Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920

Simulation Timestamp: 2015-09-09 18:48:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1677.91 535.29 594.17
Net Site Energy 1677.91 535.29 594.17
Total Source Energy 4574.98 1459.50 1620.05
Net Source Energy 4574.98 1459.50 1620.05


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 354.76 0.00 0.00 0.00 0.00
Cooling 42.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.03 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 192.32 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 412.32 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1323.15 354.76 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 354.76 0.00 0.00 0.00 0.00
Cooling General 42.36 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.03 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 192.32 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 412.32 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.13 0.00 0.00 0.00 0.00 0.00
HVAC 229.11 125.63 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 468.54 125.63 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.56 0.00 0.00 0.00 0.00 0.00
HVAC 206.41 113.18 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 422.11 113.18 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1323.15 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1323.15 100.00
     
Total On-Site and Utility Electric Sources 1323.15 100.00
Total Electricity End Uses 1323.15 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 77.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 1144.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
RunPeriod Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Weather File Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Latitude [deg] 49.18
Longitude [deg] -123.2
Elevation [m] 2.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 23-JUN-17:15 16-DEC-16:00 - - - 01-JAN-07:15
Heating 0.00 80290.91 0.00 0.00 0.00 0.00
Cooling 10938.11 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6098.55 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25609.99 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 74257.52 80290.91 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 80290.91 0.00 0.00 0.00 0.00
Cooling General 10938.11 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6098.55 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 25609.99 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 384.56 0.00 0.00 0.00
Cooling 134.14 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 126.78 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 609.09 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 1305.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 4190.42 384.56 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 136.18 0.00 0.00 0.00
Cooling 47.50 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.90 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 215.69 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 462.41 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1483.87 136.18 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 136.18 0.00 0.00 0.00
Cooling 47.50 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 44.90 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 215.69 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 462.41 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1483.87 136.18 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
VANCOUVER INT'L ANN HTG 99.6% CONDNS DB -7.00 0.00 -7.00 Wetbulb [C] 2.90 100.00
VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 25.00 7.60 18.20 Wetbulb [C] 3.60 300.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.363 0.384 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.363 0.384 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.363 0.384 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.363 0.384 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 9.29 2.653 0.426 0.308     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 14.12 2.653 0.426 0.308     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_0.52_SHGC_0.40 4.65 0.00 0.00 4.65 4.65 2.653 0.426 0.308     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_0.52_SHGC_0.40 7.06 0.00 0.00 7.06 7.06 2.653 0.426 0.308     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 1.11 2.653 0.426 0.308     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_0.52_SHGC_0.40 3.32 0.00 0.00 3.32 3.32 2.653 0.426 0.308     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_0.52_SHGC_0.40 1.11 0.00 0.00 1.11 2.23 2.653 0.426 0.308     No M EWALL C 270.00 90.00 W
Total or Average           306.92 2.653 0.426 0.308              
North Total or Average           112.97 2.653 0.426 0.308              
Non-North Total or Average           193.95 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.53 83.53 40.03
Exterior Lighting Total 2553.00           40.03



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   2568.25 2044.86 523.39 0.80 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   1866.51 1477.64 388.87 0.79 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7393.65 5904.98 1488.67 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   1348.41 1051.82 296.59 0.78 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   970.11 754.66 215.45 0.78 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   954.76 742.26 212.50 0.78 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   1970.28 1554.50 415.78 0.79 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2017.85 1595.26 422.59 0.79 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   7291.30 5823.23 1468.06 0.80 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5368.28 4287.40 1080.87 0.80 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   6888.30 5501.38 1386.92 0.80 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4182.29 3330.37 851.92 0.80 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3077.63 2435.43 642.20 0.79 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3049.51 2412.36 637.15 0.79 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5666.57 4525.63 1140.93 0.80 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5688.44 4543.10 1145.34 0.80 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   4757.33 3799.46 957.86 0.80 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   3433.89 2742.49 691.40 0.80 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   4498.41 3592.68 905.73 0.80 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   2607.38 2075.15 532.23 0.80 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   2084.42 1639.10 445.31 0.79 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   2094.07 1645.36 448.70 0.79 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3906.65 3120.07 786.58 0.80 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3922.03 3132.35 789.68 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 2447.5 3.13 10.69 11.10 10.40
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 1779.8 3.14 10.71 11.13 10.44
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7043.6 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 1287.8 3.16 10.78 11.21 10.54
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 926.7 3.16 10.79 11.22 10.55
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 912.1 3.16 10.80 11.22 10.56
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1879.4 3.14 10.73 11.15 10.46
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1924.4 3.14 10.72 11.14 10.45
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 6946.1 3.13 10.67 11.09 10.38
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 5114.1 3.13 10.67 11.09 10.38
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 6562.2 3.13 10.67 11.09 10.38
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 3985.5 3.13 10.68 11.10 10.40
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 2934.8 3.14 10.71 11.14 10.44
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2908.1 3.14 10.72 11.14 10.44
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5398.3 3.13 10.67 11.09 10.38
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5419.1 3.13 10.67 11.09 10.38
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 4532.1 3.13 10.67 11.09 10.38
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 3271.3 3.13 10.67 11.09 10.38
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 4285.4 3.13 10.67 11.09 10.38
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 2484.9 3.13 10.69 11.11 10.40
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 1989.0 3.15 10.74 11.17 10.48
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 1998.4 3.15 10.75 11.17 10.49
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3721.7 3.13 10.67 11.09 10.38
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3736.3 3.13 10.67 11.09 10.38
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   2433.05 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   2403.16 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   4464.75 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   2408.34 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1812.18 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1812.31 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1811.39 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1913.31 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   4675.60 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   4678.55 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   4689.48 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   4692.43 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   3579.58 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   3579.58 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   3579.58 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   3579.58 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   3565.16 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   3568.35 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   3572.43 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   3575.62 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   2761.13 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   2761.33 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   2756.13 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   2756.34 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.15 178.90 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.11 128.40 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.45 518.49 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.08 89.77 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.06 64.19 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.05 63.09 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 134.53 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 138.39 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 511.31 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 376.46 1160.84 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 483.05 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 291.41 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 211.52 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 209.44 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 397.38 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.34 398.91 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 333.61 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.21 240.81 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.27 315.46 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.16 181.46 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 141.28 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.12 141.68 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 273.96 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.24 275.04 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1639.78 1967.74 0.128 0.154 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 24.66 0.01029
G NW APARTMENT 1176.91 1412.29 0.092 0.111 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 23.18 0.01029
OFFICE 4655.99 5587.19 0.372 0.447 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 20.82 0.01029
G NE APARTMENT 822.79 987.35 0.064 0.077 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 10:15:00 22.40 0.01029
G N1 APARTMENT 588.38 706.06 0.046 0.055 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.04 0.01029
G N2 APARTMENT 578.28 693.93 0.045 0.054 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.04 0.01029
G S1 APARTMENT 1233.08 1479.70 0.097 0.116 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 24.91 0.01029
G S2 APARTMENT 1268.50 1522.20 0.099 0.119 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.81 0.01029
M SW APARTMENT 4686.52 5623.83 0.367 0.440 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 24.66 0.01029
M NW APARTMENT 3450.57 4140.68 0.270 0.324 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 23.18 0.01029
M SE APARTMENT 4427.50 5313.00 0.347 0.416 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.81 0.01029
M NE APARTMENT 2670.95 3205.14 0.209 0.251 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 10:15:00 22.40 0.01029
M N1 APARTMENT 1938.82 2326.59 0.152 0.182 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.04 0.01029
M N2 APARTMENT 1919.68 2303.62 0.150 0.180 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 22.04 0.01029
M S1 APARTMENT 3642.29 4370.74 0.285 0.342 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 25.00 0.01029
M S2 APARTMENT 3656.34 4387.61 0.286 0.344 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 24.91 0.01029
T SW APARTMENT 3057.74 3669.29 0.239 0.287 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 24.77 0.01029
T NW APARTMENT 2207.13 2648.56 0.173 0.207 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 23.75 0.01029
T SE APARTMENT 2891.32 3469.58 0.226 0.272 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 24.91 0.01029
T NE APARTMENT 1663.19 1995.82 0.130 0.156 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 11:15:00 23.44 0.01029
T N1 APARTMENT 1294.97 1553.97 0.101 0.122 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 24.89 0.01029
T N2 APARTMENT 1298.64 1558.37 0.102 0.122 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 25.00 0.01029
T S1 APARTMENT 2511.04 3013.24 0.197 0.236 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 25.00 0.01029
T S2 APARTMENT 2520.92 3025.10 0.197 0.237 VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 25.00 0.01029


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 1267.69 1521.23 0.036 0.044 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G NW APARTMENT 1270.17 1524.21 0.037 0.044 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
OFFICE 2712.01 3254.41 0.075 0.090 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G NE APARTMENT 1274.55 1529.46 0.037 0.044 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G N1 APARTMENT 770.41 924.49 0.022 0.027 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G N2 APARTMENT 770.51 924.61 0.022 0.027 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G S1 APARTMENT 769.73 923.68 0.022 0.027 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
G S2 APARTMENT 855.93 1027.11 0.025 0.030 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.00 0.00208
M SW APARTMENT 2429.91 2915.89 0.070 0.084 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M NW APARTMENT 2432.40 2918.88 0.070 0.084 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M SE APARTMENT 2441.64 2929.97 0.070 0.084 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M NE APARTMENT 2444.14 2932.97 0.070 0.084 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M N1 APARTMENT 1172.84 1407.41 0.034 0.052 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M N2 APARTMENT 1173.15 1407.78 0.034 0.052 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M S1 APARTMENT 1171.89 1406.27 0.034 0.052 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
M S2 APARTMENT 1172.20 1406.64 0.034 0.052 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T SW APARTMENT 2252.90 2703.49 0.065 0.078 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T NW APARTMENT 2255.60 2706.72 0.065 0.078 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T SE APARTMENT 2259.05 2710.86 0.065 0.078 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T NE APARTMENT 2261.75 2714.10 0.065 0.078 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T N1 APARTMENT 1572.93 1887.52 0.045 0.054 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T N2 APARTMENT 1573.10 1887.72 0.045 0.054 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T S1 APARTMENT 1568.71 1882.45 0.045 0.054 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208
T S2 APARTMENT 1568.88 1882.65 0.045 0.054 VANCOUVER INT'L ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.00 0.00208


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.15 0.15 0.04 0.04
SPLIT GNW 0.11 0.11 0.04 0.04
SPLIT OFFICE 0.45 0.45 0.09 0.09
SPLIT GNE 0.08 0.08 0.04 0.04
SPLIT GN1 0.06 0.06 0.03 0.03
SPLIT GN2 0.05 0.05 0.03 0.03
SPLIT GS1 0.12 0.12 0.03 0.03
SPLIT GS2 0.12 0.12 0.03 0.03
SPLIT MSW 0.44 0.44 0.08 0.08
SPLIT MNW 0.32 0.32 0.08 0.08
SPLIT MSE 0.42 0.42 0.08 0.08
SPLIT MNE 0.25 0.25 0.08 0.08
SPLIT MN1 0.18 0.18 0.05 0.05
SPLIT MN2 0.18 0.18 0.05 0.05
SPLIT MS1 0.34 0.34 0.05 0.05
SPLIT MS2 0.34 0.34 0.05 0.05
SPLIT TSW 0.29 0.29 0.08 0.08
SPLIT TNW 0.21 0.21 0.08 0.08
SPLIT TSE 0.27 0.27 0.08 0.08
SPLIT TNE 0.16 0.16 0.08 0.08
SPLIT TN1 0.12 0.12 0.05 0.05
SPLIT TN2 0.12 0.12 0.05 0.05
SPLIT TS1 0.24 0.24 0.05 0.05
SPLIT TS2 0.24 0.24 0.05 0.05



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 1379.00 6739.25 256.75
G NW APARTMENT 1103.50 7254.25 382.75
OFFICE 279.25 1658.75 47.75
G NE APARTMENT 1066.75 7365.00 378.25
G N1 APARTMENT 516.25 7511.50 135.75
G N2 APARTMENT 510.75 7519.50 135.75
G S1 APARTMENT 1061.50 6718.00 48.25
G S2 APARTMENT 1154.75 6635.00 73.50
M SW APARTMENT 2622.75 4969.00 0.00
M NW APARTMENT 2270.50 5647.50 48.75
M SE APARTMENT 2570.50 4990.50 0.00
M NE APARTMENT 2199.50 5714.00 51.25
M N1 APARTMENT 2131.50 5603.00 0.00
M N2 APARTMENT 2122.75 5608.00 0.00
M S1 APARTMENT 2590.75 4648.00 0.00
M S2 APARTMENT 2589.25 4651.25 0.00
T SW APARTMENT 2697.75 5912.75 853.50
T NW APARTMENT 2533.50 6603.75 1104.00
T SE APARTMENT 2697.50 5943.00 858.25
T NE APARTMENT 2523.50 6717.25 1107.75
T N1 APARTMENT 1781.75 6631.25 475.25
T N2 APARTMENT 1783.50 6645.25 475.75
T S1 APARTMENT 2156.00 5694.00 299.50
T S2 APARTMENT 2156.25 5698.75 299.75
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4042.50 7637.50 1144.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 6.50 0.00 6.50 0.00
G NW APARTMENT 5.75 0.00 5.75 0.00
OFFICE 6.25 0.25 0.00 0.00
G NE APARTMENT 6.25 0.00 6.25 0.00
G N1 APARTMENT 5.75 0.00 5.75 0.00
G N2 APARTMENT 5.75 0.00 5.75 0.00
G S1 APARTMENT 8.50 0.00 8.50 0.00
G S2 APARTMENT 12.75 0.00 12.75 0.00
M SW APARTMENT 1.50 0.00 1.50 0.00
M NW APARTMENT 1.50 0.00 1.50 0.00
M SE APARTMENT 1.00 0.00 1.00 0.00
M NE APARTMENT 2.50 0.00 2.50 0.00
M N1 APARTMENT 3.00 0.00 3.00 0.00
M N2 APARTMENT 2.25 0.00 2.25 0.00
M S1 APARTMENT 2.25 0.00 2.25 0.00
M S2 APARTMENT 1.75 0.00 1.75 0.00
T SW APARTMENT 0.50 0.00 0.50 0.00
T NW APARTMENT 0.00 0.00 0.00 0.00
T SE APARTMENT 0.75 0.00 0.75 0.00
T NE APARTMENT 2.75 0.00 2.75 0.00
T N1 APARTMENT 7.75 0.00 7.75 0.00
T N2 APARTMENT 7.25 0.00 7.25 0.00
T S1 APARTMENT 2.25 0.00 2.25 0.00
T S2 APARTMENT 1.75 0.00 1.75 0.00
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 83.25 0.25 77.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.366 0.151 0.000 0.064
G NW APARTMENT 1.71 2.50 268.97 0.353 0.151 0.000 0.061
OFFICE 0.94 1.00 268.97 0.519 0.169 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.352 0.151 0.000 0.061
G N1 APARTMENT 1.71 2.50 268.97 0.352 0.091 0.000 0.060
G N2 APARTMENT 1.71 2.50 268.97 0.352 0.091 0.000 0.060
G S1 APARTMENT 1.71 2.50 268.97 0.353 0.091 0.000 0.064
G S2 APARTMENT 1.71 2.50 268.97 0.353 0.091 0.000 0.064
M SW APARTMENT 1.71 2.50 268.97 0.353 0.218 0.000 0.074
M NW APARTMENT 1.71 2.50 268.97 0.353 0.218 0.000 0.070
M SE APARTMENT 1.71 2.50 268.97 0.353 0.218 0.000 0.074
M NE APARTMENT 1.71 2.50 268.97 0.353 0.218 0.000 0.070
M N1 APARTMENT 1.71 2.50 268.97 0.353 0.131 0.000 0.070
M N2 APARTMENT 1.71 2.50 268.97 0.353 0.131 0.000 0.070
M S1 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.074
M S2 APARTMENT 1.71 2.50 268.97 0.354 0.131 0.000 0.074
T SW APARTMENT 1.71 2.50 268.97 0.353 0.288 0.000 0.079
T NW APARTMENT 1.71 2.50 268.97 0.353 0.288 0.000 0.075
T SE APARTMENT 1.71 2.50 268.97 0.353 0.288 0.000 0.080
T NE APARTMENT 1.71 2.50 268.97 0.353 0.288 0.000 0.075
T N1 APARTMENT 1.71 2.50 268.97 0.353 0.173 0.000 0.075
T N2 APARTMENT 1.71 2.50 268.97 0.353 0.173 0.000 0.075
T S1 APARTMENT 1.71 2.50 268.97 0.353 0.174 0.000 0.080
T S2 APARTMENT 1.71 2.50 268.97 0.353 0.174 0.000 0.080
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.354 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.501 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.367 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.342 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 412.32 0.00 01-JAN-00:15 32548.73 13-FEB-07:30
WaterSystems:Electricity 412.32 0.00 01-JAN-00:15 32548.73 13-FEB-07:30
Water Heater:WaterSystems:Electricity 412.32 0.00 01-JAN-00:15 32548.73 13-FEB-07:30
Fans:Electricity 192.32 6098.55 01-JAN-00:15 6098.55 01-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
ElectricityPurchased:Plant 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
Cogeneration:ElectricityPurchased 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
ElectricityNet:Plant 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
Cogeneration:ElectricityNet 1323.15 19211.16 01-JAN-03:15 74257.52 23-JUN-17:15
ExteriorLights:Electricity 40.03 0.00 01-JAN-08:15 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.03 0.00 01-JAN-08:15 2553.00 01-JAN-00:15
Electricity:HVAC 234.68 6098.55 01-JAN-00:15 20408.27 12-JUL-15:15
General:Fans:Electricity 192.32 6098.55 01-JAN-00:15 6098.55 01-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 42.36 0.00 01-JAN-00:15 14309.72 12-JUL-15:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 354.76 0.00 26-MAR-15:15 80290.91 16-DEC-17:00
Gas:HVAC 354.76 0.00 26-MAR-15:15 80290.91 16-DEC-17:00
Heating:Gas 354.76 0.00 26-MAR-15:15 80290.91 16-DEC-17:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 851.29 1808.05 01-SEP-16:00 116264.99 03-DEC-02:00
EnergyTransfer:Building 394.63 1808.05 01-SEP-16:00 53035.00 03-DEC-02:00
EnergyTransfer:Zone:G SW APARTMENT 10.27 0.11 29-JAN-20:00 1646.60 03-DEC-02:00
Heating:EnergyTransfer 144.71 0.00 22-FEB-15:15 53035.00 03-DEC-02:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 5.65 0.00 01-JAN-10:45 1646.60 03-DEC-02:00
Cooling:EnergyTransfer 249.93 0.00 05-JAN-07:15 47011.70 16-JUL-15:45
Cooling:EnergyTransfer:Zone:G SW APARTMENT 4.62 0.00 01-JAN-00:15 1558.79 13-SEP-15:15
EnergyTransfer:Zone:G NW APARTMENT 10.09 0.13 29-APR-04:30 1658.22 03-DEC-02:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 6.99 0.00 21-JAN-17:15 1658.22 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 3.10 0.00 01-JAN-00:15 1338.84 11-JUL-17:30
EnergyTransfer:Zone:OFFICE 17.61 0.00 18-SEP-01:15 3857.82 13-AUG-13:15
Heating:EnergyTransfer:Zone:OFFICE 0.75 0.00 01-JAN-00:15 2350.14 17-DEC-07:15
Cooling:EnergyTransfer:Zone:OFFICE 16.86 0.00 02-JAN-07:45 3857.82 13-AUG-13:15
EnergyTransfer:Zone:G NE APARTMENT 10.11 0.06 29-APR-15:30 1650.96 03-DEC-02:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 7.03 0.00 04-FEB-21:00 1650.96 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 3.08 0.00 01-JAN-00:15 801.24 11-JUL-18:30
EnergyTransfer:Zone:G N1 APARTMENT 6.51 0.12 11-MAY-13:45 948.82 03-DEC-02:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 3.18 0.00 01-JAN-17:15 948.82 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 3.33 0.00 01-JAN-00:15 657.31 11-JUL-18:30
EnergyTransfer:Zone:G N2 APARTMENT 6.51 0.04 17-MAR-18:30 947.21 03-DEC-02:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 3.18 0.00 01-JAN-17:15 947.21 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 3.33 0.00 01-JAN-00:15 644.97 11-JUL-18:30
EnergyTransfer:Zone:G S1 APARTMENT 7.04 0.19 20-FEB-17:00 1150.69 13-SEP-13:30
Heating:EnergyTransfer:Zone:G S1 APARTMENT 2.25 0.00 01-JAN-09:45 936.34 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 4.79 0.00 01-JAN-00:15 1150.69 13-SEP-13:30
EnergyTransfer:Zone:G S2 APARTMENT 7.29 0.12 20-FEB-20:30 1159.46 13-SEP-13:30
Heating:EnergyTransfer:Zone:G S2 APARTMENT 2.43 0.00 01-JAN-10:00 989.84 03-DEC-02:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 4.86 0.00 01-JAN-00:15 1159.46 13-SEP-13:30
EnergyTransfer:Zone:M SW APARTMENT 28.79 0.11 14-AUG-09:30 4685.19 13-SEP-15:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 6.51 0.00 01-JAN-00:15 3986.60 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 22.28 0.00 01-JAN-04:15 4685.19 13-SEP-15:15
EnergyTransfer:Zone:M NW APARTMENT 23.82 0.24 05-SEP-15:00 4032.56 16-JUL-18:00
Heating:EnergyTransfer:Zone:M NW APARTMENT 9.13 0.00 01-JAN-11:45 4021.20 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 14.69 0.00 01-JAN-00:15 4032.56 16-JUL-18:00
EnergyTransfer:Zone:M SE APARTMENT 28.14 0.02 07-JAN-21:30 4238.04 13-SEP-13:15
Heating:EnergyTransfer:Zone:M SE APARTMENT 6.63 0.00 01-JAN-00:15 3967.31 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 21.51 0.00 01-JAN-04:15 4238.04 13-SEP-13:15
EnergyTransfer:Zone:M NE APARTMENT 23.48 0.20 14-APR-10:45 3971.08 03-DEC-02:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 9.29 0.00 01-JAN-10:30 3971.08 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 14.20 0.00 01-JAN-00:15 2772.86 11-JUL-18:30
EnergyTransfer:Zone:M N1 APARTMENT 18.31 0.07 07-DEC-13:00 2323.35 11-JUL-18:45
Heating:EnergyTransfer:Zone:M N1 APARTMENT 2.13 0.00 01-JAN-00:15 2102.89 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 16.17 0.00 01-JAN-04:30 2323.35 11-JUL-18:45
EnergyTransfer:Zone:M N2 APARTMENT 18.25 0.11 12-NOV-11:30 2300.75 11-JUL-18:45
Heating:EnergyTransfer:Zone:M N2 APARTMENT 2.13 0.00 01-JAN-00:15 2102.15 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 16.11 0.00 01-JAN-04:30 2300.75 11-JUL-18:45
EnergyTransfer:Zone:M S1 APARTMENT 25.82 0.39 15-APR-01:45 3678.96 13-SEP-13:30
Heating:EnergyTransfer:Zone:M S1 APARTMENT 1.19 0.00 01-JAN-00:15 2065.54 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 24.62 0.00 02-JAN-23:30 3678.96 13-SEP-13:30
EnergyTransfer:Zone:M S2 APARTMENT 25.76 0.06 18-MAR-23:45 3691.89 13-SEP-13:30
Heating:EnergyTransfer:Zone:M S2 APARTMENT 1.19 0.00 01-JAN-00:15 2064.72 03-DEC-02:00
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 24.57 0.00 02-JAN-23:30 3691.89 13-SEP-13:30
EnergyTransfer:Zone:T SW APARTMENT 19.41 0.02 25-SEP-19:30 3102.71 03-DEC-02:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 11.21 0.00 01-JAN-10:45 3102.71 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 8.20 0.00 01-JAN-00:15 2899.05 11-JUL-17:15
EnergyTransfer:Zone:T NW APARTMENT 18.45 0.01 14-AUG-02:15 3116.92 03-DEC-02:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 13.15 0.00 04-FEB-18:00 3116.92 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 5.30 0.00 01-JAN-00:15 2668.43 11-JUL-17:30
EnergyTransfer:Zone:T SE APARTMENT 18.98 0.01 20-AUG-06:00 3094.51 03-DEC-02:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 11.24 0.00 01-JAN-10:30 3094.51 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 7.74 0.00 01-JAN-00:15 2608.16 13-SEP-13:30
EnergyTransfer:Zone:T NE APARTMENT 18.33 0.07 13-APR-08:30 3109.62 03-DEC-02:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 13.23 0.00 05-FEB-13:00 3109.62 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 5.10 0.00 01-JAN-00:15 1862.98 11-JUL-16:15
EnergyTransfer:Zone:T N1 APARTMENT 12.30 0.03 25-MAR-09:45 1896.42 03-DEC-02:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 7.37 0.00 21-JAN-13:45 1896.42 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 4.93 0.00 01-JAN-00:15 1593.60 11-JUL-17:15
EnergyTransfer:Zone:T N2 APARTMENT 12.28 0.03 19-MAY-10:15 1896.10 03-DEC-02:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 7.38 0.00 21-JAN-13:45 1896.10 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 4.90 0.00 01-JAN-00:15 1574.24 11-JUL-17:15
EnergyTransfer:Zone:T S1 APARTMENT 13.54 0.00 14-AUG-02:00 2345.81 13-SEP-13:45
Heating:EnergyTransfer:Zone:T S1 APARTMENT 5.73 0.00 01-JAN-10:15 1879.20 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 7.81 0.00 01-JAN-00:15 2345.81 13-SEP-13:45
EnergyTransfer:Zone:T S2 APARTMENT 13.54 0.01 15-SEP-08:30 2354.03 13-SEP-13:45
Heating:EnergyTransfer:Zone:T S2 APARTMENT 5.74 0.00 01-JAN-10:15 1878.89 03-DEC-02:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 7.80 0.00 01-JAN-00:15 2354.03 13-SEP-13:45
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 456.66 0.00 06-JUN-00:45 64232.73 16-DEC-17:00
HeatingCoils:EnergyTransfer 283.81 0.00 26-MAR-15:15 64232.73 16-DEC-17:00
CoolingCoils:EnergyTransfer 172.85 0.00 01-JAN-00:15 62903.79 12-JUL-15:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 5.647 -4.624 0.000 0.000 3.910 1.087 12.213 11.434 0.000 0.000 0.000 0.000 -8.378 0.000 -6.478 -14.811
G NW APARTMENT 6.993 -3.098 0.000 0.000 3.940 1.087 12.213 5.692 0.000 0.000 0.000 0.000 -8.398 0.000 -6.316 -12.113
OFFICE 0.747 -16.863 0.000 0.000 0.523 26.452 9.482 10.677 0.000 0.000 0.000 0.000 -8.379 0.000 -5.497 -17.142
G NE APARTMENT 7.034 -3.081 0.000 0.000 3.954 1.087 12.213 5.074 0.000 0.000 0.000 0.000 -8.310 0.000 -6.302 -11.668
G N1 APARTMENT 3.177 -3.332 0.000 0.000 3.951 1.087 12.213 1.728 0.000 0.000 0.000 0.000 -5.164 0.000 -4.152 -9.508
G N2 APARTMENT 3.180 -3.328 0.000 0.000 3.952 1.087 12.213 1.728 0.000 0.000 0.000 0.000 -5.162 0.000 -4.151 -9.519
G S1 APARTMENT 2.247 -4.793 0.000 0.000 3.908 1.087 12.213 7.513 0.000 0.000 0.000 0.000 -5.145 0.000 -4.333 -12.697
G S2 APARTMENT 2.429 -4.861 0.000 0.000 3.905 1.087 12.213 7.508 0.000 0.000 0.000 0.000 -5.147 0.000 -4.343 -12.790
M SW APARTMENT 6.506 -22.283 0.000 0.000 3.793 1.087 12.213 11.047 0.000 0.000 6.052 0.000 -9.076 0.000 -9.339 -0.000
M NW APARTMENT 9.125 -14.692 0.000 0.000 3.848 1.087 12.213 5.363 0.000 0.000 1.163 0.000 -8.982 0.000 -9.125 -0.001
M SE APARTMENT 6.626 -21.514 0.000 0.000 3.799 1.087 12.213 10.434 0.000 0.000 5.688 0.000 -8.999 0.000 -9.333 -0.000
M NE APARTMENT 9.286 -14.197 0.000 0.000 3.860 1.087 12.213 4.745 0.000 0.000 0.996 0.000 -8.882 0.000 -9.107 -0.000
M N1 APARTMENT 2.133 -16.175 0.000 0.000 3.841 1.087 12.213 1.520 0.000 0.000 6.990 0.000 -5.600 0.000 -6.008 -0.000
M N2 APARTMENT 2.135 -16.115 0.000 0.000 3.842 1.087 12.213 1.520 0.000 0.000 6.923 0.000 -5.597 0.000 -6.007 -0.000
M S1 APARTMENT 1.194 -24.625 0.000 0.000 3.761 1.087 12.213 7.268 0.000 0.000 10.949 0.000 -5.640 0.000 -6.207 -0.000
M S2 APARTMENT 1.194 -24.566 0.000 0.000 3.761 1.087 12.213 7.268 0.000 0.000 10.889 0.000 -5.639 0.000 -6.207 -0.000
T SW APARTMENT 11.214 -8.198 0.000 0.000 3.865 1.087 12.213 10.986 0.000 0.001 0.000 0.000 -8.536 0.000 -11.783 -10.847
T NW APARTMENT 13.151 -5.295 0.000 0.000 3.908 1.087 12.213 5.356 0.000 0.000 0.000 0.000 -8.498 0.000 -11.503 -10.419
T SE APARTMENT 11.236 -7.743 0.000 0.000 3.872 1.087 12.213 10.394 0.000 0.001 0.000 0.000 -8.483 0.000 -11.792 -10.783
T NE APARTMENT 13.231 -5.104 0.000 0.000 3.925 1.087 12.213 4.759 0.000 0.000 0.000 0.000 -8.415 0.000 -11.486 -10.209
T N1 APARTMENT 7.369 -4.929 0.000 0.000 3.909 1.087 12.213 1.550 0.000 0.000 0.000 0.000 -5.253 0.000 -7.428 -8.519
T N2 APARTMENT 7.380 -4.898 0.000 0.000 3.911 1.087 12.213 1.549 0.000 0.000 0.000 0.000 -5.250 0.000 -7.428 -8.563
T S1 APARTMENT 5.733 -7.811 0.000 0.000 3.847 1.087 12.213 7.245 0.000 0.000 0.000 0.000 -5.290 0.000 -7.691 -9.333
T S2 APARTMENT 5.742 -7.800 0.000 0.000 3.848 1.087 12.213 7.244 0.000 0.000 0.000 0.000 -5.288 0.000 -7.692 -9.353
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.029 0.000 0.000 0.000 0.000 -0.993 0.000 -1.890 -11.729
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 0.143 0.000 0.000 13.418 0.000 -2.591 0.000 -32.031 -0.000
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.028 0.000 0.000 0.000 0.000 -1.098 0.000 -1.567 -11.944
Total Facility 144.708 -249.926 0.000 0.000 89.635 95.189 296.854 149.800 0.000 0.010 63.068 0.000 -172.194 0.000 -215.198 -201.948


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 13-SEP-15:15 0.00 -1559.14 0.00 0.00 48.90 45.40 470.90 2484.14 0.00 0.00 0.00 0.00 0.00 0.00 -41.94 -1448.26
G NW APARTMENT 11-JUL-17:30 0.00 -1338.85 0.00 0.00 141.81 87.56 588.62 1904.18 0.00 10.10 0.00 0.00 0.00 0.00 0.00 -1393.42
OFFICE 06-AUG-06:01 0.00 -7036.43 0.00 0.00 0.00 416.15 294.31 529.80 0.00 0.00 5893.20 0.00 0.00 0.00 -97.03 0.00
G NE APARTMENT 11-JUL-18:30 0.00 -801.21 0.00 0.00 141.81 103.77 547.42 559.33 0.00 0.00 0.00 0.00 0.00 0.00 -12.42 -538.71
G N1 APARTMENT 11-JUL-18:30 0.00 -657.28 0.00 0.00 141.81 103.77 547.42 488.16 0.00 0.00 0.00 0.00 0.00 0.00 -11.05 -612.82
G N2 APARTMENT 11-JUL-18:30 0.00 -644.94 0.00 0.00 141.81 103.77 547.42 488.39 0.00 0.00 0.00 0.00 0.00 0.00 -11.05 -625.40
G S1 APARTMENT 13-SEP-13:30 0.00 -1150.75 0.00 0.00 40.75 12.97 382.60 2017.32 0.00 0.00 0.00 0.00 0.00 0.00 -55.63 -1247.27
G S2 APARTMENT 13-SEP-13:30 0.00 -1159.53 0.00 0.00 40.75 12.97 382.60 2017.14 0.00 0.00 0.00 0.00 0.00 0.00 -55.63 -1238.30
M SW APARTMENT 13-SEP-15:15 0.00 -4686.17 0.00 0.00 48.90 45.40 470.90 2462.24 0.00 0.00 1716.16 0.00 0.00 0.00 -57.43 0.00
M NW APARTMENT 16-JUL-18:00 0.00 -4032.20 0.00 0.00 141.81 87.56 588.62 1853.41 0.00 0.00 1377.45 0.00 0.00 0.00 -16.66 0.00
M SE APARTMENT 13-SEP-13:15 0.00 -4238.25 0.00 0.00 40.75 12.97 382.60 2212.29 0.00 0.00 1680.46 0.00 0.00 0.00 -90.83 0.00
M NE APARTMENT 11-JUL-18:30 0.00 -2772.70 0.00 0.00 141.81 103.77 547.42 542.94 0.00 0.00 1451.86 0.00 0.00 0.00 -15.10 0.00
M N1 APARTMENT 11-JUL-18:45 0.00 -2323.08 0.00 0.00 141.81 103.77 547.42 441.91 0.00 0.00 1101.64 0.00 0.00 0.00 -13.47 0.00
M N2 APARTMENT 11-JUL-18:45 0.00 -2300.49 0.00 0.00 141.81 103.77 547.42 442.06 0.00 0.00 1078.90 0.00 0.00 0.00 -13.47 0.00
M S1 APARTMENT 13-SEP-13:30 0.00 -3679.20 0.00 0.00 40.75 12.97 382.60 2004.64 0.00 0.00 1309.90 0.00 0.00 0.00 -71.66 0.00
M S2 APARTMENT 13-SEP-13:30 0.00 -3692.14 0.00 0.00 40.75 12.97 382.60 2004.57 0.00 0.00 1322.91 0.00 0.00 0.00 -71.66 0.00
T SW APARTMENT 11-JUL-17:15 0.00 -2899.21 0.00 0.00 141.81 87.56 588.62 1815.32 0.00 24.96 240.94 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 11-JUL-17:30 0.00 -2668.47 0.00 0.00 141.81 87.56 588.62 1855.94 0.00 14.23 0.00 0.00 0.00 0.00 0.00 -19.68
T SE APARTMENT 13-SEP-13:30 0.00 -2608.35 0.00 0.00 40.75 12.97 382.60 2115.51 0.00 0.00 166.87 0.00 0.00 0.00 -110.36 0.00
T NE APARTMENT 11-JUL-16:08 0.00 -1863.44 0.00 0.00 84.76 64.86 588.62 463.80 0.00 22.07 639.34 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 11-JUL-17:15 0.00 -1593.89 0.00 0.00 141.81 87.56 588.62 214.33 0.00 21.78 539.80 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 11-JUL-17:15 0.00 -1574.57 0.00 0.00 141.81 87.56 588.62 214.60 0.00 21.78 520.21 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 13-SEP-13:45 0.00 -2346.01 0.00 0.00 40.75 12.97 382.60 1895.13 0.00 0.00 100.68 0.00 0.00 0.00 -86.12 0.00
T S2 APARTMENT 13-SEP-13:45 0.00 -2354.23 0.00 0.00 40.75 12.97 382.60 1895.00 0.00 0.00 109.02 0.00 0.00 0.00 -86.12 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 16-JUL-15:45 0.00 -47008.76 0.00 0.00 1191.99 4512.09 11708.34 19541.90 0.00 478.17 9663.11 0.00 0.00 0.00 -86.83 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 03-DEC-02:00 1646.20 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -466.51 0.00 -1299.90 -317.29
G NW APARTMENT 13-NOV-17:01 2024.44 0.00 0.00 0.00 99.99 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -387.41 0.00 -22.24 -2368.26
OFFICE 04-DEC-07:01 4154.71 0.00 0.00 0.00 0.00 416.15 294.31 0.00 0.00 0.00 0.00 0.00 -436.93 0.00 -413.21 -4015.03
G NE APARTMENT 03-DEC-02:00 1650.55 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -467.88 0.00 -1299.89 -320.26
G N1 APARTMENT 28-DEC-18:02 1407.06 0.00 0.00 0.00 167.35 87.56 588.62 0.00 0.00 0.00 0.00 0.00 -213.73 0.00 -91.50 -1945.35
G N2 APARTMENT 20-MAY-06:01 993.58 0.00 0.00 0.00 163.04 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -107.27 0.00 -103.56 -1370.55
G S1 APARTMENT 01-APR-07:01 1284.11 0.00 0.00 0.00 74.06 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -62.67 0.00 -72.83 -1630.62
G S2 APARTMENT 28-DEC-17:01 1582.37 0.00 0.00 0.00 99.68 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -200.99 0.00 -62.36 -2072.18
M SW APARTMENT 03-DEC-02:00 3985.62 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -481.62 0.00 -1870.35 -2071.13
M NW APARTMENT 03-DEC-02:00 4020.20 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -489.26 0.00 -1870.35 -2098.08
M SE APARTMENT 03-DEC-02:00 3966.33 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -475.97 0.00 -1870.35 -2057.49
M NE APARTMENT 03-DEC-02:00 3970.10 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -483.64 0.00 -1868.84 -2055.12
M N1 APARTMENT 06-JAN-07:01 2491.39 0.00 0.00 0.00 161.36 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -318.88 0.00 -93.42 -2665.21
M N2 APARTMENT 06-JAN-07:01 2489.63 0.00 0.00 0.00 161.36 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -318.89 0.00 -93.42 -2663.45
M S1 APARTMENT 03-DEC-02:00 2065.05 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -291.46 0.00 -1128.15 -1082.93
M S2 APARTMENT 03-DEC-02:00 2064.24 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -291.47 0.00 -1128.15 -1082.11
T SW APARTMENT 03-DEC-02:00 3101.94 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -466.89 0.00 -2479.97 -592.57
T NW APARTMENT 03-DEC-02:00 3116.15 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -473.94 0.00 -2479.97 -599.73
T SE APARTMENT 03-DEC-02:00 3093.74 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -461.21 0.00 -2479.97 -590.05
T NE APARTMENT 03-DEC-02:00 3108.86 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -468.27 0.00 -2479.97 -598.11
T N1 APARTMENT 03-DEC-02:00 1895.95 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -288.13 0.00 -1495.91 -549.40
T N2 APARTMENT 23-FEB-17:01 2365.98 0.00 0.00 0.00 99.94 64.86 588.62 0.00 0.00 0.00 0.00 0.00 -212.55 0.00 -74.08 -2832.77
T S1 APARTMENT 03-DEC-02:00 1878.75 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -281.77 0.00 -1495.91 -538.56
T S2 APARTMENT 03-DEC-02:00 1878.44 0.00 0.00 0.00 189.67 6.49 241.34 0.00 0.00 0.00 0.00 0.00 -281.78 0.00 -1495.91 -538.24
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-DEC-02:00 53022.06 0.00 0.00 0.00 4362.43 1952.47 5793.19 0.00 0.00 0.00 0.00 0.00 -9282.91 0.00 -36891.90 -18955.34



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Sec1.1A-General Information

Data
Weather File Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 77.00
Number of hours cooling loads not met 0.00
Number of hours not met 77.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.03 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 354.76 80290.91 0.00 0.00
Space Cooling 42.36 10938.11 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 192.32 6098.55 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 412.32 25609.99 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1323.15   354.76   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1323.15
Natural Gas 0.00 354.76
Additional 0.00 0.00
Total 517.65 1677.91


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 13.51
Fans-Interior 61.35
Service Water Heating 131.54
Receptacle Equipment 165.14
Miscellaneous 12.77
Subtotal 422.11


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 113.18
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 113.18


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.06
Space Heating 21.14
Space Cooling 2.52
Fans-Interior 11.46
Service Water Heating 24.57
Receptacle Equipment 30.85
Miscellaneous 2.39



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.154115
G NW APARTMENT DIRECT AIR 0.110610
OFFICE DIRECT AIR 0.446651
G NE APARTMENT DIRECT AIR 0.077334
G N1 APARTMENT DIRECT AIR 0.055298
G N2 APARTMENT DIRECT AIR 0.054348
G S1 APARTMENT DIRECT AIR 0.115890
G S2 APARTMENT DIRECT AIR 0.119219
M SW APARTMENT DIRECT AIR 0.440467
M NW APARTMENT DIRECT AIR 0.324298
M SE APARTMENT DIRECT AIR 0.416122
M NE APARTMENT DIRECT AIR 0.251036
M N1 APARTMENT DIRECT AIR 0.182217
M N2 APARTMENT DIRECT AIR 0.180418
M S1 APARTMENT DIRECT AIR 0.342317
M S2 APARTMENT DIRECT AIR 0.343638
T SW APARTMENT DIRECT AIR 0.287390
T NW APARTMENT DIRECT AIR 0.207441
T SE APARTMENT DIRECT AIR 0.271749
T NE APARTMENT DIRECT AIR 0.156320
T N1 APARTMENT DIRECT AIR 0.121709
T N2 APARTMENT DIRECT AIR 0.122054
T S1 APARTMENT DIRECT AIR 0.236001
T S2 APARTMENT DIRECT AIR 0.236930


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.154115
SPLIT GNW MAIN BRANCH 0.110610
SPLIT OFFICE MAIN BRANCH 0.446651
SPLIT GNE MAIN BRANCH 0.077334
SPLIT GN1 MAIN BRANCH 0.055298
SPLIT GN2 MAIN BRANCH 0.054348
SPLIT GS1 MAIN BRANCH 0.115890
SPLIT GS2 MAIN BRANCH 0.119219
SPLIT MSW MAIN BRANCH 0.440467
SPLIT MNW MAIN BRANCH 0.324298
SPLIT MSE MAIN BRANCH 0.416122
SPLIT MNE MAIN BRANCH 0.251036
SPLIT MN1 MAIN BRANCH 0.182217
SPLIT MN2 MAIN BRANCH 0.180418
SPLIT MS1 MAIN BRANCH 0.342317
SPLIT MS2 MAIN BRANCH 0.343638
SPLIT TSW MAIN BRANCH 0.287390
SPLIT TNW MAIN BRANCH 0.207441
SPLIT TSE MAIN BRANCH 0.271749
SPLIT TNE MAIN BRANCH 0.156320
SPLIT TN1 MAIN BRANCH 0.121709
SPLIT TN2 MAIN BRANCH 0.122054
SPLIT TS1 MAIN BRANCH 0.236001
SPLIT TS2 MAIN BRANCH 0.236930


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.154115
SPLIT GNW 0.110610
SPLIT OFFICE 0.446651
SPLIT GNE 0.077334
SPLIT GN1 0.055298
SPLIT GN2 0.054348
SPLIT GS1 0.115890
SPLIT GS2 0.119219
SPLIT MSW 0.440467
SPLIT MNW 0.324298
SPLIT MSE 0.416122
SPLIT MNE 0.251036
SPLIT MN1 0.182217
SPLIT MN2 0.180418
SPLIT MS1 0.342317
SPLIT MS2 0.343638
SPLIT TSW 0.287390
SPLIT TNW 0.207441
SPLIT TSE 0.271749
SPLIT TNE 0.156320
SPLIT TN1 0.121709
SPLIT TN2 0.122054
SPLIT TS1 0.236001
SPLIT TS2 0.236930


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.154115 0.026898
SPLIT GNW OA CONTROLLER 0.110610 0.025953
SPLIT OFFICE OA CONTROLLER 0.446651 0.038104
SPLIT GNE OA CONTROLLER 0.077334 0.025953
SPLIT GN1 OA CONTROLLER 0.055298 0.025953
SPLIT GN2 OA CONTROLLER 0.054348 0.025953
SPLIT GS1 OA CONTROLLER 0.115890 0.025953
SPLIT GS2 OA CONTROLLER 0.119219 0.025953
SPLIT MSW OA CONTROLLER 0.440467 0.051906
SPLIT MNW OA CONTROLLER 0.324298 0.051906
SPLIT MSE OA CONTROLLER 0.416122 0.051906
SPLIT MNE OA CONTROLLER 0.251036 0.051906
SPLIT MN1 OA CONTROLLER 0.182217 0.051906
SPLIT MN2 OA CONTROLLER 0.180418 0.051906
SPLIT MS1 OA CONTROLLER 0.342317 0.051906
SPLIT MS2 OA CONTROLLER 0.343638 0.051906
SPLIT TSW OA CONTROLLER 0.287390 0.025953
SPLIT TNW OA CONTROLLER 0.207441 0.025953
SPLIT TSE OA CONTROLLER 0.271749 0.025953
SPLIT TNE OA CONTROLLER 0.156320 0.025953
SPLIT TN1 OA CONTROLLER 0.121709 0.025953
SPLIT TN2 OA CONTROLLER 0.122054 0.025953
SPLIT TS1 OA CONTROLLER 0.236001 0.025953
SPLIT TS2 OA CONTROLLER 0.236930 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.154115 2568.25 0.796207
SPLIT GNW COOLING COIL 0.110610 1866.51 0.791657
SPLIT OFFICE COOLING COIL 0.446651 7393.65 0.798655
SPLIT GNE COOLING COIL 0.077334 1348.41 0.780042
SPLIT GN1 COOLING COIL 0.055298 970.11 0.777911
SPLIT GN2 COOLING COIL 0.054348 954.76 0.777435
SPLIT GS1 COOLING COIL 0.115890 1970.28 0.788972
SPLIT GS2 COOLING COIL 0.119219 2017.85 0.790575
SPLIT MSW COOLING COIL 0.440467 7291.30 0.798655
SPLIT MNW COOLING COIL 0.324298 5368.28 0.798655
SPLIT MSE COOLING COIL 0.416122 6888.30 0.798655
SPLIT MNE COOLING COIL 0.251036 4182.29 0.796303
SPLIT MN1 COOLING COIL 0.182217 3077.63 0.791333
SPLIT MN2 COOLING COIL 0.180418 3049.51 0.791065
SPLIT MS1 COOLING COIL 0.342317 5666.57 0.798655
SPLIT MS2 COOLING COIL 0.343638 5688.44 0.798655
SPLIT TSW COOLING COIL 0.287390 4757.33 0.798655
SPLIT TNW COOLING COIL 0.207441 3433.89 0.798655
SPLIT TSE COOLING COIL 0.271749 4498.41 0.798655
SPLIT TNE COOLING COIL 0.156320 2607.38 0.795875
SPLIT TN1 COOLING COIL 0.121709 2084.42 0.786360
SPLIT TN2 COOLING COIL 0.122054 2094.07 0.785726
SPLIT TS1 COOLING COIL 0.236001 3906.65 0.798655
SPLIT TS2 COOLING COIL 0.236930 3922.03 0.798655


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.154115 0.154115 0.154115 0.154115 2433.05 2568.25 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.110610 0.110610 0.110610 0.110610 2403.16 1866.51 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.446651 0.446651 0.446651 0.446651 4464.75 7393.65 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.077334 0.077334 0.077334 0.077334 2408.34 1348.41 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.055298 0.055298 0.055298 0.055298 1812.18 970.11 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.054348 0.054348 0.054348 0.054348 1812.31 954.76 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.115890 0.115890 0.115890 0.115890 1811.39 1970.28 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.119219 0.119219 0.119219 0.119219 1913.31 2017.85 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.440467 0.440467 0.440467 0.440467 4675.60 7291.30 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.324298 0.324298 0.324298 0.324298 4678.55 5368.28 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.416122 0.416122 0.416122 0.416122 4689.48 6888.30 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.251036 0.251036 0.251036 0.251036 4692.43 4182.29 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.182217 0.182217 0.182217 0.182217 3579.58 3077.63 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.180418 0.180418 0.180418 0.180418 3579.58 3049.51 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.342317 0.342317 0.342317 0.342317 3579.58 5666.57 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.343638 0.343638 0.343638 0.343638 3579.58 5688.44 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.287390 0.287390 0.287390 0.287390 3565.16 4757.33 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.207441 0.207441 0.207441 0.207441 3568.35 3433.89 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.271749 0.271749 0.271749 0.271749 3572.43 4498.41 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.156320 0.156320 0.156320 0.156320 3575.62 2607.38 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.121709 0.121709 0.121709 0.121709 2761.13 2084.42 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.122054 0.122054 0.122054 0.122054 2761.33 2094.07 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.236001 0.236001 0.236001 0.236001 2756.13 3906.65 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.236930 0.236930 0.236930 0.236930 2756.34 3922.03 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.154115
SPLIT GNW SUPPLY FAN 0.110610
SPLIT OFFICE SUPPLY FAN 0.446651
SPLIT GNE SUPPLY FAN 0.077334
SPLIT GN1 SUPPLY FAN 0.055298
SPLIT GN2 SUPPLY FAN 0.054348
SPLIT GS1 SUPPLY FAN 0.115890
SPLIT GS2 SUPPLY FAN 0.119219
SPLIT MSW SUPPLY FAN 0.440467
SPLIT MNW SUPPLY FAN 0.324298
SPLIT MSE SUPPLY FAN 0.416122
SPLIT MNE SUPPLY FAN 0.251036
SPLIT MN1 SUPPLY FAN 0.182217
SPLIT MN2 SUPPLY FAN 0.180418
SPLIT MS1 SUPPLY FAN 0.342317
SPLIT MS2 SUPPLY FAN 0.343638
SPLIT TSW SUPPLY FAN 0.287390
SPLIT TNW SUPPLY FAN 0.207441
SPLIT TSE SUPPLY FAN 0.271749
SPLIT TNE SUPPLY FAN 0.156320
SPLIT TN1 SUPPLY FAN 0.121709
SPLIT TN2 SUPPLY FAN 0.122054
SPLIT TS1 SUPPLY FAN 0.236001
SPLIT TS2 SUPPLY FAN 0.236930


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 2433.05
SPLIT GNW HEATING COIL 2403.16
SPLIT OFFICE HEATING COIL 4464.75
SPLIT GNE HEATING COIL 2408.34
SPLIT GN1 HEATING COIL 1812.18
SPLIT GN2 HEATING COIL 1812.31
SPLIT GS1 HEATING COIL 1811.39
SPLIT GS2 HEATING COIL 1913.31
SPLIT MSW HEATING COIL 4675.60
SPLIT MNW HEATING COIL 4678.55
SPLIT MSE HEATING COIL 4689.48
SPLIT MNE HEATING COIL 4692.43
SPLIT MN1 HEATING COIL 3579.58
SPLIT MN2 HEATING COIL 3579.58
SPLIT MS1 HEATING COIL 3579.58
SPLIT MS2 HEATING COIL 3579.58
SPLIT TSW HEATING COIL 3565.16
SPLIT TNW HEATING COIL 3568.35
SPLIT TSE HEATING COIL 3572.43
SPLIT TNE HEATING COIL 3575.62
SPLIT TN1 HEATING COIL 2761.13
SPLIT TN2 HEATING COIL 2761.33
SPLIT TS1 HEATING COIL 2756.13
SPLIT TS2 HEATING COIL 2756.34



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.77 5.10
March 21.86 6.09
April 22.16 8.68
May 22.49 11.83
June 23.81 15.06
July 24.15 16.98
August 24.18 17.08
September 23.66 13.78
October 22.02 9.83
November 21.74 5.28
December 21.70 3.63
     
Annual Sum or Average 22.61 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.18 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.73 6.09
April 21.84 8.68
May 22.14 11.83
June 23.61 15.06
July 24.05 16.98
August 24.03 17.08
September 23.21 13.78
October 21.76 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.43 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.05 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 3.20
February 21.59 5.10
March 21.79 6.09
April 22.64 8.68
May 23.34 11.83
June 24.92 15.06
July 25.51 16.98
August 25.45 17.08
September 24.81 13.78
October 22.72 9.83
November 21.36 5.28
December 20.59 3.63
     
Annual Sum or Average 22.97 9.74
Minimum of Months 20.59 3.20
Maximum of Months 25.51 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.71 6.09
April 21.80 8.68
May 22.02 11.83
June 23.51 15.06
July 24.01 16.98
August 23.99 17.08
September 23.11 13.78
October 21.75 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.40 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.01 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.71 6.09
April 21.75 8.68
May 21.91 11.83
June 23.45 15.06
July 23.99 16.98
August 23.98 17.08
September 23.17 13.78
October 21.75 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.38 9.74
Minimum of Months 21.70 3.20
Maximum of Months 23.99 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.71 6.09
April 21.75 8.68
May 21.90 11.83
June 23.44 15.06
July 23.98 16.98
August 23.97 17.08
September 23.16 13.78
October 21.75 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.38 9.74
Minimum of Months 21.70 3.20
Maximum of Months 23.98 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.78 5.10
March 21.85 6.09
April 22.11 8.68
May 22.35 11.83
June 23.82 15.06
July 24.18 16.98
August 24.24 17.08
September 23.83 13.78
October 22.09 9.83
November 21.75 5.28
December 21.71 3.63
     
Annual Sum or Average 22.62 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.24 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.78 5.10
March 21.85 6.09
April 22.12 8.68
May 22.38 11.83
June 23.85 15.06
July 24.20 16.98
August 24.26 17.08
September 23.86 13.78
October 22.11 9.83
November 21.75 5.28
December 21.70 3.63
     
Annual Sum or Average 22.64 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.26 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 3.20
February 22.11 5.10
March 22.48 6.09
April 23.38 8.68
May 24.10 11.83
June 24.36 15.06
July 24.40 16.98
August 24.40 17.08
September 24.13 13.78
October 22.90 9.83
November 21.95 5.28
December 21.72 3.63
     
Annual Sum or Average 23.14 9.74
Minimum of Months 21.72 3.20
Maximum of Months 24.40 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.71 5.10
March 21.97 6.09
April 22.47 8.68
May 23.85 11.83
June 24.32 15.06
July 24.39 16.98
August 24.38 17.08
September 23.88 13.78
October 22.15 9.83
November 21.71 5.28
December 21.70 3.63
     
Annual Sum or Average 22.86 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.39 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 3.20
February 22.08 5.10
March 22.44 6.09
April 23.30 8.68
May 24.08 11.83
June 24.35 15.06
July 24.40 16.98
August 24.40 17.08
September 24.13 13.78
October 22.90 9.83
November 21.94 5.28
December 21.72 3.63
     
Annual Sum or Average 23.13 9.74
Minimum of Months 21.72 3.20
Maximum of Months 24.40 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.90 6.09
April 22.34 8.68
May 23.75 11.83
June 24.29 15.06
July 24.38 16.98
August 24.37 17.08
September 23.81 13.78
October 22.12 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.82 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.38 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.71 5.10
March 21.95 6.09
April 22.43 8.68
May 23.94 11.83
June 24.35 15.06
July 24.39 16.98
August 24.39 17.08
September 24.00 13.78
October 22.35 9.83
November 21.73 5.28
December 21.70 3.63
     
Annual Sum or Average 22.89 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.39 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.71 5.10
March 21.95 6.09
April 22.41 8.68
May 23.93 11.83
June 24.35 15.06
July 24.39 16.98
August 24.39 17.08
September 23.99 13.78
October 22.35 9.83
November 21.73 5.28
December 21.70 3.63
     
Annual Sum or Average 22.89 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.39 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 3.20
February 22.43 5.10
March 22.63 6.09
April 23.61 8.68
May 24.25 11.83
June 24.39 15.06
July 24.40 16.98
August 24.40 17.08
September 24.28 13.78
October 23.41 9.83
November 22.18 5.28
December 21.77 3.63
     
Annual Sum or Average 23.30 9.74
Minimum of Months 21.77 3.20
Maximum of Months 24.40 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.78 3.20
February 22.43 5.10
March 22.63 6.09
April 23.60 8.68
May 24.24 11.83
June 24.39 15.06
July 24.40 16.98
August 24.40 17.08
September 24.28 13.78
October 23.41 9.83
November 22.18 5.28
December 21.77 3.63
     
Annual Sum or Average 23.30 9.74
Minimum of Months 21.77 3.20
Maximum of Months 24.40 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 3.20
February 22.00 5.10
March 22.21 6.09
April 22.76 8.68
May 23.38 11.83
June 24.03 15.06
July 24.24 16.98
August 24.23 17.08
September 23.54 13.78
October 22.36 9.83
November 21.84 5.28
December 21.72 3.63
     
Annual Sum or Average 22.84 9.74
Minimum of Months 21.72 3.20
Maximum of Months 24.24 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.71 5.10
March 21.87 6.09
April 22.29 8.68
May 23.09 11.83
June 23.88 15.06
July 24.14 16.98
August 24.08 17.08
September 23.11 13.78
October 21.91 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.60 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.14 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 3.20
February 21.98 5.10
March 22.19 6.09
April 22.75 8.68
May 23.38 11.83
June 24.01 15.06
July 24.22 16.98
August 24.23 17.08
September 23.53 13.78
October 22.37 9.83
November 21.84 5.28
December 21.71 3.63
     
Annual Sum or Average 22.83 9.74
Minimum of Months 21.71 3.20
Maximum of Months 24.23 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.82 6.09
April 22.20 8.68
May 23.04 11.83
June 23.81 15.06
July 24.05 16.98
August 24.01 17.08
September 23.04 13.78
October 21.88 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.56 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.05 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.82 6.09
April 22.18 8.68
May 23.09 11.83
June 23.93 15.06
July 24.16 16.98
August 24.11 17.08
September 23.11 13.78
October 21.89 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.60 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.16 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 3.20
February 21.70 5.10
March 21.82 6.09
April 22.17 8.68
May 23.09 11.83
June 23.92 15.06
July 24.15 16.98
August 24.10 17.08
September 23.11 13.78
October 21.90 9.83
November 21.70 5.28
December 21.70 3.63
     
Annual Sum or Average 22.59 9.74
Minimum of Months 21.70 3.20
Maximum of Months 24.15 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 3.20
February 22.06 5.10
March 22.27 6.09
April 22.85 8.68
May 23.54 11.83
June 24.14 15.06
July 24.31 16.98
August 24.31 17.08
September 23.72 13.78
October 22.51 9.83
November 21.88 5.28
December 21.74 3.63
     
Annual Sum or Average 22.93 9.74
Minimum of Months 21.73 3.20
Maximum of Months 24.31 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 3.20
February 22.06 5.10
March 22.27 6.09
April 22.85 8.68
May 23.53 11.83
June 24.14 15.06
July 24.30 16.98
August 24.31 17.08
September 23.72 13.78
October 22.51 9.83
November 21.88 5.28
December 21.74 3.63
     
Annual Sum or Average 22.92 9.74
Minimum of Months 21.73 3.20
Maximum of Months 24.31 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.19 3.20
February 21.79 5.10
March 22.16 6.09
April 23.22 8.68
May 24.45 11.83
June 25.57 15.06
July 26.00 16.98
August 25.87 17.08
September 24.61 13.78
October 22.63 9.83
November 21.52 5.28
December 21.14 3.63
     
Annual Sum or Average 23.35 9.74
Minimum of Months 21.14 3.20
Maximum of Months 26.00 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.99 3.20
February 19.54 5.10
March 19.84 6.09
April 20.66 8.68
May 21.60 11.83
June 23.74 15.06
July 24.65 16.98
August 24.61 17.08
September 23.50 13.78
October 20.87 9.83
November 19.55 5.28
December 19.01 3.63
     
Annual Sum or Average 21.39 9.74
Minimum of Months 18.99 3.20
Maximum of Months 24.65 17.08



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:48:11

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.79 3.20
February 23.37 5.10
March 23.64 6.09
April 24.68 8.68
May 25.93 11.83
June 26.45 15.06
July 26.63 16.98
August 26.57 17.08
September 26.06 13.78
October 24.26 9.83
November 23.11 5.28
December 22.67 3.63
     
Annual Sum or Average 24.69 9.74
Minimum of Months 22.67 3.20
Maximum of Months 26.63 17.08



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:11

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.111728E+12 71988.302 05-JAN-18:15 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 31725.877 0.000 0.000 0.000
February 0.100890E+12 71708.716 12-FEB-18:45 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 31446.291 0.000 0.000 0.000
March 0.111299E+12 71344.389 01-MAR-18:30 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 31081.964 0.000 0.000 0.000
April 0.107612E+12 71333.872 29-APR-17:45 4979.953 26630.920 6098.551 0.000 8009.198 0.000 0.000 0.000 0.000 0.000 0.000 25615.248 0.000 0.000 0.000
May 0.111537E+12 68950.495 28-MAY-17:00 4979.953 26630.920 6098.551 0.000 5177.389 0.000 0.000 0.000 0.000 0.000 0.000 26063.681 0.000 0.000 0.000
June 0.110289E+12 74257.522 23-JUN-17:15 4979.953 26630.920 6098.551 0.000 10938.109 0.000 0.000 0.000 0.000 0.000 0.000 25609.988 0.000 0.000 0.000
July 0.117864E+12 73937.577 12-JUL-17:00 4979.953 26630.920 6098.551 0.000 12658.825 0.000 0.000 0.000 0.000 0.000 0.000 23569.327 0.000 0.000 0.000
August 0.116906E+12 71282.703 01-AUG-17:30 4979.953 26630.920 6098.551 0.000 9810.198 0.000 0.000 0.000 0.000 0.000 0.000 23763.080 0.000 0.000 0.000
September 0.108536E+12 68908.882 13-SEP-17:15 4979.953 26630.920 6098.551 0.000 11220.903 0.000 0.000 0.000 0.000 0.000 0.000 19978.554 0.000 0.000 0.000
October 0.109101E+12 65768.620 10-OCT-17:45 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 25506.194 0.000 0.000 0.000
November 0.106332E+12 66024.546 11-NOV-18:30 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 25762.121 0.000 0.000 0.000
December 0.111057E+12 70594.067 28-DEC-18:15 4979.953 26630.920 6098.551 0.000 0.000 2553.000 0.000 0.000 0.000 0.000 0.000 30331.642 0.000 0.000 0.000
                                     
Annual Sum or Average 0.132315E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.100890E+12 65768.620   4979.953 26630.920 6098.551 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 19978.554 0.000 0.000 0.000
Maximum of Months 0.117864E+12 74257.522   4979.953 26630.920 6098.551 0.000 12658.825 2553.000 0.000 0.000 0.000 0.000 0.000 31725.877 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:11

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.781011E+11 55907.196 09-JAN-16:00 55907.196 0.000 0.000 0.000 0.000 0.000 55907.196
February 0.434960E+11 68592.062 17-FEB-16:00 68592.062 0.000 0.000 0.000 0.000 0.000 68592.062
March 0.453018E+11 55051.180 20-MAR-00:00 55051.180 0.000 0.000 0.000 0.000 0.000 55051.180
April 0.169953E+11 64425.458 15-APR-04:00 64425.458 0.000 0.000 0.000 0.000 0.000 64425.458
May 0.425025E+10 16323.893 06-MAY-03:00 16323.893 0.000 0.000 0.000 0.000 0.000 16323.893
June 0.699858E+08 3225.046 16-JUN-02:00 3225.046 0.000 0.000 0.000 0.000 0.000 3225.046
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.179504E+10 13148.009 29-SEP-03:00 13148.009 0.000 0.000 0.000 0.000 0.000 13148.009
October 0.188248E+11 41869.671 28-OCT-04:00 41869.671 0.000 0.000 0.000 0.000 0.000 41869.671
November 0.580666E+11 67068.927 20-NOV-17:00 67068.927 0.000 0.000 0.000 0.000 0.000 67068.927
December 0.878617E+11 80290.915 16-DEC-16:00 80290.915 0.000 0.000 0.000 0.000 0.000 80290.915
                     
Annual Sum or Average 0.354762E+12       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.878617E+11 80290.915   80290.915 0.000 0.000 0.000 0.000 0.000 80290.915