Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: RIYADH - SAU IWEC Data WMO#=404380
Simulation Timestamp: 2015-09-09 18:48:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1724.77 | 550.24 | 610.76 |
Net Site Energy | 1724.77 | 550.24 | 610.76 |
Total Source Energy | 5451.55 | 1739.14 | 1930.45 |
Net Source Energy | 5451.55 | 1739.14 | 1930.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 349.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 281.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1719.58 | 5.19 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 412.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 349.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 281.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 369.45 | 1.84 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 608.92 | 1.84 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 332.84 | 1.66 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 548.58 | 1.66 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1719.58 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1719.58 | 100.00 |
Total On-Site and Utility Electric Sources | 1719.58 | 100.00 |
Total Electricity End Uses | 1719.58 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.50 |
Time Setpoint Not Met During Occupied Cooling | 85.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 99.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | RIYADH - SAU IWEC Data WMO#=404380 |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
Latitude [deg] | 24.70 |
Longitude [deg] | 46.80 |
Elevation [m] | 612.00 |
Time Zone | 3.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUL-17:15 | 09-JAN-04:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 22560.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37953.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11093.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 16912.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 97570.67 | 22560.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 22560.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37953.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 11093.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 16912.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5.63 | 0.00 | 0.00 | 0.00 |
Cooling | 1304.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1107.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 891.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5445.92 | 5.63 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.99 | 0.00 | 0.00 | 0.00 |
Cooling | 462.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 392.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 315.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1928.46 | 1.99 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.99 | 0.00 | 0.00 | 0.00 |
Cooling | 462.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 392.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 315.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1928.46 | 1.99 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00 | 5.90 | Wetbulb [C] | 1.60 | 320.00 |
RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 13.50 | 18.70 | Wetbulb [C] | 4.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_1.22_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 5.778 | 0.306 | 0.155 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 5.778 | 0.306 | 0.155 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 112.97 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 193.95 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.78 | 83.78 | 40.15 | |
Exterior Lighting Total | 2553.00 | 40.15 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5259.89 | 4059.53 | 1200.37 | 0.77 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5233.09 | 4073.34 | 1159.75 | 0.78 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9745.98 | 7783.68 | 1962.30 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4375.08 | 3398.33 | 976.75 | 0.78 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3141.83 | 2440.97 | 700.86 | 0.78 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3128.53 | 2430.42 | 698.12 | 0.78 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3183.99 | 2413.92 | 770.08 | 0.76 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3244.39 | 2448.89 | 795.50 | 0.75 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12365.62 | 9614.77 | 2750.84 | 0.78 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12353.48 | 9677.24 | 2676.24 | 0.78 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10964.42 | 8463.45 | 2500.97 | 0.77 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10666.24 | 8327.07 | 2339.17 | 0.78 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7616.03 | 5944.70 | 1671.33 | 0.78 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7594.97 | 5928.02 | 1666.95 | 0.78 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7649.61 | 5853.90 | 1795.71 | 0.77 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7679.73 | 5863.62 | 1816.11 | 0.76 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8281.58 | 6460.41 | 1821.16 | 0.78 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8281.09 | 6472.75 | 1808.34 | 0.78 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7482.21 | 5812.53 | 1669.68 | 0.78 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7408.17 | 5754.89 | 1653.28 | 0.78 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5705.92 | 4400.57 | 1305.36 | 0.77 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5694.04 | 4391.29 | 1302.75 | 0.77 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5781.79 | 4450.08 | 1331.71 | 0.77 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5779.09 | 4447.96 | 1331.12 | 0.77 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5028.8 | 3.17 | 10.83 | 11.26 | 10.61 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4998.8 | 3.16 | 10.79 | 11.22 | 10.55 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9284.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4180.1 | 3.17 | 10.80 | 11.23 | 10.56 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3001.8 | 3.17 | 10.80 | 11.23 | 10.56 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2989.1 | 3.17 | 10.80 | 11.23 | 10.56 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3049.6 | 3.20 | 10.91 | 11.35 | 10.73 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3108.9 | 3.20 | 10.93 | 11.37 | 10.76 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11813.4 | 3.16 | 10.80 | 11.22 | 10.56 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11792.6 | 3.15 | 10.76 | 11.19 | 10.51 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10482.6 | 3.17 | 10.83 | 11.26 | 10.61 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10185.6 | 3.16 | 10.78 | 11.20 | 10.53 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7273.0 | 3.16 | 10.78 | 11.20 | 10.53 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7252.9 | 3.16 | 10.78 | 11.20 | 10.53 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7319.9 | 3.19 | 10.87 | 11.30 | 10.67 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7350.4 | 3.19 | 10.88 | 11.32 | 10.68 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7909.0 | 3.16 | 10.78 | 11.21 | 10.54 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7907.0 | 3.16 | 10.77 | 11.20 | 10.52 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7148.7 | 3.17 | 10.80 | 11.23 | 10.56 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7078.0 | 3.17 | 10.80 | 11.23 | 10.56 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5455.7 | 3.18 | 10.83 | 11.27 | 10.61 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5444.3 | 3.18 | 10.83 | 11.27 | 10.61 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5529.4 | 3.18 | 10.84 | 11.28 | 10.63 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5526.8 | 3.18 | 10.84 | 11.28 | 10.63 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1449.18 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1439.46 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 2806.95 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1433.26 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1287.47 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1287.47 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1287.47 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1287.47 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 2929.10 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 2955.86 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 2911.82 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 2938.65 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 2574.94 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 2574.94 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 2574.94 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 2574.94 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2152.60 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2166.89 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2143.56 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2157.86 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 1593.88 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 1593.62 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 1577.52 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 1577.26 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 341.90 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 346.74 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.59 | 683.45 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 288.53 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 207.30 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 206.38 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 198.68 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 200.38 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.70 | 817.35 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.55 | 622.50 | 0.72 | 815.44 | 1140.11 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.61 | 712.94 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.61 | 711.44 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 507.78 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 506.33 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 487.70 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 487.08 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 551.44 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 553.83 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 493.58 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 488.67 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 370.28 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 369.49 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 373.49 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 373.31 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2914.05 | 3496.86 | 0.245 | 0.295 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
G NW APARTMENT | 2955.28 | 3546.34 | 0.249 | 0.299 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
OFFICE | 5688.65 | 6826.37 | 0.491 | 0.589 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 36.78 | 0.00412 |
G NE APARTMENT | 2459.11 | 2950.94 | 0.207 | 0.249 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
G N1 APARTMENT | 1766.77 | 2120.13 | 0.149 | 0.179 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 41.64 | 0.00412 |
G N2 APARTMENT | 1758.94 | 2110.72 | 0.148 | 0.178 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 41.64 | 0.00412 |
G S1 APARTMENT | 1693.28 | 2031.94 | 0.143 | 0.171 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
G S2 APARTMENT | 1707.82 | 2049.38 | 0.144 | 0.173 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
M SW APARTMENT | 6966.50 | 8359.81 | 0.587 | 0.704 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
M NW APARTMENT | 7076.56 | 8491.87 | 0.596 | 0.715 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
M SE APARTMENT | 6076.57 | 7291.88 | 0.512 | 0.614 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
M NE APARTMENT | 6063.78 | 7276.54 | 0.511 | 0.613 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
M N1 APARTMENT | 4327.76 | 5193.32 | 0.365 | 0.437 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 41.97 | 0.00412 |
M N2 APARTMENT | 4315.40 | 5178.48 | 0.363 | 0.436 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 41.97 | 0.00412 |
M S1 APARTMENT | 4156.66 | 4988.00 | 0.350 | 0.420 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
M S2 APARTMENT | 4151.36 | 4981.64 | 0.350 | 0.420 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
T SW APARTMENT | 4700.20 | 5640.24 | 0.396 | 0.475 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
T NW APARTMENT | 4720.60 | 5664.72 | 0.398 | 0.477 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
T SE APARTMENT | 4207.02 | 5048.42 | 0.354 | 0.425 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 44.20 | 0.00412 |
T NE APARTMENT | 4165.18 | 4998.22 | 0.351 | 0.421 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
T N1 APARTMENT | 3155.98 | 3787.17 | 0.266 | 0.319 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
T N2 APARTMENT | 3149.22 | 3779.07 | 0.265 | 0.318 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
T S1 APARTMENT | 3183.32 | 3819.98 | 0.268 | 0.322 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
T S2 APARTMENT | 3181.77 | 3818.12 | 0.268 | 0.322 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 821.21 | 985.45 | 0.025 | 0.031 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
G NW APARTMENT | 827.20 | 992.64 | 0.026 | 0.031 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
OFFICE | 1853.11 | 2223.73 | 0.055 | 0.066 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 5.90 | 0.00619 |
G NE APARTMENT | 821.96 | 986.35 | 0.025 | 0.031 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
G N1 APARTMENT | 436.83 | 524.19 | 0.014 | 0.026 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
G N2 APARTMENT | 436.70 | 524.04 | 0.014 | 0.026 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
G S1 APARTMENT | 431.61 | 517.94 | 0.013 | 0.026 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
G S2 APARTMENT | 494.76 | 593.71 | 0.015 | 0.026 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M SW APARTMENT | 1696.85 | 2036.22 | 0.053 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M NW APARTMENT | 1719.47 | 2063.37 | 0.053 | 0.064 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M SE APARTMENT | 1682.24 | 2018.68 | 0.052 | 0.062 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M NE APARTMENT | 1704.92 | 2045.90 | 0.053 | 0.063 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M N1 APARTMENT | 745.70 | 894.83 | 0.023 | 0.052 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M N2 APARTMENT | 745.31 | 894.37 | 0.023 | 0.052 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M S1 APARTMENT | 722.32 | 866.79 | 0.022 | 0.052 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
M S2 APARTMENT | 721.93 | 866.32 | 0.022 | 0.052 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T SW APARTMENT | 1430.27 | 1716.33 | 0.044 | 0.053 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T NW APARTMENT | 1442.36 | 1730.83 | 0.045 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T SE APARTMENT | 1422.63 | 1707.16 | 0.044 | 0.053 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T NE APARTMENT | 1434.73 | 1721.67 | 0.044 | 0.053 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T N1 APARTMENT | 957.79 | 1149.35 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T N2 APARTMENT | 957.57 | 1149.08 | 0.030 | 0.036 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T S1 APARTMENT | 943.95 | 1132.74 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
T S2 APARTMENT | 943.73 | 1132.48 | 0.029 | 0.035 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 5.90 | 0.00619 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.29 | 0.29 | 0.03 | 0.03 |
SPLIT GNW | 0.30 | 0.30 | 0.03 | 0.03 |
SPLIT OFFICE | 0.59 | 0.59 | 0.07 | 0.07 |
SPLIT GNE | 0.25 | 0.25 | 0.03 | 0.03 |
SPLIT GN1 | 0.18 | 0.18 | 0.03 | 0.03 |
SPLIT GN2 | 0.18 | 0.18 | 0.03 | 0.03 |
SPLIT GS1 | 0.17 | 0.17 | 0.03 | 0.03 |
SPLIT GS2 | 0.17 | 0.17 | 0.03 | 0.03 |
SPLIT MSW | 0.70 | 0.70 | 0.06 | 0.06 |
SPLIT MNW | 0.72 | 0.72 | 0.06 | 0.06 |
SPLIT MSE | 0.61 | 0.61 | 0.06 | 0.06 |
SPLIT MNE | 0.61 | 0.61 | 0.06 | 0.06 |
SPLIT MN1 | 0.44 | 0.44 | 0.05 | 0.05 |
SPLIT MN2 | 0.44 | 0.44 | 0.05 | 0.05 |
SPLIT MS1 | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT MS2 | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT TSW | 0.48 | 0.48 | 0.05 | 0.05 |
SPLIT TNW | 0.48 | 0.48 | 0.05 | 0.05 |
SPLIT TSE | 0.43 | 0.43 | 0.05 | 0.05 |
SPLIT TNE | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT TN1 | 0.32 | 0.32 | 0.04 | 0.04 |
SPLIT TN2 | 0.32 | 0.32 | 0.04 | 0.04 |
SPLIT TS1 | 0.32 | 0.32 | 0.04 | 0.04 |
SPLIT TS2 | 0.32 | 0.32 | 0.04 | 0.04 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1679.50 | 3450.00 | 37.75 |
G NW APARTMENT | 1393.25 | 4237.50 | 52.50 |
OFFICE | 682.75 | 660.50 | 0.00 |
G NE APARTMENT | 1406.50 | 4269.25 | 55.25 |
G N1 APARTMENT | 588.00 | 4867.75 | 60.75 |
G N2 APARTMENT | 586.50 | 4865.00 | 61.00 |
G S1 APARTMENT | 856.00 | 3982.75 | 50.00 |
G S2 APARTMENT | 959.75 | 3791.25 | 47.75 |
M SW APARTMENT | 2777.50 | 1028.00 | 2.00 |
M NW APARTMENT | 2145.25 | 2060.25 | 9.50 |
M SE APARTMENT | 2792.50 | 1062.75 | 5.00 |
M NE APARTMENT | 2136.50 | 2085.50 | 12.75 |
M N1 APARTMENT | 1162.75 | 1946.00 | 10.75 |
M N2 APARTMENT | 1162.50 | 1953.25 | 11.75 |
M S1 APARTMENT | 1807.00 | 591.25 | 2.75 |
M S2 APARTMENT | 1805.00 | 596.75 | 2.75 |
T SW APARTMENT | 3933.25 | 2016.00 | 9.75 |
T NW APARTMENT | 3409.00 | 2592.75 | 42.50 |
T SE APARTMENT | 3996.50 | 1997.50 | 12.25 |
T NE APARTMENT | 3442.75 | 2606.50 | 45.00 |
T N1 APARTMENT | 2745.75 | 2609.00 | 15.75 |
T N2 APARTMENT | 2747.50 | 2611.50 | 15.75 |
T S1 APARTMENT | 3423.50 | 1862.25 | 10.00 |
T S2 APARTMENT | 3424.25 | 1862.00 | 10.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4466.25 | 4888.50 | 99.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
G NW APARTMENT | 0.00 | 14.00 | 0.00 | 14.00 |
OFFICE | 0.00 | 36.00 | 0.00 | 0.00 |
G NE APARTMENT | 0.00 | 16.00 | 0.00 | 16.00 |
G N1 APARTMENT | 0.75 | 30.00 | 0.75 | 30.00 |
G N2 APARTMENT | 1.00 | 30.25 | 1.00 | 30.25 |
G S1 APARTMENT | 0.00 | 28.00 | 0.00 | 28.00 |
G S2 APARTMENT | 0.00 | 30.50 | 0.00 | 30.50 |
M SW APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
M NW APARTMENT | 0.00 | 7.50 | 0.00 | 7.50 |
M SE APARTMENT | 0.00 | 10.75 | 0.00 | 10.75 |
M NE APARTMENT | 0.00 | 14.25 | 0.00 | 14.25 |
M N1 APARTMENT | 0.00 | 22.00 | 0.00 | 22.00 |
M N2 APARTMENT | 0.00 | 22.25 | 0.00 | 22.25 |
M S1 APARTMENT | 0.00 | 23.75 | 0.00 | 23.75 |
M S2 APARTMENT | 0.00 | 21.25 | 0.00 | 21.25 |
T SW APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
T NW APARTMENT | 0.00 | 11.75 | 0.00 | 11.75 |
T SE APARTMENT | 0.00 | 8.75 | 0.00 | 8.75 |
T NE APARTMENT | 0.00 | 6.25 | 0.00 | 6.25 |
T N1 APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T N2 APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T S1 APARTMENT | 0.00 | 2.00 | 0.00 | 2.00 |
T S2 APARTMENT | 0.00 | 1.75 | 0.00 | 1.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.50 | 121.25 | 1.50 | 85.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.369 | 0.129 | 0.000 | 0.065 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.129 | 0.000 | 0.062 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.522 | 0.155 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.129 | 0.000 | 0.062 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.078 | 0.000 | 0.061 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.078 | 0.000 | 0.061 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.078 | 0.000 | 0.065 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.078 | 0.000 | 0.065 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.186 | 0.000 | 0.076 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.186 | 0.000 | 0.074 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.186 | 0.000 | 0.076 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.186 | 0.000 | 0.074 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.112 | 0.000 | 0.074 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.112 | 0.000 | 0.074 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.112 | 0.000 | 0.076 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.112 | 0.000 | 0.076 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.246 | 0.000 | 0.088 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.246 | 0.000 | 0.085 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.246 | 0.000 | 0.088 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.246 | 0.000 | 0.085 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.148 | 0.000 | 0.085 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.148 | 0.000 | 0.085 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.148 | 0.000 | 0.088 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.148 | 0.000 | 0.088 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.507 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.383 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.379 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.382 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.379 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.380 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.380 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.386 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.386 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 281.43 | 0.00 | 01-JAN-00:15 | 30504.07 | 01-JAN-08:15 |
WaterSystems:Electricity | 281.43 | 0.00 | 01-JAN-00:15 | 30504.07 | 01-JAN-08:15 |
Water Heater:WaterSystems:Electricity | 281.43 | 0.00 | 01-JAN-00:15 | 30504.07 | 01-JAN-08:15 |
Fans:Electricity | 349.85 | 11093.54 | 01-JAN-00:15 | 11093.54 | 01-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
ElectricityPurchased:Plant | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
Cogeneration:ElectricityPurchased | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
ElectricityNet:Plant | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
Cogeneration:ElectricityNet | 1719.58 | 24206.16 | 01-JAN-03:15 | 97570.67 | 30-JUL-17:15 |
ExteriorLights:Electricity | 40.15 | 0.00 | 01-JAN-06:45 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.15 | 0.00 | 01-JAN-06:45 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 761.89 | 11093.54 | 01-JAN-00:15 | 51754.45 | 30-JUL-14:15 |
General:Fans:Electricity | 349.85 | 11093.54 | 01-JAN-00:15 | 11093.54 | 01-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 412.04 | 0.00 | 01-JAN-00:15 | 40660.91 | 30-JUL-14:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 5.19 | 0.00 | 01-JAN-10:45 | 22560.99 | 09-JAN-05:00 |
Gas:HVAC | 5.19 | 0.00 | 01-JAN-10:45 | 22560.99 | 09-JAN-05:00 |
Heating:Gas | 5.19 | 0.00 | 01-JAN-10:45 | 22560.99 | 09-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2550.85 | 2441.96 | 25-DEC-15:00 | 237960.55 | 29-JUN-19:00 |
EnergyTransfer:Building | 1087.62 | 2062.69 | 24-MAR-06:00 | 106971.38 | 29-JUN-19:00 |
EnergyTransfer:Zone:G SW APARTMENT | 27.56 | 0.02 | 19-MAR-04:45 | 3375.63 | 29-JUN-19:00 |
Heating:EnergyTransfer | 24.10 | 0.00 | 20-FEB-13:15 | 17323.49 | 09-JAN-05:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 843.72 | 09-JAN-05:00 |
Cooling:EnergyTransfer | 1063.52 | 0.00 | 13-JAN-10:00 | 106971.38 | 29-JUN-19:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 26.82 | 0.00 | 01-JAN-03:15 | 3375.63 | 29-JUN-19:00 |
EnergyTransfer:Zone:G NW APARTMENT | 24.19 | 0.05 | 26-JAN-14:15 | 3462.57 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.61 | 0.00 | 17-JAN-04:15 | 894.68 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 22.57 | 0.00 | 01-JAN-00:15 | 3462.57 | 29-JUN-19:00 |
EnergyTransfer:Zone:OFFICE | 42.47 | 0.01 | 12-NOV-15:00 | 5788.59 | 24-AUG-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 7.53 | 0.00 | 01-JAN-02:30 | 1021.22 | 18-MAY-17:30 |
Cooling:EnergyTransfer:Zone:OFFICE | 34.93 | 0.00 | 01-JAN-00:15 | 5788.59 | 24-AUG-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 23.56 | 0.07 | 08-DEC-24:00 | 2971.60 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.23 | 0.00 | 01-JAN-07:30 | 904.69 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 22.33 | 0.00 | 01-JAN-00:15 | 2971.60 | 13-JUN-20:00 |
EnergyTransfer:Zone:G N1 APARTMENT | 15.78 | 0.02 | 27-DEC-04:00 | 2055.08 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.54 | 0.00 | 01-JAN-09:00 | 426.41 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 15.24 | 0.00 | 01-JAN-00:15 | 2055.08 | 13-JUN-20:00 |
EnergyTransfer:Zone:G N2 APARTMENT | 15.78 | 0.02 | 26-FEB-11:30 | 2046.22 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.54 | 0.00 | 01-JAN-00:30 | 428.00 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 15.24 | 0.00 | 01-JAN-00:15 | 2046.22 | 13-JUN-20:00 |
EnergyTransfer:Zone:G S1 APARTMENT | 19.68 | 0.04 | 05-JAN-20:00 | 2077.64 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 365.15 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 19.57 | 0.00 | 04-JAN-15:45 | 2077.64 | 13-JUN-20:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 20.84 | 0.00 | 16-MAR-14:45 | 2152.43 | 22-SEP-13:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.10 | 0.00 | 01-JAN-00:15 | 363.09 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 20.74 | 0.00 | 04-JAN-15:45 | 2152.43 | 22-SEP-13:00 |
EnergyTransfer:Zone:M SW APARTMENT | 87.54 | 0.01 | 05-MAR-07:00 | 8434.45 | 13-JUN-19:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.22 | 0.00 | 01-JAN-00:30 | 663.94 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 87.33 | 0.00 | 01-JAN-00:15 | 8434.45 | 13-JUN-19:15 |
EnergyTransfer:Zone:M NW APARTMENT | 72.93 | 0.02 | 21-JAN-00:45 | 8505.18 | 13-JUN-19:45 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.95 | 0.00 | 01-JAN-00:45 | 965.42 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 71.98 | 0.00 | 01-JAN-00:15 | 8505.18 | 13-JUN-19:45 |
EnergyTransfer:Zone:M SE APARTMENT | 87.16 | 0.01 | 23-DEC-05:45 | 7652.83 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.13 | 0.00 | 01-JAN-00:15 | 744.65 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 87.03 | 0.00 | 04-JAN-23:30 | 7652.83 | 13-JUN-20:00 |
EnergyTransfer:Zone:M NE APARTMENT | 72.26 | 0.02 | 27-DEC-23:00 | 7453.11 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.66 | 0.00 | 01-JAN-00:30 | 1033.60 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 71.60 | 0.00 | 01-JAN-00:15 | 7453.11 | 13-JUN-20:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 54.25 | 0.05 | 14-FEB-18:00 | 5151.60 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 260.33 | 12-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 54.14 | 0.00 | 01-JAN-14:30 | 5151.60 | 13-JUN-20:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 54.24 | 0.13 | 28-DEC-16:00 | 5137.93 | 13-JUN-20:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.11 | 0.00 | 01-JAN-00:15 | 260.25 | 12-JAN-16:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 54.14 | 0.00 | 01-JAN-14:30 | 5137.93 | 13-JUN-20:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 70.60 | 0.43 | 16-MAR-14:15 | 5348.93 | 09-OCT-12:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 160.54 | 10-APR-05:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 70.59 | 0.00 | 12-JAN-10:45 | 5348.93 | 09-OCT-12:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 70.59 | 0.48 | 16-MAR-14:15 | 5371.14 | 09-OCT-12:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 159.40 | 10-APR-05:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 70.59 | 0.00 | 12-JAN-10:45 | 5371.14 | 09-OCT-12:45 |
EnergyTransfer:Zone:T SW APARTMENT | 49.54 | 0.09 | 25-NOV-23:30 | 5666.79 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.49 | 0.00 | 01-JAN-09:00 | 1508.49 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 48.05 | 0.00 | 01-JAN-00:15 | 5666.79 | 29-JUN-19:00 |
EnergyTransfer:Zone:T NW APARTMENT | 43.63 | 0.09 | 22-MAR-22:30 | 5696.64 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.35 | 0.00 | 01-JAN-14:45 | 1538.11 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 41.28 | 0.00 | 01-JAN-00:15 | 5696.64 | 29-JUN-19:00 |
EnergyTransfer:Zone:T SE APARTMENT | 49.04 | 0.02 | 14-APR-04:30 | 5156.80 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.29 | 0.00 | 01-JAN-07:30 | 1516.90 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 47.75 | 0.00 | 01-JAN-00:15 | 5156.80 | 29-JUN-19:00 |
EnergyTransfer:Zone:T NE APARTMENT | 42.90 | 0.20 | 22-JAN-17:00 | 5137.57 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.03 | 0.00 | 01-JAN-09:00 | 1545.56 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 40.87 | 0.00 | 01-JAN-00:15 | 5137.57 | 29-JUN-19:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 32.44 | 0.03 | 28-JAN-06:45 | 3834.86 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.85 | 0.00 | 01-JAN-00:45 | 872.63 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 31.59 | 0.00 | 01-JAN-00:15 | 3834.86 | 29-JUN-19:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 32.44 | 0.01 | 19-FEB-07:00 | 3826.00 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.85 | 0.00 | 01-JAN-00:45 | 874.19 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 31.59 | 0.00 | 01-JAN-00:15 | 3826.00 | 29-JUN-19:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 39.10 | 0.00 | 05-JAN-04:00 | 3849.01 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.33 | 0.00 | 01-JAN-00:30 | 827.27 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 38.77 | 0.00 | 01-JAN-00:15 | 3849.01 | 29-JUN-19:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 39.11 | 0.00 | 05-JAN-04:45 | 3839.43 | 29-JUN-19:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.33 | 0.00 | 01-JAN-00:30 | 828.97 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 38.78 | 0.00 | 01-JAN-00:15 | 3839.43 | 29-JUN-19:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1463.23 | 0.00 | 09-JAN-17:15 | 130989.17 | 29-JUN-19:00 |
HeatingCoils:EnergyTransfer | 4.15 | 0.00 | 01-JAN-10:45 | 18048.80 | 09-JAN-05:00 |
CoolingCoils:EnergyTransfer | 1459.07 | 0.00 | 01-JAN-00:15 | 130989.17 | 29-JUN-19:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.736 | -26.824 | 0.000 | 0.000 | 3.594 | 1.087 | 12.213 | 21.752 | 0.000 | 2.088 | 0.000 | 0.000 | -3.751 | 0.000 | -1.557 | -9.337 |
G NW APARTMENT | 1.612 | -22.575 | 0.000 | 0.000 | 3.622 | 1.087 | 12.213 | 15.306 | 0.000 | 2.086 | 0.000 | 0.000 | -3.764 | 0.000 | -1.399 | -8.188 |
OFFICE | 7.535 | -34.933 | 0.000 | 0.000 | 0.517 | 26.452 | 9.482 | 20.078 | 0.000 | 1.509 | 0.001 | 0.000 | -4.376 | 0.000 | -1.033 | -25.230 |
G NE APARTMENT | 1.228 | -22.329 | 0.000 | 0.000 | 3.633 | 1.087 | 12.213 | 14.907 | 0.000 | 2.086 | 0.000 | 0.000 | -3.509 | 0.000 | -1.372 | -7.944 |
G N1 APARTMENT | 0.542 | -15.241 | 0.000 | 0.000 | 3.635 | 1.087 | 12.213 | 6.938 | 0.000 | 1.270 | 0.000 | 0.000 | -2.258 | 0.000 | -1.015 | -7.170 |
G N2 APARTMENT | 0.539 | -15.240 | 0.000 | 0.000 | 3.636 | 1.087 | 12.213 | 6.938 | 0.000 | 1.270 | 0.000 | 0.000 | -2.256 | 0.000 | -1.014 | -7.171 |
G S1 APARTMENT | 0.115 | -19.568 | 0.000 | 0.000 | 3.595 | 1.087 | 12.213 | 13.460 | 0.000 | 1.271 | 0.000 | 0.000 | -2.249 | 0.000 | -1.208 | -8.714 |
G S2 APARTMENT | 0.103 | -20.736 | 0.000 | 0.000 | 3.592 | 1.087 | 12.213 | 13.427 | 0.000 | 1.271 | 0.000 | 0.000 | -2.264 | 0.000 | -1.214 | -7.478 |
M SW APARTMENT | 0.216 | -87.325 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 21.144 | 0.000 | 2.987 | 52.680 | 0.000 | -4.381 | 0.000 | -2.150 | 0.000 |
M NW APARTMENT | 0.947 | -71.984 | 0.000 | 0.000 | 3.551 | 1.087 | 12.213 | 14.777 | 0.000 | 2.985 | 42.971 | 0.000 | -4.473 | 0.000 | -2.073 | -0.001 |
M SE APARTMENT | 0.128 | -87.028 | 0.000 | 0.000 | 3.533 | 1.087 | 12.213 | 20.863 | 0.000 | 2.987 | 52.623 | 0.000 | -4.260 | 0.000 | -2.145 | 0.000 |
M NE APARTMENT | 0.659 | -71.597 | 0.000 | 0.000 | 3.557 | 1.087 | 12.213 | 14.337 | 0.000 | 2.984 | 42.999 | 0.000 | -4.182 | 0.000 | -2.057 | -0.000 |
M N1 APARTMENT | 0.107 | -54.142 | 0.000 | 0.000 | 3.544 | 1.087 | 12.213 | 6.589 | 0.000 | 1.813 | 33.148 | 0.000 | -2.787 | 0.000 | -1.571 | -0.000 |
M N2 APARTMENT | 0.107 | -54.137 | 0.000 | 0.000 | 3.544 | 1.087 | 12.213 | 6.589 | 0.000 | 1.813 | 33.141 | 0.000 | -2.785 | 0.000 | -1.571 | -0.000 |
M S1 APARTMENT | 0.001 | -70.594 | 0.000 | 0.000 | 3.523 | 1.087 | 12.213 | 13.057 | 0.000 | 1.816 | 43.176 | 0.000 | -2.643 | 0.000 | -1.636 | 0.000 |
M S2 APARTMENT | 0.001 | -70.587 | 0.000 | 0.000 | 3.523 | 1.087 | 12.213 | 13.057 | 0.000 | 1.816 | 43.167 | 0.000 | -2.642 | 0.000 | -1.636 | 0.000 |
T SW APARTMENT | 1.491 | -48.048 | 0.000 | 0.000 | 3.565 | 1.087 | 12.213 | 20.616 | 0.000 | 3.931 | 11.833 | 0.000 | -4.075 | 0.000 | -2.612 | -0.000 |
T NW APARTMENT | 2.352 | -41.282 | 0.000 | 0.000 | 3.582 | 1.087 | 12.213 | 14.337 | 0.000 | 3.928 | 10.434 | 0.000 | -4.149 | 0.000 | -2.502 | -0.000 |
T SE APARTMENT | 1.291 | -47.746 | 0.000 | 0.000 | 3.570 | 1.087 | 12.213 | 20.349 | 0.000 | 3.931 | 11.870 | 0.000 | -3.960 | 0.000 | -2.604 | -0.000 |
T NE APARTMENT | 2.027 | -40.871 | 0.000 | 0.000 | 3.589 | 1.087 | 12.213 | 13.946 | 0.000 | 3.928 | 10.478 | 0.000 | -3.905 | 0.000 | -2.492 | -0.001 |
T N1 APARTMENT | 0.849 | -31.587 | 0.000 | 0.000 | 3.580 | 1.087 | 12.213 | 6.416 | 0.000 | 2.385 | 9.470 | 0.000 | -2.560 | 0.000 | -1.852 | -0.001 |
T N2 APARTMENT | 0.850 | -31.591 | 0.000 | 0.000 | 3.580 | 1.087 | 12.213 | 6.415 | 0.000 | 2.385 | 9.471 | 0.000 | -2.558 | 0.000 | -1.853 | -0.001 |
T S1 APARTMENT | 0.329 | -38.770 | 0.000 | 0.000 | 3.557 | 1.087 | 12.213 | 12.767 | 0.000 | 2.389 | 10.870 | 0.000 | -2.482 | 0.000 | -1.959 | -0.000 |
T S2 APARTMENT | 0.332 | -38.777 | 0.000 | 0.000 | 3.557 | 1.087 | 12.213 | 12.766 | 0.000 | 2.389 | 10.873 | 0.000 | -2.480 | 0.000 | -1.959 | -0.000 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.731 | 0.000 | 0.443 | 0.000 | 0.000 | -0.400 | 0.000 | -0.345 | -15.011 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 2.266 | 0.000 | 8.962 | 0.000 | 0.000 | -0.932 | 0.000 | -6.497 | -24.860 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.761 | 0.000 | 0.362 | 0.000 | 0.000 | -0.458 | 0.000 | -0.294 | -14.953 |
Total Facility | 24.098 | -1063.510 | 0.000 | 0.000 | 82.710 | 95.189 | 296.854 | 334.589 | 0.000 | 67.082 | 429.205 | 0.000 | -80.539 | 0.000 | -49.619 | -136.060 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-JUN-19:00 | 0.00 | -3375.31 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 584.10 | 0.00 | 1592.97 | 405.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G NW APARTMENT | 29-JUN-18:53 | 0.00 | -3462.61 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 636.48 | 0.00 | 1591.66 | 441.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE | 25-SEP-06:01 | 0.00 | -8694.24 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 271.57 | 0.00 | 0.00 | 7712.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 13-JUN-20:00 | 0.00 | -2971.53 | 0.00 | 0.00 | 140.63 | 103.77 | 523.87 | 439.33 | 0.00 | 1530.73 | 233.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G N1 APARTMENT | 13-JUN-20:00 | 0.00 | -2055.03 | 0.00 | 0.00 | 140.69 | 103.77 | 523.87 | 256.02 | 0.00 | 923.65 | 107.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G N2 APARTMENT | 13-JUN-20:00 | 0.00 | -2046.17 | 0.00 | 0.00 | 140.59 | 103.77 | 523.87 | 255.91 | 0.00 | 922.71 | 99.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G S1 APARTMENT | 13-JUN-20:00 | 0.00 | -2077.59 | 0.00 | 0.00 | 141.55 | 103.77 | 523.87 | 306.20 | 0.00 | 929.46 | 72.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G S2 APARTMENT | 22-SEP-13:00 | 0.00 | -2152.19 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1736.43 | 0.00 | 120.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146.51 |
M SW APARTMENT | 13-JUN-19:15 | 0.00 | -8434.59 | 0.00 | 0.00 | 141.56 | 103.77 | 523.87 | 518.46 | 0.00 | 2130.03 | 5016.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 13-JUN-19:45 | 0.00 | -8505.06 | 0.00 | 0.00 | 141.50 | 103.77 | 523.87 | 427.03 | 0.00 | 2188.44 | 5120.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 13-JUN-20:00 | 0.00 | -7652.68 | 0.00 | 0.00 | 138.31 | 103.77 | 523.87 | 499.72 | 0.00 | 2149.39 | 4237.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 13-JUN-20:00 | 0.00 | -7452.96 | 0.00 | 0.00 | 136.76 | 103.77 | 523.87 | 437.89 | 0.00 | 2121.02 | 4129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 13-JUN-20:00 | 0.00 | -5151.49 | 0.00 | 0.00 | 137.80 | 103.77 | 523.87 | 252.73 | 0.00 | 1290.87 | 2842.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 13-JUN-20:00 | 0.00 | -5137.81 | 0.00 | 0.00 | 137.71 | 103.77 | 523.87 | 252.57 | 0.00 | 1289.72 | 2830.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 09-OCT-12:45 | 0.00 | -5348.87 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2028.46 | 0.00 | 203.34 | 2674.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 09-OCT-12:45 | 0.00 | -5371.08 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2028.37 | 0.00 | 203.42 | 2697.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 29-JUN-18:53 | 0.00 | -5667.88 | 0.00 | 0.00 | 141.80 | 103.77 | 547.42 | 584.12 | 0.00 | 3015.31 | 1275.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 29-JUN-19:00 | 0.00 | -5696.31 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 642.36 | 0.00 | 2994.19 | 1266.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 29-JUN-19:00 | 0.00 | -5160.42 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 549.64 | 0.00 | 2961.84 | 855.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 29-JUN-19:00 | 0.00 | -5145.36 | 0.00 | 0.00 | 141.41 | 103.77 | 547.42 | 608.17 | 0.00 | 2931.27 | 813.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-JUN-19:00 | 0.00 | -3836.81 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 405.87 | 0.00 | 1800.58 | 837.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUN-19:00 | 0.00 | -3827.94 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 406.16 | 0.00 | 1800.64 | 828.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 29-JUN-18:53 | 0.00 | -3848.61 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 339.96 | 0.00 | 1819.30 | 896.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 29-JUN-18:53 | 0.00 | -3839.03 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 340.22 | 0.00 | 1819.30 | 886.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-19:00 | 0.00 | -107177.22 | 0.00 | 0.00 | 3235.73 | 4190.04 | 13114.08 | 11837.63 | 0.00 | 44415.37 | 30384.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-JAN-05:00 | 843.70 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 72.53 | 0.00 | -1080.29 | 0.00 | -268.74 | 0.00 |
G NW APARTMENT | 09-JAN-05:00 | 894.66 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 12.69 | 0.00 | -1071.42 | 0.00 | -268.74 | 0.00 |
OFFICE | 25-JUL-16:01 | 1232.41 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 1346.09 | 0.00 | 258.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3547.95 |
G NE APARTMENT | 09-JAN-05:00 | 904.68 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 | -1070.37 | 0.00 | -268.74 | 0.00 |
G N1 APARTMENT | 19-JAN-08:02 | 892.81 | 0.00 | 0.00 | 0.00 | 74.58 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -214.61 | 0.00 | -58.02 | -1102.72 |
G N2 APARTMENT | 02-JAN-07:01 | 1055.54 | 0.00 | 0.00 | 0.00 | 162.74 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -309.16 | 0.00 | 0.00 | -1333.88 |
G S1 APARTMENT | 06-DEC-06:23 | 421.49 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.24 | 0.00 | -106.96 | -389.22 |
G S2 APARTMENT | 06-DEC-06:26 | 423.93 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.12 | 0.00 | -106.96 | -391.77 |
M SW APARTMENT | 09-JAN-05:00 | 663.93 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 448.77 | 0.00 | -1158.74 | 0.00 | -386.77 | 0.00 |
M NW APARTMENT | 09-JAN-05:00 | 965.40 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 131.88 | 0.00 | -1143.32 | 0.00 | -386.77 | 0.00 |
M SE APARTMENT | 09-JAN-05:00 | 744.64 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 364.66 | 0.00 | -1155.33 | 0.00 | -386.77 | 0.00 |
M NE APARTMENT | 09-JAN-05:00 | 1033.58 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 60.42 | 0.00 | -1140.04 | 0.00 | -386.77 | 0.00 |
M N1 APARTMENT | 12-JAN-16:00 | 260.34 | 0.00 | 0.00 | 0.00 | 41.53 | 22.70 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4.08 | 0.00 | -171.24 | -549.51 |
M N2 APARTMENT | 12-JAN-16:00 | 260.26 | 0.00 | 0.00 | 0.00 | 41.57 | 22.70 | 400.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.64 | 0.00 | -170.43 | -550.72 |
M S1 APARTMENT | 10-APR-05:15 | 168.25 | 0.00 | 0.00 | 0.00 | 162.99 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 341.48 | 0.00 | -680.13 | 0.00 | -355.85 | 0.00 |
M S2 APARTMENT | 10-APR-05:15 | 167.03 | 0.00 | 0.00 | 0.00 | 162.99 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 342.91 | 0.00 | -680.24 | 0.00 | -355.95 | 0.00 |
T SW APARTMENT | 09-JAN-05:00 | 1508.47 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1051.40 | 0.00 | -513.05 | -376.82 |
T NW APARTMENT | 09-JAN-05:00 | 1538.09 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1044.11 | 0.00 | -513.05 | -413.74 |
T SE APARTMENT | 09-JAN-05:00 | 1516.87 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1050.66 | 0.00 | -513.05 | -385.97 |
T NE APARTMENT | 09-JAN-05:00 | 1545.54 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1043.46 | 0.00 | -513.05 | -421.84 |
T N1 APARTMENT | 09-JAN-05:00 | 872.62 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -646.07 | 0.00 | -309.47 | -349.89 |
T N2 APARTMENT | 09-JAN-05:00 | 874.18 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.98 | 0.00 | -309.47 | -351.54 |
T S1 APARTMENT | 09-JAN-05:00 | 827.26 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -655.28 | 0.00 | -309.47 | -295.32 |
T S2 APARTMENT | 09-JAN-05:00 | 828.96 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -655.18 | 0.00 | -309.47 | -297.11 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-JAN-05:00 | 16059.94 | 0.00 | 0.00 | 0.00 | 4344.64 | 2250.82 | 5427.18 | 0.00 | 0.00 | 0.00 | 1444.39 | 0.00 | -21807.97 | 0.00 | -7719.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Sec1.1A-General InformationData | |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 1.50 |
Number of hours cooling loads not met | 85.25 |
Number of hours not met | 86.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 5.19 | 22560.99 | 0.00 | 0.00 |
Space Cooling | 412.04 | 37953.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 349.85 | 11093.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 281.43 | 16912.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1719.58 | 5.19 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1719.58 |
Natural Gas | 0.00 | 5.19 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1724.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 131.45 |
Fans-Interior | 111.61 |
Service Water Heating | 89.78 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.81 |
Subtotal | 548.58 |
Natural Gas [MJ/m2] | |
Space Heating | 1.66 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 1.66 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.87 |
Space Heating | 0.30 |
Space Cooling | 23.89 |
Fans-Interior | 20.28 |
Service Water Heating | 16.32 |
Receptacle Equipment | 30.01 |
Miscellaneous | 2.33 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.294531 |
G NW APARTMENT DIRECT AIR | 0.298698 |
OFFICE DIRECT AIR | 0.588755 |
G NE APARTMENT DIRECT AIR | 0.248549 |
G N1 APARTMENT DIRECT AIR | 0.178580 |
G N2 APARTMENT DIRECT AIR | 0.177788 |
G S1 APARTMENT DIRECT AIR | 0.171150 |
G S2 APARTMENT DIRECT AIR | 0.172618 |
M SW APARTMENT DIRECT AIR | 0.704106 |
M NW APARTMENT DIRECT AIR | 0.715231 |
M SE APARTMENT DIRECT AIR | 0.614161 |
M NE APARTMENT DIRECT AIR | 0.612869 |
M N1 APARTMENT DIRECT AIR | 0.437429 |
M N2 APARTMENT DIRECT AIR | 0.436180 |
M S1 APARTMENT DIRECT AIR | 0.420131 |
M S2 APARTMENT DIRECT AIR | 0.419595 |
T SW APARTMENT DIRECT AIR | 0.475034 |
T NW APARTMENT DIRECT AIR | 0.477095 |
T SE APARTMENT DIRECT AIR | 0.425189 |
T NE APARTMENT DIRECT AIR | 0.420961 |
T N1 APARTMENT DIRECT AIR | 0.318980 |
T N2 APARTMENT DIRECT AIR | 0.318298 |
T S1 APARTMENT DIRECT AIR | 0.321743 |
T S2 APARTMENT DIRECT AIR | 0.321587 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.294531 |
SPLIT GNW MAIN BRANCH | 0.298698 |
SPLIT OFFICE MAIN BRANCH | 0.588755 |
SPLIT GNE MAIN BRANCH | 0.248549 |
SPLIT GN1 MAIN BRANCH | 0.178580 |
SPLIT GN2 MAIN BRANCH | 0.177788 |
SPLIT GS1 MAIN BRANCH | 0.171150 |
SPLIT GS2 MAIN BRANCH | 0.172618 |
SPLIT MSW MAIN BRANCH | 0.704106 |
SPLIT MNW MAIN BRANCH | 0.715231 |
SPLIT MSE MAIN BRANCH | 0.614161 |
SPLIT MNE MAIN BRANCH | 0.612869 |
SPLIT MN1 MAIN BRANCH | 0.437429 |
SPLIT MN2 MAIN BRANCH | 0.436180 |
SPLIT MS1 MAIN BRANCH | 0.420131 |
SPLIT MS2 MAIN BRANCH | 0.419595 |
SPLIT TSW MAIN BRANCH | 0.475034 |
SPLIT TNW MAIN BRANCH | 0.477095 |
SPLIT TSE MAIN BRANCH | 0.425189 |
SPLIT TNE MAIN BRANCH | 0.420961 |
SPLIT TN1 MAIN BRANCH | 0.318980 |
SPLIT TN2 MAIN BRANCH | 0.318298 |
SPLIT TS1 MAIN BRANCH | 0.321743 |
SPLIT TS2 MAIN BRANCH | 0.321587 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.294531 |
SPLIT GNW | 0.298698 |
SPLIT OFFICE | 0.588755 |
SPLIT GNE | 0.248549 |
SPLIT GN1 | 0.178580 |
SPLIT GN2 | 0.177788 |
SPLIT GS1 | 0.171150 |
SPLIT GS2 | 0.172618 |
SPLIT MSW | 0.704106 |
SPLIT MNW | 0.715231 |
SPLIT MSE | 0.614161 |
SPLIT MNE | 0.612869 |
SPLIT MN1 | 0.437429 |
SPLIT MN2 | 0.436180 |
SPLIT MS1 | 0.420131 |
SPLIT MS2 | 0.419595 |
SPLIT TSW | 0.475034 |
SPLIT TNW | 0.477095 |
SPLIT TSE | 0.425189 |
SPLIT TNE | 0.420961 |
SPLIT TN1 | 0.318980 |
SPLIT TN2 | 0.318298 |
SPLIT TS1 | 0.321743 |
SPLIT TS2 | 0.321587 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.294531 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.298698 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.588755 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.248549 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.178580 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.177788 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.171150 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.172618 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.704106 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.715231 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.614161 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.612869 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.437429 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.436180 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.420131 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.419595 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.475034 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.477095 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.425189 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.420961 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.318980 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.318298 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.321743 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.321587 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.294531 | 5259.89 | 0.771789 |
SPLIT GNW COOLING COIL | 0.298698 | 5233.09 | 0.778381 |
SPLIT OFFICE COOLING COIL | 0.588755 | 9745.98 | 0.798655 |
SPLIT GNE COOLING COIL | 0.248549 | 4375.08 | 0.776747 |
SPLIT GN1 COOLING COIL | 0.178580 | 3141.83 | 0.776926 |
SPLIT GN2 COOLING COIL | 0.177788 | 3128.53 | 0.776855 |
SPLIT GS1 COOLING COIL | 0.171150 | 3183.99 | 0.758141 |
SPLIT GS2 COOLING COIL | 0.172618 | 3244.39 | 0.754807 |
SPLIT MSW COOLING COIL | 0.704106 | 12365.62 | 0.777541 |
SPLIT MNW COOLING COIL | 0.715231 | 12353.48 | 0.783362 |
SPLIT MSE COOLING COIL | 0.614161 | 10964.42 | 0.771901 |
SPLIT MNE COOLING COIL | 0.612869 | 10666.24 | 0.780694 |
SPLIT MN1 COOLING COIL | 0.437429 | 7616.03 | 0.780552 |
SPLIT MN2 COOLING COIL | 0.436180 | 7594.97 | 0.780519 |
SPLIT MS1 COOLING COIL | 0.420131 | 7649.61 | 0.765254 |
SPLIT MS2 COOLING COIL | 0.419595 | 7679.73 | 0.763519 |
SPLIT TSW COOLING COIL | 0.475034 | 8281.58 | 0.780095 |
SPLIT TNW COOLING COIL | 0.477095 | 8281.09 | 0.781630 |
SPLIT TSE COOLING COIL | 0.425189 | 7482.21 | 0.776847 |
SPLIT TNE COOLING COIL | 0.420961 | 7408.17 | 0.776830 |
SPLIT TN1 COOLING COIL | 0.318980 | 5705.92 | 0.771228 |
SPLIT TN2 COOLING COIL | 0.318298 | 5694.04 | 0.771208 |
SPLIT TS1 COOLING COIL | 0.321743 | 5781.79 | 0.769672 |
SPLIT TS2 COOLING COIL | 0.321587 | 5779.09 | 0.769665 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.294531 | 0.294531 | 0.294531 | 0.294531 | 1449.18 | 5259.89 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.298698 | 0.298698 | 0.298698 | 0.298698 | 1439.46 | 5233.09 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.588755 | 0.588755 | 0.588755 | 0.588755 | 2806.95 | 9745.98 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.248549 | 0.248549 | 0.248549 | 0.248549 | 1433.26 | 4375.08 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.178580 | 0.178580 | 0.178580 | 0.178580 | 1287.47 | 3141.83 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.177788 | 0.177788 | 0.177788 | 0.177788 | 1287.47 | 3128.53 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.171150 | 0.171150 | 0.171150 | 0.171150 | 1287.47 | 3183.99 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.172618 | 0.172618 | 0.172618 | 0.172618 | 1287.47 | 3244.39 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.704106 | 0.704106 | 0.704106 | 0.704106 | 2929.10 | 12365.62 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.715231 | 0.715231 | 0.715231 | 0.715231 | 2955.86 | 12353.48 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.614161 | 0.614161 | 0.614161 | 0.614161 | 2911.82 | 10964.42 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.612869 | 0.612869 | 0.612869 | 0.612869 | 2938.65 | 10666.24 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.437429 | 0.437429 | 0.437429 | 0.437429 | 2574.94 | 7616.03 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.436180 | 0.436180 | 0.436180 | 0.436180 | 2574.94 | 7594.97 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.420131 | 0.420131 | 0.420131 | 0.420131 | 2574.94 | 7649.61 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.419595 | 0.419595 | 0.419595 | 0.419595 | 2574.94 | 7679.73 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.475034 | 0.475034 | 0.475034 | 0.475034 | 2152.60 | 8281.58 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.477095 | 0.477095 | 0.477095 | 0.477095 | 2166.89 | 8281.09 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.425189 | 0.425189 | 0.425189 | 0.425189 | 2143.56 | 7482.21 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.420961 | 0.420961 | 0.420961 | 0.420961 | 2157.86 | 7408.17 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.318980 | 0.318980 | 0.318980 | 0.318980 | 1593.88 | 5705.92 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.318298 | 0.318298 | 0.318298 | 0.318298 | 1593.62 | 5694.04 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.321743 | 0.321743 | 0.321743 | 0.321743 | 1577.52 | 5781.79 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.321587 | 0.321587 | 0.321587 | 0.321587 | 1577.26 | 5779.09 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.294531 |
SPLIT GNW SUPPLY FAN | 0.298698 |
SPLIT OFFICE SUPPLY FAN | 0.588755 |
SPLIT GNE SUPPLY FAN | 0.248549 |
SPLIT GN1 SUPPLY FAN | 0.178580 |
SPLIT GN2 SUPPLY FAN | 0.177788 |
SPLIT GS1 SUPPLY FAN | 0.171150 |
SPLIT GS2 SUPPLY FAN | 0.172618 |
SPLIT MSW SUPPLY FAN | 0.704106 |
SPLIT MNW SUPPLY FAN | 0.715231 |
SPLIT MSE SUPPLY FAN | 0.614161 |
SPLIT MNE SUPPLY FAN | 0.612869 |
SPLIT MN1 SUPPLY FAN | 0.437429 |
SPLIT MN2 SUPPLY FAN | 0.436180 |
SPLIT MS1 SUPPLY FAN | 0.420131 |
SPLIT MS2 SUPPLY FAN | 0.419595 |
SPLIT TSW SUPPLY FAN | 0.475034 |
SPLIT TNW SUPPLY FAN | 0.477095 |
SPLIT TSE SUPPLY FAN | 0.425189 |
SPLIT TNE SUPPLY FAN | 0.420961 |
SPLIT TN1 SUPPLY FAN | 0.318980 |
SPLIT TN2 SUPPLY FAN | 0.318298 |
SPLIT TS1 SUPPLY FAN | 0.321743 |
SPLIT TS2 SUPPLY FAN | 0.321587 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1449.18 |
SPLIT GNW HEATING COIL | 1439.46 |
SPLIT OFFICE HEATING COIL | 2806.95 |
SPLIT GNE HEATING COIL | 1433.26 |
SPLIT GN1 HEATING COIL | 1287.47 |
SPLIT GN2 HEATING COIL | 1287.47 |
SPLIT GS1 HEATING COIL | 1287.47 |
SPLIT GS2 HEATING COIL | 1287.47 |
SPLIT MSW HEATING COIL | 2929.10 |
SPLIT MNW HEATING COIL | 2955.86 |
SPLIT MSE HEATING COIL | 2911.82 |
SPLIT MNE HEATING COIL | 2938.65 |
SPLIT MN1 HEATING COIL | 2574.94 |
SPLIT MN2 HEATING COIL | 2574.94 |
SPLIT MS1 HEATING COIL | 2574.94 |
SPLIT MS2 HEATING COIL | 2574.94 |
SPLIT TSW HEATING COIL | 2152.60 |
SPLIT TNW HEATING COIL | 2166.89 |
SPLIT TSE HEATING COIL | 2143.56 |
SPLIT TNE HEATING COIL | 2157.86 |
SPLIT TN1 HEATING COIL | 1593.88 |
SPLIT TN2 HEATING COIL | 1593.62 |
SPLIT TS1 HEATING COIL | 1577.52 |
SPLIT TS2 HEATING COIL | 1577.26 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 14.02 |
February | 23.64 | 16.67 |
March | 24.06 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.29 | 21.57 |
December | 23.35 | 14.93 |
Annual Sum or Average | 24.11 | 26.21 |
Minimum of Months | 23.28 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.56 | 14.02 |
February | 23.22 | 16.67 |
March | 23.90 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.18 | 21.57 |
December | 22.80 | 14.93 |
Annual Sum or Average | 23.95 | 26.21 |
Minimum of Months | 22.56 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.18 | 14.02 |
February | 24.74 | 16.67 |
March | 25.41 | 20.28 |
April | 26.48 | 25.86 |
May | 27.33 | 32.05 |
June | 27.71 | 35.24 |
July | 27.77 | 36.21 |
August | 27.61 | 36.44 |
September | 27.86 | 33.05 |
October | 27.04 | 27.59 |
November | 26.12 | 21.57 |
December | 24.37 | 14.93 |
Annual Sum or Average | 26.39 | 26.21 |
Minimum of Months | 24.18 | 14.02 |
Maximum of Months | 27.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 14.02 |
February | 23.12 | 16.67 |
March | 23.87 | 20.28 |
April | 24.34 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.15 | 21.57 |
December | 22.66 | 14.93 |
Annual Sum or Average | 23.92 | 26.21 |
Minimum of Months | 22.46 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 14.02 |
February | 22.98 | 16.67 |
March | 23.77 | 20.28 |
April | 24.33 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.11 | 21.57 |
December | 22.63 | 14.93 |
Annual Sum or Average | 23.88 | 26.21 |
Minimum of Months | 22.34 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 14.02 |
February | 22.98 | 16.67 |
March | 23.77 | 20.28 |
April | 24.32 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.38 | 27.59 |
November | 24.11 | 21.57 |
December | 22.62 | 14.93 |
Annual Sum or Average | 23.88 | 26.21 |
Minimum of Months | 22.33 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 14.02 |
February | 23.62 | 16.67 |
March | 24.01 | 20.28 |
April | 24.34 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.41 | 36.44 |
September | 24.40 | 33.05 |
October | 24.39 | 27.59 |
November | 24.27 | 21.57 |
December | 23.38 | 14.93 |
Annual Sum or Average | 24.11 | 26.21 |
Minimum of Months | 23.31 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 14.02 |
February | 23.65 | 16.67 |
March | 24.04 | 20.28 |
April | 24.35 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.41 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.29 | 21.57 |
December | 23.40 | 14.93 |
Annual Sum or Average | 24.12 | 26.21 |
Minimum of Months | 23.33 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.16 | 14.02 |
February | 24.33 | 16.67 |
March | 24.39 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 24.17 | 14.93 |
Annual Sum or Average | 24.35 | 26.21 |
Minimum of Months | 24.16 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.64 | 14.02 |
February | 24.18 | 16.67 |
March | 24.36 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 23.75 | 14.93 |
Annual Sum or Average | 24.26 | 26.21 |
Minimum of Months | 23.64 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.12 | 14.02 |
February | 24.31 | 16.67 |
March | 24.38 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 24.12 | 14.93 |
Annual Sum or Average | 24.34 | 26.21 |
Minimum of Months | 24.12 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 14.02 |
February | 24.15 | 16.67 |
March | 24.36 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 23.64 | 14.93 |
Annual Sum or Average | 24.24 | 26.21 |
Minimum of Months | 23.57 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 14.02 |
February | 24.23 | 16.67 |
March | 24.38 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.41 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 23.88 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.76 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 14.02 |
February | 24.23 | 16.67 |
March | 24.38 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.41 | 35.24 |
July | 24.41 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 23.87 | 14.93 |
Annual Sum or Average | 24.29 | 26.21 |
Minimum of Months | 23.76 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.28 | 14.02 |
February | 24.37 | 16.67 |
March | 24.40 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.41 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 24.29 | 14.93 |
Annual Sum or Average | 24.38 | 26.21 |
Minimum of Months | 24.28 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.28 | 14.02 |
February | 24.37 | 16.67 |
March | 24.40 | 20.28 |
April | 24.40 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.41 | 36.21 |
August | 24.41 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.40 | 21.57 |
December | 24.29 | 14.93 |
Annual Sum or Average | 24.38 | 26.21 |
Minimum of Months | 24.28 | 14.02 |
Maximum of Months | 24.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.62 | 14.02 |
February | 23.97 | 16.67 |
March | 24.26 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.37 | 21.57 |
December | 23.66 | 14.93 |
Annual Sum or Average | 24.22 | 26.21 |
Minimum of Months | 23.62 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 14.02 |
February | 23.77 | 16.67 |
March | 24.20 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.34 | 21.57 |
December | 23.32 | 14.93 |
Annual Sum or Average | 24.13 | 26.21 |
Minimum of Months | 23.18 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.60 | 14.02 |
February | 23.93 | 16.67 |
March | 24.24 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.35 | 21.57 |
December | 23.61 | 14.93 |
Annual Sum or Average | 24.21 | 26.21 |
Minimum of Months | 23.60 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 14.02 |
February | 23.75 | 16.67 |
March | 24.19 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.32 | 21.57 |
December | 23.24 | 14.93 |
Annual Sum or Average | 24.12 | 26.21 |
Minimum of Months | 23.17 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 14.02 |
February | 23.82 | 16.67 |
March | 24.23 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.34 | 21.57 |
December | 23.33 | 14.93 |
Annual Sum or Average | 24.14 | 26.21 |
Minimum of Months | 23.18 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 14.02 |
February | 23.81 | 16.67 |
March | 24.23 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.34 | 21.57 |
December | 23.32 | 14.93 |
Annual Sum or Average | 24.14 | 26.21 |
Minimum of Months | 23.18 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 14.02 |
February | 24.06 | 16.67 |
March | 24.30 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.37 | 21.57 |
December | 23.79 | 14.93 |
Annual Sum or Average | 24.25 | 26.21 |
Minimum of Months | 23.75 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 14.02 |
February | 24.06 | 16.67 |
March | 24.29 | 20.28 |
April | 24.39 | 25.86 |
May | 24.40 | 32.05 |
June | 24.40 | 35.24 |
July | 24.40 | 36.21 |
August | 24.40 | 36.44 |
September | 24.40 | 33.05 |
October | 24.40 | 27.59 |
November | 24.37 | 21.57 |
December | 23.78 | 14.93 |
Annual Sum or Average | 24.25 | 26.21 |
Minimum of Months | 23.75 | 14.02 |
Maximum of Months | 24.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 14.02 |
February | 25.03 | 16.67 |
March | 25.82 | 20.28 |
April | 26.70 | 25.86 |
May | 27.59 | 32.05 |
June | 27.98 | 35.24 |
July | 28.07 | 36.21 |
August | 28.12 | 36.44 |
September | 27.73 | 33.05 |
October | 27.02 | 27.59 |
November | 26.07 | 21.57 |
December | 24.30 | 14.93 |
Annual Sum or Average | 26.55 | 26.21 |
Minimum of Months | 24.14 | 14.02 |
Maximum of Months | 28.12 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 14.02 |
February | 23.28 | 16.67 |
March | 24.30 | 20.28 |
April | 25.77 | 25.86 |
May | 27.20 | 32.05 |
June | 28.58 | 35.24 |
July | 28.91 | 36.21 |
August | 28.96 | 36.44 |
September | 28.38 | 33.05 |
October | 26.56 | 27.59 |
November | 25.00 | 21.57 |
December | 22.71 | 14.93 |
Annual Sum or Average | 26.01 | 26.21 |
Minimum of Months | 22.39 | 14.02 |
Maximum of Months | 28.96 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:04
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.56 | 14.02 |
February | 26.11 | 16.67 |
March | 26.44 | 20.28 |
April | 26.84 | 25.86 |
May | 27.31 | 32.05 |
June | 27.55 | 35.24 |
July | 27.61 | 36.21 |
August | 27.63 | 36.44 |
September | 27.44 | 33.05 |
October | 27.11 | 27.59 |
November | 26.67 | 21.57 |
December | 25.67 | 14.93 |
Annual Sum or Average | 26.83 | 26.21 |
Minimum of Months | 25.56 | 14.02 |
Maximum of Months | 27.63 | 36.44 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:04
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.123014E+12 | 75118.388 | 24-JAN-18:00 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 7697.650 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22163.322 | 0.000 | 0.000 | 0.000 |
February | 0.114432E+12 | 77848.976 | 26-FEB-18:15 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 13367.961 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19223.599 | 0.000 | 0.000 | 0.000 |
March | 0.130619E+12 | 82625.519 | 31-MAR-17:30 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 20845.723 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19075.380 | 0.000 | 0.000 | 0.000 |
April | 0.136048E+12 | 84872.579 | 18-APR-16:15 | 4276.255 | 26730.986 | 11093.542 | 0.000 | 23824.341 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18947.454 | 0.000 | 0.000 | 0.000 |
May | 0.155005E+12 | 90957.269 | 18-MAY-16:30 | 4276.255 | 26730.986 | 11093.542 | 0.000 | 31139.324 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17717.162 | 0.000 | 0.000 | 0.000 |
June | 0.160535E+12 | 96116.561 | 16-JUN-17:15 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 37863.162 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15548.983 | 0.000 | 0.000 | 0.000 |
July | 0.168866E+12 | 97570.667 | 30-JUL-17:15 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 37953.630 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16912.622 | 0.000 | 0.000 | 0.000 |
August | 0.170341E+12 | 96014.002 | 24-AUG-16:15 | 4276.255 | 26730.986 | 11093.542 | 0.000 | 38066.203 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15847.016 | 0.000 | 0.000 | 0.000 |
September | 0.156777E+12 | 94471.239 | 03-SEP-16:15 | 4276.255 | 26630.920 | 11093.542 | 0.000 | 34613.920 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17856.602 | 0.000 | 0.000 | 0.000 |
October | 0.148858E+12 | 87609.505 | 09-OCT-16:30 | 4276.255 | 26730.986 | 11093.542 | 0.000 | 27541.733 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17966.988 | 0.000 | 0.000 | 0.000 |
November | 0.131709E+12 | 81926.177 | 02-NOV-17:15 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 15523.013 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21145.748 | 0.000 | 0.000 | 0.000 |
December | 0.123380E+12 | 74305.990 | 16-DEC-18:15 | 4979.953 | 26630.920 | 11093.542 | 0.000 | 8640.985 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20407.589 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.171958E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.114432E+12 | 74305.990 | 4276.255 | 26630.920 | 11093.542 | 0.000 | 7697.650 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15548.983 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.170341E+12 | 97570.667 | 4979.953 | 26730.986 | 11093.542 | 0.000 | 38066.203 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22163.322 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:04
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.249937E+10 | 22560.994 | 09-JAN-04:00 | 22560.994 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22560.994 |
February | 0.495896E+09 | 7946.625 | 11-FEB-04:00 | 7946.625 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7946.625 |
March | 7085200.731 | 1121.359 | 16-MAR-10:00 | 1121.359 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1121.359 |
April | 0.000 | 0.000 | 01-APR-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 01-OCT-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.000 | 0.000 | 01-NOV-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.218873E+10 | 17284.030 | 06-DEC-03:00 | 17284.030 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17284.030 |
Annual Sum or Average | 0.519108E+10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.249937E+10 | 22560.994 | 22560.994 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22560.994 |