Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2015-09-09 18:47:44


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2539.12 810.03 899.13
Net Site Energy 2539.12 810.03 899.13
Total Source Energy 5734.76 1829.50 2030.74
Net Source Energy 5734.76 1829.50 2030.74


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1107.35 0.00 0.00 0.00 0.00
Cooling 39.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 39.80 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 213.26 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 502.69 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1431.76 1107.35 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 1107.35 0.00 0.00 0.00 0.00
Cooling General 39.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 39.80 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 213.26 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 502.69 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.04 0.00 0.00 0.00 0.00 0.00
HVAC 267.65 392.13 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 507.00 392.13 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.49 0.00 0.00 0.00 0.00 0.00
HVAC 241.13 353.27 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 456.76 353.27 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1431.76 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1431.76 100.00
     
Total On-Site and Utility Electric Sources 1431.76 100.00
Total Electricity End Uses 1431.76 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 48.50
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 4621.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 11-AUG-17:00 29-JAN-00:15 - - - 01-JAN-07:15
Heating 0.00 158809.24 0.00 0.00 0.00 0.00
Cooling 12449.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6762.30 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 31245.45 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 82068.52 158809.24 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 158809.24 0.00 0.00 0.00 0.00
Cooling General 12449.90 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6762.30 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 31245.45 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1200.37 0.00 0.00 0.00
Cooling 126.37 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.06 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 675.38 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1592.01 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4534.39 1200.37 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 425.06 0.00 0.00 0.00
Cooling 44.75 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.64 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 239.16 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 563.75 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1605.68 425.06 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 425.06 0.00 0.00 0.00
Cooling 44.75 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.64 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 239.16 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 563.75 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1605.68 425.06 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.210 0.217 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.210 0.217 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.210 0.217 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.210 0.217 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.219 0.228 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.219 0.228 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.210 0.217 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.210 0.217 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.210 0.217 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 9.29 2.493 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 14.12 2.493 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.42_SHGC_0.45 4.65 0.00 0.00 4.65 4.65 2.493 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.42_SHGC_0.45 7.06 0.00 0.00 7.06 7.06 2.493 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 1.11 2.493 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.42_SHGC_0.45 3.32 0.00 0.00 3.32 3.32 2.493 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.42_SHGC_0.45 1.11 0.00 0.00 1.11 2.23 2.493 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.493 0.426 0.308              
North Total or Average           112.97 2.493 0.426 0.308              
Non-North Total or Average           193.95 2.493 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.06 83.06 39.80
Exterior Lighting Total 2553.00           39.80



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   2655.15 2120.55 534.60 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   1977.04 1578.97 398.07 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7302.21 5831.95 1470.26 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   1453.34 1160.71 292.62 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1100.63 879.03 221.61 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1082.61 864.64 217.98 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2015.54 1609.72 405.82 0.80 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2068.56 1652.07 416.49 0.80 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   8000.55 6389.68 1610.87 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   6173.73 4930.68 1243.05 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7715.21 6161.79 1553.42 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   5089.93 4065.10 1024.83 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3864.40 3086.32 778.08 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3830.60 3059.33 771.27 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6311.71 5040.88 1270.83 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6332.89 5057.80 1275.09 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5010.47 4001.64 1008.83 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3789.17 3026.24 762.93 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4813.97 3844.71 969.27 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2983.86 2383.07 600.78 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2281.37 1822.03 459.34 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2254.63 1800.67 453.96 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4153.09 3316.88 836.20 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4169.63 3330.10 839.53 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2529.4 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 1883.4 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6956.5 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1384.5 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1048.5 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1031.4 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1920.1 3.13 10.67 11.09 10.38
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1970.6 3.13 10.67 11.09 10.38
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7621.8 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5881.4 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7349.9 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4849.0 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3681.4 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3649.2 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6012.9 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6033.1 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4773.3 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3609.8 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4586.1 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2842.6 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2173.4 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2147.9 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3956.5 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3972.2 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   4743.27 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   4687.30 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   7957.76 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   4693.33 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   3903.99 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   3904.12 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   3892.09 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   4034.18 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   7769.23 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   7797.98 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   7785.25 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   7814.02 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   5966.13 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   5966.50 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   5941.02 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   5941.38 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   5650.78 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   5668.71 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   5659.62 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   5677.56 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   4753.68 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   4753.89 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   4734.38 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   4734.59 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 186.20 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 138.64 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 512.08 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.09 101.92 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.07 77.18 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.07 75.92 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 141.34 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 145.06 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 561.05 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.37 432.94 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 541.04 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.31 356.94 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 271.00 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 268.63 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 442.62 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 444.10 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 351.37 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.23 265.72 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 337.59 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 209.25 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 159.98 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 158.11 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 291.24 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 292.40 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1680.38 2016.46 0.134 0.160 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
G NW APARTMENT 1251.21 1501.46 0.100 0.119 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 23.42 0.00698
OFFICE 4527.29 5432.75 0.368 0.441 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 21.79 0.00698
G NE APARTMENT 919.77 1103.73 0.073 0.088 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
G N1 APARTMENT 696.55 835.86 0.055 0.066 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38 0.00698
G N2 APARTMENT 685.14 822.17 0.055 0.065 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38 0.00698
G S1 APARTMENT 1275.58 1530.70 0.101 0.122 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
G S2 APARTMENT 1309.14 1570.97 0.104 0.125 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
M SW APARTMENT 5063.40 6076.09 0.403 0.483 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 26.38 0.00698
M NW APARTMENT 3907.17 4688.61 0.311 0.373 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:45:00 22.58 0.00698
M SE APARTMENT 4882.81 5859.38 0.388 0.466 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
M NE APARTMENT 3221.31 3865.57 0.256 0.307 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.29 0.00698
M N1 APARTMENT 2445.63 2934.76 0.195 0.233 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38 0.00698
M N2 APARTMENT 2424.24 2909.09 0.193 0.231 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38 0.00698
M S1 APARTMENT 3994.53 4793.44 0.318 0.381 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
M S2 APARTMENT 4007.94 4809.53 0.319 0.383 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
T SW APARTMENT 3171.06 3805.27 0.252 0.303 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 26.58 0.00698
T NW APARTMENT 2398.09 2877.71 0.191 0.229 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 24.57 0.00698
T SE APARTMENT 3046.70 3656.04 0.242 0.291 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
T NE APARTMENT 1888.44 2266.13 0.150 0.180 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 25.31 0.00698
T N1 APARTMENT 1443.83 1732.59 0.115 0.138 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95 0.00698
T N2 APARTMENT 1426.90 1712.28 0.114 0.136 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95 0.00698
T S1 APARTMENT 2628.40 3154.09 0.209 0.251 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
T S2 APARTMENT 2638.87 3166.65 0.210 0.252 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2287.85 2745.42 0.067 0.080 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G NW APARTMENT 2301.10 2761.31 0.067 0.081 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
OFFICE 4336.83 5204.19 0.123 0.147 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G NE APARTMENT 2306.20 2767.43 0.067 0.081 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G N1 APARTMENT 1638.69 1966.42 0.048 0.057 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G N2 APARTMENT 1638.80 1966.55 0.048 0.057 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G S1 APARTMENT 1628.63 1954.35 0.048 0.057 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
G S2 APARTMENT 1748.78 2098.54 0.051 0.061 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
M SW APARTMENT 3244.61 3893.54 0.095 0.114 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M NW APARTMENT 3268.92 3922.71 0.096 0.115 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M SE APARTMENT 3258.15 3909.78 0.095 0.114 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M NE APARTMENT 3282.48 3938.98 0.096 0.115 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M N1 APARTMENT 1719.81 2063.77 0.050 0.060 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M N2 APARTMENT 1720.11 2064.14 0.050 0.060 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M S1 APARTMENT 1698.57 2038.28 0.050 0.060 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
M S2 APARTMENT 1698.87 2038.65 0.050 0.060 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T SW APARTMENT 3115.87 3739.05 0.091 0.109 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T NW APARTMENT 3131.03 3757.24 0.092 0.110 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T SE APARTMENT 3123.35 3748.01 0.091 0.110 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T NE APARTMENT 3138.52 3766.22 0.092 0.110 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T N1 APARTMENT 2357.23 2828.67 0.069 0.083 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T N2 APARTMENT 2357.41 2828.89 0.069 0.083 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T S1 APARTMENT 2340.91 2809.09 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006
T S2 APARTMENT 2341.09 2809.30 0.068 0.082 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -41.90 0.00006


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.16 0.16 0.08 0.08
SPLIT GNW 0.12 0.12 0.08 0.08
SPLIT OFFICE 0.44 0.44 0.15 0.15
SPLIT GNE 0.09 0.09 0.08 0.08
SPLIT GN1 0.07 0.07 0.06 0.06
SPLIT GN2 0.07 0.07 0.06 0.06
SPLIT GS1 0.12 0.12 0.06 0.06
SPLIT GS2 0.12 0.12 0.06 0.06
SPLIT MSW 0.48 0.48 0.11 0.11
SPLIT MNW 0.37 0.37 0.11 0.11
SPLIT MSE 0.47 0.47 0.11 0.11
SPLIT MNE 0.31 0.31 0.12 0.12
SPLIT MN1 0.23 0.23 0.06 0.06
SPLIT MN2 0.23 0.23 0.06 0.06
SPLIT MS1 0.38 0.38 0.06 0.06
SPLIT MS2 0.38 0.38 0.06 0.06
SPLIT TSW 0.30 0.30 0.11 0.11
SPLIT TNW 0.23 0.23 0.11 0.11
SPLIT TSE 0.29 0.29 0.11 0.11
SPLIT TNE 0.18 0.18 0.11 0.11
SPLIT TN1 0.14 0.14 0.08 0.08
SPLIT TN2 0.14 0.14 0.08 0.08
SPLIT TS1 0.25 0.25 0.08 0.08
SPLIT TS2 0.25 0.25 0.08 0.08



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 4443.25 7407.25 4031.00
G NW APARTMENT 4549.50 7772.50 4397.25
OFFICE 959.00 1816.00 909.75
G NE APARTMENT 4564.50 7661.50 4347.50
G N1 APARTMENT 4272.25 7968.75 4207.75
G N2 APARTMENT 4273.00 7964.50 4206.75
G S1 APARTMENT 4096.25 7445.50 3796.50
G S2 APARTMENT 4202.25 7363.00 3862.50
M SW APARTMENT 4219.75 5831.25 2890.50
M NW APARTMENT 4499.00 6426.25 3472.00
M SE APARTMENT 4268.25 5739.00 2812.75
M NE APARTMENT 4583.75 6324.75 3412.75
M N1 APARTMENT 3598.25 6384.75 2702.25
M N2 APARTMENT 3596.00 6365.25 2695.50
M S1 APARTMENT 3063.00 5603.25 1800.50
M S2 APARTMENT 3065.25 5596.75 1798.50
T SW APARTMENT 5234.25 6494.75 4064.00
T NW APARTMENT 5411.00 6928.25 4457.00
T SE APARTMENT 5269.25 6401.75 3997.00
T NE APARTMENT 5459.25 6879.25 4409.50
T N1 APARTMENT 5093.50 6977.50 4240.50
T N2 APARTMENT 5094.00 6970.75 4236.75
T S1 APARTMENT 4899.25 6386.75 3771.50
T S2 APARTMENT 4902.00 6374.75 3768.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 6318.50 7994.75 4621.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 4.25 0.00 4.25 0.00
G NW APARTMENT 3.25 0.00 3.25 0.00
OFFICE 29.25 0.50 0.75 0.00
G NE APARTMENT 2.25 0.00 2.25 0.00
G N1 APARTMENT 2.75 0.00 2.75 0.00
G N2 APARTMENT 1.00 0.00 1.00 0.00
G S1 APARTMENT 0.75 0.00 0.75 0.00
G S2 APARTMENT 1.75 0.00 1.75 0.00
M SW APARTMENT 6.75 0.00 6.75 0.00
M NW APARTMENT 12.50 0.00 12.50 0.00
M SE APARTMENT 7.75 0.00 7.75 0.00
M NE APARTMENT 13.25 0.00 13.25 0.00
M N1 APARTMENT 3.50 0.00 3.50 0.00
M N2 APARTMENT 3.50 0.00 3.50 0.00
M S1 APARTMENT 2.50 0.00 2.50 0.00
M S2 APARTMENT 2.50 0.00 2.50 0.00
T SW APARTMENT 5.00 0.00 5.00 0.00
T NW APARTMENT 12.75 0.00 12.75 0.00
T SE APARTMENT 6.00 0.00 6.00 0.00
T NE APARTMENT 13.00 0.00 13.00 0.00
T N1 APARTMENT 5.25 0.00 5.25 0.00
T N2 APARTMENT 5.75 0.00 5.75 0.00
T S1 APARTMENT 3.00 0.00 3.00 0.00
T S2 APARTMENT 2.75 0.00 2.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 77.00 0.50 48.50 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.367 0.114 0.000 0.044
G NW APARTMENT 1.71 2.50 268.97 0.354 0.114 0.000 0.043
OFFICE 0.94 1.00 268.97 0.520 0.110 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.354 0.114 0.000 0.043
G N1 APARTMENT 1.71 2.50 268.97 0.354 0.069 0.000 0.043
G N2 APARTMENT 1.71 2.50 268.97 0.354 0.069 0.000 0.043
G S1 APARTMENT 1.71 2.50 268.97 0.354 0.069 0.000 0.044
G S2 APARTMENT 1.71 2.50 268.97 0.354 0.069 0.000 0.044
M SW APARTMENT 1.71 2.50 268.97 0.354 0.164 0.000 0.051
M NW APARTMENT 1.71 2.50 268.97 0.354 0.164 0.000 0.052
M SE APARTMENT 1.71 2.50 268.97 0.354 0.164 0.000 0.051
M NE APARTMENT 1.71 2.50 268.97 0.354 0.164 0.000 0.052
M N1 APARTMENT 1.71 2.50 268.97 0.354 0.099 0.000 0.051
M N2 APARTMENT 1.71 2.50 268.97 0.354 0.099 0.000 0.051
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.099 0.000 0.051
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.099 0.000 0.051
T SW APARTMENT 1.71 2.50 268.97 0.354 0.217 0.000 0.057
T NW APARTMENT 1.71 2.50 268.97 0.354 0.217 0.000 0.057
T SE APARTMENT 1.71 2.50 268.97 0.354 0.217 0.000 0.057
T NE APARTMENT 1.71 2.50 268.97 0.354 0.217 0.000 0.057
T N1 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.057
T N2 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.057
T S1 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.057
T S2 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.057
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.355 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.502 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.371 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.343 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 502.69 0.00 01-JAN-00:15 33128.08 09-JAN-07:30
WaterSystems:Electricity 502.69 0.00 01-JAN-00:15 33128.08 09-JAN-07:30
Water Heater:WaterSystems:Electricity 502.69 0.00 01-JAN-00:15 33128.08 09-JAN-07:30
Fans:Electricity 213.26 6762.30 04-JAN-12:00 6762.30 01-JAN-06:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
ElectricityPurchased:Plant 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
Cogeneration:ElectricityPurchased 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
ElectricityNet:Plant 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
Cogeneration:ElectricityNet 1431.76 17474.28 05-JUN-02:45 82068.52 11-AUG-18:00
ExteriorLights:Electricity 39.80 0.00 01-JAN-11:30 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 39.80 0.00 01-JAN-11:30 2553.00 01-JAN-00:15
Electricity:HVAC 253.16 6762.30 04-JAN-12:00 22816.59 29-JUL-16:15
General:Fans:Electricity 213.26 6762.30 04-JAN-12:00 6762.30 01-JAN-06:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 39.90 0.00 01-JAN-00:15 16054.30 29-JUL-16:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 1107.35 0.00 17-APR-16:15 158809.24 29-JAN-00:15
Gas:HVAC 1107.35 0.00 17-APR-16:15 158809.24 29-JAN-00:15
Heating:Gas 1107.35 0.00 17-APR-16:15 158809.24 29-JAN-00:15


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1692.15 2669.67 29-AUG-17:00 215918.98 28-JAN-24:00
EnergyTransfer:Building 646.80 2422.12 29-AUG-17:00 88885.01 28-JAN-24:00
EnergyTransfer:Zone:G SW APARTMENT 20.27 0.13 30-MAY-15:00 3282.54 28-JAN-24:00
Heating:EnergyTransfer 414.65 0.00 22-MAR-16:15 88885.01 28-JAN-24:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 16.58 0.00 09-FEB-12:00 3282.54 28-JAN-24:00
Cooling:EnergyTransfer 232.15 0.00 01-JAN-18:30 52531.18 11-JUL-16:00
Cooling:EnergyTransfer:Zone:G SW APARTMENT 3.69 0.00 01-JAN-00:15 1562.94 11-AUG-16:15
EnergyTransfer:Zone:G NW APARTMENT 21.61 0.02 03-OCT-14:45 3365.18 28-JAN-24:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 19.04 0.00 22-MAR-15:15 3365.18 28-JAN-24:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 2.58 0.00 01-JAN-00:15 1244.55 11-JUL-17:45
EnergyTransfer:Zone:OFFICE 22.96 0.01 01-JUL-15:00 4717.37 29-JAN-07:30
Heating:EnergyTransfer:Zone:OFFICE 2.16 0.00 01-JAN-00:15 4717.37 29-JAN-07:30
Cooling:EnergyTransfer:Zone:OFFICE 20.80 0.00 01-JAN-18:30 4213.62 23-JUL-12:15
EnergyTransfer:Zone:G NE APARTMENT 21.76 0.02 25-SEP-01:15 3353.50 28-JAN-24:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 18.70 0.00 22-MAR-09:45 3353.50 28-JAN-24:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 3.06 0.00 01-JAN-00:15 924.10 21-JUL-16:15
EnergyTransfer:Zone:G N1 APARTMENT 14.86 0.04 12-MAY-12:45 2116.36 29-JAN-00:15
Heating:EnergyTransfer:Zone:G N1 APARTMENT 11.87 0.00 22-MAR-16:15 2116.36 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 2.99 0.00 01-JAN-00:15 692.31 11-JUL-19:00
EnergyTransfer:Zone:G N2 APARTMENT 14.86 0.10 23-APR-16:45 2116.52 29-JAN-00:15
Heating:EnergyTransfer:Zone:G N2 APARTMENT 11.86 0.00 22-MAR-16:15 2116.52 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 3.01 0.00 01-JAN-00:15 686.53 11-JUL-19:00
EnergyTransfer:Zone:G S1 APARTMENT 13.66 0.00 12-MAY-18:15 2039.00 29-JAN-00:15
Heating:EnergyTransfer:Zone:G S1 APARTMENT 9.68 0.00 09-FEB-11:30 2039.00 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 3.98 0.00 01-JAN-00:15 1186.83 23-JUL-13:30
EnergyTransfer:Zone:G S2 APARTMENT 15.13 0.11 12-FEB-14:30 2197.82 29-JAN-00:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 11.08 0.00 09-FEB-11:30 2197.82 29-JAN-00:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 4.06 0.00 01-JAN-00:15 1243.41 21-JUL-14:15
EnergyTransfer:Zone:M SW APARTMENT 40.47 0.26 22-FEB-13:15 5813.90 28-JAN-15:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 21.23 0.00 23-JAN-12:15 5813.90 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 19.23 0.00 01-JAN-00:15 4929.14 11-AUG-16:15
EnergyTransfer:Zone:M NW APARTMENT 39.38 0.01 10-OCT-15:30 5783.64 28-JAN-15:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 26.78 0.00 07-FEB-21:00 5783.64 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 12.60 0.00 01-JAN-00:15 3956.24 11-JUL-17:45
EnergyTransfer:Zone:M SE APARTMENT 42.08 0.12 17-FEB-12:15 5824.03 28-JAN-15:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 20.79 0.00 21-JAN-21:30 5824.03 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 21.29 0.00 01-JAN-00:15 4831.45 22-JUL-11:30
EnergyTransfer:Zone:M NE APARTMENT 40.55 0.24 27-MAY-02:15 5718.98 28-JAN-15:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 26.09 0.00 07-FEB-21:00 5718.98 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 14.46 0.00 01-JAN-00:15 3362.90 21-JUL-16:00
EnergyTransfer:Zone:M N1 APARTMENT 24.05 0.30 09-OCT-14:00 3681.96 28-JAN-15:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 10.22 0.00 04-JAN-20:00 3681.96 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 13.83 0.00 01-JAN-00:15 2508.61 11-JUL-19:00
EnergyTransfer:Zone:M N2 APARTMENT 24.11 0.22 22-MAR-03:15 3680.09 28-JAN-15:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 10.19 0.00 04-JAN-20:00 3680.09 28-JAN-15:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 13.92 0.00 01-JAN-00:15 2505.12 11-JUL-17:30
EnergyTransfer:Zone:M S1 APARTMENT 29.04 0.06 20-JAN-20:30 3887.28 11-AUG-15:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 6.81 0.00 04-JAN-19:45 3574.04 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 22.23 0.00 01-JAN-00:15 3887.28 11-AUG-15:15
EnergyTransfer:Zone:M S2 APARTMENT 29.13 0.30 20-JAN-20:30 3895.50 11-AUG-15:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 6.80 0.00 04-JAN-19:45 3575.85 28-JAN-24:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 22.34 0.00 01-JAN-00:15 3895.50 11-AUG-15:15
EnergyTransfer:Zone:T SW APARTMENT 33.33 0.03 26-APR-24:00 4717.16 28-JAN-15:30
Heating:EnergyTransfer:Zone:T SW APARTMENT 26.38 0.00 09-FEB-11:45 4717.16 28-JAN-15:30
Cooling:EnergyTransfer:Zone:T SW APARTMENT 6.96 0.00 01-JAN-00:15 3094.29 29-JUL-15:30
EnergyTransfer:Zone:T NW APARTMENT 34.20 0.01 01-OCT-15:00 4728.85 28-JAN-15:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 29.78 0.00 18-MAR-15:15 4728.85 28-JAN-15:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 4.42 0.00 01-JAN-00:15 2487.82 11-JUL-17:45
EnergyTransfer:Zone:T SE APARTMENT 33.68 0.03 24-JUN-19:45 4716.98 28-JAN-15:30
Heating:EnergyTransfer:Zone:T SE APARTMENT 25.99 0.00 09-FEB-11:45 4716.98 28-JAN-15:30
Cooling:EnergyTransfer:Zone:T SE APARTMENT 7.69 0.00 01-JAN-00:15 2964.16 22-JUL-11:45
EnergyTransfer:Zone:T NE APARTMENT 34.50 0.07 05-SEP-08:15 4676.01 28-JAN-15:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 29.32 0.00 18-MAR-11:45 4676.01 28-JAN-15:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 5.18 0.00 01-JAN-00:15 2056.30 21-JUL-16:00
EnergyTransfer:Zone:T N1 APARTMENT 24.46 0.24 08-SEP-08:15 3502.77 28-JAN-24:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 19.87 0.00 18-MAR-11:30 3502.77 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 4.59 0.00 01-JAN-00:15 1605.38 11-JUL-17:15
EnergyTransfer:Zone:T N2 APARTMENT 24.48 0.03 26-MAY-00:45 3501.25 28-JAN-24:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 19.85 0.00 18-MAR-11:30 3501.25 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 4.63 0.00 01-JAN-00:15 1596.87 11-JUL-17:15
EnergyTransfer:Zone:T S1 APARTMENT 24.09 0.22 25-JUN-22:45 3608.19 28-JAN-24:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 16.81 0.00 09-FEB-11:30 3608.19 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 7.27 0.00 01-JAN-00:15 2546.96 23-JUL-13:45
EnergyTransfer:Zone:T S2 APARTMENT 24.13 0.19 02-MAY-03:15 3609.60 28-JAN-24:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 16.80 0.00 09-FEB-11:30 3609.60 28-JAN-24:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 7.33 0.00 01-JAN-00:15 2561.35 23-JUL-13:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1045.35 0.00 02-JUN-01:00 127047.39 29-JAN-00:15
HeatingCoils:EnergyTransfer 885.88 0.00 17-APR-16:15 127047.39 29-JAN-00:15
CoolingCoils:EnergyTransfer 159.47 0.00 01-JAN-00:15 63412.19 29-JUL-16:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 16.578 -3.688 0.000 0.000 3.948 1.087 12.213 9.438 0.000 0.011 0.000 0.000 -13.714 0.000 -6.947 -18.924
G NW APARTMENT 19.036 -2.577 0.000 0.000 3.972 1.087 12.213 3.891 0.000 0.011 0.000 0.000 -14.729 0.000 -6.840 -16.062
OFFICE 2.159 -20.798 0.000 0.000 0.551 26.452 9.482 10.481 0.000 0.002 0.001 0.000 -12.529 0.000 -6.009 -9.791
G NE APARTMENT 18.702 -3.056 0.000 0.000 3.975 1.087 12.213 4.877 0.000 0.011 0.000 0.000 -14.376 0.000 -6.846 -16.587
G N1 APARTMENT 11.870 -2.987 0.000 0.000 3.977 1.087 12.213 1.536 0.000 0.008 0.000 0.000 -9.112 0.000 -4.331 -14.261
G N2 APARTMENT 11.855 -3.009 0.000 0.000 3.977 1.087 12.213 1.534 0.000 0.008 0.000 0.000 -9.113 0.000 -4.332 -14.221
G S1 APARTMENT 9.676 -3.981 0.000 0.000 3.943 1.087 12.213 7.302 0.000 0.008 0.000 0.000 -8.276 0.000 -4.445 -17.527
G S2 APARTMENT 11.077 -4.057 0.000 0.000 3.940 1.087 12.213 7.299 0.000 0.008 0.000 0.000 -8.262 0.000 -4.452 -18.854
M SW APARTMENT 21.235 -19.233 0.000 0.000 3.861 1.087 12.213 9.076 0.000 0.014 0.000 0.000 -14.337 0.000 -10.056 -3.861
M NW APARTMENT 26.777 -12.603 0.000 0.000 3.895 1.087 12.213 3.564 0.000 0.014 0.000 0.000 -15.302 0.000 -9.961 -9.684
M SE APARTMENT 20.792 -21.289 0.000 0.000 3.861 1.087 12.213 10.127 0.000 0.014 0.001 0.000 -14.063 0.000 -10.061 -2.681
M NE APARTMENT 26.091 -14.463 0.000 0.000 3.896 1.087 12.213 4.535 0.000 0.014 0.000 0.000 -14.946 0.000 -9.962 -8.464
M N1 APARTMENT 10.215 -13.834 0.000 0.000 3.888 1.087 12.213 1.333 0.000 0.011 0.942 0.000 -9.531 0.000 -6.324 -0.000
M N2 APARTMENT 10.189 -13.922 0.000 0.000 3.888 1.087 12.213 1.332 0.000 0.011 1.060 0.000 -9.532 0.000 -6.325 -0.000
M S1 APARTMENT 6.809 -22.226 0.000 0.000 3.846 1.087 12.213 7.075 0.000 0.011 6.270 0.000 -8.684 0.000 -6.400 -0.001
M S2 APARTMENT 6.798 -22.337 0.000 0.000 3.845 1.087 12.213 7.074 0.000 0.011 6.396 0.000 -8.684 0.000 -6.401 -0.001
T SW APARTMENT 26.377 -6.956 0.000 0.000 3.911 1.087 12.213 9.065 0.000 0.019 0.000 0.000 -13.847 0.000 -12.974 -18.894
T NW APARTMENT 29.776 -4.424 0.000 0.000 3.936 1.087 12.213 3.585 0.000 0.019 0.000 0.000 -14.828 0.000 -12.857 -18.506
T SE APARTMENT 25.989 -7.694 0.000 0.000 3.910 1.087 12.213 10.139 0.000 0.019 0.000 0.000 -13.610 0.000 -12.983 -19.070
T NE APARTMENT 29.315 -5.181 0.000 0.000 3.941 1.087 12.213 4.570 0.000 0.019 0.000 0.000 -14.488 0.000 -12.856 -18.619
T N1 APARTMENT 19.867 -4.594 0.000 0.000 3.936 1.087 12.213 1.367 0.000 0.015 0.000 0.000 -9.194 0.000 -8.077 -16.618
T N2 APARTMENT 19.849 -4.635 0.000 0.000 3.936 1.087 12.213 1.364 0.000 0.015 0.000 0.000 -9.194 0.000 -8.079 -16.556
T S1 APARTMENT 16.814 -7.274 0.000 0.000 3.897 1.087 12.213 7.078 0.000 0.015 0.000 0.000 -8.389 0.000 -8.184 -17.256
T S2 APARTMENT 16.800 -7.331 0.000 0.000 3.897 1.087 12.213 7.075 0.000 0.015 0.000 0.000 -8.389 0.000 -8.184 -17.182
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.015 0.000 0.000 0.000 0.000 -1.603 0.000 -2.144 -10.850
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.085 0.000 0.012 43.203 0.000 -4.148 0.000 -60.212 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.015 0.000 0.000 0.000 0.000 -1.723 0.000 -1.735 -11.139
Total Facility 414.647 -232.149 0.000 0.000 90.627 95.189 296.854 134.834 0.000 0.314 57.872 0.000 -284.601 0.000 -257.977 -315.609


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 11-AUG-16:15 0.00 -1563.08 0.00 0.00 84.75 64.86 588.62 2158.17 0.00 61.17 0.00 0.00 0.00 0.00 0.00 -1394.50
G NW APARTMENT 11-JUL-17:45 0.00 -1244.35 0.00 0.00 141.80 87.56 588.62 1636.78 0.00 90.49 0.00 0.00 0.00 0.00 0.00 -1300.90
OFFICE 27-AUG-06:01 0.00 -7065.21 0.00 0.00 0.00 416.15 294.31 486.66 0.00 0.00 5938.13 0.00 0.00 0.00 -70.04 0.00
G NE APARTMENT 21-JUL-16:10 0.00 -924.64 0.00 0.00 84.76 64.86 588.62 548.50 0.00 161.47 0.00 0.00 0.00 0.00 0.00 -523.57
G N1 APARTMENT 29-SEP-06:50 0.00 -744.29 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 759.49 0.00 -425.76 0.00 -175.43 0.00
G N2 APARTMENT 29-SEP-06:50 0.00 -745.96 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 761.18 0.00 -425.78 0.00 -175.42 0.00
G S1 APARTMENT 23-JUL-13:30 0.00 -1186.69 0.00 0.00 40.75 12.97 382.60 2232.20 0.00 11.25 0.00 0.00 0.00 0.00 0.00 -1493.09
G S2 APARTMENT 21-JUL-14:15 0.00 -1243.30 0.00 0.00 40.75 22.70 400.26 1955.03 0.00 52.92 0.00 0.00 0.00 0.00 0.00 -1228.37
M SW APARTMENT 11-AUG-16:15 0.00 -4929.55 0.00 0.00 84.76 64.86 588.62 2136.94 0.00 83.97 1970.41 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 11-JUL-17:45 0.00 -3955.60 0.00 0.00 141.80 87.56 588.62 1617.89 0.00 124.11 1395.61 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 22-JUL-11:30 0.00 -4831.14 0.00 0.00 40.75 12.97 406.15 2745.04 0.00 43.30 1582.94 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 21-JUL-16:00 0.00 -3362.40 0.00 0.00 48.90 45.40 470.90 580.08 0.00 327.08 1890.04 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 11-JUL-19:00 0.00 -2508.34 0.00 0.00 141.80 103.77 547.42 262.16 0.00 97.29 1355.90 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 11-JUL-17:30 0.00 -2505.11 0.00 0.00 141.80 87.56 588.62 231.94 0.00 103.99 1351.19 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 11-AUG-15:15 0.00 -3887.55 0.00 0.00 48.90 45.40 470.90 1698.92 0.00 16.18 1607.25 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 11-AUG-15:15 0.00 -3895.77 0.00 0.00 48.90 45.40 470.90 1698.86 0.00 16.18 1615.53 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 29-JUL-15:30 0.00 -3094.45 0.00 0.00 48.90 45.40 470.90 2489.76 0.00 163.87 0.00 0.00 0.00 0.00 0.00 -124.38
T NW APARTMENT 11-JUL-17:45 0.00 -2487.40 0.00 0.00 141.80 87.56 588.62 1594.65 0.00 157.88 0.00 0.00 0.00 0.00 0.00 -83.12
T SE APARTMENT 22-JUL-11:45 0.00 -2963.93 0.00 0.00 40.75 12.97 406.15 2538.69 0.00 83.02 0.00 0.00 0.00 0.00 0.00 -117.66
T NE APARTMENT 21-JUL-16:00 0.00 -2055.97 0.00 0.00 48.90 45.40 470.90 565.86 0.00 429.18 495.74 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 11-JUL-17:15 0.00 -1605.42 0.00 0.00 141.81 87.56 588.62 235.95 0.00 132.55 418.93 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 11-JUL-17:15 0.00 -1596.91 0.00 0.00 141.81 87.56 588.62 236.07 0.00 132.55 410.31 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 23-JUL-13:45 0.00 -2546.74 0.00 0.00 40.75 12.97 382.60 2127.44 0.00 17.75 0.00 0.00 0.00 0.00 0.00 -34.77
T S2 APARTMENT 23-JUL-13:45 0.00 -2561.14 0.00 0.00 40.75 12.97 382.60 2127.25 0.00 17.75 0.00 0.00 0.00 0.00 0.00 -20.19
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-16:00 0.00 -52528.94 0.00 0.00 1191.96 4512.09 11708.34 24308.04 0.00 2348.55 8496.00 0.00 0.00 0.00 -36.02 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 28-JAN-24:00 3282.52 0.00 0.00 0.00 189.67 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -1119.79 0.00 -2066.56 -643.45
G NW APARTMENT 28-JAN-24:00 3365.15 0.00 0.00 0.00 189.67 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -1142.12 0.00 -2066.56 -703.75
OFFICE 24-DEC-07:01 7263.13 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -456.24 0.00 -277.39 -7239.96
G NE APARTMENT 28-JAN-24:00 3353.47 0.00 0.00 0.00 189.67 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -1159.13 0.00 -2065.76 -675.87
G N1 APARTMENT 29-JAN-00:15 2116.35 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -702.71 0.00 -1214.70 -659.98
G N2 APARTMENT 29-JAN-00:15 2116.51 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -702.71 0.00 -1214.70 -660.14
G S1 APARTMENT 29-JAN-00:15 2039.00 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -680.40 0.00 -1214.70 -604.93
G S2 APARTMENT 29-JAN-00:15 2197.81 0.00 0.00 0.00 189.67 6.49 264.88 0.00 0.00 0.00 0.00 0.00 -678.31 0.00 -1214.70 -765.83
M SW APARTMENT 28-JAN-15:00 5813.77 0.00 0.00 0.00 47.42 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -341.65 0.00 -2731.82 -3183.29
M NW APARTMENT 28-JAN-15:00 5783.50 0.00 0.00 0.00 48.63 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -871.98 0.00 -2688.70 -2667.02
M SE APARTMENT 28-JAN-15:00 5823.89 0.00 0.00 0.00 47.43 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -508.27 0.00 -2729.53 -3029.10
M NE APARTMENT 28-JAN-15:00 5718.84 0.00 0.00 0.00 48.89 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -1036.41 0.00 -2679.82 -2447.08
M N1 APARTMENT 28-JAN-15:00 3681.88 0.00 0.00 0.00 47.46 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -636.34 0.00 -1648.12 -1840.45
M N2 APARTMENT 28-JAN-15:00 3680.00 0.00 0.00 0.00 47.46 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -636.33 0.00 -1648.05 -1838.67
M S1 APARTMENT 28-JAN-24:00 3574.01 0.00 0.00 0.00 192.25 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -695.14 0.00 -1775.94 -1652.79
M S2 APARTMENT 28-JAN-24:00 3575.82 0.00 0.00 0.00 192.23 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -695.15 0.00 -1776.02 -1654.50
T SW APARTMENT 28-JAN-15:30 4717.09 0.00 0.00 0.00 47.42 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -934.13 0.00 -3476.00 -777.35
T NW APARTMENT 28-JAN-15:00 4728.73 0.00 0.00 0.00 48.25 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -857.87 0.00 -3570.87 -743.82
T SE APARTMENT 28-JAN-15:30 4716.91 0.00 0.00 0.00 47.55 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -977.51 0.00 -3470.30 -739.62
T NE APARTMENT 28-JAN-15:00 4675.89 0.00 0.00 0.00 48.62 12.97 382.60 0.00 0.00 0.00 0.00 0.00 -1020.82 0.00 -3554.13 -545.14
T N1 APARTMENT 28-JAN-24:00 3502.73 0.00 0.00 0.00 192.64 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -707.03 0.00 -2348.67 -997.28
T N2 APARTMENT 28-JAN-24:00 3501.21 0.00 0.00 0.00 192.72 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -706.88 0.00 -2348.18 -996.48
T S1 APARTMENT 28-JAN-24:00 3608.17 0.00 0.00 0.00 190.00 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -684.00 0.00 -2366.34 -1105.45
T S2 APARTMENT 28-JAN-24:00 3609.58 0.00 0.00 0.00 190.00 16.21 341.40 0.00 0.00 0.00 0.00 0.00 -683.99 0.00 -2366.36 -1106.85
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 28-JAN-24:00 88883.85 0.00 0.00 0.00 4503.01 2176.23 8134.84 0.00 0.00 0.00 0.00 0.00 -22319.09 0.00 -57415.49 -23963.36



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Sec1.1A-General Information

Data
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 48.50
Number of hours cooling loads not met 0.00
Number of hours not met 48.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 39.80 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 1107.35 158809.24 0.00 0.00
Space Cooling 39.90 12449.90 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 213.26 6762.30 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 502.69 31245.45 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1431.76   1107.35   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1431.76
Natural Gas 0.00 1107.35
Additional 0.00 0.00
Total 517.65 2539.12


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 12.73
Fans-Interior 68.03
Service Water Heating 160.37
Receptacle Equipment 165.14
Miscellaneous 12.70
Subtotal 456.76


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 353.27
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 353.27


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.67
Space Heating 43.61
Space Cooling 1.57
Fans-Interior 8.40
Service Water Heating 19.80
Receptacle Equipment 20.39
Miscellaneous 1.57



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.160397
G NW APARTMENT DIRECT AIR 0.119433
OFFICE DIRECT AIR 0.441127
G NE APARTMENT DIRECT AIR 0.087796
G N1 APARTMENT DIRECT AIR 0.066489
G N2 APARTMENT DIRECT AIR 0.065401
G S1 APARTMENT DIRECT AIR 0.121759
G S2 APARTMENT DIRECT AIR 0.124962
M SW APARTMENT DIRECT AIR 0.483313
M NW APARTMENT DIRECT AIR 0.372955
M SE APARTMENT DIRECT AIR 0.466076
M NE APARTMENT DIRECT AIR 0.307482
M N1 APARTMENT DIRECT AIR 0.233448
M N2 APARTMENT DIRECT AIR 0.231406
M S1 APARTMENT DIRECT AIR 0.381290
M S2 APARTMENT DIRECT AIR 0.382570
T SW APARTMENT DIRECT AIR 0.302682
T NW APARTMENT DIRECT AIR 0.228904
T SE APARTMENT DIRECT AIR 0.290812
T NE APARTMENT DIRECT AIR 0.180255
T N1 APARTMENT DIRECT AIR 0.137818
T N2 APARTMENT DIRECT AIR 0.136202
T S1 APARTMENT DIRECT AIR 0.250888
T S2 APARTMENT DIRECT AIR 0.251887


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.160397
SPLIT GNW MAIN BRANCH 0.119433
SPLIT OFFICE MAIN BRANCH 0.441127
SPLIT GNE MAIN BRANCH 0.087796
SPLIT GN1 MAIN BRANCH 0.066489
SPLIT GN2 MAIN BRANCH 0.065401
SPLIT GS1 MAIN BRANCH 0.121759
SPLIT GS2 MAIN BRANCH 0.124962
SPLIT MSW MAIN BRANCH 0.483313
SPLIT MNW MAIN BRANCH 0.372955
SPLIT MSE MAIN BRANCH 0.466076
SPLIT MNE MAIN BRANCH 0.307482
SPLIT MN1 MAIN BRANCH 0.233448
SPLIT MN2 MAIN BRANCH 0.231406
SPLIT MS1 MAIN BRANCH 0.381290
SPLIT MS2 MAIN BRANCH 0.382570
SPLIT TSW MAIN BRANCH 0.302682
SPLIT TNW MAIN BRANCH 0.228904
SPLIT TSE MAIN BRANCH 0.290812
SPLIT TNE MAIN BRANCH 0.180255
SPLIT TN1 MAIN BRANCH 0.137818
SPLIT TN2 MAIN BRANCH 0.136202
SPLIT TS1 MAIN BRANCH 0.250888
SPLIT TS2 MAIN BRANCH 0.251887


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.160397
SPLIT GNW 0.119433
SPLIT OFFICE 0.441127
SPLIT GNE 0.087796
SPLIT GN1 0.066489
SPLIT GN2 0.065401
SPLIT GS1 0.121759
SPLIT GS2 0.124962
SPLIT MSW 0.483313
SPLIT MNW 0.372955
SPLIT MSE 0.466076
SPLIT MNE 0.307482
SPLIT MN1 0.233448
SPLIT MN2 0.231406
SPLIT MS1 0.381290
SPLIT MS2 0.382570
SPLIT TSW 0.302682
SPLIT TNW 0.228904
SPLIT TSE 0.290812
SPLIT TNE 0.180255
SPLIT TN1 0.137818
SPLIT TN2 0.136202
SPLIT TS1 0.250888
SPLIT TS2 0.251887


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.160397 0.026898
SPLIT GNW OA CONTROLLER 0.119433 0.025953
SPLIT OFFICE OA CONTROLLER 0.441127 0.038104
SPLIT GNE OA CONTROLLER 0.087796 0.025953
SPLIT GN1 OA CONTROLLER 0.066489 0.025953
SPLIT GN2 OA CONTROLLER 0.065401 0.025953
SPLIT GS1 OA CONTROLLER 0.121759 0.025953
SPLIT GS2 OA CONTROLLER 0.124962 0.025953
SPLIT MSW OA CONTROLLER 0.483313 0.051906
SPLIT MNW OA CONTROLLER 0.372955 0.051906
SPLIT MSE OA CONTROLLER 0.466076 0.051906
SPLIT MNE OA CONTROLLER 0.307482 0.051906
SPLIT MN1 OA CONTROLLER 0.233448 0.051906
SPLIT MN2 OA CONTROLLER 0.231406 0.051906
SPLIT MS1 OA CONTROLLER 0.381290 0.051906
SPLIT MS2 OA CONTROLLER 0.382570 0.051906
SPLIT TSW OA CONTROLLER 0.302682 0.025953
SPLIT TNW OA CONTROLLER 0.228904 0.025953
SPLIT TSE OA CONTROLLER 0.290812 0.025953
SPLIT TNE OA CONTROLLER 0.180255 0.025953
SPLIT TN1 OA CONTROLLER 0.137818 0.025953
SPLIT TN2 OA CONTROLLER 0.136202 0.025953
SPLIT TS1 OA CONTROLLER 0.250888 0.025953
SPLIT TS2 OA CONTROLLER 0.251887 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.160397 2655.15 0.798655
SPLIT GNW COOLING COIL 0.119433 1977.04 0.798655
SPLIT OFFICE COOLING COIL 0.441127 7302.21 0.798655
SPLIT GNE COOLING COIL 0.087796 1453.34 0.798655
SPLIT GN1 COOLING COIL 0.066489 1100.63 0.798655
SPLIT GN2 COOLING COIL 0.065401 1082.61 0.798655
SPLIT GS1 COOLING COIL 0.121759 2015.54 0.798655
SPLIT GS2 COOLING COIL 0.124962 2068.56 0.798655
SPLIT MSW COOLING COIL 0.483313 8000.55 0.798655
SPLIT MNW COOLING COIL 0.372955 6173.73 0.798655
SPLIT MSE COOLING COIL 0.466076 7715.21 0.798655
SPLIT MNE COOLING COIL 0.307482 5089.93 0.798655
SPLIT MN1 COOLING COIL 0.233448 3864.40 0.798655
SPLIT MN2 COOLING COIL 0.231406 3830.60 0.798655
SPLIT MS1 COOLING COIL 0.381290 6311.71 0.798655
SPLIT MS2 COOLING COIL 0.382570 6332.89 0.798655
SPLIT TSW COOLING COIL 0.302682 5010.47 0.798655
SPLIT TNW COOLING COIL 0.228904 3789.17 0.798655
SPLIT TSE COOLING COIL 0.290812 4813.97 0.798655
SPLIT TNE COOLING COIL 0.180255 2983.86 0.798655
SPLIT TN1 COOLING COIL 0.137818 2281.37 0.798655
SPLIT TN2 COOLING COIL 0.136202 2254.63 0.798655
SPLIT TS1 COOLING COIL 0.250888 4153.09 0.798655
SPLIT TS2 COOLING COIL 0.251887 4169.63 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.160397 0.160397 0.160397 0.160397 4743.27 2655.15 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.119433 0.119433 0.119433 0.119433 4687.30 1977.04 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.441127 0.441127 0.441127 0.441127 7957.76 7302.21 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.087796 0.087796 0.087796 0.087796 4693.33 1453.34 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.066489 0.066489 0.066489 0.066489 3903.99 1100.63 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.065401 0.065401 0.065401 0.065401 3904.12 1082.61 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.121759 0.121759 0.121759 0.121759 3892.09 2015.54 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.124962 0.124962 0.124962 0.124962 4034.18 2068.56 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.483313 0.483313 0.483313 0.483313 7769.23 8000.55 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.372955 0.372955 0.372955 0.372955 7797.98 6173.73 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.466076 0.466076 0.466076 0.466076 7785.25 7715.21 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.307482 0.307482 0.307482 0.307482 7814.02 5089.93 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.233448 0.233448 0.233448 0.233448 5966.13 3864.40 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.231406 0.231406 0.231406 0.231406 5966.50 3830.60 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.381290 0.381290 0.381290 0.381290 5941.02 6311.71 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.382570 0.382570 0.382570 0.382570 5941.38 6332.89 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.302682 0.302682 0.302682 0.302682 5650.78 5010.47 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.228904 0.228904 0.228904 0.228904 5668.71 3789.17 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.290812 0.290812 0.290812 0.290812 5659.62 4813.97 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.180255 0.180255 0.180255 0.180255 5677.56 2983.86 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.137818 0.137818 0.137818 0.137818 4753.68 2281.37 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.136202 0.136202 0.136202 0.136202 4753.89 2254.63 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.250888 0.250888 0.250888 0.250888 4734.38 4153.09 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.251887 0.251887 0.251887 0.251887 4734.59 4169.63 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.160397
SPLIT GNW SUPPLY FAN 0.119433
SPLIT OFFICE SUPPLY FAN 0.441127
SPLIT GNE SUPPLY FAN 0.087796
SPLIT GN1 SUPPLY FAN 0.066489
SPLIT GN2 SUPPLY FAN 0.065401
SPLIT GS1 SUPPLY FAN 0.121759
SPLIT GS2 SUPPLY FAN 0.124962
SPLIT MSW SUPPLY FAN 0.483313
SPLIT MNW SUPPLY FAN 0.372955
SPLIT MSE SUPPLY FAN 0.466076
SPLIT MNE SUPPLY FAN 0.307482
SPLIT MN1 SUPPLY FAN 0.233448
SPLIT MN2 SUPPLY FAN 0.231406
SPLIT MS1 SUPPLY FAN 0.381290
SPLIT MS2 SUPPLY FAN 0.382570
SPLIT TSW SUPPLY FAN 0.302682
SPLIT TNW SUPPLY FAN 0.228904
SPLIT TSE SUPPLY FAN 0.290812
SPLIT TNE SUPPLY FAN 0.180255
SPLIT TN1 SUPPLY FAN 0.137818
SPLIT TN2 SUPPLY FAN 0.136202
SPLIT TS1 SUPPLY FAN 0.250888
SPLIT TS2 SUPPLY FAN 0.251887


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 4743.27
SPLIT GNW HEATING COIL 4687.30
SPLIT OFFICE HEATING COIL 7957.76
SPLIT GNE HEATING COIL 4693.33
SPLIT GN1 HEATING COIL 3903.99
SPLIT GN2 HEATING COIL 3904.12
SPLIT GS1 HEATING COIL 3892.09
SPLIT GS2 HEATING COIL 4034.18
SPLIT MSW HEATING COIL 7769.23
SPLIT MNW HEATING COIL 7797.98
SPLIT MSE HEATING COIL 7785.25
SPLIT MNE HEATING COIL 7814.02
SPLIT MN1 HEATING COIL 5966.13
SPLIT MN2 HEATING COIL 5966.50
SPLIT MS1 HEATING COIL 5941.02
SPLIT MS2 HEATING COIL 5941.38
SPLIT TSW HEATING COIL 5650.78
SPLIT TNW HEATING COIL 5668.71
SPLIT TSE HEATING COIL 5659.62
SPLIT TNE HEATING COIL 5677.56
SPLIT TN1 HEATING COIL 4753.68
SPLIT TN2 HEATING COIL 4753.89
SPLIT TS1 HEATING COIL 4734.38
SPLIT TS2 HEATING COIL 4734.59



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:44

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.92 0.73
May 22.39 10.60
June 23.92 15.96
July 24.14 16.86
August 23.84 14.24
September 22.57 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.42 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.14 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.73 0.73
May 21.98 10.60
June 23.76 15.96
July 24.04 16.86
August 23.54 14.24
September 22.11 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.28 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.04 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.45 -17.6
February 17.93 -15.4
March 18.74 -10.3
April 20.92 0.73
May 23.04 10.60
June 25.24 15.96
July 25.64 16.86
August 25.07 14.24
September 23.39 6.72
October 20.15 -3.1
November 17.51 -17.6
December 17.29 -19.3
     
Annual Sum or Average 21.05 -1.4
Minimum of Months 17.29 -19.3
Maximum of Months 25.64 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.71 0.73
May 22.02 10.60
June 23.80 15.96
July 24.04 16.86
August 23.55 14.24
September 22.10 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.29 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.04 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.70 0.73
May 21.84 10.60
June 23.66 15.96
July 23.99 16.86
August 23.51 14.24
September 22.13 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.26 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 23.99 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.70 0.73
May 21.84 10.60
June 23.66 15.96
July 23.99 16.86
August 23.51 14.24
September 22.13 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.26 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 23.99 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.89 0.73
May 22.32 10.60
June 23.94 15.96
July 24.17 16.86
August 23.94 14.24
September 22.78 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.44 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.17 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.89 0.73
May 22.35 10.60
June 23.98 15.96
July 24.20 16.86
August 23.97 14.24
September 22.81 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.20 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -17.6
February 21.70 -15.4
March 21.75 -10.3
April 22.74 0.73
May 24.03 10.60
June 24.37 15.96
July 24.40 16.86
August 24.32 14.24
September 23.44 6.72
October 21.83 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.81 -1.4
Minimum of Months 21.69 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 22.03 0.73
May 23.69 10.60
June 24.36 15.96
July 24.39 16.86
August 24.21 14.24
September 22.77 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.64 -1.4
Minimum of Months 21.69 -19.3
Maximum of Months 24.39 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -17.6
February 21.70 -15.4
March 21.76 -10.3
April 22.75 0.73
May 24.07 10.60
June 24.37 15.96
July 24.40 16.86
August 24.33 14.24
September 23.48 6.72
October 21.86 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.82 -1.4
Minimum of Months 21.69 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.99 0.73
May 23.77 10.60
June 24.36 15.96
July 24.39 16.86
August 24.22 14.24
September 22.81 6.72
October 21.71 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.65 -1.4
Minimum of Months 21.68 -19.3
Maximum of Months 24.39 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.96 0.73
May 23.79 10.60
June 24.38 15.96
July 24.40 16.86
August 24.26 14.24
September 22.97 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.96 0.73
May 23.80 10.60
June 24.38 15.96
July 24.40 16.86
August 24.27 14.24
September 22.98 6.72
October 21.73 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.67 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.79 -10.3
April 22.91 0.73
May 24.17 10.60
June 24.39 15.96
July 24.40 16.86
August 24.36 14.24
September 23.70 6.72
October 22.01 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.88 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.71 -15.4
March 21.79 -10.3
April 22.91 0.73
May 24.18 10.60
June 24.39 15.96
July 24.40 16.86
August 24.36 14.24
September 23.71 6.72
October 22.01 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.89 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.40 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -17.6
February 21.70 -15.4
March 21.75 -10.3
April 22.43 0.73
May 23.36 10.60
June 24.21 15.96
July 24.30 16.86
August 23.98 14.24
September 22.59 6.72
October 21.75 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.60 -1.4
Minimum of Months 21.69 -19.3
Maximum of Months 24.30 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.97 0.73
May 23.03 10.60
June 24.18 15.96
July 24.26 16.86
August 23.73 14.24
September 22.11 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.68 -19.3
Maximum of Months 24.26 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -17.6
February 21.70 -15.4
March 21.76 -10.3
April 22.43 0.73
May 23.47 10.60
June 24.23 15.96
July 24.31 16.86
August 24.01 14.24
September 22.64 6.72
October 21.76 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.62 -1.4
Minimum of Months 21.69 -19.3
Maximum of Months 24.31 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.94 0.73
May 23.18 10.60
June 24.16 15.96
July 24.22 16.86
August 23.71 14.24
September 22.09 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.68 -19.3
Maximum of Months 24.22 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.90 0.73
May 23.05 10.60
June 24.22 15.96
July 24.28 16.86
August 23.76 14.24
September 22.06 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.28 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.70 -10.3
April 21.90 0.73
May 23.07 10.60
June 24.21 15.96
July 24.28 16.86
August 23.76 14.24
September 22.06 6.72
October 21.70 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.46 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.28 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.76 -10.3
April 22.50 0.73
May 23.52 10.60
June 24.28 15.96
July 24.35 16.86
August 24.11 14.24
September 22.76 6.72
October 21.79 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.66 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -17.6
February 21.70 -15.4
March 21.77 -10.3
April 22.50 0.73
May 23.53 10.60
June 24.28 15.96
July 24.35 16.86
August 24.11 14.24
September 22.77 6.72
October 21.79 -3.1
November 21.70 -17.6
December 21.70 -19.3
     
Annual Sum or Average 22.66 -1.4
Minimum of Months 21.70 -19.3
Maximum of Months 24.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.71 -17.6
February 20.05 -15.4
March 20.72 -10.3
April 22.41 0.73
May 24.60 10.60
June 26.15 15.96
July 26.26 16.86
August 25.49 14.24
September 23.04 6.72
October 21.15 -3.1
November 19.92 -17.6
December 19.61 -19.3
     
Annual Sum or Average 22.44 -1.4
Minimum of Months 19.61 -19.3
Maximum of Months 26.26 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.77 -17.6
February 15.34 -15.4
March 16.46 -10.3
April 18.93 0.73
May 21.33 10.60
June 24.02 15.96
July 24.58 16.86
August 23.79 14.24
September 21.51 6.72
October 18.16 -3.1
November 15.05 -17.6
December 14.56 -19.3
     
Annual Sum or Average 19.06 -1.4
Minimum of Months 14.56 -19.3
Maximum of Months 24.58 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.05 -17.6
February 22.35 -15.4
March 22.77 -10.3
April 23.99 0.73
May 25.94 10.60
June 26.68 15.96
July 26.70 16.86
August 26.43 14.24
September 25.00 6.72
October 22.96 -3.1
November 22.25 -17.6
December 21.99 -19.3
     
Annual Sum or Average 24.10 -1.4
Minimum of Months 21.99 -19.3
Maximum of Months 26.70 16.86



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:44

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.121439E+12 73566.387 14-JAN-18:45 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32640.215 0.000 0.000 0.000
February 0.108835E+12 73565.023 24-FEB-18:30 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32638.851 0.000 0.000 0.000
March 0.119619E+12 73564.713 01-MAR-18:45 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32638.541 0.000 0.000 0.000
April 0.115601E+12 70907.251 27-APR-17:45 4979.953 26630.920 6762.298 0.000 2230.657 0.000 0.000 0.000 0.000 0.000 0.000 30303.422 0.000 0.000 0.000
May 0.121845E+12 75576.832 31-MAY-17:15 4979.953 26630.920 6762.298 0.000 8831.682 0.000 0.000 0.000 0.000 0.000 0.000 28371.977 0.000 0.000 0.000
June 0.123480E+12 80190.694 20-JUN-17:00 4979.953 26630.920 6762.298 0.000 12933.576 0.000 0.000 0.000 0.000 0.000 0.000 28883.946 0.000 0.000 0.000
July 0.128514E+12 80615.059 11-JUL-17:45 4979.953 26630.920 6762.298 0.000 14031.920 0.000 0.000 0.000 0.000 0.000 0.000 28209.967 0.000 0.000 0.000
August 0.123616E+12 82068.523 11-AUG-17:00 4979.953 26630.920 6762.298 0.000 12449.900 0.000 0.000 0.000 0.000 0.000 0.000 31245.451 0.000 0.000 0.000
September 0.113499E+12 69673.195 01-SEP-17:30 4979.953 26630.920 6762.298 0.000 2467.182 0.000 0.000 0.000 0.000 0.000 0.000 28832.841 0.000 0.000 0.000
October 0.117709E+12 71259.767 29-OCT-17:15 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30333.595 0.000 0.000 0.000
November 0.115925E+12 73424.489 26-NOV-18:30 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32498.317 0.000 0.000 0.000
December 0.121681E+12 73563.724 23-DEC-18:15 4979.953 26630.920 6762.298 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32637.552 0.000 0.000 0.000
                                     
Annual Sum or Average 0.143176E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.108835E+12 69673.195   4979.953 26630.920 6762.298 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 28209.967 0.000 0.000 0.000
Maximum of Months 0.128514E+12 82068.523   4979.953 26630.920 6762.298 0.000 14031.920 2553.000 0.000 0.000 0.000 0.000 0.000 32640.215 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:44

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.214850E+12 158809.237 29-JAN-00:15 158809.237 0.000 0.000 0.000 0.000 0.000 158809.237
February 0.166101E+12 144966.361 25-FEB-00:00 144966.361 0.000 0.000 0.000 0.000 0.000 144966.361
March 0.141739E+12 119739.424 02-MAR-04:00 119739.424 0.000 0.000 0.000 0.000 0.000 119739.424
April 0.610495E+11 98376.325 02-APR-06:00 98376.325 0.000 0.000 0.000 0.000 0.000 98376.325
May 0.740070E+10 33542.676 28-MAY-02:00 33542.676 0.000 0.000 0.000 0.000 0.000 33542.676
June 0.521324E+08 2045.893 25-JUN-05:00 2045.893 0.000 0.000 0.000 0.000 0.000 2045.893
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.907731E+09 15599.463 31-AUG-03:00 15599.463 0.000 0.000 0.000 0.000 0.000 15599.463
September 0.134639E+11 42475.158 30-SEP-04:00 42475.158 0.000 0.000 0.000 0.000 0.000 42475.158
October 0.999746E+11 98557.834 27-OCT-03:00 98557.834 0.000 0.000 0.000 0.000 0.000 98557.834
November 0.180433E+12 123215.672 29-NOV-07:00 123215.672 0.000 0.000 0.000 0.000 0.000 123215.672
December 0.221382E+12 130487.321 15-DEC-11:00 130487.321 0.000 0.000 0.000 0.000 0.000 130487.321
                     
Annual Sum or Average 0.110735E+13       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.221382E+12 158809.237   158809.237 0.000 0.000 0.000 0.000 0.000 158809.237