Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Simulation Timestamp: 2015-09-09 18:47:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1752.84 | 559.19 | 620.70 |
Net Site Energy | 1752.84 | 559.19 | 620.70 |
Total Source Energy | 4896.19 | 1561.98 | 1733.79 |
Net Source Energy | 4896.19 | 1561.98 | 1733.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 314.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 145.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 389.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1438.36 | 314.48 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 314.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 145.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 389.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.88 | 111.36 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 509.34 | 111.36 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 243.13 | 100.33 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 458.86 | 100.33 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1438.36 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1438.36 | 100.00 |
Total On-Site and Utility Electric Sources | 1438.36 | 100.00 |
Total Electricity End Uses | 1438.36 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 49.25 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2725.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47 |
RunPeriod | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Weather File | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Latitude [deg] | 39.17 |
Longitude [deg] | -76.7 |
Elevation [m] | 45.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JUL-16:30 | 25-DEC-06:00 | - | - | - | 01-JAN-07:15 |
Heating | 0.00 | 109274.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7206.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 86255.13 | 109274.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 109274.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28889.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 3538.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 738.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7206.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 19152.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 340.90 | 0.00 | 0.00 | 0.00 |
Cooling | 461.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 127.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 719.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1232.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4555.30 | 340.90 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 120.72 | 0.00 | 0.00 | 0.00 |
Cooling | 163.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 254.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 436.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1613.08 | 120.72 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 120.72 | 0.00 | 0.00 | 0.00 |
Cooling | 163.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 45.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 254.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 436.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1613.08 | 120.72 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00 | -10.60 | Wetbulb [C] | 3.90 | 290.00 |
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 10.40 | 23.90 | Wetbulb [C] | 4.60 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 2.653 | 0.426 | 0.308 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 2.653 | 0.426 | 0.308 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.52_SHGC_0.40 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 2.653 | 0.426 | 0.308 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.52_SHGC_0.40 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 2.653 | 0.426 | 0.308 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.52_SHGC_0.40 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 2.653 | 0.426 | 0.308 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 2.653 | 0.426 | 0.308 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 112.97 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 193.95 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.72 | 83.72 | 40.12 | |
Exterior Lighting Total | 2553.00 | 40.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3634.27 | 2600.44 | 1033.83 | 0.72 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3434.95 | 2468.73 | 966.22 | 0.72 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8020.81 | 6266.09 | 1754.72 | 0.78 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2795.95 | 1968.63 | 827.32 | 0.70 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2239.95 | 1546.78 | 693.17 | 0.69 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2224.18 | 1534.30 | 689.88 | 0.69 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2546.71 | 1748.41 | 798.30 | 0.69 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2589.53 | 1784.21 | 805.33 | 0.69 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9355.65 | 6846.50 | 2509.16 | 0.73 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8909.12 | 6516.34 | 2392.77 | 0.73 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8789.56 | 6329.09 | 2460.47 | 0.72 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7556.22 | 5445.81 | 2110.41 | 0.72 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5879.33 | 4180.68 | 1698.65 | 0.71 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5853.62 | 4160.13 | 1693.49 | 0.71 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6717.00 | 4751.30 | 1965.70 | 0.71 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6734.02 | 4764.95 | 1969.07 | 0.71 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6330.81 | 4686.06 | 1644.75 | 0.74 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5932.82 | 4382.01 | 1550.81 | 0.74 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5976.11 | 4390.97 | 1585.13 | 0.73 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5269.18 | 3822.29 | 1446.89 | 0.73 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4175.83 | 3008.66 | 1167.16 | 0.72 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4186.89 | 3013.81 | 1173.07 | 0.72 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4860.73 | 3552.78 | 1307.95 | 0.73 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4871.16 | 3561.20 | 1309.96 | 0.73 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3500.6 | 3.28 | 11.18 | 11.64 | 11.12 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3307.2 | 3.27 | 11.16 | 11.62 | 11.09 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7658.8 | 3.16 | 10.77 | 11.20 | 10.53 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2697.2 | 3.30 | 11.25 | 11.72 | 11.23 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2164.7 | 3.32 | 11.34 | 11.81 | 11.36 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2149.6 | 3.32 | 11.34 | 11.82 | 11.37 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2462.4 | 3.33 | 11.36 | 11.84 | 11.40 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2503.0 | 3.33 | 11.35 | 11.82 | 11.38 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8992.2 | 3.25 | 11.07 | 11.53 | 10.97 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8563.4 | 3.25 | 11.08 | 11.53 | 10.97 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8461.2 | 3.27 | 11.15 | 11.61 | 11.08 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7273.3 | 3.27 | 11.14 | 11.60 | 11.07 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5666.4 | 3.28 | 11.20 | 11.67 | 11.16 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5641.9 | 3.28 | 11.21 | 11.67 | 11.17 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6476.9 | 3.29 | 11.23 | 11.70 | 11.20 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6493.1 | 3.29 | 11.23 | 11.69 | 11.20 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6078.1 | 3.23 | 11.02 | 11.47 | 10.89 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5697.2 | 3.23 | 11.03 | 11.48 | 10.91 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5741.7 | 3.24 | 11.06 | 11.51 | 10.94 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5068.8 | 3.26 | 11.11 | 11.57 | 11.03 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4019.6 | 3.27 | 11.15 | 11.60 | 11.07 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4030.6 | 3.27 | 11.15 | 11.61 | 11.08 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4672.5 | 3.25 | 11.08 | 11.53 | 10.98 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4682.4 | 3.25 | 11.08 | 11.53 | 10.97 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 2963.30 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 2940.52 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 5176.62 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 2933.44 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 2200.11 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 2199.94 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 2188.79 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 2304.81 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 5889.43 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 5920.90 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 5870.67 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 5902.14 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 4033.26 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 4032.78 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 4003.65 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 4003.17 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 4373.07 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 4391.13 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 4363.26 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 4381.32 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 3344.55 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 3344.28 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 3324.47 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 3324.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.17 | 197.24 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 188.50 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.46 | 535.81 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.13 | 145.64 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.10 | 110.89 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.09 | 109.80 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 124.13 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.11 | 127.44 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.46 | 536.78 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 510.52 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 484.63 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 417.54 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 314.09 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 312.28 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 354.06 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.31 | 355.27 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.32 | 373.37 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 348.09 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 346.24 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 295.89 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.58 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.20 | 230.65 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 278.06 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.24 | 278.81 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1798.44 | 2158.13 | 0.142 | 0.170 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 33.15 | 0.01446 |
G NW APARTMENT | 1718.90 | 2062.68 | 0.135 | 0.162 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.90 | 0.01446 |
OFFICE | 4650.78 | 5580.93 | 0.385 | 0.462 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 29.56 | 0.01446 |
G NE APARTMENT | 1327.98 | 1593.58 | 0.105 | 0.125 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.23 | 0.01446 |
G N1 APARTMENT | 1011.19 | 1213.43 | 0.080 | 0.096 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.12 | 0.01446 |
G N2 APARTMENT | 1001.31 | 1201.57 | 0.079 | 0.095 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.12 | 0.01446 |
G S1 APARTMENT | 1131.89 | 1358.27 | 0.089 | 0.107 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.27 | 0.01446 |
G S2 APARTMENT | 1162.04 | 1394.44 | 0.091 | 0.110 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.14 | 0.01446 |
M SW APARTMENT | 4894.47 | 5873.37 | 0.385 | 0.462 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
M NW APARTMENT | 4655.18 | 5586.22 | 0.366 | 0.440 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.90 | 0.01446 |
M SE APARTMENT | 4418.77 | 5302.53 | 0.348 | 0.417 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.14 | 0.01446 |
M NE APARTMENT | 3807.08 | 4568.49 | 0.300 | 0.360 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
M N1 APARTMENT | 2864.13 | 3436.95 | 0.225 | 0.271 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.12 | 0.01446 |
M N2 APARTMENT | 2847.66 | 3417.19 | 0.224 | 0.269 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.12 | 0.01446 |
M S1 APARTMENT | 3228.51 | 3874.21 | 0.254 | 0.305 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.27 | 0.01446 |
M S2 APARTMENT | 3239.49 | 3887.38 | 0.255 | 0.306 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.27 | 0.01446 |
T SW APARTMENT | 3404.10 | 4084.92 | 0.268 | 0.322 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 33.93 | 0.01446 |
T NW APARTMENT | 3173.64 | 3808.37 | 0.250 | 0.300 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.36 | 0.01446 |
T SE APARTMENT | 3156.79 | 3788.15 | 0.249 | 0.298 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.27 | 0.01446 |
T NE APARTMENT | 2697.70 | 3237.24 | 0.212 | 0.255 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 34.40 | 0.01446 |
T N1 APARTMENT | 2102.45 | 2522.94 | 0.166 | 0.199 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.24 | 0.01446 |
T N2 APARTMENT | 2103.12 | 2523.74 | 0.166 | 0.199 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 34.40 | 0.01446 |
T S1 APARTMENT | 2535.37 | 3042.45 | 0.200 | 0.240 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01446 |
T S2 APARTMENT | 2542.20 | 3050.64 | 0.200 | 0.240 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01446 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 1621.55 | 1945.86 | 0.047 | 0.056 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G NW APARTMENT | 1633.38 | 1960.05 | 0.047 | 0.057 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
OFFICE | 3176.34 | 3811.61 | 0.089 | 0.106 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G NE APARTMENT | 1627.38 | 1952.86 | 0.047 | 0.056 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G N1 APARTMENT | 1007.24 | 1208.68 | 0.029 | 0.035 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G N2 APARTMENT | 1007.09 | 1208.51 | 0.029 | 0.035 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G S1 APARTMENT | 997.66 | 1197.19 | 0.029 | 0.035 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
G S2 APARTMENT | 1095.77 | 1314.92 | 0.032 | 0.038 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
M SW APARTMENT | 3274.00 | 3928.80 | 0.095 | 0.114 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M NW APARTMENT | 3300.61 | 3960.73 | 0.095 | 0.115 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M SE APARTMENT | 3258.14 | 3909.76 | 0.094 | 0.113 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M NE APARTMENT | 3284.75 | 3941.70 | 0.095 | 0.114 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M N1 APARTMENT | 1704.24 | 2045.09 | 0.049 | 0.059 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M N2 APARTMENT | 1703.83 | 2044.60 | 0.049 | 0.059 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M S1 APARTMENT | 1679.20 | 2015.04 | 0.049 | 0.058 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
M S2 APARTMENT | 1678.79 | 2014.55 | 0.049 | 0.058 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T SW APARTMENT | 2844.93 | 3413.92 | 0.082 | 0.099 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T NW APARTMENT | 2860.21 | 3432.25 | 0.083 | 0.099 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T SE APARTMENT | 2836.64 | 3403.96 | 0.082 | 0.098 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T NE APARTMENT | 2851.91 | 3422.29 | 0.082 | 0.099 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T N1 APARTMENT | 1975.11 | 2370.13 | 0.057 | 0.069 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T N2 APARTMENT | 1974.88 | 2369.85 | 0.057 | 0.069 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T S1 APARTMENT | 1958.12 | 2349.75 | 0.057 | 0.068 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
T S2 APARTMENT | 1957.90 | 2349.48 | 0.057 | 0.068 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | -10.60 | 0.00152 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.17 | 0.17 | 0.06 | 0.06 |
SPLIT GNW | 0.16 | 0.16 | 0.06 | 0.06 |
SPLIT OFFICE | 0.46 | 0.46 | 0.11 | 0.11 |
SPLIT GNE | 0.13 | 0.13 | 0.06 | 0.06 |
SPLIT GN1 | 0.10 | 0.10 | 0.03 | 0.03 |
SPLIT GN2 | 0.09 | 0.09 | 0.03 | 0.03 |
SPLIT GS1 | 0.11 | 0.11 | 0.03 | 0.03 |
SPLIT GS2 | 0.11 | 0.11 | 0.04 | 0.04 |
SPLIT MSW | 0.46 | 0.46 | 0.11 | 0.11 |
SPLIT MNW | 0.44 | 0.44 | 0.11 | 0.11 |
SPLIT MSE | 0.42 | 0.42 | 0.11 | 0.11 |
SPLIT MNE | 0.36 | 0.36 | 0.11 | 0.11 |
SPLIT MN1 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MN2 | 0.27 | 0.27 | 0.06 | 0.06 |
SPLIT MS1 | 0.31 | 0.31 | 0.06 | 0.06 |
SPLIT MS2 | 0.31 | 0.31 | 0.06 | 0.06 |
SPLIT TSW | 0.32 | 0.32 | 0.10 | 0.10 |
SPLIT TNW | 0.30 | 0.30 | 0.10 | 0.10 |
SPLIT TSE | 0.30 | 0.30 | 0.10 | 0.10 |
SPLIT TNE | 0.25 | 0.25 | 0.10 | 0.10 |
SPLIT TN1 | 0.20 | 0.20 | 0.07 | 0.07 |
SPLIT TN2 | 0.20 | 0.20 | 0.07 | 0.07 |
SPLIT TS1 | 0.24 | 0.24 | 0.07 | 0.07 |
SPLIT TS2 | 0.24 | 0.24 | 0.07 | 0.07 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 3606.75 | 6205.25 | 1520.50 |
G NW APARTMENT | 4036.75 | 6443.50 | 2114.50 |
OFFICE | 725.25 | 1378.75 | 80.00 |
G NE APARTMENT | 4033.75 | 6440.00 | 2089.00 |
G N1 APARTMENT | 3598.50 | 6575.50 | 1872.00 |
G N2 APARTMENT | 3600.50 | 6573.75 | 1869.25 |
G S1 APARTMENT | 3146.75 | 6296.50 | 1162.00 |
G S2 APARTMENT | 3252.00 | 6187.75 | 1142.00 |
M SW APARTMENT | 3812.75 | 4009.50 | 314.25 |
M NW APARTMENT | 3939.50 | 4612.75 | 750.50 |
M SE APARTMENT | 3797.50 | 4009.00 | 299.25 |
M NE APARTMENT | 3917.25 | 4622.50 | 736.50 |
M N1 APARTMENT | 3573.25 | 4491.00 | 400.25 |
M N2 APARTMENT | 3570.75 | 4492.00 | 399.50 |
M S1 APARTMENT | 3654.50 | 3712.00 | 167.75 |
M S2 APARTMENT | 3655.25 | 3713.25 | 169.50 |
T SW APARTMENT | 4617.25 | 4840.75 | 1500.75 |
T NW APARTMENT | 4956.00 | 5302.25 | 2100.00 |
T SE APARTMENT | 4619.75 | 4825.50 | 1485.00 |
T NE APARTMENT | 4918.50 | 5316.00 | 2074.75 |
T N1 APARTMENT | 4563.00 | 5266.75 | 1734.25 |
T N2 APARTMENT | 4560.75 | 5264.75 | 1732.00 |
T S1 APARTMENT | 4259.25 | 4682.75 | 1122.75 |
T S2 APARTMENT | 4263.00 | 4682.00 | 1124.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 5787.00 | 6641.25 | 2725.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
G NW APARTMENT | 4.25 | 0.00 | 4.25 | 0.00 |
OFFICE | 10.00 | 16.25 | 0.00 | 0.00 |
G NE APARTMENT | 4.75 | 0.00 | 4.75 | 0.00 |
G N1 APARTMENT | 6.75 | 0.00 | 6.75 | 0.00 |
G N2 APARTMENT | 9.00 | 0.50 | 9.00 | 0.50 |
G S1 APARTMENT | 3.00 | 0.00 | 3.00 | 0.00 |
G S2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M SW APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
M NW APARTMENT | 5.50 | 0.00 | 5.50 | 0.00 |
M SE APARTMENT | 1.75 | 0.00 | 1.75 | 0.00 |
M NE APARTMENT | 6.00 | 0.00 | 6.00 | 0.00 |
M N1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
M N2 APARTMENT | 2.75 | 0.00 | 2.75 | 0.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.50 | 0.00 | 0.50 | 0.00 |
T SW APARTMENT | 3.50 | 0.00 | 3.50 | 0.00 |
T NW APARTMENT | 5.25 | 0.00 | 5.25 | 0.00 |
T SE APARTMENT | 3.75 | 0.00 | 3.75 | 0.00 |
T NE APARTMENT | 5.00 | 0.00 | 5.00 | 0.00 |
T N1 APARTMENT | 1.50 | 0.00 | 1.50 | 0.00 |
T N2 APARTMENT | 0.75 | 0.00 | 0.75 | 0.00 |
T S1 APARTMENT | 2.50 | 0.00 | 2.50 | 0.00 |
T S2 APARTMENT | 2.00 | 0.00 | 2.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 59.25 | 16.75 | 49.25 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.366 | 0.176 | 0.000 | 0.076 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.074 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.519 | 0.208 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.176 | 0.000 | 0.073 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.073 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.073 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.075 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.106 | 0.000 | 0.075 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.253 | 0.000 | 0.094 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.253 | 0.000 | 0.092 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.253 | 0.000 | 0.094 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.253 | 0.000 | 0.092 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.153 | 0.000 | 0.092 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.153 | 0.000 | 0.092 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.153 | 0.000 | 0.094 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.153 | 0.000 | 0.094 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.335 | 0.000 | 0.112 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.334 | 0.000 | 0.109 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.335 | 0.000 | 0.112 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.334 | 0.000 | 0.109 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.202 | 0.000 | 0.109 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.202 | 0.000 | 0.109 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.202 | 0.000 | 0.112 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.354 | 0.202 | 0.000 | 0.112 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.353 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.498 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.360 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.359 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.340 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1438.36 | 20318.93 | 03-JAN-03:30 | 86255.13 | 09-JUL-16:30 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 389.06 | 0.00 | 01-JAN-00:15 | 32533.94 | 14-JAN-07:30 |
WaterSystems:Electricity | 389.06 | 0.00 | 01-JAN-00:15 | 32533.94 | 14-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 389.06 | 0.00 | 01-JAN-00:15 | 32533.94 | 14-JAN-07:30 |
Fans:Electricity | 227.26 | 7206.32 | 01-JAN-00:15 | 7206.32 | 01-JAN-00:30 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
ElectricityPurchased:Plant | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
Cogeneration:ElectricityPurchased | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
ElectricityNet:Plant | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
Cogeneration:ElectricityNet | 1438.36 | 20318.93 | 02-JAN-03:15 | 86255.13 | 09-JUL-16:30 |
ExteriorLights:Electricity | 40.12 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.12 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 373.07 | 7206.32 | 01-JAN-00:15 | 37839.99 | 20-JUL-13:30 |
General:Fans:Electricity | 227.26 | 7206.32 | 01-JAN-00:15 | 7206.32 | 01-JAN-00:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 145.81 | 0.00 | 01-JAN-00:15 | 30633.67 | 20-JUL-13:30 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 314.48 | 0.00 | 01-FEB-13:30 | 109274.00 | 25-DEC-07:00 |
Gas:HVAC | 314.48 | 0.00 | 01-FEB-13:30 | 109274.00 | 25-DEC-07:00 |
Heating:Gas | 314.48 | 0.00 | 01-FEB-13:30 | 109274.00 | 25-DEC-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:15 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1417.55 | 1480.65 | 28-OCT-14:00 | 181629.64 | 20-JUL-13:30 |
EnergyTransfer:Building | 570.59 | 1480.65 | 28-OCT-14:00 | 63971.36 | 09-JUL-15:30 |
EnergyTransfer:Zone:G SW APARTMENT | 12.96 | 0.05 | 14-MAY-21:45 | 1993.08 | 25-DEC-04:00 |
Heating:EnergyTransfer | 140.18 | 0.00 | 17-FEB-13:45 | 63238.37 | 25-DEC-03:15 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 4.64 | 0.00 | 01-JAN-11:15 | 1993.08 | 25-DEC-04:00 |
Cooling:EnergyTransfer | 430.41 | 0.00 | 04-JAN-07:15 | 63971.36 | 09-JUL-15:30 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 8.33 | 0.00 | 01-JAN-00:15 | 1946.99 | 09-JUL-16:30 |
EnergyTransfer:Zone:G NW APARTMENT | 13.40 | 0.04 | 09-APR-10:45 | 2094.78 | 25-DEC-08:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 6.85 | 0.00 | 16-JAN-16:00 | 2094.78 | 25-DEC-08:30 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 6.56 | 0.00 | 01-JAN-00:15 | 1917.11 | 09-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 24.15 | 0.02 | 09-SEP-09:15 | 4670.72 | 09-JUL-10:00 |
Heating:EnergyTransfer:Zone:OFFICE | 2.96 | 0.00 | 01-JAN-00:15 | 3468.27 | 26-DEC-07:15 |
Cooling:EnergyTransfer:Zone:OFFICE | 21.19 | 0.00 | 02-JAN-07:45 | 4670.72 | 09-JUL-10:00 |
EnergyTransfer:Zone:G NE APARTMENT | 13.41 | 0.01 | 09-APR-18:30 | 2021.82 | 25-DEC-04:00 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 6.66 | 0.00 | 26-JAN-17:15 | 2021.82 | 25-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 6.75 | 0.00 | 01-JAN-00:15 | 1464.77 | 09-JUL-09:45 |
EnergyTransfer:Zone:G N1 APARTMENT | 9.07 | 0.00 | 26-OCT-16:00 | 1265.67 | 25-DEC-08:30 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 3.45 | 0.00 | 16-JAN-16:15 | 1265.67 | 25-DEC-08:30 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 5.62 | 0.00 | 01-JAN-00:15 | 1085.63 | 09-JUL-17:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 9.08 | 0.01 | 27-NOV-13:30 | 1262.56 | 25-DEC-08:30 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 3.45 | 0.00 | 16-JAN-16:15 | 1262.56 | 25-DEC-08:30 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 5.63 | 0.00 | 01-JAN-00:15 | 1074.19 | 09-JUL-17:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 9.52 | 0.01 | 28-MAR-22:30 | 1302.16 | 29-AUG-13:15 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 1.81 | 0.00 | 01-JAN-10:00 | 1145.95 | 25-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 7.71 | 0.00 | 01-JAN-00:15 | 1302.16 | 29-AUG-13:15 |
EnergyTransfer:Zone:G S2 APARTMENT | 10.07 | 0.02 | 15-MAY-20:45 | 1359.85 | 12-AUG-13:30 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 2.00 | 0.00 | 01-JAN-10:15 | 1227.82 | 25-DEC-04:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 8.07 | 0.00 | 01-JAN-00:15 | 1359.85 | 12-AUG-13:30 |
EnergyTransfer:Zone:M SW APARTMENT | 40.27 | 0.03 | 09-DEC-01:00 | 5229.21 | 09-JUL-16:30 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 5.12 | 0.00 | 01-JAN-10:30 | 4517.26 | 25-DEC-03:15 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 35.15 | 0.00 | 01-JAN-00:15 | 5229.21 | 09-JUL-16:30 |
EnergyTransfer:Zone:M NW APARTMENT | 37.19 | 0.05 | 27-JAN-04:30 | 5072.43 | 09-JUL-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 9.95 | 0.00 | 02-JAN-21:00 | 4664.08 | 13-FEB-11:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 27.23 | 0.00 | 01-JAN-00:15 | 5072.43 | 09-JUL-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 40.67 | 0.06 | 27-FEB-15:00 | 4718.60 | 29-AUG-12:45 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 4.99 | 0.00 | 01-JAN-09:45 | 4493.92 | 25-DEC-02:30 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 35.68 | 0.00 | 01-JAN-00:15 | 4718.60 | 29-AUG-12:45 |
EnergyTransfer:Zone:M NE APARTMENT | 37.51 | 0.00 | 01-MAR-23:45 | 4581.75 | 25-DEC-01:15 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 9.71 | 0.00 | 02-JAN-21:00 | 4581.75 | 25-DEC-01:15 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 27.81 | 0.00 | 01-JAN-00:15 | 4171.19 | 09-JUL-10:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 28.58 | 0.04 | 02-MAR-13:15 | 3062.06 | 29-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 3.22 | 0.00 | 01-JAN-18:15 | 2488.27 | 25-DEC-02:30 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 25.36 | 0.00 | 01-JAN-00:15 | 3062.06 | 29-JUN-17:30 |
EnergyTransfer:Zone:M N2 APARTMENT | 28.59 | 0.04 | 07-JAN-15:15 | 3048.74 | 29-JUN-17:30 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 3.22 | 0.00 | 01-JAN-18:15 | 2487.60 | 25-DEC-02:30 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 25.37 | 0.00 | 01-JAN-00:15 | 3048.74 | 29-JUN-17:30 |
EnergyTransfer:Zone:M S1 APARTMENT | 36.48 | 0.06 | 01-FEB-21:30 | 3694.65 | 08-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 1.01 | 0.00 | 01-JAN-00:15 | 2352.70 | 25-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 35.47 | 0.00 | 01-JAN-05:00 | 3694.65 | 08-OCT-13:30 |
EnergyTransfer:Zone:M S2 APARTMENT | 36.49 | 0.04 | 01-FEB-19:15 | 3700.27 | 08-OCT-13:30 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 1.01 | 0.00 | 01-JAN-00:15 | 2355.67 | 25-DEC-04:00 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 35.48 | 0.00 | 01-JAN-05:00 | 3700.27 | 08-OCT-13:30 |
EnergyTransfer:Zone:T SW APARTMENT | 26.14 | 0.00 | 27-APR-06:45 | 3806.72 | 25-DEC-03:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 9.77 | 0.00 | 01-JAN-11:45 | 3806.72 | 25-DEC-03:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 16.37 | 0.00 | 01-JAN-00:15 | 3606.96 | 17-AUG-15:15 |
EnergyTransfer:Zone:T NW APARTMENT | 26.45 | 0.02 | 05-JUN-23:15 | 3816.84 | 25-DEC-02:30 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 13.01 | 0.00 | 16-JAN-15:15 | 3816.84 | 25-DEC-02:30 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 13.44 | 0.00 | 01-JAN-00:15 | 3453.73 | 29-JUN-16:15 |
EnergyTransfer:Zone:T SE APARTMENT | 25.97 | 0.01 | 15-SEP-23:15 | 3779.36 | 25-DEC-02:45 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 9.54 | 0.00 | 01-JAN-11:00 | 3779.36 | 25-DEC-02:45 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 16.43 | 0.00 | 01-JAN-00:15 | 3341.21 | 17-AUG-14:00 |
EnergyTransfer:Zone:T NE APARTMENT | 26.22 | 0.01 | 14-MAR-12:15 | 3769.07 | 25-DEC-02:15 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 12.71 | 0.00 | 02-FEB-17:15 | 3769.07 | 25-DEC-02:15 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 13.51 | 0.00 | 01-JAN-00:15 | 2865.77 | 29-JUN-14:00 |
EnergyTransfer:Zone:T N1 APARTMENT | 19.26 | 0.05 | 17-FEB-20:00 | 2562.55 | 25-DEC-05:00 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 7.61 | 0.00 | 16-JAN-15:30 | 2562.55 | 25-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 11.64 | 0.00 | 01-JAN-00:15 | 2280.85 | 29-JUN-16:15 |
EnergyTransfer:Zone:T N2 APARTMENT | 19.26 | 0.00 | 06-OCT-11:30 | 2562.64 | 25-DEC-05:00 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 7.61 | 0.00 | 16-JAN-15:30 | 2562.64 | 25-DEC-05:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 11.64 | 0.00 | 01-JAN-00:15 | 2267.15 | 29-JUN-16:15 |
EnergyTransfer:Zone:T S1 APARTMENT | 19.91 | 0.11 | 11-OCT-21:45 | 2761.23 | 17-AUG-14:00 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 4.94 | 0.00 | 01-JAN-10:30 | 2535.17 | 25-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 14.97 | 0.00 | 01-JAN-00:15 | 2761.23 | 17-AUG-14:00 |
EnergyTransfer:Zone:T S2 APARTMENT | 19.92 | 0.05 | 31-AUG-05:00 | 2763.42 | 17-AUG-14:00 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 4.94 | 0.00 | 01-JAN-10:30 | 2536.11 | 25-DEC-06:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 14.99 | 0.00 | 01-JAN-00:15 | 2763.42 | 17-AUG-14:00 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 846.96 | 0.00 | 01-FEB-18:00 | 118718.08 | 20-JUL-13:30 |
HeatingCoils:EnergyTransfer | 251.58 | 0.00 | 01-FEB-13:30 | 87419.20 | 25-DEC-07:00 |
CoolingCoils:EnergyTransfer | 595.37 | 0.00 | 01-JAN-00:15 | 118718.08 | 20-JUL-13:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 4.638 | -8.325 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 13.959 | 0.000 | 0.302 | 0.000 | 0.000 | -6.125 | 0.000 | -6.196 | -15.382 |
G NW APARTMENT | 6.848 | -6.557 | 0.000 | 0.000 | 3.849 | 1.087 | 12.213 | 7.496 | 0.000 | 0.301 | 0.000 | 0.000 | -6.428 | 0.000 | -6.060 | -12.748 |
OFFICE | 2.960 | -21.187 | 0.000 | 0.000 | 0.523 | 26.452 | 9.482 | 13.822 | 0.000 | 0.177 | 0.001 | 0.000 | -6.180 | 0.000 | -5.639 | -20.409 |
G NE APARTMENT | 6.665 | -6.748 | 0.000 | 0.000 | 3.857 | 1.087 | 12.213 | 7.517 | 0.000 | 0.301 | 0.000 | 0.000 | -6.217 | 0.000 | -6.040 | -12.635 |
G N1 APARTMENT | 3.452 | -5.623 | 0.000 | 0.000 | 3.858 | 1.087 | 12.213 | 2.916 | 0.000 | 0.200 | 0.000 | 0.000 | -4.014 | 0.000 | -3.886 | -10.202 |
G N2 APARTMENT | 3.449 | -5.631 | 0.000 | 0.000 | 3.859 | 1.087 | 12.213 | 2.915 | 0.000 | 0.200 | 0.000 | 0.000 | -4.013 | 0.000 | -3.885 | -10.193 |
G S1 APARTMENT | 1.809 | -7.707 | 0.000 | 0.000 | 3.832 | 1.087 | 12.213 | 9.418 | 0.000 | 0.199 | 0.000 | 0.000 | -3.700 | 0.000 | -4.022 | -13.128 |
G S2 APARTMENT | 1.999 | -8.072 | 0.000 | 0.000 | 3.830 | 1.087 | 12.213 | 9.411 | 0.000 | 0.199 | 0.000 | 0.000 | -3.704 | 0.000 | -4.032 | -12.930 |
M SW APARTMENT | 5.122 | -35.149 | 0.000 | 0.000 | 3.718 | 1.087 | 12.213 | 13.503 | 0.000 | 0.426 | 15.027 | 0.000 | -6.753 | 0.000 | -9.193 | -0.000 |
M NW APARTMENT | 9.955 | -27.233 | 0.000 | 0.000 | 3.761 | 1.087 | 12.213 | 7.133 | 0.000 | 0.424 | 8.622 | 0.000 | -7.000 | 0.000 | -8.960 | -0.000 |
M SE APARTMENT | 4.987 | -35.683 | 0.000 | 0.000 | 3.722 | 1.087 | 12.213 | 13.602 | 0.000 | 0.426 | 15.450 | 0.000 | -6.616 | 0.000 | -9.188 | -0.000 |
M NE APARTMENT | 9.707 | -27.805 | 0.000 | 0.000 | 3.768 | 1.087 | 12.213 | 7.144 | 0.000 | 0.424 | 9.168 | 0.000 | -6.767 | 0.000 | -8.938 | -0.001 |
M N1 APARTMENT | 3.223 | -25.361 | 0.000 | 0.000 | 3.752 | 1.087 | 12.213 | 2.690 | 0.000 | 0.275 | 12.360 | 0.000 | -4.432 | 0.000 | -5.806 | -0.000 |
M N2 APARTMENT | 3.220 | -25.369 | 0.000 | 0.000 | 3.753 | 1.087 | 12.213 | 2.690 | 0.000 | 0.275 | 12.366 | 0.000 | -4.431 | 0.000 | -5.804 | -0.000 |
M S1 APARTMENT | 1.007 | -35.472 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 9.120 | 0.000 | 0.277 | 18.209 | 0.000 | -4.117 | 0.000 | -6.017 | -0.000 |
M S2 APARTMENT | 1.010 | -35.479 | 0.000 | 0.000 | 3.693 | 1.087 | 12.213 | 9.119 | 0.000 | 0.277 | 18.213 | 0.000 | -4.116 | 0.000 | -6.018 | -0.000 |
T SW APARTMENT | 9.766 | -16.374 | 0.000 | 0.000 | 3.772 | 1.087 | 12.213 | 13.393 | 0.000 | 0.560 | 0.000 | 0.000 | -6.392 | 0.000 | -11.758 | -6.266 |
T NW APARTMENT | 13.015 | -13.438 | 0.000 | 0.000 | 3.800 | 1.087 | 12.213 | 7.050 | 0.000 | 0.557 | 0.000 | 0.000 | -6.669 | 0.000 | -11.519 | -6.094 |
T SE APARTMENT | 9.535 | -16.434 | 0.000 | 0.000 | 3.777 | 1.087 | 12.213 | 13.506 | 0.000 | 0.560 | 0.000 | 0.000 | -6.268 | 0.000 | -11.758 | -6.218 |
T NE APARTMENT | 12.711 | -13.512 | 0.000 | 0.000 | 3.808 | 1.087 | 12.213 | 7.083 | 0.000 | 0.557 | 0.000 | 0.000 | -6.457 | 0.000 | -11.503 | -5.986 |
T N1 APARTMENT | 7.615 | -11.642 | 0.000 | 0.000 | 3.797 | 1.087 | 12.213 | 2.673 | 0.000 | 0.363 | 0.000 | 0.000 | -4.191 | 0.000 | -7.375 | -4.539 |
T N2 APARTMENT | 7.614 | -11.644 | 0.000 | 0.000 | 3.797 | 1.087 | 12.213 | 2.672 | 0.000 | 0.363 | 0.000 | 0.000 | -4.189 | 0.000 | -7.376 | -4.537 |
T S1 APARTMENT | 4.937 | -14.974 | 0.000 | 0.000 | 3.758 | 1.087 | 12.213 | 9.069 | 0.000 | 0.366 | 0.000 | 0.000 | -3.896 | 0.000 | -7.600 | -4.960 |
T S2 APARTMENT | 4.939 | -14.985 | 0.000 | 0.000 | 3.758 | 1.087 | 12.213 | 9.067 | 0.000 | 0.366 | 0.000 | 0.000 | -3.894 | 0.000 | -7.601 | -4.950 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.124 | 0.000 | 0.029 | 0.000 | 0.000 | -0.787 | 0.000 | -1.937 | -12.010 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 0.451 | 0.000 | 0.870 | 5.540 | 0.000 | -1.992 | 0.000 | -25.931 | -0.000 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.127 | 0.000 | 0.028 | 0.000 | 0.000 | -0.865 | 0.000 | -1.602 | -12.270 |
Total Facility | 140.181 | -430.404 | 0.000 | 0.000 | 87.565 | 95.189 | 296.854 | 197.670 | 0.000 | 9.303 | 114.956 | 0.000 | -130.213 | 0.000 | -205.643 | -175.460 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 09-JUL-17:08 | 0.00 | -1947.85 | 0.00 | 0.00 | 141.82 | 87.56 | 588.62 | 1791.94 | 0.00 | 156.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -818.36 |
G NW APARTMENT | 09-JUL-17:30 | 0.00 | -1918.05 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1921.83 | 0.00 | 146.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -968.06 |
OFFICE | 24-SEP-06:01 | 0.00 | -7561.72 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 7106.95 | 0.00 | -79.28 | 0.00 | -176.41 | 0.00 |
G NE APARTMENT | 09-JUL-09:45 | 0.00 | -1464.85 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 1673.43 | 0.00 | 142.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -810.51 |
G N1 APARTMENT | 09-JUL-17:45 | 0.00 | -1085.53 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 521.32 | 0.00 | 82.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -336.17 |
G N2 APARTMENT | 09-JUL-17:45 | 0.00 | -1074.10 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 521.49 | 0.00 | 82.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -347.78 |
G S1 APARTMENT | 29-AUG-13:15 | 0.00 | -1302.02 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1628.32 | 0.00 | 69.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -832.09 |
G S2 APARTMENT | 12-AUG-13:30 | 0.00 | -1359.82 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1399.23 | 0.00 | 75.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -550.91 |
M SW APARTMENT | 09-JUL-16:20 | 0.00 | -5230.09 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1949.90 | 0.00 | 270.75 | 2271.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 09-JUL-17:23 | 0.00 | -5073.42 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 1907.62 | 0.00 | 209.76 | 2138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 29-AUG-12:45 | 0.00 | -4718.65 | 0.00 | 0.00 | 40.75 | 12.97 | 388.49 | 2015.45 | 0.00 | 174.15 | 2086.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 09-JUL-10:00 | 0.00 | -4171.67 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 1562.96 | 0.00 | 218.94 | 1929.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 29-JUN-17:25 | 0.00 | -3062.62 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 492.60 | 0.00 | 168.23 | 1583.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 29-JUN-17:25 | 0.00 | -3049.69 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 492.68 | 0.00 | 168.23 | 1570.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 08-OCT-13:30 | 0.00 | -3694.60 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2143.66 | 0.00 | 0.00 | 1192.73 | 0.00 | 0.00 | 0.00 | -78.12 | 0.00 |
M S2 APARTMENT | 08-OCT-13:30 | 0.00 | -3700.22 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2143.62 | 0.00 | 0.00 | 1198.40 | 0.00 | 0.00 | 0.00 | -78.12 | 0.00 |
T SW APARTMENT | 17-AUG-15:15 | 0.00 | -3607.05 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 2210.83 | 0.00 | 272.69 | 558.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 29-JUN-16:04 | 0.00 | -3456.90 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 1833.11 | 0.00 | 449.15 | 436.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 17-AUG-14:00 | 0.00 | -3341.24 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1582.17 | 0.00 | 365.75 | 956.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 29-JUN-14:00 | 0.00 | -2865.64 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 865.44 | 0.00 | 506.59 | 1057.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 29-JUN-16:04 | 0.00 | -2283.19 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 425.25 | 0.00 | 270.92 | 848.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 29-JUN-16:04 | 0.00 | -2269.47 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 425.43 | 0.00 | 270.92 | 834.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 17-AUG-14:00 | 0.00 | -2761.15 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1264.28 | 0.00 | 220.62 | 839.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 17-AUG-14:00 | 0.00 | -2763.34 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1264.23 | 0.00 | 220.62 | 842.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-JUL-15:30 | 0.00 | -63966.69 | 0.00 | 0.00 | 1192.13 | 4512.09 | 11708.34 | 21743.18 | 0.00 | 6366.73 | 18444.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 25-DEC-04:00 | 1992.93 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -845.26 | 0.00 | -1291.02 | -276.48 |
G NW APARTMENT | 25-DEC-08:35 | 2097.39 | 0.00 | 0.00 | 0.00 | 74.05 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -706.99 | 0.00 | -1195.27 | -677.13 |
OFFICE | 20-FEB-07:01 | 4792.58 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -239.89 | 0.00 | -352.43 | -4910.72 |
G NE APARTMENT | 25-DEC-04:00 | 2021.67 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -848.83 | 0.00 | -1291.02 | -301.65 |
G N1 APARTMENT | 14-OCT-06:01 | 1490.95 | 0.00 | 0.00 | 0.00 | 161.38 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -327.02 | 0.00 | -120.03 | -1630.05 |
G N2 APARTMENT | 14-OCT-06:01 | 1401.55 | 0.00 | 0.00 | 0.00 | 163.51 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -325.24 | 0.00 | -120.03 | -1544.54 |
G S1 APARTMENT | 02-JAN-08:01 | 1510.17 | 0.00 | 0.00 | 0.00 | 74.06 | 19.46 | 388.49 | 412.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42.33 | -2362.36 |
G S2 APARTMENT | 05-JAN-17:01 | 1623.85 | 0.00 | 0.00 | 0.00 | 98.76 | 64.86 | 588.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -414.65 | 0.00 | -228.73 | -1732.70 |
M SW APARTMENT | 25-DEC-03:15 | 4516.85 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -838.55 | 0.00 | -1881.93 | -2216.21 |
M NW APARTMENT | 13-FEB-11:00 | 4663.99 | 0.00 | 0.00 | 0.00 | 47.42 | 12.97 | 406.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -228.72 | 0.00 | -2127.32 | -2774.49 |
M SE APARTMENT | 25-DEC-02:30 | 4493.42 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -799.66 | 0.00 | -1893.97 | -2225.51 |
M NE APARTMENT | 25-DEC-01:15 | 4580.92 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 241.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -769.50 | 0.00 | -1902.89 | -2346.02 |
M N1 APARTMENT | 25-DEC-02:30 | 2487.98 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.99 | 0.00 | -1142.39 | -1267.32 |
M N2 APARTMENT | 25-DEC-02:30 | 2487.30 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.96 | 0.00 | -1142.39 | -1266.67 |
M S1 APARTMENT | 25-DEC-04:00 | 2352.51 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -519.86 | 0.00 | -1119.77 | -1132.71 |
M S2 APARTMENT | 25-DEC-04:00 | 2355.49 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -519.81 | 0.00 | -1119.77 | -1135.73 |
T SW APARTMENT | 25-DEC-03:00 | 3806.35 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -807.81 | 0.00 | -2501.13 | -923.13 |
T NW APARTMENT | 25-DEC-02:30 | 3816.42 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -808.06 | 0.00 | -2508.45 | -925.62 |
T SE APARTMENT | 25-DEC-02:45 | 3778.97 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -786.74 | 0.00 | -2504.98 | -912.98 |
T NE APARTMENT | 25-DEC-02:15 | 3768.64 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -787.12 | 0.00 | -2509.39 | -897.85 |
T N1 APARTMENT | 25-DEC-05:00 | 2562.43 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.46 | 0.00 | -1455.73 | -1006.05 |
T N2 APARTMENT | 25-DEC-05:00 | 2562.52 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -533.44 | 0.00 | -1455.68 | -1006.21 |
T S1 APARTMENT | 25-DEC-06:00 | 2535.08 | 0.00 | 0.00 | 0.00 | 189.67 | 42.16 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.93 | 0.00 | -1448.65 | -1045.44 |
T S2 APARTMENT | 25-DEC-06:00 | 2536.02 | 0.00 | 0.00 | 0.00 | 189.67 | 42.16 | 253.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -525.92 | 0.00 | -1448.65 | -1046.39 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-DEC-03:15 | 62648.87 | 0.00 | 0.00 | 0.00 | 4368.33 | 1952.47 | 5387.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16224.11 | 0.00 | -37105.36 | -21027.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Sec1.1A-General InformationData | |
Weather File | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 49.25 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 49.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4276.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 314.48 | 109274.00 | 0.00 | 0.00 |
Space Cooling | 145.81 | 28889.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 227.26 | 7206.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 389.06 | 19152.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26730.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1438.36 | 314.48 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1438.36 |
Natural Gas | 0.00 | 314.48 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1752.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 46.52 |
Fans-Interior | 72.50 |
Service Water Heating | 124.12 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.80 |
Subtotal | 458.86 |
Natural Gas [MJ/m2] | |
Space Heating | 100.33 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 100.33 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.76 |
Space Heating | 17.94 |
Space Cooling | 8.32 |
Fans-Interior | 12.97 |
Service Water Heating | 22.20 |
Receptacle Equipment | 29.53 |
Miscellaneous | 2.29 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.169909 |
G NW APARTMENT DIRECT AIR | 0.162384 |
OFFICE DIRECT AIR | 0.461572 |
G NE APARTMENT DIRECT AIR | 0.125464 |
G N1 APARTMENT DIRECT AIR | 0.095524 |
G N2 APARTMENT DIRECT AIR | 0.094591 |
G S1 APARTMENT DIRECT AIR | 0.106931 |
G S2 APARTMENT DIRECT AIR | 0.109779 |
M SW APARTMENT DIRECT AIR | 0.462407 |
M NW APARTMENT DIRECT AIR | 0.439782 |
M SE APARTMENT DIRECT AIR | 0.417480 |
M NE APARTMENT DIRECT AIR | 0.359691 |
M N1 APARTMENT DIRECT AIR | 0.270570 |
M N2 APARTMENT DIRECT AIR | 0.269013 |
M S1 APARTMENT DIRECT AIR | 0.305007 |
M S2 APARTMENT DIRECT AIR | 0.306044 |
T SW APARTMENT DIRECT AIR | 0.321636 |
T NW APARTMENT DIRECT AIR | 0.299862 |
T SE APARTMENT DIRECT AIR | 0.298270 |
T NE APARTMENT DIRECT AIR | 0.254892 |
T N1 APARTMENT DIRECT AIR | 0.198633 |
T N2 APARTMENT DIRECT AIR | 0.198696 |
T S1 APARTMENT DIRECT AIR | 0.239534 |
T S2 APARTMENT DIRECT AIR | 0.240179 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.169909 |
SPLIT GNW MAIN BRANCH | 0.162384 |
SPLIT OFFICE MAIN BRANCH | 0.461572 |
SPLIT GNE MAIN BRANCH | 0.125464 |
SPLIT GN1 MAIN BRANCH | 0.095524 |
SPLIT GN2 MAIN BRANCH | 0.094591 |
SPLIT GS1 MAIN BRANCH | 0.106931 |
SPLIT GS2 MAIN BRANCH | 0.109779 |
SPLIT MSW MAIN BRANCH | 0.462407 |
SPLIT MNW MAIN BRANCH | 0.439782 |
SPLIT MSE MAIN BRANCH | 0.417480 |
SPLIT MNE MAIN BRANCH | 0.359691 |
SPLIT MN1 MAIN BRANCH | 0.270570 |
SPLIT MN2 MAIN BRANCH | 0.269013 |
SPLIT MS1 MAIN BRANCH | 0.305007 |
SPLIT MS2 MAIN BRANCH | 0.306044 |
SPLIT TSW MAIN BRANCH | 0.321636 |
SPLIT TNW MAIN BRANCH | 0.299862 |
SPLIT TSE MAIN BRANCH | 0.298270 |
SPLIT TNE MAIN BRANCH | 0.254892 |
SPLIT TN1 MAIN BRANCH | 0.198633 |
SPLIT TN2 MAIN BRANCH | 0.198696 |
SPLIT TS1 MAIN BRANCH | 0.239534 |
SPLIT TS2 MAIN BRANCH | 0.240179 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.169909 |
SPLIT GNW | 0.162384 |
SPLIT OFFICE | 0.461572 |
SPLIT GNE | 0.125464 |
SPLIT GN1 | 0.095524 |
SPLIT GN2 | 0.094591 |
SPLIT GS1 | 0.106931 |
SPLIT GS2 | 0.109779 |
SPLIT MSW | 0.462407 |
SPLIT MNW | 0.439782 |
SPLIT MSE | 0.417480 |
SPLIT MNE | 0.359691 |
SPLIT MN1 | 0.270570 |
SPLIT MN2 | 0.269013 |
SPLIT MS1 | 0.305007 |
SPLIT MS2 | 0.306044 |
SPLIT TSW | 0.321636 |
SPLIT TNW | 0.299862 |
SPLIT TSE | 0.298270 |
SPLIT TNE | 0.254892 |
SPLIT TN1 | 0.198633 |
SPLIT TN2 | 0.198696 |
SPLIT TS1 | 0.239534 |
SPLIT TS2 | 0.240179 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.169909 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.162384 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.461572 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.125464 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.095524 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.094591 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.106931 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.109779 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.462407 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.439782 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.417480 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.359691 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.270570 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.269013 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.305007 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.306044 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.321636 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.299862 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.298270 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.254892 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.198633 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.198696 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.239534 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.240179 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.169909 | 3634.27 | 0.715532 |
SPLIT GNW COOLING COIL | 0.162384 | 3434.95 | 0.718709 |
SPLIT OFFICE COOLING COIL | 0.461572 | 8020.81 | 0.781229 |
SPLIT GNE COOLING COIL | 0.125464 | 2795.95 | 0.704101 |
SPLIT GN1 COOLING COIL | 0.095524 | 2239.95 | 0.690542 |
SPLIT GN2 COOLING COIL | 0.094591 | 2224.18 | 0.689827 |
SPLIT GS1 COOLING COIL | 0.106931 | 2546.71 | 0.686539 |
SPLIT GS2 COOLING COIL | 0.109779 | 2589.53 | 0.689007 |
SPLIT MSW COOLING COIL | 0.462407 | 9355.65 | 0.731803 |
SPLIT MNW COOLING COIL | 0.439782 | 8909.12 | 0.731424 |
SPLIT MSE COOLING COIL | 0.417480 | 8789.56 | 0.720069 |
SPLIT MNE COOLING COIL | 0.359691 | 7556.22 | 0.720705 |
SPLIT MN1 COOLING COIL | 0.270570 | 5879.33 | 0.711081 |
SPLIT MN2 COOLING COIL | 0.269013 | 5853.62 | 0.710693 |
SPLIT MS1 COOLING COIL | 0.305007 | 6717.00 | 0.707355 |
SPLIT MS2 COOLING COIL | 0.306044 | 6734.02 | 0.707593 |
SPLIT TSW COOLING COIL | 0.321636 | 6330.81 | 0.740199 |
SPLIT TNW COOLING COIL | 0.299862 | 5932.82 | 0.738604 |
SPLIT TSE COOLING COIL | 0.298270 | 5976.11 | 0.734755 |
SPLIT TNE COOLING COIL | 0.254892 | 5269.18 | 0.725405 |
SPLIT TN1 COOLING COIL | 0.198633 | 4175.83 | 0.720495 |
SPLIT TN2 COOLING COIL | 0.198696 | 4186.89 | 0.719822 |
SPLIT TS1 COOLING COIL | 0.239534 | 4860.73 | 0.730915 |
SPLIT TS2 COOLING COIL | 0.240179 | 4871.16 | 0.731079 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.169909 | 0.169909 | 0.169909 | 0.169909 | 2963.30 | 3634.27 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.162384 | 0.162384 | 0.162384 | 0.162384 | 2940.52 | 3434.95 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.461572 | 0.461572 | 0.461572 | 0.461572 | 5176.62 | 8020.81 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.125464 | 0.125464 | 0.125464 | 0.125464 | 2933.44 | 2795.95 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.095524 | 0.095524 | 0.095524 | 0.095524 | 2200.11 | 2239.95 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.094591 | 0.094591 | 0.094591 | 0.094591 | 2199.94 | 2224.18 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.106931 | 0.106931 | 0.106931 | 0.106931 | 2188.79 | 2546.71 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.109779 | 0.109779 | 0.109779 | 0.109779 | 2304.81 | 2589.53 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.462407 | 0.462407 | 0.462407 | 0.462407 | 5889.43 | 9355.65 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.439782 | 0.439782 | 0.439782 | 0.439782 | 5920.90 | 8909.12 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.417480 | 0.417480 | 0.417480 | 0.417480 | 5870.67 | 8789.56 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.359691 | 0.359691 | 0.359691 | 0.359691 | 5902.14 | 7556.22 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.270570 | 0.270570 | 0.270570 | 0.270570 | 4033.26 | 5879.33 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.269013 | 0.269013 | 0.269013 | 0.269013 | 4032.78 | 5853.62 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.305007 | 0.305007 | 0.305007 | 0.305007 | 4003.65 | 6717.00 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.306044 | 0.306044 | 0.306044 | 0.306044 | 4003.17 | 6734.02 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.321636 | 0.321636 | 0.321636 | 0.321636 | 4373.07 | 6330.81 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.299862 | 0.299862 | 0.299862 | 0.299862 | 4391.13 | 5932.82 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.298270 | 0.298270 | 0.298270 | 0.298270 | 4363.26 | 5976.11 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.254892 | 0.254892 | 0.254892 | 0.254892 | 4381.32 | 5269.18 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.198633 | 0.198633 | 0.198633 | 0.198633 | 3344.55 | 4175.83 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.198696 | 0.198696 | 0.198696 | 0.198696 | 3344.28 | 4186.89 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.239534 | 0.239534 | 0.239534 | 0.239534 | 3324.47 | 4860.73 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.240179 | 0.240179 | 0.240179 | 0.240179 | 3324.20 | 4871.16 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.169909 |
SPLIT GNW SUPPLY FAN | 0.162384 |
SPLIT OFFICE SUPPLY FAN | 0.461572 |
SPLIT GNE SUPPLY FAN | 0.125464 |
SPLIT GN1 SUPPLY FAN | 0.095524 |
SPLIT GN2 SUPPLY FAN | 0.094591 |
SPLIT GS1 SUPPLY FAN | 0.106931 |
SPLIT GS2 SUPPLY FAN | 0.109779 |
SPLIT MSW SUPPLY FAN | 0.462407 |
SPLIT MNW SUPPLY FAN | 0.439782 |
SPLIT MSE SUPPLY FAN | 0.417480 |
SPLIT MNE SUPPLY FAN | 0.359691 |
SPLIT MN1 SUPPLY FAN | 0.270570 |
SPLIT MN2 SUPPLY FAN | 0.269013 |
SPLIT MS1 SUPPLY FAN | 0.305007 |
SPLIT MS2 SUPPLY FAN | 0.306044 |
SPLIT TSW SUPPLY FAN | 0.321636 |
SPLIT TNW SUPPLY FAN | 0.299862 |
SPLIT TSE SUPPLY FAN | 0.298270 |
SPLIT TNE SUPPLY FAN | 0.254892 |
SPLIT TN1 SUPPLY FAN | 0.198633 |
SPLIT TN2 SUPPLY FAN | 0.198696 |
SPLIT TS1 SUPPLY FAN | 0.239534 |
SPLIT TS2 SUPPLY FAN | 0.240179 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 2963.30 |
SPLIT GNW HEATING COIL | 2940.52 |
SPLIT OFFICE HEATING COIL | 5176.62 |
SPLIT GNE HEATING COIL | 2933.44 |
SPLIT GN1 HEATING COIL | 2200.11 |
SPLIT GN2 HEATING COIL | 2199.94 |
SPLIT GS1 HEATING COIL | 2188.79 |
SPLIT GS2 HEATING COIL | 2304.81 |
SPLIT MSW HEATING COIL | 5889.43 |
SPLIT MNW HEATING COIL | 5920.90 |
SPLIT MSE HEATING COIL | 5870.67 |
SPLIT MNE HEATING COIL | 5902.14 |
SPLIT MN1 HEATING COIL | 4033.26 |
SPLIT MN2 HEATING COIL | 4032.78 |
SPLIT MS1 HEATING COIL | 4003.65 |
SPLIT MS2 HEATING COIL | 4003.17 |
SPLIT TSW HEATING COIL | 4373.07 |
SPLIT TNW HEATING COIL | 4391.13 |
SPLIT TSE HEATING COIL | 4363.26 |
SPLIT TNE HEATING COIL | 4381.32 |
SPLIT TN1 HEATING COIL | 3344.55 |
SPLIT TN2 HEATING COIL | 3344.28 |
SPLIT TS1 HEATING COIL | 3324.47 |
SPLIT TS2 HEATING COIL | 3324.20 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:47:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -0.5 |
February | 21.75 | 2.24 |
March | 22.08 | 8.00 |
April | 22.57 | 13.18 |
May | 23.40 | 18.32 |
June | 24.34 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.33 | 20.44 |
October | 22.94 | 12.66 |
November | 22.10 | 8.91 |
December | 21.81 | 2.07 |
Annual Sum or Average | 22.99 | 13.21 |
Minimum of Months | 21.71 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.71 | 2.24 |
March | 21.89 | 8.00 |
April | 22.28 | 13.18 |
May | 23.31 | 18.32 |
June | 24.35 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.28 | 20.44 |
October | 22.49 | 12.66 |
November | 21.79 | 8.91 |
December | 21.73 | 2.07 |
Annual Sum or Average | 22.87 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | -0.5 |
February | 20.81 | 2.24 |
March | 22.22 | 8.00 |
April | 23.53 | 13.18 |
May | 24.49 | 18.32 |
June | 26.34 | 22.93 |
July | 26.90 | 25.34 |
August | 26.64 | 24.28 |
September | 26.25 | 20.44 |
October | 23.77 | 12.66 |
November | 22.65 | 8.91 |
December | 20.91 | 2.07 |
Annual Sum or Average | 23.75 | 13.21 |
Minimum of Months | 20.28 | -0.5 |
Maximum of Months | 26.90 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.70 | 2.24 |
March | 21.85 | 8.00 |
April | 22.22 | 13.18 |
May | 23.25 | 18.32 |
June | 24.34 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.27 | 20.44 |
October | 22.41 | 12.66 |
November | 21.75 | 8.91 |
December | 21.72 | 2.07 |
Annual Sum or Average | 22.84 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.71 | 2.24 |
March | 21.84 | 8.00 |
April | 22.10 | 13.18 |
May | 23.13 | 18.32 |
June | 24.34 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.28 | 20.44 |
October | 22.39 | 12.66 |
November | 21.76 | 8.91 |
December | 21.73 | 2.07 |
Annual Sum or Average | 22.82 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.71 | 2.24 |
March | 21.84 | 8.00 |
April | 22.09 | 13.18 |
May | 23.13 | 18.32 |
June | 24.34 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.27 | 20.44 |
October | 22.38 | 12.66 |
November | 21.76 | 8.91 |
December | 21.72 | 2.07 |
Annual Sum or Average | 22.82 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -0.5 |
February | 21.75 | 2.24 |
March | 22.06 | 8.00 |
April | 22.47 | 13.18 |
May | 23.29 | 18.32 |
June | 24.34 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.34 | 20.44 |
October | 22.99 | 12.66 |
November | 22.13 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 22.98 | 13.21 |
Minimum of Months | 21.71 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -0.5 |
February | 21.75 | 2.24 |
March | 22.08 | 8.00 |
April | 22.51 | 13.18 |
May | 23.33 | 18.32 |
June | 24.35 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.36 | 20.44 |
October | 23.02 | 12.66 |
November | 22.15 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.00 | 13.21 |
Minimum of Months | 21.71 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | -0.5 |
February | 21.94 | 2.24 |
March | 22.83 | 8.00 |
April | 24.14 | 13.18 |
May | 24.32 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 23.95 | 12.66 |
November | 23.29 | 8.91 |
December | 22.13 | 2.07 |
Annual Sum or Average | 23.50 | 13.21 |
Minimum of Months | 21.78 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.75 | 2.24 |
March | 22.21 | 8.00 |
April | 23.92 | 13.18 |
May | 24.30 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.39 | 20.44 |
October | 23.60 | 12.66 |
November | 22.29 | 8.91 |
December | 21.84 | 2.07 |
Annual Sum or Average | 23.27 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | -0.5 |
February | 21.93 | 2.24 |
March | 22.84 | 8.00 |
April | 24.13 | 13.18 |
May | 24.32 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 23.94 | 12.66 |
November | 23.25 | 8.91 |
December | 22.09 | 2.07 |
Annual Sum or Average | 23.49 | 13.21 |
Minimum of Months | 21.76 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.73 | 2.24 |
March | 22.17 | 8.00 |
April | 23.86 | 13.18 |
May | 24.29 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.39 | 20.44 |
October | 23.56 | 12.66 |
November | 22.18 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.25 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -0.5 |
February | 21.76 | 2.24 |
March | 22.23 | 8.00 |
April | 24.00 | 13.18 |
May | 24.34 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 23.71 | 12.66 |
November | 22.42 | 8.91 |
December | 21.88 | 2.07 |
Annual Sum or Average | 23.31 | 13.21 |
Minimum of Months | 21.71 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | -0.5 |
February | 21.76 | 2.24 |
March | 22.22 | 8.00 |
April | 24.00 | 13.18 |
May | 24.34 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 23.71 | 12.66 |
November | 22.41 | 8.91 |
December | 21.88 | 2.07 |
Annual Sum or Average | 23.31 | 13.21 |
Minimum of Months | 21.71 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | -0.5 |
February | 22.08 | 2.24 |
March | 23.12 | 8.00 |
April | 24.25 | 13.18 |
May | 24.36 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 24.12 | 12.66 |
November | 23.69 | 8.91 |
December | 22.30 | 2.07 |
Annual Sum or Average | 23.62 | 13.21 |
Minimum of Months | 21.87 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | -0.5 |
February | 22.08 | 2.24 |
March | 23.13 | 8.00 |
April | 24.25 | 13.18 |
May | 24.36 | 18.32 |
June | 24.40 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.40 | 20.44 |
October | 24.11 | 12.66 |
November | 23.68 | 8.91 |
December | 22.30 | 2.07 |
Annual Sum or Average | 23.62 | 13.21 |
Minimum of Months | 21.87 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | -0.5 |
February | 21.91 | 2.24 |
March | 22.52 | 8.00 |
April | 23.51 | 13.18 |
May | 24.04 | 18.32 |
June | 24.37 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.32 | 20.44 |
October | 23.43 | 12.66 |
November | 22.57 | 8.91 |
December | 22.00 | 2.07 |
Annual Sum or Average | 23.27 | 13.21 |
Minimum of Months | 21.76 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.75 | 2.24 |
March | 22.16 | 8.00 |
April | 23.29 | 13.18 |
May | 24.00 | 18.32 |
June | 24.36 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.27 | 20.44 |
October | 23.03 | 12.66 |
November | 22.03 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.11 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | -0.5 |
February | 21.90 | 2.24 |
March | 22.54 | 8.00 |
April | 23.50 | 13.18 |
May | 24.04 | 18.32 |
June | 24.37 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.31 | 20.44 |
October | 23.42 | 12.66 |
November | 22.53 | 8.91 |
December | 21.96 | 2.07 |
Annual Sum or Average | 23.27 | 13.21 |
Minimum of Months | 21.74 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.73 | 2.24 |
March | 22.12 | 8.00 |
April | 23.24 | 13.18 |
May | 23.98 | 18.32 |
June | 24.36 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.26 | 20.44 |
October | 22.99 | 12.66 |
November | 21.96 | 8.91 |
December | 21.80 | 2.07 |
Annual Sum or Average | 23.08 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.74 | 2.24 |
March | 22.13 | 8.00 |
April | 23.35 | 13.18 |
May | 24.04 | 18.32 |
June | 24.37 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.29 | 20.44 |
October | 23.06 | 12.66 |
November | 22.00 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.12 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -0.5 |
February | 21.74 | 2.24 |
March | 22.13 | 8.00 |
April | 23.35 | 13.18 |
May | 24.04 | 18.32 |
June | 24.37 | 22.93 |
July | 24.40 | 25.34 |
August | 24.39 | 24.28 |
September | 24.29 | 20.44 |
October | 23.05 | 12.66 |
November | 22.00 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 23.11 | 13.21 |
Minimum of Months | 21.70 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -0.5 |
February | 21.97 | 2.24 |
March | 22.63 | 8.00 |
April | 23.68 | 13.18 |
May | 24.12 | 18.32 |
June | 24.38 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.35 | 20.44 |
October | 23.57 | 12.66 |
November | 22.72 | 8.91 |
December | 22.06 | 2.07 |
Annual Sum or Average | 23.35 | 13.21 |
Minimum of Months | 21.80 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | -0.5 |
February | 21.97 | 2.24 |
March | 22.64 | 8.00 |
April | 23.68 | 13.18 |
May | 24.12 | 18.32 |
June | 24.38 | 22.93 |
July | 24.40 | 25.34 |
August | 24.40 | 24.28 |
September | 24.35 | 20.44 |
October | 23.57 | 12.66 |
November | 22.72 | 8.91 |
December | 22.06 | 2.07 |
Annual Sum or Average | 23.35 | 13.21 |
Minimum of Months | 21.80 | -0.5 |
Maximum of Months | 24.40 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | -0.5 |
February | 21.40 | 2.24 |
March | 22.79 | 8.00 |
April | 24.63 | 13.18 |
May | 25.84 | 18.32 |
June | 26.74 | 22.93 |
July | 27.04 | 25.34 |
August | 26.92 | 24.28 |
September | 26.30 | 20.44 |
October | 24.31 | 12.66 |
November | 22.74 | 8.91 |
December | 21.39 | 2.07 |
Annual Sum or Average | 24.27 | 13.21 |
Minimum of Months | 20.93 | -0.5 |
Maximum of Months | 27.04 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.40 | -0.5 |
February | 19.02 | 2.24 |
March | 20.48 | 8.00 |
April | 21.95 | 13.18 |
May | 23.53 | 18.32 |
June | 25.95 | 22.93 |
July | 26.62 | 25.34 |
August | 26.42 | 24.28 |
September | 25.48 | 20.44 |
October | 22.26 | 12.66 |
November | 20.80 | 8.91 |
December | 19.09 | 2.07 |
Annual Sum or Average | 22.52 | 13.21 |
Minimum of Months | 18.40 | -0.5 |
Maximum of Months | 26.62 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:47:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | -0.5 |
February | 23.12 | 2.24 |
March | 24.19 | 8.00 |
April | 25.96 | 13.18 |
May | 26.48 | 18.32 |
June | 26.84 | 22.93 |
July | 26.95 | 25.34 |
August | 26.90 | 24.28 |
September | 26.67 | 20.44 |
October | 25.76 | 12.66 |
November | 24.55 | 8.91 |
December | 23.23 | 2.07 |
Annual Sum or Average | 25.30 | 13.21 |
Minimum of Months | 22.84 | -0.5 |
Maximum of Months | 26.95 | 25.34 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:16
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.114521E+12 | 73480.652 | 02-JAN-18:15 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32110.461 | 0.000 | 0.000 | 0.000 |
February | 0.103548E+12 | 70262.452 | 07-FEB-18:00 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28892.260 | 0.000 | 0.000 | 0.000 |
March | 0.114773E+12 | 74433.157 | 28-MAR-16:45 | 4276.255 | 26730.986 | 7206.318 | 0.000 | 11910.405 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24309.193 | 0.000 | 0.000 | 0.000 |
April | 0.111653E+12 | 70259.445 | 09-APR-17:00 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 4229.753 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27212.501 | 0.000 | 0.000 | 0.000 |
May | 0.123419E+12 | 80100.947 | 29-MAY-17:15 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 21139.559 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20144.196 | 0.000 | 0.000 | 0.000 |
June | 0.130418E+12 | 82480.940 | 29-JUN-16:30 | 4276.255 | 26730.986 | 7206.318 | 0.000 | 25100.617 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19166.763 | 0.000 | 0.000 | 0.000 |
July | 0.141687E+12 | 86255.132 | 09-JUL-16:30 | 4276.255 | 26730.986 | 7206.318 | 0.000 | 28889.374 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19152.199 | 0.000 | 0.000 | 0.000 |
August | 0.138183E+12 | 83784.852 | 13-AUG-16:00 | 4276.255 | 26730.986 | 7206.318 | 0.000 | 26435.800 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19135.493 | 0.000 | 0.000 | 0.000 |
September | 0.124458E+12 | 85147.331 | 02-SEP-16:15 | 4276.255 | 26630.920 | 7206.318 | 0.000 | 23911.821 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23122.017 | 0.000 | 0.000 | 0.000 |
October | 0.114202E+12 | 71933.292 | 02-OCT-17:30 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 9614.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23501.664 | 0.000 | 0.000 | 0.000 |
November | 0.108245E+12 | 67651.701 | 29-NOV-18:15 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26281.510 | 0.000 | 0.000 | 0.000 |
December | 0.113257E+12 | 68858.641 | 27-DEC-18:45 | 4979.953 | 26630.920 | 7206.318 | 0.000 | 0.000 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 27488.449 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.143836E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.103548E+12 | 67651.701 | 4276.255 | 26630.920 | 7206.318 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19135.493 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.141687E+12 | 86255.132 | 4979.953 | 26730.986 | 7206.318 | 0.000 | 28889.374 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 32110.461 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:47:16
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.101971E+12 | 99577.070 | 18-JAN-04:00 | 99577.070 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 99577.070 |
February | 0.736810E+11 | 98912.258 | 13-FEB-02:00 | 98912.258 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 98912.258 |
March | 0.292843E+11 | 51832.814 | 18-MAR-01:00 | 51832.814 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 51832.814 |
April | 0.356713E+10 | 24857.964 | 17-APR-04:00 | 24857.964 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 24857.964 |
May | 0.732273E+09 | 14401.992 | 05-MAY-04:00 | 14401.992 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14401.992 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.656559E+10 | 29226.784 | 27-OCT-06:30 | 29226.784 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 29226.784 |
November | 0.183519E+11 | 38278.106 | 23-NOV-04:00 | 38278.106 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 38278.106 |
December | 0.803272E+11 | 109273.997 | 25-DEC-06:00 | 109273.997 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 109273.997 |
Annual Sum or Average | 0.314481E+12 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.101971E+12 | 109273.997 | 109273.997 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 109273.997 |