Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2015-09-09 18:48:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1615.80 | 515.47 | 572.17 |
Net Site Energy | 1615.80 | 515.47 | 572.17 |
Total Source Energy | 4636.33 | 1479.07 | 1641.77 |
Net Source Energy | 4636.33 | 1479.07 | 1641.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 230.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 76.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 229.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 402.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1384.93 | 230.87 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 230.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 76.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 229.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 402.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 250.96 | 81.75 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 490.42 | 81.75 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 226.09 | 73.65 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 441.82 | 73.65 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1384.93 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1384.93 | 100.00 |
Total On-Site and Utility Electric Sources | 1384.93 | 100.00 |
Total Electricity End Uses | 1384.93 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 79.75 |
Time Setpoint Not Met During Occupied Cooling | 17.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 580.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48 |
RunPeriod | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [m] | 60.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-JUL-16:15 | 20-DEC-04:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 78565.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23107.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7266.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22867.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 84248.10 | 78565.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 78565.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23107.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 3538.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 738.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7266.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 22867.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 250.27 | 0.00 | 0.00 | 0.00 |
Cooling | 242.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 725.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1275.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4386.06 | 250.27 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 88.62 | 0.00 | 0.00 | 0.00 |
Cooling | 86.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 256.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 451.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1553.15 | 88.62 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 88.62 | 0.00 | 0.00 | 0.00 |
Cooling | 86.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 256.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 451.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1553.15 | 88.62 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00 | -5.60 | Wetbulb [C] | 2.10 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 15.40 | 19.40 | Wetbulb [C] | 4.30 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.68 | 83.68 | 40.10 | |
Exterior Lighting Total | 2553.00 | 40.10 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3245.56 | 2536.40 | 709.16 | 0.78 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2507.69 | 1987.76 | 519.92 | 0.79 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7684.46 | 6137.24 | 1547.23 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1736.80 | 1360.14 | 376.66 | 0.78 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1322.93 | 1035.81 | 287.12 | 0.78 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1305.08 | 1021.18 | 283.91 | 0.78 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2388.64 | 1833.85 | 554.79 | 0.77 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2438.77 | 1874.71 | 564.06 | 0.77 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8582.99 | 6808.54 | 1774.45 | 0.79 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6775.78 | 5411.51 | 1364.27 | 0.80 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8143.90 | 6399.50 | 1744.40 | 0.79 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5072.00 | 4038.80 | 1033.20 | 0.80 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3783.21 | 3006.79 | 776.42 | 0.79 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3752.42 | 2981.42 | 771.00 | 0.79 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6540.08 | 5091.66 | 1448.42 | 0.78 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6557.94 | 5106.20 | 1451.74 | 0.78 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5777.49 | 4594.72 | 1182.76 | 0.80 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4559.44 | 3641.42 | 918.02 | 0.80 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5438.17 | 4304.37 | 1133.80 | 0.79 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3786.67 | 2960.48 | 826.19 | 0.78 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2986.63 | 2318.59 | 668.04 | 0.78 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2984.28 | 2316.70 | 667.58 | 0.78 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4602.08 | 3628.31 | 973.76 | 0.79 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4614.03 | 3638.00 | 976.03 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3099.0 | 3.16 | 10.77 | 11.20 | 10.52 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2390.9 | 3.14 | 10.71 | 11.13 | 10.43 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7320.7 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1658.0 | 3.15 | 10.76 | 11.19 | 10.51 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1262.9 | 3.15 | 10.76 | 11.19 | 10.51 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1246.0 | 3.16 | 10.77 | 11.19 | 10.52 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2284.9 | 3.18 | 10.85 | 11.29 | 10.64 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2332.6 | 3.18 | 10.85 | 11.28 | 10.63 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8182.5 | 3.14 | 10.70 | 11.12 | 10.42 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6455.0 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7771.6 | 3.15 | 10.75 | 11.17 | 10.49 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4833.4 | 3.13 | 10.68 | 11.10 | 10.40 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3606.0 | 3.13 | 10.69 | 11.11 | 10.41 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3576.7 | 3.13 | 10.70 | 11.11 | 10.41 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6247.2 | 3.16 | 10.79 | 11.22 | 10.55 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6264.2 | 3.16 | 10.79 | 11.22 | 10.55 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5506.4 | 3.13 | 10.69 | 11.11 | 10.41 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4343.6 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5185.7 | 3.14 | 10.71 | 11.13 | 10.44 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3615.5 | 3.16 | 10.77 | 11.20 | 10.52 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2853.7 | 3.17 | 10.80 | 11.23 | 10.57 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2851.5 | 3.17 | 10.80 | 11.23 | 10.57 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4390.2 | 3.15 | 10.73 | 11.15 | 10.46 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4401.6 | 3.14 | 10.73 | 11.15 | 10.46 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2140.09 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2117.83 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 3966.80 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2117.83 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1733.86 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1733.86 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1733.86 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1733.86 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 4028.96 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 4048.78 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 4028.96 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 4048.78 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 3467.71 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 3467.71 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 3467.71 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 3467.71 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 3146.11 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 3158.16 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 3146.11 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 3158.16 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 2472.26 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 2472.26 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 2458.18 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 2458.18 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.19 | 216.98 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 172.99 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.46 | 538.88 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 116.65 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 88.81 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.08 | 87.49 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 153.42 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.14 | 157.09 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.51 | 593.06 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.41 | 475.16 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 551.14 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 353.39 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.23 | 262.50 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 260.19 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 433.53 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.37 | 434.83 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 401.44 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.28 | 319.74 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 373.95 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 253.38 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 196.72 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 196.55 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 313.73 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 314.60 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1975.19 | 2370.23 | 0.156 | 0.187 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 32.61 | 0.00850 |
G NW APARTMENT | 1574.78 | 1889.74 | 0.124 | 0.149 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.60 | 0.00850 |
OFFICE | 4803.48 | 5764.18 | 0.387 | 0.464 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.83 | 0.00850 |
G NE APARTMENT | 1061.89 | 1274.27 | 0.084 | 0.100 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
G N1 APARTMENT | 808.50 | 970.20 | 0.064 | 0.077 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
G N2 APARTMENT | 796.44 | 955.73 | 0.063 | 0.075 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
G S1 APARTMENT | 1396.63 | 1675.95 | 0.110 | 0.132 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
G S2 APARTMENT | 1430.06 | 1716.07 | 0.113 | 0.135 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
M SW APARTMENT | 5398.75 | 6478.50 | 0.426 | 0.511 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 32.07 | 0.00850 |
M NW APARTMENT | 4325.51 | 5190.61 | 0.341 | 0.409 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.60 | 0.00850 |
M SE APARTMENT | 5017.11 | 6020.53 | 0.396 | 0.475 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 33.11 | 0.00850 |
M NE APARTMENT | 3217.01 | 3860.41 | 0.254 | 0.304 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
M N1 APARTMENT | 2389.62 | 2867.54 | 0.188 | 0.226 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
M N2 APARTMENT | 2368.60 | 2842.32 | 0.187 | 0.224 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 27.87 | 0.00850 |
M S1 APARTMENT | 3946.51 | 4735.81 | 0.311 | 0.373 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
M S2 APARTMENT | 3958.39 | 4750.07 | 0.312 | 0.375 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
T SW APARTMENT | 3654.33 | 4385.19 | 0.288 | 0.346 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 32.84 | 0.00850 |
T NW APARTMENT | 2910.61 | 3492.73 | 0.230 | 0.275 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.14 | 0.00850 |
T SE APARTMENT | 3404.11 | 4084.93 | 0.268 | 0.322 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
T NE APARTMENT | 2306.58 | 2767.89 | 0.182 | 0.218 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.30 | 0.00850 |
T N1 APARTMENT | 1790.77 | 2148.93 | 0.141 | 0.169 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.07 | 0.00850 |
T N2 APARTMENT | 1789.25 | 2147.10 | 0.141 | 0.169 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.07 | 0.00850 |
T S1 APARTMENT | 2855.96 | 3427.15 | 0.225 | 0.270 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 33.30 | 0.00850 |
T S2 APARTMENT | 2863.84 | 3436.61 | 0.226 | 0.271 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.30 | 0.00850 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1063.62 | 1276.34 | 0.031 | 0.037 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G NW APARTMENT | 1071.03 | 1285.23 | 0.031 | 0.037 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
OFFICE | 2352.50 | 2823.00 | 0.066 | 0.079 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G NE APARTMENT | 1071.03 | 1285.23 | 0.031 | 0.037 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G N1 APARTMENT | 632.08 | 758.50 | 0.018 | 0.026 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G N2 APARTMENT | 632.08 | 758.50 | 0.018 | 0.026 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G S1 APARTMENT | 626.15 | 751.38 | 0.018 | 0.026 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
G S2 APARTMENT | 704.83 | 845.80 | 0.020 | 0.026 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.60 | 0.00237 |
M SW APARTMENT | 1967.32 | 2360.78 | 0.057 | 0.068 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M NW APARTMENT | 1984.08 | 2380.89 | 0.057 | 0.069 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M SE APARTMENT | 1967.32 | 2360.78 | 0.057 | 0.068 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M NE APARTMENT | 1984.08 | 2380.89 | 0.057 | 0.069 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M N1 APARTMENT | 889.03 | 1066.83 | 0.026 | 0.052 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M N2 APARTMENT | 889.03 | 1066.83 | 0.026 | 0.052 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M S1 APARTMENT | 873.70 | 1048.44 | 0.025 | 0.052 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
M S2 APARTMENT | 873.70 | 1048.44 | 0.025 | 0.052 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T SW APARTMENT | 1940.64 | 2328.77 | 0.056 | 0.067 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T NW APARTMENT | 1950.84 | 2341.00 | 0.057 | 0.068 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T SE APARTMENT | 1940.64 | 2328.77 | 0.056 | 0.067 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T NE APARTMENT | 1950.84 | 2341.00 | 0.057 | 0.068 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T N1 APARTMENT | 1370.77 | 1644.93 | 0.040 | 0.048 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T N2 APARTMENT | 1370.77 | 1644.93 | 0.040 | 0.048 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T S1 APARTMENT | 1358.86 | 1630.64 | 0.039 | 0.047 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
T S2 APARTMENT | 1358.86 | 1630.64 | 0.039 | 0.047 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -5.60 | 0.00237 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.19 | 0.19 | 0.04 | 0.04 |
SPLIT GNW | 0.15 | 0.15 | 0.04 | 0.04 |
SPLIT OFFICE | 0.46 | 0.46 | 0.08 | 0.08 |
SPLIT GNE | 0.10 | 0.10 | 0.04 | 0.04 |
SPLIT GN1 | 0.08 | 0.08 | 0.03 | 0.03 |
SPLIT GN2 | 0.08 | 0.08 | 0.03 | 0.03 |
SPLIT GS1 | 0.13 | 0.13 | 0.03 | 0.03 |
SPLIT GS2 | 0.14 | 0.14 | 0.03 | 0.03 |
SPLIT MSW | 0.51 | 0.51 | 0.07 | 0.07 |
SPLIT MNW | 0.41 | 0.41 | 0.07 | 0.07 |
SPLIT MSE | 0.47 | 0.47 | 0.07 | 0.07 |
SPLIT MNE | 0.30 | 0.30 | 0.07 | 0.07 |
SPLIT MN1 | 0.23 | 0.23 | 0.05 | 0.05 |
SPLIT MN2 | 0.22 | 0.22 | 0.05 | 0.05 |
SPLIT MS1 | 0.37 | 0.37 | 0.05 | 0.05 |
SPLIT MS2 | 0.37 | 0.37 | 0.05 | 0.05 |
SPLIT TSW | 0.35 | 0.35 | 0.07 | 0.07 |
SPLIT TNW | 0.28 | 0.28 | 0.07 | 0.07 |
SPLIT TSE | 0.32 | 0.32 | 0.07 | 0.07 |
SPLIT TNE | 0.22 | 0.22 | 0.07 | 0.07 |
SPLIT TN1 | 0.17 | 0.17 | 0.05 | 0.05 |
SPLIT TN2 | 0.17 | 0.17 | 0.05 | 0.05 |
SPLIT TS1 | 0.27 | 0.27 | 0.05 | 0.05 |
SPLIT TS2 | 0.27 | 0.27 | 0.05 | 0.05 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 1583.00 | 6173.00 | 167.50 |
G NW APARTMENT | 1229.00 | 6538.50 | 254.25 |
OFFICE | 359.25 | 1512.50 | 24.00 |
G NE APARTMENT | 1203.75 | 6657.25 | 245.00 |
G N1 APARTMENT | 694.50 | 6741.75 | 147.75 |
G N2 APARTMENT | 688.50 | 6758.25 | 147.50 |
G S1 APARTMENT | 1212.25 | 6197.25 | 88.50 |
G S2 APARTMENT | 1310.75 | 6131.75 | 96.75 |
M SW APARTMENT | 2899.75 | 4041.50 | 27.25 |
M NW APARTMENT | 2591.75 | 4833.00 | 106.00 |
M SE APARTMENT | 2856.50 | 4120.50 | 24.50 |
M NE APARTMENT | 2533.25 | 4965.25 | 106.25 |
M N1 APARTMENT | 2327.00 | 4759.00 | 38.25 |
M N2 APARTMENT | 2322.75 | 4778.25 | 38.75 |
M S1 APARTMENT | 2781.25 | 3713.25 | 0.00 |
M S2 APARTMENT | 2781.75 | 3722.00 | 0.00 |
T SW APARTMENT | 2611.75 | 5200.25 | 375.25 |
T NW APARTMENT | 2445.50 | 5837.50 | 552.25 |
T SE APARTMENT | 2612.25 | 5262.25 | 377.00 |
T NE APARTMENT | 2408.25 | 5919.50 | 547.50 |
T N1 APARTMENT | 2078.00 | 5864.75 | 322.50 |
T N2 APARTMENT | 2077.50 | 5872.00 | 322.50 |
T S1 APARTMENT | 2379.00 | 5035.75 | 201.00 |
T S2 APARTMENT | 2378.50 | 5041.50 | 201.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 3773.50 | 6875.00 | 580.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
G NW APARTMENT | 9.25 | 0.00 | 9.25 | 0.00 |
OFFICE | 3.50 | 2.00 | 0.00 | 0.00 |
G NE APARTMENT | 10.75 | 13.25 | 10.75 | 13.25 |
G N1 APARTMENT | 11.00 | 15.00 | 11.00 | 15.00 |
G N2 APARTMENT | 9.50 | 15.25 | 9.50 | 15.25 |
G S1 APARTMENT | 8.75 | 0.00 | 8.75 | 0.00 |
G S2 APARTMENT | 9.00 | 0.00 | 9.00 | 0.00 |
M SW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M NW APARTMENT | 7.25 | 0.00 | 7.25 | 0.00 |
M SE APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
M NE APARTMENT | 10.00 | 6.25 | 10.00 | 6.25 |
M N1 APARTMENT | 2.00 | 9.50 | 2.00 | 9.50 |
M N2 APARTMENT | 2.00 | 11.50 | 2.00 | 11.50 |
M S1 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
M S2 APARTMENT | 1.00 | 0.00 | 1.00 | 0.00 |
T SW APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
T NW APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
T SE APARTMENT | 3.25 | 0.00 | 3.25 | 0.00 |
T NE APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
T N1 APARTMENT | 3.25 | 0.25 | 3.25 | 0.25 |
T N2 APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
T S1 APARTMENT | 1.25 | 0.00 | 1.25 | 0.00 |
T S2 APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 83.25 | 19.50 | 79.75 | 17.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.365 | 0.153 | 0.000 | 0.068 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.153 | 0.000 | 0.067 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.176 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.153 | 0.000 | 0.067 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.092 | 0.000 | 0.066 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.092 | 0.000 | 0.066 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.092 | 0.000 | 0.068 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.092 | 0.000 | 0.068 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.221 | 0.000 | 0.081 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.082 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.221 | 0.000 | 0.081 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.220 | 0.000 | 0.081 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.081 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.081 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.081 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.133 | 0.000 | 0.081 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.292 | 0.000 | 0.092 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.291 | 0.000 | 0.093 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.291 | 0.000 | 0.092 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.291 | 0.000 | 0.093 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.176 | 0.000 | 0.093 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.352 | 0.176 | 0.000 | 0.093 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.092 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.092 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.500 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.363 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.341 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 402.84 | 0.00 | 01-JAN-00:15 | 32482.32 | 05-FEB-07:45 |
WaterSystems:Electricity | 402.84 | 0.00 | 01-JAN-00:15 | 32482.32 | 05-FEB-07:45 |
Water Heater:WaterSystems:Electricity | 402.84 | 0.00 | 01-JAN-00:15 | 32482.32 | 05-FEB-07:45 |
Fans:Electricity | 229.15 | 7266.23 | 01-JAN-17:15 | 7266.23 | 03-JAN-08:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
ElectricityPurchased:Plant | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
Cogeneration:ElectricityPurchased | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
ElectricityNet:Plant | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
Cogeneration:ElectricityNet | 1384.93 | 20378.84 | 01-JAN-03:15 | 84248.10 | 18-JUL-16:15 |
ExteriorLights:Electricity | 40.10 | 0.00 | 01-JAN-08:00 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.10 | 0.00 | 01-JAN-08:00 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 305.87 | 7266.23 | 01-JAN-17:15 | 31871.43 | 17-JUL-16:00 |
General:Fans:Electricity | 229.15 | 7266.23 | 01-JAN-17:15 | 7266.23 | 03-JAN-08:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 76.72 | 0.00 | 01-JAN-00:15 | 24605.20 | 17-JUL-16:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 230.87 | 0.00 | 21-FEB-13:45 | 78565.15 | 20-DEC-05:00 |
Gas:HVAC | 230.87 | 0.00 | 21-FEB-13:45 | 78565.15 | 20-DEC-05:00 |
Heating:Gas | 230.87 | 0.00 | 21-FEB-13:45 | 78565.15 | 20-DEC-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 931.60 | 1534.97 | 10-NOV-12:15 | 157195.94 | 19-JUL-16:00 |
EnergyTransfer:Building | 439.37 | 1534.97 | 10-NOV-12:15 | 66474.15 | 19-JUL-16:00 |
EnergyTransfer:Zone:G SW APARTMENT | 10.26 | 0.00 | 30-JUN-15:30 | 2121.88 | 09-SEP-15:15 |
Heating:EnergyTransfer | 99.03 | 0.00 | 15-JAN-18:45 | 49879.44 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 3.79 | 0.00 | 01-JAN-09:45 | 1676.68 | 15-FEB-02:00 |
Cooling:EnergyTransfer | 340.34 | 0.00 | 03-JAN-07:30 | 66474.15 | 19-JUL-16:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 6.47 | 0.00 | 01-JAN-00:15 | 2121.88 | 09-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 9.46 | 0.01 | 04-OCT-08:45 | 1903.86 | 15-JUL-18:00 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 4.91 | 0.00 | 15-JAN-16:15 | 1642.03 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 4.55 | 0.00 | 01-JAN-00:15 | 1903.86 | 15-JUL-18:00 |
EnergyTransfer:Zone:OFFICE | 20.28 | 0.00 | 17-AUG-04:45 | 4500.45 | 10-SEP-13:00 |
Heating:EnergyTransfer:Zone:OFFICE | 1.57 | 0.00 | 01-JAN-00:15 | 2495.56 | 24-DEC-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 18.70 | 0.00 | 02-JAN-07:45 | 4500.45 | 10-SEP-13:00 |
EnergyTransfer:Zone:G NE APARTMENT | 9.53 | 0.04 | 06-OCT-15:45 | 1587.70 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 4.91 | 0.00 | 15-JAN-16:15 | 1587.70 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 4.62 | 0.00 | 01-JAN-00:15 | 1303.07 | 16-JUL-18:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 6.55 | 0.03 | 15-OCT-04:15 | 1005.37 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 2.09 | 0.00 | 02-JAN-19:30 | 1005.37 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 4.46 | 0.00 | 01-JAN-00:15 | 980.35 | 15-JUL-19:15 |
EnergyTransfer:Zone:G N2 APARTMENT | 6.54 | 0.01 | 15-OCT-04:15 | 1005.56 | 15-FEB-02:00 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 2.09 | 0.00 | 02-JAN-19:30 | 1005.56 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 4.45 | 0.00 | 01-JAN-00:15 | 965.58 | 16-JUL-19:30 |
EnergyTransfer:Zone:G S1 APARTMENT | 7.69 | 0.01 | 10-NOV-13:15 | 1455.41 | 09-SEP-13:45 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.36 | 0.00 | 01-JAN-08:45 | 980.81 | 15-FEB-02:15 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 6.33 | 0.00 | 01-JAN-00:15 | 1455.41 | 09-SEP-13:45 |
EnergyTransfer:Zone:G S2 APARTMENT | 7.96 | 0.01 | 28-DEC-17:45 | 1548.87 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 1.45 | 0.00 | 01-JAN-09:00 | 1029.17 | 15-FEB-02:15 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 6.51 | 0.00 | 01-JAN-00:15 | 1548.87 | 09-SEP-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 33.69 | 0.14 | 26-OCT-11:30 | 5864.35 | 09-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 3.93 | 0.00 | 01-JAN-00:15 | 3422.37 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 29.76 | 0.00 | 01-JAN-02:30 | 5864.35 | 09-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 27.03 | 0.00 | 06-OCT-08:45 | 5363.03 | 24-JUN-18:15 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 5.88 | 0.00 | 01-JAN-17:30 | 3332.97 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 21.15 | 0.00 | 01-JAN-00:15 | 5363.03 | 24-JUN-18:15 |
EnergyTransfer:Zone:M SE APARTMENT | 33.14 | 0.01 | 09-NOV-21:00 | 5209.49 | 09-SEP-13:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 3.95 | 0.00 | 01-JAN-00:15 | 3385.83 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 29.19 | 0.00 | 01-JAN-02:30 | 5209.49 | 09-SEP-13:30 |
EnergyTransfer:Zone:M NE APARTMENT | 26.95 | 0.06 | 07-APR-06:45 | 3940.14 | 24-JUN-18:45 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 5.92 | 0.00 | 01-JAN-09:30 | 3203.97 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 21.03 | 0.00 | 01-JAN-00:15 | 3940.14 | 24-JUN-18:45 |
EnergyTransfer:Zone:M N1 APARTMENT | 23.02 | 0.23 | 19-NOV-22:00 | 2985.80 | 24-JUN-19:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 1.28 | 0.00 | 01-JAN-06:30 | 2065.80 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 21.74 | 0.00 | 01-JAN-00:15 | 2985.80 | 24-JUN-19:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 22.96 | 0.23 | 09-DEC-04:45 | 2959.47 | 24-JUN-19:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 1.28 | 0.00 | 01-JAN-06:30 | 2066.24 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 21.67 | 0.00 | 01-JAN-00:15 | 2959.47 | 24-JUN-19:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 31.57 | 0.06 | 13-JAN-01:30 | 4242.08 | 09-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.67 | 0.00 | 01-JAN-00:15 | 1939.88 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 30.90 | 0.00 | 03-JAN-05:45 | 4242.08 | 09-SEP-14:15 |
EnergyTransfer:Zone:M S2 APARTMENT | 31.52 | 0.17 | 12-DEC-13:45 | 4245.36 | 09-SEP-14:15 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.67 | 0.00 | 01-JAN-00:15 | 1940.22 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 30.84 | 0.00 | 03-JAN-05:45 | 4245.36 | 09-SEP-14:15 |
EnergyTransfer:Zone:T SW APARTMENT | 20.11 | 0.02 | 02-MAY-23:00 | 3964.04 | 17-JUL-16:15 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 8.08 | 0.00 | 01-JAN-10:00 | 2960.65 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 12.03 | 0.00 | 01-JAN-00:15 | 3964.04 | 17-JUL-16:15 |
EnergyTransfer:Zone:T NW APARTMENT | 18.15 | 0.00 | 28-JUN-02:15 | 3575.88 | 24-JUN-18:00 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 9.63 | 0.00 | 15-JAN-17:45 | 2892.92 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 8.52 | 0.00 | 01-JAN-00:15 | 3575.88 | 24-JUN-18:00 |
EnergyTransfer:Zone:T SE APARTMENT | 19.62 | 0.01 | 27-JUL-04:45 | 3448.38 | 09-SEP-13:45 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 8.00 | 0.00 | 01-JAN-09:30 | 2935.59 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 11.61 | 0.00 | 01-JAN-00:15 | 3448.38 | 09-SEP-13:45 |
EnergyTransfer:Zone:T NE APARTMENT | 17.94 | 0.01 | 15-OCT-15:00 | 2867.29 | 17-JUL-16:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 9.59 | 0.00 | 15-JAN-17:15 | 2820.89 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 8.35 | 0.00 | 01-JAN-00:15 | 2867.29 | 17-JUL-16:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 12.80 | 0.03 | 08-AUG-09:45 | 2229.47 | 17-JUL-17:45 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 5.13 | 0.00 | 14-JAN-18:45 | 2005.20 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 7.66 | 0.00 | 01-JAN-00:15 | 2229.47 | 17-JUL-17:45 |
EnergyTransfer:Zone:T N2 APARTMENT | 12.79 | 0.01 | 19-OCT-12:30 | 2221.14 | 17-JUL-17:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 5.15 | 0.00 | 14-JAN-18:45 | 2005.61 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 7.64 | 0.00 | 01-JAN-00:15 | 2221.14 | 17-JUL-17:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 14.91 | 0.00 | 12-NOV-15:30 | 2909.78 | 09-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 3.83 | 0.00 | 01-JAN-09:30 | 1988.02 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 11.09 | 0.00 | 01-JAN-00:15 | 2909.78 | 09-SEP-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 14.91 | 0.02 | 27-OCT-10:30 | 2910.96 | 09-SEP-13:45 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 3.83 | 0.00 | 01-JAN-09:30 | 1988.24 | 15-FEB-02:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 11.07 | 0.00 | 01-JAN-00:15 | 2910.96 | 09-SEP-13:45 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 492.23 | 0.00 | 13-APR-19:45 | 90851.59 | 19-JUL-15:45 |
HeatingCoils:EnergyTransfer | 184.70 | 0.00 | 21-FEB-13:45 | 62852.12 | 20-DEC-05:00 |
CoolingCoils:EnergyTransfer | 307.54 | 0.00 | 01-JAN-00:15 | 90851.59 | 19-JUL-15:45 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 3.789 | -6.473 | 0.000 | 0.000 | 3.870 | 1.087 | 12.213 | 12.588 | 0.000 | 0.138 | 0.000 | 0.000 | -6.864 | 0.000 | -5.527 | -14.819 |
G NW APARTMENT | 4.914 | -4.551 | 0.000 | 0.000 | 3.897 | 1.087 | 12.213 | 6.884 | 0.000 | 0.139 | 0.000 | 0.000 | -6.887 | 0.000 | -5.398 | -12.298 |
OFFICE | 1.575 | -18.702 | 0.000 | 0.000 | 0.521 | 26.452 | 9.482 | 11.778 | 0.000 | 0.075 | 0.001 | 0.000 | -6.948 | 0.000 | -4.882 | -19.350 |
G NE APARTMENT | 4.914 | -4.621 | 0.000 | 0.000 | 3.912 | 1.087 | 12.213 | 6.255 | 0.000 | 0.139 | 0.000 | 0.000 | -6.715 | 0.000 | -5.368 | -11.815 |
G N1 APARTMENT | 2.091 | -4.459 | 0.000 | 0.000 | 3.910 | 1.087 | 12.213 | 2.388 | 0.000 | 0.094 | 0.000 | 0.000 | -4.199 | 0.000 | -3.522 | -9.602 |
G N2 APARTMENT | 2.092 | -4.450 | 0.000 | 0.000 | 3.911 | 1.087 | 12.213 | 2.388 | 0.000 | 0.094 | 0.000 | 0.000 | -4.197 | 0.000 | -3.521 | -9.616 |
G S1 APARTMENT | 1.357 | -6.333 | 0.000 | 0.000 | 3.870 | 1.087 | 12.213 | 8.138 | 0.000 | 0.091 | 0.000 | 0.000 | -4.183 | 0.000 | -3.667 | -12.574 |
G S2 APARTMENT | 1.448 | -6.514 | 0.000 | 0.000 | 3.867 | 1.087 | 12.213 | 8.132 | 0.000 | 0.091 | 0.000 | 0.000 | -4.188 | 0.000 | -3.675 | -12.461 |
M SW APARTMENT | 3.934 | -29.756 | 0.000 | 0.000 | 3.729 | 1.087 | 12.213 | 12.138 | 0.000 | 0.194 | 12.128 | 0.000 | -7.581 | 0.000 | -8.084 | -0.001 |
M NW APARTMENT | 5.878 | -21.148 | 0.000 | 0.000 | 3.781 | 1.087 | 12.213 | 6.498 | 0.000 | 0.196 | 6.920 | 0.000 | -7.512 | 0.000 | -7.912 | -0.000 |
M SE APARTMENT | 3.953 | -29.189 | 0.000 | 0.000 | 3.737 | 1.087 | 12.213 | 11.526 | 0.000 | 0.194 | 11.974 | 0.000 | -7.427 | 0.000 | -8.068 | -0.001 |
M NE APARTMENT | 5.922 | -21.025 | 0.000 | 0.000 | 3.798 | 1.087 | 12.213 | 5.867 | 0.000 | 0.195 | 7.121 | 0.000 | -7.308 | 0.000 | -7.869 | -0.001 |
M N1 APARTMENT | 1.280 | -21.738 | 0.000 | 0.000 | 3.773 | 1.087 | 12.213 | 2.145 | 0.000 | 0.128 | 10.959 | 0.000 | -4.648 | 0.000 | -5.199 | -0.000 |
M N2 APARTMENT | 1.283 | -21.675 | 0.000 | 0.000 | 3.775 | 1.087 | 12.213 | 2.146 | 0.000 | 0.128 | 10.883 | 0.000 | -4.644 | 0.000 | -5.196 | -0.000 |
M S1 APARTMENT | 0.672 | -30.902 | 0.000 | 0.000 | 3.698 | 1.087 | 12.213 | 7.849 | 0.000 | 0.127 | 15.295 | 0.000 | -4.672 | 0.000 | -5.366 | 0.000 |
M S2 APARTMENT | 0.672 | -30.844 | 0.000 | 0.000 | 3.698 | 1.087 | 12.213 | 7.849 | 0.000 | 0.127 | 15.234 | 0.000 | -4.670 | 0.000 | -5.366 | 0.000 |
T SW APARTMENT | 8.081 | -12.026 | 0.000 | 0.000 | 3.810 | 1.087 | 12.213 | 12.085 | 0.000 | 0.255 | 0.000 | 0.000 | -7.109 | 0.000 | -10.228 | -8.167 |
T NW APARTMENT | 9.633 | -8.520 | 0.000 | 0.000 | 3.850 | 1.087 | 12.213 | 6.478 | 0.000 | 0.257 | 0.000 | 0.000 | -7.070 | 0.000 | -10.045 | -7.883 |
T SE APARTMENT | 8.004 | -11.611 | 0.000 | 0.000 | 3.818 | 1.087 | 12.213 | 11.495 | 0.000 | 0.255 | 0.000 | 0.000 | -6.979 | 0.000 | -10.220 | -8.062 |
T NE APARTMENT | 9.590 | -8.347 | 0.000 | 0.000 | 3.868 | 1.087 | 12.213 | 5.873 | 0.000 | 0.257 | 0.000 | 0.000 | -6.899 | 0.000 | -10.009 | -7.633 |
T N1 APARTMENT | 5.135 | -7.660 | 0.000 | 0.000 | 3.852 | 1.087 | 12.213 | 2.171 | 0.000 | 0.170 | 0.000 | 0.000 | -4.334 | 0.000 | -6.488 | -6.145 |
T N2 APARTMENT | 5.149 | -7.637 | 0.000 | 0.000 | 3.853 | 1.087 | 12.213 | 2.170 | 0.000 | 0.170 | 0.000 | 0.000 | -4.330 | 0.000 | -6.488 | -6.186 |
T S1 APARTMENT | 3.827 | -11.086 | 0.000 | 0.000 | 3.793 | 1.087 | 12.213 | 7.837 | 0.000 | 0.167 | 0.000 | 0.000 | -4.375 | 0.000 | -6.671 | -6.792 |
T S2 APARTMENT | 3.835 | -11.073 | 0.000 | 0.000 | 3.793 | 1.087 | 12.213 | 7.836 | 0.000 | 0.167 | 0.000 | 0.000 | -4.372 | 0.000 | -6.672 | -6.814 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.085 | 0.000 | 0.014 | 0.000 | 0.000 | -0.854 | 0.000 | -1.668 | -12.159 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.321 | 0.000 | 0.430 | 7.350 | 0.000 | -2.196 | 0.000 | -26.966 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.084 | 0.000 | 0.013 | 0.000 | 0.000 | -0.946 | 0.000 | -1.385 | -12.348 |
Total Facility | 99.027 | -340.341 | 0.000 | 0.000 | 88.384 | 95.189 | 296.854 | 171.006 | 0.000 | 4.308 | 97.864 | 0.000 | -142.107 | 0.000 | -185.460 | -184.727 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-SEP-15:15 | 0.00 | -2121.91 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2657.62 | 0.00 | 241.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1342.30 |
G NW APARTMENT | 15-JUL-18:00 | 0.00 | -1903.96 | 0.00 | 0.00 | 141.37 | 87.56 | 588.62 | 1977.22 | 0.00 | 208.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1099.47 |
OFFICE | 17-SEP-06:01 | 0.00 | -7390.76 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 298.71 | 0.00 | 0.00 | 6381.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G NE APARTMENT | 16-JUL-18:45 | 0.00 | -1303.34 | 0.00 | 0.00 | 140.77 | 103.77 | 547.42 | 638.84 | 0.00 | 107.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -235.13 |
G N1 APARTMENT | 15-JUL-19:15 | 0.00 | -980.48 | 0.00 | 0.00 | 140.16 | 103.77 | 523.87 | 510.87 | 0.00 | 80.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -378.72 |
G N2 APARTMENT | 16-JUL-19:30 | 0.00 | -965.68 | 0.00 | 0.00 | 140.79 | 103.77 | 523.87 | 334.79 | 0.00 | 45.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -182.67 |
G S1 APARTMENT | 09-SEP-13:45 | 0.00 | -1455.49 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1921.21 | 0.00 | 134.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1036.21 |
G S2 APARTMENT | 09-SEP-13:30 | 0.00 | -1548.95 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2002.79 | 0.00 | 131.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1021.87 |
M SW APARTMENT | 09-SEP-15:15 | 0.00 | -5864.41 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2639.16 | 0.00 | 346.15 | 2313.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 24-JUN-18:15 | 0.00 | -5362.76 | 0.00 | 0.00 | 141.56 | 103.77 | 547.42 | 1999.80 | 0.00 | 325.00 | 2245.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 09-SEP-13:30 | 0.00 | -5209.73 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2279.62 | 0.00 | 313.06 | 2180.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 24-JUN-18:45 | 0.00 | -3940.01 | 0.00 | 0.00 | 141.29 | 103.77 | 547.42 | 766.32 | 0.00 | 250.85 | 2130.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 24-JUN-19:30 | 0.00 | -2985.97 | 0.00 | 0.00 | 140.90 | 103.77 | 523.87 | 514.58 | 0.00 | 97.42 | 1605.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 24-JUN-19:30 | 0.00 | -2959.64 | 0.00 | 0.00 | 140.86 | 103.77 | 523.87 | 514.67 | 0.00 | 97.34 | 1579.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 09-SEP-14:15 | 0.00 | -4242.27 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1720.95 | 0.00 | 198.24 | 1859.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 09-SEP-14:15 | 0.00 | -4245.55 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1720.92 | 0.00 | 198.24 | 1862.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 17-JUL-16:03 | 0.00 | -3965.20 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2168.84 | 0.00 | 475.71 | 582.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 15-JUL-17:03 | 0.00 | -3595.39 | 0.00 | 0.00 | 141.73 | 87.56 | 588.62 | 2024.54 | 0.00 | 463.98 | 288.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 09-SEP-13:45 | 0.00 | -3448.53 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2161.30 | 0.00 | 419.92 | 431.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 17-JUL-16:20 | 0.00 | -2868.18 | 0.00 | 0.00 | 84.05 | 64.86 | 588.62 | 706.79 | 0.00 | 446.04 | 977.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 16-JUL-17:19 | 0.00 | -2255.73 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 457.55 | 0.00 | 134.13 | 846.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 16-JUL-17:03 | 0.00 | -2230.88 | 0.00 | 0.00 | 141.65 | 87.56 | 588.62 | 416.06 | 0.00 | 134.48 | 862.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 09-SEP-14:15 | 0.00 | -2909.89 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1700.45 | 0.00 | 261.04 | 484.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 09-SEP-13:45 | 0.00 | -2911.09 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1888.95 | 0.00 | 253.29 | 332.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUL-16:00 | 0.00 | -66478.73 | 0.00 | 0.00 | 1187.56 | 4512.09 | 11708.34 | 23866.13 | 0.00 | 10034.55 | 15170.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 15-FEB-02:00 | 1676.72 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -571.04 | 0.00 | -1224.25 | -318.92 |
G NW APARTMENT | 15-FEB-02:00 | 1642.07 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -555.01 | 0.00 | -1221.48 | -303.08 |
OFFICE | 09-FEB-07:01 | 3706.94 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -337.42 | 0.00 | -412.36 | -3667.62 |
G NE APARTMENT | 29-OCT-16:01 | 1795.72 | 0.00 | 0.00 | 0.00 | 99.87 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.09 | 0.00 | -71.91 | -2196.07 |
G N1 APARTMENT | 10-MAR-17:01 | 1458.01 | 0.00 | 0.00 | 0.00 | 99.73 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -119.69 | 0.00 | -124.81 | -1966.73 |
G N2 APARTMENT | 01-MAR-07:01 | 1415.48 | 0.00 | 0.00 | 0.00 | 163.49 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -152.44 | 0.00 | -135.02 | -1716.28 |
G S1 APARTMENT | 15-NOV-07:01 | 1434.43 | 0.00 | 0.00 | 0.00 | 163.26 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -134.77 | 0.00 | -152.04 | -1735.64 |
G S2 APARTMENT | 15-NOV-07:01 | 1437.28 | 0.00 | 0.00 | 0.00 | 163.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -134.83 | 0.00 | -152.09 | -1738.33 |
M SW APARTMENT | 15-FEB-02:00 | 3422.47 | 0.00 | 0.00 | 0.00 | 190.44 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -593.01 | 0.00 | -1739.90 | -1527.82 |
M NW APARTMENT | 15-FEB-02:00 | 3333.07 | 0.00 | 0.00 | 0.00 | 191.91 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -571.28 | 0.00 | -1722.47 | -1479.05 |
M SE APARTMENT | 15-FEB-02:00 | 3385.93 | 0.00 | 0.00 | 0.00 | 190.61 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -592.70 | 0.00 | -1736.47 | -1495.20 |
M NE APARTMENT | 25-NOV-07:01 | 3465.01 | 0.00 | 0.00 | 0.00 | 162.84 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -371.61 | 0.00 | -199.85 | -3481.15 |
M N1 APARTMENT | 04-MAR-07:01 | 2463.36 | 0.00 | 0.00 | 0.00 | 161.37 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.86 | 0.00 | -256.72 | -2520.91 |
M N2 APARTMENT | 19-DEC-07:03 | 2080.60 | 0.00 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -409.99 | 0.00 | -105.57 | -2151.03 |
M S1 APARTMENT | 15-FEB-02:00 | 1939.93 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -363.35 | 0.00 | -1063.44 | -950.63 |
M S2 APARTMENT | 15-FEB-02:00 | 1940.27 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -363.34 | 0.00 | -1063.44 | -950.97 |
T SW APARTMENT | 15-FEB-02:00 | 2960.74 | 0.00 | 0.00 | 0.00 | 190.34 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -575.19 | 0.00 | -2308.99 | -514.72 |
T NW APARTMENT | 15-FEB-02:00 | 2893.01 | 0.00 | 0.00 | 0.00 | 190.90 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -556.17 | 0.00 | -2297.17 | -478.39 |
T SE APARTMENT | 15-FEB-02:00 | 2935.68 | 0.00 | 0.00 | 0.00 | 190.51 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -574.88 | 0.00 | -2304.94 | -494.19 |
T NE APARTMENT | 15-FEB-02:00 | 2820.98 | 0.00 | 0.00 | 0.00 | 191.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -554.91 | 0.00 | -2284.88 | -420.67 |
T N1 APARTMENT | 15-FEB-02:00 | 2005.25 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -332.28 | 0.00 | -1409.29 | -701.17 |
T N2 APARTMENT | 15-FEB-02:00 | 2005.66 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -332.28 | 0.00 | -1409.29 | -701.58 |
T S1 APARTMENT | 15-FEB-02:00 | 1988.08 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.58 | 0.00 | -1409.29 | -664.69 |
T S2 APARTMENT | 15-FEB-02:00 | 1988.29 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -351.58 | 0.00 | -1409.29 | -664.91 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-FEB-02:00 | 49699.60 | 0.00 | 0.00 | 0.00 | 4374.74 | 1952.47 | 5793.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11188.91 | 0.00 | -34507.66 | -16123.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Sec1.1A-General InformationData | |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 79.75 |
Number of hours cooling loads not met | 17.50 |
Number of hours not met | 97.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 230.87 | 78565.15 | 0.00 | 0.00 |
Space Cooling | 76.72 | 23107.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 229.15 | 7266.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 402.84 | 22867.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1384.93 | 230.87 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1384.93 |
Natural Gas | 0.00 | 230.87 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1615.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 24.48 |
Fans-Interior | 73.10 |
Service Water Heating | 128.51 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.79 |
Subtotal | 441.82 |
Natural Gas [MJ/m2] | |
Space Heating | 73.65 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 73.65 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.33 |
Space Heating | 14.29 |
Space Cooling | 4.75 |
Fans-Interior | 14.18 |
Service Water Heating | 24.93 |
Receptacle Equipment | 32.04 |
Miscellaneous | 2.48 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.186914 |
G NW APARTMENT DIRECT AIR | 0.149022 |
OFFICE DIRECT AIR | 0.464218 |
G NE APARTMENT DIRECT AIR | 0.100489 |
G N1 APARTMENT DIRECT AIR | 0.076508 |
G N2 APARTMENT DIRECT AIR | 0.075368 |
G S1 APARTMENT DIRECT AIR | 0.132164 |
G S2 APARTMENT DIRECT AIR | 0.135328 |
M SW APARTMENT DIRECT AIR | 0.510889 |
M NW APARTMENT DIRECT AIR | 0.409325 |
M SE APARTMENT DIRECT AIR | 0.474774 |
M NE APARTMENT DIRECT AIR | 0.304431 |
M N1 APARTMENT DIRECT AIR | 0.226130 |
M N2 APARTMENT DIRECT AIR | 0.224142 |
M S1 APARTMENT DIRECT AIR | 0.373461 |
M S2 APARTMENT DIRECT AIR | 0.374585 |
T SW APARTMENT DIRECT AIR | 0.345815 |
T NW APARTMENT DIRECT AIR | 0.275436 |
T SE APARTMENT DIRECT AIR | 0.322136 |
T NE APARTMENT DIRECT AIR | 0.218275 |
T N1 APARTMENT DIRECT AIR | 0.169463 |
T N2 APARTMENT DIRECT AIR | 0.169319 |
T S1 APARTMENT DIRECT AIR | 0.270262 |
T S2 APARTMENT DIRECT AIR | 0.271008 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.186914 |
SPLIT GNW MAIN BRANCH | 0.149022 |
SPLIT OFFICE MAIN BRANCH | 0.464218 |
SPLIT GNE MAIN BRANCH | 0.100489 |
SPLIT GN1 MAIN BRANCH | 0.076508 |
SPLIT GN2 MAIN BRANCH | 0.075368 |
SPLIT GS1 MAIN BRANCH | 0.132164 |
SPLIT GS2 MAIN BRANCH | 0.135328 |
SPLIT MSW MAIN BRANCH | 0.510889 |
SPLIT MNW MAIN BRANCH | 0.409325 |
SPLIT MSE MAIN BRANCH | 0.474774 |
SPLIT MNE MAIN BRANCH | 0.304431 |
SPLIT MN1 MAIN BRANCH | 0.226130 |
SPLIT MN2 MAIN BRANCH | 0.224142 |
SPLIT MS1 MAIN BRANCH | 0.373461 |
SPLIT MS2 MAIN BRANCH | 0.374585 |
SPLIT TSW MAIN BRANCH | 0.345815 |
SPLIT TNW MAIN BRANCH | 0.275436 |
SPLIT TSE MAIN BRANCH | 0.322136 |
SPLIT TNE MAIN BRANCH | 0.218275 |
SPLIT TN1 MAIN BRANCH | 0.169463 |
SPLIT TN2 MAIN BRANCH | 0.169319 |
SPLIT TS1 MAIN BRANCH | 0.270262 |
SPLIT TS2 MAIN BRANCH | 0.271008 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.186914 |
SPLIT GNW | 0.149022 |
SPLIT OFFICE | 0.464218 |
SPLIT GNE | 0.100489 |
SPLIT GN1 | 0.076508 |
SPLIT GN2 | 0.075368 |
SPLIT GS1 | 0.132164 |
SPLIT GS2 | 0.135328 |
SPLIT MSW | 0.510889 |
SPLIT MNW | 0.409325 |
SPLIT MSE | 0.474774 |
SPLIT MNE | 0.304431 |
SPLIT MN1 | 0.226130 |
SPLIT MN2 | 0.224142 |
SPLIT MS1 | 0.373461 |
SPLIT MS2 | 0.374585 |
SPLIT TSW | 0.345815 |
SPLIT TNW | 0.275436 |
SPLIT TSE | 0.322136 |
SPLIT TNE | 0.218275 |
SPLIT TN1 | 0.169463 |
SPLIT TN2 | 0.169319 |
SPLIT TS1 | 0.270262 |
SPLIT TS2 | 0.271008 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.186914 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.149022 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.464218 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.100489 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.076508 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.075368 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.132164 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.135328 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.510889 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.409325 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.474774 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.304431 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.226130 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.224142 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.373461 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.374585 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.345815 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.275436 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.322136 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.218275 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.169463 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.169319 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.270262 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.271008 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.186914 | 3245.56 | 0.781498 |
SPLIT GNW COOLING COIL | 0.149022 | 2507.69 | 0.792668 |
SPLIT OFFICE COOLING COIL | 0.464218 | 7684.46 | 0.798655 |
SPLIT GNE COOLING COIL | 0.100489 | 1736.80 | 0.783129 |
SPLIT GN1 COOLING COIL | 0.076508 | 1322.93 | 0.782970 |
SPLIT GN2 COOLING COIL | 0.075368 | 1305.08 | 0.782462 |
SPLIT GS1 COOLING COIL | 0.132164 | 2388.64 | 0.767740 |
SPLIT GS2 COOLING COIL | 0.135328 | 2438.77 | 0.768713 |
SPLIT MSW COOLING COIL | 0.510889 | 8582.99 | 0.793260 |
SPLIT MNW COOLING COIL | 0.409325 | 6775.78 | 0.798655 |
SPLIT MSE COOLING COIL | 0.474774 | 8143.90 | 0.785803 |
SPLIT MNE COOLING COIL | 0.304431 | 5072.00 | 0.796293 |
SPLIT MN1 COOLING COIL | 0.226130 | 3783.21 | 0.794772 |
SPLIT MN2 COOLING COIL | 0.224142 | 3752.42 | 0.794532 |
SPLIT MS1 COOLING COIL | 0.373461 | 6540.08 | 0.778531 |
SPLIT MS2 COOLING COIL | 0.374585 | 6557.94 | 0.778629 |
SPLIT TSW COOLING COIL | 0.345815 | 5777.49 | 0.795281 |
SPLIT TNW COOLING COIL | 0.275436 | 4559.44 | 0.798655 |
SPLIT TSE COOLING COIL | 0.322136 | 5438.17 | 0.791511 |
SPLIT TNE COOLING COIL | 0.218275 | 3786.67 | 0.781816 |
SPLIT TN1 COOLING COIL | 0.169463 | 2986.63 | 0.776323 |
SPLIT TN2 COOLING COIL | 0.169319 | 2984.28 | 0.776301 |
SPLIT TS1 COOLING COIL | 0.270262 | 4602.08 | 0.788407 |
SPLIT TS2 COOLING COIL | 0.271008 | 4614.03 | 0.788465 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.186914 | 0.186914 | 0.186914 | 0.186914 | 2140.09 | 3245.56 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.149022 | 0.149022 | 0.149022 | 0.149022 | 2117.83 | 2507.69 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.464218 | 0.464218 | 0.464218 | 0.464218 | 3966.80 | 7684.46 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.100489 | 0.100489 | 0.100489 | 0.100489 | 2117.83 | 1736.80 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.076508 | 0.076508 | 0.076508 | 0.076508 | 1733.86 | 1322.93 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.075368 | 0.075368 | 0.075368 | 0.075368 | 1733.86 | 1305.08 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.132164 | 0.132164 | 0.132164 | 0.132164 | 1733.86 | 2388.64 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.135328 | 0.135328 | 0.135328 | 0.135328 | 1733.86 | 2438.77 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.510889 | 0.510889 | 0.510889 | 0.510889 | 4028.96 | 8582.99 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.409325 | 0.409325 | 0.409325 | 0.409325 | 4048.78 | 6775.78 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.474774 | 0.474774 | 0.474774 | 0.474774 | 4028.96 | 8143.90 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.304431 | 0.304431 | 0.304431 | 0.304431 | 4048.78 | 5072.00 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.226130 | 0.226130 | 0.226130 | 0.226130 | 3467.71 | 3783.21 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.224142 | 0.224142 | 0.224142 | 0.224142 | 3467.71 | 3752.42 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.373461 | 0.373461 | 0.373461 | 0.373461 | 3467.71 | 6540.08 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.374585 | 0.374585 | 0.374585 | 0.374585 | 3467.71 | 6557.94 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.345815 | 0.345815 | 0.345815 | 0.345815 | 3146.11 | 5777.49 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.275436 | 0.275436 | 0.275436 | 0.275436 | 3158.16 | 4559.44 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.322136 | 0.322136 | 0.322136 | 0.322136 | 3146.11 | 5438.17 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.218275 | 0.218275 | 0.218275 | 0.218275 | 3158.16 | 3786.67 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.169463 | 0.169463 | 0.169463 | 0.169463 | 2472.26 | 2986.63 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.169319 | 0.169319 | 0.169319 | 0.169319 | 2472.26 | 2984.28 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.270262 | 0.270262 | 0.270262 | 0.270262 | 2458.18 | 4602.08 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.271008 | 0.271008 | 0.271008 | 0.271008 | 2458.18 | 4614.03 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.186914 |
SPLIT GNW SUPPLY FAN | 0.149022 |
SPLIT OFFICE SUPPLY FAN | 0.464218 |
SPLIT GNE SUPPLY FAN | 0.100489 |
SPLIT GN1 SUPPLY FAN | 0.076508 |
SPLIT GN2 SUPPLY FAN | 0.075368 |
SPLIT GS1 SUPPLY FAN | 0.132164 |
SPLIT GS2 SUPPLY FAN | 0.135328 |
SPLIT MSW SUPPLY FAN | 0.510889 |
SPLIT MNW SUPPLY FAN | 0.409325 |
SPLIT MSE SUPPLY FAN | 0.474774 |
SPLIT MNE SUPPLY FAN | 0.304431 |
SPLIT MN1 SUPPLY FAN | 0.226130 |
SPLIT MN2 SUPPLY FAN | 0.224142 |
SPLIT MS1 SUPPLY FAN | 0.373461 |
SPLIT MS2 SUPPLY FAN | 0.374585 |
SPLIT TSW SUPPLY FAN | 0.345815 |
SPLIT TNW SUPPLY FAN | 0.275436 |
SPLIT TSE SUPPLY FAN | 0.322136 |
SPLIT TNE SUPPLY FAN | 0.218275 |
SPLIT TN1 SUPPLY FAN | 0.169463 |
SPLIT TN2 SUPPLY FAN | 0.169319 |
SPLIT TS1 SUPPLY FAN | 0.270262 |
SPLIT TS2 SUPPLY FAN | 0.271008 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2140.09 |
SPLIT GNW HEATING COIL | 2117.83 |
SPLIT OFFICE HEATING COIL | 3966.80 |
SPLIT GNE HEATING COIL | 2117.83 |
SPLIT GN1 HEATING COIL | 1733.86 |
SPLIT GN2 HEATING COIL | 1733.86 |
SPLIT GS1 HEATING COIL | 1733.86 |
SPLIT GS2 HEATING COIL | 1733.86 |
SPLIT MSW HEATING COIL | 4028.96 |
SPLIT MNW HEATING COIL | 4048.78 |
SPLIT MSE HEATING COIL | 4028.96 |
SPLIT MNE HEATING COIL | 4048.78 |
SPLIT MN1 HEATING COIL | 3467.71 |
SPLIT MN2 HEATING COIL | 3467.71 |
SPLIT MS1 HEATING COIL | 3467.71 |
SPLIT MS2 HEATING COIL | 3467.71 |
SPLIT TSW HEATING COIL | 3146.11 |
SPLIT TNW HEATING COIL | 3158.16 |
SPLIT TSE HEATING COIL | 3146.11 |
SPLIT TNE HEATING COIL | 3158.16 |
SPLIT TN1 HEATING COIL | 2472.26 |
SPLIT TN2 HEATING COIL | 2472.26 |
SPLIT TS1 HEATING COIL | 2458.18 |
SPLIT TS2 HEATING COIL | 2458.18 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 4.90 |
February | 21.85 | 5.21 |
March | 22.10 | 8.41 |
April | 22.30 | 10.40 |
May | 22.76 | 13.39 |
June | 24.04 | 17.41 |
July | 24.28 | 20.12 |
August | 24.33 | 19.46 |
September | 24.18 | 16.66 |
October | 22.58 | 11.27 |
November | 21.81 | 8.49 |
December | 21.74 | 4.55 |
Annual Sum or Average | 22.82 | 11.73 |
Minimum of Months | 21.74 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.73 | 5.21 |
March | 21.82 | 8.41 |
April | 22.05 | 10.40 |
May | 22.53 | 13.39 |
June | 23.96 | 17.41 |
July | 24.25 | 20.12 |
August | 24.27 | 19.46 |
September | 23.99 | 16.66 |
October | 22.14 | 11.27 |
November | 21.72 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.66 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.27 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 4.90 |
February | 21.36 | 5.21 |
March | 22.62 | 8.41 |
April | 22.95 | 10.40 |
May | 23.72 | 13.39 |
June | 25.35 | 17.41 |
July | 25.99 | 20.12 |
August | 25.88 | 19.46 |
September | 25.72 | 16.66 |
October | 23.46 | 11.27 |
November | 22.29 | 8.49 |
December | 21.17 | 4.55 |
Annual Sum or Average | 23.51 | 11.73 |
Minimum of Months | 21.17 | 4.55 |
Maximum of Months | 25.99 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 21.77 | 8.41 |
April | 21.98 | 10.40 |
May | 22.42 | 13.39 |
June | 23.86 | 17.41 |
July | 24.21 | 20.12 |
August | 24.22 | 19.46 |
September | 23.92 | 16.66 |
October | 22.04 | 11.27 |
November | 21.70 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.61 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.22 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 21.75 | 8.41 |
April | 21.92 | 10.40 |
May | 22.30 | 13.39 |
June | 23.87 | 17.41 |
July | 24.21 | 20.12 |
August | 24.23 | 19.46 |
September | 23.94 | 16.66 |
October | 22.04 | 11.27 |
November | 21.71 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.59 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.23 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.90 |
February | 21.71 | 5.21 |
March | 21.75 | 8.41 |
April | 21.92 | 10.40 |
May | 22.29 | 13.39 |
June | 23.86 | 17.41 |
July | 24.20 | 20.12 |
August | 24.22 | 19.46 |
September | 23.94 | 16.66 |
October | 22.04 | 11.27 |
November | 21.71 | 8.49 |
December | 21.70 | 4.55 |
Annual Sum or Average | 22.59 | 11.73 |
Minimum of Months | 21.70 | 4.55 |
Maximum of Months | 24.22 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.90 |
February | 21.85 | 5.21 |
March | 22.08 | 8.41 |
April | 22.23 | 10.40 |
May | 22.66 | 13.39 |
June | 24.04 | 17.41 |
July | 24.28 | 20.12 |
August | 24.34 | 19.46 |
September | 24.23 | 16.66 |
October | 22.64 | 11.27 |
November | 21.84 | 8.49 |
December | 21.75 | 4.55 |
Annual Sum or Average | 22.81 | 11.73 |
Minimum of Months | 21.75 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 4.90 |
February | 21.85 | 5.21 |
March | 22.09 | 8.41 |
April | 22.25 | 10.40 |
May | 22.69 | 13.39 |
June | 24.07 | 17.41 |
July | 24.30 | 20.12 |
August | 24.35 | 19.46 |
September | 24.25 | 16.66 |
October | 22.66 | 11.27 |
November | 21.85 | 8.49 |
December | 21.75 | 4.55 |
Annual Sum or Average | 22.83 | 11.73 |
Minimum of Months | 21.75 | 4.55 |
Maximum of Months | 24.35 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.00 | 4.90 |
February | 22.15 | 5.21 |
March | 23.40 | 8.41 |
April | 23.59 | 10.40 |
May | 24.23 | 13.39 |
June | 24.39 | 17.41 |
July | 24.40 | 20.12 |
August | 24.40 | 19.46 |
September | 24.40 | 16.66 |
October | 23.95 | 11.27 |
November | 22.48 | 8.49 |
December | 21.91 | 4.55 |
Annual Sum or Average | 23.45 | 11.73 |
Minimum of Months | 21.91 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.90 |
February | 21.82 | 5.21 |
March | 22.78 | 8.41 |
April | 23.10 | 10.40 |
May | 24.14 | 13.39 |
June | 24.38 | 17.41 |
July | 24.39 | 20.12 |
August | 24.40 | 19.46 |
September | 24.37 | 16.66 |
October | 23.35 | 11.27 |
November | 21.95 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 23.19 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 4.90 |
February | 22.11 | 5.21 |
March | 23.35 | 8.41 |
April | 23.49 | 10.40 |
May | 24.21 | 13.39 |
June | 24.38 | 17.41 |
July | 24.39 | 20.12 |
August | 24.40 | 19.46 |
September | 24.39 | 16.66 |
October | 23.91 | 11.27 |
November | 22.42 | 8.49 |
December | 21.89 | 4.55 |
Annual Sum or Average | 23.42 | 11.73 |
Minimum of Months | 21.89 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.78 | 5.21 |
March | 22.63 | 8.41 |
April | 22.99 | 10.40 |
May | 24.05 | 13.39 |
June | 24.36 | 17.41 |
July | 24.39 | 20.12 |
August | 24.40 | 19.46 |
September | 24.35 | 16.66 |
October | 23.11 | 11.27 |
November | 21.85 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 23.12 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.90 |
February | 21.81 | 5.21 |
March | 22.83 | 8.41 |
April | 23.11 | 10.40 |
May | 24.20 | 13.39 |
June | 24.39 | 17.41 |
July | 24.40 | 20.12 |
August | 24.40 | 19.46 |
September | 24.38 | 16.66 |
October | 23.50 | 11.27 |
November | 22.06 | 8.49 |
December | 21.74 | 4.55 |
Annual Sum or Average | 23.22 | 11.73 |
Minimum of Months | 21.73 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 4.90 |
February | 21.80 | 5.21 |
March | 22.81 | 8.41 |
April | 23.09 | 10.40 |
May | 24.19 | 13.39 |
June | 24.39 | 17.41 |
July | 24.40 | 20.12 |
August | 24.40 | 19.46 |
September | 24.38 | 16.66 |
October | 23.46 | 11.27 |
November | 22.05 | 8.49 |
December | 21.74 | 4.55 |
Annual Sum or Average | 23.21 | 11.73 |
Minimum of Months | 21.73 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.90 |
February | 22.31 | 5.21 |
March | 23.69 | 8.41 |
April | 23.81 | 10.40 |
May | 24.31 | 13.39 |
June | 24.40 | 17.41 |
July | 24.40 | 20.12 |
August | 24.40 | 19.46 |
September | 24.40 | 16.66 |
October | 24.16 | 11.27 |
November | 22.91 | 8.49 |
December | 22.04 | 4.55 |
Annual Sum or Average | 23.59 | 11.73 |
Minimum of Months | 22.04 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 4.90 |
February | 22.31 | 5.21 |
March | 23.69 | 8.41 |
April | 23.80 | 10.40 |
May | 24.31 | 13.39 |
June | 24.40 | 17.41 |
July | 24.40 | 20.12 |
August | 24.40 | 19.46 |
September | 24.40 | 16.66 |
October | 24.16 | 11.27 |
November | 22.91 | 8.49 |
December | 22.04 | 4.55 |
Annual Sum or Average | 23.59 | 11.73 |
Minimum of Months | 22.04 | 4.55 |
Maximum of Months | 24.40 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.90 |
February | 22.02 | 5.21 |
March | 22.71 | 8.41 |
April | 23.00 | 10.40 |
May | 23.66 | 13.39 |
June | 24.20 | 17.41 |
July | 24.31 | 20.12 |
August | 24.34 | 19.46 |
September | 24.17 | 16.66 |
October | 23.04 | 11.27 |
November | 22.06 | 8.49 |
December | 21.86 | 4.55 |
Annual Sum or Average | 23.11 | 11.73 |
Minimum of Months | 21.86 | 4.55 |
Maximum of Months | 24.34 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 4.90 |
February | 21.81 | 5.21 |
March | 22.29 | 8.41 |
April | 22.69 | 10.40 |
May | 23.47 | 13.39 |
June | 24.12 | 17.41 |
July | 24.27 | 20.12 |
August | 24.28 | 19.46 |
September | 23.96 | 16.66 |
October | 22.57 | 11.27 |
November | 21.79 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.90 | 11.73 |
Minimum of Months | 21.72 | 4.55 |
Maximum of Months | 24.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 4.90 |
February | 22.00 | 5.21 |
March | 22.68 | 8.41 |
April | 22.97 | 10.40 |
May | 23.64 | 13.39 |
June | 24.17 | 17.41 |
July | 24.30 | 20.12 |
August | 24.33 | 19.46 |
September | 24.15 | 16.66 |
October | 23.02 | 11.27 |
November | 22.03 | 8.49 |
December | 21.85 | 4.55 |
Annual Sum or Average | 23.09 | 11.73 |
Minimum of Months | 21.85 | 4.55 |
Maximum of Months | 24.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.77 | 5.21 |
March | 22.22 | 8.41 |
April | 22.60 | 10.40 |
May | 23.39 | 13.39 |
June | 24.04 | 17.41 |
July | 24.23 | 20.12 |
August | 24.24 | 19.46 |
September | 23.90 | 16.66 |
October | 22.45 | 11.27 |
November | 21.74 | 8.49 |
December | 21.71 | 4.55 |
Annual Sum or Average | 22.84 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.24 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.77 | 5.21 |
March | 22.23 | 8.41 |
April | 22.66 | 10.40 |
May | 23.50 | 13.39 |
June | 24.14 | 17.41 |
July | 24.27 | 20.12 |
August | 24.27 | 19.46 |
September | 23.96 | 16.66 |
October | 22.52 | 11.27 |
November | 21.78 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.88 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.27 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 4.90 |
February | 21.77 | 5.21 |
March | 22.23 | 8.41 |
April | 22.65 | 10.40 |
May | 23.49 | 13.39 |
June | 24.13 | 17.41 |
July | 24.27 | 20.12 |
August | 24.27 | 19.46 |
September | 23.95 | 16.66 |
October | 22.51 | 11.27 |
November | 21.78 | 8.49 |
December | 21.72 | 4.55 |
Annual Sum or Average | 22.88 | 11.73 |
Minimum of Months | 21.71 | 4.55 |
Maximum of Months | 24.27 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 4.90 |
February | 22.06 | 5.21 |
March | 22.82 | 8.41 |
April | 23.12 | 10.40 |
May | 23.79 | 13.39 |
June | 24.26 | 17.41 |
July | 24.34 | 20.12 |
August | 24.37 | 19.46 |
September | 24.23 | 16.66 |
October | 23.21 | 11.27 |
November | 22.17 | 8.49 |
December | 21.90 | 4.55 |
Annual Sum or Average | 23.19 | 11.73 |
Minimum of Months | 21.90 | 4.55 |
Maximum of Months | 24.37 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.94 | 4.90 |
February | 22.06 | 5.21 |
March | 22.82 | 8.41 |
April | 23.11 | 10.40 |
May | 23.79 | 13.39 |
June | 24.26 | 17.41 |
July | 24.34 | 20.12 |
August | 24.37 | 19.46 |
September | 24.23 | 16.66 |
October | 23.21 | 11.27 |
November | 22.17 | 8.49 |
December | 21.90 | 4.55 |
Annual Sum or Average | 23.19 | 11.73 |
Minimum of Months | 21.90 | 4.55 |
Maximum of Months | 24.37 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 4.90 |
February | 21.78 | 5.21 |
March | 23.10 | 8.41 |
April | 23.75 | 10.40 |
May | 24.95 | 13.39 |
June | 25.96 | 17.41 |
July | 26.37 | 20.12 |
August | 26.24 | 19.46 |
September | 25.66 | 16.66 |
October | 23.64 | 11.27 |
November | 22.20 | 8.49 |
December | 21.46 | 4.55 |
Annual Sum or Average | 23.91 | 11.73 |
Minimum of Months | 21.46 | 4.55 |
Maximum of Months | 26.37 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 4.90 |
February | 19.62 | 5.21 |
March | 20.61 | 8.41 |
April | 21.23 | 10.40 |
May | 22.28 | 13.39 |
June | 24.64 | 17.41 |
July | 25.58 | 20.12 |
August | 25.46 | 19.46 |
September | 24.71 | 16.66 |
October | 21.77 | 11.27 |
November | 20.39 | 8.49 |
December | 19.39 | 4.55 |
Annual Sum or Average | 22.11 | 11.73 |
Minimum of Months | 19.39 | 4.55 |
Maximum of Months | 25.58 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:09
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 4.90 |
February | 23.29 | 5.21 |
March | 24.85 | 8.41 |
April | 25.13 | 10.40 |
May | 26.20 | 13.39 |
June | 26.60 | 17.41 |
July | 26.76 | 20.12 |
August | 26.71 | 19.46 |
September | 26.56 | 16.66 |
October | 25.53 | 11.27 |
November | 23.81 | 8.49 |
December | 23.01 | 4.55 |
Annual Sum or Average | 25.15 | 11.73 |
Minimum of Months | 23.01 | 4.55 |
Maximum of Months | 26.76 | 20.12 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:09
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.114135E+12 | 73511.662 | 13-JAN-18:00 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32081.559 | 0.000 | 0.000 | 0.000 |
February | 0.103215E+12 | 71901.326 | 13-FEB-18:15 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30471.223 | 0.000 | 0.000 | 0.000 |
March | 0.114695E+12 | 68933.484 | 20-MAR-17:30 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 6047.468 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24008.913 | 0.000 | 0.000 | 0.000 |
April | 0.110873E+12 | 71755.860 | 22-APR-17:45 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 6244.635 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26634.123 | 0.000 | 0.000 | 0.000 |
May | 0.116493E+12 | 75091.361 | 04-MAY-17:15 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 12786.661 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23427.597 | 0.000 | 0.000 | 0.000 |
June | 0.118017E+12 | 80553.131 | 24-JUN-17:30 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 20577.148 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21098.880 | 0.000 | 0.000 | 0.000 |
July | 0.127738E+12 | 84248.103 | 18-JUL-16:15 | 4276.255 | 26730.986 | 7266.229 | 0.000 | 23107.304 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22867.328 | 0.000 | 0.000 | 0.000 |
August | 0.126156E+12 | 80307.818 | 01-AUG-17:00 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 16338.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25091.871 | 0.000 | 0.000 | 0.000 |
September | 0.117706E+12 | 78309.224 | 09-SEP-17:00 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 15144.172 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24287.949 | 0.000 | 0.000 | 0.000 |
October | 0.113823E+12 | 69768.954 | 02-OCT-17:45 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 4254.251 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26637.600 | 0.000 | 0.000 | 0.000 |
November | 0.108700E+12 | 68436.201 | 24-NOV-18:15 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27006.098 | 0.000 | 0.000 | 0.000 |
December | 0.113374E+12 | 68480.687 | 31-DEC-18:15 | 4979.953 | 26630.920 | 7266.229 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27050.585 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.138493E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.103215E+12 | 68436.201 | 4276.255 | 26630.920 | 7266.229 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21098.880 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.127738E+12 | 84248.103 | 4979.953 | 26730.986 | 7266.229 | 0.000 | 23107.304 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32081.559 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:09
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.502954E+11 | 45733.910 | 01-JAN-03:00 | 45733.910 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 45733.910 |
February | 0.544977E+11 | 78560.181 | 15-FEB-01:00 | 78560.181 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 78560.181 |
March | 0.161607E+11 | 36846.239 | 03-MAR-05:00 | 36846.239 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 36846.239 |
April | 0.104138E+11 | 30903.388 | 11-APR-03:00 | 30903.388 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30903.388 |
May | 0.222133E+10 | 12593.766 | 24-MAY-03:00 | 12593.766 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12593.766 |
June | 230191.391 | 55.022 | 17-JUN-05:30 | 55.022 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 55.022 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 2163274.429 | 213.416 | 15-SEP-04:00 | 213.416 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 213.416 |
October | 0.644920E+10 | 26209.658 | 30-OCT-02:15 | 26209.658 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26209.658 |
November | 0.249646E+11 | 34728.805 | 30-NOV-05:00 | 34728.805 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 34728.805 |
December | 0.658677E+11 | 78565.154 | 20-DEC-04:00 | 78565.154 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 78565.154 |
Annual Sum or Average | 0.230873E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.658677E+11 | 78565.154 | 78565.154 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 78565.154 |