Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780

Simulation Timestamp: 2015-09-09 18:48:13


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1650.91 526.67 584.61
Net Site Energy 1650.91 526.67 584.61
Total Source Energy 5202.64 1659.74 1842.31
Net Source Energy 5202.64 1659.74 1842.31


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 12.39 0.00 0.00 0.00 0.00
Cooling 345.76 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.09 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 306.50 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 310.06 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1638.52 12.39 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 12.39 0.00 0.00 0.00 0.00
Cooling General 345.76 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.09 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 306.50 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 310.06 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.15 0.00 0.00 0.00 0.00 0.00
HVAC 340.77 4.39 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 580.22 4.39 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.58 0.00 0.00 0.00 0.00 0.00
HVAC 307.00 3.95 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 522.72 3.95 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1638.52 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1638.52 100.00
     
Total On-Site and Utility Electric Sources 1638.52 100.00
Total Electricity End Uses 1638.52 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 11.25
Time Setpoint Not Met During Occupied Cooling 9.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 97.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
RunPeriod Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Weather File Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Latitude [deg] 33.45
Longitude [deg] -112.0
Elevation [m] 337.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-17:15 10-FEB-06:00 - - - 01-JAN-07:30
Heating 0.00 22335.71 0.00 0.00 0.00 0.00
Cooling 33445.01 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9718.96 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 18998.62 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 93773.47 22335.71 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 22335.71 0.00 0.00 0.00 0.00
Cooling General 33445.01 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 9718.96 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 18998.62 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 13.43 0.00 0.00 0.00
Cooling 1095.02 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.97 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 970.68 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 981.97 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 5189.21 13.43 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 4.76 0.00 0.00 0.00
Cooling 387.76 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.96 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 343.73 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 347.73 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1837.55 4.76 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 4.76 0.00 0.00 0.00
Cooling 387.76 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.96 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 343.73 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 347.73 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1837.55 4.76 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 3.70 0.00 3.70 Wetbulb [C] 1.70 100.00
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 43.40 12.00 21.10 Wetbulb [C] 4.10 260.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 4.600 0.293 0.130     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 4.600 0.293 0.130     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.72_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 4.600 0.293 0.130     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.72_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 4.600 0.293 0.130     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 4.600 0.293 0.130     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.72_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 4.600 0.293 0.130     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.72_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 4.600 0.293 0.130     No M EWALL C 270.00 90.00 W
Total or Average           306.92 4.600 0.293 0.130              
North Total or Average           112.97 4.600 0.293 0.130              
Non-North Total or Average           193.95 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.65 83.65 40.09
Exterior Lighting Total 2553.00           40.09



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4908.30 3677.73 1230.56 0.75 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   4706.32 3570.13 1136.19 0.76 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   9279.36 7411.01 1868.35 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4003.88 3039.68 964.20 0.76 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2905.22 2172.66 732.56 0.75 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2893.68 2163.52 730.16 0.75 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3294.66 2391.49 903.18 0.73 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3342.35 2428.36 913.99 0.73 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   11351.41 8593.06 2758.35 0.76 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   11015.27 8392.01 2623.25 0.76 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   10183.62 7735.10 2448.52 0.76 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   9541.04 7271.73 2269.31 0.76 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6846.63 5150.19 1696.44 0.75 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6828.62 5135.94 1692.68 0.75 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   7753.24 5688.21 2065.02 0.73 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   7768.52 5700.04 2068.47 0.73 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   7749.77 5877.27 1872.50 0.76 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   7430.85 5663.31 1767.54 0.76 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7206.01 5426.30 1779.71 0.75 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6671.19 5012.04 1659.15 0.75 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5242.50 3905.88 1336.63 0.75 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5240.83 3904.58 1336.25 0.75 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5765.89 4303.82 1462.08 0.75 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5774.29 4310.31 1463.97 0.75 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4706.7 3.21 10.97 11.41 10.81
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4507.5 3.20 10.91 11.35 10.72
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8840.1 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3834.4 3.20 10.91 11.34 10.72
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2786.4 3.22 10.98 11.42 10.82
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2775.4 3.22 10.98 11.42 10.82
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3169.2 3.26 11.11 11.57 11.02
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3214.7 3.26 11.11 11.56 11.02
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 10874.1 3.20 10.92 11.36 10.74
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 10545.3 3.19 10.89 11.33 10.70
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 9752.1 3.20 10.90 11.34 10.72
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 9133.6 3.19 10.89 11.32 10.69
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 6562.9 3.21 10.95 11.39 10.78
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 6545.7 3.21 10.95 11.39 10.78
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 7450.2 3.24 11.06 11.52 10.95
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 7464.8 3.24 11.06 11.51 10.95
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7422.5 3.20 10.91 11.35 10.73
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7113.5 3.19 10.89 11.32 10.69
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 6906.6 3.21 10.94 11.39 10.77
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6395.5 3.21 10.95 11.40 10.79
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5030.0 3.22 10.99 11.44 10.85
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5028.4 3.22 10.99 11.44 10.85
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5531.2 3.22 10.98 11.43 10.83
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5539.2 3.22 10.98 11.43 10.83
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1447.88 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   2781.59 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1396.99 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2793.97 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   2097.95 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   2099.59 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   2106.14 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   2107.78 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1586.83 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1586.98 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1584.84 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1584.99 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.26 297.98 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 294.06 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.56 650.73 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 250.63 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 175.58 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 174.78 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 185.30 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 188.41 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.61 705.85 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.60 695.14 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.55 638.21 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.52 602.65 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 419.49 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.36 418.25 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.39 447.58 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.39 448.58 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 483.93 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.40 469.34 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 442.61 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 407.56 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 314.03 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 313.92 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 346.90 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 347.45 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2624.65 3149.58 0.214 0.257 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 42.20 0.00720
G NW APARTMENT 2590.11 3108.14 0.211 0.253 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 40.82 0.00720
OFFICE 5600.71 6720.85 0.467 0.561 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 36.80 0.00720
G NE APARTMENT 2207.58 2649.09 0.180 0.216 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 40.19 0.00720
G N1 APARTMENT 1546.48 1855.77 0.126 0.151 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 39.62 0.00720
G N2 APARTMENT 1539.48 1847.37 0.125 0.151 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 39.62 0.00720
G S1 APARTMENT 1632.12 1958.55 0.133 0.160 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 43.25 0.00720
G S2 APARTMENT 1659.55 1991.46 0.135 0.162 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 43.25 0.00720
M SW APARTMENT 6217.18 7460.62 0.507 0.608 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 41.96 0.00720
M NW APARTMENT 6122.80 7347.35 0.499 0.599 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 41.12 0.00720
M SE APARTMENT 5621.38 6745.66 0.458 0.550 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 41.24 0.00720
M NE APARTMENT 5308.17 6369.81 0.433 0.519 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 40.64 0.00720
M N1 APARTMENT 3694.86 4433.84 0.301 0.361 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 40.07 0.00720
M N2 APARTMENT 3683.97 4420.76 0.300 0.360 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 40.07 0.00720
M S1 APARTMENT 3942.32 4730.78 0.321 0.386 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 43.25 0.00720
M S2 APARTMENT 3951.13 4741.35 0.322 0.386 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 43.25 0.00720
T SW APARTMENT 4262.51 5115.01 0.347 0.417 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 42.86 0.00720
T NW APARTMENT 4133.98 4960.77 0.337 0.404 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 42.20 0.00720
T SE APARTMENT 3898.59 4678.31 0.318 0.381 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 43.40 0.00720
T NE APARTMENT 3589.88 4307.86 0.293 0.351 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 43.40 0.00720
T N1 APARTMENT 2765.95 3319.14 0.225 0.271 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 43.22 0.00720
T N2 APARTMENT 2764.98 3317.98 0.225 0.270 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 43.22 0.00720
T S1 APARTMENT 3055.52 3666.62 0.249 0.299 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 43.40 0.00720
T S2 APARTMENT 3060.35 3672.43 0.249 0.299 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 43.40 0.00720


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 710.12 852.14 0.021 0.027 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
G NW APARTMENT 710.04 852.05 0.021 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
OFFICE 1733.63 2080.36 0.050 0.060 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 09:00:00 3.70 0.00513
G NE APARTMENT 715.01 858.01 0.021 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
G N1 APARTMENT 365.35 438.42 0.011 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
G N2 APARTMENT 365.42 438.50 0.011 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
G S1 APARTMENT 367.14 440.56 0.011 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
G S2 APARTMENT 425.74 510.89 0.013 0.026 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M SW APARTMENT 1271.32 1525.58 0.038 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M NW APARTMENT 1272.78 1527.33 0.038 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M SE APARTMENT 1284.15 1540.98 0.038 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M NE APARTMENT 1285.60 1542.72 0.039 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M N1 APARTMENT 433.40 520.08 0.013 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M N2 APARTMENT 433.64 520.36 0.013 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M S1 APARTMENT 433.03 519.63 0.013 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
M S2 APARTMENT 433.26 519.92 0.013 0.052 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T SW APARTMENT 1314.88 1577.85 0.039 0.047 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T NW APARTMENT 1316.26 1579.51 0.039 0.047 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T SE APARTMENT 1321.79 1586.15 0.040 0.048 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T NE APARTMENT 1323.18 1587.82 0.040 0.048 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T N1 APARTMENT 882.63 1059.16 0.026 0.032 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T N2 APARTMENT 882.76 1059.31 0.026 0.032 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T S1 APARTMENT 880.95 1057.14 0.026 0.032 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513
T S2 APARTMENT 881.07 1057.29 0.026 0.032 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 04:00:00 3.70 0.00513


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.26 0.26 0.03 0.03
SPLIT GNW 0.25 0.25 0.03 0.03
SPLIT OFFICE 0.56 0.56 0.06 0.06
SPLIT GNE 0.22 0.22 0.03 0.03
SPLIT GN1 0.15 0.15 0.03 0.03
SPLIT GN2 0.15 0.15 0.03 0.03
SPLIT GS1 0.16 0.16 0.03 0.03
SPLIT GS2 0.16 0.16 0.03 0.03
SPLIT MSW 0.61 0.61 0.05 0.05
SPLIT MNW 0.60 0.60 0.05 0.05
SPLIT MSE 0.55 0.55 0.05 0.05
SPLIT MNE 0.52 0.52 0.05 0.05
SPLIT MN1 0.36 0.36 0.05 0.05
SPLIT MN2 0.36 0.36 0.05 0.05
SPLIT MS1 0.39 0.39 0.05 0.05
SPLIT MS2 0.39 0.39 0.05 0.05
SPLIT TSW 0.42 0.42 0.05 0.05
SPLIT TNW 0.40 0.40 0.05 0.05
SPLIT TSE 0.38 0.38 0.05 0.05
SPLIT TNE 0.35 0.35 0.05 0.05
SPLIT TN1 0.27 0.27 0.03 0.03
SPLIT TN2 0.27 0.27 0.03 0.03
SPLIT TS1 0.30 0.30 0.03 0.03
SPLIT TS2 0.30 0.30 0.03 0.03



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 2618.75 4334.50 41.50
G NW APARTMENT 2410.75 4928.25 48.00
OFFICE 773.75 960.75 0.00
G NE APARTMENT 2394.50 4928.25 56.25
G N1 APARTMENT 2096.00 5278.50 59.50
G N2 APARTMENT 2094.50 5277.75 59.75
G S1 APARTMENT 2259.75 4835.75 45.75
G S2 APARTMENT 2378.75 4702.25 37.75
M SW APARTMENT 3640.50 1103.75 3.50
M NW APARTMENT 3153.75 2250.50 3.75
M SE APARTMENT 3672.75 1134.00 6.25
M NE APARTMENT 3186.00 2250.75 8.50
M N1 APARTMENT 2729.75 2186.50 8.25
M N2 APARTMENT 2730.25 2193.75 8.25
M S1 APARTMENT 3239.50 704.25 3.00
M S2 APARTMENT 3241.50 710.75 3.00
T SW APARTMENT 4268.75 2232.50 12.00
T NW APARTMENT 3792.25 2910.75 37.00
T SE APARTMENT 4293.25 2204.50 12.75
T NE APARTMENT 3835.25 2889.00 43.75
T N1 APARTMENT 3426.00 2930.50 12.25
T N2 APARTMENT 3426.25 2929.25 12.50
T S1 APARTMENT 3985.25 2083.75 8.25
T S2 APARTMENT 3986.00 2086.75 8.25
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4758.50 5283.75 97.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 0.25 0.00 0.25
G NW APARTMENT 0.00 3.75 0.00 3.75
OFFICE 0.00 29.75 0.00 0.00
G NE APARTMENT 0.25 0.50 0.25 0.50
G N1 APARTMENT 4.25 2.25 4.25 2.25
G N2 APARTMENT 5.25 2.00 5.25 2.00
G S1 APARTMENT 2.25 0.00 2.25 0.00
G S2 APARTMENT 2.25 0.00 2.25 0.00
M SW APARTMENT 0.00 0.00 0.00 0.00
M NW APARTMENT 0.00 0.75 0.00 0.75
M SE APARTMENT 0.00 0.00 0.00 0.00
M NE APARTMENT 0.00 0.00 0.00 0.00
M N1 APARTMENT 0.00 1.00 0.00 1.00
M N2 APARTMENT 0.00 1.00 0.00 1.00
M S1 APARTMENT 0.00 0.00 0.00 0.00
M S2 APARTMENT 0.00 0.00 0.00 0.00
T SW APARTMENT 0.00 1.25 0.00 1.25
T NW APARTMENT 0.00 2.00 0.00 2.00
T SE APARTMENT 0.00 0.25 0.00 0.25
T NE APARTMENT 0.00 0.50 0.00 0.50
T N1 APARTMENT 0.00 0.00 0.00 0.00
T N2 APARTMENT 0.00 0.00 0.00 0.00
T S1 APARTMENT 0.00 0.00 0.00 0.00
T S2 APARTMENT 0.00 0.00 0.00 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 11.25 39.50 11.25 9.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.368 0.119 0.000 0.068
G NW APARTMENT 1.71 2.50 268.97 0.355 0.119 0.000 0.065
OFFICE 0.94 1.00 268.97 0.521 0.136 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.355 0.119 0.000 0.064
G N1 APARTMENT 1.71 2.50 268.97 0.355 0.072 0.000 0.063
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.072 0.000 0.063
G S1 APARTMENT 1.71 2.50 268.97 0.355 0.072 0.000 0.067
G S2 APARTMENT 1.71 2.50 268.97 0.355 0.072 0.000 0.067
M SW APARTMENT 1.71 2.50 268.97 0.356 0.171 0.000 0.078
M NW APARTMENT 1.71 2.50 268.97 0.355 0.171 0.000 0.077
M SE APARTMENT 1.71 2.50 268.97 0.355 0.171 0.000 0.078
M NE APARTMENT 1.71 2.50 268.97 0.355 0.171 0.000 0.077
M N1 APARTMENT 1.71 2.50 268.97 0.355 0.103 0.000 0.077
M N2 APARTMENT 1.71 2.50 268.97 0.355 0.103 0.000 0.077
M S1 APARTMENT 1.71 2.50 268.97 0.356 0.103 0.000 0.078
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.103 0.000 0.078
T SW APARTMENT 1.71 2.50 268.97 0.355 0.227 0.000 0.089
T NW APARTMENT 1.71 2.50 268.97 0.355 0.227 0.000 0.087
T SE APARTMENT 1.71 2.50 268.97 0.355 0.227 0.000 0.089
T NE APARTMENT 1.71 2.50 268.97 0.355 0.227 0.000 0.088
T N1 APARTMENT 1.71 2.50 268.97 0.355 0.137 0.000 0.087
T N2 APARTMENT 1.71 2.50 268.97 0.355 0.137 0.000 0.087
T S1 APARTMENT 1.71 2.50 268.97 0.355 0.137 0.000 0.089
T S2 APARTMENT 1.71 2.50 268.97 0.355 0.137 0.000 0.089
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.357 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.507 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.386 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.381 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.385 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.381 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.384 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.384 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.389 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.389 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.345 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 310.06 0.00 01-JAN-00:15 31948.81 01-JAN-08:45
WaterSystems:Electricity 310.06 0.00 01-JAN-00:15 31948.81 01-JAN-08:45
Water Heater:WaterSystems:Electricity 310.06 0.00 01-JAN-00:15 31948.81 01-JAN-08:45
Fans:Electricity 306.50 9718.96 01-JAN-07:15 9718.96 01-JAN-00:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
ElectricityPurchased:Plant 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
Cogeneration:ElectricityPurchased 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
ElectricityNet:Plant 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
Cogeneration:ElectricityNet 1638.52 22831.58 01-JAN-03:15 93773.47 07-AUG-17:15
ExteriorLights:Electricity 40.09 0.00 01-JAN-07:45 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.09 0.00 01-JAN-07:45 2553.00 01-JAN-00:15
Electricity:HVAC 652.26 9718.96 01-JAN-07:15 47800.03 24-JUL-16:00
General:Fans:Electricity 306.50 9718.96 01-JAN-07:15 9718.96 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 345.76 0.00 01-JAN-01:45 38081.07 24-JUL-16:00


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 12.39 0.00 01-JAN-10:00 22335.71 10-FEB-07:00
Gas:HVAC 12.39 0.00 01-JAN-10:00 22335.71 10-FEB-07:00
Heating:Gas 12.39 0.00 01-JAN-10:00 22335.71 10-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2194.89 2397.17 09-MAR-00:15 215979.10 24-JUL-16:00
EnergyTransfer:Building 929.52 2067.55 30-MAR-06:00 90106.48 24-JUL-16:00
EnergyTransfer:Zone:G SW APARTMENT 23.02 0.00 05-FEB-20:15 3123.52 29-SEP-15:15
Heating:EnergyTransfer 20.07 0.00 30-JAN-20:00 13463.17 07-MAR-03:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.59 0.00 01-JAN-00:30 730.93 07-MAR-03:00
Cooling:EnergyTransfer 909.45 96.20 29-DEC-12:00 90106.48 24-JUL-16:00
Cooling:EnergyTransfer:Zone:G SW APARTMENT 22.43 0.00 01-JAN-00:15 3123.52 29-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 18.90 0.01 05-MAR-10:45 3081.93 08-JUL-17:30
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.42 0.00 01-JAN-09:00 738.71 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 17.48 0.00 01-JAN-00:15 3081.93 08-JUL-17:30
EnergyTransfer:Zone:OFFICE 39.41 0.02 13-DEC-20:00 5435.09 09-JUL-08:30
Heating:EnergyTransfer:Zone:OFFICE 7.06 0.00 01-JAN-03:30 1043.01 14-MAY-19:00
Cooling:EnergyTransfer:Zone:OFFICE 32.35 0.00 01-JAN-00:15 5435.09 09-JUL-08:30
EnergyTransfer:Zone:G NE APARTMENT 18.49 0.00 04-JAN-00:15 2412.48 16-JUL-18:15
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.16 0.00 01-JAN-08:00 743.41 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 17.32 0.00 01-JAN-00:15 2412.48 16-JUL-18:15
EnergyTransfer:Zone:G N1 APARTMENT 12.53 0.01 16-JAN-12:00 1794.75 08-JUL-17:45
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.48 0.00 01-JAN-00:15 346.22 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 12.05 0.00 01-JAN-07:00 1794.75 08-JUL-17:45
EnergyTransfer:Zone:G N2 APARTMENT 12.54 0.01 29-NOV-10:30 1786.04 08-JUL-17:45
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.48 0.00 01-JAN-00:15 346.87 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 12.06 0.00 01-JAN-07:00 1786.04 08-JUL-17:45
EnergyTransfer:Zone:G S1 APARTMENT 17.01 0.01 04-MAR-22:00 2105.55 29-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.09 0.00 01-JAN-00:15 333.94 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 16.92 0.00 01-JAN-17:15 2105.55 29-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 18.00 0.02 13-APR-03:30 2212.21 29-SEP-13:15
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.07 0.00 01-JAN-00:15 327.17 07-MAR-03:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 17.93 0.00 01-JAN-17:30 2212.21 29-SEP-13:15
EnergyTransfer:Zone:M SW APARTMENT 76.46 0.28 04-DEC-12:30 7283.85 29-SEP-15:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.02 0.00 01-JAN-00:15 448.36 07-MAR-05:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 76.44 0.00 02-JAN-00:15 7283.85 29-SEP-15:15
EnergyTransfer:Zone:M NW APARTMENT 58.98 0.01 11-NOV-02:00 7203.50 08-JUL-17:30
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.28 0.00 01-JAN-00:30 530.35 07-MAR-05:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 58.71 0.00 01-JAN-00:15 7203.50 08-JUL-17:30
EnergyTransfer:Zone:M SE APARTMENT 76.43 0.18 14-NOV-07:00 6367.34 02-SEP-11:30
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.01 0.00 01-JAN-00:15 506.92 07-MAR-05:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 76.42 0.00 02-JAN-19:00 6367.34 02-SEP-11:30
EnergyTransfer:Zone:M NE APARTMENT 59.00 0.10 23-DEC-14:15 5932.68 09-JUL-17:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.21 0.00 01-JAN-00:15 615.59 10-FEB-07:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 58.79 0.00 01-JAN-11:30 5932.68 09-JUL-17:00
EnergyTransfer:Zone:M N1 APARTMENT 45.90 0.42 06-DEC-12:30 4275.85 08-JUL-18:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.02 0.00 01-JAN-00:15 343.91 19-DEC-15:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 45.88 0.00 02-JAN-10:45 4275.85 08-JUL-18:00
EnergyTransfer:Zone:M N2 APARTMENT 45.90 0.03 02-JAN-12:15 4261.96 08-JUL-18:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.02 0.00 01-JAN-00:15 343.65 19-DEC-15:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 45.88 0.00 02-JAN-10:45 4261.96 08-JUL-18:00
EnergyTransfer:Zone:M S1 APARTMENT 64.18 46.59 10-APR-07:15 5234.47 14-OCT-13:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 64.18 46.59 10-APR-07:15 5234.47 14-OCT-13:45
EnergyTransfer:Zone:M S2 APARTMENT 64.18 45.88 10-APR-07:15 5240.19 14-OCT-13:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 64.18 45.88 10-APR-07:15 5240.19 14-OCT-13:45
EnergyTransfer:Zone:T SW APARTMENT 42.69 0.12 10-JAN-01:00 4900.24 16-JUL-17:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.35 0.00 01-JAN-08:45 1236.83 07-MAR-03:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 41.34 0.00 01-JAN-00:15 4900.24 16-JUL-17:00
EnergyTransfer:Zone:T NW APARTMENT 35.87 0.01 20-JAN-15:30 4861.33 16-JUL-17:15
Heating:EnergyTransfer:Zone:T NW APARTMENT 2.16 0.00 01-JAN-14:15 1243.14 07-MAR-03:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 33.70 0.00 01-JAN-00:15 4861.33 16-JUL-17:15
EnergyTransfer:Zone:T SE APARTMENT 42.26 0.27 10-DEC-19:30 4183.24 16-JUL-13:45
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.16 0.00 01-JAN-08:00 1239.59 07-MAR-03:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 41.10 0.00 01-JAN-00:15 4183.24 16-JUL-13:45
EnergyTransfer:Zone:T NE APARTMENT 35.10 0.01 08-NOV-09:30 4100.62 16-JUL-17:30
Heating:EnergyTransfer:Zone:T NE APARTMENT 1.77 0.00 01-JAN-08:30 1272.48 31-JAN-07:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 33.33 0.00 01-JAN-00:15 4100.62 16-JUL-17:30
EnergyTransfer:Zone:T N1 APARTMENT 26.84 0.00 03-DEC-01:45 3229.90 16-JUL-17:30
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.61 0.00 01-JAN-00:30 725.51 10-FEB-07:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 26.23 0.00 01-JAN-00:15 3229.90 16-JUL-17:30
EnergyTransfer:Zone:T N2 APARTMENT 26.85 0.00 23-FEB-02:15 3215.66 16-JUL-17:30
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.61 0.00 01-JAN-00:30 727.11 10-FEB-07:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 26.24 0.00 01-JAN-00:15 3215.66 16-JUL-17:30
EnergyTransfer:Zone:T S1 APARTMENT 34.49 0.00 29-JAN-02:00 3484.54 29-SEP-14:15
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.24 0.00 01-JAN-00:45 708.97 07-MAR-03:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 34.24 0.00 01-JAN-00:15 3484.54 29-SEP-14:15
EnergyTransfer:Zone:T S2 APARTMENT 34.50 0.01 05-MAR-22:45 3485.72 29-SEP-14:15
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.25 0.00 01-JAN-00:45 709.52 07-MAR-03:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 34.25 0.00 01-JAN-00:15 3485.72 29-SEP-14:15
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1265.37 0.00 16-FEB-05:00 126039.68 10-AUG-15:30
HeatingCoils:EnergyTransfer 9.91 0.00 01-JAN-10:00 17868.57 10-FEB-07:00
CoolingCoils:EnergyTransfer 1255.46 0.00 01-JAN-01:45 126039.68 10-AUG-15:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.588 -22.428 0.000 0.000 3.634 1.087 12.213 21.347 0.000 1.461 0.001 0.000 -3.969 0.000 -1.929 -12.004
G NW APARTMENT 1.424 -17.479 0.000 0.000 3.670 1.087 12.213 13.188 0.000 1.460 0.000 0.000 -4.043 0.000 -1.753 -9.766
OFFICE 7.060 -32.353 0.000 0.000 0.517 26.452 9.482 19.989 0.000 1.006 0.000 0.000 -4.525 0.000 -1.389 -26.239
G NE APARTMENT 1.164 -17.323 0.000 0.000 3.679 1.087 12.213 12.804 0.000 1.460 0.000 0.000 -3.747 0.000 -1.746 -9.591
G N1 APARTMENT 0.481 -12.052 0.000 0.000 3.685 1.087 12.213 5.361 0.000 0.892 0.000 0.000 -2.435 0.000 -1.244 -7.988
G N2 APARTMENT 0.480 -12.056 0.000 0.000 3.685 1.087 12.213 5.360 0.000 0.892 0.000 0.000 -2.433 0.000 -1.244 -7.985
G S1 APARTMENT 0.087 -16.918 0.000 0.000 3.634 1.087 12.213 13.611 0.000 0.892 0.000 0.000 -2.387 0.000 -1.463 -10.756
G S2 APARTMENT 0.074 -17.930 0.000 0.000 3.630 1.087 12.213 13.591 0.000 0.892 0.000 0.000 -2.400 0.000 -1.471 -9.686
M SW APARTMENT 0.016 -76.438 0.000 0.000 3.539 1.087 12.213 20.767 0.000 2.088 44.030 0.000 -4.582 0.000 -2.720 0.000
M NW APARTMENT 0.276 -58.705 0.000 0.000 3.563 1.087 12.213 12.720 0.000 2.087 34.151 0.000 -4.737 0.000 -2.655 0.000
M SE APARTMENT 0.011 -76.414 0.000 0.000 3.542 1.087 12.213 20.525 0.000 2.088 44.112 0.000 -4.447 0.000 -2.716 0.000
M NE APARTMENT 0.210 -58.787 0.000 0.000 3.571 1.087 12.213 12.277 0.000 2.087 34.368 0.000 -4.385 0.000 -2.641 0.000
M N1 APARTMENT 0.018 -45.878 0.000 0.000 3.553 1.087 12.213 5.086 0.000 1.272 27.561 0.000 -2.948 0.000 -1.964 0.000
M N2 APARTMENT 0.018 -45.878 0.000 0.000 3.554 1.087 12.213 5.086 0.000 1.272 27.558 0.000 -2.946 0.000 -1.963 0.000
M S1 APARTMENT 0.000 -64.184 0.000 0.000 3.529 1.087 12.213 13.234 0.000 1.273 37.640 0.000 -2.776 0.000 -2.015 0.000
M S2 APARTMENT 0.000 -64.180 0.000 0.000 3.529 1.087 12.213 13.234 0.000 1.273 37.636 0.000 -2.776 0.000 -2.015 0.000
T SW APARTMENT 1.353 -41.338 0.000 0.000 3.587 1.087 12.213 20.365 0.000 2.754 7.536 0.000 -4.306 0.000 -3.249 -0.000
T NW APARTMENT 2.163 -33.705 0.000 0.000 3.609 1.087 12.213 12.419 0.000 2.752 7.030 0.000 -4.426 0.000 -3.142 -0.000
T SE APARTMENT 1.165 -41.099 0.000 0.000 3.591 1.087 12.213 20.127 0.000 2.754 7.589 0.000 -4.180 0.000 -3.247 -0.001
T NE APARTMENT 1.771 -33.332 0.000 0.000 3.618 1.087 12.213 12.020 0.000 2.752 7.130 0.000 -4.122 0.000 -3.137 -0.000
T N1 APARTMENT 0.606 -26.231 0.000 0.000 3.607 1.087 12.213 4.973 0.000 1.679 7.044 0.000 -2.724 0.000 -2.254 -0.001
T N2 APARTMENT 0.613 -26.240 0.000 0.000 3.607 1.087 12.213 4.972 0.000 1.679 7.046 0.000 -2.722 0.000 -2.255 -0.000
T S1 APARTMENT 0.243 -34.243 0.000 0.000 3.576 1.087 12.213 13.000 0.000 1.681 7.425 0.000 -2.623 0.000 -2.358 -0.000
T S2 APARTMENT 0.246 -34.254 0.000 0.000 3.576 1.087 12.213 12.999 0.000 1.681 7.433 0.000 -2.622 0.000 -2.358 -0.000
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.495 0.000 0.297 0.000 0.000 -0.439 0.000 -0.464 -14.471
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 1.538 0.000 7.430 0.001 0.000 -0.989 0.000 -9.464 -19.575
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.520 0.000 0.248 0.000 0.000 -0.500 0.000 -0.395 -14.454
Total Facility 20.068 -909.444 0.000 0.000 83.285 95.189 296.854 311.612 0.000 48.101 345.290 0.000 -85.187 0.000 -63.250 -142.518


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-SEP-15:15 0.00 -3123.31 0.00 0.00 48.90 45.40 470.90 3071.49 0.00 177.52 0.00 0.00 0.00 0.00 0.00 -690.90
G NW APARTMENT 08-JUL-17:23 0.00 -3082.05 0.00 0.00 141.80 87.56 588.62 2249.56 0.00 428.41 0.00 0.00 0.00 0.00 0.00 -413.91
OFFICE 20-AUG-06:01 0.00 -8445.18 0.00 0.00 0.00 416.15 294.31 315.97 0.00 0.00 7452.91 0.00 0.00 0.00 -34.16 0.00
G NE APARTMENT 16-JUL-17:30 0.00 -2413.85 0.00 0.00 140.82 87.56 588.62 1334.71 0.00 442.89 0.00 0.00 0.00 0.00 0.00 -180.76
G N1 APARTMENT 08-JUL-17:45 0.00 -1794.74 0.00 0.00 141.80 87.56 588.62 814.88 0.00 248.76 0.00 0.00 0.00 0.00 0.00 -86.89
G N2 APARTMENT 08-JUL-17:45 0.00 -1786.02 0.00 0.00 141.80 87.56 588.62 815.00 0.00 248.76 0.00 0.00 0.00 0.00 0.00 -95.73
G S1 APARTMENT 29-SEP-13:30 0.00 -2105.56 0.00 0.00 40.75 12.97 382.60 2064.52 0.00 61.51 0.00 0.00 0.00 0.00 0.00 -456.79
G S2 APARTMENT 29-SEP-13:15 0.00 -2212.27 0.00 0.00 40.75 12.97 382.60 2097.33 0.00 60.99 0.00 0.00 0.00 0.00 0.00 -382.37
M SW APARTMENT 29-SEP-15:15 0.00 -7283.35 0.00 0.00 48.90 45.40 470.90 3047.20 0.00 254.79 3416.17 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 08-JUL-17:23 0.00 -7203.96 0.00 0.00 141.80 87.56 588.62 2228.85 0.00 614.99 3542.14 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 02-SEP-11:30 0.00 -6366.50 0.00 0.00 40.75 12.97 406.15 2451.52 0.00 388.71 3066.40 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 09-JUL-17:00 0.00 -5931.62 0.00 0.00 84.76 64.86 588.62 960.21 0.00 837.12 3396.05 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 08-JUL-17:53 0.00 -4276.23 0.00 0.00 141.81 87.56 588.62 826.97 0.00 343.24 2288.03 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 08-JUL-17:53 0.00 -4262.35 0.00 0.00 141.81 87.56 588.62 827.05 0.00 343.24 2274.07 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 14-OCT-13:45 0.00 -5234.54 0.00 0.00 40.75 12.97 382.60 2101.35 0.00 182.16 2514.71 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 14-OCT-13:45 0.00 -5240.25 0.00 0.00 40.75 12.97 382.60 2101.30 0.00 182.16 2520.47 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 16-JUL-17:00 0.00 -4900.67 0.00 0.00 84.76 64.86 588.62 2214.85 0.00 878.27 1069.31 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 16-JUL-17:15 0.00 -4864.71 0.00 0.00 141.20 87.56 588.62 2297.55 0.00 858.64 891.14 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 16-JUL-13:45 0.00 -4183.21 0.00 0.00 40.75 12.97 382.60 1521.47 0.00 823.10 1402.32 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 16-JUL-17:30 0.00 -4101.47 0.00 0.00 141.80 87.56 588.62 1305.95 0.00 845.44 1132.10 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 16-JUL-17:30 0.00 -3230.66 0.00 0.00 141.80 87.56 588.62 879.70 0.00 509.97 1023.01 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 16-JUL-17:23 0.00 -3215.92 0.00 0.00 141.80 87.56 588.62 879.89 0.00 509.97 1008.07 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 29-SEP-14:15 0.00 -3484.39 0.00 0.00 40.75 22.70 400.26 1855.94 0.00 143.58 1021.16 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 29-SEP-14:15 0.00 -3485.57 0.00 0.00 40.75 22.70 400.26 1855.90 0.00 143.58 1022.37 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-JUL-16:00 0.00 -90110.30 0.00 0.00 1191.99 4512.09 11708.34 30097.94 0.00 13293.76 29306.18 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 12-FEB-07:01 1223.85 0.00 0.00 0.00 162.43 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -608.88 0.00 -39.88 -1162.28
G NW APARTMENT 07-MAR-03:00 738.69 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -887.51 0.00 -221.55 -55.35
OFFICE 07-FEB-07:01 2482.39 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -725.66 0.00 -263.94 -2203.25
G NE APARTMENT 07-MAR-03:00 743.38 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -887.29 0.00 -221.55 -60.26
G N1 APARTMENT 03-APR-07:01 694.43 0.00 0.00 0.00 74.70 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -311.36 0.00 -109.43 -756.28
G N2 APARTMENT 11-DEC-07:01 1144.30 0.00 0.00 0.00 162.94 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -296.54 0.00 -120.56 -1314.90
G S1 APARTMENT 22-JAN-07:01 1060.61 0.00 0.00 0.00 163.40 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -425.26 0.00 -187.97 -1035.54
G S2 APARTMENT 24-JAN-07:02 537.38 0.00 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -449.32 0.00 -142.56 -531.48
M SW APARTMENT 07-MAR-05:00 448.35 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 322.63 0.00 -928.43 0.00 -275.36 0.00
M NW APARTMENT 16-DEC-07:11 626.84 0.00 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -753.37 0.00 -189.09 -270.36
M SE APARTMENT 07-MAR-05:00 506.92 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 262.65 0.00 -927.01 0.00 -275.36 0.00
M NE APARTMENT 10-FEB-07:00 615.57 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -778.57 0.00 -284.15 -105.77
M N1 APARTMENT 19-DEC-15:00 343.89 0.00 0.00 0.00 41.27 12.97 382.60 100.84 0.00 0.00 0.00 0.00 0.00 0.00 -50.06 -831.52
M N2 APARTMENT 19-DEC-15:00 343.63 0.00 0.00 0.00 41.29 12.97 382.60 100.97 0.00 0.00 0.00 0.00 0.00 0.00 -49.71 -831.75
M S1 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 07-MAR-03:00 1236.80 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -879.24 0.00 -422.73 -360.55
T NW APARTMENT 07-MAR-03:00 1243.10 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -876.99 0.00 -422.73 -369.10
T SE APARTMENT 07-MAR-03:00 1239.55 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -879.17 0.00 -422.73 -363.37
T NE APARTMENT 31-JAN-07:00 1272.50 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -745.24 0.00 -451.28 -628.91
T N1 APARTMENT 10-FEB-07:00 725.49 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -457.63 0.00 -227.18 -593.61
T N2 APARTMENT 10-FEB-07:00 727.10 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -457.59 0.00 -227.18 -595.25
T S1 APARTMENT 07-MAR-03:00 708.95 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -536.61 0.00 -254.99 -343.07
T S2 APARTMENT 07-MAR-03:00 709.50 0.00 0.00 0.00 189.67 6.49 229.56 0.00 0.00 0.00 0.00 0.00 -536.59 0.00 -254.99 -343.64
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 07-MAR-03:00 11434.28 0.00 0.00 0.00 4338.32 1952.47 5522.42 0.00 0.00 0.00 978.75 0.00 -17855.82 0.00 -6370.44 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Sec1.1A-General Information

Data
Weather File Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 11.25
Number of hours cooling loads not met 9.75
Number of hours not met 21.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.09 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 12.39 22335.71 0.00 0.00
Space Cooling 345.76 33445.01 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 306.50 9718.96 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 310.06 18998.62 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1638.52   12.39   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1638.52
Natural Gas 0.00 12.39
Additional 0.00 0.00
Total 517.65 1650.91


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 110.30
Fans-Interior 97.78
Service Water Heating 98.92
Receptacle Equipment 165.14
Miscellaneous 12.79
Subtotal 522.72


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 3.95
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 3.95


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.18
Space Heating 0.75
Space Cooling 20.94
Fans-Interior 18.57
Service Water Heating 18.78
Receptacle Equipment 31.36
Miscellaneous 2.43



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.256697
G NW APARTMENT DIRECT AIR 0.253320
OFFICE DIRECT AIR 0.560566
G NE APARTMENT DIRECT AIR 0.215907
G N1 APARTMENT DIRECT AIR 0.151250
G N2 APARTMENT DIRECT AIR 0.150566
G S1 APARTMENT DIRECT AIR 0.159626
G S2 APARTMENT DIRECT AIR 0.162308
M SW APARTMENT DIRECT AIR 0.608051
M NW APARTMENT DIRECT AIR 0.598823
M SE APARTMENT DIRECT AIR 0.549780
M NE APARTMENT DIRECT AIR 0.519148
M N1 APARTMENT DIRECT AIR 0.361368
M N2 APARTMENT DIRECT AIR 0.360303
M S1 APARTMENT DIRECT AIR 0.385569
M S2 APARTMENT DIRECT AIR 0.386430
T SW APARTMENT DIRECT AIR 0.416878
T NW APARTMENT DIRECT AIR 0.404307
T SE APARTMENT DIRECT AIR 0.381286
T NE APARTMENT DIRECT AIR 0.351094
T N1 APARTMENT DIRECT AIR 0.270516
T N2 APARTMENT DIRECT AIR 0.270421
T S1 APARTMENT DIRECT AIR 0.298836
T S2 APARTMENT DIRECT AIR 0.299309


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.256697
SPLIT GNW MAIN BRANCH 0.253320
SPLIT OFFICE MAIN BRANCH 0.560566
SPLIT GNE MAIN BRANCH 0.215907
SPLIT GN1 MAIN BRANCH 0.151250
SPLIT GN2 MAIN BRANCH 0.150566
SPLIT GS1 MAIN BRANCH 0.159626
SPLIT GS2 MAIN BRANCH 0.162308
SPLIT MSW MAIN BRANCH 0.608051
SPLIT MNW MAIN BRANCH 0.598823
SPLIT MSE MAIN BRANCH 0.549780
SPLIT MNE MAIN BRANCH 0.519148
SPLIT MN1 MAIN BRANCH 0.361368
SPLIT MN2 MAIN BRANCH 0.360303
SPLIT MS1 MAIN BRANCH 0.385569
SPLIT MS2 MAIN BRANCH 0.386430
SPLIT TSW MAIN BRANCH 0.416878
SPLIT TNW MAIN BRANCH 0.404307
SPLIT TSE MAIN BRANCH 0.381286
SPLIT TNE MAIN BRANCH 0.351094
SPLIT TN1 MAIN BRANCH 0.270516
SPLIT TN2 MAIN BRANCH 0.270421
SPLIT TS1 MAIN BRANCH 0.298836
SPLIT TS2 MAIN BRANCH 0.299309


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.256697
SPLIT GNW 0.253320
SPLIT OFFICE 0.560566
SPLIT GNE 0.215907
SPLIT GN1 0.151250
SPLIT GN2 0.150566
SPLIT GS1 0.159626
SPLIT GS2 0.162308
SPLIT MSW 0.608051
SPLIT MNW 0.598823
SPLIT MSE 0.549780
SPLIT MNE 0.519148
SPLIT MN1 0.361368
SPLIT MN2 0.360303
SPLIT MS1 0.385569
SPLIT MS2 0.386430
SPLIT TSW 0.416878
SPLIT TNW 0.404307
SPLIT TSE 0.381286
SPLIT TNE 0.351094
SPLIT TN1 0.270516
SPLIT TN2 0.270421
SPLIT TS1 0.298836
SPLIT TS2 0.299309


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.256697 0.026898
SPLIT GNW OA CONTROLLER 0.253320 0.025953
SPLIT OFFICE OA CONTROLLER 0.560566 0.038104
SPLIT GNE OA CONTROLLER 0.215907 0.025953
SPLIT GN1 OA CONTROLLER 0.151250 0.025953
SPLIT GN2 OA CONTROLLER 0.150566 0.025953
SPLIT GS1 OA CONTROLLER 0.159626 0.025953
SPLIT GS2 OA CONTROLLER 0.162308 0.025953
SPLIT MSW OA CONTROLLER 0.608051 0.051906
SPLIT MNW OA CONTROLLER 0.598823 0.051906
SPLIT MSE OA CONTROLLER 0.549780 0.051906
SPLIT MNE OA CONTROLLER 0.519148 0.051906
SPLIT MN1 OA CONTROLLER 0.361368 0.051906
SPLIT MN2 OA CONTROLLER 0.360303 0.051906
SPLIT MS1 OA CONTROLLER 0.385569 0.051906
SPLIT MS2 OA CONTROLLER 0.386430 0.051906
SPLIT TSW OA CONTROLLER 0.416878 0.025953
SPLIT TNW OA CONTROLLER 0.404307 0.025953
SPLIT TSE OA CONTROLLER 0.381286 0.025953
SPLIT TNE OA CONTROLLER 0.351094 0.025953
SPLIT TN1 OA CONTROLLER 0.270516 0.025953
SPLIT TN2 OA CONTROLLER 0.270421 0.025953
SPLIT TS1 OA CONTROLLER 0.298836 0.025953
SPLIT TS2 OA CONTROLLER 0.299309 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.256697 4908.30 0.749289
SPLIT GNW COOLING COIL 0.253320 4706.32 0.758582
SPLIT OFFICE COOLING COIL 0.560566 9279.36 0.798655
SPLIT GNE COOLING COIL 0.215907 4003.88 0.759184
SPLIT GN1 COOLING COIL 0.151250 2905.22 0.747847
SPLIT GN2 COOLING COIL 0.150566 2893.68 0.747671
SPLIT GS1 COOLING COIL 0.159626 3294.66 0.725867
SPLIT GS2 COOLING COIL 0.162308 3342.35 0.726543
SPLIT MSW COOLING COIL 0.608051 11351.41 0.757004
SPLIT MNW COOLING COIL 0.598823 11015.27 0.761853
SPLIT MSE COOLING COIL 0.549780 10183.62 0.759563
SPLIT MNE COOLING COIL 0.519148 9541.04 0.762152
SPLIT MN1 COOLING COIL 0.361368 6846.63 0.752222
SPLIT MN2 COOLING COIL 0.360303 6828.62 0.752120
SPLIT MS1 COOLING COIL 0.385569 7753.24 0.733657
SPLIT MS2 COOLING COIL 0.386430 7768.52 0.733736
SPLIT TSW COOLING COIL 0.416878 7749.77 0.758380
SPLIT TNW COOLING COIL 0.404307 7430.85 0.762135
SPLIT TSE COOLING COIL 0.381286 7206.01 0.753024
SPLIT TNE COOLING COIL 0.351094 6671.19 0.751296
SPLIT TN1 COOLING COIL 0.270516 5242.50 0.745041
SPLIT TN2 COOLING COIL 0.270421 5240.83 0.745031
SPLIT TS1 COOLING COIL 0.298836 5765.89 0.746427
SPLIT TS2 COOLING COIL 0.299309 5774.29 0.746467


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.256697 0.256697 0.256697 0.256697 1447.88 4908.30 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.253320 0.253320 0.253320 0.253320 1396.99 4706.32 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.560566 0.560566 0.560566 0.560566 2781.59 9279.36 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.215907 0.215907 0.215907 0.215907 1396.99 4003.88 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.151250 0.151250 0.151250 0.151250 1396.99 2905.22 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.150566 0.150566 0.150566 0.150566 1396.99 2893.68 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.159626 0.159626 0.159626 0.159626 1396.99 3294.66 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.162308 0.162308 0.162308 0.162308 1396.99 3342.35 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.608051 0.608051 0.608051 0.608051 2793.97 11351.41 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.598823 0.598823 0.598823 0.598823 2793.97 11015.27 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.549780 0.549780 0.549780 0.549780 2793.97 10183.62 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.519148 0.519148 0.519148 0.519148 2793.97 9541.04 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.361368 0.361368 0.361368 0.361368 2793.97 6846.63 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.360303 0.360303 0.360303 0.360303 2793.97 6828.62 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.385569 0.385569 0.385569 0.385569 2793.97 7753.24 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.386430 0.386430 0.386430 0.386430 2793.97 7768.52 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.416878 0.416878 0.416878 0.416878 2097.95 7749.77 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.404307 0.404307 0.404307 0.404307 2099.59 7430.85 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.381286 0.381286 0.381286 0.381286 2106.14 7206.01 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.351094 0.351094 0.351094 0.351094 2107.78 6671.19 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.270516 0.270516 0.270516 0.270516 1586.83 5242.50 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.270421 0.270421 0.270421 0.270421 1586.98 5240.83 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.298836 0.298836 0.298836 0.298836 1584.84 5765.89 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.299309 0.299309 0.299309 0.299309 1584.99 5774.29 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.256697
SPLIT GNW SUPPLY FAN 0.253320
SPLIT OFFICE SUPPLY FAN 0.560566
SPLIT GNE SUPPLY FAN 0.215907
SPLIT GN1 SUPPLY FAN 0.151250
SPLIT GN2 SUPPLY FAN 0.150566
SPLIT GS1 SUPPLY FAN 0.159626
SPLIT GS2 SUPPLY FAN 0.162308
SPLIT MSW SUPPLY FAN 0.608051
SPLIT MNW SUPPLY FAN 0.598823
SPLIT MSE SUPPLY FAN 0.549780
SPLIT MNE SUPPLY FAN 0.519148
SPLIT MN1 SUPPLY FAN 0.361368
SPLIT MN2 SUPPLY FAN 0.360303
SPLIT MS1 SUPPLY FAN 0.385569
SPLIT MS2 SUPPLY FAN 0.386430
SPLIT TSW SUPPLY FAN 0.416878
SPLIT TNW SUPPLY FAN 0.404307
SPLIT TSE SUPPLY FAN 0.381286
SPLIT TNE SUPPLY FAN 0.351094
SPLIT TN1 SUPPLY FAN 0.270516
SPLIT TN2 SUPPLY FAN 0.270421
SPLIT TS1 SUPPLY FAN 0.298836
SPLIT TS2 SUPPLY FAN 0.299309


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1447.88
SPLIT GNW HEATING COIL 1396.99
SPLIT OFFICE HEATING COIL 2781.59
SPLIT GNE HEATING COIL 1396.99
SPLIT GN1 HEATING COIL 1396.99
SPLIT GN2 HEATING COIL 1396.99
SPLIT GS1 HEATING COIL 1396.99
SPLIT GS2 HEATING COIL 1396.99
SPLIT MSW HEATING COIL 2793.97
SPLIT MNW HEATING COIL 2793.97
SPLIT MSE HEATING COIL 2793.97
SPLIT MNE HEATING COIL 2793.97
SPLIT MN1 HEATING COIL 2793.97
SPLIT MN2 HEATING COIL 2793.97
SPLIT MS1 HEATING COIL 2793.97
SPLIT MS2 HEATING COIL 2793.97
SPLIT TSW HEATING COIL 2097.95
SPLIT TNW HEATING COIL 2099.59
SPLIT TSE HEATING COIL 2106.14
SPLIT TNE HEATING COIL 2107.78
SPLIT TN1 HEATING COIL 1586.83
SPLIT TN2 HEATING COIL 1586.98
SPLIT TS1 HEATING COIL 1584.84
SPLIT TS2 HEATING COIL 1584.99



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:13

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.06 13.01
February 23.34 15.66
March 23.67 17.34
April 24.09 23.65
May 24.35 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.33 24.81
November 23.97 17.95
December 22.96 11.71
     
Annual Sum or Average 23.95 23.80
Minimum of Months 22.96 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.40 13.01
February 22.91 15.66
March 23.42 17.34
April 24.03 23.65
May 24.35 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.28 24.81
November 23.61 17.95
December 22.25 11.71
     
Annual Sum or Average 23.74 23.80
Minimum of Months 22.25 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.95 13.01
February 24.49 15.66
March 25.03 17.34
April 26.04 23.65
May 26.59 27.29
June 27.64 33.99
July 27.76 35.56
August 27.58 33.82
September 27.73 30.39
October 26.48 24.81
November 25.24 17.95
December 23.80 11.71
     
Annual Sum or Average 26.03 23.80
Minimum of Months 23.80 11.71
Maximum of Months 27.76 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.27 13.01
February 22.87 15.66
March 23.41 17.34
April 24.04 23.65
May 24.35 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.29 24.81
November 23.62 17.95
December 22.13 11.71
     
Annual Sum or Average 23.72 23.80
Minimum of Months 22.13 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 13.01
February 22.72 15.66
March 23.23 17.34
April 23.95 23.65
May 24.32 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.26 24.81
November 23.47 17.95
December 22.06 11.71
     
Annual Sum or Average 23.65 23.80
Minimum of Months 22.06 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 13.01
February 22.71 15.66
March 23.23 17.34
April 23.95 23.65
May 24.32 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.26 24.81
November 23.47 17.95
December 22.06 11.71
     
Annual Sum or Average 23.65 23.80
Minimum of Months 22.06 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.09 13.01
February 23.34 15.66
March 23.62 17.34
April 24.07 23.65
May 24.33 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.33 24.81
November 23.99 17.95
December 23.01 11.71
     
Annual Sum or Average 23.95 23.80
Minimum of Months 23.01 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.12 13.01
February 23.37 15.66
March 23.66 17.34
April 24.09 23.65
May 24.34 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.34 24.81
November 24.01 17.95
December 23.04 11.71
     
Annual Sum or Average 23.97 23.80
Minimum of Months 23.04 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.19 13.01
February 24.15 15.66
March 24.24 17.34
April 24.36 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.39 17.95
December 24.06 11.71
     
Annual Sum or Average 24.32 23.80
Minimum of Months 24.06 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.83 13.01
February 23.89 15.66
March 24.19 17.34
April 24.35 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.36 17.95
December 23.47 11.71
     
Annual Sum or Average 24.21 23.80
Minimum of Months 23.47 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 13.01
February 24.14 15.66
March 24.23 17.34
April 24.36 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.39 17.95
December 24.02 11.71
     
Annual Sum or Average 24.31 23.80
Minimum of Months 24.02 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 13.01
February 23.85 15.66
March 24.16 17.34
April 24.35 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.39 24.81
November 24.35 17.95
December 23.36 11.71
     
Annual Sum or Average 24.18 23.80
Minimum of Months 23.36 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.96 13.01
February 23.97 15.66
March 24.23 17.34
April 24.37 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.38 17.95
December 23.62 11.71
     
Annual Sum or Average 24.24 23.80
Minimum of Months 23.62 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.95 13.01
February 23.96 15.66
March 24.23 17.34
April 24.37 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.38 17.95
December 23.61 11.71
     
Annual Sum or Average 24.24 23.80
Minimum of Months 23.61 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 13.01
February 24.27 15.66
March 24.30 17.34
April 24.38 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.40 17.95
December 24.23 11.71
     
Annual Sum or Average 24.36 23.80
Minimum of Months 24.23 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.30 13.01
February 24.27 15.66
March 24.30 17.34
April 24.38 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.40 24.81
November 24.40 17.95
December 24.23 11.71
     
Annual Sum or Average 24.36 23.80
Minimum of Months 24.23 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.53 13.01
February 23.77 15.66
March 24.05 17.34
April 24.26 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.37 24.81
November 24.22 17.95
December 23.36 11.71
     
Annual Sum or Average 24.13 23.80
Minimum of Months 23.36 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.09 13.01
February 23.54 15.66
March 23.96 17.34
April 24.23 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.34 24.81
November 24.06 17.95
December 22.87 11.71
     
Annual Sum or Average 24.01 23.80
Minimum of Months 22.87 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.50 13.01
February 23.76 15.66
March 24.03 17.34
April 24.27 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.37 24.81
November 24.20 17.95
December 23.35 11.71
     
Annual Sum or Average 24.12 23.80
Minimum of Months 23.35 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.99 13.01
February 23.51 15.66
March 23.95 17.34
April 24.24 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.35 24.81
November 24.07 17.95
December 22.78 11.71
     
Annual Sum or Average 23.99 23.80
Minimum of Months 22.78 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.06 13.01
February 23.56 15.66
March 23.99 17.34
April 24.26 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.35 24.81
November 24.10 17.95
December 22.84 11.71
     
Annual Sum or Average 24.01 23.80
Minimum of Months 22.84 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 13.01
February 23.56 15.66
March 23.99 17.34
April 24.26 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.35 24.81
November 24.10 17.95
December 22.84 11.71
     
Annual Sum or Average 24.01 23.80
Minimum of Months 22.84 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 13.01
February 23.87 15.66
March 24.10 17.34
April 24.29 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.38 24.81
November 24.27 17.95
December 23.50 11.71
     
Annual Sum or Average 24.17 23.80
Minimum of Months 23.50 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.67 13.01
February 23.87 15.66
March 24.10 17.34
April 24.29 23.65
May 24.40 27.29
June 24.40 33.99
July 24.40 35.56
August 24.40 33.82
September 24.40 30.39
October 24.38 24.81
November 24.27 17.95
December 23.50 11.71
     
Annual Sum or Average 24.17 23.80
Minimum of Months 23.50 11.71
Maximum of Months 24.40 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.09 13.01
February 24.84 15.66
March 25.45 17.34
April 26.36 23.65
May 26.98 27.29
June 27.73 33.99
July 27.98 35.56
August 27.73 33.82
September 27.32 30.39
October 26.59 24.81
November 25.55 17.95
December 23.83 11.71
     
Annual Sum or Average 26.21 23.80
Minimum of Months 23.83 11.71
Maximum of Months 27.98 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.11 13.01
February 22.81 15.66
March 23.47 17.34
April 25.08 23.65
May 26.04 27.29
June 28.17 33.99
July 28.61 35.56
August 28.29 33.82
September 27.72 30.39
October 25.74 24.81
November 23.89 17.95
December 21.80 11.71
     
Annual Sum or Average 25.32 23.80
Minimum of Months 21.80 11.71
Maximum of Months 28.61 35.56



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:48:13

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.86 13.01
February 25.96 15.66
March 26.28 17.34
April 26.69 23.65
May 26.92 27.29
June 27.25 33.99
July 27.33 35.56
August 27.23 33.82
September 27.09 30.39
October 26.82 24.81
November 26.47 17.95
December 25.57 11.71
     
Annual Sum or Average 26.63 23.80
Minimum of Months 25.57 11.71
Maximum of Months 27.33 35.56



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:13

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.120900E+12 75295.755 01-JAN-18:45 4979.953 26630.920 9718.964 0.000 3013.678 2553.000 0.000 0.000 0.000 0.000 0.000 28399.239 0.000 0.000 0.000
February 0.112913E+12 79813.784 27-FEB-18:30 4979.953 26630.920 9718.964 0.000 14043.702 2553.000 0.000 0.000 0.000 0.000 0.000 21887.244 0.000 0.000 0.000
March 0.125714E+12 77496.207 18-MAR-17:15 4979.953 26630.920 9718.964 0.000 15932.427 0.000 0.000 0.000 0.000 0.000 0.000 20233.942 0.000 0.000 0.000
April 0.130817E+12 79796.111 26-APR-16:30 4276.255 26730.986 9718.964 0.000 24784.694 0.000 0.000 0.000 0.000 0.000 0.000 14285.211 0.000 0.000 0.000
May 0.140762E+12 85899.165 15-MAY-16:00 4276.255 26730.986 9718.964 0.000 28530.378 0.000 0.000 0.000 0.000 0.000 0.000 16642.581 0.000 0.000 0.000
June 0.153116E+12 91085.279 26-JUN-17:30 4979.953 26630.920 9718.964 0.000 32722.468 0.000 0.000 0.000 0.000 0.000 0.000 17032.972 0.000 0.000 0.000
July 0.166786E+12 93685.977 16-JUL-17:45 4979.953 26630.920 9718.964 0.000 36416.679 0.000 0.000 0.000 0.000 0.000 0.000 15939.460 0.000 0.000 0.000
August 0.161384E+12 93773.473 07-AUG-17:15 4979.953 26630.920 9718.964 0.000 33445.013 0.000 0.000 0.000 0.000 0.000 0.000 18998.622 0.000 0.000 0.000
September 0.146352E+12 89332.379 11-SEP-16:45 4276.255 26730.986 9718.964 0.000 29303.337 0.000 0.000 0.000 0.000 0.000 0.000 19302.836 0.000 0.000 0.000
October 0.138634E+12 86440.896 14-OCT-16:30 4276.255 26630.920 9718.964 0.000 25611.277 0.000 0.000 0.000 0.000 0.000 0.000 20203.479 0.000 0.000 0.000
November 0.122026E+12 71567.160 18-NOV-18:30 4979.953 26630.920 9718.964 0.000 8411.735 2553.000 0.000 0.000 0.000 0.000 0.000 19272.587 0.000 0.000 0.000
December 0.119119E+12 69998.951 21-DEC-18:15 4979.953 26630.920 9718.964 0.000 2414.620 2553.000 0.000 0.000 0.000 0.000 0.000 23701.494 0.000 0.000 0.000
                                     
Annual Sum or Average 0.163852E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.112913E+12 69998.951   4276.255 26630.920 9718.964 0.000 2414.620 0.000 0.000 0.000 0.000 0.000 0.000 14285.211 0.000 0.000 0.000
Maximum of Months 0.166786E+12 93773.473   4979.953 26730.986 9718.964 0.000 36416.679 2553.000 0.000 0.000 0.000 0.000 0.000 28399.239 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:13

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.324114E+10 17928.371 31-JAN-07:15 17928.371 0.000 0.000 0.000 0.000 0.000 17928.371
February 0.259538E+10 22335.714 10-FEB-06:00 22335.714 0.000 0.000 0.000 0.000 0.000 22335.714
March 0.139082E+10 21269.975 07-MAR-02:00 21269.975 0.000 0.000 0.000 0.000 0.000 21269.975
April 0.289841E+09 11016.630 03-APR-05:00 11016.630 0.000 0.000 0.000 0.000 0.000 11016.630
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 01-OCT-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.104730E+08 738.740 25-NOV-06:00 738.740 0.000 0.000 0.000 0.000 0.000 738.740
December 0.486053E+10 17650.926 16-DEC-03:00 17650.926 0.000 0.000 0.000 0.000 0.000 17650.926
                     
Annual Sum or Average 0.123882E+11       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.486053E+10 22335.714   22335.714 0.000 0.000 0.000 0.000 0.000 22335.714