Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300

Simulation Timestamp: 2015-09-09 18:47:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2009.85 641.18 711.71
Net Site Energy 2009.85 641.18 711.71
Total Source Energy 5167.51 1648.53 1829.87
Net Source Energy 5167.51 1648.53 1829.87


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 574.98 0.00 0.00 0.00 0.00
Cooling 116.32 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.07 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 230.57 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 411.79 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1434.87 574.98 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 574.98 0.00 0.00 0.00 0.00
Cooling General 116.32 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.07 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 230.57 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 411.79 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.14 0.00 0.00 0.00 0.00 0.00
HVAC 268.66 203.61 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 508.10 203.61 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.58 0.00 0.00 0.00 0.00 0.00
HVAC 242.03 183.43 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 457.75 183.43 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1434.87 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1434.87 100.00
     
Total On-Site and Utility Electric Sources 1434.87 100.00
Total Electricity End Uses 1434.87 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 43.00
Time Setpoint Not Met During Occupied Cooling 0.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 3403.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Weather File Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Latitude [deg] 41.98
Longitude [deg] -87.9
Elevation [m] 201.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-JUL-17:00 27-JAN-00:00 - - - 01-JAN-07:15
Heating 0.00 159144.11 0.00 0.00 0.00 0.00
Cooling 25197.42 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7311.31 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24933.99 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 89053.59 159144.11 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 159144.11 0.00 0.00 0.00 0.00
Cooling General 25197.42 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7311.31 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 24933.99 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 623.28 0.00 0.00 0.00
Cooling 368.38 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.91 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 730.21 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1304.15 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4544.23 623.28 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 220.71 0.00 0.00 0.00
Cooling 130.45 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.94 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 258.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 461.81 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1609.16 220.71 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 220.71 0.00 0.00 0.00
Cooling 130.45 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.94 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 258.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 461.81 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1609.16 220.71 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB -20.00 0.00 -20.00 Wetbulb [C] 4.90 270.00
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 33.30 10.50 23.70 Wetbulb [C] 5.20 230.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.62 83.62 40.07
Exterior Lighting Total 2553.00           40.07



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3615.57 2605.16 1010.41 0.72 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3439.93 2482.07 957.86 0.72 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8081.51 6362.05 1719.46 0.79 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2704.56 1906.43 798.13 0.70 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2189.20 1512.35 676.86 0.69 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2171.21 1498.04 673.17 0.69 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2557.94 1769.06 788.89 0.69 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2608.08 1809.47 798.61 0.69 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9517.41 7002.31 2515.10 0.74 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   9040.27 6642.70 2397.57 0.73 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8947.10 6484.34 2462.76 0.72 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7430.85 5383.14 2047.71 0.72 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5855.25 4175.88 1679.37 0.71 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5825.73 4152.12 1673.61 0.71 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6846.57 4884.48 1962.09 0.71 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6866.13 4900.33 1965.80 0.71 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6385.88 4743.80 1642.07 0.74 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5898.42 4374.36 1524.05 0.74 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   6019.55 4445.49 1574.06 0.74 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5164.63 3749.10 1415.53 0.73 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4082.32 2943.78 1138.55 0.72 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4083.77 2944.84 1138.93 0.72 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4896.49 3604.09 1292.40 0.74 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4908.88 3614.20 1294.68 0.74 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3480.3 3.27 11.15 11.60 11.07
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3310.8 3.26 11.14 11.60 11.06
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7710.6 3.15 10.74 11.16 10.47
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2608.7 3.30 11.24 11.71 11.22
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2115.6 3.32 11.33 11.81 11.36
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2098.4 3.32 11.34 11.82 11.37
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2471.6 3.32 11.33 11.81 11.35
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2519.4 3.32 11.32 11.79 11.33
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 9142.9 3.24 11.05 11.50 10.93
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 8685.6 3.24 11.06 11.51 10.94
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 8607.6 3.26 11.12 11.58 11.03
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7149.1 3.26 11.12 11.58 11.04
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5641.6 3.28 11.19 11.65 11.14
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5613.5 3.28 11.19 11.66 11.15
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6596.6 3.28 11.19 11.65 11.14
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6615.2 3.28 11.19 11.65 11.14
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6128.8 3.23 11.01 11.45 10.87
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5661.9 3.23 11.01 11.46 10.88
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5780.6 3.23 11.03 11.48 10.91
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4967.9 3.26 11.11 11.57 11.02
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3929.3 3.27 11.14 11.60 11.07
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3930.7 3.27 11.14 11.60 11.07
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4703.6 3.24 11.05 11.50 10.93
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4715.4 3.24 11.05 11.50 10.93
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   4216.86 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   4173.98 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   6928.90 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   4162.43 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   3123.07 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   3122.81 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   3122.83 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   3256.81 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   8602.32 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   8606.02 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   8572.26 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   8575.94 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   5907.26 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   5906.53 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   5905.97 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   5905.25 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   6192.06 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   6195.79 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   6176.35 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   6180.07 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   4672.09 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   4671.68 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   4666.85 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   4666.45 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 199.67 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 190.64 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 549.12 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 141.29 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 108.49 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 107.24 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 127.14 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 130.73 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 553.20 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.45 523.83 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.43 501.29 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 415.90 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 315.15 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 313.05 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 368.81 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 370.23 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 379.86 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 349.46 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 353.07 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 290.52 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 225.89 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 225.98 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 284.91 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 285.82 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1787.23 2144.67 0.143 0.172 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.57 0.01496
G NW APARTMENT 1706.40 2047.68 0.137 0.164 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 30.78 0.01496
OFFICE 4678.59 5614.31 0.394 0.473 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 28.42 0.01496
G NE APARTMENT 1264.59 1517.51 0.101 0.122 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
G N1 APARTMENT 971.15 1165.38 0.078 0.093 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
G N2 APARTMENT 959.97 1151.96 0.077 0.092 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
G S1 APARTMENT 1138.04 1365.65 0.091 0.110 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
G S2 APARTMENT 1170.15 1404.18 0.094 0.113 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
M SW APARTMENT 4951.37 5941.64 0.397 0.477 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.57 0.01496
M NW APARTMENT 4688.75 5626.50 0.376 0.451 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 30.78 0.01496
M SE APARTMENT 4486.55 5383.85 0.360 0.432 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 32.91 0.01496
M NE APARTMENT 3722.22 4466.67 0.299 0.358 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 29.70 0.01496
M N1 APARTMENT 2820.99 3385.18 0.226 0.271 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
M N2 APARTMENT 2802.14 3362.57 0.225 0.270 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.99 0.01496
M S1 APARTMENT 3301.13 3961.36 0.265 0.318 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
M S2 APARTMENT 3313.80 3976.56 0.266 0.319 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
T SW APARTMENT 3399.44 4079.32 0.273 0.327 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 32.98 0.01496
T NW APARTMENT 3127.44 3752.93 0.251 0.301 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.04 0.01496
T SE APARTMENT 3159.73 3791.67 0.253 0.304 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.04 0.01496
T NE APARTMENT 2599.98 3119.97 0.209 0.250 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.30 0.01496
T N1 APARTMENT 2021.78 2426.13 0.162 0.195 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.30 0.01496
T N2 APARTMENT 2022.53 2427.04 0.162 0.195 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.30 0.01496
T S1 APARTMENT 2549.99 3059.99 0.205 0.245 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.17 0.01496
T S2 APARTMENT 2558.13 3069.76 0.205 0.246 CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 33.17 0.01496


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2445.24 2934.29 0.072 0.086 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G NW APARTMENT 2448.38 2938.06 0.072 0.087 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
OFFICE 4319.73 5183.67 0.123 0.148 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G NE APARTMENT 2438.61 2926.33 0.072 0.086 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G N1 APARTMENT 1559.66 1871.59 0.046 0.055 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G N2 APARTMENT 1559.44 1871.32 0.046 0.055 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G S1 APARTMENT 1559.45 1871.34 0.046 0.055 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
G S2 APARTMENT 1672.76 2007.31 0.049 0.059 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -20.00 0.00065
M SW APARTMENT 5112.09 6134.50 0.151 0.181 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M NW APARTMENT 5115.21 6138.26 0.151 0.181 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M SE APARTMENT 5086.67 6104.00 0.150 0.180 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M NE APARTMENT 5089.78 6107.73 0.150 0.180 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M N1 APARTMENT 2832.89 3399.46 0.083 0.100 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M N2 APARTMENT 2832.27 3398.72 0.083 0.100 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M S1 APARTMENT 2831.79 3398.15 0.083 0.100 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
M S2 APARTMENT 2831.18 3397.42 0.083 0.100 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T SW APARTMENT 4155.14 4986.17 0.122 0.147 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T NW APARTMENT 4158.30 4989.96 0.123 0.147 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T SE APARTMENT 4141.86 4970.23 0.122 0.146 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T NE APARTMENT 4145.00 4974.00 0.122 0.147 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T N1 APARTMENT 2869.70 3443.64 0.085 0.101 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T N2 APARTMENT 2869.36 3443.23 0.085 0.101 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T S1 APARTMENT 2865.27 3438.32 0.084 0.101 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065
T S2 APARTMENT 2864.93 3437.91 0.084 0.101 CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -20.00 0.00065


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.17 0.17 0.09 0.09
SPLIT GNW 0.16 0.16 0.09 0.09
SPLIT OFFICE 0.47 0.47 0.15 0.15
SPLIT GNE 0.12 0.12 0.09 0.09
SPLIT GN1 0.09 0.09 0.06 0.06
SPLIT GN2 0.09 0.09 0.06 0.06
SPLIT GS1 0.11 0.11 0.06 0.06
SPLIT GS2 0.11 0.11 0.06 0.06
SPLIT MSW 0.48 0.48 0.18 0.18
SPLIT MNW 0.45 0.45 0.18 0.18
SPLIT MSE 0.43 0.43 0.18 0.18
SPLIT MNE 0.36 0.36 0.18 0.18
SPLIT MN1 0.27 0.27 0.10 0.10
SPLIT MN2 0.27 0.27 0.10 0.10
SPLIT MS1 0.32 0.32 0.10 0.10
SPLIT MS2 0.32 0.32 0.10 0.10
SPLIT TSW 0.33 0.33 0.15 0.15
SPLIT TNW 0.30 0.30 0.15 0.15
SPLIT TSE 0.30 0.30 0.15 0.15
SPLIT TNE 0.25 0.25 0.15 0.15
SPLIT TN1 0.19 0.19 0.10 0.10
SPLIT TN2 0.19 0.19 0.10 0.10
SPLIT TS1 0.25 0.25 0.10 0.10
SPLIT TS2 0.25 0.25 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4053.25 6398.00 2208.75
G NW APARTMENT 4392.75 6644.25 2793.50
OFFICE 861.25 1426.00 268.00
G NE APARTMENT 4397.00 6655.75 2782.00
G N1 APARTMENT 3691.25 6797.75 2287.75
G N2 APARTMENT 3692.50 6798.25 2288.50
G S1 APARTMENT 3283.75 6481.75 1583.00
G S2 APARTMENT 3484.75 6372.75 1679.25
M SW APARTMENT 3726.50 4727.00 705.25
M NW APARTMENT 3996.50 5157.75 1270.25
M SE APARTMENT 3707.50 4746.25 688.25
M NE APARTMENT 3998.50 5234.00 1278.25
M N1 APARTMENT 3420.50 5028.00 719.75
M N2 APARTMENT 3417.00 5042.25 720.50
M S1 APARTMENT 3356.50 4519.75 275.25
M S2 APARTMENT 3358.00 4519.75 277.50
T SW APARTMENT 5079.25 5497.75 2464.00
T NW APARTMENT 5351.50 5817.00 2950.00
T SE APARTMENT 5067.25 5488.75 2425.25
T NE APARTMENT 5348.75 5822.00 2927.00
T N1 APARTMENT 4900.50 5771.75 2515.25
T N2 APARTMENT 4904.75 5773.75 2517.50
T S1 APARTMENT 4558.25 5379.75 1921.25
T S2 APARTMENT 4561.00 5378.25 1923.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6158.50 6868.50 3403.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.00 0.00 3.00 0.00
G NW APARTMENT 3.00 0.00 3.00 0.00
OFFICE 13.00 11.75 0.00 0.00
G NE APARTMENT 3.00 0.00 3.00 0.00
G N1 APARTMENT 5.25 0.50 5.25 0.50
G N2 APARTMENT 5.00 0.25 5.00 0.25
G S1 APARTMENT 3.00 0.00 3.00 0.00
G S2 APARTMENT 2.50 0.00 2.50 0.00
M SW APARTMENT 1.75 0.00 1.75 0.00
M NW APARTMENT 2.75 0.00 2.75 0.00
M SE APARTMENT 1.25 0.00 1.25 0.00
M NE APARTMENT 5.50 0.00 5.50 0.00
M N1 APARTMENT 3.75 0.00 3.75 0.00
M N2 APARTMENT 3.75 0.00 3.75 0.00
M S1 APARTMENT 1.25 0.00 1.25 0.00
M S2 APARTMENT 2.25 0.00 2.25 0.00
T SW APARTMENT 2.50 0.00 2.50 0.00
T NW APARTMENT 3.50 0.00 3.50 0.00
T SE APARTMENT 2.25 0.00 2.25 0.00
T NE APARTMENT 4.00 0.00 4.00 0.00
T N1 APARTMENT 1.25 0.00 1.25 0.00
T N2 APARTMENT 0.75 0.00 0.75 0.00
T S1 APARTMENT 1.50 0.00 1.50 0.00
T S2 APARTMENT 1.50 0.00 1.50 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 56.00 12.50 43.00 0.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.366 0.207 0.000 0.075
G NW APARTMENT 1.71 2.50 268.97 0.353 0.207 0.000 0.074
OFFICE 0.94 1.00 268.97 0.519 0.235 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.353 0.207 0.000 0.074
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.125 0.000 0.074
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.125 0.000 0.074
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.125 0.000 0.074
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.125 0.000 0.075
M SW APARTMENT 1.71 2.50 268.97 0.354 0.298 0.000 0.094
M NW APARTMENT 1.71 2.50 268.97 0.353 0.297 0.000 0.094
M SE APARTMENT 1.71 2.50 268.97 0.354 0.298 0.000 0.094
M NE APARTMENT 1.71 2.50 268.97 0.353 0.297 0.000 0.094
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.179 0.000 0.094
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.179 0.000 0.094
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.180 0.000 0.094
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.180 0.000 0.094
T SW APARTMENT 1.71 2.50 268.97 0.353 0.393 0.000 0.112
T NW APARTMENT 1.71 2.50 268.97 0.353 0.393 0.000 0.112
T SE APARTMENT 1.71 2.50 268.97 0.353 0.393 0.000 0.112
T NE APARTMENT 1.71 2.50 268.97 0.353 0.393 0.000 0.112
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.237 0.000 0.112
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.237 0.000 0.112
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.237 0.000 0.112
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.237 0.000 0.112
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.352 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.498 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.358 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.357 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.340 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 411.79 0.00 01-JAN-00:15 32730.25 20-FEB-07:30
WaterSystems:Electricity 411.79 0.00 01-JAN-00:15 32730.25 20-FEB-07:30
Water Heater:WaterSystems:Electricity 411.79 0.00 01-JAN-00:15 32730.25 20-FEB-07:30
Fans:Electricity 230.57 7311.31 01-JAN-00:45 7311.31 01-JAN-06:30
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
ElectricityPurchased:Plant 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
Cogeneration:ElectricityPurchased 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
ElectricityNet:Plant 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
Cogeneration:ElectricityNet 1434.87 20423.92 01-JAN-03:15 89053.59 16-JUL-18:00
ExteriorLights:Electricity 40.07 0.00 01-JAN-07:30 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.07 0.00 01-JAN-07:30 2553.00 01-JAN-00:15
Electricity:HVAC 346.89 7311.31 01-JAN-00:45 38808.10 19-JUL-15:15
General:Fans:Electricity 230.57 7311.31 01-JAN-00:45 7311.31 01-JAN-06:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 116.32 0.00 01-JAN-00:15 31496.79 19-JUL-15:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 574.98 0.00 10-MAR-15:45 159144.11 27-JAN-01:00
Gas:HVAC 574.98 0.00 10-MAR-15:45 159144.11 27-JAN-01:00
Heating:Gas 574.98 0.00 10-MAR-15:45 159144.11 27-JAN-01:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1554.90 1590.43 24-APR-17:00 222035.64 27-JAN-01:00
EnergyTransfer:Building 619.25 1575.53 13-MAY-15:00 94720.35 27-JAN-01:00
EnergyTransfer:Zone:G SW APARTMENT 16.00 0.02 12-OCT-12:30 3011.11 27-JAN-01:00
Heating:EnergyTransfer 270.81 0.00 11-FEB-17:00 94720.35 27-JAN-01:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 9.24 0.00 10-JAN-11:00 3011.11 27-JAN-01:00
Cooling:EnergyTransfer 348.44 0.00 02-JAN-07:30 70049.02 19-JUL-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 6.75 0.00 01-JAN-00:15 1962.61 27-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 16.90 0.05 10-OCT-19:45 3069.04 27-JAN-01:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 11.70 0.00 11-FEB-14:30 3069.04 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 5.20 0.00 01-JAN-00:15 1841.13 05-JUL-17:30
EnergyTransfer:Zone:OFFICE 22.91 0.00 30-APR-06:45 4537.37 16-JUL-09:45
Heating:EnergyTransfer:Zone:OFFICE 2.84 0.00 01-JAN-00:15 4040.50 29-JAN-07:15
Cooling:EnergyTransfer:Zone:OFFICE 20.07 0.00 02-JAN-07:30 4537.37 16-JUL-09:45
EnergyTransfer:Zone:G NE APARTMENT 16.86 0.04 19-APR-01:30 3045.68 27-JAN-01:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 11.52 0.00 11-FEB-16:15 3045.68 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 5.34 0.00 01-JAN-00:15 1476.16 17-JUL-16:15
EnergyTransfer:Zone:G N1 APARTMENT 10.85 0.01 15-APR-02:00 1906.80 27-JAN-08:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 6.39 0.00 11-FEB-15:15 1906.80 27-JAN-08:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.46 0.00 01-JAN-00:15 1087.80 18-JUL-17:30
EnergyTransfer:Zone:G N2 APARTMENT 10.85 0.02 30-APR-04:15 1902.83 27-JAN-08:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 6.39 0.00 11-FEB-15:15 1902.83 27-JAN-08:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.46 0.00 01-JAN-00:15 1078.95 18-JUL-17:30
EnergyTransfer:Zone:G S1 APARTMENT 10.50 0.00 21-APR-19:45 1802.53 27-JAN-01:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 4.33 0.00 01-JAN-17:15 1802.53 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 6.18 0.00 01-JAN-00:15 1297.96 28-SEP-12:30
EnergyTransfer:Zone:G S2 APARTMENT 11.29 0.01 07-OCT-00:30 1914.10 27-JAN-01:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 4.85 0.00 05-JAN-12:45 1914.10 27-JAN-01:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 6.44 0.00 01-JAN-00:15 1310.12 28-SEP-12:30
EnergyTransfer:Zone:M SW APARTMENT 41.97 0.05 10-OCT-13:30 6702.57 27-JAN-01:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 13.82 0.00 01-JAN-16:15 6702.57 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 28.15 0.00 01-JAN-00:15 5451.13 27-SEP-15:15
EnergyTransfer:Zone:M NW APARTMENT 41.73 0.02 10-JUN-10:15 6706.55 27-JAN-01:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 19.75 0.00 10-FEB-17:45 6706.55 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 21.98 0.00 01-JAN-00:15 5022.98 05-JUL-17:30
EnergyTransfer:Zone:M SE APARTMENT 42.18 0.03 09-NOV-02:30 6634.16 26-JAN-22:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 13.61 0.00 01-JAN-16:15 6634.16 26-JAN-22:15
Cooling:EnergyTransfer:Zone:M SE APARTMENT 28.57 0.00 01-JAN-00:15 4951.54 16-APR-13:15
EnergyTransfer:Zone:M NE APARTMENT 42.02 0.07 25-OCT-09:30 6602.16 26-JAN-20:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 19.49 0.00 10-FEB-18:15 6602.16 26-JAN-20:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 22.53 0.00 01-JAN-00:15 4326.85 19-JUL-14:45
EnergyTransfer:Zone:M N1 APARTMENT 27.93 0.25 08-DEC-20:00 3751.84 26-JAN-22:45
Heating:EnergyTransfer:Zone:M N1 APARTMENT 7.54 0.00 01-JAN-16:15 3751.84 26-JAN-22:45
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 20.39 0.00 01-JAN-00:15 3186.78 19-JUL-15:15
EnergyTransfer:Zone:M N2 APARTMENT 27.94 0.14 18-MAR-18:30 3753.91 26-JAN-22:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 7.54 0.00 01-JAN-16:15 3753.91 26-JAN-22:30
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 20.40 0.00 01-JAN-00:15 3181.22 19-JUL-15:15
EnergyTransfer:Zone:M S1 APARTMENT 32.33 0.26 25-FEB-19:45 3909.04 26-SEP-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 3.82 0.00 01-JAN-09:00 3758.15 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 28.51 0.00 01-JAN-00:15 3909.04 26-SEP-12:45
EnergyTransfer:Zone:M S2 APARTMENT 32.34 0.40 06-FEB-09:45 3918.70 26-SEP-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 3.82 0.00 01-JAN-09:00 3759.28 27-JAN-01:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 28.52 0.00 01-JAN-00:15 3918.70 26-SEP-12:45
EnergyTransfer:Zone:T SW APARTMENT 31.18 0.00 25-MAY-22:30 5388.95 27-JAN-01:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 17.96 0.00 10-JAN-11:15 5388.95 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 13.22 0.00 01-JAN-00:15 3671.67 19-JUL-15:00
EnergyTransfer:Zone:T NW APARTMENT 32.07 0.06 23-OCT-18:15 5367.89 27-JAN-01:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 21.34 0.00 11-FEB-13:45 5367.89 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 10.73 0.00 01-JAN-00:15 3454.93 19-JUL-15:15
EnergyTransfer:Zone:T SE APARTMENT 30.92 0.01 04-NOV-06:45 5346.74 27-JAN-01:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 17.70 0.00 10-JAN-10:45 5346.74 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 13.22 0.00 01-JAN-00:15 3375.93 16-APR-13:15
EnergyTransfer:Zone:T NE APARTMENT 31.80 0.01 24-MAY-03:30 5288.46 27-JAN-01:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 21.02 0.00 11-FEB-13:30 5288.46 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 10.78 0.00 01-JAN-00:15 3095.85 19-JUL-15:00
EnergyTransfer:Zone:T N1 APARTMENT 22.33 0.05 19-APR-05:15 3657.95 27-JAN-01:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 13.05 0.00 11-FEB-12:30 3657.95 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 9.28 0.00 01-JAN-00:15 2393.31 19-JUL-15:15
EnergyTransfer:Zone:T N2 APARTMENT 22.33 0.02 11-MAR-09:15 3658.07 27-JAN-01:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 13.04 0.00 11-FEB-12:30 3658.07 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 9.28 0.00 01-JAN-00:15 2385.46 19-JUL-15:15
EnergyTransfer:Zone:T S1 APARTMENT 22.01 0.01 22-SEP-01:15 3693.83 27-JAN-01:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 10.03 0.00 05-JAN-13:45 3693.83 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 11.99 0.00 01-JAN-00:15 2788.42 16-APR-13:30
EnergyTransfer:Zone:T S2 APARTMENT 22.02 0.05 23-FEB-18:30 3694.50 27-JAN-01:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 10.03 0.00 05-JAN-13:45 3694.50 27-JAN-01:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 12.00 0.00 01-JAN-00:15 2793.16 16-APR-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 935.66 0.00 26-MAR-18:30 127315.28 27-JAN-01:00
HeatingCoils:EnergyTransfer 459.98 0.00 10-MAR-15:45 127315.28 27-JAN-01:00
CoolingCoils:EnergyTransfer 475.67 0.00 01-JAN-00:15 122318.41 19-JUL-15:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 9.244 -6.751 0.000 0.000 3.865 1.087 12.213 12.358 0.000 0.264 0.000 0.000 -7.719 0.000 -8.489 -16.071
G NW APARTMENT 11.701 -5.197 0.000 0.000 3.877 1.087 12.213 6.606 0.000 0.263 0.000 0.000 -8.162 0.000 -8.410 -13.977
OFFICE 2.839 -20.070 0.000 0.000 0.530 26.452 9.482 12.299 0.000 0.168 0.001 0.000 -7.451 0.000 -7.607 -16.641
G NE APARTMENT 11.519 -5.342 0.000 0.000 3.884 1.087 12.213 6.636 0.000 0.263 0.000 0.000 -7.968 0.000 -8.394 -13.897
G N1 APARTMENT 6.391 -4.455 0.000 0.000 3.883 1.087 12.213 2.570 0.000 0.173 0.000 0.000 -5.107 0.000 -5.326 -11.428
G N2 APARTMENT 6.388 -4.461 0.000 0.000 3.884 1.087 12.213 2.570 0.000 0.173 0.000 0.000 -5.106 0.000 -5.326 -11.421
G S1 APARTMENT 4.327 -6.177 0.000 0.000 3.865 1.087 12.213 8.365 0.000 0.172 0.000 0.000 -4.673 0.000 -5.411 -13.768
G S2 APARTMENT 4.848 -6.444 0.000 0.000 3.863 1.087 12.213 8.360 0.000 0.172 0.000 0.000 -4.671 0.000 -5.420 -14.007
M SW APARTMENT 13.819 -28.153 0.000 0.000 3.781 1.087 12.213 11.959 0.000 0.373 5.643 0.000 -8.308 0.000 -12.413 -0.000
M NW APARTMENT 19.750 -21.975 0.000 0.000 3.809 1.087 12.213 6.292 0.000 0.371 0.000 0.000 -8.712 0.000 -12.260 -0.575
M SE APARTMENT 13.606 -28.571 0.000 0.000 3.785 1.087 12.213 12.043 0.000 0.373 6.034 0.000 -8.162 0.000 -12.406 -0.000
M NE APARTMENT 19.490 -22.525 0.000 0.000 3.816 1.087 12.213 6.316 0.000 0.371 0.000 0.000 -8.495 0.000 -12.235 -0.037
M N1 APARTMENT 7.542 -20.392 0.000 0.000 3.802 1.087 12.213 2.374 0.000 0.239 6.442 0.000 -5.505 0.000 -7.802 -0.001
M N2 APARTMENT 7.543 -20.396 0.000 0.000 3.802 1.087 12.213 2.374 0.000 0.239 6.442 0.000 -5.503 0.000 -7.800 -0.001
M S1 APARTMENT 3.821 -28.509 0.000 0.000 3.765 1.087 12.213 8.106 0.000 0.241 12.268 0.000 -5.057 0.000 -7.934 -0.000
M S2 APARTMENT 3.823 -28.517 0.000 0.000 3.765 1.087 12.213 8.105 0.000 0.241 12.274 0.000 -5.056 0.000 -7.935 -0.000
T SW APARTMENT 17.957 -13.219 0.000 0.000 3.827 1.087 12.213 11.855 0.000 0.495 0.000 0.000 -7.933 0.000 -16.026 -10.255
T NW APARTMENT 21.340 -10.729 0.000 0.000 3.846 1.087 12.213 6.222 0.000 0.492 0.000 0.000 -8.352 0.000 -15.876 -10.242
T SE APARTMENT 17.697 -13.220 0.000 0.000 3.831 1.087 12.213 11.953 0.000 0.495 0.000 0.000 -7.800 0.000 -16.029 -10.226
T NE APARTMENT 21.020 -10.777 0.000 0.000 3.854 1.087 12.213 6.262 0.000 0.492 0.000 0.000 -8.151 0.000 -15.856 -10.143
T N1 APARTMENT 13.046 -9.284 0.000 0.000 3.843 1.087 12.213 2.362 0.000 0.319 0.000 0.000 -5.244 0.000 -10.002 -8.340
T N2 APARTMENT 13.045 -9.285 0.000 0.000 3.844 1.087 12.213 2.361 0.000 0.319 0.000 0.000 -5.242 0.000 -10.003 -8.338
T S1 APARTMENT 10.025 -11.987 0.000 0.000 3.815 1.087 12.213 8.054 0.000 0.322 0.000 0.000 -4.832 0.000 -10.150 -8.546
T S2 APARTMENT 10.026 -11.997 0.000 0.000 3.815 1.087 12.213 8.053 0.000 0.322 0.000 0.000 -4.831 0.000 -10.151 -8.536
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.100 0.000 0.023 0.000 0.000 -0.989 0.000 -2.646 -11.070
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.366 0.000 0.569 13.392 0.000 -2.551 0.000 -32.837 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.102 0.000 0.023 0.000 0.000 -1.077 0.000 -2.176 -11.453
Total Facility 270.809 -348.434 0.000 0.000 88.648 95.189 296.854 175.023 0.000 7.967 62.496 0.000 -162.657 0.000 -276.922 -208.974


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 27-SEP-15:15 0.00 -1962.27 0.00 0.00 48.90 45.40 470.90 2527.77 0.00 182.86 0.00 0.00 0.00 0.00 0.00 -1313.55
G NW APARTMENT 05-JUL-17:25 0.00 -1841.44 0.00 0.00 141.82 87.56 588.62 1839.86 0.00 212.53 0.00 0.00 0.00 0.00 0.00 -1028.93
OFFICE 07-AUG-06:01 0.00 -7389.19 0.00 0.00 0.00 416.15 294.31 1036.29 0.00 0.00 5745.23 0.00 0.00 0.00 -102.79 0.00
G NE APARTMENT 17-JUL-16:15 0.00 -1478.00 0.00 0.00 84.77 64.86 588.62 758.49 0.00 275.69 0.00 0.00 0.00 0.00 0.00 -294.43
G N1 APARTMENT 18-JUL-17:30 0.00 -1088.47 0.00 0.00 141.81 87.56 588.62 441.96 0.00 138.99 0.00 0.00 0.00 0.00 0.00 -310.47
G N2 APARTMENT 18-JUL-17:30 0.00 -1079.43 0.00 0.00 141.81 87.56 588.62 442.10 0.00 138.99 0.00 0.00 0.00 0.00 0.00 -319.65
G S1 APARTMENT 28-SEP-12:30 0.00 -1297.94 0.00 0.00 40.75 12.97 388.49 2161.04 0.00 46.83 0.00 0.00 0.00 0.00 0.00 -1352.15
G S2 APARTMENT 28-SEP-12:30 0.00 -1310.11 0.00 0.00 40.75 12.97 388.49 2160.81 0.00 46.83 0.00 0.00 0.00 0.00 0.00 -1339.75
M SW APARTMENT 27-SEP-15:15 0.00 -5450.32 0.00 0.00 48.90 45.40 470.90 2506.43 0.00 262.02 2116.67 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 05-JUL-17:10 0.00 -5026.42 0.00 0.00 141.83 87.56 588.62 1813.53 0.00 331.61 2063.28 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 16-APR-13:15 0.00 -4951.11 0.00 0.00 40.75 12.97 382.60 1932.18 0.00 329.15 2253.45 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 19-JUL-14:45 0.00 -4327.38 0.00 0.00 40.76 22.70 400.26 955.38 0.00 513.79 2394.50 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 19-JUL-15:15 0.00 -3187.18 0.00 0.00 48.90 45.40 470.90 527.11 0.00 318.50 1776.37 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 19-JUL-15:15 0.00 -3181.62 0.00 0.00 48.90 45.40 470.90 527.13 0.00 318.50 1770.79 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 26-SEP-12:45 0.00 -3909.39 0.00 0.00 40.75 12.97 388.49 2094.24 0.00 123.08 1249.86 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 26-SEP-12:45 0.00 -3919.06 0.00 0.00 40.75 12.97 388.49 2094.19 0.00 123.07 1259.59 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 19-JUL-15:00 0.00 -3672.27 0.00 0.00 40.76 22.70 400.26 1806.61 0.00 752.10 649.85 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 19-JUL-15:15 0.00 -3455.51 0.00 0.00 48.91 45.40 470.90 1612.40 0.00 695.90 582.01 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 16-APR-13:15 0.00 -3375.66 0.00 0.00 40.76 12.97 382.60 1892.76 0.00 432.39 614.18 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 19-JUL-15:00 0.00 -3096.48 0.00 0.00 40.76 22.70 400.26 893.62 0.00 752.13 987.01 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 19-JUL-15:15 0.00 -2393.71 0.00 0.00 48.91 45.40 470.90 514.01 0.00 419.70 894.79 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 19-JUL-15:15 0.00 -2385.87 0.00 0.00 48.91 45.40 470.90 514.10 0.00 419.70 886.86 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 16-APR-13:30 0.00 -2788.12 0.00 0.00 40.75 12.97 382.60 1536.42 0.00 267.44 547.93 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 16-APR-13:30 0.00 -2792.87 0.00 0.00 40.75 12.97 382.60 1536.33 0.00 267.44 552.77 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 19-JUL-15:15 0.00 -70060.71 0.00 0.00 1191.87 4512.09 11708.34 22777.56 0.00 10959.78 18911.06 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 27-JAN-01:00 3011.09 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1068.79 0.00 -1878.89 -524.44
G NW APARTMENT 27-JAN-01:00 3069.02 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1090.20 0.00 -1878.89 -560.97
OFFICE 19-MAR-06:01 6470.25 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -340.48 0.00 -419.24 -6420.99
G NE APARTMENT 27-JAN-01:00 3045.66 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1073.78 0.00 -1878.01 -554.92
G N1 APARTMENT 27-JAN-08:06 1907.79 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -588.77 0.00 -990.55 -810.40
G N2 APARTMENT 27-JAN-08:06 1903.82 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -588.81 0.00 -990.55 -806.38
G S1 APARTMENT 27-JAN-01:00 1802.52 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -640.33 0.00 -1133.30 -489.93
G S2 APARTMENT 27-JAN-01:00 1914.09 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -638.74 0.00 -1133.30 -603.09
M SW APARTMENT 27-JAN-01:00 6702.54 0.00 0.00 0.00 189.97 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1093.44 0.00 -2691.48 -3378.95
M NW APARTMENT 27-JAN-01:00 6706.52 0.00 0.00 0.00 190.91 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1115.01 0.00 -2681.28 -3372.51
M SE APARTMENT 26-JAN-22:06 6634.35 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -1047.22 0.00 -2729.35 -3504.28
M NE APARTMENT 26-JAN-20:00 6602.06 0.00 0.00 0.00 165.01 103.77 547.42 0.00 0.00 0.00 0.00 0.00 -1049.34 0.00 -2781.06 -3587.87
M N1 APARTMENT 26-JAN-22:45 3752.38 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -669.92 0.00 -1672.00 -2056.97
M N2 APARTMENT 26-JAN-22:28 3754.87 0.00 0.00 0.00 189.67 38.91 417.92 0.00 0.00 0.00 0.00 0.00 -665.92 0.00 -1659.72 -2075.73
M S1 APARTMENT 27-JAN-01:00 3758.13 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -655.16 0.00 -1628.88 -1935.13
M S2 APARTMENT 27-JAN-01:00 3759.26 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -655.13 0.00 -1628.83 -1936.34
T SW APARTMENT 27-JAN-01:00 5388.92 0.00 0.00 0.00 190.73 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1066.70 0.00 -3549.69 -1234.63
T NW APARTMENT 27-JAN-01:00 5367.86 0.00 0.00 0.00 191.82 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1088.75 0.00 -3537.19 -1205.10
T SE APARTMENT 27-JAN-01:00 5346.71 0.00 0.00 0.00 191.20 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1046.81 0.00 -3544.20 -1218.27
T NE APARTMENT 27-JAN-01:00 5288.43 0.00 0.00 0.00 192.94 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -1067.30 0.00 -3525.00 -1160.44
T N1 APARTMENT 27-JAN-01:00 3657.93 0.00 0.00 0.00 189.81 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -663.65 0.00 -2151.95 -1303.51
T N2 APARTMENT 27-JAN-01:00 3658.05 0.00 0.00 0.00 189.83 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -663.59 0.00 -2151.76 -1303.91
T S1 APARTMENT 27-JAN-01:00 3693.82 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -639.11 0.00 -2156.87 -1358.88
T S2 APARTMENT 27-JAN-01:00 3694.48 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -639.09 0.00 -2156.84 -1359.59
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-JAN-01:00 94719.90 0.00 0.00 0.00 4376.24 1952.47 6334.72 0.00 0.00 0.00 0.00 0.00 -21186.40 0.00 -53109.71 -33087.22



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Sec1.1A-General Information

Data
Weather File Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 43.00
Number of hours cooling loads not met 0.75
Number of hours not met 43.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.07 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 574.98 159144.11 0.00 0.00
Space Cooling 116.32 25197.42 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 230.57 7311.31 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 411.79 24933.99 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1434.87   574.98   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1434.87
Natural Gas 0.00 574.98
Additional 0.00 0.00
Total 517.65 2009.85


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 37.11
Fans-Interior 73.56
Service Water Heating 131.37
Receptacle Equipment 165.14
Miscellaneous 12.78
Subtotal 457.75


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 183.43
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 183.43


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.89
Space Heating 28.61
Space Cooling 5.79
Fans-Interior 11.47
Service Water Heating 20.49
Receptacle Equipment 25.76
Miscellaneous 1.99



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.172009
G NW APARTMENT DIRECT AIR 0.164224
OFFICE DIRECT AIR 0.473040
G NE APARTMENT DIRECT AIR 0.121716
G N1 APARTMENT DIRECT AIR 0.093460
G N2 APARTMENT DIRECT AIR 0.092384
G S1 APARTMENT DIRECT AIR 0.109527
G S2 APARTMENT DIRECT AIR 0.112617
M SW APARTMENT DIRECT AIR 0.476554
M NW APARTMENT DIRECT AIR 0.451255
M SE APARTMENT DIRECT AIR 0.431834
M NE APARTMENT DIRECT AIR 0.358272
M N1 APARTMENT DIRECT AIR 0.271487
M N2 APARTMENT DIRECT AIR 0.269674
M S1 APARTMENT DIRECT AIR 0.317714
M S2 APARTMENT DIRECT AIR 0.318933
T SW APARTMENT DIRECT AIR 0.327225
T NW APARTMENT DIRECT AIR 0.301043
T SE APARTMENT DIRECT AIR 0.304151
T NE APARTMENT DIRECT AIR 0.250270
T N1 APARTMENT DIRECT AIR 0.194593
T N2 APARTMENT DIRECT AIR 0.194666
T S1 APARTMENT DIRECT AIR 0.245433
T S2 APARTMENT DIRECT AIR 0.246216


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.172009
SPLIT GNW MAIN BRANCH 0.164224
SPLIT OFFICE MAIN BRANCH 0.473040
SPLIT GNE MAIN BRANCH 0.121716
SPLIT GN1 MAIN BRANCH 0.093460
SPLIT GN2 MAIN BRANCH 0.092384
SPLIT GS1 MAIN BRANCH 0.109527
SPLIT GS2 MAIN BRANCH 0.112617
SPLIT MSW MAIN BRANCH 0.476554
SPLIT MNW MAIN BRANCH 0.451255
SPLIT MSE MAIN BRANCH 0.431834
SPLIT MNE MAIN BRANCH 0.358272
SPLIT MN1 MAIN BRANCH 0.271487
SPLIT MN2 MAIN BRANCH 0.269674
SPLIT MS1 MAIN BRANCH 0.317714
SPLIT MS2 MAIN BRANCH 0.318933
SPLIT TSW MAIN BRANCH 0.327225
SPLIT TNW MAIN BRANCH 0.301043
SPLIT TSE MAIN BRANCH 0.304151
SPLIT TNE MAIN BRANCH 0.250270
SPLIT TN1 MAIN BRANCH 0.194593
SPLIT TN2 MAIN BRANCH 0.194666
SPLIT TS1 MAIN BRANCH 0.245433
SPLIT TS2 MAIN BRANCH 0.246216


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.172009
SPLIT GNW 0.164224
SPLIT OFFICE 0.473040
SPLIT GNE 0.121716
SPLIT GN1 0.093460
SPLIT GN2 0.092384
SPLIT GS1 0.109527
SPLIT GS2 0.112617
SPLIT MSW 0.476554
SPLIT MNW 0.451255
SPLIT MSE 0.431834
SPLIT MNE 0.358272
SPLIT MN1 0.271487
SPLIT MN2 0.269674
SPLIT MS1 0.317714
SPLIT MS2 0.318933
SPLIT TSW 0.327225
SPLIT TNW 0.301043
SPLIT TSE 0.304151
SPLIT TNE 0.250270
SPLIT TN1 0.194593
SPLIT TN2 0.194666
SPLIT TS1 0.245433
SPLIT TS2 0.246216


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.172009 0.026898
SPLIT GNW OA CONTROLLER 0.164224 0.025953
SPLIT OFFICE OA CONTROLLER 0.473040 0.038104
SPLIT GNE OA CONTROLLER 0.121716 0.025953
SPLIT GN1 OA CONTROLLER 0.093460 0.025953
SPLIT GN2 OA CONTROLLER 0.092384 0.025953
SPLIT GS1 OA CONTROLLER 0.109527 0.025953
SPLIT GS2 OA CONTROLLER 0.112617 0.025953
SPLIT MSW OA CONTROLLER 0.476554 0.051906
SPLIT MNW OA CONTROLLER 0.451255 0.051906
SPLIT MSE OA CONTROLLER 0.431834 0.051906
SPLIT MNE OA CONTROLLER 0.358272 0.051906
SPLIT MN1 OA CONTROLLER 0.271487 0.051906
SPLIT MN2 OA CONTROLLER 0.269674 0.051906
SPLIT MS1 OA CONTROLLER 0.317714 0.051906
SPLIT MS2 OA CONTROLLER 0.318933 0.051906
SPLIT TSW OA CONTROLLER 0.327225 0.025953
SPLIT TNW OA CONTROLLER 0.301043 0.025953
SPLIT TSE OA CONTROLLER 0.304151 0.025953
SPLIT TNE OA CONTROLLER 0.250270 0.025953
SPLIT TN1 OA CONTROLLER 0.194593 0.025953
SPLIT TN2 OA CONTROLLER 0.194666 0.025953
SPLIT TS1 OA CONTROLLER 0.245433 0.025953
SPLIT TS2 OA CONTROLLER 0.246216 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.172009 3615.57 0.720539
SPLIT GNW COOLING COIL 0.164224 3439.93 0.721548
SPLIT OFFICE COOLING COIL 0.473040 8081.51 0.787235
SPLIT GNE COOLING COIL 0.121716 2704.56 0.704894
SPLIT GN1 COOLING COIL 0.093460 2189.20 0.690820
SPLIT GN2 COOLING COIL 0.092384 2171.21 0.689958
SPLIT GS1 COOLING COIL 0.109527 2557.94 0.691593
SPLIT GS2 COOLING COIL 0.112617 2608.08 0.693794
SPLIT MSW COOLING COIL 0.476554 9517.41 0.735737
SPLIT MNW COOLING COIL 0.451255 9040.27 0.734790
SPLIT MSE COOLING COIL 0.431834 8947.10 0.724742
SPLIT MNE COOLING COIL 0.358272 7430.85 0.724431
SPLIT MN1 COOLING COIL 0.271487 5855.25 0.713186
SPLIT MN2 COOLING COIL 0.269674 5825.73 0.712721
SPLIT MS1 COOLING COIL 0.317714 6846.57 0.713420
SPLIT MS2 COOLING COIL 0.318933 6866.13 0.713696
SPLIT TSW COOLING COIL 0.327225 6385.88 0.742858
SPLIT TNW COOLING COIL 0.301043 5898.42 0.741617
SPLIT TSE COOLING COIL 0.304151 6019.55 0.738509
SPLIT TNE COOLING COIL 0.250270 5164.63 0.725918
SPLIT TN1 COOLING COIL 0.194593 4082.32 0.721103
SPLIT TN2 COOLING COIL 0.194666 4083.77 0.721108
SPLIT TS1 COOLING COIL 0.245433 4896.49 0.736056
SPLIT TS2 COOLING COIL 0.246216 4908.88 0.736257


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.172009 0.172009 0.172009 0.172009 4216.86 3615.57 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.164224 0.164224 0.164224 0.164224 4173.98 3439.93 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.473040 0.473040 0.473040 0.473040 6928.90 8081.51 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.121716 0.121716 0.121716 0.121716 4162.43 2704.56 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.093460 0.093460 0.093460 0.093460 3123.07 2189.20 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.092384 0.092384 0.092384 0.092384 3122.81 2171.21 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.109527 0.109527 0.109527 0.109527 3122.83 2557.94 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.112617 0.112617 0.112617 0.112617 3256.81 2608.08 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.476554 0.476554 0.476554 0.476554 8602.32 9517.41 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.451255 0.451255 0.451255 0.451255 8606.02 9040.27 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.431834 0.431834 0.431834 0.431834 8572.26 8947.10 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.358272 0.358272 0.358272 0.358272 8575.94 7430.85 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.271487 0.271487 0.271487 0.271487 5907.26 5855.25 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.269674 0.269674 0.269674 0.269674 5906.53 5825.73 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.317714 0.317714 0.317714 0.317714 5905.97 6846.57 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.318933 0.318933 0.318933 0.318933 5905.25 6866.13 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.327225 0.327225 0.327225 0.327225 6192.06 6385.88 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.301043 0.301043 0.301043 0.301043 6195.79 5898.42 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.304151 0.304151 0.304151 0.304151 6176.35 6019.55 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.250270 0.250270 0.250270 0.250270 6180.07 5164.63 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.194593 0.194593 0.194593 0.194593 4672.09 4082.32 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.194666 0.194666 0.194666 0.194666 4671.68 4083.77 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.245433 0.245433 0.245433 0.245433 4666.85 4896.49 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.246216 0.246216 0.246216 0.246216 4666.45 4908.88 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.172009
SPLIT GNW SUPPLY FAN 0.164224
SPLIT OFFICE SUPPLY FAN 0.473040
SPLIT GNE SUPPLY FAN 0.121716
SPLIT GN1 SUPPLY FAN 0.093460
SPLIT GN2 SUPPLY FAN 0.092384
SPLIT GS1 SUPPLY FAN 0.109527
SPLIT GS2 SUPPLY FAN 0.112617
SPLIT MSW SUPPLY FAN 0.476554
SPLIT MNW SUPPLY FAN 0.451255
SPLIT MSE SUPPLY FAN 0.431834
SPLIT MNE SUPPLY FAN 0.358272
SPLIT MN1 SUPPLY FAN 0.271487
SPLIT MN2 SUPPLY FAN 0.269674
SPLIT MS1 SUPPLY FAN 0.317714
SPLIT MS2 SUPPLY FAN 0.318933
SPLIT TSW SUPPLY FAN 0.327225
SPLIT TNW SUPPLY FAN 0.301043
SPLIT TSE SUPPLY FAN 0.304151
SPLIT TNE SUPPLY FAN 0.250270
SPLIT TN1 SUPPLY FAN 0.194593
SPLIT TN2 SUPPLY FAN 0.194666
SPLIT TS1 SUPPLY FAN 0.245433
SPLIT TS2 SUPPLY FAN 0.246216


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 4216.86
SPLIT GNW HEATING COIL 4173.98
SPLIT OFFICE HEATING COIL 6928.90
SPLIT GNE HEATING COIL 4162.43
SPLIT GN1 HEATING COIL 3123.07
SPLIT GN2 HEATING COIL 3122.81
SPLIT GS1 HEATING COIL 3122.83
SPLIT GS2 HEATING COIL 3256.81
SPLIT MSW HEATING COIL 8602.32
SPLIT MNW HEATING COIL 8606.02
SPLIT MSE HEATING COIL 8572.26
SPLIT MNE HEATING COIL 8575.94
SPLIT MN1 HEATING COIL 5907.26
SPLIT MN2 HEATING COIL 5906.53
SPLIT MS1 HEATING COIL 5905.97
SPLIT MS2 HEATING COIL 5905.25
SPLIT TSW HEATING COIL 6192.06
SPLIT TNW HEATING COIL 6195.79
SPLIT TSE HEATING COIL 6176.35
SPLIT TNE HEATING COIL 6180.07
SPLIT TN1 HEATING COIL 4672.09
SPLIT TN2 HEATING COIL 4671.68
SPLIT TS1 HEATING COIL 4666.85
SPLIT TS2 HEATING COIL 4666.45



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.80 3.82
April 22.36 9.95
May 22.99 15.31
June 24.23 21.11
July 24.39 24.13
August 24.37 21.78
September 24.18 18.14
October 22.44 10.98
November 21.88 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.82 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.72 3.82
April 22.24 9.95
May 22.87 15.31
June 24.22 21.11
July 24.39 24.13
August 24.37 21.78
September 24.10 18.14
October 22.06 10.98
November 21.79 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.74 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.05 -4.6
February 19.63 -2.5
March 21.11 3.82
April 22.50 9.95
May 24.08 15.31
June 25.87 21.11
July 26.70 24.13
August 26.24 21.78
September 25.80 18.14
October 23.25 10.98
November 21.28 4.73
December 19.27 -3.7
     
Annual Sum or Average 22.91 9.99
Minimum of Months 19.05 -4.6
Maximum of Months 26.70 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.19 9.95
May 22.81 15.31
June 24.19 21.11
July 24.38 24.13
August 24.36 21.78
September 24.07 18.14
October 22.00 10.98
November 21.77 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.72 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.15 9.95
May 22.66 15.31
June 24.20 21.11
July 24.38 24.13
August 24.36 21.78
September 24.10 18.14
October 22.01 10.98
November 21.78 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.71 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.71 3.82
April 22.14 9.95
May 22.66 15.31
June 24.19 21.11
July 24.38 24.13
August 24.36 21.78
September 24.10 18.14
October 22.00 10.98
November 21.78 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.71 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.38 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -4.6
February 21.71 -2.5
March 21.79 3.82
April 22.30 9.95
May 22.87 15.31
June 24.23 21.11
July 24.39 24.13
August 24.37 21.78
September 24.23 18.14
October 22.50 10.98
November 21.91 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.81 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -4.6
February 21.71 -2.5
March 21.79 3.82
April 22.31 9.95
May 22.90 15.31
June 24.25 21.11
July 24.39 24.13
August 24.38 21.78
September 24.25 18.14
October 22.53 10.98
November 21.93 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.83 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.77 -2.5
March 22.14 3.82
April 22.90 9.95
May 24.25 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.38 18.14
October 23.65 10.98
November 22.51 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.20 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.81 3.82
April 22.67 9.95
May 24.19 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.35 18.14
October 22.90 10.98
November 22.29 4.73
December 21.70 -3.7
     
Annual Sum or Average 23.05 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.76 -2.5
March 22.13 3.82
April 22.86 9.95
May 24.25 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.38 18.14
October 23.65 10.98
November 22.48 4.73
December 21.71 -3.7
     
Annual Sum or Average 23.19 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.77 3.82
April 22.60 9.95
May 24.15 15.31
June 24.38 21.11
July 24.40 24.13
August 24.40 21.78
September 24.34 18.14
October 22.83 10.98
November 22.22 4.73
December 21.70 -3.7
     
Annual Sum or Average 23.02 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.82 3.82
April 22.64 9.95
May 24.23 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.38 18.14
October 23.09 10.98
November 22.38 4.73
December 21.70 -3.7
     
Annual Sum or Average 23.08 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.82 3.82
April 22.64 9.95
May 24.22 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.38 18.14
October 23.09 10.98
November 22.37 4.73
December 21.70 -3.7
     
Annual Sum or Average 23.07 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.82 -2.5
March 22.29 3.82
April 23.00 9.95
May 24.31 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.40 18.14
October 23.98 10.98
November 22.66 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.27 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.6
February 21.82 -2.5
March 22.29 3.82
April 23.00 9.95
May 24.31 15.31
June 24.39 21.11
July 24.40 24.13
August 24.40 21.78
September 24.40 18.14
October 23.98 10.98
November 22.66 4.73
December 21.74 -3.7
     
Annual Sum or Average 23.27 9.99
Minimum of Months 21.74 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -4.6
February 21.76 -2.5
March 22.04 3.82
April 22.74 9.95
May 23.78 15.31
June 24.28 21.11
July 24.39 24.13
August 24.38 21.78
September 24.13 18.14
October 22.93 10.98
November 22.16 4.73
December 21.71 -3.7
     
Annual Sum or Average 23.01 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.71 -2.5
March 21.81 3.82
April 22.60 9.95
May 23.68 15.31
June 24.26 21.11
July 24.39 24.13
August 24.37 21.78
September 24.02 18.14
October 22.45 10.98
November 22.00 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.90 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -4.6
February 21.75 -2.5
March 22.04 3.82
April 22.73 9.95
May 23.78 15.31
June 24.27 21.11
July 24.39 24.13
August 24.38 21.78
September 24.13 18.14
October 22.93 10.98
November 22.13 4.73
December 21.71 -3.7
     
Annual Sum or Average 23.00 9.99
Minimum of Months 21.71 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.78 3.82
April 22.56 9.95
May 23.66 15.31
June 24.24 21.11
July 24.39 24.13
August 24.36 21.78
September 24.00 18.14
October 22.38 10.98
November 21.95 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.87 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.79 3.82
April 22.56 9.95
May 23.70 15.31
June 24.29 21.11
July 24.39 24.13
August 24.37 21.78
September 24.06 18.14
October 22.47 10.98
November 22.04 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.90 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.6
February 21.70 -2.5
March 21.79 3.82
April 22.56 9.95
May 23.70 15.31
June 24.28 21.11
July 24.39 24.13
August 24.37 21.78
September 24.06 18.14
October 22.47 10.98
November 22.04 4.73
December 21.70 -3.7
     
Annual Sum or Average 22.90 9.99
Minimum of Months 21.70 -4.6
Maximum of Months 24.39 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.78 -2.5
March 22.12 3.82
April 22.78 9.95
May 23.87 15.31
June 24.32 21.11
July 24.40 24.13
August 24.38 21.78
September 24.21 18.14
October 23.12 10.98
November 22.29 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.07 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -4.6
February 21.78 -2.5
March 22.13 3.82
April 22.78 9.95
May 23.87 15.31
June 24.32 21.11
July 24.40 24.13
August 24.38 21.78
September 24.21 18.14
October 23.12 10.98
November 22.29 4.73
December 21.72 -3.7
     
Annual Sum or Average 23.07 9.99
Minimum of Months 21.72 -4.6
Maximum of Months 24.40 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.32 -4.6
February 20.69 -2.5
March 21.79 3.82
April 23.36 9.95
May 25.27 15.31
June 26.45 21.11
July 26.92 24.13
August 26.56 21.78
September 25.82 18.14
October 23.50 10.98
November 21.90 4.73
December 20.44 -3.7
     
Annual Sum or Average 23.60 9.99
Minimum of Months 20.32 -4.6
Maximum of Months 26.92 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.48 -4.6
February 17.96 -2.5
March 19.39 3.82
April 21.01 9.95
May 22.80 15.31
June 25.46 21.11
July 26.36 24.13
August 25.85 21.78
September 24.95 18.14
October 21.62 10.98
November 19.71 4.73
December 17.74 -3.7
     
Annual Sum or Average 21.71 9.99
Minimum of Months 17.48 -4.6
Maximum of Months 26.36 24.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.42 -4.6
February 22.65 -2.5
March 23.36 3.82
April 24.46 9.95
May 26.26 15.31
June 26.74 21.11
July 26.92 24.13
August 26.77 21.78
September 26.55 18.14
October 25.16 10.98
November 23.73 4.73
December 22.48 -3.7
     
Annual Sum or Average 24.80 9.99
Minimum of Months 22.42 -4.6
Maximum of Months 26.92 24.13



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:16

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.116626E+12 73757.197 20-JAN-18:00 4979.953 26630.920 7311.308 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32282.015 0.000 0.000 0.000
February 0.105516E+12 71900.514 21-FEB-18:45 4979.953 26630.920 7311.308 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30425.332 0.000 0.000 0.000
March 0.116087E+12 72005.055 05-MAR-18:15 4979.953 26630.920 7311.308 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30529.873 0.000 0.000 0.000
April 0.115299E+12 79871.500 15-APR-17:45 4979.953 26630.920 7311.308 0.000 16268.299 0.000 0.000 0.000 0.000 0.000 0.000 24681.019 0.000 0.000 0.000
May 0.120602E+12 79553.476 30-MAY-17:45 4979.953 26630.920 7311.308 0.000 17080.711 0.000 0.000 0.000 0.000 0.000 0.000 23550.582 0.000 0.000 0.000
June 0.127535E+12 83285.733 27-JUN-17:15 4979.953 26630.920 7311.308 0.000 18661.807 0.000 0.000 0.000 0.000 0.000 0.000 25701.744 0.000 0.000 0.000
July 0.142572E+12 89053.588 16-JUL-17:00 4979.953 26630.920 7311.308 0.000 25197.417 0.000 0.000 0.000 0.000 0.000 0.000 24933.989 0.000 0.000 0.000
August 0.133782E+12 86931.828 04-AUG-17:15 4979.953 26630.920 7311.308 0.000 24615.474 0.000 0.000 0.000 0.000 0.000 0.000 23394.173 0.000 0.000 0.000
September 0.119494E+12 78035.777 09-SEP-17:15 4979.953 26630.920 7311.308 0.000 11738.081 0.000 0.000 0.000 0.000 0.000 0.000 27375.514 0.000 0.000 0.000
October 0.112478E+12 70081.601 21-OCT-17:15 4979.953 26630.920 7311.308 0.000 4932.987 2553.000 0.000 0.000 0.000 0.000 0.000 23673.433 0.000 0.000 0.000
November 0.109773E+12 70208.735 03-NOV-17:15 4979.953 26630.920 7311.308 0.000 4083.095 2553.000 0.000 0.000 0.000 0.000 0.000 24650.457 0.000 0.000 0.000
December 0.115104E+12 71076.535 14-DEC-18:45 4979.953 26630.920 7311.308 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 29601.353 0.000 0.000 0.000
                                     
Annual Sum or Average 0.143487E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.105516E+12 70081.601   4979.953 26630.920 7311.308 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 23394.173 0.000 0.000 0.000
Maximum of Months 0.142572E+12 89053.588   4979.953 26630.920 7311.308 0.000 25197.417 2553.000 0.000 0.000 0.000 0.000 0.000 32282.015 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:16

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.151971E+12 159144.106 27-JAN-00:00 159144.106 0.000 0.000 0.000 0.000 0.000 159144.106
February 0.113195E+12 110445.315 06-FEB-04:00 110445.315 0.000 0.000 0.000 0.000 0.000 110445.315
March 0.668911E+11 100697.455 05-MAR-04:00 100697.455 0.000 0.000 0.000 0.000 0.000 100697.455
April 0.280554E+11 56114.040 01-APR-00:15 56114.040 0.000 0.000 0.000 0.000 0.000 56114.040
May 0.164723E+10 13017.077 09-MAY-02:00 13017.077 0.000 0.000 0.000 0.000 0.000 13017.077
June 517019.243 319.420 25-JUN-04:15 319.420 0.000 0.000 0.000 0.000 0.000 319.420
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.132330E+08 620.499 21-SEP-04:00 620.499 0.000 0.000 0.000 0.000 0.000 620.499
October 0.105076E+11 30580.051 17-OCT-03:00 30580.051 0.000 0.000 0.000 0.000 0.000 30580.051
November 0.672244E+11 116287.659 25-NOV-22:00 116287.659 0.000 0.000 0.000 0.000 0.000 116287.659
December 0.135475E+12 120199.082 20-DEC-20:00 120199.082 0.000 0.000 0.000 0.000 0.000 120199.082
                     
Annual Sum or Average 0.574980E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.151971E+12 159144.106   159144.106 0.000 0.000 0.000 0.000 0.000 159144.106