Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Duluth International Arpt MN USA TMY3 WMO#=727450

Simulation Timestamp: 2015-09-09 18:47:40


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2320.61 740.32 821.75
Net Site Energy 2320.61 740.32 821.75
Total Source Energy 5430.22 1732.34 1922.90
Net Source Energy 5430.22 1732.34 1922.90


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 921.33 0.00 0.00 0.00 0.00
Cooling 51.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 208.21 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 463.66 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1399.27 921.33 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 921.33 0.00 0.00 0.00 0.00
Cooling General 51.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 208.21 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 463.66 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.13 0.00 0.00 0.00 0.00 0.00
HVAC 256.06 326.25 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 495.50 326.25 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.57 0.00 0.00 0.00 0.00 0.00
HVAC 230.69 293.92 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 446.39 293.92 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1399.27 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1399.27 100.00
     
Total On-Site and Utility Electric Sources 1399.27 100.00
Total Electricity End Uses 1399.27 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 38.00
Time Setpoint Not Met During Occupied Cooling 1.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3971.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Duluth International Arpt MN USA TMY3 WMO#=727450
Weather File Duluth International Arpt MN USA TMY3 WMO#=727450
Latitude [deg] 46.83
Longitude [deg] -92.2
Elevation [m] 433.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUN-17:00 19-DEC-02:00 - - - 01-JAN-07:15
Heating 0.00 177327.73 0.00 0.00 0.00 0.00
Cooling 17033.20 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6602.29 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 30600.80 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 85847.16 177327.73 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 177327.73 0.00 0.00 0.00 0.00
Cooling General 17033.20 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6602.29 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 30600.80 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 998.73 0.00 0.00 0.00
Cooling 162.26 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.83 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 659.40 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1468.42 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4431.50 998.73 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 353.66 0.00 0.00 0.00
Cooling 57.46 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.91 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 233.50 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 519.98 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1569.24 353.66 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 353.66 0.00 0.00 0.00
Cooling 57.46 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.91 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 233.50 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 519.98 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1569.24 353.66 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -28.60 0.00 -28.60 Wetbulb [C] 4.60 310.00
DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 29.20 10.90 21.00 Wetbulb [C] 5.20 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.295 0.309 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.295 0.309 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.295 0.309 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.295 0.309 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.295 0.309 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.295 0.309 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.295 0.309 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.295 0.309 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.295 0.309 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.295 0.309 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.295 0.309 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.295 0.309 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.295 0.309 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.295 0.309 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.295 0.309 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.295 0.309 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.295 0.309 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.295 0.309 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.295 0.309 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.295 0.309 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.295 0.309 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.295 0.309 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.295 0.309 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.295 0.309 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.219 0.228 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.295 0.309 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.295 0.309 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.295 0.309 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.295 0.309 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.42_SHGC_0.45 3.32 0.00 0.00 3.32 3.32 2.493 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 2.23 2.493 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.493 0.426 0.308              
North Total or Average           112.97 2.493 0.426 0.308              
Non-North Total or Average           193.95 2.493 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.57 83.57 40.05
Exterior Lighting Total 2553.00           40.05



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   2836.41 2147.06 689.35 0.76 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   2623.54 1980.36 643.18 0.75 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7699.75 6149.45 1550.30 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2057.81 1509.15 548.66 0.73 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1556.86 1131.32 425.54 0.73 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1538.85 1116.71 422.14 0.73 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2050.66 1492.52 558.14 0.73 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2099.60 1534.63 564.97 0.73 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   7946.89 6144.41 1802.48 0.77 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   7324.81 5638.56 1686.25 0.77 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7560.72 5752.86 1807.86 0.76 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5870.72 4447.39 1423.33 0.76 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4591.43 3458.10 1133.33 0.75 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4561.02 3432.96 1128.06 0.75 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5898.60 4442.33 1456.27 0.75 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5919.29 4459.61 1459.68 0.75 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5169.68 4005.51 1164.17 0.77 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4588.20 3554.17 1034.04 0.77 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4894.68 3768.22 1126.46 0.77 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   3819.29 2874.83 944.46 0.75 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2993.03 2240.81 752.22 0.75 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3000.58 2244.17 756.41 0.75 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4024.69 3094.15 930.54 0.77 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4038.78 3105.96 932.82 0.77 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2717.2 3.20 10.92 11.36 10.74
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2513.9 3.20 10.93 11.37 10.76
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7335.2 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1977.5 3.24 11.07 11.52 10.95
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1497.4 3.26 11.11 11.56 11.02
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1480.3 3.26 11.11 11.57 11.03
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1972.0 3.25 11.10 11.55 11.01
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2018.3 3.25 11.08 11.53 10.98
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7596.4 3.17 10.82 11.25 10.60
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7004.9 3.18 10.84 11.27 10.63
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7239.1 3.19 10.90 11.33 10.70
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 5623.4 3.20 10.92 11.36 10.73
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4400.6 3.21 10.94 11.38 10.77
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4371.7 3.21 10.95 11.39 10.78
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5653.5 3.21 10.94 11.38 10.77
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5673.1 3.21 10.94 11.38 10.77
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4940.6 3.17 10.81 11.24 10.58
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4385.0 3.17 10.81 11.24 10.58
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4680.9 3.18 10.84 11.27 10.62
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3660.8 3.21 10.95 11.39 10.78
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2870.3 3.22 10.97 11.41 10.81
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2877.9 3.22 10.98 11.42 10.82
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3849.4 3.18 10.85 11.28 10.63
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3862.8 3.18 10.85 11.28 10.63
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   4869.23 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   4839.39 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   7734.25 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   4825.90 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   3678.62 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   3678.32 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   3657.29 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   3794.38 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   9724.61 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   9781.53 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   9689.57 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   9746.46 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   6801.41 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   6800.57 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   6747.17 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   6746.34 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   6783.04 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   6814.92 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   6764.56 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   6796.43 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   5121.17 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   5120.70 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   5087.63 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   5087.16 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 176.35 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 162.05 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 539.95 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 118.68 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.08 87.80 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.07 86.49 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 116.10 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 120.11 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.45 518.68 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.41 473.33 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.41 475.74 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 365.67 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 282.14 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 279.85 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 362.41 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 364.01 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 339.02 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 300.73 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 316.36 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.20 234.36 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 181.36 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 181.38 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 259.31 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 260.41 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1535.44 1842.53 0.127 0.152 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
G NW APARTMENT 1410.95 1693.15 0.116 0.140 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 26.18 0.01308
OFFICE 4602.66 5523.20 0.388 0.465 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 23.20 0.01308
G NE APARTMENT 979.77 1175.72 0.081 0.097 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
G N1 APARTMENT 764.46 917.36 0.063 0.076 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.95 0.01308
G N2 APARTMENT 753.10 903.71 0.062 0.075 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.95 0.01308
G S1 APARTMENT 1010.82 1212.99 0.083 0.100 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 29.06 0.01308
G S2 APARTMENT 1045.73 1254.87 0.086 0.103 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 28.93 0.01308
M SW APARTMENT 4515.89 5419.07 0.372 0.447 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
M NW APARTMENT 4121.06 4945.27 0.340 0.408 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 26.18 0.01308
M SE APARTMENT 4141.78 4970.14 0.342 0.410 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 28.93 0.01308
M NE APARTMENT 3183.46 3820.15 0.263 0.315 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 25.88 0.01308
M N1 APARTMENT 2456.55 2947.86 0.203 0.243 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.95 0.01308
M N2 APARTMENT 2436.56 2923.87 0.201 0.241 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 24.95 0.01308
M S1 APARTMENT 3155.30 3786.36 0.260 0.312 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 29.06 0.01308
M S2 APARTMENT 3169.18 3803.02 0.261 0.314 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 29.06 0.01308
T SW APARTMENT 2951.29 3541.54 0.243 0.292 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 28.71 0.01308
T NW APARTMENT 2618.22 3141.87 0.216 0.259 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
T SE APARTMENT 2754.08 3304.90 0.227 0.273 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 29.06 0.01308
T NE APARTMENT 2040.25 2448.30 0.168 0.202 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 29.20 0.01308
T N1 APARTMENT 1578.92 1894.70 0.130 0.156 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 29.04 0.01308
T N2 APARTMENT 1579.10 1894.91 0.130 0.156 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 29.20 0.01308
T S1 APARTMENT 2257.59 2709.11 0.186 0.223 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 29.20 0.01308
T S2 APARTMENT 2267.12 2720.54 0.187 0.224 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 29.20 0.01308


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2802.71 3363.25 0.085 0.102 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G NW APARTMENT 2823.70 3388.44 0.086 0.103 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
OFFICE 4728.61 5674.34 0.139 0.167 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G NE APARTMENT 2812.30 3374.75 0.085 0.102 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G N1 APARTMENT 1842.08 2210.49 0.056 0.067 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G N2 APARTMENT 1841.82 2210.19 0.056 0.067 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G S1 APARTMENT 1824.04 2188.85 0.055 0.066 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
G S2 APARTMENT 1939.97 2327.96 0.059 0.071 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
M SW APARTMENT 5686.40 6823.68 0.172 0.207 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M NW APARTMENT 5734.53 6881.43 0.174 0.208 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M SE APARTMENT 5656.77 6788.12 0.171 0.206 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M NE APARTMENT 5704.88 6845.85 0.173 0.207 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M N1 APARTMENT 3214.26 3857.12 0.097 0.117 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M N2 APARTMENT 3213.56 3856.27 0.097 0.117 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M S1 APARTMENT 3168.40 3802.07 0.096 0.115 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
M S2 APARTMENT 3167.70 3801.23 0.096 0.115 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T SW APARTMENT 4467.53 5361.04 0.135 0.162 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T NW APARTMENT 4494.49 5393.39 0.136 0.163 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T SE APARTMENT 4451.90 5342.28 0.135 0.162 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T NE APARTMENT 4478.85 5374.62 0.136 0.163 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T N1 APARTMENT 3062.08 3674.50 0.093 0.111 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T N2 APARTMENT 3061.69 3674.02 0.093 0.111 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T S1 APARTMENT 3033.72 3640.46 0.092 0.110 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028
T S2 APARTMENT 3033.32 3639.99 0.092 0.110 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -28.60 0.00028


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.15 0.15 0.10 0.10
SPLIT GNW 0.14 0.14 0.10 0.10
SPLIT OFFICE 0.47 0.47 0.17 0.17
SPLIT GNE 0.10 0.10 0.10 0.10
SPLIT GN1 0.08 0.08 0.07 0.07
SPLIT GN2 0.07 0.07 0.07 0.07
SPLIT GS1 0.10 0.10 0.07 0.07
SPLIT GS2 0.10 0.10 0.07 0.07
SPLIT MSW 0.45 0.45 0.21 0.21
SPLIT MNW 0.41 0.41 0.21 0.21
SPLIT MSE 0.41 0.41 0.21 0.21
SPLIT MNE 0.32 0.32 0.21 0.21
SPLIT MN1 0.24 0.24 0.12 0.12
SPLIT MN2 0.24 0.24 0.12 0.12
SPLIT MS1 0.31 0.31 0.12 0.12
SPLIT MS2 0.31 0.31 0.12 0.12
SPLIT TSW 0.29 0.29 0.16 0.16
SPLIT TNW 0.26 0.26 0.16 0.16
SPLIT TSE 0.27 0.27 0.16 0.16
SPLIT TNE 0.20 0.20 0.16 0.16
SPLIT TN1 0.16 0.16 0.11 0.11
SPLIT TN2 0.16 0.16 0.11 0.11
SPLIT TS1 0.22 0.22 0.11 0.11
SPLIT TS2 0.22 0.22 0.11 0.11



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 3971.75 7016.75 2913.00
G NW APARTMENT 4270.50 7318.25 3466.75
OFFICE 796.25 1656.00 558.50
G NE APARTMENT 4210.50 7455.25 3493.75
G N1 APARTMENT 3709.50 7574.50 3156.75
G N2 APARTMENT 3706.50 7587.50 3162.50
G S1 APARTMENT 3322.00 7063.50 2425.25
G S2 APARTMENT 3548.75 6991.00 2585.75
M SW APARTMENT 3604.50 5595.00 1230.75
M NW APARTMENT 4260.25 5949.25 2111.00
M SE APARTMENT 3545.50 5630.50 1187.25
M NE APARTMENT 4194.25 5992.25 2092.00
M N1 APARTMENT 3320.75 5872.50 1275.25
M N2 APARTMENT 3313.75 5879.00 1273.75
M S1 APARTMENT 2668.75 5438.50 333.25
M S2 APARTMENT 2666.00 5440.50 333.25
T SW APARTMENT 4802.50 6161.50 2890.00
T NW APARTMENT 5160.75 6537.25 3485.50
T SE APARTMENT 4783.75 6191.75 2887.50
T NE APARTMENT 5128.75 6638.25 3520.00
T N1 APARTMENT 4758.50 6549.75 3126.75
T N2 APARTMENT 4757.25 6557.50 3130.00
T S1 APARTMENT 4346.25 6052.25 2398.25
T S2 APARTMENT 4343.75 6051.50 2399.50
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6166.50 7666.75 3971.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 4.25 0.00 4.25 0.00
G NW APARTMENT 2.50 0.00 2.50 0.00
OFFICE 21.25 2.25 0.25 0.00
G NE APARTMENT 3.25 0.00 3.25 0.00
G N1 APARTMENT 1.75 0.75 1.75 0.75
G N2 APARTMENT 2.75 1.00 2.75 1.00
G S1 APARTMENT 0.75 0.00 0.75 0.00
G S2 APARTMENT 3.25 0.00 3.25 0.00
M SW APARTMENT 2.00 0.00 2.00 0.00
M NW APARTMENT 2.00 0.00 2.00 0.00
M SE APARTMENT 1.75 0.00 1.75 0.00
M NE APARTMENT 3.00 0.00 3.00 0.00
M N1 APARTMENT 0.50 0.00 0.50 0.00
M N2 APARTMENT 1.00 0.00 1.00 0.00
M S1 APARTMENT 1.75 0.00 1.75 0.00
M S2 APARTMENT 1.00 0.00 1.00 0.00
T SW APARTMENT 1.75 0.00 1.75 0.00
T NW APARTMENT 2.00 0.00 2.00 0.00
T SE APARTMENT 1.75 0.00 1.75 0.00
T NE APARTMENT 2.75 0.00 2.75 0.00
T N1 APARTMENT 1.50 0.00 1.50 0.00
T N2 APARTMENT 1.75 0.00 1.75 0.00
T S1 APARTMENT 1.25 0.00 1.25 0.00
T S2 APARTMENT 2.00 0.00 2.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 59.00 3.25 38.00 1.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.365 0.215 0.000 0.064
G NW APARTMENT 1.71 2.50 268.97 0.353 0.215 0.000 0.062
OFFICE 0.94 1.00 268.97 0.518 0.246 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.352 0.215 0.000 0.061
G N1 APARTMENT 1.71 2.50 268.97 0.353 0.130 0.000 0.061
G N2 APARTMENT 1.71 2.50 268.97 0.353 0.130 0.000 0.061
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.130 0.000 0.064
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.130 0.000 0.064
M SW APARTMENT 1.71 2.50 268.97 0.353 0.309 0.000 0.079
M NW APARTMENT 1.71 2.50 268.97 0.353 0.309 0.000 0.076
M SE APARTMENT 1.71 2.50 268.97 0.353 0.309 0.000 0.079
M NE APARTMENT 1.71 2.50 268.97 0.353 0.309 0.000 0.076
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.186 0.000 0.076
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.186 0.000 0.076
M S1 APARTMENT 1.71 2.50 268.97 0.353 0.187 0.000 0.079
M S2 APARTMENT 1.71 2.50 268.97 0.353 0.187 0.000 0.079
T SW APARTMENT 1.71 2.50 268.97 0.353 0.409 0.000 0.092
T NW APARTMENT 1.71 2.50 268.97 0.353 0.409 0.000 0.088
T SE APARTMENT 1.71 2.50 268.97 0.353 0.409 0.000 0.092
T NE APARTMENT 1.71 2.50 268.97 0.353 0.408 0.000 0.088
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.246 0.000 0.088
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.246 0.000 0.088
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.247 0.000 0.092
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.247 0.000 0.092
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.353 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.499 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.363 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.341 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 463.66 0.00 01-JAN-00:15 33056.56 26-FEB-07:30
WaterSystems:Electricity 463.66 0.00 01-JAN-00:15 33056.56 26-FEB-07:30
Water Heater:WaterSystems:Electricity 463.66 0.00 01-JAN-00:15 33056.56 26-FEB-07:30
Fans:Electricity 208.21 6602.29 01-JAN-08:30 6602.29 03-JAN-08:30
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
ElectricityPurchased:Plant 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
Cogeneration:ElectricityPurchased 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
ElectricityNet:Plant 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
Cogeneration:ElectricityNet 1399.27 19714.91 01-JAN-03:15 85847.16 28-JUN-18:00
ExteriorLights:Electricity 40.05 0.00 01-JAN-08:15 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.05 0.00 01-JAN-08:15 2553.00 01-JAN-00:15
Electricity:HVAC 259.45 6602.29 01-JAN-08:30 31124.09 16-JUL-16:00
General:Fans:Electricity 208.21 6602.29 01-JAN-08:30 6602.29 03-JAN-08:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 51.24 0.00 01-JAN-00:15 24521.80 16-JUL-16:00


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 921.33 0.00 31-MAR-17:15 177327.73 19-DEC-03:00
Gas:HVAC 921.33 0.00 31-MAR-17:15 177327.73 19-DEC-03:00
Heating:Gas 921.33 0.00 31-MAR-17:15 177327.73 19-DEC-03:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1595.45 1568.25 09-OCT-16:15 246893.68 11-JAN-12:00
EnergyTransfer:Building 648.52 1301.13 11-MAY-07:00 106106.05 11-JAN-12:00
EnergyTransfer:Zone:G SW APARTMENT 18.75 0.08 16-OCT-19:45 3292.22 11-JAN-12:00
Heating:EnergyTransfer 425.28 0.00 10-MAR-13:45 106106.05 11-JAN-12:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 14.73 0.00 01-FEB-13:00 3292.22 11-JAN-12:00
Cooling:EnergyTransfer 223.24 0.00 02-JAN-07:15 57757.41 16-JUL-15:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 4.02 0.00 01-JAN-00:15 1618.16 16-JUL-16:15
EnergyTransfer:Zone:G NW APARTMENT 20.84 0.00 23-OCT-14:15 3372.12 11-JAN-12:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 18.00 0.00 10-MAR-13:45 3372.12 11-JAN-12:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 2.85 0.00 01-JAN-00:15 1561.15 25-JUN-18:00
EnergyTransfer:Zone:OFFICE 20.31 0.00 09-JUN-23:00 5128.99 08-JAN-07:30
Heating:EnergyTransfer:Zone:OFFICE 2.31 0.00 01-JAN-00:15 5128.99 08-JAN-07:30
Cooling:EnergyTransfer:Zone:OFFICE 18.00 0.00 02-JAN-07:15 4122.43 16-JUL-10:30
EnergyTransfer:Zone:G NE APARTMENT 20.75 0.11 15-JUN-14:00 3351.28 19-DEC-03:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 17.84 0.00 10-MAR-13:45 3351.28 19-DEC-03:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 2.91 0.00 01-JAN-00:15 1121.84 17-JUL-09:30
EnergyTransfer:Zone:G N1 APARTMENT 13.46 0.01 06-APR-12:30 2060.98 11-JAN-12:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 10.57 0.00 10-MAR-13:45 2060.98 11-JAN-12:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 2.89 0.00 01-JAN-00:15 834.49 25-JUN-18:00
EnergyTransfer:Zone:G N2 APARTMENT 13.45 0.07 07-APR-12:15 2059.99 11-JAN-12:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 10.57 0.00 10-MAR-13:45 2059.99 11-JAN-12:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 2.89 0.00 01-JAN-00:15 824.02 25-JUN-18:00
EnergyTransfer:Zone:G S1 APARTMENT 11.60 0.06 22-MAY-14:30 1982.88 11-JAN-12:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 7.60 0.00 02-JAN-12:00 1982.88 11-JAN-12:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 4.00 0.00 01-JAN-00:15 1101.30 11-AUG-12:45
EnergyTransfer:Zone:G S2 APARTMENT 12.61 0.10 11-MAY-10:45 2089.86 19-DEC-03:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 8.54 0.00 02-JAN-12:15 2089.86 19-DEC-03:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 4.07 0.00 01-JAN-00:15 1169.53 11-AUG-12:45
EnergyTransfer:Zone:M SW APARTMENT 42.49 0.10 16-MAY-09:45 7721.85 11-JAN-12:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 23.80 0.00 02-JAN-13:30 7721.85 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 18.68 0.00 01-JAN-00:15 4923.56 25-JUN-17:30
EnergyTransfer:Zone:M NW APARTMENT 45.52 0.03 01-APR-12:15 7750.27 11-JAN-12:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 32.10 0.00 09-FEB-15:00 7750.27 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 13.42 0.00 01-JAN-00:15 4804.66 25-JUN-18:00
EnergyTransfer:Zone:M SE APARTMENT 41.88 0.00 23-OCT-14:15 7642.12 11-JAN-12:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 23.57 0.00 02-JAN-13:30 7642.12 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 18.32 0.00 01-JAN-00:15 4434.72 17-JUL-12:00
EnergyTransfer:Zone:M NE APARTMENT 45.13 0.30 03-MAY-11:30 7603.23 11-JAN-12:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 31.86 0.00 09-FEB-17:00 7603.23 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 13.27 0.00 01-JAN-00:15 3677.11 25-JUN-18:00
EnergyTransfer:Zone:M N1 APARTMENT 27.77 0.28 11-MAY-10:30 4530.05 11-JAN-12:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 14.15 0.00 15-JAN-18:15 4530.05 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 13.63 0.00 01-JAN-00:15 2879.24 25-JUN-18:30
EnergyTransfer:Zone:M N2 APARTMENT 27.74 0.01 11-MAY-10:45 4527.05 11-JAN-12:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 14.15 0.00 15-JAN-18:15 4527.05 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 13.59 0.00 01-JAN-00:15 2861.02 25-JUN-18:30
EnergyTransfer:Zone:M S1 APARTMENT 28.85 0.07 15-OCT-09:30 4310.53 11-JAN-12:00
Heating:EnergyTransfer:Zone:M S1 APARTMENT 8.17 0.00 02-JAN-10:45 4310.53 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 20.68 0.00 01-JAN-00:15 3432.12 11-AUG-12:45
EnergyTransfer:Zone:M S2 APARTMENT 28.81 0.07 20-NOV-11:00 4308.35 11-JAN-12:00
Heating:EnergyTransfer:Zone:M S2 APARTMENT 8.16 0.00 02-JAN-10:45 4308.35 11-JAN-12:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 20.64 0.00 01-JAN-00:15 3445.50 11-AUG-12:45
EnergyTransfer:Zone:T SW APARTMENT 33.40 0.00 15-JUN-01:30 5846.19 11-JAN-12:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 25.96 0.00 01-FEB-12:45 5846.19 11-JAN-12:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 7.44 0.00 01-JAN-00:15 3225.61 25-JUN-16:15
EnergyTransfer:Zone:T NW APARTMENT 35.79 0.01 31-AUG-01:30 5859.09 11-JAN-12:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 30.42 0.00 09-FEB-16:15 5859.09 11-JAN-12:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 5.37 0.00 01-JAN-00:15 3086.84 25-JUN-18:00
EnergyTransfer:Zone:T SE APARTMENT 32.85 0.01 30-MAR-23:00 5803.90 11-JAN-12:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 25.73 0.00 01-FEB-12:30 5803.90 11-JAN-12:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 7.12 0.00 01-JAN-00:15 3025.20 17-JUL-12:00
EnergyTransfer:Zone:T NE APARTMENT 35.39 0.05 17-AUG-01:45 5775.44 11-JAN-12:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 30.18 0.00 10-MAR-11:00 5775.44 11-JAN-12:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 5.21 0.00 01-JAN-00:15 2412.43 25-JUN-16:30
EnergyTransfer:Zone:T N1 APARTMENT 23.76 0.10 11-OCT-13:00 3947.28 19-DEC-03:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 18.78 0.00 11-FEB-13:00 3947.28 19-DEC-03:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 4.98 0.00 01-JAN-00:15 1940.84 25-JUN-18:15
EnergyTransfer:Zone:T N2 APARTMENT 23.75 0.01 15-AUG-12:00 3946.95 19-DEC-03:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 18.79 0.00 11-FEB-13:00 3946.95 19-DEC-03:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 4.96 0.00 01-JAN-00:15 1932.91 25-JUN-18:00
EnergyTransfer:Zone:T S1 APARTMENT 21.81 0.01 08-MAY-22:30 3879.78 19-DEC-03:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 14.65 0.00 02-JAN-12:15 3879.78 19-DEC-03:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 7.16 0.00 01-JAN-00:15 2432.62 17-JUL-14:00
EnergyTransfer:Zone:T S2 APARTMENT 21.81 0.04 13-JUL-08:00 3879.83 19-DEC-03:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 14.65 0.00 02-JAN-12:15 3879.83 19-DEC-03:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 7.16 0.00 01-JAN-00:15 2441.57 17-JUL-13:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 946.93 0.00 16-APR-20:15 141862.19 19-DEC-03:00
HeatingCoils:EnergyTransfer 737.07 0.00 31-MAR-17:15 141862.19 19-DEC-03:00
CoolingCoils:EnergyTransfer 209.86 0.00 01-JAN-00:15 100471.93 16-JUL-16:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 14.731 -4.019 0.000 0.000 3.926 1.087 12.213 11.669 0.000 0.044 0.000 0.000 -9.885 0.000 -12.097 -17.667
G NW APARTMENT 17.996 -2.846 0.000 0.000 3.939 1.087 12.213 5.492 0.000 0.043 0.000 0.000 -10.735 0.000 -12.001 -15.189
OFFICE 2.312 -17.999 0.000 0.000 0.541 26.452 9.482 11.365 0.000 0.026 0.000 0.000 -9.237 0.000 -10.705 -12.237
G NE APARTMENT 17.844 -2.907 0.000 0.000 3.951 1.087 12.213 5.137 0.000 0.043 0.000 0.000 -10.514 0.000 -11.980 -14.873
G N1 APARTMENT 10.569 -2.888 0.000 0.000 3.946 1.087 12.213 1.779 0.000 0.031 0.000 0.000 -6.788 0.000 -7.500 -12.449
G N2 APARTMENT 10.566 -2.888 0.000 0.000 3.947 1.087 12.213 1.779 0.000 0.031 0.000 0.000 -6.787 0.000 -7.498 -12.450
G S1 APARTMENT 7.599 -4.003 0.000 0.000 3.924 1.087 12.213 8.052 0.000 0.030 0.000 0.000 -5.997 0.000 -7.610 -15.295
G S2 APARTMENT 8.535 -4.073 0.000 0.000 3.921 1.087 12.213 8.051 0.000 0.030 0.000 0.000 -5.989 0.000 -7.619 -16.157
M SW APARTMENT 23.804 -18.682 0.000 0.000 3.845 1.087 12.213 11.274 0.000 0.061 0.000 0.000 -10.481 0.000 -17.525 -5.595
M NW APARTMENT 32.105 -13.419 0.000 0.000 3.871 1.087 12.213 5.191 0.000 0.061 0.000 0.000 -11.310 0.000 -17.366 -12.431
M SE APARTMENT 23.569 -18.315 0.000 0.000 3.850 1.087 12.213 10.986 0.000 0.061 0.001 0.000 -10.328 0.000 -17.520 -5.601
M NE APARTMENT 31.859 -13.271 0.000 0.000 3.880 1.087 12.213 4.834 0.000 0.061 0.000 0.000 -11.074 0.000 -17.343 -12.244
M N1 APARTMENT 14.149 -13.625 0.000 0.000 3.867 1.087 12.213 1.598 0.000 0.042 0.000 0.000 -7.203 0.000 -10.870 -1.257
M N2 APARTMENT 14.148 -13.589 0.000 0.000 3.867 1.087 12.213 1.599 0.000 0.042 0.001 0.000 -7.201 0.000 -10.868 -1.296
M S1 APARTMENT 8.174 -20.678 0.000 0.000 3.829 1.087 12.213 7.801 0.000 0.042 4.939 0.000 -6.388 0.000 -11.019 -0.000
M S2 APARTMENT 8.165 -20.642 0.000 0.000 3.830 1.087 12.213 7.801 0.000 0.042 4.912 0.000 -6.387 0.000 -11.020 -0.000
T SW APARTMENT 25.958 -7.441 0.000 0.000 3.890 1.087 12.213 11.209 0.000 0.081 0.000 0.000 -10.102 0.000 -22.800 -14.094
T NW APARTMENT 30.422 -5.369 0.000 0.000 3.910 1.087 12.213 5.170 0.000 0.080 0.000 0.000 -10.947 0.000 -22.602 -13.964
T SE APARTMENT 25.728 -7.121 0.000 0.000 3.896 1.087 12.213 10.939 0.000 0.081 0.000 0.000 -9.964 0.000 -22.806 -14.052
T NE APARTMENT 30.183 -5.206 0.000 0.000 3.923 1.087 12.213 4.829 0.000 0.080 0.000 0.000 -10.718 0.000 -22.581 -13.809
T N1 APARTMENT 18.783 -4.979 0.000 0.000 3.911 1.087 12.213 1.615 0.000 0.056 0.000 0.000 -6.941 0.000 -14.043 -11.700
T N2 APARTMENT 18.787 -4.959 0.000 0.000 3.911 1.087 12.213 1.614 0.000 0.056 0.000 0.000 -6.939 0.000 -14.044 -11.726
T S1 APARTMENT 14.647 -7.160 0.000 0.000 3.878 1.087 12.213 7.773 0.000 0.056 0.000 0.000 -6.160 0.000 -14.241 -12.094
T S2 APARTMENT 14.650 -7.155 0.000 0.000 3.879 1.087 12.213 7.772 0.000 0.056 0.000 0.000 -6.158 0.000 -14.242 -12.101
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.049 0.000 0.002 0.000 0.000 -1.291 0.000 -3.772 -9.569
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.199 0.000 0.081 27.854 0.000 -3.331 0.000 -45.863 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.048 0.000 0.002 0.000 0.000 -1.385 0.000 -3.056 -10.191
Total Facility 425.282 -223.235 0.000 0.000 90.131 95.189 296.854 155.626 0.000 1.322 37.706 0.000 -210.240 0.000 -390.591 -278.043


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 16-JUL-16:05 0.00 -1621.89 0.00 0.00 84.77 64.86 588.62 1627.40 0.00 178.11 0.00 0.00 0.00 0.00 0.00 -921.87
G NW APARTMENT 25-JUN-18:00 0.00 -1560.82 0.00 0.00 141.83 87.56 588.62 1874.63 0.00 218.82 0.00 0.00 0.00 0.00 0.00 -1350.65
OFFICE 23-JUL-06:01 0.00 -7124.37 0.00 0.00 0.00 416.15 294.31 1101.14 0.00 0.00 5589.20 0.00 0.00 0.00 -276.44 0.00
G NE APARTMENT 17-JUL-09:30 0.00 -1121.48 0.00 0.00 40.75 12.97 406.15 1724.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -1062.62
G N1 APARTMENT 25-JUN-18:00 0.00 -834.30 0.00 0.00 141.82 87.56 588.62 528.24 0.00 131.98 0.00 0.00 0.00 0.00 0.00 -643.93
G N2 APARTMENT 25-JUN-18:00 0.00 -823.83 0.00 0.00 141.82 87.56 588.62 528.45 0.00 131.98 0.00 0.00 0.00 0.00 0.00 -654.60
G S1 APARTMENT 11-AUG-12:45 0.00 -1101.20 0.00 0.00 40.75 12.97 388.49 1788.20 0.00 70.49 0.00 0.00 0.00 0.00 0.00 -1199.70
G S2 APARTMENT 11-AUG-12:45 0.00 -1169.43 0.00 0.00 40.75 12.97 388.49 1787.22 0.00 70.49 0.00 0.00 0.00 0.00 0.00 -1130.50
M SW APARTMENT 25-JUN-17:23 0.00 -4923.39 0.00 0.00 141.82 87.56 588.62 1703.62 0.00 309.72 2092.05 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 25-JUN-18:00 0.00 -4803.86 0.00 0.00 141.83 87.56 588.62 1851.99 0.00 313.48 1820.38 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 17-JUL-12:00 0.00 -4436.34 0.00 0.00 40.75 12.97 406.15 1720.53 0.00 195.54 2060.40 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 25-JUN-18:00 0.00 -3676.56 0.00 0.00 141.83 87.56 588.62 653.29 0.00 313.47 1891.79 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 25-JUN-18:30 0.00 -2878.71 0.00 0.00 141.56 103.77 547.42 612.38 0.00 129.38 1344.20 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 25-JUN-18:30 0.00 -2860.49 0.00 0.00 141.53 103.77 547.42 612.49 0.00 129.37 1325.91 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 11-AUG-12:45 0.00 -3431.88 0.00 0.00 40.75 12.97 388.49 1776.78 0.00 90.95 1121.94 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 11-AUG-12:45 0.00 -3445.26 0.00 0.00 40.75 12.97 388.49 1776.71 0.00 90.95 1135.39 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 25-JUN-16:06 0.00 -3230.61 0.00 0.00 84.78 64.86 588.62 1745.15 0.00 463.53 283.67 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 25-JUN-18:00 0.00 -3086.43 0.00 0.00 141.84 87.56 588.62 1822.53 0.00 412.04 33.85 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 17-JUL-12:00 0.00 -3026.38 0.00 0.00 40.75 12.97 406.15 1687.38 0.00 257.24 621.89 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 25-JUN-16:15 0.00 -2415.94 0.00 0.00 84.55 64.86 588.62 653.16 0.00 459.98 564.77 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 25-JUN-18:15 0.00 -1940.54 0.00 0.00 141.33 103.77 547.42 553.28 0.00 207.07 387.67 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 25-JUN-18:00 0.00 -1932.65 0.00 0.00 141.65 87.56 588.62 505.73 0.00 248.01 361.09 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 17-JUL-13:45 0.00 -2432.12 0.00 0.00 40.75 12.97 382.60 1184.42 0.00 103.28 708.09 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 17-JUL-13:45 0.00 -2441.11 0.00 0.00 40.75 12.97 382.60 1184.30 0.00 103.28 717.21 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 16-JUL-15:15 0.00 -57763.14 0.00 0.00 1192.08 4512.09 11708.34 23043.79 0.00 5503.98 11802.86 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-JAN-12:00 3292.08 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -652.03 0.00 -2345.43 -767.05
G NW APARTMENT 11-JAN-12:00 3371.98 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -757.22 0.00 -2345.43 -741.77
OFFICE 18-APR-06:01 7152.67 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -492.96 0.00 -574.82 -6795.34
G NE APARTMENT 19-DEC-03:00 3351.26 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -1116.08 0.00 -2083.75 -577.14
G N1 APARTMENT 11-JAN-12:00 2060.86 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -459.85 0.00 -1414.70 -658.73
G N2 APARTMENT 11-JAN-12:00 2059.87 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -459.87 0.00 -1414.70 -657.72
G S1 APARTMENT 11-JAN-12:00 1982.76 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -354.74 0.00 -1414.70 -685.74
G S2 APARTMENT 19-DEC-03:00 2089.85 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -663.72 0.00 -1256.87 -594.99
M SW APARTMENT 11-JAN-12:00 7721.59 0.00 0.00 0.00 47.48 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -684.53 0.00 -3365.28 -4144.27
M NW APARTMENT 11-JAN-12:00 7750.03 0.00 0.00 0.00 47.69 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -786.89 0.00 -3355.30 -4080.53
M SE APARTMENT 11-JAN-12:00 7641.88 0.00 0.00 0.00 47.48 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -658.95 0.00 -3365.10 -4090.32
M NE APARTMENT 11-JAN-12:00 7603.03 0.00 0.00 0.00 47.80 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -760.77 0.00 -3351.13 -3963.93
M N1 APARTMENT 11-JAN-12:00 4529.83 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -480.95 0.00 -2033.82 -2487.48
M N2 APARTMENT 11-JAN-12:00 4526.84 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -480.97 0.00 -2033.80 -2484.50
M S1 APARTMENT 11-JAN-12:00 4310.31 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -375.55 0.00 -2034.00 -2373.19
M S2 APARTMENT 11-JAN-12:00 4308.13 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -375.57 0.00 -2034.00 -2370.99
T SW APARTMENT 11-JAN-12:00 5846.05 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -674.51 0.00 -4464.03 -1179.93
T NW APARTMENT 11-JAN-12:00 5858.95 0.00 0.00 0.00 47.46 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -777.01 0.00 -4455.63 -1098.78
T SE APARTMENT 11-JAN-12:00 5803.76 0.00 0.00 0.00 47.42 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -648.02 0.00 -4464.39 -1163.78
T NE APARTMENT 11-JAN-12:00 5775.34 0.00 0.00 0.00 47.51 12.97 412.04 0.00 0.00 0.00 0.00 0.00 -750.30 0.00 -4450.93 -1046.63
T N1 APARTMENT 19-DEC-03:00 3947.26 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -691.92 0.00 -2390.82 -1290.24
T N2 APARTMENT 19-DEC-03:00 3946.93 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -691.92 0.00 -2390.78 -1289.95
T S1 APARTMENT 19-DEC-03:00 3879.76 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -666.22 0.00 -2392.32 -1246.94
T S2 APARTMENT 19-DEC-03:00 3879.81 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -666.22 0.00 -2392.32 -1246.99
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JAN-12:00 106102.19 0.00 0.00 0.00 1169.51 3766.23 10193.95 0.00 0.00 0.00 0.00 0.00 -13949.83 0.00 -70266.35 -37015.71



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Sec1.1A-General Information

Data
Weather File Duluth International Arpt MN USA TMY3 WMO#=727450
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 38.00
Number of hours cooling loads not met 1.00
Number of hours not met 39.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.05 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 921.33 177327.73 0.00 0.00
Space Cooling 51.24 17033.20 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 208.21 6602.29 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 463.66 30600.80 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1399.27   921.33   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1399.27
Natural Gas 0.00 921.33
Additional 0.00 0.00
Total 517.65 2320.61


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 16.35
Fans-Interior 66.42
Service Water Heating 147.92
Receptacle Equipment 165.14
Miscellaneous 12.78
Subtotal 446.39


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 293.92
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 293.92


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.10
Space Heating 39.70
Space Cooling 2.21
Fans-Interior 8.97
Service Water Heating 19.98
Receptacle Equipment 22.31
Miscellaneous 1.73



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.151917
G NW APARTMENT DIRECT AIR 0.139601
OFFICE DIRECT AIR 0.465142
G NE APARTMENT DIRECT AIR 0.102240
G N1 APARTMENT DIRECT AIR 0.075635
G N2 APARTMENT DIRECT AIR 0.074510
G S1 APARTMENT DIRECT AIR 0.100014
G S2 APARTMENT DIRECT AIR 0.103467
M SW APARTMENT DIRECT AIR 0.446812
M NW APARTMENT DIRECT AIR 0.407749
M SE APARTMENT DIRECT AIR 0.409824
M NE APARTMENT DIRECT AIR 0.315004
M N1 APARTMENT DIRECT AIR 0.243049
M N2 APARTMENT DIRECT AIR 0.241072
M S1 APARTMENT DIRECT AIR 0.312197
M S2 APARTMENT DIRECT AIR 0.313571
T SW APARTMENT DIRECT AIR 0.292044
T NW APARTMENT DIRECT AIR 0.259062
T SE APARTMENT DIRECT AIR 0.272529
T NE APARTMENT DIRECT AIR 0.201892
T N1 APARTMENT DIRECT AIR 0.156230
T N2 APARTMENT DIRECT AIR 0.156247
T S1 APARTMENT DIRECT AIR 0.223382
T S2 APARTMENT DIRECT AIR 0.224325


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.151917
SPLIT GNW MAIN BRANCH 0.139601
SPLIT OFFICE MAIN BRANCH 0.465142
SPLIT GNE MAIN BRANCH 0.102240
SPLIT GN1 MAIN BRANCH 0.075635
SPLIT GN2 MAIN BRANCH 0.074510
SPLIT GS1 MAIN BRANCH 0.100014
SPLIT GS2 MAIN BRANCH 0.103467
SPLIT MSW MAIN BRANCH 0.446812
SPLIT MNW MAIN BRANCH 0.407749
SPLIT MSE MAIN BRANCH 0.409824
SPLIT MNE MAIN BRANCH 0.315004
SPLIT MN1 MAIN BRANCH 0.243049
SPLIT MN2 MAIN BRANCH 0.241072
SPLIT MS1 MAIN BRANCH 0.312197
SPLIT MS2 MAIN BRANCH 0.313571
SPLIT TSW MAIN BRANCH 0.292044
SPLIT TNW MAIN BRANCH 0.259062
SPLIT TSE MAIN BRANCH 0.272529
SPLIT TNE MAIN BRANCH 0.201892
SPLIT TN1 MAIN BRANCH 0.156230
SPLIT TN2 MAIN BRANCH 0.156247
SPLIT TS1 MAIN BRANCH 0.223382
SPLIT TS2 MAIN BRANCH 0.224325


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.151917
SPLIT GNW 0.139601
SPLIT OFFICE 0.465142
SPLIT GNE 0.102240
SPLIT GN1 0.075635
SPLIT GN2 0.074510
SPLIT GS1 0.100014
SPLIT GS2 0.103467
SPLIT MSW 0.446812
SPLIT MNW 0.407749
SPLIT MSE 0.409824
SPLIT MNE 0.315004
SPLIT MN1 0.243049
SPLIT MN2 0.241072
SPLIT MS1 0.312197
SPLIT MS2 0.313571
SPLIT TSW 0.292044
SPLIT TNW 0.259062
SPLIT TSE 0.272529
SPLIT TNE 0.201892
SPLIT TN1 0.156230
SPLIT TN2 0.156247
SPLIT TS1 0.223382
SPLIT TS2 0.224325


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.151917 0.026898
SPLIT GNW OA CONTROLLER 0.139601 0.025953
SPLIT OFFICE OA CONTROLLER 0.465142 0.038104
SPLIT GNE OA CONTROLLER 0.102240 0.025953
SPLIT GN1 OA CONTROLLER 0.075635 0.025953
SPLIT GN2 OA CONTROLLER 0.074510 0.025953
SPLIT GS1 OA CONTROLLER 0.100014 0.025953
SPLIT GS2 OA CONTROLLER 0.103467 0.025953
SPLIT MSW OA CONTROLLER 0.446812 0.051906
SPLIT MNW OA CONTROLLER 0.407749 0.051906
SPLIT MSE OA CONTROLLER 0.409824 0.051906
SPLIT MNE OA CONTROLLER 0.315004 0.051906
SPLIT MN1 OA CONTROLLER 0.243049 0.051906
SPLIT MN2 OA CONTROLLER 0.241072 0.051906
SPLIT MS1 OA CONTROLLER 0.312197 0.051906
SPLIT MS2 OA CONTROLLER 0.313571 0.051906
SPLIT TSW OA CONTROLLER 0.292044 0.025953
SPLIT TNW OA CONTROLLER 0.259062 0.025953
SPLIT TSE OA CONTROLLER 0.272529 0.025953
SPLIT TNE OA CONTROLLER 0.201892 0.025953
SPLIT TN1 OA CONTROLLER 0.156230 0.025953
SPLIT TN2 OA CONTROLLER 0.156247 0.025953
SPLIT TS1 OA CONTROLLER 0.223382 0.025953
SPLIT TS2 OA CONTROLLER 0.224325 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.151917 2836.41 0.756964
SPLIT GNW COOLING COIL 0.139601 2623.54 0.754843
SPLIT OFFICE COOLING COIL 0.465142 7699.75 0.798655
SPLIT GNE COOLING COIL 0.102240 2057.81 0.733377
SPLIT GN1 COOLING COIL 0.075635 1556.86 0.726668
SPLIT GN2 COOLING COIL 0.074510 1538.85 0.725680
SPLIT GS1 COOLING COIL 0.100014 2050.66 0.727823
SPLIT GS2 COOLING COIL 0.103467 2099.60 0.730915
SPLIT MSW COOLING COIL 0.446812 7946.89 0.773184
SPLIT MNW COOLING COIL 0.407749 7324.81 0.769789
SPLIT MSE COOLING COIL 0.409824 7560.72 0.760888
SPLIT MNE COOLING COIL 0.315004 5870.72 0.757555
SPLIT MN1 COOLING COIL 0.243049 4591.43 0.753165
SPLIT MN2 COOLING COIL 0.241072 4561.02 0.752674
SPLIT MS1 COOLING COIL 0.312197 5898.60 0.753116
SPLIT MS2 COOLING COIL 0.313571 5919.29 0.753402
SPLIT TSW COOLING COIL 0.292044 5169.68 0.774808
SPLIT TNW COOLING COIL 0.259062 4588.20 0.774631
SPLIT TSE COOLING COIL 0.272529 4894.68 0.769860
SPLIT TNE COOLING COIL 0.201892 3819.29 0.752713
SPLIT TN1 COOLING COIL 0.156230 2993.03 0.748676
SPLIT TN2 COOLING COIL 0.156247 3000.58 0.747913
SPLIT TS1 COOLING COIL 0.223382 4024.69 0.768791
SPLIT TS2 COOLING COIL 0.224325 4038.78 0.769033


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.151917 0.151917 0.151917 0.151917 4869.23 2836.41 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.139601 0.139601 0.139601 0.139601 4839.39 2623.54 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.465142 0.465142 0.465142 0.465142 7734.25 7699.75 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.102240 0.102240 0.102240 0.102240 4825.90 2057.81 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.075635 0.075635 0.075635 0.075635 3678.62 1556.86 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.074510 0.074510 0.074510 0.074510 3678.32 1538.85 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.100014 0.100014 0.100014 0.100014 3657.29 2050.66 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.103467 0.103467 0.103467 0.103467 3794.38 2099.60 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.446812 0.446812 0.446812 0.446812 9724.61 7946.89 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.407749 0.407749 0.407749 0.407749 9781.53 7324.81 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.409824 0.409824 0.409824 0.409824 9689.57 7560.72 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.315004 0.315004 0.315004 0.315004 9746.46 5870.72 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.243049 0.243049 0.243049 0.243049 6801.41 4591.43 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.241072 0.241072 0.241072 0.241072 6800.57 4561.02 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.312197 0.312197 0.312197 0.312197 6747.17 5898.60 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.313571 0.313571 0.313571 0.313571 6746.34 5919.29 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.292044 0.292044 0.292044 0.292044 6783.04 5169.68 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.259062 0.259062 0.259062 0.259062 6814.92 4588.20 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.272529 0.272529 0.272529 0.272529 6764.56 4894.68 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.201892 0.201892 0.201892 0.201892 6796.43 3819.29 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.156230 0.156230 0.156230 0.156230 5121.17 2993.03 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.156247 0.156247 0.156247 0.156247 5120.70 3000.58 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.223382 0.223382 0.223382 0.223382 5087.63 4024.69 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.224325 0.224325 0.224325 0.224325 5087.16 4038.78 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.151917
SPLIT GNW SUPPLY FAN 0.139601
SPLIT OFFICE SUPPLY FAN 0.465142
SPLIT GNE SUPPLY FAN 0.102240
SPLIT GN1 SUPPLY FAN 0.075635
SPLIT GN2 SUPPLY FAN 0.074510
SPLIT GS1 SUPPLY FAN 0.100014
SPLIT GS2 SUPPLY FAN 0.103467
SPLIT MSW SUPPLY FAN 0.446812
SPLIT MNW SUPPLY FAN 0.407749
SPLIT MSE SUPPLY FAN 0.409824
SPLIT MNE SUPPLY FAN 0.315004
SPLIT MN1 SUPPLY FAN 0.243049
SPLIT MN2 SUPPLY FAN 0.241072
SPLIT MS1 SUPPLY FAN 0.312197
SPLIT MS2 SUPPLY FAN 0.313571
SPLIT TSW SUPPLY FAN 0.292044
SPLIT TNW SUPPLY FAN 0.259062
SPLIT TSE SUPPLY FAN 0.272529
SPLIT TNE SUPPLY FAN 0.201892
SPLIT TN1 SUPPLY FAN 0.156230
SPLIT TN2 SUPPLY FAN 0.156247
SPLIT TS1 SUPPLY FAN 0.223382
SPLIT TS2 SUPPLY FAN 0.224325


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 4869.23
SPLIT GNW HEATING COIL 4839.39
SPLIT OFFICE HEATING COIL 7734.25
SPLIT GNE HEATING COIL 4825.90
SPLIT GN1 HEATING COIL 3678.62
SPLIT GN2 HEATING COIL 3678.32
SPLIT GS1 HEATING COIL 3657.29
SPLIT GS2 HEATING COIL 3794.38
SPLIT MSW HEATING COIL 9724.61
SPLIT MNW HEATING COIL 9781.53
SPLIT MSE HEATING COIL 9689.57
SPLIT MNE HEATING COIL 9746.46
SPLIT MN1 HEATING COIL 6801.41
SPLIT MN2 HEATING COIL 6800.57
SPLIT MS1 HEATING COIL 6747.17
SPLIT MS2 HEATING COIL 6746.34
SPLIT TSW HEATING COIL 6783.04
SPLIT TNW HEATING COIL 6814.92
SPLIT TSE HEATING COIL 6764.56
SPLIT TNE HEATING COIL 6796.43
SPLIT TN1 HEATING COIL 5121.17
SPLIT TN2 HEATING COIL 5120.70
SPLIT TS1 HEATING COIL 5087.63
SPLIT TS2 HEATING COIL 5087.16



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:40

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.74 -2.6
April 21.88 4.03
May 22.61 12.37
June 23.69 16.19
July 24.07 17.83
August 24.14 17.50
September 23.43 12.89
October 21.93 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.53 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.14 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.71 -2.6
April 21.75 4.03
May 22.43 12.37
June 23.63 16.19
July 24.04 17.83
August 24.06 17.50
September 23.12 12.89
October 21.78 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.45 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.06 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.82 -13.0
February 18.52 -8.2
March 19.82 -2.6
April 21.69 4.03
May 23.43 12.37
June 24.97 16.19
July 25.53 17.83
August 25.52 17.50
September 24.56 12.89
October 21.93 6.03
November 19.35 -4.5
December 17.91 -11.1
     
Annual Sum or Average 21.77 4.02
Minimum of Months 17.82 -13.0
Maximum of Months 25.53 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.70 -2.6
April 21.72 4.03
May 22.33 12.37
June 23.59 16.19
July 23.98 17.83
August 23.98 17.50
September 23.02 12.89
October 21.76 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.41 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 23.98 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.70 -2.6
April 21.71 4.03
May 22.21 12.37
June 23.56 16.19
July 24.01 17.83
August 24.01 17.50
September 23.13 12.89
October 21.76 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.41 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.01 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.70 -2.6
April 21.71 4.03
May 22.20 12.37
June 23.56 16.19
July 24.01 17.83
August 24.00 17.50
September 23.12 12.89
October 21.76 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.41 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.01 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.73 -2.6
April 21.83 4.03
May 22.46 12.37
June 23.70 16.19
July 24.10 17.83
August 24.17 17.50
September 23.60 12.89
October 21.96 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.53 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.17 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.73 -2.6
April 21.83 4.03
May 22.49 12.37
June 23.73 16.19
July 24.13 17.83
August 24.20 17.50
September 23.63 12.89
October 21.96 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.55 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.20 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.74 -8.2
March 21.85 -2.6
April 22.45 4.03
May 23.98 12.37
June 24.29 16.19
July 24.37 17.83
August 24.39 17.50
September 24.05 12.89
October 22.42 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.89 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.39 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.73 -2.6
April 21.97 4.03
May 23.68 12.37
June 24.26 16.19
July 24.36 17.83
August 24.37 17.50
September 23.80 12.89
October 22.01 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.76 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.37 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.73 -8.2
March 21.83 -2.6
April 22.44 4.03
May 23.95 12.37
June 24.29 16.19
July 24.36 17.83
August 24.38 17.50
September 24.02 12.89
October 22.40 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.88 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.38 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.72 -2.6
April 21.91 4.03
May 23.58 12.37
June 24.25 16.19
July 24.33 17.83
August 24.35 17.50
September 23.71 12.89
October 21.97 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.73 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.35 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.72 -2.6
April 21.90 4.03
May 23.66 12.37
June 24.31 16.19
July 24.38 17.83
August 24.38 17.50
September 23.96 12.89
October 22.08 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.77 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.38 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.72 -2.6
April 21.90 4.03
May 23.65 12.37
June 24.31 16.19
July 24.38 17.83
August 24.38 17.50
September 23.95 12.89
October 22.07 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.77 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.38 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.77 -8.2
March 21.88 -2.6
April 22.60 4.03
May 24.10 12.37
June 24.34 16.19
July 24.39 17.83
August 24.39 17.50
September 24.22 12.89
October 22.70 6.03
November 21.72 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.97 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.39 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.77 -8.2
March 21.88 -2.6
April 22.61 4.03
May 24.10 12.37
June 24.34 16.19
July 24.39 17.83
August 24.39 17.50
September 24.22 12.89
October 22.70 6.03
November 21.72 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.97 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.39 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.74 -8.2
March 21.86 -2.6
April 22.33 4.03
May 23.49 12.37
June 23.92 16.19
July 24.13 17.83
August 24.24 17.50
September 23.36 12.89
October 22.18 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.70 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.24 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.75 -2.6
April 22.01 4.03
May 23.32 12.37
June 23.87 16.19
July 24.10 17.83
August 24.16 17.50
September 23.05 12.89
October 21.90 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.59 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.16 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.73 -8.2
March 21.85 -2.6
April 22.32 4.03
May 23.48 12.37
June 23.93 16.19
July 24.11 17.83
August 24.22 17.50
September 23.34 12.89
October 22.17 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.70 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.22 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.73 -2.6
April 21.94 4.03
May 23.24 12.37
June 23.84 16.19
July 24.03 17.83
August 24.10 17.50
September 22.98 12.89
October 21.86 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.55 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.10 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.74 -2.6
April 21.93 4.03
May 23.29 12.37
June 23.91 16.19
July 24.12 17.83
August 24.19 17.50
September 23.07 12.89
October 21.88 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.58 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.19 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.70 -8.2
March 21.73 -2.6
April 21.92 4.03
May 23.29 12.37
June 23.91 16.19
July 24.11 17.83
August 24.18 17.50
September 23.07 12.89
October 21.88 6.03
November 21.70 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.58 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.18 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.75 -8.2
March 21.88 -2.6
April 22.37 4.03
May 23.58 12.37
June 24.02 16.19
July 24.20 17.83
August 24.30 17.50
September 23.53 12.89
October 22.29 6.03
November 21.71 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.76 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.30 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -13.0
February 21.75 -8.2
March 21.88 -2.6
April 22.37 4.03
May 23.58 12.37
June 24.02 16.19
July 24.20 17.83
August 24.30 17.50
September 23.53 12.89
October 22.29 6.03
November 21.71 -4.5
December 21.70 -11.1
     
Annual Sum or Average 22.76 4.02
Minimum of Months 21.70 -13.0
Maximum of Months 24.30 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.81 -13.0
February 20.49 -8.2
March 21.26 -2.6
April 22.64 4.03
May 24.82 12.37
June 25.69 16.19
July 26.02 17.83
August 26.02 17.50
September 24.54 12.89
October 22.33 6.03
November 20.74 -4.5
December 19.92 -11.1
     
Annual Sum or Average 22.87 4.02
Minimum of Months 19.81 -13.0
Maximum of Months 26.02 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.86 -13.0
February 16.91 -8.2
March 18.08 -2.6
April 19.70 4.03
May 21.88 12.37
June 24.02 16.19
July 24.81 17.83
August 24.70 17.50
September 23.32 12.89
October 20.24 6.03
November 17.74 -4.5
December 16.23 -11.1
     
Annual Sum or Average 20.31 4.02
Minimum of Months 15.86 -13.0
Maximum of Months 24.81 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.00 -13.0
February 22.47 -8.2
March 22.88 -2.6
April 23.85 4.03
May 25.80 12.37
June 26.43 16.19
July 26.58 17.83
August 26.54 17.50
September 25.92 12.89
October 23.81 6.03
November 22.54 -4.5
December 22.05 -11.1
     
Annual Sum or Average 24.25 4.02
Minimum of Months 22.00 -13.0
Maximum of Months 26.58 17.83



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:40

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.118209E+12 73320.591 31-JAN-18:45 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32554.426 0.000 0.000 0.000
February 0.107138E+12 73332.079 07-FEB-18:45 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32565.913 0.000 0.000 0.000
March 0.118149E+12 71181.751 05-MAR-18:00 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30415.585 0.000 0.000 0.000
April 0.113163E+12 70533.799 09-APR-17:00 4979.953 26630.920 6602.291 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 32320.634 0.000 0.000 0.000
May 0.119939E+12 77218.044 18-MAY-17:30 4979.953 26630.920 6602.291 0.000 12536.229 0.000 0.000 0.000 0.000 0.000 0.000 26468.649 0.000 0.000 0.000
June 0.120773E+12 85847.164 28-JUN-17:00 4979.953 26630.920 6602.291 0.000 17033.201 0.000 0.000 0.000 0.000 0.000 0.000 30600.798 0.000 0.000 0.000
July 0.126006E+12 84777.612 16-JUL-17:45 4979.953 26630.920 6602.291 0.000 21929.750 0.000 0.000 0.000 0.000 0.000 0.000 24634.697 0.000 0.000 0.000
August 0.123113E+12 77140.190 25-AUG-17:45 4979.953 26630.920 6602.291 0.000 13514.885 0.000 0.000 0.000 0.000 0.000 0.000 25412.139 0.000 0.000 0.000
September 0.111804E+12 73233.951 17-SEP-17:15 4979.953 26630.920 6602.291 0.000 11521.377 0.000 0.000 0.000 0.000 0.000 0.000 23499.409 0.000 0.000 0.000
October 0.113229E+12 68287.453 24-OCT-17:15 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 27521.288 0.000 0.000 0.000
November 0.111023E+12 73011.081 30-NOV-18:45 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32244.916 0.000 0.000 0.000
December 0.116726E+12 73200.118 23-DEC-18:00 4979.953 26630.920 6602.291 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32433.953 0.000 0.000 0.000
                                     
Annual Sum or Average 0.139927E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.107138E+12 68287.453   4979.953 26630.920 6602.291 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 23499.409 0.000 0.000 0.000
Maximum of Months 0.126006E+12 85847.164   4979.953 26630.920 6602.291 0.000 21929.750 2553.000 0.000 0.000 0.000 0.000 0.000 32565.913 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:40

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.225122E+12 175984.542 11-JAN-11:00 175984.542 0.000 0.000 0.000 0.000 0.000 175984.542
February 0.150097E+12 138890.337 05-FEB-05:00 138890.337 0.000 0.000 0.000 0.000 0.000 138890.337
March 0.114995E+12 111928.737 23-MAR-04:00 111928.737 0.000 0.000 0.000 0.000 0.000 111928.737
April 0.392948E+11 49655.696 10-APR-02:00 49655.696 0.000 0.000 0.000 0.000 0.000 49655.696
May 0.616818E+10 24604.551 01-MAY-03:00 24604.551 0.000 0.000 0.000 0.000 0.000 24604.551
June 0.505827E+09 9135.960 02-JUN-00:00 9135.960 0.000 0.000 0.000 0.000 0.000 9135.960
July 0.100413E+09 3453.565 02-JUL-03:45 3453.565 0.000 0.000 0.000 0.000 0.000 3453.565
August 0.116662E+08 1149.865 18-AUG-04:00 1149.865 0.000 0.000 0.000 0.000 0.000 1149.865
September 0.184266E+10 13288.189 29-SEP-02:00 13288.189 0.000 0.000 0.000 0.000 0.000 13288.189
October 0.428795E+11 68972.530 26-OCT-00:00 68972.530 0.000 0.000 0.000 0.000 0.000 68972.530
November 0.130752E+12 133382.610 28-NOV-07:15 133382.610 0.000 0.000 0.000 0.000 0.000 133382.610
December 0.209565E+12 177327.734 19-DEC-02:00 177327.734 0.000 0.000 0.000 0.000 0.000 177327.734
                     
Annual Sum or Average 0.921333E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.116662E+08 1149.865   1149.865 0.000 0.000 0.000 0.000 0.000 1149.865
Maximum of Months 0.225122E+12 177327.734   177327.734 0.000 0.000 0.000 0.000 0.000 177327.734