Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Simulation Timestamp: 2015-09-09 18:48:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1677.91 | 535.29 | 594.17 |
Net Site Energy | 1677.91 | 535.29 | 594.17 |
Total Source Energy | 4574.98 | 1459.50 | 1620.05 |
Net Source Energy | 4574.98 | 1459.50 | 1620.05 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 354.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 412.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1323.15 | 354.76 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 354.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 42.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 192.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 412.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.11 | 125.63 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 468.54 | 125.63 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 206.41 | 113.18 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 422.11 | 113.18 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1323.15 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1323.15 | 100.00 |
Total On-Site and Utility Electric Sources | 1323.15 | 100.00 |
Total Electricity End Uses | 1323.15 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 77.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1144.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48 |
RunPeriod | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Latitude [deg] | 49.18 |
Longitude [deg] | -123.2 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 23-JUN-17:15 | 16-DEC-16:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 80290.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10938.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6098.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25609.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74257.52 | 80290.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 80290.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 10938.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6098.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 25609.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 384.56 | 0.00 | 0.00 | 0.00 |
Cooling | 134.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 609.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1305.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4190.42 | 384.56 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 136.18 | 0.00 | 0.00 | 0.00 |
Cooling | 47.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 215.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 462.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1483.87 | 136.18 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 136.18 | 0.00 | 0.00 | 0.00 |
Cooling | 47.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 215.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 462.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1483.87 | 136.18 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00 | -7.00 | Wetbulb [C] | 2.90 | 100.00 |
VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 7.60 | 18.20 | Wetbulb [C] | 3.60 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.53 | 83.53 | 40.03 | |
Exterior Lighting Total | 2553.00 | 40.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2568.25 | 2044.86 | 523.39 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1866.51 | 1477.64 | 388.87 | 0.79 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7393.65 | 5904.98 | 1488.67 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1348.41 | 1051.82 | 296.59 | 0.78 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 970.11 | 754.66 | 215.45 | 0.78 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 954.76 | 742.26 | 212.50 | 0.78 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1970.28 | 1554.50 | 415.78 | 0.79 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2017.85 | 1595.26 | 422.59 | 0.79 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7291.30 | 5823.23 | 1468.06 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5368.28 | 4287.40 | 1080.87 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6888.30 | 5501.38 | 1386.92 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4182.29 | 3330.37 | 851.92 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3077.63 | 2435.43 | 642.20 | 0.79 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3049.51 | 2412.36 | 637.15 | 0.79 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5666.57 | 4525.63 | 1140.93 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5688.44 | 4543.10 | 1145.34 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4757.33 | 3799.46 | 957.86 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3433.89 | 2742.49 | 691.40 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4498.41 | 3592.68 | 905.73 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2607.38 | 2075.15 | 532.23 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2084.42 | 1639.10 | 445.31 | 0.79 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2094.07 | 1645.36 | 448.70 | 0.79 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3906.65 | 3120.07 | 786.58 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3922.03 | 3132.35 | 789.68 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2447.5 | 3.13 | 10.69 | 11.10 | 10.40 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1779.8 | 3.14 | 10.71 | 11.13 | 10.44 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7043.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1287.8 | 3.16 | 10.78 | 11.21 | 10.54 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 926.7 | 3.16 | 10.79 | 11.22 | 10.55 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 912.1 | 3.16 | 10.80 | 11.22 | 10.56 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1879.4 | 3.14 | 10.73 | 11.15 | 10.46 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1924.4 | 3.14 | 10.72 | 11.14 | 10.45 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6946.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5114.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6562.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3985.5 | 3.13 | 10.68 | 11.10 | 10.40 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2934.8 | 3.14 | 10.71 | 11.14 | 10.44 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2908.1 | 3.14 | 10.72 | 11.14 | 10.44 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5398.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5419.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4532.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3271.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4285.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2484.9 | 3.13 | 10.69 | 11.11 | 10.40 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1989.0 | 3.15 | 10.74 | 11.17 | 10.48 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1998.4 | 3.15 | 10.75 | 11.17 | 10.49 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3721.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3736.3 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2433.05 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2403.16 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 4464.75 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2408.34 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1812.18 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1812.31 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1811.39 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1913.31 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 4675.60 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 4678.55 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 4689.48 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 4692.43 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3579.58 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3579.58 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3579.58 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3579.58 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 3565.16 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 3568.35 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 3572.43 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 3575.62 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2761.13 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2761.33 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2756.13 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2756.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 178.90 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 128.40 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 518.49 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 89.77 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 64.19 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.05 | 63.09 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 134.53 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 138.39 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 511.31 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 376.46 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 483.05 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 291.41 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 211.52 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 209.44 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 397.38 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 398.91 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.29 | 333.61 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 240.81 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 315.46 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 181.46 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.28 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.68 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 273.96 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 275.04 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1639.78 | 1967.74 | 0.128 | 0.154 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
G NW APARTMENT | 1176.91 | 1412.29 | 0.092 | 0.111 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
OFFICE | 4655.99 | 5587.19 | 0.372 | 0.447 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 20.82 | 0.01029 |
G NE APARTMENT | 822.79 | 987.35 | 0.064 | 0.077 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
G N1 APARTMENT | 588.38 | 706.06 | 0.046 | 0.055 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
G N2 APARTMENT | 578.28 | 693.93 | 0.045 | 0.054 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
G S1 APARTMENT | 1233.08 | 1479.70 | 0.097 | 0.116 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
G S2 APARTMENT | 1268.50 | 1522.20 | 0.099 | 0.119 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
M SW APARTMENT | 4686.52 | 5623.83 | 0.367 | 0.440 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 24.66 | 0.01029 |
M NW APARTMENT | 3450.57 | 4140.68 | 0.270 | 0.324 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
M SE APARTMENT | 4427.50 | 5313.00 | 0.347 | 0.416 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.81 | 0.01029 |
M NE APARTMENT | 2670.95 | 3205.14 | 0.209 | 0.251 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
M N1 APARTMENT | 1938.82 | 2326.59 | 0.152 | 0.182 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
M N2 APARTMENT | 1919.68 | 2303.62 | 0.150 | 0.180 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.04 | 0.01029 |
M S1 APARTMENT | 3642.29 | 4370.74 | 0.285 | 0.342 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 25.00 | 0.01029 |
M S2 APARTMENT | 3656.34 | 4387.61 | 0.286 | 0.344 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
T SW APARTMENT | 3057.74 | 3669.29 | 0.239 | 0.287 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.77 | 0.01029 |
T NW APARTMENT | 2207.13 | 2648.56 | 0.173 | 0.207 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 23.75 | 0.01029 |
T SE APARTMENT | 2891.32 | 3469.58 | 0.226 | 0.272 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 24.91 | 0.01029 |
T NE APARTMENT | 1663.19 | 1995.82 | 0.130 | 0.156 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 23.44 | 0.01029 |
T N1 APARTMENT | 1294.97 | 1553.97 | 0.101 | 0.122 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 24.89 | 0.01029 |
T N2 APARTMENT | 1298.64 | 1558.37 | 0.102 | 0.122 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 25.00 | 0.01029 |
T S1 APARTMENT | 2511.04 | 3013.24 | 0.197 | 0.236 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 25.00 | 0.01029 |
T S2 APARTMENT | 2520.92 | 3025.10 | 0.197 | 0.237 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 25.00 | 0.01029 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1267.69 | 1521.23 | 0.036 | 0.044 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G NW APARTMENT | 1270.17 | 1524.21 | 0.037 | 0.044 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
OFFICE | 2712.01 | 3254.41 | 0.075 | 0.090 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G NE APARTMENT | 1274.55 | 1529.46 | 0.037 | 0.044 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G N1 APARTMENT | 770.41 | 924.49 | 0.022 | 0.027 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G N2 APARTMENT | 770.51 | 924.61 | 0.022 | 0.027 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G S1 APARTMENT | 769.73 | 923.68 | 0.022 | 0.027 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
G S2 APARTMENT | 855.93 | 1027.11 | 0.025 | 0.030 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
M SW APARTMENT | 2429.91 | 2915.89 | 0.070 | 0.084 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M NW APARTMENT | 2432.40 | 2918.88 | 0.070 | 0.084 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M SE APARTMENT | 2441.64 | 2929.97 | 0.070 | 0.084 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M NE APARTMENT | 2444.14 | 2932.97 | 0.070 | 0.084 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M N1 APARTMENT | 1172.84 | 1407.41 | 0.034 | 0.052 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M N2 APARTMENT | 1173.15 | 1407.78 | 0.034 | 0.052 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M S1 APARTMENT | 1171.89 | 1406.27 | 0.034 | 0.052 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
M S2 APARTMENT | 1172.20 | 1406.64 | 0.034 | 0.052 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T SW APARTMENT | 2252.90 | 2703.49 | 0.065 | 0.078 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T NW APARTMENT | 2255.60 | 2706.72 | 0.065 | 0.078 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T SE APARTMENT | 2259.05 | 2710.86 | 0.065 | 0.078 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T NE APARTMENT | 2261.75 | 2714.10 | 0.065 | 0.078 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T N1 APARTMENT | 1572.93 | 1887.52 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T N2 APARTMENT | 1573.10 | 1887.72 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T S1 APARTMENT | 1568.71 | 1882.45 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
T S2 APARTMENT | 1568.88 | 1882.65 | 0.045 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.00 | 0.00208 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.15 | 0.15 | 0.04 | 0.04 |
SPLIT GNW | 0.11 | 0.11 | 0.04 | 0.04 |
SPLIT OFFICE | 0.45 | 0.45 | 0.09 | 0.09 |
SPLIT GNE | 0.08 | 0.08 | 0.04 | 0.04 |
SPLIT GN1 | 0.06 | 0.06 | 0.03 | 0.03 |
SPLIT GN2 | 0.05 | 0.05 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT MSW | 0.44 | 0.44 | 0.08 | 0.08 |
SPLIT MNW | 0.32 | 0.32 | 0.08 | 0.08 |
SPLIT MSE | 0.42 | 0.42 | 0.08 | 0.08 |
SPLIT MNE | 0.25 | 0.25 | 0.08 | 0.08 |
SPLIT MN1 | 0.18 | 0.18 | 0.05 | 0.05 |
SPLIT MN2 | 0.18 | 0.18 | 0.05 | 0.05 |
SPLIT MS1 | 0.34 | 0.34 | 0.05 | 0.05 |
SPLIT MS2 | 0.34 | 0.34 | 0.05 | 0.05 |
SPLIT TSW | 0.29 | 0.29 | 0.08 | 0.08 |
SPLIT TNW | 0.21 | 0.21 | 0.08 | 0.08 |
SPLIT TSE | 0.27 | 0.27 | 0.08 | 0.08 |
SPLIT TNE | 0.16 | 0.16 | 0.08 | 0.08 |
SPLIT TN1 | 0.12 | 0.12 | 0.05 | 0.05 |
SPLIT TN2 | 0.12 | 0.12 | 0.05 | 0.05 |
SPLIT TS1 | 0.24 | 0.24 | 0.05 | 0.05 |
SPLIT TS2 | 0.24 | 0.24 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1379.00 | 6739.25 | 256.75 |
G NW APARTMENT | 1103.50 | 7254.25 | 382.75 |
OFFICE | 279.25 | 1658.75 | 47.75 |
G NE APARTMENT | 1066.75 | 7365.00 | 378.25 |
G N1 APARTMENT | 516.25 | 7511.50 | 135.75 |
G N2 APARTMENT | 510.75 | 7519.50 | 135.75 |
G S1 APARTMENT | 1061.50 | 6718.00 | 48.25 |
G S2 APARTMENT | 1154.75 | 6635.00 | 73.50 |
M SW APARTMENT | 2622.75 | 4969.00 | 0.00 |
M NW APARTMENT | 2270.50 | 5647.50 | 48.75 |
M SE APARTMENT | 2570.50 | 4990.50 | 0.00 |
M NE APARTMENT | 2199.50 | 5714.00 | 51.25 |
M N1 APARTMENT | 2131.50 | 5603.00 | 0.00 |
M N2 APARTMENT | 2122.75 | 5608.00 | 0.00 |
M S1 APARTMENT | 2590.75 | 4648.00 | 0.00 |
M S2 APARTMENT | 2589.25 | 4651.25 | 0.00 |
T SW APARTMENT | 2697.75 | 5912.75 | 853.50 |
T NW APARTMENT | 2533.50 | 6603.75 | 1104.00 |
T SE APARTMENT | 2697.50 | 5943.00 | 858.25 |
T NE APARTMENT | 2523.50 | 6717.25 | 1107.75 |
T N1 APARTMENT | 1781.75 | 6631.25 | 475.25 |
T N2 APARTMENT | 1783.50 | 6645.25 | 475.75 |
T S1 APARTMENT | 2156.00 | 5694.00 | 299.50 |
T S2 APARTMENT | 2156.25 | 5698.75 | 299.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4042.50 | 7637.50 | 1144.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 6.50 | 0.00 | 6.50 | 0.00 |
G NW APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
OFFICE | 6.25 | 0.25 | 0.00 | 0.00 |
G NE APARTMENT | 6.25 | 0.00 | 6.25 | 0.00 |
G N1 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
G N2 APARTMENT | 5.75 | 0.00 | 5.75 | 0.00 |
G S1 APARTMENT | 8.50 | 0.00 | 8.50 | 0.00 |
G S2 APARTMENT | 12.75 | 0.00 | 12.75 | 0.00 |
M SW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M NW APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
M SE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M NE APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M N1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M N2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T SW APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T NE APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T N1 APARTMENT | 7.75 | 0.00 | 7.75 | 0.00 |
T N2 APARTMENT | 7.25 | 0.00 | 7.25 | 0.00 |
T S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
T S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 83.25 | 0.25 | 77.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.151 | 0.000 | 0.064 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.151 | 0.000 | 0.061 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.169 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.151 | 0.000 | 0.061 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.091 | 0.000 | 0.060 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.091 | 0.000 | 0.060 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.064 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.091 | 0.000 | 0.064 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.218 | 0.000 | 0.074 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.218 | 0.000 | 0.070 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.218 | 0.000 | 0.074 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.218 | 0.000 | 0.070 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.070 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.131 | 0.000 | 0.070 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.074 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.131 | 0.000 | 0.074 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.288 | 0.000 | 0.079 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.288 | 0.000 | 0.075 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.288 | 0.000 | 0.080 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.288 | 0.000 | 0.075 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.173 | 0.000 | 0.075 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.173 | 0.000 | 0.075 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.174 | 0.000 | 0.080 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.174 | 0.000 | 0.080 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.501 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.367 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 412.32 | 0.00 | 01-JAN-00:15 | 32548.73 | 13-FEB-07:30 |
WaterSystems:Electricity | 412.32 | 0.00 | 01-JAN-00:15 | 32548.73 | 13-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 412.32 | 0.00 | 01-JAN-00:15 | 32548.73 | 13-FEB-07:30 |
Fans:Electricity | 192.32 | 6098.55 | 01-JAN-00:15 | 6098.55 | 01-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
ElectricityPurchased:Plant | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
Cogeneration:ElectricityPurchased | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
ElectricityNet:Plant | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
Cogeneration:ElectricityNet | 1323.15 | 19211.16 | 01-JAN-03:15 | 74257.52 | 23-JUN-17:15 |
ExteriorLights:Electricity | 40.03 | 0.00 | 01-JAN-08:15 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.03 | 0.00 | 01-JAN-08:15 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 234.68 | 6098.55 | 01-JAN-00:15 | 20408.27 | 12-JUL-15:15 |
General:Fans:Electricity | 192.32 | 6098.55 | 01-JAN-00:15 | 6098.55 | 01-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 42.36 | 0.00 | 01-JAN-00:15 | 14309.72 | 12-JUL-15:15 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 354.76 | 0.00 | 26-MAR-15:15 | 80290.91 | 16-DEC-17:00 |
Gas:HVAC | 354.76 | 0.00 | 26-MAR-15:15 | 80290.91 | 16-DEC-17:00 |
Heating:Gas | 354.76 | 0.00 | 26-MAR-15:15 | 80290.91 | 16-DEC-17:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 851.29 | 1808.05 | 01-SEP-16:00 | 116264.99 | 03-DEC-02:00 |
EnergyTransfer:Building | 394.63 | 1808.05 | 01-SEP-16:00 | 53035.00 | 03-DEC-02:00 |
EnergyTransfer:Zone:G SW APARTMENT | 10.27 | 0.11 | 29-JAN-20:00 | 1646.60 | 03-DEC-02:00 |
Heating:EnergyTransfer | 144.71 | 0.00 | 22-FEB-15:15 | 53035.00 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 5.65 | 0.00 | 01-JAN-10:45 | 1646.60 | 03-DEC-02:00 |
Cooling:EnergyTransfer | 249.93 | 0.00 | 05-JAN-07:15 | 47011.70 | 16-JUL-15:45 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 4.62 | 0.00 | 01-JAN-00:15 | 1558.79 | 13-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 10.09 | 0.13 | 29-APR-04:30 | 1658.22 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.99 | 0.00 | 21-JAN-17:15 | 1658.22 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 3.10 | 0.00 | 01-JAN-00:15 | 1338.84 | 11-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 17.61 | 0.00 | 18-SEP-01:15 | 3857.82 | 13-AUG-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 0.75 | 0.00 | 01-JAN-00:15 | 2350.14 | 17-DEC-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 16.86 | 0.00 | 02-JAN-07:45 | 3857.82 | 13-AUG-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 10.11 | 0.06 | 29-APR-15:30 | 1650.96 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 7.03 | 0.00 | 04-FEB-21:00 | 1650.96 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 3.08 | 0.00 | 01-JAN-00:15 | 801.24 | 11-JUL-18:30 |
EnergyTransfer:Zone:G N1 APARTMENT | 6.51 | 0.12 | 11-MAY-13:45 | 948.82 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.18 | 0.00 | 01-JAN-17:15 | 948.82 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.33 | 0.00 | 01-JAN-00:15 | 657.31 | 11-JUL-18:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 6.51 | 0.04 | 17-MAR-18:30 | 947.21 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.18 | 0.00 | 01-JAN-17:15 | 947.21 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.33 | 0.00 | 01-JAN-00:15 | 644.97 | 11-JUL-18:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.04 | 0.19 | 20-FEB-17:00 | 1150.69 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 2.25 | 0.00 | 01-JAN-09:45 | 936.34 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 4.79 | 0.00 | 01-JAN-00:15 | 1150.69 | 13-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.29 | 0.12 | 20-FEB-20:30 | 1159.46 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 2.43 | 0.00 | 01-JAN-10:00 | 989.84 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 4.86 | 0.00 | 01-JAN-00:15 | 1159.46 | 13-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 28.79 | 0.11 | 14-AUG-09:30 | 4685.19 | 13-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 6.51 | 0.00 | 01-JAN-00:15 | 3986.60 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 22.28 | 0.00 | 01-JAN-04:15 | 4685.19 | 13-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 23.82 | 0.24 | 05-SEP-15:00 | 4032.56 | 16-JUL-18:00 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 9.13 | 0.00 | 01-JAN-11:45 | 4021.20 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 14.69 | 0.00 | 01-JAN-00:15 | 4032.56 | 16-JUL-18:00 |
EnergyTransfer:Zone:M SE APARTMENT | 28.14 | 0.02 | 07-JAN-21:30 | 4238.04 | 13-SEP-13:15 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 6.63 | 0.00 | 01-JAN-00:15 | 3967.31 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 21.51 | 0.00 | 01-JAN-04:15 | 4238.04 | 13-SEP-13:15 |
EnergyTransfer:Zone:M NE APARTMENT | 23.48 | 0.20 | 14-APR-10:45 | 3971.08 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 9.29 | 0.00 | 01-JAN-10:30 | 3971.08 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 14.20 | 0.00 | 01-JAN-00:15 | 2772.86 | 11-JUL-18:30 |
EnergyTransfer:Zone:M N1 APARTMENT | 18.31 | 0.07 | 07-DEC-13:00 | 2323.35 | 11-JUL-18:45 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 2.13 | 0.00 | 01-JAN-00:15 | 2102.89 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 16.17 | 0.00 | 01-JAN-04:30 | 2323.35 | 11-JUL-18:45 |
EnergyTransfer:Zone:M N2 APARTMENT | 18.25 | 0.11 | 12-NOV-11:30 | 2300.75 | 11-JUL-18:45 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 2.13 | 0.00 | 01-JAN-00:15 | 2102.15 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 16.11 | 0.00 | 01-JAN-04:30 | 2300.75 | 11-JUL-18:45 |
EnergyTransfer:Zone:M S1 APARTMENT | 25.82 | 0.39 | 15-APR-01:45 | 3678.96 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 2065.54 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 24.62 | 0.00 | 02-JAN-23:30 | 3678.96 | 13-SEP-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 25.76 | 0.06 | 18-MAR-23:45 | 3691.89 | 13-SEP-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.19 | 0.00 | 01-JAN-00:15 | 2064.72 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 24.57 | 0.00 | 02-JAN-23:30 | 3691.89 | 13-SEP-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 19.41 | 0.02 | 25-SEP-19:30 | 3102.71 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 11.21 | 0.00 | 01-JAN-10:45 | 3102.71 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 8.20 | 0.00 | 01-JAN-00:15 | 2899.05 | 11-JUL-17:15 |
EnergyTransfer:Zone:T NW APARTMENT | 18.45 | 0.01 | 14-AUG-02:15 | 3116.92 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.15 | 0.00 | 04-FEB-18:00 | 3116.92 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 5.30 | 0.00 | 01-JAN-00:15 | 2668.43 | 11-JUL-17:30 |
EnergyTransfer:Zone:T SE APARTMENT | 18.98 | 0.01 | 20-AUG-06:00 | 3094.51 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 11.24 | 0.00 | 01-JAN-10:30 | 3094.51 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 7.74 | 0.00 | 01-JAN-00:15 | 2608.16 | 13-SEP-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 18.33 | 0.07 | 13-APR-08:30 | 3109.62 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 13.23 | 0.00 | 05-FEB-13:00 | 3109.62 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 5.10 | 0.00 | 01-JAN-00:15 | 1862.98 | 11-JUL-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 12.30 | 0.03 | 25-MAR-09:45 | 1896.42 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.37 | 0.00 | 21-JAN-13:45 | 1896.42 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 4.93 | 0.00 | 01-JAN-00:15 | 1593.60 | 11-JUL-17:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 12.28 | 0.03 | 19-MAY-10:15 | 1896.10 | 03-DEC-02:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.38 | 0.00 | 21-JAN-13:45 | 1896.10 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 4.90 | 0.00 | 01-JAN-00:15 | 1574.24 | 11-JUL-17:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 13.54 | 0.00 | 14-AUG-02:00 | 2345.81 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 5.73 | 0.00 | 01-JAN-10:15 | 1879.20 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 7.81 | 0.00 | 01-JAN-00:15 | 2345.81 | 13-SEP-13:45 |
EnergyTransfer:Zone:T S2 APARTMENT | 13.54 | 0.01 | 15-SEP-08:30 | 2354.03 | 13-SEP-13:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 5.74 | 0.00 | 01-JAN-10:15 | 1878.89 | 03-DEC-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 7.80 | 0.00 | 01-JAN-00:15 | 2354.03 | 13-SEP-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 456.66 | 0.00 | 06-JUN-00:45 | 64232.73 | 16-DEC-17:00 |
HeatingCoils:EnergyTransfer | 283.81 | 0.00 | 26-MAR-15:15 | 64232.73 | 16-DEC-17:00 |
CoolingCoils:EnergyTransfer | 172.85 | 0.00 | 01-JAN-00:15 | 62903.79 | 12-JUL-15:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 5.647 | -4.624 | 0.000 | 0.000 | 3.910 | 1.087 | 12.213 | 11.434 | 0.000 | 0.000 | 0.000 | 0.000 | -8.378 | 0.000 | -6.478 | -14.811 |
G NW APARTMENT | 6.993 | -3.098 | 0.000 | 0.000 | 3.940 | 1.087 | 12.213 | 5.692 | 0.000 | 0.000 | 0.000 | 0.000 | -8.398 | 0.000 | -6.316 | -12.113 |
OFFICE | 0.747 | -16.863 | 0.000 | 0.000 | 0.523 | 26.452 | 9.482 | 10.677 | 0.000 | 0.000 | 0.000 | 0.000 | -8.379 | 0.000 | -5.497 | -17.142 |
G NE APARTMENT | 7.034 | -3.081 | 0.000 | 0.000 | 3.954 | 1.087 | 12.213 | 5.074 | 0.000 | 0.000 | 0.000 | 0.000 | -8.310 | 0.000 | -6.302 | -11.668 |
G N1 APARTMENT | 3.177 | -3.332 | 0.000 | 0.000 | 3.951 | 1.087 | 12.213 | 1.728 | 0.000 | 0.000 | 0.000 | 0.000 | -5.164 | 0.000 | -4.152 | -9.508 |
G N2 APARTMENT | 3.180 | -3.328 | 0.000 | 0.000 | 3.952 | 1.087 | 12.213 | 1.728 | 0.000 | 0.000 | 0.000 | 0.000 | -5.162 | 0.000 | -4.151 | -9.519 |
G S1 APARTMENT | 2.247 | -4.793 | 0.000 | 0.000 | 3.908 | 1.087 | 12.213 | 7.513 | 0.000 | 0.000 | 0.000 | 0.000 | -5.145 | 0.000 | -4.333 | -12.697 |
G S2 APARTMENT | 2.429 | -4.861 | 0.000 | 0.000 | 3.905 | 1.087 | 12.213 | 7.508 | 0.000 | 0.000 | 0.000 | 0.000 | -5.147 | 0.000 | -4.343 | -12.790 |
M SW APARTMENT | 6.506 | -22.283 | 0.000 | 0.000 | 3.793 | 1.087 | 12.213 | 11.047 | 0.000 | 0.000 | 6.052 | 0.000 | -9.076 | 0.000 | -9.339 | -0.000 |
M NW APARTMENT | 9.125 | -14.692 | 0.000 | 0.000 | 3.848 | 1.087 | 12.213 | 5.363 | 0.000 | 0.000 | 1.163 | 0.000 | -8.982 | 0.000 | -9.125 | -0.001 |
M SE APARTMENT | 6.626 | -21.514 | 0.000 | 0.000 | 3.799 | 1.087 | 12.213 | 10.434 | 0.000 | 0.000 | 5.688 | 0.000 | -8.999 | 0.000 | -9.333 | -0.000 |
M NE APARTMENT | 9.286 | -14.197 | 0.000 | 0.000 | 3.860 | 1.087 | 12.213 | 4.745 | 0.000 | 0.000 | 0.996 | 0.000 | -8.882 | 0.000 | -9.107 | -0.000 |
M N1 APARTMENT | 2.133 | -16.175 | 0.000 | 0.000 | 3.841 | 1.087 | 12.213 | 1.520 | 0.000 | 0.000 | 6.990 | 0.000 | -5.600 | 0.000 | -6.008 | -0.000 |
M N2 APARTMENT | 2.135 | -16.115 | 0.000 | 0.000 | 3.842 | 1.087 | 12.213 | 1.520 | 0.000 | 0.000 | 6.923 | 0.000 | -5.597 | 0.000 | -6.007 | -0.000 |
M S1 APARTMENT | 1.194 | -24.625 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 7.268 | 0.000 | 0.000 | 10.949 | 0.000 | -5.640 | 0.000 | -6.207 | -0.000 |
M S2 APARTMENT | 1.194 | -24.566 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 7.268 | 0.000 | 0.000 | 10.889 | 0.000 | -5.639 | 0.000 | -6.207 | -0.000 |
T SW APARTMENT | 11.214 | -8.198 | 0.000 | 0.000 | 3.865 | 1.087 | 12.213 | 10.986 | 0.000 | 0.001 | 0.000 | 0.000 | -8.536 | 0.000 | -11.783 | -10.847 |
T NW APARTMENT | 13.151 | -5.295 | 0.000 | 0.000 | 3.908 | 1.087 | 12.213 | 5.356 | 0.000 | 0.000 | 0.000 | 0.000 | -8.498 | 0.000 | -11.503 | -10.419 |
T SE APARTMENT | 11.236 | -7.743 | 0.000 | 0.000 | 3.872 | 1.087 | 12.213 | 10.394 | 0.000 | 0.001 | 0.000 | 0.000 | -8.483 | 0.000 | -11.792 | -10.783 |
T NE APARTMENT | 13.231 | -5.104 | 0.000 | 0.000 | 3.925 | 1.087 | 12.213 | 4.759 | 0.000 | 0.000 | 0.000 | 0.000 | -8.415 | 0.000 | -11.486 | -10.209 |
T N1 APARTMENT | 7.369 | -4.929 | 0.000 | 0.000 | 3.909 | 1.087 | 12.213 | 1.550 | 0.000 | 0.000 | 0.000 | 0.000 | -5.253 | 0.000 | -7.428 | -8.519 |
T N2 APARTMENT | 7.380 | -4.898 | 0.000 | 0.000 | 3.911 | 1.087 | 12.213 | 1.549 | 0.000 | 0.000 | 0.000 | 0.000 | -5.250 | 0.000 | -7.428 | -8.563 |
T S1 APARTMENT | 5.733 | -7.811 | 0.000 | 0.000 | 3.847 | 1.087 | 12.213 | 7.245 | 0.000 | 0.000 | 0.000 | 0.000 | -5.290 | 0.000 | -7.691 | -9.333 |
T S2 APARTMENT | 5.742 | -7.800 | 0.000 | 0.000 | 3.848 | 1.087 | 12.213 | 7.244 | 0.000 | 0.000 | 0.000 | 0.000 | -5.288 | 0.000 | -7.692 | -9.353 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.029 | 0.000 | 0.000 | 0.000 | 0.000 | -0.993 | 0.000 | -1.890 | -11.729 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.143 | 0.000 | 0.000 | 13.418 | 0.000 | -2.591 | 0.000 | -32.031 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.028 | 0.000 | 0.000 | 0.000 | 0.000 | -1.098 | 0.000 | -1.567 | -11.944 |
Total Facility | 144.708 | -249.926 | 0.000 | 0.000 | 89.635 | 95.189 | 296.854 | 149.800 | 0.000 | 0.010 | 63.068 | 0.000 | -172.194 | 0.000 | -215.198 | -201.948 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 13-SEP-15:15 | 0.00 | -1559.14 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2484.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.94 | -1448.26 |
G NW APARTMENT | 11-JUL-17:30 | 0.00 | -1338.85 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1904.18 | 0.00 | 10.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1393.42 |
OFFICE | 06-AUG-06:01 | 0.00 | -7036.43 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 529.80 | 0.00 | 0.00 | 5893.20 | 0.00 | 0.00 | 0.00 | -97.03 | 0.00 |
G NE APARTMENT | 11-JUL-18:30 | 0.00 | -801.21 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 559.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12.42 | -538.71 |
G N1 APARTMENT | 11-JUL-18:30 | 0.00 | -657.28 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 488.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.05 | -612.82 |
G N2 APARTMENT | 11-JUL-18:30 | 0.00 | -644.94 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 488.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.05 | -625.40 |
G S1 APARTMENT | 13-SEP-13:30 | 0.00 | -1150.75 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2017.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55.63 | -1247.27 |
G S2 APARTMENT | 13-SEP-13:30 | 0.00 | -1159.53 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2017.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55.63 | -1238.30 |
M SW APARTMENT | 13-SEP-15:15 | 0.00 | -4686.17 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2462.24 | 0.00 | 0.00 | 1716.16 | 0.00 | 0.00 | 0.00 | -57.43 | 0.00 |
M NW APARTMENT | 16-JUL-18:00 | 0.00 | -4032.20 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1853.41 | 0.00 | 0.00 | 1377.45 | 0.00 | 0.00 | 0.00 | -16.66 | 0.00 |
M SE APARTMENT | 13-SEP-13:15 | 0.00 | -4238.25 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2212.29 | 0.00 | 0.00 | 1680.46 | 0.00 | 0.00 | 0.00 | -90.83 | 0.00 |
M NE APARTMENT | 11-JUL-18:30 | 0.00 | -2772.70 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 542.94 | 0.00 | 0.00 | 1451.86 | 0.00 | 0.00 | 0.00 | -15.10 | 0.00 |
M N1 APARTMENT | 11-JUL-18:45 | 0.00 | -2323.08 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 441.91 | 0.00 | 0.00 | 1101.64 | 0.00 | 0.00 | 0.00 | -13.47 | 0.00 |
M N2 APARTMENT | 11-JUL-18:45 | 0.00 | -2300.49 | 0.00 | 0.00 | 141.81 | 103.77 | 547.42 | 442.06 | 0.00 | 0.00 | 1078.90 | 0.00 | 0.00 | 0.00 | -13.47 | 0.00 |
M S1 APARTMENT | 13-SEP-13:30 | 0.00 | -3679.20 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2004.64 | 0.00 | 0.00 | 1309.90 | 0.00 | 0.00 | 0.00 | -71.66 | 0.00 |
M S2 APARTMENT | 13-SEP-13:30 | 0.00 | -3692.14 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2004.57 | 0.00 | 0.00 | 1322.91 | 0.00 | 0.00 | 0.00 | -71.66 | 0.00 |
T SW APARTMENT | 11-JUL-17:15 | 0.00 | -2899.21 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1815.32 | 0.00 | 24.96 | 240.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 11-JUL-17:30 | 0.00 | -2668.47 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1855.94 | 0.00 | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19.68 |
T SE APARTMENT | 13-SEP-13:30 | 0.00 | -2608.35 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2115.51 | 0.00 | 0.00 | 166.87 | 0.00 | 0.00 | 0.00 | -110.36 | 0.00 |
T NE APARTMENT | 11-JUL-16:08 | 0.00 | -1863.44 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 463.80 | 0.00 | 22.07 | 639.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 11-JUL-17:15 | 0.00 | -1593.89 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 214.33 | 0.00 | 21.78 | 539.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 11-JUL-17:15 | 0.00 | -1574.57 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 214.60 | 0.00 | 21.78 | 520.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 13-SEP-13:45 | 0.00 | -2346.01 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1895.13 | 0.00 | 0.00 | 100.68 | 0.00 | 0.00 | 0.00 | -86.12 | 0.00 |
T S2 APARTMENT | 13-SEP-13:45 | 0.00 | -2354.23 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1895.00 | 0.00 | 0.00 | 109.02 | 0.00 | 0.00 | 0.00 | -86.12 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUL-15:45 | 0.00 | -47008.76 | 0.00 | 0.00 | 1191.99 | 4512.09 | 11708.34 | 19541.90 | 0.00 | 478.17 | 9663.11 | 0.00 | 0.00 | 0.00 | -86.83 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 03-DEC-02:00 | 1646.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -466.51 | 0.00 | -1299.90 | -317.29 |
G NW APARTMENT | 13-NOV-17:01 | 2024.44 | 0.00 | 0.00 | 0.00 | 99.99 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -387.41 | 0.00 | -22.24 | -2368.26 |
OFFICE | 04-DEC-07:01 | 4154.71 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -436.93 | 0.00 | -413.21 | -4015.03 |
G NE APARTMENT | 03-DEC-02:00 | 1650.55 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -467.88 | 0.00 | -1299.89 | -320.26 |
G N1 APARTMENT | 28-DEC-18:02 | 1407.06 | 0.00 | 0.00 | 0.00 | 167.35 | 87.56 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.73 | 0.00 | -91.50 | -1945.35 |
G N2 APARTMENT | 20-MAY-06:01 | 993.58 | 0.00 | 0.00 | 0.00 | 163.04 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.27 | 0.00 | -103.56 | -1370.55 |
G S1 APARTMENT | 01-APR-07:01 | 1284.11 | 0.00 | 0.00 | 0.00 | 74.06 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -62.67 | 0.00 | -72.83 | -1630.62 |
G S2 APARTMENT | 28-DEC-17:01 | 1582.37 | 0.00 | 0.00 | 0.00 | 99.68 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -200.99 | 0.00 | -62.36 | -2072.18 |
M SW APARTMENT | 03-DEC-02:00 | 3985.62 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -481.62 | 0.00 | -1870.35 | -2071.13 |
M NW APARTMENT | 03-DEC-02:00 | 4020.20 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -489.26 | 0.00 | -1870.35 | -2098.08 |
M SE APARTMENT | 03-DEC-02:00 | 3966.33 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -475.97 | 0.00 | -1870.35 | -2057.49 |
M NE APARTMENT | 03-DEC-02:00 | 3970.10 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -483.64 | 0.00 | -1868.84 | -2055.12 |
M N1 APARTMENT | 06-JAN-07:01 | 2491.39 | 0.00 | 0.00 | 0.00 | 161.36 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -318.88 | 0.00 | -93.42 | -2665.21 |
M N2 APARTMENT | 06-JAN-07:01 | 2489.63 | 0.00 | 0.00 | 0.00 | 161.36 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -318.89 | 0.00 | -93.42 | -2663.45 |
M S1 APARTMENT | 03-DEC-02:00 | 2065.05 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -291.46 | 0.00 | -1128.15 | -1082.93 |
M S2 APARTMENT | 03-DEC-02:00 | 2064.24 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -291.47 | 0.00 | -1128.15 | -1082.11 |
T SW APARTMENT | 03-DEC-02:00 | 3101.94 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -466.89 | 0.00 | -2479.97 | -592.57 |
T NW APARTMENT | 03-DEC-02:00 | 3116.15 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -473.94 | 0.00 | -2479.97 | -599.73 |
T SE APARTMENT | 03-DEC-02:00 | 3093.74 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -461.21 | 0.00 | -2479.97 | -590.05 |
T NE APARTMENT | 03-DEC-02:00 | 3108.86 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -468.27 | 0.00 | -2479.97 | -598.11 |
T N1 APARTMENT | 03-DEC-02:00 | 1895.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -288.13 | 0.00 | -1495.91 | -549.40 |
T N2 APARTMENT | 23-FEB-17:01 | 2365.98 | 0.00 | 0.00 | 0.00 | 99.94 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -212.55 | 0.00 | -74.08 | -2832.77 |
T S1 APARTMENT | 03-DEC-02:00 | 1878.75 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.77 | 0.00 | -1495.91 | -538.56 |
T S2 APARTMENT | 03-DEC-02:00 | 1878.44 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.78 | 0.00 | -1495.91 | -538.24 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-DEC-02:00 | 53022.06 | 0.00 | 0.00 | 0.00 | 4362.43 | 1952.47 | 5793.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9282.91 | 0.00 | -36891.90 | -18955.34 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Sec1.1A-General InformationData | |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 77.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 77.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 354.76 | 80290.91 | 0.00 | 0.00 |
Space Cooling | 42.36 | 10938.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 192.32 | 6098.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 412.32 | 25609.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1323.15 | 354.76 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1323.15 |
Natural Gas | 0.00 | 354.76 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1677.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 13.51 |
Fans-Interior | 61.35 |
Service Water Heating | 131.54 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.77 |
Subtotal | 422.11 |
Natural Gas [MJ/m2] | |
Space Heating | 113.18 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 113.18 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.06 |
Space Heating | 21.14 |
Space Cooling | 2.52 |
Fans-Interior | 11.46 |
Service Water Heating | 24.57 |
Receptacle Equipment | 30.85 |
Miscellaneous | 2.39 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.154115 |
G NW APARTMENT DIRECT AIR | 0.110610 |
OFFICE DIRECT AIR | 0.446651 |
G NE APARTMENT DIRECT AIR | 0.077334 |
G N1 APARTMENT DIRECT AIR | 0.055298 |
G N2 APARTMENT DIRECT AIR | 0.054348 |
G S1 APARTMENT DIRECT AIR | 0.115890 |
G S2 APARTMENT DIRECT AIR | 0.119219 |
M SW APARTMENT DIRECT AIR | 0.440467 |
M NW APARTMENT DIRECT AIR | 0.324298 |
M SE APARTMENT DIRECT AIR | 0.416122 |
M NE APARTMENT DIRECT AIR | 0.251036 |
M N1 APARTMENT DIRECT AIR | 0.182217 |
M N2 APARTMENT DIRECT AIR | 0.180418 |
M S1 APARTMENT DIRECT AIR | 0.342317 |
M S2 APARTMENT DIRECT AIR | 0.343638 |
T SW APARTMENT DIRECT AIR | 0.287390 |
T NW APARTMENT DIRECT AIR | 0.207441 |
T SE APARTMENT DIRECT AIR | 0.271749 |
T NE APARTMENT DIRECT AIR | 0.156320 |
T N1 APARTMENT DIRECT AIR | 0.121709 |
T N2 APARTMENT DIRECT AIR | 0.122054 |
T S1 APARTMENT DIRECT AIR | 0.236001 |
T S2 APARTMENT DIRECT AIR | 0.236930 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.154115 |
SPLIT GNW MAIN BRANCH | 0.110610 |
SPLIT OFFICE MAIN BRANCH | 0.446651 |
SPLIT GNE MAIN BRANCH | 0.077334 |
SPLIT GN1 MAIN BRANCH | 0.055298 |
SPLIT GN2 MAIN BRANCH | 0.054348 |
SPLIT GS1 MAIN BRANCH | 0.115890 |
SPLIT GS2 MAIN BRANCH | 0.119219 |
SPLIT MSW MAIN BRANCH | 0.440467 |
SPLIT MNW MAIN BRANCH | 0.324298 |
SPLIT MSE MAIN BRANCH | 0.416122 |
SPLIT MNE MAIN BRANCH | 0.251036 |
SPLIT MN1 MAIN BRANCH | 0.182217 |
SPLIT MN2 MAIN BRANCH | 0.180418 |
SPLIT MS1 MAIN BRANCH | 0.342317 |
SPLIT MS2 MAIN BRANCH | 0.343638 |
SPLIT TSW MAIN BRANCH | 0.287390 |
SPLIT TNW MAIN BRANCH | 0.207441 |
SPLIT TSE MAIN BRANCH | 0.271749 |
SPLIT TNE MAIN BRANCH | 0.156320 |
SPLIT TN1 MAIN BRANCH | 0.121709 |
SPLIT TN2 MAIN BRANCH | 0.122054 |
SPLIT TS1 MAIN BRANCH | 0.236001 |
SPLIT TS2 MAIN BRANCH | 0.236930 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.154115 |
SPLIT GNW | 0.110610 |
SPLIT OFFICE | 0.446651 |
SPLIT GNE | 0.077334 |
SPLIT GN1 | 0.055298 |
SPLIT GN2 | 0.054348 |
SPLIT GS1 | 0.115890 |
SPLIT GS2 | 0.119219 |
SPLIT MSW | 0.440467 |
SPLIT MNW | 0.324298 |
SPLIT MSE | 0.416122 |
SPLIT MNE | 0.251036 |
SPLIT MN1 | 0.182217 |
SPLIT MN2 | 0.180418 |
SPLIT MS1 | 0.342317 |
SPLIT MS2 | 0.343638 |
SPLIT TSW | 0.287390 |
SPLIT TNW | 0.207441 |
SPLIT TSE | 0.271749 |
SPLIT TNE | 0.156320 |
SPLIT TN1 | 0.121709 |
SPLIT TN2 | 0.122054 |
SPLIT TS1 | 0.236001 |
SPLIT TS2 | 0.236930 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.154115 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.110610 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.446651 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.077334 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.055298 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.054348 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.115890 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.119219 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.440467 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.324298 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.416122 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.251036 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.182217 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.180418 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.342317 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.343638 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.287390 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.207441 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.271749 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.156320 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.121709 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.122054 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.236001 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.236930 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.154115 | 2568.25 | 0.796207 |
SPLIT GNW COOLING COIL | 0.110610 | 1866.51 | 0.791657 |
SPLIT OFFICE COOLING COIL | 0.446651 | 7393.65 | 0.798655 |
SPLIT GNE COOLING COIL | 0.077334 | 1348.41 | 0.780042 |
SPLIT GN1 COOLING COIL | 0.055298 | 970.11 | 0.777911 |
SPLIT GN2 COOLING COIL | 0.054348 | 954.76 | 0.777435 |
SPLIT GS1 COOLING COIL | 0.115890 | 1970.28 | 0.788972 |
SPLIT GS2 COOLING COIL | 0.119219 | 2017.85 | 0.790575 |
SPLIT MSW COOLING COIL | 0.440467 | 7291.30 | 0.798655 |
SPLIT MNW COOLING COIL | 0.324298 | 5368.28 | 0.798655 |
SPLIT MSE COOLING COIL | 0.416122 | 6888.30 | 0.798655 |
SPLIT MNE COOLING COIL | 0.251036 | 4182.29 | 0.796303 |
SPLIT MN1 COOLING COIL | 0.182217 | 3077.63 | 0.791333 |
SPLIT MN2 COOLING COIL | 0.180418 | 3049.51 | 0.791065 |
SPLIT MS1 COOLING COIL | 0.342317 | 5666.57 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.343638 | 5688.44 | 0.798655 |
SPLIT TSW COOLING COIL | 0.287390 | 4757.33 | 0.798655 |
SPLIT TNW COOLING COIL | 0.207441 | 3433.89 | 0.798655 |
SPLIT TSE COOLING COIL | 0.271749 | 4498.41 | 0.798655 |
SPLIT TNE COOLING COIL | 0.156320 | 2607.38 | 0.795875 |
SPLIT TN1 COOLING COIL | 0.121709 | 2084.42 | 0.786360 |
SPLIT TN2 COOLING COIL | 0.122054 | 2094.07 | 0.785726 |
SPLIT TS1 COOLING COIL | 0.236001 | 3906.65 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.236930 | 3922.03 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.154115 | 0.154115 | 0.154115 | 0.154115 | 2433.05 | 2568.25 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.110610 | 0.110610 | 0.110610 | 0.110610 | 2403.16 | 1866.51 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.446651 | 0.446651 | 0.446651 | 0.446651 | 4464.75 | 7393.65 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.077334 | 0.077334 | 0.077334 | 0.077334 | 2408.34 | 1348.41 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.055298 | 0.055298 | 0.055298 | 0.055298 | 1812.18 | 970.11 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.054348 | 0.054348 | 0.054348 | 0.054348 | 1812.31 | 954.76 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.115890 | 0.115890 | 0.115890 | 0.115890 | 1811.39 | 1970.28 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.119219 | 0.119219 | 0.119219 | 0.119219 | 1913.31 | 2017.85 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.440467 | 0.440467 | 0.440467 | 0.440467 | 4675.60 | 7291.30 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.324298 | 0.324298 | 0.324298 | 0.324298 | 4678.55 | 5368.28 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.416122 | 0.416122 | 0.416122 | 0.416122 | 4689.48 | 6888.30 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.251036 | 0.251036 | 0.251036 | 0.251036 | 4692.43 | 4182.29 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.182217 | 0.182217 | 0.182217 | 0.182217 | 3579.58 | 3077.63 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.180418 | 0.180418 | 0.180418 | 0.180418 | 3579.58 | 3049.51 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.342317 | 0.342317 | 0.342317 | 0.342317 | 3579.58 | 5666.57 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.343638 | 0.343638 | 0.343638 | 0.343638 | 3579.58 | 5688.44 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.287390 | 0.287390 | 0.287390 | 0.287390 | 3565.16 | 4757.33 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.207441 | 0.207441 | 0.207441 | 0.207441 | 3568.35 | 3433.89 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.271749 | 0.271749 | 0.271749 | 0.271749 | 3572.43 | 4498.41 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.156320 | 0.156320 | 0.156320 | 0.156320 | 3575.62 | 2607.38 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.121709 | 0.121709 | 0.121709 | 0.121709 | 2761.13 | 2084.42 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.122054 | 0.122054 | 0.122054 | 0.122054 | 2761.33 | 2094.07 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.236001 | 0.236001 | 0.236001 | 0.236001 | 2756.13 | 3906.65 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.236930 | 0.236930 | 0.236930 | 0.236930 | 2756.34 | 3922.03 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.154115 |
SPLIT GNW SUPPLY FAN | 0.110610 |
SPLIT OFFICE SUPPLY FAN | 0.446651 |
SPLIT GNE SUPPLY FAN | 0.077334 |
SPLIT GN1 SUPPLY FAN | 0.055298 |
SPLIT GN2 SUPPLY FAN | 0.054348 |
SPLIT GS1 SUPPLY FAN | 0.115890 |
SPLIT GS2 SUPPLY FAN | 0.119219 |
SPLIT MSW SUPPLY FAN | 0.440467 |
SPLIT MNW SUPPLY FAN | 0.324298 |
SPLIT MSE SUPPLY FAN | 0.416122 |
SPLIT MNE SUPPLY FAN | 0.251036 |
SPLIT MN1 SUPPLY FAN | 0.182217 |
SPLIT MN2 SUPPLY FAN | 0.180418 |
SPLIT MS1 SUPPLY FAN | 0.342317 |
SPLIT MS2 SUPPLY FAN | 0.343638 |
SPLIT TSW SUPPLY FAN | 0.287390 |
SPLIT TNW SUPPLY FAN | 0.207441 |
SPLIT TSE SUPPLY FAN | 0.271749 |
SPLIT TNE SUPPLY FAN | 0.156320 |
SPLIT TN1 SUPPLY FAN | 0.121709 |
SPLIT TN2 SUPPLY FAN | 0.122054 |
SPLIT TS1 SUPPLY FAN | 0.236001 |
SPLIT TS2 SUPPLY FAN | 0.236930 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2433.05 |
SPLIT GNW HEATING COIL | 2403.16 |
SPLIT OFFICE HEATING COIL | 4464.75 |
SPLIT GNE HEATING COIL | 2408.34 |
SPLIT GN1 HEATING COIL | 1812.18 |
SPLIT GN2 HEATING COIL | 1812.31 |
SPLIT GS1 HEATING COIL | 1811.39 |
SPLIT GS2 HEATING COIL | 1913.31 |
SPLIT MSW HEATING COIL | 4675.60 |
SPLIT MNW HEATING COIL | 4678.55 |
SPLIT MSE HEATING COIL | 4689.48 |
SPLIT MNE HEATING COIL | 4692.43 |
SPLIT MN1 HEATING COIL | 3579.58 |
SPLIT MN2 HEATING COIL | 3579.58 |
SPLIT MS1 HEATING COIL | 3579.58 |
SPLIT MS2 HEATING COIL | 3579.58 |
SPLIT TSW HEATING COIL | 3565.16 |
SPLIT TNW HEATING COIL | 3568.35 |
SPLIT TSE HEATING COIL | 3572.43 |
SPLIT TNE HEATING COIL | 3575.62 |
SPLIT TN1 HEATING COIL | 2761.13 |
SPLIT TN2 HEATING COIL | 2761.33 |
SPLIT TS1 HEATING COIL | 2756.13 |
SPLIT TS2 HEATING COIL | 2756.34 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.77 | 5.10 |
March | 21.86 | 6.09 |
April | 22.16 | 8.68 |
May | 22.49 | 11.83 |
June | 23.81 | 15.06 |
July | 24.15 | 16.98 |
August | 24.18 | 17.08 |
September | 23.66 | 13.78 |
October | 22.02 | 9.83 |
November | 21.74 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.61 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.18 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.73 | 6.09 |
April | 21.84 | 8.68 |
May | 22.14 | 11.83 |
June | 23.61 | 15.06 |
July | 24.05 | 16.98 |
August | 24.03 | 17.08 |
September | 23.21 | 13.78 |
October | 21.76 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.43 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.05 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 3.20 |
February | 21.59 | 5.10 |
March | 21.79 | 6.09 |
April | 22.64 | 8.68 |
May | 23.34 | 11.83 |
June | 24.92 | 15.06 |
July | 25.51 | 16.98 |
August | 25.45 | 17.08 |
September | 24.81 | 13.78 |
October | 22.72 | 9.83 |
November | 21.36 | 5.28 |
December | 20.59 | 3.63 |
Annual Sum or Average | 22.97 | 9.74 |
Minimum of Months | 20.59 | 3.20 |
Maximum of Months | 25.51 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.71 | 6.09 |
April | 21.80 | 8.68 |
May | 22.02 | 11.83 |
June | 23.51 | 15.06 |
July | 24.01 | 16.98 |
August | 23.99 | 17.08 |
September | 23.11 | 13.78 |
October | 21.75 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.40 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.01 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.71 | 6.09 |
April | 21.75 | 8.68 |
May | 21.91 | 11.83 |
June | 23.45 | 15.06 |
July | 23.99 | 16.98 |
August | 23.98 | 17.08 |
September | 23.17 | 13.78 |
October | 21.75 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.38 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.99 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.71 | 6.09 |
April | 21.75 | 8.68 |
May | 21.90 | 11.83 |
June | 23.44 | 15.06 |
July | 23.98 | 16.98 |
August | 23.97 | 17.08 |
September | 23.16 | 13.78 |
October | 21.75 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.38 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 23.98 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.78 | 5.10 |
March | 21.85 | 6.09 |
April | 22.11 | 8.68 |
May | 22.35 | 11.83 |
June | 23.82 | 15.06 |
July | 24.18 | 16.98 |
August | 24.24 | 17.08 |
September | 23.83 | 13.78 |
October | 22.09 | 9.83 |
November | 21.75 | 5.28 |
December | 21.71 | 3.63 |
Annual Sum or Average | 22.62 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.24 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.78 | 5.10 |
March | 21.85 | 6.09 |
April | 22.12 | 8.68 |
May | 22.38 | 11.83 |
June | 23.85 | 15.06 |
July | 24.20 | 16.98 |
August | 24.26 | 17.08 |
September | 23.86 | 13.78 |
October | 22.11 | 9.83 |
November | 21.75 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.64 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.26 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.11 | 5.10 |
March | 22.48 | 6.09 |
April | 23.38 | 8.68 |
May | 24.10 | 11.83 |
June | 24.36 | 15.06 |
July | 24.40 | 16.98 |
August | 24.40 | 17.08 |
September | 24.13 | 13.78 |
October | 22.90 | 9.83 |
November | 21.95 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 23.14 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.40 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.97 | 6.09 |
April | 22.47 | 8.68 |
May | 23.85 | 11.83 |
June | 24.32 | 15.06 |
July | 24.39 | 16.98 |
August | 24.38 | 17.08 |
September | 23.88 | 13.78 |
October | 22.15 | 9.83 |
November | 21.71 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.86 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.39 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.08 | 5.10 |
March | 22.44 | 6.09 |
April | 23.30 | 8.68 |
May | 24.08 | 11.83 |
June | 24.35 | 15.06 |
July | 24.40 | 16.98 |
August | 24.40 | 17.08 |
September | 24.13 | 13.78 |
October | 22.90 | 9.83 |
November | 21.94 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 23.13 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.40 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.90 | 6.09 |
April | 22.34 | 8.68 |
May | 23.75 | 11.83 |
June | 24.29 | 15.06 |
July | 24.38 | 16.98 |
August | 24.37 | 17.08 |
September | 23.81 | 13.78 |
October | 22.12 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.82 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.38 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.95 | 6.09 |
April | 22.43 | 8.68 |
May | 23.94 | 11.83 |
June | 24.35 | 15.06 |
July | 24.39 | 16.98 |
August | 24.39 | 17.08 |
September | 24.00 | 13.78 |
October | 22.35 | 9.83 |
November | 21.73 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.89 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.39 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.95 | 6.09 |
April | 22.41 | 8.68 |
May | 23.93 | 11.83 |
June | 24.35 | 15.06 |
July | 24.39 | 16.98 |
August | 24.39 | 17.08 |
September | 23.99 | 13.78 |
October | 22.35 | 9.83 |
November | 21.73 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.89 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.39 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 3.20 |
February | 22.43 | 5.10 |
March | 22.63 | 6.09 |
April | 23.61 | 8.68 |
May | 24.25 | 11.83 |
June | 24.39 | 15.06 |
July | 24.40 | 16.98 |
August | 24.40 | 17.08 |
September | 24.28 | 13.78 |
October | 23.41 | 9.83 |
November | 22.18 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.30 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.40 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 22.43 | 5.10 |
March | 22.63 | 6.09 |
April | 23.60 | 8.68 |
May | 24.24 | 11.83 |
June | 24.39 | 15.06 |
July | 24.40 | 16.98 |
August | 24.40 | 17.08 |
September | 24.28 | 13.78 |
October | 23.41 | 9.83 |
November | 22.18 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 23.30 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 24.40 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.20 |
February | 22.00 | 5.10 |
March | 22.21 | 6.09 |
April | 22.76 | 8.68 |
May | 23.38 | 11.83 |
June | 24.03 | 15.06 |
July | 24.24 | 16.98 |
August | 24.23 | 17.08 |
September | 23.54 | 13.78 |
October | 22.36 | 9.83 |
November | 21.84 | 5.28 |
December | 21.72 | 3.63 |
Annual Sum or Average | 22.84 | 9.74 |
Minimum of Months | 21.72 | 3.20 |
Maximum of Months | 24.24 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.71 | 5.10 |
March | 21.87 | 6.09 |
April | 22.29 | 8.68 |
May | 23.09 | 11.83 |
June | 23.88 | 15.06 |
July | 24.14 | 16.98 |
August | 24.08 | 17.08 |
September | 23.11 | 13.78 |
October | 21.91 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.60 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.14 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 3.20 |
February | 21.98 | 5.10 |
March | 22.19 | 6.09 |
April | 22.75 | 8.68 |
May | 23.38 | 11.83 |
June | 24.01 | 15.06 |
July | 24.22 | 16.98 |
August | 24.23 | 17.08 |
September | 23.53 | 13.78 |
October | 22.37 | 9.83 |
November | 21.84 | 5.28 |
December | 21.71 | 3.63 |
Annual Sum or Average | 22.83 | 9.74 |
Minimum of Months | 21.71 | 3.20 |
Maximum of Months | 24.23 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 22.20 | 8.68 |
May | 23.04 | 11.83 |
June | 23.81 | 15.06 |
July | 24.05 | 16.98 |
August | 24.01 | 17.08 |
September | 23.04 | 13.78 |
October | 21.88 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.56 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.05 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 22.18 | 8.68 |
May | 23.09 | 11.83 |
June | 23.93 | 15.06 |
July | 24.16 | 16.98 |
August | 24.11 | 17.08 |
September | 23.11 | 13.78 |
October | 21.89 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.60 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.16 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 3.20 |
February | 21.70 | 5.10 |
March | 21.82 | 6.09 |
April | 22.17 | 8.68 |
May | 23.09 | 11.83 |
June | 23.92 | 15.06 |
July | 24.15 | 16.98 |
August | 24.10 | 17.08 |
September | 23.11 | 13.78 |
October | 21.90 | 9.83 |
November | 21.70 | 5.28 |
December | 21.70 | 3.63 |
Annual Sum or Average | 22.59 | 9.74 |
Minimum of Months | 21.70 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.06 | 5.10 |
March | 22.27 | 6.09 |
April | 22.85 | 8.68 |
May | 23.54 | 11.83 |
June | 24.14 | 15.06 |
July | 24.31 | 16.98 |
August | 24.31 | 17.08 |
September | 23.72 | 13.78 |
October | 22.51 | 9.83 |
November | 21.88 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.93 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.31 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 3.20 |
February | 22.06 | 5.10 |
March | 22.27 | 6.09 |
April | 22.85 | 8.68 |
May | 23.53 | 11.83 |
June | 24.14 | 15.06 |
July | 24.30 | 16.98 |
August | 24.31 | 17.08 |
September | 23.72 | 13.78 |
October | 22.51 | 9.83 |
November | 21.88 | 5.28 |
December | 21.74 | 3.63 |
Annual Sum or Average | 22.92 | 9.74 |
Minimum of Months | 21.73 | 3.20 |
Maximum of Months | 24.31 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 3.20 |
February | 21.79 | 5.10 |
March | 22.16 | 6.09 |
April | 23.22 | 8.68 |
May | 24.45 | 11.83 |
June | 25.57 | 15.06 |
July | 26.00 | 16.98 |
August | 25.87 | 17.08 |
September | 24.61 | 13.78 |
October | 22.63 | 9.83 |
November | 21.52 | 5.28 |
December | 21.14 | 3.63 |
Annual Sum or Average | 23.35 | 9.74 |
Minimum of Months | 21.14 | 3.20 |
Maximum of Months | 26.00 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.99 | 3.20 |
February | 19.54 | 5.10 |
March | 19.84 | 6.09 |
April | 20.66 | 8.68 |
May | 21.60 | 11.83 |
June | 23.74 | 15.06 |
July | 24.65 | 16.98 |
August | 24.61 | 17.08 |
September | 23.50 | 13.78 |
October | 20.87 | 9.83 |
November | 19.55 | 5.28 |
December | 19.01 | 3.63 |
Annual Sum or Average | 21.39 | 9.74 |
Minimum of Months | 18.99 | 3.20 |
Maximum of Months | 24.65 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:11
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 3.20 |
February | 23.37 | 5.10 |
March | 23.64 | 6.09 |
April | 24.68 | 8.68 |
May | 25.93 | 11.83 |
June | 26.45 | 15.06 |
July | 26.63 | 16.98 |
August | 26.57 | 17.08 |
September | 26.06 | 13.78 |
October | 24.26 | 9.83 |
November | 23.11 | 5.28 |
December | 22.67 | 3.63 |
Annual Sum or Average | 24.69 | 9.74 |
Minimum of Months | 22.67 | 3.20 |
Maximum of Months | 26.63 | 17.08 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:11
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.111728E+12 | 71988.302 | 05-JAN-18:15 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31725.877 | 0.000 | 0.000 | 0.000 |
February | 0.100890E+12 | 71708.716 | 12-FEB-18:45 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31446.291 | 0.000 | 0.000 | 0.000 |
March | 0.111299E+12 | 71344.389 | 01-MAR-18:30 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31081.964 | 0.000 | 0.000 | 0.000 |
April | 0.107612E+12 | 71333.872 | 29-APR-17:45 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 8009.198 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25615.248 | 0.000 | 0.000 | 0.000 |
May | 0.111537E+12 | 68950.495 | 28-MAY-17:00 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 5177.389 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26063.681 | 0.000 | 0.000 | 0.000 |
June | 0.110289E+12 | 74257.522 | 23-JUN-17:15 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 10938.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25609.988 | 0.000 | 0.000 | 0.000 |
July | 0.117864E+12 | 73937.577 | 12-JUL-17:00 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 12658.825 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23569.327 | 0.000 | 0.000 | 0.000 |
August | 0.116906E+12 | 71282.703 | 01-AUG-17:30 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 9810.198 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23763.080 | 0.000 | 0.000 | 0.000 |
September | 0.108536E+12 | 68908.882 | 13-SEP-17:15 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 11220.903 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19978.554 | 0.000 | 0.000 | 0.000 |
October | 0.109101E+12 | 65768.620 | 10-OCT-17:45 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25506.194 | 0.000 | 0.000 | 0.000 |
November | 0.106332E+12 | 66024.546 | 11-NOV-18:30 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25762.121 | 0.000 | 0.000 | 0.000 |
December | 0.111057E+12 | 70594.067 | 28-DEC-18:15 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30331.642 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.132315E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.100890E+12 | 65768.620 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19978.554 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.117864E+12 | 74257.522 | 4979.953 | 26630.920 | 6098.551 | 0.000 | 12658.825 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31725.877 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:11
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.781011E+11 | 55907.196 | 09-JAN-16:00 | 55907.196 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 55907.196 |
February | 0.434960E+11 | 68592.062 | 17-FEB-16:00 | 68592.062 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68592.062 |
March | 0.453018E+11 | 55051.180 | 20-MAR-00:00 | 55051.180 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 55051.180 |
April | 0.169953E+11 | 64425.458 | 15-APR-04:00 | 64425.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 64425.458 |
May | 0.425025E+10 | 16323.893 | 06-MAY-03:00 | 16323.893 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16323.893 |
June | 0.699858E+08 | 3225.046 | 16-JUN-02:00 | 3225.046 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3225.046 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.179504E+10 | 13148.009 | 29-SEP-03:00 | 13148.009 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13148.009 |
October | 0.188248E+11 | 41869.671 | 28-OCT-04:00 | 41869.671 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 41869.671 |
November | 0.580666E+11 | 67068.927 | 20-NOV-17:00 | 67068.927 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 67068.927 |
December | 0.878617E+11 | 80290.915 | 16-DEC-16:00 | 80290.915 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 80290.915 |
Annual Sum or Average | 0.354762E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.878617E+11 | 80290.915 | 80290.915 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 80290.915 |