Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2015-09-09 18:47:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1521.56 | 485.41 | 538.80 |
Net Site Energy | 1521.56 | 485.41 | 538.80 |
Total Source Energy | 4716.25 | 1504.57 | 1670.07 |
Net Source Energy | 4716.25 | 1504.57 | 1670.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 49.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 193.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 347.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1472.34 | 49.22 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 49.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 193.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 347.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 281.90 | 17.43 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 521.37 | 17.43 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.96 | 15.70 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.70 | 15.70 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1472.34 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1472.34 | 100.00 |
Total On-Site and Utility Electric Sources | 1472.34 | 100.00 |
Total Electricity End Uses | 1472.34 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 34.25 |
Time Setpoint Not Met During Occupied Cooling | 3.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 878.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-17:45 | 28-JAN-05:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 38020.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22630.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8103.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 21556.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83900.92 | 38020.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 38020.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 22630.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8103.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 21556.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 53.36 | 0.00 | 0.00 | 0.00 |
Cooling | 611.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 809.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1100.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4662.89 | 53.36 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 18.89 | 0.00 | 0.00 | 0.00 |
Cooling | 216.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 389.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1651.18 | 18.89 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 18.89 | 0.00 | 0.00 | 0.00 |
Cooling | 216.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 389.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1651.18 | 18.89 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.848 | 0.287 | 0.200 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.848 | 0.287 | 0.200 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.62_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.848 | 0.287 | 0.200 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.62_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.848 | 0.287 | 0.200 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.62_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.848 | 0.287 | 0.200 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.848 | 0.287 | 0.200 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 112.97 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 193.95 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.77 | 83.77 | 40.15 | |
Exterior Lighting Total | 2553.00 | 40.15 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3238.79 | 2586.68 | 652.11 | 0.80 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3214.51 | 2567.28 | 647.22 | 0.80 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8722.60 | 6966.35 | 1756.25 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2574.86 | 2056.43 | 518.44 | 0.80 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2018.24 | 1611.88 | 406.36 | 0.80 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2005.65 | 1601.83 | 403.83 | 0.80 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1973.91 | 1576.47 | 397.44 | 0.80 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2099.96 | 1640.94 | 459.02 | 0.78 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8227.20 | 6570.69 | 1656.50 | 0.80 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8160.59 | 6517.50 | 1643.09 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7185.49 | 5738.73 | 1446.76 | 0.80 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6774.24 | 5410.28 | 1363.96 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5264.22 | 4204.30 | 1059.92 | 0.80 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5243.97 | 4188.13 | 1055.85 | 0.80 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5294.44 | 4189.51 | 1104.93 | 0.79 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5305.85 | 4198.98 | 1106.88 | 0.79 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5871.35 | 4689.18 | 1182.17 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5726.07 | 4573.16 | 1152.91 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5356.85 | 4278.28 | 1078.57 | 0.80 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5031.75 | 4018.63 | 1013.12 | 0.80 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3987.09 | 3184.31 | 802.78 | 0.80 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3986.98 | 3184.22 | 802.76 | 0.80 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4294.29 | 3429.66 | 864.63 | 0.80 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4300.53 | 3434.64 | 865.89 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3085.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3062.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8309.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2453.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1922.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1910.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1880.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2005.1 | 3.16 | 10.77 | 11.20 | 10.52 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7837.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7774.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6845.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6453.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5015.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4995.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5048.7 | 3.14 | 10.71 | 11.14 | 10.44 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5059.6 | 3.14 | 10.71 | 11.13 | 10.44 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5593.4 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5455.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5103.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4793.5 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3798.3 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3798.2 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4091.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4096.9 | 3.13 | 10.67 | 11.09 | 10.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1946.11 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1928.35 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 3616.86 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1933.09 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1503.38 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1504.62 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 3739.52 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 3761.73 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 3752.38 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 3774.58 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3006.76 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2971.95 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2985.12 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2978.70 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2991.88 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2320.77 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2320.96 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2305.62 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2305.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 227.12 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 225.42 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.53 | 611.68 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 180.57 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 141.53 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 140.65 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 138.42 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 140.36 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.50 | 576.94 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 572.27 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.43 | 503.89 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 475.05 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 369.16 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 367.74 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 363.86 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 364.72 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 411.74 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 401.55 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 375.66 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 352.86 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 279.60 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 279.59 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.14 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 301.58 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1805.78 | 2166.94 | 0.163 | 0.196 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
G NW APARTMENT | 1792.23 | 2150.68 | 0.162 | 0.194 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63 | 0.00682 |
OFFICE | 4629.50 | 5555.40 | 0.439 | 0.527 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 32.05 | 0.00682 |
G NE APARTMENT | 1435.60 | 1722.72 | 0.130 | 0.156 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
G N1 APARTMENT | 1125.25 | 1350.30 | 0.102 | 0.122 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G N2 APARTMENT | 1118.23 | 1341.88 | 0.101 | 0.121 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 34.49 | 0.00682 |
G S1 APARTMENT | 1100.53 | 1320.64 | 0.099 | 0.119 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
G S2 APARTMENT | 1115.92 | 1339.10 | 0.101 | 0.121 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
M SW APARTMENT | 4587.08 | 5504.50 | 0.414 | 0.497 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
M NW APARTMENT | 4549.91 | 5459.90 | 0.411 | 0.493 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 35.63 | 0.00682 |
M SE APARTMENT | 4006.28 | 4807.53 | 0.362 | 0.434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 37.94 | 0.00682 |
M NE APARTMENT | 3776.94 | 4532.33 | 0.341 | 0.409 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M N1 APARTMENT | 2935.02 | 3522.03 | 0.265 | 0.318 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M N2 APARTMENT | 2923.73 | 3508.48 | 0.264 | 0.317 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
M S1 APARTMENT | 2892.86 | 3471.44 | 0.261 | 0.313 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
M S2 APARTMENT | 2899.76 | 3479.71 | 0.262 | 0.314 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T SW APARTMENT | 3273.61 | 3928.33 | 0.296 | 0.355 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
T NW APARTMENT | 3192.61 | 3831.13 | 0.288 | 0.346 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
T SE APARTMENT | 2986.74 | 3584.09 | 0.270 | 0.324 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
T NE APARTMENT | 2805.48 | 3366.58 | 0.253 | 0.304 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10 | 0.00682 |
T N1 APARTMENT | 2222.99 | 2667.59 | 0.201 | 0.241 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
T N2 APARTMENT | 2222.93 | 2667.52 | 0.201 | 0.241 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
T S1 APARTMENT | 2394.27 | 2873.13 | 0.216 | 0.259 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
T S2 APARTMENT | 2397.75 | 2877.30 | 0.216 | 0.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1003.63 | 1204.35 | 0.033 | 0.040 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G NW APARTMENT | 1011.18 | 1213.41 | 0.034 | 0.040 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
OFFICE | 2195.55 | 2634.66 | 0.070 | 0.084 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G NE APARTMENT | 1015.18 | 1218.22 | 0.034 | 0.040 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N1 APARTMENT | 582.26 | 698.72 | 0.019 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G N2 APARTMENT | 582.36 | 698.84 | 0.019 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S1 APARTMENT | 576.16 | 691.40 | 0.019 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
G S2 APARTMENT | 652.84 | 783.41 | 0.022 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
M SW APARTMENT | 1923.30 | 2307.97 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M NW APARTMENT | 1942.08 | 2330.50 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M SE APARTMENT | 1934.18 | 2321.02 | 0.064 | 0.077 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M NE APARTMENT | 1952.95 | 2343.54 | 0.065 | 0.078 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M N1 APARTMENT | 872.05 | 1046.46 | 0.029 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M N2 APARTMENT | 872.35 | 1046.82 | 0.029 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M S1 APARTMENT | 854.63 | 1025.56 | 0.028 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
M S2 APARTMENT | 854.93 | 1025.91 | 0.028 | 0.052 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T SW APARTMENT | 1893.73 | 2272.48 | 0.063 | 0.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T NW APARTMENT | 1904.87 | 2285.84 | 0.063 | 0.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T SE APARTMENT | 1899.45 | 2279.34 | 0.063 | 0.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T NE APARTMENT | 1910.59 | 2292.70 | 0.063 | 0.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T N1 APARTMENT | 1343.04 | 1611.65 | 0.045 | 0.053 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T N2 APARTMENT | 1343.21 | 1611.85 | 0.045 | 0.053 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T S1 APARTMENT | 1330.23 | 1596.28 | 0.044 | 0.053 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
T S2 APARTMENT | 1330.40 | 1596.48 | 0.044 | 0.053 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.20 | 0.20 | 0.04 | 0.04 |
SPLIT GNW | 0.19 | 0.19 | 0.04 | 0.04 |
SPLIT OFFICE | 0.53 | 0.53 | 0.08 | 0.08 |
SPLIT GNE | 0.16 | 0.16 | 0.04 | 0.04 |
SPLIT GN1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GN2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT MSW | 0.50 | 0.50 | 0.08 | 0.08 |
SPLIT MNW | 0.49 | 0.49 | 0.08 | 0.08 |
SPLIT MSE | 0.43 | 0.43 | 0.08 | 0.08 |
SPLIT MNE | 0.41 | 0.41 | 0.08 | 0.08 |
SPLIT MN1 | 0.32 | 0.32 | 0.05 | 0.05 |
SPLIT MN2 | 0.32 | 0.32 | 0.05 | 0.05 |
SPLIT MS1 | 0.31 | 0.31 | 0.05 | 0.05 |
SPLIT MS2 | 0.31 | 0.31 | 0.05 | 0.05 |
SPLIT TSW | 0.35 | 0.35 | 0.08 | 0.08 |
SPLIT TNW | 0.35 | 0.35 | 0.08 | 0.08 |
SPLIT TSE | 0.32 | 0.32 | 0.08 | 0.08 |
SPLIT TNE | 0.30 | 0.30 | 0.08 | 0.08 |
SPLIT TN1 | 0.24 | 0.24 | 0.05 | 0.05 |
SPLIT TN2 | 0.24 | 0.24 | 0.05 | 0.05 |
SPLIT TS1 | 0.26 | 0.26 | 0.05 | 0.05 |
SPLIT TS2 | 0.26 | 0.26 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2723.00 | 5348.75 | 325.25 |
G NW APARTMENT | 2811.25 | 5618.75 | 548.75 |
OFFICE | 703.00 | 1237.00 | 0.25 |
G NE APARTMENT | 2803.50 | 5645.00 | 566.75 |
G N1 APARTMENT | 2473.25 | 5872.25 | 500.75 |
G N2 APARTMENT | 2475.75 | 5873.00 | 504.75 |
G S1 APARTMENT | 2455.50 | 5635.00 | 326.25 |
G S2 APARTMENT | 2515.00 | 5496.00 | 251.75 |
M SW APARTMENT | 3479.25 | 2699.25 | 107.75 |
M NW APARTMENT | 3215.75 | 3843.00 | 120.50 |
M SE APARTMENT | 3436.75 | 2705.75 | 111.50 |
M NE APARTMENT | 3202.75 | 3865.00 | 135.00 |
M N1 APARTMENT | 2998.25 | 3868.25 | 133.50 |
M N2 APARTMENT | 2996.50 | 3869.75 | 134.00 |
M S1 APARTMENT | 3265.00 | 2227.50 | 112.50 |
M S2 APARTMENT | 3264.25 | 2231.00 | 112.50 |
T SW APARTMENT | 3867.00 | 3580.25 | 355.50 |
T NW APARTMENT | 3840.00 | 4284.00 | 610.25 |
T SE APARTMENT | 3865.25 | 3549.50 | 369.00 |
T NE APARTMENT | 3846.25 | 4304.50 | 616.00 |
T N1 APARTMENT | 3527.25 | 4372.00 | 447.00 |
T N2 APARTMENT | 3528.25 | 4365.25 | 450.50 |
T S1 APARTMENT | 3594.75 | 3476.75 | 225.00 |
T S2 APARTMENT | 3594.25 | 3473.75 | 224.75 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4547.25 | 5914.25 | 878.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 6.00 | 0.00 | 6.00 | 0.00 |
G NW APARTMENT | 0.75 | 0.75 | 0.75 | 0.75 |
OFFICE | 0.00 | 21.25 | 0.00 | 0.00 |
G NE APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G N1 APARTMENT | 10.25 | 0.50 | 10.25 | 0.50 |
G N2 APARTMENT | 10.00 | 0.25 | 10.00 | 0.25 |
G S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
G S2 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M SW APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M NW APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
M SE APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
M NE APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
T NW APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
T N1 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T N2 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T S1 APARTMENT | 0.25 | 0.00 | 0.25 | 0.00 |
T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 34.25 | 24.75 | 34.25 | 3.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.163 | 0.000 | 0.085 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.163 | 0.000 | 0.081 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.518 | 0.176 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.163 | 0.000 | 0.081 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.080 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.080 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.084 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.098 | 0.000 | 0.084 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.235 | 0.000 | 0.105 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.235 | 0.000 | 0.102 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.235 | 0.000 | 0.105 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.235 | 0.000 | 0.102 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.102 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.102 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.105 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.142 | 0.000 | 0.105 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.311 | 0.000 | 0.126 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.310 | 0.000 | 0.122 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.311 | 0.000 | 0.126 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.310 | 0.000 | 0.123 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.187 | 0.000 | 0.122 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.187 | 0.000 | 0.122 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.187 | 0.000 | 0.126 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.187 | 0.000 | 0.126 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.505 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.378 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.373 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.373 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.374 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.374 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.343 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 347.53 | 0.00 | 01-JAN-00:15 | 30806.68 | 01-MAR-07:30 |
WaterSystems:Electricity | 347.53 | 0.00 | 01-JAN-00:15 | 30806.68 | 01-MAR-07:30 |
Water Heater:WaterSystems:Electricity | 347.53 | 0.00 | 01-JAN-00:15 | 30806.68 | 01-MAR-07:30 |
Fans:Electricity | 255.54 | 8103.11 | 01-JAN-07:15 | 8103.11 | 01-JAN-18:30 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
ElectricityPurchased:Plant | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
Cogeneration:ElectricityPurchased | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
ElectricityNet:Plant | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
Cogeneration:ElectricityNet | 1472.34 | 21215.72 | 01-JAN-03:15 | 83900.92 | 26-JUL-17:45 |
ExteriorLights:Electricity | 40.15 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.15 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 448.54 | 8103.11 | 01-JAN-07:15 | 32991.26 | 15-JUN-15:30 |
General:Fans:Electricity | 255.54 | 8103.11 | 01-JAN-07:15 | 8103.11 | 01-JAN-18:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 193.00 | 0.00 | 01-JAN-00:15 | 24888.16 | 15-JUN-15:30 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 49.22 | 0.00 | 01-JAN-11:00 | 38020.19 | 28-JAN-06:00 |
Gas:HVAC | 49.22 | 0.00 | 01-JAN-11:00 | 38020.19 | 28-JAN-06:00 |
Heating:Gas | 49.22 | 0.00 | 01-JAN-11:00 | 38020.19 | 28-JAN-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1410.22 | 1461.72 | 04-MAY-06:00 | 155655.67 | 15-JUN-17:00 |
EnergyTransfer:Building | 622.44 | 1461.72 | 04-MAY-06:00 | 68126.79 | 15-JUN-17:00 |
EnergyTransfer:Zone:G SW APARTMENT | 12.71 | 0.01 | 26-APR-21:45 | 2069.71 | 15-JUN-17:00 |
Heating:EnergyTransfer | 31.86 | 0.00 | 04-JAN-21:00 | 20788.76 | 26-JAN-00:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.89 | 0.00 | 01-JAN-00:15 | 917.01 | 09-FEB-01:00 |
Cooling:EnergyTransfer | 590.58 | 0.00 | 03-MAR-19:15 | 68126.79 | 15-JUN-17:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 11.82 | 0.00 | 01-JAN-03:45 | 2069.71 | 15-JUN-17:00 |
EnergyTransfer:Zone:G NW APARTMENT | 11.55 | 0.01 | 25-MAY-04:15 | 2159.96 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 2.07 | 0.00 | 01-JAN-09:00 | 1084.49 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 9.47 | 0.00 | 01-JAN-00:15 | 2159.96 | 15-JUN-17:15 |
EnergyTransfer:Zone:OFFICE | 30.39 | 0.01 | 18-APR-02:15 | 4528.15 | 27-AUG-10:30 |
Heating:EnergyTransfer:Zone:OFFICE | 5.71 | 0.00 | 01-JAN-00:30 | 909.01 | 05-JUN-17:45 |
Cooling:EnergyTransfer:Zone:OFFICE | 24.69 | 0.00 | 01-JAN-00:15 | 4528.15 | 27-AUG-10:30 |
EnergyTransfer:Zone:G NE APARTMENT | 11.46 | 0.01 | 14-APR-20:30 | 1647.77 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.83 | 0.00 | 01-JAN-09:00 | 1087.57 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 9.63 | 0.00 | 01-JAN-00:15 | 1647.77 | 15-JUN-17:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 8.24 | 0.01 | 09-APR-09:00 | 1260.71 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.79 | 0.00 | 01-JAN-07:15 | 566.33 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 7.45 | 0.00 | 01-JAN-00:15 | 1260.71 | 15-JUN-17:30 |
EnergyTransfer:Zone:G N2 APARTMENT | 8.24 | 0.01 | 03-APR-04:30 | 1251.69 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.79 | 0.00 | 01-JAN-07:15 | 566.03 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 7.45 | 0.00 | 01-JAN-00:15 | 1251.69 | 15-JUN-17:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 10.26 | 0.01 | 14-NOV-17:45 | 1399.27 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.19 | 0.00 | 01-JAN-00:15 | 413.92 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 10.07 | 0.00 | 03-JAN-13:30 | 1399.27 | 19-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 10.90 | 0.02 | 16-JAN-06:45 | 1417.33 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.18 | 0.00 | 01-JAN-00:15 | 409.40 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 10.72 | 0.00 | 03-JAN-13:30 | 1417.33 | 19-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 49.64 | 0.20 | 11-DEC-10:30 | 5428.33 | 15-JUN-17:00 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 811.46 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 49.58 | 0.00 | 03-JAN-19:00 | 5428.33 | 15-JUN-17:00 |
EnergyTransfer:Zone:M NW APARTMENT | 38.30 | 0.06 | 25-MAR-23:15 | 5623.05 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.75 | 0.00 | 01-JAN-00:15 | 1717.02 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 37.56 | 0.00 | 01-JAN-12:00 | 5623.05 | 15-JUN-17:15 |
EnergyTransfer:Zone:M SE APARTMENT | 50.11 | 0.54 | 24-MAR-15:30 | 4536.84 | 19-SEP-13:00 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.05 | 0.00 | 01-JAN-00:15 | 829.19 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 50.05 | 0.00 | 03-JAN-19:00 | 4536.84 | 19-SEP-13:00 |
EnergyTransfer:Zone:M NE APARTMENT | 38.96 | 0.11 | 17-NOV-13:45 | 4525.67 | 15-JUN-17:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.70 | 0.00 | 01-JAN-00:15 | 1722.56 | 26-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 38.27 | 0.00 | 01-JAN-13:00 | 4525.67 | 15-JUN-17:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 33.18 | 0.00 | 13-JAN-13:45 | 3436.48 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 503.16 | 30-DEC-06:45 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 33.12 | 0.00 | 02-JAN-12:30 | 3436.48 | 15-JUN-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 33.18 | 0.04 | 18-FEB-13:00 | 3421.18 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 445.84 | 28-JAN-06:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 33.12 | 0.00 | 02-JAN-12:30 | 3421.18 | 15-JUN-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 46.01 | 1.14 | 14-FEB-17:00 | 3721.33 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 54.74 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 46.01 | 0.00 | 14-FEB-17:00 | 3721.33 | 18-OCT-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 46.01 | 2.89 | 10-NOV-07:15 | 3726.27 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 55.74 | 10-NOV-06:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 46.01 | 0.00 | 14-FEB-17:00 | 3726.27 | 18-OCT-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 27.09 | 0.01 | 09-OCT-02:15 | 3758.07 | 15-JUN-16:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 2.47 | 0.00 | 01-JAN-08:30 | 1918.51 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 24.61 | 0.00 | 01-JAN-00:15 | 3758.07 | 15-JUN-16:30 |
EnergyTransfer:Zone:T NW APARTMENT | 24.13 | 0.01 | 04-JAN-21:00 | 3839.29 | 15-JUN-17:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 4.14 | 0.00 | 01-JAN-21:45 | 2114.51 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 19.99 | 0.00 | 01-JAN-00:15 | 3839.29 | 15-JUN-17:00 |
EnergyTransfer:Zone:T SE APARTMENT | 26.84 | 0.03 | 23-OCT-19:45 | 3158.41 | 21-JUN-13:00 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 2.29 | 0.00 | 01-JAN-00:45 | 1942.37 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 24.55 | 0.00 | 01-JAN-00:15 | 3158.41 | 21-JUN-13:00 |
EnergyTransfer:Zone:T NE APARTMENT | 23.70 | 0.01 | 16-NOV-21:30 | 3129.56 | 15-JUN-16:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 3.79 | 0.00 | 01-JAN-09:00 | 2122.11 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 19.91 | 0.00 | 01-JAN-00:15 | 3129.56 | 15-JUN-16:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 18.34 | 0.00 | 01-NOV-12:45 | 2546.55 | 15-JUN-17:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 1.78 | 0.00 | 01-JAN-00:15 | 1175.95 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 16.56 | 0.00 | 01-JAN-01:00 | 2546.55 | 15-JUN-17:00 |
EnergyTransfer:Zone:T N2 APARTMENT | 18.36 | 0.02 | 03-JAN-22:00 | 2530.28 | 15-JUN-17:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 1.79 | 0.00 | 01-JAN-00:15 | 1175.69 | 09-FEB-01:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 16.57 | 0.00 | 01-JAN-01:00 | 2530.28 | 15-JUN-17:00 |
EnergyTransfer:Zone:T S1 APARTMENT | 22.40 | 0.03 | 07-MAR-06:45 | 2704.19 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 1020.70 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 21.67 | 0.00 | 02-JAN-05:30 | 2704.19 | 19-SEP-13:30 |
EnergyTransfer:Zone:T S2 APARTMENT | 22.43 | 0.02 | 16-JAN-16:00 | 2709.40 | 19-SEP-13:30 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.74 | 0.00 | 01-JAN-00:15 | 1021.02 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 21.69 | 0.00 | 02-JAN-05:30 | 2709.40 | 19-SEP-13:30 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 787.78 | 0.00 | 14-FEB-17:45 | 87686.84 | 05-JUN-17:00 |
HeatingCoils:EnergyTransfer | 39.38 | 0.00 | 01-JAN-11:00 | 30416.15 | 28-JAN-06:00 |
CoolingCoils:EnergyTransfer | 748.40 | 0.00 | 01-JAN-00:15 | 87686.84 | 05-JUN-17:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.892 | -11.819 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 15.377 | 0.000 | 0.622 | 0.001 | 0.000 | -4.857 | 0.000 | -3.268 | -13.968 |
G NW APARTMENT | 2.071 | -9.475 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 8.788 | 0.000 | 0.621 | 0.000 | 0.000 | -4.931 | 0.000 | -3.054 | -11.080 |
OFFICE | 5.707 | -24.687 | 0.000 | 0.000 | 0.518 | 26.452 | 9.482 | 14.951 | 0.000 | 0.357 | 0.000 | 0.000 | -5.282 | 0.000 | -2.896 | -24.602 |
G NE APARTMENT | 1.832 | -9.625 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 8.669 | 0.000 | 0.621 | 0.000 | 0.000 | -4.691 | 0.000 | -3.031 | -10.846 |
G N1 APARTMENT | 0.789 | -7.451 | 0.000 | 0.000 | 3.773 | 1.087 | 12.213 | 3.183 | 0.000 | 0.392 | 0.000 | 0.000 | -3.007 | 0.000 | -2.037 | -8.942 |
G N2 APARTMENT | 0.789 | -7.454 | 0.000 | 0.000 | 3.774 | 1.087 | 12.213 | 3.182 | 0.000 | 0.392 | 0.000 | 0.000 | -3.005 | 0.000 | -2.036 | -8.940 |
G S1 APARTMENT | 0.186 | -10.070 | 0.000 | 0.000 | 3.724 | 1.087 | 12.213 | 9.846 | 0.000 | 0.391 | 0.000 | 0.000 | -2.930 | 0.000 | -2.255 | -12.193 |
G S2 APARTMENT | 0.179 | -10.722 | 0.000 | 0.000 | 3.721 | 1.087 | 12.213 | 9.833 | 0.000 | 0.391 | 0.000 | 0.000 | -2.941 | 0.000 | -2.265 | -11.496 |
M SW APARTMENT | 0.058 | -49.584 | 0.000 | 0.000 | 3.580 | 1.087 | 12.213 | 14.762 | 0.000 | 0.885 | 27.454 | 0.000 | -5.546 | 0.000 | -4.908 | 0.000 |
M NW APARTMENT | 0.748 | -37.556 | 0.000 | 0.000 | 3.644 | 1.087 | 12.213 | 8.308 | 0.000 | 0.883 | 20.966 | 0.000 | -5.592 | 0.000 | -4.700 | 0.000 |
M SE APARTMENT | 0.052 | -50.054 | 0.000 | 0.000 | 3.586 | 1.087 | 12.213 | 14.747 | 0.000 | 0.885 | 27.802 | 0.000 | -5.416 | 0.000 | -4.902 | 0.000 |
M NE APARTMENT | 0.699 | -38.266 | 0.000 | 0.000 | 3.656 | 1.087 | 12.213 | 8.167 | 0.000 | 0.883 | 21.547 | 0.000 | -5.314 | 0.000 | -4.671 | 0.000 |
M N1 APARTMENT | 0.059 | -33.124 | 0.000 | 0.000 | 3.626 | 1.087 | 12.213 | 2.903 | 0.000 | 0.552 | 19.427 | 0.000 | -3.507 | 0.000 | -3.235 | 0.000 |
M N2 APARTMENT | 0.059 | -33.122 | 0.000 | 0.000 | 3.627 | 1.087 | 12.213 | 2.902 | 0.000 | 0.552 | 19.420 | 0.000 | -3.504 | 0.000 | -3.234 | 0.000 |
M S1 APARTMENT | 0.000 | -46.008 | 0.000 | 0.000 | 3.555 | 1.087 | 12.213 | 9.445 | 0.000 | 0.554 | 25.923 | 0.000 | -3.379 | 0.000 | -3.390 | 0.000 |
M S2 APARTMENT | 0.000 | -46.011 | 0.000 | 0.000 | 3.555 | 1.087 | 12.213 | 9.445 | 0.000 | 0.554 | 25.925 | 0.000 | -3.379 | 0.000 | -3.390 | 0.000 |
T SW APARTMENT | 2.472 | -24.613 | 0.000 | 0.000 | 3.662 | 1.087 | 12.213 | 14.524 | 0.000 | 1.167 | 0.716 | 0.000 | -5.158 | 0.000 | -6.070 | -0.000 |
T NW APARTMENT | 4.140 | -19.990 | 0.000 | 0.000 | 3.699 | 1.087 | 12.213 | 8.112 | 0.000 | 1.164 | 0.667 | 0.000 | -5.233 | 0.000 | -5.858 | -0.000 |
T SE APARTMENT | 2.290 | -24.552 | 0.000 | 0.000 | 3.668 | 1.087 | 12.213 | 14.515 | 0.000 | 1.167 | 0.732 | 0.000 | -5.043 | 0.000 | -6.075 | -0.001 |
T NE APARTMENT | 3.792 | -19.908 | 0.000 | 0.000 | 3.709 | 1.087 | 12.213 | 8.011 | 0.000 | 1.164 | 0.787 | 0.000 | -5.007 | 0.000 | -5.847 | -0.000 |
T N1 APARTMENT | 1.778 | -16.560 | 0.000 | 0.000 | 3.696 | 1.087 | 12.213 | 2.840 | 0.000 | 0.730 | 1.402 | 0.000 | -3.240 | 0.000 | -3.945 | -0.000 |
T N2 APARTMENT | 1.789 | -16.570 | 0.000 | 0.000 | 3.697 | 1.087 | 12.213 | 2.837 | 0.000 | 0.730 | 1.401 | 0.000 | -3.238 | 0.000 | -3.946 | -0.000 |
T S1 APARTMENT | 0.738 | -21.665 | 0.000 | 0.000 | 3.647 | 1.087 | 12.213 | 9.317 | 0.000 | 0.733 | 1.217 | 0.000 | -3.149 | 0.000 | -4.136 | -0.000 |
T S2 APARTMENT | 0.742 | -21.687 | 0.000 | 0.000 | 3.647 | 1.087 | 12.213 | 9.315 | 0.000 | 0.733 | 1.235 | 0.000 | -3.148 | 0.000 | -4.137 | -0.000 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.205 | 0.000 | 0.087 | 0.000 | 0.000 | -0.557 | 0.000 | -0.973 | -13.344 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.727 | 0.000 | 2.390 | 0.001 | 0.000 | -1.389 | 0.000 | -14.995 | -7.794 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.213 | 0.000 | 0.078 | 0.000 | 0.000 | -0.627 | 0.000 | -0.820 | -13.425 |
Total Facility | 31.861 | -590.571 | 0.000 | 0.000 | 85.019 | 95.189 | 296.854 | 215.124 | 0.000 | 19.676 | 196.623 | 0.000 | -103.070 | 0.000 | -110.074 | -136.632 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 15-JUN-17:00 | 0.00 | -2069.75 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1664.83 | 0.00 | 335.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -668.87 |
G NW APARTMENT | 15-JUN-17:19 | 0.00 | -2173.09 | 0.00 | 0.00 | 141.62 | 87.56 | 588.62 | 1841.44 | 0.00 | 273.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -759.44 |
OFFICE | 16-JUL-06:01 | 0.00 | -7869.90 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 729.32 | 0.00 | 0.00 | 6463.49 | 0.00 | 0.00 | 0.00 | -33.38 | 0.00 |
G NE APARTMENT | 15-JUN-17:05 | 0.00 | -1648.23 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 815.96 | 0.00 | 304.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -289.72 |
G N1 APARTMENT | 15-JUN-17:19 | 0.00 | -1265.02 | 0.00 | 0.00 | 141.71 | 87.56 | 588.62 | 628.01 | 0.00 | 164.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -345.76 |
G N2 APARTMENT | 15-JUN-17:19 | 0.00 | -1255.46 | 0.00 | 0.00 | 141.71 | 87.56 | 588.62 | 628.17 | 0.00 | 164.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -355.49 |
G S1 APARTMENT | 19-SEP-13:30 | 0.00 | -1399.11 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1513.68 | 0.00 | 58.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -609.89 |
G S2 APARTMENT | 19-SEP-13:30 | 0.00 | -1417.20 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1513.35 | 0.00 | 58.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -591.47 |
M SW APARTMENT | 15-JUN-17:00 | 0.00 | -5428.43 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1642.13 | 0.00 | 481.47 | 2566.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 15-JUN-17:03 | 0.00 | -5625.49 | 0.00 | 0.00 | 141.68 | 87.56 | 588.62 | 1846.19 | 0.00 | 435.87 | 2525.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 19-SEP-13:00 | 0.00 | -4536.43 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1813.19 | 0.00 | 141.68 | 2139.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 15-JUN-17:00 | 0.00 | -4525.75 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 803.27 | 0.00 | 481.47 | 2502.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 15-JUN-17:15 | 0.00 | -3436.85 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 602.87 | 0.00 | 263.02 | 1752.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 15-JUN-17:15 | 0.00 | -3421.55 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 602.96 | 0.00 | 263.01 | 1737.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 18-OCT-13:30 | 0.00 | -3720.97 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1651.77 | 0.00 | 35.07 | 1597.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 18-OCT-13:30 | 0.00 | -3725.91 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1651.74 | 0.00 | 35.07 | 1602.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 15-JUN-16:30 | 0.00 | -3758.25 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1710.41 | 0.00 | 611.33 | 698.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 15-JUN-17:00 | 0.00 | -3839.35 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1824.49 | 0.00 | 634.85 | 641.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 21-JUN-13:00 | 0.00 | -3158.48 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 894.75 | 0.00 | 774.69 | 1046.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 15-JUN-16:23 | 0.00 | -3129.67 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 756.15 | 0.00 | 611.33 | 1023.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 15-JUN-17:00 | 0.00 | -2546.60 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 566.47 | 0.00 | 382.94 | 858.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 15-JUN-17:00 | 0.00 | -2530.33 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 566.70 | 0.00 | 382.94 | 842.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 19-SEP-13:30 | 0.00 | -2703.96 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1463.12 | 0.00 | 111.39 | 693.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 19-SEP-13:30 | 0.00 | -2709.17 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1463.03 | 0.00 | 111.39 | 698.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-16:30 | 0.00 | -68405.14 | 0.00 | 0.00 | 1949.38 | 3295.01 | 14242.10 | 20898.80 | 0.00 | 12349.17 | 15670.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 13-APR-06:01 | 1663.01 | 0.00 | 0.00 | 0.00 | 163.16 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -355.60 | 0.00 | -139.00 | -1756.33 |
G NW APARTMENT | 21-FEB-07:01 | 1655.76 | 0.00 | 0.00 | 0.00 | 163.04 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -385.91 | 0.00 | -68.21 | -1789.44 |
OFFICE | 20-DEC-07:01 | 3417.72 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -490.23 | 0.00 | -465.61 | -3172.34 |
G NE APARTMENT | 25-FEB-08:01 | 1468.14 | 0.00 | 0.00 | 0.00 | 74.87 | 19.46 | 388.49 | 596.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -172.35 | -2374.69 |
G N1 APARTMENT | 05-MAR-07:01 | 966.96 | 0.00 | 0.00 | 0.00 | 161.37 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211.41 | 0.00 | -121.48 | -1220.20 |
G N2 APARTMENT | 05-MAR-07:01 | 981.88 | 0.00 | 0.00 | 0.00 | 161.37 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -211.30 | 0.00 | -121.48 | -1235.24 |
G S1 APARTMENT | 24-DEC-07:01 | 1070.01 | 0.00 | 0.00 | 0.00 | 161.39 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -358.43 | 0.00 | -167.14 | -1130.59 |
G S2 APARTMENT | 15-JAN-07:01 | 1246.19 | 0.00 | 0.00 | 0.00 | 163.04 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -225.42 | 0.00 | -114.18 | -1494.39 |
M SW APARTMENT | 26-JAN-00:15 | 811.51 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 275.52 | 0.00 | -501.09 | 0.00 | -1046.98 | 0.00 |
M NW APARTMENT | 29-DEC-07:01 | 3034.24 | 0.00 | 0.00 | 0.00 | 163.41 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -642.76 | 0.00 | -61.79 | -2917.87 |
M SE APARTMENT | 26-JAN-00:15 | 829.24 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 249.00 | 0.00 | -492.30 | 0.00 | -1046.98 | 0.00 |
M NE APARTMENT | 26-JAN-00:15 | 1722.66 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -477.24 | 0.00 | -1046.98 | -659.47 |
M N1 APARTMENT | 30-DEC-06:45 | 1006.30 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -438.99 | 0.00 | -187.38 | -932.86 |
M N2 APARTMENT | 28-JAN-06:00 | 445.83 | 0.00 | 0.00 | 0.00 | 189.67 | 42.16 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -455.55 | 0.00 | -368.29 | -106.92 |
M S1 APARTMENT | 10-NOV-06:10 | 62.77 | 0.00 | 0.00 | 0.00 | 162.99 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 506.07 | 0.00 | -159.99 | 0.00 | -935.09 | 0.00 |
M S2 APARTMENT | 10-NOV-06:10 | 63.79 | 0.00 | 0.00 | 0.00 | 162.99 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 505.02 | 0.00 | -159.98 | 0.00 | -935.08 | 0.00 |
T SW APARTMENT | 09-FEB-01:00 | 1918.42 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 26.98 | 0.00 | -638.91 | 0.00 | -1767.52 | 0.00 |
T NW APARTMENT | 09-FEB-01:00 | 2114.41 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.49 | 0.00 | -1767.52 | -195.43 |
T SE APARTMENT | 09-FEB-01:00 | 1942.27 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -627.29 | 0.00 | -1767.52 | -8.49 |
T NE APARTMENT | 09-FEB-01:00 | 2121.99 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -601.70 | 0.00 | -1767.52 | -213.80 |
T N1 APARTMENT | 09-FEB-01:00 | 1175.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -366.23 | 0.00 | -1066.16 | -204.57 |
T N2 APARTMENT | 09-FEB-01:00 | 1175.66 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 264.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -366.23 | 0.00 | -1066.16 | -204.30 |
T S1 APARTMENT | 17-JAN-07:01 | 1071.70 | 0.00 | 0.00 | 0.00 | 162.27 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.17 | 0.00 | 0.00 | -1389.56 |
T S2 APARTMENT | 17-JAN-07:01 | 1078.81 | 0.00 | 0.00 | 0.00 | 162.28 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.12 | 0.00 | 0.00 | -1396.73 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JAN-00:15 | 19782.50 | 0.00 | 0.00 | 0.00 | 4352.66 | 1952.47 | 6334.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9336.63 | 0.00 | -20838.23 | -2247.49 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Sec1.1A-General InformationData | |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 34.25 |
Number of hours cooling loads not met | 3.50 |
Number of hours not met | 37.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 49.22 | 38020.19 | 0.00 | 0.00 |
Space Cooling | 193.00 | 22630.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 255.54 | 8103.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 347.53 | 21556.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1472.34 | 49.22 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1472.34 |
Natural Gas | 0.00 | 49.22 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1521.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 61.57 |
Fans-Interior | 81.52 |
Service Water Heating | 110.87 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.81 |
Subtotal | 469.70 |
Natural Gas [MJ/m2] | |
Space Heating | 15.70 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 15.70 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.79 |
Space Heating | 3.23 |
Space Cooling | 12.68 |
Fans-Interior | 16.79 |
Service Water Heating | 22.84 |
Receptacle Equipment | 34.02 |
Miscellaneous | 2.64 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.195656 |
G NW APARTMENT DIRECT AIR | 0.194188 |
OFFICE DIRECT AIR | 0.526933 |
G NE APARTMENT DIRECT AIR | 0.155548 |
G N1 APARTMENT DIRECT AIR | 0.121922 |
G N2 APARTMENT DIRECT AIR | 0.121161 |
G S1 APARTMENT DIRECT AIR | 0.119244 |
G S2 APARTMENT DIRECT AIR | 0.120910 |
M SW APARTMENT DIRECT AIR | 0.497005 |
M NW APARTMENT DIRECT AIR | 0.492981 |
M SE APARTMENT DIRECT AIR | 0.434075 |
M NE APARTMENT DIRECT AIR | 0.409232 |
M N1 APARTMENT DIRECT AIR | 0.318011 |
M N2 APARTMENT DIRECT AIR | 0.316788 |
M S1 APARTMENT DIRECT AIR | 0.313442 |
M S2 APARTMENT DIRECT AIR | 0.314189 |
T SW APARTMENT DIRECT AIR | 0.354688 |
T NW APARTMENT DIRECT AIR | 0.345912 |
T SE APARTMENT DIRECT AIR | 0.323607 |
T NE APARTMENT DIRECT AIR | 0.303968 |
T N1 APARTMENT DIRECT AIR | 0.240860 |
T N2 APARTMENT DIRECT AIR | 0.240853 |
T S1 APARTMENT DIRECT AIR | 0.259418 |
T S2 APARTMENT DIRECT AIR | 0.259795 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.195656 |
SPLIT GNW MAIN BRANCH | 0.194188 |
SPLIT OFFICE MAIN BRANCH | 0.526933 |
SPLIT GNE MAIN BRANCH | 0.155548 |
SPLIT GN1 MAIN BRANCH | 0.121922 |
SPLIT GN2 MAIN BRANCH | 0.121161 |
SPLIT GS1 MAIN BRANCH | 0.119244 |
SPLIT GS2 MAIN BRANCH | 0.120910 |
SPLIT MSW MAIN BRANCH | 0.497005 |
SPLIT MNW MAIN BRANCH | 0.492981 |
SPLIT MSE MAIN BRANCH | 0.434075 |
SPLIT MNE MAIN BRANCH | 0.409232 |
SPLIT MN1 MAIN BRANCH | 0.318011 |
SPLIT MN2 MAIN BRANCH | 0.316788 |
SPLIT MS1 MAIN BRANCH | 0.313442 |
SPLIT MS2 MAIN BRANCH | 0.314189 |
SPLIT TSW MAIN BRANCH | 0.354688 |
SPLIT TNW MAIN BRANCH | 0.345912 |
SPLIT TSE MAIN BRANCH | 0.323607 |
SPLIT TNE MAIN BRANCH | 0.303968 |
SPLIT TN1 MAIN BRANCH | 0.240860 |
SPLIT TN2 MAIN BRANCH | 0.240853 |
SPLIT TS1 MAIN BRANCH | 0.259418 |
SPLIT TS2 MAIN BRANCH | 0.259795 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.195656 |
SPLIT GNW | 0.194188 |
SPLIT OFFICE | 0.526933 |
SPLIT GNE | 0.155548 |
SPLIT GN1 | 0.121922 |
SPLIT GN2 | 0.121161 |
SPLIT GS1 | 0.119244 |
SPLIT GS2 | 0.120910 |
SPLIT MSW | 0.497005 |
SPLIT MNW | 0.492981 |
SPLIT MSE | 0.434075 |
SPLIT MNE | 0.409232 |
SPLIT MN1 | 0.318011 |
SPLIT MN2 | 0.316788 |
SPLIT MS1 | 0.313442 |
SPLIT MS2 | 0.314189 |
SPLIT TSW | 0.354688 |
SPLIT TNW | 0.345912 |
SPLIT TSE | 0.323607 |
SPLIT TNE | 0.303968 |
SPLIT TN1 | 0.240860 |
SPLIT TN2 | 0.240853 |
SPLIT TS1 | 0.259418 |
SPLIT TS2 | 0.259795 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.195656 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.194188 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.526933 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.155548 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.121922 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.121161 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.119244 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.120910 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.497005 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.492981 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.434075 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.409232 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.318011 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.316788 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.313442 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.314189 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.354688 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.345912 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.323607 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.303968 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.240860 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.240853 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.259418 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.259795 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.195656 | 3238.79 | 0.798655 |
SPLIT GNW COOLING COIL | 0.194188 | 3214.51 | 0.798655 |
SPLIT OFFICE COOLING COIL | 0.526933 | 8722.60 | 0.798655 |
SPLIT GNE COOLING COIL | 0.155548 | 2574.86 | 0.798655 |
SPLIT GN1 COOLING COIL | 0.121922 | 2018.24 | 0.798655 |
SPLIT GN2 COOLING COIL | 0.121161 | 2005.65 | 0.798655 |
SPLIT GS1 COOLING COIL | 0.119244 | 1973.91 | 0.798655 |
SPLIT GS2 COOLING COIL | 0.120910 | 2099.96 | 0.781416 |
SPLIT MSW COOLING COIL | 0.497005 | 8227.20 | 0.798655 |
SPLIT MNW COOLING COIL | 0.492981 | 8160.59 | 0.798655 |
SPLIT MSE COOLING COIL | 0.434075 | 7185.49 | 0.798655 |
SPLIT MNE COOLING COIL | 0.409232 | 6774.24 | 0.798655 |
SPLIT MN1 COOLING COIL | 0.318011 | 5264.22 | 0.798655 |
SPLIT MN2 COOLING COIL | 0.316788 | 5243.97 | 0.798655 |
SPLIT MS1 COOLING COIL | 0.313442 | 5294.44 | 0.791304 |
SPLIT MS2 COOLING COIL | 0.314189 | 5305.85 | 0.791386 |
SPLIT TSW COOLING COIL | 0.354688 | 5871.35 | 0.798655 |
SPLIT TNW COOLING COIL | 0.345912 | 5726.07 | 0.798655 |
SPLIT TSE COOLING COIL | 0.323607 | 5356.85 | 0.798655 |
SPLIT TNE COOLING COIL | 0.303968 | 5031.75 | 0.798655 |
SPLIT TN1 COOLING COIL | 0.240860 | 3987.09 | 0.798655 |
SPLIT TN2 COOLING COIL | 0.240853 | 3986.98 | 0.798655 |
SPLIT TS1 COOLING COIL | 0.259418 | 4294.29 | 0.798655 |
SPLIT TS2 COOLING COIL | 0.259795 | 4300.53 | 0.798655 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.195656 | 0.195656 | 0.195656 | 0.195656 | 1946.11 | 3238.79 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.194188 | 0.194188 | 0.194188 | 0.194188 | 1928.35 | 3214.51 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.526933 | 0.526933 | 0.526933 | 0.526933 | 3616.86 | 8722.60 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.155548 | 0.155548 | 0.155548 | 0.155548 | 1933.09 | 2574.86 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.121922 | 0.121922 | 0.121922 | 0.121922 | 1503.38 | 2018.24 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.121161 | 0.121161 | 0.121161 | 0.121161 | 1503.38 | 2005.65 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.119244 | 0.119244 | 0.119244 | 0.119244 | 1503.38 | 1973.91 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.120910 | 0.120910 | 0.120910 | 0.120910 | 1504.62 | 2099.96 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.497005 | 0.497005 | 0.497005 | 0.497005 | 3739.52 | 8227.20 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.492981 | 0.492981 | 0.492981 | 0.492981 | 3761.73 | 8160.59 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.434075 | 0.434075 | 0.434075 | 0.434075 | 3752.38 | 7185.49 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.409232 | 0.409232 | 0.409232 | 0.409232 | 3774.58 | 6774.24 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.318011 | 0.318011 | 0.318011 | 0.318011 | 3006.76 | 5264.22 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.316788 | 0.316788 | 0.316788 | 0.316788 | 3006.76 | 5243.97 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.313442 | 0.313442 | 0.313442 | 0.313442 | 3006.76 | 5294.44 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.314189 | 0.314189 | 0.314189 | 0.314189 | 3006.76 | 5305.85 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.354688 | 0.354688 | 0.354688 | 0.354688 | 2971.95 | 5871.35 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.345912 | 0.345912 | 0.345912 | 0.345912 | 2985.12 | 5726.07 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.323607 | 0.323607 | 0.323607 | 0.323607 | 2978.70 | 5356.85 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.303968 | 0.303968 | 0.303968 | 0.303968 | 2991.88 | 5031.75 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.240860 | 0.240860 | 0.240860 | 0.240860 | 2320.77 | 3987.09 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.240853 | 0.240853 | 0.240853 | 0.240853 | 2320.96 | 3986.98 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.259418 | 0.259418 | 0.259418 | 0.259418 | 2305.62 | 4294.29 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.259795 | 0.259795 | 0.259795 | 0.259795 | 2305.82 | 4300.53 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.195656 |
SPLIT GNW SUPPLY FAN | 0.194188 |
SPLIT OFFICE SUPPLY FAN | 0.526933 |
SPLIT GNE SUPPLY FAN | 0.155548 |
SPLIT GN1 SUPPLY FAN | 0.121922 |
SPLIT GN2 SUPPLY FAN | 0.121161 |
SPLIT GS1 SUPPLY FAN | 0.119244 |
SPLIT GS2 SUPPLY FAN | 0.120910 |
SPLIT MSW SUPPLY FAN | 0.497005 |
SPLIT MNW SUPPLY FAN | 0.492981 |
SPLIT MSE SUPPLY FAN | 0.434075 |
SPLIT MNE SUPPLY FAN | 0.409232 |
SPLIT MN1 SUPPLY FAN | 0.318011 |
SPLIT MN2 SUPPLY FAN | 0.316788 |
SPLIT MS1 SUPPLY FAN | 0.313442 |
SPLIT MS2 SUPPLY FAN | 0.314189 |
SPLIT TSW SUPPLY FAN | 0.354688 |
SPLIT TNW SUPPLY FAN | 0.345912 |
SPLIT TSE SUPPLY FAN | 0.323607 |
SPLIT TNE SUPPLY FAN | 0.303968 |
SPLIT TN1 SUPPLY FAN | 0.240860 |
SPLIT TN2 SUPPLY FAN | 0.240853 |
SPLIT TS1 SUPPLY FAN | 0.259418 |
SPLIT TS2 SUPPLY FAN | 0.259795 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1946.11 |
SPLIT GNW HEATING COIL | 1928.35 |
SPLIT OFFICE HEATING COIL | 3616.86 |
SPLIT GNE HEATING COIL | 1933.09 |
SPLIT GN1 HEATING COIL | 1503.38 |
SPLIT GN2 HEATING COIL | 1503.38 |
SPLIT GS1 HEATING COIL | 1503.38 |
SPLIT GS2 HEATING COIL | 1504.62 |
SPLIT MSW HEATING COIL | 3739.52 |
SPLIT MNW HEATING COIL | 3761.73 |
SPLIT MSE HEATING COIL | 3752.38 |
SPLIT MNE HEATING COIL | 3774.58 |
SPLIT MN1 HEATING COIL | 3006.76 |
SPLIT MN2 HEATING COIL | 3006.76 |
SPLIT MS1 HEATING COIL | 3006.76 |
SPLIT MS2 HEATING COIL | 3006.76 |
SPLIT TSW HEATING COIL | 2971.95 |
SPLIT TNW HEATING COIL | 2985.12 |
SPLIT TSE HEATING COIL | 2978.70 |
SPLIT TNE HEATING COIL | 2991.88 |
SPLIT TN1 HEATING COIL | 2320.77 |
SPLIT TN2 HEATING COIL | 2320.96 |
SPLIT TS1 HEATING COIL | 2305.62 |
SPLIT TS2 HEATING COIL | 2305.82 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 8.14 |
February | 22.60 | 10.27 |
March | 22.83 | 12.55 |
April | 23.74 | 19.23 |
May | 24.23 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.98 | 18.30 |
November | 22.96 | 11.18 |
December | 22.37 | 6.79 |
Annual Sum or Average | 23.56 | 17.98 |
Minimum of Months | 22.37 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | 8.14 |
February | 22.07 | 10.27 |
March | 22.43 | 12.55 |
April | 23.62 | 19.23 |
May | 24.23 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.74 | 18.30 |
November | 22.29 | 11.18 |
December | 21.81 | 6.79 |
Annual Sum or Average | 23.31 | 17.98 |
Minimum of Months | 21.81 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 8.14 |
February | 23.34 | 10.27 |
March | 23.74 | 12.55 |
April | 25.16 | 19.23 |
May | 25.96 | 23.84 |
June | 27.14 | 27.86 |
July | 27.31 | 27.54 |
August | 27.01 | 26.28 |
September | 27.02 | 23.38 |
October | 25.29 | 18.30 |
November | 23.90 | 11.18 |
December | 22.86 | 6.79 |
Annual Sum or Average | 25.14 | 17.98 |
Minimum of Months | 22.86 | 6.79 |
Maximum of Months | 27.31 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 8.14 |
February | 22.01 | 10.27 |
March | 22.37 | 12.55 |
April | 23.62 | 19.23 |
May | 24.23 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.67 | 18.30 |
November | 22.18 | 11.18 |
December | 21.75 | 6.79 |
Annual Sum or Average | 23.27 | 17.98 |
Minimum of Months | 21.75 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 8.14 |
February | 21.95 | 10.27 |
March | 22.23 | 12.55 |
April | 23.47 | 19.23 |
May | 24.17 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.64 | 18.30 |
November | 22.15 | 11.18 |
December | 21.76 | 6.79 |
Annual Sum or Average | 23.23 | 17.98 |
Minimum of Months | 21.76 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 8.14 |
February | 21.95 | 10.27 |
March | 22.23 | 12.55 |
April | 23.47 | 19.23 |
May | 24.17 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 23.63 | 18.30 |
November | 22.14 | 11.18 |
December | 21.75 | 6.79 |
Annual Sum or Average | 23.23 | 17.98 |
Minimum of Months | 21.75 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 8.14 |
February | 22.61 | 10.27 |
March | 22.76 | 12.55 |
April | 23.66 | 19.23 |
May | 24.18 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 23.97 | 18.30 |
November | 23.00 | 11.18 |
December | 22.39 | 6.79 |
Annual Sum or Average | 23.55 | 17.98 |
Minimum of Months | 22.39 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 8.14 |
February | 22.63 | 10.27 |
March | 22.79 | 12.55 |
April | 23.70 | 19.23 |
May | 24.21 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.00 | 18.30 |
November | 23.03 | 11.18 |
December | 22.40 | 6.79 |
Annual Sum or Average | 23.57 | 17.98 |
Minimum of Months | 22.40 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.64 | 8.14 |
February | 23.89 | 10.27 |
March | 24.10 | 12.55 |
April | 24.34 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.05 | 11.18 |
December | 23.52 | 6.79 |
Annual Sum or Average | 24.16 | 17.98 |
Minimum of Months | 23.52 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 8.14 |
February | 23.16 | 10.27 |
March | 23.81 | 12.55 |
April | 24.31 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.38 | 18.30 |
November | 23.62 | 11.18 |
December | 22.35 | 6.79 |
Annual Sum or Average | 23.85 | 17.98 |
Minimum of Months | 22.35 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.58 | 8.14 |
February | 23.88 | 10.27 |
March | 24.09 | 12.55 |
April | 24.34 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.39 | 18.30 |
November | 24.00 | 11.18 |
December | 23.47 | 6.79 |
Annual Sum or Average | 24.15 | 17.98 |
Minimum of Months | 23.47 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 8.14 |
February | 23.10 | 10.27 |
March | 23.77 | 12.55 |
April | 24.31 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.37 | 18.30 |
November | 23.54 | 11.18 |
December | 22.23 | 6.79 |
Annual Sum or Average | 23.81 | 17.98 |
Minimum of Months | 22.23 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.74 | 8.14 |
February | 23.34 | 10.27 |
March | 23.94 | 12.55 |
April | 24.34 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.39 | 18.30 |
November | 23.81 | 11.18 |
December | 22.49 | 6.79 |
Annual Sum or Average | 23.92 | 17.98 |
Minimum of Months | 22.49 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 8.14 |
February | 23.34 | 10.27 |
March | 23.94 | 12.55 |
April | 24.34 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.39 | 18.30 |
November | 23.80 | 11.18 |
December | 22.48 | 6.79 |
Annual Sum or Average | 23.92 | 17.98 |
Minimum of Months | 22.48 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 8.14 |
February | 24.12 | 10.27 |
March | 24.24 | 12.55 |
April | 24.37 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.20 | 11.18 |
December | 23.86 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.86 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 8.14 |
February | 24.12 | 10.27 |
March | 24.24 | 12.55 |
April | 24.37 | 19.23 |
May | 24.40 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.40 | 23.38 |
October | 24.40 | 18.30 |
November | 24.20 | 11.18 |
December | 23.85 | 6.79 |
Annual Sum or Average | 24.26 | 17.98 |
Minimum of Months | 23.85 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 8.14 |
February | 23.15 | 10.27 |
March | 23.43 | 12.55 |
April | 24.13 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.23 | 18.30 |
November | 23.33 | 11.18 |
December | 22.83 | 6.79 |
Annual Sum or Average | 23.83 | 17.98 |
Minimum of Months | 22.83 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 8.14 |
February | 22.69 | 10.27 |
March | 23.18 | 12.55 |
April | 24.08 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.14 | 18.30 |
November | 22.91 | 11.18 |
December | 22.17 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.17 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 8.14 |
February | 23.16 | 10.27 |
March | 23.46 | 12.55 |
April | 24.14 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.21 | 18.30 |
November | 23.31 | 11.18 |
December | 22.83 | 6.79 |
Annual Sum or Average | 23.83 | 17.98 |
Minimum of Months | 22.83 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 8.14 |
February | 22.67 | 10.27 |
March | 23.19 | 12.55 |
April | 24.09 | 19.23 |
May | 24.37 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.38 | 23.38 |
October | 24.11 | 18.30 |
November | 22.87 | 11.18 |
December | 22.07 | 6.79 |
Annual Sum or Average | 23.59 | 17.98 |
Minimum of Months | 22.07 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.20 | 8.14 |
February | 22.70 | 10.27 |
March | 23.22 | 12.55 |
April | 24.12 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.19 | 18.30 |
November | 22.94 | 11.18 |
December | 22.08 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.08 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 8.14 |
February | 22.70 | 10.27 |
March | 23.23 | 12.55 |
April | 24.12 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.19 | 18.30 |
November | 22.93 | 11.18 |
December | 22.08 | 6.79 |
Annual Sum or Average | 23.62 | 17.98 |
Minimum of Months | 22.08 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 8.14 |
February | 23.31 | 10.27 |
March | 23.57 | 12.55 |
April | 24.19 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.29 | 18.30 |
November | 23.47 | 11.18 |
December | 22.95 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 22.95 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 8.14 |
February | 23.31 | 10.27 |
March | 23.57 | 12.55 |
April | 24.19 | 19.23 |
May | 24.38 | 23.84 |
June | 24.40 | 27.86 |
July | 24.40 | 27.54 |
August | 24.40 | 26.28 |
September | 24.39 | 23.38 |
October | 24.29 | 18.30 |
November | 23.46 | 11.18 |
December | 22.95 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 22.95 | 6.79 |
Maximum of Months | 24.40 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 8.14 |
February | 23.55 | 10.27 |
March | 24.26 | 12.55 |
April | 25.78 | 19.23 |
May | 26.56 | 23.84 |
June | 27.12 | 27.86 |
July | 27.16 | 27.54 |
August | 26.98 | 26.28 |
September | 26.64 | 23.38 |
October | 25.80 | 18.30 |
November | 23.89 | 11.18 |
December | 22.66 | 6.79 |
Annual Sum or Average | 25.28 | 17.98 |
Minimum of Months | 22.66 | 6.79 |
Maximum of Months | 27.16 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.87 | 8.14 |
February | 21.48 | 10.27 |
March | 22.15 | 12.55 |
April | 23.95 | 19.23 |
May | 25.24 | 23.84 |
June | 26.98 | 27.86 |
July | 27.08 | 27.54 |
August | 26.84 | 26.28 |
September | 26.37 | 23.38 |
October | 24.17 | 18.30 |
November | 21.97 | 11.18 |
December | 20.69 | 6.79 |
Annual Sum or Average | 23.99 | 17.98 |
Minimum of Months | 20.69 | 6.79 |
Maximum of Months | 27.08 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:31
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.81 | 8.14 |
February | 25.30 | 10.27 |
March | 25.81 | 12.55 |
April | 26.46 | 19.23 |
May | 26.75 | 23.84 |
June | 26.97 | 27.86 |
July | 26.94 | 27.54 |
August | 26.88 | 26.28 |
September | 26.80 | 23.38 |
October | 26.52 | 18.30 |
November | 25.72 | 11.18 |
December | 24.62 | 6.79 |
Annual Sum or Average | 26.14 | 17.98 |
Minimum of Months | 24.62 | 6.79 |
Maximum of Months | 26.97 | 27.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:31
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.115269E+12 | 70245.240 | 13-JAN-18:30 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 1723.749 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26254.512 | 0.000 | 0.000 | 0.000 |
February | 0.104987E+12 | 71409.749 | 19-FEB-18:15 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 4891.179 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24251.591 | 0.000 | 0.000 | 0.000 |
March | 0.116295E+12 | 71853.771 | 21-MAR-17:30 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 8272.898 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23866.894 | 0.000 | 0.000 | 0.000 |
April | 0.119643E+12 | 75686.510 | 30-APR-17:30 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 14853.274 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21119.257 | 0.000 | 0.000 | 0.000 |
May | 0.129929E+12 | 76096.268 | 19-MAY-17:15 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 19871.962 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16510.327 | 0.000 | 0.000 | 0.000 |
June | 0.134238E+12 | 81748.525 | 15-JUN-16:00 | 4276.255 | 26730.986 | 8103.106 | 0.000 | 24571.469 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18066.708 | 0.000 | 0.000 | 0.000 |
July | 0.140488E+12 | 83900.917 | 26-JUL-17:45 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 22630.760 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21556.178 | 0.000 | 0.000 | 0.000 |
August | 0.136185E+12 | 82861.937 | 07-AUG-17:30 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 21021.139 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22126.818 | 0.000 | 0.000 | 0.000 |
September | 0.128055E+12 | 76950.937 | 20-SEP-16:15 | 4276.255 | 26730.986 | 8103.106 | 0.000 | 18773.099 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19067.490 | 0.000 | 0.000 | 0.000 |
October | 0.122119E+12 | 75558.365 | 05-OCT-17:45 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 14057.457 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19233.928 | 0.000 | 0.000 | 0.000 |
November | 0.111198E+12 | 69095.113 | 11-NOV-18:15 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 3963.011 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22865.122 | 0.000 | 0.000 | 0.000 |
December | 0.113931E+12 | 69262.187 | 31-DEC-18:45 | 4979.953 | 26630.920 | 8103.106 | 0.000 | 241.812 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26753.396 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.147234E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.104987E+12 | 69095.113 | 4276.255 | 26630.920 | 8103.106 | 0.000 | 241.812 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16510.327 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.140488E+12 | 83900.917 | 4979.953 | 26730.986 | 8103.106 | 0.000 | 24571.469 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26753.396 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:31
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.135777E+11 | 38020.190 | 28-JAN-05:00 | 38020.190 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38020.190 |
February | 0.859951E+10 | 33059.710 | 09-FEB-01:15 | 33059.710 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 33059.710 |
March | 0.403183E+10 | 26569.010 | 02-MAR-05:00 | 26569.010 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26569.010 |
April | 0.404539E+09 | 13896.510 | 11-APR-01:00 | 13896.510 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13896.510 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 5255214.127 | 1040.382 | 25-OCT-05:00 | 1040.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1040.382 |
November | 0.523019E+10 | 33316.154 | 28-NOV-04:00 | 33316.154 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 33316.154 |
December | 0.173720E+11 | 37891.297 | 27-DEC-07:30 | 37891.297 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 37891.297 |
Annual Sum or Average | 0.492210E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.173720E+11 | 38020.190 | 38020.190 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38020.190 |