Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: San Francisco Intl Ap CA USA TMY3 WMO#=724940
Simulation Timestamp: 2015-09-09 19:12:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3475.58 | 443.51 | 492.30 |
Net Site Energy | 3475.58 | 443.51 | 492.30 |
Total Source Energy | 8448.61 | 1078.11 | 1196.70 |
Net Source Energy | 8448.61 | 1078.11 | 1196.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 55.40 | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 473.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 179.99 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1093.79 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2247.28 | 1228.31 | 0.00 | 0.00 | 0.00 | 4958.51 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 134.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 55.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 473.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 38.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 179.99 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1093.79 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 87.04 | 173.98 | 0.00 | 0.00 | 0.00 | 0.70 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 318.32 | 173.98 | 0.00 | 0.00 | 0.00 | 0.70 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 78.41 | 156.74 | 0.00 | 0.00 | 0.00 | 0.63 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 286.77 | 156.74 | 0.00 | 0.00 | 0.00 | 0.63 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2247.28 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2247.28 | 100.00 |
Total On-Site and Utility Electric Sources | 2247.28 | 100.00 |
Total Electricity End Uses | 2247.28 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4958.51 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4958.51 | 100.00 |
Total Water End Uses | 4958.51 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 119.00 |
Time Setpoint Not Met During Occupied Cooling | 12.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 72.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:11 |
RunPeriod | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Latitude [deg] | 37.62 |
Longitude [deg] | -122.4 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-16:45 | 17-MAY-19:00 | - | - | - | 30-JUN-17:15 |
Heating | 0.00 | 118213.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47332.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15015.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1332.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1520.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 68877.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 135664.16 | 187090.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 118213.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 47332.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 9220.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2106.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 15015.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1332.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1520.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 68877.58 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 175.45 | 145.81 | 0.00 | 0.00 | 0.00 |
Cooling | 143.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1499.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 121.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1185.67 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7117.12 | 1331.49 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 24.85 | 20.65 | 0.00 | 0.00 | 0.00 |
Cooling | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 167.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1008.11 | 188.60 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 24.85 | 20.65 | 0.00 | 0.00 | 0.00 |
Cooling | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 167.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1008.11 | 188.60 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 2.20 | 150.00 |
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 8.50 | 17.20 | Wetbulb [C] | 5.90 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.65 | 83.65 | 162.73 | |
Exterior Lighting Total | 10364.00 | 162.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 186493.07 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 149194.46 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2563.84 | 1990.97 | 572.87 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2112.46 | 1645.03 | 467.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4156.08 | 3239.54 | 916.53 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1477.02 | 1157.70 | 319.32 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 931.68 | 723.93 | 207.74 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 912.56 | 709.13 | 203.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1700.88 | 1308.59 | 392.28 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1787.39 | 1376.63 | 410.76 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3237.00 | 2525.49 | 711.51 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2695.86 | 2105.63 | 590.23 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3200.43 | 2492.51 | 707.92 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1984.64 | 1561.08 | 423.56 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1344.49 | 1046.79 | 297.71 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1328.10 | 1034.03 | 294.08 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2236.36 | 1730.31 | 506.05 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2267.91 | 1755.08 | 512.82 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3246.91 | 2535.19 | 711.72 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2718.42 | 2125.19 | 593.23 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2943.71 | 2292.76 | 650.94 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2017.99 | 1589.16 | 428.83 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1400.14 | 1091.27 | 308.87 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1383.98 | 1078.68 | 305.30 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2284.07 | 1768.96 | 515.11 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2297.37 | 1779.40 | 517.97 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3240.61 | 2531.64 | 708.96 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2715.17 | 2124.00 | 591.17 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2921.19 | 2276.42 | 644.77 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2024.77 | 1593.31 | 431.47 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1416.45 | 1104.80 | 311.65 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1400.53 | 1092.39 | 308.15 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2294.27 | 1777.83 | 516.44 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2304.78 | 1786.09 | 518.70 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3260.58 | 2548.45 | 712.13 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2737.36 | 2142.49 | 594.87 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2948.26 | 2298.77 | 649.49 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2047.31 | 1612.02 | 435.28 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1451.87 | 1133.08 | 318.79 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1436.15 | 1120.82 | 315.33 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2325.72 | 1803.23 | 522.49 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2335.83 | 1811.16 | 524.66 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3216.33 | 2511.89 | 704.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2684.22 | 2101.68 | 582.54 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2903.81 | 2264.73 | 639.08 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1995.95 | 1572.43 | 423.52 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1413.58 | 1103.74 | 309.84 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1398.17 | 1091.71 | 306.46 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2282.63 | 1769.97 | 512.67 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2292.69 | 1777.86 | 514.82 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3192.94 | 2494.32 | 698.62 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2660.65 | 2083.95 | 576.70 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2887.09 | 2252.36 | 634.73 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1973.20 | 1555.22 | 417.98 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1401.45 | 1094.73 | 306.72 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1386.26 | 1082.87 | 303.39 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2266.59 | 1757.86 | 508.72 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2276.63 | 1765.76 | 510.88 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3185.00 | 2488.79 | 696.21 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2652.90 | 2078.54 | 574.36 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2884.61 | 2251.09 | 633.51 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1965.16 | 1549.50 | 415.67 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1403.70 | 1096.89 | 306.81 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1388.72 | 1085.19 | 303.53 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2264.91 | 1756.99 | 507.91 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2274.97 | 1764.90 | 510.07 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3246.27 | 2540.34 | 705.94 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2726.00 | 2136.57 | 589.43 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2944.46 | 2297.78 | 646.68 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1988.83 | 1565.90 | 422.93 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1476.09 | 1153.79 | 322.30 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1461.16 | 1142.13 | 319.03 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2311.99 | 1794.40 | 517.59 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2323.24 | 1803.24 | 520.00 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4035.11 | 3156.96 | 878.15 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3358.57 | 2631.20 | 727.37 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3661.84 | 2863.28 | 798.56 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2508.57 | 1972.57 | 536.00 | 0.79 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2034.57 | 1575.70 | 458.87 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2035.77 | 1576.65 | 459.12 | 0.77 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3113.02 | 2424.04 | 688.98 | 0.78 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3123.67 | 2432.40 | 691.27 | 0.78 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2563.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2112.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4156.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1477.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 931.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 912.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1700.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1787.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3237.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2695.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3200.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1984.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1344.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1328.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2236.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2267.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3246.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2718.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2943.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2017.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1400.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1383.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2284.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2297.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3240.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2715.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2921.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2024.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1416.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1400.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2294.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2304.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3260.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2737.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2948.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2047.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1451.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1436.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2325.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2335.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3216.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2684.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2903.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1995.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1413.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1398.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2282.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2292.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3192.94 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2660.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2887.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1973.20 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1401.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1386.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2266.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2276.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3185.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2652.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2884.61 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1965.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1403.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1388.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2264.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2274.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3246.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 2726.00 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2944.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 1988.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1476.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1461.16 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2311.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2323.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4035.11 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3358.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3661.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2508.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2034.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2035.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3113.02 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3123.67 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 1666.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 1672.45 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 2242.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 1670.56 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 1238.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 1238.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 1227.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 1234.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 1572.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 1576.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 1589.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 1574.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 1553.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 1556.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 1554.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 1555.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 1574.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 1577.31 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 1573.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 1576.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 1578.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 1580.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 1577.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 1579.71 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 1640.86 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 1643.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 1640.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 1642.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 1680.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 1682.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 1680.49 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 1682.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 1722.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 1724.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 1722.57 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 1723.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 1136.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 1845.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 1844.46 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 1845.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 1844.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 1208.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 1208.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 1208.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 1208.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 2251.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 2254.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 2251.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 2254.97 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 1646.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 1646.47 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 1639.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 1639.75 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 205.34 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 170.53 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 335.23 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 121.06 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 74.74 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 73.19 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 132.98 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 140.15 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 262.36 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.28 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 258.17 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 163.89 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 108.74 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 107.40 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 177.39 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.00 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 263.48 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.44 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 237.20 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 166.96 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.48 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 112.16 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.53 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 182.63 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 263.18 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 221.39 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 235.54 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.00 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 114.95 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.64 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 182.51 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 183.38 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 265.02 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 223.39 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 237.96 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.03 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 117.96 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 116.67 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 185.23 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 186.06 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 260.76 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.14 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 234.41 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 164.88 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 114.90 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.63 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.75 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 182.58 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 258.95 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 217.31 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 233.15 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 163.10 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.97 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 112.73 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.50 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.33 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 258.40 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.77 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 233.05 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 162.53 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 114.22 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 112.99 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.43 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.27 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 264.33 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.93 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 237.85 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 163.81 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 120.23 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 119.00 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 184.40 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 185.33 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 328.82 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 274.41 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.75 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 206.33 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.19 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.29 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 250.85 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 251.73 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0041 | 1295.38 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1882.20 | 2258.64 | 0.147 | 0.177 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 27.92 | 0.00771 |
G NW APARTMENT | 1563.16 | 1875.79 | 0.122 | 0.147 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
OFFICE | 3072.83 | 3687.40 | 0.241 | 0.289 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 27.98 | 0.00771 |
G NE APARTMENT | 1109.63 | 1331.56 | 0.087 | 0.104 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.39 | 0.00771 |
G N1 APARTMENT | 685.11 | 822.13 | 0.054 | 0.064 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
G N2 APARTMENT | 670.89 | 805.07 | 0.053 | 0.063 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
G S1 APARTMENT | 1218.89 | 1462.67 | 0.095 | 0.115 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
G S2 APARTMENT | 1284.65 | 1541.58 | 0.101 | 0.121 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F2 SW APARTMENT | 2404.84 | 2885.81 | 0.188 | 0.226 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
F2 NW APARTMENT | 2009.96 | 2411.95 | 0.157 | 0.189 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F2 SE APARTMENT | 2366.49 | 2839.79 | 0.185 | 0.222 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F2 NE APARTMENT | 1502.29 | 1802.75 | 0.118 | 0.141 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.39 | 0.00771 |
F2 N1 APARTMENT | 996.76 | 1196.11 | 0.078 | 0.094 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F2 N2 APARTMENT | 984.46 | 1181.36 | 0.077 | 0.093 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F2 S1 APARTMENT | 1626.01 | 1951.21 | 0.127 | 0.153 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F2 S2 APARTMENT | 1649.95 | 1979.94 | 0.129 | 0.155 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F3 SW APARTMENT | 2415.17 | 2898.20 | 0.189 | 0.227 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
F3 NW APARTMENT | 2029.79 | 2435.74 | 0.159 | 0.191 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F3 SE APARTMENT | 2174.21 | 2609.05 | 0.170 | 0.204 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F3 NE APARTMENT | 1530.39 | 1836.46 | 0.120 | 0.144 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 25.39 | 0.00771 |
F3 N1 APARTMENT | 1040.18 | 1248.21 | 0.081 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F3 N2 APARTMENT | 1028.04 | 1233.65 | 0.081 | 0.097 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F3 S1 APARTMENT | 1663.94 | 1996.73 | 0.130 | 0.156 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F3 S2 APARTMENT | 1674.04 | 2008.84 | 0.131 | 0.157 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F4 SW APARTMENT | 2412.41 | 2894.90 | 0.189 | 0.227 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
F4 NW APARTMENT | 2029.29 | 2435.15 | 0.159 | 0.191 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F4 SE APARTMENT | 2159.06 | 2590.87 | 0.169 | 0.203 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F4 NE APARTMENT | 1530.73 | 1836.87 | 0.120 | 0.144 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
F4 N1 APARTMENT | 1053.62 | 1264.34 | 0.083 | 0.099 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F4 N2 APARTMENT | 1041.66 | 1249.99 | 0.082 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F4 S1 APARTMENT | 1672.94 | 2007.53 | 0.131 | 0.157 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F4 S2 APARTMENT | 1680.92 | 2017.11 | 0.132 | 0.158 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
M SW APARTMENT | 2429.22 | 2915.07 | 0.190 | 0.228 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
M NW APARTMENT | 2047.71 | 2457.25 | 0.160 | 0.192 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
M SE APARTMENT | 2181.20 | 2617.44 | 0.171 | 0.205 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
M NE APARTMENT | 1549.34 | 1859.20 | 0.121 | 0.146 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
M N1 APARTMENT | 1081.21 | 1297.45 | 0.085 | 0.102 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
M N2 APARTMENT | 1069.39 | 1283.26 | 0.084 | 0.101 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
M S1 APARTMENT | 1697.83 | 2037.40 | 0.133 | 0.160 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
M S2 APARTMENT | 1705.51 | 2046.61 | 0.134 | 0.160 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F6 SW APARTMENT | 2390.19 | 2868.23 | 0.187 | 0.225 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 27.92 | 0.00771 |
F6 NW APARTMENT | 2008.67 | 2410.40 | 0.157 | 0.189 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F6 SE APARTMENT | 2148.71 | 2578.45 | 0.168 | 0.202 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F6 NE APARTMENT | 1511.38 | 1813.65 | 0.118 | 0.142 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
F6 N1 APARTMENT | 1053.18 | 1263.81 | 0.082 | 0.099 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F6 N2 APARTMENT | 1041.57 | 1249.89 | 0.082 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F6 S1 APARTMENT | 1665.96 | 1999.16 | 0.130 | 0.157 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F6 S2 APARTMENT | 1673.60 | 2008.32 | 0.131 | 0.157 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F7 SW APARTMENT | 2373.58 | 2848.30 | 0.186 | 0.223 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 27.92 | 0.00771 |
F7 NW APARTMENT | 1991.90 | 2390.27 | 0.156 | 0.187 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F7 SE APARTMENT | 2137.12 | 2564.54 | 0.167 | 0.201 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F7 NE APARTMENT | 1495.04 | 1794.05 | 0.117 | 0.141 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
F7 N1 APARTMENT | 1044.71 | 1253.65 | 0.082 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F7 N2 APARTMENT | 1033.27 | 1239.93 | 0.081 | 0.097 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F7 S1 APARTMENT | 1654.51 | 1985.42 | 0.130 | 0.155 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F7 S2 APARTMENT | 1662.14 | 1994.57 | 0.130 | 0.156 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F8 SW APARTMENT | 2368.58 | 2842.30 | 0.185 | 0.223 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 27.92 | 0.00771 |
F8 NW APARTMENT | 1987.00 | 2384.40 | 0.156 | 0.187 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F8 SE APARTMENT | 2136.22 | 2563.47 | 0.167 | 0.201 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
F8 NE APARTMENT | 1489.79 | 1787.75 | 0.117 | 0.140 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
F8 N1 APARTMENT | 1046.99 | 1256.39 | 0.082 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F8 N2 APARTMENT | 1035.71 | 1242.85 | 0.081 | 0.097 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F8 S1 APARTMENT | 1653.89 | 1984.67 | 0.130 | 0.155 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F8 S2 APARTMENT | 1661.53 | 1993.84 | 0.130 | 0.156 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F9 SW APARTMENT | 2422.90 | 2907.48 | 0.190 | 0.228 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
F9 NW APARTMENT | 2043.44 | 2452.12 | 0.160 | 0.192 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
F9 SE APARTMENT | 2180.24 | 2616.28 | 0.171 | 0.205 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F9 NE APARTMENT | 1501.54 | 1801.85 | 0.118 | 0.141 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 26.03 | 0.00771 |
F9 N1 APARTMENT | 1102.07 | 1322.48 | 0.086 | 0.104 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F9 N2 APARTMENT | 1090.82 | 1308.98 | 0.085 | 0.103 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
F9 S1 APARTMENT | 1690.26 | 2028.31 | 0.132 | 0.159 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
F9 S2 APARTMENT | 1698.80 | 2038.56 | 0.133 | 0.160 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
T SW APARTMENT | 3014.05 | 3616.86 | 0.236 | 0.283 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 28.05 | 0.00771 |
T NW APARTMENT | 2515.31 | 3018.38 | 0.197 | 0.236 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 27.28 | 0.00771 |
T SE APARTMENT | 2729.26 | 3275.12 | 0.214 | 0.256 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
T NE APARTMENT | 1891.27 | 2269.53 | 0.148 | 0.178 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 26.34 | 0.00771 |
T N1 APARTMENT | 1477.56 | 1773.07 | 0.116 | 0.139 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 28.30 | 0.00771 |
T N2 APARTMENT | 1478.48 | 1774.17 | 0.116 | 0.139 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 28.30 | 0.00771 |
T S1 APARTMENT | 2299.37 | 2759.24 | 0.180 | 0.216 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
T S2 APARTMENT | 2307.45 | 2768.94 | 0.181 | 0.217 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 934.04 | 1120.85 | 0.042 | 0.050 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 3.80 | 0.00496 |
G NW APARTMENT | 939.02 | 1126.83 | 0.042 | 0.050 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
OFFICE | 1198.48 | 1438.18 | 0.053 | 0.064 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 3.80 | 0.00496 |
G NE APARTMENT | 937.43 | 1124.91 | 0.042 | 0.050 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
G N1 APARTMENT | 571.67 | 686.00 | 0.025 | 0.031 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
G N2 APARTMENT | 571.62 | 685.95 | 0.025 | 0.031 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
G S1 APARTMENT | 563.13 | 675.76 | 0.025 | 0.030 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
G S2 APARTMENT | 568.31 | 681.97 | 0.025 | 0.030 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
F2 SW APARTMENT | 854.36 | 1025.23 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 NW APARTMENT | 857.98 | 1029.58 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 SE APARTMENT | 868.89 | 1042.66 | 0.039 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 NE APARTMENT | 856.37 | 1027.64 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 N1 APARTMENT | 403.67 | 484.41 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 N2 APARTMENT | 403.63 | 484.36 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 S1 APARTMENT | 402.14 | 482.57 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F2 S2 APARTMENT | 403.24 | 483.89 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 SW APARTMENT | 838.33 | 1005.99 | 0.037 | 0.045 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 NW APARTMENT | 841.27 | 1009.53 | 0.037 | 0.045 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 SE APARTMENT | 838.97 | 1006.77 | 0.037 | 0.045 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 NE APARTMENT | 839.96 | 1007.95 | 0.037 | 0.045 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 N1 APARTMENT | 369.12 | 442.94 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 N2 APARTMENT | 369.08 | 442.90 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 S1 APARTMENT | 366.61 | 439.93 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F3 S2 APARTMENT | 366.77 | 440.13 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 SW APARTMENT | 855.79 | 1026.95 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 NW APARTMENT | 858.58 | 1030.30 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 SE APARTMENT | 854.97 | 1025.97 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 NE APARTMENT | 857.53 | 1029.04 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 N1 APARTMENT | 371.77 | 446.13 | 0.017 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 N2 APARTMENT | 371.74 | 446.09 | 0.017 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 S1 APARTMENT | 369.22 | 443.06 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F4 S2 APARTMENT | 369.22 | 443.06 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M SW APARTMENT | 859.74 | 1031.68 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M NW APARTMENT | 861.42 | 1033.70 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M SE APARTMENT | 858.96 | 1030.75 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M NE APARTMENT | 860.61 | 1032.74 | 0.038 | 0.046 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M N1 APARTMENT | 365.25 | 438.30 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M N2 APARTMENT | 365.23 | 438.28 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M S1 APARTMENT | 363.77 | 436.53 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
M S2 APARTMENT | 363.76 | 436.51 | 0.016 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 SW APARTMENT | 912.33 | 1094.80 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 NW APARTMENT | 914.39 | 1097.27 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 SE APARTMENT | 911.74 | 1094.09 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 NE APARTMENT | 913.80 | 1096.56 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 N1 APARTMENT | 405.26 | 486.31 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 N2 APARTMENT | 405.24 | 486.29 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 S1 APARTMENT | 403.38 | 484.06 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F6 S2 APARTMENT | 403.37 | 484.04 | 0.018 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 SW APARTMENT | 946.24 | 1135.49 | 0.042 | 0.051 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 NW APARTMENT | 947.81 | 1137.37 | 0.042 | 0.051 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 SE APARTMENT | 945.85 | 1135.02 | 0.042 | 0.051 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 NE APARTMENT | 947.42 | 1136.90 | 0.042 | 0.051 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 N1 APARTMENT | 429.46 | 515.36 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 N2 APARTMENT | 429.45 | 515.34 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 S1 APARTMENT | 428.06 | 513.67 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F7 S2 APARTMENT | 428.05 | 513.66 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 SW APARTMENT | 981.64 | 1177.97 | 0.044 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 NW APARTMENT | 982.64 | 1179.17 | 0.044 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 SE APARTMENT | 981.43 | 1177.72 | 0.044 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 NE APARTMENT | 982.43 | 1178.92 | 0.044 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 N1 APARTMENT | 456.48 | 547.78 | 0.020 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 N2 APARTMENT | 456.48 | 547.77 | 0.020 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 S1 APARTMENT | 455.62 | 546.74 | 0.020 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F8 S2 APARTMENT | 455.61 | 546.74 | 0.020 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 SW APARTMENT | 1085.22 | 1302.26 | 0.048 | 0.058 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 NW APARTMENT | 1084.51 | 1301.41 | 0.048 | 0.058 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 SE APARTMENT | 1085.17 | 1302.21 | 0.048 | 0.058 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 NE APARTMENT | 1084.47 | 1301.36 | 0.048 | 0.058 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 N1 APARTMENT | 546.57 | 655.88 | 0.024 | 0.029 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 N2 APARTMENT | 546.57 | 655.88 | 0.024 | 0.029 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 S1 APARTMENT | 547.03 | 656.44 | 0.024 | 0.029 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
F9 S2 APARTMENT | 547.03 | 656.44 | 0.024 | 0.029 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T SW APARTMENT | 1428.49 | 1714.19 | 0.064 | 0.076 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T NW APARTMENT | 1431.57 | 1717.89 | 0.064 | 0.076 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T SE APARTMENT | 1428.58 | 1714.29 | 0.064 | 0.076 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T NE APARTMENT | 1431.66 | 1717.99 | 0.064 | 0.076 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T N1 APARTMENT | 917.07 | 1100.48 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T N2 APARTMENT | 917.07 | 1100.48 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T S1 APARTMENT | 911.38 | 1093.66 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
T S2 APARTMENT | 911.39 | 1093.66 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 3.80 | 0.00496 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.18 | 0.18 | 0.05 | 0.05 |
AIRLOOP G NW | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP OFFICE | 0.29 | 0.29 | 0.06 | 0.06 |
AIRLOOP G NE | 0.10 | 0.10 | 0.05 | 0.05 |
AIRLOOP G N1 | 0.06 | 0.06 | 0.03 | 0.03 |
AIRLOOP G N2 | 0.06 | 0.06 | 0.03 | 0.03 |
AIRLOOP G S1 | 0.11 | 0.11 | 0.03 | 0.03 |
AIRLOOP G S2 | 0.12 | 0.12 | 0.03 | 0.03 |
AIRLOOP F2 SW | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F2 NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F2 SE | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F2 NE | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F2 N1 | 0.09 | 0.09 | 0.03 | 0.03 |
AIRLOOP F2 N2 | 0.09 | 0.09 | 0.03 | 0.03 |
AIRLOOP F2 S1 | 0.15 | 0.15 | 0.03 | 0.03 |
AIRLOOP F2 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F3 SW | 0.23 | 0.23 | 0.04 | 0.04 |
AIRLOOP F3 NW | 0.19 | 0.19 | 0.04 | 0.04 |
AIRLOOP F3 SE | 0.20 | 0.20 | 0.04 | 0.04 |
AIRLOOP F3 NE | 0.14 | 0.14 | 0.04 | 0.04 |
AIRLOOP F3 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F3 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F3 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F3 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F4 SW | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP F4 NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F4 SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F4 NE | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F4 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F4 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F4 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F4 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP M SW | 0.23 | 0.23 | 0.05 | 0.05 |
AIRLOOP M NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP M SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP M NE | 0.15 | 0.15 | 0.05 | 0.05 |
AIRLOOP M N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP M N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP M S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP M S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F6 SW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F6 NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F6 SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F6 NE | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F6 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F6 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F6 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F6 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F7 SW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F7 NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F7 SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F7 NE | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F7 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F7 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F7 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F7 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F8 SW | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP F8 NW | 0.19 | 0.19 | 0.05 | 0.05 |
AIRLOOP F8 SE | 0.20 | 0.20 | 0.05 | 0.05 |
AIRLOOP F8 NE | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP F8 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F8 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F8 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F8 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F9 SW | 0.23 | 0.23 | 0.06 | 0.06 |
AIRLOOP F9 NW | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F9 SE | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F9 NE | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP F9 N1 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F9 N2 | 0.10 | 0.10 | 0.03 | 0.03 |
AIRLOOP F9 S1 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP F9 S2 | 0.16 | 0.16 | 0.03 | 0.03 |
AIRLOOP T SW | 0.28 | 0.28 | 0.08 | 0.08 |
AIRLOOP T NW | 0.24 | 0.24 | 0.08 | 0.08 |
AIRLOOP T SE | 0.26 | 0.26 | 0.08 | 0.08 |
AIRLOOP T NE | 0.18 | 0.18 | 0.08 | 0.08 |
AIRLOOP T N1 | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP T N2 | 0.14 | 0.14 | 0.05 | 0.05 |
AIRLOOP T S1 | 0.22 | 0.22 | 0.05 | 0.05 |
AIRLOOP T S2 | 0.22 | 0.22 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 709.50 | 7290.75 | 22.50 |
G NW APARTMENT | 272.75 | 8211.50 | 19.50 |
OFFICE | 1098.25 | 391.75 | 0.00 |
G NE APARTMENT | 224.75 | 8285.75 | 19.25 |
G N1 APARTMENT | 109.25 | 8527.25 | 31.00 |
G N2 APARTMENT | 108.25 | 8529.25 | 30.75 |
G S1 APARTMENT | 535.50 | 7530.00 | 40.75 |
G S2 APARTMENT | 605.00 | 7382.50 | 43.50 |
F2 SW APARTMENT | 1496.00 | 5655.25 | 17.25 |
F2 NW APARTMENT | 369.25 | 7870.50 | 20.25 |
F2 SE APARTMENT | 1912.50 | 5018.25 | 17.00 |
F2 NE APARTMENT | 322.25 | 8013.50 | 20.50 |
F2 N1 APARTMENT | 190.50 | 8306.75 | 36.00 |
F2 N2 APARTMENT | 187.50 | 8316.25 | 35.25 |
F2 S1 APARTMENT | 1532.75 | 5447.00 | 33.50 |
F2 S2 APARTMENT | 1601.75 | 5331.00 | 32.00 |
F3 SW APARTMENT | 1663.25 | 5419.75 | 15.25 |
F3 NW APARTMENT | 344.50 | 7895.50 | 19.25 |
F3 SE APARTMENT | 1676.75 | 5474.50 | 16.25 |
F3 NE APARTMENT | 331.50 | 7984.00 | 19.50 |
F3 N1 APARTMENT | 199.75 | 8228.75 | 37.00 |
F3 N2 APARTMENT | 196.25 | 8239.50 | 36.75 |
F3 S1 APARTMENT | 2004.50 | 4764.25 | 28.50 |
F3 S2 APARTMENT | 2019.50 | 4741.25 | 28.50 |
F4 SW APARTMENT | 1650.25 | 5465.25 | 14.25 |
F4 NW APARTMENT | 330.25 | 7943.75 | 22.75 |
F4 SE APARTMENT | 1590.50 | 5640.00 | 14.75 |
F4 NE APARTMENT | 329.25 | 8007.50 | 23.50 |
F4 N1 APARTMENT | 217.25 | 8197.50 | 46.50 |
F4 N2 APARTMENT | 213.00 | 8208.75 | 46.00 |
F4 S1 APARTMENT | 2160.00 | 4642.50 | 31.50 |
F4 S2 APARTMENT | 2148.50 | 4656.75 | 31.50 |
M SW APARTMENT | 1532.75 | 5658.00 | 13.50 |
M NW APARTMENT | 305.75 | 7994.00 | 19.75 |
M SE APARTMENT | 1484.50 | 5830.00 | 14.00 |
M NE APARTMENT | 316.00 | 8048.50 | 21.75 |
M N1 APARTMENT | 215.75 | 8201.75 | 43.25 |
M N2 APARTMENT | 213.25 | 8211.00 | 42.75 |
M S1 APARTMENT | 2105.50 | 4719.50 | 26.25 |
M S2 APARTMENT | 2090.25 | 4730.25 | 26.00 |
F6 SW APARTMENT | 1236.50 | 6150.00 | 12.75 |
F6 NW APARTMENT | 235.50 | 8175.75 | 18.75 |
F6 SE APARTMENT | 1208.75 | 6303.00 | 13.00 |
F6 NE APARTMENT | 250.50 | 8189.75 | 19.75 |
F6 N1 APARTMENT | 166.50 | 8339.00 | 38.75 |
F6 N2 APARTMENT | 168.25 | 8343.75 | 39.00 |
F6 S1 APARTMENT | 1724.50 | 5240.50 | 24.00 |
F6 S2 APARTMENT | 1716.00 | 5258.75 | 24.00 |
F7 SW APARTMENT | 1029.75 | 6514.50 | 12.50 |
F7 NW APARTMENT | 200.00 | 8277.00 | 18.25 |
F7 SE APARTMENT | 1033.00 | 6604.50 | 12.50 |
F7 NE APARTMENT | 216.25 | 8272.75 | 17.50 |
F7 N1 APARTMENT | 137.50 | 8414.25 | 37.00 |
F7 N2 APARTMENT | 135.75 | 8419.50 | 36.75 |
F7 S1 APARTMENT | 1436.00 | 5653.75 | 21.50 |
F7 S2 APARTMENT | 1430.75 | 5670.75 | 21.00 |
F8 SW APARTMENT | 884.50 | 6789.00 | 11.75 |
F8 NW APARTMENT | 180.75 | 8327.50 | 17.25 |
F8 SE APARTMENT | 915.00 | 6846.00 | 11.75 |
F8 NE APARTMENT | 196.25 | 8329.00 | 17.00 |
F8 N1 APARTMENT | 114.00 | 8461.75 | 34.00 |
F8 N2 APARTMENT | 112.75 | 8469.00 | 33.50 |
F8 S1 APARTMENT | 1219.00 | 6013.50 | 19.25 |
F8 S2 APARTMENT | 1217.25 | 6024.75 | 19.50 |
F9 SW APARTMENT | 761.25 | 7050.00 | 10.50 |
F9 NW APARTMENT | 173.50 | 8359.25 | 17.00 |
F9 SE APARTMENT | 785.50 | 7087.75 | 10.75 |
F9 NE APARTMENT | 182.00 | 8361.75 | 17.00 |
F9 N1 APARTMENT | 106.25 | 8479.25 | 31.25 |
F9 N2 APARTMENT | 106.00 | 8482.25 | 31.25 |
F9 S1 APARTMENT | 998.25 | 6388.00 | 18.50 |
F9 S2 APARTMENT | 993.25 | 6395.75 | 18.50 |
T SW APARTMENT | 1170.25 | 7023.00 | 10.25 |
T NW APARTMENT | 422.25 | 8114.00 | 17.50 |
T SE APARTMENT | 1235.25 | 6991.75 | 11.75 |
T NE APARTMENT | 446.75 | 8027.00 | 21.75 |
T N1 APARTMENT | 271.25 | 8290.50 | 25.00 |
T N2 APARTMENT | 275.50 | 8287.00 | 25.25 |
T S1 APARTMENT | 1206.50 | 6807.00 | 16.50 |
T S2 APARTMENT | 1214.50 | 6808.00 | 16.50 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 3248.50 | 8606.50 | 72.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G NW APARTMENT | 1.00 | 0.25 | 1.00 | 0.25 |
OFFICE | 3.00 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 9.25 | 0.00 | 9.25 | 0.00 |
G N1 APARTMENT | 13.00 | 2.50 | 13.00 | 2.50 |
G N2 APARTMENT | 16.50 | 2.50 | 16.50 | 2.50 |
G S1 APARTMENT | 3.50 | 1.50 | 3.50 | 1.50 |
G S2 APARTMENT | 1.25 | 1.00 | 1.25 | 1.00 |
F2 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F2 NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
F2 SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F2 NE APARTMENT | 6.50 | 0.25 | 6.50 | 0.25 |
F2 N1 APARTMENT | 3.25 | 1.75 | 3.25 | 1.75 |
F2 N2 APARTMENT | 3.25 | 1.75 | 3.25 | 1.75 |
F2 S1 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F2 S2 APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F3 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F3 NW APARTMENT | 2.00 | 0.50 | 2.00 | 0.50 |
F3 SE APARTMENT | 0.25 | 0.25 | 0.25 | 0.25 |
F3 NE APARTMENT | 3.75 | 0.50 | 3.75 | 0.50 |
F3 N1 APARTMENT | 2.50 | 1.75 | 2.50 | 1.75 |
F3 N2 APARTMENT | 1.75 | 1.75 | 1.75 | 1.75 |
F3 S1 APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
F3 S2 APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
F4 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F4 NW APARTMENT | 1.75 | 0.50 | 1.75 | 0.50 |
F4 SE APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F4 NE APARTMENT | 1.75 | 0.75 | 1.75 | 0.75 |
F4 N1 APARTMENT | 1.50 | 1.75 | 1.50 | 1.75 |
F4 N2 APARTMENT | 1.25 | 1.75 | 1.25 | 1.75 |
F4 S1 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
F4 S2 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
M SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M NW APARTMENT | 0.50 | 0.50 | 0.50 | 0.50 |
M SE APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
M NE APARTMENT | 1.50 | 1.00 | 1.50 | 1.00 |
M N1 APARTMENT | 2.50 | 1.75 | 2.50 | 1.75 |
M N2 APARTMENT | 1.00 | 1.75 | 1.00 | 1.75 |
M S1 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
M S2 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
F6 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F6 NW APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
F6 SE APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
F6 NE APARTMENT | 2.50 | 1.50 | 2.50 | 1.50 |
F6 N1 APARTMENT | 3.50 | 1.75 | 3.50 | 1.75 |
F6 N2 APARTMENT | 4.50 | 1.75 | 4.50 | 1.75 |
F6 S1 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
F6 S2 APARTMENT | 0.00 | 2.75 | 0.00 | 2.75 |
F7 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F7 NW APARTMENT | 1.25 | 0.50 | 1.25 | 0.50 |
F7 SE APARTMENT | 0.25 | 0.50 | 0.25 | 0.50 |
F7 NE APARTMENT | 1.75 | 1.50 | 1.75 | 1.50 |
F7 N1 APARTMENT | 4.25 | 1.50 | 4.25 | 1.50 |
F7 N2 APARTMENT | 4.25 | 1.50 | 4.25 | 1.50 |
F7 S1 APARTMENT | 0.25 | 2.00 | 0.25 | 2.00 |
F7 S2 APARTMENT | 0.25 | 2.00 | 0.25 | 2.00 |
F8 SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F8 NW APARTMENT | 1.75 | 0.50 | 1.75 | 0.50 |
F8 SE APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
F8 NE APARTMENT | 3.25 | 1.50 | 3.25 | 1.50 |
F8 N1 APARTMENT | 5.50 | 1.50 | 5.50 | 1.50 |
F8 N2 APARTMENT | 4.50 | 1.50 | 4.50 | 1.50 |
F8 S1 APARTMENT | 0.00 | 1.75 | 0.00 | 1.75 |
F8 S2 APARTMENT | 0.25 | 1.75 | 0.25 | 1.75 |
F9 SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F9 NW APARTMENT | 0.50 | 0.50 | 0.50 | 0.50 |
F9 SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 2.25 | 2.00 | 2.25 | 2.00 |
F9 N1 APARTMENT | 7.25 | 1.50 | 7.25 | 1.50 |
F9 N2 APARTMENT | 6.75 | 1.50 | 6.75 | 1.50 |
F9 S1 APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
F9 S2 APARTMENT | 0.25 | 0.25 | 0.25 | 0.25 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
T SE APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
T NE APARTMENT | 0.00 | 7.25 | 0.00 | 7.25 |
T N1 APARTMENT | 2.75 | 6.25 | 2.75 | 6.25 |
T N2 APARTMENT | 2.75 | 6.00 | 2.75 | 6.00 |
T S1 APARTMENT | 0.50 | 1.75 | 0.50 | 1.75 |
T S2 APARTMENT | 0.50 | 1.75 | 0.50 | 1.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 121.25 | 12.75 | 119.00 | 12.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.208 | 0.000 | 0.474 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.208 | 0.000 | 0.455 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.521 | 0.222 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.207 | 0.000 | 0.454 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.125 | 0.000 | 0.444 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.125 | 0.000 | 0.444 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.125 | 0.000 | 0.466 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.125 | 0.000 | 0.469 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.299 | 0.000 | 0.560 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.298 | 0.000 | 0.539 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.299 | 0.000 | 0.566 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.298 | 0.000 | 0.539 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.180 | 0.000 | 0.530 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.180 | 0.000 | 0.529 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.180 | 0.000 | 0.555 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.180 | 0.000 | 0.556 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.611 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.353 | 0.000 | 0.591 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.354 | 0.000 | 0.613 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.353 | 0.000 | 0.591 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.213 | 0.000 | 0.583 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.213 | 0.000 | 0.583 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.214 | 0.000 | 0.607 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.214 | 0.000 | 0.608 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.396 | 0.000 | 0.614 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.395 | 0.000 | 0.596 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.395 | 0.000 | 0.615 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.395 | 0.000 | 0.597 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.238 | 0.000 | 0.590 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.238 | 0.000 | 0.590 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.239 | 0.000 | 0.611 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.239 | 0.000 | 0.611 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.430 | 0.000 | 0.646 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.429 | 0.000 | 0.629 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.430 | 0.000 | 0.647 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.429 | 0.000 | 0.629 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.259 | 0.000 | 0.624 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.259 | 0.000 | 0.624 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.259 | 0.000 | 0.643 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.259 | 0.000 | 0.644 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.459 | 0.000 | 0.671 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.458 | 0.000 | 0.655 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.459 | 0.000 | 0.672 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.458 | 0.000 | 0.656 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.276 | 0.000 | 0.650 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.276 | 0.000 | 0.650 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.277 | 0.000 | 0.669 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.277 | 0.000 | 0.669 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.485 | 0.000 | 0.692 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.484 | 0.000 | 0.677 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.485 | 0.000 | 0.694 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.484 | 0.000 | 0.678 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.292 | 0.000 | 0.673 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.292 | 0.000 | 0.673 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.293 | 0.000 | 0.691 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.293 | 0.000 | 0.691 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.508 | 0.000 | 0.715 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.507 | 0.000 | 0.700 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.508 | 0.000 | 0.716 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.507 | 0.000 | 0.701 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.306 | 0.000 | 0.696 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.306 | 0.000 | 0.696 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.307 | 0.000 | 0.713 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.307 | 0.000 | 0.713 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.529 | 0.000 | 0.734 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.529 | 0.000 | 0.721 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.529 | 0.000 | 0.736 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.528 | 0.000 | 0.722 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.319 | 0.000 | 0.717 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.319 | 0.000 | 0.717 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.320 | 0.000 | 0.733 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.320 | 0.000 | 0.733 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.549 | 0.000 | 0.750 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.548 | 0.000 | 0.738 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.549 | 0.000 | 0.752 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.548 | 0.000 | 0.740 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.331 | 0.000 | 0.734 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.331 | 0.000 | 0.734 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.354 | 0.331 | 0.000 | 0.748 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.331 | 0.000 | 0.748 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.345 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 473.52 | 15015.24 | 06-JAN-13:15 | 15015.24 | 01-JAN-06:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 610.47 | 15676.48 | 13-APR-02:45 | 64342.56 | 30-JUN-16:45 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
ElectricityPurchased:Plant | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
Cogeneration:ElectricityPurchased | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
ElectricityNet:Plant | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
Cogeneration:ElectricityNet | 2247.28 | 49729.53 | 02-JUN-05:00 | 135664.16 | 30-JUN-16:45 |
ExteriorLights:Electricity | 162.73 | 0.00 | 01-JAN-07:30 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.73 | 0.00 | 01-JAN-07:30 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 473.52 | 15015.24 | 06-JAN-13:15 | 15015.24 | 01-JAN-06:15 |
Cooling:Electricity | 45.38 | 0.00 | 01-JAN-00:15 | 47398.40 | 03-AUG-14:30 |
Heating:Electricity | 55.40 | 0.00 | 02-JAN-13:00 | 46994.03 | 30-APR-15:30 |
Electricity:Plant | 40.19 | 36.93 | 16-JAN-11:00 | 2960.95 | 30-JUN-14:00 |
HeatRejection:Electricity | 1.75 | 0.00 | 01-JAN-00:15 | 1628.64 | 30-JUN-14:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 38.45 | 36.93 | 16-JAN-11:00 | 1332.31 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1228.31 | 2357.00 | 01-JAN-00:15 | 187090.97 | 17-MAY-20:00 |
Gas:Plant | 1228.31 | 2357.00 | 01-JAN-00:15 | 187090.97 | 17-MAY-20:00 |
WaterSystems:Gas | 1093.79 | 2357.00 | 01-JAN-00:15 | 77425.82 | 09-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1093.79 | 2357.00 | 01-JAN-00:15 | 77425.82 | 09-FEB-08:00 |
Heating:Gas | 134.51 | 0.00 | 01-JAN-00:15 | 120179.38 | 17-MAY-20:15 |
Boiler:Heating:Gas | 134.51 | 0.00 | 01-JAN-00:15 | 120179.38 | 17-MAY-20:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 182.41 | 0.00 | 01-JAN-00:15 | 216413.43 | 03-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 182.41 | 0.00 | 01-JAN-00:15 | 216413.43 | 03-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 182.41 | 0.00 | 01-JAN-00:15 | 216413.43 | 03-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 4958.51 | 0.00 | 01-JAN-02:15 | 0.00 | 30-JUN-17:15 |
Water:Plant | 4958.51 | 0.00 | 01-JAN-02:15 | 0.00 | 30-JUN-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 4958.51 | 0.00 | 01-JAN-02:15 | 0.00 | 30-JUN-17:15 |
MainsWater:Plant | 4958.51 | 0.00 | 01-JAN-02:15 | 0.00 | 30-JUN-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 179.99 | 0.00 | 01-JAN-00:15 | 0.00 | 30-JUN-14:00 |
HeatRejection:MainsWater | 179.99 | 0.00 | 01-JAN-00:15 | 0.00 | 30-JUN-14:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1000.39 | 478.53 | 10-AUG-01:15 | 131688.36 | 17-MAY-20:00 |
PlantLoopHeatingDemand:Plant | 850.24 | 478.53 | 10-AUG-01:15 | 54003.88 | 03-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 850.24 | 478.53 | 10-AUG-01:15 | 54003.88 | 03-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1810.42 | 4158.40 | 24-MAY-01:15 | 397462.46 | 11-SEP-18:15 |
EnergyTransfer:Building | 523.76 | 2744.46 | 16-OCT-19:45 | 141651.97 | 30-JUN-16:45 |
EnergyTransfer:Zone:G SW APARTMENT | 4.56 | 0.00 | 14-NOV-14:00 | 1965.53 | 15-SEP-16:15 |
Heating:EnergyTransfer | 169.70 | 0.00 | 01-JAN-12:45 | 137929.28 | 11-SEP-18:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.07 | 0.00 | 01-JAN-00:15 | 1141.93 | 16-APR-13:00 |
Cooling:EnergyTransfer | 354.06 | 0.00 | 04-MAR-15:30 | 141651.97 | 30-JUN-16:45 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 3.49 | 0.00 | 01-JAN-02:00 | 1965.53 | 15-SEP-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 4.68 | 0.01 | 05-JUL-15:00 | 1662.36 | 30-JUN-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.61 | 0.00 | 01-JAN-12:45 | 1447.63 | 12-MAR-08:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 2.07 | 0.00 | 01-JAN-00:15 | 1662.36 | 30-JUN-17:30 |
EnergyTransfer:Zone:OFFICE | 13.92 | 0.01 | 24-JUN-17:00 | 3087.16 | 15-SEP-14:00 |
Heating:EnergyTransfer:Zone:OFFICE | 0.32 | 0.00 | 01-JAN-00:15 | 806.70 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 13.60 | 0.00 | 01-JAN-02:30 | 3087.16 | 15-SEP-14:00 |
EnergyTransfer:Zone:G NE APARTMENT | 5.13 | 0.01 | 19-FEB-15:00 | 1479.52 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.60 | 0.00 | 01-JAN-08:30 | 1479.52 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 2.53 | 0.00 | 01-JAN-00:15 | 1153.88 | 30-JUN-17:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 5.23 | 0.01 | 19-JAN-01:15 | 1392.18 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 1.58 | 0.00 | 01-JAN-06:30 | 1392.18 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.66 | 0.00 | 01-JAN-00:15 | 738.81 | 30-JUN-19:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 5.25 | 0.03 | 04-NOV-24:00 | 1397.37 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 1.59 | 0.00 | 01-JAN-06:30 | 1397.37 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.66 | 0.00 | 01-JAN-00:15 | 724.49 | 30-JUN-19:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 5.62 | 0.01 | 04-MAR-15:15 | 1295.77 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 1012.60 | 16-APR-13:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 5.23 | 0.00 | 07-JAN-11:30 | 1295.77 | 31-AUG-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 5.60 | 0.02 | 09-OCT-13:30 | 1359.00 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.33 | 0.00 | 01-JAN-00:15 | 992.76 | 16-APR-13:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 5.27 | 0.00 | 08-JAN-01:45 | 1359.00 | 31-AUG-13:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 5.46 | 0.01 | 24-MAY-00:15 | 2522.94 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 0.78 | 0.00 | 01-JAN-00:15 | 1149.09 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 4.68 | 0.00 | 03-JAN-04:00 | 2522.94 | 30-JUN-16:45 |
EnergyTransfer:Zone:F2 NW APARTMENT | 4.09 | 0.03 | 29-DEC-05:45 | 2148.43 | 30-JUN-17:30 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 1.77 | 0.00 | 01-JAN-01:00 | 1679.03 | 12-MAR-08:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 2.32 | 0.00 | 01-JAN-00:15 | 2148.43 | 30-JUN-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 6.37 | 0.01 | 29-SEP-01:00 | 2430.79 | 16-SEP-13:15 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.61 | 0.00 | 01-JAN-00:15 | 908.40 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 5.76 | 0.00 | 03-JAN-04:00 | 2430.79 | 16-SEP-13:15 |
EnergyTransfer:Zone:F2 NE APARTMENT | 4.71 | 0.01 | 28-SEP-08:00 | 1754.45 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 1.67 | 0.00 | 01-JAN-01:00 | 1754.45 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 3.04 | 0.00 | 01-JAN-00:15 | 1580.23 | 30-JUN-17:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 5.53 | 0.01 | 25-FEB-04:30 | 1594.35 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 0.86 | 0.00 | 01-JAN-00:15 | 1594.35 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 4.67 | 0.00 | 01-JAN-04:30 | 1069.29 | 30-JUN-19:00 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 5.54 | 0.00 | 21-OCT-14:00 | 1600.43 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 0.87 | 0.00 | 01-JAN-00:15 | 1600.43 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 4.67 | 0.00 | 01-JAN-04:30 | 1056.57 | 30-JUN-19:00 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 6.79 | 0.01 | 27-MAY-10:15 | 1758.17 | 16-SEP-15:45 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1035.00 | 21-APR-12:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 6.51 | 0.00 | 19-JAN-12:45 | 1758.17 | 16-SEP-15:45 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 6.85 | 0.00 | 15-APR-12:45 | 1762.85 | 16-SEP-15:45 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 1004.50 | 21-APR-12:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 6.58 | 0.00 | 19-JAN-12:45 | 1762.85 | 16-SEP-15:45 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 5.92 | 0.00 | 08-OCT-02:00 | 2551.10 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.87 | 0.00 | 01-JAN-00:15 | 1366.54 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 5.05 | 0.00 | 03-JAN-04:00 | 2551.10 | 30-JUN-16:45 |
EnergyTransfer:Zone:F3 NW APARTMENT | 4.30 | 0.01 | 03-JAN-23:45 | 2178.02 | 30-JUN-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 1.89 | 0.00 | 01-JAN-00:30 | 1889.12 | 21-APR-12:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 2178.02 | 30-JUN-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 6.47 | 0.03 | 08-OCT-00:15 | 2302.91 | 16-SEP-14:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.73 | 0.00 | 01-JAN-00:15 | 1403.58 | 21-JUN-15:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 5.74 | 0.00 | 03-JAN-13:00 | 2302.91 | 16-SEP-14:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 5.00 | 0.00 | 08-AUG-09:45 | 2059.20 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 1.84 | 0.00 | 01-JAN-00:30 | 2059.20 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 3.16 | 0.00 | 01-JAN-00:15 | 1619.12 | 30-JUN-17:30 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 5.87 | 0.00 | 04-SEP-09:15 | 1823.63 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 0.97 | 0.00 | 01-JAN-00:15 | 1823.63 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 4.90 | 0.00 | 01-JAN-05:00 | 1120.95 | 30-JUN-17:45 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 5.88 | 0.00 | 09-AUG-09:45 | 1830.12 | 22-APR-15:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 0.98 | 0.00 | 01-JAN-00:15 | 1830.12 | 22-APR-15:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 4.90 | 0.00 | 01-JAN-05:00 | 1108.23 | 30-JUN-17:45 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 7.61 | 0.02 | 04-MAY-11:30 | 1830.09 | 16-SEP-15:45 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1252.58 | 21-JUN-15:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 7.24 | 0.00 | 19-JAN-12:45 | 1830.09 | 16-SEP-15:45 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 7.63 | 0.00 | 06-AUG-09:45 | 1837.32 | 16-SEP-15:45 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 1252.43 | 21-JUN-15:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 7.26 | 0.00 | 19-JAN-12:45 | 1837.32 | 16-SEP-15:45 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 5.98 | 0.00 | 15-FEB-11:30 | 2571.18 | 15-SEP-16:15 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1513.05 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 5.02 | 0.00 | 03-JAN-04:00 | 2571.18 | 15-SEP-16:15 |
EnergyTransfer:Zone:F4 NW APARTMENT | 4.42 | 0.05 | 17-OCT-01:00 | 2181.95 | 30-JUN-17:15 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 2.06 | 0.00 | 01-JAN-00:30 | 2010.73 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 2.36 | 0.00 | 01-JAN-00:15 | 2181.95 | 30-JUN-17:15 |
EnergyTransfer:Zone:F4 SE APARTMENT | 6.46 | 0.02 | 14-MAY-06:30 | 2293.79 | 16-SEP-14:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.88 | 0.00 | 01-JAN-00:15 | 1571.03 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 5.57 | 0.00 | 03-JAN-13:15 | 2293.79 | 16-SEP-14:00 |
EnergyTransfer:Zone:F4 NE APARTMENT | 5.14 | 0.00 | 20-AUG-09:30 | 2123.05 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 2.03 | 0.00 | 01-JAN-00:15 | 2123.05 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 3.12 | 0.00 | 01-JAN-01:45 | 1629.90 | 30-JUN-17:30 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 5.95 | 0.02 | 22-AUG-11:15 | 1929.14 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 1.02 | 0.00 | 01-JAN-00:15 | 1929.14 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 4.93 | 0.00 | 01-JAN-05:00 | 1138.22 | 30-JUN-17:45 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 5.97 | 0.01 | 27-MAY-13:00 | 1919.94 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 1.03 | 0.00 | 01-JAN-00:15 | 1919.94 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 4.94 | 0.00 | 01-JAN-05:00 | 1125.70 | 30-JUN-17:45 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 7.90 | 0.00 | 15-MAY-07:45 | 1874.84 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.44 | 0.00 | 01-JAN-00:15 | 1369.43 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 7.46 | 0.00 | 19-JAN-12:45 | 1874.84 | 19-NOV-14:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 7.89 | 0.00 | 27-SEP-11:30 | 1877.11 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.44 | 0.00 | 01-JAN-00:15 | 1374.03 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 7.45 | 0.00 | 19-JAN-12:45 | 1877.11 | 19-NOV-14:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 5.97 | 0.00 | 04-NOV-14:45 | 2589.37 | 15-SEP-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.17 | 0.00 | 01-JAN-00:15 | 1693.11 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 4.80 | 0.00 | 03-JAN-03:45 | 2589.37 | 15-SEP-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 4.67 | 0.02 | 28-FEB-15:15 | 2235.88 | 03-OCT-10:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 2.41 | 0.00 | 01-JAN-00:15 | 2235.88 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 2.26 | 0.00 | 01-JAN-01:45 | 2203.50 | 30-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 6.43 | 0.02 | 21-APR-11:45 | 2320.78 | 16-SEP-14:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.11 | 0.00 | 01-JAN-00:15 | 1793.70 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 5.32 | 0.00 | 03-JAN-13:15 | 2320.78 | 16-SEP-14:00 |
EnergyTransfer:Zone:M NE APARTMENT | 5.41 | 0.01 | 13-MAR-19:45 | 2357.83 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 2.39 | 0.00 | 01-JAN-00:30 | 2357.83 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 3.02 | 0.00 | 01-JAN-00:15 | 1654.62 | 09-AUG-15:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 6.12 | 0.01 | 27-JUN-11:30 | 2136.64 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.26 | 0.00 | 01-JAN-00:15 | 2136.64 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 4.87 | 0.00 | 03-JAN-05:00 | 1168.69 | 30-JUN-17:45 |
EnergyTransfer:Zone:M N2 APARTMENT | 6.14 | 0.00 | 07-AUG-10:15 | 2127.37 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.27 | 0.00 | 01-JAN-00:15 | 2127.37 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 4.88 | 0.00 | 03-JAN-05:00 | 1156.36 | 30-JUN-17:45 |
EnergyTransfer:Zone:M S1 APARTMENT | 7.94 | 0.05 | 09-SEP-08:45 | 1917.38 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 1578.64 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 7.35 | 0.00 | 19-JAN-12:45 | 1917.38 | 19-NOV-14:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 7.92 | 0.03 | 13-SEP-11:15 | 1918.86 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 1583.81 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 7.33 | 0.00 | 19-JAN-12:45 | 1918.86 | 19-NOV-14:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 5.80 | 0.01 | 21-APR-10:45 | 2544.98 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 1.52 | 0.00 | 01-JAN-00:15 | 1922.76 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 4.28 | 0.00 | 03-JAN-03:45 | 2544.98 | 30-JUN-16:45 |
EnergyTransfer:Zone:F6 NW APARTMENT | 5.22 | 0.01 | 08-OCT-02:30 | 2501.03 | 03-OCT-10:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 3.19 | 0.00 | 01-JAN-00:30 | 2501.03 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 2.03 | 0.00 | 01-JAN-00:15 | 2161.71 | 30-JUN-17:15 |
EnergyTransfer:Zone:F6 SE APARTMENT | 6.27 | 0.00 | 24-MAY-13:15 | 2287.29 | 16-SEP-14:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 1.49 | 0.00 | 01-JAN-00:15 | 2035.56 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 4.78 | 0.00 | 03-JAN-13:15 | 2287.29 | 16-SEP-14:00 |
EnergyTransfer:Zone:F6 NE APARTMENT | 5.94 | 0.01 | 08-AUG-09:15 | 2634.89 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 3.22 | 0.00 | 01-JAN-00:45 | 2634.89 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 2.72 | 0.00 | 01-JAN-00:15 | 1621.66 | 09-AUG-15:30 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 6.34 | 0.01 | 08-JUL-18:15 | 2384.18 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 1.75 | 0.00 | 01-JAN-00:15 | 2384.18 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 4.58 | 0.00 | 01-JAN-04:45 | 1138.66 | 30-JUN-17:30 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 6.36 | 0.02 | 11-DEC-03:45 | 2375.28 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 1.76 | 0.00 | 01-JAN-00:15 | 2375.28 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 4.59 | 0.00 | 01-JAN-04:45 | 1126.64 | 30-JUN-17:30 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 7.62 | 0.02 | 08-OCT-09:00 | 1877.81 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.82 | 0.00 | 01-JAN-00:15 | 1827.67 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 6.80 | 0.00 | 19-JAN-12:45 | 1877.81 | 19-NOV-14:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 7.61 | 0.02 | 11-MAR-12:30 | 1879.14 | 19-NOV-14:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.82 | 0.00 | 01-JAN-00:15 | 1831.61 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 6.78 | 0.00 | 19-JAN-12:45 | 1879.14 | 19-NOV-14:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 5.79 | 0.00 | 27-AUG-09:00 | 2528.33 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 1.89 | 0.00 | 01-JAN-00:15 | 2111.19 | 17-MAY-20:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 3.90 | 0.00 | 03-JAN-03:45 | 2528.33 | 30-JUN-16:45 |
EnergyTransfer:Zone:F7 NW APARTMENT | 5.76 | 0.00 | 27-MAY-04:15 | 2719.20 | 03-OCT-10:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 3.92 | 0.00 | 01-JAN-00:45 | 2719.20 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 1.84 | 0.00 | 01-JAN-00:15 | 2143.42 | 30-JUN-17:15 |
EnergyTransfer:Zone:F7 SE APARTMENT | 6.28 | 0.05 | 31-JUL-03:45 | 2275.61 | 16-SEP-14:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 1.89 | 0.00 | 01-JAN-00:15 | 2234.35 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 4.39 | 0.00 | 03-JAN-13:15 | 2275.61 | 16-SEP-14:00 |
EnergyTransfer:Zone:F7 NE APARTMENT | 6.45 | 0.03 | 06-OCT-10:00 | 2865.45 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 3.96 | 0.00 | 01-JAN-00:45 | 2865.45 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 2.49 | 0.00 | 01-JAN-00:15 | 1602.34 | 09-AUG-15:30 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 6.53 | 0.02 | 27-JUN-09:30 | 2491.09 | 30-APR-15:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 2.20 | 0.00 | 01-JAN-00:15 | 2491.09 | 30-APR-15:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 4.33 | 0.00 | 01-JAN-04:45 | 1129.60 | 30-JUN-17:15 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 6.55 | 0.00 | 21-OCT-13:45 | 2474.95 | 30-APR-15:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 2.21 | 0.00 | 01-JAN-00:15 | 2474.95 | 30-APR-15:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 4.34 | 0.00 | 01-JAN-04:45 | 1117.92 | 30-JUN-17:15 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 7.45 | 0.02 | 02-OCT-09:30 | 2027.94 | 21-JUN-14:45 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 1.05 | 0.00 | 01-JAN-00:15 | 2027.94 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 6.39 | 0.00 | 19-JAN-12:45 | 1849.58 | 19-NOV-14:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 7.44 | 0.01 | 11-MAY-08:00 | 2030.85 | 21-JUN-14:45 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 1.06 | 0.00 | 01-JAN-00:15 | 2030.85 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 6.38 | 0.00 | 19-JAN-12:45 | 1850.88 | 19-NOV-14:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 5.87 | 0.01 | 02-JUN-23:15 | 2524.44 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 2.30 | 0.00 | 01-JAN-00:15 | 2275.50 | 16-APR-13:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 3.57 | 0.00 | 03-JAN-03:45 | 2524.44 | 30-JUN-16:45 |
EnergyTransfer:Zone:F8 NW APARTMENT | 6.32 | 0.02 | 31-OCT-15:00 | 2913.35 | 03-OCT-10:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 4.62 | 0.00 | 01-JAN-00:45 | 2913.35 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 1.70 | 0.00 | 01-JAN-00:15 | 2138.20 | 30-JUN-17:15 |
EnergyTransfer:Zone:F8 SE APARTMENT | 6.35 | 0.00 | 17-FEB-12:15 | 2476.25 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 2.31 | 0.00 | 01-JAN-00:15 | 2476.25 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 4.04 | 0.00 | 03-JAN-06:45 | 2274.78 | 16-SEP-14:00 |
EnergyTransfer:Zone:F8 NE APARTMENT | 6.99 | 0.00 | 19-JUL-03:15 | 3068.18 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 4.67 | 0.00 | 01-JAN-00:45 | 3068.18 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 2.31 | 0.00 | 01-JAN-00:15 | 1594.33 | 30-JUN-17:15 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 6.74 | 0.01 | 18-JUN-09:00 | 2508.99 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 2.64 | 0.00 | 01-JAN-00:15 | 2508.99 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 4.10 | 0.00 | 01-JAN-04:30 | 1132.55 | 30-JUN-17:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 6.76 | 0.01 | 13-NOV-15:15 | 2494.06 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 2.65 | 0.00 | 01-JAN-00:15 | 2494.06 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 4.11 | 0.00 | 01-JAN-04:30 | 1121.06 | 30-JUN-17:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 7.32 | 0.01 | 24-MAY-04:45 | 2198.14 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 1.30 | 0.00 | 01-JAN-00:15 | 2198.14 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 6.02 | 0.00 | 19-JAN-12:45 | 1836.47 | 16-SEP-15:45 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 7.31 | 0.03 | 22-JUL-09:00 | 2196.86 | 21-JUN-14:45 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 1.31 | 0.00 | 01-JAN-00:15 | 2196.86 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 6.00 | 0.00 | 19-JAN-12:45 | 1844.04 | 16-SEP-15:45 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 5.96 | 0.01 | 21-DEC-15:00 | 2579.61 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 2.85 | 0.00 | 01-JAN-00:15 | 2536.10 | 16-APR-13:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 3.11 | 0.00 | 02-JAN-07:45 | 2579.61 | 30-JUN-16:45 |
EnergyTransfer:Zone:F9 NW APARTMENT | 6.93 | 0.00 | 24-SEP-23:45 | 3121.41 | 03-OCT-10:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 5.46 | 0.00 | 01-JAN-01:00 | 3121.41 | 03-OCT-10:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 1.48 | 0.00 | 01-JAN-00:15 | 2199.21 | 30-JUN-17:15 |
EnergyTransfer:Zone:F9 SE APARTMENT | 6.40 | 0.02 | 22-APR-16:00 | 2682.76 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 2.83 | 0.00 | 01-JAN-00:15 | 2682.76 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 3.57 | 0.00 | 03-JAN-04:00 | 2311.47 | 16-SEP-13:45 |
EnergyTransfer:Zone:F9 NE APARTMENT | 7.58 | 0.01 | 17-NOV-15:30 | 3250.86 | 22-APR-14:45 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 5.47 | 0.00 | 01-JAN-01:00 | 3250.86 | 22-APR-14:45 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 2.11 | 0.00 | 01-JAN-00:15 | 1621.82 | 09-AUG-15:30 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 6.85 | 0.00 | 07-AUG-09:15 | 2664.80 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.12 | 0.00 | 01-JAN-00:15 | 2664.80 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 3.73 | 0.00 | 01-JAN-03:00 | 1192.03 | 30-JUN-17:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 6.86 | 0.01 | 06-AUG-10:15 | 2649.87 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.13 | 0.00 | 01-JAN-00:15 | 2649.87 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 3.73 | 0.00 | 01-JAN-03:00 | 1180.68 | 30-JUN-17:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 7.04 | 0.03 | 27-OCT-14:00 | 2344.64 | 30-APR-15:45 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 1.57 | 0.00 | 01-JAN-00:15 | 2344.64 | 30-APR-15:45 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 5.47 | 0.00 | 19-JAN-12:45 | 1877.46 | 16-SEP-15:45 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 7.03 | 0.00 | 04-AUG-19:30 | 2337.89 | 21-JUN-14:45 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 1.57 | 0.00 | 01-JAN-00:15 | 2337.89 | 21-JUN-14:45 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 5.45 | 0.00 | 19-JAN-12:45 | 1886.02 | 16-SEP-15:45 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 9.58 | 0.01 | 12-FEB-19:30 | 3222.31 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 6.11 | 0.00 | 01-JAN-00:30 | 2993.85 | 16-APR-13:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 3.47 | 0.00 | 01-JAN-00:15 | 3222.31 | 30-JUN-16:45 |
EnergyTransfer:Zone:T NW APARTMENT | 9.90 | 0.00 | 17-APR-22:15 | 3526.93 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.71 | 0.00 | 01-JAN-09:45 | 3526.93 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 2730.19 | 30-JUN-16:45 |
EnergyTransfer:Zone:T SE APARTMENT | 9.78 | 0.00 | 11-JAN-19:45 | 3092.94 | 11-SEP-18:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 6.00 | 0.00 | 01-JAN-00:30 | 3092.94 | 11-SEP-18:15 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 3.78 | 0.00 | 01-JAN-00:15 | 2907.62 | 16-SEP-13:45 |
EnergyTransfer:Zone:T NE APARTMENT | 10.30 | 0.03 | 02-APR-23:30 | 3605.59 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 8.66 | 0.00 | 01-JAN-08:30 | 3605.59 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 1.64 | 0.00 | 01-JAN-00:15 | 2071.00 | 09-AUG-15:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 6.96 | 0.02 | 06-MAR-12:45 | 3198.90 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 4.59 | 0.00 | 01-JAN-09:00 | 3198.90 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 2.37 | 0.00 | 01-JAN-00:15 | 1645.71 | 09-AUG-15:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 6.97 | 0.00 | 03-APR-12:15 | 3205.79 | 20-NOV-19:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 4.61 | 0.00 | 01-JAN-09:00 | 3205.79 | 20-NOV-19:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 2.36 | 0.00 | 01-JAN-00:15 | 1646.21 | 09-AUG-15:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 7.10 | 0.00 | 08-OCT-23:30 | 2664.49 | 11-SEP-18:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.59 | 0.00 | 01-JAN-00:15 | 2664.49 | 11-SEP-18:15 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 4.51 | 0.00 | 01-JAN-04:15 | 2468.24 | 06-OCT-13:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 7.12 | 0.01 | 08-FEB-12:30 | 2688.31 | 11-SEP-18:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.61 | 0.00 | 01-JAN-00:15 | 2688.31 | 11-SEP-18:15 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 4.51 | 0.00 | 01-JAN-04:15 | 2472.31 | 06-OCT-13:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 946.96 | 478.53 | 10-AUG-01:15 | 126967.28 | 17-MAY-20:00 |
WaterSystems:EnergyTransfer | 850.23 | 478.53 | 10-AUG-01:15 | 53998.36 | 03-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 850.23 | 478.53 | 10-AUG-01:15 | 53998.36 | 03-FEB-08:00 |
EnergyTransfer:HVAC | 339.70 | 0.00 | 16-JAN-11:00 | 169155.80 | 03-AUG-14:30 |
CoolingCoils:EnergyTransfer | 141.98 | 0.00 | 01-JAN-00:15 | 169155.80 | 03-AUG-14:30 |
HeatingCoils:EnergyTransfer | 197.72 | 0.00 | 02-JAN-13:00 | 135468.38 | 11-SEP-18:15 |
PlantLoopHeatingDemand:HVAC | 150.15 | 0.00 | 02-JAN-13:00 | 93381.13 | 17-MAY-20:00 |
HeatingCoils:PlantLoopHeatingDemand | 150.15 | 0.00 | 02-JAN-13:00 | 93381.13 | 17-MAY-20:00 |
Boilers:EnergyTransfer | 96.73 | 0.00 | 01-JAN-00:15 | 90134.54 | 17-MAY-20:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.071 | -3.493 | 0.000 | 0.000 | 3.898 | 1.087 | 12.213 | 16.904 | 0.000 | 0.046 | 0.000 | 0.000 | -8.678 | 0.000 | -11.488 | -11.559 |
G NW APARTMENT | 2.611 | -2.069 | 0.000 | 0.000 | 3.970 | 1.087 | 12.213 | 8.339 | 0.000 | 0.047 | 0.000 | 0.000 | -8.442 | 0.000 | -10.426 | -7.328 |
OFFICE | 0.319 | -13.605 | 0.000 | 0.000 | 0.508 | 29.882 | 9.495 | 16.184 | 0.000 | 0.020 | 0.000 | 0.000 | -8.936 | 0.000 | -5.195 | -28.673 |
G NE APARTMENT | 2.598 | -2.533 | 0.000 | 0.000 | 3.997 | 1.087 | 12.213 | 7.759 | 0.000 | 0.046 | 0.000 | 0.000 | -8.186 | 0.000 | -10.231 | -6.749 |
G N1 APARTMENT | 1.575 | -3.656 | 0.000 | 0.000 | 3.992 | 1.087 | 12.213 | 2.541 | 0.000 | 0.040 | 0.000 | 0.000 | -5.158 | 0.000 | -8.041 | -4.592 |
G N2 APARTMENT | 1.586 | -3.664 | 0.000 | 0.000 | 3.994 | 1.087 | 12.213 | 2.541 | 0.000 | 0.040 | 0.000 | 0.000 | -5.151 | 0.000 | -8.032 | -4.613 |
G S1 APARTMENT | 0.397 | -5.227 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 11.278 | 0.000 | 0.038 | 0.000 | 0.000 | -5.399 | 0.000 | -9.159 | -9.114 |
G S2 APARTMENT | 0.331 | -5.270 | 0.000 | 0.000 | 3.873 | 1.087 | 12.213 | 11.248 | 0.000 | 0.038 | 0.000 | 0.000 | -5.430 | 0.000 | -9.295 | -8.795 |
F2 SW APARTMENT | 0.781 | -4.683 | 0.000 | 0.000 | 3.768 | 1.087 | 12.213 | 15.784 | 0.000 | 0.061 | 0.001 | 0.000 | -9.572 | 0.000 | -15.540 | -3.898 |
F2 NW APARTMENT | 1.771 | -2.319 | 0.000 | 0.000 | 3.914 | 1.087 | 12.213 | 7.562 | 0.000 | 0.061 | 0.000 | 0.000 | -9.063 | 0.000 | -13.813 | -1.414 |
F2 SE APARTMENT | 0.609 | -5.764 | 0.000 | 0.000 | 3.744 | 1.087 | 12.213 | 15.338 | 0.000 | 0.061 | 0.001 | 0.000 | -9.649 | 0.000 | -15.942 | -1.696 |
F2 NE APARTMENT | 1.671 | -3.041 | 0.000 | 0.000 | 3.951 | 1.087 | 12.213 | 7.146 | 0.000 | 0.061 | 0.000 | 0.000 | -8.746 | 0.000 | -13.556 | -0.786 |
F2 N1 APARTMENT | 0.864 | -4.666 | 0.000 | 0.000 | 3.931 | 1.087 | 12.213 | 2.191 | 0.000 | 0.050 | 0.412 | 0.000 | -5.605 | 0.000 | -10.477 | -0.000 |
F2 N2 APARTMENT | 0.873 | -4.671 | 0.000 | 0.000 | 3.934 | 1.087 | 12.213 | 2.192 | 0.000 | 0.050 | 0.378 | 0.000 | -5.595 | 0.000 | -10.460 | -0.001 |
F2 S1 APARTMENT | 0.276 | -6.515 | 0.000 | 0.000 | 3.735 | 1.087 | 12.213 | 10.633 | 0.000 | 0.050 | 0.000 | 0.000 | -5.977 | 0.000 | -12.295 | -3.208 |
F2 S2 APARTMENT | 0.268 | -6.583 | 0.000 | 0.000 | 3.730 | 1.087 | 12.213 | 10.622 | 0.000 | 0.050 | 0.000 | 0.000 | -5.993 | 0.000 | -12.355 | -3.038 |
F3 SW APARTMENT | 0.870 | -5.051 | 0.000 | 0.000 | 3.757 | 1.087 | 12.213 | 15.325 | 0.000 | 0.074 | 0.000 | 0.000 | -9.791 | 0.000 | -17.490 | -0.992 |
F3 NW APARTMENT | 1.891 | -2.410 | 0.000 | 0.000 | 3.913 | 1.087 | 12.213 | 7.249 | 0.000 | 0.074 | 0.808 | 0.000 | -9.240 | 0.000 | -15.583 | -0.000 |
F3 SE APARTMENT | 0.731 | -5.742 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 15.059 | 0.000 | 0.073 | 0.000 | 0.000 | -9.676 | 0.000 | -17.451 | -0.067 |
F3 NE APARTMENT | 1.842 | -3.160 | 0.000 | 0.000 | 3.948 | 1.087 | 12.213 | 6.910 | 0.000 | 0.073 | 1.325 | 0.000 | -8.913 | 0.000 | -15.325 | -0.000 |
F3 N1 APARTMENT | 0.969 | -4.898 | 0.000 | 0.000 | 3.915 | 1.087 | 12.213 | 2.064 | 0.000 | 0.060 | 2.184 | 0.000 | -5.754 | 0.000 | -11.840 | 0.000 |
F3 N2 APARTMENT | 0.979 | -4.902 | 0.000 | 0.000 | 3.918 | 1.087 | 12.213 | 2.066 | 0.000 | 0.060 | 2.145 | 0.000 | -5.744 | 0.000 | -11.822 | 0.000 |
F3 S1 APARTMENT | 0.366 | -7.242 | 0.000 | 0.000 | 3.708 | 1.087 | 12.213 | 10.362 | 0.000 | 0.060 | 0.001 | 0.000 | -6.150 | 0.000 | -13.826 | -0.578 |
F3 S2 APARTMENT | 0.364 | -7.263 | 0.000 | 0.000 | 3.707 | 1.087 | 12.213 | 10.358 | 0.000 | 0.060 | 0.000 | 0.000 | -6.151 | 0.000 | -13.842 | -0.534 |
F4 SW APARTMENT | 0.961 | -5.020 | 0.000 | 0.000 | 3.764 | 1.087 | 12.213 | 15.049 | 0.000 | 0.080 | 0.000 | 0.000 | -9.861 | 0.000 | -18.158 | -0.114 |
F4 NW APARTMENT | 2.060 | -2.356 | 0.000 | 0.000 | 3.918 | 1.087 | 12.213 | 7.060 | 0.000 | 0.080 | 1.496 | 0.000 | -9.315 | 0.000 | -16.242 | -0.000 |
F4 SE APARTMENT | 0.882 | -5.574 | 0.000 | 0.000 | 3.787 | 1.087 | 12.213 | 14.858 | 0.000 | 0.080 | 0.397 | 0.000 | -9.698 | 0.000 | -18.031 | -0.000 |
F4 NE APARTMENT | 2.028 | -3.115 | 0.000 | 0.000 | 3.951 | 1.087 | 12.213 | 6.769 | 0.000 | 0.080 | 1.979 | 0.000 | -8.988 | 0.000 | -16.003 | -0.000 |
F4 N1 APARTMENT | 1.022 | -4.931 | 0.000 | 0.000 | 3.911 | 1.087 | 12.213 | 1.991 | 0.000 | 0.065 | 2.693 | 0.000 | -5.828 | 0.000 | -12.222 | 0.000 |
F4 N2 APARTMENT | 1.032 | -4.938 | 0.000 | 0.000 | 3.914 | 1.087 | 12.213 | 1.992 | 0.000 | 0.065 | 2.658 | 0.000 | -5.818 | 0.000 | -12.205 | 0.000 |
F4 S1 APARTMENT | 0.440 | -7.456 | 0.000 | 0.000 | 3.706 | 1.087 | 12.213 | 10.198 | 0.000 | 0.065 | 0.154 | 0.000 | -6.216 | 0.000 | -14.191 | -0.000 |
F4 S2 APARTMENT | 0.443 | -7.446 | 0.000 | 0.000 | 3.706 | 1.087 | 12.213 | 10.197 | 0.000 | 0.065 | 0.139 | 0.000 | -6.212 | 0.000 | -14.193 | -0.000 |
M SW APARTMENT | 1.166 | -4.800 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 14.854 | 0.000 | 0.085 | 0.704 | 0.000 | -9.887 | 0.000 | -19.199 | -0.001 |
M NW APARTMENT | 2.408 | -2.262 | 0.000 | 0.000 | 3.926 | 1.087 | 12.213 | 6.925 | 0.000 | 0.085 | 2.245 | 0.000 | -9.361 | 0.000 | -17.264 | -0.000 |
M SE APARTMENT | 1.111 | -5.322 | 0.000 | 0.000 | 3.800 | 1.087 | 12.213 | 14.705 | 0.000 | 0.085 | 1.095 | 0.000 | -9.713 | 0.000 | -19.060 | -0.000 |
M NE APARTMENT | 2.393 | -3.020 | 0.000 | 0.000 | 3.956 | 1.087 | 12.213 | 6.667 | 0.000 | 0.085 | 2.703 | 0.000 | -9.038 | 0.000 | -17.046 | -0.000 |
M N1 APARTMENT | 1.255 | -4.867 | 0.000 | 0.000 | 3.913 | 1.087 | 12.213 | 1.941 | 0.000 | 0.069 | 3.282 | 0.000 | -5.875 | 0.000 | -13.017 | 0.000 |
M N2 APARTMENT | 1.266 | -4.875 | 0.000 | 0.000 | 3.916 | 1.087 | 12.213 | 1.942 | 0.000 | 0.069 | 3.252 | 0.000 | -5.866 | 0.000 | -13.002 | 0.000 |
M S1 APARTMENT | 0.585 | -7.350 | 0.000 | 0.000 | 3.712 | 1.087 | 12.213 | 10.083 | 0.000 | 0.069 | 0.844 | 0.000 | -6.247 | 0.000 | -14.995 | -0.000 |
M S2 APARTMENT | 0.590 | -7.331 | 0.000 | 0.000 | 3.714 | 1.087 | 12.213 | 10.082 | 0.000 | 0.069 | 0.813 | 0.000 | -6.242 | 0.000 | -14.993 | -0.000 |
F6 SW APARTMENT | 1.518 | -4.282 | 0.000 | 0.000 | 3.810 | 1.087 | 12.213 | 14.759 | 0.000 | 0.089 | 0.432 | 0.000 | -9.793 | 0.000 | -19.832 | -0.000 |
F6 NW APARTMENT | 3.194 | -2.027 | 0.000 | 0.000 | 3.951 | 1.087 | 12.213 | 6.872 | 0.000 | 0.089 | 1.841 | 0.000 | -9.295 | 0.000 | -17.925 | -0.000 |
F6 SE APARTMENT | 1.490 | -4.785 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 14.636 | 0.000 | 0.089 | 0.766 | 0.000 | -9.619 | 0.000 | -19.708 | -0.000 |
F6 NE APARTMENT | 3.219 | -2.720 | 0.000 | 0.000 | 3.978 | 1.087 | 12.213 | 6.640 | 0.000 | 0.089 | 2.219 | 0.000 | -8.982 | 0.000 | -17.741 | -0.000 |
F6 N1 APARTMENT | 1.752 | -4.584 | 0.000 | 0.000 | 3.938 | 1.087 | 12.213 | 1.933 | 0.000 | 0.072 | 2.928 | 0.000 | -5.835 | 0.000 | -13.505 | 0.000 |
F6 N2 APARTMENT | 1.763 | -4.592 | 0.000 | 0.000 | 3.941 | 1.087 | 12.213 | 1.934 | 0.000 | 0.072 | 2.903 | 0.000 | -5.827 | 0.000 | -13.493 | 0.000 |
F6 S1 APARTMENT | 0.818 | -6.804 | 0.000 | 0.000 | 3.742 | 1.087 | 12.213 | 10.025 | 0.000 | 0.072 | 0.503 | 0.000 | -6.198 | 0.000 | -15.457 | -0.000 |
F6 S2 APARTMENT | 0.823 | -6.785 | 0.000 | 0.000 | 3.743 | 1.087 | 12.213 | 10.025 | 0.000 | 0.072 | 0.471 | 0.000 | -6.193 | 0.000 | -15.456 | -0.000 |
F7 SW APARTMENT | 1.893 | -3.895 | 0.000 | 0.000 | 3.835 | 1.087 | 12.213 | 14.670 | 0.000 | 0.093 | 0.221 | 0.000 | -9.727 | 0.000 | -20.390 | -0.000 |
F7 NW APARTMENT | 3.919 | -1.845 | 0.000 | 0.000 | 3.969 | 1.087 | 12.213 | 6.816 | 0.000 | 0.093 | 1.545 | 0.000 | -9.258 | 0.000 | -18.538 | -0.000 |
F7 SE APARTMENT | 1.890 | -4.386 | 0.000 | 0.000 | 3.856 | 1.087 | 12.213 | 14.568 | 0.000 | 0.093 | 0.519 | 0.000 | -9.556 | 0.000 | -20.283 | -0.000 |
F7 NE APARTMENT | 3.962 | -2.493 | 0.000 | 0.000 | 3.992 | 1.087 | 12.213 | 6.604 | 0.000 | 0.092 | 1.878 | 0.000 | -8.954 | 0.000 | -18.380 | -0.000 |
F7 N1 APARTMENT | 2.200 | -4.333 | 0.000 | 0.000 | 3.956 | 1.087 | 12.213 | 1.922 | 0.000 | 0.075 | 2.642 | 0.000 | -5.812 | 0.000 | -13.949 | 0.000 |
F7 N2 APARTMENT | 2.210 | -4.340 | 0.000 | 0.000 | 3.958 | 1.087 | 12.213 | 1.922 | 0.000 | 0.075 | 2.621 | 0.000 | -5.805 | 0.000 | -13.940 | 0.000 |
F7 S1 APARTMENT | 1.053 | -6.395 | 0.000 | 0.000 | 3.766 | 1.087 | 12.213 | 9.973 | 0.000 | 0.075 | 0.245 | 0.000 | -6.161 | 0.000 | -15.855 | -0.000 |
F7 S2 APARTMENT | 1.058 | -6.377 | 0.000 | 0.000 | 3.767 | 1.087 | 12.213 | 9.972 | 0.000 | 0.075 | 0.217 | 0.000 | -6.156 | 0.000 | -15.854 | -0.001 |
F8 SW APARTMENT | 2.302 | -3.567 | 0.000 | 0.000 | 3.856 | 1.087 | 12.213 | 14.591 | 0.000 | 0.097 | 0.074 | 0.000 | -9.675 | 0.000 | -20.978 | -0.000 |
F8 NW APARTMENT | 4.619 | -1.696 | 0.000 | 0.000 | 3.981 | 1.087 | 12.213 | 6.761 | 0.000 | 0.097 | 1.365 | 0.000 | -9.239 | 0.000 | -19.187 | -0.000 |
F8 SE APARTMENT | 2.315 | -4.040 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 14.506 | 0.000 | 0.097 | 0.345 | 0.000 | -9.508 | 0.000 | -20.889 | -0.000 |
F8 NE APARTMENT | 4.674 | -2.314 | 0.000 | 0.000 | 4.001 | 1.087 | 12.213 | 6.567 | 0.000 | 0.097 | 1.666 | 0.000 | -8.942 | 0.000 | -19.049 | -0.000 |
F8 N1 APARTMENT | 2.641 | -4.103 | 0.000 | 0.000 | 3.968 | 1.087 | 12.213 | 1.907 | 0.000 | 0.079 | 2.447 | 0.000 | -5.800 | 0.000 | -14.439 | 0.000 |
F8 N2 APARTMENT | 2.648 | -4.108 | 0.000 | 0.000 | 3.970 | 1.087 | 12.213 | 1.907 | 0.000 | 0.079 | 2.430 | 0.000 | -5.793 | 0.000 | -14.432 | 0.000 |
F8 S1 APARTMENT | 1.300 | -6.017 | 0.000 | 0.000 | 3.786 | 1.087 | 12.213 | 9.927 | 0.000 | 0.079 | 0.046 | 0.000 | -6.130 | 0.000 | -16.290 | -0.000 |
F8 S2 APARTMENT | 1.305 | -6.002 | 0.000 | 0.000 | 3.787 | 1.087 | 12.213 | 9.926 | 0.000 | 0.079 | 0.022 | 0.000 | -6.126 | 0.000 | -16.291 | -0.000 |
F9 SW APARTMENT | 2.848 | -3.110 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 14.538 | 0.000 | 0.100 | 0.000 | 0.000 | -9.619 | 0.000 | -21.521 | -0.411 |
F9 NW APARTMENT | 5.455 | -1.479 | 0.000 | 0.000 | 3.988 | 1.087 | 12.213 | 6.716 | 0.000 | 0.101 | 0.967 | 0.000 | -9.229 | 0.000 | -19.818 | -0.001 |
F9 SE APARTMENT | 2.832 | -3.569 | 0.000 | 0.000 | 3.893 | 1.087 | 12.213 | 14.469 | 0.000 | 0.100 | 0.001 | 0.000 | -9.455 | 0.000 | -21.446 | -0.122 |
F9 NE APARTMENT | 5.465 | -2.115 | 0.000 | 0.000 | 4.008 | 1.087 | 12.213 | 6.538 | 0.000 | 0.100 | 1.325 | 0.000 | -8.934 | 0.000 | -19.687 | -0.000 |
F9 N1 APARTMENT | 3.124 | -3.725 | 0.000 | 0.000 | 3.976 | 1.087 | 12.213 | 1.898 | 0.000 | 0.082 | 2.045 | 0.000 | -5.789 | 0.000 | -14.909 | -0.000 |
F9 N2 APARTMENT | 3.127 | -3.731 | 0.000 | 0.000 | 3.978 | 1.087 | 12.213 | 1.897 | 0.000 | 0.082 | 2.036 | 0.000 | -5.783 | 0.000 | -14.903 | -0.000 |
F9 S1 APARTMENT | 1.570 | -5.466 | 0.000 | 0.000 | 3.808 | 1.087 | 12.213 | 9.902 | 0.000 | 0.082 | 0.000 | 0.000 | -6.089 | 0.000 | -16.671 | -0.435 |
F9 S2 APARTMENT | 1.574 | -5.451 | 0.000 | 0.000 | 3.809 | 1.087 | 12.213 | 9.901 | 0.000 | 0.082 | 0.000 | 0.000 | -6.084 | 0.000 | -16.673 | -0.456 |
T SW APARTMENT | 6.108 | -3.468 | 0.000 | 0.000 | 3.937 | 1.087 | 12.213 | 14.197 | 0.000 | 0.102 | 0.000 | 0.000 | -9.056 | 0.000 | -22.342 | -2.778 |
T NW APARTMENT | 8.709 | -1.194 | 0.000 | 0.000 | 4.009 | 1.087 | 12.213 | 6.413 | 0.000 | 0.102 | 0.000 | 0.000 | -8.830 | 0.000 | -20.807 | -1.702 |
T SE APARTMENT | 6.001 | -3.782 | 0.000 | 0.000 | 3.954 | 1.087 | 12.213 | 14.169 | 0.000 | 0.102 | 0.000 | 0.000 | -8.929 | 0.000 | -22.239 | -2.576 |
T NE APARTMENT | 8.657 | -1.641 | 0.000 | 0.000 | 4.027 | 1.087 | 12.213 | 6.288 | 0.000 | 0.100 | 0.000 | 0.000 | -8.586 | 0.000 | -20.665 | -1.479 |
T N1 APARTMENT | 4.593 | -2.366 | 0.000 | 0.000 | 4.003 | 1.087 | 12.213 | 1.797 | 0.000 | 0.081 | 0.000 | 0.000 | -5.528 | 0.000 | -15.605 | -0.275 |
T N2 APARTMENT | 4.610 | -2.359 | 0.000 | 0.000 | 4.004 | 1.087 | 12.213 | 1.793 | 0.000 | 0.081 | 0.000 | 0.000 | -5.520 | 0.000 | -15.610 | -0.298 |
T S1 APARTMENT | 2.593 | -4.507 | 0.000 | 0.000 | 3.885 | 1.087 | 12.213 | 9.748 | 0.000 | 0.083 | 0.000 | 0.000 | -5.768 | 0.000 | -17.246 | -2.087 |
T S2 APARTMENT | 2.606 | -4.513 | 0.000 | 0.000 | 3.886 | 1.087 | 12.213 | 9.744 | 0.000 | 0.083 | 0.000 | 0.000 | -5.761 | 0.000 | -17.253 | -2.091 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.685 | 0.000 | 0.140 | 22.672 | 0.000 | -1.991 | 0.000 | -40.946 | -0.000 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.607 | 0.000 | 0.003 | 0.000 | 0.000 | -1.201 | 0.000 | -1.372 | -15.477 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.538 | 0.000 | 0.003 | 0.000 | 0.000 | -1.250 | 0.000 | -1.673 | -15.058 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.499 | 0.000 | 0.003 | 0.000 | 0.000 | -1.272 | 0.000 | -1.887 | -14.783 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.459 | 0.000 | 0.003 | 0.000 | 0.000 | -1.303 | 0.000 | -2.159 | -30.879 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.465 | 0.000 | 0.004 | 0.000 | 0.000 | -1.270 | 0.000 | -2.158 | -14.480 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.461 | 0.000 | 0.004 | 0.000 | 0.000 | -1.256 | 0.000 | -2.240 | -14.410 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.454 | 0.000 | 0.005 | 0.000 | 0.000 | -1.250 | 0.000 | -2.326 | -14.322 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.448 | 0.000 | 0.005 | 0.000 | 0.000 | -1.247 | 0.000 | -2.410 | -14.236 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.382 | 0.000 | 0.001 | 0.000 | 0.000 | -1.213 | 0.000 | -2.666 | -22.096 |
Total Facility | 169.694 | -354.054 | 0.000 | 0.000 | 307.130 | 296.560 | 982.450 | 699.339 | 0.000 | 6.144 | 91.107 | 0.000 | -617.765 | 0.000 | -1312.395 | -268.207 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 15-SEP-16:15 | 0.00 | -1964.22 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1873.74 | 0.00 | 290.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -937.90 |
G NW APARTMENT | 30-JUN-17:30 | 0.00 | -1662.35 | 0.00 | 0.00 | 140.26 | 87.56 | 588.62 | 1850.08 | 0.00 | 257.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1261.79 |
OFFICE | 15-SEP-14:00 | 0.00 | -3086.93 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 2321.68 | 0.00 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2289.67 |
G NE APARTMENT | 30-JUN-17:45 | 0.00 | -1153.93 | 0.00 | 0.00 | 141.34 | 87.56 | 588.62 | 531.76 | 0.00 | 246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -441.85 |
G N1 APARTMENT | 30-JUN-19:00 | 0.00 | -738.79 | 0.00 | 0.00 | 140.03 | 103.77 | 547.42 | 330.74 | 0.00 | 56.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -439.72 |
G N2 APARTMENT | 30-JUN-19:00 | 0.00 | -724.47 | 0.00 | 0.00 | 139.93 | 103.77 | 547.42 | 330.97 | 0.00 | 55.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -452.94 |
G S1 APARTMENT | 31-AUG-13:30 | 0.00 | -1295.16 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1828.64 | 0.00 | 249.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1219.07 |
G S2 APARTMENT | 31-AUG-13:30 | 0.00 | -1358.37 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1826.88 | 0.00 | 249.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.10 |
F2 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2529.07 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1805.09 | 0.00 | 639.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -654.21 |
F2 NW APARTMENT | 30-JUN-17:30 | 0.00 | -2148.46 | 0.00 | 0.00 | 140.64 | 87.56 | 588.62 | 1734.87 | 0.00 | 360.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -763.31 |
F2 SE APARTMENT | 16-SEP-13:15 | 0.00 | -2430.12 | 0.00 | 0.00 | 40.71 | 12.97 | 382.60 | 2298.16 | 0.00 | 214.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -519.17 |
F2 NE APARTMENT | 30-JUN-17:30 | 0.00 | -1580.24 | 0.00 | 0.00 | 140.62 | 87.56 | 588.62 | 481.64 | 0.00 | 361.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79.93 |
F2 N1 APARTMENT | 30-JUN-19:00 | 0.00 | -1069.23 | 0.00 | 0.00 | 140.98 | 103.77 | 547.42 | 303.84 | 0.00 | 89.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -116.45 |
F2 N2 APARTMENT | 30-JUN-19:00 | 0.00 | -1056.51 | 0.00 | 0.00 | 140.94 | 103.77 | 547.42 | 304.02 | 0.00 | 88.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -128.56 |
F2 S1 APARTMENT | 16-SEP-15:45 | 0.00 | -1758.07 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 725.91 | 0.00 | 323.87 | 143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S2 APARTMENT | 16-SEP-15:45 | 0.00 | -1762.76 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 725.77 | 0.00 | 323.87 | 147.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2559.48 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1754.87 | 0.00 | 715.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -649.47 |
F3 NW APARTMENT | 30-JUN-17:30 | 0.00 | -2178.07 | 0.00 | 0.00 | 140.26 | 87.56 | 588.62 | 1680.78 | 0.00 | 404.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.28 |
F3 SE APARTMENT | 16-SEP-14:00 | 0.00 | -2302.52 | 0.00 | 0.00 | 40.42 | 12.97 | 382.60 | 1775.82 | 0.00 | 234.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144.05 |
F3 NE APARTMENT | 30-JUN-17:30 | 0.00 | -1619.15 | 0.00 | 0.00 | 140.05 | 87.56 | 588.62 | 465.37 | 0.00 | 400.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.48 |
F3 N1 APARTMENT | 30-JUN-17:45 | 0.00 | -1121.02 | 0.00 | 0.00 | 138.68 | 87.56 | 588.62 | 384.90 | 0.00 | 270.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -349.10 |
F3 N2 APARTMENT | 30-JUN-17:45 | 0.00 | -1108.30 | 0.00 | 0.00 | 138.62 | 87.56 | 588.62 | 385.06 | 0.00 | 268.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -360.45 |
F3 S1 APARTMENT | 16-SEP-15:45 | 0.00 | -1836.03 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 711.02 | 0.00 | 367.82 | 191.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S2 APARTMENT | 16-SEP-15:45 | 0.00 | -1840.26 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 710.95 | 0.00 | 368.97 | 195.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 SW APARTMENT | 15-SEP-16:15 | 0.00 | -2569.28 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1698.83 | 0.00 | 482.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.12 |
F4 NW APARTMENT | 30-JUN-17:15 | 0.00 | -2181.81 | 0.00 | 0.00 | 139.91 | 87.56 | 588.62 | 1675.76 | 0.00 | 485.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -795.97 |
F4 SE APARTMENT | 16-SEP-14:00 | 0.00 | -2293.39 | 0.00 | 0.00 | 40.34 | 12.97 | 382.60 | 1755.54 | 0.00 | 259.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157.53 |
F4 NE APARTMENT | 30-JUN-17:30 | 0.00 | -1629.94 | 0.00 | 0.00 | 139.75 | 87.56 | 588.62 | 455.46 | 0.00 | 427.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.30 |
F4 N1 APARTMENT | 30-JUN-17:45 | 0.00 | -1138.30 | 0.00 | 0.00 | 138.52 | 87.56 | 588.62 | 375.94 | 0.00 | 290.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -342.59 |
F4 N2 APARTMENT | 30-JUN-17:45 | 0.00 | -1125.78 | 0.00 | 0.00 | 138.46 | 87.56 | 588.62 | 376.08 | 0.00 | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -353.43 |
F4 S1 APARTMENT | 19-NOV-14:00 | 0.00 | -1874.74 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -743.24 |
F4 S2 APARTMENT | 19-NOV-14:00 | 0.00 | -1877.01 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -740.90 |
M SW APARTMENT | 30-JUN-16:45 | 0.00 | -2590.21 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1697.20 | 0.00 | 821.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -666.50 |
M NW APARTMENT | 30-JUN-17:15 | 0.00 | -2203.37 | 0.00 | 0.00 | 139.91 | 87.56 | 588.62 | 1649.25 | 0.00 | 519.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -781.21 |
M SE APARTMENT | 16-SEP-14:00 | 0.00 | -2320.37 | 0.00 | 0.00 | 40.35 | 12.97 | 382.60 | 1739.99 | 0.00 | 280.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -136.32 |
M NE APARTMENT | 09-AUG-15:30 | 0.00 | -1654.52 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 513.84 | 0.00 | 719.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144.21 |
M N1 APARTMENT | 30-JUN-17:45 | 0.00 | -1168.77 | 0.00 | 0.00 | 138.56 | 87.56 | 588.62 | 369.38 | 0.00 | 310.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.39 |
M N2 APARTMENT | 30-JUN-17:45 | 0.00 | -1156.44 | 0.00 | 0.00 | 138.50 | 87.56 | 588.62 | 369.48 | 0.00 | 307.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -335.68 |
M S1 APARTMENT | 19-NOV-14:00 | 0.00 | -1917.29 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -699.58 |
M S2 APARTMENT | 19-NOV-14:00 | 0.00 | -1918.78 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2174.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -698.04 |
F6 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2555.40 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1679.82 | 0.00 | 864.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -727.50 |
F6 NW APARTMENT | 30-JUN-17:15 | 0.00 | -2161.58 | 0.00 | 0.00 | 139.96 | 87.56 | 588.62 | 1630.77 | 0.00 | 548.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -834.13 |
F6 SE APARTMENT | 16-SEP-14:00 | 0.00 | -2286.88 | 0.00 | 0.00 | 40.36 | 12.97 | 382.60 | 1729.36 | 0.00 | 299.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -177.56 |
F6 NE APARTMENT | 09-AUG-15:30 | 0.00 | -1621.60 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 512.42 | 0.00 | 758.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -214.12 |
F6 N1 APARTMENT | 09-AUG-15:30 | 0.00 | -1138.91 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 312.28 | 0.00 | 648.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387.38 |
F6 N2 APARTMENT | 09-AUG-15:30 | 0.00 | -1127.40 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 312.21 | 0.00 | 644.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -394.58 |
F6 S1 APARTMENT | 19-NOV-14:00 | 0.00 | -1877.72 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -739.59 |
F6 S2 APARTMENT | 19-NOV-14:00 | 0.00 | -1879.05 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -738.21 |
F7 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2538.96 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1664.78 | 0.00 | 901.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.51 |
F7 NW APARTMENT | 30-JUN-16:45 | 0.00 | -2143.92 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1712.99 | 0.00 | 807.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1114.71 |
F7 SE APARTMENT | 16-SEP-14:00 | 0.00 | -2275.20 | 0.00 | 0.00 | 40.39 | 12.97 | 382.60 | 1719.96 | 0.00 | 315.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196.21 |
F7 NE APARTMENT | 09-AUG-15:30 | 0.00 | -1602.32 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 510.87 | 0.00 | 790.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -264.21 |
F7 N1 APARTMENT | 09-AUG-15:30 | 0.00 | -1130.23 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 311.53 | 0.00 | 679.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -425.97 |
F7 N2 APARTMENT | 09-AUG-15:30 | 0.00 | -1118.94 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 311.45 | 0.00 | 674.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -432.51 |
F7 S1 APARTMENT | 19-NOV-14:00 | 0.00 | -1849.49 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -768.00 |
F7 S2 APARTMENT | 19-NOV-14:00 | 0.00 | -1850.79 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2175.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -766.65 |
F8 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2535.27 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1651.37 | 0.00 | 932.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -786.46 |
F8 NW APARTMENT | 30-JUN-16:45 | 0.00 | -2139.99 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1698.44 | 0.00 | 834.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1131.15 |
F8 SE APARTMENT | 16-SEP-14:00 | 0.00 | -2274.36 | 0.00 | 0.00 | 40.43 | 12.97 | 382.60 | 1711.61 | 0.00 | 330.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203.66 |
F8 NE APARTMENT | 30-JUN-17:15 | 0.00 | -1594.21 | 0.00 | 0.00 | 139.11 | 87.56 | 588.62 | 425.88 | 0.00 | 549.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196.72 |
F8 N1 APARTMENT | 09-AUG-15:30 | 0.00 | -1132.96 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 310.53 | 0.00 | 706.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -449.72 |
F8 N2 APARTMENT | 09-AUG-15:30 | 0.00 | -1121.83 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 310.43 | 0.00 | 702.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -455.85 |
F8 S1 APARTMENT | 16-SEP-15:45 | 0.00 | -1843.96 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 678.80 | 0.00 | 469.33 | 130.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S2 APARTMENT | 16-SEP-15:45 | 0.00 | -1851.40 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 678.76 | 0.00 | 471.37 | 136.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SW APARTMENT | 30-JUN-16:45 | 0.00 | -2590.84 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1636.87 | 0.00 | 956.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -740.87 |
F9 NW APARTMENT | 30-JUN-16:45 | 0.00 | -2202.48 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1682.71 | 0.00 | 859.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1077.61 |
F9 SE APARTMENT | 30-JUN-16:45 | 0.00 | -2313.53 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 399.64 | 0.00 | 1019.90 | 155.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 NE APARTMENT | 09-AUG-15:30 | 0.00 | -1621.82 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 505.32 | 0.00 | 842.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -290.76 |
F9 N1 APARTMENT | 30-JUN-17:15 | 0.00 | -1191.87 | 0.00 | 0.00 | 137.93 | 87.56 | 588.62 | 309.61 | 0.00 | 455.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387.62 |
F9 N2 APARTMENT | 30-JUN-17:15 | 0.00 | -1180.53 | 0.00 | 0.00 | 137.82 | 87.56 | 588.62 | 309.51 | 0.00 | 450.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -393.91 |
F9 S1 APARTMENT | 16-SEP-15:45 | 0.00 | -1884.98 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 674.06 | 0.00 | 483.28 | 162.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S2 APARTMENT | 16-SEP-15:45 | 0.00 | -1893.42 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 674.00 | 0.00 | 485.36 | 168.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 30-JUN-16:45 | 0.00 | -3232.35 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1588.05 | 0.00 | 1007.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.58 |
T NW APARTMENT | 30-JUN-16:45 | 0.00 | -2748.16 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1630.36 | 0.00 | 848.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -468.91 |
T SE APARTMENT | 16-SEP-13:45 | 0.00 | -2907.07 | 0.00 | 0.00 | 40.24 | 12.97 | 382.60 | 1862.76 | 0.00 | 359.07 | 249.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 09-AUG-15:30 | 0.00 | -2071.57 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 469.52 | 0.00 | 850.92 | 185.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 09-AUG-15:30 | 0.00 | -1651.71 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 285.62 | 0.00 | 740.84 | 60.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 09-AUG-15:30 | 0.00 | -1652.10 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 285.74 | 0.00 | 742.90 | 58.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 06-OCT-13:15 | 0.00 | -2467.57 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2481.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -237.36 | -212.85 |
T S2 APARTMENT | 06-OCT-13:15 | 0.00 | -2471.64 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2481.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -237.36 | -208.68 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-16:45 | 0.00 | -142412.62 | 0.00 | 0.00 | 6693.84 | 11327.17 | 47312.53 | 57277.74 | 0.00 | 57934.32 | 0.00 | 0.00 | 0.00 | 0.00 | -48.70 | -38084.27 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 21-APR-11:55 | 1942.33 | 0.00 | 0.00 | 0.00 | 45.65 | 12.97 | 406.15 | 850.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1919.76 | -1337.57 |
G NW APARTMENT | 21-APR-11:55 | 1687.63 | 0.00 | 0.00 | 0.00 | 46.97 | 12.97 | 406.15 | 630.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1912.54 | -871.31 |
OFFICE | 22-DEC-05:00 | 806.65 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 47.88 | 0.00 | -655.36 | 0.00 | -862.59 | 0.00 |
G NE APARTMENT | 21-APR-11:55 | 1615.99 | 0.00 | 0.00 | 0.00 | 47.09 | 12.97 | 406.15 | 660.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1912.06 | -830.13 |
G N1 APARTMENT | 21-APR-11:55 | 1579.10 | 0.00 | 0.00 | 0.00 | 47.08 | 12.97 | 406.15 | 396.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1787.43 | -653.93 |
G N2 APARTMENT | 21-APR-11:55 | 1574.47 | 0.00 | 0.00 | 0.00 | 47.09 | 12.97 | 406.15 | 396.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1787.42 | -649.36 |
G S1 APARTMENT | 21-APR-11:55 | 1822.55 | 0.00 | 0.00 | 0.00 | 45.36 | 12.97 | 406.15 | 621.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1798.75 | -1109.68 |
G S2 APARTMENT | 21-APR-11:55 | 1531.54 | 0.00 | 0.00 | 0.00 | 44.91 | 12.97 | 406.15 | 616.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1809.77 | -802.30 |
F2 SW APARTMENT | 21-APR-12:00 | 1615.85 | 0.00 | 0.00 | 0.00 | 44.10 | 12.97 | 406.15 | 713.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2542.84 | -250.04 |
F2 NW APARTMENT | 21-APR-11:55 | 2373.46 | 0.00 | 0.00 | 0.00 | 46.07 | 12.97 | 406.15 | 543.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2542.16 | -839.60 |
F2 SE APARTMENT | 21-APR-12:00 | 1687.37 | 0.00 | 0.00 | 0.00 | 43.15 | 12.97 | 406.15 | 733.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2544.90 | -337.96 |
F2 NE APARTMENT | 21-APR-11:55 | 2322.71 | 0.00 | 0.00 | 0.00 | 46.18 | 12.97 | 406.15 | 582.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2540.99 | -829.08 |
F2 N1 APARTMENT | 21-APR-11:55 | 2423.50 | 0.00 | 0.00 | 0.00 | 45.91 | 12.97 | 406.15 | 344.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2361.00 | -872.25 |
F2 N2 APARTMENT | 21-APR-11:55 | 2412.48 | 0.00 | 0.00 | 0.00 | 45.92 | 12.97 | 406.15 | 344.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2360.09 | -862.29 |
F2 S1 APARTMENT | 21-APR-12:00 | 1760.35 | 0.00 | 0.00 | 0.00 | 43.49 | 12.97 | 406.15 | 528.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2362.38 | -389.13 |
F2 S2 APARTMENT | 21-APR-12:00 | 1779.76 | 0.00 | 0.00 | 0.00 | 43.34 | 12.97 | 406.15 | 526.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2362.65 | -406.38 |
F3 SW APARTMENT | 21-APR-11:55 | 1848.08 | 0.00 | 0.00 | 0.00 | 43.98 | 12.97 | 406.15 | 663.21 | 0.00 | 0.00 | 6.20 | 0.00 | 0.00 | 0.00 | -2980.60 | 0.00 |
F3 NW APARTMENT | 21-APR-11:55 | 2659.78 | 0.00 | 0.00 | 0.00 | 46.10 | 12.97 | 406.15 | 511.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2944.31 | -692.45 |
F3 SE APARTMENT | 21-APR-12:00 | 1722.46 | 0.00 | 0.00 | 0.00 | 43.81 | 12.97 | 406.15 | 701.58 | 0.00 | 0.00 | 57.59 | 0.00 | 0.00 | 0.00 | -2944.55 | 0.00 |
F3 NE APARTMENT | 21-APR-11:55 | 2618.07 | 0.00 | 0.00 | 0.00 | 46.19 | 12.97 | 406.15 | 553.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2943.26 | -693.92 |
F3 N1 APARTMENT | 21-APR-11:55 | 2502.14 | 0.00 | 0.00 | 0.00 | 45.68 | 12.97 | 406.15 | 325.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2688.35 | -604.15 |
F3 N2 APARTMENT | 21-APR-11:55 | 2484.87 | 0.00 | 0.00 | 0.00 | 45.69 | 12.97 | 406.15 | 325.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2686.21 | -589.14 |
F3 S1 APARTMENT | 21-APR-12:00 | 1877.84 | 0.00 | 0.00 | 0.00 | 43.06 | 12.97 | 406.15 | 491.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2731.12 | -100.05 |
F3 S2 APARTMENT | 21-APR-12:00 | 1884.52 | 0.00 | 0.00 | 0.00 | 43.01 | 12.97 | 406.15 | 490.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2731.21 | -106.04 |
F4 SW APARTMENT | 24-JUN-09:40 | 1720.92 | 0.00 | 0.00 | 0.00 | 44.93 | 12.97 | 406.15 | 604.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2370.44 | -418.88 |
F4 NW APARTMENT | 03-OCT-09:10 | 2339.47 | 0.00 | 0.00 | 0.00 | 46.75 | 12.97 | 406.15 | 94.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2702.03 | -198.23 |
F4 SE APARTMENT | 17-MAY-19:10 | 1764.37 | 0.00 | 0.00 | 0.00 | 155.54 | 103.77 | 523.87 | 0.00 | 0.00 | 0.00 | 12.44 | 0.00 | -423.79 | 0.00 | -2136.20 | 0.00 |
F4 NE APARTMENT | 03-OCT-09:10 | 2303.86 | 0.00 | 0.00 | 0.00 | 45.08 | 12.97 | 406.15 | 1158.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2711.23 | -1215.06 |
F4 N1 APARTMENT | 03-OCT-09:10 | 2503.77 | 0.00 | 0.00 | 0.00 | 45.76 | 12.97 | 406.15 | 46.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2491.95 | -523.29 |
F4 N2 APARTMENT | 03-OCT-09:10 | 2487.13 | 0.00 | 0.00 | 0.00 | 45.75 | 12.97 | 406.15 | 46.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2489.63 | -508.81 |
F4 S1 APARTMENT | 21-MAY-10:15 | 1686.09 | 0.00 | 0.00 | 0.00 | 43.57 | 12.97 | 412.03 | 517.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1813.15 | -859.48 |
F4 S2 APARTMENT | 21-MAY-10:15 | 1682.48 | 0.00 | 0.00 | 0.00 | 43.56 | 12.97 | 412.03 | 517.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1813.18 | -855.78 |
M SW APARTMENT | 24-JUN-09:40 | 2274.36 | 0.00 | 0.00 | 0.00 | 45.33 | 12.97 | 406.15 | 591.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2528.87 | -801.62 |
M NW APARTMENT | 30-MAY-14:10 | 2479.73 | 0.00 | 0.00 | 0.00 | 45.95 | 22.70 | 400.26 | 1055.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2841.35 | -1162.30 |
M SE APARTMENT | 30-MAY-14:10 | 2204.52 | 0.00 | 0.00 | 0.00 | 45.26 | 22.70 | 400.26 | 606.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2853.03 | -426.68 |
M NE APARTMENT | 03-OCT-09:10 | 2782.93 | 0.00 | 0.00 | 0.00 | 45.30 | 12.97 | 406.15 | 1140.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2914.75 | -1473.18 |
M N1 APARTMENT | 03-OCT-09:10 | 2545.64 | 0.00 | 0.00 | 0.00 | 45.87 | 12.97 | 406.15 | 41.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2670.75 | -381.54 |
M N2 APARTMENT | 03-OCT-09:10 | 2529.21 | 0.00 | 0.00 | 0.00 | 45.86 | 12.97 | 406.15 | 41.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2668.22 | -367.44 |
M S1 APARTMENT | 03-OCT-09:15 | 2000.49 | 0.00 | 0.00 | 0.00 | 42.04 | 12.97 | 406.15 | 1230.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2694.33 | -998.03 |
M S2 APARTMENT | 30-MAY-14:10 | 2012.13 | 0.00 | 0.00 | 0.00 | 44.93 | 22.70 | 400.26 | 495.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2646.15 | -329.51 |
F6 SW APARTMENT | 17-MAY-19:10 | 2524.21 | 0.00 | 0.00 | 0.00 | 156.80 | 103.77 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -419.92 | 0.00 | -2404.50 | -484.23 |
F6 NW APARTMENT | 30-MAY-14:10 | 2556.06 | 0.00 | 0.00 | 0.00 | 46.29 | 22.70 | 400.26 | 1041.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3020.63 | -1046.32 |
F6 SE APARTMENT | 30-MAY-14:10 | 2718.34 | 0.00 | 0.00 | 0.00 | 45.63 | 22.70 | 400.26 | 598.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3021.82 | -763.75 |
F6 NE APARTMENT | 03-OCT-09:10 | 2816.51 | 0.00 | 0.00 | 0.00 | 45.73 | 12.97 | 406.15 | 1131.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3099.55 | -1313.58 |
F6 N1 APARTMENT | 03-OCT-09:10 | 2506.04 | 0.00 | 0.00 | 0.00 | 46.29 | 12.97 | 406.15 | 41.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2827.55 | -185.83 |
F6 N2 APARTMENT | 03-OCT-09:10 | 2489.93 | 0.00 | 0.00 | 0.00 | 46.28 | 12.97 | 406.15 | 41.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2824.81 | -172.22 |
F6 S1 APARTMENT | 30-MAY-14:10 | 2585.85 | 0.00 | 0.00 | 0.00 | 45.25 | 22.70 | 400.26 | 487.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2799.81 | -741.57 |
F6 S2 APARTMENT | 30-MAY-14:10 | 2597.73 | 0.00 | 0.00 | 0.00 | 45.26 | 22.70 | 400.26 | 487.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2799.57 | -753.88 |
F7 SW APARTMENT | 03-OCT-09:10 | 3000.33 | 0.00 | 0.00 | 0.00 | 45.15 | 12.97 | 406.15 | 1236.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3270.32 | -1431.13 |
F7 NW APARTMENT | 03-OCT-10:00 | 2718.67 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 406.15 | 184.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3347.19 | -22.63 |
F7 SE APARTMENT | 30-MAY-14:10 | 2799.22 | 0.00 | 0.00 | 0.00 | 45.90 | 22.70 | 400.26 | 590.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3183.69 | -675.08 |
F7 NE APARTMENT | 03-OCT-09:10 | 2872.62 | 0.00 | 0.00 | 0.00 | 46.04 | 12.97 | 406.15 | 1123.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3266.48 | -1194.77 |
F7 N1 APARTMENT | 24-JUN-09:55 | 2497.99 | 0.00 | 0.00 | 0.00 | 46.15 | 12.97 | 406.15 | 302.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2602.34 | -663.65 |
F7 N2 APARTMENT | 24-JUN-09:55 | 2482.33 | 0.00 | 0.00 | 0.00 | 46.13 | 12.97 | 406.15 | 302.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2599.16 | -650.78 |
F7 S1 APARTMENT | 30-MAY-14:10 | 2919.18 | 0.00 | 0.00 | 0.00 | 45.52 | 22.70 | 400.26 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2942.85 | -925.24 |
F7 S2 APARTMENT | 30-MAY-14:10 | 2918.99 | 0.00 | 0.00 | 0.00 | 45.53 | 22.70 | 400.26 | 480.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2942.85 | -925.17 |
F8 SW APARTMENT | 03-OCT-09:10 | 3050.95 | 0.00 | 0.00 | 0.00 | 45.56 | 12.97 | 406.15 | 1226.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3422.95 | -1319.52 |
F8 NW APARTMENT | 03-OCT-10:00 | 2912.82 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 406.15 | 180.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3509.05 | -50.82 |
F8 SE APARTMENT | 30-MAY-14:10 | 2882.57 | 0.00 | 0.00 | 0.00 | 46.09 | 22.70 | 400.26 | 582.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3332.43 | -602.09 |
F8 NE APARTMENT | 22-APR-14:35 | 3067.77 | 0.00 | 0.00 | 0.00 | 47.42 | 22.70 | 400.26 | 195.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3704.44 | -28.75 |
F8 N1 APARTMENT | 20-NOV-19:00 | 2507.96 | 0.00 | 0.00 | 0.00 | 165.01 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 659.01 | 0.00 | -202.96 | 0.00 | -3805.21 | 0.00 |
F8 N2 APARTMENT | 20-NOV-19:00 | 2493.04 | 0.00 | 0.00 | 0.00 | 165.01 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 666.01 | 0.00 | -202.78 | 0.00 | -3797.46 | 0.00 |
F8 S1 APARTMENT | 30-MAY-14:10 | 2991.71 | 0.00 | 0.00 | 0.00 | 45.72 | 22.70 | 400.26 | 474.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3079.19 | -855.43 |
F8 S2 APARTMENT | 30-MAY-14:10 | 2992.14 | 0.00 | 0.00 | 0.00 | 45.73 | 22.70 | 400.26 | 474.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3079.20 | -855.94 |
F9 SW APARTMENT | 03-OCT-09:10 | 3096.50 | 0.00 | 0.00 | 0.00 | 46.00 | 12.97 | 406.15 | 1221.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3564.81 | -1217.95 |
F9 NW APARTMENT | 03-OCT-10:00 | 3120.86 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 406.15 | 178.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3659.51 | -106.86 |
F9 SE APARTMENT | 30-MAY-14:10 | 2977.14 | 0.00 | 0.00 | 0.00 | 46.16 | 22.70 | 400.26 | 573.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3470.97 | -549.04 |
F9 NE APARTMENT | 22-APR-14:35 | 3250.42 | 0.00 | 0.00 | 0.00 | 47.42 | 22.70 | 400.26 | 191.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3861.27 | -50.98 |
F9 N1 APARTMENT | 04-MAR-12:40 | 2748.11 | 0.00 | 0.00 | 0.00 | 45.12 | 12.97 | 406.15 | 246.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2499.39 | -959.28 |
F9 N2 APARTMENT | 04-MAR-12:40 | 2771.23 | 0.00 | 0.00 | 0.00 | 45.15 | 12.97 | 406.15 | 246.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2498.78 | -983.43 |
F9 S1 APARTMENT | 30-MAY-14:10 | 3071.16 | 0.00 | 0.00 | 0.00 | 45.86 | 22.70 | 400.26 | 468.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3206.15 | -802.00 |
F9 S2 APARTMENT | 30-MAY-14:10 | 3072.73 | 0.00 | 0.00 | 0.00 | 45.86 | 22.70 | 400.26 | 468.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3206.17 | -803.54 |
T SW APARTMENT | 03-OCT-09:25 | 3294.01 | 0.00 | 0.00 | 0.00 | 45.86 | 12.97 | 406.15 | 1313.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3740.43 | -1332.44 |
T NW APARTMENT | 20-NOV-19:00 | 3525.56 | 0.00 | 0.00 | 0.00 | 165.01 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 407.93 | 0.00 | -321.42 | 0.00 | -4453.26 | 0.00 |
T SE APARTMENT | 11-SEP-18:15 | 3092.72 | 0.00 | 0.00 | 0.00 | 165.01 | 103.77 | 547.42 | 0.00 | 0.00 | 0.00 | 593.11 | 0.00 | -339.05 | 0.00 | -4162.98 | 0.00 |
T NE APARTMENT | 20-NOV-19:00 | 3604.16 | 0.00 | 0.00 | 0.00 | 165.01 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 324.48 | 0.00 | -316.51 | 0.00 | -4453.32 | 0.00 |
T N1 APARTMENT | 17-MAY-19:25 | 3326.26 | 0.00 | 0.00 | 0.00 | 156.27 | 103.77 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -250.69 | 0.00 | -2824.20 | -1035.27 |
T N2 APARTMENT | 17-MAY-19:25 | 3322.62 | 0.00 | 0.00 | 0.00 | 156.30 | 103.77 | 523.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -250.52 | 0.00 | -2824.19 | -1031.85 |
T S1 APARTMENT | 03-OCT-09:25 | 3264.07 | 0.00 | 0.00 | 0.00 | 44.06 | 12.97 | 406.15 | 1272.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3462.99 | -1536.84 |
T S2 APARTMENT | 03-OCT-09:25 | 3174.65 | 0.00 | 0.00 | 0.00 | 43.94 | 12.97 | 406.15 | 1270.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3466.24 | -1442.22 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-MAY-14:10 | 141050.79 | 0.00 | 0.00 | 0.00 | 3730.31 | 9873.49 | 32370.09 | 49856.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -195602.30 | -41278.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Sec1.1A-General InformationData | |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 119.00 |
Number of hours cooling loads not met | 12.75 |
Number of hours not met | 131.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 11327.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 55.40 | 0.00 | 134.51 | 118213.39 | 0.00 | 0.00 |
Space Cooling | 45.38 | 47332.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.45 | 1332.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1.75 | 1520.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 473.52 | 15015.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1093.79 | 68877.58 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 57142.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 2247.28 | 1228.31 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 2247.28 |
Natural Gas | 0.00 | 1228.31 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 3475.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 7.07 |
Space Cooling | 5.79 |
Fans-Interior | 60.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 30.51 |
Subtotal | 286.77 |
Natural Gas [MJ/m2] | |
Space Heating | 17.17 |
Service Water Heating | 139.58 |
Miscellaneous | -0.00 |
Subtotal | 156.74 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.53 |
Space Heating | 5.46 |
Space Cooling | 1.31 |
Fans-Interior | 13.62 |
Service Water Heating | 31.47 |
Receptacle Equipment | 32.72 |
Miscellaneous | 6.88 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.176890 |
G NW APARTMENT DIRECT AIR | 0.146906 |
OFFICE DIRECT AIR | 0.288783 |
G NE APARTMENT DIRECT AIR | 0.104285 |
G N1 APARTMENT DIRECT AIR | 0.064387 |
G N2 APARTMENT DIRECT AIR | 0.063051 |
G S1 APARTMENT DIRECT AIR | 0.114553 |
G S2 APARTMENT DIRECT AIR | 0.120732 |
F2 SW APARTMENT DIRECT AIR | 0.226007 |
F2 NW APARTMENT DIRECT AIR | 0.188896 |
F2 SE APARTMENT DIRECT AIR | 0.222403 |
F2 NE APARTMENT DIRECT AIR | 0.141186 |
F2 N1 APARTMENT DIRECT AIR | 0.093676 |
F2 N2 APARTMENT DIRECT AIR | 0.092521 |
F2 S1 APARTMENT DIRECT AIR | 0.152813 |
F2 S2 APARTMENT DIRECT AIR | 0.155063 |
F3 SW APARTMENT DIRECT AIR | 0.226977 |
F3 NW APARTMENT DIRECT AIR | 0.190759 |
F3 SE APARTMENT DIRECT AIR | 0.204332 |
F3 NE APARTMENT DIRECT AIR | 0.143826 |
F3 N1 APARTMENT DIRECT AIR | 0.097757 |
F3 N2 APARTMENT DIRECT AIR | 0.096616 |
F3 S1 APARTMENT DIRECT AIR | 0.156377 |
F3 S2 APARTMENT DIRECT AIR | 0.157326 |
F4 SW APARTMENT DIRECT AIR | 0.226718 |
F4 NW APARTMENT DIRECT AIR | 0.190712 |
F4 SE APARTMENT DIRECT AIR | 0.202908 |
F4 NE APARTMENT DIRECT AIR | 0.143858 |
F4 N1 APARTMENT DIRECT AIR | 0.099020 |
F4 N2 APARTMENT DIRECT AIR | 0.097895 |
F4 S1 APARTMENT DIRECT AIR | 0.157223 |
F4 S2 APARTMENT DIRECT AIR | 0.157973 |
M SW APARTMENT DIRECT AIR | 0.228297 |
M NW APARTMENT DIRECT AIR | 0.192443 |
M SE APARTMENT DIRECT AIR | 0.204988 |
M NE APARTMENT DIRECT AIR | 0.145606 |
M N1 APARTMENT DIRECT AIR | 0.101613 |
M N2 APARTMENT DIRECT AIR | 0.100501 |
M S1 APARTMENT DIRECT AIR | 0.159562 |
M S2 APARTMENT DIRECT AIR | 0.160283 |
F6 SW APARTMENT DIRECT AIR | 0.224629 |
F6 NW APARTMENT DIRECT AIR | 0.188774 |
F6 SE APARTMENT DIRECT AIR | 0.201934 |
F6 NE APARTMENT DIRECT AIR | 0.142039 |
F6 N1 APARTMENT DIRECT AIR | 0.098978 |
F6 N2 APARTMENT DIRECT AIR | 0.097887 |
F6 S1 APARTMENT DIRECT AIR | 0.156567 |
F6 S2 APARTMENT DIRECT AIR | 0.157285 |
F7 SW APARTMENT DIRECT AIR | 0.223068 |
F7 NW APARTMENT DIRECT AIR | 0.187197 |
F7 SE APARTMENT DIRECT AIR | 0.200845 |
F7 NE APARTMENT DIRECT AIR | 0.140503 |
F7 N1 APARTMENT DIRECT AIR | 0.098182 |
F7 N2 APARTMENT DIRECT AIR | 0.097107 |
F7 S1 APARTMENT DIRECT AIR | 0.155491 |
F7 S2 APARTMENT DIRECT AIR | 0.156208 |
F8 SW APARTMENT DIRECT AIR | 0.222598 |
F8 NW APARTMENT DIRECT AIR | 0.186737 |
F8 SE APARTMENT DIRECT AIR | 0.200761 |
F8 NE APARTMENT DIRECT AIR | 0.140010 |
F8 N1 APARTMENT DIRECT AIR | 0.098397 |
F8 N2 APARTMENT DIRECT AIR | 0.097336 |
F8 S1 APARTMENT DIRECT AIR | 0.155432 |
F8 S2 APARTMENT DIRECT AIR | 0.156151 |
F9 SW APARTMENT DIRECT AIR | 0.227702 |
F9 NW APARTMENT DIRECT AIR | 0.192041 |
F9 SE APARTMENT DIRECT AIR | 0.204897 |
F9 NE APARTMENT DIRECT AIR | 0.141114 |
F9 N1 APARTMENT DIRECT AIR | 0.103573 |
F9 N2 APARTMENT DIRECT AIR | 0.102515 |
F9 S1 APARTMENT DIRECT AIR | 0.158850 |
F9 S2 APARTMENT DIRECT AIR | 0.159653 |
T SW APARTMENT DIRECT AIR | 0.283258 |
T NW APARTMENT DIRECT AIR | 0.236387 |
T SE APARTMENT DIRECT AIR | 0.256494 |
T NE APARTMENT DIRECT AIR | 0.177740 |
T N1 APARTMENT DIRECT AIR | 0.138861 |
T N2 APARTMENT DIRECT AIR | 0.138947 |
T S1 APARTMENT DIRECT AIR | 0.216094 |
T S2 APARTMENT DIRECT AIR | 0.216854 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.176890 |
AIRLOOP G NW MAIN BRANCH | 0.146906 |
AIRLOOP OFFICE MAIN BRANCH | 0.288783 |
AIRLOOP G NE MAIN BRANCH | 0.104285 |
AIRLOOP G N1 MAIN BRANCH | 0.064387 |
AIRLOOP G N2 MAIN BRANCH | 0.063051 |
AIRLOOP G S1 MAIN BRANCH | 0.114553 |
AIRLOOP G S2 MAIN BRANCH | 0.120732 |
AIRLOOP F2 SW MAIN BRANCH | 0.226007 |
AIRLOOP F2 NW MAIN BRANCH | 0.188896 |
AIRLOOP F2 SE MAIN BRANCH | 0.222403 |
AIRLOOP F2 NE MAIN BRANCH | 0.141186 |
AIRLOOP F2 N1 MAIN BRANCH | 0.093676 |
AIRLOOP F2 N2 MAIN BRANCH | 0.092521 |
AIRLOOP F2 S1 MAIN BRANCH | 0.152813 |
AIRLOOP F2 S2 MAIN BRANCH | 0.155063 |
AIRLOOP F3 SW MAIN BRANCH | 0.226977 |
AIRLOOP F3 NW MAIN BRANCH | 0.190759 |
AIRLOOP F3 SE MAIN BRANCH | 0.204332 |
AIRLOOP F3 NE MAIN BRANCH | 0.143826 |
AIRLOOP F3 N1 MAIN BRANCH | 0.097757 |
AIRLOOP F3 N2 MAIN BRANCH | 0.096616 |
AIRLOOP F3 S1 MAIN BRANCH | 0.156377 |
AIRLOOP F3 S2 MAIN BRANCH | 0.157326 |
AIRLOOP F4 SW MAIN BRANCH | 0.226718 |
AIRLOOP F4 NW MAIN BRANCH | 0.190712 |
AIRLOOP F4 SE MAIN BRANCH | 0.202908 |
AIRLOOP F4 NE MAIN BRANCH | 0.143858 |
AIRLOOP F4 N1 MAIN BRANCH | 0.099020 |
AIRLOOP F4 N2 MAIN BRANCH | 0.097895 |
AIRLOOP F4 S1 MAIN BRANCH | 0.157223 |
AIRLOOP F4 S2 MAIN BRANCH | 0.157973 |
AIRLOOP M SW MAIN BRANCH | 0.228297 |
AIRLOOP M NW MAIN BRANCH | 0.192443 |
AIRLOOP M SE MAIN BRANCH | 0.204988 |
AIRLOOP M NE MAIN BRANCH | 0.145606 |
AIRLOOP M N1 MAIN BRANCH | 0.101613 |
AIRLOOP M N2 MAIN BRANCH | 0.100501 |
AIRLOOP M S1 MAIN BRANCH | 0.159562 |
AIRLOOP M S2 MAIN BRANCH | 0.160283 |
AIRLOOP F6 SW MAIN BRANCH | 0.224629 |
AIRLOOP F6 NW MAIN BRANCH | 0.188774 |
AIRLOOP F6 SE MAIN BRANCH | 0.201934 |
AIRLOOP F6 NE MAIN BRANCH | 0.142039 |
AIRLOOP F6 N1 MAIN BRANCH | 0.098978 |
AIRLOOP F6 N2 MAIN BRANCH | 0.097887 |
AIRLOOP F6 S1 MAIN BRANCH | 0.156567 |
AIRLOOP F6 S2 MAIN BRANCH | 0.157285 |
AIRLOOP F7 SW MAIN BRANCH | 0.223068 |
AIRLOOP F7 NW MAIN BRANCH | 0.187197 |
AIRLOOP F7 SE MAIN BRANCH | 0.200845 |
AIRLOOP F7 NE MAIN BRANCH | 0.140503 |
AIRLOOP F7 N1 MAIN BRANCH | 0.098182 |
AIRLOOP F7 N2 MAIN BRANCH | 0.097107 |
AIRLOOP F7 S1 MAIN BRANCH | 0.155491 |
AIRLOOP F7 S2 MAIN BRANCH | 0.156208 |
AIRLOOP F8 SW MAIN BRANCH | 0.222598 |
AIRLOOP F8 NW MAIN BRANCH | 0.186737 |
AIRLOOP F8 SE MAIN BRANCH | 0.200761 |
AIRLOOP F8 NE MAIN BRANCH | 0.140010 |
AIRLOOP F8 N1 MAIN BRANCH | 0.098397 |
AIRLOOP F8 N2 MAIN BRANCH | 0.097336 |
AIRLOOP F8 S1 MAIN BRANCH | 0.155432 |
AIRLOOP F8 S2 MAIN BRANCH | 0.156151 |
AIRLOOP F9 SW MAIN BRANCH | 0.227702 |
AIRLOOP F9 NW MAIN BRANCH | 0.192041 |
AIRLOOP F9 SE MAIN BRANCH | 0.204897 |
AIRLOOP F9 NE MAIN BRANCH | 0.141114 |
AIRLOOP F9 N1 MAIN BRANCH | 0.103573 |
AIRLOOP F9 N2 MAIN BRANCH | 0.102515 |
AIRLOOP F9 S1 MAIN BRANCH | 0.158850 |
AIRLOOP F9 S2 MAIN BRANCH | 0.159653 |
AIRLOOP T SW MAIN BRANCH | 0.283258 |
AIRLOOP T NW MAIN BRANCH | 0.236387 |
AIRLOOP T SE MAIN BRANCH | 0.256494 |
AIRLOOP T NE MAIN BRANCH | 0.177740 |
AIRLOOP T N1 MAIN BRANCH | 0.138861 |
AIRLOOP T N2 MAIN BRANCH | 0.138947 |
AIRLOOP T S1 MAIN BRANCH | 0.216094 |
AIRLOOP T S2 MAIN BRANCH | 0.216854 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.176890 |
AIRLOOP G NW | 0.146906 |
AIRLOOP OFFICE | 0.288783 |
AIRLOOP G NE | 0.104285 |
AIRLOOP G N1 | 0.064387 |
AIRLOOP G N2 | 0.063051 |
AIRLOOP G S1 | 0.114553 |
AIRLOOP G S2 | 0.120732 |
AIRLOOP F2 SW | 0.226007 |
AIRLOOP F2 NW | 0.188896 |
AIRLOOP F2 SE | 0.222403 |
AIRLOOP F2 NE | 0.141186 |
AIRLOOP F2 N1 | 0.093676 |
AIRLOOP F2 N2 | 0.092521 |
AIRLOOP F2 S1 | 0.152813 |
AIRLOOP F2 S2 | 0.155063 |
AIRLOOP F3 SW | 0.226977 |
AIRLOOP F3 NW | 0.190759 |
AIRLOOP F3 SE | 0.204332 |
AIRLOOP F3 NE | 0.143826 |
AIRLOOP F3 N1 | 0.097757 |
AIRLOOP F3 N2 | 0.096616 |
AIRLOOP F3 S1 | 0.156377 |
AIRLOOP F3 S2 | 0.157326 |
AIRLOOP F4 SW | 0.226718 |
AIRLOOP F4 NW | 0.190712 |
AIRLOOP F4 SE | 0.202908 |
AIRLOOP F4 NE | 0.143858 |
AIRLOOP F4 N1 | 0.099020 |
AIRLOOP F4 N2 | 0.097895 |
AIRLOOP F4 S1 | 0.157223 |
AIRLOOP F4 S2 | 0.157973 |
AIRLOOP M SW | 0.228297 |
AIRLOOP M NW | 0.192443 |
AIRLOOP M SE | 0.204988 |
AIRLOOP M NE | 0.145606 |
AIRLOOP M N1 | 0.101613 |
AIRLOOP M N2 | 0.100501 |
AIRLOOP M S1 | 0.159562 |
AIRLOOP M S2 | 0.160283 |
AIRLOOP F6 SW | 0.224629 |
AIRLOOP F6 NW | 0.188774 |
AIRLOOP F6 SE | 0.201934 |
AIRLOOP F6 NE | 0.142039 |
AIRLOOP F6 N1 | 0.098978 |
AIRLOOP F6 N2 | 0.097887 |
AIRLOOP F6 S1 | 0.156567 |
AIRLOOP F6 S2 | 0.157285 |
AIRLOOP F7 SW | 0.223068 |
AIRLOOP F7 NW | 0.187197 |
AIRLOOP F7 SE | 0.200845 |
AIRLOOP F7 NE | 0.140503 |
AIRLOOP F7 N1 | 0.098182 |
AIRLOOP F7 N2 | 0.097107 |
AIRLOOP F7 S1 | 0.155491 |
AIRLOOP F7 S2 | 0.156208 |
AIRLOOP F8 SW | 0.222598 |
AIRLOOP F8 NW | 0.186737 |
AIRLOOP F8 SE | 0.200761 |
AIRLOOP F8 NE | 0.140010 |
AIRLOOP F8 N1 | 0.098397 |
AIRLOOP F8 N2 | 0.097336 |
AIRLOOP F8 S1 | 0.155432 |
AIRLOOP F8 S2 | 0.156151 |
AIRLOOP F9 SW | 0.227702 |
AIRLOOP F9 NW | 0.192041 |
AIRLOOP F9 SE | 0.204897 |
AIRLOOP F9 NE | 0.141114 |
AIRLOOP F9 N1 | 0.103573 |
AIRLOOP F9 N2 | 0.102515 |
AIRLOOP F9 S1 | 0.158850 |
AIRLOOP F9 S2 | 0.159653 |
AIRLOOP T SW | 0.283258 |
AIRLOOP T NW | 0.236387 |
AIRLOOP T SE | 0.256494 |
AIRLOOP T NE | 0.177740 |
AIRLOOP T N1 | 0.138861 |
AIRLOOP T N2 | 0.138947 |
AIRLOOP T S1 | 0.216094 |
AIRLOOP T S2 | 0.216854 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.176890 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.146906 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.288783 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.104285 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.064387 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.063051 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.114553 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.120732 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.226007 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.188896 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.222403 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.141186 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.093676 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.092521 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.152813 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.155063 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.226977 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.190759 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.204332 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.143826 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.097757 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.096616 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.156377 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.157326 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.226718 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.190712 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.202908 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.143858 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.099020 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.097895 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.157223 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.157973 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.228297 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.192443 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.204988 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.145606 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.101613 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.100501 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.159562 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.160283 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.224629 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.188774 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.201934 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.142039 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.098978 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.097887 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.156567 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.157285 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.223068 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.187197 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.200845 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.140503 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.098182 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.097107 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.155491 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.156208 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.222598 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.186737 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.200761 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.140010 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.098397 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.097336 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.155432 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.156151 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.227702 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.192041 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.204897 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.141114 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.103573 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.102515 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.158850 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.159653 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.283258 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.236387 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.256494 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.177740 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.138861 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.138947 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.216094 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.216854 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.176890 | 2563.84 | 1990.97 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.146906 | 2112.46 | 1645.03 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.288783 | 4156.08 | 3239.54 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.104285 | 1477.02 | 1157.70 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.064387 | 931.68 | 723.93 | 0.000020 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.063051 | 912.56 | 709.13 | 0.000020 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.114553 | 1700.88 | 1308.59 | 0.000037 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.120732 | 1787.39 | 1376.63 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.226007 | 3237.00 | 2525.49 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.188896 | 2695.86 | 2105.63 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.222403 | 3200.43 | 2492.51 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.141186 | 1984.64 | 1561.08 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.093676 | 1344.49 | 1046.79 | 0.000029 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.092521 | 1328.10 | 1034.03 | 0.000029 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.152813 | 2236.36 | 1730.31 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.155063 | 2267.91 | 1755.08 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.226977 | 3246.91 | 2535.19 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.190759 | 2718.42 | 2125.19 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.204332 | 2943.71 | 2292.76 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.143826 | 2017.99 | 1589.16 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.097757 | 1400.14 | 1091.27 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.096616 | 1383.98 | 1078.68 | 0.000030 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.156377 | 2284.07 | 1768.96 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.157326 | 2297.37 | 1779.40 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.226718 | 3240.61 | 2531.64 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.190712 | 2715.17 | 2124.00 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.202908 | 2921.19 | 2276.42 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.143858 | 2024.77 | 1593.31 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.099020 | 1416.45 | 1104.80 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.097895 | 1400.53 | 1092.39 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.157223 | 2294.27 | 1777.83 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.157973 | 2304.78 | 1786.09 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.228297 | 3260.58 | 2548.45 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.192443 | 2737.36 | 2142.49 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.204988 | 2948.26 | 2298.77 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.145606 | 2047.31 | 1612.02 | 0.000045 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.101613 | 1451.87 | 1133.08 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.100501 | 1436.15 | 1120.82 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.159562 | 2325.72 | 1803.23 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.160283 | 2335.83 | 1811.16 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.224629 | 3216.33 | 2511.89 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.188774 | 2684.22 | 2101.68 | 0.000059 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.201934 | 2903.81 | 2264.73 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.142039 | 1995.95 | 1572.43 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.098978 | 1413.58 | 1103.74 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.097887 | 1398.17 | 1091.71 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.156567 | 2282.63 | 1769.97 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.157285 | 2292.69 | 1777.86 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.223068 | 3192.94 | 2494.32 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.187197 | 2660.65 | 2083.95 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.200845 | 2887.09 | 2252.36 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.140503 | 1973.20 | 1555.22 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.098182 | 1401.45 | 1094.73 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.097107 | 1386.26 | 1082.87 | 0.000030 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.155491 | 2266.59 | 1757.86 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.156208 | 2276.63 | 1765.76 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.222598 | 3185.00 | 2488.79 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.186737 | 2652.90 | 2078.54 | 0.000058 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.200761 | 2884.61 | 2251.09 | 0.000063 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.140010 | 1965.16 | 1549.50 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.098397 | 1403.70 | 1096.89 | 0.000031 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.097336 | 1388.72 | 1085.19 | 0.000030 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.155432 | 2264.91 | 1756.99 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.156151 | 2274.97 | 1764.90 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.227702 | 3246.27 | 2540.34 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.192041 | 2726.00 | 2136.57 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.204897 | 2944.46 | 2297.78 | 0.000064 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.141114 | 1988.83 | 1565.90 | 0.000043 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.103573 | 1476.09 | 1153.79 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.102515 | 1461.16 | 1142.13 | 0.000032 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.158850 | 2311.99 | 1794.40 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.159653 | 2323.24 | 1803.24 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.283258 | 4035.11 | 3156.96 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.236387 | 3358.57 | 2631.20 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.256494 | 3661.84 | 2863.28 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.177740 | 2508.57 | 1972.57 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.138861 | 2034.57 | 1575.70 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.138947 | 2035.77 | 1576.65 | 0.000044 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.216094 | 3113.02 | 2424.04 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.216854 | 3123.67 | 2432.40 | 0.000068 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.176890 | 0.176890 | 0.176890 | 0.176890 | 2563.84 | 2563.84 | 1666.56 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.146906 | 0.146906 | 0.146906 | 0.146906 | 2112.46 | 2112.46 | 1672.45 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.288783 | 0.288783 | 0.288783 | 0.288783 | 4156.08 | 4156.08 | 2242.41 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.104285 | 0.104285 | 0.104285 | 0.104285 | 1477.02 | 1477.02 | 1670.56 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.064387 | 0.064387 | 0.064387 | 0.064387 | 931.68 | 931.68 | 1238.05 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.063051 | 0.063051 | 0.063051 | 0.063051 | 912.56 | 912.56 | 1238.00 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.114553 | 0.114553 | 0.114553 | 0.114553 | 1700.88 | 1700.88 | 1227.96 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.120732 | 0.120732 | 0.120732 | 0.120732 | 1787.39 | 1787.39 | 1234.08 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.226007 | 0.226007 | 0.226007 | 0.226007 | 3237.00 | 3237.00 | 1572.32 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.188896 | 0.188896 | 0.188896 | 0.188896 | 2695.86 | 2695.86 | 1576.60 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.222403 | 0.222403 | 0.222403 | 0.222403 | 3200.43 | 3200.43 | 1589.50 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.141186 | 0.141186 | 0.141186 | 0.141186 | 1984.64 | 1984.64 | 1574.69 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.093676 | 0.093676 | 0.093676 | 0.093676 | 1344.49 | 1344.49 | 1136.65 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.092521 | 0.092521 | 0.092521 | 0.092521 | 1328.10 | 1328.10 | 1136.65 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.152813 | 0.152813 | 0.152813 | 0.152813 | 2236.36 | 2236.36 | 1136.65 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.155063 | 0.155063 | 0.155063 | 0.155063 | 2267.91 | 2267.91 | 1136.65 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.226977 | 0.226977 | 0.226977 | 0.226977 | 3246.91 | 3246.91 | 1553.36 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.190759 | 0.190759 | 0.190759 | 0.190759 | 2718.42 | 2718.42 | 1556.84 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.204332 | 0.204332 | 0.204332 | 0.204332 | 2943.71 | 2943.71 | 1554.12 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.143826 | 0.143826 | 0.143826 | 0.143826 | 2017.99 | 2017.99 | 1555.28 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.097757 | 0.097757 | 0.097757 | 0.097757 | 1400.14 | 1400.14 | 1136.65 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.096616 | 0.096616 | 0.096616 | 0.096616 | 1383.98 | 1383.98 | 1136.65 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.156377 | 0.156377 | 0.156377 | 0.156377 | 2284.07 | 2284.07 | 1136.65 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.157326 | 0.157326 | 0.157326 | 0.157326 | 2297.37 | 2297.37 | 1136.65 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.226718 | 0.226718 | 0.226718 | 0.226718 | 3240.61 | 3240.61 | 1574.01 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.190712 | 0.190712 | 0.190712 | 0.190712 | 2715.17 | 2715.17 | 1577.31 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.202908 | 0.202908 | 0.202908 | 0.202908 | 2921.19 | 2921.19 | 1573.04 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.143858 | 0.143858 | 0.143858 | 0.143858 | 2024.77 | 2024.77 | 1576.07 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.099020 | 0.099020 | 0.099020 | 0.099020 | 1416.45 | 1416.45 | 1136.65 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.097895 | 0.097895 | 0.097895 | 0.097895 | 1400.53 | 1400.53 | 1136.65 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.157223 | 0.157223 | 0.157223 | 0.157223 | 2294.27 | 2294.27 | 1136.65 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.157973 | 0.157973 | 0.157973 | 0.157973 | 2304.78 | 2304.78 | 1136.65 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.228297 | 0.228297 | 0.228297 | 0.228297 | 3260.58 | 3260.58 | 1578.67 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.192443 | 0.192443 | 0.192443 | 0.192443 | 2737.36 | 2737.36 | 1580.66 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.204988 | 0.204988 | 0.204988 | 0.204988 | 2948.26 | 2948.26 | 1577.75 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.145606 | 0.145606 | 0.145606 | 0.145606 | 2047.31 | 2047.31 | 1579.71 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.101613 | 0.101613 | 0.101613 | 0.101613 | 1451.87 | 1451.87 | 1136.65 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.100501 | 0.100501 | 0.100501 | 0.100501 | 1436.15 | 1436.15 | 1136.65 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.159562 | 0.159562 | 0.159562 | 0.159562 | 2325.72 | 2325.72 | 1136.65 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.160283 | 0.160283 | 0.160283 | 0.160283 | 2335.83 | 2335.83 | 1136.65 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.224629 | 0.224629 | 0.224629 | 0.224629 | 3216.33 | 3216.33 | 1640.86 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.188774 | 0.188774 | 0.188774 | 0.188774 | 2684.22 | 2684.22 | 1643.30 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.201934 | 0.201934 | 0.201934 | 0.201934 | 2903.81 | 2903.81 | 1640.17 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.142039 | 0.142039 | 0.142039 | 0.142039 | 1995.95 | 1995.95 | 1642.60 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.098978 | 0.098978 | 0.098978 | 0.098978 | 1413.58 | 1413.58 | 1136.65 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.097887 | 0.097887 | 0.097887 | 0.097887 | 1398.17 | 1398.17 | 1136.65 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.156567 | 0.156567 | 0.156567 | 0.156567 | 2282.63 | 2282.63 | 1136.65 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.157285 | 0.157285 | 0.157285 | 0.157285 | 2292.69 | 2292.69 | 1136.65 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.223068 | 0.223068 | 0.223068 | 0.223068 | 3192.94 | 3192.94 | 1680.96 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.187197 | 0.187197 | 0.187197 | 0.187197 | 2660.65 | 2660.65 | 1682.82 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.200845 | 0.200845 | 0.200845 | 0.200845 | 2887.09 | 2887.09 | 1680.49 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.140503 | 0.140503 | 0.140503 | 0.140503 | 1973.20 | 1973.20 | 1682.35 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.098182 | 0.098182 | 0.098182 | 0.098182 | 1401.45 | 1401.45 | 1136.65 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.097107 | 0.097107 | 0.097107 | 0.097107 | 1386.26 | 1386.26 | 1136.65 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.155491 | 0.155491 | 0.155491 | 0.155491 | 2266.59 | 2266.59 | 1136.65 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.156208 | 0.156208 | 0.156208 | 0.156208 | 2276.63 | 2276.63 | 1136.65 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.222598 | 0.222598 | 0.222598 | 0.222598 | 3185.00 | 3185.00 | 1722.82 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.186737 | 0.186737 | 0.186737 | 0.186737 | 2652.90 | 2652.90 | 1724.00 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.200761 | 0.200761 | 0.200761 | 0.200761 | 2884.61 | 2884.61 | 1722.57 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.140010 | 0.140010 | 0.140010 | 0.140010 | 1965.16 | 1965.16 | 1723.75 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.098397 | 0.098397 | 0.098397 | 0.098397 | 1403.70 | 1403.70 | 1136.65 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.097336 | 0.097336 | 0.097336 | 0.097336 | 1388.72 | 1388.72 | 1136.65 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.155432 | 0.155432 | 0.155432 | 0.155432 | 2264.91 | 2264.91 | 1136.65 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.156151 | 0.156151 | 0.156151 | 0.156151 | 2274.97 | 2274.97 | 1136.65 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.227702 | 0.227702 | 0.227702 | 0.227702 | 3246.27 | 3246.27 | 1845.30 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.192041 | 0.192041 | 0.192041 | 0.192041 | 2726.00 | 2726.00 | 1844.46 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.204897 | 0.204897 | 0.204897 | 0.204897 | 2944.46 | 2944.46 | 1845.25 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.141114 | 0.141114 | 0.141114 | 0.141114 | 1988.83 | 1988.83 | 1844.41 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.103573 | 0.103573 | 0.103573 | 0.103573 | 1476.09 | 1476.09 | 1208.35 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.102515 | 0.102515 | 0.102515 | 0.102515 | 1461.16 | 1461.16 | 1208.35 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.158850 | 0.158850 | 0.158850 | 0.158850 | 2311.99 | 2311.99 | 1208.90 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.159653 | 0.159653 | 0.159653 | 0.159653 | 2323.24 | 2323.24 | 1208.90 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.283258 | 0.283258 | 0.283258 | 0.283258 | 4035.11 | 4035.11 | 2251.22 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.236387 | 0.236387 | 0.236387 | 0.236387 | 3358.57 | 3358.57 | 2254.87 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.256494 | 0.256494 | 0.256494 | 0.256494 | 3661.84 | 3661.84 | 2251.32 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.177740 | 0.177740 | 0.177740 | 0.177740 | 2508.57 | 2508.57 | 2254.97 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.138861 | 0.138861 | 0.138861 | 0.138861 | 2034.57 | 2034.57 | 1646.47 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.138947 | 0.138947 | 0.138947 | 0.138947 | 2035.77 | 2035.77 | 1646.47 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.216094 | 0.216094 | 0.216094 | 0.216094 | 3113.02 | 3113.02 | 1639.75 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.216854 | 0.216854 | 0.216854 | 0.216854 | 3123.67 | 3123.67 | 1639.75 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.176890 |
AIRLOOP G NW SUPPLY FAN | 0.146906 |
AIRLOOP OFFICE SUPPLY FAN | 0.288783 |
AIRLOOP G NE SUPPLY FAN | 0.104285 |
AIRLOOP G N1 SUPPLY FAN | 0.064387 |
AIRLOOP G N2 SUPPLY FAN | 0.063051 |
AIRLOOP G S1 SUPPLY FAN | 0.114553 |
AIRLOOP G S2 SUPPLY FAN | 0.120732 |
AIRLOOP F2 SW SUPPLY FAN | 0.226007 |
AIRLOOP F2 NW SUPPLY FAN | 0.188896 |
AIRLOOP F2 SE SUPPLY FAN | 0.222403 |
AIRLOOP F2 NE SUPPLY FAN | 0.141186 |
AIRLOOP F2 N1 SUPPLY FAN | 0.093676 |
AIRLOOP F2 N2 SUPPLY FAN | 0.092521 |
AIRLOOP F2 S1 SUPPLY FAN | 0.152813 |
AIRLOOP F2 S2 SUPPLY FAN | 0.155063 |
AIRLOOP F3 SW SUPPLY FAN | 0.226977 |
AIRLOOP F3 NW SUPPLY FAN | 0.190759 |
AIRLOOP F3 SE SUPPLY FAN | 0.204332 |
AIRLOOP F3 NE SUPPLY FAN | 0.143826 |
AIRLOOP F3 N1 SUPPLY FAN | 0.097757 |
AIRLOOP F3 N2 SUPPLY FAN | 0.096616 |
AIRLOOP F3 S1 SUPPLY FAN | 0.156377 |
AIRLOOP F3 S2 SUPPLY FAN | 0.157326 |
AIRLOOP F4 SW SUPPLY FAN | 0.226718 |
AIRLOOP F4 NW SUPPLY FAN | 0.190712 |
AIRLOOP F4 SE SUPPLY FAN | 0.202908 |
AIRLOOP F4 NE SUPPLY FAN | 0.143858 |
AIRLOOP F4 N1 SUPPLY FAN | 0.099020 |
AIRLOOP F4 N2 SUPPLY FAN | 0.097895 |
AIRLOOP F4 S1 SUPPLY FAN | 0.157223 |
AIRLOOP F4 S2 SUPPLY FAN | 0.157973 |
AIRLOOP M SW SUPPLY FAN | 0.228297 |
AIRLOOP M NW SUPPLY FAN | 0.192443 |
AIRLOOP M SE SUPPLY FAN | 0.204988 |
AIRLOOP M NE SUPPLY FAN | 0.145606 |
AIRLOOP M N1 SUPPLY FAN | 0.101613 |
AIRLOOP M N2 SUPPLY FAN | 0.100501 |
AIRLOOP M S1 SUPPLY FAN | 0.159562 |
AIRLOOP M S2 SUPPLY FAN | 0.160283 |
AIRLOOP F6 SW SUPPLY FAN | 0.224629 |
AIRLOOP F6 NW SUPPLY FAN | 0.188774 |
AIRLOOP F6 SE SUPPLY FAN | 0.201934 |
AIRLOOP F6 NE SUPPLY FAN | 0.142039 |
AIRLOOP F6 N1 SUPPLY FAN | 0.098978 |
AIRLOOP F6 N2 SUPPLY FAN | 0.097887 |
AIRLOOP F6 S1 SUPPLY FAN | 0.156567 |
AIRLOOP F6 S2 SUPPLY FAN | 0.157285 |
AIRLOOP F7 SW SUPPLY FAN | 0.223068 |
AIRLOOP F7 NW SUPPLY FAN | 0.187197 |
AIRLOOP F7 SE SUPPLY FAN | 0.200845 |
AIRLOOP F7 NE SUPPLY FAN | 0.140503 |
AIRLOOP F7 N1 SUPPLY FAN | 0.098182 |
AIRLOOP F7 N2 SUPPLY FAN | 0.097107 |
AIRLOOP F7 S1 SUPPLY FAN | 0.155491 |
AIRLOOP F7 S2 SUPPLY FAN | 0.156208 |
AIRLOOP F8 SW SUPPLY FAN | 0.222598 |
AIRLOOP F8 NW SUPPLY FAN | 0.186737 |
AIRLOOP F8 SE SUPPLY FAN | 0.200761 |
AIRLOOP F8 NE SUPPLY FAN | 0.140010 |
AIRLOOP F8 N1 SUPPLY FAN | 0.098397 |
AIRLOOP F8 N2 SUPPLY FAN | 0.097336 |
AIRLOOP F8 S1 SUPPLY FAN | 0.155432 |
AIRLOOP F8 S2 SUPPLY FAN | 0.156151 |
AIRLOOP F9 SW SUPPLY FAN | 0.227702 |
AIRLOOP F9 NW SUPPLY FAN | 0.192041 |
AIRLOOP F9 SE SUPPLY FAN | 0.204897 |
AIRLOOP F9 NE SUPPLY FAN | 0.141114 |
AIRLOOP F9 N1 SUPPLY FAN | 0.103573 |
AIRLOOP F9 N2 SUPPLY FAN | 0.102515 |
AIRLOOP F9 S1 SUPPLY FAN | 0.158850 |
AIRLOOP F9 S2 SUPPLY FAN | 0.159653 |
AIRLOOP T SW SUPPLY FAN | 0.283258 |
AIRLOOP T NW SUPPLY FAN | 0.236387 |
AIRLOOP T SE SUPPLY FAN | 0.256494 |
AIRLOOP T NE SUPPLY FAN | 0.177740 |
AIRLOOP T N1 SUPPLY FAN | 0.138861 |
AIRLOOP T N2 SUPPLY FAN | 0.138947 |
AIRLOOP T S1 SUPPLY FAN | 0.216094 |
AIRLOOP T S2 SUPPLY FAN | 0.216854 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.176890 | 2563.84 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.146906 | 2112.46 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.288783 | 4156.08 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.104285 | 1477.02 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.064387 | 931.68 | 0.000020 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.063051 | 912.56 | 0.000020 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.114553 | 1700.88 | 0.000037 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.120732 | 1787.39 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.226007 | 3237.00 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.188896 | 2695.86 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.222403 | 3200.43 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.141186 | 1984.64 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.093676 | 1344.49 | 0.000029 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.092521 | 1328.10 | 0.000029 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.152813 | 2236.36 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.155063 | 2267.91 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.226977 | 3246.91 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.190759 | 2718.42 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.204332 | 2943.71 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.143826 | 2017.99 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.097757 | 1400.14 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.096616 | 1383.98 | 0.000030 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.156377 | 2284.07 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.157326 | 2297.37 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.226718 | 3240.61 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.190712 | 2715.17 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.202908 | 2921.19 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.143858 | 2024.77 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.099020 | 1416.45 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.097895 | 1400.53 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.157223 | 2294.27 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.157973 | 2304.78 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.228297 | 3260.58 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.192443 | 2737.36 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.204988 | 2948.26 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.145606 | 2047.31 | 0.000045 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.101613 | 1451.87 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.100501 | 1436.15 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.159562 | 2325.72 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.160283 | 2335.83 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.224629 | 3216.33 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.188774 | 2684.22 | 0.000059 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.201934 | 2903.81 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.142039 | 1995.95 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.098978 | 1413.58 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.097887 | 1398.17 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.156567 | 2282.63 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.157285 | 2292.69 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.223068 | 3192.94 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.187197 | 2660.65 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.200845 | 2887.09 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.140503 | 1973.20 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.098182 | 1401.45 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.097107 | 1386.26 | 0.000030 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.155491 | 2266.59 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.156208 | 2276.63 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.222598 | 3185.00 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.186737 | 2652.90 | 0.000058 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.200761 | 2884.61 | 0.000063 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.140010 | 1965.16 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.098397 | 1403.70 | 0.000031 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.097336 | 1388.72 | 0.000030 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.155432 | 2264.91 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.156151 | 2274.97 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.227702 | 3246.27 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.192041 | 2726.00 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.204897 | 2944.46 | 0.000064 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.141114 | 1988.83 | 0.000043 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.103573 | 1476.09 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.102515 | 1461.16 | 0.000032 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.158850 | 2311.99 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.159653 | 2323.24 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.283258 | 4035.11 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.236387 | 3358.57 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.256494 | 3661.84 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.177740 | 2508.57 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.138861 | 2034.57 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.138947 | 2035.77 | 0.000044 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.216094 | 3113.02 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.216854 | 3123.67 | 0.000068 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 1666.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 1672.45 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 2242.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 1670.56 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 1238.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 1238.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 1227.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 1234.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 1572.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 1576.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 1589.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 1574.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 1553.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 1556.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 1554.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 1555.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 1574.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 1577.31 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 1573.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 1576.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 1578.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 1580.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 1577.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 1579.71 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 1640.86 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 1643.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 1640.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 1642.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 1680.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 1682.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 1680.49 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 1682.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 1722.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 1724.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 1722.57 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 1723.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 1136.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 1845.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 1844.46 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 1845.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 1844.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 1208.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 1208.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 1208.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 1208.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 2251.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 2254.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 2251.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 2254.97 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 1646.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 1646.47 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 1639.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 1639.75 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.004056 | 4.56 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.004056 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.004056 | 1958.18 | 5.15 | 6075.76 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.004056 | 1295.38 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:12:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 9.60 |
February | 22.45 | 11.29 |
March | 22.49 | 12.66 |
April | 22.40 | 13.68 |
May | 22.37 | 15.00 |
June | 22.91 | 15.34 |
July | 23.22 | 15.94 |
August | 23.51 | 16.62 |
September | 23.68 | 16.72 |
October | 22.92 | 15.11 |
November | 22.68 | 12.79 |
December | 22.45 | 10.66 |
Annual Sum or Average | 22.77 | 13.79 |
Minimum of Months | 22.10 | 9.60 |
Maximum of Months | 23.68 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 9.60 |
February | 21.80 | 11.29 |
March | 21.92 | 12.66 |
April | 22.07 | 13.68 |
May | 22.22 | 15.00 |
June | 22.81 | 15.34 |
July | 23.04 | 15.94 |
August | 23.20 | 16.62 |
September | 23.14 | 16.72 |
October | 22.25 | 15.11 |
November | 21.92 | 12.79 |
December | 21.75 | 10.66 |
Annual Sum or Average | 22.32 | 13.79 |
Minimum of Months | 21.71 | 9.60 |
Maximum of Months | 23.20 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 9.60 |
February | 22.81 | 11.29 |
March | 22.99 | 12.66 |
April | 23.04 | 13.68 |
May | 23.17 | 15.00 |
June | 23.58 | 15.34 |
July | 23.91 | 15.94 |
August | 24.06 | 16.62 |
September | 24.14 | 16.72 |
October | 23.52 | 15.11 |
November | 23.10 | 12.79 |
December | 22.72 | 10.66 |
Annual Sum or Average | 23.29 | 13.79 |
Minimum of Months | 22.48 | 9.60 |
Maximum of Months | 24.14 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.76 | 11.29 |
March | 21.89 | 12.66 |
April | 22.04 | 13.68 |
May | 22.17 | 15.00 |
June | 22.68 | 15.34 |
July | 22.83 | 15.94 |
August | 23.05 | 16.62 |
September | 22.97 | 16.72 |
October | 22.19 | 15.11 |
November | 21.88 | 12.79 |
December | 21.71 | 10.66 |
Annual Sum or Average | 22.24 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 23.05 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.74 | 11.29 |
March | 21.82 | 12.66 |
April | 21.93 | 13.68 |
May | 22.06 | 15.00 |
June | 22.63 | 15.34 |
July | 22.75 | 15.94 |
August | 22.98 | 16.62 |
September | 22.93 | 16.72 |
October | 22.16 | 15.11 |
November | 21.87 | 12.79 |
December | 21.72 | 10.66 |
Annual Sum or Average | 22.19 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 22.98 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.73 | 11.29 |
March | 21.82 | 12.66 |
April | 21.93 | 13.68 |
May | 22.06 | 15.00 |
June | 22.62 | 15.34 |
July | 22.74 | 15.94 |
August | 22.97 | 16.62 |
September | 22.91 | 16.72 |
October | 22.16 | 15.11 |
November | 21.87 | 12.79 |
December | 21.72 | 10.66 |
Annual Sum or Average | 22.19 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 22.97 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 9.60 |
February | 22.57 | 11.29 |
March | 22.54 | 12.66 |
April | 22.35 | 13.68 |
May | 22.28 | 15.00 |
June | 22.86 | 15.34 |
July | 23.08 | 15.94 |
August | 23.47 | 16.62 |
September | 23.70 | 16.72 |
October | 23.01 | 15.11 |
November | 22.87 | 12.79 |
December | 22.63 | 10.66 |
Annual Sum or Average | 22.80 | 13.79 |
Minimum of Months | 22.22 | 9.60 |
Maximum of Months | 23.70 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 9.60 |
February | 22.64 | 11.29 |
March | 22.61 | 12.66 |
April | 22.42 | 13.68 |
May | 22.34 | 15.00 |
June | 22.93 | 15.34 |
July | 23.15 | 15.94 |
August | 23.53 | 16.62 |
September | 23.75 | 16.72 |
October | 23.08 | 15.11 |
November | 22.95 | 12.79 |
December | 22.69 | 10.66 |
Annual Sum or Average | 22.86 | 13.79 |
Minimum of Months | 22.27 | 9.60 |
Maximum of Months | 23.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.51 | 9.60 |
February | 19.35 | 11.29 |
March | 19.90 | 12.66 |
April | 20.30 | 13.68 |
May | 20.82 | 15.00 |
June | 21.73 | 15.34 |
July | 22.04 | 15.94 |
August | 22.42 | 16.62 |
September | 22.45 | 16.72 |
October | 21.04 | 15.11 |
November | 19.95 | 12.79 |
December | 19.02 | 10.66 |
Annual Sum or Average | 20.63 | 13.79 |
Minimum of Months | 18.51 | 9.60 |
Maximum of Months | 22.45 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 9.60 |
February | 23.24 | 11.29 |
March | 23.29 | 12.66 |
April | 23.03 | 13.68 |
May | 22.90 | 15.00 |
June | 23.12 | 15.34 |
July | 23.46 | 15.94 |
August | 23.80 | 16.62 |
September | 23.99 | 16.72 |
October | 23.67 | 15.11 |
November | 23.56 | 12.79 |
December | 23.19 | 10.66 |
Annual Sum or Average | 23.32 | 13.79 |
Minimum of Months | 22.60 | 9.60 |
Maximum of Months | 23.99 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 9.60 |
February | 21.99 | 11.29 |
March | 22.24 | 12.66 |
April | 22.45 | 13.68 |
May | 22.61 | 15.00 |
June | 22.94 | 15.34 |
July | 23.19 | 15.94 |
August | 23.37 | 16.62 |
September | 23.30 | 16.72 |
October | 22.68 | 15.11 |
November | 22.37 | 12.79 |
December | 21.93 | 10.66 |
Annual Sum or Average | 22.58 | 13.79 |
Minimum of Months | 21.79 | 9.60 |
Maximum of Months | 23.37 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 9.60 |
February | 23.39 | 11.29 |
March | 23.44 | 12.66 |
April | 23.23 | 13.68 |
May | 23.09 | 15.00 |
June | 23.31 | 15.34 |
July | 23.55 | 15.94 |
August | 23.88 | 16.62 |
September | 24.04 | 16.72 |
October | 23.78 | 15.11 |
November | 23.71 | 12.79 |
December | 23.35 | 10.66 |
Annual Sum or Average | 23.46 | 13.79 |
Minimum of Months | 22.78 | 9.60 |
Maximum of Months | 24.04 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 9.60 |
February | 21.91 | 11.29 |
March | 22.15 | 12.66 |
April | 22.37 | 13.68 |
May | 22.52 | 15.00 |
June | 22.81 | 15.34 |
July | 22.95 | 15.94 |
August | 23.20 | 16.62 |
September | 23.10 | 16.72 |
October | 22.58 | 15.11 |
November | 22.27 | 12.79 |
December | 21.84 | 10.66 |
Annual Sum or Average | 22.46 | 13.79 |
Minimum of Months | 21.75 | 9.60 |
Maximum of Months | 23.20 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 9.60 |
February | 21.97 | 11.29 |
March | 22.18 | 12.66 |
April | 22.36 | 13.68 |
May | 22.47 | 15.00 |
June | 22.79 | 15.34 |
July | 22.89 | 15.94 |
August | 23.15 | 16.62 |
September | 23.09 | 16.72 |
October | 22.64 | 15.11 |
November | 22.42 | 12.79 |
December | 21.94 | 10.66 |
Annual Sum or Average | 22.48 | 13.79 |
Minimum of Months | 21.81 | 9.60 |
Maximum of Months | 23.15 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 9.60 |
February | 21.96 | 11.29 |
March | 22.17 | 12.66 |
April | 22.35 | 13.68 |
May | 22.46 | 15.00 |
June | 22.78 | 15.34 |
July | 22.87 | 15.94 |
August | 23.13 | 16.62 |
September | 23.07 | 16.72 |
October | 22.63 | 15.11 |
November | 22.41 | 12.79 |
December | 21.94 | 10.66 |
Annual Sum or Average | 22.47 | 13.79 |
Minimum of Months | 21.81 | 9.60 |
Maximum of Months | 23.13 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.03 | 9.60 |
February | 23.59 | 11.29 |
March | 23.50 | 12.66 |
April | 23.11 | 13.68 |
May | 22.85 | 15.00 |
June | 23.06 | 15.34 |
July | 23.28 | 15.94 |
August | 23.73 | 16.62 |
September | 23.98 | 16.72 |
October | 23.79 | 15.11 |
November | 23.83 | 12.79 |
December | 23.58 | 10.66 |
Annual Sum or Average | 23.44 | 13.79 |
Minimum of Months | 22.85 | 9.60 |
Maximum of Months | 23.98 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 9.60 |
February | 23.62 | 11.29 |
March | 23.52 | 12.66 |
April | 23.15 | 13.68 |
May | 22.88 | 15.00 |
June | 23.09 | 15.34 |
July | 23.31 | 15.94 |
August | 23.75 | 16.62 |
September | 23.99 | 16.72 |
October | 23.81 | 15.11 |
November | 23.85 | 12.79 |
December | 23.61 | 10.66 |
Annual Sum or Average | 23.47 | 13.79 |
Minimum of Months | 22.88 | 9.60 |
Maximum of Months | 23.99 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 9.60 |
February | 23.28 | 11.29 |
March | 23.53 | 12.66 |
April | 23.61 | 13.68 |
May | 23.70 | 15.00 |
June | 24.08 | 15.34 |
July | 24.40 | 15.94 |
August | 24.71 | 16.62 |
September | 24.79 | 16.72 |
October | 24.13 | 15.11 |
November | 23.70 | 12.79 |
December | 23.12 | 10.66 |
Annual Sum or Average | 23.82 | 13.79 |
Minimum of Months | 22.71 | 9.60 |
Maximum of Months | 24.79 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 9.60 |
February | 23.41 | 11.29 |
March | 23.42 | 12.66 |
April | 23.10 | 13.68 |
May | 22.92 | 15.00 |
June | 22.99 | 15.34 |
July | 23.33 | 15.94 |
August | 23.72 | 16.62 |
September | 23.93 | 16.72 |
October | 23.73 | 15.11 |
November | 23.72 | 12.79 |
December | 23.37 | 10.66 |
Annual Sum or Average | 23.36 | 13.79 |
Minimum of Months | 22.75 | 9.60 |
Maximum of Months | 23.93 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 9.60 |
February | 22.05 | 11.29 |
March | 22.32 | 12.66 |
April | 22.50 | 13.68 |
May | 22.63 | 15.00 |
June | 22.82 | 15.34 |
July | 23.04 | 15.94 |
August | 23.28 | 16.62 |
September | 23.20 | 16.72 |
October | 22.75 | 15.11 |
November | 22.56 | 12.79 |
December | 22.01 | 10.66 |
Annual Sum or Average | 22.59 | 13.79 |
Minimum of Months | 21.82 | 9.60 |
Maximum of Months | 23.28 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 9.60 |
February | 23.39 | 11.29 |
March | 23.39 | 12.66 |
April | 23.10 | 13.68 |
May | 22.93 | 15.00 |
June | 22.99 | 15.34 |
July | 23.23 | 15.94 |
August | 23.65 | 16.62 |
September | 23.87 | 16.72 |
October | 23.69 | 15.11 |
November | 23.72 | 12.79 |
December | 23.37 | 10.66 |
Annual Sum or Average | 23.34 | 13.79 |
Minimum of Months | 22.75 | 9.60 |
Maximum of Months | 23.87 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.96 | 11.29 |
March | 22.23 | 12.66 |
April | 22.43 | 13.68 |
May | 22.55 | 15.00 |
June | 22.72 | 15.34 |
July | 22.83 | 15.94 |
August | 23.12 | 16.62 |
September | 23.02 | 16.72 |
October | 22.66 | 15.11 |
November | 22.44 | 12.79 |
December | 21.90 | 10.66 |
Annual Sum or Average | 22.47 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 23.12 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 9.60 |
February | 22.09 | 11.29 |
March | 22.33 | 12.66 |
April | 22.49 | 13.68 |
May | 22.56 | 15.00 |
June | 22.73 | 15.34 |
July | 22.81 | 15.94 |
August | 23.10 | 16.62 |
September | 23.04 | 16.72 |
October | 22.78 | 15.11 |
November | 22.69 | 12.79 |
December | 22.08 | 10.66 |
Annual Sum or Average | 22.55 | 13.79 |
Minimum of Months | 21.88 | 9.60 |
Maximum of Months | 23.10 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 9.60 |
February | 22.08 | 11.29 |
March | 22.32 | 12.66 |
April | 22.48 | 13.68 |
May | 22.55 | 15.00 |
June | 22.72 | 15.34 |
July | 22.79 | 15.94 |
August | 23.08 | 16.62 |
September | 23.02 | 16.72 |
October | 22.77 | 15.11 |
November | 22.68 | 12.79 |
December | 22.07 | 10.66 |
Annual Sum or Average | 22.54 | 13.79 |
Minimum of Months | 21.88 | 9.60 |
Maximum of Months | 23.08 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 9.60 |
February | 23.84 | 11.29 |
March | 23.71 | 12.66 |
April | 23.28 | 13.68 |
May | 22.95 | 15.00 |
June | 22.99 | 15.34 |
July | 23.20 | 15.94 |
August | 23.69 | 16.62 |
September | 23.95 | 16.72 |
October | 23.89 | 15.11 |
November | 24.02 | 12.79 |
December | 23.82 | 10.66 |
Annual Sum or Average | 23.55 | 13.79 |
Minimum of Months | 22.95 | 9.60 |
Maximum of Months | 24.02 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 9.60 |
February | 23.85 | 11.29 |
March | 23.71 | 12.66 |
April | 23.29 | 13.68 |
May | 22.96 | 15.00 |
June | 23.00 | 15.34 |
July | 23.20 | 15.94 |
August | 23.69 | 16.62 |
September | 23.95 | 16.72 |
October | 23.89 | 15.11 |
November | 24.03 | 12.79 |
December | 23.82 | 10.66 |
Annual Sum or Average | 23.55 | 13.79 |
Minimum of Months | 22.96 | 9.60 |
Maximum of Months | 24.03 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 9.60 |
February | 23.75 | 11.29 |
March | 23.97 | 12.66 |
April | 23.98 | 13.68 |
May | 23.99 | 15.00 |
June | 24.15 | 15.34 |
July | 24.44 | 15.94 |
August | 24.81 | 16.62 |
September | 24.90 | 16.72 |
October | 24.49 | 15.11 |
November | 24.22 | 12.79 |
December | 23.61 | 10.66 |
Annual Sum or Average | 24.12 | 13.79 |
Minimum of Months | 23.18 | 9.60 |
Maximum of Months | 24.90 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 9.60 |
February | 23.41 | 11.29 |
March | 23.42 | 12.66 |
April | 23.11 | 13.68 |
May | 22.86 | 15.00 |
June | 22.88 | 15.34 |
July | 23.20 | 15.94 |
August | 23.66 | 16.62 |
September | 23.89 | 16.72 |
October | 23.71 | 15.11 |
November | 23.78 | 12.79 |
December | 23.38 | 10.66 |
Annual Sum or Average | 23.34 | 13.79 |
Minimum of Months | 22.75 | 9.60 |
Maximum of Months | 23.89 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 9.60 |
February | 22.05 | 11.29 |
March | 22.33 | 12.66 |
April | 22.51 | 13.68 |
May | 22.59 | 15.00 |
June | 22.72 | 15.34 |
July | 22.92 | 15.94 |
August | 23.22 | 16.62 |
September | 23.14 | 16.72 |
October | 22.76 | 15.11 |
November | 22.68 | 12.79 |
December | 22.03 | 10.66 |
Annual Sum or Average | 22.57 | 13.79 |
Minimum of Months | 21.83 | 9.60 |
Maximum of Months | 23.22 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 9.60 |
February | 23.34 | 11.29 |
March | 23.35 | 12.66 |
April | 23.06 | 13.68 |
May | 22.84 | 15.00 |
June | 22.85 | 15.34 |
July | 23.07 | 15.94 |
August | 23.56 | 16.62 |
September | 23.81 | 16.72 |
October | 23.64 | 15.11 |
November | 23.74 | 12.79 |
December | 23.35 | 10.66 |
Annual Sum or Average | 23.28 | 13.79 |
Minimum of Months | 22.71 | 9.60 |
Maximum of Months | 23.81 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.96 | 11.29 |
March | 22.24 | 12.66 |
April | 22.44 | 13.68 |
May | 22.53 | 15.00 |
June | 22.65 | 15.34 |
July | 22.73 | 15.94 |
August | 23.07 | 16.62 |
September | 22.97 | 16.72 |
October | 22.67 | 15.11 |
November | 22.56 | 12.79 |
December | 21.92 | 10.66 |
Annual Sum or Average | 22.46 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 23.07 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 9.60 |
February | 22.12 | 11.29 |
March | 22.38 | 12.66 |
April | 22.54 | 13.68 |
May | 22.57 | 15.00 |
June | 22.68 | 15.34 |
July | 22.74 | 15.94 |
August | 23.08 | 16.62 |
September | 23.03 | 16.72 |
October | 22.83 | 15.11 |
November | 22.86 | 12.79 |
December | 22.13 | 10.66 |
Annual Sum or Average | 22.57 | 13.79 |
Minimum of Months | 21.90 | 9.60 |
Maximum of Months | 23.08 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 9.60 |
February | 22.11 | 11.29 |
March | 22.37 | 12.66 |
April | 22.53 | 13.68 |
May | 22.56 | 15.00 |
June | 22.67 | 15.34 |
July | 22.72 | 15.94 |
August | 23.06 | 16.62 |
September | 23.01 | 16.72 |
October | 22.82 | 15.11 |
November | 22.85 | 12.79 |
December | 22.12 | 10.66 |
Annual Sum or Average | 22.56 | 13.79 |
Minimum of Months | 21.90 | 9.60 |
Maximum of Months | 23.06 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 9.60 |
February | 23.89 | 11.29 |
March | 23.75 | 12.66 |
April | 23.35 | 13.68 |
May | 22.95 | 15.00 |
June | 22.92 | 15.34 |
July | 23.12 | 15.94 |
August | 23.67 | 16.62 |
September | 23.94 | 16.72 |
October | 23.91 | 15.11 |
November | 24.10 | 12.79 |
December | 23.86 | 10.66 |
Annual Sum or Average | 23.56 | 13.79 |
Minimum of Months | 22.92 | 9.60 |
Maximum of Months | 24.10 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 9.60 |
February | 23.88 | 11.29 |
March | 23.75 | 12.66 |
April | 23.35 | 13.68 |
May | 22.95 | 15.00 |
June | 22.93 | 15.34 |
July | 23.11 | 15.94 |
August | 23.66 | 16.62 |
September | 23.93 | 16.72 |
October | 23.90 | 15.11 |
November | 24.10 | 12.79 |
December | 23.86 | 10.66 |
Annual Sum or Average | 23.56 | 13.79 |
Minimum of Months | 22.93 | 9.60 |
Maximum of Months | 24.10 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 9.60 |
February | 23.90 | 11.29 |
March | 24.10 | 12.66 |
April | 24.10 | 13.68 |
May | 24.06 | 15.00 |
June | 24.14 | 15.34 |
July | 24.42 | 15.94 |
August | 24.83 | 16.62 |
September | 24.94 | 16.72 |
October | 24.60 | 15.11 |
November | 24.43 | 12.79 |
December | 23.78 | 10.66 |
Annual Sum or Average | 24.22 | 13.79 |
Minimum of Months | 23.33 | 9.60 |
Maximum of Months | 24.94 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 9.60 |
February | 23.37 | 11.29 |
March | 23.37 | 12.66 |
April | 23.03 | 13.68 |
May | 22.78 | 15.00 |
June | 22.78 | 15.34 |
July | 23.08 | 15.94 |
August | 23.57 | 16.62 |
September | 23.82 | 16.72 |
October | 23.65 | 15.11 |
November | 23.77 | 12.79 |
December | 23.37 | 10.66 |
Annual Sum or Average | 23.27 | 13.79 |
Minimum of Months | 22.72 | 9.60 |
Maximum of Months | 23.82 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 9.60 |
February | 22.04 | 11.29 |
March | 22.30 | 12.66 |
April | 22.47 | 13.68 |
May | 22.54 | 15.00 |
June | 22.65 | 15.34 |
July | 22.81 | 15.94 |
August | 23.14 | 16.62 |
September | 23.07 | 16.72 |
October | 22.73 | 15.11 |
November | 22.70 | 12.79 |
December | 22.04 | 10.66 |
Annual Sum or Average | 22.53 | 13.79 |
Minimum of Months | 21.83 | 9.60 |
Maximum of Months | 23.14 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 9.60 |
February | 23.29 | 11.29 |
March | 23.29 | 12.66 |
April | 22.99 | 13.68 |
May | 22.76 | 15.00 |
June | 22.76 | 15.34 |
July | 22.96 | 15.94 |
August | 23.48 | 16.62 |
September | 23.73 | 16.72 |
October | 23.58 | 15.11 |
November | 23.72 | 12.79 |
December | 23.32 | 10.66 |
Annual Sum or Average | 23.21 | 13.79 |
Minimum of Months | 22.69 | 9.60 |
Maximum of Months | 23.73 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 9.60 |
February | 21.96 | 11.29 |
March | 22.22 | 12.66 |
April | 22.41 | 13.68 |
May | 22.48 | 15.00 |
June | 22.59 | 15.34 |
July | 22.64 | 15.94 |
August | 23.01 | 16.62 |
September | 22.90 | 16.72 |
October | 22.65 | 15.11 |
November | 22.59 | 12.79 |
December | 21.93 | 10.66 |
Annual Sum or Average | 22.43 | 13.79 |
Minimum of Months | 21.79 | 9.60 |
Maximum of Months | 23.01 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 9.60 |
February | 22.14 | 11.29 |
March | 22.38 | 12.66 |
April | 22.53 | 13.68 |
May | 22.54 | 15.00 |
June | 22.63 | 15.34 |
July | 22.68 | 15.94 |
August | 23.04 | 16.62 |
September | 22.99 | 16.72 |
October | 22.83 | 15.11 |
November | 22.92 | 12.79 |
December | 22.16 | 10.66 |
Annual Sum or Average | 22.56 | 13.79 |
Minimum of Months | 21.92 | 9.60 |
Maximum of Months | 23.04 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 9.60 |
February | 22.13 | 11.29 |
March | 22.37 | 12.66 |
April | 22.52 | 13.68 |
May | 22.53 | 15.00 |
June | 22.63 | 15.34 |
July | 22.66 | 15.94 |
August | 23.02 | 16.62 |
September | 22.97 | 16.72 |
October | 22.82 | 15.11 |
November | 22.91 | 12.79 |
December | 22.15 | 10.66 |
Annual Sum or Average | 22.55 | 13.79 |
Minimum of Months | 21.92 | 9.60 |
Maximum of Months | 23.02 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 9.60 |
February | 23.88 | 11.29 |
March | 23.73 | 12.66 |
April | 23.31 | 13.68 |
May | 22.90 | 15.00 |
June | 22.86 | 15.34 |
July | 23.04 | 15.94 |
August | 23.60 | 16.62 |
September | 23.89 | 16.72 |
October | 23.87 | 15.11 |
November | 24.11 | 12.79 |
December | 23.87 | 10.66 |
Annual Sum or Average | 23.53 | 13.79 |
Minimum of Months | 22.86 | 9.60 |
Maximum of Months | 24.11 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 9.60 |
February | 23.88 | 11.29 |
March | 23.72 | 12.66 |
April | 23.31 | 13.68 |
May | 22.90 | 15.00 |
June | 22.86 | 15.34 |
July | 23.03 | 15.94 |
August | 23.59 | 16.62 |
September | 23.88 | 16.72 |
October | 23.87 | 15.11 |
November | 24.11 | 12.79 |
December | 23.87 | 10.66 |
Annual Sum or Average | 23.53 | 13.79 |
Minimum of Months | 22.86 | 9.60 |
Maximum of Months | 24.11 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.90 | 9.60 |
February | 24.45 | 11.29 |
March | 24.64 | 12.66 |
April | 24.61 | 13.68 |
May | 24.56 | 15.00 |
June | 24.61 | 15.34 |
July | 24.86 | 15.94 |
August | 25.30 | 16.62 |
September | 25.41 | 16.72 |
October | 25.13 | 15.11 |
November | 25.02 | 12.79 |
December | 24.35 | 10.66 |
Annual Sum or Average | 24.74 | 13.79 |
Minimum of Months | 23.90 | 9.60 |
Maximum of Months | 25.41 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 9.60 |
February | 23.21 | 11.29 |
March | 23.22 | 12.66 |
April | 22.86 | 13.68 |
May | 22.63 | 15.00 |
June | 22.63 | 15.34 |
July | 22.89 | 15.94 |
August | 23.41 | 16.62 |
September | 23.67 | 16.72 |
October | 23.50 | 15.11 |
November | 23.66 | 12.79 |
December | 23.26 | 10.66 |
Annual Sum or Average | 23.13 | 13.79 |
Minimum of Months | 22.60 | 9.60 |
Maximum of Months | 23.67 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 9.60 |
February | 21.96 | 11.29 |
March | 22.18 | 12.66 |
April | 22.34 | 13.68 |
May | 22.41 | 15.00 |
June | 22.51 | 15.34 |
July | 22.64 | 15.94 |
August | 22.99 | 16.62 |
September | 22.90 | 16.72 |
October | 22.60 | 15.11 |
November | 22.59 | 12.79 |
December | 21.97 | 10.66 |
Annual Sum or Average | 22.41 | 13.79 |
Minimum of Months | 21.80 | 9.60 |
Maximum of Months | 22.99 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 9.60 |
February | 23.14 | 11.29 |
March | 23.14 | 12.66 |
April | 22.83 | 13.68 |
May | 22.62 | 15.00 |
June | 22.63 | 15.34 |
July | 22.79 | 15.94 |
August | 23.32 | 16.62 |
September | 23.58 | 16.72 |
October | 23.43 | 15.11 |
November | 23.61 | 12.79 |
December | 23.21 | 10.66 |
Annual Sum or Average | 23.07 | 13.79 |
Minimum of Months | 22.57 | 9.60 |
Maximum of Months | 23.61 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 9.60 |
February | 21.90 | 11.29 |
March | 22.12 | 12.66 |
April | 22.31 | 13.68 |
May | 22.37 | 15.00 |
June | 22.48 | 15.34 |
July | 22.49 | 15.94 |
August | 22.86 | 16.62 |
September | 22.75 | 16.72 |
October | 22.53 | 15.11 |
November | 22.48 | 12.79 |
December | 21.88 | 10.66 |
Annual Sum or Average | 22.33 | 13.79 |
Minimum of Months | 21.77 | 9.60 |
Maximum of Months | 22.86 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 9.60 |
February | 22.04 | 11.29 |
March | 22.26 | 12.66 |
April | 22.41 | 13.68 |
May | 22.43 | 15.00 |
June | 22.51 | 15.34 |
July | 22.53 | 15.94 |
August | 22.89 | 16.62 |
September | 22.84 | 16.72 |
October | 22.70 | 15.11 |
November | 22.80 | 12.79 |
December | 22.07 | 10.66 |
Annual Sum or Average | 22.45 | 13.79 |
Minimum of Months | 21.87 | 9.60 |
Maximum of Months | 22.89 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 9.60 |
February | 22.03 | 11.29 |
March | 22.25 | 12.66 |
April | 22.40 | 13.68 |
May | 22.42 | 15.00 |
June | 22.50 | 15.34 |
July | 22.52 | 15.94 |
August | 22.88 | 16.62 |
September | 22.83 | 16.72 |
October | 22.70 | 15.11 |
November | 22.78 | 12.79 |
December | 22.06 | 10.66 |
Annual Sum or Average | 22.44 | 13.79 |
Minimum of Months | 21.86 | 9.60 |
Maximum of Months | 22.88 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 9.60 |
February | 23.77 | 11.29 |
March | 23.60 | 12.66 |
April | 23.14 | 13.68 |
May | 22.75 | 15.00 |
June | 22.71 | 15.34 |
July | 22.87 | 15.94 |
August | 23.45 | 16.62 |
September | 23.77 | 16.72 |
October | 23.75 | 15.11 |
November | 24.04 | 12.79 |
December | 23.78 | 10.66 |
Annual Sum or Average | 23.40 | 13.79 |
Minimum of Months | 22.71 | 9.60 |
Maximum of Months | 24.04 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 9.60 |
February | 23.76 | 11.29 |
March | 23.59 | 12.66 |
April | 23.14 | 13.68 |
May | 22.75 | 15.00 |
June | 22.71 | 15.34 |
July | 22.86 | 15.94 |
August | 23.44 | 16.62 |
September | 23.76 | 16.72 |
October | 23.75 | 15.11 |
November | 24.04 | 12.79 |
December | 23.78 | 10.66 |
Annual Sum or Average | 23.40 | 13.79 |
Minimum of Months | 22.71 | 9.60 |
Maximum of Months | 24.04 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 9.60 |
February | 23.79 | 11.29 |
March | 23.96 | 12.66 |
April | 23.92 | 13.68 |
May | 23.88 | 15.00 |
June | 23.93 | 15.34 |
July | 24.16 | 15.94 |
August | 24.61 | 16.62 |
September | 24.73 | 16.72 |
October | 24.45 | 15.11 |
November | 24.36 | 12.79 |
December | 23.70 | 10.66 |
Annual Sum or Average | 24.06 | 13.79 |
Minimum of Months | 23.25 | 9.60 |
Maximum of Months | 24.73 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 9.60 |
February | 23.08 | 11.29 |
March | 23.10 | 12.66 |
April | 22.73 | 13.68 |
May | 22.53 | 15.00 |
June | 22.55 | 15.34 |
July | 22.75 | 15.94 |
August | 23.28 | 16.62 |
September | 23.55 | 16.72 |
October | 23.37 | 15.11 |
November | 23.56 | 12.79 |
December | 23.16 | 10.66 |
Annual Sum or Average | 23.01 | 13.79 |
Minimum of Months | 22.51 | 9.60 |
Maximum of Months | 23.56 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.92 | 11.29 |
March | 22.11 | 12.66 |
April | 22.26 | 13.68 |
May | 22.33 | 15.00 |
June | 22.44 | 15.34 |
July | 22.51 | 15.94 |
August | 22.87 | 16.62 |
September | 22.79 | 16.72 |
October | 22.50 | 15.11 |
November | 22.50 | 12.79 |
December | 21.93 | 10.66 |
Annual Sum or Average | 22.33 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 22.87 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.49 | 9.60 |
February | 23.01 | 11.29 |
March | 23.02 | 12.66 |
April | 22.71 | 13.68 |
May | 22.53 | 15.00 |
June | 22.55 | 15.34 |
July | 22.66 | 15.94 |
August | 23.21 | 16.62 |
September | 23.47 | 16.72 |
October | 23.31 | 15.11 |
November | 23.52 | 12.79 |
December | 23.11 | 10.66 |
Annual Sum or Average | 22.96 | 13.79 |
Minimum of Months | 22.49 | 9.60 |
Maximum of Months | 23.52 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 9.60 |
February | 21.87 | 11.29 |
March | 22.06 | 12.66 |
April | 22.24 | 13.68 |
May | 22.30 | 15.00 |
June | 22.42 | 15.34 |
July | 22.38 | 15.94 |
August | 22.76 | 16.62 |
September | 22.65 | 16.72 |
October | 22.45 | 15.11 |
November | 22.39 | 12.79 |
December | 21.84 | 10.66 |
Annual Sum or Average | 22.26 | 13.79 |
Minimum of Months | 21.75 | 9.60 |
Maximum of Months | 22.76 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 9.60 |
February | 21.97 | 11.29 |
March | 22.18 | 12.66 |
April | 22.32 | 13.68 |
May | 22.35 | 15.00 |
June | 22.44 | 15.34 |
July | 22.43 | 15.94 |
August | 22.79 | 16.62 |
September | 22.75 | 16.72 |
October | 22.61 | 15.11 |
November | 22.69 | 12.79 |
December | 22.02 | 10.66 |
Annual Sum or Average | 22.37 | 13.79 |
Minimum of Months | 21.83 | 9.60 |
Maximum of Months | 22.79 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 9.60 |
February | 21.97 | 11.29 |
March | 22.18 | 12.66 |
April | 22.32 | 13.68 |
May | 22.35 | 15.00 |
June | 22.44 | 15.34 |
July | 22.42 | 15.94 |
August | 22.78 | 16.62 |
September | 22.73 | 16.72 |
October | 22.61 | 15.11 |
November | 22.68 | 12.79 |
December | 22.01 | 10.66 |
Annual Sum or Average | 22.36 | 13.79 |
Minimum of Months | 21.83 | 9.60 |
Maximum of Months | 22.78 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 9.60 |
February | 23.66 | 11.29 |
March | 23.49 | 12.66 |
April | 23.00 | 13.68 |
May | 22.65 | 15.00 |
June | 22.63 | 15.34 |
July | 22.75 | 15.94 |
August | 23.33 | 16.62 |
September | 23.66 | 16.72 |
October | 23.65 | 15.11 |
November | 23.97 | 12.79 |
December | 23.70 | 10.66 |
Annual Sum or Average | 23.30 | 13.79 |
Minimum of Months | 22.63 | 9.60 |
Maximum of Months | 23.97 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 9.60 |
February | 23.66 | 11.29 |
March | 23.48 | 12.66 |
April | 23.00 | 13.68 |
May | 22.65 | 15.00 |
June | 22.63 | 15.34 |
July | 22.74 | 15.94 |
August | 23.33 | 16.62 |
September | 23.66 | 16.72 |
October | 23.65 | 15.11 |
November | 23.97 | 12.79 |
December | 23.70 | 10.66 |
Annual Sum or Average | 23.29 | 13.79 |
Minimum of Months | 22.63 | 9.60 |
Maximum of Months | 23.97 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.08 | 9.60 |
February | 23.60 | 11.29 |
March | 23.77 | 12.66 |
April | 23.72 | 13.68 |
May | 23.70 | 15.00 |
June | 23.75 | 15.34 |
July | 23.96 | 15.94 |
August | 24.41 | 16.62 |
September | 24.53 | 16.72 |
October | 24.26 | 15.11 |
November | 24.18 | 12.79 |
December | 23.54 | 10.66 |
Annual Sum or Average | 23.87 | 13.79 |
Minimum of Months | 23.08 | 9.60 |
Maximum of Months | 24.53 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.44 | 9.60 |
February | 22.96 | 11.29 |
March | 22.98 | 12.66 |
April | 22.63 | 13.68 |
May | 22.46 | 15.00 |
June | 22.48 | 15.34 |
July | 22.65 | 15.94 |
August | 23.18 | 16.62 |
September | 23.45 | 16.72 |
October | 23.26 | 15.11 |
November | 23.47 | 12.79 |
December | 23.07 | 10.66 |
Annual Sum or Average | 22.92 | 13.79 |
Minimum of Months | 22.44 | 9.60 |
Maximum of Months | 23.47 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 9.60 |
February | 21.88 | 11.29 |
March | 22.06 | 12.66 |
April | 22.21 | 13.68 |
May | 22.28 | 15.00 |
June | 22.39 | 15.34 |
July | 22.42 | 15.94 |
August | 22.79 | 16.62 |
September | 22.70 | 16.72 |
October | 22.44 | 15.11 |
November | 22.42 | 12.79 |
December | 21.90 | 10.66 |
Annual Sum or Average | 22.27 | 13.79 |
Minimum of Months | 21.77 | 9.60 |
Maximum of Months | 22.79 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.42 | 9.60 |
February | 22.89 | 11.29 |
March | 22.92 | 12.66 |
April | 22.62 | 13.68 |
May | 22.46 | 15.00 |
June | 22.50 | 15.34 |
July | 22.57 | 15.94 |
August | 23.11 | 16.62 |
September | 23.37 | 16.72 |
October | 23.21 | 15.11 |
November | 23.42 | 12.79 |
December | 23.02 | 10.66 |
Annual Sum or Average | 22.87 | 13.79 |
Minimum of Months | 22.42 | 9.60 |
Maximum of Months | 23.42 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 9.60 |
February | 21.85 | 11.29 |
March | 22.02 | 12.66 |
April | 22.19 | 13.68 |
May | 22.25 | 15.00 |
June | 22.38 | 15.34 |
July | 22.31 | 15.94 |
August | 22.69 | 16.62 |
September | 22.58 | 16.72 |
October | 22.39 | 15.11 |
November | 22.32 | 12.79 |
December | 21.82 | 10.66 |
Annual Sum or Average | 22.21 | 13.79 |
Minimum of Months | 21.74 | 9.60 |
Maximum of Months | 22.69 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 9.60 |
February | 21.92 | 11.29 |
March | 22.13 | 12.66 |
April | 22.26 | 13.68 |
May | 22.30 | 15.00 |
June | 22.39 | 15.34 |
July | 22.37 | 15.94 |
August | 22.72 | 16.62 |
September | 22.68 | 16.72 |
October | 22.54 | 15.11 |
November | 22.60 | 12.79 |
December | 21.97 | 10.66 |
Annual Sum or Average | 22.31 | 13.79 |
Minimum of Months | 21.81 | 9.60 |
Maximum of Months | 22.72 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 9.60 |
February | 21.92 | 11.29 |
March | 22.12 | 12.66 |
April | 22.26 | 13.68 |
May | 22.30 | 15.00 |
June | 22.39 | 15.34 |
July | 22.36 | 15.94 |
August | 22.71 | 16.62 |
September | 22.66 | 16.72 |
October | 22.54 | 15.11 |
November | 22.59 | 12.79 |
December | 21.96 | 10.66 |
Annual Sum or Average | 22.30 | 13.79 |
Minimum of Months | 21.80 | 9.60 |
Maximum of Months | 22.71 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 9.60 |
February | 23.55 | 11.29 |
March | 23.38 | 12.66 |
April | 22.89 | 13.68 |
May | 22.58 | 15.00 |
June | 22.56 | 15.34 |
July | 22.67 | 15.94 |
August | 23.24 | 16.62 |
September | 23.57 | 16.72 |
October | 23.56 | 15.11 |
November | 23.90 | 12.79 |
December | 23.61 | 10.66 |
Annual Sum or Average | 23.21 | 13.79 |
Minimum of Months | 22.56 | 9.60 |
Maximum of Months | 23.90 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 9.60 |
February | 23.54 | 11.29 |
March | 23.38 | 12.66 |
April | 22.89 | 13.68 |
May | 22.58 | 15.00 |
June | 22.56 | 15.34 |
July | 22.66 | 15.94 |
August | 23.24 | 16.62 |
September | 23.57 | 16.72 |
October | 23.55 | 15.11 |
November | 23.90 | 12.79 |
December | 23.61 | 10.66 |
Annual Sum or Average | 23.20 | 13.79 |
Minimum of Months | 22.56 | 9.60 |
Maximum of Months | 23.90 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 9.60 |
February | 23.49 | 11.29 |
March | 23.65 | 12.66 |
April | 23.61 | 13.68 |
May | 23.61 | 15.00 |
June | 23.67 | 15.34 |
July | 23.86 | 15.94 |
August | 24.30 | 16.62 |
September | 24.42 | 16.72 |
October | 24.14 | 15.11 |
November | 24.06 | 12.79 |
December | 23.42 | 10.66 |
Annual Sum or Average | 23.77 | 13.79 |
Minimum of Months | 22.98 | 9.60 |
Maximum of Months | 24.42 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 9.60 |
February | 22.82 | 11.29 |
March | 22.87 | 12.66 |
April | 22.55 | 13.68 |
May | 22.41 | 15.00 |
June | 22.45 | 15.34 |
July | 22.59 | 15.94 |
August | 23.10 | 16.62 |
September | 23.36 | 16.72 |
October | 23.14 | 15.11 |
November | 23.34 | 12.79 |
December | 22.93 | 10.66 |
Annual Sum or Average | 22.83 | 13.79 |
Minimum of Months | 22.35 | 9.60 |
Maximum of Months | 23.36 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 9.60 |
February | 21.86 | 11.29 |
March | 22.02 | 12.66 |
April | 22.17 | 13.68 |
May | 22.25 | 15.00 |
June | 22.37 | 15.34 |
July | 22.38 | 15.94 |
August | 22.73 | 16.62 |
September | 22.64 | 16.72 |
October | 22.38 | 15.11 |
November | 22.34 | 12.79 |
December | 21.87 | 10.66 |
Annual Sum or Average | 22.23 | 13.79 |
Minimum of Months | 21.76 | 9.60 |
Maximum of Months | 22.73 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 9.60 |
February | 22.76 | 11.29 |
March | 22.81 | 12.66 |
April | 22.55 | 13.68 |
May | 22.42 | 15.00 |
June | 22.47 | 15.34 |
July | 22.52 | 15.94 |
August | 23.04 | 16.62 |
September | 23.27 | 16.72 |
October | 23.09 | 15.11 |
November | 23.30 | 12.79 |
December | 22.89 | 10.66 |
Annual Sum or Average | 22.79 | 13.79 |
Minimum of Months | 22.33 | 9.60 |
Maximum of Months | 23.30 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 9.60 |
February | 21.83 | 11.29 |
March | 21.99 | 12.66 |
April | 22.16 | 13.68 |
May | 22.22 | 15.00 |
June | 22.35 | 15.34 |
July | 22.28 | 15.94 |
August | 22.63 | 16.62 |
September | 22.52 | 16.72 |
October | 22.33 | 15.11 |
November | 22.24 | 12.79 |
December | 21.79 | 10.66 |
Annual Sum or Average | 22.17 | 13.79 |
Minimum of Months | 21.73 | 9.60 |
Maximum of Months | 22.63 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.88 | 11.29 |
March | 22.08 | 12.66 |
April | 22.22 | 13.68 |
May | 22.28 | 15.00 |
June | 22.38 | 15.34 |
July | 22.34 | 15.94 |
August | 22.68 | 16.62 |
September | 22.63 | 16.72 |
October | 22.48 | 15.11 |
November | 22.49 | 12.79 |
December | 21.91 | 10.66 |
Annual Sum or Average | 22.26 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 22.68 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.88 | 11.29 |
March | 22.07 | 12.66 |
April | 22.22 | 13.68 |
May | 22.27 | 15.00 |
June | 22.37 | 15.34 |
July | 22.33 | 15.94 |
August | 22.67 | 16.62 |
September | 22.62 | 16.72 |
October | 22.47 | 15.11 |
November | 22.48 | 12.79 |
December | 21.91 | 10.66 |
Annual Sum or Average | 22.26 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 22.67 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 9.60 |
February | 23.37 | 11.29 |
March | 23.25 | 12.66 |
April | 22.80 | 13.68 |
May | 22.53 | 15.00 |
June | 22.53 | 15.34 |
July | 22.63 | 15.94 |
August | 23.17 | 16.62 |
September | 23.49 | 16.72 |
October | 23.44 | 15.11 |
November | 23.77 | 12.79 |
December | 23.45 | 10.66 |
Annual Sum or Average | 23.10 | 13.79 |
Minimum of Months | 22.53 | 9.60 |
Maximum of Months | 23.77 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 9.60 |
February | 23.36 | 11.29 |
March | 23.24 | 12.66 |
April | 22.80 | 13.68 |
May | 22.53 | 15.00 |
June | 22.53 | 15.34 |
July | 22.62 | 15.94 |
August | 23.17 | 16.62 |
September | 23.48 | 16.72 |
October | 23.44 | 15.11 |
November | 23.77 | 12.79 |
December | 23.44 | 10.66 |
Annual Sum or Average | 23.10 | 13.79 |
Minimum of Months | 22.53 | 9.60 |
Maximum of Months | 23.77 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 9.60 |
February | 23.35 | 11.29 |
March | 23.54 | 12.66 |
April | 23.54 | 13.68 |
May | 23.58 | 15.00 |
June | 23.66 | 15.34 |
July | 23.83 | 15.94 |
August | 24.25 | 16.62 |
September | 24.36 | 16.72 |
October | 24.03 | 15.11 |
November | 23.91 | 12.79 |
December | 23.26 | 10.66 |
Annual Sum or Average | 23.68 | 13.79 |
Minimum of Months | 22.83 | 9.60 |
Maximum of Months | 24.36 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 9.60 |
February | 22.59 | 11.29 |
March | 22.65 | 12.66 |
April | 22.50 | 13.68 |
May | 22.37 | 15.00 |
June | 22.42 | 15.34 |
July | 22.48 | 15.94 |
August | 22.86 | 16.62 |
September | 23.04 | 16.72 |
October | 22.84 | 15.11 |
November | 22.98 | 12.79 |
December | 22.64 | 10.66 |
Annual Sum or Average | 22.64 | 13.79 |
Minimum of Months | 22.26 | 9.60 |
Maximum of Months | 23.04 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 9.60 |
February | 21.95 | 11.29 |
March | 22.07 | 12.66 |
April | 22.18 | 13.68 |
May | 22.23 | 15.00 |
June | 22.34 | 15.34 |
July | 22.31 | 15.94 |
August | 22.56 | 16.62 |
September | 22.50 | 16.72 |
October | 22.27 | 15.11 |
November | 22.30 | 12.79 |
December | 21.93 | 10.66 |
Annual Sum or Average | 22.20 | 13.79 |
Minimum of Months | 21.79 | 9.60 |
Maximum of Months | 22.56 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 9.60 |
February | 22.56 | 11.29 |
March | 22.61 | 12.66 |
April | 22.49 | 13.68 |
May | 22.38 | 15.00 |
June | 22.43 | 15.34 |
July | 22.44 | 15.94 |
August | 22.81 | 16.62 |
September | 22.97 | 16.72 |
October | 22.80 | 15.11 |
November | 22.94 | 12.79 |
December | 22.62 | 10.66 |
Annual Sum or Average | 22.61 | 13.79 |
Minimum of Months | 22.25 | 9.60 |
Maximum of Months | 22.97 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 9.60 |
February | 21.91 | 11.29 |
March | 22.06 | 12.66 |
April | 22.18 | 13.68 |
May | 22.22 | 15.00 |
June | 22.34 | 15.34 |
July | 22.25 | 15.94 |
August | 22.50 | 16.62 |
September | 22.42 | 16.72 |
October | 22.26 | 15.11 |
November | 22.23 | 12.79 |
December | 21.83 | 10.66 |
Annual Sum or Average | 22.16 | 13.79 |
Minimum of Months | 21.75 | 9.60 |
Maximum of Months | 22.50 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.93 | 11.29 |
March | 22.07 | 12.66 |
April | 22.20 | 13.68 |
May | 22.24 | 15.00 |
June | 22.34 | 15.34 |
July | 22.27 | 15.94 |
August | 22.55 | 16.62 |
September | 22.50 | 16.72 |
October | 22.33 | 15.11 |
November | 22.36 | 12.79 |
December | 21.91 | 10.66 |
Annual Sum or Average | 22.21 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 22.55 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 21.93 | 11.29 |
March | 22.07 | 12.66 |
April | 22.20 | 13.68 |
May | 22.23 | 15.00 |
June | 22.34 | 15.34 |
July | 22.26 | 15.94 |
August | 22.54 | 16.62 |
September | 22.49 | 16.72 |
October | 22.33 | 15.11 |
November | 22.35 | 12.79 |
December | 21.90 | 10.66 |
Annual Sum or Average | 22.20 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 22.54 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.50 | 9.60 |
February | 22.91 | 11.29 |
March | 22.93 | 12.66 |
April | 22.67 | 13.68 |
May | 22.47 | 15.00 |
June | 22.48 | 15.34 |
July | 22.54 | 15.94 |
August | 23.00 | 16.62 |
September | 23.25 | 16.72 |
October | 23.11 | 15.11 |
November | 23.36 | 12.79 |
December | 22.97 | 10.66 |
Annual Sum or Average | 22.85 | 13.79 |
Minimum of Months | 22.47 | 9.60 |
Maximum of Months | 23.36 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.50 | 9.60 |
February | 22.91 | 11.29 |
March | 22.93 | 12.66 |
April | 22.67 | 13.68 |
May | 22.47 | 15.00 |
June | 22.48 | 15.34 |
July | 22.54 | 15.94 |
August | 22.99 | 16.62 |
September | 23.24 | 16.72 |
October | 23.11 | 15.11 |
November | 23.35 | 12.79 |
December | 22.97 | 10.66 |
Annual Sum or Average | 22.85 | 13.79 |
Minimum of Months | 22.47 | 9.60 |
Maximum of Months | 23.35 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:12:07
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 9.60 |
February | 23.59 | 11.29 |
March | 23.91 | 12.66 |
April | 24.03 | 13.68 |
May | 24.14 | 15.00 |
June | 24.27 | 15.34 |
July | 24.42 | 15.94 |
August | 24.79 | 16.62 |
September | 24.85 | 16.72 |
October | 24.37 | 15.11 |
November | 24.12 | 12.79 |
December | 23.36 | 10.66 |
Annual Sum or Average | 24.07 | 13.79 |
Minimum of Months | 22.96 | 9.60 |
Maximum of Months | 24.85 | 16.72 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:07
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.196668E+12 | 112332.369 | 31-JAN-18:15 | 13120.457 | 57042.023 | 15015.237 | 13470.532 | 0.000 | 10364.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.173052E+12 | 106111.159 | 13-FEB-18:45 | 13120.457 | 57042.023 | 15015.237 | 7249.125 | 0.000 | 10364.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.190329E+12 | 112436.715 | 13-MAR-16:15 | 11327.174 | 57142.088 | 15015.237 | 0.000 | 24733.254 | 0.000 | 1332.309 | 891.457 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.183387E+12 | 130720.933 | 02-APR-17:15 | 13120.457 | 57042.023 | 15015.237 | 0.000 | 40920.865 | 0.000 | 1332.309 | 1302.231 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.188168E+12 | 129216.718 | 17-MAY-19:00 | 14401.373 | 49889.926 | 15015.237 | 36572.570 | 0.000 | 10364.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.183256E+12 | 135664.155 | 30-JUN-16:45 | 11327.174 | 57142.088 | 15015.237 | 0.000 | 47332.163 | 0.000 | 1332.309 | 1520.026 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.183675E+12 | 130110.870 | 09-JUL-19:30 | 14401.373 | 49889.926 | 15015.237 | 37466.721 | 0.000 | 10364.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.188618E+12 | 123149.851 | 03-AUG-16:15 | 11327.174 | 57142.088 | 15015.237 | 0.000 | 34925.401 | 0.000 | 1332.309 | 1412.446 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.185118E+12 | 131223.180 | 11-SEP-18:15 | 14401.373 | 51749.961 | 15015.237 | 46963.402 | 0.000 | 0.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.192143E+12 | 130309.391 | 09-OCT-17:15 | 13120.457 | 57042.023 | 15015.237 | 41811.553 | 0.000 | 0.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.187267E+12 | 134468.198 | 20-NOV-18:00 | 13120.457 | 57042.023 | 15015.237 | 35606.163 | 0.000 | 10364.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.195594E+12 | 104449.334 | 29-DEC-18:00 | 13120.457 | 57042.023 | 15015.237 | 0.000 | 5373.330 | 10364.000 | 1332.309 | 213.970 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.224728E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.173052E+12 | 104449.334 | 11327.174 | 49889.926 | 15015.237 | 0.000 | 0.000 | 0.000 | 1332.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.196668E+12 | 135664.155 | 14401.373 | 57142.088 | 15015.237 | 46963.402 | 47332.163 | 10364.000 | 1332.309 | 1520.026 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:12:07
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.126285E+12 | 145527.951 | 26-JAN-08:00 | 0.000 | 0.000 | 0.000 | 145527.951 | 76075.582 | 76075.582 | 69452.369 |
February | 0.952011E+11 | 102727.333 | 02-FEB-08:30 | 0.000 | 0.000 | 0.000 | 102727.333 | 76213.731 | 76213.731 | 26513.603 |
March | 0.106794E+12 | 141065.923 | 12-MAR-08:30 | 0.000 | 0.000 | 0.000 | 141065.923 | 72614.208 | 72614.208 | 68451.715 |
April | 0.107240E+12 | 167510.962 | 25-APR-15:00 | 0.000 | 0.000 | 0.000 | 167510.962 | 48233.645 | 48233.645 | 119277.317 |
May | 0.111409E+12 | 187090.971 | 17-MAY-19:00 | 0.000 | 0.000 | 0.000 | 187090.971 | 68877.576 | 68877.576 | 118213.395 |
June | 0.100885E+12 | 160664.881 | 09-JUN-17:00 | 0.000 | 0.000 | 0.000 | 160664.881 | 71293.915 | 71293.915 | 89370.966 |
July | 0.980031E+11 | 167559.444 | 09-JUL-19:30 | 0.000 | 0.000 | 0.000 | 167559.444 | 57779.494 | 57779.494 | 109779.949 |
August | 0.916017E+11 | 134522.286 | 16-AUG-17:15 | 0.000 | 0.000 | 0.000 | 134522.286 | 69092.417 | 69092.417 | 65429.869 |
September | 0.891593E+11 | 169766.774 | 11-SEP-17:00 | 0.000 | 0.000 | 0.000 | 169766.774 | 70898.170 | 70898.170 | 98868.604 |
October | 0.975194E+11 | 157117.463 | 03-OCT-09:00 | 0.000 | 0.000 | 0.000 | 157117.463 | 53194.808 | 53194.808 | 103922.655 |
November | 0.934100E+11 | 142561.233 | 20-NOV-19:30 | 0.000 | 0.000 | 0.000 | 142561.233 | 71106.771 | 71106.771 | 71454.462 |
December | 0.110800E+12 | 157345.229 | 22-DEC-06:30 | 0.000 | 0.000 | 0.000 | 157345.229 | 65485.906 | 65485.906 | 91859.323 |
Annual Sum or Average | 0.122831E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.891593E+11 | 102727.333 | 0.000 | 0.000 | 0.000 | 102727.333 | 48233.645 | 48233.645 | 26513.603 | |
Maximum of Months | 0.126285E+12 | 187090.971 | 0.000 | 0.000 | 0.000 | 187090.971 | 76213.731 | 76213.731 | 119277.317 |