Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48
Tabular Output Report in Format: HTML
Building: Mid-Rise Apartment
Environment: Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Simulation Timestamp: 2015-09-09 18:48:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1650.91 | 526.67 | 584.61 |
Net Site Energy | 1650.91 | 526.67 | 584.61 |
Total Source Energy | 5202.64 | 1659.74 | 1842.31 |
Net Source Energy | 5202.64 | 1659.74 | 1842.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3134.61 |
Net Conditioned Building Area | 2823.98 |
Unconditioned Building Area | 310.64 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 12.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 345.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 118.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 310.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1638.52 | 12.39 | 0.00 | 0.00 | 0.00 | 1874.72 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 12.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 345.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 96.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 517.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 306.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 310.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1874.72 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 340.77 | 4.39 | 0.00 | 0.00 | 0.00 | 0.66 |
Other | 183.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 580.22 | 4.39 | 0.00 | 0.00 | 0.00 | 0.66 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 307.00 | 3.95 | 0.00 | 0.00 | 0.00 | 0.60 |
Other | 165.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 522.72 | 3.95 | 0.00 | 0.00 | 0.00 | 0.60 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1638.52 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1638.52 | 100.00 |
Total On-Site and Utility Electric Sources | 1638.52 | 100.00 |
Total Electricity End Uses | 1638.52 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 1874.72 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 1874.72 | 100.00 |
Total Water End Uses | 1874.72 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 11.25 |
Time Setpoint Not Met During Occupied Cooling | 9.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 97.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| G SW APARTMENT | G NW APARTMENT | OFFICE | G NE APARTMENT | G N1 APARTMENT | G N2 APARTMENT | G S1 APARTMENT | G S2 APARTMENT | M SW APARTMENT | M NW APARTMENT | M SE APARTMENT | M NE APARTMENT | M N1 APARTMENT | M N2 APARTMENT | M S1 APARTMENT | M S2 APARTMENT | T SW APARTMENT | T NW APARTMENT | T SE APARTMENT | T NE APARTMENT | T N1 APARTMENT | T N2 APARTMENT | T S1 APARTMENT | T S2 APARTMENT | T CORRIDOR | G CORRIDOR | M CORRIDOR |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.09 18:48 |
RunPeriod | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Weather File | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Latitude [deg] | 33.45 |
Longitude [deg] | -112.0 |
Elevation [m] | 337.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1542.04 | 564.80 | 206.22 | 564.80 | 206.22 |
Window Opening Area [m2] | 306.92 | 112.97 | 37.16 | 112.97 | 43.82 |
Window-Wall Ratio [%] | 19.90 | 20.00 | 18.02 | 20.00 | 21.25 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1501.17 | 564.80 | 185.79 | 564.80 | 185.79 |
Window Opening Area [m2] | 300.26 | 112.97 | 37.16 | 112.97 | 37.16 |
Window-Wall Ratio [%] | 20.00 | 20.00 | 20.00 | 20.00 | 20.00 |
Total | |
Gross Roof Area [m2] | 783.65 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
G SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
OFFICE | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 26.1977 | 88.25 | 6.6700 |
G NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
G N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
G S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
M N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
M S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 2.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T SW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NW APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T SE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T NE APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 58.52 | 11.71 | 3.6746 | 35.30 | 6.6700 |
T N1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T N2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S1 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T S2 APARTMENT | 88.25 | Yes | Yes | 268.97 | 1.00 | 35.30 | 7.06 | 3.6746 | 35.30 | 6.6700 |
T CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
G CORRIDOR | 77.66 | No | Yes | 236.69 | 1.00 | 10.22 | 3.32 | 5.9540 | 208.8202 | |
M CORRIDOR | 77.66 | No | Yes | 236.69 | 2.00 | 10.22 | 1.11 | 5.9540 | 0.0000 | |
Total | 3134.61 | 9553.84 | 1542.04 | 306.92 | 4.5346 | 39.93 | 11.1825 | |||
Conditioned Total | 2823.98 | 8607.06 | 1501.17 | 300.26 | 4.3785 | 35.97 | 6.6700 | |||
Unconditioned Total | 310.64 | 946.78 | 40.87 | 6.66 | 5.9540 | 52.2051 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-17:15 | 10-FEB-06:00 | - | - | - | 01-JAN-07:30 |
Heating | 0.00 | 22335.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33445.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9718.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18998.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93773.47 | 22335.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 22335.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33445.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GeneralLights | 4056.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GeneralLights-plugin | 923.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9718.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 18998.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 13.43 | 0.00 | 0.00 | 0.00 |
Cooling | 1095.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 126.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1639.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 970.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 981.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5189.21 | 13.43 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.76 | 0.00 | 0.00 | 0.00 |
Cooling | 387.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 343.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 347.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1837.55 | 4.76 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4.76 | 0.00 | 0.00 | 0.00 |
Cooling | 387.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 132.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 580.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 343.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 347.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1837.55 | 4.76 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 3.70 | 0.00 | 3.70 | Wetbulb [C] | 1.70 | 100.00 |
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 43.40 | 12.00 | 21.10 | Wetbulb [C] | 4.10 | 260.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
G SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR SWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
G GFLOOR NWA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR SEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
G GFLOOR NEA | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
G GFLOOR N2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S1A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
G SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
G GFLOOR S2A | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 88.25 | 90.00 | 180.00 | |
M WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 270.00 | 90.00 | W |
M EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 46.45 | 90.00 | 90.00 | E |
M NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 0.00 | 90.00 | N |
M SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
M SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 70.60 | 180.00 | 90.00 | S |
T WWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T SWALL SWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T WWALL NWA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 270.00 | 90.00 | W |
T ROOF NWA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T EWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T SWALL SEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF SEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T EWALL NEA | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.22 | 90.00 | 90.00 | E |
T ROOF NEA | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T NWALL N2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 0.00 | 90.00 | N |
T ROOF N2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S1A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S1A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T SWALL S2A | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.30 | 180.00 | 90.00 | S |
T ROOF S2A | RES_ROOF | 0.30 | 0.269 | 0.283 | 88.25 | 180.00 | 0.00 | |
T WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
T EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
T ROOF C | RES_ROOF | 0.30 | 0.269 | 0.283 | 77.66 | 180.00 | 0.00 | |
G WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 270.00 | 90.00 | W |
G EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
G FLOOR C | INT_SLAB_CEILING | 0.30 | 1.986 | 3.839 | 77.66 | 90.00 | 180.00 | |
M WWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
M EWALL C | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
GWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SWA | 180.00 | 90.00 | S | ||
GWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL SWA | 270.00 | 90.00 | W | ||
GWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NWA | 0.00 | 90.00 | N | ||
GWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G WWALL NWA | 270.00 | 90.00 | W | ||
GWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL SEA | 180.00 | 90.00 | S | ||
GWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL SEA | 90.00 | 90.00 | E | ||
GWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL NEA | 0.00 | 90.00 | N | ||
GWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | G EWALL NEA | 90.00 | 90.00 | E | ||
GWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N1A | 0.00 | 90.00 | N | ||
GWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G NWALL N2A | 0.00 | 90.00 | N | ||
GWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S1A | 180.00 | 90.00 | S | ||
GWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | G SWALL S2A | 180.00 | 90.00 | S | ||
MWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL SWA | 270.00 | 90.00 | W | ||
MWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SWA | 180.00 | 90.00 | S | ||
MWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NWA | 0.00 | 90.00 | N | ||
MWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M WWALL NWA | 270.00 | 90.00 | W | ||
MWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL SEA | 90.00 | 90.00 | E | ||
MWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL SEA | 180.00 | 90.00 | S | ||
MWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL NEA | 0.00 | 90.00 | N | ||
MWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 9.29 | 4.600 | 0.293 | 0.130 | No | M EWALL NEA | 90.00 | 90.00 | E | ||
MWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N1A | 0.00 | 90.00 | N | ||
MWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M NWALL N2A | 0.00 | 90.00 | N | ||
MWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S1A | 180.00 | 90.00 | S | ||
MWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 14.12 | 4.600 | 0.293 | 0.130 | No | M SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW1 W SWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL SWA | 270.00 | 90.00 | W | ||
TWINDOW1 S SWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SWA | 180.00 | 90.00 | S | ||
TWINDOW1 N NWA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NWA | 0.00 | 90.00 | N | ||
TWINDOW1 W NWA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T WWALL NWA | 270.00 | 90.00 | W | ||
TWINDOW1 E SEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL SEA | 90.00 | 90.00 | E | ||
TWINDOW1 S SEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL SEA | 180.00 | 90.00 | S | ||
TWINDOW1 N NEA | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL NEA | 0.00 | 90.00 | N | ||
TWINDOW1 E NEA | WINDOW_U_0.72_SHGC_0.25 | 4.65 | 0.00 | 0.00 | 4.65 | 4.65 | 4.600 | 0.293 | 0.130 | No | T EWALL NEA | 90.00 | 90.00 | E | ||
TWINDOW1 N N1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N1A | 0.00 | 90.00 | N | ||
TWINDOW1 N N2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T NWALL N2A | 0.00 | 90.00 | N | ||
TWINDOW1 S S1A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S1A | 180.00 | 90.00 | S | ||
TWINDOW1 S S2A | WINDOW_U_0.72_SHGC_0.25 | 7.06 | 0.00 | 0.00 | 7.06 | 7.06 | 4.600 | 0.293 | 0.130 | No | T SWALL S2A | 180.00 | 90.00 | S | ||
TWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 4.600 | 0.293 | 0.130 | No | T EWALL C | 270.00 | 90.00 | W | ||
ENTRANCE DOOR | WINDOW_U_0.72_SHGC_0.25 | 3.32 | 0.00 | 0.00 | 3.32 | 3.32 | 4.600 | 0.293 | 0.130 | No | G EWALL C | 270.00 | 90.00 | W | ||
MWINDOW14 | WINDOW_U_0.72_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 2.23 | 4.600 | 0.293 | 0.130 | No | M EWALL C | 270.00 | 90.00 | W | ||
Total or Average | 306.92 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 112.97 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 193.95 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
GWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
GWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
GWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
GWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
MWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
MWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 W SWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 S SWA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NWA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 W NWA | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
TWINDOW1 E SEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 S SEA | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 N NEA | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 E NEA | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
TWINDOW1 N N1A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 N N2A | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TWINDOW1 S S1A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW1 S S2A | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
TWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ENTRANCE DOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
MWINDOW14 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LIGHTING_HARDWIRED_GSW | G SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GNW | G NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_HARDWIRED_GNE | G NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN1 | G N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GN2 | G N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS1 | G S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GS2 | G S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSW | M SW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNW | M NW APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MSE | M SE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MNE | M NE APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN1 | M N1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MN2 | M N2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS1 | M S1 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_MS2 | M S2 APARTMENT | 2.7059 | 176.50 | 477.59 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSW | T SW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNW | T NW APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TSE | T SE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TNE | T NE APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN1 | T N1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TN2 | T N2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS1 | T S1 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_TS2 | T S2 APARTMENT | 2.7059 | 88.25 | 238.79 | GeneralLights | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.80 |
LIGHTING_HARDWIRED_GC | G CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_MC | M CORRIDOR | 5.9540 | 155.32 | 924.77 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_HARDWIRED_TC | T CORRIDOR | 5.9540 | 77.66 | 462.39 | GeneralLights | LTG_COR_SCH | 168.00 | 168.00 | 168.00 | 0.0000 | N | 14.58 |
LIGHTING_PLUGIN_GSW | G SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GNW | G NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_OFFICE | OFFICE | 13.0989 | 88.25 | 1155.96 | GeneralLights-plugin | LTG_OFF_SCH | 62.17 | 168.00 | 60.95 | 0.0000 | Y | 13.23 |
LIGHTING_PLUGIN_GNE | G NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN1 | G N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GN2 | G N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS1 | G S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_GS2 | G S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSW | M SW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNW | M NW APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MSE | M SE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MNE | M NE APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN1 | M N1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MN2 | M N2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS1 | M S1 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_MS2 | M S2 APARTMENT | 0.9688 | 176.50 | 170.98 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSW | T SW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNW | T NW APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TSE | T SE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TNE | T NE APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN1 | T N1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TN2 | T N2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS1 | T S1 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
LIGHTING_PLUGIN_TS2 | T S2 APARTMENT | 0.9688 | 88.25 | 85.49 | GeneralLights-plugin | LTG_APT_SCH | 17.85 | 168.00 | 17.85 | 0.0000 | Y | 0.29 |
Interior Lighting Total | 2.3855 | 5958.59 | 14214.30 | 95.19 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
FACADE LIGHTING | 2553.00 | AstronomicalClock | - | 83.65 | 83.65 | 40.09 | |
Exterior Lighting Total | 2553.00 | 40.09 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4908.30 | 3677.73 | 1230.56 | 0.75 | 3.91 | |||
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4706.32 | 3570.13 | 1136.19 | 0.76 | 3.91 | |||
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9279.36 | 7411.01 | 1868.35 | 0.80 | 3.91 | |||
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4003.88 | 3039.68 | 964.20 | 0.76 | 3.91 | |||
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2905.22 | 2172.66 | 732.56 | 0.75 | 3.91 | |||
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2893.68 | 2163.52 | 730.16 | 0.75 | 3.91 | |||
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3294.66 | 2391.49 | 903.18 | 0.73 | 3.91 | |||
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3342.35 | 2428.36 | 913.99 | 0.73 | 3.91 | |||
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11351.41 | 8593.06 | 2758.35 | 0.76 | 3.91 | |||
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11015.27 | 8392.01 | 2623.25 | 0.76 | 3.91 | |||
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10183.62 | 7735.10 | 2448.52 | 0.76 | 3.91 | |||
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9541.04 | 7271.73 | 2269.31 | 0.76 | 3.91 | |||
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6846.63 | 5150.19 | 1696.44 | 0.75 | 3.91 | |||
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6828.62 | 5135.94 | 1692.68 | 0.75 | 3.91 | |||
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7753.24 | 5688.21 | 2065.02 | 0.73 | 3.91 | |||
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7768.52 | 5700.04 | 2068.47 | 0.73 | 3.91 | |||
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7749.77 | 5877.27 | 1872.50 | 0.76 | 3.91 | |||
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7430.85 | 5663.31 | 1767.54 | 0.76 | 3.91 | |||
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7206.01 | 5426.30 | 1779.71 | 0.75 | 3.91 | |||
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6671.19 | 5012.04 | 1659.15 | 0.75 | 3.91 | |||
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5242.50 | 3905.88 | 1336.63 | 0.75 | 3.91 | |||
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5240.83 | 3904.58 | 1336.25 | 0.75 | 3.91 | |||
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5765.89 | 4303.82 | 1462.08 | 0.75 | 3.91 | |||
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5774.29 | 4310.31 | 1463.97 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
SPLIT GSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4706.7 | 3.21 | 10.97 | 11.41 | 10.81 |
SPLIT GNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4507.5 | 3.20 | 10.91 | 11.35 | 10.72 |
SPLIT OFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8840.1 | 3.13 | 10.67 | 11.09 | 10.38 |
SPLIT GNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3834.4 | 3.20 | 10.91 | 11.34 | 10.72 |
SPLIT GN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2786.4 | 3.22 | 10.98 | 11.42 | 10.82 |
SPLIT GN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2775.4 | 3.22 | 10.98 | 11.42 | 10.82 |
SPLIT GS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3169.2 | 3.26 | 11.11 | 11.57 | 11.02 |
SPLIT GS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3214.7 | 3.26 | 11.11 | 11.56 | 11.02 |
SPLIT MSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10874.1 | 3.20 | 10.92 | 11.36 | 10.74 |
SPLIT MNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10545.3 | 3.19 | 10.89 | 11.33 | 10.70 |
SPLIT MSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9752.1 | 3.20 | 10.90 | 11.34 | 10.72 |
SPLIT MNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9133.6 | 3.19 | 10.89 | 11.32 | 10.69 |
SPLIT MN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6562.9 | 3.21 | 10.95 | 11.39 | 10.78 |
SPLIT MN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6545.7 | 3.21 | 10.95 | 11.39 | 10.78 |
SPLIT MS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7450.2 | 3.24 | 11.06 | 11.52 | 10.95 |
SPLIT MS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7464.8 | 3.24 | 11.06 | 11.51 | 10.95 |
SPLIT TSW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7422.5 | 3.20 | 10.91 | 11.35 | 10.73 |
SPLIT TNW COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7113.5 | 3.19 | 10.89 | 11.32 | 10.69 |
SPLIT TSE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6906.6 | 3.21 | 10.94 | 11.39 | 10.77 |
SPLIT TNE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6395.5 | 3.21 | 10.95 | 11.40 | 10.79 |
SPLIT TN1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5030.0 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT TN2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5028.4 | 3.22 | 10.99 | 11.44 | 10.85 |
SPLIT TS1 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5531.2 | 3.22 | 10.98 | 11.43 | 10.83 |
SPLIT TS2 COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5539.2 | 3.22 | 10.98 | 11.43 | 10.83 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
SPLIT GSW HEATING COIL | Coil:Heating:Gas | 1447.88 | 0.80 | |
SPLIT GNW HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT OFFICE HEATING COIL | Coil:Heating:Gas | 2781.59 | 0.80 | |
SPLIT GNE HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT GN1 HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT GN2 HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT GS1 HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT GS2 HEATING COIL | Coil:Heating:Gas | 1396.99 | 0.80 | |
SPLIT MSW HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MNW HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MSE HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MNE HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MN1 HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MN2 HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MS1 HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT MS2 HEATING COIL | Coil:Heating:Gas | 2793.97 | 0.80 | |
SPLIT TSW HEATING COIL | Coil:Heating:Gas | 2097.95 | 0.80 | |
SPLIT TNW HEATING COIL | Coil:Heating:Gas | 2099.59 | 0.80 | |
SPLIT TSE HEATING COIL | Coil:Heating:Gas | 2106.14 | 0.80 | |
SPLIT TNE HEATING COIL | Coil:Heating:Gas | 2107.78 | 0.80 | |
SPLIT TN1 HEATING COIL | Coil:Heating:Gas | 1586.83 | 0.80 | |
SPLIT TN2 HEATING COIL | Coil:Heating:Gas | 1586.98 | 0.80 | |
SPLIT TS1 HEATING COIL | Coil:Heating:Gas | 1584.84 | 0.80 | |
SPLIT TS2 HEATING COIL | Coil:Heating:Gas | 1584.99 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
SPLIT GSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.26 | 297.98 | 1160.84 | 1.00 | General |
SPLIT GNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.25 | 294.06 | 1160.84 | 1.00 | General |
SPLIT OFFICE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.56 | 650.73 | 1160.84 | 1.00 | General |
SPLIT GNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.22 | 250.63 | 1160.84 | 1.00 | General |
SPLIT GN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 175.58 | 1160.84 | 1.00 | General |
SPLIT GN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.15 | 174.78 | 1160.84 | 1.00 | General |
SPLIT GS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 185.30 | 1160.84 | 1.00 | General |
SPLIT GS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.16 | 188.41 | 1160.84 | 1.00 | General |
SPLIT MSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.61 | 705.85 | 1160.84 | 1.00 | General |
SPLIT MNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.60 | 695.14 | 1160.84 | 1.00 | General |
SPLIT MSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.55 | 638.21 | 1160.84 | 1.00 | General |
SPLIT MNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.52 | 602.65 | 1160.84 | 1.00 | General |
SPLIT MN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 419.49 | 1160.84 | 1.00 | General |
SPLIT MN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.36 | 418.25 | 1160.84 | 1.00 | General |
SPLIT MS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 447.58 | 1160.84 | 1.00 | General |
SPLIT MS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.39 | 448.58 | 1160.84 | 1.00 | General |
SPLIT TSW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 483.93 | 1160.84 | 1.00 | General |
SPLIT TNW SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.40 | 469.34 | 1160.84 | 1.00 | General |
SPLIT TSE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.38 | 442.61 | 1160.84 | 1.00 | General |
SPLIT TNE SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.35 | 407.56 | 1160.84 | 1.00 | General |
SPLIT TN1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 314.03 | 1160.84 | 1.00 | General |
SPLIT TN2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.27 | 313.92 | 1160.84 | 1.00 | General |
SPLIT TS1 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 346.90 | 1160.84 | 1.00 | General |
SPLIT TS2 SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.30 | 347.45 | 1160.84 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
G SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
G S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
M S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NW APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T SE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T NE APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T N2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S1 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
T S2 APARTMENT WATER HEATER | WaterHeater:Mixed | 0.19 | 14653.55 | 1.00 | 3.78 | 0.90 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 2624.65 | 3149.58 | 0.214 | 0.257 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.20 | 0.00720 |
G NW APARTMENT | 2590.11 | 3108.14 | 0.211 | 0.253 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 40.82 | 0.00720 |
OFFICE | 5600.71 | 6720.85 | 0.467 | 0.561 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 36.80 | 0.00720 |
G NE APARTMENT | 2207.58 | 2649.09 | 0.180 | 0.216 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 40.19 | 0.00720 |
G N1 APARTMENT | 1546.48 | 1855.77 | 0.126 | 0.151 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 39.62 | 0.00720 |
G N2 APARTMENT | 1539.48 | 1847.37 | 0.125 | 0.151 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 39.62 | 0.00720 |
G S1 APARTMENT | 1632.12 | 1958.55 | 0.133 | 0.160 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 43.25 | 0.00720 |
G S2 APARTMENT | 1659.55 | 1991.46 | 0.135 | 0.162 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 43.25 | 0.00720 |
M SW APARTMENT | 6217.18 | 7460.62 | 0.507 | 0.608 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 41.96 | 0.00720 |
M NW APARTMENT | 6122.80 | 7347.35 | 0.499 | 0.599 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 41.12 | 0.00720 |
M SE APARTMENT | 5621.38 | 6745.66 | 0.458 | 0.550 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 41.24 | 0.00720 |
M NE APARTMENT | 5308.17 | 6369.81 | 0.433 | 0.519 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 40.64 | 0.00720 |
M N1 APARTMENT | 3694.86 | 4433.84 | 0.301 | 0.361 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 40.07 | 0.00720 |
M N2 APARTMENT | 3683.97 | 4420.76 | 0.300 | 0.360 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 40.07 | 0.00720 |
M S1 APARTMENT | 3942.32 | 4730.78 | 0.321 | 0.386 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 43.25 | 0.00720 |
M S2 APARTMENT | 3951.13 | 4741.35 | 0.322 | 0.386 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 43.25 | 0.00720 |
T SW APARTMENT | 4262.51 | 5115.01 | 0.347 | 0.417 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 42.86 | 0.00720 |
T NW APARTMENT | 4133.98 | 4960.77 | 0.337 | 0.404 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.20 | 0.00720 |
T SE APARTMENT | 3898.59 | 4678.31 | 0.318 | 0.381 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 43.40 | 0.00720 |
T NE APARTMENT | 3589.88 | 4307.86 | 0.293 | 0.351 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 43.40 | 0.00720 |
T N1 APARTMENT | 2765.95 | 3319.14 | 0.225 | 0.271 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 43.22 | 0.00720 |
T N2 APARTMENT | 2764.98 | 3317.98 | 0.225 | 0.270 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 43.22 | 0.00720 |
T S1 APARTMENT | 3055.52 | 3666.62 | 0.249 | 0.299 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 43.40 | 0.00720 |
T S2 APARTMENT | 3060.35 | 3672.43 | 0.249 | 0.299 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 43.40 | 0.00720 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
G SW APARTMENT | 710.12 | 852.14 | 0.021 | 0.027 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
G NW APARTMENT | 710.04 | 852.05 | 0.021 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
OFFICE | 1733.63 | 2080.36 | 0.050 | 0.060 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.70 | 0.00513 |
G NE APARTMENT | 715.01 | 858.01 | 0.021 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
G N1 APARTMENT | 365.35 | 438.42 | 0.011 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
G N2 APARTMENT | 365.42 | 438.50 | 0.011 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
G S1 APARTMENT | 367.14 | 440.56 | 0.011 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
G S2 APARTMENT | 425.74 | 510.89 | 0.013 | 0.026 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M SW APARTMENT | 1271.32 | 1525.58 | 0.038 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M NW APARTMENT | 1272.78 | 1527.33 | 0.038 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M SE APARTMENT | 1284.15 | 1540.98 | 0.038 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M NE APARTMENT | 1285.60 | 1542.72 | 0.039 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M N1 APARTMENT | 433.40 | 520.08 | 0.013 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M N2 APARTMENT | 433.64 | 520.36 | 0.013 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M S1 APARTMENT | 433.03 | 519.63 | 0.013 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
M S2 APARTMENT | 433.26 | 519.92 | 0.013 | 0.052 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T SW APARTMENT | 1314.88 | 1577.85 | 0.039 | 0.047 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T NW APARTMENT | 1316.26 | 1579.51 | 0.039 | 0.047 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T SE APARTMENT | 1321.79 | 1586.15 | 0.040 | 0.048 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T NE APARTMENT | 1323.18 | 1587.82 | 0.040 | 0.048 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T N1 APARTMENT | 882.63 | 1059.16 | 0.026 | 0.032 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T N2 APARTMENT | 882.76 | 1059.31 | 0.026 | 0.032 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T S1 APARTMENT | 880.95 | 1057.14 | 0.026 | 0.032 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
T S2 APARTMENT | 881.07 | 1057.29 | 0.026 | 0.032 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 3.70 | 0.00513 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SPLIT GSW | 0.26 | 0.26 | 0.03 | 0.03 |
SPLIT GNW | 0.25 | 0.25 | 0.03 | 0.03 |
SPLIT OFFICE | 0.56 | 0.56 | 0.06 | 0.06 |
SPLIT GNE | 0.22 | 0.22 | 0.03 | 0.03 |
SPLIT GN1 | 0.15 | 0.15 | 0.03 | 0.03 |
SPLIT GN2 | 0.15 | 0.15 | 0.03 | 0.03 |
SPLIT GS1 | 0.16 | 0.16 | 0.03 | 0.03 |
SPLIT GS2 | 0.16 | 0.16 | 0.03 | 0.03 |
SPLIT MSW | 0.61 | 0.61 | 0.05 | 0.05 |
SPLIT MNW | 0.60 | 0.60 | 0.05 | 0.05 |
SPLIT MSE | 0.55 | 0.55 | 0.05 | 0.05 |
SPLIT MNE | 0.52 | 0.52 | 0.05 | 0.05 |
SPLIT MN1 | 0.36 | 0.36 | 0.05 | 0.05 |
SPLIT MN2 | 0.36 | 0.36 | 0.05 | 0.05 |
SPLIT MS1 | 0.39 | 0.39 | 0.05 | 0.05 |
SPLIT MS2 | 0.39 | 0.39 | 0.05 | 0.05 |
SPLIT TSW | 0.42 | 0.42 | 0.05 | 0.05 |
SPLIT TNW | 0.40 | 0.40 | 0.05 | 0.05 |
SPLIT TSE | 0.38 | 0.38 | 0.05 | 0.05 |
SPLIT TNE | 0.35 | 0.35 | 0.05 | 0.05 |
SPLIT TN1 | 0.27 | 0.27 | 0.03 | 0.03 |
SPLIT TN2 | 0.27 | 0.27 | 0.03 | 0.03 |
SPLIT TS1 | 0.30 | 0.30 | 0.03 | 0.03 |
SPLIT TS2 | 0.30 | 0.30 | 0.03 | 0.03 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
G SW APARTMENT | 2618.75 | 4334.50 | 41.50 |
G NW APARTMENT | 2410.75 | 4928.25 | 48.00 |
OFFICE | 773.75 | 960.75 | 0.00 |
G NE APARTMENT | 2394.50 | 4928.25 | 56.25 |
G N1 APARTMENT | 2096.00 | 5278.50 | 59.50 |
G N2 APARTMENT | 2094.50 | 5277.75 | 59.75 |
G S1 APARTMENT | 2259.75 | 4835.75 | 45.75 |
G S2 APARTMENT | 2378.75 | 4702.25 | 37.75 |
M SW APARTMENT | 3640.50 | 1103.75 | 3.50 |
M NW APARTMENT | 3153.75 | 2250.50 | 3.75 |
M SE APARTMENT | 3672.75 | 1134.00 | 6.25 |
M NE APARTMENT | 3186.00 | 2250.75 | 8.50 |
M N1 APARTMENT | 2729.75 | 2186.50 | 8.25 |
M N2 APARTMENT | 2730.25 | 2193.75 | 8.25 |
M S1 APARTMENT | 3239.50 | 704.25 | 3.00 |
M S2 APARTMENT | 3241.50 | 710.75 | 3.00 |
T SW APARTMENT | 4268.75 | 2232.50 | 12.00 |
T NW APARTMENT | 3792.25 | 2910.75 | 37.00 |
T SE APARTMENT | 4293.25 | 2204.50 | 12.75 |
T NE APARTMENT | 3835.25 | 2889.00 | 43.75 |
T N1 APARTMENT | 3426.00 | 2930.50 | 12.25 |
T N2 APARTMENT | 3426.25 | 2929.25 | 12.50 |
T S1 APARTMENT | 3985.25 | 2083.75 | 8.25 |
T S2 APARTMENT | 3986.00 | 2086.75 | 8.25 |
T CORRIDOR | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 |
Facility | 4758.50 | 5283.75 | 97.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
G SW APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
G NW APARTMENT | 0.00 | 3.75 | 0.00 | 3.75 |
OFFICE | 0.00 | 29.75 | 0.00 | 0.00 |
G NE APARTMENT | 0.25 | 0.50 | 0.25 | 0.50 |
G N1 APARTMENT | 4.25 | 2.25 | 4.25 | 2.25 |
G N2 APARTMENT | 5.25 | 2.00 | 5.25 | 2.00 |
G S1 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
G S2 APARTMENT | 2.25 | 0.00 | 2.25 | 0.00 |
M SW APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 0.00 | 0.75 | 0.00 | 0.75 |
M SE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
M N2 APARTMENT | 0.00 | 1.00 | 0.00 | 1.00 |
M S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 0.00 | 1.25 | 0.00 | 1.25 |
T NW APARTMENT | 0.00 | 2.00 | 0.00 | 2.00 |
T SE APARTMENT | 0.00 | 0.25 | 0.00 | 0.25 |
T NE APARTMENT | 0.00 | 0.50 | 0.00 | 0.50 |
T N1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 11.25 | 39.50 | 11.25 | 9.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.368 | 0.119 | 0.000 | 0.068 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.119 | 0.000 | 0.065 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.521 | 0.136 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.119 | 0.000 | 0.064 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.072 | 0.000 | 0.063 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.072 | 0.000 | 0.063 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.072 | 0.000 | 0.067 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.072 | 0.000 | 0.067 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.171 | 0.000 | 0.078 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.171 | 0.000 | 0.077 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.171 | 0.000 | 0.078 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.171 | 0.000 | 0.077 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.103 | 0.000 | 0.077 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.103 | 0.000 | 0.077 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.103 | 0.000 | 0.078 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.356 | 0.103 | 0.000 | 0.078 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.227 | 0.000 | 0.089 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.227 | 0.000 | 0.087 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.227 | 0.000 | 0.089 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.227 | 0.000 | 0.088 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.137 | 0.000 | 0.087 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.137 | 0.000 | 0.087 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.137 | 0.000 | 0.089 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.355 | 0.137 | 0.000 | 0.089 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
G SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.357 | 0.000 | 0.000 | 0.000 |
G NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
OFFICE | 0.94 | 1.00 | 268.97 | 0.507 | 0.000 | 0.000 | 0.000 |
G NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
G N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
G N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
G S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
G S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
M SW APARTMENT | 1.71 | 2.50 | 268.97 | 1.386 | 0.000 | 0.000 | 0.000 |
M NW APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
M SE APARTMENT | 1.71 | 2.50 | 268.97 | 1.385 | 0.000 | 0.000 | 0.000 |
M NE APARTMENT | 1.71 | 2.50 | 268.97 | 1.381 | 0.000 | 0.000 | 0.000 |
M N1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.384 | 0.000 | 0.000 | 0.000 |
M N2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.384 | 0.000 | 0.000 | 0.000 |
M S1 APARTMENT | 1.71 | 2.50 | 268.97 | 1.389 | 0.000 | 0.000 | 0.000 |
M S2 APARTMENT | 1.71 | 2.50 | 268.97 | 1.389 | 0.000 | 0.000 | 0.000 |
T SW APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T NW APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T SE APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T NE APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T N1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T N2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T S1 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
T S2 APARTMENT | 1.71 | 2.50 | 268.97 | 0.345 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Surfaces by ClassTotal | Outdoors | |
Wall | 126 | 42 |
Floor | 27 | 9 |
Roof | 27 | 9 |
Internal Mass | 24 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 39 | 39 |
Door | 0 | 0 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 24 |
Conditioned Zones | 24 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1385 |
Defaulted Fields | 439 |
Fields with Defaults | 3704 |
Autosized Fields | 336 |
Autosizable Fields | 454 |
Autocalculated Fields | 247 |
Autocalculatable Fields | 424 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum | Electricity Maximum Value [W] | Timestamp of Maximum | |
Electricity:Facility | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
Electricity:Building | 636.11 | 10559.61 | 01-JAN-03:15 | 31610.87 | 01-JAN-18:15 |
Electricity:Zone:G SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity | 118.46 | 2466.75 | 01-JAN-00:15 | 5482.59 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:G SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
GeneralLights:InteriorLights:Electricity | 96.36 | 2205.67 | 01-JAN-00:15 | 4426.44 | 01-JAN-19:15 |
Electricity:Zone:G NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:OFFICE | 35.93 | 610.39 | 01-JAN-00:15 | 2669.36 | 02-JAN-08:15 |
InteriorLights:Electricity:Zone:OFFICE | 26.45 | 416.15 | 01-JAN-00:15 | 2080.74 | 02-JAN-08:15 |
Electricity:Zone:G NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:G S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:M SW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NW APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NW APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M SE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M SE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M NE APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M NE APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M N2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M N2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S1 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S1 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:M S2 APARTMENT | 26.60 | 460.32 | 01-JAN-03:15 | 1352.36 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:M S2 APARTMENT | 2.17 | 12.97 | 01-JAN-00:15 | 207.54 | 01-JAN-19:15 |
Electricity:Zone:T SW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NW APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NW APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T SE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T SE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T NE APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T NE APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T N2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T N2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S1 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S1 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:T S2 APARTMENT | 13.30 | 230.16 | 01-JAN-03:15 | 676.18 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:T S2 APARTMENT | 1.09 | 6.49 | 01-JAN-00:15 | 103.77 | 01-JAN-19:15 |
Electricity:Zone:G CORRIDOR | 144.16 | 1427.03 | 01-JAN-00:15 | 8651.76 | 01-JAN-07:15 |
InteriorLights:Electricity:Zone:G CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:M CORRIDOR | 29.16 | 924.77 | 01-JAN-00:15 | 924.77 | 01-JAN-00:15 |
Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
InteriorLights:Electricity:Zone:T CORRIDOR | 14.58 | 462.39 | 01-JAN-00:15 | 462.39 | 01-JAN-00:15 |
GeneralLights-plugin:InteriorLights:Electricity | 22.11 | 261.08 | 01-JAN-00:15 | 1411.40 | 02-JAN-16:15 |
InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
MiscPlug:InteriorEquipment:Electricity | 517.65 | 8092.87 | 01-JAN-03:15 | 26730.99 | 02-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:OFFICE | 9.48 | 194.25 | 01-JAN-00:15 | 588.62 | 02-JAN-08:15 |
InteriorEquipment:Electricity:Zone:G NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NW APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M SE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M NE APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M N2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S1 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:M S2 APARTMENT | 24.43 | 447.35 | 01-JAN-03:15 | 1177.25 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NW APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T SE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T NE APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T N2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S1 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:T S2 APARTMENT | 12.21 | 223.68 | 01-JAN-03:15 | 588.62 | 01-JAN-17:15 |
InteriorEquipment:Electricity:Zone:G CORRIDOR | 129.57 | 964.65 | 01-JAN-00:15 | 8189.37 | 01-JAN-07:15 |
Electricity:Plant | 310.06 | 0.00 | 01-JAN-00:15 | 31948.81 | 01-JAN-08:45 |
WaterSystems:Electricity | 310.06 | 0.00 | 01-JAN-00:15 | 31948.81 | 01-JAN-08:45 |
Water Heater:WaterSystems:Electricity | 310.06 | 0.00 | 01-JAN-00:15 | 31948.81 | 01-JAN-08:45 |
Fans:Electricity | 306.50 | 9718.96 | 01-JAN-07:15 | 9718.96 | 01-JAN-00:15 |
Fans:Electricity:Zone:G SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:G S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NW APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T SE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T NE APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T N2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:T S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
ElectricityPurchased:Plant | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
Cogeneration:ElectricityPurchased | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
ElectricityNet:Plant | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
Cogeneration:ElectricityNet | 1638.52 | 22831.58 | 01-JAN-03:15 | 93773.47 | 07-AUG-17:15 |
ExteriorLights:Electricity | 40.09 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
General:ExteriorLights:Electricity | 40.09 | 0.00 | 01-JAN-07:45 | 2553.00 | 01-JAN-00:15 |
Electricity:HVAC | 652.26 | 9718.96 | 01-JAN-07:15 | 47800.03 | 24-JUL-16:00 |
General:Fans:Electricity | 306.50 | 9718.96 | 01-JAN-07:15 | 9718.96 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 345.76 | 0.00 | 01-JAN-01:45 | 38081.07 | 24-JUL-16:00 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum | Gas Maximum Value [W] | Timestamp of Maximum | |
Gas:Facility | 12.39 | 0.00 | 01-JAN-10:00 | 22335.71 | 10-FEB-07:00 |
Gas:HVAC | 12.39 | 0.00 | 01-JAN-10:00 | 22335.71 | 10-FEB-07:00 |
Heating:Gas | 12.39 | 0.00 | 01-JAN-10:00 | 22335.71 | 10-FEB-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum | Cooling Maximum Value [W] | Timestamp of Maximum | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
Water:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
Water:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
Water Heater:WaterSystems:Water | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
MainsWater:Facility | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
MainsWater:Plant | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
Water Heater:WaterSystems:MainsWater | 1874.72 | 0.00 | 01-JAN-02:15 | 0.00 | 01-JAN-07:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum | Maximum Value [kg/s] | Timestamp of Maximum | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum | Maximum Value [m3/s] | Timestamp of Maximum | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum | Maximum Value [L] | Timestamp of Maximum | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum | Maximum Value [W] | Timestamp of Maximum | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 2194.89 | 2397.17 | 09-MAR-00:15 | 215979.10 | 24-JUL-16:00 |
EnergyTransfer:Building | 929.52 | 2067.55 | 30-MAR-06:00 | 90106.48 | 24-JUL-16:00 |
EnergyTransfer:Zone:G SW APARTMENT | 23.02 | 0.00 | 05-FEB-20:15 | 3123.52 | 29-SEP-15:15 |
Heating:EnergyTransfer | 20.07 | 0.00 | 30-JAN-20:00 | 13463.17 | 07-MAR-03:00 |
Heating:EnergyTransfer:Zone:G SW APARTMENT | 0.59 | 0.00 | 01-JAN-00:30 | 730.93 | 07-MAR-03:00 |
Cooling:EnergyTransfer | 909.45 | 96.20 | 29-DEC-12:00 | 90106.48 | 24-JUL-16:00 |
Cooling:EnergyTransfer:Zone:G SW APARTMENT | 22.43 | 0.00 | 01-JAN-00:15 | 3123.52 | 29-SEP-15:15 |
EnergyTransfer:Zone:G NW APARTMENT | 18.90 | 0.01 | 05-MAR-10:45 | 3081.93 | 08-JUL-17:30 |
Heating:EnergyTransfer:Zone:G NW APARTMENT | 1.42 | 0.00 | 01-JAN-09:00 | 738.71 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G NW APARTMENT | 17.48 | 0.00 | 01-JAN-00:15 | 3081.93 | 08-JUL-17:30 |
EnergyTransfer:Zone:OFFICE | 39.41 | 0.02 | 13-DEC-20:00 | 5435.09 | 09-JUL-08:30 |
Heating:EnergyTransfer:Zone:OFFICE | 7.06 | 0.00 | 01-JAN-03:30 | 1043.01 | 14-MAY-19:00 |
Cooling:EnergyTransfer:Zone:OFFICE | 32.35 | 0.00 | 01-JAN-00:15 | 5435.09 | 09-JUL-08:30 |
EnergyTransfer:Zone:G NE APARTMENT | 18.49 | 0.00 | 04-JAN-00:15 | 2412.48 | 16-JUL-18:15 |
Heating:EnergyTransfer:Zone:G NE APARTMENT | 1.16 | 0.00 | 01-JAN-08:00 | 743.41 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G NE APARTMENT | 17.32 | 0.00 | 01-JAN-00:15 | 2412.48 | 16-JUL-18:15 |
EnergyTransfer:Zone:G N1 APARTMENT | 12.53 | 0.01 | 16-JAN-12:00 | 1794.75 | 08-JUL-17:45 |
Heating:EnergyTransfer:Zone:G N1 APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 346.22 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G N1 APARTMENT | 12.05 | 0.00 | 01-JAN-07:00 | 1794.75 | 08-JUL-17:45 |
EnergyTransfer:Zone:G N2 APARTMENT | 12.54 | 0.01 | 29-NOV-10:30 | 1786.04 | 08-JUL-17:45 |
Heating:EnergyTransfer:Zone:G N2 APARTMENT | 0.48 | 0.00 | 01-JAN-00:15 | 346.87 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G N2 APARTMENT | 12.06 | 0.00 | 01-JAN-07:00 | 1786.04 | 08-JUL-17:45 |
EnergyTransfer:Zone:G S1 APARTMENT | 17.01 | 0.01 | 04-MAR-22:00 | 2105.55 | 29-SEP-13:30 |
Heating:EnergyTransfer:Zone:G S1 APARTMENT | 0.09 | 0.00 | 01-JAN-00:15 | 333.94 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G S1 APARTMENT | 16.92 | 0.00 | 01-JAN-17:15 | 2105.55 | 29-SEP-13:30 |
EnergyTransfer:Zone:G S2 APARTMENT | 18.00 | 0.02 | 13-APR-03:30 | 2212.21 | 29-SEP-13:15 |
Heating:EnergyTransfer:Zone:G S2 APARTMENT | 0.07 | 0.00 | 01-JAN-00:15 | 327.17 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:G S2 APARTMENT | 17.93 | 0.00 | 01-JAN-17:30 | 2212.21 | 29-SEP-13:15 |
EnergyTransfer:Zone:M SW APARTMENT | 76.46 | 0.28 | 04-DEC-12:30 | 7283.85 | 29-SEP-15:15 |
Heating:EnergyTransfer:Zone:M SW APARTMENT | 0.02 | 0.00 | 01-JAN-00:15 | 448.36 | 07-MAR-05:00 |
Cooling:EnergyTransfer:Zone:M SW APARTMENT | 76.44 | 0.00 | 02-JAN-00:15 | 7283.85 | 29-SEP-15:15 |
EnergyTransfer:Zone:M NW APARTMENT | 58.98 | 0.01 | 11-NOV-02:00 | 7203.50 | 08-JUL-17:30 |
Heating:EnergyTransfer:Zone:M NW APARTMENT | 0.28 | 0.00 | 01-JAN-00:30 | 530.35 | 07-MAR-05:00 |
Cooling:EnergyTransfer:Zone:M NW APARTMENT | 58.71 | 0.00 | 01-JAN-00:15 | 7203.50 | 08-JUL-17:30 |
EnergyTransfer:Zone:M SE APARTMENT | 76.43 | 0.18 | 14-NOV-07:00 | 6367.34 | 02-SEP-11:30 |
Heating:EnergyTransfer:Zone:M SE APARTMENT | 0.01 | 0.00 | 01-JAN-00:15 | 506.92 | 07-MAR-05:00 |
Cooling:EnergyTransfer:Zone:M SE APARTMENT | 76.42 | 0.00 | 02-JAN-19:00 | 6367.34 | 02-SEP-11:30 |
EnergyTransfer:Zone:M NE APARTMENT | 59.00 | 0.10 | 23-DEC-14:15 | 5932.68 | 09-JUL-17:00 |
Heating:EnergyTransfer:Zone:M NE APARTMENT | 0.21 | 0.00 | 01-JAN-00:15 | 615.59 | 10-FEB-07:00 |
Cooling:EnergyTransfer:Zone:M NE APARTMENT | 58.79 | 0.00 | 01-JAN-11:30 | 5932.68 | 09-JUL-17:00 |
EnergyTransfer:Zone:M N1 APARTMENT | 45.90 | 0.42 | 06-DEC-12:30 | 4275.85 | 08-JUL-18:00 |
Heating:EnergyTransfer:Zone:M N1 APARTMENT | 0.02 | 0.00 | 01-JAN-00:15 | 343.91 | 19-DEC-15:00 |
Cooling:EnergyTransfer:Zone:M N1 APARTMENT | 45.88 | 0.00 | 02-JAN-10:45 | 4275.85 | 08-JUL-18:00 |
EnergyTransfer:Zone:M N2 APARTMENT | 45.90 | 0.03 | 02-JAN-12:15 | 4261.96 | 08-JUL-18:00 |
Heating:EnergyTransfer:Zone:M N2 APARTMENT | 0.02 | 0.00 | 01-JAN-00:15 | 343.65 | 19-DEC-15:00 |
Cooling:EnergyTransfer:Zone:M N2 APARTMENT | 45.88 | 0.00 | 02-JAN-10:45 | 4261.96 | 08-JUL-18:00 |
EnergyTransfer:Zone:M S1 APARTMENT | 64.18 | 46.59 | 10-APR-07:15 | 5234.47 | 14-OCT-13:45 |
Heating:EnergyTransfer:Zone:M S1 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S1 APARTMENT | 64.18 | 46.59 | 10-APR-07:15 | 5234.47 | 14-OCT-13:45 |
EnergyTransfer:Zone:M S2 APARTMENT | 64.18 | 45.88 | 10-APR-07:15 | 5240.19 | 14-OCT-13:45 |
Heating:EnergyTransfer:Zone:M S2 APARTMENT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M S2 APARTMENT | 64.18 | 45.88 | 10-APR-07:15 | 5240.19 | 14-OCT-13:45 |
EnergyTransfer:Zone:T SW APARTMENT | 42.69 | 0.12 | 10-JAN-01:00 | 4900.24 | 16-JUL-17:00 |
Heating:EnergyTransfer:Zone:T SW APARTMENT | 1.35 | 0.00 | 01-JAN-08:45 | 1236.83 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:T SW APARTMENT | 41.34 | 0.00 | 01-JAN-00:15 | 4900.24 | 16-JUL-17:00 |
EnergyTransfer:Zone:T NW APARTMENT | 35.87 | 0.01 | 20-JAN-15:30 | 4861.33 | 16-JUL-17:15 |
Heating:EnergyTransfer:Zone:T NW APARTMENT | 2.16 | 0.00 | 01-JAN-14:15 | 1243.14 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:T NW APARTMENT | 33.70 | 0.00 | 01-JAN-00:15 | 4861.33 | 16-JUL-17:15 |
EnergyTransfer:Zone:T SE APARTMENT | 42.26 | 0.27 | 10-DEC-19:30 | 4183.24 | 16-JUL-13:45 |
Heating:EnergyTransfer:Zone:T SE APARTMENT | 1.16 | 0.00 | 01-JAN-08:00 | 1239.59 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:T SE APARTMENT | 41.10 | 0.00 | 01-JAN-00:15 | 4183.24 | 16-JUL-13:45 |
EnergyTransfer:Zone:T NE APARTMENT | 35.10 | 0.01 | 08-NOV-09:30 | 4100.62 | 16-JUL-17:30 |
Heating:EnergyTransfer:Zone:T NE APARTMENT | 1.77 | 0.00 | 01-JAN-08:30 | 1272.48 | 31-JAN-07:00 |
Cooling:EnergyTransfer:Zone:T NE APARTMENT | 33.33 | 0.00 | 01-JAN-00:15 | 4100.62 | 16-JUL-17:30 |
EnergyTransfer:Zone:T N1 APARTMENT | 26.84 | 0.00 | 03-DEC-01:45 | 3229.90 | 16-JUL-17:30 |
Heating:EnergyTransfer:Zone:T N1 APARTMENT | 0.61 | 0.00 | 01-JAN-00:30 | 725.51 | 10-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T N1 APARTMENT | 26.23 | 0.00 | 01-JAN-00:15 | 3229.90 | 16-JUL-17:30 |
EnergyTransfer:Zone:T N2 APARTMENT | 26.85 | 0.00 | 23-FEB-02:15 | 3215.66 | 16-JUL-17:30 |
Heating:EnergyTransfer:Zone:T N2 APARTMENT | 0.61 | 0.00 | 01-JAN-00:30 | 727.11 | 10-FEB-07:00 |
Cooling:EnergyTransfer:Zone:T N2 APARTMENT | 26.24 | 0.00 | 01-JAN-00:15 | 3215.66 | 16-JUL-17:30 |
EnergyTransfer:Zone:T S1 APARTMENT | 34.49 | 0.00 | 29-JAN-02:00 | 3484.54 | 29-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S1 APARTMENT | 0.24 | 0.00 | 01-JAN-00:45 | 708.97 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:T S1 APARTMENT | 34.24 | 0.00 | 01-JAN-00:15 | 3484.54 | 29-SEP-14:15 |
EnergyTransfer:Zone:T S2 APARTMENT | 34.50 | 0.01 | 05-MAR-22:45 | 3485.72 | 29-SEP-14:15 |
Heating:EnergyTransfer:Zone:T S2 APARTMENT | 0.25 | 0.00 | 01-JAN-00:45 | 709.52 | 07-MAR-03:00 |
Cooling:EnergyTransfer:Zone:T S2 APARTMENT | 34.25 | 0.00 | 01-JAN-00:15 | 3485.72 | 29-SEP-14:15 |
EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:T CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:G CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:M CORRIDOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:HVAC | 1265.37 | 0.00 | 16-FEB-05:00 | 126039.68 | 10-AUG-15:30 |
HeatingCoils:EnergyTransfer | 9.91 | 0.00 | 01-JAN-10:00 | 17868.57 | 10-FEB-07:00 |
CoolingCoils:EnergyTransfer | 1255.46 | 0.00 | 01-JAN-01:45 | 126039.68 | 10-AUG-15:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Annual Building Sensible Heat Gain ComponentsHVAC Input Sensible Air Heating [GJ] | HVAC Input Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
G SW APARTMENT | 0.588 | -22.428 | 0.000 | 0.000 | 3.634 | 1.087 | 12.213 | 21.347 | 0.000 | 1.461 | 0.001 | 0.000 | -3.969 | 0.000 | -1.929 | -12.004 |
G NW APARTMENT | 1.424 | -17.479 | 0.000 | 0.000 | 3.670 | 1.087 | 12.213 | 13.188 | 0.000 | 1.460 | 0.000 | 0.000 | -4.043 | 0.000 | -1.753 | -9.766 |
OFFICE | 7.060 | -32.353 | 0.000 | 0.000 | 0.517 | 26.452 | 9.482 | 19.989 | 0.000 | 1.006 | 0.000 | 0.000 | -4.525 | 0.000 | -1.389 | -26.239 |
G NE APARTMENT | 1.164 | -17.323 | 0.000 | 0.000 | 3.679 | 1.087 | 12.213 | 12.804 | 0.000 | 1.460 | 0.000 | 0.000 | -3.747 | 0.000 | -1.746 | -9.591 |
G N1 APARTMENT | 0.481 | -12.052 | 0.000 | 0.000 | 3.685 | 1.087 | 12.213 | 5.361 | 0.000 | 0.892 | 0.000 | 0.000 | -2.435 | 0.000 | -1.244 | -7.988 |
G N2 APARTMENT | 0.480 | -12.056 | 0.000 | 0.000 | 3.685 | 1.087 | 12.213 | 5.360 | 0.000 | 0.892 | 0.000 | 0.000 | -2.433 | 0.000 | -1.244 | -7.985 |
G S1 APARTMENT | 0.087 | -16.918 | 0.000 | 0.000 | 3.634 | 1.087 | 12.213 | 13.611 | 0.000 | 0.892 | 0.000 | 0.000 | -2.387 | 0.000 | -1.463 | -10.756 |
G S2 APARTMENT | 0.074 | -17.930 | 0.000 | 0.000 | 3.630 | 1.087 | 12.213 | 13.591 | 0.000 | 0.892 | 0.000 | 0.000 | -2.400 | 0.000 | -1.471 | -9.686 |
M SW APARTMENT | 0.016 | -76.438 | 0.000 | 0.000 | 3.539 | 1.087 | 12.213 | 20.767 | 0.000 | 2.088 | 44.030 | 0.000 | -4.582 | 0.000 | -2.720 | 0.000 |
M NW APARTMENT | 0.276 | -58.705 | 0.000 | 0.000 | 3.563 | 1.087 | 12.213 | 12.720 | 0.000 | 2.087 | 34.151 | 0.000 | -4.737 | 0.000 | -2.655 | 0.000 |
M SE APARTMENT | 0.011 | -76.414 | 0.000 | 0.000 | 3.542 | 1.087 | 12.213 | 20.525 | 0.000 | 2.088 | 44.112 | 0.000 | -4.447 | 0.000 | -2.716 | 0.000 |
M NE APARTMENT | 0.210 | -58.787 | 0.000 | 0.000 | 3.571 | 1.087 | 12.213 | 12.277 | 0.000 | 2.087 | 34.368 | 0.000 | -4.385 | 0.000 | -2.641 | 0.000 |
M N1 APARTMENT | 0.018 | -45.878 | 0.000 | 0.000 | 3.553 | 1.087 | 12.213 | 5.086 | 0.000 | 1.272 | 27.561 | 0.000 | -2.948 | 0.000 | -1.964 | 0.000 |
M N2 APARTMENT | 0.018 | -45.878 | 0.000 | 0.000 | 3.554 | 1.087 | 12.213 | 5.086 | 0.000 | 1.272 | 27.558 | 0.000 | -2.946 | 0.000 | -1.963 | 0.000 |
M S1 APARTMENT | 0.000 | -64.184 | 0.000 | 0.000 | 3.529 | 1.087 | 12.213 | 13.234 | 0.000 | 1.273 | 37.640 | 0.000 | -2.776 | 0.000 | -2.015 | 0.000 |
M S2 APARTMENT | 0.000 | -64.180 | 0.000 | 0.000 | 3.529 | 1.087 | 12.213 | 13.234 | 0.000 | 1.273 | 37.636 | 0.000 | -2.776 | 0.000 | -2.015 | 0.000 |
T SW APARTMENT | 1.353 | -41.338 | 0.000 | 0.000 | 3.587 | 1.087 | 12.213 | 20.365 | 0.000 | 2.754 | 7.536 | 0.000 | -4.306 | 0.000 | -3.249 | -0.000 |
T NW APARTMENT | 2.163 | -33.705 | 0.000 | 0.000 | 3.609 | 1.087 | 12.213 | 12.419 | 0.000 | 2.752 | 7.030 | 0.000 | -4.426 | 0.000 | -3.142 | -0.000 |
T SE APARTMENT | 1.165 | -41.099 | 0.000 | 0.000 | 3.591 | 1.087 | 12.213 | 20.127 | 0.000 | 2.754 | 7.589 | 0.000 | -4.180 | 0.000 | -3.247 | -0.001 |
T NE APARTMENT | 1.771 | -33.332 | 0.000 | 0.000 | 3.618 | 1.087 | 12.213 | 12.020 | 0.000 | 2.752 | 7.130 | 0.000 | -4.122 | 0.000 | -3.137 | -0.000 |
T N1 APARTMENT | 0.606 | -26.231 | 0.000 | 0.000 | 3.607 | 1.087 | 12.213 | 4.973 | 0.000 | 1.679 | 7.044 | 0.000 | -2.724 | 0.000 | -2.254 | -0.001 |
T N2 APARTMENT | 0.613 | -26.240 | 0.000 | 0.000 | 3.607 | 1.087 | 12.213 | 4.972 | 0.000 | 1.679 | 7.046 | 0.000 | -2.722 | 0.000 | -2.255 | -0.000 |
T S1 APARTMENT | 0.243 | -34.243 | 0.000 | 0.000 | 3.576 | 1.087 | 12.213 | 13.000 | 0.000 | 1.681 | 7.425 | 0.000 | -2.623 | 0.000 | -2.358 | -0.000 |
T S2 APARTMENT | 0.246 | -34.254 | 0.000 | 0.000 | 3.576 | 1.087 | 12.213 | 12.999 | 0.000 | 1.681 | 7.433 | 0.000 | -2.622 | 0.000 | -2.358 | -0.000 |
T CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.495 | 0.000 | 0.297 | 0.000 | 0.000 | -0.439 | 0.000 | -0.464 | -14.471 |
G CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 6.479 | 1.538 | 0.000 | 7.430 | 0.001 | 0.000 | -0.989 | 0.000 | -9.464 | -19.575 |
M CORRIDOR | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14.582 | 0.000 | 0.520 | 0.000 | 0.248 | 0.000 | 0.000 | -0.500 | 0.000 | -0.395 | -14.454 |
Total Facility | 20.068 | -909.444 | 0.000 | 0.000 | 83.285 | 95.189 | 296.854 | 311.612 | 0.000 | 48.101 | 345.290 | 0.000 | -85.187 | 0.000 | -63.250 | -142.518 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 29-SEP-15:15 | 0.00 | -3123.31 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 3071.49 | 0.00 | 177.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -690.90 |
G NW APARTMENT | 08-JUL-17:23 | 0.00 | -3082.05 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2249.56 | 0.00 | 428.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.91 |
OFFICE | 20-AUG-06:01 | 0.00 | -8445.18 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 315.97 | 0.00 | 0.00 | 7452.91 | 0.00 | 0.00 | 0.00 | -34.16 | 0.00 |
G NE APARTMENT | 16-JUL-17:30 | 0.00 | -2413.85 | 0.00 | 0.00 | 140.82 | 87.56 | 588.62 | 1334.71 | 0.00 | 442.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -180.76 |
G N1 APARTMENT | 08-JUL-17:45 | 0.00 | -1794.74 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 814.88 | 0.00 | 248.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -86.89 |
G N2 APARTMENT | 08-JUL-17:45 | 0.00 | -1786.02 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 815.00 | 0.00 | 248.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95.73 |
G S1 APARTMENT | 29-SEP-13:30 | 0.00 | -2105.56 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2064.52 | 0.00 | 61.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -456.79 |
G S2 APARTMENT | 29-SEP-13:15 | 0.00 | -2212.27 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2097.33 | 0.00 | 60.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -382.37 |
M SW APARTMENT | 29-SEP-15:15 | 0.00 | -7283.35 | 0.00 | 0.00 | 48.90 | 45.40 | 470.90 | 3047.20 | 0.00 | 254.79 | 3416.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NW APARTMENT | 08-JUL-17:23 | 0.00 | -7203.96 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 2228.85 | 0.00 | 614.99 | 3542.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M SE APARTMENT | 02-SEP-11:30 | 0.00 | -6366.50 | 0.00 | 0.00 | 40.75 | 12.97 | 406.15 | 2451.52 | 0.00 | 388.71 | 3066.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M NE APARTMENT | 09-JUL-17:00 | 0.00 | -5931.62 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 960.21 | 0.00 | 837.12 | 3396.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N1 APARTMENT | 08-JUL-17:53 | 0.00 | -4276.23 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 826.97 | 0.00 | 343.24 | 2288.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M N2 APARTMENT | 08-JUL-17:53 | 0.00 | -4262.35 | 0.00 | 0.00 | 141.81 | 87.56 | 588.62 | 827.05 | 0.00 | 343.24 | 2274.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S1 APARTMENT | 14-OCT-13:45 | 0.00 | -5234.54 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2101.35 | 0.00 | 182.16 | 2514.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | 14-OCT-13:45 | 0.00 | -5240.25 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 2101.30 | 0.00 | 182.16 | 2520.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 16-JUL-17:00 | 0.00 | -4900.67 | 0.00 | 0.00 | 84.76 | 64.86 | 588.62 | 2214.85 | 0.00 | 878.27 | 1069.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NW APARTMENT | 16-JUL-17:15 | 0.00 | -4864.71 | 0.00 | 0.00 | 141.20 | 87.56 | 588.62 | 2297.55 | 0.00 | 858.64 | 891.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SE APARTMENT | 16-JUL-13:45 | 0.00 | -4183.21 | 0.00 | 0.00 | 40.75 | 12.97 | 382.60 | 1521.47 | 0.00 | 823.10 | 1402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T NE APARTMENT | 16-JUL-17:30 | 0.00 | -4101.47 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 1305.95 | 0.00 | 845.44 | 1132.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N1 APARTMENT | 16-JUL-17:30 | 0.00 | -3230.66 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 879.70 | 0.00 | 509.97 | 1023.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T N2 APARTMENT | 16-JUL-17:23 | 0.00 | -3215.92 | 0.00 | 0.00 | 141.80 | 87.56 | 588.62 | 879.89 | 0.00 | 509.97 | 1008.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S1 APARTMENT | 29-SEP-14:15 | 0.00 | -3484.39 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1855.94 | 0.00 | 143.58 | 1021.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T S2 APARTMENT | 29-SEP-14:15 | 0.00 | -3485.57 | 0.00 | 0.00 | 40.75 | 22.70 | 400.26 | 1855.90 | 0.00 | 143.58 | 1022.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-16:00 | 0.00 | -90110.30 | 0.00 | 0.00 | 1191.99 | 4512.09 | 11708.34 | 30097.94 | 0.00 | 13293.76 | 29306.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak | HVAC Input Sensible Air Heating [W] | HVAC Input Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
G SW APARTMENT | 12-FEB-07:01 | 1223.85 | 0.00 | 0.00 | 0.00 | 162.43 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -608.88 | 0.00 | -39.88 | -1162.28 |
G NW APARTMENT | 07-MAR-03:00 | 738.69 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -887.51 | 0.00 | -221.55 | -55.35 |
OFFICE | 07-FEB-07:01 | 2482.39 | 0.00 | 0.00 | 0.00 | 0.00 | 416.15 | 294.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -725.66 | 0.00 | -263.94 | -2203.25 |
G NE APARTMENT | 07-MAR-03:00 | 743.38 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -887.29 | 0.00 | -221.55 | -60.26 |
G N1 APARTMENT | 03-APR-07:01 | 694.43 | 0.00 | 0.00 | 0.00 | 74.70 | 19.46 | 388.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -311.36 | 0.00 | -109.43 | -756.28 |
G N2 APARTMENT | 11-DEC-07:01 | 1144.30 | 0.00 | 0.00 | 0.00 | 162.94 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -296.54 | 0.00 | -120.56 | -1314.90 |
G S1 APARTMENT | 22-JAN-07:01 | 1060.61 | 0.00 | 0.00 | 0.00 | 163.40 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -425.26 | 0.00 | -187.97 | -1035.54 |
G S2 APARTMENT | 24-JAN-07:02 | 537.38 | 0.00 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -449.32 | 0.00 | -142.56 | -531.48 |
M SW APARTMENT | 07-MAR-05:00 | 448.35 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 322.63 | 0.00 | -928.43 | 0.00 | -275.36 | 0.00 |
M NW APARTMENT | 16-DEC-07:11 | 626.84 | 0.00 | 0.00 | 0.00 | 161.22 | 42.16 | 382.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -753.37 | 0.00 | -189.09 | -270.36 |
M SE APARTMENT | 07-MAR-05:00 | 506.92 | 0.00 | 0.00 | 0.00 | 189.67 | 19.46 | 223.68 | 0.00 | 0.00 | 0.00 | 262.65 | 0.00 | -927.01 | 0.00 | -275.36 | 0.00 |
M NE APARTMENT | 10-FEB-07:00 | 615.57 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -778.57 | 0.00 | -284.15 | -105.77 |
M N1 APARTMENT | 19-DEC-15:00 | 343.89 | 0.00 | 0.00 | 0.00 | 41.27 | 12.97 | 382.60 | 100.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50.06 | -831.52 |
M N2 APARTMENT | 19-DEC-15:00 | 343.63 | 0.00 | 0.00 | 0.00 | 41.29 | 12.97 | 382.60 | 100.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49.71 | -831.75 |
M S1 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M S2 APARTMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
T SW APARTMENT | 07-MAR-03:00 | 1236.80 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -879.24 | 0.00 | -422.73 | -360.55 |
T NW APARTMENT | 07-MAR-03:00 | 1243.10 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.99 | 0.00 | -422.73 | -369.10 |
T SE APARTMENT | 07-MAR-03:00 | 1239.55 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -879.17 | 0.00 | -422.73 | -363.37 |
T NE APARTMENT | 31-JAN-07:00 | 1272.50 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -745.24 | 0.00 | -451.28 | -628.91 |
T N1 APARTMENT | 10-FEB-07:00 | 725.49 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -457.63 | 0.00 | -227.18 | -593.61 |
T N2 APARTMENT | 10-FEB-07:00 | 727.10 | 0.00 | 0.00 | 0.00 | 189.67 | 45.40 | 317.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -457.59 | 0.00 | -227.18 | -595.25 |
T S1 APARTMENT | 07-MAR-03:00 | 708.95 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -536.61 | 0.00 | -254.99 | -343.07 |
T S2 APARTMENT | 07-MAR-03:00 | 709.50 | 0.00 | 0.00 | 0.00 | 189.67 | 6.49 | 229.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -536.59 | 0.00 | -254.99 | -343.64 |
T CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
G CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
M CORRIDOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-MAR-03:00 | 11434.28 | 0.00 | 0.00 | 0.00 | 4338.32 | 1952.47 | 5522.42 | 0.00 | 0.00 | 0.00 | 978.75 | 0.00 | -17855.82 | 0.00 | -6370.44 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | |
None |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
None |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Sec1.1A-General InformationData | |
Weather File | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
HDD and CDD data source | Weather File Stat |
Total gross floor area [m2] | 3134.61 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
G SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
OFFICE | 88.25 | 88.25 | 0.00 | 43.32 |
G NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
G S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
M S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NW APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T SE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T NE APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T N2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S1 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T S2 APARTMENT | 88.25 | 88.25 | 0.00 | 168.00 |
T CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
G CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
M CORRIDOR | 77.66 | 0.00 | 77.66 | 0.00 |
Totals | 3134.61 | 2823.98 | 310.64 |
Data | |
Number of hours heating loads not met | 11.25 |
Number of hours cooling loads not met | 9.75 |
Number of hours not met | 21.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Energy Use [GJ] | Additional Demand [W] | |
Interior Lighting | 118.46 | 4979.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 12.39 | 22335.71 | 0.00 | 0.00 |
Space Cooling | 345.76 | 33445.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 306.50 | 9718.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 310.06 | 18998.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 517.65 | 26630.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting (process) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 1638.52 | 12.39 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 517.65 | 1638.52 |
Natural Gas | 0.00 | 12.39 |
Additional | 0.00 | 0.00 |
Total | 517.65 | 1650.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting | 37.79 |
Space Heating | 0.00 |
Space Cooling | 110.30 |
Fans-Interior | 97.78 |
Service Water Heating | 98.92 |
Receptacle Equipment | 165.14 |
Miscellaneous | 12.79 |
Subtotal | 522.72 |
Natural Gas [MJ/m2] | |
Space Heating | 3.95 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 3.95 |
Additional [MJ/m2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 7.18 |
Space Heating | 0.75 |
Space Cooling | 20.94 |
Fans-Interior | 18.57 |
Service Water Heating | 18.78 |
Receptacle Equipment | 31.36 |
Miscellaneous | 2.43 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
AirTerminal:SingleDuct:UncontrolledMaximum Air Flow Rate [m3/s] | |
G SW APARTMENT DIRECT AIR | 0.256697 |
G NW APARTMENT DIRECT AIR | 0.253320 |
OFFICE DIRECT AIR | 0.560566 |
G NE APARTMENT DIRECT AIR | 0.215907 |
G N1 APARTMENT DIRECT AIR | 0.151250 |
G N2 APARTMENT DIRECT AIR | 0.150566 |
G S1 APARTMENT DIRECT AIR | 0.159626 |
G S2 APARTMENT DIRECT AIR | 0.162308 |
M SW APARTMENT DIRECT AIR | 0.608051 |
M NW APARTMENT DIRECT AIR | 0.598823 |
M SE APARTMENT DIRECT AIR | 0.549780 |
M NE APARTMENT DIRECT AIR | 0.519148 |
M N1 APARTMENT DIRECT AIR | 0.361368 |
M N2 APARTMENT DIRECT AIR | 0.360303 |
M S1 APARTMENT DIRECT AIR | 0.385569 |
M S2 APARTMENT DIRECT AIR | 0.386430 |
T SW APARTMENT DIRECT AIR | 0.416878 |
T NW APARTMENT DIRECT AIR | 0.404307 |
T SE APARTMENT DIRECT AIR | 0.381286 |
T NE APARTMENT DIRECT AIR | 0.351094 |
T N1 APARTMENT DIRECT AIR | 0.270516 |
T N2 APARTMENT DIRECT AIR | 0.270421 |
T S1 APARTMENT DIRECT AIR | 0.298836 |
T S2 APARTMENT DIRECT AIR | 0.299309 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW MAIN BRANCH | 0.256697 |
SPLIT GNW MAIN BRANCH | 0.253320 |
SPLIT OFFICE MAIN BRANCH | 0.560566 |
SPLIT GNE MAIN BRANCH | 0.215907 |
SPLIT GN1 MAIN BRANCH | 0.151250 |
SPLIT GN2 MAIN BRANCH | 0.150566 |
SPLIT GS1 MAIN BRANCH | 0.159626 |
SPLIT GS2 MAIN BRANCH | 0.162308 |
SPLIT MSW MAIN BRANCH | 0.608051 |
SPLIT MNW MAIN BRANCH | 0.598823 |
SPLIT MSE MAIN BRANCH | 0.549780 |
SPLIT MNE MAIN BRANCH | 0.519148 |
SPLIT MN1 MAIN BRANCH | 0.361368 |
SPLIT MN2 MAIN BRANCH | 0.360303 |
SPLIT MS1 MAIN BRANCH | 0.385569 |
SPLIT MS2 MAIN BRANCH | 0.386430 |
SPLIT TSW MAIN BRANCH | 0.416878 |
SPLIT TNW MAIN BRANCH | 0.404307 |
SPLIT TSE MAIN BRANCH | 0.381286 |
SPLIT TNE MAIN BRANCH | 0.351094 |
SPLIT TN1 MAIN BRANCH | 0.270516 |
SPLIT TN2 MAIN BRANCH | 0.270421 |
SPLIT TS1 MAIN BRANCH | 0.298836 |
SPLIT TS2 MAIN BRANCH | 0.299309 |
Design Supply Air Flow Rate [m3/s] | |
SPLIT GSW | 0.256697 |
SPLIT GNW | 0.253320 |
SPLIT OFFICE | 0.560566 |
SPLIT GNE | 0.215907 |
SPLIT GN1 | 0.151250 |
SPLIT GN2 | 0.150566 |
SPLIT GS1 | 0.159626 |
SPLIT GS2 | 0.162308 |
SPLIT MSW | 0.608051 |
SPLIT MNW | 0.598823 |
SPLIT MSE | 0.549780 |
SPLIT MNE | 0.519148 |
SPLIT MN1 | 0.361368 |
SPLIT MN2 | 0.360303 |
SPLIT MS1 | 0.385569 |
SPLIT MS2 | 0.386430 |
SPLIT TSW | 0.416878 |
SPLIT TNW | 0.404307 |
SPLIT TSE | 0.381286 |
SPLIT TNE | 0.351094 |
SPLIT TN1 | 0.270516 |
SPLIT TN2 | 0.270421 |
SPLIT TS1 | 0.298836 |
SPLIT TS2 | 0.299309 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SPLIT GSW OA CONTROLLER | 0.256697 | 0.026898 |
SPLIT GNW OA CONTROLLER | 0.253320 | 0.025953 |
SPLIT OFFICE OA CONTROLLER | 0.560566 | 0.038104 |
SPLIT GNE OA CONTROLLER | 0.215907 | 0.025953 |
SPLIT GN1 OA CONTROLLER | 0.151250 | 0.025953 |
SPLIT GN2 OA CONTROLLER | 0.150566 | 0.025953 |
SPLIT GS1 OA CONTROLLER | 0.159626 | 0.025953 |
SPLIT GS2 OA CONTROLLER | 0.162308 | 0.025953 |
SPLIT MSW OA CONTROLLER | 0.608051 | 0.051906 |
SPLIT MNW OA CONTROLLER | 0.598823 | 0.051906 |
SPLIT MSE OA CONTROLLER | 0.549780 | 0.051906 |
SPLIT MNE OA CONTROLLER | 0.519148 | 0.051906 |
SPLIT MN1 OA CONTROLLER | 0.361368 | 0.051906 |
SPLIT MN2 OA CONTROLLER | 0.360303 | 0.051906 |
SPLIT MS1 OA CONTROLLER | 0.385569 | 0.051906 |
SPLIT MS2 OA CONTROLLER | 0.386430 | 0.051906 |
SPLIT TSW OA CONTROLLER | 0.416878 | 0.025953 |
SPLIT TNW OA CONTROLLER | 0.404307 | 0.025953 |
SPLIT TSE OA CONTROLLER | 0.381286 | 0.025953 |
SPLIT TNE OA CONTROLLER | 0.351094 | 0.025953 |
SPLIT TN1 OA CONTROLLER | 0.270516 | 0.025953 |
SPLIT TN2 OA CONTROLLER | 0.270421 | 0.025953 |
SPLIT TS1 OA CONTROLLER | 0.298836 | 0.025953 |
SPLIT TS2 OA CONTROLLER | 0.299309 | 0.025953 |
Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | Rated Sensible Heat Ratio | |
SPLIT GSW COOLING COIL | 0.256697 | 4908.30 | 0.749289 |
SPLIT GNW COOLING COIL | 0.253320 | 4706.32 | 0.758582 |
SPLIT OFFICE COOLING COIL | 0.560566 | 9279.36 | 0.798655 |
SPLIT GNE COOLING COIL | 0.215907 | 4003.88 | 0.759184 |
SPLIT GN1 COOLING COIL | 0.151250 | 2905.22 | 0.747847 |
SPLIT GN2 COOLING COIL | 0.150566 | 2893.68 | 0.747671 |
SPLIT GS1 COOLING COIL | 0.159626 | 3294.66 | 0.725867 |
SPLIT GS2 COOLING COIL | 0.162308 | 3342.35 | 0.726543 |
SPLIT MSW COOLING COIL | 0.608051 | 11351.41 | 0.757004 |
SPLIT MNW COOLING COIL | 0.598823 | 11015.27 | 0.761853 |
SPLIT MSE COOLING COIL | 0.549780 | 10183.62 | 0.759563 |
SPLIT MNE COOLING COIL | 0.519148 | 9541.04 | 0.762152 |
SPLIT MN1 COOLING COIL | 0.361368 | 6846.63 | 0.752222 |
SPLIT MN2 COOLING COIL | 0.360303 | 6828.62 | 0.752120 |
SPLIT MS1 COOLING COIL | 0.385569 | 7753.24 | 0.733657 |
SPLIT MS2 COOLING COIL | 0.386430 | 7768.52 | 0.733736 |
SPLIT TSW COOLING COIL | 0.416878 | 7749.77 | 0.758380 |
SPLIT TNW COOLING COIL | 0.404307 | 7430.85 | 0.762135 |
SPLIT TSE COOLING COIL | 0.381286 | 7206.01 | 0.753024 |
SPLIT TNE COOLING COIL | 0.351094 | 6671.19 | 0.751296 |
SPLIT TN1 COOLING COIL | 0.270516 | 5242.50 | 0.745041 |
SPLIT TN2 COOLING COIL | 0.270421 | 5240.83 | 0.745031 |
SPLIT TS1 COOLING COIL | 0.298836 | 5765.89 | 0.746427 |
SPLIT TS2 COOLING COIL | 0.299309 | 5774.29 | 0.746467 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SPLIT GSW FURNACE WITH DX COOLING | 0.256697 | 0.256697 | 0.256697 | 0.256697 | 1447.88 | 4908.30 | 1.00 |
SPLIT GNW FURNACE WITH DX COOLING | 0.253320 | 0.253320 | 0.253320 | 0.253320 | 1396.99 | 4706.32 | 1.00 |
SPLIT OFFICE FURNACE WITH DX COOLING | 0.560566 | 0.560566 | 0.560566 | 0.560566 | 2781.59 | 9279.36 | 1.00 |
SPLIT GNE FURNACE WITH DX COOLING | 0.215907 | 0.215907 | 0.215907 | 0.215907 | 1396.99 | 4003.88 | 1.00 |
SPLIT GN1 FURNACE WITH DX COOLING | 0.151250 | 0.151250 | 0.151250 | 0.151250 | 1396.99 | 2905.22 | 1.00 |
SPLIT GN2 FURNACE WITH DX COOLING | 0.150566 | 0.150566 | 0.150566 | 0.150566 | 1396.99 | 2893.68 | 1.00 |
SPLIT GS1 FURNACE WITH DX COOLING | 0.159626 | 0.159626 | 0.159626 | 0.159626 | 1396.99 | 3294.66 | 1.00 |
SPLIT GS2 FURNACE WITH DX COOLING | 0.162308 | 0.162308 | 0.162308 | 0.162308 | 1396.99 | 3342.35 | 1.00 |
SPLIT MSW FURNACE WITH DX COOLING | 0.608051 | 0.608051 | 0.608051 | 0.608051 | 2793.97 | 11351.41 | 1.00 |
SPLIT MNW FURNACE WITH DX COOLING | 0.598823 | 0.598823 | 0.598823 | 0.598823 | 2793.97 | 11015.27 | 1.00 |
SPLIT MSE FURNACE WITH DX COOLING | 0.549780 | 0.549780 | 0.549780 | 0.549780 | 2793.97 | 10183.62 | 1.00 |
SPLIT MNE FURNACE WITH DX COOLING | 0.519148 | 0.519148 | 0.519148 | 0.519148 | 2793.97 | 9541.04 | 1.00 |
SPLIT MN1 FURNACE WITH DX COOLING | 0.361368 | 0.361368 | 0.361368 | 0.361368 | 2793.97 | 6846.63 | 1.00 |
SPLIT MN2 FURNACE WITH DX COOLING | 0.360303 | 0.360303 | 0.360303 | 0.360303 | 2793.97 | 6828.62 | 1.00 |
SPLIT MS1 FURNACE WITH DX COOLING | 0.385569 | 0.385569 | 0.385569 | 0.385569 | 2793.97 | 7753.24 | 1.00 |
SPLIT MS2 FURNACE WITH DX COOLING | 0.386430 | 0.386430 | 0.386430 | 0.386430 | 2793.97 | 7768.52 | 1.00 |
SPLIT TSW FURNACE WITH DX COOLING | 0.416878 | 0.416878 | 0.416878 | 0.416878 | 2097.95 | 7749.77 | 1.00 |
SPLIT TNW FURNACE WITH DX COOLING | 0.404307 | 0.404307 | 0.404307 | 0.404307 | 2099.59 | 7430.85 | 1.00 |
SPLIT TSE FURNACE WITH DX COOLING | 0.381286 | 0.381286 | 0.381286 | 0.381286 | 2106.14 | 7206.01 | 1.00 |
SPLIT TNE FURNACE WITH DX COOLING | 0.351094 | 0.351094 | 0.351094 | 0.351094 | 2107.78 | 6671.19 | 1.00 |
SPLIT TN1 FURNACE WITH DX COOLING | 0.270516 | 0.270516 | 0.270516 | 0.270516 | 1586.83 | 5242.50 | 1.00 |
SPLIT TN2 FURNACE WITH DX COOLING | 0.270421 | 0.270421 | 0.270421 | 0.270421 | 1586.98 | 5240.83 | 1.00 |
SPLIT TS1 FURNACE WITH DX COOLING | 0.298836 | 0.298836 | 0.298836 | 0.298836 | 1584.84 | 5765.89 | 1.00 |
SPLIT TS2 FURNACE WITH DX COOLING | 0.299309 | 0.299309 | 0.299309 | 0.299309 | 1584.99 | 5774.29 | 1.00 |
Maximum Flow Rate [m3/s] | |
SPLIT GSW SUPPLY FAN | 0.256697 |
SPLIT GNW SUPPLY FAN | 0.253320 |
SPLIT OFFICE SUPPLY FAN | 0.560566 |
SPLIT GNE SUPPLY FAN | 0.215907 |
SPLIT GN1 SUPPLY FAN | 0.151250 |
SPLIT GN2 SUPPLY FAN | 0.150566 |
SPLIT GS1 SUPPLY FAN | 0.159626 |
SPLIT GS2 SUPPLY FAN | 0.162308 |
SPLIT MSW SUPPLY FAN | 0.608051 |
SPLIT MNW SUPPLY FAN | 0.598823 |
SPLIT MSE SUPPLY FAN | 0.549780 |
SPLIT MNE SUPPLY FAN | 0.519148 |
SPLIT MN1 SUPPLY FAN | 0.361368 |
SPLIT MN2 SUPPLY FAN | 0.360303 |
SPLIT MS1 SUPPLY FAN | 0.385569 |
SPLIT MS2 SUPPLY FAN | 0.386430 |
SPLIT TSW SUPPLY FAN | 0.416878 |
SPLIT TNW SUPPLY FAN | 0.404307 |
SPLIT TSE SUPPLY FAN | 0.381286 |
SPLIT TNE SUPPLY FAN | 0.351094 |
SPLIT TN1 SUPPLY FAN | 0.270516 |
SPLIT TN2 SUPPLY FAN | 0.270421 |
SPLIT TS1 SUPPLY FAN | 0.298836 |
SPLIT TS2 SUPPLY FAN | 0.299309 |
Nominal Capacity [W] | |
SPLIT GSW HEATING COIL | 1447.88 |
SPLIT GNW HEATING COIL | 1396.99 |
SPLIT OFFICE HEATING COIL | 2781.59 |
SPLIT GNE HEATING COIL | 1396.99 |
SPLIT GN1 HEATING COIL | 1396.99 |
SPLIT GN2 HEATING COIL | 1396.99 |
SPLIT GS1 HEATING COIL | 1396.99 |
SPLIT GS2 HEATING COIL | 1396.99 |
SPLIT MSW HEATING COIL | 2793.97 |
SPLIT MNW HEATING COIL | 2793.97 |
SPLIT MSE HEATING COIL | 2793.97 |
SPLIT MNE HEATING COIL | 2793.97 |
SPLIT MN1 HEATING COIL | 2793.97 |
SPLIT MN2 HEATING COIL | 2793.97 |
SPLIT MS1 HEATING COIL | 2793.97 |
SPLIT MS2 HEATING COIL | 2793.97 |
SPLIT TSW HEATING COIL | 2097.95 |
SPLIT TNW HEATING COIL | 2099.59 |
SPLIT TSE HEATING COIL | 2106.14 |
SPLIT TNE HEATING COIL | 2107.78 |
SPLIT TN1 HEATING COIL | 1586.83 |
SPLIT TN2 HEATING COIL | 1586.98 |
SPLIT TS1 HEATING COIL | 1584.84 |
SPLIT TS2 HEATING COIL | 1584.99 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
G SWALL SWA | GWINDOW1 S SWA | |
G WWALL SWA | GWINDOW1 W SWA | |
G NWALL NWA | GWINDOW1 N NWA | |
G WWALL NWA | GWINDOW1 W NWA | |
G SWALL SEA | GWINDOW1 S SEA | |
G EWALL SEA | GWINDOW1 E SEA | |
G NWALL NEA | GWINDOW1 N NEA | |
G EWALL NEA | GWINDOW1 E NEA | |
G NWALL N1A | GWINDOW1 N N1A | |
G NWALL N2A | GWINDOW1 N N2A | |
G SWALL S1A | GWINDOW1 S S1A | |
G SWALL S2A | GWINDOW1 S S2A | |
M WWALL SWA | MWINDOW1 W SWA | |
M SWALL SWA | MWINDOW1 S SWA | |
M NWALL NWA | MWINDOW1 N NWA | |
M WWALL NWA | MWINDOW1 W NWA | |
M EWALL SEA | MWINDOW1 E SEA | |
M SWALL SEA | MWINDOW1 S SEA | |
M NWALL NEA | MWINDOW1 N NEA | |
M EWALL NEA | MWINDOW1 E NEA | |
M NWALL N1A | MWINDOW1 N N1A | |
M NWALL N2A | MWINDOW1 N N2A | |
M SWALL S1A | MWINDOW1 S S1A | |
M SWALL S2A | MWINDOW1 S S2A | |
T WWALL SWA | TWINDOW1 W SWA | |
T SWALL SWA | TWINDOW1 S SWA | |
T NWALL NWA | TWINDOW1 N NWA | |
T WWALL NWA | TWINDOW1 W NWA | |
T EWALL SEA | TWINDOW1 E SEA | |
T SWALL SEA | TWINDOW1 S SEA | |
T NWALL NEA | TWINDOW1 N NEA | |
T EWALL NEA | TWINDOW1 E NEA | |
T NWALL N1A | TWINDOW1 N N1A | |
T NWALL N2A | TWINDOW1 N N2A | |
T SWALL S1A | TWINDOW1 S S1A | |
T SWALL S2A | TWINDOW1 S S2A | |
T EWALL C | TWINDOW14 | |
G EWALL C | ENTRANCE DOOR | |
M EWALL C | MWINDOW14 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2015-09-09 18:48:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: MONTHLY INDOOR TEMP
For: G SW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 13.01 |
February | 23.34 | 15.66 |
March | 23.67 | 17.34 |
April | 24.09 | 23.65 |
May | 24.35 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.33 | 24.81 |
November | 23.97 | 17.95 |
December | 22.96 | 11.71 |
Annual Sum or Average | 23.95 | 23.80 |
Minimum of Months | 22.96 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G NW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.40 | 13.01 |
February | 22.91 | 15.66 |
March | 23.42 | 17.34 |
April | 24.03 | 23.65 |
May | 24.35 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.28 | 24.81 |
November | 23.61 | 17.95 |
December | 22.25 | 11.71 |
Annual Sum or Average | 23.74 | 23.80 |
Minimum of Months | 22.25 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: OFFICE
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 13.01 |
February | 24.49 | 15.66 |
March | 25.03 | 17.34 |
April | 26.04 | 23.65 |
May | 26.59 | 27.29 |
June | 27.64 | 33.99 |
July | 27.76 | 35.56 |
August | 27.58 | 33.82 |
September | 27.73 | 30.39 |
October | 26.48 | 24.81 |
November | 25.24 | 17.95 |
December | 23.80 | 11.71 |
Annual Sum or Average | 26.03 | 23.80 |
Minimum of Months | 23.80 | 11.71 |
Maximum of Months | 27.76 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G NE APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | 13.01 |
February | 22.87 | 15.66 |
March | 23.41 | 17.34 |
April | 24.04 | 23.65 |
May | 24.35 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.29 | 24.81 |
November | 23.62 | 17.95 |
December | 22.13 | 11.71 |
Annual Sum or Average | 23.72 | 23.80 |
Minimum of Months | 22.13 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G N1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 13.01 |
February | 22.72 | 15.66 |
March | 23.23 | 17.34 |
April | 23.95 | 23.65 |
May | 24.32 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.26 | 24.81 |
November | 23.47 | 17.95 |
December | 22.06 | 11.71 |
Annual Sum or Average | 23.65 | 23.80 |
Minimum of Months | 22.06 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G N2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 13.01 |
February | 22.71 | 15.66 |
March | 23.23 | 17.34 |
April | 23.95 | 23.65 |
May | 24.32 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.26 | 24.81 |
November | 23.47 | 17.95 |
December | 22.06 | 11.71 |
Annual Sum or Average | 23.65 | 23.80 |
Minimum of Months | 22.06 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G S1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 13.01 |
February | 23.34 | 15.66 |
March | 23.62 | 17.34 |
April | 24.07 | 23.65 |
May | 24.33 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.33 | 24.81 |
November | 23.99 | 17.95 |
December | 23.01 | 11.71 |
Annual Sum or Average | 23.95 | 23.80 |
Minimum of Months | 23.01 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G S2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.12 | 13.01 |
February | 23.37 | 15.66 |
March | 23.66 | 17.34 |
April | 24.09 | 23.65 |
May | 24.34 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.34 | 24.81 |
November | 24.01 | 17.95 |
December | 23.04 | 11.71 |
Annual Sum or Average | 23.97 | 23.80 |
Minimum of Months | 23.04 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M SW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.19 | 13.01 |
February | 24.15 | 15.66 |
March | 24.24 | 17.34 |
April | 24.36 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.39 | 17.95 |
December | 24.06 | 11.71 |
Annual Sum or Average | 24.32 | 23.80 |
Minimum of Months | 24.06 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M NW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.83 | 13.01 |
February | 23.89 | 15.66 |
March | 24.19 | 17.34 |
April | 24.35 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.36 | 17.95 |
December | 23.47 | 11.71 |
Annual Sum or Average | 24.21 | 23.80 |
Minimum of Months | 23.47 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M SE APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.16 | 13.01 |
February | 24.14 | 15.66 |
March | 24.23 | 17.34 |
April | 24.36 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.39 | 17.95 |
December | 24.02 | 11.71 |
Annual Sum or Average | 24.31 | 23.80 |
Minimum of Months | 24.02 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M NE APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 13.01 |
February | 23.85 | 15.66 |
March | 24.16 | 17.34 |
April | 24.35 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.39 | 24.81 |
November | 24.35 | 17.95 |
December | 23.36 | 11.71 |
Annual Sum or Average | 24.18 | 23.80 |
Minimum of Months | 23.36 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M N1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 13.01 |
February | 23.97 | 15.66 |
March | 24.23 | 17.34 |
April | 24.37 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.38 | 17.95 |
December | 23.62 | 11.71 |
Annual Sum or Average | 24.24 | 23.80 |
Minimum of Months | 23.62 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M N2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | 13.01 |
February | 23.96 | 15.66 |
March | 24.23 | 17.34 |
April | 24.37 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.38 | 17.95 |
December | 23.61 | 11.71 |
Annual Sum or Average | 24.24 | 23.80 |
Minimum of Months | 23.61 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M S1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.30 | 13.01 |
February | 24.27 | 15.66 |
March | 24.30 | 17.34 |
April | 24.38 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.40 | 17.95 |
December | 24.23 | 11.71 |
Annual Sum or Average | 24.36 | 23.80 |
Minimum of Months | 24.23 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M S2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.30 | 13.01 |
February | 24.27 | 15.66 |
March | 24.30 | 17.34 |
April | 24.38 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.40 | 24.81 |
November | 24.40 | 17.95 |
December | 24.23 | 11.71 |
Annual Sum or Average | 24.36 | 23.80 |
Minimum of Months | 24.23 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T SW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | 13.01 |
February | 23.77 | 15.66 |
March | 24.05 | 17.34 |
April | 24.26 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.37 | 24.81 |
November | 24.22 | 17.95 |
December | 23.36 | 11.71 |
Annual Sum or Average | 24.13 | 23.80 |
Minimum of Months | 23.36 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T NW APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 13.01 |
February | 23.54 | 15.66 |
March | 23.96 | 17.34 |
April | 24.23 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.34 | 24.81 |
November | 24.06 | 17.95 |
December | 22.87 | 11.71 |
Annual Sum or Average | 24.01 | 23.80 |
Minimum of Months | 22.87 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T SE APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.50 | 13.01 |
February | 23.76 | 15.66 |
March | 24.03 | 17.34 |
April | 24.27 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.37 | 24.81 |
November | 24.20 | 17.95 |
December | 23.35 | 11.71 |
Annual Sum or Average | 24.12 | 23.80 |
Minimum of Months | 23.35 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T NE APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 13.01 |
February | 23.51 | 15.66 |
March | 23.95 | 17.34 |
April | 24.24 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.35 | 24.81 |
November | 24.07 | 17.95 |
December | 22.78 | 11.71 |
Annual Sum or Average | 23.99 | 23.80 |
Minimum of Months | 22.78 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T N1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 13.01 |
February | 23.56 | 15.66 |
March | 23.99 | 17.34 |
April | 24.26 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.35 | 24.81 |
November | 24.10 | 17.95 |
December | 22.84 | 11.71 |
Annual Sum or Average | 24.01 | 23.80 |
Minimum of Months | 22.84 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T N2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 13.01 |
February | 23.56 | 15.66 |
March | 23.99 | 17.34 |
April | 24.26 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.35 | 24.81 |
November | 24.10 | 17.95 |
December | 22.84 | 11.71 |
Annual Sum or Average | 24.01 | 23.80 |
Minimum of Months | 22.84 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T S1 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 13.01 |
February | 23.87 | 15.66 |
March | 24.10 | 17.34 |
April | 24.29 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.38 | 24.81 |
November | 24.27 | 17.95 |
December | 23.50 | 11.71 |
Annual Sum or Average | 24.17 | 23.80 |
Minimum of Months | 23.50 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T S2 APARTMENT
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 13.01 |
February | 23.87 | 15.66 |
March | 24.10 | 17.34 |
April | 24.29 | 23.65 |
May | 24.40 | 27.29 |
June | 24.40 | 33.99 |
July | 24.40 | 35.56 |
August | 24.40 | 33.82 |
September | 24.40 | 30.39 |
October | 24.38 | 24.81 |
November | 24.27 | 17.95 |
December | 23.50 | 11.71 |
Annual Sum or Average | 24.17 | 23.80 |
Minimum of Months | 23.50 | 11.71 |
Maximum of Months | 24.40 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: T CORRIDOR
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.09 | 13.01 |
February | 24.84 | 15.66 |
March | 25.45 | 17.34 |
April | 26.36 | 23.65 |
May | 26.98 | 27.29 |
June | 27.73 | 33.99 |
July | 27.98 | 35.56 |
August | 27.73 | 33.82 |
September | 27.32 | 30.39 |
October | 26.59 | 24.81 |
November | 25.55 | 17.95 |
December | 23.83 | 11.71 |
Annual Sum or Average | 26.21 | 23.80 |
Minimum of Months | 23.83 | 11.71 |
Maximum of Months | 27.98 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: G CORRIDOR
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 13.01 |
February | 22.81 | 15.66 |
March | 23.47 | 17.34 |
April | 25.08 | 23.65 |
May | 26.04 | 27.29 |
June | 28.17 | 33.99 |
July | 28.61 | 35.56 |
August | 28.29 | 33.82 |
September | 27.72 | 30.39 |
October | 25.74 | 24.81 |
November | 23.89 | 17.95 |
December | 21.80 | 11.71 |
Annual Sum or Average | 25.32 | 23.80 |
Minimum of Months | 21.80 | 11.71 |
Maximum of Months | 28.61 | 35.56 |
Report: MONTHLY INDOOR TEMP
For: M CORRIDOR
Timestamp: 2015-09-09 18:48:13
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.86 | 13.01 |
February | 25.96 | 15.66 |
March | 26.28 | 17.34 |
April | 26.69 | 23.65 |
May | 26.92 | 27.29 |
June | 27.25 | 33.99 |
July | 27.33 | 35.56 |
August | 27.23 | 33.82 |
September | 27.09 | 30.39 |
October | 26.82 | 24.81 |
November | 26.47 | 17.95 |
December | 25.57 | 11.71 |
Annual Sum or Average | 26.63 | 23.80 |
Minimum of Months | 25.57 | 11.71 |
Maximum of Months | 27.33 | 35.56 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:13
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [Invalid/Undefined] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY {AT MAX/MIN} [W] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.120900E+12 | 75295.755 | 01-JAN-18:45 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 3013.678 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28399.239 | 0.000 | 0.000 | 0.000 |
February | 0.112913E+12 | 79813.784 | 27-FEB-18:30 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 14043.702 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21887.244 | 0.000 | 0.000 | 0.000 |
March | 0.125714E+12 | 77496.207 | 18-MAR-17:15 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 15932.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20233.942 | 0.000 | 0.000 | 0.000 |
April | 0.130817E+12 | 79796.111 | 26-APR-16:30 | 4276.255 | 26730.986 | 9718.964 | 0.000 | 24784.694 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14285.211 | 0.000 | 0.000 | 0.000 |
May | 0.140762E+12 | 85899.165 | 15-MAY-16:00 | 4276.255 | 26730.986 | 9718.964 | 0.000 | 28530.378 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16642.581 | 0.000 | 0.000 | 0.000 |
June | 0.153116E+12 | 91085.279 | 26-JUN-17:30 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 32722.468 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17032.972 | 0.000 | 0.000 | 0.000 |
July | 0.166786E+12 | 93685.977 | 16-JUL-17:45 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 36416.679 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15939.460 | 0.000 | 0.000 | 0.000 |
August | 0.161384E+12 | 93773.473 | 07-AUG-17:15 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 33445.013 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18998.622 | 0.000 | 0.000 | 0.000 |
September | 0.146352E+12 | 89332.379 | 11-SEP-16:45 | 4276.255 | 26730.986 | 9718.964 | 0.000 | 29303.337 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19302.836 | 0.000 | 0.000 | 0.000 |
October | 0.138634E+12 | 86440.896 | 14-OCT-16:30 | 4276.255 | 26630.920 | 9718.964 | 0.000 | 25611.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20203.479 | 0.000 | 0.000 | 0.000 |
November | 0.122026E+12 | 71567.160 | 18-NOV-18:30 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 8411.735 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19272.587 | 0.000 | 0.000 | 0.000 |
December | 0.119119E+12 | 69998.951 | 21-DEC-18:15 | 4979.953 | 26630.920 | 9718.964 | 0.000 | 2414.620 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 23701.494 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.163852E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.112913E+12 | 69998.951 | 4276.255 | 26630.920 | 9718.964 | 0.000 | 2414.620 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14285.211 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.166786E+12 | 93773.473 | 4979.953 | 26730.986 | 9718.964 | 0.000 | 36416.679 | 2553.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28399.239 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-09 18:48:13
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS [Invalid/Undefined] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT [Invalid/Undefined] | WATERSYSTEMS:GAS [Invalid/Undefined] | WATER HEATER:WATERSYSTEMS:GAS [Invalid/Undefined] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.324114E+10 | 17928.371 | 31-JAN-07:15 | 17928.371 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17928.371 |
February | 0.259538E+10 | 22335.714 | 10-FEB-06:00 | 22335.714 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22335.714 |
March | 0.139082E+10 | 21269.975 | 07-MAR-02:00 | 21269.975 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21269.975 |
April | 0.289841E+09 | 11016.630 | 03-APR-05:00 | 11016.630 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 11016.630 |
May | 0.000 | 0.000 | 01-MAY-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.000 | 0.000 | 01-JUN-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.000 | 0.000 | 01-JUL-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 01-AUG-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 01-SEP-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 01-OCT-00:15 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.104730E+08 | 738.740 | 25-NOV-06:00 | 738.740 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 738.740 |
December | 0.486053E+10 | 17650.926 | 16-DEC-03:00 | 17650.926 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17650.926 |
Annual Sum or Average | 0.123882E+11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | ||||
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.486053E+10 | 22335.714 | 22335.714 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22335.714 |