Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Simulation Timestamp: 2015-09-09 18:47:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1725.14 | 550.35 | 610.89 |
Net Site Energy | 1725.14 | 550.35 | 610.89 |
Total Source Energy | 4893.08 | 1560.98 | 1732.69 |
Net Source Energy | 4893.08 | 1560.98 | 1732.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 273.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 105.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 261.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 407.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1451.29 | 273.85 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 273.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 105.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 261.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 407.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 274.48 | 96.97 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 513.92 | 96.97 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 247.28 | 87.36 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 462.99 | 87.36 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1451.29 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1451.29 | 100.00 |
Total On-Site and Utility Electric Sources | 1451.29 | 100.00 |
Total Electricity End Uses | 1451.29 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 46.25 |
Time Setpoint Not Met During Occupied Cooling | 0.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1791.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Latitude [deg] | 43.62 |
Longitude [deg] | -116.2 |
Elevation [m] | 701.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUL-17:00 | 04-JAN-07:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 80039.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23997.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23607.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87515.24 | 80039.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 80039.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23997.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23607.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 296.85 | 0.00 | 0.00 | 0.00 |
Cooling | 335.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 828.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1290.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4596.23 | 296.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 105.12 | 0.00 | 0.00 | 0.00 |
Cooling | 118.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 293.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 457.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1627.57 | 105.12 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 105.12 | 0.00 | 0.00 | 0.00 |
Cooling | 118.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 293.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 457.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1627.57 | 105.12 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 2.30 | 120.00 |
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 16.70 | 17.90 | Wetbulb [C] | 4.20 | 330.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.58 | 83.58 | 40.06 | |
Exterior Lighting Total | 2553.00 | 40.06 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3394.82 | 2711.29 | 683.53 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3126.95 | 2497.36 | 629.60 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8192.01 | 6542.59 | 1649.42 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2300.66 | 1837.43 | 463.23 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1715.86 | 1370.38 | 345.48 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1695.05 | 1353.76 | 341.29 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2212.37 | 1744.57 | 467.79 | 0.79 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2259.55 | 1783.34 | 476.21 | 0.79 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9138.95 | 7298.87 | 1840.08 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8348.72 | 6667.75 | 1680.97 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8281.29 | 6613.90 | 1667.40 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6667.30 | 5324.87 | 1342.42 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4846.87 | 3870.98 | 975.89 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4812.79 | 3843.76 | 969.03 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6080.81 | 4856.47 | 1224.34 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6103.03 | 4874.22 | 1228.81 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6273.59 | 5010.44 | 1263.16 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5693.30 | 4546.98 | 1146.32 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5870.78 | 4688.73 | 1182.05 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4706.02 | 3758.49 | 947.53 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3632.62 | 2901.21 | 731.41 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3633.57 | 2901.97 | 731.60 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4732.26 | 3779.45 | 952.82 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4745.75 | 3790.22 | 955.53 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3234.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2978.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7804.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2191.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1634.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1614.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2110.5 | 3.14 | 10.73 | 11.15 | 10.46 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2155.3 | 3.14 | 10.73 | 11.15 | 10.46 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8706.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7953.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7889.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6351.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4617.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4584.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5792.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5814.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5976.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5423.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5592.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4483.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3460.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3461.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4508.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4521.1 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 3090.00 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 3042.14 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5450.83 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 3049.53 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2320.92 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2321.09 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2331.74 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2452.70 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 5913.15 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 5887.20 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 5932.81 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 5906.88 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 4095.72 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 4096.22 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 4124.14 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 4124.64 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4458.36 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4446.32 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4468.76 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4456.75 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3492.72 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3493.00 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3503.36 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3503.64 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 238.07 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 219.28 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 574.48 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 161.34 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 120.33 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 118.87 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 150.88 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 154.40 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.55 | 640.88 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.50 | 585.47 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.50 | 580.74 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 467.55 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 339.89 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 337.50 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 426.42 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 427.98 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 439.94 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 399.25 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 411.70 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 330.02 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 254.74 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 254.81 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 331.86 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 332.80 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2007.31 | 2408.77 | 0.171 | 0.205 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
G NW APARTMENT | 1848.92 | 2218.71 | 0.157 | 0.189 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.44 | 0.00627 |
OFFICE | 4741.51 | 5689.81 | 0.412 | 0.495 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.52 | 0.00627 |
G NE APARTMENT | 1360.37 | 1632.44 | 0.116 | 0.139 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
G N1 APARTMENT | 1014.55 | 1217.46 | 0.086 | 0.104 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.19 | 0.00627 |
G N2 APARTMENT | 1002.25 | 1202.70 | 0.085 | 0.102 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.19 | 0.00627 |
G S1 APARTMENT | 1272.20 | 1526.65 | 0.108 | 0.130 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
G S2 APARTMENT | 1301.85 | 1562.22 | 0.111 | 0.133 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
M SW APARTMENT | 5403.77 | 6484.52 | 0.460 | 0.552 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
M NW APARTMENT | 4936.52 | 5923.82 | 0.420 | 0.504 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
M SE APARTMENT | 4896.73 | 5876.08 | 0.417 | 0.500 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 36.70 | 0.00627 |
M NE APARTMENT | 3942.38 | 4730.85 | 0.336 | 0.403 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
M N1 APARTMENT | 2865.87 | 3439.05 | 0.244 | 0.293 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.19 | 0.00627 |
M N2 APARTMENT | 2845.72 | 3414.86 | 0.242 | 0.291 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 30.19 | 0.00627 |
M S1 APARTMENT | 3595.53 | 4314.63 | 0.306 | 0.367 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
M S2 APARTMENT | 3608.67 | 4330.40 | 0.307 | 0.369 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
T SW APARTMENT | 3709.63 | 4451.56 | 0.316 | 0.379 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 35.03 | 0.00627 |
T NW APARTMENT | 3366.43 | 4039.71 | 0.287 | 0.344 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.11 | 0.00627 |
T SE APARTMENT | 3471.45 | 4165.74 | 0.296 | 0.355 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
T NE APARTMENT | 2782.71 | 3339.26 | 0.237 | 0.284 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.70 | 0.00627 |
T N1 APARTMENT | 2147.95 | 2577.54 | 0.183 | 0.219 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 35.95 | 0.00627 |
T N2 APARTMENT | 2148.52 | 2578.22 | 0.183 | 0.220 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 36.20 | 0.00627 |
T S1 APARTMENT | 2798.17 | 3357.80 | 0.238 | 0.286 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.70 | 0.00627 |
T S2 APARTMENT | 2806.15 | 3367.37 | 0.239 | 0.287 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.70 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1651.11 | 1981.33 | 0.052 | 0.062 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G NW APARTMENT | 1644.44 | 1973.33 | 0.051 | 0.062 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
OFFICE | 3296.07 | 3955.29 | 0.100 | 0.120 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G NE APARTMENT | 1650.70 | 1980.84 | 0.052 | 0.062 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G N1 APARTMENT | 1034.54 | 1241.44 | 0.032 | 0.039 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G N2 APARTMENT | 1034.69 | 1241.62 | 0.032 | 0.039 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G S1 APARTMENT | 1043.69 | 1252.43 | 0.033 | 0.039 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
G S2 APARTMENT | 1145.97 | 1375.17 | 0.036 | 0.043 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
M SW APARTMENT | 3144.28 | 3773.13 | 0.098 | 0.118 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M NW APARTMENT | 3122.33 | 3746.80 | 0.098 | 0.117 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M SE APARTMENT | 3160.90 | 3793.08 | 0.099 | 0.119 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M NE APARTMENT | 3138.97 | 3766.76 | 0.098 | 0.118 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M N1 APARTMENT | 1607.31 | 1928.77 | 0.050 | 0.060 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M N2 APARTMENT | 1607.73 | 1929.28 | 0.050 | 0.060 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M S1 APARTMENT | 1631.34 | 1957.61 | 0.051 | 0.061 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
M S2 APARTMENT | 1631.76 | 1958.11 | 0.051 | 0.061 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T SW APARTMENT | 2842.15 | 3410.57 | 0.089 | 0.107 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T NW APARTMENT | 2831.97 | 3398.36 | 0.089 | 0.106 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T SE APARTMENT | 2850.95 | 3421.14 | 0.089 | 0.107 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T NE APARTMENT | 2840.79 | 3408.94 | 0.089 | 0.107 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T N1 APARTMENT | 2025.51 | 2430.62 | 0.063 | 0.076 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T N2 APARTMENT | 2025.75 | 2430.90 | 0.063 | 0.076 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T S1 APARTMENT | 2034.52 | 2441.42 | 0.064 | 0.076 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
T S2 APARTMENT | 2034.75 | 2441.70 | 0.064 | 0.076 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -16.30 | 0.00098 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.21 | 0.21 | 0.06 | 0.06 |
SPLIT GNW | 0.19 | 0.19 | 0.06 | 0.06 |
SPLIT OFFICE | 0.49 | 0.49 | 0.12 | 0.12 |
SPLIT GNE | 0.14 | 0.14 | 0.06 | 0.06 |
SPLIT GN1 | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT GN2 | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT GS1 | 0.13 | 0.13 | 0.04 | 0.04 |
SPLIT GS2 | 0.13 | 0.13 | 0.04 | 0.04 |
SPLIT MSW | 0.55 | 0.55 | 0.12 | 0.12 |
SPLIT MNW | 0.50 | 0.50 | 0.12 | 0.12 |
SPLIT MSE | 0.50 | 0.50 | 0.12 | 0.12 |
SPLIT MNE | 0.40 | 0.40 | 0.12 | 0.12 |
SPLIT MN1 | 0.29 | 0.29 | 0.06 | 0.06 |
SPLIT MN2 | 0.29 | 0.29 | 0.06 | 0.06 |
SPLIT MS1 | 0.37 | 0.37 | 0.06 | 0.06 |
SPLIT MS2 | 0.37 | 0.37 | 0.06 | 0.06 |
SPLIT TSW | 0.38 | 0.38 | 0.11 | 0.11 |
SPLIT TNW | 0.34 | 0.34 | 0.11 | 0.11 |
SPLIT TSE | 0.35 | 0.35 | 0.11 | 0.11 |
SPLIT TNE | 0.28 | 0.28 | 0.11 | 0.11 |
SPLIT TN1 | 0.22 | 0.22 | 0.08 | 0.08 |
SPLIT TN2 | 0.22 | 0.22 | 0.08 | 0.08 |
SPLIT TS1 | 0.29 | 0.29 | 0.08 | 0.08 |
SPLIT TS2 | 0.29 | 0.29 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1303.25 | 6247.50 | 515.75 |
G NW APARTMENT | 1494.25 | 6619.75 | 999.50 |
OFFICE | 304.75 | 1543.25 | 52.00 |
G NE APARTMENT | 1471.50 | 6588.25 | 974.50 |
G N1 APARTMENT | 616.00 | 6873.50 | 419.00 |
G N2 APARTMENT | 615.50 | 6874.25 | 418.00 |
G S1 APARTMENT | 576.50 | 6364.00 | 148.25 |
G S2 APARTMENT | 713.00 | 6295.25 | 193.25 |
M SW APARTMENT | 1756.75 | 4099.00 | 27.50 |
M NW APARTMENT | 1350.25 | 4863.75 | 157.75 |
M SE APARTMENT | 1812.75 | 4094.25 | 27.50 |
M NE APARTMENT | 1374.50 | 4915.75 | 164.25 |
M N1 APARTMENT | 781.25 | 4791.75 | 23.25 |
M N2 APARTMENT | 783.50 | 4799.00 | 22.75 |
M S1 APARTMENT | 1310.00 | 3771.25 | 0.00 |
M S2 APARTMENT | 1310.75 | 3770.50 | 0.00 |
T SW APARTMENT | 2920.25 | 5237.50 | 1108.25 |
T NW APARTMENT | 3118.25 | 5772.00 | 1686.75 |
T SE APARTMENT | 3008.25 | 5177.50 | 1114.25 |
T NE APARTMENT | 3169.50 | 5751.25 | 1651.75 |
T N1 APARTMENT | 2279.75 | 5839.25 | 1146.00 |
T N2 APARTMENT | 2282.25 | 5837.00 | 1146.75 |
T S1 APARTMENT | 2224.50 | 5121.50 | 609.50 |
T S2 APARTMENT | 2228.25 | 5113.25 | 611.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4182.25 | 6936.75 | 1791.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.50 | 0.00 | 4.50 | 0.00 |
G NW APARTMENT | 1.50 | 0.25 | 1.50 | 0.25 |
OFFICE | 5.00 | 7.50 | 0.00 | 0.00 |
G NE APARTMENT | 6.50 | 0.00 | 6.50 | 0.00 |
G N1 APARTMENT | 8.25 | 0.00 | 8.25 | 0.00 |
G N2 APARTMENT | 6.75 | 0.50 | 6.75 | 0.50 |
G S1 APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
G S2 APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
M SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
M SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M NE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M N1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M N2 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M S2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T N2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
T S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 51.25 | 8.25 | 46.25 | 0.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.372 | 0.152 | 0.000 | 0.057 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.152 | 0.000 | 0.055 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.528 | 0.167 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.152 | 0.000 | 0.055 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.054 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.054 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.057 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.092 | 0.000 | 0.057 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.219 | 0.000 | 0.068 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.219 | 0.000 | 0.066 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.219 | 0.000 | 0.068 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.219 | 0.000 | 0.066 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.132 | 0.000 | 0.066 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.132 | 0.000 | 0.066 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.132 | 0.000 | 0.068 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.132 | 0.000 | 0.068 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.289 | 0.000 | 0.080 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.289 | 0.000 | 0.077 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.289 | 0.000 | 0.080 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.289 | 0.000 | 0.077 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.174 | 0.000 | 0.077 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.359 | 0.174 | 0.000 | 0.077 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.174 | 0.000 | 0.080 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.360 | 0.174 | 0.000 | 0.080 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.361 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.511 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.392 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.348 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1451.29 | 21411.80 | 25-APR-03:00 | 87515.24 | 29-JUL-18:00 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 407.59 | 0.00 | 01-JAN-00:15 | 32681.37 | 26-JAN-07:30 |
WaterSystems:Electricity | 407.59 | 0.00 | 01-JAN-00:15 | 32681.37 | 26-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 407.59 | 0.00 | 01-JAN-00:15 | 32681.37 | 26-JAN-07:30 |
Fans:Electricity | 261.72 | 8299.19 | 25-MAR-17:15 | 8299.19 | 13-JAN-06:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
ElectricityPurchased:Plant | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
Cogeneration:ElectricityPurchased | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
ElectricityNet:Plant | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
Cogeneration:ElectricityNet | 1451.29 | 21411.80 | 01-JAN-03:15 | 87515.24 | 29-JUL-18:00 |
ExteriorLights:Electricity | 40.06 | 0.00 | 01-JAN-08:30 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.06 | 0.00 | 01-JAN-08:30 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 367.53 | 8299.19 | 25-MAR-17:15 | 33747.40 | 21-JUL-17:15 |
General:Fans:Electricity | 261.72 | 8299.19 | 25-MAR-17:15 | 8299.19 | 13-JAN-06:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 105.80 | 0.00 | 01-JAN-00:15 | 25448.21 | 21-JUL-17:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 273.85 | 0.00 | 10-FEB-15:15 | 80039.05 | 04-JAN-08:00 |
Gas:HVAC | 273.85 | 0.00 | 10-FEB-15:15 | 80039.05 | 04-JAN-08:00 |
Heating:Gas | 273.85 | 0.00 | 10-FEB-15:15 | 80039.05 | 04-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1153.75 | 1732.55 | 03-MAR-18:45 | 158737.23 | 31-JUL-18:00 |
EnergyTransfer:Building | 526.66 | 1732.55 | 03-MAR-18:45 | 69419.46 | 31-JUL-18:00 |
EnergyTransfer:Zone:G SW APARTMENT | 12.54 | 0.02 | 03-MAY-01:00 | 2350.23 | 31-JUL-18:00 |
Heating:EnergyTransfer | 121.96 | 0.00 | 05-FEB-16:30 | 45607.37 | 04-JAN-08:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 4.36 | 0.00 | 01-JAN-13:30 | 1502.64 | 04-JAN-08:00 |
Cooling:EnergyTransfer | 404.70 | 0.00 | 02-JAN-07:45 | 69129.83 | 22-JUL-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 8.18 | 0.00 | 01-JAN-00:15 | 2350.23 | 31-JUL-18:00 |
EnergyTransfer:Zone:G NW APARTMENT | 11.98 | 0.02 | 06-NOV-14:45 | 2188.99 | 31-JUL-18:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.40 | 0.00 | 26-JAN-16:45 | 1577.79 | 28-DEC-10:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 5.58 | 0.00 | 01-JAN-00:15 | 2188.99 | 31-JUL-18:00 |
EnergyTransfer:Zone:OFFICE | 22.89 | 0.00 | 31-OCT-23:15 | 4594.36 | 06-AUG-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 2.54 | 0.00 | 01-JAN-00:15 | 2452.81 | 04-JAN-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 20.35 | 0.00 | 02-JAN-07:30 | 4594.36 | 06-AUG-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 12.04 | 0.01 | 03-NOV-13:15 | 1542.96 | 04-JAN-08:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.25 | 0.00 | 05-FEB-16:30 | 1542.96 | 04-JAN-08:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 5.79 | 0.00 | 01-JAN-00:15 | 1504.90 | 12-JUL-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 7.84 | 0.03 | 07-OCT-12:30 | 1153.75 | 12-JUL-19:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.10 | 0.00 | 18-JAN-17:15 | 911.86 | 04-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.74 | 0.00 | 01-JAN-00:15 | 1153.75 | 12-JUL-19:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 7.84 | 0.01 | 30-NOV-15:45 | 1142.13 | 12-JUL-19:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.09 | 0.00 | 18-JAN-17:15 | 911.91 | 04-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.75 | 0.00 | 01-JAN-00:15 | 1142.13 | 12-JUL-19:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 9.27 | 0.04 | 06-APR-10:45 | 1491.13 | 26-SEP-14:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.69 | 0.00 | 01-JAN-13:00 | 876.00 | 04-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.58 | 0.00 | 01-JAN-00:15 | 1491.13 | 26-SEP-14:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 9.78 | 0.00 | 16-APR-10:45 | 1500.92 | 26-SEP-14:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.86 | 0.00 | 01-JAN-13:15 | 924.36 | 04-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 7.92 | 0.00 | 01-JAN-00:15 | 1500.92 | 26-SEP-14:30 |
EnergyTransfer:Zone:M SW APARTMENT | 39.41 | 0.05 | 13-FEB-13:15 | 6195.66 | 31-JUL-18:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 3.70 | 0.00 | 01-JAN-10:00 | 3008.79 | 28-DEC-08:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 35.71 | 0.00 | 01-JAN-00:15 | 6195.66 | 31-JUL-18:00 |
EnergyTransfer:Zone:M NW APARTMENT | 31.64 | 0.01 | 31-JAN-14:15 | 5724.64 | 31-JUL-18:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 7.52 | 0.00 | 03-JAN-17:15 | 3450.82 | 28-DEC-10:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 24.12 | 0.00 | 01-JAN-00:15 | 5724.64 | 31-JUL-18:00 |
EnergyTransfer:Zone:M SE APARTMENT | 40.39 | 0.00 | 28-OCT-01:15 | 5273.55 | 22-JUL-14:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 3.81 | 0.00 | 01-JAN-13:15 | 3018.19 | 28-DEC-08:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 36.58 | 0.00 | 01-JAN-00:15 | 5273.55 | 22-JUL-14:15 |
EnergyTransfer:Zone:M NE APARTMENT | 32.49 | 0.01 | 26-NOV-19:15 | 4270.68 | 22-JUL-16:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 7.50 | 0.00 | 03-JAN-17:30 | 3216.15 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 24.98 | 0.00 | 01-JAN-00:15 | 4270.68 | 22-JUL-16:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 24.36 | 0.02 | 06-MAR-00:45 | 3331.58 | 23-JUN-19:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.83 | 0.00 | 01-JAN-10:00 | 1652.36 | 28-DEC-10:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 22.53 | 0.00 | 01-JAN-00:15 | 3331.58 | 23-JUN-19:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 24.38 | 0.26 | 11-APR-11:45 | 3306.49 | 23-JUN-19:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.83 | 0.00 | 01-JAN-10:00 | 1643.95 | 28-DEC-10:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 22.54 | 0.00 | 01-JAN-00:15 | 3306.49 | 23-JUN-19:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 36.61 | 0.25 | 14-JAN-20:45 | 4441.80 | 01-OCT-15:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.52 | 0.00 | 01-JAN-02:15 | 1368.67 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 36.08 | 0.00 | 01-JAN-00:15 | 4441.80 | 01-OCT-15:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 36.63 | 0.01 | 29-NOV-02:45 | 4440.24 | 01-OCT-15:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.53 | 0.00 | 01-JAN-02:15 | 1369.29 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 36.10 | 0.00 | 01-JAN-00:15 | 4440.24 | 01-OCT-15:15 |
EnergyTransfer:Zone:T SW APARTMENT | 25.03 | 0.00 | 15-APR-05:00 | 4129.67 | 31-JUL-18:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 9.21 | 0.00 | 01-JAN-13:30 | 2843.61 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 15.82 | 0.00 | 01-JAN-00:15 | 4129.67 | 31-JUL-18:00 |
EnergyTransfer:Zone:T NW APARTMENT | 23.51 | 0.01 | 12-OCT-13:00 | 3918.65 | 31-JUL-18:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 12.16 | 0.00 | 26-JAN-16:15 | 2908.84 | 28-DEC-10:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 11.35 | 0.00 | 01-JAN-00:15 | 3918.65 | 31-JUL-18:00 |
EnergyTransfer:Zone:T SE APARTMENT | 24.89 | 0.01 | 30-APR-22:45 | 3611.55 | 22-JUL-14:15 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 9.01 | 0.00 | 01-JAN-13:45 | 2851.77 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 15.88 | 0.00 | 01-JAN-00:15 | 3611.55 | 22-JUL-14:15 |
EnergyTransfer:Zone:T NE APARTMENT | 23.17 | 0.00 | 25-OCT-11:30 | 3014.55 | 12-JUL-16:45 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 11.79 | 0.00 | 30-JAN-17:30 | 2901.51 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 11.38 | 0.00 | 01-JAN-00:15 | 3014.55 | 12-JUL-16:45 |
EnergyTransfer:Zone:T N1 APARTMENT | 16.29 | 0.03 | 19-MAR-10:15 | 2417.35 | 12-JUL-17:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.00 | 0.00 | 26-JAN-17:15 | 1913.32 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 9.30 | 0.00 | 01-JAN-00:15 | 2417.35 | 12-JUL-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 16.31 | 0.06 | 04-NOV-02:15 | 2400.02 | 12-JUL-17:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.00 | 0.00 | 26-JAN-17:15 | 1913.51 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 9.31 | 0.00 | 01-JAN-00:15 | 2400.02 | 12-JUL-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 18.67 | 0.04 | 15-SEP-05:45 | 2959.34 | 01-OCT-14:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 4.62 | 0.00 | 01-JAN-13:15 | 1858.53 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.05 | 0.00 | 01-JAN-00:15 | 2959.34 | 01-OCT-14:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 18.71 | 0.01 | 11-APR-24:00 | 2962.77 | 01-OCT-14:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 4.63 | 0.00 | 01-JAN-13:15 | 1858.55 | 04-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.08 | 0.00 | 01-JAN-00:15 | 2962.77 | 01-OCT-14:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 627.10 | 0.00 | 03-MAR-17:30 | 89607.00 | 12-JUL-17:00 |
HeatingCoils:EnergyTransfer | 219.08 | 0.00 | 10-FEB-15:15 | 64031.24 | 04-JAN-08:00 |
CoolingCoils:EnergyTransfer | 408.02 | 0.00 | 01-JAN-00:15 | 89607.00 | 12-JUL-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 4.358 | -8.182 | 0.000 | 0.000 | 3.843 | 1.087 | 12.213 | 15.610 | 0.000 | 0.251 | 0.000 | 0.000 | -7.435 | 0.000 | -5.235 | -16.509 |
G NW APARTMENT | 6.400 | -5.582 | 0.000 | 0.000 | 3.869 | 1.087 | 12.213 | 7.838 | 0.000 | 0.251 | 0.000 | 0.000 | -7.581 | 0.000 | -5.105 | -13.390 |
OFFICE | 2.542 | -20.347 | 0.000 | 0.000 | 0.522 | 26.452 | 9.482 | 15.387 | 0.000 | 0.148 | 0.001 | 0.000 | -7.432 | 0.000 | -4.794 | -21.960 |
G NE APARTMENT | 6.247 | -5.794 | 0.000 | 0.000 | 3.881 | 1.087 | 12.213 | 7.847 | 0.000 | 0.251 | 0.000 | 0.000 | -7.350 | 0.000 | -5.093 | -13.289 |
G N1 APARTMENT | 3.098 | -4.742 | 0.000 | 0.000 | 3.883 | 1.087 | 12.213 | 2.564 | 0.000 | 0.160 | 0.000 | 0.000 | -4.688 | 0.000 | -3.262 | -10.312 |
G N2 APARTMENT | 3.094 | -4.747 | 0.000 | 0.000 | 3.884 | 1.087 | 12.213 | 2.563 | 0.000 | 0.160 | 0.000 | 0.000 | -4.687 | 0.000 | -3.262 | -10.304 |
G S1 APARTMENT | 1.691 | -7.580 | 0.000 | 0.000 | 3.846 | 1.087 | 12.213 | 10.376 | 0.000 | 0.159 | 0.000 | 0.000 | -4.519 | 0.000 | -3.399 | -13.873 |
G S2 APARTMENT | 1.859 | -7.923 | 0.000 | 0.000 | 3.843 | 1.087 | 12.213 | 10.368 | 0.000 | 0.159 | 0.000 | 0.000 | -4.524 | 0.000 | -3.407 | -13.673 |
M SW APARTMENT | 3.702 | -35.712 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 15.157 | 0.000 | 0.356 | 15.279 | 0.000 | -8.115 | 0.000 | -7.687 | -0.001 |
M NW APARTMENT | 7.520 | -24.118 | 0.000 | 0.000 | 3.769 | 1.087 | 12.213 | 7.468 | 0.000 | 0.355 | 7.403 | 0.000 | -8.185 | 0.000 | -7.512 | -0.001 |
M SE APARTMENT | 3.810 | -36.582 | 0.000 | 0.000 | 3.727 | 1.087 | 12.213 | 15.179 | 0.000 | 0.356 | 15.795 | 0.000 | -7.901 | 0.000 | -7.682 | -0.000 |
M NE APARTMENT | 7.504 | -24.983 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 7.461 | 0.000 | 0.355 | 8.020 | 0.000 | -7.933 | 0.000 | -7.501 | -0.001 |
M N1 APARTMENT | 1.833 | -22.527 | 0.000 | 0.000 | 3.762 | 1.087 | 12.213 | 2.336 | 0.000 | 0.223 | 11.047 | 0.000 | -5.130 | 0.000 | -4.844 | -0.000 |
M N2 APARTMENT | 1.834 | -22.542 | 0.000 | 0.000 | 3.763 | 1.087 | 12.213 | 2.336 | 0.000 | 0.223 | 11.060 | 0.000 | -5.129 | 0.000 | -4.843 | -0.000 |
M S1 APARTMENT | 0.524 | -36.082 | 0.000 | 0.000 | 3.695 | 1.087 | 12.213 | 10.082 | 0.000 | 0.223 | 18.234 | 0.000 | -4.977 | 0.000 | -4.999 | -0.000 |
M S2 APARTMENT | 0.529 | -36.098 | 0.000 | 0.000 | 3.696 | 1.087 | 12.213 | 10.081 | 0.000 | 0.223 | 18.244 | 0.000 | -4.976 | 0.000 | -4.999 | -0.000 |
T SW APARTMENT | 9.213 | -15.816 | 0.000 | 0.000 | 3.790 | 1.087 | 12.213 | 15.065 | 0.000 | 0.471 | 0.000 | 0.000 | -7.657 | 0.000 | -9.795 | -8.571 |
T NW APARTMENT | 12.156 | -11.352 | 0.000 | 0.000 | 3.824 | 1.087 | 12.213 | 7.412 | 0.000 | 0.470 | 0.000 | 0.000 | -7.755 | 0.000 | -9.592 | -8.463 |
T SE APARTMENT | 9.009 | -15.880 | 0.000 | 0.000 | 3.796 | 1.087 | 12.213 | 15.108 | 0.000 | 0.471 | 0.000 | 0.000 | -7.470 | 0.000 | -9.801 | -8.532 |
T NE APARTMENT | 11.789 | -11.378 | 0.000 | 0.000 | 3.836 | 1.087 | 12.213 | 7.437 | 0.000 | 0.470 | 0.000 | 0.000 | -7.535 | 0.000 | -9.585 | -8.333 |
T N1 APARTMENT | 6.998 | -9.295 | 0.000 | 0.000 | 3.826 | 1.087 | 12.213 | 2.341 | 0.000 | 0.297 | 0.000 | 0.000 | -4.823 | 0.000 | -6.105 | -6.537 |
T N2 APARTMENT | 7.004 | -9.306 | 0.000 | 0.000 | 3.826 | 1.087 | 12.213 | 2.338 | 0.000 | 0.297 | 0.000 | 0.000 | -4.821 | 0.000 | -6.106 | -6.531 |
T S1 APARTMENT | 4.618 | -14.052 | 0.000 | 0.000 | 3.775 | 1.087 | 12.213 | 10.048 | 0.000 | 0.297 | 0.000 | 0.000 | -4.695 | 0.000 | -6.295 | -6.996 |
T S2 APARTMENT | 4.625 | -14.080 | 0.000 | 0.000 | 3.776 | 1.087 | 12.213 | 10.046 | 0.000 | 0.297 | 0.000 | 0.000 | -4.693 | 0.000 | -6.296 | -6.973 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.133 | 0.000 | 0.036 | 0.000 | 0.000 | -0.887 | 0.000 | -1.620 | -12.243 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.474 | 0.000 | 1.121 | 7.587 | 0.000 | -2.310 | 0.000 | -27.932 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.134 | 0.000 | 0.032 | 0.000 | 0.000 | -0.981 | 0.000 | -1.347 | -12.419 |
Total Facility | 121.955 | -404.699 | 0.000 | 0.000 | 87.929 | 95.189 | 296.854 | 213.189 | 0.000 | 8.111 | 112.670 | 0.000 | -154.192 | 0.000 | -178.096 | -198.913 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 31-JUL-18:00 | 0.00 | -2350.12 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2248.46 | 0.00 | 265.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -981.72 |
G NW APARTMENT | 31-JUL-18:00 | 0.00 | -2188.89 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2327.32 | 0.00 | 265.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1221.81 |
OFFICE | 13-AUG-06:01 | 0.00 | -7594.42 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 7530.62 | 0.00 | -348.99 | 0.00 | -297.66 | 0.00 |
G NE APARTMENT | 12-JUL-17:09 | 0.00 | -1505.41 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 727.80 | 0.00 | 244.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -284.58 |
G N1 APARTMENT | 12-JUL-19:30 | 0.00 | -1153.75 | 0.00 | 0.00 | 141.64 | 103.77 | 523.87 | 858.55 | 0.00 | 63.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -537.23 |
G N2 APARTMENT | 12-JUL-19:30 | 0.00 | -1142.13 | 0.00 | 0.00 | 141.59 | 103.77 | 523.87 | 858.72 | 0.00 | 63.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -548.96 |
G S1 APARTMENT | 26-SEP-14:30 | 0.00 | -1491.14 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2025.00 | 0.00 | 66.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1064.00 |
G S2 APARTMENT | 26-SEP-14:30 | 0.00 | -1500.93 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2024.80 | 0.00 | 66.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1054.00 |
M SW APARTMENT | 31-JUL-18:00 | 0.00 | -6195.37 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2236.55 | 0.00 | 380.84 | 2759.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 31-JUL-18:00 | 0.00 | -5724.34 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2314.92 | 0.00 | 380.84 | 2210.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 22-JUL-14:15 | 0.00 | -5273.34 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1785.25 | 0.00 | 353.27 | 2671.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 22-JUL-16:13 | 0.00 | -4272.64 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 802.83 | 0.00 | 317.49 | 2414.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 23-JUN-19:00 | 0.00 | -3331.10 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 785.05 | 0.00 | 165.64 | 1587.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 23-JUN-19:00 | 0.00 | -3306.02 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 785.20 | 0.00 | 165.64 | 1562.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 01-OCT-15:15 | 0.00 | -4441.87 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 1793.99 | 0.00 | 46.20 | 2036.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 01-OCT-15:15 | 0.00 | -4440.31 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 1793.98 | 0.00 | 46.20 | 2034.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 21-JUL-17:04 | 0.00 | -4129.89 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 2291.59 | 0.00 | 380.24 | 640.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 31-JUL-18:00 | 0.00 | -3918.42 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2277.36 | 0.00 | 502.29 | 320.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 22-JUL-14:15 | 0.00 | -3611.40 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1753.76 | 0.00 | 465.75 | 928.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 12-JUL-16:45 | 0.00 | -3014.75 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 751.09 | 0.00 | 461.59 | 1063.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 12-JUL-17:06 | 0.00 | -2417.73 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 431.88 | 0.00 | 278.70 | 889.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 12-JUL-17:06 | 0.00 | -2400.40 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 432.11 | 0.00 | 278.70 | 871.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 01-OCT-14:30 | 0.00 | -2959.43 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2121.98 | 0.00 | 27.01 | 346.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 01-OCT-14:30 | 0.00 | -2962.86 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 2121.91 | 0.00 | 27.01 | 350.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUL-16:04 | 0.00 | -69140.97 | 0.00 | 0.00 | 1949.41 | 3295.01 | 14142.04 | 26068.85 | 0.00 | 9624.37 | 14061.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 04-JAN-08:02 | 1503.51 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -742.82 | 0.00 | -750.33 | -492.28 |
G NW APARTMENT | 28-DEC-10:00 | 1577.65 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -539.70 | 0.00 | -953.09 | -539.62 |
OFFICE | 24-DEC-07:01 | 5142.63 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -360.07 | 0.00 | -343.69 | -5149.33 |
G NE APARTMENT | 21-APR-06:01 | 1785.73 | 0.00 | 0.00 | 0.00 | 163.01 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -122.25 | 0.00 | -89.96 | -2161.28 |
G N1 APARTMENT | 11-MAR-16:01 | 2003.54 | 0.00 | 0.00 | 0.00 | 99.95 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46.60 | 0.00 | -151.48 | -2558.89 |
G N2 APARTMENT | 27-OCT-06:01 | 1039.73 | 0.00 | 0.00 | 0.00 | 163.21 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -298.35 | 0.00 | -122.73 | -1206.63 |
G S1 APARTMENT | 06-DEC-07:01 | 1296.37 | 0.00 | 0.00 | 0.00 | 161.41 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -339.21 | 0.00 | 0.00 | -1543.34 |
G S2 APARTMENT | 27-JAN-18:01 | 1350.83 | 0.00 | 0.00 | 0.00 | 165.23 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -354.73 | 0.00 | -120.53 | -1716.99 |
M SW APARTMENT | 28-DEC-07:55 | 3008.80 | 0.00 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -751.04 | 0.00 | -1189.81 | -1653.93 |
M NW APARTMENT | 28-DEC-10:00 | 3450.54 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -559.41 | 0.00 | -1370.71 | -1975.18 |
M SE APARTMENT | 28-DEC-08:00 | 3018.63 | 0.00 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -761.19 | 0.00 | -1189.81 | -1653.61 |
M NE APARTMENT | 04-JAN-05:00 | 3216.04 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -749.62 | 0.00 | -1132.57 | -1766.66 |
M N1 APARTMENT | 18-NOV-07:01 | 2979.23 | 0.00 | 0.00 | 0.00 | 161.47 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -393.40 | 0.00 | -156.05 | -3016.01 |
M N2 APARTMENT | 18-NOV-07:01 | 2977.84 | 0.00 | 0.00 | 0.00 | 161.47 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -393.37 | 0.00 | -156.04 | -3014.66 |
M S1 APARTMENT | 11-JAN-09:00 | 1437.16 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 39.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -161.64 | -1796.95 |
M S2 APARTMENT | 13-JAN-01:25 | 1874.26 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -565.99 | 0.00 | -95.36 | -1650.39 |
T SW APARTMENT | 04-JAN-05:00 | 2843.51 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.93 | 0.00 | -1500.17 | -1040.21 |
T NW APARTMENT | 28-DEC-10:00 | 2908.62 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 394.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -541.42 | 0.00 | -1815.78 | -1006.19 |
T SE APARTMENT | 04-JAN-05:00 | 2851.67 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.87 | 0.00 | -1500.17 | -1037.42 |
T NE APARTMENT | 04-JAN-05:00 | 2901.41 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -727.34 | 0.00 | -1500.17 | -1106.70 |
T N1 APARTMENT | 04-JAN-05:00 | 1913.26 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.48 | 0.00 | -904.90 | -1005.69 |
T N2 APARTMENT | 04-JAN-05:00 | 1913.45 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.48 | 0.00 | -904.90 | -1005.88 |
T S1 APARTMENT | 04-JAN-05:00 | 1858.47 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -455.54 | 0.00 | -904.90 | -930.83 |
T S2 APARTMENT | 04-JAN-05:00 | 1858.49 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -455.54 | 0.00 | -904.90 | -930.86 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-JAN-07:50 | 45621.53 | 0.00 | 0.00 | 0.00 | 3708.06 | 2772.92 | 9503.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14713.52 | 0.00 | -33431.32 | -13461.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Sec1.1A-General InformationData | |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 46.25 |
Number of hours cooling loads not met | 0.75 |
Number of hours not met | 47.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 273.85 | 80039.05 | 0.00 | 0.00 |
Space Cooling | 105.80 | 23997.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 261.72 | 8299.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 407.59 | 23607.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1451.29 | 273.85 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1451.29 |
Natural Gas | 0.00 | 273.85 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1725.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 33.75 |
Fans-Interior | 83.49 |
Service Water Heating | 130.03 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.78 |
Subtotal | 462.99 |
Natural Gas [MJ/m2] | |
Space Heating | 87.36 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 87.36 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.87 |
Space Heating | 15.87 |
Space Cooling | 6.13 |
Fans-Interior | 15.17 |
Service Water Heating | 23.63 |
Receptacle Equipment | 30.01 |
Miscellaneous | 2.32 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.205081 |
G NW APARTMENT DIRECT AIR | 0.188899 |
OFFICE DIRECT AIR | 0.494879 |
G NE APARTMENT DIRECT AIR | 0.138983 |
G N1 APARTMENT DIRECT AIR | 0.103655 |
G N2 APARTMENT DIRECT AIR | 0.102398 |
G S1 APARTMENT DIRECT AIR | 0.129977 |
G S2 APARTMENT DIRECT AIR | 0.133006 |
M SW APARTMENT DIRECT AIR | 0.552084 |
M NW APARTMENT DIRECT AIR | 0.504346 |
M SE APARTMENT DIRECT AIR | 0.500273 |
M NE APARTMENT DIRECT AIR | 0.402771 |
M N1 APARTMENT DIRECT AIR | 0.292800 |
M N2 APARTMENT DIRECT AIR | 0.290741 |
M S1 APARTMENT DIRECT AIR | 0.367342 |
M S2 APARTMENT DIRECT AIR | 0.368684 |
T SW APARTMENT DIRECT AIR | 0.378988 |
T NW APARTMENT DIRECT AIR | 0.343932 |
T SE APARTMENT DIRECT AIR | 0.354654 |
T NE APARTMENT DIRECT AIR | 0.284291 |
T N1 APARTMENT DIRECT AIR | 0.219446 |
T N2 APARTMENT DIRECT AIR | 0.219504 |
T S1 APARTMENT DIRECT AIR | 0.285876 |
T S2 APARTMENT DIRECT AIR | 0.286691 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.205081 |
SPLIT GNW MAIN BRANCH | 0.188899 |
SPLIT OFFICE MAIN BRANCH | 0.494879 |
SPLIT GNE MAIN BRANCH | 0.138983 |
SPLIT GN1 MAIN BRANCH | 0.103655 |
SPLIT GN2 MAIN BRANCH | 0.102398 |
SPLIT GS1 MAIN BRANCH | 0.129977 |
SPLIT GS2 MAIN BRANCH | 0.133006 |
SPLIT MSW MAIN BRANCH | 0.552084 |
SPLIT MNW MAIN BRANCH | 0.504346 |
SPLIT MSE MAIN BRANCH | 0.500273 |
SPLIT MNE MAIN BRANCH | 0.402771 |
SPLIT MN1 MAIN BRANCH | 0.292800 |
SPLIT MN2 MAIN BRANCH | 0.290741 |
SPLIT MS1 MAIN BRANCH | 0.367342 |
SPLIT MS2 MAIN BRANCH | 0.368684 |
SPLIT TSW MAIN BRANCH | 0.378988 |
SPLIT TNW MAIN BRANCH | 0.343932 |
SPLIT TSE MAIN BRANCH | 0.354654 |
SPLIT TNE MAIN BRANCH | 0.284291 |
SPLIT TN1 MAIN BRANCH | 0.219446 |
SPLIT TN2 MAIN BRANCH | 0.219504 |
SPLIT TS1 MAIN BRANCH | 0.285876 |
SPLIT TS2 MAIN BRANCH | 0.286691 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.205081 |
SPLIT GNW | 0.188899 |
SPLIT OFFICE | 0.494879 |
SPLIT GNE | 0.138983 |
SPLIT GN1 | 0.103655 |
SPLIT GN2 | 0.102398 |
SPLIT GS1 | 0.129977 |
SPLIT GS2 | 0.133006 |
SPLIT MSW | 0.552084 |
SPLIT MNW | 0.504346 |
SPLIT MSE | 0.500273 |
SPLIT MNE | 0.402771 |
SPLIT MN1 | 0.292800 |
SPLIT MN2 | 0.290741 |
SPLIT MS1 | 0.367342 |
SPLIT MS2 | 0.368684 |
SPLIT TSW | 0.378988 |
SPLIT TNW | 0.343932 |
SPLIT TSE | 0.354654 |
SPLIT TNE | 0.284291 |
SPLIT TN1 | 0.219446 |
SPLIT TN2 | 0.219504 |
SPLIT TS1 | 0.285876 |
SPLIT TS2 | 0.286691 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.205081 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.188899 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.494879 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.138983 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.103655 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.102398 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.129977 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.133006 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.552084 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.504346 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.500273 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.402771 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.292800 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.290741 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.367342 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.368684 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.378988 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.343932 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.354654 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.284291 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.219446 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.219504 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.285876 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.286691 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.205081 | 3394.82 | 0.798655 |
SPLIT GNW COOLING COIL | 0.188899 | 3126.95 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.494879 | 8192.01 | 0.798655 |
SPLIT GNE COOLING COIL | 0.138983 | 2300.66 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.103655 | 1715.86 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.102398 | 1695.05 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.129977 | 2212.37 | 0.788555 |
SPLIT GS2 COOLING COIL | 0.133006 | 2259.55 | 0.789247 |
SPLIT MSW COOLING COIL | 0.552084 | 9138.95 | 0.798655 |
SPLIT MNW COOLING COIL | 0.504346 | 8348.72 | 0.798655 |
SPLIT MSE COOLING COIL | 0.500273 | 8281.29 | 0.798655 |
SPLIT MNE COOLING COIL | 0.402771 | 6667.30 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.292800 | 4846.87 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.290741 | 4812.79 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.367342 | 6080.81 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.368684 | 6103.03 | 0.798655 |
SPLIT TSW COOLING COIL | 0.378988 | 6273.59 | 0.798655 |
SPLIT TNW COOLING COIL | 0.343932 | 5693.30 | 0.798655 |
SPLIT TSE COOLING COIL | 0.354654 | 5870.78 | 0.798655 |
SPLIT TNE COOLING COIL | 0.284291 | 4706.02 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.219446 | 3632.62 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.219504 | 3633.57 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.285876 | 4732.26 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.286691 | 4745.75 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.205081 | 0.205081 | 0.205081 | 0.205081 | 3090.00 | 3394.82 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.188899 | 0.188899 | 0.188899 | 0.188899 | 3042.14 | 3126.95 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.494879 | 0.494879 | 0.494879 | 0.494879 | 5450.83 | 8192.01 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.138983 | 0.138983 | 0.138983 | 0.138983 | 3049.53 | 2300.66 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.103655 | 0.103655 | 0.103655 | 0.103655 | 2320.92 | 1715.86 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.102398 | 0.102398 | 0.102398 | 0.102398 | 2321.09 | 1695.05 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.129977 | 0.129977 | 0.129977 | 0.129977 | 2331.74 | 2212.37 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.133006 | 0.133006 | 0.133006 | 0.133006 | 2452.70 | 2259.55 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.552084 | 0.552084 | 0.552084 | 0.552084 | 5913.15 | 9138.95 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.504346 | 0.504346 | 0.504346 | 0.504346 | 5887.20 | 8348.72 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.500273 | 0.500273 | 0.500273 | 0.500273 | 5932.81 | 8281.29 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.402771 | 0.402771 | 0.402771 | 0.402771 | 5906.88 | 6667.30 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.292800 | 0.292800 | 0.292800 | 0.292800 | 4095.72 | 4846.87 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.290741 | 0.290741 | 0.290741 | 0.290741 | 4096.22 | 4812.79 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.367342 | 0.367342 | 0.367342 | 0.367342 | 4124.14 | 6080.81 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.368684 | 0.368684 | 0.368684 | 0.368684 | 4124.64 | 6103.03 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.378988 | 0.378988 | 0.378988 | 0.378988 | 4458.36 | 6273.59 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.343932 | 0.343932 | 0.343932 | 0.343932 | 4446.32 | 5693.30 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.354654 | 0.354654 | 0.354654 | 0.354654 | 4468.76 | 5870.78 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.284291 | 0.284291 | 0.284291 | 0.284291 | 4456.75 | 4706.02 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.219446 | 0.219446 | 0.219446 | 0.219446 | 3492.72 | 3632.62 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.219504 | 0.219504 | 0.219504 | 0.219504 | 3493.00 | 3633.57 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.285876 | 0.285876 | 0.285876 | 0.285876 | 3503.36 | 4732.26 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.286691 | 0.286691 | 0.286691 | 0.286691 | 3503.64 | 4745.75 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.205081 |
SPLIT GNW SUPPLY FAN | 0.188899 |
SPLIT OFFICE SUPPLY FAN | 0.494879 |
SPLIT GNE SUPPLY FAN | 0.138983 |
SPLIT GN1 SUPPLY FAN | 0.103655 |
SPLIT GN2 SUPPLY FAN | 0.102398 |
SPLIT GS1 SUPPLY FAN | 0.129977 |
SPLIT GS2 SUPPLY FAN | 0.133006 |
SPLIT MSW SUPPLY FAN | 0.552084 |
SPLIT MNW SUPPLY FAN | 0.504346 |
SPLIT MSE SUPPLY FAN | 0.500273 |
SPLIT MNE SUPPLY FAN | 0.402771 |
SPLIT MN1 SUPPLY FAN | 0.292800 |
SPLIT MN2 SUPPLY FAN | 0.290741 |
SPLIT MS1 SUPPLY FAN | 0.367342 |
SPLIT MS2 SUPPLY FAN | 0.368684 |
SPLIT TSW SUPPLY FAN | 0.378988 |
SPLIT TNW SUPPLY FAN | 0.343932 |
SPLIT TSE SUPPLY FAN | 0.354654 |
SPLIT TNE SUPPLY FAN | 0.284291 |
SPLIT TN1 SUPPLY FAN | 0.219446 |
SPLIT TN2 SUPPLY FAN | 0.219504 |
SPLIT TS1 SUPPLY FAN | 0.285876 |
SPLIT TS2 SUPPLY FAN | 0.286691 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 3090.00 |
SPLIT GNW HEATING COIL | 3042.14 |
SPLIT OFFICE HEATING COIL | 5450.83 |
SPLIT GNE HEATING COIL | 3049.53 |
SPLIT GN1 HEATING COIL | 2320.92 |
SPLIT GN2 HEATING COIL | 2321.09 |
SPLIT GS1 HEATING COIL | 2331.74 |
SPLIT GS2 HEATING COIL | 2452.70 |
SPLIT MSW HEATING COIL | 5913.15 |
SPLIT MNW HEATING COIL | 5887.20 |
SPLIT MSE HEATING COIL | 5932.81 |
SPLIT MNE HEATING COIL | 5906.88 |
SPLIT MN1 HEATING COIL | 4095.72 |
SPLIT MN2 HEATING COIL | 4096.22 |
SPLIT MS1 HEATING COIL | 4124.14 |
SPLIT MS2 HEATING COIL | 4124.64 |
SPLIT TSW HEATING COIL | 4458.36 |
SPLIT TNW HEATING COIL | 4446.32 |
SPLIT TSE HEATING COIL | 4468.76 |
SPLIT TNE HEATING COIL | 4456.75 |
SPLIT TN1 HEATING COIL | 3492.72 |
SPLIT TN2 HEATING COIL | 3493.00 |
SPLIT TS1 HEATING COIL | 3503.36 |
SPLIT TS2 HEATING COIL | 3503.64 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -1.7 |
February | 21.84 | 2.70 |
March | 22.03 | 6.07 |
April | 22.72 | 11.58 |
May | 23.09 | 14.61 |
June | 24.18 | 19.78 |
July | 24.39 | 24.54 |
August | 24.32 | 21.22 |
September | 24.21 | 17.37 |
October | 22.93 | 11.70 |
November | 21.93 | 4.05 |
December | 21.77 | 1.86 |
Annual Sum or Average | 22.93 | 11.20 |
Minimum of Months | 21.71 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.71 | 2.70 |
March | 21.78 | 6.07 |
April | 22.39 | 11.58 |
May | 22.88 | 14.61 |
June | 24.15 | 19.78 |
July | 24.39 | 24.54 |
August | 24.28 | 21.22 |
September | 24.07 | 17.37 |
October | 22.38 | 11.70 |
November | 21.74 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.77 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.30 | -1.7 |
February | 21.50 | 2.70 |
March | 22.38 | 6.07 |
April | 23.63 | 11.58 |
May | 24.24 | 14.61 |
June | 26.03 | 19.78 |
July | 26.95 | 24.54 |
August | 26.33 | 21.22 |
September | 26.07 | 17.37 |
October | 24.03 | 11.70 |
November | 21.86 | 4.05 |
December | 21.06 | 1.86 |
Annual Sum or Average | 23.71 | 11.20 |
Minimum of Months | 20.30 | -1.7 |
Maximum of Months | 26.95 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.70 | 2.70 |
March | 21.75 | 6.07 |
April | 22.33 | 11.58 |
May | 22.82 | 14.61 |
June | 24.13 | 19.78 |
July | 24.38 | 24.54 |
August | 24.26 | 21.22 |
September | 24.02 | 17.37 |
October | 22.31 | 11.70 |
November | 21.73 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.74 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.38 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.70 | 2.70 |
March | 21.73 | 6.07 |
April | 22.18 | 11.58 |
May | 22.60 | 14.61 |
June | 24.10 | 19.78 |
July | 24.38 | 24.54 |
August | 24.25 | 21.22 |
September | 24.03 | 17.37 |
October | 22.25 | 11.70 |
November | 21.73 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.70 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.38 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.70 | 2.70 |
March | 21.73 | 6.07 |
April | 22.18 | 11.58 |
May | 22.60 | 14.61 |
June | 24.10 | 19.78 |
July | 24.38 | 24.54 |
August | 24.25 | 21.22 |
September | 24.03 | 17.37 |
October | 22.25 | 11.70 |
November | 21.73 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.70 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.38 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -1.7 |
February | 21.84 | 2.70 |
March | 22.00 | 6.07 |
April | 22.63 | 11.58 |
May | 22.92 | 14.61 |
June | 24.17 | 19.78 |
July | 24.39 | 24.54 |
August | 24.33 | 21.22 |
September | 24.24 | 17.37 |
October | 23.00 | 11.70 |
November | 21.95 | 4.05 |
December | 21.78 | 1.86 |
Annual Sum or Average | 22.92 | 11.20 |
Minimum of Months | 21.72 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -1.7 |
February | 21.84 | 2.70 |
March | 22.01 | 6.07 |
April | 22.66 | 11.58 |
May | 22.96 | 14.61 |
June | 24.20 | 19.78 |
July | 24.39 | 24.54 |
August | 24.34 | 21.22 |
September | 24.26 | 17.37 |
October | 23.04 | 11.70 |
November | 21.96 | 4.05 |
December | 21.78 | 1.86 |
Annual Sum or Average | 22.94 | 11.20 |
Minimum of Months | 21.72 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -1.7 |
February | 22.27 | 2.70 |
March | 22.86 | 6.07 |
April | 24.07 | 11.58 |
May | 24.32 | 14.61 |
June | 24.37 | 19.78 |
July | 24.40 | 24.54 |
August | 24.40 | 21.22 |
September | 24.38 | 17.37 |
October | 24.17 | 11.70 |
November | 22.72 | 4.05 |
December | 22.03 | 1.86 |
Annual Sum or Average | 23.49 | 11.20 |
Minimum of Months | 21.80 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.77 | 2.70 |
March | 22.08 | 6.07 |
April | 23.74 | 11.58 |
May | 24.28 | 14.61 |
June | 24.36 | 19.78 |
July | 24.40 | 24.54 |
August | 24.39 | 21.22 |
September | 24.34 | 17.37 |
October | 23.68 | 11.70 |
November | 22.26 | 4.05 |
December | 21.71 | 1.86 |
Annual Sum or Average | 23.23 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -1.7 |
February | 22.23 | 2.70 |
March | 22.86 | 6.07 |
April | 24.09 | 11.58 |
May | 24.31 | 14.61 |
June | 24.37 | 19.78 |
July | 24.40 | 24.54 |
August | 24.40 | 21.22 |
September | 24.37 | 17.37 |
October | 24.17 | 11.70 |
November | 22.69 | 4.05 |
December | 21.99 | 1.86 |
Annual Sum or Average | 23.48 | 11.20 |
Minimum of Months | 21.78 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.73 | 2.70 |
March | 22.03 | 6.07 |
April | 23.73 | 11.58 |
May | 24.25 | 14.61 |
June | 24.36 | 19.78 |
July | 24.40 | 24.54 |
August | 24.39 | 21.22 |
September | 24.32 | 17.37 |
October | 23.64 | 11.70 |
November | 22.18 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 23.21 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.76 | 2.70 |
March | 22.06 | 6.07 |
April | 23.79 | 11.58 |
May | 24.32 | 14.61 |
June | 24.37 | 19.78 |
July | 24.40 | 24.54 |
August | 24.39 | 21.22 |
September | 24.35 | 17.37 |
October | 23.82 | 11.70 |
November | 22.38 | 4.05 |
December | 21.71 | 1.86 |
Annual Sum or Average | 23.26 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.76 | 2.70 |
March | 22.06 | 6.07 |
April | 23.79 | 11.58 |
May | 24.31 | 14.61 |
June | 24.37 | 19.78 |
July | 24.40 | 24.54 |
August | 24.39 | 21.22 |
September | 24.35 | 17.37 |
October | 23.82 | 11.70 |
November | 22.38 | 4.05 |
December | 21.71 | 1.86 |
Annual Sum or Average | 23.26 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | -1.7 |
February | 22.53 | 2.70 |
March | 23.19 | 6.07 |
April | 24.21 | 11.58 |
May | 24.36 | 14.61 |
June | 24.38 | 19.78 |
July | 24.40 | 24.54 |
August | 24.40 | 21.22 |
September | 24.40 | 17.37 |
October | 24.31 | 11.70 |
November | 22.98 | 4.05 |
December | 22.27 | 1.86 |
Annual Sum or Average | 23.61 | 11.20 |
Minimum of Months | 21.87 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | -1.7 |
February | 22.53 | 2.70 |
March | 23.19 | 6.07 |
April | 24.21 | 11.58 |
May | 24.36 | 14.61 |
June | 24.38 | 19.78 |
July | 24.40 | 24.54 |
August | 24.40 | 21.22 |
September | 24.40 | 17.37 |
October | 24.31 | 11.70 |
November | 22.98 | 4.05 |
December | 22.26 | 1.86 |
Annual Sum or Average | 23.61 | 11.20 |
Minimum of Months | 21.87 | -1.7 |
Maximum of Months | 24.40 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | -1.7 |
February | 22.11 | 2.70 |
March | 22.46 | 6.07 |
April | 23.43 | 11.58 |
May | 23.91 | 14.61 |
June | 24.22 | 19.78 |
July | 24.39 | 24.54 |
August | 24.29 | 21.22 |
September | 24.14 | 17.37 |
October | 23.37 | 11.70 |
November | 22.21 | 4.05 |
December | 21.91 | 1.86 |
Annual Sum or Average | 23.19 | 11.20 |
Minimum of Months | 21.79 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.77 | 2.70 |
March | 22.06 | 6.07 |
April | 23.18 | 11.58 |
May | 23.83 | 14.61 |
June | 24.20 | 19.78 |
July | 24.39 | 24.54 |
August | 24.25 | 21.22 |
September | 23.98 | 17.37 |
October | 22.87 | 11.70 |
November | 21.87 | 4.05 |
December | 21.71 | 1.86 |
Annual Sum or Average | 22.99 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | -1.7 |
February | 22.09 | 2.70 |
March | 22.47 | 6.07 |
April | 23.46 | 11.58 |
May | 23.92 | 14.61 |
June | 24.24 | 19.78 |
July | 24.39 | 24.54 |
August | 24.29 | 21.22 |
September | 24.12 | 17.37 |
October | 23.40 | 11.70 |
November | 22.20 | 4.05 |
December | 21.89 | 1.86 |
Annual Sum or Average | 23.19 | 11.20 |
Minimum of Months | 21.77 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.73 | 2.70 |
March | 22.01 | 6.07 |
April | 23.17 | 11.58 |
May | 23.79 | 14.61 |
June | 24.19 | 19.78 |
July | 24.38 | 24.54 |
August | 24.23 | 21.22 |
September | 23.94 | 17.37 |
October | 22.83 | 11.70 |
November | 21.85 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.97 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.38 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.73 | 2.70 |
March | 21.99 | 6.07 |
April | 23.19 | 11.58 |
May | 23.85 | 14.61 |
June | 24.22 | 19.78 |
July | 24.39 | 24.54 |
August | 24.25 | 21.22 |
September | 23.98 | 17.37 |
October | 22.83 | 11.70 |
November | 21.85 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.98 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -1.7 |
February | 21.73 | 2.70 |
March | 21.99 | 6.07 |
April | 23.19 | 11.58 |
May | 23.84 | 14.61 |
June | 24.22 | 19.78 |
July | 24.39 | 24.54 |
August | 24.25 | 21.22 |
September | 23.98 | 17.37 |
October | 22.83 | 11.70 |
November | 21.85 | 4.05 |
December | 21.70 | 1.86 |
Annual Sum or Average | 22.98 | 11.20 |
Minimum of Months | 21.70 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -1.7 |
February | 22.18 | 2.70 |
March | 22.55 | 6.07 |
April | 23.57 | 11.58 |
May | 24.00 | 14.61 |
June | 24.26 | 19.78 |
July | 24.39 | 24.54 |
August | 24.32 | 21.22 |
September | 24.20 | 17.37 |
October | 23.54 | 11.70 |
November | 22.31 | 4.05 |
December | 21.97 | 1.86 |
Annual Sum or Average | 23.27 | 11.20 |
Minimum of Months | 21.82 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -1.7 |
February | 22.18 | 2.70 |
March | 22.55 | 6.07 |
April | 23.57 | 11.58 |
May | 24.00 | 14.61 |
June | 24.26 | 19.78 |
July | 24.39 | 24.54 |
August | 24.32 | 21.22 |
September | 24.20 | 17.37 |
October | 23.55 | 11.70 |
November | 22.31 | 4.05 |
December | 21.97 | 1.86 |
Annual Sum or Average | 23.27 | 11.20 |
Minimum of Months | 21.82 | -1.7 |
Maximum of Months | 24.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | -1.7 |
February | 21.72 | 2.70 |
March | 22.52 | 6.07 |
April | 24.46 | 11.58 |
May | 25.31 | 14.61 |
June | 26.24 | 19.78 |
July | 26.88 | 24.54 |
August | 26.38 | 21.22 |
September | 25.66 | 17.37 |
October | 24.03 | 11.70 |
November | 21.92 | 4.05 |
December | 21.31 | 1.86 |
Annual Sum or Average | 23.96 | 11.20 |
Minimum of Months | 20.93 | -1.7 |
Maximum of Months | 26.88 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.40 | -1.7 |
February | 19.47 | 2.70 |
March | 20.26 | 6.07 |
April | 21.87 | 11.58 |
May | 22.67 | 14.61 |
June | 25.21 | 19.78 |
July | 26.51 | 24.54 |
August | 25.88 | 21.22 |
September | 24.90 | 17.37 |
October | 22.19 | 11.70 |
November | 19.83 | 4.05 |
December | 19.15 | 1.86 |
Annual Sum or Average | 22.21 | 11.20 |
Minimum of Months | 18.40 | -1.7 |
Maximum of Months | 26.51 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:26
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.80 | -1.7 |
February | 23.47 | 2.70 |
March | 24.10 | 6.07 |
April | 25.87 | 11.58 |
May | 26.37 | 14.61 |
June | 26.72 | 19.78 |
July | 26.98 | 24.54 |
August | 26.80 | 21.22 |
September | 26.58 | 17.37 |
October | 25.88 | 11.70 |
November | 24.02 | 4.05 |
December | 23.13 | 1.86 |
Annual Sum or Average | 25.23 | 11.20 |
Minimum of Months | 22.80 | -1.7 |
Maximum of Months | 26.98 | 24.54 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:26
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.118969E+12 | 74708.810 | 16-JAN-18:45 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32245.746 | 0.000 | 0.000 | 0.000 |
February | 0.107828E+12 | 73725.253 | 16-FEB-18:45 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31262.190 | 0.000 | 0.000 | 0.000 |
March | 0.118969E+12 | 71412.340 | 16-MAR-17:00 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 1483.961 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30018.316 | 0.000 | 0.000 | 0.000 |
April | 0.117479E+12 | 80553.276 | 12-APR-17:15 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 12691.678 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27951.534 | 0.000 | 0.000 | 0.000 |
May | 0.122509E+12 | 80227.305 | 04-MAY-17:00 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 16673.725 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23643.518 | 0.000 | 0.000 | 0.000 |
June | 0.126286E+12 | 84500.315 | 23-JUN-17:00 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 21664.896 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22925.356 | 0.000 | 0.000 | 0.000 |
July | 0.138542E+12 | 87515.237 | 29-JUL-17:00 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 23997.968 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23607.206 | 0.000 | 0.000 | 0.000 |
August | 0.131803E+12 | 82518.614 | 04-AUG-17:45 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 22263.654 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20344.897 | 0.000 | 0.000 | 0.000 |
September | 0.120845E+12 | 76555.557 | 08-SEP-17:15 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 17895.363 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18750.131 | 0.000 | 0.000 | 0.000 |
October | 0.118212E+12 | 75779.506 | 01-OCT-17:30 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 15893.010 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19976.433 | 0.000 | 0.000 | 0.000 |
November | 0.112231E+12 | 70675.017 | 04-NOV-17:45 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 4014.965 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24196.989 | 0.000 | 0.000 | 0.000 |
December | 0.117615E+12 | 71016.870 | 27-DEC-18:45 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28553.807 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.145129E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.107828E+12 | 70675.017 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18750.131 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.138542E+12 | 87515.237 | 4979.953 | 26630.920 | 8299.189 | 0.000 | 23997.968 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32245.746 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:26
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.884584E+11 | 80039.050 | 04-JAN-07:00 | 80039.050 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 80039.050 |
February | 0.438192E+11 | 51074.671 | 27-FEB-03:00 | 51074.671 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 51074.671 |
March | 0.258370E+11 | 39535.753 | 11-MAR-05:00 | 39535.753 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 39535.753 |
April | 0.570249E+10 | 29373.712 | 08-APR-04:00 | 29373.712 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29373.712 |
May | 0.106153E+10 | 9585.550 | 13-MAY-04:00 | 9585.550 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9585.550 |
June | 0.989059E+08 | 6494.753 | 13-JUN-03:00 | 6494.753 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6494.753 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 582513.883 | 165.588 | 18-AUG-05:45 | 165.588 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 165.588 |
September | 0.953695E+08 | 3842.773 | 20-SEP-06:30 | 3842.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3842.773 |
October | 0.417692E+10 | 20156.089 | 26-OCT-07:15 | 20156.089 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20156.089 |
November | 0.402540E+11 | 59313.837 | 24-NOV-04:00 | 59313.837 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 59313.837 |
December | 0.643444E+11 | 77137.283 | 28-DEC-07:00 | 77137.283 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 77137.283 |
Annual Sum or Average | 0.273849E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.884584E+11 | 80039.050 | 80039.050 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 80039.050 |