Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Boise Air Terminal Uo ID USA TMY3 WMO#=726810

Simulation Timestamp: 2015-09-09 18:47:26


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1725.14 550.35 610.89
Net Site Energy 1725.14 550.35 610.89
Total Source Energy 4893.08 1560.98 1732.69
Net Source Energy 4893.08 1560.98 1732.69


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 273.85 0.00 0.00 0.00 0.00
Cooling 105.80 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.06 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 261.72 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 407.59 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1451.29 273.85 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 273.85 0.00 0.00 0.00 0.00
Cooling General 105.80 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.06 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 261.72 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 407.59 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.13 0.00 0.00 0.00 0.00 0.00
HVAC 274.48 96.97 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 513.92 96.97 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.57 0.00 0.00 0.00 0.00 0.00
HVAC 247.28 87.36 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 462.99 87.36 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1451.29 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1451.29 100.00
     
Total On-Site and Utility Electric Sources 1451.29 100.00
Total Electricity End Uses 1451.29 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 46.25
Time Setpoint Not Met During Occupied Cooling 0.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 1791.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Latitude [deg] 43.62
Longitude [deg] -116.2
Elevation [m] 701.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 29-JUL-17:00 04-JAN-07:00 - - - 01-JAN-07:15
Heating 0.00 80039.05 0.00 0.00 0.00 0.00
Cooling 23997.97 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8299.19 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23607.21 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 87515.24 80039.05 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 80039.05 0.00 0.00 0.00 0.00
Cooling General 23997.97 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 8299.19 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 23607.21 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 296.85 0.00 0.00 0.00
Cooling 335.08 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.86 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 828.88 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1290.84 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4596.23 296.85 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 105.12 0.00 0.00 0.00
Cooling 118.65 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.92 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 293.51 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 457.10 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1627.57 105.12 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 105.12 0.00 0.00 0.00
Cooling 118.65 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.92 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 293.51 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 457.10 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1627.57 105.12 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 2.30 120.00
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 36.70 16.70 17.90 Wetbulb [C] 4.20 330.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.58 83.58 40.06
Exterior Lighting Total 2553.00           40.06



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   3394.82 2711.29 683.53 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3126.95 2497.36 629.60 0.80 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8192.01 6542.59 1649.42 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2300.66 1837.43 463.23 0.80 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1715.86 1370.38 345.48 0.80 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   1695.05 1353.76 341.29 0.80 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2212.37 1744.57 467.79 0.79 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2259.55 1783.34 476.21 0.79 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   9138.95 7298.87 1840.08 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8348.72 6667.75 1680.97 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   8281.29 6613.90 1667.40 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   6667.30 5324.87 1342.42 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4846.87 3870.98 975.89 0.80 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4812.79 3843.76 969.03 0.80 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   6080.81 4856.47 1224.34 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   6103.03 4874.22 1228.81 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   6273.59 5010.44 1263.16 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5693.30 4546.98 1146.32 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   5870.78 4688.73 1182.05 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4706.02 3758.49 947.53 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3632.62 2901.21 731.41 0.80 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3633.57 2901.97 731.60 0.80 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   4732.26 3779.45 952.82 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   4745.75 3790.22 955.53 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 3234.1 3.13 10.67 11.09 10.38
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 2978.9 3.13 10.67 11.09 10.38
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7804.2 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2191.7 3.13 10.67 11.09 10.38
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1634.6 3.13 10.67 11.09 10.38
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1614.8 3.13 10.67 11.09 10.38
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2110.5 3.14 10.73 11.15 10.46
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2155.3 3.14 10.73 11.15 10.46
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 8706.3 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7953.5 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7889.2 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 6351.6 3.13 10.67 11.09 10.38
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4617.4 3.13 10.67 11.09 10.38
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4584.9 3.13 10.67 11.09 10.38
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5792.9 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5814.1 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5976.6 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5423.8 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 5592.8 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4483.2 3.13 10.67 11.09 10.38
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3460.6 3.13 10.67 11.09 10.38
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3461.5 3.13 10.67 11.09 10.38
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 4508.2 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 4521.1 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   3090.00 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   3042.14 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   5450.83 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   3049.53 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   2320.92 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   2321.09 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   2331.74 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   2452.70 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   5913.15 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   5887.20 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   5932.81 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   5906.88 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   4095.72 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   4096.22 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   4124.14 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   4124.64 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   4458.36 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   4446.32 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   4468.76 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   4456.75 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   3492.72 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   3493.00 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   3503.36 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   3503.64 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 238.07 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.19 219.28 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.49 574.48 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.14 161.34 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 120.33 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.10 118.87 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 150.88 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.13 154.40 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.55 640.88 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.50 585.47 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.50 580.74 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.40 467.55 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 339.89 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 337.50 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.37 426.42 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.37 427.98 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.38 439.94 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 399.25 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.35 411.70 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.28 330.02 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 254.74 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.22 254.81 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 331.86 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 332.80 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2007.31 2408.77 0.171 0.205 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
G NW APARTMENT 1848.92 2218.71 0.157 0.189 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.44 0.00627
OFFICE 4741.51 5689.81 0.412 0.495 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 27.52 0.00627
G NE APARTMENT 1360.37 1632.44 0.116 0.139 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
G N1 APARTMENT 1014.55 1217.46 0.086 0.104 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.19 0.00627
G N2 APARTMENT 1002.25 1202.70 0.085 0.102 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.19 0.00627
G S1 APARTMENT 1272.20 1526.65 0.108 0.130 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.70 0.00627
G S2 APARTMENT 1301.85 1562.22 0.111 0.133 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.70 0.00627
M SW APARTMENT 5403.77 6484.52 0.460 0.552 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
M NW APARTMENT 4936.52 5923.82 0.420 0.504 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
M SE APARTMENT 4896.73 5876.08 0.417 0.500 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 36.70 0.00627
M NE APARTMENT 3942.38 4730.85 0.336 0.403 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
M N1 APARTMENT 2865.87 3439.05 0.244 0.293 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.19 0.00627
M N2 APARTMENT 2845.72 3414.86 0.242 0.291 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.19 0.00627
M S1 APARTMENT 3595.53 4314.63 0.306 0.367 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.70 0.00627
M S2 APARTMENT 3608.67 4330.40 0.307 0.369 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.70 0.00627
T SW APARTMENT 3709.63 4451.56 0.316 0.379 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 35.03 0.00627
T NW APARTMENT 3366.43 4039.71 0.287 0.344 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.11 0.00627
T SE APARTMENT 3471.45 4165.74 0.296 0.355 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 36.70 0.00627
T NE APARTMENT 2782.71 3339.26 0.237 0.284 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 36.70 0.00627
T N1 APARTMENT 2147.95 2577.54 0.183 0.219 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 35.95 0.00627
T N2 APARTMENT 2148.52 2578.22 0.183 0.220 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 36.20 0.00627
T S1 APARTMENT 2798.17 3357.80 0.238 0.286 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 36.70 0.00627
T S2 APARTMENT 2806.15 3367.37 0.239 0.287 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 36.70 0.00627


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1651.11 1981.33 0.052 0.062 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G NW APARTMENT 1644.44 1973.33 0.051 0.062 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
OFFICE 3296.07 3955.29 0.100 0.120 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G NE APARTMENT 1650.70 1980.84 0.052 0.062 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G N1 APARTMENT 1034.54 1241.44 0.032 0.039 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G N2 APARTMENT 1034.69 1241.62 0.032 0.039 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G S1 APARTMENT 1043.69 1252.43 0.033 0.039 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
G S2 APARTMENT 1145.97 1375.17 0.036 0.043 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
M SW APARTMENT 3144.28 3773.13 0.098 0.118 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M NW APARTMENT 3122.33 3746.80 0.098 0.117 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M SE APARTMENT 3160.90 3793.08 0.099 0.119 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M NE APARTMENT 3138.97 3766.76 0.098 0.118 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M N1 APARTMENT 1607.31 1928.77 0.050 0.060 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M N2 APARTMENT 1607.73 1929.28 0.050 0.060 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M S1 APARTMENT 1631.34 1957.61 0.051 0.061 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
M S2 APARTMENT 1631.76 1958.11 0.051 0.061 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T SW APARTMENT 2842.15 3410.57 0.089 0.107 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T NW APARTMENT 2831.97 3398.36 0.089 0.106 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T SE APARTMENT 2850.95 3421.14 0.089 0.107 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T NE APARTMENT 2840.79 3408.94 0.089 0.107 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T N1 APARTMENT 2025.51 2430.62 0.063 0.076 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T N2 APARTMENT 2025.75 2430.90 0.063 0.076 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T S1 APARTMENT 2034.52 2441.42 0.064 0.076 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098
T S2 APARTMENT 2034.75 2441.70 0.064 0.076 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -16.30 0.00098


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.21 0.21 0.06 0.06
SPLIT GNW 0.19 0.19 0.06 0.06
SPLIT OFFICE 0.49 0.49 0.12 0.12
SPLIT GNE 0.14 0.14 0.06 0.06
SPLIT GN1 0.10 0.10 0.04 0.04
SPLIT GN2 0.10 0.10 0.04 0.04
SPLIT GS1 0.13 0.13 0.04 0.04
SPLIT GS2 0.13 0.13 0.04 0.04
SPLIT MSW 0.55 0.55 0.12 0.12
SPLIT MNW 0.50 0.50 0.12 0.12
SPLIT MSE 0.50 0.50 0.12 0.12
SPLIT MNE 0.40 0.40 0.12 0.12
SPLIT MN1 0.29 0.29 0.06 0.06
SPLIT MN2 0.29 0.29 0.06 0.06
SPLIT MS1 0.37 0.37 0.06 0.06
SPLIT MS2 0.37 0.37 0.06 0.06
SPLIT TSW 0.38 0.38 0.11 0.11
SPLIT TNW 0.34 0.34 0.11 0.11
SPLIT TSE 0.35 0.35 0.11 0.11
SPLIT TNE 0.28 0.28 0.11 0.11
SPLIT TN1 0.22 0.22 0.08 0.08
SPLIT TN2 0.22 0.22 0.08 0.08
SPLIT TS1 0.29 0.29 0.08 0.08
SPLIT TS2 0.29 0.29 0.08 0.08



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 1303.25 6247.50 515.75
G NW APARTMENT 1494.25 6619.75 999.50
OFFICE 304.75 1543.25 52.00
G NE APARTMENT 1471.50 6588.25 974.50
G N1 APARTMENT 616.00 6873.50 419.00
G N2 APARTMENT 615.50 6874.25 418.00
G S1 APARTMENT 576.50 6364.00 148.25
G S2 APARTMENT 713.00 6295.25 193.25
M SW APARTMENT 1756.75 4099.00 27.50
M NW APARTMENT 1350.25 4863.75 157.75
M SE APARTMENT 1812.75 4094.25 27.50
M NE APARTMENT 1374.50 4915.75 164.25
M N1 APARTMENT 781.25 4791.75 23.25
M N2 APARTMENT 783.50 4799.00 22.75
M S1 APARTMENT 1310.00 3771.25 0.00
M S2 APARTMENT 1310.75 3770.50 0.00
T SW APARTMENT 2920.25 5237.50 1108.25
T NW APARTMENT 3118.25 5772.00 1686.75
T SE APARTMENT 3008.25 5177.50 1114.25
T NE APARTMENT 3169.50 5751.25 1651.75
T N1 APARTMENT 2279.75 5839.25 1146.00
T N2 APARTMENT 2282.25 5837.00 1146.75
T S1 APARTMENT 2224.50 5121.50 609.50
T S2 APARTMENT 2228.25 5113.25 611.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4182.25 6936.75 1791.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 4.50 0.00 4.50 0.00
G NW APARTMENT 1.50 0.25 1.50 0.25
OFFICE 5.00 7.50 0.00 0.00
G NE APARTMENT 6.50 0.00 6.50 0.00
G N1 APARTMENT 8.25 0.00 8.25 0.00
G N2 APARTMENT 6.75 0.50 6.75 0.50
G S1 APARTMENT 3.25 0.00 3.25 0.00
G S2 APARTMENT 5.00 0.00 5.00 0.00
M SW APARTMENT 1.50 0.00 1.50 0.00
M NW APARTMENT 0.50 0.00 0.50 0.00
M SE APARTMENT 1.00 0.00 1.00 0.00
M NE APARTMENT 1.75 0.00 1.75 0.00
M N1 APARTMENT 1.00 0.00 1.00 0.00
M N2 APARTMENT 1.50 0.00 1.50 0.00
M S1 APARTMENT 1.25 0.00 1.25 0.00
M S2 APARTMENT 0.50 0.00 0.50 0.00
T SW APARTMENT 0.50 0.00 0.50 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.00 0.00 0.00 0.00
T NE APARTMENT 0.00 0.00 0.00 0.00
T N1 APARTMENT 1.50 0.00 1.50 0.00
T N2 APARTMENT 1.25 0.00 1.25 0.00
T S1 APARTMENT 2.00 0.00 2.00 0.00
T S2 APARTMENT 1.75 0.00 1.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 51.25 8.25 46.25 0.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.372 0.152 0.000 0.057
G NW APARTMENT 1.71 2.50 268.97 0.359 0.152 0.000 0.055
OFFICE 0.94 1.00 268.97 0.528 0.167 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.359 0.152 0.000 0.055
G N1 APARTMENT 1.71 2.50 268.97 0.359 0.092 0.000 0.054
G N2 APARTMENT 1.71 2.50 268.97 0.359 0.092 0.000 0.054
G S1 APARTMENT 1.71 2.50 268.97 0.359 0.092 0.000 0.057
G S2 APARTMENT 1.71 2.50 268.97 0.359 0.092 0.000 0.057
M SW APARTMENT 1.71 2.50 268.97 0.360 0.219 0.000 0.068
M NW APARTMENT 1.71 2.50 268.97 0.360 0.219 0.000 0.066
M SE APARTMENT 1.71 2.50 268.97 0.360 0.219 0.000 0.068
M NE APARTMENT 1.71 2.50 268.97 0.360 0.219 0.000 0.066
M N1 APARTMENT 1.71 2.50 268.97 0.360 0.132 0.000 0.066
M N2 APARTMENT 1.71 2.50 268.97 0.360 0.132 0.000 0.066
M S1 APARTMENT 1.71 2.50 268.97 0.360 0.132 0.000 0.068
M S2 APARTMENT 1.71 2.50 268.97 0.360 0.132 0.000 0.068
T SW APARTMENT 1.71 2.50 268.97 0.360 0.289 0.000 0.080
T NW APARTMENT 1.71 2.50 268.97 0.359 0.289 0.000 0.077
T SE APARTMENT 1.71 2.50 268.97 0.360 0.289 0.000 0.080
T NE APARTMENT 1.71 2.50 268.97 0.359 0.289 0.000 0.077
T N1 APARTMENT 1.71 2.50 268.97 0.359 0.174 0.000 0.077
T N2 APARTMENT 1.71 2.50 268.97 0.359 0.174 0.000 0.077
T S1 APARTMENT 1.71 2.50 268.97 0.360 0.174 0.000 0.080
T S2 APARTMENT 1.71 2.50 268.97 0.360 0.174 0.000 0.080
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.361 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.511 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.392 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.348 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1451.29 21411.80 25-APR-03:00 87515.24 29-JUL-18:00
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 407.59 0.00 01-JAN-00:15 32681.37 26-JAN-07:30
WaterSystems:Electricity 407.59 0.00 01-JAN-00:15 32681.37 26-JAN-07:30
Water Heater:WaterSystems:Electricity 407.59 0.00 01-JAN-00:15 32681.37 26-JAN-07:30
Fans:Electricity 261.72 8299.19 25-MAR-17:15 8299.19 13-JAN-06:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
ElectricityPurchased:Plant 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
Cogeneration:ElectricityPurchased 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
ElectricityNet:Plant 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
Cogeneration:ElectricityNet 1451.29 21411.80 01-JAN-03:15 87515.24 29-JUL-18:00
ExteriorLights:Electricity 40.06 0.00 01-JAN-08:30 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.06 0.00 01-JAN-08:30 2553.00 01-JAN-00:15
Electricity:HVAC 367.53 8299.19 25-MAR-17:15 33747.40 21-JUL-17:15
General:Fans:Electricity 261.72 8299.19 25-MAR-17:15 8299.19 13-JAN-06:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 105.80 0.00 01-JAN-00:15 25448.21 21-JUL-17:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 273.85 0.00 10-FEB-15:15 80039.05 04-JAN-08:00
Gas:HVAC 273.85 0.00 10-FEB-15:15 80039.05 04-JAN-08:00
Heating:Gas 273.85 0.00 10-FEB-15:15 80039.05 04-JAN-08:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1153.75 1732.55 03-MAR-18:45 158737.23 31-JUL-18:00
EnergyTransfer:Building 526.66 1732.55 03-MAR-18:45 69419.46 31-JUL-18:00
EnergyTransfer:Zone:G SW APARTMENT 12.54 0.02 03-MAY-01:00 2350.23 31-JUL-18:00
Heating:EnergyTransfer 121.96 0.00 05-FEB-16:30 45607.37 04-JAN-08:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 4.36 0.00 01-JAN-13:30 1502.64 04-JAN-08:00
Cooling:EnergyTransfer 404.70 0.00 02-JAN-07:45 69129.83 22-JUL-16:15
Cooling:EnergyTransfer:Zone:G SW APARTMENT 8.18 0.00 01-JAN-00:15 2350.23 31-JUL-18:00
EnergyTransfer:Zone:G NW APARTMENT 11.98 0.02 06-NOV-14:45 2188.99 31-JUL-18:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 6.40 0.00 26-JAN-16:45 1577.79 28-DEC-10:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 5.58 0.00 01-JAN-00:15 2188.99 31-JUL-18:00
EnergyTransfer:Zone:OFFICE 22.89 0.00 31-OCT-23:15 4594.36 06-AUG-13:15
Heating:EnergyTransfer:Zone:OFFICE 2.54 0.00 01-JAN-00:15 2452.81 04-JAN-07:15
Cooling:EnergyTransfer:Zone:OFFICE 20.35 0.00 02-JAN-07:30 4594.36 06-AUG-13:15
EnergyTransfer:Zone:G NE APARTMENT 12.04 0.01 03-NOV-13:15 1542.96 04-JAN-08:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 6.25 0.00 05-FEB-16:30 1542.96 04-JAN-08:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 5.79 0.00 01-JAN-00:15 1504.90 12-JUL-17:15
EnergyTransfer:Zone:G N1 APARTMENT 7.84 0.03 07-OCT-12:30 1153.75 12-JUL-19:30
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.10 0.00 18-JAN-17:15 911.86 04-JAN-08:15
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 4.74 0.00 01-JAN-00:15 1153.75 12-JUL-19:30
EnergyTransfer:Zone:G N2 APARTMENT 7.84 0.01 30-NOV-15:45 1142.13 12-JUL-19:30
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.09 0.00 18-JAN-17:15 911.91 04-JAN-08:15
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 4.75 0.00 01-JAN-00:15 1142.13 12-JUL-19:30
EnergyTransfer:Zone:G S1 APARTMENT 9.27 0.04 06-APR-10:45 1491.13 26-SEP-14:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 1.69 0.00 01-JAN-13:00 876.00 04-JAN-08:15
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 7.58 0.00 01-JAN-00:15 1491.13 26-SEP-14:30
EnergyTransfer:Zone:G S2 APARTMENT 9.78 0.00 16-APR-10:45 1500.92 26-SEP-14:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 1.86 0.00 01-JAN-13:15 924.36 04-JAN-08:15
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 7.92 0.00 01-JAN-00:15 1500.92 26-SEP-14:30
EnergyTransfer:Zone:M SW APARTMENT 39.41 0.05 13-FEB-13:15 6195.66 31-JUL-18:00
Heating:EnergyTransfer:Zone:M SW APARTMENT 3.70 0.00 01-JAN-10:00 3008.79 28-DEC-08:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 35.71 0.00 01-JAN-00:15 6195.66 31-JUL-18:00
EnergyTransfer:Zone:M NW APARTMENT 31.64 0.01 31-JAN-14:15 5724.64 31-JUL-18:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 7.52 0.00 03-JAN-17:15 3450.82 28-DEC-10:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 24.12 0.00 01-JAN-00:15 5724.64 31-JUL-18:00
EnergyTransfer:Zone:M SE APARTMENT 40.39 0.00 28-OCT-01:15 5273.55 22-JUL-14:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 3.81 0.00 01-JAN-13:15 3018.19 28-DEC-08:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 36.58 0.00 01-JAN-00:15 5273.55 22-JUL-14:15
EnergyTransfer:Zone:M NE APARTMENT 32.49 0.01 26-NOV-19:15 4270.68 22-JUL-16:15
Heating:EnergyTransfer:Zone:M NE APARTMENT 7.50 0.00 03-JAN-17:30 3216.15 04-JAN-05:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 24.98 0.00 01-JAN-00:15 4270.68 22-JUL-16:15
EnergyTransfer:Zone:M N1 APARTMENT 24.36 0.02 06-MAR-00:45 3331.58 23-JUN-19:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 1.83 0.00 01-JAN-10:00 1652.36 28-DEC-10:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 22.53 0.00 01-JAN-00:15 3331.58 23-JUN-19:00
EnergyTransfer:Zone:M N2 APARTMENT 24.38 0.26 11-APR-11:45 3306.49 23-JUN-19:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 1.83 0.00 01-JAN-10:00 1643.95 28-DEC-10:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 22.54 0.00 01-JAN-00:15 3306.49 23-JUN-19:00
EnergyTransfer:Zone:M S1 APARTMENT 36.61 0.25 14-JAN-20:45 4441.80 01-OCT-15:15
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.52 0.00 01-JAN-02:15 1368.67 04-JAN-05:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 36.08 0.00 01-JAN-00:15 4441.80 01-OCT-15:15
EnergyTransfer:Zone:M S2 APARTMENT 36.63 0.01 29-NOV-02:45 4440.24 01-OCT-15:15
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.53 0.00 01-JAN-02:15 1369.29 04-JAN-05:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 36.10 0.00 01-JAN-00:15 4440.24 01-OCT-15:15
EnergyTransfer:Zone:T SW APARTMENT 25.03 0.00 15-APR-05:00 4129.67 31-JUL-18:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 9.21 0.00 01-JAN-13:30 2843.61 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 15.82 0.00 01-JAN-00:15 4129.67 31-JUL-18:00
EnergyTransfer:Zone:T NW APARTMENT 23.51 0.01 12-OCT-13:00 3918.65 31-JUL-18:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 12.16 0.00 26-JAN-16:15 2908.84 28-DEC-10:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 11.35 0.00 01-JAN-00:15 3918.65 31-JUL-18:00
EnergyTransfer:Zone:T SE APARTMENT 24.89 0.01 30-APR-22:45 3611.55 22-JUL-14:15
Heating:EnergyTransfer:Zone:T SE APARTMENT 9.01 0.00 01-JAN-13:45 2851.77 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 15.88 0.00 01-JAN-00:15 3611.55 22-JUL-14:15
EnergyTransfer:Zone:T NE APARTMENT 23.17 0.00 25-OCT-11:30 3014.55 12-JUL-16:45
Heating:EnergyTransfer:Zone:T NE APARTMENT 11.79 0.00 30-JAN-17:30 2901.51 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 11.38 0.00 01-JAN-00:15 3014.55 12-JUL-16:45
EnergyTransfer:Zone:T N1 APARTMENT 16.29 0.03 19-MAR-10:15 2417.35 12-JUL-17:15
Heating:EnergyTransfer:Zone:T N1 APARTMENT 7.00 0.00 26-JAN-17:15 1913.32 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 9.30 0.00 01-JAN-00:15 2417.35 12-JUL-17:15
EnergyTransfer:Zone:T N2 APARTMENT 16.31 0.06 04-NOV-02:15 2400.02 12-JUL-17:15
Heating:EnergyTransfer:Zone:T N2 APARTMENT 7.00 0.00 26-JAN-17:15 1913.51 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 9.31 0.00 01-JAN-00:15 2400.02 12-JUL-17:15
EnergyTransfer:Zone:T S1 APARTMENT 18.67 0.04 15-SEP-05:45 2959.34 01-OCT-14:30
Heating:EnergyTransfer:Zone:T S1 APARTMENT 4.62 0.00 01-JAN-13:15 1858.53 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 14.05 0.00 01-JAN-00:15 2959.34 01-OCT-14:30
EnergyTransfer:Zone:T S2 APARTMENT 18.71 0.01 11-APR-24:00 2962.77 01-OCT-14:30
Heating:EnergyTransfer:Zone:T S2 APARTMENT 4.63 0.00 01-JAN-13:15 1858.55 04-JAN-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 14.08 0.00 01-JAN-00:15 2962.77 01-OCT-14:30
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 627.10 0.00 03-MAR-17:30 89607.00 12-JUL-17:00
HeatingCoils:EnergyTransfer 219.08 0.00 10-FEB-15:15 64031.24 04-JAN-08:00
CoolingCoils:EnergyTransfer 408.02 0.00 01-JAN-00:15 89607.00 12-JUL-17:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 4.358 -8.182 0.000 0.000 3.843 1.087 12.213 15.610 0.000 0.251 0.000 0.000 -7.435 0.000 -5.235 -16.509
G NW APARTMENT 6.400 -5.582 0.000 0.000 3.869 1.087 12.213 7.838 0.000 0.251 0.000 0.000 -7.581 0.000 -5.105 -13.390
OFFICE 2.542 -20.347 0.000 0.000 0.522 26.452 9.482 15.387 0.000 0.148 0.001 0.000 -7.432 0.000 -4.794 -21.960
G NE APARTMENT 6.247 -5.794 0.000 0.000 3.881 1.087 12.213 7.847 0.000 0.251 0.000 0.000 -7.350 0.000 -5.093 -13.289
G N1 APARTMENT 3.098 -4.742 0.000 0.000 3.883 1.087 12.213 2.564 0.000 0.160 0.000 0.000 -4.688 0.000 -3.262 -10.312
G N2 APARTMENT 3.094 -4.747 0.000 0.000 3.884 1.087 12.213 2.563 0.000 0.160 0.000 0.000 -4.687 0.000 -3.262 -10.304
G S1 APARTMENT 1.691 -7.580 0.000 0.000 3.846 1.087 12.213 10.376 0.000 0.159 0.000 0.000 -4.519 0.000 -3.399 -13.873
G S2 APARTMENT 1.859 -7.923 0.000 0.000 3.843 1.087 12.213 10.368 0.000 0.159 0.000 0.000 -4.524 0.000 -3.407 -13.673
M SW APARTMENT 3.702 -35.712 0.000 0.000 3.722 1.087 12.213 15.157 0.000 0.356 15.279 0.000 -8.115 0.000 -7.687 -0.001
M NW APARTMENT 7.520 -24.118 0.000 0.000 3.769 1.087 12.213 7.468 0.000 0.355 7.403 0.000 -8.185 0.000 -7.512 -0.001
M SE APARTMENT 3.810 -36.582 0.000 0.000 3.727 1.087 12.213 15.179 0.000 0.356 15.795 0.000 -7.901 0.000 -7.682 -0.000
M NE APARTMENT 7.504 -24.983 0.000 0.000 3.777 1.087 12.213 7.461 0.000 0.355 8.020 0.000 -7.933 0.000 -7.501 -0.001
M N1 APARTMENT 1.833 -22.527 0.000 0.000 3.762 1.087 12.213 2.336 0.000 0.223 11.047 0.000 -5.130 0.000 -4.844 -0.000
M N2 APARTMENT 1.834 -22.542 0.000 0.000 3.763 1.087 12.213 2.336 0.000 0.223 11.060 0.000 -5.129 0.000 -4.843 -0.000
M S1 APARTMENT 0.524 -36.082 0.000 0.000 3.695 1.087 12.213 10.082 0.000 0.223 18.234 0.000 -4.977 0.000 -4.999 -0.000
M S2 APARTMENT 0.529 -36.098 0.000 0.000 3.696 1.087 12.213 10.081 0.000 0.223 18.244 0.000 -4.976 0.000 -4.999 -0.000
T SW APARTMENT 9.213 -15.816 0.000 0.000 3.790 1.087 12.213 15.065 0.000 0.471 0.000 0.000 -7.657 0.000 -9.795 -8.571
T NW APARTMENT 12.156 -11.352 0.000 0.000 3.824 1.087 12.213 7.412 0.000 0.470 0.000 0.000 -7.755 0.000 -9.592 -8.463
T SE APARTMENT 9.009 -15.880 0.000 0.000 3.796 1.087 12.213 15.108 0.000 0.471 0.000 0.000 -7.470 0.000 -9.801 -8.532
T NE APARTMENT 11.789 -11.378 0.000 0.000 3.836 1.087 12.213 7.437 0.000 0.470 0.000 0.000 -7.535 0.000 -9.585 -8.333
T N1 APARTMENT 6.998 -9.295 0.000 0.000 3.826 1.087 12.213 2.341 0.000 0.297 0.000 0.000 -4.823 0.000 -6.105 -6.537
T N2 APARTMENT 7.004 -9.306 0.000 0.000 3.826 1.087 12.213 2.338 0.000 0.297 0.000 0.000 -4.821 0.000 -6.106 -6.531
T S1 APARTMENT 4.618 -14.052 0.000 0.000 3.775 1.087 12.213 10.048 0.000 0.297 0.000 0.000 -4.695 0.000 -6.295 -6.996
T S2 APARTMENT 4.625 -14.080 0.000 0.000 3.776 1.087 12.213 10.046 0.000 0.297 0.000 0.000 -4.693 0.000 -6.296 -6.973
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.133 0.000 0.036 0.000 0.000 -0.887 0.000 -1.620 -12.243
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.474 0.000 1.121 7.587 0.000 -2.310 0.000 -27.932 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.134 0.000 0.032 0.000 0.000 -0.981 0.000 -1.347 -12.419
Total Facility 121.955 -404.699 0.000 0.000 87.929 95.189 296.854 213.189 0.000 8.111 112.670 0.000 -154.192 0.000 -178.096 -198.913


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 31-JUL-18:00 0.00 -2350.12 0.00 0.00 141.80 87.56 588.62 2248.46 0.00 265.39 0.00 0.00 0.00 0.00 0.00 -981.72
G NW APARTMENT 31-JUL-18:00 0.00 -2188.89 0.00 0.00 141.80 87.56 588.62 2327.32 0.00 265.39 0.00 0.00 0.00 0.00 0.00 -1221.81
OFFICE 13-AUG-06:01 0.00 -7594.42 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 7530.62 0.00 -348.99 0.00 -297.66 0.00
G NE APARTMENT 12-JUL-17:09 0.00 -1505.41 0.00 0.00 141.80 87.56 588.62 727.80 0.00 244.21 0.00 0.00 0.00 0.00 0.00 -284.58
G N1 APARTMENT 12-JUL-19:30 0.00 -1153.75 0.00 0.00 141.64 103.77 523.87 858.55 0.00 63.14 0.00 0.00 0.00 0.00 0.00 -537.23
G N2 APARTMENT 12-JUL-19:30 0.00 -1142.13 0.00 0.00 141.59 103.77 523.87 858.72 0.00 63.14 0.00 0.00 0.00 0.00 0.00 -548.96
G S1 APARTMENT 26-SEP-14:30 0.00 -1491.14 0.00 0.00 40.75 22.70 400.26 2025.00 0.00 66.43 0.00 0.00 0.00 0.00 0.00 -1064.00
G S2 APARTMENT 26-SEP-14:30 0.00 -1500.93 0.00 0.00 40.75 22.70 400.26 2024.80 0.00 66.43 0.00 0.00 0.00 0.00 0.00 -1054.00
M SW APARTMENT 31-JUL-18:00 0.00 -6195.37 0.00 0.00 141.80 87.56 588.62 2236.55 0.00 380.84 2759.99 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 31-JUL-18:00 0.00 -5724.34 0.00 0.00 141.80 87.56 588.62 2314.92 0.00 380.84 2210.59 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 22-JUL-14:15 0.00 -5273.34 0.00 0.00 40.75 22.70 400.26 1785.25 0.00 353.27 2671.11 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 22-JUL-16:13 0.00 -4272.64 0.00 0.00 84.76 64.86 588.62 802.83 0.00 317.49 2414.07 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 23-JUN-19:00 0.00 -3331.10 0.00 0.00 141.81 103.77 547.42 785.05 0.00 165.64 1587.42 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 23-JUN-19:00 0.00 -3306.02 0.00 0.00 141.81 103.77 547.42 785.20 0.00 165.64 1562.19 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 01-OCT-15:15 0.00 -4441.87 0.00 0.00 48.90 45.40 470.90 1793.99 0.00 46.20 2036.49 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 01-OCT-15:15 0.00 -4440.31 0.00 0.00 48.90 45.40 470.90 1793.98 0.00 46.20 2034.94 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 21-JUL-17:04 0.00 -4129.89 0.00 0.00 141.81 87.56 588.62 2291.59 0.00 380.24 640.08 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 31-JUL-18:00 0.00 -3918.42 0.00 0.00 141.80 87.56 588.62 2277.36 0.00 502.29 320.78 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 22-JUL-14:15 0.00 -3611.40 0.00 0.00 40.75 22.70 400.26 1753.76 0.00 465.75 928.18 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 12-JUL-16:45 0.00 -3014.75 0.00 0.00 84.76 64.86 588.62 751.09 0.00 461.59 1063.83 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 12-JUL-17:06 0.00 -2417.73 0.00 0.00 141.80 87.56 588.62 431.88 0.00 278.70 889.17 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 12-JUL-17:06 0.00 -2400.40 0.00 0.00 141.80 87.56 588.62 432.11 0.00 278.70 871.61 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 01-OCT-14:30 0.00 -2959.43 0.00 0.00 40.75 22.70 400.26 2121.98 0.00 27.01 346.74 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 01-OCT-14:30 0.00 -2962.86 0.00 0.00 40.75 22.70 400.26 2121.91 0.00 27.01 350.24 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 22-JUL-16:04 0.00 -69140.97 0.00 0.00 1949.41 3295.01 14142.04 26068.85 0.00 9624.37 14061.29 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 04-JAN-08:02 1503.51 0.00 0.00 0.00 73.97 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -742.82 0.00 -750.33 -492.28
G NW APARTMENT 28-DEC-10:00 1577.65 0.00 0.00 0.00 47.42 12.97 394.38 0.00 0.00 0.00 0.00 0.00 -539.70 0.00 -953.09 -539.62
OFFICE 24-DEC-07:01 5142.63 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -360.07 0.00 -343.69 -5149.33
G NE APARTMENT 21-APR-06:01 1785.73 0.00 0.00 0.00 163.01 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -122.25 0.00 -89.96 -2161.28
G N1 APARTMENT 11-MAR-16:01 2003.54 0.00 0.00 0.00 99.95 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -46.60 0.00 -151.48 -2558.89
G N2 APARTMENT 27-OCT-06:01 1039.73 0.00 0.00 0.00 163.21 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -298.35 0.00 -122.73 -1206.63
G S1 APARTMENT 06-DEC-07:01 1296.37 0.00 0.00 0.00 161.41 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -339.21 0.00 0.00 -1543.34
G S2 APARTMENT 27-JAN-18:01 1350.83 0.00 0.00 0.00 165.23 87.56 588.62 0.00 0.00 0.00 0.00 0.00 -354.73 0.00 -120.53 -1716.99
M SW APARTMENT 28-DEC-07:55 3008.80 0.00 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -751.04 0.00 -1189.81 -1653.93
M NW APARTMENT 28-DEC-10:00 3450.54 0.00 0.00 0.00 47.42 12.97 394.38 0.00 0.00 0.00 0.00 0.00 -559.41 0.00 -1370.71 -1975.18
M SE APARTMENT 28-DEC-08:00 3018.63 0.00 0.00 0.00 161.22 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -761.19 0.00 -1189.81 -1653.61
M NE APARTMENT 04-JAN-05:00 3216.04 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -749.62 0.00 -1132.57 -1766.66
M N1 APARTMENT 18-NOV-07:01 2979.23 0.00 0.00 0.00 161.47 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -393.40 0.00 -156.05 -3016.01
M N2 APARTMENT 18-NOV-07:01 2977.84 0.00 0.00 0.00 161.47 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -393.37 0.00 -156.04 -3014.66
M S1 APARTMENT 11-JAN-09:00 1437.16 0.00 0.00 0.00 73.97 19.46 388.49 39.50 0.00 0.00 0.00 0.00 0.00 0.00 -161.64 -1796.95
M S2 APARTMENT 13-JAN-01:25 1874.26 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -565.99 0.00 -95.36 -1650.39
T SW APARTMENT 04-JAN-05:00 2843.51 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -735.93 0.00 -1500.17 -1040.21
T NW APARTMENT 28-DEC-10:00 2908.62 0.00 0.00 0.00 47.42 12.97 394.38 0.00 0.00 0.00 0.00 0.00 -541.42 0.00 -1815.78 -1006.19
T SE APARTMENT 04-JAN-05:00 2851.67 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -746.87 0.00 -1500.17 -1037.42
T NE APARTMENT 04-JAN-05:00 2901.41 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -727.34 0.00 -1500.17 -1106.70
T N1 APARTMENT 04-JAN-05:00 1913.26 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -435.48 0.00 -904.90 -1005.69
T N2 APARTMENT 04-JAN-05:00 1913.45 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -435.48 0.00 -904.90 -1005.88
T S1 APARTMENT 04-JAN-05:00 1858.47 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -455.54 0.00 -904.90 -930.83
T S2 APARTMENT 04-JAN-05:00 1858.49 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -455.54 0.00 -904.90 -930.86
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-JAN-07:50 45621.53 0.00 0.00 0.00 3708.06 2772.92 9503.69 0.00 0.00 0.00 0.00 0.00 -14713.52 0.00 -33431.32 -13461.36



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Sec1.1A-General Information

Data
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 46.25
Number of hours cooling loads not met 0.75
Number of hours not met 47.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.06 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 273.85 80039.05 0.00 0.00
Space Cooling 105.80 23997.97 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 261.72 8299.19 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 407.59 23607.21 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1451.29   273.85   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1451.29
Natural Gas 0.00 273.85
Additional 0.00 0.00
Total 517.65 1725.14


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 33.75
Fans-Interior 83.49
Service Water Heating 130.03
Receptacle Equipment 165.14
Miscellaneous 12.78
Subtotal 462.99


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 87.36
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 87.36


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.87
Space Heating 15.87
Space Cooling 6.13
Fans-Interior 15.17
Service Water Heating 23.63
Receptacle Equipment 30.01
Miscellaneous 2.32



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.205081
G NW APARTMENT DIRECT AIR 0.188899
OFFICE DIRECT AIR 0.494879
G NE APARTMENT DIRECT AIR 0.138983
G N1 APARTMENT DIRECT AIR 0.103655
G N2 APARTMENT DIRECT AIR 0.102398
G S1 APARTMENT DIRECT AIR 0.129977
G S2 APARTMENT DIRECT AIR 0.133006
M SW APARTMENT DIRECT AIR 0.552084
M NW APARTMENT DIRECT AIR 0.504346
M SE APARTMENT DIRECT AIR 0.500273
M NE APARTMENT DIRECT AIR 0.402771
M N1 APARTMENT DIRECT AIR 0.292800
M N2 APARTMENT DIRECT AIR 0.290741
M S1 APARTMENT DIRECT AIR 0.367342
M S2 APARTMENT DIRECT AIR 0.368684
T SW APARTMENT DIRECT AIR 0.378988
T NW APARTMENT DIRECT AIR 0.343932
T SE APARTMENT DIRECT AIR 0.354654
T NE APARTMENT DIRECT AIR 0.284291
T N1 APARTMENT DIRECT AIR 0.219446
T N2 APARTMENT DIRECT AIR 0.219504
T S1 APARTMENT DIRECT AIR 0.285876
T S2 APARTMENT DIRECT AIR 0.286691


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.205081
SPLIT GNW MAIN BRANCH 0.188899
SPLIT OFFICE MAIN BRANCH 0.494879
SPLIT GNE MAIN BRANCH 0.138983
SPLIT GN1 MAIN BRANCH 0.103655
SPLIT GN2 MAIN BRANCH 0.102398
SPLIT GS1 MAIN BRANCH 0.129977
SPLIT GS2 MAIN BRANCH 0.133006
SPLIT MSW MAIN BRANCH 0.552084
SPLIT MNW MAIN BRANCH 0.504346
SPLIT MSE MAIN BRANCH 0.500273
SPLIT MNE MAIN BRANCH 0.402771
SPLIT MN1 MAIN BRANCH 0.292800
SPLIT MN2 MAIN BRANCH 0.290741
SPLIT MS1 MAIN BRANCH 0.367342
SPLIT MS2 MAIN BRANCH 0.368684
SPLIT TSW MAIN BRANCH 0.378988
SPLIT TNW MAIN BRANCH 0.343932
SPLIT TSE MAIN BRANCH 0.354654
SPLIT TNE MAIN BRANCH 0.284291
SPLIT TN1 MAIN BRANCH 0.219446
SPLIT TN2 MAIN BRANCH 0.219504
SPLIT TS1 MAIN BRANCH 0.285876
SPLIT TS2 MAIN BRANCH 0.286691


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.205081
SPLIT GNW 0.188899
SPLIT OFFICE 0.494879
SPLIT GNE 0.138983
SPLIT GN1 0.103655
SPLIT GN2 0.102398
SPLIT GS1 0.129977
SPLIT GS2 0.133006
SPLIT MSW 0.552084
SPLIT MNW 0.504346
SPLIT MSE 0.500273
SPLIT MNE 0.402771
SPLIT MN1 0.292800
SPLIT MN2 0.290741
SPLIT MS1 0.367342
SPLIT MS2 0.368684
SPLIT TSW 0.378988
SPLIT TNW 0.343932
SPLIT TSE 0.354654
SPLIT TNE 0.284291
SPLIT TN1 0.219446
SPLIT TN2 0.219504
SPLIT TS1 0.285876
SPLIT TS2 0.286691


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.205081 0.026898
SPLIT GNW OA CONTROLLER 0.188899 0.025953
SPLIT OFFICE OA CONTROLLER 0.494879 0.038104
SPLIT GNE OA CONTROLLER 0.138983 0.025953
SPLIT GN1 OA CONTROLLER 0.103655 0.025953
SPLIT GN2 OA CONTROLLER 0.102398 0.025953
SPLIT GS1 OA CONTROLLER 0.129977 0.025953
SPLIT GS2 OA CONTROLLER 0.133006 0.025953
SPLIT MSW OA CONTROLLER 0.552084 0.051906
SPLIT MNW OA CONTROLLER 0.504346 0.051906
SPLIT MSE OA CONTROLLER 0.500273 0.051906
SPLIT MNE OA CONTROLLER 0.402771 0.051906
SPLIT MN1 OA CONTROLLER 0.292800 0.051906
SPLIT MN2 OA CONTROLLER 0.290741 0.051906
SPLIT MS1 OA CONTROLLER 0.367342 0.051906
SPLIT MS2 OA CONTROLLER 0.368684 0.051906
SPLIT TSW OA CONTROLLER 0.378988 0.025953
SPLIT TNW OA CONTROLLER 0.343932 0.025953
SPLIT TSE OA CONTROLLER 0.354654 0.025953
SPLIT TNE OA CONTROLLER 0.284291 0.025953
SPLIT TN1 OA CONTROLLER 0.219446 0.025953
SPLIT TN2 OA CONTROLLER 0.219504 0.025953
SPLIT TS1 OA CONTROLLER 0.285876 0.025953
SPLIT TS2 OA CONTROLLER 0.286691 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.205081 3394.82 0.798655
SPLIT GNW COOLING COIL 0.188899 3126.95 0.798655
SPLIT OFFICE COOLING COIL 0.494879 8192.01 0.798655
SPLIT GNE COOLING COIL 0.138983 2300.66 0.798655
SPLIT GN1 COOLING COIL 0.103655 1715.86 0.798655
SPLIT GN2 COOLING COIL 0.102398 1695.05 0.798655
SPLIT GS1 COOLING COIL 0.129977 2212.37 0.788555
SPLIT GS2 COOLING COIL 0.133006 2259.55 0.789247
SPLIT MSW COOLING COIL 0.552084 9138.95 0.798655
SPLIT MNW COOLING COIL 0.504346 8348.72 0.798655
SPLIT MSE COOLING COIL 0.500273 8281.29 0.798655
SPLIT MNE COOLING COIL 0.402771 6667.30 0.798655
SPLIT MN1 COOLING COIL 0.292800 4846.87 0.798655
SPLIT MN2 COOLING COIL 0.290741 4812.79 0.798655
SPLIT MS1 COOLING COIL 0.367342 6080.81 0.798655
SPLIT MS2 COOLING COIL 0.368684 6103.03 0.798655
SPLIT TSW COOLING COIL 0.378988 6273.59 0.798655
SPLIT TNW COOLING COIL 0.343932 5693.30 0.798655
SPLIT TSE COOLING COIL 0.354654 5870.78 0.798655
SPLIT TNE COOLING COIL 0.284291 4706.02 0.798655
SPLIT TN1 COOLING COIL 0.219446 3632.62 0.798655
SPLIT TN2 COOLING COIL 0.219504 3633.57 0.798655
SPLIT TS1 COOLING COIL 0.285876 4732.26 0.798655
SPLIT TS2 COOLING COIL 0.286691 4745.75 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.205081 0.205081 0.205081 0.205081 3090.00 3394.82 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.188899 0.188899 0.188899 0.188899 3042.14 3126.95 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.494879 0.494879 0.494879 0.494879 5450.83 8192.01 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.138983 0.138983 0.138983 0.138983 3049.53 2300.66 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.103655 0.103655 0.103655 0.103655 2320.92 1715.86 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.102398 0.102398 0.102398 0.102398 2321.09 1695.05 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.129977 0.129977 0.129977 0.129977 2331.74 2212.37 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.133006 0.133006 0.133006 0.133006 2452.70 2259.55 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.552084 0.552084 0.552084 0.552084 5913.15 9138.95 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.504346 0.504346 0.504346 0.504346 5887.20 8348.72 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.500273 0.500273 0.500273 0.500273 5932.81 8281.29 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.402771 0.402771 0.402771 0.402771 5906.88 6667.30 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.292800 0.292800 0.292800 0.292800 4095.72 4846.87 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.290741 0.290741 0.290741 0.290741 4096.22 4812.79 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.367342 0.367342 0.367342 0.367342 4124.14 6080.81 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.368684 0.368684 0.368684 0.368684 4124.64 6103.03 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.378988 0.378988 0.378988 0.378988 4458.36 6273.59 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.343932 0.343932 0.343932 0.343932 4446.32 5693.30 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.354654 0.354654 0.354654 0.354654 4468.76 5870.78 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.284291 0.284291 0.284291 0.284291 4456.75 4706.02 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.219446 0.219446 0.219446 0.219446 3492.72 3632.62 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.219504 0.219504 0.219504 0.219504 3493.00 3633.57 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.285876 0.285876 0.285876 0.285876 3503.36 4732.26 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.286691 0.286691 0.286691 0.286691 3503.64 4745.75 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.205081
SPLIT GNW SUPPLY FAN 0.188899
SPLIT OFFICE SUPPLY FAN 0.494879
SPLIT GNE SUPPLY FAN 0.138983
SPLIT GN1 SUPPLY FAN 0.103655
SPLIT GN2 SUPPLY FAN 0.102398
SPLIT GS1 SUPPLY FAN 0.129977
SPLIT GS2 SUPPLY FAN 0.133006
SPLIT MSW SUPPLY FAN 0.552084
SPLIT MNW SUPPLY FAN 0.504346
SPLIT MSE SUPPLY FAN 0.500273
SPLIT MNE SUPPLY FAN 0.402771
SPLIT MN1 SUPPLY FAN 0.292800
SPLIT MN2 SUPPLY FAN 0.290741
SPLIT MS1 SUPPLY FAN 0.367342
SPLIT MS2 SUPPLY FAN 0.368684
SPLIT TSW SUPPLY FAN 0.378988
SPLIT TNW SUPPLY FAN 0.343932
SPLIT TSE SUPPLY FAN 0.354654
SPLIT TNE SUPPLY FAN 0.284291
SPLIT TN1 SUPPLY FAN 0.219446
SPLIT TN2 SUPPLY FAN 0.219504
SPLIT TS1 SUPPLY FAN 0.285876
SPLIT TS2 SUPPLY FAN 0.286691


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 3090.00
SPLIT GNW HEATING COIL 3042.14
SPLIT OFFICE HEATING COIL 5450.83
SPLIT GNE HEATING COIL 3049.53
SPLIT GN1 HEATING COIL 2320.92
SPLIT GN2 HEATING COIL 2321.09
SPLIT GS1 HEATING COIL 2331.74
SPLIT GS2 HEATING COIL 2452.70
SPLIT MSW HEATING COIL 5913.15
SPLIT MNW HEATING COIL 5887.20
SPLIT MSE HEATING COIL 5932.81
SPLIT MNE HEATING COIL 5906.88
SPLIT MN1 HEATING COIL 4095.72
SPLIT MN2 HEATING COIL 4096.22
SPLIT MS1 HEATING COIL 4124.14
SPLIT MS2 HEATING COIL 4124.64
SPLIT TSW HEATING COIL 4458.36
SPLIT TNW HEATING COIL 4446.32
SPLIT TSE HEATING COIL 4468.76
SPLIT TNE HEATING COIL 4456.75
SPLIT TN1 HEATING COIL 3492.72
SPLIT TN2 HEATING COIL 3493.00
SPLIT TS1 HEATING COIL 3503.36
SPLIT TS2 HEATING COIL 3503.64



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:47:26

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 -1.7
February 21.84 2.70
March 22.03 6.07
April 22.72 11.58
May 23.09 14.61
June 24.18 19.78
July 24.39 24.54
August 24.32 21.22
September 24.21 17.37
October 22.93 11.70
November 21.93 4.05
December 21.77 1.86
     
Annual Sum or Average 22.93 11.20
Minimum of Months 21.71 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.71 2.70
March 21.78 6.07
April 22.39 11.58
May 22.88 14.61
June 24.15 19.78
July 24.39 24.54
August 24.28 21.22
September 24.07 17.37
October 22.38 11.70
November 21.74 4.05
December 21.70 1.86
     
Annual Sum or Average 22.77 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.30 -1.7
February 21.50 2.70
March 22.38 6.07
April 23.63 11.58
May 24.24 14.61
June 26.03 19.78
July 26.95 24.54
August 26.33 21.22
September 26.07 17.37
October 24.03 11.70
November 21.86 4.05
December 21.06 1.86
     
Annual Sum or Average 23.71 11.20
Minimum of Months 20.30 -1.7
Maximum of Months 26.95 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.70 2.70
March 21.75 6.07
April 22.33 11.58
May 22.82 14.61
June 24.13 19.78
July 24.38 24.54
August 24.26 21.22
September 24.02 17.37
October 22.31 11.70
November 21.73 4.05
December 21.70 1.86
     
Annual Sum or Average 22.74 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.38 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.70 2.70
March 21.73 6.07
April 22.18 11.58
May 22.60 14.61
June 24.10 19.78
July 24.38 24.54
August 24.25 21.22
September 24.03 17.37
October 22.25 11.70
November 21.73 4.05
December 21.70 1.86
     
Annual Sum or Average 22.70 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.38 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.70 2.70
March 21.73 6.07
April 22.18 11.58
May 22.60 14.61
June 24.10 19.78
July 24.38 24.54
August 24.25 21.22
September 24.03 17.37
October 22.25 11.70
November 21.73 4.05
December 21.70 1.86
     
Annual Sum or Average 22.70 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.38 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -1.7
February 21.84 2.70
March 22.00 6.07
April 22.63 11.58
May 22.92 14.61
June 24.17 19.78
July 24.39 24.54
August 24.33 21.22
September 24.24 17.37
October 23.00 11.70
November 21.95 4.05
December 21.78 1.86
     
Annual Sum or Average 22.92 11.20
Minimum of Months 21.72 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -1.7
February 21.84 2.70
March 22.01 6.07
April 22.66 11.58
May 22.96 14.61
June 24.20 19.78
July 24.39 24.54
August 24.34 21.22
September 24.26 17.37
October 23.04 11.70
November 21.96 4.05
December 21.78 1.86
     
Annual Sum or Average 22.94 11.20
Minimum of Months 21.72 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.80 -1.7
February 22.27 2.70
March 22.86 6.07
April 24.07 11.58
May 24.32 14.61
June 24.37 19.78
July 24.40 24.54
August 24.40 21.22
September 24.38 17.37
October 24.17 11.70
November 22.72 4.05
December 22.03 1.86
     
Annual Sum or Average 23.49 11.20
Minimum of Months 21.80 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.77 2.70
March 22.08 6.07
April 23.74 11.58
May 24.28 14.61
June 24.36 19.78
July 24.40 24.54
August 24.39 21.22
September 24.34 17.37
October 23.68 11.70
November 22.26 4.05
December 21.71 1.86
     
Annual Sum or Average 23.23 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 -1.7
February 22.23 2.70
March 22.86 6.07
April 24.09 11.58
May 24.31 14.61
June 24.37 19.78
July 24.40 24.54
August 24.40 21.22
September 24.37 17.37
October 24.17 11.70
November 22.69 4.05
December 21.99 1.86
     
Annual Sum or Average 23.48 11.20
Minimum of Months 21.78 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.73 2.70
March 22.03 6.07
April 23.73 11.58
May 24.25 14.61
June 24.36 19.78
July 24.40 24.54
August 24.39 21.22
September 24.32 17.37
October 23.64 11.70
November 22.18 4.05
December 21.70 1.86
     
Annual Sum or Average 23.21 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.76 2.70
March 22.06 6.07
April 23.79 11.58
May 24.32 14.61
June 24.37 19.78
July 24.40 24.54
August 24.39 21.22
September 24.35 17.37
October 23.82 11.70
November 22.38 4.05
December 21.71 1.86
     
Annual Sum or Average 23.26 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.76 2.70
March 22.06 6.07
April 23.79 11.58
May 24.31 14.61
June 24.37 19.78
July 24.40 24.54
August 24.39 21.22
September 24.35 17.37
October 23.82 11.70
November 22.38 4.05
December 21.71 1.86
     
Annual Sum or Average 23.26 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 -1.7
February 22.53 2.70
March 23.19 6.07
April 24.21 11.58
May 24.36 14.61
June 24.38 19.78
July 24.40 24.54
August 24.40 21.22
September 24.40 17.37
October 24.31 11.70
November 22.98 4.05
December 22.27 1.86
     
Annual Sum or Average 23.61 11.20
Minimum of Months 21.87 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.87 -1.7
February 22.53 2.70
March 23.19 6.07
April 24.21 11.58
May 24.36 14.61
June 24.38 19.78
July 24.40 24.54
August 24.40 21.22
September 24.40 17.37
October 24.31 11.70
November 22.98 4.05
December 22.26 1.86
     
Annual Sum or Average 23.61 11.20
Minimum of Months 21.87 -1.7
Maximum of Months 24.40 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -1.7
February 22.11 2.70
March 22.46 6.07
April 23.43 11.58
May 23.91 14.61
June 24.22 19.78
July 24.39 24.54
August 24.29 21.22
September 24.14 17.37
October 23.37 11.70
November 22.21 4.05
December 21.91 1.86
     
Annual Sum or Average 23.19 11.20
Minimum of Months 21.79 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.77 2.70
March 22.06 6.07
April 23.18 11.58
May 23.83 14.61
June 24.20 19.78
July 24.39 24.54
August 24.25 21.22
September 23.98 17.37
October 22.87 11.70
November 21.87 4.05
December 21.71 1.86
     
Annual Sum or Average 22.99 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -1.7
February 22.09 2.70
March 22.47 6.07
April 23.46 11.58
May 23.92 14.61
June 24.24 19.78
July 24.39 24.54
August 24.29 21.22
September 24.12 17.37
October 23.40 11.70
November 22.20 4.05
December 21.89 1.86
     
Annual Sum or Average 23.19 11.20
Minimum of Months 21.77 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.73 2.70
March 22.01 6.07
April 23.17 11.58
May 23.79 14.61
June 24.19 19.78
July 24.38 24.54
August 24.23 21.22
September 23.94 17.37
October 22.83 11.70
November 21.85 4.05
December 21.70 1.86
     
Annual Sum or Average 22.97 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.38 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.73 2.70
March 21.99 6.07
April 23.19 11.58
May 23.85 14.61
June 24.22 19.78
July 24.39 24.54
August 24.25 21.22
September 23.98 17.37
October 22.83 11.70
November 21.85 4.05
December 21.70 1.86
     
Annual Sum or Average 22.98 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 -1.7
February 21.73 2.70
March 21.99 6.07
April 23.19 11.58
May 23.84 14.61
June 24.22 19.78
July 24.39 24.54
August 24.25 21.22
September 23.98 17.37
October 22.83 11.70
November 21.85 4.05
December 21.70 1.86
     
Annual Sum or Average 22.98 11.20
Minimum of Months 21.70 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -1.7
February 22.18 2.70
March 22.55 6.07
April 23.57 11.58
May 24.00 14.61
June 24.26 19.78
July 24.39 24.54
August 24.32 21.22
September 24.20 17.37
October 23.54 11.70
November 22.31 4.05
December 21.97 1.86
     
Annual Sum or Average 23.27 11.20
Minimum of Months 21.82 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -1.7
February 22.18 2.70
March 22.55 6.07
April 23.57 11.58
May 24.00 14.61
June 24.26 19.78
July 24.39 24.54
August 24.32 21.22
September 24.20 17.37
October 23.55 11.70
November 22.31 4.05
December 21.97 1.86
     
Annual Sum or Average 23.27 11.20
Minimum of Months 21.82 -1.7
Maximum of Months 24.39 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.93 -1.7
February 21.72 2.70
March 22.52 6.07
April 24.46 11.58
May 25.31 14.61
June 26.24 19.78
July 26.88 24.54
August 26.38 21.22
September 25.66 17.37
October 24.03 11.70
November 21.92 4.05
December 21.31 1.86
     
Annual Sum or Average 23.96 11.20
Minimum of Months 20.93 -1.7
Maximum of Months 26.88 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.40 -1.7
February 19.47 2.70
March 20.26 6.07
April 21.87 11.58
May 22.67 14.61
June 25.21 19.78
July 26.51 24.54
August 25.88 21.22
September 24.90 17.37
October 22.19 11.70
November 19.83 4.05
December 19.15 1.86
     
Annual Sum or Average 22.21 11.20
Minimum of Months 18.40 -1.7
Maximum of Months 26.51 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:47:26

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.80 -1.7
February 23.47 2.70
March 24.10 6.07
April 25.87 11.58
May 26.37 14.61
June 26.72 19.78
July 26.98 24.54
August 26.80 21.22
September 26.58 17.37
October 25.88 11.70
November 24.02 4.05
December 23.13 1.86
     
Annual Sum or Average 25.23 11.20
Minimum of Months 22.80 -1.7
Maximum of Months 26.98 24.54



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:26

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.118969E+12 74708.810 16-JAN-18:45 4979.953 26630.920 8299.189 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 32245.746 0.000 0.000 0.000
February 0.107828E+12 73725.253 16-FEB-18:45 4979.953 26630.920 8299.189 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 31262.190 0.000 0.000 0.000
March 0.118969E+12 71412.340 16-MAR-17:00 4979.953 26630.920 8299.189 0.000 1483.961 0.000 0.000 0.000 0.000 0.000 0.000 30018.316 0.000 0.000 0.000
April 0.117479E+12 80553.276 12-APR-17:15 4979.953 26630.920 8299.189 0.000 12691.678 0.000 0.000 0.000 0.000 0.000 0.000 27951.534 0.000 0.000 0.000
May 0.122509E+12 80227.305 04-MAY-17:00 4979.953 26630.920 8299.189 0.000 16673.725 0.000 0.000 0.000 0.000 0.000 0.000 23643.518 0.000 0.000 0.000
June 0.126286E+12 84500.315 23-JUN-17:00 4979.953 26630.920 8299.189 0.000 21664.896 0.000 0.000 0.000 0.000 0.000 0.000 22925.356 0.000 0.000 0.000
July 0.138542E+12 87515.237 29-JUL-17:00 4979.953 26630.920 8299.189 0.000 23997.968 0.000 0.000 0.000 0.000 0.000 0.000 23607.206 0.000 0.000 0.000
August 0.131803E+12 82518.614 04-AUG-17:45 4979.953 26630.920 8299.189 0.000 22263.654 0.000 0.000 0.000 0.000 0.000 0.000 20344.897 0.000 0.000 0.000
September 0.120845E+12 76555.557 08-SEP-17:15 4979.953 26630.920 8299.189 0.000 17895.363 0.000 0.000 0.000 0.000 0.000 0.000 18750.131 0.000 0.000 0.000
October 0.118212E+12 75779.506 01-OCT-17:30 4979.953 26630.920 8299.189 0.000 15893.010 0.000 0.000 0.000 0.000 0.000 0.000 19976.433 0.000 0.000 0.000
November 0.112231E+12 70675.017 04-NOV-17:45 4979.953 26630.920 8299.189 0.000 4014.965 2553.000 0.000 0.000 0.000 0.000 0.000 24196.989 0.000 0.000 0.000
December 0.117615E+12 71016.870 27-DEC-18:45 4979.953 26630.920 8299.189 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 28553.807 0.000 0.000 0.000
                                     
Annual Sum or Average 0.145129E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.107828E+12 70675.017   4979.953 26630.920 8299.189 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18750.131 0.000 0.000 0.000
Maximum of Months 0.138542E+12 87515.237   4979.953 26630.920 8299.189 0.000 23997.968 2553.000 0.000 0.000 0.000 0.000 0.000 32245.746 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:47:26

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.884584E+11 80039.050 04-JAN-07:00 80039.050 0.000 0.000 0.000 0.000 0.000 80039.050
February 0.438192E+11 51074.671 27-FEB-03:00 51074.671 0.000 0.000 0.000 0.000 0.000 51074.671
March 0.258370E+11 39535.753 11-MAR-05:00 39535.753 0.000 0.000 0.000 0.000 0.000 39535.753
April 0.570249E+10 29373.712 08-APR-04:00 29373.712 0.000 0.000 0.000 0.000 0.000 29373.712
May 0.106153E+10 9585.550 13-MAY-04:00 9585.550 0.000 0.000 0.000 0.000 0.000 9585.550
June 0.989059E+08 6494.753 13-JUN-03:00 6494.753 0.000 0.000 0.000 0.000 0.000 6494.753
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 582513.883 165.588 18-AUG-05:45 165.588 0.000 0.000 0.000 0.000 0.000 165.588
September 0.953695E+08 3842.773 20-SEP-06:30 3842.773 0.000 0.000 0.000 0.000 0.000 3842.773
October 0.417692E+10 20156.089 26-OCT-07:15 20156.089 0.000 0.000 0.000 0.000 0.000 20156.089
November 0.402540E+11 59313.837 24-NOV-04:00 59313.837 0.000 0.000 0.000 0.000 0.000 59313.837
December 0.643444E+11 77137.283 28-DEC-07:00 77137.283 0.000 0.000 0.000 0.000 0.000 77137.283
                     
Annual Sum or Average 0.273849E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.884584E+11 80039.050   80039.050 0.000 0.000 0.000 0.000 0.000 80039.050