 | 12.213 | 30.742 | 0.000 | 4.843 | 7.845 | 0.000 | -6.359 | 0.000 | -5.939 | -0.000 |
F7 NE APARTMENT | 2.133 | -41.109 | 0.000 | 0.000 | 3.596 | 1.087 | 12.213 | 21.343 | 0.000 | 4.838 | 7.113 | 0.000 | -6.058 | 0.000 | -5.155 | -0.000 |
F7 N1 APARTMENT | 0.865 | -29.166 | 0.000 | 0.000 | 3.590 | 1.087 | 12.213 | 9.970 | 0.000 | 2.996 | 6.752 | 0.000 | -4.031 | 0.000 | -4.276 | -0.000 |
F7 N2 APARTMENT | 0.865 | -29.183 | 0.000 | 0.000 | 3.591 | 1.087 | 12.213 | 9.967 | 0.000 | 2.995 | 6.765 | 0.000 | -4.026 | 0.000 | -4.272 | -0.000 |
F7 S1 APARTMENT | 0.278 | -37.412 | 0.000 | 0.000 | 3.535 | 1.087 | 12.213 | 19.303 | 0.000 | 2.990 | 7.153 | 0.000 | -3.991 | 0.000 | -5.156 | -0.001 |
F7 S2 APARTMENT | 0.279 | -37.424 | 0.000 | 0.000 | 3.535 | 1.087 | 12.213 | 19.301 | 0.000 | 2.989 | 7.163 | 0.000 | -3.988 | 0.000 | -5.154 | -0.000 |
F8 SW APARTMENT | 1.415 | -49.269 | 0.000 | 0.000 | 3.551 | 1.087 | 12.213 | 30.873 | 0.000 | 5.094 | 7.757 | 0.000 | -6.576 | 0.000 | -6.143 | -0.001 |
F8 NW APARTMENT | 2.706 | -41.651 | 0.000 | 0.000 | 3.592 | 1.087 | 12.213 | 21.781 | 0.000 | 5.089 | 7.074 | 0.000 | -6.534 | 0.000 | -5.356 | -0.000 |
F8 SE APARTMENT | 1.122 | -49.069 | 0.000 | 0.000 | 3.555 | 1.087 | 12.213 | 30.655 | 0.000 | 5.063 | 7.832 | 0.000 | -6.361 | 0.000 | -6.094 | -0.000 |
F8 NE APARTMENT | 2.269 | -41.328 | 0.000 | 0.000 | 3.598 | 1.087 | 12.213 | 21.314 | 0.000 | 5.057 | 7.142 | 0.000 | -6.063 | 0.000 | -5.288 | -0.000 |
F8 N1 APARTMENT | 0.941 | -29.332 | 0.000 | 0.000 | 3.593 | 1.087 | 12.213 | 9.973 | 0.000 | 3.132 | 6.799 | 0.000 | -4.034 | 0.000 | -4.371 | -0.000 |
F8 N2 APARTMENT | 0.942 | -29.349 | 0.000 | 0.000 | 3.593 | 1.087 | 12.213 | 9.970 | 0.000 | 3.131 | 6.812 | 0.000 | -4.030 | 0.000 | -4.368 | -0.000 |
F8 S1 APARTMENT | 0.306 | -37.399 | 0.000 | 0.000 | 3.537 | 1.087 | 12.213 | 19.248 | 0.000 | 3.127 | 7.150 | 0.000 | -3.993 | 0.000 | -5.275 | -0.000 |
F8 S2 APARTMENT | 0.306 | -37.411 | 0.000 | 0.000 | 3.537 | 1.087 | 12.213 | 19.245 | 0.000 | 3.126 | 7.161 | 0.000 | -3.991 | 0.000 | -5.273 | -0.000 |
F9 SW APARTMENT | 1.606 | -50.429 | 0.000 | 0.000 | 3.554 | 1.087 | 12.213 | 30.747 | 0.000 | 5.292 | 8.755 | 0.000 | -6.578 | 0.000 | -6.245 | -0.000 |
F9 NW APARTMENT | 2.952 | -42.943 | 0.000 | 0.000 | 3.593 | 1.087 | 12.213 | 21.698 | 0.000 | 5.287 | 8.118 | 0.000 | -6.549 | 0.000 | -5.456 | -0.001 |
F9 SE APARTMENT | 1.297 | -50.213 | 0.000 | 0.000 | 3.558 | 1.087 | 12.213 | 30.537 | 0.000 | 5.261 | 8.825 | 0.000 | -6.364 | 0.000 | -6.200 | -0.000 |
F9 NE APARTMENT | 2.501 | -42.608 | 0.000 | 0.000 | 3.599 | 1.087 | 12.213 | 21.241 | 0.000 | 5.255 | 8.186 | 0.000 | -6.080 | 0.000 | -5.392 | -0.000 |
F9 N1 APARTMENT | 1.096 | -30.469 | 0.000 | 0.000 | 3.594 | 1.087 | 12.213 | 9.945 | 0.000 | 3.254 | 7.762 | 0.000 | -4.043 | 0.000 | -4.438 | -0.000 |
F9 N2 APARTMENT | 1.096 | -30.486 | 0.000 | 0.000 | 3.594 | 1.087 | 12.213 | 9.942 | 0.000 | 3.253 | 7.776 | 0.000 | -4.039 | 0.000 | -4.435 | -0.000 |
F9 S1 APARTMENT | 0.370 | -38.382 | 0.000 | 0.000 | 3.540 | 1.087 | 12.213 | 19.178 | 0.000 | 3.250 | 8.080 | 0.000 | -3.995 | 0.000 | -5.342 | -0.000 |
F9 S2 APARTMENT | 0.370 | -38.395 | 0.000 | 0.000 | 3.541 | 1.087 | 12.213 | 19.176 | 0.000 | 3.249 | 8.092 | 0.000 | -3.992 | 0.000 | -5.340 | -0.000 |
T SW APARTMENT | 3.102 | -54.074 | 0.000 | 0.000 | 3.581 | 1.087 | 12.213 | 29.925 | 0.000 | 5.483 | 11.144 | 0.000 | -6.149 | 0.000 | -6.310 | -0.000 |
T NW APARTMENT | 4.507 | -46.648 | 0.000 | 0.000 | 3.607 | 1.087 | 12.213 | 20.951 | 0.000 | 5.476 | 10.686 | 0.000 | -6.207 | 0.000 | -5.671 | -0.000 |
T SE APARTMENT | 2.712 | -53.816 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 29.751 | 0.000 | 5.464 | 11.225 | 0.000 | -5.954 | 0.000 | -6.268 | -0.000 |
T NE APARTMENT | 3.974 | -46.212 | 0.000 | 0.000 | 3.614 | 1.087 | 12.213 | 20.566 | 0.000 | 5.455 | 10.722 | 0.000 | -5.801 | 0.000 | -5.617 | -0.001 |
T N1 APARTMENT | 2.176 | -34.479 | 0.000 | 0.000 | 3.609 | 1.087 | 12.213 | 9.642 | 0.000 | 3.375 | 10.820 | 0.000 | -3.838 | 0.000 | -4.605 | -0.000 |
T N2 APARTMENT | 2.175 | -34.499 | 0.000 | 0.000 | 3.610 | 1.087 | 12.213 | 9.639 | 0.000 | 3.375 | 10.839 | 0.000 | -3.834 | 0.000 | -4.604 | -0.000 |
T S1 APARTMENT | 1.132 | -42.146 | 0.000 | 0.000 | 3.571 | 1.087 | 12.213 | 18.758 | 0.000 | 3.379 | 11.158 | 0.000 | -3.776 | 0.000 | -5.375 | -0.000 |
T S2 APARTMENT | 1.136 | -42.172 | 0.000 | 0.000 | 3.572 | 1.087 | 12.213 | 18.755 | 0.000 | 3.379 | 11.177 | 0.000 | -3.772 | 0.000 | -5.373 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 7.425 | 0.000 | 19.911 | 0.001 | 0.000 | -1.385 | 0.000 | -11.259 | -31.132 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.671 | 0.000 | 0.364 | 0.000 | 0.000 | -0.850 | 0.000 | -0.248 | -19.377 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.626 | 0.000 | 0.430 | 0.000 | 0.000 | -0.884 | 0.000 | -0.307 | -19.304 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.586 | 0.000 | 0.474 | 0.000 | 0.000 | -0.902 | 0.000 | -0.350 | -19.249 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 3.510 | 0.000 | 0.479 | 0.000 | 0.000 | -0.942 | 0.000 | -0.410 | -35.516 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.553 | 0.000 | 0.546 | 0.000 | 0.000 | -0.907 | 0.000 | -0.404 | -19.227 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.553 | 0.000 | 0.580 | 0.000 | 0.000 | -0.899 | 0.000 | -0.421 | -19.253 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.541 | 0.000 | 0.604 | 0.000 | 0.000 | -0.899 | 0.000 | -0.439 | -19.247 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.512 | 0.000 | 0.615 | 0.000 | 0.000 | -0.905 | 0.000 | -0.457 | -19.205 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 3.302 | 0.000 | 0.517 | 0.000 | 0.000 | -0.880 | 0.000 | -0.514 | -27.016 |
Total Facility | 99.867 | -3082.592 | 0.000 | 0.000 | 282.772 | 296.560 | 982.450 | 1680.598 | 0.000 | 299.049 | 553.063 | 0.000 | -415.341 | 0.000 | -392.361 | -304.079 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-SEP-14:15 | 0.00 | -3763.63 | 0.00 | 0.00 | 40.62 | 22.70 | 400.26 | 4365.23 | 0.00 | 115.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1180.26 |
G NW APARTMENT | 03-JUN-16:30 | 0.00 | -3676.17 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3474.65 | 0.00 | 228.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.63 |
OFFICE | 14-SEP-10:00 | 0.00 | -4449.84 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 3715.79 | 0.00 | 186.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2451.98 |
G NE APARTMENT | 28-JUL-10:00 | 0.00 | -2983.15 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3000.42 | 0.00 | 163.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -640.43 |
G N1 APARTMENT | 26-JUL-19:00 | 0.00 | -2055.42 | 0.00 | 0.00 | 141.18 | 103.77 | 547.42 | 578.82 | 0.00 | 306.78 | 377.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G N2 APARTMENT | 26-JUL-19:00 | 0.00 | -2044.14 | 0.00 | 0.00 | 141.02 | 103.77 | 547.42 | 578.45 | 0.00 | 306.42 | 367.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G S1 APARTMENT | 28-OCT-12:45 | 0.00 | -2252.03 | 0.00 | 0.00 | 40.54 | 12.97 | 388.49 | 3297.31 | 0.00 | 17.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1504.95 |
G S2 APARTMENT | 28-OCT-12:45 | 0.00 | -2302.73 | 0.00 | 0.00 | 40.67 | 12.97 | 388.49 | 3297.93 | 0.00 | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1455.24 |
F2 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4457.94 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 4708.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -713.84 |
F2 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4373.97 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3441.57 | 0.00 | 328.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -134.40 |
F2 SE APARTMENT | 30-AUG-10:30 | 0.00 | -3968.51 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3874.71 | 0.00 | 154.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.15 |
F2 NE APARTMENT | 26-JUL-15:45 | 0.00 | -3603.03 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2088.70 | 0.00 | 370.85 | 578.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 26-JUL-19:00 | 0.00 | -2486.92 | 0.00 | 0.00 | 140.61 | 103.77 | 547.42 | 620.47 | 0.00 | 437.47 | 637.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 26-JUL-19:00 | 0.00 | -2478.04 | 0.00 | 0.00 | 140.49 | 103.77 | 547.42 | 620.07 | 0.00 | 437.06 | 629.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2745.46 | 0.00 | 0.00 | 40.03 | 12.97 | 406.15 | 3412.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.97 |
F2 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2755.79 | 0.00 | 0.00 | 40.02 | 12.97 | 406.15 | 3411.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1115.06 |
F3 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4474.10 | 0.00 | 0.00 | 40.68 | 22.70 | 400.26 | 4703.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -693.36 |
F3 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4409.32 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3426.20 | 0.00 | 388.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -143.58 |
F3 SE APARTMENT | 30-SEP-12:00 | 0.00 | -3824.60 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3491.49 | 0.00 | 130.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.51 |
F3 NE APARTMENT | 26-JUL-19:00 | 0.00 | -3661.22 | 0.00 | 0.00 | 141.70 | 103.77 | 547.42 | 1033.99 | 0.00 | 863.36 | 970.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 26-JUL-19:00 | 0.00 | -2513.82 | 0.00 | 0.00 | 140.01 | 103.77 | 547.42 | 643.87 | 0.00 | 514.58 | 564.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 26-JUL-19:00 | 0.00 | -2505.73 | 0.00 | 0.00 | 139.89 | 103.77 | 547.42 | 643.42 | 0.00 | 514.10 | 557.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2786.66 | 0.00 | 0.00 | 39.91 | 12.97 | 406.15 | 3408.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.00 |
F3 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2786.51 | 0.00 | 0.00 | 39.87 | 12.97 | 406.15 | 3407.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1080.42 |
F4 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4500.67 | 0.00 | 0.00 | 40.70 | 22.70 | 400.26 | 4702.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -665.13 |
F4 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4449.84 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3414.24 | 0.00 | 433.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -136.22 |
F4 SE APARTMENT | 30-SEP-12:00 | 0.00 | -3832.81 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3475.07 | 0.00 | 145.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -248.11 |
F4 NE APARTMENT | 26-JUL-19:00 | 0.00 | -3702.22 | 0.00 | 0.00 | 140.88 | 103.77 | 547.42 | 1055.67 | 0.00 | 957.05 | 897.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 03-JUN-17:05 | 0.00 | -2548.43 | 0.00 | 0.00 | 141.30 | 87.56 | 588.62 | 1172.20 | 0.00 | 233.56 | 325.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 03-JUN-17:05 | 0.00 | -2539.76 | 0.00 | 0.00 | 141.31 | 87.56 | 588.62 | 1172.53 | 0.00 | 233.59 | 316.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2822.99 | 0.00 | 0.00 | 40.02 | 12.97 | 406.15 | 3409.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1045.22 |
F4 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2821.44 | 0.00 | 0.00 | 39.98 | 12.97 | 406.15 | 3408.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1046.04 |
M SW APARTMENT | 12-OCT-14:30 | 0.00 | -4547.12 | 0.00 | 0.00 | 40.73 | 22.70 | 400.26 | 4700.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -616.61 |
M NW APARTMENT | 03-JUN-16:30 | 0.00 | -4507.36 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3403.49 | 0.00 | 470.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -104.91 |
M SE APARTMENT | 28-SEP-10:15 | 0.00 | -3874.21 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3845.59 | 0.00 | 243.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -680.27 |
M NE APARTMENT | 15-JUN-17:45 | 0.00 | -3782.92 | 0.00 | 0.00 | 141.10 | 87.56 | 588.62 | 1544.74 | 0.00 | 707.35 | 713.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 03-JUN-17:05 | 0.00 | -2599.63 | 0.00 | 0.00 | 141.28 | 87.56 | 588.62 | 1173.09 | 0.00 | 253.46 | 355.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 03-JUN-17:05 | 0.00 | -2590.55 | 0.00 | 0.00 | 141.30 | 87.56 | 588.62 | 1173.42 | 0.00 | 253.48 | 346.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2876.45 | 0.00 | 0.00 | 40.14 | 12.97 | 406.15 | 3409.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -992.08 |
M S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2874.76 | 0.00 | 0.00 | 40.10 | 12.97 | 406.15 | 3408.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -993.08 |
F6 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4528.57 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 4700.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -635.37 |
F6 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4500.96 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3396.58 | 0.00 | 502.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -136.04 |
F6 SE APARTMENT | 28-SEP-10:15 | 0.00 | -3851.57 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3821.03 | 0.00 | 259.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -694.60 |
F6 NE APARTMENT | 15-JUN-17:45 | 0.00 | -3792.40 | 0.00 | 0.00 | 140.95 | 87.56 | 588.62 | 1556.15 | 0.00 | 754.18 | 664.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 15-JUN-18:00 | 0.00 | -2584.40 | 0.00 | 0.00 | 139.03 | 87.56 | 588.62 | 952.18 | 0.00 | 449.60 | 367.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 15-JUN-18:00 | 0.00 | -2576.48 | 0.00 | 0.00 | 139.01 | 87.56 | 588.62 | 952.35 | 0.00 | 449.53 | 359.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2865.28 | 0.00 | 0.00 | 40.24 | 12.97 | 406.15 | 3410.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.94 |
F6 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2863.61 | 0.00 | 0.00 | 40.20 | 12.97 | 406.15 | 3410.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1005.94 |
F7 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4531.25 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 4699.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -631.77 |
F7 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4515.21 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3389.62 | 0.00 | 530.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -142.68 |
F7 SE APARTMENT | 28-SEP-10:15 | 0.00 | -3857.08 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3798.53 | 0.00 | 273.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -680.99 |
F7 NE APARTMENT | 15-JUN-17:45 | 0.00 | -3820.58 | 0.00 | 0.00 | 140.84 | 87.56 | 588.62 | 1564.71 | 0.00 | 795.44 | 643.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 15-JUN-18:00 | 0.00 | -2599.07 | 0.00 | 0.00 | 138.94 | 87.56 | 588.62 | 957.32 | 0.00 | 474.29 | 352.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 15-JUN-18:00 | 0.00 | -2591.23 | 0.00 | 0.00 | 138.93 | 87.56 | 588.62 | 957.49 | 0.00 | 474.22 | 344.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2874.58 | 0.00 | 0.00 | 40.34 | 12.97 | 406.15 | 3411.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -996.61 |
F7 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2872.94 | 0.00 | 0.00 | 40.30 | 12.97 | 406.15 | 3411.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -997.58 |
F8 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4548.39 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 4697.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -613.24 |
F8 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4536.00 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3382.63 | 0.00 | 554.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -139.70 |
F8 SE APARTMENT | 30-AUG-10:30 | 0.00 | -3876.82 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3796.12 | 0.00 | 259.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -644.72 |
F8 NE APARTMENT | 15-JUN-17:45 | 0.00 | -3860.91 | 0.00 | 0.00 | 140.75 | 87.56 | 588.62 | 1571.10 | 0.00 | 832.48 | 640.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 15-JUN-18:00 | 0.00 | -2623.82 | 0.00 | 0.00 | 138.89 | 87.56 | 588.62 | 961.53 | 0.00 | 496.40 | 350.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 15-JUN-18:00 | 0.00 | -2615.67 | 0.00 | 0.00 | 138.88 | 87.56 | 588.62 | 961.70 | 0.00 | 496.32 | 342.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -2897.97 | 0.00 | 0.00 | 40.44 | 12.97 | 406.15 | 3412.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -973.96 |
F8 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -2895.28 | 0.00 | 0.00 | 40.40 | 12.97 | 406.15 | 3411.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -975.97 |
F9 SW APARTMENT | 12-OCT-14:30 | 0.00 | -4676.01 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 4692.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -480.17 |
F9 NW APARTMENT | 03-JUN-16:30 | 0.00 | -4685.04 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3369.79 | 0.00 | 577.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.59 |
F9 SE APARTMENT | 15-AUG-13:00 | 0.00 | -4009.81 | 0.00 | 0.00 | 40.58 | 12.97 | 388.49 | 2334.51 | 0.00 | 1068.19 | 165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 15-JUN-17:45 | 0.00 | -4016.63 | 0.00 | 0.00 | 140.71 | 87.56 | 588.62 | 1568.89 | 0.00 | 866.31 | 764.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 15-JUN-18:00 | 0.00 | -2760.83 | 0.00 | 0.00 | 138.97 | 87.56 | 588.62 | 961.02 | 0.00 | 516.95 | 467.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 15-JUN-18:00 | 0.00 | -2752.80 | 0.00 | 0.00 | 138.96 | 87.56 | 588.62 | 961.20 | 0.00 | 516.87 | 459.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 28-OCT-12:00 | 0.00 | -3011.19 | 0.00 | 0.00 | 40.71 | 12.97 | 406.15 | 3413.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.24 |
F9 S2 APARTMENT | 28-OCT-12:00 | 0.00 | -3010.85 | 0.00 | 0.00 | 40.69 | 12.97 | 406.15 | 3413.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.15 |
T SW APARTMENT | 12-OCT-14:30 | 0.00 | -5724.49 | 0.00 | 0.00 | 40.67 | 22.70 | 400.26 | 4594.64 | 0.00 | 0.00 | 666.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 27-JUL-15:00 | 0.00 | -5557.47 | 0.00 | 0.00 | 40.61 | 22.70 | 400.26 | 3335.21 | 0.00 | 1037.13 | 721.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 15-AUG-13:00 | 0.00 | -4934.84 | 0.00 | 0.00 | 40.58 | 12.97 | 388.49 | 2237.74 | 0.00 | 1108.30 | 1146.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 15-AUG-13:00 | 0.00 | -4789.90 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1866.37 | 0.00 | 1122.47 | 1358.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 26-JUL-16:05 | 0.00 | -3527.03 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1299.73 | 0.00 | 416.22 | 1072.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 26-JUL-14:00 | 0.00 | -3521.06 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1440.16 | 0.00 | 353.46 | 1291.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 28-OCT-12:15 | 0.00 | -3970.71 | 0.00 | 0.00 | 40.63 | 12.97 | 388.49 | 3278.84 | 0.00 | 13.12 | 236.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 28-OCT-12:15 | 0.00 | -3971.98 | 0.00 | 0.00 | 40.61 | 12.97 | 388.49 | 3278.29 | 0.00 | 13.07 | 238.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUL-15:00 | 0.00 | -264264.69 | 0.00 | 0.00 | 3251.80 | 9873.49 | 32370.09 | 177341.71 | 0.00 | 54725.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13298.39 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-JAN-05:00 | 1151.72 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 279.19 | 0.00 | -1594.97 | 0.00 | -268.74 | 0.00 |
G NW APARTMENT | 18-JAN-12:40 | 1349.89 | 0.00 | 0.00 | 0.00 | 46.47 | 12.97 | 406.15 | 373.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1377.05 | -811.53 |
OFFICE | 09-JAN-05:00 | 1082.13 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 131.08 | 0.00 | -1607.90 | 0.00 | -268.74 | 0.00 |
G NE APARTMENT | 18-JAN-12:40 | 1416.69 | 0.00 | 0.00 | 0.00 | 46.50 | 12.97 | 406.15 | 77.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1376.10 | -583.89 |
G N1 APARTMENT | 18-JAN-12:40 | 1325.24 | 0.00 | 0.00 | 0.00 | 46.54 | 12.97 | 406.15 | 44.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1283.96 | -551.31 |
G N2 APARTMENT | 18-JAN-12:40 | 1329.92 | 0.00 | 0.00 | 0.00 | 46.52 | 12.97 | 406.15 | 44.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1284.00 | -555.59 |
G S1 APARTMENT | 09-JAN-05:00 | 501.98 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 224.10 | 0.00 | -996.79 | 0.00 | -162.10 | 0.00 |
G S2 APARTMENT | 16-MAR-13:50 | 528.19 | 0.00 | 0.00 | 0.00 | 47.32 | 12.97 | 382.60 | 144.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.32 | -159.79 |
F2 SW APARTMENT | 09-JAN-05:00 | 1065.96 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 524.89 | 0.00 | -1636.90 | 0.00 | -386.76 | 0.00 |
F2 NW APARTMENT | 18-JAN-12:40 | 1575.66 | 0.00 | 0.00 | 0.00 | 45.71 | 12.97 | 406.15 | 232.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1745.15 | -528.04 |
F2 SE APARTMENT | 09-JAN-05:00 | 1061.01 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 530.39 | 0.00 | -1637.44 | 0.00 | -386.76 | 0.00 |
F2 NE APARTMENT | 18-JAN-12:40 | 1669.37 | 0.00 | 0.00 | 0.00 | 45.74 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.81 | 0.00 | -1740.96 | -367.45 |
F2 N1 APARTMENT | 19-JAN-13:25 | 1553.51 | 0.00 | 0.00 | 0.00 | 46.19 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16.26 | 0.00 | -1462.82 | -522.08 |
F2 N2 APARTMENT | 19-JAN-13:25 | 1561.09 | 0.00 | 0.00 | 0.00 | 46.16 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16.95 | 0.00 | -1462.90 | -528.86 |
F2 S1 APARTMENT | 09-JAN-05:00 | 350.15 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 479.03 | 0.00 | -1028.70 | 0.00 | -233.28 | 0.00 |
F2 S2 APARTMENT | 09-JAN-05:00 | 349.28 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 480.04 | 0.00 | -1028.84 | 0.00 | -233.28 | 0.00 |
F3 SW APARTMENT | 09-JAN-05:00 | 1039.62 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 641.20 | 0.00 | -1655.16 | 0.00 | -458.46 | 0.00 |
F3 NW APARTMENT | 18-JAN-12:40 | 1918.96 | 0.00 | 0.00 | 0.00 | 45.78 | 12.97 | 406.15 | 176.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1972.20 | -588.20 |
F3 SE APARTMENT | 09-JAN-05:00 | 1058.20 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 619.35 | 0.00 | -1651.88 | 0.00 | -458.46 | 0.00 |
F3 NE APARTMENT | 18-JAN-12:40 | 1885.41 | 0.00 | 0.00 | 0.00 | 45.77 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63.72 | 0.00 | -1970.95 | -315.62 |
F3 N1 APARTMENT | 19-JAN-13:25 | 1733.90 | 0.00 | 0.00 | 0.00 | 46.09 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.83 | 0.00 | -1650.39 | -489.23 |
F3 N2 APARTMENT | 19-JAN-13:25 | 1741.28 | 0.00 | 0.00 | 0.00 | 46.06 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.44 | 0.00 | -1650.45 | -495.90 |
F3 S1 APARTMENT | 16-MAR-13:40 | 290.12 | 0.00 | 0.00 | 0.00 | 40.81 | 12.97 | 382.60 | 41.93 | 0.00 | 0.00 | 808.27 | 0.00 | 0.00 | 0.00 | -1576.70 | 0.00 |
F3 S2 APARTMENT | 16-MAR-13:40 | 290.23 | 0.00 | 0.00 | 0.00 | 40.82 | 12.97 | 382.60 | 42.09 | 0.00 | 0.00 | 806.44 | 0.00 | 0.00 | 0.00 | -1575.15 | 0.00 |
F4 SW APARTMENT | 09-JAN-05:00 | 1082.15 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 657.99 | 0.00 | -1659.86 | 0.00 | -513.08 | 0.00 |
F4 NW APARTMENT | 18-JAN-12:40 | 2018.46 | 0.00 | 0.00 | 0.00 | 46.01 | 12.97 | 406.15 | 147.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2155.71 | -475.35 |
F4 SE APARTMENT | 09-JAN-05:00 | 1106.80 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 628.93 | 0.00 | -1655.45 | 0.00 | -513.08 | 0.00 |
F4 NE APARTMENT | 18-JAN-12:40 | 2029.79 | 0.00 | 0.00 | 0.00 | 45.98 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.41 | 0.00 | -2153.96 | -259.51 |
F4 N1 APARTMENT | 18-JAN-12:40 | 1979.51 | 0.00 | 0.00 | 0.00 | 45.41 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.48 | 0.00 | -1983.55 | -383.00 |
F4 N2 APARTMENT | 18-JAN-12:40 | 1996.19 | 0.00 | 0.00 | 0.00 | 45.42 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77.23 | 0.00 | -1983.08 | -400.41 |
F4 S1 APARTMENT | 12-JAN-10:40 | 313.70 | 0.00 | 0.00 | 0.00 | 41.03 | 12.97 | 406.15 | 540.84 | 0.00 | 0.00 | 650.53 | 0.00 | 0.00 | 0.00 | -1965.21 | 0.00 |
F4 S2 APARTMENT | 12-JAN-10:40 | 313.35 | 0.00 | 0.00 | 0.00 | 41.01 | 12.97 | 406.15 | 540.45 | 0.00 | 0.00 | 652.79 | 0.00 | 0.00 | 0.00 | -1966.71 | 0.00 |
M SW APARTMENT | 09-JAN-05:00 | 1127.72 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 660.48 | 0.00 | -1662.72 | 0.00 | -558.29 | 0.00 |
M NW APARTMENT | 18-JAN-12:40 | 2114.86 | 0.00 | 0.00 | 0.00 | 46.18 | 12.97 | 406.15 | 126.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2312.41 | -393.96 |
M SE APARTMENT | 09-JAN-05:00 | 1152.44 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 631.21 | 0.00 | -1658.17 | 0.00 | -558.29 | 0.00 |
M NE APARTMENT | 18-JAN-12:40 | 2126.36 | 0.00 | 0.00 | 0.00 | 46.15 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94.12 | 0.00 | -2310.96 | -186.55 |
M N1 APARTMENT | 18-JAN-12:40 | 2219.22 | 0.00 | 0.00 | 0.00 | 45.52 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87.73 | 0.00 | -2121.01 | -475.12 |
M N2 APARTMENT | 18-JAN-12:40 | 2224.64 | 0.00 | 0.00 | 0.00 | 45.53 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -87.46 | 0.00 | -2120.97 | -480.85 |
M S1 APARTMENT | 12-JAN-10:40 | 341.64 | 0.00 | 0.00 | 0.00 | 41.12 | 12.97 | 406.15 | 516.58 | 0.00 | 0.00 | 721.99 | 0.00 | 0.00 | 0.00 | -2040.44 | 0.00 |
M S2 APARTMENT | 12-JAN-10:40 | 341.22 | 0.00 | 0.00 | 0.00 | 41.11 | 12.97 | 406.15 | 516.31 | 0.00 | 0.00 | 723.61 | 0.00 | 0.00 | 0.00 | -2041.37 | 0.00 |
F6 SW APARTMENT | 09-JAN-05:00 | 1209.95 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 612.02 | 0.00 | -1657.36 | 0.00 | -597.41 | 0.00 |
F6 NW APARTMENT | 18-JAN-12:40 | 2186.41 | 0.00 | 0.00 | 0.00 | 46.56 | 12.97 | 406.15 | 118.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2449.13 | -321.43 |
F6 SE APARTMENT | 09-JAN-05:00 | 1236.50 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 581.11 | 0.00 | -1653.00 | 0.00 | -597.41 | 0.00 |
F6 NE APARTMENT | 18-JAN-12:40 | 2194.22 | 0.00 | 0.00 | 0.00 | 46.55 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -94.54 | 0.00 | -2448.14 | -117.21 |
F6 N1 APARTMENT | 18-JAN-12:40 | 2238.81 | 0.00 | 0.00 | 0.00 | 45.94 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88.39 | 0.00 | -2245.24 | -370.25 |
F6 N2 APARTMENT | 18-JAN-12:40 | 2237.20 | 0.00 | 0.00 | 0.00 | 45.95 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88.08 | 0.00 | -2245.17 | -369.02 |
F6 S1 APARTMENT | 12-JAN-10:45 | 553.48 | 0.00 | 0.00 | 0.00 | 41.57 | 12.97 | 406.15 | 504.03 | 0.00 | 0.00 | 339.14 | 0.00 | 0.00 | 0.00 | -1857.34 | 0.00 |
F6 S2 APARTMENT | 12-JAN-10:45 | 550.20 | 0.00 | 0.00 | 0.00 | 41.55 | 12.97 | 406.15 | 503.76 | 0.00 | 0.00 | 342.89 | 0.00 | 0.00 | 0.00 | -1857.52 | 0.00 |
F7 SW APARTMENT | 12-JAN-10:45 | 1434.96 | 0.00 | 0.00 | 0.00 | 43.29 | 12.97 | 406.15 | 586.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2055.21 | -428.24 |
F7 NW APARTMENT | 18-JAN-12:40 | 2261.92 | 0.00 | 0.00 | 0.00 | 46.83 | 12.97 | 406.15 | 110.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2573.32 | -265.01 |
F7 SE APARTMENT | 12-JAN-10:45 | 1504.57 | 0.00 | 0.00 | 0.00 | 42.96 | 12.97 | 406.15 | 665.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2053.52 | -578.24 |
F7 NE APARTMENT | 18-JAN-12:40 | 2265.13 | 0.00 | 0.00 | 0.00 | 46.84 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96.23 | 0.00 | -2572.62 | -62.24 |
F7 N1 APARTMENT | 18-JAN-12:40 | 2285.73 | 0.00 | 0.00 | 0.00 | 46.22 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.13 | 0.00 | -2358.13 | -302.81 |
F7 N2 APARTMENT | 18-JAN-12:40 | 2280.50 | 0.00 | 0.00 | 0.00 | 46.24 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.81 | 0.00 | -2358.06 | -297.98 |
F7 S1 APARTMENT | 12-JAN-10:45 | 982.52 | 0.00 | 0.00 | 0.00 | 41.91 | 12.97 | 406.15 | 492.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1928.68 | -7.84 |
F7 S2 APARTMENT | 12-JAN-10:45 | 978.65 | 0.00 | 0.00 | 0.00 | 41.90 | 12.97 | 406.15 | 492.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1928.89 | -3.42 |
F8 SW APARTMENT | 12-JAN-10:45 | 1680.69 | 0.00 | 0.00 | 0.00 | 43.61 | 12.97 | 406.15 | 576.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2129.80 | -589.97 |
F8 NW APARTMENT | 18-JAN-12:40 | 2344.74 | 0.00 | 0.00 | 0.00 | 47.03 | 12.97 | 406.15 | 102.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2687.97 | -225.08 |
F8 SE APARTMENT | 12-JAN-10:45 | 1760.27 | 0.00 | 0.00 | 0.00 | 43.29 | 12.97 | 406.15 | 652.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2128.72 | -746.29 |
F8 NE APARTMENT | 18-JAN-12:40 | 2337.79 | 0.00 | 0.00 | 0.00 | 47.06 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -99.03 | 0.00 | -2687.39 | -17.55 |
F8 N1 APARTMENT | 18-JAN-12:40 | 2337.76 | 0.00 | 0.00 | 0.00 | 46.42 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.80 | 0.00 | -2462.31 | -248.19 |
F8 N2 APARTMENT | 18-JAN-12:40 | 2334.35 | 0.00 | 0.00 | 0.00 | 46.44 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.50 | 0.00 | -2462.25 | -245.16 |
F8 S1 APARTMENT | 12-JAN-10:45 | 1373.03 | 0.00 | 0.00 | 0.00 | 42.22 | 12.97 | 406.15 | 483.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1995.02 | -323.02 |
F8 S2 APARTMENT | 12-JAN-10:45 | 1368.28 | 0.00 | 0.00 | 0.00 | 42.21 | 12.97 | 406.15 | 483.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1995.27 | -317.66 |
F9 SW APARTMENT | 12-JAN-10:45 | 1691.75 | 0.00 | 0.00 | 0.00 | 44.14 | 12.97 | 406.15 | 578.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2205.93 | -527.09 |
F9 NW APARTMENT | 18-JAN-12:40 | 2445.36 | 0.00 | 0.00 | 0.00 | 47.23 | 12.97 | 406.15 | 98.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2794.64 | -215.88 |
F9 SE APARTMENT | 12-JAN-10:45 | 1749.26 | 0.00 | 0.00 | 0.00 | 43.82 | 12.97 | 406.15 | 650.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2205.41 | -657.70 |
F9 NE APARTMENT | 18-JAN-12:40 | 2426.33 | 0.00 | 0.00 | 0.00 | 47.26 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 | -99.32 | 0.00 | -2794.32 | 0.00 |
F9 N1 APARTMENT | 18-JAN-12:40 | 2400.61 | 0.00 | 0.00 | 0.00 | 46.62 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93.40 | 0.00 | -2559.54 | -213.41 |
F9 N2 APARTMENT | 18-JAN-12:40 | 2397.80 | 0.00 | 0.00 | 0.00 | 46.63 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93.20 | 0.00 | -2559.49 | -210.87 |
F9 S1 APARTMENT | 12-JAN-10:45 | 1752.22 | 0.00 | 0.00 | 0.00 | 42.84 | 12.97 | 406.15 | 483.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2054.62 | -642.82 |
F9 S2 APARTMENT | 12-JAN-10:45 | 1755.52 | 0.00 | 0.00 | 0.00 | 42.83 | 12.97 | 406.15 | 482.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2054.66 | -645.69 |
T SW APARTMENT | 09-JAN-05:00 | 2028.44 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1566.98 | 0.00 | -719.74 | -174.52 |
T NW APARTMENT | 18-JAN-12:40 | 2629.20 | 0.00 | 0.00 | 0.00 | 47.37 | 12.97 | 406.15 | 105.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2895.41 | -305.95 |
T SE APARTMENT | 09-JAN-05:00 | 2037.77 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1565.77 | 0.00 | -719.74 | -185.06 |
T NE APARTMENT | 18-JAN-12:35 | 2604.62 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.70 | 0.00 | -2895.00 | -85.46 |
T N1 APARTMENT | 18-JAN-12:40 | 2450.67 | 0.00 | 0.00 | 0.00 | 46.90 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.37 | 0.00 | -2651.11 | -182.21 |
T N2 APARTMENT | 18-JAN-12:40 | 2453.83 | 0.00 | 0.00 | 0.00 | 46.89 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.99 | 0.00 | -2651.20 | -184.65 |
T S1 APARTMENT | 12-JAN-10:45 | 1746.97 | 0.00 | 0.00 | 0.00 | 42.68 | 12.97 | 406.15 | 473.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2130.88 | -551.18 |
T S2 APARTMENT | 12-JAN-10:45 | 1720.36 | 0.00 | 0.00 | 0.00 | 42.61 | 12.97 | 406.15 | 471.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2132.36 | -521.55 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JAN-12:40 | 98475.64 | 0.00 | 0.00 | 0.00 | 3474.17 | 8844.29 | 32799.78 | 96973.60 | 0.00 | 0.00 | 0.00 | 0.00 | -2159.86 | 0.00 | -198656.44 | -39751.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Sec1.1A-General InformationData | |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1093.25 |
Number of hours not met | 1102.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.00 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 5.04 | 0.00 | 3.20 | 48692.15 | 0.00 | 0.00 |
Space Cooling | 1286.36 | 91462.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 80.51 | 2606.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46.78 | 2994.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 1005.71 | 31891.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 764.50 | 54400.98 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 4057.46 | 767.70 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 4057.46 |
Natural Gas | 0.00 | 767.70 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4825.16 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 0.64 |
Space Cooling | 164.15 |
Fans-Interior | 128.34 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 41.66 |
Subtotal | 517.77 |
Natural Gas [MJ/m2] | |
Space Heating | 0.41 |
Service Water Heating | 97.56 |
Miscellaneous | 0.00 |
Subtotal | 97.97 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.15 |
Space Heating | 0.17 |
Space Cooling | 26.66 |
Fans-Interior | 20.84 |
Service Water Heating | 15.84 |
Receptacle Equipment | 23.57 |
Miscellaneous | 6.77 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.363453 |
G NW APARTMENT DIRECT AIR | 0.368404 |
OFFICE DIRECT AIR | 0.447435 |
G NE APARTMENT DIRECT AIR | 0.296483 |
G N1 APARTMENT DIRECT AIR | 0.205837 |
G N2 APARTMENT DIRECT AIR | 0.204707 |
G S1 APARTMENT DIRECT AIR | 0.199790 |
G S2 APARTMENT DIRECT AIR | 0.204776 |
F2 SW APARTMENT DIRECT AIR | 0.430435 |
F2 NW APARTMENT DIRECT AIR | 0.436066 |
F2 SE APARTMENT DIRECT AIR | 0.387466 |
F2 NE APARTMENT DIRECT AIR | 0.363827 |
F2 N1 APARTMENT DIRECT AIR | 0.249944 |
F2 N2 APARTMENT DIRECT AIR | 0.249044 |
F2 S1 APARTMENT DIRECT AIR | 0.242369 |
F2 S2 APARTMENT DIRECT AIR | 0.243258 |
F3 SW APARTMENT DIRECT AIR | 0.434271 |
F3 NW APARTMENT DIRECT AIR | 0.440010 |
F3 SE APARTMENT DIRECT AIR | 0.372912 |
F3 NE APARTMENT DIRECT AIR | 0.369983 |
F3 N1 APARTMENT DIRECT AIR | 0.253571 |
F3 N2 APARTMENT DIRECT AIR | 0.252740 |
F3 S1 APARTMENT DIRECT AIR | 0.246314 |
F3 S2 APARTMENT DIRECT AIR | 0.246138 |
F4 SW APARTMENT DIRECT AIR | 0.439506 |
F4 NW APARTMENT DIRECT AIR | 0.445109 |
F4 SE APARTMENT DIRECT AIR | 0.377438 |
F4 NE APARTMENT DIRECT AIR | 0.376517 |
F4 N1 APARTMENT DIRECT AIR | 0.257753 |
F4 N2 APARTMENT DIRECT AIR | 0.256932 |
F4 S1 APARTMENT DIRECT AIR | 0.250666 |
F4 S2 APARTMENT DIRECT AIR | 0.250349 |
M SW APARTMENT DIRECT AIR | 0.446283 |
M NW APARTMENT DIRECT AIR | 0.451843 |
M SE APARTMENT DIRECT AIR | 0.384889 |
M NE APARTMENT DIRECT AIR | 0.384361 |
M N1 APARTMENT DIRECT AIR | 0.263611 |
M N2 APARTMENT DIRECT AIR | 0.262798 |
M S1 APARTMENT DIRECT AIR | 0.256587 |
M S2 APARTMENT DIRECT AIR | 0.256253 |
F6 SW APARTMENT DIRECT AIR | 0.446671 |
F6 NW APARTMENT DIRECT AIR | 0.452031 |
F6 SE APARTMENT DIRECT AIR | 0.386067 |
F6 NE APARTMENT DIRECT AIR | 0.385591 |
F6 N1 APARTMENT DIRECT AIR | 0.263197 |
F6 N2 APARTMENT DIRECT AIR | 0.262394 |
F6 S1 APARTMENT DIRECT AIR | 0.256389 |
F6 S2 APARTMENT DIRECT AIR | 0.256057 |
F7 SW APARTMENT DIRECT AIR | 0.448868 |
F7 NW APARTMENT DIRECT AIR | 0.454144 |
F7 SE APARTMENT DIRECT AIR | 0.388925 |
F7 NE APARTMENT DIRECT AIR | 0.388574 |
F7 N1 APARTMENT DIRECT AIR | 0.264705 |
F7 N2 APARTMENT DIRECT AIR | 0.263909 |
F7 S1 APARTMENT DIRECT AIR | 0.258000 |
F7 S2 APARTMENT DIRECT AIR | 0.257670 |
F8 SW APARTMENT DIRECT AIR | 0.452332 |
F8 NW APARTMENT DIRECT AIR | 0.457515 |
F8 SE APARTMENT DIRECT AIR | 0.392962 |
F8 NE APARTMENT DIRECT AIR | 0.392686 |
F8 N1 APARTMENT DIRECT AIR | 0.267527 |
F8 N2 APARTMENT DIRECT AIR | 0.266740 |
F8 S1 APARTMENT DIRECT AIR | 0.260906 |
F8 S2 APARTMENT DIRECT AIR | 0.260579 |
F9 SW APARTMENT DIRECT AIR | 0.467246 |
F9 NW APARTMENT DIRECT AIR | 0.472651 |
F9 SE APARTMENT DIRECT AIR | 0.407542 |
F9 NE APARTMENT DIRECT AIR | 0.407731 |
F9 N1 APARTMENT DIRECT AIR | 0.280810 |
F9 N2 APARTMENT DIRECT AIR | 0.280036 |
F9 S1 APARTMENT DIRECT AIR | 0.273408 |
F9 S2 APARTMENT DIRECT AIR | 0.273119 |
T SW APARTMENT DIRECT AIR | 0.561353 |
T NW APARTMENT DIRECT AIR | 0.564995 |
T SE APARTMENT DIRECT AIR | 0.493880 |
T NE APARTMENT DIRECT AIR | 0.490216 |
T N1 APARTMENT DIRECT AIR | 0.360413 |
T N2 APARTMENT DIRECT AIR | 0.359362 |
T S1 APARTMENT DIRECT AIR | 0.362646 |
T S2 APARTMENT DIRECT AIR | 0.362403 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.363453 |
AIRLOOP G NW MAIN BRANCH | 0.368404 |
AIRLOOP OFFICE MAIN BRANCH | 0.447435 |
AIRLOOP G NE MAIN BRANCH | 0.296483 |
AIRLOOP G N1 MAIN BRANCH | 0.205837 |
AIRLOOP G N2 MAIN BRANCH | 0.204707 |
AIRLOOP G S1 MAIN BRANCH | 0.199790 |
AIRLOOP G S2 MAIN BRANCH | 0.204776 |
AIRLOOP F2 SW MAIN BRANCH | 0.430435 |
AIRLOOP F2 NW MAIN BRANCH | 0.436066 |
AIRLOOP F2 SE MAIN BRANCH | 0.387466 |
AIRLOOP F2 NE MAIN BRANCH | 0.363827 |
AIRLOOP F2 N1 MAIN BRANCH | 0.249944 |
AIRLOOP F2 N2 MAIN BRANCH | 0.249044 |
AIRLOOP F2 S1 MAIN BRANCH | 0.242369 |
AIRLOOP F2 S2 MAIN BRANCH | 0.243258 |
AIRLOOP F3 SW MAIN BRANCH | 0.434271 |
AIRLOOP F3 NW MAIN BRANCH | 0.440010 |
AIRLOOP F3 SE MAIN BRANCH | 0.372912 |
AIRLOOP F3 NE MAIN BRANCH | 0.369983 |
AIRLOOP F3 N1 MAIN BRANCH | 0.253571 |
AIRLOOP F3 N2 MAIN BRANCH | 0.252740 |
AIRLOOP F3 S1 MAIN BRANCH | 0.246314 |
AIRLOOP F3 S2 MAIN BRANCH | 0.246138 |
AIRLOOP F4 SW MAIN BRANCH | 0.439506 |
AIRLOOP F4 NW MAIN BRANCH | 0.445109 |
AIRLOOP F4 SE MAIN BRANCH | 0.377438 |
AIRLOOP F4 NE MAIN BRANCH | 0.376517 |
AIRLOOP F4 N1 MAIN BRANCH | 0.257753 |
AIRLOOP F4 N2 MAIN BRANCH | 0.256932 |
AIRLOOP F4 S1 MAIN BRANCH | 0.250666 |
AIRLOOP F4 S2 MAIN BRANCH | 0.250349 |
AIRLOOP M SW MAIN BRANCH | 0.446283 |
AIRLOOP M NW MAIN BRANCH | 0.451843 |
AIRLOOP M SE MAIN BRANCH | 0.384889 |
AIRLOOP M NE MAIN BRANCH | 0.384361 |
AIRLOOP M N1 MAIN BRANCH | 0.263611 |
AIRLOOP M N2 MAIN BRANCH | 0.262798 |
AIRLOOP M S1 MAIN BRANCH | 0.256587 |
AIRLOOP M S2 MAIN BRANCH | 0.256253 |
AIRLOOP F6 SW MAIN BRANCH | 0.446671 |
AIRLOOP F6 NW MAIN BRANCH | 0.452031 |
AIRLOOP F6 SE MAIN BRANCH | 0.386067 |
AIRLOOP F6 NE MAIN BRANCH | 0.385591 |
AIRLOOP F6 N1 MAIN BRANCH | 0.263197 |
AIRLOOP F6 N2 MAIN BRANCH | 0.262394 |
AIRLOOP F6 S1 MAIN BRANCH | 0.256389 |
AIRLOOP F6 S2 MAIN BRANCH | 0.256057 |
AIRLOOP F7 SW MAIN BRANCH | 0.448868 |
AIRLOOP F7 NW MAIN BRANCH | 0.454144 |
AIRLOOP F7 SE MAIN BRANCH | 0.388925 |
AIRLOOP F7 NE MAIN BRANCH | 0.388574 |
AIRLOOP F7 N1 MAIN BRANCH | 0.264705 |
AIRLOOP F7 N2 MAIN BRANCH | 0.263909 |
AIRLOOP F7 S1 MAIN BRANCH | 0.258000 |
AIRLOOP F7 S2 MAIN BRANCH | 0.257670 |
AIRLOOP F8 SW MAIN BRANCH | 0.452332 |
AIRLOOP F8 NW MAIN BRANCH | 0.457515 |
AIRLOOP F8 SE MAIN BRANCH | 0.392962 |
AIRLOOP F8 NE MAIN BRANCH | 0.392686 |
AIRLOOP F8 N1 MAIN BRANCH | 0.267527 |
AIRLOOP F8 N2 MAIN BRANCH | 0.266740 |
AIRLOOP F8 S1 MAIN BRANCH | 0.260906 |
AIRLOOP F8 S2 MAIN BRANCH | 0.260579 |
AIRLOOP F9 SW MAIN BRANCH | 0.467246 |
AIRLOOP F9 NW MAIN BRANCH | 0.472651 |
AIRLOOP F9 SE MAIN BRANCH | 0.407542 |
AIRLOOP F9 NE MAIN BRANCH | 0.407731 |
AIRLOOP F9 N1 MAIN BRANCH | 0.280810 |
AIRLOOP F9 N2 MAIN BRANCH | 0.280036 |
AIRLOOP F9 S1 MAIN BRANCH | 0.273408 |
AIRLOOP F9 S2 MAIN BRANCH | 0.273119 |
AIRLOOP T SW MAIN BRANCH | 0.561353 |
AIRLOOP T NW MAIN BRANCH | 0.564995 |
AIRLOOP T SE MAIN BRANCH | 0.493880 |
AIRLOOP T NE MAIN BRANCH | 0.490216 |
AIRLOOP T N1 MAIN BRANCH | 0.360413 |
AIRLOOP T N2 MAIN BRANCH | 0.359362 |
AIRLOOP T S1 MAIN BRANCH | 0.362646 |
AIRLOOP T S2 MAIN BRANCH | 0.362403 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.363453 |
AIRLOOP G NW | 0.368404 |
AIRLOOP OFFICE | 0.447435 |
AIRLOOP G NE | 0.296483 |
AIRLOOP G N1 | 0.205837 |
AIRLOOP G N2 | 0.204707 |
AIRLOOP G S1 | 0.199790 |
AIRLOOP G S2 | 0.204776 |
AIRLOOP F2 SW | 0.430435 |
AIRLOOP F2 NW | 0.436066 |
AIRLOOP F2 SE | 0.387466 |
AIRLOOP F2 NE | 0.363827 |
AIRLOOP F2 N1 | 0.249944 |
AIRLOOP F2 N2 | 0.249044 |
AIRLOOP F2 S1 | 0.242369 |
AIRLOOP F2 S2 | 0.243258 |
AIRLOOP F3 SW | 0.434271 |
AIRLOOP F3 NW | 0.440010 |
AIRLOOP F3 SE | 0.372912 |
AIRLOOP F3 NE | 0.369983 |
AIRLOOP F3 N1 | 0.253571 |
AIRLOOP F3 N2 | 0.252740 |
AIRLOOP F3 S1 | 0.246314 |
AIRLOOP F3 S2 | 0.246138 |
AIRLOOP F4 SW | 0.439506 |
AIRLOOP F4 NW | 0.445109 |
AIRLOOP F4 SE | 0.377438 |
AIRLOOP F4 NE | 0.376517 |
AIRLOOP F4 N1 | 0.257753 |
AIRLOOP F4 N2 | 0.256932 |
AIRLOOP F4 S1 | 0.250666 |
AIRLOOP F4 S2 | 0.250349 |
AIRLOOP M SW | 0.446283 |
AIRLOOP M NW | 0.451843 |
AIRLOOP M SE | 0.384889 |
AIRLOOP M NE | 0.384361 |
AIRLOOP M N1 | 0.263611 |
AIRLOOP M N2 | 0.262798 |
AIRLOOP M S1 | 0.256587 |
AIRLOOP M S2 | 0.256253 |
AIRLOOP F6 SW | 0.446671 |
AIRLOOP F6 NW | 0.452031 |
AIRLOOP F6 SE | 0.386067 |
AIRLOOP F6 NE | 0.385591 |
AIRLOOP F6 N1 | 0.263197 |
AIRLOOP F6 N2 | 0.262394 |
AIRLOOP F6 S1 | 0.256389 |
AIRLOOP F6 S2 | 0.256057 |
AIRLOOP F7 SW | 0.448868 |
AIRLOOP F7 NW | 0.454144 |
AIRLOOP F7 SE | 0.388925 |
AIRLOOP F7 NE | 0.388574 |
AIRLOOP F7 N1 | 0.264705 |
AIRLOOP F7 N2 | 0.263909 |
AIRLOOP F7 S1 | 0.258000 |
AIRLOOP F7 S2 | 0.257670 |
AIRLOOP F8 SW | 0.452332 |
AIRLOOP F8 NW | 0.457515 |
AIRLOOP F8 SE | 0.392962 |
AIRLOOP F8 NE | 0.392686 |
AIRLOOP F8 N1 | 0.267527 |
AIRLOOP F8 N2 | 0.266740 |
AIRLOOP F8 S1 | 0.260906 |
AIRLOOP F8 S2 | 0.260579 |
AIRLOOP F9 SW | 0.467246 |
AIRLOOP F9 NW | 0.472651 |
AIRLOOP F9 SE | 0.407542 |
AIRLOOP F9 NE | 0.407731 |
AIRLOOP F9 N1 | 0.280810 |
AIRLOOP F9 N2 | 0.280036 |
AIRLOOP F9 S1 | 0.273408 |
AIRLOOP F9 S2 | 0.273119 |
AIRLOOP T SW | 0.561353 |
AIRLOOP T NW | 0.564995 |
AIRLOOP T SE | 0.493880 |
AIRLOOP T NE | 0.490216 |
AIRLOOP T N1 | 0.360413 |
AIRLOOP T N2 | 0.359362 |
AIRLOOP T S1 | 0.362646 |
AIRLOOP T S2 | 0.362403 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.363453 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.368404 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.447435 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.296483 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.205837 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.204707 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.199790 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.204776 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.430435 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.436066 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.387466 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.363827 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.249944 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.249044 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.242369 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.243258 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.434271 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.440010 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.372912 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.369983 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.253571 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.252740 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.246314 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.246138 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.439506 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.445109 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.377438 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.376517 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.257753 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.256932 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.250666 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.250349 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.446283 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.451843 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.384889 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.384361 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.263611 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.262798 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.256587 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.256253 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.446671 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.452031 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.386067 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.385591 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.263197 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.262394 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.256389 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.256057 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.448868 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.454144 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.388925 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.388574 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.264705 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.263909 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.258000 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.257670 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.452332 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.457515 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.392962 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.392686 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.267527 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.266740 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.260906 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.260579 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.467246 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.472651 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.407542 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.407731 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.280810 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.280036 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.273408 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.273119 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.561353 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.564995 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.493880 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.490216 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.360413 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.359362 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.362646 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.362403 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.363453 | 4960.28 | 3649.21 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.368404 | 5011.98 | 3691.25 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.447435 | 6204.90 | 4544.14 | 0.000136 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.296483 | 4077.61 | 3004.47 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.205837 | 2900.22 | 2125.27 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.204707 | 2885.24 | 2114.29 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.199790 | 2857.63 | 2081.42 | 0.000062 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.204776 | 2929.33 | 2132.08 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.430435 | 5783.47 | 4281.42 | 0.000126 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.436066 | 5843.66 | 4329.77 | 0.000128 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.387466 | 5230.93 | 3874.19 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.363827 | 4906.36 | 3641.30 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.249944 | 3434.15 | 2538.73 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.249044 | 3422.22 | 2530.02 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.242369 | 3385.29 | 2487.01 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.243258 | 3397.10 | 2495.63 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.434271 | 5795.32 | 4310.02 | 0.000127 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.440010 | 5856.62 | 4359.33 | 0.000128 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.372912 | 5000.20 | 3725.63 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.369983 | 4949.94 | 3692.58 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.253571 | 3473.65 | 2575.25 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.252740 | 3462.67 | 2567.22 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.246314 | 3415.42 | 2520.51 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.246138 | 3413.14 | 2518.82 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.439506 | 5835.46 | 4354.21 | 0.000127 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.445109 | 5894.74 | 4402.16 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.377438 | 5031.69 | 3763.22 | 0.000110 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.376517 | 5007.98 | 3749.53 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.257753 | 3512.23 | 2612.14 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.256932 | 3501.40 | 2604.20 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.250666 | 3456.41 | 2559.14 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.250349 | 3452.27 | 2556.07 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.446283 | 5901.32 | 4414.42 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.451843 | 5959.85 | 4461.90 | 0.000130 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.384889 | 5106.98 | 3830.13 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.384361 | 5088.47 | 3820.22 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.263611 | 3575.97 | 2665.85 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.262798 | 3565.26 | 2658.00 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.256587 | 3521.08 | 2613.55 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.256253 | 3516.72 | 2610.34 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.446671 | 5886.14 | 4413.82 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.452031 | 5941.86 | 4459.34 | 0.000130 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.386067 | 5102.82 | 3837.30 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.385591 | 5085.01 | 3827.89 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.263197 | 3558.82 | 2659.37 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.262394 | 3548.25 | 2651.62 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.256389 | 3506.91 | 2609.19 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.256057 | 3502.58 | 2605.99 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.448868 | 5897.33 | 4431.18 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.454144 | 5951.82 | 4475.86 | 0.000130 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.388925 | 5123.21 | 3861.16 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.388574 | 5107.05 | 3852.95 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.264705 | 3568.47 | 2671.77 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.263909 | 3558.00 | 2664.10 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.258000 | 3518.01 | 2622.62 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.257670 | 3513.71 | 2619.44 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.452332 | 5927.09 | 4461.13 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.457515 | 5980.22 | 4504.88 | 0.000131 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.392962 | 5160.89 | 3896.76 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.392686 | 5145.73 | 3889.27 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.267527 | 3596.50 | 2697.09 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.266740 | 3586.14 | 2689.49 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.260906 | 3547.20 | 2648.79 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.260579 | 3542.95 | 2645.63 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.467246 | 6109.35 | 4601.57 | 0.000133 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.472651 | 6165.32 | 4647.42 | 0.000135 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.407542 | 5338.69 | 4034.11 | 0.000117 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.407731 | 5329.68 | 4031.08 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.280810 | 3763.14 | 2823.51 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.280036 | 3752.96 | 2816.05 | 0.000082 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.273408 | 3703.47 | 2767.80 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.273119 | 3699.71 | 2765.02 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.561353 | 7345.22 | 5506.94 | 0.000160 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.564995 | 7387.88 | 5539.54 | 0.000161 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.493880 | 6464.48 | 4862.38 | 0.000141 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.490216 | 6416.11 | 4827.12 | 0.000140 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.360413 | 4844.30 | 3605.92 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.359362 | 4836.14 | 3598.17 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.362646 | 4879.56 | 3629.84 | 0.000107 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.362403 | 4876.40 | 3627.51 | 0.000107 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.363453 | 0.363453 | 0.363453 | 0.363453 | 4960.28 | 4960.28 | 1821.96 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.368404 | 0.368404 | 0.368404 | 0.368404 | 5011.98 | 5011.98 | 1814.55 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.447435 | 0.447435 | 0.447435 | 0.447435 | 6204.90 | 6204.90 | 2344.74 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.296483 | 0.296483 | 0.296483 | 0.296483 | 4077.61 | 4077.61 | 1819.30 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.205837 | 0.205837 | 0.205837 | 0.205837 | 2900.22 | 2900.22 | 1255.00 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.204707 | 0.204707 | 0.204707 | 0.204707 | 2885.24 | 2885.24 | 1255.12 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.199790 | 0.199790 | 0.199790 | 0.199790 | 2857.63 | 2857.63 | 1258.86 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.204776 | 0.204776 | 0.204776 | 0.204776 | 2929.33 | 2929.33 | 1264.85 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.430435 | 0.430435 | 0.430435 | 0.430435 | 5783.47 | 5783.47 | 1905.06 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.436066 | 0.436066 | 0.436066 | 0.436066 | 5843.66 | 5843.66 | 1894.88 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.387466 | 0.387466 | 0.387466 | 0.387466 | 5230.93 | 5230.93 | 1929.22 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.363827 | 0.363827 | 0.363827 | 0.363827 | 4906.36 | 4906.36 | 1900.78 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.249944 | 0.249944 | 0.249944 | 0.249944 | 3434.15 | 3434.15 | 1211.26 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.249044 | 0.249044 | 0.249044 | 0.249044 | 3422.22 | 3422.22 | 1211.41 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.242369 | 0.242369 | 0.242369 | 0.242369 | 3385.29 | 3385.29 | 1223.15 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.243258 | 0.243258 | 0.243258 | 0.243258 | 3397.10 | 3397.10 | 1224.53 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.434271 | 0.434271 | 0.434271 | 0.434271 | 5795.32 | 5795.32 | 1891.76 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.440010 | 0.440010 | 0.440010 | 0.440010 | 5856.62 | 5856.62 | 1882.53 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.372912 | 0.372912 | 0.372912 | 0.372912 | 5000.20 | 5000.20 | 1899.55 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.369983 | 0.369983 | 0.369983 | 0.369983 | 4949.94 | 4949.94 | 1888.29 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.253571 | 0.253571 | 0.253571 | 0.253571 | 3473.65 | 3473.65 | 1184.54 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.252740 | 0.252740 | 0.252740 | 0.252740 | 3462.67 | 3462.67 | 1184.69 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.246314 | 0.246314 | 0.246314 | 0.246314 | 3415.42 | 3415.42 | 1193.40 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.246138 | 0.246138 | 0.246138 | 0.246138 | 3413.14 | 3413.14 | 1193.74 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.439506 | 0.439506 | 0.439506 | 0.439506 | 5835.46 | 5835.46 | 1905.30 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.445109 | 0.445109 | 0.445109 | 0.445109 | 5894.74 | 5894.74 | 1896.88 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.377438 | 0.377438 | 0.377438 | 0.377438 | 5031.69 | 5031.69 | 1911.01 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.376517 | 0.376517 | 0.376517 | 0.376517 | 5007.98 | 5007.98 | 1902.36 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.257753 | 0.257753 | 0.257753 | 0.257753 | 3512.23 | 3512.23 | 1186.47 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.256932 | 0.256932 | 0.256932 | 0.256932 | 3501.40 | 3501.40 | 1186.61 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.250666 | 0.250666 | 0.250666 | 0.250666 | 3456.41 | 3456.41 | 1194.23 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.250349 | 0.250349 | 0.250349 | 0.250349 | 3452.27 | 3452.27 | 1194.40 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.446283 | 0.446283 | 0.446283 | 0.446283 | 5901.32 | 5901.32 | 1899.76 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.451843 | 0.451843 | 0.451843 | 0.451843 | 5959.85 | 5959.85 | 1890.92 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.384889 | 0.384889 | 0.384889 | 0.384889 | 5106.98 | 5106.98 | 1904.94 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.384361 | 0.384361 | 0.384361 | 0.384361 | 5088.47 | 5088.47 | 1896.07 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.263611 | 0.263611 | 0.263611 | 0.263611 | 3575.97 | 3575.97 | 1172.40 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.262798 | 0.262798 | 0.262798 | 0.262798 | 3565.26 | 3565.26 | 1172.53 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.256587 | 0.256587 | 0.256587 | 0.256587 | 3521.08 | 3521.08 | 1180.47 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.256253 | 0.256253 | 0.256253 | 0.256253 | 3516.72 | 3516.72 | 1180.61 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.446671 | 0.446671 | 0.446671 | 0.446671 | 5886.14 | 5886.14 | 1954.50 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.452031 | 0.452031 | 0.452031 | 0.452031 | 5941.86 | 5941.86 | 1947.05 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.386067 | 0.386067 | 0.386067 | 0.386067 | 5102.82 | 5102.82 | 1959.33 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.385591 | 0.385591 | 0.385591 | 0.385591 | 5085.01 | 5085.01 | 1951.87 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.263197 | 0.263197 | 0.263197 | 0.263197 | 3558.82 | 3558.82 | 1217.35 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.262394 | 0.262394 | 0.262394 | 0.262394 | 3548.25 | 3548.25 | 1217.47 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.256389 | 0.256389 | 0.256389 | 0.256389 | 3506.91 | 3506.91 | 1224.00 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.256057 | 0.256057 | 0.256057 | 0.256057 | 3502.58 | 3502.58 | 1224.13 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.448868 | 0.448868 | 0.448868 | 0.448868 | 5897.33 | 5897.33 | 1986.04 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.454144 | 0.454144 | 0.454144 | 0.454144 | 5951.82 | 5951.82 | 1978.90 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.388925 | 0.388925 | 0.388925 | 0.388925 | 5123.21 | 5123.21 | 1990.53 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.388574 | 0.388574 | 0.388574 | 0.388574 | 5107.05 | 5107.05 | 1983.38 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.264705 | 0.264705 | 0.264705 | 0.264705 | 3568.47 | 3568.47 | 1241.11 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.263909 | 0.263909 | 0.263909 | 0.263909 | 3558.00 | 3558.00 | 1241.22 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.258000 | 0.258000 | 0.258000 | 0.258000 | 3518.01 | 3518.01 | 1247.42 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.257670 | 0.257670 | 0.257670 | 0.257670 | 3513.71 | 3513.71 | 1247.54 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.452332 | 0.452332 | 0.452332 | 0.452332 | 5927.09 | 5927.09 | 2019.28 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.457515 | 0.457515 | 0.457515 | 0.457515 | 5980.22 | 5980.22 | 2012.20 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.392962 | 0.392962 | 0.392962 | 0.392962 | 5160.89 | 5160.89 | 2023.44 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.392686 | 0.392686 | 0.392686 | 0.392686 | 5145.73 | 5145.73 | 2016.35 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.267527 | 0.267527 | 0.267527 | 0.267527 | 3596.50 | 3596.50 | 1267.48 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.266740 | 0.266740 | 0.266740 | 0.266740 | 3586.14 | 3586.14 | 1267.58 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.260906 | 0.260906 | 0.260906 | 0.260906 | 3547.20 | 3547.20 | 1273.71 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.260579 | 0.260579 | 0.260579 | 0.260579 | 3542.95 | 3542.95 | 1273.81 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.467246 | 0.467246 | 0.467246 | 0.467246 | 6109.35 | 6109.35 | 2136.18 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.472651 | 0.472651 | 0.472651 | 0.472651 | 6165.32 | 6165.32 | 2126.69 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.407542 | 0.407542 | 0.407542 | 0.407542 | 5338.69 | 5338.69 | 2140.04 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.407731 | 0.407731 | 0.407731 | 0.407731 | 5329.68 | 5329.68 | 2130.54 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.280810 | 0.280810 | 0.280810 | 0.280810 | 3763.14 | 3763.14 | 1368.85 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.280036 | 0.280036 | 0.280036 | 0.280036 | 3752.96 | 3752.96 | 1368.95 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.273408 | 0.273408 | 0.273408 | 0.273408 | 3703.47 | 3703.47 | 1377.22 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.273119 | 0.273119 | 0.273119 | 0.273119 | 3699.71 | 3699.71 | 1377.31 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.561353 | 0.561353 | 0.561353 | 0.561353 | 7345.22 | 7345.22 | 2456.54 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.564995 | 0.564995 | 0.564995 | 0.564995 | 7387.88 | 7387.88 | 2453.47 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.493880 | 0.493880 | 0.493880 | 0.493880 | 6464.48 | 6464.48 | 2459.78 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.490216 | 0.490216 | 0.490216 | 0.490216 | 6416.11 | 6416.11 | 2456.71 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.360413 | 0.360413 | 0.360413 | 0.360413 | 4844.30 | 4844.30 | 1748.22 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.359362 | 0.359362 | 0.359362 | 0.359362 | 4836.14 | 4836.14 | 1748.31 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.362646 | 0.362646 | 0.362646 | 0.362646 | 4879.56 | 4879.56 | 1748.72 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.362403 | 0.362403 | 0.362403 | 0.362403 | 4876.40 | 4876.40 | 1748.82 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.363453 |
AIRLOOP G NW SUPPLY FAN | 0.368404 |
AIRLOOP OFFICE SUPPLY FAN | 0.447435 |
AIRLOOP G NE SUPPLY FAN | 0.296483 |
AIRLOOP G N1 SUPPLY FAN | 0.205837 |
AIRLOOP G N2 SUPPLY FAN | 0.204707 |
AIRLOOP G S1 SUPPLY FAN | 0.199790 |
AIRLOOP G S2 SUPPLY FAN | 0.204776 |
AIRLOOP F2 SW SUPPLY FAN | 0.430435 |
AIRLOOP F2 NW SUPPLY FAN | 0.436066 |
AIRLOOP F2 SE SUPPLY FAN | 0.387466 |
AIRLOOP F2 NE SUPPLY FAN | 0.363827 |
AIRLOOP F2 N1 SUPPLY FAN | 0.249944 |
AIRLOOP F2 N2 SUPPLY FAN | 0.249044 |
AIRLOOP F2 S1 SUPPLY FAN | 0.242369 |
AIRLOOP F2 S2 SUPPLY FAN | 0.243258 |
AIRLOOP F3 SW SUPPLY FAN | 0.434271 |
AIRLOOP F3 NW SUPPLY FAN | 0.440010 |
AIRLOOP F3 SE SUPPLY FAN | 0.372912 |
AIRLOOP F3 NE SUPPLY FAN | 0.369983 |
AIRLOOP F3 N1 SUPPLY FAN | 0.253571 |
AIRLOOP F3 N2 SUPPLY FAN | 0.252740 |
AIRLOOP F3 S1 SUPPLY FAN | 0.246314 |
AIRLOOP F3 S2 SUPPLY FAN | 0.246138 |
AIRLOOP F4 SW SUPPLY FAN | 0.439506 |
AIRLOOP F4 NW SUPPLY FAN | 0.445109 |
AIRLOOP F4 SE SUPPLY FAN | 0.377438 |
AIRLOOP F4 NE SUPPLY FAN | 0.376517 |
AIRLOOP F4 N1 SUPPLY FAN | 0.257753 |
AIRLOOP F4 N2 SUPPLY FAN | 0.256932 |
AIRLOOP F4 S1 SUPPLY FAN | 0.250666 |
AIRLOOP F4 S2 SUPPLY FAN | 0.250349 |
AIRLOOP M SW SUPPLY FAN | 0.446283 |
AIRLOOP M NW SUPPLY FAN | 0.451843 |
AIRLOOP M SE SUPPLY FAN | 0.384889 |
AIRLOOP M NE SUPPLY FAN | 0.384361 |
AIRLOOP M N1 SUPPLY FAN | 0.263611 |
AIRLOOP M N2 SUPPLY FAN | 0.262798 |
AIRLOOP M S1 SUPPLY FAN | 0.256587 |
AIRLOOP M S2 SUPPLY FAN | 0.256253 |
AIRLOOP F6 SW SUPPLY FAN | 0.446671 |
AIRLOOP F6 NW SUPPLY FAN | 0.452031 |
AIRLOOP F6 SE SUPPLY FAN | 0.386067 |
AIRLOOP F6 NE SUPPLY FAN | 0.385591 |
AIRLOOP F6 N1 SUPPLY FAN | 0.263197 |
AIRLOOP F6 N2 SUPPLY FAN | 0.262394 |
AIRLOOP F6 S1 SUPPLY FAN | 0.256389 |
AIRLOOP F6 S2 SUPPLY FAN | 0.256057 |
AIRLOOP F7 SW SUPPLY FAN | 0.448868 |
AIRLOOP F7 NW SUPPLY FAN | 0.454144 |
AIRLOOP F7 SE SUPPLY FAN | 0.388925 |
AIRLOOP F7 NE SUPPLY FAN | 0.388574 |
AIRLOOP F7 N1 SUPPLY FAN | 0.264705 |
AIRLOOP F7 N2 SUPPLY FAN | 0.263909 |
AIRLOOP F7 S1 SUPPLY FAN | 0.258000 |
AIRLOOP F7 S2 SUPPLY FAN | 0.257670 |
AIRLOOP F8 SW SUPPLY FAN | 0.452332 |
AIRLOOP F8 NW SUPPLY FAN | 0.457515 |
AIRLOOP F8 SE SUPPLY FAN | 0.392962 |
AIRLOOP F8 NE SUPPLY FAN | 0.392686 |
AIRLOOP F8 N1 SUPPLY FAN | 0.267527 |
AIRLOOP F8 N2 SUPPLY FAN | 0.266740 |
AIRLOOP F8 S1 SUPPLY FAN | 0.260906 |
AIRLOOP F8 S2 SUPPLY FAN | 0.260579 |
AIRLOOP F9 SW SUPPLY FAN | 0.467246 |
AIRLOOP F9 NW SUPPLY FAN | 0.472651 |
AIRLOOP F9 SE SUPPLY FAN | 0.407542 |
AIRLOOP F9 NE SUPPLY FAN | 0.407731 |
AIRLOOP F9 N1 SUPPLY FAN | 0.280810 |
AIRLOOP F9 N2 SUPPLY FAN | 0.280036 |
AIRLOOP F9 S1 SUPPLY FAN | 0.273408 |
AIRLOOP F9 S2 SUPPLY FAN | 0.273119 |
AIRLOOP T SW SUPPLY FAN | 0.561353 |
AIRLOOP T NW SUPPLY FAN | 0.564995 |
AIRLOOP T SE SUPPLY FAN | 0.493880 |
AIRLOOP T NE SUPPLY FAN | 0.490216 |
AIRLOOP T N1 SUPPLY FAN | 0.360413 |
AIRLOOP T N2 SUPPLY FAN | 0.359362 |
AIRLOOP T S1 SUPPLY FAN | 0.362646 |
AIRLOOP T S2 SUPPLY FAN | 0.362403 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.363453 | 4960.28 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.368404 | 5011.98 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.447435 | 6204.90 | 0.000136 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.296483 | 4077.61 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.205837 | 2900.22 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.204707 | 2885.24 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.199790 | 2857.63 | 0.000062 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.204776 | 2929.33 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.430435 | 5783.47 | 0.000126 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.436066 | 5843.66 | 0.000128 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.387466 | 5230.93 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.363827 | 4906.36 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.249944 | 3434.15 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.249044 | 3422.22 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.242369 | 3385.29 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.243258 | 3397.10 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.434271 | 5795.32 | 0.000127 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.440010 | 5856.62 | 0.000128 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.372912 | 5000.20 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.369983 | 4949.94 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.253571 | 3473.65 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.252740 | 3462.67 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.246314 | 3415.42 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.246138 | 3413.14 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.439506 | 5835.46 | 0.000127 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.445109 | 5894.74 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.377438 | 5031.69 | 0.000110 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.376517 | 5007.98 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.257753 | 3512.23 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.256932 | 3501.40 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.250666 | 3456.41 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.250349 | 3452.27 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.446283 | 5901.32 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.451843 | 5959.85 | 0.000130 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.384889 | 5106.98 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.384361 | 5088.47 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.263611 | 3575.97 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.262798 | 3565.26 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.256587 | 3521.08 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.256253 | 3516.72 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.446671 | 5886.14 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.452031 | 5941.86 | 0.000130 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.386067 | 5102.82 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.385591 | 5085.01 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.263197 | 3558.82 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.262394 | 3548.25 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.256389 | 3506.91 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.256057 | 3502.58 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.448868 | 5897.33 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.454144 | 5951.82 | 0.000130 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.388925 | 5123.21 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.388574 | 5107.05 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.264705 | 3568.47 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.263909 | 3558.00 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.258000 | 3518.01 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.257670 | 3513.71 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.452332 | 5927.09 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.457515 | 5980.22 | 0.000131 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.392962 | 5160.89 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.392686 | 5145.73 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.267527 | 3596.50 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.266740 | 3586.14 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.260906 | 3547.20 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.260579 | 3542.95 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.467246 | 6109.35 | 0.000133 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.472651 | 6165.32 | 0.000135 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.407542 | 5338.69 | 0.000117 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.407731 | 5329.68 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.280810 | 3763.14 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.280036 | 3752.96 | 0.000082 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.273408 | 3703.47 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.273119 | 3699.71 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.561353 | 7345.22 | 0.000160 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.564995 | 7387.88 | 0.000161 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.493880 | 6464.48 | 0.000141 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.490216 | 6416.11 | 0.000140 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.360413 | 4844.30 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.359362 | 4836.14 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.362646 | 4879.56 | 0.000107 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.362403 | 4876.40 | 0.000107 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 1821.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 1814.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2344.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 1819.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1255.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1255.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1258.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1264.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 1905.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 1894.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 1929.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 1900.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1211.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1211.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1223.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1224.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1891.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1882.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1899.55 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1888.29 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1184.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1184.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1193.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1193.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1905.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1896.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1911.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1902.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1186.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1186.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1194.23 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1194.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1899.76 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1890.92 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1904.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1896.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1172.40 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1172.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1180.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1180.61 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 1954.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 1947.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 1959.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 1951.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1217.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1217.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1224.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1224.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 1986.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 1978.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 1990.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 1983.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1241.11 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1241.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1247.42 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1247.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 2019.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 2012.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 2023.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 2016.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1267.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1267.58 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1273.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1273.81 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 2136.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 2126.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 2140.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 2130.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1368.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1368.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1377.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1377.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2456.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2453.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2459.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2456.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 1748.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 1748.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 1748.72 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 1748.82 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.008045 | 9.05 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.008045 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.008045 | 3883.78 | 11.00 | 11197.00 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.008045 | 2569.22 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 14.02 |
February | 23.65 | 16.67 |
March | 24.01 | 20.28 |
April | 24.31 | 25.86 |
May | 24.40 | 32.05 |
June | 24.42 | 35.24 |
July | 24.45 | 36.21 |
August | 24.45 | 36.44 |
September | 24.43 | 33.05 |
October | 24.37 | 27.59 |
November | 24.26 | 21.57 |
December | 23.34 | 14.93 |
Annual Sum or Average | 24.12 | 26.21 |
Minimum of Months | 23.32 | 14.02 |
Maximum of Months | 24.45 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.45 | 14.02 |
February | 23.13 | 16.67 |
March | 23.85 | 20.28 |
April | 24.31 | 25.86 |
May | 24.40 | 32.05 |
June | 24.43 | 35.24 |
July | 24.46 | 36.21 |
August | 24.42 | 36.44 |
September | 24.40 | 33.05 |
October | 24.36 | 27.59 |
November | 24.14 | 21.57 |
December | 22.67 | 14.93 |
Annual Sum or Average | 23.92 | 26.21 |
Minimum of Months | 22.45 | 14.02 |
Maximum of Months | 24.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.56 | 14.02 |
February | 23.89 | 16.67 |
March | 24.24 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.41 | 35.24 |
July | 24.46 | 36.21 |
August | 24.51 | 36.44 |
September | 24.49 | 33.05 |
October | 24.42 | 27.59 |
November | 24.34 | 21.57 |
December | 23.61 | 14.93 |
Annual Sum or Average | 24.23 | 26.21 |
Minimum of Months | 23.56 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 14.02 |
February | 23.04 | 16.67 |
March | 23.82 | 20.28 |
April | 24.31 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.51 | 36.21 |
August | 24.43 | 36.44 |
September | 24.40 | 33.05 |
October | 24.36 | 27.59 |
November | 24.12 | 21.57 |
December | 22.54 | 14.93 |
Annual Sum or Average | 23.90 | 26.21 |
Minimum of Months | 22.37 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 14.02 |
February | 22.87 | 16.67 |
March | 23.69 | 20.28 |
April | 24.28 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.51 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.34 | 27.59 |
November | 24.07 | 21.57 |
December | 22.49 | 14.93 |
Annual Sum or Average | 23.85 | 26.21 |
Minimum of Months | 22.21 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 14.02 |
February | 22.86 | 16.67 |
March | 23.69 | 20.28 |
April | 24.28 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.51 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.34 | 27.59 |
November | 24.06 | 21.57 |
December | 22.48 | 14.93 |
Annual Sum or Average | 23.85 | 26.21 |
Minimum of Months | 22.21 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 14.02 |
February | 23.62 | 16.67 |
March | 23.97 | 20.28 |
April | 24.29 | 25.86 |
May | 24.40 | 32.05 |
June | 24.43 | 35.24 |
July | 24.50 | 36.21 |
August | 24.53 | 36.44 |
September | 24.54 | 33.05 |
October | 24.42 | 27.59 |
November | 24.26 | 21.57 |
December | 23.36 | 14.93 |
Annual Sum or Average | 24.14 | 26.21 |
Minimum of Months | 23.34 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 14.02 |
February | 23.65 | 16.67 |
March | 23.99 | 20.28 |
April | 24.29 | 25.86 |
May | 24.40 | 32.05 |
June | 24.42 | 35.24 |
July | 24.49 | 36.21 |
August | 24.51 | 36.44 |
September | 24.53 | 33.05 |
October | 24.42 | 27.59 |
November | 24.26 | 21.57 |
December | 23.40 | 14.93 |
Annual Sum or Average | 24.15 | 26.21 |
Minimum of Months | 23.37 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 14.02 |
February | 21.99 | 16.67 |
March | 23.38 | 20.28 |
April | 25.54 | 25.86 |
May | 27.67 | 32.05 |
June | 29.22 | 35.24 |
July | 29.66 | 36.21 |
August | 29.72 | 36.44 |
September | 28.72 | 33.05 |
October | 26.45 | 27.59 |
November | 24.23 | 21.57 |
December | 21.14 | 14.93 |
Annual Sum or Average | 25.73 | 26.21 |
Minimum of Months | 20.78 | 14.02 |
Maximum of Months | 29.72 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 14.02 |
February | 24.15 | 16.67 |
March | 24.28 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.43 | 35.24 |
July | 24.46 | 36.21 |
August | 24.45 | 36.44 |
September | 24.43 | 33.05 |
October | 24.42 | 27.59 |
November | 24.38 | 21.57 |
December | 23.83 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.83 | 14.02 |
Maximum of Months | 24.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 14.02 |
February | 23.62 | 16.67 |
March | 24.16 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.47 | 36.21 |
August | 24.42 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.05 | 14.93 |
Annual Sum or Average | 24.07 | 26.21 |
Minimum of Months | 22.85 | 14.02 |
Maximum of Months | 24.47 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 14.02 |
February | 24.15 | 16.67 |
March | 24.31 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.42 | 35.24 |
July | 24.47 | 36.21 |
August | 24.46 | 36.44 |
September | 24.43 | 33.05 |
October | 24.42 | 27.59 |
November | 24.38 | 21.57 |
December | 23.84 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.84 | 14.02 |
Maximum of Months | 24.47 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 14.02 |
February | 23.51 | 16.67 |
March | 24.15 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.53 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.90 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.75 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.65 | 14.02 |
February | 23.42 | 16.67 |
March | 24.10 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.52 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.31 | 21.57 |
December | 22.94 | 14.93 |
Annual Sum or Average | 24.03 | 26.21 |
Minimum of Months | 22.65 | 14.02 |
Maximum of Months | 24.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.64 | 14.02 |
February | 23.41 | 16.67 |
March | 24.10 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.52 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.31 | 21.57 |
December | 22.92 | 14.93 |
Annual Sum or Average | 24.03 | 26.21 |
Minimum of Months | 22.64 | 14.02 |
Maximum of Months | 24.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 14.02 |
February | 24.17 | 16.67 |
March | 24.28 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.43 | 35.24 |
July | 24.51 | 36.21 |
August | 24.52 | 36.44 |
September | 24.53 | 33.05 |
October | 24.52 | 27.59 |
November | 24.42 | 21.57 |
December | 23.93 | 14.93 |
Annual Sum or Average | 24.34 | 26.21 |
Minimum of Months | 23.93 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 14.02 |
February | 24.17 | 16.67 |
March | 24.28 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.43 | 35.24 |
July | 24.51 | 36.21 |
August | 24.51 | 36.44 |
September | 24.53 | 33.05 |
October | 24.52 | 27.59 |
November | 24.42 | 21.57 |
December | 23.94 | 14.93 |
Annual Sum or Average | 24.34 | 26.21 |
Minimum of Months | 23.94 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 14.02 |
February | 24.75 | 16.67 |
March | 25.44 | 20.28 |
April | 26.23 | 25.86 |
May | 27.00 | 32.05 |
June | 27.52 | 35.24 |
July | 27.68 | 36.21 |
August | 27.68 | 36.44 |
September | 27.36 | 33.05 |
October | 26.71 | 27.59 |
November | 25.89 | 21.57 |
December | 24.10 | 14.93 |
Annual Sum or Average | 26.20 | 26.21 |
Minimum of Months | 23.95 | 14.02 |
Maximum of Months | 27.68 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 14.02 |
February | 24.19 | 16.67 |
March | 24.30 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.48 | 36.21 |
August | 24.46 | 36.44 |
September | 24.43 | 33.05 |
October | 24.42 | 27.59 |
November | 24.39 | 21.57 |
December | 23.89 | 14.93 |
Annual Sum or Average | 24.31 | 26.21 |
Minimum of Months | 23.89 | 14.02 |
Maximum of Months | 24.48 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 14.02 |
February | 23.71 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.49 | 36.21 |
August | 24.43 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 23.13 | 14.93 |
Annual Sum or Average | 24.10 | 26.21 |
Minimum of Months | 22.93 | 14.02 |
Maximum of Months | 24.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.86 | 14.02 |
February | 24.14 | 16.67 |
March | 24.30 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.53 | 36.21 |
August | 24.50 | 36.44 |
September | 24.45 | 33.05 |
October | 24.44 | 27.59 |
November | 24.39 | 21.57 |
December | 23.80 | 14.93 |
Annual Sum or Average | 24.30 | 26.21 |
Minimum of Months | 23.80 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 14.02 |
February | 23.59 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.57 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.36 | 21.57 |
December | 22.98 | 14.93 |
Annual Sum or Average | 24.08 | 26.21 |
Minimum of Months | 22.83 | 14.02 |
Maximum of Months | 24.57 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 14.02 |
February | 23.56 | 16.67 |
March | 24.16 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.54 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.06 | 14.93 |
Annual Sum or Average | 24.08 | 26.21 |
Minimum of Months | 22.78 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 14.02 |
February | 23.55 | 16.67 |
March | 24.16 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.55 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.05 | 14.93 |
Annual Sum or Average | 24.07 | 26.21 |
Minimum of Months | 22.78 | 14.02 |
Maximum of Months | 24.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 14.02 |
February | 24.23 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.53 | 36.21 |
August | 24.53 | 36.44 |
September | 24.53 | 33.05 |
October | 24.54 | 27.59 |
November | 24.44 | 21.57 |
December | 24.02 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.02 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 14.02 |
February | 24.23 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.53 | 36.21 |
August | 24.53 | 36.44 |
September | 24.53 | 33.05 |
October | 24.54 | 27.59 |
November | 24.44 | 21.57 |
December | 24.02 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.02 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.33 | 14.02 |
February | 25.11 | 16.67 |
March | 25.74 | 20.28 |
April | 26.41 | 25.86 |
May | 27.08 | 32.05 |
June | 27.47 | 35.24 |
July | 27.61 | 36.21 |
August | 27.59 | 36.44 |
September | 27.30 | 33.05 |
October | 26.83 | 27.59 |
November | 26.15 | 21.57 |
December | 24.46 | 14.93 |
Annual Sum or Average | 26.34 | 26.21 |
Minimum of Months | 24.33 | 14.02 |
Maximum of Months | 27.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.91 | 14.02 |
February | 24.19 | 16.67 |
March | 24.30 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.49 | 36.21 |
August | 24.47 | 36.44 |
September | 24.44 | 33.05 |
October | 24.42 | 27.59 |
November | 24.39 | 21.57 |
December | 23.88 | 14.93 |
Annual Sum or Average | 24.31 | 26.21 |
Minimum of Months | 23.88 | 14.02 |
Maximum of Months | 24.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 14.02 |
February | 23.71 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.50 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.35 | 21.57 |
December | 23.13 | 14.93 |
Annual Sum or Average | 24.11 | 26.21 |
Minimum of Months | 22.93 | 14.02 |
Maximum of Months | 24.50 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.83 | 14.02 |
February | 24.13 | 16.67 |
March | 24.29 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.56 | 36.21 |
August | 24.52 | 36.44 |
September | 24.45 | 33.05 |
October | 24.44 | 27.59 |
November | 24.39 | 21.57 |
December | 23.77 | 14.93 |
Annual Sum or Average | 24.30 | 26.21 |
Minimum of Months | 23.77 | 14.02 |
Maximum of Months | 24.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 14.02 |
February | 23.60 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.36 | 21.57 |
December | 22.99 | 14.93 |
Annual Sum or Average | 24.09 | 26.21 |
Minimum of Months | 22.84 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 14.02 |
February | 23.59 | 16.67 |
March | 24.17 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.56 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.10 | 14.93 |
Annual Sum or Average | 24.09 | 26.21 |
Minimum of Months | 22.82 | 14.02 |
Maximum of Months | 24.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 14.02 |
February | 23.58 | 16.67 |
March | 24.17 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.56 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.08 | 14.93 |
Annual Sum or Average | 24.09 | 26.21 |
Minimum of Months | 22.82 | 14.02 |
Maximum of Months | 24.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 14.02 |
February | 24.24 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.55 | 36.21 |
August | 24.54 | 36.44 |
September | 24.52 | 33.05 |
October | 24.54 | 27.59 |
November | 24.44 | 21.57 |
December | 24.03 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.03 | 14.02 |
Maximum of Months | 24.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 14.02 |
February | 24.23 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.55 | 36.21 |
August | 24.54 | 36.44 |
September | 24.53 | 33.05 |
October | 24.54 | 27.59 |
November | 24.44 | 21.57 |
December | 24.03 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.03 | 14.02 |
Maximum of Months | 24.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.46 | 14.02 |
February | 25.25 | 16.67 |
March | 25.86 | 20.28 |
April | 26.51 | 25.86 |
May | 27.16 | 32.05 |
June | 27.54 | 35.24 |
July | 27.69 | 36.21 |
August | 27.66 | 36.44 |
September | 27.37 | 33.05 |
October | 26.92 | 27.59 |
November | 26.27 | 21.57 |
December | 24.59 | 14.93 |
Annual Sum or Average | 26.44 | 26.21 |
Minimum of Months | 24.46 | 14.02 |
Maximum of Months | 27.69 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 14.02 |
February | 24.18 | 16.67 |
March | 24.29 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.51 | 36.21 |
August | 24.48 | 36.44 |
September | 24.44 | 33.05 |
October | 24.42 | 27.59 |
November | 24.39 | 21.57 |
December | 23.87 | 14.93 |
Annual Sum or Average | 24.31 | 26.21 |
Minimum of Months | 23.87 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 14.02 |
February | 23.71 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.51 | 36.21 |
August | 24.44 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.36 | 21.57 |
December | 23.13 | 14.93 |
Annual Sum or Average | 24.11 | 26.21 |
Minimum of Months | 22.93 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.81 | 14.02 |
February | 24.12 | 16.67 |
March | 24.29 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.58 | 36.21 |
August | 24.53 | 36.44 |
September | 24.45 | 33.05 |
October | 24.44 | 27.59 |
November | 24.39 | 21.57 |
December | 23.76 | 14.93 |
Annual Sum or Average | 24.30 | 26.21 |
Minimum of Months | 23.76 | 14.02 |
Maximum of Months | 24.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 14.02 |
February | 23.60 | 16.67 |
March | 24.19 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.61 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.36 | 21.57 |
December | 23.00 | 14.93 |
Annual Sum or Average | 24.10 | 26.21 |
Minimum of Months | 22.85 | 14.02 |
Maximum of Months | 24.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 14.02 |
February | 23.60 | 16.67 |
March | 24.18 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.57 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 23.12 | 14.93 |
Annual Sum or Average | 24.10 | 26.21 |
Minimum of Months | 22.85 | 14.02 |
Maximum of Months | 24.57 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 14.02 |
February | 23.59 | 16.67 |
March | 24.17 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.58 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 23.10 | 14.93 |
Annual Sum or Average | 24.10 | 26.21 |
Minimum of Months | 22.84 | 14.02 |
Maximum of Months | 24.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 14.02 |
February | 24.24 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.56 | 36.21 |
August | 24.54 | 36.44 |
September | 24.52 | 33.05 |
October | 24.53 | 27.59 |
November | 24.44 | 21.57 |
December | 24.03 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.03 | 14.02 |
Maximum of Months | 24.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.03 | 14.02 |
February | 24.23 | 16.67 |
March | 24.31 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.57 | 36.21 |
August | 24.55 | 36.44 |
September | 24.52 | 33.05 |
October | 24.53 | 27.59 |
November | 24.44 | 21.57 |
December | 24.02 | 14.93 |
Annual Sum or Average | 24.37 | 26.21 |
Minimum of Months | 24.02 | 14.02 |
Maximum of Months | 24.57 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.00 | 14.02 |
February | 25.79 | 16.67 |
March | 26.39 | 20.28 |
April | 27.03 | 25.86 |
May | 27.68 | 32.05 |
June | 28.06 | 35.24 |
July | 28.22 | 36.21 |
August | 28.18 | 36.44 |
September | 27.88 | 33.05 |
October | 27.44 | 27.59 |
November | 26.82 | 21.57 |
December | 25.14 | 14.93 |
Annual Sum or Average | 26.97 | 26.21 |
Minimum of Months | 25.00 | 14.02 |
Maximum of Months | 28.22 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.83 | 14.02 |
February | 24.14 | 16.67 |
March | 24.28 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.52 | 36.21 |
August | 24.48 | 36.44 |
September | 24.44 | 33.05 |
October | 24.42 | 27.59 |
November | 24.39 | 21.57 |
December | 23.81 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.81 | 14.02 |
Maximum of Months | 24.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 14.02 |
February | 23.62 | 16.67 |
March | 24.16 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.52 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 23.06 | 14.93 |
Annual Sum or Average | 24.09 | 26.21 |
Minimum of Months | 22.84 | 14.02 |
Maximum of Months | 24.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 14.02 |
February | 24.08 | 16.67 |
March | 24.27 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.60 | 36.21 |
August | 24.54 | 36.44 |
September | 24.45 | 33.05 |
October | 24.43 | 27.59 |
November | 24.39 | 21.57 |
December | 23.69 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.69 | 14.02 |
Maximum of Months | 24.60 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 14.02 |
February | 23.52 | 16.67 |
March | 24.16 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.50 | 35.24 |
July | 24.63 | 36.21 |
August | 24.48 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.36 | 21.57 |
December | 22.93 | 14.93 |
Annual Sum or Average | 24.08 | 26.21 |
Minimum of Months | 22.76 | 14.02 |
Maximum of Months | 24.63 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 14.02 |
February | 23.52 | 16.67 |
March | 24.14 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.50 | 35.24 |
July | 24.59 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.04 | 14.93 |
Annual Sum or Average | 24.07 | 26.21 |
Minimum of Months | 22.75 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.74 | 14.02 |
February | 23.51 | 16.67 |
March | 24.14 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.50 | 35.24 |
July | 24.59 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 23.02 | 14.93 |
Annual Sum or Average | 24.07 | 26.21 |
Minimum of Months | 22.74 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | 14.02 |
February | 24.20 | 16.67 |
March | 24.29 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.58 | 36.21 |
August | 24.55 | 36.44 |
September | 24.52 | 33.05 |
October | 24.52 | 27.59 |
November | 24.43 | 21.57 |
December | 23.98 | 14.93 |
Annual Sum or Average | 24.36 | 26.21 |
Minimum of Months | 23.97 | 14.02 |
Maximum of Months | 24.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | 14.02 |
February | 24.20 | 16.67 |
March | 24.29 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.58 | 36.21 |
August | 24.55 | 36.44 |
September | 24.52 | 33.05 |
October | 24.53 | 27.59 |
November | 24.43 | 21.57 |
December | 23.97 | 14.93 |
Annual Sum or Average | 24.36 | 26.21 |
Minimum of Months | 23.97 | 14.02 |
Maximum of Months | 24.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.37 | 14.02 |
February | 25.17 | 16.67 |
March | 25.81 | 20.28 |
April | 26.49 | 25.86 |
May | 27.16 | 32.05 |
June | 27.57 | 35.24 |
July | 27.73 | 36.21 |
August | 27.68 | 36.44 |
September | 27.37 | 33.05 |
October | 26.91 | 27.59 |
November | 26.26 | 21.57 |
December | 24.52 | 14.93 |
Annual Sum or Average | 26.43 | 26.21 |
Minimum of Months | 24.37 | 14.02 |
Maximum of Months | 27.73 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 14.02 |
February | 24.11 | 16.67 |
March | 24.26 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.53 | 36.21 |
August | 24.49 | 36.44 |
September | 24.44 | 33.05 |
October | 24.42 | 27.59 |
November | 24.38 | 21.57 |
December | 23.76 | 14.93 |
Annual Sum or Average | 24.28 | 26.21 |
Minimum of Months | 23.76 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 14.02 |
February | 23.56 | 16.67 |
March | 24.14 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.53 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 23.00 | 14.93 |
Annual Sum or Average | 24.07 | 26.21 |
Minimum of Months | 22.78 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 14.02 |
February | 24.04 | 16.67 |
March | 24.26 | 20.28 |
April | 24.37 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.62 | 36.21 |
August | 24.55 | 36.44 |
September | 24.45 | 33.05 |
October | 24.43 | 27.59 |
November | 24.39 | 21.57 |
December | 23.65 | 14.93 |
Annual Sum or Average | 24.28 | 26.21 |
Minimum of Months | 23.65 | 14.02 |
Maximum of Months | 24.62 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 14.02 |
February | 23.46 | 16.67 |
March | 24.14 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.65 | 36.21 |
August | 24.49 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.36 | 21.57 |
December | 22.88 | 14.93 |
Annual Sum or Average | 24.06 | 26.21 |
Minimum of Months | 22.70 | 14.02 |
Maximum of Months | 24.65 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.68 | 14.02 |
February | 23.45 | 16.67 |
March | 24.12 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.60 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.98 | 14.93 |
Annual Sum or Average | 24.06 | 26.21 |
Minimum of Months | 22.68 | 14.02 |
Maximum of Months | 24.60 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.68 | 14.02 |
February | 23.44 | 16.67 |
March | 24.12 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.61 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.97 | 14.93 |
Annual Sum or Average | 24.06 | 26.21 |
Minimum of Months | 22.68 | 14.02 |
Maximum of Months | 24.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 14.02 |
February | 24.18 | 16.67 |
March | 24.28 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.55 | 36.44 |
September | 24.52 | 33.05 |
October | 24.52 | 27.59 |
November | 24.43 | 21.57 |
December | 23.93 | 14.93 |
Annual Sum or Average | 24.35 | 26.21 |
Minimum of Months | 23.93 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.92 | 14.02 |
February | 24.17 | 16.67 |
March | 24.28 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.56 | 36.44 |
September | 24.52 | 33.05 |
October | 24.52 | 27.59 |
November | 24.43 | 21.57 |
December | 23.92 | 14.93 |
Annual Sum or Average | 24.35 | 26.21 |
Minimum of Months | 23.92 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.22 | 14.02 |
February | 25.04 | 16.67 |
March | 25.71 | 20.28 |
April | 26.41 | 25.86 |
May | 27.10 | 32.05 |
June | 27.52 | 35.24 |
July | 27.69 | 36.21 |
August | 27.63 | 36.44 |
September | 27.30 | 33.05 |
October | 26.83 | 27.59 |
November | 26.18 | 21.57 |
December | 24.38 | 14.93 |
Annual Sum or Average | 26.34 | 26.21 |
Minimum of Months | 24.22 | 14.02 |
Maximum of Months | 27.69 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.73 | 14.02 |
February | 24.08 | 16.67 |
March | 24.25 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.53 | 36.21 |
August | 24.49 | 36.44 |
September | 24.44 | 33.05 |
October | 24.42 | 27.59 |
November | 24.38 | 21.57 |
December | 23.71 | 14.93 |
Annual Sum or Average | 24.27 | 26.21 |
Minimum of Months | 23.71 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 14.02 |
February | 23.51 | 16.67 |
March | 24.12 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.54 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 22.96 | 14.93 |
Annual Sum or Average | 24.06 | 26.21 |
Minimum of Months | 22.73 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 14.02 |
February | 24.01 | 16.67 |
March | 24.25 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.63 | 36.21 |
August | 24.55 | 36.44 |
September | 24.45 | 33.05 |
October | 24.43 | 27.59 |
November | 24.39 | 21.57 |
December | 23.60 | 14.93 |
Annual Sum or Average | 24.27 | 26.21 |
Minimum of Months | 23.60 | 14.02 |
Maximum of Months | 24.63 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 14.02 |
February | 23.42 | 16.67 |
March | 24.12 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.52 | 35.24 |
July | 24.66 | 36.21 |
August | 24.50 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.36 | 21.57 |
December | 22.85 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.66 | 14.02 |
Maximum of Months | 24.66 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 14.02 |
February | 23.41 | 16.67 |
March | 24.10 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.61 | 36.21 |
August | 24.48 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.94 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.63 | 14.02 |
Maximum of Months | 24.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 14.02 |
February | 23.40 | 16.67 |
March | 24.10 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.61 | 36.21 |
August | 24.48 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.93 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.63 | 14.02 |
Maximum of Months | 24.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 14.02 |
February | 24.16 | 16.67 |
March | 24.27 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.56 | 36.44 |
September | 24.52 | 33.05 |
October | 24.51 | 27.59 |
November | 24.42 | 21.57 |
December | 23.89 | 14.93 |
Annual Sum or Average | 24.34 | 26.21 |
Minimum of Months | 23.88 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 14.02 |
February | 24.15 | 16.67 |
March | 24.27 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.60 | 36.21 |
August | 24.56 | 36.44 |
September | 24.52 | 33.05 |
October | 24.51 | 27.59 |
November | 24.42 | 21.57 |
December | 23.88 | 14.93 |
Annual Sum or Average | 24.34 | 26.21 |
Minimum of Months | 23.88 | 14.02 |
Maximum of Months | 24.60 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 14.02 |
February | 24.98 | 16.67 |
March | 25.67 | 20.28 |
April | 26.41 | 25.86 |
May | 27.12 | 32.05 |
June | 27.54 | 35.24 |
July | 27.72 | 36.21 |
August | 27.66 | 36.44 |
September | 27.32 | 33.05 |
October | 26.83 | 27.59 |
November | 26.17 | 21.57 |
December | 24.30 | 14.93 |
Annual Sum or Average | 26.33 | 26.21 |
Minimum of Months | 24.14 | 14.02 |
Maximum of Months | 27.72 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 14.02 |
February | 24.05 | 16.67 |
March | 24.23 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.54 | 36.21 |
August | 24.49 | 36.44 |
September | 24.44 | 33.05 |
October | 24.41 | 27.59 |
November | 24.38 | 21.57 |
December | 23.66 | 14.93 |
Annual Sum or Average | 24.26 | 26.21 |
Minimum of Months | 23.66 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 14.02 |
February | 23.49 | 16.67 |
March | 24.10 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.54 | 36.21 |
August | 24.46 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.35 | 21.57 |
December | 22.94 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.70 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 14.02 |
February | 23.98 | 16.67 |
March | 24.23 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.49 | 35.24 |
July | 24.63 | 36.21 |
August | 24.55 | 36.44 |
September | 24.45 | 33.05 |
October | 24.42 | 27.59 |
November | 24.38 | 21.57 |
December | 23.56 | 14.93 |
Annual Sum or Average | 24.25 | 26.21 |
Minimum of Months | 23.56 | 14.02 |
Maximum of Months | 24.63 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 14.02 |
February | 23.39 | 16.67 |
March | 24.10 | 20.28 |
April | 24.36 | 25.86 |
May | 24.40 | 32.05 |
June | 24.52 | 35.24 |
July | 24.66 | 36.21 |
August | 24.49 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.36 | 21.57 |
December | 22.84 | 14.93 |
Annual Sum or Average | 24.05 | 26.21 |
Minimum of Months | 22.63 | 14.02 |
Maximum of Months | 24.66 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 14.02 |
February | 23.39 | 16.67 |
March | 24.08 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.60 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.91 | 14.93 |
Annual Sum or Average | 24.04 | 26.21 |
Minimum of Months | 22.60 | 14.02 |
Maximum of Months | 24.60 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 14.02 |
February | 23.38 | 16.67 |
March | 24.08 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.51 | 35.24 |
July | 24.61 | 36.21 |
August | 24.48 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.34 | 21.57 |
December | 22.90 | 14.93 |
Annual Sum or Average | 24.04 | 26.21 |
Minimum of Months | 22.60 | 14.02 |
Maximum of Months | 24.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.82 | 14.02 |
February | 24.13 | 16.67 |
March | 24.26 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.55 | 36.44 |
September | 24.50 | 33.05 |
October | 24.49 | 27.59 |
November | 24.40 | 21.57 |
December | 23.83 | 14.93 |
Annual Sum or Average | 24.32 | 26.21 |
Minimum of Months | 23.82 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.82 | 14.02 |
February | 24.12 | 16.67 |
March | 24.25 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.59 | 36.21 |
August | 24.56 | 36.44 |
September | 24.51 | 33.05 |
October | 24.50 | 27.59 |
November | 24.41 | 21.57 |
December | 23.82 | 14.93 |
Annual Sum or Average | 24.32 | 26.21 |
Minimum of Months | 23.82 | 14.02 |
Maximum of Months | 24.59 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 14.02 |
February | 24.93 | 16.67 |
March | 25.67 | 20.28 |
April | 26.49 | 25.86 |
May | 27.26 | 32.05 |
June | 27.71 | 35.24 |
July | 27.88 | 36.21 |
August | 27.83 | 36.44 |
September | 27.46 | 33.05 |
October | 26.92 | 27.59 |
November | 26.18 | 21.57 |
December | 24.22 | 14.93 |
Annual Sum or Average | 26.39 | 26.21 |
Minimum of Months | 24.04 | 14.02 |
Maximum of Months | 27.88 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.36 | 14.02 |
February | 23.75 | 16.67 |
March | 24.10 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.45 | 35.24 |
July | 24.52 | 36.21 |
August | 24.49 | 36.44 |
September | 24.44 | 33.05 |
October | 24.40 | 27.59 |
November | 24.33 | 21.57 |
December | 23.42 | 14.93 |
Annual Sum or Average | 24.17 | 26.21 |
Minimum of Months | 23.36 | 14.02 |
Maximum of Months | 24.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 14.02 |
February | 23.39 | 16.67 |
March | 23.98 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.53 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.37 | 27.59 |
November | 24.27 | 21.57 |
December | 22.90 | 14.93 |
Annual Sum or Average | 24.02 | 26.21 |
Minimum of Months | 22.69 | 14.02 |
Maximum of Months | 24.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 14.02 |
February | 23.69 | 16.67 |
March | 24.09 | 20.28 |
April | 24.34 | 25.86 |
May | 24.40 | 32.05 |
June | 24.46 | 35.24 |
July | 24.56 | 36.21 |
August | 24.52 | 36.44 |
September | 24.45 | 33.05 |
October | 24.41 | 27.59 |
November | 24.32 | 21.57 |
December | 23.33 | 14.93 |
Annual Sum or Average | 24.16 | 26.21 |
Minimum of Months | 23.29 | 14.02 |
Maximum of Months | 24.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 14.02 |
February | 23.33 | 16.67 |
March | 23.99 | 20.28 |
April | 24.34 | 25.86 |
May | 24.40 | 32.05 |
June | 24.48 | 35.24 |
July | 24.60 | 36.21 |
August | 24.47 | 36.44 |
September | 24.40 | 33.05 |
October | 24.37 | 27.59 |
November | 24.26 | 21.57 |
December | 22.82 | 14.93 |
Annual Sum or Average | 24.01 | 26.21 |
Minimum of Months | 22.66 | 14.02 |
Maximum of Months | 24.60 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.59 | 14.02 |
February | 23.31 | 16.67 |
March | 23.98 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.54 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.36 | 27.59 |
November | 24.25 | 21.57 |
December | 22.85 | 14.93 |
Annual Sum or Average | 24.00 | 26.21 |
Minimum of Months | 22.59 | 14.02 |
Maximum of Months | 24.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.59 | 14.02 |
February | 23.31 | 16.67 |
March | 23.98 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.47 | 35.24 |
July | 24.55 | 36.21 |
August | 24.45 | 36.44 |
September | 24.40 | 33.05 |
October | 24.36 | 27.59 |
November | 24.25 | 21.57 |
December | 22.84 | 14.93 |
Annual Sum or Average | 23.99 | 26.21 |
Minimum of Months | 22.59 | 14.02 |
Maximum of Months | 24.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.49 | 14.02 |
February | 23.85 | 16.67 |
March | 24.14 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.51 | 36.21 |
August | 24.51 | 36.44 |
September | 24.49 | 33.05 |
October | 24.47 | 27.59 |
November | 24.36 | 21.57 |
December | 23.54 | 14.93 |
Annual Sum or Average | 24.21 | 26.21 |
Minimum of Months | 23.49 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.49 | 14.02 |
February | 23.85 | 16.67 |
March | 24.13 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.44 | 35.24 |
July | 24.51 | 36.21 |
August | 24.51 | 36.44 |
September | 24.49 | 33.05 |
October | 24.47 | 27.59 |
November | 24.36 | 21.57 |
December | 23.54 | 14.93 |
Annual Sum or Average | 24.21 | 26.21 |
Minimum of Months | 23.49 | 14.02 |
Maximum of Months | 24.51 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:11:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.33 | 14.02 |
February | 25.39 | 16.67 |
March | 26.25 | 20.28 |
April | 27.31 | 25.86 |
May | 28.37 | 32.05 |
June | 28.86 | 35.24 |
July | 29.01 | 36.21 |
August | 29.03 | 36.44 |
September | 28.54 | 33.05 |
October | 27.75 | 27.59 |
November | 26.71 | 21.57 |
December | 24.52 | 14.93 |
Annual Sum or Average | 27.18 | 26.21 |
Minimum of Months | 24.33 | 14.02 |
Maximum of Months | 29.03 | 36.44 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:11:41
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.250568E+12 | 168187.801 | 25-JAN-17:30 | 11327.174 | 57142.088 | 31891.013 | 0.000 | 50923.739 | 10364.000 | 2606.145 | 1938.483 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.237018E+12 | 173661.836 | 25-FEB-18:00 | 13120.457 | 57042.023 | 31891.013 | 0.000 | 54887.130 | 10364.000 | 2606.145 | 1763.060 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.285877E+12 | 182588.828 | 31-MAR-16:15 | 11327.174 | 57142.088 | 31891.013 | 0.000 | 74967.343 | 0.000 | 2606.145 | 2659.868 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.325195E+12 | 188240.735 | 21-APR-16:15 | 11327.174 | 57142.088 | 31891.013 | 0.000 | 80732.548 | 0.000 | 2606.145 | 2546.570 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.387160E+12 | 202661.191 | 20-MAY-18:30 | 14401.373 | 51749.961 | 31891.013 | 0.000 | 87016.036 | 10364.000 | 2606.145 | 2871.638 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.403984E+12 | 207192.372 | 29-JUN-18:00 | 14401.373 | 51749.961 | 31891.013 | 0.000 | 91561.407 | 10364.000 | 2606.145 | 2857.448 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.428830E+12 | 207230.493 | 30-JUL-18:45 | 14401.373 | 51749.961 | 31891.013 | 0.000 | 91462.956 | 10364.000 | 2606.145 | 2994.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.425204E+12 | 207032.746 | 24-AUG-18:30 | 14401.373 | 51749.961 | 31891.013 | 0.000 | 91307.623 | 10364.000 | 2606.145 | 2951.605 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.388978E+12 | 205827.344 | 11-SEP-17:00 | 13120.457 | 57042.023 | 31891.013 | 0.000 | 85928.136 | 10364.000 | 2606.145 | 2887.561 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.364136E+12 | 198151.702 | 04-OCT-17:45 | 13120.457 | 57042.023 | 31891.013 | 0.000 | 78528.106 | 10364.000 | 2606.145 | 2611.949 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.306401E+12 | 178431.051 | 04-NOV-17:15 | 13120.457 | 57042.023 | 31891.013 | 0.000 | 59325.056 | 10364.000 | 2606.145 | 2094.545 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.254108E+12 | 159652.866 | 16-DEC-17:15 | 11327.174 | 57042.023 | 31891.013 | 0.000 | 42904.497 | 10364.000 | 2606.145 | 1530.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.405746E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.237018E+12 | 159652.866 | 11327.174 | 51749.961 | 31891.013 | 0.000 | 42904.497 | 0.000 | 2606.145 | 1530.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.428830E+12 | 207230.493 | 14401.373 | 57142.088 | 31891.013 | 0.000 | 91561.407 | 10364.000 | 2606.145 | 2994.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:11:41
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.848537E+11 | 103093.129 | 09-JAN-06:30 | 0.000 | 0.000 | 0.000 | 103093.129 | 54400.976 | 54400.976 | 48692.154 |
February | 0.725605E+11 | 72472.244 | 01-FEB-07:00 | 0.000 | 0.000 | 0.000 | 72472.244 | 72472.244 | 72472.244 | 0.000 |
March | 0.740405E+11 | 71079.261 | 02-MAR-07:00 | 0.000 | 0.000 | 0.000 | 71079.261 | 71079.261 | 71079.261 | 0.000 |
April | 0.630485E+11 | 68653.539 | 03-APR-06:45 | 0.000 | 0.000 | 0.000 | 68653.539 | 68653.539 | 68653.539 | 0.000 |
May | 0.562083E+11 | 66028.164 | 02-MAY-07:15 | 0.000 | 0.000 | 0.000 | 66028.164 | 66028.164 | 66028.164 | 0.000 |
June | 0.479942E+11 | 49881.937 | 01-JUN-06:45 | 0.000 | 0.000 | 0.000 | 49881.937 | 49881.937 | 49881.937 | 0.000 |
July | 0.471650E+11 | 34904.502 | 04-JUL-06:00 | 0.000 | 0.000 | 0.000 | 34904.502 | 34904.502 | 34904.502 | 0.000 |
August | 0.495542E+11 | 52874.640 | 30-AUG-06:00 | 0.000 | 0.000 | 0.000 | 52874.640 | 52874.640 | 52874.640 | 0.000 |
September | 0.542950E+11 | 66337.635 | 30-SEP-06:00 | 0.000 | 0.000 | 0.000 | 66337.635 | 66337.635 | 66337.635 | 0.000 |
October | 0.650114E+11 | 68638.210 | 30-OCT-06:30 | 0.000 | 0.000 | 0.000 | 68638.210 | 68638.210 | 68638.210 | 0.000 |
November | 0.715258E+11 | 71021.491 | 29-NOV-07:00 | 0.000 | 0.000 | 0.000 | 71021.491 | 71021.491 | 71021.491 | 0.000 |
December | 0.814465E+11 | 97264.451 | 06-DEC-06:00 | 0.000 | 0.000 | 0.000 | 97264.451 | 68016.553 | 68016.553 | 29247.898 |
Annual Sum or Average | 0.767704E+12 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.471650E+11 | 34904.502 | 0.000 | 0.000 | 0.000 | 34904.502 | 34904.502 | 34904.502 | 0.000 | |
Maximum of Months | 0.848537E+11 | 103093.129 | 0.000 | 0.000 | 0.000 | 103093.129 | 72472.244 | 72472.244 | 48692.154 |