Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Houston Bush Intercontinental TX USA TMY3 WMO#=722430

Simulation Timestamp: 2015-09-09 18:47:59


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1575.52 502.62 557.91
Net Site Energy 1575.52 502.62 557.91
Total Source Energy 4867.24 1552.74 1723.54
Net Source Energy 4867.24 1552.74 1723.54


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 58.77 0.00 0.00 0.00 0.00
Cooling 275.47 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 235.20 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 329.84 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1516.74 58.77 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 58.77 0.00 0.00 0.00 0.00
Cooling General 275.47 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 235.20 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 329.84 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.16 0.00 0.00 0.00 0.00 0.00
HVAC 297.63 20.81 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 537.10 20.81 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.59 0.00 0.00 0.00 0.00 0.00
HVAC 268.14 18.75 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 483.87 18.75 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1516.74 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1516.74 100.00
     
Total On-Site and Utility Electric Sources 1516.74 100.00
Total Electricity End Uses 1516.74 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 20.25
Time Setpoint Not Met During Occupied Cooling 4.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3338.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Weather File Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Latitude [deg] 30.00
Longitude [deg] -95.4
Elevation [m] 29.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 04-AUG-16:30 11-FEB-04:00 - - - 01-JAN-07:15
Heating 0.00 73740.65 0.00 0.00 0.00 0.00
Cooling 32724.58 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4276.26 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7458.16 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 18142.01 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 89231.93 73740.65 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 73740.65 0.00 0.00 0.00 0.00
Cooling General 32724.58 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 3538.13 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 738.12 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7458.16 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 18142.01 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 63.71 0.00 0.00 0.00
Cooling 872.42 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 127.05 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 744.88 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1044.60 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4803.53 63.71 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 22.56 0.00 0.00 0.00
Cooling 308.93 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.99 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 263.77 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 369.90 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1700.98 22.56 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 22.56 0.00 0.00 0.00
Cooling 308.93 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.99 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 263.77 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 369.90 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1700.98 22.56 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB -1.60 0.00 -1.60 Wetbulb [C] 2.80 0.00
HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 36.00 10.10 24.80 Wetbulb [C] 3.50 170.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.72_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 4.600 0.293 0.130     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 4.600 0.293 0.130     No M EWALL C 270.00 90.00 W
Total or Average           306.92 4.600 0.293 0.130              
North Total or Average           112.97 4.600 0.293 0.130              
Non-North Total or Average           193.95 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.71 83.71 40.12
Exterior Lighting Total 2553.00           40.12



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4135.87 2964.95 1170.93 0.72 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4174.00 3014.33 1159.67 0.72 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8562.96 6630.64 1932.33 0.77 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3429.90 2438.80 991.10 0.71 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2639.28 1826.62 812.67 0.69 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2627.29 1817.12 810.17 0.69 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2635.73 1781.98 853.76 0.68 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2687.59 1820.67 866.93 0.68 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9801.70 7114.41 2687.28 0.73 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   9924.36 7234.33 2690.03 0.73 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8481.53 6091.64 2389.89 0.72 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   8320.35 5995.32 2325.03 0.72 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6436.85 4534.70 1902.15 0.70 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6417.69 4519.47 1898.22 0.70 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6468.93 4471.65 1997.28 0.69 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6482.44 4482.35 2000.09 0.69 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6450.85 4749.25 1701.61 0.74 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6404.44 4730.34 1674.10 0.74 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5806.87 4204.47 1602.40 0.72 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5557.04 4006.32 1550.72 0.72 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4508.38 3223.50 1284.88 0.72 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4511.11 3225.73 1285.39 0.72 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4736.69 3404.79 1331.90 0.72 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4743.96 3410.62 1333.35 0.72 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3983.0 3.27 11.17 11.63 11.11
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4017.0 3.26 11.14 11.59 11.06
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8184.0 3.17 10.82 11.24 10.59
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3305.7 3.28 11.21 11.67 11.16
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2550.1 3.32 11.33 11.80 11.35
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2538.6 3.32 11.33 11.81 11.35
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2552.0 3.35 11.43 11.92 11.51
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2601.7 3.35 11.42 11.91 11.50
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 9428.4 3.26 11.11 11.57 11.02
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 9542.4 3.25 11.09 11.55 10.99
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 8166.7 3.27 11.16 11.62 11.10
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 8009.0 3.27 11.15 11.60 11.07
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6209.1 3.30 11.25 11.72 11.23
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6190.9 3.30 11.25 11.72 11.23
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6251.0 3.32 11.33 11.81 11.36
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6263.8 3.32 11.33 11.81 11.35
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6196.6 3.24 11.05 11.50 10.93
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 6150.1 3.23 11.03 11.48 10.91
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5587.0 3.26 11.12 11.58 11.04
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 5348.8 3.27 11.14 11.60 11.07
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4342.9 3.28 11.18 11.64 11.13
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4345.5 3.28 11.18 11.64 11.13
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4560.5 3.27 11.16 11.62 11.09
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4567.4 3.27 11.16 11.62 11.09
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   2150.32 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   2142.14 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   3890.86 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   2142.14 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1615.05 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1615.05 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1615.05 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1615.05 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   4192.75 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   4237.24 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   4192.75 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   4237.24 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3230.10 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3230.10 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3230.10 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3230.10 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   3124.18 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   3148.92 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   3124.18 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   3148.92 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2361.06 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2361.06 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2335.82 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2335.82 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 225.53 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 231.81 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 560.77 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 183.21 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 131.44 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 130.61 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 123.21 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 126.33 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 551.21 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.49 564.00 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.40 464.66 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.40 459.54 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 335.78 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 334.45 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 321.12 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 322.05 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 375.55 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 375.76 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 324.58 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 307.33 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 244.22 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 244.42 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 260.03 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 260.54 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2060.39 2472.47 0.162 0.194 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 34.33 0.01519
G NW APARTMENT 2117.88 2541.46 0.166 0.200 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.83 0.01519
OFFICE 4876.81 5852.18 0.403 0.483 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 31.30 0.01519
G NE APARTMENT 1673.69 2008.43 0.132 0.158 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.92 0.01519
G N1 APARTMENT 1200.85 1441.02 0.094 0.113 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.82 0.01519
G N2 APARTMENT 1193.30 1431.96 0.094 0.113 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.82 0.01519
G S1 APARTMENT 1125.67 1350.81 0.088 0.106 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.87 0.01519
G S2 APARTMENT 1154.15 1384.98 0.091 0.109 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.87 0.01519
M SW APARTMENT 5035.70 6042.84 0.396 0.475 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 34.33 0.01519
M NW APARTMENT 5152.73 6183.27 0.405 0.486 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.83 0.01519
M SE APARTMENT 4244.81 5093.77 0.334 0.400 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 33.68 0.01519
M NE APARTMENT 4198.02 5037.62 0.330 0.396 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.92 0.01519
M N1 APARTMENT 3067.79 3681.35 0.241 0.289 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.20 0.01519
M N2 APARTMENT 3055.64 3666.77 0.240 0.288 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.20 0.01519
M S1 APARTMENT 2933.69 3520.43 0.231 0.277 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.87 0.01519
M S2 APARTMENT 2942.19 3530.63 0.231 0.277 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.87 0.01519
T SW APARTMENT 3430.62 4116.74 0.270 0.324 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 34.99 0.01519
T NW APARTMENT 3432.67 4119.20 0.270 0.324 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 34.33 0.01519
T SE APARTMENT 2965.02 3558.02 0.233 0.280 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 36.00 0.01519
T NE APARTMENT 2807.38 3368.85 0.221 0.265 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.00 0.01519
T N1 APARTMENT 2231.10 2677.32 0.175 0.210 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 36.00 0.01519
T N2 APARTMENT 2232.92 2679.50 0.175 0.211 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 36.00 0.01519
T S1 APARTMENT 2375.53 2850.63 0.187 0.224 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 36.00 0.01519
T S2 APARTMENT 2380.22 2856.26 0.187 0.224 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 36.00 0.01519


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1179.25 1415.10 0.034 0.041 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G NW APARTMENT 1194.80 1433.76 0.034 0.041 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
OFFICE 2437.60 2925.12 0.068 0.081 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G NE APARTMENT 1194.80 1433.76 0.034 0.041 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G N1 APARTMENT 680.87 817.05 0.020 0.026 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G N2 APARTMENT 680.87 817.05 0.020 0.026 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G S1 APARTMENT 668.06 801.68 0.019 0.026 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -1.60 0.00331
G S2 APARTMENT 748.54 898.25 0.022 0.026 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M SW APARTMENT 2312.28 2774.73 0.067 0.080 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M NW APARTMENT 2349.90 2819.88 0.068 0.081 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M SE APARTMENT 2312.28 2774.73 0.067 0.080 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M NE APARTMENT 2349.90 2819.88 0.068 0.081 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M N1 APARTMENT 1103.19 1323.83 0.032 0.052 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M N2 APARTMENT 1103.19 1323.83 0.032 0.052 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M S1 APARTMENT 1066.76 1280.11 0.031 0.052 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
M S2 APARTMENT 1066.76 1280.11 0.031 0.052 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T SW APARTMENT 2025.32 2430.38 0.058 0.070 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T NW APARTMENT 2046.25 2455.50 0.059 0.071 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T SE APARTMENT 2025.32 2430.38 0.058 0.070 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T NE APARTMENT 2046.25 2455.50 0.059 0.071 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T N1 APARTMENT 1379.96 1655.95 0.040 0.048 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T N2 APARTMENT 1379.96 1655.95 0.040 0.048 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T S1 APARTMENT 1358.61 1630.33 0.039 0.047 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331
T S2 APARTMENT 1358.61 1630.33 0.039 0.047 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -1.60 0.00331


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.19 0.19 0.04 0.04
SPLIT GNW 0.20 0.20 0.04 0.04
SPLIT OFFICE 0.48 0.48 0.08 0.08
SPLIT GNE 0.16 0.16 0.04 0.04
SPLIT GN1 0.11 0.11 0.03 0.03
SPLIT GN2 0.11 0.11 0.03 0.03
SPLIT GS1 0.11 0.11 0.03 0.03
SPLIT GS2 0.11 0.11 0.03 0.03
SPLIT MSW 0.47 0.47 0.08 0.08
SPLIT MNW 0.49 0.49 0.08 0.08
SPLIT MSE 0.40 0.40 0.08 0.08
SPLIT MNE 0.40 0.40 0.08 0.08
SPLIT MN1 0.29 0.29 0.05 0.05
SPLIT MN2 0.29 0.29 0.05 0.05
SPLIT MS1 0.28 0.28 0.05 0.05
SPLIT MS2 0.28 0.28 0.05 0.05
SPLIT TSW 0.32 0.32 0.07 0.07
SPLIT TNW 0.32 0.32 0.07 0.07
SPLIT TSE 0.28 0.28 0.07 0.07
SPLIT TNE 0.26 0.26 0.07 0.07
SPLIT TN1 0.21 0.21 0.05 0.05
SPLIT TN2 0.21 0.21 0.05 0.05
SPLIT TS1 0.22 0.22 0.05 0.05
SPLIT TS2 0.22 0.22 0.05 0.05



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4964.25 6042.75 2762.00
G NW APARTMENT 4910.00 6358.00 2903.75
OFFICE 899.00 939.50 7.75
G NE APARTMENT 4902.75 6248.75 2789.50
G N1 APARTMENT 4810.00 6632.75 3019.50
G N2 APARTMENT 4807.50 6631.00 3014.50
G S1 APARTMENT 4836.00 6163.00 2744.25
G S2 APARTMENT 4869.25 5954.00 2570.50
M SW APARTMENT 6088.50 2645.75 879.75
M NW APARTMENT 5871.00 3254.50 938.25
M SE APARTMENT 6049.25 2677.75 858.00
M NE APARTMENT 5833.00 3300.75 940.25
M N1 APARTMENT 5865.25 2954.75 734.25
M N2 APARTMENT 5862.75 2963.00 731.25
M S1 APARTMENT 6105.25 2107.75 613.00
M S2 APARTMENT 6101.75 2116.75 615.50
T SW APARTMENT 6053.00 3715.50 1629.25
T NW APARTMENT 5915.25 4098.00 1752.25
T SE APARTMENT 6024.75 3742.00 1613.50
T NE APARTMENT 5853.50 4125.25 1719.25
T N1 APARTMENT 5789.50 3922.25 1460.00
T N2 APARTMENT 5786.50 3927.25 1463.00
T S1 APARTMENT 5998.75 3431.25 1383.50
T S2 APARTMENT 5997.00 3439.25 1387.00
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6597.75 6736.00 3338.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.75 0.00 0.75 0.00
G NW APARTMENT 1.50 0.25 1.50 0.25
OFFICE 1.00 30.75 0.00 0.00
G NE APARTMENT 3.00 0.00 3.00 0.00
G N1 APARTMENT 3.75 0.50 3.75 0.50
G N2 APARTMENT 5.50 0.25 5.50 0.25
G S1 APARTMENT 1.00 0.50 1.00 0.50
G S2 APARTMENT 2.25 2.75 2.25 2.75
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 0.00 0.00 0.00
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 1.00 0.00 1.00 0.00
M N2 APARTMENT 0.25 0.00 0.25 0.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.50 0.00 0.50 0.00
T SW APARTMENT 2.75 0.00 2.75 0.00
T NW APARTMENT 4.00 0.25 4.00 0.25
T SE APARTMENT 3.25 0.00 3.25 0.00
T NE APARTMENT 3.75 0.00 3.75 0.00
T N1 APARTMENT 0.25 0.00 0.25 0.00
T N2 APARTMENT 0.00 0.00 0.00 0.00
T S1 APARTMENT 1.00 0.00 1.00 0.00
T S2 APARTMENT 1.25 0.00 1.25 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 21.25 34.75 20.25 4.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.369 0.151 0.000 0.096
G NW APARTMENT 1.71 2.50 268.97 0.356 0.151 0.000 0.088
OFFICE 0.94 1.00 268.97 0.521 0.189 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.355 0.151 0.000 0.088
G N1 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.087
G N2 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.087
G S1 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.096
G S2 APARTMENT 1.71 2.50 268.97 0.356 0.091 0.000 0.096
M SW APARTMENT 1.71 2.50 268.97 0.356 0.217 0.000 0.122
M NW APARTMENT 1.71 2.50 268.97 0.356 0.217 0.000 0.111
M SE APARTMENT 1.71 2.50 268.97 0.356 0.217 0.000 0.121
M NE APARTMENT 1.71 2.50 268.97 0.356 0.217 0.000 0.111
M N1 APARTMENT 1.71 2.50 268.97 0.356 0.131 0.000 0.111
M N2 APARTMENT 1.71 2.50 268.97 0.356 0.131 0.000 0.111
M S1 APARTMENT 1.71 2.50 268.97 0.356 0.131 0.000 0.122
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.131 0.000 0.122
T SW APARTMENT 1.71 2.50 268.97 0.356 0.287 0.000 0.149
T NW APARTMENT 1.71 2.50 268.97 0.356 0.287 0.000 0.134
T SE APARTMENT 1.71 2.50 268.97 0.356 0.287 0.000 0.149
T NE APARTMENT 1.71 2.50 268.97 0.355 0.287 0.000 0.134
T N1 APARTMENT 1.71 2.50 268.97 0.356 0.173 0.000 0.134
T N2 APARTMENT 1.71 2.50 268.97 0.356 0.173 0.000 0.134
T S1 APARTMENT 1.71 2.50 268.97 0.356 0.173 0.000 0.149
T S2 APARTMENT 1.71 2.50 268.97 0.356 0.173 0.000 0.149
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.353 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.499 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.361 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.362 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 329.84 0.00 01-JAN-00:15 30404.64 01-JAN-08:30
WaterSystems:Electricity 329.84 0.00 01-JAN-00:15 30404.64 01-JAN-08:30
Water Heater:WaterSystems:Electricity 329.84 0.00 01-JAN-00:15 30404.64 01-JAN-08:30
Fans:Electricity 235.20 7458.16 01-JAN-08:15 7458.16 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
ElectricityPurchased:Plant 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
Cogeneration:ElectricityPurchased 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
ElectricityNet:Plant 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
Cogeneration:ElectricityNet 1516.74 20570.77 01-JAN-03:15 89231.93 04-AUG-16:30
ExteriorLights:Electricity 40.12 0.00 01-JAN-07:30 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.12 0.00 01-JAN-07:30 2553.00 01-JAN-00:15
Electricity:HVAC 510.67 7458.16 01-JAN-08:15 40451.09 04-AUG-16:15
General:Fans:Electricity 235.20 7458.16 01-JAN-08:15 7458.16 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 275.47 0.00 01-JAN-00:15 32992.93 04-AUG-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 58.77 0.00 01-JAN-12:15 73740.65 11-FEB-05:00
Gas:HVAC 58.77 0.00 01-JAN-12:15 73740.65 11-FEB-05:00
Heating:Gas 58.77 0.00 01-JAN-12:15 73740.65 11-FEB-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1848.83 1564.96 08-APR-10:00 195262.68 04-AUG-16:15
EnergyTransfer:Building 676.94 1554.52 14-JAN-14:30 71756.64 04-AUG-16:15
EnergyTransfer:Zone:G SW APARTMENT 14.87 0.01 20-FEB-03:15 2580.86 25-SEP-15:15
Heating:EnergyTransfer 36.04 0.00 01-JAN-18:30 39736.99 11-FEB-04:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 1.43 0.00 01-JAN-08:00 1532.97 11-FEB-04:00
Cooling:EnergyTransfer 640.89 0.00 22-JAN-07:15 71756.64 04-AUG-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 13.45 0.00 01-JAN-00:15 2580.86 25-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 13.45 0.02 14-JAN-22:45 2407.60 04-AUG-16:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 2.29 0.00 01-JAN-16:45 1589.92 11-FEB-02:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 11.16 0.00 01-JAN-00:15 2407.60 04-AUG-16:30
EnergyTransfer:Zone:OFFICE 31.82 0.04 30-MAR-00:15 4888.49 13-AUG-10:45
Heating:EnergyTransfer:Zone:OFFICE 5.92 0.00 01-JAN-00:15 2130.13 12-FEB-07:15
Cooling:EnergyTransfer:Zone:OFFICE 25.90 0.00 01-JAN-11:30 4888.49 13-AUG-10:45
EnergyTransfer:Zone:G NE APARTMENT 13.23 0.01 11-NOV-10:15 1767.15 04-AUG-16:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 2.05 0.00 01-JAN-09:15 1550.71 11-FEB-02:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 11.17 0.00 01-JAN-00:15 1767.15 04-AUG-16:15
EnergyTransfer:Zone:G N1 APARTMENT 9.42 0.01 10-APR-17:00 1340.19 04-AUG-17:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.91 0.00 01-JAN-10:00 909.11 11-FEB-04:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 8.51 0.00 01-JAN-00:15 1340.19 04-AUG-17:30
EnergyTransfer:Zone:G N2 APARTMENT 9.43 0.01 18-MAY-10:30 1333.19 04-AUG-17:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.92 0.00 01-JAN-10:00 911.30 11-FEB-04:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 8.51 0.00 01-JAN-00:15 1333.19 04-AUG-17:30
EnergyTransfer:Zone:G S1 APARTMENT 11.27 0.03 26-MAY-05:30 1735.97 25-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.40 0.00 01-JAN-00:15 785.14 11-FEB-04:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 10.87 0.00 01-JAN-03:30 1735.97 25-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 11.92 0.01 26-MAY-05:45 1758.21 25-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.41 0.00 01-JAN-00:15 797.52 11-FEB-05:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 11.51 0.00 01-JAN-03:15 1758.21 25-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 51.57 0.24 15-JAN-02:15 6189.89 25-SEP-15:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.59 0.00 01-JAN-00:15 2562.73 11-FEB-05:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 50.97 0.00 03-JAN-04:45 6189.89 25-SEP-15:15
EnergyTransfer:Zone:M NW APARTMENT 44.29 0.03 10-NOV-04:00 5862.47 04-AUG-16:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 1.53 0.00 01-JAN-00:15 3089.14 11-FEB-05:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 42.75 0.00 01-JAN-01:30 5862.47 04-AUG-16:30
EnergyTransfer:Zone:M SE APARTMENT 51.58 0.09 06-JAN-11:30 5332.04 25-SEP-13:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.59 0.00 01-JAN-00:15 2635.52 11-FEB-05:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 50.99 0.00 03-JAN-08:00 5332.04 25-SEP-13:30
EnergyTransfer:Zone:M NE APARTMENT 44.29 0.13 23-JAN-13:00 4573.51 04-AUG-16:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 1.44 0.00 01-JAN-00:15 3078.60 11-FEB-04:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 42.85 0.00 01-JAN-01:15 4573.51 04-AUG-16:15
EnergyTransfer:Zone:M N1 APARTMENT 37.50 0.11 15-FEB-16:00 3375.67 04-AUG-17:15
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.20 0.00 01-JAN-00:15 1037.66 11-FEB-05:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 37.30 0.00 01-JAN-13:00 3375.67 04-AUG-17:15
EnergyTransfer:Zone:M N2 APARTMENT 37.48 0.01 27-JAN-18:45 3364.51 04-AUG-17:15
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.20 0.00 01-JAN-00:15 1057.14 11-FEB-05:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 37.28 0.00 01-JAN-13:00 3364.51 04-AUG-17:15
EnergyTransfer:Zone:M S1 APARTMENT 46.21 0.83 06-FEB-04:30 4593.78 31-OCT-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.03 0.00 01-JAN-00:15 829.19 22-JAN-07:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 46.18 0.00 21-JAN-01:15 4593.78 31-OCT-13:30
EnergyTransfer:Zone:M S2 APARTMENT 46.18 0.21 10-FEB-02:00 4600.23 31-OCT-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.03 0.00 01-JAN-00:15 830.16 22-JAN-07:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 46.15 0.00 21-JAN-01:15 4600.23 31-OCT-13:30
EnergyTransfer:Zone:T SW APARTMENT 29.27 0.01 19-MAR-19:15 4043.28 25-SEP-15:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 2.62 0.00 01-JAN-09:00 2745.21 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 26.65 0.00 01-JAN-00:15 4043.28 25-SEP-15:15
EnergyTransfer:Zone:T NW APARTMENT 26.87 0.08 07-MAR-07:45 3961.35 04-AUG-16:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 3.63 0.00 01-JAN-18:30 2792.39 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 23.23 0.00 01-JAN-00:15 3961.35 04-AUG-16:15
EnergyTransfer:Zone:T SE APARTMENT 28.89 0.01 03-DEC-21:15 3576.25 25-SEP-13:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 2.44 0.00 01-JAN-08:30 2698.44 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 26.46 0.00 01-JAN-00:15 3576.25 25-SEP-13:30
EnergyTransfer:Zone:T NE APARTMENT 26.34 0.00 11-DEC-12:45 3204.62 04-AUG-16:15
Heating:EnergyTransfer:Zone:T NE APARTMENT 3.32 0.00 01-JAN-09:30 2724.42 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 23.02 0.00 01-JAN-00:15 3204.62 04-AUG-16:15
EnergyTransfer:Zone:T N1 APARTMENT 21.23 0.11 19-FEB-03:45 2558.68 04-AUG-16:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 1.57 0.00 01-JAN-10:00 1780.35 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 19.66 0.00 01-JAN-00:15 2558.68 04-AUG-16:15
EnergyTransfer:Zone:T N2 APARTMENT 21.24 0.05 25-NOV-03:45 2549.02 04-AUG-16:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 1.58 0.00 01-JAN-10:00 1783.82 11-FEB-04:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 19.65 0.00 01-JAN-00:15 2549.02 04-AUG-16:15
EnergyTransfer:Zone:T S1 APARTMENT 24.30 0.01 17-FEB-21:15 3030.08 25-SEP-14:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.95 0.00 01-JAN-00:15 1686.21 11-FEB-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 23.34 0.00 01-JAN-01:30 3030.08 25-SEP-14:00
EnergyTransfer:Zone:T S2 APARTMENT 24.30 0.01 23-DEC-08:00 3033.48 25-SEP-14:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.96 0.00 01-JAN-00:15 1688.56 11-FEB-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 23.34 0.00 01-JAN-01:30 3033.48 25-SEP-14:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1171.90 0.00 06-JAN-10:30 123506.04 04-AUG-16:15
HeatingCoils:EnergyTransfer 47.02 0.00 01-JAN-12:15 58992.52 11-FEB-05:00
CoolingCoils:EnergyTransfer 1124.88 0.00 01-JAN-00:15 123506.04 04-AUG-16:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 1.426 -13.445 0.000 0.000 3.697 1.087 12.213 13.574 0.000 0.725 0.000 0.000 -4.478 0.000 -2.794 -12.004
G NW APARTMENT 2.289 -11.157 0.000 0.000 3.714 1.087 12.213 9.096 0.000 0.719 0.000 0.000 -4.627 0.000 -2.628 -10.705
OFFICE 5.925 -25.897 0.000 0.000 0.518 26.452 9.482 12.798 0.000 0.426 0.000 0.000 -5.055 0.000 -2.308 -22.341
G NE APARTMENT 2.054 -11.173 0.000 0.000 3.725 1.087 12.213 8.816 0.000 0.720 0.000 0.000 -4.420 0.000 -2.592 -10.429
G N1 APARTMENT 0.914 -8.506 0.000 0.000 3.727 1.087 12.213 3.987 0.000 0.465 0.000 0.000 -2.816 0.000 -1.795 -9.275
G N2 APARTMENT 0.917 -8.508 0.000 0.000 3.727 1.087 12.213 3.987 0.000 0.465 0.000 0.000 -2.814 0.000 -1.793 -9.280
G S1 APARTMENT 0.400 -10.865 0.000 0.000 3.701 1.087 12.213 8.503 0.000 0.465 0.000 0.000 -2.682 0.000 -1.978 -10.844
G S2 APARTMENT 0.405 -11.514 0.000 0.000 3.698 1.087 12.213 8.490 0.000 0.465 0.000 0.000 -2.694 0.000 -1.989 -10.162
M SW APARTMENT 0.594 -50.971 0.000 0.000 3.596 1.087 12.213 12.990 0.000 1.026 28.815 0.000 -5.153 0.000 -4.196 0.000
M NW APARTMENT 1.535 -42.751 0.000 0.000 3.624 1.087 12.213 8.626 0.000 1.015 23.965 0.000 -5.298 0.000 -4.015 -0.000
M SE APARTMENT 0.589 -50.986 0.000 0.000 3.603 1.087 12.213 12.785 0.000 1.026 28.900 0.000 -5.039 0.000 -4.177 0.000
M NE APARTMENT 1.443 -42.847 0.000 0.000 3.633 1.087 12.213 8.323 0.000 1.015 24.186 0.000 -5.072 0.000 -3.980 -0.000
M N1 APARTMENT 0.201 -37.301 0.000 0.000 3.614 1.087 12.213 3.700 0.000 0.643 21.992 0.000 -3.312 0.000 -2.836 0.000
M N2 APARTMENT 0.204 -37.279 0.000 0.000 3.614 1.087 12.213 3.700 0.000 0.643 21.961 0.000 -3.309 0.000 -2.834 0.000
M S1 APARTMENT 0.030 -46.176 0.000 0.000 3.578 1.087 12.213 8.112 0.000 0.654 26.638 0.000 -3.131 0.000 -3.006 0.000
M S2 APARTMENT 0.032 -46.152 0.000 0.000 3.578 1.087 12.213 8.112 0.000 0.654 26.610 0.000 -3.129 0.000 -3.005 0.000
T SW APARTMENT 2.622 -26.649 0.000 0.000 3.640 1.087 12.213 12.688 0.000 1.358 3.133 0.000 -4.911 0.000 -5.181 -0.000
T NW APARTMENT 3.634 -23.234 0.000 0.000 3.656 1.087 12.213 8.385 0.000 1.341 2.977 0.000 -5.076 0.000 -4.983 -0.000
T SE APARTMENT 2.440 -26.454 0.000 0.000 3.647 1.087 12.213 12.488 0.000 1.358 3.193 0.000 -4.807 0.000 -5.164 -0.000
T NE APARTMENT 3.321 -23.016 0.000 0.000 3.667 1.087 12.213 8.104 0.000 1.341 3.104 0.000 -4.872 0.000 -4.948 -0.000
T N1 APARTMENT 1.574 -19.660 0.000 0.000 3.652 1.087 12.213 3.606 0.000 0.854 3.258 0.000 -3.142 0.000 -3.441 -0.000
T N2 APARTMENT 1.582 -19.654 0.000 0.000 3.653 1.087 12.213 3.605 0.000 0.854 3.240 0.000 -3.139 0.000 -3.441 -0.000
T S1 APARTMENT 0.953 -23.342 0.000 0.000 3.627 1.087 12.213 7.941 0.000 0.872 3.278 0.000 -2.984 0.000 -3.644 -0.000
T S2 APARTMENT 0.959 -23.341 0.000 0.000 3.628 1.087 12.213 7.940 0.000 0.872 3.269 0.000 -2.982 0.000 -3.643 -0.001
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.210 0.000 0.090 0.000 0.000 -0.568 0.000 -0.814 -13.500
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.745 0.000 2.632 0.001 0.000 -1.274 0.000 -11.633 -11.531
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.223 0.000 0.082 0.000 0.000 -0.624 0.000 -0.673 -13.590
Total Facility 36.044 -640.878 0.000 0.000 84.516 95.189 296.854 201.536 0.000 22.779 228.519 0.000 -97.407 0.000 -93.491 -133.663


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 25-SEP-15:15 0.00 -2580.66 0.00 0.00 48.90 45.40 470.90 2624.98 0.00 174.38 0.00 0.00 0.00 0.00 0.00 -783.90
G NW APARTMENT 04-AUG-16:23 0.00 -2408.16 0.00 0.00 84.76 64.86 588.62 1937.71 0.00 315.98 0.00 0.00 0.00 0.00 0.00 -583.76
OFFICE 10-SEP-06:01 0.00 -7376.64 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 6994.50 0.00 -249.43 0.00 -78.88 0.00
G NE APARTMENT 04-AUG-16:04 0.00 -1769.62 0.00 0.00 84.76 64.86 588.62 847.73 0.00 328.47 0.00 0.00 0.00 0.00 0.00 -144.82
G N1 APARTMENT 04-AUG-17:05 0.00 -1341.64 0.00 0.00 141.81 87.56 588.62 517.30 0.00 167.91 0.00 0.00 0.00 0.00 0.00 -161.57
G N2 APARTMENT 04-AUG-17:05 0.00 -1334.45 0.00 0.00 141.81 87.56 588.62 517.41 0.00 167.91 0.00 0.00 0.00 0.00 0.00 -168.86
G S1 APARTMENT 25-SEP-13:30 0.00 -1735.83 0.00 0.00 40.75 12.97 382.60 1714.09 0.00 113.35 0.00 0.00 0.00 0.00 0.00 -527.93
G S2 APARTMENT 25-SEP-13:30 0.00 -1758.08 0.00 0.00 40.75 12.97 382.60 1713.65 0.00 113.35 0.00 0.00 0.00 0.00 0.00 -505.25
M SW APARTMENT 25-SEP-15:15 0.00 -6189.42 0.00 0.00 48.90 45.40 470.90 2592.89 0.00 250.12 2781.22 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 04-AUG-16:23 0.00 -5864.23 0.00 0.00 84.76 64.86 588.62 1919.84 0.00 453.36 2752.79 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 25-SEP-13:30 0.00 -5331.87 0.00 0.00 40.75 12.97 382.60 2006.19 0.00 269.47 2619.88 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 04-AUG-16:04 0.00 -4578.80 0.00 0.00 84.76 64.86 588.62 841.58 0.00 471.29 2527.68 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 04-AUG-17:05 0.00 -3380.32 0.00 0.00 141.82 87.56 588.62 511.55 0.00 240.87 1809.90 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 04-AUG-17:05 0.00 -3371.31 0.00 0.00 141.82 87.56 588.62 511.61 0.00 240.87 1800.83 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 31-OCT-13:30 0.00 -4593.58 0.00 0.00 40.75 12.97 382.60 1977.63 0.00 104.92 2074.70 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 31-OCT-13:30 0.00 -4600.04 0.00 0.00 40.75 12.97 382.60 1977.59 0.00 104.92 2081.20 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 25-SEP-15:15 0.00 -4042.99 0.00 0.00 48.90 45.40 470.90 2535.16 0.00 329.57 613.06 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 04-AUG-16:04 0.00 -3966.42 0.00 0.00 84.77 64.86 588.62 1866.23 0.00 621.41 740.54 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 25-SEP-13:30 0.00 -3576.14 0.00 0.00 40.75 12.97 382.60 1961.53 0.00 354.89 823.39 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 04-AUG-16:04 0.00 -3209.90 0.00 0.00 84.77 64.86 588.62 813.67 0.00 621.40 1036.58 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 04-AUG-16:04 0.00 -2561.85 0.00 0.00 84.76 64.86 588.62 498.04 0.00 374.82 950.74 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 04-AUG-16:04 0.00 -2552.15 0.00 0.00 84.76 64.86 588.62 498.16 0.00 374.82 940.93 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 25-SEP-14:00 0.00 -3029.97 0.00 0.00 40.75 12.97 382.60 1584.86 0.00 230.88 777.91 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 25-SEP-14:00 0.00 -3033.37 0.00 0.00 40.75 12.97 382.60 1584.79 0.00 230.88 781.37 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-AUG-16:04 0.00 -71845.19 0.00 0.00 1949.54 3295.01 14142.04 22575.99 0.00 13070.12 16812.49 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-FEB-04:00 1532.81 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 232.76 0.00 -1078.68 0.00 -1106.72 0.00
G NW APARTMENT 11-FEB-02:00 1589.70 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 172.77 0.00 -1041.08 0.00 -1158.88 0.00
OFFICE 05-FEB-07:01 3618.01 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -462.75 0.00 -310.73 -3554.99
G NE APARTMENT 12-OCT-06:01 1826.11 0.00 0.00 0.00 163.00 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -622.72 0.00 -167.76 -1623.39
G N1 APARTMENT 11-FEB-04:00 909.01 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 7.64 0.00 -668.29 0.00 -668.19 0.00
G N2 APARTMENT 11-FEB-04:00 911.20 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 5.37 0.00 -668.21 0.00 -668.19 0.00
G S1 APARTMENT 27-DEC-08:01 1126.89 0.00 0.00 0.00 74.05 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -207.00 0.00 -112.82 -1289.06
G S2 APARTMENT 14-JAN-07:01 1372.33 0.00 0.00 0.00 162.83 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -242.23 0.00 -89.69 -1628.00
M SW APARTMENT 18-JAN-07:01 3273.20 0.00 0.00 0.00 162.56 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -679.21 0.00 -583.27 -2598.03
M NW APARTMENT 11-FEB-05:00 3088.84 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1194.81 0.00 -1504.39 -822.44
M SE APARTMENT 11-FEB-05:00 2635.26 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1132.29 0.00 -1504.44 -431.33
M NE APARTMENT 11-FEB-04:00 3078.27 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -1123.17 0.00 -1590.67 -784.26
M N1 APARTMENT 25-JAN-08:01 1787.56 0.00 0.00 0.00 74.04 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -401.29 0.00 -431.91 -1436.35
M N2 APARTMENT 19-JAN-08:14 1555.47 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -423.75 0.00 -195.76 -1417.88
M S1 APARTMENT 22-JAN-07:00 829.17 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -467.75 0.00 -492.96 -421.39
M S2 APARTMENT 22-JAN-07:00 830.14 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -467.74 0.00 -492.96 -422.37
T SW APARTMENT 11-FEB-04:00 2744.92 0.00 0.00 0.00 190.07 6.49 223.68 0.00 0.00 0.00 24.63 0.00 -1095.81 0.00 -2093.96 0.00
T NW APARTMENT 11-FEB-04:00 2792.10 0.00 0.00 0.00 190.59 6.49 223.68 0.00 0.00 0.00 2.55 0.00 -1130.34 0.00 -2085.06 0.00
T SE APARTMENT 11-FEB-04:00 2698.16 0.00 0.00 0.00 190.38 6.49 223.68 0.00 0.00 0.00 35.46 0.00 -1065.77 0.00 -2088.39 0.00
T NE APARTMENT 11-FEB-04:00 2724.14 0.00 0.00 0.00 191.37 6.49 223.68 0.00 0.00 0.00 27.77 0.00 -1098.57 0.00 -2074.86 0.00
T N1 APARTMENT 17-DEC-07:01 1798.43 0.00 0.00 0.00 162.69 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -338.85 0.00 -27.33 -2019.71
T N2 APARTMENT 17-DEC-07:01 1806.43 0.00 0.00 0.00 162.70 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -338.81 0.00 -27.33 -2027.76
T S1 APARTMENT 11-FEB-05:00 1686.05 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -673.10 0.00 -1202.05 -243.70
T S2 APARTMENT 11-FEB-05:00 1688.40 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -673.04 0.00 -1202.05 -246.10
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-FEB-04:00 39317.28 0.00 0.00 0.00 4366.71 1952.47 5387.04 0.00 0.00 0.00 2068.84 0.00 -21633.16 0.00 -31459.18 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Sec1.1A-General Information

Data
Weather File Houston Bush Intercontinental TX USA TMY3 WMO#=722430
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 20.25
Number of hours cooling loads not met 4.00
Number of hours not met 24.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4276.26 0.00 0.00 0.00 0.00
Exterior Lighting 40.12 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 58.77 73740.65 0.00 0.00
Space Cooling 275.47 32724.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 235.20 7458.16 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 329.84 18142.01 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1516.74   58.77   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1516.74
Natural Gas 0.00 58.77
Additional 0.00 0.00
Total 517.65 1575.52


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 87.88
Fans-Interior 75.03
Service Water Heating 105.22
Receptacle Equipment 165.14
Miscellaneous 12.80
Subtotal 483.87


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 18.75
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 18.75


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.52
Space Heating 3.73
Space Cooling 17.48
Fans-Interior 14.93
Service Water Heating 20.94
Receptacle Equipment 32.86
Miscellaneous 2.55



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.194279
G NW APARTMENT DIRECT AIR 0.199694
OFFICE DIRECT AIR 0.483076
G NE APARTMENT DIRECT AIR 0.157823
G N1 APARTMENT DIRECT AIR 0.113225
G N2 APARTMENT DIRECT AIR 0.112513
G S1 APARTMENT DIRECT AIR 0.106141
G S2 APARTMENT DIRECT AIR 0.108826
M SW APARTMENT DIRECT AIR 0.474841
M NW APARTMENT DIRECT AIR 0.485857
M SE APARTMENT DIRECT AIR 0.400279
M NE APARTMENT DIRECT AIR 0.395868
M N1 APARTMENT DIRECT AIR 0.289257
M N2 APARTMENT DIRECT AIR 0.288112
M S1 APARTMENT DIRECT AIR 0.276626
M S2 APARTMENT DIRECT AIR 0.277427
T SW APARTMENT DIRECT AIR 0.323518
T NW APARTMENT DIRECT AIR 0.323698
T SE APARTMENT DIRECT AIR 0.279611
T NE APARTMENT DIRECT AIR 0.264744
T N1 APARTMENT DIRECT AIR 0.210383
T N2 APARTMENT DIRECT AIR 0.210555
T S1 APARTMENT DIRECT AIR 0.224002
T S2 APARTMENT DIRECT AIR 0.224444


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.194279
SPLIT GNW MAIN BRANCH 0.199694
SPLIT OFFICE MAIN BRANCH 0.483076
SPLIT GNE MAIN BRANCH 0.157823
SPLIT GN1 MAIN BRANCH 0.113225
SPLIT GN2 MAIN BRANCH 0.112513
SPLIT GS1 MAIN BRANCH 0.106141
SPLIT GS2 MAIN BRANCH 0.108826
SPLIT MSW MAIN BRANCH 0.474841
SPLIT MNW MAIN BRANCH 0.485857
SPLIT MSE MAIN BRANCH 0.400279
SPLIT MNE MAIN BRANCH 0.395868
SPLIT MN1 MAIN BRANCH 0.289257
SPLIT MN2 MAIN BRANCH 0.288112
SPLIT MS1 MAIN BRANCH 0.276626
SPLIT MS2 MAIN BRANCH 0.277427
SPLIT TSW MAIN BRANCH 0.323518
SPLIT TNW MAIN BRANCH 0.323698
SPLIT TSE MAIN BRANCH 0.279611
SPLIT TNE MAIN BRANCH 0.264744
SPLIT TN1 MAIN BRANCH 0.210383
SPLIT TN2 MAIN BRANCH 0.210555
SPLIT TS1 MAIN BRANCH 0.224002
SPLIT TS2 MAIN BRANCH 0.224444


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.194279
SPLIT GNW 0.199694
SPLIT OFFICE 0.483076
SPLIT GNE 0.157823
SPLIT GN1 0.113225
SPLIT GN2 0.112513
SPLIT GS1 0.106141
SPLIT GS2 0.108826
SPLIT MSW 0.474841
SPLIT MNW 0.485857
SPLIT MSE 0.400279
SPLIT MNE 0.395868
SPLIT MN1 0.289257
SPLIT MN2 0.288112
SPLIT MS1 0.276626
SPLIT MS2 0.277427
SPLIT TSW 0.323518
SPLIT TNW 0.323698
SPLIT TSE 0.279611
SPLIT TNE 0.264744
SPLIT TN1 0.210383
SPLIT TN2 0.210555
SPLIT TS1 0.224002
SPLIT TS2 0.224444


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.194279 0.026898
SPLIT GNW OA CONTROLLER 0.199694 0.025953
SPLIT OFFICE OA CONTROLLER 0.483076 0.038104
SPLIT GNE OA CONTROLLER 0.157823 0.025953
SPLIT GN1 OA CONTROLLER 0.113225 0.025953
SPLIT GN2 OA CONTROLLER 0.112513 0.025953
SPLIT GS1 OA CONTROLLER 0.106141 0.025953
SPLIT GS2 OA CONTROLLER 0.108826 0.025953
SPLIT MSW OA CONTROLLER 0.474841 0.051906
SPLIT MNW OA CONTROLLER 0.485857 0.051906
SPLIT MSE OA CONTROLLER 0.400279 0.051906
SPLIT MNE OA CONTROLLER 0.395868 0.051906
SPLIT MN1 OA CONTROLLER 0.289257 0.051906
SPLIT MN2 OA CONTROLLER 0.288112 0.051906
SPLIT MS1 OA CONTROLLER 0.276626 0.051906
SPLIT MS2 OA CONTROLLER 0.277427 0.051906
SPLIT TSW OA CONTROLLER 0.323518 0.025953
SPLIT TNW OA CONTROLLER 0.323698 0.025953
SPLIT TSE OA CONTROLLER 0.279611 0.025953
SPLIT TNE OA CONTROLLER 0.264744 0.025953
SPLIT TN1 OA CONTROLLER 0.210383 0.025953
SPLIT TN2 OA CONTROLLER 0.210555 0.025953
SPLIT TS1 OA CONTROLLER 0.224002 0.025953
SPLIT TS2 OA CONTROLLER 0.224444 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.194279 4135.87 0.716885
SPLIT GNW COOLING COIL 0.199694 4174.00 0.722169
SPLIT OFFICE COOLING COIL 0.483076 8562.96 0.774339
SPLIT GNE COOLING COIL 0.157823 3429.90 0.711041
SPLIT GN1 COOLING COIL 0.113225 2639.28 0.692088
SPLIT GN2 COOLING COIL 0.112513 2627.29 0.691632
SPLIT GS1 COOLING COIL 0.106141 2635.73 0.676083
SPLIT GS2 COOLING COIL 0.108826 2687.59 0.677434
SPLIT MSW COOLING COIL 0.474841 9801.70 0.725835
SPLIT MNW COOLING COIL 0.485857 9924.36 0.728947
SPLIT MSE COOLING COIL 0.400279 8481.53 0.718224
SPLIT MNE COOLING COIL 0.395868 8320.35 0.720561
SPLIT MN1 COOLING COIL 0.289257 6436.85 0.704490
SPLIT MN2 COOLING COIL 0.288112 6417.69 0.704221
SPLIT MS1 COOLING COIL 0.276626 6468.93 0.691251
SPLIT MS2 COOLING COIL 0.277427 6482.44 0.691461
SPLIT TSW COOLING COIL 0.323518 6450.85 0.736220
SPLIT TNW COOLING COIL 0.323698 6404.44 0.738603
SPLIT TSE COOLING COIL 0.279611 5806.87 0.724051
SPLIT TNE COOLING COIL 0.264744 5557.04 0.720945
SPLIT TN1 COOLING COIL 0.210383 4508.38 0.715002
SPLIT TN2 COOLING COIL 0.210555 4511.11 0.715062
SPLIT TS1 COOLING COIL 0.224002 4736.69 0.718812
SPLIT TS2 COOLING COIL 0.224444 4743.96 0.718938


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.194279 0.194279 0.194279 0.194279 2150.32 4135.87 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.199694 0.199694 0.199694 0.199694 2142.14 4174.00 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.483076 0.483076 0.483076 0.483076 3890.86 8562.96 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.157823 0.157823 0.157823 0.157823 2142.14 3429.90 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.113225 0.113225 0.113225 0.113225 1615.05 2639.28 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.112513 0.112513 0.112513 0.112513 1615.05 2627.29 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.106141 0.106141 0.106141 0.106141 1615.05 2635.73 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.108826 0.108826 0.108826 0.108826 1615.05 2687.59 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.474841 0.474841 0.474841 0.474841 4192.75 9801.70 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.485857 0.485857 0.485857 0.485857 4237.24 9924.36 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.400279 0.400279 0.400279 0.400279 4192.75 8481.53 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.395868 0.395868 0.395868 0.395868 4237.24 8320.35 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.289257 0.289257 0.289257 0.289257 3230.10 6436.85 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.288112 0.288112 0.288112 0.288112 3230.10 6417.69 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.276626 0.276626 0.276626 0.276626 3230.10 6468.93 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.277427 0.277427 0.277427 0.277427 3230.10 6482.44 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.323518 0.323518 0.323518 0.323518 3124.18 6450.85 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.323698 0.323698 0.323698 0.323698 3148.92 6404.44 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.279611 0.279611 0.279611 0.279611 3124.18 5806.87 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.264744 0.264744 0.264744 0.264744 3148.92 5557.04 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.210383 0.210383 0.210383 0.210383 2361.06 4508.38 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.210555 0.210555 0.210555 0.210555 2361.06 4511.11 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.224002 0.224002 0.224002 0.224002 2335.82 4736.69 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.224444 0.224444 0.224444 0.224444 2335.82 4743.96 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.194279
SPLIT GNW SUPPLY FAN 0.199694
SPLIT OFFICE SUPPLY FAN 0.483076
SPLIT GNE SUPPLY FAN 0.157823
SPLIT GN1 SUPPLY FAN 0.113225
SPLIT GN2 SUPPLY FAN 0.112513
SPLIT GS1 SUPPLY FAN 0.106141
SPLIT GS2 SUPPLY FAN 0.108826
SPLIT MSW SUPPLY FAN 0.474841
SPLIT MNW SUPPLY FAN 0.485857
SPLIT MSE SUPPLY FAN 0.400279
SPLIT MNE SUPPLY FAN 0.395868
SPLIT MN1 SUPPLY FAN 0.289257
SPLIT MN2 SUPPLY FAN 0.288112
SPLIT MS1 SUPPLY FAN 0.276626
SPLIT MS2 SUPPLY FAN 0.277427
SPLIT TSW SUPPLY FAN 0.323518
SPLIT TNW SUPPLY FAN 0.323698
SPLIT TSE SUPPLY FAN 0.279611
SPLIT TNE SUPPLY FAN 0.264744
SPLIT TN1 SUPPLY FAN 0.210383
SPLIT TN2 SUPPLY FAN 0.210555
SPLIT TS1 SUPPLY FAN 0.224002
SPLIT TS2 SUPPLY FAN 0.224444


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 2150.32
SPLIT GNW HEATING COIL 2142.14
SPLIT OFFICE HEATING COIL 3890.86
SPLIT GNE HEATING COIL 2142.14
SPLIT GN1 HEATING COIL 1615.05
SPLIT GN2 HEATING COIL 1615.05
SPLIT GS1 HEATING COIL 1615.05
SPLIT GS2 HEATING COIL 1615.05
SPLIT MSW HEATING COIL 4192.75
SPLIT MNW HEATING COIL 4237.24
SPLIT MSE HEATING COIL 4192.75
SPLIT MNE HEATING COIL 4237.24
SPLIT MN1 HEATING COIL 3230.10
SPLIT MN2 HEATING COIL 3230.10
SPLIT MS1 HEATING COIL 3230.10
SPLIT MS2 HEATING COIL 3230.10
SPLIT TSW HEATING COIL 3124.18
SPLIT TNW HEATING COIL 3148.92
SPLIT TSE HEATING COIL 3124.18
SPLIT TNE HEATING COIL 3148.92
SPLIT TN1 HEATING COIL 2361.06
SPLIT TN2 HEATING COIL 2361.06
SPLIT TS1 HEATING COIL 2335.82
SPLIT TS2 HEATING COIL 2335.82



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:59

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.28 10.50
February 22.68 12.77
March 23.12 16.20
April 23.82 20.49
May 24.28 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 23.96 20.33
November 23.51 17.10
December 22.67 12.54
     
Annual Sum or Average 23.66 20.36
Minimum of Months 22.28 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.99 10.50
February 22.47 12.77
March 22.95 16.20
April 23.78 20.49
May 24.29 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 23.84 20.33
November 23.22 17.10
December 22.33 12.54
     
Annual Sum or Average 23.54 20.36
Minimum of Months 21.99 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.63 10.50
February 23.20 12.77
March 23.96 16.20
April 25.00 20.49
May 25.80 24.03
June 26.92 27.02
July 27.27 28.27
August 27.07 28.21
September 27.15 26.44
October 25.37 20.33
November 24.49 17.10
December 23.17 12.54
     
Annual Sum or Average 25.18 20.36
Minimum of Months 22.63 10.50
Maximum of Months 27.27 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 10.50
February 22.39 12.77
March 22.87 16.20
April 23.73 20.49
May 24.28 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 23.82 20.33
November 23.15 17.10
December 22.23 12.54
     
Annual Sum or Average 23.50 20.36
Minimum of Months 21.92 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 10.50
February 22.34 12.77
March 22.78 16.20
April 23.66 20.49
May 24.25 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 23.78 20.33
November 23.10 17.10
December 22.21 12.54
     
Annual Sum or Average 23.47 20.36
Minimum of Months 21.91 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 10.50
February 22.33 12.77
March 22.78 16.20
April 23.66 20.49
May 24.25 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 23.77 20.33
November 23.09 17.10
December 22.21 12.54
     
Annual Sum or Average 23.47 20.36
Minimum of Months 21.91 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.27 10.50
February 22.63 12.77
March 23.06 16.20
April 23.74 20.49
May 24.25 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 23.95 20.33
November 23.51 17.10
December 22.66 12.54
     
Annual Sum or Average 23.64 20.36
Minimum of Months 22.27 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.29 10.50
February 22.65 12.77
March 23.08 16.20
April 23.77 20.49
May 24.26 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 23.98 20.33
November 23.53 17.10
December 22.67 12.54
     
Annual Sum or Average 23.66 20.36
Minimum of Months 22.29 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.10 10.50
February 23.41 12.77
March 23.99 16.20
April 24.35 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.36 20.33
November 24.17 17.10
December 23.53 12.54
     
Annual Sum or Average 24.08 20.36
Minimum of Months 23.10 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 10.50
February 23.13 12.77
March 23.80 16.20
April 24.34 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.32 20.33
November 23.97 17.10
December 23.07 12.54
     
Annual Sum or Average 23.93 20.36
Minimum of Months 22.54 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.01 10.50
February 23.35 12.77
March 23.96 16.20
April 24.35 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.35 20.33
November 24.14 17.10
December 23.48 12.54
     
Annual Sum or Average 24.06 20.36
Minimum of Months 23.01 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.41 10.50
February 23.04 12.77
March 23.76 16.20
April 24.33 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.32 20.33
November 23.93 17.10
December 22.95 12.54
     
Annual Sum or Average 23.90 20.36
Minimum of Months 22.41 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.62 10.50
February 23.17 12.77
March 23.90 16.20
April 24.36 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.34 20.33
November 24.09 17.10
December 23.17 12.54
     
Annual Sum or Average 23.97 20.36
Minimum of Months 22.62 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.61 10.50
February 23.16 12.77
March 23.90 16.20
April 24.36 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.34 20.33
November 24.08 17.10
December 23.16 12.54
     
Annual Sum or Average 23.97 20.36
Minimum of Months 22.61 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 10.50
February 23.54 12.77
March 24.13 16.20
April 24.37 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.38 20.33
November 24.27 17.10
December 23.75 12.54
     
Annual Sum or Average 24.16 20.36
Minimum of Months 23.39 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 10.50
February 23.53 12.77
March 24.13 16.20
April 24.37 20.49
May 24.40 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.38 20.33
November 24.27 17.10
December 23.75 12.54
     
Annual Sum or Average 24.15 20.36
Minimum of Months 23.39 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.73 10.50
February 23.19 12.77
March 23.57 16.20
April 24.19 20.49
May 24.38 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.18 20.33
November 23.81 17.10
December 23.11 12.54
     
Annual Sum or Average 23.90 20.36
Minimum of Months 22.73 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.41 10.50
February 23.00 12.77
March 23.45 16.20
April 24.16 20.49
May 24.38 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 24.11 20.33
November 23.62 17.10
December 22.80 12.54
     
Annual Sum or Average 23.80 20.36
Minimum of Months 22.41 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.66 10.50
February 23.13 12.77
March 23.54 16.20
April 24.18 20.49
May 24.38 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 24.16 20.33
November 23.79 17.10
December 23.06 12.54
     
Annual Sum or Average 23.88 20.36
Minimum of Months 22.66 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.29 10.50
February 22.91 12.77
March 23.40 16.20
April 24.15 20.49
May 24.38 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 24.09 20.33
November 23.58 17.10
December 22.67 12.54
     
Annual Sum or Average 23.76 20.36
Minimum of Months 22.29 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.42 10.50
February 23.00 12.77
March 23.48 16.20
April 24.19 20.49
May 24.39 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 24.13 20.33
November 23.65 17.10
December 22.79 12.54
     
Annual Sum or Average 23.81 20.36
Minimum of Months 22.42 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.41 10.50
February 22.99 12.77
March 23.48 16.20
April 24.19 20.49
May 24.39 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.39 26.44
October 24.12 20.33
November 23.65 17.10
December 22.78 12.54
     
Annual Sum or Average 23.80 20.36
Minimum of Months 22.41 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.88 10.50
February 23.26 12.77
March 23.67 16.20
April 24.23 20.49
May 24.39 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.21 20.33
November 23.90 17.10
December 23.23 12.54
     
Annual Sum or Average 23.95 20.36
Minimum of Months 22.88 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.87 10.50
February 23.26 12.77
March 23.67 16.20
April 24.23 20.49
May 24.39 24.03
June 24.40 27.02
July 24.40 28.27
August 24.40 28.21
September 24.40 26.44
October 24.21 20.33
November 23.90 17.10
December 23.23 12.54
     
Annual Sum or Average 23.95 20.36
Minimum of Months 22.87 10.50
Maximum of Months 24.40 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.08 10.50
February 23.90 12.77
March 24.86 16.20
April 26.05 20.49
May 26.72 24.03
June 27.07 27.02
July 27.21 28.27
August 27.20 28.21
September 26.93 26.44
October 25.94 20.33
November 25.12 17.10
December 23.69 12.54
     
Annual Sum or Average 25.65 20.36
Minimum of Months 23.08 10.50
Maximum of Months 27.21 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 10.50
February 21.76 12.77
March 22.82 16.20
April 24.14 20.49
May 25.21 24.03
June 26.78 27.02
July 27.20 28.27
August 27.20 28.21
September 26.88 26.44
October 24.55 20.33
November 23.34 17.10
December 21.74 12.54
     
Annual Sum or Average 24.40 20.36
Minimum of Months 21.06 10.50
Maximum of Months 27.20 28.27



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:59

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.40 10.50
February 24.95 12.77
March 25.82 16.20
April 26.44 20.49
May 26.71 24.03
June 26.87 27.02
July 26.95 28.27
August 26.92 28.21
September 26.86 26.44
October 26.50 20.33
November 26.08 17.10
December 25.03 12.54
     
Annual Sum or Average 26.13 20.36
Minimum of Months 24.40 10.50
Maximum of Months 26.95 28.27



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:59

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.111144E+12 67095.477 29-JAN-18:30 4979.953 26630.920 7458.159 0.000 6081.360 2553.000 0.000 0.000 0.000 0.000 0.000 19392.085 0.000 0.000 0.000
February 0.103031E+12 70613.752 20-FEB-18:45 4979.953 26630.920 7458.159 0.000 8229.468 2553.000 0.000 0.000 0.000 0.000 0.000 20762.252 0.000 0.000 0.000
March 0.116819E+12 76430.720 25-MAR-17:00 4979.953 26630.920 7458.159 0.000 15338.123 0.000 0.000 0.000 0.000 0.000 0.000 22023.565 0.000 0.000 0.000
April 0.120568E+12 76362.300 29-APR-17:30 4979.953 26630.920 7458.159 0.000 19039.471 0.000 0.000 0.000 0.000 0.000 0.000 18253.797 0.000 0.000 0.000
May 0.133896E+12 83167.595 24-MAY-17:15 4979.953 26630.920 7458.159 0.000 23756.175 0.000 0.000 0.000 0.000 0.000 0.000 20342.387 0.000 0.000 0.000
June 0.140555E+12 86985.040 24-JUN-17:30 4979.953 26630.920 7458.159 0.000 25802.448 0.000 0.000 0.000 0.000 0.000 0.000 22113.559 0.000 0.000 0.000
July 0.149146E+12 87017.264 14-JUL-17:30 4979.953 26630.920 7458.159 0.000 26872.136 0.000 0.000 0.000 0.000 0.000 0.000 21076.095 0.000 0.000 0.000
August 0.148912E+12 89231.929 04-AUG-16:30 4276.255 26630.920 7458.159 0.000 32724.583 0.000 0.000 0.000 0.000 0.000 0.000 18142.011 0.000 0.000 0.000
September 0.139144E+12 85763.930 22-SEP-16:15 4276.255 26630.920 7458.159 0.000 27101.560 0.000 0.000 0.000 0.000 0.000 0.000 20297.036 0.000 0.000 0.000
October 0.125119E+12 82407.790 01-OCT-17:15 4979.953 26630.920 7458.159 0.000 22366.013 0.000 0.000 0.000 0.000 0.000 0.000 20972.745 0.000 0.000 0.000
November 0.115601E+12 76164.412 27-NOV-18:45 4979.953 26630.920 7458.159 0.000 14571.836 2553.000 0.000 0.000 0.000 0.000 0.000 19970.543 0.000 0.000 0.000
December 0.112809E+12 70052.012 07-DEC-18:30 4979.953 26630.920 7458.159 0.000 8247.299 2553.000 0.000 0.000 0.000 0.000 0.000 20182.681 0.000 0.000 0.000
                                     
Annual Sum or Average 0.151674E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.103031E+12 67095.477   4276.255 26630.920 7458.159 0.000 6081.360 0.000 0.000 0.000 0.000 0.000 0.000 18142.011 0.000 0.000 0.000
Maximum of Months 0.149146E+12 89231.929   4979.953 26630.920 7458.159 0.000 32724.583 2553.000 0.000 0.000 0.000 0.000 0.000 22113.559 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:59

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.215459E+11 53279.528 22-JAN-06:00 53279.528 0.000 0.000 0.000 0.000 0.000 53279.528
February 0.167057E+11 73740.646 11-FEB-04:00 73740.646 0.000 0.000 0.000 0.000 0.000 73740.646
March 0.417096E+10 34041.597 19-MAR-06:15 34041.597 0.000 0.000 0.000 0.000 0.000 34041.597
April 0.241623E+09 8488.803 07-APR-04:00 8488.803 0.000 0.000 0.000 0.000 0.000 8488.803
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.275167E+09 7571.075 13-OCT-05:00 7571.075 0.000 0.000 0.000 0.000 0.000 7571.075
November 0.247625E+10 21890.791 30-NOV-05:00 21890.791 0.000 0.000 0.000 0.000 0.000 21890.791
December 0.133565E+11 43581.905 21-DEC-05:00 43581.905 0.000 0.000 0.000 0.000 0.000 43581.905
                     
Annual Sum or Average 0.587720E+11       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.215459E+11 73740.646   73740.646 0.000 0.000 0.000 0.000 0.000 73740.646