Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59

Tabular Output Report in Format: HTML

Building: High-Rise Apartment

Environment: Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650

Simulation Timestamp: 2015-09-09 19:00:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 4297.04 548.34 608.66
Net Site Energy 4297.04 548.34 608.66
Total Source Energy 10931.76 1394.98 1548.43
Net Source Energy 10931.76 1394.98 1548.43


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 7836.48
Net Conditioned Building Area 7059.89
Unconditioned Building Area 776.58


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 70.42 194.94 0.00 0.00 0.00 0.00
Cooling 496.27 0.00 0.00 0.00 0.00 0.00
Interior Lighting 296.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 162.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 740.36 0.00 0.00 0.00 0.00 0.00
Pumps 54.36 0.00 0.00 0.00 0.00 0.00
Heat Rejection 17.58 0.00 0.00 0.00 0.00 1696.74
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1090.21 0.00 0.00 0.00 4778.51
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 3011.89 1285.16 0.00 0.00 0.00 6475.26
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 194.94 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 70.42 0.00 0.00 0.00 0.00 0.00
Cooling General 496.27 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 242.55 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 54.01 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 162.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 1137.32 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 740.36 0.00 0.00 0.00 0.00 0.00
Pumps General 54.36 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 17.58 0.00 0.00 0.00 0.00 1696.74
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 1090.21 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 4778.51
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 65.07 0.00 0.00 0.00 0.00 0.00
HVAC 195.33 182.04 0.00 0.00 0.00 0.92
Other 161.10 0.00 0.00 0.00 0.00 0.00
Total 426.62 182.04 0.00 0.00 0.00 0.92


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 58.62 0.00 0.00 0.00 0.00 0.00
HVAC 175.97 164.00 0.00 0.00 0.00 0.83
Other 145.13 0.00 0.00 0.00 0.00 0.00
Total 384.34 164.00 0.00 0.00 0.00 0.83


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 3011.89 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 3011.89 100.00
     
Total On-Site and Utility Electric Sources 3011.89 100.00
Total Electricity End Uses 3011.89 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 6475.26 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 6475.26 100.00
Total Water End Uses 6475.26 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 105.00
Time Setpoint Not Met During Occupied Cooling 525.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1341.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

COMPONENTS OF PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
RunPeriod Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
Weather File Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3855.02 1411.96 515.55 1411.96 515.55
Window Opening Area [m2] 1150.39 423.59 152.73 423.59 150.48
Window-Wall Ratio [%] 29.84 30.00 29.62 30.00 29.19


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 3752.84 1411.96 464.46 1411.96 464.46
Window Opening Area [m2] 1125.85 423.59 139.34 423.59 139.34
Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.96 1.00 58.52 17.56 29.5362 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 4.47 6.7128   0.0000
F2 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F2 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F2 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F3 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F3 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F3 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F4 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F4 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F4 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
M SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
M CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 13.4255   0.0000
F6 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F6 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F6 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F7 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F7 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F7 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F8 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F8 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F8 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
F9 SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
F9 N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
F9 CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   0.0000
T SW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.96 1.00 58.52 17.56 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.96 1.00 35.30 10.59 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 10.59 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 2.23 6.7128   264.3872
Total 7836.48     23884.04   3855.02 1150.39 4.3335 39.48 8.6291
Conditioned Total 7059.89     21517.16   3752.84 1125.85 3.9979 35.57 6.6700
Unconditioned Total 776.58     2366.87   102.18 24.54 7.3840   26.4387
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 21-JUL-19:15 17-JAN-08:15 - - - 21-JUL-17:15
Heating 0.00 150090.38 0.00 0.00 0.00 0.00
Cooling 60361.60 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14401.37 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 49889.93 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23476.58 0.00 0.00 0.00 0.00 0.00
Pumps 1741.30 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1886.79 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 79368.04 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 163762.87 229458.43 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 150090.38 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 60361.60 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 11484.27 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 2917.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10364.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49889.93 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 23476.58 0.00 0.00 0.00 0.00 0.00
Pumps General 1741.30 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1886.79 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 79368.04 0.00 0.00 0.00 0.00
  sub cat 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 223.01 211.32 0.00 0.00 0.00
Cooling 1571.70 0.00 0.00 0.00 0.00
Interior Lighting 939.20 0.00 0.00 0.00 0.00
Exterior Lighting 515.72 0.00 0.00 0.00 0.00
Interior Equipment 3601.91 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2344.71 0.00 0.00 0.00 0.00
Pumps 172.17 0.00 0.00 0.00 0.00
Heat Rejection 55.67 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 1181.79 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 9538.65 1393.11 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 31.59 29.93 0.00 0.00 0.00
Cooling 222.62 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.05 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 332.12 0.00 0.00 0.00 0.00
Pumps 24.39 0.00 0.00 0.00 0.00
Heat Rejection 7.89 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 167.39 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1351.10 197.33 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 31.59 29.93 0.00 0.00 0.00
Cooling 222.62 0.00 0.00 0.00 0.00
Interior Lighting 133.03 0.00 0.00 0.00 0.00
Exterior Lighting 73.05 0.00 0.00 0.00 0.00
Interior Equipment 510.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 332.12 0.00 0.00 0.00 0.00
Pumps 24.39 0.00 0.00 0.00 0.00
Heat Rejection 7.89 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 167.39 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1351.10 197.33 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 270.00 180.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 270.00 180.00  
F2 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F2 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F2 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F2 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F2 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F2 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F3 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F3 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F3 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F3 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F3 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F3 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F4 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F4 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F4 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F4 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F4 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F4 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F6 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F6 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F6 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F6 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F6 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F6 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F7 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F7 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F7 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F7 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F7 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F7 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F8 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F8 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F8 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F8 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F8 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F8 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
F9 WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
F9 EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
F9 NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
F9 SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
F9 WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
F9 EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 0.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
GWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No G WWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.48_SHGC_0.40 3.36 0.00 0.00 3.36 3.36 2.653 0.426 0.308     No G EWALL C 90.00 90.00 E
F2WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL SWA 270.00 90.00 W
F2WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SWA 180.00 90.00 S
F2WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NWA 0.00 90.00 N
F2WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 WWALL NWA 270.00 90.00 W
F2WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL SEA 90.00 90.00 E
F2WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL SEA 180.00 90.00 S
F2WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL NEA 0.00 90.00 N
F2WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F2 EWALL NEA 90.00 90.00 E
F2WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N1A 0.00 90.00 N
F2WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 NWALL N2A 0.00 90.00 N
F2WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S1A 180.00 90.00 S
F2WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F2 SWALL S2A 180.00 90.00 S
F2WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 WWALL C 270.00 90.00 W
F2WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F2 EWALL C 90.00 90.00 E
F3WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL SWA 270.00 90.00 W
F3WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SWA 180.00 90.00 S
F3WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NWA 0.00 90.00 N
F3WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 WWALL NWA 270.00 90.00 W
F3WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL SEA 90.00 90.00 E
F3WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL SEA 180.00 90.00 S
F3WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL NEA 0.00 90.00 N
F3WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F3 EWALL NEA 90.00 90.00 E
F3WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N1A 0.00 90.00 N
F3WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 NWALL N2A 0.00 90.00 N
F3WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S1A 180.00 90.00 S
F3WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F3 SWALL S2A 180.00 90.00 S
F3WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 WWALL C 270.00 90.00 W
F3WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F3 EWALL C 90.00 90.00 E
F4WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL SWA 270.00 90.00 W
F4WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SWA 180.00 90.00 S
F4WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NWA 0.00 90.00 N
F4WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 WWALL NWA 270.00 90.00 W
F4WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL SEA 90.00 90.00 E
F4WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL SEA 180.00 90.00 S
F4WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL NEA 0.00 90.00 N
F4WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F4 EWALL NEA 90.00 90.00 E
F4WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N1A 0.00 90.00 N
F4WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 NWALL N2A 0.00 90.00 N
F4WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S1A 180.00 90.00 S
F4WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F4 SWALL S2A 180.00 90.00 S
F4WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 WWALL C 270.00 90.00 W
F4WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F4 EWALL C 90.00 90.00 E
MWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
MWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M WWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No M EWALL C 90.00 90.00 E
F6WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL SWA 270.00 90.00 W
F6WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SWA 180.00 90.00 S
F6WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NWA 0.00 90.00 N
F6WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 WWALL NWA 270.00 90.00 W
F6WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL SEA 90.00 90.00 E
F6WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL SEA 180.00 90.00 S
F6WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL NEA 0.00 90.00 N
F6WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F6 EWALL NEA 90.00 90.00 E
F6WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N1A 0.00 90.00 N
F6WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 NWALL N2A 0.00 90.00 N
F6WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S1A 180.00 90.00 S
F6WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F6 SWALL S2A 180.00 90.00 S
F6WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 WWALL C 270.00 90.00 W
F6WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F6 EWALL C 90.00 90.00 E
F7WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL SWA 270.00 90.00 W
F7WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SWA 180.00 90.00 S
F7WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NWA 0.00 90.00 N
F7WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 WWALL NWA 270.00 90.00 W
F7WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL SEA 90.00 90.00 E
F7WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL SEA 180.00 90.00 S
F7WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL NEA 0.00 90.00 N
F7WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F7 EWALL NEA 90.00 90.00 E
F7WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N1A 0.00 90.00 N
F7WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 NWALL N2A 0.00 90.00 N
F7WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S1A 180.00 90.00 S
F7WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F7 SWALL S2A 180.00 90.00 S
F7WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 WWALL C 270.00 90.00 W
F7WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F7 EWALL C 90.00 90.00 E
F8WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL SWA 270.00 90.00 W
F8WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SWA 180.00 90.00 S
F8WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NWA 0.00 90.00 N
F8WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 WWALL NWA 270.00 90.00 W
F8WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL SEA 90.00 90.00 E
F8WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL SEA 180.00 90.00 S
F8WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL NEA 0.00 90.00 N
F8WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F8 EWALL NEA 90.00 90.00 E
F8WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N1A 0.00 90.00 N
F8WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 NWALL N2A 0.00 90.00 N
F8WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S1A 180.00 90.00 S
F8WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F8 SWALL S2A 180.00 90.00 S
F8WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 WWALL C 270.00 90.00 W
F8WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F8 EWALL C 90.00 90.00 E
F9WINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL SWA 270.00 90.00 W
F9WINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SWA 180.00 90.00 S
F9WINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NWA 0.00 90.00 N
F9WINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 WWALL NWA 270.00 90.00 W
F9WINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL SEA 90.00 90.00 E
F9WINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL SEA 180.00 90.00 S
F9WINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL NEA 0.00 90.00 N
F9WINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No F9 EWALL NEA 90.00 90.00 E
F9WINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N1A 0.00 90.00 N
F9WINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 NWALL N2A 0.00 90.00 N
F9WINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S1A 180.00 90.00 S
F9WINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No F9 SWALL S2A 180.00 90.00 S
F9WINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 WWALL C 270.00 90.00 W
F9WINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No F9 EWALL C 90.00 90.00 E
TWINDOW2 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW3 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW4 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW6 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW8 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW5 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW7 WINDOW_U_0.48_SHGC_0.40 6.97 0.00 0.00 6.97 6.97 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW9 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW10 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW11 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW12 WINDOW_U_0.48_SHGC_0.40 10.59 0.00 0.00 10.59 10.59 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW13 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T WWALL C 270.00 90.00 W
TWINDOW14 WINDOW_U_0.48_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 90.00 90.00 E
Total or Average           1150.39 2.653 0.426 0.308              
North Total or Average           423.59 2.653 0.426 0.308              
Non-North Total or Average           726.80 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F2WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F2WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F2WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F3WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F3WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F3WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F4WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F4WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F4WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F6WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F6WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F6WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F7WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F7WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F7WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F8WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F8WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F8WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
F9WINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9WINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
F9WINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
F9WINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW6 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW8 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW7 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW11 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW12 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW13 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
G SW APARTMENT_LIGHTS_HARDWIRED G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G NW APARTMENT_LIGHTS_HARDWIRED G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
OFFICE_LIGHTS_HARDWIRED OFFICE 14.7681 88.25 1303.26 GeneralLights LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_HARDWIRED G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N1 APARTMENT_LIGHTS_HARDWIRED G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G N2 APARTMENT_LIGHTS_HARDWIRED G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S1 APARTMENT_LIGHTS_HARDWIRED G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G S2 APARTMENT_LIGHTS_HARDWIRED G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
G CORRIDOR_LIGHTS_HARDWIRED G CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F2 SW APARTMENT_LIGHTS_HARDWIRED F2 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NW APARTMENT_LIGHTS_HARDWIRED F2 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 SE APARTMENT_LIGHTS_HARDWIRED F2 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 NE APARTMENT_LIGHTS_HARDWIRED F2 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N1 APARTMENT_LIGHTS_HARDWIRED F2 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 N2 APARTMENT_LIGHTS_HARDWIRED F2 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S1 APARTMENT_LIGHTS_HARDWIRED F2 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 S2 APARTMENT_LIGHTS_HARDWIRED F2 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F2 CORRIDOR_LIGHTS_HARDWIRED F2 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F3 SW APARTMENT_LIGHTS_HARDWIRED F3 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NW APARTMENT_LIGHTS_HARDWIRED F3 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 SE APARTMENT_LIGHTS_HARDWIRED F3 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 NE APARTMENT_LIGHTS_HARDWIRED F3 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N1 APARTMENT_LIGHTS_HARDWIRED F3 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 N2 APARTMENT_LIGHTS_HARDWIRED F3 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S1 APARTMENT_LIGHTS_HARDWIRED F3 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 S2 APARTMENT_LIGHTS_HARDWIRED F3 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F3 CORRIDOR_LIGHTS_HARDWIRED F3 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F4 SW APARTMENT_LIGHTS_HARDWIRED F4 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NW APARTMENT_LIGHTS_HARDWIRED F4 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 SE APARTMENT_LIGHTS_HARDWIRED F4 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 NE APARTMENT_LIGHTS_HARDWIRED F4 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N1 APARTMENT_LIGHTS_HARDWIRED F4 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 N2 APARTMENT_LIGHTS_HARDWIRED F4 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S1 APARTMENT_LIGHTS_HARDWIRED F4 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 S2 APARTMENT_LIGHTS_HARDWIRED F4 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F4 CORRIDOR_LIGHTS_HARDWIRED F4 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
M SW APARTMENT_LIGHTS_HARDWIRED M SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NW APARTMENT_LIGHTS_HARDWIRED M NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M SE APARTMENT_LIGHTS_HARDWIRED M SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M NE APARTMENT_LIGHTS_HARDWIRED M NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N1 APARTMENT_LIGHTS_HARDWIRED M N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M N2 APARTMENT_LIGHTS_HARDWIRED M N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S1 APARTMENT_LIGHTS_HARDWIRED M S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M S2 APARTMENT_LIGHTS_HARDWIRED M S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
M CORRIDOR_LIGHTS_HARDWIRED M CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_HARDWIRED F6 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NW APARTMENT_LIGHTS_HARDWIRED F6 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 SE APARTMENT_LIGHTS_HARDWIRED F6 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 NE APARTMENT_LIGHTS_HARDWIRED F6 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N1 APARTMENT_LIGHTS_HARDWIRED F6 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 N2 APARTMENT_LIGHTS_HARDWIRED F6 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S1 APARTMENT_LIGHTS_HARDWIRED F6 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 S2 APARTMENT_LIGHTS_HARDWIRED F6 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F6 CORRIDOR_LIGHTS_HARDWIRED F6 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F7 SW APARTMENT_LIGHTS_HARDWIRED F7 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NW APARTMENT_LIGHTS_HARDWIRED F7 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 SE APARTMENT_LIGHTS_HARDWIRED F7 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 NE APARTMENT_LIGHTS_HARDWIRED F7 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N1 APARTMENT_LIGHTS_HARDWIRED F7 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 N2 APARTMENT_LIGHTS_HARDWIRED F7 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S1 APARTMENT_LIGHTS_HARDWIRED F7 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 S2 APARTMENT_LIGHTS_HARDWIRED F7 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F7 CORRIDOR_LIGHTS_HARDWIRED F7 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F8 SW APARTMENT_LIGHTS_HARDWIRED F8 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NW APARTMENT_LIGHTS_HARDWIRED F8 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 SE APARTMENT_LIGHTS_HARDWIRED F8 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 NE APARTMENT_LIGHTS_HARDWIRED F8 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N1 APARTMENT_LIGHTS_HARDWIRED F8 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 N2 APARTMENT_LIGHTS_HARDWIRED F8 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S1 APARTMENT_LIGHTS_HARDWIRED F8 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 S2 APARTMENT_LIGHTS_HARDWIRED F8 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F8 CORRIDOR_LIGHTS_HARDWIRED F8 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F9 SW APARTMENT_LIGHTS_HARDWIRED F9 SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NW APARTMENT_LIGHTS_HARDWIRED F9 NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 SE APARTMENT_LIGHTS_HARDWIRED F9 SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 NE APARTMENT_LIGHTS_HARDWIRED F9 NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N1 APARTMENT_LIGHTS_HARDWIRED F9 N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 N2 APARTMENT_LIGHTS_HARDWIRED F9 N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S1 APARTMENT_LIGHTS_HARDWIRED F9 S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 S2 APARTMENT_LIGHTS_HARDWIRED F9 S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
F9 CORRIDOR_LIGHTS_HARDWIRED F9 CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
T SW APARTMENT_LIGHTS_HARDWIRED T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NW APARTMENT_LIGHTS_HARDWIRED T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T SE APARTMENT_LIGHTS_HARDWIRED T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T NE APARTMENT_LIGHTS_HARDWIRED T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N1 APARTMENT_LIGHTS_HARDWIRED T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T N2 APARTMENT_LIGHTS_HARDWIRED T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S1 APARTMENT_LIGHTS_HARDWIRED T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T S2 APARTMENT_LIGHTS_HARDWIRED T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
T CORRIDOR_LIGHTS_HARDWIRED T CORRIDOR 6.7128 77.66 521.30 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
G SW APARTMENT_LIGHTS_PLUGIN G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G NW APARTMENT_LIGHTS_PLUGIN G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
OFFICE_LIGHTS_PLUGIN OFFICE 14.7681 88.25 1303.26 GeneralLights-plugin LTG_OFF_SCH 62.05 168.00 61.07 0.0000 Y 14.94
G NE APARTMENT_LIGHTS_PLUGIN G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N1 APARTMENT_LIGHTS_PLUGIN G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G N2 APARTMENT_LIGHTS_PLUGIN G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S1 APARTMENT_LIGHTS_PLUGIN G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
G S2 APARTMENT_LIGHTS_PLUGIN G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SW APARTMENT_LIGHTS_PLUGIN F2 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NW APARTMENT_LIGHTS_PLUGIN F2 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 SE APARTMENT_LIGHTS_PLUGIN F2 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 NE APARTMENT_LIGHTS_PLUGIN F2 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N1 APARTMENT_LIGHTS_PLUGIN F2 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 N2 APARTMENT_LIGHTS_PLUGIN F2 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S1 APARTMENT_LIGHTS_PLUGIN F2 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F2 S2 APARTMENT_LIGHTS_PLUGIN F2 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SW APARTMENT_LIGHTS_PLUGIN F3 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NW APARTMENT_LIGHTS_PLUGIN F3 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 SE APARTMENT_LIGHTS_PLUGIN F3 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 NE APARTMENT_LIGHTS_PLUGIN F3 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N1 APARTMENT_LIGHTS_PLUGIN F3 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 N2 APARTMENT_LIGHTS_PLUGIN F3 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S1 APARTMENT_LIGHTS_PLUGIN F3 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F3 S2 APARTMENT_LIGHTS_PLUGIN F3 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SW APARTMENT_LIGHTS_PLUGIN F4 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NW APARTMENT_LIGHTS_PLUGIN F4 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 SE APARTMENT_LIGHTS_PLUGIN F4 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 NE APARTMENT_LIGHTS_PLUGIN F4 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N1 APARTMENT_LIGHTS_PLUGIN F4 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 N2 APARTMENT_LIGHTS_PLUGIN F4 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S1 APARTMENT_LIGHTS_PLUGIN F4 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F4 S2 APARTMENT_LIGHTS_PLUGIN F4 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SW APARTMENT_LIGHTS_PLUGIN M SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NW APARTMENT_LIGHTS_PLUGIN M NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M SE APARTMENT_LIGHTS_PLUGIN M SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M NE APARTMENT_LIGHTS_PLUGIN M NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N1 APARTMENT_LIGHTS_PLUGIN M N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M N2 APARTMENT_LIGHTS_PLUGIN M N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S1 APARTMENT_LIGHTS_PLUGIN M S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M S2 APARTMENT_LIGHTS_PLUGIN M S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
M CORRIDOR_LIGHTS_PLUGIN M CORRIDOR 6.7128 77.66 521.30 GeneralLights-plugin LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 16.44
F6 SW APARTMENT_LIGHTS_PLUGIN F6 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NW APARTMENT_LIGHTS_PLUGIN F6 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 SE APARTMENT_LIGHTS_PLUGIN F6 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 NE APARTMENT_LIGHTS_PLUGIN F6 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N1 APARTMENT_LIGHTS_PLUGIN F6 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 N2 APARTMENT_LIGHTS_PLUGIN F6 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S1 APARTMENT_LIGHTS_PLUGIN F6 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F6 S2 APARTMENT_LIGHTS_PLUGIN F6 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SW APARTMENT_LIGHTS_PLUGIN F7 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NW APARTMENT_LIGHTS_PLUGIN F7 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 SE APARTMENT_LIGHTS_PLUGIN F7 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 NE APARTMENT_LIGHTS_PLUGIN F7 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N1 APARTMENT_LIGHTS_PLUGIN F7 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 N2 APARTMENT_LIGHTS_PLUGIN F7 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S1 APARTMENT_LIGHTS_PLUGIN F7 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F7 S2 APARTMENT_LIGHTS_PLUGIN F7 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SW APARTMENT_LIGHTS_PLUGIN F8 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NW APARTMENT_LIGHTS_PLUGIN F8 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 SE APARTMENT_LIGHTS_PLUGIN F8 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 NE APARTMENT_LIGHTS_PLUGIN F8 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N1 APARTMENT_LIGHTS_PLUGIN F8 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 N2 APARTMENT_LIGHTS_PLUGIN F8 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S1 APARTMENT_LIGHTS_PLUGIN F8 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F8 S2 APARTMENT_LIGHTS_PLUGIN F8 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SW APARTMENT_LIGHTS_PLUGIN F9 SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NW APARTMENT_LIGHTS_PLUGIN F9 NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 SE APARTMENT_LIGHTS_PLUGIN F9 SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 NE APARTMENT_LIGHTS_PLUGIN F9 NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N1 APARTMENT_LIGHTS_PLUGIN F9 N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 N2 APARTMENT_LIGHTS_PLUGIN F9 N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S1 APARTMENT_LIGHTS_PLUGIN F9 S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
F9 S2 APARTMENT_LIGHTS_PLUGIN F9 S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SW APARTMENT_LIGHTS_PLUGIN T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NW APARTMENT_LIGHTS_PLUGIN T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T SE APARTMENT_LIGHTS_PLUGIN T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T NE APARTMENT_LIGHTS_PLUGIN T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N1 APARTMENT_LIGHTS_PLUGIN T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T N2 APARTMENT_LIGHTS_PLUGIN T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S1 APARTMENT_LIGHTS_PLUGIN T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
T S2 APARTMENT_LIGHTS_PLUGIN T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.2679 14974.03 33959.19               296.56


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 10364.00 AstronomicalClock -   83.70 83.70 162.84
Exterior Lighting Total 10364.00           162.84



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 245374.47 0.75    
CENTRAL TOWER EvaporativeFluidCooler:SingleSpeed 196299.58      


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
HEAT PUMP COOLING MODE AIRLOOP G SW Coil:Cooling:WaterToAirHeatPump:EquationFit   3205.13 2086.17 1118.97 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3136.29 2042.61 1093.68 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP OFFICE Coil:Cooling:WaterToAirHeatPump:EquationFit   4571.65 2982.58 1589.07 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2235.31 1482.58 752.73 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1610.05 1060.80 549.24 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1585.74 1045.39 540.35 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   1790.21 1157.32 632.90 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP G S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   1874.97 1212.83 662.14 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4083.63 2661.66 1421.97 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3968.98 2588.31 1380.67 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3709.07 2413.66 1295.41 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2955.28 1957.90 997.37 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2120.03 1393.05 726.98 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2100.22 1380.48 719.74 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2348.56 1523.76 824.80 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F2 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2379.83 1543.73 836.10 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4099.50 2681.69 1417.81 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   3992.78 2613.32 1379.47 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3450.55 2258.26 1192.29 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   2994.18 1992.19 1001.99 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2162.96 1425.86 737.10 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2143.35 1413.40 729.95 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2398.22 1561.04 837.18 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F3 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2411.72 1569.66 842.06 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4115.74 2699.43 1416.31 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4016.31 2634.80 1381.52 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3447.95 2263.63 1184.32 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3006.86 2007.32 999.54 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2184.05 1443.42 740.64 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2164.55 1431.01 733.53 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2421.46 1580.05 841.40 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F4 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2432.36 1587.00 845.35 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4158.53 2732.71 1425.82 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4061.50 2669.53 1391.97 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3495.15 2299.51 1195.63 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3046.55 2038.40 1008.15 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2231.85 1479.05 752.80 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2212.59 1466.76 745.83 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2467.66 1613.00 854.65 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP M S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2478.17 1619.71 858.46 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4118.48 2712.30 1406.17 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4021.15 2648.90 1372.24 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3463.15 2283.91 1179.25 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3003.59 2015.76 987.83 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2196.01 1459.13 736.89 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2176.92 1446.93 729.99 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2433.36 1593.91 839.45 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F6 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2443.82 1600.59 843.23 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4108.10 2710.17 1397.93 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4011.78 2647.38 1364.40 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3459.59 2285.87 1173.72 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3006.60 2018.43 988.17 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2189.24 1457.34 731.90 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2170.27 1445.21 725.06 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2427.05 1592.38 834.66 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F7 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2437.49 1599.05 838.44 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4116.29 2719.41 1396.88 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4020.82 2657.12 1363.71 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3472.41 2297.88 1174.53 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3012.72 2026.10 986.62 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2200.53 1466.80 733.73 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2181.69 1454.75 726.94 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2437.62 1601.42 836.21 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F8 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2448.08 1608.09 839.99 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SW Coil:Cooling:WaterToAirHeatPump:EquationFit   4261.51 2815.74 1445.77 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NW Coil:Cooling:WaterToAirHeatPump:EquationFit   4163.87 2751.97 1411.91 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 SE Coil:Cooling:WaterToAirHeatPump:EquationFit   3585.82 2372.82 1213.00 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 NE Coil:Cooling:WaterToAirHeatPump:EquationFit   3068.81 2065.52 1003.29 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2326.72 1549.40 777.32 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2307.77 1537.29 770.49 0.67 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   2531.51 1663.57 867.93 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP F9 S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   2541.48 1669.94 871.54 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SW Coil:Cooling:WaterToAirHeatPump:EquationFit   5311.88 3485.44 1826.44 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NW Coil:Cooling:WaterToAirHeatPump:EquationFit   5134.82 3374.01 1760.81 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T SE Coil:Cooling:WaterToAirHeatPump:EquationFit   4586.60 3017.05 1569.55 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T NE Coil:Cooling:WaterToAirHeatPump:EquationFit   4053.30 2675.11 1378.19 0.66 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3150.60 2061.78 1088.82 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T N2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3147.08 2059.48 1087.60 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S1 Coil:Cooling:WaterToAirHeatPump:EquationFit   3656.71 2384.97 1271.74 0.65 0.00    
HEAT PUMP COOLING MODE AIRLOOP T S2 Coil:Cooling:WaterToAirHeatPump:EquationFit   3665.00 2390.23 1274.77 0.65 0.00    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
None            


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
HEAT PUMP HEATING MODE AIRLOOP G SW Coil:Heating:WaterToAirHeatPump:EquationFit   3205.13 0.00
HEAT PUMP HEATING MODE AIRLOOP G NW Coil:Heating:WaterToAirHeatPump:EquationFit   3136.29 0.00
HEAT PUMP HEATING MODE AIRLOOP OFFICE Coil:Heating:WaterToAirHeatPump:EquationFit   4571.65 0.00
HEAT PUMP HEATING MODE AIRLOOP G NE Coil:Heating:WaterToAirHeatPump:EquationFit   2235.31 0.00
HEAT PUMP HEATING MODE AIRLOOP G N1 Coil:Heating:WaterToAirHeatPump:EquationFit   1610.05 0.00
HEAT PUMP HEATING MODE AIRLOOP G N2 Coil:Heating:WaterToAirHeatPump:EquationFit   1585.74 0.00
HEAT PUMP HEATING MODE AIRLOOP G S1 Coil:Heating:WaterToAirHeatPump:EquationFit   1790.21 0.00
HEAT PUMP HEATING MODE AIRLOOP G S2 Coil:Heating:WaterToAirHeatPump:EquationFit   1874.97 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4083.63 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3968.98 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3709.07 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2955.28 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2120.03 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2100.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2348.56 0.00
HEAT PUMP HEATING MODE AIRLOOP F2 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2379.83 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4099.50 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NW Coil:Heating:WaterToAirHeatPump:EquationFit   3992.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3450.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 NE Coil:Heating:WaterToAirHeatPump:EquationFit   2994.18 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2162.96 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2143.35 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2398.22 0.00
HEAT PUMP HEATING MODE AIRLOOP F3 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2411.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4115.74 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4016.31 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3447.95 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3006.86 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2184.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2164.55 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2421.46 0.00
HEAT PUMP HEATING MODE AIRLOOP F4 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2432.36 0.00
HEAT PUMP HEATING MODE AIRLOOP M SW Coil:Heating:WaterToAirHeatPump:EquationFit   4158.53 0.00
HEAT PUMP HEATING MODE AIRLOOP M NW Coil:Heating:WaterToAirHeatPump:EquationFit   4061.50 0.00
HEAT PUMP HEATING MODE AIRLOOP M SE Coil:Heating:WaterToAirHeatPump:EquationFit   3495.15 0.00
HEAT PUMP HEATING MODE AIRLOOP M NE Coil:Heating:WaterToAirHeatPump:EquationFit   3046.55 0.00
HEAT PUMP HEATING MODE AIRLOOP M N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2231.85 0.00
HEAT PUMP HEATING MODE AIRLOOP M N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2212.59 0.00
HEAT PUMP HEATING MODE AIRLOOP M S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2467.66 0.00
HEAT PUMP HEATING MODE AIRLOOP M S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2478.17 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4118.48 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4021.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3463.15 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3003.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2196.01 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2176.92 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2433.36 0.00
HEAT PUMP HEATING MODE AIRLOOP F6 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2443.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4108.10 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4011.78 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3459.59 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3006.60 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2189.24 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2170.27 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2427.05 0.00
HEAT PUMP HEATING MODE AIRLOOP F7 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2437.49 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4116.29 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4020.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3472.41 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3012.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2200.53 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2181.69 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2437.62 0.00
HEAT PUMP HEATING MODE AIRLOOP F8 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2448.08 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SW Coil:Heating:WaterToAirHeatPump:EquationFit   4261.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NW Coil:Heating:WaterToAirHeatPump:EquationFit   4163.87 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 SE Coil:Heating:WaterToAirHeatPump:EquationFit   3585.82 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 NE Coil:Heating:WaterToAirHeatPump:EquationFit   3068.81 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N1 Coil:Heating:WaterToAirHeatPump:EquationFit   2326.72 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 N2 Coil:Heating:WaterToAirHeatPump:EquationFit   2307.77 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S1 Coil:Heating:WaterToAirHeatPump:EquationFit   2531.51 0.00
HEAT PUMP HEATING MODE AIRLOOP F9 S2 Coil:Heating:WaterToAirHeatPump:EquationFit   2541.48 0.00
HEAT PUMP HEATING MODE AIRLOOP T SW Coil:Heating:WaterToAirHeatPump:EquationFit   5311.88 0.00
HEAT PUMP HEATING MODE AIRLOOP T NW Coil:Heating:WaterToAirHeatPump:EquationFit   5134.82 0.00
HEAT PUMP HEATING MODE AIRLOOP T SE Coil:Heating:WaterToAirHeatPump:EquationFit   4586.60 0.00
HEAT PUMP HEATING MODE AIRLOOP T NE Coil:Heating:WaterToAirHeatPump:EquationFit   4053.30 0.00
HEAT PUMP HEATING MODE AIRLOOP T N1 Coil:Heating:WaterToAirHeatPump:EquationFit   3150.60 0.00
HEAT PUMP HEATING MODE AIRLOOP T N2 Coil:Heating:WaterToAirHeatPump:EquationFit   3147.08 0.00
HEAT PUMP HEATING MODE AIRLOOP T S1 Coil:Heating:WaterToAirHeatPump:EquationFit   3656.71 0.00
HEAT PUMP HEATING MODE AIRLOOP T S2 Coil:Heating:WaterToAirHeatPump:EquationFit   3665.00 0.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW Coil:Heating:Electric   2756.67 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW Coil:Heating:Electric   2757.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE Coil:Heating:Electric   3460.54 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE Coil:Heating:Electric   2757.08 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 Coil:Heating:Electric   2051.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 Coil:Heating:Electric   2051.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 Coil:Heating:Electric   2047.88 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 Coil:Heating:Electric   2054.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW Coil:Heating:Electric   2735.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW Coil:Heating:Electric   2733.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE Coil:Heating:Electric   2754.50 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE Coil:Heating:Electric   2733.39 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 Coil:Heating:Electric   1854.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 Coil:Heating:Electric   1854.16 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 Coil:Heating:Electric   1859.28 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 Coil:Heating:Electric   1860.51 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW Coil:Heating:Electric   2759.41 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW Coil:Heating:Electric   2759.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE Coil:Heating:Electric   2761.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE Coil:Heating:Electric   2759.94 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 Coil:Heating:Electric   1835.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 Coil:Heating:Electric   1835.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 Coil:Heating:Electric   1835.99 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 Coil:Heating:Electric   1836.18 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW Coil:Heating:Electric   2823.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW Coil:Heating:Electric   2826.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE Coil:Heating:Electric   2824.06 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE Coil:Heating:Electric   2826.48 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 Coil:Heating:Electric   1866.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 Coil:Heating:Electric   1866.24 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 Coil:Heating:Electric   1864.05 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 Coil:Heating:Electric   1864.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW Coil:Heating:Electric   2864.82 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW Coil:Heating:Electric   2867.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE Coil:Heating:Electric   2864.84 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE Coil:Heating:Electric   2867.93 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 Coil:Heating:Electric   1879.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 Coil:Heating:Electric   1879.85 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 Coil:Heating:Electric   1877.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 Coil:Heating:Electric   1877.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW Coil:Heating:Electric   2960.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW Coil:Heating:Electric   2965.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE Coil:Heating:Electric   2960.79 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE Coil:Heating:Electric   2965.87 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 Coil:Heating:Electric   1951.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 Coil:Heating:Electric   1951.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 Coil:Heating:Electric   1946.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 Coil:Heating:Electric   1946.32 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW Coil:Heating:Electric   3029.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW Coil:Heating:Electric   3035.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE Coil:Heating:Electric   3029.36 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE Coil:Heating:Electric   3035.21 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 Coil:Heating:Electric   1998.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 Coil:Heating:Electric   1998.43 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 Coil:Heating:Electric   1992.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 Coil:Heating:Electric   1992.91 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW Coil:Heating:Electric   3100.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW Coil:Heating:Electric   3106.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE Coil:Heating:Electric   3100.69 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE Coil:Heating:Electric   3106.95 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 Coil:Heating:Electric   2050.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 Coil:Heating:Electric   2050.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 Coil:Heating:Electric   2044.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 Coil:Heating:Electric   2044.75 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW Coil:Heating:Electric   3289.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW Coil:Heating:Electric   3294.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE Coil:Heating:Electric   3289.74 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE Coil:Heating:Electric   3294.09 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 Coil:Heating:Electric   2212.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 Coil:Heating:Electric   2212.13 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 Coil:Heating:Electric   2207.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 Coil:Heating:Electric   2207.63 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW Coil:Heating:Electric   3902.78 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW Coil:Heating:Electric   3913.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE Coil:Heating:Electric   3902.78 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE Coil:Heating:Electric   3913.70 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 Coil:Heating:Electric   2870.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 Coil:Heating:Electric   2870.02 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 Coil:Heating:Electric   2856.07 1.00
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 Coil:Heating:Electric   2856.07 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
AIRLOOP G SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 303.98 1160.84 1.00 General
AIRLOOP G NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 298.33 1160.84 1.00 General
AIRLOOP OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 435.55 1160.84 1.00 General
AIRLOOP G NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 216.78 1160.84 1.00 General
AIRLOOP G N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 152.66 1160.84 1.00 General
AIRLOOP G N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 150.36 1160.84 1.00 General
AIRLOOP G S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 161.32 1160.84 1.00 General
AIRLOOP G S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 169.83 1160.84 1.00 General
AIRLOOP F2 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 390.99 1160.84 1.00 General
AIRLOOP F2 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 380.85 1160.84 1.00 General
AIRLOOP F2 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 350.77 1160.84 1.00 General
AIRLOOP F2 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 288.82 1160.84 1.00 General
AIRLOOP F2 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 202.70 1160.84 1.00 General
AIRLOOP F2 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 200.82 1160.84 1.00 General
AIRLOOP F2 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 216.40 1160.84 1.00 General
AIRLOOP F2 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 219.38 1160.84 1.00 General
AIRLOOP F3 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 394.52 1160.84 1.00 General
AIRLOOP F3 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 385.13 1160.84 1.00 General
AIRLOOP F3 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 328.02 1160.84 1.00 General
AIRLOOP F3 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 294.45 1160.84 1.00 General
AIRLOOP F3 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 207.90 1160.84 1.00 General
AIRLOOP F3 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 206.04 1160.84 1.00 General
AIRLOOP F3 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 222.26 1160.84 1.00 General
AIRLOOP F3 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 223.55 1160.84 1.00 General
AIRLOOP F4 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 397.57 1160.84 1.00 General
AIRLOOP F4 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 388.26 1160.84 1.00 General
AIRLOOP F4 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 329.20 1160.84 1.00 General
AIRLOOP F4 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 297.09 1160.84 1.00 General
AIRLOOP F4 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 210.74 1160.84 1.00 General
AIRLOOP F4 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 208.89 1160.84 1.00 General
AIRLOOP F4 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 225.32 1160.84 1.00 General
AIRLOOP F4 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 226.36 1160.84 1.00 General
AIRLOOP M SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 402.88 1160.84 1.00 General
AIRLOOP M NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 393.78 1160.84 1.00 General
AIRLOOP M SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 334.88 1160.84 1.00 General
AIRLOOP M NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 302.05 1160.84 1.00 General
AIRLOOP M N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 215.73 1160.84 1.00 General
AIRLOOP M N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 213.89 1160.84 1.00 General
AIRLOOP M S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 230.42 1160.84 1.00 General
AIRLOOP M S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 231.42 1160.84 1.00 General
AIRLOOP F6 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 400.09 1160.84 1.00 General
AIRLOOP F6 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 390.96 1160.84 1.00 General
AIRLOOP F6 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 332.80 1160.84 1.00 General
AIRLOOP F6 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 298.90 1160.84 1.00 General
AIRLOOP F6 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 212.90 1160.84 1.00 General
AIRLOOP F6 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 211.07 1160.84 1.00 General
AIRLOOP F6 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 227.72 1160.84 1.00 General
AIRLOOP F6 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 228.72 1160.84 1.00 General
AIRLOOP F7 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 400.01 1160.84 1.00 General
AIRLOOP F7 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 390.97 1160.84 1.00 General
AIRLOOP F7 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 333.32 1160.84 1.00 General
AIRLOOP F7 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 298.70 1160.84 1.00 General
AIRLOOP F7 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 212.77 1160.84 1.00 General
AIRLOOP F7 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 210.95 1160.84 1.00 General
AIRLOOP F7 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 227.62 1160.84 1.00 General
AIRLOOP F7 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 228.62 1160.84 1.00 General
AIRLOOP F8 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 401.61 1160.84 1.00 General
AIRLOOP F8 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 392.64 1160.84 1.00 General
AIRLOOP F8 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 335.32 1160.84 1.00 General
AIRLOOP F8 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 300.04 1160.84 1.00 General
AIRLOOP F8 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 214.30 1160.84 1.00 General
AIRLOOP F8 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 212.50 1160.84 1.00 General
AIRLOOP F8 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 229.09 1160.84 1.00 General
AIRLOOP F8 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 230.09 1160.84 1.00 General
AIRLOOP F9 SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 416.24 1160.84 1.00 General
AIRLOOP F9 NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 407.04 1160.84 1.00 General
AIRLOOP F9 SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 346.46 1160.84 1.00 General
AIRLOOP F9 NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 306.14 1160.84 1.00 General
AIRLOOP F9 N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 226.77 1160.84 1.00 General
AIRLOOP F9 N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 224.96 1160.84 1.00 General
AIRLOOP F9 S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 238.49 1160.84 1.00 General
AIRLOOP F9 S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 239.44 1160.84 1.00 General
AIRLOOP T SW SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 515.11 1160.84 1.00 General
AIRLOOP T NW SUPPLY FAN Fan:OnOff 0.54 622.50 0.43 499.19 1160.84 1.00 General
AIRLOOP T SE SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 443.45 1160.84 1.00 General
AIRLOOP T NE SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 391.93 1160.84 1.00 General
AIRLOOP T N1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 298.16 1160.84 1.00 General
AIRLOOP T N2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 297.81 1160.84 1.00 General
AIRLOOP T S1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 346.52 1160.84 1.00 General
AIRLOOP T S2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 347.31 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0003 36.93 127739.32 0.30
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 224180.02 0.0053 1704.37 319344.75 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.64 0.80 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2292.11 2750.53 0.218 0.262 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
G NW APARTMENT 2249.44 2699.33 0.214 0.257 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.20 0.00565
OFFICE 3284.21 3941.05 0.313 0.375 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 32.33 0.00565
G NE APARTMENT 1634.58 1961.49 0.156 0.187 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
G N1 APARTMENT 1151.06 1381.28 0.110 0.132 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
G N2 APARTMENT 1133.75 1360.50 0.108 0.130 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
G S1 APARTMENT 1216.40 1459.69 0.116 0.139 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
G S2 APARTMENT 1280.52 1536.62 0.122 0.146 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F2 SW APARTMENT 2948.19 3537.83 0.281 0.337 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F2 NW APARTMENT 2871.74 3446.09 0.273 0.328 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.20 0.00565
F2 SE APARTMENT 2644.93 3173.92 0.252 0.302 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F2 NE APARTMENT 2177.79 2613.34 0.207 0.249 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
F2 N1 APARTMENT 1528.39 1834.07 0.146 0.175 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F2 N2 APARTMENT 1514.23 1817.08 0.144 0.173 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F2 S1 APARTMENT 1631.72 1958.06 0.155 0.186 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F2 S2 APARTMENT 1654.17 1985.01 0.157 0.189 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F3 SW APARTMENT 2974.84 3569.81 0.283 0.340 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F3 NW APARTMENT 2903.99 3484.79 0.276 0.332 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 32.20 0.00565
F3 SE APARTMENT 2473.46 2968.15 0.235 0.283 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F3 NE APARTMENT 2220.30 2664.36 0.211 0.254 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
F3 N1 APARTMENT 1567.60 1881.12 0.149 0.179 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F3 N2 APARTMENT 1553.56 1864.27 0.148 0.177 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F3 S1 APARTMENT 1675.91 2011.09 0.160 0.191 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F3 S2 APARTMENT 1685.59 2022.71 0.160 0.193 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F4 SW APARTMENT 2997.87 3597.45 0.285 0.342 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F4 NW APARTMENT 2927.62 3513.15 0.279 0.334 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
F4 SE APARTMENT 2482.35 2978.82 0.236 0.284 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F4 NE APARTMENT 2240.20 2688.24 0.213 0.256 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
F4 N1 APARTMENT 1589.05 1906.86 0.151 0.182 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F4 N2 APARTMENT 1575.07 1890.08 0.150 0.180 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
F4 S1 APARTMENT 1698.98 2038.77 0.162 0.194 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F4 S2 APARTMENT 1706.80 2048.15 0.162 0.195 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
M SW APARTMENT 3037.90 3645.49 0.289 0.347 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
M NW APARTMENT 2969.25 3563.10 0.283 0.339 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
M SE APARTMENT 2525.17 3030.20 0.240 0.288 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
M NE APARTMENT 2277.62 2733.14 0.217 0.260 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
M N1 APARTMENT 1626.62 1951.95 0.155 0.186 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
M N2 APARTMENT 1612.75 1935.30 0.154 0.184 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
M S1 APARTMENT 1737.45 2084.94 0.165 0.198 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
M S2 APARTMENT 1744.99 2093.99 0.166 0.199 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F6 SW APARTMENT 3016.92 3620.31 0.287 0.345 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F6 NW APARTMENT 2948.01 3537.61 0.281 0.337 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
F6 SE APARTMENT 2509.49 3011.39 0.239 0.287 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F6 NE APARTMENT 2253.92 2704.70 0.215 0.257 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 30.98 0.00565
F6 N1 APARTMENT 1605.31 1926.38 0.153 0.183 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F6 N2 APARTMENT 1591.54 1909.85 0.152 0.182 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F6 S1 APARTMENT 1717.10 2060.51 0.163 0.196 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F6 S2 APARTMENT 1724.61 2069.53 0.164 0.197 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F7 SW APARTMENT 3016.32 3619.58 0.287 0.345 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F7 NW APARTMENT 2948.08 3537.69 0.281 0.337 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
F7 SE APARTMENT 2513.41 3016.10 0.239 0.287 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F7 NE APARTMENT 2252.36 2702.83 0.214 0.257 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.49 0.00565
F7 N1 APARTMENT 1604.30 1925.16 0.153 0.183 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F7 N2 APARTMENT 1590.60 1908.73 0.151 0.182 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F7 S1 APARTMENT 1716.38 2059.65 0.163 0.196 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F7 S2 APARTMENT 1723.88 2068.65 0.164 0.197 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F8 SW APARTMENT 3028.37 3634.05 0.288 0.346 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F8 NW APARTMENT 2960.67 3552.81 0.282 0.338 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
F8 SE APARTMENT 2528.49 3034.19 0.241 0.289 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
F8 NE APARTMENT 2262.52 2715.02 0.215 0.258 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.49 0.00565
F8 N1 APARTMENT 1615.88 1939.05 0.154 0.185 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F8 N2 APARTMENT 1602.27 1922.72 0.153 0.183 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F8 S1 APARTMENT 1727.46 2072.95 0.164 0.197 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F8 S2 APARTMENT 1734.97 2081.96 0.165 0.198 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F9 SW APARTMENT 3138.72 3766.46 0.299 0.359 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
F9 NW APARTMENT 3069.31 3683.17 0.292 0.351 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.54 0.00565
F9 SE APARTMENT 2612.55 3135.06 0.249 0.298 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
F9 NE APARTMENT 2308.50 2770.20 0.220 0.264 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.49 0.00565
F9 N1 APARTMENT 1709.93 2051.92 0.163 0.195 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F9 N2 APARTMENT 1696.24 2035.49 0.161 0.194 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
F9 S1 APARTMENT 1798.31 2157.97 0.171 0.205 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565
F9 S2 APARTMENT 1805.47 2166.57 0.172 0.206 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565
T SW APARTMENT 3884.29 4661.15 0.370 0.444 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 34.02 0.00565
T NW APARTMENT 3764.25 4517.10 0.358 0.430 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.48 0.00565
T SE APARTMENT 3343.92 4012.70 0.318 0.382 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
T NE APARTMENT 2955.44 3546.53 0.281 0.338 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
T N1 APARTMENT 2248.24 2697.89 0.214 0.257 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
T N2 APARTMENT 2245.64 2694.76 0.214 0.257 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
T S1 APARTMENT 2612.92 3135.50 0.249 0.299 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
T S2 APARTMENT 2618.84 3142.61 0.249 0.299 ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1684.68 2021.62 0.091 0.109 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G NW APARTMENT 1685.03 2022.04 0.091 0.109 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
OFFICE 1977.23 2372.68 0.107 0.128 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -7.90 0.00234
G NE APARTMENT 1685.03 2022.04 0.091 0.109 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G N1 APARTMENT 1088.63 1306.36 0.059 0.071 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G N2 APARTMENT 1088.63 1306.36 0.059 0.071 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G S1 APARTMENT 1085.28 1302.34 0.059 0.070 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
G S2 APARTMENT 1090.60 1308.72 0.059 0.071 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
F2 SW APARTMENT 1667.05 2000.46 0.090 0.108 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 NW APARTMENT 1665.02 1998.03 0.090 0.108 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 SE APARTMENT 1682.87 2019.45 0.091 0.109 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 NE APARTMENT 1665.02 1998.03 0.090 0.108 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 N1 APARTMENT 921.48 1105.78 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 N2 APARTMENT 921.48 1105.78 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 S1 APARTMENT 925.81 1110.97 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F2 S2 APARTMENT 926.85 1112.22 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 SW APARTMENT 1687.03 2024.44 0.091 0.110 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 NW APARTMENT 1687.48 2024.98 0.091 0.110 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 SE APARTMENT 1688.78 2026.54 0.091 0.110 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 NE APARTMENT 1687.48 2024.98 0.091 0.110 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 N1 APARTMENT 905.95 1087.14 0.049 0.059 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 N2 APARTMENT 905.95 1087.14 0.049 0.059 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 S1 APARTMENT 906.12 1087.35 0.049 0.059 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F3 S2 APARTMENT 906.28 1087.54 0.049 0.059 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 SW APARTMENT 1741.53 2089.83 0.094 0.113 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 NW APARTMENT 1743.75 2092.50 0.094 0.113 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 SE APARTMENT 1741.71 2090.05 0.094 0.113 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 NE APARTMENT 1743.75 2092.50 0.094 0.113 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 N1 APARTMENT 931.71 1118.05 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 N2 APARTMENT 931.71 1118.05 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 S1 APARTMENT 929.85 1115.82 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F4 S2 APARTMENT 929.87 1115.85 0.050 0.060 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M SW APARTMENT 1776.18 2131.42 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M NW APARTMENT 1778.81 2134.58 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M SE APARTMENT 1776.20 2131.44 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M NE APARTMENT 1778.81 2134.58 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M N1 APARTMENT 943.22 1131.87 0.051 0.061 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M N2 APARTMENT 943.22 1131.87 0.051 0.061 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M S1 APARTMENT 940.91 1129.10 0.051 0.061 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
M S2 APARTMENT 940.92 1129.10 0.051 0.061 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 SW APARTMENT 1857.34 2228.81 0.100 0.121 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 NW APARTMENT 1861.64 2233.97 0.101 0.121 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 SE APARTMENT 1857.34 2228.81 0.100 0.121 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 NE APARTMENT 1861.64 2233.97 0.101 0.121 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 N1 APARTMENT 1003.45 1204.14 0.054 0.065 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 N2 APARTMENT 1003.45 1204.14 0.054 0.065 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 S1 APARTMENT 999.43 1199.31 0.054 0.065 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F6 S2 APARTMENT 999.43 1199.32 0.054 0.065 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 SW APARTMENT 1915.33 2298.40 0.104 0.124 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 NW APARTMENT 1920.28 2304.33 0.104 0.125 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 SE APARTMENT 1915.33 2298.40 0.104 0.124 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 NE APARTMENT 1920.28 2304.33 0.104 0.125 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 N1 APARTMENT 1043.50 1252.21 0.056 0.068 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 N2 APARTMENT 1043.50 1252.21 0.056 0.068 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 S1 APARTMENT 1038.83 1246.60 0.056 0.067 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F7 S2 APARTMENT 1038.83 1246.60 0.056 0.067 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 SW APARTMENT 1975.66 2370.79 0.107 0.128 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 NW APARTMENT 1980.95 2377.14 0.107 0.129 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 SE APARTMENT 1975.66 2370.79 0.107 0.128 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 NE APARTMENT 1980.95 2377.14 0.107 0.129 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 N1 APARTMENT 1087.70 1305.25 0.059 0.071 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 N2 APARTMENT 1087.70 1305.25 0.059 0.071 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 S1 APARTMENT 1082.67 1299.20 0.059 0.070 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F8 S2 APARTMENT 1082.67 1299.20 0.059 0.070 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 SW APARTMENT 2135.53 2562.63 0.116 0.139 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 NW APARTMENT 2139.21 2567.05 0.116 0.139 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 SE APARTMENT 2135.53 2562.63 0.116 0.139 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 NE APARTMENT 2139.21 2567.05 0.116 0.139 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 N1 APARTMENT 1224.22 1469.07 0.066 0.079 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 N2 APARTMENT 1224.22 1469.07 0.066 0.079 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 S1 APARTMENT 1220.41 1464.49 0.066 0.079 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
F9 S2 APARTMENT 1220.41 1464.49 0.066 0.079 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T SW APARTMENT 2653.95 3184.74 0.144 0.172 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T NW APARTMENT 2663.19 3195.83 0.144 0.173 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T SE APARTMENT 2653.95 3184.74 0.144 0.172 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T NE APARTMENT 2663.19 3195.83 0.144 0.173 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T N1 APARTMENT 1780.57 2136.68 0.096 0.116 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T N2 APARTMENT 1780.57 2136.68 0.096 0.116 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T S1 APARTMENT 1768.78 2122.53 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
T S2 APARTMENT 1768.78 2122.53 0.096 0.115 ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AIRLOOP G SW 0.26 0.26 0.11 0.11
AIRLOOP G NW 0.26 0.26 0.11 0.11
AIRLOOP OFFICE 0.38 0.38 0.13 0.13
AIRLOOP G NE 0.19 0.19 0.11 0.11
AIRLOOP G N1 0.13 0.13 0.07 0.07
AIRLOOP G N2 0.13 0.13 0.07 0.07
AIRLOOP G S1 0.14 0.14 0.07 0.07
AIRLOOP G S2 0.15 0.15 0.07 0.07
AIRLOOP F2 SW 0.34 0.34 0.11 0.11
AIRLOOP F2 NW 0.33 0.33 0.11 0.11
AIRLOOP F2 SE 0.30 0.30 0.11 0.11
AIRLOOP F2 NE 0.25 0.25 0.11 0.11
AIRLOOP F2 N1 0.17 0.17 0.06 0.06
AIRLOOP F2 N2 0.17 0.17 0.06 0.06
AIRLOOP F2 S1 0.19 0.19 0.06 0.06
AIRLOOP F2 S2 0.19 0.19 0.06 0.06
AIRLOOP F3 SW 0.34 0.34 0.11 0.11
AIRLOOP F3 NW 0.33 0.33 0.11 0.11
AIRLOOP F3 SE 0.28 0.28 0.11 0.11
AIRLOOP F3 NE 0.25 0.25 0.11 0.11
AIRLOOP F3 N1 0.18 0.18 0.06 0.06
AIRLOOP F3 N2 0.18 0.18 0.06 0.06
AIRLOOP F3 S1 0.19 0.19 0.06 0.06
AIRLOOP F3 S2 0.19 0.19 0.06 0.06
AIRLOOP F4 SW 0.34 0.34 0.11 0.11
AIRLOOP F4 NW 0.33 0.33 0.11 0.11
AIRLOOP F4 SE 0.28 0.28 0.11 0.11
AIRLOOP F4 NE 0.26 0.26 0.11 0.11
AIRLOOP F4 N1 0.18 0.18 0.06 0.06
AIRLOOP F4 N2 0.18 0.18 0.06 0.06
AIRLOOP F4 S1 0.19 0.19 0.06 0.06
AIRLOOP F4 S2 0.19 0.19 0.06 0.06
AIRLOOP M SW 0.35 0.35 0.12 0.12
AIRLOOP M NW 0.34 0.34 0.12 0.12
AIRLOOP M SE 0.29 0.29 0.12 0.12
AIRLOOP M NE 0.26 0.26 0.12 0.12
AIRLOOP M N1 0.19 0.19 0.06 0.06
AIRLOOP M N2 0.18 0.18 0.06 0.06
AIRLOOP M S1 0.20 0.20 0.06 0.06
AIRLOOP M S2 0.20 0.20 0.06 0.06
AIRLOOP F6 SW 0.34 0.34 0.12 0.12
AIRLOOP F6 NW 0.34 0.34 0.12 0.12
AIRLOOP F6 SE 0.29 0.29 0.12 0.12
AIRLOOP F6 NE 0.26 0.26 0.12 0.12
AIRLOOP F6 N1 0.18 0.18 0.07 0.07
AIRLOOP F6 N2 0.18 0.18 0.07 0.07
AIRLOOP F6 S1 0.20 0.20 0.06 0.06
AIRLOOP F6 S2 0.20 0.20 0.06 0.06
AIRLOOP F7 SW 0.34 0.34 0.12 0.12
AIRLOOP F7 NW 0.34 0.34 0.12 0.12
AIRLOOP F7 SE 0.29 0.29 0.12 0.12
AIRLOOP F7 NE 0.26 0.26 0.12 0.12
AIRLOOP F7 N1 0.18 0.18 0.07 0.07
AIRLOOP F7 N2 0.18 0.18 0.07 0.07
AIRLOOP F7 S1 0.20 0.20 0.07 0.07
AIRLOOP F7 S2 0.20 0.20 0.07 0.07
AIRLOOP F8 SW 0.35 0.35 0.13 0.13
AIRLOOP F8 NW 0.34 0.34 0.13 0.13
AIRLOOP F8 SE 0.29 0.29 0.13 0.13
AIRLOOP F8 NE 0.26 0.26 0.13 0.13
AIRLOOP F8 N1 0.18 0.18 0.07 0.07
AIRLOOP F8 N2 0.18 0.18 0.07 0.07
AIRLOOP F8 S1 0.20 0.20 0.07 0.07
AIRLOOP F8 S2 0.20 0.20 0.07 0.07
AIRLOOP F9 SW 0.36 0.36 0.14 0.14
AIRLOOP F9 NW 0.35 0.35 0.14 0.14
AIRLOOP F9 SE 0.30 0.30 0.14 0.14
AIRLOOP F9 NE 0.26 0.26 0.14 0.14
AIRLOOP F9 N1 0.20 0.20 0.08 0.08
AIRLOOP F9 N2 0.19 0.19 0.08 0.08
AIRLOOP F9 S1 0.21 0.21 0.08 0.08
AIRLOOP F9 S2 0.21 0.21 0.08 0.08
AIRLOOP T SW 0.44 0.44 0.17 0.17
AIRLOOP T NW 0.43 0.43 0.17 0.17
AIRLOOP T SE 0.38 0.38 0.17 0.17
AIRLOOP T NE 0.34 0.34 0.17 0.17
AIRLOOP T N1 0.26 0.26 0.12 0.12
AIRLOOP T N2 0.26 0.26 0.12 0.12
AIRLOOP T S1 0.30 0.30 0.11 0.11
AIRLOOP T S2 0.30 0.30 0.11 0.11



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2766.50 4951.50 328.50
G NW APARTMENT 2687.75 5884.25 549.00
OFFICE 991.25 437.00 1.00
G NE APARTMENT 2787.75 5852.50 595.50
G N1 APARTMENT 2355.00 6238.50 496.50
G N2 APARTMENT 2358.00 6234.00 496.25
G S1 APARTMENT 2603.75 5303.00 381.00
G S2 APARTMENT 2644.75 5197.25 368.50
F2 SW APARTMENT 3483.75 3349.75 173.00
F2 NW APARTMENT 2992.25 5016.00 248.00
F2 SE APARTMENT 3680.25 3042.25 135.25
F2 NE APARTMENT 3115.50 4995.50 281.75
F2 N1 APARTMENT 2757.25 5379.50 290.50
F2 N2 APARTMENT 2764.25 5372.25 289.00
F2 S1 APARTMENT 3381.25 3237.25 225.75
F2 S2 APARTMENT 3408.75 3183.25 221.50
F3 SW APARTMENT 3605.25 3080.50 172.00
F3 NW APARTMENT 3047.50 4842.25 229.75
F3 SE APARTMENT 3673.75 3041.75 153.50
F3 NE APARTMENT 3162.25 4827.50 254.00
F3 N1 APARTMENT 2845.25 5115.50 263.25
F3 N2 APARTMENT 2851.25 5114.75 262.50
F3 S1 APARTMENT 3587.50 2769.00 210.25
F3 S2 APARTMENT 3598.50 2748.00 207.75
F4 SW APARTMENT 3606.75 3095.50 176.00
F4 NW APARTMENT 3058.50 4822.50 234.00
F4 SE APARTMENT 3657.00 3096.25 164.25
F4 NE APARTMENT 3167.25 4805.75 257.75
F4 N1 APARTMENT 2868.00 5050.50 259.75
F4 N2 APARTMENT 2872.50 5048.75 259.75
F4 S1 APARTMENT 3626.00 2711.75 212.50
F4 S2 APARTMENT 3629.25 2705.75 210.25
M SW APARTMENT 3591.00 3124.00 176.50
M NW APARTMENT 3062.25 4826.50 232.00
M SE APARTMENT 3641.00 3125.25 165.00
M NE APARTMENT 3166.50 4809.75 253.75
M N1 APARTMENT 2882.75 5029.00 254.00
M N2 APARTMENT 2888.00 5026.25 253.25
M S1 APARTMENT 3619.50 2714.75 206.25
M S2 APARTMENT 3626.75 2714.75 204.75
F6 SW APARTMENT 3487.50 3320.00 189.75
F6 NW APARTMENT 3010.00 4925.50 256.25
F6 SE APARTMENT 3544.75 3303.25 175.00
F6 NE APARTMENT 3109.75 4913.25 279.50
F6 N1 APARTMENT 2817.75 5129.50 266.25
F6 N2 APARTMENT 2824.00 5127.25 266.75
F6 S1 APARTMENT 3489.25 2948.25 225.50
F6 S2 APARTMENT 3496.25 2945.00 223.50
F7 SW APARTMENT 3421.50 3467.00 193.75
F7 NW APARTMENT 2984.75 4983.75 272.75
F7 SE APARTMENT 3490.25 3430.75 183.75
F7 NE APARTMENT 3090.75 4982.00 298.50
F7 N1 APARTMENT 2783.25 5197.50 274.50
F7 N2 APARTMENT 2791.50 5194.00 274.50
F7 S1 APARTMENT 3420.25 3115.75 232.00
F7 S2 APARTMENT 3422.75 3112.25 229.75
F8 SW APARTMENT 3366.00 3577.75 198.50
F8 NW APARTMENT 2969.75 5032.25 284.50
F8 SE APARTMENT 3436.00 3537.00 189.75
F8 NE APARTMENT 3082.50 5031.25 316.50
F8 N1 APARTMENT 2759.75 5243.00 277.00
F8 N2 APARTMENT 2766.25 5242.75 277.25
F8 S1 APARTMENT 3349.50 3271.00 234.50
F8 S2 APARTMENT 3356.75 3264.75 233.00
F9 SW APARTMENT 3307.25 3735.25 205.25
F9 NW APARTMENT 2989.00 5079.75 323.75
F9 SE APARTMENT 3362.75 3669.75 196.00
F9 NE APARTMENT 3098.50 5082.75 362.25
F9 N1 APARTMENT 2750.50 5278.75 277.75
F9 N2 APARTMENT 2756.75 5274.25 277.00
F9 S1 APARTMENT 3243.25 3484.00 227.50
F9 S2 APARTMENT 3249.25 3476.00 225.75
T SW APARTMENT 3896.00 4207.75 564.00
T NW APARTMENT 3555.75 5235.50 1005.00
T SE APARTMENT 3991.75 4113.75 580.25
T NE APARTMENT 3653.75 5205.25 1022.50
T N1 APARTMENT 3008.75 5420.00 625.75
T N2 APARTMENT 3017.00 5409.75 628.00
T S1 APARTMENT 3563.00 4045.25 333.75
T S2 APARTMENT 3575.75 4039.00 333.25
G CORRIDOR 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00
Facility 5288.25 6395.00 1341.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 2.25 58.50 2.25 58.50
G NW APARTMENT 0.25 44.25 0.25 44.25
OFFICE 3.75 41.25 0.00 41.00
G NE APARTMENT 2.25 89.75 2.25 89.75
G N1 APARTMENT 7.25 71.00 7.25 71.00
G N2 APARTMENT 5.75 75.25 5.75 75.25
G S1 APARTMENT 1.00 212.25 1.00 212.25
G S2 APARTMENT 1.00 170.75 1.00 170.75
F2 SW APARTMENT 0.50 64.50 0.50 64.50
F2 NW APARTMENT 0.00 43.25 0.00 43.25
F2 SE APARTMENT 0.25 40.25 0.25 40.25
F2 NE APARTMENT 0.50 104.25 0.50 104.25
F2 N1 APARTMENT 4.50 63.75 4.50 63.75
F2 N2 APARTMENT 5.75 68.75 5.75 68.75
F2 S1 APARTMENT 0.25 238.50 0.25 238.50
F2 S2 APARTMENT 0.50 217.00 0.50 217.00
F3 SW APARTMENT 0.25 85.25 0.25 85.25
F3 NW APARTMENT 0.00 51.00 0.00 51.00
F3 SE APARTMENT 0.25 108.25 0.25 108.25
F3 NE APARTMENT 0.50 120.25 0.50 120.25
F3 N1 APARTMENT 4.00 82.00 4.00 82.00
F3 N2 APARTMENT 4.50 87.25 4.50 87.25
F3 S1 APARTMENT 1.25 276.00 1.25 276.00
F3 S2 APARTMENT 0.50 268.25 0.50 268.25
F4 SW APARTMENT 0.75 92.25 0.75 92.25
F4 NW APARTMENT 0.00 53.25 0.00 53.25
F4 SE APARTMENT 0.50 121.50 0.50 121.50
F4 NE APARTMENT 1.50 134.25 1.50 134.25
F4 N1 APARTMENT 5.75 90.25 5.75 90.25
F4 N2 APARTMENT 4.00 97.25 4.00 97.25
F4 S1 APARTMENT 0.25 290.00 0.25 290.00
F4 S2 APARTMENT 0.00 281.75 0.00 281.75
M SW APARTMENT 0.50 95.00 0.50 95.00
M NW APARTMENT 0.00 55.25 0.00 55.25
M SE APARTMENT 0.50 123.75 0.50 123.75
M NE APARTMENT 0.25 141.00 0.25 141.00
M N1 APARTMENT 5.75 92.75 5.75 92.75
M N2 APARTMENT 5.00 101.00 5.00 101.00
M S1 APARTMENT 0.50 287.00 0.50 287.00
M S2 APARTMENT 0.75 277.75 0.75 277.75
F6 SW APARTMENT 0.25 96.00 0.25 96.00
F6 NW APARTMENT 0.00 58.00 0.00 58.00
F6 SE APARTMENT 1.00 124.50 1.00 124.50
F6 NE APARTMENT 0.75 149.00 0.75 149.00
F6 N1 APARTMENT 5.50 100.50 5.50 100.50
F6 N2 APARTMENT 4.75 109.00 4.75 109.00
F6 S1 APARTMENT 1.00 280.75 1.00 280.75
F6 S2 APARTMENT 0.50 272.00 0.50 272.00
F7 SW APARTMENT 0.25 97.25 0.25 97.25
F7 NW APARTMENT 0.00 60.00 0.00 60.00
F7 SE APARTMENT 0.50 124.50 0.50 124.50
F7 NE APARTMENT 1.00 148.50 1.00 148.50
F7 N1 APARTMENT 4.00 105.00 4.00 105.00
F7 N2 APARTMENT 5.00 113.75 5.00 113.75
F7 S1 APARTMENT 1.00 270.50 1.00 270.50
F7 S2 APARTMENT 0.75 264.75 0.75 264.75
F8 SW APARTMENT 0.00 97.25 0.00 97.25
F8 NW APARTMENT 0.00 60.25 0.00 60.25
F8 SE APARTMENT 1.00 120.50 1.00 120.50
F8 NE APARTMENT 0.50 156.00 0.50 156.00
F8 N1 APARTMENT 5.75 107.00 5.75 107.00
F8 N2 APARTMENT 4.00 115.50 4.00 115.50
F8 S1 APARTMENT 1.00 260.00 1.00 260.00
F8 S2 APARTMENT 1.25 252.25 1.25 252.25
F9 SW APARTMENT 0.00 86.50 0.00 86.50
F9 NW APARTMENT 0.00 60.50 0.00 60.50
F9 SE APARTMENT 0.50 105.75 0.50 105.75
F9 NE APARTMENT 0.00 170.00 0.00 170.00
F9 N1 APARTMENT 5.75 97.25 5.75 97.25
F9 N2 APARTMENT 4.25 105.75 4.25 105.75
F9 S1 APARTMENT 0.75 229.75 0.75 229.75
F9 S2 APARTMENT 1.25 224.50 1.25 224.50
T SW APARTMENT 0.00 79.75 0.00 79.75
T NW APARTMENT 0.00 67.00 0.00 67.00
T SE APARTMENT 0.00 66.75 0.00 66.75
T NE APARTMENT 0.00 76.75 0.00 76.75
T N1 APARTMENT 0.25 71.25 0.25 71.25
T N2 APARTMENT 0.00 68.75 0.00 68.75
T S1 APARTMENT 0.00 117.00 0.00 117.00
T S2 APARTMENT 0.50 114.75 0.50 114.75
G CORRIDOR 0.00 0.00 0.00 0.00
F2 CORRIDOR 0.00 0.00 0.00 0.00
F3 CORRIDOR 0.00 0.00 0.00 0.00
F4 CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
F6 CORRIDOR 0.00 0.00 0.00 0.00
F7 CORRIDOR 0.00 0.00 0.00 0.00
F8 CORRIDOR 0.00 0.00 0.00 0.00
F9 CORRIDOR 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
Facility 108.50 525.50 105.00 525.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.353 0.174 0.000 0.327
G NW APARTMENT 1.71 2.50 268.96 0.352 0.174 0.000 0.312
OFFICE 0.94 1.00 268.96 0.518 0.180 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.352 0.174 0.000 0.312
G N1 APARTMENT 1.71 2.50 268.96 0.352 0.105 0.000 0.304
G N2 APARTMENT 1.71 2.50 268.97 0.352 0.105 0.000 0.304
G S1 APARTMENT 1.71 2.50 268.96 0.353 0.105 0.000 0.323
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.105 0.000 0.324
F2 SW APARTMENT 1.71 2.50 268.96 0.353 0.250 0.000 0.386
F2 NW APARTMENT 1.71 2.50 268.96 0.352 0.250 0.000 0.368
F2 SE APARTMENT 1.71 2.50 268.96 0.353 0.250 0.000 0.387
F2 NE APARTMENT 1.71 2.50 268.96 0.352 0.250 0.000 0.368
F2 N1 APARTMENT 1.71 2.50 268.96 0.352 0.151 0.000 0.362
F2 N2 APARTMENT 1.71 2.50 268.97 0.352 0.151 0.000 0.362
F2 S1 APARTMENT 1.71 2.50 268.96 0.353 0.151 0.000 0.384
F2 S2 APARTMENT 1.71 2.50 268.97 0.353 0.151 0.000 0.384
F3 SW APARTMENT 1.71 2.50 268.96 0.353 0.296 0.000 0.429
F3 NW APARTMENT 1.71 2.50 268.96 0.352 0.296 0.000 0.408
F3 SE APARTMENT 1.71 2.50 268.96 0.353 0.296 0.000 0.430
F3 NE APARTMENT 1.71 2.50 268.96 0.352 0.296 0.000 0.408
F3 N1 APARTMENT 1.71 2.50 268.96 0.353 0.178 0.000 0.404
F3 N2 APARTMENT 1.71 2.50 268.97 0.353 0.178 0.000 0.404
F3 S1 APARTMENT 1.71 2.50 268.96 0.353 0.179 0.000 0.427
F3 S2 APARTMENT 1.71 2.50 268.97 0.353 0.179 0.000 0.428
F4 SW APARTMENT 1.71 2.50 268.96 0.353 0.331 0.000 0.448
F4 NW APARTMENT 1.71 2.50 268.96 0.352 0.331 0.000 0.424
F4 SE APARTMENT 1.71 2.50 268.96 0.353 0.331 0.000 0.448
F4 NE APARTMENT 1.71 2.50 268.96 0.352 0.330 0.000 0.424
F4 N1 APARTMENT 1.71 2.50 268.96 0.353 0.199 0.000 0.421
F4 N2 APARTMENT 1.71 2.50 268.97 0.353 0.199 0.000 0.421
F4 S1 APARTMENT 1.71 2.50 268.96 0.353 0.200 0.000 0.446
F4 S2 APARTMENT 1.71 2.50 268.97 0.353 0.200 0.000 0.446
M SW APARTMENT 1.71 2.50 268.96 0.353 0.360 0.000 0.471
M NW APARTMENT 1.71 2.50 268.96 0.352 0.359 0.000 0.445
M SE APARTMENT 1.71 2.50 268.96 0.353 0.360 0.000 0.471
M NE APARTMENT 1.71 2.50 268.96 0.352 0.359 0.000 0.445
M N1 APARTMENT 1.71 2.50 268.96 0.352 0.217 0.000 0.442
M N2 APARTMENT 1.71 2.50 268.97 0.352 0.217 0.000 0.442
M S1 APARTMENT 1.71 2.50 268.96 0.353 0.217 0.000 0.469
M S2 APARTMENT 1.71 2.50 268.97 0.353 0.217 0.000 0.469
F6 SW APARTMENT 1.71 2.50 268.96 0.353 0.384 0.000 0.491
F6 NW APARTMENT 1.71 2.50 268.96 0.352 0.384 0.000 0.463
F6 SE APARTMENT 1.71 2.50 268.96 0.353 0.384 0.000 0.491
F6 NE APARTMENT 1.71 2.50 268.96 0.352 0.384 0.000 0.463
F6 N1 APARTMENT 1.71 2.50 268.96 0.352 0.231 0.000 0.460
F6 N2 APARTMENT 1.71 2.50 268.97 0.352 0.231 0.000 0.460
F6 S1 APARTMENT 1.71 2.50 268.96 0.353 0.232 0.000 0.489
F6 S2 APARTMENT 1.71 2.50 268.97 0.353 0.232 0.000 0.489
F7 SW APARTMENT 1.71 2.50 268.96 0.353 0.406 0.000 0.508
F7 NW APARTMENT 1.71 2.50 268.96 0.352 0.405 0.000 0.479
F7 SE APARTMENT 1.71 2.50 268.96 0.353 0.406 0.000 0.508
F7 NE APARTMENT 1.71 2.50 268.96 0.352 0.405 0.000 0.479
F7 N1 APARTMENT 1.71 2.50 268.96 0.352 0.244 0.000 0.475
F7 N2 APARTMENT 1.71 2.50 268.97 0.352 0.244 0.000 0.475
F7 S1 APARTMENT 1.71 2.50 268.96 0.353 0.245 0.000 0.506
F7 S2 APARTMENT 1.71 2.50 268.97 0.353 0.245 0.000 0.506
F8 SW APARTMENT 1.71 2.50 268.96 0.353 0.426 0.000 0.526
F8 NW APARTMENT 1.71 2.50 268.96 0.352 0.425 0.000 0.495
F8 SE APARTMENT 1.71 2.50 268.96 0.353 0.426 0.000 0.526
F8 NE APARTMENT 1.71 2.50 268.96 0.352 0.425 0.000 0.495
F8 N1 APARTMENT 1.71 2.50 268.96 0.352 0.256 0.000 0.491
F8 N2 APARTMENT 1.71 2.50 268.97 0.352 0.256 0.000 0.491
F8 S1 APARTMENT 1.71 2.50 268.96 0.353 0.257 0.000 0.524
F8 S2 APARTMENT 1.71 2.50 268.97 0.353 0.257 0.000 0.524
F9 SW APARTMENT 1.71 2.50 268.96 0.353 0.444 0.000 0.542
F9 NW APARTMENT 1.71 2.50 268.96 0.352 0.443 0.000 0.509
F9 SE APARTMENT 1.71 2.50 268.96 0.353 0.444 0.000 0.542
F9 NE APARTMENT 1.71 2.50 268.96 0.352 0.443 0.000 0.509
F9 N1 APARTMENT 1.71 2.50 268.96 0.352 0.267 0.000 0.506
F9 N2 APARTMENT 1.71 2.50 268.97 0.352 0.267 0.000 0.506
F9 S1 APARTMENT 1.71 2.50 268.96 0.353 0.268 0.000 0.540
F9 S2 APARTMENT 1.71 2.50 268.97 0.353 0.268 0.000 0.540
T SW APARTMENT 1.71 2.50 268.96 0.352 0.460 0.000 0.554
T NW APARTMENT 1.71 2.50 268.96 0.352 0.459 0.000 0.522
T SE APARTMENT 1.71 2.50 268.96 0.352 0.460 0.000 0.554
T NE APARTMENT 1.71 2.50 268.96 0.352 0.459 0.000 0.522
T N1 APARTMENT 1.71 2.50 268.96 0.352 0.277 0.000 0.519
T N2 APARTMENT 1.71 2.50 268.97 0.352 0.277 0.000 0.519
T S1 APARTMENT 1.71 2.50 268.96 0.353 0.277 0.000 0.552
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.277 0.000 0.552
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.96 0.504 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F2 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F2 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F2 S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F2 S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F3 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F3 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F3 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F3 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F3 S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F3 S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F4 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F4 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F4 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F4 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F4 S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
F4 S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.96 0.344 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
F6 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F6 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F6 N1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F6 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F6 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F7 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F7 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F7 N1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F7 N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F7 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F7 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F8 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F8 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F8 N1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F8 N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F8 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F8 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
F9 SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F9 SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F9 N1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
F9 N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
F9 S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
F9 S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.96 0.342 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.96 0.343 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Surfaces by Class

Total Outdoors
Wall 420 140
Floor 90 9
Roof 90 9
Internal Mass 80 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 140 140
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 80
Conditioned Zones 80
Unconditioned Zones 10
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 4156
Defaulted Fields 814
Fields with Defaults 11184
Autosized Fields 1293
Autosizable Fields 1630
Autocalculated Fields 907
Autocalculatable Fields 1710



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
Electricity:Building 1433.88 25760.85 01-JAN-03:15 70162.48 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 296.56 6715.87 01-JAN-00:15 14401.37 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 242.55 5824.91 01-JAN-00:15 11484.27 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 39.38 663.42 01-JAN-00:15 2934.49 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 29.88 469.18 01-JAN-00:15 2345.88 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:G CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F2 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F2 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F2 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F3 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F3 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F3 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F4 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F4 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F4 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:M SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 32.88 1042.61 01-JAN-00:15 1042.61 01-JAN-00:15
Electricity:Zone:F6 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F6 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F6 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F7 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F7 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F7 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F8 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F8 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F8 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:F9 SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:F9 S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
InteriorLights:Electricity:Zone:F9 CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T CORRIDOR 179.47 1701.70 01-JAN-00:15 10868.20 01-JAN-07:15
InteriorLights:Electricity:Zone:T CORRIDOR 16.44 521.30 01-JAN-00:15 521.30 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 54.01 890.97 01-JAN-00:15 2917.11 01-JAN-19:15
InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 1137.32 19044.98 01-JAN-03:15 57142.09 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.50 194.24 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T CORRIDOR 163.03 1180.40 01-JAN-00:15 10346.90 01-JAN-07:15
Fans:Electricity 740.36 23476.58 01-JAN-08:00 23476.58 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F2 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F3 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F4 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F6 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F7 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F8 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:F9 S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:HVAC 1343.22 24137.82 03-APR-02:15 88328.59 31-JUL-16:30
ElectricityProduced:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityProduced:HVAC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricityProduced 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
ElectricityPurchased:Plant 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
Cogeneration:ElectricityPurchased 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
ElectricityNet:Plant 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
Cogeneration:ElectricityNet 3011.89 58190.87 02-JUN-05:00 163762.87 21-JUL-19:15
ExteriorLights:Electricity 162.84 0.00 01-JAN-07:30 10364.00 01-JAN-00:15
General:ExteriorLights:Electricity 162.84 0.00 01-JAN-07:30 10364.00 01-JAN-00:15
General:Fans:Electricity 740.36 23476.58 01-JAN-08:00 23476.58 01-JAN-00:15
Cooling:Electricity 496.27 0.00 01-JAN-00:15 63183.51 31-JUL-15:15
Heating:Electricity 70.42 0.00 01-JAN-13:30 41181.77 14-DEC-04:00
Electricity:Plant 71.94 36.93 13-MAR-23:00 3919.48 31-JUL-15:00
HeatRejection:Electricity 17.58 0.00 01-JAN-00:15 2178.18 31-JUL-15:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 54.36 36.93 13-MAR-23:00 1741.30 01-JAN-00:15
WIRED_LTG_ELECTRICITY 0.44 0.00 01-JAN-00:15 21.60 01-JAN-19:30
WIRED_INT_EQUIP 979.40 1018.50 01-JAN-00:15 10185.00 01-JAN-07:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1285.16 2357.00 01-JAN-00:15 229458.43 17-JAN-08:15
Gas:Plant 1285.16 2357.00 01-JAN-00:15 229458.43 17-JAN-08:15
WaterSystems:Gas 1090.21 2357.00 01-JAN-00:15 80534.53 05-FEB-08:00
Water Heater:WaterSystems:Gas 1090.21 2357.00 01-JAN-00:15 80534.53 05-FEB-08:00
Heating:Gas 194.94 0.00 01-JAN-00:15 157563.37 18-JAN-01:30
Boiler:Heating:Gas 194.94 0.00 01-JAN-00:15 157563.37 18-JAN-01:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
PlantLoopCoolingDemand:Facility 1983.83 0.00 01-JAN-00:15 283526.85 31-JUL-16:30
PlantLoopCoolingDemand:HVAC 1983.83 0.00 01-JAN-00:15 283526.85 31-JUL-16:30
CoolingCoils:PlantLoopCoolingDemand 1983.83 0.00 01-JAN-00:15 283526.85 31-JUL-16:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 6475.26 0.00 01-JAN-02:15 0.00 21-JUL-17:15
Water:Plant 6475.26 0.00 01-JAN-02:15 0.00 21-JUL-17:15
WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 6475.26 0.00 01-JAN-02:15 0.00 21-JUL-17:15
MainsWater:Plant 6475.26 0.00 01-JAN-02:15 0.00 21-JUL-17:15
WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
sub cat:WaterSystems:Water 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
sub cat:WaterSystems:MainsWater 4778.51 0.00 01-JAN-02:15 0.00 01-JAN-07:15
HeatRejection:Water 1696.74 0.00 01-JAN-00:15 0.00 28-JUN-16:00
HeatRejection:MainsWater 1696.74 0.00 01-JAN-00:15 0.00 28-JUN-16:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 1043.76 426.25 10-AUG-01:15 172580.30 17-JAN-08:00
PlantLoopHeatingDemand:Plant 847.41 426.25 10-AUG-01:15 58841.40 08-FEB-08:00
WaterSystems:PlantLoopHeatingDemand 847.41 426.25 10-AUG-01:15 58841.40 08-FEB-08:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 4297.72 6570.35 17-APR-01:30 439933.70 17-JAN-08:15
EnergyTransfer:Building 1528.79 3998.20 03-MAY-18:15 175730.97 05-JUL-17:00
EnergyTransfer:Zone:G SW APARTMENT 14.73 0.00 16-MAR-22:00 2494.95 29-SEP-14:30
Heating:EnergyTransfer 199.34 0.00 20-FEB-22:00 136854.88 14-DEC-04:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 2.06 0.00 01-JAN-00:15 1452.01 18-JAN-01:15
Cooling:EnergyTransfer 1329.45 0.00 16-JAN-23:15 175730.97 05-JUL-17:00
Cooling:EnergyTransfer:Zone:G SW APARTMENT 12.67 0.00 01-JAN-01:30 2494.95 29-SEP-14:30
EnergyTransfer:Zone:G NW APARTMENT 13.25 0.00 26-FEB-18:45 2324.84 22-JUL-17:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 4.88 0.00 01-JAN-17:45 1708.37 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 8.36 0.00 01-JAN-00:15 2324.84 22-JUL-17:30
EnergyTransfer:Zone:OFFICE 25.50 0.02 08-OCT-23:00 3518.30 12-SEP-12:30
Heating:EnergyTransfer:Zone:OFFICE 1.31 0.00 01-JAN-00:15 1431.30 17-JAN-08:00
Cooling:EnergyTransfer:Zone:OFFICE 24.19 0.00 01-JAN-01:30 3518.30 12-SEP-12:30
EnergyTransfer:Zone:G NE APARTMENT 13.30 0.01 01-OCT-07:45 1749.73 14-DEC-04:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 4.42 0.00 01-JAN-09:00 1749.73 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 8.88 0.00 01-JAN-00:15 1725.90 28-JUN-08:15
EnergyTransfer:Zone:G N1 APARTMENT 8.57 0.02 24-MAY-17:00 1170.11 16-JUN-19:45
Heating:EnergyTransfer:Zone:G N1 APARTMENT 2.26 0.00 01-JAN-12:00 987.72 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 6.31 0.00 01-JAN-00:15 1170.11 16-JUN-19:45
EnergyTransfer:Zone:G N2 APARTMENT 8.59 0.02 08-SEP-19:45 1155.63 29-JUN-18:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 2.26 0.00 01-JAN-11:45 990.85 14-DEC-04:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 6.33 0.00 01-JAN-00:15 1155.63 29-JUN-18:00
EnergyTransfer:Zone:G S1 APARTMENT 11.75 0.01 03-FEB-09:15 1429.87 29-SEP-11:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.38 0.00 01-JAN-00:15 780.00 18-JAN-01:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 11.37 0.00 06-JAN-08:00 1429.87 29-SEP-11:30
EnergyTransfer:Zone:G S2 APARTMENT 12.09 0.01 19-MAY-03:15 1497.03 29-SEP-11:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.36 0.00 01-JAN-00:15 762.78 18-JAN-01:30
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 11.72 0.00 06-JAN-08:00 1497.03 29-SEP-11:30
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F2 SW APARTMENT 22.58 0.02 09-OCT-01:30 3202.45 10-OCT-16:15
Heating:EnergyTransfer:Zone:F2 SW APARTMENT 1.01 0.00 01-JAN-00:15 1604.92 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT 21.57 0.00 05-JAN-13:45 3202.45 10-OCT-16:15
EnergyTransfer:Zone:F2 NW APARTMENT 17.29 0.00 08-MAR-01:00 2972.75 18-JUL-17:15
Heating:EnergyTransfer:Zone:F2 NW APARTMENT 3.86 0.00 01-JAN-18:30 2072.06 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT 13.43 0.00 01-JAN-00:15 2972.75 18-JUL-17:15
EnergyTransfer:Zone:F2 SE APARTMENT 25.17 0.01 21-APR-07:45 2928.24 01-OCT-12:00
Heating:EnergyTransfer:Zone:F2 SE APARTMENT 0.74 0.00 01-JAN-00:15 1531.64 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT 24.43 0.00 01-JAN-15:15 2928.24 01-OCT-12:00
EnergyTransfer:Zone:F2 NE APARTMENT 17.88 0.00 29-MAY-04:15 2304.40 28-JUN-08:15
Heating:EnergyTransfer:Zone:F2 NE APARTMENT 3.48 0.00 01-JAN-08:00 2142.93 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT 14.40 0.00 01-JAN-00:15 2304.40 28-JUN-08:15
EnergyTransfer:Zone:F2 N1 APARTMENT 11.76 0.07 08-JAN-11:30 1581.40 24-JUN-19:30
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT 1.18 0.00 01-JAN-07:30 1142.89 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT 10.58 0.00 01-JAN-00:15 1581.40 24-JUN-19:30
EnergyTransfer:Zone:F2 N2 APARTMENT 11.81 0.02 19-NOV-15:15 1577.00 29-JUN-20:15
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT 1.19 0.00 01-JAN-07:30 1148.21 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT 10.62 0.00 01-JAN-00:15 1577.00 29-JUN-20:15
EnergyTransfer:Zone:F2 S1 APARTMENT 19.65 0.36 29-JUL-05:45 2061.04 01-NOV-12:30
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT 0.18 0.00 01-JAN-00:15 763.78 18-JAN-01:30
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT 19.47 0.00 05-JAN-14:45 2061.04 01-NOV-12:30
EnergyTransfer:Zone:F2 S2 APARTMENT 19.85 0.13 17-JAN-19:15 2084.86 01-NOV-12:30
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT 0.18 0.00 01-JAN-00:15 758.07 18-JAN-01:30
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT 19.67 0.00 01-JAN-16:00 2084.86 01-NOV-12:30
EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F2 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F3 SW APARTMENT 23.88 0.00 24-DEC-23:45 3258.37 10-OCT-16:00
Heating:EnergyTransfer:Zone:F3 SW APARTMENT 0.95 0.00 01-JAN-00:15 1718.91 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT 22.94 0.00 05-JAN-13:45 3258.37 10-OCT-16:00
EnergyTransfer:Zone:F3 NW APARTMENT 18.02 0.00 20-NOV-20:30 3013.51 18-JUL-17:30
Heating:EnergyTransfer:Zone:F3 NW APARTMENT 3.75 0.00 02-JAN-18:15 2311.23 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT 14.27 0.00 01-JAN-00:15 3013.51 18-JUL-17:30
EnergyTransfer:Zone:F3 SE APARTMENT 25.07 0.12 20-MAR-05:00 2744.39 01-OCT-11:00
Heating:EnergyTransfer:Zone:F3 SE APARTMENT 0.79 0.00 01-JAN-00:15 1725.16 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT 24.28 0.00 01-JAN-15:15 2744.39 01-OCT-11:00
EnergyTransfer:Zone:F3 NE APARTMENT 18.71 0.02 10-MAY-04:45 2384.09 14-DEC-04:00
Heating:EnergyTransfer:Zone:F3 NE APARTMENT 3.42 0.00 01-JAN-08:00 2384.09 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT 15.29 0.00 01-JAN-00:15 2353.84 28-JUN-08:15
EnergyTransfer:Zone:F3 N1 APARTMENT 12.69 0.06 01-MAR-04:15 1701.35 23-JUN-21:00
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT 1.06 0.00 01-JAN-07:15 1259.24 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT 11.63 0.00 01-JAN-00:15 1701.35 23-JUN-21:00
EnergyTransfer:Zone:F3 N2 APARTMENT 12.73 0.01 24-FEB-18:30 1686.66 23-JUN-21:00
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT 1.07 0.00 01-JAN-07:15 1265.15 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT 11.67 0.00 01-JAN-00:15 1686.66 23-JUN-21:00
EnergyTransfer:Zone:F3 S1 APARTMENT 21.51 0.04 18-JUL-06:00 2129.56 30-DEC-12:00
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT 0.17 0.00 01-JAN-00:15 805.02 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT 21.34 0.00 01-JAN-16:00 2129.56 30-DEC-12:00
EnergyTransfer:Zone:F3 S2 APARTMENT 21.59 0.05 29-JUL-05:45 2139.88 30-DEC-12:00
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT 0.17 0.00 01-JAN-00:15 804.85 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT 21.42 0.00 01-JAN-15:45 2139.88 30-DEC-12:00
EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F3 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F4 SW APARTMENT 24.01 0.00 08-OCT-05:00 3283.65 10-OCT-16:00
Heating:EnergyTransfer:Zone:F4 SW APARTMENT 1.05 0.00 01-JAN-00:15 1856.37 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT 22.96 0.00 01-JAN-20:45 3283.65 10-OCT-16:00
EnergyTransfer:Zone:F4 NW APARTMENT 18.39 0.00 18-NOV-21:00 3036.22 18-JUL-17:45
Heating:EnergyTransfer:Zone:F4 NW APARTMENT 4.00 0.00 02-JAN-18:15 2531.82 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT 14.39 0.00 01-JAN-00:15 3036.22 18-JUL-17:45
EnergyTransfer:Zone:F4 SE APARTMENT 25.00 0.04 01-MAY-04:45 2747.42 11-OCT-12:45
Heating:EnergyTransfer:Zone:F4 SE APARTMENT 0.92 0.00 01-JAN-00:15 1874.20 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT 24.08 0.00 01-JAN-15:00 2747.42 11-OCT-12:45
EnergyTransfer:Zone:F4 NE APARTMENT 19.08 0.02 16-APR-23:45 2602.18 14-DEC-04:00
Heating:EnergyTransfer:Zone:F4 NE APARTMENT 3.67 0.00 01-JAN-08:00 2602.18 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT 15.41 0.00 01-JAN-00:15 2366.14 02-AUG-09:00
EnergyTransfer:Zone:F4 N1 APARTMENT 12.98 0.00 03-JAN-04:30 1721.69 23-JUN-21:00
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT 1.13 0.00 01-JAN-07:15 1380.81 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT 11.85 0.00 01-JAN-00:15 1721.69 23-JUN-21:00
EnergyTransfer:Zone:F4 N2 APARTMENT 13.02 0.07 01-FEB-22:30 1707.13 23-JUN-21:00
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT 1.13 0.00 01-JAN-07:15 1386.49 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT 11.88 0.00 01-JAN-00:15 1707.13 23-JUN-21:00
EnergyTransfer:Zone:F4 S1 APARTMENT 21.83 0.11 05-JAN-15:45 2151.88 30-DEC-12:00
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT 0.19 0.00 01-JAN-00:15 885.24 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT 21.64 0.00 01-JAN-15:45 2151.88 30-DEC-12:00
EnergyTransfer:Zone:F4 S2 APARTMENT 21.88 0.76 09-DEC-00:45 2159.94 30-DEC-12:00
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT 0.19 0.00 01-JAN-00:15 885.99 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT 21.69 0.00 01-JAN-15:45 2159.94 30-DEC-12:00
EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F4 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M SW APARTMENT 24.17 0.04 06-MAY-03:45 3321.60 10-OCT-16:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 1.18 0.00 01-JAN-00:15 1971.11 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 22.99 0.00 01-JAN-15:45 3321.60 10-OCT-16:00
EnergyTransfer:Zone:M NW APARTMENT 18.86 0.01 02-NOV-08:45 3067.31 18-JUL-17:45
Heating:EnergyTransfer:Zone:M NW APARTMENT 4.25 0.00 02-JAN-18:15 2711.96 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 14.61 0.00 01-JAN-00:15 3067.31 18-JUL-17:45
EnergyTransfer:Zone:M SE APARTMENT 25.11 0.02 30-MAR-22:30 2795.17 11-OCT-12:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 1.05 0.00 01-JAN-00:15 1990.52 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 24.07 0.00 01-JAN-14:45 2795.17 11-OCT-12:45
EnergyTransfer:Zone:M NE APARTMENT 19.50 0.00 26-JAN-16:15 2778.44 14-DEC-04:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 3.90 0.00 01-JAN-08:00 2778.44 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 15.60 0.00 01-JAN-00:15 2408.39 02-AUG-09:00
EnergyTransfer:Zone:M N1 APARTMENT 13.31 0.04 14-FEB-11:15 1762.24 23-JUN-21:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 1.19 0.00 01-JAN-07:15 1478.99 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 12.11 0.00 01-JAN-00:15 1762.24 23-JUN-21:00
EnergyTransfer:Zone:M N2 APARTMENT 13.35 0.02 20-MAR-11:45 1747.93 23-JUN-21:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 1.20 0.00 01-JAN-07:15 1484.15 14-DEC-04:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 12.15 0.00 01-JAN-00:15 1747.93 23-JUN-21:00
EnergyTransfer:Zone:M S1 APARTMENT 22.04 0.44 07-SEP-10:45 2185.19 30-DEC-12:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.21 0.00 01-JAN-00:15 952.16 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 21.83 0.00 01-JAN-15:30 2185.19 30-DEC-12:00
EnergyTransfer:Zone:M S2 APARTMENT 22.08 0.16 03-JUN-08:15 2192.85 30-DEC-12:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.21 0.00 01-JAN-00:15 953.10 18-JAN-01:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 21.87 0.00 01-JAN-15:30 2192.85 30-DEC-12:00
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F6 SW APARTMENT 23.36 0.01 07-DEC-13:15 3290.23 10-OCT-16:00
Heating:EnergyTransfer:Zone:F6 SW APARTMENT 1.45 0.00 01-JAN-00:15 2122.03 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT 21.91 0.00 01-JAN-15:30 3290.23 10-OCT-16:00
EnergyTransfer:Zone:F6 NW APARTMENT 18.91 0.01 18-NOV-22:00 3031.34 18-JUL-17:45
Heating:EnergyTransfer:Zone:F6 NW APARTMENT 4.89 0.00 02-JAN-18:15 2918.22 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT 14.02 0.00 01-JAN-00:15 3031.34 18-JUL-17:45
EnergyTransfer:Zone:F6 SE APARTMENT 24.26 0.05 21-MAR-16:30 2772.60 11-OCT-12:45
Heating:EnergyTransfer:Zone:F6 SE APARTMENT 1.30 0.00 01-JAN-00:15 2142.22 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT 22.96 0.00 01-JAN-05:00 2772.60 11-OCT-12:45
EnergyTransfer:Zone:F6 NE APARTMENT 19.46 0.02 08-NOV-03:15 2979.06 14-DEC-04:00
Heating:EnergyTransfer:Zone:F6 NE APARTMENT 4.50 0.00 01-JAN-08:15 2979.06 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT 14.96 0.00 01-JAN-00:15 2379.08 02-AUG-09:00
EnergyTransfer:Zone:F6 N1 APARTMENT 12.95 0.04 07-NOV-15:30 1735.89 23-JUN-21:00
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT 1.48 0.00 01-JAN-07:30 1610.46 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT 11.47 0.00 01-JAN-00:15 1735.89 23-JUN-21:00
EnergyTransfer:Zone:F6 N2 APARTMENT 12.99 0.08 30-JAN-13:15 1721.71 23-JUN-21:00
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT 1.48 0.00 01-JAN-07:30 1615.29 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT 11.51 0.00 01-JAN-00:15 1721.71 23-JUN-21:00
EnergyTransfer:Zone:F6 S1 APARTMENT 21.07 0.19 01-FEB-03:15 2154.82 30-DEC-12:00
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT 0.26 0.00 01-JAN-00:15 1043.56 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT 20.81 0.00 01-JAN-15:15 2154.82 30-DEC-12:00
EnergyTransfer:Zone:F6 S2 APARTMENT 21.10 0.70 15-MAR-14:15 2162.43 30-DEC-12:00
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT 0.26 0.00 01-JAN-00:15 1044.45 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT 20.84 0.00 01-JAN-15:15 2162.43 30-DEC-12:00
EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F6 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F7 SW APARTMENT 22.95 0.00 23-OCT-01:15 3281.56 10-OCT-16:00
Heating:EnergyTransfer:Zone:F7 SW APARTMENT 1.71 0.00 01-JAN-00:15 2247.94 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT 21.25 0.00 01-JAN-05:00 3281.56 10-OCT-16:00
EnergyTransfer:Zone:F7 NW APARTMENT 19.16 0.00 05-DEC-16:00 3090.62 14-DEC-04:00
Heating:EnergyTransfer:Zone:F7 NW APARTMENT 5.42 0.00 02-JAN-18:15 3090.62 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT 13.73 0.00 01-JAN-00:15 3020.44 18-JUL-17:45
EnergyTransfer:Zone:F7 SE APARTMENT 23.82 0.16 18-MAY-06:00 2770.11 11-OCT-12:45
Heating:EnergyTransfer:Zone:F7 SE APARTMENT 1.55 0.00 01-JAN-00:15 2268.29 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT 22.28 0.00 01-JAN-03:00 2770.11 11-OCT-12:45
EnergyTransfer:Zone:F7 NE APARTMENT 19.64 0.00 24-SEP-03:30 3146.91 14-DEC-04:00
Heating:EnergyTransfer:Zone:F7 NE APARTMENT 4.99 0.00 01-JAN-08:30 3146.91 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT 14.65 0.00 01-JAN-00:15 2381.64 02-AUG-09:00
EnergyTransfer:Zone:F7 N1 APARTMENT 12.84 0.09 07-NOV-14:45 1732.14 23-JUN-21:00
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT 1.72 0.00 01-JAN-07:45 1718.48 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT 11.12 0.00 01-JAN-00:15 1732.14 23-JUN-21:00
EnergyTransfer:Zone:F7 N2 APARTMENT 12.89 0.00 25-MAR-03:00 1722.98 14-DEC-04:00
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT 1.73 0.00 01-JAN-07:45 1722.98 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT 11.16 0.00 01-JAN-00:15 1718.05 23-JUN-21:00
EnergyTransfer:Zone:F7 S1 APARTMENT 20.47 0.01 04-MAR-00:45 2144.63 30-DEC-12:00
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT 0.31 0.00 01-JAN-00:15 1118.97 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT 20.16 0.00 01-JAN-15:00 2144.63 30-DEC-12:00
EnergyTransfer:Zone:F7 S2 APARTMENT 20.51 0.20 04-DEC-01:15 2152.22 30-DEC-12:00
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT 0.31 0.00 01-JAN-00:15 1119.77 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT 20.20 0.00 01-JAN-15:00 2152.22 30-DEC-12:00
EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F7 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F8 SW APARTMENT 22.73 0.02 06-MAY-03:00 3286.40 10-OCT-16:00
Heating:EnergyTransfer:Zone:F8 SW APARTMENT 1.99 0.00 01-JAN-00:15 2371.79 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT 20.74 0.00 01-JAN-03:00 3286.40 10-OCT-16:00
EnergyTransfer:Zone:F8 NW APARTMENT 19.53 0.01 15-APR-05:45 3247.98 14-DEC-04:00
Heating:EnergyTransfer:Zone:F8 NW APARTMENT 5.94 0.00 02-JAN-18:30 3247.98 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT 13.59 0.00 01-JAN-00:15 3024.40 18-JUL-17:45
EnergyTransfer:Zone:F8 SE APARTMENT 23.57 0.02 21-OCT-05:00 2780.30 11-OCT-12:45
Heating:EnergyTransfer:Zone:F8 SE APARTMENT 1.81 0.00 01-JAN-00:15 2391.83 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT 21.75 0.00 01-JAN-02:45 2780.30 11-OCT-12:45
EnergyTransfer:Zone:F8 NE APARTMENT 19.94 0.01 11-APR-02:30 3301.92 14-DEC-04:00
Heating:EnergyTransfer:Zone:F8 NE APARTMENT 5.47 0.00 01-JAN-08:30 3301.92 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT 14.47 0.00 01-JAN-00:15 2386.52 02-AUG-09:00
EnergyTransfer:Zone:F8 N1 APARTMENT 12.91 0.07 20-MAR-15:45 1874.32 17-MAR-15:00
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT 1.98 0.00 01-JAN-08:30 1874.32 17-MAR-15:00
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT 10.93 0.00 01-JAN-00:15 1742.34 23-JUN-21:00
EnergyTransfer:Zone:F8 N2 APARTMENT 12.95 0.06 21-NOV-14:30 1867.08 17-MAR-15:00
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT 1.98 0.00 01-JAN-08:30 1867.08 17-MAR-15:00
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT 10.97 0.00 01-JAN-00:15 1728.14 23-JUN-21:00
EnergyTransfer:Zone:F8 S1 APARTMENT 20.01 0.35 19-MAR-13:45 2134.27 30-DEC-12:00
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT 0.37 0.00 01-JAN-00:15 1195.34 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT 19.64 0.00 01-JAN-14:30 2134.27 30-DEC-12:00
EnergyTransfer:Zone:F8 S2 APARTMENT 20.05 0.43 30-APR-18:45 2141.00 30-DEC-12:00
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT 0.37 0.00 01-JAN-00:15 1196.19 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT 19.68 0.00 01-JAN-14:30 2141.00 30-DEC-12:00
EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F8 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:F9 SW APARTMENT 22.96 0.01 02-NOV-08:45 3394.17 10-OCT-15:45
Heating:EnergyTransfer:Zone:F9 SW APARTMENT 2.59 0.00 01-JAN-00:15 2564.83 18-JAN-01:00
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT 20.37 0.00 01-JAN-02:30 3394.17 10-OCT-15:45
EnergyTransfer:Zone:F9 NW APARTMENT 20.69 0.01 20-APR-11:15 3441.65 14-DEC-04:00
Heating:EnergyTransfer:Zone:F9 NW APARTMENT 6.86 0.00 02-JAN-18:45 3441.65 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT 13.83 0.00 01-JAN-00:15 3134.55 18-JUL-17:45
EnergyTransfer:Zone:F9 SE APARTMENT 23.69 0.04 01-MAR-21:15 2867.48 11-OCT-12:45
Heating:EnergyTransfer:Zone:F9 SE APARTMENT 2.35 0.00 01-JAN-00:15 2602.91 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT 21.34 0.00 01-JAN-02:15 2867.48 11-OCT-12:45
EnergyTransfer:Zone:F9 NE APARTMENT 20.87 0.00 21-NOV-10:45 3500.08 14-DEC-04:00
Heating:EnergyTransfer:Zone:F9 NE APARTMENT 6.27 0.00 01-JAN-08:45 3500.08 14-DEC-04:00
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT 14.59 0.00 01-JAN-00:15 2428.53 02-AUG-09:00
EnergyTransfer:Zone:F9 N1 APARTMENT 13.48 0.01 30-OCT-19:30 2032.98 17-MAR-15:00
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT 2.50 0.00 01-JAN-10:15 2032.98 17-MAR-15:00
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT 10.97 0.00 01-JAN-00:15 1843.00 23-JUN-21:00
EnergyTransfer:Zone:F9 N2 APARTMENT 13.52 0.02 06-MAR-11:30 2023.44 17-MAR-15:00
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT 2.51 0.00 01-JAN-09:00 2023.44 17-MAR-15:00
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT 11.01 0.00 01-JAN-00:15 1828.87 23-JUN-21:00
EnergyTransfer:Zone:F9 S1 APARTMENT 19.60 0.05 14-OCT-18:00 2119.48 07-NOV-12:45
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT 0.51 0.00 01-JAN-00:15 1342.44 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT 19.08 0.00 01-JAN-14:15 2119.48 07-NOV-12:45
EnergyTransfer:Zone:F9 S2 APARTMENT 19.64 0.01 21-APR-22:15 2127.29 07-NOV-12:45
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT 0.52 0.00 01-JAN-00:15 1343.45 18-JAN-01:15
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT 19.13 0.00 01-JAN-14:15 2127.29 07-NOV-12:45
EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:F9 CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:T SW APARTMENT 30.12 0.01 10-JAN-21:15 4173.66 10-OCT-15:45
Heating:EnergyTransfer:Zone:T SW APARTMENT 7.76 0.00 01-JAN-08:30 3625.62 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 22.36 0.00 01-JAN-00:15 4173.66 10-OCT-15:45
EnergyTransfer:Zone:T NW APARTMENT 27.28 0.01 04-JUN-02:30 4097.01 14-DEC-04:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 11.83 0.00 02-JAN-14:15 4097.01 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 15.45 0.00 01-JAN-00:15 3899.37 18-JUL-17:30
EnergyTransfer:Zone:T SE APARTMENT 29.94 0.02 29-JAN-19:00 3646.61 14-DEC-04:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 7.22 0.00 01-JAN-08:00 3646.61 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 22.72 0.00 01-JAN-00:15 3637.15 11-OCT-13:00
EnergyTransfer:Zone:T NE APARTMENT 26.65 0.00 06-SEP-20:00 4125.62 14-DEC-04:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 10.90 0.00 01-JAN-09:00 4125.62 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 15.75 0.00 01-JAN-00:15 3086.12 05-JUL-08:45
EnergyTransfer:Zone:T N1 APARTMENT 17.60 0.01 31-MAR-09:00 2506.19 14-DEC-04:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 5.90 0.00 01-JAN-10:30 2506.19 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 11.70 0.00 01-JAN-00:15 2400.74 23-JUN-21:00
EnergyTransfer:Zone:T N2 APARTMENT 17.66 0.02 20-JAN-16:45 2509.40 14-DEC-04:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 5.92 0.00 01-JAN-10:30 2509.40 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 11.73 0.00 01-JAN-00:15 2387.43 23-JUN-21:00
EnergyTransfer:Zone:T S1 APARTMENT 22.20 0.05 01-APR-03:15 2937.55 01-OCT-12:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 2.91 0.00 01-JAN-00:15 1977.20 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 19.29 0.00 01-JAN-01:15 2937.55 01-OCT-12:00
EnergyTransfer:Zone:T S2 APARTMENT 22.26 0.01 08-NOV-01:15 2945.31 01-OCT-12:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 2.92 0.00 01-JAN-00:15 1980.17 14-DEC-04:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 19.34 0.00 01-JAN-01:15 2945.31 01-OCT-12:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 992.72 426.25 10-AUG-01:15 168711.18 17-JAN-08:00
WaterSystems:EnergyTransfer 847.40 426.25 10-AUG-01:15 58835.39 08-FEB-08:00
sub cat:WaterSystems:EnergyTransfer 847.40 426.25 10-AUG-01:15 58835.39 08-FEB-08:00
EnergyTransfer:HVAC 1776.21 0.00 13-MAR-23:00 220717.61 31-JUL-16:30
CoolingCoils:EnergyTransfer 1519.72 0.00 01-JAN-00:15 220717.61 31-JUL-16:30
HeatingCoils:EnergyTransfer 256.49 0.00 01-JAN-13:30 159739.18 14-DEC-04:00
PlantLoopHeatingDemand:HVAC 196.35 0.00 01-JAN-13:30 120310.79 14-DEC-04:00
HeatingCoils:PlantLoopHeatingDemand 196.35 0.00 01-JAN-13:30 120310.79 14-DEC-04:00
Boilers:EnergyTransfer 145.32 0.00 01-JAN-00:15 118172.53 18-JAN-01:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 2.058 -12.670 0.000 0.000 3.748 1.087 12.213 27.930 0.000 0.416 0.001 0.000 -9.772 0.000 -6.897 -18.112
G NW APARTMENT 4.882 -8.364 0.000 0.000 3.807 1.087 12.213 14.093 0.000 0.410 0.000 0.000 -9.795 0.000 -6.414 -11.918
OFFICE 1.305 -24.191 0.000 0.000 0.507 29.882 9.495 28.597 0.000 0.298 0.001 0.000 -9.687 0.000 -4.028 -32.179
G NE APARTMENT 4.416 -8.883 0.000 0.000 3.822 1.087 12.213 14.630 0.000 0.407 0.000 0.000 -9.312 0.000 -6.401 -11.979
G N1 APARTMENT 2.259 -6.306 0.000 0.000 3.831 1.087 12.213 4.662 0.000 0.292 0.000 0.000 -5.988 0.000 -4.625 -7.424
G N2 APARTMENT 2.261 -6.329 0.000 0.000 3.832 1.087 12.213 4.658 0.000 0.291 0.000 0.000 -5.984 0.000 -4.627 -7.401
G S1 APARTMENT 0.380 -11.372 0.000 0.000 3.750 1.087 12.213 18.689 0.000 0.290 0.001 0.000 -5.923 0.000 -5.175 -13.937
G S2 APARTMENT 0.363 -11.722 0.000 0.000 3.745 1.087 12.213 18.668 0.000 0.291 0.001 0.000 -5.937 0.000 -5.221 -13.486
F2 SW APARTMENT 1.009 -21.567 0.000 0.000 3.658 1.087 12.213 27.218 0.000 0.569 0.000 0.000 -10.544 0.000 -9.462 -4.180
F2 NW APARTMENT 3.861 -13.428 0.000 0.000 3.753 1.087 12.213 13.588 0.000 0.560 0.000 0.000 -10.422 0.000 -8.849 -2.363
F2 SE APARTMENT 0.739 -24.432 0.000 0.000 3.653 1.087 12.213 27.891 0.000 0.569 0.001 0.000 -10.341 0.000 -9.558 -1.820
F2 NE APARTMENT 3.481 -14.401 0.000 0.000 3.770 1.087 12.213 14.122 0.000 0.556 0.000 0.000 -9.892 0.000 -8.814 -2.123
F2 N1 APARTMENT 1.184 -10.575 0.000 0.000 3.774 1.087 12.213 4.395 0.000 0.390 0.309 0.000 -6.420 0.000 -6.358 -0.000
F2 N2 APARTMENT 1.194 -10.615 0.000 0.000 3.775 1.087 12.213 4.392 0.000 0.390 0.338 0.000 -6.415 0.000 -6.359 -0.000
F2 S1 APARTMENT 0.181 -19.470 0.000 0.000 3.637 1.087 12.213 18.238 0.000 0.385 0.002 0.000 -6.413 0.000 -7.075 -2.782
F2 S2 APARTMENT 0.180 -19.669 0.000 0.000 3.635 1.087 12.213 18.231 0.000 0.386 0.002 0.000 -6.419 0.000 -7.089 -2.555
F3 SW APARTMENT 0.947 -22.935 0.000 0.000 3.646 1.087 12.213 26.953 0.000 0.703 0.001 0.000 -10.723 0.000 -10.831 -1.060
F3 NW APARTMENT 3.748 -14.273 0.000 0.000 3.744 1.087 12.213 13.417 0.000 0.692 0.140 0.000 -10.604 0.000 -10.163 -0.000
F3 SE APARTMENT 0.790 -24.276 0.000 0.000 3.655 1.087 12.213 27.690 0.000 0.698 0.001 0.000 -10.433 0.000 -10.848 -0.574
F3 NE APARTMENT 3.420 -15.291 0.000 0.000 3.760 1.087 12.213 13.956 0.000 0.686 0.351 0.000 -10.061 0.000 -10.120 -0.000
F3 N1 APARTMENT 1.060 -11.628 0.000 0.000 3.759 1.087 12.213 4.319 0.000 0.491 2.536 0.000 -6.555 0.000 -7.280 -0.000
F3 N2 APARTMENT 1.067 -11.666 0.000 0.000 3.760 1.087 12.213 4.316 0.000 0.490 2.564 0.000 -6.550 0.000 -7.281 -0.000
F3 S1 APARTMENT 0.168 -21.344 0.000 0.000 3.616 1.087 12.213 18.064 0.000 0.481 0.308 0.000 -6.546 0.000 -8.046 -0.000
F3 S2 APARTMENT 0.168 -21.422 0.000 0.000 3.616 1.087 12.213 18.061 0.000 0.482 0.395 0.000 -6.546 0.000 -8.052 -0.000
F4 SW APARTMENT 1.049 -22.963 0.000 0.000 3.648 1.087 12.213 26.801 0.000 0.771 0.001 0.000 -10.787 0.000 -11.656 -0.162
F4 NW APARTMENT 3.998 -14.392 0.000 0.000 3.744 1.087 12.213 13.325 0.000 0.760 0.911 0.000 -10.685 0.000 -10.961 -0.000
F4 SE APARTMENT 0.920 -24.077 0.000 0.000 3.659 1.087 12.213 27.553 0.000 0.766 0.016 0.000 -10.479 0.000 -11.657 -0.000
F4 NE APARTMENT 3.671 -15.407 0.000 0.000 3.760 1.087 12.213 13.867 0.000 0.752 1.108 0.000 -10.136 0.000 -10.915 -0.000
F4 N1 APARTMENT 1.128 -11.848 0.000 0.000 3.755 1.087 12.213 4.283 0.000 0.535 3.251 0.000 -6.619 0.000 -7.785 0.000
F4 N2 APARTMENT 1.133 -11.884 0.000 0.000 3.756 1.087 12.213 4.280 0.000 0.535 3.280 0.000 -6.614 0.000 -7.785 0.000
F4 S1 APARTMENT 0.186 -21.642 0.000 0.000 3.614 1.087 12.213 17.966 0.000 0.525 1.214 0.000 -6.596 0.000 -8.566 -0.000
F4 S2 APARTMENT 0.187 -21.689 0.000 0.000 3.615 1.087 12.213 17.963 0.000 0.526 1.263 0.000 -6.594 0.000 -8.570 -0.000
M SW APARTMENT 1.180 -22.990 0.000 0.000 3.652 1.087 12.213 26.681 0.000 0.826 0.667 0.000 -10.837 0.000 -12.479 -0.001
M NW APARTMENT 4.250 -14.605 0.000 0.000 3.746 1.087 12.213 13.255 0.000 0.814 1.732 0.000 -10.748 0.000 -11.743 -0.000
M SE APARTMENT 1.047 -24.066 0.000 0.000 3.663 1.087 12.213 27.440 0.000 0.821 0.796 0.000 -10.525 0.000 -12.476 -0.000
M NE APARTMENT 3.895 -15.604 0.000 0.000 3.761 1.087 12.213 13.797 0.000 0.804 1.933 0.000 -10.194 0.000 -11.692 -0.000
M N1 APARTMENT 1.194 -12.113 0.000 0.000 3.755 1.087 12.213 4.256 0.000 0.571 4.020 0.000 -6.666 0.000 -8.316 0.000
M N2 APARTMENT 1.199 -12.151 0.000 0.000 3.756 1.087 12.213 4.253 0.000 0.570 4.050 0.000 -6.661 0.000 -8.316 0.000
M S1 APARTMENT 0.211 -21.831 0.000 0.000 3.615 1.087 12.213 17.890 0.000 0.562 2.019 0.000 -6.631 0.000 -9.133 -0.000
M S2 APARTMENT 0.212 -21.871 0.000 0.000 3.616 1.087 12.213 17.887 0.000 0.562 2.060 0.000 -6.629 0.000 -9.136 -0.000
F6 SW APARTMENT 1.449 -21.914 0.000 0.000 3.663 1.087 12.213 26.620 0.000 0.872 0.001 0.000 -10.818 0.000 -13.131 -0.040
F6 NW APARTMENT 4.893 -14.020 0.000 0.000 3.755 1.087 12.213 13.235 0.000 0.859 1.057 0.000 -10.737 0.000 -12.342 -0.000
F6 SE APARTMENT 1.304 -22.957 0.000 0.000 3.674 1.087 12.213 27.383 0.000 0.867 0.067 0.000 -10.506 0.000 -13.131 -0.000
F6 NE APARTMENT 4.499 -14.964 0.000 0.000 3.770 1.087 12.213 13.779 0.000 0.848 1.241 0.000 -10.181 0.000 -12.292 -0.000
F6 N1 APARTMENT 1.478 -11.469 0.000 0.000 3.764 1.087 12.213 4.257 0.000 0.600 3.419 0.000 -6.658 0.000 -8.692 0.000
F6 N2 APARTMENT 1.484 -11.505 0.000 0.000 3.765 1.087 12.213 4.254 0.000 0.600 3.449 0.000 -6.653 0.000 -8.693 0.000
F6 S1 APARTMENT 0.258 -20.807 0.000 0.000 3.627 1.087 12.213 17.851 0.000 0.591 1.365 0.000 -6.620 0.000 -9.565 -0.000
F6 S2 APARTMENT 0.258 -20.844 0.000 0.000 3.627 1.087 12.213 17.849 0.000 0.592 1.404 0.000 -6.618 0.000 -9.568 -0.000
F7 SW APARTMENT 1.707 -21.246 0.000 0.000 3.671 1.087 12.213 26.561 0.000 0.912 0.001 0.000 -10.814 0.000 -13.708 -0.382
F7 NW APARTMENT 5.424 -13.733 0.000 0.000 3.762 1.087 12.213 13.211 0.000 0.897 0.756 0.000 -10.739 0.000 -12.879 -0.000
F7 SE APARTMENT 1.549 -22.275 0.000 0.000 3.682 1.087 12.213 27.326 0.000 0.907 0.001 0.000 -10.501 0.000 -13.708 -0.279
F7 NE APARTMENT 4.991 -14.645 0.000 0.000 3.776 1.087 12.213 13.756 0.000 0.886 0.943 0.000 -10.182 0.000 -12.826 -0.000
F7 N1 APARTMENT 1.718 -11.122 0.000 0.000 3.771 1.087 12.213 4.254 0.000 0.625 3.143 0.000 -6.658 0.000 -9.031 0.000
F7 N2 APARTMENT 1.727 -11.162 0.000 0.000 3.772 1.087 12.213 4.251 0.000 0.625 3.173 0.000 -6.653 0.000 -9.032 0.000
F7 S1 APARTMENT 0.306 -20.162 0.000 0.000 3.636 1.087 12.213 17.815 0.000 0.618 1.048 0.000 -6.616 0.000 -9.943 -0.000
F7 S2 APARTMENT 0.308 -20.200 0.000 0.000 3.637 1.087 12.213 17.812 0.000 0.618 1.087 0.000 -6.614 0.000 -9.947 -0.000
F8 SW APARTMENT 1.990 -20.738 0.000 0.000 3.679 1.087 12.213 26.508 0.000 0.954 0.001 0.000 -10.810 0.000 -14.241 -0.641
F8 NW APARTMENT 5.937 -13.594 0.000 0.000 3.767 1.087 12.213 13.187 0.000 0.938 0.593 0.000 -10.746 0.000 -13.381 -0.000
F8 SE APARTMENT 1.814 -21.754 0.000 0.000 3.689 1.087 12.213 27.276 0.000 0.949 0.001 0.000 -10.498 0.000 -14.243 -0.532
F8 NE APARTMENT 5.470 -14.470 0.000 0.000 3.781 1.087 12.213 13.733 0.000 0.925 0.776 0.000 -10.187 0.000 -13.327 -0.000
F8 N1 APARTMENT 1.975 -10.930 0.000 0.000 3.777 1.087 12.213 4.249 0.000 0.654 2.994 0.000 -6.661 0.000 -9.358 -0.000
F8 N2 APARTMENT 1.981 -10.967 0.000 0.000 3.778 1.087 12.213 4.246 0.000 0.653 3.025 0.000 -6.657 0.000 -9.358 -0.000
F8 S1 APARTMENT 0.366 -19.640 0.000 0.000 3.645 1.087 12.213 17.783 0.000 0.648 0.805 0.000 -6.611 0.000 -10.296 -0.000
F8 S2 APARTMENT 0.367 -19.678 0.000 0.000 3.646 1.087 12.213 17.780 0.000 0.648 0.846 0.000 -6.609 0.000 -10.300 -0.000
F9 SW APARTMENT 2.591 -20.371 0.000 0.000 3.689 1.087 12.213 26.483 0.000 0.994 0.003 0.000 -10.786 0.000 -14.700 -1.201
F9 NW APARTMENT 6.862 -13.832 0.000 0.000 3.771 1.087 12.213 13.170 0.000 0.975 0.340 0.000 -10.749 0.000 -13.836 -0.000
F9 SE APARTMENT 2.352 -21.336 0.000 0.000 3.699 1.087 12.213 27.250 0.000 0.990 0.002 0.000 -10.474 0.000 -14.705 -1.075
F9 NE APARTMENT 6.274 -14.591 0.000 0.000 3.785 1.087 12.213 13.718 0.000 0.960 0.525 0.000 -10.190 0.000 -13.780 -0.001
F9 N1 APARTMENT 2.504 -10.975 0.000 0.000 3.781 1.087 12.213 4.246 0.000 0.681 2.781 0.000 -6.661 0.000 -9.656 -0.000
F9 N2 APARTMENT 2.511 -11.013 0.000 0.000 3.782 1.087 12.213 4.243 0.000 0.681 2.813 0.000 -6.657 0.000 -9.658 -0.001
F9 S1 APARTMENT 0.513 -19.083 0.000 0.000 3.660 1.087 12.213 17.770 0.000 0.678 0.335 0.000 -6.587 0.000 -10.585 -0.000
F9 S2 APARTMENT 0.516 -19.127 0.000 0.000 3.660 1.087 12.213 17.767 0.000 0.679 0.380 0.000 -6.585 0.000 -10.590 -0.000
T SW APARTMENT 7.763 -22.357 0.000 0.000 3.740 1.087 12.213 26.132 0.000 1.026 0.000 0.000 -10.211 0.000 -14.979 -4.414
T NW APARTMENT 11.831 -15.451 0.000 0.000 3.785 1.087 12.213 12.847 0.000 1.002 0.000 0.000 -10.340 0.000 -14.324 -2.648
T SE APARTMENT 7.219 -22.718 0.000 0.000 3.749 1.087 12.213 26.923 0.000 1.026 0.000 0.000 -9.934 0.000 -14.991 -4.574
T NE APARTMENT 10.902 -15.748 0.000 0.000 3.801 1.087 12.213 13.460 0.000 1.002 0.000 0.000 -9.841 0.000 -14.258 -2.617
T N1 APARTMENT 5.904 -11.697 0.000 0.000 3.794 1.087 12.213 4.128 0.000 0.704 0.288 0.000 -6.420 0.000 -10.000 -0.001
T N2 APARTMENT 5.922 -11.734 0.000 0.000 3.795 1.087 12.213 4.122 0.000 0.704 0.312 0.000 -6.414 0.000 -10.007 -0.000
T S1 APARTMENT 2.908 -19.287 0.000 0.000 3.722 1.087 12.213 17.594 0.000 0.718 0.000 0.000 -6.266 0.000 -10.754 -1.936
T S2 APARTMENT 2.917 -19.340 0.000 0.000 3.723 1.087 12.213 17.589 0.000 0.718 0.001 0.000 -6.262 0.000 -10.759 -1.885
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 6.615 0.000 2.626 19.201 0.000 -2.253 0.000 -42.628 -0.002
F2 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 3.005 0.000 0.038 0.000 0.000 -1.326 0.000 -1.091 -17.065
F3 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.954 0.000 0.043 0.000 0.000 -1.373 0.000 -1.333 -16.731
F4 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.927 0.000 0.047 0.000 0.000 -1.393 0.000 -1.506 -16.514
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 32.880 0.000 2.895 0.000 0.043 0.000 0.000 -1.423 0.000 -1.709 -32.686
F6 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.906 0.000 0.054 0.000 0.000 -1.399 0.000 -1.742 -16.258
F7 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.906 0.000 0.058 0.000 0.000 -1.392 0.000 -1.823 -16.189
F8 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.902 0.000 0.060 0.000 0.000 -1.390 0.000 -1.902 -16.110
F9 CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 0.000 2.899 0.000 0.060 0.000 0.000 -1.389 0.000 -1.973 -16.036
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 16.440 8.151 2.828 0.000 0.031 0.000 0.000 -1.344 0.000 -2.111 -23.995
Total Facility 199.330 -1329.417 0.000 0.000 294.418 296.560 982.450 1293.533 0.000 56.807 93.448 0.000 -690.091 0.000 -869.152 -327.876


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-SEP-14:30 0.00 -2495.10 0.00 0.00 39.18 22.70 400.26 4654.53 0.00 59.62 0.00 0.00 0.00 0.00 0.00 -2681.19
G NW APARTMENT 22-JUL-17:30 0.00 -2332.07 0.00 0.00 140.63 87.56 588.62 3088.07 0.00 192.76 0.00 0.00 0.00 0.00 0.00 -1765.57
OFFICE 12-SEP-12:30 0.00 -3518.24 0.00 0.00 65.15 2345.88 588.62 3073.98 0.00 55.91 0.00 0.00 0.00 0.00 0.00 -2611.29
G NE APARTMENT 28-JUN-08:15 0.00 -1725.89 0.00 0.00 40.62 12.97 394.37 2859.14 0.00 191.98 0.00 0.00 0.00 0.00 0.00 -1773.19
G N1 APARTMENT 16-JUN-19:45 0.00 -1169.29 0.00 0.00 141.66 103.77 523.87 0.00 0.00 226.43 208.45 0.00 -34.88 0.00 0.00 0.00
G N2 APARTMENT 29-JUN-18:00 0.00 -1156.10 0.00 0.00 140.95 87.56 588.62 432.66 0.00 49.19 0.00 0.00 0.00 0.00 0.00 -142.88
G S1 APARTMENT 29-SEP-11:30 0.00 -1429.90 0.00 0.00 39.69 12.97 406.15 3273.03 0.00 69.08 0.00 0.00 0.00 0.00 0.00 -2371.02
G S2 APARTMENT 29-SEP-11:30 0.00 -1497.06 0.00 0.00 39.74 12.97 406.15 3272.07 0.00 70.88 0.00 0.00 0.00 0.00 0.00 -2304.75
F2 SW APARTMENT 10-OCT-16:15 0.00 -3215.52 0.00 0.00 84.76 64.86 588.62 3043.60 0.00 506.61 0.00 0.00 0.00 0.00 0.00 -1072.92
F2 NW APARTMENT 18-JUL-17:20 0.00 -2982.87 0.00 0.00 138.30 87.56 588.62 3302.45 0.00 283.37 0.00 0.00 0.00 0.00 0.00 -1417.43
F2 SE APARTMENT 01-OCT-12:00 0.00 -2928.47 0.00 0.00 40.50 12.97 406.15 3719.43 0.00 66.69 0.00 0.00 0.00 0.00 0.00 -1317.27
F2 NE APARTMENT 28-JUN-07:38 0.00 -2306.08 0.00 0.00 63.57 19.46 388.49 2911.92 0.00 108.16 0.00 0.00 0.00 0.00 0.00 -1185.51
F2 N1 APARTMENT 24-JUN-19:30 0.00 -1580.15 0.00 0.00 140.96 103.77 523.87 0.00 0.00 232.79 615.02 0.00 -36.27 0.00 0.00 0.00
F2 N2 APARTMENT 29-JUN-20:15 0.00 -1575.62 0.00 0.00 163.01 71.34 500.33 0.00 0.00 278.03 585.26 0.00 -22.34 0.00 0.00 0.00
F2 S1 APARTMENT 01-NOV-12:30 0.00 -2060.71 0.00 0.00 40.75 12.97 388.49 3597.60 0.00 0.00 0.00 0.00 0.00 0.00 -338.76 -1640.34
F2 S2 APARTMENT 01-NOV-12:30 0.00 -2084.52 0.00 0.00 40.75 12.97 388.49 3597.25 0.00 0.00 0.00 0.00 0.00 0.00 -338.68 -1616.26
F3 SW APARTMENT 10-OCT-16:00 0.00 -3264.02 0.00 0.00 48.90 45.40 470.89 3284.35 0.00 660.47 0.00 0.00 0.00 0.00 0.00 -1245.98
F3 NW APARTMENT 18-JUL-17:20 0.00 -3020.02 0.00 0.00 137.99 87.56 588.62 3278.43 0.00 333.52 0.00 0.00 0.00 0.00 0.00 -1406.09
F3 SE APARTMENT 01-OCT-11:00 0.00 -2744.74 0.00 0.00 40.59 12.97 412.03 3985.39 0.00 0.00 0.00 0.00 0.00 0.00 -39.41 -1666.84
F3 NE APARTMENT 28-JUN-08:15 0.00 -2353.89 0.00 0.00 40.54 12.97 394.37 2819.37 0.00 230.28 0.00 0.00 0.00 0.00 0.00 -1143.66
F3 N1 APARTMENT 23-JUN-21:00 0.00 -1703.45 0.00 0.00 162.93 71.34 500.33 2.10 0.00 595.56 371.19 0.00 0.00 0.00 0.00 0.00
F3 N2 APARTMENT 23-JUN-21:00 0.00 -1688.61 0.00 0.00 162.91 71.34 500.33 2.11 0.00 592.17 359.74 0.00 0.00 0.00 0.00 0.00
F3 S1 APARTMENT 30-DEC-12:00 0.00 -2129.54 0.00 0.00 40.75 12.97 412.03 3993.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2329.45
F3 S2 APARTMENT 30-DEC-12:00 0.00 -2139.85 0.00 0.00 40.75 12.97 412.03 3993.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2318.95
F4 SW APARTMENT 10-OCT-15:53 0.00 -3285.50 0.00 0.00 48.89 45.40 470.89 3265.87 0.00 788.98 0.00 0.00 0.00 0.00 0.00 -1334.54
F4 NW APARTMENT 18-JUL-17:45 0.00 -3036.57 0.00 0.00 137.43 87.56 588.62 3086.00 0.00 352.72 0.00 0.00 0.00 0.00 0.00 -1215.76
F4 SE APARTMENT 01-OCT-11:00 0.00 -2745.41 0.00 0.00 40.59 12.97 412.03 3976.90 0.00 0.00 0.00 0.00 0.00 0.00 -43.50 -1653.59
F4 NE APARTMENT 02-AUG-09:00 0.00 -2366.26 0.00 0.00 40.56 12.97 394.37 2624.90 0.00 539.12 0.00 0.00 0.00 0.00 0.00 -1245.66
F4 N1 APARTMENT 23-JUN-21:00 0.00 -1723.48 0.00 0.00 162.88 71.34 500.33 3.21 0.00 635.18 350.55 0.00 0.00 0.00 0.00 0.00
F4 N2 APARTMENT 23-JUN-21:00 0.00 -1708.74 0.00 0.00 162.86 71.34 500.33 3.18 0.00 631.21 339.82 0.00 0.00 0.00 0.00 0.00
F4 S1 APARTMENT 30-DEC-12:00 0.00 -2151.86 0.00 0.00 40.75 12.97 412.03 3991.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2305.49
F4 S2 APARTMENT 30-DEC-12:00 0.00 -2159.92 0.00 0.00 40.75 12.97 412.03 3991.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2297.31
M SW APARTMENT 10-OCT-15:53 0.00 -3326.73 0.00 0.00 48.90 45.40 470.89 3251.64 0.00 840.39 0.00 0.00 0.00 0.00 0.00 -1330.49
M NW APARTMENT 18-JUL-17:45 0.00 -3067.65 0.00 0.00 137.19 87.56 588.62 3073.19 0.00 381.19 0.00 0.00 0.00 0.00 0.00 -1200.10
M SE APARTMENT 11-OCT-12:45 0.00 -2793.07 0.00 0.00 40.10 12.97 388.49 3163.39 0.00 877.00 0.00 0.00 0.00 0.00 0.00 -1688.89
M NE APARTMENT 02-AUG-09:00 0.00 -2408.53 0.00 0.00 40.55 12.97 394.37 2612.16 0.00 572.73 0.00 0.00 0.00 0.00 0.00 -1224.25
M N1 APARTMENT 23-JUN-21:00 0.00 -1763.85 0.00 0.00 162.85 71.34 500.33 3.49 0.00 667.37 358.47 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 23-JUN-21:00 0.00 -1749.34 0.00 0.00 162.83 71.34 500.33 3.44 0.00 662.97 348.44 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 30-DEC-12:00 0.00 -2185.19 0.00 0.00 40.75 12.97 412.03 3990.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2271.05
M S2 APARTMENT 30-DEC-12:00 0.00 -2192.85 0.00 0.00 40.75 12.97 412.03 3990.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2263.29
F6 SW APARTMENT 10-OCT-15:53 0.00 -3296.07 0.00 0.00 48.90 45.40 470.89 3241.95 0.00 880.79 0.00 0.00 0.00 0.00 0.00 -1391.86
F6 NW APARTMENT 18-JUL-17:45 0.00 -3031.67 0.00 0.00 136.91 87.56 588.62 3064.04 0.00 404.85 0.00 0.00 0.00 0.00 0.00 -1250.30
F6 SE APARTMENT 11-OCT-12:45 0.00 -2770.49 0.00 0.00 40.13 12.97 388.49 3153.70 0.00 921.76 0.00 0.00 0.00 0.00 0.00 -1746.55
F6 NE APARTMENT 02-AUG-09:00 0.00 -2379.23 0.00 0.00 40.53 12.97 394.37 2603.53 0.00 597.62 0.00 0.00 0.00 0.00 0.00 -1269.79
F6 N1 APARTMENT 23-JUN-21:00 0.00 -1737.22 0.00 0.00 162.82 71.34 500.33 4.77 0.00 688.98 308.98 0.00 0.00 0.00 0.00 0.00
F6 N2 APARTMENT 23-JUN-21:00 0.00 -1722.83 0.00 0.00 162.80 71.34 500.33 4.69 0.00 684.15 299.53 0.00 0.00 0.00 0.00 0.00
F6 S1 APARTMENT 30-DEC-12:00 0.00 -2154.83 0.00 0.00 40.75 12.97 412.03 3990.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2301.89
F6 S2 APARTMENT 30-DEC-12:00 0.00 -2162.43 0.00 0.00 40.75 12.97 412.03 3990.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2294.19
F7 SW APARTMENT 10-OCT-15:53 0.00 -3287.86 0.00 0.00 48.90 45.40 470.89 3233.36 0.00 915.51 0.00 0.00 0.00 0.00 0.00 -1426.19
F7 NW APARTMENT 18-JUL-17:45 0.00 -3020.76 0.00 0.00 136.69 87.56 588.62 3055.80 0.00 425.60 0.00 0.00 0.00 0.00 0.00 -1273.51
F7 SE APARTMENT 11-OCT-12:45 0.00 -2767.97 0.00 0.00 40.16 12.97 388.49 3145.27 0.00 960.83 0.00 0.00 0.00 0.00 0.00 -1779.75
F7 NE APARTMENT 02-AUG-09:00 0.00 -2381.79 0.00 0.00 40.53 12.97 394.37 2595.77 0.00 621.53 0.00 0.00 0.00 0.00 0.00 -1283.38
F7 N1 APARTMENT 23-JUN-21:00 0.00 -1733.24 0.00 0.00 162.80 71.34 500.33 5.35 0.00 707.37 286.06 0.00 0.00 0.00 0.00 0.00
F7 N2 APARTMENT 23-JUN-21:00 0.00 -1718.93 0.00 0.00 162.78 71.34 500.33 5.26 0.00 702.27 276.96 0.00 0.00 0.00 0.00 0.00
F7 S1 APARTMENT 30-DEC-12:00 0.00 -2144.64 0.00 0.00 40.75 12.97 412.03 3991.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2312.27
F7 S2 APARTMENT 30-DEC-12:00 0.00 -2152.23 0.00 0.00 40.75 12.97 412.03 3991.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2304.58
F8 SW APARTMENT 10-OCT-15:53 0.00 -3293.13 0.00 0.00 48.90 45.40 470.89 3225.88 0.00 947.14 0.00 0.00 0.00 0.00 0.00 -1445.08
F8 NW APARTMENT 18-JUL-17:45 0.00 -3024.71 0.00 0.00 136.53 87.56 588.62 3048.32 0.00 444.22 0.00 0.00 0.00 0.00 0.00 -1280.55
F8 SE APARTMENT 11-OCT-12:45 0.00 -2778.13 0.00 0.00 40.20 12.97 388.49 3138.12 0.00 998.48 0.00 0.00 0.00 0.00 0.00 -1800.14
F8 NE APARTMENT 02-AUG-09:00 0.00 -2386.68 0.00 0.00 40.51 12.97 394.37 2588.60 0.00 639.79 0.00 0.00 0.00 0.00 0.00 -1289.58
F8 N1 APARTMENT 23-JUN-21:00 0.00 -1743.26 0.00 0.00 162.78 71.34 500.33 5.50 0.00 723.80 279.52 0.00 0.00 0.00 0.00 0.00
F8 N2 APARTMENT 23-JUN-21:00 0.00 -1728.92 0.00 0.00 162.71 71.34 500.33 5.35 0.00 718.14 271.05 0.00 0.00 0.00 0.00 0.00
F8 S1 APARTMENT 30-DEC-12:00 0.00 -2134.29 0.00 0.00 40.75 12.97 412.03 3991.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2323.23
F8 S2 APARTMENT 30-DEC-12:00 0.00 -2141.01 0.00 0.00 40.75 12.97 412.03 3991.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -2316.40
F9 SW APARTMENT 10-OCT-15:38 0.00 -3402.09 0.00 0.00 48.90 45.40 470.89 3491.22 0.00 989.62 0.00 0.00 0.00 0.00 0.00 -1643.95
F9 NW APARTMENT 18-JUL-17:45 0.00 -3134.86 0.00 0.00 136.63 87.56 588.62 3038.99 0.00 462.38 0.00 0.00 0.00 0.00 0.00 -1179.32
F9 SE APARTMENT 11-OCT-12:45 0.00 -2865.24 0.00 0.00 40.37 12.97 388.49 3133.24 0.00 1073.82 0.00 0.00 0.00 0.00 0.00 -1783.65
F9 NE APARTMENT 02-AUG-09:00 0.00 -2428.69 0.00 0.00 40.55 12.97 394.37 2582.21 0.00 664.88 0.00 0.00 0.00 0.00 0.00 -1266.30
F9 N1 APARTMENT 23-JUN-21:00 0.00 -1843.91 0.00 0.00 162.78 71.34 500.33 3.41 0.00 746.06 359.99 0.00 0.00 0.00 0.00 0.00
F9 N2 APARTMENT 23-JUN-21:00 0.00 -1829.57 0.00 0.00 162.76 71.34 500.33 3.36 0.00 741.11 350.67 0.00 0.00 0.00 0.00 0.00
F9 S1 APARTMENT 07-NOV-12:45 0.00 -2119.18 0.00 0.00 40.75 12.97 406.15 3673.62 0.00 0.00 0.00 0.00 0.00 0.00 -117.00 -1897.31
F9 S2 APARTMENT 07-NOV-12:45 0.00 -2126.99 0.00 0.00 40.75 12.97 406.15 3673.44 0.00 0.00 0.00 0.00 0.00 0.00 -117.02 -1889.30
T SW APARTMENT 10-OCT-15:38 0.00 -4180.29 0.00 0.00 48.90 45.40 470.89 3447.76 0.00 1102.59 0.00 0.00 0.00 0.00 0.00 -935.26
T NW APARTMENT 18-JUL-17:20 0.00 -3901.77 0.00 0.00 137.04 87.56 588.62 3160.09 0.00 504.48 0.00 0.00 0.00 0.00 0.00 -576.01
T SE APARTMENT 11-OCT-13:00 0.00 -3634.04 0.00 0.00 40.40 12.97 388.49 2962.31 0.00 1432.50 0.00 0.00 0.00 0.00 0.00 -1202.63
T NE APARTMENT 05-JUL-08:45 0.00 -3085.70 0.00 0.00 40.75 12.97 394.37 2711.27 0.00 303.58 0.00 0.00 0.00 0.00 0.00 -377.25
T N1 APARTMENT 23-JUN-21:00 0.00 -2401.79 0.00 0.00 162.99 71.34 500.33 5.20 0.00 1009.31 652.63 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 23-JUN-21:00 0.00 -2388.47 0.00 0.00 162.99 71.34 500.33 5.63 0.00 1009.31 638.88 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 01-OCT-12:00 0.00 -2937.80 0.00 0.00 39.34 12.97 406.15 3382.19 0.00 24.81 0.00 0.00 0.00 0.00 0.00 -927.67
T S2 APARTMENT 01-OCT-12:00 0.00 -2945.57 0.00 0.00 39.28 12.97 406.15 3381.37 0.00 23.08 0.00 0.00 0.00 0.00 0.00 -917.28
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-JUL-17:00 0.00 -175720.16 0.00 0.00 6630.14 11327.17 47312.53 95458.61 0.00 34140.32 0.00 0.00 0.00 0.00 0.00 -19148.61


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 18-JAN-01:15 1451.52 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 0.00 0.00 -978.04 0.00 -775.27 -135.71
G NW APARTMENT 14-DEC-04:00 1707.86 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 44.71 0.00 -996.46 0.00 -1175.95 0.00
OFFICE 17-JAN-07:53 1431.30 0.00 0.00 0.00 0.00 469.18 294.31 0.00 0.00 0.00 0.00 0.00 -778.83 0.00 -803.33 -612.63
G NE APARTMENT 14-DEC-04:00 1749.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -986.42 0.00 -1175.95 -6.67
G N1 APARTMENT 20-MAR-11:55 1256.23 0.00 0.00 0.00 46.33 12.97 406.15 370.85 0.00 0.00 0.00 0.00 0.00 0.00 -1193.93 -898.61
G N2 APARTMENT 20-MAR-11:55 1249.98 0.00 0.00 0.00 46.35 12.97 406.15 370.86 0.00 0.00 0.00 0.00 0.00 0.00 -1193.88 -892.43
G S1 APARTMENT 20-MAR-12:00 1038.20 0.00 0.00 0.00 43.99 12.97 406.15 1754.35 0.00 0.00 0.00 0.00 0.00 0.00 -1310.30 -1945.36
G S2 APARTMENT 19-MAR-16:00 853.96 0.00 0.00 0.00 52.31 45.40 470.89 56.35 0.00 0.00 0.00 0.00 0.00 0.00 -1186.92 -291.99
F2 SW APARTMENT 18-JAN-01:15 1604.43 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 91.51 0.00 -1018.39 0.00 -1115.05 0.00
F2 NW APARTMENT 14-DEC-04:00 2071.46 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 235.04 0.00 -1034.93 0.00 -1691.40 0.00
F2 SE APARTMENT 18-JAN-01:15 1531.16 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 176.79 0.00 -1030.40 0.00 -1115.04 0.00
F2 NE APARTMENT 14-DEC-04:00 2142.30 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 149.89 0.00 -1020.62 0.00 -1691.40 0.00
F2 N1 APARTMENT 09-NOV-10:00 1328.64 0.00 0.00 0.00 43.58 12.97 394.37 123.16 0.00 0.00 0.00 0.00 0.00 0.00 -1645.79 -256.92
F2 N2 APARTMENT 09-NOV-10:00 1315.41 0.00 0.00 0.00 43.60 12.97 394.37 123.32 0.00 0.00 0.00 0.00 0.00 0.00 -1645.71 -243.97
F2 S1 APARTMENT 18-JAN-01:30 763.52 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 89.68 0.00 -627.29 0.00 -663.40 0.00
F2 S2 APARTMENT 18-JAN-01:30 757.82 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 95.60 0.00 -627.50 0.00 -663.40 0.00
F3 SW APARTMENT 18-JAN-01:15 1718.40 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 200.64 0.00 -1035.55 0.00 -1320.98 0.00
F3 NW APARTMENT 14-DEC-04:00 2310.57 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 323.92 0.00 -1050.46 0.00 -2003.86 0.00
F3 SE APARTMENT 18-JAN-01:15 1724.62 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 204.38 0.00 -1045.51 0.00 -1320.98 0.00
F3 NE APARTMENT 14-DEC-04:00 2383.40 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 235.39 0.00 -1034.76 0.00 -2003.86 0.00
F3 N1 APARTMENT 09-NOV-10:00 1622.08 0.00 0.00 0.00 42.96 12.97 394.37 107.39 0.00 0.00 0.00 0.00 0.00 0.00 -1881.97 -297.82
F3 N2 APARTMENT 09-NOV-10:00 1596.98 0.00 0.00 0.00 42.99 12.97 394.37 107.68 0.00 0.00 0.00 0.00 0.00 0.00 -1881.86 -273.14
F3 S1 APARTMENT 18-JAN-01:15 804.73 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 196.05 0.00 -641.49 0.00 -796.78 0.00
F3 S2 APARTMENT 18-JAN-01:15 804.56 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 196.22 0.00 -641.50 0.00 -796.78 0.00
F4 SW APARTMENT 18-JAN-01:15 1855.82 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 229.31 0.00 -1045.19 0.00 -1477.44 0.00
F4 NW APARTMENT 14-DEC-04:00 2531.10 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 349.24 0.00 -1058.89 0.00 -2241.29 0.00
F4 SE APARTMENT 18-JAN-01:15 1873.63 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 221.92 0.00 -1055.60 0.00 -1477.44 0.00
F4 NE APARTMENT 14-DEC-04:00 2601.44 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 262.62 0.00 -1042.60 0.00 -2241.29 0.00
F4 N1 APARTMENT 09-NOV-10:15 1522.47 0.00 0.00 0.00 42.94 12.97 406.15 121.56 0.00 0.00 0.00 0.00 0.00 0.00 -1927.88 -178.21
F4 N2 APARTMENT 09-NOV-10:15 1505.25 0.00 0.00 0.00 42.97 12.97 406.15 121.89 0.00 0.00 0.00 0.00 0.00 0.00 -1927.78 -161.44
F4 S1 APARTMENT 18-JAN-01:15 884.92 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 217.05 0.00 -648.32 0.00 -891.15 0.00
F4 S2 APARTMENT 18-JAN-01:15 885.68 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 216.26 0.00 -648.28 0.00 -891.15 0.00
M SW APARTMENT 18-JAN-01:15 1970.54 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 251.24 0.00 -1052.63 0.00 -1606.64 0.00
M NW APARTMENT 14-DEC-04:00 2711.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 371.73 0.00 -1065.38 0.00 -2437.38 0.00
M SE APARTMENT 18-JAN-01:15 1989.92 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 242.93 0.00 -1063.71 0.00 -1606.64 0.00
M NE APARTMENT 14-DEC-04:00 2777.65 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 288.75 0.00 -1048.85 0.00 -2437.38 0.00
M N1 APARTMENT 09-NOV-10:15 1544.52 0.00 0.00 0.00 42.91 12.97 406.15 116.95 0.00 0.00 0.00 0.00 0.00 0.00 -2075.08 -48.42
M N2 APARTMENT 09-NOV-10:15 1526.35 0.00 0.00 0.00 42.94 12.97 406.15 117.26 0.00 0.00 0.00 0.00 0.00 0.00 -2074.99 -30.68
M S1 APARTMENT 18-JAN-01:15 951.83 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 233.25 0.00 -653.49 0.00 -969.08 0.00
M S2 APARTMENT 18-JAN-01:15 952.76 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 232.27 0.00 -653.45 0.00 -969.08 0.00
F6 SW APARTMENT 18-JAN-01:00 2121.34 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 216.68 0.00 -1057.47 0.00 -1741.59 0.00
F6 NW APARTMENT 14-DEC-04:00 2917.40 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 337.27 0.00 -1067.80 0.00 -2606.70 0.00
F6 SE APARTMENT 18-JAN-01:00 2141.49 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 208.20 0.00 -1069.13 0.00 -1741.59 0.00
F6 NE APARTMENT 14-DEC-04:00 2978.21 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 260.08 0.00 -1051.42 0.00 -2606.71 0.00
F6 N1 APARTMENT 24-JAN-14:55 1703.11 0.00 0.00 0.00 45.29 12.97 382.60 170.49 0.00 0.00 0.00 0.00 0.00 0.00 -1746.94 -567.53
F6 N2 APARTMENT 24-JAN-14:55 1714.22 0.00 0.00 0.00 45.30 12.97 382.60 170.58 0.00 0.00 0.00 0.00 0.00 0.00 -1746.66 -579.02
F6 S1 APARTMENT 18-JAN-01:15 1043.20 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 211.54 0.00 -655.87 0.00 -1036.36 0.00
F6 S2 APARTMENT 18-JAN-01:15 1044.09 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 210.61 0.00 -655.83 0.00 -1036.36 0.00
F7 SW APARTMENT 18-JAN-01:00 2247.21 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 194.46 0.00 -1060.76 0.00 -1841.94 0.00
F7 NW APARTMENT 14-DEC-04:00 3089.75 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 317.76 0.00 -1070.32 0.00 -2757.02 0.00
F7 SE APARTMENT 18-JAN-01:00 2267.53 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 186.24 0.00 -1072.86 0.00 -1841.94 0.00
F7 NE APARTMENT 14-DEC-04:00 3146.01 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 245.23 0.00 -1054.05 0.00 -2757.03 0.00
F7 N1 APARTMENT 24-JAN-14:55 1968.93 0.00 0.00 0.00 45.46 12.97 382.60 170.44 0.00 0.00 0.00 0.00 0.00 0.00 -1829.79 -750.62
F7 N2 APARTMENT 24-JAN-14:55 1979.42 0.00 0.00 0.00 45.47 12.97 382.60 170.52 0.00 0.00 0.00 0.00 0.00 0.00 -1829.53 -761.46
F7 S1 APARTMENT 18-JAN-01:15 1118.58 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 198.13 0.00 -658.12 0.00 -1096.08 0.00
F7 S2 APARTMENT 18-JAN-01:15 1119.38 0.00 0.00 0.00 189.67 6.49 241.33 0.00 0.00 0.00 197.29 0.00 -658.08 0.00 -1096.08 0.00
F8 SW APARTMENT 18-JAN-01:00 2371.03 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 163.87 0.00 -1063.19 0.00 -1932.75 0.00
F8 NW APARTMENT 14-DEC-04:00 3247.07 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 298.59 0.00 -1072.44 0.00 -2893.05 0.00
F8 SE APARTMENT 18-JAN-01:00 2391.04 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 156.36 0.00 -1075.68 0.00 -1932.75 0.00
F8 NE APARTMENT 14-DEC-04:00 3300.97 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 228.44 0.00 -1056.20 0.00 -2893.05 0.00
F8 N1 APARTMENT 24-JAN-14:55 2087.75 0.00 0.00 0.00 45.62 12.97 382.60 170.48 0.00 0.00 0.00 0.00 0.00 0.00 -1909.01 -790.41
F8 N2 APARTMENT 24-JAN-14:55 2088.93 0.00 0.00 0.00 45.62 12.97 382.60 170.54 0.00 0.00 0.00 0.00 0.00 0.00 -1908.96 -791.70
F8 S1 APARTMENT 20-MAR-12:15 1474.64 0.00 0.00 0.00 42.05 12.97 388.49 1732.75 0.00 0.00 0.00 0.00 0.00 0.00 -2329.63 -1321.27
F8 S2 APARTMENT 20-MAR-12:15 1468.45 0.00 0.00 0.00 42.05 12.97 388.49 1732.69 0.00 0.00 0.00 0.00 0.00 0.00 -2329.80 -1314.84
F9 SW APARTMENT 18-JAN-01:00 2564.02 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 53.08 0.00 -1062.08 0.00 -2016.06 0.00
F9 NW APARTMENT 14-DEC-04:00 3440.69 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 229.13 0.00 -1071.78 0.00 -3017.87 0.00
F9 SE APARTMENT 14-DEC-04:00 2602.17 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 1084.29 0.00 -1088.43 0.00 -3017.87 0.00
F9 NE APARTMENT 14-DEC-04:00 3499.09 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 154.44 0.00 -1055.48 0.00 -3017.88 0.00
F9 N1 APARTMENT 09-NOV-10:10 2288.12 0.00 0.00 0.00 44.33 12.97 406.15 123.56 0.00 0.00 0.00 0.00 0.00 0.00 -2542.59 -332.54
F9 N2 APARTMENT 09-NOV-10:10 2302.58 0.00 0.00 0.00 44.35 12.97 406.15 123.72 0.00 0.00 0.00 0.00 0.00 0.00 -2542.17 -347.61
F9 S1 APARTMENT 09-NOV-10:15 1566.57 0.00 0.00 0.00 41.13 12.97 406.15 127.10 0.00 0.00 381.99 0.00 0.00 0.00 -2535.90 0.00
F9 S2 APARTMENT 09-NOV-10:15 1563.18 0.00 0.00 0.00 41.11 12.97 406.15 126.98 0.00 0.00 385.73 0.00 0.00 0.00 -2536.12 0.00
T SW APARTMENT 14-DEC-04:00 3624.63 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 141.34 0.00 -1052.42 0.00 -3133.38 0.00
T NW APARTMENT 14-DEC-04:00 4095.89 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1041.73 0.00 -3133.38 -340.61
T SE APARTMENT 14-DEC-04:00 3645.60 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 105.49 0.00 -1037.54 0.00 -3133.38 0.00
T NE APARTMENT 14-DEC-04:00 4124.46 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1027.34 0.00 -3133.39 -383.57
T N1 APARTMENT 09-NOV-10:10 2653.21 0.00 0.00 0.00 44.17 12.97 406.15 125.33 0.00 0.00 0.00 0.00 0.00 0.00 -2640.05 -601.78
T N2 APARTMENT 09-NOV-10:10 2604.79 0.00 0.00 0.00 44.07 12.97 406.15 123.97 0.00 0.00 0.00 0.00 0.00 0.00 -2642.30 -549.64
T S1 APARTMENT 09-NOV-10:15 2062.58 0.00 0.00 0.00 40.94 12.97 406.15 126.02 0.00 0.00 0.00 0.00 0.00 0.00 -2632.18 -16.46
T S2 APARTMENT 09-NOV-10:15 2064.05 0.00 0.00 0.00 40.90 12.97 406.15 125.47 0.00 0.00 0.00 0.00 0.00 0.00 -2632.34 -17.19
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F2 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F3 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F4 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F6 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F7 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F8 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
F9 CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 14-DEC-04:00 136531.46 0.00 0.00 0.00 14983.75 6715.87 17923.60 0.00 0.00 0.00 51717.52 0.00 -70030.81 0.00 -157841.39 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Sec1.1A-General Information

Data
Weather File Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 7836.48
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.50
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
F2 SW APARTMENT 88.25 88.25 0.00 168.00
F2 NW APARTMENT 88.25 88.25 0.00 168.00
F2 SE APARTMENT 88.25 88.25 0.00 168.00
F2 NE APARTMENT 88.25 88.25 0.00 168.00
F2 N1 APARTMENT 88.25 88.25 0.00 168.00
F2 N2 APARTMENT 88.25 88.25 0.00 168.00
F2 S1 APARTMENT 88.25 88.25 0.00 168.00
F2 S2 APARTMENT 88.25 88.25 0.00 168.00
F3 SW APARTMENT 88.25 88.25 0.00 168.00
F3 NW APARTMENT 88.25 88.25 0.00 168.00
F3 SE APARTMENT 88.25 88.25 0.00 168.00
F3 NE APARTMENT 88.25 88.25 0.00 168.00
F3 N1 APARTMENT 88.25 88.25 0.00 168.00
F3 N2 APARTMENT 88.25 88.25 0.00 168.00
F3 S1 APARTMENT 88.25 88.25 0.00 168.00
F3 S2 APARTMENT 88.25 88.25 0.00 168.00
F4 SW APARTMENT 88.25 88.25 0.00 168.00
F4 NW APARTMENT 88.25 88.25 0.00 168.00
F4 SE APARTMENT 88.25 88.25 0.00 168.00
F4 NE APARTMENT 88.25 88.25 0.00 168.00
F4 N1 APARTMENT 88.25 88.25 0.00 168.00
F4 N2 APARTMENT 88.25 88.25 0.00 168.00
F4 S1 APARTMENT 88.25 88.25 0.00 168.00
F4 S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
F6 SW APARTMENT 88.25 88.25 0.00 168.00
F6 NW APARTMENT 88.25 88.25 0.00 168.00
F6 SE APARTMENT 88.25 88.25 0.00 168.00
F6 NE APARTMENT 88.25 88.25 0.00 168.00
F6 N1 APARTMENT 88.25 88.25 0.00 168.00
F6 N2 APARTMENT 88.25 88.25 0.00 168.00
F6 S1 APARTMENT 88.25 88.25 0.00 168.00
F6 S2 APARTMENT 88.25 88.25 0.00 168.00
F7 SW APARTMENT 88.25 88.25 0.00 168.00
F7 NW APARTMENT 88.25 88.25 0.00 168.00
F7 SE APARTMENT 88.25 88.25 0.00 168.00
F7 NE APARTMENT 88.25 88.25 0.00 168.00
F7 N1 APARTMENT 88.25 88.25 0.00 168.00
F7 N2 APARTMENT 88.25 88.25 0.00 168.00
F7 S1 APARTMENT 88.25 88.25 0.00 168.00
F7 S2 APARTMENT 88.25 88.25 0.00 168.00
F8 SW APARTMENT 88.25 88.25 0.00 168.00
F8 NW APARTMENT 88.25 88.25 0.00 168.00
F8 SE APARTMENT 88.25 88.25 0.00 168.00
F8 NE APARTMENT 88.25 88.25 0.00 168.00
F8 N1 APARTMENT 88.25 88.25 0.00 168.00
F8 N2 APARTMENT 88.25 88.25 0.00 168.00
F8 S1 APARTMENT 88.25 88.25 0.00 168.00
F8 S2 APARTMENT 88.25 88.25 0.00 168.00
F9 SW APARTMENT 88.25 88.25 0.00 168.00
F9 NW APARTMENT 88.25 88.25 0.00 168.00
F9 SE APARTMENT 88.25 88.25 0.00 168.00
F9 NE APARTMENT 88.25 88.25 0.00 168.00
F9 N1 APARTMENT 88.25 88.25 0.00 168.00
F9 N2 APARTMENT 88.25 88.25 0.00 168.00
F9 S1 APARTMENT 88.25 88.25 0.00 168.00
F9 S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
G CORRIDOR 77.66 0.00 77.66 0.00
F2 CORRIDOR 77.66 0.00 77.66 0.00
F3 CORRIDOR 77.66 0.00 77.66 0.00
F4 CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
F6 CORRIDOR 77.66 0.00 77.66 0.00
F7 CORRIDOR 77.66 0.00 77.66 0.00
F8 CORRIDOR 77.66 0.00 77.66 0.00
F9 CORRIDOR 77.66 0.00 77.66 0.00
T CORRIDOR 77.66 0.00 77.66 0.00
Totals 7836.48 7059.89 776.58  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 105.00
Number of hours cooling loads not met 525.25
Number of hours not met 639.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 296.56 14401.37 0.00 0.00 0.00 0.00
Exterior Lighting 162.84 10364.00 0.00 0.00 0.00 0.00
Space Heating 70.42 0.00 194.94 150090.38 0.00 0.00
Space Cooling 496.27 60361.60 0.00 0.00 0.00 0.00
Pumps 54.36 1741.30 0.00 0.00 0.00 0.00
Heat Rejection 17.58 1886.79 0.00 0.00 0.00 0.00
Fans-Interior 740.36 23476.58 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1090.21 79368.04 0.00 0.00
Receptacle Equipment 1137.32 49889.93 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 3011.89   1285.16   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1137.32 3011.89
Natural Gas 0.00 1285.16
Additional 0.00 0.00
Total 1137.32 4297.04


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.84
Space Heating 8.99
Space Cooling 63.33
Fans-Interior 94.48
Service Water Heating 0.00
Receptacle Equipment 145.13
Miscellaneous 34.58
Subtotal 384.34


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.88
Service Water Heating 139.12
Miscellaneous 0.00
Subtotal 164.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.90
Space Heating 6.18
Space Cooling 11.55
Fans-Interior 17.23
Service Water Heating 25.37
Receptacle Equipment 26.47
Miscellaneous 6.31



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.261865
G NW APARTMENT DIRECT AIR 0.256992
OFFICE DIRECT AIR 0.375203
G NE APARTMENT DIRECT AIR 0.186744
G N1 APARTMENT DIRECT AIR 0.131508
G N2 APARTMENT DIRECT AIR 0.129530
G S1 APARTMENT DIRECT AIR 0.138971
G S2 APARTMENT DIRECT AIR 0.146296
F2 SW APARTMENT DIRECT AIR 0.336816
F2 NW APARTMENT DIRECT AIR 0.328085
F2 SE APARTMENT DIRECT AIR 0.302169
F2 NE APARTMENT DIRECT AIR 0.248800
F2 N1 APARTMENT DIRECT AIR 0.174616
F2 N2 APARTMENT DIRECT AIR 0.172998
F2 S1 APARTMENT DIRECT AIR 0.186418
F2 S2 APARTMENT DIRECT AIR 0.188984
F3 SW APARTMENT DIRECT AIR 0.339857
F3 NW APARTMENT DIRECT AIR 0.331767
F3 SE APARTMENT DIRECT AIR 0.282576
F3 NE APARTMENT DIRECT AIR 0.253655
F3 N1 APARTMENT DIRECT AIR 0.179094
F3 N2 APARTMENT DIRECT AIR 0.177490
F3 S1 APARTMENT DIRECT AIR 0.191466
F3 S2 APARTMENT DIRECT AIR 0.192572
F4 SW APARTMENT DIRECT AIR 0.342486
F4 NW APARTMENT DIRECT AIR 0.334463
F4 SE APARTMENT DIRECT AIR 0.283590
F4 NE APARTMENT DIRECT AIR 0.255926
F4 N1 APARTMENT DIRECT AIR 0.181545
F4 N2 APARTMENT DIRECT AIR 0.179947
F4 S1 APARTMENT DIRECT AIR 0.194100
F4 S2 APARTMENT DIRECT AIR 0.194994
M SW APARTMENT DIRECT AIR 0.347058
M NW APARTMENT DIRECT AIR 0.339217
M SE APARTMENT DIRECT AIR 0.288480
M NE APARTMENT DIRECT AIR 0.260199
M N1 APARTMENT DIRECT AIR 0.185837
M N2 APARTMENT DIRECT AIR 0.184252
M S1 APARTMENT DIRECT AIR 0.198495
M S2 APARTMENT DIRECT AIR 0.199357
F6 SW APARTMENT DIRECT AIR 0.344659
F6 NW APARTMENT DIRECT AIR 0.336789
F6 SE APARTMENT DIRECT AIR 0.286688
F6 NE APARTMENT DIRECT AIR 0.257490
F6 N1 APARTMENT DIRECT AIR 0.183402
F6 N2 APARTMENT DIRECT AIR 0.181828
F6 S1 APARTMENT DIRECT AIR 0.196169
F6 S2 APARTMENT DIRECT AIR 0.197027
F7 SW APARTMENT DIRECT AIR 0.344589
F7 NW APARTMENT DIRECT AIR 0.336795
F7 SE APARTMENT DIRECT AIR 0.287134
F7 NE APARTMENT DIRECT AIR 0.257311
F7 N1 APARTMENT DIRECT AIR 0.183286
F7 N2 APARTMENT DIRECT AIR 0.181721
F7 S1 APARTMENT DIRECT AIR 0.196086
F7 S2 APARTMENT DIRECT AIR 0.196943
F8 SW APARTMENT DIRECT AIR 0.345965
F8 NW APARTMENT DIRECT AIR 0.338234
F8 SE APARTMENT DIRECT AIR 0.288856
F8 NE APARTMENT DIRECT AIR 0.258470
F8 N1 APARTMENT DIRECT AIR 0.184608
F8 N2 APARTMENT DIRECT AIR 0.183053
F8 S1 APARTMENT DIRECT AIR 0.197351
F8 S2 APARTMENT DIRECT AIR 0.198210
F9 SW APARTMENT DIRECT AIR 0.358570
F9 NW APARTMENT DIRECT AIR 0.350643
F9 SE APARTMENT DIRECT AIR 0.298457
F9 NE APARTMENT DIRECT AIR 0.263722
F9 N1 APARTMENT DIRECT AIR 0.195353
F9 N2 APARTMENT DIRECT AIR 0.193789
F9 S1 APARTMENT DIRECT AIR 0.205446
F9 S2 APARTMENT DIRECT AIR 0.206264
T SW APARTMENT DIRECT AIR 0.443737
T NW APARTMENT DIRECT AIR 0.430023
T SE APARTMENT DIRECT AIR 0.382005
T NE APARTMENT DIRECT AIR 0.337625
T N1 APARTMENT DIRECT AIR 0.256846
T N2 APARTMENT DIRECT AIR 0.256548
T S1 APARTMENT DIRECT AIR 0.298508
T S2 APARTMENT DIRECT AIR 0.299185


Branch

Maximum Flow Rate [m3/s]
AIRLOOP G SW MAIN BRANCH 0.261865
AIRLOOP G NW MAIN BRANCH 0.256992
AIRLOOP OFFICE MAIN BRANCH 0.375203
AIRLOOP G NE MAIN BRANCH 0.186744
AIRLOOP G N1 MAIN BRANCH 0.131508
AIRLOOP G N2 MAIN BRANCH 0.129530
AIRLOOP G S1 MAIN BRANCH 0.138971
AIRLOOP G S2 MAIN BRANCH 0.146296
AIRLOOP F2 SW MAIN BRANCH 0.336816
AIRLOOP F2 NW MAIN BRANCH 0.328085
AIRLOOP F2 SE MAIN BRANCH 0.302169
AIRLOOP F2 NE MAIN BRANCH 0.248800
AIRLOOP F2 N1 MAIN BRANCH 0.174616
AIRLOOP F2 N2 MAIN BRANCH 0.172998
AIRLOOP F2 S1 MAIN BRANCH 0.186418
AIRLOOP F2 S2 MAIN BRANCH 0.188984
AIRLOOP F3 SW MAIN BRANCH 0.339857
AIRLOOP F3 NW MAIN BRANCH 0.331767
AIRLOOP F3 SE MAIN BRANCH 0.282576
AIRLOOP F3 NE MAIN BRANCH 0.253655
AIRLOOP F3 N1 MAIN BRANCH 0.179094
AIRLOOP F3 N2 MAIN BRANCH 0.177490
AIRLOOP F3 S1 MAIN BRANCH 0.191466
AIRLOOP F3 S2 MAIN BRANCH 0.192572
AIRLOOP F4 SW MAIN BRANCH 0.342486
AIRLOOP F4 NW MAIN BRANCH 0.334463
AIRLOOP F4 SE MAIN BRANCH 0.283590
AIRLOOP F4 NE MAIN BRANCH 0.255926
AIRLOOP F4 N1 MAIN BRANCH 0.181545
AIRLOOP F4 N2 MAIN BRANCH 0.179947
AIRLOOP F4 S1 MAIN BRANCH 0.194100
AIRLOOP F4 S2 MAIN BRANCH 0.194994
AIRLOOP M SW MAIN BRANCH 0.347058
AIRLOOP M NW MAIN BRANCH 0.339217
AIRLOOP M SE MAIN BRANCH 0.288480
AIRLOOP M NE MAIN BRANCH 0.260199
AIRLOOP M N1 MAIN BRANCH 0.185837
AIRLOOP M N2 MAIN BRANCH 0.184252
AIRLOOP M S1 MAIN BRANCH 0.198495
AIRLOOP M S2 MAIN BRANCH 0.199357
AIRLOOP F6 SW MAIN BRANCH 0.344659
AIRLOOP F6 NW MAIN BRANCH 0.336789
AIRLOOP F6 SE MAIN BRANCH 0.286688
AIRLOOP F6 NE MAIN BRANCH 0.257490
AIRLOOP F6 N1 MAIN BRANCH 0.183402
AIRLOOP F6 N2 MAIN BRANCH 0.181828
AIRLOOP F6 S1 MAIN BRANCH 0.196169
AIRLOOP F6 S2 MAIN BRANCH 0.197027
AIRLOOP F7 SW MAIN BRANCH 0.344589
AIRLOOP F7 NW MAIN BRANCH 0.336795
AIRLOOP F7 SE MAIN BRANCH 0.287134
AIRLOOP F7 NE MAIN BRANCH 0.257311
AIRLOOP F7 N1 MAIN BRANCH 0.183286
AIRLOOP F7 N2 MAIN BRANCH 0.181721
AIRLOOP F7 S1 MAIN BRANCH 0.196086
AIRLOOP F7 S2 MAIN BRANCH 0.196943
AIRLOOP F8 SW MAIN BRANCH 0.345965
AIRLOOP F8 NW MAIN BRANCH 0.338234
AIRLOOP F8 SE MAIN BRANCH 0.288856
AIRLOOP F8 NE MAIN BRANCH 0.258470
AIRLOOP F8 N1 MAIN BRANCH 0.184608
AIRLOOP F8 N2 MAIN BRANCH 0.183053
AIRLOOP F8 S1 MAIN BRANCH 0.197351
AIRLOOP F8 S2 MAIN BRANCH 0.198210
AIRLOOP F9 SW MAIN BRANCH 0.358570
AIRLOOP F9 NW MAIN BRANCH 0.350643
AIRLOOP F9 SE MAIN BRANCH 0.298457
AIRLOOP F9 NE MAIN BRANCH 0.263722
AIRLOOP F9 N1 MAIN BRANCH 0.195353
AIRLOOP F9 N2 MAIN BRANCH 0.193789
AIRLOOP F9 S1 MAIN BRANCH 0.205446
AIRLOOP F9 S2 MAIN BRANCH 0.206264
AIRLOOP T SW MAIN BRANCH 0.443737
AIRLOOP T NW MAIN BRANCH 0.430023
AIRLOOP T SE MAIN BRANCH 0.382005
AIRLOOP T NE MAIN BRANCH 0.337625
AIRLOOP T N1 MAIN BRANCH 0.256846
AIRLOOP T N2 MAIN BRANCH 0.256548
AIRLOOP T S1 MAIN BRANCH 0.298508
AIRLOOP T S2 MAIN BRANCH 0.299185


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AIRLOOP G SW 0.261865
AIRLOOP G NW 0.256992
AIRLOOP OFFICE 0.375203
AIRLOOP G NE 0.186744
AIRLOOP G N1 0.131508
AIRLOOP G N2 0.129530
AIRLOOP G S1 0.138971
AIRLOOP G S2 0.146296
AIRLOOP F2 SW 0.336816
AIRLOOP F2 NW 0.328085
AIRLOOP F2 SE 0.302169
AIRLOOP F2 NE 0.248800
AIRLOOP F2 N1 0.174616
AIRLOOP F2 N2 0.172998
AIRLOOP F2 S1 0.186418
AIRLOOP F2 S2 0.188984
AIRLOOP F3 SW 0.339857
AIRLOOP F3 NW 0.331767
AIRLOOP F3 SE 0.282576
AIRLOOP F3 NE 0.253655
AIRLOOP F3 N1 0.179094
AIRLOOP F3 N2 0.177490
AIRLOOP F3 S1 0.191466
AIRLOOP F3 S2 0.192572
AIRLOOP F4 SW 0.342486
AIRLOOP F4 NW 0.334463
AIRLOOP F4 SE 0.283590
AIRLOOP F4 NE 0.255926
AIRLOOP F4 N1 0.181545
AIRLOOP F4 N2 0.179947
AIRLOOP F4 S1 0.194100
AIRLOOP F4 S2 0.194994
AIRLOOP M SW 0.347058
AIRLOOP M NW 0.339217
AIRLOOP M SE 0.288480
AIRLOOP M NE 0.260199
AIRLOOP M N1 0.185837
AIRLOOP M N2 0.184252
AIRLOOP M S1 0.198495
AIRLOOP M S2 0.199357
AIRLOOP F6 SW 0.344659
AIRLOOP F6 NW 0.336789
AIRLOOP F6 SE 0.286688
AIRLOOP F6 NE 0.257490
AIRLOOP F6 N1 0.183402
AIRLOOP F6 N2 0.181828
AIRLOOP F6 S1 0.196169
AIRLOOP F6 S2 0.197027
AIRLOOP F7 SW 0.344589
AIRLOOP F7 NW 0.336795
AIRLOOP F7 SE 0.287134
AIRLOOP F7 NE 0.257311
AIRLOOP F7 N1 0.183286
AIRLOOP F7 N2 0.181721
AIRLOOP F7 S1 0.196086
AIRLOOP F7 S2 0.196943
AIRLOOP F8 SW 0.345965
AIRLOOP F8 NW 0.338234
AIRLOOP F8 SE 0.288856
AIRLOOP F8 NE 0.258470
AIRLOOP F8 N1 0.184608
AIRLOOP F8 N2 0.183053
AIRLOOP F8 S1 0.197351
AIRLOOP F8 S2 0.198210
AIRLOOP F9 SW 0.358570
AIRLOOP F9 NW 0.350643
AIRLOOP F9 SE 0.298457
AIRLOOP F9 NE 0.263722
AIRLOOP F9 N1 0.195353
AIRLOOP F9 N2 0.193789
AIRLOOP F9 S1 0.205446
AIRLOOP F9 S2 0.206264
AIRLOOP T SW 0.443737
AIRLOOP T NW 0.430023
AIRLOOP T SE 0.382005
AIRLOOP T NE 0.337625
AIRLOOP T N1 0.256846
AIRLOOP T N2 0.256548
AIRLOOP T S1 0.298508
AIRLOOP T S2 0.299185


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AIRLOOP G SW OA CONTROLLER 0.261865 0.025952
AIRLOOP G NW OA CONTROLLER 0.256992 0.025952
AIRLOOP OFFICE OA CONTROLLER 0.375203 0.038103
AIRLOOP G NE OA CONTROLLER 0.186744 0.025952
AIRLOOP G N1 OA CONTROLLER 0.131508 0.025952
AIRLOOP G N2 OA CONTROLLER 0.129530 0.025952
AIRLOOP G S1 OA CONTROLLER 0.138971 0.025952
AIRLOOP G S2 OA CONTROLLER 0.146296 0.025952
AIRLOOP F2 SW OA CONTROLLER 0.336816 0.025952
AIRLOOP F2 NW OA CONTROLLER 0.328085 0.025952
AIRLOOP F2 SE OA CONTROLLER 0.302169 0.025952
AIRLOOP F2 NE OA CONTROLLER 0.248800 0.025952
AIRLOOP F2 N1 OA CONTROLLER 0.174616 0.025952
AIRLOOP F2 N2 OA CONTROLLER 0.172998 0.025952
AIRLOOP F2 S1 OA CONTROLLER 0.186418 0.025952
AIRLOOP F2 S2 OA CONTROLLER 0.188984 0.025952
AIRLOOP F3 SW OA CONTROLLER 0.339857 0.025952
AIRLOOP F3 NW OA CONTROLLER 0.331767 0.025952
AIRLOOP F3 SE OA CONTROLLER 0.282576 0.025952
AIRLOOP F3 NE OA CONTROLLER 0.253655 0.025952
AIRLOOP F3 N1 OA CONTROLLER 0.179094 0.025952
AIRLOOP F3 N2 OA CONTROLLER 0.177490 0.025952
AIRLOOP F3 S1 OA CONTROLLER 0.191466 0.025952
AIRLOOP F3 S2 OA CONTROLLER 0.192572 0.025952
AIRLOOP F4 SW OA CONTROLLER 0.342486 0.025952
AIRLOOP F4 NW OA CONTROLLER 0.334463 0.025952
AIRLOOP F4 SE OA CONTROLLER 0.283590 0.025952
AIRLOOP F4 NE OA CONTROLLER 0.255926 0.025952
AIRLOOP F4 N1 OA CONTROLLER 0.181545 0.025952
AIRLOOP F4 N2 OA CONTROLLER 0.179947 0.025952
AIRLOOP F4 S1 OA CONTROLLER 0.194100 0.025952
AIRLOOP F4 S2 OA CONTROLLER 0.194994 0.025952
AIRLOOP M SW OA CONTROLLER 0.347058 0.025952
AIRLOOP M NW OA CONTROLLER 0.339217 0.025952
AIRLOOP M SE OA CONTROLLER 0.288480 0.025952
AIRLOOP M NE OA CONTROLLER 0.260199 0.025952
AIRLOOP M N1 OA CONTROLLER 0.185837 0.025952
AIRLOOP M N2 OA CONTROLLER 0.184252 0.025952
AIRLOOP M S1 OA CONTROLLER 0.198495 0.025952
AIRLOOP M S2 OA CONTROLLER 0.199357 0.025952
AIRLOOP F6 SW OA CONTROLLER 0.344659 0.025952
AIRLOOP F6 NW OA CONTROLLER 0.336789 0.025952
AIRLOOP F6 SE OA CONTROLLER 0.286688 0.025952
AIRLOOP F6 NE OA CONTROLLER 0.257490 0.025952
AIRLOOP F6 N1 OA CONTROLLER 0.183402 0.025952
AIRLOOP F6 N2 OA CONTROLLER 0.181828 0.025952
AIRLOOP F6 S1 OA CONTROLLER 0.196169 0.025952
AIRLOOP F6 S2 OA CONTROLLER 0.197027 0.025952
AIRLOOP F7 SW OA CONTROLLER 0.344589 0.025952
AIRLOOP F7 NW OA CONTROLLER 0.336795 0.025952
AIRLOOP F7 SE OA CONTROLLER 0.287134 0.025952
AIRLOOP F7 NE OA CONTROLLER 0.257311 0.025952
AIRLOOP F7 N1 OA CONTROLLER 0.183286 0.025952
AIRLOOP F7 N2 OA CONTROLLER 0.181721 0.025952
AIRLOOP F7 S1 OA CONTROLLER 0.196086 0.025952
AIRLOOP F7 S2 OA CONTROLLER 0.196943 0.025952
AIRLOOP F8 SW OA CONTROLLER 0.345965 0.025952
AIRLOOP F8 NW OA CONTROLLER 0.338234 0.025952
AIRLOOP F8 SE OA CONTROLLER 0.288856 0.025952
AIRLOOP F8 NE OA CONTROLLER 0.258470 0.025952
AIRLOOP F8 N1 OA CONTROLLER 0.184608 0.025952
AIRLOOP F8 N2 OA CONTROLLER 0.183053 0.025952
AIRLOOP F8 S1 OA CONTROLLER 0.197351 0.025952
AIRLOOP F8 S2 OA CONTROLLER 0.198210 0.025952
AIRLOOP F9 SW OA CONTROLLER 0.358570 0.025952
AIRLOOP F9 NW OA CONTROLLER 0.350643 0.025952
AIRLOOP F9 SE OA CONTROLLER 0.298457 0.025952
AIRLOOP F9 NE OA CONTROLLER 0.263722 0.025952
AIRLOOP F9 N1 OA CONTROLLER 0.195353 0.025952
AIRLOOP F9 N2 OA CONTROLLER 0.193789 0.025952
AIRLOOP F9 S1 OA CONTROLLER 0.205446 0.025952
AIRLOOP F9 S2 OA CONTROLLER 0.206264 0.025952
AIRLOOP T SW OA CONTROLLER 0.443737 0.025952
AIRLOOP T NW OA CONTROLLER 0.430023 0.025952
AIRLOOP T SE OA CONTROLLER 0.382005 0.025952
AIRLOOP T NE OA CONTROLLER 0.337625 0.025952
AIRLOOP T N1 OA CONTROLLER 0.256846 0.025952
AIRLOOP T N2 OA CONTROLLER 0.256548 0.025952
AIRLOOP T S1 OA CONTROLLER 0.298508 0.025952
AIRLOOP T S2 OA CONTROLLER 0.299185 0.025952


COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity [W] Rated Sensible Cooling Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP COOLING MODE AIRLOOP G SW 0.261865 3205.13 2086.17 0.000070
HEAT PUMP COOLING MODE AIRLOOP G NW 0.256992 3136.29 2042.61 0.000069
HEAT PUMP COOLING MODE AIRLOOP OFFICE 0.375203 4571.65 2982.58 0.000100
HEAT PUMP COOLING MODE AIRLOOP G NE 0.186744 2235.31 1482.58 0.000049
HEAT PUMP COOLING MODE AIRLOOP G N1 0.131508 1610.05 1060.80 0.000035
HEAT PUMP COOLING MODE AIRLOOP G N2 0.129530 1585.74 1045.39 0.000035
HEAT PUMP COOLING MODE AIRLOOP G S1 0.138971 1790.21 1157.32 0.000039
HEAT PUMP COOLING MODE AIRLOOP G S2 0.146296 1874.97 1212.83 0.000041
HEAT PUMP COOLING MODE AIRLOOP F2 SW 0.336816 4083.63 2661.66 0.000089
HEAT PUMP COOLING MODE AIRLOOP F2 NW 0.328085 3968.98 2588.31 0.000087
HEAT PUMP COOLING MODE AIRLOOP F2 SE 0.302169 3709.07 2413.66 0.000081
HEAT PUMP COOLING MODE AIRLOOP F2 NE 0.248800 2955.28 1957.90 0.000065
HEAT PUMP COOLING MODE AIRLOOP F2 N1 0.174616 2120.03 1393.05 0.000046
HEAT PUMP COOLING MODE AIRLOOP F2 N2 0.172998 2100.22 1380.48 0.000046
HEAT PUMP COOLING MODE AIRLOOP F2 S1 0.186418 2348.56 1523.76 0.000051
HEAT PUMP COOLING MODE AIRLOOP F2 S2 0.188984 2379.83 1543.73 0.000052
HEAT PUMP COOLING MODE AIRLOOP F3 SW 0.339857 4099.50 2681.69 0.000090
HEAT PUMP COOLING MODE AIRLOOP F3 NW 0.331767 3992.78 2613.32 0.000087
HEAT PUMP COOLING MODE AIRLOOP F3 SE 0.282576 3450.55 2258.26 0.000075
HEAT PUMP COOLING MODE AIRLOOP F3 NE 0.253655 2994.18 1992.19 0.000065
HEAT PUMP COOLING MODE AIRLOOP F3 N1 0.179094 2162.96 1425.86 0.000047
HEAT PUMP COOLING MODE AIRLOOP F3 N2 0.177490 2143.35 1413.40 0.000047
HEAT PUMP COOLING MODE AIRLOOP F3 S1 0.191466 2398.22 1561.04 0.000052
HEAT PUMP COOLING MODE AIRLOOP F3 S2 0.192572 2411.72 1569.66 0.000053
HEAT PUMP COOLING MODE AIRLOOP F4 SW 0.342486 4115.74 2699.43 0.000090
HEAT PUMP COOLING MODE AIRLOOP F4 NW 0.334463 4016.31 2634.80 0.000088
HEAT PUMP COOLING MODE AIRLOOP F4 SE 0.283590 3447.95 2263.63 0.000075
HEAT PUMP COOLING MODE AIRLOOP F4 NE 0.255926 3006.86 2007.32 0.000066
HEAT PUMP COOLING MODE AIRLOOP F4 N1 0.181545 2184.05 1443.42 0.000048
HEAT PUMP COOLING MODE AIRLOOP F4 N2 0.179947 2164.55 1431.01 0.000047
HEAT PUMP COOLING MODE AIRLOOP F4 S1 0.194100 2421.46 1580.05 0.000053
HEAT PUMP COOLING MODE AIRLOOP F4 S2 0.194994 2432.36 1587.00 0.000053
HEAT PUMP COOLING MODE AIRLOOP M SW 0.347058 4158.53 2732.71 0.000091
HEAT PUMP COOLING MODE AIRLOOP M NW 0.339217 4061.50 2669.53 0.000089
HEAT PUMP COOLING MODE AIRLOOP M SE 0.288480 3495.15 2299.51 0.000076
HEAT PUMP COOLING MODE AIRLOOP M NE 0.260199 3046.55 2038.40 0.000067
HEAT PUMP COOLING MODE AIRLOOP M N1 0.185837 2231.85 1479.05 0.000049
HEAT PUMP COOLING MODE AIRLOOP M N2 0.184252 2212.59 1466.76 0.000048
HEAT PUMP COOLING MODE AIRLOOP M S1 0.198495 2467.66 1613.00 0.000054
HEAT PUMP COOLING MODE AIRLOOP M S2 0.199357 2478.17 1619.71 0.000054
HEAT PUMP COOLING MODE AIRLOOP F6 SW 0.344659 4118.48 2712.30 0.000090
HEAT PUMP COOLING MODE AIRLOOP F6 NW 0.336789 4021.15 2648.90 0.000088
HEAT PUMP COOLING MODE AIRLOOP F6 SE 0.286688 3463.15 2283.91 0.000076
HEAT PUMP COOLING MODE AIRLOOP F6 NE 0.257490 3003.59 2015.76 0.000066
HEAT PUMP COOLING MODE AIRLOOP F6 N1 0.183402 2196.01 1459.13 0.000048
HEAT PUMP COOLING MODE AIRLOOP F6 N2 0.181828 2176.92 1446.93 0.000048
HEAT PUMP COOLING MODE AIRLOOP F6 S1 0.196169 2433.36 1593.91 0.000053
HEAT PUMP COOLING MODE AIRLOOP F6 S2 0.197027 2443.82 1600.59 0.000053
HEAT PUMP COOLING MODE AIRLOOP F7 SW 0.344589 4108.10 2710.17 0.000090
HEAT PUMP COOLING MODE AIRLOOP F7 NW 0.336795 4011.78 2647.38 0.000088
HEAT PUMP COOLING MODE AIRLOOP F7 SE 0.287134 3459.59 2285.87 0.000076
HEAT PUMP COOLING MODE AIRLOOP F7 NE 0.257311 3006.60 2018.43 0.000066
HEAT PUMP COOLING MODE AIRLOOP F7 N1 0.183286 2189.24 1457.34 0.000048
HEAT PUMP COOLING MODE AIRLOOP F7 N2 0.181721 2170.27 1445.21 0.000047
HEAT PUMP COOLING MODE AIRLOOP F7 S1 0.196086 2427.05 1592.38 0.000053
HEAT PUMP COOLING MODE AIRLOOP F7 S2 0.196943 2437.49 1599.05 0.000053
HEAT PUMP COOLING MODE AIRLOOP F8 SW 0.345965 4116.29 2719.41 0.000090
HEAT PUMP COOLING MODE AIRLOOP F8 NW 0.338234 4020.82 2657.12 0.000088
HEAT PUMP COOLING MODE AIRLOOP F8 SE 0.288856 3472.41 2297.88 0.000076
HEAT PUMP COOLING MODE AIRLOOP F8 NE 0.258470 3012.72 2026.10 0.000066
HEAT PUMP COOLING MODE AIRLOOP F8 N1 0.184608 2200.53 1466.80 0.000048
HEAT PUMP COOLING MODE AIRLOOP F8 N2 0.183053 2181.69 1454.75 0.000048
HEAT PUMP COOLING MODE AIRLOOP F8 S1 0.197351 2437.62 1601.42 0.000053
HEAT PUMP COOLING MODE AIRLOOP F8 S2 0.198210 2448.08 1608.09 0.000053
HEAT PUMP COOLING MODE AIRLOOP F9 SW 0.358570 4261.51 2815.74 0.000093
HEAT PUMP COOLING MODE AIRLOOP F9 NW 0.350643 4163.87 2751.97 0.000091
HEAT PUMP COOLING MODE AIRLOOP F9 SE 0.298457 3585.82 2372.82 0.000078
HEAT PUMP COOLING MODE AIRLOOP F9 NE 0.263722 3068.81 2065.52 0.000067
HEAT PUMP COOLING MODE AIRLOOP F9 N1 0.195353 2326.72 1549.40 0.000051
HEAT PUMP COOLING MODE AIRLOOP F9 N2 0.193789 2307.77 1537.29 0.000050
HEAT PUMP COOLING MODE AIRLOOP F9 S1 0.205446 2531.51 1663.57 0.000055
HEAT PUMP COOLING MODE AIRLOOP F9 S2 0.206264 2541.48 1669.94 0.000056
HEAT PUMP COOLING MODE AIRLOOP T SW 0.443737 5311.88 3485.44 0.000116
HEAT PUMP COOLING MODE AIRLOOP T NW 0.430023 5134.82 3374.01 0.000112
HEAT PUMP COOLING MODE AIRLOOP T SE 0.382005 4586.60 3017.05 0.000100
HEAT PUMP COOLING MODE AIRLOOP T NE 0.337625 4053.30 2675.11 0.000089
HEAT PUMP COOLING MODE AIRLOOP T N1 0.256846 3150.60 2061.78 0.000069
HEAT PUMP COOLING MODE AIRLOOP T N2 0.256548 3147.08 2059.48 0.000069
HEAT PUMP COOLING MODE AIRLOOP T S1 0.298508 3656.71 2384.97 0.000080
HEAT PUMP COOLING MODE AIRLOOP T S2 0.299185 3665.00 2390.23 0.000080


AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP G SW DXAC HEAT PUMP 0.261865 0.261865 0.261865 0.261865 3205.13 3205.13 2756.67 1.00
AIRLOOP G NW DXAC HEAT PUMP 0.256992 0.256992 0.256992 0.256992 3136.29 3136.29 2757.08 1.00
AIRLOOP OFFICE DXAC HEAT PUMP 0.375203 0.375203 0.375203 0.375203 4571.65 4571.65 3460.54 1.00
AIRLOOP G NE DXAC HEAT PUMP 0.186744 0.186744 0.186744 0.186744 2235.31 2235.31 2757.08 1.00
AIRLOOP G N1 DXAC HEAT PUMP 0.131508 0.131508 0.131508 0.131508 1610.05 1610.05 2051.84 1.00
AIRLOOP G N2 DXAC HEAT PUMP 0.129530 0.129530 0.129530 0.129530 1585.74 1585.74 2051.84 1.00
AIRLOOP G S1 DXAC HEAT PUMP 0.138971 0.138971 0.138971 0.138971 1790.21 1790.21 2047.88 1.00
AIRLOOP G S2 DXAC HEAT PUMP 0.146296 0.146296 0.146296 0.146296 1874.97 1874.97 2054.16 1.00
AIRLOOP F2 SW DXAC HEAT PUMP 0.336816 0.336816 0.336816 0.336816 4083.63 4083.63 2735.79 1.00
AIRLOOP F2 NW DXAC HEAT PUMP 0.328085 0.328085 0.328085 0.328085 3968.98 3968.98 2733.39 1.00
AIRLOOP F2 SE DXAC HEAT PUMP 0.302169 0.302169 0.302169 0.302169 3709.07 3709.07 2754.50 1.00
AIRLOOP F2 NE DXAC HEAT PUMP 0.248800 0.248800 0.248800 0.248800 2955.28 2955.28 2733.39 1.00
AIRLOOP F2 N1 DXAC HEAT PUMP 0.174616 0.174616 0.174616 0.174616 2120.03 2120.03 1854.16 1.00
AIRLOOP F2 N2 DXAC HEAT PUMP 0.172998 0.172998 0.172998 0.172998 2100.22 2100.22 1854.16 1.00
AIRLOOP F2 S1 DXAC HEAT PUMP 0.186418 0.186418 0.186418 0.186418 2348.56 2348.56 1859.28 1.00
AIRLOOP F2 S2 DXAC HEAT PUMP 0.188984 0.188984 0.188984 0.188984 2379.83 2379.83 1860.51 1.00
AIRLOOP F3 SW DXAC HEAT PUMP 0.339857 0.339857 0.339857 0.339857 4099.50 4099.50 2759.41 1.00
AIRLOOP F3 NW DXAC HEAT PUMP 0.331767 0.331767 0.331767 0.331767 3992.78 3992.78 2759.94 1.00
AIRLOOP F3 SE DXAC HEAT PUMP 0.282576 0.282576 0.282576 0.282576 3450.55 3450.55 2761.48 1.00
AIRLOOP F3 NE DXAC HEAT PUMP 0.253655 0.253655 0.253655 0.253655 2994.18 2994.18 2759.94 1.00
AIRLOOP F3 N1 DXAC HEAT PUMP 0.179094 0.179094 0.179094 0.179094 2162.96 2162.96 1835.79 1.00
AIRLOOP F3 N2 DXAC HEAT PUMP 0.177490 0.177490 0.177490 0.177490 2143.35 2143.35 1835.79 1.00
AIRLOOP F3 S1 DXAC HEAT PUMP 0.191466 0.191466 0.191466 0.191466 2398.22 2398.22 1835.99 1.00
AIRLOOP F3 S2 DXAC HEAT PUMP 0.192572 0.192572 0.192572 0.192572 2411.72 2411.72 1836.18 1.00
AIRLOOP F4 SW DXAC HEAT PUMP 0.342486 0.342486 0.342486 0.342486 4115.74 4115.74 2823.85 1.00
AIRLOOP F4 NW DXAC HEAT PUMP 0.334463 0.334463 0.334463 0.334463 4016.31 4016.31 2826.48 1.00
AIRLOOP F4 SE DXAC HEAT PUMP 0.283590 0.283590 0.283590 0.283590 3447.95 3447.95 2824.06 1.00
AIRLOOP F4 NE DXAC HEAT PUMP 0.255926 0.255926 0.255926 0.255926 3006.86 3006.86 2826.48 1.00
AIRLOOP F4 N1 DXAC HEAT PUMP 0.181545 0.181545 0.181545 0.181545 2184.05 2184.05 1866.24 1.00
AIRLOOP F4 N2 DXAC HEAT PUMP 0.179947 0.179947 0.179947 0.179947 2164.55 2164.55 1866.24 1.00
AIRLOOP F4 S1 DXAC HEAT PUMP 0.194100 0.194100 0.194100 0.194100 2421.46 2421.46 1864.05 1.00
AIRLOOP F4 S2 DXAC HEAT PUMP 0.194994 0.194994 0.194994 0.194994 2432.36 2432.36 1864.07 1.00
AIRLOOP M SW DXAC HEAT PUMP 0.347058 0.347058 0.347058 0.347058 4158.53 4158.53 2864.82 1.00
AIRLOOP M NW DXAC HEAT PUMP 0.339217 0.339217 0.339217 0.339217 4061.50 4061.50 2867.93 1.00
AIRLOOP M SE DXAC HEAT PUMP 0.288480 0.288480 0.288480 0.288480 3495.15 3495.15 2864.84 1.00
AIRLOOP M NE DXAC HEAT PUMP 0.260199 0.260199 0.260199 0.260199 3046.55 3046.55 2867.93 1.00
AIRLOOP M N1 DXAC HEAT PUMP 0.185837 0.185837 0.185837 0.185837 2231.85 2231.85 1879.85 1.00
AIRLOOP M N2 DXAC HEAT PUMP 0.184252 0.184252 0.184252 0.184252 2212.59 2212.59 1879.85 1.00
AIRLOOP M S1 DXAC HEAT PUMP 0.198495 0.198495 0.198495 0.198495 2467.66 2467.66 1877.13 1.00
AIRLOOP M S2 DXAC HEAT PUMP 0.199357 0.199357 0.199357 0.199357 2478.17 2478.17 1877.13 1.00
AIRLOOP F6 SW DXAC HEAT PUMP 0.344659 0.344659 0.344659 0.344659 4118.48 4118.48 2960.79 1.00
AIRLOOP F6 NW DXAC HEAT PUMP 0.336789 0.336789 0.336789 0.336789 4021.15 4021.15 2965.87 1.00
AIRLOOP F6 SE DXAC HEAT PUMP 0.286688 0.286688 0.286688 0.286688 3463.15 3463.15 2960.79 1.00
AIRLOOP F6 NE DXAC HEAT PUMP 0.257490 0.257490 0.257490 0.257490 3003.59 3003.59 2965.87 1.00
AIRLOOP F6 N1 DXAC HEAT PUMP 0.183402 0.183402 0.183402 0.183402 2196.01 2196.01 1951.07 1.00
AIRLOOP F6 N2 DXAC HEAT PUMP 0.181828 0.181828 0.181828 0.181828 2176.92 2176.92 1951.07 1.00
AIRLOOP F6 S1 DXAC HEAT PUMP 0.196169 0.196169 0.196169 0.196169 2433.36 2433.36 1946.32 1.00
AIRLOOP F6 S2 DXAC HEAT PUMP 0.197027 0.197027 0.197027 0.197027 2443.82 2443.82 1946.32 1.00
AIRLOOP F7 SW DXAC HEAT PUMP 0.344589 0.344589 0.344589 0.344589 4108.10 4108.10 3029.36 1.00
AIRLOOP F7 NW DXAC HEAT PUMP 0.336795 0.336795 0.336795 0.336795 4011.78 4011.78 3035.21 1.00
AIRLOOP F7 SE DXAC HEAT PUMP 0.287134 0.287134 0.287134 0.287134 3459.59 3459.59 3029.36 1.00
AIRLOOP F7 NE DXAC HEAT PUMP 0.257311 0.257311 0.257311 0.257311 3006.60 3006.60 3035.21 1.00
AIRLOOP F7 N1 DXAC HEAT PUMP 0.183286 0.183286 0.183286 0.183286 2189.24 2189.24 1998.43 1.00
AIRLOOP F7 N2 DXAC HEAT PUMP 0.181721 0.181721 0.181721 0.181721 2170.27 2170.27 1998.43 1.00
AIRLOOP F7 S1 DXAC HEAT PUMP 0.196086 0.196086 0.196086 0.196086 2427.05 2427.05 1992.91 1.00
AIRLOOP F7 S2 DXAC HEAT PUMP 0.196943 0.196943 0.196943 0.196943 2437.49 2437.49 1992.91 1.00
AIRLOOP F8 SW DXAC HEAT PUMP 0.345965 0.345965 0.345965 0.345965 4116.29 4116.29 3100.69 1.00
AIRLOOP F8 NW DXAC HEAT PUMP 0.338234 0.338234 0.338234 0.338234 4020.82 4020.82 3106.95 1.00
AIRLOOP F8 SE DXAC HEAT PUMP 0.288856 0.288856 0.288856 0.288856 3472.41 3472.41 3100.69 1.00
AIRLOOP F8 NE DXAC HEAT PUMP 0.258470 0.258470 0.258470 0.258470 3012.72 3012.72 3106.95 1.00
AIRLOOP F8 N1 DXAC HEAT PUMP 0.184608 0.184608 0.184608 0.184608 2200.53 2200.53 2050.70 1.00
AIRLOOP F8 N2 DXAC HEAT PUMP 0.183053 0.183053 0.183053 0.183053 2181.69 2181.69 2050.70 1.00
AIRLOOP F8 S1 DXAC HEAT PUMP 0.197351 0.197351 0.197351 0.197351 2437.62 2437.62 2044.75 1.00
AIRLOOP F8 S2 DXAC HEAT PUMP 0.198210 0.198210 0.198210 0.198210 2448.08 2448.08 2044.75 1.00
AIRLOOP F9 SW DXAC HEAT PUMP 0.358570 0.358570 0.358570 0.358570 4261.51 4261.51 3289.74 1.00
AIRLOOP F9 NW DXAC HEAT PUMP 0.350643 0.350643 0.350643 0.350643 4163.87 4163.87 3294.09 1.00
AIRLOOP F9 SE DXAC HEAT PUMP 0.298457 0.298457 0.298457 0.298457 3585.82 3585.82 3289.74 1.00
AIRLOOP F9 NE DXAC HEAT PUMP 0.263722 0.263722 0.263722 0.263722 3068.81 3068.81 3294.09 1.00
AIRLOOP F9 N1 DXAC HEAT PUMP 0.195353 0.195353 0.195353 0.195353 2326.72 2326.72 2212.13 1.00
AIRLOOP F9 N2 DXAC HEAT PUMP 0.193789 0.193789 0.193789 0.193789 2307.77 2307.77 2212.13 1.00
AIRLOOP F9 S1 DXAC HEAT PUMP 0.205446 0.205446 0.205446 0.205446 2531.51 2531.51 2207.63 1.00
AIRLOOP F9 S2 DXAC HEAT PUMP 0.206264 0.206264 0.206264 0.206264 2541.48 2541.48 2207.63 1.00
AIRLOOP T SW DXAC HEAT PUMP 0.443737 0.443737 0.443737 0.443737 5311.88 5311.88 3902.78 1.00
AIRLOOP T NW DXAC HEAT PUMP 0.430023 0.430023 0.430023 0.430023 5134.82 5134.82 3913.70 1.00
AIRLOOP T SE DXAC HEAT PUMP 0.382005 0.382005 0.382005 0.382005 4586.60 4586.60 3902.78 1.00
AIRLOOP T NE DXAC HEAT PUMP 0.337625 0.337625 0.337625 0.337625 4053.30 4053.30 3913.70 1.00
AIRLOOP T N1 DXAC HEAT PUMP 0.256846 0.256846 0.256846 0.256846 3150.60 3150.60 2870.02 1.00
AIRLOOP T N2 DXAC HEAT PUMP 0.256548 0.256548 0.256548 0.256548 3147.08 3147.08 2870.02 1.00
AIRLOOP T S1 DXAC HEAT PUMP 0.298508 0.298508 0.298508 0.298508 3656.71 3656.71 2856.07 1.00
AIRLOOP T S2 DXAC HEAT PUMP 0.299185 0.299185 0.299185 0.299185 3665.00 3665.00 2856.07 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
AIRLOOP G SW SUPPLY FAN 0.261865
AIRLOOP G NW SUPPLY FAN 0.256992
AIRLOOP OFFICE SUPPLY FAN 0.375203
AIRLOOP G NE SUPPLY FAN 0.186744
AIRLOOP G N1 SUPPLY FAN 0.131508
AIRLOOP G N2 SUPPLY FAN 0.129530
AIRLOOP G S1 SUPPLY FAN 0.138971
AIRLOOP G S2 SUPPLY FAN 0.146296
AIRLOOP F2 SW SUPPLY FAN 0.336816
AIRLOOP F2 NW SUPPLY FAN 0.328085
AIRLOOP F2 SE SUPPLY FAN 0.302169
AIRLOOP F2 NE SUPPLY FAN 0.248800
AIRLOOP F2 N1 SUPPLY FAN 0.174616
AIRLOOP F2 N2 SUPPLY FAN 0.172998
AIRLOOP F2 S1 SUPPLY FAN 0.186418
AIRLOOP F2 S2 SUPPLY FAN 0.188984
AIRLOOP F3 SW SUPPLY FAN 0.339857
AIRLOOP F3 NW SUPPLY FAN 0.331767
AIRLOOP F3 SE SUPPLY FAN 0.282576
AIRLOOP F3 NE SUPPLY FAN 0.253655
AIRLOOP F3 N1 SUPPLY FAN 0.179094
AIRLOOP F3 N2 SUPPLY FAN 0.177490
AIRLOOP F3 S1 SUPPLY FAN 0.191466
AIRLOOP F3 S2 SUPPLY FAN 0.192572
AIRLOOP F4 SW SUPPLY FAN 0.342486
AIRLOOP F4 NW SUPPLY FAN 0.334463
AIRLOOP F4 SE SUPPLY FAN 0.283590
AIRLOOP F4 NE SUPPLY FAN 0.255926
AIRLOOP F4 N1 SUPPLY FAN 0.181545
AIRLOOP F4 N2 SUPPLY FAN 0.179947
AIRLOOP F4 S1 SUPPLY FAN 0.194100
AIRLOOP F4 S2 SUPPLY FAN 0.194994
AIRLOOP M SW SUPPLY FAN 0.347058
AIRLOOP M NW SUPPLY FAN 0.339217
AIRLOOP M SE SUPPLY FAN 0.288480
AIRLOOP M NE SUPPLY FAN 0.260199
AIRLOOP M N1 SUPPLY FAN 0.185837
AIRLOOP M N2 SUPPLY FAN 0.184252
AIRLOOP M S1 SUPPLY FAN 0.198495
AIRLOOP M S2 SUPPLY FAN 0.199357
AIRLOOP F6 SW SUPPLY FAN 0.344659
AIRLOOP F6 NW SUPPLY FAN 0.336789
AIRLOOP F6 SE SUPPLY FAN 0.286688
AIRLOOP F6 NE SUPPLY FAN 0.257490
AIRLOOP F6 N1 SUPPLY FAN 0.183402
AIRLOOP F6 N2 SUPPLY FAN 0.181828
AIRLOOP F6 S1 SUPPLY FAN 0.196169
AIRLOOP F6 S2 SUPPLY FAN 0.197027
AIRLOOP F7 SW SUPPLY FAN 0.344589
AIRLOOP F7 NW SUPPLY FAN 0.336795
AIRLOOP F7 SE SUPPLY FAN 0.287134
AIRLOOP F7 NE SUPPLY FAN 0.257311
AIRLOOP F7 N1 SUPPLY FAN 0.183286
AIRLOOP F7 N2 SUPPLY FAN 0.181721
AIRLOOP F7 S1 SUPPLY FAN 0.196086
AIRLOOP F7 S2 SUPPLY FAN 0.196943
AIRLOOP F8 SW SUPPLY FAN 0.345965
AIRLOOP F8 NW SUPPLY FAN 0.338234
AIRLOOP F8 SE SUPPLY FAN 0.288856
AIRLOOP F8 NE SUPPLY FAN 0.258470
AIRLOOP F8 N1 SUPPLY FAN 0.184608
AIRLOOP F8 N2 SUPPLY FAN 0.183053
AIRLOOP F8 S1 SUPPLY FAN 0.197351
AIRLOOP F8 S2 SUPPLY FAN 0.198210
AIRLOOP F9 SW SUPPLY FAN 0.358570
AIRLOOP F9 NW SUPPLY FAN 0.350643
AIRLOOP F9 SE SUPPLY FAN 0.298457
AIRLOOP F9 NE SUPPLY FAN 0.263722
AIRLOOP F9 N1 SUPPLY FAN 0.195353
AIRLOOP F9 N2 SUPPLY FAN 0.193789
AIRLOOP F9 S1 SUPPLY FAN 0.205446
AIRLOOP F9 S2 SUPPLY FAN 0.206264
AIRLOOP T SW SUPPLY FAN 0.443737
AIRLOOP T NW SUPPLY FAN 0.430023
AIRLOOP T SE SUPPLY FAN 0.382005
AIRLOOP T NE SUPPLY FAN 0.337625
AIRLOOP T N1 SUPPLY FAN 0.256846
AIRLOOP T N2 SUPPLY FAN 0.256548
AIRLOOP T S1 SUPPLY FAN 0.298508
AIRLOOP T S2 SUPPLY FAN 0.299185


COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Rated Air Flow Rate [m3/s] Rated Heating Capacity [W] Rated Water Flow Rate [m3/s]
HEAT PUMP HEATING MODE AIRLOOP G SW 0.261865 3205.13 0.000070
HEAT PUMP HEATING MODE AIRLOOP G NW 0.256992 3136.29 0.000069
HEAT PUMP HEATING MODE AIRLOOP OFFICE 0.375203 4571.65 0.000100
HEAT PUMP HEATING MODE AIRLOOP G NE 0.186744 2235.31 0.000049
HEAT PUMP HEATING MODE AIRLOOP G N1 0.131508 1610.05 0.000035
HEAT PUMP HEATING MODE AIRLOOP G N2 0.129530 1585.74 0.000035
HEAT PUMP HEATING MODE AIRLOOP G S1 0.138971 1790.21 0.000039
HEAT PUMP HEATING MODE AIRLOOP G S2 0.146296 1874.97 0.000041
HEAT PUMP HEATING MODE AIRLOOP F2 SW 0.336816 4083.63 0.000089
HEAT PUMP HEATING MODE AIRLOOP F2 NW 0.328085 3968.98 0.000087
HEAT PUMP HEATING MODE AIRLOOP F2 SE 0.302169 3709.07 0.000081
HEAT PUMP HEATING MODE AIRLOOP F2 NE 0.248800 2955.28 0.000065
HEAT PUMP HEATING MODE AIRLOOP F2 N1 0.174616 2120.03 0.000046
HEAT PUMP HEATING MODE AIRLOOP F2 N2 0.172998 2100.22 0.000046
HEAT PUMP HEATING MODE AIRLOOP F2 S1 0.186418 2348.56 0.000051
HEAT PUMP HEATING MODE AIRLOOP F2 S2 0.188984 2379.83 0.000052
HEAT PUMP HEATING MODE AIRLOOP F3 SW 0.339857 4099.50 0.000090
HEAT PUMP HEATING MODE AIRLOOP F3 NW 0.331767 3992.78 0.000087
HEAT PUMP HEATING MODE AIRLOOP F3 SE 0.282576 3450.55 0.000075
HEAT PUMP HEATING MODE AIRLOOP F3 NE 0.253655 2994.18 0.000065
HEAT PUMP HEATING MODE AIRLOOP F3 N1 0.179094 2162.96 0.000047
HEAT PUMP HEATING MODE AIRLOOP F3 N2 0.177490 2143.35 0.000047
HEAT PUMP HEATING MODE AIRLOOP F3 S1 0.191466 2398.22 0.000052
HEAT PUMP HEATING MODE AIRLOOP F3 S2 0.192572 2411.72 0.000053
HEAT PUMP HEATING MODE AIRLOOP F4 SW 0.342486 4115.74 0.000090
HEAT PUMP HEATING MODE AIRLOOP F4 NW 0.334463 4016.31 0.000088
HEAT PUMP HEATING MODE AIRLOOP F4 SE 0.283590 3447.95 0.000075
HEAT PUMP HEATING MODE AIRLOOP F4 NE 0.255926 3006.86 0.000066
HEAT PUMP HEATING MODE AIRLOOP F4 N1 0.181545 2184.05 0.000048
HEAT PUMP HEATING MODE AIRLOOP F4 N2 0.179947 2164.55 0.000047
HEAT PUMP HEATING MODE AIRLOOP F4 S1 0.194100 2421.46 0.000053
HEAT PUMP HEATING MODE AIRLOOP F4 S2 0.194994 2432.36 0.000053
HEAT PUMP HEATING MODE AIRLOOP M SW 0.347058 4158.53 0.000091
HEAT PUMP HEATING MODE AIRLOOP M NW 0.339217 4061.50 0.000089
HEAT PUMP HEATING MODE AIRLOOP M SE 0.288480 3495.15 0.000076
HEAT PUMP HEATING MODE AIRLOOP M NE 0.260199 3046.55 0.000067
HEAT PUMP HEATING MODE AIRLOOP M N1 0.185837 2231.85 0.000049
HEAT PUMP HEATING MODE AIRLOOP M N2 0.184252 2212.59 0.000048
HEAT PUMP HEATING MODE AIRLOOP M S1 0.198495 2467.66 0.000054
HEAT PUMP HEATING MODE AIRLOOP M S2 0.199357 2478.17 0.000054
HEAT PUMP HEATING MODE AIRLOOP F6 SW 0.344659 4118.48 0.000090
HEAT PUMP HEATING MODE AIRLOOP F6 NW 0.336789 4021.15 0.000088
HEAT PUMP HEATING MODE AIRLOOP F6 SE 0.286688 3463.15 0.000076
HEAT PUMP HEATING MODE AIRLOOP F6 NE 0.257490 3003.59 0.000066
HEAT PUMP HEATING MODE AIRLOOP F6 N1 0.183402 2196.01 0.000048
HEAT PUMP HEATING MODE AIRLOOP F6 N2 0.181828 2176.92 0.000048
HEAT PUMP HEATING MODE AIRLOOP F6 S1 0.196169 2433.36 0.000053
HEAT PUMP HEATING MODE AIRLOOP F6 S2 0.197027 2443.82 0.000053
HEAT PUMP HEATING MODE AIRLOOP F7 SW 0.344589 4108.10 0.000090
HEAT PUMP HEATING MODE AIRLOOP F7 NW 0.336795 4011.78 0.000088
HEAT PUMP HEATING MODE AIRLOOP F7 SE 0.287134 3459.59 0.000076
HEAT PUMP HEATING MODE AIRLOOP F7 NE 0.257311 3006.60 0.000066
HEAT PUMP HEATING MODE AIRLOOP F7 N1 0.183286 2189.24 0.000048
HEAT PUMP HEATING MODE AIRLOOP F7 N2 0.181721 2170.27 0.000047
HEAT PUMP HEATING MODE AIRLOOP F7 S1 0.196086 2427.05 0.000053
HEAT PUMP HEATING MODE AIRLOOP F7 S2 0.196943 2437.49 0.000053
HEAT PUMP HEATING MODE AIRLOOP F8 SW 0.345965 4116.29 0.000090
HEAT PUMP HEATING MODE AIRLOOP F8 NW 0.338234 4020.82 0.000088
HEAT PUMP HEATING MODE AIRLOOP F8 SE 0.288856 3472.41 0.000076
HEAT PUMP HEATING MODE AIRLOOP F8 NE 0.258470 3012.72 0.000066
HEAT PUMP HEATING MODE AIRLOOP F8 N1 0.184608 2200.53 0.000048
HEAT PUMP HEATING MODE AIRLOOP F8 N2 0.183053 2181.69 0.000048
HEAT PUMP HEATING MODE AIRLOOP F8 S1 0.197351 2437.62 0.000053
HEAT PUMP HEATING MODE AIRLOOP F8 S2 0.198210 2448.08 0.000053
HEAT PUMP HEATING MODE AIRLOOP F9 SW 0.358570 4261.51 0.000093
HEAT PUMP HEATING MODE AIRLOOP F9 NW 0.350643 4163.87 0.000091
HEAT PUMP HEATING MODE AIRLOOP F9 SE 0.298457 3585.82 0.000078
HEAT PUMP HEATING MODE AIRLOOP F9 NE 0.263722 3068.81 0.000067
HEAT PUMP HEATING MODE AIRLOOP F9 N1 0.195353 2326.72 0.000051
HEAT PUMP HEATING MODE AIRLOOP F9 N2 0.193789 2307.77 0.000050
HEAT PUMP HEATING MODE AIRLOOP F9 S1 0.205446 2531.51 0.000055
HEAT PUMP HEATING MODE AIRLOOP F9 S2 0.206264 2541.48 0.000056
HEAT PUMP HEATING MODE AIRLOOP T SW 0.443737 5311.88 0.000116
HEAT PUMP HEATING MODE AIRLOOP T NW 0.430023 5134.82 0.000112
HEAT PUMP HEATING MODE AIRLOOP T SE 0.382005 4586.60 0.000100
HEAT PUMP HEATING MODE AIRLOOP T NE 0.337625 4053.30 0.000089
HEAT PUMP HEATING MODE AIRLOOP T N1 0.256846 3150.60 0.000069
HEAT PUMP HEATING MODE AIRLOOP T N2 0.256548 3147.08 0.000069
HEAT PUMP HEATING MODE AIRLOOP T S1 0.298508 3656.71 0.000080
HEAT PUMP HEATING MODE AIRLOOP T S2 0.299185 3665.00 0.000080


Coil:Heating:Electric

Nominal Capacity [W]
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW 2756.67
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW 2757.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE 3460.54
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE 2757.08
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 2051.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 2051.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 2047.88
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 2054.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW 2735.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW 2733.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE 2754.50
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE 2733.39
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 1854.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 1854.16
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 1859.28
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 1860.51
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW 2759.41
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW 2759.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE 2761.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE 2759.94
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 1835.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 1835.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 1835.99
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 1836.18
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW 2823.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW 2826.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE 2824.06
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE 2826.48
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 1866.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 1866.24
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 1864.05
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 1864.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW 2864.82
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW 2867.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE 2864.84
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE 2867.93
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 1879.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 1879.85
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 1877.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 1877.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW 2960.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW 2965.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE 2960.79
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE 2965.87
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 1951.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 1951.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 1946.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 1946.32
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW 3029.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW 3035.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE 3029.36
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE 3035.21
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 1998.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 1998.43
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 1992.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 1992.91
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW 3100.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW 3106.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE 3100.69
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE 3106.95
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 2050.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 2050.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 2044.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 2044.75
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW 3289.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW 3294.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE 3289.74
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE 3294.09
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 2212.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 2212.13
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 2207.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 2207.63
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW 3902.78
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW 3913.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE 3902.78
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE 3913.70
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 2870.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 2870.02
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 2856.07
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 2856.07


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYS1 0.000289 0.325214
SINGLE WATER PLANT LOOP 0.005337 6.00


Boiler:HotWater

Design Water Flow Rate [m3/s]
CENTRAL BOILER 0.005337


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000289


EvaporativeFluidCooler:SingleSpeed

Design Water Flow Rate [m3/s] Fan Power at Design Air Flow Rate [W] Design Air Flow Rate [m3/s] U-Factor Times Area Value at Design Air Flow Rate [W/C]
CENTRAL TOWER 0.005337 2576.43 8.24 6567.57


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYS1 PUMP 0.000289 36.93
PLANT CIRC PUMP 0.005337 1704.37



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW3 |
G WWALL SWA GWINDOW2 |
G NWALL NWA GWINDOW4 |
G WWALL NWA GWINDOW6 |
G SWALL SEA GWINDOW1 |
G EWALL SEA GWINDOW8 |
G NWALL NEA GWINDOW5 |
G EWALL NEA GWINDOW7 |
G NWALL N1A GWINDOW9 |
G NWALL N2A GWINDOW10 |
G SWALL S1A GWINDOW11 |
G SWALL S2A GWINDOW12 |
G WWALL C GWINDOW13 |
G EWALL C ENTRANCE DOOR |
F2 WWALL SWA F2WINDOW2 |
F2 SWALL SWA F2WINDOW3 |
F2 NWALL NWA F2WINDOW4 |
F2 WWALL NWA F2WINDOW6 |
F2 EWALL SEA F2WINDOW8 |
F2 SWALL SEA F2WINDOW1 |
F2 NWALL NEA F2WINDOW5 |
F2 EWALL NEA F2WINDOW7 |
F2 NWALL N1A F2WINDOW9 |
F2 NWALL N2A F2WINDOW10 |
F2 SWALL S1A F2WINDOW11 |
F2 SWALL S2A F2WINDOW12 |
F2 WWALL C F2WINDOW13 |
F2 EWALL C F2WINDOW14 |
F3 WWALL SWA F3WINDOW2 |
F3 SWALL SWA F3WINDOW3 |
F3 NWALL NWA F3WINDOW4 |
F3 WWALL NWA F3WINDOW6 |
F3 EWALL SEA F3WINDOW8 |
F3 SWALL SEA F3WINDOW1 |
F3 NWALL NEA F3WINDOW5 |
F3 EWALL NEA F3WINDOW7 |
F3 NWALL N1A F3WINDOW9 |
F3 NWALL N2A F3WINDOW10 |
F3 SWALL S1A F3WINDOW11 |
F3 SWALL S2A F3WINDOW12 |
F3 WWALL C F3WINDOW13 |
F3 EWALL C F3WINDOW14 |
F4 WWALL SWA F4WINDOW2 |
F4 SWALL SWA F4WINDOW3 |
F4 NWALL NWA F4WINDOW4 |
F4 WWALL NWA F4WINDOW6 |
F4 EWALL SEA F4WINDOW8 |
F4 SWALL SEA F4WINDOW1 |
F4 NWALL NEA F4WINDOW5 |
F4 EWALL NEA F4WINDOW7 |
F4 NWALL N1A F4WINDOW9 |
F4 NWALL N2A F4WINDOW10 |
F4 SWALL S1A F4WINDOW11 |
F4 SWALL S2A F4WINDOW12 |
F4 WWALL C F4WINDOW13 |
F4 EWALL C F4WINDOW14 |
M WWALL SWA MWINDOW2 |
M SWALL SWA MWINDOW3 |
M NWALL NWA MWINDOW4 |
M WWALL NWA MWINDOW6 |
M EWALL SEA MWINDOW8 |
M SWALL SEA MWINDOW1 |
M NWALL NEA MWINDOW5 |
M EWALL NEA MWINDOW7 |
M NWALL N1A MWINDOW9 |
M NWALL N2A MWINDOW10 |
M SWALL S1A MWINDOW11 |
M SWALL S2A MWINDOW12 |
M WWALL C MWINDOW13 |
M EWALL C MWINDOW14 |
F6 WWALL SWA F6WINDOW2 |
F6 SWALL SWA F6WINDOW3 |
F6 NWALL NWA F6WINDOW4 |
F6 WWALL NWA F6WINDOW6 |
F6 EWALL SEA F6WINDOW8 |
F6 SWALL SEA F6WINDOW1 |
F6 NWALL NEA F6WINDOW5 |
F6 EWALL NEA F6WINDOW7 |
F6 NWALL N1A F6WINDOW9 |
F6 NWALL N2A F6WINDOW10 |
F6 SWALL S1A F6WINDOW11 |
F6 SWALL S2A F6WINDOW12 |
F6 WWALL C F6WINDOW13 |
F6 EWALL C F6WINDOW14 |
F7 WWALL SWA F7WINDOW2 |
F7 SWALL SWA F7WINDOW3 |
F7 NWALL NWA F7WINDOW4 |
F7 WWALL NWA F7WINDOW6 |
F7 EWALL SEA F7WINDOW8 |
F7 SWALL SEA F7WINDOW1 |
F7 NWALL NEA F7WINDOW5 |
F7 EWALL NEA F7WINDOW7 |
F7 NWALL N1A F7WINDOW9 |
F7 NWALL N2A F7WINDOW10 |
F7 SWALL S1A F7WINDOW11 |
F7 SWALL S2A F7WINDOW12 |
F7 WWALL C F7WINDOW13 |
F7 EWALL C F7WINDOW14 |
F8 WWALL SWA F8WINDOW2 |
F8 SWALL SWA F8WINDOW3 |
F8 NWALL NWA F8WINDOW4 |
F8 WWALL NWA F8WINDOW6 |
F8 EWALL SEA F8WINDOW8 |
F8 SWALL SEA F8WINDOW1 |
F8 NWALL NEA F8WINDOW5 |
F8 EWALL NEA F8WINDOW7 |
F8 NWALL N1A F8WINDOW9 |
F8 NWALL N2A F8WINDOW10 |
F8 SWALL S1A F8WINDOW11 |
F8 SWALL S2A F8WINDOW12 |
F8 WWALL C F8WINDOW13 |
F8 EWALL C F8WINDOW14 |
F9 WWALL SWA F9WINDOW2 |
F9 SWALL SWA F9WINDOW3 |
F9 NWALL NWA F9WINDOW4 |
F9 WWALL NWA F9WINDOW6 |
F9 EWALL SEA F9WINDOW8 |
F9 SWALL SEA F9WINDOW1 |
F9 NWALL NEA F9WINDOW5 |
F9 EWALL NEA F9WINDOW7 |
F9 NWALL N1A F9WINDOW9 |
F9 NWALL N2A F9WINDOW10 |
F9 SWALL S1A F9WINDOW11 |
F9 SWALL S2A F9WINDOW12 |
F9 WWALL C F9WINDOW13 |
F9 EWALL C F9WINDOW14 |
T WWALL SWA TWINDOW2 |
T SWALL SWA TWINDOW3 |
T NWALL NWA TWINDOW4 |
T WWALL NWA TWINDOW6 |
T EWALL SEA TWINDOW8 |
T SWALL SEA TWINDOW1 |
T NWALL NEA TWINDOW5 |
T EWALL NEA TWINDOW7 |
T NWALL N1A TWINDOW9 |
T NWALL N2A TWINDOW10 |
T SWALL S1A TWINDOW11 |
T SWALL S2A TWINDOW12 |
T WWALL C TWINDOW13 |
T EWALL C TWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 19:00:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 2.60
February 22.60 4.29
March 22.73 8.77
April 23.43 13.91
May 23.73 17.82
June 24.27 23.21
July 24.40 25.63
August 24.36 24.08
September 24.32 20.49
October 23.71 13.71
November 22.98 6.96
December 22.52 2.07
     
Annual Sum or Average 23.46 13.68
Minimum of Months 22.46 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 2.60
February 21.89 4.29
March 22.11 8.77
April 23.10 13.91
May 23.69 17.82
June 24.29 23.21
July 24.40 25.63
August 24.35 24.08
September 24.28 20.49
October 23.13 13.71
November 22.03 6.96
December 21.74 2.07
     
Annual Sum or Average 23.07 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.61 2.60
February 22.77 4.29
March 23.09 8.77
April 23.75 13.91
May 24.11 17.82
June 24.38 23.21
July 24.40 25.63
August 24.40 24.08
September 24.42 20.49
October 23.88 13.71
November 23.10 6.96
December 22.67 2.07
     
Annual Sum or Average 23.64 13.68
Minimum of Months 22.61 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 2.60
February 21.80 4.29
March 22.04 8.77
April 23.10 13.91
May 23.67 17.82
June 24.30 23.21
July 24.43 25.63
August 24.37 24.08
September 24.28 20.49
October 23.04 13.71
November 21.89 6.96
December 21.70 2.07
     
Annual Sum or Average 23.03 13.68
Minimum of Months 21.70 2.07
Maximum of Months 24.43 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 2.60
February 21.76 4.29
March 21.88 8.77
April 22.75 13.91
May 23.46 17.82
June 24.26 23.21
July 24.41 25.63
August 24.34 24.08
September 24.23 20.49
October 22.87 13.71
November 21.84 6.96
December 21.70 2.07
     
Annual Sum or Average 22.94 13.68
Minimum of Months 21.70 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 2.60
February 21.75 4.29
March 21.87 8.77
April 22.75 13.91
May 23.46 17.82
June 24.26 23.21
July 24.41 25.63
August 24.34 24.08
September 24.23 20.49
October 22.86 13.71
November 21.84 6.96
December 21.70 2.07
     
Annual Sum or Average 22.94 13.68
Minimum of Months 21.70 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.51 2.60
February 22.62 4.29
March 22.67 8.77
April 23.26 13.91
May 23.58 17.82
June 24.24 23.21
July 24.39 25.63
August 24.38 24.08
September 24.37 20.49
October 23.74 13.71
November 23.07 6.96
December 22.61 2.07
     
Annual Sum or Average 23.46 13.68
Minimum of Months 22.51 2.07
Maximum of Months 24.39 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 2.60
February 22.65 4.29
March 22.73 8.77
April 23.32 13.91
May 23.63 17.82
June 24.25 23.21
July 24.39 25.63
August 24.38 24.08
September 24.37 20.49
October 23.76 13.71
November 23.11 6.96
December 22.64 2.07
     
Annual Sum or Average 23.49 13.68
Minimum of Months 22.54 2.07
Maximum of Months 24.39 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.41 2.60
February 18.03 4.29
March 19.52 8.77
April 21.45 13.91
May 22.86 17.82
June 25.52 23.21
July 26.33 25.63
August 25.83 24.08
September 24.66 20.49
October 21.61 13.71
November 18.97 6.96
December 17.24 2.07
     
Annual Sum or Average 21.63 13.68
Minimum of Months 17.24 2.07
Maximum of Months 26.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.96 2.60
February 23.11 4.29
March 23.43 8.77
April 24.09 13.91
May 24.17 17.82
June 24.35 23.21
July 24.41 25.63
August 24.39 24.08
September 24.37 20.49
October 24.12 13.71
November 23.65 6.96
December 23.03 2.07
     
Annual Sum or Average 23.84 13.68
Minimum of Months 22.96 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 2.60
February 22.10 4.29
March 22.54 8.77
April 23.81 13.91
May 24.12 17.82
June 24.37 23.21
July 24.41 25.63
August 24.38 24.08
September 24.34 20.49
October 23.66 13.71
November 22.42 6.96
December 21.83 2.07
     
Annual Sum or Average 23.33 13.68
Minimum of Months 21.83 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 2.60
February 23.16 4.29
March 23.56 8.77
April 24.15 13.91
May 24.26 17.82
June 24.37 23.21
July 24.40 25.63
August 24.39 24.08
September 24.39 20.49
October 24.15 13.71
November 23.69 6.96
December 23.10 2.07
     
Annual Sum or Average 23.89 13.68
Minimum of Months 23.01 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 2.60
February 21.98 4.29
March 22.46 8.77
April 23.80 13.91
May 24.13 17.82
June 24.39 23.21
July 24.43 25.63
August 24.39 24.08
September 24.35 20.49
October 23.57 13.71
November 22.24 6.96
December 21.74 2.07
     
Annual Sum or Average 23.28 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.43 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 2.60
February 21.92 4.29
March 22.26 8.77
April 23.57 13.91
May 24.04 17.82
June 24.36 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.48 13.71
November 22.20 6.96
December 21.74 2.07
     
Annual Sum or Average 23.21 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 2.60
February 21.91 4.29
March 22.26 8.77
April 23.57 13.91
May 24.05 17.82
June 24.36 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.47 13.71
November 22.19 6.96
December 21.74 2.07
     
Annual Sum or Average 23.21 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 2.60
February 23.31 4.29
March 23.56 8.77
April 24.06 13.91
May 24.12 17.82
June 24.33 23.21
July 24.40 25.63
August 24.41 24.08
September 24.44 20.49
October 24.22 13.71
November 23.83 6.96
December 23.31 2.07
     
Annual Sum or Average 23.93 13.68
Minimum of Months 23.20 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.22 2.60
February 23.32 4.29
March 23.58 8.77
April 24.07 13.91
May 24.14 17.82
June 24.33 23.21
July 24.40 25.63
August 24.41 24.08
September 24.43 20.49
October 24.22 13.71
November 23.84 6.96
December 23.32 2.07
     
Annual Sum or Average 23.94 13.68
Minimum of Months 23.22 2.07
Maximum of Months 24.43 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F2 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.73 2.60
February 23.00 4.29
March 23.66 8.77
April 24.97 13.91
May 25.47 17.82
June 26.36 23.21
July 26.63 25.63
August 26.54 24.08
September 26.20 20.49
October 25.04 13.71
November 23.66 6.96
December 22.73 2.07
     
Annual Sum or Average 24.76 13.68
Minimum of Months 22.73 2.07
Maximum of Months 26.63 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 2.60
February 23.18 4.29
March 23.53 8.77
April 24.15 13.91
May 24.19 17.82
June 24.36 23.21
July 24.41 25.63
August 24.39 24.08
September 24.37 20.49
October 24.16 13.71
November 23.73 6.96
December 23.12 2.07
     
Annual Sum or Average 23.89 13.68
Minimum of Months 23.05 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 2.60
February 22.14 4.29
March 22.63 8.77
April 23.91 13.91
May 24.16 17.82
June 24.37 23.21
July 24.41 25.63
August 24.38 24.08
September 24.34 20.49
October 23.75 13.71
November 22.53 6.96
December 21.85 2.07
     
Annual Sum or Average 23.37 13.68
Minimum of Months 21.85 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 2.60
February 23.12 4.29
March 23.51 8.77
April 24.15 13.91
May 24.24 17.82
June 24.36 23.21
July 24.40 25.63
August 24.40 24.08
September 24.40 20.49
October 24.15 13.71
November 23.69 6.96
December 23.09 2.07
     
Annual Sum or Average 23.88 13.68
Minimum of Months 23.00 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 2.60
February 22.03 4.29
March 22.55 8.77
April 23.90 13.91
May 24.17 17.82
June 24.40 23.21
July 24.44 25.63
August 24.39 24.08
September 24.35 20.49
October 23.67 13.71
November 22.34 6.96
December 21.75 2.07
     
Annual Sum or Average 23.32 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 2.60
February 21.99 4.29
March 22.41 8.77
April 23.76 13.91
May 24.12 17.82
June 24.37 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.63 13.71
November 22.36 6.96
December 21.77 2.07
     
Annual Sum or Average 23.28 13.68
Minimum of Months 21.77 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 2.60
February 21.98 4.29
March 22.41 8.77
April 23.76 13.91
May 24.12 17.82
June 24.37 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.63 13.71
November 22.35 6.96
December 21.77 2.07
     
Annual Sum or Average 23.28 13.68
Minimum of Months 21.77 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.38 2.60
February 23.47 4.29
March 23.74 8.77
April 24.16 13.91
May 24.18 17.82
June 24.34 23.21
July 24.41 25.63
August 24.41 24.08
September 24.44 20.49
October 24.28 13.71
November 23.96 6.96
December 23.48 2.07
     
Annual Sum or Average 24.02 13.68
Minimum of Months 23.38 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.38 2.60
February 23.47 4.29
March 23.74 8.77
April 24.17 13.91
May 24.19 17.82
June 24.34 23.21
July 24.40 25.63
August 24.41 24.08
September 24.44 20.49
October 24.28 13.71
November 23.96 6.96
December 23.49 2.07
     
Annual Sum or Average 24.02 13.68
Minimum of Months 23.38 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F3 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.26 2.60
February 23.51 4.29
March 24.13 8.77
April 25.45 13.91
May 25.83 17.82
June 26.48 23.21
July 26.70 25.63
August 26.62 24.08
September 26.35 20.49
October 25.46 13.71
November 24.17 6.96
December 23.27 2.07
     
Annual Sum or Average 25.11 13.68
Minimum of Months 23.26 2.07
Maximum of Months 26.70 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.04 2.60
February 23.15 4.29
March 23.50 8.77
April 24.14 13.91
May 24.18 17.82
June 24.36 23.21
July 24.41 25.63
August 24.39 24.08
September 24.37 20.49
October 24.16 13.71
November 23.72 6.96
December 23.11 2.07
     
Annual Sum or Average 23.88 13.68
Minimum of Months 23.04 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 2.60
February 22.14 4.29
March 22.62 8.77
April 23.91 13.91
May 24.15 17.82
June 24.37 23.21
July 24.41 25.63
August 24.38 24.08
September 24.34 20.49
October 23.76 13.71
November 22.55 6.96
December 21.85 2.07
     
Annual Sum or Average 23.37 13.68
Minimum of Months 21.85 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.98 2.60
February 23.07 4.29
March 23.45 8.77
April 24.13 13.91
May 24.21 17.82
June 24.36 23.21
July 24.41 25.63
August 24.40 24.08
September 24.40 20.49
October 24.14 13.71
November 23.66 6.96
December 23.07 2.07
     
Annual Sum or Average 23.86 13.68
Minimum of Months 22.98 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 2.60
February 22.04 4.29
March 22.53 8.77
April 23.90 13.91
May 24.16 17.82
June 24.41 23.21
July 24.44 25.63
August 24.39 24.08
September 24.35 20.49
October 23.68 13.71
November 22.37 6.96
December 21.76 2.07
     
Annual Sum or Average 23.33 13.68
Minimum of Months 21.76 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.83 2.60
February 22.01 4.29
March 22.44 8.77
April 23.80 13.91
May 24.12 17.82
June 24.37 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.68 13.71
November 22.43 6.96
December 21.78 2.07
     
Annual Sum or Average 23.30 13.68
Minimum of Months 21.78 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 2.60
February 22.00 4.29
March 22.43 8.77
April 23.80 13.91
May 24.12 17.82
June 24.38 23.21
July 24.42 25.63
August 24.38 24.08
September 24.32 20.49
October 23.67 13.71
November 22.41 6.96
December 21.77 2.07
     
Annual Sum or Average 23.30 13.68
Minimum of Months 21.77 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 2.60
February 23.47 4.29
March 23.75 8.77
April 24.17 13.91
May 24.18 17.82
June 24.34 23.21
July 24.41 25.63
August 24.41 24.08
September 24.44 20.49
October 24.29 13.71
November 23.97 6.96
December 23.50 2.07
     
Annual Sum or Average 24.03 13.68
Minimum of Months 23.40 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 2.60
February 23.47 4.29
March 23.75 8.77
April 24.18 13.91
May 24.19 17.82
June 24.34 23.21
July 24.41 25.63
August 24.41 24.08
September 24.44 20.49
October 24.29 13.71
November 23.97 6.96
December 23.50 2.07
     
Annual Sum or Average 24.03 13.68
Minimum of Months 23.40 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F4 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.42 2.60
February 23.65 4.29
March 24.27 8.77
April 25.60 13.91
May 25.95 17.82
June 26.57 23.21
July 26.78 25.63
August 26.70 24.08
September 26.43 20.49
October 25.60 13.71
November 24.33 6.96
December 23.43 2.07
     
Annual Sum or Average 25.23 13.68
Minimum of Months 23.42 2.07
Maximum of Months 26.78 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.02 2.60
February 23.12 4.29
March 23.46 8.77
April 24.12 13.91
May 24.17 17.82
June 24.35 23.21
July 24.41 25.63
August 24.39 24.08
September 24.37 20.49
October 24.15 13.71
November 23.70 6.96
December 23.09 2.07
     
Annual Sum or Average 23.86 13.68
Minimum of Months 23.02 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 2.60
February 22.14 4.29
March 22.59 8.77
April 23.88 13.91
May 24.13 17.82
June 24.37 23.21
July 24.41 25.63
August 24.38 24.08
September 24.34 20.49
October 23.76 13.71
November 22.55 6.96
December 21.85 2.07
     
Annual Sum or Average 23.36 13.68
Minimum of Months 21.85 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.96 2.60
February 23.04 4.29
March 23.41 8.77
April 24.11 13.91
May 24.19 17.82
June 24.36 23.21
July 24.41 25.63
August 24.40 24.08
September 24.39 20.49
October 24.13 13.71
November 23.64 6.96
December 23.05 2.07
     
Annual Sum or Average 23.84 13.68
Minimum of Months 22.96 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 2.60
February 22.04 4.29
March 22.51 8.77
April 23.87 13.91
May 24.14 17.82
June 24.41 23.21
July 24.44 25.63
August 24.39 24.08
September 24.34 20.49
October 23.67 13.71
November 22.38 6.96
December 21.76 2.07
     
Annual Sum or Average 23.32 13.68
Minimum of Months 21.76 2.07
Maximum of Months 24.44 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 2.60
February 22.02 4.29
March 22.44 8.77
April 23.79 13.91
May 24.11 17.82
June 24.37 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.69 13.71
November 22.45 6.96
December 21.78 2.07
     
Annual Sum or Average 23.31 13.68
Minimum of Months 21.78 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 2.60
February 22.01 4.29
March 22.43 8.77
April 23.79 13.91
May 24.11 17.82
June 24.38 23.21
July 24.42 25.63
August 24.37 24.08
September 24.32 20.49
October 23.68 13.71
November 22.44 6.96
December 21.78 2.07
     
Annual Sum or Average 23.30 13.68
Minimum of Months 21.78 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.40 2.60
February 23.46 4.29
March 23.72 8.77
April 24.16 13.91
May 24.17 17.82
June 24.34 23.21
July 24.41 25.63
August 24.41 24.08
September 24.43 20.49
October 24.28 13.71
November 23.97 6.96
December 23.50 2.07
     
Annual Sum or Average 24.02 13.68
Minimum of Months 23.40 2.07
Maximum of Months 24.43 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 2.60
February 23.45 4.29
March 23.72 8.77
April 24.16 13.91
May 24.17 17.82
June 24.34 23.21
July 24.41 25.63
August 24.41 24.08
September 24.43 20.49
October 24.28 13.71
November 23.96 6.96
December 23.50 2.07
     
Annual Sum or Average 24.02 13.68
Minimum of Months 23.39 2.07
Maximum of Months 24.43 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.96 2.60
February 24.18 4.29
March 24.79 8.77
April 26.12 13.91
May 26.48 17.82
June 27.10 23.21
July 27.31 25.63
August 27.23 24.08
September 26.97 20.49
October 26.15 13.71
November 24.88 6.96
December 23.98 2.07
     
Annual Sum or Average 25.77 13.68
Minimum of Months 23.96 2.07
Maximum of Months 27.31 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.94 2.60
February 23.03 4.29
March 23.34 8.77
April 24.06 13.91
May 24.12 17.82
June 24.34 23.21
July 24.41 25.63
August 24.38 24.08
September 24.36 20.49
October 24.12 13.71
November 23.63 6.96
December 23.02 2.07
     
Annual Sum or Average 23.82 13.68
Minimum of Months 22.94 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.88 2.60
February 22.09 4.29
March 22.47 8.77
April 23.78 13.91
May 24.08 17.82
June 24.36 23.21
July 24.41 25.63
August 24.38 24.08
September 24.33 20.49
October 23.69 13.71
November 22.47 6.96
December 21.82 2.07
     
Annual Sum or Average 23.32 13.68
Minimum of Months 21.82 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 2.60
February 22.96 4.29
March 23.30 8.77
April 24.05 13.91
May 24.14 17.82
June 24.35 23.21
July 24.41 25.63
August 24.40 24.08
September 24.38 20.49
October 24.10 13.71
November 23.57 6.96
December 22.98 2.07
     
Annual Sum or Average 23.80 13.68
Minimum of Months 22.89 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 2.60
February 21.99 4.29
March 22.40 8.77
April 23.78 13.91
May 24.09 17.82
June 24.40 23.21
July 24.45 25.63
August 24.38 24.08
September 24.33 20.49
October 23.60 13.71
November 22.29 6.96
December 21.75 2.07
     
Annual Sum or Average 23.28 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.45 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 2.60
February 21.97 4.29
March 22.32 8.77
April 23.68 13.91
May 24.06 17.82
June 24.36 23.21
July 24.42 25.63
August 24.37 24.08
September 24.30 20.49
October 23.61 13.71
November 22.36 6.96
December 21.76 2.07
     
Annual Sum or Average 23.26 13.68
Minimum of Months 21.76 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 2.60
February 21.97 4.29
March 22.31 8.77
April 23.68 13.91
May 24.06 17.82
June 24.37 23.21
July 24.42 25.63
August 24.37 24.08
September 24.30 20.49
October 23.60 13.71
November 22.34 6.96
December 21.76 2.07
     
Annual Sum or Average 23.26 13.68
Minimum of Months 21.76 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 2.60
February 23.36 4.29
March 23.61 8.77
April 24.10 13.91
May 24.12 17.82
June 24.33 23.21
July 24.41 25.63
August 24.40 24.08
September 24.42 20.49
October 24.25 13.71
November 23.90 6.96
December 23.43 2.07
     
Annual Sum or Average 23.97 13.68
Minimum of Months 23.32 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 2.60
February 23.36 4.29
March 23.61 8.77
April 24.10 13.91
May 24.13 17.82
June 24.33 23.21
July 24.41 25.63
August 24.40 24.08
September 24.42 20.49
October 24.25 13.71
November 23.90 6.96
December 23.42 2.07
     
Annual Sum or Average 23.97 13.68
Minimum of Months 23.31 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F6 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.34 2.60
February 23.55 4.29
March 24.12 8.77
April 25.49 13.91
May 25.88 17.82
June 26.55 23.21
July 26.77 25.63
August 26.69 24.08
September 26.40 20.49
October 25.54 13.71
November 24.25 6.96
December 23.36 2.07
     
Annual Sum or Average 25.17 13.68
Minimum of Months 23.34 2.07
Maximum of Months 26.77 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 2.60
February 22.96 4.29
March 23.25 8.77
April 24.00 13.91
May 24.09 17.82
June 24.33 23.21
July 24.41 25.63
August 24.38 24.08
September 24.35 20.49
October 24.09 13.71
November 23.58 6.96
December 22.97 2.07
     
Annual Sum or Average 23.78 13.68
Minimum of Months 22.89 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 2.60
February 22.06 4.29
March 22.39 8.77
April 23.70 13.91
May 24.05 17.82
June 24.35 23.21
July 24.41 25.63
August 24.38 24.08
September 24.32 20.49
October 23.63 13.71
November 22.41 6.96
December 21.81 2.07
     
Annual Sum or Average 23.29 13.68
Minimum of Months 21.81 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.83 2.60
February 22.90 4.29
March 23.21 8.77
April 24.00 13.91
May 24.11 17.82
June 24.34 23.21
July 24.41 25.63
August 24.39 24.08
September 24.38 20.49
October 24.07 13.71
November 23.52 6.96
December 22.93 2.07
     
Annual Sum or Average 23.76 13.68
Minimum of Months 22.83 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 2.60
February 21.97 4.29
March 22.33 8.77
April 23.70 13.91
May 24.05 17.82
June 24.39 23.21
July 24.45 25.63
August 24.38 24.08
September 24.32 20.49
October 23.55 13.71
November 22.23 6.96
December 21.74 2.07
     
Annual Sum or Average 23.25 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.45 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 2.60
February 21.95 4.29
March 22.24 8.77
April 23.59 13.91
May 24.02 17.82
June 24.35 23.21
July 24.42 25.63
August 24.37 24.08
September 24.29 20.49
October 23.55 13.71
November 22.29 6.96
December 21.76 2.07
     
Annual Sum or Average 23.22 13.68
Minimum of Months 21.76 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 2.60
February 21.94 4.29
March 22.23 8.77
April 23.59 13.91
May 24.02 17.82
June 24.36 23.21
July 24.42 25.63
August 24.37 24.08
September 24.29 20.49
October 23.54 13.71
November 22.28 6.96
December 21.75 2.07
     
Annual Sum or Average 23.22 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.25 2.60
February 23.29 4.29
March 23.51 8.77
April 24.04 13.91
May 24.09 17.82
June 24.32 23.21
July 24.41 25.63
August 24.40 24.08
September 24.41 20.49
October 24.23 13.71
November 23.85 6.96
December 23.36 2.07
     
Annual Sum or Average 23.93 13.68
Minimum of Months 23.25 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.25 2.60
February 23.28 4.29
March 23.51 8.77
April 24.05 13.91
May 24.09 17.82
June 24.32 23.21
July 24.41 25.63
August 24.40 24.08
September 24.41 20.49
October 24.23 13.71
November 23.85 6.96
December 23.36 2.07
     
Annual Sum or Average 23.93 13.68
Minimum of Months 23.25 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F7 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 2.60
February 23.39 4.29
March 23.94 8.77
April 25.32 13.91
May 25.76 17.82
June 26.46 23.21
July 26.70 25.63
August 26.61 24.08
September 26.31 20.49
October 25.41 13.71
November 24.09 6.96
December 23.22 2.07
     
Annual Sum or Average 25.04 13.68
Minimum of Months 23.19 2.07
Maximum of Months 26.70 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.83 2.60
February 22.91 4.29
March 23.17 8.77
April 23.95 13.91
May 24.06 17.82
June 24.32 23.21
July 24.41 25.63
August 24.38 24.08
September 24.35 20.49
October 24.07 13.71
November 23.53 6.96
December 22.92 2.07
     
Annual Sum or Average 23.75 13.68
Minimum of Months 22.83 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 2.60
February 22.03 4.29
March 22.34 8.77
April 23.64 13.91
May 24.02 17.82
June 24.34 23.21
July 24.41 25.63
August 24.37 24.08
September 24.31 20.49
October 23.58 13.71
November 22.35 6.96
December 21.80 2.07
     
Annual Sum or Average 23.26 13.68
Minimum of Months 21.80 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.78 2.60
February 22.85 4.29
March 23.14 8.77
April 23.95 13.91
May 24.08 17.82
June 24.33 23.21
July 24.41 25.63
August 24.39 24.08
September 24.37 20.49
October 24.04 13.71
November 23.47 6.96
December 22.88 2.07
     
Annual Sum or Average 23.73 13.68
Minimum of Months 22.78 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 2.60
February 21.94 4.29
March 22.27 8.77
April 23.63 13.91
May 24.02 17.82
June 24.39 23.21
July 24.45 25.63
August 24.38 24.08
September 24.31 20.49
October 23.50 13.71
November 22.18 6.96
December 21.73 2.07
     
Annual Sum or Average 23.22 13.68
Minimum of Months 21.73 2.07
Maximum of Months 24.45 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 2.60
February 21.92 4.29
March 22.18 8.77
April 23.51 13.91
May 23.99 17.82
June 24.35 23.21
July 24.42 25.63
August 24.36 24.08
September 24.28 20.49
October 23.50 13.71
November 22.24 6.96
December 21.75 2.07
     
Annual Sum or Average 23.20 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 2.60
February 21.92 4.29
March 22.18 8.77
April 23.51 13.91
May 23.99 17.82
June 24.35 23.21
July 24.42 25.63
August 24.36 24.08
September 24.28 20.49
October 23.49 13.71
November 22.22 6.96
December 21.75 2.07
     
Annual Sum or Average 23.19 13.68
Minimum of Months 21.75 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 2.60
February 23.21 4.29
March 23.42 8.77
April 23.99 13.91
May 24.06 17.82
June 24.31 23.21
July 24.41 25.63
August 24.39 24.08
September 24.40 20.49
October 24.20 13.71
November 23.80 6.96
December 23.29 2.07
     
Annual Sum or Average 23.89 13.68
Minimum of Months 23.19 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 2.60
February 23.21 4.29
March 23.42 8.77
April 23.99 13.91
May 24.06 17.82
June 24.31 23.21
July 24.41 25.63
August 24.39 24.08
September 24.40 20.49
October 24.20 13.71
November 23.80 6.96
December 23.29 2.07
     
Annual Sum or Average 23.89 13.68
Minimum of Months 23.18 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F8 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.09 2.60
February 23.29 4.29
March 23.83 8.77
April 25.23 13.91
May 25.71 17.82
June 26.45 23.21
July 26.70 25.63
August 26.61 24.08
September 26.29 20.49
October 25.34 13.71
November 23.99 6.96
December 23.12 2.07
     
Annual Sum or Average 24.98 13.68
Minimum of Months 23.09 2.07
Maximum of Months 26.70 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.75 2.60
February 22.83 4.29
March 23.08 8.77
April 23.87 13.91
May 24.04 17.82
June 24.31 23.21
July 24.41 25.63
August 24.38 24.08
September 24.34 20.49
October 24.02 13.71
November 23.43 6.96
December 22.83 2.07
     
Annual Sum or Average 23.69 13.68
Minimum of Months 22.75 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.83 2.60
February 22.02 4.29
March 22.30 8.77
April 23.57 13.91
May 23.99 17.82
June 24.33 23.21
July 24.41 25.63
August 24.37 24.08
September 24.30 20.49
October 23.53 13.71
November 22.31 6.96
December 21.79 2.07
     
Annual Sum or Average 23.24 13.68
Minimum of Months 21.79 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.71 2.60
February 22.78 4.29
March 23.05 8.77
April 23.89 13.91
May 24.05 17.82
June 24.32 23.21
July 24.41 25.63
August 24.39 24.08
September 24.35 20.49
October 24.00 13.71
November 23.38 6.96
December 22.80 2.07
     
Annual Sum or Average 23.68 13.68
Minimum of Months 22.71 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 2.60
February 21.93 4.29
March 22.24 8.77
April 23.56 13.91
May 23.99 17.82
June 24.38 23.21
July 24.45 25.63
August 24.38 24.08
September 24.30 20.49
October 23.45 13.71
November 22.13 6.96
December 21.73 2.07
     
Annual Sum or Average 23.20 13.68
Minimum of Months 21.73 2.07
Maximum of Months 24.45 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 2.60
February 21.91 4.29
March 22.15 8.77
April 23.45 13.91
May 23.96 17.82
June 24.33 23.21
July 24.42 25.63
August 24.36 24.08
September 24.27 20.49
October 23.44 13.71
November 22.19 6.96
December 21.74 2.07
     
Annual Sum or Average 23.17 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 2.60
February 21.91 4.29
March 22.15 8.77
April 23.45 13.91
May 23.96 17.82
June 24.34 23.21
July 24.42 25.63
August 24.36 24.08
September 24.27 20.49
October 23.44 13.71
November 22.17 6.96
December 21.74 2.07
     
Annual Sum or Average 23.17 13.68
Minimum of Months 21.74 2.07
Maximum of Months 24.42 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 2.60
February 23.10 4.29
March 23.29 8.77
April 23.91 13.91
May 24.03 17.82
June 24.30 23.21
July 24.41 25.63
August 24.39 24.08
September 24.38 20.49
October 24.15 13.71
November 23.69 6.96
December 23.16 2.07
     
Annual Sum or Average 23.82 13.68
Minimum of Months 23.05 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 2.60
February 23.09 4.29
March 23.29 8.77
April 23.91 13.91
May 24.03 17.82
June 24.30 23.21
July 24.41 25.63
August 24.39 24.08
September 24.38 20.49
October 24.15 13.71
November 23.69 6.96
December 23.15 2.07
     
Annual Sum or Average 23.82 13.68
Minimum of Months 23.05 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: F9 CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.90 2.60
February 23.13 4.29
March 23.70 8.77
April 25.15 13.91
May 25.70 17.82
June 26.52 23.21
July 26.81 25.63
August 26.70 24.08
September 26.32 20.49
October 25.25 13.71
November 23.81 6.96
December 22.91 2.07
     
Annual Sum or Average 24.92 13.68
Minimum of Months 22.90 2.07
Maximum of Months 26.81 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.55 2.60
February 22.68 4.29
March 22.83 8.77
April 23.60 13.91
May 23.91 17.82
June 24.25 23.21
July 24.40 25.63
August 24.35 24.08
September 24.27 20.49
October 23.72 13.71
November 23.03 6.96
December 22.62 2.07
     
Annual Sum or Average 23.52 13.68
Minimum of Months 22.55 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 2.60
February 22.15 4.29
March 22.41 8.77
April 23.40 13.91
May 23.87 17.82
June 24.27 23.21
July 24.41 25.63
August 24.35 24.08
September 24.23 20.49
October 23.37 13.71
November 22.36 6.96
December 21.89 2.07
     
Annual Sum or Average 23.23 13.68
Minimum of Months 21.89 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 2.60
February 22.67 4.29
March 22.83 8.77
April 23.61 13.91
May 23.91 17.82
June 24.25 23.21
July 24.39 25.63
August 24.37 24.08
September 24.28 20.49
October 23.69 13.71
November 23.00 6.96
December 22.61 2.07
     
Annual Sum or Average 23.52 13.68
Minimum of Months 22.54 2.07
Maximum of Months 24.39 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 2.60
February 22.08 4.29
March 22.38 8.77
April 23.41 13.91
May 23.83 17.82
June 24.27 23.21
July 24.41 25.63
August 24.36 24.08
September 24.21 20.49
October 23.33 13.71
November 22.24 6.96
December 21.77 2.07
     
Annual Sum or Average 23.18 13.68
Minimum of Months 21.77 2.07
Maximum of Months 24.41 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 2.60
February 22.05 4.29
March 22.28 8.77
April 23.33 13.91
May 23.84 17.82
June 24.27 23.21
July 24.40 25.63
August 24.34 24.08
September 24.21 20.49
October 23.31 13.71
November 22.24 6.96
December 21.78 2.07
     
Annual Sum or Average 23.16 13.68
Minimum of Months 21.78 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 2.60
February 22.05 4.29
March 22.28 8.77
April 23.33 13.91
May 23.84 17.82
June 24.27 23.21
July 24.40 25.63
August 24.34 24.08
September 24.21 20.49
October 23.31 13.71
November 22.24 6.96
December 21.77 2.07
     
Annual Sum or Average 23.16 13.68
Minimum of Months 21.77 2.07
Maximum of Months 24.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.70 2.60
February 22.82 4.29
March 22.96 8.77
April 23.66 13.91
May 23.93 17.82
June 24.24 23.21
July 24.38 25.63
August 24.35 24.08
September 24.31 20.49
October 23.85 13.71
November 23.20 6.96
December 22.77 2.07
     
Annual Sum or Average 23.60 13.68
Minimum of Months 22.70 2.07
Maximum of Months 24.38 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 2.60
February 22.82 4.29
March 22.96 8.77
April 23.66 13.91
May 23.93 17.82
June 24.25 23.21
July 24.38 25.63
August 24.36 24.08
September 24.31 20.49
October 23.85 13.71
November 23.20 6.96
December 22.77 2.07
     
Annual Sum or Average 23.60 13.68
Minimum of Months 22.69 2.07
Maximum of Months 24.38 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 19:00:30

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.81 2.60
February 23.21 4.29
March 23.94 8.77
April 25.56 13.91
May 26.29 17.82
June 27.33 23.21
July 27.76 25.63
August 27.59 24.08
September 26.98 20.49
October 25.54 13.71
November 23.83 6.96
December 22.77 2.07
     
Annual Sum or Average 25.31 13.68
Minimum of Months 22.77 2.07
Maximum of Months 27.76 25.63



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 19:00:30

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W]
January 0.237569E+12 141821.218 16-JAN-17:00 11327.174 57042.023 23476.580 35882.331 0.000 10364.000 1741.299 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.210318E+12 126551.001 15-FEB-17:45 11327.174 57142.088 23476.580 0.000 19853.839 10364.000 1741.299 650.862 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.219586E+12 122049.323 11-MAR-18:15 13120.457 57042.023 23476.580 0.000 13918.618 10364.000 1741.299 398.534 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.224486E+12 155126.831 13-APR-17:15 13120.457 57042.023 23476.580 0.000 56129.872 0.000 1741.299 1628.788 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.250642E+12 159356.636 09-MAY-17:15 13120.457 57042.023 23476.580 0.000 60346.359 0.000 1741.299 1642.106 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.279746E+12 162404.745 18-JUN-19:00 14401.373 49889.926 23476.580 0.000 59274.547 10364.000 1741.299 1615.716 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.313895E+12 163762.871 21-JUL-19:15 14401.373 49889.926 23476.580 0.000 60361.600 10364.000 1741.299 1886.788 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.303997E+12 161913.724 21-AUG-17:15 13120.457 57042.023 23476.580 0.000 62484.880 0.000 1741.299 2060.673 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.267477E+12 159492.369 28-SEP-17:00 13120.457 57042.023 23476.580 0.000 50063.135 10364.000 1741.299 1696.866 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.245183E+12 159343.706 05-OCT-17:45 13120.457 57042.023 23476.580 0.000 50032.869 10364.000 1741.299 1578.469 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.222869E+12 126032.733 07-NOV-17:15 11327.174 57142.088 23476.580 0.000 19301.048 10364.000 1741.299 685.348 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.236120E+12 126198.360 03-DEC-18:00 13120.457 57042.023 23476.580 18465.992 0.000 10364.000 1741.299 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.301189E+13                     0.000 0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.210318E+12 122049.323   11327.174 49889.926 23476.580 0.000 0.000 0.000 1741.299 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.313895E+12 163762.871   14401.373 57142.088 23476.580 35882.331 62484.880 10364.000 1741.299 2060.673 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: COMPONENTS OF PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 19:00:30

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.168927E+12 229458.428 17-JAN-08:15 0.000 0.000 0.000 229458.428 79368.043 79368.043 150090.385
February 0.142162E+12 199460.408 06-FEB-06:00 0.000 0.000 0.000 199460.408 78138.779 78138.779 121321.629
March 0.114991E+12 160357.152 04-MAR-06:30 0.000 0.000 0.000 160357.152 75481.846 75481.846 84875.306
April 0.951555E+11 95262.237 08-APR-05:30 0.000 0.000 0.000 95262.237 73096.585 73096.585 22165.652
May 0.911279E+11 76444.364 01-MAY-06:00 0.000 0.000 0.000 76444.364 76444.364 76444.364 0.000
June 0.820353E+11 74092.424 02-JUN-06:00 0.000 0.000 0.000 74092.424 74092.424 74092.424 0.000
July 0.805276E+11 72436.343 01-JUL-06:45 0.000 0.000 0.000 72436.343 72436.343 72436.343 0.000
August 0.795816E+11 71863.904 30-AUG-06:00 0.000 0.000 0.000 71863.904 71863.904 71863.904 0.000
September 0.794624E+11 72992.365 28-SEP-06:45 0.000 0.000 0.000 72992.365 72992.365 72992.365 0.000
October 0.907933E+11 122962.462 26-OCT-05:00 0.000 0.000 0.000 122962.462 73069.371 73069.371 49893.091
November 0.103940E+12 177592.286 26-NOV-06:30 0.000 0.000 0.000 177592.286 73201.719 73201.719 104390.568
December 0.156451E+12 190982.383 22-DEC-06:00 0.000 0.000 0.000 190982.383 76764.909 76764.909 114217.475
                     
Annual Sum or Average 0.128516E+13     0.000 0.000 0.000        
Minimum of Months 0.794624E+11 71863.904   0.000 0.000 0.000 71863.904 71863.904 71863.904 0.000
Maximum of Months 0.168927E+12 229458.428   0.000 0.000 0.000 229458.428 79368.043 79368.043 150090.385