Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Memphis International Ap TN USA TMY3 WMO#=723340
Simulation Timestamp: 2015-09-09 18:48:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1651.30 | 526.80 | 584.74 |
Net Site Energy | 1651.30 | 526.80 | 584.74 |
Total Source Energy | 4830.37 | 1540.98 | 1710.48 |
Net Source Energy | 4830.37 | 1540.98 | 1710.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 191.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 206.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 356.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1459.61 | 191.69 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 191.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 206.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 220.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 356.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 277.39 | 67.88 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 516.86 | 67.88 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 249.90 | 61.15 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.64 | 61.15 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1459.61 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1459.61 | 100.00 |
Total On-Site and Utility Electric Sources | 1459.61 | 100.00 |
Total Electricity End Uses | 1459.61 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 57.25 |
Time Setpoint Not Met During Occupied Cooling | 2.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2299.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Memphis International Ap TN USA TMY3 WMO#=723340 |
Weather File | Memphis International Ap TN USA TMY3 WMO#=723340 |
Latitude [deg] | 35.07 |
Longitude [deg] | -90.0 |
Elevation [m] | 81.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-16:45 | 31-JAN-07:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 109600.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29187.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6993.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 21039.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 88227.61 | 109600.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 109600.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29187.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 3538.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 738.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6993.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 21039.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 207.80 | 0.00 | 0.00 | 0.00 |
Cooling | 653.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 698.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1129.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4622.57 | 207.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.58 | 0.00 | 0.00 | 0.00 |
Cooling | 231.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 247.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 399.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1636.90 | 73.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.58 | 0.00 | 0.00 | 0.00 |
Cooling | 231.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 247.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 399.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1636.90 | 73.58 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -8.30 | 0.00 | -8.30 | Wetbulb [C] | 4.10 | 0.00 |
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 35.60 | 9.20 | 25.20 | Wetbulb [C] | 3.80 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.62_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 112.97 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 193.95 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.76 | 83.76 | 40.14 | |
Exterior Lighting Total | 2553.00 | 40.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3767.30 | 2640.14 | 1127.16 | 0.70 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3702.47 | 2609.14 | 1093.33 | 0.70 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8451.94 | 6494.07 | 1957.87 | 0.77 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3088.81 | 2141.83 | 946.98 | 0.69 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2528.79 | 1714.86 | 813.93 | 0.68 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2516.16 | 1704.92 | 811.24 | 0.68 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.00 | 1715.22 | 821.78 | 0.68 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2607.12 | 1762.63 | 844.49 | 0.68 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9252.74 | 6611.48 | 2641.26 | 0.71 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9154.69 | 6550.64 | 2604.05 | 0.72 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8520.50 | 5978.81 | 2541.69 | 0.70 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7851.28 | 5549.27 | 2302.01 | 0.71 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6313.56 | 4382.26 | 1931.30 | 0.69 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6293.22 | 4366.15 | 1927.07 | 0.69 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6580.96 | 4517.77 | 2063.19 | 0.69 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6585.97 | 4525.58 | 2060.39 | 0.69 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6248.86 | 4537.01 | 1711.85 | 0.73 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6040.99 | 4391.01 | 1649.99 | 0.73 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5878.18 | 4232.17 | 1646.00 | 0.72 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5466.01 | 3901.29 | 1564.72 | 0.71 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4434.14 | 3140.72 | 1293.42 | 0.71 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4437.35 | 3143.35 | 1294.01 | 0.71 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4830.05 | 3455.43 | 1374.62 | 0.72 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4831.29 | 3459.17 | 1372.12 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3635.8 | 3.30 | 11.27 | 11.74 | 11.26 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3571.4 | 3.30 | 11.25 | 11.71 | 11.23 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8084.4 | 3.18 | 10.85 | 11.28 | 10.64 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2983.9 | 3.32 | 11.32 | 11.79 | 11.34 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2447.8 | 3.35 | 11.42 | 11.90 | 11.49 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2435.7 | 3.35 | 11.42 | 11.90 | 11.49 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2456.4 | 3.35 | 11.43 | 11.92 | 11.51 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2524.3 | 3.35 | 11.43 | 11.92 | 11.51 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8913.6 | 3.28 | 11.18 | 11.65 | 11.13 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8818.0 | 3.28 | 11.18 | 11.64 | 11.12 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8222.1 | 3.30 | 11.26 | 11.73 | 11.25 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7571.2 | 3.29 | 11.23 | 11.70 | 11.20 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6098.5 | 3.32 | 11.31 | 11.79 | 11.33 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6079.1 | 3.32 | 11.32 | 11.79 | 11.33 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6363.2 | 3.33 | 11.36 | 11.84 | 11.40 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6367.5 | 3.33 | 11.36 | 11.84 | 11.40 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6010.7 | 3.26 | 11.11 | 11.57 | 11.02 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5810.1 | 3.25 | 11.11 | 11.56 | 11.01 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5658.7 | 3.27 | 11.15 | 11.61 | 11.08 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5266.2 | 3.28 | 11.19 | 11.65 | 11.14 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4275.1 | 3.29 | 11.22 | 11.69 | 11.19 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4278.2 | 3.29 | 11.22 | 11.69 | 11.19 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4652.5 | 3.28 | 11.18 | 11.64 | 11.12 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4653.3 | 3.27 | 11.17 | 11.64 | 11.12 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2794.72 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2775.02 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5014.02 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2775.02 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2059.94 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2059.94 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2048.18 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2160.82 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 5568.67 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 5601.61 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 5568.67 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 5601.61 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3776.78 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3776.78 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3745.54 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3745.54 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4132.10 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4150.84 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4132.10 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4150.84 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3139.73 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3139.73 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3119.03 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3119.03 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 193.87 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 193.29 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 543.85 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 154.60 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 119.20 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 118.34 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 118.60 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 121.87 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 500.41 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 496.87 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 439.94 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 413.02 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 316.84 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 315.44 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 320.70 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 321.78 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 351.68 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 340.92 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.00 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.78 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 234.53 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 234.77 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 262.01 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 262.63 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1760.22 | 2112.27 | 0.139 | 0.167 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 34.31 | 0.01615 |
G NW APARTMENT | 1755.04 | 2106.05 | 0.139 | 0.167 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.62 | 0.01615 |
OFFICE | 4700.42 | 5640.51 | 0.390 | 0.468 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 31.32 | 0.01615 |
G NE APARTMENT | 1403.65 | 1684.38 | 0.111 | 0.133 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 32.45 | 0.01615 |
G N1 APARTMENT | 1082.37 | 1298.85 | 0.086 | 0.103 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.70 | 0.01615 |
G N2 APARTMENT | 1074.58 | 1289.49 | 0.085 | 0.102 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.70 | 0.01615 |
G S1 APARTMENT | 1076.82 | 1292.18 | 0.085 | 0.102 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
G S2 APARTMENT | 1106.58 | 1327.90 | 0.087 | 0.105 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
M SW APARTMENT | 4543.35 | 5452.02 | 0.359 | 0.431 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.08 | 0.01615 |
M NW APARTMENT | 4511.38 | 5413.66 | 0.357 | 0.428 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.62 | 0.01615 |
M SE APARTMENT | 3994.12 | 4792.95 | 0.316 | 0.379 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 35.26 | 0.01615 |
M NE APARTMENT | 3749.72 | 4499.67 | 0.296 | 0.356 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.79 | 0.01615 |
M N1 APARTMENT | 2876.89 | 3452.26 | 0.227 | 0.273 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
M N2 APARTMENT | 2864.17 | 3437.00 | 0.226 | 0.272 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.05 | 0.01615 |
M S1 APARTMENT | 2911.82 | 3494.19 | 0.230 | 0.276 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
M S2 APARTMENT | 2921.61 | 3505.93 | 0.231 | 0.277 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 35.37 | 0.01615 |
T SW APARTMENT | 3192.59 | 3831.11 | 0.252 | 0.303 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 35.19 | 0.01615 |
T NW APARTMENT | 3094.91 | 3713.90 | 0.245 | 0.294 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.50 | 0.01615 |
T SE APARTMENT | 2941.39 | 3529.67 | 0.233 | 0.279 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
T NE APARTMENT | 2676.04 | 3211.25 | 0.212 | 0.254 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.60 | 0.01615 |
T N1 APARTMENT | 2129.35 | 2555.22 | 0.168 | 0.202 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.60 | 0.01615 |
T N2 APARTMENT | 2131.51 | 2557.81 | 0.169 | 0.202 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.60 | 0.01615 |
T S1 APARTMENT | 2378.86 | 2854.63 | 0.188 | 0.226 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.60 | 0.01615 |
T S2 APARTMENT | 2384.40 | 2861.28 | 0.189 | 0.226 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.48 | 0.01615 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1545.47 | 1854.57 | 0.045 | 0.054 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G NW APARTMENT | 1557.56 | 1869.07 | 0.045 | 0.054 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
OFFICE | 3132.98 | 3759.57 | 0.088 | 0.105 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G NE APARTMENT | 1557.56 | 1869.07 | 0.045 | 0.054 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G N1 APARTMENT | 952.84 | 1143.41 | 0.028 | 0.033 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G N2 APARTMENT | 952.84 | 1143.41 | 0.028 | 0.033 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G S1 APARTMENT | 942.89 | 1131.47 | 0.027 | 0.033 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
G S2 APARTMENT | 1038.15 | 1245.78 | 0.030 | 0.036 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -8.30 | 0.00188 |
M SW APARTMENT | 3131.02 | 3757.23 | 0.091 | 0.109 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M NW APARTMENT | 3158.88 | 3790.66 | 0.092 | 0.110 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M SE APARTMENT | 3131.02 | 3757.23 | 0.091 | 0.109 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M NE APARTMENT | 3158.88 | 3790.66 | 0.092 | 0.110 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M N1 APARTMENT | 1615.62 | 1938.75 | 0.047 | 0.056 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M N2 APARTMENT | 1615.62 | 1938.75 | 0.047 | 0.056 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M S1 APARTMENT | 1589.21 | 1907.05 | 0.046 | 0.055 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
M S2 APARTMENT | 1589.21 | 1907.05 | 0.046 | 0.055 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T SW APARTMENT | 2705.29 | 3246.35 | 0.079 | 0.094 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T NW APARTMENT | 2721.14 | 3265.37 | 0.079 | 0.095 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T SE APARTMENT | 2705.29 | 3246.35 | 0.079 | 0.094 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T NE APARTMENT | 2721.14 | 3265.37 | 0.079 | 0.095 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T N1 APARTMENT | 1866.04 | 2239.25 | 0.054 | 0.065 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T N2 APARTMENT | 1866.04 | 2239.25 | 0.054 | 0.065 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T S1 APARTMENT | 1848.53 | 2218.24 | 0.054 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
T S2 APARTMENT | 1848.53 | 2218.24 | 0.054 | 0.064 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -8.30 | 0.00188 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.17 | 0.17 | 0.05 | 0.05 |
SPLIT GNW | 0.17 | 0.17 | 0.05 | 0.05 |
SPLIT OFFICE | 0.47 | 0.47 | 0.11 | 0.11 |
SPLIT GNE | 0.13 | 0.13 | 0.05 | 0.05 |
SPLIT GN1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GN2 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GS1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GS2 | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT MSW | 0.43 | 0.43 | 0.11 | 0.11 |
SPLIT MNW | 0.43 | 0.43 | 0.11 | 0.11 |
SPLIT MSE | 0.38 | 0.38 | 0.11 | 0.11 |
SPLIT MNE | 0.36 | 0.36 | 0.11 | 0.11 |
SPLIT MN1 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MN2 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MS1 | 0.28 | 0.28 | 0.06 | 0.06 |
SPLIT MS2 | 0.28 | 0.28 | 0.06 | 0.06 |
SPLIT TSW | 0.30 | 0.30 | 0.09 | 0.09 |
SPLIT TNW | 0.29 | 0.29 | 0.09 | 0.09 |
SPLIT TSE | 0.28 | 0.28 | 0.09 | 0.09 |
SPLIT TNE | 0.25 | 0.25 | 0.09 | 0.09 |
SPLIT TN1 | 0.20 | 0.20 | 0.07 | 0.07 |
SPLIT TN2 | 0.20 | 0.20 | 0.07 | 0.07 |
SPLIT TS1 | 0.23 | 0.23 | 0.06 | 0.06 |
SPLIT TS2 | 0.23 | 0.23 | 0.06 | 0.06 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3918.25 | 5793.25 | 1540.25 |
G NW APARTMENT | 4149.25 | 6100.00 | 1878.25 |
OFFICE | 798.50 | 1254.00 | 42.25 |
G NE APARTMENT | 4125.75 | 6096.75 | 1825.50 |
G N1 APARTMENT | 3818.25 | 6306.00 | 1674.25 |
G N2 APARTMENT | 3815.50 | 6303.00 | 1669.50 |
G S1 APARTMENT | 3653.00 | 5968.50 | 1366.75 |
G S2 APARTMENT | 3697.50 | 5749.50 | 1222.25 |
M SW APARTMENT | 4771.00 | 3194.75 | 386.75 |
M NW APARTMENT | 4605.25 | 3756.75 | 558.25 |
M SE APARTMENT | 4763.00 | 3180.25 | 349.00 |
M NE APARTMENT | 4579.75 | 3784.25 | 533.50 |
M N1 APARTMENT | 4378.25 | 3590.50 | 299.00 |
M N2 APARTMENT | 4375.25 | 3596.00 | 298.00 |
M S1 APARTMENT | 4621.25 | 2870.75 | 211.50 |
M S2 APARTMENT | 4622.25 | 2874.75 | 212.75 |
T SW APARTMENT | 5160.00 | 4038.50 | 1246.00 |
T NW APARTMENT | 5205.75 | 4461.25 | 1577.75 |
T SE APARTMENT | 5151.75 | 4012.75 | 1226.75 |
T NE APARTMENT | 5184.75 | 4487.25 | 1547.00 |
T N1 APARTMENT | 4976.75 | 4359.25 | 1261.75 |
T N2 APARTMENT | 4974.00 | 4361.50 | 1262.25 |
T S1 APARTMENT | 4982.50 | 3818.50 | 967.50 |
T S2 APARTMENT | 4986.50 | 3820.25 | 972.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5942.75 | 6380.00 | 2299.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 6.00 | 0.00 | 6.00 | 0.00 |
G NW APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
OFFICE | 5.00 | 23.75 | 0.00 | 0.00 |
G NE APARTMENT | 8.00 | 0.00 | 8.00 | 0.00 |
G N1 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
G N2 APARTMENT | 5.50 | 0.00 | 5.50 | 0.00 |
G S1 APARTMENT | 5.00 | 2.25 | 5.00 | 2.25 |
G S2 APARTMENT | 5.25 | 1.50 | 5.25 | 1.50 |
M SW APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
M NW APARTMENT | 11.75 | 0.00 | 11.75 | 0.00 |
M SE APARTMENT | 12.75 | 0.00 | 12.75 | 0.00 |
M NE APARTMENT | 15.00 | 0.00 | 15.00 | 0.00 |
M N1 APARTMENT | 8.00 | 0.00 | 8.00 | 0.00 |
M N2 APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
M S1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
M S2 APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
T SW APARTMENT | 10.50 | 0.00 | 10.50 | 0.00 |
T NW APARTMENT | 12.25 | 0.00 | 12.25 | 0.00 |
T SE APARTMENT | 13.00 | 0.00 | 13.00 | 0.00 |
T NE APARTMENT | 17.50 | 0.00 | 17.50 | 0.00 |
T N1 APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
T N2 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
T S1 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
T S2 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 61.75 | 26.00 | 57.25 | 2.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.367 | 0.162 | 0.000 | 0.088 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.162 | 0.000 | 0.084 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.520 | 0.196 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.162 | 0.000 | 0.084 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.083 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.083 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.088 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.098 | 0.000 | 0.088 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.233 | 0.000 | 0.110 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.233 | 0.000 | 0.106 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.233 | 0.000 | 0.110 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.233 | 0.000 | 0.106 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.106 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.106 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.111 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.141 | 0.000 | 0.111 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.308 | 0.000 | 0.133 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.308 | 0.000 | 0.127 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.308 | 0.000 | 0.133 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.308 | 0.000 | 0.127 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.186 | 0.000 | 0.127 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.186 | 0.000 | 0.127 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.186 | 0.000 | 0.133 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.186 | 0.000 | 0.133 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.369 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 356.50 | 0.00 | 01-JAN-00:15 | 32298.32 | 07-JAN-08:00 |
WaterSystems:Electricity | 356.50 | 0.00 | 01-JAN-00:15 | 32298.32 | 07-JAN-08:00 |
Water Heater:WaterSystems:Electricity | 356.50 | 0.00 | 01-JAN-00:15 | 32298.32 | 07-JAN-08:00 |
Fans:Electricity | 220.56 | 6993.96 | 02-JAN-18:15 | 6993.96 | 02-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
ElectricityPurchased:Plant | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
Cogeneration:ElectricityPurchased | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
ElectricityNet:Plant | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
Cogeneration:ElectricityNet | 1459.61 | 20106.58 | 01-JAN-03:15 | 88227.61 | 29-AUG-16:45 |
ExteriorLights:Electricity | 40.14 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.14 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 426.85 | 6993.96 | 02-JAN-18:15 | 39482.60 | 29-AUG-13:45 |
General:Fans:Electricity | 220.56 | 6993.96 | 02-JAN-18:15 | 6993.96 | 02-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 206.29 | 0.00 | 01-JAN-00:15 | 32488.63 | 29-AUG-13:45 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 191.69 | 0.00 | 13-JAN-14:00 | 109600.43 | 31-JAN-07:15 |
Gas:HVAC | 191.69 | 0.00 | 13-JAN-14:00 | 109600.43 | 31-JAN-07:15 |
Heating:Gas | 191.69 | 0.00 | 13-JAN-14:00 | 109600.43 | 31-JAN-07:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1603.69 | 1293.73 | 14-APR-11:30 | 186762.75 | 29-AUG-13:30 |
EnergyTransfer:Building | 618.12 | 1258.31 | 14-APR-11:30 | 68619.73 | 29-AUG-13:45 |
EnergyTransfer:Zone:G SW APARTMENT | 13.90 | 0.00 | 11-APR-13:45 | 2077.48 | 30-AUG-16:15 |
Heating:EnergyTransfer | 92.98 | 0.00 | 15-JAN-12:45 | 62349.94 | 31-JAN-07:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.26 | 0.00 | 01-JAN-11:00 | 2071.89 | 06-JAN-22:15 |
Cooling:EnergyTransfer | 525.14 | 0.00 | 02-JAN-07:30 | 68619.73 | 29-AUG-13:45 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 10.63 | 0.00 | 01-JAN-00:15 | 2077.48 | 30-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.32 | 0.03 | 05-APR-12:00 | 2093.75 | 06-JAN-22:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 4.52 | 0.00 | 04-JAN-21:00 | 2093.75 | 06-JAN-22:15 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 8.81 | 0.00 | 01-JAN-00:15 | 1926.52 | 12-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 27.09 | 0.02 | 12-APR-00:45 | 4839.91 | 29-AUG-10:30 |
Heating:EnergyTransfer:Zone:OFFICE | 4.39 | 0.00 | 01-JAN-00:15 | 3748.34 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 22.70 | 0.00 | 01-JAN-03:30 | 4839.91 | 29-AUG-10:30 |
EnergyTransfer:Zone:G NE APARTMENT | 13.25 | 0.00 | 17-OCT-18:15 | 2065.34 | 06-JAN-19:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.37 | 0.00 | 13-JAN-17:45 | 2065.34 | 06-JAN-19:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 8.89 | 0.00 | 01-JAN-00:15 | 1568.78 | 11-JUL-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.31 | 0.01 | 15-NOV-16:15 | 1229.64 | 31-JAN-03:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.17 | 0.00 | 04-JAN-19:15 | 1229.64 | 31-JAN-03:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 7.14 | 0.00 | 01-JAN-00:15 | 1219.73 | 11-JUL-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.31 | 0.00 | 28-MAR-08:15 | 1228.89 | 31-JAN-03:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.17 | 0.00 | 04-JAN-19:15 | 1228.89 | 31-JAN-03:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 7.14 | 0.00 | 01-JAN-00:15 | 1213.76 | 11-JUL-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 10.47 | 0.01 | 01-MAY-03:00 | 1421.35 | 30-AUG-13:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.31 | 0.00 | 01-JAN-07:15 | 1214.99 | 31-JAN-03:30 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 9.15 | 0.00 | 01-JAN-00:15 | 1421.35 | 30-AUG-13:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.10 | 0.01 | 30-DEC-12:00 | 1499.92 | 23-SEP-14:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.41 | 0.00 | 01-JAN-07:15 | 1322.38 | 31-JAN-03:45 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 9.69 | 0.00 | 01-JAN-00:15 | 1499.92 | 23-SEP-14:30 |
EnergyTransfer:Zone:M SW APARTMENT | 45.73 | 0.14 | 03-FEB-01:45 | 5314.61 | 30-AUG-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 3.71 | 0.00 | 01-JAN-01:00 | 4405.51 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 42.02 | 0.00 | 01-JAN-00:15 | 5314.61 | 30-AUG-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 40.25 | 0.01 | 15-OCT-14:30 | 4914.17 | 10-JUL-16:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 5.91 | 0.00 | 01-JAN-11:30 | 4445.57 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 34.34 | 0.00 | 01-JAN-00:15 | 4914.17 | 10-JUL-16:30 |
EnergyTransfer:Zone:M SE APARTMENT | 45.90 | 0.02 | 02-FEB-21:00 | 5065.11 | 29-AUG-10:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 3.71 | 0.00 | 01-JAN-02:00 | 4350.35 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 42.19 | 0.00 | 01-JAN-00:15 | 5065.11 | 29-AUG-10:30 |
EnergyTransfer:Zone:M NE APARTMENT | 40.30 | 0.00 | 06-NOV-14:00 | 4365.21 | 06-JAN-22:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 5.81 | 0.00 | 01-JAN-07:45 | 4365.21 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 34.50 | 0.00 | 01-JAN-00:15 | 4189.08 | 10-JUL-17:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 32.46 | 0.02 | 25-FEB-14:45 | 3224.15 | 11-JUL-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.71 | 0.00 | 01-JAN-00:45 | 2364.98 | 06-JAN-22:15 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 30.75 | 0.00 | 01-JAN-00:15 | 3224.15 | 11-JUL-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 32.45 | 0.06 | 23-JAN-17:00 | 3215.61 | 11-JUL-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.71 | 0.00 | 01-JAN-00:45 | 2363.73 | 06-JAN-22:15 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 30.74 | 0.00 | 01-JAN-00:15 | 3215.61 | 11-JUL-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 40.51 | 0.49 | 15-FEB-04:30 | 3761.91 | 30-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.90 | 0.00 | 01-JAN-00:15 | 2333.63 | 06-JAN-22:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 39.62 | 0.00 | 02-JAN-07:00 | 3761.91 | 30-AUG-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 40.50 | 0.09 | 31-DEC-09:15 | 3773.72 | 30-AUG-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.90 | 0.00 | 01-JAN-00:15 | 2334.76 | 06-JAN-22:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 39.60 | 0.00 | 02-JAN-07:00 | 3773.72 | 30-AUG-13:00 |
EnergyTransfer:Zone:T SW APARTMENT | 27.75 | 0.00 | 05-NOV-00:45 | 3670.52 | 06-JAN-22:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 6.58 | 0.00 | 01-JAN-11:15 | 3670.52 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 21.17 | 0.00 | 01-JAN-00:15 | 3637.40 | 29-AUG-13:30 |
EnergyTransfer:Zone:T NW APARTMENT | 26.35 | 0.01 | 09-APR-04:15 | 3680.80 | 06-JAN-22:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 8.25 | 0.00 | 10-JAN-14:00 | 3680.80 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 18.11 | 0.00 | 01-JAN-00:15 | 3368.07 | 10-JUL-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 27.52 | 0.01 | 13-APR-16:00 | 3645.60 | 06-JAN-22:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 6.46 | 0.00 | 01-JAN-11:00 | 3645.60 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 21.07 | 0.00 | 01-JAN-00:15 | 3586.71 | 29-AUG-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 26.08 | 0.01 | 07-SEP-03:00 | 3637.71 | 06-JAN-22:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 8.06 | 0.00 | 15-JAN-07:45 | 3637.71 | 06-JAN-22:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 18.01 | 0.00 | 01-JAN-00:15 | 2951.82 | 05-JUN-14:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 20.06 | 0.01 | 02-DEC-09:45 | 2447.09 | 31-JAN-03:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 4.54 | 0.00 | 01-JAN-11:45 | 2447.09 | 31-JAN-03:30 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 15.52 | 0.00 | 01-JAN-00:15 | 2355.41 | 10-JUL-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 20.07 | 0.03 | 06-DEC-20:45 | 2447.67 | 31-JAN-03:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 4.54 | 0.00 | 01-JAN-11:45 | 2447.67 | 31-JAN-03:30 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 15.52 | 0.00 | 01-JAN-00:15 | 2345.30 | 10-JUL-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.20 | 0.00 | 26-NOV-21:00 | 2900.10 | 29-AUG-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 3.29 | 0.00 | 01-JAN-10:45 | 2450.50 | 31-JAN-03:45 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 18.91 | 0.00 | 01-JAN-00:15 | 2900.10 | 29-AUG-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.21 | 0.05 | 07-DEC-00:45 | 2905.95 | 29-AUG-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 3.30 | 0.00 | 01-JAN-10:45 | 2451.40 | 31-JAN-03:45 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 18.91 | 0.00 | 01-JAN-00:15 | 2905.95 | 29-AUG-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 985.57 | 0.00 | 14-JAN-11:15 | 118711.52 | 21-AUG-15:15 |
HeatingCoils:EnergyTransfer | 153.36 | 0.00 | 13-JAN-14:00 | 87680.34 | 31-JAN-07:15 |
CoolingCoils:EnergyTransfer | 832.22 | 0.00 | 01-JAN-00:15 | 118711.52 | 21-AUG-15:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 3.262 | -10.634 | 0.000 | 0.000 | 3.768 | 1.087 | 12.213 | 12.107 | 0.000 | 0.542 | 0.000 | 0.000 | -5.010 | 0.000 | -4.484 | -12.850 |
G NW APARTMENT | 4.518 | -8.807 | 0.000 | 0.000 | 3.789 | 1.087 | 12.213 | 7.370 | 0.000 | 0.542 | 0.000 | 0.000 | -5.211 | 0.000 | -4.318 | -11.182 |
OFFICE | 4.395 | -22.697 | 0.000 | 0.000 | 0.520 | 26.452 | 9.482 | 11.612 | 0.000 | 0.323 | 0.000 | 0.000 | -5.272 | 0.000 | -3.851 | -20.965 |
G NE APARTMENT | 4.365 | -8.886 | 0.000 | 0.000 | 3.798 | 1.087 | 12.213 | 7.169 | 0.000 | 0.542 | 0.000 | 0.000 | -5.036 | 0.000 | -4.294 | -10.958 |
G N1 APARTMENT | 2.172 | -7.136 | 0.000 | 0.000 | 3.800 | 1.087 | 12.213 | 3.004 | 0.000 | 0.345 | 0.000 | 0.000 | -3.224 | 0.000 | -2.840 | -9.421 |
G N2 APARTMENT | 2.172 | -7.137 | 0.000 | 0.000 | 3.801 | 1.087 | 12.213 | 3.004 | 0.000 | 0.345 | 0.000 | 0.000 | -3.222 | 0.000 | -2.839 | -9.422 |
G S1 APARTMENT | 1.313 | -9.152 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 7.773 | 0.000 | 0.343 | 0.000 | 0.000 | -3.023 | 0.000 | -3.016 | -11.311 |
G S2 APARTMENT | 1.409 | -9.694 | 0.000 | 0.000 | 3.769 | 1.087 | 12.213 | 7.763 | 0.000 | 0.343 | 0.000 | 0.000 | -3.030 | 0.000 | -3.028 | -10.830 |
M SW APARTMENT | 3.707 | -42.024 | 0.000 | 0.000 | 3.664 | 1.087 | 12.213 | 11.589 | 0.000 | 0.769 | 21.294 | 0.000 | -5.625 | 0.000 | -6.673 | -0.000 |
M NW APARTMENT | 5.906 | -34.344 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 6.949 | 0.000 | 0.767 | 16.017 | 0.000 | -5.812 | 0.000 | -6.477 | -0.001 |
M SE APARTMENT | 3.713 | -42.191 | 0.000 | 0.000 | 3.669 | 1.087 | 12.213 | 11.456 | 0.000 | 0.769 | 21.462 | 0.000 | -5.517 | 0.000 | -6.660 | -0.000 |
M NE APARTMENT | 5.808 | -34.496 | 0.000 | 0.000 | 3.701 | 1.087 | 12.213 | 6.738 | 0.000 | 0.767 | 16.258 | 0.000 | -5.620 | 0.000 | -6.455 | -0.001 |
M N1 APARTMENT | 1.712 | -30.751 | 0.000 | 0.000 | 3.686 | 1.087 | 12.213 | 2.751 | 0.000 | 0.482 | 16.853 | 0.000 | -3.667 | 0.000 | -4.365 | -0.000 |
M N2 APARTMENT | 1.714 | -30.740 | 0.000 | 0.000 | 3.686 | 1.087 | 12.213 | 2.751 | 0.000 | 0.482 | 16.836 | 0.000 | -3.666 | 0.000 | -4.363 | -0.001 |
M S1 APARTMENT | 0.899 | -39.615 | 0.000 | 0.000 | 3.645 | 1.087 | 12.213 | 7.437 | 0.000 | 0.484 | 21.831 | 0.000 | -3.430 | 0.000 | -4.549 | -0.001 |
M S2 APARTMENT | 0.902 | -39.597 | 0.000 | 0.000 | 3.645 | 1.087 | 12.213 | 7.436 | 0.000 | 0.484 | 21.809 | 0.000 | -3.429 | 0.000 | -4.549 | -0.000 |
T SW APARTMENT | 6.577 | -21.173 | 0.000 | 0.000 | 3.708 | 1.087 | 12.213 | 11.361 | 0.000 | 1.019 | 0.001 | 0.000 | -5.329 | 0.000 | -8.457 | -1.005 |
T NW APARTMENT | 8.246 | -18.106 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 6.770 | 0.000 | 1.016 | 0.000 | 0.000 | -5.527 | 0.000 | -8.250 | -1.176 |
T SE APARTMENT | 6.455 | -21.067 | 0.000 | 0.000 | 3.712 | 1.087 | 12.213 | 11.241 | 0.000 | 1.019 | 0.001 | 0.000 | -5.236 | 0.000 | -8.457 | -0.966 |
T NE APARTMENT | 8.064 | -18.011 | 0.000 | 0.000 | 3.736 | 1.087 | 12.213 | 6.587 | 0.000 | 1.016 | 0.000 | 0.000 | -5.362 | 0.000 | -8.241 | -1.087 |
T N1 APARTMENT | 4.538 | -15.523 | 0.000 | 0.000 | 3.725 | 1.087 | 12.213 | 2.687 | 0.000 | 0.642 | 0.000 | 0.000 | -3.457 | 0.000 | -5.466 | -0.445 |
T N2 APARTMENT | 4.544 | -15.522 | 0.000 | 0.000 | 3.725 | 1.087 | 12.213 | 2.686 | 0.000 | 0.642 | 0.000 | 0.000 | -3.455 | 0.000 | -5.467 | -0.453 |
T S1 APARTMENT | 3.292 | -18.908 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 7.312 | 0.000 | 0.645 | 0.000 | 0.000 | -3.252 | 0.000 | -5.670 | -0.413 |
T S2 APARTMENT | 3.298 | -18.914 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 7.311 | 0.000 | 0.645 | 0.001 | 0.000 | -3.250 | 0.000 | -5.671 | -0.414 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.157 | 0.000 | 0.071 | 0.000 | 0.000 | -0.622 | 0.000 | -1.337 | -12.850 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.566 | 0.000 | 1.928 | 0.001 | 0.000 | -1.536 | 0.000 | -18.331 | -3.688 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.165 | 0.000 | 0.064 | 0.000 | 0.000 | -0.683 | 0.000 | -1.105 | -13.023 |
Total Facility | 92.979 | -525.128 | 0.000 | 0.000 | 86.131 | 95.189 | 296.854 | 173.749 | 0.000 | 17.041 | 152.364 | 0.000 | -107.504 | 0.000 | -149.211 | -132.463 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-AUG-16:13 | 0.00 | -2078.48 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1708.16 | 0.00 | 190.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -558.56 |
G NW APARTMENT | 12-JUL-17:23 | 0.00 | -1927.06 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1455.05 | 0.00 | 217.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.50 |
OFFICE | 07-SEP-06:01 | 0.00 | -7873.31 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 28.27 | 0.00 | 0.00 | 7248.67 | 0.00 | 0.00 | 0.00 | -114.08 | 0.00 |
G NE APARTMENT | 11-JUL-17:06 | 0.00 | -1571.61 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 689.14 | 0.00 | 239.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -175.47 |
G N1 APARTMENT | 11-JUL-17:23 | 0.00 | -1220.13 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 492.55 | 0.00 | 142.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -233.13 |
G N2 APARTMENT | 11-JUL-17:23 | 0.00 | -1214.07 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 492.64 | 0.00 | 142.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -239.27 |
G S1 APARTMENT | 30-AUG-13:00 | 0.00 | -1421.02 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1345.85 | 0.00 | 138.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -505.57 |
G S2 APARTMENT | 23-SEP-14:30 | 0.00 | -1499.84 | 0.00 | 0.00 | 40.62 | 22.70 | 400.26 | 1168.53 | 0.00 | 92.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224.47 |
M SW APARTMENT | 30-AUG-16:05 | 0.00 | -5317.33 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1684.85 | 0.00 | 273.37 | 2620.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 10-JUL-16:20 | 0.00 | -4915.14 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1468.74 | 0.00 | 386.83 | 2321.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 29-AUG-10:30 | 0.00 | -5065.15 | 0.00 | 0.00 | 40.76 | 12.97 | 412.04 | 2003.35 | 0.00 | 348.93 | 2247.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 10-JUL-17:00 | 0.00 | -4188.50 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 688.79 | 0.00 | 404.63 | 2356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 11-JUL-17:30 | 0.00 | -3225.17 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 484.34 | 0.00 | 204.70 | 1718.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 11-JUL-17:26 | 0.00 | -3216.29 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 484.39 | 0.00 | 204.70 | 1709.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 30-AUG-13:00 | 0.00 | -3761.18 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1332.30 | 0.00 | 198.67 | 1788.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 30-AUG-13:00 | 0.00 | -3773.00 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1332.22 | 0.00 | 198.67 | 1799.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 29-AUG-13:30 | 0.00 | -3637.11 | 0.00 | 0.00 | 40.76 | 12.97 | 382.60 | 1937.01 | 0.00 | 562.40 | 701.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 10-JUL-16:20 | 0.00 | -3368.70 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1427.87 | 0.00 | 509.79 | 692.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 29-AUG-13:30 | 0.00 | -3586.62 | 0.00 | 0.00 | 40.76 | 12.97 | 382.60 | 1527.24 | 0.00 | 562.40 | 1060.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 05-JUN-14:15 | 0.00 | -2951.49 | 0.00 | 0.00 | 40.76 | 22.70 | 400.26 | 939.49 | 0.00 | 514.58 | 1033.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 10-JUL-16:04 | 0.00 | -2360.03 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 466.62 | 0.00 | 299.97 | 855.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 10-JUL-16:04 | 0.00 | -2349.97 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 466.75 | 0.00 | 299.97 | 845.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 29-AUG-13:30 | 0.00 | -2899.99 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1214.02 | 0.00 | 339.21 | 910.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 29-AUG-13:30 | 0.00 | -2905.84 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1213.93 | 0.00 | 339.21 | 916.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-AUG-13:45 | 0.00 | -68616.94 | 0.00 | 0.00 | 1002.17 | 3766.23 | 9517.04 | 26102.03 | 0.00 | 9481.63 | 18747.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 06-JAN-22:15 | 2072.14 | 0.00 | 0.00 | 0.00 | 189.67 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -752.33 | 0.00 | -1433.22 | -533.10 |
G NW APARTMENT | 06-JAN-22:15 | 2094.02 | 0.00 | 0.00 | 0.00 | 189.67 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -771.17 | 0.00 | -1433.22 | -536.14 |
OFFICE | 29-JAN-07:01 | 4651.92 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -343.74 | 0.00 | -152.44 | -4866.20 |
G NE APARTMENT | 06-JAN-19:00 | 2065.47 | 0.00 | 0.00 | 0.00 | 165.01 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -771.62 | 0.00 | -1508.38 | -626.66 |
G N1 APARTMENT | 29-DEC-17:01 | 1621.70 | 0.00 | 0.00 | 0.00 | 99.72 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203.22 | 0.00 | -124.84 | -2046.84 |
G N2 APARTMENT | 29-DEC-17:01 | 1633.96 | 0.00 | 0.00 | 0.00 | 99.72 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203.19 | 0.00 | -124.84 | -2059.13 |
G S1 APARTMENT | 31-JAN-03:30 | 1214.93 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.75 | 0.00 | -822.66 | -308.35 |
G S2 APARTMENT | 31-JAN-03:45 | 1322.32 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -507.09 | 0.00 | -851.10 | -383.96 |
M SW APARTMENT | 06-JAN-22:00 | 4405.30 | 0.00 | 0.00 | 0.00 | 190.04 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -790.56 | 0.00 | -2116.04 | -2260.41 |
M NW APARTMENT | 06-JAN-22:00 | 4445.35 | 0.00 | 0.00 | 0.00 | 190.19 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -813.02 | 0.00 | -2113.24 | -2280.96 |
M SE APARTMENT | 06-JAN-22:00 | 4350.13 | 0.00 | 0.00 | 0.00 | 190.35 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -788.93 | 0.00 | -2111.48 | -2211.74 |
M NE APARTMENT | 06-JAN-22:00 | 4364.99 | 0.00 | 0.00 | 0.00 | 190.58 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -811.25 | 0.00 | -2107.47 | -2208.53 |
M N1 APARTMENT | 04-JAN-17:01 | 3221.26 | 0.00 | 0.00 | 0.00 | 99.71 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -220.34 | 0.00 | -266.90 | -3487.21 |
M N2 APARTMENT | 06-JAN-22:10 | 2364.44 | 0.00 | 0.00 | 0.00 | 189.78 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -495.74 | 0.00 | -1240.44 | -1274.87 |
M S1 APARTMENT | 06-JAN-22:15 | 2334.02 | 0.00 | 0.00 | 0.00 | 189.67 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -473.79 | 0.00 | -1242.03 | -1264.70 |
M S2 APARTMENT | 06-JAN-22:15 | 2335.15 | 0.00 | 0.00 | 0.00 | 189.67 | 38.91 | 417.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -473.76 | 0.00 | -1242.00 | -1265.89 |
T SW APARTMENT | 06-JAN-22:00 | 3670.33 | 0.00 | 0.00 | 0.00 | 190.03 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -772.15 | 0.00 | -2801.68 | -858.21 |
T NW APARTMENT | 06-JAN-22:00 | 3680.62 | 0.00 | 0.00 | 0.00 | 190.06 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -795.76 | 0.00 | -2800.27 | -846.33 |
T SE APARTMENT | 06-JAN-22:00 | 3645.41 | 0.00 | 0.00 | 0.00 | 190.27 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -770.76 | 0.00 | -2797.15 | -839.45 |
T NE APARTMENT | 06-JAN-22:00 | 3637.52 | 0.00 | 0.00 | 0.00 | 190.43 | 71.34 | 500.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.08 | 0.00 | -2793.12 | -812.41 |
T N1 APARTMENT | 31-JAN-03:30 | 2446.97 | 0.00 | 0.00 | 0.00 | 190.31 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.28 | 0.00 | -1558.60 | -782.57 |
T N2 APARTMENT | 31-JAN-03:30 | 2447.55 | 0.00 | 0.00 | 0.00 | 190.35 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -526.19 | 0.00 | -1558.37 | -783.51 |
T S1 APARTMENT | 31-JAN-03:45 | 2450.38 | 0.00 | 0.00 | 0.00 | 190.55 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -508.22 | 0.00 | -1610.80 | -752.08 |
T S2 APARTMENT | 31-JAN-03:45 | 2451.28 | 0.00 | 0.00 | 0.00 | 190.58 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -508.16 | 0.00 | -1610.65 | -753.21 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JAN-07:01 | 62867.41 | 0.00 | 0.00 | 0.00 | 3790.35 | 2772.92 | 9503.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15443.40 | 0.00 | -53222.88 | -10268.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Sec1.1A-General InformationData | |
Weather File | Memphis International Ap TN USA TMY3 WMO#=723340 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 57.25 |
Number of hours cooling loads not met | 2.25 |
Number of hours not met | 59.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 191.69 | 109600.43 | 0.00 | 0.00 |
Space Cooling | 206.29 | 29187.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 220.56 | 6993.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 356.50 | 21039.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1459.61 | 191.69 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1459.61 |
Natural Gas | 0.00 | 191.69 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1651.30 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 65.81 |
Fans-Interior | 70.36 |
Service Water Heating | 113.73 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.81 |
Subtotal | 465.64 |
Natural Gas [MJ/m2] | |
Space Heating | 61.15 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 61.15 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.17 |
Space Heating | 11.61 |
Space Cooling | 12.49 |
Fans-Interior | 13.36 |
Service Water Heating | 21.59 |
Receptacle Equipment | 31.35 |
Miscellaneous | 2.43 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.167012 |
G NW APARTMENT DIRECT AIR | 0.166509 |
OFFICE DIRECT AIR | 0.468499 |
G NE APARTMENT DIRECT AIR | 0.133183 |
G N1 APARTMENT DIRECT AIR | 0.102687 |
G N2 APARTMENT DIRECT AIR | 0.101947 |
G S1 APARTMENT DIRECT AIR | 0.102165 |
G S2 APARTMENT DIRECT AIR | 0.104989 |
M SW APARTMENT DIRECT AIR | 0.431079 |
M NW APARTMENT DIRECT AIR | 0.428027 |
M SE APARTMENT DIRECT AIR | 0.378981 |
M NE APARTMENT DIRECT AIR | 0.355795 |
M N1 APARTMENT DIRECT AIR | 0.272940 |
M N2 APARTMENT DIRECT AIR | 0.271734 |
M S1 APARTMENT DIRECT AIR | 0.276269 |
M S2 APARTMENT DIRECT AIR | 0.277198 |
T SW APARTMENT DIRECT AIR | 0.302949 |
T NW APARTMENT DIRECT AIR | 0.293680 |
T SE APARTMENT DIRECT AIR | 0.279113 |
T NE APARTMENT DIRECT AIR | 0.253933 |
T N1 APARTMENT DIRECT AIR | 0.202038 |
T N2 APARTMENT DIRECT AIR | 0.202243 |
T S1 APARTMENT DIRECT AIR | 0.225712 |
T S2 APARTMENT DIRECT AIR | 0.226238 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.167012 |
SPLIT GNW MAIN BRANCH | 0.166509 |
SPLIT OFFICE MAIN BRANCH | 0.468499 |
SPLIT GNE MAIN BRANCH | 0.133183 |
SPLIT GN1 MAIN BRANCH | 0.102687 |
SPLIT GN2 MAIN BRANCH | 0.101947 |
SPLIT GS1 MAIN BRANCH | 0.102165 |
SPLIT GS2 MAIN BRANCH | 0.104989 |
SPLIT MSW MAIN BRANCH | 0.431079 |
SPLIT MNW MAIN BRANCH | 0.428027 |
SPLIT MSE MAIN BRANCH | 0.378981 |
SPLIT MNE MAIN BRANCH | 0.355795 |
SPLIT MN1 MAIN BRANCH | 0.272940 |
SPLIT MN2 MAIN BRANCH | 0.271734 |
SPLIT MS1 MAIN BRANCH | 0.276269 |
SPLIT MS2 MAIN BRANCH | 0.277198 |
SPLIT TSW MAIN BRANCH | 0.302949 |
SPLIT TNW MAIN BRANCH | 0.293680 |
SPLIT TSE MAIN BRANCH | 0.279113 |
SPLIT TNE MAIN BRANCH | 0.253933 |
SPLIT TN1 MAIN BRANCH | 0.202038 |
SPLIT TN2 MAIN BRANCH | 0.202243 |
SPLIT TS1 MAIN BRANCH | 0.225712 |
SPLIT TS2 MAIN BRANCH | 0.226238 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.167012 |
SPLIT GNW | 0.166509 |
SPLIT OFFICE | 0.468499 |
SPLIT GNE | 0.133183 |
SPLIT GN1 | 0.102687 |
SPLIT GN2 | 0.101947 |
SPLIT GS1 | 0.102165 |
SPLIT GS2 | 0.104989 |
SPLIT MSW | 0.431079 |
SPLIT MNW | 0.428027 |
SPLIT MSE | 0.378981 |
SPLIT MNE | 0.355795 |
SPLIT MN1 | 0.272940 |
SPLIT MN2 | 0.271734 |
SPLIT MS1 | 0.276269 |
SPLIT MS2 | 0.277198 |
SPLIT TSW | 0.302949 |
SPLIT TNW | 0.293680 |
SPLIT TSE | 0.279113 |
SPLIT TNE | 0.253933 |
SPLIT TN1 | 0.202038 |
SPLIT TN2 | 0.202243 |
SPLIT TS1 | 0.225712 |
SPLIT TS2 | 0.226238 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.167012 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.166509 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.468499 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.133183 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.102687 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.101947 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.102165 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.104989 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.431079 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.428027 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.378981 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.355795 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.272940 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.271734 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.276269 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.277198 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.302949 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.293680 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.279113 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.253933 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.202038 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.202243 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.225712 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.226238 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.167012 | 3767.30 | 0.700805 |
SPLIT GNW COOLING COIL | 0.166509 | 3702.47 | 0.704702 |
SPLIT OFFICE COOLING COIL | 0.468499 | 8451.94 | 0.768353 |
SPLIT GNE COOLING COIL | 0.133183 | 3088.81 | 0.693416 |
SPLIT GN1 COOLING COIL | 0.102687 | 2528.79 | 0.678135 |
SPLIT GN2 COOLING COIL | 0.101947 | 2516.16 | 0.677587 |
SPLIT GS1 COOLING COIL | 0.102165 | 2537.00 | 0.676083 |
SPLIT GS2 COOLING COIL | 0.104989 | 2607.12 | 0.676083 |
SPLIT MSW COOLING COIL | 0.431079 | 9252.74 | 0.714543 |
SPLIT MNW COOLING COIL | 0.428027 | 9154.69 | 0.715550 |
SPLIT MSE COOLING COIL | 0.378981 | 8520.50 | 0.701697 |
SPLIT MNE COOLING COIL | 0.355795 | 7851.28 | 0.706798 |
SPLIT MN1 COOLING COIL | 0.272940 | 6313.56 | 0.694103 |
SPLIT MN2 COOLING COIL | 0.271734 | 6293.22 | 0.693786 |
SPLIT MS1 COOLING COIL | 0.276269 | 6580.96 | 0.686491 |
SPLIT MS2 COOLING COIL | 0.277198 | 6585.97 | 0.687155 |
SPLIT TSW COOLING COIL | 0.302949 | 6248.86 | 0.726053 |
SPLIT TNW COOLING COIL | 0.293680 | 6040.99 | 0.726868 |
SPLIT TSE COOLING COIL | 0.279113 | 5878.18 | 0.719981 |
SPLIT TNE COOLING COIL | 0.253933 | 5466.01 | 0.713736 |
SPLIT TN1 COOLING COIL | 0.202038 | 4434.14 | 0.708304 |
SPLIT TN2 COOLING COIL | 0.202243 | 4437.35 | 0.708383 |
SPLIT TS1 COOLING COIL | 0.225712 | 4830.05 | 0.715403 |
SPLIT TS2 COOLING COIL | 0.226238 | 4831.29 | 0.715993 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.167012 | 0.167012 | 0.167012 | 0.167012 | 2794.72 | 3767.30 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.166509 | 0.166509 | 0.166509 | 0.166509 | 2775.02 | 3702.47 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.468499 | 0.468499 | 0.468499 | 0.468499 | 5014.02 | 8451.94 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.133183 | 0.133183 | 0.133183 | 0.133183 | 2775.02 | 3088.81 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.102687 | 0.102687 | 0.102687 | 0.102687 | 2059.94 | 2528.79 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.101947 | 0.101947 | 0.101947 | 0.101947 | 2059.94 | 2516.16 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.102165 | 0.102165 | 0.102165 | 0.102165 | 2048.18 | 2537.00 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.104989 | 0.104989 | 0.104989 | 0.104989 | 2160.82 | 2607.12 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.431079 | 0.431079 | 0.431079 | 0.431079 | 5568.67 | 9252.74 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.428027 | 0.428027 | 0.428027 | 0.428027 | 5601.61 | 9154.69 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.378981 | 0.378981 | 0.378981 | 0.378981 | 5568.67 | 8520.50 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.355795 | 0.355795 | 0.355795 | 0.355795 | 5601.61 | 7851.28 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.272940 | 0.272940 | 0.272940 | 0.272940 | 3776.78 | 6313.56 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.271734 | 0.271734 | 0.271734 | 0.271734 | 3776.78 | 6293.22 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.276269 | 0.276269 | 0.276269 | 0.276269 | 3745.54 | 6580.96 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.277198 | 0.277198 | 0.277198 | 0.277198 | 3745.54 | 6585.97 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.302949 | 0.302949 | 0.302949 | 0.302949 | 4132.10 | 6248.86 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.293680 | 0.293680 | 0.293680 | 0.293680 | 4150.84 | 6040.99 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.279113 | 0.279113 | 0.279113 | 0.279113 | 4132.10 | 5878.18 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.253933 | 0.253933 | 0.253933 | 0.253933 | 4150.84 | 5466.01 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.202038 | 0.202038 | 0.202038 | 0.202038 | 3139.73 | 4434.14 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.202243 | 0.202243 | 0.202243 | 0.202243 | 3139.73 | 4437.35 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.225712 | 0.225712 | 0.225712 | 0.225712 | 3119.03 | 4830.05 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.226238 | 0.226238 | 0.226238 | 0.226238 | 3119.03 | 4831.29 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.167012 |
SPLIT GNW SUPPLY FAN | 0.166509 |
SPLIT OFFICE SUPPLY FAN | 0.468499 |
SPLIT GNE SUPPLY FAN | 0.133183 |
SPLIT GN1 SUPPLY FAN | 0.102687 |
SPLIT GN2 SUPPLY FAN | 0.101947 |
SPLIT GS1 SUPPLY FAN | 0.102165 |
SPLIT GS2 SUPPLY FAN | 0.104989 |
SPLIT MSW SUPPLY FAN | 0.431079 |
SPLIT MNW SUPPLY FAN | 0.428027 |
SPLIT MSE SUPPLY FAN | 0.378981 |
SPLIT MNE SUPPLY FAN | 0.355795 |
SPLIT MN1 SUPPLY FAN | 0.272940 |
SPLIT MN2 SUPPLY FAN | 0.271734 |
SPLIT MS1 SUPPLY FAN | 0.276269 |
SPLIT MS2 SUPPLY FAN | 0.277198 |
SPLIT TSW SUPPLY FAN | 0.302949 |
SPLIT TNW SUPPLY FAN | 0.293680 |
SPLIT TSE SUPPLY FAN | 0.279113 |
SPLIT TNE SUPPLY FAN | 0.253933 |
SPLIT TN1 SUPPLY FAN | 0.202038 |
SPLIT TN2 SUPPLY FAN | 0.202243 |
SPLIT TS1 SUPPLY FAN | 0.225712 |
SPLIT TS2 SUPPLY FAN | 0.226238 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2794.72 |
SPLIT GNW HEATING COIL | 2775.02 |
SPLIT OFFICE HEATING COIL | 5014.02 |
SPLIT GNE HEATING COIL | 2775.02 |
SPLIT GN1 HEATING COIL | 2059.94 |
SPLIT GN2 HEATING COIL | 2059.94 |
SPLIT GS1 HEATING COIL | 2048.18 |
SPLIT GS2 HEATING COIL | 2160.82 |
SPLIT MSW HEATING COIL | 5568.67 |
SPLIT MNW HEATING COIL | 5601.61 |
SPLIT MSE HEATING COIL | 5568.67 |
SPLIT MNE HEATING COIL | 5601.61 |
SPLIT MN1 HEATING COIL | 3776.78 |
SPLIT MN2 HEATING COIL | 3776.78 |
SPLIT MS1 HEATING COIL | 3745.54 |
SPLIT MS2 HEATING COIL | 3745.54 |
SPLIT TSW HEATING COIL | 4132.10 |
SPLIT TNW HEATING COIL | 4150.84 |
SPLIT TSE HEATING COIL | 4132.10 |
SPLIT TNE HEATING COIL | 4150.84 |
SPLIT TN1 HEATING COIL | 3139.73 |
SPLIT TN2 HEATING COIL | 3139.73 |
SPLIT TS1 HEATING COIL | 3119.03 |
SPLIT TS2 HEATING COIL | 3119.03 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 4.12 |
February | 21.99 | 6.58 |
March | 22.52 | 12.40 |
April | 23.27 | 16.79 |
May | 24.09 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.64 | 16.70 |
November | 22.66 | 12.13 |
December | 21.93 | 6.84 |
Annual Sum or Average | 23.30 | 17.04 |
Minimum of Months | 21.85 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 4.12 |
February | 21.79 | 6.58 |
March | 22.25 | 12.40 |
April | 23.09 | 16.79 |
May | 24.07 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.30 | 16.70 |
November | 22.26 | 12.13 |
December | 21.79 | 6.84 |
Annual Sum or Average | 23.16 | 17.04 |
Minimum of Months | 21.75 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 4.12 |
February | 21.71 | 6.58 |
March | 23.28 | 12.40 |
April | 24.29 | 16.79 |
May | 25.52 | 22.07 |
June | 26.81 | 26.01 |
July | 27.25 | 28.31 |
August | 27.01 | 27.55 |
September | 26.93 | 24.35 |
October | 24.69 | 16.70 |
November | 23.46 | 12.13 |
December | 21.83 | 6.84 |
Annual Sum or Average | 24.50 | 17.04 |
Minimum of Months | 21.05 | 4.12 |
Maximum of Months | 27.25 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.77 | 6.58 |
March | 22.17 | 12.40 |
April | 23.05 | 16.79 |
May | 24.06 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.20 | 16.70 |
November | 22.18 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.13 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.76 | 6.58 |
March | 22.10 | 12.40 |
April | 22.90 | 16.79 |
May | 23.98 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.15 | 16.70 |
November | 22.17 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.10 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.12 |
February | 21.76 | 6.58 |
March | 22.10 | 12.40 |
April | 22.90 | 16.79 |
May | 23.98 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.14 | 16.70 |
November | 22.16 | 12.13 |
December | 21.78 | 6.84 |
Annual Sum or Average | 23.10 | 17.04 |
Minimum of Months | 21.73 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 4.12 |
February | 21.98 | 6.58 |
March | 22.44 | 12.40 |
April | 23.15 | 16.79 |
May | 24.02 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.63 | 16.70 |
November | 22.66 | 12.13 |
December | 21.94 | 6.84 |
Annual Sum or Average | 23.28 | 17.04 |
Minimum of Months | 21.85 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.12 |
February | 21.98 | 6.58 |
March | 22.47 | 12.40 |
April | 23.19 | 16.79 |
May | 24.05 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.66 | 16.70 |
November | 22.69 | 12.13 |
December | 21.95 | 6.84 |
Annual Sum or Average | 23.29 | 17.04 |
Minimum of Months | 21.86 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 4.12 |
February | 22.59 | 6.58 |
March | 23.65 | 12.40 |
April | 24.15 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.36 | 16.70 |
November | 23.69 | 12.13 |
December | 22.38 | 6.84 |
Annual Sum or Average | 23.75 | 17.04 |
Minimum of Months | 22.17 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.12 |
February | 22.12 | 6.58 |
March | 23.34 | 12.40 |
April | 24.04 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.28 | 16.70 |
November | 23.35 | 12.13 |
December | 21.95 | 6.84 |
Annual Sum or Average | 23.59 | 17.04 |
Minimum of Months | 21.89 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.12 | 4.12 |
February | 22.58 | 6.58 |
March | 23.61 | 12.40 |
April | 24.14 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.35 | 16.70 |
November | 23.65 | 12.13 |
December | 22.33 | 6.84 |
Annual Sum or Average | 23.74 | 17.04 |
Minimum of Months | 22.12 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 4.12 |
February | 22.09 | 6.58 |
March | 23.28 | 12.40 |
April | 24.01 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.26 | 16.70 |
November | 23.27 | 12.13 |
December | 21.91 | 6.84 |
Annual Sum or Average | 23.56 | 17.04 |
Minimum of Months | 21.85 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 4.12 |
February | 22.18 | 6.58 |
March | 23.42 | 12.40 |
April | 24.09 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.32 | 16.70 |
November | 23.50 | 12.13 |
December | 22.01 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 21.92 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 4.12 |
February | 22.18 | 6.58 |
March | 23.41 | 12.40 |
April | 24.08 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.31 | 16.70 |
November | 23.49 | 12.13 |
December | 22.00 | 6.84 |
Annual Sum or Average | 23.62 | 17.04 |
Minimum of Months | 21.92 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 4.12 |
February | 22.77 | 6.58 |
March | 23.79 | 12.40 |
April | 24.22 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.38 | 16.70 |
November | 23.91 | 12.13 |
December | 22.69 | 6.84 |
Annual Sum or Average | 23.84 | 17.04 |
Minimum of Months | 22.31 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 4.12 |
February | 22.77 | 6.58 |
March | 23.79 | 12.40 |
April | 24.22 | 16.79 |
May | 24.40 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.40 | 24.35 |
October | 24.38 | 16.70 |
November | 23.91 | 12.13 |
December | 22.69 | 6.84 |
Annual Sum or Average | 23.84 | 17.04 |
Minimum of Months | 22.31 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 4.12 |
February | 22.35 | 6.58 |
March | 23.23 | 12.40 |
April | 23.84 | 16.79 |
May | 24.36 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 24.02 | 16.70 |
November | 23.16 | 12.13 |
December | 22.23 | 6.84 |
Annual Sum or Average | 23.57 | 17.04 |
Minimum of Months | 22.05 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.12 |
February | 22.09 | 6.58 |
March | 23.00 | 12.40 |
April | 23.76 | 16.79 |
May | 24.35 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.83 | 16.70 |
November | 22.85 | 12.13 |
December | 21.95 | 6.84 |
Annual Sum or Average | 23.45 | 17.04 |
Minimum of Months | 21.86 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 4.12 |
February | 22.36 | 6.58 |
March | 23.21 | 12.40 |
April | 23.86 | 16.79 |
May | 24.36 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 24.01 | 16.70 |
November | 23.15 | 12.13 |
December | 22.20 | 6.84 |
Annual Sum or Average | 23.57 | 17.04 |
Minimum of Months | 22.01 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 4.12 |
February | 22.05 | 6.58 |
March | 22.94 | 12.40 |
April | 23.77 | 16.79 |
May | 24.35 | 22.07 |
June | 24.39 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.81 | 16.70 |
November | 22.80 | 12.13 |
December | 21.92 | 6.84 |
Annual Sum or Average | 23.43 | 17.04 |
Minimum of Months | 21.82 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.12 |
February | 22.09 | 6.58 |
March | 23.04 | 12.40 |
April | 23.80 | 16.79 |
May | 24.37 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 23.86 | 16.70 |
November | 22.86 | 12.13 |
December | 21.95 | 6.84 |
Annual Sum or Average | 23.46 | 17.04 |
Minimum of Months | 21.87 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.12 |
February | 22.08 | 6.58 |
March | 23.03 | 12.40 |
April | 23.80 | 16.79 |
May | 24.37 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.38 | 24.35 |
October | 23.86 | 16.70 |
November | 22.86 | 12.13 |
December | 21.95 | 6.84 |
Annual Sum or Average | 23.46 | 17.04 |
Minimum of Months | 21.87 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 4.12 |
February | 22.45 | 6.58 |
March | 23.36 | 12.40 |
April | 23.91 | 16.79 |
May | 24.37 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 24.09 | 16.70 |
November | 23.27 | 12.13 |
December | 22.33 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 22.14 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 4.12 |
February | 22.46 | 6.58 |
March | 23.36 | 12.40 |
April | 23.91 | 16.79 |
May | 24.37 | 22.07 |
June | 24.40 | 26.01 |
July | 24.40 | 28.31 |
August | 24.40 | 27.55 |
September | 24.39 | 24.35 |
October | 24.09 | 16.70 |
November | 23.27 | 12.13 |
December | 22.33 | 6.84 |
Annual Sum or Average | 23.63 | 17.04 |
Minimum of Months | 22.14 | 4.12 |
Maximum of Months | 24.40 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | 4.12 |
February | 22.23 | 6.58 |
March | 24.04 | 12.40 |
April | 25.28 | 16.79 |
May | 26.46 | 22.07 |
June | 27.00 | 26.01 |
July | 27.24 | 28.31 |
August | 27.13 | 27.55 |
September | 26.72 | 24.35 |
October | 25.33 | 16.70 |
November | 23.81 | 12.13 |
December | 22.11 | 6.84 |
Annual Sum or Average | 24.92 | 17.04 |
Minimum of Months | 21.57 | 4.12 |
Maximum of Months | 27.24 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.35 | 4.12 |
February | 19.95 | 6.58 |
March | 21.65 | 12.40 |
April | 23.05 | 16.79 |
May | 24.73 | 22.07 |
June | 26.59 | 26.01 |
July | 27.21 | 28.31 |
August | 27.07 | 27.55 |
September | 26.41 | 24.35 |
October | 23.47 | 16.70 |
November | 21.79 | 12.13 |
December | 20.11 | 6.84 |
Annual Sum or Average | 23.47 | 17.04 |
Minimum of Months | 19.35 | 4.12 |
Maximum of Months | 27.21 | 28.31 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:02
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 4.12 |
February | 23.69 | 6.58 |
March | 25.26 | 12.40 |
April | 26.06 | 16.79 |
May | 26.65 | 22.07 |
June | 26.88 | 26.01 |
July | 26.99 | 28.31 |
August | 26.95 | 27.55 |
September | 26.79 | 24.35 |
October | 26.34 | 16.70 |
November | 25.38 | 12.13 |
December | 23.66 | 6.84 |
Annual Sum or Average | 25.66 | 17.04 |
Minimum of Months | 23.20 | 4.12 |
Maximum of Months | 26.99 | 28.31 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:02
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.111449E+12 | 71000.014 | 08-JAN-18:45 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29842.178 | 0.000 | 0.000 | 0.000 |
February | 0.100801E+12 | 68368.796 | 08-FEB-18:00 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27210.960 | 0.000 | 0.000 | 0.000 |
March | 0.113179E+12 | 69846.019 | 27-MAR-18:30 | 5482.595 | 23748.115 | 6993.962 | 0.000 | 6463.670 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24604.678 | 0.000 | 0.000 | 0.000 |
April | 0.113152E+12 | 73845.365 | 24-APR-17:15 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 14576.610 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20663.919 | 0.000 | 0.000 | 0.000 |
May | 0.127784E+12 | 77879.947 | 31-MAY-17:15 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 23346.102 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15929.009 | 0.000 | 0.000 | 0.000 |
June | 0.136038E+12 | 81365.309 | 02-JUN-17:30 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 24594.534 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18165.939 | 0.000 | 0.000 | 0.000 |
July | 0.146752E+12 | 86112.044 | 23-JUL-17:15 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 27592.546 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19914.662 | 0.000 | 0.000 | 0.000 |
August | 0.144017E+12 | 88227.609 | 29-AUG-16:45 | 4276.255 | 26730.986 | 6993.962 | 0.000 | 29187.380 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21039.026 | 0.000 | 0.000 | 0.000 |
September | 0.131941E+12 | 83622.738 | 22-SEP-16:30 | 4276.255 | 26630.920 | 6993.962 | 0.000 | 24645.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21076.472 | 0.000 | 0.000 | 0.000 |
October | 0.116127E+12 | 77832.279 | 01-OCT-17:45 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 18090.352 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18584.091 | 0.000 | 0.000 | 0.000 |
November | 0.107991E+12 | 67467.107 | 02-NOV-17:15 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 5623.252 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20686.019 | 0.000 | 0.000 | 0.000 |
December | 0.110374E+12 | 65750.853 | 21-DEC-18:00 | 4979.953 | 26630.920 | 6993.962 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24593.017 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.145961E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.100801E+12 | 65750.853 | 4276.255 | 23748.115 | 6993.962 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15929.009 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.146752E+12 | 88227.609 | 5482.595 | 26730.986 | 6993.962 | 0.000 | 29187.380 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29842.178 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:02
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.814499E+11 | 109600.427 | 31-JAN-07:15 | 109600.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 109600.427 |
February | 0.472334E+11 | 94728.812 | 12-FEB-02:00 | 94728.812 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 94728.812 |
March | 0.105490E+11 | 51774.363 | 10-MAR-03:00 | 51774.363 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 51774.363 |
April | 0.247425E+10 | 31751.886 | 13-APR-02:00 | 31751.886 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31751.886 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.512204E+09 | 7476.022 | 16-OCT-05:00 | 7476.022 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7476.022 |
November | 0.850964E+10 | 38348.025 | 22-NOV-04:00 | 38348.025 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38348.025 |
December | 0.409662E+11 | 70335.978 | 09-DEC-03:00 | 70335.978 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 70335.978 |
Annual Sum or Average | 0.191695E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.814499E+11 | 109600.427 | 109600.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 109600.427 |