Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Memphis International Ap TN USA TMY3 WMO#=723340

Simulation Timestamp: 2015-09-09 18:48:02


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1651.30 526.80 584.74
Net Site Energy 1651.30 526.80 584.74
Total Source Energy 4830.37 1540.98 1710.48
Net Source Energy 4830.37 1540.98 1710.48


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 191.69 0.00 0.00 0.00 0.00
Cooling 206.29 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.14 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 220.56 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 356.50 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1459.61 191.69 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 191.69 0.00 0.00 0.00 0.00
Cooling General 206.29 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.14 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 220.56 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 356.50 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.16 0.00 0.00 0.00 0.00 0.00
HVAC 277.39 67.88 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 516.86 67.88 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.60 0.00 0.00 0.00 0.00 0.00
HVAC 249.90 61.15 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 465.64 61.15 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1459.61 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1459.61 100.00
     
Total On-Site and Utility Electric Sources 1459.61 100.00
Total Electricity End Uses 1459.61 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 57.25
Time Setpoint Not Met During Occupied Cooling 2.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 2299.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Memphis International Ap TN USA TMY3 WMO#=723340
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
Latitude [deg] 35.07
Longitude [deg] -90.0
Elevation [m] 81.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-AUG-16:45 31-JAN-07:15 - - - 01-JAN-07:15
Heating 0.00 109600.43 0.00 0.00 0.00 0.00
Cooling 29187.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4276.26 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26730.99 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6993.96 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 21039.03 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 88227.61 109600.43 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 109600.43 0.00 0.00 0.00 0.00
Cooling General 29187.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 3538.13 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 738.12 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26730.99 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6993.96 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 21039.03 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 207.80 0.00 0.00 0.00
Cooling 653.33 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 127.13 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 698.52 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1129.03 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4622.57 207.80 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 73.58 0.00 0.00 0.00
Cooling 231.35 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.02 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 247.35 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 399.80 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1636.90 73.58 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 73.58 0.00 0.00 0.00
Cooling 231.35 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.02 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 247.35 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 399.80 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1636.90 73.58 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB -8.30 0.00 -8.30 Wetbulb [C] 4.10 0.00
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 35.60 9.20 25.20 Wetbulb [C] 3.80 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 2.848 0.287 0.200     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 2.848 0.287 0.200     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.62_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 2.848 0.287 0.200     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.62_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 2.848 0.287 0.200     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 2.848 0.287 0.200     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.62_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 2.848 0.287 0.200     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.62_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 2.848 0.287 0.200     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.848 0.287 0.200              
North Total or Average           112.97 2.848 0.287 0.200              
Non-North Total or Average           193.95 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.76 83.76 40.14
Exterior Lighting Total 2553.00           40.14



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3767.30 2640.14 1127.16 0.70 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3702.47 2609.14 1093.33 0.70 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8451.94 6494.07 1957.87 0.77 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3088.81 2141.83 946.98 0.69 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2528.79 1714.86 813.93 0.68 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2516.16 1704.92 811.24 0.68 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2537.00 1715.22 821.78 0.68 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2607.12 1762.63 844.49 0.68 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9252.74 6611.48 2641.26 0.71 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   9154.69 6550.64 2604.05 0.72 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8520.50 5978.81 2541.69 0.70 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7851.28 5549.27 2302.01 0.71 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6313.56 4382.26 1931.30 0.69 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6293.22 4366.15 1927.07 0.69 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6580.96 4517.77 2063.19 0.69 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6585.97 4525.58 2060.39 0.69 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6248.86 4537.01 1711.85 0.73 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6040.99 4391.01 1649.99 0.73 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5878.18 4232.17 1646.00 0.72 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5466.01 3901.29 1564.72 0.71 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4434.14 3140.72 1293.42 0.71 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4437.35 3143.35 1294.01 0.71 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4830.05 3455.43 1374.62 0.72 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4831.29 3459.17 1372.12 0.72 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3635.8 3.30 11.27 11.74 11.26
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3571.4 3.30 11.25 11.71 11.23
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8084.4 3.18 10.85 11.28 10.64
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2983.9 3.32 11.32 11.79 11.34
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2447.8 3.35 11.42 11.90 11.49
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2435.7 3.35 11.42 11.90 11.49
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2456.4 3.35 11.43 11.92 11.51
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2524.3 3.35 11.43 11.92 11.51
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8913.6 3.28 11.18 11.65 11.13
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 8818.0 3.28 11.18 11.64 11.12
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 8222.1 3.30 11.26 11.73 11.25
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7571.2 3.29 11.23 11.70 11.20
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6098.5 3.32 11.31 11.79 11.33
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6079.1 3.32 11.32 11.79 11.33
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6363.2 3.33 11.36 11.84 11.40
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6367.5 3.33 11.36 11.84 11.40
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6010.7 3.26 11.11 11.57 11.02
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5810.1 3.25 11.11 11.56 11.01
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5658.7 3.27 11.15 11.61 11.08
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 5266.2 3.28 11.19 11.65 11.14
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4275.1 3.29 11.22 11.69 11.19
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4278.2 3.29 11.22 11.69 11.19
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4652.5 3.28 11.18 11.64 11.12
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4653.3 3.27 11.17 11.64 11.12
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   2794.72 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   2775.02 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   5014.02 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   2775.02 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   2059.94 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   2059.94 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   2048.18 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   2160.82 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   5568.67 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   5601.61 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   5568.67 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   5601.61 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3776.78 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3776.78 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3745.54 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3745.54 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   4132.10 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   4150.84 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   4132.10 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   4150.84 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   3139.73 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   3139.73 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   3119.03 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   3119.03 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 193.87 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 193.29 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 543.85 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 154.60 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 119.20 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 118.34 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 118.60 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 121.87 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.43 500.41 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.43 496.87 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 439.94 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 413.02 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 316.84 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 315.44 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 320.70 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 321.78 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 351.68 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 340.92 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 324.00 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 294.78 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 234.53 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 234.77 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 262.01 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 262.63 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1760.22 2112.27 0.139 0.167 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 34.31 0.01615
G NW APARTMENT 1755.04 2106.05 0.139 0.167 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.62 0.01615
OFFICE 4700.42 5640.51 0.390 0.468 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 31.32 0.01615
G NE APARTMENT 1403.65 1684.38 0.111 0.133 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 32.45 0.01615
G N1 APARTMENT 1082.37 1298.85 0.086 0.103 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.70 0.01615
G N2 APARTMENT 1074.58 1289.49 0.085 0.102 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 32.70 0.01615
G S1 APARTMENT 1076.82 1292.18 0.085 0.102 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
G S2 APARTMENT 1106.58 1327.90 0.087 0.105 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
M SW APARTMENT 4543.35 5452.02 0.359 0.431 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 34.08 0.01615
M NW APARTMENT 4511.38 5413.66 0.357 0.428 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.62 0.01615
M SE APARTMENT 3994.12 4792.95 0.316 0.379 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 35.26 0.01615
M NE APARTMENT 3749.72 4499.67 0.296 0.356 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 32.79 0.01615
M N1 APARTMENT 2876.89 3452.26 0.227 0.273 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
M N2 APARTMENT 2864.17 3437.00 0.226 0.272 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 33.05 0.01615
M S1 APARTMENT 2911.82 3494.19 0.230 0.276 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
M S2 APARTMENT 2921.61 3505.93 0.231 0.277 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 35.37 0.01615
T SW APARTMENT 3192.59 3831.11 0.252 0.303 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 35.19 0.01615
T NW APARTMENT 3094.91 3713.90 0.245 0.294 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 34.50 0.01615
T SE APARTMENT 2941.39 3529.67 0.233 0.279 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615
T NE APARTMENT 2676.04 3211.25 0.212 0.254 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.60 0.01615
T N1 APARTMENT 2129.35 2555.22 0.168 0.202 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.60 0.01615
T N2 APARTMENT 2131.51 2557.81 0.169 0.202 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.60 0.01615
T S1 APARTMENT 2378.86 2854.63 0.188 0.226 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.60 0.01615
T S2 APARTMENT 2384.40 2861.28 0.189 0.226 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 35.48 0.01615


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1545.47 1854.57 0.045 0.054 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G NW APARTMENT 1557.56 1869.07 0.045 0.054 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
OFFICE 3132.98 3759.57 0.088 0.105 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G NE APARTMENT 1557.56 1869.07 0.045 0.054 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G N1 APARTMENT 952.84 1143.41 0.028 0.033 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G N2 APARTMENT 952.84 1143.41 0.028 0.033 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G S1 APARTMENT 942.89 1131.47 0.027 0.033 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
G S2 APARTMENT 1038.15 1245.78 0.030 0.036 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -8.30 0.00188
M SW APARTMENT 3131.02 3757.23 0.091 0.109 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M NW APARTMENT 3158.88 3790.66 0.092 0.110 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M SE APARTMENT 3131.02 3757.23 0.091 0.109 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M NE APARTMENT 3158.88 3790.66 0.092 0.110 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M N1 APARTMENT 1615.62 1938.75 0.047 0.056 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M N2 APARTMENT 1615.62 1938.75 0.047 0.056 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M S1 APARTMENT 1589.21 1907.05 0.046 0.055 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
M S2 APARTMENT 1589.21 1907.05 0.046 0.055 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T SW APARTMENT 2705.29 3246.35 0.079 0.094 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T NW APARTMENT 2721.14 3265.37 0.079 0.095 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T SE APARTMENT 2705.29 3246.35 0.079 0.094 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T NE APARTMENT 2721.14 3265.37 0.079 0.095 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T N1 APARTMENT 1866.04 2239.25 0.054 0.065 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T N2 APARTMENT 1866.04 2239.25 0.054 0.065 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T S1 APARTMENT 1848.53 2218.24 0.054 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188
T S2 APARTMENT 1848.53 2218.24 0.054 0.064 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -8.30 0.00188


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.17 0.17 0.05 0.05
SPLIT GNW 0.17 0.17 0.05 0.05
SPLIT OFFICE 0.47 0.47 0.11 0.11
SPLIT GNE 0.13 0.13 0.05 0.05
SPLIT GN1 0.10 0.10 0.03 0.03
SPLIT GN2 0.10 0.10 0.03 0.03
SPLIT GS1 0.10 0.10 0.03 0.03
SPLIT GS2 0.10 0.10 0.04 0.04
SPLIT MSW 0.43 0.43 0.11 0.11
SPLIT MNW 0.43 0.43 0.11 0.11
SPLIT MSE 0.38 0.38 0.11 0.11
SPLIT MNE 0.36 0.36 0.11 0.11
SPLIT MN1 0.27 0.27 0.06 0.06
SPLIT MN2 0.27 0.27 0.06 0.06
SPLIT MS1 0.28 0.28 0.06 0.06
SPLIT MS2 0.28 0.28 0.06 0.06
SPLIT TSW 0.30 0.30 0.09 0.09
SPLIT TNW 0.29 0.29 0.09 0.09
SPLIT TSE 0.28 0.28 0.09 0.09
SPLIT TNE 0.25 0.25 0.09 0.09
SPLIT TN1 0.20 0.20 0.07 0.07
SPLIT TN2 0.20 0.20 0.07 0.07
SPLIT TS1 0.23 0.23 0.06 0.06
SPLIT TS2 0.23 0.23 0.06 0.06



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3918.25 5793.25 1540.25
G NW APARTMENT 4149.25 6100.00 1878.25
OFFICE 798.50 1254.00 42.25
G NE APARTMENT 4125.75 6096.75 1825.50
G N1 APARTMENT 3818.25 6306.00 1674.25
G N2 APARTMENT 3815.50 6303.00 1669.50
G S1 APARTMENT 3653.00 5968.50 1366.75
G S2 APARTMENT 3697.50 5749.50 1222.25
M SW APARTMENT 4771.00 3194.75 386.75
M NW APARTMENT 4605.25 3756.75 558.25
M SE APARTMENT 4763.00 3180.25 349.00
M NE APARTMENT 4579.75 3784.25 533.50
M N1 APARTMENT 4378.25 3590.50 299.00
M N2 APARTMENT 4375.25 3596.00 298.00
M S1 APARTMENT 4621.25 2870.75 211.50
M S2 APARTMENT 4622.25 2874.75 212.75
T SW APARTMENT 5160.00 4038.50 1246.00
T NW APARTMENT 5205.75 4461.25 1577.75
T SE APARTMENT 5151.75 4012.75 1226.75
T NE APARTMENT 5184.75 4487.25 1547.00
T N1 APARTMENT 4976.75 4359.25 1261.75
T N2 APARTMENT 4974.00 4361.50 1262.25
T S1 APARTMENT 4982.50 3818.50 967.50
T S2 APARTMENT 4986.50 3820.25 972.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 5942.75 6380.00 2299.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 6.00 0.00 6.00 0.00
G NW APARTMENT 4.75 0.00 4.75 0.00
OFFICE 5.00 23.75 0.00 0.00
G NE APARTMENT 8.00 0.00 8.00 0.00
G N1 APARTMENT 5.75 0.00 5.75 0.00
G N2 APARTMENT 5.50 0.00 5.50 0.00
G S1 APARTMENT 5.00 2.25 5.00 2.25
G S2 APARTMENT 5.25 1.50 5.25 1.50
M SW APARTMENT 7.75 0.00 7.75 0.00
M NW APARTMENT 11.75 0.00 11.75 0.00
M SE APARTMENT 12.75 0.00 12.75 0.00
M NE APARTMENT 15.00 0.00 15.00 0.00
M N1 APARTMENT 8.00 0.00 8.00 0.00
M N2 APARTMENT 7.75 0.00 7.75 0.00
M S1 APARTMENT 4.75 0.00 4.75 0.00
M S2 APARTMENT 5.00 0.00 5.00 0.00
T SW APARTMENT 10.50 0.00 10.50 0.00
T NW APARTMENT 12.25 0.00 12.25 0.00
T SE APARTMENT 13.00 0.00 13.00 0.00
T NE APARTMENT 17.50 0.00 17.50 0.00
T N1 APARTMENT 5.00 0.00 5.00 0.00
T N2 APARTMENT 5.25 0.00 5.25 0.00
T S1 APARTMENT 4.75 0.00 4.75 0.00
T S2 APARTMENT 4.75 0.00 4.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 61.75 26.00 57.25 2.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.367 0.162 0.000 0.088
G NW APARTMENT 1.71 2.50 268.97 0.354 0.162 0.000 0.084
OFFICE 0.94 1.00 268.97 0.520 0.196 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.354 0.162 0.000 0.084
G N1 APARTMENT 1.71 2.50 268.97 0.354 0.098 0.000 0.083
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.098 0.000 0.083
G S1 APARTMENT 1.71 2.50 268.97 0.354 0.098 0.000 0.088
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.098 0.000 0.088
M SW APARTMENT 1.71 2.50 268.97 0.355 0.233 0.000 0.110
M NW APARTMENT 1.71 2.50 268.97 0.355 0.233 0.000 0.106
M SE APARTMENT 1.71 2.50 268.97 0.355 0.233 0.000 0.110
M NE APARTMENT 1.71 2.50 268.97 0.355 0.233 0.000 0.106
M N1 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.106
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.106
M S1 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.111
M S2 APARTMENT 1.71 2.50 268.97 0.355 0.141 0.000 0.111
T SW APARTMENT 1.71 2.50 268.97 0.355 0.308 0.000 0.133
T NW APARTMENT 1.71 2.50 268.97 0.354 0.308 0.000 0.127
T SE APARTMENT 1.71 2.50 268.97 0.355 0.308 0.000 0.133
T NE APARTMENT 1.71 2.50 268.97 0.354 0.308 0.000 0.127
T N1 APARTMENT 1.71 2.50 268.97 0.354 0.186 0.000 0.127
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.186 0.000 0.127
T S1 APARTMENT 1.71 2.50 268.97 0.355 0.186 0.000 0.133
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.186 0.000 0.133
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.355 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.369 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 356.50 0.00 01-JAN-00:15 32298.32 07-JAN-08:00
WaterSystems:Electricity 356.50 0.00 01-JAN-00:15 32298.32 07-JAN-08:00
Water Heater:WaterSystems:Electricity 356.50 0.00 01-JAN-00:15 32298.32 07-JAN-08:00
Fans:Electricity 220.56 6993.96 02-JAN-18:15 6993.96 02-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
ElectricityPurchased:Plant 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
Cogeneration:ElectricityPurchased 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
ElectricityNet:Plant 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
Cogeneration:ElectricityNet 1459.61 20106.58 01-JAN-03:15 88227.61 29-AUG-16:45
ExteriorLights:Electricity 40.14 0.00 01-JAN-07:15 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.14 0.00 01-JAN-07:15 2553.00 01-JAN-00:15
Electricity:HVAC 426.85 6993.96 02-JAN-18:15 39482.60 29-AUG-13:45
General:Fans:Electricity 220.56 6993.96 02-JAN-18:15 6993.96 02-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 206.29 0.00 01-JAN-00:15 32488.63 29-AUG-13:45


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 191.69 0.00 13-JAN-14:00 109600.43 31-JAN-07:15
Gas:HVAC 191.69 0.00 13-JAN-14:00 109600.43 31-JAN-07:15
Heating:Gas 191.69 0.00 13-JAN-14:00 109600.43 31-JAN-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1603.69 1293.73 14-APR-11:30 186762.75 29-AUG-13:30
EnergyTransfer:Building 618.12 1258.31 14-APR-11:30 68619.73 29-AUG-13:45
EnergyTransfer:Zone:G SW APARTMENT 13.90 0.00 11-APR-13:45 2077.48 30-AUG-16:15
Heating:EnergyTransfer 92.98 0.00 15-JAN-12:45 62349.94 31-JAN-07:15
Heating:EnergyTransfer:Zone:G SW APARTMENT 3.26 0.00 01-JAN-11:00 2071.89 06-JAN-22:15
Cooling:EnergyTransfer 525.14 0.00 02-JAN-07:30 68619.73 29-AUG-13:45
Cooling:EnergyTransfer:Zone:G SW APARTMENT 10.63 0.00 01-JAN-00:15 2077.48 30-AUG-16:15
EnergyTransfer:Zone:G NW APARTMENT 13.32 0.03 05-APR-12:00 2093.75 06-JAN-22:15
Heating:EnergyTransfer:Zone:G NW APARTMENT 4.52 0.00 04-JAN-21:00 2093.75 06-JAN-22:15
Cooling:EnergyTransfer:Zone:G NW APARTMENT 8.81 0.00 01-JAN-00:15 1926.52 12-JUL-17:30
EnergyTransfer:Zone:OFFICE 27.09 0.02 12-APR-00:45 4839.91 29-AUG-10:30
Heating:EnergyTransfer:Zone:OFFICE 4.39 0.00 01-JAN-00:15 3748.34 31-JAN-07:15
Cooling:EnergyTransfer:Zone:OFFICE 22.70 0.00 01-JAN-03:30 4839.91 29-AUG-10:30
EnergyTransfer:Zone:G NE APARTMENT 13.25 0.00 17-OCT-18:15 2065.34 06-JAN-19:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 4.37 0.00 13-JAN-17:45 2065.34 06-JAN-19:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 8.89 0.00 01-JAN-00:15 1568.78 11-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 9.31 0.01 15-NOV-16:15 1229.64 31-JAN-03:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 2.17 0.00 04-JAN-19:15 1229.64 31-JAN-03:30
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 7.14 0.00 01-JAN-00:15 1219.73 11-JUL-17:30
EnergyTransfer:Zone:G N2 APARTMENT 9.31 0.00 28-MAR-08:15 1228.89 31-JAN-03:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 2.17 0.00 04-JAN-19:15 1228.89 31-JAN-03:30
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 7.14 0.00 01-JAN-00:15 1213.76 11-JUL-17:30
EnergyTransfer:Zone:G S1 APARTMENT 10.47 0.01 01-MAY-03:00 1421.35 30-AUG-13:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 1.31 0.00 01-JAN-07:15 1214.99 31-JAN-03:30
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 9.15 0.00 01-JAN-00:15 1421.35 30-AUG-13:00
EnergyTransfer:Zone:G S2 APARTMENT 11.10 0.01 30-DEC-12:00 1499.92 23-SEP-14:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 1.41 0.00 01-JAN-07:15 1322.38 31-JAN-03:45
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 9.69 0.00 01-JAN-00:15 1499.92 23-SEP-14:30
EnergyTransfer:Zone:M SW APARTMENT 45.73 0.14 03-FEB-01:45 5314.61 30-AUG-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 3.71 0.00 01-JAN-01:00 4405.51 06-JAN-22:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 42.02 0.00 01-JAN-00:15 5314.61 30-AUG-16:15
EnergyTransfer:Zone:M NW APARTMENT 40.25 0.01 15-OCT-14:30 4914.17 10-JUL-16:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 5.91 0.00 01-JAN-11:30 4445.57 06-JAN-22:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 34.34 0.00 01-JAN-00:15 4914.17 10-JUL-16:30
EnergyTransfer:Zone:M SE APARTMENT 45.90 0.02 02-FEB-21:00 5065.11 29-AUG-10:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 3.71 0.00 01-JAN-02:00 4350.35 06-JAN-22:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 42.19 0.00 01-JAN-00:15 5065.11 29-AUG-10:30
EnergyTransfer:Zone:M NE APARTMENT 40.30 0.00 06-NOV-14:00 4365.21 06-JAN-22:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 5.81 0.00 01-JAN-07:45 4365.21 06-JAN-22:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 34.50 0.00 01-JAN-00:15 4189.08 10-JUL-17:00
EnergyTransfer:Zone:M N1 APARTMENT 32.46 0.02 25-FEB-14:45 3224.15 11-JUL-17:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 1.71 0.00 01-JAN-00:45 2364.98 06-JAN-22:15
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 30.75 0.00 01-JAN-00:15 3224.15 11-JUL-17:30
EnergyTransfer:Zone:M N2 APARTMENT 32.45 0.06 23-JAN-17:00 3215.61 11-JUL-17:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 1.71 0.00 01-JAN-00:45 2363.73 06-JAN-22:15
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 30.74 0.00 01-JAN-00:15 3215.61 11-JUL-17:30
EnergyTransfer:Zone:M S1 APARTMENT 40.51 0.49 15-FEB-04:30 3761.91 30-AUG-13:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.90 0.00 01-JAN-00:15 2333.63 06-JAN-22:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 39.62 0.00 02-JAN-07:00 3761.91 30-AUG-13:00
EnergyTransfer:Zone:M S2 APARTMENT 40.50 0.09 31-DEC-09:15 3773.72 30-AUG-13:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.90 0.00 01-JAN-00:15 2334.76 06-JAN-22:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 39.60 0.00 02-JAN-07:00 3773.72 30-AUG-13:00
EnergyTransfer:Zone:T SW APARTMENT 27.75 0.00 05-NOV-00:45 3670.52 06-JAN-22:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 6.58 0.00 01-JAN-11:15 3670.52 06-JAN-22:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 21.17 0.00 01-JAN-00:15 3637.40 29-AUG-13:30
EnergyTransfer:Zone:T NW APARTMENT 26.35 0.01 09-APR-04:15 3680.80 06-JAN-22:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 8.25 0.00 10-JAN-14:00 3680.80 06-JAN-22:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 18.11 0.00 01-JAN-00:15 3368.07 10-JUL-16:30
EnergyTransfer:Zone:T SE APARTMENT 27.52 0.01 13-APR-16:00 3645.60 06-JAN-22:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 6.46 0.00 01-JAN-11:00 3645.60 06-JAN-22:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 21.07 0.00 01-JAN-00:15 3586.71 29-AUG-13:30
EnergyTransfer:Zone:T NE APARTMENT 26.08 0.01 07-SEP-03:00 3637.71 06-JAN-22:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 8.06 0.00 15-JAN-07:45 3637.71 06-JAN-22:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 18.01 0.00 01-JAN-00:15 2951.82 05-JUN-14:15
EnergyTransfer:Zone:T N1 APARTMENT 20.06 0.01 02-DEC-09:45 2447.09 31-JAN-03:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 4.54 0.00 01-JAN-11:45 2447.09 31-JAN-03:30
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 15.52 0.00 01-JAN-00:15 2355.41 10-JUL-16:15
EnergyTransfer:Zone:T N2 APARTMENT 20.07 0.03 06-DEC-20:45 2447.67 31-JAN-03:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 4.54 0.00 01-JAN-11:45 2447.67 31-JAN-03:30
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 15.52 0.00 01-JAN-00:15 2345.30 10-JUL-16:15
EnergyTransfer:Zone:T S1 APARTMENT 22.20 0.00 26-NOV-21:00 2900.10 29-AUG-13:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 3.29 0.00 01-JAN-10:45 2450.50 31-JAN-03:45
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 18.91 0.00 01-JAN-00:15 2900.10 29-AUG-13:30
EnergyTransfer:Zone:T S2 APARTMENT 22.21 0.05 07-DEC-00:45 2905.95 29-AUG-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 3.30 0.00 01-JAN-10:45 2451.40 31-JAN-03:45
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 18.91 0.00 01-JAN-00:15 2905.95 29-AUG-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 985.57 0.00 14-JAN-11:15 118711.52 21-AUG-15:15
HeatingCoils:EnergyTransfer 153.36 0.00 13-JAN-14:00 87680.34 31-JAN-07:15
CoolingCoils:EnergyTransfer 832.22 0.00 01-JAN-00:15 118711.52 21-AUG-15:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 3.262 -10.634 0.000 0.000 3.768 1.087 12.213 12.107 0.000 0.542 0.000 0.000 -5.010 0.000 -4.484 -12.850
G NW APARTMENT 4.518 -8.807 0.000 0.000 3.789 1.087 12.213 7.370 0.000 0.542 0.000 0.000 -5.211 0.000 -4.318 -11.182
OFFICE 4.395 -22.697 0.000 0.000 0.520 26.452 9.482 11.612 0.000 0.323 0.000 0.000 -5.272 0.000 -3.851 -20.965
G NE APARTMENT 4.365 -8.886 0.000 0.000 3.798 1.087 12.213 7.169 0.000 0.542 0.000 0.000 -5.036 0.000 -4.294 -10.958
G N1 APARTMENT 2.172 -7.136 0.000 0.000 3.800 1.087 12.213 3.004 0.000 0.345 0.000 0.000 -3.224 0.000 -2.840 -9.421
G N2 APARTMENT 2.172 -7.137 0.000 0.000 3.801 1.087 12.213 3.004 0.000 0.345 0.000 0.000 -3.222 0.000 -2.839 -9.422
G S1 APARTMENT 1.313 -9.152 0.000 0.000 3.772 1.087 12.213 7.773 0.000 0.343 0.000 0.000 -3.023 0.000 -3.016 -11.311
G S2 APARTMENT 1.409 -9.694 0.000 0.000 3.769 1.087 12.213 7.763 0.000 0.343 0.000 0.000 -3.030 0.000 -3.028 -10.830
M SW APARTMENT 3.707 -42.024 0.000 0.000 3.664 1.087 12.213 11.589 0.000 0.769 21.294 0.000 -5.625 0.000 -6.673 -0.000
M NW APARTMENT 5.906 -34.344 0.000 0.000 3.695 1.087 12.213 6.949 0.000 0.767 16.017 0.000 -5.812 0.000 -6.477 -0.001
M SE APARTMENT 3.713 -42.191 0.000 0.000 3.669 1.087 12.213 11.456 0.000 0.769 21.462 0.000 -5.517 0.000 -6.660 -0.000
M NE APARTMENT 5.808 -34.496 0.000 0.000 3.701 1.087 12.213 6.738 0.000 0.767 16.258 0.000 -5.620 0.000 -6.455 -0.001
M N1 APARTMENT 1.712 -30.751 0.000 0.000 3.686 1.087 12.213 2.751 0.000 0.482 16.853 0.000 -3.667 0.000 -4.365 -0.000
M N2 APARTMENT 1.714 -30.740 0.000 0.000 3.686 1.087 12.213 2.751 0.000 0.482 16.836 0.000 -3.666 0.000 -4.363 -0.001
M S1 APARTMENT 0.899 -39.615 0.000 0.000 3.645 1.087 12.213 7.437 0.000 0.484 21.831 0.000 -3.430 0.000 -4.549 -0.001
M S2 APARTMENT 0.902 -39.597 0.000 0.000 3.645 1.087 12.213 7.436 0.000 0.484 21.809 0.000 -3.429 0.000 -4.549 -0.000
T SW APARTMENT 6.577 -21.173 0.000 0.000 3.708 1.087 12.213 11.361 0.000 1.019 0.001 0.000 -5.329 0.000 -8.457 -1.005
T NW APARTMENT 8.246 -18.106 0.000 0.000 3.729 1.087 12.213 6.770 0.000 1.016 0.000 0.000 -5.527 0.000 -8.250 -1.176
T SE APARTMENT 6.455 -21.067 0.000 0.000 3.712 1.087 12.213 11.241 0.000 1.019 0.001 0.000 -5.236 0.000 -8.457 -0.966
T NE APARTMENT 8.064 -18.011 0.000 0.000 3.736 1.087 12.213 6.587 0.000 1.016 0.000 0.000 -5.362 0.000 -8.241 -1.087
T N1 APARTMENT 4.538 -15.523 0.000 0.000 3.725 1.087 12.213 2.687 0.000 0.642 0.000 0.000 -3.457 0.000 -5.466 -0.445
T N2 APARTMENT 4.544 -15.522 0.000 0.000 3.725 1.087 12.213 2.686 0.000 0.642 0.000 0.000 -3.455 0.000 -5.467 -0.453
T S1 APARTMENT 3.292 -18.908 0.000 0.000 3.695 1.087 12.213 7.312 0.000 0.645 0.000 0.000 -3.252 0.000 -5.670 -0.413
T S2 APARTMENT 3.298 -18.914 0.000 0.000 3.695 1.087 12.213 7.311 0.000 0.645 0.001 0.000 -3.250 0.000 -5.671 -0.414
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.157 0.000 0.071 0.000 0.000 -0.622 0.000 -1.337 -12.850
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.566 0.000 1.928 0.001 0.000 -1.536 0.000 -18.331 -3.688
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.165 0.000 0.064 0.000 0.000 -0.683 0.000 -1.105 -13.023
Total Facility 92.979 -525.128 0.000 0.000 86.131 95.189 296.854 173.749 0.000 17.041 152.364 0.000 -107.504 0.000 -149.211 -132.463


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 30-AUG-16:13 0.00 -2078.48 0.00 0.00 84.76 64.86 588.62 1708.16 0.00 190.64 0.00 0.00 0.00 0.00 0.00 -558.56
G NW APARTMENT 12-JUL-17:23 0.00 -1927.06 0.00 0.00 141.81 87.56 588.62 1455.05 0.00 217.53 0.00 0.00 0.00 0.00 0.00 -563.50
OFFICE 07-SEP-06:01 0.00 -7873.31 0.00 0.00 0.00 416.15 294.31 28.27 0.00 0.00 7248.67 0.00 0.00 0.00 -114.08 0.00
G NE APARTMENT 11-JUL-17:06 0.00 -1571.61 0.00 0.00 141.82 87.56 588.62 689.14 0.00 239.94 0.00 0.00 0.00 0.00 0.00 -175.47
G N1 APARTMENT 11-JUL-17:23 0.00 -1220.13 0.00 0.00 141.81 87.56 588.62 492.55 0.00 142.72 0.00 0.00 0.00 0.00 0.00 -233.13
G N2 APARTMENT 11-JUL-17:23 0.00 -1214.07 0.00 0.00 141.81 87.56 588.62 492.64 0.00 142.72 0.00 0.00 0.00 0.00 0.00 -239.27
G S1 APARTMENT 30-AUG-13:00 0.00 -1421.02 0.00 0.00 40.75 12.97 388.49 1345.85 0.00 138.52 0.00 0.00 0.00 0.00 0.00 -505.57
G S2 APARTMENT 23-SEP-14:30 0.00 -1499.84 0.00 0.00 40.62 22.70 400.26 1168.53 0.00 92.20 0.00 0.00 0.00 0.00 0.00 -224.47
M SW APARTMENT 30-AUG-16:05 0.00 -5317.33 0.00 0.00 84.76 64.86 588.62 1684.85 0.00 273.37 2620.87 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 10-JUL-16:20 0.00 -4915.14 0.00 0.00 84.76 64.86 588.62 1468.74 0.00 386.83 2321.34 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 29-AUG-10:30 0.00 -5065.15 0.00 0.00 40.76 12.97 412.04 2003.35 0.00 348.93 2247.10 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 10-JUL-17:00 0.00 -4188.50 0.00 0.00 84.77 64.86 588.62 688.79 0.00 404.63 2356.83 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 11-JUL-17:30 0.00 -3225.17 0.00 0.00 141.81 87.56 588.62 484.34 0.00 204.70 1718.14 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 11-JUL-17:26 0.00 -3216.29 0.00 0.00 141.81 87.56 588.62 484.39 0.00 204.70 1709.21 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 30-AUG-13:00 0.00 -3761.18 0.00 0.00 40.75 12.97 388.49 1332.30 0.00 198.67 1788.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 30-AUG-13:00 0.00 -3773.00 0.00 0.00 40.75 12.97 388.49 1332.22 0.00 198.67 1799.90 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 29-AUG-13:30 0.00 -3637.11 0.00 0.00 40.76 12.97 382.60 1937.01 0.00 562.40 701.37 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 10-JUL-16:20 0.00 -3368.70 0.00 0.00 84.76 64.86 588.62 1427.87 0.00 509.79 692.79 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 29-AUG-13:30 0.00 -3586.62 0.00 0.00 40.76 12.97 382.60 1527.24 0.00 562.40 1060.65 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 05-JUN-14:15 0.00 -2951.49 0.00 0.00 40.76 22.70 400.26 939.49 0.00 514.58 1033.69 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 10-JUL-16:04 0.00 -2360.03 0.00 0.00 84.77 64.86 588.62 466.62 0.00 299.97 855.20 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 10-JUL-16:04 0.00 -2349.97 0.00 0.00 84.77 64.86 588.62 466.75 0.00 299.97 845.00 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 29-AUG-13:30 0.00 -2899.99 0.00 0.00 40.75 12.97 382.60 1214.02 0.00 339.21 910.43 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 29-AUG-13:30 0.00 -2905.84 0.00 0.00 40.75 12.97 382.60 1213.93 0.00 339.21 916.38 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-AUG-13:45 0.00 -68616.94 0.00 0.00 1002.17 3766.23 9517.04 26102.03 0.00 9481.63 18747.83 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 06-JAN-22:15 2072.14 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -752.33 0.00 -1433.22 -533.10
G NW APARTMENT 06-JAN-22:15 2094.02 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -771.17 0.00 -1433.22 -536.14
OFFICE 29-JAN-07:01 4651.92 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -343.74 0.00 -152.44 -4866.20
G NE APARTMENT 06-JAN-19:00 2065.47 0.00 0.00 0.00 165.01 87.56 588.62 0.00 0.00 0.00 0.00 0.00 -771.62 0.00 -1508.38 -626.66
G N1 APARTMENT 29-DEC-17:01 1621.70 0.00 0.00 0.00 99.72 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -203.22 0.00 -124.84 -2046.84
G N2 APARTMENT 29-DEC-17:01 1633.96 0.00 0.00 0.00 99.72 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -203.19 0.00 -124.84 -2059.13
G S1 APARTMENT 31-JAN-03:30 1214.93 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -503.75 0.00 -822.66 -308.35
G S2 APARTMENT 31-JAN-03:45 1322.32 0.00 0.00 0.00 189.67 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -507.09 0.00 -851.10 -383.96
M SW APARTMENT 06-JAN-22:00 4405.30 0.00 0.00 0.00 190.04 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -790.56 0.00 -2116.04 -2260.41
M NW APARTMENT 06-JAN-22:00 4445.35 0.00 0.00 0.00 190.19 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -813.02 0.00 -2113.24 -2280.96
M SE APARTMENT 06-JAN-22:00 4350.13 0.00 0.00 0.00 190.35 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -788.93 0.00 -2111.48 -2211.74
M NE APARTMENT 06-JAN-22:00 4364.99 0.00 0.00 0.00 190.58 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -811.25 0.00 -2107.47 -2208.53
M N1 APARTMENT 04-JAN-17:01 3221.26 0.00 0.00 0.00 99.71 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -220.34 0.00 -266.90 -3487.21
M N2 APARTMENT 06-JAN-22:10 2364.44 0.00 0.00 0.00 189.78 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -495.74 0.00 -1240.44 -1274.87
M S1 APARTMENT 06-JAN-22:15 2334.02 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -473.79 0.00 -1242.03 -1264.70
M S2 APARTMENT 06-JAN-22:15 2335.15 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -473.76 0.00 -1242.00 -1265.89
T SW APARTMENT 06-JAN-22:00 3670.33 0.00 0.00 0.00 190.03 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -772.15 0.00 -2801.68 -858.21
T NW APARTMENT 06-JAN-22:00 3680.62 0.00 0.00 0.00 190.06 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -795.76 0.00 -2800.27 -846.33
T SE APARTMENT 06-JAN-22:00 3645.41 0.00 0.00 0.00 190.27 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -770.76 0.00 -2797.15 -839.45
T NE APARTMENT 06-JAN-22:00 3637.52 0.00 0.00 0.00 190.43 71.34 500.33 0.00 0.00 0.00 0.00 0.00 -794.08 0.00 -2793.12 -812.41
T N1 APARTMENT 31-JAN-03:30 2446.97 0.00 0.00 0.00 190.31 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -526.28 0.00 -1558.60 -782.57
T N2 APARTMENT 31-JAN-03:30 2447.55 0.00 0.00 0.00 190.35 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -526.19 0.00 -1558.37 -783.51
T S1 APARTMENT 31-JAN-03:45 2450.38 0.00 0.00 0.00 190.55 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -508.22 0.00 -1610.80 -752.08
T S2 APARTMENT 31-JAN-03:45 2451.28 0.00 0.00 0.00 190.58 6.49 223.68 0.00 0.00 0.00 0.00 0.00 -508.16 0.00 -1610.65 -753.21
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-07:01 62867.41 0.00 0.00 0.00 3790.35 2772.92 9503.69 0.00 0.00 0.00 0.00 0.00 -15443.40 0.00 -53222.88 -10268.09



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Sec1.1A-General Information

Data
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 57.25
Number of hours cooling loads not met 2.25
Number of hours not met 59.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4276.26 0.00 0.00 0.00 0.00
Exterior Lighting 40.14 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 191.69 109600.43 0.00 0.00
Space Cooling 206.29 29187.38 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 220.56 6993.96 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 356.50 21039.03 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26730.99 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1459.61   191.69   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1459.61
Natural Gas 0.00 191.69
Additional 0.00 0.00
Total 517.65 1651.30


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 65.81
Fans-Interior 70.36
Service Water Heating 113.73
Receptacle Equipment 165.14
Miscellaneous 12.81
Subtotal 465.64


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 61.15
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 61.15


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.17
Space Heating 11.61
Space Cooling 12.49
Fans-Interior 13.36
Service Water Heating 21.59
Receptacle Equipment 31.35
Miscellaneous 2.43



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.167012
G NW APARTMENT DIRECT AIR 0.166509
OFFICE DIRECT AIR 0.468499
G NE APARTMENT DIRECT AIR 0.133183
G N1 APARTMENT DIRECT AIR 0.102687
G N2 APARTMENT DIRECT AIR 0.101947
G S1 APARTMENT DIRECT AIR 0.102165
G S2 APARTMENT DIRECT AIR 0.104989
M SW APARTMENT DIRECT AIR 0.431079
M NW APARTMENT DIRECT AIR 0.428027
M SE APARTMENT DIRECT AIR 0.378981
M NE APARTMENT DIRECT AIR 0.355795
M N1 APARTMENT DIRECT AIR 0.272940
M N2 APARTMENT DIRECT AIR 0.271734
M S1 APARTMENT DIRECT AIR 0.276269
M S2 APARTMENT DIRECT AIR 0.277198
T SW APARTMENT DIRECT AIR 0.302949
T NW APARTMENT DIRECT AIR 0.293680
T SE APARTMENT DIRECT AIR 0.279113
T NE APARTMENT DIRECT AIR 0.253933
T N1 APARTMENT DIRECT AIR 0.202038
T N2 APARTMENT DIRECT AIR 0.202243
T S1 APARTMENT DIRECT AIR 0.225712
T S2 APARTMENT DIRECT AIR 0.226238


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.167012
SPLIT GNW MAIN BRANCH 0.166509
SPLIT OFFICE MAIN BRANCH 0.468499
SPLIT GNE MAIN BRANCH 0.133183
SPLIT GN1 MAIN BRANCH 0.102687
SPLIT GN2 MAIN BRANCH 0.101947
SPLIT GS1 MAIN BRANCH 0.102165
SPLIT GS2 MAIN BRANCH 0.104989
SPLIT MSW MAIN BRANCH 0.431079
SPLIT MNW MAIN BRANCH 0.428027
SPLIT MSE MAIN BRANCH 0.378981
SPLIT MNE MAIN BRANCH 0.355795
SPLIT MN1 MAIN BRANCH 0.272940
SPLIT MN2 MAIN BRANCH 0.271734
SPLIT MS1 MAIN BRANCH 0.276269
SPLIT MS2 MAIN BRANCH 0.277198
SPLIT TSW MAIN BRANCH 0.302949
SPLIT TNW MAIN BRANCH 0.293680
SPLIT TSE MAIN BRANCH 0.279113
SPLIT TNE MAIN BRANCH 0.253933
SPLIT TN1 MAIN BRANCH 0.202038
SPLIT TN2 MAIN BRANCH 0.202243
SPLIT TS1 MAIN BRANCH 0.225712
SPLIT TS2 MAIN BRANCH 0.226238


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.167012
SPLIT GNW 0.166509
SPLIT OFFICE 0.468499
SPLIT GNE 0.133183
SPLIT GN1 0.102687
SPLIT GN2 0.101947
SPLIT GS1 0.102165
SPLIT GS2 0.104989
SPLIT MSW 0.431079
SPLIT MNW 0.428027
SPLIT MSE 0.378981
SPLIT MNE 0.355795
SPLIT MN1 0.272940
SPLIT MN2 0.271734
SPLIT MS1 0.276269
SPLIT MS2 0.277198
SPLIT TSW 0.302949
SPLIT TNW 0.293680
SPLIT TSE 0.279113
SPLIT TNE 0.253933
SPLIT TN1 0.202038
SPLIT TN2 0.202243
SPLIT TS1 0.225712
SPLIT TS2 0.226238


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.167012 0.026898
SPLIT GNW OA CONTROLLER 0.166509 0.025953
SPLIT OFFICE OA CONTROLLER 0.468499 0.038104
SPLIT GNE OA CONTROLLER 0.133183 0.025953
SPLIT GN1 OA CONTROLLER 0.102687 0.025953
SPLIT GN2 OA CONTROLLER 0.101947 0.025953
SPLIT GS1 OA CONTROLLER 0.102165 0.025953
SPLIT GS2 OA CONTROLLER 0.104989 0.025953
SPLIT MSW OA CONTROLLER 0.431079 0.051906
SPLIT MNW OA CONTROLLER 0.428027 0.051906
SPLIT MSE OA CONTROLLER 0.378981 0.051906
SPLIT MNE OA CONTROLLER 0.355795 0.051906
SPLIT MN1 OA CONTROLLER 0.272940 0.051906
SPLIT MN2 OA CONTROLLER 0.271734 0.051906
SPLIT MS1 OA CONTROLLER 0.276269 0.051906
SPLIT MS2 OA CONTROLLER 0.277198 0.051906
SPLIT TSW OA CONTROLLER 0.302949 0.025953
SPLIT TNW OA CONTROLLER 0.293680 0.025953
SPLIT TSE OA CONTROLLER 0.279113 0.025953
SPLIT TNE OA CONTROLLER 0.253933 0.025953
SPLIT TN1 OA CONTROLLER 0.202038 0.025953
SPLIT TN2 OA CONTROLLER 0.202243 0.025953
SPLIT TS1 OA CONTROLLER 0.225712 0.025953
SPLIT TS2 OA CONTROLLER 0.226238 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.167012 3767.30 0.700805
SPLIT GNW COOLING COIL 0.166509 3702.47 0.704702
SPLIT OFFICE COOLING COIL 0.468499 8451.94 0.768353
SPLIT GNE COOLING COIL 0.133183 3088.81 0.693416
SPLIT GN1 COOLING COIL 0.102687 2528.79 0.678135
SPLIT GN2 COOLING COIL 0.101947 2516.16 0.677587
SPLIT GS1 COOLING COIL 0.102165 2537.00 0.676083
SPLIT GS2 COOLING COIL 0.104989 2607.12 0.676083
SPLIT MSW COOLING COIL 0.431079 9252.74 0.714543
SPLIT MNW COOLING COIL 0.428027 9154.69 0.715550
SPLIT MSE COOLING COIL 0.378981 8520.50 0.701697
SPLIT MNE COOLING COIL 0.355795 7851.28 0.706798
SPLIT MN1 COOLING COIL 0.272940 6313.56 0.694103
SPLIT MN2 COOLING COIL 0.271734 6293.22 0.693786
SPLIT MS1 COOLING COIL 0.276269 6580.96 0.686491
SPLIT MS2 COOLING COIL 0.277198 6585.97 0.687155
SPLIT TSW COOLING COIL 0.302949 6248.86 0.726053
SPLIT TNW COOLING COIL 0.293680 6040.99 0.726868
SPLIT TSE COOLING COIL 0.279113 5878.18 0.719981
SPLIT TNE COOLING COIL 0.253933 5466.01 0.713736
SPLIT TN1 COOLING COIL 0.202038 4434.14 0.708304
SPLIT TN2 COOLING COIL 0.202243 4437.35 0.708383
SPLIT TS1 COOLING COIL 0.225712 4830.05 0.715403
SPLIT TS2 COOLING COIL 0.226238 4831.29 0.715993


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.167012 0.167012 0.167012 0.167012 2794.72 3767.30 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.166509 0.166509 0.166509 0.166509 2775.02 3702.47 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.468499 0.468499 0.468499 0.468499 5014.02 8451.94 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.133183 0.133183 0.133183 0.133183 2775.02 3088.81 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.102687 0.102687 0.102687 0.102687 2059.94 2528.79 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.101947 0.101947 0.101947 0.101947 2059.94 2516.16 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.102165 0.102165 0.102165 0.102165 2048.18 2537.00 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.104989 0.104989 0.104989 0.104989 2160.82 2607.12 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.431079 0.431079 0.431079 0.431079 5568.67 9252.74 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.428027 0.428027 0.428027 0.428027 5601.61 9154.69 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.378981 0.378981 0.378981 0.378981 5568.67 8520.50 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.355795 0.355795 0.355795 0.355795 5601.61 7851.28 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.272940 0.272940 0.272940 0.272940 3776.78 6313.56 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.271734 0.271734 0.271734 0.271734 3776.78 6293.22 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.276269 0.276269 0.276269 0.276269 3745.54 6580.96 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.277198 0.277198 0.277198 0.277198 3745.54 6585.97 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.302949 0.302949 0.302949 0.302949 4132.10 6248.86 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.293680 0.293680 0.293680 0.293680 4150.84 6040.99 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.279113 0.279113 0.279113 0.279113 4132.10 5878.18 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.253933 0.253933 0.253933 0.253933 4150.84 5466.01 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.202038 0.202038 0.202038 0.202038 3139.73 4434.14 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.202243 0.202243 0.202243 0.202243 3139.73 4437.35 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.225712 0.225712 0.225712 0.225712 3119.03 4830.05 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.226238 0.226238 0.226238 0.226238 3119.03 4831.29 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.167012
SPLIT GNW SUPPLY FAN 0.166509
SPLIT OFFICE SUPPLY FAN 0.468499
SPLIT GNE SUPPLY FAN 0.133183
SPLIT GN1 SUPPLY FAN 0.102687
SPLIT GN2 SUPPLY FAN 0.101947
SPLIT GS1 SUPPLY FAN 0.102165
SPLIT GS2 SUPPLY FAN 0.104989
SPLIT MSW SUPPLY FAN 0.431079
SPLIT MNW SUPPLY FAN 0.428027
SPLIT MSE SUPPLY FAN 0.378981
SPLIT MNE SUPPLY FAN 0.355795
SPLIT MN1 SUPPLY FAN 0.272940
SPLIT MN2 SUPPLY FAN 0.271734
SPLIT MS1 SUPPLY FAN 0.276269
SPLIT MS2 SUPPLY FAN 0.277198
SPLIT TSW SUPPLY FAN 0.302949
SPLIT TNW SUPPLY FAN 0.293680
SPLIT TSE SUPPLY FAN 0.279113
SPLIT TNE SUPPLY FAN 0.253933
SPLIT TN1 SUPPLY FAN 0.202038
SPLIT TN2 SUPPLY FAN 0.202243
SPLIT TS1 SUPPLY FAN 0.225712
SPLIT TS2 SUPPLY FAN 0.226238


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 2794.72
SPLIT GNW HEATING COIL 2775.02
SPLIT OFFICE HEATING COIL 5014.02
SPLIT GNE HEATING COIL 2775.02
SPLIT GN1 HEATING COIL 2059.94
SPLIT GN2 HEATING COIL 2059.94
SPLIT GS1 HEATING COIL 2048.18
SPLIT GS2 HEATING COIL 2160.82
SPLIT MSW HEATING COIL 5568.67
SPLIT MNW HEATING COIL 5601.61
SPLIT MSE HEATING COIL 5568.67
SPLIT MNE HEATING COIL 5601.61
SPLIT MN1 HEATING COIL 3776.78
SPLIT MN2 HEATING COIL 3776.78
SPLIT MS1 HEATING COIL 3745.54
SPLIT MS2 HEATING COIL 3745.54
SPLIT TSW HEATING COIL 4132.10
SPLIT TNW HEATING COIL 4150.84
SPLIT TSE HEATING COIL 4132.10
SPLIT TNE HEATING COIL 4150.84
SPLIT TN1 HEATING COIL 3139.73
SPLIT TN2 HEATING COIL 3139.73
SPLIT TS1 HEATING COIL 3119.03
SPLIT TS2 HEATING COIL 3119.03



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:02

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 4.12
February 21.99 6.58
March 22.52 12.40
April 23.27 16.79
May 24.09 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.64 16.70
November 22.66 12.13
December 21.93 6.84
     
Annual Sum or Average 23.30 17.04
Minimum of Months 21.85 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 4.12
February 21.79 6.58
March 22.25 12.40
April 23.09 16.79
May 24.07 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.30 16.70
November 22.26 12.13
December 21.79 6.84
     
Annual Sum or Average 23.16 17.04
Minimum of Months 21.75 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.05 4.12
February 21.71 6.58
March 23.28 12.40
April 24.29 16.79
May 25.52 22.07
June 26.81 26.01
July 27.25 28.31
August 27.01 27.55
September 26.93 24.35
October 24.69 16.70
November 23.46 12.13
December 21.83 6.84
     
Annual Sum or Average 24.50 17.04
Minimum of Months 21.05 4.12
Maximum of Months 27.25 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.77 6.58
March 22.17 12.40
April 23.05 16.79
May 24.06 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.20 16.70
November 22.18 12.13
December 21.78 6.84
     
Annual Sum or Average 23.13 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.76 6.58
March 22.10 12.40
April 22.90 16.79
May 23.98 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.15 16.70
November 22.17 12.13
December 21.78 6.84
     
Annual Sum or Average 23.10 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 4.12
February 21.76 6.58
March 22.10 12.40
April 22.90 16.79
May 23.98 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.14 16.70
November 22.16 12.13
December 21.78 6.84
     
Annual Sum or Average 23.10 17.04
Minimum of Months 21.73 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 4.12
February 21.98 6.58
March 22.44 12.40
April 23.15 16.79
May 24.02 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.63 16.70
November 22.66 12.13
December 21.94 6.84
     
Annual Sum or Average 23.28 17.04
Minimum of Months 21.85 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 4.12
February 21.98 6.58
March 22.47 12.40
April 23.19 16.79
May 24.05 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.66 16.70
November 22.69 12.13
December 21.95 6.84
     
Annual Sum or Average 23.29 17.04
Minimum of Months 21.86 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.17 4.12
February 22.59 6.58
March 23.65 12.40
April 24.15 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.36 16.70
November 23.69 12.13
December 22.38 6.84
     
Annual Sum or Average 23.75 17.04
Minimum of Months 22.17 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 4.12
February 22.12 6.58
March 23.34 12.40
April 24.04 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.28 16.70
November 23.35 12.13
December 21.95 6.84
     
Annual Sum or Average 23.59 17.04
Minimum of Months 21.89 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.12 4.12
February 22.58 6.58
March 23.61 12.40
April 24.14 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.35 16.70
November 23.65 12.13
December 22.33 6.84
     
Annual Sum or Average 23.74 17.04
Minimum of Months 22.12 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 4.12
February 22.09 6.58
March 23.28 12.40
April 24.01 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.26 16.70
November 23.27 12.13
December 21.91 6.84
     
Annual Sum or Average 23.56 17.04
Minimum of Months 21.85 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 4.12
February 22.18 6.58
March 23.42 12.40
April 24.09 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.32 16.70
November 23.50 12.13
December 22.01 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 21.92 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 4.12
February 22.18 6.58
March 23.41 12.40
April 24.08 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.31 16.70
November 23.49 12.13
December 22.00 6.84
     
Annual Sum or Average 23.62 17.04
Minimum of Months 21.92 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 4.12
February 22.77 6.58
March 23.79 12.40
April 24.22 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.38 16.70
November 23.91 12.13
December 22.69 6.84
     
Annual Sum or Average 23.84 17.04
Minimum of Months 22.31 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 4.12
February 22.77 6.58
March 23.79 12.40
April 24.22 16.79
May 24.40 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.40 24.35
October 24.38 16.70
November 23.91 12.13
December 22.69 6.84
     
Annual Sum or Average 23.84 17.04
Minimum of Months 22.31 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.05 4.12
February 22.35 6.58
March 23.23 12.40
April 23.84 16.79
May 24.36 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 24.02 16.70
November 23.16 12.13
December 22.23 6.84
     
Annual Sum or Average 23.57 17.04
Minimum of Months 22.05 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 4.12
February 22.09 6.58
March 23.00 12.40
April 23.76 16.79
May 24.35 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.83 16.70
November 22.85 12.13
December 21.95 6.84
     
Annual Sum or Average 23.45 17.04
Minimum of Months 21.86 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 4.12
February 22.36 6.58
March 23.21 12.40
April 23.86 16.79
May 24.36 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 24.01 16.70
November 23.15 12.13
December 22.20 6.84
     
Annual Sum or Average 23.57 17.04
Minimum of Months 22.01 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 4.12
February 22.05 6.58
March 22.94 12.40
April 23.77 16.79
May 24.35 22.07
June 24.39 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.81 16.70
November 22.80 12.13
December 21.92 6.84
     
Annual Sum or Average 23.43 17.04
Minimum of Months 21.82 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 4.12
February 22.09 6.58
March 23.04 12.40
April 23.80 16.79
May 24.37 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 23.86 16.70
November 22.86 12.13
December 21.95 6.84
     
Annual Sum or Average 23.46 17.04
Minimum of Months 21.87 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 4.12
February 22.08 6.58
March 23.03 12.40
April 23.80 16.79
May 24.37 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.38 24.35
October 23.86 16.70
November 22.86 12.13
December 21.95 6.84
     
Annual Sum or Average 23.46 17.04
Minimum of Months 21.87 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.14 4.12
February 22.45 6.58
March 23.36 12.40
April 23.91 16.79
May 24.37 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 24.09 16.70
November 23.27 12.13
December 22.33 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 22.14 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.14 4.12
February 22.46 6.58
March 23.36 12.40
April 23.91 16.79
May 24.37 22.07
June 24.40 26.01
July 24.40 28.31
August 24.40 27.55
September 24.39 24.35
October 24.09 16.70
November 23.27 12.13
December 22.33 6.84
     
Annual Sum or Average 23.63 17.04
Minimum of Months 22.14 4.12
Maximum of Months 24.40 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.57 4.12
February 22.23 6.58
March 24.04 12.40
April 25.28 16.79
May 26.46 22.07
June 27.00 26.01
July 27.24 28.31
August 27.13 27.55
September 26.72 24.35
October 25.33 16.70
November 23.81 12.13
December 22.11 6.84
     
Annual Sum or Average 24.92 17.04
Minimum of Months 21.57 4.12
Maximum of Months 27.24 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.35 4.12
February 19.95 6.58
March 21.65 12.40
April 23.05 16.79
May 24.73 22.07
June 26.59 26.01
July 27.21 28.31
August 27.07 27.55
September 26.41 24.35
October 23.47 16.70
November 21.79 12.13
December 20.11 6.84
     
Annual Sum or Average 23.47 17.04
Minimum of Months 19.35 4.12
Maximum of Months 27.21 28.31



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:48:02

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 4.12
February 23.69 6.58
March 25.26 12.40
April 26.06 16.79
May 26.65 22.07
June 26.88 26.01
July 26.99 28.31
August 26.95 27.55
September 26.79 24.35
October 26.34 16.70
November 25.38 12.13
December 23.66 6.84
     
Annual Sum or Average 25.66 17.04
Minimum of Months 23.20 4.12
Maximum of Months 26.99 28.31



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:02

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.111449E+12 71000.014 08-JAN-18:45 4979.953 26630.920 6993.962 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 29842.178 0.000 0.000 0.000
February 0.100801E+12 68368.796 08-FEB-18:00 4979.953 26630.920 6993.962 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 27210.960 0.000 0.000 0.000
March 0.113179E+12 69846.019 27-MAR-18:30 5482.595 23748.115 6993.962 0.000 6463.670 2553.000 0.000 0.000 0.000 0.000 0.000 24604.678 0.000 0.000 0.000
April 0.113152E+12 73845.365 24-APR-17:15 4979.953 26630.920 6993.962 0.000 14576.610 0.000 0.000 0.000 0.000 0.000 0.000 20663.919 0.000 0.000 0.000
May 0.127784E+12 77879.947 31-MAY-17:15 4979.953 26630.920 6993.962 0.000 23346.102 0.000 0.000 0.000 0.000 0.000 0.000 15929.009 0.000 0.000 0.000
June 0.136038E+12 81365.309 02-JUN-17:30 4979.953 26630.920 6993.962 0.000 24594.534 0.000 0.000 0.000 0.000 0.000 0.000 18165.939 0.000 0.000 0.000
July 0.146752E+12 86112.044 23-JUL-17:15 4979.953 26630.920 6993.962 0.000 27592.546 0.000 0.000 0.000 0.000 0.000 0.000 19914.662 0.000 0.000 0.000
August 0.144017E+12 88227.609 29-AUG-16:45 4276.255 26730.986 6993.962 0.000 29187.380 0.000 0.000 0.000 0.000 0.000 0.000 21039.026 0.000 0.000 0.000
September 0.131941E+12 83622.738 22-SEP-16:30 4276.255 26630.920 6993.962 0.000 24645.128 0.000 0.000 0.000 0.000 0.000 0.000 21076.472 0.000 0.000 0.000
October 0.116127E+12 77832.279 01-OCT-17:45 4979.953 26630.920 6993.962 0.000 18090.352 2553.000 0.000 0.000 0.000 0.000 0.000 18584.091 0.000 0.000 0.000
November 0.107991E+12 67467.107 02-NOV-17:15 4979.953 26630.920 6993.962 0.000 5623.252 2553.000 0.000 0.000 0.000 0.000 0.000 20686.019 0.000 0.000 0.000
December 0.110374E+12 65750.853 21-DEC-18:00 4979.953 26630.920 6993.962 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 24593.017 0.000 0.000 0.000
                                     
Annual Sum or Average 0.145961E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.100801E+12 65750.853   4276.255 23748.115 6993.962 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 15929.009 0.000 0.000 0.000
Maximum of Months 0.146752E+12 88227.609   5482.595 26730.986 6993.962 0.000 29187.380 2553.000 0.000 0.000 0.000 0.000 0.000 29842.178 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:02

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.814499E+11 109600.427 31-JAN-07:15 109600.427 0.000 0.000 0.000 0.000 0.000 109600.427
February 0.472334E+11 94728.812 12-FEB-02:00 94728.812 0.000 0.000 0.000 0.000 0.000 94728.812
March 0.105490E+11 51774.363 10-MAR-03:00 51774.363 0.000 0.000 0.000 0.000 0.000 51774.363
April 0.247425E+10 31751.886 13-APR-02:00 31751.886 0.000 0.000 0.000 0.000 0.000 31751.886
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.512204E+09 7476.022 16-OCT-05:00 7476.022 0.000 0.000 0.000 0.000 0.000 7476.022
November 0.850964E+10 38348.025 22-NOV-04:00 38348.025 0.000 0.000 0.000 0.000 0.000 38348.025
December 0.409662E+11 70335.978 09-DEC-03:00 70335.978 0.000 0.000 0.000 0.000 0.000 70335.978
                     
Annual Sum or Average 0.191695E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.814499E+11 109600.427   109600.427 0.000 0.000 0.000 0.000 0.000 109600.427