Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: San Francisco Intl Ap CA USA TMY3 WMO#=724940
Simulation Timestamp: 2015-09-09 18:48:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1329.50 | 424.13 | 470.79 |
Net Site Energy | 1329.50 | 424.13 | 470.79 |
Total Source Energy | 4103.90 | 1309.22 | 1453.23 |
Net Source Energy | 4103.90 | 1309.22 | 1453.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 51.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 385.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1278.31 | 51.19 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 51.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 181.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 385.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 213.21 | 18.13 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 452.66 | 18.13 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.09 | 16.33 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 407.81 | 16.33 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1278.31 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1278.31 | 100.00 |
Total On-Site and Utility Electric Sources | 1278.31 | 100.00 |
Total Electricity End Uses | 1278.31 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 88.25 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 9.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48 |
RunPeriod | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Latitude [deg] | 37.62 |
Longitude [deg] | -122.4 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-17:15 | 22-DEC-04:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 37898.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13114.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5761.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24098.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 74584.72 | 37898.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 37898.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13114.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 5761.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 24098.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 55.48 | 0.00 | 0.00 | 0.00 |
Cooling | 111.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 575.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1220.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4048.42 | 55.48 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.65 | 0.00 | 0.00 | 0.00 |
Cooling | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 432.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1433.59 | 19.65 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.65 | 0.00 | 0.00 | 0.00 |
Cooling | 39.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 432.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1433.59 | 19.65 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 2.20 | 150.00 |
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 8.50 | 17.20 | Wetbulb [C] | 5.90 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.62_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 112.97 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 193.95 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.65 | 83.65 | 40.09 | |
Exterior Lighting Total | 2553.00 | 40.09 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2279.77 | 1820.75 | 459.02 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1927.86 | 1539.70 | 388.16 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7260.69 | 5798.79 | 1461.90 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1400.27 | 1118.33 | 281.94 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1021.38 | 815.73 | 205.65 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1009.31 | 806.09 | 203.22 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1564.23 | 1249.28 | 314.95 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1618.51 | 1292.63 | 325.88 | 0.80 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6348.50 | 5070.26 | 1278.24 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5428.70 | 4335.66 | 1093.04 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5825.16 | 4652.30 | 1172.87 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4267.57 | 3408.32 | 859.25 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3214.88 | 2567.58 | 647.30 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3193.22 | 2550.28 | 642.94 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4615.58 | 3686.26 | 929.32 | 0.80 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4633.00 | 3700.17 | 932.83 | 0.80 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4337.59 | 3464.24 | 873.35 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3633.49 | 2901.91 | 731.58 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4042.85 | 3228.84 | 814.01 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2947.42 | 2353.98 | 593.45 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2361.19 | 1885.77 | 475.41 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2365.69 | 1889.37 | 476.32 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3423.89 | 2734.51 | 689.38 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3435.71 | 2743.95 | 691.76 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2171.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1836.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6917.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1334.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 973.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 961.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1490.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1541.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6047.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5171.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5549.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4065.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3062.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3042.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4397.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4413.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4132.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3461.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3851.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2807.9 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2249.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2253.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3261.8 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3273.1 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1503.52 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 2694.04 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1450.67 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 2901.34 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 1986.95 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 1985.05 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 1989.98 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 1988.10 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 1518.25 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 1518.34 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 1518.27 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 1518.36 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 159.87 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 135.19 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 509.17 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 98.20 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 71.63 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.06 | 70.78 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 109.69 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 113.50 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 445.20 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 380.69 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 408.50 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 299.27 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.45 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 223.93 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 323.67 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 324.90 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 304.18 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 254.80 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 283.51 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.18 | 206.69 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 165.58 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 165.90 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 240.10 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 240.93 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1465.42 | 1758.51 | 0.115 | 0.138 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 27.62 | 0.00771 |
G NW APARTMENT | 1239.22 | 1487.06 | 0.097 | 0.116 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 26.47 | 0.00771 |
OFFICE | 4575.22 | 5490.27 | 0.366 | 0.439 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.62 | 0.00771 |
G NE APARTMENT | 900.07 | 1080.08 | 0.070 | 0.085 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
G N1 APARTMENT | 656.53 | 787.84 | 0.051 | 0.062 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
G N2 APARTMENT | 648.78 | 778.53 | 0.051 | 0.061 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
G S1 APARTMENT | 1005.47 | 1206.57 | 0.079 | 0.094 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
G S2 APARTMENT | 1040.37 | 1248.44 | 0.081 | 0.098 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
M SW APARTMENT | 4080.80 | 4896.96 | 0.320 | 0.384 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 27.45 | 0.00771 |
M NW APARTMENT | 3489.55 | 4187.46 | 0.273 | 0.328 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 26.47 | 0.00771 |
M SE APARTMENT | 3744.40 | 4493.28 | 0.293 | 0.352 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 28.09 | 0.00771 |
M NE APARTMENT | 2743.17 | 3291.80 | 0.215 | 0.258 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
M N1 APARTMENT | 2066.51 | 2479.81 | 0.162 | 0.194 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
M N2 APARTMENT | 2052.58 | 2463.10 | 0.161 | 0.193 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 25.62 | 0.00771 |
M S1 APARTMENT | 2966.87 | 3560.25 | 0.232 | 0.279 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
M S2 APARTMENT | 2978.07 | 3573.68 | 0.233 | 0.280 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
T SW APARTMENT | 2788.20 | 3345.84 | 0.218 | 0.262 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 28.05 | 0.00771 |
T NW APARTMENT | 2335.61 | 2802.73 | 0.183 | 0.219 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 27.28 | 0.00771 |
T SE APARTMENT | 2598.74 | 3118.49 | 0.204 | 0.244 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 28.19 | 0.00771 |
T NE APARTMENT | 1894.60 | 2273.52 | 0.148 | 0.178 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 28.30 | 0.00771 |
T N1 APARTMENT | 1517.76 | 1821.31 | 0.119 | 0.143 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 28.30 | 0.00771 |
T N2 APARTMENT | 1520.66 | 1824.79 | 0.119 | 0.143 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 28.30 | 0.00771 |
T S1 APARTMENT | 2200.86 | 2641.03 | 0.172 | 0.207 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 28.30 | 0.00771 |
T S2 APARTMENT | 2208.46 | 2650.15 | 0.173 | 0.208 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 28.30 | 0.00771 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 647.00 | 776.40 | 0.019 | 0.027 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
G NW APARTMENT | 645.15 | 774.18 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
OFFICE | 1635.16 | 1962.19 | 0.045 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 3.80 | 0.00496 |
G NE APARTMENT | 646.94 | 776.33 | 0.019 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
G N1 APARTMENT | 351.09 | 421.31 | 0.010 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
G N2 APARTMENT | 351.14 | 421.37 | 0.010 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
G S1 APARTMENT | 353.53 | 424.24 | 0.010 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
G S2 APARTMENT | 411.66 | 493.99 | 0.012 | 0.026 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M SW APARTMENT | 1013.84 | 1216.60 | 0.029 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M NW APARTMENT | 1007.46 | 1208.95 | 0.029 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M SE APARTMENT | 1018.89 | 1222.66 | 0.029 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M NE APARTMENT | 1012.50 | 1215.01 | 0.029 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M N1 APARTMENT | 207.93 | 249.52 | 0.006 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M N2 APARTMENT | 208.10 | 249.72 | 0.006 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M S1 APARTMENT | 221.12 | 265.34 | 0.006 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
M S2 APARTMENT | 221.28 | 265.54 | 0.006 | 0.052 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T SW APARTMENT | 1204.99 | 1445.99 | 0.035 | 0.042 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T NW APARTMENT | 1203.39 | 1444.06 | 0.035 | 0.042 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T SE APARTMENT | 1207.56 | 1449.07 | 0.035 | 0.042 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T NE APARTMENT | 1205.96 | 1447.15 | 0.035 | 0.042 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T N1 APARTMENT | 808.61 | 970.34 | 0.023 | 0.028 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T N2 APARTMENT | 808.69 | 970.43 | 0.023 | 0.028 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T S1 APARTMENT | 808.64 | 970.37 | 0.023 | 0.028 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
T S2 APARTMENT | 808.71 | 970.46 | 0.023 | 0.028 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 3.80 | 0.00496 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.14 | 0.14 | 0.03 | 0.03 |
SPLIT GNW | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT OFFICE | 0.44 | 0.44 | 0.05 | 0.05 |
SPLIT GNE | 0.08 | 0.08 | 0.03 | 0.03 |
SPLIT GN1 | 0.06 | 0.06 | 0.03 | 0.03 |
SPLIT GN2 | 0.06 | 0.06 | 0.03 | 0.03 |
SPLIT GS1 | 0.09 | 0.09 | 0.03 | 0.03 |
SPLIT GS2 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT MSW | 0.38 | 0.38 | 0.05 | 0.05 |
SPLIT MNW | 0.33 | 0.33 | 0.05 | 0.05 |
SPLIT MSE | 0.35 | 0.35 | 0.05 | 0.05 |
SPLIT MNE | 0.26 | 0.26 | 0.05 | 0.05 |
SPLIT MN1 | 0.19 | 0.19 | 0.05 | 0.05 |
SPLIT MN2 | 0.19 | 0.19 | 0.05 | 0.05 |
SPLIT MS1 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MS2 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TSW | 0.26 | 0.26 | 0.04 | 0.04 |
SPLIT TNW | 0.22 | 0.22 | 0.04 | 0.04 |
SPLIT TSE | 0.24 | 0.24 | 0.04 | 0.04 |
SPLIT TNE | 0.18 | 0.18 | 0.04 | 0.04 |
SPLIT TN1 | 0.14 | 0.14 | 0.03 | 0.03 |
SPLIT TN2 | 0.14 | 0.14 | 0.03 | 0.03 |
SPLIT TS1 | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT TS2 | 0.21 | 0.21 | 0.03 | 0.03 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 635.00 | 7312.50 | 0.00 |
G NW APARTMENT | 271.75 | 7844.00 | 0.00 |
OFFICE | 30.50 | 1673.75 | 0.00 |
G NE APARTMENT | 164.00 | 7954.25 | 0.00 |
G N1 APARTMENT | 56.25 | 8177.50 | 0.00 |
G N2 APARTMENT | 58.00 | 8188.75 | 0.00 |
G S1 APARTMENT | 424.25 | 7371.50 | 0.00 |
G S2 APARTMENT | 465.50 | 7271.00 | 0.00 |
M SW APARTMENT | 2853.25 | 2673.75 | 0.00 |
M NW APARTMENT | 1757.25 | 4718.00 | 0.00 |
M SE APARTMENT | 2806.25 | 2793.00 | 0.00 |
M NE APARTMENT | 1502.75 | 5051.25 | 0.00 |
M N1 APARTMENT | 1807.75 | 4185.50 | 0.00 |
M N2 APARTMENT | 1776.75 | 4254.50 | 0.00 |
M S1 APARTMENT | 3222.25 | 1512.75 | 0.00 |
M S2 APARTMENT | 3213.25 | 1528.50 | 0.00 |
T SW APARTMENT | 1899.25 | 5536.50 | 0.50 |
T NW APARTMENT | 1159.25 | 6712.75 | 8.00 |
T SE APARTMENT | 1856.00 | 5522.75 | 1.50 |
T NE APARTMENT | 1075.25 | 6827.75 | 8.50 |
T N1 APARTMENT | 968.75 | 6784.50 | 0.00 |
T N2 APARTMENT | 960.00 | 6799.50 | 0.00 |
T S1 APARTMENT | 1851.25 | 4994.25 | 0.00 |
T S2 APARTMENT | 1852.25 | 5003.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 3754.25 | 8224.50 | 9.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 6.75 | 0.00 | 6.75 | 0.00 |
G NW APARTMENT | 8.00 | 0.00 | 8.00 | 0.00 |
OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 16.25 | 0.00 | 16.25 | 0.00 |
G N1 APARTMENT | 24.50 | 0.00 | 24.50 | 0.00 |
G N2 APARTMENT | 23.00 | 0.00 | 23.00 | 0.00 |
G S1 APARTMENT | 9.50 | 0.00 | 9.50 | 0.00 |
G S2 APARTMENT | 9.00 | 0.00 | 9.00 | 0.00 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T N1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T N2 APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
T S1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T S2 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 88.25 | 0.00 | 88.25 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.208 | 0.000 | 0.119 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.208 | 0.000 | 0.116 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.520 | 0.224 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.208 | 0.000 | 0.116 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.125 | 0.000 | 0.115 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.125 | 0.000 | 0.115 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.125 | 0.000 | 0.119 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.125 | 0.000 | 0.119 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.300 | 0.000 | 0.151 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.300 | 0.000 | 0.150 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.300 | 0.000 | 0.151 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.299 | 0.000 | 0.150 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.181 | 0.000 | 0.150 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.181 | 0.000 | 0.150 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.181 | 0.000 | 0.151 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.181 | 0.000 | 0.151 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.396 | 0.000 | 0.173 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.395 | 0.000 | 0.172 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.396 | 0.000 | 0.174 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.395 | 0.000 | 0.172 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.239 | 0.000 | 0.172 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.239 | 0.000 | 0.172 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.239 | 0.000 | 0.174 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.239 | 0.000 | 0.174 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.503 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.374 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.370 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.374 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.370 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.370 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.370 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.378 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.378 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.342 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 385.28 | 0.00 | 01-JAN-00:15 | 30735.71 | 20-JAN-08:00 |
WaterSystems:Electricity | 385.28 | 0.00 | 01-JAN-00:15 | 30735.71 | 20-JAN-08:00 |
Water Heater:WaterSystems:Electricity | 385.28 | 0.00 | 01-JAN-00:15 | 30735.71 | 20-JAN-08:00 |
Fans:Electricity | 181.69 | 5761.33 | 02-JAN-07:15 | 5761.33 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
ElectricityPurchased:Plant | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
Cogeneration:ElectricityPurchased | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
ElectricityNet:Plant | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
Cogeneration:ElectricityNet | 1278.31 | 18873.94 | 01-JAN-03:15 | 74584.72 | 30-JUN-17:15 |
ExteriorLights:Electricity | 40.09 | 0.00 | 01-JAN-07:30 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.09 | 0.00 | 01-JAN-07:30 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 216.83 | 5761.33 | 02-JAN-07:15 | 21244.12 | 30-JUN-14:00 |
General:Fans:Electricity | 181.69 | 5761.33 | 02-JAN-07:15 | 5761.33 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 35.14 | 0.00 | 01-JAN-00:15 | 15482.79 | 30-JUN-14:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 51.19 | 0.00 | 03-JAN-12:00 | 37898.23 | 22-DEC-05:00 |
Gas:HVAC | 51.19 | 0.00 | 03-JAN-12:00 | 37898.23 | 22-DEC-05:00 |
Heating:Gas | 51.19 | 0.00 | 03-JAN-12:00 | 37898.23 | 22-DEC-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 441.16 | 1369.28 | 10-JUN-14:00 | 107313.30 | 30-JUN-16:45 |
EnergyTransfer:Building | 258.64 | 1309.18 | 24-JUN-13:45 | 48481.40 | 30-JUN-16:45 |
EnergyTransfer:Zone:G SW APARTMENT | 4.95 | 0.05 | 14-FEB-12:00 | 1433.63 | 15-SEP-15:15 |
Heating:EnergyTransfer | 18.91 | 0.00 | 01-JAN-12:45 | 24088.77 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.73 | 0.00 | 01-JAN-00:45 | 930.60 | 22-DEC-05:00 |
Cooling:EnergyTransfer | 239.73 | 442.95 | 01-APR-07:00 | 48002.36 | 30-JUN-16:45 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 4.22 | 0.00 | 01-JAN-00:15 | 1433.63 | 15-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 4.25 | 0.00 | 14-MAY-08:30 | 1247.70 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.56 | 0.00 | 01-JAN-12:45 | 1036.70 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 2.68 | 0.00 | 01-JAN-00:15 | 1247.70 | 30-JUN-16:45 |
EnergyTransfer:Zone:OFFICE | 19.53 | 0.01 | 25-JUN-01:15 | 3696.73 | 04-SEP-13:15 |
Heating:EnergyTransfer:Zone:OFFICE | 1.11 | 0.00 | 01-JAN-00:15 | 669.55 | 30-JUN-14:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 18.42 | 0.00 | 01-JAN-15:15 | 3696.73 | 04-SEP-13:15 |
EnergyTransfer:Zone:G NE APARTMENT | 4.60 | 0.01 | 09-OCT-12:15 | 1039.09 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.55 | 0.00 | 01-JAN-08:30 | 1039.09 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 3.06 | 0.00 | 01-JAN-00:15 | 870.47 | 30-JUN-16:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 4.36 | 0.06 | 25-APR-11:30 | 690.57 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.47 | 0.00 | 01-JAN-07:15 | 554.88 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 3.89 | 0.00 | 01-JAN-00:15 | 690.57 | 30-JUN-16:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 4.37 | 0.02 | 11-JUN-13:15 | 685.03 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.48 | 0.00 | 01-JAN-07:15 | 554.49 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 3.89 | 0.00 | 01-JAN-00:15 | 685.03 | 30-JUN-16:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 5.42 | 0.02 | 25-MAR-03:45 | 1050.12 | 16-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 450.41 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 5.30 | 0.00 | 01-JAN-04:30 | 1050.12 | 16-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 5.46 | 0.02 | 17-JAN-01:45 | 1126.75 | 16-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.12 | 0.00 | 01-JAN-00:15 | 454.06 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 5.34 | 0.00 | 01-JAN-04:30 | 1126.75 | 16-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 20.84 | 0.01 | 24-JUN-13:45 | 4337.87 | 02-APR-16:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.03 | 0.00 | 01-JAN-00:15 | 978.07 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 20.81 | 0.00 | 19-JAN-12:45 | 4337.87 | 02-APR-16:15 |
EnergyTransfer:Zone:M NW APARTMENT | 12.51 | 0.04 | 10-MAY-16:00 | 3917.24 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.27 | 0.00 | 01-JAN-00:15 | 2043.59 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 12.24 | 0.00 | 01-JAN-04:45 | 3917.24 | 30-JUN-16:45 |
EnergyTransfer:Zone:M SE APARTMENT | 20.95 | 0.12 | 10-JUN-13:30 | 3962.93 | 16-SEP-13:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.02 | 0.00 | 01-JAN-00:15 | 1009.46 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 20.93 | 0.00 | 19-JAN-12:45 | 3962.93 | 16-SEP-13:00 |
EnergyTransfer:Zone:M NE APARTMENT | 13.60 | 0.02 | 11-OCT-14:00 | 3050.21 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 2097.56 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 13.32 | 0.00 | 01-JAN-04:45 | 3050.21 | 30-JUN-16:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 16.25 | 0.48 | 01-MAR-15:45 | 2488.21 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 498.15 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 16.24 | 0.00 | 26-JAN-08:45 | 2488.21 | 30-JUN-16:45 |
EnergyTransfer:Zone:M N2 APARTMENT | 16.19 | 0.04 | 01-MAR-15:45 | 2479.30 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 511.43 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 16.19 | 0.00 | 26-JAN-08:45 | 2479.30 | 30-JUN-16:45 |
EnergyTransfer:Zone:M S1 APARTMENT | 25.44 | 5.51 | 17-MAY-14:30 | 3439.87 | 17-OCT-13:00 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 26.62 | 17-MAY-15:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 25.44 | 0.00 | 17-MAY-14:30 | 3439.87 | 17-OCT-13:00 |
EnergyTransfer:Zone:M S2 APARTMENT | 25.39 | 5.50 | 17-MAY-15:15 | 3449.40 | 17-OCT-13:00 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 28.02 | 17-MAY-15:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 25.39 | 0.00 | 17-MAY-14:30 | 3449.40 | 17-OCT-13:00 |
EnergyTransfer:Zone:T SW APARTMENT | 7.99 | 0.00 | 14-AUG-04:00 | 2787.22 | 02-APR-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.79 | 0.00 | 01-JAN-00:15 | 1885.28 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 6.20 | 0.00 | 01-JAN-01:30 | 2787.22 | 02-APR-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 6.19 | 0.00 | 08-OCT-23:15 | 2666.93 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 3.01 | 0.00 | 01-JAN-10:15 | 1869.56 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 3.18 | 0.00 | 01-JAN-00:15 | 2666.93 | 30-JUN-16:45 |
EnergyTransfer:Zone:T SE APARTMENT | 7.86 | 0.01 | 13-OCT-01:45 | 2649.80 | 16-SEP-13:30 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.71 | 0.00 | 01-JAN-00:15 | 1873.10 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 6.15 | 0.00 | 01-JAN-01:30 | 2649.80 | 16-SEP-13:30 |
EnergyTransfer:Zone:T NE APARTMENT | 6.43 | 0.01 | 16-AUG-10:00 | 2251.54 | 30-JUN-14:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 2.93 | 0.00 | 01-JAN-09:00 | 1824.13 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 3.50 | 0.00 | 01-JAN-00:15 | 2251.54 | 30-JUN-14:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 5.37 | 0.02 | 02-SEP-15:45 | 1817.66 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.00 | 0.00 | 01-JAN-09:30 | 1200.00 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 4.36 | 0.00 | 01-JAN-00:15 | 1817.66 | 30-JUN-16:45 |
EnergyTransfer:Zone:T N2 APARTMENT | 5.36 | 0.02 | 19-JUN-09:30 | 1805.31 | 30-JUN-16:45 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.01 | 0.00 | 01-JAN-09:30 | 1199.68 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 4.34 | 0.00 | 01-JAN-00:15 | 1805.31 | 30-JUN-16:45 |
EnergyTransfer:Zone:T S1 APARTMENT | 7.67 | 0.01 | 07-DEC-07:00 | 2239.53 | 16-SEP-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1026.70 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 7.32 | 0.00 | 01-JAN-04:00 | 2239.53 | 16-SEP-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 7.67 | 0.04 | 18-JUL-15:15 | 2246.50 | 16-SEP-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.35 | 0.00 | 01-JAN-00:15 | 1027.34 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 7.32 | 0.00 | 01-JAN-04:00 | 2246.50 | 16-SEP-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 182.52 | 0.00 | 01-APR-06:30 | 60669.53 | 03-AUG-14:30 |
HeatingCoils:EnergyTransfer | 40.95 | 0.00 | 03-JAN-12:00 | 30318.58 | 22-DEC-05:00 |
CoolingCoils:EnergyTransfer | 141.57 | 0.00 | 01-JAN-00:15 | 60669.53 | 03-AUG-14:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.730 | -4.222 | 0.000 | 0.000 | 3.899 | 1.087 | 12.213 | 11.342 | 0.000 | 0.027 | 0.000 | 0.000 | -5.711 | 0.000 | -6.765 | -12.599 |
G NW APARTMENT | 1.565 | -2.680 | 0.000 | 0.000 | 3.945 | 1.087 | 12.213 | 5.539 | 0.000 | 0.028 | 0.000 | 0.000 | -5.643 | 0.000 | -6.415 | -9.639 |
OFFICE | 1.112 | -18.416 | 0.000 | 0.000 | 0.518 | 26.452 | 9.482 | 10.813 | 0.000 | 0.016 | 0.000 | 0.000 | -6.005 | 0.000 | -5.473 | -18.498 |
G NE APARTMENT | 1.549 | -3.056 | 0.000 | 0.000 | 3.965 | 1.087 | 12.213 | 5.160 | 0.000 | 0.028 | 0.000 | 0.000 | -5.465 | 0.000 | -6.329 | -9.151 |
G N1 APARTMENT | 0.473 | -3.891 | 0.000 | 0.000 | 3.955 | 1.087 | 12.213 | 1.684 | 0.000 | 0.022 | 0.000 | 0.000 | -3.448 | 0.000 | -4.409 | -7.686 |
G N2 APARTMENT | 0.475 | -3.894 | 0.000 | 0.000 | 3.957 | 1.087 | 12.213 | 1.684 | 0.000 | 0.022 | 0.000 | 0.000 | -3.445 | 0.000 | -4.406 | -7.691 |
G S1 APARTMENT | 0.124 | -5.298 | 0.000 | 0.000 | 3.888 | 1.087 | 12.213 | 7.570 | 0.000 | 0.019 | 0.000 | 0.000 | -3.532 | 0.000 | -4.783 | -11.288 |
G S2 APARTMENT | 0.119 | -5.342 | 0.000 | 0.000 | 3.882 | 1.087 | 12.213 | 7.560 | 0.000 | 0.019 | 0.000 | 0.000 | -3.542 | 0.000 | -4.810 | -11.186 |
M SW APARTMENT | 0.028 | -20.807 | 0.000 | 0.000 | 3.616 | 1.087 | 12.213 | 10.562 | 0.000 | 0.038 | 10.657 | 0.000 | -6.791 | 0.000 | -10.603 | 0.000 |
M NW APARTMENT | 0.268 | -12.243 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 4.894 | 0.000 | 0.038 | 6.732 | 0.000 | -6.576 | 0.000 | -10.134 | 0.000 |
M SE APARTMENT | 0.022 | -20.928 | 0.000 | 0.000 | 3.627 | 1.087 | 12.213 | 10.281 | 0.000 | 0.038 | 10.907 | 0.000 | -6.676 | 0.000 | -10.571 | 0.000 |
M NE APARTMENT | 0.276 | -13.322 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 4.545 | 0.000 | 0.038 | 7.746 | 0.000 | -6.334 | 0.000 | -10.001 | 0.000 |
M N1 APARTMENT | 0.006 | -16.242 | 0.000 | 0.000 | 3.682 | 1.087 | 12.213 | 1.302 | 0.000 | 0.027 | 9.249 | 0.000 | -4.148 | 0.000 | -7.176 | 0.000 |
M N2 APARTMENT | 0.007 | -16.186 | 0.000 | 0.000 | 3.685 | 1.087 | 12.213 | 1.303 | 0.000 | 0.027 | 9.174 | 0.000 | -4.141 | 0.000 | -7.167 | 0.000 |
M S1 APARTMENT | 0.000 | -25.440 | 0.000 | 0.000 | 3.565 | 1.087 | 12.213 | 7.087 | 0.000 | 0.027 | 13.262 | 0.000 | -4.253 | 0.000 | -7.547 | 0.000 |
M S2 APARTMENT | 0.000 | -25.391 | 0.000 | 0.000 | 3.565 | 1.087 | 12.213 | 7.087 | 0.000 | 0.027 | 13.211 | 0.000 | -4.252 | 0.000 | -7.546 | 0.000 |
T SW APARTMENT | 1.789 | -6.197 | 0.000 | 0.000 | 3.805 | 1.087 | 12.213 | 10.513 | 0.000 | 0.050 | 0.000 | 0.000 | -6.096 | 0.000 | -12.693 | -4.469 |
T NW APARTMENT | 3.013 | -3.176 | 0.000 | 0.000 | 3.882 | 1.087 | 12.213 | 4.880 | 0.000 | 0.050 | 0.000 | 0.000 | -5.933 | 0.000 | -12.119 | -3.896 |
T SE APARTMENT | 1.711 | -6.146 | 0.000 | 0.000 | 3.820 | 1.087 | 12.213 | 10.275 | 0.000 | 0.050 | 0.000 | 0.000 | -6.011 | 0.000 | -12.673 | -4.326 |
T NE APARTMENT | 2.927 | -3.503 | 0.000 | 0.000 | 3.910 | 1.087 | 12.213 | 4.583 | 0.000 | 0.050 | 0.000 | 0.000 | -5.747 | 0.000 | -11.999 | -3.519 |
T N1 APARTMENT | 1.004 | -4.362 | 0.000 | 0.000 | 3.863 | 1.087 | 12.213 | 1.354 | 0.000 | 0.035 | 0.000 | 0.000 | -3.693 | 0.000 | -8.379 | -3.122 |
T N2 APARTMENT | 1.014 | -4.343 | 0.000 | 0.000 | 3.865 | 1.087 | 12.213 | 1.352 | 0.000 | 0.035 | 0.000 | 0.000 | -3.688 | 0.000 | -8.377 | -3.158 |
T S1 APARTMENT | 0.345 | -7.323 | 0.000 | 0.000 | 3.750 | 1.087 | 12.213 | 7.081 | 0.000 | 0.035 | 0.000 | 0.000 | -3.857 | 0.000 | -8.959 | -4.372 |
T S2 APARTMENT | 0.350 | -7.322 | 0.000 | 0.000 | 3.751 | 1.087 | 12.213 | 7.079 | 0.000 | 0.035 | 0.000 | 0.000 | -3.854 | 0.000 | -8.959 | -4.379 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.037 | 0.000 | 0.002 | 0.000 | 0.000 | -0.740 | 0.000 | -1.931 | -11.950 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.190 | 0.000 | 0.053 | 3.012 | 0.000 | -1.800 | 0.000 | -22.516 | -0.001 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.033 | 0.000 | 0.002 | 0.000 | 0.000 | -0.851 | 0.000 | -1.642 | -12.124 |
Total Facility | 18.907 | -239.730 | 0.000 | 0.000 | 87.873 | 95.189 | 296.854 | 145.790 | 0.000 | 0.835 | 83.949 | 0.000 | -122.232 | 0.000 | -224.380 | -143.055 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 15-SEP-15:15 | 0.00 | -1433.57 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 1797.19 | 0.00 | 122.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1051.72 |
G NW APARTMENT | 30-JUN-16:45 | 0.00 | -1247.61 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1369.63 | 0.00 | 207.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1067.73 |
OFFICE | 16-JUL-06:01 | 0.00 | -6683.86 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 130.67 | 0.00 | 0.00 | 5940.04 | 0.00 | 0.00 | 0.00 | -97.31 | 0.00 |
G NE APARTMENT | 30-JUN-16:45 | 0.00 | -870.40 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 378.86 | 0.00 | 207.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -454.16 |
G N1 APARTMENT | 30-JUN-16:45 | 0.00 | -690.49 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 255.55 | 0.00 | 169.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -472.99 |
G N2 APARTMENT | 30-JUN-16:45 | 0.00 | -684.95 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 255.67 | 0.00 | 169.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -478.66 |
G S1 APARTMENT | 16-SEP-13:30 | 0.00 | -1049.88 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1317.18 | 0.00 | 88.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -792.54 |
G S2 APARTMENT | 16-SEP-13:30 | 0.00 | -1126.50 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1315.86 | 0.00 | 88.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -714.60 |
M SW APARTMENT | 02-APR-16:08 | 0.00 | -4338.84 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1720.51 | 0.00 | 89.62 | 1790.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 30-JUN-16:45 | 0.00 | -3917.10 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1328.38 | 0.00 | 290.48 | 1559.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 16-SEP-13:00 | 0.00 | -3961.93 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1593.37 | 0.00 | 218.59 | 1707.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 30-JUN-16:45 | 0.00 | -3050.08 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 354.60 | 0.00 | 290.47 | 1666.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 30-JUN-16:45 | 0.00 | -2488.02 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 237.47 | 0.00 | 236.67 | 1275.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 30-JUN-16:45 | 0.00 | -2479.11 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 237.53 | 0.00 | 236.67 | 1266.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 17-OCT-13:00 | 0.00 | -3439.89 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1792.17 | 0.00 | 0.00 | 1244.35 | 0.00 | 0.00 | 0.00 | -38.84 | 0.00 |
M S2 APARTMENT | 17-OCT-13:00 | 0.00 | -3449.43 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1792.11 | 0.00 | 0.00 | 1253.95 | 0.00 | 0.00 | 0.00 | -38.84 | 0.00 |
T SW APARTMENT | 02-APR-16:15 | 0.00 | -2787.99 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1680.30 | 0.00 | 117.29 | 252.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 30-JUN-16:45 | 0.00 | -2666.92 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1281.76 | 0.00 | 374.70 | 272.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 16-SEP-13:30 | 0.00 | -2649.24 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1499.63 | 0.00 | 276.88 | 436.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 30-JUN-14:15 | 0.00 | -2251.57 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 617.08 | 0.00 | 394.89 | 775.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 30-JUN-16:45 | 0.00 | -1817.61 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 222.26 | 0.00 | 304.78 | 552.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 30-JUN-16:45 | 0.00 | -1805.26 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 222.47 | 0.00 | 304.78 | 539.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 16-SEP-13:30 | 0.00 | -2239.07 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1274.18 | 0.00 | 167.02 | 361.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 16-SEP-13:30 | 0.00 | -2246.04 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1274.06 | 0.00 | 167.02 | 368.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-16:45 | 0.00 | -47521.66 | 0.00 | 0.00 | 1949.43 | 3295.01 | 14142.04 | 12328.35 | 0.00 | 6157.09 | 9727.81 | 0.00 | 0.00 | 0.00 | -78.07 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 27-MAR-06:01 | 1255.56 | 0.00 | 0.00 | 0.00 | 162.85 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -295.76 | 0.00 | -110.87 | -1436.54 |
G NW APARTMENT | 16-FEB-07:01 | 1207.64 | 0.00 | 0.00 | 0.00 | 162.97 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -303.54 | 0.00 | -118.04 | -1373.80 |
OFFICE | 29-JAN-07:01 | 2338.07 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -473.45 | 0.00 | -181.60 | -2393.47 |
G NE APARTMENT | 30-MAY-06:01 | 1181.13 | 0.00 | 0.00 | 0.00 | 163.29 | 42.16 | 382.60 | 292.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -163.48 | -1897.72 |
G N1 APARTMENT | 17-JAN-07:01 | 1193.15 | 0.00 | 0.00 | 0.00 | 163.00 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -172.97 | 0.00 | -98.39 | -1509.54 |
G N2 APARTMENT | 24-DEC-17:01 | 1209.27 | 0.00 | 0.00 | 0.00 | 99.64 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -192.45 | 0.00 | -192.09 | -1577.85 |
G S1 APARTMENT | 28-APR-06:01 | 1183.60 | 0.00 | 0.00 | 0.00 | 163.20 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -140.88 | 0.00 | -189.49 | -1441.19 |
G S2 APARTMENT | 05-JAN-07:01 | 1064.86 | 0.00 | 0.00 | 0.00 | 161.34 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -276.46 | 0.00 | -100.88 | -1273.62 |
M SW APARTMENT | 22-DEC-05:00 | 977.99 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 279.64 | 0.00 | -448.87 | 0.00 | -1241.56 | 0.00 |
M NW APARTMENT | 22-DEC-05:00 | 2043.43 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -439.07 | 0.00 | -1241.56 | -795.60 |
M SE APARTMENT | 22-DEC-05:00 | 1009.38 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 242.89 | 0.00 | -443.52 | 0.00 | -1241.56 | 0.00 |
M NE APARTMENT | 22-DEC-05:00 | 2097.38 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -433.51 | 0.00 | -1241.56 | -855.12 |
M N1 APARTMENT | 22-DEC-05:00 | 498.12 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 88.15 | 0.00 | -270.19 | 0.00 | -748.88 | 0.00 |
M N2 APARTMENT | 22-DEC-05:00 | 511.39 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 74.73 | 0.00 | -270.05 | 0.00 | -748.88 | 0.00 |
M S1 APARTMENT | 17-MAY-15:00 | 26.62 | 0.00 | 0.00 | 0.00 | 40.85 | 22.70 | 400.26 | 117.86 | 0.00 | 0.00 | 23.33 | 0.00 | 0.00 | 0.00 | -631.63 | 0.00 |
M S2 APARTMENT | 17-MAY-15:00 | 28.02 | 0.00 | 0.00 | 0.00 | 40.86 | 22.70 | 400.26 | 117.89 | 0.00 | 0.00 | 21.80 | 0.00 | 0.00 | 0.00 | -631.52 | 0.00 |
T SW APARTMENT | 22-DEC-05:00 | 1885.13 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -414.78 | 0.00 | -1647.27 | -255.88 |
T NW APARTMENT | 22-DEC-05:00 | 1869.40 | 0.00 | 0.00 | 0.00 | 190.32 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.16 | 0.00 | -1622.87 | -266.83 |
T SE APARTMENT | 22-DEC-05:00 | 1872.94 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -410.26 | 0.00 | -1645.62 | -249.87 |
T NE APARTMENT | 22-DEC-05:00 | 1823.97 | 0.00 | 0.00 | 0.00 | 190.89 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -408.00 | 0.00 | -1612.66 | -237.34 |
T N1 APARTMENT | 08-DEC-07:01 | 1267.38 | 0.00 | 0.00 | 0.00 | 162.64 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -200.06 | 0.00 | 0.00 | -1654.72 |
T N2 APARTMENT | 08-DEC-07:01 | 1267.76 | 0.00 | 0.00 | 0.00 | 162.64 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -200.03 | 0.00 | 0.00 | -1655.13 |
T S1 APARTMENT | 22-DEC-05:00 | 1026.62 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.14 | 0.00 | -993.63 | -213.66 |
T S2 APARTMENT | 22-DEC-05:00 | 1027.27 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -252.13 | 0.00 | -993.63 | -214.32 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-DEC-05:00 | 23101.28 | 0.00 | 0.00 | 0.00 | 4354.15 | 2250.82 | 5427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8345.90 | 0.00 | -24634.44 | -2153.08 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Sec1.1A-General InformationData | |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 88.25 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 88.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 51.19 | 37898.23 | 0.00 | 0.00 |
Space Cooling | 35.14 | 13114.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 181.69 | 5761.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 385.28 | 24098.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1278.31 | 51.19 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1278.31 |
Natural Gas | 0.00 | 51.19 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1329.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 11.21 |
Fans-Interior | 57.96 |
Service Water Heating | 122.91 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.79 |
Subtotal | 407.81 |
Natural Gas [MJ/m2] | |
Space Heating | 16.33 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 16.33 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 8.91 |
Space Heating | 3.85 |
Space Cooling | 2.64 |
Fans-Interior | 13.67 |
Service Water Heating | 28.98 |
Receptacle Equipment | 38.94 |
Miscellaneous | 3.02 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.137721 |
G NW APARTMENT DIRECT AIR | 0.116462 |
OFFICE DIRECT AIR | 0.438618 |
G NE APARTMENT DIRECT AIR | 0.084590 |
G N1 APARTMENT DIRECT AIR | 0.061702 |
G N2 APARTMENT DIRECT AIR | 0.060973 |
G S1 APARTMENT DIRECT AIR | 0.094495 |
G S2 APARTMENT DIRECT AIR | 0.097774 |
M SW APARTMENT DIRECT AIR | 0.383513 |
M NW APARTMENT DIRECT AIR | 0.327948 |
M SE APARTMENT DIRECT AIR | 0.351898 |
M NE APARTMENT DIRECT AIR | 0.257804 |
M N1 APARTMENT DIRECT AIR | 0.194211 |
M N2 APARTMENT DIRECT AIR | 0.192902 |
M S1 APARTMENT DIRECT AIR | 0.278827 |
M S2 APARTMENT DIRECT AIR | 0.279880 |
T SW APARTMENT DIRECT AIR | 0.262034 |
T NW APARTMENT DIRECT AIR | 0.219499 |
T SE APARTMENT DIRECT AIR | 0.244228 |
T NE APARTMENT DIRECT AIR | 0.178054 |
T N1 APARTMENT DIRECT AIR | 0.142639 |
T N2 APARTMENT DIRECT AIR | 0.142912 |
T S1 APARTMENT DIRECT AIR | 0.206837 |
T S2 APARTMENT DIRECT AIR | 0.207551 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.137721 |
SPLIT GNW MAIN BRANCH | 0.116462 |
SPLIT OFFICE MAIN BRANCH | 0.438618 |
SPLIT GNE MAIN BRANCH | 0.084590 |
SPLIT GN1 MAIN BRANCH | 0.061702 |
SPLIT GN2 MAIN BRANCH | 0.060973 |
SPLIT GS1 MAIN BRANCH | 0.094495 |
SPLIT GS2 MAIN BRANCH | 0.097774 |
SPLIT MSW MAIN BRANCH | 0.383513 |
SPLIT MNW MAIN BRANCH | 0.327948 |
SPLIT MSE MAIN BRANCH | 0.351898 |
SPLIT MNE MAIN BRANCH | 0.257804 |
SPLIT MN1 MAIN BRANCH | 0.194211 |
SPLIT MN2 MAIN BRANCH | 0.192902 |
SPLIT MS1 MAIN BRANCH | 0.278827 |
SPLIT MS2 MAIN BRANCH | 0.279880 |
SPLIT TSW MAIN BRANCH | 0.262034 |
SPLIT TNW MAIN BRANCH | 0.219499 |
SPLIT TSE MAIN BRANCH | 0.244228 |
SPLIT TNE MAIN BRANCH | 0.178054 |
SPLIT TN1 MAIN BRANCH | 0.142639 |
SPLIT TN2 MAIN BRANCH | 0.142912 |
SPLIT TS1 MAIN BRANCH | 0.206837 |
SPLIT TS2 MAIN BRANCH | 0.207551 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.137721 |
SPLIT GNW | 0.116462 |
SPLIT OFFICE | 0.438618 |
SPLIT GNE | 0.084590 |
SPLIT GN1 | 0.061702 |
SPLIT GN2 | 0.060973 |
SPLIT GS1 | 0.094495 |
SPLIT GS2 | 0.097774 |
SPLIT MSW | 0.383513 |
SPLIT MNW | 0.327948 |
SPLIT MSE | 0.351898 |
SPLIT MNE | 0.257804 |
SPLIT MN1 | 0.194211 |
SPLIT MN2 | 0.192902 |
SPLIT MS1 | 0.278827 |
SPLIT MS2 | 0.279880 |
SPLIT TSW | 0.262034 |
SPLIT TNW | 0.219499 |
SPLIT TSE | 0.244228 |
SPLIT TNE | 0.178054 |
SPLIT TN1 | 0.142639 |
SPLIT TN2 | 0.142912 |
SPLIT TS1 | 0.206837 |
SPLIT TS2 | 0.207551 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.137721 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.116462 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.438618 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.084590 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.061702 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.060973 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.094495 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.097774 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.383513 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.327948 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.351898 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.257804 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.194211 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.192902 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.278827 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.279880 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.262034 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.219499 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.244228 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.178054 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.142639 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.142912 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.206837 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.207551 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.137721 | 2279.77 | 0.798655 |
SPLIT GNW COOLING COIL | 0.116462 | 1927.86 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.438618 | 7260.69 | 0.798655 |
SPLIT GNE COOLING COIL | 0.084590 | 1400.27 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.061702 | 1021.38 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.060973 | 1009.31 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.094495 | 1564.23 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.097774 | 1618.51 | 0.798655 |
SPLIT MSW COOLING COIL | 0.383513 | 6348.50 | 0.798655 |
SPLIT MNW COOLING COIL | 0.327948 | 5428.70 | 0.798655 |
SPLIT MSE COOLING COIL | 0.351898 | 5825.16 | 0.798655 |
SPLIT MNE COOLING COIL | 0.257804 | 4267.57 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.194211 | 3214.88 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.192902 | 3193.22 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.278827 | 4615.58 | 0.798655 |
SPLIT MS2 COOLING COIL | 0.279880 | 4633.00 | 0.798655 |
SPLIT TSW COOLING COIL | 0.262034 | 4337.59 | 0.798655 |
SPLIT TNW COOLING COIL | 0.219499 | 3633.49 | 0.798655 |
SPLIT TSE COOLING COIL | 0.244228 | 4042.85 | 0.798655 |
SPLIT TNE COOLING COIL | 0.178054 | 2947.42 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.142639 | 2361.19 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.142912 | 2365.69 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.206837 | 3423.89 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.207551 | 3435.71 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.137721 | 0.137721 | 0.137721 | 0.137721 | 1503.52 | 2279.77 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.116462 | 0.116462 | 0.116462 | 0.116462 | 1450.67 | 1927.86 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.438618 | 0.438618 | 0.438618 | 0.438618 | 2694.04 | 7260.69 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.084590 | 0.084590 | 0.084590 | 0.084590 | 1450.67 | 1400.27 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.061702 | 0.061702 | 0.061702 | 0.061702 | 1450.67 | 1021.38 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.060973 | 0.060973 | 0.060973 | 0.060973 | 1450.67 | 1009.31 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.094495 | 0.094495 | 0.094495 | 0.094495 | 1450.67 | 1564.23 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.097774 | 0.097774 | 0.097774 | 0.097774 | 1450.67 | 1618.51 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.383513 | 0.383513 | 0.383513 | 0.383513 | 2901.34 | 6348.50 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.327948 | 0.327948 | 0.327948 | 0.327948 | 2901.34 | 5428.70 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.351898 | 0.351898 | 0.351898 | 0.351898 | 2901.34 | 5825.16 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.257804 | 0.257804 | 0.257804 | 0.257804 | 2901.34 | 4267.57 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.194211 | 0.194211 | 0.194211 | 0.194211 | 2901.34 | 3214.88 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.192902 | 0.192902 | 0.192902 | 0.192902 | 2901.34 | 3193.22 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.278827 | 0.278827 | 0.278827 | 0.278827 | 2901.34 | 4615.58 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.279880 | 0.279880 | 0.279880 | 0.279880 | 2901.34 | 4633.00 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.262034 | 0.262034 | 0.262034 | 0.262034 | 1986.95 | 4337.59 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.219499 | 0.219499 | 0.219499 | 0.219499 | 1985.05 | 3633.49 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.244228 | 0.244228 | 0.244228 | 0.244228 | 1989.98 | 4042.85 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.178054 | 0.178054 | 0.178054 | 0.178054 | 1988.10 | 2947.42 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.142639 | 0.142639 | 0.142639 | 0.142639 | 1518.25 | 2361.19 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.142912 | 0.142912 | 0.142912 | 0.142912 | 1518.34 | 2365.69 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.206837 | 0.206837 | 0.206837 | 0.206837 | 1518.27 | 3423.89 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.207551 | 0.207551 | 0.207551 | 0.207551 | 1518.36 | 3435.71 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.137721 |
SPLIT GNW SUPPLY FAN | 0.116462 |
SPLIT OFFICE SUPPLY FAN | 0.438618 |
SPLIT GNE SUPPLY FAN | 0.084590 |
SPLIT GN1 SUPPLY FAN | 0.061702 |
SPLIT GN2 SUPPLY FAN | 0.060973 |
SPLIT GS1 SUPPLY FAN | 0.094495 |
SPLIT GS2 SUPPLY FAN | 0.097774 |
SPLIT MSW SUPPLY FAN | 0.383513 |
SPLIT MNW SUPPLY FAN | 0.327948 |
SPLIT MSE SUPPLY FAN | 0.351898 |
SPLIT MNE SUPPLY FAN | 0.257804 |
SPLIT MN1 SUPPLY FAN | 0.194211 |
SPLIT MN2 SUPPLY FAN | 0.192902 |
SPLIT MS1 SUPPLY FAN | 0.278827 |
SPLIT MS2 SUPPLY FAN | 0.279880 |
SPLIT TSW SUPPLY FAN | 0.262034 |
SPLIT TNW SUPPLY FAN | 0.219499 |
SPLIT TSE SUPPLY FAN | 0.244228 |
SPLIT TNE SUPPLY FAN | 0.178054 |
SPLIT TN1 SUPPLY FAN | 0.142639 |
SPLIT TN2 SUPPLY FAN | 0.142912 |
SPLIT TS1 SUPPLY FAN | 0.206837 |
SPLIT TS2 SUPPLY FAN | 0.207551 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1503.52 |
SPLIT GNW HEATING COIL | 1450.67 |
SPLIT OFFICE HEATING COIL | 2694.04 |
SPLIT GNE HEATING COIL | 1450.67 |
SPLIT GN1 HEATING COIL | 1450.67 |
SPLIT GN2 HEATING COIL | 1450.67 |
SPLIT GS1 HEATING COIL | 1450.67 |
SPLIT GS2 HEATING COIL | 1450.67 |
SPLIT MSW HEATING COIL | 2901.34 |
SPLIT MNW HEATING COIL | 2901.34 |
SPLIT MSE HEATING COIL | 2901.34 |
SPLIT MNE HEATING COIL | 2901.34 |
SPLIT MN1 HEATING COIL | 2901.34 |
SPLIT MN2 HEATING COIL | 2901.34 |
SPLIT MS1 HEATING COIL | 2901.34 |
SPLIT MS2 HEATING COIL | 2901.34 |
SPLIT TSW HEATING COIL | 1986.95 |
SPLIT TNW HEATING COIL | 1985.05 |
SPLIT TSE HEATING COIL | 1989.98 |
SPLIT TNE HEATING COIL | 1988.10 |
SPLIT TN1 HEATING COIL | 1518.25 |
SPLIT TN2 HEATING COIL | 1518.34 |
SPLIT TS1 HEATING COIL | 1518.27 |
SPLIT TS2 HEATING COIL | 1518.36 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 9.60 |
February | 22.18 | 11.29 |
March | 22.30 | 12.66 |
April | 22.29 | 13.68 |
May | 22.40 | 15.00 |
June | 23.24 | 15.34 |
July | 23.70 | 15.94 |
August | 23.89 | 16.62 |
September | 23.99 | 16.72 |
October | 22.92 | 15.11 |
November | 22.38 | 12.79 |
December | 22.10 | 10.66 |
Annual Sum or Average | 22.77 | 13.79 |
Minimum of Months | 21.88 | 9.60 |
Maximum of Months | 23.99 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.78 | 11.29 |
March | 21.89 | 12.66 |
April | 22.01 | 13.68 |
May | 22.25 | 15.00 |
June | 23.15 | 15.34 |
July | 23.57 | 15.94 |
August | 23.70 | 16.62 |
September | 23.68 | 16.72 |
October | 22.33 | 15.11 |
November | 21.86 | 12.79 |
December | 21.72 | 10.66 |
Annual Sum or Average | 22.47 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 23.70 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.52 | 9.60 |
February | 23.01 | 11.29 |
March | 23.16 | 12.66 |
April | 23.34 | 13.68 |
May | 23.52 | 15.00 |
June | 24.33 | 15.34 |
July | 24.76 | 15.94 |
August | 24.91 | 16.62 |
September | 25.21 | 16.72 |
October | 24.06 | 15.11 |
November | 23.37 | 12.79 |
December | 22.88 | 10.66 |
Annual Sum or Average | 23.76 | 13.79 |
Minimum of Months | 22.52 | 9.60 |
Maximum of Months | 25.21 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.75 | 11.29 |
March | 21.85 | 12.66 |
April | 21.98 | 13.68 |
May | 22.20 | 15.00 |
June | 23.06 | 15.34 |
July | 23.46 | 15.94 |
August | 23.60 | 16.62 |
September | 23.56 | 16.72 |
October | 22.26 | 15.11 |
November | 21.82 | 12.79 |
December | 21.70 | 10.66 |
Annual Sum or Average | 22.41 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 23.60 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.74 | 11.29 |
March | 21.80 | 12.66 |
April | 21.89 | 13.68 |
May | 22.08 | 15.00 |
June | 23.08 | 15.34 |
July | 23.48 | 15.94 |
August | 23.64 | 16.62 |
September | 23.63 | 16.72 |
October | 22.23 | 15.11 |
November | 21.81 | 12.79 |
December | 21.71 | 10.66 |
Annual Sum or Average | 22.40 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 23.64 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 9.60 |
February | 21.74 | 11.29 |
March | 21.80 | 12.66 |
April | 21.89 | 13.68 |
May | 22.08 | 15.00 |
June | 23.08 | 15.34 |
July | 23.47 | 15.94 |
August | 23.63 | 16.62 |
September | 23.62 | 16.72 |
October | 22.23 | 15.11 |
November | 21.81 | 12.79 |
December | 21.71 | 10.66 |
Annual Sum or Average | 22.40 | 13.79 |
Minimum of Months | 21.70 | 9.60 |
Maximum of Months | 23.63 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 9.60 |
February | 22.22 | 11.29 |
March | 22.30 | 12.66 |
April | 22.23 | 13.68 |
May | 22.32 | 15.00 |
June | 23.28 | 15.34 |
July | 23.73 | 15.94 |
August | 23.96 | 16.62 |
September | 24.08 | 16.72 |
October | 23.01 | 15.11 |
November | 22.47 | 12.79 |
December | 22.17 | 10.66 |
Annual Sum or Average | 22.81 | 13.79 |
Minimum of Months | 21.91 | 9.60 |
Maximum of Months | 24.08 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 9.60 |
February | 22.24 | 11.29 |
March | 22.32 | 12.66 |
April | 22.27 | 13.68 |
May | 22.36 | 15.00 |
June | 23.32 | 15.34 |
July | 23.77 | 15.94 |
August | 23.99 | 16.62 |
September | 24.11 | 16.72 |
October | 23.06 | 15.11 |
November | 22.51 | 12.79 |
December | 22.19 | 10.66 |
Annual Sum or Average | 22.84 | 13.79 |
Minimum of Months | 21.93 | 9.60 |
Maximum of Months | 24.11 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 9.60 |
February | 23.83 | 11.29 |
March | 23.92 | 12.66 |
April | 23.98 | 13.68 |
May | 24.10 | 15.00 |
June | 24.08 | 15.34 |
July | 24.30 | 15.94 |
August | 24.36 | 16.62 |
September | 24.38 | 16.72 |
October | 24.30 | 15.11 |
November | 24.16 | 12.79 |
December | 23.72 | 10.66 |
Annual Sum or Average | 24.02 | 13.79 |
Minimum of Months | 23.09 | 9.60 |
Maximum of Months | 24.38 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 9.60 |
February | 22.67 | 11.29 |
March | 23.20 | 12.66 |
April | 23.56 | 13.68 |
May | 23.93 | 15.00 |
June | 23.98 | 15.34 |
July | 24.23 | 15.94 |
August | 24.28 | 16.62 |
September | 24.28 | 16.72 |
October | 24.00 | 15.11 |
November | 23.54 | 12.79 |
December | 22.36 | 10.66 |
Annual Sum or Average | 23.51 | 13.79 |
Minimum of Months | 22.01 | 9.60 |
Maximum of Months | 24.28 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.04 | 9.60 |
February | 23.78 | 11.29 |
March | 23.87 | 12.66 |
April | 23.95 | 13.68 |
May | 24.07 | 15.00 |
June | 24.03 | 15.34 |
July | 24.27 | 15.94 |
August | 24.35 | 16.62 |
September | 24.37 | 16.72 |
October | 24.29 | 15.11 |
November | 24.14 | 12.79 |
December | 23.68 | 10.66 |
Annual Sum or Average | 23.99 | 13.79 |
Minimum of Months | 23.04 | 9.60 |
Maximum of Months | 24.37 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 9.60 |
February | 22.48 | 11.29 |
March | 23.05 | 12.66 |
April | 23.44 | 13.68 |
May | 23.86 | 15.00 |
June | 23.88 | 15.34 |
July | 24.14 | 15.94 |
August | 24.21 | 16.62 |
September | 24.19 | 16.72 |
October | 23.89 | 15.11 |
November | 23.42 | 12.79 |
December | 22.20 | 10.66 |
Annual Sum or Average | 23.39 | 13.79 |
Minimum of Months | 21.94 | 9.60 |
Maximum of Months | 24.21 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 9.60 |
February | 22.95 | 11.29 |
March | 23.41 | 12.66 |
April | 23.74 | 13.68 |
May | 24.04 | 15.00 |
June | 24.08 | 15.34 |
July | 24.27 | 15.94 |
August | 24.32 | 16.62 |
September | 24.31 | 16.72 |
October | 24.14 | 15.11 |
November | 23.86 | 12.79 |
December | 22.66 | 10.66 |
Annual Sum or Average | 23.67 | 13.79 |
Minimum of Months | 22.23 | 9.60 |
Maximum of Months | 24.32 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 9.60 |
February | 22.92 | 11.29 |
March | 23.39 | 12.66 |
April | 23.72 | 13.68 |
May | 24.03 | 15.00 |
June | 24.07 | 15.34 |
July | 24.26 | 15.94 |
August | 24.31 | 16.62 |
September | 24.31 | 16.72 |
October | 24.13 | 15.11 |
November | 23.85 | 12.79 |
December | 22.64 | 10.66 |
Annual Sum or Average | 23.66 | 13.79 |
Minimum of Months | 22.22 | 9.60 |
Maximum of Months | 24.31 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 9.60 |
February | 24.16 | 11.29 |
March | 24.17 | 12.66 |
April | 24.21 | 13.68 |
May | 24.24 | 15.00 |
June | 24.22 | 15.34 |
July | 24.36 | 15.94 |
August | 24.39 | 16.62 |
September | 24.39 | 16.72 |
October | 24.38 | 15.11 |
November | 24.33 | 12.79 |
December | 24.10 | 10.66 |
Annual Sum or Average | 24.22 | 13.79 |
Minimum of Months | 23.69 | 9.60 |
Maximum of Months | 24.39 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 9.60 |
February | 24.16 | 11.29 |
March | 24.16 | 12.66 |
April | 24.20 | 13.68 |
May | 24.24 | 15.00 |
June | 24.22 | 15.34 |
July | 24.36 | 15.94 |
August | 24.39 | 16.62 |
September | 24.39 | 16.72 |
October | 24.38 | 15.11 |
November | 24.33 | 12.79 |
December | 24.10 | 10.66 |
Annual Sum or Average | 24.22 | 13.79 |
Minimum of Months | 23.69 | 9.60 |
Maximum of Months | 24.39 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 9.60 |
February | 22.75 | 11.29 |
March | 23.05 | 12.66 |
April | 23.13 | 13.68 |
May | 23.38 | 15.00 |
June | 23.36 | 15.34 |
July | 23.75 | 15.94 |
August | 23.92 | 16.62 |
September | 23.96 | 16.72 |
October | 23.58 | 15.11 |
November | 23.16 | 12.79 |
December | 22.63 | 10.66 |
Annual Sum or Average | 23.25 | 13.79 |
Minimum of Months | 22.25 | 9.60 |
Maximum of Months | 23.96 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 9.60 |
February | 22.12 | 11.29 |
March | 22.50 | 12.66 |
April | 22.81 | 13.68 |
May | 23.21 | 15.00 |
June | 23.24 | 15.34 |
July | 23.59 | 15.94 |
August | 23.70 | 16.62 |
September | 23.64 | 16.72 |
October | 22.97 | 15.11 |
November | 22.46 | 12.79 |
December | 21.92 | 10.66 |
Annual Sum or Average | 22.83 | 13.79 |
Minimum of Months | 21.79 | 9.60 |
Maximum of Months | 23.70 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 9.60 |
February | 22.73 | 11.29 |
March | 23.03 | 12.66 |
April | 23.13 | 13.68 |
May | 23.40 | 15.00 |
June | 23.34 | 15.34 |
July | 23.71 | 15.94 |
August | 23.89 | 16.62 |
September | 23.91 | 16.72 |
October | 23.55 | 15.11 |
November | 23.14 | 12.79 |
December | 22.60 | 10.66 |
Annual Sum or Average | 23.22 | 13.79 |
Minimum of Months | 22.23 | 9.60 |
Maximum of Months | 23.91 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 9.60 |
February | 22.05 | 11.29 |
March | 22.45 | 12.66 |
April | 22.76 | 13.68 |
May | 23.17 | 15.00 |
June | 23.17 | 15.34 |
July | 23.48 | 15.94 |
August | 23.59 | 16.62 |
September | 23.50 | 16.72 |
October | 22.88 | 15.11 |
November | 22.38 | 12.79 |
December | 21.83 | 10.66 |
Annual Sum or Average | 22.75 | 13.79 |
Minimum of Months | 21.75 | 9.60 |
Maximum of Months | 23.59 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 22.11 | 11.29 |
March | 22.53 | 12.66 |
April | 22.88 | 13.68 |
May | 23.31 | 15.00 |
June | 23.35 | 15.34 |
July | 23.71 | 15.94 |
August | 23.81 | 16.62 |
September | 23.75 | 16.72 |
October | 23.06 | 15.11 |
November | 22.51 | 12.79 |
December | 21.89 | 10.66 |
Annual Sum or Average | 22.90 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 23.81 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 9.60 |
February | 22.11 | 11.29 |
March | 22.53 | 12.66 |
April | 22.87 | 13.68 |
May | 23.31 | 15.00 |
June | 23.35 | 15.34 |
July | 23.70 | 15.94 |
August | 23.80 | 16.62 |
September | 23.73 | 16.72 |
October | 23.05 | 15.11 |
November | 22.50 | 12.79 |
December | 21.89 | 10.66 |
Annual Sum or Average | 22.89 | 13.79 |
Minimum of Months | 21.78 | 9.60 |
Maximum of Months | 23.80 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | 9.60 |
February | 23.00 | 11.29 |
March | 23.30 | 12.66 |
April | 23.38 | 13.68 |
May | 23.61 | 15.00 |
June | 23.58 | 15.34 |
July | 23.96 | 15.94 |
August | 24.10 | 16.62 |
September | 24.14 | 16.72 |
October | 23.85 | 15.11 |
November | 23.47 | 12.79 |
December | 22.87 | 10.66 |
Annual Sum or Average | 23.47 | 13.79 |
Minimum of Months | 22.43 | 9.60 |
Maximum of Months | 24.14 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | 9.60 |
February | 23.00 | 11.29 |
March | 23.30 | 12.66 |
April | 23.38 | 13.68 |
May | 23.61 | 15.00 |
June | 23.58 | 15.34 |
July | 23.95 | 15.94 |
August | 24.10 | 16.62 |
September | 24.13 | 16.72 |
October | 23.84 | 15.11 |
November | 23.46 | 12.79 |
December | 22.87 | 10.66 |
Annual Sum or Average | 23.47 | 13.79 |
Minimum of Months | 22.43 | 9.60 |
Maximum of Months | 24.13 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 9.60 |
February | 23.23 | 11.29 |
March | 23.80 | 12.66 |
April | 24.20 | 13.68 |
May | 24.66 | 15.00 |
June | 24.71 | 15.34 |
July | 25.15 | 15.94 |
August | 25.32 | 16.62 |
September | 25.30 | 16.72 |
October | 24.52 | 15.11 |
November | 23.74 | 12.79 |
December | 22.84 | 10.66 |
Annual Sum or Average | 24.17 | 13.79 |
Minimum of Months | 22.51 | 9.60 |
Maximum of Months | 25.32 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | 9.60 |
February | 21.14 | 11.29 |
March | 21.52 | 12.66 |
April | 21.83 | 13.68 |
May | 22.27 | 15.00 |
June | 23.49 | 15.34 |
July | 23.96 | 15.94 |
August | 24.21 | 16.62 |
September | 24.27 | 16.72 |
October | 22.59 | 15.11 |
November | 21.61 | 12.79 |
December | 20.91 | 10.66 |
Annual Sum or Average | 22.37 | 13.79 |
Minimum of Months | 20.54 | 9.60 |
Maximum of Months | 24.27 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:14
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.33 | 9.60 |
February | 25.04 | 11.29 |
March | 25.39 | 12.66 |
April | 25.65 | 13.68 |
May | 25.90 | 15.00 |
June | 25.91 | 15.34 |
July | 26.18 | 15.94 |
August | 26.27 | 16.62 |
September | 26.30 | 16.72 |
October | 26.06 | 15.11 |
November | 25.70 | 12.79 |
December | 24.80 | 10.66 |
Annual Sum or Average | 25.63 | 13.79 |
Minimum of Months | 24.33 | 9.60 |
Maximum of Months | 26.30 | 16.72 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:14
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.108086E+12 | 68311.889 | 26-JAN-18:45 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28386.685 | 0.000 | 0.000 | 0.000 |
February | 0.982863E+11 | 66048.942 | 26-FEB-18:45 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 459.684 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25664.055 | 0.000 | 0.000 | 0.000 |
March | 0.108889E+12 | 65224.602 | 06-MAR-18:45 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 1474.114 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23825.284 | 0.000 | 0.000 | 0.000 |
April | 0.104503E+12 | 69662.404 | 02-APR-17:15 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 11162.656 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21127.544 | 0.000 | 0.000 | 0.000 |
May | 0.107465E+12 | 66249.174 | 25-MAY-17:15 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 7650.096 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21226.874 | 0.000 | 0.000 | 0.000 |
June | 0.104301E+12 | 74584.723 | 30-JUN-17:15 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 13114.351 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24098.169 | 0.000 | 0.000 | 0.000 |
July | 0.107313E+12 | 65865.051 | 22-JUL-17:30 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 4447.521 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24045.326 | 0.000 | 0.000 | 0.000 |
August | 0.109795E+12 | 68614.138 | 02-AUG-16:30 | 4276.255 | 26730.986 | 5761.330 | 0.000 | 10633.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21211.863 | 0.000 | 0.000 | 0.000 |
September | 0.107146E+12 | 67517.879 | 15-SEP-17:30 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 10372.388 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19773.288 | 0.000 | 0.000 | 0.000 |
October | 0.109148E+12 | 66072.163 | 19-OCT-17:30 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 3657.196 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22489.763 | 0.000 | 0.000 | 0.000 |
November | 0.105161E+12 | 64897.074 | 15-NOV-18:15 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 2995.113 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21976.757 | 0.000 | 0.000 | 0.000 |
December | 0.108220E+12 | 65116.512 | 31-DEC-18:30 | 4979.953 | 26630.920 | 5761.330 | 0.000 | 334.364 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24856.945 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.127831E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.982863E+11 | 64897.074 | 4276.255 | 26630.920 | 5761.330 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19773.288 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.109795E+12 | 74584.723 | 4979.953 | 26730.986 | 5761.330 | 0.000 | 13114.351 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28386.685 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:14
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.166054E+11 | 27184.451 | 24-JAN-05:00 | 27184.451 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27184.451 |
February | 0.728016E+10 | 15181.670 | 02-FEB-04:45 | 15181.670 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15181.670 |
March | 0.565927E+10 | 17251.762 | 23-MAR-05:00 | 17251.762 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17251.762 |
April | 0.348115E+10 | 12591.906 | 23-APR-00:00 | 12591.906 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12591.906 |
May | 0.203283E+10 | 11225.377 | 31-MAY-02:00 | 11225.377 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11225.377 |
June | 0.492788E+09 | 6341.241 | 17-JUN-04:00 | 6341.241 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6341.241 |
July | 0.122055E+08 | 760.482 | 20-JUL-03:00 | 760.482 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 760.482 |
August | 0.150016E+08 | 1208.234 | 27-AUG-04:00 | 1208.234 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1208.234 |
September | 942255.366 | 159.420 | 07-SEP-01:00 | 159.420 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 159.420 |
October | 0.874836E+09 | 6575.229 | 31-OCT-04:00 | 6575.229 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6575.229 |
November | 0.346624E+10 | 16395.753 | 30-NOV-04:00 | 16395.753 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16395.753 |
December | 0.112646E+11 | 37898.226 | 22-DEC-04:00 | 37898.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37898.226 |
Annual Sum or Average | 0.511854E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 942255.366 | 159.420 | 159.420 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 159.420 | |
Maximum of Months | 0.166054E+11 | 37898.226 | 37898.226 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37898.226 |