Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Helena Regional Airport MT USA TMY3 WMO#=727720

Simulation Timestamp: 2015-09-09 18:47:55


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1859.47 593.20 658.46
Net Site Energy 1859.47 593.20 658.46
Total Source Energy 5017.04 1600.53 1776.59
Net Source Energy 5017.04 1600.53 1776.59


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 418.58 0.00 0.00 0.00 0.00
Cooling 73.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 256.97 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 434.73 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1440.89 418.58 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 418.58 0.00 0.00 0.00 0.00
Cooling General 73.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 256.97 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 434.73 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.13 0.00 0.00 0.00 0.00 0.00
HVAC 270.80 148.22 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 510.23 148.22 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.57 0.00 0.00 0.00 0.00 0.00
HVAC 243.96 133.53 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 459.67 133.53 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1440.89 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1440.89 100.00
     
Total On-Site and Utility Electric Sources 1440.89 100.00
Total Electricity End Uses 1440.89 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 40.75
Time Setpoint Not Met During Occupied Cooling 0.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 3032.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Helena Regional Airport MT USA TMY3 WMO#=727720
Weather File Helena Regional Airport MT USA TMY3 WMO#=727720
Latitude [deg] 46.60
Longitude [deg] -112.0
Elevation [m] 1167.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 19-JUL-17:15 25-DEC-08:00 - - - 01-JAN-07:15
Heating 0.00 104817.13 0.00 0.00 0.00 0.00
Cooling 18090.85 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8148.48 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24991.60 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 82841.81 104817.13 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 104817.13 0.00 0.00 0.00 0.00
Cooling General 18090.85 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 8148.48 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 24991.60 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 453.74 0.00 0.00 0.00
Cooling 231.28 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.83 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 813.83 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1376.80 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4563.30 453.74 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 160.67 0.00 0.00 0.00
Cooling 81.90 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.91 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 288.18 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 487.54 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1615.91 160.67 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 160.67 0.00 0.00 0.00
Cooling 81.90 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.91 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 288.18 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 487.54 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1615.91 160.67 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB -26.30 0.00 -26.30 Wetbulb [C] 1.60 300.00
HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 33.70 16.10 16.40 Wetbulb [C] 4.90 290.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.324 0.340 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.324 0.340 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.324 0.340 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.324 0.340 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.324 0.340 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.324 0.340 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.324 0.340 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.324 0.340 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.324 0.340 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.324 0.340 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.324 0.340 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.324 0.340 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.324 0.340 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.324 0.340 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.324 0.340 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.324 0.340 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.324 0.340 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.324 0.340 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.324 0.340 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.324 0.340 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.324 0.340 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.324 0.340 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.324 0.340 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.324 0.340 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.324 0.340 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.324 0.340 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.324 0.340 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.324 0.340 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.56 83.56 40.05
Exterior Lighting Total 2553.00           40.05



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3223.35 2574.34 649.00 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   2919.64 2331.79 587.85 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8470.75 6765.21 1705.54 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2040.74 1629.85 410.89 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1571.78 1255.31 316.47 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1549.85 1237.80 312.05 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2123.47 1695.92 427.55 0.80 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2182.55 1743.11 439.45 0.80 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9060.84 7236.49 1824.35 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8139.50 6500.66 1638.85 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8358.03 6675.18 1682.84 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6298.75 5030.53 1268.22 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4729.52 3777.25 952.26 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4692.38 3747.60 944.79 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6277.49 5013.55 1263.94 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6301.33 5032.59 1268.74 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6197.92 4950.00 1247.92 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5450.59 4353.14 1097.45 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5817.90 4646.50 1171.40 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4427.21 3535.82 891.40 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3425.15 2735.52 689.64 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3425.20 2735.56 689.65 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4748.65 3792.53 956.12 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4764.57 3805.25 959.32 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3070.7 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2781.4 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8069.7 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1944.1 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1497.4 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1476.5 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2022.9 3.13 10.67 11.09 10.38
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2079.2 3.13 10.67 11.09 10.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8631.9 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7754.2 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7962.3 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6000.5 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4505.6 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4470.2 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5980.3 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6003.0 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5904.5 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5192.5 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5542.5 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4217.6 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3263.0 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3263.0 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4523.8 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4539.0 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   3677.46 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   3646.64 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   6389.14 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   3637.61 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   2830.30 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   2830.09 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   2816.84 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   2950.70 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   6845.21 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   6885.27 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   6821.26 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   6861.30 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   4888.65 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   4888.07 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   4851.33 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   4850.75 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   5194.76 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   5218.05 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   5181.93 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   5205.22 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   4176.00 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   4175.67 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   4151.02 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   4150.69 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 226.04 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 204.74 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.51 594.02 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 143.11 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 110.22 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 108.69 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 148.91 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 153.05 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.55 635.40 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.49 570.79 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.50 586.12 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 441.71 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 331.66 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 329.06 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 440.22 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 441.89 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.37 434.64 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.33 382.23 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 407.99 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 310.46 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 240.19 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 240.20 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 333.01 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 334.12 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1801.33 2161.60 0.162 0.195 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
G NW APARTMENT 1631.61 1957.94 0.147 0.176 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
OFFICE 4628.63 5554.36 0.426 0.512 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.84 0.00635
G NE APARTMENT 1140.46 1368.55 0.103 0.123 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
G N1 APARTMENT 878.37 1054.04 0.079 0.095 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.42 0.00635
G N2 APARTMENT 866.11 1039.33 0.078 0.094 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.42 0.00635
G S1 APARTMENT 1186.68 1424.01 0.107 0.128 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.70 0.00635
G S2 APARTMENT 1219.70 1463.64 0.110 0.132 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.70 0.00635
M SW APARTMENT 5063.60 6076.32 0.456 0.547 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.24 0.00635
M NW APARTMENT 4548.71 5458.45 0.410 0.492 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
M SE APARTMENT 4670.91 5605.10 0.421 0.505 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.70 0.00635
M NE APARTMENT 3520.08 4224.10 0.317 0.381 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
M N1 APARTMENT 2643.02 3171.63 0.238 0.286 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.42 0.00635
M N2 APARTMENT 2622.27 3146.73 0.236 0.283 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.42 0.00635
M S1 APARTMENT 3508.14 4209.77 0.316 0.379 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.70 0.00635
M S2 APARTMENT 3521.46 4225.76 0.317 0.381 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.70 0.00635
T SW APARTMENT 3463.79 4156.55 0.312 0.374 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 32.98 0.00635
T NW APARTMENT 3046.06 3655.27 0.274 0.329 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.24 0.00635
T SE APARTMENT 3251.41 3901.69 0.293 0.351 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.70 0.00635
T NE APARTMENT 2474.21 2969.05 0.223 0.267 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.70 0.00635
T N1 APARTMENT 1914.15 2296.98 0.172 0.207 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 33.22 0.00635
T N2 APARTMENT 1914.18 2297.01 0.172 0.207 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 33.46 0.00635
T S1 APARTMENT 2653.78 3184.54 0.239 0.287 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.70 0.00635
T S2 APARTMENT 2662.68 3195.22 0.240 0.288 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.70 0.00635


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1961.42 2353.70 0.065 0.078 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G NW APARTMENT 1975.72 2370.87 0.065 0.078 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
OFFICE 3818.92 4582.71 0.122 0.147 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G NE APARTMENT 1968.09 2361.71 0.065 0.078 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G N1 APARTMENT 1285.38 1542.46 0.043 0.051 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G N2 APARTMENT 1285.20 1542.25 0.043 0.051 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G S1 APARTMENT 1274.00 1528.80 0.042 0.051 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
G S2 APARTMENT 1387.19 1664.63 0.046 0.055 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
M SW APARTMENT 3572.61 4287.13 0.118 0.142 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M NW APARTMENT 3606.48 4327.77 0.119 0.143 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M SE APARTMENT 3552.35 4262.82 0.118 0.141 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M NE APARTMENT 3586.21 4303.45 0.119 0.142 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M N1 APARTMENT 1917.99 2301.59 0.063 0.076 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M N2 APARTMENT 1917.50 2301.00 0.063 0.076 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M S1 APARTMENT 1886.43 2263.72 0.062 0.075 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
M S2 APARTMENT 1885.94 2263.13 0.062 0.075 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T SW APARTMENT 3284.95 3941.94 0.109 0.130 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T NW APARTMENT 3304.64 3965.57 0.109 0.131 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T SE APARTMENT 3274.10 3928.92 0.108 0.130 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T NE APARTMENT 3293.79 3952.54 0.109 0.131 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T N1 APARTMENT 2423.40 2908.08 0.080 0.096 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T N2 APARTMENT 2423.12 2907.74 0.080 0.096 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T S1 APARTMENT 2402.28 2882.73 0.080 0.095 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039
T S2 APARTMENT 2402.00 2882.40 0.080 0.095 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -26.30 0.00039


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.19 0.19 0.08 0.08
SPLIT GNW 0.18 0.18 0.08 0.08
SPLIT OFFICE 0.51 0.51 0.15 0.15
SPLIT GNE 0.12 0.12 0.08 0.08
SPLIT GN1 0.09 0.09 0.05 0.05
SPLIT GN2 0.09 0.09 0.05 0.05
SPLIT GS1 0.13 0.13 0.05 0.05
SPLIT GS2 0.13 0.13 0.06 0.06
SPLIT MSW 0.55 0.55 0.14 0.14
SPLIT MNW 0.49 0.49 0.14 0.14
SPLIT MSE 0.50 0.50 0.14 0.14
SPLIT MNE 0.38 0.38 0.14 0.14
SPLIT MN1 0.29 0.29 0.08 0.08
SPLIT MN2 0.28 0.28 0.08 0.08
SPLIT MS1 0.38 0.38 0.07 0.07
SPLIT MS2 0.38 0.38 0.07 0.07
SPLIT TSW 0.37 0.37 0.13 0.13
SPLIT TNW 0.33 0.33 0.13 0.13
SPLIT TSE 0.35 0.35 0.13 0.13
SPLIT TNE 0.27 0.27 0.13 0.13
SPLIT TN1 0.21 0.21 0.10 0.10
SPLIT TN2 0.21 0.21 0.10 0.10
SPLIT TS1 0.29 0.29 0.10 0.10
SPLIT TS2 0.29 0.29 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2260.00 6520.50 1526.25
G NW APARTMENT 2780.25 6832.25 2368.00
OFFICE 393.50 1617.75 146.75
G NE APARTMENT 2871.50 6879.00 2378.00
G N1 APARTMENT 1830.25 7029.25 1699.25
G N2 APARTMENT 1833.00 7027.00 1701.50
G S1 APARTMENT 1310.00 6582.00 847.25
G S2 APARTMENT 1497.00 6512.00 971.00
M SW APARTMENT 1949.75 5008.75 282.25
M NW APARTMENT 2168.25 5641.50 863.00
M SE APARTMENT 2023.75 5007.25 287.25
M NE APARTMENT 2228.00 5671.25 869.00
M N1 APARTMENT 1297.75 5614.75 296.50
M N2 APARTMENT 1300.75 5621.00 296.25
M S1 APARTMENT 1502.75 4733.50 48.75
M S2 APARTMENT 1504.75 4731.75 48.75
T SW APARTMENT 3580.50 5767.00 2052.25
T NW APARTMENT 4072.25 6264.75 2820.25
T SE APARTMENT 3630.75 5739.25 2053.75
T NE APARTMENT 4169.50 6293.25 2840.25
T N1 APARTMENT 3508.50 6319.50 2439.25
T N2 APARTMENT 3512.25 6317.25 2439.75
T S1 APARTMENT 2902.00 5708.50 1528.75
T S2 APARTMENT 2912.25 5695.75 1533.00
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 5180.75 7115.25 3032.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 3.50 0.00 3.50 0.00
G NW APARTMENT 4.50 0.50 4.50 0.50
OFFICE 7.25 3.00 0.00 0.00
G NE APARTMENT 4.25 0.00 4.25 0.00
G N1 APARTMENT 2.50 0.00 2.50 0.00
G N2 APARTMENT 4.00 0.00 4.00 0.00
G S1 APARTMENT 3.50 0.00 3.50 0.00
G S2 APARTMENT 4.00 0.00 4.00 0.00
M SW APARTMENT 0.75 0.00 0.75 0.00
M NW APARTMENT 1.75 0.00 1.75 0.00
M SE APARTMENT 1.00 0.00 1.00 0.00
M NE APARTMENT 1.75 0.00 1.75 0.00
M N1 APARTMENT 1.50 0.00 1.50 0.00
M N2 APARTMENT 1.25 0.00 1.25 0.00
M S1 APARTMENT 0.25 0.00 0.25 0.00
M S2 APARTMENT 0.50 0.00 0.50 0.00
T SW APARTMENT 0.50 0.00 0.50 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.50 0.00 0.50 0.00
T N1 APARTMENT 1.25 0.00 1.25 0.00
T N2 APARTMENT 3.75 0.00 3.75 0.00
T S1 APARTMENT 1.00 0.00 1.00 0.00
T S2 APARTMENT 1.25 0.00 1.25 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 48.00 3.50 40.75 0.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.365 0.148 0.000 0.057
G NW APARTMENT 1.71 2.50 268.97 0.352 0.148 0.000 0.056
OFFICE 0.94 1.00 268.97 0.519 0.166 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.352 0.148 0.000 0.056
G N1 APARTMENT 1.71 2.50 268.97 0.352 0.089 0.000 0.055
G N2 APARTMENT 1.71 2.50 268.97 0.352 0.089 0.000 0.055
G S1 APARTMENT 1.71 2.50 268.97 0.352 0.089 0.000 0.056
G S2 APARTMENT 1.71 2.50 268.97 0.352 0.089 0.000 0.056
M SW APARTMENT 1.71 2.50 268.97 0.353 0.213 0.000 0.068
M NW APARTMENT 1.71 2.50 268.97 0.353 0.212 0.000 0.068
M SE APARTMENT 1.71 2.50 268.97 0.353 0.213 0.000 0.068
M NE APARTMENT 1.71 2.50 268.97 0.353 0.212 0.000 0.068
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.128 0.000 0.068
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.128 0.000 0.068
M S1 APARTMENT 1.71 2.50 268.97 0.353 0.128 0.000 0.068
M S2 APARTMENT 1.71 2.50 268.97 0.353 0.128 0.000 0.068
T SW APARTMENT 1.71 2.50 268.97 0.353 0.281 0.000 0.079
T NW APARTMENT 1.71 2.50 268.97 0.352 0.281 0.000 0.080
T SE APARTMENT 1.71 2.50 268.97 0.353 0.281 0.000 0.079
T NE APARTMENT 1.71 2.50 268.97 0.352 0.281 0.000 0.080
T N1 APARTMENT 1.71 2.50 268.97 0.352 0.169 0.000 0.080
T N2 APARTMENT 1.71 2.50 268.97 0.352 0.169 0.000 0.080
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.170 0.000 0.079
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.170 0.000 0.079
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.355 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.503 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.370 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 434.73 0.00 01-JAN-00:15 32854.10 23-FEB-07:15
WaterSystems:Electricity 434.73 0.00 01-JAN-00:15 32854.10 23-FEB-07:15
Water Heater:WaterSystems:Electricity 434.73 0.00 01-JAN-00:15 32854.10 23-FEB-07:15
Fans:Electricity 256.97 8148.48 04-JAN-18:15 8148.48 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
ElectricityPurchased:Plant 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
Cogeneration:ElectricityPurchased 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
ElectricityNet:Plant 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
Cogeneration:ElectricityNet 1440.89 21261.09 01-JAN-03:15 82841.81 19-JUL-17:15
ExteriorLights:Electricity 40.05 0.00 01-JAN-08:30 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.05 0.00 01-JAN-08:30 2553.00 01-JAN-00:15
Electricity:HVAC 330.00 8148.48 04-JAN-18:15 29748.41 10-AUG-15:30
General:Fans:Electricity 256.97 8148.48 04-JAN-18:15 8148.48 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 73.03 0.00 01-JAN-00:15 21599.93 10-AUG-15:30


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 418.58 0.00 18-MAR-15:45 104817.13 25-DEC-09:00
Gas:HVAC 418.58 0.00 18-MAR-15:45 104817.13 25-DEC-09:00
Heating:Gas 418.58 0.00 18-MAR-15:45 104817.13 25-DEC-09:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1113.50 1851.25 26-MAR-20:45 144564.99 10-AUG-15:30
EnergyTransfer:Building 493.87 1581.68 11-MAY-16:15 64330.33 10-AUG-15:30
EnergyTransfer:Zone:G SW APARTMENT 12.29 0.03 30-JUN-05:45 2029.72 10-AUG-16:15
Heating:EnergyTransfer 180.79 0.00 19-MAR-11:30 59559.97 25-DEC-09:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 6.35 0.00 02-JAN-14:00 1977.40 25-DEC-09:00
Cooling:EnergyTransfer 313.08 0.00 02-JAN-07:30 64330.33 10-AUG-15:30
Cooling:EnergyTransfer:Zone:G SW APARTMENT 5.94 0.00 01-JAN-00:15 2029.72 10-AUG-16:15
EnergyTransfer:Zone:G NW APARTMENT 13.00 0.00 27-MAY-02:15 2070.83 25-DEC-09:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 9.18 0.00 11-FEB-16:30 2070.83 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 3.82 0.00 01-JAN-00:15 1720.95 21-JUL-17:30
EnergyTransfer:Zone:OFFICE 21.43 0.01 08-NOV-00:45 4410.42 10-AUG-13:30
Heating:EnergyTransfer:Zone:OFFICE 2.26 0.00 01-JAN-00:15 3462.16 27-DEC-07:15
Cooling:EnergyTransfer:Zone:OFFICE 19.18 0.00 02-JAN-07:30 4410.42 10-AUG-13:30
EnergyTransfer:Zone:G NE APARTMENT 13.25 0.02 01-NOV-19:15 2042.69 25-DEC-09:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 9.09 0.00 04-MAR-16:15 2042.69 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 4.16 0.00 01-JAN-00:15 1204.47 06-AUG-16:15
EnergyTransfer:Zone:G N1 APARTMENT 8.42 0.04 10-MAY-09:15 1257.67 25-DEC-09:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 4.88 0.00 26-JAN-21:00 1257.67 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 3.54 0.00 01-JAN-00:15 894.07 21-JUL-18:00
EnergyTransfer:Zone:G N2 APARTMENT 8.44 0.07 25-OCT-04:15 1257.08 25-DEC-09:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 4.88 0.00 26-JAN-21:00 1257.08 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 3.55 0.00 01-JAN-00:15 883.68 21-JUL-18:00
EnergyTransfer:Zone:G S1 APARTMENT 8.61 0.00 02-JUN-15:45 1345.11 02-SEP-13:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 2.68 0.00 01-JAN-11:30 1164.19 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 5.93 0.00 01-JAN-00:15 1345.11 02-SEP-13:15
EnergyTransfer:Zone:G S2 APARTMENT 9.13 0.03 01-DEC-10:30 1443.04 02-SEP-13:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 2.99 0.00 01-JAN-11:45 1271.60 25-DEC-09:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 6.14 0.00 01-JAN-00:15 1443.04 02-SEP-13:15
EnergyTransfer:Zone:M SW APARTMENT 33.19 0.03 07-NOV-13:30 5597.48 10-AUG-16:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 5.70 0.00 01-JAN-11:30 3957.65 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 27.49 0.00 01-JAN-00:15 5597.48 10-AUG-16:15
EnergyTransfer:Zone:M NW APARTMENT 29.20 0.11 14-APR-09:45 5012.73 30-JUN-18:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 11.38 0.00 04-JAN-22:00 4335.46 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 17.81 0.00 01-JAN-00:15 5012.73 30-JUN-18:00
EnergyTransfer:Zone:M SE APARTMENT 34.22 0.40 08-DEC-11:00 5195.52 10-AUG-13:45
Heating:EnergyTransfer:Zone:M SE APARTMENT 5.77 0.00 01-JAN-10:00 3885.77 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 28.46 0.00 01-JAN-00:15 5195.52 10-AUG-13:45
EnergyTransfer:Zone:M NE APARTMENT 30.37 0.05 04-NOV-03:30 4266.10 25-DEC-09:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 11.42 0.00 04-JAN-22:00 4266.10 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 18.95 0.00 01-JAN-00:15 3702.11 18-JUN-17:00
EnergyTransfer:Zone:M N1 APARTMENT 21.36 0.06 05-APR-13:45 2844.56 30-JUN-18:30
Heating:EnergyTransfer:Zone:M N1 APARTMENT 3.24 0.00 01-JAN-16:00 2220.04 25-DEC-12:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 18.12 0.00 01-JAN-00:15 2844.56 30-JUN-18:30
EnergyTransfer:Zone:M N2 APARTMENT 21.38 0.06 02-APR-09:15 2814.66 30-JUN-18:30
Heating:EnergyTransfer:Zone:M N2 APARTMENT 3.25 0.00 01-JAN-16:00 2217.76 25-DEC-12:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 18.13 0.00 01-JAN-00:15 2814.66 30-JUN-18:30
EnergyTransfer:Zone:M S1 APARTMENT 31.32 0.04 23-FEB-12:45 3949.37 13-SEP-15:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 1.00 0.00 01-JAN-09:15 1826.06 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 30.32 0.00 01-JAN-00:15 3949.37 13-SEP-15:15
EnergyTransfer:Zone:M S2 APARTMENT 31.33 0.04 19-DEC-10:00 3956.44 02-SEP-13:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 1.01 0.00 01-JAN-09:15 1824.27 25-DEC-09:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 30.32 0.00 01-JAN-00:15 3956.44 02-SEP-13:15
EnergyTransfer:Zone:T SW APARTMENT 24.11 0.02 23-MAY-04:30 3665.63 30-JUN-16:15
Heating:EnergyTransfer:Zone:T SW APARTMENT 13.04 0.00 02-JAN-14:15 3589.62 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 11.08 0.00 01-JAN-00:15 3665.63 30-JUN-16:15
EnergyTransfer:Zone:T NW APARTMENT 24.67 0.00 07-APR-22:15 3691.10 25-DEC-09:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 17.12 0.00 27-JAN-14:30 3691.10 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 7.55 0.00 01-JAN-00:15 3336.95 30-JUN-17:45
EnergyTransfer:Zone:T SE APARTMENT 24.14 0.01 31-MAY-01:15 3551.88 25-DEC-09:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 12.88 0.00 02-JAN-14:30 3551.88 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 11.26 0.00 01-JAN-00:15 3467.77 10-AUG-13:45
EnergyTransfer:Zone:T NE APARTMENT 24.67 0.00 18-SEP-02:00 3653.93 25-DEC-09:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 16.88 0.00 27-JAN-12:30 3653.93 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 7.79 0.00 01-JAN-00:15 2601.64 30-JUN-15:15
EnergyTransfer:Zone:T N1 APARTMENT 17.24 0.04 18-MAY-13:30 2434.29 25-DEC-09:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 10.73 0.00 27-JAN-12:30 2434.29 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 6.51 0.00 01-JAN-00:15 2120.86 30-JUN-16:15
EnergyTransfer:Zone:T N2 APARTMENT 17.26 0.00 11-OCT-02:15 2433.49 25-DEC-09:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 10.74 0.00 27-JAN-12:30 2433.49 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 6.52 0.00 01-JAN-00:15 2105.05 30-JUN-16:15
EnergyTransfer:Zone:T S1 APARTMENT 17.40 0.01 25-MAY-02:00 2791.78 10-AUG-13:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 7.15 0.00 01-JAN-11:45 2326.49 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 10.25 0.00 01-JAN-00:15 2791.78 10-AUG-13:30
EnergyTransfer:Zone:T S2 APARTMENT 17.43 0.03 01-OCT-04:30 2804.78 10-AUG-13:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 7.16 0.00 01-JAN-11:45 2325.55 25-DEC-09:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 10.27 0.00 01-JAN-00:15 2804.78 10-AUG-13:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 619.62 0.00 26-MAR-19:00 83853.71 25-DEC-09:00
HeatingCoils:EnergyTransfer 334.86 0.00 18-MAR-15:45 83853.71 25-DEC-09:00
CoolingCoils:EnergyTransfer 284.76 0.00 01-JAN-00:15 80234.65 10-AUG-15:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 6.354 -5.939 0.000 0.000 3.884 1.087 12.213 14.133 0.000 0.112 0.000 0.000 -8.988 0.000 -5.712 -17.143
G NW APARTMENT 9.178 -3.824 0.000 0.000 3.905 1.087 12.213 6.414 0.000 0.112 0.000 0.000 -9.483 0.000 -5.618 -13.985
OFFICE 2.255 -19.179 0.000 0.000 0.525 26.452 9.482 13.969 0.000 0.062 0.001 0.000 -8.745 0.000 -5.192 -19.628
G NE APARTMENT 9.094 -4.157 0.000 0.000 3.916 1.087 12.213 6.416 0.000 0.112 0.000 0.000 -9.209 0.000 -5.599 -13.872
G N1 APARTMENT 4.882 -3.542 0.000 0.000 3.916 1.087 12.213 2.019 0.000 0.073 0.000 0.000 -5.963 0.000 -3.591 -11.093
G N2 APARTMENT 4.884 -3.553 0.000 0.000 3.916 1.087 12.213 2.018 0.000 0.073 0.000 0.000 -5.962 0.000 -3.591 -11.086
G S1 APARTMENT 2.683 -5.929 0.000 0.000 3.885 1.087 12.213 9.787 0.000 0.073 0.000 0.000 -5.454 0.000 -3.692 -14.652
G S2 APARTMENT 2.989 -6.140 0.000 0.000 3.882 1.087 12.213 9.782 0.000 0.073 0.000 0.000 -5.456 0.000 -3.700 -14.729
M SW APARTMENT 5.701 -27.489 0.000 0.000 3.776 1.087 12.213 13.687 0.000 0.157 8.854 0.000 -9.651 0.000 -8.334 -0.000
M NW APARTMENT 11.383 -17.814 0.000 0.000 3.831 1.087 12.213 6.083 0.000 0.158 1.281 0.000 -10.047 0.000 -8.173 -0.001
M SE APARTMENT 5.769 -28.456 0.000 0.000 3.782 1.087 12.213 13.699 0.000 0.157 9.445 0.000 -9.371 0.000 -8.326 -0.000
M NE APARTMENT 11.418 -18.947 0.000 0.000 3.842 1.087 12.213 6.080 0.000 0.158 2.041 0.000 -9.740 0.000 -8.151 -0.001
M N1 APARTMENT 3.243 -18.115 0.000 0.000 3.829 1.087 12.213 1.820 0.000 0.102 7.442 0.000 -6.374 0.000 -5.246 -0.000
M N2 APARTMENT 3.251 -18.130 0.000 0.000 3.830 1.087 12.213 1.820 0.000 0.102 7.444 0.000 -6.372 0.000 -5.245 -0.000
M S1 APARTMENT 1.004 -30.316 0.000 0.000 3.749 1.087 12.213 9.498 0.000 0.102 13.968 0.000 -5.903 0.000 -5.400 -0.000
M S2 APARTMENT 1.006 -30.322 0.000 0.000 3.749 1.087 12.213 9.497 0.000 0.102 13.971 0.000 -5.902 0.000 -5.400 -0.000
T SW APARTMENT 13.037 -11.077 0.000 0.000 3.841 1.087 12.213 13.634 0.000 0.208 0.000 0.000 -9.151 0.000 -10.702 -13.088
T NW APARTMENT 17.118 -7.555 0.000 0.000 3.874 1.087 12.213 6.040 0.000 0.208 0.000 0.000 -9.596 0.000 -10.550 -12.837
T SE APARTMENT 12.880 -11.260 0.000 0.000 3.846 1.087 12.213 13.671 0.000 0.208 0.000 0.000 -8.902 0.000 -10.699 -13.044
T NE APARTMENT 16.880 -7.792 0.000 0.000 3.885 1.087 12.213 6.066 0.000 0.208 0.000 0.000 -9.322 0.000 -10.531 -12.694
T N1 APARTMENT 10.732 -6.505 0.000 0.000 3.878 1.087 12.213 1.827 0.000 0.135 0.000 0.000 -6.052 0.000 -6.698 -10.616
T N2 APARTMENT 10.745 -6.516 0.000 0.000 3.878 1.087 12.213 1.825 0.000 0.135 0.000 0.000 -6.050 0.000 -6.700 -10.616
T S1 APARTMENT 7.148 -10.250 0.000 0.000 3.829 1.087 12.213 9.491 0.000 0.135 0.000 0.000 -5.587 0.000 -6.845 -11.220
T S2 APARTMENT 7.158 -10.275 0.000 0.000 3.829 1.087 12.213 9.489 0.000 0.135 0.000 0.000 -5.586 0.000 -6.846 -11.204
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.076 0.000 0.011 0.000 0.000 -1.122 0.000 -1.756 -11.791
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.286 0.000 0.395 16.347 0.000 -2.957 0.000 -35.132 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.076 0.000 0.011 0.000 0.000 -1.233 0.000 -1.447 -11.989
Total Facility 180.793 -313.080 0.000 0.000 89.077 95.189 296.854 189.202 0.000 3.514 80.793 0.000 -188.179 0.000 -198.875 -235.289


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 10-AUG-16:13 0.00 -2030.67 0.00 0.00 84.76 64.86 588.62 2361.73 0.00 179.49 0.00 0.00 0.00 0.00 0.00 -1248.78
G NW APARTMENT 21-JUL-17:25 0.00 -1721.11 0.00 0.00 141.80 87.56 588.62 1983.07 0.00 127.41 0.00 0.00 0.00 0.00 0.00 -1207.35
OFFICE 14-SEP-06:01 0.00 -7725.94 0.00 0.00 0.00 416.15 294.31 73.47 0.00 0.00 6942.01 0.00 0.00 0.00 0.00 0.00
G NE APARTMENT 06-AUG-16:05 0.00 -1205.18 0.00 0.00 84.76 64.86 588.62 575.85 0.00 247.29 0.00 0.00 0.00 0.00 0.00 -356.20
G N1 APARTMENT 21-JUL-18:00 0.00 -894.08 0.00 0.00 141.81 87.56 588.62 378.72 0.00 69.04 0.00 0.00 0.00 0.00 0.00 -371.67
G N2 APARTMENT 21-JUL-18:00 0.00 -883.69 0.00 0.00 141.81 87.56 588.62 378.89 0.00 69.04 0.00 0.00 0.00 0.00 0.00 -382.22
G S1 APARTMENT 02-SEP-13:15 0.00 -1344.87 0.00 0.00 40.75 12.97 382.60 2190.16 0.00 80.22 0.00 0.00 0.00 0.00 0.00 -1361.83
G S2 APARTMENT 02-SEP-13:15 0.00 -1442.79 0.00 0.00 40.75 12.97 382.60 2188.73 0.00 80.22 0.00 0.00 0.00 0.00 0.00 -1262.48
M SW APARTMENT 10-AUG-16:08 0.00 -5598.60 0.00 0.00 84.76 64.86 588.62 2342.19 0.00 257.34 2260.84 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 30-JUN-18:00 0.00 -5012.60 0.00 0.00 141.80 87.56 588.62 2129.37 0.00 228.37 1836.88 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 10-AUG-13:45 0.00 -5195.28 0.00 0.00 40.75 12.97 382.60 1860.63 0.00 399.47 2498.86 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 18-JUN-17:00 0.00 -3702.12 0.00 0.00 84.76 64.86 588.62 767.40 0.00 222.25 1974.23 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 30-JUN-18:30 0.00 -2844.46 0.00 0.00 141.81 103.77 547.42 590.17 0.00 112.12 1349.18 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 30-JUN-18:30 0.00 -2814.56 0.00 0.00 141.81 103.77 547.42 590.36 0.00 112.12 1319.08 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 13-SEP-15:15 0.00 -3948.46 0.00 0.00 48.90 45.40 470.90 1451.54 0.00 70.64 1861.08 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 02-SEP-13:15 0.00 -3955.77 0.00 0.00 40.75 12.97 382.60 2177.50 0.00 107.34 1234.61 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 30-JUN-16:08 0.00 -3666.10 0.00 0.00 84.76 64.86 588.62 2103.25 0.00 434.93 389.68 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 30-JUN-17:45 0.00 -3336.90 0.00 0.00 141.80 87.56 588.62 2098.85 0.00 301.49 118.58 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 10-AUG-13:45 0.00 -3467.61 0.00 0.00 40.75 12.97 382.60 1828.29 0.00 525.94 677.06 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 30-JUN-15:15 0.00 -2601.49 0.00 0.00 48.90 45.40 470.90 730.69 0.00 505.78 799.82 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 30-JUN-16:15 0.00 -2121.80 0.00 0.00 84.76 64.86 588.62 420.61 0.00 262.35 700.61 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 30-JUN-16:15 0.00 -2105.99 0.00 0.00 84.76 64.86 588.62 420.83 0.00 262.35 684.58 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 10-AUG-13:45 0.00 -2791.61 0.00 0.00 40.75 12.97 382.60 1555.47 0.00 317.24 482.57 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 10-AUG-13:30 0.00 -2804.55 0.00 0.00 40.75 12.97 382.60 1674.85 0.00 296.61 396.78 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-AUG-15:30 0.00 -64324.69 0.00 0.00 1191.97 4512.09 11708.34 28983.35 0.00 6551.42 11377.52 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 25-DEC-08:53 1977.49 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -755.47 0.00 -1038.62 -665.31
G NW APARTMENT 25-DEC-09:00 2071.07 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -851.84 0.00 -1038.62 -662.52
OFFICE 28-NOV-07:01 5961.89 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -473.34 0.00 -367.32 -5831.70
G NE APARTMENT 25-DEC-08:53 2042.78 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -784.04 0.00 -1038.62 -702.04
G N1 APARTMENT 25-DEC-09:00 1257.70 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -517.53 0.00 -626.47 -595.62
G N2 APARTMENT 25-DEC-09:00 1257.12 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -517.54 0.00 -626.47 -595.03
G S1 APARTMENT 04-APR-06:01 1621.31 0.00 0.00 0.00 161.47 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -381.67 0.00 0.00 -1825.87
G S2 APARTMENT 23-OCT-06:01 1475.43 0.00 0.00 0.00 161.45 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -402.16 0.00 -117.35 -1542.13
M SW APARTMENT 25-DEC-09:00 3957.78 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -783.32 0.00 -1493.39 -2162.99
M NW APARTMENT 25-DEC-09:00 4335.41 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -879.80 0.00 -1493.39 -2444.14
M SE APARTMENT 25-DEC-09:00 3886.01 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -714.09 0.00 -1493.39 -2160.45
M NE APARTMENT 25-DEC-09:00 4266.06 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -810.57 0.00 -1493.39 -2444.03
M N1 APARTMENT 11-FEB-08:01 2696.31 0.00 0.00 0.00 74.08 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -338.55 0.00 -116.18 -2723.60
M N2 APARTMENT 13-NOV-17:01 2705.46 0.00 0.00 0.00 98.77 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -395.61 0.00 -206.67 -2855.43
M S1 APARTMENT 16-JAN-01:55 2233.98 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -654.90 0.00 0.00 -2016.57
M S2 APARTMENT 10-MAR-07:01 1910.03 0.00 0.00 0.00 161.40 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -272.18 0.00 -472.39 -1751.62
T SW APARTMENT 25-DEC-08:53 3589.58 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -760.11 0.00 -1977.40 -1333.99
T NW APARTMENT 25-DEC-08:53 3691.05 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -859.43 0.00 -1977.40 -1336.14
T SE APARTMENT 25-DEC-09:00 3552.00 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -690.07 0.00 -1977.40 -1366.44
T NE APARTMENT 25-DEC-08:53 3653.96 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -789.42 0.00 -1977.40 -1369.07
T N1 APARTMENT 25-DEC-09:00 2434.61 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -522.44 0.00 -1192.76 -1201.33
T N2 APARTMENT 25-DEC-09:00 2433.81 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -522.45 0.00 -1192.76 -1200.52
T S1 APARTMENT 25-DEC-08:53 2326.60 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -422.95 0.00 -1192.76 -1192.80
T S2 APARTMENT 25-DEC-08:53 2325.66 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -422.97 0.00 -1192.76 -1191.85
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 25-DEC-09:00 59107.32 0.00 0.00 0.00 1701.35 2250.82 9539.01 0.00 0.00 0.00 0.00 0.00 -15385.43 0.00 -32236.74 -24976.31



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Sec1.1A-General Information

Data
Weather File Helena Regional Airport MT USA TMY3 WMO#=727720
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 40.75
Number of hours cooling loads not met 0.50
Number of hours not met 41.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.05 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 418.58 104817.13 0.00 0.00
Space Cooling 73.03 18090.85 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 256.97 8148.48 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 434.73 24991.60 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1440.89   418.58   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1440.89
Natural Gas 0.00 418.58
Additional 0.00 0.00
Total 517.65 1859.47


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 23.30
Fans-Interior 81.98
Service Water Heating 138.69
Receptacle Equipment 165.14
Miscellaneous 12.78
Subtotal 459.67


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 133.53
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 133.53


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.37
Space Heating 22.51
Space Cooling 3.93
Fans-Interior 13.82
Service Water Heating 23.38
Receptacle Equipment 27.84
Miscellaneous 2.15



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.194722
G NW APARTMENT DIRECT AIR 0.176376
OFFICE DIRECT AIR 0.511718
G NE APARTMENT DIRECT AIR 0.123281
G N1 APARTMENT DIRECT AIR 0.094951
G N2 APARTMENT DIRECT AIR 0.093626
G S1 APARTMENT DIRECT AIR 0.128279
G S2 APARTMENT DIRECT AIR 0.131848
M SW APARTMENT DIRECT AIR 0.547365
M NW APARTMENT DIRECT AIR 0.491707
M SE APARTMENT DIRECT AIR 0.504908
M NE APARTMENT DIRECT AIR 0.380507
M N1 APARTMENT DIRECT AIR 0.285710
M N2 APARTMENT DIRECT AIR 0.283467
M S1 APARTMENT DIRECT AIR 0.379223
M S2 APARTMENT DIRECT AIR 0.380663
T SW APARTMENT DIRECT AIR 0.374417
T NW APARTMENT DIRECT AIR 0.329270
T SE APARTMENT DIRECT AIR 0.351459
T NE APARTMENT DIRECT AIR 0.267448
T N1 APARTMENT DIRECT AIR 0.206914
T N2 APARTMENT DIRECT AIR 0.206917
T S1 APARTMENT DIRECT AIR 0.286866
T S2 APARTMENT DIRECT AIR 0.287828


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.194722
SPLIT GNW MAIN BRANCH 0.176376
SPLIT OFFICE MAIN BRANCH 0.511718
SPLIT GNE MAIN BRANCH 0.123281
SPLIT GN1 MAIN BRANCH 0.094951
SPLIT GN2 MAIN BRANCH 0.093626
SPLIT GS1 MAIN BRANCH 0.128279
SPLIT GS2 MAIN BRANCH 0.131848
SPLIT MSW MAIN BRANCH 0.547365
SPLIT MNW MAIN BRANCH 0.491707
SPLIT MSE MAIN BRANCH 0.504908
SPLIT MNE MAIN BRANCH 0.380507
SPLIT MN1 MAIN BRANCH 0.285710
SPLIT MN2 MAIN BRANCH 0.283467
SPLIT MS1 MAIN BRANCH 0.379223
SPLIT MS2 MAIN BRANCH 0.380663
SPLIT TSW MAIN BRANCH 0.374417
SPLIT TNW MAIN BRANCH 0.329270
SPLIT TSE MAIN BRANCH 0.351459
SPLIT TNE MAIN BRANCH 0.267448
SPLIT TN1 MAIN BRANCH 0.206914
SPLIT TN2 MAIN BRANCH 0.206917
SPLIT TS1 MAIN BRANCH 0.286866
SPLIT TS2 MAIN BRANCH 0.287828


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.194722
SPLIT GNW 0.176376
SPLIT OFFICE 0.511718
SPLIT GNE 0.123281
SPLIT GN1 0.094951
SPLIT GN2 0.093626
SPLIT GS1 0.128279
SPLIT GS2 0.131848
SPLIT MSW 0.547365
SPLIT MNW 0.491707
SPLIT MSE 0.504908
SPLIT MNE 0.380507
SPLIT MN1 0.285710
SPLIT MN2 0.283467
SPLIT MS1 0.379223
SPLIT MS2 0.380663
SPLIT TSW 0.374417
SPLIT TNW 0.329270
SPLIT TSE 0.351459
SPLIT TNE 0.267448
SPLIT TN1 0.206914
SPLIT TN2 0.206917
SPLIT TS1 0.286866
SPLIT TS2 0.287828


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.194722 0.026898
SPLIT GNW OA CONTROLLER 0.176376 0.025953
SPLIT OFFICE OA CONTROLLER 0.511718 0.038104
SPLIT GNE OA CONTROLLER 0.123281 0.025953
SPLIT GN1 OA CONTROLLER 0.094951 0.025953
SPLIT GN2 OA CONTROLLER 0.093626 0.025953
SPLIT GS1 OA CONTROLLER 0.128279 0.025953
SPLIT GS2 OA CONTROLLER 0.131848 0.025953
SPLIT MSW OA CONTROLLER 0.547365 0.051906
SPLIT MNW OA CONTROLLER 0.491707 0.051906
SPLIT MSE OA CONTROLLER 0.504908 0.051906
SPLIT MNE OA CONTROLLER 0.380507 0.051906
SPLIT MN1 OA CONTROLLER 0.285710 0.051906
SPLIT MN2 OA CONTROLLER 0.283467 0.051906
SPLIT MS1 OA CONTROLLER 0.379223 0.051906
SPLIT MS2 OA CONTROLLER 0.380663 0.051906
SPLIT TSW OA CONTROLLER 0.374417 0.025953
SPLIT TNW OA CONTROLLER 0.329270 0.025953
SPLIT TSE OA CONTROLLER 0.351459 0.025953
SPLIT TNE OA CONTROLLER 0.267448 0.025953
SPLIT TN1 OA CONTROLLER 0.206914 0.025953
SPLIT TN2 OA CONTROLLER 0.206917 0.025953
SPLIT TS1 OA CONTROLLER 0.286866 0.025953
SPLIT TS2 OA CONTROLLER 0.287828 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.194722 3223.35 0.798655
SPLIT GNW COOLING COIL 0.176376 2919.64 0.798655
SPLIT OFFICE COOLING COIL 0.511718 8470.75 0.798655
SPLIT GNE COOLING COIL 0.123281 2040.74 0.798655
SPLIT GN1 COOLING COIL 0.094951 1571.78 0.798655
SPLIT GN2 COOLING COIL 0.093626 1549.85 0.798655
SPLIT GS1 COOLING COIL 0.128279 2123.47 0.798655
SPLIT GS2 COOLING COIL 0.131848 2182.55 0.798655
SPLIT MSW COOLING COIL 0.547365 9060.84 0.798655
SPLIT MNW COOLING COIL 0.491707 8139.50 0.798655
SPLIT MSE COOLING COIL 0.504908 8358.03 0.798655
SPLIT MNE COOLING COIL 0.380507 6298.75 0.798655
SPLIT MN1 COOLING COIL 0.285710 4729.52 0.798655
SPLIT MN2 COOLING COIL 0.283467 4692.38 0.798655
SPLIT MS1 COOLING COIL 0.379223 6277.49 0.798655
SPLIT MS2 COOLING COIL 0.380663 6301.33 0.798655
SPLIT TSW COOLING COIL 0.374417 6197.92 0.798655
SPLIT TNW COOLING COIL 0.329270 5450.59 0.798655
SPLIT TSE COOLING COIL 0.351459 5817.90 0.798655
SPLIT TNE COOLING COIL 0.267448 4427.21 0.798655
SPLIT TN1 COOLING COIL 0.206914 3425.15 0.798655
SPLIT TN2 COOLING COIL 0.206917 3425.20 0.798655
SPLIT TS1 COOLING COIL 0.286866 4748.65 0.798655
SPLIT TS2 COOLING COIL 0.287828 4764.57 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.194722 0.194722 0.194722 0.194722 3677.46 3223.35 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.176376 0.176376 0.176376 0.176376 3646.64 2919.64 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.511718 0.511718 0.511718 0.511718 6389.14 8470.75 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.123281 0.123281 0.123281 0.123281 3637.61 2040.74 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.094951 0.094951 0.094951 0.094951 2830.30 1571.78 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.093626 0.093626 0.093626 0.093626 2830.09 1549.85 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.128279 0.128279 0.128279 0.128279 2816.84 2123.47 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.131848 0.131848 0.131848 0.131848 2950.70 2182.55 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.547365 0.547365 0.547365 0.547365 6845.21 9060.84 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.491707 0.491707 0.491707 0.491707 6885.27 8139.50 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.504908 0.504908 0.504908 0.504908 6821.26 8358.03 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.380507 0.380507 0.380507 0.380507 6861.30 6298.75 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.285710 0.285710 0.285710 0.285710 4888.65 4729.52 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.283467 0.283467 0.283467 0.283467 4888.07 4692.38 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.379223 0.379223 0.379223 0.379223 4851.33 6277.49 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.380663 0.380663 0.380663 0.380663 4850.75 6301.33 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.374417 0.374417 0.374417 0.374417 5194.76 6197.92 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.329270 0.329270 0.329270 0.329270 5218.05 5450.59 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.351459 0.351459 0.351459 0.351459 5181.93 5817.90 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.267448 0.267448 0.267448 0.267448 5205.22 4427.21 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.206914 0.206914 0.206914 0.206914 4176.00 3425.15 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.206917 0.206917 0.206917 0.206917 4175.67 3425.20 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.286866 0.286866 0.286866 0.286866 4151.02 4748.65 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.287828 0.287828 0.287828 0.287828 4150.69 4764.57 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.194722
SPLIT GNW SUPPLY FAN 0.176376
SPLIT OFFICE SUPPLY FAN 0.511718
SPLIT GNE SUPPLY FAN 0.123281
SPLIT GN1 SUPPLY FAN 0.094951
SPLIT GN2 SUPPLY FAN 0.093626
SPLIT GS1 SUPPLY FAN 0.128279
SPLIT GS2 SUPPLY FAN 0.131848
SPLIT MSW SUPPLY FAN 0.547365
SPLIT MNW SUPPLY FAN 0.491707
SPLIT MSE SUPPLY FAN 0.504908
SPLIT MNE SUPPLY FAN 0.380507
SPLIT MN1 SUPPLY FAN 0.285710
SPLIT MN2 SUPPLY FAN 0.283467
SPLIT MS1 SUPPLY FAN 0.379223
SPLIT MS2 SUPPLY FAN 0.380663
SPLIT TSW SUPPLY FAN 0.374417
SPLIT TNW SUPPLY FAN 0.329270
SPLIT TSE SUPPLY FAN 0.351459
SPLIT TNE SUPPLY FAN 0.267448
SPLIT TN1 SUPPLY FAN 0.206914
SPLIT TN2 SUPPLY FAN 0.206917
SPLIT TS1 SUPPLY FAN 0.286866
SPLIT TS2 SUPPLY FAN 0.287828


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 3677.46
SPLIT GNW HEATING COIL 3646.64
SPLIT OFFICE HEATING COIL 6389.14
SPLIT GNE HEATING COIL 3637.61
SPLIT GN1 HEATING COIL 2830.30
SPLIT GN2 HEATING COIL 2830.09
SPLIT GS1 HEATING COIL 2816.84
SPLIT GS2 HEATING COIL 2950.70
SPLIT MSW HEATING COIL 6845.21
SPLIT MNW HEATING COIL 6885.27
SPLIT MSE HEATING COIL 6821.26
SPLIT MNE HEATING COIL 6861.30
SPLIT MN1 HEATING COIL 4888.65
SPLIT MN2 HEATING COIL 4888.07
SPLIT MS1 HEATING COIL 4851.33
SPLIT MS2 HEATING COIL 4850.75
SPLIT TSW HEATING COIL 5194.76
SPLIT TNW HEATING COIL 5218.05
SPLIT TSE HEATING COIL 5181.93
SPLIT TNE HEATING COIL 5205.22
SPLIT TN1 HEATING COIL 4176.00
SPLIT TN2 HEATING COIL 4175.67
SPLIT TS1 HEATING COIL 4151.02
SPLIT TS2 HEATING COIL 4150.69



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:55

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -4.7
February 21.74 -3.7
March 21.88 2.15
April 22.18 6.19
May 22.67 11.83
June 24.07 17.35
July 24.35 20.52
August 24.28 18.54
September 24.01 14.70
October 22.33 6.26
November 21.81 1.12
December 21.72 -5.0
     
Annual Sum or Average 22.73 7.16
Minimum of Months 21.71 -5.0
Maximum of Months 24.35 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.73 2.15
April 21.90 6.19
May 22.46 11.83
June 24.02 17.35
July 24.34 20.52
August 24.22 18.54
September 23.78 14.70
October 21.89 6.26
November 21.71 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.60 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.34 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.14 -4.7
February 20.59 -3.7
March 21.69 2.15
April 22.63 6.19
May 23.73 11.83
June 25.58 17.35
July 26.40 20.52
August 26.01 18.54
September 25.66 14.70
October 22.97 6.26
November 21.41 1.12
December 19.96 -5.0
     
Annual Sum or Average 23.08 7.16
Minimum of Months 19.96 -5.0
Maximum of Months 26.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.71 2.15
April 21.84 6.19
May 22.42 11.83
June 23.97 17.35
July 24.32 20.52
August 24.19 18.54
September 23.69 14.70
October 21.82 6.26
November 21.70 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.57 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.32 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.71 2.15
April 21.79 6.19
May 22.23 11.83
June 23.92 17.35
July 24.31 20.52
August 24.19 18.54
September 23.75 14.70
October 21.82 6.26
November 21.70 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.55 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.31 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.71 2.15
April 21.79 6.19
May 22.22 11.83
June 23.91 17.35
July 24.31 20.52
August 24.19 18.54
September 23.74 14.70
October 21.82 6.26
November 21.70 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.55 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.31 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -4.7
February 21.73 -3.7
March 21.86 2.15
April 22.11 6.19
May 22.53 11.83
June 24.06 17.35
July 24.35 20.52
August 24.30 18.54
September 24.10 14.70
October 22.37 6.26
November 21.83 1.12
December 21.73 -5.0
     
Annual Sum or Average 22.73 7.16
Minimum of Months 21.71 -5.0
Maximum of Months 24.35 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -4.7
February 21.73 -3.7
March 21.86 2.15
April 22.13 6.19
May 22.58 11.83
June 24.09 17.35
July 24.36 20.52
August 24.31 18.54
September 24.12 14.70
October 22.39 6.26
November 21.83 1.12
December 21.73 -5.0
     
Annual Sum or Average 22.74 7.16
Minimum of Months 21.71 -5.0
Maximum of Months 24.36 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -4.7
February 21.99 -3.7
March 22.51 2.15
April 23.29 6.19
May 24.03 11.83
June 24.39 17.35
July 24.40 20.52
August 24.40 18.54
September 24.34 14.70
October 23.50 6.26
November 22.30 1.12
December 21.83 -5.0
     
Annual Sum or Average 23.24 7.16
Minimum of Months 21.80 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.71 -3.7
March 21.88 2.15
April 22.68 6.19
May 23.79 11.83
June 24.39 17.35
July 24.40 20.52
August 24.39 18.54
September 24.23 14.70
October 22.56 6.26
November 21.81 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.94 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.7
February 21.94 -3.7
March 22.46 2.15
April 23.29 6.19
May 24.03 11.83
June 24.39 17.35
July 24.40 20.52
August 24.40 18.54
September 24.33 14.70
October 23.47 6.26
November 22.25 1.12
December 21.82 -5.0
     
Annual Sum or Average 23.22 7.16
Minimum of Months 21.79 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.83 2.15
April 22.59 6.19
May 23.72 11.83
June 24.37 17.35
July 24.40 20.52
August 24.39 18.54
September 24.18 14.70
October 22.44 6.26
November 21.77 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.91 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.86 2.15
April 22.64 6.19
May 23.83 11.83
June 24.39 17.35
July 24.40 20.52
August 24.40 18.54
September 24.28 14.70
October 22.63 6.26
November 21.84 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.95 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.85 2.15
April 22.63 6.19
May 23.82 11.83
June 24.39 17.35
July 24.40 20.52
August 24.40 18.54
September 24.27 14.70
October 22.62 6.26
November 21.83 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.95 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 -4.7
February 22.15 -3.7
March 22.74 2.15
April 23.51 6.19
May 24.16 11.83
June 24.40 17.35
July 24.40 20.52
August 24.40 18.54
September 24.38 14.70
October 23.80 6.26
November 22.59 1.12
December 21.96 -5.0
     
Annual Sum or Average 23.37 7.16
Minimum of Months 21.90 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.90 -4.7
February 22.15 -3.7
March 22.74 2.15
April 23.52 6.19
May 24.16 11.83
June 24.40 17.35
July 24.40 20.52
August 24.40 18.54
September 24.38 14.70
October 23.80 6.26
November 22.58 1.12
December 21.96 -5.0
     
Annual Sum or Average 23.37 7.16
Minimum of Months 21.90 -5.0
Maximum of Months 24.40 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.7
February 21.91 -3.7
March 22.22 2.15
April 22.79 6.19
May 23.47 11.83
June 24.22 17.35
July 24.36 20.52
August 24.28 18.54
September 23.91 14.70
October 22.69 6.26
November 22.02 1.12
December 21.79 -5.0
     
Annual Sum or Average 22.96 7.16
Minimum of Months 21.79 -5.0
Maximum of Months 24.36 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.71 -3.7
March 21.87 2.15
April 22.43 6.19
May 23.31 11.83
June 24.18 17.35
July 24.35 20.52
August 24.22 18.54
September 23.67 14.70
October 22.19 6.26
November 21.75 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.76 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.35 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -4.7
February 21.88 -3.7
March 22.19 2.15
April 22.82 6.19
May 23.50 11.83
June 24.21 17.35
July 24.36 20.52
August 24.28 18.54
September 23.90 14.70
October 22.71 6.26
November 22.00 1.12
December 21.78 -5.0
     
Annual Sum or Average 22.96 7.16
Minimum of Months 21.77 -5.0
Maximum of Months 24.36 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.82 2.15
April 22.38 6.19
May 23.31 11.83
June 24.13 17.35
July 24.33 20.52
August 24.19 18.54
September 23.63 14.70
October 22.11 6.26
November 21.73 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.73 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.33 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.81 2.15
April 22.34 6.19
May 23.30 11.83
June 24.19 17.35
July 24.35 20.52
August 24.23 18.54
September 23.66 14.70
October 22.09 6.26
November 21.74 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.74 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.35 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -4.7
February 21.70 -3.7
March 21.81 2.15
April 22.34 6.19
May 23.31 11.83
June 24.19 17.35
July 24.35 20.52
August 24.23 18.54
September 23.66 14.70
October 22.09 6.26
November 21.74 1.12
December 21.70 -5.0
     
Annual Sum or Average 22.74 7.16
Minimum of Months 21.70 -5.0
Maximum of Months 24.35 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -4.7
February 21.92 -3.7
March 22.27 2.15
April 22.88 6.19
May 23.57 11.83
June 24.26 17.35
July 24.38 20.52
August 24.32 18.54
September 24.01 14.70
October 22.80 6.26
November 22.09 1.12
December 21.82 -5.0
     
Annual Sum or Average 23.02 7.16
Minimum of Months 21.81 -5.0
Maximum of Months 24.38 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -4.7
February 21.92 -3.7
March 22.27 2.15
April 22.88 6.19
May 23.57 11.83
June 24.26 17.35
July 24.38 20.52
August 24.32 18.54
September 24.01 14.70
October 22.80 6.26
November 22.09 1.12
December 21.82 -5.0
     
Annual Sum or Average 23.02 7.16
Minimum of Months 21.81 -5.0
Maximum of Months 24.38 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 -4.7
February 21.03 -3.7
March 21.91 2.15
April 23.06 6.19
May 24.55 11.83
June 25.99 17.35
July 26.48 20.52
August 26.10 18.54
September 25.17 14.70
October 22.73 6.26
November 21.43 1.12
December 20.58 -5.0
     
Annual Sum or Average 23.32 7.16
Minimum of Months 20.58 -5.0
Maximum of Months 26.48 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.97 -4.7
February 18.22 -3.7
March 19.49 2.15
April 20.51 6.19
May 21.99 11.83
June 24.59 17.35
July 25.73 20.52
August 25.25 18.54
September 24.23 14.70
October 20.78 6.26
November 19.30 1.12
December 17.92 -5.0
     
Annual Sum or Average 21.35 7.16
Minimum of Months 17.92 -5.0
Maximum of Months 25.73 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:55

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 -4.7
February 23.07 -3.7
March 23.71 2.15
April 24.69 6.19
May 25.85 11.83
June 26.62 17.35
July 26.81 20.52
August 26.68 18.54
September 26.39 14.70
October 24.80 6.26
November 23.44 1.12
December 22.73 -5.0
     
Annual Sum or Average 24.81 7.16
Minimum of Months 22.73 -5.0
Maximum of Months 26.81 20.52



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:55

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.120325E+12 74694.157 22-JAN-18:15 4979.953 26630.920 8148.477 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32381.806 0.000 0.000 0.000
February 0.108938E+12 73704.475 28-FEB-18:30 4979.953 26630.920 8148.477 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 31392.124 0.000 0.000 0.000
March 0.120289E+12 72524.561 01-MAR-18:45 4979.953 26630.920 8148.477 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30212.210 0.000 0.000 0.000
April 0.115867E+12 72944.610 08-APR-17:00 4979.953 26630.920 8148.477 0.000 5040.029 0.000 0.000 0.000 0.000 0.000 0.000 28145.230 0.000 0.000 0.000
May 0.121210E+12 77201.995 26-MAY-17:45 4979.953 26630.920 8148.477 0.000 13492.489 0.000 0.000 0.000 0.000 0.000 0.000 23950.155 0.000 0.000 0.000
June 0.123936E+12 80369.945 30-JUN-17:15 4979.953 26630.920 8148.477 0.000 19409.899 0.000 0.000 0.000 0.000 0.000 0.000 21200.695 0.000 0.000 0.000
July 0.133089E+12 82841.806 19-JUL-17:15 4979.953 26630.920 8148.477 0.000 18090.855 0.000 0.000 0.000 0.000 0.000 0.000 24991.600 0.000 0.000 0.000
August 0.128928E+12 82774.096 10-AUG-17:15 4979.953 26630.920 8148.477 0.000 19100.997 0.000 0.000 0.000 0.000 0.000 0.000 23913.748 0.000 0.000 0.000
September 0.119615E+12 79435.571 15-SEP-17:00 4979.953 26630.920 8148.477 0.000 15937.966 0.000 0.000 0.000 0.000 0.000 0.000 23738.254 0.000 0.000 0.000
October 0.116493E+12 70938.125 09-OCT-17:30 4979.953 26630.920 8148.477 0.000 3981.151 0.000 0.000 0.000 0.000 0.000 0.000 27197.623 0.000 0.000 0.000
November 0.113273E+12 70781.435 10-NOV-18:45 4979.953 26630.920 8148.477 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 28469.084 0.000 0.000 0.000
December 0.118930E+12 70374.171 03-DEC-18:45 4979.953 26630.920 8148.477 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 28061.820 0.000 0.000 0.000
                                     
Annual Sum or Average 0.144089E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.108938E+12 70374.171   4979.953 26630.920 8148.477 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 21200.695 0.000 0.000 0.000
Maximum of Months 0.133089E+12 82841.806   4979.953 26630.920 8148.477 0.000 19409.899 2553.000 0.000 0.000 0.000 0.000 0.000 32381.806 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:55

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.980085E+11 99540.547 15-JAN-05:00 99540.547 0.000 0.000 0.000 0.000 0.000 99540.547
February 0.733409E+11 93128.989 23-FEB-07:30 93128.989 0.000 0.000 0.000 0.000 0.000 93128.989
March 0.459315E+11 59388.776 11-MAR-08:00 59388.776 0.000 0.000 0.000 0.000 0.000 59388.776
April 0.224466E+11 79985.126 13-APR-06:15 79985.126 0.000 0.000 0.000 0.000 0.000 79985.126
May 0.451256E+10 17472.001 10-MAY-02:15 17472.001 0.000 0.000 0.000 0.000 0.000 17472.001
June 5062108.382 1226.960 23-JUN-04:30 1226.960 0.000 0.000 0.000 0.000 0.000 1226.960
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 891980.501 112.204 18-AUG-03:00 112.204 0.000 0.000 0.000 0.000 0.000 112.204
September 0.445743E+09 4443.430 28-SEP-05:00 4443.430 0.000 0.000 0.000 0.000 0.000 4443.430
October 0.156876E+11 34643.666 05-OCT-02:00 34643.666 0.000 0.000 0.000 0.000 0.000 34643.666
November 0.530489E+11 65406.307 30-NOV-21:15 65406.307 0.000 0.000 0.000 0.000 0.000 65406.307
December 0.105149E+12 104817.133 25-DEC-08:00 104817.133 0.000 0.000 0.000 0.000 0.000 104817.133
                     
Annual Sum or Average 0.418577E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.105149E+12 104817.133   104817.133 0.000 0.000 0.000 0.000 0.000 104817.133