Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Simulation Timestamp: 2015-09-09 18:47:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1575.52 | 502.62 | 557.91 |
Net Site Energy | 1575.52 | 502.62 | 557.91 |
Total Source Energy | 4867.24 | 1552.74 | 1723.54 |
Net Source Energy | 4867.24 | 1552.74 | 1723.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 275.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 235.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 329.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1516.74 | 58.77 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 58.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 275.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 235.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 329.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 297.63 | 20.81 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 537.10 | 20.81 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 268.14 | 18.75 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.87 | 18.75 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1516.74 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1516.74 | 100.00 |
Total On-Site and Utility Electric Sources | 1516.74 | 100.00 |
Total Electricity End Uses | 1516.74 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.25 |
Time Setpoint Not Met During Occupied Cooling | 4.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3338.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Houston Bush Intercontinental TX USA TMY3 WMO#=722430 |
Weather File | Houston Bush Intercontinental TX USA TMY3 WMO#=722430 |
Latitude [deg] | 30.00 |
Longitude [deg] | -95.4 |
Elevation [m] | 29.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-16:30 | 11-FEB-04:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 73740.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 32724.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7458.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18142.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 89231.93 | 73740.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 73740.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 32724.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 3538.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 738.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7458.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18142.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 63.71 | 0.00 | 0.00 | 0.00 |
Cooling | 872.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 744.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1044.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4803.53 | 63.71 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.56 | 0.00 | 0.00 | 0.00 |
Cooling | 308.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 369.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1700.98 | 22.56 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.56 | 0.00 | 0.00 | 0.00 |
Cooling | 308.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 263.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 369.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1700.98 | 22.56 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00 | -1.60 | Wetbulb [C] | 2.80 | 0.00 |
HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 10.10 | 24.80 | Wetbulb [C] | 3.50 | 170.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.72_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 4.600 | 0.293 | 0.130 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 4.600 | 0.293 | 0.130 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 112.97 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 193.95 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.71 | 83.71 | 40.12 | |
Exterior Lighting Total | 2553.00 | 40.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4135.87 | 2964.95 | 1170.93 | 0.72 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4174.00 | 3014.33 | 1159.67 | 0.72 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8562.96 | 6630.64 | 1932.33 | 0.77 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3429.90 | 2438.80 | 991.10 | 0.71 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2639.28 | 1826.62 | 812.67 | 0.69 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2627.29 | 1817.12 | 810.17 | 0.69 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2635.73 | 1781.98 | 853.76 | 0.68 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2687.59 | 1820.67 | 866.93 | 0.68 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9801.70 | 7114.41 | 2687.28 | 0.73 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9924.36 | 7234.33 | 2690.03 | 0.73 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8481.53 | 6091.64 | 2389.89 | 0.72 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8320.35 | 5995.32 | 2325.03 | 0.72 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6436.85 | 4534.70 | 1902.15 | 0.70 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6417.69 | 4519.47 | 1898.22 | 0.70 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6468.93 | 4471.65 | 1997.28 | 0.69 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6482.44 | 4482.35 | 2000.09 | 0.69 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6450.85 | 4749.25 | 1701.61 | 0.74 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6404.44 | 4730.34 | 1674.10 | 0.74 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5806.87 | 4204.47 | 1602.40 | 0.72 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5557.04 | 4006.32 | 1550.72 | 0.72 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4508.38 | 3223.50 | 1284.88 | 0.72 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4511.11 | 3225.73 | 1285.39 | 0.72 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4736.69 | 3404.79 | 1331.90 | 0.72 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4743.96 | 3410.62 | 1333.35 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3983.0 | 3.27 | 11.17 | 11.63 | 11.11 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4017.0 | 3.26 | 11.14 | 11.59 | 11.06 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8184.0 | 3.17 | 10.82 | 11.24 | 10.59 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3305.7 | 3.28 | 11.21 | 11.67 | 11.16 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2550.1 | 3.32 | 11.33 | 11.80 | 11.35 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2538.6 | 3.32 | 11.33 | 11.81 | 11.35 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2552.0 | 3.35 | 11.43 | 11.92 | 11.51 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2601.7 | 3.35 | 11.42 | 11.91 | 11.50 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9428.4 | 3.26 | 11.11 | 11.57 | 11.02 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9542.4 | 3.25 | 11.09 | 11.55 | 10.99 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8166.7 | 3.27 | 11.16 | 11.62 | 11.10 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8009.0 | 3.27 | 11.15 | 11.60 | 11.07 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6209.1 | 3.30 | 11.25 | 11.72 | 11.23 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6190.9 | 3.30 | 11.25 | 11.72 | 11.23 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6251.0 | 3.32 | 11.33 | 11.81 | 11.36 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6263.8 | 3.32 | 11.33 | 11.81 | 11.35 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6196.6 | 3.24 | 11.05 | 11.50 | 10.93 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6150.1 | 3.23 | 11.03 | 11.48 | 10.91 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5587.0 | 3.26 | 11.12 | 11.58 | 11.04 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5348.8 | 3.27 | 11.14 | 11.60 | 11.07 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4342.9 | 3.28 | 11.18 | 11.64 | 11.13 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4345.5 | 3.28 | 11.18 | 11.64 | 11.13 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4560.5 | 3.27 | 11.16 | 11.62 | 11.09 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4567.4 | 3.27 | 11.16 | 11.62 | 11.09 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2150.32 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2142.14 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 3890.86 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2142.14 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1615.05 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1615.05 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1615.05 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1615.05 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 4192.75 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 4237.24 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 4192.75 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 4237.24 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3230.10 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3230.10 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3230.10 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3230.10 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 3124.18 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 3148.92 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 3124.18 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 3148.92 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2361.06 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2361.06 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2335.82 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2335.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.53 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 231.81 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 560.77 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 183.21 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 131.44 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 130.61 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 123.21 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 126.33 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 551.21 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 564.00 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 464.66 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 459.54 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 335.78 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 334.45 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 321.12 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 322.05 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 375.55 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 375.76 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.58 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 307.33 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.22 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 244.42 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 260.03 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 260.54 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2060.39 | 2472.47 | 0.162 | 0.194 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
G NW APARTMENT | 2117.88 | 2541.46 | 0.166 | 0.200 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.83 | 0.01519 |
OFFICE | 4876.81 | 5852.18 | 0.403 | 0.483 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 31.30 | 0.01519 |
G NE APARTMENT | 1673.69 | 2008.43 | 0.132 | 0.158 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
G N1 APARTMENT | 1200.85 | 1441.02 | 0.094 | 0.113 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.82 | 0.01519 |
G N2 APARTMENT | 1193.30 | 1431.96 | 0.094 | 0.113 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.82 | 0.01519 |
G S1 APARTMENT | 1125.67 | 1350.81 | 0.088 | 0.106 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.87 | 0.01519 |
G S2 APARTMENT | 1154.15 | 1384.98 | 0.091 | 0.109 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.87 | 0.01519 |
M SW APARTMENT | 5035.70 | 6042.84 | 0.396 | 0.475 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
M NW APARTMENT | 5152.73 | 6183.27 | 0.405 | 0.486 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.83 | 0.01519 |
M SE APARTMENT | 4244.81 | 5093.77 | 0.334 | 0.400 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 33.68 | 0.01519 |
M NE APARTMENT | 4198.02 | 5037.62 | 0.330 | 0.396 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
M N1 APARTMENT | 3067.79 | 3681.35 | 0.241 | 0.289 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.20 | 0.01519 |
M N2 APARTMENT | 3055.64 | 3666.77 | 0.240 | 0.288 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 33.20 | 0.01519 |
M S1 APARTMENT | 2933.69 | 3520.43 | 0.231 | 0.277 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.87 | 0.01519 |
M S2 APARTMENT | 2942.19 | 3530.63 | 0.231 | 0.277 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 35.87 | 0.01519 |
T SW APARTMENT | 3430.62 | 4116.74 | 0.270 | 0.324 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 34.99 | 0.01519 |
T NW APARTMENT | 3432.67 | 4119.20 | 0.270 | 0.324 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
T SE APARTMENT | 2965.02 | 3558.02 | 0.233 | 0.280 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 36.00 | 0.01519 |
T NE APARTMENT | 2807.38 | 3368.85 | 0.221 | 0.265 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.00 | 0.01519 |
T N1 APARTMENT | 2231.10 | 2677.32 | 0.175 | 0.210 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.00 | 0.01519 |
T N2 APARTMENT | 2232.92 | 2679.50 | 0.175 | 0.211 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.00 | 0.01519 |
T S1 APARTMENT | 2375.53 | 2850.63 | 0.187 | 0.224 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 36.00 | 0.01519 |
T S2 APARTMENT | 2380.22 | 2856.26 | 0.187 | 0.224 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 36.00 | 0.01519 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1179.25 | 1415.10 | 0.034 | 0.041 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G NW APARTMENT | 1194.80 | 1433.76 | 0.034 | 0.041 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
OFFICE | 2437.60 | 2925.12 | 0.068 | 0.081 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G NE APARTMENT | 1194.80 | 1433.76 | 0.034 | 0.041 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G N1 APARTMENT | 680.87 | 817.05 | 0.020 | 0.026 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G N2 APARTMENT | 680.87 | 817.05 | 0.020 | 0.026 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G S1 APARTMENT | 668.06 | 801.68 | 0.019 | 0.026 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
G S2 APARTMENT | 748.54 | 898.25 | 0.022 | 0.026 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M SW APARTMENT | 2312.28 | 2774.73 | 0.067 | 0.080 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M NW APARTMENT | 2349.90 | 2819.88 | 0.068 | 0.081 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M SE APARTMENT | 2312.28 | 2774.73 | 0.067 | 0.080 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M NE APARTMENT | 2349.90 | 2819.88 | 0.068 | 0.081 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M N1 APARTMENT | 1103.19 | 1323.83 | 0.032 | 0.052 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M N2 APARTMENT | 1103.19 | 1323.83 | 0.032 | 0.052 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M S1 APARTMENT | 1066.76 | 1280.11 | 0.031 | 0.052 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
M S2 APARTMENT | 1066.76 | 1280.11 | 0.031 | 0.052 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T SW APARTMENT | 2025.32 | 2430.38 | 0.058 | 0.070 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T NW APARTMENT | 2046.25 | 2455.50 | 0.059 | 0.071 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T SE APARTMENT | 2025.32 | 2430.38 | 0.058 | 0.070 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T NE APARTMENT | 2046.25 | 2455.50 | 0.059 | 0.071 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T N1 APARTMENT | 1379.96 | 1655.95 | 0.040 | 0.048 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T N2 APARTMENT | 1379.96 | 1655.95 | 0.040 | 0.048 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T S1 APARTMENT | 1358.61 | 1630.33 | 0.039 | 0.047 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
T S2 APARTMENT | 1358.61 | 1630.33 | 0.039 | 0.047 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -1.60 | 0.00331 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.19 | 0.19 | 0.04 | 0.04 |
SPLIT GNW | 0.20 | 0.20 | 0.04 | 0.04 |
SPLIT OFFICE | 0.48 | 0.48 | 0.08 | 0.08 |
SPLIT GNE | 0.16 | 0.16 | 0.04 | 0.04 |
SPLIT GN1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GN2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT MSW | 0.47 | 0.47 | 0.08 | 0.08 |
SPLIT MNW | 0.49 | 0.49 | 0.08 | 0.08 |
SPLIT MSE | 0.40 | 0.40 | 0.08 | 0.08 |
SPLIT MNE | 0.40 | 0.40 | 0.08 | 0.08 |
SPLIT MN1 | 0.29 | 0.29 | 0.05 | 0.05 |
SPLIT MN2 | 0.29 | 0.29 | 0.05 | 0.05 |
SPLIT MS1 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MS2 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TSW | 0.32 | 0.32 | 0.07 | 0.07 |
SPLIT TNW | 0.32 | 0.32 | 0.07 | 0.07 |
SPLIT TSE | 0.28 | 0.28 | 0.07 | 0.07 |
SPLIT TNE | 0.26 | 0.26 | 0.07 | 0.07 |
SPLIT TN1 | 0.21 | 0.21 | 0.05 | 0.05 |
SPLIT TN2 | 0.21 | 0.21 | 0.05 | 0.05 |
SPLIT TS1 | 0.22 | 0.22 | 0.05 | 0.05 |
SPLIT TS2 | 0.22 | 0.22 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 4964.25 | 6042.75 | 2762.00 |
G NW APARTMENT | 4910.00 | 6358.00 | 2903.75 |
OFFICE | 899.00 | 939.50 | 7.75 |
G NE APARTMENT | 4902.75 | 6248.75 | 2789.50 |
G N1 APARTMENT | 4810.00 | 6632.75 | 3019.50 |
G N2 APARTMENT | 4807.50 | 6631.00 | 3014.50 |
G S1 APARTMENT | 4836.00 | 6163.00 | 2744.25 |
G S2 APARTMENT | 4869.25 | 5954.00 | 2570.50 |
M SW APARTMENT | 6088.50 | 2645.75 | 879.75 |
M NW APARTMENT | 5871.00 | 3254.50 | 938.25 |
M SE APARTMENT | 6049.25 | 2677.75 | 858.00 |
M NE APARTMENT | 5833.00 | 3300.75 | 940.25 |
M N1 APARTMENT | 5865.25 | 2954.75 | 734.25 |
M N2 APARTMENT | 5862.75 | 2963.00 | 731.25 |
M S1 APARTMENT | 6105.25 | 2107.75 | 613.00 |
M S2 APARTMENT | 6101.75 | 2116.75 | 615.50 |
T SW APARTMENT | 6053.00 | 3715.50 | 1629.25 |
T NW APARTMENT | 5915.25 | 4098.00 | 1752.25 |
T SE APARTMENT | 6024.75 | 3742.00 | 1613.50 |
T NE APARTMENT | 5853.50 | 4125.25 | 1719.25 |
T N1 APARTMENT | 5789.50 | 3922.25 | 1460.00 |
T N2 APARTMENT | 5786.50 | 3927.25 | 1463.00 |
T S1 APARTMENT | 5998.75 | 3431.25 | 1383.50 |
T S2 APARTMENT | 5997.00 | 3439.25 | 1387.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 6597.75 | 6736.00 | 3338.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G NW APARTMENT | 1.50 | 0.25 | 1.50 | 0.25 |
OFFICE | 1.00 | 30.75 | 0.00 | 0.00 |
G NE APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
G N1 APARTMENT | 3.75 | 0.50 | 3.75 | 0.50 |
G N2 APARTMENT | 5.50 | 0.25 | 5.50 | 0.25 |
G S1 APARTMENT | 1.00 | 0.50 | 1.00 | 0.50 |
G S2 APARTMENT | 2.25 | 2.75 | 2.25 | 2.75 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M N2 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T SW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T NW APARTMENT | 4.00 | 0.25 | 4.00 | 0.25 |
T SE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
T NE APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T N1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 21.25 | 34.75 | 20.25 | 4.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.369 | 0.151 | 0.000 | 0.096 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.151 | 0.000 | 0.088 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.521 | 0.189 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.151 | 0.000 | 0.088 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.091 | 0.000 | 0.087 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.091 | 0.000 | 0.087 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.091 | 0.000 | 0.096 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.091 | 0.000 | 0.096 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.217 | 0.000 | 0.122 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.217 | 0.000 | 0.111 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.217 | 0.000 | 0.121 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.217 | 0.000 | 0.111 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.131 | 0.000 | 0.111 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.131 | 0.000 | 0.111 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.131 | 0.000 | 0.122 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.131 | 0.000 | 0.122 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.287 | 0.000 | 0.149 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.287 | 0.000 | 0.134 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.287 | 0.000 | 0.149 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.287 | 0.000 | 0.134 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.173 | 0.000 | 0.134 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.173 | 0.000 | 0.134 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.173 | 0.000 | 0.149 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.173 | 0.000 | 0.149 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.499 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.362 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 329.84 | 0.00 | 01-JAN-00:15 | 30404.64 | 01-JAN-08:30 |
WaterSystems:Electricity | 329.84 | 0.00 | 01-JAN-00:15 | 30404.64 | 01-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 329.84 | 0.00 | 01-JAN-00:15 | 30404.64 | 01-JAN-08:30 |
Fans:Electricity | 235.20 | 7458.16 | 01-JAN-08:15 | 7458.16 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
ElectricityPurchased:Plant | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
Cogeneration:ElectricityPurchased | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
ElectricityNet:Plant | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
Cogeneration:ElectricityNet | 1516.74 | 20570.77 | 01-JAN-03:15 | 89231.93 | 04-AUG-16:30 |
ExteriorLights:Electricity | 40.12 | 0.00 | 01-JAN-07:30 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.12 | 0.00 | 01-JAN-07:30 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 510.67 | 7458.16 | 01-JAN-08:15 | 40451.09 | 04-AUG-16:15 |
General:Fans:Electricity | 235.20 | 7458.16 | 01-JAN-08:15 | 7458.16 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 275.47 | 0.00 | 01-JAN-00:15 | 32992.93 | 04-AUG-16:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 58.77 | 0.00 | 01-JAN-12:15 | 73740.65 | 11-FEB-05:00 |
Gas:HVAC | 58.77 | 0.00 | 01-JAN-12:15 | 73740.65 | 11-FEB-05:00 |
Heating:Gas | 58.77 | 0.00 | 01-JAN-12:15 | 73740.65 | 11-FEB-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1848.83 | 1564.96 | 08-APR-10:00 | 195262.68 | 04-AUG-16:15 |
EnergyTransfer:Building | 676.94 | 1554.52 | 14-JAN-14:30 | 71756.64 | 04-AUG-16:15 |
EnergyTransfer:Zone:G SW APARTMENT | 14.87 | 0.01 | 20-FEB-03:15 | 2580.86 | 25-SEP-15:15 |
Heating:EnergyTransfer | 36.04 | 0.00 | 01-JAN-18:30 | 39736.99 | 11-FEB-04:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 1.43 | 0.00 | 01-JAN-08:00 | 1532.97 | 11-FEB-04:00 |
Cooling:EnergyTransfer | 640.89 | 0.00 | 22-JAN-07:15 | 71756.64 | 04-AUG-16:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 13.45 | 0.00 | 01-JAN-00:15 | 2580.86 | 25-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 13.45 | 0.02 | 14-JAN-22:45 | 2407.60 | 04-AUG-16:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.29 | 0.00 | 01-JAN-16:45 | 1589.92 | 11-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 11.16 | 0.00 | 01-JAN-00:15 | 2407.60 | 04-AUG-16:30 |
EnergyTransfer:Zone:OFFICE | 31.82 | 0.04 | 30-MAR-00:15 | 4888.49 | 13-AUG-10:45 |
Heating:EnergyTransfer:Zone:OFFICE | 5.92 | 0.00 | 01-JAN-00:15 | 2130.13 | 12-FEB-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 25.90 | 0.00 | 01-JAN-11:30 | 4888.49 | 13-AUG-10:45 |
EnergyTransfer:Zone:G NE APARTMENT | 13.23 | 0.01 | 11-NOV-10:15 | 1767.15 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 2.05 | 0.00 | 01-JAN-09:15 | 1550.71 | 11-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 11.17 | 0.00 | 01-JAN-00:15 | 1767.15 | 04-AUG-16:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.42 | 0.01 | 10-APR-17:00 | 1340.19 | 04-AUG-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.91 | 0.00 | 01-JAN-10:00 | 909.11 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 8.51 | 0.00 | 01-JAN-00:15 | 1340.19 | 04-AUG-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.43 | 0.01 | 18-MAY-10:30 | 1333.19 | 04-AUG-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.92 | 0.00 | 01-JAN-10:00 | 911.30 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 8.51 | 0.00 | 01-JAN-00:15 | 1333.19 | 04-AUG-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 11.27 | 0.03 | 26-MAY-05:30 | 1735.97 | 25-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 785.14 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 10.87 | 0.00 | 01-JAN-03:30 | 1735.97 | 25-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 11.92 | 0.01 | 26-MAY-05:45 | 1758.21 | 25-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.41 | 0.00 | 01-JAN-00:15 | 797.52 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 11.51 | 0.00 | 01-JAN-03:15 | 1758.21 | 25-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 51.57 | 0.24 | 15-JAN-02:15 | 6189.89 | 25-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 2562.73 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 50.97 | 0.00 | 03-JAN-04:45 | 6189.89 | 25-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 44.29 | 0.03 | 10-NOV-04:00 | 5862.47 | 04-AUG-16:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 1.53 | 0.00 | 01-JAN-00:15 | 3089.14 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 42.75 | 0.00 | 01-JAN-01:30 | 5862.47 | 04-AUG-16:30 |
EnergyTransfer:Zone:M SE APARTMENT | 51.58 | 0.09 | 06-JAN-11:30 | 5332.04 | 25-SEP-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.59 | 0.00 | 01-JAN-00:15 | 2635.52 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 50.99 | 0.00 | 03-JAN-08:00 | 5332.04 | 25-SEP-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 44.29 | 0.13 | 23-JAN-13:00 | 4573.51 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 1.44 | 0.00 | 01-JAN-00:15 | 3078.60 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 42.85 | 0.00 | 01-JAN-01:15 | 4573.51 | 04-AUG-16:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 37.50 | 0.11 | 15-FEB-16:00 | 3375.67 | 04-AUG-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 1037.66 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 37.30 | 0.00 | 01-JAN-13:00 | 3375.67 | 04-AUG-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 37.48 | 0.01 | 27-JAN-18:45 | 3364.51 | 04-AUG-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.20 | 0.00 | 01-JAN-00:15 | 1057.14 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 37.28 | 0.00 | 01-JAN-13:00 | 3364.51 | 04-AUG-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 46.21 | 0.83 | 06-FEB-04:30 | 4593.78 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 829.19 | 22-JAN-07:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 46.18 | 0.00 | 21-JAN-01:15 | 4593.78 | 31-OCT-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 46.18 | 0.21 | 10-FEB-02:00 | 4600.23 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 830.16 | 22-JAN-07:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 46.15 | 0.00 | 21-JAN-01:15 | 4600.23 | 31-OCT-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 29.27 | 0.01 | 19-MAR-19:15 | 4043.28 | 25-SEP-15:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 2.62 | 0.00 | 01-JAN-09:00 | 2745.21 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 26.65 | 0.00 | 01-JAN-00:15 | 4043.28 | 25-SEP-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 26.87 | 0.08 | 07-MAR-07:45 | 3961.35 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 3.63 | 0.00 | 01-JAN-18:30 | 2792.39 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 23.23 | 0.00 | 01-JAN-00:15 | 3961.35 | 04-AUG-16:15 |
EnergyTransfer:Zone:T SE APARTMENT | 28.89 | 0.01 | 03-DEC-21:15 | 3576.25 | 25-SEP-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 2.44 | 0.00 | 01-JAN-08:30 | 2698.44 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 26.46 | 0.00 | 01-JAN-00:15 | 3576.25 | 25-SEP-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 26.34 | 0.00 | 11-DEC-12:45 | 3204.62 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 3.32 | 0.00 | 01-JAN-09:30 | 2724.42 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 23.02 | 0.00 | 01-JAN-00:15 | 3204.62 | 04-AUG-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 21.23 | 0.11 | 19-FEB-03:45 | 2558.68 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.57 | 0.00 | 01-JAN-10:00 | 1780.35 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 19.66 | 0.00 | 01-JAN-00:15 | 2558.68 | 04-AUG-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 21.24 | 0.05 | 25-NOV-03:45 | 2549.02 | 04-AUG-16:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.58 | 0.00 | 01-JAN-10:00 | 1783.82 | 11-FEB-04:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 19.65 | 0.00 | 01-JAN-00:15 | 2549.02 | 04-AUG-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 24.30 | 0.01 | 17-FEB-21:15 | 3030.08 | 25-SEP-14:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.95 | 0.00 | 01-JAN-00:15 | 1686.21 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 23.34 | 0.00 | 01-JAN-01:30 | 3030.08 | 25-SEP-14:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 24.30 | 0.01 | 23-DEC-08:00 | 3033.48 | 25-SEP-14:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.96 | 0.00 | 01-JAN-00:15 | 1688.56 | 11-FEB-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 23.34 | 0.00 | 01-JAN-01:30 | 3033.48 | 25-SEP-14:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1171.90 | 0.00 | 06-JAN-10:30 | 123506.04 | 04-AUG-16:15 |
HeatingCoils:EnergyTransfer | 47.02 | 0.00 | 01-JAN-12:15 | 58992.52 | 11-FEB-05:00 |
CoolingCoils:EnergyTransfer | 1124.88 | 0.00 | 01-JAN-00:15 | 123506.04 | 04-AUG-16:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 1.426 | -13.445 | 0.000 | 0.000 | 3.697 | 1.087 | 12.213 | 13.574 | 0.000 | 0.725 | 0.000 | 0.000 | -4.478 | 0.000 | -2.794 | -12.004 |
G NW APARTMENT | 2.289 | -11.157 | 0.000 | 0.000 | 3.714 | 1.087 | 12.213 | 9.096 | 0.000 | 0.719 | 0.000 | 0.000 | -4.627 | 0.000 | -2.628 | -10.705 |
OFFICE | 5.925 | -25.897 | 0.000 | 0.000 | 0.518 | 26.452 | 9.482 | 12.798 | 0.000 | 0.426 | 0.000 | 0.000 | -5.055 | 0.000 | -2.308 | -22.341 |
G NE APARTMENT | 2.054 | -11.173 | 0.000 | 0.000 | 3.725 | 1.087 | 12.213 | 8.816 | 0.000 | 0.720 | 0.000 | 0.000 | -4.420 | 0.000 | -2.592 | -10.429 |
G N1 APARTMENT | 0.914 | -8.506 | 0.000 | 0.000 | 3.727 | 1.087 | 12.213 | 3.987 | 0.000 | 0.465 | 0.000 | 0.000 | -2.816 | 0.000 | -1.795 | -9.275 |
G N2 APARTMENT | 0.917 | -8.508 | 0.000 | 0.000 | 3.727 | 1.087 | 12.213 | 3.987 | 0.000 | 0.465 | 0.000 | 0.000 | -2.814 | 0.000 | -1.793 | -9.280 |
G S1 APARTMENT | 0.400 | -10.865 | 0.000 | 0.000 | 3.701 | 1.087 | 12.213 | 8.503 | 0.000 | 0.465 | 0.000 | 0.000 | -2.682 | 0.000 | -1.978 | -10.844 |
G S2 APARTMENT | 0.405 | -11.514 | 0.000 | 0.000 | 3.698 | 1.087 | 12.213 | 8.490 | 0.000 | 0.465 | 0.000 | 0.000 | -2.694 | 0.000 | -1.989 | -10.162 |
M SW APARTMENT | 0.594 | -50.971 | 0.000 | 0.000 | 3.596 | 1.087 | 12.213 | 12.990 | 0.000 | 1.026 | 28.815 | 0.000 | -5.153 | 0.000 | -4.196 | 0.000 |
M NW APARTMENT | 1.535 | -42.751 | 0.000 | 0.000 | 3.624 | 1.087 | 12.213 | 8.626 | 0.000 | 1.015 | 23.965 | 0.000 | -5.298 | 0.000 | -4.015 | -0.000 |
M SE APARTMENT | 0.589 | -50.986 | 0.000 | 0.000 | 3.603 | 1.087 | 12.213 | 12.785 | 0.000 | 1.026 | 28.900 | 0.000 | -5.039 | 0.000 | -4.177 | 0.000 |
M NE APARTMENT | 1.443 | -42.847 | 0.000 | 0.000 | 3.633 | 1.087 | 12.213 | 8.323 | 0.000 | 1.015 | 24.186 | 0.000 | -5.072 | 0.000 | -3.980 | -0.000 |
M N1 APARTMENT | 0.201 | -37.301 | 0.000 | 0.000 | 3.614 | 1.087 | 12.213 | 3.700 | 0.000 | 0.643 | 21.992 | 0.000 | -3.312 | 0.000 | -2.836 | 0.000 |
M N2 APARTMENT | 0.204 | -37.279 | 0.000 | 0.000 | 3.614 | 1.087 | 12.213 | 3.700 | 0.000 | 0.643 | 21.961 | 0.000 | -3.309 | 0.000 | -2.834 | 0.000 |
M S1 APARTMENT | 0.030 | -46.176 | 0.000 | 0.000 | 3.578 | 1.087 | 12.213 | 8.112 | 0.000 | 0.654 | 26.638 | 0.000 | -3.131 | 0.000 | -3.006 | 0.000 |
M S2 APARTMENT | 0.032 | -46.152 | 0.000 | 0.000 | 3.578 | 1.087 | 12.213 | 8.112 | 0.000 | 0.654 | 26.610 | 0.000 | -3.129 | 0.000 | -3.005 | 0.000 |
T SW APARTMENT | 2.622 | -26.649 | 0.000 | 0.000 | 3.640 | 1.087 | 12.213 | 12.688 | 0.000 | 1.358 | 3.133 | 0.000 | -4.911 | 0.000 | -5.181 | -0.000 |
T NW APARTMENT | 3.634 | -23.234 | 0.000 | 0.000 | 3.656 | 1.087 | 12.213 | 8.385 | 0.000 | 1.341 | 2.977 | 0.000 | -5.076 | 0.000 | -4.983 | -0.000 |
T SE APARTMENT | 2.440 | -26.454 | 0.000 | 0.000 | 3.647 | 1.087 | 12.213 | 12.488 | 0.000 | 1.358 | 3.193 | 0.000 | -4.807 | 0.000 | -5.164 | -0.000 |
T NE APARTMENT | 3.321 | -23.016 | 0.000 | 0.000 | 3.667 | 1.087 | 12.213 | 8.104 | 0.000 | 1.341 | 3.104 | 0.000 | -4.872 | 0.000 | -4.948 | -0.000 |
T N1 APARTMENT | 1.574 | -19.660 | 0.000 | 0.000 | 3.652 | 1.087 | 12.213 | 3.606 | 0.000 | 0.854 | 3.258 | 0.000 | -3.142 | 0.000 | -3.441 | -0.000 |
T N2 APARTMENT | 1.582 | -19.654 | 0.000 | 0.000 | 3.653 | 1.087 | 12.213 | 3.605 | 0.000 | 0.854 | 3.240 | 0.000 | -3.139 | 0.000 | -3.441 | -0.000 |
T S1 APARTMENT | 0.953 | -23.342 | 0.000 | 0.000 | 3.627 | 1.087 | 12.213 | 7.941 | 0.000 | 0.872 | 3.278 | 0.000 | -2.984 | 0.000 | -3.644 | -0.000 |
T S2 APARTMENT | 0.959 | -23.341 | 0.000 | 0.000 | 3.628 | 1.087 | 12.213 | 7.940 | 0.000 | 0.872 | 3.269 | 0.000 | -2.982 | 0.000 | -3.643 | -0.001 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.210 | 0.000 | 0.090 | 0.000 | 0.000 | -0.568 | 0.000 | -0.814 | -13.500 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.745 | 0.000 | 2.632 | 0.001 | 0.000 | -1.274 | 0.000 | -11.633 | -11.531 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.223 | 0.000 | 0.082 | 0.000 | 0.000 | -0.624 | 0.000 | -0.673 | -13.590 |
Total Facility | 36.044 | -640.878 | 0.000 | 0.000 | 84.516 | 95.189 | 296.854 | 201.536 | 0.000 | 22.779 | 228.519 | 0.000 | -97.407 | 0.000 | -93.491 | -133.663 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 25-SEP-15:15 | 0.00 | -2580.66 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2624.98 | 0.00 | 174.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -783.90 |
G NW APARTMENT | 04-AUG-16:23 | 0.00 | -2408.16 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1937.71 | 0.00 | 315.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -583.76 |
OFFICE | 10-SEP-06:01 | 0.00 | -7376.64 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 6994.50 | 0.00 | -249.43 | 0.00 | -78.88 | 0.00 |
G NE APARTMENT | 04-AUG-16:04 | 0.00 | -1769.62 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 847.73 | 0.00 | 328.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144.82 |
G N1 APARTMENT | 04-AUG-17:05 | 0.00 | -1341.64 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 517.30 | 0.00 | 167.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -161.57 |
G N2 APARTMENT | 04-AUG-17:05 | 0.00 | -1334.45 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 517.41 | 0.00 | 167.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -168.86 |
G S1 APARTMENT | 25-SEP-13:30 | 0.00 | -1735.83 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1714.09 | 0.00 | 113.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.93 |
G S2 APARTMENT | 25-SEP-13:30 | 0.00 | -1758.08 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1713.65 | 0.00 | 113.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -505.25 |
M SW APARTMENT | 25-SEP-15:15 | 0.00 | -6189.42 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2592.89 | 0.00 | 250.12 | 2781.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 04-AUG-16:23 | 0.00 | -5864.23 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1919.84 | 0.00 | 453.36 | 2752.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 25-SEP-13:30 | 0.00 | -5331.87 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2006.19 | 0.00 | 269.47 | 2619.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 04-AUG-16:04 | 0.00 | -4578.80 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 841.58 | 0.00 | 471.29 | 2527.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 04-AUG-17:05 | 0.00 | -3380.32 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 511.55 | 0.00 | 240.87 | 1809.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 04-AUG-17:05 | 0.00 | -3371.31 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 511.61 | 0.00 | 240.87 | 1800.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 31-OCT-13:30 | 0.00 | -4593.58 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1977.63 | 0.00 | 104.92 | 2074.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 31-OCT-13:30 | 0.00 | -4600.04 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1977.59 | 0.00 | 104.92 | 2081.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 25-SEP-15:15 | 0.00 | -4042.99 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2535.16 | 0.00 | 329.57 | 613.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 04-AUG-16:04 | 0.00 | -3966.42 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 1866.23 | 0.00 | 621.41 | 740.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 25-SEP-13:30 | 0.00 | -3576.14 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1961.53 | 0.00 | 354.89 | 823.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 04-AUG-16:04 | 0.00 | -3209.90 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 813.67 | 0.00 | 621.40 | 1036.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 04-AUG-16:04 | 0.00 | -2561.85 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 498.04 | 0.00 | 374.82 | 950.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 04-AUG-16:04 | 0.00 | -2552.15 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 498.16 | 0.00 | 374.82 | 940.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 25-SEP-14:00 | 0.00 | -3029.97 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1584.86 | 0.00 | 230.88 | 777.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 25-SEP-14:00 | 0.00 | -3033.37 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1584.79 | 0.00 | 230.88 | 781.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-AUG-16:04 | 0.00 | -71845.19 | 0.00 | 0.00 | 1949.54 | 3295.01 | 14142.04 | 22575.99 | 0.00 | 13070.12 | 16812.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 11-FEB-04:00 | 1532.81 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 232.76 | 0.00 | -1078.68 | 0.00 | -1106.72 | 0.00 |
G NW APARTMENT | 11-FEB-02:00 | 1589.70 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 172.77 | 0.00 | -1041.08 | 0.00 | -1158.88 | 0.00 |
OFFICE | 05-FEB-07:01 | 3618.01 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -462.75 | 0.00 | -310.73 | -3554.99 |
G NE APARTMENT | 12-OCT-06:01 | 1826.11 | 0.00 | 0.00 | 0.00 | 163.00 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -622.72 | 0.00 | -167.76 | -1623.39 |
G N1 APARTMENT | 11-FEB-04:00 | 909.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 | -668.29 | 0.00 | -668.19 | 0.00 |
G N2 APARTMENT | 11-FEB-04:00 | 911.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 | -668.21 | 0.00 | -668.19 | 0.00 |
G S1 APARTMENT | 27-DEC-08:01 | 1126.89 | 0.00 | 0.00 | 0.00 | 74.05 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -207.00 | 0.00 | -112.82 | -1289.06 |
G S2 APARTMENT | 14-JAN-07:01 | 1372.33 | 0.00 | 0.00 | 0.00 | 162.83 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -242.23 | 0.00 | -89.69 | -1628.00 |
M SW APARTMENT | 18-JAN-07:01 | 3273.20 | 0.00 | 0.00 | 0.00 | 162.56 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -679.21 | 0.00 | -583.27 | -2598.03 |
M NW APARTMENT | 11-FEB-05:00 | 3088.84 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1194.81 | 0.00 | -1504.39 | -822.44 |
M SE APARTMENT | 11-FEB-05:00 | 2635.26 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1132.29 | 0.00 | -1504.44 | -431.33 |
M NE APARTMENT | 11-FEB-04:00 | 3078.27 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1123.17 | 0.00 | -1590.67 | -784.26 |
M N1 APARTMENT | 25-JAN-08:01 | 1787.56 | 0.00 | 0.00 | 0.00 | 74.04 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -401.29 | 0.00 | -431.91 | -1436.35 |
M N2 APARTMENT | 19-JAN-08:14 | 1555.47 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -423.75 | 0.00 | -195.76 | -1417.88 |
M S1 APARTMENT | 22-JAN-07:00 | 829.17 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -467.75 | 0.00 | -492.96 | -421.39 |
M S2 APARTMENT | 22-JAN-07:00 | 830.14 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -467.74 | 0.00 | -492.96 | -422.37 |
T SW APARTMENT | 11-FEB-04:00 | 2744.92 | 0.00 | 0.00 | 0.00 | 190.07 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 24.63 | 0.00 | -1095.81 | 0.00 | -2093.96 | 0.00 |
T NW APARTMENT | 11-FEB-04:00 | 2792.10 | 0.00 | 0.00 | 0.00 | 190.59 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 | -1130.34 | 0.00 | -2085.06 | 0.00 |
T SE APARTMENT | 11-FEB-04:00 | 2698.16 | 0.00 | 0.00 | 0.00 | 190.38 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 35.46 | 0.00 | -1065.77 | 0.00 | -2088.39 | 0.00 |
T NE APARTMENT | 11-FEB-04:00 | 2724.14 | 0.00 | 0.00 | 0.00 | 191.37 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 | -1098.57 | 0.00 | -2074.86 | 0.00 |
T N1 APARTMENT | 17-DEC-07:01 | 1798.43 | 0.00 | 0.00 | 0.00 | 162.69 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.85 | 0.00 | -27.33 | -2019.71 |
T N2 APARTMENT | 17-DEC-07:01 | 1806.43 | 0.00 | 0.00 | 0.00 | 162.70 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -338.81 | 0.00 | -27.33 | -2027.76 |
T S1 APARTMENT | 11-FEB-05:00 | 1686.05 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.10 | 0.00 | -1202.05 | -243.70 |
T S2 APARTMENT | 11-FEB-05:00 | 1688.40 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -673.04 | 0.00 | -1202.05 | -246.10 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-FEB-04:00 | 39317.28 | 0.00 | 0.00 | 0.00 | 4366.71 | 1952.47 | 5387.04 | 0.00 | 0.00 | 0.00 | 2068.84 | 0.00 | -21633.16 | 0.00 | -31459.18 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Sec1.1A-General InformationData | |
Weather File | Houston Bush Intercontinental TX USA TMY3 WMO#=722430 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 20.25 |
Number of hours cooling loads not met | 4.00 |
Number of hours not met | 24.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 58.77 | 73740.65 | 0.00 | 0.00 |
Space Cooling | 275.47 | 32724.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 235.20 | 7458.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 329.84 | 18142.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1516.74 | 58.77 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1516.74 |
Natural Gas | 0.00 | 58.77 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1575.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 87.88 |
Fans-Interior | 75.03 |
Service Water Heating | 105.22 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.80 |
Subtotal | 483.87 |
Natural Gas [MJ/m2] | |
Space Heating | 18.75 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 18.75 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.52 |
Space Heating | 3.73 |
Space Cooling | 17.48 |
Fans-Interior | 14.93 |
Service Water Heating | 20.94 |
Receptacle Equipment | 32.86 |
Miscellaneous | 2.55 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.194279 |
G NW APARTMENT DIRECT AIR | 0.199694 |
OFFICE DIRECT AIR | 0.483076 |
G NE APARTMENT DIRECT AIR | 0.157823 |
G N1 APARTMENT DIRECT AIR | 0.113225 |
G N2 APARTMENT DIRECT AIR | 0.112513 |
G S1 APARTMENT DIRECT AIR | 0.106141 |
G S2 APARTMENT DIRECT AIR | 0.108826 |
M SW APARTMENT DIRECT AIR | 0.474841 |
M NW APARTMENT DIRECT AIR | 0.485857 |
M SE APARTMENT DIRECT AIR | 0.400279 |
M NE APARTMENT DIRECT AIR | 0.395868 |
M N1 APARTMENT DIRECT AIR | 0.289257 |
M N2 APARTMENT DIRECT AIR | 0.288112 |
M S1 APARTMENT DIRECT AIR | 0.276626 |
M S2 APARTMENT DIRECT AIR | 0.277427 |
T SW APARTMENT DIRECT AIR | 0.323518 |
T NW APARTMENT DIRECT AIR | 0.323698 |
T SE APARTMENT DIRECT AIR | 0.279611 |
T NE APARTMENT DIRECT AIR | 0.264744 |
T N1 APARTMENT DIRECT AIR | 0.210383 |
T N2 APARTMENT DIRECT AIR | 0.210555 |
T S1 APARTMENT DIRECT AIR | 0.224002 |
T S2 APARTMENT DIRECT AIR | 0.224444 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.194279 |
SPLIT GNW MAIN BRANCH | 0.199694 |
SPLIT OFFICE MAIN BRANCH | 0.483076 |
SPLIT GNE MAIN BRANCH | 0.157823 |
SPLIT GN1 MAIN BRANCH | 0.113225 |
SPLIT GN2 MAIN BRANCH | 0.112513 |
SPLIT GS1 MAIN BRANCH | 0.106141 |
SPLIT GS2 MAIN BRANCH | 0.108826 |
SPLIT MSW MAIN BRANCH | 0.474841 |
SPLIT MNW MAIN BRANCH | 0.485857 |
SPLIT MSE MAIN BRANCH | 0.400279 |
SPLIT MNE MAIN BRANCH | 0.395868 |
SPLIT MN1 MAIN BRANCH | 0.289257 |
SPLIT MN2 MAIN BRANCH | 0.288112 |
SPLIT MS1 MAIN BRANCH | 0.276626 |
SPLIT MS2 MAIN BRANCH | 0.277427 |
SPLIT TSW MAIN BRANCH | 0.323518 |
SPLIT TNW MAIN BRANCH | 0.323698 |
SPLIT TSE MAIN BRANCH | 0.279611 |
SPLIT TNE MAIN BRANCH | 0.264744 |
SPLIT TN1 MAIN BRANCH | 0.210383 |
SPLIT TN2 MAIN BRANCH | 0.210555 |
SPLIT TS1 MAIN BRANCH | 0.224002 |
SPLIT TS2 MAIN BRANCH | 0.224444 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.194279 |
SPLIT GNW | 0.199694 |
SPLIT OFFICE | 0.483076 |
SPLIT GNE | 0.157823 |
SPLIT GN1 | 0.113225 |
SPLIT GN2 | 0.112513 |
SPLIT GS1 | 0.106141 |
SPLIT GS2 | 0.108826 |
SPLIT MSW | 0.474841 |
SPLIT MNW | 0.485857 |
SPLIT MSE | 0.400279 |
SPLIT MNE | 0.395868 |
SPLIT MN1 | 0.289257 |
SPLIT MN2 | 0.288112 |
SPLIT MS1 | 0.276626 |
SPLIT MS2 | 0.277427 |
SPLIT TSW | 0.323518 |
SPLIT TNW | 0.323698 |
SPLIT TSE | 0.279611 |
SPLIT TNE | 0.264744 |
SPLIT TN1 | 0.210383 |
SPLIT TN2 | 0.210555 |
SPLIT TS1 | 0.224002 |
SPLIT TS2 | 0.224444 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.194279 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.199694 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.483076 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.157823 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.113225 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.112513 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.106141 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.108826 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.474841 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.485857 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.400279 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.395868 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.289257 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.288112 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.276626 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.277427 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.323518 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.323698 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.279611 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.264744 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.210383 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.210555 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.224002 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.224444 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.194279 | 4135.87 | 0.716885 |
SPLIT GNW COOLING COIL | 0.199694 | 4174.00 | 0.722169 |
SPLIT OFFICE COOLING COIL | 0.483076 | 8562.96 | 0.774339 |
SPLIT GNE COOLING COIL | 0.157823 | 3429.90 | 0.711041 |
SPLIT GN1 COOLING COIL | 0.113225 | 2639.28 | 0.692088 |
SPLIT GN2 COOLING COIL | 0.112513 | 2627.29 | 0.691632 |
SPLIT GS1 COOLING COIL | 0.106141 | 2635.73 | 0.676083 |
SPLIT GS2 COOLING COIL | 0.108826 | 2687.59 | 0.677434 |
SPLIT MSW COOLING COIL | 0.474841 | 9801.70 | 0.725835 |
SPLIT MNW COOLING COIL | 0.485857 | 9924.36 | 0.728947 |
SPLIT MSE COOLING COIL | 0.400279 | 8481.53 | 0.718224 |
SPLIT MNE COOLING COIL | 0.395868 | 8320.35 | 0.720561 |
SPLIT MN1 COOLING COIL | 0.289257 | 6436.85 | 0.704490 |
SPLIT MN2 COOLING COIL | 0.288112 | 6417.69 | 0.704221 |
SPLIT MS1 COOLING COIL | 0.276626 | 6468.93 | 0.691251 |
SPLIT MS2 COOLING COIL | 0.277427 | 6482.44 | 0.691461 |
SPLIT TSW COOLING COIL | 0.323518 | 6450.85 | 0.736220 |
SPLIT TNW COOLING COIL | 0.323698 | 6404.44 | 0.738603 |
SPLIT TSE COOLING COIL | 0.279611 | 5806.87 | 0.724051 |
SPLIT TNE COOLING COIL | 0.264744 | 5557.04 | 0.720945 |
SPLIT TN1 COOLING COIL | 0.210383 | 4508.38 | 0.715002 |
SPLIT TN2 COOLING COIL | 0.210555 | 4511.11 | 0.715062 |
SPLIT TS1 COOLING COIL | 0.224002 | 4736.69 | 0.718812 |
SPLIT TS2 COOLING COIL | 0.224444 | 4743.96 | 0.718938 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.194279 | 0.194279 | 0.194279 | 0.194279 | 2150.32 | 4135.87 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.199694 | 0.199694 | 0.199694 | 0.199694 | 2142.14 | 4174.00 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.483076 | 0.483076 | 0.483076 | 0.483076 | 3890.86 | 8562.96 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.157823 | 0.157823 | 0.157823 | 0.157823 | 2142.14 | 3429.90 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.113225 | 0.113225 | 0.113225 | 0.113225 | 1615.05 | 2639.28 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.112513 | 0.112513 | 0.112513 | 0.112513 | 1615.05 | 2627.29 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.106141 | 0.106141 | 0.106141 | 0.106141 | 1615.05 | 2635.73 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.108826 | 0.108826 | 0.108826 | 0.108826 | 1615.05 | 2687.59 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.474841 | 0.474841 | 0.474841 | 0.474841 | 4192.75 | 9801.70 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.485857 | 0.485857 | 0.485857 | 0.485857 | 4237.24 | 9924.36 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.400279 | 0.400279 | 0.400279 | 0.400279 | 4192.75 | 8481.53 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.395868 | 0.395868 | 0.395868 | 0.395868 | 4237.24 | 8320.35 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.289257 | 0.289257 | 0.289257 | 0.289257 | 3230.10 | 6436.85 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.288112 | 0.288112 | 0.288112 | 0.288112 | 3230.10 | 6417.69 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.276626 | 0.276626 | 0.276626 | 0.276626 | 3230.10 | 6468.93 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.277427 | 0.277427 | 0.277427 | 0.277427 | 3230.10 | 6482.44 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.323518 | 0.323518 | 0.323518 | 0.323518 | 3124.18 | 6450.85 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.323698 | 0.323698 | 0.323698 | 0.323698 | 3148.92 | 6404.44 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.279611 | 0.279611 | 0.279611 | 0.279611 | 3124.18 | 5806.87 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.264744 | 0.264744 | 0.264744 | 0.264744 | 3148.92 | 5557.04 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.210383 | 0.210383 | 0.210383 | 0.210383 | 2361.06 | 4508.38 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.210555 | 0.210555 | 0.210555 | 0.210555 | 2361.06 | 4511.11 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.224002 | 0.224002 | 0.224002 | 0.224002 | 2335.82 | 4736.69 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.224444 | 0.224444 | 0.224444 | 0.224444 | 2335.82 | 4743.96 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.194279 |
SPLIT GNW SUPPLY FAN | 0.199694 |
SPLIT OFFICE SUPPLY FAN | 0.483076 |
SPLIT GNE SUPPLY FAN | 0.157823 |
SPLIT GN1 SUPPLY FAN | 0.113225 |
SPLIT GN2 SUPPLY FAN | 0.112513 |
SPLIT GS1 SUPPLY FAN | 0.106141 |
SPLIT GS2 SUPPLY FAN | 0.108826 |
SPLIT MSW SUPPLY FAN | 0.474841 |
SPLIT MNW SUPPLY FAN | 0.485857 |
SPLIT MSE SUPPLY FAN | 0.400279 |
SPLIT MNE SUPPLY FAN | 0.395868 |
SPLIT MN1 SUPPLY FAN | 0.289257 |
SPLIT MN2 SUPPLY FAN | 0.288112 |
SPLIT MS1 SUPPLY FAN | 0.276626 |
SPLIT MS2 SUPPLY FAN | 0.277427 |
SPLIT TSW SUPPLY FAN | 0.323518 |
SPLIT TNW SUPPLY FAN | 0.323698 |
SPLIT TSE SUPPLY FAN | 0.279611 |
SPLIT TNE SUPPLY FAN | 0.264744 |
SPLIT TN1 SUPPLY FAN | 0.210383 |
SPLIT TN2 SUPPLY FAN | 0.210555 |
SPLIT TS1 SUPPLY FAN | 0.224002 |
SPLIT TS2 SUPPLY FAN | 0.224444 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2150.32 |
SPLIT GNW HEATING COIL | 2142.14 |
SPLIT OFFICE HEATING COIL | 3890.86 |
SPLIT GNE HEATING COIL | 2142.14 |
SPLIT GN1 HEATING COIL | 1615.05 |
SPLIT GN2 HEATING COIL | 1615.05 |
SPLIT GS1 HEATING COIL | 1615.05 |
SPLIT GS2 HEATING COIL | 1615.05 |
SPLIT MSW HEATING COIL | 4192.75 |
SPLIT MNW HEATING COIL | 4237.24 |
SPLIT MSE HEATING COIL | 4192.75 |
SPLIT MNE HEATING COIL | 4237.24 |
SPLIT MN1 HEATING COIL | 3230.10 |
SPLIT MN2 HEATING COIL | 3230.10 |
SPLIT MS1 HEATING COIL | 3230.10 |
SPLIT MS2 HEATING COIL | 3230.10 |
SPLIT TSW HEATING COIL | 3124.18 |
SPLIT TNW HEATING COIL | 3148.92 |
SPLIT TSE HEATING COIL | 3124.18 |
SPLIT TNE HEATING COIL | 3148.92 |
SPLIT TN1 HEATING COIL | 2361.06 |
SPLIT TN2 HEATING COIL | 2361.06 |
SPLIT TS1 HEATING COIL | 2335.82 |
SPLIT TS2 HEATING COIL | 2335.82 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 10.50 |
February | 22.68 | 12.77 |
March | 23.12 | 16.20 |
April | 23.82 | 20.49 |
May | 24.28 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 23.96 | 20.33 |
November | 23.51 | 17.10 |
December | 22.67 | 12.54 |
Annual Sum or Average | 23.66 | 20.36 |
Minimum of Months | 22.28 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 10.50 |
February | 22.47 | 12.77 |
March | 22.95 | 16.20 |
April | 23.78 | 20.49 |
May | 24.29 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 23.84 | 20.33 |
November | 23.22 | 17.10 |
December | 22.33 | 12.54 |
Annual Sum or Average | 23.54 | 20.36 |
Minimum of Months | 21.99 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 10.50 |
February | 23.20 | 12.77 |
March | 23.96 | 16.20 |
April | 25.00 | 20.49 |
May | 25.80 | 24.03 |
June | 26.92 | 27.02 |
July | 27.27 | 28.27 |
August | 27.07 | 28.21 |
September | 27.15 | 26.44 |
October | 25.37 | 20.33 |
November | 24.49 | 17.10 |
December | 23.17 | 12.54 |
Annual Sum or Average | 25.18 | 20.36 |
Minimum of Months | 22.63 | 10.50 |
Maximum of Months | 27.27 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 10.50 |
February | 22.39 | 12.77 |
March | 22.87 | 16.20 |
April | 23.73 | 20.49 |
May | 24.28 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 23.82 | 20.33 |
November | 23.15 | 17.10 |
December | 22.23 | 12.54 |
Annual Sum or Average | 23.50 | 20.36 |
Minimum of Months | 21.92 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 10.50 |
February | 22.34 | 12.77 |
March | 22.78 | 16.20 |
April | 23.66 | 20.49 |
May | 24.25 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 23.78 | 20.33 |
November | 23.10 | 17.10 |
December | 22.21 | 12.54 |
Annual Sum or Average | 23.47 | 20.36 |
Minimum of Months | 21.91 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 10.50 |
February | 22.33 | 12.77 |
March | 22.78 | 16.20 |
April | 23.66 | 20.49 |
May | 24.25 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 23.77 | 20.33 |
November | 23.09 | 17.10 |
December | 22.21 | 12.54 |
Annual Sum or Average | 23.47 | 20.36 |
Minimum of Months | 21.91 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 10.50 |
February | 22.63 | 12.77 |
March | 23.06 | 16.20 |
April | 23.74 | 20.49 |
May | 24.25 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 23.95 | 20.33 |
November | 23.51 | 17.10 |
December | 22.66 | 12.54 |
Annual Sum or Average | 23.64 | 20.36 |
Minimum of Months | 22.27 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.29 | 10.50 |
February | 22.65 | 12.77 |
March | 23.08 | 16.20 |
April | 23.77 | 20.49 |
May | 24.26 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 23.98 | 20.33 |
November | 23.53 | 17.10 |
December | 22.67 | 12.54 |
Annual Sum or Average | 23.66 | 20.36 |
Minimum of Months | 22.29 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.10 | 10.50 |
February | 23.41 | 12.77 |
March | 23.99 | 16.20 |
April | 24.35 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.36 | 20.33 |
November | 24.17 | 17.10 |
December | 23.53 | 12.54 |
Annual Sum or Average | 24.08 | 20.36 |
Minimum of Months | 23.10 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 10.50 |
February | 23.13 | 12.77 |
March | 23.80 | 16.20 |
April | 24.34 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.32 | 20.33 |
November | 23.97 | 17.10 |
December | 23.07 | 12.54 |
Annual Sum or Average | 23.93 | 20.36 |
Minimum of Months | 22.54 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 10.50 |
February | 23.35 | 12.77 |
March | 23.96 | 16.20 |
April | 24.35 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.35 | 20.33 |
November | 24.14 | 17.10 |
December | 23.48 | 12.54 |
Annual Sum or Average | 24.06 | 20.36 |
Minimum of Months | 23.01 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 10.50 |
February | 23.04 | 12.77 |
March | 23.76 | 16.20 |
April | 24.33 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.32 | 20.33 |
November | 23.93 | 17.10 |
December | 22.95 | 12.54 |
Annual Sum or Average | 23.90 | 20.36 |
Minimum of Months | 22.41 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.62 | 10.50 |
February | 23.17 | 12.77 |
March | 23.90 | 16.20 |
April | 24.36 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.34 | 20.33 |
November | 24.09 | 17.10 |
December | 23.17 | 12.54 |
Annual Sum or Average | 23.97 | 20.36 |
Minimum of Months | 22.62 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 10.50 |
February | 23.16 | 12.77 |
March | 23.90 | 16.20 |
April | 24.36 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.34 | 20.33 |
November | 24.08 | 17.10 |
December | 23.16 | 12.54 |
Annual Sum or Average | 23.97 | 20.36 |
Minimum of Months | 22.61 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 10.50 |
February | 23.54 | 12.77 |
March | 24.13 | 16.20 |
April | 24.37 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.38 | 20.33 |
November | 24.27 | 17.10 |
December | 23.75 | 12.54 |
Annual Sum or Average | 24.16 | 20.36 |
Minimum of Months | 23.39 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 10.50 |
February | 23.53 | 12.77 |
March | 24.13 | 16.20 |
April | 24.37 | 20.49 |
May | 24.40 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.38 | 20.33 |
November | 24.27 | 17.10 |
December | 23.75 | 12.54 |
Annual Sum or Average | 24.15 | 20.36 |
Minimum of Months | 23.39 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.73 | 10.50 |
February | 23.19 | 12.77 |
March | 23.57 | 16.20 |
April | 24.19 | 20.49 |
May | 24.38 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.18 | 20.33 |
November | 23.81 | 17.10 |
December | 23.11 | 12.54 |
Annual Sum or Average | 23.90 | 20.36 |
Minimum of Months | 22.73 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 10.50 |
February | 23.00 | 12.77 |
March | 23.45 | 16.20 |
April | 24.16 | 20.49 |
May | 24.38 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 24.11 | 20.33 |
November | 23.62 | 17.10 |
December | 22.80 | 12.54 |
Annual Sum or Average | 23.80 | 20.36 |
Minimum of Months | 22.41 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.66 | 10.50 |
February | 23.13 | 12.77 |
March | 23.54 | 16.20 |
April | 24.18 | 20.49 |
May | 24.38 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 24.16 | 20.33 |
November | 23.79 | 17.10 |
December | 23.06 | 12.54 |
Annual Sum or Average | 23.88 | 20.36 |
Minimum of Months | 22.66 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.29 | 10.50 |
February | 22.91 | 12.77 |
March | 23.40 | 16.20 |
April | 24.15 | 20.49 |
May | 24.38 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 24.09 | 20.33 |
November | 23.58 | 17.10 |
December | 22.67 | 12.54 |
Annual Sum or Average | 23.76 | 20.36 |
Minimum of Months | 22.29 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.42 | 10.50 |
February | 23.00 | 12.77 |
March | 23.48 | 16.20 |
April | 24.19 | 20.49 |
May | 24.39 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 24.13 | 20.33 |
November | 23.65 | 17.10 |
December | 22.79 | 12.54 |
Annual Sum or Average | 23.81 | 20.36 |
Minimum of Months | 22.42 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 10.50 |
February | 22.99 | 12.77 |
March | 23.48 | 16.20 |
April | 24.19 | 20.49 |
May | 24.39 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.39 | 26.44 |
October | 24.12 | 20.33 |
November | 23.65 | 17.10 |
December | 22.78 | 12.54 |
Annual Sum or Average | 23.80 | 20.36 |
Minimum of Months | 22.41 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 10.50 |
February | 23.26 | 12.77 |
March | 23.67 | 16.20 |
April | 24.23 | 20.49 |
May | 24.39 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.21 | 20.33 |
November | 23.90 | 17.10 |
December | 23.23 | 12.54 |
Annual Sum or Average | 23.95 | 20.36 |
Minimum of Months | 22.88 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 10.50 |
February | 23.26 | 12.77 |
March | 23.67 | 16.20 |
April | 24.23 | 20.49 |
May | 24.39 | 24.03 |
June | 24.40 | 27.02 |
July | 24.40 | 28.27 |
August | 24.40 | 28.21 |
September | 24.40 | 26.44 |
October | 24.21 | 20.33 |
November | 23.90 | 17.10 |
December | 23.23 | 12.54 |
Annual Sum or Average | 23.95 | 20.36 |
Minimum of Months | 22.87 | 10.50 |
Maximum of Months | 24.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.08 | 10.50 |
February | 23.90 | 12.77 |
March | 24.86 | 16.20 |
April | 26.05 | 20.49 |
May | 26.72 | 24.03 |
June | 27.07 | 27.02 |
July | 27.21 | 28.27 |
August | 27.20 | 28.21 |
September | 26.93 | 26.44 |
October | 25.94 | 20.33 |
November | 25.12 | 17.10 |
December | 23.69 | 12.54 |
Annual Sum or Average | 25.65 | 20.36 |
Minimum of Months | 23.08 | 10.50 |
Maximum of Months | 27.21 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 10.50 |
February | 21.76 | 12.77 |
March | 22.82 | 16.20 |
April | 24.14 | 20.49 |
May | 25.21 | 24.03 |
June | 26.78 | 27.02 |
July | 27.20 | 28.27 |
August | 27.20 | 28.21 |
September | 26.88 | 26.44 |
October | 24.55 | 20.33 |
November | 23.34 | 17.10 |
December | 21.74 | 12.54 |
Annual Sum or Average | 24.40 | 20.36 |
Minimum of Months | 21.06 | 10.50 |
Maximum of Months | 27.20 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:59
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.40 | 10.50 |
February | 24.95 | 12.77 |
March | 25.82 | 16.20 |
April | 26.44 | 20.49 |
May | 26.71 | 24.03 |
June | 26.87 | 27.02 |
July | 26.95 | 28.27 |
August | 26.92 | 28.21 |
September | 26.86 | 26.44 |
October | 26.50 | 20.33 |
November | 26.08 | 17.10 |
December | 25.03 | 12.54 |
Annual Sum or Average | 26.13 | 20.36 |
Minimum of Months | 24.40 | 10.50 |
Maximum of Months | 26.95 | 28.27 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:59
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.111144E+12 | 67095.477 | 29-JAN-18:30 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 6081.360 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19392.085 | 0.000 | 0.000 | 0.000 |
February | 0.103031E+12 | 70613.752 | 20-FEB-18:45 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 8229.468 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20762.252 | 0.000 | 0.000 | 0.000 |
March | 0.116819E+12 | 76430.720 | 25-MAR-17:00 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 15338.123 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22023.565 | 0.000 | 0.000 | 0.000 |
April | 0.120568E+12 | 76362.300 | 29-APR-17:30 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 19039.471 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18253.797 | 0.000 | 0.000 | 0.000 |
May | 0.133896E+12 | 83167.595 | 24-MAY-17:15 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 23756.175 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20342.387 | 0.000 | 0.000 | 0.000 |
June | 0.140555E+12 | 86985.040 | 24-JUN-17:30 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 25802.448 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22113.559 | 0.000 | 0.000 | 0.000 |
July | 0.149146E+12 | 87017.264 | 14-JUL-17:30 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 26872.136 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21076.095 | 0.000 | 0.000 | 0.000 |
August | 0.148912E+12 | 89231.929 | 04-AUG-16:30 | 4276.255 | 26630.920 | 7458.159 | 0.000 | 32724.583 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18142.011 | 0.000 | 0.000 | 0.000 |
September | 0.139144E+12 | 85763.930 | 22-SEP-16:15 | 4276.255 | 26630.920 | 7458.159 | 0.000 | 27101.560 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20297.036 | 0.000 | 0.000 | 0.000 |
October | 0.125119E+12 | 82407.790 | 01-OCT-17:15 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 22366.013 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20972.745 | 0.000 | 0.000 | 0.000 |
November | 0.115601E+12 | 76164.412 | 27-NOV-18:45 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 14571.836 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19970.543 | 0.000 | 0.000 | 0.000 |
December | 0.112809E+12 | 70052.012 | 07-DEC-18:30 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 8247.299 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20182.681 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.151674E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.103031E+12 | 67095.477 | 4276.255 | 26630.920 | 7458.159 | 0.000 | 6081.360 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18142.011 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.149146E+12 | 89231.929 | 4979.953 | 26630.920 | 7458.159 | 0.000 | 32724.583 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22113.559 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:59
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.215459E+11 | 53279.528 | 22-JAN-06:00 | 53279.528 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 53279.528 |
February | 0.167057E+11 | 73740.646 | 11-FEB-04:00 | 73740.646 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 73740.646 |
March | 0.417096E+10 | 34041.597 | 19-MAR-06:15 | 34041.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 34041.597 |
April | 0.241623E+09 | 8488.803 | 07-APR-04:00 | 8488.803 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8488.803 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.275167E+09 | 7571.075 | 13-OCT-05:00 | 7571.075 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7571.075 |
November | 0.247625E+10 | 21890.791 | 30-NOV-05:00 | 21890.791 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21890.791 |
December | 0.133565E+11 | 43581.905 | 21-DEC-05:00 | 43581.905 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 43581.905 |
Annual Sum or Average | 0.587720E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.215459E+11 | 73740.646 | 73740.646 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 73740.646 |