Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2015-09-09 18:48:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1623.49 | 517.92 | 574.90 |
Net Site Energy | 1623.49 | 517.92 | 574.90 |
Total Source Energy | 5137.96 | 1639.10 | 1819.41 |
Net Source Energy | 5137.96 | 1639.10 | 1819.41 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 407.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 241.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 295.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1621.74 | 1.75 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 407.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 241.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 295.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 334.79 | 0.62 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 574.28 | 0.62 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 301.61 | 0.56 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 517.37 | 0.56 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1621.74 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1621.74 | 100.00 |
Total On-Site and Utility Electric Sources | 1621.74 | 100.00 |
Total Electricity End Uses | 1621.74 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.00 |
Time Setpoint Not Met During Occupied Cooling | 15.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4228.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 27-JUL-17:15 | 04-FEB-06:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 23115.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29475.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7665.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19384.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 88137.22 | 23115.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 23115.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29475.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7665.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 19384.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 |
Cooling | 1291.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 765.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 936.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5136.06 | 1.90 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Cooling | 457.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 331.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1818.73 | 0.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Cooling | 457.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 331.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1818.73 | 0.67 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 5.778 | 0.306 | 0.155 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 5.778 | 0.306 | 0.155 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_1.22_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 5.778 | 0.306 | 0.155 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_1.22_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 5.778 | 0.306 | 0.155 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_1.22_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 5.778 | 0.306 | 0.155 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_1.22_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 5.778 | 0.306 | 0.155 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 112.97 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 193.95 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.86 | 83.86 | 40.19 | |
Exterior Lighting Total | 2553.00 | 40.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4366.02 | 3103.71 | 1262.32 | 0.71 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4525.00 | 3246.48 | 1278.52 | 0.72 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8767.51 | 6709.30 | 2058.21 | 0.77 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3726.37 | 2615.20 | 1111.17 | 0.70 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2890.13 | 1979.99 | 910.14 | 0.69 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2873.37 | 1966.73 | 906.64 | 0.68 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2630.57 | 1778.49 | 852.09 | 0.68 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2644.56 | 1787.94 | 856.62 | 0.68 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10464.11 | 7526.25 | 2937.87 | 0.72 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10885.24 | 7876.42 | 3008.82 | 0.72 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8968.12 | 6342.60 | 2625.52 | 0.71 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9110.09 | 6472.57 | 2637.52 | 0.71 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7054.75 | 4928.08 | 2126.68 | 0.70 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7027.23 | 4906.18 | 2121.05 | 0.70 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6508.80 | 4491.38 | 2017.42 | 0.69 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6482.04 | 4470.30 | 2011.74 | 0.69 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6707.07 | 4893.49 | 1813.59 | 0.73 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6856.01 | 5019.34 | 1836.67 | 0.73 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5873.47 | 4203.50 | 1669.97 | 0.72 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5799.83 | 4174.62 | 1625.21 | 0.72 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4585.70 | 3280.88 | 1304.81 | 0.72 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4556.60 | 3257.60 | 1299.00 | 0.71 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4663.32 | 3314.83 | 1348.49 | 0.71 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4668.26 | 3318.89 | 1349.37 | 0.71 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4208.0 | 3.28 | 11.21 | 11.67 | 11.17 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4357.5 | 3.27 | 11.16 | 11.63 | 11.10 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8389.7 | 3.19 | 10.87 | 11.30 | 10.67 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3595.8 | 3.30 | 11.26 | 11.73 | 11.25 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2795.0 | 3.33 | 11.37 | 11.85 | 11.42 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2779.0 | 3.33 | 11.38 | 11.86 | 11.42 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2547.0 | 3.35 | 11.43 | 11.92 | 11.51 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2560.5 | 3.35 | 11.43 | 11.92 | 11.51 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10074.3 | 3.27 | 11.15 | 11.61 | 11.09 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10473.7 | 3.26 | 11.13 | 11.58 | 11.04 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8647.7 | 3.29 | 11.23 | 11.70 | 11.20 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8780.9 | 3.28 | 11.21 | 11.67 | 11.17 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6810.5 | 3.31 | 11.28 | 11.76 | 11.29 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6784.3 | 3.31 | 11.29 | 11.76 | 11.29 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6290.5 | 3.32 | 11.34 | 11.82 | 11.37 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6265.0 | 3.32 | 11.34 | 11.82 | 11.37 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6448.4 | 3.25 | 11.09 | 11.54 | 10.99 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6589.4 | 3.25 | 11.07 | 11.53 | 10.97 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5657.3 | 3.28 | 11.18 | 11.64 | 11.12 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5583.4 | 3.27 | 11.15 | 11.61 | 11.08 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4417.1 | 3.28 | 11.18 | 11.64 | 11.12 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4389.4 | 3.28 | 11.18 | 11.64 | 11.13 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4494.6 | 3.28 | 11.21 | 11.67 | 11.17 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4499.3 | 3.28 | 11.21 | 11.67 | 11.17 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1342.62 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1298.56 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 2545.96 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1295.43 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1295.43 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1295.43 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1295.43 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1295.43 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 2748.33 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 2776.06 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 2730.36 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 2758.20 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 2590.86 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 2590.86 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 2590.86 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 2590.86 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2020.56 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2035.11 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2011.32 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2025.89 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 1441.97 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 1441.69 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 1425.23 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 1424.96 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 233.07 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 247.24 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 558.96 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 192.48 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 140.07 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.12 | 138.92 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 122.97 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 123.63 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.50 | 575.31 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.52 | 607.48 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 472.53 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 485.65 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 360.02 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 358.10 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 321.60 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 319.78 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.33 | 382.00 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.34 | 393.76 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 318.92 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 319.47 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 248.81 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 246.76 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 248.90 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.21 | 249.27 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2133.75 | 2560.50 | 0.167 | 0.201 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.09 | 0.01715 |
G NW APARTMENT | 2263.54 | 2716.24 | 0.177 | 0.213 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
OFFICE | 4871.06 | 5845.27 | 0.401 | 0.482 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 30.08 | 0.01715 |
G NE APARTMENT | 1762.05 | 2114.46 | 0.138 | 0.166 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.41 | 0.01715 |
G N1 APARTMENT | 1282.42 | 1538.90 | 0.101 | 0.121 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.34 | 0.01715 |
G N2 APARTMENT | 1271.87 | 1526.24 | 0.100 | 0.120 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.34 | 0.01715 |
G S1 APARTMENT | 1125.89 | 1351.07 | 0.088 | 0.106 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.59 | 0.01715 |
G S2 APARTMENT | 1131.88 | 1358.25 | 0.089 | 0.106 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.59 | 0.01715 |
M SW APARTMENT | 5266.65 | 6319.98 | 0.413 | 0.496 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.09 | 0.01715 |
M NW APARTMENT | 5561.51 | 6673.81 | 0.436 | 0.523 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
M SE APARTMENT | 4325.50 | 5190.60 | 0.339 | 0.407 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 31.83 | 0.01715 |
M NE APARTMENT | 4445.59 | 5334.71 | 0.349 | 0.418 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.41 | 0.01715 |
M N1 APARTMENT | 3296.12 | 3955.34 | 0.258 | 0.310 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.34 | 0.01715 |
M N2 APARTMENT | 3278.59 | 3934.31 | 0.257 | 0.308 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.34 | 0.01715 |
M S1 APARTMENT | 2944.45 | 3533.33 | 0.231 | 0.277 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.59 | 0.01715 |
M S2 APARTMENT | 2927.78 | 3513.33 | 0.230 | 0.275 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.59 | 0.01715 |
T SW APARTMENT | 3496.53 | 4195.84 | 0.274 | 0.329 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.40 | 0.01715 |
T NW APARTMENT | 3604.41 | 4325.30 | 0.283 | 0.339 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.09 | 0.01715 |
T SE APARTMENT | 2919.17 | 3503.01 | 0.229 | 0.275 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20 | 0.01715 |
T NE APARTMENT | 2924.12 | 3508.95 | 0.229 | 0.275 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 31.99 | 0.01715 |
T N1 APARTMENT | 2277.91 | 2733.49 | 0.179 | 0.214 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
T N2 APARTMENT | 2259.14 | 2710.97 | 0.177 | 0.213 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
T S1 APARTMENT | 2278.55 | 2734.26 | 0.179 | 0.214 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20 | 0.01715 |
T S2 APARTMENT | 2281.91 | 2738.30 | 0.179 | 0.215 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20 | 0.01715 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 746.52 | 895.83 | 0.022 | 0.027 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
G NW APARTMENT | 753.30 | 903.96 | 0.022 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
OFFICE | 1701.98 | 2042.38 | 0.047 | 0.056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 8.70 | 0.00699 |
G NE APARTMENT | 747.84 | 897.40 | 0.022 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
G N1 APARTMENT | 377.51 | 453.02 | 0.011 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
G N2 APARTMENT | 377.38 | 452.86 | 0.011 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
G S1 APARTMENT | 371.34 | 445.61 | 0.011 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
G S2 APARTMENT | 427.66 | 513.19 | 0.012 | 0.026 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M SW APARTMENT | 1634.48 | 1961.38 | 0.047 | 0.057 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M NW APARTMENT | 1657.94 | 1989.52 | 0.048 | 0.057 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M SE APARTMENT | 1619.29 | 1943.15 | 0.047 | 0.056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M NE APARTMENT | 1642.83 | 1971.40 | 0.047 | 0.057 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M N1 APARTMENT | 696.54 | 835.85 | 0.020 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M N2 APARTMENT | 696.13 | 835.36 | 0.020 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M S1 APARTMENT | 672.16 | 806.60 | 0.019 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
M S2 APARTMENT | 671.76 | 806.11 | 0.019 | 0.052 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T SW APARTMENT | 1363.87 | 1636.65 | 0.039 | 0.047 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T NW APARTMENT | 1376.17 | 1651.41 | 0.040 | 0.048 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T SE APARTMENT | 1356.06 | 1627.27 | 0.039 | 0.047 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T NE APARTMENT | 1368.38 | 1642.06 | 0.039 | 0.047 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T N1 APARTMENT | 874.57 | 1049.49 | 0.025 | 0.030 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T N2 APARTMENT | 874.35 | 1049.21 | 0.025 | 0.030 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T S1 APARTMENT | 860.42 | 1032.50 | 0.025 | 0.030 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
T S2 APARTMENT | 860.19 | 1032.23 | 0.025 | 0.030 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | 8.70 | 0.00699 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.20 | 0.20 | 0.03 | 0.03 |
SPLIT GNW | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT OFFICE | 0.48 | 0.48 | 0.06 | 0.06 |
SPLIT GNE | 0.17 | 0.17 | 0.03 | 0.03 |
SPLIT GN1 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GN2 | 0.12 | 0.12 | 0.03 | 0.03 |
SPLIT GS1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS2 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT MSW | 0.50 | 0.50 | 0.06 | 0.06 |
SPLIT MNW | 0.52 | 0.52 | 0.06 | 0.06 |
SPLIT MSE | 0.41 | 0.41 | 0.06 | 0.06 |
SPLIT MNE | 0.42 | 0.42 | 0.06 | 0.06 |
SPLIT MN1 | 0.31 | 0.31 | 0.05 | 0.05 |
SPLIT MN2 | 0.31 | 0.31 | 0.05 | 0.05 |
SPLIT MS1 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT MS2 | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TSW | 0.33 | 0.33 | 0.05 | 0.05 |
SPLIT TNW | 0.34 | 0.34 | 0.05 | 0.05 |
SPLIT TSE | 0.27 | 0.27 | 0.05 | 0.05 |
SPLIT TNE | 0.28 | 0.28 | 0.05 | 0.05 |
SPLIT TN1 | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT TN2 | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT TS1 | 0.21 | 0.21 | 0.03 | 0.03 |
SPLIT TS2 | 0.21 | 0.21 | 0.03 | 0.03 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 7290.00 | 4349.50 | 3393.50 |
G NW APARTMENT | 7077.75 | 5024.00 | 3702.50 |
OFFICE | 1656.00 | 180.75 | 11.75 |
G NE APARTMENT | 7044.25 | 4970.00 | 3620.50 |
G N1 APARTMENT | 6954.00 | 5611.50 | 4103.75 |
G N2 APARTMENT | 6951.00 | 5602.50 | 4091.00 |
G S1 APARTMENT | 7154.50 | 4458.75 | 3459.00 |
G S2 APARTMENT | 7171.00 | 4126.75 | 3157.50 |
M SW APARTMENT | 8109.50 | 1279.00 | 1086.50 |
M NW APARTMENT | 7728.25 | 1774.50 | 1352.25 |
M SE APARTMENT | 8119.25 | 1227.00 | 1029.25 |
M NE APARTMENT | 7705.00 | 1730.50 | 1311.00 |
M N1 APARTMENT | 7740.75 | 1467.00 | 1117.00 |
M N2 APARTMENT | 7741.50 | 1468.25 | 1117.75 |
M S1 APARTMENT | 8133.00 | 816.75 | 736.75 |
M S2 APARTMENT | 8132.75 | 815.00 | 734.75 |
T SW APARTMENT | 7844.75 | 2548.00 | 2045.25 |
T NW APARTMENT | 7610.00 | 2913.25 | 2191.25 |
T SE APARTMENT | 7849.50 | 2553.25 | 2043.00 |
T NE APARTMENT | 7613.50 | 3012.75 | 2271.25 |
T N1 APARTMENT | 7600.50 | 2732.00 | 2041.75 |
T N2 APARTMENT | 7597.50 | 2732.50 | 2041.75 |
T S1 APARTMENT | 7904.25 | 2173.25 | 1768.00 |
T S2 APARTMENT | 7905.25 | 2177.25 | 1771.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 8225.00 | 5737.50 | 4228.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
G NW APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
OFFICE | 0.00 | 48.75 | 0.00 | 0.00 |
G NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
G N1 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
G N2 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
G S1 APARTMENT | 0.00 | 6.25 | 0.00 | 6.25 |
G S2 APARTMENT | 0.00 | 10.50 | 0.00 | 10.50 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 0.00 | 5.25 | 0.00 | 5.25 |
M S2 APARTMENT | 0.00 | 5.75 | 0.00 | 5.75 |
T SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
T SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.00 | 64.25 | 2.00 | 15.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.370 | 0.178 | 0.000 | 0.106 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.178 | 0.000 | 0.103 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.521 | 0.211 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.178 | 0.000 | 0.103 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.107 | 0.000 | 0.102 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.107 | 0.000 | 0.102 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.107 | 0.000 | 0.106 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.107 | 0.000 | 0.106 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.256 | 0.000 | 0.137 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.256 | 0.000 | 0.134 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.256 | 0.000 | 0.137 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.256 | 0.000 | 0.134 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.155 | 0.000 | 0.134 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.155 | 0.000 | 0.134 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.155 | 0.000 | 0.137 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.155 | 0.000 | 0.137 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.339 | 0.000 | 0.182 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.339 | 0.000 | 0.178 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.339 | 0.000 | 0.182 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.339 | 0.000 | 0.178 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.204 | 0.000 | 0.178 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.204 | 0.000 | 0.178 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.204 | 0.000 | 0.182 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.204 | 0.000 | 0.182 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.508 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.376 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.377 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.376 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.379 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.378 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.344 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 295.79 | 0.00 | 01-JAN-00:15 | 27845.09 | 04-JAN-08:30 |
WaterSystems:Electricity | 295.79 | 0.00 | 01-JAN-00:15 | 27845.09 | 04-JAN-08:30 |
Water Heater:WaterSystems:Electricity | 295.79 | 0.00 | 01-JAN-00:15 | 27845.09 | 04-JAN-08:30 |
Fans:Electricity | 241.75 | 7665.70 | 01-JAN-00:15 | 7665.70 | 03-JAN-07:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
ElectricityPurchased:Plant | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
Cogeneration:ElectricityPurchased | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
ElectricityNet:Plant | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
Cogeneration:ElectricityNet | 1621.74 | 20778.32 | 23-JAN-03:45 | 88137.22 | 27-JUL-17:15 |
ExteriorLights:Electricity | 40.19 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.19 | 0.00 | 01-JAN-07:15 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 649.65 | 7665.70 | 08-JAN-06:15 | 39444.28 | 27-JUL-16:00 |
General:Fans:Electricity | 241.75 | 7665.70 | 01-JAN-00:15 | 7665.70 | 03-JAN-07:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 407.91 | 0.00 | 08-JAN-06:15 | 31778.58 | 27-JUL-16:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 1.75 | 0.00 | 01-JAN-00:15 | 23115.49 | 04-FEB-07:00 |
Gas:HVAC | 1.75 | 0.00 | 01-JAN-00:15 | 23115.49 | 04-FEB-07:00 |
Heating:Gas | 1.75 | 0.00 | 01-JAN-00:15 | 23115.49 | 04-FEB-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2598.07 | 1826.90 | 12-NOV-10:30 | 196207.09 | 20-SEP-14:15 |
EnergyTransfer:Building | 907.59 | 1826.90 | 12-NOV-10:30 | 72579.64 | 27-JUL-16:00 |
EnergyTransfer:Zone:G SW APARTMENT | 19.76 | 0.01 | 16-MAR-01:00 | 2559.22 | 30-SEP-15:15 |
Heating:EnergyTransfer | 12.73 | 0.00 | 02-JAN-10:45 | 12527.54 | 04-FEB-07:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.30 | 0.00 | 01-JAN-00:15 | 581.90 | 04-FEB-05:00 |
Cooling:EnergyTransfer | 894.86 | 120.85 | 06-FEB-06:15 | 72579.64 | 27-JUL-16:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 19.46 | 0.00 | 01-JAN-00:45 | 2559.22 | 30-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 16.39 | 0.01 | 21-MAR-04:00 | 2290.63 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 0.72 | 0.00 | 01-JAN-10:15 | 704.20 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 15.67 | 0.00 | 01-JAN-00:15 | 2290.63 | 29-JUL-16:30 |
EnergyTransfer:Zone:OFFICE | 38.45 | 0.12 | 27-DEC-00:30 | 5179.37 | 24-SEP-11:00 |
Heating:EnergyTransfer:Zone:OFFICE | 7.98 | 0.00 | 02-JAN-07:30 | 695.87 | 31-JUL-18:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 30.47 | 0.00 | 01-JAN-00:15 | 5179.37 | 24-SEP-11:00 |
EnergyTransfer:Zone:G NE APARTMENT | 16.20 | 0.01 | 13-FEB-20:15 | 1866.80 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 0.48 | 0.00 | 01-JAN-08:30 | 726.27 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 15.72 | 0.00 | 01-JAN-00:15 | 1866.80 | 29-JUL-16:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 11.34 | 0.01 | 01-NOV-05:30 | 1365.58 | 27-JUL-17:15 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.31 | 0.00 | 01-JAN-01:00 | 300.23 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 11.02 | 0.00 | 01-JAN-00:15 | 1365.58 | 27-JUL-17:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 11.34 | 0.02 | 16-MAR-14:15 | 1358.76 | 27-JUL-17:15 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.31 | 0.00 | 01-JAN-01:00 | 302.45 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 11.03 | 0.00 | 01-JAN-00:15 | 1358.76 | 27-JUL-17:15 |
EnergyTransfer:Zone:G S1 APARTMENT | 14.89 | 0.01 | 07-NOV-06:30 | 1581.80 | 30-SEP-14:00 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.06 | 0.00 | 01-JAN-00:15 | 156.26 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 14.83 | 0.00 | 04-JAN-03:45 | 1581.80 | 30-SEP-14:00 |
EnergyTransfer:Zone:G S2 APARTMENT | 15.83 | 0.03 | 14-JAN-20:00 | 1614.42 | 23-SEP-14:00 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 156.84 | 04-FEB-05:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 15.79 | 0.00 | 04-JAN-03:45 | 1614.42 | 23-SEP-14:00 |
EnergyTransfer:Zone:M SW APARTMENT | 73.51 | 0.13 | 21-FEB-08:00 | 6215.59 | 25-OCT-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.02 | 0.00 | 01-JAN-00:15 | 267.73 | 06-FEB-06:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 73.50 | 0.00 | 05-JAN-06:15 | 6215.59 | 25-OCT-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 61.12 | 0.03 | 22-MAR-03:00 | 5688.79 | 29-MAY-16:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.17 | 0.00 | 01-JAN-00:15 | 414.49 | 05-FEB-14:30 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 60.94 | 0.00 | 05-JAN-06:15 | 5688.79 | 29-MAY-16:30 |
EnergyTransfer:Zone:M SE APARTMENT | 73.85 | 0.98 | 26-DEC-07:00 | 5669.32 | 25-OCT-12:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 201.14 | 01-FEB-07:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 73.84 | 0.00 | 05-JAN-06:15 | 5669.32 | 25-OCT-12:30 |
EnergyTransfer:Zone:M NE APARTMENT | 61.28 | 0.03 | 22-JAN-21:00 | 4745.99 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.08 | 0.00 | 01-JAN-00:15 | 513.10 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 61.20 | 0.00 | 05-JAN-06:15 | 4745.99 | 29-JUL-16:15 |
EnergyTransfer:Zone:M N1 APARTMENT | 49.51 | 0.35 | 17-MAR-09:30 | 3505.56 | 29-MAY-17:15 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 189.27 | 05-FEB-14:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 49.50 | 0.00 | 10-JAN-10:30 | 3505.56 | 29-MAY-17:15 |
EnergyTransfer:Zone:M N2 APARTMENT | 49.53 | 0.14 | 15-DEC-17:45 | 3491.60 | 29-MAY-17:15 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 187.63 | 05-FEB-14:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 49.52 | 0.00 | 10-JAN-10:30 | 3491.60 | 29-MAY-17:15 |
EnergyTransfer:Zone:M S1 APARTMENT | 62.53 | 45.49 | 06-FEB-06:15 | 4739.65 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 62.53 | 45.49 | 06-FEB-06:15 | 4739.65 | 04-DEC-14:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 62.54 | 46.84 | 06-FEB-06:15 | 4736.36 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 62.54 | 46.84 | 06-FEB-06:15 | 4736.36 | 04-DEC-14:30 |
EnergyTransfer:Zone:T SW APARTMENT | 39.49 | 0.20 | 07-FEB-02:15 | 4037.88 | 30-SEP-14:30 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 0.40 | 0.00 | 01-JAN-00:15 | 1388.32 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 39.09 | 0.00 | 01-JAN-06:00 | 4037.88 | 30-SEP-14:30 |
EnergyTransfer:Zone:T NW APARTMENT | 34.15 | 0.56 | 07-NOV-06:30 | 3778.16 | 29-MAY-16:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 0.70 | 0.00 | 01-JAN-00:15 | 1547.36 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 33.44 | 0.00 | 01-JAN-05:45 | 3778.16 | 29-MAY-16:30 |
EnergyTransfer:Zone:T SE APARTMENT | 39.38 | 0.04 | 22-JAN-21:30 | 3650.92 | 25-OCT-12:45 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 0.28 | 0.00 | 01-JAN-00:15 | 1412.50 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 39.10 | 0.00 | 01-JAN-06:00 | 3650.92 | 25-OCT-12:45 |
EnergyTransfer:Zone:T NE APARTMENT | 33.85 | 0.08 | 24-FEB-02:15 | 3214.28 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 1586.24 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 33.37 | 0.00 | 01-JAN-05:45 | 3214.28 | 29-JUL-16:15 |
EnergyTransfer:Zone:T N1 APARTMENT | 27.72 | 0.02 | 22-FEB-00:30 | 2563.00 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 844.57 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 27.58 | 0.00 | 01-JAN-06:15 | 2563.00 | 29-JUL-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 27.73 | 0.03 | 28-DEC-04:15 | 2554.26 | 29-JUL-16:15 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.14 | 0.00 | 01-JAN-00:15 | 849.68 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 27.59 | 0.00 | 01-JAN-06:15 | 2554.26 | 29-JUL-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 33.59 | 0.01 | 02-FEB-20:15 | 3105.17 | 25-OCT-13:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 667.95 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 33.55 | 0.00 | 01-JAN-06:15 | 3105.17 | 25-OCT-13:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 33.60 | 0.21 | 23-FEB-22:00 | 3114.97 | 25-OCT-13:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.04 | 0.00 | 01-JAN-00:15 | 670.41 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 33.56 | 0.00 | 01-JAN-06:15 | 3114.97 | 25-OCT-13:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1690.48 | 0.00 | 08-JAN-06:15 | 125251.38 | 20-SEP-14:00 |
HeatingCoils:EnergyTransfer | 1.40 | 0.00 | 01-JAN-00:15 | 18492.39 | 04-FEB-07:00 |
CoolingCoils:EnergyTransfer | 1689.08 | 0.00 | 08-JAN-06:15 | 125251.38 | 20-SEP-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.297 | -19.462 | 0.000 | 0.000 | 3.557 | 1.087 | 12.213 | 16.352 | 0.000 | 1.072 | 0.000 | 0.000 | -2.300 | 0.000 | -1.286 | -11.530 |
G NW APARTMENT | 0.721 | -15.671 | 0.000 | 0.000 | 3.571 | 1.087 | 12.213 | 11.315 | 0.000 | 1.066 | 0.000 | 0.000 | -2.263 | 0.000 | -1.195 | -10.844 |
OFFICE | 7.978 | -30.470 | 0.000 | 0.000 | 0.517 | 26.452 | 9.482 | 15.616 | 0.000 | 0.544 | 0.000 | 0.000 | -3.224 | 0.000 | -1.255 | -25.639 |
G NE APARTMENT | 0.481 | -15.719 | 0.000 | 0.000 | 3.578 | 1.087 | 12.213 | 11.389 | 0.000 | 1.066 | 0.000 | 0.000 | -2.126 | 0.000 | -1.183 | -10.786 |
G N1 APARTMENT | 0.313 | -11.024 | 0.000 | 0.000 | 3.579 | 1.087 | 12.213 | 5.233 | 0.000 | 0.694 | 0.000 | 0.000 | -1.313 | 0.000 | -0.879 | -9.903 |
G N2 APARTMENT | 0.310 | -11.030 | 0.000 | 0.000 | 3.579 | 1.087 | 12.213 | 5.232 | 0.000 | 0.694 | 0.000 | 0.000 | -1.311 | 0.000 | -0.878 | -9.895 |
G S1 APARTMENT | 0.060 | -14.828 | 0.000 | 0.000 | 3.558 | 1.087 | 12.213 | 10.307 | 0.000 | 0.698 | 0.000 | 0.000 | -1.356 | 0.000 | -0.993 | -10.745 |
G S2 APARTMENT | 0.045 | -15.789 | 0.000 | 0.000 | 3.556 | 1.087 | 12.213 | 10.282 | 0.000 | 0.698 | 0.000 | 0.000 | -1.375 | 0.000 | -0.999 | -9.717 |
M SW APARTMENT | 0.017 | -73.496 | 0.000 | 0.000 | 3.522 | 1.087 | 12.213 | 15.676 | 0.000 | 1.513 | 44.199 | 0.000 | -2.889 | 0.000 | -1.842 | 0.000 |
M NW APARTMENT | 0.174 | -60.942 | 0.000 | 0.000 | 3.528 | 1.087 | 12.213 | 10.686 | 0.000 | 1.504 | 36.501 | 0.000 | -2.931 | 0.000 | -1.819 | 0.000 |
M SE APARTMENT | 0.006 | -73.838 | 0.000 | 0.000 | 3.523 | 1.087 | 12.213 | 15.771 | 0.000 | 1.514 | 44.372 | 0.000 | -2.806 | 0.000 | -1.841 | 0.000 |
M NE APARTMENT | 0.078 | -61.197 | 0.000 | 0.000 | 3.530 | 1.087 | 12.213 | 10.710 | 0.000 | 1.504 | 36.672 | 0.000 | -2.776 | 0.000 | -1.820 | 0.000 |
M N1 APARTMENT | 0.011 | -49.504 | 0.000 | 0.000 | 3.524 | 1.087 | 12.213 | 4.805 | 0.000 | 0.971 | 30.075 | 0.000 | -1.791 | 0.000 | -1.390 | 0.000 |
M N2 APARTMENT | 0.010 | -49.520 | 0.000 | 0.000 | 3.524 | 1.087 | 12.213 | 4.804 | 0.000 | 0.971 | 30.091 | 0.000 | -1.791 | 0.000 | -1.390 | 0.000 |
M S1 APARTMENT | 0.000 | -62.530 | 0.000 | 0.000 | 3.519 | 1.087 | 12.213 | 9.858 | 0.000 | 0.980 | 37.991 | 0.000 | -1.716 | 0.000 | -1.403 | 0.000 |
M S2 APARTMENT | 0.000 | -62.543 | 0.000 | 0.000 | 3.519 | 1.087 | 12.213 | 9.858 | 0.000 | 0.980 | 38.005 | 0.000 | -1.716 | 0.000 | -1.402 | 0.000 |
T SW APARTMENT | 0.404 | -39.085 | 0.000 | 0.000 | 3.539 | 1.087 | 12.213 | 15.149 | 0.000 | 2.043 | 9.661 | 0.000 | -2.746 | 0.000 | -2.265 | -0.001 |
T NW APARTMENT | 0.704 | -33.442 | 0.000 | 0.000 | 3.546 | 1.087 | 12.213 | 10.258 | 0.000 | 2.028 | 8.582 | 0.000 | -2.762 | 0.000 | -2.214 | -0.000 |
T SE APARTMENT | 0.277 | -39.103 | 0.000 | 0.000 | 3.542 | 1.087 | 12.213 | 15.229 | 0.000 | 2.043 | 9.640 | 0.000 | -2.663 | 0.000 | -2.265 | -0.000 |
T NE APARTMENT | 0.483 | -33.368 | 0.000 | 0.000 | 3.550 | 1.087 | 12.213 | 10.285 | 0.000 | 2.028 | 8.563 | 0.000 | -2.623 | 0.000 | -2.217 | -0.000 |
T N1 APARTMENT | 0.141 | -27.580 | 0.000 | 0.000 | 3.543 | 1.087 | 12.213 | 4.619 | 0.000 | 1.331 | 7.976 | 0.000 | -1.668 | 0.000 | -1.662 | -0.000 |
T N2 APARTMENT | 0.139 | -27.589 | 0.000 | 0.000 | 3.543 | 1.087 | 12.213 | 4.617 | 0.000 | 1.331 | 7.987 | 0.000 | -1.666 | 0.000 | -1.662 | -0.000 |
T S1 APARTMENT | 0.041 | -33.550 | 0.000 | 0.000 | 3.534 | 1.087 | 12.213 | 9.550 | 0.000 | 1.346 | 9.145 | 0.000 | -1.657 | 0.000 | -1.708 | -0.000 |
T S2 APARTMENT | 0.042 | -33.559 | 0.000 | 0.000 | 3.534 | 1.087 | 12.213 | 9.549 | 0.000 | 1.346 | 9.153 | 0.000 | -1.656 | 0.000 | -1.708 | -0.000 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.267 | 0.000 | 0.082 | 0.000 | 0.000 | -0.306 | 0.000 | -0.432 | -14.193 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 1.025 | 0.000 | 2.204 | 0.000 | 0.000 | -0.592 | 0.000 | -4.499 | -19.198 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.290 | 0.000 | 0.082 | 0.000 | 0.000 | -0.330 | 0.000 | -0.347 | -14.277 |
Total Facility | 12.731 | -894.839 | 0.000 | 0.000 | 82.016 | 95.189 | 296.854 | 248.731 | 0.000 | 32.335 | 368.614 | 0.000 | -52.351 | 0.000 | -42.553 | -146.728 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 30-SEP-15:15 | 0.00 | -2558.98 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2420.96 | 0.00 | 97.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -524.99 |
G NW APARTMENT | 29-JUL-16:23 | 0.00 | -2290.73 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1829.16 | 0.00 | 142.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -419.00 |
OFFICE | 02-APR-06:02 | 0.00 | -7115.52 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 6972.15 | 0.00 | -524.57 | 0.00 | -42.52 | 0.00 |
G NE APARTMENT | 29-JUL-16:04 | 0.00 | -1868.57 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1097.09 | 0.00 | 146.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -112.98 |
G N1 APARTMENT | 27-JUL-17:06 | 0.00 | -1367.76 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 594.23 | 0.00 | 121.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -166.04 |
G N2 APARTMENT | 27-JUL-17:06 | 0.00 | -1360.92 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 594.39 | 0.00 | 121.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -173.03 |
G S1 APARTMENT | 30-SEP-14:00 | 0.00 | -1581.89 | 0.00 | 0.00 | 40.10 | 12.97 | 382.60 | 1495.48 | 0.00 | 76.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -426.03 |
G S2 APARTMENT | 23-SEP-14:00 | 0.00 | -1614.11 | 0.00 | 0.00 | 40.23 | 12.97 | 382.60 | 1248.81 | 0.00 | 72.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -143.01 |
M SW APARTMENT | 25-OCT-15:15 | 0.00 | -6215.19 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2408.61 | 0.00 | 115.84 | 3125.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 29-MAY-16:20 | 0.00 | -5689.28 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1893.32 | 0.00 | 381.89 | 2675.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 25-OCT-12:30 | 0.00 | -5669.24 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2197.51 | 0.00 | 156.98 | 2872.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 29-JUL-16:04 | 0.00 | -4751.93 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1086.75 | 0.00 | 209.75 | 2717.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 29-MAY-17:08 | 0.00 | -3510.03 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 601.23 | 0.00 | 210.30 | 1880.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 29-MAY-17:08 | 0.00 | -3496.07 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 601.37 | 0.00 | 210.30 | 1866.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 04-DEC-14:30 | 0.00 | -4739.26 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1888.89 | 0.00 | 47.01 | 2367.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 04-DEC-14:30 | 0.00 | -4735.97 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1888.90 | 0.00 | 47.01 | 2363.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 30-SEP-14:30 | 0.00 | -4037.65 | 0.00 | 0.00 | 40.76 | 22.70 | 400.26 | 2536.87 | 0.00 | 210.74 | 826.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 29-MAY-16:05 | 0.00 | -3780.69 | 0.00 | 0.00 | 84.78 | 64.86 | 588.62 | 1844.79 | 0.00 | 510.35 | 687.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 25-OCT-12:45 | 0.00 | -3650.99 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2055.60 | 0.00 | 217.14 | 936.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 29-JUL-16:04 | 0.00 | -3217.92 | 0.00 | 0.00 | 84.77 | 64.86 | 588.62 | 1040.70 | 0.00 | 276.42 | 1162.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-JUL-16:04 | 0.00 | -2565.79 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 661.26 | 0.00 | 166.73 | 999.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUL-16:04 | 0.00 | -2557.06 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 661.44 | 0.00 | 166.73 | 990.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 25-OCT-13:00 | 0.00 | -3105.13 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1743.68 | 0.00 | 137.57 | 781.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 25-OCT-13:00 | 0.00 | -3114.93 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 1743.44 | 0.00 | 137.57 | 791.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUL-16:00 | 0.00 | -72583.14 | 0.00 | 0.00 | 1192.08 | 4512.09 | 11708.34 | 25294.20 | 0.00 | 6951.98 | 22924.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 04-FEB-05:00 | 581.85 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 226.50 | 0.00 | -805.32 | 0.00 | -435.83 | 0.00 |
G NW APARTMENT | 04-FEB-05:00 | 704.14 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 114.29 | 0.00 | -815.40 | 0.00 | -435.83 | 0.00 |
OFFICE | 18-OCT-06:06 | 782.28 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 19.97 | 0.00 | 0.00 | -76.82 | 0.00 | 0.00 | -1435.90 |
G NE APARTMENT | 04-FEB-05:00 | 726.22 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 90.00 | 0.00 | -813.18 | 0.00 | -435.83 | 0.00 |
G N1 APARTMENT | 16-MAR-07:02 | 684.07 | 0.00 | 0.00 | 0.00 | 74.03 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.78 | 0.00 | -126.54 | -666.72 |
G N2 APARTMENT | 25-JAN-08:13 | 343.72 | 0.00 | 0.00 | 0.00 | 73.97 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.98 | 0.00 | -123.66 | -444.00 |
G S1 APARTMENT | 04-FEB-05:00 | 156.25 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 157.54 | 0.00 | -483.71 | 0.00 | -262.88 | 0.00 |
G S2 APARTMENT | 04-FEB-05:00 | 156.82 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 157.03 | 0.00 | -483.77 | 0.00 | -262.88 | 0.00 |
M SW APARTMENT | 06-FEB-06:15 | 267.76 | 0.00 | 0.00 | 0.00 | 162.99 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 49.08 | 0.00 | -361.89 | 0.00 | -481.19 | 0.00 |
M NW APARTMENT | 05-FEB-14:30 | 414.52 | 0.00 | 0.00 | 0.00 | 40.91 | 12.97 | 382.60 | 663.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.87 | -1233.03 |
M SE APARTMENT | 01-FEB-07:00 | 201.17 | 0.00 | 0.00 | 0.00 | 163.09 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -280.84 | 0.00 | -432.30 | -14.38 |
M NE APARTMENT | 04-FEB-07:00 | 513.09 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 421.17 | 0.00 | -913.85 | 0.00 | -573.34 | 0.00 |
M N1 APARTMENT | 05-FEB-14:00 | 189.31 | 0.00 | 0.00 | 0.00 | 41.46 | 12.97 | 388.49 | 223.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -197.96 | -658.15 |
M N2 APARTMENT | 05-FEB-14:00 | 187.67 | 0.00 | 0.00 | 0.00 | 41.45 | 12.97 | 388.49 | 223.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -198.11 | -656.23 |
M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 04-FEB-07:00 | 1388.29 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -840.33 | 0.00 | -760.14 | -340.74 |
T NW APARTMENT | 04-FEB-07:00 | 1547.33 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.30 | 0.00 | -760.14 | -481.82 |
T SE APARTMENT | 04-FEB-07:00 | 1412.47 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.95 | 0.00 | -760.14 | -366.30 |
T NE APARTMENT | 04-FEB-07:00 | 1586.22 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -856.19 | 0.00 | -760.14 | -522.81 |
T N1 APARTMENT | 04-FEB-07:00 | 844.56 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.13 | 0.00 | -458.51 | -413.84 |
T N2 APARTMENT | 04-FEB-07:00 | 849.67 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -524.94 | 0.00 | -458.51 | -419.14 |
T S1 APARTMENT | 04-FEB-07:00 | 667.93 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.00 | 0.00 | -458.51 | -256.34 |
T S2 APARTMENT | 04-FEB-07:00 | 670.40 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -505.90 | 0.00 | -458.51 | -258.91 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-07:00 | 8982.20 | 0.00 | 0.00 | 0.00 | 4338.98 | 2847.50 | 7834.13 | 0.00 | 0.00 | 0.00 | 6102.30 | 0.00 | -17178.10 | 0.00 | -12927.01 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Sec1.1A-General InformationData | |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 2.00 |
Number of hours cooling loads not met | 15.50 |
Number of hours not met | 17.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1.75 | 23115.49 | 0.00 | 0.00 |
Space Cooling | 407.91 | 29475.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 241.75 | 7665.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 295.79 | 19384.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1621.74 | 1.75 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1621.74 |
Natural Gas | 0.00 | 1.75 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1623.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 130.13 |
Fans-Interior | 77.12 |
Service Water Heating | 94.36 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.82 |
Subtotal | 517.37 |
Natural Gas [MJ/m2] | |
Space Heating | 0.56 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 0.56 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.30 |
Space Heating | 0.11 |
Space Cooling | 25.13 |
Fans-Interior | 14.89 |
Service Water Heating | 18.22 |
Receptacle Equipment | 31.89 |
Miscellaneous | 2.48 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.200780 |
G NW APARTMENT DIRECT AIR | 0.212982 |
OFFICE DIRECT AIR | 0.481515 |
G NE APARTMENT DIRECT AIR | 0.165812 |
G N1 APARTMENT DIRECT AIR | 0.120661 |
G N2 APARTMENT DIRECT AIR | 0.119669 |
G S1 APARTMENT DIRECT AIR | 0.105933 |
G S2 APARTMENT DIRECT AIR | 0.106496 |
M SW APARTMENT DIRECT AIR | 0.495599 |
M NW APARTMENT DIRECT AIR | 0.523313 |
M SE APARTMENT DIRECT AIR | 0.407056 |
M NE APARTMENT DIRECT AIR | 0.418358 |
M N1 APARTMENT DIRECT AIR | 0.310135 |
M N2 APARTMENT DIRECT AIR | 0.308485 |
M S1 APARTMENT DIRECT AIR | 0.277044 |
M S2 APARTMENT DIRECT AIR | 0.275475 |
T SW APARTMENT DIRECT AIR | 0.329073 |
T NW APARTMENT DIRECT AIR | 0.339205 |
T SE APARTMENT DIRECT AIR | 0.274735 |
T NE APARTMENT DIRECT AIR | 0.275204 |
T N1 APARTMENT DIRECT AIR | 0.214336 |
T N2 APARTMENT DIRECT AIR | 0.212570 |
T S1 APARTMENT DIRECT AIR | 0.214417 |
T S2 APARTMENT DIRECT AIR | 0.214734 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.200780 |
SPLIT GNW MAIN BRANCH | 0.212982 |
SPLIT OFFICE MAIN BRANCH | 0.481515 |
SPLIT GNE MAIN BRANCH | 0.165812 |
SPLIT GN1 MAIN BRANCH | 0.120661 |
SPLIT GN2 MAIN BRANCH | 0.119669 |
SPLIT GS1 MAIN BRANCH | 0.105933 |
SPLIT GS2 MAIN BRANCH | 0.106496 |
SPLIT MSW MAIN BRANCH | 0.495599 |
SPLIT MNW MAIN BRANCH | 0.523313 |
SPLIT MSE MAIN BRANCH | 0.407056 |
SPLIT MNE MAIN BRANCH | 0.418358 |
SPLIT MN1 MAIN BRANCH | 0.310135 |
SPLIT MN2 MAIN BRANCH | 0.308485 |
SPLIT MS1 MAIN BRANCH | 0.277044 |
SPLIT MS2 MAIN BRANCH | 0.275475 |
SPLIT TSW MAIN BRANCH | 0.329073 |
SPLIT TNW MAIN BRANCH | 0.339205 |
SPLIT TSE MAIN BRANCH | 0.274735 |
SPLIT TNE MAIN BRANCH | 0.275204 |
SPLIT TN1 MAIN BRANCH | 0.214336 |
SPLIT TN2 MAIN BRANCH | 0.212570 |
SPLIT TS1 MAIN BRANCH | 0.214417 |
SPLIT TS2 MAIN BRANCH | 0.214734 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.200780 |
SPLIT GNW | 0.212982 |
SPLIT OFFICE | 0.481515 |
SPLIT GNE | 0.165812 |
SPLIT GN1 | 0.120661 |
SPLIT GN2 | 0.119669 |
SPLIT GS1 | 0.105933 |
SPLIT GS2 | 0.106496 |
SPLIT MSW | 0.495599 |
SPLIT MNW | 0.523313 |
SPLIT MSE | 0.407056 |
SPLIT MNE | 0.418358 |
SPLIT MN1 | 0.310135 |
SPLIT MN2 | 0.308485 |
SPLIT MS1 | 0.277044 |
SPLIT MS2 | 0.275475 |
SPLIT TSW | 0.329073 |
SPLIT TNW | 0.339205 |
SPLIT TSE | 0.274735 |
SPLIT TNE | 0.275204 |
SPLIT TN1 | 0.214336 |
SPLIT TN2 | 0.212570 |
SPLIT TS1 | 0.214417 |
SPLIT TS2 | 0.214734 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.200780 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.212982 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.481515 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.165812 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.120661 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.119669 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.105933 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.106496 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.495599 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.523313 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.407056 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.418358 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.310135 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.308485 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.277044 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.275475 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.329073 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.339205 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.274735 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.275204 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.214336 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.212570 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.214417 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.214734 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.200780 | 4366.02 | 0.710877 |
SPLIT GNW COOLING COIL | 0.212982 | 4525.00 | 0.717455 |
SPLIT OFFICE COOLING COIL | 0.481515 | 8767.51 | 0.765245 |
SPLIT GNE COOLING COIL | 0.165812 | 3726.37 | 0.701809 |
SPLIT GN1 COOLING COIL | 0.120661 | 2890.13 | 0.685087 |
SPLIT GN2 COOLING COIL | 0.119669 | 2873.37 | 0.684467 |
SPLIT GS1 COOLING COIL | 0.105933 | 2630.57 | 0.676083 |
SPLIT GS2 COOLING COIL | 0.106496 | 2644.56 | 0.676083 |
SPLIT MSW COOLING COIL | 0.495599 | 10464.11 | 0.719243 |
SPLIT MNW COOLING COIL | 0.523313 | 10885.24 | 0.723587 |
SPLIT MSE COOLING COIL | 0.407056 | 8968.12 | 0.707239 |
SPLIT MNE COOLING COIL | 0.418358 | 9110.09 | 0.710484 |
SPLIT MN1 COOLING COIL | 0.310135 | 7054.75 | 0.698547 |
SPLIT MN2 COOLING COIL | 0.308485 | 7027.23 | 0.698166 |
SPLIT MS1 COOLING COIL | 0.277044 | 6508.80 | 0.690047 |
SPLIT MS2 COOLING COIL | 0.275475 | 6482.04 | 0.689644 |
SPLIT TSW COOLING COIL | 0.329073 | 6707.07 | 0.729601 |
SPLIT TNW COOLING COIL | 0.339205 | 6856.01 | 0.732108 |
SPLIT TSE COOLING COIL | 0.274735 | 5873.47 | 0.715676 |
SPLIT TNE COOLING COIL | 0.275204 | 5799.83 | 0.719782 |
SPLIT TN1 COOLING COIL | 0.214336 | 4585.70 | 0.715460 |
SPLIT TN2 COOLING COIL | 0.212570 | 4556.60 | 0.714918 |
SPLIT TS1 COOLING COIL | 0.214417 | 4663.32 | 0.710831 |
SPLIT TS2 COOLING COIL | 0.214734 | 4668.26 | 0.710948 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.200780 | 0.200780 | 0.200780 | 0.200780 | 1342.62 | 4366.02 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.212982 | 0.212982 | 0.212982 | 0.212982 | 1298.56 | 4525.00 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.481515 | 0.481515 | 0.481515 | 0.481515 | 2545.96 | 8767.51 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.165812 | 0.165812 | 0.165812 | 0.165812 | 1295.43 | 3726.37 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.120661 | 0.120661 | 0.120661 | 0.120661 | 1295.43 | 2890.13 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.119669 | 0.119669 | 0.119669 | 0.119669 | 1295.43 | 2873.37 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.105933 | 0.105933 | 0.105933 | 0.105933 | 1295.43 | 2630.57 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.106496 | 0.106496 | 0.106496 | 0.106496 | 1295.43 | 2644.56 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.495599 | 0.495599 | 0.495599 | 0.495599 | 2748.33 | 10464.11 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.523313 | 0.523313 | 0.523313 | 0.523313 | 2776.06 | 10885.24 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.407056 | 0.407056 | 0.407056 | 0.407056 | 2730.36 | 8968.12 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.418358 | 0.418358 | 0.418358 | 0.418358 | 2758.20 | 9110.09 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.310135 | 0.310135 | 0.310135 | 0.310135 | 2590.86 | 7054.75 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.308485 | 0.308485 | 0.308485 | 0.308485 | 2590.86 | 7027.23 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.277044 | 0.277044 | 0.277044 | 0.277044 | 2590.86 | 6508.80 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.275475 | 0.275475 | 0.275475 | 0.275475 | 2590.86 | 6482.04 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.329073 | 0.329073 | 0.329073 | 0.329073 | 2020.56 | 6707.07 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.339205 | 0.339205 | 0.339205 | 0.339205 | 2035.11 | 6856.01 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.274735 | 0.274735 | 0.274735 | 0.274735 | 2011.32 | 5873.47 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.275204 | 0.275204 | 0.275204 | 0.275204 | 2025.89 | 5799.83 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.214336 | 0.214336 | 0.214336 | 0.214336 | 1441.97 | 4585.70 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.212570 | 0.212570 | 0.212570 | 0.212570 | 1441.69 | 4556.60 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.214417 | 0.214417 | 0.214417 | 0.214417 | 1425.23 | 4663.32 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.214734 | 0.214734 | 0.214734 | 0.214734 | 1424.96 | 4668.26 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.200780 |
SPLIT GNW SUPPLY FAN | 0.212982 |
SPLIT OFFICE SUPPLY FAN | 0.481515 |
SPLIT GNE SUPPLY FAN | 0.165812 |
SPLIT GN1 SUPPLY FAN | 0.120661 |
SPLIT GN2 SUPPLY FAN | 0.119669 |
SPLIT GS1 SUPPLY FAN | 0.105933 |
SPLIT GS2 SUPPLY FAN | 0.106496 |
SPLIT MSW SUPPLY FAN | 0.495599 |
SPLIT MNW SUPPLY FAN | 0.523313 |
SPLIT MSE SUPPLY FAN | 0.407056 |
SPLIT MNE SUPPLY FAN | 0.418358 |
SPLIT MN1 SUPPLY FAN | 0.310135 |
SPLIT MN2 SUPPLY FAN | 0.308485 |
SPLIT MS1 SUPPLY FAN | 0.277044 |
SPLIT MS2 SUPPLY FAN | 0.275475 |
SPLIT TSW SUPPLY FAN | 0.329073 |
SPLIT TNW SUPPLY FAN | 0.339205 |
SPLIT TSE SUPPLY FAN | 0.274735 |
SPLIT TNE SUPPLY FAN | 0.275204 |
SPLIT TN1 SUPPLY FAN | 0.214336 |
SPLIT TN2 SUPPLY FAN | 0.212570 |
SPLIT TS1 SUPPLY FAN | 0.214417 |
SPLIT TS2 SUPPLY FAN | 0.214734 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1342.62 |
SPLIT GNW HEATING COIL | 1298.56 |
SPLIT OFFICE HEATING COIL | 2545.96 |
SPLIT GNE HEATING COIL | 1295.43 |
SPLIT GN1 HEATING COIL | 1295.43 |
SPLIT GN2 HEATING COIL | 1295.43 |
SPLIT GS1 HEATING COIL | 1295.43 |
SPLIT GS2 HEATING COIL | 1295.43 |
SPLIT MSW HEATING COIL | 2748.33 |
SPLIT MNW HEATING COIL | 2776.06 |
SPLIT MSE HEATING COIL | 2730.36 |
SPLIT MNE HEATING COIL | 2758.20 |
SPLIT MN1 HEATING COIL | 2590.86 |
SPLIT MN2 HEATING COIL | 2590.86 |
SPLIT MS1 HEATING COIL | 2590.86 |
SPLIT MS2 HEATING COIL | 2590.86 |
SPLIT TSW HEATING COIL | 2020.56 |
SPLIT TNW HEATING COIL | 2035.11 |
SPLIT TSE HEATING COIL | 2011.32 |
SPLIT TNE HEATING COIL | 2025.89 |
SPLIT TN1 HEATING COIL | 1441.97 |
SPLIT TN2 HEATING COIL | 1441.69 |
SPLIT TS1 HEATING COIL | 1425.23 |
SPLIT TS2 HEATING COIL | 1424.96 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.90 | 19.42 |
February | 24.01 | 20.87 |
March | 24.10 | 21.57 |
April | 24.37 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.26 | 23.59 |
December | 23.97 | 20.30 |
Annual Sum or Average | 24.25 | 24.51 |
Minimum of Months | 23.90 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 19.42 |
February | 23.84 | 20.87 |
March | 23.98 | 21.57 |
April | 24.37 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.20 | 23.59 |
December | 23.73 | 20.30 |
Annual Sum or Average | 24.18 | 24.51 |
Minimum of Months | 23.59 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.18 | 19.42 |
February | 25.23 | 20.87 |
March | 25.46 | 21.57 |
April | 26.05 | 24.11 |
May | 26.36 | 26.41 |
June | 27.19 | 27.68 |
July | 27.35 | 28.13 |
August | 27.13 | 27.97 |
September | 27.45 | 27.49 |
October | 26.63 | 26.35 |
November | 26.00 | 23.59 |
December | 25.32 | 20.30 |
Annual Sum or Average | 26.28 | 24.51 |
Minimum of Months | 25.18 | 19.42 |
Maximum of Months | 27.45 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 19.42 |
February | 23.80 | 20.87 |
March | 23.97 | 21.57 |
April | 24.36 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.19 | 23.59 |
December | 23.64 | 20.30 |
Annual Sum or Average | 24.16 | 24.51 |
Minimum of Months | 23.53 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.46 | 19.42 |
February | 23.76 | 20.87 |
March | 23.89 | 21.57 |
April | 24.34 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.18 | 23.59 |
December | 23.62 | 20.30 |
Annual Sum or Average | 24.14 | 24.51 |
Minimum of Months | 23.46 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.45 | 19.42 |
February | 23.75 | 20.87 |
March | 23.89 | 21.57 |
April | 24.34 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.18 | 23.59 |
December | 23.61 | 20.30 |
Annual Sum or Average | 24.14 | 24.51 |
Minimum of Months | 23.45 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.91 | 19.42 |
February | 24.00 | 20.87 |
March | 24.08 | 21.57 |
April | 24.35 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.27 | 23.59 |
December | 23.97 | 20.30 |
Annual Sum or Average | 24.25 | 24.51 |
Minimum of Months | 23.91 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.93 | 19.42 |
February | 24.02 | 20.87 |
March | 24.10 | 21.57 |
April | 24.36 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.41 | 27.49 |
October | 24.40 | 26.35 |
November | 24.28 | 23.59 |
December | 23.98 | 20.30 |
Annual Sum or Average | 24.26 | 24.51 |
Minimum of Months | 23.93 | 19.42 |
Maximum of Months | 24.41 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.36 | 19.42 |
February | 24.32 | 20.87 |
March | 24.35 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.38 | 23.59 |
December | 24.34 | 20.30 |
Annual Sum or Average | 24.38 | 24.51 |
Minimum of Months | 24.32 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.28 | 19.42 |
February | 24.24 | 20.87 |
March | 24.29 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.36 | 23.59 |
December | 24.26 | 20.30 |
Annual Sum or Average | 24.35 | 24.51 |
Minimum of Months | 24.24 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.35 | 19.42 |
February | 24.32 | 20.87 |
March | 24.35 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.38 | 23.59 |
December | 24.33 | 20.30 |
Annual Sum or Average | 24.38 | 24.51 |
Minimum of Months | 24.32 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.27 | 19.42 |
February | 24.22 | 20.87 |
March | 24.31 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.36 | 23.59 |
December | 24.24 | 20.30 |
Annual Sum or Average | 24.35 | 24.51 |
Minimum of Months | 24.22 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.32 | 19.42 |
February | 24.28 | 20.87 |
March | 24.33 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.38 | 23.59 |
December | 24.32 | 20.30 |
Annual Sum or Average | 24.37 | 24.51 |
Minimum of Months | 24.28 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.32 | 19.42 |
February | 24.28 | 20.87 |
March | 24.33 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.38 | 23.59 |
December | 24.32 | 20.30 |
Annual Sum or Average | 24.37 | 24.51 |
Minimum of Months | 24.28 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.39 | 19.42 |
February | 24.36 | 20.87 |
March | 24.37 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.39 | 23.59 |
December | 24.38 | 20.30 |
Annual Sum or Average | 24.39 | 24.51 |
Minimum of Months | 24.36 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.39 | 19.42 |
February | 24.36 | 20.87 |
March | 24.37 | 21.57 |
April | 24.40 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.39 | 23.59 |
December | 24.38 | 20.30 |
Annual Sum or Average | 24.39 | 24.51 |
Minimum of Months | 24.36 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.15 | 19.42 |
February | 24.17 | 20.87 |
March | 24.20 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.31 | 23.59 |
December | 24.17 | 20.30 |
Annual Sum or Average | 24.32 | 24.51 |
Minimum of Months | 24.15 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.00 | 19.42 |
February | 24.07 | 20.87 |
March | 24.14 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.28 | 23.59 |
December | 24.05 | 20.30 |
Annual Sum or Average | 24.28 | 24.51 |
Minimum of Months | 24.00 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.12 | 19.42 |
February | 24.15 | 20.87 |
March | 24.21 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.30 | 23.59 |
December | 24.15 | 20.30 |
Annual Sum or Average | 24.31 | 24.51 |
Minimum of Months | 24.12 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | 19.42 |
February | 24.05 | 20.87 |
March | 24.16 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.27 | 23.59 |
December | 24.02 | 20.30 |
Annual Sum or Average | 24.27 | 24.51 |
Minimum of Months | 23.97 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 19.42 |
February | 24.10 | 20.87 |
March | 24.17 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.30 | 23.59 |
December | 24.08 | 20.30 |
Annual Sum or Average | 24.29 | 24.51 |
Minimum of Months | 24.04 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.04 | 19.42 |
February | 24.10 | 20.87 |
March | 24.17 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.30 | 23.59 |
December | 24.08 | 20.30 |
Annual Sum or Average | 24.29 | 24.51 |
Minimum of Months | 24.04 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.22 | 19.42 |
February | 24.22 | 20.87 |
March | 24.25 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.34 | 23.59 |
December | 24.22 | 20.30 |
Annual Sum or Average | 24.34 | 24.51 |
Minimum of Months | 24.22 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.22 | 19.42 |
February | 24.22 | 20.87 |
March | 24.25 | 21.57 |
April | 24.39 | 24.11 |
May | 24.40 | 26.41 |
June | 24.40 | 27.68 |
July | 24.40 | 28.13 |
August | 24.40 | 27.97 |
September | 24.40 | 27.49 |
October | 24.40 | 26.35 |
November | 24.33 | 23.59 |
December | 24.22 | 20.30 |
Annual Sum or Average | 24.34 | 24.51 |
Minimum of Months | 24.22 | 19.42 |
Maximum of Months | 24.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.65 | 19.42 |
February | 25.91 | 20.87 |
March | 26.15 | 21.57 |
April | 26.74 | 24.11 |
May | 27.08 | 26.41 |
June | 27.27 | 27.68 |
July | 27.35 | 28.13 |
August | 27.23 | 27.97 |
September | 27.23 | 27.49 |
October | 26.98 | 26.35 |
November | 26.45 | 23.59 |
December | 25.82 | 20.30 |
Annual Sum or Average | 26.66 | 24.51 |
Minimum of Months | 25.65 | 19.42 |
Maximum of Months | 27.35 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 19.42 |
February | 24.38 | 20.87 |
March | 24.59 | 21.57 |
April | 25.40 | 24.11 |
May | 25.95 | 26.41 |
June | 26.96 | 27.68 |
July | 27.26 | 28.13 |
August | 27.17 | 27.97 |
September | 27.13 | 27.49 |
October | 26.09 | 26.35 |
November | 25.22 | 23.59 |
December | 24.23 | 20.30 |
Annual Sum or Average | 25.70 | 24.51 |
Minimum of Months | 23.95 | 19.42 |
Maximum of Months | 27.26 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:05
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.35 | 19.42 |
February | 26.40 | 20.87 |
March | 26.52 | 21.57 |
April | 26.79 | 24.11 |
May | 26.94 | 26.41 |
June | 27.04 | 27.68 |
July | 27.09 | 28.13 |
August | 27.02 | 27.97 |
September | 27.04 | 27.49 |
October | 26.94 | 26.35 |
November | 26.69 | 23.59 |
December | 26.38 | 20.30 |
Annual Sum or Average | 26.77 | 24.51 |
Minimum of Months | 26.35 | 19.42 |
Maximum of Months | 27.09 | 28.13 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:05
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.121040E+12 | 78393.562 | 06-JAN-18:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 13365.504 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23198.481 | 0.000 | 0.000 | 0.000 |
February | 0.112681E+12 | 75871.961 | 11-FEB-18:30 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 16902.450 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17139.934 | 0.000 | 0.000 | 0.000 |
March | 0.127136E+12 | 77336.049 | 13-MAR-16:15 | 4276.255 | 26730.986 | 7665.703 | 0.000 | 22652.876 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16010.228 | 0.000 | 0.000 | 0.000 |
April | 0.129536E+12 | 79375.306 | 23-APR-17:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 19885.514 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20213.215 | 0.000 | 0.000 | 0.000 |
May | 0.142845E+12 | 84287.271 | 29-MAY-17:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 27336.788 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17673.906 | 0.000 | 0.000 | 0.000 |
June | 0.144467E+12 | 86245.636 | 08-JUN-16:45 | 4276.255 | 26730.986 | 7665.703 | 0.000 | 27871.936 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19700.756 | 0.000 | 0.000 | 0.000 |
July | 0.150536E+12 | 88137.217 | 27-JUL-17:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 29475.977 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19384.662 | 0.000 | 0.000 | 0.000 |
August | 0.150218E+12 | 86419.905 | 19-AUG-16:15 | 4276.255 | 26630.920 | 7665.703 | 0.000 | 26907.618 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20939.408 | 0.000 | 0.000 | 0.000 |
September | 0.145198E+12 | 86940.150 | 20-SEP-17:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 26634.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21029.139 | 0.000 | 0.000 | 0.000 |
October | 0.144014E+12 | 84383.118 | 29-OCT-16:15 | 4276.255 | 26730.986 | 7665.703 | 0.000 | 24702.853 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21007.320 | 0.000 | 0.000 | 0.000 |
November | 0.130124E+12 | 82270.306 | 21-NOV-18:45 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 17279.124 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23161.606 | 0.000 | 0.000 | 0.000 |
December | 0.123949E+12 | 77267.052 | 10-DEC-18:15 | 4979.953 | 26630.920 | 7665.703 | 0.000 | 16242.023 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19195.452 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.162174E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.112681E+12 | 75871.961 | 4276.255 | 26630.920 | 7665.703 | 0.000 | 13365.504 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16010.228 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.150536E+12 | 88137.217 | 4979.953 | 26730.986 | 7665.703 | 0.000 | 29475.977 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23198.481 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:05
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.192624E+09 | 8124.364 | 25-JAN-06:00 | 8124.364 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8124.364 |
February | 0.729104E+09 | 23115.493 | 04-FEB-06:00 | 23115.493 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23115.493 |
March | 0.315915E+09 | 14236.930 | 16-MAR-05:00 | 14236.930 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14236.930 |
April | 0.000 | 0.000 | 01-APR-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 01-OCT-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.468633E+08 | 3164.113 | 13-NOV-05:00 | 3164.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3164.113 |
December | 0.464581E+09 | 11776.518 | 15-DEC-05:00 | 11776.518 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11776.518 |
Annual Sum or Average | 0.174909E+10 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.729104E+09 | 23115.493 | 23115.493 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23115.493 |