Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650
Simulation Timestamp: 2015-09-09 19:00:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4297.04 | 548.34 | 608.66 |
Net Site Energy | 4297.04 | 548.34 | 608.66 |
Total Source Energy | 10931.76 | 1394.98 | 1548.43 |
Net Source Energy | 10931.76 | 1394.98 | 1548.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 70.42 | 194.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 496.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 740.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.74 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1090.21 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3011.89 | 1285.16 | 0.00 | 0.00 | 0.00 | 6475.26 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 194.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 70.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 496.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 740.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 54.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 17.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.74 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1090.21 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.33 | 182.04 | 0.00 | 0.00 | 0.00 | 0.92 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 426.62 | 182.04 | 0.00 | 0.00 | 0.00 | 0.92 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.97 | 164.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 384.34 | 164.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3011.89 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3011.89 | 100.00 |
Total On-Site and Utility Electric Sources | 3011.89 | 100.00 |
Total Electricity End Uses | 3011.89 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6475.26 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6475.26 | 100.00 |
Total Water End Uses | 6475.26 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 105.00 |
Time Setpoint Not Met During Occupied Cooling | 525.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1341.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:59 |
RunPeriod | Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650 |
Weather File | Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-19:15 | 17-JAN-08:15 | - | - | - | 21-JUL-17:15 |
Heating | 0.00 | 150090.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60361.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23476.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1741.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1886.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 79368.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 163762.87 | 229458.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 150090.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 60361.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 11484.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2917.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23476.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1741.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1886.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 79368.04 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 223.01 | 211.32 | 0.00 | 0.00 | 0.00 |
Cooling | 1571.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 515.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2344.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 172.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1181.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9538.65 | 1393.11 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 31.59 | 29.93 | 0.00 | 0.00 | 0.00 |
Cooling | 222.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 332.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 167.39 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1351.10 | 197.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 31.59 | 29.93 | 0.00 | 0.00 | 0.00 |
Cooling | 222.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 332.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 167.39 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1351.10 | 197.33 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.48_SHGC_0.40 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.48_SHGC_0.40 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.48_SHGC_0.40 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 423.59 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 726.80 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.70 | 83.70 | 162.84 | |
Exterior Lighting Total | 10364.00 | 162.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 245374.47 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 196299.58 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3205.13 | 2086.17 | 1118.97 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3136.29 | 2042.61 | 1093.68 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4571.65 | 2982.58 | 1589.07 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2235.31 | 1482.58 | 752.73 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1610.05 | 1060.80 | 549.24 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1585.74 | 1045.39 | 540.35 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1790.21 | 1157.32 | 632.90 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 1874.97 | 1212.83 | 662.14 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4083.63 | 2661.66 | 1421.97 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3968.98 | 2588.31 | 1380.67 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3709.07 | 2413.66 | 1295.41 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2955.28 | 1957.90 | 997.37 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2120.03 | 1393.05 | 726.98 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2100.22 | 1380.48 | 719.74 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2348.56 | 1523.76 | 824.80 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2379.83 | 1543.73 | 836.10 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4099.50 | 2681.69 | 1417.81 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3992.78 | 2613.32 | 1379.47 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3450.55 | 2258.26 | 1192.29 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2994.18 | 1992.19 | 1001.99 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2162.96 | 1425.86 | 737.10 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2143.35 | 1413.40 | 729.95 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2398.22 | 1561.04 | 837.18 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2411.72 | 1569.66 | 842.06 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4115.74 | 2699.43 | 1416.31 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4016.31 | 2634.80 | 1381.52 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3447.95 | 2263.63 | 1184.32 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3006.86 | 2007.32 | 999.54 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2184.05 | 1443.42 | 740.64 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2164.55 | 1431.01 | 733.53 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2421.46 | 1580.05 | 841.40 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2432.36 | 1587.00 | 845.35 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4158.53 | 2732.71 | 1425.82 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4061.50 | 2669.53 | 1391.97 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3495.15 | 2299.51 | 1195.63 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3046.55 | 2038.40 | 1008.15 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2231.85 | 1479.05 | 752.80 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2212.59 | 1466.76 | 745.83 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2467.66 | 1613.00 | 854.65 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2478.17 | 1619.71 | 858.46 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4118.48 | 2712.30 | 1406.17 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4021.15 | 2648.90 | 1372.24 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3463.15 | 2283.91 | 1179.25 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3003.59 | 2015.76 | 987.83 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2196.01 | 1459.13 | 736.89 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2176.92 | 1446.93 | 729.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2433.36 | 1593.91 | 839.45 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2443.82 | 1600.59 | 843.23 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4108.10 | 2710.17 | 1397.93 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4011.78 | 2647.38 | 1364.40 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3459.59 | 2285.87 | 1173.72 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3006.60 | 2018.43 | 988.17 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2189.24 | 1457.34 | 731.90 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2170.27 | 1445.21 | 725.06 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2427.05 | 1592.38 | 834.66 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2437.49 | 1599.05 | 838.44 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4116.29 | 2719.41 | 1396.88 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4020.82 | 2657.12 | 1363.71 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.41 | 2297.88 | 1174.53 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3012.72 | 2026.10 | 986.62 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2200.53 | 1466.80 | 733.73 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2181.69 | 1454.75 | 726.94 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2437.62 | 1601.42 | 836.21 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2448.08 | 1608.09 | 839.99 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4261.51 | 2815.74 | 1445.77 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4163.87 | 2751.97 | 1411.91 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3585.82 | 2372.82 | 1213.00 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3068.81 | 2065.52 | 1003.29 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2326.72 | 1549.40 | 777.32 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2307.77 | 1537.29 | 770.49 | 0.67 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2531.51 | 1663.57 | 867.93 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2541.48 | 1669.94 | 871.54 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5311.88 | 3485.44 | 1826.44 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5134.82 | 3374.01 | 1760.81 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4586.60 | 3017.05 | 1569.55 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4053.30 | 2675.11 | 1378.19 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3150.60 | 2061.78 | 1088.82 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3147.08 | 2059.48 | 1087.60 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3656.71 | 2384.97 | 1271.74 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3665.00 | 2390.23 | 1274.77 | 0.65 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3205.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3136.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4571.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2235.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1610.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1585.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1790.21 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 1874.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4083.63 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3968.98 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3709.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2955.28 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2120.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2100.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2348.56 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2379.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4099.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 3992.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3450.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 2994.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2162.96 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2143.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2398.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2411.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4115.74 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4016.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3447.95 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3006.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2184.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2164.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2421.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2432.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4158.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4061.50 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3495.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3046.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2231.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2212.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2467.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2478.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4118.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4021.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3463.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3003.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2196.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2176.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2433.36 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2443.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4108.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4011.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3459.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3006.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2189.24 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2170.27 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2427.05 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2437.49 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4116.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4020.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3012.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2200.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2181.69 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2437.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2448.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4261.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4163.87 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3585.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3068.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2326.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2307.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2531.51 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2541.48 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5311.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5134.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4586.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4053.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3150.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3147.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3656.71 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3665.00 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 2756.67 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 2757.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 3460.54 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 2757.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2051.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2051.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2047.88 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2054.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 2735.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 2733.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 2754.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 2733.39 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 1854.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 1854.16 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 1859.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 1860.51 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 2759.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 2759.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 2761.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 2759.94 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 1835.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 1835.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 1835.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 1836.18 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 2823.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 2826.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 2824.06 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 2826.48 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 1866.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 1866.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 1864.05 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 1864.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 2864.82 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 2867.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 2864.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 2867.93 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 1879.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 1879.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 1877.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 1877.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 2960.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 2965.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 2960.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 2965.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 1951.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 1951.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 1946.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 1946.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 3029.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 3035.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 3029.36 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 3035.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 1998.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 1998.43 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 1992.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 1992.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 3100.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 3106.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 3100.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 3106.95 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2050.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2050.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2044.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2044.75 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 3289.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 3294.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 3289.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 3294.09 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2212.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2212.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2207.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2207.63 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 3902.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 3913.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 3902.78 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 3913.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 2870.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 2870.02 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 2856.07 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 2856.07 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 303.98 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.33 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 435.55 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.78 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 152.66 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.36 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.32 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.83 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 390.99 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 380.85 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 350.77 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 288.82 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 202.70 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 200.82 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.40 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.38 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 394.52 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 385.13 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 328.02 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.45 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 207.90 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 206.04 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 222.26 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 223.55 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 397.57 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 388.26 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 329.20 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.09 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.74 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 208.89 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.32 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 226.36 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 402.88 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 393.78 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 334.88 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 302.05 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 215.73 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 213.89 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.42 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 231.42 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 400.09 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 390.96 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 332.80 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.90 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.90 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 211.07 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 227.72 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 228.72 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 400.01 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 390.97 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 333.32 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.70 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.77 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 210.95 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 227.62 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 228.62 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 401.61 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 392.64 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 335.32 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 300.04 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 214.30 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 212.50 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 229.09 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.09 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 416.24 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 407.04 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 346.46 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 306.14 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 226.77 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 224.96 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 238.49 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 239.44 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 515.11 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 499.19 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 443.45 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 391.93 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 298.16 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.81 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 346.52 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 347.31 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0053 | 1704.37 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2292.11 | 2750.53 | 0.218 | 0.262 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
G NW APARTMENT | 2249.44 | 2699.33 | 0.214 | 0.257 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
OFFICE | 3284.21 | 3941.05 | 0.313 | 0.375 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 32.33 | 0.00565 |
G NE APARTMENT | 1634.58 | 1961.49 | 0.156 | 0.187 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
G N1 APARTMENT | 1151.06 | 1381.28 | 0.110 | 0.132 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
G N2 APARTMENT | 1133.75 | 1360.50 | 0.108 | 0.130 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
G S1 APARTMENT | 1216.40 | 1459.69 | 0.116 | 0.139 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
G S2 APARTMENT | 1280.52 | 1536.62 | 0.122 | 0.146 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F2 SW APARTMENT | 2948.19 | 3537.83 | 0.281 | 0.337 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F2 NW APARTMENT | 2871.74 | 3446.09 | 0.273 | 0.328 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F2 SE APARTMENT | 2644.93 | 3173.92 | 0.252 | 0.302 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F2 NE APARTMENT | 2177.79 | 2613.34 | 0.207 | 0.249 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F2 N1 APARTMENT | 1528.39 | 1834.07 | 0.146 | 0.175 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F2 N2 APARTMENT | 1514.23 | 1817.08 | 0.144 | 0.173 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F2 S1 APARTMENT | 1631.72 | 1958.06 | 0.155 | 0.186 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F2 S2 APARTMENT | 1654.17 | 1985.01 | 0.157 | 0.189 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F3 SW APARTMENT | 2974.84 | 3569.81 | 0.283 | 0.340 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F3 NW APARTMENT | 2903.99 | 3484.79 | 0.276 | 0.332 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 32.20 | 0.00565 |
F3 SE APARTMENT | 2473.46 | 2968.15 | 0.235 | 0.283 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F3 NE APARTMENT | 2220.30 | 2664.36 | 0.211 | 0.254 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F3 N1 APARTMENT | 1567.60 | 1881.12 | 0.149 | 0.179 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F3 N2 APARTMENT | 1553.56 | 1864.27 | 0.148 | 0.177 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F3 S1 APARTMENT | 1675.91 | 2011.09 | 0.160 | 0.191 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F3 S2 APARTMENT | 1685.59 | 2022.71 | 0.160 | 0.193 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F4 SW APARTMENT | 2997.87 | 3597.45 | 0.285 | 0.342 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F4 NW APARTMENT | 2927.62 | 3513.15 | 0.279 | 0.334 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
F4 SE APARTMENT | 2482.35 | 2978.82 | 0.236 | 0.284 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F4 NE APARTMENT | 2240.20 | 2688.24 | 0.213 | 0.256 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F4 N1 APARTMENT | 1589.05 | 1906.86 | 0.151 | 0.182 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F4 N2 APARTMENT | 1575.07 | 1890.08 | 0.150 | 0.180 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
F4 S1 APARTMENT | 1698.98 | 2038.77 | 0.162 | 0.194 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F4 S2 APARTMENT | 1706.80 | 2048.15 | 0.162 | 0.195 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
M SW APARTMENT | 3037.90 | 3645.49 | 0.289 | 0.347 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
M NW APARTMENT | 2969.25 | 3563.10 | 0.283 | 0.339 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
M SE APARTMENT | 2525.17 | 3030.20 | 0.240 | 0.288 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
M NE APARTMENT | 2277.62 | 2733.14 | 0.217 | 0.260 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
M N1 APARTMENT | 1626.62 | 1951.95 | 0.155 | 0.186 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
M N2 APARTMENT | 1612.75 | 1935.30 | 0.154 | 0.184 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
M S1 APARTMENT | 1737.45 | 2084.94 | 0.165 | 0.198 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
M S2 APARTMENT | 1744.99 | 2093.99 | 0.166 | 0.199 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F6 SW APARTMENT | 3016.92 | 3620.31 | 0.287 | 0.345 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F6 NW APARTMENT | 2948.01 | 3537.61 | 0.281 | 0.337 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
F6 SE APARTMENT | 2509.49 | 3011.39 | 0.239 | 0.287 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F6 NE APARTMENT | 2253.92 | 2704.70 | 0.215 | 0.257 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.98 | 0.00565 |
F6 N1 APARTMENT | 1605.31 | 1926.38 | 0.153 | 0.183 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F6 N2 APARTMENT | 1591.54 | 1909.85 | 0.152 | 0.182 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F6 S1 APARTMENT | 1717.10 | 2060.51 | 0.163 | 0.196 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F6 S2 APARTMENT | 1724.61 | 2069.53 | 0.164 | 0.197 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F7 SW APARTMENT | 3016.32 | 3619.58 | 0.287 | 0.345 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F7 NW APARTMENT | 2948.08 | 3537.69 | 0.281 | 0.337 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
F7 SE APARTMENT | 2513.41 | 3016.10 | 0.239 | 0.287 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F7 NE APARTMENT | 2252.36 | 2702.83 | 0.214 | 0.257 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.49 | 0.00565 |
F7 N1 APARTMENT | 1604.30 | 1925.16 | 0.153 | 0.183 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F7 N2 APARTMENT | 1590.60 | 1908.73 | 0.151 | 0.182 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F7 S1 APARTMENT | 1716.38 | 2059.65 | 0.163 | 0.196 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F7 S2 APARTMENT | 1723.88 | 2068.65 | 0.164 | 0.197 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F8 SW APARTMENT | 3028.37 | 3634.05 | 0.288 | 0.346 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F8 NW APARTMENT | 2960.67 | 3552.81 | 0.282 | 0.338 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
F8 SE APARTMENT | 2528.49 | 3034.19 | 0.241 | 0.289 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
F8 NE APARTMENT | 2262.52 | 2715.02 | 0.215 | 0.258 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.49 | 0.00565 |
F8 N1 APARTMENT | 1615.88 | 1939.05 | 0.154 | 0.185 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F8 N2 APARTMENT | 1602.27 | 1922.72 | 0.153 | 0.183 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F8 S1 APARTMENT | 1727.46 | 2072.95 | 0.164 | 0.197 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F8 S2 APARTMENT | 1734.97 | 2081.96 | 0.165 | 0.198 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F9 SW APARTMENT | 3138.72 | 3766.46 | 0.299 | 0.359 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
F9 NW APARTMENT | 3069.31 | 3683.17 | 0.292 | 0.351 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.54 | 0.00565 |
F9 SE APARTMENT | 2612.55 | 3135.06 | 0.249 | 0.298 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
F9 NE APARTMENT | 2308.50 | 2770.20 | 0.220 | 0.264 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.49 | 0.00565 |
F9 N1 APARTMENT | 1709.93 | 2051.92 | 0.163 | 0.195 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F9 N2 APARTMENT | 1696.24 | 2035.49 | 0.161 | 0.194 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
F9 S1 APARTMENT | 1798.31 | 2157.97 | 0.171 | 0.205 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 35.10 | 0.00565 |
F9 S2 APARTMENT | 1805.47 | 2166.57 | 0.172 | 0.206 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 35.10 | 0.00565 |
T SW APARTMENT | 3884.29 | 4661.15 | 0.370 | 0.444 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 34.02 | 0.00565 |
T NW APARTMENT | 3764.25 | 4517.10 | 0.358 | 0.430 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 33.48 | 0.00565 |
T SE APARTMENT | 3343.92 | 4012.70 | 0.318 | 0.382 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
T NE APARTMENT | 2955.44 | 3546.53 | 0.281 | 0.338 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
T N1 APARTMENT | 2248.24 | 2697.89 | 0.214 | 0.257 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
T N2 APARTMENT | 2245.64 | 2694.76 | 0.214 | 0.257 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
T S1 APARTMENT | 2612.92 | 3135.50 | 0.249 | 0.299 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
T S2 APARTMENT | 2618.84 | 3142.61 | 0.249 | 0.299 | ALBUQUERQUE INTL ARPT ISIS ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1684.68 | 2021.62 | 0.091 | 0.109 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G NW APARTMENT | 1685.03 | 2022.04 | 0.091 | 0.109 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
OFFICE | 1977.23 | 2372.68 | 0.107 | 0.128 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -7.90 | 0.00234 |
G NE APARTMENT | 1685.03 | 2022.04 | 0.091 | 0.109 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G N1 APARTMENT | 1088.63 | 1306.36 | 0.059 | 0.071 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G N2 APARTMENT | 1088.63 | 1306.36 | 0.059 | 0.071 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G S1 APARTMENT | 1085.28 | 1302.34 | 0.059 | 0.070 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
G S2 APARTMENT | 1090.60 | 1308.72 | 0.059 | 0.071 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
F2 SW APARTMENT | 1667.05 | 2000.46 | 0.090 | 0.108 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 NW APARTMENT | 1665.02 | 1998.03 | 0.090 | 0.108 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 SE APARTMENT | 1682.87 | 2019.45 | 0.091 | 0.109 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 NE APARTMENT | 1665.02 | 1998.03 | 0.090 | 0.108 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 N1 APARTMENT | 921.48 | 1105.78 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 N2 APARTMENT | 921.48 | 1105.78 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 S1 APARTMENT | 925.81 | 1110.97 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F2 S2 APARTMENT | 926.85 | 1112.22 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 SW APARTMENT | 1687.03 | 2024.44 | 0.091 | 0.110 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 NW APARTMENT | 1687.48 | 2024.98 | 0.091 | 0.110 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 SE APARTMENT | 1688.78 | 2026.54 | 0.091 | 0.110 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 NE APARTMENT | 1687.48 | 2024.98 | 0.091 | 0.110 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 N1 APARTMENT | 905.95 | 1087.14 | 0.049 | 0.059 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 N2 APARTMENT | 905.95 | 1087.14 | 0.049 | 0.059 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 S1 APARTMENT | 906.12 | 1087.35 | 0.049 | 0.059 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F3 S2 APARTMENT | 906.28 | 1087.54 | 0.049 | 0.059 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 SW APARTMENT | 1741.53 | 2089.83 | 0.094 | 0.113 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 NW APARTMENT | 1743.75 | 2092.50 | 0.094 | 0.113 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 SE APARTMENT | 1741.71 | 2090.05 | 0.094 | 0.113 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 NE APARTMENT | 1743.75 | 2092.50 | 0.094 | 0.113 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 N1 APARTMENT | 931.71 | 1118.05 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 N2 APARTMENT | 931.71 | 1118.05 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 S1 APARTMENT | 929.85 | 1115.82 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F4 S2 APARTMENT | 929.87 | 1115.85 | 0.050 | 0.060 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M SW APARTMENT | 1776.18 | 2131.42 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M NW APARTMENT | 1778.81 | 2134.58 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M SE APARTMENT | 1776.20 | 2131.44 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M NE APARTMENT | 1778.81 | 2134.58 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M N1 APARTMENT | 943.22 | 1131.87 | 0.051 | 0.061 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M N2 APARTMENT | 943.22 | 1131.87 | 0.051 | 0.061 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M S1 APARTMENT | 940.91 | 1129.10 | 0.051 | 0.061 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
M S2 APARTMENT | 940.92 | 1129.10 | 0.051 | 0.061 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 SW APARTMENT | 1857.34 | 2228.81 | 0.100 | 0.121 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 NW APARTMENT | 1861.64 | 2233.97 | 0.101 | 0.121 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 SE APARTMENT | 1857.34 | 2228.81 | 0.100 | 0.121 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 NE APARTMENT | 1861.64 | 2233.97 | 0.101 | 0.121 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 N1 APARTMENT | 1003.45 | 1204.14 | 0.054 | 0.065 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 N2 APARTMENT | 1003.45 | 1204.14 | 0.054 | 0.065 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 S1 APARTMENT | 999.43 | 1199.31 | 0.054 | 0.065 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F6 S2 APARTMENT | 999.43 | 1199.32 | 0.054 | 0.065 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 SW APARTMENT | 1915.33 | 2298.40 | 0.104 | 0.124 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 NW APARTMENT | 1920.28 | 2304.33 | 0.104 | 0.125 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 SE APARTMENT | 1915.33 | 2298.40 | 0.104 | 0.124 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 NE APARTMENT | 1920.28 | 2304.33 | 0.104 | 0.125 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 N1 APARTMENT | 1043.50 | 1252.21 | 0.056 | 0.068 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 N2 APARTMENT | 1043.50 | 1252.21 | 0.056 | 0.068 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 S1 APARTMENT | 1038.83 | 1246.60 | 0.056 | 0.067 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F7 S2 APARTMENT | 1038.83 | 1246.60 | 0.056 | 0.067 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 SW APARTMENT | 1975.66 | 2370.79 | 0.107 | 0.128 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 NW APARTMENT | 1980.95 | 2377.14 | 0.107 | 0.129 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 SE APARTMENT | 1975.66 | 2370.79 | 0.107 | 0.128 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 NE APARTMENT | 1980.95 | 2377.14 | 0.107 | 0.129 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 N1 APARTMENT | 1087.70 | 1305.25 | 0.059 | 0.071 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 N2 APARTMENT | 1087.70 | 1305.25 | 0.059 | 0.071 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 S1 APARTMENT | 1082.67 | 1299.20 | 0.059 | 0.070 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F8 S2 APARTMENT | 1082.67 | 1299.20 | 0.059 | 0.070 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 SW APARTMENT | 2135.53 | 2562.63 | 0.116 | 0.139 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 NW APARTMENT | 2139.21 | 2567.05 | 0.116 | 0.139 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 SE APARTMENT | 2135.53 | 2562.63 | 0.116 | 0.139 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 NE APARTMENT | 2139.21 | 2567.05 | 0.116 | 0.139 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 N1 APARTMENT | 1224.22 | 1469.07 | 0.066 | 0.079 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 N2 APARTMENT | 1224.22 | 1469.07 | 0.066 | 0.079 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 S1 APARTMENT | 1220.41 | 1464.49 | 0.066 | 0.079 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
F9 S2 APARTMENT | 1220.41 | 1464.49 | 0.066 | 0.079 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T SW APARTMENT | 2653.95 | 3184.74 | 0.144 | 0.172 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T NW APARTMENT | 2663.19 | 3195.83 | 0.144 | 0.173 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T SE APARTMENT | 2653.95 | 3184.74 | 0.144 | 0.172 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T NE APARTMENT | 2663.19 | 3195.83 | 0.144 | 0.173 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T N1 APARTMENT | 1780.57 | 2136.68 | 0.096 | 0.116 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T N2 APARTMENT | 1780.57 | 2136.68 | 0.096 | 0.116 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T S1 APARTMENT | 1768.78 | 2122.53 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
T S2 APARTMENT | 1768.78 | 2122.53 | 0.096 | 0.115 | ALBUQUERQUE INTL ARPT ISIS ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP G NW | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP OFFICE | 0.38 | 0.38 | 0.13 | 0.13 |
AIRLOOP G NE | 0.19 | 0.19 | 0.11 | 0.11 |
AIRLOOP G N1 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP G N2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP G S1 | 0.14 | 0.14 | 0.07 | 0.07 |
AIRLOOP G S2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F2 SW | 0.34 | 0.34 | 0.11 | 0.11 |
AIRLOOP F2 NW | 0.33 | 0.33 | 0.11 | 0.11 |
AIRLOOP F2 SE | 0.30 | 0.30 | 0.11 | 0.11 |
AIRLOOP F2 NE | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F2 N1 | 0.17 | 0.17 | 0.06 | 0.06 |
AIRLOOP F2 N2 | 0.17 | 0.17 | 0.06 | 0.06 |
AIRLOOP F2 S1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F2 S2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F3 SW | 0.34 | 0.34 | 0.11 | 0.11 |
AIRLOOP F3 NW | 0.33 | 0.33 | 0.11 | 0.11 |
AIRLOOP F3 SE | 0.28 | 0.28 | 0.11 | 0.11 |
AIRLOOP F3 NE | 0.25 | 0.25 | 0.11 | 0.11 |
AIRLOOP F3 N1 | 0.18 | 0.18 | 0.06 | 0.06 |
AIRLOOP F3 N2 | 0.18 | 0.18 | 0.06 | 0.06 |
AIRLOOP F3 S1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F3 S2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F4 SW | 0.34 | 0.34 | 0.11 | 0.11 |
AIRLOOP F4 NW | 0.33 | 0.33 | 0.11 | 0.11 |
AIRLOOP F4 SE | 0.28 | 0.28 | 0.11 | 0.11 |
AIRLOOP F4 NE | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F4 N1 | 0.18 | 0.18 | 0.06 | 0.06 |
AIRLOOP F4 N2 | 0.18 | 0.18 | 0.06 | 0.06 |
AIRLOOP F4 S1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP F4 S2 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP M SW | 0.35 | 0.35 | 0.12 | 0.12 |
AIRLOOP M NW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP M SE | 0.29 | 0.29 | 0.12 | 0.12 |
AIRLOOP M NE | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP M N1 | 0.19 | 0.19 | 0.06 | 0.06 |
AIRLOOP M N2 | 0.18 | 0.18 | 0.06 | 0.06 |
AIRLOOP M S1 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP M S2 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F6 SW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP F6 NW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP F6 SE | 0.29 | 0.29 | 0.12 | 0.12 |
AIRLOOP F6 NE | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F6 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F6 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F6 S1 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F6 S2 | 0.20 | 0.20 | 0.06 | 0.06 |
AIRLOOP F7 SW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP F7 NW | 0.34 | 0.34 | 0.12 | 0.12 |
AIRLOOP F7 SE | 0.29 | 0.29 | 0.12 | 0.12 |
AIRLOOP F7 NE | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F7 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F7 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F7 S1 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F7 S2 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F8 SW | 0.35 | 0.35 | 0.13 | 0.13 |
AIRLOOP F8 NW | 0.34 | 0.34 | 0.13 | 0.13 |
AIRLOOP F8 SE | 0.29 | 0.29 | 0.13 | 0.13 |
AIRLOOP F8 NE | 0.26 | 0.26 | 0.13 | 0.13 |
AIRLOOP F8 N1 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F8 N2 | 0.18 | 0.18 | 0.07 | 0.07 |
AIRLOOP F8 S1 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F8 S2 | 0.20 | 0.20 | 0.07 | 0.07 |
AIRLOOP F9 SW | 0.36 | 0.36 | 0.14 | 0.14 |
AIRLOOP F9 NW | 0.35 | 0.35 | 0.14 | 0.14 |
AIRLOOP F9 SE | 0.30 | 0.30 | 0.14 | 0.14 |
AIRLOOP F9 NE | 0.26 | 0.26 | 0.14 | 0.14 |
AIRLOOP F9 N1 | 0.20 | 0.20 | 0.08 | 0.08 |
AIRLOOP F9 N2 | 0.19 | 0.19 | 0.08 | 0.08 |
AIRLOOP F9 S1 | 0.21 | 0.21 | 0.08 | 0.08 |
AIRLOOP F9 S2 | 0.21 | 0.21 | 0.08 | 0.08 |
AIRLOOP T SW | 0.44 | 0.44 | 0.17 | 0.17 |
AIRLOOP T NW | 0.43 | 0.43 | 0.17 | 0.17 |
AIRLOOP T SE | 0.38 | 0.38 | 0.17 | 0.17 |
AIRLOOP T NE | 0.34 | 0.34 | 0.17 | 0.17 |
AIRLOOP T N1 | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP T N2 | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP T S1 | 0.30 | 0.30 | 0.11 | 0.11 |
AIRLOOP T S2 | 0.30 | 0.30 | 0.11 | 0.11 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2766.50 | 4951.50 | 328.50 |
G NW APARTMENT | 2687.75 | 5884.25 | 549.00 |
OFFICE | 991.25 | 437.00 | 1.00 |
G NE APARTMENT | 2787.75 | 5852.50 | 595.50 |
G N1 APARTMENT | 2355.00 | 6238.50 | 496.50 |
G N2 APARTMENT | 2358.00 | 6234.00 | 496.25 |
G S1 APARTMENT | 2603.75 | 5303.00 | 381.00 |
G S2 APARTMENT | 2644.75 | 5197.25 | 368.50 |
F2 SW APARTMENT | 3483.75 | 3349.75 | 173.00 |
F2 NW APARTMENT | 2992.25 | 5016.00 | 248.00 |
F2 SE APARTMENT | 3680.25 | 3042.25 | 135.25 |
F2 NE APARTMENT | 3115.50 | 4995.50 | 281.75 |
F2 N1 APARTMENT | 2757.25 | 5379.50 | 290.50 |
F2 N2 APARTMENT | 2764.25 | 5372.25 | 289.00 |
F2 S1 APARTMENT | 3381.25 | 3237.25 | 225.75 |
F2 S2 APARTMENT | 3408.75 | 3183.25 | 221.50 |
F3 SW APARTMENT | 3605.25 | 3080.50 | 172.00 |
F3 NW APARTMENT | 3047.50 | 4842.25 | 229.75 |
F3 SE APARTMENT | 3673.75 | 3041.75 | 153.50 |
F3 NE APARTMENT | 3162.25 | 4827.50 | 254.00 |
F3 N1 APARTMENT | 2845.25 | 5115.50 | 263.25 |
F3 N2 APARTMENT | 2851.25 | 5114.75 | 262.50 |
F3 S1 APARTMENT | 3587.50 | 2769.00 | 210.25 |
F3 S2 APARTMENT | 3598.50 | 2748.00 | 207.75 |
F4 SW APARTMENT | 3606.75 | 3095.50 | 176.00 |
F4 NW APARTMENT | 3058.50 | 4822.50 | 234.00 |
F4 SE APARTMENT | 3657.00 | 3096.25 | 164.25 |
F4 NE APARTMENT | 3167.25 | 4805.75 | 257.75 |
F4 N1 APARTMENT | 2868.00 | 5050.50 | 259.75 |
F4 N2 APARTMENT | 2872.50 | 5048.75 | 259.75 |
F4 S1 APARTMENT | 3626.00 | 2711.75 | 212.50 |
F4 S2 APARTMENT | 3629.25 | 2705.75 | 210.25 |
M SW APARTMENT | 3591.00 | 3124.00 | 176.50 |
M NW APARTMENT | 3062.25 | 4826.50 | 232.00 |
M SE APARTMENT | 3641.00 | 3125.25 | 165.00 |
M NE APARTMENT | 3166.50 | 4809.75 | 253.75 |
M N1 APARTMENT | 2882.75 | 5029.00 | 254.00 |
M N2 APARTMENT | 2888.00 | 5026.25 | 253.25 |
M S1 APARTMENT | 3619.50 | 2714.75 | 206.25 |
M S2 APARTMENT | 3626.75 | 2714.75 | 204.75 |
F6 SW APARTMENT | 3487.50 | 3320.00 | 189.75 |
F6 NW APARTMENT | 3010.00 | 4925.50 | 256.25 |
F6 SE APARTMENT | 3544.75 | 3303.25 | 175.00 |
F6 NE APARTMENT | 3109.75 | 4913.25 | 279.50 |
F6 N1 APARTMENT | 2817.75 | 5129.50 | 266.25 |
F6 N2 APARTMENT | 2824.00 | 5127.25 | 266.75 |
F6 S1 APARTMENT | 3489.25 | 2948.25 | 225.50 |
F6 S2 APARTMENT | 3496.25 | 2945.00 | 223.50 |
F7 SW APARTMENT | 3421.50 | 3467.00 | 193.75 |
F7 NW APARTMENT | 2984.75 | 4983.75 | 272.75 |
F7 SE APARTMENT | 3490.25 | 3430.75 | 183.75 |
F7 NE APARTMENT | 3090.75 | 4982.00 | 298.50 |
F7 N1 APARTMENT | 2783.25 | 5197.50 | 274.50 |
F7 N2 APARTMENT | 2791.50 | 5194.00 | 274.50 |
F7 S1 APARTMENT | 3420.25 | 3115.75 | 232.00 |
F7 S2 APARTMENT | 3422.75 | 3112.25 | 229.75 |
F8 SW APARTMENT | 3366.00 | 3577.75 | 198.50 |
F8 NW APARTMENT | 2969.75 | 5032.25 | 284.50 |
F8 SE APARTMENT | 3436.00 | 3537.00 | 189.75 |
F8 NE APARTMENT | 3082.50 | 5031.25 | 316.50 |
F8 N1 APARTMENT | 2759.75 | 5243.00 | 277.00 |
F8 N2 APARTMENT | 2766.25 | 5242.75 | 277.25 |
F8 S1 APARTMENT | 3349.50 | 3271.00 | 234.50 |
F8 S2 APARTMENT | 3356.75 | 3264.75 | 233.00 |
F9 SW APARTMENT | 3307.25 | 3735.25 | 205.25 |
F9 NW APARTMENT | 2989.00 | 5079.75 | 323.75 |
F9 SE APARTMENT | 3362.75 | 3669.75 | 196.00 |
F9 NE APARTMENT | 3098.50 | 5082.75 | 362.25 |
F9 N1 APARTMENT | 2750.50 | 5278.75 | 277.75 |
F9 N2 APARTMENT | 2756.75 | 5274.25 | 277.00 |
F9 S1 APARTMENT | 3243.25 | 3484.00 | 227.50 |
F9 S2 APARTMENT | 3249.25 | 3476.00 | 225.75 |
T SW APARTMENT | 3896.00 | 4207.75 | 564.00 |
T NW APARTMENT | 3555.75 | 5235.50 | 1005.00 |
T SE APARTMENT | 3991.75 | 4113.75 | 580.25 |
T NE APARTMENT | 3653.75 | 5205.25 | 1022.50 |
T N1 APARTMENT | 3008.75 | 5420.00 | 625.75 |
T N2 APARTMENT | 3017.00 | 5409.75 | 628.00 |
T S1 APARTMENT | 3563.00 | 4045.25 | 333.75 |
T S2 APARTMENT | 3575.75 | 4039.00 | 333.25 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5288.25 | 6395.00 | 1341.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 2.25 | 58.50 | 2.25 | 58.50 |
G NW APARTMENT | 0.25 | 44.25 | 0.25 | 44.25 |
OFFICE | 3.75 | 41.25 | 0.00 | 41.00 |
G NE APARTMENT | 2.25 | 89.75 | 2.25 | 89.75 |
G N1 APARTMENT | 7.25 | 71.00 | 7.25 | 71.00 |
G N2 APARTMENT | 5.75 | 75.25 | 5.75 | 75.25 |
G S1 APARTMENT | 1.00 | 212.25 | 1.00 | 212.25 |
G S2 APARTMENT | 1.00 | 170.75 | 1.00 | 170.75 |
F2 SW APARTMENT | 0.50 | 64.50 | 0.50 | 64.50 |
F2 NW APARTMENT | 0.00 | 43.25 | 0.00 | 43.25 |
F2 SE APARTMENT | 0.25 | 40.25 | 0.25 | 40.25 |
F2 NE APARTMENT | 0.50 | 104.25 | 0.50 | 104.25 |
F2 N1 APARTMENT | 4.50 | 63.75 | 4.50 | 63.75 |
F2 N2 APARTMENT | 5.75 | 68.75 | 5.75 | 68.75 |
F2 S1 APARTMENT | 0.25 | 238.50 | 0.25 | 238.50 |
F2 S2 APARTMENT | 0.50 | 217.00 | 0.50 | 217.00 |
F3 SW APARTMENT | 0.25 | 85.25 | 0.25 | 85.25 |
F3 NW APARTMENT | 0.00 | 51.00 | 0.00 | 51.00 |
F3 SE APARTMENT | 0.25 | 108.25 | 0.25 | 108.25 |
F3 NE APARTMENT | 0.50 | 120.25 | 0.50 | 120.25 |
F3 N1 APARTMENT | 4.00 | 82.00 | 4.00 | 82.00 |
F3 N2 APARTMENT | 4.50 | 87.25 | 4.50 | 87.25 |
F3 S1 APARTMENT | 1.25 | 276.00 | 1.25 | 276.00 |
F3 S2 APARTMENT | 0.50 | 268.25 | 0.50 | 268.25 |
F4 SW APARTMENT | 0.75 | 92.25 | 0.75 | 92.25 |
F4 NW APARTMENT | 0.00 | 53.25 | 0.00 | 53.25 |
F4 SE APARTMENT | 0.50 | 121.50 | 0.50 | 121.50 |
F4 NE APARTMENT | 1.50 | 134.25 | 1.50 | 134.25 |
F4 N1 APARTMENT | 5.75 | 90.25 | 5.75 | 90.25 |
F4 N2 APARTMENT | 4.00 | 97.25 | 4.00 | 97.25 |
F4 S1 APARTMENT | 0.25 | 290.00 | 0.25 | 290.00 |
F4 S2 APARTMENT | 0.00 | 281.75 | 0.00 | 281.75 |
M SW APARTMENT | 0.50 | 95.00 | 0.50 | 95.00 |
M NW APARTMENT | 0.00 | 55.25 | 0.00 | 55.25 |
M SE APARTMENT | 0.50 | 123.75 | 0.50 | 123.75 |
M NE APARTMENT | 0.25 | 141.00 | 0.25 | 141.00 |
M N1 APARTMENT | 5.75 | 92.75 | 5.75 | 92.75 |
M N2 APARTMENT | 5.00 | 101.00 | 5.00 | 101.00 |
M S1 APARTMENT | 0.50 | 287.00 | 0.50 | 287.00 |
M S2 APARTMENT | 0.75 | 277.75 | 0.75 | 277.75 |
F6 SW APARTMENT | 0.25 | 96.00 | 0.25 | 96.00 |
F6 NW APARTMENT | 0.00 | 58.00 | 0.00 | 58.00 |
F6 SE APARTMENT | 1.00 | 124.50 | 1.00 | 124.50 |
F6 NE APARTMENT | 0.75 | 149.00 | 0.75 | 149.00 |
F6 N1 APARTMENT | 5.50 | 100.50 | 5.50 | 100.50 |
F6 N2 APARTMENT | 4.75 | 109.00 | 4.75 | 109.00 |
F6 S1 APARTMENT | 1.00 | 280.75 | 1.00 | 280.75 |
F6 S2 APARTMENT | 0.50 | 272.00 | 0.50 | 272.00 |
F7 SW APARTMENT | 0.25 | 97.25 | 0.25 | 97.25 |
F7 NW APARTMENT | 0.00 | 60.00 | 0.00 | 60.00 |
F7 SE APARTMENT | 0.50 | 124.50 | 0.50 | 124.50 |
F7 NE APARTMENT | 1.00 | 148.50 | 1.00 | 148.50 |
F7 N1 APARTMENT | 4.00 | 105.00 | 4.00 | 105.00 |
F7 N2 APARTMENT | 5.00 | 113.75 | 5.00 | 113.75 |
F7 S1 APARTMENT | 1.00 | 270.50 | 1.00 | 270.50 |
F7 S2 APARTMENT | 0.75 | 264.75 | 0.75 | 264.75 |
F8 SW APARTMENT | 0.00 | 97.25 | 0.00 | 97.25 |
F8 NW APARTMENT | 0.00 | 60.25 | 0.00 | 60.25 |
F8 SE APARTMENT | 1.00 | 120.50 | 1.00 | 120.50 |
F8 NE APARTMENT | 0.50 | 156.00 | 0.50 | 156.00 |
F8 N1 APARTMENT | 5.75 | 107.00 | 5.75 | 107.00 |
F8 N2 APARTMENT | 4.00 | 115.50 | 4.00 | 115.50 |
F8 S1 APARTMENT | 1.00 | 260.00 | 1.00 | 260.00 |
F8 S2 APARTMENT | 1.25 | 252.25 | 1.25 | 252.25 |
F9 SW APARTMENT | 0.00 | 86.50 | 0.00 | 86.50 |
F9 NW APARTMENT | 0.00 | 60.50 | 0.00 | 60.50 |
F9 SE APARTMENT | 0.50 | 105.75 | 0.50 | 105.75 |
F9 NE APARTMENT | 0.00 | 170.00 | 0.00 | 170.00 |
F9 N1 APARTMENT | 5.75 | 97.25 | 5.75 | 97.25 |
F9 N2 APARTMENT | 4.25 | 105.75 | 4.25 | 105.75 |
F9 S1 APARTMENT | 0.75 | 229.75 | 0.75 | 229.75 |
F9 S2 APARTMENT | 1.25 | 224.50 | 1.25 | 224.50 |
T SW APARTMENT | 0.00 | 79.75 | 0.00 | 79.75 |
T NW APARTMENT | 0.00 | 67.00 | 0.00 | 67.00 |
T SE APARTMENT | 0.00 | 66.75 | 0.00 | 66.75 |
T NE APARTMENT | 0.00 | 76.75 | 0.00 | 76.75 |
T N1 APARTMENT | 0.25 | 71.25 | 0.25 | 71.25 |
T N2 APARTMENT | 0.00 | 68.75 | 0.00 | 68.75 |
T S1 APARTMENT | 0.00 | 117.00 | 0.00 | 117.00 |
T S2 APARTMENT | 0.50 | 114.75 | 0.50 | 114.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 108.50 | 525.50 | 105.00 | 525.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.174 | 0.000 | 0.327 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.174 | 0.000 | 0.312 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.518 | 0.180 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.174 | 0.000 | 0.312 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.105 | 0.000 | 0.304 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.105 | 0.000 | 0.304 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.105 | 0.000 | 0.323 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.105 | 0.000 | 0.324 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.250 | 0.000 | 0.386 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.250 | 0.000 | 0.368 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.250 | 0.000 | 0.387 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.250 | 0.000 | 0.368 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.151 | 0.000 | 0.362 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.151 | 0.000 | 0.362 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.151 | 0.000 | 0.384 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.151 | 0.000 | 0.384 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.296 | 0.000 | 0.429 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.296 | 0.000 | 0.408 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.296 | 0.000 | 0.430 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.296 | 0.000 | 0.408 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.178 | 0.000 | 0.404 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.178 | 0.000 | 0.404 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.179 | 0.000 | 0.427 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.179 | 0.000 | 0.428 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.331 | 0.000 | 0.448 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.331 | 0.000 | 0.424 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.331 | 0.000 | 0.448 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.330 | 0.000 | 0.424 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.199 | 0.000 | 0.421 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.199 | 0.000 | 0.421 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.200 | 0.000 | 0.446 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.200 | 0.000 | 0.446 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.360 | 0.000 | 0.471 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.359 | 0.000 | 0.445 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.360 | 0.000 | 0.471 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.359 | 0.000 | 0.445 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.217 | 0.000 | 0.442 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.217 | 0.000 | 0.442 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.217 | 0.000 | 0.469 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.217 | 0.000 | 0.469 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.384 | 0.000 | 0.491 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.384 | 0.000 | 0.463 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.384 | 0.000 | 0.491 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.384 | 0.000 | 0.463 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.231 | 0.000 | 0.460 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.231 | 0.000 | 0.460 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.232 | 0.000 | 0.489 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.232 | 0.000 | 0.489 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.406 | 0.000 | 0.508 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.405 | 0.000 | 0.479 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.406 | 0.000 | 0.508 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.405 | 0.000 | 0.479 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.244 | 0.000 | 0.475 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.244 | 0.000 | 0.475 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.245 | 0.000 | 0.506 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.245 | 0.000 | 0.506 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.426 | 0.000 | 0.526 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.425 | 0.000 | 0.495 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.426 | 0.000 | 0.526 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.425 | 0.000 | 0.495 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.256 | 0.000 | 0.491 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.256 | 0.000 | 0.491 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.257 | 0.000 | 0.524 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.257 | 0.000 | 0.524 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.444 | 0.000 | 0.542 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.443 | 0.000 | 0.509 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.444 | 0.000 | 0.542 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.443 | 0.000 | 0.509 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.267 | 0.000 | 0.506 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.267 | 0.000 | 0.506 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.268 | 0.000 | 0.540 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.268 | 0.000 | 0.540 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.460 | 0.000 | 0.554 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.459 | 0.000 | 0.522 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.460 | 0.000 | 0.554 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.459 | 0.000 | 0.522 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.352 | 0.277 | 0.000 | 0.519 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.277 | 0.000 | 0.519 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.353 | 0.277 | 0.000 | 0.552 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.277 | 0.000 | 0.552 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.344 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 740.36 | 23476.58 | 01-JAN-08:00 | 23476.58 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1343.22 | 24137.82 | 03-APR-02:15 | 88328.59 | 31-JUL-16:30 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
ElectricityPurchased:Plant | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
Cogeneration:ElectricityPurchased | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
ElectricityNet:Plant | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
Cogeneration:ElectricityNet | 3011.89 | 58190.87 | 02-JUN-05:00 | 163762.87 | 21-JUL-19:15 |
ExteriorLights:Electricity | 162.84 | 0.00 | 01-JAN-07:30 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.84 | 0.00 | 01-JAN-07:30 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 740.36 | 23476.58 | 01-JAN-08:00 | 23476.58 | 01-JAN-00:15 |
Cooling:Electricity | 496.27 | 0.00 | 01-JAN-00:15 | 63183.51 | 31-JUL-15:15 |
Heating:Electricity | 70.42 | 0.00 | 01-JAN-13:30 | 41181.77 | 14-DEC-04:00 |
Electricity:Plant | 71.94 | 36.93 | 13-MAR-23:00 | 3919.48 | 31-JUL-15:00 |
HeatRejection:Electricity | 17.58 | 0.00 | 01-JAN-00:15 | 2178.18 | 31-JUL-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 54.36 | 36.93 | 13-MAR-23:00 | 1741.30 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1285.16 | 2357.00 | 01-JAN-00:15 | 229458.43 | 17-JAN-08:15 |
Gas:Plant | 1285.16 | 2357.00 | 01-JAN-00:15 | 229458.43 | 17-JAN-08:15 |
WaterSystems:Gas | 1090.21 | 2357.00 | 01-JAN-00:15 | 80534.53 | 05-FEB-08:00 |
Water Heater:WaterSystems:Gas | 1090.21 | 2357.00 | 01-JAN-00:15 | 80534.53 | 05-FEB-08:00 |
Heating:Gas | 194.94 | 0.00 | 01-JAN-00:15 | 157563.37 | 18-JAN-01:30 |
Boiler:Heating:Gas | 194.94 | 0.00 | 01-JAN-00:15 | 157563.37 | 18-JAN-01:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 1983.83 | 0.00 | 01-JAN-00:15 | 283526.85 | 31-JUL-16:30 |
PlantLoopCoolingDemand:HVAC | 1983.83 | 0.00 | 01-JAN-00:15 | 283526.85 | 31-JUL-16:30 |
CoolingCoils:PlantLoopCoolingDemand | 1983.83 | 0.00 | 01-JAN-00:15 | 283526.85 | 31-JUL-16:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6475.26 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
Water:Plant | 6475.26 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6475.26 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
MainsWater:Plant | 6475.26 | 0.00 | 01-JAN-02:15 | 0.00 | 21-JUL-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1696.74 | 0.00 | 01-JAN-00:15 | 0.00 | 28-JUN-16:00 |
HeatRejection:MainsWater | 1696.74 | 0.00 | 01-JAN-00:15 | 0.00 | 28-JUN-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1043.76 | 426.25 | 10-AUG-01:15 | 172580.30 | 17-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 847.41 | 426.25 | 10-AUG-01:15 | 58841.40 | 08-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 847.41 | 426.25 | 10-AUG-01:15 | 58841.40 | 08-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 4297.72 | 6570.35 | 17-APR-01:30 | 439933.70 | 17-JAN-08:15 |
EnergyTransfer:Building | 1528.79 | 3998.20 | 03-MAY-18:15 | 175730.97 | 05-JUL-17:00 |
EnergyTransfer:Zone:G SW APARTMENT | 14.73 | 0.00 | 16-MAR-22:00 | 2494.95 | 29-SEP-14:30 |
Heating:EnergyTransfer | 199.34 | 0.00 | 20-FEB-22:00 | 136854.88 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 2.06 | 0.00 | 01-JAN-00:15 | 1452.01 | 18-JAN-01:15 |
Cooling:EnergyTransfer | 1329.45 | 0.00 | 16-JAN-23:15 | 175730.97 | 05-JUL-17:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 12.67 | 0.00 | 01-JAN-01:30 | 2494.95 | 29-SEP-14:30 |
EnergyTransfer:Zone:G NW APARTMENT | 13.25 | 0.00 | 26-FEB-18:45 | 2324.84 | 22-JUL-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 4.88 | 0.00 | 01-JAN-17:45 | 1708.37 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 8.36 | 0.00 | 01-JAN-00:15 | 2324.84 | 22-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 25.50 | 0.02 | 08-OCT-23:00 | 3518.30 | 12-SEP-12:30 |
Heating:EnergyTransfer:Zone:OFFICE | 1.31 | 0.00 | 01-JAN-00:15 | 1431.30 | 17-JAN-08:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 24.19 | 0.00 | 01-JAN-01:30 | 3518.30 | 12-SEP-12:30 |
EnergyTransfer:Zone:G NE APARTMENT | 13.30 | 0.01 | 01-OCT-07:45 | 1749.73 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.42 | 0.00 | 01-JAN-09:00 | 1749.73 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 8.88 | 0.00 | 01-JAN-00:15 | 1725.90 | 28-JUN-08:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.57 | 0.02 | 24-MAY-17:00 | 1170.11 | 16-JUN-19:45 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.26 | 0.00 | 01-JAN-12:00 | 987.72 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 6.31 | 0.00 | 01-JAN-00:15 | 1170.11 | 16-JUN-19:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.59 | 0.02 | 08-SEP-19:45 | 1155.63 | 29-JUN-18:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.26 | 0.00 | 01-JAN-11:45 | 990.85 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 6.33 | 0.00 | 01-JAN-00:15 | 1155.63 | 29-JUN-18:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.75 | 0.01 | 03-FEB-09:15 | 1429.87 | 29-SEP-11:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.38 | 0.00 | 01-JAN-00:15 | 780.00 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 11.37 | 0.00 | 06-JAN-08:00 | 1429.87 | 29-SEP-11:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.09 | 0.01 | 19-MAY-03:15 | 1497.03 | 29-SEP-11:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.36 | 0.00 | 01-JAN-00:15 | 762.78 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.72 | 0.00 | 06-JAN-08:00 | 1497.03 | 29-SEP-11:30 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 22.58 | 0.02 | 09-OCT-01:30 | 3202.45 | 10-OCT-16:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 1.01 | 0.00 | 01-JAN-00:15 | 1604.92 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 21.57 | 0.00 | 05-JAN-13:45 | 3202.45 | 10-OCT-16:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 17.29 | 0.00 | 08-MAR-01:00 | 2972.75 | 18-JUL-17:15 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 3.86 | 0.00 | 01-JAN-18:30 | 2072.06 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 13.43 | 0.00 | 01-JAN-00:15 | 2972.75 | 18-JUL-17:15 |
EnergyTransfer:Zone:F2 SE APARTMENT | 25.17 | 0.01 | 21-APR-07:45 | 2928.24 | 01-OCT-12:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 1531.64 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 24.43 | 0.00 | 01-JAN-15:15 | 2928.24 | 01-OCT-12:00 |
EnergyTransfer:Zone:F2 NE APARTMENT | 17.88 | 0.00 | 29-MAY-04:15 | 2304.40 | 28-JUN-08:15 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 3.48 | 0.00 | 01-JAN-08:00 | 2142.93 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 14.40 | 0.00 | 01-JAN-00:15 | 2304.40 | 28-JUN-08:15 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 11.76 | 0.07 | 08-JAN-11:30 | 1581.40 | 24-JUN-19:30 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 1.18 | 0.00 | 01-JAN-07:30 | 1142.89 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 10.58 | 0.00 | 01-JAN-00:15 | 1581.40 | 24-JUN-19:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 11.81 | 0.02 | 19-NOV-15:15 | 1577.00 | 29-JUN-20:15 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 1.19 | 0.00 | 01-JAN-07:30 | 1148.21 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 10.62 | 0.00 | 01-JAN-00:15 | 1577.00 | 29-JUN-20:15 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 19.65 | 0.36 | 29-JUL-05:45 | 2061.04 | 01-NOV-12:30 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 763.78 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 19.47 | 0.00 | 05-JAN-14:45 | 2061.04 | 01-NOV-12:30 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 19.85 | 0.13 | 17-JAN-19:15 | 2084.86 | 01-NOV-12:30 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 758.07 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 19.67 | 0.00 | 01-JAN-16:00 | 2084.86 | 01-NOV-12:30 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 23.88 | 0.00 | 24-DEC-23:45 | 3258.37 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 0.95 | 0.00 | 01-JAN-00:15 | 1718.91 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 22.94 | 0.00 | 05-JAN-13:45 | 3258.37 | 10-OCT-16:00 |
EnergyTransfer:Zone:F3 NW APARTMENT | 18.02 | 0.00 | 20-NOV-20:30 | 3013.51 | 18-JUL-17:30 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 3.75 | 0.00 | 02-JAN-18:15 | 2311.23 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 14.27 | 0.00 | 01-JAN-00:15 | 3013.51 | 18-JUL-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 25.07 | 0.12 | 20-MAR-05:00 | 2744.39 | 01-OCT-11:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 0.79 | 0.00 | 01-JAN-00:15 | 1725.16 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 24.28 | 0.00 | 01-JAN-15:15 | 2744.39 | 01-OCT-11:00 |
EnergyTransfer:Zone:F3 NE APARTMENT | 18.71 | 0.02 | 10-MAY-04:45 | 2384.09 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 3.42 | 0.00 | 01-JAN-08:00 | 2384.09 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 15.29 | 0.00 | 01-JAN-00:15 | 2353.84 | 28-JUN-08:15 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 12.69 | 0.06 | 01-MAR-04:15 | 1701.35 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 1.06 | 0.00 | 01-JAN-07:15 | 1259.24 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 11.63 | 0.00 | 01-JAN-00:15 | 1701.35 | 23-JUN-21:00 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 12.73 | 0.01 | 24-FEB-18:30 | 1686.66 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 1.07 | 0.00 | 01-JAN-07:15 | 1265.15 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 11.67 | 0.00 | 01-JAN-00:15 | 1686.66 | 23-JUN-21:00 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 21.51 | 0.04 | 18-JUL-06:00 | 2129.56 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 805.02 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 21.34 | 0.00 | 01-JAN-16:00 | 2129.56 | 30-DEC-12:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 21.59 | 0.05 | 29-JUL-05:45 | 2139.88 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 804.85 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 21.42 | 0.00 | 01-JAN-15:45 | 2139.88 | 30-DEC-12:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 24.01 | 0.00 | 08-OCT-05:00 | 3283.65 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 1.05 | 0.00 | 01-JAN-00:15 | 1856.37 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 22.96 | 0.00 | 01-JAN-20:45 | 3283.65 | 10-OCT-16:00 |
EnergyTransfer:Zone:F4 NW APARTMENT | 18.39 | 0.00 | 18-NOV-21:00 | 3036.22 | 18-JUL-17:45 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 4.00 | 0.00 | 02-JAN-18:15 | 2531.82 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 14.39 | 0.00 | 01-JAN-00:15 | 3036.22 | 18-JUL-17:45 |
EnergyTransfer:Zone:F4 SE APARTMENT | 25.00 | 0.04 | 01-MAY-04:45 | 2747.42 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 0.92 | 0.00 | 01-JAN-00:15 | 1874.20 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 24.08 | 0.00 | 01-JAN-15:00 | 2747.42 | 11-OCT-12:45 |
EnergyTransfer:Zone:F4 NE APARTMENT | 19.08 | 0.02 | 16-APR-23:45 | 2602.18 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 3.67 | 0.00 | 01-JAN-08:00 | 2602.18 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 15.41 | 0.00 | 01-JAN-00:15 | 2366.14 | 02-AUG-09:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 12.98 | 0.00 | 03-JAN-04:30 | 1721.69 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 1.13 | 0.00 | 01-JAN-07:15 | 1380.81 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 11.85 | 0.00 | 01-JAN-00:15 | 1721.69 | 23-JUN-21:00 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 13.02 | 0.07 | 01-FEB-22:30 | 1707.13 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 1.13 | 0.00 | 01-JAN-07:15 | 1386.49 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 11.88 | 0.00 | 01-JAN-00:15 | 1707.13 | 23-JUN-21:00 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 21.83 | 0.11 | 05-JAN-15:45 | 2151.88 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 885.24 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 21.64 | 0.00 | 01-JAN-15:45 | 2151.88 | 30-DEC-12:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 21.88 | 0.76 | 09-DEC-00:45 | 2159.94 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 885.99 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 21.69 | 0.00 | 01-JAN-15:45 | 2159.94 | 30-DEC-12:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 24.17 | 0.04 | 06-MAY-03:45 | 3321.60 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 1.18 | 0.00 | 01-JAN-00:15 | 1971.11 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 22.99 | 0.00 | 01-JAN-15:45 | 3321.60 | 10-OCT-16:00 |
EnergyTransfer:Zone:M NW APARTMENT | 18.86 | 0.01 | 02-NOV-08:45 | 3067.31 | 18-JUL-17:45 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 4.25 | 0.00 | 02-JAN-18:15 | 2711.96 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 14.61 | 0.00 | 01-JAN-00:15 | 3067.31 | 18-JUL-17:45 |
EnergyTransfer:Zone:M SE APARTMENT | 25.11 | 0.02 | 30-MAR-22:30 | 2795.17 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 1.05 | 0.00 | 01-JAN-00:15 | 1990.52 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 24.07 | 0.00 | 01-JAN-14:45 | 2795.17 | 11-OCT-12:45 |
EnergyTransfer:Zone:M NE APARTMENT | 19.50 | 0.00 | 26-JAN-16:15 | 2778.44 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 3.90 | 0.00 | 01-JAN-08:00 | 2778.44 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 15.60 | 0.00 | 01-JAN-00:15 | 2408.39 | 02-AUG-09:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 13.31 | 0.04 | 14-FEB-11:15 | 1762.24 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.19 | 0.00 | 01-JAN-07:15 | 1478.99 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 12.11 | 0.00 | 01-JAN-00:15 | 1762.24 | 23-JUN-21:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 13.35 | 0.02 | 20-MAR-11:45 | 1747.93 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.20 | 0.00 | 01-JAN-07:15 | 1484.15 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 12.15 | 0.00 | 01-JAN-00:15 | 1747.93 | 23-JUN-21:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 22.04 | 0.44 | 07-SEP-10:45 | 2185.19 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 952.16 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 21.83 | 0.00 | 01-JAN-15:30 | 2185.19 | 30-DEC-12:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 22.08 | 0.16 | 03-JUN-08:15 | 2192.85 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 953.10 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 21.87 | 0.00 | 01-JAN-15:30 | 2192.85 | 30-DEC-12:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 23.36 | 0.01 | 07-DEC-13:15 | 3290.23 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 1.45 | 0.00 | 01-JAN-00:15 | 2122.03 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 21.91 | 0.00 | 01-JAN-15:30 | 3290.23 | 10-OCT-16:00 |
EnergyTransfer:Zone:F6 NW APARTMENT | 18.91 | 0.01 | 18-NOV-22:00 | 3031.34 | 18-JUL-17:45 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 4.89 | 0.00 | 02-JAN-18:15 | 2918.22 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 14.02 | 0.00 | 01-JAN-00:15 | 3031.34 | 18-JUL-17:45 |
EnergyTransfer:Zone:F6 SE APARTMENT | 24.26 | 0.05 | 21-MAR-16:30 | 2772.60 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 1.30 | 0.00 | 01-JAN-00:15 | 2142.22 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 22.96 | 0.00 | 01-JAN-05:00 | 2772.60 | 11-OCT-12:45 |
EnergyTransfer:Zone:F6 NE APARTMENT | 19.46 | 0.02 | 08-NOV-03:15 | 2979.06 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 4.50 | 0.00 | 01-JAN-08:15 | 2979.06 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 14.96 | 0.00 | 01-JAN-00:15 | 2379.08 | 02-AUG-09:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 12.95 | 0.04 | 07-NOV-15:30 | 1735.89 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 1.48 | 0.00 | 01-JAN-07:30 | 1610.46 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 11.47 | 0.00 | 01-JAN-00:15 | 1735.89 | 23-JUN-21:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 12.99 | 0.08 | 30-JAN-13:15 | 1721.71 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 1.48 | 0.00 | 01-JAN-07:30 | 1615.29 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 11.51 | 0.00 | 01-JAN-00:15 | 1721.71 | 23-JUN-21:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 21.07 | 0.19 | 01-FEB-03:15 | 2154.82 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 0.26 | 0.00 | 01-JAN-00:15 | 1043.56 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 20.81 | 0.00 | 01-JAN-15:15 | 2154.82 | 30-DEC-12:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 21.10 | 0.70 | 15-MAR-14:15 | 2162.43 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 0.26 | 0.00 | 01-JAN-00:15 | 1044.45 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 20.84 | 0.00 | 01-JAN-15:15 | 2162.43 | 30-DEC-12:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 22.95 | 0.00 | 23-OCT-01:15 | 3281.56 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 1.71 | 0.00 | 01-JAN-00:15 | 2247.94 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 21.25 | 0.00 | 01-JAN-05:00 | 3281.56 | 10-OCT-16:00 |
EnergyTransfer:Zone:F7 NW APARTMENT | 19.16 | 0.00 | 05-DEC-16:00 | 3090.62 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 5.42 | 0.00 | 02-JAN-18:15 | 3090.62 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 13.73 | 0.00 | 01-JAN-00:15 | 3020.44 | 18-JUL-17:45 |
EnergyTransfer:Zone:F7 SE APARTMENT | 23.82 | 0.16 | 18-MAY-06:00 | 2770.11 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 1.55 | 0.00 | 01-JAN-00:15 | 2268.29 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 22.28 | 0.00 | 01-JAN-03:00 | 2770.11 | 11-OCT-12:45 |
EnergyTransfer:Zone:F7 NE APARTMENT | 19.64 | 0.00 | 24-SEP-03:30 | 3146.91 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 4.99 | 0.00 | 01-JAN-08:30 | 3146.91 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 14.65 | 0.00 | 01-JAN-00:15 | 2381.64 | 02-AUG-09:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 12.84 | 0.09 | 07-NOV-14:45 | 1732.14 | 23-JUN-21:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 1.72 | 0.00 | 01-JAN-07:45 | 1718.48 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 11.12 | 0.00 | 01-JAN-00:15 | 1732.14 | 23-JUN-21:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 12.89 | 0.00 | 25-MAR-03:00 | 1722.98 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 1.73 | 0.00 | 01-JAN-07:45 | 1722.98 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 11.16 | 0.00 | 01-JAN-00:15 | 1718.05 | 23-JUN-21:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 20.47 | 0.01 | 04-MAR-00:45 | 2144.63 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 1118.97 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 20.16 | 0.00 | 01-JAN-15:00 | 2144.63 | 30-DEC-12:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 20.51 | 0.20 | 04-DEC-01:15 | 2152.22 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 0.31 | 0.00 | 01-JAN-00:15 | 1119.77 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 20.20 | 0.00 | 01-JAN-15:00 | 2152.22 | 30-DEC-12:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 22.73 | 0.02 | 06-MAY-03:00 | 3286.40 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 1.99 | 0.00 | 01-JAN-00:15 | 2371.79 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 20.74 | 0.00 | 01-JAN-03:00 | 3286.40 | 10-OCT-16:00 |
EnergyTransfer:Zone:F8 NW APARTMENT | 19.53 | 0.01 | 15-APR-05:45 | 3247.98 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 5.94 | 0.00 | 02-JAN-18:30 | 3247.98 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 13.59 | 0.00 | 01-JAN-00:15 | 3024.40 | 18-JUL-17:45 |
EnergyTransfer:Zone:F8 SE APARTMENT | 23.57 | 0.02 | 21-OCT-05:00 | 2780.30 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 1.81 | 0.00 | 01-JAN-00:15 | 2391.83 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 21.75 | 0.00 | 01-JAN-02:45 | 2780.30 | 11-OCT-12:45 |
EnergyTransfer:Zone:F8 NE APARTMENT | 19.94 | 0.01 | 11-APR-02:30 | 3301.92 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 5.47 | 0.00 | 01-JAN-08:30 | 3301.92 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 14.47 | 0.00 | 01-JAN-00:15 | 2386.52 | 02-AUG-09:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 12.91 | 0.07 | 20-MAR-15:45 | 1874.32 | 17-MAR-15:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 1.98 | 0.00 | 01-JAN-08:30 | 1874.32 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 10.93 | 0.00 | 01-JAN-00:15 | 1742.34 | 23-JUN-21:00 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 12.95 | 0.06 | 21-NOV-14:30 | 1867.08 | 17-MAR-15:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 1.98 | 0.00 | 01-JAN-08:30 | 1867.08 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 10.97 | 0.00 | 01-JAN-00:15 | 1728.14 | 23-JUN-21:00 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 20.01 | 0.35 | 19-MAR-13:45 | 2134.27 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1195.34 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 19.64 | 0.00 | 01-JAN-14:30 | 2134.27 | 30-DEC-12:00 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 20.05 | 0.43 | 30-APR-18:45 | 2141.00 | 30-DEC-12:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 0.37 | 0.00 | 01-JAN-00:15 | 1196.19 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 19.68 | 0.00 | 01-JAN-14:30 | 2141.00 | 30-DEC-12:00 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 22.96 | 0.01 | 02-NOV-08:45 | 3394.17 | 10-OCT-15:45 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 2.59 | 0.00 | 01-JAN-00:15 | 2564.83 | 18-JAN-01:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 20.37 | 0.00 | 01-JAN-02:30 | 3394.17 | 10-OCT-15:45 |
EnergyTransfer:Zone:F9 NW APARTMENT | 20.69 | 0.01 | 20-APR-11:15 | 3441.65 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 6.86 | 0.00 | 02-JAN-18:45 | 3441.65 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 13.83 | 0.00 | 01-JAN-00:15 | 3134.55 | 18-JUL-17:45 |
EnergyTransfer:Zone:F9 SE APARTMENT | 23.69 | 0.04 | 01-MAR-21:15 | 2867.48 | 11-OCT-12:45 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 2.35 | 0.00 | 01-JAN-00:15 | 2602.91 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 21.34 | 0.00 | 01-JAN-02:15 | 2867.48 | 11-OCT-12:45 |
EnergyTransfer:Zone:F9 NE APARTMENT | 20.87 | 0.00 | 21-NOV-10:45 | 3500.08 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 6.27 | 0.00 | 01-JAN-08:45 | 3500.08 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 14.59 | 0.00 | 01-JAN-00:15 | 2428.53 | 02-AUG-09:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 13.48 | 0.01 | 30-OCT-19:30 | 2032.98 | 17-MAR-15:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 2.50 | 0.00 | 01-JAN-10:15 | 2032.98 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 10.97 | 0.00 | 01-JAN-00:15 | 1843.00 | 23-JUN-21:00 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 13.52 | 0.02 | 06-MAR-11:30 | 2023.44 | 17-MAR-15:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 2.51 | 0.00 | 01-JAN-09:00 | 2023.44 | 17-MAR-15:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 11.01 | 0.00 | 01-JAN-00:15 | 1828.87 | 23-JUN-21:00 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 19.60 | 0.05 | 14-OCT-18:00 | 2119.48 | 07-NOV-12:45 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 0.51 | 0.00 | 01-JAN-00:15 | 1342.44 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 19.08 | 0.00 | 01-JAN-14:15 | 2119.48 | 07-NOV-12:45 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 19.64 | 0.01 | 21-APR-22:15 | 2127.29 | 07-NOV-12:45 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 0.52 | 0.00 | 01-JAN-00:15 | 1343.45 | 18-JAN-01:15 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 19.13 | 0.00 | 01-JAN-14:15 | 2127.29 | 07-NOV-12:45 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 30.12 | 0.01 | 10-JAN-21:15 | 4173.66 | 10-OCT-15:45 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 7.76 | 0.00 | 01-JAN-08:30 | 3625.62 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 22.36 | 0.00 | 01-JAN-00:15 | 4173.66 | 10-OCT-15:45 |
EnergyTransfer:Zone:T NW APARTMENT | 27.28 | 0.01 | 04-JUN-02:30 | 4097.01 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 11.83 | 0.00 | 02-JAN-14:15 | 4097.01 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 15.45 | 0.00 | 01-JAN-00:15 | 3899.37 | 18-JUL-17:30 |
EnergyTransfer:Zone:T SE APARTMENT | 29.94 | 0.02 | 29-JAN-19:00 | 3646.61 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 7.22 | 0.00 | 01-JAN-08:00 | 3646.61 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 22.72 | 0.00 | 01-JAN-00:15 | 3637.15 | 11-OCT-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 26.65 | 0.00 | 06-SEP-20:00 | 4125.62 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 10.90 | 0.00 | 01-JAN-09:00 | 4125.62 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 15.75 | 0.00 | 01-JAN-00:15 | 3086.12 | 05-JUL-08:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 17.60 | 0.01 | 31-MAR-09:00 | 2506.19 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 5.90 | 0.00 | 01-JAN-10:30 | 2506.19 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 11.70 | 0.00 | 01-JAN-00:15 | 2400.74 | 23-JUN-21:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 17.66 | 0.02 | 20-JAN-16:45 | 2509.40 | 14-DEC-04:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 5.92 | 0.00 | 01-JAN-10:30 | 2509.40 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 11.73 | 0.00 | 01-JAN-00:15 | 2387.43 | 23-JUN-21:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.20 | 0.05 | 01-APR-03:15 | 2937.55 | 01-OCT-12:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 2.91 | 0.00 | 01-JAN-00:15 | 1977.20 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 19.29 | 0.00 | 01-JAN-01:15 | 2937.55 | 01-OCT-12:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.26 | 0.01 | 08-NOV-01:15 | 2945.31 | 01-OCT-12:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 2.92 | 0.00 | 01-JAN-00:15 | 1980.17 | 14-DEC-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 19.34 | 0.00 | 01-JAN-01:15 | 2945.31 | 01-OCT-12:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 992.72 | 426.25 | 10-AUG-01:15 | 168711.18 | 17-JAN-08:00 |
WaterSystems:EnergyTransfer | 847.40 | 426.25 | 10-AUG-01:15 | 58835.39 | 08-FEB-08:00 |
sub cat:WaterSystems:EnergyTransfer | 847.40 | 426.25 | 10-AUG-01:15 | 58835.39 | 08-FEB-08:00 |
EnergyTransfer:HVAC | 1776.21 | 0.00 | 13-MAR-23:00 | 220717.61 | 31-JUL-16:30 |
CoolingCoils:EnergyTransfer | 1519.72 | 0.00 | 01-JAN-00:15 | 220717.61 | 31-JUL-16:30 |
HeatingCoils:EnergyTransfer | 256.49 | 0.00 | 01-JAN-13:30 | 159739.18 | 14-DEC-04:00 |
PlantLoopHeatingDemand:HVAC | 196.35 | 0.00 | 01-JAN-13:30 | 120310.79 | 14-DEC-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 196.35 | 0.00 | 01-JAN-13:30 | 120310.79 | 14-DEC-04:00 |
Boilers:EnergyTransfer | 145.32 | 0.00 | 01-JAN-00:15 | 118172.53 | 18-JAN-01:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 2.058 | -12.670 | 0.000 | 0.000 | 3.748 | 1.087 | 12.213 | 27.930 | 0.000 | 0.416 | 0.001 | 0.000 | -9.772 | 0.000 | -6.897 | -18.112 |
G NW APARTMENT | 4.882 | -8.364 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 14.093 | 0.000 | 0.410 | 0.000 | 0.000 | -9.795 | 0.000 | -6.414 | -11.918 |
OFFICE | 1.305 | -24.191 | 0.000 | 0.000 | 0.507 | 29.882 | 9.495 | 28.597 | 0.000 | 0.298 | 0.001 | 0.000 | -9.687 | 0.000 | -4.028 | -32.179 |
G NE APARTMENT | 4.416 | -8.883 | 0.000 | 0.000 | 3.822 | 1.087 | 12.213 | 14.630 | 0.000 | 0.407 | 0.000 | 0.000 | -9.312 | 0.000 | -6.401 | -11.979 |
G N1 APARTMENT | 2.259 | -6.306 | 0.000 | 0.000 | 3.831 | 1.087 | 12.213 | 4.662 | 0.000 | 0.292 | 0.000 | 0.000 | -5.988 | 0.000 | -4.625 | -7.424 |
G N2 APARTMENT | 2.261 | -6.329 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 4.658 | 0.000 | 0.291 | 0.000 | 0.000 | -5.984 | 0.000 | -4.627 | -7.401 |
G S1 APARTMENT | 0.380 | -11.372 | 0.000 | 0.000 | 3.750 | 1.087 | 12.213 | 18.689 | 0.000 | 0.290 | 0.001 | 0.000 | -5.923 | 0.000 | -5.175 | -13.937 |
G S2 APARTMENT | 0.363 | -11.722 | 0.000 | 0.000 | 3.745 | 1.087 | 12.213 | 18.668 | 0.000 | 0.291 | 0.001 | 0.000 | -5.937 | 0.000 | -5.221 | -13.486 |
F2 SW APARTMENT | 1.009 | -21.567 | 0.000 | 0.000 | 3.658 | 1.087 | 12.213 | 27.218 | 0.000 | 0.569 | 0.000 | 0.000 | -10.544 | 0.000 | -9.462 | -4.180 |
F2 NW APARTMENT | 3.861 | -13.428 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 13.588 | 0.000 | 0.560 | 0.000 | 0.000 | -10.422 | 0.000 | -8.849 | -2.363 |
F2 SE APARTMENT | 0.739 | -24.432 | 0.000 | 0.000 | 3.653 | 1.087 | 12.213 | 27.891 | 0.000 | 0.569 | 0.001 | 0.000 | -10.341 | 0.000 | -9.558 | -1.820 |
F2 NE APARTMENT | 3.481 | -14.401 | 0.000 | 0.000 | 3.770 | 1.087 | 12.213 | 14.122 | 0.000 | 0.556 | 0.000 | 0.000 | -9.892 | 0.000 | -8.814 | -2.123 |
F2 N1 APARTMENT | 1.184 | -10.575 | 0.000 | 0.000 | 3.774 | 1.087 | 12.213 | 4.395 | 0.000 | 0.390 | 0.309 | 0.000 | -6.420 | 0.000 | -6.358 | -0.000 |
F2 N2 APARTMENT | 1.194 | -10.615 | 0.000 | 0.000 | 3.775 | 1.087 | 12.213 | 4.392 | 0.000 | 0.390 | 0.338 | 0.000 | -6.415 | 0.000 | -6.359 | -0.000 |
F2 S1 APARTMENT | 0.181 | -19.470 | 0.000 | 0.000 | 3.637 | 1.087 | 12.213 | 18.238 | 0.000 | 0.385 | 0.002 | 0.000 | -6.413 | 0.000 | -7.075 | -2.782 |
F2 S2 APARTMENT | 0.180 | -19.669 | 0.000 | 0.000 | 3.635 | 1.087 | 12.213 | 18.231 | 0.000 | 0.386 | 0.002 | 0.000 | -6.419 | 0.000 | -7.089 | -2.555 |
F3 SW APARTMENT | 0.947 | -22.935 | 0.000 | 0.000 | 3.646 | 1.087 | 12.213 | 26.953 | 0.000 | 0.703 | 0.001 | 0.000 | -10.723 | 0.000 | -10.831 | -1.060 |
F3 NW APARTMENT | 3.748 | -14.273 | 0.000 | 0.000 | 3.744 | 1.087 | 12.213 | 13.417 | 0.000 | 0.692 | 0.140 | 0.000 | -10.604 | 0.000 | -10.163 | -0.000 |
F3 SE APARTMENT | 0.790 | -24.276 | 0.000 | 0.000 | 3.655 | 1.087 | 12.213 | 27.690 | 0.000 | 0.698 | 0.001 | 0.000 | -10.433 | 0.000 | -10.848 | -0.574 |
F3 NE APARTMENT | 3.420 | -15.291 | 0.000 | 0.000 | 3.760 | 1.087 | 12.213 | 13.956 | 0.000 | 0.686 | 0.351 | 0.000 | -10.061 | 0.000 | -10.120 | -0.000 |
F3 N1 APARTMENT | 1.060 | -11.628 | 0.000 | 0.000 | 3.759 | 1.087 | 12.213 | 4.319 | 0.000 | 0.491 | 2.536 | 0.000 | -6.555 | 0.000 | -7.280 | -0.000 |
F3 N2 APARTMENT | 1.067 | -11.666 | 0.000 | 0.000 | 3.760 | 1.087 | 12.213 | 4.316 | 0.000 | 0.490 | 2.564 | 0.000 | -6.550 | 0.000 | -7.281 | -0.000 |
F3 S1 APARTMENT | 0.168 | -21.344 | 0.000 | 0.000 | 3.616 | 1.087 | 12.213 | 18.064 | 0.000 | 0.481 | 0.308 | 0.000 | -6.546 | 0.000 | -8.046 | -0.000 |
F3 S2 APARTMENT | 0.168 | -21.422 | 0.000 | 0.000 | 3.616 | 1.087 | 12.213 | 18.061 | 0.000 | 0.482 | 0.395 | 0.000 | -6.546 | 0.000 | -8.052 | -0.000 |
F4 SW APARTMENT | 1.049 | -22.963 | 0.000 | 0.000 | 3.648 | 1.087 | 12.213 | 26.801 | 0.000 | 0.771 | 0.001 | 0.000 | -10.787 | 0.000 | -11.656 | -0.162 |
F4 NW APARTMENT | 3.998 | -14.392 | 0.000 | 0.000 | 3.744 | 1.087 | 12.213 | 13.325 | 0.000 | 0.760 | 0.911 | 0.000 | -10.685 | 0.000 | -10.961 | -0.000 |
F4 SE APARTMENT | 0.920 | -24.077 | 0.000 | 0.000 | 3.659 | 1.087 | 12.213 | 27.553 | 0.000 | 0.766 | 0.016 | 0.000 | -10.479 | 0.000 | -11.657 | -0.000 |
F4 NE APARTMENT | 3.671 | -15.407 | 0.000 | 0.000 | 3.760 | 1.087 | 12.213 | 13.867 | 0.000 | 0.752 | 1.108 | 0.000 | -10.136 | 0.000 | -10.915 | -0.000 |
F4 N1 APARTMENT | 1.128 | -11.848 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 4.283 | 0.000 | 0.535 | 3.251 | 0.000 | -6.619 | 0.000 | -7.785 | 0.000 |
F4 N2 APARTMENT | 1.133 | -11.884 | 0.000 | 0.000 | 3.756 | 1.087 | 12.213 | 4.280 | 0.000 | 0.535 | 3.280 | 0.000 | -6.614 | 0.000 | -7.785 | 0.000 |
F4 S1 APARTMENT | 0.186 | -21.642 | 0.000 | 0.000 | 3.614 | 1.087 | 12.213 | 17.966 | 0.000 | 0.525 | 1.214 | 0.000 | -6.596 | 0.000 | -8.566 | -0.000 |
F4 S2 APARTMENT | 0.187 | -21.689 | 0.000 | 0.000 | 3.615 | 1.087 | 12.213 | 17.963 | 0.000 | 0.526 | 1.263 | 0.000 | -6.594 | 0.000 | -8.570 | -0.000 |
M SW APARTMENT | 1.180 | -22.990 | 0.000 | 0.000 | 3.652 | 1.087 | 12.213 | 26.681 | 0.000 | 0.826 | 0.667 | 0.000 | -10.837 | 0.000 | -12.479 | -0.001 |
M NW APARTMENT | 4.250 | -14.605 | 0.000 | 0.000 | 3.746 | 1.087 | 12.213 | 13.255 | 0.000 | 0.814 | 1.732 | 0.000 | -10.748 | 0.000 | -11.743 | -0.000 |
M SE APARTMENT | 1.047 | -24.066 | 0.000 | 0.000 | 3.663 | 1.087 | 12.213 | 27.440 | 0.000 | 0.821 | 0.796 | 0.000 | -10.525 | 0.000 | -12.476 | -0.000 |
M NE APARTMENT | 3.895 | -15.604 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 13.797 | 0.000 | 0.804 | 1.933 | 0.000 | -10.194 | 0.000 | -11.692 | -0.000 |
M N1 APARTMENT | 1.194 | -12.113 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 4.256 | 0.000 | 0.571 | 4.020 | 0.000 | -6.666 | 0.000 | -8.316 | 0.000 |
M N2 APARTMENT | 1.199 | -12.151 | 0.000 | 0.000 | 3.756 | 1.087 | 12.213 | 4.253 | 0.000 | 0.570 | 4.050 | 0.000 | -6.661 | 0.000 | -8.316 | 0.000 |
M S1 APARTMENT | 0.211 | -21.831 | 0.000 | 0.000 | 3.615 | 1.087 | 12.213 | 17.890 | 0.000 | 0.562 | 2.019 | 0.000 | -6.631 | 0.000 | -9.133 | -0.000 |
M S2 APARTMENT | 0.212 | -21.871 | 0.000 | 0.000 | 3.616 | 1.087 | 12.213 | 17.887 | 0.000 | 0.562 | 2.060 | 0.000 | -6.629 | 0.000 | -9.136 | -0.000 |
F6 SW APARTMENT | 1.449 | -21.914 | 0.000 | 0.000 | 3.663 | 1.087 | 12.213 | 26.620 | 0.000 | 0.872 | 0.001 | 0.000 | -10.818 | 0.000 | -13.131 | -0.040 |
F6 NW APARTMENT | 4.893 | -14.020 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 13.235 | 0.000 | 0.859 | 1.057 | 0.000 | -10.737 | 0.000 | -12.342 | -0.000 |
F6 SE APARTMENT | 1.304 | -22.957 | 0.000 | 0.000 | 3.674 | 1.087 | 12.213 | 27.383 | 0.000 | 0.867 | 0.067 | 0.000 | -10.506 | 0.000 | -13.131 | -0.000 |
F6 NE APARTMENT | 4.499 | -14.964 | 0.000 | 0.000 | 3.770 | 1.087 | 12.213 | 13.779 | 0.000 | 0.848 | 1.241 | 0.000 | -10.181 | 0.000 | -12.292 | -0.000 |
F6 N1 APARTMENT | 1.478 | -11.469 | 0.000 | 0.000 | 3.764 | 1.087 | 12.213 | 4.257 | 0.000 | 0.600 | 3.419 | 0.000 | -6.658 | 0.000 | -8.692 | 0.000 |
F6 N2 APARTMENT | 1.484 | -11.505 | 0.000 | 0.000 | 3.765 | 1.087 | 12.213 | 4.254 | 0.000 | 0.600 | 3.449 | 0.000 | -6.653 | 0.000 | -8.693 | 0.000 |
F6 S1 APARTMENT | 0.258 | -20.807 | 0.000 | 0.000 | 3.627 | 1.087 | 12.213 | 17.851 | 0.000 | 0.591 | 1.365 | 0.000 | -6.620 | 0.000 | -9.565 | -0.000 |
F6 S2 APARTMENT | 0.258 | -20.844 | 0.000 | 0.000 | 3.627 | 1.087 | 12.213 | 17.849 | 0.000 | 0.592 | 1.404 | 0.000 | -6.618 | 0.000 | -9.568 | -0.000 |
F7 SW APARTMENT | 1.707 | -21.246 | 0.000 | 0.000 | 3.671 | 1.087 | 12.213 | 26.561 | 0.000 | 0.912 | 0.001 | 0.000 | -10.814 | 0.000 | -13.708 | -0.382 |
F7 NW APARTMENT | 5.424 | -13.733 | 0.000 | 0.000 | 3.762 | 1.087 | 12.213 | 13.211 | 0.000 | 0.897 | 0.756 | 0.000 | -10.739 | 0.000 | -12.879 | -0.000 |
F7 SE APARTMENT | 1.549 | -22.275 | 0.000 | 0.000 | 3.682 | 1.087 | 12.213 | 27.326 | 0.000 | 0.907 | 0.001 | 0.000 | -10.501 | 0.000 | -13.708 | -0.279 |
F7 NE APARTMENT | 4.991 | -14.645 | 0.000 | 0.000 | 3.776 | 1.087 | 12.213 | 13.756 | 0.000 | 0.886 | 0.943 | 0.000 | -10.182 | 0.000 | -12.826 | -0.000 |
F7 N1 APARTMENT | 1.718 | -11.122 | 0.000 | 0.000 | 3.771 | 1.087 | 12.213 | 4.254 | 0.000 | 0.625 | 3.143 | 0.000 | -6.658 | 0.000 | -9.031 | 0.000 |
F7 N2 APARTMENT | 1.727 | -11.162 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 4.251 | 0.000 | 0.625 | 3.173 | 0.000 | -6.653 | 0.000 | -9.032 | 0.000 |
F7 S1 APARTMENT | 0.306 | -20.162 | 0.000 | 0.000 | 3.636 | 1.087 | 12.213 | 17.815 | 0.000 | 0.618 | 1.048 | 0.000 | -6.616 | 0.000 | -9.943 | -0.000 |
F7 S2 APARTMENT | 0.308 | -20.200 | 0.000 | 0.000 | 3.637 | 1.087 | 12.213 | 17.812 | 0.000 | 0.618 | 1.087 | 0.000 | -6.614 | 0.000 | -9.947 | -0.000 |
F8 SW APARTMENT | 1.990 | -20.738 | 0.000 | 0.000 | 3.679 | 1.087 | 12.213 | 26.508 | 0.000 | 0.954 | 0.001 | 0.000 | -10.810 | 0.000 | -14.241 | -0.641 |
F8 NW APARTMENT | 5.937 | -13.594 | 0.000 | 0.000 | 3.767 | 1.087 | 12.213 | 13.187 | 0.000 | 0.938 | 0.593 | 0.000 | -10.746 | 0.000 | -13.381 | -0.000 |
F8 SE APARTMENT | 1.814 | -21.754 | 0.000 | 0.000 | 3.689 | 1.087 | 12.213 | 27.276 | 0.000 | 0.949 | 0.001 | 0.000 | -10.498 | 0.000 | -14.243 | -0.532 |
F8 NE APARTMENT | 5.470 | -14.470 | 0.000 | 0.000 | 3.781 | 1.087 | 12.213 | 13.733 | 0.000 | 0.925 | 0.776 | 0.000 | -10.187 | 0.000 | -13.327 | -0.000 |
F8 N1 APARTMENT | 1.975 | -10.930 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 4.249 | 0.000 | 0.654 | 2.994 | 0.000 | -6.661 | 0.000 | -9.358 | -0.000 |
F8 N2 APARTMENT | 1.981 | -10.967 | 0.000 | 0.000 | 3.778 | 1.087 | 12.213 | 4.246 | 0.000 | 0.653 | 3.025 | 0.000 | -6.657 | 0.000 | -9.358 | -0.000 |
F8 S1 APARTMENT | 0.366 | -19.640 | 0.000 | 0.000 | 3.645 | 1.087 | 12.213 | 17.783 | 0.000 | 0.648 | 0.805 | 0.000 | -6.611 | 0.000 | -10.296 | -0.000 |
F8 S2 APARTMENT | 0.367 | -19.678 | 0.000 | 0.000 | 3.646 | 1.087 | 12.213 | 17.780 | 0.000 | 0.648 | 0.846 | 0.000 | -6.609 | 0.000 | -10.300 | -0.000 |
F9 SW APARTMENT | 2.591 | -20.371 | 0.000 | 0.000 | 3.689 | 1.087 | 12.213 | 26.483 | 0.000 | 0.994 | 0.003 | 0.000 | -10.786 | 0.000 | -14.700 | -1.201 |
F9 NW APARTMENT | 6.862 | -13.832 | 0.000 | 0.000 | 3.771 | 1.087 | 12.213 | 13.170 | 0.000 | 0.975 | 0.340 | 0.000 | -10.749 | 0.000 | -13.836 | -0.000 |
F9 SE APARTMENT | 2.352 | -21.336 | 0.000 | 0.000 | 3.699 | 1.087 | 12.213 | 27.250 | 0.000 | 0.990 | 0.002 | 0.000 | -10.474 | 0.000 | -14.705 | -1.075 |
F9 NE APARTMENT | 6.274 | -14.591 | 0.000 | 0.000 | 3.785 | 1.087 | 12.213 | 13.718 | 0.000 | 0.960 | 0.525 | 0.000 | -10.190 | 0.000 | -13.780 | -0.001 |
F9 N1 APARTMENT | 2.504 | -10.975 | 0.000 | 0.000 | 3.781 | 1.087 | 12.213 | 4.246 | 0.000 | 0.681 | 2.781 | 0.000 | -6.661 | 0.000 | -9.656 | -0.000 |
F9 N2 APARTMENT | 2.511 | -11.013 | 0.000 | 0.000 | 3.782 | 1.087 | 12.213 | 4.243 | 0.000 | 0.681 | 2.813 | 0.000 | -6.657 | 0.000 | -9.658 | -0.001 |
F9 S1 APARTMENT | 0.513 | -19.083 | 0.000 | 0.000 | 3.660 | 1.087 | 12.213 | 17.770 | 0.000 | 0.678 | 0.335 | 0.000 | -6.587 | 0.000 | -10.585 | -0.000 |
F9 S2 APARTMENT | 0.516 | -19.127 | 0.000 | 0.000 | 3.660 | 1.087 | 12.213 | 17.767 | 0.000 | 0.679 | 0.380 | 0.000 | -6.585 | 0.000 | -10.590 | -0.000 |
T SW APARTMENT | 7.763 | -22.357 | 0.000 | 0.000 | 3.740 | 1.087 | 12.213 | 26.132 | 0.000 | 1.026 | 0.000 | 0.000 | -10.211 | 0.000 | -14.979 | -4.414 |
T NW APARTMENT | 11.831 | -15.451 | 0.000 | 0.000 | 3.785 | 1.087 | 12.213 | 12.847 | 0.000 | 1.002 | 0.000 | 0.000 | -10.340 | 0.000 | -14.324 | -2.648 |
T SE APARTMENT | 7.219 | -22.718 | 0.000 | 0.000 | 3.749 | 1.087 | 12.213 | 26.923 | 0.000 | 1.026 | 0.000 | 0.000 | -9.934 | 0.000 | -14.991 | -4.574 |
T NE APARTMENT | 10.902 | -15.748 | 0.000 | 0.000 | 3.801 | 1.087 | 12.213 | 13.460 | 0.000 | 1.002 | 0.000 | 0.000 | -9.841 | 0.000 | -14.258 | -2.617 |
T N1 APARTMENT | 5.904 | -11.697 | 0.000 | 0.000 | 3.794 | 1.087 | 12.213 | 4.128 | 0.000 | 0.704 | 0.288 | 0.000 | -6.420 | 0.000 | -10.000 | -0.001 |
T N2 APARTMENT | 5.922 | -11.734 | 0.000 | 0.000 | 3.795 | 1.087 | 12.213 | 4.122 | 0.000 | 0.704 | 0.312 | 0.000 | -6.414 | 0.000 | -10.007 | -0.000 |
T S1 APARTMENT | 2.908 | -19.287 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 17.594 | 0.000 | 0.718 | 0.000 | 0.000 | -6.266 | 0.000 | -10.754 | -1.936 |
T S2 APARTMENT | 2.917 | -19.340 | 0.000 | 0.000 | 3.723 | 1.087 | 12.213 | 17.589 | 0.000 | 0.718 | 0.001 | 0.000 | -6.262 | 0.000 | -10.759 | -1.885 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 6.615 | 0.000 | 2.626 | 19.201 | 0.000 | -2.253 | 0.000 | -42.628 | -0.002 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 3.005 | 0.000 | 0.038 | 0.000 | 0.000 | -1.326 | 0.000 | -1.091 | -17.065 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.954 | 0.000 | 0.043 | 0.000 | 0.000 | -1.373 | 0.000 | -1.333 | -16.731 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.927 | 0.000 | 0.047 | 0.000 | 0.000 | -1.393 | 0.000 | -1.506 | -16.514 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 2.895 | 0.000 | 0.043 | 0.000 | 0.000 | -1.423 | 0.000 | -1.709 | -32.686 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.906 | 0.000 | 0.054 | 0.000 | 0.000 | -1.399 | 0.000 | -1.742 | -16.258 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.906 | 0.000 | 0.058 | 0.000 | 0.000 | -1.392 | 0.000 | -1.823 | -16.189 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.902 | 0.000 | 0.060 | 0.000 | 0.000 | -1.390 | 0.000 | -1.902 | -16.110 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 2.899 | 0.000 | 0.060 | 0.000 | 0.000 | -1.389 | 0.000 | -1.973 | -16.036 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 2.828 | 0.000 | 0.031 | 0.000 | 0.000 | -1.344 | 0.000 | -2.111 | -23.995 |
Total Facility | 199.330 | -1329.417 | 0.000 | 0.000 | 294.418 | 296.560 | 982.450 | 1293.533 | 0.000 | 56.807 | 93.448 | 0.000 | -690.091 | 0.000 | -869.152 | -327.876 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-SEP-14:30 | 0.00 | -2495.10 | 0.00 | 0.00 | 39.18 | 22.70 | 400.26 | 4654.53 | 0.00 | 59.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2681.19 |
G NW APARTMENT | 22-JUL-17:30 | 0.00 | -2332.07 | 0.00 | 0.00 | 140.63 | 87.56 | 588.62 | 3088.07 | 0.00 | 192.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1765.57 |
OFFICE | 12-SEP-12:30 | 0.00 | -3518.24 | 0.00 | 0.00 | 65.15 | 2345.88 | 588.62 | 3073.98 | 0.00 | 55.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2611.29 |
G NE APARTMENT | 28-JUN-08:15 | 0.00 | -1725.89 | 0.00 | 0.00 | 40.62 | 12.97 | 394.37 | 2859.14 | 0.00 | 191.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1773.19 |
G N1 APARTMENT | 16-JUN-19:45 | 0.00 | -1169.29 | 0.00 | 0.00 | 141.66 | 103.77 | 523.87 | 0.00 | 0.00 | 226.43 | 208.45 | 0.00 | -34.88 | 0.00 | 0.00 | 0.00 |
G N2 APARTMENT | 29-JUN-18:00 | 0.00 | -1156.10 | 0.00 | 0.00 | 140.95 | 87.56 | 588.62 | 432.66 | 0.00 | 49.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -142.88 |
G S1 APARTMENT | 29-SEP-11:30 | 0.00 | -1429.90 | 0.00 | 0.00 | 39.69 | 12.97 | 406.15 | 3273.03 | 0.00 | 69.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2371.02 |
G S2 APARTMENT | 29-SEP-11:30 | 0.00 | -1497.06 | 0.00 | 0.00 | 39.74 | 12.97 | 406.15 | 3272.07 | 0.00 | 70.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2304.75 |
F2 SW APARTMENT | 10-OCT-16:15 | 0.00 | -3215.52 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 3043.60 | 0.00 | 506.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1072.92 |
F2 NW APARTMENT | 18-JUL-17:20 | 0.00 | -2982.87 | 0.00 | 0.00 | 138.30 | 87.56 | 588.62 | 3302.45 | 0.00 | 283.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1417.43 |
F2 SE APARTMENT | 01-OCT-12:00 | 0.00 | -2928.47 | 0.00 | 0.00 | 40.50 | 12.97 | 406.15 | 3719.43 | 0.00 | 66.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1317.27 |
F2 NE APARTMENT | 28-JUN-07:38 | 0.00 | -2306.08 | 0.00 | 0.00 | 63.57 | 19.46 | 388.49 | 2911.92 | 0.00 | 108.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1185.51 |
F2 N1 APARTMENT | 24-JUN-19:30 | 0.00 | -1580.15 | 0.00 | 0.00 | 140.96 | 103.77 | 523.87 | 0.00 | 0.00 | 232.79 | 615.02 | 0.00 | -36.27 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 29-JUN-20:15 | 0.00 | -1575.62 | 0.00 | 0.00 | 163.01 | 71.34 | 500.33 | 0.00 | 0.00 | 278.03 | 585.26 | 0.00 | -22.34 | 0.00 | 0.00 | 0.00 |
F2 S1 APARTMENT | 01-NOV-12:30 | 0.00 | -2060.71 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3597.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.76 | -1640.34 |
F2 S2 APARTMENT | 01-NOV-12:30 | 0.00 | -2084.52 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 3597.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.68 | -1616.26 |
F3 SW APARTMENT | 10-OCT-16:00 | 0.00 | -3264.02 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3284.35 | 0.00 | 660.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1245.98 |
F3 NW APARTMENT | 18-JUL-17:20 | 0.00 | -3020.02 | 0.00 | 0.00 | 137.99 | 87.56 | 588.62 | 3278.43 | 0.00 | 333.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1406.09 |
F3 SE APARTMENT | 01-OCT-11:00 | 0.00 | -2744.74 | 0.00 | 0.00 | 40.59 | 12.97 | 412.03 | 3985.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39.41 | -1666.84 |
F3 NE APARTMENT | 28-JUN-08:15 | 0.00 | -2353.89 | 0.00 | 0.00 | 40.54 | 12.97 | 394.37 | 2819.37 | 0.00 | 230.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1143.66 |
F3 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1703.45 | 0.00 | 0.00 | 162.93 | 71.34 | 500.33 | 2.10 | 0.00 | 595.56 | 371.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1688.61 | 0.00 | 0.00 | 162.91 | 71.34 | 500.33 | 2.11 | 0.00 | 592.17 | 359.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2129.54 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3993.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2329.45 |
F3 S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2139.85 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3993.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2318.95 |
F4 SW APARTMENT | 10-OCT-15:53 | 0.00 | -3285.50 | 0.00 | 0.00 | 48.89 | 45.40 | 470.89 | 3265.87 | 0.00 | 788.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1334.54 |
F4 NW APARTMENT | 18-JUL-17:45 | 0.00 | -3036.57 | 0.00 | 0.00 | 137.43 | 87.56 | 588.62 | 3086.00 | 0.00 | 352.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1215.76 |
F4 SE APARTMENT | 01-OCT-11:00 | 0.00 | -2745.41 | 0.00 | 0.00 | 40.59 | 12.97 | 412.03 | 3976.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43.50 | -1653.59 |
F4 NE APARTMENT | 02-AUG-09:00 | 0.00 | -2366.26 | 0.00 | 0.00 | 40.56 | 12.97 | 394.37 | 2624.90 | 0.00 | 539.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1245.66 |
F4 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1723.48 | 0.00 | 0.00 | 162.88 | 71.34 | 500.33 | 3.21 | 0.00 | 635.18 | 350.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1708.74 | 0.00 | 0.00 | 162.86 | 71.34 | 500.33 | 3.18 | 0.00 | 631.21 | 339.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2151.86 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2305.49 |
F4 S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2159.92 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2297.31 |
M SW APARTMENT | 10-OCT-15:53 | 0.00 | -3326.73 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3251.64 | 0.00 | 840.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1330.49 |
M NW APARTMENT | 18-JUL-17:45 | 0.00 | -3067.65 | 0.00 | 0.00 | 137.19 | 87.56 | 588.62 | 3073.19 | 0.00 | 381.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1200.10 |
M SE APARTMENT | 11-OCT-12:45 | 0.00 | -2793.07 | 0.00 | 0.00 | 40.10 | 12.97 | 388.49 | 3163.39 | 0.00 | 877.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1688.89 |
M NE APARTMENT | 02-AUG-09:00 | 0.00 | -2408.53 | 0.00 | 0.00 | 40.55 | 12.97 | 394.37 | 2612.16 | 0.00 | 572.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1224.25 |
M N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1763.85 | 0.00 | 0.00 | 162.85 | 71.34 | 500.33 | 3.49 | 0.00 | 667.37 | 358.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1749.34 | 0.00 | 0.00 | 162.83 | 71.34 | 500.33 | 3.44 | 0.00 | 662.97 | 348.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2185.19 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3990.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2271.05 |
M S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2192.85 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3990.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2263.29 |
F6 SW APARTMENT | 10-OCT-15:53 | 0.00 | -3296.07 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3241.95 | 0.00 | 880.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1391.86 |
F6 NW APARTMENT | 18-JUL-17:45 | 0.00 | -3031.67 | 0.00 | 0.00 | 136.91 | 87.56 | 588.62 | 3064.04 | 0.00 | 404.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1250.30 |
F6 SE APARTMENT | 11-OCT-12:45 | 0.00 | -2770.49 | 0.00 | 0.00 | 40.13 | 12.97 | 388.49 | 3153.70 | 0.00 | 921.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1746.55 |
F6 NE APARTMENT | 02-AUG-09:00 | 0.00 | -2379.23 | 0.00 | 0.00 | 40.53 | 12.97 | 394.37 | 2603.53 | 0.00 | 597.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1269.79 |
F6 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1737.22 | 0.00 | 0.00 | 162.82 | 71.34 | 500.33 | 4.77 | 0.00 | 688.98 | 308.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1722.83 | 0.00 | 0.00 | 162.80 | 71.34 | 500.33 | 4.69 | 0.00 | 684.15 | 299.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2154.83 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3990.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2301.89 |
F6 S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2162.43 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3990.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2294.19 |
F7 SW APARTMENT | 10-OCT-15:53 | 0.00 | -3287.86 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3233.36 | 0.00 | 915.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1426.19 |
F7 NW APARTMENT | 18-JUL-17:45 | 0.00 | -3020.76 | 0.00 | 0.00 | 136.69 | 87.56 | 588.62 | 3055.80 | 0.00 | 425.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1273.51 |
F7 SE APARTMENT | 11-OCT-12:45 | 0.00 | -2767.97 | 0.00 | 0.00 | 40.16 | 12.97 | 388.49 | 3145.27 | 0.00 | 960.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1779.75 |
F7 NE APARTMENT | 02-AUG-09:00 | 0.00 | -2381.79 | 0.00 | 0.00 | 40.53 | 12.97 | 394.37 | 2595.77 | 0.00 | 621.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1283.38 |
F7 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1733.24 | 0.00 | 0.00 | 162.80 | 71.34 | 500.33 | 5.35 | 0.00 | 707.37 | 286.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1718.93 | 0.00 | 0.00 | 162.78 | 71.34 | 500.33 | 5.26 | 0.00 | 702.27 | 276.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2144.64 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2312.27 |
F7 S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2152.23 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2304.58 |
F8 SW APARTMENT | 10-OCT-15:53 | 0.00 | -3293.13 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3225.88 | 0.00 | 947.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1445.08 |
F8 NW APARTMENT | 18-JUL-17:45 | 0.00 | -3024.71 | 0.00 | 0.00 | 136.53 | 87.56 | 588.62 | 3048.32 | 0.00 | 444.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1280.55 |
F8 SE APARTMENT | 11-OCT-12:45 | 0.00 | -2778.13 | 0.00 | 0.00 | 40.20 | 12.97 | 388.49 | 3138.12 | 0.00 | 998.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1800.14 |
F8 NE APARTMENT | 02-AUG-09:00 | 0.00 | -2386.68 | 0.00 | 0.00 | 40.51 | 12.97 | 394.37 | 2588.60 | 0.00 | 639.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1289.58 |
F8 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1743.26 | 0.00 | 0.00 | 162.78 | 71.34 | 500.33 | 5.50 | 0.00 | 723.80 | 279.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1728.92 | 0.00 | 0.00 | 162.71 | 71.34 | 500.33 | 5.35 | 0.00 | 718.14 | 271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 30-DEC-12:00 | 0.00 | -2134.29 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2323.23 |
F8 S2 APARTMENT | 30-DEC-12:00 | 0.00 | -2141.01 | 0.00 | 0.00 | 40.75 | 12.97 | 412.03 | 3991.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2316.40 |
F9 SW APARTMENT | 10-OCT-15:38 | 0.00 | -3402.09 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3491.22 | 0.00 | 989.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1643.95 |
F9 NW APARTMENT | 18-JUL-17:45 | 0.00 | -3134.86 | 0.00 | 0.00 | 136.63 | 87.56 | 588.62 | 3038.99 | 0.00 | 462.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1179.32 |
F9 SE APARTMENT | 11-OCT-12:45 | 0.00 | -2865.24 | 0.00 | 0.00 | 40.37 | 12.97 | 388.49 | 3133.24 | 0.00 | 1073.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1783.65 |
F9 NE APARTMENT | 02-AUG-09:00 | 0.00 | -2428.69 | 0.00 | 0.00 | 40.55 | 12.97 | 394.37 | 2582.21 | 0.00 | 664.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1266.30 |
F9 N1 APARTMENT | 23-JUN-21:00 | 0.00 | -1843.91 | 0.00 | 0.00 | 162.78 | 71.34 | 500.33 | 3.41 | 0.00 | 746.06 | 359.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 23-JUN-21:00 | 0.00 | -1829.57 | 0.00 | 0.00 | 162.76 | 71.34 | 500.33 | 3.36 | 0.00 | 741.11 | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 07-NOV-12:45 | 0.00 | -2119.18 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3673.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.00 | -1897.31 |
F9 S2 APARTMENT | 07-NOV-12:45 | 0.00 | -2126.99 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 3673.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.02 | -1889.30 |
T SW APARTMENT | 10-OCT-15:38 | 0.00 | -4180.29 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3447.76 | 0.00 | 1102.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -935.26 |
T NW APARTMENT | 18-JUL-17:20 | 0.00 | -3901.77 | 0.00 | 0.00 | 137.04 | 87.56 | 588.62 | 3160.09 | 0.00 | 504.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -576.01 |
T SE APARTMENT | 11-OCT-13:00 | 0.00 | -3634.04 | 0.00 | 0.00 | 40.40 | 12.97 | 388.49 | 2962.31 | 0.00 | 1432.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1202.63 |
T NE APARTMENT | 05-JUL-08:45 | 0.00 | -3085.70 | 0.00 | 0.00 | 40.75 | 12.97 | 394.37 | 2711.27 | 0.00 | 303.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -377.25 |
T N1 APARTMENT | 23-JUN-21:00 | 0.00 | -2401.79 | 0.00 | 0.00 | 162.99 | 71.34 | 500.33 | 5.20 | 0.00 | 1009.31 | 652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 23-JUN-21:00 | 0.00 | -2388.47 | 0.00 | 0.00 | 162.99 | 71.34 | 500.33 | 5.63 | 0.00 | 1009.31 | 638.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 01-OCT-12:00 | 0.00 | -2937.80 | 0.00 | 0.00 | 39.34 | 12.97 | 406.15 | 3382.19 | 0.00 | 24.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -927.67 |
T S2 APARTMENT | 01-OCT-12:00 | 0.00 | -2945.57 | 0.00 | 0.00 | 39.28 | 12.97 | 406.15 | 3381.37 | 0.00 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -917.28 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-17:00 | 0.00 | -175720.16 | 0.00 | 0.00 | 6630.14 | 11327.17 | 47312.53 | 95458.61 | 0.00 | 34140.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19148.61 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 18-JAN-01:15 | 1451.52 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -978.04 | 0.00 | -775.27 | -135.71 |
G NW APARTMENT | 14-DEC-04:00 | 1707.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 44.71 | 0.00 | -996.46 | 0.00 | -1175.95 | 0.00 |
OFFICE | 17-JAN-07:53 | 1431.30 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -778.83 | 0.00 | -803.33 | -612.63 |
G NE APARTMENT | 14-DEC-04:00 | 1749.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -986.42 | 0.00 | -1175.95 | -6.67 |
G N1 APARTMENT | 20-MAR-11:55 | 1256.23 | 0.00 | 0.00 | 0.00 | 46.33 | 12.97 | 406.15 | 370.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1193.93 | -898.61 |
G N2 APARTMENT | 20-MAR-11:55 | 1249.98 | 0.00 | 0.00 | 0.00 | 46.35 | 12.97 | 406.15 | 370.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1193.88 | -892.43 |
G S1 APARTMENT | 20-MAR-12:00 | 1038.20 | 0.00 | 0.00 | 0.00 | 43.99 | 12.97 | 406.15 | 1754.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1310.30 | -1945.36 |
G S2 APARTMENT | 19-MAR-16:00 | 853.96 | 0.00 | 0.00 | 0.00 | 52.31 | 45.40 | 470.89 | 56.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1186.92 | -291.99 |
F2 SW APARTMENT | 18-JAN-01:15 | 1604.43 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 91.51 | 0.00 | -1018.39 | 0.00 | -1115.05 | 0.00 |
F2 NW APARTMENT | 14-DEC-04:00 | 2071.46 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 235.04 | 0.00 | -1034.93 | 0.00 | -1691.40 | 0.00 |
F2 SE APARTMENT | 18-JAN-01:15 | 1531.16 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 176.79 | 0.00 | -1030.40 | 0.00 | -1115.04 | 0.00 |
F2 NE APARTMENT | 14-DEC-04:00 | 2142.30 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 149.89 | 0.00 | -1020.62 | 0.00 | -1691.40 | 0.00 |
F2 N1 APARTMENT | 09-NOV-10:00 | 1328.64 | 0.00 | 0.00 | 0.00 | 43.58 | 12.97 | 394.37 | 123.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1645.79 | -256.92 |
F2 N2 APARTMENT | 09-NOV-10:00 | 1315.41 | 0.00 | 0.00 | 0.00 | 43.60 | 12.97 | 394.37 | 123.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1645.71 | -243.97 |
F2 S1 APARTMENT | 18-JAN-01:30 | 763.52 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 89.68 | 0.00 | -627.29 | 0.00 | -663.40 | 0.00 |
F2 S2 APARTMENT | 18-JAN-01:30 | 757.82 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 95.60 | 0.00 | -627.50 | 0.00 | -663.40 | 0.00 |
F3 SW APARTMENT | 18-JAN-01:15 | 1718.40 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 200.64 | 0.00 | -1035.55 | 0.00 | -1320.98 | 0.00 |
F3 NW APARTMENT | 14-DEC-04:00 | 2310.57 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 323.92 | 0.00 | -1050.46 | 0.00 | -2003.86 | 0.00 |
F3 SE APARTMENT | 18-JAN-01:15 | 1724.62 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 204.38 | 0.00 | -1045.51 | 0.00 | -1320.98 | 0.00 |
F3 NE APARTMENT | 14-DEC-04:00 | 2383.40 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 235.39 | 0.00 | -1034.76 | 0.00 | -2003.86 | 0.00 |
F3 N1 APARTMENT | 09-NOV-10:00 | 1622.08 | 0.00 | 0.00 | 0.00 | 42.96 | 12.97 | 394.37 | 107.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1881.97 | -297.82 |
F3 N2 APARTMENT | 09-NOV-10:00 | 1596.98 | 0.00 | 0.00 | 0.00 | 42.99 | 12.97 | 394.37 | 107.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1881.86 | -273.14 |
F3 S1 APARTMENT | 18-JAN-01:15 | 804.73 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 196.05 | 0.00 | -641.49 | 0.00 | -796.78 | 0.00 |
F3 S2 APARTMENT | 18-JAN-01:15 | 804.56 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 196.22 | 0.00 | -641.50 | 0.00 | -796.78 | 0.00 |
F4 SW APARTMENT | 18-JAN-01:15 | 1855.82 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 229.31 | 0.00 | -1045.19 | 0.00 | -1477.44 | 0.00 |
F4 NW APARTMENT | 14-DEC-04:00 | 2531.10 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 349.24 | 0.00 | -1058.89 | 0.00 | -2241.29 | 0.00 |
F4 SE APARTMENT | 18-JAN-01:15 | 1873.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 221.92 | 0.00 | -1055.60 | 0.00 | -1477.44 | 0.00 |
F4 NE APARTMENT | 14-DEC-04:00 | 2601.44 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 262.62 | 0.00 | -1042.60 | 0.00 | -2241.29 | 0.00 |
F4 N1 APARTMENT | 09-NOV-10:15 | 1522.47 | 0.00 | 0.00 | 0.00 | 42.94 | 12.97 | 406.15 | 121.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1927.88 | -178.21 |
F4 N2 APARTMENT | 09-NOV-10:15 | 1505.25 | 0.00 | 0.00 | 0.00 | 42.97 | 12.97 | 406.15 | 121.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1927.78 | -161.44 |
F4 S1 APARTMENT | 18-JAN-01:15 | 884.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 217.05 | 0.00 | -648.32 | 0.00 | -891.15 | 0.00 |
F4 S2 APARTMENT | 18-JAN-01:15 | 885.68 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 216.26 | 0.00 | -648.28 | 0.00 | -891.15 | 0.00 |
M SW APARTMENT | 18-JAN-01:15 | 1970.54 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 251.24 | 0.00 | -1052.63 | 0.00 | -1606.64 | 0.00 |
M NW APARTMENT | 14-DEC-04:00 | 2711.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 371.73 | 0.00 | -1065.38 | 0.00 | -2437.38 | 0.00 |
M SE APARTMENT | 18-JAN-01:15 | 1989.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 242.93 | 0.00 | -1063.71 | 0.00 | -1606.64 | 0.00 |
M NE APARTMENT | 14-DEC-04:00 | 2777.65 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 288.75 | 0.00 | -1048.85 | 0.00 | -2437.38 | 0.00 |
M N1 APARTMENT | 09-NOV-10:15 | 1544.52 | 0.00 | 0.00 | 0.00 | 42.91 | 12.97 | 406.15 | 116.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2075.08 | -48.42 |
M N2 APARTMENT | 09-NOV-10:15 | 1526.35 | 0.00 | 0.00 | 0.00 | 42.94 | 12.97 | 406.15 | 117.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2074.99 | -30.68 |
M S1 APARTMENT | 18-JAN-01:15 | 951.83 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 233.25 | 0.00 | -653.49 | 0.00 | -969.08 | 0.00 |
M S2 APARTMENT | 18-JAN-01:15 | 952.76 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 232.27 | 0.00 | -653.45 | 0.00 | -969.08 | 0.00 |
F6 SW APARTMENT | 18-JAN-01:00 | 2121.34 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 216.68 | 0.00 | -1057.47 | 0.00 | -1741.59 | 0.00 |
F6 NW APARTMENT | 14-DEC-04:00 | 2917.40 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 337.27 | 0.00 | -1067.80 | 0.00 | -2606.70 | 0.00 |
F6 SE APARTMENT | 18-JAN-01:00 | 2141.49 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 208.20 | 0.00 | -1069.13 | 0.00 | -1741.59 | 0.00 |
F6 NE APARTMENT | 14-DEC-04:00 | 2978.21 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 260.08 | 0.00 | -1051.42 | 0.00 | -2606.71 | 0.00 |
F6 N1 APARTMENT | 24-JAN-14:55 | 1703.11 | 0.00 | 0.00 | 0.00 | 45.29 | 12.97 | 382.60 | 170.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1746.94 | -567.53 |
F6 N2 APARTMENT | 24-JAN-14:55 | 1714.22 | 0.00 | 0.00 | 0.00 | 45.30 | 12.97 | 382.60 | 170.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1746.66 | -579.02 |
F6 S1 APARTMENT | 18-JAN-01:15 | 1043.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 211.54 | 0.00 | -655.87 | 0.00 | -1036.36 | 0.00 |
F6 S2 APARTMENT | 18-JAN-01:15 | 1044.09 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 210.61 | 0.00 | -655.83 | 0.00 | -1036.36 | 0.00 |
F7 SW APARTMENT | 18-JAN-01:00 | 2247.21 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 194.46 | 0.00 | -1060.76 | 0.00 | -1841.94 | 0.00 |
F7 NW APARTMENT | 14-DEC-04:00 | 3089.75 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 317.76 | 0.00 | -1070.32 | 0.00 | -2757.02 | 0.00 |
F7 SE APARTMENT | 18-JAN-01:00 | 2267.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 186.24 | 0.00 | -1072.86 | 0.00 | -1841.94 | 0.00 |
F7 NE APARTMENT | 14-DEC-04:00 | 3146.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 245.23 | 0.00 | -1054.05 | 0.00 | -2757.03 | 0.00 |
F7 N1 APARTMENT | 24-JAN-14:55 | 1968.93 | 0.00 | 0.00 | 0.00 | 45.46 | 12.97 | 382.60 | 170.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1829.79 | -750.62 |
F7 N2 APARTMENT | 24-JAN-14:55 | 1979.42 | 0.00 | 0.00 | 0.00 | 45.47 | 12.97 | 382.60 | 170.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1829.53 | -761.46 |
F7 S1 APARTMENT | 18-JAN-01:15 | 1118.58 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 198.13 | 0.00 | -658.12 | 0.00 | -1096.08 | 0.00 |
F7 S2 APARTMENT | 18-JAN-01:15 | 1119.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.33 | 0.00 | 0.00 | 0.00 | 197.29 | 0.00 | -658.08 | 0.00 | -1096.08 | 0.00 |
F8 SW APARTMENT | 18-JAN-01:00 | 2371.03 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 163.87 | 0.00 | -1063.19 | 0.00 | -1932.75 | 0.00 |
F8 NW APARTMENT | 14-DEC-04:00 | 3247.07 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 298.59 | 0.00 | -1072.44 | 0.00 | -2893.05 | 0.00 |
F8 SE APARTMENT | 18-JAN-01:00 | 2391.04 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 156.36 | 0.00 | -1075.68 | 0.00 | -1932.75 | 0.00 |
F8 NE APARTMENT | 14-DEC-04:00 | 3300.97 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 228.44 | 0.00 | -1056.20 | 0.00 | -2893.05 | 0.00 |
F8 N1 APARTMENT | 24-JAN-14:55 | 2087.75 | 0.00 | 0.00 | 0.00 | 45.62 | 12.97 | 382.60 | 170.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1909.01 | -790.41 |
F8 N2 APARTMENT | 24-JAN-14:55 | 2088.93 | 0.00 | 0.00 | 0.00 | 45.62 | 12.97 | 382.60 | 170.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1908.96 | -791.70 |
F8 S1 APARTMENT | 20-MAR-12:15 | 1474.64 | 0.00 | 0.00 | 0.00 | 42.05 | 12.97 | 388.49 | 1732.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2329.63 | -1321.27 |
F8 S2 APARTMENT | 20-MAR-12:15 | 1468.45 | 0.00 | 0.00 | 0.00 | 42.05 | 12.97 | 388.49 | 1732.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2329.80 | -1314.84 |
F9 SW APARTMENT | 18-JAN-01:00 | 2564.02 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 53.08 | 0.00 | -1062.08 | 0.00 | -2016.06 | 0.00 |
F9 NW APARTMENT | 14-DEC-04:00 | 3440.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 229.13 | 0.00 | -1071.78 | 0.00 | -3017.87 | 0.00 |
F9 SE APARTMENT | 14-DEC-04:00 | 2602.17 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 1084.29 | 0.00 | -1088.43 | 0.00 | -3017.87 | 0.00 |
F9 NE APARTMENT | 14-DEC-04:00 | 3499.09 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 154.44 | 0.00 | -1055.48 | 0.00 | -3017.88 | 0.00 |
F9 N1 APARTMENT | 09-NOV-10:10 | 2288.12 | 0.00 | 0.00 | 0.00 | 44.33 | 12.97 | 406.15 | 123.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2542.59 | -332.54 |
F9 N2 APARTMENT | 09-NOV-10:10 | 2302.58 | 0.00 | 0.00 | 0.00 | 44.35 | 12.97 | 406.15 | 123.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2542.17 | -347.61 |
F9 S1 APARTMENT | 09-NOV-10:15 | 1566.57 | 0.00 | 0.00 | 0.00 | 41.13 | 12.97 | 406.15 | 127.10 | 0.00 | 0.00 | 381.99 | 0.00 | 0.00 | 0.00 | -2535.90 | 0.00 |
F9 S2 APARTMENT | 09-NOV-10:15 | 1563.18 | 0.00 | 0.00 | 0.00 | 41.11 | 12.97 | 406.15 | 126.98 | 0.00 | 0.00 | 385.73 | 0.00 | 0.00 | 0.00 | -2536.12 | 0.00 |
T SW APARTMENT | 14-DEC-04:00 | 3624.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 141.34 | 0.00 | -1052.42 | 0.00 | -3133.38 | 0.00 |
T NW APARTMENT | 14-DEC-04:00 | 4095.89 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1041.73 | 0.00 | -3133.38 | -340.61 |
T SE APARTMENT | 14-DEC-04:00 | 3645.60 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 105.49 | 0.00 | -1037.54 | 0.00 | -3133.38 | 0.00 |
T NE APARTMENT | 14-DEC-04:00 | 4124.46 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1027.34 | 0.00 | -3133.39 | -383.57 |
T N1 APARTMENT | 09-NOV-10:10 | 2653.21 | 0.00 | 0.00 | 0.00 | 44.17 | 12.97 | 406.15 | 125.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2640.05 | -601.78 |
T N2 APARTMENT | 09-NOV-10:10 | 2604.79 | 0.00 | 0.00 | 0.00 | 44.07 | 12.97 | 406.15 | 123.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2642.30 | -549.64 |
T S1 APARTMENT | 09-NOV-10:15 | 2062.58 | 0.00 | 0.00 | 0.00 | 40.94 | 12.97 | 406.15 | 126.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2632.18 | -16.46 |
T S2 APARTMENT | 09-NOV-10:15 | 2064.05 | 0.00 | 0.00 | 0.00 | 40.90 | 12.97 | 406.15 | 125.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2632.34 | -17.19 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-DEC-04:00 | 136531.46 | 0.00 | 0.00 | 0.00 | 14983.75 | 6715.87 | 17923.60 | 0.00 | 0.00 | 0.00 | 51717.52 | 0.00 | -70030.81 | 0.00 | -157841.39 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Sec1.1A-General InformationData | |
Weather File | Albuquerque Intl Arpt Isis NM USA TMY3 WMO#=723650 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 105.00 |
Number of hours cooling loads not met | 525.25 |
Number of hours not met | 639.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.84 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 70.42 | 0.00 | 194.94 | 150090.38 | 0.00 | 0.00 |
Space Cooling | 496.27 | 60361.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.36 | 1741.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.58 | 1886.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 740.36 | 23476.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1090.21 | 79368.04 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 49889.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3011.89 | 1285.16 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 3011.89 |
Natural Gas | 0.00 | 1285.16 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4297.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 8.99 |
Space Cooling | 63.33 |
Fans-Interior | 94.48 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 34.58 |
Subtotal | 384.34 |
Natural Gas [MJ/m2] | |
Space Heating | 24.88 |
Service Water Heating | 139.12 |
Miscellaneous | 0.00 |
Subtotal | 164.00 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.90 |
Space Heating | 6.18 |
Space Cooling | 11.55 |
Fans-Interior | 17.23 |
Service Water Heating | 25.37 |
Receptacle Equipment | 26.47 |
Miscellaneous | 6.31 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.261865 |
G NW APARTMENT DIRECT AIR | 0.256992 |
OFFICE DIRECT AIR | 0.375203 |
G NE APARTMENT DIRECT AIR | 0.186744 |
G N1 APARTMENT DIRECT AIR | 0.131508 |
G N2 APARTMENT DIRECT AIR | 0.129530 |
G S1 APARTMENT DIRECT AIR | 0.138971 |
G S2 APARTMENT DIRECT AIR | 0.146296 |
F2 SW APARTMENT DIRECT AIR | 0.336816 |
F2 NW APARTMENT DIRECT AIR | 0.328085 |
F2 SE APARTMENT DIRECT AIR | 0.302169 |
F2 NE APARTMENT DIRECT AIR | 0.248800 |
F2 N1 APARTMENT DIRECT AIR | 0.174616 |
F2 N2 APARTMENT DIRECT AIR | 0.172998 |
F2 S1 APARTMENT DIRECT AIR | 0.186418 |
F2 S2 APARTMENT DIRECT AIR | 0.188984 |
F3 SW APARTMENT DIRECT AIR | 0.339857 |
F3 NW APARTMENT DIRECT AIR | 0.331767 |
F3 SE APARTMENT DIRECT AIR | 0.282576 |
F3 NE APARTMENT DIRECT AIR | 0.253655 |
F3 N1 APARTMENT DIRECT AIR | 0.179094 |
F3 N2 APARTMENT DIRECT AIR | 0.177490 |
F3 S1 APARTMENT DIRECT AIR | 0.191466 |
F3 S2 APARTMENT DIRECT AIR | 0.192572 |
F4 SW APARTMENT DIRECT AIR | 0.342486 |
F4 NW APARTMENT DIRECT AIR | 0.334463 |
F4 SE APARTMENT DIRECT AIR | 0.283590 |
F4 NE APARTMENT DIRECT AIR | 0.255926 |
F4 N1 APARTMENT DIRECT AIR | 0.181545 |
F4 N2 APARTMENT DIRECT AIR | 0.179947 |
F4 S1 APARTMENT DIRECT AIR | 0.194100 |
F4 S2 APARTMENT DIRECT AIR | 0.194994 |
M SW APARTMENT DIRECT AIR | 0.347058 |
M NW APARTMENT DIRECT AIR | 0.339217 |
M SE APARTMENT DIRECT AIR | 0.288480 |
M NE APARTMENT DIRECT AIR | 0.260199 |
M N1 APARTMENT DIRECT AIR | 0.185837 |
M N2 APARTMENT DIRECT AIR | 0.184252 |
M S1 APARTMENT DIRECT AIR | 0.198495 |
M S2 APARTMENT DIRECT AIR | 0.199357 |
F6 SW APARTMENT DIRECT AIR | 0.344659 |
F6 NW APARTMENT DIRECT AIR | 0.336789 |
F6 SE APARTMENT DIRECT AIR | 0.286688 |
F6 NE APARTMENT DIRECT AIR | 0.257490 |
F6 N1 APARTMENT DIRECT AIR | 0.183402 |
F6 N2 APARTMENT DIRECT AIR | 0.181828 |
F6 S1 APARTMENT DIRECT AIR | 0.196169 |
F6 S2 APARTMENT DIRECT AIR | 0.197027 |
F7 SW APARTMENT DIRECT AIR | 0.344589 |
F7 NW APARTMENT DIRECT AIR | 0.336795 |
F7 SE APARTMENT DIRECT AIR | 0.287134 |
F7 NE APARTMENT DIRECT AIR | 0.257311 |
F7 N1 APARTMENT DIRECT AIR | 0.183286 |
F7 N2 APARTMENT DIRECT AIR | 0.181721 |
F7 S1 APARTMENT DIRECT AIR | 0.196086 |
F7 S2 APARTMENT DIRECT AIR | 0.196943 |
F8 SW APARTMENT DIRECT AIR | 0.345965 |
F8 NW APARTMENT DIRECT AIR | 0.338234 |
F8 SE APARTMENT DIRECT AIR | 0.288856 |
F8 NE APARTMENT DIRECT AIR | 0.258470 |
F8 N1 APARTMENT DIRECT AIR | 0.184608 |
F8 N2 APARTMENT DIRECT AIR | 0.183053 |
F8 S1 APARTMENT DIRECT AIR | 0.197351 |
F8 S2 APARTMENT DIRECT AIR | 0.198210 |
F9 SW APARTMENT DIRECT AIR | 0.358570 |
F9 NW APARTMENT DIRECT AIR | 0.350643 |
F9 SE APARTMENT DIRECT AIR | 0.298457 |
F9 NE APARTMENT DIRECT AIR | 0.263722 |
F9 N1 APARTMENT DIRECT AIR | 0.195353 |
F9 N2 APARTMENT DIRECT AIR | 0.193789 |
F9 S1 APARTMENT DIRECT AIR | 0.205446 |
F9 S2 APARTMENT DIRECT AIR | 0.206264 |
T SW APARTMENT DIRECT AIR | 0.443737 |
T NW APARTMENT DIRECT AIR | 0.430023 |
T SE APARTMENT DIRECT AIR | 0.382005 |
T NE APARTMENT DIRECT AIR | 0.337625 |
T N1 APARTMENT DIRECT AIR | 0.256846 |
T N2 APARTMENT DIRECT AIR | 0.256548 |
T S1 APARTMENT DIRECT AIR | 0.298508 |
T S2 APARTMENT DIRECT AIR | 0.299185 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.261865 |
AIRLOOP G NW MAIN BRANCH | 0.256992 |
AIRLOOP OFFICE MAIN BRANCH | 0.375203 |
AIRLOOP G NE MAIN BRANCH | 0.186744 |
AIRLOOP G N1 MAIN BRANCH | 0.131508 |
AIRLOOP G N2 MAIN BRANCH | 0.129530 |
AIRLOOP G S1 MAIN BRANCH | 0.138971 |
AIRLOOP G S2 MAIN BRANCH | 0.146296 |
AIRLOOP F2 SW MAIN BRANCH | 0.336816 |
AIRLOOP F2 NW MAIN BRANCH | 0.328085 |
AIRLOOP F2 SE MAIN BRANCH | 0.302169 |
AIRLOOP F2 NE MAIN BRANCH | 0.248800 |
AIRLOOP F2 N1 MAIN BRANCH | 0.174616 |
AIRLOOP F2 N2 MAIN BRANCH | 0.172998 |
AIRLOOP F2 S1 MAIN BRANCH | 0.186418 |
AIRLOOP F2 S2 MAIN BRANCH | 0.188984 |
AIRLOOP F3 SW MAIN BRANCH | 0.339857 |
AIRLOOP F3 NW MAIN BRANCH | 0.331767 |
AIRLOOP F3 SE MAIN BRANCH | 0.282576 |
AIRLOOP F3 NE MAIN BRANCH | 0.253655 |
AIRLOOP F3 N1 MAIN BRANCH | 0.179094 |
AIRLOOP F3 N2 MAIN BRANCH | 0.177490 |
AIRLOOP F3 S1 MAIN BRANCH | 0.191466 |
AIRLOOP F3 S2 MAIN BRANCH | 0.192572 |
AIRLOOP F4 SW MAIN BRANCH | 0.342486 |
AIRLOOP F4 NW MAIN BRANCH | 0.334463 |
AIRLOOP F4 SE MAIN BRANCH | 0.283590 |
AIRLOOP F4 NE MAIN BRANCH | 0.255926 |
AIRLOOP F4 N1 MAIN BRANCH | 0.181545 |
AIRLOOP F4 N2 MAIN BRANCH | 0.179947 |
AIRLOOP F4 S1 MAIN BRANCH | 0.194100 |
AIRLOOP F4 S2 MAIN BRANCH | 0.194994 |
AIRLOOP M SW MAIN BRANCH | 0.347058 |
AIRLOOP M NW MAIN BRANCH | 0.339217 |
AIRLOOP M SE MAIN BRANCH | 0.288480 |
AIRLOOP M NE MAIN BRANCH | 0.260199 |
AIRLOOP M N1 MAIN BRANCH | 0.185837 |
AIRLOOP M N2 MAIN BRANCH | 0.184252 |
AIRLOOP M S1 MAIN BRANCH | 0.198495 |
AIRLOOP M S2 MAIN BRANCH | 0.199357 |
AIRLOOP F6 SW MAIN BRANCH | 0.344659 |
AIRLOOP F6 NW MAIN BRANCH | 0.336789 |
AIRLOOP F6 SE MAIN BRANCH | 0.286688 |
AIRLOOP F6 NE MAIN BRANCH | 0.257490 |
AIRLOOP F6 N1 MAIN BRANCH | 0.183402 |
AIRLOOP F6 N2 MAIN BRANCH | 0.181828 |
AIRLOOP F6 S1 MAIN BRANCH | 0.196169 |
AIRLOOP F6 S2 MAIN BRANCH | 0.197027 |
AIRLOOP F7 SW MAIN BRANCH | 0.344589 |
AIRLOOP F7 NW MAIN BRANCH | 0.336795 |
AIRLOOP F7 SE MAIN BRANCH | 0.287134 |
AIRLOOP F7 NE MAIN BRANCH | 0.257311 |
AIRLOOP F7 N1 MAIN BRANCH | 0.183286 |
AIRLOOP F7 N2 MAIN BRANCH | 0.181721 |
AIRLOOP F7 S1 MAIN BRANCH | 0.196086 |
AIRLOOP F7 S2 MAIN BRANCH | 0.196943 |
AIRLOOP F8 SW MAIN BRANCH | 0.345965 |
AIRLOOP F8 NW MAIN BRANCH | 0.338234 |
AIRLOOP F8 SE MAIN BRANCH | 0.288856 |
AIRLOOP F8 NE MAIN BRANCH | 0.258470 |
AIRLOOP F8 N1 MAIN BRANCH | 0.184608 |
AIRLOOP F8 N2 MAIN BRANCH | 0.183053 |
AIRLOOP F8 S1 MAIN BRANCH | 0.197351 |
AIRLOOP F8 S2 MAIN BRANCH | 0.198210 |
AIRLOOP F9 SW MAIN BRANCH | 0.358570 |
AIRLOOP F9 NW MAIN BRANCH | 0.350643 |
AIRLOOP F9 SE MAIN BRANCH | 0.298457 |
AIRLOOP F9 NE MAIN BRANCH | 0.263722 |
AIRLOOP F9 N1 MAIN BRANCH | 0.195353 |
AIRLOOP F9 N2 MAIN BRANCH | 0.193789 |
AIRLOOP F9 S1 MAIN BRANCH | 0.205446 |
AIRLOOP F9 S2 MAIN BRANCH | 0.206264 |
AIRLOOP T SW MAIN BRANCH | 0.443737 |
AIRLOOP T NW MAIN BRANCH | 0.430023 |
AIRLOOP T SE MAIN BRANCH | 0.382005 |
AIRLOOP T NE MAIN BRANCH | 0.337625 |
AIRLOOP T N1 MAIN BRANCH | 0.256846 |
AIRLOOP T N2 MAIN BRANCH | 0.256548 |
AIRLOOP T S1 MAIN BRANCH | 0.298508 |
AIRLOOP T S2 MAIN BRANCH | 0.299185 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.261865 |
AIRLOOP G NW | 0.256992 |
AIRLOOP OFFICE | 0.375203 |
AIRLOOP G NE | 0.186744 |
AIRLOOP G N1 | 0.131508 |
AIRLOOP G N2 | 0.129530 |
AIRLOOP G S1 | 0.138971 |
AIRLOOP G S2 | 0.146296 |
AIRLOOP F2 SW | 0.336816 |
AIRLOOP F2 NW | 0.328085 |
AIRLOOP F2 SE | 0.302169 |
AIRLOOP F2 NE | 0.248800 |
AIRLOOP F2 N1 | 0.174616 |
AIRLOOP F2 N2 | 0.172998 |
AIRLOOP F2 S1 | 0.186418 |
AIRLOOP F2 S2 | 0.188984 |
AIRLOOP F3 SW | 0.339857 |
AIRLOOP F3 NW | 0.331767 |
AIRLOOP F3 SE | 0.282576 |
AIRLOOP F3 NE | 0.253655 |
AIRLOOP F3 N1 | 0.179094 |
AIRLOOP F3 N2 | 0.177490 |
AIRLOOP F3 S1 | 0.191466 |
AIRLOOP F3 S2 | 0.192572 |
AIRLOOP F4 SW | 0.342486 |
AIRLOOP F4 NW | 0.334463 |
AIRLOOP F4 SE | 0.283590 |
AIRLOOP F4 NE | 0.255926 |
AIRLOOP F4 N1 | 0.181545 |
AIRLOOP F4 N2 | 0.179947 |
AIRLOOP F4 S1 | 0.194100 |
AIRLOOP F4 S2 | 0.194994 |
AIRLOOP M SW | 0.347058 |
AIRLOOP M NW | 0.339217 |
AIRLOOP M SE | 0.288480 |
AIRLOOP M NE | 0.260199 |
AIRLOOP M N1 | 0.185837 |
AIRLOOP M N2 | 0.184252 |
AIRLOOP M S1 | 0.198495 |
AIRLOOP M S2 | 0.199357 |
AIRLOOP F6 SW | 0.344659 |
AIRLOOP F6 NW | 0.336789 |
AIRLOOP F6 SE | 0.286688 |
AIRLOOP F6 NE | 0.257490 |
AIRLOOP F6 N1 | 0.183402 |
AIRLOOP F6 N2 | 0.181828 |
AIRLOOP F6 S1 | 0.196169 |
AIRLOOP F6 S2 | 0.197027 |
AIRLOOP F7 SW | 0.344589 |
AIRLOOP F7 NW | 0.336795 |
AIRLOOP F7 SE | 0.287134 |
AIRLOOP F7 NE | 0.257311 |
AIRLOOP F7 N1 | 0.183286 |
AIRLOOP F7 N2 | 0.181721 |
AIRLOOP F7 S1 | 0.196086 |
AIRLOOP F7 S2 | 0.196943 |
AIRLOOP F8 SW | 0.345965 |
AIRLOOP F8 NW | 0.338234 |
AIRLOOP F8 SE | 0.288856 |
AIRLOOP F8 NE | 0.258470 |
AIRLOOP F8 N1 | 0.184608 |
AIRLOOP F8 N2 | 0.183053 |
AIRLOOP F8 S1 | 0.197351 |
AIRLOOP F8 S2 | 0.198210 |
AIRLOOP F9 SW | 0.358570 |
AIRLOOP F9 NW | 0.350643 |
AIRLOOP F9 SE | 0.298457 |
AIRLOOP F9 NE | 0.263722 |
AIRLOOP F9 N1 | 0.195353 |
AIRLOOP F9 N2 | 0.193789 |
AIRLOOP F9 S1 | 0.205446 |
AIRLOOP F9 S2 | 0.206264 |
AIRLOOP T SW | 0.443737 |
AIRLOOP T NW | 0.430023 |
AIRLOOP T SE | 0.382005 |
AIRLOOP T NE | 0.337625 |
AIRLOOP T N1 | 0.256846 |
AIRLOOP T N2 | 0.256548 |
AIRLOOP T S1 | 0.298508 |
AIRLOOP T S2 | 0.299185 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.261865 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.256992 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.375203 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.186744 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.131508 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.129530 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.138971 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.146296 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.336816 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.328085 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.302169 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.248800 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.174616 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.172998 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.186418 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.188984 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.339857 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.331767 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.282576 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.253655 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.179094 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.177490 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.191466 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.192572 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.342486 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.334463 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.283590 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.255926 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.181545 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.179947 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.194100 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.194994 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.347058 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.339217 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.288480 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.260199 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.185837 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.184252 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.198495 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.199357 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.344659 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.336789 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.286688 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.257490 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.183402 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.181828 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.196169 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.197027 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.344589 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.336795 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.287134 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.257311 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.183286 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.181721 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.196086 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.196943 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.345965 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.338234 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.288856 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.258470 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.184608 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.183053 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.197351 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.198210 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.358570 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.350643 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.298457 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.263722 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.195353 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.193789 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.205446 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.206264 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.443737 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.430023 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.382005 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.337625 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.256846 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.256548 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.298508 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.299185 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.261865 | 3205.13 | 2086.17 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.256992 | 3136.29 | 2042.61 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.375203 | 4571.65 | 2982.58 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.186744 | 2235.31 | 1482.58 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.131508 | 1610.05 | 1060.80 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.129530 | 1585.74 | 1045.39 | 0.000035 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.138971 | 1790.21 | 1157.32 | 0.000039 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.146296 | 1874.97 | 1212.83 | 0.000041 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.336816 | 4083.63 | 2661.66 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.328085 | 3968.98 | 2588.31 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.302169 | 3709.07 | 2413.66 | 0.000081 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.248800 | 2955.28 | 1957.90 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.174616 | 2120.03 | 1393.05 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.172998 | 2100.22 | 1380.48 | 0.000046 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.186418 | 2348.56 | 1523.76 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.188984 | 2379.83 | 1543.73 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.339857 | 4099.50 | 2681.69 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.331767 | 3992.78 | 2613.32 | 0.000087 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.282576 | 3450.55 | 2258.26 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.253655 | 2994.18 | 1992.19 | 0.000065 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.179094 | 2162.96 | 1425.86 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.177490 | 2143.35 | 1413.40 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.191466 | 2398.22 | 1561.04 | 0.000052 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.192572 | 2411.72 | 1569.66 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.342486 | 4115.74 | 2699.43 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.334463 | 4016.31 | 2634.80 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.283590 | 3447.95 | 2263.63 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.255926 | 3006.86 | 2007.32 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.181545 | 2184.05 | 1443.42 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.179947 | 2164.55 | 1431.01 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.194100 | 2421.46 | 1580.05 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.194994 | 2432.36 | 1587.00 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.347058 | 4158.53 | 2732.71 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.339217 | 4061.50 | 2669.53 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.288480 | 3495.15 | 2299.51 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.260199 | 3046.55 | 2038.40 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.185837 | 2231.85 | 1479.05 | 0.000049 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.184252 | 2212.59 | 1466.76 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.198495 | 2467.66 | 1613.00 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.199357 | 2478.17 | 1619.71 | 0.000054 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.344659 | 4118.48 | 2712.30 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.336789 | 4021.15 | 2648.90 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.286688 | 3463.15 | 2283.91 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.257490 | 3003.59 | 2015.76 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.183402 | 2196.01 | 1459.13 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.181828 | 2176.92 | 1446.93 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.196169 | 2433.36 | 1593.91 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.197027 | 2443.82 | 1600.59 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.344589 | 4108.10 | 2710.17 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.336795 | 4011.78 | 2647.38 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.287134 | 3459.59 | 2285.87 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.257311 | 3006.60 | 2018.43 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.183286 | 2189.24 | 1457.34 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.181721 | 2170.27 | 1445.21 | 0.000047 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.196086 | 2427.05 | 1592.38 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.196943 | 2437.49 | 1599.05 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.345965 | 4116.29 | 2719.41 | 0.000090 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.338234 | 4020.82 | 2657.12 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.288856 | 3472.41 | 2297.88 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.258470 | 3012.72 | 2026.10 | 0.000066 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.184608 | 2200.53 | 1466.80 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.183053 | 2181.69 | 1454.75 | 0.000048 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.197351 | 2437.62 | 1601.42 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.198210 | 2448.08 | 1608.09 | 0.000053 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.358570 | 4261.51 | 2815.74 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.350643 | 4163.87 | 2751.97 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.298457 | 3585.82 | 2372.82 | 0.000078 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.263722 | 3068.81 | 2065.52 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.195353 | 2326.72 | 1549.40 | 0.000051 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.193789 | 2307.77 | 1537.29 | 0.000050 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.205446 | 2531.51 | 1663.57 | 0.000055 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.206264 | 2541.48 | 1669.94 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.443737 | 5311.88 | 3485.44 | 0.000116 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.430023 | 5134.82 | 3374.01 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.382005 | 4586.60 | 3017.05 | 0.000100 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.337625 | 4053.30 | 2675.11 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.256846 | 3150.60 | 2061.78 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.256548 | 3147.08 | 2059.48 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.298508 | 3656.71 | 2384.97 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.299185 | 3665.00 | 2390.23 | 0.000080 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.261865 | 0.261865 | 0.261865 | 0.261865 | 3205.13 | 3205.13 | 2756.67 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.256992 | 0.256992 | 0.256992 | 0.256992 | 3136.29 | 3136.29 | 2757.08 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.375203 | 0.375203 | 0.375203 | 0.375203 | 4571.65 | 4571.65 | 3460.54 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.186744 | 0.186744 | 0.186744 | 0.186744 | 2235.31 | 2235.31 | 2757.08 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.131508 | 0.131508 | 0.131508 | 0.131508 | 1610.05 | 1610.05 | 2051.84 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.129530 | 0.129530 | 0.129530 | 0.129530 | 1585.74 | 1585.74 | 2051.84 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.138971 | 0.138971 | 0.138971 | 0.138971 | 1790.21 | 1790.21 | 2047.88 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.146296 | 0.146296 | 0.146296 | 0.146296 | 1874.97 | 1874.97 | 2054.16 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.336816 | 0.336816 | 0.336816 | 0.336816 | 4083.63 | 4083.63 | 2735.79 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.328085 | 0.328085 | 0.328085 | 0.328085 | 3968.98 | 3968.98 | 2733.39 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.302169 | 0.302169 | 0.302169 | 0.302169 | 3709.07 | 3709.07 | 2754.50 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.248800 | 0.248800 | 0.248800 | 0.248800 | 2955.28 | 2955.28 | 2733.39 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.174616 | 0.174616 | 0.174616 | 0.174616 | 2120.03 | 2120.03 | 1854.16 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.172998 | 0.172998 | 0.172998 | 0.172998 | 2100.22 | 2100.22 | 1854.16 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.186418 | 0.186418 | 0.186418 | 0.186418 | 2348.56 | 2348.56 | 1859.28 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.188984 | 0.188984 | 0.188984 | 0.188984 | 2379.83 | 2379.83 | 1860.51 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.339857 | 0.339857 | 0.339857 | 0.339857 | 4099.50 | 4099.50 | 2759.41 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.331767 | 0.331767 | 0.331767 | 0.331767 | 3992.78 | 3992.78 | 2759.94 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.282576 | 0.282576 | 0.282576 | 0.282576 | 3450.55 | 3450.55 | 2761.48 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.253655 | 0.253655 | 0.253655 | 0.253655 | 2994.18 | 2994.18 | 2759.94 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.179094 | 0.179094 | 0.179094 | 0.179094 | 2162.96 | 2162.96 | 1835.79 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.177490 | 0.177490 | 0.177490 | 0.177490 | 2143.35 | 2143.35 | 1835.79 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.191466 | 0.191466 | 0.191466 | 0.191466 | 2398.22 | 2398.22 | 1835.99 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.192572 | 0.192572 | 0.192572 | 0.192572 | 2411.72 | 2411.72 | 1836.18 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.342486 | 0.342486 | 0.342486 | 0.342486 | 4115.74 | 4115.74 | 2823.85 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.334463 | 0.334463 | 0.334463 | 0.334463 | 4016.31 | 4016.31 | 2826.48 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.283590 | 0.283590 | 0.283590 | 0.283590 | 3447.95 | 3447.95 | 2824.06 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.255926 | 0.255926 | 0.255926 | 0.255926 | 3006.86 | 3006.86 | 2826.48 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.181545 | 0.181545 | 0.181545 | 0.181545 | 2184.05 | 2184.05 | 1866.24 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.179947 | 0.179947 | 0.179947 | 0.179947 | 2164.55 | 2164.55 | 1866.24 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.194100 | 0.194100 | 0.194100 | 0.194100 | 2421.46 | 2421.46 | 1864.05 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.194994 | 0.194994 | 0.194994 | 0.194994 | 2432.36 | 2432.36 | 1864.07 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.347058 | 0.347058 | 0.347058 | 0.347058 | 4158.53 | 4158.53 | 2864.82 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.339217 | 0.339217 | 0.339217 | 0.339217 | 4061.50 | 4061.50 | 2867.93 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.288480 | 0.288480 | 0.288480 | 0.288480 | 3495.15 | 3495.15 | 2864.84 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.260199 | 0.260199 | 0.260199 | 0.260199 | 3046.55 | 3046.55 | 2867.93 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.185837 | 0.185837 | 0.185837 | 0.185837 | 2231.85 | 2231.85 | 1879.85 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.184252 | 0.184252 | 0.184252 | 0.184252 | 2212.59 | 2212.59 | 1879.85 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.198495 | 0.198495 | 0.198495 | 0.198495 | 2467.66 | 2467.66 | 1877.13 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.199357 | 0.199357 | 0.199357 | 0.199357 | 2478.17 | 2478.17 | 1877.13 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.344659 | 0.344659 | 0.344659 | 0.344659 | 4118.48 | 4118.48 | 2960.79 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.336789 | 0.336789 | 0.336789 | 0.336789 | 4021.15 | 4021.15 | 2965.87 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.286688 | 0.286688 | 0.286688 | 0.286688 | 3463.15 | 3463.15 | 2960.79 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.257490 | 0.257490 | 0.257490 | 0.257490 | 3003.59 | 3003.59 | 2965.87 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.183402 | 0.183402 | 0.183402 | 0.183402 | 2196.01 | 2196.01 | 1951.07 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.181828 | 0.181828 | 0.181828 | 0.181828 | 2176.92 | 2176.92 | 1951.07 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.196169 | 0.196169 | 0.196169 | 0.196169 | 2433.36 | 2433.36 | 1946.32 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.197027 | 0.197027 | 0.197027 | 0.197027 | 2443.82 | 2443.82 | 1946.32 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.344589 | 0.344589 | 0.344589 | 0.344589 | 4108.10 | 4108.10 | 3029.36 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.336795 | 0.336795 | 0.336795 | 0.336795 | 4011.78 | 4011.78 | 3035.21 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.287134 | 0.287134 | 0.287134 | 0.287134 | 3459.59 | 3459.59 | 3029.36 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.257311 | 0.257311 | 0.257311 | 0.257311 | 3006.60 | 3006.60 | 3035.21 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.183286 | 0.183286 | 0.183286 | 0.183286 | 2189.24 | 2189.24 | 1998.43 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.181721 | 0.181721 | 0.181721 | 0.181721 | 2170.27 | 2170.27 | 1998.43 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.196086 | 0.196086 | 0.196086 | 0.196086 | 2427.05 | 2427.05 | 1992.91 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.196943 | 0.196943 | 0.196943 | 0.196943 | 2437.49 | 2437.49 | 1992.91 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.345965 | 0.345965 | 0.345965 | 0.345965 | 4116.29 | 4116.29 | 3100.69 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.338234 | 0.338234 | 0.338234 | 0.338234 | 4020.82 | 4020.82 | 3106.95 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.288856 | 0.288856 | 0.288856 | 0.288856 | 3472.41 | 3472.41 | 3100.69 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.258470 | 0.258470 | 0.258470 | 0.258470 | 3012.72 | 3012.72 | 3106.95 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.184608 | 0.184608 | 0.184608 | 0.184608 | 2200.53 | 2200.53 | 2050.70 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.183053 | 0.183053 | 0.183053 | 0.183053 | 2181.69 | 2181.69 | 2050.70 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.197351 | 0.197351 | 0.197351 | 0.197351 | 2437.62 | 2437.62 | 2044.75 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.198210 | 0.198210 | 0.198210 | 0.198210 | 2448.08 | 2448.08 | 2044.75 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.358570 | 0.358570 | 0.358570 | 0.358570 | 4261.51 | 4261.51 | 3289.74 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.350643 | 0.350643 | 0.350643 | 0.350643 | 4163.87 | 4163.87 | 3294.09 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.298457 | 0.298457 | 0.298457 | 0.298457 | 3585.82 | 3585.82 | 3289.74 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.263722 | 0.263722 | 0.263722 | 0.263722 | 3068.81 | 3068.81 | 3294.09 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.195353 | 0.195353 | 0.195353 | 0.195353 | 2326.72 | 2326.72 | 2212.13 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.193789 | 0.193789 | 0.193789 | 0.193789 | 2307.77 | 2307.77 | 2212.13 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.205446 | 0.205446 | 0.205446 | 0.205446 | 2531.51 | 2531.51 | 2207.63 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.206264 | 0.206264 | 0.206264 | 0.206264 | 2541.48 | 2541.48 | 2207.63 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.443737 | 0.443737 | 0.443737 | 0.443737 | 5311.88 | 5311.88 | 3902.78 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.430023 | 0.430023 | 0.430023 | 0.430023 | 5134.82 | 5134.82 | 3913.70 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.382005 | 0.382005 | 0.382005 | 0.382005 | 4586.60 | 4586.60 | 3902.78 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.337625 | 0.337625 | 0.337625 | 0.337625 | 4053.30 | 4053.30 | 3913.70 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.256846 | 0.256846 | 0.256846 | 0.256846 | 3150.60 | 3150.60 | 2870.02 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.256548 | 0.256548 | 0.256548 | 0.256548 | 3147.08 | 3147.08 | 2870.02 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.298508 | 0.298508 | 0.298508 | 0.298508 | 3656.71 | 3656.71 | 2856.07 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.299185 | 0.299185 | 0.299185 | 0.299185 | 3665.00 | 3665.00 | 2856.07 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.261865 |
AIRLOOP G NW SUPPLY FAN | 0.256992 |
AIRLOOP OFFICE SUPPLY FAN | 0.375203 |
AIRLOOP G NE SUPPLY FAN | 0.186744 |
AIRLOOP G N1 SUPPLY FAN | 0.131508 |
AIRLOOP G N2 SUPPLY FAN | 0.129530 |
AIRLOOP G S1 SUPPLY FAN | 0.138971 |
AIRLOOP G S2 SUPPLY FAN | 0.146296 |
AIRLOOP F2 SW SUPPLY FAN | 0.336816 |
AIRLOOP F2 NW SUPPLY FAN | 0.328085 |
AIRLOOP F2 SE SUPPLY FAN | 0.302169 |
AIRLOOP F2 NE SUPPLY FAN | 0.248800 |
AIRLOOP F2 N1 SUPPLY FAN | 0.174616 |
AIRLOOP F2 N2 SUPPLY FAN | 0.172998 |
AIRLOOP F2 S1 SUPPLY FAN | 0.186418 |
AIRLOOP F2 S2 SUPPLY FAN | 0.188984 |
AIRLOOP F3 SW SUPPLY FAN | 0.339857 |
AIRLOOP F3 NW SUPPLY FAN | 0.331767 |
AIRLOOP F3 SE SUPPLY FAN | 0.282576 |
AIRLOOP F3 NE SUPPLY FAN | 0.253655 |
AIRLOOP F3 N1 SUPPLY FAN | 0.179094 |
AIRLOOP F3 N2 SUPPLY FAN | 0.177490 |
AIRLOOP F3 S1 SUPPLY FAN | 0.191466 |
AIRLOOP F3 S2 SUPPLY FAN | 0.192572 |
AIRLOOP F4 SW SUPPLY FAN | 0.342486 |
AIRLOOP F4 NW SUPPLY FAN | 0.334463 |
AIRLOOP F4 SE SUPPLY FAN | 0.283590 |
AIRLOOP F4 NE SUPPLY FAN | 0.255926 |
AIRLOOP F4 N1 SUPPLY FAN | 0.181545 |
AIRLOOP F4 N2 SUPPLY FAN | 0.179947 |
AIRLOOP F4 S1 SUPPLY FAN | 0.194100 |
AIRLOOP F4 S2 SUPPLY FAN | 0.194994 |
AIRLOOP M SW SUPPLY FAN | 0.347058 |
AIRLOOP M NW SUPPLY FAN | 0.339217 |
AIRLOOP M SE SUPPLY FAN | 0.288480 |
AIRLOOP M NE SUPPLY FAN | 0.260199 |
AIRLOOP M N1 SUPPLY FAN | 0.185837 |
AIRLOOP M N2 SUPPLY FAN | 0.184252 |
AIRLOOP M S1 SUPPLY FAN | 0.198495 |
AIRLOOP M S2 SUPPLY FAN | 0.199357 |
AIRLOOP F6 SW SUPPLY FAN | 0.344659 |
AIRLOOP F6 NW SUPPLY FAN | 0.336789 |
AIRLOOP F6 SE SUPPLY FAN | 0.286688 |
AIRLOOP F6 NE SUPPLY FAN | 0.257490 |
AIRLOOP F6 N1 SUPPLY FAN | 0.183402 |
AIRLOOP F6 N2 SUPPLY FAN | 0.181828 |
AIRLOOP F6 S1 SUPPLY FAN | 0.196169 |
AIRLOOP F6 S2 SUPPLY FAN | 0.197027 |
AIRLOOP F7 SW SUPPLY FAN | 0.344589 |
AIRLOOP F7 NW SUPPLY FAN | 0.336795 |
AIRLOOP F7 SE SUPPLY FAN | 0.287134 |
AIRLOOP F7 NE SUPPLY FAN | 0.257311 |
AIRLOOP F7 N1 SUPPLY FAN | 0.183286 |
AIRLOOP F7 N2 SUPPLY FAN | 0.181721 |
AIRLOOP F7 S1 SUPPLY FAN | 0.196086 |
AIRLOOP F7 S2 SUPPLY FAN | 0.196943 |
AIRLOOP F8 SW SUPPLY FAN | 0.345965 |
AIRLOOP F8 NW SUPPLY FAN | 0.338234 |
AIRLOOP F8 SE SUPPLY FAN | 0.288856 |
AIRLOOP F8 NE SUPPLY FAN | 0.258470 |
AIRLOOP F8 N1 SUPPLY FAN | 0.184608 |
AIRLOOP F8 N2 SUPPLY FAN | 0.183053 |
AIRLOOP F8 S1 SUPPLY FAN | 0.197351 |
AIRLOOP F8 S2 SUPPLY FAN | 0.198210 |
AIRLOOP F9 SW SUPPLY FAN | 0.358570 |
AIRLOOP F9 NW SUPPLY FAN | 0.350643 |
AIRLOOP F9 SE SUPPLY FAN | 0.298457 |
AIRLOOP F9 NE SUPPLY FAN | 0.263722 |
AIRLOOP F9 N1 SUPPLY FAN | 0.195353 |
AIRLOOP F9 N2 SUPPLY FAN | 0.193789 |
AIRLOOP F9 S1 SUPPLY FAN | 0.205446 |
AIRLOOP F9 S2 SUPPLY FAN | 0.206264 |
AIRLOOP T SW SUPPLY FAN | 0.443737 |
AIRLOOP T NW SUPPLY FAN | 0.430023 |
AIRLOOP T SE SUPPLY FAN | 0.382005 |
AIRLOOP T NE SUPPLY FAN | 0.337625 |
AIRLOOP T N1 SUPPLY FAN | 0.256846 |
AIRLOOP T N2 SUPPLY FAN | 0.256548 |
AIRLOOP T S1 SUPPLY FAN | 0.298508 |
AIRLOOP T S2 SUPPLY FAN | 0.299185 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.261865 | 3205.13 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.256992 | 3136.29 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.375203 | 4571.65 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.186744 | 2235.31 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.131508 | 1610.05 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.129530 | 1585.74 | 0.000035 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.138971 | 1790.21 | 0.000039 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.146296 | 1874.97 | 0.000041 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.336816 | 4083.63 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.328085 | 3968.98 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.302169 | 3709.07 | 0.000081 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.248800 | 2955.28 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.174616 | 2120.03 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.172998 | 2100.22 | 0.000046 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.186418 | 2348.56 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.188984 | 2379.83 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.339857 | 4099.50 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.331767 | 3992.78 | 0.000087 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.282576 | 3450.55 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.253655 | 2994.18 | 0.000065 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.179094 | 2162.96 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.177490 | 2143.35 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.191466 | 2398.22 | 0.000052 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.192572 | 2411.72 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.342486 | 4115.74 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.334463 | 4016.31 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.283590 | 3447.95 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.255926 | 3006.86 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.181545 | 2184.05 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.179947 | 2164.55 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.194100 | 2421.46 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.194994 | 2432.36 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.347058 | 4158.53 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.339217 | 4061.50 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.288480 | 3495.15 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.260199 | 3046.55 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.185837 | 2231.85 | 0.000049 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.184252 | 2212.59 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.198495 | 2467.66 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.199357 | 2478.17 | 0.000054 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.344659 | 4118.48 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.336789 | 4021.15 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.286688 | 3463.15 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.257490 | 3003.59 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.183402 | 2196.01 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.181828 | 2176.92 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.196169 | 2433.36 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.197027 | 2443.82 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.344589 | 4108.10 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.336795 | 4011.78 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.287134 | 3459.59 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.257311 | 3006.60 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.183286 | 2189.24 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.181721 | 2170.27 | 0.000047 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.196086 | 2427.05 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.196943 | 2437.49 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.345965 | 4116.29 | 0.000090 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.338234 | 4020.82 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.288856 | 3472.41 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.258470 | 3012.72 | 0.000066 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.184608 | 2200.53 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.183053 | 2181.69 | 0.000048 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.197351 | 2437.62 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.198210 | 2448.08 | 0.000053 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.358570 | 4261.51 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.350643 | 4163.87 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.298457 | 3585.82 | 0.000078 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.263722 | 3068.81 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.195353 | 2326.72 | 0.000051 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.193789 | 2307.77 | 0.000050 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.205446 | 2531.51 | 0.000055 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.206264 | 2541.48 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.443737 | 5311.88 | 0.000116 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.430023 | 5134.82 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.382005 | 4586.60 | 0.000100 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.337625 | 4053.30 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.256846 | 3150.60 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.256548 | 3147.08 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.298508 | 3656.71 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.299185 | 3665.00 | 0.000080 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 2756.67 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 2757.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 3460.54 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 2757.08 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2051.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2051.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2047.88 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2054.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 2735.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 2733.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 2754.50 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 2733.39 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 1854.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 1854.16 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 1859.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 1860.51 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 2759.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 2759.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 2761.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 2759.94 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 1835.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 1835.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 1835.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 1836.18 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 2823.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 2826.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 2824.06 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 2826.48 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 1866.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 1866.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 1864.05 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 1864.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 2864.82 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 2867.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 2864.84 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 2867.93 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 1879.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 1879.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 1877.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 1877.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 2960.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 2965.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 2960.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 2965.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 1951.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 1951.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 1946.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 1946.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 3029.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 3035.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 3029.36 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 3035.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 1998.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 1998.43 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 1992.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 1992.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 3100.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 3106.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 3100.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 3106.95 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2050.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2050.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2044.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2044.75 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 3289.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 3294.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 3289.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 3294.09 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2212.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2212.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2207.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2207.63 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 3902.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 3913.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 3902.78 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 3913.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 2870.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 2870.02 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 2856.07 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 2856.07 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.005337 | 6.00 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.005337 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.005337 | 2576.43 | 8.24 | 6567.57 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.005337 | 1704.37 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:00:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 2.60 |
February | 22.60 | 4.29 |
March | 22.73 | 8.77 |
April | 23.43 | 13.91 |
May | 23.73 | 17.82 |
June | 24.27 | 23.21 |
July | 24.40 | 25.63 |
August | 24.36 | 24.08 |
September | 24.32 | 20.49 |
October | 23.71 | 13.71 |
November | 22.98 | 6.96 |
December | 22.52 | 2.07 |
Annual Sum or Average | 23.46 | 13.68 |
Minimum of Months | 22.46 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 2.60 |
February | 21.89 | 4.29 |
March | 22.11 | 8.77 |
April | 23.10 | 13.91 |
May | 23.69 | 17.82 |
June | 24.29 | 23.21 |
July | 24.40 | 25.63 |
August | 24.35 | 24.08 |
September | 24.28 | 20.49 |
October | 23.13 | 13.71 |
November | 22.03 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.07 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 2.60 |
February | 22.77 | 4.29 |
March | 23.09 | 8.77 |
April | 23.75 | 13.91 |
May | 24.11 | 17.82 |
June | 24.38 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.42 | 20.49 |
October | 23.88 | 13.71 |
November | 23.10 | 6.96 |
December | 22.67 | 2.07 |
Annual Sum or Average | 23.64 | 13.68 |
Minimum of Months | 22.61 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 2.60 |
February | 21.80 | 4.29 |
March | 22.04 | 8.77 |
April | 23.10 | 13.91 |
May | 23.67 | 17.82 |
June | 24.30 | 23.21 |
July | 24.43 | 25.63 |
August | 24.37 | 24.08 |
September | 24.28 | 20.49 |
October | 23.04 | 13.71 |
November | 21.89 | 6.96 |
December | 21.70 | 2.07 |
Annual Sum or Average | 23.03 | 13.68 |
Minimum of Months | 21.70 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 2.60 |
February | 21.76 | 4.29 |
March | 21.88 | 8.77 |
April | 22.75 | 13.91 |
May | 23.46 | 17.82 |
June | 24.26 | 23.21 |
July | 24.41 | 25.63 |
August | 24.34 | 24.08 |
September | 24.23 | 20.49 |
October | 22.87 | 13.71 |
November | 21.84 | 6.96 |
December | 21.70 | 2.07 |
Annual Sum or Average | 22.94 | 13.68 |
Minimum of Months | 21.70 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 2.60 |
February | 21.75 | 4.29 |
March | 21.87 | 8.77 |
April | 22.75 | 13.91 |
May | 23.46 | 17.82 |
June | 24.26 | 23.21 |
July | 24.41 | 25.63 |
August | 24.34 | 24.08 |
September | 24.23 | 20.49 |
October | 22.86 | 13.71 |
November | 21.84 | 6.96 |
December | 21.70 | 2.07 |
Annual Sum or Average | 22.94 | 13.68 |
Minimum of Months | 21.70 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 2.60 |
February | 22.62 | 4.29 |
March | 22.67 | 8.77 |
April | 23.26 | 13.91 |
May | 23.58 | 17.82 |
June | 24.24 | 23.21 |
July | 24.39 | 25.63 |
August | 24.38 | 24.08 |
September | 24.37 | 20.49 |
October | 23.74 | 13.71 |
November | 23.07 | 6.96 |
December | 22.61 | 2.07 |
Annual Sum or Average | 23.46 | 13.68 |
Minimum of Months | 22.51 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 2.60 |
February | 22.65 | 4.29 |
March | 22.73 | 8.77 |
April | 23.32 | 13.91 |
May | 23.63 | 17.82 |
June | 24.25 | 23.21 |
July | 24.39 | 25.63 |
August | 24.38 | 24.08 |
September | 24.37 | 20.49 |
October | 23.76 | 13.71 |
November | 23.11 | 6.96 |
December | 22.64 | 2.07 |
Annual Sum or Average | 23.49 | 13.68 |
Minimum of Months | 22.54 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.41 | 2.60 |
February | 18.03 | 4.29 |
March | 19.52 | 8.77 |
April | 21.45 | 13.91 |
May | 22.86 | 17.82 |
June | 25.52 | 23.21 |
July | 26.33 | 25.63 |
August | 25.83 | 24.08 |
September | 24.66 | 20.49 |
October | 21.61 | 13.71 |
November | 18.97 | 6.96 |
December | 17.24 | 2.07 |
Annual Sum or Average | 21.63 | 13.68 |
Minimum of Months | 17.24 | 2.07 |
Maximum of Months | 26.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 2.60 |
February | 23.11 | 4.29 |
March | 23.43 | 8.77 |
April | 24.09 | 13.91 |
May | 24.17 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.12 | 13.71 |
November | 23.65 | 6.96 |
December | 23.03 | 2.07 |
Annual Sum or Average | 23.84 | 13.68 |
Minimum of Months | 22.96 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.10 | 4.29 |
March | 22.54 | 8.77 |
April | 23.81 | 13.91 |
May | 24.12 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.66 | 13.71 |
November | 22.42 | 6.96 |
December | 21.83 | 2.07 |
Annual Sum or Average | 23.33 | 13.68 |
Minimum of Months | 21.83 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 2.60 |
February | 23.16 | 4.29 |
March | 23.56 | 8.77 |
April | 24.15 | 13.91 |
May | 24.26 | 17.82 |
June | 24.37 | 23.21 |
July | 24.40 | 25.63 |
August | 24.39 | 24.08 |
September | 24.39 | 20.49 |
October | 24.15 | 13.71 |
November | 23.69 | 6.96 |
December | 23.10 | 2.07 |
Annual Sum or Average | 23.89 | 13.68 |
Minimum of Months | 23.01 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 2.60 |
February | 21.98 | 4.29 |
March | 22.46 | 8.77 |
April | 23.80 | 13.91 |
May | 24.13 | 17.82 |
June | 24.39 | 23.21 |
July | 24.43 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.57 | 13.71 |
November | 22.24 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.28 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 2.60 |
February | 21.92 | 4.29 |
March | 22.26 | 8.77 |
April | 23.57 | 13.91 |
May | 24.04 | 17.82 |
June | 24.36 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.48 | 13.71 |
November | 22.20 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.21 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 2.60 |
February | 21.91 | 4.29 |
March | 22.26 | 8.77 |
April | 23.57 | 13.91 |
May | 24.05 | 17.82 |
June | 24.36 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.47 | 13.71 |
November | 22.19 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.21 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 2.60 |
February | 23.31 | 4.29 |
March | 23.56 | 8.77 |
April | 24.06 | 13.91 |
May | 24.12 | 17.82 |
June | 24.33 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.44 | 20.49 |
October | 24.22 | 13.71 |
November | 23.83 | 6.96 |
December | 23.31 | 2.07 |
Annual Sum or Average | 23.93 | 13.68 |
Minimum of Months | 23.20 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 2.60 |
February | 23.32 | 4.29 |
March | 23.58 | 8.77 |
April | 24.07 | 13.91 |
May | 24.14 | 17.82 |
June | 24.33 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.43 | 20.49 |
October | 24.22 | 13.71 |
November | 23.84 | 6.96 |
December | 23.32 | 2.07 |
Annual Sum or Average | 23.94 | 13.68 |
Minimum of Months | 23.22 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 2.60 |
February | 23.00 | 4.29 |
March | 23.66 | 8.77 |
April | 24.97 | 13.91 |
May | 25.47 | 17.82 |
June | 26.36 | 23.21 |
July | 26.63 | 25.63 |
August | 26.54 | 24.08 |
September | 26.20 | 20.49 |
October | 25.04 | 13.71 |
November | 23.66 | 6.96 |
December | 22.73 | 2.07 |
Annual Sum or Average | 24.76 | 13.68 |
Minimum of Months | 22.73 | 2.07 |
Maximum of Months | 26.63 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 2.60 |
February | 23.18 | 4.29 |
March | 23.53 | 8.77 |
April | 24.15 | 13.91 |
May | 24.19 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.16 | 13.71 |
November | 23.73 | 6.96 |
December | 23.12 | 2.07 |
Annual Sum or Average | 23.89 | 13.68 |
Minimum of Months | 23.05 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 2.60 |
February | 22.14 | 4.29 |
March | 22.63 | 8.77 |
April | 23.91 | 13.91 |
May | 24.16 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.75 | 13.71 |
November | 22.53 | 6.96 |
December | 21.85 | 2.07 |
Annual Sum or Average | 23.37 | 13.68 |
Minimum of Months | 21.85 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 2.60 |
February | 23.12 | 4.29 |
March | 23.51 | 8.77 |
April | 24.15 | 13.91 |
May | 24.24 | 17.82 |
June | 24.36 | 23.21 |
July | 24.40 | 25.63 |
August | 24.40 | 24.08 |
September | 24.40 | 20.49 |
October | 24.15 | 13.71 |
November | 23.69 | 6.96 |
December | 23.09 | 2.07 |
Annual Sum or Average | 23.88 | 13.68 |
Minimum of Months | 23.00 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 2.60 |
February | 22.03 | 4.29 |
March | 22.55 | 8.77 |
April | 23.90 | 13.91 |
May | 24.17 | 17.82 |
June | 24.40 | 23.21 |
July | 24.44 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.67 | 13.71 |
November | 22.34 | 6.96 |
December | 21.75 | 2.07 |
Annual Sum or Average | 23.32 | 13.68 |
Minimum of Months | 21.75 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 2.60 |
February | 21.99 | 4.29 |
March | 22.41 | 8.77 |
April | 23.76 | 13.91 |
May | 24.12 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.63 | 13.71 |
November | 22.36 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.28 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 2.60 |
February | 21.98 | 4.29 |
March | 22.41 | 8.77 |
April | 23.76 | 13.91 |
May | 24.12 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.63 | 13.71 |
November | 22.35 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.28 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 2.60 |
February | 23.47 | 4.29 |
March | 23.74 | 8.77 |
April | 24.16 | 13.91 |
May | 24.18 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.44 | 20.49 |
October | 24.28 | 13.71 |
November | 23.96 | 6.96 |
December | 23.48 | 2.07 |
Annual Sum or Average | 24.02 | 13.68 |
Minimum of Months | 23.38 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 2.60 |
February | 23.47 | 4.29 |
March | 23.74 | 8.77 |
April | 24.17 | 13.91 |
May | 24.19 | 17.82 |
June | 24.34 | 23.21 |
July | 24.40 | 25.63 |
August | 24.41 | 24.08 |
September | 24.44 | 20.49 |
October | 24.28 | 13.71 |
November | 23.96 | 6.96 |
December | 23.49 | 2.07 |
Annual Sum or Average | 24.02 | 13.68 |
Minimum of Months | 23.38 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.26 | 2.60 |
February | 23.51 | 4.29 |
March | 24.13 | 8.77 |
April | 25.45 | 13.91 |
May | 25.83 | 17.82 |
June | 26.48 | 23.21 |
July | 26.70 | 25.63 |
August | 26.62 | 24.08 |
September | 26.35 | 20.49 |
October | 25.46 | 13.71 |
November | 24.17 | 6.96 |
December | 23.27 | 2.07 |
Annual Sum or Average | 25.11 | 13.68 |
Minimum of Months | 23.26 | 2.07 |
Maximum of Months | 26.70 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.04 | 2.60 |
February | 23.15 | 4.29 |
March | 23.50 | 8.77 |
April | 24.14 | 13.91 |
May | 24.18 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.16 | 13.71 |
November | 23.72 | 6.96 |
December | 23.11 | 2.07 |
Annual Sum or Average | 23.88 | 13.68 |
Minimum of Months | 23.04 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 2.60 |
February | 22.14 | 4.29 |
March | 22.62 | 8.77 |
April | 23.91 | 13.91 |
May | 24.15 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.76 | 13.71 |
November | 22.55 | 6.96 |
December | 21.85 | 2.07 |
Annual Sum or Average | 23.37 | 13.68 |
Minimum of Months | 21.85 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 2.60 |
February | 23.07 | 4.29 |
March | 23.45 | 8.77 |
April | 24.13 | 13.91 |
May | 24.21 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.40 | 20.49 |
October | 24.14 | 13.71 |
November | 23.66 | 6.96 |
December | 23.07 | 2.07 |
Annual Sum or Average | 23.86 | 13.68 |
Minimum of Months | 22.98 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 2.60 |
February | 22.04 | 4.29 |
March | 22.53 | 8.77 |
April | 23.90 | 13.91 |
May | 24.16 | 17.82 |
June | 24.41 | 23.21 |
July | 24.44 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 23.68 | 13.71 |
November | 22.37 | 6.96 |
December | 21.76 | 2.07 |
Annual Sum or Average | 23.33 | 13.68 |
Minimum of Months | 21.76 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 2.60 |
February | 22.01 | 4.29 |
March | 22.44 | 8.77 |
April | 23.80 | 13.91 |
May | 24.12 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.68 | 13.71 |
November | 22.43 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.30 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 2.60 |
February | 22.00 | 4.29 |
March | 22.43 | 8.77 |
April | 23.80 | 13.91 |
May | 24.12 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.38 | 24.08 |
September | 24.32 | 20.49 |
October | 23.67 | 13.71 |
November | 22.41 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.30 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 2.60 |
February | 23.47 | 4.29 |
March | 23.75 | 8.77 |
April | 24.17 | 13.91 |
May | 24.18 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.44 | 20.49 |
October | 24.29 | 13.71 |
November | 23.97 | 6.96 |
December | 23.50 | 2.07 |
Annual Sum or Average | 24.03 | 13.68 |
Minimum of Months | 23.40 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 2.60 |
February | 23.47 | 4.29 |
March | 23.75 | 8.77 |
April | 24.18 | 13.91 |
May | 24.19 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.44 | 20.49 |
October | 24.29 | 13.71 |
November | 23.97 | 6.96 |
December | 23.50 | 2.07 |
Annual Sum or Average | 24.03 | 13.68 |
Minimum of Months | 23.40 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.42 | 2.60 |
February | 23.65 | 4.29 |
March | 24.27 | 8.77 |
April | 25.60 | 13.91 |
May | 25.95 | 17.82 |
June | 26.57 | 23.21 |
July | 26.78 | 25.63 |
August | 26.70 | 24.08 |
September | 26.43 | 20.49 |
October | 25.60 | 13.71 |
November | 24.33 | 6.96 |
December | 23.43 | 2.07 |
Annual Sum or Average | 25.23 | 13.68 |
Minimum of Months | 23.42 | 2.07 |
Maximum of Months | 26.78 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 2.60 |
February | 23.12 | 4.29 |
March | 23.46 | 8.77 |
April | 24.12 | 13.91 |
May | 24.17 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.15 | 13.71 |
November | 23.70 | 6.96 |
December | 23.09 | 2.07 |
Annual Sum or Average | 23.86 | 13.68 |
Minimum of Months | 23.02 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 2.60 |
February | 22.14 | 4.29 |
March | 22.59 | 8.77 |
April | 23.88 | 13.91 |
May | 24.13 | 17.82 |
June | 24.37 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 23.76 | 13.71 |
November | 22.55 | 6.96 |
December | 21.85 | 2.07 |
Annual Sum or Average | 23.36 | 13.68 |
Minimum of Months | 21.85 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 2.60 |
February | 23.04 | 4.29 |
March | 23.41 | 8.77 |
April | 24.11 | 13.91 |
May | 24.19 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.39 | 20.49 |
October | 24.13 | 13.71 |
November | 23.64 | 6.96 |
December | 23.05 | 2.07 |
Annual Sum or Average | 23.84 | 13.68 |
Minimum of Months | 22.96 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 2.60 |
February | 22.04 | 4.29 |
March | 22.51 | 8.77 |
April | 23.87 | 13.91 |
May | 24.14 | 17.82 |
June | 24.41 | 23.21 |
July | 24.44 | 25.63 |
August | 24.39 | 24.08 |
September | 24.34 | 20.49 |
October | 23.67 | 13.71 |
November | 22.38 | 6.96 |
December | 21.76 | 2.07 |
Annual Sum or Average | 23.32 | 13.68 |
Minimum of Months | 21.76 | 2.07 |
Maximum of Months | 24.44 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 2.60 |
February | 22.02 | 4.29 |
March | 22.44 | 8.77 |
April | 23.79 | 13.91 |
May | 24.11 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.69 | 13.71 |
November | 22.45 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.31 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 2.60 |
February | 22.01 | 4.29 |
March | 22.43 | 8.77 |
April | 23.79 | 13.91 |
May | 24.11 | 17.82 |
June | 24.38 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.32 | 20.49 |
October | 23.68 | 13.71 |
November | 22.44 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.30 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 2.60 |
February | 23.46 | 4.29 |
March | 23.72 | 8.77 |
April | 24.16 | 13.91 |
May | 24.17 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.43 | 20.49 |
October | 24.28 | 13.71 |
November | 23.97 | 6.96 |
December | 23.50 | 2.07 |
Annual Sum or Average | 24.02 | 13.68 |
Minimum of Months | 23.40 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 2.60 |
February | 23.45 | 4.29 |
March | 23.72 | 8.77 |
April | 24.16 | 13.91 |
May | 24.17 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.41 | 24.08 |
September | 24.43 | 20.49 |
October | 24.28 | 13.71 |
November | 23.96 | 6.96 |
December | 23.50 | 2.07 |
Annual Sum or Average | 24.02 | 13.68 |
Minimum of Months | 23.39 | 2.07 |
Maximum of Months | 24.43 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 2.60 |
February | 24.18 | 4.29 |
March | 24.79 | 8.77 |
April | 26.12 | 13.91 |
May | 26.48 | 17.82 |
June | 27.10 | 23.21 |
July | 27.31 | 25.63 |
August | 27.23 | 24.08 |
September | 26.97 | 20.49 |
October | 26.15 | 13.71 |
November | 24.88 | 6.96 |
December | 23.98 | 2.07 |
Annual Sum or Average | 25.77 | 13.68 |
Minimum of Months | 23.96 | 2.07 |
Maximum of Months | 27.31 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.94 | 2.60 |
February | 23.03 | 4.29 |
March | 23.34 | 8.77 |
April | 24.06 | 13.91 |
May | 24.12 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.36 | 20.49 |
October | 24.12 | 13.71 |
November | 23.63 | 6.96 |
December | 23.02 | 2.07 |
Annual Sum or Average | 23.82 | 13.68 |
Minimum of Months | 22.94 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 2.60 |
February | 22.09 | 4.29 |
March | 22.47 | 8.77 |
April | 23.78 | 13.91 |
May | 24.08 | 17.82 |
June | 24.36 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.69 | 13.71 |
November | 22.47 | 6.96 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.32 | 13.68 |
Minimum of Months | 21.82 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 2.60 |
February | 22.96 | 4.29 |
March | 23.30 | 8.77 |
April | 24.05 | 13.91 |
May | 24.14 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.38 | 20.49 |
October | 24.10 | 13.71 |
November | 23.57 | 6.96 |
December | 22.98 | 2.07 |
Annual Sum or Average | 23.80 | 13.68 |
Minimum of Months | 22.89 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 2.60 |
February | 21.99 | 4.29 |
March | 22.40 | 8.77 |
April | 23.78 | 13.91 |
May | 24.09 | 17.82 |
June | 24.40 | 23.21 |
July | 24.45 | 25.63 |
August | 24.38 | 24.08 |
September | 24.33 | 20.49 |
October | 23.60 | 13.71 |
November | 22.29 | 6.96 |
December | 21.75 | 2.07 |
Annual Sum or Average | 23.28 | 13.68 |
Minimum of Months | 21.75 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 2.60 |
February | 21.97 | 4.29 |
March | 22.32 | 8.77 |
April | 23.68 | 13.91 |
May | 24.06 | 17.82 |
June | 24.36 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.30 | 20.49 |
October | 23.61 | 13.71 |
November | 22.36 | 6.96 |
December | 21.76 | 2.07 |
Annual Sum or Average | 23.26 | 13.68 |
Minimum of Months | 21.76 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 2.60 |
February | 21.97 | 4.29 |
March | 22.31 | 8.77 |
April | 23.68 | 13.91 |
May | 24.06 | 17.82 |
June | 24.37 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.30 | 20.49 |
October | 23.60 | 13.71 |
November | 22.34 | 6.96 |
December | 21.76 | 2.07 |
Annual Sum or Average | 23.26 | 13.68 |
Minimum of Months | 21.76 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 2.60 |
February | 23.36 | 4.29 |
March | 23.61 | 8.77 |
April | 24.10 | 13.91 |
May | 24.12 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.42 | 20.49 |
October | 24.25 | 13.71 |
November | 23.90 | 6.96 |
December | 23.43 | 2.07 |
Annual Sum or Average | 23.97 | 13.68 |
Minimum of Months | 23.32 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 2.60 |
February | 23.36 | 4.29 |
March | 23.61 | 8.77 |
April | 24.10 | 13.91 |
May | 24.13 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.42 | 20.49 |
October | 24.25 | 13.71 |
November | 23.90 | 6.96 |
December | 23.42 | 2.07 |
Annual Sum or Average | 23.97 | 13.68 |
Minimum of Months | 23.31 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 2.60 |
February | 23.55 | 4.29 |
March | 24.12 | 8.77 |
April | 25.49 | 13.91 |
May | 25.88 | 17.82 |
June | 26.55 | 23.21 |
July | 26.77 | 25.63 |
August | 26.69 | 24.08 |
September | 26.40 | 20.49 |
October | 25.54 | 13.71 |
November | 24.25 | 6.96 |
December | 23.36 | 2.07 |
Annual Sum or Average | 25.17 | 13.68 |
Minimum of Months | 23.34 | 2.07 |
Maximum of Months | 26.77 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 2.60 |
February | 22.96 | 4.29 |
March | 23.25 | 8.77 |
April | 24.00 | 13.91 |
May | 24.09 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.35 | 20.49 |
October | 24.09 | 13.71 |
November | 23.58 | 6.96 |
December | 22.97 | 2.07 |
Annual Sum or Average | 23.78 | 13.68 |
Minimum of Months | 22.89 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 2.60 |
February | 22.06 | 4.29 |
March | 22.39 | 8.77 |
April | 23.70 | 13.91 |
May | 24.05 | 17.82 |
June | 24.35 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.32 | 20.49 |
October | 23.63 | 13.71 |
November | 22.41 | 6.96 |
December | 21.81 | 2.07 |
Annual Sum or Average | 23.29 | 13.68 |
Minimum of Months | 21.81 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 2.60 |
February | 22.90 | 4.29 |
March | 23.21 | 8.77 |
April | 24.00 | 13.91 |
May | 24.11 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.07 | 13.71 |
November | 23.52 | 6.96 |
December | 22.93 | 2.07 |
Annual Sum or Average | 23.76 | 13.68 |
Minimum of Months | 22.83 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 2.60 |
February | 21.97 | 4.29 |
March | 22.33 | 8.77 |
April | 23.70 | 13.91 |
May | 24.05 | 17.82 |
June | 24.39 | 23.21 |
July | 24.45 | 25.63 |
August | 24.38 | 24.08 |
September | 24.32 | 20.49 |
October | 23.55 | 13.71 |
November | 22.23 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.25 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 2.60 |
February | 21.95 | 4.29 |
March | 22.24 | 8.77 |
April | 23.59 | 13.91 |
May | 24.02 | 17.82 |
June | 24.35 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.29 | 20.49 |
October | 23.55 | 13.71 |
November | 22.29 | 6.96 |
December | 21.76 | 2.07 |
Annual Sum or Average | 23.22 | 13.68 |
Minimum of Months | 21.76 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 2.60 |
February | 21.94 | 4.29 |
March | 22.23 | 8.77 |
April | 23.59 | 13.91 |
May | 24.02 | 17.82 |
June | 24.36 | 23.21 |
July | 24.42 | 25.63 |
August | 24.37 | 24.08 |
September | 24.29 | 20.49 |
October | 23.54 | 13.71 |
November | 22.28 | 6.96 |
December | 21.75 | 2.07 |
Annual Sum or Average | 23.22 | 13.68 |
Minimum of Months | 21.75 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 2.60 |
February | 23.29 | 4.29 |
March | 23.51 | 8.77 |
April | 24.04 | 13.91 |
May | 24.09 | 17.82 |
June | 24.32 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.41 | 20.49 |
October | 24.23 | 13.71 |
November | 23.85 | 6.96 |
December | 23.36 | 2.07 |
Annual Sum or Average | 23.93 | 13.68 |
Minimum of Months | 23.25 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 2.60 |
February | 23.28 | 4.29 |
March | 23.51 | 8.77 |
April | 24.05 | 13.91 |
May | 24.09 | 17.82 |
June | 24.32 | 23.21 |
July | 24.41 | 25.63 |
August | 24.40 | 24.08 |
September | 24.41 | 20.49 |
October | 24.23 | 13.71 |
November | 23.85 | 6.96 |
December | 23.36 | 2.07 |
Annual Sum or Average | 23.93 | 13.68 |
Minimum of Months | 23.25 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 2.60 |
February | 23.39 | 4.29 |
March | 23.94 | 8.77 |
April | 25.32 | 13.91 |
May | 25.76 | 17.82 |
June | 26.46 | 23.21 |
July | 26.70 | 25.63 |
August | 26.61 | 24.08 |
September | 26.31 | 20.49 |
October | 25.41 | 13.71 |
November | 24.09 | 6.96 |
December | 23.22 | 2.07 |
Annual Sum or Average | 25.04 | 13.68 |
Minimum of Months | 23.19 | 2.07 |
Maximum of Months | 26.70 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.83 | 2.60 |
February | 22.91 | 4.29 |
March | 23.17 | 8.77 |
April | 23.95 | 13.91 |
May | 24.06 | 17.82 |
June | 24.32 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.35 | 20.49 |
October | 24.07 | 13.71 |
November | 23.53 | 6.96 |
December | 22.92 | 2.07 |
Annual Sum or Average | 23.75 | 13.68 |
Minimum of Months | 22.83 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | 2.60 |
February | 22.03 | 4.29 |
March | 22.34 | 8.77 |
April | 23.64 | 13.91 |
May | 24.02 | 17.82 |
June | 24.34 | 23.21 |
July | 24.41 | 25.63 |
August | 24.37 | 24.08 |
September | 24.31 | 20.49 |
October | 23.58 | 13.71 |
November | 22.35 | 6.96 |
December | 21.80 | 2.07 |
Annual Sum or Average | 23.26 | 13.68 |
Minimum of Months | 21.80 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 2.60 |
February | 22.85 | 4.29 |
March | 23.14 | 8.77 |
April | 23.95 | 13.91 |
May | 24.08 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.37 | 20.49 |
October | 24.04 | 13.71 |
November | 23.47 | 6.96 |
December | 22.88 | 2.07 |
Annual Sum or Average | 23.73 | 13.68 |
Minimum of Months | 22.78 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 2.60 |
February | 21.94 | 4.29 |
March | 22.27 | 8.77 |
April | 23.63 | 13.91 |
May | 24.02 | 17.82 |
June | 24.39 | 23.21 |
July | 24.45 | 25.63 |
August | 24.38 | 24.08 |
September | 24.31 | 20.49 |
October | 23.50 | 13.71 |
November | 22.18 | 6.96 |
December | 21.73 | 2.07 |
Annual Sum or Average | 23.22 | 13.68 |
Minimum of Months | 21.73 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 2.60 |
February | 21.92 | 4.29 |
March | 22.18 | 8.77 |
April | 23.51 | 13.91 |
May | 23.99 | 17.82 |
June | 24.35 | 23.21 |
July | 24.42 | 25.63 |
August | 24.36 | 24.08 |
September | 24.28 | 20.49 |
October | 23.50 | 13.71 |
November | 22.24 | 6.96 |
December | 21.75 | 2.07 |
Annual Sum or Average | 23.20 | 13.68 |
Minimum of Months | 21.75 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 2.60 |
February | 21.92 | 4.29 |
March | 22.18 | 8.77 |
April | 23.51 | 13.91 |
May | 23.99 | 17.82 |
June | 24.35 | 23.21 |
July | 24.42 | 25.63 |
August | 24.36 | 24.08 |
September | 24.28 | 20.49 |
October | 23.49 | 13.71 |
November | 22.22 | 6.96 |
December | 21.75 | 2.07 |
Annual Sum or Average | 23.19 | 13.68 |
Minimum of Months | 21.75 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 2.60 |
February | 23.21 | 4.29 |
March | 23.42 | 8.77 |
April | 23.99 | 13.91 |
May | 24.06 | 17.82 |
June | 24.31 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.40 | 20.49 |
October | 24.20 | 13.71 |
November | 23.80 | 6.96 |
December | 23.29 | 2.07 |
Annual Sum or Average | 23.89 | 13.68 |
Minimum of Months | 23.19 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 2.60 |
February | 23.21 | 4.29 |
March | 23.42 | 8.77 |
April | 23.99 | 13.91 |
May | 24.06 | 17.82 |
June | 24.31 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.40 | 20.49 |
October | 24.20 | 13.71 |
November | 23.80 | 6.96 |
December | 23.29 | 2.07 |
Annual Sum or Average | 23.89 | 13.68 |
Minimum of Months | 23.18 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 2.60 |
February | 23.29 | 4.29 |
March | 23.83 | 8.77 |
April | 25.23 | 13.91 |
May | 25.71 | 17.82 |
June | 26.45 | 23.21 |
July | 26.70 | 25.63 |
August | 26.61 | 24.08 |
September | 26.29 | 20.49 |
October | 25.34 | 13.71 |
November | 23.99 | 6.96 |
December | 23.12 | 2.07 |
Annual Sum or Average | 24.98 | 13.68 |
Minimum of Months | 23.09 | 2.07 |
Maximum of Months | 26.70 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 2.60 |
February | 22.83 | 4.29 |
March | 23.08 | 8.77 |
April | 23.87 | 13.91 |
May | 24.04 | 17.82 |
June | 24.31 | 23.21 |
July | 24.41 | 25.63 |
August | 24.38 | 24.08 |
September | 24.34 | 20.49 |
October | 24.02 | 13.71 |
November | 23.43 | 6.96 |
December | 22.83 | 2.07 |
Annual Sum or Average | 23.69 | 13.68 |
Minimum of Months | 22.75 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 2.60 |
February | 22.02 | 4.29 |
March | 22.30 | 8.77 |
April | 23.57 | 13.91 |
May | 23.99 | 17.82 |
June | 24.33 | 23.21 |
July | 24.41 | 25.63 |
August | 24.37 | 24.08 |
September | 24.30 | 20.49 |
October | 23.53 | 13.71 |
November | 22.31 | 6.96 |
December | 21.79 | 2.07 |
Annual Sum or Average | 23.24 | 13.68 |
Minimum of Months | 21.79 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 2.60 |
February | 22.78 | 4.29 |
March | 23.05 | 8.77 |
April | 23.89 | 13.91 |
May | 24.05 | 17.82 |
June | 24.32 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.35 | 20.49 |
October | 24.00 | 13.71 |
November | 23.38 | 6.96 |
December | 22.80 | 2.07 |
Annual Sum or Average | 23.68 | 13.68 |
Minimum of Months | 22.71 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 2.60 |
February | 21.93 | 4.29 |
March | 22.24 | 8.77 |
April | 23.56 | 13.91 |
May | 23.99 | 17.82 |
June | 24.38 | 23.21 |
July | 24.45 | 25.63 |
August | 24.38 | 24.08 |
September | 24.30 | 20.49 |
October | 23.45 | 13.71 |
November | 22.13 | 6.96 |
December | 21.73 | 2.07 |
Annual Sum or Average | 23.20 | 13.68 |
Minimum of Months | 21.73 | 2.07 |
Maximum of Months | 24.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 2.60 |
February | 21.91 | 4.29 |
March | 22.15 | 8.77 |
April | 23.45 | 13.91 |
May | 23.96 | 17.82 |
June | 24.33 | 23.21 |
July | 24.42 | 25.63 |
August | 24.36 | 24.08 |
September | 24.27 | 20.49 |
October | 23.44 | 13.71 |
November | 22.19 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.17 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 2.60 |
February | 21.91 | 4.29 |
March | 22.15 | 8.77 |
April | 23.45 | 13.91 |
May | 23.96 | 17.82 |
June | 24.34 | 23.21 |
July | 24.42 | 25.63 |
August | 24.36 | 24.08 |
September | 24.27 | 20.49 |
October | 23.44 | 13.71 |
November | 22.17 | 6.96 |
December | 21.74 | 2.07 |
Annual Sum or Average | 23.17 | 13.68 |
Minimum of Months | 21.74 | 2.07 |
Maximum of Months | 24.42 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 2.60 |
February | 23.10 | 4.29 |
March | 23.29 | 8.77 |
April | 23.91 | 13.91 |
May | 24.03 | 17.82 |
June | 24.30 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.15 | 13.71 |
November | 23.69 | 6.96 |
December | 23.16 | 2.07 |
Annual Sum or Average | 23.82 | 13.68 |
Minimum of Months | 23.05 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 2.60 |
February | 23.09 | 4.29 |
March | 23.29 | 8.77 |
April | 23.91 | 13.91 |
May | 24.03 | 17.82 |
June | 24.30 | 23.21 |
July | 24.41 | 25.63 |
August | 24.39 | 24.08 |
September | 24.38 | 20.49 |
October | 24.15 | 13.71 |
November | 23.69 | 6.96 |
December | 23.15 | 2.07 |
Annual Sum or Average | 23.82 | 13.68 |
Minimum of Months | 23.05 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 2.60 |
February | 23.13 | 4.29 |
March | 23.70 | 8.77 |
April | 25.15 | 13.91 |
May | 25.70 | 17.82 |
June | 26.52 | 23.21 |
July | 26.81 | 25.63 |
August | 26.70 | 24.08 |
September | 26.32 | 20.49 |
October | 25.25 | 13.71 |
November | 23.81 | 6.96 |
December | 22.91 | 2.07 |
Annual Sum or Average | 24.92 | 13.68 |
Minimum of Months | 22.90 | 2.07 |
Maximum of Months | 26.81 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 2.60 |
February | 22.68 | 4.29 |
March | 22.83 | 8.77 |
April | 23.60 | 13.91 |
May | 23.91 | 17.82 |
June | 24.25 | 23.21 |
July | 24.40 | 25.63 |
August | 24.35 | 24.08 |
September | 24.27 | 20.49 |
October | 23.72 | 13.71 |
November | 23.03 | 6.96 |
December | 22.62 | 2.07 |
Annual Sum or Average | 23.52 | 13.68 |
Minimum of Months | 22.55 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 2.60 |
February | 22.15 | 4.29 |
March | 22.41 | 8.77 |
April | 23.40 | 13.91 |
May | 23.87 | 17.82 |
June | 24.27 | 23.21 |
July | 24.41 | 25.63 |
August | 24.35 | 24.08 |
September | 24.23 | 20.49 |
October | 23.37 | 13.71 |
November | 22.36 | 6.96 |
December | 21.89 | 2.07 |
Annual Sum or Average | 23.23 | 13.68 |
Minimum of Months | 21.89 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 2.60 |
February | 22.67 | 4.29 |
March | 22.83 | 8.77 |
April | 23.61 | 13.91 |
May | 23.91 | 17.82 |
June | 24.25 | 23.21 |
July | 24.39 | 25.63 |
August | 24.37 | 24.08 |
September | 24.28 | 20.49 |
October | 23.69 | 13.71 |
November | 23.00 | 6.96 |
December | 22.61 | 2.07 |
Annual Sum or Average | 23.52 | 13.68 |
Minimum of Months | 22.54 | 2.07 |
Maximum of Months | 24.39 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.08 | 4.29 |
March | 22.38 | 8.77 |
April | 23.41 | 13.91 |
May | 23.83 | 17.82 |
June | 24.27 | 23.21 |
July | 24.41 | 25.63 |
August | 24.36 | 24.08 |
September | 24.21 | 20.49 |
October | 23.33 | 13.71 |
November | 22.24 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.18 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.41 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 2.60 |
February | 22.05 | 4.29 |
March | 22.28 | 8.77 |
April | 23.33 | 13.91 |
May | 23.84 | 17.82 |
June | 24.27 | 23.21 |
July | 24.40 | 25.63 |
August | 24.34 | 24.08 |
September | 24.21 | 20.49 |
October | 23.31 | 13.71 |
November | 22.24 | 6.96 |
December | 21.78 | 2.07 |
Annual Sum or Average | 23.16 | 13.68 |
Minimum of Months | 21.78 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 2.60 |
February | 22.05 | 4.29 |
March | 22.28 | 8.77 |
April | 23.33 | 13.91 |
May | 23.84 | 17.82 |
June | 24.27 | 23.21 |
July | 24.40 | 25.63 |
August | 24.34 | 24.08 |
September | 24.21 | 20.49 |
October | 23.31 | 13.71 |
November | 22.24 | 6.96 |
December | 21.77 | 2.07 |
Annual Sum or Average | 23.16 | 13.68 |
Minimum of Months | 21.77 | 2.07 |
Maximum of Months | 24.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 2.60 |
February | 22.82 | 4.29 |
March | 22.96 | 8.77 |
April | 23.66 | 13.91 |
May | 23.93 | 17.82 |
June | 24.24 | 23.21 |
July | 24.38 | 25.63 |
August | 24.35 | 24.08 |
September | 24.31 | 20.49 |
October | 23.85 | 13.71 |
November | 23.20 | 6.96 |
December | 22.77 | 2.07 |
Annual Sum or Average | 23.60 | 13.68 |
Minimum of Months | 22.70 | 2.07 |
Maximum of Months | 24.38 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 2.60 |
February | 22.82 | 4.29 |
March | 22.96 | 8.77 |
April | 23.66 | 13.91 |
May | 23.93 | 17.82 |
June | 24.25 | 23.21 |
July | 24.38 | 25.63 |
August | 24.36 | 24.08 |
September | 24.31 | 20.49 |
October | 23.85 | 13.71 |
November | 23.20 | 6.96 |
December | 22.77 | 2.07 |
Annual Sum or Average | 23.60 | 13.68 |
Minimum of Months | 22.69 | 2.07 |
Maximum of Months | 24.38 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:00:30
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 2.60 |
February | 23.21 | 4.29 |
March | 23.94 | 8.77 |
April | 25.56 | 13.91 |
May | 26.29 | 17.82 |
June | 27.33 | 23.21 |
July | 27.76 | 25.63 |
August | 27.59 | 24.08 |
September | 26.98 | 20.49 |
October | 25.54 | 13.71 |
November | 23.83 | 6.96 |
December | 22.77 | 2.07 |
Annual Sum or Average | 25.31 | 13.68 |
Minimum of Months | 22.77 | 2.07 |
Maximum of Months | 27.76 | 25.63 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.237569E+12 | 141821.218 | 16-JAN-17:00 | 11327.174 | 57042.023 | 23476.580 | 35882.331 | 0.000 | 10364.000 | 1741.299 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.210318E+12 | 126551.001 | 15-FEB-17:45 | 11327.174 | 57142.088 | 23476.580 | 0.000 | 19853.839 | 10364.000 | 1741.299 | 650.862 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.219586E+12 | 122049.323 | 11-MAR-18:15 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 13918.618 | 10364.000 | 1741.299 | 398.534 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.224486E+12 | 155126.831 | 13-APR-17:15 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 56129.872 | 0.000 | 1741.299 | 1628.788 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.250642E+12 | 159356.636 | 09-MAY-17:15 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 60346.359 | 0.000 | 1741.299 | 1642.106 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.279746E+12 | 162404.745 | 18-JUN-19:00 | 14401.373 | 49889.926 | 23476.580 | 0.000 | 59274.547 | 10364.000 | 1741.299 | 1615.716 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.313895E+12 | 163762.871 | 21-JUL-19:15 | 14401.373 | 49889.926 | 23476.580 | 0.000 | 60361.600 | 10364.000 | 1741.299 | 1886.788 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.303997E+12 | 161913.724 | 21-AUG-17:15 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 62484.880 | 0.000 | 1741.299 | 2060.673 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.267477E+12 | 159492.369 | 28-SEP-17:00 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 50063.135 | 10364.000 | 1741.299 | 1696.866 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.245183E+12 | 159343.706 | 05-OCT-17:45 | 13120.457 | 57042.023 | 23476.580 | 0.000 | 50032.869 | 10364.000 | 1741.299 | 1578.469 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.222869E+12 | 126032.733 | 07-NOV-17:15 | 11327.174 | 57142.088 | 23476.580 | 0.000 | 19301.048 | 10364.000 | 1741.299 | 685.348 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.236120E+12 | 126198.360 | 03-DEC-18:00 | 13120.457 | 57042.023 | 23476.580 | 18465.992 | 0.000 | 10364.000 | 1741.299 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.301189E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.210318E+12 | 122049.323 | 11327.174 | 49889.926 | 23476.580 | 0.000 | 0.000 | 0.000 | 1741.299 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.313895E+12 | 163762.871 | 14401.373 | 57142.088 | 23476.580 | 35882.331 | 62484.880 | 10364.000 | 1741.299 | 2060.673 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:00:30
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.168927E+12 | 229458.428 | 17-JAN-08:15 | 0.000 | 0.000 | 0.000 | 229458.428 | 79368.043 | 79368.043 | 150090.385 |
February | 0.142162E+12 | 199460.408 | 06-FEB-06:00 | 0.000 | 0.000 | 0.000 | 199460.408 | 78138.779 | 78138.779 | 121321.629 |
March | 0.114991E+12 | 160357.152 | 04-MAR-06:30 | 0.000 | 0.000 | 0.000 | 160357.152 | 75481.846 | 75481.846 | 84875.306 |
April | 0.951555E+11 | 95262.237 | 08-APR-05:30 | 0.000 | 0.000 | 0.000 | 95262.237 | 73096.585 | 73096.585 | 22165.652 |
May | 0.911279E+11 | 76444.364 | 01-MAY-06:00 | 0.000 | 0.000 | 0.000 | 76444.364 | 76444.364 | 76444.364 | 0.000 |
June | 0.820353E+11 | 74092.424 | 02-JUN-06:00 | 0.000 | 0.000 | 0.000 | 74092.424 | 74092.424 | 74092.424 | 0.000 |
July | 0.805276E+11 | 72436.343 | 01-JUL-06:45 | 0.000 | 0.000 | 0.000 | 72436.343 | 72436.343 | 72436.343 | 0.000 |
August | 0.795816E+11 | 71863.904 | 30-AUG-06:00 | 0.000 | 0.000 | 0.000 | 71863.904 | 71863.904 | 71863.904 | 0.000 |
September | 0.794624E+11 | 72992.365 | 28-SEP-06:45 | 0.000 | 0.000 | 0.000 | 72992.365 | 72992.365 | 72992.365 | 0.000 |
October | 0.907933E+11 | 122962.462 | 26-OCT-05:00 | 0.000 | 0.000 | 0.000 | 122962.462 | 73069.371 | 73069.371 | 49893.091 |
November | 0.103940E+12 | 177592.286 | 26-NOV-06:30 | 0.000 | 0.000 | 0.000 | 177592.286 | 73201.719 | 73201.719 | 104390.568 |
December | 0.156451E+12 | 190982.383 | 22-DEC-06:00 | 0.000 | 0.000 | 0.000 | 190982.383 | 76764.909 | 76764.909 | 114217.475 |
Annual Sum or Average | 0.128516E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.794624E+11 | 71863.904 | 0.000 | 0.000 | 0.000 | 71863.904 | 71863.904 | 71863.904 | 0.000 | |
Maximum of Months | 0.168927E+12 | 229458.428 | 0.000 | 0.000 | 0.000 | 229458.428 | 79368.043 | 79368.043 | 150090.385 |