Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060

Simulation Timestamp: 2015-09-09 18:47:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1752.84 559.19 620.70
Net Site Energy 1752.84 559.19 620.70
Total Source Energy 4896.19 1561.98 1733.79
Net Source Energy 4896.19 1561.98 1733.79


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 314.48 0.00 0.00 0.00 0.00
Cooling 145.81 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 227.26 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 389.06 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1438.36 314.48 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 314.48 0.00 0.00 0.00 0.00
Cooling General 145.81 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 227.26 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 389.06 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.16 0.00 0.00 0.00 0.00 0.00
HVAC 269.88 111.36 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 509.34 111.36 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.59 0.00 0.00 0.00 0.00 0.00
HVAC 243.13 100.33 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 458.86 100.33 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1438.36 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1438.36 100.00
     
Total On-Site and Utility Electric Sources 1438.36 100.00
Total Electricity End Uses 1438.36 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 49.25
Time Setpoint Not Met During Occupied Cooling 0.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2725.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Weather File Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Latitude [deg] 39.17
Longitude [deg] -76.7
Elevation [m] 45.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-JUL-16:30 25-DEC-06:00 - - - 01-JAN-07:15
Heating 0.00 109274.00 0.00 0.00 0.00 0.00
Cooling 28889.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4276.26 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26730.99 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7206.32 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19152.20 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 86255.13 109274.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 109274.00 0.00 0.00 0.00 0.00
Cooling General 28889.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 3538.13 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 738.12 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26730.99 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7206.32 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 19152.20 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 340.90 0.00 0.00 0.00
Cooling 461.79 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 127.07 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 719.73 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1232.14 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4555.30 340.90 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 120.72 0.00 0.00 0.00
Cooling 163.52 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.00 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 254.86 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 436.31 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1613.08 120.72 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 120.72 0.00 0.00 0.00
Cooling 163.52 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.00 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 254.86 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 436.31 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1613.08 120.72 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB -10.60 0.00 -10.60 Wetbulb [C] 3.90 290.00
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 34.40 10.40 23.90 Wetbulb [C] 4.60 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.72 83.72 40.12
Exterior Lighting Total 2553.00           40.12



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3634.27 2600.44 1033.83 0.72 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3434.95 2468.73 966.22 0.72 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8020.81 6266.09 1754.72 0.78 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2795.95 1968.63 827.32 0.70 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2239.95 1546.78 693.17 0.69 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2224.18 1534.30 689.88 0.69 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2546.71 1748.41 798.30 0.69 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2589.53 1784.21 805.33 0.69 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9355.65 6846.50 2509.16 0.73 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8909.12 6516.34 2392.77 0.73 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8789.56 6329.09 2460.47 0.72 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7556.22 5445.81 2110.41 0.72 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5879.33 4180.68 1698.65 0.71 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5853.62 4160.13 1693.49 0.71 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6717.00 4751.30 1965.70 0.71 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6734.02 4764.95 1969.07 0.71 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6330.81 4686.06 1644.75 0.74 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5932.82 4382.01 1550.81 0.74 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5976.11 4390.97 1585.13 0.73 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5269.18 3822.29 1446.89 0.73 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4175.83 3008.66 1167.16 0.72 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4186.89 3013.81 1173.07 0.72 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4860.73 3552.78 1307.95 0.73 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4871.16 3561.20 1309.96 0.73 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3500.6 3.28 11.18 11.64 11.12
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3307.2 3.27 11.16 11.62 11.09
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7658.8 3.16 10.77 11.20 10.53
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2697.2 3.30 11.25 11.72 11.23
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2164.7 3.32 11.34 11.81 11.36
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2149.6 3.32 11.34 11.82 11.37
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2462.4 3.33 11.36 11.84 11.40
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2503.0 3.33 11.35 11.82 11.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8992.2 3.25 11.07 11.53 10.97
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 8563.4 3.25 11.08 11.53 10.97
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 8461.2 3.27 11.15 11.61 11.08
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7273.3 3.27 11.14 11.60 11.07
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5666.4 3.28 11.20 11.67 11.16
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5641.9 3.28 11.21 11.67 11.17
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6476.9 3.29 11.23 11.70 11.20
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6493.1 3.29 11.23 11.69 11.20
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6078.1 3.23 11.02 11.47 10.89
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5697.2 3.23 11.03 11.48 10.91
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5741.7 3.24 11.06 11.51 10.94
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 5068.8 3.26 11.11 11.57 11.03
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4019.6 3.27 11.15 11.60 11.07
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4030.6 3.27 11.15 11.61 11.08
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4672.5 3.25 11.08 11.53 10.98
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4682.4 3.25 11.08 11.53 10.97
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   2963.30 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   2940.52 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   5176.62 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   2933.44 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   2200.11 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   2199.94 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   2188.79 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   2304.81 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   5889.43 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   5920.90 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   5870.67 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   5902.14 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   4033.26 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   4032.78 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   4003.65 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   4003.17 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   4373.07 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   4391.13 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   4363.26 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   4381.32 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   3344.55 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   3344.28 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   3324.47 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   3324.20 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 197.24 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.50 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.46 535.81 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 145.64 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 110.89 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 109.80 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 124.13 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 127.44 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.46 536.78 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 510.52 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 484.63 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 417.54 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 314.09 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 312.28 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 354.06 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 355.27 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 373.37 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 348.09 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 346.24 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 295.89 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 230.58 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 230.65 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 278.06 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 278.81 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1798.44 2158.13 0.142 0.170 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.15 0.01446
G NW APARTMENT 1718.90 2062.68 0.135 0.162 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.90 0.01446
OFFICE 4650.78 5580.93 0.385 0.462 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 29.56 0.01446
G NE APARTMENT 1327.98 1593.58 0.105 0.125 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.23 0.01446
G N1 APARTMENT 1011.19 1213.43 0.080 0.096 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.12 0.01446
G N2 APARTMENT 1001.31 1201.57 0.079 0.095 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.12 0.01446
G S1 APARTMENT 1131.89 1358.27 0.089 0.107 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.27 0.01446
G S2 APARTMENT 1162.04 1394.44 0.091 0.110 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.14 0.01446
M SW APARTMENT 4894.47 5873.37 0.385 0.462 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
M NW APARTMENT 4655.18 5586.22 0.366 0.440 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.90 0.01446
M SE APARTMENT 4418.77 5302.53 0.348 0.417 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.14 0.01446
M NE APARTMENT 3807.08 4568.49 0.300 0.360 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
M N1 APARTMENT 2864.13 3436.95 0.225 0.271 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.12 0.01446
M N2 APARTMENT 2847.66 3417.19 0.224 0.269 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.12 0.01446
M S1 APARTMENT 3228.51 3874.21 0.254 0.305 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.27 0.01446
M S2 APARTMENT 3239.49 3887.38 0.255 0.306 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.27 0.01446
T SW APARTMENT 3404.10 4084.92 0.268 0.322 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 33.93 0.01446
T NW APARTMENT 3173.64 3808.37 0.250 0.300 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.36 0.01446
T SE APARTMENT 3156.79 3788.15 0.249 0.298 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.27 0.01446
T NE APARTMENT 2697.70 3237.24 0.212 0.255 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 34.40 0.01446
T N1 APARTMENT 2102.45 2522.94 0.166 0.199 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.24 0.01446
T N2 APARTMENT 2103.12 2523.74 0.166 0.199 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 34.40 0.01446
T S1 APARTMENT 2535.37 3042.45 0.200 0.240 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01446
T S2 APARTMENT 2542.20 3050.64 0.200 0.240 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01446


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1621.55 1945.86 0.047 0.056 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G NW APARTMENT 1633.38 1960.05 0.047 0.057 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
OFFICE 3176.34 3811.61 0.089 0.106 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G NE APARTMENT 1627.38 1952.86 0.047 0.056 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G N1 APARTMENT 1007.24 1208.68 0.029 0.035 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G N2 APARTMENT 1007.09 1208.51 0.029 0.035 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G S1 APARTMENT 997.66 1197.19 0.029 0.035 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
G S2 APARTMENT 1095.77 1314.92 0.032 0.038 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
M SW APARTMENT 3274.00 3928.80 0.095 0.114 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M NW APARTMENT 3300.61 3960.73 0.095 0.115 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M SE APARTMENT 3258.14 3909.76 0.094 0.113 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M NE APARTMENT 3284.75 3941.70 0.095 0.114 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M N1 APARTMENT 1704.24 2045.09 0.049 0.059 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M N2 APARTMENT 1703.83 2044.60 0.049 0.059 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M S1 APARTMENT 1679.20 2015.04 0.049 0.058 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
M S2 APARTMENT 1678.79 2014.55 0.049 0.058 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T SW APARTMENT 2844.93 3413.92 0.082 0.099 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T NW APARTMENT 2860.21 3432.25 0.083 0.099 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T SE APARTMENT 2836.64 3403.96 0.082 0.098 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T NE APARTMENT 2851.91 3422.29 0.082 0.099 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T N1 APARTMENT 1975.11 2370.13 0.057 0.069 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T N2 APARTMENT 1974.88 2369.85 0.057 0.069 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T S1 APARTMENT 1958.12 2349.75 0.057 0.068 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152
T S2 APARTMENT 1957.90 2349.48 0.057 0.068 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -10.60 0.00152


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.17 0.17 0.06 0.06
SPLIT GNW 0.16 0.16 0.06 0.06
SPLIT OFFICE 0.46 0.46 0.11 0.11
SPLIT GNE 0.13 0.13 0.06 0.06
SPLIT GN1 0.10 0.10 0.03 0.03
SPLIT GN2 0.09 0.09 0.03 0.03
SPLIT GS1 0.11 0.11 0.03 0.03
SPLIT GS2 0.11 0.11 0.04 0.04
SPLIT MSW 0.46 0.46 0.11 0.11
SPLIT MNW 0.44 0.44 0.11 0.11
SPLIT MSE 0.42 0.42 0.11 0.11
SPLIT MNE 0.36 0.36 0.11 0.11
SPLIT MN1 0.27 0.27 0.06 0.06
SPLIT MN2 0.27 0.27 0.06 0.06
SPLIT MS1 0.31 0.31 0.06 0.06
SPLIT MS2 0.31 0.31 0.06 0.06
SPLIT TSW 0.32 0.32 0.10 0.10
SPLIT TNW 0.30 0.30 0.10 0.10
SPLIT TSE 0.30 0.30 0.10 0.10
SPLIT TNE 0.25 0.25 0.10 0.10
SPLIT TN1 0.20 0.20 0.07 0.07
SPLIT TN2 0.20 0.20 0.07 0.07
SPLIT TS1 0.24 0.24 0.07 0.07
SPLIT TS2 0.24 0.24 0.07 0.07



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3606.75 6205.25 1520.50
G NW APARTMENT 4036.75 6443.50 2114.50
OFFICE 725.25 1378.75 80.00
G NE APARTMENT 4033.75 6440.00 2089.00
G N1 APARTMENT 3598.50 6575.50 1872.00
G N2 APARTMENT 3600.50 6573.75 1869.25
G S1 APARTMENT 3146.75 6296.50 1162.00
G S2 APARTMENT 3252.00 6187.75 1142.00
M SW APARTMENT 3812.75 4009.50 314.25
M NW APARTMENT 3939.50 4612.75 750.50
M SE APARTMENT 3797.50 4009.00 299.25
M NE APARTMENT 3917.25 4622.50 736.50
M N1 APARTMENT 3573.25 4491.00 400.25
M N2 APARTMENT 3570.75 4492.00 399.50
M S1 APARTMENT 3654.50 3712.00 167.75
M S2 APARTMENT 3655.25 3713.25 169.50
T SW APARTMENT 4617.25 4840.75 1500.75
T NW APARTMENT 4956.00 5302.25 2100.00
T SE APARTMENT 4619.75 4825.50 1485.00
T NE APARTMENT 4918.50 5316.00 2074.75
T N1 APARTMENT 4563.00 5266.75 1734.25
T N2 APARTMENT 4560.75 5264.75 1732.00
T S1 APARTMENT 4259.25 4682.75 1122.75
T S2 APARTMENT 4263.00 4682.00 1124.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 5787.00 6641.25 2725.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.75 0.00 3.75 0.00
G NW APARTMENT 4.25 0.00 4.25 0.00
OFFICE 10.00 16.25 0.00 0.00
G NE APARTMENT 4.75 0.00 4.75 0.00
G N1 APARTMENT 6.75 0.00 6.75 0.00
G N2 APARTMENT 9.00 0.50 9.00 0.50
G S1 APARTMENT 3.00 0.00 3.00 0.00
G S2 APARTMENT 2.75 0.00 2.75 0.00
M SW APARTMENT 2.00 0.00 2.00 0.00
M NW APARTMENT 5.50 0.00 5.50 0.00
M SE APARTMENT 1.75 0.00 1.75 0.00
M NE APARTMENT 6.00 0.00 6.00 0.00
M N1 APARTMENT 2.50 0.00 2.50 0.00
M N2 APARTMENT 2.75 0.00 2.75 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.50 0.00 0.50 0.00
T SW APARTMENT 3.50 0.00 3.50 0.00
T NW APARTMENT 5.25 0.00 5.25 0.00
T SE APARTMENT 3.75 0.00 3.75 0.00
T NE APARTMENT 5.00 0.00 5.00 0.00
T N1 APARTMENT 1.50 0.00 1.50 0.00
T N2 APARTMENT 0.75 0.00 0.75 0.00
T S1 APARTMENT 2.50 0.00 2.50 0.00
T S2 APARTMENT 2.00 0.00 2.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 59.25 16.75 49.25 0.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.366 0.176 0.000 0.076
G NW APARTMENT 1.71 2.50 268.97 0.353 0.176 0.000 0.074
OFFICE 0.94 1.00 268.97 0.519 0.208 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.353 0.176 0.000 0.073
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.106 0.000 0.073
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.106 0.000 0.073
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.106 0.000 0.075
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.106 0.000 0.075
M SW APARTMENT 1.71 2.50 268.97 0.354 0.253 0.000 0.094
M NW APARTMENT 1.71 2.50 268.97 0.353 0.253 0.000 0.092
M SE APARTMENT 1.71 2.50 268.97 0.354 0.253 0.000 0.094
M NE APARTMENT 1.71 2.50 268.97 0.353 0.253 0.000 0.092
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.153 0.000 0.092
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.153 0.000 0.092
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.153 0.000 0.094
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.153 0.000 0.094
T SW APARTMENT 1.71 2.50 268.97 0.353 0.335 0.000 0.112
T NW APARTMENT 1.71 2.50 268.97 0.353 0.334 0.000 0.109
T SE APARTMENT 1.71 2.50 268.97 0.353 0.335 0.000 0.112
T NE APARTMENT 1.71 2.50 268.97 0.353 0.334 0.000 0.109
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.202 0.000 0.109
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.202 0.000 0.109
T S1 APARTMENT 1.71 2.50 268.97 0.354 0.202 0.000 0.112
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.202 0.000 0.112
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.353 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.498 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.360 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.359 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1438.36 20318.93 03-JAN-03:30 86255.13 09-JUL-16:30
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 389.06 0.00 01-JAN-00:15 32533.94 14-JAN-07:30
WaterSystems:Electricity 389.06 0.00 01-JAN-00:15 32533.94 14-JAN-07:30
Water Heater:WaterSystems:Electricity 389.06 0.00 01-JAN-00:15 32533.94 14-JAN-07:30
Fans:Electricity 227.26 7206.32 01-JAN-00:15 7206.32 01-JAN-00:30
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
ElectricityPurchased:Plant 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
Cogeneration:ElectricityPurchased 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
ElectricityNet:Plant 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
Cogeneration:ElectricityNet 1438.36 20318.93 02-JAN-03:15 86255.13 09-JUL-16:30
ExteriorLights:Electricity 40.12 0.00 01-JAN-07:45 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.12 0.00 01-JAN-07:45 2553.00 01-JAN-00:15
Electricity:HVAC 373.07 7206.32 01-JAN-00:15 37839.99 20-JUL-13:30
General:Fans:Electricity 227.26 7206.32 01-JAN-00:15 7206.32 01-JAN-00:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 145.81 0.00 01-JAN-00:15 30633.67 20-JUL-13:30


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 314.48 0.00 01-FEB-13:30 109274.00 25-DEC-07:00
Gas:HVAC 314.48 0.00 01-FEB-13:30 109274.00 25-DEC-07:00
Heating:Gas 314.48 0.00 01-FEB-13:30 109274.00 25-DEC-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1417.55 1480.65 28-OCT-14:00 181629.64 20-JUL-13:30
EnergyTransfer:Building 570.59 1480.65 28-OCT-14:00 63971.36 09-JUL-15:30
EnergyTransfer:Zone:G SW APARTMENT 12.96 0.05 14-MAY-21:45 1993.08 25-DEC-04:00
Heating:EnergyTransfer 140.18 0.00 17-FEB-13:45 63238.37 25-DEC-03:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 4.64 0.00 01-JAN-11:15 1993.08 25-DEC-04:00
Cooling:EnergyTransfer 430.41 0.00 04-JAN-07:15 63971.36 09-JUL-15:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 8.33 0.00 01-JAN-00:15 1946.99 09-JUL-16:30
EnergyTransfer:Zone:G NW APARTMENT 13.40 0.04 09-APR-10:45 2094.78 25-DEC-08:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 6.85 0.00 16-JAN-16:00 2094.78 25-DEC-08:30
Cooling:EnergyTransfer:Zone:G NW APARTMENT 6.56 0.00 01-JAN-00:15 1917.11 09-JUL-17:30
EnergyTransfer:Zone:OFFICE 24.15 0.02 09-SEP-09:15 4670.72 09-JUL-10:00
Heating:EnergyTransfer:Zone:OFFICE 2.96 0.00 01-JAN-00:15 3468.27 26-DEC-07:15
Cooling:EnergyTransfer:Zone:OFFICE 21.19 0.00 02-JAN-07:45 4670.72 09-JUL-10:00
EnergyTransfer:Zone:G NE APARTMENT 13.41 0.01 09-APR-18:30 2021.82 25-DEC-04:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 6.66 0.00 26-JAN-17:15 2021.82 25-DEC-04:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 6.75 0.00 01-JAN-00:15 1464.77 09-JUL-09:45
EnergyTransfer:Zone:G N1 APARTMENT 9.07 0.00 26-OCT-16:00 1265.67 25-DEC-08:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.45 0.00 16-JAN-16:15 1265.67 25-DEC-08:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 5.62 0.00 01-JAN-00:15 1085.63 09-JUL-17:45
EnergyTransfer:Zone:G N2 APARTMENT 9.08 0.01 27-NOV-13:30 1262.56 25-DEC-08:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.45 0.00 16-JAN-16:15 1262.56 25-DEC-08:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 5.63 0.00 01-JAN-00:15 1074.19 09-JUL-17:45
EnergyTransfer:Zone:G S1 APARTMENT 9.52 0.01 28-MAR-22:30 1302.16 29-AUG-13:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 1.81 0.00 01-JAN-10:00 1145.95 25-DEC-04:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.71 0.00 01-JAN-00:15 1302.16 29-AUG-13:15
EnergyTransfer:Zone:G S2 APARTMENT 10.07 0.02 15-MAY-20:45 1359.85 12-AUG-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 2.00 0.00 01-JAN-10:15 1227.82 25-DEC-04:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 8.07 0.00 01-JAN-00:15 1359.85 12-AUG-13:30
EnergyTransfer:Zone:M SW APARTMENT 40.27 0.03 09-DEC-01:00 5229.21 09-JUL-16:30
Heating:EnergyTransfer:Zone:M SW APARTMENT 5.12 0.00 01-JAN-10:30 4517.26 25-DEC-03:15
Cooling:EnergyTransfer:Zone:M SW APARTMENT 35.15 0.00 01-JAN-00:15 5229.21 09-JUL-16:30
EnergyTransfer:Zone:M NW APARTMENT 37.19 0.05 27-JAN-04:30 5072.43 09-JUL-17:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 9.95 0.00 02-JAN-21:00 4664.08 13-FEB-11:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 27.23 0.00 01-JAN-00:15 5072.43 09-JUL-17:30
EnergyTransfer:Zone:M SE APARTMENT 40.67 0.06 27-FEB-15:00 4718.60 29-AUG-12:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 4.99 0.00 01-JAN-09:45 4493.92 25-DEC-02:30
Cooling:EnergyTransfer:Zone:M SE APARTMENT 35.68 0.00 01-JAN-00:15 4718.60 29-AUG-12:45
EnergyTransfer:Zone:M NE APARTMENT 37.51 0.00 01-MAR-23:45 4581.75 25-DEC-01:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 9.71 0.00 02-JAN-21:00 4581.75 25-DEC-01:15
Cooling:EnergyTransfer:Zone:M NE APARTMENT 27.81 0.00 01-JAN-00:15 4171.19 09-JUL-10:00
EnergyTransfer:Zone:M N1 APARTMENT 28.58 0.04 02-MAR-13:15 3062.06 29-JUN-17:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 3.22 0.00 01-JAN-18:15 2488.27 25-DEC-02:30
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 25.36 0.00 01-JAN-00:15 3062.06 29-JUN-17:30
EnergyTransfer:Zone:M N2 APARTMENT 28.59 0.04 07-JAN-15:15 3048.74 29-JUN-17:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 3.22 0.00 01-JAN-18:15 2487.60 25-DEC-02:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 25.37 0.00 01-JAN-00:15 3048.74 29-JUN-17:30
EnergyTransfer:Zone:M S1 APARTMENT 36.48 0.06 01-FEB-21:30 3694.65 08-OCT-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 1.01 0.00 01-JAN-00:15 2352.70 25-DEC-04:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 35.47 0.00 01-JAN-05:00 3694.65 08-OCT-13:30
EnergyTransfer:Zone:M S2 APARTMENT 36.49 0.04 01-FEB-19:15 3700.27 08-OCT-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 1.01 0.00 01-JAN-00:15 2355.67 25-DEC-04:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 35.48 0.00 01-JAN-05:00 3700.27 08-OCT-13:30
EnergyTransfer:Zone:T SW APARTMENT 26.14 0.00 27-APR-06:45 3806.72 25-DEC-03:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 9.77 0.00 01-JAN-11:45 3806.72 25-DEC-03:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 16.37 0.00 01-JAN-00:15 3606.96 17-AUG-15:15
EnergyTransfer:Zone:T NW APARTMENT 26.45 0.02 05-JUN-23:15 3816.84 25-DEC-02:30
Heating:EnergyTransfer:Zone:T NW APARTMENT 13.01 0.00 16-JAN-15:15 3816.84 25-DEC-02:30
Cooling:EnergyTransfer:Zone:T NW APARTMENT 13.44 0.00 01-JAN-00:15 3453.73 29-JUN-16:15
EnergyTransfer:Zone:T SE APARTMENT 25.97 0.01 15-SEP-23:15 3779.36 25-DEC-02:45
Heating:EnergyTransfer:Zone:T SE APARTMENT 9.54 0.00 01-JAN-11:00 3779.36 25-DEC-02:45
Cooling:EnergyTransfer:Zone:T SE APARTMENT 16.43 0.00 01-JAN-00:15 3341.21 17-AUG-14:00
EnergyTransfer:Zone:T NE APARTMENT 26.22 0.01 14-MAR-12:15 3769.07 25-DEC-02:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 12.71 0.00 02-FEB-17:15 3769.07 25-DEC-02:15
Cooling:EnergyTransfer:Zone:T NE APARTMENT 13.51 0.00 01-JAN-00:15 2865.77 29-JUN-14:00
EnergyTransfer:Zone:T N1 APARTMENT 19.26 0.05 17-FEB-20:00 2562.55 25-DEC-05:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 7.61 0.00 16-JAN-15:30 2562.55 25-DEC-05:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 11.64 0.00 01-JAN-00:15 2280.85 29-JUN-16:15
EnergyTransfer:Zone:T N2 APARTMENT 19.26 0.00 06-OCT-11:30 2562.64 25-DEC-05:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 7.61 0.00 16-JAN-15:30 2562.64 25-DEC-05:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 11.64 0.00 01-JAN-00:15 2267.15 29-JUN-16:15
EnergyTransfer:Zone:T S1 APARTMENT 19.91 0.11 11-OCT-21:45 2761.23 17-AUG-14:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 4.94 0.00 01-JAN-10:30 2535.17 25-DEC-06:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 14.97 0.00 01-JAN-00:15 2761.23 17-AUG-14:00
EnergyTransfer:Zone:T S2 APARTMENT 19.92 0.05 31-AUG-05:00 2763.42 17-AUG-14:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 4.94 0.00 01-JAN-10:30 2536.11 25-DEC-06:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 14.99 0.00 01-JAN-00:15 2763.42 17-AUG-14:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 846.96 0.00 01-FEB-18:00 118718.08 20-JUL-13:30
HeatingCoils:EnergyTransfer 251.58 0.00 01-FEB-13:30 87419.20 25-DEC-07:00
CoolingCoils:EnergyTransfer 595.37 0.00 01-JAN-00:15 118718.08 20-JUL-13:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 4.638 -8.325 0.000 0.000 3.830 1.087 12.213 13.959 0.000 0.302 0.000 0.000 -6.125 0.000 -6.196 -15.382
G NW APARTMENT 6.848 -6.557 0.000 0.000 3.849 1.087 12.213 7.496 0.000 0.301 0.000 0.000 -6.428 0.000 -6.060 -12.748
OFFICE 2.960 -21.187 0.000 0.000 0.523 26.452 9.482 13.822 0.000 0.177 0.001 0.000 -6.180 0.000 -5.639 -20.409
G NE APARTMENT 6.665 -6.748 0.000 0.000 3.857 1.087 12.213 7.517 0.000 0.301 0.000 0.000 -6.217 0.000 -6.040 -12.635
G N1 APARTMENT 3.452 -5.623 0.000 0.000 3.858 1.087 12.213 2.916 0.000 0.200 0.000 0.000 -4.014 0.000 -3.886 -10.202
G N2 APARTMENT 3.449 -5.631 0.000 0.000 3.859 1.087 12.213 2.915 0.000 0.200 0.000 0.000 -4.013 0.000 -3.885 -10.193
G S1 APARTMENT 1.809 -7.707 0.000 0.000 3.832 1.087 12.213 9.418 0.000 0.199 0.000 0.000 -3.700 0.000 -4.022 -13.128
G S2 APARTMENT 1.999 -8.072 0.000 0.000 3.830 1.087 12.213 9.411 0.000 0.199 0.000 0.000 -3.704 0.000 -4.032 -12.930
M SW APARTMENT 5.122 -35.149 0.000 0.000 3.718 1.087 12.213 13.503 0.000 0.426 15.027 0.000 -6.753 0.000 -9.193 -0.000
M NW APARTMENT 9.955 -27.233 0.000 0.000 3.761 1.087 12.213 7.133 0.000 0.424 8.622 0.000 -7.000 0.000 -8.960 -0.000
M SE APARTMENT 4.987 -35.683 0.000 0.000 3.722 1.087 12.213 13.602 0.000 0.426 15.450 0.000 -6.616 0.000 -9.188 -0.000
M NE APARTMENT 9.707 -27.805 0.000 0.000 3.768 1.087 12.213 7.144 0.000 0.424 9.168 0.000 -6.767 0.000 -8.938 -0.001
M N1 APARTMENT 3.223 -25.361 0.000 0.000 3.752 1.087 12.213 2.690 0.000 0.275 12.360 0.000 -4.432 0.000 -5.806 -0.000
M N2 APARTMENT 3.220 -25.369 0.000 0.000 3.753 1.087 12.213 2.690 0.000 0.275 12.366 0.000 -4.431 0.000 -5.804 -0.000
M S1 APARTMENT 1.007 -35.472 0.000 0.000 3.693 1.087 12.213 9.120 0.000 0.277 18.209 0.000 -4.117 0.000 -6.017 -0.000
M S2 APARTMENT 1.010 -35.479 0.000 0.000 3.693 1.087 12.213 9.119 0.000 0.277 18.213 0.000 -4.116 0.000 -6.018 -0.000
T SW APARTMENT 9.766 -16.374 0.000 0.000 3.772 1.087 12.213 13.393 0.000 0.560 0.000 0.000 -6.392 0.000 -11.758 -6.266
T NW APARTMENT 13.015 -13.438 0.000 0.000 3.800 1.087 12.213 7.050 0.000 0.557 0.000 0.000 -6.669 0.000 -11.519 -6.094
T SE APARTMENT 9.535 -16.434 0.000 0.000 3.777 1.087 12.213 13.506 0.000 0.560 0.000 0.000 -6.268 0.000 -11.758 -6.218
T NE APARTMENT 12.711 -13.512 0.000 0.000 3.808 1.087 12.213 7.083 0.000 0.557 0.000 0.000 -6.457 0.000 -11.503 -5.986
T N1 APARTMENT 7.615 -11.642 0.000 0.000 3.797 1.087 12.213 2.673 0.000 0.363 0.000 0.000 -4.191 0.000 -7.375 -4.539
T N2 APARTMENT 7.614 -11.644 0.000 0.000 3.797 1.087 12.213 2.672 0.000 0.363 0.000 0.000 -4.189 0.000 -7.376 -4.537
T S1 APARTMENT 4.937 -14.974 0.000 0.000 3.758 1.087 12.213 9.069 0.000 0.366 0.000 0.000 -3.896 0.000 -7.600 -4.960
T S2 APARTMENT 4.939 -14.985 0.000 0.000 3.758 1.087 12.213 9.067 0.000 0.366 0.000 0.000 -3.894 0.000 -7.601 -4.950
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.124 0.000 0.029 0.000 0.000 -0.787 0.000 -1.937 -12.010
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.451 0.000 0.870 5.540 0.000 -1.992 0.000 -25.931 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.127 0.000 0.028 0.000 0.000 -0.865 0.000 -1.602 -12.270
Total Facility 140.181 -430.404 0.000 0.000 87.565 95.189 296.854 197.670 0.000 9.303 114.956 0.000 -130.213 0.000 -205.643 -175.460


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 09-JUL-17:08 0.00 -1947.85 0.00 0.00 141.82 87.56 588.62 1791.94 0.00 156.27 0.00 0.00 0.00 0.00 0.00 -818.36
G NW APARTMENT 09-JUL-17:30 0.00 -1918.05 0.00 0.00 141.81 87.56 588.62 1921.83 0.00 146.29 0.00 0.00 0.00 0.00 0.00 -968.06
OFFICE 24-SEP-06:01 0.00 -7561.72 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 7106.95 0.00 -79.28 0.00 -176.41 0.00
G NE APARTMENT 09-JUL-09:45 0.00 -1464.85 0.00 0.00 40.75 12.97 406.15 1673.43 0.00 142.06 0.00 0.00 0.00 0.00 0.00 -810.51
G N1 APARTMENT 09-JUL-17:45 0.00 -1085.53 0.00 0.00 141.81 87.56 588.62 521.32 0.00 82.39 0.00 0.00 0.00 0.00 0.00 -336.17
G N2 APARTMENT 09-JUL-17:45 0.00 -1074.10 0.00 0.00 141.81 87.56 588.62 521.49 0.00 82.39 0.00 0.00 0.00 0.00 0.00 -347.78
G S1 APARTMENT 29-AUG-13:15 0.00 -1302.02 0.00 0.00 40.75 12.97 382.60 1628.32 0.00 69.46 0.00 0.00 0.00 0.00 0.00 -832.09
G S2 APARTMENT 12-AUG-13:30 0.00 -1359.82 0.00 0.00 40.75 12.97 382.60 1399.23 0.00 75.18 0.00 0.00 0.00 0.00 0.00 -550.91
M SW APARTMENT 09-JUL-16:20 0.00 -5230.09 0.00 0.00 84.76 64.86 588.62 1949.90 0.00 270.75 2271.21 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 09-JUL-17:23 0.00 -5073.42 0.00 0.00 141.81 87.56 588.62 1907.62 0.00 209.76 2138.05 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 29-AUG-12:45 0.00 -4718.65 0.00 0.00 40.75 12.97 388.49 2015.45 0.00 174.15 2086.83 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 09-JUL-10:00 0.00 -4171.67 0.00 0.00 40.75 12.97 406.15 1562.96 0.00 218.94 1929.89 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 29-JUN-17:25 0.00 -3062.62 0.00 0.00 141.81 87.56 588.62 492.60 0.00 168.23 1583.81 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 29-JUN-17:25 0.00 -3049.69 0.00 0.00 141.81 87.56 588.62 492.68 0.00 168.23 1570.80 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 08-OCT-13:30 0.00 -3694.60 0.00 0.00 40.75 12.97 382.60 2143.66 0.00 0.00 1192.73 0.00 0.00 0.00 -78.12 0.00
M S2 APARTMENT 08-OCT-13:30 0.00 -3700.22 0.00 0.00 40.75 12.97 382.60 2143.62 0.00 0.00 1198.40 0.00 0.00 0.00 -78.12 0.00
T SW APARTMENT 17-AUG-15:15 0.00 -3607.05 0.00 0.00 48.90 45.40 470.90 2210.83 0.00 272.69 558.33 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 29-JUN-16:04 0.00 -3456.90 0.00 0.00 84.76 64.86 588.62 1833.11 0.00 449.15 436.38 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 17-AUG-14:00 0.00 -3341.24 0.00 0.00 40.75 12.97 382.60 1582.17 0.00 365.75 956.99 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 29-JUN-14:00 0.00 -2865.64 0.00 0.00 40.75 12.97 382.60 865.44 0.00 506.59 1057.28 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-JUN-16:04 0.00 -2283.19 0.00 0.00 84.76 64.86 588.62 425.25 0.00 270.92 848.77 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-16:04 0.00 -2269.47 0.00 0.00 84.76 64.86 588.62 425.43 0.00 270.92 834.88 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 17-AUG-14:00 0.00 -2761.15 0.00 0.00 40.75 12.97 382.60 1264.28 0.00 220.62 839.93 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 17-AUG-14:00 0.00 -2763.34 0.00 0.00 40.75 12.97 382.60 1264.23 0.00 220.62 842.17 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-JUL-15:30 0.00 -63966.69 0.00 0.00 1192.13 4512.09 11708.34 21743.18 0.00 6366.73 18444.23 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 25-DEC-04:00 1992.93 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -845.26 0.00 -1291.02 -276.48
G NW APARTMENT 25-DEC-08:35 2097.39 0.00 0.00 0.00 74.05 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -706.99 0.00 -1195.27 -677.13
OFFICE 20-FEB-07:01 4792.58 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -239.89 0.00 -352.43 -4910.72
G NE APARTMENT 25-DEC-04:00 2021.67 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -848.83 0.00 -1291.02 -301.65
G N1 APARTMENT 14-OCT-06:01 1490.95 0.00 0.00 0.00 161.38 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -327.02 0.00 -120.03 -1630.05
G N2 APARTMENT 14-OCT-06:01 1401.55 0.00 0.00 0.00 163.51 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -325.24 0.00 -120.03 -1544.54
G S1 APARTMENT 02-JAN-08:01 1510.17 0.00 0.00 0.00 74.06 19.46 388.49 412.49 0.00 0.00 0.00 0.00 0.00 0.00 -42.33 -2362.36
G S2 APARTMENT 05-JAN-17:01 1623.85 0.00 0.00 0.00 98.76 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -414.65 0.00 -228.73 -1732.70
M SW APARTMENT 25-DEC-03:15 4516.85 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -838.55 0.00 -1881.93 -2216.21
M NW APARTMENT 13-FEB-11:00 4663.99 0.00 0.00 0.00 47.42 12.97 406.15 0.00 0.00 0.00 0.00 0.00 -228.72 0.00 -2127.32 -2774.49
M SE APARTMENT 25-DEC-02:30 4493.42 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -799.66 0.00 -1893.97 -2225.51
M NE APARTMENT 25-DEC-01:15 4580.92 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -769.50 0.00 -1902.89 -2346.02
M N1 APARTMENT 25-DEC-02:30 2487.98 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -503.99 0.00 -1142.39 -1267.32
M N2 APARTMENT 25-DEC-02:30 2487.30 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -503.96 0.00 -1142.39 -1266.67
M S1 APARTMENT 25-DEC-04:00 2352.51 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -519.86 0.00 -1119.77 -1132.71
M S2 APARTMENT 25-DEC-04:00 2355.49 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -519.81 0.00 -1119.77 -1135.73
T SW APARTMENT 25-DEC-03:00 3806.35 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -807.81 0.00 -2501.13 -923.13
T NW APARTMENT 25-DEC-02:30 3816.42 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -808.06 0.00 -2508.45 -925.62
T SE APARTMENT 25-DEC-02:45 3778.97 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -786.74 0.00 -2504.98 -912.98
T NE APARTMENT 25-DEC-02:15 3768.64 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -787.12 0.00 -2509.39 -897.85
T N1 APARTMENT 25-DEC-05:00 2562.43 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -533.46 0.00 -1455.73 -1006.05
T N2 APARTMENT 25-DEC-05:00 2562.52 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -533.44 0.00 -1455.68 -1006.21
T S1 APARTMENT 25-DEC-06:00 2535.08 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 0.00 0.00 -525.93 0.00 -1448.65 -1045.44
T S2 APARTMENT 25-DEC-06:00 2536.02 0.00 0.00 0.00 189.67 42.16 253.11 0.00 0.00 0.00 0.00 0.00 -525.92 0.00 -1448.65 -1046.39
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 25-DEC-03:15 62648.87 0.00 0.00 0.00 4368.33 1952.47 5387.04 0.00 0.00 0.00 0.00 0.00 -16224.11 0.00 -37105.36 -21027.24



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Sec1.1A-General Information

Data
Weather File Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 49.25
Number of hours cooling loads not met 0.50
Number of hours not met 49.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4276.26 0.00 0.00 0.00 0.00
Exterior Lighting 40.12 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 314.48 109274.00 0.00 0.00
Space Cooling 145.81 28889.37 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 227.26 7206.32 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 389.06 19152.20 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26730.99 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1438.36   314.48   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1438.36
Natural Gas 0.00 314.48
Additional 0.00 0.00
Total 517.65 1752.84


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 46.52
Fans-Interior 72.50
Service Water Heating 124.12
Receptacle Equipment 165.14
Miscellaneous 12.80
Subtotal 458.86


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 100.33
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 100.33


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.76
Space Heating 17.94
Space Cooling 8.32
Fans-Interior 12.97
Service Water Heating 22.20
Receptacle Equipment 29.53
Miscellaneous 2.29



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.169909
G NW APARTMENT DIRECT AIR 0.162384
OFFICE DIRECT AIR 0.461572
G NE APARTMENT DIRECT AIR 0.125464
G N1 APARTMENT DIRECT AIR 0.095524
G N2 APARTMENT DIRECT AIR 0.094591
G S1 APARTMENT DIRECT AIR 0.106931
G S2 APARTMENT DIRECT AIR 0.109779
M SW APARTMENT DIRECT AIR 0.462407
M NW APARTMENT DIRECT AIR 0.439782
M SE APARTMENT DIRECT AIR 0.417480
M NE APARTMENT DIRECT AIR 0.359691
M N1 APARTMENT DIRECT AIR 0.270570
M N2 APARTMENT DIRECT AIR 0.269013
M S1 APARTMENT DIRECT AIR 0.305007
M S2 APARTMENT DIRECT AIR 0.306044
T SW APARTMENT DIRECT AIR 0.321636
T NW APARTMENT DIRECT AIR 0.299862
T SE APARTMENT DIRECT AIR 0.298270
T NE APARTMENT DIRECT AIR 0.254892
T N1 APARTMENT DIRECT AIR 0.198633
T N2 APARTMENT DIRECT AIR 0.198696
T S1 APARTMENT DIRECT AIR 0.239534
T S2 APARTMENT DIRECT AIR 0.240179


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.169909
SPLIT GNW MAIN BRANCH 0.162384
SPLIT OFFICE MAIN BRANCH 0.461572
SPLIT GNE MAIN BRANCH 0.125464
SPLIT GN1 MAIN BRANCH 0.095524
SPLIT GN2 MAIN BRANCH 0.094591
SPLIT GS1 MAIN BRANCH 0.106931
SPLIT GS2 MAIN BRANCH 0.109779
SPLIT MSW MAIN BRANCH 0.462407
SPLIT MNW MAIN BRANCH 0.439782
SPLIT MSE MAIN BRANCH 0.417480
SPLIT MNE MAIN BRANCH 0.359691
SPLIT MN1 MAIN BRANCH 0.270570
SPLIT MN2 MAIN BRANCH 0.269013
SPLIT MS1 MAIN BRANCH 0.305007
SPLIT MS2 MAIN BRANCH 0.306044
SPLIT TSW MAIN BRANCH 0.321636
SPLIT TNW MAIN BRANCH 0.299862
SPLIT TSE MAIN BRANCH 0.298270
SPLIT TNE MAIN BRANCH 0.254892
SPLIT TN1 MAIN BRANCH 0.198633
SPLIT TN2 MAIN BRANCH 0.198696
SPLIT TS1 MAIN BRANCH 0.239534
SPLIT TS2 MAIN BRANCH 0.240179


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.169909
SPLIT GNW 0.162384
SPLIT OFFICE 0.461572
SPLIT GNE 0.125464
SPLIT GN1 0.095524
SPLIT GN2 0.094591
SPLIT GS1 0.106931
SPLIT GS2 0.109779
SPLIT MSW 0.462407
SPLIT MNW 0.439782
SPLIT MSE 0.417480
SPLIT MNE 0.359691
SPLIT MN1 0.270570
SPLIT MN2 0.269013
SPLIT MS1 0.305007
SPLIT MS2 0.306044
SPLIT TSW 0.321636
SPLIT TNW 0.299862
SPLIT TSE 0.298270
SPLIT TNE 0.254892
SPLIT TN1 0.198633
SPLIT TN2 0.198696
SPLIT TS1 0.239534
SPLIT TS2 0.240179


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.169909 0.026898
SPLIT GNW OA CONTROLLER 0.162384 0.025953
SPLIT OFFICE OA CONTROLLER 0.461572 0.038104
SPLIT GNE OA CONTROLLER 0.125464 0.025953
SPLIT GN1 OA CONTROLLER 0.095524 0.025953
SPLIT GN2 OA CONTROLLER 0.094591 0.025953
SPLIT GS1 OA CONTROLLER 0.106931 0.025953
SPLIT GS2 OA CONTROLLER 0.109779 0.025953
SPLIT MSW OA CONTROLLER 0.462407 0.051906
SPLIT MNW OA CONTROLLER 0.439782 0.051906
SPLIT MSE OA CONTROLLER 0.417480 0.051906
SPLIT MNE OA CONTROLLER 0.359691 0.051906
SPLIT MN1 OA CONTROLLER 0.270570 0.051906
SPLIT MN2 OA CONTROLLER 0.269013 0.051906
SPLIT MS1 OA CONTROLLER 0.305007 0.051906
SPLIT MS2 OA CONTROLLER 0.306044 0.051906
SPLIT TSW OA CONTROLLER 0.321636 0.025953
SPLIT TNW OA CONTROLLER 0.299862 0.025953
SPLIT TSE OA CONTROLLER 0.298270 0.025953
SPLIT TNE OA CONTROLLER 0.254892 0.025953
SPLIT TN1 OA CONTROLLER 0.198633 0.025953
SPLIT TN2 OA CONTROLLER 0.198696 0.025953
SPLIT TS1 OA CONTROLLER 0.239534 0.025953
SPLIT TS2 OA CONTROLLER 0.240179 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.169909 3634.27 0.715532
SPLIT GNW COOLING COIL 0.162384 3434.95 0.718709
SPLIT OFFICE COOLING COIL 0.461572 8020.81 0.781229
SPLIT GNE COOLING COIL 0.125464 2795.95 0.704101
SPLIT GN1 COOLING COIL 0.095524 2239.95 0.690542
SPLIT GN2 COOLING COIL 0.094591 2224.18 0.689827
SPLIT GS1 COOLING COIL 0.106931 2546.71 0.686539
SPLIT GS2 COOLING COIL 0.109779 2589.53 0.689007
SPLIT MSW COOLING COIL 0.462407 9355.65 0.731803
SPLIT MNW COOLING COIL 0.439782 8909.12 0.731424
SPLIT MSE COOLING COIL 0.417480 8789.56 0.720069
SPLIT MNE COOLING COIL 0.359691 7556.22 0.720705
SPLIT MN1 COOLING COIL 0.270570 5879.33 0.711081
SPLIT MN2 COOLING COIL 0.269013 5853.62 0.710693
SPLIT MS1 COOLING COIL 0.305007 6717.00 0.707355
SPLIT MS2 COOLING COIL 0.306044 6734.02 0.707593
SPLIT TSW COOLING COIL 0.321636 6330.81 0.740199
SPLIT TNW COOLING COIL 0.299862 5932.82 0.738604
SPLIT TSE COOLING COIL 0.298270 5976.11 0.734755
SPLIT TNE COOLING COIL 0.254892 5269.18 0.725405
SPLIT TN1 COOLING COIL 0.198633 4175.83 0.720495
SPLIT TN2 COOLING COIL 0.198696 4186.89 0.719822
SPLIT TS1 COOLING COIL 0.239534 4860.73 0.730915
SPLIT TS2 COOLING COIL 0.240179 4871.16 0.731079


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.169909 0.169909 0.169909 0.169909 2963.30 3634.27 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.162384 0.162384 0.162384 0.162384 2940.52 3434.95 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.461572 0.461572 0.461572 0.461572 5176.62 8020.81 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.125464 0.125464 0.125464 0.125464 2933.44 2795.95 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.095524 0.095524 0.095524 0.095524 2200.11 2239.95 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.094591 0.094591 0.094591 0.094591 2199.94 2224.18 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.106931 0.106931 0.106931 0.106931 2188.79 2546.71 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.109779 0.109779 0.109779 0.109779 2304.81 2589.53 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.462407 0.462407 0.462407 0.462407 5889.43 9355.65 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.439782 0.439782 0.439782 0.439782 5920.90 8909.12 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.417480 0.417480 0.417480 0.417480 5870.67 8789.56 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.359691 0.359691 0.359691 0.359691 5902.14 7556.22 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.270570 0.270570 0.270570 0.270570 4033.26 5879.33 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.269013 0.269013 0.269013 0.269013 4032.78 5853.62 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.305007 0.305007 0.305007 0.305007 4003.65 6717.00 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.306044 0.306044 0.306044 0.306044 4003.17 6734.02 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.321636 0.321636 0.321636 0.321636 4373.07 6330.81 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.299862 0.299862 0.299862 0.299862 4391.13 5932.82 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.298270 0.298270 0.298270 0.298270 4363.26 5976.11 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.254892 0.254892 0.254892 0.254892 4381.32 5269.18 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.198633 0.198633 0.198633 0.198633 3344.55 4175.83 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.198696 0.198696 0.198696 0.198696 3344.28 4186.89 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.239534 0.239534 0.239534 0.239534 3324.47 4860.73 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.240179 0.240179 0.240179 0.240179 3324.20 4871.16 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.169909
SPLIT GNW SUPPLY FAN 0.162384
SPLIT OFFICE SUPPLY FAN 0.461572
SPLIT GNE SUPPLY FAN 0.125464
SPLIT GN1 SUPPLY FAN 0.095524
SPLIT GN2 SUPPLY FAN 0.094591
SPLIT GS1 SUPPLY FAN 0.106931
SPLIT GS2 SUPPLY FAN 0.109779
SPLIT MSW SUPPLY FAN 0.462407
SPLIT MNW SUPPLY FAN 0.439782
SPLIT MSE SUPPLY FAN 0.417480
SPLIT MNE SUPPLY FAN 0.359691
SPLIT MN1 SUPPLY FAN 0.270570
SPLIT MN2 SUPPLY FAN 0.269013
SPLIT MS1 SUPPLY FAN 0.305007
SPLIT MS2 SUPPLY FAN 0.306044
SPLIT TSW SUPPLY FAN 0.321636
SPLIT TNW SUPPLY FAN 0.299862
SPLIT TSE SUPPLY FAN 0.298270
SPLIT TNE SUPPLY FAN 0.254892
SPLIT TN1 SUPPLY FAN 0.198633
SPLIT TN2 SUPPLY FAN 0.198696
SPLIT TS1 SUPPLY FAN 0.239534
SPLIT TS2 SUPPLY FAN 0.240179


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 2963.30
SPLIT GNW HEATING COIL 2940.52
SPLIT OFFICE HEATING COIL 5176.62
SPLIT GNE HEATING COIL 2933.44
SPLIT GN1 HEATING COIL 2200.11
SPLIT GN2 HEATING COIL 2199.94
SPLIT GS1 HEATING COIL 2188.79
SPLIT GS2 HEATING COIL 2304.81
SPLIT MSW HEATING COIL 5889.43
SPLIT MNW HEATING COIL 5920.90
SPLIT MSE HEATING COIL 5870.67
SPLIT MNE HEATING COIL 5902.14
SPLIT MN1 HEATING COIL 4033.26
SPLIT MN2 HEATING COIL 4032.78
SPLIT MS1 HEATING COIL 4003.65
SPLIT MS2 HEATING COIL 4003.17
SPLIT TSW HEATING COIL 4373.07
SPLIT TNW HEATING COIL 4391.13
SPLIT TSE HEATING COIL 4363.26
SPLIT TNE HEATING COIL 4381.32
SPLIT TN1 HEATING COIL 3344.55
SPLIT TN2 HEATING COIL 3344.28
SPLIT TS1 HEATING COIL 3324.47
SPLIT TS2 HEATING COIL 3324.20



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -0.5
February 21.75 2.24
March 22.08 8.00
April 22.57 13.18
May 23.40 18.32
June 24.34 22.93
July 24.40 25.34
August 24.39 24.28
September 24.33 20.44
October 22.94 12.66
November 22.10 8.91
December 21.81 2.07
     
Annual Sum or Average 22.99 13.21
Minimum of Months 21.71 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.71 2.24
March 21.89 8.00
April 22.28 13.18
May 23.31 18.32
June 24.35 22.93
July 24.40 25.34
August 24.39 24.28
September 24.28 20.44
October 22.49 12.66
November 21.79 8.91
December 21.73 2.07
     
Annual Sum or Average 22.87 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.28 -0.5
February 20.81 2.24
March 22.22 8.00
April 23.53 13.18
May 24.49 18.32
June 26.34 22.93
July 26.90 25.34
August 26.64 24.28
September 26.25 20.44
October 23.77 12.66
November 22.65 8.91
December 20.91 2.07
     
Annual Sum or Average 23.75 13.21
Minimum of Months 20.28 -0.5
Maximum of Months 26.90 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.70 2.24
March 21.85 8.00
April 22.22 13.18
May 23.25 18.32
June 24.34 22.93
July 24.40 25.34
August 24.39 24.28
September 24.27 20.44
October 22.41 12.66
November 21.75 8.91
December 21.72 2.07
     
Annual Sum or Average 22.84 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.71 2.24
March 21.84 8.00
April 22.10 13.18
May 23.13 18.32
June 24.34 22.93
July 24.40 25.34
August 24.39 24.28
September 24.28 20.44
October 22.39 12.66
November 21.76 8.91
December 21.73 2.07
     
Annual Sum or Average 22.82 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.71 2.24
March 21.84 8.00
April 22.09 13.18
May 23.13 18.32
June 24.34 22.93
July 24.40 25.34
August 24.39 24.28
September 24.27 20.44
October 22.38 12.66
November 21.76 8.91
December 21.72 2.07
     
Annual Sum or Average 22.82 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -0.5
February 21.75 2.24
March 22.06 8.00
April 22.47 13.18
May 23.29 18.32
June 24.34 22.93
July 24.40 25.34
August 24.39 24.28
September 24.34 20.44
October 22.99 12.66
November 22.13 8.91
December 21.82 2.07
     
Annual Sum or Average 22.98 13.21
Minimum of Months 21.71 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -0.5
February 21.75 2.24
March 22.08 8.00
April 22.51 13.18
May 23.33 18.32
June 24.35 22.93
July 24.40 25.34
August 24.39 24.28
September 24.36 20.44
October 23.02 12.66
November 22.15 8.91
December 21.82 2.07
     
Annual Sum or Average 23.00 13.21
Minimum of Months 21.71 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 -0.5
February 21.94 2.24
March 22.83 8.00
April 24.14 13.18
May 24.32 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 23.95 12.66
November 23.29 8.91
December 22.13 2.07
     
Annual Sum or Average 23.50 13.21
Minimum of Months 21.78 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.75 2.24
March 22.21 8.00
April 23.92 13.18
May 24.30 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.39 20.44
October 23.60 12.66
November 22.29 8.91
December 21.84 2.07
     
Annual Sum or Average 23.27 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -0.5
February 21.93 2.24
March 22.84 8.00
April 24.13 13.18
May 24.32 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 23.94 12.66
November 23.25 8.91
December 22.09 2.07
     
Annual Sum or Average 23.49 13.21
Minimum of Months 21.76 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.73 2.24
March 22.17 8.00
April 23.86 13.18
May 24.29 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.39 20.44
October 23.56 12.66
November 22.18 8.91
December 21.82 2.07
     
Annual Sum or Average 23.25 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -0.5
February 21.76 2.24
March 22.23 8.00
April 24.00 13.18
May 24.34 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 23.71 12.66
November 22.42 8.91
December 21.88 2.07
     
Annual Sum or Average 23.31 13.21
Minimum of Months 21.71 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -0.5
February 21.76 2.24
March 22.22 8.00
April 24.00 13.18
May 24.34 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 23.71 12.66
November 22.41 8.91
December 21.88 2.07
     
Annual Sum or Average 23.31 13.21
Minimum of Months 21.71 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 -0.5
February 22.08 2.24
March 23.12 8.00
April 24.25 13.18
May 24.36 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 24.12 12.66
November 23.69 8.91
December 22.30 2.07
     
Annual Sum or Average 23.62 13.21
Minimum of Months 21.87 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 -0.5
February 22.08 2.24
March 23.13 8.00
April 24.25 13.18
May 24.36 18.32
June 24.40 22.93
July 24.40 25.34
August 24.40 24.28
September 24.40 20.44
October 24.11 12.66
November 23.68 8.91
December 22.30 2.07
     
Annual Sum or Average 23.62 13.21
Minimum of Months 21.87 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -0.5
February 21.91 2.24
March 22.52 8.00
April 23.51 13.18
May 24.04 18.32
June 24.37 22.93
July 24.40 25.34
August 24.39 24.28
September 24.32 20.44
October 23.43 12.66
November 22.57 8.91
December 22.00 2.07
     
Annual Sum or Average 23.27 13.21
Minimum of Months 21.76 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.75 2.24
March 22.16 8.00
April 23.29 13.18
May 24.00 18.32
June 24.36 22.93
July 24.40 25.34
August 24.39 24.28
September 24.27 20.44
October 23.03 12.66
November 22.03 8.91
December 21.82 2.07
     
Annual Sum or Average 23.11 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 -0.5
February 21.90 2.24
March 22.54 8.00
April 23.50 13.18
May 24.04 18.32
June 24.37 22.93
July 24.40 25.34
August 24.39 24.28
September 24.31 20.44
October 23.42 12.66
November 22.53 8.91
December 21.96 2.07
     
Annual Sum or Average 23.27 13.21
Minimum of Months 21.74 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.73 2.24
March 22.12 8.00
April 23.24 13.18
May 23.98 18.32
June 24.36 22.93
July 24.40 25.34
August 24.39 24.28
September 24.26 20.44
October 22.99 12.66
November 21.96 8.91
December 21.80 2.07
     
Annual Sum or Average 23.08 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.74 2.24
March 22.13 8.00
April 23.35 13.18
May 24.04 18.32
June 24.37 22.93
July 24.40 25.34
August 24.39 24.28
September 24.29 20.44
October 23.06 12.66
November 22.00 8.91
December 21.82 2.07
     
Annual Sum or Average 23.12 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -0.5
February 21.74 2.24
March 22.13 8.00
April 23.35 13.18
May 24.04 18.32
June 24.37 22.93
July 24.40 25.34
August 24.39 24.28
September 24.29 20.44
October 23.05 12.66
November 22.00 8.91
December 21.82 2.07
     
Annual Sum or Average 23.11 13.21
Minimum of Months 21.70 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -0.5
February 21.97 2.24
March 22.63 8.00
April 23.68 13.18
May 24.12 18.32
June 24.38 22.93
July 24.40 25.34
August 24.40 24.28
September 24.35 20.44
October 23.57 12.66
November 22.72 8.91
December 22.06 2.07
     
Annual Sum or Average 23.35 13.21
Minimum of Months 21.80 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -0.5
February 21.97 2.24
March 22.64 8.00
April 23.68 13.18
May 24.12 18.32
June 24.38 22.93
July 24.40 25.34
August 24.40 24.28
September 24.35 20.44
October 23.57 12.66
November 22.72 8.91
December 22.06 2.07
     
Annual Sum or Average 23.35 13.21
Minimum of Months 21.80 -0.5
Maximum of Months 24.40 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.93 -0.5
February 21.40 2.24
March 22.79 8.00
April 24.63 13.18
May 25.84 18.32
June 26.74 22.93
July 27.04 25.34
August 26.92 24.28
September 26.30 20.44
October 24.31 12.66
November 22.74 8.91
December 21.39 2.07
     
Annual Sum or Average 24.27 13.21
Minimum of Months 20.93 -0.5
Maximum of Months 27.04 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.40 -0.5
February 19.02 2.24
March 20.48 8.00
April 21.95 13.18
May 23.53 18.32
June 25.95 22.93
July 26.62 25.34
August 26.42 24.28
September 25.48 20.44
October 22.26 12.66
November 20.80 8.91
December 19.09 2.07
     
Annual Sum or Average 22.52 13.21
Minimum of Months 18.40 -0.5
Maximum of Months 26.62 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.84 -0.5
February 23.12 2.24
March 24.19 8.00
April 25.96 13.18
May 26.48 18.32
June 26.84 22.93
July 26.95 25.34
August 26.90 24.28
September 26.67 20.44
October 25.76 12.66
November 24.55 8.91
December 23.23 2.07
     
Annual Sum or Average 25.30 13.21
Minimum of Months 22.84 -0.5
Maximum of Months 26.95 25.34



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:16

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.114521E+12 73480.652 02-JAN-18:15 4979.953 26630.920 7206.318 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32110.461 0.000 0.000 0.000
February 0.103548E+12 70262.452 07-FEB-18:00 4979.953 26630.920 7206.318 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 28892.260 0.000 0.000 0.000
March 0.114773E+12 74433.157 28-MAR-16:45 4276.255 26730.986 7206.318 0.000 11910.405 0.000 0.000 0.000 0.000 0.000 0.000 24309.193 0.000 0.000 0.000
April 0.111653E+12 70259.445 09-APR-17:00 4979.953 26630.920 7206.318 0.000 4229.753 0.000 0.000 0.000 0.000 0.000 0.000 27212.501 0.000 0.000 0.000
May 0.123419E+12 80100.947 29-MAY-17:15 4979.953 26630.920 7206.318 0.000 21139.559 0.000 0.000 0.000 0.000 0.000 0.000 20144.196 0.000 0.000 0.000
June 0.130418E+12 82480.940 29-JUN-16:30 4276.255 26730.986 7206.318 0.000 25100.617 0.000 0.000 0.000 0.000 0.000 0.000 19166.763 0.000 0.000 0.000
July 0.141687E+12 86255.132 09-JUL-16:30 4276.255 26730.986 7206.318 0.000 28889.374 0.000 0.000 0.000 0.000 0.000 0.000 19152.199 0.000 0.000 0.000
August 0.138183E+12 83784.852 13-AUG-16:00 4276.255 26730.986 7206.318 0.000 26435.800 0.000 0.000 0.000 0.000 0.000 0.000 19135.493 0.000 0.000 0.000
September 0.124458E+12 85147.331 02-SEP-16:15 4276.255 26630.920 7206.318 0.000 23911.821 0.000 0.000 0.000 0.000 0.000 0.000 23122.017 0.000 0.000 0.000
October 0.114202E+12 71933.292 02-OCT-17:30 4979.953 26630.920 7206.318 0.000 9614.436 0.000 0.000 0.000 0.000 0.000 0.000 23501.664 0.000 0.000 0.000
November 0.108245E+12 67651.701 29-NOV-18:15 4979.953 26630.920 7206.318 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 26281.510 0.000 0.000 0.000
December 0.113257E+12 68858.641 27-DEC-18:45 4979.953 26630.920 7206.318 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 27488.449 0.000 0.000 0.000
                                     
Annual Sum or Average 0.143836E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.103548E+12 67651.701   4276.255 26630.920 7206.318 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 19135.493 0.000 0.000 0.000
Maximum of Months 0.141687E+12 86255.132   4979.953 26730.986 7206.318 0.000 28889.374 2553.000 0.000 0.000 0.000 0.000 0.000 32110.461 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:16

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.101971E+12 99577.070 18-JAN-04:00 99577.070 0.000 0.000 0.000 0.000 0.000 99577.070
February 0.736810E+11 98912.258 13-FEB-02:00 98912.258 0.000 0.000 0.000 0.000 0.000 98912.258
March 0.292843E+11 51832.814 18-MAR-01:00 51832.814 0.000 0.000 0.000 0.000 0.000 51832.814
April 0.356713E+10 24857.964 17-APR-04:00 24857.964 0.000 0.000 0.000 0.000 0.000 24857.964
May 0.732273E+09 14401.992 05-MAY-04:00 14401.992 0.000 0.000 0.000 0.000 0.000 14401.992
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.656559E+10 29226.784 27-OCT-06:30 29226.784 0.000 0.000 0.000 0.000 0.000 29226.784
November 0.183519E+11 38278.106 23-NOV-04:00 38278.106 0.000 0.000 0.000 0.000 0.000 38278.106
December 0.803272E+11 109273.997 25-DEC-06:00 109273.997 0.000 0.000 0.000 0.000 0.000 109273.997
                     
Annual Sum or Average 0.314481E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.101971E+12 109273.997   109273.997 0.000 0.000 0.000 0.000 0.000 109273.997