Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10
Tabular Output Report in Format: HTML
Building: High-Rise Apartment
Environment: Memphis International Ap TN USA TMY3 WMO#=723340
Simulation Timestamp: 2015-09-09 19:11:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4622.39 | 589.85 | 654.74 |
Net Site Energy | 4622.39 | 589.85 | 654.74 |
Total Source Energy | 11563.59 | 1475.61 | 1637.93 |
Net Source Energy | 11563.59 | 1475.61 | 1637.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 7836.48 |
Net Conditioned Building Area | 7059.89 |
Unconditioned Building Area | 776.58 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 135.05 | 473.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 674.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 296.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 599.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 71.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.94 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1002.57 | 0.00 | 0.00 | 0.00 | 4778.51 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3145.91 | 1476.48 | 0.00 | 0.00 | 0.00 | 6648.45 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 473.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 135.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 674.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 242.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 54.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 162.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 1137.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 599.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 71.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 32.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1869.94 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1002.57 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.51 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 65.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.29 | 209.14 | 0.00 | 0.00 | 0.00 | 0.94 |
Other | 161.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 445.60 | 209.14 | 0.00 | 0.00 | 0.00 | 0.94 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 58.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 193.06 | 188.41 | 0.00 | 0.00 | 0.00 | 0.85 |
Other | 145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 401.44 | 188.41 | 0.00 | 0.00 | 0.00 | 0.85 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3145.91 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3145.91 | 100.00 |
Total On-Site and Utility Electric Sources | 3145.91 | 100.00 |
Total Electricity End Uses | 3145.91 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6648.45 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6648.45 | 100.00 |
Total Water End Uses | 6648.45 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.50 |
Time Setpoint Not Met During Occupied Cooling | 101.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2332.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | G CORRIDOR | F2 SW APARTMENT | F2 NW APARTMENT | F2 SE APARTMENT | F2 NE APARTMENT | F2 N1 APARTMENT | F2 N2 APARTMENT | F2 S1 APARTMENT | F2 S2 APARTMENT | F2 CORRIDOR | F3 SW APARTMENT | F3 NW APARTMENT | F3 SE APARTMENT | F3 NE APARTMENT | F3 N1 APARTMENT | F3 N2 APARTMENT | F3 S1 APARTMENT | F3 S2 APARTMENT | F3 CORRIDOR | F4 SW APARTMENT | F4 NW APARTMENT | F4 SE APARTMENT | F4 NE APARTMENT | F4 N1 APARTMENT | F4 N2 APARTMENT | F4 S1 APARTMENT | F4 S2 APARTMENT | F4 CORRIDOR | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | M CORRIDOR | F6 SW APARTMENT | F6 NW APARTMENT | F6 SE APARTMENT | F6 NE APARTMENT | F6 N1 APARTMENT | F6 N2 APARTMENT | F6 S1 APARTMENT | F6 S2 APARTMENT | F6 CORRIDOR | F7 SW APARTMENT | F7 NW APARTMENT | F7 SE APARTMENT | F7 NE APARTMENT | F7 N1 APARTMENT | F7 N2 APARTMENT | F7 S1 APARTMENT | F7 S2 APARTMENT | F7 CORRIDOR | F8 SW APARTMENT | F8 NW APARTMENT | F8 SE APARTMENT | F8 NE APARTMENT | F8 N1 APARTMENT | F8 N2 APARTMENT | F8 S1 APARTMENT | F8 S2 APARTMENT | F8 CORRIDOR | F9 SW APARTMENT | F9 NW APARTMENT | F9 SE APARTMENT | F9 NE APARTMENT | F9 N1 APARTMENT | F9 N2 APARTMENT | F9 S1 APARTMENT | F9 S2 APARTMENT | F9 CORRIDOR | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |COMPONENTS OF PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 19:10 |
RunPeriod | Memphis International Ap TN USA TMY3 WMO#=723340 |
Weather File | Memphis International Ap TN USA TMY3 WMO#=723340 |
Latitude [deg] | 35.07 |
Longitude [deg] | -90.0 |
Elevation [m] | 81.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3855.02 | 1411.96 | 515.55 | 1411.96 | 515.55 |
Window Opening Area [m2] | 1150.39 | 423.59 | 152.73 | 423.59 | 150.48 |
Window-Wall Ratio [%] | 29.84 | 30.00 | 29.62 | 30.00 | 29.19 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 3752.84 | 1411.96 | 464.46 | 1411.96 | 464.46 |
Window Opening Area [m2] | 1125.85 | 423.59 | 139.34 | 423.59 | 139.34 |
Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 29.5362 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 4.47 | 6.7128 | 0.0000 | |
F2 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F2 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F2 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F3 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F3 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F3 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F4 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F4 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F4 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
M SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 13.4255 | 0.0000 | |
F6 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F6 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F6 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F7 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F7 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F7 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F8 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F8 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F8 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
F9 SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
F9 N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
F9 CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 0.0000 | |
T SW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 58.52 | 17.56 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.96 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 10.59 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 2.23 | 6.7128 | 264.3872 | |
Total | 7836.48 | 23884.04 | 3855.02 | 1150.39 | 4.3335 | 39.48 | 8.6291 | |||
Conditioned Total | 7059.89 | 21517.16 | 3752.84 | 1125.85 | 3.9979 | 35.57 | 6.6700 | |||
Unconditioned Total | 776.58 | 2366.87 | 102.18 | 24.54 | 7.3840 | 26.4387 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-18:30 | 31-JAN-06:00 | - | - | - | 29-AUG-17:15 |
Heating | 0.00 | 294826.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78343.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19000.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2349.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3357.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 75821.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 181326.71 | 370648.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 294826.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 78343.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 11484.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 2917.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19000.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2349.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 3357.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 75821.85 | 0.00 | 0.00 | 0.00 | 0.00 |
sub cat | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 427.69 | 513.72 | 0.00 | 0.00 | 0.00 |
Cooling | 2137.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 939.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 516.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3601.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1897.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 225.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 103.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1086.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9963.08 | 1600.50 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.58 | 72.77 | 0.00 | 0.00 | 0.00 |
Cooling | 302.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 268.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 153.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1411.22 | 226.70 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 60.58 | 72.77 | 0.00 | 0.00 | 0.00 |
Cooling | 302.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 510.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 268.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 14.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 153.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1411.22 | 226.70 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -8.30 | 0.00 | -8.30 | Wetbulb [C] | 4.10 | 0.00 |
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 35.60 | 9.20 | 25.20 | Wetbulb [C] | 3.80 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 270.00 | 180.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 270.00 | 180.00 | |
F2 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F2 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F2 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F2 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F2 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F2 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F3 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F3 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F3 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F3 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F3 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F3 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F4 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F4 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F4 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F4 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F4 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F4 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F6 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F6 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F6 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F6 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F6 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F6 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F7 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F7 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F7 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F7 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F7 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F7 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F8 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F8 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F8 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F8 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F8 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F8 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
F9 WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
F9 EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
F9 NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
F9 SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
F9 WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
F9 EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 0.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
GWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | G WWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.65_SHGC_0.25 | 3.36 | 0.00 | 0.00 | 3.36 | 3.36 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 90.00 | 90.00 | E | ||
F2WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL SWA | 270.00 | 90.00 | W | ||
F2WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SWA | 180.00 | 90.00 | S | ||
F2WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NWA | 0.00 | 90.00 | N | ||
F2WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 WWALL NWA | 270.00 | 90.00 | W | ||
F2WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL SEA | 90.00 | 90.00 | E | ||
F2WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL SEA | 180.00 | 90.00 | S | ||
F2WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL NEA | 0.00 | 90.00 | N | ||
F2WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F2 EWALL NEA | 90.00 | 90.00 | E | ||
F2WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N1A | 0.00 | 90.00 | N | ||
F2WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 NWALL N2A | 0.00 | 90.00 | N | ||
F2WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S1A | 180.00 | 90.00 | S | ||
F2WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F2 SWALL S2A | 180.00 | 90.00 | S | ||
F2WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 WWALL C | 270.00 | 90.00 | W | ||
F2WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F2 EWALL C | 90.00 | 90.00 | E | ||
F3WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL SWA | 270.00 | 90.00 | W | ||
F3WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SWA | 180.00 | 90.00 | S | ||
F3WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NWA | 0.00 | 90.00 | N | ||
F3WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 WWALL NWA | 270.00 | 90.00 | W | ||
F3WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL SEA | 90.00 | 90.00 | E | ||
F3WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL SEA | 180.00 | 90.00 | S | ||
F3WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL NEA | 0.00 | 90.00 | N | ||
F3WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F3 EWALL NEA | 90.00 | 90.00 | E | ||
F3WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N1A | 0.00 | 90.00 | N | ||
F3WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 NWALL N2A | 0.00 | 90.00 | N | ||
F3WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S1A | 180.00 | 90.00 | S | ||
F3WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F3 SWALL S2A | 180.00 | 90.00 | S | ||
F3WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 WWALL C | 270.00 | 90.00 | W | ||
F3WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F3 EWALL C | 90.00 | 90.00 | E | ||
F4WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL SWA | 270.00 | 90.00 | W | ||
F4WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SWA | 180.00 | 90.00 | S | ||
F4WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NWA | 0.00 | 90.00 | N | ||
F4WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 WWALL NWA | 270.00 | 90.00 | W | ||
F4WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL SEA | 90.00 | 90.00 | E | ||
F4WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL SEA | 180.00 | 90.00 | S | ||
F4WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL NEA | 0.00 | 90.00 | N | ||
F4WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F4 EWALL NEA | 90.00 | 90.00 | E | ||
F4WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N1A | 0.00 | 90.00 | N | ||
F4WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 NWALL N2A | 0.00 | 90.00 | N | ||
F4WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S1A | 180.00 | 90.00 | S | ||
F4WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F4 SWALL S2A | 180.00 | 90.00 | S | ||
F4WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 WWALL C | 270.00 | 90.00 | W | ||
F4WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F4 EWALL C | 90.00 | 90.00 | E | ||
MWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M WWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 90.00 | 90.00 | E | ||
F6WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL SWA | 270.00 | 90.00 | W | ||
F6WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SWA | 180.00 | 90.00 | S | ||
F6WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NWA | 0.00 | 90.00 | N | ||
F6WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 WWALL NWA | 270.00 | 90.00 | W | ||
F6WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL SEA | 90.00 | 90.00 | E | ||
F6WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL SEA | 180.00 | 90.00 | S | ||
F6WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL NEA | 0.00 | 90.00 | N | ||
F6WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F6 EWALL NEA | 90.00 | 90.00 | E | ||
F6WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N1A | 0.00 | 90.00 | N | ||
F6WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 NWALL N2A | 0.00 | 90.00 | N | ||
F6WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S1A | 180.00 | 90.00 | S | ||
F6WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F6 SWALL S2A | 180.00 | 90.00 | S | ||
F6WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 WWALL C | 270.00 | 90.00 | W | ||
F6WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F6 EWALL C | 90.00 | 90.00 | E | ||
F7WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL SWA | 270.00 | 90.00 | W | ||
F7WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SWA | 180.00 | 90.00 | S | ||
F7WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NWA | 0.00 | 90.00 | N | ||
F7WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 WWALL NWA | 270.00 | 90.00 | W | ||
F7WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL SEA | 90.00 | 90.00 | E | ||
F7WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL SEA | 180.00 | 90.00 | S | ||
F7WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL NEA | 0.00 | 90.00 | N | ||
F7WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F7 EWALL NEA | 90.00 | 90.00 | E | ||
F7WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N1A | 0.00 | 90.00 | N | ||
F7WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 NWALL N2A | 0.00 | 90.00 | N | ||
F7WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S1A | 180.00 | 90.00 | S | ||
F7WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F7 SWALL S2A | 180.00 | 90.00 | S | ||
F7WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 WWALL C | 270.00 | 90.00 | W | ||
F7WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F7 EWALL C | 90.00 | 90.00 | E | ||
F8WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL SWA | 270.00 | 90.00 | W | ||
F8WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SWA | 180.00 | 90.00 | S | ||
F8WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NWA | 0.00 | 90.00 | N | ||
F8WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 WWALL NWA | 270.00 | 90.00 | W | ||
F8WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL SEA | 90.00 | 90.00 | E | ||
F8WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL SEA | 180.00 | 90.00 | S | ||
F8WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL NEA | 0.00 | 90.00 | N | ||
F8WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F8 EWALL NEA | 90.00 | 90.00 | E | ||
F8WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N1A | 0.00 | 90.00 | N | ||
F8WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 NWALL N2A | 0.00 | 90.00 | N | ||
F8WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S1A | 180.00 | 90.00 | S | ||
F8WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F8 SWALL S2A | 180.00 | 90.00 | S | ||
F8WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 WWALL C | 270.00 | 90.00 | W | ||
F8WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F8 EWALL C | 90.00 | 90.00 | E | ||
F9WINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL SWA | 270.00 | 90.00 | W | ||
F9WINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SWA | 180.00 | 90.00 | S | ||
F9WINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NWA | 0.00 | 90.00 | N | ||
F9WINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 WWALL NWA | 270.00 | 90.00 | W | ||
F9WINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL SEA | 90.00 | 90.00 | E | ||
F9WINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL SEA | 180.00 | 90.00 | S | ||
F9WINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL NEA | 0.00 | 90.00 | N | ||
F9WINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | F9 EWALL NEA | 90.00 | 90.00 | E | ||
F9WINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N1A | 0.00 | 90.00 | N | ||
F9WINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 NWALL N2A | 0.00 | 90.00 | N | ||
F9WINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S1A | 180.00 | 90.00 | S | ||
F9WINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | F9 SWALL S2A | 180.00 | 90.00 | S | ||
F9WINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 WWALL C | 270.00 | 90.00 | W | ||
F9WINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | F9 EWALL C | 90.00 | 90.00 | E | ||
TWINDOW2 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW3 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW4 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW6 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW8 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW5 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW7 | WINDOW_U_0.65_SHGC_0.25 | 6.97 | 0.00 | 0.00 | 6.97 | 6.97 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW9 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW10 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW11 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW12 | WINDOW_U_0.65_SHGC_0.25 | 10.59 | 0.00 | 0.00 | 10.59 | 10.59 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW13 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T WWALL C | 270.00 | 90.00 | W | ||
TWINDOW14 | WINDOW_U_0.65_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 90.00 | 90.00 | E | ||
Total or Average | 1150.39 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 423.59 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 726.80 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F2WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F2WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F2WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F3WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F3WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F3WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F4WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F4WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F4WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F6WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F6WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F6WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F7WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F7WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F7WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F8WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F8WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F8WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
F9WINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9WINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
F9WINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
F9WINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW6 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW8 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW7 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW9 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW11 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW12 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW13 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
G SW APARTMENT_LIGHTS_HARDWIRED | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G NW APARTMENT_LIGHTS_HARDWIRED | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
OFFICE_LIGHTS_HARDWIRED | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_HARDWIRED | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N1 APARTMENT_LIGHTS_HARDWIRED | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G N2 APARTMENT_LIGHTS_HARDWIRED | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S1 APARTMENT_LIGHTS_HARDWIRED | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G S2 APARTMENT_LIGHTS_HARDWIRED | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
G CORRIDOR_LIGHTS_HARDWIRED | G CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F2 SW APARTMENT_LIGHTS_HARDWIRED | F2 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NW APARTMENT_LIGHTS_HARDWIRED | F2 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 SE APARTMENT_LIGHTS_HARDWIRED | F2 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 NE APARTMENT_LIGHTS_HARDWIRED | F2 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N1 APARTMENT_LIGHTS_HARDWIRED | F2 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 N2 APARTMENT_LIGHTS_HARDWIRED | F2 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S1 APARTMENT_LIGHTS_HARDWIRED | F2 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 S2 APARTMENT_LIGHTS_HARDWIRED | F2 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F2 CORRIDOR_LIGHTS_HARDWIRED | F2 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F3 SW APARTMENT_LIGHTS_HARDWIRED | F3 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NW APARTMENT_LIGHTS_HARDWIRED | F3 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 SE APARTMENT_LIGHTS_HARDWIRED | F3 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 NE APARTMENT_LIGHTS_HARDWIRED | F3 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N1 APARTMENT_LIGHTS_HARDWIRED | F3 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 N2 APARTMENT_LIGHTS_HARDWIRED | F3 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S1 APARTMENT_LIGHTS_HARDWIRED | F3 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 S2 APARTMENT_LIGHTS_HARDWIRED | F3 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F3 CORRIDOR_LIGHTS_HARDWIRED | F3 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F4 SW APARTMENT_LIGHTS_HARDWIRED | F4 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NW APARTMENT_LIGHTS_HARDWIRED | F4 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 SE APARTMENT_LIGHTS_HARDWIRED | F4 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 NE APARTMENT_LIGHTS_HARDWIRED | F4 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N1 APARTMENT_LIGHTS_HARDWIRED | F4 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 N2 APARTMENT_LIGHTS_HARDWIRED | F4 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S1 APARTMENT_LIGHTS_HARDWIRED | F4 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 S2 APARTMENT_LIGHTS_HARDWIRED | F4 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F4 CORRIDOR_LIGHTS_HARDWIRED | F4 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
M SW APARTMENT_LIGHTS_HARDWIRED | M SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NW APARTMENT_LIGHTS_HARDWIRED | M NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M SE APARTMENT_LIGHTS_HARDWIRED | M SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M NE APARTMENT_LIGHTS_HARDWIRED | M NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N1 APARTMENT_LIGHTS_HARDWIRED | M N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M N2 APARTMENT_LIGHTS_HARDWIRED | M N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S1 APARTMENT_LIGHTS_HARDWIRED | M S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M S2 APARTMENT_LIGHTS_HARDWIRED | M S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
M CORRIDOR_LIGHTS_HARDWIRED | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_HARDWIRED | F6 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NW APARTMENT_LIGHTS_HARDWIRED | F6 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 SE APARTMENT_LIGHTS_HARDWIRED | F6 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 NE APARTMENT_LIGHTS_HARDWIRED | F6 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N1 APARTMENT_LIGHTS_HARDWIRED | F6 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 N2 APARTMENT_LIGHTS_HARDWIRED | F6 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S1 APARTMENT_LIGHTS_HARDWIRED | F6 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 S2 APARTMENT_LIGHTS_HARDWIRED | F6 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F6 CORRIDOR_LIGHTS_HARDWIRED | F6 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F7 SW APARTMENT_LIGHTS_HARDWIRED | F7 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NW APARTMENT_LIGHTS_HARDWIRED | F7 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 SE APARTMENT_LIGHTS_HARDWIRED | F7 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 NE APARTMENT_LIGHTS_HARDWIRED | F7 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N1 APARTMENT_LIGHTS_HARDWIRED | F7 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 N2 APARTMENT_LIGHTS_HARDWIRED | F7 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S1 APARTMENT_LIGHTS_HARDWIRED | F7 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 S2 APARTMENT_LIGHTS_HARDWIRED | F7 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F7 CORRIDOR_LIGHTS_HARDWIRED | F7 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F8 SW APARTMENT_LIGHTS_HARDWIRED | F8 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NW APARTMENT_LIGHTS_HARDWIRED | F8 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 SE APARTMENT_LIGHTS_HARDWIRED | F8 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 NE APARTMENT_LIGHTS_HARDWIRED | F8 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N1 APARTMENT_LIGHTS_HARDWIRED | F8 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 N2 APARTMENT_LIGHTS_HARDWIRED | F8 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S1 APARTMENT_LIGHTS_HARDWIRED | F8 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 S2 APARTMENT_LIGHTS_HARDWIRED | F8 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F8 CORRIDOR_LIGHTS_HARDWIRED | F8 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F9 SW APARTMENT_LIGHTS_HARDWIRED | F9 SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NW APARTMENT_LIGHTS_HARDWIRED | F9 NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 SE APARTMENT_LIGHTS_HARDWIRED | F9 SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 NE APARTMENT_LIGHTS_HARDWIRED | F9 NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N1 APARTMENT_LIGHTS_HARDWIRED | F9 N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 N2 APARTMENT_LIGHTS_HARDWIRED | F9 N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S1 APARTMENT_LIGHTS_HARDWIRED | F9 S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 S2 APARTMENT_LIGHTS_HARDWIRED | F9 S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
F9 CORRIDOR_LIGHTS_HARDWIRED | F9 CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
T SW APARTMENT_LIGHTS_HARDWIRED | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NW APARTMENT_LIGHTS_HARDWIRED | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T SE APARTMENT_LIGHTS_HARDWIRED | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T NE APARTMENT_LIGHTS_HARDWIRED | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N1 APARTMENT_LIGHTS_HARDWIRED | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T N2 APARTMENT_LIGHTS_HARDWIRED | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S1 APARTMENT_LIGHTS_HARDWIRED | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T S2 APARTMENT_LIGHTS_HARDWIRED | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
T CORRIDOR_LIGHTS_HARDWIRED | T CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
G SW APARTMENT_LIGHTS_PLUGIN | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G NW APARTMENT_LIGHTS_PLUGIN | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
OFFICE_LIGHTS_PLUGIN | OFFICE | 14.7681 | 88.25 | 1303.26 | GeneralLights-plugin | LTG_OFF_SCH | 62.05 | 168.00 | 61.07 | 0.0000 | Y | 14.94 |
G NE APARTMENT_LIGHTS_PLUGIN | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N1 APARTMENT_LIGHTS_PLUGIN | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G N2 APARTMENT_LIGHTS_PLUGIN | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S1 APARTMENT_LIGHTS_PLUGIN | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
G S2 APARTMENT_LIGHTS_PLUGIN | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SW APARTMENT_LIGHTS_PLUGIN | F2 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NW APARTMENT_LIGHTS_PLUGIN | F2 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 SE APARTMENT_LIGHTS_PLUGIN | F2 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 NE APARTMENT_LIGHTS_PLUGIN | F2 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N1 APARTMENT_LIGHTS_PLUGIN | F2 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 N2 APARTMENT_LIGHTS_PLUGIN | F2 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S1 APARTMENT_LIGHTS_PLUGIN | F2 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F2 S2 APARTMENT_LIGHTS_PLUGIN | F2 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SW APARTMENT_LIGHTS_PLUGIN | F3 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NW APARTMENT_LIGHTS_PLUGIN | F3 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 SE APARTMENT_LIGHTS_PLUGIN | F3 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 NE APARTMENT_LIGHTS_PLUGIN | F3 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N1 APARTMENT_LIGHTS_PLUGIN | F3 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 N2 APARTMENT_LIGHTS_PLUGIN | F3 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S1 APARTMENT_LIGHTS_PLUGIN | F3 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F3 S2 APARTMENT_LIGHTS_PLUGIN | F3 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SW APARTMENT_LIGHTS_PLUGIN | F4 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NW APARTMENT_LIGHTS_PLUGIN | F4 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 SE APARTMENT_LIGHTS_PLUGIN | F4 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 NE APARTMENT_LIGHTS_PLUGIN | F4 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N1 APARTMENT_LIGHTS_PLUGIN | F4 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 N2 APARTMENT_LIGHTS_PLUGIN | F4 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S1 APARTMENT_LIGHTS_PLUGIN | F4 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F4 S2 APARTMENT_LIGHTS_PLUGIN | F4 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SW APARTMENT_LIGHTS_PLUGIN | M SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NW APARTMENT_LIGHTS_PLUGIN | M NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M SE APARTMENT_LIGHTS_PLUGIN | M SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M NE APARTMENT_LIGHTS_PLUGIN | M NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N1 APARTMENT_LIGHTS_PLUGIN | M N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M N2 APARTMENT_LIGHTS_PLUGIN | M N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S1 APARTMENT_LIGHTS_PLUGIN | M S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M S2 APARTMENT_LIGHTS_PLUGIN | M S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
M CORRIDOR_LIGHTS_PLUGIN | M CORRIDOR | 6.7128 | 77.66 | 521.30 | GeneralLights-plugin | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 16.44 |
F6 SW APARTMENT_LIGHTS_PLUGIN | F6 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NW APARTMENT_LIGHTS_PLUGIN | F6 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 SE APARTMENT_LIGHTS_PLUGIN | F6 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 NE APARTMENT_LIGHTS_PLUGIN | F6 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N1 APARTMENT_LIGHTS_PLUGIN | F6 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 N2 APARTMENT_LIGHTS_PLUGIN | F6 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S1 APARTMENT_LIGHTS_PLUGIN | F6 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F6 S2 APARTMENT_LIGHTS_PLUGIN | F6 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SW APARTMENT_LIGHTS_PLUGIN | F7 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NW APARTMENT_LIGHTS_PLUGIN | F7 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 SE APARTMENT_LIGHTS_PLUGIN | F7 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 NE APARTMENT_LIGHTS_PLUGIN | F7 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N1 APARTMENT_LIGHTS_PLUGIN | F7 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 N2 APARTMENT_LIGHTS_PLUGIN | F7 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S1 APARTMENT_LIGHTS_PLUGIN | F7 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F7 S2 APARTMENT_LIGHTS_PLUGIN | F7 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SW APARTMENT_LIGHTS_PLUGIN | F8 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NW APARTMENT_LIGHTS_PLUGIN | F8 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 SE APARTMENT_LIGHTS_PLUGIN | F8 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 NE APARTMENT_LIGHTS_PLUGIN | F8 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N1 APARTMENT_LIGHTS_PLUGIN | F8 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 N2 APARTMENT_LIGHTS_PLUGIN | F8 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S1 APARTMENT_LIGHTS_PLUGIN | F8 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F8 S2 APARTMENT_LIGHTS_PLUGIN | F8 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SW APARTMENT_LIGHTS_PLUGIN | F9 SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NW APARTMENT_LIGHTS_PLUGIN | F9 NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 SE APARTMENT_LIGHTS_PLUGIN | F9 SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 NE APARTMENT_LIGHTS_PLUGIN | F9 NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N1 APARTMENT_LIGHTS_PLUGIN | F9 N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 N2 APARTMENT_LIGHTS_PLUGIN | F9 N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S1 APARTMENT_LIGHTS_PLUGIN | F9 S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
F9 S2 APARTMENT_LIGHTS_PLUGIN | F9 S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SW APARTMENT_LIGHTS_PLUGIN | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NW APARTMENT_LIGHTS_PLUGIN | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T SE APARTMENT_LIGHTS_PLUGIN | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T NE APARTMENT_LIGHTS_PLUGIN | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N1 APARTMENT_LIGHTS_PLUGIN | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T N2 APARTMENT_LIGHTS_PLUGIN | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S1 APARTMENT_LIGHTS_PLUGIN | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
T S2 APARTMENT_LIGHTS_PLUGIN | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.2679 | 14974.03 | 33959.19 | 296.56 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 10364.00 | AstronomicalClock | - | 83.76 | 83.76 | 162.95 | |
Exterior Lighting Total | 10364.00 | 162.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 332898.18 | 0.75 | ||
CENTRAL TOWER | EvaporativeFluidCooler:SingleSpeed | 266318.55 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4089.33 | 2665.72 | 1423.61 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4025.42 | 2619.30 | 1406.12 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP OFFICE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5922.42 | 3923.34 | 1999.09 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3326.60 | 2110.51 | 1216.09 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2580.22 | 1583.81 | 996.41 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2562.41 | 1570.95 | 991.46 | 0.61 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2729.55 | 1680.21 | 1049.34 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP G S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 2815.25 | 1743.57 | 1071.68 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4927.57 | 3253.14 | 1674.44 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4837.03 | 3186.11 | 1650.92 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4665.33 | 3061.45 | 1603.88 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4070.88 | 2624.58 | 1446.30 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3099.53 | 1943.06 | 1156.47 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3085.19 | 1932.58 | 1152.60 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3283.13 | 2068.74 | 1214.39 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3312.09 | 2090.31 | 1221.78 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5012.12 | 3290.43 | 1721.70 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4929.13 | 3229.34 | 1699.78 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4472.45 | 2892.13 | 1580.32 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4174.31 | 2678.40 | 1495.90 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3176.97 | 1987.60 | 1189.38 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3162.83 | 1977.31 | 1185.52 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3358.42 | 2111.54 | 1246.88 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3370.37 | 2120.44 | 1249.92 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5082.31 | 3323.83 | 1758.48 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5001.06 | 3264.24 | 1736.82 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4512.72 | 2904.46 | 1608.26 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4242.66 | 2712.23 | 1530.43 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3230.82 | 2017.95 | 1212.86 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3216.78 | 2007.78 | 1209.01 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3407.92 | 2138.53 | 1269.39 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3417.37 | 2145.56 | 1271.80 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5169.68 | 3373.76 | 1795.92 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5090.66 | 3315.94 | 1774.73 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4636.25 | 2971.84 | 1664.41 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4329.25 | 2762.70 | 1566.55 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3304.58 | 2064.53 | 1240.05 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3290.66 | 2054.45 | 1236.22 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3477.34 | 2181.96 | 1295.38 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP M S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3486.43 | 2188.72 | 1297.71 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5169.64 | 3360.79 | 1808.85 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5090.35 | 3302.97 | 1787.38 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4640.90 | 2963.67 | 1677.23 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4326.41 | 2749.51 | 1576.90 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3292.46 | 2049.59 | 1242.87 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3278.65 | 2039.63 | 1239.02 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3464.85 | 2165.92 | 1298.93 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3472.17 | 2171.74 | 1300.43 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5194.08 | 3367.83 | 1826.25 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5115.75 | 3310.86 | 1804.89 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4669.70 | 2974.89 | 1694.81 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4355.99 | 2760.38 | 1595.61 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3306.89 | 2054.84 | 1252.05 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3293.18 | 2044.98 | 1248.20 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3476.76 | 2169.10 | 1307.66 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3483.86 | 2174.73 | 1309.13 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5235.52 | 3388.75 | 1846.78 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5158.18 | 3332.60 | 1825.58 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4714.22 | 2998.78 | 1715.43 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4396.26 | 2781.42 | 1614.84 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3339.91 | 2074.13 | 1265.78 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3326.31 | 2064.36 | 1261.95 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3506.45 | 2185.89 | 1320.56 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3513.31 | 2191.34 | 1321.97 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5413.81 | 3512.02 | 1901.80 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5338.92 | 3457.56 | 1881.36 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4863.88 | 3100.48 | 1763.40 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4503.70 | 2852.00 | 1651.71 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3498.59 | 2184.79 | 1313.80 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3484.99 | 2174.98 | 1310.00 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3630.79 | 2272.05 | 1358.74 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 3639.73 | 2278.66 | 1361.07 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6492.52 | 4304.98 | 2187.54 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NW | Coil:Cooling:WaterToAirHeatPump:EquationFit | 6310.39 | 4171.76 | 2138.63 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T SE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5949.07 | 3897.03 | 2052.03 | 0.66 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T NE | Coil:Cooling:WaterToAirHeatPump:EquationFit | 5420.29 | 3514.43 | 1905.87 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4323.83 | 2778.60 | 1545.23 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T N2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4322.73 | 2777.92 | 1544.81 | 0.64 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S1 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4779.92 | 3119.96 | 1659.96 | 0.65 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP T S2 | Coil:Cooling:WaterToAirHeatPump:EquationFit | 4787.24 | 3125.54 | 1661.69 | 0.65 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4089.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4025.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5922.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 3326.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2580.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2562.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2729.55 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP G S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 2815.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4927.57 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4837.03 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4665.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4070.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3099.53 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3085.19 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3283.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3312.09 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5012.12 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 4929.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4472.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4174.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3176.97 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3162.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3358.42 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3370.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5082.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5001.06 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4512.72 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4242.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3230.82 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3216.78 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3407.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3417.37 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5169.68 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5090.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4636.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4329.25 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3304.58 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3290.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3477.34 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP M S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3486.43 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5169.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5090.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4640.90 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4326.41 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3292.46 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3278.65 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3464.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3472.17 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5194.08 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5115.75 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4669.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4355.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3306.89 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3293.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3476.76 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3483.86 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5235.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5158.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4714.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4396.26 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3339.91 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3326.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3506.45 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3513.31 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5413.81 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 5338.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4863.88 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 4503.70 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3498.59 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3484.99 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3630.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 3639.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6492.52 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NW | Coil:Heating:WaterToAirHeatPump:EquationFit | 6310.39 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T SE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5949.07 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T NE | Coil:Heating:WaterToAirHeatPump:EquationFit | 5420.29 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4323.83 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T N2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4322.73 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S1 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4779.92 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP T S2 | Coil:Heating:WaterToAirHeatPump:EquationFit | 4787.24 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | Coil:Heating:Electric | 3368.22 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | Coil:Heating:Electric | 3370.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | Coil:Heating:Electric | 4164.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | Coil:Heating:Electric | 3370.28 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | Coil:Heating:Electric | 2526.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | Coil:Heating:Electric | 2526.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | Coil:Heating:Electric | 2521.41 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | Coil:Heating:Electric | 2527.68 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | Coil:Heating:Electric | 3396.35 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | Coil:Heating:Electric | 3397.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | Coil:Heating:Electric | 3414.85 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | Coil:Heating:Electric | 3397.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | Coil:Heating:Electric | 2334.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | Coil:Heating:Electric | 2334.30 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | Coil:Heating:Electric | 2336.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | Coil:Heating:Electric | 2337.53 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | Coil:Heating:Electric | 3472.13 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | Coil:Heating:Electric | 3477.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | Coil:Heating:Electric | 3474.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | Coil:Heating:Electric | 3477.12 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | Coil:Heating:Electric | 2343.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | Coil:Heating:Electric | 2343.90 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | Coil:Heating:Electric | 2339.60 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | Coil:Heating:Electric | 2339.79 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | Coil:Heating:Electric | 3584.04 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | Coil:Heating:Electric | 3592.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | Coil:Heating:Electric | 3584.25 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | Coil:Heating:Electric | 3592.00 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | Coil:Heating:Electric | 2403.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | Coil:Heating:Electric | 2403.20 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | Coil:Heating:Electric | 2395.62 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | Coil:Heating:Electric | 2395.65 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | Coil:Heating:Electric | 3665.19 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | Coil:Heating:Electric | 3674.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | Coil:Heating:Electric | 3665.21 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | Coil:Heating:Electric | 3674.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | Coil:Heating:Electric | 2441.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | Coil:Heating:Electric | 2441.15 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | Coil:Heating:Electric | 2432.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | Coil:Heating:Electric | 2432.44 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | Coil:Heating:Electric | 3795.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | Coil:Heating:Electric | 3807.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | Coil:Heating:Electric | 3795.91 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | Coil:Heating:Electric | 3807.37 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | Coil:Heating:Electric | 2534.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | Coil:Heating:Electric | 2534.38 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | Coil:Heating:Electric | 2523.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | Coil:Heating:Electric | 2523.17 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | Coil:Heating:Electric | 3895.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | Coil:Heating:Electric | 3907.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | Coil:Heating:Electric | 3895.14 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | Coil:Heating:Electric | 3907.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | Coil:Heating:Electric | 2600.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | Coil:Heating:Electric | 2600.66 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | Coil:Heating:Electric | 2588.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | Coil:Heating:Electric | 2588.32 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | Coil:Heating:Electric | 3993.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | Coil:Heating:Electric | 4007.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | Coil:Heating:Electric | 3993.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | Coil:Heating:Electric | 4007.24 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | Coil:Heating:Electric | 2669.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | Coil:Heating:Electric | 2669.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | Coil:Heating:Electric | 2656.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | Coil:Heating:Electric | 2656.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | Coil:Heating:Electric | 4208.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | Coil:Heating:Electric | 4220.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | Coil:Heating:Electric | 4208.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | Coil:Heating:Electric | 4220.26 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | Coil:Heating:Electric | 2846.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | Coil:Heating:Electric | 2846.73 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | Coil:Heating:Electric | 2834.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | Coil:Heating:Electric | 2834.99 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | Coil:Heating:Electric | 4832.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | Coil:Heating:Electric | 4850.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | Coil:Heating:Electric | 4832.87 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | Coil:Heating:Electric | 4850.74 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | Coil:Heating:Electric | 3509.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | Coil:Heating:Electric | 3509.69 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | Coil:Heating:Electric | 3488.70 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | Coil:Heating:Electric | 3488.70 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
AIRLOOP G SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.02 | 1160.84 | 1.00 | General |
AIRLOOP G NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 239.65 | 1160.84 | 1.00 | General |
AIRLOOP OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 366.07 | 1160.84 | 1.00 | General |
AIRLOOP G NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 187.49 | 1160.84 | 1.00 | General |
AIRLOOP G N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 133.01 | 1160.84 | 1.00 | General |
AIRLOOP G N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 131.64 | 1160.84 | 1.00 | General |
AIRLOOP G S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.00 | 1160.84 | 1.00 | General |
AIRLOOP G S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 147.75 | 1160.84 | 1.00 | General |
AIRLOOP F2 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 303.29 | 1160.84 | 1.00 | General |
AIRLOOP F2 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 296.72 | 1160.84 | 1.00 | General |
AIRLOOP F2 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.86 | 1160.84 | 1.00 | General |
AIRLOOP F2 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 238.74 | 1160.84 | 1.00 | General |
AIRLOOP F2 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 169.03 | 1160.84 | 1.00 | General |
AIRLOOP F2 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.92 | 1160.84 | 1.00 | General |
AIRLOOP F2 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.27 | 1160.84 | 1.00 | General |
AIRLOOP F2 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 182.58 | 1160.84 | 1.00 | General |
AIRLOOP F3 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.16 | 1160.84 | 1.00 | General |
AIRLOOP F3 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 299.22 | 1160.84 | 1.00 | General |
AIRLOOP F3 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 263.65 | 1160.84 | 1.00 | General |
AIRLOOP F3 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 242.42 | 1160.84 | 1.00 | General |
AIRLOOP F3 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 172.53 | 1160.84 | 1.00 | General |
AIRLOOP F3 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 171.44 | 1160.84 | 1.00 | General |
AIRLOOP F3 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 183.60 | 1160.84 | 1.00 | General |
AIRLOOP F3 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 184.55 | 1160.84 | 1.00 | General |
AIRLOOP F4 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 307.14 | 1160.84 | 1.00 | General |
AIRLOOP F4 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.37 | 1160.84 | 1.00 | General |
AIRLOOP F4 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 263.40 | 1160.84 | 1.00 | General |
AIRLOOP F4 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.47 | 1160.84 | 1.00 | General |
AIRLOOP F4 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 174.83 | 1160.84 | 1.00 | General |
AIRLOOP F4 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 173.75 | 1160.84 | 1.00 | General |
AIRLOOP F4 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 185.55 | 1160.84 | 1.00 | General |
AIRLOOP F4 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 186.30 | 1160.84 | 1.00 | General |
AIRLOOP M SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 311.18 | 1160.84 | 1.00 | General |
AIRLOOP M NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 305.60 | 1160.84 | 1.00 | General |
AIRLOOP M SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 267.25 | 1160.84 | 1.00 | General |
AIRLOOP M NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 248.59 | 1160.84 | 1.00 | General |
AIRLOOP M N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 179.03 | 1160.84 | 1.00 | General |
AIRLOOP M N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 177.96 | 1160.84 | 1.00 | General |
AIRLOOP M S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 189.41 | 1160.84 | 1.00 | General |
AIRLOOP M S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 190.13 | 1160.84 | 1.00 | General |
AIRLOOP F6 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 308.69 | 1160.84 | 1.00 | General |
AIRLOOP F6 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 303.11 | 1160.84 | 1.00 | General |
AIRLOOP F6 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 265.31 | 1160.84 | 1.00 | General |
AIRLOOP F6 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 246.11 | 1160.84 | 1.00 | General |
AIRLOOP F6 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 176.79 | 1160.84 | 1.00 | General |
AIRLOOP F6 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 175.73 | 1160.84 | 1.00 | General |
AIRLOOP F6 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 186.97 | 1160.84 | 1.00 | General |
AIRLOOP F6 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 187.69 | 1160.84 | 1.00 | General |
AIRLOOP F7 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 308.48 | 1160.84 | 1.00 | General |
AIRLOOP F7 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 302.99 | 1160.84 | 1.00 | General |
AIRLOOP F7 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 265.57 | 1160.84 | 1.00 | General |
AIRLOOP F7 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 245.96 | 1160.84 | 1.00 | General |
AIRLOOP F7 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 176.78 | 1160.84 | 1.00 | General |
AIRLOOP F7 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 175.74 | 1160.84 | 1.00 | General |
AIRLOOP F7 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 186.75 | 1160.84 | 1.00 | General |
AIRLOOP F7 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 187.44 | 1160.84 | 1.00 | General |
AIRLOOP F8 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 309.84 | 1160.84 | 1.00 | General |
AIRLOOP F8 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 304.44 | 1160.84 | 1.00 | General |
AIRLOOP F8 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 267.27 | 1160.84 | 1.00 | General |
AIRLOOP F8 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 247.36 | 1160.84 | 1.00 | General |
AIRLOOP F8 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 178.32 | 1160.84 | 1.00 | General |
AIRLOOP F8 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 177.29 | 1160.84 | 1.00 | General |
AIRLOOP F8 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 188.02 | 1160.84 | 1.00 | General |
AIRLOOP F8 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 188.70 | 1160.84 | 1.00 | General |
AIRLOOP F9 SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.19 | 1160.84 | 1.00 | General |
AIRLOOP F9 NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 316.96 | 1160.84 | 1.00 | General |
AIRLOOP F9 SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 277.29 | 1160.84 | 1.00 | General |
AIRLOOP F9 NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 254.09 | 1160.84 | 1.00 | General |
AIRLOOP F9 N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 189.61 | 1160.84 | 1.00 | General |
AIRLOOP F9 N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 188.58 | 1160.84 | 1.00 | General |
AIRLOOP F9 S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 196.68 | 1160.84 | 1.00 | General |
AIRLOOP F9 S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 197.38 | 1160.84 | 1.00 | General |
AIRLOOP T SW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 405.03 | 1160.84 | 1.00 | General |
AIRLOOP T NW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 391.62 | 1160.84 | 1.00 | General |
AIRLOOP T SE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 361.39 | 1160.84 | 1.00 | General |
AIRLOOP T NE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 323.01 | 1160.84 | 1.00 | General |
AIRLOOP T N1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 249.98 | 1160.84 | 1.00 | General |
AIRLOOP T N2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 249.92 | 1160.84 | 1.00 | General |
AIRLOOP T S1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 286.52 | 1160.84 | 1.00 | General |
AIRLOOP T S2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 287.12 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0003 | 36.93 | 127739.32 | 0.30 |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 224180.02 | 0.0072 | 2312.31 | 319344.75 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.64 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2215.53 | 2658.64 | 0.175 | 0.210 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
G NW APARTMENT | 2175.88 | 2611.05 | 0.172 | 0.206 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
OFFICE | 3323.73 | 3988.47 | 0.263 | 0.315 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 33.48 | 0.01615 |
G NE APARTMENT | 1702.21 | 2042.65 | 0.135 | 0.162 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 32.10 | 0.01615 |
G N1 APARTMENT | 1207.70 | 1449.24 | 0.095 | 0.115 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.70 | 0.01615 |
G N2 APARTMENT | 1195.31 | 1434.38 | 0.095 | 0.113 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.70 | 0.01615 |
G S1 APARTMENT | 1280.26 | 1536.32 | 0.101 | 0.121 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
G S2 APARTMENT | 1341.50 | 1609.81 | 0.106 | 0.127 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F2 SW APARTMENT | 2753.54 | 3304.24 | 0.218 | 0.261 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F2 NW APARTMENT | 2693.96 | 3232.76 | 0.213 | 0.256 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F2 SE APARTMENT | 2577.10 | 3092.52 | 0.204 | 0.245 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.71 | 0.01615 |
F2 NE APARTMENT | 2167.50 | 2601.00 | 0.171 | 0.206 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
F2 N1 APARTMENT | 1534.73 | 1841.68 | 0.121 | 0.146 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F2 N2 APARTMENT | 1524.64 | 1829.57 | 0.121 | 0.145 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F2 S1 APARTMENT | 1636.79 | 1964.15 | 0.129 | 0.155 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F2 S2 APARTMENT | 1657.70 | 1989.24 | 0.131 | 0.157 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F3 SW APARTMENT | 2770.39 | 3324.47 | 0.219 | 0.263 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F3 NW APARTMENT | 2716.63 | 3259.96 | 0.215 | 0.258 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F3 SE APARTMENT | 2393.52 | 2872.22 | 0.189 | 0.227 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.71 | 0.01615 |
F3 NE APARTMENT | 2200.78 | 2640.93 | 0.174 | 0.209 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
F3 N1 APARTMENT | 1566.50 | 1879.79 | 0.124 | 0.149 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F3 N2 APARTMENT | 1556.59 | 1867.91 | 0.123 | 0.148 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F3 S1 APARTMENT | 1666.95 | 2000.34 | 0.132 | 0.158 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F3 S2 APARTMENT | 1675.60 | 2010.72 | 0.132 | 0.159 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F4 SW APARTMENT | 2788.33 | 3346.00 | 0.220 | 0.265 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F4 NW APARTMENT | 2736.05 | 3283.26 | 0.216 | 0.260 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F4 SE APARTMENT | 2391.22 | 2869.46 | 0.189 | 0.227 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.71 | 0.01615 |
F4 NE APARTMENT | 2219.40 | 2663.28 | 0.176 | 0.211 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
F4 N1 APARTMENT | 1587.36 | 1904.84 | 0.126 | 0.151 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F4 N2 APARTMENT | 1577.58 | 1893.10 | 0.125 | 0.150 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F4 S1 APARTMENT | 1684.60 | 2021.52 | 0.133 | 0.160 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F4 S2 APARTMENT | 1691.44 | 2029.73 | 0.134 | 0.160 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
M SW APARTMENT | 2824.95 | 3389.94 | 0.223 | 0.268 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
M NW APARTMENT | 2774.40 | 3329.28 | 0.219 | 0.263 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
M SE APARTMENT | 2426.17 | 2911.41 | 0.192 | 0.230 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
M NE APARTMENT | 2256.76 | 2708.11 | 0.178 | 0.214 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
M N1 APARTMENT | 1625.49 | 1950.59 | 0.129 | 0.154 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
M N2 APARTMENT | 1615.81 | 1938.97 | 0.128 | 0.153 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
M S1 APARTMENT | 1719.65 | 2063.58 | 0.136 | 0.163 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
M S2 APARTMENT | 1726.23 | 2071.48 | 0.136 | 0.164 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F6 SW APARTMENT | 2802.34 | 3362.81 | 0.222 | 0.266 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F6 NW APARTMENT | 2751.82 | 3302.19 | 0.218 | 0.261 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F6 SE APARTMENT | 2408.55 | 2890.26 | 0.190 | 0.229 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F6 NE APARTMENT | 2234.17 | 2681.00 | 0.177 | 0.212 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
F6 N1 APARTMENT | 1605.13 | 1926.16 | 0.127 | 0.152 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F6 N2 APARTMENT | 1595.57 | 1914.69 | 0.126 | 0.151 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F6 S1 APARTMENT | 1697.49 | 2036.98 | 0.134 | 0.161 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
F6 S2 APARTMENT | 1704.00 | 2044.80 | 0.135 | 0.162 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F7 SW APARTMENT | 2800.36 | 3360.43 | 0.221 | 0.266 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F7 NW APARTMENT | 2750.69 | 3300.82 | 0.218 | 0.261 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F7 SE APARTMENT | 2410.86 | 2893.03 | 0.191 | 0.229 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F7 NE APARTMENT | 2232.82 | 2679.38 | 0.177 | 0.212 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.79 | 0.01615 |
F7 N1 APARTMENT | 1605.03 | 1926.04 | 0.127 | 0.152 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F7 N2 APARTMENT | 1595.58 | 1914.69 | 0.126 | 0.151 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F7 S1 APARTMENT | 1695.45 | 2034.54 | 0.134 | 0.161 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
F7 S2 APARTMENT | 1701.76 | 2042.11 | 0.135 | 0.161 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F8 SW APARTMENT | 2812.71 | 3375.25 | 0.222 | 0.267 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F8 NW APARTMENT | 2763.85 | 3316.62 | 0.219 | 0.262 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F8 SE APARTMENT | 2426.26 | 2911.51 | 0.192 | 0.230 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F8 NE APARTMENT | 2245.49 | 2694.59 | 0.178 | 0.213 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.79 | 0.01615 |
F8 N1 APARTMENT | 1619.02 | 1942.83 | 0.128 | 0.154 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F8 N2 APARTMENT | 1609.67 | 1931.60 | 0.127 | 0.153 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F8 S1 APARTMENT | 1707.04 | 2048.44 | 0.135 | 0.162 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
F8 S2 APARTMENT | 1713.17 | 2055.80 | 0.135 | 0.163 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F9 SW APARTMENT | 2924.71 | 3509.66 | 0.231 | 0.278 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
F9 NW APARTMENT | 2877.49 | 3452.99 | 0.228 | 0.273 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.85 | 0.01615 |
F9 SE APARTMENT | 2517.20 | 3020.64 | 0.199 | 0.239 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
F9 NE APARTMENT | 2306.50 | 2767.80 | 0.182 | 0.219 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.79 | 0.01615 |
F9 N1 APARTMENT | 1721.54 | 2065.85 | 0.136 | 0.163 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F9 N2 APARTMENT | 1712.14 | 2054.56 | 0.135 | 0.162 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
F9 S1 APARTMENT | 1785.56 | 2142.67 | 0.141 | 0.169 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
F9 S2 APARTMENT | 1791.99 | 2150.39 | 0.142 | 0.170 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
T SW APARTMENT | 3676.59 | 4411.91 | 0.291 | 0.349 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 35.32 | 0.01615 |
T NW APARTMENT | 3554.88 | 4265.86 | 0.281 | 0.337 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 34.68 | 0.01615 |
T SE APARTMENT | 3280.53 | 3936.63 | 0.259 | 0.311 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
T NE APARTMENT | 2932.11 | 3518.53 | 0.232 | 0.278 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 33.48 | 0.01615 |
T N1 APARTMENT | 2269.46 | 2723.35 | 0.179 | 0.215 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.60 | 0.01615 |
T N2 APARTMENT | 2268.91 | 2722.69 | 0.179 | 0.215 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.60 | 0.01615 |
T S1 APARTMENT | 2601.18 | 3121.42 | 0.206 | 0.247 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
T S2 APARTMENT | 2606.66 | 3128.00 | 0.206 | 0.247 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2059.23 | 2471.07 | 0.093 | 0.111 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G NW APARTMENT | 2060.97 | 2473.17 | 0.093 | 0.111 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
OFFICE | 2363.04 | 2835.64 | 0.106 | 0.127 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -8.30 | 0.00188 |
G NE APARTMENT | 2060.97 | 2473.17 | 0.093 | 0.111 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G N1 APARTMENT | 1347.75 | 1617.30 | 0.061 | 0.073 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G N2 APARTMENT | 1347.75 | 1617.30 | 0.061 | 0.073 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G S1 APARTMENT | 1343.11 | 1611.73 | 0.060 | 0.072 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G S2 APARTMENT | 1348.41 | 1618.09 | 0.061 | 0.073 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
F2 SW APARTMENT | 2083.05 | 2499.67 | 0.094 | 0.112 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 NW APARTMENT | 2083.62 | 2500.34 | 0.094 | 0.112 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 SE APARTMENT | 2098.70 | 2518.45 | 0.094 | 0.113 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 NE APARTMENT | 2083.62 | 2500.34 | 0.094 | 0.112 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 N1 APARTMENT | 1184.91 | 1421.89 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 N2 APARTMENT | 1184.91 | 1421.89 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 S1 APARTMENT | 1186.62 | 1423.95 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F2 S2 APARTMENT | 1187.64 | 1425.17 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 SW APARTMENT | 2147.15 | 2576.58 | 0.096 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 NW APARTMENT | 2151.38 | 2581.65 | 0.097 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 SE APARTMENT | 2148.85 | 2578.62 | 0.097 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 NE APARTMENT | 2151.38 | 2581.65 | 0.097 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 N1 APARTMENT | 1193.04 | 1431.64 | 0.054 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 N2 APARTMENT | 1193.04 | 1431.64 | 0.054 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 S1 APARTMENT | 1189.40 | 1427.28 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F3 S2 APARTMENT | 1189.55 | 1427.47 | 0.053 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 SW APARTMENT | 2241.80 | 2690.16 | 0.101 | 0.121 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 NW APARTMENT | 2248.53 | 2698.24 | 0.101 | 0.121 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 SE APARTMENT | 2241.98 | 2690.37 | 0.101 | 0.121 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 NE APARTMENT | 2248.53 | 2698.24 | 0.101 | 0.121 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 N1 APARTMENT | 1243.18 | 1491.82 | 0.056 | 0.067 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 N2 APARTMENT | 1243.18 | 1491.82 | 0.056 | 0.067 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 S1 APARTMENT | 1236.77 | 1484.13 | 0.056 | 0.067 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F4 S2 APARTMENT | 1236.80 | 1484.16 | 0.056 | 0.067 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M SW APARTMENT | 2310.43 | 2772.52 | 0.104 | 0.125 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M NW APARTMENT | 2318.01 | 2781.62 | 0.104 | 0.125 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M SE APARTMENT | 2310.45 | 2772.54 | 0.104 | 0.125 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M NE APARTMENT | 2318.01 | 2781.62 | 0.104 | 0.125 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M N1 APARTMENT | 1275.28 | 1530.33 | 0.057 | 0.069 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M N2 APARTMENT | 1275.28 | 1530.33 | 0.057 | 0.069 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M S1 APARTMENT | 1267.92 | 1521.50 | 0.057 | 0.068 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
M S2 APARTMENT | 1267.92 | 1521.50 | 0.057 | 0.068 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 SW APARTMENT | 2420.98 | 2905.18 | 0.109 | 0.130 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 NW APARTMENT | 2430.67 | 2916.81 | 0.109 | 0.131 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 SE APARTMENT | 2420.98 | 2905.18 | 0.109 | 0.130 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 NE APARTMENT | 2430.67 | 2916.81 | 0.109 | 0.131 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 N1 APARTMENT | 1354.12 | 1624.95 | 0.061 | 0.073 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 N2 APARTMENT | 1354.12 | 1624.95 | 0.061 | 0.073 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 S1 APARTMENT | 1344.65 | 1613.58 | 0.060 | 0.072 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F6 S2 APARTMENT | 1344.65 | 1613.58 | 0.060 | 0.072 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 SW APARTMENT | 2504.90 | 3005.88 | 0.113 | 0.135 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 NW APARTMENT | 2515.55 | 3018.66 | 0.113 | 0.136 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 SE APARTMENT | 2504.90 | 3005.88 | 0.113 | 0.135 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 NE APARTMENT | 2515.55 | 3018.66 | 0.113 | 0.136 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 N1 APARTMENT | 1410.18 | 1692.21 | 0.063 | 0.076 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 N2 APARTMENT | 1410.18 | 1692.21 | 0.063 | 0.076 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 S1 APARTMENT | 1399.74 | 1679.69 | 0.063 | 0.075 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F7 S2 APARTMENT | 1399.74 | 1679.69 | 0.063 | 0.075 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 SW APARTMENT | 2588.47 | 3106.17 | 0.116 | 0.140 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 NW APARTMENT | 2599.70 | 3119.64 | 0.117 | 0.140 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 SE APARTMENT | 2588.47 | 3106.17 | 0.116 | 0.140 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 NE APARTMENT | 2599.70 | 3119.64 | 0.117 | 0.140 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 N1 APARTMENT | 1468.60 | 1762.32 | 0.066 | 0.079 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 N2 APARTMENT | 1468.60 | 1762.32 | 0.066 | 0.079 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 S1 APARTMENT | 1457.56 | 1749.08 | 0.065 | 0.079 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F8 S2 APARTMENT | 1457.56 | 1749.08 | 0.065 | 0.079 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 SW APARTMENT | 2770.10 | 3324.12 | 0.124 | 0.149 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 NW APARTMENT | 2779.85 | 3335.82 | 0.125 | 0.150 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 SE APARTMENT | 2770.10 | 3324.12 | 0.124 | 0.149 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 NE APARTMENT | 2779.85 | 3335.82 | 0.125 | 0.150 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 N1 APARTMENT | 1618.27 | 1941.93 | 0.073 | 0.087 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 N2 APARTMENT | 1618.27 | 1941.93 | 0.073 | 0.087 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 S1 APARTMENT | 1608.35 | 1930.02 | 0.072 | 0.087 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
F9 S2 APARTMENT | 1608.35 | 1930.02 | 0.072 | 0.087 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T SW APARTMENT | 3297.92 | 3957.50 | 0.148 | 0.178 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T NW APARTMENT | 3313.03 | 3975.63 | 0.149 | 0.179 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T SE APARTMENT | 3297.92 | 3957.50 | 0.148 | 0.178 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T NE APARTMENT | 3313.03 | 3975.63 | 0.149 | 0.179 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T N1 APARTMENT | 2178.92 | 2614.70 | 0.098 | 0.117 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T N2 APARTMENT | 2178.92 | 2614.70 | 0.098 | 0.117 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T S1 APARTMENT | 2161.17 | 2593.40 | 0.097 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
T S2 APARTMENT | 2161.17 | 2593.40 | 0.097 | 0.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -8.30 | 0.00188 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AIRLOOP G SW | 0.21 | 0.21 | 0.11 | 0.11 |
AIRLOOP G NW | 0.21 | 0.21 | 0.11 | 0.11 |
AIRLOOP OFFICE | 0.32 | 0.32 | 0.13 | 0.13 |
AIRLOOP G NE | 0.16 | 0.16 | 0.11 | 0.11 |
AIRLOOP G N1 | 0.11 | 0.11 | 0.07 | 0.07 |
AIRLOOP G N2 | 0.11 | 0.11 | 0.07 | 0.07 |
AIRLOOP G S1 | 0.12 | 0.12 | 0.07 | 0.07 |
AIRLOOP G S2 | 0.13 | 0.13 | 0.07 | 0.07 |
AIRLOOP F2 SW | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F2 NW | 0.26 | 0.26 | 0.11 | 0.11 |
AIRLOOP F2 SE | 0.24 | 0.24 | 0.11 | 0.11 |
AIRLOOP F2 NE | 0.21 | 0.21 | 0.11 | 0.11 |
AIRLOOP F2 N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F2 N2 | 0.14 | 0.14 | 0.06 | 0.06 |
AIRLOOP F2 S1 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F2 S2 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F3 SW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F3 NW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F3 SE | 0.23 | 0.23 | 0.12 | 0.12 |
AIRLOOP F3 NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP F3 N1 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F3 N2 | 0.15 | 0.15 | 0.06 | 0.06 |
AIRLOOP F3 S1 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F3 S2 | 0.16 | 0.16 | 0.06 | 0.06 |
AIRLOOP F4 SW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F4 NW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP F4 SE | 0.23 | 0.23 | 0.12 | 0.12 |
AIRLOOP F4 NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP F4 N1 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F4 N2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F4 S1 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F4 S2 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP M SW | 0.27 | 0.27 | 0.12 | 0.12 |
AIRLOOP M NW | 0.26 | 0.26 | 0.12 | 0.12 |
AIRLOOP M SE | 0.23 | 0.23 | 0.12 | 0.12 |
AIRLOOP M NE | 0.21 | 0.21 | 0.12 | 0.12 |
AIRLOOP M N1 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP M N2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP M S1 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP M S2 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F6 SW | 0.27 | 0.27 | 0.13 | 0.13 |
AIRLOOP F6 NW | 0.26 | 0.26 | 0.13 | 0.13 |
AIRLOOP F6 SE | 0.23 | 0.23 | 0.13 | 0.13 |
AIRLOOP F6 NE | 0.21 | 0.21 | 0.13 | 0.13 |
AIRLOOP F6 N1 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F6 N2 | 0.15 | 0.15 | 0.07 | 0.07 |
AIRLOOP F6 S1 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F6 S2 | 0.16 | 0.16 | 0.07 | 0.07 |
AIRLOOP F7 SW | 0.27 | 0.27 | 0.14 | 0.14 |
AIRLOOP F7 NW | 0.26 | 0.26 | 0.14 | 0.14 |
AIRLOOP F7 SE | 0.23 | 0.23 | 0.14 | 0.14 |
AIRLOOP F7 NE | 0.21 | 0.21 | 0.14 | 0.14 |
AIRLOOP F7 N1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F7 N2 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F7 S1 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP F7 S2 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP F8 SW | 0.27 | 0.27 | 0.14 | 0.14 |
AIRLOOP F8 NW | 0.26 | 0.26 | 0.14 | 0.14 |
AIRLOOP F8 SE | 0.23 | 0.23 | 0.14 | 0.14 |
AIRLOOP F8 NE | 0.21 | 0.21 | 0.14 | 0.14 |
AIRLOOP F8 N1 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F8 N2 | 0.15 | 0.15 | 0.08 | 0.08 |
AIRLOOP F8 S1 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP F8 S2 | 0.16 | 0.16 | 0.08 | 0.08 |
AIRLOOP F9 SW | 0.28 | 0.28 | 0.15 | 0.15 |
AIRLOOP F9 NW | 0.27 | 0.27 | 0.15 | 0.15 |
AIRLOOP F9 SE | 0.24 | 0.24 | 0.15 | 0.15 |
AIRLOOP F9 NE | 0.22 | 0.22 | 0.15 | 0.15 |
AIRLOOP F9 N1 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F9 N2 | 0.16 | 0.16 | 0.09 | 0.09 |
AIRLOOP F9 S1 | 0.17 | 0.17 | 0.09 | 0.09 |
AIRLOOP F9 S2 | 0.17 | 0.17 | 0.09 | 0.09 |
AIRLOOP T SW | 0.35 | 0.35 | 0.18 | 0.18 |
AIRLOOP T NW | 0.34 | 0.34 | 0.18 | 0.18 |
AIRLOOP T SE | 0.31 | 0.31 | 0.18 | 0.18 |
AIRLOOP T NE | 0.28 | 0.28 | 0.18 | 0.18 |
AIRLOOP T N1 | 0.22 | 0.22 | 0.12 | 0.12 |
AIRLOOP T N2 | 0.22 | 0.22 | 0.12 | 0.12 |
AIRLOOP T S1 | 0.25 | 0.25 | 0.12 | 0.12 |
AIRLOOP T S2 | 0.25 | 0.25 | 0.12 | 0.12 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4151.50 | 5665.00 | 1536.25 |
G NW APARTMENT | 4112.00 | 6081.00 | 1772.25 |
OFFICE | 1299.75 | 616.50 | 15.50 |
G NE APARTMENT | 4108.00 | 6003.25 | 1672.25 |
G N1 APARTMENT | 3756.00 | 6282.25 | 1565.00 |
G N2 APARTMENT | 3757.50 | 6273.00 | 1557.00 |
G S1 APARTMENT | 3833.00 | 5769.25 | 1337.50 |
G S2 APARTMENT | 3856.00 | 5698.00 | 1315.00 |
F2 SW APARTMENT | 4553.25 | 4228.50 | 901.00 |
F2 NW APARTMENT | 4286.25 | 5020.75 | 1072.00 |
F2 SE APARTMENT | 4719.50 | 3909.25 | 768.00 |
F2 NE APARTMENT | 4269.25 | 5023.25 | 1000.75 |
F2 N1 APARTMENT | 3991.25 | 5205.75 | 913.75 |
F2 N2 APARTMENT | 3989.50 | 5208.25 | 910.50 |
F2 S1 APARTMENT | 4389.25 | 4224.75 | 812.50 |
F2 S2 APARTMENT | 4411.75 | 4181.00 | 807.75 |
F3 SW APARTMENT | 4683.50 | 4029.75 | 882.00 |
F3 NW APARTMENT | 4382.25 | 4815.50 | 1038.50 |
F3 SE APARTMENT | 4730.25 | 3984.75 | 817.50 |
F3 NE APARTMENT | 4373.75 | 4846.25 | 966.75 |
F3 N1 APARTMENT | 4107.00 | 4932.25 | 867.00 |
F3 N2 APARTMENT | 4104.00 | 4943.25 | 867.50 |
F3 S1 APARTMENT | 4591.00 | 3899.25 | 781.75 |
F3 S2 APARTMENT | 4596.75 | 3891.25 | 780.75 |
F4 SW APARTMENT | 4717.50 | 4033.75 | 907.50 |
F4 NW APARTMENT | 4406.75 | 4804.25 | 1066.25 |
F4 SE APARTMENT | 4736.50 | 4034.50 | 857.25 |
F4 NE APARTMENT | 4409.00 | 4812.25 | 991.00 |
F4 N1 APARTMENT | 4139.00 | 4878.50 | 876.75 |
F4 N2 APARTMENT | 4137.00 | 4885.75 | 875.50 |
F4 S1 APARTMENT | 4642.00 | 3861.75 | 794.00 |
F4 S2 APARTMENT | 4642.00 | 3860.25 | 793.25 |
M SW APARTMENT | 4718.25 | 4064.75 | 911.50 |
M NW APARTMENT | 4406.00 | 4800.25 | 1063.00 |
M SE APARTMENT | 4729.50 | 4055.25 | 857.25 |
M NE APARTMENT | 4411.50 | 4807.25 | 991.25 |
M N1 APARTMENT | 4149.00 | 4852.00 | 867.75 |
M N2 APARTMENT | 4147.50 | 4858.00 | 864.75 |
M S1 APARTMENT | 4648.25 | 3870.00 | 790.25 |
M S2 APARTMENT | 4646.50 | 3872.50 | 791.00 |
F6 SW APARTMENT | 4650.50 | 4241.00 | 984.00 |
F6 NW APARTMENT | 4365.50 | 4970.75 | 1153.75 |
F6 SE APARTMENT | 4664.50 | 4207.75 | 920.25 |
F6 NE APARTMENT | 4352.50 | 4965.50 | 1069.00 |
F6 N1 APARTMENT | 4097.25 | 4992.00 | 925.25 |
F6 N2 APARTMENT | 4092.50 | 5003.00 | 924.75 |
F6 S1 APARTMENT | 4557.25 | 4065.50 | 842.50 |
F6 S2 APARTMENT | 4556.00 | 4073.00 | 842.25 |
F7 SW APARTMENT | 4601.00 | 4361.50 | 1030.75 |
F7 NW APARTMENT | 4343.25 | 5070.75 | 1205.00 |
F7 SE APARTMENT | 4624.25 | 4314.00 | 959.75 |
F7 NE APARTMENT | 4328.50 | 5058.50 | 1121.00 |
F7 N1 APARTMENT | 4066.00 | 5091.25 | 956.00 |
F7 N2 APARTMENT | 4061.75 | 5099.75 | 954.75 |
F7 S1 APARTMENT | 4500.25 | 4204.75 | 870.25 |
F7 S2 APARTMENT | 4501.00 | 4210.75 | 871.00 |
F8 SW APARTMENT | 4566.25 | 4453.50 | 1063.25 |
F8 NW APARTMENT | 4329.50 | 5141.00 | 1242.00 |
F8 SE APARTMENT | 4579.50 | 4400.75 | 985.50 |
F8 NE APARTMENT | 4321.50 | 5127.00 | 1162.25 |
F8 N1 APARTMENT | 4047.00 | 5162.75 | 977.00 |
F8 N2 APARTMENT | 4044.50 | 5169.00 | 975.50 |
F8 S1 APARTMENT | 4453.25 | 4301.50 | 888.25 |
F8 S2 APARTMENT | 4454.00 | 4306.25 | 890.75 |
F9 SW APARTMENT | 4546.50 | 4540.75 | 1105.00 |
F9 NW APARTMENT | 4380.75 | 5178.50 | 1306.25 |
F9 SE APARTMENT | 4569.00 | 4487.50 | 1032.50 |
F9 NE APARTMENT | 4367.00 | 5164.50 | 1227.75 |
F9 N1 APARTMENT | 4064.75 | 5205.00 | 1007.00 |
F9 N2 APARTMENT | 4064.00 | 5211.25 | 1006.00 |
F9 S1 APARTMENT | 4402.25 | 4406.00 | 903.50 |
F9 S2 APARTMENT | 4402.00 | 4408.75 | 903.25 |
T SW APARTMENT | 4923.25 | 4912.00 | 1648.00 |
T NW APARTMENT | 4852.50 | 5436.00 | 1903.00 |
T SE APARTMENT | 4937.50 | 4871.75 | 1616.00 |
T NE APARTMENT | 4820.50 | 5435.00 | 1852.75 |
T N1 APARTMENT | 4438.50 | 5448.75 | 1501.00 |
T N2 APARTMENT | 4439.25 | 5453.75 | 1503.75 |
T S1 APARTMENT | 4618.25 | 4731.25 | 1290.25 |
T S2 APARTMENT | 4618.50 | 4730.75 | 1289.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5803.75 | 6417.50 | 2332.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 2.25 | 5.75 | 2.25 | 5.75 |
G NW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
OFFICE | 1.25 | 5.50 | 0.00 | 5.50 |
G NE APARTMENT | 1.25 | 8.00 | 1.25 | 8.00 |
G N1 APARTMENT | 3.50 | 5.75 | 3.50 | 5.75 |
G N2 APARTMENT | 3.25 | 6.50 | 3.25 | 6.50 |
G S1 APARTMENT | 3.75 | 69.50 | 3.75 | 69.50 |
G S2 APARTMENT | 2.75 | 52.00 | 2.75 | 52.00 |
F2 SW APARTMENT | 0.25 | 2.50 | 0.25 | 2.50 |
F2 NW APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
F2 SE APARTMENT | 1.75 | 9.75 | 1.75 | 9.75 |
F2 NE APARTMENT | 1.00 | 6.25 | 1.00 | 6.25 |
F2 N1 APARTMENT | 4.00 | 4.00 | 4.00 | 4.00 |
F2 N2 APARTMENT | 3.25 | 4.25 | 3.25 | 4.25 |
F2 S1 APARTMENT | 2.00 | 49.25 | 2.00 | 49.25 |
F2 S2 APARTMENT | 2.00 | 45.25 | 2.00 | 45.25 |
F3 SW APARTMENT | 0.50 | 4.50 | 0.50 | 4.50 |
F3 NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F3 SE APARTMENT | 1.00 | 25.00 | 1.00 | 25.00 |
F3 NE APARTMENT | 1.00 | 8.75 | 1.00 | 8.75 |
F3 N1 APARTMENT | 4.00 | 7.00 | 4.00 | 7.00 |
F3 N2 APARTMENT | 4.50 | 7.50 | 4.50 | 7.50 |
F3 S1 APARTMENT | 1.00 | 51.25 | 1.00 | 51.25 |
F3 S2 APARTMENT | 2.00 | 50.75 | 2.00 | 50.75 |
F4 SW APARTMENT | 0.75 | 5.50 | 0.75 | 5.50 |
F4 NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
F4 SE APARTMENT | 0.25 | 28.75 | 0.25 | 28.75 |
F4 NE APARTMENT | 1.50 | 14.50 | 1.50 | 14.50 |
F4 N1 APARTMENT | 3.75 | 8.50 | 3.75 | 8.50 |
F4 N2 APARTMENT | 2.75 | 8.75 | 2.75 | 8.75 |
F4 S1 APARTMENT | 1.25 | 51.25 | 1.25 | 51.25 |
F4 S2 APARTMENT | 2.00 | 50.50 | 2.00 | 50.50 |
M SW APARTMENT | 0.25 | 6.00 | 0.25 | 6.00 |
M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 0.75 | 23.50 | 0.75 | 23.50 |
M NE APARTMENT | 0.75 | 16.50 | 0.75 | 16.50 |
M N1 APARTMENT | 2.75 | 9.00 | 2.75 | 9.00 |
M N2 APARTMENT | 3.75 | 10.00 | 3.75 | 10.00 |
M S1 APARTMENT | 1.25 | 50.50 | 1.25 | 50.50 |
M S2 APARTMENT | 1.50 | 50.25 | 1.50 | 50.25 |
F6 SW APARTMENT | 0.25 | 6.25 | 0.25 | 6.25 |
F6 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F6 SE APARTMENT | 0.50 | 24.00 | 0.50 | 24.00 |
F6 NE APARTMENT | 1.25 | 18.50 | 1.25 | 18.50 |
F6 N1 APARTMENT | 3.75 | 9.75 | 3.75 | 9.75 |
F6 N2 APARTMENT | 2.50 | 11.00 | 2.50 | 11.00 |
F6 S1 APARTMENT | 1.50 | 48.50 | 1.50 | 48.50 |
F6 S2 APARTMENT | 1.00 | 48.50 | 1.00 | 48.50 |
F7 SW APARTMENT | 0.75 | 6.75 | 0.75 | 6.75 |
F7 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F7 SE APARTMENT | 0.25 | 23.50 | 0.25 | 23.50 |
F7 NE APARTMENT | 0.25 | 19.50 | 0.25 | 19.50 |
F7 N1 APARTMENT | 3.50 | 11.25 | 3.50 | 11.25 |
F7 N2 APARTMENT | 2.25 | 13.00 | 2.25 | 13.00 |
F7 S1 APARTMENT | 0.75 | 48.25 | 0.75 | 48.25 |
F7 S2 APARTMENT | 1.50 | 48.50 | 1.50 | 48.50 |
F8 SW APARTMENT | 0.25 | 6.75 | 0.25 | 6.75 |
F8 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F8 SE APARTMENT | 0.50 | 23.50 | 0.50 | 23.50 |
F8 NE APARTMENT | 0.00 | 20.75 | 0.00 | 20.75 |
F8 N1 APARTMENT | 2.50 | 12.50 | 2.50 | 12.50 |
F8 N2 APARTMENT | 2.25 | 14.00 | 2.25 | 14.00 |
F8 S1 APARTMENT | 1.75 | 49.25 | 1.75 | 49.25 |
F8 S2 APARTMENT | 1.50 | 49.50 | 1.50 | 49.50 |
F9 SW APARTMENT | 0.50 | 6.25 | 0.50 | 6.25 |
F9 NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SE APARTMENT | 0.00 | 19.00 | 0.00 | 19.00 |
F9 NE APARTMENT | 0.00 | 23.50 | 0.00 | 23.50 |
F9 N1 APARTMENT | 0.75 | 9.75 | 0.75 | 9.75 |
F9 N2 APARTMENT | 1.00 | 12.00 | 1.00 | 12.00 |
F9 S1 APARTMENT | 1.25 | 42.25 | 1.25 | 42.25 |
F9 S2 APARTMENT | 1.00 | 41.75 | 1.00 | 41.75 |
T SW APARTMENT | 0.25 | 1.75 | 0.25 | 1.75 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.50 | 6.75 | 0.50 | 6.75 |
T NE APARTMENT | 0.00 | 9.00 | 0.00 | 9.00 |
T N1 APARTMENT | 0.50 | 0.25 | 0.50 | 0.25 |
T N2 APARTMENT | 0.75 | 0.25 | 0.75 | 0.25 |
T S1 APARTMENT | 1.25 | 8.25 | 1.25 | 8.25 |
T S2 APARTMENT | 0.25 | 8.75 | 0.25 | 8.75 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 84.50 | 101.00 | 83.50 | 101.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.359 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.343 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.520 | 0.192 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.162 | 0.000 | 0.342 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.098 | 0.000 | 0.335 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.098 | 0.000 | 0.335 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.098 | 0.000 | 0.355 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.098 | 0.000 | 0.357 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.424 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.404 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.426 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.233 | 0.000 | 0.403 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.140 | 0.000 | 0.399 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.140 | 0.000 | 0.399 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.141 | 0.000 | 0.421 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.422 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.276 | 0.000 | 0.469 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.276 | 0.000 | 0.447 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.276 | 0.000 | 0.469 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.276 | 0.000 | 0.447 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.166 | 0.000 | 0.443 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.166 | 0.000 | 0.443 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.166 | 0.000 | 0.467 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.166 | 0.000 | 0.468 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.308 | 0.000 | 0.487 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.308 | 0.000 | 0.465 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.308 | 0.000 | 0.487 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.308 | 0.000 | 0.464 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.186 | 0.000 | 0.461 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.186 | 0.000 | 0.461 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.186 | 0.000 | 0.486 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.186 | 0.000 | 0.486 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.335 | 0.000 | 0.511 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.335 | 0.000 | 0.488 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.335 | 0.000 | 0.511 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.335 | 0.000 | 0.487 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.202 | 0.000 | 0.484 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.202 | 0.000 | 0.484 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.202 | 0.000 | 0.510 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.202 | 0.000 | 0.510 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.358 | 0.000 | 0.532 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.358 | 0.000 | 0.506 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.358 | 0.000 | 0.532 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.357 | 0.000 | 0.506 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.216 | 0.000 | 0.503 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.216 | 0.000 | 0.503 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.216 | 0.000 | 0.531 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.216 | 0.000 | 0.531 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.378 | 0.000 | 0.550 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.378 | 0.000 | 0.523 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.378 | 0.000 | 0.550 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.378 | 0.000 | 0.522 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.228 | 0.000 | 0.520 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.228 | 0.000 | 0.520 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.228 | 0.000 | 0.549 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.228 | 0.000 | 0.549 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.396 | 0.000 | 0.568 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.396 | 0.000 | 0.540 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.396 | 0.000 | 0.568 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.396 | 0.000 | 0.539 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.239 | 0.000 | 0.537 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.239 | 0.000 | 0.537 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.239 | 0.000 | 0.567 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.239 | 0.000 | 0.567 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.413 | 0.000 | 0.585 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.413 | 0.000 | 0.557 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.413 | 0.000 | 0.585 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.413 | 0.000 | 0.556 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.249 | 0.000 | 0.554 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.249 | 0.000 | 0.554 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.249 | 0.000 | 0.584 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.249 | 0.000 | 0.584 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.428 | 0.000 | 0.599 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.428 | 0.000 | 0.570 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.428 | 0.000 | 0.599 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.428 | 0.000 | 0.570 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.258 | 0.000 | 0.568 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.258 | 0.000 | 0.568 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.355 | 0.258 | 0.000 | 0.598 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.258 | 0.000 | 0.598 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.96 | 0.504 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F2 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F3 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F4 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F6 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F7 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F8 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.342 | 0.000 | 0.000 | 0.000 |
F8 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
F9 SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
F9 S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.96 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Surfaces by ClassTotal | Outdoors | |
Wall | 420 | 140 |
Floor | 90 | 9 |
Roof | 90 | 9 |
Internal Mass | 80 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 140 | 140 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 80 |
Conditioned Zones | 80 |
Unconditioned Zones | 10 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 4156 |
Defaulted Fields | 814 |
Fields with Defaults | 11184 |
Autosized Fields | 1293 |
Autosizable Fields | 1630 |
Autocalculated Fields | 907 |
Autocalculatable Fields | 1710 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
Electricity:Building | 1433.88 | 25760.85 | 01-JAN-03:15 | 70162.48 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 296.56 | 6715.87 | 01-JAN-00:15 | 14401.37 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 242.55 | 5824.91 | 01-JAN-00:15 | 11484.27 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 39.38 | 663.42 | 01-JAN-00:15 | 2934.49 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 29.88 | 469.18 | 01-JAN-00:15 | 2345.88 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F2 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F2 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F2 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F3 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F3 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F3 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F4 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F4 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F4 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:M SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 32.88 | 1042.61 | 01-JAN-00:15 | 1042.61 | 01-JAN-00:15 |
Electricity:Zone:F6 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F6 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F6 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F7 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F7 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F7 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F8 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F8 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F8 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:F9 SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:F9 S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:F9 CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T CORRIDOR | 179.47 | 1701.70 | 01-JAN-00:15 | 10868.20 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 16.44 | 521.30 | 01-JAN-00:15 | 521.30 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 54.01 | 890.97 | 01-JAN-00:15 | 2917.11 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 1137.32 | 19044.98 | 01-JAN-03:15 | 57142.09 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.50 | 194.24 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F2 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F3 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F4 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F6 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F7 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F8 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:F9 S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T CORRIDOR | 163.03 | 1180.40 | 01-JAN-00:15 | 10346.90 | 01-JAN-07:15 |
Fans:Electricity | 599.19 | 19000.27 | 01-JAN-00:15 | 19000.27 | 01-JAN-00:30 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F2 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F3 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F4 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F6 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F7 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F8 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:F9 S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:HVAC | 1445.35 | 19661.52 | 18-JAN-03:15 | 107444.82 | 21-AUG-15:15 |
ElectricityProduced:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityProduced:HVAC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricityProduced | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
ElectricityPurchased:Plant | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
Cogeneration:ElectricityPurchased | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
ElectricityNet:Plant | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
Cogeneration:ElectricityNet | 3145.91 | 53714.57 | 18-MAY-05:00 | 181326.71 | 29-AUG-18:30 |
ExteriorLights:Electricity | 162.95 | 0.00 | 01-JAN-07:15 | 10364.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 162.95 | 0.00 | 01-JAN-07:15 | 10364.00 | 01-JAN-00:15 |
General:Fans:Electricity | 599.19 | 19000.27 | 01-JAN-00:15 | 19000.27 | 01-JAN-00:30 |
Cooling:Electricity | 674.94 | 0.00 | 01-JAN-00:15 | 87026.09 | 21-AUG-15:15 |
Heating:Electricity | 135.05 | 0.00 | 13-JAN-17:45 | 77030.10 | 31-JAN-04:00 |
Electricity:Plant | 103.72 | 36.93 | 13-JAN-17:45 | 5844.67 | 31-MAY-16:15 |
HeatRejection:Electricity | 32.61 | 0.00 | 01-JAN-00:15 | 3495.43 | 31-MAY-16:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 71.11 | 36.93 | 13-JAN-17:45 | 2349.24 | 01-JAN-00:15 |
WIRED_LTG_ELECTRICITY | 0.44 | 0.00 | 01-JAN-00:15 | 21.60 | 01-JAN-19:30 |
WIRED_INT_EQUIP | 979.40 | 1018.50 | 01-JAN-00:15 | 10185.00 | 01-JAN-07:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1476.48 | 2357.00 | 14-JAN-24:00 | 370648.49 | 31-JAN-07:00 |
Gas:Plant | 1476.48 | 2357.00 | 14-JAN-24:00 | 370648.49 | 31-JAN-07:00 |
WaterSystems:Gas | 1002.57 | 2357.00 | 01-JAN-00:15 | 77910.06 | 29-JAN-08:00 |
Water Heater:WaterSystems:Gas | 1002.57 | 2357.00 | 01-JAN-00:15 | 77910.06 | 29-JAN-08:00 |
Heating:Gas | 473.91 | 0.00 | 10-JAN-14:30 | 312472.66 | 31-JAN-04:15 |
Boiler:Heating:Gas | 473.91 | 0.00 | 10-JAN-14:30 | 312472.66 | 31-JAN-04:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
PlantLoopCoolingDemand:Facility | 2981.87 | 0.00 | 01-JAN-00:15 | 413980.45 | 03-AUG-14:45 |
PlantLoopCoolingDemand:HVAC | 2981.87 | 0.00 | 01-JAN-00:15 | 413980.45 | 03-AUG-14:45 |
CoolingCoils:PlantLoopCoolingDemand | 2981.87 | 0.00 | 01-JAN-00:15 | 413980.45 | 03-AUG-14:45 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 6648.45 | 0.00 | 01-JAN-02:15 | 0.00 | 29-AUG-17:15 |
Water:Plant | 6648.45 | 0.00 | 01-JAN-02:15 | 0.00 | 29-AUG-17:15 |
WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 6648.45 | 0.00 | 01-JAN-02:15 | 0.00 | 29-AUG-17:15 |
MainsWater:Plant | 6648.45 | 0.00 | 01-JAN-02:15 | 0.00 | 29-AUG-17:15 |
WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
sub cat:WaterSystems:Water | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
sub cat:WaterSystems:MainsWater | 4778.51 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
HeatRejection:Water | 1869.94 | 0.00 | 01-JAN-00:15 | 0.00 | 29-AUG-14:15 |
HeatRejection:MainsWater | 1869.94 | 0.00 | 01-JAN-00:15 | 0.00 | 29-AUG-14:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 1161.52 | 383.77 | 30-JUL-01:15 | 275230.20 | 31-JAN-06:15 |
PlantLoopHeatingDemand:Plant | 777.89 | 383.77 | 30-JUL-01:15 | 54794.45 | 30-JAN-08:00 |
WaterSystems:PlantLoopHeatingDemand | 777.89 | 383.77 | 30-JUL-01:15 | 54794.45 | 30-JAN-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 5676.94 | 4813.22 | 22-APR-02:00 | 799905.91 | 31-JAN-04:15 |
EnergyTransfer:Building | 1693.26 | 3313.17 | 01-NOV-21:15 | 253648.02 | 31-JAN-04:00 |
EnergyTransfer:Zone:G SW APARTMENT | 17.22 | 0.01 | 08-APR-04:15 | 2722.63 | 30-AUG-15:15 |
Heating:EnergyTransfer | 364.50 | 0.00 | 26-FEB-19:45 | 253648.02 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 4.28 | 0.00 | 01-JAN-11:00 | 2556.30 | 31-JAN-04:00 |
Cooling:EnergyTransfer | 1328.76 | 0.00 | 01-JAN-00:15 | 187379.53 | 10-JUL-16:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 12.94 | 0.00 | 01-JAN-00:15 | 2722.63 | 30-AUG-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 16.78 | 0.02 | 22-OCT-00:15 | 2582.77 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.09 | 0.00 | 10-JAN-14:30 | 2582.77 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 10.69 | 0.00 | 01-JAN-00:15 | 2421.50 | 02-JUN-17:15 |
EnergyTransfer:Zone:OFFICE | 25.04 | 0.00 | 03-MAY-23:30 | 3824.70 | 30-AUG-13:00 |
Heating:EnergyTransfer:Zone:OFFICE | 2.82 | 0.00 | 01-JAN-08:30 | 2416.69 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 22.22 | 0.00 | 01-JAN-00:15 | 3824.70 | 30-AUG-13:00 |
EnergyTransfer:Zone:G NE APARTMENT | 16.52 | 0.01 | 02-MAY-00:15 | 2592.62 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 5.86 | 0.00 | 13-JAN-10:30 | 2592.62 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 10.67 | 0.00 | 01-JAN-00:15 | 1858.55 | 10-JUL-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 11.43 | 0.01 | 04-OCT-10:00 | 1528.61 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.28 | 0.00 | 04-JAN-20:30 | 1528.61 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 8.15 | 0.00 | 01-JAN-00:15 | 1351.66 | 04-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 11.43 | 0.01 | 01-NOV-12:00 | 1529.08 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.28 | 0.00 | 04-JAN-20:30 | 1529.08 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 8.15 | 0.00 | 01-JAN-00:15 | 1338.31 | 04-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 12.57 | 0.01 | 13-JAN-16:30 | 1748.01 | 30-AUG-15:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.69 | 0.00 | 01-JAN-06:30 | 1469.20 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 10.87 | 0.00 | 01-JAN-00:15 | 1748.01 | 30-AUG-15:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 12.77 | 0.00 | 17-MAR-13:30 | 1813.59 | 30-AUG-14:45 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.60 | 0.00 | 01-JAN-06:30 | 1454.74 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.16 | 0.00 | 01-JAN-00:15 | 1813.59 | 30-AUG-14:45 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F2 SW APARTMENT | 23.34 | 0.02 | 02-NOV-03:45 | 3314.28 | 30-AUG-16:15 |
Heating:EnergyTransfer:Zone:F2 SW APARTMENT | 3.65 | 0.00 | 01-JAN-07:45 | 3067.57 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 SW APARTMENT | 19.69 | 0.00 | 01-JAN-00:15 | 3314.28 | 30-AUG-16:15 |
EnergyTransfer:Zone:F2 NW APARTMENT | 21.55 | 0.01 | 23-NOV-11:15 | 3169.91 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F2 NW APARTMENT | 5.65 | 0.00 | 04-JAN-20:45 | 3169.91 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 NW APARTMENT | 15.91 | 0.00 | 01-JAN-00:15 | 2976.83 | 02-JUN-17:30 |
EnergyTransfer:Zone:F2 SE APARTMENT | 24.42 | 0.06 | 01-DEC-16:00 | 3148.01 | 30-AUG-13:00 |
Heating:EnergyTransfer:Zone:F2 SE APARTMENT | 3.15 | 0.00 | 01-JAN-07:15 | 3012.46 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 SE APARTMENT | 21.27 | 0.00 | 01-JAN-00:15 | 3148.01 | 30-AUG-13:00 |
EnergyTransfer:Zone:F2 NE APARTMENT | 21.38 | 0.05 | 08-APR-01:45 | 3188.67 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F2 NE APARTMENT | 5.43 | 0.00 | 04-JAN-20:45 | 3188.67 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 NE APARTMENT | 15.95 | 0.00 | 01-JAN-00:15 | 2370.51 | 10-JUL-16:30 |
EnergyTransfer:Zone:F2 N1 APARTMENT | 14.95 | 0.03 | 29-APR-20:45 | 1776.51 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F2 N1 APARTMENT | 2.31 | 0.00 | 01-JAN-06:30 | 1776.51 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 N1 APARTMENT | 12.64 | 0.00 | 01-JAN-00:15 | 1716.11 | 04-JUN-17:30 |
EnergyTransfer:Zone:F2 N2 APARTMENT | 14.95 | 0.02 | 03-NOV-11:00 | 1777.62 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F2 N2 APARTMENT | 2.31 | 0.00 | 01-JAN-06:30 | 1777.62 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 N2 APARTMENT | 12.64 | 0.00 | 01-JAN-00:15 | 1705.74 | 04-JUN-17:30 |
EnergyTransfer:Zone:F2 S1 APARTMENT | 17.96 | 0.05 | 02-MAY-09:45 | 2188.25 | 30-AUG-15:00 |
Heating:EnergyTransfer:Zone:F2 S1 APARTMENT | 1.16 | 0.00 | 01-JAN-01:00 | 1657.22 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 S1 APARTMENT | 16.80 | 0.00 | 01-JAN-00:15 | 2188.25 | 30-AUG-15:00 |
EnergyTransfer:Zone:F2 S2 APARTMENT | 18.06 | 0.04 | 15-MAR-12:00 | 2209.73 | 30-AUG-15:00 |
Heating:EnergyTransfer:Zone:F2 S2 APARTMENT | 1.14 | 0.00 | 01-JAN-01:00 | 1652.86 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F2 S2 APARTMENT | 16.93 | 0.00 | 01-JAN-00:15 | 2209.73 | 30-AUG-15:00 |
EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F2 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F3 SW APARTMENT | 24.48 | 0.09 | 28-FEB-00:30 | 3360.97 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 SW APARTMENT | 3.83 | 0.00 | 01-JAN-07:45 | 3360.97 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 SW APARTMENT | 20.65 | 0.00 | 01-JAN-00:15 | 3328.91 | 30-AUG-15:15 |
EnergyTransfer:Zone:F3 NW APARTMENT | 22.61 | 0.03 | 12-MAR-02:00 | 3485.68 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 NW APARTMENT | 5.86 | 0.00 | 04-JAN-20:30 | 3485.68 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 NW APARTMENT | 16.75 | 0.00 | 01-JAN-00:15 | 3015.99 | 02-JUN-17:30 |
EnergyTransfer:Zone:F3 SE APARTMENT | 24.54 | 0.02 | 18-MAR-23:00 | 3376.28 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 SE APARTMENT | 3.63 | 0.00 | 01-JAN-07:15 | 3376.28 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 SE APARTMENT | 20.91 | 0.00 | 01-JAN-00:15 | 3020.99 | 30-AUG-13:30 |
EnergyTransfer:Zone:F3 NE APARTMENT | 22.44 | 0.11 | 08-MAR-23:45 | 3508.28 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 NE APARTMENT | 5.66 | 0.00 | 04-JAN-20:45 | 3508.28 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 NE APARTMENT | 16.79 | 0.00 | 01-JAN-00:15 | 2433.25 | 10-JUL-17:00 |
EnergyTransfer:Zone:F3 N1 APARTMENT | 15.88 | 0.01 | 02-OCT-16:30 | 1931.16 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 N1 APARTMENT | 2.29 | 0.00 | 01-JAN-03:00 | 1931.16 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 N1 APARTMENT | 13.59 | 0.00 | 01-JAN-00:15 | 1763.26 | 04-JUN-17:30 |
EnergyTransfer:Zone:F3 N2 APARTMENT | 15.88 | 0.00 | 25-MAR-08:00 | 1932.67 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F3 N2 APARTMENT | 2.29 | 0.00 | 01-JAN-03:00 | 1932.67 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 N2 APARTMENT | 13.59 | 0.00 | 01-JAN-00:15 | 1753.16 | 04-JUN-17:30 |
EnergyTransfer:Zone:F3 S1 APARTMENT | 19.21 | 0.06 | 17-MAR-13:30 | 2315.49 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F3 S1 APARTMENT | 1.17 | 0.00 | 01-JAN-00:45 | 1789.56 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 S1 APARTMENT | 18.04 | 0.00 | 01-JAN-00:15 | 2315.49 | 22-OCT-13:00 |
EnergyTransfer:Zone:F3 S2 APARTMENT | 19.24 | 0.00 | 04-APR-15:30 | 2322.91 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F3 S2 APARTMENT | 1.17 | 0.00 | 01-JAN-00:45 | 1790.21 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F3 S2 APARTMENT | 18.08 | 0.00 | 01-JAN-00:15 | 2322.91 | 22-OCT-13:00 |
EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F3 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F4 SW APARTMENT | 24.97 | 0.02 | 05-MAR-01:15 | 3640.85 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 SW APARTMENT | 4.19 | 0.00 | 01-JAN-07:45 | 3640.85 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 SW APARTMENT | 20.77 | 0.00 | 01-JAN-00:15 | 3351.09 | 30-AUG-15:15 |
EnergyTransfer:Zone:F4 NW APARTMENT | 23.19 | 0.02 | 10-OCT-08:45 | 3770.76 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 NW APARTMENT | 6.28 | 0.00 | 04-JAN-20:30 | 3770.76 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 NW APARTMENT | 16.92 | 0.00 | 01-JAN-00:15 | 3040.48 | 02-JUN-17:30 |
EnergyTransfer:Zone:F4 SE APARTMENT | 24.89 | 0.12 | 22-DEC-01:00 | 3668.94 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 SE APARTMENT | 4.06 | 0.00 | 01-JAN-07:30 | 3668.94 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 SE APARTMENT | 20.83 | 0.00 | 01-JAN-00:15 | 3038.92 | 30-AUG-13:30 |
EnergyTransfer:Zone:F4 NE APARTMENT | 23.03 | 0.02 | 27-APR-10:00 | 3795.06 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 NE APARTMENT | 6.08 | 0.00 | 04-JAN-20:45 | 3795.06 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 NE APARTMENT | 16.95 | 0.00 | 01-JAN-00:15 | 2466.05 | 10-JUL-17:00 |
EnergyTransfer:Zone:F4 N1 APARTMENT | 16.27 | 0.01 | 01-NOV-10:15 | 2092.00 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 N1 APARTMENT | 2.45 | 0.00 | 01-JAN-02:45 | 2092.00 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 N1 APARTMENT | 13.82 | 0.00 | 01-JAN-00:15 | 1787.13 | 04-JUN-17:30 |
EnergyTransfer:Zone:F4 N2 APARTMENT | 16.27 | 0.01 | 17-MAR-12:45 | 2093.68 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F4 N2 APARTMENT | 2.45 | 0.00 | 01-JAN-03:00 | 2093.68 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 N2 APARTMENT | 13.81 | 0.00 | 01-JAN-00:15 | 1777.29 | 04-JUN-17:30 |
EnergyTransfer:Zone:F4 S1 APARTMENT | 19.58 | 0.01 | 02-MAY-12:00 | 2348.53 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F4 S1 APARTMENT | 1.30 | 0.00 | 01-JAN-00:45 | 1947.97 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 S1 APARTMENT | 18.28 | 0.00 | 01-JAN-00:15 | 2348.53 | 22-OCT-13:00 |
EnergyTransfer:Zone:F4 S2 APARTMENT | 19.59 | 0.02 | 17-OCT-19:00 | 2354.73 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F4 S2 APARTMENT | 1.30 | 0.00 | 01-JAN-00:45 | 1949.83 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F4 S2 APARTMENT | 18.29 | 0.00 | 01-JAN-00:15 | 2354.73 | 22-OCT-13:00 |
EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F4 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M SW APARTMENT | 25.51 | 0.01 | 16-MAR-00:15 | 3871.01 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 4.53 | 0.00 | 01-JAN-07:45 | 3871.01 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 20.99 | 0.00 | 01-JAN-00:15 | 3391.86 | 30-AUG-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 23.87 | 0.01 | 10-NOV-16:45 | 3998.26 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 6.64 | 0.00 | 04-JAN-20:30 | 3998.26 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 17.23 | 0.00 | 01-JAN-00:15 | 3081.15 | 02-JUN-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 25.42 | 0.01 | 05-NOV-09:45 | 3901.22 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 4.40 | 0.00 | 01-JAN-07:30 | 3901.22 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 21.02 | 0.00 | 01-JAN-00:15 | 3113.39 | 30-AUG-13:15 |
EnergyTransfer:Zone:M NE APARTMENT | 23.70 | 0.00 | 05-OCT-09:30 | 4023.04 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 6.43 | 0.00 | 04-JAN-20:45 | 4023.04 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 17.27 | 0.00 | 01-JAN-00:15 | 2516.50 | 10-JUL-17:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 16.77 | 0.03 | 19-DEC-03:15 | 2220.45 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.61 | 0.00 | 01-JAN-02:45 | 2220.45 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 14.16 | 0.00 | 01-JAN-00:15 | 1827.95 | 10-JUL-17:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 16.77 | 0.01 | 17-MAY-05:45 | 2222.05 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.61 | 0.00 | 01-JAN-02:45 | 2222.05 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 14.16 | 0.00 | 01-JAN-00:15 | 1818.41 | 10-JUL-17:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 19.98 | 0.00 | 10-APR-19:15 | 2376.91 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.43 | 0.00 | 01-JAN-01:00 | 2080.46 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 18.55 | 0.00 | 01-JAN-00:15 | 2376.91 | 22-OCT-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 19.98 | 0.04 | 15-NOV-13:45 | 2382.83 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.43 | 0.00 | 01-JAN-01:00 | 2082.30 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 18.55 | 0.00 | 01-JAN-00:15 | 2382.83 | 22-OCT-13:00 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F6 SW APARTMENT | 25.34 | 0.06 | 16-NOV-04:15 | 4126.15 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 SW APARTMENT | 5.11 | 0.00 | 01-JAN-11:00 | 4126.15 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 SW APARTMENT | 20.23 | 0.00 | 01-JAN-00:15 | 3372.62 | 30-AUG-15:15 |
EnergyTransfer:Zone:F6 NW APARTMENT | 24.04 | 0.08 | 22-FEB-23:00 | 4250.45 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 NW APARTMENT | 7.36 | 0.00 | 04-JAN-20:45 | 4250.45 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 NW APARTMENT | 16.68 | 0.00 | 01-JAN-00:15 | 3059.62 | 02-JUN-17:30 |
EnergyTransfer:Zone:F6 SE APARTMENT | 25.23 | 0.00 | 08-MAR-23:30 | 4156.81 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 SE APARTMENT | 4.98 | 0.00 | 01-JAN-07:45 | 4156.81 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 SE APARTMENT | 20.25 | 0.00 | 01-JAN-00:15 | 3104.00 | 30-AUG-13:15 |
EnergyTransfer:Zone:F6 NE APARTMENT | 23.86 | 0.02 | 13-MAR-03:30 | 4274.93 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 NE APARTMENT | 7.14 | 0.00 | 04-JAN-20:45 | 4274.93 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 NE APARTMENT | 16.72 | 0.00 | 01-JAN-00:15 | 2501.39 | 10-JUL-17:00 |
EnergyTransfer:Zone:F6 N1 APARTMENT | 16.62 | 0.00 | 06-APR-09:30 | 2385.94 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 N1 APARTMENT | 3.03 | 0.00 | 01-JAN-06:30 | 2385.94 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 N1 APARTMENT | 13.59 | 0.00 | 01-JAN-00:15 | 1810.62 | 10-JUL-17:00 |
EnergyTransfer:Zone:F6 N2 APARTMENT | 16.62 | 0.00 | 06-APR-20:45 | 2387.34 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F6 N2 APARTMENT | 3.03 | 0.00 | 01-JAN-06:30 | 2387.34 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 N2 APARTMENT | 13.59 | 0.00 | 01-JAN-00:15 | 1801.24 | 10-JUL-17:00 |
EnergyTransfer:Zone:F6 S1 APARTMENT | 19.46 | 0.01 | 15-MAR-12:00 | 2338.25 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F6 S1 APARTMENT | 1.69 | 0.00 | 01-JAN-01:00 | 2244.36 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 S1 APARTMENT | 17.77 | 0.00 | 01-JAN-00:15 | 2338.25 | 22-OCT-13:00 |
EnergyTransfer:Zone:F6 S2 APARTMENT | 19.46 | 0.02 | 14-OCT-18:45 | 2344.23 | 22-OCT-13:00 |
Heating:EnergyTransfer:Zone:F6 S2 APARTMENT | 1.70 | 0.00 | 01-JAN-01:00 | 2246.17 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F6 S2 APARTMENT | 17.77 | 0.00 | 01-JAN-00:15 | 2344.23 | 22-OCT-13:00 |
EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F6 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F7 SW APARTMENT | 25.42 | 0.03 | 10-APR-21:45 | 4340.11 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 SW APARTMENT | 5.60 | 0.00 | 01-JAN-11:00 | 4340.11 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 SW APARTMENT | 19.82 | 0.00 | 01-JAN-00:15 | 3373.62 | 30-AUG-15:15 |
EnergyTransfer:Zone:F7 NW APARTMENT | 24.36 | 0.04 | 06-NOV-10:30 | 4459.48 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 NW APARTMENT | 7.92 | 0.00 | 04-JAN-20:45 | 4459.48 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 NW APARTMENT | 16.44 | 0.00 | 01-JAN-00:15 | 3059.45 | 10-JUL-16:30 |
EnergyTransfer:Zone:F7 SE APARTMENT | 25.30 | 0.00 | 04-MAR-15:15 | 4370.74 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 SE APARTMENT | 5.45 | 0.00 | 01-JAN-07:45 | 4370.74 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 SE APARTMENT | 19.85 | 0.00 | 01-JAN-00:15 | 3115.58 | 30-AUG-13:15 |
EnergyTransfer:Zone:F7 NE APARTMENT | 24.18 | 0.04 | 22-APR-02:00 | 4483.53 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 NE APARTMENT | 7.71 | 0.00 | 04-JAN-20:45 | 4483.53 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 NE APARTMENT | 16.47 | 0.00 | 01-JAN-00:15 | 2511.60 | 10-JUL-17:00 |
EnergyTransfer:Zone:F7 N1 APARTMENT | 16.71 | 0.02 | 10-APR-18:15 | 2520.51 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 N1 APARTMENT | 3.37 | 0.00 | 01-JAN-06:30 | 2520.51 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 N1 APARTMENT | 13.34 | 0.00 | 01-JAN-00:15 | 1814.36 | 10-JUL-17:00 |
EnergyTransfer:Zone:F7 N2 APARTMENT | 16.71 | 0.07 | 20-JUN-05:45 | 2521.72 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 N2 APARTMENT | 3.37 | 0.00 | 01-JAN-06:30 | 2521.72 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 N2 APARTMENT | 13.34 | 0.00 | 01-JAN-00:15 | 1805.10 | 10-JUL-17:00 |
EnergyTransfer:Zone:F7 S1 APARTMENT | 19.26 | 0.01 | 07-APR-20:45 | 2380.67 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 S1 APARTMENT | 1.92 | 0.00 | 01-JAN-01:00 | 2380.67 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 S1 APARTMENT | 17.34 | 0.00 | 01-JAN-00:15 | 2317.20 | 22-OCT-13:00 |
EnergyTransfer:Zone:F7 S2 APARTMENT | 19.26 | 0.00 | 02-MAY-11:15 | 2382.44 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F7 S2 APARTMENT | 1.93 | 0.00 | 01-JAN-01:00 | 2382.44 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F7 S2 APARTMENT | 17.34 | 0.00 | 01-JAN-00:15 | 2323.23 | 22-OCT-13:00 |
EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F7 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F8 SW APARTMENT | 25.67 | 0.00 | 23-NOV-10:30 | 4538.34 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 SW APARTMENT | 6.06 | 0.00 | 01-JAN-11:15 | 4538.34 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 SW APARTMENT | 19.61 | 0.00 | 01-JAN-00:15 | 3385.25 | 30-AUG-15:15 |
EnergyTransfer:Zone:F8 NW APARTMENT | 24.82 | 0.00 | 05-APR-08:45 | 4650.99 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 NW APARTMENT | 8.46 | 0.00 | 04-JAN-20:45 | 4650.99 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 NW APARTMENT | 16.36 | 0.00 | 01-JAN-00:15 | 3078.73 | 10-JUL-16:30 |
EnergyTransfer:Zone:F8 SE APARTMENT | 25.54 | 0.01 | 25-DEC-21:30 | 4568.78 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 SE APARTMENT | 5.91 | 0.00 | 01-JAN-08:00 | 4568.78 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 SE APARTMENT | 19.63 | 0.00 | 01-JAN-00:15 | 3137.43 | 30-AUG-13:15 |
EnergyTransfer:Zone:F8 NE APARTMENT | 24.64 | 0.02 | 15-MAR-23:45 | 4674.98 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 NE APARTMENT | 8.24 | 0.00 | 04-JAN-21:00 | 4674.98 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 NE APARTMENT | 16.40 | 0.00 | 01-JAN-00:15 | 2531.73 | 10-JUL-17:00 |
EnergyTransfer:Zone:F8 N1 APARTMENT | 16.96 | 0.00 | 22-MAY-18:15 | 2644.92 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 N1 APARTMENT | 3.70 | 0.00 | 01-JAN-06:30 | 2644.92 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 N1 APARTMENT | 13.26 | 0.00 | 01-JAN-00:15 | 1966.79 | 06-AUG-18:15 |
EnergyTransfer:Zone:F8 N2 APARTMENT | 16.96 | 0.02 | 25-OCT-20:30 | 2646.05 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 N2 APARTMENT | 3.71 | 0.00 | 01-JAN-06:30 | 2646.05 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 N2 APARTMENT | 13.26 | 0.00 | 01-JAN-00:15 | 1960.44 | 06-AUG-18:15 |
EnergyTransfer:Zone:F8 S1 APARTMENT | 19.25 | 0.01 | 29-OCT-19:15 | 2509.18 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 S1 APARTMENT | 2.16 | 0.00 | 01-JAN-01:00 | 2509.18 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 S1 APARTMENT | 17.10 | 0.00 | 01-JAN-00:15 | 2315.52 | 30-AUG-14:30 |
EnergyTransfer:Zone:F8 S2 APARTMENT | 19.25 | 0.03 | 17-OCT-20:15 | 2510.94 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F8 S2 APARTMENT | 2.16 | 0.00 | 01-JAN-01:00 | 2510.94 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F8 S2 APARTMENT | 17.09 | 0.00 | 01-JAN-00:15 | 2321.14 | 30-AUG-14:30 |
EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F8 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:F9 SW APARTMENT | 26.68 | 0.00 | 13-JAN-21:45 | 4825.06 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 SW APARTMENT | 6.83 | 0.00 | 01-JAN-11:15 | 4825.06 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 SW APARTMENT | 19.85 | 0.00 | 01-JAN-00:15 | 3472.41 | 30-AUG-15:15 |
EnergyTransfer:Zone:F9 NW APARTMENT | 26.12 | 0.02 | 15-OCT-01:00 | 4920.33 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 NW APARTMENT | 9.35 | 0.00 | 04-JAN-21:00 | 4920.33 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 NW APARTMENT | 16.76 | 0.00 | 01-JAN-00:15 | 3200.03 | 10-JUL-16:30 |
EnergyTransfer:Zone:F9 SE APARTMENT | 26.52 | 0.06 | 05-MAR-05:45 | 4854.31 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 SE APARTMENT | 6.66 | 0.00 | 01-JAN-11:15 | 4854.31 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 SE APARTMENT | 19.86 | 0.00 | 01-JAN-00:15 | 3228.86 | 30-AUG-13:00 |
EnergyTransfer:Zone:F9 NE APARTMENT | 25.90 | 0.00 | 27-FEB-19:45 | 4944.50 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 NE APARTMENT | 9.10 | 0.00 | 04-JAN-21:00 | 4944.50 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 NE APARTMENT | 16.80 | 0.00 | 01-JAN-00:15 | 2608.82 | 10-JUL-17:00 |
EnergyTransfer:Zone:F9 N1 APARTMENT | 17.92 | 0.04 | 02-MAY-24:00 | 2843.61 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 N1 APARTMENT | 4.34 | 0.00 | 04-JAN-19:30 | 2843.61 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 N1 APARTMENT | 13.58 | 0.00 | 01-JAN-00:15 | 2038.25 | 06-AUG-18:15 |
EnergyTransfer:Zone:F9 N2 APARTMENT | 17.93 | 0.05 | 13-MAR-08:30 | 2844.68 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 N2 APARTMENT | 4.35 | 0.00 | 04-JAN-19:45 | 2844.68 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 N2 APARTMENT | 13.58 | 0.00 | 01-JAN-00:15 | 2032.07 | 06-AUG-18:15 |
EnergyTransfer:Zone:F9 S1 APARTMENT | 19.81 | 0.01 | 22-MAY-20:15 | 2724.09 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 S1 APARTMENT | 2.60 | 0.00 | 01-JAN-02:45 | 2724.09 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 S1 APARTMENT | 17.21 | 0.00 | 01-JAN-00:15 | 2395.24 | 30-AUG-14:15 |
EnergyTransfer:Zone:F9 S2 APARTMENT | 19.81 | 0.01 | 29-OCT-07:45 | 2725.79 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:F9 S2 APARTMENT | 2.60 | 0.00 | 01-JAN-02:45 | 2725.79 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:F9 S2 APARTMENT | 17.21 | 0.00 | 01-JAN-00:15 | 2402.47 | 30-AUG-14:15 |
EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:F9 CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:T SW APARTMENT | 31.54 | 0.02 | 16-APR-22:45 | 5623.65 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 10.32 | 0.00 | 01-JAN-11:30 | 5623.65 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 21.22 | 0.00 | 01-JAN-00:15 | 4189.37 | 30-AUG-14:45 |
EnergyTransfer:Zone:T NW APARTMENT | 30.86 | 0.01 | 22-OCT-23:15 | 5682.93 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 12.63 | 0.00 | 10-JAN-14:00 | 5682.93 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 18.23 | 0.00 | 01-JAN-00:15 | 3796.90 | 10-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 31.05 | 0.01 | 05-OCT-02:00 | 5646.94 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 10.04 | 0.00 | 01-JAN-11:15 | 5646.94 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 21.01 | 0.00 | 01-JAN-00:15 | 3920.78 | 30-AUG-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 30.24 | 0.01 | 23-NOV-14:15 | 5704.56 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 12.20 | 0.00 | 15-JAN-07:45 | 5704.56 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 18.04 | 0.00 | 01-JAN-00:15 | 3261.21 | 05-JUN-14:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 21.62 | 0.02 | 20-DEC-18:45 | 3566.93 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 6.90 | 0.00 | 04-JAN-20:30 | 3566.93 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 14.72 | 0.00 | 01-JAN-00:15 | 2505.75 | 10-JUL-16:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 21.62 | 0.02 | 20-DEC-18:00 | 3567.65 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 6.91 | 0.00 | 04-JAN-20:30 | 3567.65 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 14.71 | 0.00 | 01-JAN-00:15 | 2490.50 | 10-JUL-16:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 23.12 | 0.00 | 15-JAN-04:30 | 3494.22 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 5.11 | 0.00 | 01-JAN-08:00 | 3494.22 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 18.01 | 0.00 | 01-JAN-00:15 | 3215.90 | 30-AUG-13:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 23.13 | 0.01 | 23-MAY-03:45 | 3495.21 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 5.12 | 0.00 | 01-JAN-08:00 | 3495.21 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 18.02 | 0.00 | 01-JAN-00:15 | 3225.31 | 30-AUG-13:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Plant | 1131.52 | 383.77 | 30-JUL-01:15 | 274097.09 | 31-JAN-06:15 |
WaterSystems:EnergyTransfer | 777.88 | 383.77 | 30-JUL-01:15 | 54788.85 | 30-JAN-08:00 |
sub cat:WaterSystems:EnergyTransfer | 777.88 | 383.77 | 30-JUL-01:15 | 54788.85 | 30-JAN-08:00 |
EnergyTransfer:HVAC | 2852.16 | 0.00 | 13-JAN-17:45 | 330429.08 | 03-AUG-14:45 |
CoolingCoils:EnergyTransfer | 2351.75 | 0.00 | 01-JAN-00:15 | 330429.08 | 03-AUG-14:45 |
HeatingCoils:EnergyTransfer | 500.41 | 0.00 | 13-JAN-17:45 | 313191.48 | 31-JAN-04:00 |
PlantLoopHeatingDemand:HVAC | 383.64 | 0.00 | 13-JAN-17:45 | 237138.33 | 31-JAN-04:00 |
HeatingCoils:PlantLoopHeatingDemand | 383.64 | 0.00 | 13-JAN-17:45 | 237138.33 | 31-JAN-04:00 |
Boilers:EnergyTransfer | 353.64 | 0.00 | 10-JAN-14:30 | 234354.50 | 31-JAN-04:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 4.279 | -12.938 | 0.000 | 0.000 | 3.762 | 1.087 | 12.213 | 18.230 | 0.000 | 0.660 | 0.000 | 0.000 | -7.638 | 0.000 | -7.023 | -12.630 |
G NW APARTMENT | 6.089 | -10.692 | 0.000 | 0.000 | 3.789 | 1.087 | 12.213 | 11.050 | 0.000 | 0.658 | 0.000 | 0.000 | -7.857 | 0.000 | -6.508 | -9.829 |
OFFICE | 2.824 | -22.218 | 0.000 | 0.000 | 0.514 | 29.882 | 9.495 | 17.932 | 0.000 | 0.502 | 0.000 | 0.000 | -7.706 | 0.000 | -3.767 | -27.459 |
G NE APARTMENT | 5.856 | -10.666 | 0.000 | 0.000 | 3.800 | 1.087 | 12.213 | 10.717 | 0.000 | 0.658 | 0.000 | 0.000 | -7.574 | 0.000 | -6.455 | -9.636 |
G N1 APARTMENT | 3.277 | -8.148 | 0.000 | 0.000 | 3.803 | 1.087 | 12.213 | 4.440 | 0.000 | 0.461 | 0.000 | 0.000 | -4.858 | 0.000 | -4.845 | -7.430 |
G N2 APARTMENT | 3.279 | -8.150 | 0.000 | 0.000 | 3.804 | 1.087 | 12.213 | 4.439 | 0.000 | 0.461 | 0.000 | 0.000 | -4.855 | 0.000 | -4.842 | -7.435 |
G S1 APARTMENT | 1.695 | -10.873 | 0.000 | 0.000 | 3.764 | 1.087 | 12.213 | 11.694 | 0.000 | 0.460 | 0.000 | 0.000 | -4.628 | 0.000 | -5.410 | -10.001 |
G S2 APARTMENT | 1.603 | -11.164 | 0.000 | 0.000 | 3.759 | 1.087 | 12.213 | 11.675 | 0.000 | 0.460 | 0.000 | 0.000 | -4.645 | 0.000 | -5.471 | -9.517 |
F2 SW APARTMENT | 3.654 | -19.687 | 0.000 | 0.000 | 3.700 | 1.087 | 12.213 | 17.359 | 0.000 | 0.905 | 0.000 | 0.000 | -8.298 | 0.000 | -9.647 | -1.286 |
F2 NW APARTMENT | 5.646 | -15.907 | 0.000 | 0.000 | 3.744 | 1.087 | 12.213 | 10.445 | 0.000 | 0.900 | 0.000 | 0.000 | -8.483 | 0.000 | -8.943 | -0.703 |
F2 SE APARTMENT | 3.150 | -21.265 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 17.087 | 0.000 | 0.904 | 1.170 | 0.000 | -8.232 | 0.000 | -9.805 | -0.000 |
F2 NE APARTMENT | 5.427 | -15.950 | 0.000 | 0.000 | 3.756 | 1.087 | 12.213 | 10.132 | 0.000 | 0.900 | 0.000 | 0.000 | -8.168 | 0.000 | -8.874 | -0.522 |
F2 N1 APARTMENT | 2.307 | -12.645 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 4.126 | 0.000 | 0.616 | 0.476 | 0.000 | -5.301 | 0.000 | -6.632 | -0.000 |
F2 N2 APARTMENT | 2.309 | -12.644 | 0.000 | 0.000 | 3.754 | 1.087 | 12.213 | 4.126 | 0.000 | 0.616 | 0.464 | 0.000 | -5.297 | 0.000 | -6.627 | -0.000 |
F2 S1 APARTMENT | 1.156 | -16.798 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 11.143 | 0.000 | 0.618 | 0.002 | 0.000 | -5.035 | 0.000 | -7.421 | -0.655 |
F2 S2 APARTMENT | 1.136 | -16.925 | 0.000 | 0.000 | 3.691 | 1.087 | 12.213 | 11.137 | 0.000 | 0.618 | 0.000 | 0.000 | -5.042 | 0.000 | -7.443 | -0.472 |
F3 SW APARTMENT | 3.828 | -20.654 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 16.994 | 0.000 | 1.104 | 1.190 | 0.000 | -8.464 | 0.000 | -10.990 | -0.000 |
F3 NW APARTMENT | 5.856 | -16.749 | 0.000 | 0.000 | 3.736 | 1.087 | 12.213 | 10.212 | 0.000 | 1.096 | 1.469 | 0.000 | -8.672 | 0.000 | -10.247 | -0.000 |
F3 SE APARTMENT | 3.630 | -20.913 | 0.000 | 0.000 | 3.698 | 1.087 | 12.213 | 16.798 | 0.000 | 1.102 | 1.688 | 0.000 | -8.302 | 0.000 | -10.999 | -0.000 |
F3 NE APARTMENT | 5.657 | -16.787 | 0.000 | 0.000 | 3.747 | 1.087 | 12.213 | 9.913 | 0.000 | 1.095 | 1.606 | 0.000 | -8.352 | 0.000 | -10.179 | -0.000 |
F3 N1 APARTMENT | 2.288 | -13.592 | 0.000 | 0.000 | 3.741 | 1.087 | 12.213 | 4.026 | 0.000 | 0.759 | 2.503 | 0.000 | -5.440 | 0.000 | -7.585 | -0.000 |
F3 N2 APARTMENT | 2.290 | -13.591 | 0.000 | 0.000 | 3.742 | 1.087 | 12.213 | 4.026 | 0.000 | 0.759 | 2.489 | 0.000 | -5.436 | 0.000 | -7.579 | -0.000 |
F3 S1 APARTMENT | 1.168 | -18.045 | 0.000 | 0.000 | 3.680 | 1.087 | 12.213 | 10.907 | 0.000 | 0.764 | 1.797 | 0.000 | -5.153 | 0.000 | -8.417 | -0.000 |
F3 S2 APARTMENT | 1.167 | -18.075 | 0.000 | 0.000 | 3.680 | 1.087 | 12.213 | 10.905 | 0.000 | 0.764 | 1.837 | 0.000 | -5.153 | 0.000 | -8.423 | -0.000 |
F4 SW APARTMENT | 4.194 | -20.771 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 16.758 | 0.000 | 1.214 | 1.896 | 0.000 | -8.536 | 0.000 | -11.747 | -0.000 |
F4 NW APARTMENT | 6.277 | -16.916 | 0.000 | 0.000 | 3.734 | 1.087 | 12.213 | 10.069 | 0.000 | 1.205 | 2.103 | 0.000 | -8.768 | 0.000 | -11.004 | -0.000 |
F4 SE APARTMENT | 4.061 | -20.828 | 0.000 | 0.000 | 3.700 | 1.087 | 12.213 | 16.585 | 0.000 | 1.211 | 2.057 | 0.000 | -8.355 | 0.000 | -11.729 | -0.000 |
F4 NE APARTMENT | 6.076 | -16.953 | 0.000 | 0.000 | 3.745 | 1.087 | 12.213 | 9.780 | 0.000 | 1.204 | 2.234 | 0.000 | -8.446 | 0.000 | -10.939 | -0.000 |
F4 N1 APARTMENT | 2.452 | -13.818 | 0.000 | 0.000 | 3.736 | 1.087 | 12.213 | 3.969 | 0.000 | 0.830 | 3.115 | 0.000 | -5.511 | 0.000 | -8.073 | -0.000 |
F4 N2 APARTMENT | 2.453 | -13.814 | 0.000 | 0.000 | 3.737 | 1.087 | 12.213 | 3.969 | 0.000 | 0.830 | 3.101 | 0.000 | -5.507 | 0.000 | -8.067 | -0.000 |
F4 S1 APARTMENT | 1.299 | -18.283 | 0.000 | 0.000 | 3.678 | 1.087 | 12.213 | 10.756 | 0.000 | 0.835 | 2.518 | 0.000 | -5.204 | 0.000 | -8.899 | -0.000 |
F4 S2 APARTMENT | 1.304 | -18.287 | 0.000 | 0.000 | 3.679 | 1.087 | 12.213 | 10.755 | 0.000 | 0.835 | 2.517 | 0.000 | -5.202 | 0.000 | -8.901 | -0.000 |
M SW APARTMENT | 4.528 | -20.985 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 16.570 | 0.000 | 1.302 | 2.714 | 0.000 | -8.593 | 0.000 | -12.531 | -0.000 |
M NW APARTMENT | 6.638 | -17.229 | 0.000 | 0.000 | 3.735 | 1.087 | 12.213 | 9.955 | 0.000 | 1.293 | 2.924 | 0.000 | -8.844 | 0.000 | -11.770 | -0.000 |
M SE APARTMENT | 4.404 | -21.016 | 0.000 | 0.000 | 3.702 | 1.087 | 12.213 | 16.409 | 0.000 | 1.299 | 2.818 | 0.000 | -8.408 | 0.000 | -12.507 | -0.000 |
M NE APARTMENT | 6.431 | -17.266 | 0.000 | 0.000 | 3.745 | 1.087 | 12.213 | 9.674 | 0.000 | 1.290 | 3.051 | 0.000 | -8.520 | 0.000 | -11.704 | -0.000 |
M N1 APARTMENT | 2.606 | -14.162 | 0.000 | 0.000 | 3.735 | 1.087 | 12.213 | 3.924 | 0.000 | 0.886 | 3.889 | 0.000 | -5.566 | 0.000 | -8.611 | -0.000 |
M N2 APARTMENT | 2.606 | -14.160 | 0.000 | 0.000 | 3.736 | 1.087 | 12.213 | 3.924 | 0.000 | 0.886 | 3.877 | 0.000 | -5.562 | 0.000 | -8.605 | -0.000 |
M S1 APARTMENT | 1.426 | -18.553 | 0.000 | 0.000 | 3.679 | 1.087 | 12.213 | 10.637 | 0.000 | 0.892 | 3.312 | 0.000 | -5.241 | 0.000 | -9.452 | -0.000 |
M S2 APARTMENT | 1.432 | -18.549 | 0.000 | 0.000 | 3.680 | 1.087 | 12.213 | 10.637 | 0.000 | 0.892 | 3.301 | 0.000 | -5.239 | 0.000 | -9.452 | -0.000 |
F6 SW APARTMENT | 5.109 | -20.228 | 0.000 | 0.000 | 3.703 | 1.087 | 12.213 | 16.452 | 0.000 | 1.375 | 1.998 | 0.000 | -8.582 | 0.000 | -13.127 | -0.000 |
F6 NW APARTMENT | 7.356 | -16.682 | 0.000 | 0.000 | 3.742 | 1.087 | 12.213 | 9.895 | 0.000 | 1.366 | 2.206 | 0.000 | -8.845 | 0.000 | -12.337 | -0.000 |
F6 SE APARTMENT | 4.975 | -20.250 | 0.000 | 0.000 | 3.710 | 1.087 | 12.213 | 16.299 | 0.000 | 1.372 | 2.091 | 0.000 | -8.397 | 0.000 | -13.101 | -0.000 |
F6 NE APARTMENT | 7.143 | -16.718 | 0.000 | 0.000 | 3.752 | 1.087 | 12.213 | 9.623 | 0.000 | 1.363 | 2.330 | 0.000 | -8.521 | 0.000 | -12.270 | -0.000 |
F6 N1 APARTMENT | 3.026 | -13.595 | 0.000 | 0.000 | 3.742 | 1.087 | 12.213 | 3.909 | 0.000 | 0.933 | 3.228 | 0.000 | -5.567 | 0.000 | -8.976 | -0.000 |
F6 N2 APARTMENT | 3.028 | -13.594 | 0.000 | 0.000 | 3.743 | 1.087 | 12.213 | 3.908 | 0.000 | 0.933 | 3.215 | 0.000 | -5.563 | 0.000 | -8.970 | -0.000 |
F6 S1 APARTMENT | 1.689 | -17.772 | 0.000 | 0.000 | 3.688 | 1.087 | 12.213 | 10.564 | 0.000 | 0.940 | 2.667 | 0.000 | -5.232 | 0.000 | -9.843 | -0.000 |
F6 S2 APARTMENT | 1.695 | -17.766 | 0.000 | 0.000 | 3.689 | 1.087 | 12.213 | 10.563 | 0.000 | 0.940 | 2.654 | 0.000 | -5.230 | 0.000 | -9.843 | -0.000 |
F7 SW APARTMENT | 5.597 | -19.823 | 0.000 | 0.000 | 3.709 | 1.087 | 12.213 | 16.342 | 0.000 | 1.439 | 1.690 | 0.000 | -8.586 | 0.000 | -13.667 | -0.000 |
F7 NW APARTMENT | 7.924 | -16.438 | 0.000 | 0.000 | 3.747 | 1.087 | 12.213 | 9.837 | 0.000 | 1.429 | 1.918 | 0.000 | -8.858 | 0.000 | -12.856 | -0.000 |
F7 SE APARTMENT | 5.455 | -19.845 | 0.000 | 0.000 | 3.716 | 1.087 | 12.213 | 16.196 | 0.000 | 1.435 | 1.783 | 0.000 | -8.400 | 0.000 | -13.640 | -0.000 |
F7 NE APARTMENT | 7.705 | -16.473 | 0.000 | 0.000 | 3.757 | 1.087 | 12.213 | 9.571 | 0.000 | 1.425 | 2.040 | 0.000 | -8.535 | 0.000 | -12.789 | -0.000 |
F7 N1 APARTMENT | 3.368 | -13.342 | 0.000 | 0.000 | 3.748 | 1.087 | 12.213 | 3.891 | 0.000 | 0.973 | 2.954 | 0.000 | -5.575 | 0.000 | -9.316 | -0.000 |
F7 N2 APARTMENT | 3.371 | -13.342 | 0.000 | 0.000 | 3.749 | 1.087 | 12.213 | 3.890 | 0.000 | 0.973 | 2.941 | 0.000 | -5.572 | 0.000 | -9.310 | -0.000 |
F7 S1 APARTMENT | 1.921 | -17.340 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 10.495 | 0.000 | 0.980 | 2.383 | 0.000 | -5.232 | 0.000 | -10.200 | -0.000 |
F7 S2 APARTMENT | 1.926 | -17.335 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 10.494 | 0.000 | 0.980 | 2.370 | 0.000 | -5.230 | 0.000 | -10.200 | -0.000 |
F8 SW APARTMENT | 6.061 | -19.609 | 0.000 | 0.000 | 3.714 | 1.087 | 12.213 | 16.242 | 0.000 | 1.500 | 1.557 | 0.000 | -8.594 | 0.000 | -14.170 | -0.000 |
F8 NW APARTMENT | 8.455 | -16.362 | 0.000 | 0.000 | 3.751 | 1.087 | 12.213 | 9.781 | 0.000 | 1.490 | 1.807 | 0.000 | -8.876 | 0.000 | -13.344 | -0.000 |
F8 SE APARTMENT | 5.913 | -19.631 | 0.000 | 0.000 | 3.721 | 1.087 | 12.213 | 16.101 | 0.000 | 1.497 | 1.651 | 0.000 | -8.408 | 0.000 | -14.143 | -0.000 |
F8 NE APARTMENT | 8.235 | -16.400 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 9.520 | 0.000 | 1.486 | 1.927 | 0.000 | -8.552 | 0.000 | -13.276 | -0.000 |
F8 N1 APARTMENT | 3.703 | -13.258 | 0.000 | 0.000 | 3.752 | 1.087 | 12.213 | 3.872 | 0.000 | 1.014 | 2.846 | 0.000 | -5.587 | 0.000 | -9.641 | -0.000 |
F8 N2 APARTMENT | 3.705 | -13.258 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 3.871 | 0.000 | 1.014 | 2.834 | 0.000 | -5.583 | 0.000 | -9.635 | -0.000 |
F8 S1 APARTMENT | 2.155 | -17.096 | 0.000 | 0.000 | 3.700 | 1.087 | 12.213 | 10.432 | 0.000 | 1.021 | 2.262 | 0.000 | -5.235 | 0.000 | -10.539 | -0.000 |
F8 S2 APARTMENT | 2.161 | -17.092 | 0.000 | 0.000 | 3.701 | 1.087 | 12.213 | 10.431 | 0.000 | 1.021 | 2.249 | 0.000 | -5.233 | 0.000 | -10.539 | -0.000 |
F9 SW APARTMENT | 6.835 | -19.847 | 0.000 | 0.000 | 3.718 | 1.087 | 12.213 | 16.152 | 0.000 | 1.565 | 1.491 | 0.000 | -8.596 | 0.000 | -14.617 | -0.000 |
F9 NW APARTMENT | 9.353 | -16.763 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 9.724 | 0.000 | 1.554 | 1.761 | 0.000 | -8.890 | 0.000 | -13.792 | -0.000 |
F9 SE APARTMENT | 6.661 | -19.861 | 0.000 | 0.000 | 3.725 | 1.087 | 12.213 | 16.016 | 0.000 | 1.562 | 1.602 | 0.000 | -8.411 | 0.000 | -14.593 | -0.001 |
F9 NE APARTMENT | 9.099 | -16.798 | 0.000 | 0.000 | 3.764 | 1.087 | 12.213 | 9.469 | 0.000 | 1.550 | 1.904 | 0.000 | -8.566 | 0.000 | -13.721 | -0.000 |
F9 N1 APARTMENT | 4.344 | -13.580 | 0.000 | 0.000 | 3.754 | 1.087 | 12.213 | 3.850 | 0.000 | 1.060 | 2.808 | 0.000 | -5.593 | 0.000 | -9.942 | -0.000 |
F9 N2 APARTMENT | 4.346 | -13.582 | 0.000 | 0.000 | 3.755 | 1.087 | 12.213 | 3.849 | 0.000 | 1.060 | 2.798 | 0.000 | -5.589 | 0.000 | -9.937 | -0.000 |
F9 S1 APARTMENT | 2.596 | -17.214 | 0.000 | 0.000 | 3.706 | 1.087 | 12.213 | 10.377 | 0.000 | 1.069 | 2.232 | 0.000 | -5.233 | 0.000 | -10.832 | -0.000 |
F9 S2 APARTMENT | 2.601 | -17.210 | 0.000 | 0.000 | 3.706 | 1.087 | 12.213 | 10.376 | 0.000 | 1.069 | 2.223 | 0.000 | -5.231 | 0.000 | -10.832 | -0.000 |
T SW APARTMENT | 10.317 | -21.223 | 0.000 | 0.000 | 3.740 | 1.087 | 12.213 | 15.807 | 0.000 | 1.610 | 0.001 | 0.000 | -8.251 | 0.000 | -15.043 | -0.256 |
T NW APARTMENT | 12.631 | -18.233 | 0.000 | 0.000 | 3.765 | 1.087 | 12.213 | 9.438 | 0.000 | 1.597 | 0.376 | 0.000 | -8.589 | 0.000 | -14.285 | -0.000 |
T SE APARTMENT | 10.043 | -21.009 | 0.000 | 0.000 | 3.746 | 1.087 | 12.213 | 15.690 | 0.000 | 1.609 | 0.001 | 0.000 | -8.090 | 0.000 | -15.058 | -0.230 |
T NE APARTMENT | 12.200 | -18.039 | 0.000 | 0.000 | 3.776 | 1.087 | 12.213 | 9.219 | 0.000 | 1.597 | 0.480 | 0.000 | -8.300 | 0.000 | -14.232 | -0.000 |
T N1 APARTMENT | 6.899 | -14.715 | 0.000 | 0.000 | 3.767 | 1.087 | 12.213 | 3.739 | 0.000 | 1.091 | 1.587 | 0.000 | -5.390 | 0.000 | -10.277 | -0.001 |
T N2 APARTMENT | 6.907 | -14.713 | 0.000 | 0.000 | 3.768 | 1.087 | 12.213 | 3.737 | 0.000 | 1.091 | 1.574 | 0.000 | -5.386 | 0.000 | -10.277 | -0.000 |
T S1 APARTMENT | 5.108 | -18.013 | 0.000 | 0.000 | 3.728 | 1.087 | 12.213 | 10.188 | 0.000 | 1.103 | 0.774 | 0.000 | -5.053 | 0.000 | -11.136 | -0.000 |
T S2 APARTMENT | 5.116 | -18.015 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 10.186 | 0.000 | 1.103 | 0.771 | 0.000 | -5.050 | 0.000 | -11.139 | -0.000 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 4.224 | 0.000 | 4.479 | 10.327 | 0.000 | -1.750 | 0.000 | -33.719 | -0.001 |
F2 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.936 | 0.000 | 0.070 | 0.000 | 0.000 | -1.078 | 0.000 | -0.979 | -16.389 |
F3 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.881 | 0.000 | 0.081 | 0.000 | 0.000 | -1.124 | 0.000 | -1.197 | -16.080 |
F4 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.847 | 0.000 | 0.087 | 0.000 | 0.000 | -1.146 | 0.000 | -1.354 | -15.873 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32.880 | 0.000 | 1.809 | 0.000 | 0.081 | 0.000 | 0.000 | -1.178 | 0.000 | -1.548 | -32.043 |
F6 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.813 | 0.000 | 0.101 | 0.000 | 0.000 | -1.155 | 0.000 | -1.566 | -15.633 |
F7 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.807 | 0.000 | 0.108 | 0.000 | 0.000 | -1.147 | 0.000 | -1.636 | -15.571 |
F8 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.796 | 0.000 | 0.112 | 0.000 | 0.000 | -1.147 | 0.000 | -1.708 | -15.494 |
F9 CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 0.000 | 1.784 | 0.000 | 0.112 | 0.000 | 0.000 | -1.148 | 0.000 | -1.773 | -15.415 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.440 | 8.151 | 1.707 | 0.000 | 0.067 | 0.000 | 0.000 | -1.127 | 0.000 | -1.914 | -23.325 |
Total Facility | 364.488 | -1328.730 | 0.000 | 0.000 | 295.244 | 296.560 | 982.450 | 844.481 | 0.000 | 90.228 | 150.429 | 0.000 | -560.301 | 0.000 | -870.961 | -263.896 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-15:15 | 0.00 | -2722.57 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 3048.79 | 0.00 | 194.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1086.01 |
G NW APARTMENT | 02-JUN-17:05 | 0.00 | -2423.06 | 0.00 | 0.00 | 141.83 | 87.56 | 588.62 | 2516.30 | 0.00 | 168.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1079.72 |
OFFICE | 30-AUG-13:00 | 0.00 | -3824.28 | 0.00 | 0.00 | 65.20 | 2345.88 | 588.62 | 2506.12 | 0.00 | 229.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1911.18 |
G NE APARTMENT | 10-JUL-17:15 | 0.00 | -1858.89 | 0.00 | 0.00 | 141.83 | 87.56 | 588.62 | 961.42 | 0.00 | 252.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -172.81 |
G N1 APARTMENT | 04-JUN-17:20 | 0.00 | -1351.73 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 791.40 | 0.00 | 82.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -340.39 |
G N2 APARTMENT | 04-JUN-17:20 | 0.00 | -1338.38 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 791.71 | 0.00 | 82.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -354.05 |
G S1 APARTMENT | 30-AUG-15:00 | 0.00 | -1747.88 | 0.00 | 0.00 | 40.48 | 22.70 | 400.26 | 1377.82 | 0.00 | 115.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -209.08 |
G S2 APARTMENT | 30-AUG-14:45 | 0.00 | -1813.45 | 0.00 | 0.00 | 40.44 | 22.70 | 400.26 | 1523.40 | 0.00 | 110.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -284.01 |
F2 SW APARTMENT | 30-AUG-16:10 | 0.00 | -3315.26 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2559.57 | 0.00 | 273.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -255.93 |
F2 NW APARTMENT | 02-JUN-17:30 | 0.00 | -2977.10 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2415.88 | 0.00 | 221.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.26 |
F2 SE APARTMENT | 30-AUG-13:00 | 0.00 | -3147.55 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2426.49 | 0.00 | 329.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.55 |
F2 NE APARTMENT | 10-JUL-16:38 | 0.00 | -2371.36 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1025.10 | 0.00 | 395.93 | 212.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N1 APARTMENT | 04-JUN-17:20 | 0.00 | -1716.16 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 773.96 | 0.00 | 118.66 | 5.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 N2 APARTMENT | 04-JUN-17:20 | 0.00 | -1705.79 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 774.15 | 0.00 | 118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5.02 |
F2 S1 APARTMENT | 30-AUG-15:00 | 0.00 | -2188.10 | 0.00 | 0.00 | 40.44 | 22.70 | 400.26 | 1346.66 | 0.00 | 165.43 | 212.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 S2 APARTMENT | 30-AUG-15:00 | 0.00 | -2209.58 | 0.00 | 0.00 | 40.49 | 22.70 | 400.26 | 1346.80 | 0.00 | 165.76 | 233.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3328.88 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2936.04 | 0.00 | 329.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -502.04 |
F3 NW APARTMENT | 02-JUN-17:30 | 0.00 | -3016.27 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2392.55 | 0.00 | 261.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -455.87 |
F3 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3020.57 | 0.00 | 0.00 | 40.54 | 12.97 | 382.60 | 2251.99 | 0.00 | 329.98 | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2433.20 | 0.00 | 0.00 | 84.63 | 64.86 | 588.62 | 986.93 | 0.00 | 477.24 | 230.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N1 APARTMENT | 04-JUN-17:20 | 0.00 | -1763.30 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 768.23 | 0.00 | 140.19 | 36.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 N2 APARTMENT | 04-JUN-17:20 | 0.00 | -1753.20 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 768.42 | 0.00 | 140.19 | 26.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2315.54 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2475.11 | 0.00 | 171.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -773.19 |
F3 S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2322.95 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2474.97 | 0.00 | 171.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -765.64 |
F4 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3351.07 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2908.12 | 0.00 | 367.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -489.94 |
F4 NW APARTMENT | 02-JUN-17:30 | 0.00 | -3040.76 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2375.87 | 0.00 | 291.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -444.80 |
F4 SE APARTMENT | 30-AUG-13:30 | 0.00 | -3038.49 | 0.00 | 0.00 | 40.51 | 12.97 | 382.60 | 2233.96 | 0.00 | 367.73 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2465.99 | 0.00 | 0.00 | 84.47 | 64.86 | 588.62 | 982.46 | 0.00 | 530.80 | 214.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N1 APARTMENT | 04-JUN-17:20 | 0.00 | -1787.17 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 764.13 | 0.00 | 156.36 | 48.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 N2 APARTMENT | 04-JUN-17:20 | 0.00 | -1777.33 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 764.31 | 0.00 | 156.36 | 38.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2348.58 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2460.21 | 0.00 | 177.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -731.73 |
F4 S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2354.78 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2460.09 | 0.00 | 177.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -725.41 |
M SW APARTMENT | 30-AUG-15:15 | 0.00 | -3391.84 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2885.45 | 0.00 | 398.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -457.50 |
M NW APARTMENT | 02-JUN-17:30 | 0.00 | -3081.43 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2362.24 | 0.00 | 316.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -415.04 |
M SE APARTMENT | 30-AUG-13:15 | 0.00 | -3112.97 | 0.00 | 0.00 | 40.57 | 12.97 | 382.60 | 2296.05 | 0.00 | 433.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -52.38 |
M NE APARTMENT | 10-JUL-17:00 | 0.00 | -2516.45 | 0.00 | 0.00 | 84.35 | 64.86 | 588.62 | 978.20 | 0.00 | 574.45 | 225.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 10-JUL-17:15 | 0.00 | -1828.01 | 0.00 | 0.00 | 140.84 | 87.56 | 588.62 | 622.91 | 0.00 | 308.02 | 80.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 10-JUL-17:10 | 0.00 | -1818.44 | 0.00 | 0.00 | 140.81 | 87.56 | 588.62 | 622.98 | 0.00 | 308.07 | 70.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2376.98 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2447.48 | 0.00 | 182.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -695.66 |
M S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2382.90 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2447.36 | 0.00 | 182.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -689.63 |
F6 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3372.60 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2868.24 | 0.00 | 425.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -485.99 |
F6 NW APARTMENT | 02-JUN-17:30 | 0.00 | -3059.90 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 2352.21 | 0.00 | 337.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -447.46 |
F6 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3103.57 | 0.00 | 0.00 | 40.60 | 12.97 | 382.60 | 2285.02 | 0.00 | 462.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -79.97 |
F6 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2501.33 | 0.00 | 0.00 | 84.22 | 64.86 | 588.62 | 976.04 | 0.00 | 611.20 | 176.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N1 APARTMENT | 10-JUL-17:00 | 0.00 | -1810.59 | 0.00 | 0.00 | 84.12 | 64.86 | 588.62 | 642.99 | 0.00 | 367.86 | 62.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 N2 APARTMENT | 10-JUL-17:00 | 0.00 | -1801.21 | 0.00 | 0.00 | 84.10 | 64.86 | 588.62 | 643.06 | 0.00 | 367.71 | 52.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2338.32 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2437.43 | 0.00 | 187.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.35 |
F6 S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2344.30 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2437.31 | 0.00 | 187.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -722.25 |
F7 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3373.61 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2852.92 | 0.00 | 448.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -492.89 |
F7 NW APARTMENT | 10-JUL-16:30 | 0.00 | -3059.46 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2050.00 | 0.00 | 621.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -350.21 |
F7 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3115.13 | 0.00 | 0.00 | 40.62 | 12.97 | 382.60 | 2275.01 | 0.00 | 488.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -84.15 |
F7 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2511.54 | 0.00 | 0.00 | 84.14 | 64.86 | 588.62 | 973.68 | 0.00 | 643.67 | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N1 APARTMENT | 10-JUL-17:00 | 0.00 | -1814.33 | 0.00 | 0.00 | 84.07 | 64.86 | 588.62 | 641.33 | 0.00 | 387.67 | 47.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 N2 APARTMENT | 10-JUL-17:00 | 0.00 | -1805.06 | 0.00 | 0.00 | 84.05 | 64.86 | 588.62 | 641.39 | 0.00 | 387.51 | 38.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 S1 APARTMENT | 22-OCT-13:00 | 0.00 | -2317.27 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2428.11 | 0.00 | 190.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -743.38 |
F7 S2 APARTMENT | 22-OCT-13:00 | 0.00 | -2323.30 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2427.99 | 0.00 | 190.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -737.23 |
F8 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3385.24 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2839.15 | 0.00 | 469.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -488.24 |
F8 NW APARTMENT | 10-JUL-16:30 | 0.00 | -3078.74 | 0.00 | 0.00 | 84.75 | 64.86 | 588.62 | 2038.79 | 0.00 | 649.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -348.24 |
F8 SE APARTMENT | 30-AUG-13:15 | 0.00 | -3136.97 | 0.00 | 0.00 | 40.66 | 12.97 | 382.60 | 2265.94 | 0.00 | 511.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.50 |
F8 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2531.67 | 0.00 | 0.00 | 84.05 | 64.86 | 588.62 | 971.00 | 0.00 | 672.50 | 150.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N1 APARTMENT | 06-AUG-18:15 | 0.00 | -1967.41 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 211.38 | 0.00 | 741.56 | 221.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 N2 APARTMENT | 06-AUG-18:15 | 0.00 | -1961.06 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 211.51 | 0.00 | 741.57 | 214.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S1 APARTMENT | 30-AUG-14:30 | 0.00 | -2315.30 | 0.00 | 0.00 | 40.61 | 22.70 | 400.26 | 1579.42 | 0.00 | 256.24 | 16.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 S2 APARTMENT | 30-AUG-14:30 | 0.00 | -2320.92 | 0.00 | 0.00 | 40.60 | 22.70 | 400.26 | 1579.20 | 0.00 | 256.19 | 21.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 SW APARTMENT | 30-AUG-15:15 | 0.00 | -3472.40 | 0.00 | 0.00 | 48.90 | 45.40 | 470.89 | 2824.30 | 0.00 | 487.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -405.05 |
F9 NW APARTMENT | 10-JUL-16:30 | 0.00 | -3200.03 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 2025.87 | 0.00 | 676.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -241.07 |
F9 SE APARTMENT | 30-AUG-13:00 | 0.00 | -3228.30 | 0.00 | 0.00 | 40.76 | 12.97 | 388.49 | 2320.00 | 0.00 | 575.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -109.55 |
F9 NE APARTMENT | 10-JUL-17:00 | 0.00 | -2608.76 | 0.00 | 0.00 | 83.83 | 64.86 | 588.62 | 964.74 | 0.00 | 696.75 | 209.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N1 APARTMENT | 06-AUG-18:15 | 0.00 | -2038.92 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 208.37 | 0.00 | 763.46 | 274.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 N2 APARTMENT | 06-AUG-18:15 | 0.00 | -2032.74 | 0.00 | 0.00 | 141.82 | 103.77 | 547.42 | 208.49 | 0.00 | 763.46 | 267.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S1 APARTMENT | 30-AUG-14:15 | 0.00 | -2394.93 | 0.00 | 0.00 | 40.69 | 22.70 | 400.26 | 1653.61 | 0.00 | 255.98 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 S2 APARTMENT | 30-AUG-14:15 | 0.00 | -2402.16 | 0.00 | 0.00 | 40.69 | 22.70 | 400.26 | 1653.39 | 0.00 | 255.95 | 29.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 30-AUG-14:45 | 0.00 | -4189.05 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 3024.44 | 0.00 | 479.17 | 221.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 10-JUL-16:30 | 0.00 | -3796.94 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 1979.76 | 0.00 | 701.45 | 377.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 30-AUG-13:00 | 0.00 | -3920.19 | 0.00 | 0.00 | 40.76 | 12.97 | 388.49 | 2268.67 | 0.00 | 596.40 | 612.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 05-JUN-14:00 | 0.00 | -3260.80 | 0.00 | 0.00 | 40.76 | 12.97 | 382.60 | 1320.22 | 0.00 | 721.85 | 782.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 10-JUL-16:30 | 0.00 | -2505.79 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 652.53 | 0.00 | 423.08 | 691.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 26-JUN-13:38 | 0.00 | -2507.06 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 357.99 | 0.00 | 986.69 | 726.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 30-AUG-13:00 | 0.00 | -3215.37 | 0.00 | 0.00 | 40.76 | 12.97 | 388.49 | 1885.19 | 0.00 | 359.73 | 528.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 30-AUG-13:00 | 0.00 | -3224.79 | 0.00 | 0.00 | 40.76 | 12.97 | 388.49 | 1884.97 | 0.00 | 359.73 | 537.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-16:30 | 0.00 | -187383.05 | 0.00 | 0.00 | 6686.73 | 11327.17 | 47312.53 | 89532.25 | 0.00 | 39514.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6990.52 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 31-JAN-04:00 | 2556.03 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1327.06 | 0.00 | -1459.09 | -189.72 |
G NW APARTMENT | 31-JAN-04:00 | 2582.51 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1339.51 | 0.00 | -1459.09 | -203.74 |
OFFICE | 06-JAN-22:00 | 2416.57 | 0.00 | 0.00 | 0.00 | 0.00 | 469.18 | 194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1213.72 | 0.00 | -1480.59 | -385.68 |
G NE APARTMENT | 31-JAN-04:00 | 2592.36 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1349.74 | 0.00 | -1459.09 | -203.37 |
G N1 APARTMENT | 31-JAN-04:00 | 1528.43 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.89 | 0.00 | -880.09 | -245.29 |
G N2 APARTMENT | 31-JAN-04:00 | 1528.90 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -822.87 | 0.00 | -880.09 | -245.77 |
G S1 APARTMENT | 31-JAN-04:00 | 1469.02 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -811.35 | 0.00 | -880.08 | -197.42 |
G S2 APARTMENT | 31-JAN-04:00 | 1454.56 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -811.74 | 0.00 | -880.08 | -182.57 |
F2 SW APARTMENT | 31-JAN-04:00 | 3067.31 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1374.85 | 0.00 | -2098.17 | -14.11 |
F2 NW APARTMENT | 31-JAN-04:00 | 3169.64 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1395.11 | 0.00 | -2098.17 | -96.18 |
F2 SE APARTMENT | 31-JAN-04:00 | 3012.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 60.47 | 0.00 | -1394.33 | 0.00 | -2098.17 | 0.00 |
F2 NE APARTMENT | 31-JAN-04:00 | 3188.41 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1411.43 | 0.00 | -2098.17 | -98.64 |
F2 N1 APARTMENT | 31-JAN-04:00 | 1776.32 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -863.52 | 0.00 | -1265.56 | -67.07 |
F2 N2 APARTMENT | 31-JAN-04:00 | 1777.43 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -863.50 | 0.00 | -1265.56 | -68.21 |
F2 S1 APARTMENT | 31-JAN-04:00 | 1657.04 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 29.25 | 0.00 | -840.56 | 0.00 | -1265.56 | 0.00 |
F2 S2 APARTMENT | 31-JAN-04:00 | 1652.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 33.73 | 0.00 | -840.69 | 0.00 | -1265.56 | 0.00 |
F3 SW APARTMENT | 31-JAN-04:00 | 3360.70 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 100.33 | 0.00 | -1395.67 | 0.00 | -2485.20 | 0.00 |
F3 NW APARTMENT | 31-JAN-04:00 | 3485.41 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1419.06 | 0.00 | -2485.20 | -0.98 |
F3 SE APARTMENT | 31-JAN-04:00 | 3376.02 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 104.36 | 0.00 | -1415.01 | 0.00 | -2485.20 | 0.00 |
F3 NE APARTMENT | 31-JAN-04:00 | 3508.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1437.95 | 0.00 | -2485.20 | -4.69 |
F3 N1 APARTMENT | 31-JAN-04:00 | 1930.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 28.61 | 0.00 | -880.41 | 0.00 | -1499.01 | 0.00 |
F3 N2 APARTMENT | 31-JAN-04:00 | 1932.49 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 27.06 | 0.00 | -880.37 | 0.00 | -1499.01 | 0.00 |
F3 S1 APARTMENT | 31-JAN-04:00 | 1789.39 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 143.90 | 0.00 | -854.11 | 0.00 | -1499.01 | 0.00 |
F3 S2 APARTMENT | 31-JAN-04:00 | 1790.03 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 143.24 | 0.00 | -854.09 | 0.00 | -1499.01 | 0.00 |
F4 SW APARTMENT | 31-JAN-04:00 | 3640.58 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 126.44 | 0.00 | -1407.83 | 0.00 | -2779.03 | 0.00 |
F4 NW APARTMENT | 31-JAN-04:00 | 3770.48 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 22.16 | 0.00 | -1433.45 | 0.00 | -2779.03 | 0.00 |
F4 SE APARTMENT | 31-JAN-04:00 | 3668.68 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 118.79 | 0.00 | -1428.27 | 0.00 | -2779.03 | 0.00 |
F4 NE APARTMENT | 31-JAN-04:00 | 3794.79 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 18.31 | 0.00 | -1453.91 | 0.00 | -2779.03 | 0.00 |
F4 N1 APARTMENT | 31-JAN-04:00 | 2091.81 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 55.11 | 0.00 | -890.51 | 0.00 | -1676.24 | 0.00 |
F4 N2 APARTMENT | 31-JAN-04:00 | 2093.50 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 53.37 | 0.00 | -890.46 | 0.00 | -1676.24 | 0.00 |
F4 S1 APARTMENT | 31-JAN-04:00 | 1947.79 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 170.45 | 0.00 | -861.84 | 0.00 | -1676.24 | 0.00 |
F4 S2 APARTMENT | 31-JAN-04:00 | 1949.65 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 168.53 | 0.00 | -861.77 | 0.00 | -1676.24 | 0.00 |
M SW APARTMENT | 31-JAN-04:00 | 3870.73 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 148.16 | 0.00 | -1417.24 | 0.00 | -3021.48 | 0.00 |
M NW APARTMENT | 31-JAN-04:00 | 3997.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 48.27 | 0.00 | -1444.60 | 0.00 | -3021.48 | 0.00 |
M SE APARTMENT | 31-JAN-04:00 | 3900.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 139.45 | 0.00 | -1438.75 | 0.00 | -3021.48 | 0.00 |
M NE APARTMENT | 31-JAN-04:00 | 4022.76 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 45.08 | 0.00 | -1466.19 | 0.00 | -3021.48 | 0.00 |
M N1 APARTMENT | 31-JAN-04:00 | 2220.26 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 80.61 | 0.00 | -898.22 | 0.00 | -1822.48 | 0.00 |
M N2 APARTMENT | 31-JAN-04:00 | 2221.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 78.96 | 0.00 | -898.17 | 0.00 | -1822.48 | 0.00 |
M S1 APARTMENT | 31-JAN-04:00 | 2080.28 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 190.10 | 0.00 | -867.73 | 0.00 | -1822.48 | 0.00 |
M S2 APARTMENT | 31-JAN-04:00 | 2082.12 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 188.20 | 0.00 | -867.67 | 0.00 | -1822.48 | 0.00 |
F6 SW APARTMENT | 31-JAN-04:00 | 4125.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 107.53 | 0.00 | -1422.58 | 0.00 | -3230.64 | 0.00 |
F6 NW APARTMENT | 31-JAN-04:00 | 4250.16 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 12.08 | 0.00 | -1451.43 | 0.00 | -3230.64 | 0.00 |
F6 SE APARTMENT | 31-JAN-04:00 | 4156.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 99.20 | 0.00 | -1444.92 | 0.00 | -3230.64 | 0.00 |
F6 NE APARTMENT | 31-JAN-04:00 | 4274.65 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 10.03 | 0.00 | -1473.87 | 0.00 | -3230.64 | 0.00 |
F6 N1 APARTMENT | 31-JAN-04:00 | 2385.74 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 45.85 | 0.00 | -902.79 | 0.00 | -1948.64 | 0.00 |
F6 N2 APARTMENT | 31-JAN-04:00 | 2387.14 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 44.41 | 0.00 | -902.75 | 0.00 | -1948.64 | 0.00 |
F6 S1 APARTMENT | 31-JAN-04:00 | 2244.17 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 155.51 | 0.00 | -870.88 | 0.00 | -1948.64 | 0.00 |
F6 S2 APARTMENT | 31-JAN-04:00 | 2245.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 153.64 | 0.00 | -870.82 | 0.00 | -1948.64 | 0.00 |
F7 SW APARTMENT | 31-JAN-04:00 | 4339.82 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 84.07 | 0.00 | -1427.57 | 0.00 | -3416.16 | 0.00 |
F7 NW APARTMENT | 31-JAN-04:00 | 4459.18 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.64 | 0.00 | -3416.16 | -5.22 |
F7 SE APARTMENT | 31-JAN-04:00 | 4370.46 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 76.45 | 0.00 | -1450.57 | 0.00 | -3416.16 | 0.00 |
F7 NE APARTMENT | 31-JAN-04:00 | 4483.24 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1480.76 | 0.00 | -3416.16 | -6.15 |
F7 N1 APARTMENT | 31-JAN-04:00 | 2520.31 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 27.28 | 0.00 | -906.88 | 0.00 | -2060.54 | 0.00 |
F7 N2 APARTMENT | 31-JAN-04:00 | 2521.52 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 26.04 | 0.00 | -906.85 | 0.00 | -2060.54 | 0.00 |
F7 S1 APARTMENT | 31-JAN-04:00 | 2380.47 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 134.06 | 0.00 | -873.82 | 0.00 | -2060.54 | 0.00 |
F7 S2 APARTMENT | 31-JAN-04:00 | 2382.25 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 132.23 | 0.00 | -873.77 | 0.00 | -2060.54 | 0.00 |
F8 SW APARTMENT | 31-JAN-04:00 | 4538.05 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 57.76 | 0.00 | -1431.75 | 0.00 | -3583.89 | 0.00 |
F8 NW APARTMENT | 31-JAN-04:00 | 4650.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1462.90 | 0.00 | -3583.89 | -23.73 |
F8 SE APARTMENT | 31-JAN-04:00 | 4568.49 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 50.88 | 0.00 | -1455.31 | 0.00 | -3583.89 | 0.00 |
F8 NE APARTMENT | 31-JAN-04:00 | 4674.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1486.57 | 0.00 | -3583.89 | -24.05 |
F8 N1 APARTMENT | 31-JAN-04:00 | 2644.72 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 | -910.32 | 0.00 | -2161.71 | 0.00 |
F8 N2 APARTMENT | 31-JAN-04:00 | 2645.84 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 6.32 | 0.00 | -910.29 | 0.00 | -2161.71 | 0.00 |
F8 S1 APARTMENT | 31-JAN-04:00 | 2508.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 109.15 | 0.00 | -876.25 | 0.00 | -2161.71 | 0.00 |
F8 S2 APARTMENT | 31-JAN-04:00 | 2510.74 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 107.34 | 0.00 | -876.20 | 0.00 | -2161.71 | 0.00 |
F9 SW APARTMENT | 31-JAN-04:00 | 4824.75 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1431.81 | 0.00 | -3737.67 | -75.10 |
F9 NW APARTMENT | 31-JAN-04:00 | 4920.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1464.17 | 0.00 | -3737.67 | -138.00 |
F9 SE APARTMENT | 31-JAN-04:00 | 4854.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1455.83 | 0.00 | -3737.67 | -80.34 |
F9 NE APARTMENT | 31-JAN-04:00 | 4944.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1488.24 | 0.00 | -3737.68 | -138.11 |
F9 N1 APARTMENT | 31-JAN-04:00 | 2843.39 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -911.05 | 0.00 | -2254.47 | -97.70 |
F9 N2 APARTMENT | 31-JAN-04:00 | 2844.47 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -911.02 | 0.00 | -2254.47 | -98.81 |
F9 S1 APARTMENT | 31-JAN-04:00 | 2723.88 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.84 | 0.00 | -2254.47 | -13.40 |
F9 S2 APARTMENT | 31-JAN-04:00 | 2725.58 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -875.80 | 0.00 | -2254.47 | -15.15 |
T SW APARTMENT | 31-JAN-04:00 | 5623.28 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1401.72 | 0.00 | -3879.86 | -761.54 |
T NW APARTMENT | 31-JAN-04:00 | 5682.56 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1433.88 | 0.00 | -3879.86 | -788.65 |
T SE APARTMENT | 31-JAN-04:00 | 5646.58 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1425.67 | 0.00 | -3879.86 | -760.88 |
T NE APARTMENT | 31-JAN-04:00 | 5704.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1457.83 | 0.00 | -3879.86 | -786.35 |
T N1 APARTMENT | 31-JAN-04:00 | 3566.64 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -890.35 | 0.00 | -2340.32 | -755.81 |
T N2 APARTMENT | 31-JAN-04:00 | 3567.37 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -890.33 | 0.00 | -2340.32 | -756.55 |
T S1 APARTMENT | 31-JAN-04:00 | 3493.94 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.18 | 0.00 | -2340.32 | -715.26 |
T S2 APARTMENT | 31-JAN-04:00 | 3494.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.16 | 0.00 | -2340.32 | -716.28 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F2 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F3 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F4 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F6 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F7 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F8 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
F9 CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JAN-04:00 | 253628.67 | 0.00 | 0.00 | 0.00 | 14983.98 | 6715.87 | 17923.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93978.02 | 0.00 | -195290.74 | -3983.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Sec1.1A-General InformationData | |
Weather File | Memphis International Ap TN USA TMY3 WMO#=723340 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 7836.48 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.50 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F2 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F3 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F4 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F6 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F7 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F8 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
F9 S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F2 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F3 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F4 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F6 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F7 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F8 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
F9 CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 7836.48 | 7059.89 | 776.58 |
Data | |
Number of hours heating loads not met | 83.50 |
Number of hours cooling loads not met | 101.00 |
Number of hours not met | 184.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 296.56 | 14401.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.95 | 10364.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 135.05 | 0.00 | 473.91 | 294826.64 | 0.00 | 0.00 |
Space Cooling | 674.94 | 78343.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 71.11 | 2349.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 32.61 | 3357.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 599.19 | 19000.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1002.57 | 75821.85 | 0.00 | 0.00 |
Receptacle Equipment | 1137.32 | 51749.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 3145.91 | 1476.48 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1137.32 | 3145.91 |
Natural Gas | 0.00 | 1476.48 |
Additional | 0.00 | 0.00 |
Total | 1137.32 | 4622.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.84 |
Space Heating | 17.23 |
Space Cooling | 86.13 |
Fans-Interior | 76.46 |
Service Water Heating | 0.00 |
Receptacle Equipment | 145.13 |
Miscellaneous | 38.65 |
Subtotal | 401.44 |
Natural Gas [MJ/m2] | |
Space Heating | 60.47 |
Service Water Heating | 127.94 |
Miscellaneous | -0.00 |
Subtotal | 188.41 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.42 |
Space Heating | 13.17 |
Space Cooling | 14.60 |
Fans-Interior | 12.96 |
Service Water Heating | 21.69 |
Receptacle Equipment | 24.60 |
Miscellaneous | 6.55 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.210212 |
G NW APARTMENT DIRECT AIR | 0.206443 |
OFFICE DIRECT AIR | 0.315353 |
G NE APARTMENT DIRECT AIR | 0.161511 |
G N1 APARTMENT DIRECT AIR | 0.114578 |
G N2 APARTMENT DIRECT AIR | 0.113403 |
G S1 APARTMENT DIRECT AIR | 0.121467 |
G S2 APARTMENT DIRECT AIR | 0.127277 |
F2 SW APARTMENT DIRECT AIR | 0.261267 |
F2 NW APARTMENT DIRECT AIR | 0.255606 |
F2 SE APARTMENT DIRECT AIR | 0.244527 |
F2 NE APARTMENT DIRECT AIR | 0.205664 |
F2 N1 APARTMENT DIRECT AIR | 0.145607 |
F2 N2 APARTMENT DIRECT AIR | 0.144650 |
F2 S1 APARTMENT DIRECT AIR | 0.155296 |
F2 S2 APARTMENT DIRECT AIR | 0.157280 |
F3 SW APARTMENT DIRECT AIR | 0.262875 |
F3 NW APARTMENT DIRECT AIR | 0.257763 |
F3 SE APARTMENT DIRECT AIR | 0.227116 |
F3 NE APARTMENT DIRECT AIR | 0.208829 |
F3 N1 APARTMENT DIRECT AIR | 0.148623 |
F3 N2 APARTMENT DIRECT AIR | 0.147683 |
F3 S1 APARTMENT DIRECT AIR | 0.158161 |
F3 S2 APARTMENT DIRECT AIR | 0.158982 |
F4 SW APARTMENT DIRECT AIR | 0.264584 |
F4 NW APARTMENT DIRECT AIR | 0.259611 |
F4 SE APARTMENT DIRECT AIR | 0.226903 |
F4 NE APARTMENT DIRECT AIR | 0.210601 |
F4 N1 APARTMENT DIRECT AIR | 0.150604 |
F4 N2 APARTMENT DIRECT AIR | 0.149676 |
F4 S1 APARTMENT DIRECT AIR | 0.159838 |
F4 S2 APARTMENT DIRECT AIR | 0.160487 |
M SW APARTMENT DIRECT AIR | 0.268064 |
M NW APARTMENT DIRECT AIR | 0.263254 |
M SE APARTMENT DIRECT AIR | 0.230223 |
M NE APARTMENT DIRECT AIR | 0.214150 |
M N1 APARTMENT DIRECT AIR | 0.154223 |
M N2 APARTMENT DIRECT AIR | 0.153304 |
M S1 APARTMENT DIRECT AIR | 0.163166 |
M S2 APARTMENT DIRECT AIR | 0.163790 |
F6 SW APARTMENT DIRECT AIR | 0.265923 |
F6 NW APARTMENT DIRECT AIR | 0.261115 |
F6 SE APARTMENT DIRECT AIR | 0.228554 |
F6 NE APARTMENT DIRECT AIR | 0.212010 |
F6 N1 APARTMENT DIRECT AIR | 0.152292 |
F6 N2 APARTMENT DIRECT AIR | 0.151386 |
F6 S1 APARTMENT DIRECT AIR | 0.161064 |
F6 S2 APARTMENT DIRECT AIR | 0.161683 |
F7 SW APARTMENT DIRECT AIR | 0.265738 |
F7 NW APARTMENT DIRECT AIR | 0.261010 |
F7 SE APARTMENT DIRECT AIR | 0.228777 |
F7 NE APARTMENT DIRECT AIR | 0.211883 |
F7 N1 APARTMENT DIRECT AIR | 0.152284 |
F7 N2 APARTMENT DIRECT AIR | 0.151387 |
F7 S1 APARTMENT DIRECT AIR | 0.160872 |
F7 S2 APARTMENT DIRECT AIR | 0.161472 |
F8 SW APARTMENT DIRECT AIR | 0.266914 |
F8 NW APARTMENT DIRECT AIR | 0.262262 |
F8 SE APARTMENT DIRECT AIR | 0.230241 |
F8 NE APARTMENT DIRECT AIR | 0.213089 |
F8 N1 APARTMENT DIRECT AIR | 0.153612 |
F8 N2 APARTMENT DIRECT AIR | 0.152725 |
F8 S1 APARTMENT DIRECT AIR | 0.161973 |
F8 S2 APARTMENT DIRECT AIR | 0.162555 |
F9 SW APARTMENT DIRECT AIR | 0.277545 |
F9 NW APARTMENT DIRECT AIR | 0.273047 |
F9 SE APARTMENT DIRECT AIR | 0.238873 |
F9 NE APARTMENT DIRECT AIR | 0.218881 |
F9 N1 APARTMENT DIRECT AIR | 0.163340 |
F9 N2 APARTMENT DIRECT AIR | 0.162447 |
F9 S1 APARTMENT DIRECT AIR | 0.169425 |
F9 S2 APARTMENT DIRECT AIR | 0.170035 |
T SW APARTMENT DIRECT AIR | 0.348908 |
T NW APARTMENT DIRECT AIR | 0.337357 |
T SE APARTMENT DIRECT AIR | 0.311321 |
T NE APARTMENT DIRECT AIR | 0.278258 |
T N1 APARTMENT DIRECT AIR | 0.215344 |
T N2 APARTMENT DIRECT AIR | 0.215292 |
T S1 APARTMENT DIRECT AIR | 0.246821 |
T S2 APARTMENT DIRECT AIR | 0.247341 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW MAIN BRANCH | 0.210212 |
AIRLOOP G NW MAIN BRANCH | 0.206443 |
AIRLOOP OFFICE MAIN BRANCH | 0.315353 |
AIRLOOP G NE MAIN BRANCH | 0.161511 |
AIRLOOP G N1 MAIN BRANCH | 0.114578 |
AIRLOOP G N2 MAIN BRANCH | 0.113403 |
AIRLOOP G S1 MAIN BRANCH | 0.121467 |
AIRLOOP G S2 MAIN BRANCH | 0.127277 |
AIRLOOP F2 SW MAIN BRANCH | 0.261267 |
AIRLOOP F2 NW MAIN BRANCH | 0.255606 |
AIRLOOP F2 SE MAIN BRANCH | 0.244527 |
AIRLOOP F2 NE MAIN BRANCH | 0.205664 |
AIRLOOP F2 N1 MAIN BRANCH | 0.145607 |
AIRLOOP F2 N2 MAIN BRANCH | 0.144650 |
AIRLOOP F2 S1 MAIN BRANCH | 0.155296 |
AIRLOOP F2 S2 MAIN BRANCH | 0.157280 |
AIRLOOP F3 SW MAIN BRANCH | 0.262875 |
AIRLOOP F3 NW MAIN BRANCH | 0.257763 |
AIRLOOP F3 SE MAIN BRANCH | 0.227116 |
AIRLOOP F3 NE MAIN BRANCH | 0.208829 |
AIRLOOP F3 N1 MAIN BRANCH | 0.148623 |
AIRLOOP F3 N2 MAIN BRANCH | 0.147683 |
AIRLOOP F3 S1 MAIN BRANCH | 0.158161 |
AIRLOOP F3 S2 MAIN BRANCH | 0.158982 |
AIRLOOP F4 SW MAIN BRANCH | 0.264584 |
AIRLOOP F4 NW MAIN BRANCH | 0.259611 |
AIRLOOP F4 SE MAIN BRANCH | 0.226903 |
AIRLOOP F4 NE MAIN BRANCH | 0.210601 |
AIRLOOP F4 N1 MAIN BRANCH | 0.150604 |
AIRLOOP F4 N2 MAIN BRANCH | 0.149676 |
AIRLOOP F4 S1 MAIN BRANCH | 0.159838 |
AIRLOOP F4 S2 MAIN BRANCH | 0.160487 |
AIRLOOP M SW MAIN BRANCH | 0.268064 |
AIRLOOP M NW MAIN BRANCH | 0.263254 |
AIRLOOP M SE MAIN BRANCH | 0.230223 |
AIRLOOP M NE MAIN BRANCH | 0.214150 |
AIRLOOP M N1 MAIN BRANCH | 0.154223 |
AIRLOOP M N2 MAIN BRANCH | 0.153304 |
AIRLOOP M S1 MAIN BRANCH | 0.163166 |
AIRLOOP M S2 MAIN BRANCH | 0.163790 |
AIRLOOP F6 SW MAIN BRANCH | 0.265923 |
AIRLOOP F6 NW MAIN BRANCH | 0.261115 |
AIRLOOP F6 SE MAIN BRANCH | 0.228554 |
AIRLOOP F6 NE MAIN BRANCH | 0.212010 |
AIRLOOP F6 N1 MAIN BRANCH | 0.152292 |
AIRLOOP F6 N2 MAIN BRANCH | 0.151386 |
AIRLOOP F6 S1 MAIN BRANCH | 0.161064 |
AIRLOOP F6 S2 MAIN BRANCH | 0.161683 |
AIRLOOP F7 SW MAIN BRANCH | 0.265738 |
AIRLOOP F7 NW MAIN BRANCH | 0.261010 |
AIRLOOP F7 SE MAIN BRANCH | 0.228777 |
AIRLOOP F7 NE MAIN BRANCH | 0.211883 |
AIRLOOP F7 N1 MAIN BRANCH | 0.152284 |
AIRLOOP F7 N2 MAIN BRANCH | 0.151387 |
AIRLOOP F7 S1 MAIN BRANCH | 0.160872 |
AIRLOOP F7 S2 MAIN BRANCH | 0.161472 |
AIRLOOP F8 SW MAIN BRANCH | 0.266914 |
AIRLOOP F8 NW MAIN BRANCH | 0.262262 |
AIRLOOP F8 SE MAIN BRANCH | 0.230241 |
AIRLOOP F8 NE MAIN BRANCH | 0.213089 |
AIRLOOP F8 N1 MAIN BRANCH | 0.153612 |
AIRLOOP F8 N2 MAIN BRANCH | 0.152725 |
AIRLOOP F8 S1 MAIN BRANCH | 0.161973 |
AIRLOOP F8 S2 MAIN BRANCH | 0.162555 |
AIRLOOP F9 SW MAIN BRANCH | 0.277545 |
AIRLOOP F9 NW MAIN BRANCH | 0.273047 |
AIRLOOP F9 SE MAIN BRANCH | 0.238873 |
AIRLOOP F9 NE MAIN BRANCH | 0.218881 |
AIRLOOP F9 N1 MAIN BRANCH | 0.163340 |
AIRLOOP F9 N2 MAIN BRANCH | 0.162447 |
AIRLOOP F9 S1 MAIN BRANCH | 0.169425 |
AIRLOOP F9 S2 MAIN BRANCH | 0.170035 |
AIRLOOP T SW MAIN BRANCH | 0.348908 |
AIRLOOP T NW MAIN BRANCH | 0.337357 |
AIRLOOP T SE MAIN BRANCH | 0.311321 |
AIRLOOP T NE MAIN BRANCH | 0.278258 |
AIRLOOP T N1 MAIN BRANCH | 0.215344 |
AIRLOOP T N2 MAIN BRANCH | 0.215292 |
AIRLOOP T S1 MAIN BRANCH | 0.246821 |
AIRLOOP T S2 MAIN BRANCH | 0.247341 |
Design Supply Air Flow Rate [m3/s] | |
AIRLOOP G SW | 0.210212 |
AIRLOOP G NW | 0.206443 |
AIRLOOP OFFICE | 0.315353 |
AIRLOOP G NE | 0.161511 |
AIRLOOP G N1 | 0.114578 |
AIRLOOP G N2 | 0.113403 |
AIRLOOP G S1 | 0.121467 |
AIRLOOP G S2 | 0.127277 |
AIRLOOP F2 SW | 0.261267 |
AIRLOOP F2 NW | 0.255606 |
AIRLOOP F2 SE | 0.244527 |
AIRLOOP F2 NE | 0.205664 |
AIRLOOP F2 N1 | 0.145607 |
AIRLOOP F2 N2 | 0.144650 |
AIRLOOP F2 S1 | 0.155296 |
AIRLOOP F2 S2 | 0.157280 |
AIRLOOP F3 SW | 0.262875 |
AIRLOOP F3 NW | 0.257763 |
AIRLOOP F3 SE | 0.227116 |
AIRLOOP F3 NE | 0.208829 |
AIRLOOP F3 N1 | 0.148623 |
AIRLOOP F3 N2 | 0.147683 |
AIRLOOP F3 S1 | 0.158161 |
AIRLOOP F3 S2 | 0.158982 |
AIRLOOP F4 SW | 0.264584 |
AIRLOOP F4 NW | 0.259611 |
AIRLOOP F4 SE | 0.226903 |
AIRLOOP F4 NE | 0.210601 |
AIRLOOP F4 N1 | 0.150604 |
AIRLOOP F4 N2 | 0.149676 |
AIRLOOP F4 S1 | 0.159838 |
AIRLOOP F4 S2 | 0.160487 |
AIRLOOP M SW | 0.268064 |
AIRLOOP M NW | 0.263254 |
AIRLOOP M SE | 0.230223 |
AIRLOOP M NE | 0.214150 |
AIRLOOP M N1 | 0.154223 |
AIRLOOP M N2 | 0.153304 |
AIRLOOP M S1 | 0.163166 |
AIRLOOP M S2 | 0.163790 |
AIRLOOP F6 SW | 0.265923 |
AIRLOOP F6 NW | 0.261115 |
AIRLOOP F6 SE | 0.228554 |
AIRLOOP F6 NE | 0.212010 |
AIRLOOP F6 N1 | 0.152292 |
AIRLOOP F6 N2 | 0.151386 |
AIRLOOP F6 S1 | 0.161064 |
AIRLOOP F6 S2 | 0.161683 |
AIRLOOP F7 SW | 0.265738 |
AIRLOOP F7 NW | 0.261010 |
AIRLOOP F7 SE | 0.228777 |
AIRLOOP F7 NE | 0.211883 |
AIRLOOP F7 N1 | 0.152284 |
AIRLOOP F7 N2 | 0.151387 |
AIRLOOP F7 S1 | 0.160872 |
AIRLOOP F7 S2 | 0.161472 |
AIRLOOP F8 SW | 0.266914 |
AIRLOOP F8 NW | 0.262262 |
AIRLOOP F8 SE | 0.230241 |
AIRLOOP F8 NE | 0.213089 |
AIRLOOP F8 N1 | 0.153612 |
AIRLOOP F8 N2 | 0.152725 |
AIRLOOP F8 S1 | 0.161973 |
AIRLOOP F8 S2 | 0.162555 |
AIRLOOP F9 SW | 0.277545 |
AIRLOOP F9 NW | 0.273047 |
AIRLOOP F9 SE | 0.238873 |
AIRLOOP F9 NE | 0.218881 |
AIRLOOP F9 N1 | 0.163340 |
AIRLOOP F9 N2 | 0.162447 |
AIRLOOP F9 S1 | 0.169425 |
AIRLOOP F9 S2 | 0.170035 |
AIRLOOP T SW | 0.348908 |
AIRLOOP T NW | 0.337357 |
AIRLOOP T SE | 0.311321 |
AIRLOOP T NE | 0.278258 |
AIRLOOP T N1 | 0.215344 |
AIRLOOP T N2 | 0.215292 |
AIRLOOP T S1 | 0.246821 |
AIRLOOP T S2 | 0.247341 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AIRLOOP G SW OA CONTROLLER | 0.210212 | 0.025952 |
AIRLOOP G NW OA CONTROLLER | 0.206443 | 0.025952 |
AIRLOOP OFFICE OA CONTROLLER | 0.315353 | 0.038103 |
AIRLOOP G NE OA CONTROLLER | 0.161511 | 0.025952 |
AIRLOOP G N1 OA CONTROLLER | 0.114578 | 0.025952 |
AIRLOOP G N2 OA CONTROLLER | 0.113403 | 0.025952 |
AIRLOOP G S1 OA CONTROLLER | 0.121467 | 0.025952 |
AIRLOOP G S2 OA CONTROLLER | 0.127277 | 0.025952 |
AIRLOOP F2 SW OA CONTROLLER | 0.261267 | 0.025952 |
AIRLOOP F2 NW OA CONTROLLER | 0.255606 | 0.025952 |
AIRLOOP F2 SE OA CONTROLLER | 0.244527 | 0.025952 |
AIRLOOP F2 NE OA CONTROLLER | 0.205664 | 0.025952 |
AIRLOOP F2 N1 OA CONTROLLER | 0.145607 | 0.025952 |
AIRLOOP F2 N2 OA CONTROLLER | 0.144650 | 0.025952 |
AIRLOOP F2 S1 OA CONTROLLER | 0.155296 | 0.025952 |
AIRLOOP F2 S2 OA CONTROLLER | 0.157280 | 0.025952 |
AIRLOOP F3 SW OA CONTROLLER | 0.262875 | 0.025952 |
AIRLOOP F3 NW OA CONTROLLER | 0.257763 | 0.025952 |
AIRLOOP F3 SE OA CONTROLLER | 0.227116 | 0.025952 |
AIRLOOP F3 NE OA CONTROLLER | 0.208829 | 0.025952 |
AIRLOOP F3 N1 OA CONTROLLER | 0.148623 | 0.025952 |
AIRLOOP F3 N2 OA CONTROLLER | 0.147683 | 0.025952 |
AIRLOOP F3 S1 OA CONTROLLER | 0.158161 | 0.025952 |
AIRLOOP F3 S2 OA CONTROLLER | 0.158982 | 0.025952 |
AIRLOOP F4 SW OA CONTROLLER | 0.264584 | 0.025952 |
AIRLOOP F4 NW OA CONTROLLER | 0.259611 | 0.025952 |
AIRLOOP F4 SE OA CONTROLLER | 0.226903 | 0.025952 |
AIRLOOP F4 NE OA CONTROLLER | 0.210601 | 0.025952 |
AIRLOOP F4 N1 OA CONTROLLER | 0.150604 | 0.025952 |
AIRLOOP F4 N2 OA CONTROLLER | 0.149676 | 0.025952 |
AIRLOOP F4 S1 OA CONTROLLER | 0.159838 | 0.025952 |
AIRLOOP F4 S2 OA CONTROLLER | 0.160487 | 0.025952 |
AIRLOOP M SW OA CONTROLLER | 0.268064 | 0.025952 |
AIRLOOP M NW OA CONTROLLER | 0.263254 | 0.025952 |
AIRLOOP M SE OA CONTROLLER | 0.230223 | 0.025952 |
AIRLOOP M NE OA CONTROLLER | 0.214150 | 0.025952 |
AIRLOOP M N1 OA CONTROLLER | 0.154223 | 0.025952 |
AIRLOOP M N2 OA CONTROLLER | 0.153304 | 0.025952 |
AIRLOOP M S1 OA CONTROLLER | 0.163166 | 0.025952 |
AIRLOOP M S2 OA CONTROLLER | 0.163790 | 0.025952 |
AIRLOOP F6 SW OA CONTROLLER | 0.265923 | 0.025952 |
AIRLOOP F6 NW OA CONTROLLER | 0.261115 | 0.025952 |
AIRLOOP F6 SE OA CONTROLLER | 0.228554 | 0.025952 |
AIRLOOP F6 NE OA CONTROLLER | 0.212010 | 0.025952 |
AIRLOOP F6 N1 OA CONTROLLER | 0.152292 | 0.025952 |
AIRLOOP F6 N2 OA CONTROLLER | 0.151386 | 0.025952 |
AIRLOOP F6 S1 OA CONTROLLER | 0.161064 | 0.025952 |
AIRLOOP F6 S2 OA CONTROLLER | 0.161683 | 0.025952 |
AIRLOOP F7 SW OA CONTROLLER | 0.265738 | 0.025952 |
AIRLOOP F7 NW OA CONTROLLER | 0.261010 | 0.025952 |
AIRLOOP F7 SE OA CONTROLLER | 0.228777 | 0.025952 |
AIRLOOP F7 NE OA CONTROLLER | 0.211883 | 0.025952 |
AIRLOOP F7 N1 OA CONTROLLER | 0.152284 | 0.025952 |
AIRLOOP F7 N2 OA CONTROLLER | 0.151387 | 0.025952 |
AIRLOOP F7 S1 OA CONTROLLER | 0.160872 | 0.025952 |
AIRLOOP F7 S2 OA CONTROLLER | 0.161472 | 0.025952 |
AIRLOOP F8 SW OA CONTROLLER | 0.266914 | 0.025952 |
AIRLOOP F8 NW OA CONTROLLER | 0.262262 | 0.025952 |
AIRLOOP F8 SE OA CONTROLLER | 0.230241 | 0.025952 |
AIRLOOP F8 NE OA CONTROLLER | 0.213089 | 0.025952 |
AIRLOOP F8 N1 OA CONTROLLER | 0.153612 | 0.025952 |
AIRLOOP F8 N2 OA CONTROLLER | 0.152725 | 0.025952 |
AIRLOOP F8 S1 OA CONTROLLER | 0.161973 | 0.025952 |
AIRLOOP F8 S2 OA CONTROLLER | 0.162555 | 0.025952 |
AIRLOOP F9 SW OA CONTROLLER | 0.277545 | 0.025952 |
AIRLOOP F9 NW OA CONTROLLER | 0.273047 | 0.025952 |
AIRLOOP F9 SE OA CONTROLLER | 0.238873 | 0.025952 |
AIRLOOP F9 NE OA CONTROLLER | 0.218881 | 0.025952 |
AIRLOOP F9 N1 OA CONTROLLER | 0.163340 | 0.025952 |
AIRLOOP F9 N2 OA CONTROLLER | 0.162447 | 0.025952 |
AIRLOOP F9 S1 OA CONTROLLER | 0.169425 | 0.025952 |
AIRLOOP F9 S2 OA CONTROLLER | 0.170035 | 0.025952 |
AIRLOOP T SW OA CONTROLLER | 0.348908 | 0.025952 |
AIRLOOP T NW OA CONTROLLER | 0.337357 | 0.025952 |
AIRLOOP T SE OA CONTROLLER | 0.311321 | 0.025952 |
AIRLOOP T NE OA CONTROLLER | 0.278258 | 0.025952 |
AIRLOOP T N1 OA CONTROLLER | 0.215344 | 0.025952 |
AIRLOOP T N2 OA CONTROLLER | 0.215292 | 0.025952 |
AIRLOOP T S1 OA CONTROLLER | 0.246821 | 0.025952 |
AIRLOOP T S2 OA CONTROLLER | 0.247341 | 0.025952 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity [W] | Rated Sensible Cooling Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP G SW | 0.210212 | 4089.33 | 2665.72 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP G NW | 0.206443 | 4025.42 | 2619.30 | 0.000088 |
HEAT PUMP COOLING MODE AIRLOOP OFFICE | 0.315353 | 5922.42 | 3923.34 | 0.000129 |
HEAT PUMP COOLING MODE AIRLOOP G NE | 0.161511 | 3326.60 | 2110.51 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP G N1 | 0.114578 | 2580.22 | 1583.81 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G N2 | 0.113403 | 2562.41 | 1570.95 | 0.000056 |
HEAT PUMP COOLING MODE AIRLOOP G S1 | 0.121467 | 2729.55 | 1680.21 | 0.000060 |
HEAT PUMP COOLING MODE AIRLOOP G S2 | 0.127277 | 2815.25 | 1743.57 | 0.000061 |
HEAT PUMP COOLING MODE AIRLOOP F2 SW | 0.261267 | 4927.57 | 3253.14 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F2 NW | 0.255606 | 4837.03 | 3186.11 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F2 SE | 0.244527 | 4665.33 | 3061.45 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F2 NE | 0.205664 | 4070.88 | 2624.58 | 0.000089 |
HEAT PUMP COOLING MODE AIRLOOP F2 N1 | 0.145607 | 3099.53 | 1943.06 | 0.000068 |
HEAT PUMP COOLING MODE AIRLOOP F2 N2 | 0.144650 | 3085.19 | 1932.58 | 0.000067 |
HEAT PUMP COOLING MODE AIRLOOP F2 S1 | 0.155296 | 3283.13 | 2068.74 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F2 S2 | 0.157280 | 3312.09 | 2090.31 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F3 SW | 0.262875 | 5012.12 | 3290.43 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F3 NW | 0.257763 | 4929.13 | 3229.34 | 0.000108 |
HEAT PUMP COOLING MODE AIRLOOP F3 SE | 0.227116 | 4472.45 | 2892.13 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F3 NE | 0.208829 | 4174.31 | 2678.40 | 0.000091 |
HEAT PUMP COOLING MODE AIRLOOP F3 N1 | 0.148623 | 3176.97 | 1987.60 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F3 N2 | 0.147683 | 3162.83 | 1977.31 | 0.000069 |
HEAT PUMP COOLING MODE AIRLOOP F3 S1 | 0.158161 | 3358.42 | 2111.54 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F3 S2 | 0.158982 | 3370.37 | 2120.44 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F4 SW | 0.264584 | 5082.31 | 3323.83 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F4 NW | 0.259611 | 5001.06 | 3264.24 | 0.000109 |
HEAT PUMP COOLING MODE AIRLOOP F4 SE | 0.226903 | 4512.72 | 2904.46 | 0.000099 |
HEAT PUMP COOLING MODE AIRLOOP F4 NE | 0.210601 | 4242.66 | 2712.23 | 0.000093 |
HEAT PUMP COOLING MODE AIRLOOP F4 N1 | 0.150604 | 3230.82 | 2017.95 | 0.000071 |
HEAT PUMP COOLING MODE AIRLOOP F4 N2 | 0.149676 | 3216.78 | 2007.78 | 0.000070 |
HEAT PUMP COOLING MODE AIRLOOP F4 S1 | 0.159838 | 3407.92 | 2138.53 | 0.000074 |
HEAT PUMP COOLING MODE AIRLOOP F4 S2 | 0.160487 | 3417.37 | 2145.56 | 0.000075 |
HEAT PUMP COOLING MODE AIRLOOP M SW | 0.268064 | 5169.68 | 3373.76 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP M NW | 0.263254 | 5090.66 | 3315.94 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP M SE | 0.230223 | 4636.25 | 2971.84 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP M NE | 0.214150 | 4329.25 | 2762.70 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP M N1 | 0.154223 | 3304.58 | 2064.53 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP M N2 | 0.153304 | 3290.66 | 2054.45 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP M S1 | 0.163166 | 3477.34 | 2181.96 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP M S2 | 0.163790 | 3486.43 | 2188.72 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 SW | 0.265923 | 5169.64 | 3360.79 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F6 NW | 0.261115 | 5090.35 | 3302.97 | 0.000111 |
HEAT PUMP COOLING MODE AIRLOOP F6 SE | 0.228554 | 4640.90 | 2963.67 | 0.000101 |
HEAT PUMP COOLING MODE AIRLOOP F6 NE | 0.212010 | 4326.41 | 2749.51 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F6 N1 | 0.152292 | 3292.46 | 2049.59 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F6 N2 | 0.151386 | 3278.65 | 2039.63 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F6 S1 | 0.161064 | 3464.85 | 2165.92 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F6 S2 | 0.161683 | 3472.17 | 2171.74 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 SW | 0.265738 | 5194.08 | 3367.83 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F7 NW | 0.261010 | 5115.75 | 3310.86 | 0.000112 |
HEAT PUMP COOLING MODE AIRLOOP F7 SE | 0.228777 | 4669.70 | 2974.89 | 0.000102 |
HEAT PUMP COOLING MODE AIRLOOP F7 NE | 0.211883 | 4355.99 | 2760.38 | 0.000095 |
HEAT PUMP COOLING MODE AIRLOOP F7 N1 | 0.152284 | 3306.89 | 2054.84 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F7 N2 | 0.151387 | 3293.18 | 2044.98 | 0.000072 |
HEAT PUMP COOLING MODE AIRLOOP F7 S1 | 0.160872 | 3476.76 | 2169.10 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F7 S2 | 0.161472 | 3483.86 | 2174.73 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F8 SW | 0.266914 | 5235.52 | 3388.75 | 0.000114 |
HEAT PUMP COOLING MODE AIRLOOP F8 NW | 0.262262 | 5158.18 | 3332.60 | 0.000113 |
HEAT PUMP COOLING MODE AIRLOOP F8 SE | 0.230241 | 4714.22 | 2998.78 | 0.000103 |
HEAT PUMP COOLING MODE AIRLOOP F8 NE | 0.213089 | 4396.26 | 2781.42 | 0.000096 |
HEAT PUMP COOLING MODE AIRLOOP F8 N1 | 0.153612 | 3339.91 | 2074.13 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F8 N2 | 0.152725 | 3326.31 | 2064.36 | 0.000073 |
HEAT PUMP COOLING MODE AIRLOOP F8 S1 | 0.161973 | 3506.45 | 2185.89 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F8 S2 | 0.162555 | 3513.31 | 2191.34 | 0.000077 |
HEAT PUMP COOLING MODE AIRLOOP F9 SW | 0.277545 | 5413.81 | 3512.02 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP F9 NW | 0.273047 | 5338.92 | 3457.56 | 0.000117 |
HEAT PUMP COOLING MODE AIRLOOP F9 SE | 0.238873 | 4863.88 | 3100.48 | 0.000106 |
HEAT PUMP COOLING MODE AIRLOOP F9 NE | 0.218881 | 4503.70 | 2852.00 | 0.000098 |
HEAT PUMP COOLING MODE AIRLOOP F9 N1 | 0.163340 | 3498.59 | 2184.79 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 N2 | 0.162447 | 3484.99 | 2174.98 | 0.000076 |
HEAT PUMP COOLING MODE AIRLOOP F9 S1 | 0.169425 | 3630.79 | 2272.05 | 0.000079 |
HEAT PUMP COOLING MODE AIRLOOP F9 S2 | 0.170035 | 3639.73 | 2278.66 | 0.000080 |
HEAT PUMP COOLING MODE AIRLOOP T SW | 0.348908 | 6492.52 | 4304.98 | 0.000142 |
HEAT PUMP COOLING MODE AIRLOOP T NW | 0.337357 | 6310.39 | 4171.76 | 0.000138 |
HEAT PUMP COOLING MODE AIRLOOP T SE | 0.311321 | 5949.07 | 3897.03 | 0.000130 |
HEAT PUMP COOLING MODE AIRLOOP T NE | 0.278258 | 5420.29 | 3514.43 | 0.000118 |
HEAT PUMP COOLING MODE AIRLOOP T N1 | 0.215344 | 4323.83 | 2778.60 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP T N2 | 0.215292 | 4322.73 | 2777.92 | 0.000094 |
HEAT PUMP COOLING MODE AIRLOOP T S1 | 0.246821 | 4779.92 | 3119.96 | 0.000104 |
HEAT PUMP COOLING MODE AIRLOOP T S2 | 0.247341 | 4787.24 | 3125.54 | 0.000105 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP G SW DXAC HEAT PUMP | 0.210212 | 0.210212 | 0.210212 | 0.210212 | 4089.33 | 4089.33 | 3368.22 | 1.00 |
AIRLOOP G NW DXAC HEAT PUMP | 0.206443 | 0.206443 | 0.206443 | 0.206443 | 4025.42 | 4025.42 | 3370.28 | 1.00 |
AIRLOOP OFFICE DXAC HEAT PUMP | 0.315353 | 0.315353 | 0.315353 | 0.315353 | 5922.42 | 5922.42 | 4164.37 | 1.00 |
AIRLOOP G NE DXAC HEAT PUMP | 0.161511 | 0.161511 | 0.161511 | 0.161511 | 3326.60 | 3326.60 | 3370.28 | 1.00 |
AIRLOOP G N1 DXAC HEAT PUMP | 0.114578 | 0.114578 | 0.114578 | 0.114578 | 2580.22 | 2580.22 | 2526.90 | 1.00 |
AIRLOOP G N2 DXAC HEAT PUMP | 0.113403 | 0.113403 | 0.113403 | 0.113403 | 2562.41 | 2562.41 | 2526.90 | 1.00 |
AIRLOOP G S1 DXAC HEAT PUMP | 0.121467 | 0.121467 | 0.121467 | 0.121467 | 2729.55 | 2729.55 | 2521.41 | 1.00 |
AIRLOOP G S2 DXAC HEAT PUMP | 0.127277 | 0.127277 | 0.127277 | 0.127277 | 2815.25 | 2815.25 | 2527.68 | 1.00 |
AIRLOOP F2 SW DXAC HEAT PUMP | 0.261267 | 0.261267 | 0.261267 | 0.261267 | 4927.57 | 4927.57 | 3396.35 | 1.00 |
AIRLOOP F2 NW DXAC HEAT PUMP | 0.255606 | 0.255606 | 0.255606 | 0.255606 | 4837.03 | 4837.03 | 3397.01 | 1.00 |
AIRLOOP F2 SE DXAC HEAT PUMP | 0.244527 | 0.244527 | 0.244527 | 0.244527 | 4665.33 | 4665.33 | 3414.85 | 1.00 |
AIRLOOP F2 NE DXAC HEAT PUMP | 0.205664 | 0.205664 | 0.205664 | 0.205664 | 4070.88 | 4070.88 | 3397.01 | 1.00 |
AIRLOOP F2 N1 DXAC HEAT PUMP | 0.145607 | 0.145607 | 0.145607 | 0.145607 | 3099.53 | 3099.53 | 2334.30 | 1.00 |
AIRLOOP F2 N2 DXAC HEAT PUMP | 0.144650 | 0.144650 | 0.144650 | 0.144650 | 3085.19 | 3085.19 | 2334.30 | 1.00 |
AIRLOOP F2 S1 DXAC HEAT PUMP | 0.155296 | 0.155296 | 0.155296 | 0.155296 | 3283.13 | 3283.13 | 2336.33 | 1.00 |
AIRLOOP F2 S2 DXAC HEAT PUMP | 0.157280 | 0.157280 | 0.157280 | 0.157280 | 3312.09 | 3312.09 | 2337.53 | 1.00 |
AIRLOOP F3 SW DXAC HEAT PUMP | 0.262875 | 0.262875 | 0.262875 | 0.262875 | 5012.12 | 5012.12 | 3472.13 | 1.00 |
AIRLOOP F3 NW DXAC HEAT PUMP | 0.257763 | 0.257763 | 0.257763 | 0.257763 | 4929.13 | 4929.13 | 3477.12 | 1.00 |
AIRLOOP F3 SE DXAC HEAT PUMP | 0.227116 | 0.227116 | 0.227116 | 0.227116 | 4472.45 | 4472.45 | 3474.14 | 1.00 |
AIRLOOP F3 NE DXAC HEAT PUMP | 0.208829 | 0.208829 | 0.208829 | 0.208829 | 4174.31 | 4174.31 | 3477.12 | 1.00 |
AIRLOOP F3 N1 DXAC HEAT PUMP | 0.148623 | 0.148623 | 0.148623 | 0.148623 | 3176.97 | 3176.97 | 2343.90 | 1.00 |
AIRLOOP F3 N2 DXAC HEAT PUMP | 0.147683 | 0.147683 | 0.147683 | 0.147683 | 3162.83 | 3162.83 | 2343.90 | 1.00 |
AIRLOOP F3 S1 DXAC HEAT PUMP | 0.158161 | 0.158161 | 0.158161 | 0.158161 | 3358.42 | 3358.42 | 2339.60 | 1.00 |
AIRLOOP F3 S2 DXAC HEAT PUMP | 0.158982 | 0.158982 | 0.158982 | 0.158982 | 3370.37 | 3370.37 | 2339.79 | 1.00 |
AIRLOOP F4 SW DXAC HEAT PUMP | 0.264584 | 0.264584 | 0.264584 | 0.264584 | 5082.31 | 5082.31 | 3584.04 | 1.00 |
AIRLOOP F4 NW DXAC HEAT PUMP | 0.259611 | 0.259611 | 0.259611 | 0.259611 | 5001.06 | 5001.06 | 3592.00 | 1.00 |
AIRLOOP F4 SE DXAC HEAT PUMP | 0.226903 | 0.226903 | 0.226903 | 0.226903 | 4512.72 | 4512.72 | 3584.25 | 1.00 |
AIRLOOP F4 NE DXAC HEAT PUMP | 0.210601 | 0.210601 | 0.210601 | 0.210601 | 4242.66 | 4242.66 | 3592.00 | 1.00 |
AIRLOOP F4 N1 DXAC HEAT PUMP | 0.150604 | 0.150604 | 0.150604 | 0.150604 | 3230.82 | 3230.82 | 2403.20 | 1.00 |
AIRLOOP F4 N2 DXAC HEAT PUMP | 0.149676 | 0.149676 | 0.149676 | 0.149676 | 3216.78 | 3216.78 | 2403.20 | 1.00 |
AIRLOOP F4 S1 DXAC HEAT PUMP | 0.159838 | 0.159838 | 0.159838 | 0.159838 | 3407.92 | 3407.92 | 2395.62 | 1.00 |
AIRLOOP F4 S2 DXAC HEAT PUMP | 0.160487 | 0.160487 | 0.160487 | 0.160487 | 3417.37 | 3417.37 | 2395.65 | 1.00 |
AIRLOOP M SW DXAC HEAT PUMP | 0.268064 | 0.268064 | 0.268064 | 0.268064 | 5169.68 | 5169.68 | 3665.19 | 1.00 |
AIRLOOP M NW DXAC HEAT PUMP | 0.263254 | 0.263254 | 0.263254 | 0.263254 | 5090.66 | 5090.66 | 3674.15 | 1.00 |
AIRLOOP M SE DXAC HEAT PUMP | 0.230223 | 0.230223 | 0.230223 | 0.230223 | 4636.25 | 4636.25 | 3665.21 | 1.00 |
AIRLOOP M NE DXAC HEAT PUMP | 0.214150 | 0.214150 | 0.214150 | 0.214150 | 4329.25 | 4329.25 | 3674.15 | 1.00 |
AIRLOOP M N1 DXAC HEAT PUMP | 0.154223 | 0.154223 | 0.154223 | 0.154223 | 3304.58 | 3304.58 | 2441.15 | 1.00 |
AIRLOOP M N2 DXAC HEAT PUMP | 0.153304 | 0.153304 | 0.153304 | 0.153304 | 3290.66 | 3290.66 | 2441.15 | 1.00 |
AIRLOOP M S1 DXAC HEAT PUMP | 0.163166 | 0.163166 | 0.163166 | 0.163166 | 3477.34 | 3477.34 | 2432.44 | 1.00 |
AIRLOOP M S2 DXAC HEAT PUMP | 0.163790 | 0.163790 | 0.163790 | 0.163790 | 3486.43 | 3486.43 | 2432.44 | 1.00 |
AIRLOOP F6 SW DXAC HEAT PUMP | 0.265923 | 0.265923 | 0.265923 | 0.265923 | 5169.64 | 5169.64 | 3795.91 | 1.00 |
AIRLOOP F6 NW DXAC HEAT PUMP | 0.261115 | 0.261115 | 0.261115 | 0.261115 | 5090.35 | 5090.35 | 3807.37 | 1.00 |
AIRLOOP F6 SE DXAC HEAT PUMP | 0.228554 | 0.228554 | 0.228554 | 0.228554 | 4640.90 | 4640.90 | 3795.91 | 1.00 |
AIRLOOP F6 NE DXAC HEAT PUMP | 0.212010 | 0.212010 | 0.212010 | 0.212010 | 4326.41 | 4326.41 | 3807.37 | 1.00 |
AIRLOOP F6 N1 DXAC HEAT PUMP | 0.152292 | 0.152292 | 0.152292 | 0.152292 | 3292.46 | 3292.46 | 2534.38 | 1.00 |
AIRLOOP F6 N2 DXAC HEAT PUMP | 0.151386 | 0.151386 | 0.151386 | 0.151386 | 3278.65 | 3278.65 | 2534.38 | 1.00 |
AIRLOOP F6 S1 DXAC HEAT PUMP | 0.161064 | 0.161064 | 0.161064 | 0.161064 | 3464.85 | 3464.85 | 2523.17 | 1.00 |
AIRLOOP F6 S2 DXAC HEAT PUMP | 0.161683 | 0.161683 | 0.161683 | 0.161683 | 3472.17 | 3472.17 | 2523.17 | 1.00 |
AIRLOOP F7 SW DXAC HEAT PUMP | 0.265738 | 0.265738 | 0.265738 | 0.265738 | 5194.08 | 5194.08 | 3895.14 | 1.00 |
AIRLOOP F7 NW DXAC HEAT PUMP | 0.261010 | 0.261010 | 0.261010 | 0.261010 | 5115.75 | 5115.75 | 3907.73 | 1.00 |
AIRLOOP F7 SE DXAC HEAT PUMP | 0.228777 | 0.228777 | 0.228777 | 0.228777 | 4669.70 | 4669.70 | 3895.14 | 1.00 |
AIRLOOP F7 NE DXAC HEAT PUMP | 0.211883 | 0.211883 | 0.211883 | 0.211883 | 4355.99 | 4355.99 | 3907.73 | 1.00 |
AIRLOOP F7 N1 DXAC HEAT PUMP | 0.152284 | 0.152284 | 0.152284 | 0.152284 | 3306.89 | 3306.89 | 2600.66 | 1.00 |
AIRLOOP F7 N2 DXAC HEAT PUMP | 0.151387 | 0.151387 | 0.151387 | 0.151387 | 3293.18 | 3293.18 | 2600.66 | 1.00 |
AIRLOOP F7 S1 DXAC HEAT PUMP | 0.160872 | 0.160872 | 0.160872 | 0.160872 | 3476.76 | 3476.76 | 2588.32 | 1.00 |
AIRLOOP F7 S2 DXAC HEAT PUMP | 0.161472 | 0.161472 | 0.161472 | 0.161472 | 3483.86 | 3483.86 | 2588.32 | 1.00 |
AIRLOOP F8 SW DXAC HEAT PUMP | 0.266914 | 0.266914 | 0.266914 | 0.266914 | 5235.52 | 5235.52 | 3993.96 | 1.00 |
AIRLOOP F8 NW DXAC HEAT PUMP | 0.262262 | 0.262262 | 0.262262 | 0.262262 | 5158.18 | 5158.18 | 4007.24 | 1.00 |
AIRLOOP F8 SE DXAC HEAT PUMP | 0.230241 | 0.230241 | 0.230241 | 0.230241 | 4714.22 | 4714.22 | 3993.96 | 1.00 |
AIRLOOP F8 NE DXAC HEAT PUMP | 0.213089 | 0.213089 | 0.213089 | 0.213089 | 4396.26 | 4396.26 | 4007.24 | 1.00 |
AIRLOOP F8 N1 DXAC HEAT PUMP | 0.153612 | 0.153612 | 0.153612 | 0.153612 | 3339.91 | 3339.91 | 2669.74 | 1.00 |
AIRLOOP F8 N2 DXAC HEAT PUMP | 0.152725 | 0.152725 | 0.152725 | 0.152725 | 3326.31 | 3326.31 | 2669.74 | 1.00 |
AIRLOOP F8 S1 DXAC HEAT PUMP | 0.161973 | 0.161973 | 0.161973 | 0.161973 | 3506.45 | 3506.45 | 2656.69 | 1.00 |
AIRLOOP F8 S2 DXAC HEAT PUMP | 0.162555 | 0.162555 | 0.162555 | 0.162555 | 3513.31 | 3513.31 | 2656.69 | 1.00 |
AIRLOOP F9 SW DXAC HEAT PUMP | 0.277545 | 0.277545 | 0.277545 | 0.277545 | 5413.81 | 5413.81 | 4208.73 | 1.00 |
AIRLOOP F9 NW DXAC HEAT PUMP | 0.273047 | 0.273047 | 0.273047 | 0.273047 | 5338.92 | 5338.92 | 4220.26 | 1.00 |
AIRLOOP F9 SE DXAC HEAT PUMP | 0.238873 | 0.238873 | 0.238873 | 0.238873 | 4863.88 | 4863.88 | 4208.73 | 1.00 |
AIRLOOP F9 NE DXAC HEAT PUMP | 0.218881 | 0.218881 | 0.218881 | 0.218881 | 4503.70 | 4503.70 | 4220.26 | 1.00 |
AIRLOOP F9 N1 DXAC HEAT PUMP | 0.163340 | 0.163340 | 0.163340 | 0.163340 | 3498.59 | 3498.59 | 2846.73 | 1.00 |
AIRLOOP F9 N2 DXAC HEAT PUMP | 0.162447 | 0.162447 | 0.162447 | 0.162447 | 3484.99 | 3484.99 | 2846.73 | 1.00 |
AIRLOOP F9 S1 DXAC HEAT PUMP | 0.169425 | 0.169425 | 0.169425 | 0.169425 | 3630.79 | 3630.79 | 2834.99 | 1.00 |
AIRLOOP F9 S2 DXAC HEAT PUMP | 0.170035 | 0.170035 | 0.170035 | 0.170035 | 3639.73 | 3639.73 | 2834.99 | 1.00 |
AIRLOOP T SW DXAC HEAT PUMP | 0.348908 | 0.348908 | 0.348908 | 0.348908 | 6492.52 | 6492.52 | 4832.87 | 1.00 |
AIRLOOP T NW DXAC HEAT PUMP | 0.337357 | 0.337357 | 0.337357 | 0.337357 | 6310.39 | 6310.39 | 4850.74 | 1.00 |
AIRLOOP T SE DXAC HEAT PUMP | 0.311321 | 0.311321 | 0.311321 | 0.311321 | 5949.07 | 5949.07 | 4832.87 | 1.00 |
AIRLOOP T NE DXAC HEAT PUMP | 0.278258 | 0.278258 | 0.278258 | 0.278258 | 5420.29 | 5420.29 | 4850.74 | 1.00 |
AIRLOOP T N1 DXAC HEAT PUMP | 0.215344 | 0.215344 | 0.215344 | 0.215344 | 4323.83 | 4323.83 | 3509.69 | 1.00 |
AIRLOOP T N2 DXAC HEAT PUMP | 0.215292 | 0.215292 | 0.215292 | 0.215292 | 4322.73 | 4322.73 | 3509.69 | 1.00 |
AIRLOOP T S1 DXAC HEAT PUMP | 0.246821 | 0.246821 | 0.246821 | 0.246821 | 4779.92 | 4779.92 | 3488.70 | 1.00 |
AIRLOOP T S2 DXAC HEAT PUMP | 0.247341 | 0.247341 | 0.247341 | 0.247341 | 4787.24 | 4787.24 | 3488.70 | 1.00 |
Maximum Flow Rate [m3/s] | |
AIRLOOP G SW SUPPLY FAN | 0.210212 |
AIRLOOP G NW SUPPLY FAN | 0.206443 |
AIRLOOP OFFICE SUPPLY FAN | 0.315353 |
AIRLOOP G NE SUPPLY FAN | 0.161511 |
AIRLOOP G N1 SUPPLY FAN | 0.114578 |
AIRLOOP G N2 SUPPLY FAN | 0.113403 |
AIRLOOP G S1 SUPPLY FAN | 0.121467 |
AIRLOOP G S2 SUPPLY FAN | 0.127277 |
AIRLOOP F2 SW SUPPLY FAN | 0.261267 |
AIRLOOP F2 NW SUPPLY FAN | 0.255606 |
AIRLOOP F2 SE SUPPLY FAN | 0.244527 |
AIRLOOP F2 NE SUPPLY FAN | 0.205664 |
AIRLOOP F2 N1 SUPPLY FAN | 0.145607 |
AIRLOOP F2 N2 SUPPLY FAN | 0.144650 |
AIRLOOP F2 S1 SUPPLY FAN | 0.155296 |
AIRLOOP F2 S2 SUPPLY FAN | 0.157280 |
AIRLOOP F3 SW SUPPLY FAN | 0.262875 |
AIRLOOP F3 NW SUPPLY FAN | 0.257763 |
AIRLOOP F3 SE SUPPLY FAN | 0.227116 |
AIRLOOP F3 NE SUPPLY FAN | 0.208829 |
AIRLOOP F3 N1 SUPPLY FAN | 0.148623 |
AIRLOOP F3 N2 SUPPLY FAN | 0.147683 |
AIRLOOP F3 S1 SUPPLY FAN | 0.158161 |
AIRLOOP F3 S2 SUPPLY FAN | 0.158982 |
AIRLOOP F4 SW SUPPLY FAN | 0.264584 |
AIRLOOP F4 NW SUPPLY FAN | 0.259611 |
AIRLOOP F4 SE SUPPLY FAN | 0.226903 |
AIRLOOP F4 NE SUPPLY FAN | 0.210601 |
AIRLOOP F4 N1 SUPPLY FAN | 0.150604 |
AIRLOOP F4 N2 SUPPLY FAN | 0.149676 |
AIRLOOP F4 S1 SUPPLY FAN | 0.159838 |
AIRLOOP F4 S2 SUPPLY FAN | 0.160487 |
AIRLOOP M SW SUPPLY FAN | 0.268064 |
AIRLOOP M NW SUPPLY FAN | 0.263254 |
AIRLOOP M SE SUPPLY FAN | 0.230223 |
AIRLOOP M NE SUPPLY FAN | 0.214150 |
AIRLOOP M N1 SUPPLY FAN | 0.154223 |
AIRLOOP M N2 SUPPLY FAN | 0.153304 |
AIRLOOP M S1 SUPPLY FAN | 0.163166 |
AIRLOOP M S2 SUPPLY FAN | 0.163790 |
AIRLOOP F6 SW SUPPLY FAN | 0.265923 |
AIRLOOP F6 NW SUPPLY FAN | 0.261115 |
AIRLOOP F6 SE SUPPLY FAN | 0.228554 |
AIRLOOP F6 NE SUPPLY FAN | 0.212010 |
AIRLOOP F6 N1 SUPPLY FAN | 0.152292 |
AIRLOOP F6 N2 SUPPLY FAN | 0.151386 |
AIRLOOP F6 S1 SUPPLY FAN | 0.161064 |
AIRLOOP F6 S2 SUPPLY FAN | 0.161683 |
AIRLOOP F7 SW SUPPLY FAN | 0.265738 |
AIRLOOP F7 NW SUPPLY FAN | 0.261010 |
AIRLOOP F7 SE SUPPLY FAN | 0.228777 |
AIRLOOP F7 NE SUPPLY FAN | 0.211883 |
AIRLOOP F7 N1 SUPPLY FAN | 0.152284 |
AIRLOOP F7 N2 SUPPLY FAN | 0.151387 |
AIRLOOP F7 S1 SUPPLY FAN | 0.160872 |
AIRLOOP F7 S2 SUPPLY FAN | 0.161472 |
AIRLOOP F8 SW SUPPLY FAN | 0.266914 |
AIRLOOP F8 NW SUPPLY FAN | 0.262262 |
AIRLOOP F8 SE SUPPLY FAN | 0.230241 |
AIRLOOP F8 NE SUPPLY FAN | 0.213089 |
AIRLOOP F8 N1 SUPPLY FAN | 0.153612 |
AIRLOOP F8 N2 SUPPLY FAN | 0.152725 |
AIRLOOP F8 S1 SUPPLY FAN | 0.161973 |
AIRLOOP F8 S2 SUPPLY FAN | 0.162555 |
AIRLOOP F9 SW SUPPLY FAN | 0.277545 |
AIRLOOP F9 NW SUPPLY FAN | 0.273047 |
AIRLOOP F9 SE SUPPLY FAN | 0.238873 |
AIRLOOP F9 NE SUPPLY FAN | 0.218881 |
AIRLOOP F9 N1 SUPPLY FAN | 0.163340 |
AIRLOOP F9 N2 SUPPLY FAN | 0.162447 |
AIRLOOP F9 S1 SUPPLY FAN | 0.169425 |
AIRLOOP F9 S2 SUPPLY FAN | 0.170035 |
AIRLOOP T SW SUPPLY FAN | 0.348908 |
AIRLOOP T NW SUPPLY FAN | 0.337357 |
AIRLOOP T SE SUPPLY FAN | 0.311321 |
AIRLOOP T NE SUPPLY FAN | 0.278258 |
AIRLOOP T N1 SUPPLY FAN | 0.215344 |
AIRLOOP T N2 SUPPLY FAN | 0.215292 |
AIRLOOP T S1 SUPPLY FAN | 0.246821 |
AIRLOOP T S2 SUPPLY FAN | 0.247341 |
Rated Air Flow Rate [m3/s] | Rated Heating Capacity [W] | Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP G SW | 0.210212 | 4089.33 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP G NW | 0.206443 | 4025.42 | 0.000088 |
HEAT PUMP HEATING MODE AIRLOOP OFFICE | 0.315353 | 5922.42 | 0.000129 |
HEAT PUMP HEATING MODE AIRLOOP G NE | 0.161511 | 3326.60 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP G N1 | 0.114578 | 2580.22 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G N2 | 0.113403 | 2562.41 | 0.000056 |
HEAT PUMP HEATING MODE AIRLOOP G S1 | 0.121467 | 2729.55 | 0.000060 |
HEAT PUMP HEATING MODE AIRLOOP G S2 | 0.127277 | 2815.25 | 0.000061 |
HEAT PUMP HEATING MODE AIRLOOP F2 SW | 0.261267 | 4927.57 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F2 NW | 0.255606 | 4837.03 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F2 SE | 0.244527 | 4665.33 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F2 NE | 0.205664 | 4070.88 | 0.000089 |
HEAT PUMP HEATING MODE AIRLOOP F2 N1 | 0.145607 | 3099.53 | 0.000068 |
HEAT PUMP HEATING MODE AIRLOOP F2 N2 | 0.144650 | 3085.19 | 0.000067 |
HEAT PUMP HEATING MODE AIRLOOP F2 S1 | 0.155296 | 3283.13 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F2 S2 | 0.157280 | 3312.09 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F3 SW | 0.262875 | 5012.12 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F3 NW | 0.257763 | 4929.13 | 0.000108 |
HEAT PUMP HEATING MODE AIRLOOP F3 SE | 0.227116 | 4472.45 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F3 NE | 0.208829 | 4174.31 | 0.000091 |
HEAT PUMP HEATING MODE AIRLOOP F3 N1 | 0.148623 | 3176.97 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F3 N2 | 0.147683 | 3162.83 | 0.000069 |
HEAT PUMP HEATING MODE AIRLOOP F3 S1 | 0.158161 | 3358.42 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F3 S2 | 0.158982 | 3370.37 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F4 SW | 0.264584 | 5082.31 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F4 NW | 0.259611 | 5001.06 | 0.000109 |
HEAT PUMP HEATING MODE AIRLOOP F4 SE | 0.226903 | 4512.72 | 0.000099 |
HEAT PUMP HEATING MODE AIRLOOP F4 NE | 0.210601 | 4242.66 | 0.000093 |
HEAT PUMP HEATING MODE AIRLOOP F4 N1 | 0.150604 | 3230.82 | 0.000071 |
HEAT PUMP HEATING MODE AIRLOOP F4 N2 | 0.149676 | 3216.78 | 0.000070 |
HEAT PUMP HEATING MODE AIRLOOP F4 S1 | 0.159838 | 3407.92 | 0.000074 |
HEAT PUMP HEATING MODE AIRLOOP F4 S2 | 0.160487 | 3417.37 | 0.000075 |
HEAT PUMP HEATING MODE AIRLOOP M SW | 0.268064 | 5169.68 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP M NW | 0.263254 | 5090.66 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP M SE | 0.230223 | 4636.25 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP M NE | 0.214150 | 4329.25 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP M N1 | 0.154223 | 3304.58 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP M N2 | 0.153304 | 3290.66 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP M S1 | 0.163166 | 3477.34 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP M S2 | 0.163790 | 3486.43 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 SW | 0.265923 | 5169.64 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F6 NW | 0.261115 | 5090.35 | 0.000111 |
HEAT PUMP HEATING MODE AIRLOOP F6 SE | 0.228554 | 4640.90 | 0.000101 |
HEAT PUMP HEATING MODE AIRLOOP F6 NE | 0.212010 | 4326.41 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F6 N1 | 0.152292 | 3292.46 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F6 N2 | 0.151386 | 3278.65 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F6 S1 | 0.161064 | 3464.85 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F6 S2 | 0.161683 | 3472.17 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 SW | 0.265738 | 5194.08 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F7 NW | 0.261010 | 5115.75 | 0.000112 |
HEAT PUMP HEATING MODE AIRLOOP F7 SE | 0.228777 | 4669.70 | 0.000102 |
HEAT PUMP HEATING MODE AIRLOOP F7 NE | 0.211883 | 4355.99 | 0.000095 |
HEAT PUMP HEATING MODE AIRLOOP F7 N1 | 0.152284 | 3306.89 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F7 N2 | 0.151387 | 3293.18 | 0.000072 |
HEAT PUMP HEATING MODE AIRLOOP F7 S1 | 0.160872 | 3476.76 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F7 S2 | 0.161472 | 3483.86 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F8 SW | 0.266914 | 5235.52 | 0.000114 |
HEAT PUMP HEATING MODE AIRLOOP F8 NW | 0.262262 | 5158.18 | 0.000113 |
HEAT PUMP HEATING MODE AIRLOOP F8 SE | 0.230241 | 4714.22 | 0.000103 |
HEAT PUMP HEATING MODE AIRLOOP F8 NE | 0.213089 | 4396.26 | 0.000096 |
HEAT PUMP HEATING MODE AIRLOOP F8 N1 | 0.153612 | 3339.91 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F8 N2 | 0.152725 | 3326.31 | 0.000073 |
HEAT PUMP HEATING MODE AIRLOOP F8 S1 | 0.161973 | 3506.45 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F8 S2 | 0.162555 | 3513.31 | 0.000077 |
HEAT PUMP HEATING MODE AIRLOOP F9 SW | 0.277545 | 5413.81 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP F9 NW | 0.273047 | 5338.92 | 0.000117 |
HEAT PUMP HEATING MODE AIRLOOP F9 SE | 0.238873 | 4863.88 | 0.000106 |
HEAT PUMP HEATING MODE AIRLOOP F9 NE | 0.218881 | 4503.70 | 0.000098 |
HEAT PUMP HEATING MODE AIRLOOP F9 N1 | 0.163340 | 3498.59 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 N2 | 0.162447 | 3484.99 | 0.000076 |
HEAT PUMP HEATING MODE AIRLOOP F9 S1 | 0.169425 | 3630.79 | 0.000079 |
HEAT PUMP HEATING MODE AIRLOOP F9 S2 | 0.170035 | 3639.73 | 0.000080 |
HEAT PUMP HEATING MODE AIRLOOP T SW | 0.348908 | 6492.52 | 0.000142 |
HEAT PUMP HEATING MODE AIRLOOP T NW | 0.337357 | 6310.39 | 0.000138 |
HEAT PUMP HEATING MODE AIRLOOP T SE | 0.311321 | 5949.07 | 0.000130 |
HEAT PUMP HEATING MODE AIRLOOP T NE | 0.278258 | 5420.29 | 0.000118 |
HEAT PUMP HEATING MODE AIRLOOP T N1 | 0.215344 | 4323.83 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP T N2 | 0.215292 | 4322.73 | 0.000094 |
HEAT PUMP HEATING MODE AIRLOOP T S1 | 0.246821 | 4779.92 | 0.000104 |
HEAT PUMP HEATING MODE AIRLOOP T S2 | 0.247341 | 4787.24 | 0.000105 |
Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G SW | 3368.22 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NW | 3370.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP OFFICE | 4164.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G NE | 3370.28 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N1 | 2526.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G N2 | 2526.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S1 | 2521.41 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP G S2 | 2527.68 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SW | 3396.35 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NW | 3397.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 SE | 3414.85 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 NE | 3397.01 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N1 | 2334.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 N2 | 2334.30 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S1 | 2336.33 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F2 S2 | 2337.53 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SW | 3472.13 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NW | 3477.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 SE | 3474.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 NE | 3477.12 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N1 | 2343.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 N2 | 2343.90 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S1 | 2339.60 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F3 S2 | 2339.79 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SW | 3584.04 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NW | 3592.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 SE | 3584.25 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 NE | 3592.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N1 | 2403.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 N2 | 2403.20 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S1 | 2395.62 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F4 S2 | 2395.65 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SW | 3665.19 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NW | 3674.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M SE | 3665.21 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M NE | 3674.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N1 | 2441.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M N2 | 2441.15 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S1 | 2432.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP M S2 | 2432.44 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SW | 3795.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NW | 3807.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 SE | 3795.91 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 NE | 3807.37 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N1 | 2534.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 N2 | 2534.38 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S1 | 2523.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F6 S2 | 2523.17 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SW | 3895.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NW | 3907.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 SE | 3895.14 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 NE | 3907.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N1 | 2600.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 N2 | 2600.66 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S1 | 2588.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F7 S2 | 2588.32 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SW | 3993.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NW | 4007.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 SE | 3993.96 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 NE | 4007.24 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N1 | 2669.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 N2 | 2669.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S1 | 2656.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F8 S2 | 2656.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SW | 4208.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NW | 4220.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 SE | 4208.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 NE | 4220.26 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N1 | 2846.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 N2 | 2846.73 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S1 | 2834.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP F9 S2 | 2834.99 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SW | 4832.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NW | 4850.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T SE | 4832.87 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T NE | 4850.74 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N1 | 3509.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T N2 | 3509.69 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S1 | 3488.70 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP T S2 | 3488.70 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000289 | 0.325214 |
SINGLE WATER PLANT LOOP | 0.007241 | 8.15 |
Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 0.007241 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000289 |
Design Water Flow Rate [m3/s] | Fan Power at Design Air Flow Rate [W] | Design Air Flow Rate [m3/s] | U-Factor Times Area Value at Design Air Flow Rate [W/C] | |
CENTRAL TOWER | 0.007241 | 3495.43 | 9.29 | 10743.26 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYS1 PUMP | 0.000289 | 36.93 |
PLANT CIRC PUMP | 0.007241 | 2312.31 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW3 | |
G WWALL SWA | GWINDOW2 | |
G NWALL NWA | GWINDOW4 | |
G WWALL NWA | GWINDOW6 | |
G SWALL SEA | GWINDOW1 | |
G EWALL SEA | GWINDOW8 | |
G NWALL NEA | GWINDOW5 | |
G EWALL NEA | GWINDOW7 | |
G NWALL N1A | GWINDOW9 | |
G NWALL N2A | GWINDOW10 | |
G SWALL S1A | GWINDOW11 | |
G SWALL S2A | GWINDOW12 | |
G WWALL C | GWINDOW13 | |
G EWALL C | ENTRANCE DOOR | |
F2 WWALL SWA | F2WINDOW2 | |
F2 SWALL SWA | F2WINDOW3 | |
F2 NWALL NWA | F2WINDOW4 | |
F2 WWALL NWA | F2WINDOW6 | |
F2 EWALL SEA | F2WINDOW8 | |
F2 SWALL SEA | F2WINDOW1 | |
F2 NWALL NEA | F2WINDOW5 | |
F2 EWALL NEA | F2WINDOW7 | |
F2 NWALL N1A | F2WINDOW9 | |
F2 NWALL N2A | F2WINDOW10 | |
F2 SWALL S1A | F2WINDOW11 | |
F2 SWALL S2A | F2WINDOW12 | |
F2 WWALL C | F2WINDOW13 | |
F2 EWALL C | F2WINDOW14 | |
F3 WWALL SWA | F3WINDOW2 | |
F3 SWALL SWA | F3WINDOW3 | |
F3 NWALL NWA | F3WINDOW4 | |
F3 WWALL NWA | F3WINDOW6 | |
F3 EWALL SEA | F3WINDOW8 | |
F3 SWALL SEA | F3WINDOW1 | |
F3 NWALL NEA | F3WINDOW5 | |
F3 EWALL NEA | F3WINDOW7 | |
F3 NWALL N1A | F3WINDOW9 | |
F3 NWALL N2A | F3WINDOW10 | |
F3 SWALL S1A | F3WINDOW11 | |
F3 SWALL S2A | F3WINDOW12 | |
F3 WWALL C | F3WINDOW13 | |
F3 EWALL C | F3WINDOW14 | |
F4 WWALL SWA | F4WINDOW2 | |
F4 SWALL SWA | F4WINDOW3 | |
F4 NWALL NWA | F4WINDOW4 | |
F4 WWALL NWA | F4WINDOW6 | |
F4 EWALL SEA | F4WINDOW8 | |
F4 SWALL SEA | F4WINDOW1 | |
F4 NWALL NEA | F4WINDOW5 | |
F4 EWALL NEA | F4WINDOW7 | |
F4 NWALL N1A | F4WINDOW9 | |
F4 NWALL N2A | F4WINDOW10 | |
F4 SWALL S1A | F4WINDOW11 | |
F4 SWALL S2A | F4WINDOW12 | |
F4 WWALL C | F4WINDOW13 | |
F4 EWALL C | F4WINDOW14 | |
M WWALL SWA | MWINDOW2 | |
M SWALL SWA | MWINDOW3 | |
M NWALL NWA | MWINDOW4 | |
M WWALL NWA | MWINDOW6 | |
M EWALL SEA | MWINDOW8 | |
M SWALL SEA | MWINDOW1 | |
M NWALL NEA | MWINDOW5 | |
M EWALL NEA | MWINDOW7 | |
M NWALL N1A | MWINDOW9 | |
M NWALL N2A | MWINDOW10 | |
M SWALL S1A | MWINDOW11 | |
M SWALL S2A | MWINDOW12 | |
M WWALL C | MWINDOW13 | |
M EWALL C | MWINDOW14 | |
F6 WWALL SWA | F6WINDOW2 | |
F6 SWALL SWA | F6WINDOW3 | |
F6 NWALL NWA | F6WINDOW4 | |
F6 WWALL NWA | F6WINDOW6 | |
F6 EWALL SEA | F6WINDOW8 | |
F6 SWALL SEA | F6WINDOW1 | |
F6 NWALL NEA | F6WINDOW5 | |
F6 EWALL NEA | F6WINDOW7 | |
F6 NWALL N1A | F6WINDOW9 | |
F6 NWALL N2A | F6WINDOW10 | |
F6 SWALL S1A | F6WINDOW11 | |
F6 SWALL S2A | F6WINDOW12 | |
F6 WWALL C | F6WINDOW13 | |
F6 EWALL C | F6WINDOW14 | |
F7 WWALL SWA | F7WINDOW2 | |
F7 SWALL SWA | F7WINDOW3 | |
F7 NWALL NWA | F7WINDOW4 | |
F7 WWALL NWA | F7WINDOW6 | |
F7 EWALL SEA | F7WINDOW8 | |
F7 SWALL SEA | F7WINDOW1 | |
F7 NWALL NEA | F7WINDOW5 | |
F7 EWALL NEA | F7WINDOW7 | |
F7 NWALL N1A | F7WINDOW9 | |
F7 NWALL N2A | F7WINDOW10 | |
F7 SWALL S1A | F7WINDOW11 | |
F7 SWALL S2A | F7WINDOW12 | |
F7 WWALL C | F7WINDOW13 | |
F7 EWALL C | F7WINDOW14 | |
F8 WWALL SWA | F8WINDOW2 | |
F8 SWALL SWA | F8WINDOW3 | |
F8 NWALL NWA | F8WINDOW4 | |
F8 WWALL NWA | F8WINDOW6 | |
F8 EWALL SEA | F8WINDOW8 | |
F8 SWALL SEA | F8WINDOW1 | |
F8 NWALL NEA | F8WINDOW5 | |
F8 EWALL NEA | F8WINDOW7 | |
F8 NWALL N1A | F8WINDOW9 | |
F8 NWALL N2A | F8WINDOW10 | |
F8 SWALL S1A | F8WINDOW11 | |
F8 SWALL S2A | F8WINDOW12 | |
F8 WWALL C | F8WINDOW13 | |
F8 EWALL C | F8WINDOW14 | |
F9 WWALL SWA | F9WINDOW2 | |
F9 SWALL SWA | F9WINDOW3 | |
F9 NWALL NWA | F9WINDOW4 | |
F9 WWALL NWA | F9WINDOW6 | |
F9 EWALL SEA | F9WINDOW8 | |
F9 SWALL SEA | F9WINDOW1 | |
F9 NWALL NEA | F9WINDOW5 | |
F9 EWALL NEA | F9WINDOW7 | |
F9 NWALL N1A | F9WINDOW9 | |
F9 NWALL N2A | F9WINDOW10 | |
F9 SWALL S1A | F9WINDOW11 | |
F9 SWALL S2A | F9WINDOW12 | |
F9 WWALL C | F9WINDOW13 | |
F9 EWALL C | F9WINDOW14 | |
T WWALL SWA | TWINDOW2 | |
T SWALL SWA | TWINDOW3 | |
T NWALL NWA | TWINDOW4 | |
T WWALL NWA | TWINDOW6 | |
T EWALL SEA | TWINDOW8 | |
T SWALL SEA | TWINDOW1 | |
T NWALL NEA | TWINDOW5 | |
T EWALL NEA | TWINDOW7 | |
T NWALL N1A | TWINDOW9 | |
T NWALL N2A | TWINDOW10 | |
T SWALL S1A | TWINDOW11 | |
T SWALL S2A | TWINDOW12 | |
T WWALL C | TWINDOW13 | |
T EWALL C | TWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 19:11:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.12 |
February | 22.06 | 6.58 |
March | 22.61 | 12.40 |
April | 23.21 | 16.79 |
May | 24.03 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.64 | 16.70 |
November | 22.73 | 12.13 |
December | 22.05 | 6.84 |
Annual Sum or Average | 23.32 | 17.04 |
Minimum of Months | 21.93 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.12 |
February | 21.79 | 6.58 |
March | 22.26 | 12.40 |
April | 23.05 | 16.79 |
May | 24.03 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.35 | 24.35 |
October | 23.24 | 16.70 |
November | 22.22 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.14 | 17.04 |
Minimum of Months | 21.74 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 4.12 |
February | 22.39 | 6.58 |
March | 23.18 | 12.40 |
April | 23.79 | 16.79 |
May | 24.33 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 23.97 | 16.70 |
November | 23.20 | 12.13 |
December | 22.43 | 6.84 |
Annual Sum or Average | 23.60 | 17.04 |
Minimum of Months | 22.19 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.12 |
February | 21.76 | 6.58 |
March | 22.17 | 12.40 |
April | 23.00 | 16.79 |
May | 24.01 | 22.07 |
June | 24.38 | 26.01 |
July | 24.41 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.13 | 16.70 |
November | 22.13 | 12.13 |
December | 21.76 | 6.84 |
Annual Sum or Average | 23.11 | 17.04 |
Minimum of Months | 21.72 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.12 |
February | 21.75 | 6.58 |
March | 22.10 | 12.40 |
April | 22.83 | 16.79 |
May | 23.93 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.34 | 24.35 |
October | 23.05 | 16.70 |
November | 22.11 | 12.13 |
December | 21.76 | 6.84 |
Annual Sum or Average | 23.07 | 17.04 |
Minimum of Months | 21.72 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.12 |
February | 21.75 | 6.58 |
March | 22.09 | 12.40 |
April | 22.83 | 16.79 |
May | 23.92 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.34 | 24.35 |
October | 23.04 | 16.70 |
November | 22.10 | 12.13 |
December | 21.76 | 6.84 |
Annual Sum or Average | 23.07 | 17.04 |
Minimum of Months | 21.72 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 4.12 |
February | 22.06 | 6.58 |
March | 22.53 | 12.40 |
April | 23.09 | 16.79 |
May | 23.97 | 22.07 |
June | 24.37 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.38 | 24.35 |
October | 23.62 | 16.70 |
November | 22.74 | 12.13 |
December | 22.08 | 6.84 |
Annual Sum or Average | 23.31 | 17.04 |
Minimum of Months | 21.94 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 4.12 |
February | 22.09 | 6.58 |
March | 22.58 | 12.40 |
April | 23.14 | 16.79 |
May | 24.00 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.38 | 24.35 |
October | 23.66 | 16.70 |
November | 22.80 | 12.13 |
December | 22.12 | 6.84 |
Annual Sum or Average | 23.33 | 17.04 |
Minimum of Months | 21.96 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.68 | 4.12 |
February | 17.57 | 6.58 |
March | 19.97 | 12.40 |
April | 21.81 | 16.79 |
May | 24.11 | 22.07 |
June | 26.17 | 26.01 |
July | 27.05 | 28.31 |
August | 26.80 | 27.55 |
September | 25.63 | 24.35 |
October | 22.13 | 16.70 |
November | 20.00 | 12.13 |
December | 17.75 | 6.84 |
Annual Sum or Average | 22.16 | 17.04 |
Minimum of Months | 16.68 | 4.12 |
Maximum of Months | 27.05 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.12 |
February | 22.34 | 6.58 |
March | 23.19 | 12.40 |
April | 23.75 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 24.17 | 16.70 |
November | 23.30 | 12.13 |
December | 22.25 | 6.84 |
Annual Sum or Average | 23.58 | 17.04 |
Minimum of Months | 22.09 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.12 |
February | 21.89 | 6.58 |
March | 22.70 | 12.40 |
April | 23.52 | 16.79 |
May | 24.26 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 23.80 | 16.70 |
November | 22.64 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.34 | 17.04 |
Minimum of Months | 21.78 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 4.12 |
February | 22.41 | 6.58 |
March | 23.30 | 12.40 |
April | 23.85 | 16.79 |
May | 24.31 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 24.22 | 16.70 |
November | 23.39 | 12.13 |
December | 22.34 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 22.10 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.85 | 6.58 |
March | 22.57 | 12.40 |
April | 23.47 | 16.79 |
May | 24.26 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 23.70 | 16.70 |
November | 22.52 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.30 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.12 |
February | 21.85 | 6.58 |
March | 22.56 | 12.40 |
April | 23.36 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.68 | 16.70 |
November | 22.56 | 12.13 |
December | 21.81 | 6.84 |
Annual Sum or Average | 23.29 | 17.04 |
Minimum of Months | 21.77 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.12 |
February | 21.85 | 6.58 |
March | 22.55 | 12.40 |
April | 23.35 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.67 | 16.70 |
November | 22.55 | 12.13 |
December | 21.81 | 6.84 |
Annual Sum or Average | 23.28 | 17.04 |
Minimum of Months | 21.77 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 4.12 |
February | 22.43 | 6.58 |
March | 23.19 | 12.40 |
April | 23.68 | 16.79 |
May | 24.24 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.18 | 16.70 |
November | 23.41 | 12.13 |
December | 22.41 | 6.84 |
Annual Sum or Average | 23.62 | 17.04 |
Minimum of Months | 22.18 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 4.12 |
February | 22.44 | 6.58 |
March | 23.21 | 12.40 |
April | 23.70 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.19 | 16.70 |
November | 23.43 | 12.13 |
December | 22.43 | 6.84 |
Annual Sum or Average | 23.62 | 17.04 |
Minimum of Months | 22.18 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F2 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 4.12 |
February | 22.11 | 6.58 |
March | 23.58 | 12.40 |
April | 24.60 | 16.79 |
May | 25.76 | 22.07 |
June | 26.44 | 26.01 |
July | 26.67 | 28.31 |
August | 26.61 | 27.55 |
September | 26.29 | 24.35 |
October | 25.04 | 16.70 |
November | 23.66 | 12.13 |
December | 22.19 | 6.84 |
Annual Sum or Average | 24.56 | 17.04 |
Minimum of Months | 21.65 | 4.12 |
Maximum of Months | 26.67 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 4.12 |
February | 22.38 | 6.58 |
March | 23.27 | 12.40 |
April | 23.81 | 16.79 |
May | 24.28 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 24.23 | 16.70 |
November | 23.39 | 12.13 |
December | 22.25 | 6.84 |
Annual Sum or Average | 23.61 | 17.04 |
Minimum of Months | 22.09 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.90 | 6.58 |
March | 22.79 | 12.40 |
April | 23.59 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 23.90 | 16.70 |
November | 22.76 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.37 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.12 |
February | 22.37 | 6.58 |
March | 23.23 | 12.40 |
April | 23.82 | 16.79 |
May | 24.30 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.21 | 16.70 |
November | 23.36 | 12.13 |
December | 22.24 | 6.84 |
Annual Sum or Average | 23.60 | 17.04 |
Minimum of Months | 22.04 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.86 | 6.58 |
March | 22.67 | 12.40 |
April | 23.55 | 16.79 |
May | 24.28 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.82 | 16.70 |
November | 22.65 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.34 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.89 | 6.58 |
March | 22.70 | 12.40 |
April | 23.47 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.84 | 16.70 |
November | 22.72 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.34 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.12 |
February | 21.88 | 6.58 |
March | 22.69 | 12.40 |
April | 23.47 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.83 | 16.70 |
November | 22.71 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.34 | 17.04 |
Minimum of Months | 21.78 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.12 |
February | 22.51 | 6.58 |
March | 23.33 | 12.40 |
April | 23.79 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.25 | 16.70 |
November | 23.54 | 12.13 |
December | 22.49 | 6.84 |
Annual Sum or Average | 23.67 | 17.04 |
Minimum of Months | 22.21 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.12 |
February | 22.51 | 6.58 |
March | 23.34 | 12.40 |
April | 23.79 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.25 | 16.70 |
November | 23.54 | 12.13 |
December | 22.49 | 6.84 |
Annual Sum or Average | 23.67 | 17.04 |
Minimum of Months | 22.21 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F3 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.12 |
February | 22.53 | 6.58 |
March | 24.01 | 12.40 |
April | 24.98 | 16.79 |
May | 26.03 | 22.07 |
June | 26.51 | 26.01 |
July | 26.69 | 28.31 |
August | 26.64 | 27.55 |
September | 26.37 | 24.35 |
October | 25.44 | 16.70 |
November | 24.12 | 12.13 |
December | 22.59 | 6.84 |
Annual Sum or Average | 24.84 | 17.04 |
Minimum of Months | 22.06 | 4.12 |
Maximum of Months | 26.69 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.12 |
February | 22.37 | 6.58 |
March | 23.26 | 12.40 |
April | 23.81 | 16.79 |
May | 24.29 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 24.23 | 16.70 |
November | 23.40 | 12.13 |
December | 22.22 | 6.84 |
Annual Sum or Average | 23.61 | 17.04 |
Minimum of Months | 22.06 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.12 |
February | 21.91 | 6.58 |
March | 22.80 | 12.40 |
April | 23.60 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 23.95 | 16.70 |
November | 22.80 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.38 | 17.04 |
Minimum of Months | 21.78 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.12 |
February | 22.35 | 6.58 |
March | 23.19 | 12.40 |
April | 23.80 | 16.79 |
May | 24.30 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.22 | 16.70 |
November | 23.36 | 12.13 |
December | 22.18 | 6.84 |
Annual Sum or Average | 23.59 | 17.04 |
Minimum of Months | 22.00 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.87 | 6.58 |
March | 22.67 | 12.40 |
April | 23.55 | 16.79 |
May | 24.28 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.87 | 16.70 |
November | 22.70 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.35 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.90 | 6.58 |
March | 22.74 | 12.40 |
April | 23.50 | 16.79 |
May | 24.26 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.91 | 16.70 |
November | 22.80 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.36 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.90 | 6.58 |
March | 22.73 | 12.40 |
April | 23.50 | 16.79 |
May | 24.26 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.90 | 16.70 |
November | 22.79 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.36 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 4.12 |
February | 22.52 | 6.58 |
March | 23.35 | 12.40 |
April | 23.81 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.26 | 16.70 |
November | 23.57 | 12.13 |
December | 22.47 | 6.84 |
Annual Sum or Average | 23.68 | 17.04 |
Minimum of Months | 22.19 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 4.12 |
February | 22.52 | 6.58 |
March | 23.35 | 12.40 |
April | 23.81 | 16.79 |
May | 24.28 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.26 | 16.70 |
November | 23.57 | 12.13 |
December | 22.47 | 6.84 |
Annual Sum or Average | 23.68 | 17.04 |
Minimum of Months | 22.19 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F4 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 4.12 |
February | 22.65 | 6.58 |
March | 24.15 | 12.40 |
April | 25.11 | 16.79 |
May | 26.14 | 22.07 |
June | 26.59 | 26.01 |
July | 26.76 | 28.31 |
August | 26.71 | 27.55 |
September | 26.45 | 24.35 |
October | 25.60 | 16.70 |
November | 24.29 | 12.13 |
December | 22.70 | 6.84 |
Annual Sum or Average | 24.95 | 17.04 |
Minimum of Months | 22.16 | 4.12 |
Maximum of Months | 26.76 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.12 |
February | 22.35 | 6.58 |
March | 23.23 | 12.40 |
April | 23.79 | 16.79 |
May | 24.28 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 24.23 | 16.70 |
November | 23.40 | 12.13 |
December | 22.19 | 6.84 |
Annual Sum or Average | 23.60 | 17.04 |
Minimum of Months | 22.04 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.12 |
February | 21.90 | 6.58 |
March | 22.78 | 12.40 |
April | 23.58 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 23.95 | 16.70 |
November | 22.82 | 12.13 |
December | 21.81 | 6.84 |
Annual Sum or Average | 23.38 | 17.04 |
Minimum of Months | 21.78 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 4.12 |
February | 22.32 | 6.58 |
March | 23.16 | 12.40 |
April | 23.78 | 16.79 |
May | 24.29 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.21 | 16.70 |
November | 23.35 | 12.13 |
December | 22.15 | 6.84 |
Annual Sum or Average | 23.58 | 17.04 |
Minimum of Months | 21.98 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.86 | 6.58 |
March | 22.66 | 12.40 |
April | 23.54 | 16.79 |
May | 24.27 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.88 | 16.70 |
November | 22.71 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.35 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.90 | 6.58 |
March | 22.74 | 12.40 |
April | 23.50 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.93 | 16.70 |
November | 22.83 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.37 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 4.12 |
February | 21.90 | 6.58 |
March | 22.73 | 12.40 |
April | 23.50 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.92 | 16.70 |
November | 22.82 | 12.13 |
December | 21.82 | 6.84 |
Annual Sum or Average | 23.36 | 17.04 |
Minimum of Months | 21.79 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 4.12 |
February | 22.51 | 6.58 |
March | 23.34 | 12.40 |
April | 23.80 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.27 | 16.70 |
November | 23.57 | 12.13 |
December | 22.45 | 6.84 |
Annual Sum or Average | 23.67 | 17.04 |
Minimum of Months | 22.17 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 4.12 |
February | 22.51 | 6.58 |
March | 23.33 | 12.40 |
April | 23.80 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.40 | 24.35 |
October | 24.26 | 16.70 |
November | 23.56 | 12.13 |
December | 22.45 | 6.84 |
Annual Sum or Average | 23.67 | 17.04 |
Minimum of Months | 22.17 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 4.12 |
February | 23.21 | 6.58 |
March | 24.69 | 12.40 |
April | 25.65 | 16.79 |
May | 26.67 | 22.07 |
June | 27.12 | 26.01 |
July | 27.29 | 28.31 |
August | 27.24 | 27.55 |
September | 26.98 | 24.35 |
October | 26.16 | 16.70 |
November | 24.85 | 12.13 |
December | 23.25 | 6.84 |
Annual Sum or Average | 25.50 | 17.04 |
Minimum of Months | 22.69 | 4.12 |
Maximum of Months | 27.29 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.12 |
February | 22.28 | 6.58 |
March | 23.14 | 12.40 |
April | 23.73 | 16.79 |
May | 24.26 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 24.20 | 16.70 |
November | 23.33 | 12.13 |
December | 22.12 | 6.84 |
Annual Sum or Average | 23.56 | 17.04 |
Minimum of Months | 21.99 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.87 | 6.58 |
March | 22.68 | 12.40 |
April | 23.51 | 16.79 |
May | 24.24 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.89 | 16.70 |
November | 22.74 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.34 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 4.12 |
February | 22.26 | 6.58 |
March | 23.06 | 12.40 |
April | 23.71 | 16.79 |
May | 24.27 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.18 | 16.70 |
November | 23.29 | 12.13 |
December | 22.09 | 6.84 |
Annual Sum or Average | 23.54 | 17.04 |
Minimum of Months | 21.94 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.12 |
February | 21.83 | 6.58 |
March | 22.56 | 12.40 |
April | 23.47 | 16.79 |
May | 24.25 | 22.07 |
June | 24.40 | 26.01 |
July | 24.41 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.81 | 16.70 |
November | 22.64 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.31 | 17.04 |
Minimum of Months | 21.74 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.12 |
February | 21.87 | 6.58 |
March | 22.65 | 12.40 |
April | 23.43 | 16.79 |
May | 24.23 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.86 | 16.70 |
November | 22.75 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.33 | 17.04 |
Minimum of Months | 21.77 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.12 |
February | 21.87 | 6.58 |
March | 22.63 | 12.40 |
April | 23.43 | 16.79 |
May | 24.23 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.85 | 16.70 |
November | 22.74 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.33 | 17.04 |
Minimum of Months | 21.77 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 4.12 |
February | 22.43 | 6.58 |
March | 23.23 | 12.40 |
April | 23.73 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.24 | 16.70 |
November | 23.50 | 12.13 |
December | 22.36 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 22.11 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 4.12 |
February | 22.43 | 6.58 |
March | 23.23 | 12.40 |
April | 23.73 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.24 | 16.70 |
November | 23.50 | 12.13 |
December | 22.36 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 22.11 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F6 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 4.12 |
February | 22.55 | 6.58 |
March | 24.03 | 12.40 |
April | 25.02 | 16.79 |
May | 26.10 | 22.07 |
June | 26.58 | 26.01 |
July | 26.75 | 28.31 |
August | 26.70 | 27.55 |
September | 26.43 | 24.35 |
October | 25.55 | 16.70 |
November | 24.22 | 12.13 |
December | 22.60 | 6.84 |
Annual Sum or Average | 24.90 | 17.04 |
Minimum of Months | 22.05 | 4.12 |
Maximum of Months | 26.75 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 4.12 |
February | 22.23 | 6.58 |
March | 23.06 | 12.40 |
April | 23.68 | 16.79 |
May | 24.24 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 24.17 | 16.70 |
November | 23.29 | 12.13 |
December | 22.08 | 6.84 |
Annual Sum or Average | 23.53 | 17.04 |
Minimum of Months | 21.96 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.85 | 6.58 |
March | 22.61 | 12.40 |
April | 23.46 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.83 | 16.70 |
November | 22.69 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.32 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 4.12 |
February | 22.21 | 6.58 |
March | 22.98 | 12.40 |
April | 23.66 | 16.79 |
May | 24.25 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.15 | 16.70 |
November | 23.24 | 12.13 |
December | 22.04 | 6.84 |
Annual Sum or Average | 23.51 | 17.04 |
Minimum of Months | 21.91 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.82 | 6.58 |
March | 22.49 | 12.40 |
April | 23.42 | 16.79 |
May | 24.23 | 22.07 |
June | 24.39 | 26.01 |
July | 24.41 | 28.31 |
August | 24.40 | 27.55 |
September | 24.37 | 24.35 |
October | 23.75 | 16.70 |
November | 22.59 | 12.13 |
December | 21.77 | 6.84 |
Annual Sum or Average | 23.29 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.85 | 6.58 |
March | 22.57 | 12.40 |
April | 23.38 | 16.79 |
May | 24.21 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.81 | 16.70 |
November | 22.68 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.31 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.85 | 6.58 |
March | 22.56 | 12.40 |
April | 23.38 | 16.79 |
May | 24.21 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.80 | 16.70 |
November | 22.67 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.30 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 4.12 |
February | 22.37 | 6.58 |
March | 23.16 | 12.40 |
April | 23.67 | 16.79 |
May | 24.23 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.22 | 16.70 |
November | 23.45 | 12.13 |
December | 22.30 | 6.84 |
Annual Sum or Average | 23.59 | 17.04 |
Minimum of Months | 22.07 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 4.12 |
February | 22.37 | 6.58 |
March | 23.15 | 12.40 |
April | 23.67 | 16.79 |
May | 24.23 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.22 | 16.70 |
November | 23.44 | 12.13 |
December | 22.29 | 6.84 |
Annual Sum or Average | 23.59 | 17.04 |
Minimum of Months | 22.07 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F7 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 4.12 |
February | 22.40 | 6.58 |
March | 23.86 | 12.40 |
April | 24.88 | 16.79 |
May | 26.00 | 22.07 |
June | 26.51 | 26.01 |
July | 26.69 | 28.31 |
August | 26.63 | 27.55 |
September | 26.36 | 24.35 |
October | 25.43 | 16.70 |
November | 24.07 | 12.13 |
December | 22.44 | 6.84 |
Annual Sum or Average | 24.77 | 17.04 |
Minimum of Months | 21.90 | 4.12 |
Maximum of Months | 26.69 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 4.12 |
February | 22.18 | 6.58 |
March | 23.00 | 12.40 |
April | 23.64 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 24.15 | 16.70 |
November | 23.25 | 12.13 |
December | 22.04 | 6.84 |
Annual Sum or Average | 23.50 | 17.04 |
Minimum of Months | 21.94 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.12 |
February | 21.83 | 6.58 |
March | 22.55 | 12.40 |
April | 23.43 | 16.79 |
May | 24.21 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.37 | 24.35 |
October | 23.79 | 16.70 |
November | 22.64 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.30 | 17.04 |
Minimum of Months | 21.74 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.12 |
February | 22.17 | 6.58 |
March | 22.92 | 12.40 |
April | 23.62 | 16.79 |
May | 24.24 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.38 | 24.35 |
October | 24.13 | 16.70 |
November | 23.20 | 12.13 |
December | 22.01 | 6.84 |
Annual Sum or Average | 23.48 | 17.04 |
Minimum of Months | 21.89 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.80 | 6.58 |
March | 22.44 | 12.40 |
April | 23.39 | 16.79 |
May | 24.21 | 22.07 |
June | 24.39 | 26.01 |
July | 24.41 | 28.31 |
August | 24.40 | 27.55 |
September | 24.37 | 24.35 |
October | 23.70 | 16.70 |
November | 22.54 | 12.13 |
December | 21.76 | 6.84 |
Annual Sum or Average | 23.27 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.84 | 6.58 |
March | 22.52 | 12.40 |
April | 23.35 | 16.79 |
May | 24.19 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.76 | 16.70 |
November | 22.63 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.29 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.84 | 6.58 |
March | 22.51 | 12.40 |
April | 23.34 | 16.79 |
May | 24.19 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.75 | 16.70 |
November | 22.62 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.28 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.12 |
February | 22.33 | 6.58 |
March | 23.09 | 12.40 |
April | 23.63 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.20 | 16.70 |
November | 23.40 | 12.13 |
December | 22.24 | 6.84 |
Annual Sum or Average | 23.57 | 17.04 |
Minimum of Months | 22.04 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 4.12 |
February | 22.32 | 6.58 |
March | 23.09 | 12.40 |
April | 23.63 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.20 | 16.70 |
November | 23.40 | 12.13 |
December | 22.24 | 6.84 |
Annual Sum or Average | 23.57 | 17.04 |
Minimum of Months | 22.04 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F8 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 4.12 |
February | 22.31 | 6.58 |
March | 23.77 | 12.40 |
April | 24.82 | 16.79 |
May | 25.98 | 22.07 |
June | 26.51 | 26.01 |
July | 26.70 | 28.31 |
August | 26.64 | 27.55 |
September | 26.35 | 24.35 |
October | 25.36 | 16.70 |
November | 23.98 | 12.13 |
December | 22.36 | 6.84 |
Annual Sum or Average | 24.73 | 17.04 |
Minimum of Months | 21.81 | 4.12 |
Maximum of Months | 26.70 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 4.12 |
February | 22.16 | 6.58 |
March | 22.94 | 12.40 |
April | 23.61 | 16.79 |
May | 24.21 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.38 | 24.35 |
October | 24.10 | 16.70 |
November | 23.19 | 12.13 |
December | 22.01 | 6.84 |
Annual Sum or Average | 23.48 | 17.04 |
Minimum of Months | 21.91 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.12 |
February | 21.83 | 6.58 |
March | 22.52 | 12.40 |
April | 23.41 | 16.79 |
May | 24.20 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.73 | 16.70 |
November | 22.59 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.29 | 17.04 |
Minimum of Months | 21.74 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.12 |
February | 22.14 | 6.58 |
March | 22.86 | 12.40 |
April | 23.59 | 16.79 |
May | 24.22 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 24.08 | 16.70 |
November | 23.14 | 12.13 |
December | 21.98 | 6.84 |
Annual Sum or Average | 23.46 | 17.04 |
Minimum of Months | 21.87 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.80 | 6.58 |
March | 22.41 | 12.40 |
April | 23.37 | 16.79 |
May | 24.20 | 22.07 |
June | 24.39 | 26.01 |
July | 24.41 | 28.31 |
August | 24.40 | 27.55 |
September | 24.37 | 24.35 |
October | 23.63 | 16.70 |
November | 22.48 | 12.13 |
December | 21.76 | 6.84 |
Annual Sum or Average | 23.25 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.83 | 6.58 |
March | 22.49 | 12.40 |
April | 23.34 | 16.79 |
May | 24.18 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.70 | 16.70 |
November | 22.57 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.27 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.83 | 6.58 |
March | 22.48 | 12.40 |
April | 23.33 | 16.79 |
May | 24.18 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.69 | 16.70 |
November | 22.56 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.27 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.12 |
February | 22.28 | 6.58 |
March | 23.03 | 12.40 |
April | 23.60 | 16.79 |
May | 24.20 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.16 | 16.70 |
November | 23.33 | 12.13 |
December | 22.18 | 6.84 |
Annual Sum or Average | 23.54 | 17.04 |
Minimum of Months | 22.00 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.12 |
February | 22.28 | 6.58 |
March | 23.03 | 12.40 |
April | 23.60 | 16.79 |
May | 24.20 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.41 | 27.55 |
September | 24.39 | 24.35 |
October | 24.16 | 16.70 |
November | 23.32 | 12.13 |
December | 22.18 | 6.84 |
Annual Sum or Average | 23.54 | 17.04 |
Minimum of Months | 22.00 | 4.12 |
Maximum of Months | 24.41 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: F9 CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 4.12 |
February | 22.20 | 6.58 |
March | 23.69 | 12.40 |
April | 24.80 | 16.79 |
May | 26.02 | 22.07 |
June | 26.61 | 26.01 |
July | 26.82 | 28.31 |
August | 26.75 | 27.55 |
September | 26.42 | 24.35 |
October | 25.29 | 16.70 |
November | 23.85 | 12.13 |
December | 22.23 | 6.84 |
Annual Sum or Average | 24.71 | 17.04 |
Minimum of Months | 21.67 | 4.12 |
Maximum of Months | 26.82 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 4.12 |
February | 22.15 | 6.58 |
March | 22.83 | 12.40 |
April | 23.48 | 16.79 |
May | 24.15 | 22.07 |
June | 24.37 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.35 | 24.35 |
October | 23.82 | 16.70 |
November | 22.97 | 12.13 |
December | 22.08 | 6.84 |
Annual Sum or Average | 23.42 | 17.04 |
Minimum of Months | 21.95 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.87 | 6.58 |
March | 22.51 | 12.40 |
April | 23.34 | 16.79 |
May | 24.13 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.38 | 27.55 |
September | 24.33 | 24.35 |
October | 23.51 | 16.70 |
November | 22.52 | 12.13 |
December | 21.81 | 6.84 |
Annual Sum or Average | 23.25 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.90 | 4.12 |
February | 22.13 | 6.58 |
March | 22.78 | 12.40 |
April | 23.49 | 16.79 |
May | 24.16 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.36 | 24.35 |
October | 23.80 | 16.70 |
November | 22.94 | 12.13 |
December | 22.05 | 6.84 |
Annual Sum or Average | 23.40 | 17.04 |
Minimum of Months | 21.90 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.12 |
February | 21.83 | 6.58 |
March | 22.41 | 12.40 |
April | 23.32 | 16.79 |
May | 24.13 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.34 | 24.35 |
October | 23.43 | 16.70 |
November | 22.43 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.22 | 17.04 |
Minimum of Months | 21.74 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.86 | 6.58 |
March | 22.46 | 12.40 |
April | 23.28 | 16.79 |
May | 24.12 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.38 | 27.55 |
September | 24.33 | 24.35 |
October | 23.48 | 16.70 |
November | 22.48 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.23 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 4.12 |
February | 21.86 | 6.58 |
March | 22.45 | 12.40 |
April | 23.28 | 16.79 |
May | 24.12 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.38 | 27.55 |
September | 24.33 | 24.35 |
October | 23.47 | 16.70 |
November | 22.47 | 12.13 |
December | 21.80 | 6.84 |
Annual Sum or Average | 23.23 | 17.04 |
Minimum of Months | 21.76 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 4.12 |
February | 22.24 | 6.58 |
March | 22.93 | 12.40 |
April | 23.50 | 16.79 |
May | 24.15 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.91 | 16.70 |
November | 23.09 | 12.13 |
December | 22.20 | 6.84 |
Annual Sum or Average | 23.47 | 17.04 |
Minimum of Months | 22.03 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 4.12 |
February | 22.24 | 6.58 |
March | 22.93 | 12.40 |
April | 23.50 | 16.79 |
May | 24.16 | 22.07 |
June | 24.38 | 26.01 |
July | 24.40 | 28.31 |
August | 24.39 | 27.55 |
September | 24.36 | 24.35 |
October | 23.91 | 16.70 |
November | 23.09 | 12.13 |
December | 22.19 | 6.84 |
Annual Sum or Average | 23.47 | 17.04 |
Minimum of Months | 22.02 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 19:11:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 22.37 | 6.58 |
March | 24.07 | 12.40 |
April | 25.35 | 16.79 |
May | 26.75 | 22.07 |
June | 27.54 | 26.01 |
July | 27.83 | 28.31 |
August | 27.71 | 27.55 |
September | 27.21 | 24.35 |
October | 25.63 | 16.70 |
November | 24.00 | 12.13 |
December | 22.33 | 6.84 |
Annual Sum or Average | 25.22 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 27.83 | 28.31 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 19:11:14
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY {AT MAX/MIN} [W] | |
January | 0.253136E+12 | 171519.599 | 06-JAN-18:00 | 13120.457 | 57042.023 | 19000.275 | 67655.596 | 0.000 | 10364.000 | 2349.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.211462E+12 | 132409.459 | 12-FEB-18:15 | 13120.457 | 57042.023 | 19000.275 | 28545.653 | 0.000 | 10364.000 | 2349.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.209223E+12 | 134902.356 | 27-MAR-16:15 | 11327.174 | 57142.088 | 19000.275 | 0.000 | 41321.728 | 0.000 | 2349.239 | 1766.655 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.212866E+12 | 156402.113 | 30-APR-16:30 | 11327.174 | 57042.023 | 19000.275 | 0.000 | 61900.326 | 0.000 | 2349.239 | 2795.265 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.272564E+12 | 174857.616 | 31-MAY-17:30 | 13120.457 | 57042.023 | 19000.275 | 0.000 | 77862.182 | 0.000 | 2349.239 | 3495.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.320073E+12 | 178286.671 | 25-JUN-17:30 | 13120.457 | 57042.023 | 19000.275 | 0.000 | 81484.123 | 0.000 | 2349.239 | 3302.545 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.353750E+12 | 180896.339 | 23-JUL-17:15 | 13120.457 | 57042.023 | 19000.275 | 0.000 | 83901.102 | 0.000 | 2349.239 | 3495.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.344438E+12 | 181326.709 | 29-AUG-18:30 | 14401.373 | 51749.961 | 19000.275 | 0.000 | 78343.458 | 10364.000 | 2349.239 | 3357.378 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.308383E+12 | 178725.300 | 22-SEP-17:00 | 13120.457 | 57042.023 | 19000.275 | 0.000 | 71520.004 | 10364.000 | 2349.239 | 3341.293 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.227236E+12 | 170284.638 | 01-OCT-17:45 | 13120.457 | 57042.023 | 19000.275 | 0.000 | 63227.189 | 10364.000 | 2349.239 | 3193.446 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.204992E+12 | 123146.051 | 30-NOV-17:45 | 11327.174 | 57142.088 | 19000.275 | 20968.116 | 0.000 | 10364.000 | 2349.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.227782E+12 | 135028.194 | 08-DEC-17:15 | 11327.174 | 57142.088 | 19000.275 | 32850.221 | 0.000 | 10364.000 | 2349.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.314591E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||||
Minimum of Months | 0.204992E+12 | 123146.051 | 11327.174 | 51749.961 | 19000.275 | 0.000 | 0.000 | 0.000 | 2349.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.353750E+12 | 181326.709 | 14401.373 | 57142.088 | 19000.275 | 67655.596 | 83901.102 | 10364.000 | 2349.239 | 3495.431 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: COMPONENTS OF PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 19:11:14
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.306655E+12 | 370648.491 | 31-JAN-06:00 | 0.000 | 0.000 | 0.000 | 370648.491 | 75821.852 | 75821.852 | 294826.639 |
February | 0.205451E+12 | 306277.182 | 12-FEB-06:30 | 0.000 | 0.000 | 0.000 | 306277.182 | 73531.063 | 73531.063 | 232746.120 |
March | 0.119878E+12 | 179777.727 | 10-MAR-06:00 | 0.000 | 0.000 | 0.000 | 179777.727 | 74995.779 | 74995.779 | 104781.948 |
April | 0.923372E+11 | 132694.883 | 13-APR-05:45 | 0.000 | 0.000 | 0.000 | 132694.883 | 71256.106 | 71256.106 | 61438.778 |
May | 0.822138E+11 | 73553.565 | 01-MAY-06:00 | 0.000 | 0.000 | 0.000 | 73553.565 | 73553.565 | 73553.565 | 0.000 |
June | 0.736141E+11 | 71406.264 | 01-JUN-06:45 | 0.000 | 0.000 | 0.000 | 71406.264 | 71406.264 | 71406.264 | 0.000 |
July | 0.723490E+11 | 69937.219 | 01-JUL-06:45 | 0.000 | 0.000 | 0.000 | 69937.219 | 69937.219 | 69937.219 | 0.000 |
August | 0.721356E+11 | 69840.704 | 31-AUG-06:00 | 0.000 | 0.000 | 0.000 | 69840.704 | 69840.704 | 69840.704 | 0.000 |
September | 0.729670E+11 | 71184.239 | 30-SEP-06:00 | 0.000 | 0.000 | 0.000 | 71184.239 | 71184.239 | 71184.239 | 0.000 |
October | 0.813604E+11 | 73268.645 | 31-OCT-06:00 | 0.000 | 0.000 | 0.000 | 73268.645 | 73268.645 | 73268.645 | 0.000 |
November | 0.103480E+12 | 145622.816 | 30-NOV-13:30 | 0.000 | 0.000 | 0.000 | 145622.816 | 32467.427 | 32467.427 | 113155.389 |
December | 0.194040E+12 | 254497.265 | 09-DEC-06:00 | 0.000 | 0.000 | 0.000 | 254497.265 | 74137.566 | 74137.566 | 180359.699 |
Annual Sum or Average | 0.147648E+13 | 0.000 | 0.000 | 0.000 | ||||||
Minimum of Months | 0.721356E+11 | 69840.704 | 0.000 | 0.000 | 0.000 | 69840.704 | 32467.427 | 32467.427 | 0.000 | |
Maximum of Months | 0.306655E+12 | 370648.491 | 0.000 | 0.000 | 0.000 | 370648.491 | 75821.852 | 75821.852 | 294826.639 |