Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47

Tabular Output Report in Format: HTML

Building: Mid-Rise Apartment

Environment: RIYADH - SAU IWEC Data WMO#=404380

Simulation Timestamp: 2015-09-09 18:48:04


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1724.77 550.24 610.76
Net Site Energy 1724.77 550.24 610.76
Total Source Energy 5451.55 1739.14 1930.45
Net Source Energy 5451.55 1739.14 1930.45


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3134.61
Net Conditioned Building Area 2823.98
Unconditioned Building Area 310.64


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 5.19 0.00 0.00 0.00 0.00
Cooling 412.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting 118.46 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 40.15 0.00 0.00 0.00 0.00 0.00
Interior Equipment 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 349.85 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 281.43 0.00 0.00 0.00 0.00 1874.72
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1719.58 5.19 0.00 0.00 0.00 1874.72
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 5.19 0.00 0.00 0.00 0.00
Cooling General 412.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 96.36 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 22.11 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 40.15 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 517.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 349.85 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 281.43 0.00 0.00 0.00 0.00 1874.72
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.17 0.00 0.00 0.00 0.00 0.00
HVAC 369.45 1.84 0.00 0.00 0.00 0.66
Other 183.31 0.00 0.00 0.00 0.00 0.00
Total 608.92 1.84 0.00 0.00 0.00 0.66


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.60 0.00 0.00 0.00 0.00 0.00
HVAC 332.84 1.66 0.00 0.00 0.00 0.60
Other 165.14 0.00 0.00 0.00 0.00 0.00
Total 548.58 1.66 0.00 0.00 0.00 0.60


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1719.58 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1719.58 100.00
     
Total On-Site and Utility Electric Sources 1719.58 100.00
Total Electricity End Uses 1719.58 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 1874.72 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 1874.72 100.00
Total Water End Uses 1874.72 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.50
Time Setpoint Not Met During Occupied Cooling 85.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 99.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

MONTHLY INDOOR TEMP

| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:47
RunPeriod RIYADH - SAU IWEC Data WMO#=404380
Weather File RIYADH - SAU IWEC Data WMO#=404380
Latitude [deg] 24.70
Longitude [deg] 46.80
Elevation [m] 612.00
Time Zone 3.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1542.04 564.80 206.22 564.80 206.22
Window Opening Area [m2] 306.92 112.97 37.16 112.97 43.82
Window-Wall Ratio [%] 19.90 20.00 18.02 20.00 21.25


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1501.17 564.80 185.79 564.80 185.79
Window Opening Area [m2] 300.26 112.97 37.16 112.97 37.16
Window-Wall Ratio [%] 20.00 20.00 20.00 20.00 20.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 783.65
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
G SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
OFFICE 88.25 Yes Yes 268.97 1.00 58.52 11.71 26.1977 88.25 6.6700
G NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
G N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
G S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
M SW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NW APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M SE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M NE APARTMENT 88.25 Yes Yes 268.97 2.00 58.52 11.71 3.6746 35.30 6.6700
M N1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M N2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S1 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
M S2 APARTMENT 88.25 Yes Yes 268.97 2.00 35.30 7.06 3.6746 35.30 6.6700
T SW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NW APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T SE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T NE APARTMENT 88.25 Yes Yes 268.97 1.00 58.52 11.71 3.6746 35.30 6.6700
T N1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T N2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S1 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T S2 APARTMENT 88.25 Yes Yes 268.97 1.00 35.30 7.06 3.6746 35.30 6.6700
T CORRIDOR 77.66 No Yes 236.69 1.00 10.22 1.11 5.9540   0.0000
G CORRIDOR 77.66 No Yes 236.69 1.00 10.22 3.32 5.9540   208.8202
M CORRIDOR 77.66 No Yes 236.69 2.00 10.22 1.11 5.9540   0.0000
Total 3134.61     9553.84   1542.04 306.92 4.5346 39.93 11.1825
Conditioned Total 2823.98     8607.06   1501.17 300.26 4.3785 35.97 6.6700
Unconditioned Total 310.64     946.78   40.87 6.66 5.9540   52.2051
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 30-JUL-17:15 09-JAN-04:00 - - - 01-JAN-07:15
Heating 0.00 22560.99 0.00 0.00 0.00 0.00
Cooling 37953.63 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4979.95 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 11093.54 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 16912.62 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 97570.67 22560.99 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 22560.99 0.00 0.00 0.00 0.00
Cooling General 37953.63 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 4056.31 0.00 0.00 0.00 0.00 0.00
  GeneralLights-plugin 923.64 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 26630.92 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 11093.54 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 16912.62 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 5.63 0.00 0.00 0.00
Cooling 1304.94 0.00 0.00 0.00 0.00
Interior Lighting 375.17 0.00 0.00 0.00 0.00
Exterior Lighting 127.16 0.00 0.00 0.00 0.00
Interior Equipment 1639.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 1107.96 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 891.28 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 5445.92 5.63 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.99 0.00 0.00 0.00
Cooling 462.09 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.03 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 392.34 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 315.61 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1928.46 1.99 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.99 0.00 0.00 0.00
Cooling 462.09 0.00 0.00 0.00 0.00
Interior Lighting 132.85 0.00 0.00 0.00 0.00
Exterior Lighting 45.03 0.00 0.00 0.00 0.00
Interior Equipment 580.53 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 392.34 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 315.61 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1928.46 1.99 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
RIYADH ANN HTG 99.6% CONDNS DB 5.90 0.00 5.90 Wetbulb [C] 1.60 320.00
RIYADH ANN CLG .4% CONDNS DB=>MWB 44.20 13.50 18.70 Wetbulb [C] 4.50 0.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
G SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR SWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
G GFLOOR NWA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR SEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
G GFLOOR NEA EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
G GFLOOR N2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S1A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
G SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
G GFLOOR S2A EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 88.25 90.00 180.00  
M WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 46.45 270.00 90.00 W
M EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 46.45 90.00 90.00 E
M NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 70.60 0.00 90.00 N
M SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
M SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 70.60 180.00 90.00 S
T WWALL SWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T SWALL SWA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NWA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T WWALL NWA RES_EXT_WALL 0.30 0.704 0.787 23.22 270.00 90.00 W
T ROOF NWA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T EWALL SEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T SWALL SEA RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF SEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL NEA RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T EWALL NEA RES_EXT_WALL 0.30 0.704 0.787 23.22 90.00 90.00 E
T ROOF NEA RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N1A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T NWALL N2A RES_EXT_WALL 0.30 0.704 0.787 35.30 0.00 90.00 N
T ROOF N2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S1A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S1A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T SWALL S2A RES_EXT_WALL 0.30 0.704 0.787 35.30 180.00 90.00 S
T ROOF S2A RES_ROOF 0.30 0.269 0.283 88.25 180.00 0.00  
T WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
T EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
T ROOF C RES_ROOF 0.30 0.269 0.283 77.66 180.00 0.00  
G WWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 270.00 90.00 W
G EWALL C RES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
G FLOOR C INT_SLAB_CEILING 0.30 1.986 3.839 77.66 90.00 180.00  
M WWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 270.00 90.00 W
M EWALL C RES_EXT_WALL 0.30 0.704 0.787 10.22 90.00 90.00 E


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
GWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SWA 180.00 90.00 S
GWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL SWA 270.00 90.00 W
GWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NWA 0.00 90.00 N
GWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G WWALL NWA 270.00 90.00 W
GWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL SEA 180.00 90.00 S
GWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL SEA 90.00 90.00 E
GWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL NEA 0.00 90.00 N
GWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No G EWALL NEA 90.00 90.00 E
GWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N1A 0.00 90.00 N
GWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G NWALL N2A 0.00 90.00 N
GWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S1A 180.00 90.00 S
GWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No G SWALL S2A 180.00 90.00 S
MWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL SWA 270.00 90.00 W
MWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SWA 180.00 90.00 S
MWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NWA 0.00 90.00 N
MWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M WWALL NWA 270.00 90.00 W
MWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL SEA 90.00 90.00 E
MWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL SEA 180.00 90.00 S
MWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL NEA 0.00 90.00 N
MWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 9.29 5.778 0.306 0.155     No M EWALL NEA 90.00 90.00 E
MWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N1A 0.00 90.00 N
MWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M NWALL N2A 0.00 90.00 N
MWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S1A 180.00 90.00 S
MWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 14.12 5.778 0.306 0.155     No M SWALL S2A 180.00 90.00 S
TWINDOW1 W SWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL SWA 270.00 90.00 W
TWINDOW1 S SWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SWA 180.00 90.00 S
TWINDOW1 N NWA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NWA 0.00 90.00 N
TWINDOW1 W NWA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T WWALL NWA 270.00 90.00 W
TWINDOW1 E SEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL SEA 90.00 90.00 E
TWINDOW1 S SEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL SEA 180.00 90.00 S
TWINDOW1 N NEA WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL NEA 0.00 90.00 N
TWINDOW1 E NEA WINDOW_U_1.22_SHGC_0.25 4.65 0.00 0.00 4.65 4.65 5.778 0.306 0.155     No T EWALL NEA 90.00 90.00 E
TWINDOW1 N N1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N1A 0.00 90.00 N
TWINDOW1 N N2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T NWALL N2A 0.00 90.00 N
TWINDOW1 S S1A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S1A 180.00 90.00 S
TWINDOW1 S S2A WINDOW_U_1.22_SHGC_0.25 7.06 0.00 0.00 7.06 7.06 5.778 0.306 0.155     No T SWALL S2A 180.00 90.00 S
TWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No T EWALL C 270.00 90.00 W
ENTRANCE DOOR WINDOW_U_1.22_SHGC_0.25 3.32 0.00 0.00 3.32 3.32 5.778 0.306 0.155     No G EWALL C 270.00 90.00 W
MWINDOW14 WINDOW_U_1.22_SHGC_0.25 1.11 0.00 0.00 1.11 2.23 5.778 0.306 0.155     No M EWALL C 270.00 90.00 W
Total or Average           306.92 5.778 0.306 0.155              
North Total or Average           112.97 5.778 0.306 0.155              
Non-North Total or Average           193.95 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
GWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
GWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
GWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
GWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
GWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
MWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
MWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
MWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 W SWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 S SWA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NWA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 W NWA 0.00 0.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00
TWINDOW1 E SEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 S SEA 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 N NEA 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 E NEA 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
TWINDOW1 N N1A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 N N2A 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
TWINDOW1 S S1A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW1 S S2A 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
TWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
ENTRANCE DOOR 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
MWINDOW14 1.00 1.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
LIGHTING_HARDWIRED_GSW G SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GNW G NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_HARDWIRED_GNE G NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN1 G N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GN2 G N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS1 G S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GS2 G S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSW M SW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNW M NW APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MSE M SE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MNE M NE APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN1 M N1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MN2 M N2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS1 M S1 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_MS2 M S2 APARTMENT 2.7059 176.50 477.59 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSW T SW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNW T NW APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TSE T SE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TNE T NE APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN1 T N1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TN2 T N2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS1 T S1 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_TS2 T S2 APARTMENT 2.7059 88.25 238.79 GeneralLights LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.80
LIGHTING_HARDWIRED_GC G CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_MC M CORRIDOR 5.9540 155.32 924.77 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_HARDWIRED_TC T CORRIDOR 5.9540 77.66 462.39 GeneralLights LTG_COR_SCH 168.00 168.00 168.00 0.0000 N 14.58
LIGHTING_PLUGIN_GSW G SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GNW G NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_OFFICE OFFICE 13.0989 88.25 1155.96 GeneralLights-plugin LTG_OFF_SCH 62.17 168.00 60.95 0.0000 Y 13.23
LIGHTING_PLUGIN_GNE G NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN1 G N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GN2 G N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS1 G S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_GS2 G S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSW M SW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNW M NW APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MSE M SE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MNE M NE APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN1 M N1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MN2 M N2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS1 M S1 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_MS2 M S2 APARTMENT 0.9688 176.50 170.98 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSW T SW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNW T NW APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TSE T SE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TNE T NE APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN1 T N1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TN2 T N2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS1 T S1 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
LIGHTING_PLUGIN_TS2 T S2 APARTMENT 0.9688 88.25 85.49 GeneralLights-plugin LTG_APT_SCH 17.85 168.00 17.85 0.0000 Y 0.29
Interior Lighting Total   2.3855 5958.59 14214.30               95.19


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
FACADE LIGHTING 2553.00 AstronomicalClock -   83.78 83.78 40.15
Exterior Lighting Total 2553.00           40.15



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed   5259.89 4059.53 1200.37 0.77 3.91    
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed   5233.09 4073.34 1159.75 0.78 3.91    
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   9745.98 7783.68 1962.30 0.80 3.91    
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed   4375.08 3398.33 976.75 0.78 3.91    
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3141.83 2440.97 700.86 0.78 3.91    
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3128.53 2430.42 698.12 0.78 3.91    
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   3183.99 2413.92 770.08 0.76 3.91    
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   3244.39 2448.89 795.50 0.75 3.91    
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed   12365.62 9614.77 2750.84 0.78 3.91    
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed   12353.48 9677.24 2676.24 0.78 3.91    
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed   10964.42 8463.45 2500.97 0.77 3.91    
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed   10666.24 8327.07 2339.17 0.78 3.91    
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   7616.03 5944.70 1671.33 0.78 3.91    
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   7594.97 5928.02 1666.95 0.78 3.91    
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   7649.61 5853.90 1795.71 0.77 3.91    
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   7679.73 5863.62 1816.11 0.76 3.91    
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed   8281.58 6460.41 1821.16 0.78 3.91    
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed   8281.09 6472.75 1808.34 0.78 3.91    
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed   7482.21 5812.53 1669.68 0.78 3.91    
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed   7408.17 5754.89 1653.28 0.78 3.91    
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5705.92 4400.57 1305.36 0.77 3.91    
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5694.04 4391.29 1302.75 0.77 3.91    
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed   5781.79 4450.08 1331.71 0.77 3.91    
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed   5779.09 4447.96 1331.12 0.77 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
SPLIT GSW COOLING COIL Coil:Cooling:DX:SingleSpeed 5028.8 3.17 10.83 11.26 10.61
SPLIT GNW COOLING COIL Coil:Cooling:DX:SingleSpeed 4998.8 3.16 10.79 11.22 10.55
SPLIT OFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 9284.6 3.13 10.67 11.09 10.38
SPLIT GNE COOLING COIL Coil:Cooling:DX:SingleSpeed 4180.1 3.17 10.80 11.23 10.56
SPLIT GN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3001.8 3.17 10.80 11.23 10.56
SPLIT GN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 2989.1 3.17 10.80 11.23 10.56
SPLIT GS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 3049.6 3.20 10.91 11.35 10.73
SPLIT GS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 3108.9 3.20 10.93 11.37 10.76
SPLIT MSW COOLING COIL Coil:Cooling:DX:SingleSpeed 11813.4 3.16 10.80 11.22 10.56
SPLIT MNW COOLING COIL Coil:Cooling:DX:SingleSpeed 11792.6 3.15 10.76 11.19 10.51
SPLIT MSE COOLING COIL Coil:Cooling:DX:SingleSpeed 10482.6 3.17 10.83 11.26 10.61
SPLIT MNE COOLING COIL Coil:Cooling:DX:SingleSpeed 10185.6 3.16 10.78 11.20 10.53
SPLIT MN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 7273.0 3.16 10.78 11.20 10.53
SPLIT MN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 7252.9 3.16 10.78 11.20 10.53
SPLIT MS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 7319.9 3.19 10.87 11.30 10.67
SPLIT MS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 7350.4 3.19 10.88 11.32 10.68
SPLIT TSW COOLING COIL Coil:Cooling:DX:SingleSpeed 7909.0 3.16 10.78 11.21 10.54
SPLIT TNW COOLING COIL Coil:Cooling:DX:SingleSpeed 7907.0 3.16 10.77 11.20 10.52
SPLIT TSE COOLING COIL Coil:Cooling:DX:SingleSpeed 7148.7 3.17 10.80 11.23 10.56
SPLIT TNE COOLING COIL Coil:Cooling:DX:SingleSpeed 7078.0 3.17 10.80 11.23 10.56
SPLIT TN1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5455.7 3.18 10.83 11.27 10.61
SPLIT TN2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5444.3 3.18 10.83 11.27 10.61
SPLIT TS1 COOLING COIL Coil:Cooling:DX:SingleSpeed 5529.4 3.18 10.84 11.28 10.63
SPLIT TS2 COOLING COIL Coil:Cooling:DX:SingleSpeed 5526.8 3.18 10.84 11.28 10.63
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SPLIT GSW HEATING COIL Coil:Heating:Gas   1449.18 0.80
SPLIT GNW HEATING COIL Coil:Heating:Gas   1439.46 0.80
SPLIT OFFICE HEATING COIL Coil:Heating:Gas   2806.95 0.80
SPLIT GNE HEATING COIL Coil:Heating:Gas   1433.26 0.80
SPLIT GN1 HEATING COIL Coil:Heating:Gas   1287.47 0.80
SPLIT GN2 HEATING COIL Coil:Heating:Gas   1287.47 0.80
SPLIT GS1 HEATING COIL Coil:Heating:Gas   1287.47 0.80
SPLIT GS2 HEATING COIL Coil:Heating:Gas   1287.47 0.80
SPLIT MSW HEATING COIL Coil:Heating:Gas   2929.10 0.80
SPLIT MNW HEATING COIL Coil:Heating:Gas   2955.86 0.80
SPLIT MSE HEATING COIL Coil:Heating:Gas   2911.82 0.80
SPLIT MNE HEATING COIL Coil:Heating:Gas   2938.65 0.80
SPLIT MN1 HEATING COIL Coil:Heating:Gas   2574.94 0.80
SPLIT MN2 HEATING COIL Coil:Heating:Gas   2574.94 0.80
SPLIT MS1 HEATING COIL Coil:Heating:Gas   2574.94 0.80
SPLIT MS2 HEATING COIL Coil:Heating:Gas   2574.94 0.80
SPLIT TSW HEATING COIL Coil:Heating:Gas   2152.60 0.80
SPLIT TNW HEATING COIL Coil:Heating:Gas   2166.89 0.80
SPLIT TSE HEATING COIL Coil:Heating:Gas   2143.56 0.80
SPLIT TNE HEATING COIL Coil:Heating:Gas   2157.86 0.80
SPLIT TN1 HEATING COIL Coil:Heating:Gas   1593.88 0.80
SPLIT TN2 HEATING COIL Coil:Heating:Gas   1593.62 0.80
SPLIT TS1 HEATING COIL Coil:Heating:Gas   1577.52 0.80
SPLIT TS2 HEATING COIL Coil:Heating:Gas   1577.26 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
SPLIT GSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.29 341.90 1160.84 1.00 General
SPLIT GNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.30 346.74 1160.84 1.00 General
SPLIT OFFICE SUPPLY FAN Fan:OnOff 0.54 622.50 0.59 683.45 1160.84 1.00 General
SPLIT GNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.25 288.53 1160.84 1.00 General
SPLIT GN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 207.30 1160.84 1.00 General
SPLIT GN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.18 206.38 1160.84 1.00 General
SPLIT GS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 198.68 1160.84 1.00 General
SPLIT GS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.17 200.38 1160.84 1.00 General
SPLIT MSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.70 817.35 1160.84 1.00 General
SPLIT MNW SUPPLY FAN Fan:OnOff 0.55 622.50 0.72 815.44 1140.11 1.00 General
SPLIT MSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.61 712.94 1160.84 1.00 General
SPLIT MNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.61 711.44 1160.84 1.00 General
SPLIT MN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 507.78 1160.84 1.00 General
SPLIT MN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.44 506.33 1160.84 1.00 General
SPLIT MS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 487.70 1160.84 1.00 General
SPLIT MS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 487.08 1160.84 1.00 General
SPLIT TSW SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 551.44 1160.84 1.00 General
SPLIT TNW SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 553.83 1160.84 1.00 General
SPLIT TSE SUPPLY FAN Fan:OnOff 0.54 622.50 0.43 493.58 1160.84 1.00 General
SPLIT TNE SUPPLY FAN Fan:OnOff 0.54 622.50 0.42 488.67 1160.84 1.00 General
SPLIT TN1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 370.28 1160.84 1.00 General
SPLIT TN2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 369.49 1160.84 1.00 General
SPLIT TS1 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 373.49 1160.84 1.00 General
SPLIT TS2 SUPPLY FAN Fan:OnOff 0.54 622.50 0.32 373.31 1160.84 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
None              


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
G SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
G S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
M S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NW APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T SE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T NE APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T N2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S1 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90
T S2 APARTMENT WATER HEATER WaterHeater:Mixed 0.19 14653.55 1.00 3.78 0.90



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 2914.05 3496.86 0.245 0.295 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 43.59 0.00412
G NW APARTMENT 2955.28 3546.34 0.249 0.299 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 42.85 0.00412
OFFICE 5688.65 6826.37 0.491 0.589 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 36.78 0.00412
G NE APARTMENT 2459.11 2950.94 0.207 0.249 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 42.85 0.00412
G N1 APARTMENT 1766.77 2120.13 0.149 0.179 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 41.64 0.00412
G N2 APARTMENT 1758.94 2110.72 0.148 0.178 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 41.64 0.00412
G S1 APARTMENT 1693.28 2031.94 0.143 0.171 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 43.80 0.00412
G S2 APARTMENT 1707.82 2049.38 0.144 0.173 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
M SW APARTMENT 6966.50 8359.81 0.587 0.704 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 43.59 0.00412
M NW APARTMENT 7076.56 8491.87 0.596 0.715 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 42.85 0.00412
M SE APARTMENT 6076.57 7291.88 0.512 0.614 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
M NE APARTMENT 6063.78 7276.54 0.511 0.613 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 43.12 0.00412
M N1 APARTMENT 4327.76 5193.32 0.365 0.437 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 41.97 0.00412
M N2 APARTMENT 4315.40 5178.48 0.363 0.436 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 41.97 0.00412
M S1 APARTMENT 4156.66 4988.00 0.350 0.420 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 43.80 0.00412
M S2 APARTMENT 4151.36 4981.64 0.350 0.420 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 44.00 0.00412
T SW APARTMENT 4700.20 5640.24 0.396 0.475 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 43.80 0.00412
T NW APARTMENT 4720.60 5664.72 0.398 0.477 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 43.59 0.00412
T SE APARTMENT 4207.02 5048.42 0.354 0.425 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 44.20 0.00412
T NE APARTMENT 4165.18 4998.22 0.351 0.421 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
T N1 APARTMENT 3155.98 3787.17 0.266 0.319 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 44.00 0.00412
T N2 APARTMENT 3149.22 3779.07 0.265 0.318 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 44.00 0.00412
T S1 APARTMENT 3183.32 3819.98 0.268 0.322 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
T S2 APARTMENT 3181.77 3818.12 0.268 0.322 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
G SW APARTMENT 821.21 985.45 0.025 0.031 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
G NW APARTMENT 827.20 992.64 0.026 0.031 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
OFFICE 1853.11 2223.73 0.055 0.066 RIYADH ANN HTG 99.6% CONDNS DB 1/21 09:00:00 5.90 0.00619
G NE APARTMENT 821.96 986.35 0.025 0.031 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
G N1 APARTMENT 436.83 524.19 0.014 0.026 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
G N2 APARTMENT 436.70 524.04 0.014 0.026 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
G S1 APARTMENT 431.61 517.94 0.013 0.026 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
G S2 APARTMENT 494.76 593.71 0.015 0.026 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M SW APARTMENT 1696.85 2036.22 0.053 0.063 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M NW APARTMENT 1719.47 2063.37 0.053 0.064 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M SE APARTMENT 1682.24 2018.68 0.052 0.062 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M NE APARTMENT 1704.92 2045.90 0.053 0.063 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M N1 APARTMENT 745.70 894.83 0.023 0.052 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M N2 APARTMENT 745.31 894.37 0.023 0.052 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M S1 APARTMENT 722.32 866.79 0.022 0.052 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
M S2 APARTMENT 721.93 866.32 0.022 0.052 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T SW APARTMENT 1430.27 1716.33 0.044 0.053 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T NW APARTMENT 1442.36 1730.83 0.045 0.054 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T SE APARTMENT 1422.63 1707.16 0.044 0.053 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T NE APARTMENT 1434.73 1721.67 0.044 0.053 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T N1 APARTMENT 957.79 1149.35 0.030 0.036 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T N2 APARTMENT 957.57 1149.08 0.030 0.036 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T S1 APARTMENT 943.95 1132.74 0.029 0.035 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619
T S2 APARTMENT 943.73 1132.48 0.029 0.035 RIYADH ANN HTG 99.6% CONDNS DB 1/21 04:00:00 5.90 0.00619


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SPLIT GSW 0.29 0.29 0.03 0.03
SPLIT GNW 0.30 0.30 0.03 0.03
SPLIT OFFICE 0.59 0.59 0.07 0.07
SPLIT GNE 0.25 0.25 0.03 0.03
SPLIT GN1 0.18 0.18 0.03 0.03
SPLIT GN2 0.18 0.18 0.03 0.03
SPLIT GS1 0.17 0.17 0.03 0.03
SPLIT GS2 0.17 0.17 0.03 0.03
SPLIT MSW 0.70 0.70 0.06 0.06
SPLIT MNW 0.72 0.72 0.06 0.06
SPLIT MSE 0.61 0.61 0.06 0.06
SPLIT MNE 0.61 0.61 0.06 0.06
SPLIT MN1 0.44 0.44 0.05 0.05
SPLIT MN2 0.44 0.44 0.05 0.05
SPLIT MS1 0.42 0.42 0.05 0.05
SPLIT MS2 0.42 0.42 0.05 0.05
SPLIT TSW 0.48 0.48 0.05 0.05
SPLIT TNW 0.48 0.48 0.05 0.05
SPLIT TSE 0.43 0.43 0.05 0.05
SPLIT TNE 0.42 0.42 0.05 0.05
SPLIT TN1 0.32 0.32 0.04 0.04
SPLIT TN2 0.32 0.32 0.04 0.04
SPLIT TS1 0.32 0.32 0.04 0.04
SPLIT TS2 0.32 0.32 0.04 0.04



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
G SW APARTMENT 1679.50 3450.00 37.75
G NW APARTMENT 1393.25 4237.50 52.50
OFFICE 682.75 660.50 0.00
G NE APARTMENT 1406.50 4269.25 55.25
G N1 APARTMENT 588.00 4867.75 60.75
G N2 APARTMENT 586.50 4865.00 61.00
G S1 APARTMENT 856.00 3982.75 50.00
G S2 APARTMENT 959.75 3791.25 47.75
M SW APARTMENT 2777.50 1028.00 2.00
M NW APARTMENT 2145.25 2060.25 9.50
M SE APARTMENT 2792.50 1062.75 5.00
M NE APARTMENT 2136.50 2085.50 12.75
M N1 APARTMENT 1162.75 1946.00 10.75
M N2 APARTMENT 1162.50 1953.25 11.75
M S1 APARTMENT 1807.00 591.25 2.75
M S2 APARTMENT 1805.00 596.75 2.75
T SW APARTMENT 3933.25 2016.00 9.75
T NW APARTMENT 3409.00 2592.75 42.50
T SE APARTMENT 3996.50 1997.50 12.25
T NE APARTMENT 3442.75 2606.50 45.00
T N1 APARTMENT 2745.75 2609.00 15.75
T N2 APARTMENT 2747.50 2611.50 15.75
T S1 APARTMENT 3423.50 1862.25 10.00
T S2 APARTMENT 3424.25 1862.00 10.00
T CORRIDOR 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00
Facility 4466.25 4888.50 99.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
G SW APARTMENT 0.00 8.75 0.00 8.75
G NW APARTMENT 0.00 14.00 0.00 14.00
OFFICE 0.00 36.00 0.00 0.00
G NE APARTMENT 0.00 16.00 0.00 16.00
G N1 APARTMENT 0.75 30.00 0.75 30.00
G N2 APARTMENT 1.00 30.25 1.00 30.25
G S1 APARTMENT 0.00 28.00 0.00 28.00
G S2 APARTMENT 0.00 30.50 0.00 30.50
M SW APARTMENT 0.00 8.75 0.00 8.75
M NW APARTMENT 0.00 7.50 0.00 7.50
M SE APARTMENT 0.00 10.75 0.00 10.75
M NE APARTMENT 0.00 14.25 0.00 14.25
M N1 APARTMENT 0.00 22.00 0.00 22.00
M N2 APARTMENT 0.00 22.25 0.00 22.25
M S1 APARTMENT 0.00 23.75 0.00 23.75
M S2 APARTMENT 0.00 21.25 0.00 21.25
T SW APARTMENT 0.00 8.75 0.00 8.75
T NW APARTMENT 0.00 11.75 0.00 11.75
T SE APARTMENT 0.00 8.75 0.00 8.75
T NE APARTMENT 0.00 6.25 0.00 6.25
T N1 APARTMENT 0.00 1.25 0.00 1.25
T N2 APARTMENT 0.00 1.25 0.00 1.25
T S1 APARTMENT 0.00 2.00 0.00 2.00
T S2 APARTMENT 0.00 1.75 0.00 1.75
T CORRIDOR 0.00 0.00 0.00 0.00
G CORRIDOR 0.00 0.00 0.00 0.00
M CORRIDOR 0.00 0.00 0.00 0.00
Facility 1.50 121.25 1.50 85.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.369 0.129 0.000 0.065
G NW APARTMENT 1.71 2.50 268.97 0.356 0.129 0.000 0.062
OFFICE 0.94 1.00 268.97 0.522 0.155 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.355 0.129 0.000 0.062
G N1 APARTMENT 1.71 2.50 268.97 0.355 0.078 0.000 0.061
G N2 APARTMENT 1.71 2.50 268.97 0.355 0.078 0.000 0.061
G S1 APARTMENT 1.71 2.50 268.97 0.356 0.078 0.000 0.065
G S2 APARTMENT 1.71 2.50 268.97 0.356 0.078 0.000 0.065
M SW APARTMENT 1.71 2.50 268.97 0.356 0.186 0.000 0.076
M NW APARTMENT 1.71 2.50 268.97 0.356 0.186 0.000 0.074
M SE APARTMENT 1.71 2.50 268.97 0.356 0.186 0.000 0.076
M NE APARTMENT 1.71 2.50 268.97 0.356 0.186 0.000 0.074
M N1 APARTMENT 1.71 2.50 268.97 0.356 0.112 0.000 0.074
M N2 APARTMENT 1.71 2.50 268.97 0.356 0.112 0.000 0.074
M S1 APARTMENT 1.71 2.50 268.97 0.356 0.112 0.000 0.076
M S2 APARTMENT 1.71 2.50 268.97 0.356 0.112 0.000 0.076
T SW APARTMENT 1.71 2.50 268.97 0.356 0.246 0.000 0.088
T NW APARTMENT 1.71 2.50 268.97 0.356 0.246 0.000 0.085
T SE APARTMENT 1.71 2.50 268.97 0.356 0.246 0.000 0.088
T NE APARTMENT 1.71 2.50 268.97 0.356 0.246 0.000 0.085
T N1 APARTMENT 1.71 2.50 268.97 0.356 0.148 0.000 0.085
T N2 APARTMENT 1.71 2.50 268.97 0.356 0.148 0.000 0.085
T S1 APARTMENT 1.71 2.50 268.97 0.356 0.148 0.000 0.088
T S2 APARTMENT 1.71 2.50 268.97 0.356 0.148 0.000 0.088
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
G SW APARTMENT 1.71 2.50 268.97 0.357 0.000 0.000 0.000
G NW APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
OFFICE 0.94 1.00 268.97 0.507 0.000 0.000 0.000
G NE APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
G N1 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
G N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
G S1 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
G S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
M SW APARTMENT 1.71 2.50 268.97 1.383 0.000 0.000 0.000
M NW APARTMENT 1.71 2.50 268.97 1.379 0.000 0.000 0.000
M SE APARTMENT 1.71 2.50 268.97 1.382 0.000 0.000 0.000
M NE APARTMENT 1.71 2.50 268.97 1.379 0.000 0.000 0.000
M N1 APARTMENT 1.71 2.50 268.97 1.380 0.000 0.000 0.000
M N2 APARTMENT 1.71 2.50 268.97 1.380 0.000 0.000 0.000
M S1 APARTMENT 1.71 2.50 268.97 1.386 0.000 0.000 0.000
M S2 APARTMENT 1.71 2.50 268.97 1.386 0.000 0.000 0.000
T SW APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T NW APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T SE APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T NE APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T N1 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T N2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T S1 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
T S2 APARTMENT 1.71 2.50 268.97 0.344 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Surfaces by Class

Total Outdoors
Wall 126 42
Floor 27 9
Roof 27 9
Internal Mass 24 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 39 39
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 24
Conditioned Zones 24
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1385
Defaulted Fields 439
Fields with Defaults 3704
Autosized Fields 336
Autosizable Fields 454
Autocalculated Fields 247
Autocalculatable Fields 424



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
Electricity:Building 636.11 10559.61 01-JAN-03:15 31610.87 01-JAN-18:15
Electricity:Zone:G SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity 118.46 2466.75 01-JAN-00:15 5482.59 01-JAN-19:15
InteriorLights:Electricity:Zone:G SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
GeneralLights:InteriorLights:Electricity 96.36 2205.67 01-JAN-00:15 4426.44 01-JAN-19:15
Electricity:Zone:G NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:OFFICE 35.93 610.39 01-JAN-00:15 2669.36 02-JAN-08:15
InteriorLights:Electricity:Zone:OFFICE 26.45 416.15 01-JAN-00:15 2080.74 02-JAN-08:15
Electricity:Zone:G NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:G S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:M SW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NW APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NW APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M SE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M SE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M NE APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M NE APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M N2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M N2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S1 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S1 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:M S2 APARTMENT 26.60 460.32 01-JAN-03:15 1352.36 01-JAN-18:15
InteriorLights:Electricity:Zone:M S2 APARTMENT 2.17 12.97 01-JAN-00:15 207.54 01-JAN-19:15
Electricity:Zone:T SW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NW APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NW APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T SE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T SE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T NE APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T NE APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T N2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T N2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S1 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S1 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:T S2 APARTMENT 13.30 230.16 01-JAN-03:15 676.18 01-JAN-18:15
InteriorLights:Electricity:Zone:T S2 APARTMENT 1.09 6.49 01-JAN-00:15 103.77 01-JAN-19:15
Electricity:Zone:G CORRIDOR 144.16 1427.03 01-JAN-00:15 8651.76 01-JAN-07:15
InteriorLights:Electricity:Zone:G CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
InteriorLights:Electricity:Zone:M CORRIDOR 29.16 924.77 01-JAN-00:15 924.77 01-JAN-00:15
Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
InteriorLights:Electricity:Zone:T CORRIDOR 14.58 462.39 01-JAN-00:15 462.39 01-JAN-00:15
GeneralLights-plugin:InteriorLights:Electricity 22.11 261.08 01-JAN-00:15 1411.40 02-JAN-16:15
InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
MiscPlug:InteriorEquipment:Electricity 517.65 8092.87 01-JAN-03:15 26730.99 02-JAN-17:15
InteriorEquipment:Electricity:Zone:G NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:OFFICE 9.48 194.25 01-JAN-00:15 588.62 02-JAN-08:15
InteriorEquipment:Electricity:Zone:G NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NW APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M SE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M NE APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M N2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S1 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:M S2 APARTMENT 24.43 447.35 01-JAN-03:15 1177.25 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NW APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T SE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T NE APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T N2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S1 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:T S2 APARTMENT 12.21 223.68 01-JAN-03:15 588.62 01-JAN-17:15
InteriorEquipment:Electricity:Zone:G CORRIDOR 129.57 964.65 01-JAN-00:15 8189.37 01-JAN-07:15
Electricity:Plant 281.43 0.00 01-JAN-00:15 30504.07 01-JAN-08:15
WaterSystems:Electricity 281.43 0.00 01-JAN-00:15 30504.07 01-JAN-08:15
Water Heater:WaterSystems:Electricity 281.43 0.00 01-JAN-00:15 30504.07 01-JAN-08:15
Fans:Electricity 349.85 11093.54 01-JAN-00:15 11093.54 01-JAN-08:15
Fans:Electricity:Zone:G SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:G S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NW APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T SE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T NE APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T N2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S1 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:T S2 APARTMENT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
ElectricityPurchased:Plant 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
Cogeneration:ElectricityPurchased 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
ElectricityNet:Plant 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
Cogeneration:ElectricityNet 1719.58 24206.16 01-JAN-03:15 97570.67 30-JUL-17:15
ExteriorLights:Electricity 40.15 0.00 01-JAN-06:45 2553.00 01-JAN-00:15
General:ExteriorLights:Electricity 40.15 0.00 01-JAN-06:45 2553.00 01-JAN-00:15
Electricity:HVAC 761.89 11093.54 01-JAN-00:15 51754.45 30-JUL-14:15
General:Fans:Electricity 349.85 11093.54 01-JAN-00:15 11093.54 01-JAN-08:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 412.04 0.00 01-JAN-00:15 40660.91 30-JUL-14:15


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum Gas Maximum Value [W] Timestamp of Maximum
Gas:Facility 5.19 0.00 01-JAN-10:45 22560.99 09-JAN-05:00
Gas:HVAC 5.19 0.00 01-JAN-10:45 22560.99 09-JAN-05:00
Heating:Gas 5.19 0.00 01-JAN-10:45 22560.99 09-JAN-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum Cooling Maximum Value [W] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
Water:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:Water 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Facility 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
MainsWater:Plant 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15
Water Heater:WaterSystems:MainsWater 1874.72 0.00 01-JAN-02:15 0.00 01-JAN-07:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum Maximum Value [kg/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum Maximum Value [m3/s] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum Maximum Value [L] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum Maximum Value [W] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 2550.85 2441.96 25-DEC-15:00 237960.55 29-JUN-19:00
EnergyTransfer:Building 1087.62 2062.69 24-MAR-06:00 106971.38 29-JUN-19:00
EnergyTransfer:Zone:G SW APARTMENT 27.56 0.02 19-MAR-04:45 3375.63 29-JUN-19:00
Heating:EnergyTransfer 24.10 0.00 20-FEB-13:15 17323.49 09-JAN-05:00
Heating:EnergyTransfer:Zone:G SW APARTMENT 0.74 0.00 01-JAN-00:15 843.72 09-JAN-05:00
Cooling:EnergyTransfer 1063.52 0.00 13-JAN-10:00 106971.38 29-JUN-19:00
Cooling:EnergyTransfer:Zone:G SW APARTMENT 26.82 0.00 01-JAN-03:15 3375.63 29-JUN-19:00
EnergyTransfer:Zone:G NW APARTMENT 24.19 0.05 26-JAN-14:15 3462.57 29-JUN-19:00
Heating:EnergyTransfer:Zone:G NW APARTMENT 1.61 0.00 17-JAN-04:15 894.68 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G NW APARTMENT 22.57 0.00 01-JAN-00:15 3462.57 29-JUN-19:00
EnergyTransfer:Zone:OFFICE 42.47 0.01 12-NOV-15:00 5788.59 24-AUG-13:15
Heating:EnergyTransfer:Zone:OFFICE 7.53 0.00 01-JAN-02:30 1021.22 18-MAY-17:30
Cooling:EnergyTransfer:Zone:OFFICE 34.93 0.00 01-JAN-00:15 5788.59 24-AUG-13:15
EnergyTransfer:Zone:G NE APARTMENT 23.56 0.07 08-DEC-24:00 2971.60 13-JUN-20:00
Heating:EnergyTransfer:Zone:G NE APARTMENT 1.23 0.00 01-JAN-07:30 904.69 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G NE APARTMENT 22.33 0.00 01-JAN-00:15 2971.60 13-JUN-20:00
EnergyTransfer:Zone:G N1 APARTMENT 15.78 0.02 27-DEC-04:00 2055.08 13-JUN-20:00
Heating:EnergyTransfer:Zone:G N1 APARTMENT 0.54 0.00 01-JAN-09:00 426.41 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G N1 APARTMENT 15.24 0.00 01-JAN-00:15 2055.08 13-JUN-20:00
EnergyTransfer:Zone:G N2 APARTMENT 15.78 0.02 26-FEB-11:30 2046.22 13-JUN-20:00
Heating:EnergyTransfer:Zone:G N2 APARTMENT 0.54 0.00 01-JAN-00:30 428.00 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G N2 APARTMENT 15.24 0.00 01-JAN-00:15 2046.22 13-JUN-20:00
EnergyTransfer:Zone:G S1 APARTMENT 19.68 0.04 05-JAN-20:00 2077.64 13-JUN-20:00
Heating:EnergyTransfer:Zone:G S1 APARTMENT 0.11 0.00 01-JAN-00:15 365.15 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G S1 APARTMENT 19.57 0.00 04-JAN-15:45 2077.64 13-JUN-20:00
EnergyTransfer:Zone:G S2 APARTMENT 20.84 0.00 16-MAR-14:45 2152.43 22-SEP-13:00
Heating:EnergyTransfer:Zone:G S2 APARTMENT 0.10 0.00 01-JAN-00:15 363.09 09-JAN-05:00
Cooling:EnergyTransfer:Zone:G S2 APARTMENT 20.74 0.00 04-JAN-15:45 2152.43 22-SEP-13:00
EnergyTransfer:Zone:M SW APARTMENT 87.54 0.01 05-MAR-07:00 8434.45 13-JUN-19:15
Heating:EnergyTransfer:Zone:M SW APARTMENT 0.22 0.00 01-JAN-00:30 663.94 09-JAN-05:00
Cooling:EnergyTransfer:Zone:M SW APARTMENT 87.33 0.00 01-JAN-00:15 8434.45 13-JUN-19:15
EnergyTransfer:Zone:M NW APARTMENT 72.93 0.02 21-JAN-00:45 8505.18 13-JUN-19:45
Heating:EnergyTransfer:Zone:M NW APARTMENT 0.95 0.00 01-JAN-00:45 965.42 09-JAN-05:00
Cooling:EnergyTransfer:Zone:M NW APARTMENT 71.98 0.00 01-JAN-00:15 8505.18 13-JUN-19:45
EnergyTransfer:Zone:M SE APARTMENT 87.16 0.01 23-DEC-05:45 7652.83 13-JUN-20:00
Heating:EnergyTransfer:Zone:M SE APARTMENT 0.13 0.00 01-JAN-00:15 744.65 09-JAN-05:00
Cooling:EnergyTransfer:Zone:M SE APARTMENT 87.03 0.00 04-JAN-23:30 7652.83 13-JUN-20:00
EnergyTransfer:Zone:M NE APARTMENT 72.26 0.02 27-DEC-23:00 7453.11 13-JUN-20:00
Heating:EnergyTransfer:Zone:M NE APARTMENT 0.66 0.00 01-JAN-00:30 1033.60 09-JAN-05:00
Cooling:EnergyTransfer:Zone:M NE APARTMENT 71.60 0.00 01-JAN-00:15 7453.11 13-JUN-20:00
EnergyTransfer:Zone:M N1 APARTMENT 54.25 0.05 14-FEB-18:00 5151.60 13-JUN-20:00
Heating:EnergyTransfer:Zone:M N1 APARTMENT 0.11 0.00 01-JAN-00:15 260.33 12-JAN-16:00
Cooling:EnergyTransfer:Zone:M N1 APARTMENT 54.14 0.00 01-JAN-14:30 5151.60 13-JUN-20:00
EnergyTransfer:Zone:M N2 APARTMENT 54.24 0.13 28-DEC-16:00 5137.93 13-JUN-20:00
Heating:EnergyTransfer:Zone:M N2 APARTMENT 0.11 0.00 01-JAN-00:15 260.25 12-JAN-16:00
Cooling:EnergyTransfer:Zone:M N2 APARTMENT 54.14 0.00 01-JAN-14:30 5137.93 13-JUN-20:00
EnergyTransfer:Zone:M S1 APARTMENT 70.60 0.43 16-MAR-14:15 5348.93 09-OCT-12:45
Heating:EnergyTransfer:Zone:M S1 APARTMENT 0.00 0.00 01-JAN-00:15 160.54 10-APR-05:15
Cooling:EnergyTransfer:Zone:M S1 APARTMENT 70.59 0.00 12-JAN-10:45 5348.93 09-OCT-12:45
EnergyTransfer:Zone:M S2 APARTMENT 70.59 0.48 16-MAR-14:15 5371.14 09-OCT-12:45
Heating:EnergyTransfer:Zone:M S2 APARTMENT 0.00 0.00 01-JAN-00:15 159.40 10-APR-05:15
Cooling:EnergyTransfer:Zone:M S2 APARTMENT 70.59 0.00 12-JAN-10:45 5371.14 09-OCT-12:45
EnergyTransfer:Zone:T SW APARTMENT 49.54 0.09 25-NOV-23:30 5666.79 29-JUN-19:00
Heating:EnergyTransfer:Zone:T SW APARTMENT 1.49 0.00 01-JAN-09:00 1508.49 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T SW APARTMENT 48.05 0.00 01-JAN-00:15 5666.79 29-JUN-19:00
EnergyTransfer:Zone:T NW APARTMENT 43.63 0.09 22-MAR-22:30 5696.64 29-JUN-19:00
Heating:EnergyTransfer:Zone:T NW APARTMENT 2.35 0.00 01-JAN-14:45 1538.11 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T NW APARTMENT 41.28 0.00 01-JAN-00:15 5696.64 29-JUN-19:00
EnergyTransfer:Zone:T SE APARTMENT 49.04 0.02 14-APR-04:30 5156.80 29-JUN-19:00
Heating:EnergyTransfer:Zone:T SE APARTMENT 1.29 0.00 01-JAN-07:30 1516.90 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T SE APARTMENT 47.75 0.00 01-JAN-00:15 5156.80 29-JUN-19:00
EnergyTransfer:Zone:T NE APARTMENT 42.90 0.20 22-JAN-17:00 5137.57 29-JUN-19:00
Heating:EnergyTransfer:Zone:T NE APARTMENT 2.03 0.00 01-JAN-09:00 1545.56 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T NE APARTMENT 40.87 0.00 01-JAN-00:15 5137.57 29-JUN-19:00
EnergyTransfer:Zone:T N1 APARTMENT 32.44 0.03 28-JAN-06:45 3834.86 29-JUN-19:00
Heating:EnergyTransfer:Zone:T N1 APARTMENT 0.85 0.00 01-JAN-00:45 872.63 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T N1 APARTMENT 31.59 0.00 01-JAN-00:15 3834.86 29-JUN-19:00
EnergyTransfer:Zone:T N2 APARTMENT 32.44 0.01 19-FEB-07:00 3826.00 29-JUN-19:00
Heating:EnergyTransfer:Zone:T N2 APARTMENT 0.85 0.00 01-JAN-00:45 874.19 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T N2 APARTMENT 31.59 0.00 01-JAN-00:15 3826.00 29-JUN-19:00
EnergyTransfer:Zone:T S1 APARTMENT 39.10 0.00 05-JAN-04:00 3849.01 29-JUN-19:00
Heating:EnergyTransfer:Zone:T S1 APARTMENT 0.33 0.00 01-JAN-00:30 827.27 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T S1 APARTMENT 38.77 0.00 01-JAN-00:15 3849.01 29-JUN-19:00
EnergyTransfer:Zone:T S2 APARTMENT 39.11 0.00 05-JAN-04:45 3839.43 29-JUN-19:00
Heating:EnergyTransfer:Zone:T S2 APARTMENT 0.33 0.00 01-JAN-00:30 828.97 09-JAN-05:00
Cooling:EnergyTransfer:Zone:T S2 APARTMENT 38.78 0.00 01-JAN-00:15 3839.43 29-JUN-19:00
EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:T CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:G CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:M CORRIDOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:HVAC 1463.23 0.00 09-JAN-17:15 130989.17 29-JUN-19:00
HeatingCoils:EnergyTransfer 4.15 0.00 01-JAN-10:45 18048.80 09-JAN-05:00
CoolingCoils:EnergyTransfer 1459.07 0.00 01-JAN-00:15 130989.17 29-JUN-19:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [GJ] HVAC Input Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
G SW APARTMENT 0.736 -26.824 0.000 0.000 3.594 1.087 12.213 21.752 0.000 2.088 0.000 0.000 -3.751 0.000 -1.557 -9.337
G NW APARTMENT 1.612 -22.575 0.000 0.000 3.622 1.087 12.213 15.306 0.000 2.086 0.000 0.000 -3.764 0.000 -1.399 -8.188
OFFICE 7.535 -34.933 0.000 0.000 0.517 26.452 9.482 20.078 0.000 1.509 0.001 0.000 -4.376 0.000 -1.033 -25.230
G NE APARTMENT 1.228 -22.329 0.000 0.000 3.633 1.087 12.213 14.907 0.000 2.086 0.000 0.000 -3.509 0.000 -1.372 -7.944
G N1 APARTMENT 0.542 -15.241 0.000 0.000 3.635 1.087 12.213 6.938 0.000 1.270 0.000 0.000 -2.258 0.000 -1.015 -7.170
G N2 APARTMENT 0.539 -15.240 0.000 0.000 3.636 1.087 12.213 6.938 0.000 1.270 0.000 0.000 -2.256 0.000 -1.014 -7.171
G S1 APARTMENT 0.115 -19.568 0.000 0.000 3.595 1.087 12.213 13.460 0.000 1.271 0.000 0.000 -2.249 0.000 -1.208 -8.714
G S2 APARTMENT 0.103 -20.736 0.000 0.000 3.592 1.087 12.213 13.427 0.000 1.271 0.000 0.000 -2.264 0.000 -1.214 -7.478
M SW APARTMENT 0.216 -87.325 0.000 0.000 3.530 1.087 12.213 21.144 0.000 2.987 52.680 0.000 -4.381 0.000 -2.150 0.000
M NW APARTMENT 0.947 -71.984 0.000 0.000 3.551 1.087 12.213 14.777 0.000 2.985 42.971 0.000 -4.473 0.000 -2.073 -0.001
M SE APARTMENT 0.128 -87.028 0.000 0.000 3.533 1.087 12.213 20.863 0.000 2.987 52.623 0.000 -4.260 0.000 -2.145 0.000
M NE APARTMENT 0.659 -71.597 0.000 0.000 3.557 1.087 12.213 14.337 0.000 2.984 42.999 0.000 -4.182 0.000 -2.057 -0.000
M N1 APARTMENT 0.107 -54.142 0.000 0.000 3.544 1.087 12.213 6.589 0.000 1.813 33.148 0.000 -2.787 0.000 -1.571 -0.000
M N2 APARTMENT 0.107 -54.137 0.000 0.000 3.544 1.087 12.213 6.589 0.000 1.813 33.141 0.000 -2.785 0.000 -1.571 -0.000
M S1 APARTMENT 0.001 -70.594 0.000 0.000 3.523 1.087 12.213 13.057 0.000 1.816 43.176 0.000 -2.643 0.000 -1.636 0.000
M S2 APARTMENT 0.001 -70.587 0.000 0.000 3.523 1.087 12.213 13.057 0.000 1.816 43.167 0.000 -2.642 0.000 -1.636 0.000
T SW APARTMENT 1.491 -48.048 0.000 0.000 3.565 1.087 12.213 20.616 0.000 3.931 11.833 0.000 -4.075 0.000 -2.612 -0.000
T NW APARTMENT 2.352 -41.282 0.000 0.000 3.582 1.087 12.213 14.337 0.000 3.928 10.434 0.000 -4.149 0.000 -2.502 -0.000
T SE APARTMENT 1.291 -47.746 0.000 0.000 3.570 1.087 12.213 20.349 0.000 3.931 11.870 0.000 -3.960 0.000 -2.604 -0.000
T NE APARTMENT 2.027 -40.871 0.000 0.000 3.589 1.087 12.213 13.946 0.000 3.928 10.478 0.000 -3.905 0.000 -2.492 -0.001
T N1 APARTMENT 0.849 -31.587 0.000 0.000 3.580 1.087 12.213 6.416 0.000 2.385 9.470 0.000 -2.560 0.000 -1.852 -0.001
T N2 APARTMENT 0.850 -31.591 0.000 0.000 3.580 1.087 12.213 6.415 0.000 2.385 9.471 0.000 -2.558 0.000 -1.853 -0.001
T S1 APARTMENT 0.329 -38.770 0.000 0.000 3.557 1.087 12.213 12.767 0.000 2.389 10.870 0.000 -2.482 0.000 -1.959 -0.000
T S2 APARTMENT 0.332 -38.777 0.000 0.000 3.557 1.087 12.213 12.766 0.000 2.389 10.873 0.000 -2.480 0.000 -1.959 -0.000
T CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.731 0.000 0.443 0.000 0.000 -0.400 0.000 -0.345 -15.011
G CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 6.479 2.266 0.000 8.962 0.000 0.000 -0.932 0.000 -6.497 -24.860
M CORRIDOR 0.000 0.000 0.000 0.000 0.000 14.582 0.000 0.761 0.000 0.362 0.000 0.000 -0.458 0.000 -0.294 -14.953
Total Facility 24.098 -1063.510 0.000 0.000 82.710 95.189 296.854 334.589 0.000 67.082 429.205 0.000 -80.539 0.000 -49.619 -136.060


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 29-JUN-19:00 0.00 -3375.31 0.00 0.00 141.81 103.77 547.42 584.10 0.00 1592.97 405.25 0.00 0.00 0.00 0.00 0.00
G NW APARTMENT 29-JUN-18:53 0.00 -3462.61 0.00 0.00 141.81 103.77 547.42 636.48 0.00 1591.66 441.47 0.00 0.00 0.00 0.00 0.00
OFFICE 25-SEP-06:01 0.00 -8694.24 0.00 0.00 0.00 416.15 294.31 271.57 0.00 0.00 7712.22 0.00 0.00 0.00 0.00 0.00
G NE APARTMENT 13-JUN-20:00 0.00 -2971.53 0.00 0.00 140.63 103.77 523.87 439.33 0.00 1530.73 233.19 0.00 0.00 0.00 0.00 0.00
G N1 APARTMENT 13-JUN-20:00 0.00 -2055.03 0.00 0.00 140.69 103.77 523.87 256.02 0.00 923.65 107.03 0.00 0.00 0.00 0.00 0.00
G N2 APARTMENT 13-JUN-20:00 0.00 -2046.17 0.00 0.00 140.59 103.77 523.87 255.91 0.00 922.71 99.32 0.00 0.00 0.00 0.00 0.00
G S1 APARTMENT 13-JUN-20:00 0.00 -2077.59 0.00 0.00 141.55 103.77 523.87 306.20 0.00 929.46 72.74 0.00 0.00 0.00 0.00 0.00
G S2 APARTMENT 22-SEP-13:00 0.00 -2152.19 0.00 0.00 40.75 12.97 388.49 1736.43 0.00 120.06 0.00 0.00 0.00 0.00 0.00 -146.51
M SW APARTMENT 13-JUN-19:15 0.00 -8434.59 0.00 0.00 141.56 103.77 523.87 518.46 0.00 2130.03 5016.90 0.00 0.00 0.00 0.00 0.00
M NW APARTMENT 13-JUN-19:45 0.00 -8505.06 0.00 0.00 141.50 103.77 523.87 427.03 0.00 2188.44 5120.44 0.00 0.00 0.00 0.00 0.00
M SE APARTMENT 13-JUN-20:00 0.00 -7652.68 0.00 0.00 138.31 103.77 523.87 499.72 0.00 2149.39 4237.62 0.00 0.00 0.00 0.00 0.00
M NE APARTMENT 13-JUN-20:00 0.00 -7452.96 0.00 0.00 136.76 103.77 523.87 437.89 0.00 2121.02 4129.64 0.00 0.00 0.00 0.00 0.00
M N1 APARTMENT 13-JUN-20:00 0.00 -5151.49 0.00 0.00 137.80 103.77 523.87 252.73 0.00 1290.87 2842.44 0.00 0.00 0.00 0.00 0.00
M N2 APARTMENT 13-JUN-20:00 0.00 -5137.81 0.00 0.00 137.71 103.77 523.87 252.57 0.00 1289.72 2830.16 0.00 0.00 0.00 0.00 0.00
M S1 APARTMENT 09-OCT-12:45 0.00 -5348.87 0.00 0.00 40.75 12.97 388.49 2028.46 0.00 203.34 2674.86 0.00 0.00 0.00 0.00 0.00
M S2 APARTMENT 09-OCT-12:45 0.00 -5371.08 0.00 0.00 40.75 12.97 388.49 2028.37 0.00 203.42 2697.08 0.00 0.00 0.00 0.00 0.00
T SW APARTMENT 29-JUN-18:53 0.00 -5667.88 0.00 0.00 141.80 103.77 547.42 584.12 0.00 3015.31 1275.45 0.00 0.00 0.00 0.00 0.00
T NW APARTMENT 29-JUN-19:00 0.00 -5696.31 0.00 0.00 141.81 103.77 547.42 642.36 0.00 2994.19 1266.77 0.00 0.00 0.00 0.00 0.00
T SE APARTMENT 29-JUN-19:00 0.00 -5160.42 0.00 0.00 141.81 103.77 547.42 549.64 0.00 2961.84 855.95 0.00 0.00 0.00 0.00 0.00
T NE APARTMENT 29-JUN-19:00 0.00 -5145.36 0.00 0.00 141.41 103.77 547.42 608.17 0.00 2931.27 813.32 0.00 0.00 0.00 0.00 0.00
T N1 APARTMENT 29-JUN-19:00 0.00 -3836.81 0.00 0.00 141.81 103.77 547.42 405.87 0.00 1800.58 837.36 0.00 0.00 0.00 0.00 0.00
T N2 APARTMENT 29-JUN-19:00 0.00 -3827.94 0.00 0.00 141.81 103.77 547.42 406.16 0.00 1800.64 828.15 0.00 0.00 0.00 0.00 0.00
T S1 APARTMENT 29-JUN-18:53 0.00 -3848.61 0.00 0.00 141.81 103.77 547.42 339.96 0.00 1819.30 896.35 0.00 0.00 0.00 0.00 0.00
T S2 APARTMENT 29-JUN-18:53 0.00 -3839.03 0.00 0.00 141.81 103.77 547.42 340.22 0.00 1819.30 886.51 0.00 0.00 0.00 0.00 0.00
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUN-19:00 0.00 -107177.22 0.00 0.00 3235.73 4190.04 13114.08 11837.63 0.00 44415.37 30384.38 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [W] HVAC Input Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
G SW APARTMENT 09-JAN-05:00 843.70 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 72.53 0.00 -1080.29 0.00 -268.74 0.00
G NW APARTMENT 09-JAN-05:00 894.66 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 12.69 0.00 -1071.42 0.00 -268.74 0.00
OFFICE 25-JUL-16:01 1232.41 0.00 0.00 0.00 0.00 416.15 294.31 1346.09 0.00 258.99 0.00 0.00 0.00 0.00 0.00 -3547.95
G NE APARTMENT 09-JAN-05:00 904.68 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 1.63 0.00 -1070.37 0.00 -268.74 0.00
G N1 APARTMENT 19-JAN-08:02 892.81 0.00 0.00 0.00 74.58 19.46 388.49 0.00 0.00 0.00 0.00 0.00 -214.61 0.00 -58.02 -1102.72
G N2 APARTMENT 02-JAN-07:01 1055.54 0.00 0.00 0.00 162.74 42.16 382.60 0.00 0.00 0.00 0.00 0.00 -309.16 0.00 0.00 -1333.88
G S1 APARTMENT 06-DEC-06:23 421.49 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -478.24 0.00 -106.96 -389.22
G S2 APARTMENT 06-DEC-06:26 423.93 0.00 0.00 0.00 189.67 45.40 317.86 0.00 0.00 0.00 0.00 0.00 -478.12 0.00 -106.96 -391.77
M SW APARTMENT 09-JAN-05:00 663.93 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 448.77 0.00 -1158.74 0.00 -386.77 0.00
M NW APARTMENT 09-JAN-05:00 965.40 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 131.88 0.00 -1143.32 0.00 -386.77 0.00
M SE APARTMENT 09-JAN-05:00 744.64 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 364.66 0.00 -1155.33 0.00 -386.77 0.00
M NE APARTMENT 09-JAN-05:00 1033.58 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 60.42 0.00 -1140.04 0.00 -386.77 0.00
M N1 APARTMENT 12-JAN-16:00 260.34 0.00 0.00 0.00 41.53 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -4.08 0.00 -171.24 -549.51
M N2 APARTMENT 12-JAN-16:00 260.26 0.00 0.00 0.00 41.57 22.70 400.26 0.00 0.00 0.00 0.00 0.00 -3.64 0.00 -170.43 -550.72
M S1 APARTMENT 10-APR-05:15 168.25 0.00 0.00 0.00 162.99 45.40 317.86 0.00 0.00 0.00 341.48 0.00 -680.13 0.00 -355.85 0.00
M S2 APARTMENT 10-APR-05:15 167.03 0.00 0.00 0.00 162.99 45.40 317.86 0.00 0.00 0.00 342.91 0.00 -680.24 0.00 -355.95 0.00
T SW APARTMENT 09-JAN-05:00 1508.47 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1051.40 0.00 -513.05 -376.82
T NW APARTMENT 09-JAN-05:00 1538.09 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1044.11 0.00 -513.05 -413.74
T SE APARTMENT 09-JAN-05:00 1516.87 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1050.66 0.00 -513.05 -385.97
T NE APARTMENT 09-JAN-05:00 1545.54 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -1043.46 0.00 -513.05 -421.84
T N1 APARTMENT 09-JAN-05:00 872.62 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -646.07 0.00 -309.47 -349.89
T N2 APARTMENT 09-JAN-05:00 874.18 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -645.98 0.00 -309.47 -351.54
T S1 APARTMENT 09-JAN-05:00 827.26 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -655.28 0.00 -309.47 -295.32
T S2 APARTMENT 09-JAN-05:00 828.96 0.00 0.00 0.00 189.67 19.46 223.68 0.00 0.00 0.00 0.00 0.00 -655.18 0.00 -309.47 -297.11
T CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
G CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M CORRIDOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-JAN-05:00 16059.94 0.00 0.00 0.00 4344.64 2250.82 5427.18 0.00 0.00 0.00 1444.39 0.00 -21807.97 0.00 -7719.00 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Sec1.1A-General Information

Data
Weather File RIYADH - SAU IWEC Data WMO#=404380
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 3134.61
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
G SW APARTMENT 88.25 88.25 0.00 168.00
G NW APARTMENT 88.25 88.25 0.00 168.00
OFFICE 88.25 88.25 0.00 43.32
G NE APARTMENT 88.25 88.25 0.00 168.00
G N1 APARTMENT 88.25 88.25 0.00 168.00
G N2 APARTMENT 88.25 88.25 0.00 168.00
G S1 APARTMENT 88.25 88.25 0.00 168.00
G S2 APARTMENT 88.25 88.25 0.00 168.00
M SW APARTMENT 88.25 88.25 0.00 168.00
M NW APARTMENT 88.25 88.25 0.00 168.00
M SE APARTMENT 88.25 88.25 0.00 168.00
M NE APARTMENT 88.25 88.25 0.00 168.00
M N1 APARTMENT 88.25 88.25 0.00 168.00
M N2 APARTMENT 88.25 88.25 0.00 168.00
M S1 APARTMENT 88.25 88.25 0.00 168.00
M S2 APARTMENT 88.25 88.25 0.00 168.00
T SW APARTMENT 88.25 88.25 0.00 168.00
T NW APARTMENT 88.25 88.25 0.00 168.00
T SE APARTMENT 88.25 88.25 0.00 168.00
T NE APARTMENT 88.25 88.25 0.00 168.00
T N1 APARTMENT 88.25 88.25 0.00 168.00
T N2 APARTMENT 88.25 88.25 0.00 168.00
T S1 APARTMENT 88.25 88.25 0.00 168.00
T S2 APARTMENT 88.25 88.25 0.00 168.00
T CORRIDOR 77.66 0.00 77.66 0.00
G CORRIDOR 77.66 0.00 77.66 0.00
M CORRIDOR 77.66 0.00 77.66 0.00
Totals 3134.61 2823.98 310.64  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.50
Number of hours cooling loads not met 85.25
Number of hours not met 86.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 118.46 4979.95 0.00 0.00 0.00 0.00
Exterior Lighting 40.15 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 5.19 22560.99 0.00 0.00
Space Cooling 412.04 37953.63 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 349.85 11093.54 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 281.43 16912.62 0.00 0.00 0.00 0.00
Receptacle Equipment 517.65 26630.92 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 1719.58   5.19   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 517.65 1719.58
Natural Gas 0.00 5.19
Additional 0.00 0.00
Total 517.65 1724.77


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 37.79
Space Heating 0.00
Space Cooling 131.45
Fans-Interior 111.61
Service Water Heating 89.78
Receptacle Equipment 165.14
Miscellaneous 12.81
Subtotal 548.58


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.66
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 1.66


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.87
Space Heating 0.30
Space Cooling 23.89
Fans-Interior 20.28
Service Water Heating 16.32
Receptacle Equipment 30.01
Miscellaneous 2.33



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
G SW APARTMENT DIRECT AIR 0.294531
G NW APARTMENT DIRECT AIR 0.298698
OFFICE DIRECT AIR 0.588755
G NE APARTMENT DIRECT AIR 0.248549
G N1 APARTMENT DIRECT AIR 0.178580
G N2 APARTMENT DIRECT AIR 0.177788
G S1 APARTMENT DIRECT AIR 0.171150
G S2 APARTMENT DIRECT AIR 0.172618
M SW APARTMENT DIRECT AIR 0.704106
M NW APARTMENT DIRECT AIR 0.715231
M SE APARTMENT DIRECT AIR 0.614161
M NE APARTMENT DIRECT AIR 0.612869
M N1 APARTMENT DIRECT AIR 0.437429
M N2 APARTMENT DIRECT AIR 0.436180
M S1 APARTMENT DIRECT AIR 0.420131
M S2 APARTMENT DIRECT AIR 0.419595
T SW APARTMENT DIRECT AIR 0.475034
T NW APARTMENT DIRECT AIR 0.477095
T SE APARTMENT DIRECT AIR 0.425189
T NE APARTMENT DIRECT AIR 0.420961
T N1 APARTMENT DIRECT AIR 0.318980
T N2 APARTMENT DIRECT AIR 0.318298
T S1 APARTMENT DIRECT AIR 0.321743
T S2 APARTMENT DIRECT AIR 0.321587


Branch

Maximum Flow Rate [m3/s]
SPLIT GSW MAIN BRANCH 0.294531
SPLIT GNW MAIN BRANCH 0.298698
SPLIT OFFICE MAIN BRANCH 0.588755
SPLIT GNE MAIN BRANCH 0.248549
SPLIT GN1 MAIN BRANCH 0.178580
SPLIT GN2 MAIN BRANCH 0.177788
SPLIT GS1 MAIN BRANCH 0.171150
SPLIT GS2 MAIN BRANCH 0.172618
SPLIT MSW MAIN BRANCH 0.704106
SPLIT MNW MAIN BRANCH 0.715231
SPLIT MSE MAIN BRANCH 0.614161
SPLIT MNE MAIN BRANCH 0.612869
SPLIT MN1 MAIN BRANCH 0.437429
SPLIT MN2 MAIN BRANCH 0.436180
SPLIT MS1 MAIN BRANCH 0.420131
SPLIT MS2 MAIN BRANCH 0.419595
SPLIT TSW MAIN BRANCH 0.475034
SPLIT TNW MAIN BRANCH 0.477095
SPLIT TSE MAIN BRANCH 0.425189
SPLIT TNE MAIN BRANCH 0.420961
SPLIT TN1 MAIN BRANCH 0.318980
SPLIT TN2 MAIN BRANCH 0.318298
SPLIT TS1 MAIN BRANCH 0.321743
SPLIT TS2 MAIN BRANCH 0.321587


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SPLIT GSW 0.294531
SPLIT GNW 0.298698
SPLIT OFFICE 0.588755
SPLIT GNE 0.248549
SPLIT GN1 0.178580
SPLIT GN2 0.177788
SPLIT GS1 0.171150
SPLIT GS2 0.172618
SPLIT MSW 0.704106
SPLIT MNW 0.715231
SPLIT MSE 0.614161
SPLIT MNE 0.612869
SPLIT MN1 0.437429
SPLIT MN2 0.436180
SPLIT MS1 0.420131
SPLIT MS2 0.419595
SPLIT TSW 0.475034
SPLIT TNW 0.477095
SPLIT TSE 0.425189
SPLIT TNE 0.420961
SPLIT TN1 0.318980
SPLIT TN2 0.318298
SPLIT TS1 0.321743
SPLIT TS2 0.321587


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SPLIT GSW OA CONTROLLER 0.294531 0.026898
SPLIT GNW OA CONTROLLER 0.298698 0.025953
SPLIT OFFICE OA CONTROLLER 0.588755 0.038104
SPLIT GNE OA CONTROLLER 0.248549 0.025953
SPLIT GN1 OA CONTROLLER 0.178580 0.025953
SPLIT GN2 OA CONTROLLER 0.177788 0.025953
SPLIT GS1 OA CONTROLLER 0.171150 0.025953
SPLIT GS2 OA CONTROLLER 0.172618 0.025953
SPLIT MSW OA CONTROLLER 0.704106 0.051906
SPLIT MNW OA CONTROLLER 0.715231 0.051906
SPLIT MSE OA CONTROLLER 0.614161 0.051906
SPLIT MNE OA CONTROLLER 0.612869 0.051906
SPLIT MN1 OA CONTROLLER 0.437429 0.051906
SPLIT MN2 OA CONTROLLER 0.436180 0.051906
SPLIT MS1 OA CONTROLLER 0.420131 0.051906
SPLIT MS2 OA CONTROLLER 0.419595 0.051906
SPLIT TSW OA CONTROLLER 0.475034 0.025953
SPLIT TNW OA CONTROLLER 0.477095 0.025953
SPLIT TSE OA CONTROLLER 0.425189 0.025953
SPLIT TNE OA CONTROLLER 0.420961 0.025953
SPLIT TN1 OA CONTROLLER 0.318980 0.025953
SPLIT TN2 OA CONTROLLER 0.318298 0.025953
SPLIT TS1 OA CONTROLLER 0.321743 0.025953
SPLIT TS2 OA CONTROLLER 0.321587 0.025953


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W] Rated Sensible Heat Ratio
SPLIT GSW COOLING COIL 0.294531 5259.89 0.771789
SPLIT GNW COOLING COIL 0.298698 5233.09 0.778381
SPLIT OFFICE COOLING COIL 0.588755 9745.98 0.798655
SPLIT GNE COOLING COIL 0.248549 4375.08 0.776747
SPLIT GN1 COOLING COIL 0.178580 3141.83 0.776926
SPLIT GN2 COOLING COIL 0.177788 3128.53 0.776855
SPLIT GS1 COOLING COIL 0.171150 3183.99 0.758141
SPLIT GS2 COOLING COIL 0.172618 3244.39 0.754807
SPLIT MSW COOLING COIL 0.704106 12365.62 0.777541
SPLIT MNW COOLING COIL 0.715231 12353.48 0.783362
SPLIT MSE COOLING COIL 0.614161 10964.42 0.771901
SPLIT MNE COOLING COIL 0.612869 10666.24 0.780694
SPLIT MN1 COOLING COIL 0.437429 7616.03 0.780552
SPLIT MN2 COOLING COIL 0.436180 7594.97 0.780519
SPLIT MS1 COOLING COIL 0.420131 7649.61 0.765254
SPLIT MS2 COOLING COIL 0.419595 7679.73 0.763519
SPLIT TSW COOLING COIL 0.475034 8281.58 0.780095
SPLIT TNW COOLING COIL 0.477095 8281.09 0.781630
SPLIT TSE COOLING COIL 0.425189 7482.21 0.776847
SPLIT TNE COOLING COIL 0.420961 7408.17 0.776830
SPLIT TN1 COOLING COIL 0.318980 5705.92 0.771228
SPLIT TN2 COOLING COIL 0.318298 5694.04 0.771208
SPLIT TS1 COOLING COIL 0.321743 5781.79 0.769672
SPLIT TS2 COOLING COIL 0.321587 5779.09 0.769665


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SPLIT GSW FURNACE WITH DX COOLING 0.294531 0.294531 0.294531 0.294531 1449.18 5259.89 1.00
SPLIT GNW FURNACE WITH DX COOLING 0.298698 0.298698 0.298698 0.298698 1439.46 5233.09 1.00
SPLIT OFFICE FURNACE WITH DX COOLING 0.588755 0.588755 0.588755 0.588755 2806.95 9745.98 1.00
SPLIT GNE FURNACE WITH DX COOLING 0.248549 0.248549 0.248549 0.248549 1433.26 4375.08 1.00
SPLIT GN1 FURNACE WITH DX COOLING 0.178580 0.178580 0.178580 0.178580 1287.47 3141.83 1.00
SPLIT GN2 FURNACE WITH DX COOLING 0.177788 0.177788 0.177788 0.177788 1287.47 3128.53 1.00
SPLIT GS1 FURNACE WITH DX COOLING 0.171150 0.171150 0.171150 0.171150 1287.47 3183.99 1.00
SPLIT GS2 FURNACE WITH DX COOLING 0.172618 0.172618 0.172618 0.172618 1287.47 3244.39 1.00
SPLIT MSW FURNACE WITH DX COOLING 0.704106 0.704106 0.704106 0.704106 2929.10 12365.62 1.00
SPLIT MNW FURNACE WITH DX COOLING 0.715231 0.715231 0.715231 0.715231 2955.86 12353.48 1.00
SPLIT MSE FURNACE WITH DX COOLING 0.614161 0.614161 0.614161 0.614161 2911.82 10964.42 1.00
SPLIT MNE FURNACE WITH DX COOLING 0.612869 0.612869 0.612869 0.612869 2938.65 10666.24 1.00
SPLIT MN1 FURNACE WITH DX COOLING 0.437429 0.437429 0.437429 0.437429 2574.94 7616.03 1.00
SPLIT MN2 FURNACE WITH DX COOLING 0.436180 0.436180 0.436180 0.436180 2574.94 7594.97 1.00
SPLIT MS1 FURNACE WITH DX COOLING 0.420131 0.420131 0.420131 0.420131 2574.94 7649.61 1.00
SPLIT MS2 FURNACE WITH DX COOLING 0.419595 0.419595 0.419595 0.419595 2574.94 7679.73 1.00
SPLIT TSW FURNACE WITH DX COOLING 0.475034 0.475034 0.475034 0.475034 2152.60 8281.58 1.00
SPLIT TNW FURNACE WITH DX COOLING 0.477095 0.477095 0.477095 0.477095 2166.89 8281.09 1.00
SPLIT TSE FURNACE WITH DX COOLING 0.425189 0.425189 0.425189 0.425189 2143.56 7482.21 1.00
SPLIT TNE FURNACE WITH DX COOLING 0.420961 0.420961 0.420961 0.420961 2157.86 7408.17 1.00
SPLIT TN1 FURNACE WITH DX COOLING 0.318980 0.318980 0.318980 0.318980 1593.88 5705.92 1.00
SPLIT TN2 FURNACE WITH DX COOLING 0.318298 0.318298 0.318298 0.318298 1593.62 5694.04 1.00
SPLIT TS1 FURNACE WITH DX COOLING 0.321743 0.321743 0.321743 0.321743 1577.52 5781.79 1.00
SPLIT TS2 FURNACE WITH DX COOLING 0.321587 0.321587 0.321587 0.321587 1577.26 5779.09 1.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SPLIT GSW SUPPLY FAN 0.294531
SPLIT GNW SUPPLY FAN 0.298698
SPLIT OFFICE SUPPLY FAN 0.588755
SPLIT GNE SUPPLY FAN 0.248549
SPLIT GN1 SUPPLY FAN 0.178580
SPLIT GN2 SUPPLY FAN 0.177788
SPLIT GS1 SUPPLY FAN 0.171150
SPLIT GS2 SUPPLY FAN 0.172618
SPLIT MSW SUPPLY FAN 0.704106
SPLIT MNW SUPPLY FAN 0.715231
SPLIT MSE SUPPLY FAN 0.614161
SPLIT MNE SUPPLY FAN 0.612869
SPLIT MN1 SUPPLY FAN 0.437429
SPLIT MN2 SUPPLY FAN 0.436180
SPLIT MS1 SUPPLY FAN 0.420131
SPLIT MS2 SUPPLY FAN 0.419595
SPLIT TSW SUPPLY FAN 0.475034
SPLIT TNW SUPPLY FAN 0.477095
SPLIT TSE SUPPLY FAN 0.425189
SPLIT TNE SUPPLY FAN 0.420961
SPLIT TN1 SUPPLY FAN 0.318980
SPLIT TN2 SUPPLY FAN 0.318298
SPLIT TS1 SUPPLY FAN 0.321743
SPLIT TS2 SUPPLY FAN 0.321587


Coil:Heating:Gas

Nominal Capacity [W]
SPLIT GSW HEATING COIL 1449.18
SPLIT GNW HEATING COIL 1439.46
SPLIT OFFICE HEATING COIL 2806.95
SPLIT GNE HEATING COIL 1433.26
SPLIT GN1 HEATING COIL 1287.47
SPLIT GN2 HEATING COIL 1287.47
SPLIT GS1 HEATING COIL 1287.47
SPLIT GS2 HEATING COIL 1287.47
SPLIT MSW HEATING COIL 2929.10
SPLIT MNW HEATING COIL 2955.86
SPLIT MSE HEATING COIL 2911.82
SPLIT MNE HEATING COIL 2938.65
SPLIT MN1 HEATING COIL 2574.94
SPLIT MN2 HEATING COIL 2574.94
SPLIT MS1 HEATING COIL 2574.94
SPLIT MS2 HEATING COIL 2574.94
SPLIT TSW HEATING COIL 2152.60
SPLIT TNW HEATING COIL 2166.89
SPLIT TSE HEATING COIL 2143.56
SPLIT TNE HEATING COIL 2157.86
SPLIT TN1 HEATING COIL 1593.88
SPLIT TN2 HEATING COIL 1593.62
SPLIT TS1 HEATING COIL 1577.52
SPLIT TS2 HEATING COIL 1577.26



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
G SWALL SWA GWINDOW1 S SWA |
G WWALL SWA GWINDOW1 W SWA |
G NWALL NWA GWINDOW1 N NWA |
G WWALL NWA GWINDOW1 W NWA |
G SWALL SEA GWINDOW1 S SEA |
G EWALL SEA GWINDOW1 E SEA |
G NWALL NEA GWINDOW1 N NEA |
G EWALL NEA GWINDOW1 E NEA |
G NWALL N1A GWINDOW1 N N1A |
G NWALL N2A GWINDOW1 N N2A |
G SWALL S1A GWINDOW1 S S1A |
G SWALL S2A GWINDOW1 S S2A |
M WWALL SWA MWINDOW1 W SWA |
M SWALL SWA MWINDOW1 S SWA |
M NWALL NWA MWINDOW1 N NWA |
M WWALL NWA MWINDOW1 W NWA |
M EWALL SEA MWINDOW1 E SEA |
M SWALL SEA MWINDOW1 S SEA |
M NWALL NEA MWINDOW1 N NEA |
M EWALL NEA MWINDOW1 E NEA |
M NWALL N1A MWINDOW1 N N1A |
M NWALL N2A MWINDOW1 N N2A |
M SWALL S1A MWINDOW1 S S1A |
M SWALL S2A MWINDOW1 S S2A |
T WWALL SWA TWINDOW1 W SWA |
T SWALL SWA TWINDOW1 S SWA |
T NWALL NWA TWINDOW1 N NWA |
T WWALL NWA TWINDOW1 W NWA |
T EWALL SEA TWINDOW1 E SEA |
T SWALL SEA TWINDOW1 S SEA |
T NWALL NEA TWINDOW1 N NEA |
T EWALL NEA TWINDOW1 E NEA |
T NWALL N1A TWINDOW1 N N1A |
T NWALL N2A TWINDOW1 N N2A |
T SWALL S1A TWINDOW1 S S1A |
T SWALL S2A TWINDOW1 S S2A |
T EWALL C TWINDOW14 |
G EWALL C ENTRANCE DOOR |
M EWALL C MWINDOW14 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2015-09-09 18:48:04

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G SW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.28 14.02
February 23.64 16.67
March 24.06 20.28
April 24.35 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.29 21.57
December 23.35 14.93
     
Annual Sum or Average 24.11 26.21
Minimum of Months 23.28 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.56 14.02
February 23.22 16.67
March 23.90 20.28
April 24.35 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.39 27.59
November 24.18 21.57
December 22.80 14.93
     
Annual Sum or Average 23.95 26.21
Minimum of Months 22.56 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: OFFICE

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.18 14.02
February 24.74 16.67
March 25.41 20.28
April 26.48 25.86
May 27.33 32.05
June 27.71 35.24
July 27.77 36.21
August 27.61 36.44
September 27.86 33.05
October 27.04 27.59
November 26.12 21.57
December 24.37 14.93
     
Annual Sum or Average 26.39 26.21
Minimum of Months 24.18 14.02
Maximum of Months 27.86 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G NE APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.46 14.02
February 23.12 16.67
March 23.87 20.28
April 24.34 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.39 27.59
November 24.15 21.57
December 22.66 14.93
     
Annual Sum or Average 23.92 26.21
Minimum of Months 22.46 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.34 14.02
February 22.98 16.67
March 23.77 20.28
April 24.33 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.38 27.59
November 24.11 21.57
December 22.63 14.93
     
Annual Sum or Average 23.88 26.21
Minimum of Months 22.34 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G N2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.33 14.02
February 22.98 16.67
March 23.77 20.28
April 24.32 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.38 27.59
November 24.11 21.57
December 22.62 14.93
     
Annual Sum or Average 23.88 26.21
Minimum of Months 22.33 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 14.02
February 23.62 16.67
March 24.01 20.28
April 24.34 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.41 36.44
September 24.40 33.05
October 24.39 27.59
November 24.27 21.57
December 23.38 14.93
     
Annual Sum or Average 24.11 26.21
Minimum of Months 23.31 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G S2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 14.02
February 23.65 16.67
March 24.04 20.28
April 24.35 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.41 36.44
September 24.40 33.05
October 24.40 27.59
November 24.29 21.57
December 23.40 14.93
     
Annual Sum or Average 24.12 26.21
Minimum of Months 23.33 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 14.02
February 24.33 16.67
March 24.39 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 24.17 14.93
     
Annual Sum or Average 24.35 26.21
Minimum of Months 24.16 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.64 14.02
February 24.18 16.67
March 24.36 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 23.75 14.93
     
Annual Sum or Average 24.26 26.21
Minimum of Months 23.64 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M SE APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.12 14.02
February 24.31 16.67
March 24.38 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 24.12 14.93
     
Annual Sum or Average 24.34 26.21
Minimum of Months 24.12 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M NE APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.57 14.02
February 24.15 16.67
March 24.36 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 23.64 14.93
     
Annual Sum or Average 24.24 26.21
Minimum of Months 23.57 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 14.02
February 24.23 16.67
March 24.38 20.28
April 24.40 25.86
May 24.40 32.05
June 24.41 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 23.88 14.93
     
Annual Sum or Average 24.29 26.21
Minimum of Months 23.76 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M N2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 14.02
February 24.23 16.67
March 24.38 20.28
April 24.40 25.86
May 24.40 32.05
June 24.41 35.24
July 24.41 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 23.87 14.93
     
Annual Sum or Average 24.29 26.21
Minimum of Months 23.76 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 14.02
February 24.37 16.67
March 24.40 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.41 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 24.29 14.93
     
Annual Sum or Average 24.38 26.21
Minimum of Months 24.28 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M S2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.28 14.02
February 24.37 16.67
March 24.40 20.28
April 24.40 25.86
May 24.40 32.05
June 24.40 35.24
July 24.41 36.21
August 24.41 36.44
September 24.40 33.05
October 24.40 27.59
November 24.40 21.57
December 24.29 14.93
     
Annual Sum or Average 24.38 26.21
Minimum of Months 24.28 14.02
Maximum of Months 24.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.62 14.02
February 23.97 16.67
March 24.26 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.37 21.57
December 23.66 14.93
     
Annual Sum or Average 24.22 26.21
Minimum of Months 23.62 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NW APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 14.02
February 23.77 16.67
March 24.20 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.34 21.57
December 23.32 14.93
     
Annual Sum or Average 24.13 26.21
Minimum of Months 23.18 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T SE APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.60 14.02
February 23.93 16.67
March 24.24 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.35 21.57
December 23.61 14.93
     
Annual Sum or Average 24.21 26.21
Minimum of Months 23.60 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T NE APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.17 14.02
February 23.75 16.67
March 24.19 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.32 21.57
December 23.24 14.93
     
Annual Sum or Average 24.12 26.21
Minimum of Months 23.17 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 14.02
February 23.82 16.67
March 24.23 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.34 21.57
December 23.33 14.93
     
Annual Sum or Average 24.14 26.21
Minimum of Months 23.18 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T N2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.18 14.02
February 23.81 16.67
March 24.23 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.34 21.57
December 23.32 14.93
     
Annual Sum or Average 24.14 26.21
Minimum of Months 23.18 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S1 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.75 14.02
February 24.06 16.67
March 24.30 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.37 21.57
December 23.79 14.93
     
Annual Sum or Average 24.25 26.21
Minimum of Months 23.75 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T S2 APARTMENT

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.75 14.02
February 24.06 16.67
March 24.29 20.28
April 24.39 25.86
May 24.40 32.05
June 24.40 35.24
July 24.40 36.21
August 24.40 36.44
September 24.40 33.05
October 24.40 27.59
November 24.37 21.57
December 23.78 14.93
     
Annual Sum or Average 24.25 26.21
Minimum of Months 23.75 14.02
Maximum of Months 24.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: T CORRIDOR

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 14.02
February 25.03 16.67
March 25.82 20.28
April 26.70 25.86
May 27.59 32.05
June 27.98 35.24
July 28.07 36.21
August 28.12 36.44
September 27.73 33.05
October 27.02 27.59
November 26.07 21.57
December 24.30 14.93
     
Annual Sum or Average 26.55 26.21
Minimum of Months 24.14 14.02
Maximum of Months 28.12 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: G CORRIDOR

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 14.02
February 23.28 16.67
March 24.30 20.28
April 25.77 25.86
May 27.20 32.05
June 28.58 35.24
July 28.91 36.21
August 28.96 36.44
September 28.38 33.05
October 26.56 27.59
November 25.00 21.57
December 22.71 14.93
     
Annual Sum or Average 26.01 26.21
Minimum of Months 22.39 14.02
Maximum of Months 28.96 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: M CORRIDOR

Timestamp: 2015-09-09 18:48:04

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.56 14.02
February 26.11 16.67
March 26.44 20.28
April 26.84 25.86
May 27.31 32.05
June 27.55 35.24
July 27.61 36.21
August 27.63 36.44
September 27.44 33.05
October 27.11 27.59
November 26.67 21.57
December 25.67 14.93
     
Annual Sum or Average 26.83 26.21
Minimum of Months 25.56 14.02
Maximum of Months 27.63 36.44



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:04

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY [Invalid/Undefined] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.123014E+12 75118.388 24-JAN-18:00 4979.953 26630.920 11093.542 0.000 7697.650 2553.000 0.000 0.000 0.000 0.000 0.000 22163.322 0.000 0.000 0.000
February 0.114432E+12 77848.976 26-FEB-18:15 4979.953 26630.920 11093.542 0.000 13367.961 2553.000 0.000 0.000 0.000 0.000 0.000 19223.599 0.000 0.000 0.000
March 0.130619E+12 82625.519 31-MAR-17:30 4979.953 26630.920 11093.542 0.000 20845.723 0.000 0.000 0.000 0.000 0.000 0.000 19075.380 0.000 0.000 0.000
April 0.136048E+12 84872.579 18-APR-16:15 4276.255 26730.986 11093.542 0.000 23824.341 0.000 0.000 0.000 0.000 0.000 0.000 18947.454 0.000 0.000 0.000
May 0.155005E+12 90957.269 18-MAY-16:30 4276.255 26730.986 11093.542 0.000 31139.324 0.000 0.000 0.000 0.000 0.000 0.000 17717.162 0.000 0.000 0.000
June 0.160535E+12 96116.561 16-JUN-17:15 4979.953 26630.920 11093.542 0.000 37863.162 0.000 0.000 0.000 0.000 0.000 0.000 15548.983 0.000 0.000 0.000
July 0.168866E+12 97570.667 30-JUL-17:15 4979.953 26630.920 11093.542 0.000 37953.630 0.000 0.000 0.000 0.000 0.000 0.000 16912.622 0.000 0.000 0.000
August 0.170341E+12 96014.002 24-AUG-16:15 4276.255 26730.986 11093.542 0.000 38066.203 0.000 0.000 0.000 0.000 0.000 0.000 15847.016 0.000 0.000 0.000
September 0.156777E+12 94471.239 03-SEP-16:15 4276.255 26630.920 11093.542 0.000 34613.920 0.000 0.000 0.000 0.000 0.000 0.000 17856.602 0.000 0.000 0.000
October 0.148858E+12 87609.505 09-OCT-16:30 4276.255 26730.986 11093.542 0.000 27541.733 0.000 0.000 0.000 0.000 0.000 0.000 17966.988 0.000 0.000 0.000
November 0.131709E+12 81926.177 02-NOV-17:15 4979.953 26630.920 11093.542 0.000 15523.013 2553.000 0.000 0.000 0.000 0.000 0.000 21145.748 0.000 0.000 0.000
December 0.123380E+12 74305.990 16-DEC-18:15 4979.953 26630.920 11093.542 0.000 8640.985 2553.000 0.000 0.000 0.000 0.000 0.000 20407.589 0.000 0.000 0.000
                                     
Annual Sum or Average 0.171958E+13                 0.000 0.000 0.000 0.000 0.000   0.000 0.000 0.000
Minimum of Months 0.114432E+12 74305.990   4276.255 26630.920 11093.542 0.000 7697.650 0.000 0.000 0.000 0.000 0.000 0.000 15548.983 0.000 0.000 0.000
Maximum of Months 0.170341E+12 97570.667   4979.953 26730.986 11093.542 0.000 38066.203 2553.000 0.000 0.000 0.000 0.000 0.000 22163.322 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-09 18:48:04

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS [Invalid/Undefined] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT [Invalid/Undefined] WATERSYSTEMS:GAS [Invalid/Undefined] WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] HEATING:GAS {AT MAX/MIN} [W]
January 0.249937E+10 22560.994 09-JAN-04:00 22560.994 0.000 0.000 0.000 0.000 0.000 22560.994
February 0.495896E+09 7946.625 11-FEB-04:00 7946.625 0.000 0.000 0.000 0.000 0.000 7946.625
March 7085200.731 1121.359 16-MAR-10:00 1121.359 0.000 0.000 0.000 0.000 0.000 1121.359
April 0.000 0.000 01-APR-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.000 0.000 01-MAY-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.000 0.000 01-JUN-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 01-JUL-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 01-AUG-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 01-SEP-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 01-OCT-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.000 0.000 01-NOV-00:15 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.218873E+10 17284.030 06-DEC-03:00 17284.030 0.000 0.000 0.000 0.000 0.000 17284.030
                     
Annual Sum or Average 0.519108E+10       0.000 0.000 0.000 0.000 0.000  
Minimum of Months 0.000 0.000   0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.249937E+10 22560.994   22560.994 0.000 0.000 0.000 0.000 0.000 22560.994