Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Burlington International Ap VT USA TMY3 WMO#=726170
Simulation Timestamp: 2015-09-09 18:47:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2060.40 | 657.31 | 729.61 |
Net Site Energy | 2060.40 | 657.31 | 729.61 |
Total Source Energy | 5145.14 | 1641.39 | 1821.95 |
Net Source Energy | 5145.14 | 1641.39 | 1821.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 662.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 76.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 431.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1397.82 | 662.58 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 662.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 76.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 213.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 431.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 255.54 | 234.63 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 494.98 | 234.63 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 230.21 | 211.37 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 445.93 | 211.37 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1397.82 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1397.82 | 100.00 |
Total On-Site and Utility Electric Sources | 1397.82 | 100.00 |
Total Electricity End Uses | 1397.82 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 41.50 |
Time Setpoint Not Met During Occupied Cooling | 4.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3528.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Burlington International Ap VT USA TMY3 WMO#=726170 |
Weather File | Burlington International Ap VT USA TMY3 WMO#=726170 |
Latitude [deg] | 44.47 |
Longitude [deg] | -73.2 |
Elevation [m] | 101.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-17:00 | 27-JAN-06:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 133750.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25971.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6760.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23590.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87933.02 | 133750.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 133750.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 25971.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6760.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 23590.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 718.24 | 0.00 | 0.00 | 0.00 |
Cooling | 242.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 675.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1367.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4426.90 | 718.24 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 254.33 | 0.00 | 0.00 | 0.00 |
Cooling | 85.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 239.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 484.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1567.61 | 254.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 254.33 | 0.00 | 0.00 | 0.00 |
Cooling | 85.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 239.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 484.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1567.61 | 254.33 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00 | -22.40 | Wetbulb [C] | 3.00 | 60.00 |
BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 10.70 | 21.70 | Wetbulb [C] | 4.50 | 170.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.63 | 83.63 | 40.08 | |
Exterior Lighting Total | 2553.00 | 40.08 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3028.38 | 2249.93 | 778.45 | 0.74 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2802.54 | 2088.19 | 714.35 | 0.75 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7733.97 | 6176.78 | 1557.19 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2101.91 | 1531.19 | 570.72 | 0.73 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1720.68 | 1236.84 | 483.84 | 0.72 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1704.02 | 1223.42 | 480.60 | 0.72 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2170.39 | 1559.46 | 610.93 | 0.72 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2216.37 | 1598.54 | 617.83 | 0.72 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8180.55 | 6218.11 | 1962.44 | 0.76 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7602.89 | 5769.12 | 1833.77 | 0.76 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7707.98 | 5780.76 | 1927.22 | 0.75 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6045.70 | 4534.82 | 1510.89 | 0.75 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4842.64 | 3593.24 | 1249.40 | 0.74 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4814.15 | 3570.00 | 1244.14 | 0.74 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6024.82 | 4462.93 | 1561.89 | 0.74 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6042.44 | 4477.36 | 1565.08 | 0.74 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5554.63 | 4252.11 | 1302.52 | 0.77 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4986.66 | 3809.79 | 1176.87 | 0.76 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5210.40 | 3969.18 | 1241.22 | 0.76 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4260.45 | 3189.23 | 1071.22 | 0.75 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3417.11 | 2541.99 | 875.12 | 0.74 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3418.88 | 2543.31 | 875.56 | 0.74 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4330.78 | 3289.83 | 1040.95 | 0.76 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4342.08 | 3299.12 | 1042.96 | 0.76 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2906.4 | 3.23 | 11.01 | 11.45 | 10.87 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2688.9 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7367.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2021.1 | 3.25 | 11.10 | 11.55 | 11.00 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1656.7 | 3.27 | 11.16 | 11.62 | 11.09 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1640.8 | 3.27 | 11.16 | 11.62 | 11.10 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2089.7 | 3.27 | 11.16 | 11.62 | 11.09 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2133.2 | 3.27 | 11.14 | 11.60 | 11.07 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7833.3 | 3.19 | 10.90 | 11.34 | 10.71 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7281.4 | 3.20 | 10.91 | 11.35 | 10.72 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7390.7 | 3.21 | 10.96 | 11.41 | 10.80 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5796.8 | 3.21 | 10.96 | 11.40 | 10.80 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4648.2 | 3.23 | 11.01 | 11.46 | 10.87 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4621.2 | 3.23 | 11.01 | 11.46 | 10.88 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5783.9 | 3.23 | 11.02 | 11.47 | 10.89 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5800.7 | 3.23 | 11.02 | 11.47 | 10.88 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5315.1 | 3.19 | 10.87 | 11.30 | 10.66 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4772.5 | 3.19 | 10.88 | 11.31 | 10.68 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4988.1 | 3.19 | 10.89 | 11.33 | 10.70 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4085.9 | 3.22 | 10.97 | 11.41 | 10.81 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3279.1 | 3.22 | 11.00 | 11.45 | 10.86 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3280.8 | 3.22 | 11.00 | 11.45 | 10.86 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4147.2 | 3.20 | 10.90 | 11.34 | 10.72 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4158.0 | 3.20 | 10.90 | 11.34 | 10.71 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 3969.55 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 3939.34 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 6758.44 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 3949.77 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 3038.82 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 3039.06 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 3022.61 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 3157.36 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 7653.02 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 7697.97 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 7680.34 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 7725.31 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 5436.16 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 5436.81 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 5393.69 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 5394.34 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 5631.73 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 5657.45 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 5646.20 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 5671.92 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 4418.61 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 4418.97 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 4391.11 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 4391.48 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.19 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 167.91 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 542.35 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 119.26 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 94.46 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 93.27 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 119.03 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 122.70 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 513.53 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 475.38 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 468.95 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 367.96 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 287.27 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 285.18 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 355.96 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 357.27 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 354.41 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 316.73 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 328.74 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 258.07 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 203.94 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 204.05 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 271.47 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 272.32 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1632.20 | 1958.64 | 0.129 | 0.155 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 30.02 | 0.01255 |
G NW APARTMENT | 1520.99 | 1825.19 | 0.121 | 0.145 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.73 | 0.01255 |
OFFICE | 4810.79 | 5772.95 | 0.389 | 0.467 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.41 | 0.01255 |
G NE APARTMENT | 1080.26 | 1296.32 | 0.086 | 0.103 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
G N1 APARTMENT | 855.68 | 1026.82 | 0.068 | 0.081 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
G N2 APARTMENT | 844.89 | 1013.87 | 0.067 | 0.080 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
G S1 APARTMENT | 1078.18 | 1293.81 | 0.085 | 0.103 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
G S2 APARTMENT | 1111.47 | 1333.76 | 0.088 | 0.106 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
M SW APARTMENT | 4651.61 | 5581.93 | 0.369 | 0.442 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
M NW APARTMENT | 4306.15 | 5167.38 | 0.341 | 0.410 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.73 | 0.01255 |
M SE APARTMENT | 4247.76 | 5097.32 | 0.337 | 0.404 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 30.90 | 0.01255 |
M NE APARTMENT | 3332.90 | 3999.49 | 0.264 | 0.317 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
M N1 APARTMENT | 2602.23 | 3122.68 | 0.206 | 0.247 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
M N2 APARTMENT | 2583.31 | 3099.97 | 0.205 | 0.246 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.53 | 0.01255 |
M S1 APARTMENT | 3224.44 | 3869.33 | 0.256 | 0.307 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
M S2 APARTMENT | 3236.25 | 3883.50 | 0.256 | 0.308 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
T SW APARTMENT | 3210.04 | 3852.05 | 0.254 | 0.305 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.98 | 0.01255 |
T NW APARTMENT | 2868.79 | 3442.55 | 0.227 | 0.273 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 30.02 | 0.01255 |
T SE APARTMENT | 2977.56 | 3573.07 | 0.236 | 0.283 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.03 | 0.01255 |
T NE APARTMENT | 2337.44 | 2804.92 | 0.185 | 0.222 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 31.30 | 0.01255 |
T N1 APARTMENT | 1847.31 | 2216.78 | 0.146 | 0.176 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.30 | 0.01255 |
T N2 APARTMENT | 1848.28 | 2217.94 | 0.146 | 0.176 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.30 | 0.01255 |
T S1 APARTMENT | 2459.01 | 2950.81 | 0.195 | 0.234 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.17 | 0.01255 |
T S2 APARTMENT | 2466.65 | 2959.98 | 0.195 | 0.235 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.17 | 0.01255 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2157.40 | 2588.88 | 0.063 | 0.075 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G NW APARTMENT | 2174.01 | 2608.82 | 0.063 | 0.076 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
OFFICE | 4066.11 | 4879.33 | 0.115 | 0.138 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G NE APARTMENT | 2182.83 | 2619.39 | 0.064 | 0.076 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G N1 APARTMENT | 1412.48 | 1694.97 | 0.041 | 0.049 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G N2 APARTMENT | 1412.68 | 1695.21 | 0.041 | 0.049 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G S1 APARTMENT | 1398.76 | 1678.52 | 0.041 | 0.049 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
G S2 APARTMENT | 1512.72 | 1815.26 | 0.044 | 0.053 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
M SW APARTMENT | 4157.35 | 4988.82 | 0.121 | 0.145 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M NW APARTMENT | 4195.37 | 5034.44 | 0.122 | 0.147 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M SE APARTMENT | 4180.46 | 5016.55 | 0.122 | 0.146 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M NE APARTMENT | 4218.49 | 5062.18 | 0.123 | 0.147 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M N1 APARTMENT | 2282.57 | 2739.09 | 0.066 | 0.080 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M N2 APARTMENT | 2283.13 | 2739.76 | 0.066 | 0.080 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M S1 APARTMENT | 2246.66 | 2696.00 | 0.065 | 0.079 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
M S2 APARTMENT | 2247.22 | 2696.66 | 0.065 | 0.079 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T SW APARTMENT | 3605.30 | 4326.36 | 0.105 | 0.126 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T NW APARTMENT | 3627.05 | 4352.46 | 0.106 | 0.127 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T SE APARTMENT | 3617.54 | 4341.05 | 0.105 | 0.126 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T NE APARTMENT | 3639.29 | 4367.15 | 0.106 | 0.127 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T N1 APARTMENT | 2579.37 | 3095.24 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T N2 APARTMENT | 2579.68 | 3095.61 | 0.075 | 0.090 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T S1 APARTMENT | 2556.12 | 3067.34 | 0.074 | 0.089 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
T S2 APARTMENT | 2556.43 | 3067.71 | 0.074 | 0.089 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -22.40 | 0.00051 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.16 | 0.16 | 0.08 | 0.08 |
SPLIT GNW | 0.14 | 0.14 | 0.08 | 0.08 |
SPLIT OFFICE | 0.47 | 0.47 | 0.14 | 0.14 |
SPLIT GNE | 0.10 | 0.10 | 0.08 | 0.08 |
SPLIT GN1 | 0.08 | 0.08 | 0.05 | 0.05 |
SPLIT GN2 | 0.08 | 0.08 | 0.05 | 0.05 |
SPLIT GS1 | 0.10 | 0.10 | 0.05 | 0.05 |
SPLIT GS2 | 0.11 | 0.11 | 0.05 | 0.05 |
SPLIT MSW | 0.44 | 0.44 | 0.15 | 0.15 |
SPLIT MNW | 0.41 | 0.41 | 0.15 | 0.15 |
SPLIT MSE | 0.40 | 0.40 | 0.15 | 0.15 |
SPLIT MNE | 0.32 | 0.32 | 0.15 | 0.15 |
SPLIT MN1 | 0.25 | 0.25 | 0.08 | 0.08 |
SPLIT MN2 | 0.25 | 0.25 | 0.08 | 0.08 |
SPLIT MS1 | 0.31 | 0.31 | 0.08 | 0.08 |
SPLIT MS2 | 0.31 | 0.31 | 0.08 | 0.08 |
SPLIT TSW | 0.31 | 0.31 | 0.13 | 0.13 |
SPLIT TNW | 0.27 | 0.27 | 0.13 | 0.13 |
SPLIT TSE | 0.28 | 0.28 | 0.13 | 0.13 |
SPLIT TNE | 0.22 | 0.22 | 0.13 | 0.13 |
SPLIT TN1 | 0.18 | 0.18 | 0.09 | 0.09 |
SPLIT TN2 | 0.18 | 0.18 | 0.09 | 0.09 |
SPLIT TS1 | 0.23 | 0.23 | 0.09 | 0.09 |
SPLIT TS2 | 0.23 | 0.23 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3848.00 | 6682.25 | 2445.75 |
G NW APARTMENT | 4222.50 | 6870.50 | 2988.75 |
OFFICE | 792.75 | 1551.75 | 418.00 |
G NE APARTMENT | 4208.50 | 6900.75 | 2991.00 |
G N1 APARTMENT | 3588.00 | 7024.25 | 2587.75 |
G N2 APARTMENT | 3589.00 | 7021.00 | 2588.00 |
G S1 APARTMENT | 3062.75 | 6697.50 | 1818.00 |
G S2 APARTMENT | 3323.75 | 6620.00 | 2002.25 |
M SW APARTMENT | 3215.00 | 5118.25 | 750.75 |
M NW APARTMENT | 3686.75 | 5546.50 | 1401.25 |
M SE APARTMENT | 3221.00 | 5128.75 | 725.50 |
M NE APARTMENT | 3668.00 | 5577.75 | 1396.00 |
M N1 APARTMENT | 2863.00 | 5478.25 | 686.00 |
M N2 APARTMENT | 2862.50 | 5480.50 | 685.00 |
M S1 APARTMENT | 2639.25 | 4896.00 | 212.75 |
M S2 APARTMENT | 2637.25 | 4897.50 | 214.00 |
T SW APARTMENT | 4778.25 | 5814.00 | 2585.25 |
T NW APARTMENT | 5118.75 | 6104.25 | 3097.50 |
T SE APARTMENT | 4800.50 | 5809.50 | 2574.00 |
T NE APARTMENT | 5118.00 | 6098.25 | 3091.75 |
T N1 APARTMENT | 4730.25 | 6098.00 | 2758.75 |
T N2 APARTMENT | 4727.50 | 6095.00 | 2758.25 |
T S1 APARTMENT | 4344.50 | 5718.25 | 2168.50 |
T S2 APARTMENT | 4348.50 | 5716.50 | 2170.50 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5968.00 | 7094.00 | 3528.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.00 | 3.00 | 3.00 | 3.00 |
G NW APARTMENT | 3.25 | 2.50 | 3.25 | 2.50 |
OFFICE | 17.50 | 6.75 | 0.50 | 0.00 |
G NE APARTMENT | 6.50 | 4.75 | 6.50 | 4.75 |
G N1 APARTMENT | 3.50 | 3.50 | 3.50 | 3.50 |
G N2 APARTMENT | 3.50 | 3.75 | 3.50 | 3.75 |
G S1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
G S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
M SW APARTMENT | 2.50 | 2.25 | 2.50 | 2.25 |
M NW APARTMENT | 1.25 | 2.00 | 1.25 | 2.00 |
M SE APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M NE APARTMENT | 1.50 | 3.75 | 1.50 | 3.75 |
M N1 APARTMENT | 0.50 | 2.75 | 0.50 | 2.75 |
M N2 APARTMENT | 1.00 | 2.75 | 1.00 | 2.75 |
M S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
M S2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T SW APARTMENT | 0.25 | 0.75 | 0.25 | 0.75 |
T NW APARTMENT | 0.00 | 2.50 | 0.00 | 2.50 |
T SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T NE APARTMENT | 0.75 | 3.25 | 0.75 | 3.25 |
T N1 APARTMENT | 2.25 | 3.25 | 2.25 | 3.25 |
T N2 APARTMENT | 2.50 | 3.00 | 2.50 | 3.00 |
T S1 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
T S2 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 58.50 | 11.50 | 41.50 | 4.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.192 | 0.000 | 0.076 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.192 | 0.000 | 0.067 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.219 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.192 | 0.000 | 0.067 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.116 | 0.000 | 0.066 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.116 | 0.000 | 0.066 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.116 | 0.000 | 0.076 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.116 | 0.000 | 0.076 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.276 | 0.000 | 0.095 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.276 | 0.000 | 0.081 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.276 | 0.000 | 0.095 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.276 | 0.000 | 0.081 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.167 | 0.000 | 0.081 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.167 | 0.000 | 0.081 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.167 | 0.000 | 0.095 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.167 | 0.000 | 0.095 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.365 | 0.000 | 0.114 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.365 | 0.000 | 0.095 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.365 | 0.000 | 0.114 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.365 | 0.000 | 0.095 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.095 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.095 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.114 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.114 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.499 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.361 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 431.90 | 0.00 | 01-JAN-00:15 | 32852.25 | 21-FEB-08:00 |
WaterSystems:Electricity | 431.90 | 0.00 | 01-JAN-00:15 | 32852.25 | 21-FEB-08:00 |
Water Heater:WaterSystems:Electricity | 431.90 | 0.00 | 01-JAN-00:15 | 32852.25 | 21-FEB-08:00 |
Fans:Electricity | 213.20 | 6760.37 | 02-JAN-18:15 | 6760.37 | 01-JAN-18:30 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
ElectricityPurchased:Plant | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
Cogeneration:ElectricityPurchased | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
ElectricityNet:Plant | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
Cogeneration:ElectricityNet | 1397.82 | 19872.99 | 01-JAN-03:15 | 87933.02 | 20-JUL-18:00 |
ExteriorLights:Electricity | 40.08 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.08 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 289.73 | 6760.37 | 02-JAN-18:15 | 35363.23 | 20-JUL-16:00 |
General:Fans:Electricity | 213.20 | 6760.37 | 02-JAN-18:15 | 6760.37 | 01-JAN-18:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 76.53 | 0.00 | 01-JAN-00:15 | 28602.86 | 20-JUL-16:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 662.58 | 0.00 | 28-MAR-16:15 | 133750.90 | 27-JAN-07:00 |
Gas:HVAC | 662.58 | 0.00 | 28-MAR-16:15 | 133750.90 | 27-JAN-07:00 |
Heating:Gas | 662.58 | 0.00 | 28-MAR-16:15 | 133750.90 | 27-JAN-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1431.22 | 1561.80 | 14-OCT-14:00 | 175701.46 | 07-FEB-02:00 |
EnergyTransfer:Building | 586.32 | 1438.33 | 08-OCT-13:30 | 72440.38 | 07-FEB-02:00 |
EnergyTransfer:Zone:G SW APARTMENT | 15.52 | 0.00 | 20-APR-09:00 | 2277.07 | 07-FEB-02:00 |
Heating:EnergyTransfer | 299.47 | 0.00 | 17-MAR-15:15 | 72293.54 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 10.28 | 0.00 | 04-JAN-11:30 | 2277.07 | 07-FEB-02:00 |
Cooling:EnergyTransfer | 286.85 | 0.00 | 02-JAN-07:15 | 66375.26 | 20-JUL-15:15 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 5.24 | 0.00 | 01-JAN-00:15 | 1813.02 | 20-JUL-14:30 |
EnergyTransfer:Zone:G NW APARTMENT | 16.56 | 0.00 | 27-SEP-21:00 | 2389.13 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 12.63 | 0.00 | 18-FEB-15:00 | 2389.13 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 3.93 | 0.00 | 01-JAN-00:15 | 1634.09 | 20-JUL-17:00 |
EnergyTransfer:Zone:OFFICE | 21.41 | 0.02 | 30-OCT-04:00 | 4355.43 | 17-DEC-07:15 |
Heating:EnergyTransfer:Zone:OFFICE | 2.33 | 0.00 | 01-JAN-00:15 | 4355.43 | 17-DEC-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 19.08 | 0.00 | 02-JAN-07:15 | 4350.06 | 06-AUG-11:00 |
EnergyTransfer:Zone:G NE APARTMENT | 16.54 | 0.00 | 21-MAY-11:30 | 2369.73 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 12.51 | 0.00 | 17-MAR-09:30 | 2369.73 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.02 | 0.00 | 01-JAN-00:15 | 1201.05 | 19-JUL-18:00 |
EnergyTransfer:Zone:G N1 APARTMENT | 10.73 | 0.02 | 27-APR-13:00 | 1528.47 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 7.02 | 0.00 | 01-FEB-19:15 | 1528.47 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.71 | 0.00 | 01-JAN-00:15 | 927.33 | 19-JUL-18:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 10.73 | 0.00 | 31-OCT-18:30 | 1525.94 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 7.02 | 0.00 | 01-FEB-19:15 | 1525.94 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.71 | 0.00 | 01-JAN-00:15 | 916.84 | 19-JUL-18:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 10.19 | 0.04 | 22-APR-14:30 | 1349.06 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 5.04 | 0.00 | 01-JAN-11:15 | 1349.06 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 5.15 | 0.00 | 01-JAN-00:15 | 1263.00 | 02-SEP-12:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 10.98 | 0.06 | 13-MAY-15:00 | 1464.50 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 5.66 | 0.00 | 01-JAN-11:30 | 1464.50 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 5.32 | 0.00 | 01-JAN-00:15 | 1350.32 | 02-SEP-12:30 |
EnergyTransfer:Zone:M SW APARTMENT | 39.20 | 0.06 | 31-MAY-05:45 | 5249.08 | 20-JUL-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 15.78 | 0.00 | 01-JAN-11:15 | 4946.88 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 23.42 | 0.00 | 01-JAN-00:15 | 5249.08 | 20-JUL-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 39.14 | 0.02 | 25-AUG-13:00 | 5402.39 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 21.21 | 0.00 | 01-FEB-17:45 | 5402.39 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 17.93 | 0.00 | 01-JAN-00:15 | 4718.69 | 20-JUL-17:00 |
EnergyTransfer:Zone:M SE APARTMENT | 39.31 | 0.08 | 08-OCT-20:30 | 4899.51 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 15.72 | 0.00 | 01-JAN-11:00 | 4899.51 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 23.59 | 0.00 | 01-JAN-00:15 | 4813.06 | 20-JUL-14:15 |
EnergyTransfer:Zone:M NE APARTMENT | 39.41 | 0.03 | 14-OCT-14:15 | 5348.63 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 21.11 | 0.00 | 01-FEB-17:45 | 5348.63 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 18.30 | 0.00 | 01-JAN-00:15 | 3667.44 | 19-JUL-16:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 26.05 | 0.05 | 11-OCT-08:30 | 2935.15 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 8.31 | 0.00 | 09-JAN-16:45 | 2935.15 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 17.74 | 0.00 | 01-JAN-00:15 | 2850.82 | 19-JUL-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 26.04 | 0.16 | 01-OCT-16:00 | 2930.95 | 07-MAR-14:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 8.31 | 0.00 | 09-JAN-16:45 | 2930.95 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 17.73 | 0.00 | 01-JAN-00:15 | 2838.51 | 19-JUL-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 29.67 | 0.20 | 10-DEC-09:30 | 3701.24 | 02-SEP-12:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 4.94 | 0.00 | 01-JAN-09:15 | 2528.32 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 24.74 | 0.00 | 01-JAN-00:15 | 3701.24 | 02-SEP-12:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 29.67 | 0.07 | 10-NOV-04:00 | 3713.52 | 02-SEP-12:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 4.94 | 0.00 | 01-JAN-09:15 | 2525.08 | 07-MAR-14:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 24.73 | 0.00 | 01-JAN-00:15 | 3713.52 | 02-SEP-12:30 |
EnergyTransfer:Zone:T SW APARTMENT | 29.72 | 0.00 | 20-MAY-01:00 | 4212.71 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 19.77 | 0.00 | 04-JAN-11:00 | 4212.71 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 9.95 | 0.00 | 01-JAN-00:15 | 3749.09 | 20-JUL-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 30.92 | 0.01 | 18-SEP-03:15 | 4344.48 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 23.06 | 0.00 | 18-FEB-14:15 | 4344.48 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 7.87 | 0.00 | 01-JAN-00:15 | 3285.80 | 20-JUL-15:30 |
EnergyTransfer:Zone:T SE APARTMENT | 29.47 | 0.02 | 15-MAY-15:45 | 4185.81 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 19.61 | 0.00 | 04-JAN-10:45 | 4185.81 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 9.86 | 0.00 | 01-JAN-00:15 | 3407.82 | 20-JUL-14:15 |
EnergyTransfer:Zone:T NE APARTMENT | 30.71 | 0.00 | 21-SEP-03:45 | 4320.14 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 22.86 | 0.00 | 18-FEB-15:00 | 4320.14 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 7.85 | 0.00 | 01-JAN-00:15 | 2743.01 | 20-JUL-14:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 21.43 | 0.00 | 24-AUG-09:15 | 2868.98 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 14.31 | 0.00 | 01-FEB-19:45 | 2868.98 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 7.12 | 0.00 | 01-JAN-00:15 | 2130.53 | 20-JUL-14:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 21.43 | 0.01 | 12-MAY-11:15 | 2867.81 | 07-FEB-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 14.32 | 0.00 | 01-FEB-19:45 | 2867.81 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 7.11 | 0.00 | 01-JAN-00:15 | 2133.49 | 20-JUL-14:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 20.74 | 0.02 | 10-SEP-21:45 | 2790.02 | 20-JUL-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 11.37 | 0.00 | 01-JAN-11:30 | 2728.81 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 9.38 | 0.00 | 01-JAN-00:15 | 2790.02 | 20-JUL-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 20.75 | 0.02 | 04-OCT-00:15 | 2790.30 | 20-JUL-14:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 11.37 | 0.00 | 01-JAN-11:30 | 2727.25 | 07-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 9.38 | 0.00 | 01-JAN-00:15 | 2790.30 | 20-JUL-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 844.90 | 0.00 | 28-MAR-16:15 | 107420.24 | 20-JUL-15:15 |
HeatingCoils:EnergyTransfer | 530.06 | 0.00 | 28-MAR-16:15 | 107000.72 | 27-JAN-07:00 |
CoolingCoils:EnergyTransfer | 314.83 | 0.00 | 01-JAN-00:15 | 107420.24 | 20-JUL-15:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 10.282 | -5.242 | 0.000 | 0.000 | 3.895 | 1.087 | 12.213 | 11.249 | 0.000 | 0.104 | 0.000 | 0.000 | -8.474 | 0.000 | -9.085 | -16.027 |
G NW APARTMENT | 12.631 | -3.927 | 0.000 | 0.000 | 3.907 | 1.087 | 12.213 | 5.822 | 0.000 | 0.099 | 0.000 | 0.000 | -8.986 | 0.000 | -8.938 | -13.908 |
OFFICE | 2.330 | -19.080 | 0.000 | 0.000 | 0.535 | 26.452 | 9.482 | 11.055 | 0.000 | 0.052 | 0.002 | 0.000 | -8.097 | 0.000 | -7.979 | -14.749 |
G NE APARTMENT | 12.515 | -4.022 | 0.000 | 0.000 | 3.915 | 1.087 | 12.213 | 5.716 | 0.000 | 0.099 | 0.000 | 0.000 | -8.839 | 0.000 | -8.922 | -13.761 |
G N1 APARTMENT | 7.018 | -3.711 | 0.000 | 0.000 | 3.913 | 1.087 | 12.213 | 2.135 | 0.000 | 0.068 | 0.000 | 0.000 | -5.651 | 0.000 | -5.656 | -11.415 |
G N2 APARTMENT | 7.019 | -3.715 | 0.000 | 0.000 | 3.914 | 1.087 | 12.213 | 2.134 | 0.000 | 0.068 | 0.000 | 0.000 | -5.650 | 0.000 | -5.656 | -11.414 |
G S1 APARTMENT | 5.040 | -5.149 | 0.000 | 0.000 | 3.895 | 1.087 | 12.213 | 7.594 | 0.000 | 0.072 | 0.000 | 0.000 | -5.139 | 0.000 | -5.809 | -13.804 |
G S2 APARTMENT | 5.662 | -5.320 | 0.000 | 0.000 | 3.892 | 1.087 | 12.213 | 7.591 | 0.000 | 0.072 | 0.000 | 0.000 | -5.136 | 0.000 | -5.819 | -14.241 |
M SW APARTMENT | 15.780 | -23.422 | 0.000 | 0.000 | 3.803 | 1.087 | 12.213 | 10.833 | 0.000 | 0.145 | 1.873 | 0.000 | -9.083 | 0.000 | -13.229 | -0.000 |
M NW APARTMENT | 21.213 | -17.930 | 0.000 | 0.000 | 3.837 | 1.087 | 12.213 | 5.504 | 0.000 | 0.138 | 0.000 | 0.000 | -9.550 | 0.000 | -12.953 | -3.559 |
M SE APARTMENT | 15.724 | -23.585 | 0.000 | 0.000 | 3.807 | 1.087 | 12.213 | 10.734 | 0.000 | 0.145 | 2.047 | 0.000 | -8.945 | 0.000 | -13.225 | -0.001 |
M NE APARTMENT | 21.113 | -18.296 | 0.000 | 0.000 | 3.846 | 1.087 | 12.213 | 5.395 | 0.000 | 0.138 | 0.000 | 0.000 | -9.386 | 0.000 | -12.929 | -3.180 |
M N1 APARTMENT | 8.308 | -17.741 | 0.000 | 0.000 | 3.831 | 1.087 | 12.213 | 1.941 | 0.000 | 0.093 | 4.547 | 0.000 | -6.063 | 0.000 | -8.216 | -0.000 |
M N2 APARTMENT | 8.306 | -17.729 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 1.941 | 0.000 | 0.093 | 4.533 | 0.000 | -6.061 | 0.000 | -8.215 | -0.000 |
M S1 APARTMENT | 4.937 | -24.736 | 0.000 | 0.000 | 3.783 | 1.087 | 12.213 | 7.327 | 0.000 | 0.100 | 9.313 | 0.000 | -5.546 | 0.000 | -8.478 | -0.000 |
M S2 APARTMENT | 4.936 | -24.729 | 0.000 | 0.000 | 3.783 | 1.087 | 12.213 | 7.327 | 0.000 | 0.100 | 9.306 | 0.000 | -5.545 | 0.000 | -8.478 | -0.000 |
T SW APARTMENT | 19.766 | -9.949 | 0.000 | 0.000 | 3.855 | 1.087 | 12.213 | 10.768 | 0.000 | 0.200 | 0.000 | 0.000 | -8.671 | 0.000 | -17.093 | -12.176 |
T NW APARTMENT | 23.057 | -7.865 | 0.000 | 0.000 | 3.875 | 1.087 | 12.213 | 5.457 | 0.000 | 0.187 | 0.000 | 0.000 | -9.167 | 0.000 | -16.794 | -12.050 |
T SE APARTMENT | 19.605 | -9.861 | 0.000 | 0.000 | 3.860 | 1.087 | 12.213 | 10.687 | 0.000 | 0.200 | 0.000 | 0.000 | -8.551 | 0.000 | -17.096 | -12.143 |
T NE APARTMENT | 22.860 | -7.850 | 0.000 | 0.000 | 3.884 | 1.087 | 12.213 | 5.367 | 0.000 | 0.187 | 0.000 | 0.000 | -9.025 | 0.000 | -16.777 | -11.945 |
T N1 APARTMENT | 14.313 | -7.117 | 0.000 | 0.000 | 3.874 | 1.087 | 12.213 | 1.942 | 0.000 | 0.129 | 0.000 | 0.000 | -5.784 | 0.000 | -10.556 | -10.100 |
T N2 APARTMENT | 14.318 | -7.114 | 0.000 | 0.000 | 3.874 | 1.087 | 12.213 | 1.941 | 0.000 | 0.129 | 0.000 | 0.000 | -5.783 | 0.000 | -10.557 | -10.107 |
T S1 APARTMENT | 11.366 | -9.376 | 0.000 | 0.000 | 3.843 | 1.087 | 12.213 | 7.303 | 0.000 | 0.141 | 0.000 | 0.000 | -5.290 | 0.000 | -10.851 | -10.437 |
T S2 APARTMENT | 11.372 | -9.383 | 0.000 | 0.000 | 3.843 | 1.087 | 12.213 | 7.302 | 0.000 | 0.141 | 0.000 | 0.000 | -5.289 | 0.000 | -10.852 | -10.434 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.060 | 0.000 | 0.006 | 0.000 | 0.000 | -1.091 | 0.000 | -2.787 | -10.770 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.242 | 0.000 | 0.206 | 18.956 | 0.000 | -2.822 | 0.000 | -37.642 | -0.001 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.061 | 0.000 | 0.006 | 0.000 | 0.000 | -1.190 | 0.000 | -2.290 | -11.169 |
Total Facility | 299.470 | -286.850 | 0.000 | 0.000 | 89.294 | 95.189 | 296.854 | 155.428 | 0.000 | 3.122 | 50.579 | 0.000 | -178.813 | 0.000 | -296.882 | -227.392 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 20-JUL-14:30 | 0.00 | -1813.07 | 0.00 | 0.00 | 40.66 | 22.70 | 400.26 | 2376.61 | 0.00 | 237.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1265.04 |
G NW APARTMENT | 20-JUL-17:00 | 0.00 | -1634.35 | 0.00 | 0.00 | 82.51 | 64.86 | 588.62 | 1642.63 | 0.00 | 304.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1048.81 |
OFFICE | 23-JUL-06:01 | 0.00 | -7353.38 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 918.02 | 0.00 | 0.00 | 5811.23 | 0.00 | 0.00 | 0.00 | -86.33 | 0.00 |
G NE APARTMENT | 19-JUL-18:00 | 0.00 | -1200.97 | 0.00 | 0.00 | 140.72 | 87.56 | 588.62 | 562.31 | 0.00 | 111.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -289.36 |
G N1 APARTMENT | 19-JUL-18:45 | 0.00 | -927.25 | 0.00 | 0.00 | 141.48 | 103.77 | 547.42 | 347.83 | 0.00 | 48.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -261.72 |
G N2 APARTMENT | 19-JUL-18:45 | 0.00 | -916.76 | 0.00 | 0.00 | 141.36 | 103.77 | 547.42 | 347.82 | 0.00 | 48.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.99 |
G S1 APARTMENT | 02-SEP-12:30 | 0.00 | -1262.82 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1952.77 | 0.00 | 113.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1246.05 |
G S2 APARTMENT | 02-SEP-12:30 | 0.00 | -1350.14 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1951.46 | 0.00 | 113.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1157.42 |
M SW APARTMENT | 20-JUL-15:15 | 0.00 | -5249.47 | 0.00 | 0.00 | 48.72 | 45.40 | 470.90 | 2216.12 | 0.00 | 375.94 | 2092.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 20-JUL-16:25 | 0.00 | -4720.10 | 0.00 | 0.00 | 83.23 | 64.86 | 588.62 | 1824.77 | 0.00 | 428.25 | 1730.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 20-JUL-14:15 | 0.00 | -4813.50 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1488.85 | 0.00 | 331.98 | 2528.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 19-JUL-16:30 | 0.00 | -3668.18 | 0.00 | 0.00 | 84.62 | 64.86 | 588.62 | 734.77 | 0.00 | 198.92 | 1996.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 19-JUL-17:20 | 0.00 | -2857.93 | 0.00 | 0.00 | 141.75 | 87.56 | 588.62 | 421.06 | 0.00 | 103.27 | 1515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 19-JUL-17:38 | 0.00 | -2846.73 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 415.27 | 0.00 | 100.19 | 1513.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 02-SEP-12:30 | 0.00 | -3700.80 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1935.42 | 0.00 | 157.28 | 1165.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 02-SEP-12:30 | 0.00 | -3713.09 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1935.35 | 0.00 | 157.28 | 1178.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 20-JUL-15:15 | 0.00 | -3749.38 | 0.00 | 0.00 | 48.77 | 45.40 | 470.90 | 2175.98 | 0.00 | 496.44 | 511.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 20-JUL-15:30 | 0.00 | -3286.06 | 0.00 | 0.00 | 48.59 | 45.40 | 470.90 | 1926.51 | 0.00 | 508.58 | 286.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 20-JUL-14:15 | 0.00 | -3408.14 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1454.51 | 0.00 | 437.65 | 1052.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 20-JUL-14:00 | 0.00 | -2743.25 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 858.96 | 0.00 | 422.02 | 1025.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 20-JUL-14:00 | 0.00 | -2130.63 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 523.44 | 0.00 | 254.69 | 916.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 20-JUL-14:00 | 0.00 | -2133.60 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 523.38 | 0.00 | 254.68 | 919.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 20-JUL-14:15 | 0.00 | -2790.22 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1121.26 | 0.00 | 263.97 | 941.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 20-JUL-14:15 | 0.00 | -2790.51 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1121.24 | 0.00 | 263.97 | 941.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-15:15 | 0.00 | -66380.24 | 0.00 | 0.00 | 1188.30 | 4512.09 | 11708.34 | 25939.92 | 0.00 | 8170.94 | 14860.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 05-OCT-06:01 | 2676.75 | 0.00 | 0.00 | 0.00 | 163.44 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -328.68 | 0.00 | -151.30 | -2784.97 |
G NW APARTMENT | 07-FEB-02:00 | 2389.04 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1000.11 | 0.00 | -1304.79 | -521.62 |
OFFICE | 01-FEB-07:01 | 6375.22 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -289.63 | 0.00 | -253.05 | -6543.00 |
G NE APARTMENT | 07-FEB-02:00 | 2369.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -986.93 | 0.00 | -1304.79 | -515.40 |
G N1 APARTMENT | 27-JAN-08:15 | 1529.25 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -656.71 | 0.00 | -459.95 | -894.50 |
G N2 APARTMENT | 27-JAN-08:15 | 1526.72 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -656.74 | 0.00 | -459.95 | -891.95 |
G S1 APARTMENT | 07-FEB-02:00 | 1349.01 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.15 | 0.00 | -787.02 | -387.33 |
G S2 APARTMENT | 14-FEB-18:01 | 2045.02 | 0.00 | 0.00 | 0.00 | 168.21 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -435.06 | 0.00 | -162.39 | -2291.96 |
M SW APARTMENT | 07-MAR-14:00 | 4946.82 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8.94 | 0.00 | -2341.49 | -3045.27 |
M NW APARTMENT | 07-MAR-14:00 | 5402.32 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -315.59 | 0.00 | -2341.49 | -3194.12 |
M SE APARTMENT | 07-MAR-14:00 | 4899.45 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -135.10 | 0.00 | -2341.49 | -2871.74 |
M NE APARTMENT | 07-MAR-14:00 | 5348.57 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -441.68 | 0.00 | -2341.49 | -3014.28 |
M N1 APARTMENT | 31-OCT-06:01 | 3485.19 | 0.00 | 0.00 | 0.00 | 161.43 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -430.23 | 0.00 | -202.89 | -3438.26 |
M N2 APARTMENT | 31-OCT-06:01 | 3494.13 | 0.00 | 0.00 | 0.00 | 161.43 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -430.23 | 0.00 | -202.89 | -3447.20 |
M S1 APARTMENT | 22-JAN-18:01 | 3624.52 | 0.00 | 0.00 | 0.00 | 165.30 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -408.54 | 0.00 | -329.00 | -3728.46 |
M S2 APARTMENT | 22-JAN-18:01 | 3626.17 | 0.00 | 0.00 | 0.00 | 165.30 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -408.52 | 0.00 | -329.00 | -3730.13 |
T SW APARTMENT | 07-FEB-02:00 | 4212.53 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1011.10 | 0.00 | -2484.10 | -1154.82 |
T NW APARTMENT | 07-FEB-02:00 | 4344.30 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1004.35 | 0.00 | -2484.10 | -1293.33 |
T SE APARTMENT | 07-FEB-02:00 | 4185.63 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -995.59 | 0.00 | -2484.10 | -1143.43 |
T NE APARTMENT | 07-FEB-02:00 | 4319.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -988.83 | 0.00 | -2484.10 | -1284.51 |
T N1 APARTMENT | 07-FEB-02:00 | 2868.87 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -609.67 | 0.00 | -1498.40 | -1198.29 |
T N2 APARTMENT | 07-FEB-02:00 | 2867.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -609.69 | 0.00 | -1498.40 | -1197.09 |
T S1 APARTMENT | 07-FEB-02:00 | 2728.71 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -615.98 | 0.00 | -1498.40 | -1051.81 |
T S2 APARTMENT | 07-FEB-02:00 | 2727.14 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -616.01 | 0.00 | -1498.40 | -1050.23 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-FEB-02:00 | 72143.80 | 0.00 | 0.00 | 0.00 | 4362.43 | 1952.47 | 5793.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19803.73 | 0.00 | -37055.58 | -27392.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Sec1.1A-General InformationData | |
Weather File | Burlington International Ap VT USA TMY3 WMO#=726170 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 41.50 |
Number of hours cooling loads not met | 4.75 |
Number of hours not met | 46.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 662.58 | 133750.90 | 0.00 | 0.00 |
Space Cooling | 76.53 | 25971.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 213.20 | 6760.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 431.90 | 23590.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1397.82 | 662.58 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1397.82 |
Natural Gas | 0.00 | 662.58 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 2060.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 24.42 |
Fans-Interior | 68.01 |
Service Water Heating | 137.78 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.79 |
Subtotal | 445.93 |
Natural Gas [MJ/m2] | |
Space Heating | 211.37 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 211.37 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.75 |
Space Heating | 32.16 |
Space Cooling | 3.71 |
Fans-Interior | 10.35 |
Service Water Heating | 20.96 |
Receptacle Equipment | 25.12 |
Miscellaneous | 1.95 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.155225 |
G NW APARTMENT DIRECT AIR | 0.144642 |
OFFICE DIRECT AIR | 0.467209 |
G NE APARTMENT DIRECT AIR | 0.102738 |
G N1 APARTMENT DIRECT AIR | 0.081372 |
G N2 APARTMENT DIRECT AIR | 0.080346 |
G S1 APARTMENT DIRECT AIR | 0.102534 |
G S2 APARTMENT DIRECT AIR | 0.105700 |
M SW APARTMENT DIRECT AIR | 0.442375 |
M NW APARTMENT DIRECT AIR | 0.409510 |
M SE APARTMENT DIRECT AIR | 0.403979 |
M NE APARTMENT DIRECT AIR | 0.316977 |
M N1 APARTMENT DIRECT AIR | 0.247463 |
M N2 APARTMENT DIRECT AIR | 0.245663 |
M S1 APARTMENT DIRECT AIR | 0.306644 |
M S2 APARTMENT DIRECT AIR | 0.307767 |
T SW APARTMENT DIRECT AIR | 0.305301 |
T NW APARTMENT DIRECT AIR | 0.272846 |
T SE APARTMENT DIRECT AIR | 0.283191 |
T NE APARTMENT DIRECT AIR | 0.222310 |
T N1 APARTMENT DIRECT AIR | 0.175684 |
T N2 APARTMENT DIRECT AIR | 0.175777 |
T S1 APARTMENT DIRECT AIR | 0.233858 |
T S2 APARTMENT DIRECT AIR | 0.234585 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.155225 |
SPLIT GNW MAIN BRANCH | 0.144642 |
SPLIT OFFICE MAIN BRANCH | 0.467209 |
SPLIT GNE MAIN BRANCH | 0.102738 |
SPLIT GN1 MAIN BRANCH | 0.081372 |
SPLIT GN2 MAIN BRANCH | 0.080346 |
SPLIT GS1 MAIN BRANCH | 0.102534 |
SPLIT GS2 MAIN BRANCH | 0.105700 |
SPLIT MSW MAIN BRANCH | 0.442375 |
SPLIT MNW MAIN BRANCH | 0.409510 |
SPLIT MSE MAIN BRANCH | 0.403979 |
SPLIT MNE MAIN BRANCH | 0.316977 |
SPLIT MN1 MAIN BRANCH | 0.247463 |
SPLIT MN2 MAIN BRANCH | 0.245663 |
SPLIT MS1 MAIN BRANCH | 0.306644 |
SPLIT MS2 MAIN BRANCH | 0.307767 |
SPLIT TSW MAIN BRANCH | 0.305301 |
SPLIT TNW MAIN BRANCH | 0.272846 |
SPLIT TSE MAIN BRANCH | 0.283191 |
SPLIT TNE MAIN BRANCH | 0.222310 |
SPLIT TN1 MAIN BRANCH | 0.175684 |
SPLIT TN2 MAIN BRANCH | 0.175777 |
SPLIT TS1 MAIN BRANCH | 0.233858 |
SPLIT TS2 MAIN BRANCH | 0.234585 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.155225 |
SPLIT GNW | 0.144642 |
SPLIT OFFICE | 0.467209 |
SPLIT GNE | 0.102738 |
SPLIT GN1 | 0.081372 |
SPLIT GN2 | 0.080346 |
SPLIT GS1 | 0.102534 |
SPLIT GS2 | 0.105700 |
SPLIT MSW | 0.442375 |
SPLIT MNW | 0.409510 |
SPLIT MSE | 0.403979 |
SPLIT MNE | 0.316977 |
SPLIT MN1 | 0.247463 |
SPLIT MN2 | 0.245663 |
SPLIT MS1 | 0.306644 |
SPLIT MS2 | 0.307767 |
SPLIT TSW | 0.305301 |
SPLIT TNW | 0.272846 |
SPLIT TSE | 0.283191 |
SPLIT TNE | 0.222310 |
SPLIT TN1 | 0.175684 |
SPLIT TN2 | 0.175777 |
SPLIT TS1 | 0.233858 |
SPLIT TS2 | 0.234585 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.155225 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.144642 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.467209 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.102738 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.081372 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.080346 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.102534 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.105700 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.442375 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.409510 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.403979 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.316977 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.247463 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.245663 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.306644 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.307767 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.305301 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.272846 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.283191 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.222310 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.175684 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.175777 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.233858 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.234585 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.155225 | 3028.38 | 0.742948 |
SPLIT GNW COOLING COIL | 0.144642 | 2802.54 | 0.745105 |
SPLIT OFFICE COOLING COIL | 0.467209 | 7733.97 | 0.798655 |
SPLIT GNE COOLING COIL | 0.102738 | 2101.91 | 0.728474 |
SPLIT GN1 COOLING COIL | 0.081372 | 1720.68 | 0.718810 |
SPLIT GN2 COOLING COIL | 0.080346 | 1704.02 | 0.717959 |
SPLIT GS1 COOLING COIL | 0.102534 | 2170.39 | 0.718515 |
SPLIT GS2 COOLING COIL | 0.105700 | 2216.37 | 0.721244 |
SPLIT MSW COOLING COIL | 0.442375 | 8180.55 | 0.760109 |
SPLIT MNW COOLING COIL | 0.409510 | 7602.89 | 0.758807 |
SPLIT MSE COOLING COIL | 0.403979 | 7707.98 | 0.749970 |
SPLIT MNE COOLING COIL | 0.316977 | 6045.70 | 0.750089 |
SPLIT MN1 COOLING COIL | 0.247463 | 4842.64 | 0.742000 |
SPLIT MN2 COOLING COIL | 0.245663 | 4814.15 | 0.741565 |
SPLIT MS1 COOLING COIL | 0.306644 | 6024.82 | 0.740758 |
SPLIT MS2 COOLING COIL | 0.307767 | 6042.44 | 0.740986 |
SPLIT TSW COOLING COIL | 0.305301 | 5554.63 | 0.765507 |
SPLIT TNW COOLING COIL | 0.272846 | 4986.66 | 0.763997 |
SPLIT TSE COOLING COIL | 0.283191 | 5210.40 | 0.761780 |
SPLIT TNE COOLING COIL | 0.222310 | 4260.45 | 0.748567 |
SPLIT TN1 COOLING COIL | 0.175684 | 3417.11 | 0.743900 |
SPLIT TN2 COOLING COIL | 0.175777 | 3418.88 | 0.743903 |
SPLIT TS1 COOLING COIL | 0.233858 | 4330.78 | 0.759639 |
SPLIT TS2 COOLING COIL | 0.234585 | 4342.08 | 0.759801 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.155225 | 0.155225 | 0.155225 | 0.155225 | 3969.55 | 3028.38 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.144642 | 0.144642 | 0.144642 | 0.144642 | 3939.34 | 2802.54 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.467209 | 0.467209 | 0.467209 | 0.467209 | 6758.44 | 7733.97 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.102738 | 0.102738 | 0.102738 | 0.102738 | 3949.77 | 2101.91 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.081372 | 0.081372 | 0.081372 | 0.081372 | 3038.82 | 1720.68 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.080346 | 0.080346 | 0.080346 | 0.080346 | 3039.06 | 1704.02 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.102534 | 0.102534 | 0.102534 | 0.102534 | 3022.61 | 2170.39 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.105700 | 0.105700 | 0.105700 | 0.105700 | 3157.36 | 2216.37 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.442375 | 0.442375 | 0.442375 | 0.442375 | 7653.02 | 8180.55 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.409510 | 0.409510 | 0.409510 | 0.409510 | 7697.97 | 7602.89 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.403979 | 0.403979 | 0.403979 | 0.403979 | 7680.34 | 7707.98 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.316977 | 0.316977 | 0.316977 | 0.316977 | 7725.31 | 6045.70 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.247463 | 0.247463 | 0.247463 | 0.247463 | 5436.16 | 4842.64 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.245663 | 0.245663 | 0.245663 | 0.245663 | 5436.81 | 4814.15 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.306644 | 0.306644 | 0.306644 | 0.306644 | 5393.69 | 6024.82 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.307767 | 0.307767 | 0.307767 | 0.307767 | 5394.34 | 6042.44 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.305301 | 0.305301 | 0.305301 | 0.305301 | 5631.73 | 5554.63 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.272846 | 0.272846 | 0.272846 | 0.272846 | 5657.45 | 4986.66 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.283191 | 0.283191 | 0.283191 | 0.283191 | 5646.20 | 5210.40 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.222310 | 0.222310 | 0.222310 | 0.222310 | 5671.92 | 4260.45 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.175684 | 0.175684 | 0.175684 | 0.175684 | 4418.61 | 3417.11 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.175777 | 0.175777 | 0.175777 | 0.175777 | 4418.97 | 3418.88 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.233858 | 0.233858 | 0.233858 | 0.233858 | 4391.11 | 4330.78 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.234585 | 0.234585 | 0.234585 | 0.234585 | 4391.48 | 4342.08 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.155225 |
SPLIT GNW SUPPLY FAN | 0.144642 |
SPLIT OFFICE SUPPLY FAN | 0.467209 |
SPLIT GNE SUPPLY FAN | 0.102738 |
SPLIT GN1 SUPPLY FAN | 0.081372 |
SPLIT GN2 SUPPLY FAN | 0.080346 |
SPLIT GS1 SUPPLY FAN | 0.102534 |
SPLIT GS2 SUPPLY FAN | 0.105700 |
SPLIT MSW SUPPLY FAN | 0.442375 |
SPLIT MNW SUPPLY FAN | 0.409510 |
SPLIT MSE SUPPLY FAN | 0.403979 |
SPLIT MNE SUPPLY FAN | 0.316977 |
SPLIT MN1 SUPPLY FAN | 0.247463 |
SPLIT MN2 SUPPLY FAN | 0.245663 |
SPLIT MS1 SUPPLY FAN | 0.306644 |
SPLIT MS2 SUPPLY FAN | 0.307767 |
SPLIT TSW SUPPLY FAN | 0.305301 |
SPLIT TNW SUPPLY FAN | 0.272846 |
SPLIT TSE SUPPLY FAN | 0.283191 |
SPLIT TNE SUPPLY FAN | 0.222310 |
SPLIT TN1 SUPPLY FAN | 0.175684 |
SPLIT TN2 SUPPLY FAN | 0.175777 |
SPLIT TS1 SUPPLY FAN | 0.233858 |
SPLIT TS2 SUPPLY FAN | 0.234585 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 3969.55 |
SPLIT GNW HEATING COIL | 3939.34 |
SPLIT OFFICE HEATING COIL | 6758.44 |
SPLIT GNE HEATING COIL | 3949.77 |
SPLIT GN1 HEATING COIL | 3038.82 |
SPLIT GN2 HEATING COIL | 3039.06 |
SPLIT GS1 HEATING COIL | 3022.61 |
SPLIT GS2 HEATING COIL | 3157.36 |
SPLIT MSW HEATING COIL | 7653.02 |
SPLIT MNW HEATING COIL | 7697.97 |
SPLIT MSE HEATING COIL | 7680.34 |
SPLIT MNE HEATING COIL | 7725.31 |
SPLIT MN1 HEATING COIL | 5436.16 |
SPLIT MN2 HEATING COIL | 5436.81 |
SPLIT MS1 HEATING COIL | 5393.69 |
SPLIT MS2 HEATING COIL | 5394.34 |
SPLIT TSW HEATING COIL | 5631.73 |
SPLIT TNW HEATING COIL | 5657.45 |
SPLIT TSE HEATING COIL | 5646.20 |
SPLIT TNE HEATING COIL | 5671.92 |
SPLIT TN1 HEATING COIL | 4418.61 |
SPLIT TN2 HEATING COIL | 4418.97 |
SPLIT TS1 HEATING COIL | 4391.11 |
SPLIT TS2 HEATING COIL | 4391.48 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.77 | -0.5 |
April | 22.14 | 7.83 |
May | 22.62 | 13.82 |
June | 24.19 | 19.28 |
July | 24.32 | 21.06 |
August | 24.29 | 19.79 |
September | 23.75 | 15.09 |
October | 22.07 | 8.66 |
November | 21.77 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.67 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.71 | -0.5 |
April | 21.99 | 7.83 |
May | 22.44 | 13.82 |
June | 24.18 | 19.28 |
July | 24.31 | 21.06 |
August | 24.24 | 19.79 |
September | 23.55 | 15.09 |
October | 21.83 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.59 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.41 | -7.2 |
February | 18.88 | -5.6 |
March | 20.36 | -0.5 |
April | 22.30 | 7.83 |
May | 23.69 | 13.82 |
June | 25.69 | 19.28 |
July | 26.22 | 21.06 |
August | 25.88 | 19.79 |
September | 25.07 | 15.09 |
October | 22.72 | 8.66 |
November | 20.99 | 2.78 |
December | 19.62 | -1.5 |
Annual Sum or Average | 22.50 | 7.87 |
Minimum of Months | 18.41 | -7.2 |
Maximum of Months | 26.22 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.70 | -0.5 |
April | 21.95 | 7.83 |
May | 22.36 | 13.82 |
June | 24.16 | 19.28 |
July | 24.31 | 21.06 |
August | 24.23 | 19.79 |
September | 23.47 | 15.09 |
October | 21.78 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.57 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.31 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.70 | -0.5 |
April | 21.90 | 7.83 |
May | 22.23 | 13.82 |
June | 24.13 | 19.28 |
July | 24.30 | 21.06 |
August | 24.21 | 19.79 |
September | 23.57 | 15.09 |
October | 21.81 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.56 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.70 | -0.5 |
April | 21.89 | 7.83 |
May | 22.23 | 13.82 |
June | 24.13 | 19.28 |
July | 24.30 | 21.06 |
August | 24.21 | 19.79 |
September | 23.57 | 15.09 |
October | 21.81 | 8.66 |
November | 21.70 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.56 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.30 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.75 | -0.5 |
April | 22.08 | 7.83 |
May | 22.48 | 13.82 |
June | 24.18 | 19.28 |
July | 24.32 | 21.06 |
August | 24.30 | 19.79 |
September | 23.87 | 15.09 |
October | 22.11 | 8.66 |
November | 21.78 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.67 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.32 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.09 | 7.83 |
May | 22.52 | 13.82 |
June | 24.21 | 19.28 |
July | 24.33 | 21.06 |
August | 24.31 | 19.79 |
September | 23.89 | 15.09 |
October | 22.13 | 8.66 |
November | 21.78 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.68 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 22.09 | -0.5 |
April | 23.01 | 7.83 |
May | 24.21 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.39 | 19.79 |
September | 24.14 | 15.09 |
October | 23.21 | 8.66 |
November | 22.03 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 23.09 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.64 | 7.83 |
May | 24.06 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.38 | 19.79 |
September | 23.96 | 15.09 |
October | 22.37 | 8.66 |
November | 21.74 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.91 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.72 | -5.6 |
March | 22.07 | -0.5 |
April | 23.03 | 7.83 |
May | 24.21 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.39 | 19.79 |
September | 24.13 | 15.09 |
October | 23.17 | 8.66 |
November | 22.02 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 23.09 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.59 | 7.83 |
May | 24.02 | 13.82 |
June | 24.39 | 19.28 |
July | 24.40 | 21.06 |
August | 24.38 | 19.79 |
September | 23.91 | 15.09 |
October | 22.22 | 8.66 |
November | 21.73 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.88 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.78 | -0.5 |
April | 22.67 | 7.83 |
May | 24.09 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.38 | 19.79 |
September | 24.09 | 15.09 |
October | 22.51 | 8.66 |
November | 21.76 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.94 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.77 | -0.5 |
April | 22.67 | 7.83 |
May | 24.09 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.38 | 19.79 |
September | 24.08 | 15.09 |
October | 22.49 | 8.66 |
November | 21.76 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.94 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.16 | -0.5 |
April | 23.23 | 7.83 |
May | 24.29 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.40 | 19.79 |
September | 24.27 | 15.09 |
October | 23.64 | 8.66 |
November | 22.20 | 2.78 |
December | 21.73 | -1.5 |
Annual Sum or Average | 23.19 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.75 | -5.6 |
March | 22.16 | -0.5 |
April | 23.23 | 7.83 |
May | 24.29 | 13.82 |
June | 24.40 | 19.28 |
July | 24.40 | 21.06 |
August | 24.40 | 19.79 |
September | 24.27 | 15.09 |
October | 23.63 | 8.66 |
November | 22.20 | 2.78 |
December | 21.73 | -1.5 |
Annual Sum or Average | 23.19 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.40 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.73 | -5.6 |
March | 21.99 | -0.5 |
April | 22.58 | 7.83 |
May | 23.62 | 13.82 |
June | 24.31 | 19.28 |
July | 24.34 | 21.06 |
August | 24.30 | 19.79 |
September | 23.68 | 15.09 |
October | 22.50 | 8.66 |
November | 21.88 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.87 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.80 | -0.5 |
April | 22.38 | 7.83 |
May | 23.47 | 13.82 |
June | 24.31 | 19.28 |
July | 24.34 | 21.06 |
August | 24.25 | 19.79 |
September | 23.49 | 15.09 |
October | 22.08 | 8.66 |
November | 21.72 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.75 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.72 | -5.6 |
March | 21.99 | -0.5 |
April | 22.59 | 7.83 |
May | 23.62 | 13.82 |
June | 24.31 | 19.28 |
July | 24.34 | 21.06 |
August | 24.30 | 19.79 |
September | 23.67 | 15.09 |
October | 22.47 | 8.66 |
November | 21.87 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.86 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.36 | 7.83 |
May | 23.43 | 13.82 |
June | 24.29 | 19.28 |
July | 24.33 | 21.06 |
August | 24.26 | 19.79 |
September | 23.44 | 15.09 |
October | 21.98 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.73 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.36 | 7.83 |
May | 23.53 | 13.82 |
June | 24.32 | 19.28 |
July | 24.34 | 21.06 |
August | 24.26 | 19.79 |
September | 23.53 | 15.09 |
October | 22.07 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.76 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.70 | -5.6 |
March | 21.76 | -0.5 |
April | 22.36 | 7.83 |
May | 23.53 | 13.82 |
June | 24.32 | 19.28 |
July | 24.34 | 21.06 |
August | 24.27 | 19.79 |
September | 23.53 | 15.09 |
October | 22.07 | 8.66 |
November | 21.71 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.75 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.03 | -0.5 |
April | 22.67 | 7.83 |
May | 23.76 | 13.82 |
June | 24.34 | 19.28 |
July | 24.36 | 21.06 |
August | 24.32 | 19.79 |
September | 23.81 | 15.09 |
October | 22.68 | 8.66 |
November | 21.94 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.93 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.36 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -7.2 |
February | 21.74 | -5.6 |
March | 22.03 | -0.5 |
April | 22.67 | 7.83 |
May | 23.76 | 13.82 |
June | 24.34 | 19.28 |
July | 24.36 | 21.06 |
August | 24.32 | 19.79 |
September | 23.81 | 15.09 |
October | 22.68 | 8.66 |
November | 21.94 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 22.93 | 7.87 |
Minimum of Months | 21.70 | -7.2 |
Maximum of Months | 24.36 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | -7.2 |
February | 20.35 | -5.6 |
March | 21.30 | -0.5 |
April | 23.08 | 7.83 |
May | 24.92 | 13.82 |
June | 26.33 | 19.28 |
July | 26.53 | 21.06 |
August | 26.33 | 19.79 |
September | 25.03 | 15.09 |
October | 22.85 | 8.66 |
November | 21.40 | 2.78 |
December | 20.60 | -1.5 |
Annual Sum or Average | 23.25 | 7.87 |
Minimum of Months | 20.10 | -7.2 |
Maximum of Months | 26.53 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.95 | -7.2 |
February | 17.27 | -5.6 |
March | 18.45 | -0.5 |
April | 20.55 | 7.83 |
May | 22.18 | 13.82 |
June | 24.99 | 19.28 |
July | 25.64 | 21.06 |
August | 25.35 | 19.79 |
September | 23.95 | 15.09 |
October | 20.87 | 8.66 |
November | 19.17 | 2.78 |
December | 18.07 | -1.5 |
Annual Sum or Average | 21.14 | 7.87 |
Minimum of Months | 16.95 | -7.2 |
Maximum of Months | 25.64 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | -7.2 |
February | 22.46 | -5.6 |
March | 23.08 | -0.5 |
April | 24.59 | 7.83 |
May | 26.09 | 13.82 |
June | 26.69 | 19.28 |
July | 26.77 | 21.06 |
August | 26.69 | 19.79 |
September | 26.14 | 15.09 |
October | 24.58 | 8.66 |
November | 23.16 | 2.78 |
December | 22.52 | -1.5 |
Annual Sum or Average | 24.60 | 7.87 |
Minimum of Months | 22.31 | -7.2 |
Maximum of Months | 26.77 | 21.06 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:29
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.116445E+12 | 73318.504 | 31-JAN-18:45 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32394.257 | 0.000 | 0.000 | 0.000 |
February | 0.105425E+12 | 73333.480 | 19-FEB-18:30 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32409.232 | 0.000 | 0.000 | 0.000 |
March | 0.116145E+12 | 73327.477 | 01-MAR-18:15 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32403.229 | 0.000 | 0.000 | 0.000 |
April | 0.112443E+12 | 75864.723 | 21-APR-17:00 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 10835.828 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26657.647 | 0.000 | 0.000 | 0.000 |
May | 0.116916E+12 | 76694.903 | 31-MAY-17:15 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 14732.560 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23591.095 | 0.000 | 0.000 | 0.000 |
June | 0.122710E+12 | 82223.706 | 16-JUN-16:45 | 4276.255 | 26630.920 | 6760.374 | 0.000 | 23410.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21145.500 | 0.000 | 0.000 | 0.000 |
July | 0.130628E+12 | 87933.019 | 20-JUL-17:00 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 25971.630 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23590.141 | 0.000 | 0.000 | 0.000 |
August | 0.127762E+12 | 84690.413 | 04-AUG-17:00 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 18621.816 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27697.350 | 0.000 | 0.000 | 0.000 |
September | 0.113792E+12 | 77057.641 | 01-SEP-17:45 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 10484.264 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28202.129 | 0.000 | 0.000 | 0.000 |
October | 0.111249E+12 | 67552.248 | 30-OCT-17:15 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26628.000 | 0.000 | 0.000 | 0.000 |
November | 0.109321E+12 | 70278.311 | 20-NOV-18:00 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29354.064 | 0.000 | 0.000 | 0.000 |
December | 0.114985E+12 | 71356.306 | 01-DEC-18:45 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30432.058 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.139782E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.105425E+12 | 67552.248 | 4276.255 | 26630.920 | 6760.374 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21145.500 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.130628E+12 | 87933.019 | 4979.953 | 26630.920 | 6760.374 | 0.000 | 25971.630 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32409.232 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:29
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.170884E+12 | 133750.900 | 27-JAN-06:00 | 133750.900 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 133750.900 |
February | 0.140609E+12 | 129076.352 | 07-FEB-01:00 | 129076.352 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 129076.352 |
March | 0.983651E+11 | 122542.070 | 07-MAR-07:15 | 122542.070 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 122542.070 |
April | 0.305308E+11 | 88389.047 | 09-APR-02:00 | 88389.047 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 88389.047 |
May | 0.270640E+10 | 22885.253 | 08-MAY-02:00 | 22885.253 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22885.253 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.191548E+08 | 1828.621 | 27-AUG-04:00 | 1828.621 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1828.621 |
September | 0.178062E+10 | 16678.947 | 30-SEP-04:00 | 16678.947 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16678.947 |
October | 0.178715E+11 | 41080.295 | 31-OCT-06:15 | 41080.295 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 41080.295 |
November | 0.721677E+11 | 72596.514 | 29-NOV-07:00 | 72596.514 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 72596.514 |
December | 0.127645E+12 | 122893.980 | 17-DEC-07:15 | 122893.980 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 122893.980 |
Annual Sum or Average | 0.662579E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.170884E+12 | 133750.900 | 133750.900 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 133750.900 |