Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2015-09-09 18:47:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2539.12 | 810.03 | 899.13 |
Net Site Energy | 2539.12 | 810.03 | 899.13 |
Total Source Energy | 5734.76 | 1829.50 | 2030.74 |
Net Source Energy | 5734.76 | 1829.50 | 2030.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1107.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 502.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1431.76 | 1107.35 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1107.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 39.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 213.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 502.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 267.65 | 392.13 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 507.00 | 392.13 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 241.13 | 353.27 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.76 | 353.27 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1431.76 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1431.76 | 100.00 |
Total On-Site and Utility Electric Sources | 1431.76 | 100.00 |
Total Electricity End Uses | 1431.76 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 48.50 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4621.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-AUG-17:00 | 29-JAN-00:15 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 158809.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12449.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6762.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31245.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 82068.52 | 158809.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 158809.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12449.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6762.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 31245.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1200.37 | 0.00 | 0.00 | 0.00 |
Cooling | 126.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 675.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1592.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4534.39 | 1200.37 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 425.06 | 0.00 | 0.00 | 0.00 |
Cooling | 44.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 239.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 563.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1605.68 | 425.06 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 425.06 | 0.00 | 0.00 | 0.00 |
Cooling | 44.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 239.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 563.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1605.68 | 425.06 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.219 | 0.228 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.219 | 0.228 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.493 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.493 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.493 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.493 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.493 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.42_SHGC_0.45 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.493 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.42_SHGC_0.45 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.493 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.493 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.42_SHGC_0.45 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.493 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.42_SHGC_0.45 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.493 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.493 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.493 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.493 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.06 | 83.06 | 39.80 | |
Exterior Lighting Total | 2553.00 | 39.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2655.15 | 2120.55 | 534.60 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1977.04 | 1578.97 | 398.07 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7302.21 | 5831.95 | 1470.26 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1453.34 | 1160.71 | 292.62 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1100.63 | 879.03 | 221.61 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1082.61 | 864.64 | 217.98 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2015.54 | 1609.72 | 405.82 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2068.56 | 1652.07 | 416.49 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8000.55 | 6389.68 | 1610.87 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6173.73 | 4930.68 | 1243.05 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7715.21 | 6161.79 | 1553.42 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5089.93 | 4065.10 | 1024.83 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3864.40 | 3086.32 | 778.08 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3830.60 | 3059.33 | 771.27 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6311.71 | 5040.88 | 1270.83 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6332.89 | 5057.80 | 1275.09 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5010.47 | 4001.64 | 1008.83 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3789.17 | 3026.24 | 762.93 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4813.97 | 3844.71 | 969.27 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2983.86 | 2383.07 | 600.78 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2281.37 | 1822.03 | 459.34 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2254.63 | 1800.67 | 453.96 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4153.09 | 3316.88 | 836.20 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4169.63 | 3330.10 | 839.53 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2529.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1883.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6956.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1384.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1048.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1031.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1920.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1970.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7621.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5881.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7349.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4849.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3681.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3649.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6012.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6033.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4773.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3609.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4586.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2842.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2173.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2147.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3956.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3972.2 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 4743.27 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 4687.30 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 7957.76 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 4693.33 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 3903.99 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 3904.12 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 3892.09 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 4034.18 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 7769.23 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 7797.98 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 7785.25 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 7814.02 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 5966.13 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 5966.50 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 5941.02 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 5941.38 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 5650.78 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 5668.71 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 5659.62 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 5677.56 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 4753.68 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 4753.89 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 4734.38 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 4734.59 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 186.20 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 138.64 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 512.08 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 101.92 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.07 | 77.18 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.07 | 75.92 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.34 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 145.06 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 561.05 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 432.94 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 541.04 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 356.94 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 271.00 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 268.63 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 442.62 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 444.10 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 351.37 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 265.72 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 337.59 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.25 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 159.98 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 158.11 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 291.24 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 292.40 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1680.38 | 2016.46 | 0.134 | 0.160 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
G NW APARTMENT | 1251.21 | 1501.46 | 0.100 | 0.119 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
OFFICE | 4527.29 | 5432.75 | 0.368 | 0.441 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79 | 0.00698 |
G NE APARTMENT | 919.77 | 1103.73 | 0.073 | 0.088 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
G N1 APARTMENT | 696.55 | 835.86 | 0.055 | 0.066 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38 | 0.00698 |
G N2 APARTMENT | 685.14 | 822.17 | 0.055 | 0.065 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38 | 0.00698 |
G S1 APARTMENT | 1275.58 | 1530.70 | 0.101 | 0.122 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
G S2 APARTMENT | 1309.14 | 1570.97 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
M SW APARTMENT | 5063.40 | 6076.09 | 0.403 | 0.483 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
M NW APARTMENT | 3907.17 | 4688.61 | 0.311 | 0.373 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:45:00 | 22.58 | 0.00698 |
M SE APARTMENT | 4882.81 | 5859.38 | 0.388 | 0.466 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
M NE APARTMENT | 3221.31 | 3865.57 | 0.256 | 0.307 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
M N1 APARTMENT | 2445.63 | 2934.76 | 0.195 | 0.233 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38 | 0.00698 |
M N2 APARTMENT | 2424.24 | 2909.09 | 0.193 | 0.231 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38 | 0.00698 |
M S1 APARTMENT | 3994.53 | 4793.44 | 0.318 | 0.381 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
M S2 APARTMENT | 4007.94 | 4809.53 | 0.319 | 0.383 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
T SW APARTMENT | 3171.06 | 3805.27 | 0.252 | 0.303 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 26.58 | 0.00698 |
T NW APARTMENT | 2398.09 | 2877.71 | 0.191 | 0.229 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 24.57 | 0.00698 |
T SE APARTMENT | 3046.70 | 3656.04 | 0.242 | 0.291 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
T NE APARTMENT | 1888.44 | 2266.13 | 0.150 | 0.180 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 25.31 | 0.00698 |
T N1 APARTMENT | 1443.83 | 1732.59 | 0.115 | 0.138 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
T N2 APARTMENT | 1426.90 | 1712.28 | 0.114 | 0.136 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
T S1 APARTMENT | 2628.40 | 3154.09 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
T S2 APARTMENT | 2638.87 | 3166.65 | 0.210 | 0.252 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2287.85 | 2745.42 | 0.067 | 0.080 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G NW APARTMENT | 2301.10 | 2761.31 | 0.067 | 0.081 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
OFFICE | 4336.83 | 5204.19 | 0.123 | 0.147 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G NE APARTMENT | 2306.20 | 2767.43 | 0.067 | 0.081 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N1 APARTMENT | 1638.69 | 1966.42 | 0.048 | 0.057 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G N2 APARTMENT | 1638.80 | 1966.55 | 0.048 | 0.057 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S1 APARTMENT | 1628.63 | 1954.35 | 0.048 | 0.057 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
G S2 APARTMENT | 1748.78 | 2098.54 | 0.051 | 0.061 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
M SW APARTMENT | 3244.61 | 3893.54 | 0.095 | 0.114 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M NW APARTMENT | 3268.92 | 3922.71 | 0.096 | 0.115 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M SE APARTMENT | 3258.15 | 3909.78 | 0.095 | 0.114 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M NE APARTMENT | 3282.48 | 3938.98 | 0.096 | 0.115 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M N1 APARTMENT | 1719.81 | 2063.77 | 0.050 | 0.060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M N2 APARTMENT | 1720.11 | 2064.14 | 0.050 | 0.060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M S1 APARTMENT | 1698.57 | 2038.28 | 0.050 | 0.060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
M S2 APARTMENT | 1698.87 | 2038.65 | 0.050 | 0.060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T SW APARTMENT | 3115.87 | 3739.05 | 0.091 | 0.109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T NW APARTMENT | 3131.03 | 3757.24 | 0.092 | 0.110 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T SE APARTMENT | 3123.35 | 3748.01 | 0.091 | 0.110 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T NE APARTMENT | 3138.52 | 3766.22 | 0.092 | 0.110 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T N1 APARTMENT | 2357.23 | 2828.67 | 0.069 | 0.083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T N2 APARTMENT | 2357.41 | 2828.89 | 0.069 | 0.083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T S1 APARTMENT | 2340.91 | 2809.09 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
T S2 APARTMENT | 2341.09 | 2809.30 | 0.068 | 0.082 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -41.90 | 0.00006 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.16 | 0.16 | 0.08 | 0.08 |
SPLIT GNW | 0.12 | 0.12 | 0.08 | 0.08 |
SPLIT OFFICE | 0.44 | 0.44 | 0.15 | 0.15 |
SPLIT GNE | 0.09 | 0.09 | 0.08 | 0.08 |
SPLIT GN1 | 0.07 | 0.07 | 0.06 | 0.06 |
SPLIT GN2 | 0.07 | 0.07 | 0.06 | 0.06 |
SPLIT GS1 | 0.12 | 0.12 | 0.06 | 0.06 |
SPLIT GS2 | 0.12 | 0.12 | 0.06 | 0.06 |
SPLIT MSW | 0.48 | 0.48 | 0.11 | 0.11 |
SPLIT MNW | 0.37 | 0.37 | 0.11 | 0.11 |
SPLIT MSE | 0.47 | 0.47 | 0.11 | 0.11 |
SPLIT MNE | 0.31 | 0.31 | 0.12 | 0.12 |
SPLIT MN1 | 0.23 | 0.23 | 0.06 | 0.06 |
SPLIT MN2 | 0.23 | 0.23 | 0.06 | 0.06 |
SPLIT MS1 | 0.38 | 0.38 | 0.06 | 0.06 |
SPLIT MS2 | 0.38 | 0.38 | 0.06 | 0.06 |
SPLIT TSW | 0.30 | 0.30 | 0.11 | 0.11 |
SPLIT TNW | 0.23 | 0.23 | 0.11 | 0.11 |
SPLIT TSE | 0.29 | 0.29 | 0.11 | 0.11 |
SPLIT TNE | 0.18 | 0.18 | 0.11 | 0.11 |
SPLIT TN1 | 0.14 | 0.14 | 0.08 | 0.08 |
SPLIT TN2 | 0.14 | 0.14 | 0.08 | 0.08 |
SPLIT TS1 | 0.25 | 0.25 | 0.08 | 0.08 |
SPLIT TS2 | 0.25 | 0.25 | 0.08 | 0.08 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4443.25 | 7407.25 | 4031.00 |
G NW APARTMENT | 4549.50 | 7772.50 | 4397.25 |
OFFICE | 959.00 | 1816.00 | 909.75 |
G NE APARTMENT | 4564.50 | 7661.50 | 4347.50 |
G N1 APARTMENT | 4272.25 | 7968.75 | 4207.75 |
G N2 APARTMENT | 4273.00 | 7964.50 | 4206.75 |
G S1 APARTMENT | 4096.25 | 7445.50 | 3796.50 |
G S2 APARTMENT | 4202.25 | 7363.00 | 3862.50 |
M SW APARTMENT | 4219.75 | 5831.25 | 2890.50 |
M NW APARTMENT | 4499.00 | 6426.25 | 3472.00 |
M SE APARTMENT | 4268.25 | 5739.00 | 2812.75 |
M NE APARTMENT | 4583.75 | 6324.75 | 3412.75 |
M N1 APARTMENT | 3598.25 | 6384.75 | 2702.25 |
M N2 APARTMENT | 3596.00 | 6365.25 | 2695.50 |
M S1 APARTMENT | 3063.00 | 5603.25 | 1800.50 |
M S2 APARTMENT | 3065.25 | 5596.75 | 1798.50 |
T SW APARTMENT | 5234.25 | 6494.75 | 4064.00 |
T NW APARTMENT | 5411.00 | 6928.25 | 4457.00 |
T SE APARTMENT | 5269.25 | 6401.75 | 3997.00 |
T NE APARTMENT | 5459.25 | 6879.25 | 4409.50 |
T N1 APARTMENT | 5093.50 | 6977.50 | 4240.50 |
T N2 APARTMENT | 5094.00 | 6970.75 | 4236.75 |
T S1 APARTMENT | 4899.25 | 6386.75 | 3771.50 |
T S2 APARTMENT | 4902.00 | 6374.75 | 3768.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6318.50 | 7994.75 | 4621.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
G NW APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
OFFICE | 29.25 | 0.50 | 0.75 | 0.00 |
G NE APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G N1 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
G N2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
G S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M SW APARTMENT | 6.75 | 0.00 | 6.75 | 0.00 |
M NW APARTMENT | 12.50 | 0.00 | 12.50 | 0.00 |
M SE APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
M NE APARTMENT | 13.25 | 0.00 | 13.25 | 0.00 |
M N1 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
M N2 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
M S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M S2 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T SW APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
T NW APARTMENT | 12.75 | 0.00 | 12.75 | 0.00 |
T SE APARTMENT | 6.00 | 0.00 | 6.00 | 0.00 |
T NE APARTMENT | 13.00 | 0.00 | 13.00 | 0.00 |
T N1 APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
T N2 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
T S1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
T S2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 77.00 | 0.50 | 48.50 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.367 | 0.114 | 0.000 | 0.044 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.114 | 0.000 | 0.043 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.520 | 0.110 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.114 | 0.000 | 0.043 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.069 | 0.000 | 0.043 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.069 | 0.000 | 0.043 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.069 | 0.000 | 0.044 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.069 | 0.000 | 0.044 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.051 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.052 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.051 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.164 | 0.000 | 0.052 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.099 | 0.000 | 0.051 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.099 | 0.000 | 0.051 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.099 | 0.000 | 0.051 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.099 | 0.000 | 0.051 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.217 | 0.000 | 0.057 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.217 | 0.000 | 0.057 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.217 | 0.000 | 0.057 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.217 | 0.000 | 0.057 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.057 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.057 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.057 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.057 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.502 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.371 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 502.69 | 0.00 | 01-JAN-00:15 | 33128.08 | 09-JAN-07:30 |
WaterSystems:Electricity | 502.69 | 0.00 | 01-JAN-00:15 | 33128.08 | 09-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 502.69 | 0.00 | 01-JAN-00:15 | 33128.08 | 09-JAN-07:30 |
Fans:Electricity | 213.26 | 6762.30 | 04-JAN-12:00 | 6762.30 | 01-JAN-06:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
ElectricityPurchased:Plant | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
Cogeneration:ElectricityPurchased | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
ElectricityNet:Plant | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
Cogeneration:ElectricityNet | 1431.76 | 17474.28 | 05-JUN-02:45 | 82068.52 | 11-AUG-18:00 |
ExteriorLights:Electricity | 39.80 | 0.00 | 01-JAN-11:30 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 39.80 | 0.00 | 01-JAN-11:30 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 253.16 | 6762.30 | 04-JAN-12:00 | 22816.59 | 29-JUL-16:15 |
General:Fans:Electricity | 213.26 | 6762.30 | 04-JAN-12:00 | 6762.30 | 01-JAN-06:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 39.90 | 0.00 | 01-JAN-00:15 | 16054.30 | 29-JUL-16:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1107.35 | 0.00 | 17-APR-16:15 | 158809.24 | 29-JAN-00:15 |
Gas:HVAC | 1107.35 | 0.00 | 17-APR-16:15 | 158809.24 | 29-JAN-00:15 |
Heating:Gas | 1107.35 | 0.00 | 17-APR-16:15 | 158809.24 | 29-JAN-00:15 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1692.15 | 2669.67 | 29-AUG-17:00 | 215918.98 | 28-JAN-24:00 |
EnergyTransfer:Building | 646.80 | 2422.12 | 29-AUG-17:00 | 88885.01 | 28-JAN-24:00 |
EnergyTransfer:Zone:G SW APARTMENT | 20.27 | 0.13 | 30-MAY-15:00 | 3282.54 | 28-JAN-24:00 |
Heating:EnergyTransfer | 414.65 | 0.00 | 22-MAR-16:15 | 88885.01 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 16.58 | 0.00 | 09-FEB-12:00 | 3282.54 | 28-JAN-24:00 |
Cooling:EnergyTransfer | 232.15 | 0.00 | 01-JAN-18:30 | 52531.18 | 11-JUL-16:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 3.69 | 0.00 | 01-JAN-00:15 | 1562.94 | 11-AUG-16:15 |
EnergyTransfer:Zone:G NW APARTMENT | 21.61 | 0.02 | 03-OCT-14:45 | 3365.18 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 19.04 | 0.00 | 22-MAR-15:15 | 3365.18 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 2.58 | 0.00 | 01-JAN-00:15 | 1244.55 | 11-JUL-17:45 |
EnergyTransfer:Zone:OFFICE | 22.96 | 0.01 | 01-JUL-15:00 | 4717.37 | 29-JAN-07:30 |
Heating:EnergyTransfer:Zone:OFFICE | 2.16 | 0.00 | 01-JAN-00:15 | 4717.37 | 29-JAN-07:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 20.80 | 0.00 | 01-JAN-18:30 | 4213.62 | 23-JUL-12:15 |
EnergyTransfer:Zone:G NE APARTMENT | 21.76 | 0.02 | 25-SEP-01:15 | 3353.50 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 18.70 | 0.00 | 22-MAR-09:45 | 3353.50 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 3.06 | 0.00 | 01-JAN-00:15 | 924.10 | 21-JUL-16:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 14.86 | 0.04 | 12-MAY-12:45 | 2116.36 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 11.87 | 0.00 | 22-MAR-16:15 | 2116.36 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 2.99 | 0.00 | 01-JAN-00:15 | 692.31 | 11-JUL-19:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 14.86 | 0.10 | 23-APR-16:45 | 2116.52 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 11.86 | 0.00 | 22-MAR-16:15 | 2116.52 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.01 | 0.00 | 01-JAN-00:15 | 686.53 | 11-JUL-19:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 13.66 | 0.00 | 12-MAY-18:15 | 2039.00 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 9.68 | 0.00 | 09-FEB-11:30 | 2039.00 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 3.98 | 0.00 | 01-JAN-00:15 | 1186.83 | 23-JUL-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 15.13 | 0.11 | 12-FEB-14:30 | 2197.82 | 29-JAN-00:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 11.08 | 0.00 | 09-FEB-11:30 | 2197.82 | 29-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 4.06 | 0.00 | 01-JAN-00:15 | 1243.41 | 21-JUL-14:15 |
EnergyTransfer:Zone:M SW APARTMENT | 40.47 | 0.26 | 22-FEB-13:15 | 5813.90 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 21.23 | 0.00 | 23-JAN-12:15 | 5813.90 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 19.23 | 0.00 | 01-JAN-00:15 | 4929.14 | 11-AUG-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 39.38 | 0.01 | 10-OCT-15:30 | 5783.64 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 26.78 | 0.00 | 07-FEB-21:00 | 5783.64 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 12.60 | 0.00 | 01-JAN-00:15 | 3956.24 | 11-JUL-17:45 |
EnergyTransfer:Zone:M SE APARTMENT | 42.08 | 0.12 | 17-FEB-12:15 | 5824.03 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 20.79 | 0.00 | 21-JAN-21:30 | 5824.03 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 21.29 | 0.00 | 01-JAN-00:15 | 4831.45 | 22-JUL-11:30 |
EnergyTransfer:Zone:M NE APARTMENT | 40.55 | 0.24 | 27-MAY-02:15 | 5718.98 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 26.09 | 0.00 | 07-FEB-21:00 | 5718.98 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 14.46 | 0.00 | 01-JAN-00:15 | 3362.90 | 21-JUL-16:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 24.05 | 0.30 | 09-OCT-14:00 | 3681.96 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 10.22 | 0.00 | 04-JAN-20:00 | 3681.96 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 13.83 | 0.00 | 01-JAN-00:15 | 2508.61 | 11-JUL-19:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 24.11 | 0.22 | 22-MAR-03:15 | 3680.09 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 10.19 | 0.00 | 04-JAN-20:00 | 3680.09 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 13.92 | 0.00 | 01-JAN-00:15 | 2505.12 | 11-JUL-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 29.04 | 0.06 | 20-JAN-20:30 | 3887.28 | 11-AUG-15:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 6.81 | 0.00 | 04-JAN-19:45 | 3574.04 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 22.23 | 0.00 | 01-JAN-00:15 | 3887.28 | 11-AUG-15:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 29.13 | 0.30 | 20-JAN-20:30 | 3895.50 | 11-AUG-15:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 6.80 | 0.00 | 04-JAN-19:45 | 3575.85 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 22.34 | 0.00 | 01-JAN-00:15 | 3895.50 | 11-AUG-15:15 |
EnergyTransfer:Zone:T SW APARTMENT | 33.33 | 0.03 | 26-APR-24:00 | 4717.16 | 28-JAN-15:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 26.38 | 0.00 | 09-FEB-11:45 | 4717.16 | 28-JAN-15:30 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 6.96 | 0.00 | 01-JAN-00:15 | 3094.29 | 29-JUL-15:30 |
EnergyTransfer:Zone:T NW APARTMENT | 34.20 | 0.01 | 01-OCT-15:00 | 4728.85 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 29.78 | 0.00 | 18-MAR-15:15 | 4728.85 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 4.42 | 0.00 | 01-JAN-00:15 | 2487.82 | 11-JUL-17:45 |
EnergyTransfer:Zone:T SE APARTMENT | 33.68 | 0.03 | 24-JUN-19:45 | 4716.98 | 28-JAN-15:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 25.99 | 0.00 | 09-FEB-11:45 | 4716.98 | 28-JAN-15:30 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 7.69 | 0.00 | 01-JAN-00:15 | 2964.16 | 22-JUL-11:45 |
EnergyTransfer:Zone:T NE APARTMENT | 34.50 | 0.07 | 05-SEP-08:15 | 4676.01 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 29.32 | 0.00 | 18-MAR-11:45 | 4676.01 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 5.18 | 0.00 | 01-JAN-00:15 | 2056.30 | 21-JUL-16:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 24.46 | 0.24 | 08-SEP-08:15 | 3502.77 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 19.87 | 0.00 | 18-MAR-11:30 | 3502.77 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 4.59 | 0.00 | 01-JAN-00:15 | 1605.38 | 11-JUL-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 24.48 | 0.03 | 26-MAY-00:45 | 3501.25 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 19.85 | 0.00 | 18-MAR-11:30 | 3501.25 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 4.63 | 0.00 | 01-JAN-00:15 | 1596.87 | 11-JUL-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 24.09 | 0.22 | 25-JUN-22:45 | 3608.19 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 16.81 | 0.00 | 09-FEB-11:30 | 3608.19 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 7.27 | 0.00 | 01-JAN-00:15 | 2546.96 | 23-JUL-13:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 24.13 | 0.19 | 02-MAY-03:15 | 3609.60 | 28-JAN-24:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 16.80 | 0.00 | 09-FEB-11:30 | 3609.60 | 28-JAN-24:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 7.33 | 0.00 | 01-JAN-00:15 | 2561.35 | 23-JUL-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1045.35 | 0.00 | 02-JUN-01:00 | 127047.39 | 29-JAN-00:15 |
HeatingCoils:EnergyTransfer | 885.88 | 0.00 | 17-APR-16:15 | 127047.39 | 29-JAN-00:15 |
CoolingCoils:EnergyTransfer | 159.47 | 0.00 | 01-JAN-00:15 | 63412.19 | 29-JUL-16:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 16.578 | -3.688 | 0.000 | 0.000 | 3.948 | 1.087 | 12.213 | 9.438 | 0.000 | 0.011 | 0.000 | 0.000 | -13.714 | 0.000 | -6.947 | -18.924 |
G NW APARTMENT | 19.036 | -2.577 | 0.000 | 0.000 | 3.972 | 1.087 | 12.213 | 3.891 | 0.000 | 0.011 | 0.000 | 0.000 | -14.729 | 0.000 | -6.840 | -16.062 |
OFFICE | 2.159 | -20.798 | 0.000 | 0.000 | 0.551 | 26.452 | 9.482 | 10.481 | 0.000 | 0.002 | 0.001 | 0.000 | -12.529 | 0.000 | -6.009 | -9.791 |
G NE APARTMENT | 18.702 | -3.056 | 0.000 | 0.000 | 3.975 | 1.087 | 12.213 | 4.877 | 0.000 | 0.011 | 0.000 | 0.000 | -14.376 | 0.000 | -6.846 | -16.587 |
G N1 APARTMENT | 11.870 | -2.987 | 0.000 | 0.000 | 3.977 | 1.087 | 12.213 | 1.536 | 0.000 | 0.008 | 0.000 | 0.000 | -9.112 | 0.000 | -4.331 | -14.261 |
G N2 APARTMENT | 11.855 | -3.009 | 0.000 | 0.000 | 3.977 | 1.087 | 12.213 | 1.534 | 0.000 | 0.008 | 0.000 | 0.000 | -9.113 | 0.000 | -4.332 | -14.221 |
G S1 APARTMENT | 9.676 | -3.981 | 0.000 | 0.000 | 3.943 | 1.087 | 12.213 | 7.302 | 0.000 | 0.008 | 0.000 | 0.000 | -8.276 | 0.000 | -4.445 | -17.527 |
G S2 APARTMENT | 11.077 | -4.057 | 0.000 | 0.000 | 3.940 | 1.087 | 12.213 | 7.299 | 0.000 | 0.008 | 0.000 | 0.000 | -8.262 | 0.000 | -4.452 | -18.854 |
M SW APARTMENT | 21.235 | -19.233 | 0.000 | 0.000 | 3.861 | 1.087 | 12.213 | 9.076 | 0.000 | 0.014 | 0.000 | 0.000 | -14.337 | 0.000 | -10.056 | -3.861 |
M NW APARTMENT | 26.777 | -12.603 | 0.000 | 0.000 | 3.895 | 1.087 | 12.213 | 3.564 | 0.000 | 0.014 | 0.000 | 0.000 | -15.302 | 0.000 | -9.961 | -9.684 |
M SE APARTMENT | 20.792 | -21.289 | 0.000 | 0.000 | 3.861 | 1.087 | 12.213 | 10.127 | 0.000 | 0.014 | 0.001 | 0.000 | -14.063 | 0.000 | -10.061 | -2.681 |
M NE APARTMENT | 26.091 | -14.463 | 0.000 | 0.000 | 3.896 | 1.087 | 12.213 | 4.535 | 0.000 | 0.014 | 0.000 | 0.000 | -14.946 | 0.000 | -9.962 | -8.464 |
M N1 APARTMENT | 10.215 | -13.834 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 1.333 | 0.000 | 0.011 | 0.942 | 0.000 | -9.531 | 0.000 | -6.324 | -0.000 |
M N2 APARTMENT | 10.189 | -13.922 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 1.332 | 0.000 | 0.011 | 1.060 | 0.000 | -9.532 | 0.000 | -6.325 | -0.000 |
M S1 APARTMENT | 6.809 | -22.226 | 0.000 | 0.000 | 3.846 | 1.087 | 12.213 | 7.075 | 0.000 | 0.011 | 6.270 | 0.000 | -8.684 | 0.000 | -6.400 | -0.001 |
M S2 APARTMENT | 6.798 | -22.337 | 0.000 | 0.000 | 3.845 | 1.087 | 12.213 | 7.074 | 0.000 | 0.011 | 6.396 | 0.000 | -8.684 | 0.000 | -6.401 | -0.001 |
T SW APARTMENT | 26.377 | -6.956 | 0.000 | 0.000 | 3.911 | 1.087 | 12.213 | 9.065 | 0.000 | 0.019 | 0.000 | 0.000 | -13.847 | 0.000 | -12.974 | -18.894 |
T NW APARTMENT | 29.776 | -4.424 | 0.000 | 0.000 | 3.936 | 1.087 | 12.213 | 3.585 | 0.000 | 0.019 | 0.000 | 0.000 | -14.828 | 0.000 | -12.857 | -18.506 |
T SE APARTMENT | 25.989 | -7.694 | 0.000 | 0.000 | 3.910 | 1.087 | 12.213 | 10.139 | 0.000 | 0.019 | 0.000 | 0.000 | -13.610 | 0.000 | -12.983 | -19.070 |
T NE APARTMENT | 29.315 | -5.181 | 0.000 | 0.000 | 3.941 | 1.087 | 12.213 | 4.570 | 0.000 | 0.019 | 0.000 | 0.000 | -14.488 | 0.000 | -12.856 | -18.619 |
T N1 APARTMENT | 19.867 | -4.594 | 0.000 | 0.000 | 3.936 | 1.087 | 12.213 | 1.367 | 0.000 | 0.015 | 0.000 | 0.000 | -9.194 | 0.000 | -8.077 | -16.618 |
T N2 APARTMENT | 19.849 | -4.635 | 0.000 | 0.000 | 3.936 | 1.087 | 12.213 | 1.364 | 0.000 | 0.015 | 0.000 | 0.000 | -9.194 | 0.000 | -8.079 | -16.556 |
T S1 APARTMENT | 16.814 | -7.274 | 0.000 | 0.000 | 3.897 | 1.087 | 12.213 | 7.078 | 0.000 | 0.015 | 0.000 | 0.000 | -8.389 | 0.000 | -8.184 | -17.256 |
T S2 APARTMENT | 16.800 | -7.331 | 0.000 | 0.000 | 3.897 | 1.087 | 12.213 | 7.075 | 0.000 | 0.015 | 0.000 | 0.000 | -8.389 | 0.000 | -8.184 | -17.182 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.015 | 0.000 | 0.000 | 0.000 | 0.000 | -1.603 | 0.000 | -2.144 | -10.850 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.085 | 0.000 | 0.012 | 43.203 | 0.000 | -4.148 | 0.000 | -60.212 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.015 | 0.000 | 0.000 | 0.000 | 0.000 | -1.723 | 0.000 | -1.735 | -11.139 |
Total Facility | 414.647 | -232.149 | 0.000 | 0.000 | 90.627 | 95.189 | 296.854 | 134.834 | 0.000 | 0.314 | 57.872 | 0.000 | -284.601 | 0.000 | -257.977 | -315.609 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-AUG-16:15 | 0.00 | -1563.08 | 0.00 | 0.00 | 84.75 | 64.86 | 588.62 | 2158.17 | 0.00 | 61.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1394.50 |
G NW APARTMENT | 11-JUL-17:45 | 0.00 | -1244.35 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 1636.78 | 0.00 | 90.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1300.90 |
OFFICE | 27-AUG-06:01 | 0.00 | -7065.21 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 486.66 | 0.00 | 0.00 | 5938.13 | 0.00 | 0.00 | 0.00 | -70.04 | 0.00 |
G NE APARTMENT | 21-JUL-16:10 | 0.00 | -924.64 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 548.50 | 0.00 | 161.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -523.57 |
G N1 APARTMENT | 29-SEP-06:50 | 0.00 | -744.29 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 759.49 | 0.00 | -425.76 | 0.00 | -175.43 | 0.00 |
G N2 APARTMENT | 29-SEP-06:50 | 0.00 | -745.96 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 761.18 | 0.00 | -425.78 | 0.00 | -175.42 | 0.00 |
G S1 APARTMENT | 23-JUL-13:30 | 0.00 | -1186.69 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2232.20 | 0.00 | 11.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1493.09 |
G S2 APARTMENT | 21-JUL-14:15 | 0.00 | -1243.30 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1955.03 | 0.00 | 52.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1228.37 |
M SW APARTMENT | 11-AUG-16:15 | 0.00 | -4929.55 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2136.94 | 0.00 | 83.97 | 1970.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 11-JUL-17:45 | 0.00 | -3955.60 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 1617.89 | 0.00 | 124.11 | 1395.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 22-JUL-11:30 | 0.00 | -4831.14 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2745.04 | 0.00 | 43.30 | 1582.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 21-JUL-16:00 | 0.00 | -3362.40 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 580.08 | 0.00 | 327.08 | 1890.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 11-JUL-19:00 | 0.00 | -2508.34 | 0.00 | 0.00 | 141.80 | 103.77 | 547.42 | 262.16 | 0.00 | 97.29 | 1355.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 11-JUL-17:30 | 0.00 | -2505.11 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 231.94 | 0.00 | 103.99 | 1351.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 11-AUG-15:15 | 0.00 | -3887.55 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 1698.92 | 0.00 | 16.18 | 1607.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 11-AUG-15:15 | 0.00 | -3895.77 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 1698.86 | 0.00 | 16.18 | 1615.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 29-JUL-15:30 | 0.00 | -3094.45 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2489.76 | 0.00 | 163.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -124.38 |
T NW APARTMENT | 11-JUL-17:45 | 0.00 | -2487.40 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 1594.65 | 0.00 | 157.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83.12 |
T SE APARTMENT | 22-JUL-11:45 | 0.00 | -2963.93 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2538.69 | 0.00 | 83.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.66 |
T NE APARTMENT | 21-JUL-16:00 | 0.00 | -2055.97 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 565.86 | 0.00 | 429.18 | 495.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 11-JUL-17:15 | 0.00 | -1605.42 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 235.95 | 0.00 | 132.55 | 418.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 11-JUL-17:15 | 0.00 | -1596.91 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 236.07 | 0.00 | 132.55 | 410.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 23-JUL-13:45 | 0.00 | -2546.74 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2127.44 | 0.00 | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34.77 |
T S2 APARTMENT | 23-JUL-13:45 | 0.00 | -2561.14 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2127.25 | 0.00 | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20.19 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-16:00 | 0.00 | -52528.94 | 0.00 | 0.00 | 1191.96 | 4512.09 | 11708.34 | 24308.04 | 0.00 | 2348.55 | 8496.00 | 0.00 | 0.00 | 0.00 | -36.02 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 28-JAN-24:00 | 3282.52 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1119.79 | 0.00 | -2066.56 | -643.45 |
G NW APARTMENT | 28-JAN-24:00 | 3365.15 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1142.12 | 0.00 | -2066.56 | -703.75 |
OFFICE | 24-DEC-07:01 | 7263.13 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -456.24 | 0.00 | -277.39 | -7239.96 |
G NE APARTMENT | 28-JAN-24:00 | 3353.47 | 0.00 | 0.00 | 0.00 | 189.67 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.13 | 0.00 | -2065.76 | -675.87 |
G N1 APARTMENT | 29-JAN-00:15 | 2116.35 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -702.71 | 0.00 | -1214.70 | -659.98 |
G N2 APARTMENT | 29-JAN-00:15 | 2116.51 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -702.71 | 0.00 | -1214.70 | -660.14 |
G S1 APARTMENT | 29-JAN-00:15 | 2039.00 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -680.40 | 0.00 | -1214.70 | -604.93 |
G S2 APARTMENT | 29-JAN-00:15 | 2197.81 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.31 | 0.00 | -1214.70 | -765.83 |
M SW APARTMENT | 28-JAN-15:00 | 5813.77 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -341.65 | 0.00 | -2731.82 | -3183.29 |
M NW APARTMENT | 28-JAN-15:00 | 5783.50 | 0.00 | 0.00 | 0.00 | 48.63 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -871.98 | 0.00 | -2688.70 | -2667.02 |
M SE APARTMENT | 28-JAN-15:00 | 5823.89 | 0.00 | 0.00 | 0.00 | 47.43 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -508.27 | 0.00 | -2729.53 | -3029.10 |
M NE APARTMENT | 28-JAN-15:00 | 5718.84 | 0.00 | 0.00 | 0.00 | 48.89 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1036.41 | 0.00 | -2679.82 | -2447.08 |
M N1 APARTMENT | 28-JAN-15:00 | 3681.88 | 0.00 | 0.00 | 0.00 | 47.46 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.34 | 0.00 | -1648.12 | -1840.45 |
M N2 APARTMENT | 28-JAN-15:00 | 3680.00 | 0.00 | 0.00 | 0.00 | 47.46 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -636.33 | 0.00 | -1648.05 | -1838.67 |
M S1 APARTMENT | 28-JAN-24:00 | 3574.01 | 0.00 | 0.00 | 0.00 | 192.25 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -695.14 | 0.00 | -1775.94 | -1652.79 |
M S2 APARTMENT | 28-JAN-24:00 | 3575.82 | 0.00 | 0.00 | 0.00 | 192.23 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -695.15 | 0.00 | -1776.02 | -1654.50 |
T SW APARTMENT | 28-JAN-15:30 | 4717.09 | 0.00 | 0.00 | 0.00 | 47.42 | 22.70 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -934.13 | 0.00 | -3476.00 | -777.35 |
T NW APARTMENT | 28-JAN-15:00 | 4728.73 | 0.00 | 0.00 | 0.00 | 48.25 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -857.87 | 0.00 | -3570.87 | -743.82 |
T SE APARTMENT | 28-JAN-15:30 | 4716.91 | 0.00 | 0.00 | 0.00 | 47.55 | 22.70 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -977.51 | 0.00 | -3470.30 | -739.62 |
T NE APARTMENT | 28-JAN-15:00 | 4675.89 | 0.00 | 0.00 | 0.00 | 48.62 | 12.97 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1020.82 | 0.00 | -3554.13 | -545.14 |
T N1 APARTMENT | 28-JAN-24:00 | 3502.73 | 0.00 | 0.00 | 0.00 | 192.64 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -707.03 | 0.00 | -2348.67 | -997.28 |
T N2 APARTMENT | 28-JAN-24:00 | 3501.21 | 0.00 | 0.00 | 0.00 | 192.72 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -706.88 | 0.00 | -2348.18 | -996.48 |
T S1 APARTMENT | 28-JAN-24:00 | 3608.17 | 0.00 | 0.00 | 0.00 | 190.00 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -684.00 | 0.00 | -2366.34 | -1105.45 |
T S2 APARTMENT | 28-JAN-24:00 | 3609.58 | 0.00 | 0.00 | 0.00 | 190.00 | 16.21 | 341.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -683.99 | 0.00 | -2366.36 | -1106.85 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JAN-24:00 | 88883.85 | 0.00 | 0.00 | 0.00 | 4503.01 | 2176.23 | 8134.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22319.09 | 0.00 | -57415.49 | -23963.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Sec1.1A-General InformationData | |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 48.50 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 48.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 39.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1107.35 | 158809.24 | 0.00 | 0.00 |
Space Cooling | 39.90 | 12449.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 213.26 | 6762.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 502.69 | 31245.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1431.76 | 1107.35 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1431.76 |
Natural Gas | 0.00 | 1107.35 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 2539.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 12.73 |
Fans-Interior | 68.03 |
Service Water Heating | 160.37 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.70 |
Subtotal | 456.76 |
Natural Gas [MJ/m2] | |
Space Heating | 353.27 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 353.27 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.67 |
Space Heating | 43.61 |
Space Cooling | 1.57 |
Fans-Interior | 8.40 |
Service Water Heating | 19.80 |
Receptacle Equipment | 20.39 |
Miscellaneous | 1.57 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.160397 |
G NW APARTMENT DIRECT AIR | 0.119433 |
OFFICE DIRECT AIR | 0.441127 |
G NE APARTMENT DIRECT AIR | 0.087796 |
G N1 APARTMENT DIRECT AIR | 0.066489 |
G N2 APARTMENT DIRECT AIR | 0.065401 |
G S1 APARTMENT DIRECT AIR | 0.121759 |
G S2 APARTMENT DIRECT AIR | 0.124962 |
M SW APARTMENT DIRECT AIR | 0.483313 |
M NW APARTMENT DIRECT AIR | 0.372955 |
M SE APARTMENT DIRECT AIR | 0.466076 |
M NE APARTMENT DIRECT AIR | 0.307482 |
M N1 APARTMENT DIRECT AIR | 0.233448 |
M N2 APARTMENT DIRECT AIR | 0.231406 |
M S1 APARTMENT DIRECT AIR | 0.381290 |
M S2 APARTMENT DIRECT AIR | 0.382570 |
T SW APARTMENT DIRECT AIR | 0.302682 |
T NW APARTMENT DIRECT AIR | 0.228904 |
T SE APARTMENT DIRECT AIR | 0.290812 |
T NE APARTMENT DIRECT AIR | 0.180255 |
T N1 APARTMENT DIRECT AIR | 0.137818 |
T N2 APARTMENT DIRECT AIR | 0.136202 |
T S1 APARTMENT DIRECT AIR | 0.250888 |
T S2 APARTMENT DIRECT AIR | 0.251887 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.160397 |
SPLIT GNW MAIN BRANCH | 0.119433 |
SPLIT OFFICE MAIN BRANCH | 0.441127 |
SPLIT GNE MAIN BRANCH | 0.087796 |
SPLIT GN1 MAIN BRANCH | 0.066489 |
SPLIT GN2 MAIN BRANCH | 0.065401 |
SPLIT GS1 MAIN BRANCH | 0.121759 |
SPLIT GS2 MAIN BRANCH | 0.124962 |
SPLIT MSW MAIN BRANCH | 0.483313 |
SPLIT MNW MAIN BRANCH | 0.372955 |
SPLIT MSE MAIN BRANCH | 0.466076 |
SPLIT MNE MAIN BRANCH | 0.307482 |
SPLIT MN1 MAIN BRANCH | 0.233448 |
SPLIT MN2 MAIN BRANCH | 0.231406 |
SPLIT MS1 MAIN BRANCH | 0.381290 |
SPLIT MS2 MAIN BRANCH | 0.382570 |
SPLIT TSW MAIN BRANCH | 0.302682 |
SPLIT TNW MAIN BRANCH | 0.228904 |
SPLIT TSE MAIN BRANCH | 0.290812 |
SPLIT TNE MAIN BRANCH | 0.180255 |
SPLIT TN1 MAIN BRANCH | 0.137818 |
SPLIT TN2 MAIN BRANCH | 0.136202 |
SPLIT TS1 MAIN BRANCH | 0.250888 |
SPLIT TS2 MAIN BRANCH | 0.251887 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.160397 |
SPLIT GNW | 0.119433 |
SPLIT OFFICE | 0.441127 |
SPLIT GNE | 0.087796 |
SPLIT GN1 | 0.066489 |
SPLIT GN2 | 0.065401 |
SPLIT GS1 | 0.121759 |
SPLIT GS2 | 0.124962 |
SPLIT MSW | 0.483313 |
SPLIT MNW | 0.372955 |
SPLIT MSE | 0.466076 |
SPLIT MNE | 0.307482 |
SPLIT MN1 | 0.233448 |
SPLIT MN2 | 0.231406 |
SPLIT MS1 | 0.381290 |
SPLIT MS2 | 0.382570 |
SPLIT TSW | 0.302682 |
SPLIT TNW | 0.228904 |
SPLIT TSE | 0.290812 |
SPLIT TNE | 0.180255 |
SPLIT TN1 | 0.137818 |
SPLIT TN2 | 0.136202 |
SPLIT TS1 | 0.250888 |
SPLIT TS2 | 0.251887 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.160397 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.119433 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.441127 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.087796 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.066489 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.065401 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.121759 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.124962 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.483313 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.372955 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.466076 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.307482 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.233448 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.231406 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.381290 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.382570 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.302682 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.228904 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.290812 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.180255 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.137818 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.136202 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.250888 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.251887 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.160397 | 2655.15 | 0.798655 |
SPLIT GNW COOLING COIL | 0.119433 | 1977.04 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.441127 | 7302.21 | 0.798655 |
SPLIT GNE COOLING COIL | 0.087796 | 1453.34 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.066489 | 1100.63 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.065401 | 1082.61 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.121759 | 2015.54 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.124962 | 2068.56 | 0.798655 |
SPLIT MSW COOLING COIL | 0.483313 | 8000.55 | 0.798655 |
SPLIT MNW COOLING COIL | 0.372955 | 6173.73 | 0.798655 |
SPLIT MSE COOLING COIL | 0.466076 | 7715.21 | 0.798655 |
SPLIT MNE COOLING COIL | 0.307482 | 5089.93 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.233448 | 3864.40 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.231406 | 3830.60 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.381290 | 6311.71 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.382570 | 6332.89 | 0.798655 |
SPLIT TSW COOLING COIL | 0.302682 | 5010.47 | 0.798655 |
SPLIT TNW COOLING COIL | 0.228904 | 3789.17 | 0.798655 |
SPLIT TSE COOLING COIL | 0.290812 | 4813.97 | 0.798655 |
SPLIT TNE COOLING COIL | 0.180255 | 2983.86 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.137818 | 2281.37 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.136202 | 2254.63 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.250888 | 4153.09 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.251887 | 4169.63 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.160397 | 0.160397 | 0.160397 | 0.160397 | 4743.27 | 2655.15 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.119433 | 0.119433 | 0.119433 | 0.119433 | 4687.30 | 1977.04 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.441127 | 0.441127 | 0.441127 | 0.441127 | 7957.76 | 7302.21 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.087796 | 0.087796 | 0.087796 | 0.087796 | 4693.33 | 1453.34 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.066489 | 0.066489 | 0.066489 | 0.066489 | 3903.99 | 1100.63 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.065401 | 0.065401 | 0.065401 | 0.065401 | 3904.12 | 1082.61 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.121759 | 0.121759 | 0.121759 | 0.121759 | 3892.09 | 2015.54 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.124962 | 0.124962 | 0.124962 | 0.124962 | 4034.18 | 2068.56 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.483313 | 0.483313 | 0.483313 | 0.483313 | 7769.23 | 8000.55 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.372955 | 0.372955 | 0.372955 | 0.372955 | 7797.98 | 6173.73 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.466076 | 0.466076 | 0.466076 | 0.466076 | 7785.25 | 7715.21 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.307482 | 0.307482 | 0.307482 | 0.307482 | 7814.02 | 5089.93 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.233448 | 0.233448 | 0.233448 | 0.233448 | 5966.13 | 3864.40 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.231406 | 0.231406 | 0.231406 | 0.231406 | 5966.50 | 3830.60 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.381290 | 0.381290 | 0.381290 | 0.381290 | 5941.02 | 6311.71 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.382570 | 0.382570 | 0.382570 | 0.382570 | 5941.38 | 6332.89 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.302682 | 0.302682 | 0.302682 | 0.302682 | 5650.78 | 5010.47 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.228904 | 0.228904 | 0.228904 | 0.228904 | 5668.71 | 3789.17 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.290812 | 0.290812 | 0.290812 | 0.290812 | 5659.62 | 4813.97 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.180255 | 0.180255 | 0.180255 | 0.180255 | 5677.56 | 2983.86 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.137818 | 0.137818 | 0.137818 | 0.137818 | 4753.68 | 2281.37 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.136202 | 0.136202 | 0.136202 | 0.136202 | 4753.89 | 2254.63 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.250888 | 0.250888 | 0.250888 | 0.250888 | 4734.38 | 4153.09 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.251887 | 0.251887 | 0.251887 | 0.251887 | 4734.59 | 4169.63 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.160397 |
SPLIT GNW SUPPLY FAN | 0.119433 |
SPLIT OFFICE SUPPLY FAN | 0.441127 |
SPLIT GNE SUPPLY FAN | 0.087796 |
SPLIT GN1 SUPPLY FAN | 0.066489 |
SPLIT GN2 SUPPLY FAN | 0.065401 |
SPLIT GS1 SUPPLY FAN | 0.121759 |
SPLIT GS2 SUPPLY FAN | 0.124962 |
SPLIT MSW SUPPLY FAN | 0.483313 |
SPLIT MNW SUPPLY FAN | 0.372955 |
SPLIT MSE SUPPLY FAN | 0.466076 |
SPLIT MNE SUPPLY FAN | 0.307482 |
SPLIT MN1 SUPPLY FAN | 0.233448 |
SPLIT MN2 SUPPLY FAN | 0.231406 |
SPLIT MS1 SUPPLY FAN | 0.381290 |
SPLIT MS2 SUPPLY FAN | 0.382570 |
SPLIT TSW SUPPLY FAN | 0.302682 |
SPLIT TNW SUPPLY FAN | 0.228904 |
SPLIT TSE SUPPLY FAN | 0.290812 |
SPLIT TNE SUPPLY FAN | 0.180255 |
SPLIT TN1 SUPPLY FAN | 0.137818 |
SPLIT TN2 SUPPLY FAN | 0.136202 |
SPLIT TS1 SUPPLY FAN | 0.250888 |
SPLIT TS2 SUPPLY FAN | 0.251887 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 4743.27 |
SPLIT GNW HEATING COIL | 4687.30 |
SPLIT OFFICE HEATING COIL | 7957.76 |
SPLIT GNE HEATING COIL | 4693.33 |
SPLIT GN1 HEATING COIL | 3903.99 |
SPLIT GN2 HEATING COIL | 3904.12 |
SPLIT GS1 HEATING COIL | 3892.09 |
SPLIT GS2 HEATING COIL | 4034.18 |
SPLIT MSW HEATING COIL | 7769.23 |
SPLIT MNW HEATING COIL | 7797.98 |
SPLIT MSE HEATING COIL | 7785.25 |
SPLIT MNE HEATING COIL | 7814.02 |
SPLIT MN1 HEATING COIL | 5966.13 |
SPLIT MN2 HEATING COIL | 5966.50 |
SPLIT MS1 HEATING COIL | 5941.02 |
SPLIT MS2 HEATING COIL | 5941.38 |
SPLIT TSW HEATING COIL | 5650.78 |
SPLIT TNW HEATING COIL | 5668.71 |
SPLIT TSE HEATING COIL | 5659.62 |
SPLIT TNE HEATING COIL | 5677.56 |
SPLIT TN1 HEATING COIL | 4753.68 |
SPLIT TN2 HEATING COIL | 4753.89 |
SPLIT TS1 HEATING COIL | 4734.38 |
SPLIT TS2 HEATING COIL | 4734.59 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.92 | 0.73 |
May | 22.39 | 10.60 |
June | 23.92 | 15.96 |
July | 24.14 | 16.86 |
August | 23.84 | 14.24 |
September | 22.57 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.42 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.14 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.73 | 0.73 |
May | 21.98 | 10.60 |
June | 23.76 | 15.96 |
July | 24.04 | 16.86 |
August | 23.54 | 14.24 |
September | 22.11 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.28 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.04 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.45 | -17.6 |
February | 17.93 | -15.4 |
March | 18.74 | -10.3 |
April | 20.92 | 0.73 |
May | 23.04 | 10.60 |
June | 25.24 | 15.96 |
July | 25.64 | 16.86 |
August | 25.07 | 14.24 |
September | 23.39 | 6.72 |
October | 20.15 | -3.1 |
November | 17.51 | -17.6 |
December | 17.29 | -19.3 |
Annual Sum or Average | 21.05 | -1.4 |
Minimum of Months | 17.29 | -19.3 |
Maximum of Months | 25.64 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.71 | 0.73 |
May | 22.02 | 10.60 |
June | 23.80 | 15.96 |
July | 24.04 | 16.86 |
August | 23.55 | 14.24 |
September | 22.10 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.29 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.04 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.70 | 0.73 |
May | 21.84 | 10.60 |
June | 23.66 | 15.96 |
July | 23.99 | 16.86 |
August | 23.51 | 14.24 |
September | 22.13 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.26 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.99 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.70 | 0.73 |
May | 21.84 | 10.60 |
June | 23.66 | 15.96 |
July | 23.99 | 16.86 |
August | 23.51 | 14.24 |
September | 22.13 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.26 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 23.99 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.89 | 0.73 |
May | 22.32 | 10.60 |
June | 23.94 | 15.96 |
July | 24.17 | 16.86 |
August | 23.94 | 14.24 |
September | 22.78 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.17 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.89 | 0.73 |
May | 22.35 | 10.60 |
June | 23.98 | 15.96 |
July | 24.20 | 16.86 |
August | 23.97 | 14.24 |
September | 22.81 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.20 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -17.6 |
February | 21.70 | -15.4 |
March | 21.75 | -10.3 |
April | 22.74 | 0.73 |
May | 24.03 | 10.60 |
June | 24.37 | 15.96 |
July | 24.40 | 16.86 |
August | 24.32 | 14.24 |
September | 23.44 | 6.72 |
October | 21.83 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.81 | -1.4 |
Minimum of Months | 21.69 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 22.03 | 0.73 |
May | 23.69 | 10.60 |
June | 24.36 | 15.96 |
July | 24.39 | 16.86 |
August | 24.21 | 14.24 |
September | 22.77 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.64 | -1.4 |
Minimum of Months | 21.69 | -19.3 |
Maximum of Months | 24.39 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -17.6 |
February | 21.70 | -15.4 |
March | 21.76 | -10.3 |
April | 22.75 | 0.73 |
May | 24.07 | 10.60 |
June | 24.37 | 15.96 |
July | 24.40 | 16.86 |
August | 24.33 | 14.24 |
September | 23.48 | 6.72 |
October | 21.86 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.82 | -1.4 |
Minimum of Months | 21.69 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.99 | 0.73 |
May | 23.77 | 10.60 |
June | 24.36 | 15.96 |
July | 24.39 | 16.86 |
August | 24.22 | 14.24 |
September | 22.81 | 6.72 |
October | 21.71 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.65 | -1.4 |
Minimum of Months | 21.68 | -19.3 |
Maximum of Months | 24.39 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.96 | 0.73 |
May | 23.79 | 10.60 |
June | 24.38 | 15.96 |
July | 24.40 | 16.86 |
August | 24.26 | 14.24 |
September | 22.97 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.96 | 0.73 |
May | 23.80 | 10.60 |
June | 24.38 | 15.96 |
July | 24.40 | 16.86 |
August | 24.27 | 14.24 |
September | 22.98 | 6.72 |
October | 21.73 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.67 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.79 | -10.3 |
April | 22.91 | 0.73 |
May | 24.17 | 10.60 |
June | 24.39 | 15.96 |
July | 24.40 | 16.86 |
August | 24.36 | 14.24 |
September | 23.70 | 6.72 |
October | 22.01 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.88 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.71 | -15.4 |
March | 21.79 | -10.3 |
April | 22.91 | 0.73 |
May | 24.18 | 10.60 |
June | 24.39 | 15.96 |
July | 24.40 | 16.86 |
August | 24.36 | 14.24 |
September | 23.71 | 6.72 |
October | 22.01 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.89 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -17.6 |
February | 21.70 | -15.4 |
March | 21.75 | -10.3 |
April | 22.43 | 0.73 |
May | 23.36 | 10.60 |
June | 24.21 | 15.96 |
July | 24.30 | 16.86 |
August | 23.98 | 14.24 |
September | 22.59 | 6.72 |
October | 21.75 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.60 | -1.4 |
Minimum of Months | 21.69 | -19.3 |
Maximum of Months | 24.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.97 | 0.73 |
May | 23.03 | 10.60 |
June | 24.18 | 15.96 |
July | 24.26 | 16.86 |
August | 23.73 | 14.24 |
September | 22.11 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.68 | -19.3 |
Maximum of Months | 24.26 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -17.6 |
February | 21.70 | -15.4 |
March | 21.76 | -10.3 |
April | 22.43 | 0.73 |
May | 23.47 | 10.60 |
June | 24.23 | 15.96 |
July | 24.31 | 16.86 |
August | 24.01 | 14.24 |
September | 22.64 | 6.72 |
October | 21.76 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.62 | -1.4 |
Minimum of Months | 21.69 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.94 | 0.73 |
May | 23.18 | 10.60 |
June | 24.16 | 15.96 |
July | 24.22 | 16.86 |
August | 23.71 | 14.24 |
September | 22.09 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.68 | -19.3 |
Maximum of Months | 24.22 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.90 | 0.73 |
May | 23.05 | 10.60 |
June | 24.22 | 15.96 |
July | 24.28 | 16.86 |
August | 23.76 | 14.24 |
September | 22.06 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.70 | -10.3 |
April | 21.90 | 0.73 |
May | 23.07 | 10.60 |
June | 24.21 | 15.96 |
July | 24.28 | 16.86 |
August | 23.76 | 14.24 |
September | 22.06 | 6.72 |
October | 21.70 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.46 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.28 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.76 | -10.3 |
April | 22.50 | 0.73 |
May | 23.52 | 10.60 |
June | 24.28 | 15.96 |
July | 24.35 | 16.86 |
August | 24.11 | 14.24 |
September | 22.76 | 6.72 |
October | 21.79 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -17.6 |
February | 21.70 | -15.4 |
March | 21.77 | -10.3 |
April | 22.50 | 0.73 |
May | 23.53 | 10.60 |
June | 24.28 | 15.96 |
July | 24.35 | 16.86 |
August | 24.11 | 14.24 |
September | 22.77 | 6.72 |
October | 21.79 | -3.1 |
November | 21.70 | -17.6 |
December | 21.70 | -19.3 |
Annual Sum or Average | 22.66 | -1.4 |
Minimum of Months | 21.70 | -19.3 |
Maximum of Months | 24.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.71 | -17.6 |
February | 20.05 | -15.4 |
March | 20.72 | -10.3 |
April | 22.41 | 0.73 |
May | 24.60 | 10.60 |
June | 26.15 | 15.96 |
July | 26.26 | 16.86 |
August | 25.49 | 14.24 |
September | 23.04 | 6.72 |
October | 21.15 | -3.1 |
November | 19.92 | -17.6 |
December | 19.61 | -19.3 |
Annual Sum or Average | 22.44 | -1.4 |
Minimum of Months | 19.61 | -19.3 |
Maximum of Months | 26.26 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.77 | -17.6 |
February | 15.34 | -15.4 |
March | 16.46 | -10.3 |
April | 18.93 | 0.73 |
May | 21.33 | 10.60 |
June | 24.02 | 15.96 |
July | 24.58 | 16.86 |
August | 23.79 | 14.24 |
September | 21.51 | 6.72 |
October | 18.16 | -3.1 |
November | 15.05 | -17.6 |
December | 14.56 | -19.3 |
Annual Sum or Average | 19.06 | -1.4 |
Minimum of Months | 14.56 | -19.3 |
Maximum of Months | 24.58 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | -17.6 |
February | 22.35 | -15.4 |
March | 22.77 | -10.3 |
April | 23.99 | 0.73 |
May | 25.94 | 10.60 |
June | 26.68 | 15.96 |
July | 26.70 | 16.86 |
August | 26.43 | 14.24 |
September | 25.00 | 6.72 |
October | 22.96 | -3.1 |
November | 22.25 | -17.6 |
December | 21.99 | -19.3 |
Annual Sum or Average | 24.10 | -1.4 |
Minimum of Months | 21.99 | -19.3 |
Maximum of Months | 26.70 | 16.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:44
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.121439E+12 | 73566.387 | 14-JAN-18:45 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32640.215 | 0.000 | 0.000 | 0.000 |
February | 0.108835E+12 | 73565.023 | 24-FEB-18:30 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32638.851 | 0.000 | 0.000 | 0.000 |
March | 0.119619E+12 | 73564.713 | 01-MAR-18:45 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32638.541 | 0.000 | 0.000 | 0.000 |
April | 0.115601E+12 | 70907.251 | 27-APR-17:45 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 2230.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30303.422 | 0.000 | 0.000 | 0.000 |
May | 0.121845E+12 | 75576.832 | 31-MAY-17:15 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 8831.682 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28371.977 | 0.000 | 0.000 | 0.000 |
June | 0.123480E+12 | 80190.694 | 20-JUN-17:00 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 12933.576 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28883.946 | 0.000 | 0.000 | 0.000 |
July | 0.128514E+12 | 80615.059 | 11-JUL-17:45 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 14031.920 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28209.967 | 0.000 | 0.000 | 0.000 |
August | 0.123616E+12 | 82068.523 | 11-AUG-17:00 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 12449.900 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31245.451 | 0.000 | 0.000 | 0.000 |
September | 0.113499E+12 | 69673.195 | 01-SEP-17:30 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 2467.182 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28832.841 | 0.000 | 0.000 | 0.000 |
October | 0.117709E+12 | 71259.767 | 29-OCT-17:15 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30333.595 | 0.000 | 0.000 | 0.000 |
November | 0.115925E+12 | 73424.489 | 26-NOV-18:30 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32498.317 | 0.000 | 0.000 | 0.000 |
December | 0.121681E+12 | 73563.724 | 23-DEC-18:15 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32637.552 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.143176E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.108835E+12 | 69673.195 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28209.967 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.128514E+12 | 82068.523 | 4979.953 | 26630.920 | 6762.298 | 0.000 | 14031.920 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32640.215 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:44
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.214850E+12 | 158809.237 | 29-JAN-00:15 | 158809.237 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 158809.237 |
February | 0.166101E+12 | 144966.361 | 25-FEB-00:00 | 144966.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 144966.361 |
March | 0.141739E+12 | 119739.424 | 02-MAR-04:00 | 119739.424 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 119739.424 |
April | 0.610495E+11 | 98376.325 | 02-APR-06:00 | 98376.325 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 98376.325 |
May | 0.740070E+10 | 33542.676 | 28-MAY-02:00 | 33542.676 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 33542.676 |
June | 0.521324E+08 | 2045.893 | 25-JUN-05:00 | 2045.893 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2045.893 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.907731E+09 | 15599.463 | 31-AUG-03:00 | 15599.463 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15599.463 |
September | 0.134639E+11 | 42475.158 | 30-SEP-04:00 | 42475.158 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 42475.158 |
October | 0.999746E+11 | 98557.834 | 27-OCT-03:00 | 98557.834 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 98557.834 |
November | 0.180433E+12 | 123215.672 | 29-NOV-07:00 | 123215.672 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 123215.672 |
December | 0.221382E+12 | 130487.321 | 15-DEC-11:00 | 130487.321 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 130487.321 |
Annual Sum or Average | 0.110735E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.221382E+12 | 158809.237 | 158809.237 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 158809.237 |